Trane Ptac Svx01C En Users Manual
ptacsvx01cen 7683f12c-60ab-4bef-9b28-519a96997237 Trane Air Conditioner PTAC-SVX01C-EN User Guide |
2015-01-21
: Trane Trane-Ptac-Svx01C-En-Users-Manual-236119 trane-ptac-svx01c-en-users-manual-236119 trane pdf
Open the PDF directly: View PDF .
Page Count: 52
- Packaged Terminal Air Conditioner
- Table of Contents
- Model Number Description
- General Information
- Pre-Installation
- Unit Dimensions
- Electrical Requirements
- Installation Procedure
- Step 1. Remove rear closure panel from wall sleeve.
- Step 2. Install drain kit in wall sleeve.
- Step 3. Install outdoor air grille in wall sleeve.
- Step 4. Install wall sleeve in wall opening.
- 5. Install unit chassis in wall sleeve.
- Step 6. Install unit power supply.
- Step 7. Install the unit controls.
- Step 8. Configure the display module settings
- Field commissioning support
- Step 9. Programmable Settings
- Energy Management System
- Installation
- Sequence of Operation
- Automatic 3-minute Compressor Lockout
- Automatic 2nd Stage Electric Heat (PTHE only)
- Indoor Room Freeze Protection
- Random Restart Function
- Door Switch Occupancy Sensor
- Remote Thermostat Control
- Setpoint Limiting
- Active Defrost (PTHEs only)
- Remote Thermostat Operation
- Mode Button Operation
- Fan Operation
- Front Desk Control (FD1, FD2 Inputs)
- Remote Fan Operation
- Vent Control
- Air Discharge Grille
- Sequence of Operation
- Operation
- Maintenance Procedures
- Refrigeration System Service
- Brazing
- Evacuation
- Cooling Performance Test
- Ground Test
- Indoor Coil and Air Thermistors
- Outdoor Coil and Air Thermistors
- Heater Assembly with Power OFF to the Unit and Heater
- Reversing Valve
- Component Replacement
- Temperature-Actuated Drain Valve (model PTHE Only)
- Unit Disassembly Procedures
- Power Cord Removal
- Power cord Installation
- Capacitor Removal
- Heater Assembly Removal
- Removing the Indoor Coil and Indoor Air Thermistors
- Removing the Outdoor Coil and Outdoor Air Thermistors
- Indoor Fan and Motor
- Outdoor Fan and Motor
- Control Board Replacement Procedure
- Maintenance
- Troubleshooting
- Wiring Diagram
- Warranty
Installation,
Operation, and
Maintenance
September 2006 PTAC-SVX01C-EN
PTEE070/PTHE070 (7,000 Btuh)
PTEE090/PTHE 090 (9,000 Btuh)
PTEE120/PTHE120 (12,000 Btuh)
PTEE150/PTHE150 (15,000 Btuh)
Packaged Terminal Air
Conditioner
2PTAC-SVX01C-EN
Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Model Number Description . . . . . . . . . . . . . . . . . . . . . . . . .3
General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Pre-Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Ta b l e 1. Minimum interior and exterior projections . . . . . . . .6
Table 2. Minimum clearances and projections . . . . . . . . . . .7
Receiving and Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Energy Management System . . . . . . . . . . . . . . . . . . . . . . 19
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Refrigeration System Service . . . . . . . . . . . . . . . . . . . . . . 31
Brazing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Evacuation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Cooling Performance Test . . . . . . . . . . . . . . . . . . . . . . . . . 35
Ground Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Table 27. Thermistor indoor coil resistance . . . . . . . . . . . . 38
Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Table 28. Diagnostic codes . . . . . . . . . . . . . . . . . . . . . . . 41
Table 29. Latching diagnostics, reset required . . . . . . . . . 41
Table 30. Automatically resetting diagnostics . . . . . . . . . . 41
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Full 1st Year Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Full 2nd - 5th Sealed System Warranty . . . . . . . . . . . . . . . 50
Limited 2nd through 5th Year Functional Parts Warranty 50
Table of Contents
PTAC-SVX01C-EN 3
*All heat pump units must have electric heat.
Digit 8—Main Power Supply
1 = 230-208V/60Hz/1phase
2 = 265V/60Hz/1phase
4 = 115V/60Hz/1phase (Hydronic Only)
Digit 9 —Electric Heat Capacity*
U = Universal Heater (Heater kW determined by
power cord, see Accessories Section)
W = Hydronic (ships with no front cover & no
electric heater)
Digit 10 — Unit Features
A = Standard
C = Corrosion Resistant
D = Internal Condensate Pump
Digit 11—Minor Design Sequence
Model Number Description
P T E E 0 9 0 1 * A A
1 2 3 4 5 6 7 8 9 10 11
Each Packaged Terminal Air
Conditioner/Heat Pump is assigned a
multiple-character alphanumeric
model number that precisely
identifies each unit.
An explanation of the identification
code that appears on the unit
nameplate is shown below.
The model number helps owner/
operator, installing contractors, and
service technicians to define the
operation, components and options
for a specific unit.
Refer to the model number printed
on the equipment nameplate when
ordering replacement parts or
requesting service.
Front and discharge grille
Electric heater
Indoor Fan
Display Module
Outdoor fan
Wall sleeve
Outdoor grille
Outdoor coil
Rotary compressor
Power cord coverplate (not shown)
Power cord
Control box
Indoor coil
Digits 1, 2—Packaged Terminal Air Conditioner
Digit 3—Product Type
E = Air Conditioner with auxiliary heat
H= Heat Pump
Digit 4—Development Sequence
E = Fifth Development Series
Digit 5, 6, 7—Unit Cooling Capacity
070 = 7,000 Btu
090 = 9,000 Btu
120 = 12,000 Btu
150 = 15,000 Btu
General Information
© 2005 American Standard Inc. All rights reserved PTAC-SVX01C-EN
NOTICE:
Warnings and Cautions appear in
appropriate sections throughout this
manual. Read these carefully.
WARNING
Indicates a potentially hazardous
situation which, if not avoided, could
result in death or serious injury.
CAUTION
Indicates a potentially hazardous
situation which, if not avoided, may
result in minor or moderate injury. It
may also be used to alert against
unsafe practices.
CAUTION
Indicates a situation that may result
in equipment or property-damage-
only accidents.
Overview of Manual
Note: One copy of this document
ships with each unit and is
customer property. It must be
retained by the customer.
This booklet describes proper
installation, operation, and
maintenance procedures for PTACs.
By carefully reviewing the
information within this manual and
following the instructions, the risk of
improper operation and/or
component damage will be
minimized.
It is important that periodic
maintenance be performed to help
assure trouble free operation. A
maintenance schedule is provided at
the end of this manual. Should
equipment failure occur, contact a
service organization with qualified,
experienced HVAC technicians to
properly diagnose and repair this
equipment.
Important
Environmental Concerns!
Scientific research has shown that
certain man-made chemicals can
affect the earth’s naturally occurring
stratospheric ozone layer when
released to the atmosphere.
In particular, several of the identified
chemicals that may affect the ozone
layer are refrigerants that contain
Chlorine, Fluorine and Carbon (CFCs)
and those containing Hydrogen,
Chlorine, Fluorine and Carbon
(HCFCs).
Not all refrigerants containing these
compounds have the same potential
impact to the environment.
The manufacturer advocates the
responsible handling of all
refrigerants—including industry
replacements for CFCs such as
HCFCs and HFCs.
Responsible Refrigerant
Practices!
The manufacturer believes that
responsible refrigerant practices are
important to the environment, our
customers, and the air conditioning
industry.
All technicians who handle
refrigerants must be certified. The
Federal Clean Air Act (Section 608)
sets forth the requirements for
handling, recovering, recycling and
reclaiming of certain refrigerants and
the equipment that is used in these
service procedures.
In addition, some states or
municipalities may have additional
requirements that must also be
adhered to for responsible
management of refrigerants. Know
the applicable laws and follow them.
WARNING
Hazardous Voltage with
Capacitators!
Disconnect all electric power,
including remote disconnects before
servicing. Follow proper lockout/
tagout procedures to ensure the
power can not be inadvertently
energized. Failure to disconnect
power before servicing could result
in death or serious injury.
Disconnect all electric power,
including remote disconnects and
discharge all motor start/run
capacitors before servicing. Follow
proper lockout/tagout procedures to
ensure the power cannot be
inadvertently energized. Verify with
an appropriate voltmeter that all
capacitors have discharged. Failure
to disconnect power and discharge
capacitors before servicing could
result in death or serious injury.
CAUTION
Use Copper Conductors Only!
Unit terminals are not designed to
accept other types of conductors.
Failure to use copper conductors
may result in equipment damage.
General Information
PTAC-SVX01C-EN 5
General Information
Refrigerant Handling
Procedures
WARNING
Contains Refrigerant!
System contains oil and refrigerant
under high pressure. Recover
refrigerant to relieve pressure before
opening the system. See unit
nameplate for refrigerant type. Do
not use non-approved refrigerants,
refrigerant substitutes, or refrigerant
additives.
Failure to follow proper procedures
or the use of non-approved
refrigerants, refrigerant substitutes,
or refrigerant additives could result
in death or serious injury or
equipment damage.
Environmental Accountability
Policy
The manufacturer urges that all
HVAC servicers make every effort to
eliminate, if possible, or vigorously
reduce the emission of CFC, HCFC,
and HFC refrigerants to the
atmosphere. Always act in a
responsible manner to conserve
refrigerants for continued usage
even when acceptable alternatives
are available.
Recover and Recycle
Refrigerants
Never release refrigerant to the
atmosphere!
Always recover and/or recycle
refrigerant for reuse, reprocessing
(reclaimed), or properly dispose if
removing from equipment.
Always determine the recycle or
reclaim requirements of the
refrigerant before beginning the
recovery procedure.
Obtain a chemical analysis of the
refrigerant if necessary.
Questions about recovered
refrigerant and acceptable refrigerant
quality standards are addressed in
ARI Standard 700.
Refrigerant Handling and
Safety
Consult the manufacturer’s material
safety data sheet (MSDS) for
information on refrigerant handling
to fully understand health, safety,
storage, handling, and disposal
requirements.
Use only approved containment
vessels and refer to appropriate
safety standards. Comply with all
applicable transportation standards
when shipping refrigerant
containers.
Service Equipment and
Procedures
To minimize refrigerant emissions
while recovering refrigerant, use the
manufacturer’s recommended
recycling equipment per the MSDS.
Use equipment and methods which
will pull the lowest possible system
vacuum while recovering and
condensing refrigerant. Equipment
capable of pulling a vacuum of less
than 1,000 microns (1.0 mm) of
mercury is recommended.
Do not open the unit to the
atmosphere for service work until
refrigerant is fully removed/
recovered.
When leak-testing with trace
refrigerant and nitrogen, use HCFC-
22 (R-22) rather than CFC-12 (R-12) or
any other fully-halogenated
refrigerant.
Be aware of any new leak test
methods which may eliminate
refrigerants as a trace gas.
Perform evacuation prior to charging
with a vacuum pump capable of
pulling a vacuum of 1,000 microns
(1.0 mm) of mercury or less. Let the
unit stand for 12 hours and with the
vacuum not rising above 2,500
microns (2.6 mm) of mercury.
A rise above 2,500 microns (2.5 mm)
of mercury indicates a leak test is
required to locate and repair any
leaks. A leak test is required on any
repaired area.
Charge refrigerant into the
equipment only after equipment
does not leak or contain moisture.
Refer to proper refrigerant charge
requirements in the maintenance
section of this manual to ensure
efficient machine operation.
When charging is complete, purge or
drain charging lines into an approved
refrigerant container.
Seal all used refrigerant containers
with approved closure devices to
prevent unused refrigerant from
escaping to the atmosphere.
Take extra care to properly maintain
all service equipment directly
supporting refrigerant service work
such as gauges, hoses, vacuum
pumps, and recycling equipment.
When cleaning system components
or parts, avoid using CFC-11 (R-11) or
CFC-113 (R-113). Use only cleaning-
solvents that do not have ozone
depletion factors.
Properly dispose of used materials.
Refrigeration system cleanup
methods using filters and driers are
preferred.
Check for leaks when excessive
purge operation is observed.
Keep abreast of unit enhancements,
conversion refrigerants, compatible
parts, and manufacturer’s
recommendations that will reduce
refrigerant emissions and increase
equipment operating efficiencies.
6PTAC-SVX01C-EN
Pre-Installation
Pre-Installation
Considerations
Before beginning installation, make
the following considerations:
1. Verify the wall opening is in the
correct location and the
correct size.
2. Drill mounting holes on both
sides of the wall sleeve, if
equipment requires any of the
following options: subbase,
leveling legs, or hydronic heat
kit.
If dimension A in Figure 2 is at or
near the minimum specified in
Ta b l e 2 , p . 7 , accessory options
should be mounted to the sleeve
prior to installing the sleeve in
the wall. Otherwise, there may
not be enough access room for
the tools used to mount the
accessories to the wall sleeve.
3. If additional wall sleeve support
is required, the leveling leg
accessory kit or a subbase kit
that includes leveling legs can be
used to provide extra support.
4. If installing in a concrete or
masonry wall, you must provide
a lintel in the wall opening for
support. Do not use the wall
sleeve as a lintel.
See Figure 1 for a typical lintel
construction.
5. When installing in walls that are
deeper than 13 1/2 inches, use an
extended wall sleeve. A sleeve
without the proper depth will
require special care to prevent
problems with rain water,
condensate drainage, and intake/
discharge air.
Figure 1. Typical Installation
framing with lintel
Under these circumstances,
careful jobsite analysis and
cautions are required. Consult
your local HVAC representative
before attempting such
installations.
Checklist
The following checklist provides an
overview of the factory-
recommended pre-installation
considerations. Follow the
procedures in this section to ensure
the installation is complete and
adequate for proper unit operation.
Verify this checklist is complete
before beginning unit installation.
• If unit arrives shipped on its side,
do not accept.
• Verify the unit size and tagging
with the unit nameplate to
ensure the correct unit is
received.
• Inspect the unit for possible
shipping damage and make any
necessary claims with the freight
delivery company immediately.
• Verify the installation location is
free of airflow obstructions, such
as curtains, furniture, trees, or
other objects that may block
airflow to and from the unit.
WARNING
Fire Hazard!
Do not use extension cords. Using
extension cords could cause a fire.
• Make provisions for correct
supply power and that the
electrical receptacle is within 52
inches of the lower right corner
of the equipment.
• Ensure the unit wall opening is
level.
• Ensure adequate sealing and
insulation is around the wall
sleeve.
Figure 2. Minimum unit clearance
Table 1. Minimum interior and exterior
projections
Figure 3. Minimum wall opening
dimensions
42 1/2” min.
Finished
Floor
16 1/4” min.
Dimension B
Pre-Installation
PTAC-SVX01C-EN 7
Pre-Installation
Receiving and Handling
Shipping Package
The chassis and the cabinet front
ship in one carton. Accessories ship
separate.
Receiving Checklist
Complete the following checklist
immediately after receiving unit
shipment to detect possible shipping
damage.
• Verify that the unit nameplate
data corresponds to the sales
order and bill of lading (including
electrical data).
• Visually inspect the unit exterior
for physical signs of shipping
damage or material shortages.
• If a unit appears damaged,
inspect it immediately before
accepting the shipment. Remove
access panels and check for
interior component damage.
Make specific notations
concerning the damage on the
freight bill. Do not accept
delivery.
Table 2. Minimum clearances and
projections
Option In. Mm In. Mm In. Mm
Minimum clearances Minimum projection
AB C
Wall sleeve only 3 75 0 0 0 0
Subbase kit 3 75 3 1/4 85 2 3/4 70
Leveling legs kit 3 75 3 75 2 50
Hydronic heat kit(1)
(1) Max height is based on skirt options available.
9 230 2-6”(2)
(2) This dimension can be from 2-6", but if this dimension exceeds 6" an extended standard kick plate is
necessary.
50 -150(3)
(3) This dimension can be from 50-150mm, but if this dimension exceeds 150mm an extended standard kick
plate is necessary.
3-3 1/8(4)
(4) To achieve a flush fit between the hydronic front and the finished wall, dimension "C" must be between
3" and 3-1/8". If this dimension is more than 3-1/8" there will be a gap between the front and the wall.
This gap could permit occupant access to hydronic lines or other dangerous parts.
76-80(5)
(5) To achieve a flush fit between the hydronic front and the finished wall, dimension "C" must be between
76-80mm. If this dimension is more than 80mm there will be a gap between the front and the wall. This
gap could permit occupant access to hydronic lines or other dangerous parts.
Drain kit 3 75 0(6)
(6) If inside mounted then B = 1-1/2 inches
1(7)
(7) If inside mounted then B = 40 mm
00
Hardwire kit 3 75 3 75 0 0
• Report concealed damage to the
freight line within the allotted
time after delivery. Verify with
the carrier what their allotted
time is to submit a claim.
Note: Failure to follow these
procedures may result in no
reimbursement for damages
from the freight company.
• Do not move damaged material
from the receiving location. It is
the receiver’s responsibility to
provide reasonable evidence that
concealed damage did not occur
after delivery.
• Do not continue unpacking the
shipment if it appears damaged.
Retain all packaging. Take photos
of damaged material if possible.
• Notify the carrier’s terminal of the
damage immediately by phone
and mail. Request an immediate
joint inspection of the damage by
the carrier and consignee.
• Notify your HVAC representative
of the damage and arrange for
repair. Have the carrier inspect
the damage before making any
repairs to the unit.
8PTAC-SVX01C-EN
Unit Dimensions
Figure 4. Unit with wall sleeve and subbase accessory
Figure 5. Wall Sleeve
Unit Dimensions
PTAC-SVX01C-EN 9
Unit Dimensions
Figure 6. Top view of the hydronic kit
Figure 7. Hydronic kit front view
Figure 8. Hydronic kit side view
PTAC Wall Sleeve
Air discharge Unit controls
compartment
1“
20-1/4”
16-1/5”
1-1/20”
53-2/3”
PTAC
Air inlet
Steam inlet and outlet connection
(right hand coil connection)
Steam/water
coil position
Hotwater or steam inlet and outlet
connection (left hand coil connection)
Front View
12.62
5.00”
1-3/8” - 1-1/2”
Top of wall sleeve
Hydronic front
Toe plate 0 to 3.0” long
Bottom of wall sleeve
10 PTAC-SVX01C-EN
Installation
WARNING
Live Electrical Components!
During installation, testing, servicing
and troubleshooting of this product,
it may be necessary to work with live
electrical components. Have a
qualified licensed electrician or other
individual who has been properly
trained in handling live electrical
components perform these tasks.
Failure to follow all electrical safety
precautions when exposed to live
electrical components could result in
death or serious injury.
WARNING
Fire Hazard!
Do not use an extension cord with
this unit. Doing so may cause a fire.
CAUTION
Use Copper Conductors Only!
Unit terminals are not designed to
accept other types of conductors.
Failure to use copper conductors
may result in equipment damage.
Electrical Requirements
The PTAC can be powered by a
power cord connected to a receptacle
in the wall or in a subbase. It can also
be connected directly to the building
supply wires with a hard wire kit.
For U.S. approval, 265V units must
have a permanent wiring connection.
This requirement can be met either
by supplying a subbase for
concealed cord connection or by
direct wiring with the hard wire kit.
The power cord measures 60 inches,
with 56 inches usable from the point
where the cord exits the unit cabinet
and the attached plug.
Installation
PTAC-SVX01C-EN 11
Installation
Table 3. Electric heat capacity and electrical data, models PTEE and PTHE(i)
Nominal heating Building circuit requirement
Voltage(ii)
Electric
heater
Size (kW)
# of
stages
Btu/h at
230/208V
Btu/h at
265V
Total
watts(iii)
Unit
total
amps
Minimum
ampacity(iv)
Maximum
protection(v) Plug
230/208 2.0/1.6 1 6,800/
5,500
- 2000/
1600
8.9/7.9 11.4 15 6 - 15 P
230/208 3.0/2.4 1 10,200/
8,200
- 3000/
2400
13.4/11.8 17 20 6 - 20 P
230/208 5.0/4.0 1 17,100/
13,700
- 5000/
4000
22.2/19.7 28 30 6 - 30 P
265 2.0 1 - 6,800 2000 7.7 9.8 15 7 - 20 P
265 3.0 1 - 10,200 3000 11.6 14.7 15 7 - 20 P
265 5.0 1 - 17,100 5000 19.3 24.4 25 7 - 30 P
(i) All heat pumps have electric heat.
(ii) Minimum voltage on 230/208 volt models is 187 volts; maximum is 253 volts. Minimum voltage on 265 volt models is 239 volts; max-
imum is 292 volts.
(iii) Total watts for 7,000 and 9,000 Btu models; add 70 watts for 12,000 and 15,000 Btu models.
(iv) Minimum branch circuit ampacity ratings conform to the National Electric Code. However, local codes should apply.
(v) Overcurrent protection for all units without electric heaters is 15 amps. Overcurrent protection on 265 volt models must be cartridge-
style time delay fuses.
Table 4. Power receptacle configurations
Unit
Voltage
Rating
230/
208
230/
208
230/
208 265 265
Unit plug
Plug amp
rating
15 20 30 15/20 30
NEMA
designation
6-15P 6-20P 6-30P 7-15P/7-20P 7-30P
Receptacle
Receptacle
amp rating
20 20 30 20 30
NEMA
designation
6-20R 6-20R 6-30R 7-20R 7-30R
12 PTAC-SVX01C-EN
Installation
Installation Procedure
WARNING
Hazardous Voltage w/
Capacitors!
Disconnect all electric power,
including remote disconnects before
servicing. Follow proper lockout/
tagout procedures to ensure the
power cannot be inadvertently
energized. For variable frequency
drives or other energy storing
components provided by Trane or
others, refer to the appropriate
manufacturer’s literature for
allowable waiting periods for
discharge of capacitors. Verify with
an appropriate voltmeter that all
capacitors have discharged. Failure
to disconnect power and discharge
capacitors before servicing could
result in death or serious
injury.Install components in this
order.
1. Remove rear closure panel from
wall sleeve.
2. Install drain kit (optional).
3. Install outdoor air grille in wall
sleeve.
Figure 9. Panel wall installation
4. Install wall sleeve in wall
opening.
5. Install unit chassis in wall sleeve.
6. Install unit power supply.
•Power cord
•Hard wire kit
• Subbase kit
• Electrical receptacle
• Power switch
• Cicuit breaker
7. Install unit controls.
• Display module
• Remote wall thermostat
8. Configure display module
settings.
9. Progammable settings.
Step 1. Remove rear closure
panel from wall sleeve.
1. Remove the zigzag folded
cardboard sleeve stiffener. See
Figure 10. Remove the rear
closure panel by folding the four
flaps as indicated in Figure 11
Figure 10. Wall sleeve stiffener
Figure 11. Sleeve rear closure
panel
PTAC-SVX01C-EN 13
Installation
2. Grasping the top and bottom
flanges of the rear closure panel
as shown in Figure 12, the entire
panel is pulled out diagonally
from one side.
Step 2. Install drain kit in wall
sleeve.
Drain kits are available for indoor or
outdoor installation to help
condensate drain from either the
right or left side of the wall sleeve
externally, or from the bottom of the
sleeve internally.
Note: For installation procedures,
please refer to the Installation
Guide that accompanied the
accessory.
If you do not use the drain kit,
condensate will drain out of the rear
of the wall sleeve. The drain kit must
be installed before the outdoor grille
is installed.
Step 3. Install outdoor air
grille in wall sleeve.
An outdoor air grille directs airflow
for proper unit operation and to
protect the outdoor coil. Install the
grille before installing the chassis.
Outdoor air grille options are either a
stamped grille or an architectural
grille. When replacing an old chassis
with an existing grille, please check
with your HVAC representative to
determine if the new chassis can be
used with the old outdoor grille.
Using the wrong type outdoor grille
can decrease cooling or heating
capacity, increase energy usage, or
shorten compressor life.
Note: For installation procedures,
please refer to the Installation
Guide that accompanied the
accessory.
Figure 12. Pull rear closure panel
out of wall sleeve
Step 4. Install wall sleeve in
wall opening.
For condensate to drain properly
inside the unit, the sleeve must be
installed properly:
• level from right to left
• with a slight downward pitch
from the indoor side to the
outdoor side
Note: If equipment is 230/208 volt,
verify the electrical receptacle
is located within 52 inches of
the sleeve’s right hand corner.
Do not use an extension cord.
Note: For installation procedures,
please refer to the Installation
Guide that accompanied the
accessory.
5. Install unit chassis in wall
sleeve.
WARNING
Fire Hazard!
Do not use an extension cord with
this unit. Doing so may cause a fire.
1. Attach the insulation strip to the
upper rear of the wall sleeve. See
Ta b l e 1 3 . If using an extended
wall sleeve, attach the insulation
strip between the two baffles,
touching the baffle surface facing
towards the front.
2. Remove the cabinet front from
the chassis by pulling the bottom
of the cabinet front away from
the chassis until the retaining
clips disengage.
3. If using a subbase, be sure the
right-hand subbase cover is
removed before installing the
chassis in the wall sleeve.
Figure 13. Insulation strip location
Front 11”
Bottom
Rear
4. Slide the chassis into the wall
sleeve until the chassis flanges
contact the front edge of the wall
sleeve. See Figure 14.
5. Secure the chassis to the wall
sleeve using three screws on
each side of the chassis to ensure
a proper seal between the
chassis and the wall sleeve . The
screws are supplied in a plastic
bag which is attached to the
power cord. See Figure 15.
6. Verify the indoor and outdoor
grilles are free of airflow
obstructions.
7. Make the power supply
connections as detailed in the
next step.
Step 6. Install unit power
supply.
Note: For installation procedures,
please refer to the Installation
Guide that accompanied the
accessory.
Figure 14. Slide unit chassis into
the wall sleeve
Figure 15. Secure chassis to wall
sleeve
14 PTAC-SVX01C-EN
Installation
1. All units required either a power cord or hard wire kit to power the unit
2. The Hydronic chassis "W" ships with no electric heat
3. All Hydronic Chassis "W" units required a power cord
4. All 265volt Hydronic chassis "W" required subbase, fuses and socket.
Table 5. Unit power supply
Voltage Options Accessory Accessory part number
115V
Option 1.
Required: Universal Power Cord 15
Amp
BAYPCRD007
A field supplied 115 volt 15 amp receptacle is mounted
in the building floor or wall. A Trane 115 volt 15 amp
power cord BAYPCRD007 is connected to the PTAC and
plugged into the receptacle.
Option 2.
Required: Universal Power Cord 15
Amp
BAYPCRD007
Universal Subbase BAYSUB001
A Trane subbase BAYSUB001 is attached to the wall
sleeve. A field supplied 115 volt 15 amp receptacle is
mounted into the subbase. A Trane 115 volt 15 amp
power cord BAYPCRD007 is connected to the PTAC and
plugged into the receptacle
Option 3. Required: Hard Wire Kit BAYHWRK001
Connector for Hardwire
Kit for 15 Amp
BAYCNHK031
A Trane hardwire kit BAYHRK001 is direct wired to the
building power supply and attached to the PTAC. A
Trane connector kit BAYCNHK031 is connected to the
PTAC and connected to the hard wire kit in the unit
mounted junction box
265 V
Option 1. Required: Universal Subbase BAYSUB001
Socket for subbase 20 or
30 Amp
BAYSCKT003, BAYSCKT004
Universal Power Cord
15,20 or 30 Amp
BAYPCRD004, BAYPCRD005,
BAYPCRD006
Fuses 15, 20 or 30 Amp BAYFUSE001, BAYFUSE002,
BAYFUSE003
Optional Power Switch BAYPSW002
Option 2. Required: Hard Wire Kit BAYHWRK001
Connector for Hardwire
Kit for 15, 20 or 30 Amp
BAYCNHK021, BAYCNHK022 ,
BAYCNHK023
Optional Power Switch if 30 Amp BAYPSW002
230/ 208 V
Option 1. Required: Universal Power Cord
15,20 or 30 Amp
BAYPCRD001, BAYPCRD002,
BAYPCRD003
Optional Power Switch BAYPSW002
Option 2. Required: Universal Subbase BAYSUB001
Socket for subbase 20
or 30 Amp
BAYSCKT001, BAYSCKT002
Universal Power Cord
15,20 or 30 Amp
BAYPCRD001, BAYPCRD002,
BAYPCRD003
Optional Circuit Breaker 15, 20 or
30 Amp
BAYCBKR001, BAYCBKR002,
BAYCBKR003
Power Switch BAYPSW002
Option 3. Required: Hard Wire Kit BAYHWRK001
Connector for Hardwire
Kit for 15, 20 or 30 Amp
BAYCNHK011, BAYCNHK012,
BAYCNHK013
Optional Power Switch BAYPSW002
Step 7. Install the unit
controls.
The PTAC controller’s normal
operation can be operated by using
either
• Display module - can be wall-
mounted or unit mounted.
• Remote Class 2 thermostat -
For Remote Class 2 Thermostat
Installation, read installation,
operation, and maintenance booklet
carefully.
Look in Wiring Diagram section for
information on wiring.
If a remote thermostat is connected,
the unit's display will not be present
and the controller's normal space
temperature control functionality is
overridden by the remote device.
When the controller is being directed
by a remote thermostat, the
following inputs/functions are
disabled or not present:
1. User display inputs (setpoint/
mode/fan)
2. Dehumidification
3. Configuration setup (indoor fan,
setpoint limits, EMS offset,
display units)
4. Energy management system
5. Manual Test
Unit functions that remain under
direct supervision of the controller
are:
1. Random Restart
2. Heat Pump OAT switchover
3. Tubing burst protection
4. Room freeze protection
5. Indoor coil freeze protection
6. Defrost control
When connected to a remote
thermostat, the controller interprets
the combination of thermostat inputs
as its operating mode and behaves
accordingly.
It is recommended to use a small
screwdriver to gently pryt the
removable treminal block "TB2" up
and off for easy connection.
PTAC-SVX01C-EN 15
Installation
Note: If using a third party
thermostat to control the
unit, the thermostat must
have a clearly marked OFF
state or position.
Note: It is important to make sure
that the control board’s fuse
is functioning. The specs for
the control board fuse are:
5x20mm, 250V, 315mA, fast
acting. For more inormation
on a blown fuse on the
control board, check the
Troubleshooting section of
this document.
Table 6. Maximum wire length for front
desk switch and remote
control connections
External Interface
Wire
Specification
Size Length
Thermostat
#22 100 ft.
#20 200 ft
#18 300 ft.
Energy mgmt system #20 900 ft.
#18 1500 ft.
Remote fan #20 60 ft.
#18 66 ft.
Display module #20 100 ft.
#18 120 ft.
Table 7. Wiring Voltage
Unit Mode
Voltage at terminal Corresponding
Normal
OperationGH GL W Y O
High Heat Pump 24 0 0 24 0 Heat
PTHE Heat Pump
Auxiliary is Electric
only
Low Heat Pump 0 24 0 24 0 Heat
High Emgcy Heat 24 0 24 0 0 Heat
24 0 24 24 0 Electric Heat Only
Low Emgcy Heat 0 24 24 0 0 Heat
0 24 24 24 0 Electric Heat Only
High Cooling 24 0 0 24 24 Cool
Low Cooling 0 24 0 24 24 Cool
High Fan 24 0 0 0 0 Fan Only
Low Fan 0 24 0 0 0 Fan Only
Off 0 0 0 0 0 Off – no capacity
Notes: In the event that none of the
combinations listed in the table above is
present, the input will be deemed invalid and all
heating, cooling, and fan operation will be
disabled.
PTEE Air Conditioner
(Auxiliary is Electric,
Hot Water, or Steam
High Auxiliary Heat 24 0 24 0 X Heat
Low Auxiliary Heat 0 24 24 0 X Heat
High Cooling 24 0 0 24 X Cool
Low Cooling 0 24 0 24 X Cool
High Fan 24 0 0 0 X Fan Only
Low Fan 0 24 0 0 X Fan Only
Off 0 0 0 0 X Off – no capacity
Table 7. Wiring Voltage
Unit Mode
Voltage at terminal Corresponding
Normal
OperationGH GL W Y O
High Heat Pump 24 0 0 24 0 Heat
16 PTAC-SVX01C-EN
Installation
Notes: EN = Enabled - operations based on
other logic
Notes: N/C = No change from prior state
Step 8. Configure the display
module settings
Indoor Temperature setpoint
The indoor temperature setpoint
buttons tell the unit how warm or
cool the occupant wants the room.
The setpoint is set by pressinging the
up/down buttons on the interface
module. These buttons do not scroll
(i.e. holding the button will not
continue to adjust the setpoint value)
because each adjustment of the
setpoint value requires its own
unique button press.
Default setpoint on first power up:
72°F (22.0°C – closest approximation)
Setpoint resolution: ± 1°F (± 0.5°C)
User Mode Selection
Pressing the MODE button on the
unit tells the unit which mode the
occupant prefers. There are four
modes to choose from.
1. COOL
2. HEAT
3. FAN (fan only)
4. OFF (default for first power up)
Table 8. Output settings
User Mode / Model
ID
Fan
High
ID
Fan
Low
Aux
Heat Comp
Rev
Valve
(PTHE)
OD
Fan
Rmt
Fan
Cond
Pump
(PTHE)
Vent
Door
/Fan
High Heat Pump
(PTHE only)
ON OFF OFF ON OF ON EN EN EN
Low Heat Pump
(PTHE only)
OFF ON OFF ON OFF ON EN EN EN
High Emergency/
Auxiliary Heat
ON OFF ON OFF N/C OFF EN EN EN
Low Emergency/
Auxiliary Heat
OFF ON ON OFF N/C OFF EN EN EN
High Cooling ON OFF OFF ON ON ON EN EN EN
Low Cooling OFF ON OFF ON ON ON EN EN EN
High Fan ON OFF OFF OFF N/C OFF EN EN EN
Low Fan OFF ON OFF OFF N/C OFF EN EN EN
Off OFF OFF OFF OFF N/C OFF OFF EN OFF
Fan Speed Selection
Pressing the FAN button on the
interface module determines fan
speed. There are two fan speeds to
choose from.
1. LOW (default for first power up)
2. HIGH
Field commissioning support
Manual Test Mode
A manual test mode is provided to
allow a field technician to verify
proper output and end device
operation through a predetermined,
timed sequence.
Figure 16. Digital display module
Fan Mode
The sequence will automatically
advance through all outputs and exit
when the sequence has completed; it
is left to the technician to monitor the
status of the end devices during the
test to verify that each operates
properly.
Manual test is initiated by combining
the following conditions:
• User Mode = OFF
• Press and hold MODE &
SETPOINT DOWN for 5 seconds
During the test process, the word
"STEP" and the corresponding step
number will be lighted on the
display. After the final step has been
executed, the controller will exit
Manual test and force the controller
to into a reset.
Manual test mode may be cancelled
by pressing any button on the
display.
Manual test is not available if there is
no interface module, as is in Class 2
control applications.
The test sequence attempts to clear
unit diagnostics and restore normal
unit operation prior to testing the
outputs. If the diagnostics remain
after an attempt to clear them,
manual test may be affected or
disallowed.
Dehumidification
The PTAC controller does not directly
measure room humidity.
The PTAC provides dehumidfication
by combining the following actions
in a predefined sequence.
1. The PTAC subcools the room to a
preset state, a dehumidification
offset below the cooling setpoint.
2. The unit will automatically adjust
the fan speed.
3. When incorporating the vent
door option, the controller will
automatically adjust its position.
PTAC-SVX01C-EN 17
Installation
Step 9. Programmable
Settings
The controller has a total of six (7)
parameters that are user-
configurable:
1. Vent Door Configuration
2. Indoor Fan Cycle configuration
3. Temperature Setpoint Limiting
configuration
4. Energy Management Setpoint
Offset configuration
5. Display Units configuration
6. Indoor Temperature Calibration
7. DH Offset
The interface module texts
“SETTING” and “STEP” provide user
feedback when the unit is in the
configuration mode. The number
directly above the word “STEP”
indicates the configuration step that
is being adjusted. The numbers
above the word “SETTING” (XX.x)
indicate the value of the parameter.
In order for the user to access the
configurable parameters, a digital
display module must be present.
The configuration set-up mode is
entered by pressing and holding the
"MODE" and "FAN" buttons
simultaneously for 5 seconds.
Table 9. Set point configuration
Configuration
step Step description
Configuration
setting Setting description
1 Ventilation Enable 0
1 (default)
Ventilation is disabled
Ventilation is enabled
2 Indoor fan cycle
0 (default) Cycle with compressor
continuously, OFF in OFF mode
ON continuously, HIGH in OFF
mode
1
2
3
Tempe ratu r e
Setpoint Limits
0 (default) cool 50 - 90°F, heat 50 - 90°F
1 cool 55 - 90°F, heat 50 - 85°F
2 cool 60 - 90°F, heat 50 - 80°F
3 cool 65 - 90°F, heat 50 - 75°F
4Energy
Management
Default: 10°F (5.5°C)
Range: 0 to 20°F
(0.0 to 10.0°C)
Resolution: 1.0°F
(0.5°C)
5
Display units 0 (default) IP (English)
1SI (Metric)
6Indoor
Tempe ratu r e
Calibration
Default: 0°F (0.0°C)
Range: -9 to 9°F
(-5.0 to 5.0°C)
Resolution: 1.0°F
(0.5°C)
7 DH offset
Default: 1°F (0.5°C)
Range: 0 to 2°F
(0.0 to 1.0°C)
Resolution 1.0°F Value of zero disables DH.
(0.5°C)
18 PTAC-SVX01C-EN
Installation
1. Ventilation Door Function
The power door works based upon
control logic functions. When the unit
is on, the vent door will open to allow
fresh air to be conditioned before
entering the room. When the unit is
off, the door closes to prevent
unconditioned air from entering the
room.
For more information on vent door
function with dehumidificaiton, refer
to the dehumidification chart.
2. Indoor Fan Cycle set up
The indoor fan can be configured to
provide different types of operation
between its OFF and ON (high/low)
states. This setting is adjustable and
does not force the unit to reset.
3. Temperature Setpoint Limiting
set up
The range of temperature control
setpoints can be limited using this
configuration parameter. After the
controller has determined the
desired user setpoint from the
display, the resulting value is
validated against the setpoint limits.
There are four valid combinations of
heating and cooling setpoint limits:
These set point limits apply to both
the occupied and unoccupied
standby, heating and cooling
setpoints. This setting is adjustable
“on-the-fly” and will not force the
unit into a restart condition.
4. Energy Management Setpoint
Offset set up
The range of the Energy
Management System's effect on
setpoints can be adjusted using this
configuration parameter. This
parameter is adjustable "on-the-fly"
and will not force the controller into a
restart condition. The range and
resolution of available selections is
Range: 0°F to 20°F( 0.0°C to 11.0°C)
Resolution: 1.0°F( 0.5°C)
5. Display Unit set up
The user can change the way the
interface module displays
temperature. The symbols °F and °C
will not be present on the display;
however, the range and precision of
the room temperature and setpoint
values will make the selection
obvious.
6. Indoor temperature calibration
The indoor temperature can be
calibrated to match an independent
reading. The adjustment range is +/-
10.0°F (6°C) with a resolution of 1°F
(0.5°C).
7. Dehumidification Offset
The offset defines the point below
the setpoint where the unit will stop
running the compressor. A DH
display module is required to use this
feature.
The PTAC allows the options of 0°F
(disable), 1°F (default) and 2°F
(optional) for the dehumidification
offset. The dehumidification feature
will be disabled when the
configuration of 0°F is selected.
Last User Setpoint, Mode, and
Fan Selections
The controller saves the last inputs
that the user has chosen 5 seconds
after the user has ceased changing
them. These settings will be used
after the next power cycle or
controller reset.
Operation without configuration
The controller tests the configuration
for validity. If the data is corrupted
the controller will revert to default
values for every parameter. A
diagnostic code will be displayed
when using the default values.
Table 10. Display units
Selection
#
Unit of
Measure
Display
Example
0 IP (English) 77 (DEFAULT)
1SI (Metric)24.5
Table 11. Setpoint limiting
Cooling Setpoint Heating Setpoint
Selection
#Low Limit
High
Limit
Low
Limit High Limit
0 50°F 90°F 50°F 90°F (DEFAULT)
1 55°F 90°F 50°F 85°F
2 60°F 90°F 50°F 80°F
3 65°F 90°F 50°F 75°F
PTAC-SVX01C-EN 19
Installation
Energy Management
System
Occupancy States
The controller is designed to handle
two possible occupancy states:
• occupied
• occupied standby
When the Energy Management
System input is present, it is possible
for the controller to switch between
the two occupancy states.
If the EMS input is not connected, the
controller will always assume the
occupied state.
Occupied state
When the controller is in the
occupied state, the unit runs space
comfort control using the occupied
setpoints. All heating/cooling/
ventilation features are enabled.
Table 12. Indoor fan cycle configuration
Config # Indoor Fan Cycle Mode
Indoor fan will not run when the user mode is OFF. (DEFAULT)
0
Indoor fan will cycle to the user selected speed in conjunction with
the compressor or electric heat during HEAT or COOL
Indoor fan will run continuously at the user selected fan speed
during FAN
EMS has no affect.
1
Indoor fan will normally run continuously at the user selected fan
speed.
Indoor fan will not run when the user mode is OFF.
Indoor fan will cycle in conjunction with the compressor or electric
heat when the EMS is enabled.
2
Indoor fan will normally run continuously at the selected fan
speed.
Indoor fan will run at HIGH speed when the user mode is OFF.
Indoor fan will cycle in conjunction with the compressor or electric
heat when the EMS is enabled.
Table 13. Occupancy arbitration for
energy management
EMS Input State
Controller
Occupancy State
Open or Not Present Occupied
Closed Occupied Standby
Occupied Standby state
When the controller is in occupied
standby state, the unit runs space
comfort control using the occupied
standby setpoints. All heating/
cooling/ventilation features are
enabled. Because the occupied
standby setpoints cover a wider
range than the occupied setpoints
the demand for heating and cooling
the space is reduced.
20 PTAC-SVX01C-EN
Installation
Table 14. PTEE manual test sequence
Step
Indoor
Fan High
Indoor
Fan Low
Remote
Fan
Outdoor
Fan
Condensate
Pump Comp
Reversing
Valve Aux. Heat
Ventilation
Door/Fan
Time in
Step
1 All off Off Off Off Off N/A (Off) Off N/A (Off) Off Off 10 sec
2 Fan high On Off Off Off N/A (Off) Off N/A (Off) Off Off 20 sec
3 Fan Low Off On Off Off N/A (Off) Off N/A (Off) Off Off 20 sec
4 Remote
Fan
Off On On Off N/A (Off) Off N/A (Off) Off Off 20 sec
5 Outdoor
Fan
Off On Off On N/A (Off) Off N/A (Off) Off Off 20 sec
6 Compres
sor
Off On Off On N/A (Off) On N/A (Off) Off Off 60 sec
7 Aux Heat Off On Off OnOff N/A (Off) Off N/A (Off) On Off 60 sec
8Vent
Door
Off On Off OnOff N/A (Off) Off N/A (Off) Off On 20 sec
Exit
Table 15. PTHE manual test sequence
Step
Indoor
Fan High
Indoor
Fan Low
Remote
Fan
Outdoor
Fan
Condensate
Pump Comp
Reversing
Valve
Aux
Heat
Ventilation
Door/Fan
Time in
Step
1 All off Off Off Off Off Off Off Off Off Off 10 sec
2 Fan High On Off Off Off Off Off Off Off Off 20 sec
3 Fan Low Off On Off Off Off Off Off Off Off 20 sec
4 Remote Fan Off On On Off Off Off Off Off Off 20 sec
5 Outdoor Fan Off On Off On Off Off Off Off Off 20 sec
6 Condensate
Pump
Off On Off On On1 Off Off Off Off 20 sec
7 Compressor
on Cooling
Off On Off On Off On OffOn Off Off 60 sec
8 Compressor
Off
Off Off On Off On Off Off OffOn Off 60 sec
9 Compressor
on Heating
Off On Off On Off On OnOff Off Off 60 sec
10 Aux Heat Off On Off OnOff Off Off OnOff On Off 60 sec
11 Vent Door Off On Off OnOff Off Off Off Off On 20 sec
Exit
PTAC-SVX01C-EN 21
Sequence of Operation
Automatic 3-minute
Compressor Lockout
After the compressor cycles off, it
will not restart for three minutes.
This feature prevents the
compressor from short cycling and
extends the overall life.
Automatic 2nd Stage Electric
Heat (PTHE only)
If the room temperature falls to 2.5°F
below the setpoint temperature or
the unit compressor fails, the reverse
cycle heat is shut off and the electric
heat is turned on.
Indoor Room Freeze
Protection
When the unit senses room
temperatures of 40°F or below, the
unit activates the indoor fan motor
and either the electric resistance
heater or the hydronic heater to help
prevent pipes or fixtures from
freezing.
This also overrides the Energy
Management System input for unit
mounted or wall mounted display
modules
Random Restart Function
This function allows random restart
of the PTAC units in the event of a
power outage. The restart delay
reduces the initial inrush current
from the building to help prevent a
second power outage caused by too
much current draw.
The random restart function will
occur after every power up cycle by
delaying the operation of the unit for
0 to 90 seconds. Compressor
minimum off time is enforced after
the random restart function has
completed.
Door Switch Occupancy
Sensor
The PTAC can accommodate a field-
installed door switch and occupancy
sensor to operate the energy
management feature.
Remote Thermostat Control
Each unit can be operated from any
standard 4 or 5-wire, remote-
mounted thermostat. Also, the unit
has a built-in low voltage power
source that can accommodate either
a manual, auto changeover, or
programmable thermostat.
Setpoint Limiting
The setpoint limiting feature reduces
energy costs by controlling the
maximum setpoint in heating and
the minimum setpoint in cooling.
Active Defrost (PTHEs only)
PTACs have an active defrost system
that removes ice build-up on the
outdoor coil, which may occur
during the heat pump cycle.
Remote Thermostat
Operation
The GL, GH, O, W, Y, R, and C
terminals provide control inputs for a
remote wall-mounted thermostat.
The terminals listed control the
operation of the unit when no
display module is used. A display
module will take precedence over
any of these inputs.
Mode Button Operation
OFF - cooling and heating functions
stop.
HEAT - room temperature is
maintained by cycling in heat pump
mode or electric heat. The model
PTHE switches from heat pump
mode to electric heat when the
outdoor air temperature is below
20°F (approximately), or when the
heat pump cannot keep up with the
heating load when using a two-stage
thermostat.
COOL - room temperature is
maintained by cycling the air
conditioner.
FAN - the fan runs at the user
selected speed or runs as otherwise
configured.
Fan Operation
The fan speed may be user selected
as either high or low. Fan cycling
versus continuous is operation
configurable. See section on
configuration for details.
Front Desk Control (FD1, FD2
Inputs)
The energy management input is
used to move the setpoint up in the
case of cooling and down in the case
of heating. This conserves energy
by reducing the demand in the
space.
The energy management input is a
dry contact closure; typically this is
driven from either a occupancy
sensor or a front desk control
system.
Figure 17. Digital display module
Fan Mode
Operation
22 PTAC-SVX01C-EN
Operation
Notes:
1. Connection to R enables input functions W, Y,
GL, GH, O,VT, and/or EN.
2. Connect 24VAC, 3VA maximum Remote Fan
Control Relay to RF and C
Remote Fan Operation
PTACs can operate a remote fan to
provide conditioned air to additional
rooms or areas that are not well
ventilated. The remote fan operates
any time the PTAC indoor fan is
operating.
The remote fan requires a 24 VAC, 3
VA maximum relay that connects to
the control board RF and C terminal
user inputs. The relay and remote fan
are field supplied. Refer to the wiring
diagrams section for wiring details.
Vent Control
Vent control draws fresh air into the
conditioned area to provide
ventilation when the indoor fan is
operating. However, this may
increase heating cooling loads and
operating costs.
To obtain access to the vent control,
remove the cabinet front and locate
the vent control lever on the left side
of the chassis. Push the vent control
lever up to open the vent or down to
close.
The unit ships with the vent door
closed and secured by a screw.
Table 16. User inputs
Input Function
TB1
+Remote display
communications link (+)
-Remote display
communications link (-)
TB2
EN Energy management
system input
VT Ventilation input
O Reversing valve (class 2
thermostat)
GL Low fan speed (class 2
thermostat)
GH High speed fan (class 2
thermostat)
Y Cool (class 2 thermostat)
W Heat (class 2 thermostat)
R 24VAC common1
C Ground2
RF Remote fan relay output
CAUTION
Freezing Temperatures!
Do not allow liquid refrigerant to
contact skin. If it does, treat the
injury similar to frostbite. Slowly
warm the affected area with
lukewarm water and seek immediate
medical attention. Direct contact
with liquid refrigerant may cause
minor or moderate injury.
Air Discharge Grille
The discharge grille can be adjusted
to expel air at either a 15° or 40° (40°
default) angle. Figure 18.
To change the discharge air airflow
angle:
1. Remove the front cabinet.
2. Position the front cabinet so that
the backside is accessible.
3. Remove the four screws which
secure the discharge air grille to
the cabinet front with a phillips-
head screwdriver. See Figure 31.
4. Rotate the grille 180° end-for-
end.
5. Reinstall the screws securing the
discharge air grille to the cabinet
front. Reinstall the cabinet front
on the unit.
Figure 18. Discharge air grille
Screws
PTAC-SVX01C-EN 23
Operation
Notes: Certified in accordance with the Unitary Air-Conditioner Equipment Certification Program, which is based on ARI Standard 310/380.
Table 17. Air conditioner performance data
PTEE 07 PTEE 09 PTEE 12 PTEE 15
Voltage (V) 115 208 230 265 115 208 230 265 115 208 230 265 208 230 265
Cooling data
Cooling
capacity
(Btu/H)
7,200 6,800 7,000 7,300 9,300 8,800 9,000 8,700 12,000 11,600 11,800 11,800 13,700 13,900 14,400
Cooling amps
(A)
5.3 2.9 2.7 2.4 7.3 3.9 3.6 3.1 9.7 5.1 4.8 4.1 6.9 6.4 5.7
EER (Btu/H/
watt)
12.2 12.0 12.0 12.0 11.5 11.4 11.4 11.3 11.2 11.2 11.2 11.3 10.0 10.0 9.8
Moisture
removal
(Pts/h)
1.8 2.1 2.1 2.1 2.2 2.5 2.6 2.6 3.0 3.1 3.1 3.1 4.1 4.1 4.1
Heat pump
heating data
Heating
capacity
(Btu/H) ***** * * * * * * ****
Heating amps
(A)
***** * * * * * * ****
Heating power
(W)
***** * * * * * * ****
COP (W/W) ***** * * * * * * ****
Airflow
Indoor cfm
(wet)
@0.3 esp (hi) 280 225 256 256 325 225 256 256 350 295 325 325 320 350 350
Indoor cfm
(wet)
@0.3 esp (lo) 250 191 225 225 294 191 225 225 320 266 294 294 290 320 320
Indoor cfm
(dry)
@0.3 esp (hi) 312 260 290 290 350 260 290 290 400 320 350 350 365 400 400
Indoor cfm
(dry)
@0.3 esp (lo) 280 235 266 266 323 235 266 266 360 293 323 323 330 360 360
Electric heat
data
Heater size
(kW)
208V *1.6 2.4 * * 1.6 2.4 4.0 *1.6 2.4 4.0 1.6 2.4 4.0
230V *2.0 3.0 * * 2.0 3.0 5.0 *2.0 3.0 5.0 2.0 3.0 5.0
265V *2.0 3.0 * * 2.0 3.0 5.0 *2.0 3.0 5.0 2.0 3.0 5.0
Btu/H
208V *5,500 8,200 * * 5,500 8,200 13,700 *5,500 8,200 13,700 5,500 8,200 13,700
230V *6,800 10,200 * * 6,800 10,200 17,100 *6,800 10,200 17,100 6,800 10,200 17,100
265V *6,800 10,200 * * 6,800 10,200 17,100 *6,800 10,200 17,100 6,800 10,200 17,100
Heating watt
208V *1,600 2,400 * * 1,600 2,400 4,000 *1,600 2,400 4,000 1,600 2,400 4,000
230V *2,000 3,000 * * 2,000 3,000 5,000 *2,000 3,000 5,000 2,000 3,000 5,000
265V *2,000 3,000 * * 2,000 3,000 5,000 *2,000 3,000 5,000 2,000 3,000 5,000
Heating amps
208V *7.9 11.8 * * 7.9 11.8 19.7 *7.9 11.8 19.7 7.9 11.8 19.7
230V *8.9 13.4 * * 8.9 13.4 22.2 *8.9 13.4 22.2 8.9 13.4 22.2
265V *7.7 11.6 * * 7.7 11.6 19.3 *7.7 11.6 19.3 7.7 11.6 19.3
24 PTAC-SVX01C-EN
Operation
Notes: Certified in accordance with the Unitary Air-Conditioner Equipment Certification Program, which is based on ARI Standard 310/380.
Notes: Shaded area is rating ampere
Table 18. Heat pump performance
PTHE 07 PTHE 09 PTHE 12 PTHE 15
Voltage (V) 208 230 265 208 230 265 208 230 265 208 230 265
Cooling data
Cooling
capacity(Btu/H)
7,200 7,400 7,200 8,900 9,100 8,700 11,700 12,000 11,700 13,300 13,600 13,600
Cooling amps
(A)
2.9 2.7 2.3 3.9 3.7 3.1 5.1 4.8 4.2 6.8 6.3 5.5
EER(Btu/H watt) 12.0 12.0 12.0 11.4 11.4 10.8 11.2 11.2 11.0 9.9 9.9 9.9
Moisture
removal (Pts/h)
2.1 2.1 2.1 2.5 2.6 2.6 3.0 3.1 3.1 4.1 4.1 4.1
Heat pump
heating data
Heating capacity
(Btu/H)
5,900 6,100 6,100 7,600 7,800 7,300 9,900 10,100 10,100 12,200 12,500 12,500
Heating amps
(A)
2.6 2.5 2.1 3.4 3.2 2.6 4.3 4.0 3.5 5.8 5.4 4.7
Heating power
(W)
540 560 560 695 715 715 935 955 925 1230 1260 1260
COP (W/W) 3.2 3.2 3.2 3.2 3.2 3.0 3.1 3.1 3.2 2.9 2.9 2.9
Airflow
Indoor cfm (wet)
@0.3 esp (hi)
225 256 256 225 256 256 295 325 325 320 350 350
Indoor cfm (wet)
@0.3 esp (lo)
191 225 225 191 225 225 266 294 294 290 320 320
Indoor cfm (dry)
@0.3 esp (hi)
260 290 290 260 290 290 320 350 350 365 400 400
Indoor cfm (dry)
@0.3 esp (lo)
235 266 266 235 266 266 293 323 323 330 360 360
Electric heat
data
Heater size
(kW)
208V 1.6 2.4 *1.62.44.0 1.6 2.4 4.0 1.6 2.4 4.0
230V 2.0 3.0 *2.03.05.0 2.0 3.0 5.0 2.0 3.0 5.0
265V 2.0 3.0 *2.03.05.0 2.0 3.0 5.0 2.0 3.0 5.0
Btu/H
208V 5,500 8,200 * 5,500 8,200 13,700 5,500 8,200 13,700 5,500 8,200 13,700
230V 6,800 10,200 * 6,800 10,200 17,100 6,800 10,200 17,100 6,800 10,200 17,100
265V 6,800 10,200 * 6,800 10,200 17,100 6,800 10,200 17,100 6,800 10,200 17,100
Heating watt
208V 1,600 2,400 * 1,600 2,400 4,000 1,600 2,400 4,000 1,600 2,400 4,000
230V 2,000 3,000 * 2,000 3,000 5,000 2,000 3,000 5,000 2,000 3,000 5,000
265V 2,000 3,000 * 2,000 3,000 5,000 2,000 3,000 5,000 2,000 3,000 5,000
Heating amps
208V 7.9 11.8 * 7.9 11.8 19.7 7.9 11.8 19.7 7.9 11.8 19.7
230V 8.9 13.4 * 8.9 13.4 22.2 8.9 13.4 22.2 8.9 13.4 22.2
265V 7.7 11.6 * 7.7 11.6 19.3 7.7 11.6 19.3 7.7 11.6 19.3
PTAC-SVX01C-EN 25
Operation
Table 19. Cooling temperature change - air conditioners
Room
air dry
bulb
Room air wet
bulb
PTEE0701 PTEE0702 PTEE0901 PTEE0902 PTEE1201 PTEE1202 PTEE1501 PTEE1502
Temperature across
indoor coil (∆ T)
Temperature across
indoor coil (∆ T)
Temperature across
indoor coil (∆ T)
Temperature across
indoor coil (∆ T)
MinMaxMinMaxMinMaxMinMax
Rating Btu/H 7200 7600 8800 9000 11700 12000 14100 14300
Rating cfm 230 260 240 270 300 330 315 355
90
85 13261514
80 8 1311149 138 12
75 19 22 19 22 18 22 16 20
70 30 33 28 30 26 30 25 27
85
80 4 9 7 11 5 10 5 8
75 14 19 15 18 13 18 12 16
70 23 27 23 25 21 25 20 23
65 34 36 31 33 29 33 28 30
80
75 9 1411149 138 12
70 18 21 18 20 15 20 15 18
65 26 29 24 27 23 26 21 24
60 35 36 32 33 29 33 29 30
75
70 12 16 13 16 10 15 10 14
65 18 22 18 21 15 20 15 19
60 25 28 23 26 21 25 20 24
55 31 34 28 31 26 30 26 28
70
65 12 15 12 14 9 13 9 13
60 17 20 16 18 13 17 13 17
55 22 24 20 22 18 21 17 21
Table 20. Cooling temperature change - heat pumps
Room
airdry
bulb
Room air wet
bulb
PTHE0701 PTHE0702 PTHE0901 PTHE0902 PTHE1201 PTHE1202 PTHE1501 PTHE1502
Temperature across
indoor coil (∆ T)
Temperature
acrossndoor coil (∆ T)
Temperature across
indoor coil (∆ T)
Temperature across
indoor coil (∆ T)
Min Max Min Max Min Max Min Max
rating Btu/H 7300 7600 9000 9300 11800 12000 14000 14600
rating cfm 195 225 240 270 315 355 315 355
90
85 1 3 2 6 1 5 1 4
80 8 13 11 1510138 12
75 19 22 19 22 18 22 17 20
70 30 33 29 30 26 30 25 28
85
80 4 9 7 11 5 10 5 9
75 14 19 15 18 14 18 12 16
70 23 27 23 25 21 25 21 23
65 33 36 31 33 30 33 28 31
80
75 9 14 11 1510138 12
70 18 21 18 20 16 20 16 18
65 26 29 24 27 23 26 22 25
60 35 36 32 33 30 33 29 31
26 PTAC-SVX01C-EN
Operation
Notes: Shaded area is rating ampere
75
70 12 16 13 16 11 15 10 14
65 18 22 18 21 16 20 16 19
60 24 28 23 26 21 25 21 24
55 31 34 29 31 26 30 26 29
70
65 12 15 12 15 10 13 9 13
60 17 20 16 18 14 17 13 17
55 22 24 20 22 18 21 18 21
Table 21. Cooling amperage — air conditioners
Condenser
inlet air
temp.
PTEE0701 PTEE0702 PTEE0901 PTEE0902 PTEE1201 PTEE1202 PTEE1501 PTEE1502
Min Max Min Max Min Max Min Max Min Max Min Max Min Max Min Max
2.6 2.9 2.4 2.4 3.6 3.9 3.2 3.2 4.8 5.2 4.2 4.2 6.5 7.1 5.7 5.7
100 2.6 2.9 2.4 2.6 3.4 4.0 2.9 3.1 5.6 5.6 3.9 4.3 6.6 8.0 5.6 6.2
95 2.4 2.8 2.3 2.5 3.2 3.8 2.7 3.0 5.4 5.3 3.7 4.1 6.2 7.6 5.3 5.9
90 2.3 2.7 2.2 2.4 3.1 3.6 2.6 2.9 5.2 5.1 3.6 3.9 5.9 7.2 5.1 5.6
85 2.2 2.6 2.1 2.3 2.9 3.4 2.5 2.7 4.9 4.8 3.4 3.8 5.6 6.8 4.8 5.3
80 2.1 2.4 2.0 2.2 2.8 3.3 2.3 2.6 4.7 4.6 3.2 3.6 5.3 6.4 4.6 5.1
Table 22. Cooling amperage — heat pumps
Condenser
inlet air
temp.
PTHE0701 PTHE0702 PTHE0901 PTHE0902 PTHE1201 PTHE1202 PTHE1501 PTHE1502
Min Max Min Max Min Max Min Max Min Max Min Max Min Max Min Max
2.6 2.9 2.4 2.4 3.6 3.9 3.2 3.2 4.8 5.2 4.2 4.2 6.5 7.1 6.3 6.3
100 2.6 2.9 2.5 2.7 3.4 4.0 3.0 3.2 5.6 5.5 4.1 4.5 6.6 8.0 5.5 6.8
95 2.4 2.8 2.4 2.6 3.2 3.8 2.8 3.1 5.3 5.2 3.9 4.3 6.2 7.6 5.2 5.8
90 2.3 2.6 2.2 2.5 3.1 3.6 2.7 3.0 5.0 5.0 3.7 4.1 5.9 7.2 5.0 5.5
85 2.1 2.5 2.1 2.3 3.1 3.4 2.6 2.9 4.8 4.7 3.5 3.9 5.6 6.8 4.7 5.2
80 2.1 2.3 2.1 2.2 2.9 3.3 2.5 2.7 4.6 4.5 3.3 3.7 5.3 6.4 4.5 4.9
Table 20. Cooling temperature change - heat pumps (continued)
Room
airdry
bulb
Room air wet
bulb
PTHE0701 PTHE0702 PTHE0901 PTHE0902 PTHE1201 PTHE1202 PTHE1501 PTHE1502
Temperature across
indoor coil (∆ T)
Temperature
acrossndoor coil (∆ T)
Temperature across
indoor coil (∆ T)
Temperature across
indoor coil (∆ T)
Min Max Min Max Min Max Min Max
PTAC-SVX01C-EN 27
Operation
Notes: Shaded area is rating wattage
Table 23. Heating total wattage input — heat pumps
Outside air
dry-bulb
Room air
dry-bulb
PTHE
0701
PTHE
0702
PTHE
0901
PTHE
0902
PTHE
1201
PTHE
1202
PTHE
1501
PTHE
1502
Min Max Min Max Min Max Min Max
520 535 670 685 940 965 1210 1235
50
85 580 620 745 790 1030 1115 1295 1435
80 565 600 725 775 1010 1095 1275 1410
75 550 590 710 760 990 1075 1245 1385
70 535 575 695 740 970 1050 1225 1360
65 520 560 675 720 945 1025 1200 1335
45
85 565 600 710 760 1000 1080 1240 1375
80 550 590 695 740 975 1060 1214 1355
75 630 570 680 730 955 1040 1190 1330
70 515 555 660 710 930 1010 1160 1305
65 500 540 640 690 910 995 1145 1280
40
85 545 580 680 725 950 1040 1185 1320
80 530 570 660 710 940 1020 1160 1300
75 515 555 640 690 920 1000 1135 1270
70 500 535 630 675 895 980 1110 1250
65 480 520 610 675 875 955 1090 1220
35
85 525 565 650 695 925 1010 1130 1270
80 510 550 630 675 900 985 1110 1240
75 500 535 610 655 880 965 1080 1220
70 480 520 600 645 855 940 1060 1190
65 465 500 580 625 940 922 1030 1265
Table 24. Heat pump reverse cycle heating capacity
PTEE07 PTEE09 PTEE12 PTEE15
Voltage 208 230 265 208 230 265 208 230 265 208 230 265
Amps 2.5 2.4 2.4 3.4 3.2 2.6 4.3 4.0 3.5 5.7 5.3 4.6
Btu/H 6400 6600 6600 7600 7800 8000 10100 10300 10300 12800 13100 13100
COP 3.6 3.6 3.6 3.2 3.2 3.4 3.3 3.3 3.3 3.0 3.0 3.0
Cfm (dry) 220 230 250 240 270 270 330 360 350 350 390 380
Heating
Btu/H
Outdoor
Ambient
62 7200 7400 7400 9600 9700 9700 12800 13000 13000 15700 15800 15800
57 6900 7100 7100 9300 9600 9600 12500 12800 12800 15000 15200 15200
52 6500 6700 6700 8700 9000 9000 11700 12000 12000 14200 14400 14400
Rating
Point
47 6200 6400 6400 8200 8400 8400 10900 11200 11200 13300 13500 13500
42 5900 6100 6100 7700 7900 7900 10200 10500 10500 12500 12700 12700
37 5600 5800 5800 7200 7400 7400 9500 9700 9700 11700 11900 11900
32 5300 5500 5500 6700 6900 6900 9600 8900 8900 10800 11000 11000
27 5000 5200 5200 6200 6300 6300 7900 8200 8200 10000 10200 10200
24 4800 5000 5000 5800 6000 6000 7500 7800 7800 9500 9700 9700
28 PTAC-SVX01C-EN
Operation
Table 25. Unit accessory model numbers
Description Part Number
Architectural Grilles
ARCHITECTURAL ALUMINUM GRILLE BAYAAGL001
ARCHITECTURAL ALUMINUM GRILLE -DARK
BRONZE
BAYAAGL002
ARCHITECTURAL ALUMINUM GRILLE - SOFT
DOVE
BAYAAGL003
ARCHITECTURAL ALUMINUM GRILLE - SPECIAL
COLOR
BAYAAGL004
Circuit breakers
CIRCUIT BREAKER - 208/230 15AMP BAYCBKR001
CIRCUIT BREAKER 208/230 20AMP BAYCBKR002
CIRCUIT BREAKER - 208/230 30AMP BAYCBKR003
Condensate pump
CONDENSATE PUMP 208/230 BAYCPMP001
CONDENSATE PUMP 265 BAYCPMP002
Drain Kit
DRAIN KIT BAYDRAN001
Filters
SPARE FILTERS 10 PACK BAYFLTR009
Hard Wire Kit
HARD WIRE KIT BAYHWRK001
Leveling Legs
LEVELING LEG BAYLVLG001
Power Switch(1)
POWER SWITCH -115V, 208/230V 265V 30 AMP BAYPSW002
Stamped grille
STAMPED ALUMINUM GRILLE - SINGLE PACK BAYSAG001
STAMPED ALUMINUM GRILLE - TEN PACK BAYSAG002
Wall Sleeve
13 INCH WALL SLEEVE BAYWSLV001
18 INCH WALL SLEEVE BAYWSLV002
24 INCH WALL SLEEVE BAYWSLV003
Power Cord
UNIVERSAL POWER CORD 115 VOLT
- 15 Amp BAYPCRD007
UNIVERSAL POWER CORD 230 VOLT - 15 AMP BAYPCRD001
UNIVERSAL POWER CORD 230 VOLT - 20 AMP BAYPCRD002
UNIVERSAL POWER CORD 230 VOLT - 30 AMP BAYPCRD003
UNIVERSAL POWER CORD 265 VOLT - 15 AMP BAYPCRD004
UNIVERSAL POWER CORD 265 VOLT - 20 AMP BAYPCRD005
UNIVERSAL POWER CORD 265 VOLT - 30 AMP BAYPCRD006
Display Module
DISPLAY MODULE (AMERICAN STANDARD LOGO
STANDARD)
BAYAMDM001
DISPLAY MODULE (AMERICAN STANDARD LOGO
& DEHUMIDIFICATION)
BAYAMDM002
DISPLAY MODULE (TRANE LOGO STANDARD) BAYTRDM001
DISPLAY MODULE (TRANE LOGO &
DEHUMIDIFICATION)
BAYTRDM002
Escutcheon Cover(2)
ESCUTCHEON COVER FOR FRONT PANEL
(AMSTD LOGO)
BAYACVR001
ESCUTCHEON COVER FOR FRONT PANEL
(TRANE LOGO)
BAYTCVR001
Plastic Front Cover(3)
PLASTIC FRONT COVER FOR PTAC BAYPCVR001
Connector for Hardwire(4)
CONNECTOR FOR HARDWIRE KIT 208/230V -
15 AMP
BAYCNHK011
CONNECTOR FOR HARDWIRE KIT 208/230V -
20 AMP
BAYCNHK012
CONNECTOR FOR HARDWIRE KIT 208/230V -
30 AMP
BAYCNHK013
CONNECTOR FOR HARDWIRE KIT 265V - 15
AMP
BAYCNHK021
CONNECTOR FOR HARDWIRE KIT 265V - 20
AMP
BAYCNHK021
CONNECTOR FOR HARDWIRE KIT 265V - 30
AMP
BAYCNHK023
CONNECTOR FOR HARDWIRE KIT 115V - 15
AMP
BAYCNHK031
Subbase(5) (6)
UNIVERSAL SUBBASE BAYSUB001
SOCKET FOR SUBBASE 208/230 20 AMP BAYSCKT001
SOCKET FOR SUBBASE 208/230 30 AMP BAYSCKT002
SOCKET FOR SUBBASE 265 20 AMP BAYSCKT003
SOCKET FOR SUBBASE 265 30AMP BAYSCKT004
(1) The power switch can be installed on the hard wire junction box and
provides a way to shut on and off the PTAC unit. It is an optional ac-
cessory when using the power cord to power the PTAC unit. Check local
codes for approval
(2) This escutcheon cover should be ordered whenever the display module
is wall mounted or a thermostat or third party provider unit controls are
ordered. This escutcheon includes a control cover plate that covers the
normal unit mounted nomenclature. It comes 5 pieces per pack.
(3) All hydronic PTAC chassis come standard without a plastic front cover.
If a unit is required to work without heat and without a hydronic kit the
plastic front cover should be ordered.
(4) Not required when using a Hard Wire Kit.
(5) Provides a space to tie into a building’s wiring with a receptacle to plug
the unit into. It gives additional leveling and support capabilities and
provides a place for fuses, a circuit breaker or a mechanical disconnect
to be mounted. (30A is for units with 5kW electric heat, 20A for 3kW or
less electric heat.)
(6) All subbases require a socket. For 15 and 20 amp, the 20amp socket
can be used on either the 208/230V or the 265V.
Table 25. Unit accessory model numbers
Description Part Number
PTAC-SVX01C-EN 29
Operation
Table 26. Hydronic heat options
Kit Description
HHydronic
Coil Type
WWater Coil
SSteam Coil
Accessory Type
KKit
Power Voltage
01 208-230 VAC
02 265 VAC
04 115 VAC
Coil Positioning
L Left hand hot water coil
connection (Standard/
Stocked)
R Right hand hot water coil
connection (Not Stocked)
Kick Plate
S Standard 2" to 6" adjustable
kick plate
E Extended standard base kick
plate 7" to 13"
M Upgraded kick plate standard
height 2" to 6" (Like the unit
ventilator design)
U Upgraded kick plate extended
height 7" to 13" (Like the unit
ventilator design)
Color
S Standard Soft Dove II
C Special Color
30 PTAC-SVX01C-EN
Maintenance Procedures
Perform the following maintenance
procedures to ensure proper unit
operation.
WARNING
Live Electrical Components!
During installation, testing, servicing
and troubleshooting of this product,
it may be necessary to work with
live electrical components. Have a
qualified licensed electrician or other
individual who has been properly
trained in handling live electrical
components perform these tasks.
Failure to follow all electrical safety
precautions when exposed to live
electrical components could result in
death or serious injury.
WARNING
Hazardous Voltage!
Disconnect all electric power,
including remote disconnects before
servicing. Follow proper lockout/
tagout procedures to ensure the
power can not be inadvertently
energized. Failure to disconnect
power before servicing could result
in death or serious injury.
Chassis
Clean the chassis every four months
or more often as the atmospheric
conditions require. Use water and
detergent to clean the basepan,
center partition and coils.
Using harsh cleaning materials may
cause a deterioration of the coil fins
or end plates.
Do not use a high pressure cleaner
as it could cause severe damage to
the PTAC fins and coils.
Note: It is very important to not get
any of the electronic parts
wet.
A hose is okay to use to clean the
coils, but make sure to cover the
control with a blanket or plastic bag
to prevent it from getting wet.
Wall Sleeve
Clean the wall sleeve every four
months or more often as the
atmospheric conditions require.
Remove any debris from the bottom
of the panel, and from around any
internal or external drain kit
accessory item prior to using water
or detergent. This will ensure that no
debris clogs up the drain holes.
The use of harsh cleaning materials
may cause a deterioration of the
bottom panel over time. Do not use
a high pressure cleaner because it
could spray the side or top panel
insulation material and cause future
air quality problems like mold and
mildew.
Clean side and top panel insulation
material with a lint brush or piece of
tape. Press tape against insulation
lightly and slowly peel away to
remove dirt and debris.
Compressor/Fan Motor
The compressor and fan motor are
hermetically sealed, permanently
lubricated, and require no additional
oiling.
Cabinet Front
The cabinet front and discharge air
grille can be cleaned with a mild
soap or detergent.
Under NO circumstances should
hydrocarbon based cleaners (e.g.
acetone, benzene, naphtha gasoline,
etc.) be used to clean the front or air
grilles.
Use care when cleaning the control
area. Do not use an excessively wet
cleaning cloth.
Intake Air Filter
The intake air filter and vent door
filter are both constructed of durable
polypropylene. Clean filters monthly
to ensure proper unit operation.
The fan must be off before the filters
are cleaned.
To remove the air filters, grasp the
top of the filter and lift out of the
front cabinet (Figure 19.) Reverse the
procedure to reinstall the filters.
Vent Filter
Before cleaning the vent filter,
disconnect power to the unit by
unplugging the power cord at the
wall outlet or subbase, or disconnect
power at the fuse box or circuit
breaker. If unit is operated with vent
door closed, the vent filter does not
need to be cleaned.
1. Remove the cabinet front as
described in front removal.
2. Remove the six screws securing
the chassis to the wall sleeve
with a Phillips-Head screwdriver.
3. Slide the chassis out of the wall
sleeve far enough so that the
vent filter is accessible as shown
in Figure 20.
4. Remove the vent filter by
unscrewing the two screws at
the top of the filter and gently
pulling the filter away from the
partition panel. Refer to
Figure 21. The filter can be
cleaned by running under a low
pressure hose or sink faucet.
Figure 19. Intake air filter removal
is through top of unit. Inspect and
clean filters monthly for proper unit
operation.
Maintenance
PTAC-SVX01C-EN 31
Maintenance
5. Reinstall the filter by reattaching
the hook to the bottom of the
vent door and replacing the two
screws, slide the chassis back
into the wall sleeve, secure it in
place with six screws and
reinstall the front cabinet.
Scheduled Maintenance
To achieve top performance and high
efficiency, a cleaning/ inspection
schedule must be established for this
unit. Maintaining this schedule can
be accomplished by either a local
maintenance staff or an authorized
servicer and must follow the
instructions described in this manual.
• If the unit is operated in a dusty
climate, dust may collect in the
basepan and clog the condenser
coil. It is advisable to remove the
unit from the sleeve and
thoroughly clean the basepan
and condenser coil on a periodic
basis.
Figure 20. Vent (left side of unit)
Figure 21. Vent filter removal
Vent door
• If the unit is installed ocean side
or in a corrosive atmosphere, its
life may be greatly reduced by
the corrosive environment.
Under these conditions the unit
should be removed from the
sleeve and completely cleaned at
least four times per year. At that
time any scratches or blisters on
the painted surfaces should be
sanded and repainted.
Refrigeration System
Service
WARNING
Ensure Terminal Cover is in
Place!
Do not plug in this product or apply
power to the compressor if the
compressor terminal cover is
removed or is not firmly in place.
Failure to follow these instructions
could result in a fire that could cause
death, personal injury, or property
damage.
Service operations requiring opening
of the hermetically sealed
refrigeration system should be taken
to a well equipped shop where
special equipment for evacuating,
dehydrating, charging and testing is
available. The following equipment is
necessary:
• Nitrogen of no more than 0.0012
grains of moisture.
• Vacuum pump capable of
evacuating to a minimum of 50
microns.
• Micron gauge to check vacuum
• Refrigerant charging cylinder
accurate to within 1/4 oz.
• Electronic leak detector
• Electrical equipment to test
compressors, capacitors, voltage
relays, and overload protectors
• Voltmeter, ammeter, and
wattmeter
• Silver soldering and brazing
equipment - Pinch off tools ¼ in
to 5/8 in
• Thermocouple tester
WARNING
Hazardous Pressures!
If a heat source is required to raise
the tank pressure during removal of
refrigerant from cylinders, use only
warm water or heat blankets to raise
the tank temperature. Do not exceed
a temperature of 150°F. Do not, under
any circumstances apply direct flame
to any portion of the cylinder. Failure
to follow these safety precautions
could result in a violent explosion,
which could result in death or
serious injury.
CAUTION
Freezing Temperatures!
Do not allow liquid refrigerant to
contact skin. If it does, treat the
injury similar to frostbite. Slowly
warm the affected area with
lukewarm water and seek immediate
medical attention. Direct contact
with liquid refrigerant may cause
minor or moderate injury.
Dehydrating and Evacuating
Refrigeration System
A rather popular misconception
exists that since air conditioners
normally operate with a refrigerant
temperature above 32°F, moisture in
the system is harmless. Nothing
could be further from the truth.
Oxygen from moisture plus normal
compressor and motor heat reacts
chemically with the refrigerant and
oil to form corrosive hydrochloric
and hydrofluoric acids. These acids
contribute to the break down of
motor winding insulation and the
corrosion of compressor working
parts and cause unnecessary
compressor failure.
Sludge, which is a residue of the
chemical reaction, coats all
compressor parts, the inside of
refrigerant tubing, and may even
restrict refrigerant flow through the
capillary tube(s).
32 PTAC-SVX01C-EN
Maintenance
Leak Testing
Refrigerant leaks are best detected
with a halide or electronic leak
detector.
WARNING
Use of Pressure Regulator –
Valves – Gauges!
Always use pressure regulators,
valves, and gauges to control drum
and line pressures when pressure
testing equipment. Failure to follow
these instructions could result in an
explosion causing death, serious
injury, or equipment damage.
WARNING
Leak Testing!
Do not exceed 200 psig when leak
testing system. Failure to follow
these instructions could result in an
explosion causing death or serious
injury.
The importance of careful leak
testing cannot be over emphasized.
Undetected leaks invariably lead to
repeated calls and eventually result
in system contamination, restrictions
and burned out compressors.
For a system that contains a
refrigerant charge and is suspected
of having a leak, stop the operation,
check all tubing and fittings. Soap
suds may also be used.
Note: The flame of the halide
detector will glow green in
the presence of R22
refrigerant.
If a leak is detected, do not attempt to
apply more brazing material to the
joint. Recover the charge, unbraze the
joint, clean and rebraze.
For a system that has been newly
repaired and does not contain a
charge, connect a cylinder of
refrigerant, through a gauge
manifold, to the process tube of the
compressor and liquid line strainer.
Open the valve on the cylinder and
manifold and allow the pressure to
build up within the system. Check for
and handle leaks as described above.
After the test has been completed,
recover the test charge, evacuate the
system, and recharge with clean
refrigerant.
Brazing
WARNING
Hazard of Explosion!
Use only dry nitrogen with a
pressure regulator for pressurizing
unit. Do not use acetylene, oxygen or
compressed air or mixtures
containing them for pressure testing.
Do not use mixtures of a hydrogen
containing refrigerant and air above
atmospheric pressure for pressure
testing as they may become
flammable and could result in an
explosion. Refrigerant, when used as
a trace gas should only be mixed
with dry nitrogen for pressurizing
units. Failure to follow these
recommendations could result in
death or serious injury or equipment
or property-only damage.
CAUTION
High Temperatures!
Brazing requires high temperatures.
Direct contact with hot surfaces may
cause minor or moderate injury.
Satisfactory brazing results require
cleanliness, experience and the use
of proper material and equipment.
Verify brazing connections are
properly sized, free of rough edges,
and clean.
Use of these generally accepted
brazing materials:
• SIL-FOS (Alloy of 15% silver, 80%
copper, 5% phosphorus): use
without flux on copper to copper.
Note: DO NOT USE FOR A COPPER
TO STEEL CONNECTION.
Recommended heat is
approximately 1400°F.
• SILVER SOLDER (Alloy of 30%
silver, 38% copper, 32% zinc): use
with fluoride base flux on copper
to steel, brass to copper, steel to
steel, or brass to steel.
Recommended heat is
approximately 1200°F.
PTAC-SVX01C-EN 33
Maintenance
Figure 22. Refrigeration sealed system — heat pump (air conditioning
model
Figure 23. Refrigeration sealed system — Heat pump (heat pump model)
Evacuation CAUTION
Fan Motor Overheat!
Never test operation without the
unit in the wall sleeve. A serious
change in design specifications for
air movement through the
evaporator and condenser
compartments, causing the fan
motor to over heat and the
refrigeration system to become
unbalanced will occur when the unit
is not installed in the wall sleeve.
CAUTION
High Temperatures!
Do not allow sludge or oil to contact
skin when evacuating refrigerant
from equipment. Direct contact with
sludge or oil may cause minor or
moderate injury.
Thoroughly evacuate the system
using a high vacuum pump, capable
of producing a vacuum equivalent to
50 microns and a thermocouple
vacuum gauge to give a true reading
of the vacuum in the system.
Note: Never use the system
compressor as a vacuum
pump or run when under a
high vacuum. Motor damage
could occur.
Evacuation Procedure
1. Connect the vacuum pump,
vacuum tight manifold set with
high vacuum hoses,
thermocouple vacuum gauge,
and charging cylinder.
2. Connect the low side line to the
process tube of the compressor.
3. Connect the high side line to the
process tube of the liquid line
strainer.
Note: If either process tube is not
long enough to receive the
compression or flare fitting
and still leave room for a
pinch-off, swag the tube and
braze in an extra length of
tubing.
34 PTAC-SVX01C-EN
Maintenance
4. Start the vacuum pump and
open the shut-off valve to the
high vacuum gauge manifold
only. After the compound gauge
(low side) has dropped to
approximately 29 inches of
vacuum, open the valve to the
vacuum thermocouple gauge.
See that the vacuum pump will
bank-off to a minimum of 50
microns. A high vacuum pump
can only produce a good vacuum
if its oil is not contaminated.
5. If the vacuum pump is working
properly, close the valve to the
vacuum thermocouple gauge
and open the high and low side
valves or the high vacuum
manifold set. With the valve on
the charging cylinder closed,
open the manifold valve to the
cylinder.
6. Evacuate the system to at least
29 inches gauge before opening
valve to thermocouple vacuum
gauge.
7. Continue to evacuate to a
minimum of 250 microns. Close
valve pump and watch rate of
rise. If vacuum does not rise
above 1500 microns in three
minutes, system can be
considered properly evacuated.
8. If thermocouple vacuum gauge
continues to rise and levels off at
about 5000 microns, moisture
and non-condensables are still
present. A leak is present if the
gauge continues to rise. Repair
and re-evacuate.
9. Close valve to the thermocouple
vacuum gauge and vacuum
pump. Shut off pump and
prepare to charge.
Charging the System
Charge the system with the exact
amount of refrigerant. Refer to the
unit nameplate for the correct
refrigerant charge. An inaccurately
charged system will cause future
problems.
Charging Procedure
1. When using an ambient-
compensated calibrated
charging cylinder, allow liquid
refrigerant only to enter the high
side.
2. After the system receives all the
refrigerant it requires, close
close the valve on the high side
of the manifold.
3. Start the system and charge the
balance of the refrigerant though
the low side. Do not charge in a
liquid form.
4. Close the low side valve on the
manifold and pinch-off both
process tubes. Remove the
manifold set. Crimp shut the
open ends of the process tubes
and braze.
5. Recheck for refrigerant leaks.
Refrigerant
Do not use a refrigerant other than
that shown on the unit nameplate.
Follow all precautionary measures
recommended by the refrigerant
manufacturers.
Line Piercing Valves
Line piercing valves may be used for
diagnosis but are not suitable for
evacuating or charging due to the
minute holes pierced in the tubing.
Line piercing valves must not be left
on the refrigerant system. The
connection between the valve and
the refrigerant tubing is not
hermetically sealed and will
eventually leak.
Open Lines
Never leave refrigerant lines open to
the atmosphere when processing the
refrigeration system. Water vapor
may enter the lines and cause
improper evacuation.
Operating Test
The final step in a successful repair is
an accurate operating test. Follow the
cooling and heating performance
tests on pages 36 - 37 to make sure
the product is performing to design
standards.
WARNING
Hazardous Voltage!
Disconnect all electric power,
including remote disconnects before
servicing. Follow proper lockout/
tagout procedures to ensure the
power can not be inadvertently
energized. Failure to disconnect
power before servicing could result
in death or serious injury.
WARNING
Live Electrical Components!
During installation, testing, servicing
and troubleshooting of this product,
it may be necessary to work with live
electrical components. Have a
qualified licensed electrician or other
individual who has been properly
trained in handling live electrical
components perform these tasks.
Failure to follow all electrical safety
precautions when exposed to live
electrical components could result in
death or serious injury.
Figure 24. Proper placement of
discharge and inlet air thermostats
Place discharge and
inlet air thermostats
Place inlet thermostat
in center of grille
PTAC-SVX01C-EN 35
Maintenance
Cooling Performance Test
Thermometers
The following precautions are
necessary in observing the
thermometer readings in the cooling
performance test.
1. Use two accurately calibrated
refrigeration type thermometers
or a thermocouple
potentiometer.
2. Thermometers are affected by
body heat or changes in airflow.
Therefore, secure the
thermometers in proper
locations with masking tape,
wire, or other applicable
retainers.
3. Observe readings without
touching or moving the
thermometers.
Sling Psychrometer
Use a sling psychrometer to obtain
the wet-bulb temperature and
determine the percent relative
humidity.
To obtain the wet-bulb, follow this
procedure using the sling
psychrometer.
• Saturate the wick (only once
during procedure of obtaining
wet-bulb readings) with clean
water slightly below room
temperature.
• Obtain the psychrometer reading
five to six feet in front of the unit
and approximately four feet off
the floor.
Note: Direct discharge airflow away
from the sling psychrometer.
Do not perform the cooling
performance test when the outside
temperature is 20°F below the room
temperature. For best results,
perform the test under peak load
conditions.
The air conditioner must operate at
least 20 minutes on the HIGH COOL
position before testing.
Cooling Performance Test
Record the following temperatures
for the cooling performance test:
• Dry-bulb temperature of return
air at conditioner. Locate
thermometer as illustrated on
previous page.
• Dry-bulb temperature of
discharge air. Locate the
thermometer as illustrated on
previous page.
• The dry-bulb thermometer
temperature on the sling
psychrometer should be plus or
minus 1°F within reading
obtained on thermometer in the
return air. Check wet-bulb
temperature on sling
psychrometer and record same.
• After recording the wet-bulb
temperature, dry- bulb
temperature, and return air
temperature, calculate the
temperature difference as
follows.
• Subtract temperature obtained in
Step B from temperature
obtained in Step A. Use the
remainder temperature to
calculate from the cooling
change of temperature in the
Maintenance general
information section.
Example: Assume a PTHE1501 unit is
under test and the temperature
readings indicated below were
obtained.
1. Return air dry-bulb temperature:
80°F, Step A.
2. Discharge air dry-bulb
temperature: 69°F, Step B.
3. Return air, wet and dry-bulb
temperature as recorded in Step
C: dry- bulb 80°F, wet-bulb 75°F.
4. In left hand column of cooling
capacity charge headed dry-bulb,
find the 80° value in Table 20,
p. 25.
5. In column headed wet-bulb find
the 75° value and find the value
"8 -13" in the cooling range
column under model
“PTHE1501”.
This data shows the temperature of
the air passing through the cooling
coil is reduced at least 8°F but not
more than 13°F. This example unit is
operating normally for the existing
conditions.
For the example unit under test, the
temperature difference was 11°F
(80°F, return air, minimum 69°F
discharge air). Because the value is
within the listed cooling range 8 - 13,
this unit is considered to be
operating normally.
Note: Never test operation without
the unit in the wall sleeve. A
serious change in design
specifications for air
movement through the
evaporator and condenser
compartments, causing the
fan motor to over heat and
the refrigeration system to
become unbalanced will
occur when the unit is not
installed in the wall sleeve.
Electric Heat Test
For the electric heat test, the
following readings must be recorded
after the unit is interconnected with a
wattmeter or by recording the total
amp draw to the unit.
Note: The cabinet front must be in
place during this test.
• Record supply voltage to unit.
• Operate unit in highest heat
setting.
• Record wattage recorded on
wattmeter or total amp draw to
unit.
• Refer to the electric heat capacity
and electrical data section
(whichever is applicable for
voltage rating on the unit being
tested.)
• The total watts or amps recorded
should fall with in the minimum
and maximum watts/amps listed
on these charts
Example: Assume that a PTHE1501
230/208V with 3.5 kW electric heater
is under test.
1. Supply voltage as recorded -
208V.
2. Watts recorded -2750W or amps
recorded - 13.5 amps.
36 PTAC-SVX01C-EN
Maintenance
3. Locate the readings listed in the
Operation section of this manual.
You will note that these readings
fall within the voltage, watts and
amp draw minimum and
maximum ranges listed.
Therefore, the unit heating
performance would be
considered normal.
Heating Power Consumption
Te s t
(Heat Pump Mode Only)
For the heating wattage, record the
following readings after the unit is
interconnected with a wattmeter.
• Outside coil inlet air dry-bulb
temperature.
• Inside coil inlet air dry-bulb
temperature.
• Total watts input measured by
wattmeter.
Calculating procedure
1. Locate temperature obtained in
Step A of cooling performance
test in first column of Heating
Wattage Chart.
2. Locate in second column the
inside coil inlet dry-bulb
temperature.
3. The total watts input should
come between minimum and
maximum values indicated for
each model.
Example: Assume that a PTHE1501 is
under test. Proceed as follows and
observe test readings as
simultaneously as possible.
1. Outside coil inlet dry-bulb
temperature readings as
described above: 45°F.
2. Check watts input: 1370 W
3. Inside coil inlet dry-bulb
temperature reading as de
scribed in Step B: 75°F.
Read to the right from the 75° inside
coil inlet dry-bulb value in the
column and note the minimum and
maximum wattage of 1335 - 1470.
Since the wattage reading (1370)
obtained in the test is within the
prescribed range, the total power
input in watts is considered to be
normal.
WARNING
Live Electrical Components!
During installation, testing, servicing
and troubleshooting of this product,
it may be necessary to work with live
electrical components. Have a
qualified licensed electrician or other
individual who has been properly
trained in handling live electrical
components perform these tasks.
Failure to follow all electrical safety
precautions when exposed to live
electrical components could result in
death or serious injury.
WARNING
Hazardous Voltage!
Disconnect all electric power,
including remote disconnects before
servicing. Follow proper lockout/
tagout procedures to ensure the
power can not be inadvertently
energized. Failure to disconnect
power before servicing could result
in death or serious injury.
WARNING
Hazardous Voltage
w/Capacitors!
Disconnect all electric power,
including remote disconnects and
discharge all motor start/run
capacitors before servicing. Follow
proper lockout/tagout procedures to
ensure the power cannot be
inadvertently energized. Verify with
an appropriate voltmeter that all
capacitors have discharged. Failure
to disconnect power and discharge
capacitors before servicing could
result in death or serious injury.
Resistance Check
Discharge capacitor and remove wire
leads. Use a DC volt meter to verify
there is no power.
Testing Capacitor Resistance
1. Set an ohmmeter on its highest
ohm scale and connect the leads
to the capacitor.
a. Good Condition - indicator
swings to zero and slowly
returns to infinity. (Start
capacitor with bleed resistor
will not return to infinity. It
will still read the resistance of
the resistor).
b. Shorted - indicator swings to
zero and stops there -
replace.
c. Open - no reading - replace.
(Start capacitor would read
resistor resistance).
2. Testing for ohms between either
capacitor terminal and the
capacitor body must show
infinite ohms.
Capacitance Check
Using a hookup as shown below,
take the amperage and voltage
readings and use them in the formula
below the diagram.
Overloads
1. With no power to the unit,
remove the overload lead from
the compressor terminal.
2. Using an ohmmeter: Test
continuity between terminals of
the overload. If not continuous,
the overload is open, replace the
overload.
Compressor Windings
WARNING
Electrical Shock!
Do not connect electrical power to
this unit or to the compressor if the
compressor terminal cover has been
removed or is not firmly in place.
Doing so could result in death,
serious injury, or property damage.
If the test indicates shorted,
grounded or open windings, see
procedure for the next steps to be
taken.
PTAC-SVX01C-EN 37
Maintenance
Resistance Test
1. With no power, remove the leads
from the compressor terminals.
2. Touch the leads of an ohmmeter
to terminals C-S, start windings
and C-R, run winding.
If either winding does not test
continuous, replace the compressor.
Testing capacitance
capacitance (MFD) =
2650 X amperage
voltage
Note: Replace the capacitor if the
value obtained is not within
10% of the rating printed on
the capacitor.
Ground Test
WARNING
Live Electrical Components!
During installation, testing, servicing
and troubleshooting of this product,
it may be necessary to work with live
electrical components. Have a
qualified licensed electrician or other
individual who has been properly
trained in handling live electrical
components perform these tasks.
Failure to follow all electrical safety
precautions when exposed to live
electrical components could result in
death or serious injury.
Figure 25. Testing capacitor
resistance
15 amp
fuse
Voltmeter
Ammeter
Capacitor
With no power and compressor leads
removed:
Set an ohmmeter on its highest scale.
Touch one lead to the compressor
body (clean point of contact, as a
good connection is a must) and the
other probe to each compressor
terminal in turn. If a reading is
obtained, then compressor is
grounded and must be replaced.
If the voltage, capacitor, overload and
motor windings test fail to show the
cause for failure:
1. With no power, wire a test cord
to line voltage (Line & N).
Note: The wire size of the test cord
must equal the line size, and
the fuses in the test line must
be of the proper size and
type.
2. Connect a good capacitor of the
right MFD and voltage rating into
the circuit as shown in Figure 40.
3. Carefully apply line voltage.
a. If the compressor starts and
continues run, the cause for
failure is somewhere else in
the system.
Figure 26. Compressor ground test
Figure 27. Test cord connections
Ohmeter Compressor
top
Outlet
Terminals Accumulator
b. If the motor fails to start -
replace. Since all single
phase compressors are of the
permanent split capacitor
design the high and low side
pressure must be
approximately equal or the
low torque compressor may
not start.
Indoor Coil and Air
Thermistors
1. Remove the Indoor Coil
Thermistor leads from the circuit
board.
2. Check the resistance of the
Indoor Coil Thermistor against
the table on the next page. The
leads of the ohm meter will need
to contact the ends of the
thermistors that connect to the
board.
3. Replace the Indoor Coil
Thermistor if it does not test as
above.
Outdoor Coil and Air
Thermistors
1. Remove the outdoor coil
thermistor leads from the circuit
board.
2. Check the resistance of the
outdoor coil thermistor against
the table on the next page. The
leads of the ohm meter will need
to contact the ends of the
thermistors that connect to the
board.
3. Replace the outdoor coil
thermistor if it does not test as
above.
Heater Assembly with Power
OFF to the Unit and Heater
1. Remove the heaters in question
and visually inspect the element
for broken condition. Refer to the
disassembly procedures for
information on disassembling
the heater.
2. Test the thermal fuse (one time
fuse). If open, replace the heater
assembly.
38 PTAC-SVX01C-EN
Maintenance
Table 27. Thermistor indoor coil
resistance
x (C°)
Rmin
(kΩ)
Rnom
(kΩ)
Rmax
(kΩ)
-40.0 327.6037 342.7771 358.6311
-39.0 306.4713 320.4512 335.0471
-38.0 286.8464 299.7818 313.1748
-37.0 268.6117 380.4928 292.8787
-36.0 251.6597 262.6189 274.0353
-35.0 235.8919 246.0045 258.5312
-34.0 221.2181 230.5528 240.2626
-33.0 207.5554 216.1750 225.1344
-32.0 194.8276 202.7896 211.0696
-31.0 182.9649 190.3219 197.9580
-30.0 171.9031 178.7032 186.7663
-29.0 161.5829 167.8703 174.3869
-28.0 161.9502 157.7652 163.7880
-27.0 142.9647 148.3344 163.9026
-26.0 134.5504 139.5289 144.6781
-25.0 126.6948 131.3031 126.0653
-24.0 119.3487 123.6155 128.0227
-23.0 112.4758 116.4275 120.5064
-22.0 106.0429 109.7036 113.4795
-21.0 100.0191 103.4109 106.9073
-20.0 94.3758 97.5193 100.7575
-19.0 89.0868 92.0070 95.0050
-18.0 84.1276 86.8293 89.6087
-17.0 79.4758 81.9811 84.5569
-16.0 75.1104 77.4341 79.8216
-15.0 71.0121 73.1677 75.3810
-14.0 67.1629 69.1629 71.2151
-13.0 63.5463 65.4021 67.3053
-12.0 60.1468 61.8691 63.6342
-11.0 56.9501 68.6487 60.1860
-10.0 53.9430 55.4269 56.9458
-9.0 51.1130 52.4905 53.8998
-8.0 48.4488 49.7278 51.0353
-7.0 45.9395 47.1271 48.3404
-6.0 43.5756 44.6782 45.8041
-5.0 41.3475 42.3713 43.4161
-4.0 39.2467 40.1974 41.1670
-3.0 37.2652 38.1480 39.0478
-2.0 35.3956 36.2153 37.0504
-1.0 33.6309 34.3920 35.1569
0.0 31.9646 32.6713 33.3904
1.0 30.3900 31.4600 31.7132
2.0 28.9023 29.5113 30.1303
3.0 27.4964 28.0617 28.6358
4.0 26.1673 26.6919 27.2244
5.0 24.9103 25.3971 25.8909
6.0 23.7211 24.1727 24.6306
7.0 22.5967 23.0148 23.4391
8.0 21.5303 21.9188 22.3122
9.0 20.5214 20.8816 21.2461
10.0 19.5667 19.8995 20.2371
11.0 18.6600 18.9693 19.2819
12.0 17.8015 18.0880 18.3773
13.0 18.9874 17.2527 17.5204
14.0 16.2153 16.4608 16.7083
15.0 16.4827 16.7098 16.9385
16.0 14.7874 14.9973 16.2087
17.0 14.1272 14.3212 14.5164
18.0 13.5003 13.6794 13.8595
19.0 12.9048 13.0700 13.2381
20.0 12.3389 12.4912 12.6442
21.0 11.8010 11.9413 12.0821
22.0 11.2895 11.4187 11.5482
23.0 10.8031 10.9219 11.0408
24.0 10.3404 10.4494 10.5585
25.0 9.9000 10.0000 10.1000
26.0 9.4726 9.5724 9.6724
27.0 9.0659 9.1656 9.2652
28.0 8.6790 8.7781 8.8774
29.0 8.3106 8.4091 8.6078
30.0 7.9600 8.0577 8.6078
31.0 7.6280 7.7229 7.8203
32.0 7.3078 7.4089 7.5004
33.0 7.0047 7.0997 7.1952
34.0 6.7157 6.8087 6.9042
35.0 6.4402 6.5330 6.6264
36.0 6.1775 6.2691 6.3614
37.0 5.9269 6.0173 6.1083
38.0 5.6878 6.7769 5.8667
39.0 5.4598 5.5474 5.6359
40.0 5.2418 5.3282 5.4154
41.0 5.0388 5.1188 5.2047
42.0 4.8351 4.9188 5.0033
43.0 4.6454 4.7275 4.8107
44.0 4.4640 4.5449 4.6268
45.0 4.2907 4.3701 4.4504
46.0 4.1300 4.2050 4.2850
47.0 3.9665 4.0432 4.1207
48.0 3.8161 3.8902 3.9663
49.0 3.6701 3.7438 3.8185
Table 27. Thermistor indoor coil
resistance (continued)
x (C°)
Rmin
(kΩ)
Rnom
(kΩ)
Rmax
(kΩ)
50.0 3.5314 3.6037 3.6770
51.0 3.3982 3.4691 3.6410
52.0 3.2707 3.3402 3.4107
53.0 3.1487 3.2169 3.2860
54.0 3.0320 3.0967 3.1665
55.0 2.9201 2.9856 3.0519
56.0 2.8130 2.8771 2.9422
57.0 2.7104 2.7732 2.8370
58.0 2.6121 2.6736 2.7380
59.0 2.5179 2.5781 2.6393
60.0 2.4276 2.4855 2.5464
61.0 2.3410 2.3986 2.4573
62.0 3.2579 2.3144 2.3719
63.0 2.1782 2.2335 2.2898
64.0 2.1018 2.1559 2.2110
65.0 2.0284 2.0813 2.1353
66.0 1.9580 2.0098 2.0628
67.0 1.8904 1.9411 1.9928
68.0 1.8255 1.8750 1.9257
69.0 1.7631 1.8116 1.8612
70.0 1.7631 1.8116 1.8512
71.0 1.6456 1.6921 1.7395
72.0 1.5903 1.6357 1.6822
73.0 1.5371 1.5816 1.6270
74.0 1.4860 1.5816 1.6270
75.0 1.4368 1.4793 1.5229
76.0 1.3895 1.4311 1.4737
77.0 1.3440 1.3847 1.4284
78.0 1.3003 1.3400 1.3809
79.0 1.2581 1.2970 1.3370
80.0 1.2176 1.2558 1.2947
81.0 1.1785 1.2158 1.2540
82.0 1.1409 1.1773 1.2148
83.0 1.1047 1.1403 1.1770
84.0 1.0698 1.1047 1.1405
85.0 1.0362 1.0703 1.1054
86.0 1.0038 1.0372 1.0715
87.0 0.9726 1.0052 1.0388
88.0 0.9425 0.9744 1.0073
89.0 0.9135 0.9447 0.9769
90.0 0.8858 0.9161 0.9476
Table 27. Thermistor indoor coil
resistance (continued)
x (C°)
Rmin
(kΩ)
Rnom
(kΩ)
Rmax
(kΩ)
PTAC-SVX01C-EN 39
Maintenance
WARNING
Hazardous Voltage!
Disconnect all electric power,
including remote disconnects before
servicing. Follow proper lockout/
tagout procedures to ensure the
power can not be inadvertently
energized. Failure to disconnect
power before servicing could result
in death or serious injury.
Reversing Valve
Occasionally the reversing valve may
stick in the heating or cooling
position or in the mid-operation.
When stuck in the mid-position, part
of the discharge gas from the
compressor is directed back to the
suction side resulting in excessively
high suction pressure.
Check the operation of the valve by
starting the system and switching the
operation from COOLING to
HEATING and then back to COOLING.
If no voltage is registered to the coil,
check the operation of the reversing
relay and the continuity of the
connecting wires.
If voltage is registered at the coil, tap
the valve body lightly while switching
the system from HEATING to
COOLING etc. If this fails to cause the
valve to switch position, remove the
coil connector cap and wiring and
test the continuity of the valve coil. If
the coil does not test continuous
replace it.
If the valve is inoperative, replace.
Component Replacement
Replacement of the compressor,
evaporator, condenser, capillary
tubes and reversing valve must be in
accordance with accepted service
practices. These procedures include
a complete evacuation of both high
and low sides, and changing of the
capillary tube assembly whenever
the refrigerant system is opened.
Before replacing a component in the
sealed system, make sure that the
cause for complaint does not lie in
the electrical circuit, control, overload
or is due to some other reason. The
serviceman must be familiar with the
operational characteristics of the
product and should not jump to
conclusions.
Temperature-Actuated Drain
Valve (model PTHE Only)
The PTHE is equipped with a
temperature-actuated drain valve
located in the base pan. As the
outdoor ambient decreases to 55°F,
the drain valve will begin to open.
The valve will be completely open
when the outdoor ambient
temperature falls to 50°F.
WARNING
Hazardous Voltage!
Disconnect all electric power,
including remote disconnects before
servicing. Follow proper lockout/
tagout procedures to ensure the
power can not be inadvertently
energized. Failure to disconnect
power before servicing could result
in death or serious injury.
Unit Disassembly Procedures
1. Disconnect power to the unit.
2. Remove the unit front cover.
3. Remove the three screws on
each side of the chassis that
secure the chassis to the wall
sleeve.
4. Carefully slide the chassis out of
the wall sleeve and place on floor
or a protected cart.
WARNING
Hazardous Voltage!
Disconnect all electric power,
including remote disconnects before
servicing. Follow proper lockout/
tagout procedures to ensure the
power can not be inadvertently
energized. Failure to disconnect
power before servicing could result
in death or serious injury.
Note: ALL phases of this
installation must comply with
NATIONAL, STATE AND
LOCAL CODES. Improper
wiring or installation may
damage thermostat.
Power Cord Removal
1. Disconnect power to the unit.
2. Remove the unit front cover.
3. Remove two screws of power
cord connector front cover.
4. Remove the power cord strain
relief.
5. Remove power cord from
connector.
Power cord Installation
1. Install power cord to connector.
Gently press the connector into
position until top and bottom
latches engage.
2. Reinstall the power cord strain
relief.
3. Reinstall power cord connector
front cover.
4. Reinstall the unit front cover.
Capacitor Removal
1. Remove the control box. Refer to
the power cord disassembly for
instructions on removing the
control box.
2. Remove the screw securing the
capacitor to the control box.
Heater Assembly Removal
1. Remove the strain relief.
2. Remove the three screws
securing the discharge screen to
the chassis.
3. Unplug the power cord
connector and remove the power
cord.
Removing the Indoor Coil and
Indoor Air Thermistors
1. Remove the front cabinet.
2. Remove the control box cover.
3. Disconnect the indoor coil/air
thermistor wiring from the
control board.
4. Locate the indoor coil/air
thermistor on the suction tube or
evaporator. Gently pull the
thermistor from the housing.
5. Remove the indoor coil/air
thermistor from the unit.
40 PTAC-SVX01C-EN
Maintenance
Removing the Outdoor Coil
and Outdoor Air Thermistors
1. Remove the chassis from the
wall.
2. Remove the front cabinet.
3. Remove the control box cover.
4. Disconnect the outdoor coil/air
thermistor wiring from the
control board.
5. Gently pull outdoor coil
thermistor from the bracket near
the capillary tube.
6. Gently remove outdoor air
thermistor which is located at the
drain valve.
7. Remove the outdoor coil/air
thermistor from the unit.
Indoor Fan and Motor
1. Remove the chassis from the
wall.
2. Remove the front cabinet.
3. Remove the heater/discharge
deck assembly. (Refer to the
heater disassembly instructions)
4. Remove the control box cover.
Disconnect the control wiring.
Remove the control box. Refer to
the power cord disassembling
for instructions on
disassembling the control box.
5. Remove the indoor fan motor
bracket screws (3) as shown.
6. Remove the set screw (you will
need a long Allen wrench)
securing the indoor fan to the
motor shaft and remove the
indoor fan and motor.
Outdoor Fan and Motor
1. Follow the directions for
removing the condenser except
don’t braze or remove the tubing
connecting to the condenser.
Capturing the system refrigerant
is also not necessary.
2. Remove the screw on the right
side of the unit (If you are
looking at the back of the PTAC)
toward the bottom of the PTAC
near the lip of the basepan.
3. Lift the condenser up and over
the lip of the basepan and move
just enough to gain access to the
outdoor fan and motor. Be
careful not to damage the
bottom of the condenser by
sitting it on the lip of the
basepan. Also, use caution when
bending the condenser to gain
access to the outdoor fan and
motor. The tubing is very fragile
and must be treated with care.
4. Remove the fan.
5. Remove the fan motor by
removing the two screws
securing it to the fan motor
bracket.
6. Disconnect the fan motor wiring
from the control by removing the
wire junction box cover on the
partition panel above the control
panel cover.
Control Board Replacement
Procedure
WARNING
Hazardous Voltage!
Disconnect all electric power,
including remote disconnects before
servicing. Follow proper lockout/
tagout procedures to ensure the
power can not be inadvertently
energized. Failure to disconnect
power before servicing could result
in death or serious injury.
Note: Before replacing the whole
control board, make sure that
the control board’s fuse is still
functioning. The specs for
the control board fuse are:
5X20mm, 250V, 315mA, fast
acting. For more information
on a blown fuse on the
Control Board, check the
Troubleshooting section of
this document.
1. Remove plastic cabinet front and
the metal cover that encloses the
control board
2. Remove the replacement board
from its package and set the
power jumper to match the unit
voltage .
3. There are two different pin
connections, one for 230/208
VAC and another for 265 VAC .
The jumper for the 115 VAC
board is pre-installed in the P8
to P9 position.
Note: This is a very important
step, and it might lead to
damage of the control
board if the jumper is not
properly set.
4. Remove connections from the
existing control board, tagging
wires as required to ensure
correct re-assembly.
5. Remove 2 screws from the front
plastic mounting ears. Remove
the screw from the green wire
ground. Slide plastic chassis and
board back and lift out of place.
6. Engage catches on bottom of
plastic chassis of replacement
assembly with sheet metal
control box and slide forward to
lock in position. Re-install two
screws through the front plastic
mounting ears. Re-install green
ground wire.
7. Re-connect the wiring harness to
the new assembly in the same
positions that they were before
removal. This includes
temperature thermistors, as well
as the thermostats, zone sensors
and energy management.
8. Reinstall the sheet metal cover
over the control board.
9. Position the front cabinet over
the chassis and push the sides
until the retaining clips engage.
Figure 28. Power jumper
PTAC-SVX01C-EN 41
Diagnostics
The controller is equipped to display
a diagnostic code through the
interface module; if the display is not
present (Class 2 control), there is no
method to retrieve the diagnostic
codes from the unit.
If there is no interface module to
indicate the presence of a diagnostic,
service will only be triggered by a
comfort or operational complaint.
The controller will only display the
most severe diagnostic present.
Translating Multiple
Diagnostics
The controller senses and records
each diagnostic independently of
other diagnostics. It is possible to
have multiple diagnostics affect the
operation of the unit, but only the
most severe diagnostic will be
displayed.
Resetting Diagnostics
A reset clears any latching
diagnostics and allows the control to
try to run the PTAC normally. If the
latching condition is still present
after the reset, the control will shut
down the PTAC. A reset will reset a
unit that is running normally. A reset
is just like cycling power to the unit.
There are two ways to reset
diagnostics:
1. Manual output test at the
controller
2. Cycling power to the controller
Manual Output Test
When manual test has been initiated,
the controller exercises all outputs in
a predefined sequence. The last step
of the sequence resets the controller.
See the Manual output test section
on page 22 for more information
about the manual output test.
Cycling Power
When someone turns off the
controller’s power, then re-applies
power, the unit cycles through a
power up sequence. By default, the
controller will attempt to reset all
diagnostics at power up.
Diagnostics present at power up and
those that occur after power up will
be handled according to the defined
unit diagnostics sequences (see
Diagnostics table below)
Table 28. Diagnostic codes
Severity
Level
Diagnostic
Code
Diagnostic
Description Compressor
Auxiliary
Heat Indoor Fan
1
(severest)
C1 Compressor Failure DISABLED ENABLED ENABLED
2 C2 Indoor Temperature
Unit Sensor Failure1
ENABLED ENABLED ENABLED
3 C3 Indoor Temperature
Display Sensor Failure
ENABLED ENABLED ENABLED
4 C4 Indoor Coil
Temperature Failure
ENABLED2 ENABLED ENABLED
5 C5 Outdoor Temperature
Failure
ENABLED,
run as PTEE
ENABLED,
run as PTEE
ENABLED,
run as PTEE
6 C6 Outdoor Coil
Temperature Failure
ENABLED,
run as PTEE
ENABLED,
run as PTEE
ENABLED,
run as PTEE
7C7Configuration
Corrupted
ENABLED ENABLED ENABLED
8 - No diagnostic present ENABLED ENABLED ENABLED
Table 29. Latching diagnostics, reset
required
Code Diagnostic Description Description
C1 Compressor Failure OLP has had multiple trips (3)
C7 Configuration Corrupted configuration failure
Table 30. Automatically resetting
diagnostics
Code Diagnostic Description Description
C1 Indoor Temperature - No Backup
Available
No source of indoor temperature is
available
C2 Indoor Temperature - Unit Sensor
Failure1
Unit indoor temperature valid then not
valid
C3 Indoor Temperature - Display Sensor
Failure1
Display indoor temperature valid then not
valid
C4 Indoor Coil Temperature Failure Indoor Coil Temperature valid then not
valid
C5 Outdoor Temperature Failure Outdoor Temperature valid then not valid
C5 Outdoor Coil Temperature Failure Outdoor Coil temp valid then not valid
Troubleshooting
42 PTAC-SVX01C-EN
Troubleshooting
Table 31. Compressor output does not energize
Probable cause Explanation
Random restart timer All controller outputs remain off until the timer expires.
Selected mode OFF When off is selected at the display to the controller, the unit controls all outputs off.
Selected mode FAN ONLY When fan only is selected at the display to the controller, the unit only allows the indoor fan to energiz.
Diagnostic present A specific list of diagnostics affects compressor operation. For more information, see the Diagnostics section in the
manual.
No power to the
controller
If the controller does not have power, the compressor does not operate. For the controller to operate normally, it
must have an input voltage of 115 or 230/208, 265 VAC.
Manual output test The controller includes a manual output test sequence you can use to verify output operation and associated
output wiring. However, based on the current step in the test sequence, the compressor may not be on. Refer to
the Manual Output Test section.
Unit wiring The wiring between the controller output and the compressor must be present and correct for normal operation.
Indoor Coil Freeze
protection
The compressor has been turned off because the indoor coil temperature has fallen below 35°F and has not risen
above 50°F
Table 32. Indoor/remote fan outputs do not energize
Probable cause Explanation
Random restart timer All controller outputs remain off until the timer expires.
Normal operation Depending on the configuration selected the fan(s) may be only cycle with the compressor output
Selected mode OFF When off is selected at the display to the controller, the unit controls all outputs off.
Diagnostic present A specific list of diagnostics affects fan operation. For more information, see the Diagnostics section in the manual.
No power to the
controller
If the controller does not have power, the compressor does not operate. For the controller to operate normally, it
must have an input voltage of 230/208, 265 VAC.
Manual output test The controller includes a manual output test sequence you can use to verify output operation and associated output
wiring. However, based on the current step in the test sequence, the fan(s) may not be on. Refer to the Manual
Output Test section.
Unit wiring The wiring between the controller outputs and the fan relays and contacts must be present and correct for normal
fan operation.
Table 33. Outdoor fan output does not energize
Probable cause Explanation
Random restart timer All controller outputs remain off until the timer expires.
Selected mode OFF When off is selected at the display to the controller, the unit controls all outputs off.
Selected mode FAN ONLY When fan only is selected at the display to the controller, the unit only allows the indoor fan to energize.
Diagnostic present A specific list of diagnostics affects compressor and therefore the outdoor fan operation. For more information, see
the Diagnostics section in the manual.
No power to controller If the controller does not have power, the compressor does not operate. For the controller to operate normally, it
must have an input voltage of 115 or 230/208, 265 VAC.
Manual output test The controller includes a manual output test sequence you can use to verify output operation and associated output
wiring. However, based on the current step in the test sequence, the outdoor fan may not be on. Refer to the
Manual Output Test section.
Unit wiring The wiring between the controller output and the outdoor fan must be present and correct for normal operation.
Coil Burst Protection The outdoor fan has been turned off because the indoor coil temperature has risen above 140°F and has not fallen
below 125°F
Normal operation The outdoor fan cycles with the compressor output
Defrost Cycle During the active defrost cycle the outdoor fan is controlled off. See the section on defrost control.
Unit wiring The wiring between the controller outputs and the fan relays and contacts must be present and correct for normal
fan operation.
PTAC-SVX01C-EN 43
Troubleshooting
Table 34. Reversing valve output does not energize
Random restart timer Explanation
Power up control wait All controller outputs remain off until the timer expires.
Se le c te d m o d e O F F, FA N
ONLY
Reversing valve held in current state because compressor use is not allowed.
Diagnostic present A specific list of diagnostics affects compressor operation. For more information, see the Diagnostics section in the
manual.
No power to the
controller
If the controller does not have power, the reversing valve does not operate. For the controller to operate normally, it
must have an input voltage of 115 or 208-230, 265 VAC.
Manual output test The controller includes a manual output test sequence you can use to verify output operation and associated output
wiring. However, based on the current step in the test sequence, the reversing valve may not be energized. Refer to
the Manual Output Test section.
Unit wiring The wiring between the controller output and the reversing valve must be present and correct for normal operation.
Normal operation PTHE unit is in heating mode.
Diagnostic present A specific list of diagnostics affects unit operation. For more information, see the Diagnostics section in the manual.
Table 35. Auxiliary heat output does not energize
Probable cause Explanation
Random restart timer All controller outputs remain off until the timer expires.
Selected mode OFF When off is selected at the display to the controller, the unit controls all outputs off.
Selected mode FAN
ONLY
When fan only is selected at the display to the controller, the unit only allows the indoor fan to energize.
Diagnostic present A specific list of diagnostics affects unit operation. For more information, see the Diagnostics section in the manual.
No power to the
controller
If the controller does not have power, the compressor does not operate. For the controller to operate normally, it
must have an input voltage of 115 or 230/208, 265 VAC.
Manual output test The controller includes a manual output test sequence you can use to verify output operation and associated output
wiring. However, based on the current step in the test sequence, the auxiliary heat may not be on. Refer to the
Manual Output Test section.
Unit wiring The wiring between the controller output and the auxiliary heat must be present and correct for normal operation.
Indoor Coil Freeze
protection
The compressor has been turned off because the indoor coil temperature has fallen below 35°F and has not risen
above 50°F.
Normal operation Auxiliary heat may not be needed to meet the load conditions see the section dealing with Auxiliary Heat Control.
Defrost Cycle During the active defrost cycle the auxiliary heat is controlled off. See the section on defrost control. Reversing
Valve output does not energize.
Table 36. Ventilation output does not energize
Probable cause Explanation
Random restart timer All controller outputs remain off until the timer expires.
Selected mode OFF When off is selected at the display to the controller, the unit controls all outputs off.
Diagnostic present A specific list of diagnostics affects unit operation. For more information, see the Diagnostics section in the manual.
No power to controller If the controller does not have power, the compressor does not operate. For the controller to operate normally, it
must have an input voltage of 115 or 230/208, 265 VAC.
Manual output test The controller includes a manual output test sequence you can use to verify output operation and associated output
wiring. However, based on the current step in the test sequence, the ventilation output may not be on. Refer to the
Manual Output Test section.
Unit wiring The wiring between the controller output and the ventilation must be present and correct for normal operation.
Normal operation See the section on Ventilation operation.
Defrost Cycle During the active defrost cycle the outdoor fan is controlled off. See the section on defrost control.
44 PTAC-SVX01C-EN
Troubleshooting
Table 37. Condensate pump does not energize
Probable cause Explanation
Random restart timer All controller outputs remain off until the timer expires.
Selected mode OFF When off is selected at the display to the controller, the unit controls all outputs off.
No power to controller If the controller does not have power, the compressor does not operate. For the controller to operate normally, it
must have an input voltage of 115 or 230/208, 265 VAC.
Manual output test The controller includes a manual output test sequence you can use to verify output operation and associated output
wiring. However, based on the current step in the test sequence, the condensate Pump may not be enabled. Refer to
the Manual Output Test section.
Unit wiring The wiring between the controller output and the Condensate Pump must be present and correct for normal
operation.
Normal operation Condensate Pump is available only with Heat Pumps. Unit is in active defrost, or outdoor temperature is below enable
point.
Unit wiring The wiring between the controller outputs and the fan relays and contacts must be present and correct for normal
condensate pump operation.
Defrost Cycle During the active defrost cycle the condensate pump power is removed. See the section on defrost control.
Table 38. Output on when the mode is off
Probable cause Explanation
Fan Configuration Fan is configured to run on high in off mode (see configuration section).
Freeze Protection While in off mode, freeze protection may be active. This will cause the indoor fan to run at high speed, and the
remote fan and auxiliary heat will be on.
Fan Delay Off The indoor fan continues to run after the compressor or auxiliary heat will be on.
Table 39. Control fuse is blown
Symptom
The generic thermostat does not work
The energy input does not work
The ventilation input does not work
The remote fan output does not work
PTAC-SVX01C-EN 45
Figure 29. 230/208V wiring diagram (07 models)
GR
YL
OR
BK
HI
L
N
L
H
N
BR
YL
LO
HI
N
RD
RD
YL
RD
BK
12345678
3.0KW
12345678
8765432 1
2.0KW
654321
RD
BK
WH
YL/GR
1.0KW
2.0KW
2.0KW
RD
RD
BK
REMOTE
FAN
RELAY
THERMOSTAT
REMOTE
VENTILATION
INPUT
DISPLAY
REMOTE
INPUT
ENERGY
L
BK
N
RD
LOCAL
DISPLAY
INDOOR TEMPERATURE
INDOOR COIL TEMPERATURE
OUTDOOR COIL TEMPERATURE
OUTDOOR TEMPERATURE
TL
TL FL
NC
NO
COM
BK
COM
NO
208/230
265
K8 HEAT
K9 COOL
P8
P9
P10
RF
CRW
GL
O
VT
EN
Y
GH
TB2 TB1
P4
P3 P2 P1
AIR
COIL
F1 T1
Cond
Vent
Fan Rev Valve
P15 P14 P13 P12 P11
CP - CONDENSATE PUMP
RD - RED
PVD - POWER VENTILATION DOOR
GR - GREEN
RVS - REVERSING VALVE
WH - WHITE
IM - INDOOR MOTOR
BK - BLACK
OM - OUTDOOR MOTOR
OR - ORANGE
COMP - COMPRESSOR YL - YELLOW
FACTORY WIRING
BL - BLUE
FIELD WIRING
BR - BROWN
1) For 208/230 VAC unit, connect P8 and P10.
2) For cooling only unit, there is no outdoor temperature sensor and reversing valve.
3) For different electric heater capacity, refer to IOM for power cord selection.
4) The specs for the control board fuse are: 5 x 20mm, 250V, 315mA, fast acting.
GND WIRE
RD
P7
OR
Wiring Diagram
46 PTAC-SVX01C-EN
Wiring Diagram
Figure 30. 230/208V Wiring diagram (09, 12, 15 models)
GR
YL
OR
BK
HI
L
N
L
H
N
BR
YL
LO
HI
N
RD
RD YL
RD
BK
87654321 5.0KW
12345678
3.0KW
12345678
8765432 1
2.0KW
654321
BL
RD
BK
WH
YL/GR
1.0KW
2.0KW
2.0KW
RD
RD
BK
REMOTE
FAN
RELAY
THERMOSTAT
REMOTE
VENTILATION
INPUT DISPLAY
REMOTE
INPUT
ENERGY
L
BK
N
RD
LOCAL
DISPLAY
INDOOR TEMPERATURE
INDOOR COIL TEMPERATURE
OUTDOOR COIL TEMPERATURE
OUTDOOR TEMPERATURE TL
TL FL
NC
NO
COM
BK
COM
NO
208/230 265
K8 HEAT K9 COOL
P8
P9
P10
RF CRWGL OVT EN
YGH
TB2 TB1
P4
P3 P2 P1
AIR COIL F1 T1
Cond Vent Fan Rev Valve
P15 P14 P13 P12 P11
CP - CONDENSATE PUMP RD - RED
PVD - POWER VENTILATION DOOR GR - GREEN
RVS - REVERSING VALVE WH - WHITE
IM - INDOOR MOTOR BK - BLACK
OM - OUTDOOR MOTOR OR - ORANGE
COMP - COMPRESSOR YL - YELLOW
FACTORY WIRING BL - BLUE
FIELD WIRING BR - BROWN
GND WIRE
RD
P7
OR
1
RVS
IM OM COMP
CP PVD
1
23
4
211
2
1) For 208/230 VAC unit, connect P8 and P10.
2) For cooling only unit, there is no outdoor temperature sensor and reversing valve.
3) For different electric heater capacity, refer to IOM for power cord selection.
4) The specs for the control board fuse are: 5 x 20mm, 250V, 315mA, fast acting.
PTAC-SVX01C-EN 47
Wiring Diagram
Figure 31. 265V Wiring diagram (07 models)
GR
OR
YL
OR
BK
HI
L
N
L
H
N
BR
YL
LO
HI
N
RD
RD
YL
RD
BK
12345678
3.0KW
12345678
8765432 1
2.0KW
65432 1
RD
BK
WH
YL/GR
1.0KW
2.0KW
2.0KW
RD
RD
BK
REMOTE
FAN
RELAY
THERMOSTAT
REMOTE
VENTILATION
INPUT
DISPLAY
REMOTE
INPUT
ENERGY
L
BK
N
RD
LOCAL
DISPLAY
INDOOR TEMPERATURE
INDOOR COIL TEMPERATURE
OUTDOOR COIL TEMPERATURE
OUTDOOR TEMPERATURE
TL
TL FL
NC
NO
COM
BK
COM
NO
K8 HEAT
K9 COOL
RF
CRW
GL
O
VT
EN
Y
GH
TB2 TB1
P4
P3 P2 P1
AIR
COIL
F1 T1
Cond
Vent
Fan
Rev Valve
P15 P14 P13 P12 P11
CP - CONDENSATE PUMP
RD - RED
PVD - POWER VENTILATION DOOR
GR - GREEN
RVS - REVERSING VALVE
WH - WHITE
IM - INDOOR MOTOR
BK - BLACK
OM - OUTDOOR MOTOR
OR - ORANGE
COMP - COMPRESSOR
YL - YELLOW
FACTORY WIRING
BL - BLUE
FIELD WIRING
BR - BROWN
1) For 265 VAC unit, connect P8 and P9.
2) For cooling only unit, there is no outdoor temperature sensor and reversing valve.
3) For different electric heater capacity, refer to IOM for power cord selection.
4) The specs for the control board fuse are: 5 x 20mm, 250V, 315mA, fast acting.
GND WIRE
RD
FUSE
208/230
265
P8
P9
P10 P7
48 PTAC-SVX01C-EN
Wiring Diagram
Figure 32. 265V Wiring diagram (09, 12, 15)
GR
OR
YL
OR
BK
HI
L
N
L
H
N
BR
YL
LO
HI
N
RD
RD YL
RD
BK
87654321 5.0KW
12345678
3.0KW
12345678
8765432 1
2.0KW
654321
BL
RD
BK
WH
YL/GR
1.0KW
2.0KW
2.0KW
RD
RD
BK
REMOTE
FAN
RELAY
THERMOSTAT
REMOTE
VENTILATION
INPUT DISPLAY
REMOTE
INPUT
ENERGY
L
BK
N
RD
LOCAL
DISPLAY
INDOOR TEMPERATURE
INDOOR COIL TEMPERATURE
OUTDOOR COIL TEMPERATURE
OUTDOOR TEMPERATURE TL
TL FL
NC
NO
COM
BK
COM
NO
K8 HEAT K9 COOL
RF CRWGL OVT EN
YGH
TB2 TB1
P4
P3 P2 P1
AIR COIL F1 T1
Cond Vent Fan Rev Valve
P15 P14 P13 P12 P11
CP - CONDENSATE PUMP RD - RED
PVD - POWER VENTILATION DOOR GR - GREEN
RVS - REVERSING VALVE WH - WHITE
IM - INDOOR MOTOR BK - BLACK
OM - OUTDOOR MOTOR OR - ORANGE
COMP - COMPRESSOR YL - YELLOW
FACTORY WIRING BL - BLUE
FIELD WIRING BR - BROWN
GND WIRE
RD
FUSE
208/230 265
P8
P9
P10 P7
RVS
IM OM COMP
CP PVD
1
23
4
211
2
1) For 265 VAC unit, connect P8 and P9.
2) For cooling only unit, there is no outdoor temperature sensor and reversing valve.
3) For different electric heater capacity, refer to IOM for power cord selection.
4) The specs for the control board fuse are: 5 x 20mm, 250V, 315mA, fast acting.
1
PTAC-SVX01C-EN 49
Wiring Diagram
Figure 33. Energy management system
Figure 34. 3rd party class 2 thermostat
wiring
Figure 35. Remote
display wiring
RWYGHGL
OVT EN
RWYGHGL
OVT EN
+_
+_
50 PTAC-SVX01C-EN
Full 1st Year Warranty
Trane will repair or replace any part
which proves to be defective due to
workmanship or materials, free of
charge. This includes parts and labor.
Full 2nd - 5th Sealed
System Warranty
Trane will repair or replace the
evaporator, condenser, compressor,
or connecting tubing which proves to
be defective due to workmanship or
materials, free of charge. This
includes parts and labor.
Limited 2nd through 5th
Year Functional Parts
Warranty
During the 2nd through 5th year,
Trane will provide functional parts
which prove to be defective due to
workmanship or materials.
Components covered are switches,
solenoids, fan motors, thermistors,
circuit boards, factory installed
heaters, blower wheel, fan propeller,
capacitors, compressor overloads
and drain valves.
This limited warranty does not
include diagnostic time, labor or any
transportation and/or reinstallation
charges that may be required.
Warranty
Literature Order Number PTAC-SVX01C-EN
Date 09/06
Supersedes PTAC-SVX01B-EN
Stocking Location Webb/Mason
The manufacturer has a policy of continuous product and product data improvement and reserves
the right to change design and specifications without notice.