Telular 09000 Cellular Alarm Transmission System User Manual T100

Telular Corporation Cellular Alarm Transmission System T100

Contents

T100 User Manual

Download: Telular 09000 Cellular Alarm Transmission System User Manual T100
Mirror Download [FCC.gov]Telular 09000 Cellular Alarm Transmission System User Manual T100
Document ID131627
Application IDX9QgWXTFZRWdvOvyaEuumA==
Document DescriptionT100 User Manual
Short Term ConfidentialNo
Permanent ConfidentialNo
SupercedeNo
Document TypeUser Manual
Display FormatMicrosoft Word - pdf
Filesize50.83kB (635393 bits)
Date Submitted2001-01-05 00:00:00
Date Available2001-01-05 00:00:00
Creation Date2001-01-08 11:32:45
Producing SoftwareAcrobat Distiller 4.0 for Windows
Document Lastmod2001-01-08 11:32:52
Document TitleT100 User Manual

TELGUARD®
Cellular Alarm Transmission System
Using Microburst™ Control Channel Technology
MODEL T100C001
UL
INSTALLATION AND OPERATING INSTRUCTIONS
COMPANY CONFIDENTIAL
For use by TELGUARD® customers only.
Distribution to others strictly prohibited.
T E L U L A R®
CO RPO RATION
Corporate Headquarters
647 North Lakeview Parkway
Vernon Hills, Illinois 60061
847-247-9400 Fax: 847-247-0021
December 21, 2000
®
TELGUARD is a registered trademark of Telular Corporation. Products are protected
under one or more of the following U.S. patents:
4,658,096
4,737,975
4,775,997
4,868,519
4,922,517
© 2000 Telular Corporation
56019201
© 2000 Telular Corporation
FOREWORD
Many customers purchase the Telguard because they prefer its price and features, but do not intend to use it in an
application that requires UL Grade A Burglary or Fire Listings. If such UL Listings are not required, it is possible to
use model T100C001 that is UL Listed for Supplemental Use only. This means that the T100C001 will not enhance
the grade of service. Also, the T100C001 is not to be used as a main or secondary line for a fire or burglar alarm
system.
NOTICES
ABOUT THIS M ANUAL
This manual assumes that you have basic security system installation skills such as measuring
voltages, stripping wire, properly connecting wires together, connecting wires to terminals, and
checking phone lines. It also assumes that you have a familiarity with the proper installation and
programming tasks related to various Control/Communicator panels.
The material and instructions covered in this manual have been carefully checked for accuracy and
are presumed to be reliable. However, Telular assumes no responsibility for inaccuracies and
reserves the right to modify and revise this manual without notice.
It is our goal at Telular to always supply accurate and reliable documentation. If a discrepancy is
found in this documentation, please mail or fax a photocopy of the corrected material to:
Telular Security Products
Technical Services Department
420 Thornton Road, Suite 109
Lithia Springs, GA 30122
Fax: 678-945-1651
© 2000 Telular Corporation. Lithia Springs, GA U.S.A. All rights reserved.
FCC Notices
EXPOSURE TO RADIO FREQUENCY ENERGY
In 1991, the Institute of Electrical and Electronics Engineers (IEEE), and in 1992, the American National
Standards Institute (ANSI), updated the 1982 ANSI Standard for safety levels with respect to human exposure
to RF energy. Over 120 scientists, engineers and physicians from universities, government health agencies
and industry, after reviewing the available body of research, developed this updated Standard. In March,
1993, the U.S. Federal Communications Commission (FCC) proposed the adoption of this updated Standard.
The design of your Telular Telguard DataBurst complies with this updated Standard. Of course, if you
want to limit RF exposure even further than the updated ANSI Standard, you may choose to install the unit in
a manner that locates its antenna at an even greater distance from the general public than is recommended as a
minimum by the standard.
To insure compliance with the standard, when selecting a mounting location for your Telguard DataBurst do
not mount it (or its associated antenna) in an area where the general public could reasonably be within 8
inches (20 centimeters) of the antenna.
56019201
Page i
© 2000 Telular Corporation
EFFICIENT OPERATION
Do not operate your Telular product when holding the antenna. Be sure to mount the unit such that its antenna is a minimum of
eight (8) inches (20 centimeters) is maintained from the general public.
For the best service quality, keep the antenna free from obstructions and point the antenna straight up.
ANTENNA CARE AND REPLACEMENT
Do not use the unit with a damaged antenna. If a damaged antenna comes into contact with the skin, a minor
burn may result. Have your antenna replaced by a qualified technician immediately. Use only a manufacturerapproved antenna. Non-approved antennas, modifications, or attachments could impair service quality,
damage the Telguard and violate FCC regulations.
ELECTRONIC DEVICES
Most modern electronic equipment is shielded from RF energy. However, RF energy from cellular devices
may affect inadequately shielded electronic equipment.
RF energy may affect improperly installed or inadequately shielded electronic equipment operating in homes
and businesses. Check with the manufacturer or its representative to determine if these systems are
adequately shielded from external RF energy.
Consult the manufacturer of any personal medical devices (such as pacemakers, hearing aids, etc.) to
determine if they are adequately shielded from external RF energy.
BLASTING AREAS
To avoid interfering with blasting operations, turn OFF your unit when in a “blasting area” or in areas
posted: “Turn off two-way radio.” Construction crews often use remote control RF devices to set off
explosives.
POTENTIALLY EXPLOSIVE ATMOSPHERES
Turn OFF your unit when in any area with a potentially explosive atmosphere. It is rare, but your Telguard
DataBurst or its accessories could generate sparks. Sparks in such areas could cause an explosion or fire
resulting in bodily injury or even death.
Areas with a potentially explosive atmosphere are often, but not always, clearly marked. They include
fueling areas such as gas stations; below deck on boats; fuel or chemical transfer or storage facilities; areas
where the air contains chemicals or particles, such as grain, dust, or metal powders; and any other area
where you would normally be advised to turn off your vehicle engine.
Do not transport or store flammable gas, liquid or explosives in the area of your Telguard DataBurst or
accessories.
Vehicles using liquefied petroleum gas (such as propane or butane) must comply with the National Fire
Protection Standard (FPA-58). For a copy of this standard, contact the National Fire Protection Association,
One Batterymarch Park, Quincy, MA 02269, Attn: Publications Sales Division.
--------------------------------------------------------------------------------
FCC PART 15 CLASS B COMPLIANCE
This equipment has been tested and found to comply with the limits for a Class B digital computing device, pursuant to Part
15 of the FCC rules. These limits are designed to provide reasonable protection against harmful interference in a residential
installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in
accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee
that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or
television reception, which can be determined by turning the equipment OFF and ON, the user is encouraged to try to correct
the interference by one or more of the following measures:
•
•
56019201
Reorient or relocate the radio/television antenna.
Increase the separation between the radio/television equipment and the Telguard terminal.
Page ii
© 2000 Telular Corporation
•
Connect the radio/television equipment to an outlet on a branch circuit different from that to which the
Telguard terminal is connected.
Consult your Authorized Telular Dealer or an experienced radio/TV technician for additional suggestions.
•
The user or installer may find the following booklet prepared by the Federal Communications Commission
helpful, “Interference Handbook”. The booklet is available from the U.S. Government Printing Office,
Washington, DC 20402.
The user shall not make any changes or modifications to the equipment unless authorized by the Installation and Operating
Instructions. Unauthorized changes or modifications could void the user’s authority to operate the equipment.
PART 68
This equipment complies with Part 68 of the FCC Rules. Located behind the back-up battery of the Telguard model
T100C001 is a label that contains, among other information, the FCC Registration Number and Ringer Equivalence Number
(REN) for this equipment. If requested, this information must be provided to the Telephone Company.
The Telguard Cellular Alarm Transmission System is registered for connection to the public telephone
network using an RJ38X or RJ31X jack.
The ringer equivalence number (REN) is used to determine the quantity of devices which may be connected
to the telephone line. Excessive REN's on the telephone line may result in the devices not ringing in response
to an incoming call. In most, but not all areas, the sum of the REN's should not exceed five (5.0). To be
certain of the number of devices that may be connected to the line, as determined by the total number of
REN's, contact the telephone company to determine the maximum of REN for the calling area.
If the Telguard Cellular Alarm Transmission System caused harm to the telephone network, the Telephone
Company will notify you in advance that temporary discontinuance of the service may be required. But if
advance notice is not practical, the Telephone Company will notify the customer as soon as possible. Also,
you will be advised of your rights to file a complaint with the FCC if you believe it is necessary.
The telephone company may make changes in it's facilities, equipment, operation, or procedures that could
affect the operation of the equipment. If this happens, the Telephone Company will provide advance notice in
order for you to make the necessary modifications in order to maintain uninterrupted service. If trouble is
experienced with the Telguard Cellular Alarm Transmission System please contact Telular Technical
Service in the U.S.A. for repair and (or) warranty information.
Telular Security Products
TECHNICAL SERVICES DEPARTMENT
420 Thornton Road, Suite 109
Lithia Springs, GA 30122
Phone: (800) 229-2326
If the trouble is causing harm to the telephone network, the Telephone Company may request that you remove the equipment
from the network until the problem is resolved.
The customer (user) should not attempt any repair to the Telguard Cellular Alarm Transmission System.
Repair of this equipment should be referred to only qualified technical personnel.
Note that this equipment cannot be used on the public coin service provided by the Telephone Company.
Connection to Party Line Service is subject to state tariffs. (Contact the state public utility commission or
corporation commission for information).
56019201
Page iii
© 2000 Telular Corporation
FUTURE TESTING AND LIMITATIONS ON USE
Telguard is part of an advanced design alarm-communication system. It does not offer guaranteed protection against
burglary and fire. Any alarm communication system is subject to compromise or failure.
The Telguard will not work without power. Devices powered by AC will not work if the AC power supply is off
for any reason, however briefly, and at the same time, the backup battery is missing, dead or not properly installed.
The cellular radio network, needed to transmit alarm signals from a protected premises to a central monitoring station,
may be inoperable or temporarily out of service. Cellular radio networks are also subject to compromise by
sophisticated methods of attack.
This equipment, like any other electrical device is subject to component failure. Although this equipment is designed
to be long lasting, the electrical components could fail at any time.
Due to these limitations, we recommend that if the automatic self-test feature is not enabled, other arrangements be
made with the user to test the system at least once every three months. Moreover, arrangements should also be made
for on site inspection/test by a licensed alarm installer at least once each year.
56019201
Page iv
© 2000 Telular Corporation
TABLE OF CONTENTS
FOREWORD..................................................................................................................................................................I
NOTICES........................................................................................................................................................................I
ABOUT THIS MANUAL ................................................................................................................................................... I
FCC NOTICES...............................................................................................................................................................I
EXPOSURE TO RADIO FREQUENCY ENERGY................................................................................................................... I
EFFICIENT OPERATION ................................................................................................................................................. II
ANTENNA CARE AND REPLACEMENT............................................................................................................................ II
ELECTRONIC DEVICES .................................................................................................................................................. II
BLASTING AREAS ......................................................................................................................................................... II
POTENTIALLY EXPLOSIVE ATMOSPHERES ..................................................................................................................... II
FCC PART 15 CLASS B COMPLIANCE .......................................................................................................................... II
PART 68 ...................................................................................................................................................................... III
TECHNICAL SERVICES DEPARTMENT ........................................................................................................................... III
FUTURE TESTING AND LIMITATIONS ON USE ...............................................................................................IV
1.0
GENERAL DESCRIPTION AND OPERATION...........................................................................................1
2.0
FEATURES........................................................................................................................................................1
2.1
OPERATING MODE............................................................................................................................................1
2.2
C/C COMPATIBLE COMMUNICATION FORMATS................................................................................................2
2.3
COMPLETE SUPERVISION OF COMMUNICATION PATHS .....................................................................................2
2.3.1
Line Fault Condition (LFC) ...................................................................................................................2
2.3.2
Telco Communications Failure Condition (CFC) .................................................................................2
2.3.3
No Service Condition (NSC)...................................................................................................................2
2.3.4
Radio Communications Failure Condition (RFC) .................................................................................3
2.4
COMPLETE POWER SUPERVISION......................................................................................................................3
2.4.1
Low/Missing Battery Condition (LBC) ..................................................................................................3
2.4.2
AC Failure Condition (ACFC)................................................................................................................3
2.4.3
Watchdog Monitor/Reset (WR) ..............................................................................................................3
2.4.4
Catastrophic Failure (CF) .....................................................................................................................3
2.5
TELGUARD AUTOMATIC SELF-TEST REPORT .....................................................................................................4
2.5.1
Telguard Remote Query Capability .......................................................................................................4
2.6
TELGUARD TERMINAL STRIP CONNECTIONS.....................................................................................................4
2.6.1
Programmable Supervisory Trip Output (STC) Relay...........................................................................4
2.7
DIAGNOSTIC AND STATUS LEDS ......................................................................................................................5
2.7.1
LED Signal Strength Indication.............................................................................................................5
2.8
TELGUARD SETUP PROGRAMMING PARAMETERS ..............................................................................................5
2.9
UL LISTINGS BY MODEL...................................................................................................................................6
2.9.1
Model T100C001....................................................................................................................................6
2.9.2
Model T200C001....................................................................................................................................6
2.9.3
Model T300C001....................................................................................................................................6
3.0
3.1
4.0
REQUEST TELGUARD ACTIVATION FOR CELLULAR SERVICE FROM TELULAR .....................6
GETTING READY.........................................................................................................................................7
INSTALLATION SUMMARY.........................................................................................................................7
4.1
4.2
TRANSMIT C/C ALARMS OVER THE TELCO CONNECTION .................................................................................7
PROGRAM TELGUARD AND CONFIRM COMMUNICATIONS INTEGRITY ...............................................................7
4.3
TRANSMIT C/C ALARMS OVER THE CELLULAR RADIO NETWORK .....................................................................8
56019201
Page v
© 2000 Telular Corporation
4.4
CONNECT TELCO LINE AND SUPERVISORY TRIP OUTPUT..................................................................................8
4.5
COMPLETE THE INSTALLATION .........................................................................................................................8
5.0
INSTALLATION STEPS .................................................................................................................................8
STEP 1: TRANSMIT C/C ALARMS OVER THE TELCO CONNECTION ....................................................................9
5.1
STEP 2: PROGRAM TELGUARD AND CONFIRM COMMUNICATIONS INTEGRITY.................................................10
5.2
5.2.1
Locate Unit ...........................................................................................................................................10
5.2.2
Connect Backup Battery and AC Power Transformer .........................................................................11
5.2.3
Decide on a STC Trip Output Strategy ................................................................................................11
5.2.4
Default Programming...........................................................................................................................12
5.2.5
Complete the Telguard Programming Data Sheet...............................................................................12
5.2.7
Connect Antenna and Temporarily Place Unit ....................................................................................13
5.2.8
Measure Received Signal Strength (RSSI) for Best Antenna Placement.............................................14
5.2.9
Request Telguard Activation "PING" from Telular's IVR...................................................................15
5.3
STEP 3: TRANSMIT C/C ALARMS OVER THE CELLULAR RADIO NETWORK.......................................................17
5.3.1
Connect C/C to Telguard Jack 2...........................................................................................................17
5.3.2
Verify Alarm Signal Transmissions over Cellular...............................................................................18
5.4
STEP 4: CONNECT TELCO LINE AND SUPERVISORY TRIP OUTPUT ...................................................................19
5.4.1
Be sure the Telguard is the first device on incoming phone line ........................................................19
5.4.2
Connect RJ31X to Telguard Jack 1 and Check LFC............................................................................20
5.4.3
Connect STC Trip Output.....................................................................................................................20
5.4.4
Check Telguard Supervisory Trip to C/C ............................................................................................21
5.5
STEP 5: COMPLETE THE TELGUARD INSTALLATION .........................................................................................22
5.5.1
Check Settings ......................................................................................................................................22
5.5.2
Permanently Mount and Properly Ground the Telguard Chassis.......................................................22
A1.0
WIRING DIAGRAM ......................................................................................................................................23
A1.1
A1.2
A1.3
A1.4
A2.0
JACK AND PIN ASSIGNMENTS ....................................................................................................................24
TERMINAL STRIP PIN ASSIGNMENTS ..........................................................................................................25
LED MODES AND FUNCTIONS ...................................................................................................................26
JUMPERS ....................................................................................................................................................27
OPERATIONAL QUICK REFERENCE TABLE........................................................................................28
A2.1
A2.2
A2.3
A2.4
A2.5
SETUP PROGRAMMING PARAMETERS ..........................................................................................................29
TELGUARD COMMUNICATION FORMATS ....................................................................................................30
COMPATIBLE CONTROL COMMUNICATORS ................................................................................................30
COMPATIBLE RECEIVERS ............................................................................................................................30
ACTIVATION FORM (FAX to 678-945-1651) ......................................................................................31
A3.0
UL INSTALLATION REQUIREMENTS FOR SUPPLEMENTAL USE (MODEL T100C001). ............32
A4.0
DETAILED SPECIFICATIONS ....................................................................................................................33
A4.1
A4.2
A4.3
A4.4
A4.5
A5.0
DIALER TO INTERFACE ELECTRONICS .........................................................................................................33
POWER.......................................................................................................................................................33
MICROBURST RADIO ...............................................................................................................................33
PHYSICAL...................................................................................................................................................33
WARRANTY................................................................................................................................................33
PARTS LIST....................................................................................................................................................34
INDEX..........................................................................................................................................................................36
56019201
Page vi
© 2000 Telular Corporation
1.0
GENERAL DESCRIPTION AND OPERATION
The Telguard is a cellular radio alarm transmission device, which is used to provide a backup transmission path
(cellular) for control communicators (C/Cs) in case the primary transmission path (telco) is not available. When
transmitting over cellular, Telguard obtains its data from the C/C by way of a telco interface. The device transmits a
Link Request to the Telular operated Communication Center and when a link acknowledgement is received, the
Telguard handshakes with the C/C and causes the C/C to transmit the alarm data. Telguard encodes the alarm data into
digital packet data protocol and transmits on one of twenty-one available control channels used by the local AMPS
cellular network provider. The signal is routed from the network provider through the Aeris virtual network system to
the decoding (message) center. The Communication Center performs like a central station receiver and issues the
transmission kiss-off when the last message in the transmission is received. After decoding and reformatting, the
alarm signal is routed over telco to the appropriate alarm company central station for action.
Telguard is compatible with most control/communicators and no special equipment is needed at the premises or in the
alarm monitoring station. All Telguard programming is done with a standard touch-tone telephone or lineman’s buttset
and Telguard can be installed wherever cellular service is available. Different dialing patterns between telco and
cellular, cellular area code changes and PBX access numbers are not a problem for installers. Fraud and cloning
problems are eliminated since all transmissions occur over the cellular control channels in packet-type data format
and never over any voice channels.
In a typical alarm installation, Telguard is installed in the same area as the host alarm system. The incoming telco line
is connected from the RJ31X to Telguard and then to the host control/communicator's digital dialer in the normal
fashion. A programmable supervisory trip (STC) output is available for connection to the host control/communicator's
trip zone input terminals in order to provide a Telguard trouble signal to the C/C. Additionally, automatic self-test and
status-on-demand report signals are transmitted exclusively over the cellular network to the Communication Center.
All models are capable of transmitting an automatic self-test signal to the central station on a daily, weekly, or monthly
schedule. Telguard has its own internal power supply/battery charger. All telco line and cellular monitoring,
switching and supervisory functions are built in--no extra modules are required.
All Telguard models come with a special Microburst™ compatible 3-watt cellular transceiver (without handset),
antenna, interface with integrated control and power module, connecting cable, and plug-in transformer. The installer
to provide backup times that range from twenty-four to seventy-two hours must supply a rechargeable 12V battery,
7.0AH or 14.0AH. Type of enclosure and type of antenna included are the only differences among the three models
available. Economy model T100C001, UL Listed for Supplemental Use only, comes in a flame-retardant plastic
enclosure (9½in.x4½in.x1¾in.) with whip antenna. Model T200C001, UL Listed for residential and commercial fire,
as well as residential burglary, comes in a standard metal enclosure (12in.x12in.x3½in.) with keylock and magnetic
mount antenna with 12ft. of cable. Model T300C001, UL Listed for all residential burglary and fire, commercial
burglary and fire, and bank applications comes in an attack-resistant enclosure with keylock, tamper switch, and
magnetic mount antenna.
The Listed equipment at the Telular operated Communication Center (TCC) plays a key role in the operation of every
Telguard. All Telguard units are required to use the Communication Center because of the C/C alarm signal format
encoding and decoding requirements used in packet-data transmissions over the cellular network control channels.
The Communication Center also manages the real-time databases for cellular activation, airtime, billing, installation
site location, and a complete history of every Telguard's operating conditions. These conditions include programming
setup information, cellular alarm transmission information, supervisory trouble information, status-on-demand
information, and automatic self-test information. This information is made available to authorized personnel through
Telular's Interactive Voice Response System (IVR), Telular's computer access Communication Center Intranet System,
or though Telular's Customer Service Center.
2.0
FEATURES
This section summarizes the key features of the Telguard. Actual installation instructions begin in Section 5.0.
2.1 OPERATING M ODE
The Telguard is a cellular radio packet transmission device that is installed at the protected premises to
provide alarm transmission integrity for security systems. It is used to provide a backup transmission path
(cellular) for control communicators (C/Cs) in case the primary transmission path (telco) is not available. If
56019201
Page 1
© 2000 Telular Corporation
the telco line is cut or the C/C is unable to communicate with the central station receiver due to busy
telephone line circuits then Telguard transmits the alarm message over the cellular network.
2.2 C/C COMPATIBLE COMMUNICATION FORMATS
The Telguard reads the C/C’s alarm messages and converts the C/C’s digital data format into Microburst
packet data protocol for transmission over the cellular radio network. In order for the C/C to be compatible
with the Telguard, the C/C must be programmed to transmit alarm messages to the central station using one of
the following non-extended formats:
• 3+1 pulse; 10pps, Double Round, 1400Hz ack
• 3+1 pulse; 20pps, Double Round, 2300Hz ack
• 3+1 pulse; 40pps, Double Round, 2300Hz ack
• 4+2 pulse; 20pps, Double Round, 1400Hz ack
• 4+2 pulse; 20pps, Double Round, 2300Hz ack
• 4+2 pulse; 40pps, Double Round, 2300Hz ack
• Radionics Modem IIE or 3A2
• Ademco Contact ID
Hexadecimal account numbers (001-FFF or 0001-FFFF) can be used with 3+1 or 4+2 formats, but Contact
ID and Radionics modem IIE or 3A requires a four digit account number using digits 0-9 (0001-9999).
2.3 COMPLETE SUPERVISION OF COMMUNICATION PATHS
The Telguard continuously supervises both the primary (telco) and the secondary (cellular) communication
paths. If either path becomes inoperative, the Telguard generates a relay trip output that can be connected to
a zone input of the host control communicator and/or used to activate remote sounding devices.
2.3.1 Line Fault Condition (LFC)
The Telguard monitors voltage on the incoming telco line. If an inoperative telco line is identified,
a telco line fault condition (LFC) is declared and Telguard switches to the cellular path. Once the
telco line restores to normal, Telguard checks the radio link and switches back to the telco path after
any communications on the radio link are completed.
LFC is programmable to trip the supervisory relay output (STC) after a 30 or 60 second delay.
When the STC trips, the STC LED indicates 3 flashes at a time and the C/C zone trip message is
transmitted to the alarm company central station indicating system trouble. Upon telco restoral, the
STC relay and LFC LED are returned to normal and a STC restoral message is transmitted if the
C/C is programmed to transmit restorals.
2.3.1.1 PBX Installations
PBX’s and other proprietary phone systems sometimes operate at lower voltages than the
standard telco line. Telguard works equally well on PBX lines or telco lines.
Note: PBX connections are not allowed in any UL Listed installations.
2.3.2 Telco Communications Failure Condition (CFC)
Telco communications failure condition (CFC) is declared when the C/C fails to deliver the alarm
message to the central station receiver after a selected number (1-5) of attempts over an operative
telco line. Immediately upon CFC, Telguard switches to cellular mode and allows the C/C to
attempt five transmissions over the cellular network. If the call is not acknowledged after the fifth
attempt, Telguard switches the C/C back to telco and “disarms” the CFC detection. The CFC
detection is re-armed when the C/C has been on-hook continuously for ten-minutes.
2.3.3 No Service Condition (NSC)
Telguard declares a no service condition (NSC) when the measured “receive” cellular radio signal
strength at the protected premises drops to -114 dBm or less.
NSC is programmable to trip the supervisory relay output (STC) after a 30 or 60 second delay.
When the STC trips, the STC LED indicates 4 flashes at a time and the C/C zone trip message is
transmitted to the central station indicating system trouble. Restoral of this condition occurs when a
measurable signal strength greater than –114 dBm is maintained for the trip period of 30 or 60
seconds.
56019201
Page 2
© 2000 Telular Corporation
2.3.4 Radio Communications Failure Condition (RFC)
Radio communications failure condition (RFC) is declared when Telguard is unable to transmit
over the cellular network even with acceptable signal strength. Two conditions can cause an RFC
to occur, Link Request failure (RFC1) or Link Termination failure (RFC2).
2.3.4.1 RFC1 (Link Request Failure)
When a LFC or CFC has been declared and there is an alarm signal to communicate, the
Telguard attempts to transmit its message via radio. When the C/C goes off-hook, the
Telguard transmits a Link Request to the TCC and waits for a Link Request ACK. If the
Telguard does not receive an ACK for the transmission before the C/C hangs up, it will
retransmit the Link Request again when the C/C goes off-hook for a redial attempt. If the
Telguard does not receive an ACK after three attempts, then an RFC will be declared
which trips the STC relay, causes the STC LED to flash five times and switches the
Telguard to Telco. Restoral of RFC occurs when the communication cycle is completed.
2.3.4.2 RFC2 (Link Termination Failure)
After the Telguard receives a Link Request ACK from the TCC, the Telguard
communicates with the C/C to acquire the alarm message and transmits the message via
radio. If the Telguard does not receive a link termination ACK (where the TCC
acknowledges receiving the transmission) within 150 seconds, it will retry sending the
entire transmission. Upon failing two attempts, the Telguard switches to Telco and allows
the C/C to communicate directly with the Central Station. An RFC is declared causing the
STC relay to trip and the STC LED to flash five times. Restoral of RFC occurs when the
communication cycle is completed.
2.4 COMPLETE POWER SUPERVISION
Telguard monitors its backup battery as well as its AC power source and reports low or missing power
conditions from either. Telguard’s integrated control and power module, protected by a 3 amp 3AG fuse,
incorporates battery charger circuitry that is jumper selectable for high or low battery capacities. The high
battery capacity selection is used for 12V 7Ah, or 12V 14Ah batteries.
2.4.1 Low/Missing Battery Condition (LBC)
The Telguard checks the backup battery voltage on initial power-up and every minute thereafter.
Additionally, a battery voltage test is performed by the Telguard every 24-hours while operating on
AC power in order to measure the loaded battery voltage. Battery charging voltage is lowered to
10.0 volts and the Telguard is forced to operate entirely from the battery supply. If the battery
voltage is less than 11.6 volts, a LBC is declared whereby the STC LED blinks twice (½ sec ON, ½
sec OFF, ½ sec ON, ½ OFF every 5 seconds) and the STC relay trips. When the battery voltage
increases to 12.1 volts, the STC LED and STC relay restore.
2.4.2 AC Failure Condition (ACFC)
AC failure condition (ACFC) occurs when AC power is lost or less than 102 VAC for 6 continuous
hours. The AC Power LED goes out immediately, the STC LED blinks once and the STC trip output
is activated after 6 hours. When AC power returns too normal (≥106 VAC for 60 seconds), the AC
Power LED turns on immediately and the STC trip output restores after 60 seconds.
2.4.3 Watchdog Monitor/Reset (WR)
A watchdog monitor/reset (WR) circuit continuously monitors the Telguard’s internal operating
microprocessor functions.
2.4.4 Catastrophic Failure (CF)
Catastrophic Failure (CF) is any condition that causes the Telguard to stop functioning at all levels.
Most commonly because of AC power failure followed by a complete discharge of the backup
battery. The STC trip output is activated and visible indication is loss of all LED activity. Total
loss of power to Telguard does not prevent transmission of alarm messages from the host C/C
“through” the Telguard and out over an operative phone line in the normal fashion.
56019201
Page 3
© 2000 Telular Corporation
2.5 TELGUARD AUTOMATIC SELF-TEST REPORT
The Telguard automatic self-test signal is originated by the Communication Center on a daily, weekly, or
monthly schedule. When the time for an automatic self-test occurs, the Communication Center transmits a
radio signal to the Telguard and the Telguard responds with a self-test radio signal that is received by the
Communication Center and processed on to the central station, just as normal alarm signals are processed.
The central station receives the automatic self-test report in the same format that the C/C normally uses for
communication over the telco line. The central station provides the Telguard self-test code along with the
time and frequency of transmission when the Telguard is initially activated. However, an automatic self-test
report can be initiated later, after the Telguard is installed, as well as modifying the time or frequency of
reporting.
The Communication Center captures all current and historical data pertaining to the operation of the Telguard
when it processes the automatic self-test signal on to the central station. This data contains current
operational status (C.O.S.) of the Telguard such as "All OK", "AC fail condition", "low/missing battery
condition", "line fault condition", or any combination of these as well as the current signal strength and mode
of operation. In addition, the data also contains historical data for supervisory events that occurred since the
last self-test signal was transmitted. This data includes the number of occurrences of AC fail conditions, low
battery conditions, line fault conditions, communications failure conditions and no cellular service
conditions. This self-test data is available for review at any time by authorized personnel such as installers,
dealers, central station operators, or technical service personnel. Methods used to review this data include
Telular's Interactive Voice Response System (IVR), Telular's computer access Communication Center
Intranet System, or simply calling Telular Customer Service who can review the data using the "Back Office"
program.
2.5.1 Telguard Remote Query Capability
Although Telguard has the capability for a daily, weekly, or monthly automatic self-test, a separate
feature is provided for determining the current operational status of every Telguard. This feature is
called Remote Query and is used to provide real-time operational status for Telguard on-demand. It
is useful in resolving STC events that are reported by the C/C to the central station. Authorized
personnel can initiate the Remote Query at any time by accessing the IVR, Intranet, or calling
Customer Service. The Remote Query causes Telguard to upload current operational status data and
historical data, just as the automatic self-test described above, except that the query signal is
controlled by the one who initiates it. The query signal is held in the Telguard database at the
Communication Center for review and is not forwarded on to the central station.
2.6 TELGUARD TERMINAL STRIP CONNECTIONS
The conveniently located terminal strip provides wiring connections for the Telguard supervisory trip output
(STC-pins 1&2, N.O.), battery leads for connecting to a 12 volt 7.0Ah, or 14.0AH rechargeable battery
(BAT-pin 3 neg., pin 4 pos.), and AC power (16.5VAC 20VA, pins 6&7). The removable terminal strip can
accommodate solid or stranded wire sizes from 14 gauge to 30 gauge.
2.6.1 Programmable Supervisory Trip Output (STC) Relay
The Telguard has one supervisory relay trip output (STC), a single pole single throw (SPST, form
C) with contacts rated at 1.0A 30VDC, and is energized normally open (N.O.) in a powered up state
when no system troubles exist. It enables a supervisory trouble code (zone shorted) to be
transmitted to the central station when connected to a C/C’s 24-hour instant input zone. The STC
relay is programmable, using a standard touch-tone telephone or buttset, to meet virtually any
installation requirement.
The following supervisory features or combination of features are programmable to trip the STC
relay in order to meet a variety of installation requirements:
• Always Off.
• Trips on AC fail condition (ACFC)
• Trips on low or missing battery condition (LBC).
• Trips on line fault condition (LFC).
• Trips on no service condition (NSC).
• Trips on radio communication failure condition (RFC).
56019201
Page 4
© 2000 Telular Corporation
NOTE: For UL installations, all the above features must be enabled.
The following system trouble features are embedded in the Telguard for tripping the STC relay and
cannot be changed:
• Trips on catastrophic failure (CF) if all power is lost.
• Trips on transmit-disable command from the Communication Center. This
radio command disables only the Telguard transmitter and would be used, for
example, to shut down the Telguard due to a runaway dialer. The Telguard
receiver function stays active so that a transmit-enable command can be
received by radio to put the Telguard back into normal service.
2.7 DIAGNOSTIC AND STATUS LEDS
Four LEDs are provided as a useful aid during installation and give installers an immediate visual indication
of system status. These LEDs include an AC Power LED indicator that is green when AC power is normal
and off when AC power is low or missing. The red STC LED provides system trouble information for
low/missing AC power-ACFC (1 flash), low/missing battery-LBC (2 flashes), telco line fault-LFC (3
flashes), no cellular service-NSC (4 flashes), radio communication failure-RFC (5 flashes) and loss of dialtone voltage-DTF (6 flashes). An Operating Mode LED indicates solid yellow for normal operating mode
or slow flash for C/C off-hook when communicating over cellular. A short (1 second) solid green Radio TX
LED indicates it is in a Microburst communication cycle. Separately, these LED’s can be converted into a
bar graph during installation to indicate radio signal strength by using a single jumper (J5) to select normal
LED mode (off) or signal strength mode (on).
2.7.1 LED Signal Strength Indication
The Telguard provides the installer with an easy to use LED radio signal strength indicator (RSSI)
for positioning the unit or remote antenna to obtain the strongest RF signal possible. A signal
strength reading can be obtained at any time there is power applied to the Telguard without affecting
the operation of the unit. When the “RSSI” jumper J5 is “IN”, the Telguard displays the current
received signal strength within 5 seconds and should the jumper be inadvertently left “IN”; the
Telguard will revert to normal display operation after 10 minutes. The signal strength is read from
bottom to top using the four sequential LEDs located on the top right side of the printed circuit board
with the Radio TX LED = 1 and the AC POWER LED = 4.
RSSI Value
NO SVC
LED’s Lighted
RF dBm
LED 1* = on, LED 2-4 = off
≤ -116 dBm
LED 1 = on, LED 2-4 = off
≤ -111 dBm
LED 1 = on, LED 2 = slow flash
≥ -110 dBm
LED 3-4 = off
LED 1-2 = on, LED 3-4 = off
≥ -100 dBm
LED 1-2 = on, LED 3 = slow flash
≥ -90 dBm (Minimum signal
LED 4 = off
strength required)
LED 1-3 = on, LED 4 = off
≥ -80 dBm
LED 1-3 = on , LED 4 = slow flash
≥ -70 dBm
LED 1-4 = on
≥ -60 dBm
*Note: LED 1 = Radio TX; LED 2 = Mode; LED 3 = STC; LED 4 = AC Power.
2.8 TELGUARD SETUP PROGRAMMING PARAMETERS
The Telguard will not operate until the unit is activated from the Communication Center. There are no
radio NAM programming requirements since the radios have been preprogrammed at the factory. However,
certain Telguard operating parameters may need to be changed from the factory default programming by the
installer during installation in order to have the Communication Center process alarm signals to the central
station. These are setup parameters and are used to tell the Communication Center how to encode alarm
messages to the appropriate alarm monitoring station. Included in the setup parameters are the C/C reporting
format and cellular operating system A or B. Also included are the STC supervisory trip input settings, CFC
settings, NFC/LFC trip delay time, and standby battery size. If operating parameters are not uploaded to the
Communication Center, a "missing parameters (MP) condition" exists and the Telguard will not operate.
When an MP condition exists, the Telguard causes the STC LED to light and the STC (System Trouble) trip
output to occur.
56019201
© 2000 Telular Corporation
Page 5
If default programming is correct or operating parameters are re-programmed into the Telguard, the installer
calls the Telular IVR and follows the activation procedure to request an activation "ping". The
Communication Center responds with a radio acknowledgement to the Telguard clearing the STC condition
and allowing the Telguard to operate over the cellular radio network. The programmed parameters are
transmitted automatically to the TCC when the Telguard is activated. The installer must perform any changes
to the Telguard programming data since the Communication Center cannot download data to the unit.
2.9 UL LISTINGS BY M ODEL
There is a Telguard model designed to meet UL requirements for virtually any residential and commercial
burglary/fire installation. All models contain the same circuitry and perform the same functions. The
difference between models is simply the type of enclosure and type of antenna that is shipped with the unit.
2.9.1
Model T100C001
Economy model T100C001 is UL Listed for Supplemental Use only and is not to be used as a main
or secondary line for a fire or burglar alarm system. This means that the T100C001 will not
enhance nor detract from the grade of service of the UL Listed alarm system being used. Model
T100C001 has a compact plastic enclosure and whip antenna.
2.9.2 Model T200C001
Model T200C001 meets the requirements for Household Burglary, Household Fire, and Commercial
Fire installations. T200C001 has a standard metal enclosure, keylock, and magnetic mount antenna
with 12ft.cable. T200C001 is UL Listed for the following:
♦ UL Household Burglary
♦ UL Household Fire
♦ UL Household Burg/Fire Combination
♦ UL Commercial Fire
2.9.3 Model T300C001
Model T300C001 meets the requirements for all Household Burglary, Commercial Burglary,
Household Fire, and Commercial Fire installations. T300C001 has an attack-resistant enclosure,
keylock, tamper switch, and a magnetic mount antenna with 12ft.cable. Model T300C001 is UL
Listed for the following and UL Listed for Grade A Burglary Certificate installations:
♦ UL Household Burglary
♦ UL Household Fire
♦ UL Household Burg/Fire Combination
♦ UL Central Station Burglary
! Grade A
! Grade B
♦ UL Police Connect Burglary
! Grade A
♦ UL Commercial Fire
♦ UL Commercial Fire and Central Station Burglary Grade A
♦ UL Bank, Safe and Vault
! Grade A
3.0
Request Telguard Activation for Cellular Service from Telular
There are two ways that you may activate cellular service for a Telguard. Both methods require the activation
information to be completed and approved prior to installing the Telguard. The Telguard can only be activated when
all the necessary accounting information has been entered into the customer database located at the Telular
Communication Center. The database includes information about the customer account, unit location, and central
station information.
1.
FAX Cellular Service Activation Form: Complete the Cellular Service Activation Form that is shipped with
each Telguard and fax it to Telular Customer Service, 678-945-1651. Within 24-hours, you will be notified
of service activation.
56019201
Page 6
© 2000 Telular Corporation
2.
Computer access via Telular's Intranet: Dealers may access their Telguard customer database via
Telular's Intranet. The pertinent customer account information and serial number can be completed and
submitted on-line. After an approval acknowledgement is issued, usually within 10-minutes, the Telguard is
ready to install.
3.1 GETTING READY
Before attempting to connect Telguard to the host C/C, please note the following:
1. Be sure your unit has cellular service activated. (See Section 3.0)
2. Be sure you have all the proper parts before you go to the job site. The following items are shipped with
each Telguard unit:
Basic Telguard unit (Model T100C001 in plastic enclosure).
16.5 VAC, 20 VA UL Listed plug-in transformer (Revere, P/N: RT-1620SL).
Note: The 20 VA transformer is required for proper operation since the Telguard is
capable of transmitting at 3 watts of output power. Do not use the C/C power
transformer to provide AC power to the Telguard.
" Antenna: Whip antenna for T100C001.
" 3-foot modular plug-to-plug cord for connecting Telguard to RJ31X jack.
" Telguard Installation and Operating Instructions Manual, P/N: 56019201
" Account Activation and Programming form documenting the unit's electronic serial number, cellular
telephone number, etc.
NOTE: Backup batteries are not supplied with any models. You must source backup batteries
separately.
Telguard Model
T100C001
Approx. Standby
Time
24-Hours
72-Hours
12V. Battery
Capacity
7.0 Ah
14.0 Ah (2 ea. 7.0
Ah)
Manufacturer/model
Technacell EP 1270
Technacell EP 1270
3. You must also have certain installation test tools.
•
•
A standard telephone or lineman's buttset is required at the job site for use in programming the unit.
Optimal signal strength is determined by placing the unit where the most LEDs (up to four) are
lighted when using Telguard's on-board Signal Strength Indicator feature so that the unit can be
easily placed during installation where signal strength is greatest.
NOTE: Your unit may be subject to airtime charges for unintended use. Telular offers several cellular
service rate plans. Check the Activation and Programming form that was shipped with your unit
or call us to determine what rate plan each unit is operating under.
4.0
INSTALLATION SUMMARY
There are five steps in installing Telguard properly. IF YOU DO NOT PROCEED IN THE ORDER AND
MANNER PRESCRIBED, YOU MAY NOT COMPLETE THE INSTALLATION IN THE TIME
ALLOCATED. These five steps are summarized below and then explained in detail in the remainder of this manual.
4.1 TRANSMIT C/C ALARMS OVER THE TELCO CONNECTION
First, make sure you can transmit alarm signals from the C/C host to the central monitoring station over the
telco line without any connection to Telguard.
4.2 PROGRAM TELGUARD AND CONFIRM COMMUNICATIONS INTEGRITY
Next, you will be confirming that Telguard's programming parameters are correctly entered into the unit and cellular
service is activated. This is the most important step in the installation, since the programming parameters
contain all the necessary information for successful communications. Also, you will confirm that Telguard has
adequate cellular signal strength.
56019201
Page 7
© 2000 Telular Corporation
4.3 TRANSMIT C/C ALARMS OVER THE CELLULAR RADIO NETWORK
Next, you will be connecting the C/C's digital dialer output to Telguard and verifying that alarm signals can
be reliably sent through Telguard over cellular to the central station digital receiver. The incoming Telco
line is not connected to Telguard during this step.
4.4 CONNECT TELCO LINE AND SUPERVISORY TRIP OUTPUT
Once alarms are being successfully transmitted over cellular by the C/C, you will be ready to connect
Telguard to the incoming phone line at the RJ31X and check that it properly switches to and from cellular
upon telco restoral and telco line fault. Telguard's supervisory trip output (normally open) is connected to a
24-hour zone of the C/C and then tested.
When backing up the host C/C's phone line, Telguard must be the first device on the incoming phone
line in order to prevent Telguard from going into Telco Line Fault Condition when a phone device in
front of it goes off-hook. This is the step where this is checked.
4.5 COMPLETE THE INSTALLATION
Your last step will be to check the jumper setting of J5 (LED mode, out = normal), attach earth ground, and
permanently mount the unit.
* * * *
With this overview of the installation in mind, you should now proceed with the actual installation, following
the steps described in the remainder of this manual. Experienced installers following these steps can usually
install Telguard in new installations with good signal strength in a maximum of 30 minutes and in
retrofit/existing installations in a maximum of one hour. However, you must first get the host C/C working
correctly when transmitting over the incoming telco line.
If you come to a road block at any step during the installation of Telguard, call Telular Technical Support
Department immediately before going on to the next step, so that we can help you complete each step in the
proper order.
5.0
INSTALLATION STEPS
This five-step installation approach (5.1 through 5.5) provides the alarm installer with the easiest and fastest method
of properly installing Telguard. Please follow the instructions carefully and if you should need assistance or have any
questions, call for
Technical Support: 1-800-229-2326 / 678-945-7770 FAX: 678-945-1651
TELULAR IVR (Interactive Voice Response): 678-945-0228 (Local-Area: Atlanta, Ga.)
1-888-TELULAR (Toll-Free: 1-888-835-8527)
TELULAR INTRANET (Computer Dial-up Connection): 678-945-1993
56019201
Page 8
© 2000 Telular Corporation
5.1 STEP 1: TRANSMIT C/C ALARMS OVER THE TELCO CONNECTION
Be sure the C/C is powered up and programmed so that it will transmit a simple alarm signal over the telco
line through the RJ31X to the central station when not connected to the Telguard. In checking this, do not
connect the host C/C or incoming telco line to the Telguard.
INCOMING
TELCO
RJ31X
PREMISE
PHONES
MAKE SURE HOST C/C IS PROGRAMMED
AND WORKING THROUGH RJ31X
BEFORE INSTALLING TELGUARD.
TELCO DIALER
HOST C/C
24 HOUR ZONE INPUT
24 HOUR ZONE COMMON
TG2 Step 1.VSD
56019201
Page 9
© 2000 Telular Corporation
5.2 STEP 2: PROGRAM TELGUARD AND CONFIRM COMMUNICATIONS INTEGRITY
Confirm that Telguard's programming parameters are correctly entered into the unit, cellular service is activated, and
Telguard has adequate cellular signal-strength. This is the most important step in the installation, since the
programming parameters contain all the necessary information for successful communications and good signalstrength insures performance reliability.
INCOMING
TELCO
ANTENNA
RJ31X
S E E AP PE NDIC ES A1 .1 THRO UG H A1 .4 FO R
DE TAILS O N JACK AND P IN AS S IG NM E NT S,
TE RM INAL S TRI P, J UM PE R, AND S T AT US LE DS .
PREMISE
PHONES
S TATUS LE DS
(Se e Appe ndix A1. 3)
AC POW ER
SYSTEM T ROUBLE
OPERAT ION MODE
TELGUARD
TO P ROG RAM UNIT :
RADIO T X
USE BUT TSET CONNECT ED TO T AND R
TEST PINS OR USE T OUCHTONE
TELEPHONE PLUGGED DIRECT LY INT O J2.
SIGNAL
STRENGTH
LEDS
LED MODE SELECT
J5
OUT = NORMAL
IN = RSSI
TRA NSCEIVER
J2
J1
TELCO DIALER
+ BATTERY 12V
- BATTERY
STC (N.O.)
STC (COM)
BLANK PIN
AC (16.5V 40VA)
AC (16.5V 40VA)
HOST C/C
FUSE 3A 3AG
EARTH GROUND
2 4 H OUR ZONE I NPUT
2 4 H OUR ZONE C OM M ON
TG3 Step 02 .VS D
5.2.1 Locate Unit
Pick a spot next to the C/C where you think the Telguard will be mounted and place the unit down
temporarily in that spot. Do not mount it permanently now, since it may need to be moved to
receive a better cellular radio signal or a remote high-gain antenna may be necessary.
56019201
Page 10
© 2000 Telular Corporation
5.2.2 Connect Backup Battery and AC Power Transformer
To apply power on model T100C001, connect the battery by attaching battery leads to terminals 3 () and 4 (+) noting polarity and program Telguard memory location 67 (see section 5.2.5) for proper
battery capacity.
Connect the Telguard AC power transformer to terminals 6 and 7 marked "AC 16.5V 20VA" using
stranded copper insulated wire following wire gauge and length recommendations below:
Recommended Wire Size
18 ga
16 ga
14 ga
Length Not to Exceed
20 ft
40 ft
60 ft
5.2.3 Decide on a STC Trip Output Strategy
The Telguard provides the host C/C with one supervisory trip output for reporting a Telguard
system trouble code to the central station. The supervisory trip output (terminals 1 & 2, N.O.) is
programmable via a touch-tone telephone or buttset to suit various installation requirements. The
programming options for this supervisory trip output can be any combination of the following
(except Always off):
a. Always Off: Disables all relay supervisory functions with relay in N.C. condition.
b. ACFC: Trips 6-hours after loss of AC power. Restores 60 seconds after AC power is restored.
c. LBC: Trips within 60 seconds on low battery condition. Restores when battery voltage ≥ 12.1
vdc.
d. LFC: Trips 30/60-sec. on Telco line fault condition. Restores 30/60 seconds after Telco line
restores.
e. NSC: Trips 30/60-sec. on no service condition due to loss of RF signal strength. Restores
30/60 seconds after RF signal strength is available.
f. RFC: Trips on radio failure to communicate with the Telular Communication Center due to
either of the following:
1. Failing to receive a Link Request acknowledgement from the Communication Center
after 3 Link Request transmissions. A Link Request transmission is generated each
time the C/C goes off-hook to dial when the Telguard is in radio mode. The Link
Request acknowledgment from the Communication Center allows the Telguard to
begin accepting and transmitting alarm data from the C/C.
2. Failing to receive a Link Termination acknowledgement from the Communication
Center after 2 complete transmission retries. A Link Termination acknowledgement
is generated by the Communication Center only when all messages in an alarm
transmission have been received successfully.
56019201
Page 11
© 2000 Telular Corporation
5.2.4 Default Programming
The Telguard default setup is pre-programmed at the factory. Default setup values are listed in
Section 5.2.5 (Telguard Programming Data Sheet) and highlighted in "bold" type. Setup
parameters are stored in non-volatile memory and retain their settings when power is removed from
the unit. Review the default settings and record on the data sheet all changes that you make.
Typically, the only critical programming entries are:
Memory Location
Field
Cellular
System
or
32 *
Enter the 1-digit C/C Reporting Format
33 **
* Note: The Cellular carrier is factory defaulted to the "B" carrier. If the cellular carrier in your
area providing Microburst™ service is an "A" carrier, then memory location 32 must be
reprogrammed to 1. (Refer to the following Telguard Programming Data Sheet, location 32).
**Note: The C/C Reporting Format is already factory defaulted to Ademco Contact ID. Refer to
Telguard Programming Data Sheet, location 33.
5.2.5 Complete the Telguard Programming Data Sheet
Fill out the following Telguard Programming Data Sheet. The completed data sheet enables you
to properly install and test the Telguard as well as provide a valuable aid to future troubleshooting
if it becomes necessary. Detach and retain this data sheet in your customer account file for future
reference.
Customer Name:
Dealer No:
Installation Location:
MEM
LOC.
FIELD
Telguard Serial No:
Date Installed:
DEFAULT
VALUE
Installed By:
NEW PROGRAM
VALUE
SETTING
32
Cellular System A or B
1=System A
33
C/C Reporting Format
1=4 x 2 Pulse 40 PPS 2300 Ack (Double Round)
2=4 x 2 Pulse 20 PPS 2300 Ack (Double Round)
3=4 x 2 Pulse 20 PPS 1400 Ack (Double Round)
4=3 x 1 Pulse 40 PPS 2300 Ack (Double Round)
5=3 x 1 Pulse 20 PPS 2300 Ack (Double Round)
6=3 x 1 Pulse 10 PPS 1400 Ack (Double Round)
7=Radionics Modem IIE or 3A
2=System B
Non-Extended
Non-Extended
Non-Extended
Non-Extended
Non-Extended
Non-Extended
8=Contact ID (Ademco) 1400/2300 Ack
51
STC Trip Output Reporting
31
Enter the SUM TOTAL of the events that you wish to trip the STC relay
by ADDING the corresponding values:
(ex: 01+02+08+16=27) Note that a LFC will not trip the STC relay.
Program 31 (27+04) for all supervised features to trip the STC relay.
00 = STC Trip Input Not Used
01 = AC Failure
04 = LFC
16 = RFC
02 = Low Battery 08 = NSC
52
STC Trip Delay for LFC and NSC
1=30 Seconds
61
CFC Number of Attempts
0=Disabled
62
CFC Between Events
1=30 Seconds
67
Standby Battery Size
(standard lead-acid battery)
2=1.4 Amp Hour
3=4 Amp Hour
99
Factory Default Values
56019201
2=60 Seconds
2=4 Attempts
1=2 Attempts 3=8 Attempts
2=60 Seconds
4=7 Amp Hour
5=14 Amp Hour
Returns EEPROM to original factory settings.
12345
Page 12
© 2000 Telular Corporation
5.2.6
Setup & Programming
When the Telguard is received from the factory and is powered up for the first time, it is
immediately ready for activation after a 10-second delay, provided the default settings are what you
want. The STC LED turns on steady and the STC relay is tripped. If changes to the default values
are required, then the Telguard is re-programmed with a plain old telephone set (POTS) connected
to J2 where the C/C is usually connected. A standard lineman's buttset (set to TALK and TONE
modes) can also be used when connected to the tip (T) and ring (R) test pins on the printed circuit
board (PCB) adjacent to JI and J2. Put jumper J5 "IN" and power up the Telguard. The Telguard
Programming Data Sheet explains the programming options and memory locations.
NOTE: The telephone line input to J1 must be disconnected prior to programming and the
antenna must be connected. The Telguard will transmit the programming setup data to the
communication center automatically when you activate the Telguard using the Telular IVR.
5.2.6.1 Command Key Sequences For POTS Re-Programming
Key Sequence
memorylocation, value
Description
Selects memory-location and stores data.
Exits and stores programming.
The syntax for programming a specific memory location is as follows:
Memorylocation (2 digits), value.
For example, to re-program the Telguard to transmit over the "A" carrier, the installer would power
down the Telguard; put jumper J5 "IN", connect the buttset to T and R test pins, and then power up
the unit. After approximately 10 seconds, four tones will be sounded on the buttset indicating entry
into programming mode. After entering 32, two tones will be sounded on the buttset indicating entry
into a valid memory location (in this case, location 32). After the digit 1 is entered, four tones will
be sounded on the buttset indicating a valid entry has been selected. If an invalid memory location
or data value is entered, a long low tone will be sounded before the normal tones. To re-enter a
correct value, the memory location must be entered again and then a correct value for that
memory location.
NOTE: To reset Telguard programming to factory default values, program memory location
99 with 12345 and the Telguard will reload factory default data to the EEPROM (This takes
about 10 seconds!). The Telguard will now be ready to activate with factory default values or
to re-program again, just as it was received from the factory.
To exit programming mode, press *. Two tones will be sounded on the buttset. Remove jumper J5
and disconnect the buttset. The Telguard does not need to power down and back up again unless
you changed from B to A carrier or from A to B carrier. The red STC LED will remain on and the
STC relay will remain tripped. Call the Telular IVR (888-TELULAR) and follow the “new
activation or re-programming” menu. When the Telguard transmits the setup programming
information to the Communication Center successfully, the red STC LED will begin flashing a Telco
line fault trouble (LFC=3 flashes), the yellow Mode LED will turn on, and the AC power LED will
turn on if AC is connected. This indicates the unit is in normal operating mode and is ready to
transmit alarm signals.
5.2.7 Connect Antenna and Temporarily Place Unit
The Telguard is supplied with an antenna that is connected directly to the unit. If a stronger radio
signal is required, the unit with antenna connected must be moved to a better signal location. The
characteristics of the Telguard antenna can be altered depending upon the wall material and
materials contained within the wall chosen for mounting. These effects may not be clearly identified
by RSSI monitoring alone. The wall materials may have a more profound affect on the antennas
transmit band performance. Best antenna performance will be obtained when the Telguard is
mounted on a dry wall (plaster) with the antenna centered between wall studs and there are no metal
56019201
Page 13
© 2000 Telular Corporation
objects (such as water pipes or electrical conduit or air ducts) contained within the wall directly
behind, above or below the Telguard's antenna. Never mount the Telguard on a metal surface or on
a wall that contains metal material.
When selecting a mounting location, do not mount this unit in an area where the general public could
reasonably be within 20cm (8 inches) of the antenna.
Note 1: Optimum RF performance can usually be found at the highest point within a building with the fewest
number of walls between the Telguard’s antenna and the outside of the premises.
Note 2: To avoid interference with other electronic devices operating in the area, avoid mounting the Telguard’s
antenna near other electronic devices. Highest radiated RF energy is in the direct horizontal line of the antenna.
Therefore vertical separation (moving electronic devices or the Telguard’s antenna either higher or lower on the
wall) provided higher levels of RF isolation from the Telguard.
Note 3: The Telguard DataBurst unit is designed for indoor installations ONLY. Mounting the Telguard outdoors
will cause system failure and may constitute a shock hazard to humans. However, a Telguard remote antenna can
and should, whenever possible, be mounted outdoors for least RF interference.
These considerations should be coupled with the best RSSI indication obtainable (see section
5.2.8). Care should be taken to insure that a large metal object such as a refrigerator or a metal
cabinet is not located on the opposite side of the wall under consideration. Additionally, when the
system is armed, care should be taken that metal overhead doors or security gates are not moved into
a position that might cause a reduction of radio signal.
If moving the Telguard to a different location is not practical, then you may need a longer cable on
the remote antenna in order to receive adequate radio signal strength. Pick a high, visually secure
spot, using the guidelines below.
5.2.7.1 Tips for Improved Radio Signal Reception
•
•
•
•
The higher the antenna the better. So, start in the drop ceiling above the unit and proceed
up from there, to the roof if necessary.
Remember, the antenna should be as inconspicuous as possible for greatest visual security.
If on the roof, plan to place the antenna in PVC tubing or in a custom wooden structure.
Try to keep the antenna away from sources of RF interference, including pumps,
compressors, ovens, etc., or where metal objects can shield it or otherwise block the
cellular radio RF signal.
Place the antenna perpendicular to the ground, either right side up or upside down. Do not
mount the antenna horizontally.
5.2.8 Measure Received Signal Strength (RSSI) for Best Antenna Placement
Measure the received signal strength by putting jumper J5 "IN". This switches the LEDs to signal
strength mode. Now, slowly move the unit or remote antenna to achieve maximum signal strength.
Pick the place where the most LEDs (up to four) are lighted. The LEDs are located on the top-right
side of the PCB and are read from bottom to top with the Radio TX LED = 1 and the AC Power
LED = 4. At least two lighted LEDs with the third LED flashing are necessary to assure
continuous, trouble free operation. Move antenna slowly and check often. Only a few inches can
make a great difference in signal strength.
LED Function Table – View RSSI Mode
RSSI Value
NO SVC
56019201
LED’s Lighted
LED 1* = on, 2-4 = off
LED 1 = on, 2-4 = off
Page 14
RF dBm
≤ -116 dBm
≤ -111 dBm
© 2000 Telular Corporation
1
LED 1 = on, 2 = slow flash
LED 3-4 = off
LED 1-2 = on, LED 3-4 = off
LED 1-2 =ON, 3 =SLOW FLASH
LED 4 = off
LED 1-3 = on, LED 4 = off
LED 1-3 = on , 4 = slow flash
LED 1-4 = on
≥ -110 dBm
≥ -100 dBm
≥ -90 dBm (Minimum signal
strength required)
≥ -80 dBm
≥ -70 dBm
≥ -60 dBm
*Note: LED 1 = Radio TX; LED 2 = Mode; LED 3 = STC; LED 4 = AC Power.
NOTE: If you can not obtain a signal strength reading of TWO LEDS ON SOLID AND THE
THIRD LED ON SLOW FLASH, you will probably need to move the unit and/or remote
antenna higher, or switch to a special antenna, as described below.
5.2.8.1 Antenna Options
Antenna problems are unlikely unless the premises are located in a fringe network
coverage area, in a building below ground level, or in a metal structure. However, here
are your options:
Magnetic Mount 3-dB gain Antenna with 12ft. Cable: The 3dB magnetic mount antenna
comes with 12 feet of cable (Telular model no: 1F01A001 ).
Magnetic Mount 5-dB gain Antenna with 12ft. Cable: The 5dB magnetic mount antenna
comes with 12 feet of cable (Telular model no: 1F01A003 ).
NOTE: After determining the best signal strength location for the antenna, set the
RSSI jumper J5 "OUT" to return to normal operating mode. If the “RSSI”
jumper is inadvertently left "IN", Telguard will still operate normally.
5.2.9 Request Telguard Activation "PING" from Telular's IVR
When you are ready to install and test the Telguard, call Telular's IVR (Interactive Voice Response)
number, 1-888-TELULAR (1-888-835-8527). The automated system will ask you for the following
information: (All information must be supplied correctly)
Reminder!!! The Activation form must be faxed to the Telular Communication Center (fax:
678-945-1651) and entered into the database before this step can occur.
a) Dealer number?
b) Tech number?
c) Telguard Serial Number? Or, Confirmation Number if the Serial Number has not been
previously submitted on the Activation Form.
d) New Telguard programming/reprogramming or Requesting Status Report? (Select the
programming menu.)
After you have programmed the Telguard, entered the correct Dealer, Tech, Telguard Serial number
(or Confirmation Number), and selected "yes" for new install or reprogram on the menu, a radio
"activation ping" will be generated from the Communication Center to the Telguard. This activates
the Telguard and allows the Telguard to communicate over the cellular network. A successful
"ping" causes the red STC LED to turn off. Additionally, if the Telguard is programmed to monitor
LFC, then the STC LED will begin to flash 3 times indicating a telco line fault condition since there
is no telco line connected to J1 at this time. Also, the yellow Mode LED will turn on and if AC
power is connected, the green AC power LED will turn on.
Now, combined with other data previously submitted with the activation information such as
automatic self-test data, the communication center is able to process alarm signals from the host C/C
to the alarm monitoring station.
Note to Installers: The Telguard must be powered-up with antenna connected in order to receive
the "activation ping". Also, the Telular IVR system will allow you to enter a TEST menu to access
the Telguard's operational history (e.g., number of occurrences of ACFC, LBC, LFC, and NSC since
the last self-test transmission to the communication center). Only the Dealer number, Tech number,
56019201
Page 15
© 2000 Telular Corporation
and serial number are required to enter the TEST menu if the unit has already been activated. This
feature is extremely helpful when troubleshooting intermittent problems such as NSC or LFC.
MOVE ON
Once you have completed the Telguard Programming Data Sheet, confirmed Telguard programming, received
the "activation ping" from the Communication Center and have good signal-strength, move on to Step 3.
56019201
Page 16
© 2000 Telular Corporation
5.3 STEP 3: TRANSMIT C/C ALARMS OVER THE CELLULAR RADIO NETWORK
Confirm that the Telguard enables the host C/C to transmit alarm signals over the cellular radio network. In checking
this, do not connect the incoming telco line to the Telguard or connect the supervisory trip output (STC) to the C/C
zone input.
INCOMING
TELCO
ANTENNA
RJ31X
S E E AP PE NDIC ES A1 .1 THRO UG H A1 .4 FOR
DE TAILS O N JACK AND PI N AS SI G NM E NTS ,
TE RM I NAL S TRIP , JU M PE R, AN D S TATU S LED S.
PREMISE
PHONES
S TATUS LE DS
(Se e Appe ndix A1.3 )
TELGUARD
AC POW ER
SYSTEM TR OUBLE
OPERAT ION MODE
RADIO T X
SIGNAL
STRENGTH
LEDS
LED MODE SELECT
J5
OUT = NORMAL
IN = RSSI
TRA NSCEIVER
J2
J1
TELCO DIALER
+ BATTERY 12V
- BATTERY
STC (N.O.)
STC (COM)
BLANK PIN
AC (16.5V 40VA)
AC (16.5V 40VA)
HOST C/C
FUSE 3A 3AG
EARTH GROUND
2 4 H OUR ZONE I NPUT
2 4 H OUR ZONE C OM M ON
TG3 Step 03 .VS D
5.3.1 Connect C/C to Telguard Jack 2
Unplug the modular jack of the C/C-to-RJ31X cable (not supplied) from the RJ31X and plug it into
J2 on the Telguard.
NOTE:
56019201
Since no RJ31X telco cable is connected to J1 at this point in the installation, the
Telguard is detecting a telco line fault condition (LFC). The Telguard is forced to
switch transmission paths from telco to cellular causing all C/C alarm signals to be
transmitted over the cellular radio network during testing in this step.
Page 17
© 2000 Telular Corporation
5.3.2 Verify Alarm Signal Transmissions over Cellular
Trip several alarms on the C/C and verify that the central station received them by calling the
central station operator. Use a lineman's buttset in MONITOR MODE and connected to Telguard's
"T" and "R" test pins to "listen" to communications between the C/C and Telguard. The Radio TX
LED flashes quickly when the Telguard microprocessor is communicating with the radio and
provides a long flash (approximately 1 second) when the radio is in communication with the cellular
network.
If you are having problems getting reliable alarm signal transmissions, additional adjustments may
be necessary.
♦
♦
♦
Recheck signal strength. You need TWO LEDS ON SOLID AND THE THIRD LED
FLASHING for adequate signal strength. Also, check antenna connector and make sure it is
seated correctly.
Try resetting the Telguard by powering the unit down then back up again.
Call Telular Technical Service, 800-229-2326, and request the Communication Center operator
to check the Telguard programming configuration for proper operation on "A" carrier or "B"
carrier and proper communications format. The Telguard MUST be programmed to use the
SAME FORMAT that the C/C is using (e.g. 3+1, 4+2, etc.,) to report alarm signals.
MOVE ON
Once you have determined that the C/C can reliably transmit alarm signals over the cellular network, proceed
to Step 4.
56019201
Page 18
© 2000 Telular Corporation
5.4 STEP 4: CONNECT TELCO LINE AND SUPERVISORY TRIP OUTPUT
Now, you are ready to connect and test the incoming telco line and the supervisory trip output to the C/C.
Also, you must check to be sure that there are no other phone devices connected in front, or in parallel, of
the RJ31X.
B E SURE T ELGUARD IS FIR ST DEVICE ON INCOMING
PHONE LINE TO PREVENT
PHA NT OM TRIPPING.
INCOMING
TELCO
ANTENNA
RJ31X
S E E AP PE NDIC ES A1 .1 THRO UG H A1 .4 FOR
DE TAILS O N JACK AND P IN AS S IG NM E NTS ,
TE RM I NAL S TRIP , JU M PE R, AN D S TAT US LED S.
PREMISE
PHONES
S TATUS LE DS
(Se e Appe ndix A1.4 )
TELGUARD
AC POW ER
SYSTEM TR OUBLE
OPERAT ION MODE
RADIO T X
SIGNAL
STRENGTH
LEDS
LED MODE SELECT
J5
OUT = NORMAL
IN = RSSI
TRA NSCEIVER
J2
J1
UNPLUG AND REPLUG J/J CABL E
(SUPPLIED) AT J1 A ND VERIFY THAT
TELGUARD SW ITCHES TO CELL UL AR AND
BACK TO T EL CO BY WAT CHING T HE STC
LED (3 flashes for LF C).
TELCO DIALER
+ BATTERY 12V
- BATTERY
STC (N.O.)
STC (COM)
BLANK PIN
AC (16.5V 40VA)
AC (16.5V 40VA)
HOST C/C
FUSE 3A 3AG
EARTH GROUND
E.O.L. RESISTOR
2 4 H OUR ZONE I NPUT
2 4 H OUR ZONE C OM M ON
PROGRAM ZONE SHORTED FOR "SYSTEM T ROUBLE".
TG3 Step 04 .VS D
5.4.1 Be sure the Telguard is the first device on incoming phone line
The Telguard monitors voltage on the incoming phone line to decide when to switch transmission
paths. This requires that the Telguard must be the first device on the telco line. If not, a line fault
condition will be created (we call this a "phantom trip") each time the improperly connected device
goes off-hook. This happens because the Telguard‘s line fault monitor detects the parallel "taps" to
the street side of the RJ31X.
A phantom trip causes the Telguard to switch to cellular and if the STC trip-out is connected and
programmed to trip the C/C, the C/C will call the central station over the cellular network to report
the "Line Fault" (phantom trip). The result is a phone line trouble report although the incoming line
measurements are good at the RJ31X. Therefore, look over Exhibit I (next page) carefully and be
sure that there are no other phone devices connected to Tip and Ring on the incoming phone line.
56019201
Page 19
© 2000 Telular Corporation
Exhibit 1. Telco Signal Path through Telguard
House Phone
Current
Measurement
Dialer Current
Measurement
PREMISE PHONES
Telco Voltage
Measurement
TELGUARD
T1 T R R1 T1 T R R1
J1
J2
RJ31X
GREEN
RED
R1
1 T1
BROWN
GREY
T1 T R R1
INCOMING TELCO
Internal Circuitry
Telco Dialer
HOST C/C
SIGPATH0.VSD
5.4.2 Connect RJ31X to Telguard Jack 1 and Check LFC
Find the modular Jack-to-Jack (J/J) cable supplied and connect one end to Telguard Jack 1 and
other end to the RJ31X. Note that the STC LED goes out and the STC relay returns to normal due to
telco line restoral.
5.4.3 Connect STC Trip Output
Connect the STC trip output (terminals 1 & 2, N.O.) to the 24-hour zone input of C/C.
NOTE: Activation of a local alarm or strobe light may be desirable when a trip is declared. The
STC trip output can be used directly to activate a local signaling device, provided that the trip
output is not needed to trip the host control/communicator at the same time. If both a local signal
and a control trip input is required, then external relays are needed to provide additional
uncommitted contacts.
56019201
Page 20
© 2000 Telular Corporation
5.4.4 Check Telguard Supervisory Trip to C/C
After you have connected the STC trip output, check to be sure that it operates correctly.
5.4.4.1 Reprogram C/C to Send Proper Code
Reprogram C/C to send proper alarm code when tripped by the Telguard’s supervisory
output. Program zone restoral as desired.
5.4.4.2 Check Proper Operation of Telguard Supervisory Output
Check for proper operation of each programmed supervisory output by causing it to trip the
C/C and be sure the proper LED illuminates and that the proper trouble code is reported to
the central station. Skip the testing of any supervisory functions that have not been enabled.
Note that the yellow mode LED starts to flash when the C/C goes off-hook to report the
alarm signal over cellular. The yellow mode LED stays on solid when the C/C goes offhook to report the alarm signal over Telco.
•
•
•
•
Low Battery Condition (LBC): Disconnect the battery and during the next 60 seconds
check to see that the STC LED flashes 2 times indicating that the battery is missing.
Check to see that the C/C transmits the STC trouble code (over Telco) to the central
station. Reconnect the battery and check during the next 60 seconds to see that the
STC LED goes off, indicating the missing battery condition has been restored. If the
C/C is programmed for transmitting restorals, another transmission will be sent (over
Telco) to the central station.
Line Fault Condition (LFC): Disconnect J/J cable at RJ31X. Check to see that the
STC LED flashes 3 times in 30/60 seconds and the C/C transmits the STC trouble
code (over radio) to the central station indicating the incoming telco line is
disconnected. Reconnect J/J cable and check to see that the STC LED goes off in
30/60-seconds indicating telco line restoral. If the C/C is programmed for transmitting
restorals, another transmission will be sent to the central station (over Telco) after the
30/60-second delay.
No Service Condition (NSC): Disconnect the antenna from the Telguard. Check to
see that the STC LED flashes 4 times in 30/60 seconds and the C/C transmits the STC
trouble code over the telco line indicating loss of RF signal strength. Reconnect the
antenna and check to see that the STC LED goes off in 30/60-seconds indicating RF
signal strength restoral. If the C/C is programmed for transmitting restorals, another
transmission will be sent to the central station (over Telco) after the 30/60-second
delay.
Note: The Received Signal Strength (RSSI) must be less than -114 dBm in order to
cause a NSC condition. If the Telguard is located in a high signal strength area (close
to a cellular tower), it is possible for the signal strength to be greater than -114 dBm
even with the antenna disconnected.
AC Fail Condition (ACFC): Disconnect the 20VA AC transformer and check to see
that the AC POWER LED goes out and the STC LED flashes once indicating that AC
power is missing. Reconnect the AC transformer and check to see that the AC
POWER LED goes on and the STC LED goes off indicating that AC power has been
restored. No transmissions will be sent to the central station. The AC power must be
off, continuously, for 6-hours before the STC relay causes the C/C to send a trouble
code. If the AC power is restored for 60 seconds or more, then the 6-hour timer
restarts.
MOVE ON
When you are sure that the Telguard is monitoring the telco path and cellular path correctly and the C/C is correctly
reporting the STC supervisory trip output, move on to Step 5.
56019201
Page 21
© 2000 Telular Corporation
5.5 STEP 5: COMPLETE THE TELGUARD INSTALLATION
Last step is to handle loose ends.
5.5.1 Check Settings
Check the jumper setting of J5 (LED mode, out = normal).
5.5.2 Permanently Mount and Properly Ground the Telguard Chassis
Attach earth ground to the green grounding screw located on lower left-hand corner of printed
circuit board assembly and permanently mount the Telguard chassis.
56019201
Page 22
© 2000 Telular Corporation
A1.0 Wiring Diagram
WARNING: HIGH VOLTAGE PRESENT ON
PHONE LINES. DISCONNECT
PRIOR TO SERVICING.
INCOMING
TELCO
ANTENNA
RJ31X
PREMISE
PHONES
STATUS LEDS
(See Appendix A1.4)
AC POWER
SYSTEM TROUBLE
TELGUARD
OPERATION MODE
RADIO TX
SIGNAL
STRENGTH
LEDS
LED MODE SELECT
J5
OUT = NORMAL
IN = RSSI
TRANSCEIVER
J2
J1
TELCO DIALER
+ BATTERY 12V*
- BATTERY
STC (N.O.)
STC (COM)
THIS DEVICE COMPLIES W ITH FCC RULES PART
68 AND 15.
FCC R EGISTR ATION NO: TBD
RINGER EQUIVALENCE: 0.0B
T E L G UA RD ®
is a re gi ste re d tr ad em ark o f Te lul ar
Corporatio n. Products are prote cted under one o r more o f
the f ol lo wing U.S . p ate nts: 4 ,6 58 ,0 9 6
4 ,73 7 ,9 75
4,775,997 4,8 68,519 4 ,92 2,51 7.
BLANK PIN
AC (16.5V 40VA)*
AC (16.5V 40VA)
D O N OT
C ONNE CT T O A
SWIT C HED AC
REC EP T AC L E.
HOST C/C
FUSE 3A 3AG
EARTH GROUND
E.O .L. RESISTOR
24 HOUR ZONE INPUT
24 HOUR ZONE COMMON
CAUTION: INCORRECT CONNECTIONS MAY
RESULT IN DAMAGE TO UNIT.
© 20 00 Te lular Corpo ration.
STC Relay Maximum Contact Rating: 1A-30VDC
* INDICATES SUPE RVISED CIRCUIT.
Note: AC terminals 6 and 7 are power limited.
TG3 WIRING.VSD
56019201
Page 23
© 2000 Telular Corporation
A1.1 JACK AND PIN ASSIGNMENTS
Jack
Designation
Connects To
Pin Assignment
Incoming Telco
RJ31X Jack.
C/C Digital
Dialer
Digital Dialer
input/output of
host C/C.
J4
Radio
J1
Telco RJ31X.
J2
Radio Interface.
56019201
Gray R1
Red R(Ring)
Green T(Tip)
Brown T1
Function
Status LED
Reference
Connects telco line to
Telguard and provides
output for premises phone
connection at RJ31X.
STC LED Flash 3 times
when telco voltage is
lost.
1 Gray R1
4 Red R(Ring)
5 Green T(Tip)
8 Brown T1
Connects C/C digital dialer
input/output through unit.
None.
1 VCC
2 SVC
3 GND
4 Rsvd
5 RXD
6 Rsvd
7 TXD
8 P-IN
9 RSSI
10 N/C
11 IN-A
12 IN-B
13 OUT-A
14 OUT-B
+12V DC supply input
Service available flag
Primary Ground
Reserved
Control serial data RX
Reserved
Control serial data TX
Pulse Input
Rx signal strength indication
Pulse Ground
Auxiliary input A
Auxiliary input B
Auxiliary output A
Auxiliary output B
STC LED Flash 4 times
for NSC or Flash 5
times for RFC when
Radio is unable to
communicate.
Page 24
Or
Radio Tx LED Fast
Flash when
microprocessor is
communicating with
radio and 1 sec Flash
when Radio is
transmitting over the
cellular network.
© 2000 Telular Corporation
A1.2 TERMINAL STRIP PIN ASSIGNMENTS
Terminal
Strip Pin
1 STC
2 STC
Definition
Supervisory Relay
Trip output for
programmable trouble
conditions. (N.O.)
Connects
To
24-hour trip
zone input on
host C/C.
Status LED
Reference
Function
Enables transmission of programmed supervisory
trouble code:
When fault condition
occurs:
♦
AC Power LED OFF
STC LED Flashes 1
time.
AC Power Fail (ACFC).
AC failure detected at 102 VAC.
♦ Low/Missing Battery Condition (LBC) due to:
- Low Battery detected at 11.6 VDC.
STC LED Flashes 2
times.
♦ Line Fault Condition (LFC) due to:
- Improper Telco voltage (LFC) ≤ 18 VDC.
STC LED Flashes 3
times.
♦ No Service Condition (NSC) due to:
- Received Signal Strength ≤ -114 dBm.
STC LED Flashes 4
times.
♦ Radio Communications Failure (RFC) due to:
- RFC1- Failure to receive Link Request Ack after 3
attempts.
OR
RFC2- Failure to receive Link Termination Ack
after 2 attempts.
STC LED Flashes 5
times.
♦ Loss of Telguard Dial Tone Voltage (DTF) due
to: Improper dial tone voltage. ≤ 35 VDC.
3 - BATT
Telguard Battery
negative terminal.
4 + BATT
(12 V)
Telguard Battery
positive terminal.
5 BLANK
6 AC
Telguard
backup battery
Provides 24 to 72 hour battery stand-by for Telguard
depending on battery capacity provided.
Not Used
N/A
Not Used
AC power input.
16.5 VAC 20 VA.
120 VAC
60Hz
unswitched
circuit.
7 AC
56019201
STC LED Flashes 2
times when battery is
low or missing.
None
Provides primary operational power to Telguard and
battery charging circuit.
Page 25
STC LED Flashes 6
times.
AC Power LED ON
when AC is normal.
OR
AC power LED OFF
And
STC LED Flashes 1
time when AC is low
or missing.
© 2000 Telular Corporation
A1.3 LED M ODES AND FUNCTIONS
As shown below, J5 is a two-pin jumper used to select the LED Mode. Refer to the LED Function
Tables for a description of each LED in "Normal Operating Mode" and "Received Signal Strength
Mode".
LED Mode Selection
ON
OFF
OFF = NORMAL MODE
ON = VIEW RSSI MODE OR ENTER PROGRAMMING MODE
LED Function Table – Normal Operating Mode (J5 = OUT)
LED Symbol Color Duty Cycle
Indication
AC POWER – LED 4
Green
Solid ON
OFF
1 Flash*
STC - LED 3
MODE – LED 2
RED
Yellow
Green
System Trouble Condition – Low/Missing AC Power
2 Flashes*
System Trouble Condition – Low/Missing Battery Condition
3 Flashes*
System Trouble Condition – LFC
4 Flashes*
System Trouble Condition – NSC
5 Flashes*
System Trouble Condition – RFC
6 Flashes*
System Trouble Condition – DTF
Solid ON
Telguard operating in Mode 1
Fast Flash
C/C off-hook to transmit signals over cellular.
Solid ON (1 sec)
Radio TX – LED 1
AC Power is good
AC Failure (<102 VAC, restores at 106 VAC)
Fast Flash
OFF
Telguard in Microburst transmission.
Microprocessor communicating with Radio.
No Activity
* - Note: One flash = ½ sec On and ½ second OFF. In order to diagnose multiple problems on STC LED, each condition will
display for 5 seconds and then cycle to the next condition
LED Function Table – View RSSI Mode (J5 = IN)
RSSI Value
LED’s Lighted
RF Signal (dBm)
LED 1* = on, 2-4 = off
≤ -114 dBm (Lowest)
LED 1 = on, 2-4 = off
≤ -111 dBm
LED 1 = on, 2 = slow flash
≥ -110 dBm
LED 3-4 = off
LED 1-2 = on, LED 3-4 = off
≥ -100 dBm
LED 1-2 =ON, 3 =SLOW FLASH
≥ -90 dBm (Minimum signal
LED 4 = off
strength required)
LED 1-3 = on, LED 4 = off
≥ -80 dBm
LED 1-3 = on , 4 = slow flash
≥ -70 dBm
LED 1-4 = on
≥ -60 dBm (Highest)
*Note: LED 1 = Radio TX; LED 2 = Mode; LED 3 = STC; LED 4 = AC Power.
NO SVC
56019201
Page 26
© 2000 Telular Corporation
A1.4 JUMPERS
Jumper
Feature
J5
Normal Operating
Mode, RSSI or
Programming Mode.
56019201
Function
Used as LED Mode selector to indicate
operating conditions of Telguard, used to
view Received Signal Strength or enter
Programming Mode. Refer to A1.4.
Page 27
Jumper Position
In
Out
View Received
Signal Strength
or
Enter
Programming
Mode.
Normal*
© 2000 Telular Corporation
A2.0 Operational Quick Reference Table
Telguard Event
Typical C/C Alarm Cycle over Telco
Telguard
System
Trouble
Conditions
Radio
Message
Internal Action
None
None
Yes
AC Power off
and
STC flashes 1
time.
Yes
STC flashes 2
times.
Yes
STC flashes 3
times.
If Selected
None
Monitors Telco line voltage and C/C
attempts
Switch to standby battery if present,
monitor battery, monitor AC for
restoral.
If Selected
None
Wait for LBC restoral, charge battery.
If Selected
None
Yes
STC flashes 4
times.
Yes
STC flashes 5
times.
If Selected
None
Switch to Radio, wait for C/C to go off
hook, transmit alarm via radio if
necessary, switch back to Telco when
restored, remove LFC condition
Continue to validate signal strength,
remove NSC when signal returns
If Selected
None
Switch back to Telco so that C/C can
communicate directly with Central
Station.
Yes
Yes
Internal 50V supply circuit failure.
Return unit for repair on RMA.
MP - Missing
Programming
parameters.
Yes
STC flashes 6
times.
Yes
STC on
steady.
Yes
None
CF - Catastrophic Failure
None
Yes
None
None
None
Yes
Radio TX
When
transmitting
Yes
Radio TX
When
transmitting
Yes
Radio TX
When
transmitting
None
Yes
(Alarm data)
Yes
(Self-test))
Telguard will not function until
operating parameters are programmed
and unit receives activation ping from
Communication Center. Telguard
remains in Telco only mode.
Telguard not working. Remains in
Telco only mode.
Switch to Radio, transmit alarm via
radio, switch back to Telco
Send Self-test information to central
station via Communication Center,
return to ready state
Yes
Radio TX
When
transmitting.
LBC - Low Battery
Condition
LFC – Telco Line Fault
Condition
NSC – No Service
Condition (Low Signal
Strength)
RFC – Radio Failure to
Communicate due to:
RFC1: No Link Request
ACK.
OR
RFC2: No Link
Termination ACK.
DTF - Dial Tone Failure
CFC – C/C communication failure over
good Telco line.
Automatic Self-Test - Communication
Center Activated.
Telguard Remote Query Communication Center Activated by
IVR, Intranet, or Customer Service.
Telguard Enable and Configuration
Upload – Communication Center
Activated.
Disable TX – Communication Center
Activated.
56019201
Relay
Output
None
ACFC – AC Fail
Condition
STC
LED
Response
None
Yes
(Status data)
Send Status data to Communication
Center for review by IVR or Intranet.
None
Configuration Data
(Setup data)
Yes
Yes
(Status data)
Telguard sends setup configuration to
the Communication Center and
switches to READY state to begin
operation. Mode LED turns on and
STC LED turns off.
TX capability is disabled until further
notice. Telguard can still receive radio
signals from Communication Center.
Page 28
© 2000 Telular Corporation
A2.1 SETUP PROGRAMMING PARAMETERS
Parameter
Description
Cellular System A or B
Program Location 32
The cellular network system through which the Telguard radio is authorized to place calls to the central station.
System B is the wireline system (usually operated by the local telephone company) and System A is the nonwireline system (usually operated by the telephone company's competitor). 1=A, 2=B.
C/C Reporting Format
Program Location 33
This format must be the same format that the C/C is programmed to use when communicating with the central
station over Telco. The programmed selection tells the Telguard how to digitally encode alarm messages from the
C/C to the central station over the cellular network control channels.
1=4 + 2 Pulse 40 PPS 2300 Ack (Double Round) Non-Extended
2=4 + 2 Pulse 20 PPS 2300 Ack (Double Round) Non-Extended
3=4 + 2 Pulse 20 PPS 1400 Ack (Double Round) Non-Extended
4=3 + 1 Pulse 40 PPS 2300 Ack (Double Round) Non-Extended
5=3 + 1 Pulse 20 PPS 2300 Ack (Double Round) Non-Extended
6=3 + 1 Pulse 10 PPS 1400 Ack (Double Round) Non-Extended
7=Radionics Modem IIE or 3A2
8=Contact ID (Ademco)
STC Trip Output Reporting
Program Location 51
Telguard has the capability to supervise proper operation of both power supplies (AC & DC) and proper
operation of both paths of communication (Telco and Cellular) to the central station. Should a condition occur that
prevents Telguard from operating properly, the condition if programmed, will cause the supervisory trip output
(STC) to trip the C/C's 24-hour zone forcing the C/C to communicate the "Telguard System Trouble Condition" to
the central station.
Enter the Sum Total of STC events that you wish to report by adding the corresponding values:
Example: 01 (AC Failure) + 02 (Low Battery) + 08 (NSC) + 16 (RFC) = 27.
A failure of any individual or combination of these five programmable supervised conditions will cause the STC
relay to trip. Notice that since LFC is not selected, a Telco line fault will not cause the STC relay to trip and
therefore, no STC trouble report will be sent to the central station by the C/C.
00 = STC Relay Trip Not Used
01 = AC Failure
02 = Low Battery
04 = LFC
08 = NSC
16 = RFC
STC Trip Output Delay for LFC
and/or NSC
Program Location 52
The amount of time (30 or 60 seconds) after a LFC or NSC fault condition occurs that the STC relay will trip.
This trip delay also applies to a LFC or NSC restoral.
CFC Number of Attempts
Program Location 61
The number of attempts that the C/C will try to communicate with the central station over a good Telco line before
Telguard switches the C/C to the cellular path.
0=Disabled
1=2 Attempts
2=4 Attempts
3=8 Attempts
CFC Between Events
Program Location 62
The amount of time that the C/C is allowed to go off-hook, on-hook, then off-hook again to qualify as a
communications failure over Telco.
1=30 Seconds
2=60 Seconds
Standby Battery Size
(standard lead-acid battery)
Program Location 67
This information is provided as historical data for the Telguard database.
2=1.4 Amp/Hour 4=7 Amp/Hour
3=4 Amp/Hour
5=14 Amp/Hour
56019201
Page 29
© 2000 Telular Corporation
A2.2 TELGUARD COMMUNICATION FORMATS
Telguard Standard Communication Formats
NAME
HANDSHAKE
FREQUENCY
2300Hz
2300Hz
1400Hz
2300Hz
2300Hz
1400Hz
FSK
DUAL TONE
1400Hz / 2300Hz
RADIONICS (Double Round)
FRANKLIN (Double Round)
SIA P3 (Double Round)
RADIONICS (Double Round)
FRANKLIN (Double Round)
SIA P1 (Double Round)
Radionics Modem IIE or 3A2
ADEMCO CONTACT ID
DATA
FREQUENCY
1800Hz
1800Hz
1900Hz
1800Hz
1800Hz
1900Hz
DTMF
BAUD RATE
FORMAT
EXTENDED
40 PPS
20 PPS
20 PPS
40 PPS
20 PPS
10 PPS
300 BPS
DTMF
4-2
4-2
4-2
3-1
3-1
3-1
4 digits account
4-2-1-3-2-3
NO
NO
NO
NO
NO
NO
NO
KISS OFF
FREQUENCY
2300Hz
2300Hz
1400Hz
2300Hz
2300Hz
1400Hz
FSK
1400Hz
Telguard
CODE
A2.3 COMPATIBLE CONTROL COMMUNICATORS
For UL Listed Commercial Burglary and Fire, and Residential Burglary and Fire (Combination Listed)
Telguard Compatible Data Formats
C/C
Model
Radionics
Franklin
SIA P3
Radionics
Franklin
SIA P1
UL LISTED
4+2 40pps
2300Hz
ACK
4+2 20pps
2300Hz
ACK
4+2 20pps
1400Hz
ACK
3+1 40pps
2300Hz
ACK
3+1 20pps
2300Hz
ACK
3+1 10pps
1400Hz
ACK
DS7400Xi
NAPCO MA3000
Radionics D2112
Radionics D2212
Radionics D4112
Radionics D6112
Radionics D7212
Radionics D7412
Radionics D8112
Radionics D9112
Radionics D9412
Radionics
Modem
Ademco
Ademco
Contact ID
(DTMF)
IIE or 3A
A2.4 COMPATIBLE RECEIVERS
Compatible Data Formats
Receiver
Model
FBI CP220
Radionics 6500
Osborne-Hoffman
Quickalert
Silent Knight 9000
SUR-GARD DRL2A
Ademco 685
56019201
Radionics
Franklin
SIA P3
Radionics
Franklin
SIA P1
4+2 40pps
2300Hz ACK
4+2 20pps
2300Hz
ACK
4+2 20pps
1400Hz
ACK
3+1 40pps
2300Hz
ACK
3+1 20pps
2300Hz
ACK
3+1 10pps
1400Hz
ACK
IIE or 3A
Page 30
Radionics
Modem
Ademco
Ademco
Contact ID
(DTMF)
© 2000 Telular Corporation
A2.5 ACTIVATION FORM
(FAX to 678-945-1651)
Subscriber Information
Telguard DataBurst Information
This data is pertinent to the installation and location of the Telguard
DataBurst system.
The following data must be entered into the Telular Communication
Center computers prior to activation on the cellular network.
Subscriber Name:
Subscriber Address:
City, ST, Zip:
Contact Name:
Contact Phone:
Telguard Serial Number:
C/C Account Number:
C/C Reporting Format:
Primary C/C Phone Number:
Secondary C/C Phone Number:
Billing Information
In order to activate Telguard DataBurst systems on the cellular network,
you must be a registered Telguard DataBurst Dealer. Enter your Dealer
information below. If you are not registered as a dealer and would like
more information, contact Telular Sales at (800) 229-2326.
Dealer Company Name:
Dealer Account Number:
Contact Name:
Contact Phone:
Central Station Information
Name of Central Station: _________________________
Contact Name: _________________________________
Contact Phone: _________________________________
Telguard Automatic Self-Test
Installer Information
In order to activate the Telguard DataBurst from the toll free IVR(1888-TELULAR), your installer must be registered under your Dealer
Account.
Installer Name:
Installer Number: _______________________________
Most rate plans include options for a Telguard Automatic Self-Test
signal to be sent to your Central Station. This test signal verifies the
integrity of the DataBurst system to your central station, and logs status
information for that system on the Telular Communication Center.
Please select the Test Code, which is transmitted to your central station,
and the time of day the Test signal should be transmitted. The
frequency of the Automatic Self-Test is selected when you choose a
Cellular Service Rate Plan (Monthly Test, Weekly Test, or Daily Test).
Telguard Automatic Self-Test Code:
Telguard Automatic Self-Test Time:
AM / PM
NOTE: When activating the Telguard DataBurst unit using the Interactive Voice Recognition (IVR) system, you will be
required to enter your Dealer number, Installer number, and the unit’s Serial number or Confirmation number.
Select a Customer Code: _____________
Financial
B1 Banks
B2 Credit Unions
B3 Other Financial Locations
B4 Check Cashing Locations
B5 ATMs
Government
G1 Federal/Military Locations
G2 State Locations
G3 Local/County Locations
G4 Other Government Locations
Business Facilities
C1 Office Locations
C2 Manufacturing/Industrial
C3 Utilities/Cable Sites
C4 Warehouse/Storage
Retail General
R1 Drug/Pharmacies
R2 Supermarket/Convenient Stores
R4 Department/Chain Stores/Malls
Other Facilities
D1 Fleet/Distribution Hubs
D2 Medial/Research Labs
D3 Schools
D4 Other Facilities
Retail Specialty
R3 Office Equipment Stores
R3A Jewelry Stores
R5 Home Related Stores
R6 Other Retail Stores
R7 Electronic/Cellular/Entertainment
R8 Pawn Shops
R9 Clothing/Shoe Stores
Select a Monthly Rate Plan
Standard
Monthly Test
(Please enter Day that test is scheduled)
This rate plan includes 1 automatic self-test to allow for monthly
network testing and includes 2 free monthly alarm signals.
Day of
Month
1 to 28
❏
❏
Flat Rate
Standard
Miscellaneous
E1 Entertainment (Museums/Parks)
F1 Restaurants
H1 Residential/Private Homes
01 No Category Fit
Weekly Test
(Please enter Day that test is scheduled)
This rate plan includes 5 automatic self-tests to allow for weekly
network testing and includes 2 free monthly alarm signals.
Daily Test
This rate plan includes 31 automatic self-tests to allow for daily
network testing and includes 2 free monthly alarm signals.
Flat Rate
Day of
Week
Mon. to
Sun.
Standard
Flat Rate
❏
❏
❏
❏
❏
Promotional Rate Plan
Enter Name of Plan:__________________________________
56019201
Page 31
© 2000 Telular Corporation
A3.0 UL Installation Requirements for Supplemental Use (Model T100C001).
The T100C001 is UL Listed for Supplemental Use only. This means that the T100C001 will not enhance the grade of
service. Also, the T100C001 is not to be used as a main or secondary line for a fire or burglar alarm system. The
T100C001 is not intended for fire remote station, proprietary and central station use.
SECONDARY
INCOMING
TELCO
RJ31X
PRIMARY
INCOMING
TELCO
RJ31X
PREMISE
PHONES
ANTENNA
TELGUARD
TRANSCEIVER
TO DIGITAL DIALER
SEC
J2
TELCO DIALER
PRI
J1
TO TELCO RJ31X
+ BATTERY 12 V
- BATTERY
STC (N.O.)
STC (COM)
BLANK P IN
AC (16.5V 40VA)
AC (16.5V 40VA)
HOST C/C
EARTH GRO UND
ZONE TRIP INPUT
LINE 1
TG3 UL.VSD
56019201
Page 32
© 2000 Telular Corporation
A4.0
Detailed Specifications
A4.1 DIALER TO INTERFACE ELECTRONICS
The patented integrated interface by Telular, Inc. allows digital dialers to dial into the cellular radio
network.
• Line voltage: 48 Vdc into standard telephone device when on-hook.
• Dial tone: Precision 400 Hz @-13 dBm +/- 2 dBm. 16 digits dial out capability.
• Ringer equivalent: 0.0B
• Mode: Loop start only. 25mA max. +/- 5% off-hook.
• Protected by U.S. Patents: 4,658,096; 4,775,997; 4,922,517; 4,737,975; 4,868,519; 5,134,644.
A4.2 POWER
•
•
•
Power Input Rating: 120 VAC, 0.48A
Power Supply: Max full charge DC voltage = 13.8V +/- 0.1V. Max ripple = 30 mV
Battery charging system: Constant current, Electronic short circuit protection
Max. charging current of 250ma
Max voltage drop at max current = 1%
Transformer Supplied: 16.5 VAC, 20 VA, UL, plug-in
A4.3 M ICROBURST  RADIO
The Telguard DataBurst is equipped with an integrated radio transceiver conforming to TIA/EIA/IS-91
EAMPS standards for cellular compatibility and all applicable Aeris Microburst Standards. The integrated
Microburst radio provides RF control channel data communication facilities for the Telguard DataBurst
over the AMPS cellular network via the Aeris Microburst data communications protocol.
• Number of Control Channels: 42
• Frequency range = 824.030 - 848.980 MHz Tx; 869.030 - 893.980 MHz Rx
• Channel Spacing: 30KHz
• Air interface Protocol: TIA/EIA/IS-91
• Data communications protocol: Aeris Microburst
• Antenna Port: TNC connector (female), 50-ohm
• Receiver Sensitivity: -116 dBm
• Transmit Power: 3.0 watts max. into 50-ohm load (Class 1)
• Supplied Antenna: Dipole whip antenna, TNC base, Telular P/N 72006201 (supplied with Model
T100C001)
• Optional Antennas: Telular Model number 1F01A001, Magnetic mount, 5/8 wave, 825-896 MHz, Gain:
3 dB. One section 13-1/2" tall mast with 12 feet of cable. Telular Model number 1F01A003, Magnetic
mount, 5/8 wave, 825-896 MHz, Gain: 5 dB. One section 14-1/2" tall mast with 12 feet of cable. All
are supplied with TMC (male) plug connectors.
A4.4 PHYSICAL
•
•
•
•
•
Size: T100C001 9½"H x 4½"W x 1¾"D.
Shipping weight: T100C001 5 lbs.
Radio FCC ID: MTF09000
FCC Part 68 Registration: 2Q4USA-33648-MO-N. Ringer equivalence 0.0B.
°
°
Operating Environment: -10.0 C to +50 C; 0 - 90% humidity (non-condensing).
A4.5 WARRANTY
Telular will repair or replace (our option) inoperative units for up to two years from date of shipment.
Excludes damage due to lightning or installer error. Unauthorized modifications void this warranty. Not
responsible for incidental or consequential damages. Liability limited to price of unit. This is the exclusive
warranty and no other warranties will be honored, whether expressed or implied.
56019201
Page 33
© 2000 Telular Corporation
A5.0 Parts List
Part No.
Description
Basic Hardware:
Model T100C001
Economy model T100C001 is UL Listed for Supplemental Use only and is not to be used as
a main or secondary line for a fire or burglar alarm system. This means that the T100C001 will
not enhance nor detract from the grade of service of the UL Listed alarm system being used.
Model T100C001 has a compact plastic enclosure and whip antenna.
0 UL Supplemental Use
Model T200C001
Model T200C001 meets the requirements for Household Burglary, Household Fire, and
Commercial Fire installations. T200C001 has a standard metal enclosure, keylock, and
magnetic mount antenna with 12ft. cable. T200C001 is UL Listed for the following:
0 UL Household Burglary
0 UL Household Fire
0 UL Household Burg/Fire Combination
0 UL Commercial Fire
Model T300C001
Model T300C001 meets the requirements for all Household Burglary, Commercial
Burglary, Household Fire, and Commercial Fire installations. T300C001 has an attackresistant enclosure, keylock, tamper switch, and a magnetic mount antenna with 12ft. cable.
Model T300C001 is UL Listed for the following and UL Listed for Grade A Burglary
Certificate installations:
0 UL Household Burglary
0 UL Household Fire
0 UL Household Burg/Fire Combination
0 UL Central Station Burglary
0 Grade A
0 Grade B
0 UL Police Connect Burglary
0 Grade A
0 UL Commercial Fire
0 UL Commercial Fire and Central Station Burglary Grade A
0 UL Bank, Safe and Vault
0 Grade A
56019201
Page 34
© 2000 Telular Corporation
General
Accessories:
BMR-1250
Battery, 12V, 7.0 AH.
XXXXXTBD
Transformer, 16.5V, 20VA (Revere RT-1620SL).
XXXXXTBD
Dipole spike antenna (0dB gain).
1F01A001
Magnetic mount antenna (3dB gain), 12 ft. cable with TNC connector.
1F01A003
Magnetic mount antenna (5dB gain), 12 ft. cable with TNC connector.
56019201
Page 35
© 2000 Telular Corporation
Index
AC Failure Condition (ACFC)................................. 3
Aeris .......................................................................... 1
AMPS......................................................................... 1
Antenna Options ..................................................... 15
automatic self-test ...................................................... 1
Automatic Self-test Report...................................... 4
Backup batteries......................................................... 7
C/C Compatible Communication Formats .............. 2
Catastrophic Failure (CF) ....................................... 3
Cellular Service Activation Form.............................. 7
central station............................................................. 1
Communications Failure Condition (CFC)............ 2
Compatible Control Communicators ........................ 30
Contents ................................................................... iv
control channels ......................................................... 1
current operational status (C.O.S.) ............................. 4
Customer Service Center............................................ 1
Default Programming ............................................ 12
Detailed Specifications........................................... 33
Diagnostic and Status LEDs .................................... 5
Dialer to Interface Electronics .............................. 33
Directional Antennas................................................ 15
FCC Notices................................................................i
General Description................................................. 1
Ground .................................................................... 22
Installation Summary................................................ 7
Intranet System........................................................... 1
IVR............................................................................. 1
Jack and Pin Assignments ..................................... 24
Jumpers................................................................... 27
LED Function Table ................................................. 14
LED Function Table – Normal Operating Mode ...... 26
LED Function Table – View RSSI Mode ................. 26
LED Modes and Functions ..................................... 26
LED Signal Strength Indication.............................. 5
limitations on use .......................................................ii
Line Fault Condition (LFC) .................................... 2
Low/Missing Battery Condition (LBC) ................... 3
56019201
message center............................................................1
Microburst™..............................................................1
Model T100C001....................................................... 6
Model T200C001....................................................... 6
Model T300C001....................................................... 6
NAM programming.....................................................5
No Service Condition (NSC)..................................... 2
Operating Modes ...................................................... 1
Parts List................................................................. 34
PBX Installations...................................................... 2
Physical ................................................................... 33
POTS Programming ............................................... 13
Power....................................................................... 33
Power Supervision.................................................... 3
Primary Modes of Operation................................. 28
Programming Data Sheet ..........................................13
Quick Reference Tables ........................................ 28
Radio........................................................................ 33
Radio Communications Failure Condition (RFC) . 3
Remote Query............................................................ 4
Request for Cellular Service.................................... 7
RF Signal Strength................................................. 14
RFC1 (Link Request Failure) .................................. 3
RFC2 (Link Termination Failure) .......................... 3
RJ31X ........................................................................ 1
RSSI jumper...............................................................5
Setup Programming Parameters........................ 5, 29
STC Trip Output Strategy....................................... 11
Supervisory Trip Output (STC) Relay...................... 4
Telco Signal Path through Telguard..................... 20
Telguard Communication Formats ....................... 30
Terminal Strip Connections ..................................... 4
Terminal Strip Pin Assignments............................ 25
UL Listings by Model ............................................... 6
Warranty.................................................................. 33
Watchdog Monitor/Reset (WR)................................ 3
Wiring Diagram........................................................23
Page 36
© 2000 Telular Corporation

Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.2
Linearized                      : Yes
Create Date                     : 2001:01:08 11:32:45
Producer                        : Acrobat Distiller 4.0 for Windows
Modify Date                     : 2001:01:08 11:32:52-05:00
Page Count                      : 43
EXIF Metadata provided by EXIF.tools
FCC ID Filing: MTF09000

Navigation menu