Trane Series R Helical Rotary Rtac Catalogue RLC PRC006M EN (01/2015)

2015-04-02

: Trane Trane-Series-R-Helical-Rotary--Rtac-Catalogue-684180 trane-series-r-helical-rotary--rtac-catalogue-684180 trane pdf

Open the PDF directly: View PDF PDF.
Page Count: 82

DownloadTrane Trane-Series-R-Helical-Rotary--Rtac-Catalogue- RLC-PRC006M-EN (01/2015)  Trane-series-r-helical-rotary--rtac-catalogue
Open PDF In BrowserView PDF
Product Catalog

Air-Cooled Series R™ Chillers
Model RTAC
140 to 500 nominal tons (60 Hz)

January 2015

RLC-PRC006M-EN

Introduction
Like its chillers,Trane wants its relationships with customers to last.Trane is interested in
maintaining long term, loyal relationships.This perspective means the point in time that a
customer purchases a chiller is the beginning of a relationship, not the end.Your business is
important, but your satisfaction is paramount.
The RTAC offers high reliability coupled with proven Series R performance.
The Series R Model RTAC is an industrial grade design built for both the industrial and commercial
markets. It is ideal for schools, hospitals, retailers, office buildings, Internet service providers and
manufacturing facilities.

Copyright
This document and the information in it are the property ofTrane, and may not be used or
reproduced in whole or in part without written permission.Trane reserves the right to revise this
publication at any time, and to make changes to its content without obligation to notify any person
of such revision or change.

Trademarks
All trademarks referenced in this document are the trademarks of their respective owners.

Revision History
RLC-PRC006M-EN (15 Jan 2015)
The following points describe the changes to this revision on the manual:
•

Updated electrical data and customer wiring information

•

Rapid RestartTest

•

Add seismic isolator option

•

Added optional tarp information

© 2015Trane All rights reserved

RLC-PRC006M-EN

Table of Contents
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Application Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Model Number Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
General Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Electrical Connection

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56

Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Mechanical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77

RLC-PRC006M-EN

3

Features and Benefits
World Class Energy Efficiency
The importance of energy efficiency cannot be understated. Fortunately, ASHRAE has created a
guideline emphasizing its importance. Nonetheless, energy is often dismissed as an operational
cost over which the owner has little control.That perception results in missed opportunities for
energy efficiency, reduced utility bills, and higher profits. Lower utility bills directly affect
profitability. Every dollar saved in energy goes directly to the bottom line.Trane's RTAC is one way
to maximize your profits.

ASHRAE Standard 90.1 and Executive Order
AllTrane air-cooled chillers meet the new efficiency levels mandated by ASHRAE Standard 90.1.
This new standard requires higher efficiencies than past technologies can deliver.The US Federal
Government has adopted standard 90.1 and, in some cases, requires even higher efficiencies.
Federal Executive Order mandates energy consuming devices procured must be in the top 25% of
their class. In the case of chillers, that product standard is ASHRAE 90.1.Trane's RTAC meets and
exceeds the efficiency requirements of 90.1, while the high and extra efficiency RTAC can meet the
"stretch goals" of Executive Order.

Precise Capacity Control
Trane's patented unloading system allows the compressor to modulate infinitely and exactly match
building loads. At the same time chilled water temperatures will be maintained within +/- 1/2ºF
(0.28°C) of setpoint. Screw or scroll chillers with stepped capacity control do well to maintain chilled
water temperatures within 2ºF (1.1°C) of setpoint. Stepped control also results in over cooling
because rarely does the capacity of the machine match the building load.The result can be 10%
higher energy bills.Trane's RTAC optimizes the part load performance of your machine for energy
efficiency, precise control for process applications, and your personal comfort regardless of the
weather outside.

Excellent Reliability
A buildings environment is expected to be comfortable. When it is, no one says a word. If it's not…
that's a different story.The same is true with chillers. No one ever talks about chillers, yet alone
compressors, until they fail, and tenants are uncomfortable and productivity is lost.Trane's helical
rotary compressors have been designed and built to stay running when you need them.

Fewer moving parts
Trane's helical rotary compressors have only two major rotating parts: the male and female rotor.
A reciprocating compressor can have more than 15 times that number of critical parts. Multiples
of pistons, valves, crankshafts, and connecting rods in a reciprocating unit all represent different
failure paths for the compressor. In fact, reciprocating compressors can easily have a failure rate
four times of a helical rotor. Combine that with two to three reciprocating compressors for each
helical rotary compressor on chillers of equal tonnage, and statistics tell you it's a matter of time
before you lose a reciprocating compressor.

Robust components
Helical rotary compressors are precisely machined using state of the art processes from solid metal
bar stock.Tolerances are maintained within a micron or less than a tenth of the diameter of a
human hair.The resulting compressor is a robust yet highly sophisticated assembly capable of
ingesting liquid refrigerant without risk of damage.

4

RLC-PRC006M-EN

Features and Benefits

Condenser coils
Trane's condenser coils are manufactured with the same philosophy as the compressors; they're
built to last. Even though manufacturing processes have allowed thinner and thinner materials in
their assembly, with obvious material and manufacturing savings,Trane's coil material did not
change with the RTAC generation of air cooled chillers. Substantial condenser fins, that do not
require additional coating in non-corrosive environments, contribute to the highest reliability
standards for air-cooled chillers in the industry.

Superior Control
The Adaptive Control™ microprocessor system enhances the air-cooled Series R chiller by
providing the very latest chiller control technology. With the Adaptive Control microprocessor,
unnecessary service calls and unhappy tenants are avoided.The unit is designed not to trip or
unnecessarily shut down. Only when theTracer™ chiller controllers have exhausted all possible
corrective actions and the unit is still violating an operating limit will the chiller shut down. Controls
on other equipment typically shut down the chiller, usually just when it is needed the most.
For example: A typical five year old chiller with dirty coils might trip out on high pressure cutout
on a 100°F (38°C) day in August. A hot day is just when comfort cooling is needed the most. In
contrast, the air-cooled Series R chiller with an Adaptive Control microprocessor will stage fans on,
modulate electronic expansion valves, and modulate slide valve positions as the chiller approaches
a high pressure cutout, thereby keeping the chiller online when you need it the most.

Simple Installation

RLC-PRC006M-EN

•

Factory Installed Flow Switch. Installed in the optimum location in the piping for reduced
chiller installation cost and superior flow sensing, reducing the potential for nuisance trips.

•

Close Spacing Installation.The air-cooled Series R™ Chiller has the tightest recommended
side clearance in the industry, four feet for maximum performance. In situations where
equipment must be installed with less clearance than recommended, which frequently occurs
in retrofit applications, restricted airflow is common. Conventional chillers may not work at all.
However, the air-cooled Series R chiller with Adaptive Control™ microprocessor will make as
much chilled water as possible given the actual installed conditions, stay on line during
unforeseen abnormal conditions, and optimize the unit performance. Consult yourTrane sales
engineer for more details.

•

Factory Testing Means Trouble Free Startup. All air-cooled Series R chillers are given a
complete functional test at the factory.This computer based test program completely checks
the sensors, wiring, electrical components, microprocessor function, communication
capability, expansion valve performance and fans. In addition, each compressor is run and
tested to verify capacity and efficiency. Where applicable, each unit is factory preset to the
customer's design conditions; an example would be leaving liquid temperature setpoint.The
result of this test program is that the chiller arrives at the job site fully tested and ready for
operation.

•

Factory Installed and Tested Controls/Options Speed Installation. All Series R chiller
options, including main power supply disconnect, low ambient control, ambient temperature
sensor, low ambient lockout, communication interface and ice making controls, are factory
installed and tested. Some manufacturers send accessories in pieces to be field installed. With
Trane, the customer saves on installation expense and has assurance that ALL chiller controls/
options have been tested and will function as intended.

5

Features and Benefits

Unit Performance Testing
The AHRI Certification Program has had a certification program covering air-cooled water chillers
for many years. With this in mind, customers may ask, "Do I need to factory performance test my
chiller?"
Trane began promoting factory performance tests for water-cooled water chillers in 1984 for the
same reasons it is valid today for air-cooled water chillers, to show we stand behind the products
we design and build.
The benefits of a performance test include verification of performance, prevention of operational
problems, and assurance of a smooth startup. Only a performance test conducted in a laboratory
or laboratory grade facility will confirm both performance and operation of a specific chiller.
While most factory performance tests go smoothly, should problems occur,Trane personnel can
quickly correct them and the chiller will ship as specified. Job site diagnosis, ordering of parts, and
waiting for delivery of replacement components is significantly reduced.
A factory performance test reduces startup time, thereby saving job site expense. A chiller that has
been tested is operation and performance proven.This allows the installing contractor to
concentrate on proper electrical wiring and water piping, and the service technicians to concentrate
on proper refrigerant charge, safeties diagnosis and initial logging of the chiller. Means of obtaining
full load on the chiller and proving its performance do not have to be determined by engineers or
contractors, thus saving time.The certified test report documents performance for the unit as built.
In addition, factory testing significantly reduces commissioning time and risk by reintroducing
manufacturer responsibility, where its mitigation should reside.
When a factory performance test is requested, the test can be conducted at the specified design
conditions for all packaged chillers.The test facility has the capability to control ambient test
conditions to assure our customers that our chillers will perform as predicted.
Rapid Restart™ testing is also available to demonstrate the chiller’s rapid restart capabilities for
disaster relief.While the chiller is operating at customer specified full load conditions, power to the
chiller is cut and the customer can witness how quickly the chiller will return to full load.
For more information on test performance testing, see brochure RL-SLB012-EN.

6

RLC-PRC006M-EN

Application Considerations
Important
Certain application constraints should be considered when sizing, selecting and installingTrane aircooled Series R chillers. Unit and system reliability is often dependent upon proper and complete
compliance with these considerations.When the application varies from the guidelines presented,
it should be reviewed with your localTrane sales engineer.

Unit Sizing
Unit capacities are listed in the performance data section. Intentionally over sizing a unit to assure
adequate capacity is not recommended. Erratic system operation and excessive compressor
cycling are often a direct result of an oversized chiller. In addition, an oversized unit is usually more
expensive to purchase, install, and operate. If over sizing is desired, consider using multiple units.

Water Treatment
Dirt, scale, products of corrosion and other foreign material will adversely affect heat transfer
between the water and system components. Foreign matter in the chilled water system can also
increase pressure drop and consequently, reduce water flow. Proper water treatment must be
determined locally, depending on the type of system and local water characteristics. Neither salt
nor brackish water is recommended for use inTrane air-cooled Series R chillers. Use of either will
lead to a shortened life to an indeterminable degree.TheTrane Company encourages the
employment of a reputable water treatment specialist, familiar with local water conditions, to assist
in this determination and in the establishment of a proper water treatment program.

Effect Of Altitude On Capacity
Air-cooled Series R chiller capacities given in the performance data tables are for use at sea level.
At elevations substantially above sea level, the decreased air density will reduce condenser
capacity and, therefore, unit capacity and efficiency.

Ambient Limitations
Trane air-cooled Series R chillers are designed for year round operation over a range of ambient
temperatures.The Model RTAC chiller will operate as standard in ambient temperatures of 25°F to
115°F (-4°C to 46°C). With the low ambient option, these units will operate down to 0°F (-18°C). If
an ambient temperature as high as 125°F (51°C) is the basis for design, the high ambient option
will permit the chiller to run without going into a limiting condition. For installations in areas with
large ambient differences, the wide ambient option will allow the chiller to perform uninhibited
from 0°F to 125°F (-18°C to 51°C).

Water Flow Limits
The minimum and maximum water flow rates are given in the General Data tables. Evaporator flow
rates below the tabulated values will result in laminar flow causing freeze up problems, scaling,
stratification and poor control. Flow rates exceeding those listed may result in excessive tube
erosion.
Note: Flow rates in General Data tables are for water only.They do not include glycol.

Leaving Water Temperature Limits
Trane air-cooled Series R chillers have three distinct leaving water categories: standard, low
temperature, and ice making.The standard leaving solution temperature range is 40 to 65°F (4.4
to 15.6°C). Low temperature machines produce leaving liquid temperatures less than 40°F (4.4°C).
Since liquid supply temperature setpoints less than 40°F (4.4°C) result in suction temperatures at
or below the freezing point of water, a glycol solution is required for all low temperature machines.
Ice making machines have a leaving liquid temperature range of 20 to 60°F (-6.7 to 15.6°C). Ice
making controls include dual setpoint controls and safeties for ice making and standard cooling
capabilities. Consult your localTrane sales engineer for applications or selections involving low

RLC-PRC006M-EN

7

Application Considerations

temperature or ice making machines.The maximum water temperature that can be circulated
through an evaporator when the unit is not operating is 108°F (42°C).

Flow Rates Out of Range
Many process cooling jobs require flow rates that cannot be met with the minimum and maximum
published values for the Model RTAC evaporator. A simple piping change can alleviate this
problem. For example: A plastic injection molding process requires 80 gpm (5.1 l/s) of 50°F (10°C)
water and returns that water at 60°F (15.6°C).The selected chiller can operate at these
temperatures, but has a minimum flow rate of 120 gpm (7.6 l/s).The system layout in Figure A1 can
satisfy the process.
Figure 1. Flow rate out of range system layout

Flow Control
Trane requires the chilled water flow control in conjunction with the Air-Cooled Series R Chiller to
be done by the chiller.This will allow the chiller to protect itself in potentially harmful conditions.

Supply Water Temperature Drop
The performance data for theTrane air-cooled Series R chiller is based on a chilled water
temperature drop of 10°F (5.6°C). Chilled water temperature drops from 6 to 18°F (3.3 to 10°C) may
be used as long as minimum and maximum water temperatures and flow rates are not violated.
Temperature drops outside this range are beyond the optimum range for control and may
adversely affect the microcomputer's ability to maintain an acceptable supply water temperature
range. Further, temperature drops of less than 6°F (3.3°C) may result in inadequate refrigerant
superheat. Sufficient superheat is always a primary concern in any refrigerant system and is
especially important in a package chiller where the evaporator is closely coupled to the
compressor.When temperature drops are less than 6°F (3.3°C), an evaporator runaround loop may
be required.

Leaving Water Temperature Out of Range
Many process cooling jobs require temperature ranges that cannot be met with the minimum and
maximum published values for the Model RTAC evaporator. A simple piping change can alleviate
this problem. For example: A laboratory load requires 120 gpm (7.6 l/s) of water entering the
process at 85°F (29.4°C) and returning at 95°F (35°C).The accuracy required is better than the
cooling tower can give.The selected chiller has adequate capacity, but a maximum leaving chilled
water temperature of 60°F (15.6°C).
In Figure A2, both the chiller and process flow rates are equal.This is not necessary. For example,
if the chiller had a higher flow rate, there would simply be more water bypassing and mixing with
warm water.

8

RLC-PRC006M-EN

Application Considerations

Figure 2. Temperature out of range system layout

Variable Flow in the Evaporator
An attractive chilled water system option may be a variable primary flow (VPF) system. VPF
systems present building owners with several cost saving benefits that are directly related to the
pumps.The most obvious cost savings result from eliminating the secondary distribution pump,
which in turn avoids the expense incurred with the associated piping connections (material, labor),
electrical service, and variable frequency drive. Building owners often cite pump related energy
savings as the reason that prompted them to install a VPF system.
The evaporator on the Model RTAC can withstand up to 50 percent water flow reduction as long
as this flow is equal to or above the minimum flow rate requirements.The microprocessor and
capacity control algorithms are designed to handle a maximum of 10% change in water flow rate
per minute in order to maintain ± 0.5°F (0.28°C) leaving evaporator temperature control. For
applications in which system energy savings is most important and tight temperature control is
classified as +/- 2°F (1.1°C), up to 30 percent changes in flow per minute are possible.
With the help of a software analysis tool such as System Analyzer™, DOE-2 orTRACE™, you can
determine whether the anticipated energy savings justify the use of variable primary flow in a
particular application. It may also be easier to apply variable primary flow in an existing chilled
water plant. Unlike the "decoupled" system design, the bypass can be positioned at various points
in the chilled water loop and an additional pump is unnecessary.

Series Chiller Arrangements
Another energy saving strategy is to design the system around chillers arranged in series.The
actual savings possible with such strategies depends on the application dynamics and should be
researched by consulting yourTrane Systems Solutions Representative and applying an analysis
tool from theTrace software family. It is possible to operate a pair of chillers more efficiently in a
series chiller arrangement than in a parallel arrangement. It is also possible to achieve higher
entering to leaving chiller differentials, which may, in turn, provide the opportunity for lower chilled
water design temperature, lower design flow, and resulting installation and operational cost
savings.TheTrane screw compressor also has excellent capabilities for “lift,” which affords an
opportunity for “lift,” which affords an opportunity for savings on the evaporator water loop.
Series chiller arrangements can be controlled in several ways. Figure A3 shows a strategy where
each chiller is trying to achieve the system design set point. If the cooling load is less than 50 percent
of the systems capabilities, either chiller can fulfill the demand. As system loads increase, the
Chiller 2 becomes preferentially loaded as it attempts to meet the leaving chilled water setpoint.
Chiller 1 will finish cooling the leaving water from Chiller 2 down to the system design setpoint.

RLC-PRC006M-EN

9

Application Considerations

Staggering the chiller set points is another control technique that works well for preferentially
loading Chiller 1. If the cooling load is less than 50 percent of the system capacity, Chiller 1 would
be able to satisfy the entire call for cooling. As system loads increase, Chiller 2 is started to meet
any portion of the load that Chiller 1 can not meet.
Figure 3. Typical series chiller arrangement

Typical Water Piping
All building water piping must be flushed prior to making the final connections to the chiller.To
reduce heat loss and prevent condensation, insulation should be installed. Expansion tanks are
also usually required so that chilled water volume changes can be accommodated.

Short Water Loops
The proper location of the temperature control sensor is in the supply (outlet) water connection or
pipe.This location allows the building to act as a buffer and assures a slowly changing return water
temperature. If there is not a sufficient volume of water in the system to provide an adequate buffer,
temperature control can be lost, resulting in erratic system operation and excessive compressor
cycling. A short water loop has the same effect as attempting to control from the building return
water.Typically, a two minute water loop is sufficient to prevent problems.Therefore, as a
guideline, ensure the volume of water in the evaporator loop equals or exceeds two times the
evaporator flow rate in gallons per minute. For a rapidly changing load profile, the amount of
volume should be increased.To prevent the effect of a short water loop, the following items should
be given careful consideration: A storage tank or larger header pipe to increase the volume of water
in the system and, therefore, reduce the rate of change of the return water temperature.
ApplicationsTypes

10

•

Comfort cooling.

•

Industrial process cooling.

•

Ice/thermal storage.

•

Low temperature process cooling.

RLC-PRC006M-EN

Application Considerations

Typical Unit Installation
Outdoor HVAC equipment must be located to minimize noise and vibration transmission to the
occupied spaces of the building structure it serves. If the equipment must be located in close
proximity to a building, it could be placed next to an unoccupied space such as a storage room,
mechanical room, etc. It is not recommended to locate the equipment near occupied, sound
sensitive areas of the building or near windows. Locating the equipment away from structures will
also prevent sound reflection, which can increase levels at property lines, or other sensitive points.
When physically isolating the unit from structures, it is a good idea to not use rigid supports, and
to eliminate any metal-to-metal or hard material contact, when possible.This includes replacing
spring or metal weave isolation with elastomeric isolators. Figure A4 illustrates isolation
recommendations for the RTAC.
For chiller sound ratings, installation tips and considerations on chiller location, pipe isolation, etc.,
refer to theTrane Air-Cooled Series R Chillers Sound Data and Application Guide for Noise
Sensitive Installations.

System Options - Ice Storage
Trane air-cooled Series R Chillers are well suited for ice production. An air-cooled machine typically
switches to ice production at night.Two things happen under this assumption. First, the leaving
brine temperature from the evaporator is lowered to around 22 to 24°F (-5.5 to -4.4°C). Second, the
ambient temperature has typically dropped about 15 to 20°F (8.3 to 11°C) from the peak daytime
ambient.This effectively places a lift on the compressors that is similar to daytime running
conditions.The chiller can operate in lower ambient at night and successfully produce ice to
supplement the next day's cooling demands.
The Model RTAC produces ice by supplying ice storage tanks with a constant supply of glycol
solution. Air-cooled chillers selected for these lower leaving fluid temperatures are also selected
for efficient production of chilled fluid at nominal comfort cooling conditions.The ability ofTrane
chillers to serve “double duty” in ice production and comfort cooling greatly reduces the capital
cost of ice storage systems.
When cooling is required, ice chilled glycol is pumped from the ice storage tanks directly to the
cooling coils. No expensive heat exchanger is required.The glycol loop is a sealed system,
eliminating expensive annual chemical treatment costs.The air-cooled chiller is also available for
comfort cooling duty at nominal cooling conditions and efficiencies.The modular concept of glycol
ice storage systems and the proven simplicity ofTraneTracer controllers allow the successful blend
of reliability and energy saving performance in any ice storage application.
The ice storage system is operated in six different modes: each optimized for the utility cost of the
hour.
1. Provide comfort cooling with chiller
2. Provide comfort cooling with ice
3. Provide comfort cooling with ice and chiller
4. Freeze ice storage
5. Freeze ice storage when comfort cooling is required
6. Off
Tracer optimization software controls operation of the required equipment and accessories to
easily transition from one mode of operation to another. For example:
Even with ice storage systems there are numerous hours when ice is neither produced or
consumed, but saved. In this mode the chiller is the sole source of cooling. For example, to cool
the building after all ice is produced but before high electrical demand charges take effect,Tracer
sets the air-cooled chiller leaving fluid setpoint to its most efficient setting and starts the chiller,
chiller pump, and load pump.

RLC-PRC006M-EN

11

Application Considerations

When electrical demand is high, the ice pump is started and the chiller is either demand limited or
shut down completely.Tracer controls have the intelligence to optimally balance the contribution
of ice and chiller in meeting the cooling load.
The capacity of the chiller plant is extended by operating the chiller and ice in tandem.Tracer rations
the ice, augmenting chiller capacity while reducing cooling costs.When ice is produced,Tracer will
lower the air-cooled chiller leaving fluid setpoint and start the chiller, ice and chiller pumps, and
other accessories. Any incidental loads that persist while producing ice can be addressed by
starting the load pump and drawing spent cooling fluid from the ice storage tanks.
For specific information on ice storage applications, contact your localTrane sales office.

12

RLC-PRC006M-EN

Model Number Descriptions
Digits 1, 2 - Unit Model

Digit 16 - Evaporator
Configuration

Digit 27 - Electrical Protection
Options
0
5
6

Digit 4 - Development Sequence

N
P
Q
R

C

Digit 17 - Condenser Application

RT =

Rotary chiller

Digit 3 - Unit Type
A

=
=

Air-cooled
Development sequence

Digits 5, 6 & 7 - Nominal
Capacity
140
155
170
185
200
225
250
275
300
350
400
450
500

=
=
=
=
=
=
=
=
=
=
=
=
=

140 Nominal tons
155 Nominal tons
170 Nominal tons
185 Nominal tons
200 Nominal tons
225 Nominal tons
250 Nominal tons
275 Nominal tons
300 Nominal tons
350 Nominal tons
400 Nominal tons
450 Nominal tons
500 Nominal tons

Digit 8 - Unit Voltage
A
C
J
4
5

=
=
=
=
=

200/60/3
230/60/3
380/60/3
460/60/3
575/60/3

Digit 9 - Manufacturing Location
U

=

Water Chiller Business Unit,
Pueblo, CO USA

Digits 10, 11 - Design Sequence
XX =

Factory Input

Digit 12 - Unit Basic
Configuration
N
H
A

=
=
=

Standard efficiency/performance
High efficiency/performance
Extra efficiency/performance

N
H
L
W

=
=
=
=
=
=
=
=

2 pass, 0.75” insulation
3 pass, 0.75” insulation
2 pass, 1.25” insulation
3 pass, 1.25” insulation
Standard ambient (25-115°F)
High ambient (25-125°F)
Low ambient (0-115°F)
Wide ambient (0-125°F)

=
=
=

No short circuit rating
Default short circuit rating
High amp short circuit rating

Digit 28 - Flow Switch
T

=

U

=

Factory installed flow switch water
Factory installed flow switch
glycol

Digit 18 - Condenser Fin Material

Digit 29 - Control Panel
Accessories

1
2
4

N
A

=
=
=

Standard aluminum slit fins
Copper fins
CompleteCoat™ epoxy coated
fins

Digit 19 - Condenser Fan/Motor
Configuration
T =
W =

STD fans withTEAO motors
Low noise fans

Digit 20 - Compressor Motor
Starter Type
X
Y

=
=

Across-the-line
Wye-delta closed transition

Digit 21 - Incoming Power Line
Connection
1
2

= Single point power connection
= Dual point power connection

Digit 22 - Power Line Connection
Type
T
D
C

=
=
=

Terminal block connection
Non-fused disconnect switch(es)
Circuit breaker(s) )

Digit 23 - Unit Operator Interface
D

=

DynaView operator interface

=
=

No convenience outlet
15A 115V convenience outlet
(60Hz)

Digit 30 - Service Valves
1

=

With suction service valves

Digit 31 - Compressor Sound
Attenuation Option
0

=

1

=

No compressor sound
attenuation
Factory installed compressor
sound attenuation

Digit 32 - Appearance Options
N
A
C

=
=
=

No appearance options
Architectural louvered panels
Half louvers

Digit 33 - Installation
Accessories
N
F
R
G
E

=
=
=
=
=

S

=

No installation accessories
Flange kit for water connections
Neoprene in shear unit isolators
Neoprene isolators and flange kit
Seismic elastomeric isolation
pads
Seismic spring isolators

Digit 13 - Agency Listing

Digit 24 - Remote Operator
Interface

Digit 34 - Factory Testing
Options

N
U
S
R

N
C
B
L

0
C

=
=

C

=

E

=

=
=
=
=

No agency listing
C/UL listing
Seismic rated - IBC and OSHPD
C/UL listed and seismic rated

Digit 14 - Pressure Vessel Code
A
C
D
L

=
=
=
=

ASME pressure vessel code
Canadian code
Australian code
Chinese code

Digit 15 - Evaporator Application
F
G
R

=
=
=

Standard (40-60 F) leaving temp
Low (Less than 40 F) leaving temp
Remote (40-60 F) leaving temp

RLC-PRC006M-EN

=
=
=
=

No remote interface
Tracer™ Comm 3 interface
BACnet® interface
LonTalk® compatible (LCI-C)
interface

Digit 25 - Control Input
Accessories/Options
N
R

=
=

C
B

=
=

No remote inputs
Ext. evaporator leaving water
setpoint
Ext. current limit setpoint
Ext. leaving water and current
limit setpoint

Standard functional test
Customer-witnessed performance
test with report
Customer-witnessed performance
test plus Rapid Restart test
Non-witnessed performance test
with report

Digit 35 — Control, Label &
Literature
C
E
F

=
=
=

Spanish
English
French

Digit 36 — Special Order

Digit 26 - Control Output
Accessories/Options

X
S

N
A
C
D

Digit 37 — Safety Devices

=
=
=
=

No output options
Alarm relay outputs
Ice making I/O
Alarm relay outputs and ice
making I/O

N

=
=
=

Standard unit configuration
Unit has special order feature
Standard

13

General Data
Table 1.

60 Hz standard efficiency — I-P

Size

140

155

170

185

200

225

250

275

Compressor
Quantity
Nominal size
@60Hz

#

2

2

2

2

2

2

2

(tons)

70/
70

85/
70

85/
85

100/
85

100/
100

120/
100

120/
120

Evaporator
Water storage

300

350

400

450

500

3

3

4

4

4

Screw
3

85-85/ 100-100/ 120-120/ 100-100/ 120-120/ 120-120/
100
100
100
100-100 100-100 120-120
Flooded

(gal)

29

32

34

36

40

39

43

62

67

72

83

86

91

Min flow

(gpm)

193

214

202

217

241

217

241

309

339

375

404

422

461

Max flow

(gpm)

709

785

741

796

883

796

883

1134

1243

1374

1483

1548

1690

4

4

6

6

6

6

6

8

8

8

8

8

8

2 pass arrangement

Water connection (NPS-in)
3 pass arrangement
Min flow

(gpm)

129

143

135

145

161

145

161

206

226

250

270

282

307

Max flow

(gpm)

473

523

494

531

589

531

589

756

829

916

989

1032

1127

3.5

3.5

4

4

4

4

4

6

6

6

8

8

8

Water connection (NPS-in)

Condenser

Fin and tube

Qty of coils

#

4

4

4

4

4

4

4

8

8

8

8

8

8

Coil length

(in)

156/
156

180/
156

180/
180

216/
180

216/
216

252/
216

252/
252

180/
108

216/108

252/108

216/216

252/216

252/252

Coil height

# of rows
Fins per foot

(in)

42

42

42

42

42

42

42

42

42

42

42

42

42

(mm)

1067

1067

1067

1067

1067

1067

1067

1067

1067

1067

1067

1067

1067

#

3

3

3

3

3

3

3

3

3

3

3

3

3

(fpf)

192

192

192

192

192

192

192

192

192

192

192

192

192

14/6

12/12

14/12

14/14

Fan

Direct drive propeller
Quantity
Diameter

Air flow per fan
Power/motor

#

4/4

5/4

5/5

6/5

6/6

7/6

7/7

10/6

12/6

(in)

30.0

30.0

30.0

30.0

30.0

30.0

30.0

30.0

30.0

30.0

30.0

30.0

30.0

(cfm)

9625

9394

9209

9209

9209

9210

9210

9209

9209

9208

9209

9210

9214

(hp)

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

(rpm)

1140

1140

1140

1140

1140

1140

1140

1140

1140

1140

1140

1140

1140

Tip speed (Ft/min) 8954

8954

8954

8954

8954

8954

8954

8954

8954

8954

8954

8954

8954

Fan speed

General Unit

HFC-134a

# Refrig ckts

#

2

2

2

2

2

2

2

2

2

2

2

2

2

% min load

%

15

15

15

15

15

15

15

15

15

15

15

15

15

Refrigerant charge

(lb)

165/
165

175/
165

175/
175

215/
210

215/
215

225/
215

225/
225

365/
200

415/200

460/200

415/415

460/415

460/460

Oil charge

(gal)

1.3/
1.3

1.3/
1.3

1.3/
1.3

1.9/
1.3

1.9/
1.9

1.9/
1.9

1.9/
1.9

4.2/1.9

4.6/2.9

4.6/1.9

4.6/4.6

4.6/4.6

4.6/4.6

Min ambient-std

(°F)

25

25

25

25

25

25

25

25

25

25

25

25

25

Min ambient-low

(°F)

0

0

0

0

0

0

0

0

0

0

0

0

0

1. Data containing information on two circuits is shown as follows: ckt 1/ ckt 2.
2. Minimum start-up/operating ambient is based on a 5 mph wind across the condenser.

14

RLC-PRC006M-EN

General Data

Table 2.

60 Hz high efficiency — I-P

Size

140

155

170

185

200

Compressor
Quantity
Nominal size
@60Hz

225

250

275

300

350

400

Screw
#

2

2

2

2

2

2

100/100 120/100

2

3

3

4

4

120/120

85-85/
100

100100/100

85-85/
85/85

100-100/
100-100

72

72

83

91

(tons)

70/70

85/70

85/85

100/85

(gal)

34

36

40

39

43

43

43

Min flow

(gpm)

202

217

241

217

241

241

241

375

375

404

461

Max flow

(gpm)

741

796

883

796

883

883

883

1374

1374

1483

1690

6

6

6

6

6

6

6

8

8

8

8

Evaporator
Water storage

Flooded

2 pass arrangement

Water connection (NPS-in)
3 pass arrangement
Min flow

(gpm)

135

145

161

145

161

161

161

250

250

270

307

Max flow

(gpm)

494

531

589

531

589

589

589

916

916

989

1127

4

4

4

4

4

4

4

6

6

8

8

8

8

Water connection (NPS-in)

Condenser

Fin and tube

Qty of coils

#

Coil length

(in)

Coil height

(in)

Number of rows
Fins per foot

4

4

4

4

4

8

180/180 216/180 216/216 252/216 252/252 144/144
42

42

42

42

42

42

8

8

144/144

216/144

42

42

252/144 216/216
42

42

8
252/252
42

#

3

3

3

3

3

3

3

3

3

3

3

(fpf)

192

192

192

192

192

192

192

192

192

192

192

#

5/5

6/5

6/6

7/6

7/7

12/6

14/6

12/12

14/14

Fan

Direct drive propeller
Quantity
Diameter
Air flow/fan
Power/motor
Fan speed

8/6

8/8

(in)

30

30

30

30

30

30

30

30

30

30

30

(cfm)

9199

9199

9199

9200

9201

9783

9203

9652

9605

9199

9201

(hp)

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

(rpm)

1140

1140

1140

1140

1140

1140

1140

1140

1140

1140

1140

8954

8954

8954

8954

8954

8954

8954

8954

8954

8954

8954

Tip speed (Ft/Min)

General Unit

HFC-134a

# Refrig ckts

#

2

2

2

2

2

2

2

2

2

2

2

% min load

%

15

15

15

15

15

15

15

15

15

15

15

Refrigerant
charge

(lb)

175/175 215/205 215/215 225/215 225/225

235/235

235/235

415/200 460/200 415/415

460/460

Oil charge

(gal)

1.3/1.3

1.3/1.3

1.3/1.3

1.9/1.3

1.9/1.9

1.9/1.9

1.9/1.9

2.1-2.1/
1.9

2.3-2.3/
1.9

2.1-2.1/
2.1-2.1

2.3-2.3/
2.3-2.3

Min ambient-std

(°F)

25

25

25

25

25

25

25

25

25

25

25

Min ambient-low

(°F)

0

0

0

0

0

0

0

0

0

0

0

1. Data containing information on two circuits is shown as follows: ckt 1/ ckt 2.
2. Minimum start-up/operating ambient is based on a 5 mph wind across the condenser.

RLC-PRC006M-EN

15

General Data

Table 3.

60 Hz extra efficiency — I-P

Size

140

155

170

185

200

Compressor
Quantity
Nominal size
@60Hz

#
(tons)

2
70/70

2
85/70

2
85/85

2

275

3

3

4

4

70-70/85

85-85/85

70-70/
70-70

85-85/
85-85

72

72

83

91

2

100/85

Evaporator
Water storage

250

300

350

Screw

100/100
Flooded

(gal)

40

39

43

43

43

Min flow

(gpm)

241

217

241

241

241

375

375

404

461

Max flow

(gpm)

883

796

883

883

883

1374

1374

1483

1690

6

6

6

6

6

8

8

8

8

2 pass arrangement

Water connection (NPS-in)
3 pass arrangement
Min flow

(gpm)

161

145

161

161

161

250

250

270

307

Max flow

(gpm)

589

531

589

589

589

916

916

989

1127

4

4

4

4

4

6

6

8

8

Water connection (NPS-in)

Condenser

Fin and tube

Qty of coils

#

4

4

4

8

8

8

8

8

8

Coil length

(in)

216/216

252/216

252/252

144/144

144/144

216/144

252/144

216/216

252/252

Coil height

(in)

42

42

42

42

42

42

42

42

42

#

3

3

3

3

3

3

3

3

3

(fpf)

192

192

192

192

192

192

192

192

192

Quantity

#

6/6

7/6

7/7

8/6

8/8

12/6

14/6

12/12

14/14

Diameter

(in)

30

30

30

30

30

30

30

30

30

(cfm)

9199

9200

9201

9783

9203

9652

9605

9199

9201

Number of rows
Fins per foot

Fan

Direct drive propeller

Air flow/fan
Power/motor
Fan speed

(hp)

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

(rpm)

1140

1140

1140

1140

1140

1140

1140

1140

1140

8954

8954

8954

8954

8954

8954

8954

8954

8954

Tip speed (Ft/Min)

General Unit

HFC-134a

# Refrig ckts

#

2

2

2

2

2

2

2

2

2

% min load

%

15

15

15

15

15

15

15

15

15

Refrigerant charge

(lb)

215/215

225/215

225/225

235/235

235/235

415/200

460/200

415/415

460/460

Oil charge

(gal)

1.3/1.3

1.9/1.3

1.9/1.9

1.9/1.9

1.9/1.9

2.1-2.1/
2.1-2.1

2.1-2.1/
2.1-2.1

Min ambient-std

(°F)

25

25

25

25

25

25

25

25

25

Min ambient-low

(°F)

0

0

0

0

0

0

0

0

0

2.1-2.1/1.9 2.1-2.1/1.9

1. Data containing information on two circuits is shown as follows: ckt 1/ ckt 2.
2. Minimum start-up/operating ambient is based on a 5 mph wind across the condenser.

16

RLC-PRC006M-EN

General Data

Table 4.

60 Hz standard efficiency — SI

Size

140

155

170

185

200

225

250

275

Compressor
Quantity

300

350

400

450

500

3

3

4

4

4

Screw
#

Nominal size
(tons) @60Hz

2

2

2

2

2

2

2

100/
100

120/
100

120/
120

3

70/70

85/70

85/85

100/
85

85-85/ 100-100/ 120-120/ 100-100/ 120-120/ 120-120/
100
100
100
100-100 100-100 120-120

(L)

110.0

121

129

136

151

148

163

235

254

273

314

326

Min flow

(L/s)

12

14

13

14

15

14

15

19

21

24

25

27

29

Max flow

(L/s)

45

50

47

50

56

50

56

72

78

87

94

98

107

4

4

6

6

6

6

6

8

8

8

8

8

8

Evaporator
Water storage

Flooded
344

2 pass arrangement

Water connection (NPS-in)
3 pass arrangement
Min flow

(L/s)

8

9

9

9

10

9

10

13

14

16

17

18

19

Max flow

(L/s)

30

33

31

34

37

34

37

48

52

58

62

65

71

3.5

3.5

4

4

4

4

4

6

6

6

8

8

8

Water connection (NPS-in)

Condenser
Qty of coils

Fin and tube
#

4

4

4

8

8

8

8

8

8

Coil length

(mm)

3962/
3962

4572/
3962

4572/ 5486/ 5486/ 6400/
4572 4572 5486 5486

6400/
6400

4572/
2743

5486/
2743

6400/
2743

5486/
5486

6400/
5486

6400/
6400

Coil height

(mm)

1067

1067

1067

1067

1067

1067

1067

1067

1067

1067

# of rows
Fins per foot

4

4

1067

4

1067

4

1067

#

3

3

3

3

3

3

3

3

3

3

3

3

3

(fpf)

192

192

192

192

192

192

192

192

192

192

192

192

192

14/14

Fan

Direct drive propeller
Quantity

#

4/4

5/4

5/5

6/5

6/6

7/6

7/7

10/6

12/6

14/6

12/12

14/12

Diameter

(mm)

726.0

726.0

726.0

726.0

726.0

726.0

726.0

726.0

726.0

726.0

726.0

726.0

726.0

Air flow per fan (m³/hr) 16351 15958 15644 15644 15644 15646 15647

15644

15645

15642

15645

15646

15653

1.12

1.12

1.12

1.12

1.12

1.12

Power/motor

(kW)

1.12

1.12

1.12

1.12

1.12

1.12

1.12

Fan speed

(rps)

19

19

19

19

19

19

19

19

19

19

19

19

19

Tip speed

M/S

45

45

45

45

45

45

45

45

45

45

45

45

45

# Refrig ckts

#

2

2

2

2

2

2

2

2

2

2

2

2

2

% min load

%

15

15

15

15

15

General Unit

HFC-134a

Refrigerant
charge

(kg)

75/75

Oil charge

(L)

5/5

79/75 79/79
5/5

5/5

98/95 98/98
7/5

7/7

15

15

15

15

15

15

15

15

102/
98

102/
102

166/91

188/91

209/91

188/188

209/188

209/209

7/7

7/7

8-8/7

9-9/11

9-9/11

9-9/9-9

9-9/9-9

9-9/9-9

Min ambient-std

(°C)

-3.9

-3.9

-3.9

-3.9

-3.9

-3.9

-3.9

-3.9

-3.9

-3.9

-3.9

-3.9

-3.9

Min ambient-low

(°C)

-17.8

-17.8

-17.8

-17.8

-17.8

-17.8

-17.8

-17.8

-17.8

-17.8

-17.8

-17.8

-17.8

1. Data containing information on two circuits is shown as follows: ckt 1/ ckt 2.
2. Minimum start-up/operating ambient is based on a 5 mph wind across the condenser.

RLC-PRC006M-EN

17

General Data

Table 5.

60 Hz high efficiency — SI

Size

140

Compressor
Quantity
Nominal size
@60Hz

155

170

185

200

225

250

2

2

2

2

2

2

275

300

350

400

Screw
#

2

100/100 120/100 120/120

3

3

4

4

85-85/
100

100100/100

85-85/
85/85

100-100/
100-100

344

(tons)

70/70

85/70

85/85

100/85

(L)

129

136

151

148

163

163

163

273

273

314

Min flow

(L/s)

13

14

15

14

15

15

15

24

24

25

29

Max flow

(L/s)

47

50

56

50

56

56

56

87

87

94

107

6

6

6

6

6

6

6

8

8

8

8

Evaporator
Water storage

Flooded

2 Pass arrangement

Water connection (NPS-in)
3 Pass arrangement
Min flow

(L/s)

9

9

10

9

10

10

10

16

16

17

19

Max flow

(L/s)

31

34

37

34

37

37

37

58

58

62

71

4

4

4

4

4

4

4

6

6

8

8

Water connection (NPS-in)

Condenser
Qty of coils

Fin and tube
#

4

4

4

4

4

8

8

8

8

8

8

Coil length

(mm)

4572/
4572

5486/
4572

5486/
5486

6400/
5486

6400/
6400

3657/
3657

3657/
3657

5486/
3657

6400/
3657

5486/
5486

6400/
6400

Coil height

(mm)

1067

1067

1067

1067

1067

1067

1067

1067

1067

1067

1067

Number of rows
Fins per foot

#

3

3

3

3

3

3

3

3

3

3

3

(fpf)

192

192

192

192

192

192

192

192

192

192

192

14/14

Fan

Direct drive propeller
Quantity

#

5/5

6/5

6/6

7/6

7/7

8/6

8/8

12/6

14/6

12/12

Diameter

(mm)

762

762

762

762

762

762

762

762

762

762

762

15628

15628

15628

15629

15631

16619

15634

16397

16317

15628

15631

1.12

1.12

1.12

1.12

1.12

1.12

1.12

1.12

1.12

1.12

1.12

Air per fan (m³/hr)
Power/motor

(kW)

Fan speed

(rps)

19

19

19

19

19

19

19

19

19

19

19

Tip speed

M/S

45

45

45

45

45

45

45

45

45

45

45

#

2

2

2

2

2

2

2

2

2

2

2

15

15

15

General Unit
# refrig ckts
% min load
Refrig charge
Oil charge

HFC-134a

%

15

15

15

15

(kg)

79/79

98/93

98/98

102/98

102/102 107/107 107/107

15

15

15

15

188/91

209/91

188/188

209/209

(L)

5/5

5/5

5/5

7/5

7/7

7/7

7/7

8-8/7

9-9/7

8-8/8-8

9-9/9-9

Min ambient-std

(°C)

-3.9

-3.9

-3.9

-3.9

-3.9

-3.9

-3.9

-3.9

-3.9

-3.9

-3.9

Min ambient-low

(°C)

-17.8

-17.8

-17.8

-17.8

-17.8

-17.8

-17.8

-17.8

-17.8

-17.8

-17.8

1. Data containing information on two circuits is shown as follows: ckt 1/ ckt 2.
2. Minimum start-up/operating ambient is based on a 5 mph wind across the condenser.

18

RLC-PRC006M-EN

General Data

Table 6.

60 Hz extra efficiency — SI

Size

140

155

170

185

200

250

275

300

350

2

2

2

2

2

3

3

4

4

85-85/100

100-100/
100

85-85/85/
85

100-100/
100-100

344

Compressor
Quantity
Nominal size
@60Hz

#
(tons)

85/85

100/85

100/100

120/100

Evaporator
Water storage

120/120
Flooded

(L)

151

148

163

163

163

273

273

314

Min flow

(L/s)

15

14

15

15

15

24

24

25

29

Max flow

(L/s)

56

50

56

56

56

87

87

94

107

6

6

6

6

6

8

8

8

8

2 Pass arrangement

Water connection (NPS-in)
3 Pass arrangement
Min flow

(L/s)

10

9

10

10

10

16

16

17

19

Max flow

(L/s)

37

34

37

37

37

58

58

62

71

4

4

4

4

4

6

6

8

8

8

8

8

8

Water connection (NPS-in)

Condenser

Fin and tube

Qty of coils

#

Coil length

(mm)

Coil height

(mm)

1067

1067

1067

1067

1067

1067

1067

1067

#

3

3

3

3

3

3

3

3

3

(fpf)

192

192

192

192

192

192

192

192

192

Quantity

#

6/6

7/6

7/7

8/6

8/8

12/6

14/6

12/12

14/14

Diameter

(mm)

762

762

762

762

762

762

762

762

762

15628

15629

15631

16619

15634

16397

16317

15628

15631
1.12

Number of rows
Fins per foot

4

4

4

8

8

5486/5486 6400/5486 6400/6400 3657/3657 4572/2743 5486/3657 6400/3657 5486/5486

Fan

6400/6400
1067

Direct drive propeller

Air per fan (m³/hr)
Power/motor

(kW)

1.12

1.12

1.12

1.12

1.12

1.12

1.12

1.12

Fan speed

(rps)

19

19

19

19

19

19

19

19

19

Tip speed

M/S

45

45

45

45

45

45

45

45

45

General Unit

HFC-134a

# refrig ckts

#

2

2

2

2

2

2

2

2

2

% min load

%

15

15

15

15

15

15

15

15

15

(kg)

98/98

102/98

102/102

107/107

107/107

188/91

209/91

188/188

209/209
8-8/8-8

Refrig charge

(L)

5/5

7/5

7/7

7/7

7/7

8-8/7

8-8/7

8-8/8-8

Min ambient-std

Oil charge

(°C)

-3.9

-3.9

-3.9

-3.9

-3.9

-3.9

-3.9

-3.9

-3.9

Min ambient-low

(°C)

-17.8

-17.8

-17.8

-17.8

-17.8

-17.8

-17.8

-17.8

-17.8

1. Data containing information on two circuits is shown as follows: ckt 1/ ckt 2.
2. Minimum start-up/operating ambient is based on a 5 mph wind across the condenser.

RLC-PRC006M-EN

19

Performance Data
Table 7.

60 Hz standard efficiency – I-P units

Evap
Leaving
Water
Temp (°F)

40

42

44

20

Cond Entering Air Temp (°F)
85

95

105

115

Unit
Size

Tons

kW
Input²

EER³

Tons

kW
Input²

EER³

Tons

kW
Input²

EER³

Tons

kW
Input²

EER³

140

138.1

139.6

10.9

128.3

151.9

9.4

118.3

165.8

8

108

181.2

6.7

155

151.5

151.6

11

141

165

9.5

130.1

180.1

8.1

119

196.9

6.8

170

165.6

163.8

11.1

154.4

178.5

9.6

142.7

194.9

8.2

130.9

213.2

6.9

185

181.5

182

10.9

169.2

197.8

9.5

156.6

215.5

8.1

143.6

235.4

6.8

200

198.5

201

10.9

185.1

217.8

9.4

171.3

236.9

8.1

156.9

258.3

6.8

225

218

221.6

10.8

203.6

240.2

9.4

188.6

261.2

8.1

173.1

284.8

6.8

250

239.1

243.3

10.8

223.5

263.6

9.4

207.2

286.6

8.1

190.2

312.4

6.9

275

265.5

266.3

10.9

247.6

289.2

9.5

229.1

315.1

8.1

210.2

344

6.9

300

298.4

304.8

10.8

278.3

329.8

9.4

257.6

358.3

8

236.3

390.2

6.8

350

338.9

348.7

10.7

316.6

377.1

9.3

293.4

409.3

8

269.3

445.4

6.8

400

400.7

409.7

10.8

374.1

443.2

9.4

346.4

481.3

8

317.9

524

6.8

450

440.8

453.5

10.7

412

490.4

9.3

382

532.4

8

350.9

579.4

6.8

500

482.4

498.3

10.7

451.1

538.5

9.3

418.5

584.2

8

384.5

635.4

6.8

140

143.4

142.6

11.1

133.3

155

9.6

122.9

168.9

8.1

112.2

184.4

6.9

155

157.3

154.8

11.2

146.4

168.3

9.6

135.2

183.5

8.2

123.7

200.4

6.9

170

171.8

167.3

11.3

160.2

182

9.7

148.3

198.6

8.3

136

217

7

185

188.2

185.9

11.1

175.6

201.8

9.6

162.5

219.7

8.3

149.1

239.6

7

200

205.8

205.4

11

192

222.4

9.6

177.7

241.6

8.2

162.9

263.1

7

225

225.9

226.5

11

211.1

245.3

9.6

195.6

266.5

8.2

179.6

290.3

7

250

247.9

248.8

11

231.7

269.3

9.6

214.8

292.6

8.2

197.3

318.6

7

275

275.3

272

11.1

256.8

295.1

9.6

237.8

321.1

8.3

218.3

350.2

7

300

309.3

311.6

10.9

288.6

336.8

9.5

267.2

365.4

8.2

245.2

397.5

6.9

350

351.3

356.7

10.9

328.2

385.3

9.5

304.2

417.8

8.2

279.3

454.3

6.9

400

415.1

418.8

10.9

387.6

452.6

9.5

359.1

490.9

8.2

329.7

533.8

7

450

456.6

463.7

10.9

426.8

500.9

9.5

395.8

543.2

8.2

363.7

590.7

6.9

500

499.7

509.7

10.9

467.4

550.3

9.5

433.6

596.4

8.2

398.5

648.3

6.9

140

148.7

145.6

11.3

138.3

158.1

9.7

127.6

172.1

8.3

116.6

187.7

7

155

163.1

158.1

11.4

151.9

171.7

9.8

140.3

187

8.4

128.5

204

7.1

170

178.1

170.8

11.5

166.1

185.6

9.9

153.8

202.3

8.5

141.3

220.8

7.2

185

195

189.9

11.3

182

205.9

9.8

168.5

223.9

8.4

154.7

244

7.1

200

213.2

210

11.2

198.9

227.1

9.7

184.2

246.4

8.4

169

268.1

7.1

225

234

231.6

11.2

218.6

250.5

9.7

202.7

271.9

8.4

186.1

295.9

7.1

250

256.8

254.5

11.2

240.1

275.2

9.7

222.6

298.7

8.4

204.4

325

7.1

275

285.3

277.9

11.3

266.2

301.1

9.8

246.6

327.3

8.4

226.5

356.5

7.2

300

320.3

318.6

11.1

299

343.9

9.7

276.9

372.7

8.3

254.2

405

7.1

350

363.9

364.9

11

340

393.7

9.6

315.2

426.5

8.3

289.5

463.3

7.1

400

429.7

428.1

11.1

401.3

462.1

9.7

371.9

500.6

8.3

341.6

543.7

7.1

450

472.6

474.1

11

441.9

511.7

9.6

409.9

554.3

8.3

376.7

602.2

7.1

500

517.3

521.4

11

483.9

562.4

9.6

449

609

8.3

412.6

661.4

7.1

RLC-PRC006M-EN

Performance Data

Table 7.

60 Hz standard efficiency – I-P units (continued)

Evap
Leaving
Water
Temp (°F)

46

48

Cond Entering Air Temp (°F)
85

95

105

EER³

Tons

kW
Input²

EER³

Tons

kW
Input²

115
EER³

Tons

kW
Input²

EER³

Unit
Size

Tons

kW
Input²

140

154.1

148.8

11.5

143.4

161.3

9.9

132.3

175.4

8.5

121

191

7.2

155

169

161.5

11.6

157.4

175.2

10

145.6

190.5

8.6

133.4

207.6

7.2

170

184.5

174.4

11.7

172.2

189.3

10.1

159.5

206.1

8.7

146.6

224.7

7.3

185

201.9

194.1

11.5

188.5

210.1

10

174.6

228.3

8.6

160.4

248.5

7.3

200

220.7

214.7

11.4

206

231.9

9.9

190.8

251.3

8.5

175.1

273.1

7.2

225

242.1

236.8

11.3

226.3

255.8

9.9

209.8

277.5

8.5

192.8

301.7

7.2

250

265.8

260.2

11.3

248.5

281.2

9.9

230.5

304.9

8.5

211.6

331.6

7.2

275

295.4

284

11.5

275.8

307.3

10

255.6

333.6

8.6

234.9

362.9

7.3

300

331.5

325.7

11.3

309.5

351.2

9.8

286.7

380.2

8.5

263.3

412.6

7.2

350

376.6

373.3

11.2

352

402.4

9.8

326.3

435.4

8.4

297.3

467.6

7.2

400

444.4

437.6

11.2

415.2

471.8

9.8

384.9

510.5

8.5

353.7

553.8

7.2

450

488.8

484.8

11.2

457.1

522.7

9.8

424.1

565.7

8.4

384.5

602.6

7.2

500

535.2

533.4

11.2

500.7

574.8

9.7

464.5

621.9

8.4

416.8

652.5

7.2

140

159.6

152

11.7

148.5

164.6

10.1

137.1

178.7

8.6

124.5

192.8

7.3

155

175

164.9

11.7

163.1

178.7

10.2

150.8

194.2

8.7

137.3

209.6

7.4

170

190.9

178.1

11.8

178.3

193.1

10.3

165.3

210

8.8

152

228.6

7.5

185

208.9

198.3

11.6

195.1

214.5

10.1

180.8

232.7

8.7

166.2

253

7.4

200

228.2

219.4

11.5

213.1

236.7

10

197.4

256.3

8.6

181.3

278.1

7.4

225

250.4

242

11.5

234.1

261.3

10

217.1

283.1

8.6

199.5

307.5

7.3

250

275

266.2

11.5

257.1

287.3

10

238.4

311.3

8.6

216

331.7

7.4

275

305.7

290.2

11.7

285.4

313.6

10.1

264.7

340

8.7

243.3

369.5

7.4

300

342.8

333

11.4

320.1

358.7

10

296.7

387.7

8.6

272.5

420.3

7.3

350

389.6

381.8

11.3

364.1

411.2

9.9

337.5

444.5

8.5

301.2

462.7

7.3

400

459.4

447.4

11.4

429.2

481.7

9.9

398.1

520.6

8.6

363.2

558.7

7.3

450

505.3

495.8

11.3

472.6

533.9

9.9

438.5

577.3

8.5

389.9

597.2

7.4

500

553.4

545.7

11.3

517.7

587.5

9.9

480.3

635.2

8.5

421.5

644.1

7.4

1. Rated in accordance with AHRI Standard 550/590 based on TOPSS version 140: sea level altitude, evaporator fouling factor of 0.0001°F-ft²h/Btu,
evaporator temperature drop of 10°F, and 2 pass evaporator configuration. Consult a Trane representative for additional performance information.
2. kW input is for compressors only.
3. EER = Energy Efficiency Ratio (Btu/watt-hour). Power inputs include compressors, condenser fans and control power.
4. Interpolation between points is permissible. Extrapolation is not permitted.

RLC-PRC006M-EN

21

Performance Data

Table 8.

60 Hz high efficiency – I-P units

Evap
Leaving
Water
Temp (°F)

40

42

44

22

Cond Entering Air Temp (°F)
85

95

105

115

Unit
Size

Tons

kW
Input²

EER³

Tons

kW
Input²

EER³

Tons

kW
Input²

EER³

Tons

kW
Input²

EER³

140

141.1

134.3

11.3

131.4

145.8

9.8

121.4

158.8

8.4

111.1

173.5

7.1

155

156.2

145.2

11.5

145.6

157.9

10

134.7

172.3

8.6

123.5

188.4

7.2

170

170.1

156.6

11.7

158.7

170.4

10.1

147

186.1

8.6

134.9

203.6

7.3

185

186.9

175.1

11.5

174.6

190

10

161.8

206.9

8.6

148.7

225.9

7.3

200

204.8

194.4

11.4

191.4

210.2

9.9

177.4

228.3

8.5

163.1

248.7

7.3

225

221.3

215.8

11.2

207.2

233.2

9.8

192.5

253.1

8.4

177.2

275.5

7.2

250

244.1

236.8

11.2

228.8

255.9

9.8

212.8

277.7

8.5

196.1

302.3

7.2

275

273.5

256.1

11.6

255.4

277.6

10.1

236.8

302.2

8.6

217.7

329.8

7.3

300

306.7

294.5

11.3

286.8

318

9.9

266.1

344.9

8.5

244.8

375.2

7.3

350

344.2

318.4

11.6

321.6

346

10.1

298.2

377.3

8.7

274.3

412.4

7.3

400

413

396.6

11.3

386.3

428

9.9

358.5

463.9

8.5

329.9

504.4

7.3

140

146.6

137

11.5

136.7

148.6

10

126.3

161.8

8.6

115.7

176.5

7.3

155

162.3

148.2

11.8

151.4

161

10.2

140.2

175.4

8.8

128.6

191.6

7.4

170

176.7

159.8

11.9

165

173.7

10.3

152.9

189.5

8.8

140.5

207.1

7.5

185

194

178.8

11.7

181.3

193.8

10.2

168.2

210.8

8.8

154.7

229.9

7.5

200

212.6

198.7

11.6

198.7

214.6

10.1

184.3

232.8

8.7

169.5

253.2

7.4

225

229.7

220.6

11.4

215.1

238.1

10

199.9

258.1

8.6

184.1

280.7

7.3

250

253.3

242.1

11.4

237.5

261.3

10

220.9

283.3

8.6

203.6

308.2

7.4

275

284

261.5

11.8

265.4

283.2

10.3

246.2

307.9

8.8

226.5

335.6

7.5

300

318.4

301

11.5

297.8

324.6

10.1

276.4

351.6

8.7

254.4

382.1

7.4

350

357.3

324.9

11.8

333.9

352.7

10.3

309.9

384.1

8.9

285.2

419.4

7.5

400

428.4

405.3

11.5

400.8

436.8

10

372.2

472.9

8.7

342.7

513.6

7.4

140

152.3

139.9

11.8

142

151.5

10.2

131.4

164.8

8.8

120.4

179.5

7.4

155

168.5

151.3

12

157.3

164.1

10.4

145.7

178.6

9

133.8

194.9

7.6

170

183.4

163.1

12.1

171.3

177.1

10.5

158.9

192.9

9

146.1

210.6

7.7

185

201.3

182.6

11.9

188.2

197.6

10.4

174.6

214.7

9

160.7

233.9

7.6

200

220.5

203.1

11.8

206.2

219

10.3

191.3

237.3

8.9

176

257.9

7.6

225

238.2

225.6

11.6

223.2

243.2

10.1

207.5

263.3

8.8

191.2

286.1

7.5

250

262.7

247.5

11.6

246.3

266.9

10.2

229.2

289.1

8.8

211.3

314.2

7.5

275

294.7

267.1

12

275.5

288.9

10.5

255.7

313.7

9

235.4

341.5

7.7

300

330.2

307.7

11.7

308.9

331.4

10.3

286.8

358.5

8.9

264.1

389.1

7.6

350

370.5

331.6

12.1

346.5

359.5

10.5

321.8

391.1

9

296.4

426.5

7.7

400

444.1

414.3

11.7

415.6

445.9

10.2

386.1

482.2

8.8

355.6

523

7.6

RLC-PRC006M-EN

Performance Data

Table 8.

60 Hz high efficiency – I-P units (continued)

Evap
Leaving
Water
Temp (°F)

46

48

Cond Entering Air Temp (°F)
85

95

105

EER³

Tons

kW
Input²

EER³

Tons

kW
Input²

115
EER³

Tons

kW
Input²

EER³
7.6

Unit
Size

Tons

kW
Input²

140

158

142.8

12

147.4

154.5

10.4

136.5

167.8

9

125.2

182.7

155

174.8

154.4

12.2

163.2

167.3

10.6

151.3

181.9

9.2

139.1

198.2

7.8

170

190.3

166.4

12.3

177.8

180.5

10.7

165

196.4

9.2

151.9

214.2

7.9

185

208.6

186.5

12.1

195.1

201.6

10.6

181.2

218.7

9.1

166.9

238

7.8

200

228.5

207.5

12

213.7

223.6

10.5

198.4

241.9

9.1

182.7

262.6

7.7

225

246.9

230.6

11.8

231.3

248.3

10.3

215.1

268.6

8.9

198.3

291.5

7.6

250

272.2

253.1

11.8

255.3

272.6

10.3

237.6

295

8.9

219.1

320.4

7.7

275

305.6

272.9

12.2

285.8

294.7

10.7

265.4

319.6

9.2

244.4

347.5

7.8

300

342.1

314.5

11.9

320.2

338.3

10.4

297.5

365.6

9

274

396.3

7.7

350

384

338.5

12.3

359.3

366.5

10.7

333.9

398.2

9.2

307.8

433.7

7.9

400

459.9

423.4

11.8

430.6

455.2

10.4

400.2

491.6

9

368.8

532.6

7.7

140

163.9

145.8

12.2

153

157.6

10.6

141.7

170.9

9.1

129

184.2

7.8

155

181.2

157.6

12.5

169.3

170.6

10.8

157.1

185.2

9.3

143.7

200.4

8

170

197.2

169.9

12.6

184.4

184

10.9

171.2

200

9.4

157.7

217.9

8

185

216.1

190.5

12.3

202.2

205.6

10.8

187.9

222.8

9.3

173.1

242.2

8

200

236.6

212.1

12.2

221.4

228.2

10.7

205.7

246.6

9.2

189.4

267.3

7.9

225

255.7

235.8

11.9

239.6

253.6

10.5

222.9

274

9.1

205.5

297.1

7.8

250

281.9

258.7

12

264.5

278.4

10.5

246.1

301.1

9.1

226

324.8

7.8

275

316.7

278.7

12.4

296.2

300.7

10.8

275.2

325.6

9.4

253.7

353.6

8

300

354.3

321.5

12.1

331.6

345.4

10.6

308.2

372.7

9.2

284.1

403.6

7.9

350

397.8

345.5

12.5

372.3

373.6

10.9

346.2

405.5

9.4

319.4

441

8

400

476

432.8

12

445.8

464.7

10.6

414.5

501.2

9.2

382.1

542.4

7.9

1. Rated in accordance with AHRI Standard 550/590 based on TOPSS version 140: sea level altitude, evaporator fouling factor of 0.0001°F-ft²h/Btu,
evaporator temperature drop of 10°F, and 2 pass evaporator configuration. Consult a Trane representative for additional performance information.
2. kW input is for compressors only.
3. EER = Energy Efficiency Ratio (Btu/watt-hour). Power inputs include compressors, condenser fans and control power.
4. Interpolation between points is permissible. Extrapolation is not permitted.

RLC-PRC006M-EN

23

Performance Data

Table 9.

60 Hz extra efficiency – I-P units

Evap
Leaving
Water
Temp (°F)

40

42

44

46

24

Cond Entering Air Temp (°F)
85

95

105

EER³

Tons

kW
Input²

EER³

Tons

kW
Input²

115
EER³

Tons

kW
Input²

Unit
Size

Tons

kW
Input²

140

146

129.3

11.8

136.1

140.2

10.3

125.8

152.6

8.8

114.9

166.6

7.5

155

160.8

140.3

12

150.1

152.4

10.5

139.1

166.2

9

127.4

181.7

7.6

170

176.3

151.7

12.2

164.7

164.9

10.6

152.8

180

9.1

140.1

196.8

7.7

185

189.4

170.9

11.8

177.2

184.9

10.3

164.6

201

8.9

150.9

219

7.6

200

207.9

190

11.6

194.6

205

10.2

180.9

222.2

8.8

165.7

241.5

7.5

250

234.9

206.6

12

219.3

224

10.5

203.1

243.9

9

185.7

266.2

7.6

275

264

229.4

12.2

246.8

249.1

10.6

229.2

271.6

9.1

210.1

296.6

7.7

300

295.9

262.3

11.8

276.2

284.1

10.3

255.8

309.1

8.9

233.5

337

7.5

350

355.9

308.8

12.1

332.9

335

10.6

309.1

365

9.1

283.2

398.4

7.7

140

151.9

131.9

12.1

141.7

142.9

10.5

131.1

155.4

9.1

119.9

169.4

7.7

155

167.2

143.1

12.3

156.2

155.3

10.7

144.8

169.2

9.2

132.8

184.7

7.8

170

183.3

154.7

12.5

171.4

168

10.9

159.1

183.2

9.3

146

200.1

7.9

185

196.8

174.5

12.1

184.3

188.6

10.5

171.2

204.8

9.1

157.2

222.8

7.8

200

216

194.1

11.8

202.3

209.1

10.4

188.1

226.4

9

172.4

245.8

7.7

250

244.3

210.8

12.3

228.2

228.3

10.7

211.6

248.3

9.2

193.6

270.7

7.8

275

274.4

234.1

12.4

256.7

253.8

10.8

238.5

276.4

9.3

218.9

301.5

7.9

300

307.6

267.6

12.1

287.3

289.6

10.6

266.3

314.6

9.1

243.4

342.6

7.7

350

369.8

315

12.4

346

341.4

10.8

321.6

371.4

9.3

295

405

7.9

140

158

134.6

12.4

147.5

145.6

10.8

136.6

158.2

9.3

125

172.3

7.9

155

173.7

146

12.5

162.4

158.2

10.9

150.7

172.2

9.4

138.3

187.7

8

170

190.4

157.9

12.7

178.1

171.2

11.1

165.5

186.4

9.6

152

203.4

8.1

185

204.4

178.2

12.3

191.5

192.3

10.8

178

208.6

9.3

163.5

226.7

7.9

200

224.2

198.4

12.1

210.1

213.4

10.6

195.5

230.8

9.2

179.3

250.2

7.9

250

253.9

215.1

12.5

237.3

232.7

11

220.2

252.8

9.4

201.7

275.2

8

275

285

238.8

12.7

266.8

258.6

11.1

248.1

281.3

9.6

227.9

306.5

8.1

300

319.6

273.1

12.4

298.7

295.1

10.8

277

320.3

9.3

253.4

348.4

7.9

350

383.9

321.4

12.6

359.5

347.9

11

334.3

378

9.6

307

411.6

8.1

140

164.2

137.3

12.6

153.3

148.4

11

142.1

161

9.5

130.2

175.2

8.1

155

180.4

149

12.8

168.7

161.2

11.2

156.7

175.2

9.7

143.9

190.8

8.2

170

197.7

161.1

13

185

174.4

11.3

172

189.7

9.8

158.2

206.7

8.3

185

212.2

182

12.5

198.8

196.2

11

185

212.4

9.5

170

230.6

8.1

200

232.5

202.7

12.3

218

217.8

10.8

202.9

235.2

9.4

186.3

254.7

8

250

263.7

219.6

12.8

246.6

237.2

11.2

229

257.3

9.7

209.9

279.8

8.2

275

295.9

243.7

12.9

277.1

263.6

11.3

257.8

286.2

9.8

237.1

311.5

8.3

300

331.8

278.7

12.6

310.3

300.8

11

288

326

9.5

263.6

354.2

8.1

350

398.3

328

12.9

373.2

354.5

11.3

347.3

384.7

9.8

319.1

418.4

8.3

EER³

RLC-PRC006M-EN

Performance Data

Table 9.

60 Hz extra efficiency – I-P units (continued)

Evap
Leaving
Water
Temp (°F)

48

Cond Entering Air Temp (°F)
85

95

105

115

Unit
Size

Tons

kW
Input²

EER³

Tons

kW
Input²

EER³

Tons

kW
Input²

EER³

Tons

kW
Input²

EER³

140

170.5

140.2

12.9

159.3

151.3

11.3

147.7

164

9.7

135.4

178.1

8.3

155

187.2

152

13.1

175.2

164.3

11.4

162.8

178.3

9.9

149.6

194

8.4

170

205.1

164.3

13.2

192.1

177.7

11.6

178.6

193

10

164.4

210.1

8.6

185

220

185.9

12.7

206.2

200.1

11.2

192

216.4

9.7

176.6

234.6

8.3

200

241

207.1

12.5

226.1

222.2

11

210.5

239.7

9.6

193.3

259.3

8.2

250

273.7

224.1

13

256.1

241.8

11.4

237.9

262

9.9

218.3

284.5

8.4

275

306.9

248.7

13.2

287.6

268.6

11.6

267.7

291.3

10

246.4

316.7

8.5

300

344.3

284.4

12.8

322.1

306.6

11.3

299.1

331.9

9.8

273.9

360.1

8.3

350

413

334.7

13.1

387.1

361.3

11.5

360.5

391.6

10

331.5

425.3

8.5

1. Rated in accordance with AHRI Standard 550/590 based on TOPSS version 140: sea level altitude, evaporator fouling factor of 0.0001°F-ft²h/Btu,
evaporator temperature drop of 10°F, and 2 pass evaporator configuration. Consult a Trane representative for additional performance information.
2. kW input is for compressors only.
3. EER = Energy Efficiency Ratio (Btu/watt-hour). Power inputs include compressors, condenser fans and control power.
4. Interpolation between points is permissible. Extrapolation is not permitted.

RLC-PRC006M-EN

25

Performance Data

Table 10. AHRI and Part Load Performance — 60 Hz — I-P units
Standard efficiency
Unit
Size

Full Load Full Load
Tons
EER

High efficiency
IPLV

Unit
Size

Full Load Full Load
Tons
EER

Extra efficiency
IPLV

Unit
Size

Full Load Full Load
Tons
EER

IPLV

140

138.3

9.7

13.6

140

142.0

10.2

13.8

140

147.5

10.8

14.3

155

151.9

9.8

14.0

155

157.3

10.4

14.5

155

162.4

10.9

14.9

170

166.1

9.9

14.0

170

171.3

10.5

14.5

170

178.1

11.1

14.9

185

182.0

9.8

13.9

185

188.2

10.4

14.3

185

191.4

10.8

14.8

200

198.9

9.7

13.6

200

206.1

10.3

14.1

200

210.1

10.6

14.1

225

218.6

9.7

13.9

225

223.2

10.1

14.1

250

237.3

11.0

14.8

250

240.1

9.7

13.7

250

246.3

10.2

14.0

275

266.8

11.1

15.2

275

266.2

9.8

14.6

275

275.5

10.5

14.8

300

298.7

10.8

14.8

300

298.9

9.7

14.2

300

308.9

10.3

14.4

350

359.5

11.0

15.3

350

340.0

9.6

14.3

350

346.5

10.5

15.4

400

401.3

9.7

14.7

400

415.6

10.2

14.7

450

441.8

9.6

15.0

500

483.9

9.6

15.0

1. IPLV values are rated in accordance with AHRI Standard 550/590 and based on TOPSS version 140.
2. EER and IPLV values include compressors, condenser fans, and control kW.

26

RLC-PRC006M-EN

Performance Data

Table 11. 60 Hz standard efficiency — SI units
Evap
Leaving
Water
Temp
(°C)

5

7

9

Cond Entering Air Temp (°C)
30
Unit
Size

kW
kW
Cooling Input²

35
COP³

kW
kW
Cooling Input²

40
COP³

kW
kW
Cooling Input²

45
COP³

kW
kW
Cooling Input²

COP³

140

490.83

142.2

3.17

459.54

153.4

2.77

427.19

165.8

2.4

394.14

179.5

2.06

155

538.65

154.3

3.2

504.55

166.6

2.8

469.74

180.1

2.42

434.23

195.1

2.08

170

588.58

166.8

3.23

552.36

180.1

2.83

515.09

194.9

2.45

477.12

211.2

2.11

185

645.19

185.3

3.19

605.46

199.7

2.8

565.02

215.6

2.43

523.53

233.3

2.1

200

705.31

204.6

3.16

662.41

220

2.78

617.76

237.1

2.42

572.05

256.1

2.09

225

774.58

225.6

3.15

728.16

242.6

2.78

679.99

261.5

2.42

630.42

282.5

2.09

250

849.47

247.8

3.16

799.19

266.2

2.78

746.8

286.9

2.43

692.65

309.8

2.1

275

942.99

271.1

3.19

885.33

291.9

2.8

826.26

315.1

2.44

765.79

340.8

2.1

300

1059.72

310.2

3.13

995.03

333

2.76

928.93

358.6

2.41

860.72

386.9

2.08

350

1203.53

355

3.12

1131.8

380.8

2.75

1057.26

409.8

2.41

980.61

441.9

2.08

400

1423.28

417.1

3.13

1337.49

447.6

2.76

1248.88

481.7

2.41

1157.82

519.6

2.09

450

1565.32

461.6

3.12

1472.5

495.2

2.75

1376.51

532.9

2.41

1277.36

574.7

2.08

500

1713.35

507.4

3.11

1612.79

544

2.75

1508.01

585

2.41

1399.72

630.7

2.08

140

524.24

147.6

3.27

490.83

159

2.87

456.73

171.5

2.49

421.92

185.4

2.14

155

575.22

160.3

3.3

539.35

172.6

2.89

502.44

186.3

2.51

465.17

201.5

2.16

170

627.96

173.2

3.33

589.63

186.6

2.92

550.61

201.6

2.54

510.88

218

2.19

185

687.73

192.6

3.28

645.89

207.1

2.89

603.35

223.2

2.52

559.4

241.1

2.17

200

751.72

212.9

3.25

706.01

228.4

2.86

659.25

245.7

2.5

610.73

264.9

2.16

225

825.21

234.7

3.24

775.98

251.9

2.86

725

271.2

2.5

672.61

292.5

2.16

250

905.37

257.9

3.24

851.93

276.7

2.86

796.37

297.8

2.5

738.36

321.2

2.16

275

1005.58

281.7

3.28

944.75

302.7

2.89

882.52

326.2

2.52

818.53

352.1

2.18

300

1128.99

322.8

3.22

1060.43

345.8

2.84

990.46

371.6

2.48

918.38

400.2

2.15

350

1282.64

369.7

3.2

1205.99

395.9

2.83

1126.88

425.3

2.48

1045.31

457.9

2.15

400

1514.69

433.8

3.22

1423.98

464.7

2.84

1330.45

499.2

2.49

1234.12

537.4

2.15

450

1665.88

480.4

3.2

1567.43

514.5

2.83

1465.82

552.8

2.48

1360.34

595.2

2.15

500

1824.1

528.4

3.19

1717.22

565.7

2.83

1605.76

607.5

2.47

1490.43

654

2.14

140

558.34

153.4

3.37

523.18

164.8

2.96

487.32

177.5

2.57

450.4

191.4

2.21

155

612.49

166.5

3.4

574.87

178.9

2.98

536.19

192.8

2.6

496.46

208

2.24

170

668.39

179.8

3.42

628.31

193.4

3.01

587.17

208.5

2.63

544.98

225

2.27

185

731.33

200.1

3.37

687.38

214.8

2.97

642.37

231.1

2.59

596.31

249.1

2.25

200

798.84

221.4

3.33

750.67

237.1

2.94

701.09

254.6

2.57

650.46

273.9

2.23

225

876.89

244.2

3.32

825.21

261.7

2.93

771.06

281.2

2.57

715.51

302.8

2.22

250

962.68

268.5

3.32

906.07

287.7

2.93

846.65

309.2

2.57

785.47

333.1

2.22

275

1069.92

292.8

3.37

1005.58

314

2.97

939.83

337.6

2.6

872.67

363.7

2.25

300

1199.66

335.9

3.3

1127.58

359.1

2.92

1053.39

385.1

2.56

977.1

413.9

2.22

350

1363.51

385.1

3.28

1282.64

411.7

2.9

1198.6

441.5

2.54

1108.6

472.8

2.21

400

1608.22

451.3

3.3

1512.58

482.4

2.92

1413.78

517.2

2.56

1312.17

555.8

2.22

450

1768.9

500.1

3.28

1664.83

534.7

2.9

1557.24

573.4

2.54

1439.45

612.7

2.21

500

1937.67

550.5

3.27

1824.1

588.4

2.89

1705.61

631

2.54

1567.78

668.8

2.21

1. Ratings based on TOPSS version 140: evaporator fouling factor of 0.01761m²°C/kW, evaporator temperature drop of 5°C, and 2 pass evaporator configuration. Consult Trane representative for additional performance information.
2. kW input is for compressors only.
3. COP = Coefficient of Performance. Power inputs include compressors and control power.
4. Interpolation between points is permissible. Extrapolation is not permitted.

RLC-PRC006M-EN

27

Performance Data

Table 12. 60 Hz high efficiency — SI units
Evap
Leaving
Water
Temp
(°C)

5

7

9

Cond Entering Air Temp (°C)
30
Unit
Size

kW
kW
Cooling Input²

140

501.73

155
170

35
COP³

kW
kW
Cooling Input²

40
COP³

470.79

147.1

2.9

3.37

521.77

159.4

2.96

3.4

568.54

172

2.99

178.3

3.35

624.79

191.8

2.95

197.9

3.32

684.92

212.3

2.93

741.52

235.5

818.53

258.4

kW
kW
Cooling Input²
438.8

45
COP³

kW
kW
Cooling Input²
406.1

171.9

COP³

136.7

3.29

158.9

2.52

2.17

555.88

147.8

605.1

159.4

486.97

172.3

2.58

451.1

186.6

2.22

530.92

186.1

2.6

492.59

201.7

2.24

185

664.52

200

727.81

584.01

206.9

2.58

542.17

223.8

2.23

640.26

228.5

2.57

594.2

246.5

2.22

225

786.88

219.7

3.27

250

867.75

241

3.27

2.89

694.41

253.3

2.53

645.54

273.3

2.2

2.9

767.19

278

2.54

713.75

299.9

2.21

275

972.53

260.6

3.37

914.51

280.2

2.97

854.74

302.2

2.6

793.91

326.8

2.25

300

1090.31

299.7

3.3

1025.97

321

2.92

959.87

345.1

2.56

891.66

372.1

2.22

350

1223.92

324.1

3.39

1151.14

349.1

2.98

1076.25

377.2

2.6

999.95

408.4

2.25

400

1467.93

403.6

3.29

1382.14

432.1

2.91

1293.19

464.3

2.55

1201.77

500.3

2.22

140

537.25

141.8

3.41

504.55

152.3

3.01

470.79

164.2

2.62

435.98

177.3

2.27

155

594.56

153.3

3.49

558.69

165

3.07

522.13

178

2.68

484.15

192.4

2.32

170

647.3

165.3

3.52

608.62

178

3.1

568.89

192.2

2.71

528.46

207.9

2.34

185

709.88

185.1

3.46

668.04

198.7

3.06

625.15

214

2.68

580.84

231

2.32

200

777.39

205.7

3.42

731.68

220.2

3.03

684.57

236.6

2.66

636.04

254.8

2.31

225

840.32

228.5

3.36

792.16

244.5

2.98

742.23

262.6

2.62

690.54

282.8

2.28

250

926.82

250.8

3.37

874.43

268.4

2.99

819.93

288.3

2.63

762.97

310.5

2.28

275

1039.68

270.7

3.48

978.15

290.4

3.08

915.22

312.6

2.7

850.52

337.3

2.34

300

1164.15

311.7

3.4

1096.29

333.2

3.02

1025.97

357.5

2.65

953.89

384.6

2.3

350

1306.9

336.1

3.5

1230.25

361.4

3.09

1151.49

389.7

2.7

1071.33

421.1

2.35

400

1566.03

419.7

3.38

1475.31

448.4

3.01

1381.44

480.8

2.64

1284.75

517.1

2.3

140

573.81

147.1

3.53

539

157.8

3.11

503.49

169.7

2.72

466.92

182.9

2.36

155

634.64

159

3.6

597.02

170.8

3.18

557.99

183.9

2.78

518.26

198.4

2.41

170

690.54

171.5

3.63

649.76

184.3

3.21

608.27

198.6

2.81

565.72

214.4

2.44

185

757

192.2

3.57

712.69

205.9

3.16

667.34

221.3

2.77

620.93

238.4

2.41

200

828.37

213.9

3.52

780.2

228.5

3.12

730.27

245

2.75

678.94

263.3

2.39

225

895.53

237.8

3.46

844.54

254

3.07

791.45

272.2

2.7

736.6

292.6

2.35

250

987.29

261

3.46

932.09

278.8

3.08

874.08

299.1

2.71

813.6

321.7

2.36

275

1108.6

281.2

3.59

1043.9

301.1

3.18

977.45

323.4

2.79

909.24

348.2

2.43

300

1240.45

324.2

3.5

1168.37

345.8

3.11

1094.18

370.3

2.74

1018.23

397.5

2.39

350

1393.04

348.6

3.61

1312.17

374.1

3.19

1229.55

402.6

2.8

1144.81

434.1

2.44

400

1666.94

436.4

3.48

1570.95

465.3

3.09

1471.8

498

2.73

1369.83

534.4

2.38

1. Ratings based on TOPSS version 140: evaporator fouling factor of 0.01761m²°C/kW, evaporator temperature drop of 5°C, and 2 pass evaporator configuration. Consult Trane representative for additional performance information.
2. kW input is for compressors only.
3. COP = Coefficient of Performance. Power inputs include compressors and control power.
4. Interpolation between points is permissible. Extrapolation is not permitted.

28

RLC-PRC006M-EN

Performance Data

Table 13. 60 Hz extra efficiency — SI units
Evap
Leaving
Water
Temp
(°C)

5

7

9

Cond Entering Air Temp (°C)
30

35

40

45

Unit
Size

kW
Cooling

kW
Input²

COP³

kW
Cooling

kW
Input²

COP³

kW
Cooling

kW
Input²

COP³

kW
Cooling

kW
Input²

140

519.66

131.5

3.46

488.02

141.5

3.05

455.32

152.7

2.66

421.57

165.1

2.3

155

572.05

142.8

3.51

537.95

153.8

3.1

502.44

166.2

2.7

466.22

180

2.34

170

627.25

154.4

3.56

589.98

166.4

3.14

552.01

179.9

2.75

512.63

194.9

2.38

185

674.02

173.9

3.45

634.64

186.7

3.05

594.2

201.1

2.68

552.01

217.1

2.32

200

739.41

193.3

3.39

696.87

206.9

3.01

652.92

222.3

2.65

605.46

239.5

2.3

250

835.75

210.2

3.51

785.83

226

3.1

734.14

243.9

2.71

680.35

263.8

2.34

275

939.12

233.4

3.55

883.92

251.3

3.14

827.67

271.4

2.75

768.6

293.7

2.38

300

1053.04

266.9

3.46

989.75

286.7

3.06

924.71

309.1

2.68

855.79

334

2.31

350

1266.11

314.2

3.54

1192.28

338

3.13

1116.33

364.9

2.74

1036.17

394.7

2.37

140

557.64

136.4

3.6

524.24

146.4

3.18

489.43

157.6

2.78

453.92

170.2

2.41

155

613.19

148

3.65

576.98

159

3.22

539.71

171.5

2.82

501.38

185.4

2.45

170

671.91

160

3.7

632.88

172.1

3.27

592.45

185.7

2.87

551.31

200.8

2.49

185

721.48

180.5

3.57

679.99

193.4

3.17

637.45

207.9

2.79

592.45

224.1

2.42

200

791.1

200.9

3.51

746.1

214.6

3.12

699.33

230.1

2.75

649.05

247.4

2.4

250

896.23

217.9

3.65

843.14

233.9

3.23

788.64

251.9

2.83

731.68

271.9

2.45

275

1005.58

242

3.69

947.56

259.9

3.26

887.79

280.2

2.86

825.91

302.6

2.49

300

1127.93

276.7

3.59

1061.13

296.6

3.18

992.22

319.2

2.79

919.43

344.2

2.42

350

1354.71

325.7

3.67

1277.01

349.6

3.25

1196.85

376.6

2.86

1112.46

406.6

2.48

140

597.02

141.4

3.73

561.51

151.5

3.31

524.94

162.8

2.9

487.32

175.5

2.52

155

655.73

153.4

3.78

617.41

164.5

3.35

578.38

177

2.94

537.6

191

2.56

170

718.32

165.8

3.83

676.83

178

3.4

634.29

191.6

2.98

590.69

206.8

2.6

185

770.71

187.4

3.69

727.11

200.4

3.28

681.75

214.9

2.89

634.29

231.2

2.52

200

844.19

208.8

3.62

796.73

222.5

3.23

747.5

238.1

2.85

694.06

255.5

2.49
2.56

COP³

250

958.46

226

3.78

902.56

242.1

3.35

845.25

260.1

2.94

784.77

280.2

275

1074.84

250.9

3.82

1013.31

268.9

3.39

950.37

289.2

2.98

884.98

311.8

2.59

300

1205.64

286.9

3.72

1135.32

307

3.3

1062.54

329.6

2.9

985.18

354.7

2.52

350

1446.48

337.6

3.8

1364.56

361.7

3.37

1280.18

388.8

2.97

1190.87

418.9

2.59

1. Ratings based on TOPSS version 140: evaporator fouling factor of 0.01761m²°C/kW, evaporator temperature drop of 5°C, and 2 pass evaporator configuration. Consult Trane representative for additional performance information.
2. kW input is for compressors only.
3. COP = Coefficient of Performance. Power inputs include compressors and control power.
4. Interpolation between points is permissible. Extrapolation is not permitted.

RLC-PRC006M-EN

29

Controls
LCD Touch Screen Display
The standard DynaView display provided with theTrane CH530 control panel features an LCD touch
screen that is navigated by file tabs.This is an advanced interface that allows the user to access
any important information concerning setpoints, active temperatures, modes, electrical data,
pressure, and diagnostics. It uses full text display available in 19 languages.
Display Features Include:
• LCD touch screen with LED backlighting, for scrolling access to input and output operating
information
• Single screen, folder/tab style display of all available information on individual components
(evaporator, condenser, compressor, etc.)
• Password entry/lockout system to enable or disable display
• Automatic and immediate stop capabilities for standard or immediate manual shutdown
• Fast, easy access to available chiller data in tabbed format, including:
• Modes of operation, including normal cooling as well as ice making
• Water temperatures and setpoints
• Loading and limiting status and setpoints
• Outdoor air temperature
• Start/stop differential timers
• Pump status and override
• Chilled water reset settings
• Optional external setpoints, including:
• Chilled water, demand limit, ice building
Reports, listed on a single tabbed screen for easy access, including:
• ASHRAE, containing all guideline 3 report information
• Evaporator, condenser, compressor
Evaporator, condenser, and compressor reports containing all operational information on
individual components, including:
• Water temperatures, refrigerant pressures, temperatures, and approach
• Flow switch status, EXV position, compressor starts and run time
Alarm and diagnostic information, including:
• Flashing alarms with touch screen button for immediate address of alarm condition
• Scrollable list of last ten active diagnostics
• Specific information on applicable diagnostic from list of over one hundred
• Automatic or manual resetting diagnostic types

Adaptive Controls
Adaptive Controls directly sense the control variables that govern the operation of the chiller:
evaporator pressure and condenser pressure. When any one of these variables approaches a limit
condition when damage may occur to the unit or shutdown on a safety, Adaptive Controls takes
corrective action to avoid shutdown and keep the chiller operating.This happens through
combined actions of compressor and/or fan staging. Whenever possible, the chiller is allowed to
continue making chilled water.This keeps cooling capacity available until the problem can be
solved. Overall, the safety controls help keep the building or process running and out of trouble.

30

RLC-PRC006M-EN

Controls

Stand Alone Controls
Single chillers installed in applications without a building management system is simple to install
and control: only a remote auto/stop for scheduling is required for unit operation. Signals from the
chilled water pump contactor auxiliary, or a flow switch, are wired to the chilled water flow interlock.
Signals from a time clock or some other remote device are wired to the external auto/stop input.
•

External Auto/Stop - A job site provided contact closure will turn the unit on and off.

•

Chilled Water Flow Interlock - A job site provided contact closure from a chilled water pump
contactor or a flow switch is required and will allow unit operation if a load exists.This feature
will allow the unit to run in conjunction with the pump system.

•

External Interlock - A job site supplied contact opening wired to this input will turn the unit off
and require a manual reset of the unit microcomputer.This closure is typically triggered by a
job site supplied system such as a fire alarm.

•

Chilled Water Pump Control - Unit controls provide an output to control the chilled water
pump(s). One contact closure to the chiller is all that is required to initiate the chilled water
system. Chilled water pump control by the chiller is a requirement on the Air-Cooled Series R.

•

Chilled WaterTemperature Reset -The reset can be based on return water temperature or
outdoor air temperature.

Hardwire Points
Microcomputer controls allow simple interface with other control systems, such as time clocks,
building automation systems, and ice storage systems via hardwire points.This means you have
the flexibility to meet job requirements while not having to learn a complicated control system.
Remote devices are wired from the control panel to provide auxiliary control to a building
automation system. Inputs and outputs can be communicated via a typical 4–20 mA electrical
signal, an equivalent 2–10 Vdc signal, or by utilizing contact closures. Contact closures may be
used to trigger job site supplied alarm lights or alarm bells.
This setup has the same features as a stand alone water chiller, with the possibility of having
additional optional features:
• Circuit enable/disable
• Ice making enable/status
• External chilled water setpoint, external demand limit setpoint
• Alarm indication contacts provides three single pole double throw contact closures to
indicate: compressor on/off status, compressor running at maximum capacity, failure has
occurred (ckt 1/ckt 2)

BACnet Interface
BACnet interface capabilities are available, with communication link via single twisted-pair wiring
to a factory-installed and tested communication board.
Required features:
• BACnet Interface (selectable option with chiller)
BACnet is a data communication protocol for building automation and control networks developed
by American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE).

LonTalk LCI-C Interface
LonTalk (LCI-C) communications capabilities are available, with communication link via single
twisted pair wiring to factory installed, tested communication board.
•

RLC-PRC006M-EN

Required features: LonTalk/Tracer Summit Interface (selectable option with chiller)

31

Controls

LonTalk is a communications protocol developed by the Echelon Corporation.The LonMark
association develops control profiles using the LonTalk communication protocol. LonTalk is a unit
level communications protocol.
LonTalk Communications Interface for Chillers (LCI-C) provides a generic automation system with
the LonMark chiller profile inputs/outputs. In addition to the standard points,Trane provides other
commonly used network output variables for greater interoperability with any automation system.
The complete reference list ofTrane LonTalk points is available on the LonMark web site.
Trane controls or another vendor’s system can use the predefined list of points with ease to give
the operator a complete picture of how the system is running

Tracer Summit
The chiller plant control capabilities of theTraneTracer Summit building automation system are
unequaled in the industry.Trane’s depth of experience in chillers and controls makes us a well
qualified choice for automation of chiller plants using air-cooled chillers. Our chiller plant
automation software is fully pre-engineered and tested.
Required features:
• LonTalk/Tracer Summit Interface (selectable option with chiller)
• Building Control Unit (external device required)
Energy Efficiency
• Sequences starting of chillers to optimize the overall chiller plant energy efficiency
– Individual chillers operate as base, peak, or swing based on capacity and efficiency
– Automatically rotates individual chiller operation to equalize runtime and wear
between chillers.
– Evaluates and selects the lowest energy consumption alternative from an overall
system perspective.
Easy Operation and Maintenance
• Remote monitoring and control
• Displays both current operation conditions and scheduled automated control actions
• Concise reports assist in planning for preventative maintenance and verifying performance
• Alarm notification and diagnostic messages aid in quick and accurate troubleshooting

Tracer SC
TheTracer SC system controller acts as the central coordinator for all individual equipment devices
on aTracer building automation system.TheTracer SC scans all unit controllers to update
information and coordinate building control, including building subsystems such as VAV and
chiller water systems. With this system option, the full breadth ofTrane’s HVAC and controls
experience are applied to offer solutions to many facility issues.The LAN allows building operators
to manage these varied components as one system from any personal computer with web access.
The benefits of this system are:

32

•

Improved usability with automatic data collection, enhanced data logging, easier to create
graphics, simpler navigation, pre-programmed scheduling, reporting, and alarm logs.

•

Flexible technology allows for system sizes from 30-120 unit controllers with any combination
of LonTalk or BACnet unit controllers.

•

LEED certification through site commissioning report, energy data collection measurement,
optimizing energy performance, and maintaining indoor air quality.

•

Energy savings programs include: fan pressure optimization, ventilation reset, and chiller plant
control (adds and subtracts chillers to meet cooling loads).

RLC-PRC006M-EN

Electrical Data
Table 14. Standard efficiency — all ambient options
#
# Fan
Unit
Rated
#
Power
Ckt1/ Fan Fan VFD
Size Voltage1 Conn2 Comp Ckt2 kW FLA Input
200/60/3
230/60/3

140

380/60/3
460/60/3
575/60/3

155

170

185

Cntrl
kVA3

RLA4
Ckt1/Ckt2

XLRA5
Ckt1/Ckt2

YLRA5
Ckt1/Ckt2

1

2

8

1.5

6.5

7.3

0.83

270/270

1845/1845

600/600

2

2

4/4

1.5

6.5

7.3

0.83

270/270

1845/1845

600/600

1

2

8

1.5

6.5

7.3

0.83

235/235

1556/1556

506/506

2

2

4/4

1.5

6.5

7.3

0.83

235/235

1556/1556

506/506

1

2

8

1.5

3.5

3.7

0.83

142/142

973/973

316/316

2

2

4/4

1.5

3.5

3.7

0.83

142/142

973/973

316/316

1

2

8

1.5

3

3.7

0.83

118/118

774/774

252/252

2

2

4/4

1.5

3

3.7

0.83

118/118

774/774

252/252

1

2

8

1.5

2.5

3.0

0.83

94/94

631/631

205/205

2

2

4/4

1.5

2.5

3.0

0.83

94/94

631/631

205/205

200/60/3

1

2

9

1.5

6.5

7.3

0.83

320/270

2156/1845

701/600

200/60/3

2

2

5/4

1.5

6.5

7.3

0.83

320/270

2156/1845

701/600

230/60/3

1

2

9

1.5

6.5

7.3

0.83

278/235

1756/1556

571/506

230/60/3

2

2

5/4

1.5

6.5

7.3

0.83

278/235

1756/1556

571/506

380/60/3

1

2

9

1.5

3.5

3.7

0.83

168/142

1060/973

345/316

380/60/3

2

2

5/4

1.5

3.5

3.7

0.83

168/142

1060/973

345/316

460/60/3

1

2

9

1.5

3

3.7

0.83

139/118

878/774

285/252

460/60/3

2

2

5/4

1.5

3

3.7

0.83

139/118

878/774

285/252

575/60/3

1

2

9

1.5

2.5

3.0

0.83

111/94

705/631

229/205

575/60/3

2

2

5/4

1.5

2.5

3.0

0.83

111/94

705/631

229/205

200/60/3

1

2

10

1.5

6.5

7.3

0.83

320/320

2156/2156

701/701

200/60/3

2

2

5/5

1.5

6.5

7.3

0.83

320/320

2156/2156

701/701

230/60/3

1

2

10

1.5

6.5

7.3

0.83

278/278

1756/1756

571/571

230/60/3

2

2

5/5

1.5

6.5

7.3

0.83

278/278

1756/1756

571/571

380/60/3

1

2

10

1.5

3.5

3.7

0.83

168/168

1060/1060

345/345

380/60/3

2

2

5/5

1.5

3.5

3.7

0.83

168/168

1060/1060

345/345

460/60/3

1

2

10

1.5

3

3.7

0.83

139/139

878/878

285/285

460/60/3

2

2

5/5

1.5

3

3.7

0.83

139/139

878/878

285/285

575/60/3

1

2

10

1.5

2.5

3.0

0.83

111/111

705/705

229/229

575/60/3

2

2

5/5

1.5

2.5

3.0

0.83

111/111

705/705

229/229

200/60/3

1

2

11

1.5

6.5

7.3

0.83

386/320

2525/2156

821/701

200/60/3

2

2

6/5

1.5

6.5

7.3

0.83

386/320

2525/2156

821/701

230/60/3

1

2

11

1.5

6.5

7.3

0.83

336/278

2126/1756

691/571

230/60/3

2

2

6/5

1.5

6.5

7.3

0.83

336/278

2126/1756

691/571

380/60/3

1

2

11

1.5

3.5

3.7

0.83

203/168

1306/1060

424/345

380/60/3

2

2

6/5

1.5

3.5

3.7

0.83

203/168

1306/1060

424/345

460/60/3

1

2

11

1.5

3

3.7

0.83

168/139

1065/878

346/285

460/60/3

2

2

6/5

1.5

3

3.7

0.83

168/139

1065/878

346/285

575/60/3

1

2

11

1.5

2.5

3.0

0.83

134/111

853/705

277/229

575/60/3

2

2

6/5

1.5

2.5

3.0

0.83

134/111

853/705

277/229

RLC-PRC006M-EN

MCA6
Ckt1/
Ckt2

MOP7
Ckt1/
Ckt2

665

800

368/364 600/600
586

800

324/321 500/500
350

450

194/192 300/300
293

400

162/160 250/250
234

300

129/128 200/200
734

1000

437/364 700/600
646

800

384/321 600/500
386

500

230/192 350/300
322

450

191/160 300/250
258

350

153/128 250/200
791

1000

437/433 700/700
696

800

384/381 600/600
416

500

230/228 350/350
346

450

191/189 300/300
277

350

153/152 250/250
880

1200

526/433 800/700
775

1000

463/381 700/600
463

600

277/228 450/350
385

500

231/189 350/300
308

400

184/152 300/250

33

Electrical Data

Table 14. Standard efficiency — all ambient options (continued)
#
# Fan
Unit
Rated
#
Power
Ckt1/ Fan Fan VFD
Size Voltage1 Conn2 Comp Ckt2 kW FLA Input

200

225

275

34

RLA4
Ckt1/Ckt2

XLRA5
Ckt1/Ckt2

YLRA5
Ckt1/Ckt2

200/60/3

1

2

12

1.5

6.5

7.3

0.83

386/386

2525/2525

821/821

200/60/3

2

2

6/6

1.5

6.5

7.3

0.83

386/386

2525/2525

821/821

230/60/3

1

2

12

1.5

6.5

7.3

0.83

336/336

2126/2126

691/691

230/60/3

2

2

6/6

1.5

6.5

7.3

0.83

336/336

2126/2126

691/691

380/60/3

1

2

12

1.5

3.5

3.7

0.83

203/203

1306/1306

424/424

380/60/3

2

2

6/6

1.5

3.5

3.7

0.83

203/203

1306/1306

424/424

460/60/3

1

2

12

1.5

3

3.7

0.83

168/168

1065/1065

346/346

460/60/3

2

2

6/6

1.5

3

3.7

0.83

168/168

1065/1065

346/346

575/60/3

1

2

12

1.5

2.5

3.0

0.83

134/134

853/853

277/277

575/60/3

2

2

6/6

1.5

2.5

3.0

0.83

134/134

853/853

277/277

200/60/3

1

2

13

1.5

6.5

7.3

0.83

459/386

2525/2525

821/821

200/60/3

2

2

7/6

1.5

6.5

7.3

0.83

459/386

2525/2525

821/821

230/60/3

1

2

13

1.5

6.5

7.3

0.83

399/336

2126/2126

691/691

230/60/3

2

2

7/6

1.5

6.5

7.3

0.83

399/336

2126/2126

691/691

380/60/3

1

2

13

1.5

3.5

3.7

0.83

242/203

1306/1306

424/424

380/60/3

2

2

7/6

1.5

3.5

3.7

0.83

242/203

1306/1306

424/424

460/60/3

1

2

13

1.5

3

3.7

0.83

200/168

1065/1065

346/346

460/60/3

2

2

7/6

1.5

3

3.7

0.83

200/168

1065/1065

346/346

575/60/3

1

2

13

1.5

2.5

3.0

0.83

160/134

853/853

277/277

575/60/3

2

2

7/6

1.5

2.5

3.0

0.83

160/134

853/853

277/277

200/60/3

1

2

14

1.5

6.5

7.3

0.83

459/459

2525/2525

821/821

200/60/3

250

Cntrl
kVA3

2

2

7/7

1.5

6.5

7.3

0.83

459/459

2525/2525

821/821

230/60/3

1

2

14

1.5

6.5

7.3

0.83

399/399

2126/2126

691/691

230/60/3

2

2

7/7

1.5

6.5

7.3

0.83

399/399

2126/2126

691/691

380/60/3

1

2

14

1.5

3.5

3.7

0.83

242/242

1306/1306

424/424

380/60/3

2

2

7/7

1.5

3.5

3.7

0.83

242/242

1306/1306

424/424

460/60/3

1

2

14

1.5

3

3.7

0.83

200/200

1065/1065

346/346

460/60/3

2

2

7/7

1.5

3

3.7

0.83

200/200

1065/1065

346/346

MCA6
Ckt1/
Ckt2

MOP7
Ckt1/
Ckt2

952

1200

526/522 800/800
839

1000

463/460 700/700
501

700

277/275 450/450
417

500

231/229 350/350
334

450

184/183 300/300
1050

1200

624/522

1000/
800

924

1200

549/460 800/700
554

700

329/275 500/450
460

600

274/229 450/350
369

500

219/183 350/300
1129

1200

624/620

1000/
1000

994

1200

549/545 800/800
596

800

329/327 500/500
495

600

274/272 450/450

575/60/3

1

2

14

1.5

2.5

3.0

0.83

160/160

853/853

277/277

575/60/3

2

2

7/7

1.5

2.5

3.0

0.83

160/160

853/853

277/277

397

500

200/60/3

1

200/60/3

2

2156-2156/2525

701-701/821

791/526

1756-1756/2126

571-571/691

696/463 800/700
416/277 500/450

219/218 350/350

n/a
3

10/6

1.5

6.5

7.3

1.2

320-320/386

3

10/6

1.5

6.5

7.3

1.2

278-278/336

230/60/3

1

230/60/3

2

380/60/3

1

380/60/3

2

3

10/6

1.5

3.5

3.7

1.2

168-168/203

1060-1060/1306

345-345/424

460/60/3

1

3

16

1.5

3

3.7

1.2

139-139/168

878-878/1065

285-285/346

460/60/3

2

3

10/6

1.5

3

3.7

1.2

139-139/168

878-878/1065

285-285/346

1000/
800

n/a
n/a

575/60/3

1

3

16

1.5

2.5

3.0

1.2

111-111/134

705-705/853

229-229/277

575/60/3

2

3

10/6

1.5

2.5

3.0

1.2

111-111/134

705-705/853

229-229/277

543

700

346/231 450/350
436

500

277/184 350/300

RLC-PRC006M-EN

Electrical Data

Table 14. Standard efficiency — all ambient options (continued)
#
# Fan
Unit
Rated
#
Power
Ckt1/ Fan Fan VFD
Size Voltage1 Conn2 Comp Ckt2 kW FLA Input

300

350

400

450

200/60/3

1

200/60/3

2

230/60/3

1

230/60/3

2

Cntrl
kVA3

RLA4
Ckt1/Ckt2

XLRA5
Ckt1/Ckt2

YLRA5
Ckt1/Ckt2

MCA6
Ckt1/
Ckt2

MOP7
Ckt1/
Ckt2

2525-2525/2525

821-821/821

952/526

1200/
800

2126-2126/2126

691-691/691

839/463

1000/
700

501/277 700/450

n/a
3

12/6

1.5

6.5

7.3

1.2

386-386/386

3

12/6

1.5

6.5

7.3

1.2

336-336/336

n/a

380/60/3

1

380/60/3

2

3

12/6

1.5

3.5

3.7

1.2

203-203/203

n/a
1306-1306/1306

424-424/424

460/60/3

1

3

18

1.5

3

3.7

1.2

168-168/168

1065-1065/1065

346-346/346

460/60/3

2

3

12/6

1.5

3

3.7

1.2

168-168/168

1065-1065/1065

346-346/346

607

700

417/231 500/350

575/60/3

1

3

18

1.5

2.5

3.0

1.2

134-134/134

853-853/853

277-277/277

575/60/3

2

3

12/6

1.5

2.5

3.0

1.2

134-134/134

853-853/853

277-277/277

487

600

200/60/3

1

200/60/3

2

2525-2525/2525

821-821/821

1129/
526

1200/
800

230/60/3

1

230/60/3

2

2126-2126/2126

691-691/691

994/463

1200/
700

596/277 800/450

334/184 450/300

n/a
3

14/6

1.5

6.5

7.3

1.2

459-459/386
n/a

3

14/6

1.5

6.5

7.3

1.2

399-399/336

380/60/3

1

380/60/3

2

3

14/6

1.5

3.5

3.7

1.2

242-242/203

n/a
1306-1306/1306

424-424/424

460/60/3

1

3

20

1.5

3

3.7

1.2

200-200/168

1065-1065/1065

346-346/346

460/60/3

2

3

14/6

1.5

3

3.7

1.2

200-200/168

1065-1065/1065

346-346/346

684

800

495/231 600/350

575/60/3

1

3

20

1.5

2.5

3.0

1.2

160-160/134

853-853/853

277-277/277

575/60/3

2

3

14/6

1.5

2.5

3.0

1.2

160-160/134

853-853/853

277-277/277

200/60/3

1

2525-2525/
2525-2525

821-821/
821-821

952/952

1200/
1200

2126-2126/
2126-2126

691-691/
691-6/91

839/839

1000/
1000

501/501 700/700

200/60/3

2

230/60/3

1

230/60/3

2

380/60/3

1

550

700

397/184 500/300

n/a
4

12/12

1.5

6.5

7.3

1.59

386-386/
386-386

4

12/12

1.5

6.5

7.3

1.59

336-336/
336-336

1306-1306/
1306-1306

424-424/
424-424

n/a

n/a

380/60/3

2

4

12/12

1.5

3.5

3.7

1.59

203-203/
203-203

460/60/3

1

4

24

1.5

3

3.7

1.59

168-168/
168-168

1065-1065/
1065-1065

346-346/
346-346

460/60/3

2

4

12/12

1.5

3

3.7

1.59

168-168/
168-168

1065-1065/
1065-1065

346-346/
346-346

575/60/3

1

4

24

1.5

2.5

3.0

1.59

134-134/134-134 853-853/853-853 277-277/277-277

575/60/3

2

4

12/12

1.5

2.5

3.0

1.59

134-134/134-134 853-853/853-853 277-277/277-277 334/334 450/450

200/60/3

1

200/60/3

2

230/60/3

1

230/60/3

2

380/60/3

1

793

800

417/417 500/500
637

700

n/a
4

14/12

1.5

6.5

7.3

1.59

459-459/
386-386

1.59

399-399/
336-336

2525-2525/
2525-2525

821-821/
821-821

1129/
952

1200/
1200

2126-2126/
2126-2126

691-691/
691-691

994/839

1200/
1000

1306-1306/
1306-1306

424-424/
424-424

596/501 800/700

n/a
4

14/12

1.5

6.5

7.3

n/a

380/60/3

2

4

14/12

1.5

3.5

3.7

1.59

242-242/
203-203

460/60/3

1

4

26

1.5

3

3.7

1.59

200-200/
168-168

1065-1065/
1065-1065

346-346/
346-346

460/60/3

2

4

14/12

1.5

3

3.7

1.59

200-200/
168-168

1065-1065/
1065-1065

346-346/
346-346

575/60/3

1

4

26

1.5

2.5

3.0

1.59

160-160/134-134 853-853/853-853 277-277/277-277

575/60/3

2

4

14/12

1.5

2.5

3.0

1.59

160-160/134-134 853-853/853-853 277-277/277-277 397/334 500/450

RLC-PRC006M-EN

871

1000

495/417 600/500
699

800

35

Electrical Data

Table 14. Standard efficiency — all ambient options (continued)
#
# Fan
Unit
Rated
#
Power
Ckt1/ Fan Fan VFD
Size Voltage1 Conn2 Comp Ckt2 kW FLA Input
200/60/3

500

Cntrl
kVA3

RLA4
Ckt1/Ckt2

1

200/60/3

2

230/60/3

1

230/60/3

2

380/60/3

1

XLRA5
Ckt1/Ckt2

YLRA5
Ckt1/Ckt2

MCA6
Ckt1/
Ckt2

MOP7
Ckt1/
Ckt2

2525-2525/
2525-2525

821-821/
821-821

1129/
1129

1200/
1200

2126-2126/
2126-2126

691-691/
691-691

994/994

1200/
1200

n/a
4

14/14

1.5

6.5

7.3

1.59

459-459/
459-459

4

14/14

1.5

6.5

7.3

1.59

399-399/
399-399

1306-1306/
1306-1306

424-424/424-424 596/596 800/800

n/a

n/a

380/60/3

2

4

14/14

1.5

3.5

3.7

1.59

242-242/
242-242

460/60/3

1

4

28

1.5

3

3.7

1.59

200-200/
200-200

1065-1065/
1065-1065

346-346/346-346

460/60/3

2

4

14/14

1.5

3

3.7

1.59

200-200/
200-200

1065-1065/
1065-1065

346-346/346-346 495/495 600/600

575/60/3

1

4

28

1.5

2.5

3.0

1.59

160-160/160-160 853-853/853-853 277-277/277-277

575/60/3

2

4

14/14

1.5

2.5

3.0

1.59

160-160/160-160 853-853/853-853 277-277/277-277 397/397 500/500

941

756

1000

800

Notes:
1. Voltage Utilization Range: +/- 10% of rated voltage. Rated voltage (use range): 200/60/3 (180-220), 230/60/3 (208-254), 380/60/3 (342-418), 460/60/
3 (414-506), 575/60/3 (516-633)
2. As standard, 140-250 ton units have a single point power connection. Optional dual point power connections are available. As standard, 275-500 ton
unitshave dual point power connections. Optional single point power connections are available on 460V and 575V/60 Hz units.
3. Control VA includes operational controls only. It does not include evaporator heaters. A separate 115/60/1, 20 ampcustomer provided power connection is
required to power the evaporator heaters (1640 watts).
4. RLA - Rated Load Amps
5. XLRA - Locked Rotor Amps - based on full winding (x-line) start units). YLRA for wye-delta starters is ~1/3 of LRA of x-line units.
6. MCA - Minimum Circuit Ampacity - 125 percent of largest compressor RLA plus 100 percent of all other loads.
7. Max fuse or MOPD = 225 percent of the largest compressor RLA plus 100 percent of the second compressor RLA, plus the sum of the condenser fan FLA.
(Use FLA per circuit, NOT FLA for the entire unit).
8. Local codes may take precedence.
9. All ambient means standard, low, high and wide ambient options.

36

RLC-PRC006M-EN

Electrical Data

Table 15.

High efficiency — standard and low ambient options

#
# Fan
Unit
Rated
#
Power
Ckt1/
Size Voltage1 Conn2 Comp Ckt2

140

155

170

185

Fan Fan VFD Cntrl
kW FLA Input kVA3

RLA4
Ckt1/Ckt2

XLRA5
Ckt1/Ckt2

YLRA5
Ckt1/Ckt2

MCA6
Ckt1/
Ckt2

MOP7
Ckt1/
Ckt2

200/60/3

1

2

10

1.5

6.5

7.3

0.83

259/259

1845/1845

600/600

653

800

200/60/3

2

2

5/5

1.5

6.5

7.3

0.83

259/259

1845/1845

600/600

361/357

600/600

230/60/3

1

2

10

1.5

6.5

7.3

0.83

225/225

1556/1556

506/506

576

800

230/60/3

2

2

5/5

1.5

6.5

7.3

0.83

225/225

1556/1556

506/506

318/315

500/500

380/60/3

1

2

10

1.5

3.5

3.7

0.83

136/136

973/973

316/316

344

450

380/60/3

2

2

5/5

1.5

3.5

3.7

0.83

136/136

973/973

316/316

190/188

300/300

460/60/3

1

2

10

1.5

3

3.7

0.83

113/113

774/774

252/252

287

400

460/60/3

2

2

5/5

1.5

3

3.7

0.83

113/113

774/774

252/252

159/157

250/250

575/60/3

1

2

10

1.5

2.5

3.0

0.83

90/90

631/631

205/205

230

300

575/60/3

2

2

5/5

1.5

2.5

3.0

0.83

90/90

631/631

205/205

127/126

200/200

200/60/3

1

2

11

1.5

6.5

7.3

0.83

305/259

2156/1845

701/600

717

1000

200/60/3

2

2

6/5

1.5

6.5

7.3

0.83

305/259

2156/1845

701/600

425/357

700/600

230/60/3

1

2

11

1.5

6.5

7.3

0.83

265/225

1756/1556

571/506

633

800

230/60/3

2

2

6/5

1.5

6.5

7.3

0.83

265/225

1756/1556

571/506

375/315

600/500

380/60/3

1

2

11

1.5

3.5

3.7

0.83

161/136

1060/973

345/316

378

500

380/60/3

2

2

6/5

1.5

3.5

3.7

0.83

161/136

1060/973

345/316

225/188

350/300

460/60/3

1

2

11

1.5

3

3.7

0.83

133/113

878/774

285/252

315

400

460/60/3

2

2

6/5

1.5

3

3.7

0.83

133/113

878/774

285/252

187/157

300/250

575/60/3

1

2

11

1.5

2.5

3.0

0.83

106/90

705/631

229/205

254

350

575/60/3

2

2

6/5

1.5

2.5

3.0

0.83

106/90

705/631

229/205

149/126

250/200

200/60/3

1

2

12

1.5

6.5

7.3

0.83

305/305

2156/2156

701/701

770

1000

200/60/3

2

2

6/6

1.5

6.5

7.3

0.83

305/305

2156/2156

701/701

425/421

700/700

230/60/3

1

2

12

1.5

6.5

7.3

0.83

265/265

1756/1756

571/571

679

800

230/60/3

2

2

6/6

1.5

6.5

7.3

0.83

265/265

1756/1756

571/571

375/371

600/600

380/60/3

1

2

12

1.5

3.5

3.7

0.83

161/161

1060/1060

345/345

407

500

380/60/3

2

2

6/6

1.5

3.5

3.7

0.83

161/161

1060/1060

345/345

225/222

350/350

460/60/3

1

2

12

1.5

3

3.7

0.83

133/133

878/878

285/285

338

450

460/60/3

2

2

6/6

1.5

3

3.7

0.83

133/133

878/878

285/285

187/185

300/300

575/60/3

1

2

12

1.5

2.5

3.0

0.83

106/106

705/705

229/229

271

350

575/60/3

2

2

6/6

1.5

2.5

3.0

0.83

106/106

705/705

229/229

149/148

250/250

200/60/3

1

2

13

1.5

6.5

7.3

0.83

373-305

2525/2156

821/701

861

1200

200/60/3

2

2

7/6

1.5

6.5

7.3

0.83

373/305

2525/2156

821/701

517/421

800/700

230/60/3

1

2

13

1.5

6.5

7.3

0.83

324-265

2126/1756

691/571

760

1000

230/60/3

2

2

7/6

1.5

6.5

7.3

0.83

324/265

2126/1756

691/571

455/371

700/600

380/60/3

1

2

13

1.5

3.5

3.7

0.83

196-161

1306/1060

424/345

454

600

380/60/3

2

2

7/6

1.5

3.5

3.7

0.83

196/161

1306/1060

424/345

272/222

450/350

460/60/3

1

2

13

1.5

3

3.7

0.83

162-133

1065/878

346/285

378

500

460/60/3

2

2

7/6

1.5

3

3.7

0.83

162/133

1065/878

346/285

226/185

350/300

575/60/3

1

2

13

1.5

2.5

3.0

0.83

130-106

853/705

277/229

305

400

575/60/3

2

2

7/6

1.5

2.5

3.0

0.83

130/106

853/705

277/229

182/148

300/250

RLC-PRC006M-EN

37

Electrical Data

Table 15.

High efficiency — standard and low ambient options (continued)

#
# Fan
Unit
Rated
#
Power
Ckt1/
Size Voltage1 Conn2 Comp Ckt2

200

225

250

275

38

Fan Fan VFD Cntrl
kW FLA Input kVA3

RLA4
Ckt1/Ckt2

XLRA5
Ckt1/Ckt2

YLRA5
Ckt1/Ckt2

MCA6
Ckt1/
Ckt2

MOP7
Ckt1/
Ckt2

200/60/3

1

2

14

1.5

6.5

7.3

0.83

373/373

2525/2525

821/821

936

1200

200/60/3

2

2

7/7

1.5

6.5

7.3

0.83

373/373

2525/2525

821/821

517/513

800/800

230/60/3

1

2

14

1.5

6.5

7.3

0.83

324/324

2126/2126

691/691

825

1000

230/60/3

2

2

7/7

1.5

6.5

7.3

0.83

324/324

2126/2126

691/691

455/451

700/700

380/60/3

1

2

14

1.5

3.5

3.7

0.83

196/196

1306/1306

424/424

493

600

380/60/3

2

2

7/7

1.5

3.5

3.7

0.83

196/196

1306/1306

424/424

272/270

450/450

460/60/3

1

2

14

1.5

3

3.7

0.83

162/162

1065/1065

346/346

410

500

460/60/3

2

2

7/7

1.5

3

3.7

0.83

162/162

1065/1065

346/346

226/224

350/350

575/60/3

1

2

14

1.5

2.5

3.0

0.83

130/130

853/853

277/277

331

450

575/60/3

2

2

7/7

1.5

2.5

3.0

0.83

130/130

853/853

277/277

182/181

300/300

200/60/3

1

2

14

1.5

6.5

7.3

0.83

447/373

2525/2525

821/821

1028

1200

200/60/3

2

2

8/6

1.5

6.5

7.3

0.83

447/373

2525/2525

821/821

615/506

1000/800

230/60/3

1

2

14

1.5

6.5

7.3

0.83

388/324

2126/2126

691/691

904

1200

230/60/3

2

2

8/6

1.5

6.5

7.3

0.83

388/324

2126/2126

691/691

541/445

800/700

380/60/3

1

2

14

1.5

3.5

3.7

0.83

235/196

1306/1306

424/424

541

700

380/60/3

2

2

8/6

1.5

3.5

3.7

0.83

235/196

1306/1306

424/424

324/266

500/450

460/60/3

1

2

14

1.5

3

3.7

0.83

194/162

1065/1065

346/346

449

600

460/60/3

2

2

8/6

1.5

3

3.7

0.83

194/162

1065/1065

346/346

268/221

450/350

575/60/3

1

2

14

1.5

2.5

3.0

0.83

155/130

853/853

277/277

361

500

575/60/3

2

2

8/6

1.5

2.5

3.0

0.83

155/130

853/853

277/277

215/178

350/300

200/60/3

1

2

16

1.5

6.5

7.3

0.83

447/447

2525/2525

821/821

1115

1200

200/60/3

2

2

8/8

1.5

6.5

7.3

0.83

447/447

2525/2525

821/821

616/612

1000/1000

230/60/3

1

2

16

1.5

6.5

7.3

0.83

388/388

2126/2126

691/691

982

1200

230/60/3

2

2

8/8

1.5

6.5

7.3

0.83

388/388

2126/2126

691/691

541/538

800/800

380/60/3

1

2

16

1.5

3.5

3.7

0.83

235/235

1306/1306

424/424

587

800

380/60/3

2

2

8/8

1.5

3.5

3.7

0.83

235/235

1306/1306

424/424

324/322

500/500

460/60/3

1

2

16

1.5

3

3.7

0.83

194/194

1065/1065

346/346

488

600

460/60/3

2

2

8/8

1.5

3

3.7

0.83

194/194

1065/1065

346/346

269/267

450/450

575/60/3

1

2

7/4

1.5

2.5

3.0

0.83

155/155

853/853

277/277

391

500

575/60/3

2

2

8/8

1.5

2.5

3.0

0.83

155/155

853/853

277/277

216/214

350/350

200/60/3

1

200/60/3

2

3

12/6

1.5

6.5

7.3

1.2

305-305/373

2156-2156/2525

701-701/821

770/510

1000/800

230/60/3

1

230/60/3

2

1756-1756/2126

571-571/691

679/448

800/700

380/60/3

1

380/60/3

2

3

12/6

1.5

3.5

3.7

1.2

161-161/196

1060-1060/1306

345-345/424

407/268

500/450

460/60/3

1

3

18

1.5

3

3.7

1.2

133-133/162

878-878/1065

285-285/346

529

600

460/60/3

2

3

12/6

1.5

3

3.7

1.2

133-133/162

878-878/1065

285-285/346

338/223

450/350

575/60/3

1

3

18

1.5

2.5

3.0

1.2

106-106/130

705-705/853

229-229/277

426

500

575/60/3

2

3

12/6

1.5

2.5

3.0

1.2

106-106/130

705-705/853

229-229/277

271/179

350/300

n/a
n/a
3

12/6

1.5

6.5

7.3

1.2

265-265/324
n/a

RLC-PRC006M-EN

Electrical Data

Table 15.

High efficiency — standard and low ambient options (continued)

#
# Fan
Unit
Rated
#
Power
Ckt1/
Size Voltage1 Conn2 Comp Ckt2

300

350

400

Fan Fan VFD Cntrl
kW FLA Input kVA3

RLA4
Ckt1/Ckt2

XLRA5
Ckt1/Ckt2

YLRA5
Ckt1/Ckt2

MCA6
Ckt1/
Ckt2

MOP7
Ckt1/
Ckt2

2525-2525/2525

821-821/821

936/510

1200/800

2126-2126/2126

691-691/691

825/448

1000/700
600/450

200/60/3

1

200/60/3

2

230/60/3

1

230/60/3

2

380/60/3

1

380/60/3

2

3

14/6

1.5

3.5

3.7

1.2

196-196/196

1306-1306/1306

424-424/424

493/268

460/60/3

1

3

20

1.5

3

3.7

1.2

162-162/162

1065-1065/1065

346-346/346

592

700

460/60/3

2

3

14/6

1.5

3

3.7

1.2

162-162/162

1065-1065/1065

346-346/346

410/223

500/350

575/60/3

1

3

20

1.5

2.5

3.0

1.2

130-130/130

853-853/853

277-277/277

477

600

575/60/3

2

3

14/6

1.5

2.5

3.0

1.2

130-130/130

853-853/853

277-277/277

330/179

450/300

200/60/3

1
1.2

305-305/
305-305

2156-2156/
2156-2156

701-701/
701-701

770/770

1000/1000

1.2

265-265/
265-265

1756-1756/
1756-1756

571-571/
571-571

679/679

800/800

200/60/3

2

230/60/3

1

n/a
3

14/6

1.5

6.5

7.3

1.2

373-373/373
n/a

3

14/6

1.5

6.5

7.3

1.2

324-324/324
n/a

n/a
4

12/12

1.5

6.5

7.3

n/a

230/60/3

2

380/60/3

1

380/60/3

2

4

12/12

1.5

3.5

3.7

1.2

161-161/
161-161

1060-1060/
1060-1060

345-345/
345-345

407/407

500/500

460/60/3

1

4

24

1.5

3

3.7

1.2

133-133/
133-133

878-878/878-878

285-285/
285-285

644

700

460/60/3

2

4

12/12

1.5

3

3.7

1.2

133-133/
133-133

878-878/878-878

285-285/
285-285

338/338

450/450

575/60/3

1

4

24

1.5

2.5

3.0

1.2

106-106/
106-106

705-705/705-705

229-229/
229-229

515

600

1.2

106-106/
106-106

705-705/705-705

229-229/
229-229

271/271

350/350

1.59

373-373/
373-373

2525-2525/
2525-2525

821-821/
821-821

936/936

1200/1200

1.59

324-324/
324-324

2126-2126/
2126-2126

691-691/
691-691

825/825

1000/1000

575/60/3

2

200/60/3

1

200/60/3

2

230/60/3

1

4

12/12

1.5

6.5

7.3

n/a

4

12/12

1.5

2.5

3.0

n/a
4

14/14

1.5

6.5

7.3

n/a

230/60/3

2

4

14/14

1.5

6.5

7.3

380/60/3

1

380/60/3

2

4

14/14

1.5

3.5

3.7

1.59

196-196/
196-196

1306-1306/
1306-1306

424-424/
424-424

493/493

600/600

460/60/3

1

4

28

1.5

3

3.7

1.59

162-162/
162-162

1065-1065/
1065-1065

346-346/
346-346

779

800

460/60/3

2

4

14/14

1.5

3

3.7

1.59

162-162/
162-162

1065-1065/
1065-1065

346-346/
346-346

410/410

500/500

853-853/
853-853

277-277/
277-277

627

700

853-853/
853-853

277-277/
277-277

330/330

450/450

n/a

575/60/3

1

4

28

1.5

2.5

3.0

1.59

130-130/
130-130

575/60/3

2

4

14/14

1.5

2.5

3.0

1.59

130-130/
130-130

Notes:
1. Voltage Utilization Range: +/- 10% of rated voltage. Rated voltage (use range): 200/60/3 (180-220), 230/60/3 (208-254), 380/60/3 (342-418), 460/60/3
(414-506), 575/60/3 (516-633)
2. As standard, 140-250 ton units have a single point power connection. Optional dual point power connections are available. As standard, 275-500 ton units
have dual point power connections. Optional single point power connections are available on 460V and 575V/60 Hzunits.
3. Control VA includes operational controls only. It does not include evaporator heaters. A separate 115/60/1, 20 amp customer provided power connection is
required to power the evaporator heaters (1640 watts).
4. RLA - Rated Load Amps
5. XLRA - Locked Rotor Amps - based on full winding (x-line) start units). YLRA for wye-delta starters is ~1/3 of LRA of x-line units.
6. MCA - Minimum Circuit Ampacity - 125 percent of largest compressor RLA plus 100 percent of all other loads.
7. Max fuse or MOPD = 225 percent of the largest compressor RLA plus 100 percent of the second compressor RLA, plus the sum of the condenser fan FLA.
(Use FLA per circuit, NOT FLA for the entire unit).
8. Local codes may take precedence.
9. All ambient means standard, low, high and wide ambient options.

RLC-PRC006M-EN

39

Electrical Data

Table 16. High efficiency — high and wide ambient options
#
# Fan
Unit
Rated
#
Power
Ckt1/ Fan Fan VFD
Size Voltage1 Conn2 Comp Ckt2 kW FLA Input

140

155

170

185

40

RLA4
Cntrl
kVA3 Ckt1/Ckt2

XLRA5
Ckt1/Ckt2

YLRA5
Ckt1/Ckt2

MCA6
Ckt1/
Ckt2

MOP7
Ckt1/
Ckt2

200/60/3

1

2

10

1.5

6.5

7.3

0.83

270/270

1845/1845

600/600

678

800

200/60/3

2

2

5/5

1.5

6.5

7.3

0.83

270/270

1845/1845

600/600

375/371

600/600

230/60/3

1

2

10

1.5

6.5

7.3

0.83

235/235

1556/1556

506/506

599

800

230/60/3

2

2

5/5

1.5

6.5

7.3

0.83

235/235

1556/1556

506/506

331/327

500/500

380/60/3

1

2

10

1.5

3.5

3.7

0.83

142/142

973/973

316/316

357

450

380/60/3

2

2

5/5

1.5

3.5

3.7

0.83

142/142

973/973

316/316

197/195

300/300

460/60/3

1

2

10

1.5

3

3.7

0.83

118/118

774/774

252/252

299

400

460/60/3

2

2

5/5

1.5

3

3.7

0.83

118/118

774/774

252/252

165/163

250/250

575/60/3

1

2

10

1.5

2.5

3.0

0.83

94/94

631/631

205/205

239

300

575/60/3

2

2

5/5

1.5

2.5

3.0

0.83

94/94

631/631

205/205

132/131

225/225

200/60/3

1

2

11

1.5

6.5

7.3

0.83

320/270

2156/1845

701/600

747

1000

200/60/3

2

2

6/5

1.5

6.5

7.3

0.83

320/270

2156/1845

701/600

444/371

700/600

230/60/3

1

2

11

1.5

6.5

7.3

0.83

278/235

1756/1556

571/506

659

800

230/60/3

2

2

6/5

1.5

6.5

7.3

0.83

278/235

1756/1556

571/506

391/327

600/500

380/60/3

1

2

11

1.5

3.5

3.7

0.83

168/142

1060/973

345/316

393

500

380/60/3

2

2

6/5

1.5

3.5

3.7

0.83

168/142

1060/973

345/316

233/195

400/300

460/60/3

1

2

11

1.5

3

3.7

0.83

139/118

878/774

285/252

328

450

460/60/3

2

2

6/5

1.5

3

3.7

0.83

139/118

878/774

285/252

194/163

300/250

575/60/3

1

2

11

1.5

2.5

3.0

0.83

111/94

705/631

229/205

263

350

575/60/3

2

2

6/5

1.5

2.5

3.0

0.83

111/94

705/631

229/205

156/131

250/200

200/60/3

1

2

12

1.5

6.5

7.3

0.83

320/320

2156/2156

701/701

804

1000

200/60/3

2

2

6/6

1.5

6.5

7.3

0.83

320/320

2156/2156

701/701

444/440

700/700

230/60/3

1

2

12

1.5

6.5

7.3

0.83

278/278

1756/1756

571/571

709

800

230/60/3

2

2

6/6

1.5

6.5

7.3

0.83

278/278

1756/1756

571/571

391/387

600/600

380/60/3

1

2

12

1.5

3.5

3.7

0.83

168/168

1060/1060

345/345

423

500

380/60/3

2

2

6/6

1.5

3.5

3.7

0.83

168/168

1060/1060

345/345

233/231

400/350

460/60/3

1

2

12

1.5

3

3.7

0.83

139/139

878/878

285/285

352

450

460/60/3

2

2

6/6

1.5

3

3.7

0.83

139/139

878/878

285/285

194/192

300/300

575/60/3

1

2

12

1.5

2.5

3.0

0.83

111/111

705/705

229/229

282

350

575/60/3

2

2

6/6

1.5

2.5

3.0

0.83

111/111

705/705

229/229

156/154

250/250

200/60/3

1

2

13

1.5

6.5

7.3

0.83

386/320

2525/2156

821/701

893

1200

200/60/3

2

2

7/6

1.5

6.5

7.3

0.83

386/320

2525/2156

821/701

533/440

800/700

230/60/3

1

2

13

1.5

6.5

7.3

0.83

336/278

2126/1756

691/571

788

1000

230/60/3

2

2

7/6

1.5

6.5

7.3

0.83

336/278

2126/1756

691/571

470/387

800/600

380/60/3

1

2

13

1.5

3.5

3.7

0.83

203/168

1306/1060

424/345

470

600

380/60/3

2

2

7/6

1.5

3.5

3.7

0.83

203/168

1306/1060

424/345

281/231

450/350

460/60/3

1

2

13

1.5

3

3.7

0.83

168/139

1065/878

346/285

391

500

460/60/3

2

2

7/6

1.5

3

3.7

0.83

168/139

1065/878

346/285

234/192

400/300

575/60/3

1

2

13

1.5

2.5

3.0

0.83

134/111

853/705

277/229

313

450

575/60/3

2

2

7/6

1.5

2.5

3.0

0.83

134/111

853/705

277/229

187/154

300/250

RLC-PRC006M-EN

Electrical Data

Table 16. High efficiency — high and wide ambient options (continued)
#
# Fan
Unit
Rated
#
Power
Ckt1/ Fan Fan VFD
Size Voltage1 Conn2 Comp Ckt2 kW FLA Input

200

225

250

275

RLA4
Cntrl
kVA3 Ckt1/Ckt2

XLRA5
Ckt1/Ckt2

YLRA5
Ckt1/Ckt2

MCA6
Ckt1/
Ckt2

MOP7
Ckt1/
Ckt2

200/60/3

1

2

14

1.5

6.5

7.3

0.83

386/386

2525/2525

821/821

965

1200

200/60/3

2

2

7/7

1.5

6.5

7.3

0.83

386/386

2525/2525

821/821

533/529

800/800

230/60/3

1

2

14

1.5

6.5

7.3

0.83

336/336

2126/2126

691/691

852

1000

230/60/3

2

2

7/7

1.5

6.5

7.3

0.83

336/336

2126/2126

691/691

470/466

800/800

380/60/3

1

2

14

1.5

3.5

3.7

0.83

203/203

1306/1306

424/424

508

700

380/60/3

2

2

7/7

1.5

3.5

3.7

0.83

203/203

1306/1306

424/424

281/278

450/450

460/60/3

1

2

14

1.5

3

3.7

0.83

168/168

1065/1065

346/346

423

500

460/60/3

2

2

7/7

1.5

3

3.7

0.83

168/168

1065/1065

346/346

234/232

400/350

575/60/3

1

2

14

1.5

2.5

3.0

0.83

134/134

853/853

277/277

339

450

575/60/3

2

2

7/7

1.5

2.5

3.0

0.83

134/134

853/853

277/277

187/186

300/300

200/60/3

1

2

14

1.5

6.5

7.3

0.83

459/386

2525/2525

821/821

1056

1200

200/60/3

2

2

8/6

1.5

6.5

7.3

0.83

459/386

2525/2525

821/821

631/522

1000/800

230/60/3

1

2

14

1.5

6.5

7.3

0.83

399/336

2126/2126

691/691

931

1200

230/60/3

2

2

8/6

1.5

6.5

7.3

0.83

399/336

2126/2126

691/691

555/460

800/700

380/60/3

1

2

14

1.5

3.5

3.7

0.83

242/203

1306/1306

424/424

557

700

380/60/3

2

2

8/6

1.5

3.5

3.7

0.83

242/203

1306/1306

424/424

333/275

500/450

460/60/3

1

2

14

1.5

3

3.7

0.83

200/168

1065/1065

346/346

463

600

460/60/3

2

2

8/6

1.5

3

3.7

0.83

200/168

1065/1065

346/346

277/229

450/350

575/60/3

1

2

14

1.5

2.5

3.0

0.83

160/134

853/853

277/277

371

500

575/60/3

2

2

8/6

1.5

2.5

3.0

0.83

160/134

853/853

277/277

222/183

350/300

200/60/3

1

2

16

1.5

6.5

7.3

0.83

459/459

2525/2525

821/821

1142

1600

200/60/3

2

2

8/8

1.5

6.5

7.3

0.83

459/459

2525/2525

821/821

631/627

1000/1000

230/60/3

1

2

16

1.5

6.5

7.3

0.83

399/399

2126/2126

691/691

1007

1200

230/60/3

2

2

8/8

1.5

6.5

7.3

0.83

399/399

2126/2126

691/691

555/552

800/800

380/60/3

1

2

16

1.5

3.5

3.7

0.83

242/242

1306/1306

424/424

603

800

380/60/3

2

2

8/8

1.5

3.5

3.7

0.83

242/242

1306/1306

424/424

333/331

500/500

460/60/3

1

2

16

1.5

3

3.7

0.83

200/200

1065/1065

346/346

501

700

460/60/3

2

2

8/8

1.5

3

3.7

0.83

200/200

1065/1065

346/346

277/275

450/450

575/60/3

1

2

16

1.5

2.5

3.0

0.83

160/160

853/853

277/277

402

500

575/60/3

2

2

8/8

1.5

2.5

3.0

0.83

160/160

853/853

277/277

222/221

350/350

200/60/3

1

200/60/3

2

3

12/6

1.5

6.5

7.3

1.2

320-320/386

2156-2156/2525

701-701/821

804/526

1000/800

230/60/3

1

230/60/3

2

1756-1756/2126

571-571/691

709/463

800/700

380/60/3

1

380/60/3

2

3

12/6

1.5

3.5

3.7

1.2

168-168/203

1060-1060/1306

345-345/424

423/277

500/450

460/60/3

1

3

18

1.5

3

3.7

1.2

139-139/168

878-878/1065

285-285/346

549

700

460/60/3

2

3

12/6

1.5

3

3.7

1.2

139-139/168

878-878/1065

285-285/346

352/231

450/350

575/60/3

1

3

18

1.5

2.5

3.0

1.2

111-111/134

705-705/853

229-229/277

441

500

575/60/3

2

3

12/6

1.5

2.5

3.0

1.2

111-111/134

705-705/853

229-229/277

282/184

350/300

RLC-PRC006M-EN

n/a
n/a
3

12/6

1.5

6.5

7.3

1.2

278-278/336
n/a

41

Electrical Data

Table 16. High efficiency — high and wide ambient options (continued)
#
# Fan
Unit
Rated
#
Power
Ckt1/ Fan Fan VFD
Size Voltage1 Conn2 Comp Ckt2 kW FLA Input

300

350

400

RLA4
Cntrl
kVA3 Ckt1/Ckt2

XLRA5
Ckt1/Ckt2

YLRA5
Ckt1/Ckt2

MCA6
Ckt1/
Ckt2

MOP7
Ckt1/
Ckt2

2525-2525/2525

821-821/821

965/526

1200/800

2126-2126/2126

691-691/691

852/463

1000/700
700/450

200/60/3

1

200/60/3

2

230/60/3

1

230/60/3

2

380/60/3

1

380/60/3

2

3

14/6

1.5

3.5

3.7

1.2

203-203/203

1306-1306/1306

424-424/424

508/277

460/60/3

1

3

20

1.5

3

3.7

1.2

168-168/168

1065-1065/1065

346-346/346

612

700

460/60/3

2

3

14/6

1.5

3

3.7

1.2

168-168/168

1065-1065/1065

346-346/346

423/231

500/350

575/60/3

1

3

20

1.5

2.5

3.0

1.2

134-134/134

853-853/853

277-277/277

490

600

575/60/3

2

3

14/6

1.5

2.5

3.0

1.2

134-134/134

853-853/853

277-277/277

339/184

450/300

200/60/3

1
1.2

320-320/
320-320

2156-2156/
2156-2156

701-701/
701-701

804/804

1000/1000

1.2

278-278/
278-278

1756-1756/
1756-1756

571-571/
571-571

709/709

800/800

200/60/3

2

230/60/3

1

n/a
3

14/6

1.5

6.5

7.3

1.2

386-386/386
n/a

3

14/6

1.5

6.5

7.3

1.2

336-336/336
n/a

n/a
4

12/12

1.5

6.5

7.3

n/a

230/60/3

2

380/60/3

1

380/60/3

2

4

12/12

1.5

3.5

3.7

1.2

168-168/
168-168

1060-1060/
1060-1060

345-345/
345-345

423/423

500/500

460/60/3

1

4

24

1.5

3

3.7

1.2

139-139/
139-139

878-878/
878-878

285-285/
285-285

669

800

460/60/3

2

4

12/12

1.5

3

3.7

1.2

139-139/
139-139

878-878/
878-878

285-285/
285-285

352/352

450/450

575/60/3

1

4

24

1.5

2.5

3.0

1.2

111-111/
111-111

705-705/
705-705

229-229/
229-229

537

600

1.2

111-111/
111-111

705-705/
705-705

229-229/
229-229

282/282

350/350

1.59

386-386/
386-386

2525-2525/
2525-2525

821-821/
821-821

965/965

1200/1200

1.59

336-336/
336-336

2126-2126/
2126-2126

691-691/
691-691

852/852

1000/1000

575/60/3

2

200/60/3

1

200/60/3

2

230/60/3

1

4

12/12

1.5

6.5

7.3

n/a

4

12/12

1.5

2.5

3.0

n/a
4

14/14

1.5

6.5

7.3

n/a

230/60/3

2

4

14/14

1.5

6.5

7.3

200/60/3

1

380/60/3

2

4

14/14

1.5

3.5

3.7

1.59

203-203/
203-203

1306-1306/
1306-1306

424-424/
424-424

508/508

700/700

460/60/3

1

4

28

1.5

3

3.7

1.59

168-168/
168-168

1065-1065/
1065-1065

346-346/
346-346

804

1000

460/60/3

2

4

14/14

1.5

3

3.7

1.59

168-168/
168-168

1065-1065/
1065-1065

346-346/
346-346

423/423

500/500

853-853/
853-853

277-277/
277-277

644

700

853-853/
853-853

277-277/
277-277

339/339

450/450

n/a

575/60/3

1

4

28

1.5

2.5

3.0

1.59

134-134/
134-134

575/60/3

2

4

14/14

1.5

2.5

3.0

1.59

134-134/
134-134

Notes:
1. Voltage Utilization Range: +/- 10% of rated voltage. Rated voltage (use range): 200/60/3 (180-220), 230/60/3 (208-254), 380/60/3 (342-418), 460/60/
3 (414-506), 575/60/3 (516-633)
2. As standard, 140-250 ton units have a single point power connection. Optional dual point power connections are available. As standard, 275-500 ton
unitshave dual point power connections. Optional single point power connections are available on 460V and 575V/60 Hz units.
3. Control VA includes operational controls only. It does not include evaporator heaters. A separate 115/60/1, 20 amp customer provided power connection
is required to power the evaporator heaters (1640 watts).
4. RLA - Rated Load Amps
5. XLRA - Locked Rotor Amps - based on full winding (x-line) start units). YLRA for wye-delta starters is ~1/3 of LRA of x-line units.
6. MCA - Minimum Circuit Ampacity - 125 percent of largest compressor RLA plus 100 percent of all other loads.
7. Max fuse or MOPD = 225 percent of the largest compressor RLA plus 100 percent of the second compressor RLA, plus the sum of the condenser fan FLA.
(Use FLA per circuit, NOT FLA for the entire unit).
8. Local codes may take precedence.
9. All ambient means standard, low, high and wide ambient options.

42

RLC-PRC006M-EN

Electrical Data

Table 17. Extra efficiency — high and wide ambient
Unit
Size

140

155

170

185

#
# Fan
Rated
#
Power
Ckt1/ Fan Fan VFD Cntrl
Voltage1 Conn2 Comp Ckt2 kW FLA Input kVA3

RLA4
Ckt1/Ckt2

XLRA5
Ckt1/Ckt2

YLRA5
Ckt1/Ckt2

MCA6
Ckt1/
Ckt2

MOP7
Ckt1/
Ckt2

200/60/3

1

2

12

1.5

6.5

7.3

0.83

270/270

1845/1845

600/600

691

800

200/60/3

2

2

6/6

1.5

6.5

7.3

0.83

270/270

1845/1845

600/600

381/377

600/600

230/60/3

1

2

12

1.5

6.5

7.3

0.83

235/235

1556/1556

506/506

612

800

230/60/3

2

2

6/6

1.5

6.5

7.3

0.83

235/235

1556/1556

506/506

337/334

500/500

380/60/3

1

2

12

1.5

3.5

3.7

0.83

142/142

973/973

316/316

364

500

380/60/3

2

2

6/6

1.5

3.5

3.7

0.83

142/142

973/973

316/316

201/199

300/300

460/60/3

1

2

12

1.5

3

3.7

0.83

118/118

774/774

252/252

305

400

460/60/3

2

2

6/6

1.5

3

3.7

0.83

118/118

774/774

252/252

168/166

250/250

575/60/3

1

2

12

1.5

2.5

3.0

0.83

94/94

631/631

205/205

244

300

575/60/3

2

2

6/6

1.5

2.5

3.0

0.83

94/94

631/631

205/205

134/133

225/225

200/60/3

1

2

13

1.5

6.5

7.3

0.83

320/270

2156/1845

701/600

760

1000

200/60/3

2

2

7/6

1.5

6.5

7.3

0.83

320/270

2156/1845

701/600

450/377

700/600

230/60/3

1

2

13

1.5

6.5

7.3

0.83

278/235

1756/1556

571/506

672

800

230/60/3

2

2

7/6

1.5

6.5

7.3

0.83

278/235

1756/1556

571/506

397/334

600/500

380/60/3

1

2

13

1.5

3.5

3.7

0.83

168/142

1060/973

345/316

400

500

380/60/3

2

2

7/6

1.5

3.5

3.7

0.83

168/142

1060/973

345/316

237/199

400/300

460/60/3

1

2

13

1.5

3

3.7

0.83

139/118

878/774

285/252

334

450

460/60/3

2

2

7/6

1.5

3

3.7

0.83

139/118

878/774

285/252

197/166

300/250

575/60/3

1

2

13

1.5

2.5

3.0

0.83

111/94

705/631

229/205

268

350

575/60/3

2

2

7/6

1.5

2.5

3.0

0.83

111/94

705/631

229/205

158/133

250/225

200/60/3

1

2

14

1.5

6.5

7.3

0.83

320/320

2156/2156

701/701

817

1000

200/60/3

2

2

7/7

1.5

6.5

7.3

0.83

320/320

2156/2156

701/701

450/446

700/700

230/60/3

1

2

14

1.5

6.5

7.3

0.83

278/278

1756/1756

571/571

722

800

230/60/3

2

2

7/7

1.5

6.5

7.3

0.83

278/278

1756/1756

571/571

397/394

600/600

380/60/3

1

2

14

1.5

3.5

3.7

0.83

168/168

1060/1060

345/345

430

500

380/60/3

2

2

7/7

1.5

3.5

3.7

0.83

168/168

1060/1060

345/345

237/235

400/400

460/60/3

1

2

14

1.5

3

3.7

0.83

139/139

878/878

285/285

358

450

460/60/3

2

2

7/7

1.5

3

3.7

0.83

139/139

878/878

285/285

197/195

300/300

575/60/3

1

2

14

1.5

2.5

3.0

0.83

111/111

705/705

229/229

287

350

575/60/3

2

2

7/7

1.5

2.5

3.0

0.83

111/111

705/705

229/229

158/157

250/250

200/60/3

1

2

14

1.5

6.5

7.3

0.83

386/320

2525/2156

821/701

899

1200

200/60/3

2

2

8/6

1.5

6.5

7.3

0.83

386/320

2525/2156

821/701

539/440

800/700

230/60/3

1

2

14

1.5

6.5

7.3

0.83

336/278

2126/1756

691/571

794

1000

230/60/3

2

2

8/6

1.5

6.5

7.3

0.83

336/278

2126/1756

691/571

476/387

800/600

380/60/3

1

2

14

1.5

3.5

3.7

0.83

203/168

1306/1060

424/345

473

600

380/60/3

2

2

8/6

1.5

3.5

3.7

0.83

203/168

1306/1060

424/345

284/231

450/350

460/60/3

1

2

14

1.5

3

3.7

0.83

168/139

1065/878

346/285

394

500

460/60/3

2

2

8/6

1.5

3

3.7

0.83

168/139

1065/878

346/285

237/192

400/300

575/60/3

1

2

14

1.5

2.5

3.0

0.83

134/111

853/705

277/229

316

450

575/60/3

2

2

8/6

1.5

2.5

3.0

0.83

134/111

853/705

277/229

189/154

300/400

RLC-PRC006M-EN

43

Electrical Data

Table 17. Extra efficiency — high and wide ambient
Unit
Size

200

250

275

300

44

#
# Fan
Rated
#
Power
Ckt1/ Fan Fan VFD Cntrl
Voltage1 Conn2 Comp Ckt2 kW FLA Input kVA3

RLA4
Ckt1/Ckt2

XLRA5
Ckt1/Ckt2

YLRA5
Ckt1/Ckt2

MCA6
Ckt1/
Ckt2

MOP7
Ckt1/
Ckt2

200/60/3

1

2

16

1.5

6.5

7.3

0.83

386/386

2525/2525

821/821

978

1200

200/60/3

2

2

8/8

1.5

6.5

7.3

0.83

386/386

2525/2525

821/821

539/535

800/800

230/60/3

1

2

16

1.5

6.5

7.3

0.83

336/336

2126/2126

691/691

865

1200

230/60/3

2

2

8/8

1.5

6.5

7.3

0.83

336/336

2126/2126

691/691

476/473

800/800

380/60/3

1

2

16

1.5

3.5

3.7

0.83

203/203

1306/1306

424/424

515

700

380/60/3

2

2

8/8

1.5

3.5

3.7

0.83

203/203

1306/1306

424/424

284/282

450/450

460/60/3

1

2

16

1.5

3

3.7

0.83

168/168

1065/1065

346/346

429

500

460/60/3

2

2

8/8

1.5

3

3.7

0.83

168/168

1065/1065

346/346

237/235

400/400

575/60/3

1

2

16

1.5

2.5

3.0

0.83

134/134

853/853

277/277

344

450

575/60/3

2

2

8/8

1.5

2.5

3.0

0.83

134/134

853/853

277/277

189/188

300/300

200/60/3

1

200/60/3

2

3

12/6

1.5

6.5

7.3

1.2

270-270/386

1845-1845/2525

600-600/821

691/526

800/800

230/60/3

1

230/60/3

2

506-506/691

612/463

700/700

380/60/3

1

380/60/3

2

3

12/6

1.5

3.5

3.7

1.2

142-142/203

973-973/1306

316-316/424

364/277

450/450

460/60/3

1

3

18

1.5

3

3.7

1.2

118-118/168

774-774/1065

252-252/346

507

600

460/60/3

2

3

12/6

1.5

3

3.7

1.2

118-118/168

774-774/1065

252-252/346

305/231

350/350

575/60/3

1

3

18

1.5

2.5

3.0

1.2

94-94/134

631-631/853

205-205/277

407

500

575/60/3

2

3

12/6

1.5

2.5

3.0

1.2

94-94/134

631-631/853

205-205/277

244/184

300/300

200/60/3

1

200/60/3

2

3

14/6

1.5

6.5

7.3

1.2

320-320/386

701-701/821

817/526

1000/800

230/60/3

1

230/60/3

2

571-571/691

722/463

800/700

380/60/3

1

380/60/3

2

3

14/6

1.5

3.5

3.7

1.2

168-168/203

1060-1060/1306

345-345/424

430/277

500/450

460/60/3

1

3

20

1.5

3

3.7

1.2

139-139/168

878-878/1065

285-285/346

555

700

460/60/3

2

3

14/6

1.5

3

3.7

1.2

139-139/168

878-878/1065

285-285/346

358/231

450/350

575/60/3

1

3

20

1.5

2.5

3.0

1.2

111-111/134

705-705/853

229-229/277

446

500

575/60/3

2

3

14/6

1.5

2.5

3.0

1.2

111-111/134

705-705/853

229-229/277

287/184

350/300

200/60/3

1
1.2

270-270/
270-270

1845-1845/
1845-1845

600-600/
600-600

691/691

800/800

1556-1556/
1556-1556

506-506/
506-506

612/612

800/800

200/60/3

2

230/60/3

1

230/60/3

2

380/60/3

1

n/a
n/a
3

12/6

1.5

6.5

7.3

1.2

235-235/336

1556-1556/2126
n/a

n/a
2156-2156/2525
n/a
3

14/6

1.5

6.5

7.3

1.2

278-278/336

1756-1756/2126
n/a

n/a
4

12/12

1.5

6.5

7.3

n/a
4

12/12

1.5

6.5

7.3

1.2

235-235/
235-235

973-973/
973-973

316-316/
316-316

364/364

500/500

n/a

380/60/3

2

4

12/12

1.5

3.5

3.7

1.2

142-142/
142-142

460/60/3

1

4

24

1.5

3

3.7

1.2

118-118/
118-118

774-774/
774-774

252-252/
252-252

580

600

774-774/
774-774

252-252/
252-252

305/305

400/400

460/60/3

2

4

12/12

1.5

3

3.7

1.2

118-118/
118-118

575/60/3

1

4

24

1.5

2.5

3.0

1.2

94-94/
94-94

631-631/
631-631

205-205/
205-205

464

500

575/60/3

2

4

12/12

1.5

2.5

3.0

1.2

94-94/
94-94

631-631/
631-631

205-205/
205-205

244/244

300/300

RLC-PRC006M-EN

Electrical Data

Table 17. Extra efficiency — high and wide ambient
Unit
Size

#
# Fan
Rated
#
Power
Ckt1/ Fan Fan VFD Cntrl
Voltage1 Conn2 Comp Ckt2 kW FLA Input kVA3
200/60/3

350

1

200/60/3

2

230/60/3

1

230/60/3

2

380/60/3

1

380/60/3

RLA4
Ckt1/Ckt2

2

XLRA5
Ckt1/Ckt2

YLRA5
Ckt1/Ckt2

MCA6
Ckt1/
Ckt2

MOP7
Ckt1/
Ckt2

n/a
4

14/14

1.5

6.5

7.3

1.59

320-320/
320-320

2156-2156/
2156-2156

701-701/
701-701

817/817

1000/1000

1.59

278-278/
278-278

1756-1756/
1756-1756

571-571/
571-571

722/722

1000/1000

1.59

168-168/
168-168

1060-1060/
1060-1060

345-345/
345-345

430/430

500/500

878-878/
878-878

285-285/
285-285

681

700

n/a
4

14/14

1.5

6.5

7.3

n/a
4

14/14

1.5

3.5

3.7

460/60/3

1

4

28

1.5

3

3.7

1.59

139-139/
139-139

460/60/3

2

4

14/14

1.5

3

3.7

1.59

139-139/
139-139

878-878/
878-878

285-285/
285-285

358/358

450/450

575/60/3

1

4

28

1.5

2.5

3.0

1.59

111-111/
111-111

705-705/
705-705

229-229/
229-229

547

600

575/60/3

2

4

14/14

1.5

2.5

3.0

1.59

111-111/
111-111

705-705/
705-705

229-229/
229-229

287/287

350/350

Notes:
1. Voltage Utilization Range: +/- 10% of rated voltage. Rated voltage (use range): 200/60/3 (180-220), 230/60/3 (208-254), 380/60/3 (342-418), 460/60/
3 (414-506), 575/60/3 (516-633)
2. As standard, 140-250 ton units have a single point power connection. Optional dual point power connections are available. As standard, 275-500 ton units
have dual point power connections. Optional single point power connections are available on 460V and 575V/60 Hz units.
3. Control VA includes operational controls only. It does not include evaporator heaters. A separate 115/60/1, 20 amp customer provided power connection
is required to power the evaporator heaters (1640 watts).
4. RLA - Rated Load Amps
5. XLRA - Locked Rotor Amps - based on full winding (x-line) start units). YLRA for wye-delta starters is ~1/3 of LRA of x-line units.
6. MCA - Minimum Circuit Ampacity - 125 percent of largest compressor RLA plus 100 percent of all other loads.
7. Max fuse or MOPD = 225 percent of the largest compressor RLA plus 100 percent of the second compressor RLA, plus the sum of the condenser fan FLA.
(Use FLA per circuit, NOT FLA for the entire unit).
8. Local codes may take precedence.
9. All ambient means standard, low, high and wide ambient options.

RLC-PRC006M-EN

45

Electrical Data

Table 18. Customer wire selection — standard efficiency
Single point power
Unit
Size

Circuit
Breaker

Dual point power - Ckt 1

Term

Disc

Circuit
Breaker

(2) 2/0 500 MCM

(2) 2/0 500 MCM

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

Term

Disc

200

(2) 4 AWG 500 MCM

(3) 3/0 - 500
MCM

230

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

380

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

460

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

4 AWG 500 MCM

3/0350MCM

3/0500MCM

4 AWG 500 MCM

3/0350MCM

3/0500MCM

575

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

4 AWG - 5
00 MCM

3/0350MCM

3/0500MCM

4 AWG 500 MCM

3/0350MCM

3/0500MCM

200

(2) 4 AWG 500 MCM

(4) 3/0 500 MCM

(4) 3/0 500 MCM

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

230

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

380

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

460

4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

4 AWG 500 MCM

3/0350MCM

3/0500MCM

575

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

4 AWG 500 MCM

3/0350MCM

3/0500MCM

4 AWG 500 MCM

3/0350MCM

3/0500MCM

200

(4) 2 AWG 600 MCM

(4) 3/0 500 MCM

(4) 3/0 500 MCM

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

230

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

380

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

460

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

575

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

4 AWG 00 MCM

3/0350MCM

3/0500MCM

4 AWG 500 MCM

3/0350MCM

3/0500MCM

(3) 3/0 - 500 (2) 4 AWG MCM
500 MCM

155

170

46

Disc

Volt

140

Term

Dual point power - Ckt 2

Circuit
Breaker

RLC-PRC006M-EN

Electrical Data

Table 18. Customer wire selection — standard efficiency (continued)
Single point power
Unit
Size

Dual point power - Ckt 1

Volt

Term

Disc

200

(4) 2 AWG 600 MCM

(4) 3/0 500 MCM

(4) 3/0 500 MCM

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

230

(4) 2 AWG 600 MCM

(4) 3/0 500 MCM

(4) 3/0 500 MCM

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

380

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

460

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

575

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

4 AWG 500 MCM

3/0350MCM

3/0500MCM

200

(4) 2 AWG 600 MCM

(4) 3/0 500 MCM

(4) 3/0 500 MCM

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

230

(4) 2 AWG 600 MCM

(4) 3/0 500 MCM

(4) 3/0 500 MCM

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

380

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

460

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

575

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(1) 1 AWG (1) 1 AWG 600 MCM or
600 MCM or
(2) 1 AWG - (2) 1 AWG - 250
MCM
250 MCM

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

200

(4) 2 AWG 600 MCM

(4) 3/0 500 MCM

(4) 3/0 500 MCM

(2) 4 AWG 500 MCM

(4) 3/0 500 MCM

(4) 3/0 500 MCM

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

230

(4) 2 AWG 600 MCM

(4) 3/0 500 MCM

(4) 3/0 500 MCM

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

380

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(2) 2/0 00 MCM

(2) 2/0 500 MCM

460

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

575

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

200

(4) 2 AWG 600 MCM

(4) 3/0 500 MCM

(4) 3/0 500 MCM

(2) 4 AWG 500 MCM

(4) 3/0 500 MCM

(4) 3/0 500 MCM

(2) 4 AWG 500 MCM

(4) 3/0 500 MCM

(4) 3/0 500 MCM

230

(4) 2 AWG 600 MCM

(4) 3/0 500 MCM

(4) 3/0 500 MCM

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

380

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

460

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 00 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

575

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

Term

185

200

225

250

Dual point power - Ckt 2

Circuit
Breaker

RLC-PRC006M-EN

Disc

Circuit
Breaker

Term

Disc

Circuit
Breaker

47

Electrical Data

Table 18. Customer wire selection — standard efficiency (continued)
Single point power
Unit
Size

Volt

Term

Disc

Term

Disc

Circuit
Breaker

Dual point power - Ckt 2
Term

Disc

Circuit
Breaker

n/a

(4) 4 AWG 500 MCM

(4) 3/0 500 MCM

(4) 3/0 500 MCM

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

230

n/a

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

380

n/a

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

460

n/a

(4) 2 AWG 600 MCM

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

575

n/a

(4) 2 AWG 600 MCM

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

200

n/a

(4) 2 AWG 600 MCM

(4) 3/0 500 MCM

(4) 3/0 500 MCM

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

230

n/a

(4) 2 AWG 600 MCM

(4) 3/0 500 MCM

(4) 3/0 500 MCM

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

380

n/a

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

300
460

n/a

(4) 2 AWG 600 MCM

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

575

n/a

(4) 2 AWG 600 MCM

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

200

n/a

(4) 2 AWG 600 MCM

(4) 3/0 500 MCM

(4) 3/0 500 MCM

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

230

n/a

(4) 2 AWG 600 MCM

(4) 3/0 500 MCM

(4) 3/0 500 MCM

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

380

n/a

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

350

48

Dual point power - Ckt 1

200

275

400

Circuit
Breaker

460

n/a

(4) 2 AWG 600 MCM

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 00 MCM

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

575

n/a

(4) 2 AWG 600 MCM

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

200

n/a

(4) 2 AWG 600 MCM

(4) 3/0 500 MCM

(4) 3/0 500 MCM

(4) 2 AWG 600 MCM

(4) 3/0 500 MCM

(4) 3/0 500 MCM

230

n/a

(4) 2 AWG 600 MCM

(4) 3/0 500 MCM

(4) 3/0 500 MCM

(4) 2 AWG 600 MCM

(4) 3/0 500 MCM

(4) 3/0 500 MCM

380

n/a

(2) 4 AWG 500 MCM

(3) 3/0 00 MCM

(3) 3/0 500 MCM

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

460

n/a

(4) 2 AWG 600 MCM

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

575

n/a

(4) 2 AWG 600 MCM

(2) 4 AWG 500 MCM

(2) 2/0 00 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

RLC-PRC006M-EN

Electrical Data

Table 18. Customer wire selection — standard efficiency (continued)
Single point power
Unit
Size

450

500

1.
2.
3.
4.

Volt

Term

Disc

Circuit
Breaker

Dual point power - Ckt 1
Term

Disc

Circuit
Breaker

Dual point power - Ckt 2
Term

Disc

Circuit
Breaker

200

n/a

(4) 2 AWG 600 MCM

(4) 3/0 500 MCM

(4) 3/0 500 MCM

(4) 2 AWG 600 MCM

(4) 3/0 500 MCM

(4) 3/0 500 MCM

230

n/a

(4) 2 AWG 600 MCM

(4) 3/0 500 MCM

(4) 3/0 500 MCM

(4) 2 AWG 600 MCM

(4) 3/0 500 MCM

(4) 3/0 500 MCM

380

n/a

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

460

n/a

(4) 2 AWG 600 MCM

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

575

n/a

(4) 2 AWG 600 MCM

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

200

n/a

(4) 2 AWG 600 MCM

(4) 3/0 500 MCM

(4) 3/0 500 MCM

(4) 2 AWG 600 MCM

(4) 3/0 500 MCM

(4) 3/0 500 MCM

230

n/a

(4) 2 AWG 600 MCM

(4) 3/0 500 MCM

(4) 3/0 500 MCM

(4) 2 AWG 600 MCM

(4) 3/0 500 MCM

(4) 3/0 500 MCM

380

n/a

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

460

n/a

(4) 2 AWG 600 MCM

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

575

n/a

(4) 2 AWG 600 MCM

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

Non-fused unit disconnect and circuit breaker are optional.
Copper wire only, based on nameplate minimum circuit ampacity (MCA).
Circuit breaker sizes are for factory mounted only.
n/a - not available

RLC-PRC006M-EN

49

Electrical Data

Table 19. Customer wire selection — high efficiency
Single point power
Unit
Size Volt Ambient

Disc

Dual point power - Ckt 1
Term

Disc

Term

Disc

Circuit
Breaker

All

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

230

All

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

380

All

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

460

Std, Low

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

4 AWG 500 MCM

3/0350MCM

3/0350MCM

4 AWG 500 MCM

3/0350MCM

3/0350MCM

460

High, Wide

4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

3/0350MCM

3/0350MCM

4 AWG 500 MCM

3/0350MCM

3/0350MCM

575

All

4 AWG 500 MCM

4 AWG 500 MCM

3/0350MCM

3/0350MCM

4 AWG 500 MCM

3/0350MCM

3/0350MCM

200

All

(2) 4 AWG 500 MCM

(4) 3/0 500 MCM

(4) 3/0 500 MCM

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

230

All

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

380

All

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

460

Std, Low

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

4 AWG 500 MCM

3/0350MCM

3/0350MCM

460

High, Wide

4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

4 AWG 500 MCM

3/0350MCM

3/0350MCM

575

All

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

4 AWG 500 MCM

3/0350MCM

3/0350MCM

4 AWG 500 MCM

3/0350MCM

3/0350MCM

200

All

(4) 2 AWG 600 MCM

(4) 3/0 500 MCM

(4) 3/0 500 MCM

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

230

All

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

380

All

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

4 AWG 00 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

460

All

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

575

All

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

4 AWG 500 MCM

3/0350MCM

3/0350MCM

4 AWG 500 MCM

3/0350MCM

3/0350MCM

(1) 1 AWG (1) 1 AWG 600 MCM or
600 MCM or
(2) 1 AWG - 250 (2) 1 AWG 250 MCM
MCM

170

50

Dual point power - Ckt 2

Circuit
Breaker

200

140

155

Term

Circuit
Breaker

RLC-PRC006M-EN

Electrical Data

Table 19. Customer wire selection — high efficiency (continued)
Single point power
Unit
Size Volt Ambient

Term

Disc

Circuit
Breaker

Dual point power - Ckt 1
Term

Dual point power - Ckt 2

Disc

Circuit
Breaker

Term

Disc

Circuit
Breaker

200

All

(4) 2 AWG 600 MCM

(4) 3/0 500 MCM

(4) 3/0 500 MCM

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

230

All

(4) 2 AWG 600 MCM

(4) 3/0 500 MCM

(4) 3/0 500 MCM

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

380

All

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

460

All

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

575

All

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

4 AWG 500 MCM

3/0350MCM

3/0350MCM

200

All

(4) 2 AWG 600 MCM

(4) 3/0 500 MCM

(4) 3/0 500 MCM

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

230

All

(4) 2 AWG 600 MCM

(4) 3/0 500 MCM

(4) 3/0 500 MCM

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

380

All

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

460

All

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

575

All

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

200

All

(4) 2 AWG 600 MCM

(4) 3/0 500 MCM

(4) 3/0 500 MCM

(2) 4 AWG 500 MCM

(4) 3/0 500 MCM

(4) 3/0 500 MCM

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

230

All

(4) 2 AWG 600 MCM

(4) 3/0 500 MCM

(4) 3/0 500 MCM

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

380

All

(2) 4 AWG 500 MCM

(3) 3/0350MCM

(3) 3/0 500 MCM

4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

460

All

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

575

All

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG
- 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

200

All

(4) 2 AWG 600 MCM

(4) 3/0 500 MCM

(4) 3/0 500 MCM

(2) 4 AWG 500 MCM

(4) 3/0 500 MCM

(4) 3/0 500 MCM

(2) 4 AWG 500 MCM

(4) 3/0 500 MCM

(4) 3/0 500 MCM

230

All

(4) 2 AWG 600 MCM

(4) 3/0 500 MCM

(4) 3/0 500 MCM

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

380

All

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

460

Std, Low

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 00 MCM

4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

460

High, Wide

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

575

All

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

185

200

225

250

RLC-PRC006M-EN

51

Electrical Data

Table 19. Customer wire selection — high efficiency (continued)
Single point power
Unit
Size Volt Ambient

Term

Disc

Circuit
Breaker

Dual point power - Ckt 1
Term

Disc

Circuit
Breaker

Dual point power - Ckt 2
Term

Disc

Circuit
Breaker

200

All

n/a

(4) 4 AWG 600 MCM

(4) 3/0 500 MCM

(4) 3/0 500 MCM

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

230

All

n/a

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(4) 3/0 500 MCM

(4) 3/0 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

380

All

n/a

(4) 2 AWG - (2) 4 AWG 600 MCM
500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

460

All

n/a

(4) 2 AWG - (2) 4 AWG 600 MCM
500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

575

All

n/a

(4) 2 AWG 600 MCM

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

200

All

n/a

(4) 4 AWG 600 MCM

(4) 3/0 500 MCM

(4) 3/0 500 MCM

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

230

All

n/a

(4) 4 AWG 600 MCM

(4) 3/0 500 MCM

(4) 3/0 500 MCM

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

380

Std, Low

n/a

(4) 2 AWG - (2) 4 AWG 600 MCM
500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

380

High, Wide

n/a

(4) 2 AWG - (2) 4 AWG 600 MCM
500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

460

All

n/a

(4) 2 AWG - (2) 4 AWG 600 MCM
500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

575

All

n/a

(4) 2 AWG - (2) 4 AWG 600 MCM
500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

200

All

n/a

(4) 4 AWG 600 MCM

(4) 3/0 500 MCM

(4) 3/0 500 MCM

(4) 2 AWG 600 MCM

(4) 3/0 500 MCM

(4) 3/0 500 MCM

230

All

n/a

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

380

All

n/a

(4) 2 AWG - (2) 4 AWG 600 MCM
500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

460

All

n/a

(4) 2 AWG - (2) 4 AWG 600 MCM
500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

575

All

n/a

(4) 2 AWG 600 MCM

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

4 AWG 500 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

(1) 1 AWG 600 MCM or
(2) 1 AWG 250 MCM

200

All

n/a

(4) 4 AWG 600 MCM

(4) 3/0 500 MCM

(4) 3/0 500 MCM

(4) 2 AWG 600 MCM

(4) 3/0 500 MCM

(4) 3/0 500 MCM

230

All

n/a

(4) 4 AWG 600 MCM

(4) 3/0 500 MCM

(4) 3/0 500 MCM

(4) 2 AWG 600 MCM

(4) 3/0 500 MCM

(4) 3/0
- 500 MCM

380

Std, Low

n/a

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

380

High, Wide

n/a

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

460

All

n/a

(4) 2 AWG - (2) 4 AWG 600 MCM
500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

575

All

n/a

(4) 2 AWG - (2) 4 AWG 600 MCM
500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

275

300

350

400

1.
2.
3.
4.

52

Non-fused unit disconnect and circuit breaker are optional.
Copper wire only, based on nameplate minimum circuit ampacity (MCA).
Circuit breaker sizes are for factory mounted only.
n/a - not available

RLC-PRC006M-EN

Electrical Data

Table 20.

Customer wire selection — extra efficiency
Single point power

Unit
Size

Dual point power - Ckt 1

Dual point power - Ckt 2

Volt

Term

Disc

Circuit
Breaker

200

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

230

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

380

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG - 500
MCM

(1) #1 600 MCM or
(2) #1 250 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

4 AWG 500 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

460

4 AWG 500 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

4 AWG 500 MCM

3/0350MCM

3/0350MCM

4 AWG 500 MCM

3/0350MCM

3/0350MCM

575

4 AWG 500 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

4 AWG 500 MCM

3/0350MCM

3/0350MCM

4 AWG 500 MCM

3/0350MCM

3/0350MCM

200

(2) 4 AWG 500 MCM

(4) 3/0 500 MCM

(4) 3/0 500 MCM

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

230

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

380

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

4 AWG 500 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

460

4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

4 AWG 500 MCM

3/0350MCM

3/0500MCM

575

4 AWG 500 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

4 AWG 500 MCM

3/0350MCM

3/0350MCM

4 AWG 500 MCM

3/0350MCM

3/0350MCM

200

(4) 2 AWG 600 MCM

(4) 3/0 500 MCM

(4) 3/0 500 MCM

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

230

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 - 500
MCM

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

380

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

4 AWG 500 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

460

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

4 AWG 500 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

575

4 AWG 500 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

4 AWG 500 MCM

3/0350MCM

3/0350MCM

4 AWG 500 MCM

3/0350MCM

3/0350MCM

140

Term

155

170

RLC-PRC006M-EN

Disc

Circuit
Breaker

Term

Disc

Circuit
Breaker

53

Electrical Data

Table 20.

Customer wire selection — extra efficiency (continued)
Single point power

Unit
Size

Dual point power - Ckt 1

Volt

Term

Disc

200

(4) 2 AWG 600 MCM

(4) 3/0 500 MCM

(4) 3/0 500 MCM

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

230

(4) 2 AWG 600 MCM

(4) 3/0 500 MCM

(4) 3/0 500 MCM

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

380

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

460

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

4 AWG 500 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

575

4 AWG 500 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

4 AWG 500 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

4 AWG 500 MCM

3/0350MCM

3/0500MCM

200A

(4) 2 AWG 600 MCM

(4) 3/0 500 MCM

(4) 3/0 500 MCM

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

230A

(4) 2 AWG 600 MCM

(4) 3/0 500 MCM

(4) 3/0 500 MCM

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

380A

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

4 AWG - 500
MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

460A

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

4 AWG 500 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

575A

(2) 4 AWG 500 MCM

(2) 2/0 - 5
00 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

4 AWG 500 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

Term

185

200

Disc

Circuit
Breaker

Term

Disc

Circuit
Breaker

200A

n/a

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

230A

n/a

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

380A

n/a

(4) 2 AWG 600 MCM

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

460A

n/a

(4) 2 AWG 600 MCM

4 AWG 500 MCM

(2) 2/0 500 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

4 AWG 500 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

575A

n/a

(4) 2 AWG 600 MCM

4 AWG 500 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

4 AWG 500 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

250

200A

n/a

(4) 2 AWG 600 MCM

(4) 3/0 500 MCM

(4) 3/0 500 MCM

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

230A

n/a

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

380A

n/a

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

275

54

Dual point power - Ckt 2

Circuit
Breaker

460A

n/a

(4) 2 AWG 600 MCM

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

4 AWG 500 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

575A

n/a

(4) 2 AWG 600 MCM

4 AWG 500 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

4 AWG 500 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

RLC-PRC006M-EN

Electrical Data

Table 20.

Customer wire selection — extra efficiency (continued)
Single point power

Unit
Size

Volt

Term

Disc

1.
2.
3.
4.

Dual point power - Ckt 1
Term

Disc

Circuit
Breaker

Dual point power - Ckt 2
Term

Disc

Circuit
Breaker

200A

n/a

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0
- 500 MCM

230A

n/a

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

380A

n/a

(4) 2 AWG 600 MCM

(2) 4 AWG 500 MCM

(2) 2/0 - 500
MCM

(2) 2/0 500 MCM

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

460A

n/a

(4) 2 AWG 600 MCM

4 AWG 500 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

4 AWG 500 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

575A

n/a

(4) 2 AWG 600 MCM

4 AWG 500 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

4 AWG 500 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

300

350

Circuit
Breaker

200A

n/a

(4) 2 AWG 600 MCM

(4) 3/0 500 MCM

(4) 3/0 500 MCM

(4) 2 AWG 600 MCM

(4) 3/0 500 MCM

(4) 3/0 500 MCM

230A

n/a

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

(2) 4 AWG 500 MCM

(3) 3/0 500 MCM

(3) 3/0 500 MCM

380A

n/a

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0
- 500 MCM

460A

n/a

(4) 2 AWG 600 MCM

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

(2) 4 AWG 500 MCM

(2) 2/0 500 MCM

(2) 2/0 500 MCM

575A

n/a

(4) 2 AWG 600 MCM

4 AWG 500 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

4 AWG 500 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

(1) #1 600 MCM or
(2) #1 250 MCM

Non-fused unit disconnect and circuit breaker are optional.
Copper wire only, based on nameplate minimum circuit ampacity (MCA).
Circuit breaker sizes are for factory mounted only.
n/a - not available

RLC-PRC006M-EN

55

Release on 4/25/2

Electrical Connection

56

RLC-PRC006M-EN

Electrical Connection

RLC-PRC006M-EN

57

Electrical Connection

58

RLC-PRC006M-EN

Electrical Connection

RLC-PRC006M-EN

59

Release on 5

Electrical Connection

60

RLC-PRC006M-EN

Electrical Connection

RLC-PRC006M-EN

61

Electrical Connection

62

RLC-PRC006M-EN

Electrical Connection

RLC-PRC006M-EN

63

Dimensions
Note: Mounting location dimensions may vary on units with seismic rating. See unit submittals..

64

RLC-PRC006M-EN

Dimensions

RLC-PRC006M-EN

65

140 XE - 60 HZ

5/8

Dimensions

66

RLC-PRC006M-EN

155, 170 XE - 60 HZ

,
& 155 XE

Dimensions

RLC-PRC006M-EN

67

185 & 200 XE - 60 HZ

& 185

13
13

Dimensions

68

RLC-PRC006M-EN

Dimensions

RLC-PRC006M-EN

69

ON 275, 300 & 250

250 XE - 60 HZ

Dimensions

70

RLC-PRC006M-EN

275 XE - 60 HZ

Dimensions

RLC-PRC006M-EN

71

300 XE - 60HZ

Dimensions

72

RLC-PRC006M-EN

350 XE - 60 HZ

Dimensions

RLC-PRC006M-EN

73

Weights
Non-Seismically Rated Units
Table 21.

Weight - packaged units - 60 Hz - aluminum or CompleteCoat coils
Standard Efficiency

High Efficiency

Extra Efficiency

Unit
Size
(tons)

lb

kg

lb

kg

lb

kg

lb

kg

lb

kg

lb

kg

140

10832

4913

11146

5056

10859

4926

11160

5062

12171

5521

12585

5708

155

10910

4949

11146

5056

12114

5495

12445

5645

13984

6343

14293

6483

170

10877

4934

11218

5088

12171

5521

12585

5708

14454

6556

14721

6677

185

12479

5660

12899

5851

13984

6343

14293

6483

15915

7219

16413

7445

200

12884

5844

13193

5984

14454

6556

14721

6677

16016

7265

16413

7445

225

14635

6638

14966

6788

15915

7219

16413

7445

250

14916

6766

15191

6890

16016

7265

16413

7445

20476

9288

21048

9547

275

19025

8630

19685

8929

20393

9250

21048

9547

21667

9828

22160

10052

300

20699

9389

21214

9622

21667

9828

22160

10052

24073

10919

24700

11204

350

21550

9775

22005

9981

24073

10919

24700

11204

27136

12309

27750

12587

400

25409

11525

25854

11727

27136

12309

27750

12587

450

26816

12163

27393

12425

n/a

n/a

500

27136

12309

27912

12661

n/a

n/a

Shipping

Operating

Shipping

Operating

Shipping

Operating

n/a

n/a

1. Operating weight includes refrigerant and water.
2. Shipping weight includes refrigerant.
3. All weights +/- 3%.

Table 22. Weight - packaged units - 60 Hz - copper coils
Standard Efficiency

High Efficiency

Extra Efficiency

Unit
Size
(tons)

lb

kg

lb

kg

lb

kg

lb

kg

lb

kg

lb

kg

140

13407

6081

13734

6230

13426

6090

13734

6230

15590

7071

15998

7257

155

13420

6087

13734

6230

15647

7097

15854

7191

18250

8278

18613

8443

170

13442

6097

13733

6229

15590

7071

15998

7257

18701

8483

18958

8599

185

15870

7198

16253

7372

18250

8278

18613

8443

20794

9432

21290

9657

200

16304

7395

16630

7543

18701

8483

18958

8599

20881

9471

21290

9657

225

18739

8500

18156

8235

20794

9432

21290

9657

250

18905

8575

19223

8719

20881

9471

21290

9657

26017

11801

26558

12046

275

23905

10843

24608

11162

26017

11801

26558

12046

27660

12546

28182

12783

300

26039

11811

26580

12056

27660

12546

28182

12783

30848

13992

31431

14257

350

27395

12426

27920

12664

30848

13992

31431

14257

35166

15951

35688

16188

400

32216

14613

32723

14843

35014

15882

35688

16188

450

32682

14824

33178

15049

n/a

n/a

500

35014

15882

35787

16233

n/a

n/a

Shipping

Operating

Shipping

Operating

Shipping

Operating

n/a

n/a

1. Operating weight includes refrigerant and water.
2. Shipping weight includes refrigerant.
3. All weights +/- 3%.

74

RLC-PRC006M-EN

Weights

Seismically Rated Units
Table 23. Weight - seismically rated - packaged units - 60 Hz - aluminum or CompleteCoat coils
Standard Efficiency

High Efficiency

Extra Efficiency

Unit
Size
(tons)

lb

kg

lb

kg

lb

kg

lb

kg

lb

kg

lb

kg

140

11374

5159

11646

5283

11402

5172

11711

5312

12780

5797

13185

5981

155

11456

5196

11703

5308

12720

5770

13067

5927

14683

6660

15021

6813

170

11421

5180

11779

5343

12780

5797

13214

5994

15177

6884

15433

7000

185

13103

5943

13544

6143

14683

6660

15008

6807

16711

7580

17234

7817

200

13528

6136

13853

6284

15177

6884

15457

7011

16817

7628

17234

7817

225

15367

6970

15714

7128

16711

7580

17234

7817

250

15662

7104

15951

7235

16817

7628

17234

7817

21500

9752

22100

10025

275

19976

9061

20669

9375

21413

9713

22100

10025

22750

10319

23268

10554

300

21734

9858

22275

10104

22750

10319

23268

10554

25277

11465

25935

11764

350

22628

10264

23105

10480

25277

11465

25935

11764

28493

12924

29138

13216

400

26679

12102

27147

12313

28493

12924

29138

13216

450

28157

12772

28763

13046

n/a

n/a

500

28493

12924

29308

13294

n/a

n/a

Shipping

Operating

Shipping

Operating

Shipping

Operating

n/a

n/a

1. Operating weight includes refrigerant and water.
2. Shipping weight includes refrigerant.
3. All weights +/- 3%.

RLC-PRC006M-EN

75

Mechanical Specifications
General
Units are leak and pressure tested at 390 psig high side, 250 psig low side, then evacuated and
charged. All Air-Cooled Series R Chillers are factory tested prior to shipment. Packaged units ship
with a full operating charge of oil and refrigerant. Unit panels, structural elements and control
boxes are constructed of galvanized steel and mounted on a welded structural steel base. Unit
panels and control boxes are finished with a baked on powder paint, and the structural base with
an air dry paint. All paint meets the requirement for outdoor equipment of the US Navy and other
federal government agencies.

Evaporator
The evaporator is a tube-in-shell heat exchanger design with internally and externally finned
copper tubes roller expanded into the tube sheet.The evaporator is designed, tested and stamped
in accordance with ASME for a refrigerant side working pressure of 200 psig.The evaporator is
designed for a water side working pressure of 150 psig. Water connections are grooved pipe. Each
shell includes a vent, a drain and fittings for temperature control sensors and is insulated with
3/4 inch equal insulation (K=0.28). Evaporator heaters with thermostat are provided to help protect
the evaporator from freezing at ambient temperatures down to -20°F (-29°C). Factory installed flow
switch is installed on a pipe stub in the evaporator inlet.

Condenser and Fans
Air-cooled condenser coils have aluminum fins mechanically bonded to internally finned seamless
copper tubing.The condenser coil has an integral subcooling circuit. Condensers are factory proof
and leak tested at 506 psig. Direct drive vertical discharge condenser fans are dynamically
balanced.Totally enclosed air over motors completely seal the motor windings to prevent
exposure to ambient conditions.Three-phase condenser fan motors with permanently lubricated
ball bearings and internal thermal overload protection are provided. Standard units will start and
operate between 25 to 115°F (-4 to 46°C) ambient.

Compressor and Lube Oil System
The rotary screw compressor is semi-hermetic, direct drive, 3600 rpm, 60 Hz, with capacity control
slide valve, a load/unload valve, rolling element bearings, differential refrigerant pressure oil pump
and oil heater.The motor is a suction gas cooled, hermetically sealed, two-pole squirrel cage
induction motor. Oil separator and filtration devices are provided separate from the compressor.
Check valves in the compressor discharge and lube oil system and a solenoid valve in the lube
system are also provided.

Refrigeration Circuits
Each unit has two refrigerant circuits, with one or two rotary screw compressors per circuit. Each
refrigerant circuit includes a compressor suction and discharge service valve, liquid line shutoff
valve, removable core filter, liquid line sight glass with moisture indicator, charging port and an
electronic expansion valve. Fully modulating compressors and electronic expansion valves
provide variable capacity modulation over the entire operating range.

Unit Controls
All unit controls are housed in an outdoor rated weather tight enclosure with removable plates to
allow for customer connection of power wiring and remote interlocks. All controls, including
sensors, are factory mounted and tested prior to shipment. Microcomputer controls provide all
control functions including startup and shut down, leaving chilled water temperature control,
evaporator flow proving, compressor and electronic expansion valve modulation, fan sequencing,
anti-recycle logic, automatic lead/lag compressor starting and load limiting.The unit control
module, utilizing Adaptive Control™ microprocessor, automatically takes action to avoid unit
shutdown due to abnormal operating conditions associated with low refrigerant pressure, high
condensing pressure and motor current overload. Should the abnormal operating condition
continue until a protective limit is violated, the unit will be shut down. Unit protective functions
76

RLC-PRC006M-EN

Options

include loss of chilled water flow, evaporator freezing, loss of refrigerant, low refrigerant pressure,
high refrigerant pressure, reverse rotation, compressor starting and running over current, phase
loss, phase imbalance, phase reversal, and loss of oil flow. A digital display indicates chilled water
setpoint and leaving chilled water temperature as standard. While current limit setpoint,
evaporator and condenser refrigerant pressures, and electrical information are an option. Both
standard and optional displays can be viewed on the unit without opening any control panel doors.
Standard power connections include main three phase power to the compressors, condenser fans
and control power transformer and optional connections are available for the 115 volt/60 Hz single
phase power for freeze protection on the evaporator heaters.

Starters
Starters are housed in a weather tight enclosure with removable cover plate to allow for customer
connection of power wiring. Across-the-line starters are standard on all 380-575/60 volt units. Wye
Delta closed transition starters (33 percent of LRA inrush) are optional on 380-575/60 volt units and
standard on 200-230/60 Hz volt units.Typically,Trane helical rotary screw compressors are up to
full speed in one second when started across-the-line and have equivalent inrush with similar size
reciprocating compressor with part wind starters.

Chilled Water Reset
This provides the control logic and factory installed sensors to reset leaving chilled water
temperature.The setpoint can be reset based on ambient temperature or return evaporator water
temperature.

Flow Control
The factory installed flow switch is provided with the control logic and relays to turn the chilled
water flow on and off as the chiller requires for operation and protection.This function is a
requirement on the Air-Cooled Series R Chiller.

Options
Applications Options
High Efficiency/Performance Option
High efficiency option provides an increase in efficiency over standard efficiency by providing
oversized heat exchangers for two purposes. One, it allows the unit to be more energy efficient.
Two, the unit will have enhanced operation in high ambient conditions.

Extra Efficiency/Performance Option
Extra efficiency option provides an increase in efficiency over the high efficiency unit by providing
oversized heat exchangers for two purposes. One, it allows the unit to be more energy efficient.
Two, the unit will have enhanced operation in high ambient conditions.

Ice Making
The ice making option provides special control logic and oil coolers to handle low temperature
brine applications (less than 40°F [4.4°C] leaving evaporator temperature) for thermal storage
applications.

Low Temperature Brine
The low temperature option provides special control logic and oil coolers to handle low
temperature brine applications (less than 40°F [4.4°C] leaving evaporator temperature).

RLC-PRC006M-EN

77

Options

Low Ambient Option
The low ambient option provides special control logic, oil coolers, and variable frequency drives
on the condenser fan circuits to permit low temperature startup and operation down to 0°F (-18°C).

High Ambient Option
The high ambient option consists of special control logic and oil coolers to permit high ambient
(up to 125°F [51°C]) operation.This option offers the best performance when coupled with the high
efficiency performance option.

Remote Evaporator
The remote evaporator option is available on the RTAC 140-250 ton units.This option provides a
pre-engineered method of installing the evaporator and all related components indoors. Remote
evaporator installations allow the water loop to remain indoors to prevent freezing, thus
eliminating the addition of glycol to the system and the resulting performance degradation. Please
contact yourTrane Sales Representative for split system design guidelines found in Engineering
Bulletin RLC-PRB014-EN.

Electrical Options
Circuit Breaker
A HACR rated molded case capacity circuit breaker (UL approved) is available.The circuit breaker
can also be used to disconnect the chiller from main power with a through the door handle and
comes pre-wired from the factory with terminal block power connections.The external operator
handle is lockable.

Non-Fused Power Disconnect Switch
The non-fused molded case disconnect switch (UL approved) is used to disconnect the chiller from
main power and comes pre-wired from the factory with terminal block power connections.The
external operator handle is lockable.

Single/Dual Incoming Power Line Connection
Single or dual points of termination are available for incoming power line connections*. Units with
3-4 compressors must order circuit breakers with the single point connection option.*Some
restrictions may apply.

Wye-Delta Compressor Start Type
This option provides a reduced inrush starter. Wye-Delta starters are standard on 200-230 volt
machines.

Control Options
BACnet Communications Interface
Allows the user to easily interface with BACnet via a single twisted pair wiring to a factory installed
and tested communication board.

LonTalk (LCI-C) Communications Interface
Provides the LonMark chiller profile inputs/outputs for use with a generic building automation
system.

Remote Input Options
Permits remote chilled liquid setpoint, remote current limit setpoint, or both by accepting a 4-20
mA or 2-10 Vdc analog signal.

78

RLC-PRC006M-EN

Options

Remote Output Options
Permits alarm relay outputs, ice making outputs, or both.

Tracer Summit Communication Interface
Permits bi-directional communication to theTracer Summit system.

Other Options
Architectural Louvered Panels
Louvered panels cover the complete condensing coil and service area beneath the condenser.

Coil Protection
Louvered panels protect the condenser coils only.

Compressor Sound Enhancement
Factory installed weatherproof compressor enclosure to reduce compressor sound levels.

Condenser Corrosion Protection
Copper fins and CompleteCoat are available on all size units for corrosion protection. Job site
conditions should be matched with the appropriate condenser fin materials to inhibit coil corrosion
and ensure extended equipment life.The CompleteCoat option provides fully assembled coils with
a flexible dip and bake epoxy coating.

Convenience Outlet
Provides a 15 amp, 115 volt (60 Hz) convenience outlet on the unit.

Flange Kit
Provides a raised face flange kit that converts the grooved pipe evaporator water connections to
flange connectors.

Insulation for High Humidity
The evaporator is covered with factory-installed 1.25 inch (31.8 mm) Armaflex II or equal (k=0.28)
insulation. Foam insulation is used on the suction line.

Low Noise Fans
Complete fan assembly combining ultra quiet nine blade fans andTEAO fan motors to provide
sound reductions with no performance degradation to the unit.The fan blades are heavy-duty
molded plastic with wavy edges to reduce airflow turbulation.

Isolators - Neoprene
Isolators provide isolation between chiller and structure to help eliminate vibration transmission.
Neoprene isolators are more effective and recommended over spring isolators.

Elastomeric Isolation Pads - Seismically Rated
Elastomeric isolation pads are designed and tested to control the motion of the chiller during a
seismic event.

Isolators - Seismically Rated
Spring isolators are designed and tested to control the motion of the chiller during a seismic event.

Seismically Rated Unit - IBC & OSHPD
Unit is built and certified for seismic applications in accordance with OSHPD and the following
International Building Code (IBC) releases: 2000, 2003, 2006 and 2009.

RLC-PRC006M-EN

79

Options

Performance Tests
Performance and witness tests are available, based on requested operating points, to certify chiller
performance in accordance with AHRI Standard 550/590.

Rapid Restart Test
After completion of a standard full load witness test, power to the chiller will be cut and then
reapplied to demonstrate the chiller’s rapid restart capabilities for disaster relief.

Tarp
The unit will be covered at the factory with a PVC coated polyester tarp that is tied to the chiller base
to help protect the chiller from debris during shipment especially in the winter months and on
shipping vessels. This option may also be helpful if the chiller will be stored at the jobsite before
use.

80

RLC-PRC006M-EN

Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in
creating and sustaining safe, comfortable and energy efficient environments, Trane offers a broad portfolio of advanced
controls and HVAC systems, comprehensive building services, and parts. For more information, visit www.Trane.com.
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.

© 2015 Trane All rights reserved
RLC-PRC006M-EN 15 Jan 2015

We are committed to using environmentally

Supersedes RLC-PRC006-EN (25 May 2012)

conscious print practices that reduce waste.



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.6
Linearized                      : No
Author                          : Sheryl Hill
Create Date                     : 2015:01:15 08:28:50Z
Keywords                        : RTAC, air-cooled, 60 Hz
Modify Date                     : 2015:01:16 10:41:47-07:00
Subject                         : Air-Cooled Series R? Chillers, Model RTAC, 140 to 500 nominal tons (60 Hz)
Has XFA                         : No
Language                        : en
Tagged PDF                      : Yes
XMP Toolkit                     : Adobe XMP Core 5.2-c001 63.139439, 2010/09/27-13:37:26
Creator Tool                    : FrameMaker 10.0.2
Metadata Date                   : 2015:01:16 10:41:47-07:00
Format                          : application/pdf
Title                           : RLC-PRC006M-EN (01/2015):  Product  Catalog, Air-Cooled Series R® Chillers, Model RTAC, 140 to 500 nominal tons (60 Hz)
Creator                         : Sheryl Hill
Description                     : Air-Cooled Series R? Chillers, Model RTAC, 140 to 500 nominal tons (60 Hz)
Producer                        : Acrobat Distiller 10.1.13 (Windows)
Document ID                     : uuid:3e0643ac-fdb6-4b1c-a92d-239874bf83f1
Instance ID                     : uuid:395afb17-192b-4e4e-87e3-bda6d560433a
Page Mode                       : UseOutlines
Page Count                      : 82
EXIF Metadata provided by EXIF.tools

Navigation menu