Trane Odyssey 6 To 25 Tons Catalogue R22 Dry Charge Product Catalog For Cooling Condenser — 7.5, 10, 15 And 20 60 Hz

2015-04-02

: Trane Trane-Odyssey-6-To-25-Tons-Catalogue-684219 trane-odyssey-6-to-25-tons-catalogue-684219 trane pdf

Open the PDF directly: View PDF PDF.
Page Count: 16

DownloadTrane Trane-Odyssey-6-To-25-Tons-Catalogue- Odyssey R22 Dry Charge Product Catalog For Cooling Condenser — 7.5, 10, 15 And 20 Tons 60 Hz  Trane-odyssey-6-to-25-tons-catalogue
Open PDF In BrowserView PDF
Product Catalog

Split System Air Conditioners
Odyssey™
™
R-22 Dry Charge
Cooling Condenser — 7.5, 10, 15 and 20 Tons — 60 Hz

May 2014

SS-PRC037C-EN

Introduction

Trane’s reputation for providing quality comfort solutions continues with the development of the
next generation Light Commercial Odyssey Split Systems.
With wide network availability, flexible applications, installation ease, built-in reliability and easy
servicing, Odyssey will meet any number of customer applications. Add to that Trane’s
outstanding customer service and you have the formula to make Odyssey the clear choice for
continued customer satisfaction.

Wide network availability
A broad distribution network provides owners, maintenance personnel, contractors, etc., the
means to get their hands on equipment when they need it. Whether it’s an emergency
replacement or a new construction project in its infancy stages, Odyssey products meet an array
of needs at the right time and right price.

Flexible applications
No matter what the application, Odyssey provides the solution. A broad array of models and
tonnages are available with single or dual compressors, single or dual circuits and numerous
accessories. Condensing units can be installed on the ground or on a rooftop along with
extended piping runs, while air handlers can be free discharge on the ground or horizontally
suspended with long duct runs from a ceiling. Should application challenges arise, Odyssey
delivers.

Easy to install
Small footprints and low weights combined with factory installed components like TXVs, filter
driers, etc., reduce installation time and cost. Colored and numbered wiring and factory tested
units make Odyssey the right choice.

Built-in reliability
Keeping in mind that productivity only occurs when equipment is operational,Trane has taken
the steps to ensure that Odyssey is up and running. Early indicators such as phase/reversal
monitors and loss of charge protection provide diagnostics which prevent failure and provide
years of worry-free service and operation.

©2014 Trane

All rights reserved

SS-PRC037C-EN

Introduction

Easy to service
When preventive maintenance or service is required, technicians will find efficient access to both
air handlers and condensers. Panels provide complete, easy access coupled with standardized
cabinets in which all components are located in proximity. Odyssey’s improved design results in
minimum service times and costs.
With these capabilities, Odyssey provides customers high efficiency and superior performance
for the best all-around value in the market today.

Copyright
This document and the information in it are the property of Trane, and may not be used or
reproduced in whole or in part without written permission. Trane reserves the right to revise this
publication at any time, and to make changes to its content without obligation to notify any
person of such revision or change.

Trademarks
All trademarks referenced in this document are the trademarks of their respective owners.

SS-PRC037C-EN

3

Table of Contents
Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Cooling Condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Model Number Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Cooling Condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

General Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Dimensional Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Cooling Condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Weights. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Cooling Condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

4

SS-PRC037C-EN

Accessories
Cooling Condenser
Table 1.

TTA Accessories

Model

Used With

Coil (Hail/Vandal) Guard
BAYGARD058A

TTA090A

BAYGARD059A

TTA120A

BAYGARD061A

TTA180B, TTA240B

BAYHGBP010B

All models

Rubber Isolators
BAYISLT004A (blue)

TTA090A

BAYISLT005A (black)

TTA120A

BAYISLT009A (red)

TTA180B

BAYISLT010A (green)

TTA240B

Steel Spring Isolators
BAYISLT023A (red)

TTA090A, TTA120A

BAYISLT024A (black)

TTA180B

BAYISLT025A (yellow)

TTA240B

Low Ambient — On/Off Fan Control (External mount, small cabinets)(a) (b) (c)
BAYLOAMU01B (External Mount, small cabinets)(d)
BAYLOAMU02B (Internal mount, large cabinets)
(a)
(b)
(c)
(d)

(all voltages) TTA090A
(all voltages) TTA120A, TTA180B, TTA240B

Cycles fan on/off, (no modulating).
Quantity of 1 required for each fan (2 total for ).
ReliaTel™ requires onboard EDC function to be disabled when BAYLOAM is used, remove OA sensor from terminal J8-1&2
Kit mounts external to the outdoor unit and operates by sensing ambient and liquid line temperatures.

SS-PRC037C-EN

5

Model Number Description
Cooling Condenser
TTA

120

A

3

00

*

*

123

456

7

8

9 10

11

12

All products are identified by a multiple-character model number that precisely identifies a
particular type of unit. An explanation of the alphanumeric identification code is provided. Its use
will enable the owner/operator, installing contractors, and service engineers to define the
operation, specific components, and other options for any specific unit. When ordering
replacement parts or requesting service, be sure to refer to the specific model number, serial
number, and DL number (if applicable) stamped on the unit nameplate.
D I G I T S 1 - 3 : P r o d u c t Ty p e
TTA = Split System Cooling
DIGITS 4 - 6: Nominal Gross Cooling Capacity (MBh)
090 = 7.5 Tons (60Hz)
120 = 10 Tons (60Hz)
180 = 15 Tons (60Hz)
240 = 20 Tons (60Hz)
DIGIT 7: Major Develop men t Sequence
A = Single Compressor, Single Circuit, R-22
B = Dual Compressor, Dual Circuit, R-22
DIGIT 8: Electrical Characteristics
3 = 208–230/60/3
4 = 460/60/3
D I G I T S 9 - 10 : F a c t o r y I n s t a l l e d O p t i o n s
00 = Packed Stock
D I G I T S 11 : M i n o r D e s i g n S e q u e n c e
* = Current Design Sequence1
D I GI TS 12 : Serv i c e D ig it
* = Current Design Sequence1

1.

6

* = sequential alpha character

SS-PRC037C-EN

General Data
Table 2.

General Data – 7.5 to 20 ton
7.5 Tons
10 Tons
15 Tons
Single Compressor Single Compressor Dual Compressor
TTA090A3, A4
TTA120A3, A4
TTA180B3, B4

20 Tons
Dual Compressor
TTA240B3, B4

Compressor
Type

Scroll

Scroll

Scroll

Scroll

No./Tons

1/6.9

1/8.6

2/6.9

2/8.6

System Data
No. Refrigerant Circuits

1

1

2

2

Suction Line (in.) OD

1.38

1.38

1.38

1.38

Liquid Line (in.) OD

5/8

1/2

1/2

1/2

Outdoor Coil
Type

Lanced

Lanced

Lanced

Lanced

Tube Size (in.) OD

0.38

0.38

0.38

0.38

Face Area (sq ft)

19.2

24.0

24.0

24.0

Rows/FPI (Fins per inch)

2/18

2/18

2/18

2/18

Propeller

Propeller

Propeller

Propeller

1/26

1/28

2/28

2/28

Direct/1

Direct/1

Direct/1

Direct/1
19500

Outdoor Fan
Type
No. Used/Diameter (in.)
Drive Type/No. Speeds
CFM

6530

9600

19500

No. Motor/HP

1/0.5

1/1

2/1

2/1

Motor RPM
Refrigerant Charge (Field
Supplied)

1100

1100

1100

1100

lbs of R-22

17.6

22.5

39.0

43.8

43.54” x 43” x 36.5”

43.5” x 53” x 40.5”

49.5" x 94.8" x 47"

49.5" x 94.8" x 47"

Shipping Dimensions
HxWxD (in.)

SS-PRC037C-EN

7

Performance Data
Table 3.

Gross cooling capacities (MBH) 7.5 tons TTA090A condensing unit only (IP)
Suction Temperature (°F)

Outdoor
Temp (°F)

65

75

85

95

105

115

125

30

35

40

45

50

55

Head Press (psig)

161.3

172.4

178.7

185.3

192.4

199.8

Capacity (Btuh/1000)

76.9

84.9

93.7

102.9

112.5

122.3

Unit Power (kW)

4.9

5.0

5.2

5.3

5.5

5.7

Head Press (psig)

190.9

197.1

203.6

210.4

217.7

225.4

Capacity (Btuh/1000)

73.0

81.0

89.4

98.1

107.2

116.6

Unit Power (kW)

5.3

5.5

5.7

5.8

6.0

6.2

Head Press (psig)

217.8

224.3

231.1

238.3

246.0

254.0

Capacity (Btuh/1000)

69.4

77.0

85.0

93.3

102.0

110.9

Unit Power (kW)

5.9

6.0

6.2

6.4

6.6

6.8

Head Press (psig)

247.6

254.3

261.5

269.0

276.9

285.2

Capacity (Btuh/1000)

65.7

73.0

80.6

88.5

96.7

105.2

Unit Power (kW)

6.4

6.6

6.8

7.0

7.2

7.4

Head Press (psig)

280.1

287.1

294.6

302.4

310.6

319.1

Capacity (Btuh/1000)

61.9

68.9

76.1

83.7

91.5

99.5

Unit Power (kW)

7.1

7.3

7.5

7.7

7.9

8.1

Head Press (psig)

315.3

322.7

330.5

338.6

347.1

355.9

Capacity (Btuh/1000)

58.1

64.7

71.6

78.8

86.2

93.8

Unit Power (kW)

7.8

7.9

8.1

8.3

8.6

8.8

Head Press (psig)

353.4

361.2

369.3

377.7

386.4

395.4

Capacity (Btuh/1000)

54.2

60.5

67.1

73.9

80.9

88.1

Unit Power (kW)

8.5

8.7

8.9

9.1

9.3

9.5

Note: Performance data calculated at 15°F subcooling and 15°F superheat and does not include capacity loss due to refrigerant lines.

Figure 1. TTA090A capacity curves
Capacity Curves - Condensing Unit Only

COMPRESSOR HIGH SUCTION LIMIT

135

INDOOR COIL FROST LIMIT

Gross Cooling Capacity (MBH)

120

105

90

75
65
75
85
95
105
115
125

60

45
25

30

35

40

45

50

55

60

Sa turated Suction Temperature (F)

8

SS-PRC037C-EN

Pe r f o r m a n c e D a t a
Table 4.

Gross cooling capacities (MBH) 10 tons TTA120A condensing unit only (IP)
Suction Temperature (°F)

Outdoor
Temp (°F)

65

75

85

95

105

115

125

30

35

40

45

50

55

Head Press (psig)

161.5

166.6

172.0

177.9

184.0

190.6

Capacity (Btuh/1000)

98.2

108.8

120.0

131.8

144.0

157.0

Unit Power (kW)

7.1

7.3

7.5

7.8

8.0

8.2

Head Press (psig)

185.0

190.2

195.9

201.8

208.2

215.0

Capacity (Btuh/1000)

94.1

104.2

115.1

126.5

138.4

150.9

Unit Power (kW)

7.6

7.8

8.0

8.2

8.5

8.7

Head Press (psig)

210.8

216.2

222.0

228.3

234.9

241.9

Capacity (Btuh/1000)

89.6

99.4

109.8

120.8

132.3

144.3

Unit Power (kW)

8.2

8.4

8.6

8.8

9.1

9.3

Head Press (psig)

239.3

245.0

251.0

257.4

264.2

271.4

Capacity (Btuh/1000)

84.8

94.2

104.2

114.7

125.8

137.3

Unit Power (kW)

8.9

9.1

9.3

9.5

9.7

10.0

Head Press (psig)

270.5

276.4

282.6

289.2

296.2

303.6

Capacity (Btuh/1000)

79.7

88.8

98.3

108.3

118.9

129.9

Unit Power (kW)

9.6

9.9

10.1

10.3

10.5

10.7

Head Press (psig)

304.3

310.4

316.8

323.6

330.7

338.3

Capacity (Btuh/1000)

74.4

83.0

92.1

101.6

111.6

122.1

Unit Power (kW)

10.5

10.7

10.9

11.1

11.4

11.6

Head Press (psig)

340.9

347.2

353.8

360.7

368.0

375.7

Capacity (Btuh/1000)

68.9

77.0

85.6

94.6

104.0

113.9

Unit Power (kW)

11.4

11.6

11.9

12.1

12.3

12.5

Note: Performance data calculated at 15°F subcooling and 15°F superheat and does not include capacity loss due to refrigerant lines.

Figure 2.

TTA120A capacity curves
Capacity Curves - Condensing Unit Only

175

COMPRESSOR HIGH SUCTION LIMIT

160

INDOOR COIL FROST LIMIT

Gross Cooling Capacity (MBH)

145

130

115

100
65
75
85
95
105
115
125

85

70

55
25

30

35

40

45

50

55

60

Sa turated Suction Temperature (F)

SS-PRC037C-EN

9

Pe r f o r m a n c e D a t a
Table 5.

Gross cooling capacities (MBH) 15 tons TTA180B condensing unit only (IP)
Suction Temperature (°F)

Outdoor
Temp (°F)

65

75

85

95

105

115

125

30

35

40

45

50

55

Head Press (psig)

147.1

151.0

155.3

159.8

164.5

169.6

Capacity (Btuh/1000)

151.2

169.1

188.5

208.9

230.0

252.5

Unit Power (kW)

10.1

10.3

10.5

10.7

10.9

11.1

Head Press (psig)

169.9

174.0

178.3

182.9

187.8

192.9

Capacity (Btuh/1000)

143.8

160.9

179.2

198.7

219.1

240.4

Unit Power (kW)

10.9

11.1

11.4

11.6

11.9

12.1

Head Press (psig)

195.2

199.4

203.8

208.5

213.5

218.7

Capacity (Btuh/1000)

136.3

152.6

169.9

188.4

207.9

228.2

Unit Power (kW)

11.9

12.1

12.4

12.6

12.9

13.2

Head Press (psig)

223.1

227.5

232.0

236.9

242.0

247.4

Capacity (Btuh/1000)

128.6

144.2

160.7

178.1

196.7

216.0

Unit Power (kW)

12.9

13.2

13.5

13.7

14.1

14.4

Head Press (psig)

253.8

258.3

263.1

268.1

273.3

278.9

Capacity (Btuh/1000)

120.7

135.6

151.4

167.9

185.4

203.8

Unit Power (kW)

14.1

14.4

14.7

15.0

15.3

15.6

Head Press (psig)

287.3

292.0

296.9

302.0

307.4

313.1

Capacity (Btuh/1000)

112.8

127.0

141.9

157.7

174.2

191.5

Unit Power (kW)

15.4

15.7

15.9

16.2

16.6

16.9

Head Press (psig)

323.7

328.6

333.6

338.9

344.4

350.1

Capacity (Btuh/1000)

104.7

118.2

132.4

147.3

162.9

179.1

Unit Power (kW)

16.8

17.0

17.3

17.6

17.9

18.3

Note: Performance data calculated at 15°F subcooling and 15°F superheat and does not include capacity loss due to refrigerant lines.

Figure 3.

TTA180B capacity curves
Capacity Curves - Condensing Unit Only

290

COMPRESSOR HIGH SUCTION LIMIT

275
260

230

INDOOR COIL FROST LIMIT

Gross Cooling Capacity (MBH)

245

215
200
185
170
155

65
75
85
95
105
115
125

140
125
110
95
80
25

30

35

40

45

50

55

60

Sa turated Suction Temperature (F)

10

SS-PRC037C-EN

Pe r f o r m a n c e D a t a
Table 6.

Gross cooling capacities (MBH) 20 tons TTA240B condensing unit only (IP)
Suction Temperature (°F)

Outdoor
Temp (°F)

65

75

85

95

105

115

125

30

35

40

45

50

55

Head Press (psig)

161.1

166.0

171.2

176.7

182.6

188.8

Capacity (Btuh/1000)

203.6

224.1

245.9

268.8

293.0

318.3

Unit Power (kW)

14.2

14.6

15.1

15.5

16.0

16.5

Head Press (psig)

185.1

190.2

195.6

201.4

207.4

213.8

Capacity (Btuh/1000)

196.0

215.9

237.1

259.4

282.8

307.3

Unit Power (kW)

15.3

15.7

16.1

16.5

17.0

17.5

Head Press (psig)

211.4

216.8

222.5

228.5

234.9

241.6

Capacity (Btuh/1000)

187.5

206.9

227.3

248.9

271.6

295.3

Unit Power (kW)

16.5

16.9

17.3

17.7

18.2

18.7

Head Press (psig)

240.6

246.2

252.1

258.4

265.0

271.9

Capacity (Btuh/1000)

178.5

197.1

216.8

237.6

259.4

282.2

Unit Power (kW)

17.9

18.3

18.7

19.1

19.6

20.0

Head Press (psig)

272.3

278.2

284.4

290.9

297.7

304.9

Capacity (Btuh/1000)

168.7

186.6

205.5

225.4

246.3

268.2

Unit Power (kW)

19.5

19.9

20.3

20.7

21.1

21.6

Head Press (psig)

306.8

312.9

319.3

326.0

333.1

340.4

Capacity (Btuh/1000)

158.5

175.5

193.5

212.5

232.5

253.3

Unit Power (kW)

21.2

21.6

22.0

22.4

22.9

23.3

Head Press (psig)

344.0

350.3

356.9

363.9

371.1

378.7

Capacity (Btuh/1000)

147.8

163.9

181.0

199.0

217.9

237.7

Unit Power (kW)

23.1

23.5

23.9

24.4

24.8

25.2

Note: Performance data calculated at 15°F subcooling and 15°F superheat and does not include capacity loss due to refrigerant lines.

Figure 4.

TTA240B capacity curves
Capacity Curves - Condensing Unit Only

350
335
COMPRESSOR HIGH SUCTION LIMIT

320

290

INDOOR COIL FROST LIMIT

Gross Cooling Capacity (MBH)

305

275
260
245
230
215
200

65
75
85
95
105
115
125

185
170
155
140
125
25

30

35

40

45

50

55

60

Sa turated Suction Temperature (F)

SS-PRC037C-EN

11

Electrical Data
Table 7. Electrical characteristics — compressor and condenser fan motors — 60 Hz
Compressor Motor
Unit Model
Tons
Number

7.5

10

15

20

Condenser Fan Motor

Amps
No.

Volts

Phase

RLA

LRA

(Ea.)

(Ea.)

Amps
No.

Volts

Phase

FLA

LRA

(Ea.)

(Ea.)

TTA090A3

1

208-230

3

22.4

164

1

208-230

1

3.1

8.1

TTA090A4

1

460

3

10.9

100

1

460

1

1.6

3.8

TTA120A3

1

208-230

3

30.1

225

1

208-230

1

5.0

14.4

TTA120A4

1

460

3

15.5

114

1

460

1

2.5

5.8

TTA180B3

2

208-230

3

22.4

164

2

208-230

2

5.0

14.4

TTA180B4

2

460

3

10.9

100

2

460

2

2.5

5.8

TTA240B3

2

208-230

3

30.1

225

2

208-230

2

5.0

14.4

TTA240B4

2

460

3

15.5

114

2

460

2

2.5

5.8

Note: Electrical characteristics reflect nameplate values and are calculated in accordance with cULus and ARI
specifications.

Table 8.
Tons

Unit wiring — condensing units — 60 Hz
Unit Model
Number

Unit Operating
Voltage Range

Minimum Circuit
Ampacity

Maximum Fuse or HACR
Circuit Breaker Size
45

TTA090A3

187-253

31.1

TTA090A4

414-506

15.2

25

10

TTA120A3

187-253

42.6

60

TTA120A4

414-506

21.9

30

15

TTA180B3

187-253

60.4

80

TTA180B4

414-506

29.5

40

TTA240B3

187-253

77.7

100

TTA240B4

414-506

39.9

50

7.5

20

Note: HACR type circuit breaker per NEC.

12

SS-PRC037C-EN

Dimensional Data
Cooling Condenser
Figure 5.

7.5 ton condensing unit, single compressor
SEE NOTE 3
NOTES :
1. ACCES S OP ENING IS FOR FIELD INS TALLED BAYLOAM ACCES S ORY.
2. MINIMUM CLEARANCE FOR P ROP ER OP ERATION IS 36" (914.4) FROM
W ALLS , S HRUBBERY, P RIVACY FENCES ETC. MINIMUM CLEARANCE
B ETWEEN ADJ ACENT UNITS IS 72" (1828.8). RECOMMENDED S ERVICE
C LEARANCE 48" (1219. 2)
3. TOP DIS CHARGE AREA S HOULD BE UNRES TRICTED FOR 100" (2540)
MINIMUM. UNIT S HOULD BE P LACED S O ROOF RUN-OFF WATER DOES
NOT P OUR DIRECTLY ON UNIT
4. OUTDOOR AIR TEMP ERATURE S ENS OR OP ENING (DO NOT BLOCK OP ENING)

SERVICE PANEL

SEE NOTE 4
HAIL GUARD
(OP TIONAL)

S ERVICE CLEARANCE
48" (1219.2) (S EE NOTE 2
FOR CLEARANCE)
HAIL GUARD
(OP TIONAL)

S EE NOTE 1
35 15/1 6"
(912 .8)
WITH HAIL GUARD
33 7/8"
(86 0.4)

LINE VOLTAGE
CONT ROL WIRING

REFRIGERANT ACCES S

39 3/16"
(995.3)

SER VICE P ANEL
34 1/8" (866.8)

26 15/16"
(684.2)

29 13/16"
(757.2)
16 7/16"
(417.5)

14 3/8"
(365.1)
1/16"
(1.59)

7 15/16"
(201.6)

6" (152.4)
6" (152.4)

SUCTION LINE

1 7/8"
(47.6)

21 11 /16"
(55 0.9)

LIQUID LINE

2 7/8"
(73)

33 13/1 6"
(858 .8)

40 15/16"
(1039.8)
41 15/16"
(1065. 2)
WITH HAIL GUARD

SERVIC E P ANEL S IDE
3" (76. 2)

40 3/4"
(1035) 34 3/4"
(882.6)

7/16" (11.11) DIA. IS OLATOR MOUNTING
HOLES (OUTS IDE HOLES - 4 P LACES )

BOTTOM
OF UNIT

4 3/16"
(106.36)
1 13/16"
(46)

SS-PRC037C-EN

27 11/ 16"
(703.3 )

2 5/16"
(58.7)

13

Dimensional Data
Figure 6.

10 ton condensing unit, single compressor
SEE NOTE 3

NOTES :
1. ACCES S OP ENING IS FOR FIELD INS TALLED BAYLOAM ACCES S ORY.
2. MINIMUM CLEARANCE FOR P ROP ER OP ERATION IS 36" (914.4) FROM
WALLS , S HRUBBERY, P RIVACY FENCES ETC. MINIMUM CLEARANCE
B ETWEEN ADJ ACENT UNITS IS 72" (1828.8). RECOMMENDED S ERVICE
C LEARANCE 48" (1219.2)
3. TOP DIS CHARGE AREA S HOULD BE UNRES TRICTED FOR 100" (2540)
MINIMUM. UNIT S HOULD BE P LACED S O ROOF RUN-OFF WATER DOES
NOT P OUR DIRECTLY ON UNIT
4. OUTDOOR AIR TEMP ERATURE S ENS OR OP ENING (DO NOT BLOCK OP ENING)

SERVICE PANEL

HAIL GUARD
(OP TIONAL)

SEE NOTE 4

S ERVICE CLEARANCE
48" (1219.2) (S EE NOTE 2
FOR CLEARANCE
S EE NOTE 1

4 1/4"
(108)

HAIL GUARD
(OP TIONAL)

39 15 /16"
(1014 .4)
WITH HAIL GUARD
1 1/4"
(31.7)

REFRIGERANT ACCES S

37 15/1 6"
(963 .6)

LINE VOLTAGE
CONTROL WIRING

39 1/8"
(993.8)

SER VICE P ANEL
34 1/16" (865.2)
29 3/4"
(755.6)

26 7/8"
(682.6)
14 5/16"
(363.5)

7 1/2" 8 1/4"
(190.5) (209.5)
1/16"
(1.6)

SUCTION LINE

25 11/1 6"
(652 .5)

6"
(152. 4)

1 15/16" (49.2)
LIQUID LINE
4 15/16"
(125.4)

6"
(152. 4)

1 7/8"
(47.6)
2 7/8" (73)
50 15/16"
(1294)
51 15/16"
(1319.2)
WITH HAIL GUARD

37 11/1 6"
(957 .3)

SERVICE P ANEL S IDE
7/16" (11.1) DIA. IS OLATOR MOUNTING
HOLES (OUTS IDE HOLES - 4 P LACES )

3" (76. 2)

50 3/4"
(1289)

44 3/4"
(1136.6)

BOTTOM
OF UNIT

3 13/16"
(96.8)
2 3/16"
(55.6)

14

31 11/1 6"
(804.9)

1 11/16"
(42.9)

SS-PRC037C-EN

Dimensional Data
Figure 7. 15-20 ton condensing unit, dual compressor

SEE NOTE 2

NOTES :
1. MINIMUM CLEARANCE FOR P ROP ER OP ERATION IS 36" (914.4) FROM
WALLS , S HRUBBERY, P RIVACY FENCES ETC. MINIMUM CLEARANCE
B ETWEEN ADJ ACENT UNITS IS 72" (1828.8). RECOMMENDED S ERVICE
C LEARANCE 48" (1219.2)
2. TOP DIS CHARGE AREA S HOULD BE UNRES TRICTED FOR 100" (2540)
MINIMUM. UNIT S HOULD BE P LACED S O ROOF RUN-OFF WATER DOES
NOT P OUR DIRECTLY ON UNIT
3. OUTDOOR AIR TEMP ERATURE S ENS OR OP ENING (DO NOT BLOCK OP ENING)

HAIL GUARD
(OP TIONAL)
SEE NOTE 3

S ERVICE CLEARANCE
48" (1219.2) (S EE NOTE 1
FOR CLEARANCE)

SERVICE PANEL

DETAIL A

46"
(1168.4)
WITH HAIL GUARD

95 7/16"
(2424)
WITH HAIL GUARD
41 7/16"
(1052.5)

44"
(1117. 6)
HAIL GUARD
(OP TIONAL)

HAIL GUARD
(OP TIONAL)

45 1/8"
(1146.2)

SER VICE
P ANEL

3 3/8"
(85.7)
6 5/8"
(168.3)

1/16"
(1.6)

3/16"
(4.8)
41 3/8"
(1051)

9"
(228.6)

93 5/16"
(2370.1)

25 11/16"
(652.5)

9"
(228. 6)

9 1/4" (235)
6 13/16" (173)
1 3/16" (30.2)

7/16" (11.1) DIA. ISOLATOR MOUNTING
HOLES (OUTS IDE HOLES - 4 P LACES )

LINE VOLTAGE

CONTROL
WIRING

SERVICE PANEL SIDE
S UCTION LINE
REFRIGERANT ACCES S
39 7/8"
(1012.8)
BOTTOM OF UNIT
36 7/8"
(936.6)

3" (76. 2)
87"
(2210)
93"
(2362.2)

2 3/16" 6 13/16"
(55.6) (173)

41 1/ 2"
(105 4)

41 5/8"
(1057.3)

18 3/4"
(476.2) 14 5/8"
(371.5)
12 9/16"
(319.1)
5 9/16"
4 3/8"
(141.3)
(111.1)
S UCTION LINE

LIQUID LINES

6 5/16" (160.3)
3 11/16" (93.7)
15/16" (23.8)

FRO NT DETAIL A
DIMENS IONAL DETAIL

SS-PRC037C-EN

15

Weights
Cooling Condenser
Table 9.

TTA unit and corner weights — lbs (60 Hz)

Tons

Model No.

Shipping Max
(lbs)

Net Max (lbs)

7.5

TTA090A

363

10

TTA120A

15

TTA180B

20

TTA240B

Corner Weights
1

2

3

4

298

84

89

44

81

467

395

133

103

70

89

850

723

207

204

151

161

970

837

262

240

164

171

Figure 9. TTA180B, 240B

Figure 8. TTA090A, 120A

#4

#3

#4

#1

#1
#3

#2
S ER
AC C VIC E
ES S

#2
S ER
AC C VIC E
ES S

S ER
AC C VIC E
ES S

LIFTING HOLES
(BOTH S IDES )

LIFTING HOLES (BOTH S IDES )

Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in
creating and sustaining safe, comfortable and energy efficient environments, Trane offers a broad portfolio of advanced
controls and HVAC systems, comprehensive building services, and parts. For more information, visit www.Trane.com.
Trane has a policy of continuous product and product data improvements and reserves the right to change design and specifications without notice.
©2014 Trane

All rights reserved

SS-PRC037C-EN 19 May 2014

We are committed to using environmentally

Supersedes SS-PRC037-EN (July 2012)

conscious print practices that reduce waste.



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : Yes
XMP Toolkit                     : Adobe XMP Core 4.2.1-c041 52.342996, 2008/05/07-20:48:00
Instance ID                     : uuid:77a0b494-a765-47fc-ba51-cf9018a2e14f
Document ID                     : uuid:16D9A8FF-DCE3-FF32-897F-C2898FDAEFA9
Modify Date                     : 2014:08:18 12:13:17-05:00
Metadata Date                   : 2014:08:18 12:13:17-05:00
Create Date                     : 2014:05:19 15:04:40-05:00
Creator Tool                    : Arbortext Editor with Styler
Producer                        : PDFlib+PDI 8.0.5p2 (C++/Win32)
Keywords                        : TTA; R-22; R-22 dry charge; Odyssey
Prod                            : 
Hist model                      : 
Cur flag                        : 
Date published                  : 19 May 2014
Lit order nbr                   : SS-PRC037C
Config File                     : C:\Users\lahhf\Documents\Arbortext\Projects\Eclipse_Workspace\CCMS_DEVELOPMENT\Arbortext_PE_6.0\app\low-res.3sppdf
Stylesheet                      : C:\Users\lahhf\Documents\Arbortext\Projects\Eclipse_Workspace\CCMS_DEVELOPMENT\Arbortext_PE_6.0\application\com.ingersollrand.sma\doctypes\servicemanual\servicemanual.style
PTC Arbortext Build             : R60M110-1031
EP Sprocessor                   : PStill version 1.78.16
Print Engine                    : Arbortext Advanced Print Publisher 11.0.3157/W Library
Marked                          : True
Startup Profile                 : Print
Format                          : application/pdf
Title                           : Odyssey R22 Dry Charge Product Catalog for Cooling Condenser — 7.5, 10, 15 and 20 Tons — 60 Hz
Subject                         : TTA, R-22, R-22 dry charge, Odyssey
Rights                          : ©2014 Trane All rights reserved.
Page Layout                     : SinglePage
Page Count                      : 16
Creator                         : Arbortext Editor with Styler
Cur Flag                        : 
Date Published                  : 19 May 2014
Hist Model                      : 
Lit Order Nbr                   : SS-PRC037C
EXIF Metadata provided by EXIF.tools

Navigation menu