Diagnostic Troubleshooting Repair Series R® 70-125 Ton Air-Cooled and Water-Cooled Rotary Liquid Chillers Model RTAA 70-125 Ton RTWA 70-125 Ton RTUA 70-125 Ton August 2005 © American Standard Inc. 2005 RLC-SVD03A-EN NOTICE: Warnings and Cautions appear at appropriate sections throughout this literature. Read these carefully. WARNING: Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. CAUTION: Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices. CAUTION: Indicates a situation that may result in equipment or propertydamage only accidents. Important - Read This First! This manual is intended for experienced service personnel familiar with the proper use of electrical diagnostic instruments and all personal safety procedures when working on live electrical circuits. This Manual is not intended for individuals who have not been properly trained in handling live electrical circuits. Environmental Concerns! Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment. Trane advocates the responsible handling of all refrigerants— including industry replacements for CFCs such as and HCFCs and HFCs. Responsible Refrigerant Practices! Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified. The Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them. WARNING Contains Refrigerant! System contains oil and refrigerant under high pressure. Recover refrigerant to relieve pressure before opening the system. See unit nameplate for refrigerant type. Do not use non-approved refrigerants, refrigerant substitutes, or refrigerant additives. Failure to follow proper procedures or the use of non-approved refrigerants, refrigerant substitutes, or refrigerant additives could result in death or serious injury or equipment damage. 2 RLC-SVD03A-EN Contents General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Service Philosophy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 System Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 System Level Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Interprocessor Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 IPC Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Troubleshooting Modules Using IPC Diagnostics . . . . . . . . . . . . . . . . . . . . . . . 9 Troubleshooting Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Temperature Sensor Checkout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Temperature Sensor Checkout Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Compressor Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Restart Inhibit Timer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Compressor Start/Stop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Variable Speed Inverter/Condenser Fan Control . . . . . . . . . . . . . . . . . . 21 Outdoor Air Temperature and Fan Control . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 VSF Inverter Fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Current Transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 CT and MCSP Compressor Current Input Checkout Procedure . . . . . . . . . . . 24 Under-Over Voltage Transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Under-Over Voltage Transformer Checkout . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Compressor Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 Checkout Procedure for MCSP Load/Unload Outputs . . . . . . . . . . . . . . . . . . 35 Checkout Procedure for the Slide Valve and Load/ Unload Solenoids . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 Checkout Procedure for MCSP Step Load Output . . . . . . . . . . . . . . . . . . . . . 39 Checkout Procedure for Step Load Solenoid Valve and Piston . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40 Module Power and Miscellaneous I/O . . . . . . . . . . . . . . . . . . . . . . . . . . 41 Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 Clear Language Display (CLD) 1U6 Keypad Overview . . . . . . . . . . . . . . . . . . 42 Chiller Module (CPM) (1U1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 Options Module (CSR) (1U2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 Electronic Expansion Valve Module (EXV) (1U3) . . . . . . . . . . . . . . . . . . . . . . . 58 Compressor Module (MCSP) (1U4 AND 1U5) . . . . . . . . . . . . . . . . . . . . . . . . . 72 Interprocessor Communication Bridge Module (IPCB) (1U7) . . . . . . . . . . . . . 78 LonTalk® Communications Interface - Chillers Module (LCI-C) (1U8) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79 Variable Speed Fan System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80 Inverter Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80 Troubleshooting Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82 Other Service Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85 Service Pumpdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85 Circuit Lockout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87 Circuit Diagnostic Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87 RLC-SVD03A-EN 3 General Information The Unit Control Modules (UCMs) described in this troubleshooting guide provide a microprocessor based refrigeration control system, intended for use with Trane 70-125 ton helical rotor chillers. Six types of modules are used, and throughout this publication will be referred to by their abbreviations or their Line Wiring Drawing Designations, see Table 1. Table 1 Unit Control Module Designations Line Drawing Designation Controller Name Chiller Module Abbrev. CPM 1U2 Options Module CSR 1U3 Expansion Valve Module EXV 1U4 & 1U5 Compressor Module MCSP A & B 1U6 Clear Language Display CLD 1U7 Interprocessor Communications Bridge (Remote Display Buffer) IPCB Service Philosophy With the exception of the fuses, no other parts on or within the modules are serviceable. The intent of the troubleshooting is to determine which module is potentially at fault and then to confirm a module problem. This is done either through voltage or resistance measurements at the suspected input or output terminals or by checking related wiring and external control devices (connectors, sensors, transformers, contactors etc.) in a process of elimination. Once a problem has been traced to a module, the module can be easily replaced using only basic tools. In general, all dip switch settings of the replaced modules should be copied onto the replacement module's dip switches before applying control power. CPM replacement is more involved as there are numerous configuration and set-up items that must be programmed at the Clear Language Display in order to insure proper unit operation. It is helpful to include with the return of a module, a brief explanation of the problem, sales office, job name, and a contact person for possible follow-up. The note can be slipped into the module enclosure. Early and timely processing of Field Returns allows for real measurements of our product quality and reliability, providing valuable information for product improvement and possible design changes. 4 RLC-SVD03A-EN General Information System Description The CPM is the master module and coordinates operation of the entire system. One is used per chiller. The MCSP is a compressor protection module with one being used for each of the compressors in the chiller. The EXV is the expansion valve controller module which controls two Electronic Expansion Valves. There is one valve on each of the two refrigeration circuits. The CLD is a two line, 40 character alphanumeric interface to the system. It allows the operator to read operating and diagnostic information, as well as change control parameters. The Interprocessor Communications Bridge (IPCB) provides an extension of the IPC link to the Remote Clear Language Display, while protecting the integrity of the IPC communications link between the local modules. The CSR is an optional communications module which allows for communications between the chiller and a remote building automation system (i.e. Tracer, Tracer Summit, Generic BAS). All modules in the system communicate with each other over a serial interprocessor communications bus (IPC) consisting of a twisted wire pair “daisy chain” link and RS485 type signal levels and drive capability. Multiple modules of the same type (i.e. MCSPs) in an operating system are differentiated by address dip switches. All the modules operate from 115VAC, 50 or 60Hz power and each have their own internal step-down transformer and power supply. Each is individually fused with a replaceable fuse. The modules also are designed to segregate their high and low voltage terminals by placing the high voltage on the right side of the module and the low voltage on the left. When stacked, segregation is maintained. In addition to the modules, there are a number of “system level” components that are closely associated with the modules. These components were specifically designed and/or characterized for operation with the modules. For this reason, the exact Trane part must be used in replacement. System Level Components Description The following is a list of all the components that may be found connected to the various modules. Transformer, Under/Over voltage Current Transformer - Compressor Evap EntlLvg Water Temp Sensor Pair Sat Evap/Cprsr Suc Rfgt Temp. Sensor Pair Sat Cond RfgtIOil Temp Sensor Pair Outdoor Air Temperature Sensor Zone Temp Sensor Connector (UCM mating connectors) Connector Keying Plug Electronic Expansion Valve RLC-SVD03A-EN 5 General Information High Pressure Cutout Switch Low Pressure Cutout Switch Variable Speed Fan Drive Motor Temperature Thermostats Slide Valve Load/Unload Solenoids Step Load Solenoid Valve Chiller Module (CPM) IU1 The CPM module performs machine (chiller) level control and protection functions. Only one CPM is present in the chiller control system. The CPM acts as the master controller to the other modules, running top level machine control algorithms, initiating and controlling all inter-module communication over the IPC, and providing parameters and operational requests (i.e. loading and unloading, starting and stopping) to the other modules in the system via the IPC. The CPM also contains nonvolatile memory, which allows it to remember configuration and set-up values, setpoints, historical diagnostics etc. for an indefinite period of time following a power loss. Direct hard wired I/O associated with the CPM includes low voltage analog inputs, low voltage binary inputs, 115 VAC binary inputs and 115 VAC (rated) relay outputs. See Chiller Module (CPM) (1U1) on page 46 for further details. Compressor Module (MCSP) 1U4 and 1U5 The MCSP module employs the input and output circuits associated with a particular compressor and refrigeration circuit. Two MCSP modules are used in the UCM system, one for each compressor. Included are low voltage analog and digital circuits, 115 VAC input, and 115 VAC output switching devices. The output switching devices associated with the compressor motor controlling function are contained in this module. The outputs of this module control one compressor motor stop/start contactor, one compressor motor transition contactor, one oil heater, three solenoid valves (compressor load, compressor unload, step loader), and up to four fan motor contactors or groups of contactors. Refer to the chiller's line wiring diagrams for details. Dip switches are provided for redundant programming of the compressor current overload gains, and for unique IPC address identification during operation. Inputs to this module include motor temperature thermostats, thermisters, and safety switches. See Compressor Module (MCSP) (1U4 AND 1U5) on page 72 for details. Expansion Valve Module (EXV) 1U3 The EXV module provides power and control to the stepper motor driving the electronic expansion valves of the chiller. Each module handles two valves, one in each refrigeration circuit. Input to the EXV Module is provided by four temperature sensors (two per refrigeration circuit). The sensors are located in the respective refrigeration circuits of the chiller and sense Saturated Evaporator and Suction temperatures and calculate the superheat temperatures. High level operational commands as well as superheat setpoints are received by the EXV Module over the IPC from the CPM module to modulate the EXV's. 6 RLC-SVD03A-EN General Information Real time data for temperatures, diagnostics and control algorithms etc. are made available to the CPM and the other modules for display and for input to higher level functions. See Electronic Expansion Valve Module (EXV) (1U3) on page 58 for details. Options Module (CSR) 1U2 The CSR module is an optional part of the system and employs communications circuits for interface to Trane Building Automation Systems, done through 1C17. The CSR also provides inputs for hard wired external setpoints and reset functions. Included are low voltage analog and digital input circuits. See Options Module (CSR) (1U2) on page 50 for details. Clear Language Display (CLD) 1U6 The CLD Module provides an operator interface to the system, through a two line, 40 character alphanumeric display. Three reports may be displayed and various operating parameters may be adjusted by depressing a minimal number of keys on the CLD. Also, chiller Start/Stop functions may be performed at this keypad. See Clear Language Display (CLD) 1U6 Keypad Overview on page 42 for details. Interprocessor Communication Bridge (IPCB) 1U7 The IPCB module allows connection of a Remote Clear Language Display module to the UCM, for distances of up to 1500 feet. The Remote Clear Language Display communicates with the UCM, utilizing the same IPC protocol, and provides most of the same functions as the local CLD. The IPCB then serves to protect the UCM's IPC if wires to the Remote CLD become shorted or broken. See Section 2 and on page 75 for details. RLC-SVD03A-EN 7 Interprocessor Communications The respective modules communicate with each other via an InterProcessor Communication link (IPC). The IPC allows the modules to work in a coordinated manner with the CPM directing overall chiller operation while each module handles specific subfunctions. This IPC link is integral and necessary to the operation of the Unit Controls and should not be confused with the Optional ICS (Integrated Comfort System) communication. In the IPC communication protocol scheme, the CPM acts as the initiator and the arbitrator of all module communication. The CPM essentially requests all the possible “packets” of information from each module in turn, (including itself), in a predefined serial sequence. The other modules act as “responders” only and cannot initiate communication. Modules which are not currently responding to a specific request, can listen to the data and thus, indirectly, they communicate with each other. It is helpful to remember when troubleshooting that a module must be able to hear a request for its information from the CPM, or it will not talk. The link is non-isolated, which means that a good common ground between all the modules is necessary for trouble-free operation (provided by the module enclosures' mounting using star washers). Also, the link requires consistent polarity on all of the module interconnections. Connections between modules are made at the factory, using unshielded #18 gauge twisted pair cable terminated into a 4-position MTA type connector (orange color code). This connector is plugged onto the 4 pin IPC connection jack designated as J1, located in the upper left corner of the PC board edge on all of the modules. The 4 pins actually represent 2 pairs of communications terminals (J1-1 (+) internally connected to J1-3, and J1-2 (-) internally connected to J1-4) to allow for easy daisy chaining of the bus. IPC Diagnostics The modules, in order to work together to control the chiller, must constantly receive information from each other over the IPC. Failure of certain modules to communicate or degradation of the communication link, could potentially result in chiller misoperation. To prevent this situation, each module monitors how often it is receiving information from designated other modules. If a module fails to receive certain other module's transmitted data over a 15 second time period it will: 1. On its own, take specific action to safely shut-down (or to default) its controlled loads. 2. Report a diagnostic to the CPM (over the IPC link). The CPM (if it properly receives such) will then report and display the diagnostic on the Clear Language Display accordingly. The diagnostic will: • identify which module is reporting the communication problem and • identify which module was to have sent the missing information. The CPM itself will then send out further commands to the other modules to shutdown or take default actions as the particular case may warrant. All IPC diagnostics are displayed in the Clear Language Display's diagnostics section. For example, “Chiller Mod indicating Options Mod Comm Failure” indicates that the CPM Module has detected a loss of IPC communication 8 RLC-SVD03A-EN Interprocessor Communication from the Options Module. When some problem exists with the IPC link or a module fails, it is not uncommon for more than one of these IPC diagnostics to be displayed. Note that only those diagnostics that are indicated to be active currently exist. All other historic diagnostics should be disregarded for the purpose of the following troubleshooting discussion. See RTAA-IOM-4 for a complete listing of diagnostics. Troubleshooting Modules Using IPC Diagnostics WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. Communication problems can result from any of the following: 1. Improperly set IPC address dip switches 2. Opens or shorts in the twisted pair IPC wiring or connectors 3. Loss of power to a module 4. Internal module failure 5. Improper connections on terminal J2 6. High levels of EMI (Electro-Magnetic Interference) 7. Module specific function selected without the Options Module. These are discussed in more detail in the following paragraphs. 1. Improperly set IPC address dip switches: This could result in more than one module trying to talk at the same time, or cause the mis-addressed module to not talk at all. Only the MCSP and the EXV modules have IPC address dip switches, found in the upper left hand portion of the Module labeled as SW-1. The proper dip switch setups are shown in Table 2. 2. Opens or shorts in the twisted pair IPC wiring or connectors: One or more modules may be affected by an open or a short in the IPC wiring, depending on the location of the fault in the daisy chain. The diagram below shows the daisy chain order and is helpful in diagnosis of an open link. Extreme care should be used in making any dip switch changes or when replacing MCSP modules. “Swapping” of addresses on the MCSPs cannot be detected by the communication diagnostics discussed above and serious chiller misoperation will result. RLC-SVD03A-EN 9 Interprocessor Communication * #,$ 5 * #0 5 * -3#0 " 5 * -3#0 ! 5 * %86 -!34%2 5 * #32 5 /R * ,#) # 5 * )0#" 5 2%-/4% #,$ 5 AND 5 ARE MUTUALLY EXCLUSIVE OPTIONS 4HE 2EMOTE #,$ IS NOT AVAILABLE IF THE 5 OPTION IS INSTALLED Figure 1 10 IPC Link Order For 70-125 Ton RTAA RLC-SVD03A-EN Interprocessor Communication . Table 2 IPC Address Dip Switch (SW1) Settings for MCSP an EXV Modules MODULE DESIG. CONTROLLING MCSP “A” 1U4 COMPRESSOR A DIP SWITCH SETTING SW1-1 SW1-2 OFF OFF MCSP “B” 1U5 COMPRESSOR B OFF ON EXV 1U3 CKTS. 1 & 2 OFF OFF 3. Loss of power to a module: Generally a power loss to a particular module will only affect communications with that module. The module can usually be identified by analysis of the IPC diagnostics. (When the display is blank, check power at the CLD). Loss of power can most directly be diagnosed by measuring the AC voltage at the top of the fuse with respect to the neutral of the power connection (pins 4 or 5) on the terminal just below the fuse: 833(55,*+7 &251(52) 02'8/( IXVHGVLGH + )86( XQVZLWFKHGVLGH ³9$&´ 7R&KHFN )XVH - 1& 1(875$/ Figure 2 + + 1 1 9$&3RZHU &RQQHFWLRQ 1 Module Fuse and Power Connection, Except CLD 4. Internal module failure: Internal module failures usually result only in communication loss to the failed module, but could, in some cases, affect all the modules because the failed module may “lock up” the IPC bus and prevent all communications. The former can be identified by analyzing all of the active IPC diagnostics. The latter can be identified in a process of elimination, whereby each module, in turn, is taken out of the IPC link and a jumper installed in its place. See Figure 3. The CPM can then be reset and the new IPC diagnostics that result can be analyzed. RLC-SVD03A-EN 11 Interprocessor Communication - $03FF KHDGHUSLQV RUHTXLY :LUH MXPSHUV VROGHUHGRU ZUDSSHGLQWR SLQV Figure 3 IPC Jumper For Bypassing Modules (to be inserted into MTA connector in place of module) 5. Improper connections to terminal J2: Jack J2, present on all modules except CLD, should have no connections. This input is for manufacturing test purposes only and any connections, shorts, etc. will potentially cause the module to not respond, respond to the wrong address, or (in the case of the CPM) fail to initiate any communications and thus fail the entire IPC. 6. High levels of Electro-Magnetic Interference: The modules and the IPC have been qualified under severe EMI (both radiated and conducted) and the system was determined to be immune to all but extremely high noise levels. Always be sure to close and latch the control panel cabinet doors as the panel enclosure provides significant shielding and is integral in the overall noise immunity of the control system. 7. Module specific function selected without the Options Module: If any of the functions on the Options Module are selected but the Options Module is not present, the UCM will look for this module and generate an error. The Options Module functions include Chilled Water Reset, Ice Machine Control, External Chilled Water Setpoint, External Current Limit Setpoint, and Tracer/Summit Communications. Troubleshooting Procedure 1. Place the CPM in “Stop”. Record the active IPC diagnostics as shown in the Diagnostics Report of the CLD. The communication failure diagnostics and their meanings are shown in IPC Diagnostics of the RTAA-IOM-4 manual. 2. Determine which modules are not talking. These modules must be affected by one of the previously stated problems. If there is a group of modules not talking, suspect a wiring problem early in the daisy chain link. If only one module is not talking, suspect a loss of power or blown fuse. 12 RLC-SVD03A-EN Interprocessor Communication 3. Determine which modules are still talking. Wiring up to these is likely to be OK. 4. Try disconnecting the link or jumping out modules in the link at various places (use Figure 1). Reset the diagnostics and note which diagnostics reappear. Here are some examples of IPC diagnostics: Diagnostics present: Chiller Mod Indicating EXV Mod Communications Cprsr A Indicating EXV Mod Communications Cprsr B Indicating EXV Mod Communications The CPM and both MCSP modules are detecting a loss of communications with the EXV. Suspect power to the EXV or its fuse or a wiring problem downstream of the MCSP A and B modules. Diagnostics present: Chiller Mod Indicating Options Mod Communications Chiller Mod Indicating EXV Mod Communications Chiller Mod Indicating Cprsr A Communications Chiller Mod Indicating Cprsr B Communications The CPM is reporting that it cannot talk to any of the other modules. Suspect a shorted IPC bus or a module locking up the bus. The CPM could also be bad and not be sending recognizable tokens. Discriminating between these possibilities is done by disconnecting the link or jumping out modules in the link at various places. Refer to Item 4 in Troubleshooting Modules (Troubleshooting Modules Using IPC Diagnostics on page 9) for the procedure and the IPC Jumper for bypassing the Modules. Diagnostics present: Chiller Mod Indicating Cprsr B Communications EXV Mod Indicating Cprsr B Communications The CPM and EXV have both detected a communication loss with MCSP B. Suspect the address switch on MCSP B or a power/fuse problem. Diagnostics present: Chiller Mod Indicating Cprsr A Communications Chiller Mod Indicating Cprsr B Communications EXV Mod Indicating Cprsr A Communications EXV Mod Indicating Cprsr B Communications The CPM and EXV have both detected a communication loss with MCSP A and MCSP B. Suspect that the address switches on both modules are set to the same address. Wiring is probably OK since the EXV can talk to the CPM. Diagnostics present: Chiller Mod Indicating Cprsr B Communications Chiller Mod Indicating Cprsr A Communications Chiller Mod Indicating EXV Mod Communications RLC-SVD03A-EN 13 Interprocessor Communication The CPM has detected loss of communications with MCSP A, MCSP B, and EXV. Suspect an open early in the IPC link between the CPM and MCSP B. There are a large number of possible combinations of diagnostics. One must deduce what is causing the problem using all available information. If the CLD Comm link to the CPM is broken, the message is: No Communication, Data Not Valid 14 RLC-SVD03A-EN Temperature Sensor Checkout With the exception of the thermostats located in the motor windings of the screw compressors, all the temperature sensors used on the UCMs are negative temperature coefficient (NTC) thermistors. The thermistors employed all have a base resistance of 10 Kohms at 77F (25C) and display a decreasing resistance with an increasing temperature. The UCMs “read” the temperature by measuring the voltage developed across the thermistors in a voltage divider arrangement with a fixed internal resistance. The value of this “pull-up” resistor is different depending on the temperature range where the most accuracy is desired. The voltage source for this measurement is a closely regulated 5.0 VDC supply. An open or shorted sensor will cause the UCM to indicate the appropriate diagnostic. In most cases, an open or short will cause a CMR or MMR diagnostic that will result in a machine or circuit shutdown. Open or shorts on less critical Outdoor Air or Zone Temperature sensors will result in an Informational Warning Diagnostics and the use of default values for that parameter. Temperature Sensor Checkout Procedure WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. 1. Measure the temperature at the sensor using an accurate thermometer. Record the temperature reading observed. 2. With the sensor leads connected to the UCM and the UCM powered, measure the DC voltage across the sensor leads at the terminal or probe the back of the MTA plug. NOTE: Always use a digital volt-ohmmeter with 10 megohm or greater input impedance to avoid “loading down” the voltage divider. Failure to do so will result in erroneously high temperature calculations. 3. Locate the appropriate sensor table. Table 3: Evaporator Water and Refrigerant Temperature Sensors, Table 4: Saturated Condenser Refrigerant and Entering Oil Temperature Sensors. Then compare the temperature in the table corresponding to the voltage reading recorded in Step 2 with the actual temperature observed in Step 1. If the actual temperature measured falls within the allowable tolerance range, both the sensor and the UCM's temperature input circuits are operating properly. However, if the actual temperature is outside the allowable sensor tolerance range, proceed to Step 4. RLC-SVD03A-EN 15 Temperature Sensor Checkout 4. Again measure the temperature at the sensor with an accurate thermometer; record the temperature reading observed. 5. Remove the sensor leads from the terminal strip or unplug the respective MTA. Measure the resistance of the sensor directly or probe the MTA with a digital volt-ohmmeter. Record the resistance observed. 6. Next, with the sensor still disconnected from the module, check the resistance from each of the sensor leads to the control panel chassis. Both readings should be more than 1 Megohm. If not, the sensor or the wiring to the sensor is either shorted or leaking to chassis ground and must be repaired. 7. Select the appropriate sensor table and locate the resistance value recorded in Step 5. Verify that the temperature corresponding to this resistance value matches (i.e. within the tolerance range specified for that sensor) the temperature measured in Step 4. 8. If the sensor temperature is out of range, the problem is either with the sensor, wiring, or the MTA connector (if applicable). If an MTA connector is used and the thermistor reads open, first try cutting off the MTA, stripping a small amount of insulation from the sensor wire's end and repeating the measurement directly to the leads. Once the fault has been isolated in this manner, install a new sensor, connector or both. When replacing a sensor, it is easiest to cut the sensor wire near the MTA end and splice on a new sensor using wire nuts. 9. A decade box can be substituted for the sensor and any sensor table value used to relate resistance to temperature. By removing the MTA plug and applying the resistance to the proper pin terminals, the temperature, as sensed by the UCM, can be confirmed. Using the CLD menu displays, scroll to the display of the temperature of interest. NOTE: All displayed temperatures are slew rate limited and only accurate within a specified normal range. It is therefore important to be certain that the temperature readings are stable and that adequate time, up to 1 minute, is allowed after step changes in resistance inputs are made. 10. In all instances where module replacement is indicated, first perform the power supply/fuse check according to the information in the section “Module Power and Miscellaneous I/O” starting on page 41. 16 RLC-SVD03A-EN Temperature Sensor Checkout . Table 3 Sensor Conversion Data: Outdoor Air (6RT3), Entering and Leaving Evap Water Temp Matched Pairs (6RT7, 6RT8), and Saturated Evap and Comp Suction Refrigeration Temp (6RT9, 3B1RT5; 6RT10, 4B1RT6) Actual Temp. (F) Actual Resistance (Ohms) Thermistor Voltage (Volts DC) Actual Temp. (F) Actual Resistance (Ohms) Thermistor Voltage (Volts DC) Actual Temp. (F) Actual Resistance (Ohms) Thermistor Voltage (Volts DC) -20.0 -19.0 -18.0 -17.0 -16.0 -15.0 -14.0 -13.0 -12.0 -11.0 -10.0 -9.0 -8.0 -7.0 -6.0 -5.0 -4.0 -3.0 -2.0 -1.0 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 11.0 12.0 13.0 14.0 15.0 16.0 17.0 18.0 19.0 20.0 21.0 22.0 23.0 24.0 25.0 26.0 27.0 28.0 29.0 170040.3 164313.4 158796.5 153482.9 148365.0 143432.2 138679.6 134098.6 129684.9 125428.5 121326.1 117369.6 113554.9 109876.5 106328.1 102904.9 99602.3 96416.1 93341.6 90374.2 87510.3 84745.9 82077.1 79500.5 77012.3 74609.7 72288.8 70047.4 67881.9 65790.2 63768.7 61815.3 59927.8 58103.1 56339.6 54634.7 52986.4 51392.6 49851.6 48360.9 46919.2 45524.6 44175.6 42870.3 41607.6 40385.3 39202.7 38057.9 36950.0 35877.4 4.448 4.434 4.414 4.395 4.380 4.360 4.341 4.321 4.302 4.282 4.263 4.238 4.219 4.194 4.175 4.150 4.126 4.106 4.082 4.058 4.033 4.004 3.979 3.955 3.926 3.901 3.872 3.848 3.818 3.789 3.760 3.730 3.701 3.672 3.643 3.608 3.579 3.550 3.516 3.486 3.452 3.418 3.389 3.354 3.320 3.286 3.257 3.223 3.188 3.154 30.0 31.0 32.0 33.0 34.0 35.0 36.0 37.0 38.0 39.0 40.0 41.0 42.0 43.0 44.0 45.0 46.0 47.0 48.0 49.0 50.0 51.0 52.0 53.0 54.0 55.0 56.0 57.0 58.0 59.0 60.0 61.0 62.0 63.0 64.0 65.0 66.0 67.0 68.0 69.0 70.0 71.0 72.0 73.0 74.0 75.0 76.0 77.0 78.0 79.0 34838.9 33833.3 32861.4 31935.3 31038.7 30170.5 29329.5 28515.0 27725.9 26961.4 26220.8 25503.0 24807.5 24133.3 23479.7 22846.1 22231.9 21636.2 21058.7 20498.4 19955.0 19427.9 18916.5 18420.3 17938.8 17471.6 17018.0 16577.8 16150.5 15735.7 15332.9 14941.7 14561.9 14193.0 13834.6 13486.5 13148.3 12819.8 12500.5 12190.2 11888.7 11595.6 11310.7 11033.7 10764.4 10502.6 10248.0 10000.4 9759.6 9525.4 3.120 3.086 3.047 3.018 2.983 2.949 2.910 2.876 2.842 2.808 2.773 2.739 2.705 2.671 2.637 2.603 2.568 2.534 2.505 2.471 2.437 2.402 2.368 2.334 2.305 2.271 2.236 2.207 2.173 2.144 2.109 2.080 2.046 2.017 1.987 1.958 1.924 1.895 1.865 1.836 1.807 1.777 1.753 1.724 1.694 1.670 1.641 1.616 1.587 1.563 80.0 81.0 82.0 83.0 84.0 85.0 86.0 87.0 88.0 89.0 90.0 91.0 92.0 93.0 94.0 95.0 96.0 97.0 98.0 99.0 100.0 101.0 102.0 103.0 104.0 105.0 106.0 107.0 108.0 109.0 110.0 111.0 112.0 113.0 114.0 115.0 116.0 117.0 118.0 119.0 120.0 121.0 122.0 123.0 124.0 125.0 126.0 127.0 128.0 129.0 130.0 9297.5 9075.9 8860.2 8650.4 8446.2 8247.5 8054.1 7865.8 7682.5 7504.2 7330.5 7161.4 6996.7 6836.3 6680.1 6528.0 6379.8 6235.5 6094.8 5957.8 5824.3 5694.2 5567.4 5443.8 5323.3 5205.9 5091.5 4979.9 4871.1 4765.0 4661.5 4560.6 4462.2 4366.3 4272.6 4181.3 4092.2 4005.3 3920.5 3837.7 3756.9 3678.1 3601.1 3526.5 3453.6 3382.4 3313.0 3245.1 3178.9 3114.2 3051.0 1.533 1.509 1.484 1.460 1.436 1.411 1.387 1.362 1.343 1.318 1.294 1.274 1.250 1.230 1.211 1.187 1.167 1.147 1.128 1.108 1.089 1.069 1.050 1.030 1.016 0.996 0.977 0.962 0.942 0.928 0.913 0.894 0.879 0.864 0.850 0.835 0.820 0.806 0.791 0.776 0.762 0.747 0.732 0.723 0.708 0.698 0.684 0.674 0.659 0.649 0.635 1. Overall accuracy for any of the sensors is at least + 2 F over the range shown. Accuracy of matched sensors is + 1 F over specific ranges. 2. As you compare a thermistor resistance (or input voltage) reading with the “actual” temperature indicated by the thermometer, be sure to consider the precision and location of the thermometer when you decide whether or not the thermistor is out of specified accuracy. 3. The thermistor resistances given do not account for the self-heating effects that are present when connected to the UCM. A connected “operating” thermistor will read a slightly lower (less than 1%) resistance. RLC-SVD03A-EN 17 Temperature Sensor Checkout Table 4 Sensor Conversion Data: Saturated Condenser and Entering Oil Temperature Matched Pairs (6RT12, 3B1RT1; 6RT13, 4B1RT2) Actual Temp. (F) Actual Resistance (Ohms) Thermistor Voltage (Volts DC) Actual Temp. (F) Actual Resistance (Ohms) Thermistor Voltage (Volts DC) Actual Temp. (F) Actual Resistance (Ohms) Thermistor Voltage (Volts DC) 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 11.0 12.0 13.0 14.0 15.0 16.0 17.0 18.0 19.0 20.0 21.0 22.0 23.0 24.0 25.0 26.0 27.0 28.0 29.0 30.0 31.0 32.0 33.0 34.0 35.0 36.0 37.0 38.0 39.0 40.0 41.0 42.0 43.0 44.0 45.0 46.0 47.0 48.0 49.0 87510.3 84745.9 82072.1 79500.1 77012.3 74609.7 72288.8 70047.4 67881.9 65790.2 63768.7 61815.3 59927.8 58103.1 56339.6 54634.7 52986.4 51392.6 49851.6 48360.9 46919.2 45524.6 44175.6 42870.3 41607.6 40385.3 39202.7 38057.9 36950.0 35877.4 34838.9 33833.3 32861.4 31935.3 31038.7 30170.5 29329.5 28515.0 27725.9 26961.4 26220.8 25503.0 24807.5 24133.3 23479.7 22846.1 22231.9 21636.2 21058.7 20498.4 4.651 4.641 4.630 4.619 4.608 4.596 4.584 4.572 4.560 4.547 4.534 4.521 4.507 4.494 4.479 4.465 4.450 4.435 4.420 4.404 4.388 4.372 4.355 4.338 4.321 4.303 4.285 4.266 4.248 4.229 4.209 4.190 4.170 4.150 4.130 4.109 4.088 4.067 4.045 4.024 4.002 3.979 3.957 3.934 3.910 3.887 3.863 3.839 3.815 3.790 50.0 51.0 52.0 53.0 54.0 55.0 56.0 57.0 58.0 59.0 60.0 61.0 62.0 63.0 64.0 65.0 66.0 67.0 68.0 69.0 70.0 71.0 72.0 73.0 74.0 75.0 76.0 77.0 78.0 79.0 80.0 81.0 82.0 83.0 84.0 85.0 86.0 87.0 88.0 89.0 90.0 91.0 92.0 93.0 94.0 95.0 96.0 97.0 98.0 99.0 19955.0 19427.9 18916.5 18420.3 17938.8 17471.6 17018.0 16577.8 16150.5 15735.7 15332.9 14941.7 14561.9 14193.0 13834.6 13486.5 13148.3 12819.8 12500.5 12190.2 11888.7 11595.6 11310.7 11033.7 10764.4 10502.6 10248.0 10000.0 9759.6 9525.4 9297.5 9075.9 8860.2 8650.4 8446.2 8247.5 8054.1 7865.8 7682.5 7504.2 7330.5 7161.4 6996.7 6836.3 6680.1 6528.0 6379.8 6235.5 6094.8 5957.8 3.765 3.740 3.715 3.689 3.664 3.638 3.611 3.585 3.558 3.531 3.504 3.477 3.450 3.422 3.394 3.366 3.338 3.310 3.282 3.253 3.225 3.196 3.167 3.139 3.110 3.081 3.051 3.022 2.993 2.964 2.935 2.905 2.876 2.847 2.817 2.788 2.759 2.730 2.700 2.671 2.642 2.613 2.584 2.555 2.526 2.498 2.469 2.440 2.412 2.384 100.0 101.0 102.0 103.0 104.0 105.0 106.0 107.0 108.0 109.0 110.0 111.0 112.0 113.0 114.0 115.0 116.0 117.0 118.0 119.0 120.0 121.0 122.0 123.0 124.0 125.0 126.0 127.0 128.0 129.0 130.0 131.0 132.0 133.0 134.0 135.0 136.0 137.0 138.0 139.0 140.0 141.0 142.0 143.0 144.0 145.0 146.0 147.0 148.0 149.0 150.0 5824.3 5694.2 5567.4 5443.8 5323.3 5205.9 5091.5 4979.9 4871.1 4765.0 4661.5 4560.6 4462.2 4366.3 4272.6 4181.3 4092.2 4005.3 3920.5 3837.7 3756.9 3678.1 3601.1 3526.5 3453.6 3382.4 3313.0 3245.1 3178.9 3114.2 3051.0 2989.2 2928.9 2870.0 2812.4 2756.2 2701.2 2647.5 2595.0 2543.7 2493.6 2444.6 2396.7 2349.9 2304.1 2259.2 2216.0 2172.8 2131.6 2090.4 2051.2 2.356 2.327 2.300 2.272 2.244 2.217 2.189 2.162 2.135 2.108 2.082 2.055 2.029 2.003 1.977 1.951 1.926 1.901 1.876 1.851 1.826 1.802 1.777 1.754 1.730 1.707 1.684 1.661 1.638 1.615 1.593 1.571 1.549 1.528 1.506 1.485 1.464 1.444 1.423 1.403 1.383 1.364 1.344 1.325 1.306 1.287 1.269 1.250 1.232 1.215 1.197 1. Overall accuracy for the sensor is at least + 2 F over the range shown. 2. As you compare a thermistor resistance (or input voltage) reading with the “actual” temperature indicated by the thermometer, be sure to consider the location and precision of the thermometer when you decide whether or not the thermistor is out of specified accuracy. 3. The thermistor resistances given do not account for the self-heating effects that are present when connected to the UCM. A connected “operating” thermistor will read a slightly lower (less than 1%) resistance. 18 RLC-SVD03A-EN Compressor Operation This feature is called the Auto Lead/Lag and can be found in the Service Settings Group, under the “Balanced CPRSR Starts and Hours” menu. When this function is disabled, the UCM always starts compressor “A” first. When this function is enabled, the following occurs: The UCM equalizes operating starts and hours. This will cause the compressor with the least amount of starts to be started first. When a compressor starts, it is always started unloaded. When a compressor is stopped, it shuts down in an unloaded state, unless taken out by a manual reset diagnostic. When the first compressor is brought on line, it attempts to meet the load by staging on the step load solenoid and by pulsing the male slide valve load solenoid. If one compressor cannot meet the load demand, the second compressor is brought on line. It also attempts to meet the load demand by staging on its step load solenoid and by pulsing its male slide valve solenoid. When both compressors are running and both of their step load solenoids are energized, the male load and unload solenoids on both compressors are pulsed, thus modulating their respective slide valves to balance the load. The UCM attempts to distribute the load evenly between the two compressors. When the load drops off, the compressor with the most hours will always be the first to unload and turn off. The anti-recycle timer is approximately 5 minutes from start to start. The minimum time between compressor shutdown and restart is approximately 10 seconds, but only if the compressor has been running over 5 minutes or longer prior to shutting down on temperature. Otherwise, it is the remaining portion of the 5 minutes. Restart Inhibit Timer If compressor operation is interrupted by an extended (not momentary) loss of power or a manual reset, there will be a two minute delay between the power up or manual reset and the start of a compressor, assuming there is a call for cooling. The timer is factory set at 2 minutes but can be field adjusted from 30 seconds to two minutes in the Service Settings Group. RLC-SVD03A-EN 19 Compressor Start/Stop To start a compressor after either a “normal' shutdown, a Diagnostic reset, or power-on-reset, the following sequence will occur: 1. On a call for a compressor, the Restart Inhibit Timer will time out, if any time remains. 2. The EXV is positioned to the initial closed start position. At the same time, the unload solenoid is energized and the load solenoid is de-energized. Timing is determined by the time required to position the EXV 3. After the EXV is positioned: • the compressor is turned on • the compressor heater is de-energized • the saturated evaporator ref. temp. cutout ignore time is set, based on the saturated condenser temperature. Prior to start, the condenser temperature approximates the ambient temperature. • the fan control algorithm is executed To stop a compressor due to either the Stop button on the CLD or an External/Remote “STOP”, the sequence shall be as follows: 1. The unload solenoid is energized for 20 seconds and the load solenoid is de-energized. The compressor continues to run for the remaining 20 seconds. This is defined as the RUN:UNLOAD mode. 2. The compressor and the fans are turned off. The crankcase heater is energized. 3. The unload solenoid remains energized for 60 minutes after the compressor stops. The load solenoid is de-energized. 4. The EXV is closed. Closing begins at maximum speed when the compressor is turned off. (Max. speed is 25 steps per second, full stroke is 757 steps. 5. After 60 minutes, the unload solenoid de-energizes. The RUN:UNLOAD mode is also used to stop a compressor due to normal LWT control, Low Ambient Run Inhibit, or Freeze Avoidance. A compressor stop due to any diagnostic will skip step 1 above and go directly to step 2. 20 RLC-SVD03A-EN Variable Speed Inverter/Condenser Fan Control When Fan Control and Variable Speed Fan (VSF) are set to Enable in the Machine Configuration Menu, the UCM will control both the variable speed fan and the remaining constant speed fans per the VSF Control Algorithm. If VSF Control is disabled for a given circuit but Fan Control is enabled for the machine, the circuit will perform normal constant speed fan control. The VSF is enabled and operational, the control attempts to provide a 70 ± 5 psid between the Condenser Pressure and the Evaporator Pressure (as derived from the temperature sensor measurements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igure 4 /RZ'LIIHUHQWLDO3UHVVXUH/RFNRXW$UHD 'LDJQRVWLF2FFXUVLI'HOWD3LV36,'IRUPLQXWHV /RDG6WHS 0LQ/RDG 2II 7,0( Variable Speed Fan (VSF) and Fan Staging Control The VSF Inverter is commanded to a given speed by the UCM, using a PWM (Pulse Width Modulated) signal (10V, 15mA, 10 Hz Fundamental) with a duty cycle proportional to the desired voltage and frequency from the Inverter. The UCM also controls power to the Inverter through a contactor. The Inverter Contactor for the respective circuit is energized approximately 20 seconds prior to compressor start on that circuit. The VSF Control algorithm runs on a 5-second interval and is limited to a commanded rate of change of no greater than 40% of full speed per interval. The same algorithm that controls the RLC-SVD03A-EN 21 Variable Speed Inverter/ Condenser Fan Control speed will also cause constant speed fans to stage On and Off when the inverter is commanded to full speed and minimum speed respectively. The stage On (or Off) of a constant speed fan will occur if the inverter speed command is at max (or min.) for three consecutive intervals (15 seconds). Outdoor Air Temperature and Fan Control Outdoor air temperature is used to provide a reasonable startup state. Using this temperature, the algorithm automatically determines the number of constant speed fans to turn on immediately at compressor start. The outdoor air temperature sensor is also used to anticipate new states during normal running to minimize pressure upsets. This anticipation is based on the staging and unstaging of compressor steps at given leaving water temperatures. In this way, precise airflow can be maintained, allowing for stable differential pressures under part load and low ambient conditions. VSF Inverter Fault A fault signal will be sent to the UCM from the Inverter when it has gone through a self-shutdown or if the output frequency of the Inverter is being limited to less than 50% of the signal speed commanded by the UCM. Upon receipt of the fault signal, the UCM shall attempt to reset the fault by sending a 0 PWM command to the Inverter for a total of five seconds. The fault signal will again be checked and repeated if still in fault. If four faults are detected within one minute of each other, the power to the Inverter will be cycled off for 30 seconds (through contactor control) and then re-powered. If the fault still remains or occurs again within one minute, an IFW diagnostic occurs. The UCM will remove power from the Inverter and attempt to run the remaining constant-speed fans using normal constant-speed Fan Control Algorithm. See page 80 for step-by-step troubleshooting procedure. 22 RLC-SVD03A-EN Current Transformer Each compressor motor has all three of its line currents monitored by torroid (doughnut) current transformers. While the MCSP utilizes all three of the signals, it only displays the maximum phase at any given time. These currents are normalized with respect to the Rated Load Amps of the respective compressor and thus are expressed in terms of % (percent) RLA. The currents are “normalized” thru the proper selection of the Current Transformer, the setting of the Compressor Current Overload dip switch (SW2) on the MCSPs, and the redundant programming of the decimal equivalent of these settings in the Service Settings Group of the CLD. (The term “Compressor Current Overload setting” is actually a misnomer. Instead the setting should be thought of as an internal software gain that normalizes the currents to a % RLA for a given CT and compressor rating. The true nominal steady state overload setting is fixed at 132%). Refer to Tables 5 thru 9 for setup details. The current transformers provide the input for six basic functions of the MCSP: 1. Motor overload protection using a programmed “% RLA versus time to trip” characteristic. Refer to Table 6 for details. The steady state “must trip” value is 140% RLA and the “must hold” value is 125% RLA. The MCSP will trip out the compressor. The appropriate diagnostic descriptions are then displayed in the CLD diagnostic section. 2. Verifying contactor drop-out. If currents corresponding to less than 12 ±7% RLA are not detected on all three of the monitored compressor phases within approximately 5 seconds after an attempted contactor drop-out, the compressor will continue to be commanded Off, the Unload solenoid will be pulsed, the EXV will be opened to its fullest position, and the fans will continue to be controlled. This condition will exist until the diagnostic is manually reset. 3. Loss of Phase Current. If the detection of any or all of the three motor phase currents falls below 12 ±7% RLA for 2 ±1 seconds while the branch circuit should be “energized”, the MCSP will trip out the compressor. The Phase Loss diagnostic, or the Power Loss diagnostic, will be displayed. Failure of a contactor to pull in will cause the Phase Loss diagnostic. However when reduced voltage starting is employed, it may take an additional 3 seconds to detect a phase loss at startup, as phase loss protection is not active during the 3 second transition time. 4. Phase Rotation. Screw compressors cannot be allowed to run in reverse direction. To protect the compressors, the phase rotation is detected by the current transformers immediately at start up. If improper phasing is detected, within 1 second of startup, the MCSP will trip out the compressor. The Phase Rotation diagnostics will be displayed. This function is not sensitive to the current transformer's polarity. 5. Phase Unbalance. The MCSP will shut down the compressor if a phase current unbalance is detected by the current transformers while the compressor is running. A 15% unbalance, if protection is enabled, will cause the MCSP to trip out the compressor. The Phase Unbalance diagnostics RLC-SVD03A-EN 23 Current Transformer will be displayed. If this protection is disabled, a 30% phase unbalance will still be in effect with the diagnostic code Severe Phase Imbalance being displayed. 6. Current Limit. The MCSP will begin to unload its compressor as the %RLA exceeds 120%. Further, the CPM will cause the compressors to automatically unload when the Chiller Current Limit Setpoint is reached. The Current Limit Setpoint is set in the Service Setting Group. Individual compressor phase currents are averaged and added together to compare to the Chiller Current Limit which is in terms of % Total of all of the Compressor RLNs. NOTE: The current transformers are NOT polarity or directionally sensitive. CT and MCSP Compressor Current Input Checkout Procedure WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. 1. Check incoming 3-phase power for voltage within 10% of nominal per Chiller nameplate. 2. Interrogate the CPM for all of the presently active diagnostic codes or the historic diagnostic codes in the Diagnostics Menu. Narrow the problem down to a particular compressor or contactor as noted above. Write down all of the diagnostic codes stored in the diagnostic registers. If there is any question as to which compressor or current transformer is causing a problem, or simply to verify and “witness” the problem, an attempt should be made to restart the chiller after clearing diagnostics. The diagnostics can be cleared by entering the Diagnostics Menu and stepping to the CLEAR DIAGNOSTICS display. It is possible to “force” certain compressors to be the first or next compressor to stage on, using the “Compressor Test” feature in the Service Tests Menu. The Leaving Water Temperature must, however, be above the Chilled Water Setpoint by more than the “differential to start” setting, in order to stage on the first compressor. At startup, verify the appropriate contactor(s) pull-in. The “Compressors On” menu item in the Chiller Report Group will indicate which compressor started approximately five seconds after the contactor pulls in. Note the diagnostic(s) that results, then place the Chiller into the “Stop” mode by depressing the Stop button on the CLD. 24 RLC-SVD03A-EN Current Transformer WARNING Hazardous Voltage w/Capacitors! Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury. Note: For additional information regarding the safe discharge of capacitors, see PROD-SVB06A-EN or PROD-SVB06A-FR 3. For the next portion of the procedure, pull the unit's disconnect and interrupt all high voltage power to the control panel. Locate the torroid (doughnut) current transformers encircling the compressor power wiring and branching to the compressor contactors of the suspect compressor-in the control panel. Refer to the Component Location Drawing in the panel to identify the particular current transformer(s) of interest. Locate the part number/UL tag on the transformer leads and note the Trane part number which identifies the transformers. Note: all compressors of a given tonnage should have the same transformer extension number. Verify the proper current transformer using Table 5 in this section. Also check the setting of the dip switch (SW2) on each of the MCSP modules and verify these against Table 5 for each compressor. (Switch position SW2-1 is the Most Significant Bit). The decimal equivalent of this setting should also be verified in the Service Setting Group under the “CURRENT OVRLD SETTINGS” display. If the programmed value does not agree with the dip switch setting for each of the MCSP's, an informational diagnostic will result. The compressors will be allowed to run, but default settings (the most sensitive possible) will be used for the internal software compressor current gains. 4. Utilizing the Schematic Wiring Diagram, locate the termination of the transformer's wiring into the MTA plug at the appropriate MCSP module at pin header J5. Pull off the appropriate MTA connector from the pin header on the MCSP. Current Transformers can be damaged and high voltages can result due to running the compressors without a suitable burden load for the CTs. This load is provided by the MCSP input. Take care to properly reconnect the CT's MTA prior to attempted start of the compressors. 5. Using a digital volt-ohmmeter, measure the resistance of the transformer(s) by probing the appropriate pair(s) of receptacles within the MTA. The receptacle pairs of the MTA are most easily measured by using meter leads with pointed probes and contacting the exposed metal of the connector through either the top or the side of the MTA. (It may be necRLC-SVD03A-EN 25 Current Transformer essary to remove a cap over the top of the connector to gain access to the connector conductors.) 6. Refer to Table 7 which lists the normal resistance range for each extension of current transformer. Check the measured resistance against the value listed per transformer extension. If the resistance is within tolerance, the transformer and MTA can be considered good. Go on to step 8. 7. If the resistance reading above is out of tolerance, the problem is either with the transformer, its wiring, or the MTA connector. First double check the schematic to be sure you are working the proper lead pair. Then cut the leads to the particular transformer near the MTA connector and repeat the resistance measurement by stripping insulation from the wire's end. Once the fault has been isolated in this manner, reconnect leads or install a new transformer or connector. More than one current transformer is terminated to a single MTA. When replacing, take care to note the proper positions of the respective transformer wire terminations on the MTA for the re-termination. The current transformers are NOT polarity or directionally sensitive. The transformer lead wiring is #22 AWG, UL 1015 600V and the proper MTA connector (red color code) must be used to ensure a reliable connection. If the fault can be isolated to the current transformer or its wiring apart from the connector, the connector can be reused by cutting off the bad transformer and splicing in a new transformer using wire nuts. 8. If the transformer/connector resistance proves accurate, recheck the resistance with the connector held at different angles and with a light lead pull (less than 5 lb.) to test for an intermittent condition. 9. To perform the following test, you will need to use a digital voltmeter with a diode test function,. With the transformer MTA disconnected and the power off to the MCSP, perform a diode test across the corresponding pair of current transformer input pins on the MCSP (header J5). The meter should read from 1.0 to 1.5 volts for each current transformer input. Repeat using the opposite polarity. The same reading should result. Extreme errors suggest a defective MCSP module. If the diode voltage drops prove accurate, reconnect the transformers to the MCSP and repower the unit. 10. With the CT's reconnected to the MCSP, attempt a restart of the chiller. As the given compressor is started, and the inrush locked rotor transient has passed, (locked rotor transient should last less than one second) simultaneously monitor the actual compressor phase current(s) (using a clamp-on type ammeter) and the voltage developed at the respective current transformer's termination at the MCSP (using a digital volt-meter on a 0-20 VAC scale). Refer to Table 8 for the compressor phase current to output voltage relationship for each extension current transformer. Using Table 8, look up to current that corresponds to the output voltage read by the voltmeter and compare to ammeter reading. Assuming relatively accurate meters, the values should agree to within 5%. 11. If the measured current and the output voltage from the CT agree within the tolerance specified, the CT is good. If diagnostics, overload trips, or other problems potentially involving current sensing continue to occur 26 RLC-SVD03A-EN Current Transformer with all phase currents to the compressors verified to be within their normal range, then the problem is either with the CT selection, MCSP Compressor Overload Dip Switch Setting, or the MCSP's current input, analog to digital (A/D), or dip switch input circuitry. Since the first two items were verified in Step 2 using Table 5, that leaves only the MCSP circuitry as an issue. It is advisable to replace the MCSP module at this point. However if verification of the MCSP Current sensing operation is desired, go to step 12 below. 12. There are two ways that the MCSP's current sensing can be checked. Both methods use the CLD display of the %RLA from each MCSP (Compressor Report) for indication of the sensed current. The first is straightforward equation and assumes that the proper Compressor Overload dip switch setting and current transformer have been selected: Measured Compr. amps of max. phase Nameplate Compressor RLA %RLA = -------------------------------------------------------------------------------------------------------- To check the displayed % RLA as a function of the output voltage from the current transformers (as connected at the MCSP), Tables 8 and 9 are utilized. In Table 8 look up (or interpolate) the “% of CT rating” corresponding to the maximum of the three CT Input Voltages (VAC rms) as read at the MCSP. (The table is necessary because the voltage developed at the MCSP is not linear with the CT's secondary current). Next, check the Compressor Current Overload setting of switch SW2 on the MCSP and find the corresponding “SOFTWARE GAIN” in Table 9. The % RLA displayed by the CPM should be: %RLA = % CT Rating X SOFTWARE GAIN The preceding equations should only be applied during steady state current draws (after transition). Inrush transient currents and associated CT output voltages can be expected to be from 3 to 6 times the steady state values, and the displayed value only reads up to 255% RLA. The accuracy of the displayed value should be within ± 5% of that predicted using the Input voltage. However, the end to end accuracy of the displayed value compared to the actual %RLA max. phase current is ± 3.3% over the range of 50 to 150% of CT rating. 13. If no phase currents are measured with the amprobe on any or all of the legs to a given compressor immediately following the attempted staging of that compressor by the MCSP, the problem lies either with the contactor, motor circuit or the MCSP relay outputs. Refer to MCSP Checkout Procedure in Compressor Module (MCSP) (1U4 AND 1U5) on page 72. RLC-SVD03A-EN 27 Current Transformer Table 5 Compressor Overload DIP Switch Settings Current Transformer Extension* Overload Setting Dip Sw/Decimal 12345** 1 -02 01011/11 1 -01 11111/31 -10 01100/12 Primary Turns Through Current Transformer Compressor Tons Volts/Hz 35 200/60 115 230/60 100 346/50 58 1 40 50 60 RLA 380/60 61 1 -10 10000/16 400/50 50 1 -10 00000/0 460/60 50 1 -10 00000/0 575/60 40 1 -01 01111/15 200/60 142 1 -02 11011/27 230/60 124 1 -02 10001/17 346/50 72 1 -01 00111/7 380/60 75 1 -01 01010/10 400/50 62 1 -10 10001/17 460/60 62 1 -10 10001/17 575/60 50 1 -01 11111/31 200/60 192 1 -03 11100/28 230/60 167 1 -03 10010/18 346/50 96 1 -01 11100/28 380/60 101 1 -02 00001/1 400/50 84 1 -01 10011/19 460/60 84 1 -01 10011/19 575/60 67 1 -02 10111/23 200/60 233 1 -04 10011/19 230/60 203 1 -04 01000/8 346/50 117 1 -02 01101/13 380/60 123 1 -02 10001/17 400/50 101 1 -02 00001/1 460/60 101 1 -02 00001/1 575/60 81 1 -03 10000/16 *The current transformer base part number is X13580253. The numbers in this column are suffixes of the base part number. **On the DIP switch, 1=ON, O=OFF. The decimal value should be set in the compressor overload setting menu of the UCM. If the DIP switch value does not match the decimal value entered into the UCM, the related compressor(s) will continue to run, but a diagnostic will be initiated, both settings will be ignored, and the UCM will use the lowest possible trip setting value. 28 RLC-SVD03A-EN Current Transformer Table 6 Trip Times Vs. % Current MOTOR CURRENT (% RATED RLA) MINIMUM TRIP TIME (SEC) NOMINAL MAXIMUM 127.7 or below 132.0 132.1 140.0 (must trip pt.) 150.0 160.0 170.0 180.0 190.0 200.0 210.0 220.0 230.0 240.0 250.0 260.0 270.0 280.0 290.0 300.0 300.1 310.2 or above No trip 27.2 27.2 22.8 18.8 16.0 14.0 12.4 11.2 10.4 9.6 8.8 8.0 7.6 7.2 6.8 6.4 6.0 5.6 4.0 4.0 4.0 No Trip No Trip 30.08 25.28 20.48 17.28 15.28 13.28 12.08 10.88 10.08 9.28 8.48 8.08 7.68 6.88 6.88 6.48 6.08 5.68 4.08 4.08 No Trip No Trip No Trip 28.09 22.89 19.29 16.89 14.89 13.29 12.09 10.89 10.09 9.69 8.89 8.49 7.69 7.29 6.89 6.89 6.49 6.49 4.49 Table 7 Current Transformers Ratings and Resistance RATING USABLE RANGE RESISTANCE OHMS + 10% 01 100A 66.67 -100A 23.5 02 150A 35.0 03 200A 100 - 150A 134 - 200A 04 275A 184 -275A 67.0 05 400A 267 - 400A 68.0 09 50A 33.37 - 50A 11.5 10 75A 50 - 75A 17.0 EXT* 46.0 *The current transformer base part number is X13580253. The numbers in this column are suffixes of the base part number. RLC-SVD03A-EN 29 Current Transformer Table 8 Compressor Phase Current vs. AC Input Voltage at MCSP ACTUAL COMPRESSOR PHASE AMPS THRU CT EXT -01 EXT -02 EXT -03 EXT -04 EXT -05 EXT -09 EXT -10 TERMINAL VOLTAGE (V RMS) % OF CT RATING 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140 145 150 160 170 180 190 200 210 220 230 240 250 260 270 280 290 300 0 8 15 23 30 38 45 53 60 68 75 83 90 98 105 113 120 128 135 143 150 158 165 173 180 188 195 203 210 218 225 240 255 270 285 300 315 330 345 360 375 390 405 420 435 450 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 230 240 250 260 270 280 290 300 320 340 360 380 400 420 440 460 480 500 520 540 560 580 600 0 14 28 41 55 69 83 96 110 124 138 151 165 179 193 206 220 234 248 261 275 289 303 316 330 344 358 371 385 399 413 440 468 495 523 550 578 605 632 660 687 715 742 770 797 825 0 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540 560 580 600 640 680 720 760 800 840 880 920 960 1000 1040 1080 1120 1160 1200 0 2.5 5 7.5 10 12.5 15 17.5 20 22.5 25 27.5 30 32.5 35 37.5 40 42.5 45 47.5 50 52.5 55 57.5 60 62.5 65 67.5 70 72.5 75 80 85 90 95 100 105 110 115 120 125 130 135 140 145 150 0 3.75 7.5 11.25 15 18.75 22.5 26.25 30 33.75 37.5 41.25 45 48.75 52.5 56.25 60 63.75 67.5 71.25 75 78.75 82.5 86.25 90 93.75 97.75 101.25 105 108.75 112.5 120 127.5 135 142.5 150 157.5 165 172.5 180 187.5 195 202.5 210 217.5 225 0.00 1.19 1.37 1.53 1.67 1.81 1.95 2.09 2.23 2.36 2.50 2.63 2.77 2.90 3.03 3.17 3.30 3.43 3.57 3.70 3.83 3.96 4.10 4.23 4.36 4.49 4.62 4.75 4.88 5.02 5.15 5.41 5.67 5.94 6.20 6.46 6.72 6.99 7.25 7.51 7.77 8.03 8.29 8.56 8.82 9.08 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140 145 150 160 170 180 190 200 210 220 230 240 250 260 270 280 290 300 30 RLC-SVD03A-EN Current Transformer Table 9 RLC-SVD03A-EN Overload Dip Switch Setting vs. Internal Software Gain CPRSR RATED RLA AS A % OF CT RATING OVERLOAD DP SWITCH SETTING DECIMAL SETTING SOFTWARE GAIN 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 00000 00001 00010 00011 00100 00110 00111 01000 01001 01010 01011 01100 01101 01111 01111 10000 10001 10010 10011 10100 10101 10110 10110 10111 11000 11001 11001 11010 11011 11100 11100 11101 11110 11110 11111 00 01 02 03 04 06 07 08 09 10 11 12 13 15 15 16 17 18 19 20 21 22 22 23 24 25 25 26 27 28 28 29 30 30 31 1.500000 1.483870 1.467743 1.451613 1.435483 1.403226 1.387097 1.370969 1.354839 1.338709 1.322580 1.306452 1.290323 1.258065 1.258065 1.241936 1.225806 1.209678 1.193549 1.177419 1.161291 1.145162 1.145162 1.129032 1.112903 1.096775 1.096775 1.080645 1.064516 1.048387 1.048387 1.032258 1.016128 1.016128 1.000000 31 Under-Over Voltage Transformer The hardware required for the Under/Over voltage sensing function of the UCM is standard on the 70-125 Ton RTAA chiller. This feature must be Enabled in the Service Settings Menu for it to be active. A custom designed transformer whose primary is connected across the Line Voltage phases A to B, provides a stepped down and isolated AC voltage to the CPM at input J4. This secondary voltage is directly proportional to the line voltage applied to the primary. The Chiller Report on the CLD can directly display the % Line Voltage and, when so enabled, can cause automatically reset MAR diagnostics for High and Low Line condition. The % Line Voltage is internally calculated by dividing the selected nominal voltage rating (only certain discrete values are selectable in the Service Settings Group) by the actual line voltage as read and processed by the CPM. With the Under-Over Voltage Protection Function enabled, an Over Voltage diagnostic will occur if the calculated % Line Voltage equals or exceeds 114%, or an Under Voltage diagnostic will occur if it equals or falls below 87% for 15 continuous seconds. Reset differential is set at 3%. Under-Over Voltage Transformer Checkout WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. 1. Locate the Under-Over Voltage Transformer [1T2] in the panel by referring to the Component Location Drawing. Carefully measure the primary voltage across the Transformer (Line Voltage Phase A to B) and note the value in Vac rms. 2. Next disconnect the transformers secondary from J4 on the CPM. Using voltmeter probes, measure and note the unloaded secondary voltage (Vac rms). (low voltage class 2 less than 32 Vac). 3. The ratio of the primary or line voltage to the open circuity secondary voltage should be 20 to 1. If the unloaded turns ratio is not within ±2% of this value, replace the transformer. 4. Reconnect the secondary back to J4 and remeasure the loaded (connected) secondary voltage. The new loaded ratio should be approximately 20.2 to 1. If not within ±2% of this ratio the transformer's secondary should be disconnected from the CPM and a 1 Kohm resistor connected across the secondary. Measuring the voltage across the 1 Kohm resistor should give us a voltage ratio of 20.17. Ratios more than ±2% in error suggest a bad transformer. If the 1 Kohm loaded ratio is within tolerance, but the CPM connected ratio is out of tolerance suspect a bad CPM. Before 32 RLC-SVD03A-EN Under-Over Voltage Transformer replacing the CPM, double check the Under-Over Voltage Function's Nominal Line Voltage Setup in the Service Settings Group. 5. If the Under-Over Voltage Protection function continues to misoperate, and all of the above measured ratios are within tolerance, and all CLD Under Over Voltage setups have been verified, replace the CPM. It is a good idea, before replacing the CPM, however, to copy down all of setup data. This data will be very helpful in making the necessary setup on the replacement CPM. RLC-SVD03A-EN 33 Compressor Capacity The 35 to 60 ton helical rotary screw compressors are loaded and unloaded by means of an internal slide valve and a female unloader valve. In simple terms, these valves can regulate the amount of “bite” of the compressor rotors as they turn at relatively constant speeds. The slide valve is moved by a hydraulic cylinder and piston internal to the compressor (the hydraulic fluid is oil from the refrigerant system). The movement of the cylinder is controlled by the load and unload solenoid valves, which either add oil at compressor discharge pressures, or withdraw oil to suction pressures. The female unloader valve is moved to either the On or Off position by using internal suction and discharge gas pressure. The movement of this valve is controlled by the female unloader valve solenoid. These solenoid valves are electrically controlled by the MCSP module to handle compressor startup and shutdown, maintain chilled water temperature setpoints and limit current, condenser pressures, and evaporator temperatures etc. Although the solenoids are an “on - off” device, effective modulation and high resolution of the slide valve (under steady state conditions) is possible by pulsing on and off the solenoid valves and varying the displaced volume of the cylinder/piston. When a given compressor is operating, the MCSP will energize (apply 115 VAC) either the load or the unload solenoid, if necessary, for a period of between 40 and 400 milliseconds, once every 10 seconds to control water temperature or limit conditions. The female unloader valve solenoid receives a constant signal from the UCM as the first step in compressor loading and the last step in compressor unloading. Just prior to and just after a compressor start, and just before a compressor stop, the MCSP will continuously energize the unload solenoid for 20 to 30 seconds to assure unloaded starts. After a compressor stop, the unload solenoid valve will remain energized for approximately one hour to prevent slide valve movement due to changing cylinder/compressor pressures. The first procedure below will allow the checkout of the MCSP load and unload outputs. The next procedure will allow the checkout of the Load and Unload Solenoid valves located on the compressor as well as the operation of the Slide Valve modulating unloader. Lastly, the female unloader valve and solenoid will be discussed. RLC-SVD03A-EN 34 Compressor Capacity Checkout Procedure for MCSP Load/Unload Outputs WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. The MCSP controls the Load and Unload Solenoid valves on the respective compressor with 115 V triacs (solid state relays). Unlike mechanical relays however, a triac has a rather high leakage current when off, comparatively speaking. While this leakage is not nearly enough to actuate a solenoid valve, it may, under no load conditions (as would be experienced when a solenoid coil failed open), look like it was stuck “on” when using a voltmeter to test it. Thus it is important to verify that the solenoid coil is continuous and providing a normal load or to connect a known good load, such as a low wattage 115 Volt lamp, to the terminals when testing the outputs. Refer to the Chiller Control Wiring diagrams and Component Location Drawings for the following procedure. With the particular compressor running, the triacs may be checked (under load as explained above) by measuring the voltage from terminals E7 or E8 to 115 neutral. The triacs operate in the high side and switch 115 Vac power from J7-1 to either E7 (load solenoid) or E8 (unload solenoid) to move the slide valve in the appropriate direction. Except during compressor starts and stops, in normal operation, the solenoid valves can only be energized for a period of between 40 and 400 milliseconds once every 10 seconds. Often, if the chilled water setpoint is being met under steady state conditions, they may not energize at all. To assure loading and unloading is occurring it may be necessary to make slight adjustments to the chilled water setpoints to force action. As the pulsed on-time is potentially short it may be difficult to see, especially if using a meter movement type voltmeter. (Use of a low wattage 115 Vac test lamp may be of some help for a visual indication of output triac operation.) When a triac is off, about 0 Vac should be measured on its terminal with the solenoid load connected. When it is on, the voltage should be close to 115 Vac (the drop across the triac is about 1-2 volts). The best time to check the unload solenoid is immediately after a power-up reset of the MCSP. For the first 30 seconds after applying power the unload solenoid should be on continuously. The next best time to check it is after the compressor starts. For the first 30 seconds after a start the unload solenoid should be on continuously. Checking the load solenoid is more difficult. 30 seconds after a start, the compressor will usually start loading, until water temperatures are satisfied. Remember however, that under certain limit conditions, the MCSP may RLC-SVD03A-EN 35 Compressor Capacity prevent a compressor from loading even if the chilled water setpoint is not satisfied. Refer to the RTAA-IOM-4 for discussion on condenser, evaporator, and current limiting functions and setpoints. Refer to the Mode display under the Chiller Report on the CLD for an indication of the current running mode. Checkout Procedure for the Slide Valve and Load/ Unload Solenoids Make sure unit is off and there is no power in the control panel before beginning this procedure. Setup 1. Identify the MCSP Module associated with the compressor to be tested (1U4 or 1U5). Disconnect the stake-on terminals for the Load and Unload Solenoid Valves at the MCSP UCM (E7 and E8 respectively) but take care to identify the wires so as to prevent crosswiring when reconnecting. WARNING Hazardous Voltage w/Capacitors! Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury. Note: For additional information regarding the safe discharge of capacitors, see PROD-SVB06A-EN or PROD-SVB06A-FR 2. Install a toggle switch between Control Power HOT (1TB3-8 or 9) and the Load and Unload Solenoid Valve leads (previously connected to E7 and E8). Initially make sure that the Load toggle switch is open and the Unload toggle switch is closed. 3. Install a pressure gauge with a refrigerant hose (hose should be long enough to read the gauge from the control panel) to the slide valve piston/cylinder cavity Schrader valve located near the load/unload solenoids. 4. Reapply power to the unit and place the chiller in the “Stop” mode. Using the CLD, select and enable the “Compressor Test” (in the Service Tests Menu) for the compressor that is to be run. Additionally, to prevent the opposite refrigeration circuit from running, if desired, the circuit can be locked out through the CIRCUIT LOCKOUT display in the Service Tests Menu for the appropriate circuit. Next place the Chiller into the “Auto“ mode and provide all necessary interlocks and a load (or adjust chilled water setpoint) to start the chiller. The selected compressor will be the first to stage on (after the restart inhibit timer has expired). 36 RLC-SVD03A-EN Compressor Capacity NOTE: Enabling the “Compressor Test” only affects which compressor will be cycled on next and is not an override mode. The chiller will continue to operate normally (not withstanding circuit lockout) and will stage compressors on and off, as well as attempt to modulate running compressors to maintain chilled water setpoint. Be aware that during manual control of the load/unload solenoids, as explained in item 6, below, other compressors may stage and/or attempt to modulate and thus will affect the leaving chilled water temperature. However, all diagnostics are still active. No specific action, other than reconnecting the solenoid valves to their respective outputs on the MCSP, is required to return the Chiller to normal operation. 5. Allow the compressor to start and monitor compressor currents either in the Compressor Report display (maximum phase % RLA) or with a clamp-on type ammeter. Load 1. Once the compressor has started, allow the Unload Solenoid Valve to remain energized for approximately 30 seconds, then open the Unload toggle switch to de-energize the valve. Verify that at least one condenser fan is on before continuing with the checkout, as low differential refrigerant pressures will preclude proper Slide Valve operation. Record the cylinder cavity pressure and the compressor currents. 2. Manually close and open the Load toggle switch, to energize the Load Solenoid, in 4 or 5 short “pulses”. Each load pulse should be approximately one second in duration, with approximately 10 seconds between pulses. NOTE: Loading the compressor faster than this rate could cause control instability and possible diagnostics. Leave the toggle switch open, i.e., valve de-energized. 3. If the %RLA or the current and pressure increases,' then the Load Solenoid and Slide Valve are operating properly. 4. If the %RLA or current does not increase, read the pressure at the cylinder cavity; Pressure increases, to approximately condenser pressure (condenser pressure read via the CLD) without an increase in % RLA (unless already fully loaded), indicate the Slide Valve is bound. 5. If cylinder cavity pressure does not increase, check the coil of the Load Solenoid. 6. If the coil checks out, then one of two problems exist. Either the Load Solenoid Valve is malfunctioning or the Unload Valve is stuck open. NOTE: Refer to the flow chart shown in Figure 5. RLC-SVD03A-EN 37 Compressor Capacity 1. Install toggle switches across load and unload solenoid 2. 3. Install Pressure Gage on slide valve piston/cylinder cavity Schrader valve. Start Unit. Load: 4. Manually load compressor in short increments. 5. Does RLA increase? Yes Check UCM No Good Bad Repeat procedure for unload Replace 6. Does Cavity Press increase to a level close to discharge pressure? Yes Slide valve mechanism bound No 7. Does Magnetic Field on Solenoid Coil exist? Yes Solenoid valve mechanism bound or unloader valve stuck open No 8. Is wiring to valve OK? Yes Check for open solenoid coil No 9. Repair and reverify. Figure 5 Manual Slide Valve Diagnostic Flow Chart - Load Unload NOTE: The following assumes that the compressor's slide valve is already at some loaded position and %RLA is higher than the minimum noted in step 1. 1. Manually close the Unload toggle switch to continuously energize the Unload Solenoid Valve. 2. If the %RLA decreases, then the Unload Valve and Slide Valve are operating properly. 3. If the %RLA does not decrease, observe the cylinder cavity pressure reading. 4. If cylinder cavity pressure reading decreases to approximately the suction 38 RLC-SVD03A-EN Compressor Capacity pressure, then the Slide Valve is bound. 5. If cylinder cavity pressure does not decrease or is at suction pressure before the Unload toggle switch was closed, the problem lies with either the solenoid coil or valve. 6. Check coil 7. If coil checks out, change the valve. NOTE: Refer to the Flow Chart in Figure 6. Unload: 10. Manually unload compressor in short increments. Yes 11. Does RLA Decrease? Check UCM No Good Stop Bad Replace 12. Does Cavity Press decrease to a level close to suct pressure? Yes Slide valve mechanism bound No 13. Does Magnetic Field on Solenoid Coil exist? Yes Solenoid valve mechanism bound No 14. Is wiring to valve OK? Yes Check for open solenoid coil No 15. Repair and reverify. Figure 6 Manual Slide Valve Diagnostic Flow Chart Checkout Procedure for MCSP Step Load Output The MCSP controls the step load solenoid valve on the respective compressor with a 115 VAC dry contact output relay. This differs from the Load/Unload solenoid output, which is from a triac (solid state relay). Refer to the Chiller Control Wiring diagrams and the Component Layout Drawings for the following procedure. RLC-SVD03A-EN 39 Compressor Capacity WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. With a particular compressor running, the relay may be checked (under load, as explained above) by measuring the voltage from terminal J7-9 to the 115 VAC neutral. The relay operates in the high side and switches power from J7-8 to J7-9, to move the step load valve to the loaded position. When the CPM decides to load the compressor, the step load solenoid is energized continuously. To assure that loading and unloading is occurring, it may be necessary to make slight adjustments to the chilled water setpoints to force action. Checkout Procedure for Step Load Solenoid Valve and Piston Prior to a compressor start, connect a pressure gauge to the Schrader port near the step load solenoid valve. This port is connected to the back side of the step load piston and, therefore, will allow direct measurement of the pressure that actuates the step load valve. Observe the pressure gauge during a compressor start, either from a manual compressor test or a normal call for cooling. Initially, the pressure should drop to the suction pressure and, when the MCSP calls for compressor loading, the solenoid will actuate and supply discharge pressure to the piston. If, after verifying that 115 VAC has been applied to the step load solenoid, the pressure does not increase to discharge pressure, the step load solenoid coil and/or valve must be replaced. Also, when the solenoid valve is energized and the piston pressure is near discharge pressure, the percent RLA of the compressor, as seen in the Compressor Report, should increase. If the percent RLA does not increase, the step load valve is stuck and should be repaired. 40 RLC-SVD03A-EN Module Power and Miscellaneous I/O This section will detail the normal voltage levels present on each of the modules inputs and outputs under various conditions or states. Typical operation of the I/O will be discussed in terms of chiller operation. This should help the serviceman determine when and how they should function. Certain inputs have been presented in greater detail in earlier sections and these are referenced where applicable. Power Supply All of the modules are powered from 115 VAC 50/60hz Control Power except the CLD and the IPCB, which are powered by 24 VAC. This power is provided by either a control power transformer or is customer supplied. With the exception of the CLD, LCI-C and the IPCB modules, the other modules have incoming power connected to the upper-most terminal on the right hand side of the module, just below the fuse. The terminal is arranged with two hot pins (1 and 2), a keying pin (3), and two neutral pins (4 and 5), for ease of “daisy chaining” power from one module to another. Incoming power can be verified by measuring the voltage between the fuse bottom (hot side) and the connector's neutral (pins 4 or 5). The voltage should read between 97.8 to 132.2 volts AC rms. Refer to Figure 7. (The ±15% voltage criteria is most important for the EXV module's operation, as the Electronic Expansion Valve's available torque is directly related to this value). The fuses can be checked by looking for the supply voltage at the top of the fuse (fused side) with respect to the connector neutral. If some modules have power and some do not, the “daisy chain” wiring or power connections should be suspected. Refer to the Unit Wiring diagrams for the specifics on the power wiring. Generally a power loss to a particular module will first be noticed as a communications loss with that module. The module can be identified by analysis of the IPC diagnostics as displayed by the CPM. Refer to Section 2 Interprocessor Communication for more information about Communication (IPC) diagnostics. If the CLD's display is blank, 24 VAC power should be checked at the CLD. RLC-SVD03A-EN 41 Module Power and Miscellaneous I/O 833(55,*+7 &251(52) 02'8/( IXVHGVLGH )86( XQVZLWFKHGVLGH - 1& 1(875$/ Figure 7 + + 1 1 9$&3RZHU &RQQHFWLRQ AC Power Connection To Modules Clear Language Display (CLD) 1U6 Keypad Overview Local operator interface with the system is accomplished using the 16 keys on the front of the Clear Language Display panel. The readout screen is a two line, 40 character liquid crystal display with a backlight. The backlight allows the operator to read the display in low-light conditions. The depression of any key will activate the backlight. The backlight will stay activated for 10 minutes after the last key is pressed. At 10 F or below the backlight will stay activated continuously. The keys are grouped on the keyboard by the following functions (refer to Figure 8): - Select Report Group - Select Settings Group - Selection Keys - Stop & Auto Keys 42 RLC-SVD03A-EN Module Power and Miscellaneous I/O Figure 8 Operator Interface Adaptive Control Select Report Group This group of four keys allows the operator to select and view the following reports: - Custom Report - Chiller Report - Refrigerant Report - Compressor Report The Custom Report is the only report of the four that is defined by the operator. Any display under the other three reports can be added to the Custom Report by pressing the plus key while the desired read-out is on the display. A maximum of 20 entries can be contained under the Custom Report. Items can be deleted from the Custom Report by pressing the minus key when the desired read-out is on the display. The operator must be in the Custom Report menu to delete the desired item. The Chiller Report, Refrigerant Report and Compressor Report are informational reports that give current status. Each report and its contents are discussed in detail on the following pages. RLC-SVD03A-EN 43 Module Power and Miscellaneous I/O When any of the four report keys are pressed, the first readout on the display will be the header. The header identifies the title of the report and summarizes the items in the report. The Next key and Previous key allow the operator to scroll up and down through the display items listed under the report menus. When the last item of a report is displayed and the Next key is pressed, the display will wrap around to the header of the report. When the first item of a report is displayed and the Previous key is pressed, the display will wrap around to the last item. Select Settings Group The first three keys on the second row - Operator Settings, Service Settings and Service Tests - allow the operator to adjust various setpoints and perform various tests. Certain items in these groups are password protected. Refer to the Password section for additional information. When a setpoint key is pressed, a header will be displayed. The setpoint headers identify the available items and setpoint functions. The Next and Previous keys function in the same manner as that described in Selected Report Group, above. Setpoint values are incremented by pressing the Plus key and decremented by pressing the Minus key. Once a setpoint is changed, the Enter key must be pressed to save the new setpoint. If the Cancel key is pressed, the setpoint value on the display will be ignored and the original setpoint will remain. Passwords Passwords are needed to enter into the Service Setup Menu and the Machine Configuration Menu. Both of these menus are accessed through the Service Settings key. If access into these menus is necessary, follow the list of steps below: 1. Press Service Settings 2. Press Next until the readout in the display is: Password Required For Further Access “Please enter Password” 3. To enter into the Service Setup Menu, press: Enter 4. To enter into the Machine Configuration Menu, press: Enter Refer to RTAA or RTWA IOM for the list of items found in the Service Setup Menu and Machine Configuration Menu. Select Report Group and Select Settings Group Flowcharts Refer to RTAA or RTWA IOM for the display readouts found under each menu. The first block of the flowchart is the header which is shown on the display after the menu key is pressed. For example: Press Chiller Report and the readout on the display will be CHILLER RPRT:STATUS, WTR TEMPS & SETPTS “PRESS (NEXT) (PREVIOUS) TO CONTINUE” 44 RLC-SVD03A-EN Module Power and Miscellaneous I/O Press Next to move down through the Chiller Report. As shown in the figures, the flowchart explains the conditions that the UCM looks at to determine which readout is to be displayed next. For example: Press Chiller Report to display the header Press Next to display MODE: [OPERATING MODE] REQUESTED SETPOINT SOURCE: [SETPT SOURCE] Press Next to display COMPRESSOR ON CIRCUITS LOCKED OUT Press Next to display ACTIVE ICE TERMINATION SETPOINT or ACTIVE CHILLED WATER SETPOINT The UCM will determine which screen will be displayed after looking at the current Operating Mode. If the Operating Mode is “Ice Making” or “Ice Making Complete”, ACTIVE ICE TERMINATION SETPOINT will be displayed. Otherwise, ACTIVE CHILLED WATER SETPOINT will be shown. The flowcharts also list the setpoint ranges, default options and a brief description of the item, when necessary. This information is shown in the lefthand column of the page, adjacent to the appropriate display. Auto/Stop Keys The chiller will go through a “STOPPING” mode when the Stop key is pressed, if a compressor is running. This key has a red background color surrounding it, to distinguish it from the others. If the chiller is in the Stop mode, pressing the Auto key will cause the UCM to go into the Auto/Local or Auto/Remote mode, depending on the Setpoint Source setting. The Auto key has a green back-ground color. When either the Auto or Stop key is pressed, Chiller Operating Mode (Chiller Report Menu) will be shown on the display. Power Up When power is first applied to the control panel, the Clear Language Display goes through a self-test. For approximately five seconds, the readout on the display will be SELF TEST IN PROGRESS During the self-test, the backlight will not be energized. When the tests are successfully complete, the readout on the display will be 6200 xxxx-xx [TYPE] configuration Updating Unit Data, Please Wait RLC-SVD03A-EN 45 Module Power and Miscellaneous I/O When updating is successfully completed, the system will default to the first display after the Chiller Report header: MODE: OPERATING MODE] REQUESTED SETPOINT SOURCE: [SETPT SOURCE] and the backlight will be activated. 7% $%* 9$& 7% * 67 9'& 7; 5; TB1-1,2 IPC Communications 19.2K Baud serial data 5 V signal level Refer to Interprocessor Communication (IPC) TB2-1,2 24 VAC Power 18-30 VAC, neither side grounded Figure 9 CLD Module (1U6) LEDs There are four LEDs located to the right of TB1 of the CLD module. See Figure 9. The ST LED should be on continuously. If it blinks, it indicates the processor is repeatedly being reset. The +5 VDC LED should also be on continuously. It will go out if power drops below normal operating voltage. The TX LED should blink every second or two, as the CLD transmits on the IPC. The RX LED should blink continuously, indicating that other modules are communicating. Chiller Module (CPM) (1U1) WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. 46 RLC-SVD03A-EN Module Power and Miscellaneous I/O Test Points There are two test points associated with the CPM module. They are easily read with a DC voltmeter by probing the PC board solder pads found in the upper left hand corner of the module. The positive meter lead should be connected to the pad while referencing the negative meter lead to the board edge ground plane. NOTE: Don't use the aluminum module enclosure as a reference as it has an anodized surface with insulating properties. The DC voltages shall be within the tolerance specified below. If not replace the module. TP1: + 5 volts DC ± 5% TP2: +12 volts DC ± 5% RLC-SVD03A-EN 47 Module Power and Miscellaneous I/O ° TP1 + 5V ° TP2 +12V Figure 10 TB3-1 — CHILLED WATER FLOW — SWITCH H I G H V 0 L T A G E J1-4 J1-3 J1-2 J1-1 NO NO J2-2 J2-1 TB3-2 OUTDOOR AIR — TEMP — TB1-1 TB1-2 TB3-3 EMERGENCY — STOP — TB1-3 TB1-4 TB3-4 — EXTERNAL AUTO/STOP — INPUT NNS — NNS — TB1-5 TB1-6 TB4-1 TB4-2 TB4-3 — COM ALARM — (NO) RELAY — (NC) CEWT — CEWT — TB2-1 TB2-2 CLWT — CLWT — TB2-3 TB2-4 L 0 W I N P U T S — 115V H — 115V H — KEY (N/C) — 115V N — 115V N IPC (+) — IPC (-) — IPC (+) — IPC (-) — MANUF. USE ONLY V 0 L T A G E J5-1 J5-2 J5-3 J5-4 J5-5 NOT USED NOT USED { { EVAP ENTERING — WATER TEMP — J3-5 J3-4 KEY J3-3 EVAP LEAVING — WATER TEMP — J3-2 J3-1 AUX TEMP — KEY (N/C) AUX TEMP — J6-3 J6-2 J6-1 U/O VOLT TRANSF — KEY U/O VOLT TRANSF — J4-3 J4-2 J 4-1 TB4-4 TB4-5 — COM COMPR — (NO) RUN RELAY I N P U T S — COM MAX CAPACITY 0 — (NO) RELAY U T TB4-8 — COM EVAP PUMP P TB4-9 — (NO) RELAY U T TB4-10 — COM SPARE S TB4-11 — (NO) RELAY TB4-6 TB4-7 CPM (Chiller) Module (1U1) I/O terminals For the checkout of the I/O, refer to the block diagram of the module in Figure 10 and the Chiller Wiring Diagrams for both high and low voltage circuits. All voltages are measured differentially between terminal pairs specified unless otherwise indicated. The first terminal in the pair is the positive (or hot) terminal. Voltages given are nominals and may vary by ±5%. Unregulated Voltages (unreg) or 115 VAC voltages may vary by ±15%. 48 RLC-SVD03A-EN Module Power and Miscellaneous I/O Table 16 CPM (Chiller) Nominal Terminal Input and Output (1U1) Terminal Designation Description of Circuit Normal Terminal Voltages for Various Conditions J1-4 to 3 to CLD J1-2 to 1 to 1U5 IPC Communications 19.2 kbaud serial data, 5 volt signal level. Refer to Interprocessor Communication ([PC) J2-2, 1 Manufacturing Address Use Only +5 VDC No connection intended. TB1-1, 2 Outdoor Air Temperature Refer to Temperature Sensor Checkout TB1-3, 4 Emergency Stop open: 20.6 VDC unreg: Stopped closed: 0 VDC: Normal Must be jumpered if this feature is not used. TB1-5, 6 NNS (Not Used) open: 20.6 Vdc unreg: Normal closed: 0 VDC: Setback TB2-1, 2 ECWT (Not Used) N/A TB2-3, 4 LCWT (Not Used) N/A J3-5, 4 Entering Evaporator Water Temperature Refer to Temperature Sensor Checkout J3-2, 1 Leaving Evaporator Water Temperature Refer to Temperature Sensor Checkout J4-3, 1 Under/Over Voltage Transformer Input Refer to Under/Over Voltage Transformer Checkout Procedure J5-1 or 2 to J5-4 or 5 Input Power 115 VAC, Power Supply on page 41. J6-3, 1 Auxiliary Temp. Input Refer to Temperature Sensor Checkout TB3-2, 1 Chilled Water Flow Switch Input open: 115VAC: No Flow closed: < 5VAC: Flow (Software imposes a 6 second delay to respond to opening or closing. TB3-3,4 Chilled Water Demand Switch and External Auto Stop open: 115VAC: Stop closed: < 5VAC: Auto TB4-1, 2 Chiller Alarm or Alarm Ckt 1 (N.O. Contact) Dry SPDT Contact closes on Alarm, intended for 115 VAC customer control circuit. TB4-1, 3 Chiller Alarm or Alarm Ckt 1 (N.O. Contact) Dry SPDT Contact opens on Alarm, intended for 115 VAC customer control circuit. TB4-4, 5 Unit Running, Alarm Ckt 2, or Ckt 1 Running (N.O. Contact) Dry SPDT Contact closes on Unit Running, Alarm Ckt 2 or Ckt 1 Running, intended for 115 VAC customer control circuit. TB4-6, 7 Maximum Capacity or Ckt 2 Running (N.O. Contact) Dry SPDT Contact closes on Maximum Capacity or Ckt 2 Running, intended for 115 VAC customer control circuit. TB4-8, 9 Chilled Water Pump Starter (N.O. Contact) Dry SPST Contact closes when Chilled Water Demand Switch is closed, opens after time delay specified in UCM 115 VAC customer control circuit. TB4-10, 11 Spare Relay} (N.O.) Contact Dry SPST contact. 115 VAC customer control circuit. RLC-SVD03A-EN 49 Module Power and Miscellaneous I/O Options Module (CSR) (1U2) WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. Test Points There are three test points associated with the CSR module. They are easily read with a DC voltmeter by probing the PC board solder pads found in the upper left hand corner of the module. The positive meter lead should be connected to the pad, while referencing the negative meter lead to the board edge ground plane. Note: don't use the aluminum module enclosure as a reference as it has an anodized surface with insulating properties. The DC voltages shall be within the tolerance specified below. If not replace the module. TP1: + 5 volts DC ±5% TP2: + 6 volts DC ±5% TP3: +12 volts DC ±25% Switch SW-1 Switch SW1 is used to configure the External Chilled Water Setpoint input and the External Current Limit Setpoint input for either a 2-10VDC, or a 420ma signal. With the respective switch closed (on), a shunt resistor is switched into the input circuit to provide a fixed low value input impedance (499 ohms) for current loop operation. With the switch off, the input impedance is differentially 40Kohms. External Setpoint Inputs (4-20ma/2-10VDC) The chiller setpoint source should always be set to LOCAL when using any external inputs, except a Tracer. When using a Tracer, always set the chiller setpoint source to the Tracer mode. The setpoint source can be found in the Operator Settings Menu. These inputs accept either an isolated 4-20mA or 2-10VDC signal from an external controller or programming resistor connected to an internal +5V source. The switches SW1-1 and SW1-2 are used to select either the voltage or current option for External Chilled Water Setpoint and External Current Setpoint respectively. See Test Points, above. Alternately, either input may be used with a resistor or potentiometer. NOTE: Note: For proper operation, the 4-20mA/2-10VDC inputs are required to be used with a current or voltage source that: 1. 50 Is isolated (floats) with respect to ground, or RLC-SVD03A-EN Module Power and Miscellaneous I/O 2. Has its negative terminal tied to chassis ground. If the intended source does not meet the above requirement, an isolation module must be used The 4-20mA/2-10VDC inputs may be tested in the following ways: 1. Enable External Chilled Water Setpoint and/or External Current Limit Setpoint in the Operator Settings Menu. Advance display to Active Chilled Water Setpoint or Active Current Limit Setpoint to observe the respective setpoint in the Chiller Report. 2. With all wiring in place, apply an external voltage or current to the External Chilled Water Setpoint inputs (TB1-4 & 5) or the External Current Limit Setpoint (TB1-7 & 8). The voltage measured at the terminals and the resulting setpoint, as read on the CLD, should agree with the Table 17 for Chilled Water Setpoint inputs and Table 18 for Current Limit Setpoints inputs. Be sure to wait long enough when reading the display as the values are slew rate limited. 3. Disconnect all wiring to these inputs. The setpoints should slew back to the chiller's Front Panel settings. 4. Disconnect all wiring and install fixed resistors of values near those shown in the following tables across TB1-3,5 or TBl-6,8. The resulting setpoints should agree with the table values. Table 17 RLC-SVD03A-EN Input Values vs. External Chilled Water Setpoint INPUTS Resist (ohms) Current (ma) Voltage (Vdc) Resulting Chilled Water Setpt (F)±4F 94433 4.0 2.0 0.0 68609 5.2 2.6 5.0 52946 6.5 3.2 10.0 42434 7.7 3.9 15.0 34889 8.9 4.5 20.0 29212 10.2 5.1 25.0 24785 11.4 5.7 30.0 21236 12.6 6.3 35.0 18327 13.8 6.9 40.0 15900 15.1 7.6 45.0 13844 16.3 8.2 50.0 12080 17.5 8.8 55.0 10549 18.8 9.4 60.0 51 Module Power and Miscellaneous I/O Table 18 Input Values vs. External Current Limit Setpoint Resist (ohms) INPUTS Current (ma) Voltage (Vdc) Resulting Current Limit Setpt (%RLA)±5% 49000 4.0 2.0 40 29000 6.0 3.0 50 19000 8.0 4.0 60 13000 10.0 5.0 70 9000 12.0 6.0 80 6143 14.0 7.0 90 4010 16.0 8.0 100 2333 18.0 9.0 110 1000 20.0 10.0 120 Setpoint Priority There are many ways in which the Chilled Water and Current Limit setpoints can be adjusted or reset when the Options Module is present in the Chiller control system. The following flow charts show how these methods are prioritized and arbitrated under normal operating conditions. When abnormal conditions are present, such as loss of Tracer communications or out of range values on external setpoint inputs, the system will default to other methods. 52 RLC-SVD03A-EN Module Power and Miscellaneous I/O 67$57 /2&$/ 25 75$&(5 /RFDO 7UDFHU (;&(37)25&+,//(':$7(5 86($//27+(5)52173$1(/ 6(732,176 1R (;7(51$/ 6(732,176,1387 (1$%/('" (;&(37)25&+,//(':$7(5 86($//27+(5)52173$1(/ 6(732,176