Trane Tr200 Users Manual BAS SVX49A EN 08/12/2011 Vertical Bypass/Non Bypass Panel / Operators Guide

Trane Heating System Vertical Bypass/Non Bypass Panel BAS-SVX49A-EN

TR200 to the manual 537eb00e-1323-40f3-87a5-1448bd3b338c

2015-01-21

: Trane Trane-Tr200-Users-Manual-236152 trane-tr200-users-manual-236152 trane pdf

Open the PDF directly: View PDF PDF.
Page Count: 86

DownloadTrane Trane-Tr200-Users-Manual- BAS-SVX49A-EN 08/12/2011 TR200 Vertical Bypass/Non Bypass Panel / Operators Guide  Trane-tr200-users-manual
Open PDF In BrowserView PDF
Operators Guide

TR200 Vertical Bypass/Non Bypass Panel

Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the
leader in creating and sustaining safe, comfortable and energy efficient environments, Trane offers a broad
portfolio of advanced controls and HVAC systems, comprehensive building services, and parts. For more
information, visit www.Trane.com.

SAFETY WARNING
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
© 2011 Trane All rights reserved
BAS-SVX49A-EN 12 August 2011

Only qualified personnel should install and service the equipment. The installation, starting up, and servicing
of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and
training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or
serious injury. When working on the equipment, ovserve all precautions in the literature and on the tags,
stickers, and labels that are attached to the equipment.

August 2011
177R0253

MG14D122

*MG14D122*

Rev. 2011-08-12

BAS-SVX49A-EN

Safety

Safety

WARNING
EQUIPMENT HAZARD!
The vertical bypass/non bypass panel contains dangerous
voltages when connected to mains voltage. It is strongly
recommended that all electrical work conform to the
National Electrical Code (NEC) and all national and local
regulations. Installation, start-up and maintenance should
be performed only by qualified personnel. Failure to follow
the NEC or local regulations could result in death or
serious injury.
Motor control equipment and electronic controls are
connected to hazardous mains voltages. Extreme care
should be taken to protect against shock. The user must
be protected against supply voltage and the motor must
be protected against overload in accordance with
applicable national and local regulations. Be sure
equipment is properly grounded. Wear safety glasses
whenever working on electric control or rotating
equipment.

Grounding
Correct protective grounding of the equipment must be
established in accordance with national and local codes.
Ground currents are higher than 3mA.

Safety Guidelines
1.

Disconnect the drive and vertical bypass/non
bypass panel from mains before commencing
service work

2.

DO NOT touch electrical parts of the vertical
bypass/non bypass panel or drive when mains is
connected. After mains has been disconnected,
wait 15 minutes before touching any electrical
components or read the label on vertical
bypass/non bypass panel.

3.

The user must be protected against supply
voltage and the motor must be protected against
overload in accordance with applicable national
and local regulations.

4.

While programming parameters, the motor may
start without warning. Activate the [Off] key on
the keypad when changing parameters.

5.

The [Off] key on the keypad does not isolate the
drive from mains voltage and is not to be used as
a safety switch.

Warning against unintended start

WARNING
UNINTENDED START!
When the vertical bypass/non bypass panel is connected
to AC input power, the motor may start at any time. The
drive, panel, motor, and any driven equipment must be in
operational readiness. Failure to be in operational
readiness when panel and drive are connected to AC input
power could result in death, serious injury, or equipment
or property damage.
When the vertical bypass/non bypass panel is connected
to mains, the motor may be started by means of an
external switch, a serial bus command, an input reference
signal, or a cleared fault condition. Use appropriate
cautions to guard against an unintended start.

WARNING
GROUNDING HAZARD!
For operator safety, it is important to ground drive, vertical
bypass panel, and motor properly. Follow the grounding
guidelines of local and national codes. Failure to follow
grounding guidelines could result in death or serious
injury.

BAS-SVX49A-EN

Contents

Contents
1 Introduction
1.1.1 Purpose of the Manual

2-1

1.1.2 Overview

2-1

1.1.3 Typical Bypass Operation

2-1

1.2 Bypass Circuits

2-1

1.2.1 Three-contactor Bypass

2-1

1.3 Bypass Options

2-2

1.3.1 Common Run/Stop with Bypass

2-2

1.3.2 Automatic Bypass

2-2

1.3.3 Run Permissive in Bypass

2-2

1.3.4 Basic Fire Mode in Bypass

2-2

1.3.5 Advanced Fire Mode in Bypass

2-2

1.3.6 Overload Protection

2-2

1.4 Bypass Platform Configurations

2-3

1.5 Switch Mode Power Supply

2-3

1.5.1 Control Transformer

2-3

1.6 Disconnects

2-3

1.6.1 Main Disconnect

2-3

1.6.2 Mode Selector Switch

2-4

1.6.3 Panel Configurations

2-5

1.6.4 Panel Voltage and Frame Ratings

2-6

1.7 Power Component Functions

2-6

1.7.1 Power Fusing

2-6

2 Pre-installation

3-1

2.1.1 Receiving Inspection

3-1

2.1.2 Pre-installation Check

3-1

2.1.3 Installation Site Check

3-1

2.2 Harsh Environments

3-2

2.2.1 Airborne Liquids

3-2

2.2.2 Airborne Solids

3-2

2.2.3 Corrosive Chemicals

3-2

3 Installation

BAS-SVX49A-EN

2-1

4-1

3.1.1 Tools Required

4-1

3.1.2 Drive Fuses

4-1

3.1.3 Internal Main Panel Fuses

4-3

3.2 Mechanical Installation

4-3

Contents

3.2.1 Lifting

4-3

3.2.2 Hoist or Overhead Lift

4-3

3.2.3 Forklift

4-3

3.2.4 Shipping Weights

4-3

3.3 Cooling

4-4

3.4 Electrical Installation

4-5

3.4.1 Component Identification & Customer Connection

4-7

3.4.2 Wire and Cable Access

4-15

3.4.3 Wire Size

4-19

3.4.4 Wire Type Rating

4-20

3.4.5 Terminal Tightening Torques

4-20

3.4.6 Input Line Connection

4-25

3.4.7 Motor Wiring

4-25

3.4.8 Grounding (Earthing)

4-26

3.4.9 Control Wiring

4-26

3.4.10 Serial Communication Bus Connection

4-27

3.4.11 Drive Control Terminals

4-28

4 Start Up
4.1.1 Inspection Prior to Start Up

5-2

4.1.2 Start Up Procedure

5-2

5 Electromechanical Bypass (EMB2) Operation

6-1

5.1.1 Typical Control Connections for Common HVAC Applications

6-1

5.1.2 EMB2 Auto Bypass

6-3

5.1.3 EMB2 Common Run/Stop

6-3

5.1.4 EMB2 Run Permissive

6-4

5.1.5 EMB2 Overload

6-4

5.1.6 EMB2 Safety Interlock

6-5

5.1.7 EMB2 Fire Mode

6-5

5.1.8 EMB2 Fault Reporting

6-5

5.1.9 EMB2 Switches

6-6

6 Electronically Controlled Bypass (ECB) Operation

BAS-SVX49A-EN

5-1

7-1

6.1 Electronically Controlled Bypass (ECB) Operation

7-1

6.1.1 Overview

7-1

6.1.2 ECB Control Card

7-2

6.1.3 ECB Drive or Bypass Selection

7-5

6.1.4 ECB Programming

7-7

Contents

6.1.5 ECB Hand/OFF/Auto

7-8

6.1.6 ECB Mode of Operation

7-8

6.1.7 Bypass Status Word Bit Examples

7-10

6.1.8 ECB Auto Bypass

7-10

6.1.9 ECB Run Permissive

7-11

6.1.10 ECB Overload

7-11

6.1.11 ECB Safety Interlock

7-12

6.1.12 ECB Common Run/Stop

7-12

6.1.13 ECB Advanced Fire Mode

7-13

6.1.14 ECB Fault Reporting

7-13

7 Start Up Troubleshooting
7.1.1 Option Panel Alarm and Warnings

8 Appendix

BAS-SVX49A-EN

8-1
8-1
9-1

8.1.1 Dimensions

9-1

8.1.2 Mechanical Diagrams

9-2

8.1.3 Typical Wiring Diagrams

9-6

Contents

BAS-SVX49A-EN

Introduction

1 Introduction
1.1.1 Purpose of the Manual
This manual is intended to provide detailed information for
the installation and operation of the option panel used in
conjunction with a Trane variable frequency drive (VFD or
drive). To enable efficient handling of the equipment,
requirements are provided for installation of mechanical,
electrical, control wiring, proper grounding, and environmental considerations. Pre-start and start up procedures
are detailed. Also included is a detailed overview of the
option panel bypass function. In addition, identification of
other optional components and their operation and start
up troubleshooting instructions are included. For the
electronically controlled bypass, additional programming
and operation information is provided.

1.1.2 Overview
A variable frequency drive regulates the speed and
operation of an electric motor. The drive is programmable
and offers many features and savings compared to
operating a motor from unregulated line voltage. The
option panel is a protective enclosure in which the drive
and various optional components are assembled and
mounted. The vertical non bypass panel is always
configured with a disconnect switch and fuses to protect
the drive. The vertical bypass panel allows switching
between running the motor from the drive (variable speed)
or across the line input power (constant speed).
The vertical bypass panel comes with one of two control
options:

•
•

The electromechanical bypass (EMB2)
Electronically controlled bypass (ECB)

The EMB2 is operated by a selector switch on the front of
the panel. The EMB2 controls a motor by switching
between drive control, operation in bypass, or off. In
addition, a test selection is available, which disengages the
motor from the drive but keeps the drive operational while
the motor runs in bypass. The switching function activates
contactors to provide power to the motor through the
drive or bypass circuitry, as required.

inputs, and status reporting. The VFD’s logic circuitry is
backed up by an independent panel-mounted power
supply so that, even if the drive loses power, control and
communication functions are maintained. Programming
and display are provided by the keypad. An important
feature of the ECB is the ability to accept commands from
a building automation system (BAS) and to report
operational status in return.
See more detailed descriptions of the EMB2 in 5 Electromechanical Bypass (EMB2) Operation and ECB in 6 Electronically
Controlled Bypass (ECB) Operation of this manual.

1.1.3 Typical Bypass Operation
With contactors M1 and M2 closed and contactor M3
open, the motor is running in drive control. Opening
contactor M2 removes power to the motor but allows the
drive to remain under power. This is referred to as test
mode. With contactors M1 and M2 open and contactor M3
closed, the motor is running in bypass from the line input
power.

1.2 Bypass Circuits
1.2.1 Three-contactor Bypass
The bypass circuit consists of a bypass contactor (M3)
interlocked with a drive output contactor (M2), a drive
input contactor (M1), and an overload relay. For the EMB2,
a door mounted Drive/OFF/Bypass/Test Selector switch is
used to electrically select whether the motor is powered
by the drive, connected to the full speed bypass, or
disconnected from both. The test position applies power
to the motor through the bypass (M3 closed) contactor but
removes power from the drive (M2 open) while keeping
the drive powered (M1 closed). A Pilot light indicates when
in bypass. For the ECB, control selection is made through
the drive keypad by pressing the DRIVE BYPASS key and
selecting from the available options shown. Display data
indicates when in bypass. The circuitry may be supplied
with either an input disconnect switch or an input circuit
breaker.

The ECB also uses contactors to provide power to the
motor through the drive or bypass circuitry. However, the
ECB contains a local processor that interacts with the
drive’s control logic for programmable options, remote

BAS-SVX49A-EN

1-1

Introduction

Contactor

Drive Mode OFF

Bypass

Test Mode

Mode
M1

Closed

Open

Open

Closed

M2

Closed

Open

Open

Open

M3

Open

Open

Closed

Closed

Table 1.1 Contactor Operation

Figure 1.1 Basic Non Bypass Circuit

1.3.4 Basic Fire Mode in Bypass
1.3 Bypass Options
1.3.1 Common Run/Stop with Bypass
Allows a remote signal to initiate operation in either drive
control or bypass depending upon the position of the
bypass selector switch.

1.3.2 Automatic Bypass
This feature automatically transfers the motor from drive to
bypass without operator intervention when a fault
condition trips the drive, after a programmable time-out
period. The VFD’s internal fault circuitry controls this
action. The time delay permits all automatically resettable
faults to clear prior to transfer to bypass. Run permissive or
safety circuit signals override the auto bypass function and
may prevent or delay bypass operation.

This option switches the panel to bypass whenever a
remote fire mode signal is given to the VFD through the
input terminals. In either drive or bypass, fire mode is
intended to ignore common safety and overload inputs for
emergency situations. The motor will continue to run in
bypass until fire mode is removed or the drive, panel, or
motor fails. External safety signals and motor overload are
ignored when in fire mode.

1.3.5 Advanced Fire Mode in Bypass
The advanced fire mode allows for a variety of
programmable responses to an external fire mode
command signal. Bypass options are programmed through
the drive’s fire mode parameters. See 6.1.13 ECB Advanced
Fire Mode.

1.3.6 Overload Protection
1.3.3 Run Permissive in Bypass
With run permissive active, the drive sends a run request
and waits for a remote response before commanding the
motor to start. The response indicates the system is safe to
operate.

1-2

This thermally activated device provides mechanical
overload protection for the motor while in bypass
operation. It measures motor current and is set to the full
load amps (FLA) of the motor. A 1.2 x FLA service factor is
built-in and maintained, meaning that should the motor
current increase above that value, the overload will
calculate the level of increase to activate timing for the trip
function. The higher the current draw, the quicker the trip
response. The overload provides Class 20 motor protection.

BAS-SVX49A-EN

Introduction

1.4 Bypass Platform Configurations
The two bypass platform configurations are ECB and EMB2.
The features available as options with each platform are
listed in Table 1.2. The ECB, also listed below, has all option
features available. See 5 Electromechanical Bypass (EMB2)
Operation for additional details on the EMB2 and
6 Electronically Controlled Bypass (ECB) Operation for the
ECB.

Control Features

EMB2

Safety Interlock

X

ECB
X

Common Start / Stop

X

X

Automatic Bypass

X

X

Run Permissive

X

X

Basic Fire Mode

X

X

Advanced Fire Mode

X

Serial Communication

X

Table 1.2 Bypass Configurations

Figure 1.2 Basic Bypass Circuit

1.5.1 Control Transformer
1.5 Switch Mode Power Supply
The VFD’s logic circuitry is backed up by an independent
panel-mounted switch mode power supply so if the drive
loses power, control and communication functions are
maintained. The SMPS converts three-phase AC input
power to 24 V DC control power. Since the SMPS draws
power from all three phases, it offers immunity protection
from most phase-loss and brown-out conditions. The SMPS
is internally protected from short circuit on its output and
three board-mounted fuses provide additional protection.
The SMPS is not designed for external use and may take
up to 5 sec. to initialize at power-up. The SMPS will
maintain a 24 V DC output with a low input line voltage.
The 200 Volt SMPS will maintain the 24 V DC output with
a line voltage as low as 150 V AC and the 600 V SMPS to
335 V AC. Refer to Figure 1.2.

BAS-SVX49A-EN

A control transformer is included on larger horsepower
units where the contactor coils are AC. The control
transformer steps down the line input voltage to 120V AC.
The coils of AC contactors are isolated from the Switch
Mode Power Supply via relays.

1.6 Disconnects
1.6.1 Main Disconnect
The main disconnect removes line input power to the
drive and bypass. A main disconnect is available in four
options.

•

Fused disconnect. Two-position (ON/OFF) rotary
switch, padlock compatible, with three fuses, one
on each phase, built into the switch. For safety,
the switch must be in the OFF position before

1-3

Introduction

the option panel door can be opened. (Bypass
panel only.)

•

Disconnect without fuses. For user-supplied fuses
option. (Bypass panel only.)

•

Main circuit breaker. A thermal/ magnetic current
interrupt device using an ON/TRIP/OFF/RESET
switch. When in the ON position, a trip fault
removes power from the drive/bypass circuit and
the switch moves to the TRIP setting. The switch
must be moved to the RESET position
momentarily after the fault has been cleared to
reset the circuit breaker. (Bypass panel only.)

•

Main Disconnect with drive fuses. Non-bypass
panel two-position (ON/OFF) rotary switch that
disconnects the main AC line power to the drive
only.

1.6.2 Mode Selector Switch
The mode selector switch is used for 3-contactor bypass
on EMB2 units. The selector switch allows the operator to
select from four modes of operation.
Drive mode: When drive mode is selected, the M1 and M2
contactors are closed allowing power to flow in and out of
the drive to the motor.
Off mode: This mode opens all contactors removing any
power to the motor.
Bypass mode:When bypass mode is selected, the M3
contactor closes and allows the motor to run directly from
the input line power.
Test mode:Test mode closes the M1 and M3 contactors
and allows the motor to be powered by the input line
power. This also allows the drive to power up without
being connected to the motor. Refer to Figure 1.2.

1-4

BAS-SVX49A-EN

Introduction

1.6.3 Panel Configurations
The TR 200 Drive Series comes in two panel enclosure types. One is the non bypass and the other is the bypass. See
Table 1.3 for descriptions and available options.
Non bypass

Bypass

Drive plus both of the following:

Drive with bypass:

1. Fuses

1. Fuses

2. Disconnect

2. Disconnect/Circuit Breaker
3. Contactors
4. Power Supply
5. Control Module

Table 1.3 Tier Definitions and Features

BAS-SVX49A-EN

1-5

Introduction

1.6.4 Panel Voltage and Frame Ratings
Table 1.4Table 1.4 defines the voltage and hp ratings of the frames sizes for the panel. See 8 Appendix for overall and
mounting dimensions.
Panel P2

Bypass

Non Bypass

(B3 - Drive)

TR200

TR200

Volts VAC

HP (KW)

208 & 230

7.5 (5.5) - 15 (11)

7.5 (5.5) - 15 (11)

460 & 600

15 (11) - 25 (18.5)

15 (11) - 25 (18.5)

Panel P3

Bypass

Non Bypass

(B4 - Drive)

TR200

TR200

Volts VAC

HP (KW)

208

20 (15)

230

20 (15) - 25 (18.5)

460 & 600

30 (22) - 50 (37)

30 (22) - 50 (37)

Panel P4

Bypass

Non Bypass

(C3 - Drive)

TR200

20 (15) - 25 (18.5)

TR200

Volts VAC

HP (KW)

208

25 (18.5)

230

30 (22) - 40 (30)

460 & 600

60 (45) - 75 (55)

60 (45) - 75 (55)

Panel P5

Bypass

Non Bypass

(C4 - Drive)

TR200

30 (22) - 40 (30)

TR200

Volts VAC

HP (KW)

208 & 230

50 (37) - 60 (45)

50 (37) - 60 (45)

460 & 600

100 (75) - 125 (90)

100 (75) - 125 (90)

Table 1.4 Panel Voltage and Frame Ratings

1.7 Power Component Functions
1.7.1 Power Fusing
For main panel power fuses, only use the specified fuse or
an equivalent replacement. For drive fuses only use the
specified fuse. See the fuse ratings label on the inside
cover of the unit or Table 3.2Table 3.2, Table 3.3Table 3.3,
Table 3.4Table 3.4 and Table 3.5Table 3.5.
Main fusing
Main fuses are located ahead of the drive and bypass.
Main fuses are designed to protect the circuitry within the
bypass panel but is not adequate to protect the drive.
Main fuses are dual-element, time-delay types and mount
inside the bypass enclosure.

1-6

Drive fusing
Drive fuses are located ahead of the drive and are a fastacting type. Drive fuses are standard in all bypass and nonbypass panels.
5,000 or 100,000 amp SCCR
The bypass panel supplied with a non fusible Main
Disconnect Switch is 5,000 amps short-circuit current rating
(SCCR). The bypass panel supplied with a Fusible
disconnect or circuit breaker is 100,000 amp SCCR. The
non bypass panel supplied with a non-fusible Main
Disconnect is 100,000 amp SCCR. See the panel label for
SCCR rating.

NOTE!
The 600 V circuit breaker option is 5,000 amp (SCCR).

BAS-SVX49A-EN

Pre-installation

2 Pre-installation
2.1.1 Receiving Inspection
Inspect the packaging and equipment closely when
received. Any indication of careless handling by the carrier
should be noted on the delivery receipt, especially if the
equipment will not be immediately uncrated. Obtain the
delivery person’s signed agreement to any noted damages
for any future insurance claims. Ensure that the model
number and power match the order and intended use for
the drive.
IMPORTANT LOST OR DAMAGED GOODS INSPECT THIS
SHIPMENT IMMEDIATELY UPON ARRIVAL If goods are
received short or in damaged condition, insist on a
notation of the loss or damage across the face of the
freight bill. Otherwise no claim can be enforced against
the transportation company. If concealed loss or damage is
discovered, notify your carrier at once and request an
inspection. This is absolutely necessary. Unless you do this
the carrier will not entertain any claim for loss or damage.
The agent will make an inspection and can grant a
concealed damage notation. If you give the transportation
company a clear receipt for equipment that has been
damaged or lost in transit, you do so at your own risk and
expense.
Trane is willing to assist you to collect claims for loss or
damage, but willingness on our part does not make us
responsible for collection of claims or replacement of
material. The actual filing and processing of the claim is
your responsibility.

2.1.2 Pre-installation Check
1.

Compare panel model number to what was
ordered.

2.

Ensure each of the following are rated for the
same voltage:

•
•
•
•
3.

4.

Drive
Panel
Power line
Motor

Ensure that the panel output rating is equal to or
greater than motor total full load current for full
motor performance.

•

Motor power size and panel must match
for proper overload protection.

•

If panel rating is less than motor; full
motor output cannot be achieved.

Check motor wiring:

•

Any disconnect between drive and
motor should be interlocked to drive
safety interlock circuit to avoid
unwanted drive trips.

•

Do not connect power factor correction
capacitors between the drive and motor.

•

Two speed motors must be wired
permanently for full speed.

•

Y-start, Δ-run motors must be wired
permanently for run.

2.1.3 Installation Site Check

•

Because the option panel relies on the ambient
air for cooling, it is important to observe the
limitations on ambient air temperature. Derating
concerns start above 104°F (40°C) and 3300 feet
(1000m) elevation above sea level.

•

It is important with multiple panels to check wall
strength. Make sure that the proper mounting
screws or bolts are used.

•

Ensure that the wall or floor area for installation
will support the weight of the unit.

•

If construction work continues after the
equipment is mounted, it is important to keep
the interior free from concrete dust and similar

Figure 2.1 Sample Panel Label

BAS-SVX49A-EN

2-1

Pre-installation

dirt. If the unit does not have power applied to it,
supply a protective covering. It is important to
ensure that the components stay as clean as
possible. It may be necessary to clean the interior
once construction is completed.

•

Keep drawings and manuals accessible for
detailed installation and operation instructions. It
is important that the manuals be available for
equipment operators.

2.2 Harsh Environments

NOTE!
The mechanical and electrical components within the
option panel can be adversely affected by the
environment. The effects of contaminants in the air, either
solid, liquid, or gas, are difficult to quantify and control.

2.2.1 Airborne Liquids
Liquids in the air can condense in components. Water
carried in the air is easily measured as relative humidity,
but other vapors are often more difficult to measure or
control. Steam, oil and salt water vapor may cause
corrosion of components. In such environments, use TYPE
12 enclosures to limit the exchange of outside air into the
option enclosure. Extremely harsh environments may
require a higher level of protection.

2.2.2 Airborne Solids
Particles in the air may cause mechanical, electrical or
thermal failure in components. A TYPE 1 enclosure
provides a reasonable degree of protection against falling
particles, but it will not prevent the fan from pulling dirty
air into the enclosure.

2.2.3 Corrosive Chemicals
In environments with high temperatures and humidity,
corrosive gases such as sulfur, nitrogen and chlorine
compounds cause corrosion to occur in components.
Indications of corrosion are blackened copper or rust on
steel or oxidized aluminum. In such environments, it is
recommended that the equipment be mounted in a
cabinet with fresh air ventilation and that corrosive
compounds be kept away. A non-ventilated cabinet fitted
with an air conditioner as a heat exchanger may be used.
Conformal coated circuit boards may be specified to
reduce the corrosive effects of a harsh environment.

2-2

BAS-SVX49A-EN

Installation

3 Installation
3.1.1 Tools Required

TOOLS
Spreader bar capable of lifting up to 750 lbs.

In addition to the standard tool kit, the tools in Table 3.1
are recommended for installation of the option panel.

Max diameter 0.5 in.
Forklift, crane, hoist or other lifting device capable of handling
up to 750 lbs. (Qualified device operator available for operating
the equipment.)
Metric Socket Set: 7 - 19mm
Socket Extensions: 4, 6, and 12 inch
Torx driver set: T10 - T40
Torque wrench: 6 - 375 lbs-in
Allen Wrenches:1/8, 3/16, 1/4, & 5/16 inches
Metric or English wrenches: 7 - 19mm
Table 3.1 Tools Required

3.1.2 Drive Fuses
To maintain UL, the drive fuses should be replaced only with the fuses specified in , , , and . If an alternate drive fuse is
desired please consult the factory. See the specifications label inside the cover of the unit for acceptable replacement drive
fuses. A sample of this data can be seen in Table 3.6
208 V AC
HP (KW)

UL Motor

Panel (TR200) Non Bypass

Main Fuse (TR200)

Drive Fuse (TR200)

Transformer Fuse (TR200)

Current

& Bypass

Bussman

Bussman

Bussman

LPJ-40-SP

JJN-50

LPJ-50-SP

JJN-50

7.5 (5.5)

24,2

10 (7.5)

30,8

15 (11)

46,2

20 (15)

59,4

25 (18.5)

74,8

30 (22)

88

40 (30)

114

50 (37)

143

60 (45)

169

P2
P3
P3 - Non Bypass P4 Bypass
P4
P5

LPJ-70-SP

JJN-60

LPJ-90-SP

JJN-80

LPJ-125-SP

JJN-125

LPJ-150-SP

JJN-125

LPJ-175-SP

JJN-150

LPJ-250-SP

JJN-200

FNQ-R-1.25

LPJ-250-SP

JJN-250

FNQ-R-1.25

Table 3.2 Drive Fuses 208 V

BAS-SVX49A-EN

3-1

Installation

230 V AC
HP (KW)

UL Motor

Panel (TR200) Non Bypass

Main Fuse (TR200)

Drive Fuse (TR200)

Transformer Fuse (TR200)

Current

& Bypass

Bussman

Bussman

Bussman

LPJ-35-SP

JJN-50

7.5 (5.5)

22

10 (7.5)

28

15 (11)

42

20 (15)

54

25 (18.5)

68

30 (22)

80

40 (30)

104

50 (37)

130

60 (45)

154

P2

P3
P4
P5

LPJ-45-SP

JJN-50

LPJ-70-SP

JJN-60

LPJ-90-SP

JJN-80

LPJ-100-SP

JJN-125

LPJ-125-SP

JJN-125

LPJ-150-SP

JJN-150

LPJ-200-SP

JJN-200

FNQ-R-1.25

LPJ-250-SP

JJN-250

FNQ-R-1.25

Table 3.3 Drive Fuses 230 V
460 V AC
HP (KW)
15 (11)

UL Motor

Panel (TR200) Non

Main Fuse (TR200)

Drive Fuse (TR200)

Transformer Fuse (TR200)

Current

Bypass & Bypass

Bussman

Bussman

Bussman

LPJ-35-SP

JJS-40

21

20 (15)

27

25 (18.5)

34

30 (22)

40

40 (30)

52

50 (37)

65

60 (45)

77

75 (55)

96

100 (75)

124

125 (90)

156

P2

P3

P4
P5

LPJ-40-SP

JJS-40

LPJ-50-SP

JJS-50

LPJ-60-SP

JJS-60

LPJ-80-SP

JJS-80

LPJ-100-SP

JJS-100

LPJ-125-SP

JJS-125

LPJ-150-SP

JJS-150

LPJ-200-SP

JJS-200

FNQ-R-0.60

LPJ-250-SP

JJS-250

FNQ-R-0.60

Table 3.4 Drive Fuses 460 V
600 V AC
HP (KW)

UL Motor

Panel (TR200) Non

Main Fuse (TR200)

Drive Fuse (TR200)

Transformer Fuse (TR200)

Current

Bypass & Bypass

Bussman

Bussman

Bussman

LPJ-30-SP

JJS-35

LPJ-35-SP

JJS-35

15 (11)

17

20 (15)

22

25 (18.5)

27

LPJ-45-SP

JJS-45

30 (22)

32

LPJ-50-SP

JJS-50

40 (30)

41

LPJ-60-SP

JJS-60

P2

P3

50 (37)

52

LPJ-80-SP

JJS-80

60 (45)

62

LPJ-100-SP

JJS-100

75 (55)

77

LPJ-125-SP

JJS-125

100 (75)

99

125 (90)

125

P4
P5

LPJ-150-SP

JJS-150

FNQ-R-0.50

LPJ-200-SP

JJS-175

FNQ-R-0.50

Table 3.5 Drive Fuses 600 V

3-2

BAS-SVX49A-EN

Installation

3.1.3 Internal Main Panel Fuses
Use only the specified fuse or an equivalent replacement for the internal main fuses. See the specifications label inside the
cover of the unit for acceptable replacement main fuses. A sample of this can be seen in Table 3.6.
Fuse

Description

Manufacturer

Part Number/Size

F13A & C

Primary Transformer

Bussmann

FNQ-R-0.50
LPJ-30-SP

F15A, B, & C

Main Fuses

Bussmann

F16A, B, & C

Drive Fuses

Bussmann

JJS-35

F900, F901,F902

SMPS - Power Supply

Bussmann

FWH-020A6F, 500V

Table 3.6 Sample Fuse Rating Label

3.2 Mechanical Installation
3.2.1 Lifting

WARNING
Heavy Objects!
Do not use cables (chains or slings) except as shown. Each
of the cables (chains or slings) used to lift the unit must be
capable of supporting the entire weight of the unit. Lifting
cables (chains or slings) may not be of the same length.
Adjust as necessary for even unit lift. Other lifting
arrangements may cause equipment or property-only
damage. Failure to properly lift unit could result in death
or serious injury. See details below.

WARNING
Check the weight of unit to determine the safety of the
lifting method. Ensure that the lifting device is suitable for
the task. If necessary, plan for a hoist, crane or forklift with
appropriate rating to move the units.
Follow recommendations below. failure to do so could
result in death or serious injury.

3.2.3 Forklift

•

Only a competent lift operator with additional
support personnel should attempt moving the
unit.

•

Carefully position forklift and ensure stability prior
to lift.

3.2.4 Shipping Weights
Weights listed in Table 3.7 are approximate for base units.
Options can add or reduce weight of unit. Weights listed
are in lbs.
Frame

Non Bypass Panel

P2

36

Bypass Panel
84

P3

66

106

P4

106

167

P5

155

248

Table 3.7 Approximate Shipping Weights

3.2.2 Hoist or Overhead Lift

•

Use a solid steel spreader bar for lifting. Slide the
spreader bar through the two (2) lifting holes on
the panel. Lifting rings are 0.59in (15mm) in
diameter (see Figure 3.1). If VFD mounting screws
interfere with the spreader bar, lifting hooks can
be used instead of the lifting bar.

•

Connect the spreader bar to a hoist or other
lifting device.

•

Carefully lift the unit and secure it to the wall.
Refer to 8 Appendix for dimensional drawings to
determine fasteners size and location.

BAS-SVX49A-EN

3-3

Installation

Figure 3.2 Side Cooling Clearance
Figure 3.1 Proper Lifting Method

3.3 Cooling

•
•

Only mount the drive and panel vertically.

•

Most panels may be mounted side-by-side
without additional side clearance. However, the
P2 (B3 frame size) units require 1.5 in. minimum
clearance between units (see Figure 3.2).

•

Top and bottom clearance is required for cooling
(see Figure 3.3). Generally, 2 to 10 inches (50 to
250mm) minimum clearance is required,
depending upon the hp (kW) of the unit. See the
dimensional drawings in 8 Appendix for specific
requirements.

•

No additional back plate is required for drives
with the bypass and non bypass panels.

Panels rely on the ambient air for cooling. It is
important to observe the limitations on ambient
air temperature. The maximum ambient
temperature for all bypass panels is 40°C and
45°C for non bypass panels. Derating concerns
start above 3300 feet elevation above sea level.

Figure 3.3 Cooling Airflow

3-4

BAS-SVX49A-EN

Installation

3.4 Electrical Installation

WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects
before servicing. Follow proper lockout/tagout procedures
to ensure the power cannot be inadvertently energized.
Failure to disconnect power before servicing could result in
death or serious injury.

WARNING
Proper Field Wiring and Grounding Required!
All field wiring MUST be performed by qualified personnel.
Improperly installed and grounded field wiring poses FIRE
and ELECTROCUTION hazards. To avoid these hazards, you
MUST follow requirements for field wiring installation and
grounding as described in NEC and your local/state
electrical codes. Failure to follow codes could result in
death or serious injury.

WARNING
EQUIPMENT HAZARD!
Rotating shafts and electrical equipment can be hazardous.
It is strongly recommended that all electrical work conform
to all national and local regulations. Installation, start-up
and maintenance should be performed only by qualified
personnel. Failure to follow local regulations could result in
death or serious injury.

•

•
•
•

Motor control equipment and electronic controls
are connected to hazardous line voltages.
Extreme care should be taken to protect against
electrical hazard.
Correct protective grounding of the equipment
must be established. Ground currents are higher
than 3mA.
A dedicated ground wire is required.
Wear safety glasses whenever working on electric
control or rotating equipment.

NOTICE!
Make all power connections with a minimum of 60°C/
140°F rated copper wire.

BAS-SVX49A-EN

WARNING
INDUCED VOLTAGE!
Run output motor cables from multiple drives separately.
Induced voltage from output motor cables run together
can charge equipment capacitors even with the equipment
turned off and locked out. Failure to run output motor
cables separately could result in death or serious injury.

NOTE!
Run input power, motor wiring and control wiring in three
separate metallic conduits or raceways for high frequency
noise isolation. Failure to isolate power, motor and control
wiring could result in less than optimum drive and
associated equipment performance.
NOTE RUN INPUT POWER, MOTOR WIRING AND CONTROL
WIRING IN THREE SEPARATE METALLIC CONDUITS OR
RACEWAYS FOR HIGH FREQUENCY NOISE ISOLATION.
FAILURE TO ISOLATE POWER, MOTOR AND CONTROL
WIRING COULD RESULT IN LESS THAN OPTIMUM DRIVE
AND ASSOCIATED EQUIPMENT PERFORMANCE.

•

Because the motor wiring carries high frequency
electrical pulses, it is important that no other
wires are run together. If the incoming power
wiring is run in the same conduit as the motor
wiring, these pulses can couple electrical noise
back onto the building power grid.

At least three separate conduits must be connected to the
panel (Figure 3.4).

•

Power into the panel (and ground back to the
distribution panel)

•

Power from the panel to the motor and earth
insulated motor ground

•

Control wiring

Control wiring should always be isolated from the high
voltage power wiring.
Avoid getting metal chips into electronics.
Follow the connection procedures as illustrated in the
drawing provided with the unit.

3-5

Installation

Figure 3.4 Power Connections

3-6

BAS-SVX49A-EN

Installation

3.4.1 Component Identification & Customer Connection
Mechanical layout drawings are intended to provide the installer or equipment user with component identification and
location for that specific unit. Figure 3.5 represents a typical layout drawing. Table 3.8 provides definitions for drawing
reference designators. (Not all reference designators are shown.)

Figure 3.5 P2 Bypass Mechanical Layout Diagram

ID

Device

1

24 V DC

Panel 24 V DC SMPS

Definition

ID

Device

15

S1

2

HPC

High Pot Connector

16

TF

3

F13

T1 primary fuse

17

VFD

Definition
Auto Bypass Selector Switch
120 V AC control transformer
Variable frequency drive

4

CB1

Main Circuit Breaker

18

EMB2

Control Module

5

DS1

Main or Drive Disconnect

19

ECB

Control Module

6

F15

Main fuse

20

TB1-C

Terminal block 1 - Control

7

F16

Drive fuse

21

TB1-P

Terminal block 1 - Power

8

GND

Ground terminal

22

PR1

9

keypad

keypad

23

PR2

Control Relay for M2 Contactor

10

M1

Drive Input contactor

24

PR3

Control Relay for M3 Contactor
Under voltage module

Control Relay for M1 Contactor

11

M2

Drive Output contactor

25

UVM

12

M3

Bypass contactor

26

TC

Top Cover

13

OL1

Overload for Motor

27

DH

Disconnect Handle

14

PL1

Bypass indicator light

Table 3.8 Reference Designator Definitions

BAS-SVX49A-EN

3-7

Installation

Figure 3.6 P2 Non Bypass Mechanical Layout Diagram.

See Table 3.8 for reference designator definitions.

3-8

BAS-SVX49A-EN

Installation

Figure 3.7 P3 Bypass Mechanical Layout Diagram.

See Table 3.8 for reference designator definitions.

BAS-SVX49A-EN

3-9

Installation

Figure 3.8 P3 Non Bypass Mechanical Layout Diagram.

See Table 3.8 for reference designator definitions.

3-10

BAS-SVX49A-EN

Installation

Figure 3.9 P4 Bypass Mechanical Layout Diagram.

See Table 3.8 for reference designator definitions.

BAS-SVX49A-EN

3-11

Installation

Figure 3.10 P4 Non Bypass Mechanical Layout Diagram.

See Table 3.8 for reference designator definitions.

3-12

BAS-SVX49A-EN

Installation

Figure 3.11 P5 Bypass Mechanical Layout Diagram.

See Table 3.8 for reference designator definitions.

BAS-SVX49A-EN

3-13

Installation

Figure 3.12 P5 Non Bypass Mechanical Layout Diagram.

See Table 3.8 for reference designator definitions.

3-14

BAS-SVX49A-EN

Installation

3.4.2 Wire and Cable Access

WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects
before servicing. Follow proper lockout/tagout procedures
to ensure the power cannot be inadvertently energized.
Failure to disconnect power before servicing could result in
death or serious injury.

•

Refer to through for wire routing and termination
locations.

•

Removable access knockout covers are provided
for cable connections (see Figure 3.13 and
Figure 3.14).

•

Access holes are provided for input power, motor
leads, and control wiring.

•

Run input power, motor wiring, and control
wiring in three separate conduits for isolation.

Figure 3.13 Bypass Panel Conduit Entry Diagram

NOTE!
IMPORTANT NOTE
RUN INPUT POWER, MOTOR WIRING AND CONTROL
WIRING IN THREE SEPARATE METALLIC CONDUITS OR
RACEWAYS FOR HIGH FREQUENCY NOISE ISOLATION.
FAILURE TO ISOLATE POWER, MOTOR AND CONTROL
WIRING COULD RESULT IN LESS THAN OPTIMUM DRIVE
AND ASSOCIATED EQUIPMENT PERFORMANCE.

•

The drive always resides in the upper section of
the panel. Connections to the ECB and EMB2 are
in this area except on the P2 bypass panels.

•

Power connections are typically towards the
bottom side of the panel.

•

Control wiring should be isolated from power
components inside the unit as much as possible.
Trane has included hardware to allow for the
separation.

•

See the mechanical layout drawings in through
for connection details and recommended wire
routing.

BAS-SVX49A-EN

Figure 3.14 Non Bypass Panel Conduit Entry Diagram

3-15

Installation

Figure 3.15 P2 Panel

Figure 3.16 P3 Panel

3-16

BAS-SVX49A-EN

Installation

Figure 3.17 P4 Panel

BAS-SVX49A-EN

3-17

Installation

Figure 3.18 P5 Panel

3-18

BAS-SVX49A-EN

Installation

3.4.3 Wire Size

WARNING
ELECTROCUTION AND FIRE HAZARDS WITH IMPROPERLY INSTALLED AND GROUNDED FIELD WIRING!
Improperly installed and grounded field wiring poses FIRE & ELECTROCUTION hazards. To avoid these hazards, you MUST
follow requirements for field wiring installation and grounding as described in the National Electrical Codes (NEC) and your
local/state electrical codes. All field wiring MUST be performed by qualified personnel.
Failure to follow these requirements could result in death or serious injury.

NOTE!
Make all power connections with minimum 60 or 75°C/140 or 155°F rated copper wiring for installations in North America.
208 V AC
HP (KW)
7.5 (5.5)

UL Motor Current

Panel (TR200) Non
Bypass & Bypass

24.2

10 (7.5)

30.8

15 (11)

46.2

20 (15)

59.4

25 (18.5)

74.8

30 (22)

88

40 (30)

114

50 (37)

143

60 (45)

169

Maximum Field
Wiring Size Class B
or C
8 AWG

P2
P3
P3 - Non Bypass P4 Bypass
P4
P5

Field Ground Wiring
Size Class B or C

Minimum Temperature
Wire Rating "°C" Copper
Conductor

10 AWG

60

8 AWG

10 AWG

60

4 AWG

10 AWG

60

3 AWG

10 AWG

60

2 AWG

8 AWG

60

2 AWG

8 AWG

60

1/0 AWG

6 AWG

75

3/0 AWG

6 AWG

75

4/0 AWG

6 AWG

75

230 VAC
HP (KW)

UL Motor Current

7.5 (5.5)

22

10 (7.5)

28

15 (11)

42

20 (15)

54

25 (18.5)

68

30 (22)

80

40 (30)
50 (37)
60 (45)

154

Panel (TR200) Non
Bypass & Bypass

Maximum Field
Wiring Size Class B
or C

Field Ground Wiring
Size Class B or C

Minimum Temperature
Wire Rating "Degree C"
Copper Conductor

10 AWG

10 AWG

60

8 AWG

10 AWG

60

6 AWG

10 AWG

60

4 AWG

10 AWG

60

3AWG

8 AWG

60

3 AWG

8 AWG

60

104

1 AWG

6 AWG

75

130

2/0 AWG

6 AWG

75

3/0 AWG

6 AWG

75

P2

P3

P4

P5

Table 3.9 Wire Size Chart, 208 and 230 V

BAS-SVX49A-EN

3-19

Installation

460 VAC
HP (KW)

UL Motor Current

15 (11)

21

20 (15)

27

25 (18.5)
30 (22)

Panel (TR200) Non Bypass
& Bypass

Maximum Field

Field Ground

Minimum Temperature

Wiring Size Class B

Wiring Size Class B

Wire Rating "°C" Copper

or C

or C

Conductor

10 AWG

10 AWG

60

8 AWG

10 AWG

60

34

6 AWG

10 AWG

60

40

6 AWG

10 AWG

60

4 AWG

10 AWG

60

3 AWG

8 AWG

60

40 (30)

52

50 (37)

65

60 (45)

77

75 (55)

96

100 (75K)

124

125 (90)

156

P2

P3

P4
P5

1 AWG

8 AWG

60

1 AWG

8 AWG

60

2/0 AWG

6 AWG

75

3/0 AWG

6 AWG

75

600 VAC
HP (KW)

UL Motor Current

15 (11)

17

20 (15)

22

25 (18.5)
30 (22)
40 (30)

41

Panel (TR200) Non Bypass
& Bypass

Maximum Field

Field Ground

Minimum Temperature

Wiring Size Class B

Wiring Size Class B

Wire Rating "Degree C"
Copper Conductor

or C

or C

10 AWG

10 AWG

60

10 AWG

10 AWG

60

27

8 AWG

10 AWG

60

32

8 AWG

10 AWG

60

6 AWG

10 AWG

60
60

P2

P3

50 (37)

52

4 AWG

10 AWG

60 (45)

62

3 AWG

8 AWG

60

75 (55)

77

1 AWG

8 AWG

60

1 AWG

8 AWG

60

2/0 AWG

6 AWG

75

100 (75)

99

125 (90)

125

P4
P5

Table 3.10 Wire Size Chart 460 and 600 V

3.4.4 Wire Type Rating

•

The wire style rating specifications are provided inTable 3.9 and Table 3.10

3.4.5 Terminal Tightening Torques

•
•

3-20

Tighten all connections to the torque specifications provided in Table 3.11 and Table 3.13
The torque specifications are also located on the tightening torque and wire rating label inside the panel cover.
See Table 3.15 for a sample of the torque and wire rating data.

BAS-SVX49A-EN

BAS-SVX49A-EN

200 (22.5)

200 (22.5)

200 (22.5)

200 (22.5)

70 (7.9)

55 (6.2)

Disconnect Switch

*Note 1

124/212.4 (14/24)

88.5 (10)

88.5 (10)

40 (4.5)

40 (4.5)

40 (4.5)

16 (1.8)

16 (1.8)

16 (1.8)

Torque lb-in (N-m)

Fusible UL98 L1,

7 (0.8)

200 (22.5)

200 (22.5)

200 (22.5)

200 (22.5)

55 (6.2)

18 (2)

18 (2)

7 (0.8)

30 (3.3)

500 (56.5)

500 (56.5)

200 (22.5)

200 (22.5)

200 (22.5)

120 (13.5)

120 (13.5)

30 (3.3)

274 (31)

274 (31)

50 (5.6)

50 (5.6)

50 (5.6)

50 (5.6)

45 (5)

40 (4.5)

40 (4.5)

in (N-m)

Circuit Breaker L1,
L2, & L3 Torque lb-

Bypass
Disconnect Switch

Input

L1, L2, & L3 Torque L2, & L3 Torque lblb-in (N-m)
in (N-m)

Motor T1, T2, & T3 (w/o Fuses) UL508A

Output

208 VAC

275 (31)

275 (31)

275 (31)

50 (5.6)

50 (5.6)

50 (5.6)

50 (5.6)

24 (2.7)

24 (2.7)

T3 Torque lb-in (Nm)

Overload T1, T2, &

Single Motor

Output

* Note 1 - Tightening of terminals for different cable dimensions x/y, where x <0.147in sq [95mm sq] and y>0.147 in sq [95mm sq]

P5

Table 3.11 Tightening Torques, 208 V

60 (45)

50 (37)

40 (30)

P4

P4 - Bypass

30 (22)

P3 - Non Bypass

20 (15)

25 (18.5)

55 (6.2)

55 (6.2)

15 (11)

55 (6.2)

P2

Torque lb-in (N-m)

Drive Disconnect
Switch L1, L2, & L3

10 (7.5)

& Bypass

7.5 (5.5)

HP (KW)

Panel (TR200) Non Bypass

Input

Non Bypass
Ground Wire

40 (4.5)

40 (4.5)

40 (4.5)

40 (4.5)

40 (4.5)

40 (4.5)

40 (4.5)

40 (4.5)

40 (4.5)

Torque lb-in (N-m)

Installation

3-21

3-22

20 (15)

P5

P4

P3

Table 3.12 Tightening Torques, 230 V

60 (45)

50 (37)

40 (30)

30 (22)

25 (18.5)

40 (4.5)

70 (7.9)

200 (22.5)

200 (22.5)

200 (22.5)
124 (14)

88.5 (10)

88.5 (10)

40 (4.5)

40 (4.5)

55 (6.2)

70 (7.9)

16 (1.8)

16 (1.8)

200 (22.5)

200 (22.5)

200 (22.5)

55 (6.2)

18 (2)

18 (2)

18 (2)

7 (0.8)

7 (0.8)

L1, L2, & L3 Torque
lb-in (N-m)

16 (1.8)

(w/o Fuses) UL508A

Torque lb-in (N-m)

Disconnect Switch

230 V AC

Motor T1, T2, & T3

Output

55 (6.2)

55 (6.2)

15 (11)

55 (6.2)

P2

Torque lb-in (N-m)

Drive Disconnect
Switch L1, L2, & L3

10 (7.5)

Bypass

Non Bypass &

7.5 (5.5)

HP (KW)

Panel (TR200)

Input

Non Bypass

Bypass

500 (56.5)

200 (22.5)

200 (22.5)

200 (22.5)

120 (13.5)

120 (13.5)

120 (13.5)

30 (3.3)

30 (3.3)

L3 Torque lb-in (N-m)

274 (31)

274 (31)

50 (5.6)

50 (5.6)

50 (5.6)

50 (5.6)

45 (5)

40 (4.5)

40 (4.5)

(N-m)

Disconnect Switch
Circuit Breaker L1,
Fusible UL98 L1, L2, & L2, & L3 Torque lb-in

Input

275 (31)

275 (31)

50 (5.6)

50 (5.6)

50 (5.6)

50 (5.6)

50 (5.6)

24 (2.7)

24 (2.7)

T3 Torque lb-in (Nm)

Overload T1, T2, &

Single Motor

Output
Ground Wire

40 (4.5)

40 (4.5)

40 (4.5)

40 (4.5)

40 (4.5)

40 (4.5)

40 (4.5)

40 (4.5)

40 (4.5)

Torque lb-in (N-m)

Installation

BAS-SVX49A-EN

BAS-SVX49A-EN

P5

Table 3.13 Tightening Torques, 460V

125 (90)

100 (75)

200 (22.5)

200 (22.5)

200 (22.5)

70 (7.9)

P4

40 (4.5)

55 (6.2)

50 (37)

60 (45)

75 (55)

40 (4.5)

55 (6.2)

40 (30)

16 (1.8)

55 (6.2)

124 (14)

124 (14)

88.5 (10)

88.5 (10)

40 (4.5)

55 (6.2)

30 (22)

P3

16 (1.8)
16 (1.8)

25 (18.5)

55 (6.2)
55 (6.2)

P2

Output

460 VAC
Input

Bypass
Output

200 (22.5)

200 (22.5)

200 (22.5)

55 (6.2)

18 (2)

18 (2)

18 (2)

7 (0.8)

7 (0.8)

7 (0.8)

500 (56.5)

200 (22.5)

200 (22.5)

200 (22.5)

120 (13.5)

120 (13.5)

30 (3.3)

30 (3.3)

30 (3.3)

30 (3.3)

274 (31)

274 (31)

50 (5.6)

50 (5.6)

50 (5.6)

50 (5.6)

45 (5)

45 (5)

40 (4.5)

40 (4.5)

275 (31)

275 (31)

50 (5.6)

50 (5.6)

50 (5.6)

50 (5.6)

50 (5.6)

24 (2.7)

24 (2.7)

24 (2.7)

Disconnect Switch
Disconnect Switch
Single Motor
Drive Disconnect
Circuit Breaker L1,
Motor T1, T2, & T3 (w/o Fuses) UL508A Fusible UL98 L1, L2,
Overload T1, T2, &
Switch L1, L2, & L3
L2, & L3 Torque lbTorque lb-in (N-m) L1, L2, & L3 Torque & L3 Torque lb-in (NT3 Torque lb-in (NTorque lb-in (N-m)
in (N-m)
lb-in (N-m)
m)
m)

15 (11)

& Bypass

20 (15)

HP (KW)

Panel (TR200) Non Bypass

Input

Non Bypass
Ground Wire

40 (4.5)

40 (4.5)

40 (4.5)

40 (4.5)

40 (4.5)

40 (4.5)

40 (4.5)

40 (4.5)

40 (4.5)

40 (4.5)

Torque lb-in (N-m)

Installation

3-23

3-24

P5

Table 3.14 Tightening Torques, 600V

125 (90)

100 (75)

P4

200 (22.5)

200 (22.5)

70 (7.9)

55 (6.2)

60 (45)

75 (55)

55 (6.2)

55 (6.2)

40 (30)

P3

30 (22)

50 (37)

55 (6.2)
55 (6.2)

25 (18.5)

55 (6.2)

20 (15)

P2

Output

600 VAC
Input

Bypass
Output

124 (14)

124 (14)

88.5 (10)

88.5 (10)

40 (4.5)

40 (4.5)

40 (4.5)

16 (1.8)

16 (1.8)

16 (1.8)

200 (22.5)

200 (22.5)

55 (6.2)

55 (6.2)

18 (2)

18 (2)

7 (.79)

7 (.79)

7 (.79)

7 (.79)

200 (22.5)

200 (22.5)

200 (22.5)

120 (13.5)

120 (13.5)

30 (3.3)

30 (3.3)

30 (3.3)

30 (3.3)

17 (1.92)

200 (22.5)

200 (22.5)

62 (7)

62 (7)

62 (7)

62 (7)

62 (7)

62 (7)

62 (7)

62 (7)

275 (31)

275 (31)

50 (5.6)

50 (5.6)

50 (5.6)

50 (5.6)

50 (5.6)

24 (2.7)

24 (2.7)

24 (2.7)

40 (4.5)

40 (4.5)

40 (4.5)

40 (4.5)

40 (4.5)

40 (4.5)

40 (4.5)

40 (4.5)

40 (4.5)

40 (4.5)

Ground Wire
Disconnect Switch Disconnect Switch
Single Motor
Drive Disconnect
Circuit Breaker L1,
Torque
lb-in (N-m)
Motor T1, T2, & T3 (w/o Fuses) UL508A Fusible UL98 L1, L2,
Overload T1, T2, &
Switch L1, L2, & L3
L2, & L3 Torque
Torque lb-in (N-m) L1, L2, & L3 Torque & L3 Torque lb-in
T3 Torque lb-in
Torque lb-in (N-m)
lb-in (N-m)
lb-in (N-m)
(N-m)
(N-m)
55 (6.2)

Bypass

15 (11)

HP (KW)

Panel (TR200) Non Bypass &

Input

Non Bypass

Installation

BAS-SVX49A-EN

Installation

Field Connection

Tightening Torque lb-in (N-m)

Temperature & Type Rating

L1, L2, L3/Ground

25 (2.8) 25 (2.8)

Use 75°C Copper Conductor

2T1, 2T2, 2T3/Ground

25 (2.8) 25 (2.8)

Use 75°C Copper Conductor

TB1

25 (2.8) 25 (2.8)

Use 75°C Copper Conductor

Table 3.15 Sample Tightening Torque and Wire Rating Label

3.4.6 Input Line Connection

WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects
before servicing. Follow proper lockout/tagout procedures
to ensure the power cannot be inadvertently energized.
Failure to disconnect power before servicing could result in
death or serious injury.

CAUTION
RUN INPUT POWER, MOTOR WIRING AND CONTROL
WIRING IN THREE SEPARATE METALLIC CONDUITS OR
RACEWAYS FOR HIGH FREQUENCY NOISE ISOLATION.
FAILURE TO ISOLATE POWER, MOTOR AND CONTROL
WIRING COULD RESULT IN LESS THAN OPTIMUM DRIVE
AND ASSOCIATED EQUIPMENT PERFORMANCE.

•

Connect 3-phase AC input power wire to
terminals L1, L2, and L3. See the connection
drawing inside the cover of the unit.

•

Depending on the configuration of the
equipment, input power may be connected to a
circuit breaker or disconnect switch.

•

Torque terminals in accordance with the
information provided inTable 3.11 and Table 3.13
on the label inside the panel cover.

•

Use with Isolated Input Source. Many utility
power systems are referenced to earth ground.
Although not as common, the input power may
be an isolated source. All drives may be used
with an isolated input source as well as with
ground reference power lines.

WARNING
INDUCED VOLTAGE!
Run output motor cables from multiple drives separately.
Induced voltage from output motor cables run together
can charge equipment capacitors even with the equipment
turned off and locked out. Failure to run output motor
cables separately could result in death or serious injury.

NOTE!
Run input power, motor wiring and control wiring in three
separate metallic conduits or raceways for high frequency
noise isolation. Failure to isolate power, motor and control
wiring could result in less than optimum drive and
associated equipment performance.

CAUTION
RUN INPUT POWER, MOTOR WIRING AND CONTROL
WIRING IN THREE SEPARATE METALLIC CONDUITS OR
RACEWAYS FOR HIGH FREQUENCY NOISE ISOLATION.
FAILURE TO ISOLATE POWER, MOTOR AND CONTROL
WIRING COULD RESULT IN LESS THAN OPTIMUM DRIVE
AND ASSOCIATED EQUIPMENT PERFORMANCE.

3.4.7 Motor Wiring

WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects
before servicing. Follow proper lockout/tagout procedures
to ensure the power cannot be inadvertently energized.
Failure to disconnect power before servicing could result in
death or serious injury.

BAS-SVX49A-EN

3-25

Installation

•

Connect the 3-phase motor wiring to bypass
terminals T1 (U), T2 (V), and T3 (W). See the
connection drawing inside the cover of the unit.

•

Connect the ground wire directly to a reliable
earth ground. Grounding studs are provided on
the back plate of the panel for grounding.

•

Depending on the configuration of the
equipment, motor wiring may be connected to
overload or terminal block.

•

Do not use conduit connected to the panel as a
replacement for a ground wire.

•

•

Torque terminals in accordance with the
information provided on the connection diagram
inside the cover of the unit.

A high strand count ground wire is preferred for
dissipating high frequency electrical noise.

•

Keep the ground wire connections as short as
possible.

•

Ground the motor to the panel with insulated
wire run inside metal conduit with motor leads.

•

Motor wiring should never exceed the following
maximum distances: 300m (1000 ft) for
unshielded, 150m (500 ft) for shielded.

•

Motor wiring should always be as short as
practical.

3.4.8 Grounding (Earthing)

WARNING
GROUNDING HAZARD!
for operator safety, it is important to ground the option
panel properly. Failure to do so could result in death or
serious injury.

WARNING
ELECTROCUTION AND FIRE HAZARDS WITH
IMPROPERLY INSTALLED AND GROUNDED FIELD
WIRING!
Improperly installed and grounded field wiring poses FIRE
& ELECTROCUTION hazards. To avoid these hazards, you
MUST follow requirements for field wiring installation and
grounding as described in the National Electrical Codes
(NEC) and your local/state electrical codes. All field wiring
MUST be performed by qualified personnel. Failure to
follow these requirements could result in death or serious
injury.

NOTE!
It is the responsibility of the user or certified electrical
installer to ensure correct grounding (earthing) of the
equipment in accordance with national and local electrical
codes and standards.

•

Follow all local and national codes for proper
electrical equipment grounding (earthing).

•

Correct protective grounding of the equipment
must be established. Ground currents are higher
than 3 mA.

•

A dedicated ground wire is required for input
ground.

3-26

3.4.9 Control Wiring

WARNING
Electrocution and Fire Hazards with Improperly Installed
and Grounded
Field Wiring!
Improperly installed and grounded field wiring poses FIRE
& ELECTROCUTION hazards. To avoid these hazards, you
MUST follow requirements for field wiring installation and
grounding as described in the National Electrical Codes
(NEC) and your local/state electrical codes. All field wiring
MUST be performed by qualified personnel. Failure to
follow these requirements could result in death or serious
injury.
Detailed instructions for terminal connection, control
wiring installation, and operation are shown in Section 5
Electromechanical Bypass (EMB2) Operation and Section 6
Electronically Controlled Bypass (ECB) Operation.

•

It is recommended that control wiring is rated for
600 V for 480 V and 600 V drives and 300 V for
200-240 V drives.

•

Isolate control wiring from high power
components in the drive.

•

See 3.4.2 Wire and Cable Access for details.

BAS-SVX49A-EN

Installation

130BX224.10

Programming

1

Serial communication point maps, parameter settings, and
other details for bypass option functionality are included in
the serial communication materials supplied with the unit.

2

3
4
Figure 3.19 Control Terminals Location

1.

EIA-485 terminal

2.

Jumper wire

3.

Control terminals

4.

Grounded restraining clips

3.4.10 Serial Communication Bus
Connection
The ECB reports serial communication data to host systems
through the drive. Connection to the serial communication
network is made either through the EIA-485 terminals on
the drive (see figure above) or, for other protocols,
terminals located on the communication option card. For
option card connection, see the option card instructions
provided with the unit.

•

For ECB serial communication protocols using the
EIA-485 terminals, make connections in the
following manner.

NOTE!
It is recommended to use braided-shielded, twisted-pair
cables to reduce noise between conductors.
1.

Connect signal wires to terminal (+) 68 and
terminal (-) 69 on control terminals of drive. (See
the drive support materials for wire size and
tightening torque.)

2.

Terminate shield to grounded restraining clip
provided by stripping wire insulation at point of
contact.

3.

If shielded cabling is used, do not connect the
end of the shield to terminal 61.

BAS-SVX49A-EN

3-27

Installation

3.4.11 Drive Control Terminals

•

Connector 1 provides four digital inputs; two
selectable digital inputs or outputs, 24 V DC
terminal supply voltage, and a common for
optional customer supplied 24 V DC voltage.

•

Serial communications use EIA-485 connector 2
with terminal 68 (+) and 69 (-).

•

Connector 3 provides two analog inputs, one
analog output, 10 V DC supply voltage, and
commons for the inputs and output.

•

A USB port, connector 4, is also available for use
with the available on the Trane website.

•

Also provided are two Form C relay outputs that
are in various locations depending upon the drive
configuration and size.

130BX231.10

Definitions of the drive terminals are summarized in
Table 3.16.

Figure 3.20 Removable Drive Connectors and Terminals

Terminal No.

Function

01, 02, 03, 04,

Form-C relay output. Useable for AC or DC voltage and resistive or inductive loads. See drive support materials for

05, 06

details on voltage and current ratings and relay location.

12, 13

24 V DC digital supply voltage. Useable for digital inputs and external transducers. To use the 24 V DC for digital input

18, 19, 32, 33

Digital inputs. Selectable for NPN or PNP function in parameter 5-00. Default is PNP.

27, 29

Digital inputs or outputs. Programmable for either. Parameter 5-01 for terminal 27 and 5-02 for 29 selects input/output

20

Common for digital inputs. To use for digital input common, program parameter 5-00 for NPN operation.

39

Common for analog output.

common, program parameter 5-00 for PNP operation. Maximum output current is 200 mA total for all 24V loads.

function. Default setting is input.

42

Analog output. Programmable for various functions in parameter 6-5*. The analog signal is 0 to 20 mA or 4 to 20 mA at
a maximum of 500 Ω.

50
53, 54

10 V DC analog supply voltage. 15 mA maximum commonly used for a potentiometer or thermistor.
Analog input. Selectable for voltage (0-10 V) or current (0- or 4-20 mA). Closed is for current and open is for voltage.
Switches are located on the drive control card behind the removable keypad. See drive support materials for details.

55

Common for analog inputs.

61

Common for serial communication. Do not use to terminate shields. See drive support materials for proper shield

68 (+), 69 (-)

RS-485 interface. When the drive is connected to an RS-485 serial communication bus, a drive control card switch is

termination.
provided for termination resistance. ON for termination and OFF for no termination. See drive support materials for
details.
Table 3.16 Drive Control Terminals Functions

3-28

BAS-SVX49A-EN

Start Up

4 Start Up
1.

Input power to the unit must be OFF and locked
out per OSHA requirements. Do not rely on panel
disconnect switches.

11.

For multiple winding motors, the motor must be
wired on run winding, not start winding.

12.

Confirm motor FLA is equal to or less than
maximum panel output current. Some motors
have higher than normal NEMA currents.

13.

Check that the overload relay is set for FLA of
connected motor. Service factor is built into
overload relay. Relay trips at 120% of setting.

14.

For drive start up procedures, see drive
instruction manual.

WARNING
HAZARDOUS VOLTAGE!
if input and output connections have been connected
improperly, there is potential for high voltage on these
terminals. If power leads for multiple motors are
improperly run in same conduit, there is potential for
leakage current to charge capacitors within the panel, even
when disconnected from line input. For initial start up,
make no assumptions about power components. Follow
pre-start procedures described below. Failure to do so
could result in death, serious injury or damage to
equipment.
2.

Use AC voltmeter to verify there is no voltage on
input terminals L1, L2, and L3, phase-to-phase
and phase-to-ground, and output terminals T1,
T2, and T3, phase-to-phase and phase-to-ground.

3.

Use ohmmeter to confirm continuity of the motor
by measuring T1-T2, T2-T3, and T3-T1.

4.

Use ohmmeter to confirm open on input by
measuring L1-L2, L2-L3, and L3-L1. Note that if an
isolation transformer is between the power
source and panel, continuity will be present. In
this case, visually confirm that motor and power
leads are not reversed.

5.

Inspect the panel for loose connections on
terminals.

6.

CheckTable 3.9 and Table 3.10 for proper ground
wire: panel to main building distribution ground,
and panel to motor ground.

7.

Confirm control connections terminated per
connection diagrams supplied with the
equipment.

8.

Check for external devices between drive panel
output and motor. It is recommended that no
devices be installed between the motor and
drive.

9.

Record motor nameplate data; hp, voltage, full
load amps (FLA), and RPM. It will be needed to
match motor and drive later on.

10.

Confirm that incoming power voltage matches
drive label voltage and motor nameplate voltage.

BAS-SVX49A-EN

4-1

Start Up

4.1.1 Inspection Prior to Start Up
Before applying power to the unit, inspect the entire installation as detailed in Table 4.1.
Inspect For

Description
Look for auxiliary equipment, switches, disconnects, or input fuses/circuit breakers that may reside on input

Auxiliary equipment

power side of drive or output side to motor. Examine their operational readiness and ensure they are ready in
all respects for operation at full speed. Check function and installation of pressure sensors or encoders (etc.)
used for feedback to drive. Remove power factor correction caps on motor, if present.
Ensure that input power, motor wiring, and control wiring are in three separate metallic conduits for high

Cable routing

frequency noise isolation. Failure to isolate power, motor, and control wiring could result in less than optimum
drive and associated equipment performance.
Check for broken or damaged wires and connections. Check the voltage source of the signals, if necessary. The

Control wiring

use of shielded cable or twisted pair is recommended for serial communication. Ensure the shield is terminated

EMC considerations

Check for proper installation with regard to electromagnetic capability.

Environmental

See panel label for the maximum ambient operating temperature. Humidity levels must be less than 95% non-

conditions

condensing. Attitude less than 3300 feet.

Fusing and circuit

Check that all fuses are inserted firmly and in operational condition and that all circuit breakers are in the open

breakers

position.

correctly.

The panel requires a dedicated ground wire from its chassis to the building ground. It is required that the
Grounding

motor be grounded to the panel chassis. The use of conduit or mounting of the panel to a metal surface is not
considered a suitable ground. Check for good ground connections that are tight and free of oxidation. Run
insulated motor ground wire back to panel in conduit with motor wires.

Input and output
power wiring
Panel interior
Proper Cooling

Check for loose connections. Check for proper fusing or circuit breakers.
Panel interior must be free of dirt, metal chips, moisture, and corrosion. Check for harmful airborne contaminates such as sulfur based compounds.
Panels require top and bottom clearance adequate to ensure proper air flow for cooling. See Figure 3.2 and

Clearance

Figure 3.3

Switches

Ensure that all switch and disconnect settings are in the proper position.

Vibration

Look for any unusual amount of vibration the equipment may be subjected to when mounting panel.

Table 4.1 Inspection prior to Startup

4.1.2 Start Up Procedure
In the following procedures, changing the equipment
between drive mode and bypass mode is required.
Changing modes is different for the ECB and EMB2. The
ECB uses pushbuttons on the drive keypad while the EMB2
uses a selector switch on the front of the panel. Be familiar
with the operation of these devices prior to start up.

WARNING
HAZARDOUS VOLTAGE!

1.

Perform pre-startup procedure.

2.

Ensure that all operator devices are in the OFF
position. The main disconnect switch on the front
of the electromechanical bypass panel must be in
the OFF position. The panel door should be
closed.

3.

Keep main disconnect switch in the OFF position
and apply voltage to the panel.

4.

Confirm that input line voltage is balanced within
3%. If not, correct the input voltage imbalance
before proceeding.

The panel contains dangerous voltages when connected to
line voltage. Installation, start-up and maintenance should
be performed only by qualified personnel. Failure to
perform installation, start-up and maintenance by qualified
personnel only could result in death or serious injury.

4-2

BAS-SVX49A-EN

Start Up

within FLA of drive and balanced within
3%. If incorrect, see 7.1 Start Up Troubleshooting for isolation procedures.

CAUTION
MOTOR START!
Ensure that motor, system, and any attached equipment is
ready for start. Failure to do so could result in personal
injury or equipment damage.
5.

If a bypass is connected, place the Mode Selector
Switch in drive mode. Apply power by turning
the main disconnect switch to the ON position.

6.

Enter drive programming data per the drive
instruction manual.

7.

Check motor rotation direction in drive control as
follows.

8.

9.

7a

Put panel in drive mode.

7b

Hand start drive at minimum speed (see
drive instruction manual for details).

7c

Confirm directional rotation.

7d

If incorrect, stop the drive, remove
power, and lock out.

7e

Reverse connection of T1 & T2 motor
leads. Do not change incoming power
leads.

7f

Remove lockout and apply power.

7g

Confirm directional rotation.

10.

Check motor current in bypass mode on the
motor terminals.
10a

Put the unit in bypass mode.

10b

Check full load amps on terminals T1,
T2, and T3. Verify the motor amps are
within motor FLA rated current and
balanced within 3%. If incorrect, see
7.1 Start Up Troubleshooting for isolation
procedures.

For steps 11-13, see 5 Electromechanical Bypass (EMB2)
Operation and 6 Electronically Controlled Bypass (ECB)
Operation for details.
11.

Check operation of any optional functions to
confirm that they work, as applicable. Options
may include run permissive, fire mode, common
start/stop, or others.

12.

Exercise the safety circuit and verify that the unit
stops running.

13.

Exercise the start/stop circuit and verify that the
unit starts and stops with the system in the Auto
mode of operation.

Check motor rotation direction in bypass as
follows.
8a

Momentarily bump motor in bypass.

8b

Confirm directional rotation.

8c

If incorrect, stop drive, remove power,
and lock out.

8d

Reverse connection of L1 & L2 input
power leads to the main disconnect. Do
not change motor leads.

8e

Confirm directional rotation.

Check motor current in drive mode on the motor
terminals.
9a

Put the unit in drive mode.

9b

Check motor current on motor terminals
T1, T2, and T3. Verify the motor amps
are within drive and motor rated current
and are balanced within 3%. If incorrect,
see 7.1 Start Up Troubleshooting for
isolation procedures.

9c

Check input current on input terminals
L1, L2, and L3. Verify that current is

BAS-SVX49A-EN

4-3

Start Up

4-4

BAS-SVX49A-EN

Electromechanical Bypass (EMB2) Operation

5 Electromechanical Bypass (EMB2) Operation
5.1.1 Typical Control Connections for Common HVAC Applications
Drive Terminal

Parameter Number

27

500

Value Number

Value Name

Digital I/O Mode

27
29

Parameter Name

0

PNP

External Interlock

Function

501

Term 27 mode

0

Input

External Interlock

502

Term 29 Mode

1

Output

Auto Bypass

18

510

Term 18 digital input

8

Start

19

511

Term 19 digital input

52

Run Permissive

Common run/stop

27

512

Term 27 digital input

29

531

Term 29 digital output

7

External Interlock

160

No Alarm

Run Permissive
External Interlock
Auto Bypass

01 & 02

540 [0]

Relay 1 function

167

Start Command Active

Run Permissive

01 & 02

540 [0]

Relay 1 off delay

0.00 seconds

Off Delay

Run Permissive

Table 5.1 EMB2 Default Parameter Settings for Common HVAC Applications

If the drive is reinitialized, be sure that these settings are maintained or reset for proper bypass.
Name

Function

Remote Drive Start (with common start/stop)

Input Command

Remote Drive Start (without common start/stop)

Input Command

Motor Running on Drive

Output Status

Run Request (for run permissive)

Output Command

Run Enable (for run permissive)

Input Command

Safety Stop

Input Command

Drive Fault

Output Status

Drive Terminals

EMB2 X59

EMB2 X55
3, 4

13, 18
04, 05, 06
11, 12
1, 2
5, 6
5, 6, 7

Fire Mode

Input Command

Drive Mode

Output Status

1, 2

7, 8

Bypass Mode

Output Status

3, 4

Fire Mode

Output Status

9, 10

Table 5.2 Common Functions for Controlling Motor using Bypass and Typical Terminal Connections.

Commands enable drive functions. Status reports describe conditions, but do not enable a function.

BAS-SVX49A-EN

5-1

Electromechanical Bypass (E...

Figure 5.1 Customer Side EMB2 Control Card Terminal Connections

5-2

BAS-SVX49A-EN

Electromechanical Bypass (EMB2) Operation

5.1.2 EMB2 Auto Bypass
General Information
Auto bypass allows a fault condition in the drive to
activate running the motor in bypass without operator
intervention. Activation of the function is through setting
DIP switches (S100) located on the EMB2 bypass control
card (see Figure 5.1). A fault condition enables a delay
timer prior to tripping the drive into bypass. The fault trip
and running in bypass are reported as output from the
bypass control card. The auto bypass function is built in.
Prior to Enabling Auto Bypass

•

Complete the start-up procedure to verify that
the motor rotation direction in bypass is correct
and that the system is ready in all respects for
continuous full speed operation in bypass.

WARNING
HAZARDOUS VOLTAGE!
Remove power to the bypass panel before setting auto
bypass dip switch settings. Bypass can contain high
voltage. Failure to remove power to bypass panel before
setting dip switches could result in death or serious injury.
Operation

•

With the bypass selector switch in drive and auto
bypass enabled, a fault signal from the drive will
activate the auto bypass timer.

•

If the fault clears before the time delay is
complete, the motor remains operating in drive
mode. This allows temporary faults, such as a
momentary under or over voltage, to clear
without transferring the system to bypass.

•

If the timer completes its cycle before the fault
clears, the panel trips into bypass mode and the
motor runs at constant full speed from line input
voltage.

•

In bypass, the motor will stop if safety or motor
overload conditions are exceeded.

•

Once auto bypass is activated, the only way to
reset the unit back to drive is by operator
intervention. Ensure that the fault has been
cleared, then rotate the bypass switch to the OFF
position momentarily before setting it back to the
drive position. This resets the drive and fault
timer.

Auto Bypass Function Setup
Enable auto bypass by closing one or more DIP switches
on switch S100 located on the bypass control card. (Times
are approximate.)

BAS-SVX49A-EN

•
•
•
•
•

All OFF = no auto bypass operation
Switch 1 only ON = 30 sec. delay
Switch 2 only ON = 60 sec. delay
Switch 3 only ON = 300 sec. delay (maximum)
Switch 4 = Always OFF

5.1.3 EMB2 Common Run/Stop
General Information
The common run/stop function provides remote run and
stop control of the motor in bypass. Without common run/
stop, the motor would automatically run at full speed
whenever the bypass is activated. The remote signal
provides drive control as well as bypass control, making
this one input common to both. Common run/stop is
enabled by factory default. When used with the run
permissive function, common run/stop permits run request
operation in bypass.
Prior to Enabling Common Run/Stop

•

Complete the start-up procedure to verify motor
rotation direction in bypass is correct and that
the system is ready in all respects for continuous
full speed operation in bypass.

Operation

•

A user supplied remote start command wired to
connector X55, terminals 3 and 4 initiates remote
bypass operation. With common run/ stop,
bypass mode cannot be activated by hand on the
drive keypad or by serial communication.

Common Run/Stop Setup

•

Wire input terminals 3 and 4 on connector X55
per the system application.

To Disable Common Run/Stop

•

Common run/stop is enabled by factory default
when ordered.

•

To disable the feature, turn switch four on dip
switch S105. This allows the bypass to start when
the bypass switch is placed in the bypass
position.

•

Remove wire from terminal 18 of the drive
control terminal and insulate the end of the wire
to prevent shorting. This is required or the drive
will always have a run command.

•

If applicable, connect remote run/stop input to
terminals 12 and 18 on the drive control card.

5-3

Electromechanical Bypass (E...

5.1.4 EMB2 Run Permissive

5.1.5 EMB2 Overload

General Information
Run permissive allows a remote signal to notify the drive
to start, indicating the system is safe to operate. Run
permissive works in drive or bypass mode. Run permissive
is enabled by factory default and can be disabled by
switching dip switch #4 on S105 to the on position or
placing a jumper wire between terminal 1 and 2 of the
X55 customer connector.

General Information
The overload device provides overcurrent protection for
the motor when running in bypass. The thermally activated
overload monitors motor current and trips to remove
power to the motor if a sustained over-current condition
exists. A Class 20 overload is standard with a variable
setting for motor current. Test and reset buttons are also
provided. In drive mode, the drive provides current sensing
and trip protection. Fuses provide quick action for high
over current conditions.

Prior to Enabling Run Permissive

•

•

Complete the start-up procedure to verify that
motor rotation direction in bypass is correct and
that the system is ready in all respects for
continuous full speed operation in bypass.
Verify that the drive is programmed for the run
permissive function. See the drive support
manual provided for information on
programming the run permissive function.

Prior to Enabling Overload

•

Verify that the overload current dial setting
matches the motor FLA rating on the motor
nameplate.

•

If the motor FLA is greater or less than the range
of the current dial, reconfirm that the motor hp
and voltage are within the option panel (and
drive) rating. If greater than the FLA rating,
replace the panel with one of a proper rating.

Operation

•

A start command can be from local hand start on
the drive keypad or a remote auto start signal
through digital input connector X55 terminals 3
and 4, or via the serial communications input.

•

In response to a start command, an output
request is sent from X55 terminals 11 and 12 to
the external equipment (to activate a valve or
damper, for example).

•

When a return run signal on X55 terminals 1 and
2 is received, the motor is started in either drive
or bypass mode, depending upon the bypass
switch position.

Run Permissive Function Setup

•

Remove the factory-installed jumper wire on
connector X55, terminals 1 and 2.

•

Wire the output run request to connector X55,
terminals 11 and 12.

•

Wire the input run permission to connector X55,
terminals 1 and 2 per the system application.

Disable Run Permissive

•
•

5-4

Run permissive is enabled by factory default
when ordered.
To disable the run permissive function, jumper
between terminals 1 and 2 on connector X55 or
use dip switch 4 on 5105.

CAUTION
MOTOR DAMAGE!
Repeated attempts to reset an overload can cause motor
damage. Correct the overload condition and let the
overload and motor return to normal operating
temperature before resetting. See motor manufacturer’s
recommendations for time between start attempts. Failure
to correct the overload condition and let the motor return
to normal operating temperature could cause motor
damage.
Operation
Overloads are rated by class. The class is defined by the
NEC to determine the maximum time to trip. A Class 20
overload, for example, has a typical trip delay of 20 sec. or
less at 600% current and normal operating temperature.
This allows for high motor inrush current for 20 sec. while
the motor is ramping up to synchronous speed. The trip
time, however, is based on the percentage of overload.
The higher the overload, the shorter the trip time. It is
important that the overload class not exceed the motor
class rating or motor damage could occur.
Overload Function Setup

•

Set the overload current dial to the FLA of the
motor. DO NOT add the service factor of the
motor into the setting. A service factor of 120%
for Class 20 is designed into the overload.

•

Pressing the test pushbutton verifies the
operation of the overload. The overload should

BAS-SVX49A-EN

Electromechanical Bypass (EMB2) Operation

5.1.7 EMB2 Fire Mode

Reset is used to reset the overload after it trips. If
the overload is still hot, wait until the motor
reaches normal operating temperature before
resetting. The overload offers a manual (hand) or
auto reset selection. It is highly recommended to
operate in the manual factory setting to prevent
the risk of damage to the motor.

General Information
Fire mode runs the motor at full speed in bypass and is
intended to ignore common safety, overload, and mode
selector switch inputs in emergency situations. The motor
will continue to run in bypass until fire mode is removed
or the unit fails.

TRIP

5

MANUAL

10

Prior to Enabling Fire Mode

•

AUTO

30

20

TEST

130BX229.10

•

trip when pressed. Use the reset pushbutton to
reset the overload after the test.

RESET

Complete the start-up procedure to verify motor
rotation direction in bypass is correct and that
the system is ready in all respects for continuous
full speed operation in bypass.

Operation
97NO

T1

98NO

95NC

T2

96NC

T3

•

Activation of fire mode is accomplished by
closing connector X55, input terminals 7 and 8.

•

When activated, a relay overrides the safety
circuit, motor overload, and bypass switch (SW1)
position.

•

Fire mode is deactivated only when removed or
fuses blow.

•

Fire mode status can be reported through
connector X55, terminals 9 and 10, a normally
open dry contact that closes when fire mode is
active.

Figure 5.2 Sample Overload Device

5.1.6 EMB2 Safety Interlock
General Information
The safety interlock feature prevents the drive or bypass
from operating. For operation in drive or bypass, the safety
interlock input contact must be closed. Only a fire mode
command to run in bypass overrides this function. Safety
inputs include, but are not limited to, high and low
pressure limit switches, fire alarm, smoke alarm, high and
low temperature switches, and vibration sensors.
Operation
When an external safety input closes, the panel is in
operational mode. When open, power is interrupted to the
drive output and bypass contactors and relays, and the
bypass ignores all run commands except for fire mode
operation. When power is interrupted in drive mode, the
drive display indicates an external fault, meaning the
problem is external to the drive. In some instances, a fault
can be caused by a failure within the panel, which will still
be reported as an external fault from the drive. A factory
installed jumper allows the unit to operate when no safety
input is connected. This jumper must be removed when
connecting a safety interlock in the circuit.
Safety Interlock Function Setup

•

Remove factory-installed jumper between
terminals 5 and 6 on connector X55

•

Wire safety input to terminals 5 and 6 on
connector X55

BAS-SVX49A-EN

Fire Mode Function Setup

•

Wire the fire mode input to connector X55,
terminals 7 and 8.

•

Wire the fire mode status output to connector
X55, terminals 9 and 10.

5.1.8 EMB2 Fault Reporting
General Information
A fault indication is provided if the drive experiences a
fault or bypass input power is lost. The EMB2 bypass
control card monitors the drive fault output for status
reporting. The fault contacts are fail-safe, meaning that if
power is removed, a fault condition is automatically
reported. Fault status is not monitored in bypass
operation.
Operation
For the EMB2, fault reporting is monitored through a
Form-C relay (RL2) on the bypass control board. The relay
reports a fault on connector X59 terminals 5, 6, and 7. In
normal operation, the relay is powered and terminal 5 is
closed with terminal 7 open. In a fault condition, power to
the relay is lost and the relay positions automatically
reverse, signaling the fault condition. Terminal 6 is
common to both.

5-5

Electromechanical Bypass (E...

Fault Reporting Function Setup

•

Fault reporting status is connected to connector
X55, output terminals 5, 6, and 7.

5.1.9 EMB2 Switches
Mode selector switch.
A panel mounted Drive/OFF/Bypass/Test selector switch is
used to electrically select whether the motor is controlled
by the drive (M1 and M2 contactors), connected to the
full-speed bypass (M3 contactor), or disconnected from
both. The test position allows for operation in bypass while
providing power to the drive (M1 and M3). See Figure 1.2.

5-6

BAS-SVX49A-EN

Electronically Controlled Bypass (ECB) Operation

6 Electronically Controlled Bypass (ECB) Operation
1.

keypad Display

6.1 Electronically Controlled Bypass (ECB)
Operation

2.

Menu keys

3.

Menu navigation

6.1.1 Overview

4.

Control keys

Information provided in this section is intended to enable
the user to connect control wiring, program functions, and
operate the ECB and its optional features.
The ECB contains a local processor located on the ECB
control card, which interacts with the drive’s control logic
for programmable options, remote command input, and
output status reporting. Rather than panel-mounted
operator-activated selector switches, as on the electromechanical option panel, ECB control is provided by the
drive’s processor.
The ECB also contains a power supply which provides back
up for the drive’s logic circuitry, so even if the drive loses
power, the control and communication functions are
maintained.

Programming and display are provided by the drive’s local
control panel. (keypad See Figure 6.1)
An important feature of the ECB is the ability to accept
commands from a building automation system (BAS) and
to report operational status in return.
Control wiring connections are made to either the drive’s
control terminals (see Figure 3.20) or terminals provided on
the ECB control card (see Figure 6.2). Drive analog and
digital I/O terminals are multifunctional and need to be
programmed for their intended use while the terminals on
the ECB control card are dedicated for specific functions.
Programming options for drive terminals are seen by
pressing the [Main Menu] key or [Quick Menu] key on the
keypad keypad. Parameter menus appear in the keypad
display. The arrow keys are used for navigating through
the parameter lists. Terminal functions are programmed in
parameter group 5-**. (See Table 6.1 for factory default
parameter settings for drives with an ECB.) Bypass
functions are programmed in parameter group 31-** (see
Table 6.4). See the drive’s supporting materials for detailed
programming instructions.

Figure 6.1 keypad

BAS-SVX49A-EN

6-1

Electronically Controlled B...

Parameter

Parameter name

Setting title

Setting

Function

5-01

Term 27 Mode

Input

0

Customer Interlock

5-02

Term 29 Mode

Output

1

Auto bypass
Common run/stop

5-10

Term 18 digital input

Start

8

5-11

Term 19 digital input

Run Permissive

52

Run Permissive

5-12

Term 27 digital input

External Interlock

7

Customer Interlock

5-31

Term 29 digital output

No Alarm

160

Auto bypass

5-40(0)

Relay 1 function

Start Command Active

167

Run Permissive

5-40(0)

Relay 1 off delay

Off Delay

0.00 S

Run Permissive

Table 6.1 Parameter Group 5-** Factory Default Settings

6.1.2 ECB Control Card
The ECB control card (see Figure 6.2) provides input connector X57 for commanding bypass operation remotely and output
connector X59 for reporting the bypass mode of operation, either drive mode or running in bypass.

1

130BX232.10

See Table 6.2 for ECB control card terminal types and functions.

2

3

4

6-2

1.

Terminal X58

2.

Terminal X56

3.

Terminal X57

4.

Terminal X59

BAS-SVX49A-EN

Electronically Controlled Bypass (ECB) Operation

Figure 6.2 ECB Control Card Terminal Connections

BAS-SVX49A-EN

6-3

Electronically Controlled B...

Input Conn.

X57

Term.

Function

1

Digital input for safety stop

User supplied dry contact

2

Common

User supplied dry contact

3

Factory use only

4

No function

5

Factory use only

6

Factory use only

7

Factory use only

8
9

Digital input for remote bypass enable

Type

User supplied dry contact

Digital input overrides system to Bypass Mode ignoring all User supplied dry contact
other inputs and commands, except for safety stop on
terminal 1.

Output Conn.

X59

Relay Output
X56

10

Digital input for remote overload reset

Term.

Function

1

Common for binary I/O

2

Common for binary I/O

3

No function

User supplied dry contact

4

No function

5

Digital output indicates panel is in Drive Mode.

24 VDC digital output

6

Digital output indicates panel is in Bypass Mode

24 VDC digital output

7

Common for binary I/O

8

Common for binary I/O

Term.

Function

1

N.O. contact for running in bypass or drive

Relay output for user

2

N.O. contact for running in bypass or drive

Relay output for user

3-12

Factory use only

Table 6.2 ECB Card Terminals

6-4

BAS-SVX49A-EN

Electronically Controlled Bypass (ECB) Operation

6.1.3 ECB Drive or Bypass Selection
Use the keypad and display to switch between the motor running in drive mode or bypass when operating in local control.
The display in operating mode is shown below.
1. Press [Drive Bypass]. Display changes to show
bypass and drive mode options (shown in Step 2).

1 = Display
2 = Info key
3 = Drive/Bypass Option Key

2. When running in drive mode, press [OK] on
keypad to activate bypass mode or press CANCEL
to remain in drive mode. In bypass, the motor will
run at full speed.

3. When running in drive mode, press [OK] on the
keypad to activate drive mode or press [Cancel] to
remain in bypass mode.

4. Press [Status] to return to drive status display.

BAS-SVX49A-EN

6-5

Electronically Controlled B...

NOTE!

130BX238.10

Pressing [Info] at any time displays tips and guidelines for
performing the function currently activated.

6-6

BAS-SVX49A-EN

Electronically Controlled Bypass (ECB) Operation

6.1.4 ECB Programming
Use the keypad and display for programming ECB functional options. All programming options appear in numbered
parameters. Parameters are arranged in groups by related functions. Programming is performed by accessing the
parameters through a menu and selecting from displayed options or entering numerical values. See the drives’ supporting
materials for detailed programming instructions.
Access parameters to program bypass functions in accordance with the following instructions:
1. Press [Main Menu] on the keypad to access parameter
groups. (Note that the memory function of the menu returns
to the most recently used function. Use [Back] to return to the
main menu index when necessary.)

2. Press [▲] or [▼] to scroll through parameter groups. A
dotted outline surrounds the selected group. Bypass options
are found in parameter group 31-** Bypass.

3. Press [OK] to enter the selected parameter group.
4. Press [▲] or [▼] to scroll through the parameter list.

5. Press [OK] again to enter programming mode, which allows
changing parameter options or data. Option is inverse
highlighted.

6. Press [▲] or [▼] to scroll through programmable options.
7. Press [OK] again to activate the selection or [Cancel] to
cancel.
8. For entering numeric values, press [►] or [◄] to select
numeric digit, then Press [▲] or [▼] to scroll through digit
numbers 0-9. Selected digit is inverse highlighted.
9. Press [OK] to activate the selection or [Cancel] to cancel.
10. Press [Status] to return to operational display data or [Back]
to return to parameter menu options.

BAS-SVX49A-EN

6-7

Electronically Controlled B...

6.1.5 ECB Hand/OFF/Auto
General Information
The [Hand on], [Off Reset], and [Auto on] keys on the keypad control both the drive and bypass (see Figure 6.1). [Drive
Bypass] allows the user to locally select drive or bypass mode of operation. It does not necessarily start or stop the motor.
Prior to Enabling Hand/Off/Auto
• Complete the start-up procedure to verify that motor rotation direction in bypass is correct and that the system is
ready in all respects for continuous full speed operation in bypass.
Programming Key Functions
For [Off Reset] and [Drive Bypass], Table 6.3 lists the parameters that select functions for the control keys. A password
protection can also be assigned in these parameters.
Operation
• [Hand on] allows the user to start the motor locally from the keypad. Press the [Hand on] to start the motor locally
either in drive or bypass mode.

•

[Off Reset] allows the user to stop the motor locally from the keypad. Press the [Off Reset] to stop the motor
locally, either in drive or bypass mode.

•

[Auto on] allows the motor to be started remotely from digital input or serial communications. Press [Auto on] to
activate the remote motor start and stop from a digital input or serial communications in drive or bypass mode.

•

Press [Drive Bypass] to initiate the display to toggle between drive or bypass mode of operation. Press [OK] to
accept the change or [Cancel] to cancel the action.
Parameter No.

Key

00-44

[Off Reset]

Function
This disables or enables the [Off Reset] key on keypad. (0) disabled,
(1) enabled, (2) password Default value is (1) enabled.

00-45

[Drive Bypass]

This disables or enables the [Drive Bypass] key on keypad. (0)
disabled, (1) enabled, (2) password Default value is (1) enabled.

Table 6.3 keypad Control Keys Programming

6.1.6 ECB Mode of Operation
General Information
The ECB has four modes of operation: drive, bypass, auto bypass, and test. Each mode is selected through the keypad and
display. Bypass mode select can be accessed directly by pressing [Drive Bypass].
Prior to Enabling Mode of Operation
• Complete the start-up procedure and verify motor rotation direction in bypass is correct and that the system is
ready in all respects for continuous full speed operation in bypass.

•

Press [Off Reset] to prevent operation of the motor.

Operation
• Drive mode: The motor is connected to and controlled by the drive. Contactors M1 and M2 are closed while
contactor M3 is open. The motor will not run until a run command is present.

6-8

•

Bypass mode: The motor operates at full speed across the line when a run command is present. Contactor M3 is
closed and M1 and M2 are open.

•

Test mode: Test mode puts the panel into bypass mode and will automatically run in bypass. Contactor M1 is
closed, supplying power to the drive for test purposes while M2 is open. Contactor M3 controls the operation of
the motor in bypass, closed to run the motor, open to remove power. The control keys on the keypad will not
control the bypass until test mode is removed.

BAS-SVX49A-EN

Electronically Controlled Bypass (ECB) Operation

•

Auto bypass mode: When in drive mode, auto bypass is a timed interval that allows a fault condition in the drive
to activate running the motor in bypass without operator intervention.

Mode of Operation Select
• Mode of operation is programmed through parameter group 31-** . See Table 6.4.
Par. No.

Selection

31-00

Bypass Mode

Function
Selects source of motor power.
(0) Drive (drive mode) (1) Bypass (bypass
mode)

31-01

Bypass Start Time Delay

Sets a delay time for starting in bypass that
allows for external actions to take place prior
to line starting the motor.
0-60 sec. (default value is 5 sec.)

31-02

Bypass Trip Time Delay

Setting a value other than 0 sec. enables
auto bypass. Bypass trip delay sets the delay
time before switching to bypass mode when
the drive has a fault.
0-300 sec. (default is 0 sec. = OFF)

31-03

Test Mode Activation

Setting enabled puts bypass in test mode.
See the manual for warnings and cautions.
(0) disabled (default value) (1) enabled

31-10

Bypass Status Word

Read-only display, which shows the bypass
status in hex. See the next table for details.
0, 216-1 (default value is 0)

31-11

Bypass Running Hours

Read only display which shows bypass
running hours.

Table 6.4 Bypass Parameter Functions
Bit

Description

0

Test Mode The Test Mode bit will be true when the ECB is in Test Mode.

1

Drive Mode The Drive Mode bit will be true when the ECB is in Drive Mode.

2

Automatic Bypass Mode The Automatic Bypass Mode bit will be true when the ECB is in Automatic Bypass Mode.

3

Bypass Mode The Bypass Mode bit will be true when the ECB is in Bypass Mode.

4

Reserved This bit is reserved for future use.

5

Motor Running from Bypass/Drive The Motor Running from Bypass/Drive Bit will be true when the motor is running from
either the drive or the bypass.

6

Overload Trip The Overload Trip Bit will be true when the ECB detects an overload trip.

7

M2 Contactor Fault The Contactor Fault Bit will be true when an M2 Contactor Fault is detected.

8

M3 Contactor Fault The Contactor Fault Bit will be true when an M3 Contactor Fault is detected.

9

External Interlock The External Interlock Bit will be true when an External Interlock fault is detected.

10

Manual Bypass Override The Manual Bypass Override Bit will be true when the Manual Bypass Override input is true.

Table 6.5 Parameter 31-10 Bypass Status Word Bit Definitions

BAS-SVX49A-EN

6-9

Electronically Controlled B...

6.1.7 Bypass Status Word Bit Examples
1.

Motor running and bypass in drive mode. Status word 22 hexadecimal converts to 00000100010 binary.

Bit

10

9

8

7

6

5

4

3

2

1

0

Binary

0

0

0

0

0

1

0

0

0

1

0

1.

External interlock fault (open) and bypass in bypass mode. Status word 208 hexadecimal converts to 01000001000
binary.

Bit

10

9

8

7

6

5

4

3

2

1

0

Binary

0

1

0

0

0

0

0

1

0

0

0

6.1.8 ECB Auto Bypass

Prior to Enabling Auto Bypass

•

Complete the start-up procedure to verify motor
rotation direction in bypass is correct and that
the system is ready in all respects for continuous
full speed operation in bypass.

Operation

•

With the auto bypass function enabled, a fault
signal from the drive activates the auto bypass
timer.

•

If the fault clears before the time delay is
complete, the motor remains operating in drive
mode. This allows temporary faults, such as a
momentary under or over voltage, to clear
without transferring the system to bypass.

•

If the timer completes its cycle before the fault
clears, the panel trips into bypass mode and the
motor runs at constant full speed from line input
voltage.

•

In bypass, the motor will stop:

6-10

-

if the drive receives a remote stop
command

-

local stop ([Off]) on the keypad is
pressed

•

a remote start command is removed

-

a safety is open

-

motor overload is tripped

Once auto bypass is activated, the only way to
reset the unit back to drive mode is by operator
intervention. Ensure that the fault has been
cleared, then press [Drive Bypass] and select drive
mode.

Auto Bypass Function Setup
Enable auto bypass by changing parameters in group 31 in
the drive extended menu.

•

31-01, Bypass start time delay. Setting the timer at
anything other than 0 time activates start delay
in bypass. Leave at 30 sec. default or set as
desired up to 60 sec.

•

31-02, Bypass trip time delay. Setting the timer at
anything other than 0 time activates auto bypass.
Leave at 5 sec. default or set as desired up to 60
sec.
130BX243

General Information
Auto bypass allows a fault condition in the drive to
activate running the motor in bypass without operator
intervention. Activation of the function is through setting
timer start parameters in the drive programming. Fault trip
and running in bypass are reported through the drive
display, digital outputs, and serial communications. In
addition, the independently powered ECB card is available
to report bypass status when the drive is inoperable
(control card operative) through its serial communications
or digital outputs.

-

Figure 6.3 Bypass Trip Time Delay

BAS-SVX49A-EN

130BX244.10

Electronically Controlled Bypass (ECB) Operation

Run Permissive Function Setup

•

See the drive manual or support materials for
programming and wiring to the drive control
terminals.

•

Wire the output run request to the drive output
terminals selected, and program the terminals for
run request.

•

Wire the input run command to the drive input
terminals selected, and program the terminals for
run permissive.

Disable Run Permissive
Figure 6.4 Drive Display with Bypass Start Time Delay Active

6.1.9 ECB Run Permissive
General Information
With run permissive active, the drive sends a run request
and waits for a remote response before notifying the
motor to start. The response indicates the system is safe to
operate. Run permissive operates from the keypad
hand/off/auto select in drive or bypass mode. Run
permissive is enabled by programming in the drive
parameters.
Prior to Enabling Run Permissive

•

•

Complete the start-up procedure to verify motor
rotation direction in bypass is correct and that
the system is ready in all respects for continuous
full speed operation in bypass.
Verify that the drive is programmed for the run
permissive function. See the drive support
materials for programming the run permissive
function.

Operation

•

A start command can be initiated from local hand
start, serial communications, or a remote auto
start signal through digital drive input terminals.

•

In response to the start command, an output
request is sent from the programmable drive
relay to the external equipment (to activate a
valve or damper, for example).

•

When a return run signal on the digital input is
received, the motor is started in either drive or
bypass, depending upon which mode is active.

BAS-SVX49A-EN

•

Disable run permissive through the drive
parameters and terminal programming.

6.1.10 ECB Overload
General Information
An overload device provides overcurrent protection for the
motor when running in bypass. The thermally activated
overload monitors motor current and trips to remove
power to the motor if a sustained overcurrent condition
exists. A Class 20 overload is standard with a variable
setting for motor current. Test and reset buttons are also
provided. In drive mode, the drive provides current sensing
and trip protection. Fuses provide quick action for high
over current conditions.
Prior to Enabling Overload

•

Verify that the overload current dial setting
matches the motor FLA rating on the motor
nameplate.

•

If the motor FLA is greater or less than the range
of the current dial, reconfirm that the motor HP
and voltage are within the option panel (and
drive) rating. If greater than the FLA rating,
replace the panel with one of a proper rating.

CAUTION
MOTOR DAMAGE!
Repeated attempts to reset overload can cause motor
damage. Correct the overload condition and let the
overload and motor return to normal operating
temperature before resetting. See motor manufacturer’s
recommendations for time between start attempts. Failure
to correct the overload condition and let the motor return
to normal operating temperature could cause motor
damage.

6-11

Electronically Controlled B...

TRIP

5

MANUAL

97NO

T1

30
20
10

TEST

98NO

130BX229.10

Operation
Overloads and motors are both rated by class. The class is
defined by the NEC to determine the maximum time to
trip. A Class 20 overload, for example, has a typical trip
delay of 20 sec. or less at 600% current and normal
operating temperature. This allows for high motor inrush
current for 20 sec. while the motor is ramping up to
synchronous speed. The trip time, however, is based on
the percentage of overload. The higher the overload, the
shorter the time.

AUTO

RESET

95NC

T2

96NC

bypass ignores all run commands except for fire mode
operation, when applicable. The drive display indicates
alarm 221, bypass interlock, meaning the problem is
external to the drive. A factory installed jumper between
X57 terminals 1 and 2 allows the unit to operate when no
safety input is connected. This jumper must be removed
when connecting in a safety interlock circuit.
Safety Interlock Function Setup

•

Remove factory-installed jumper between ECB
connector X57 terminals 1 and 2 on drive control
terminals.

•

Wire safety input to connector X57 terminals 1
and 2.

•

For technicians familiar with connecting to drive
terminals 12 and 27 for safety interlock, be aware
that ECB bypass operation will NOT stop with the
external fault report. Use terminals 1 and 2 on
connector X57, as indicated, for bypass control.

T3

Figure 6.5 Sample Overload Device

6.1.12 ECB Common Run/Stop
Overload Function Setup

•

Set the overload current dial to the FLA of the
motor. DO NOT add the service factor of the
motor into the setting. A service factor of 1.2 x
FLA is designed into the overload.

•

Pressing the test pushbutton verifies the
operation of the overload. The overload should
trip when pressed. Use the reset pushbutton to
reset the overload after testing.

•

Reset is used to reset the overload after it trips. If
the overload is still hot, wait until the motor
reaches normal operating temperature before
resetting. The overload offers a manual (hand) or
auto reset selection. It is highly recommended to
operate in the manual factory setting to prevent
the risk of damage to the motor.

6.1.11 ECB Safety Interlock
General Information
The safety interlock feature prevents the drive or bypass
from operating. Only a fire mode command to run
overrides this function. For operation in drive or bypass
mode, the safety external interlock input contact must be
closed. External inputs include, but are not limited to, high
and low pressure limit switches, fire alarm, smoke alarm,
high and low temperature switches, and vibration sensors.
Operation
When an external safety input closes on ECB terminals 1
and 2 on connector X57, the option panel is in operational
mode. When open, power to the motor is disabled. The

6-12

General Information
The common run/stop function provides remote run and
stop control of the motor while in either drive or bypass.
Without common run/stop, the motor would automatically
run at full speed whenever the bypass is activated. The
remote signal provides drive control as well as bypass
control, making this one input common to both. Common
run/stop is enabled by factory default. When used with the
run permissive function, common run/stop permits run
request operation in bypass.
Operation
A user supplied remote run command wired to drive
terminals 13 and 18 initiates remote drive or bypass
operation. Common run/stop can also be activated by
hand on the keypad or through serial communication.
Operation in either drive or bypass is determined by drive
or bypass mode selection, not the run/stop command.
Prior to Enabling Common Run/Stop

•

Complete the start-up procedure to verify motor
rotation direction in bypass is correct and that
the system is ready in all respects for continuous
full speed operation in bypass.

Common Run/Stop Setup

•

Wire a remote run/stop to drive input terminals
13 and 18 (default run input). Ensure that
parameter 18 is programmed for run (default
setting).

BAS-SVX49A-EN

Electronically Controlled Bypass (ECB) Operation

6.1.13 ECB Advanced Fire Mode
General Information
Drive operation in advanced fire mode is programmable. In
the event the drive does not function, the motor is
operated in bypass at full speed. Fire mode is intended to
ignore common safety and overload inputs in emergency
situations. The fire mode function is built-in. See the drive
support materials for programmable options.

The drive monitors the ECB card communication and
detects when communication stops. An ECB card failure or
communication error could cause this. Contact Trane using
the phone number on the back of this manual for
technical support if this happens. The phone number can
also be found on the label inside the panel cover.
Fault Reporting Function Setup

•

Automatic function. No set up required.

Prior to Enabling Fire Mode

•

Complete the start-up procedure to verify motor
rotation direction in bypass is correct and that
the system is ready in all respects for continuous
full speed operation in bypass.

•

Verify that the drive is programmed for the fire
mode function. See the drive support materials
for programming the fire mode function.

Operation

•

Activation of fire mode is accomplished by
programming the drive for fire mode.

•

When activated, the ECB ignores safety circuits
and motor overload.

•

Fire mode is deactivated only when the
command is removed or the unit fails.

•

Fire mode status can be reported through serial
communications or drive output.

Fire Mode Function Setup

•
•

Program drive for fire mode.

•

See the drive support materials for programming
the fire mode function.

If required, program a drive output for fire mode
status.

6.1.14 ECB Fault Reporting
General Information
The ECB monitors bypass contactors M2 and M3 and
reports failures to the drive for display and external
reporting. The drive also monitors the ECB card for bypass
communication errors.
Operation
ECB detected faults are reported by the drive in three
ways: Warnings and alarms are displayed on the keypad
display, through serial communication, or through output
relays. The drive provides a form-C fault relay on terminals
01, 02, and 03. The fault contacts are fail-safe, meaning
that if power is removed the contacts close and a fault
condition is reported.

BAS-SVX49A-EN

6-13

Electronically Controlled B...

6-14

BAS-SVX49A-EN

Start Up Troubleshooting

7 Start Up Troubleshooting
7.1.1 Option Panel Alarm and Warnings
Code

Title

Definition

Number
220

Overload Trip

Motor overload has tripped. Indicates excess motor load. Check motor and driven load. To reset,
press [Off Reset]. Then, to restart the system, press [Auto on] or [Hand on].

221

Bypass Interlock

Bypass interlock has opened and caused the motor to stop. Correct the problem. Depending on
the setting of parameter 14-20, the system will either automatically reset this alarm or require the
[Off Reset] key to be pressed.

222

M2 Open Failed

ECB: The contactor that connects the drive to the motor failed to open. The motor can not be
operated.

223

M2 Close Failed

ECB: The contactor that connects the drive to the motor failed to close. The motor can not be

224

M3 Open Failed

ECB: The contactor that connects the motor to the power line has failed to open.

226

M3 Close Failed

operated.
ECB: The contactor that connects the motor to the power line has failed to close. The motor can
not be operated.
227

Bypass Com Error

Communication between the main control card and the bypass option has been lost. Motor control

228

APU Low Voltage

The Option Panel Power Supply has failed, or there is a power problem.

229

Motor Disconn.

lost. It will be possible to run the motor using Manual Bypass Override.
Terminal 3 on connector X57 of the ECB control card shows an open. This generally means that
neither motor has been selected in contactor motor select. Select a motor.
Table 7.1 Option Panel Alarms and Warnings (ECB only)
DisplayText

Definition

Bypass Run Starts in:

Indicates the number of sec. until the motor will be started in bypass. This time delay
can be adjusted using parameter 31-01.

Bypass Activates in:

Indicates the number of sec. left until the system automatically activates Bypass Mode.
Time delay can be adjusted using parameter 31-02.

Table 7.2 Option Panel Status Display (ECB only)

BAS-SVX49A-EN

7-1

Start Up Troubleshooting

Symptom

Possible cause

Test

Solution

Missing input power

See startup guide for voltage checks.

Correct voltage at source.

Missing or open fuses or circuit

See open fuses and tripped circuit

Reset circuit breaker. If fuses, check for

breaker tripped

breaker in this section for possible
causes.

opens with power removed from panel.

Perform pre-startup check for loose

Tighten loose connections in the panel.

Loose connections in panel

connections.
Missing customer connections

Missing customer connections can cause

See customer connections and make

the safety circuit or start signal to be

sure all applicable connections are

open.

made or jumpers installed, especially
customer interlock.

Loose customer connections

Check all customer connections for

Tighten loose customer connections.

tightness. Loose customer connections
can act like an open circuit.
Customer wires incorrectly terminated See customer connection drawing and

Correct any wrong connections. This

make sure wires are connected to correct could potentially cause damage to the
No function

Improper voltage applied

terminals.

panel.

See pre-startup check list.

Correct the voltage mismatch. This
could potentially damage the panel.
Use caution when applying power.

Incorrect power connections

See pre-startup check list to see if motor Correct any wrong connections. This
and power leads were swapped.

could potentially cause damage to the
panel.

Power disconnect open

Verify that the disconnect or circuit

Correct any wrong connections. This

breaker is closed.

could potentially cause damage to the
panel.

Operator switches off

Verify that operator devices are in

Set switches to the correct position.

operating position per startup
procedures.
OL tripped

A tripped OL will disable the motor from Perform pre-startup checklist and set
OL per instructions.
running. Verify that OL relay is in the
normal operating position per the
manual.

Improper voltage applied

See pre-startup check list and correct

Correct voltage mismatch. This could

improper voltages.

potentially damage the panel. Use
caution when applying power.

Incorrect power connections.

Motor and line voltages swapped. Make

Correct any wrong connections. This

sure the line in and motor out are on

could potentially cause damage to the

the correct terminals. See pre-startup

panel.

check list.
Power ground fault
Open power
fuses or

Eliminate any ground faults detected.

ground.
Phase to phase short

Motor or panel has a short phase to

Eliminate any shorts detected.

phase. Check motor and panel phase to

circuit
breaker trip

Check motor and panel power wires to

phase for shorts.
Motor overload

Motor is overloaded for the application.

Perform startup and verify motor
current is within specifications. If motor
current is exceeding nameplate FLA,
reduce the load on the motor.

Drive overload

Drive is overloaded for the application.

Perform startup and verify that drive
current is within specifications. If not,
reduce the load on the motor.

Loose connections

Perform pre-startup check for loose

Tighten loose connections.

connections.
Table 7.3 Fault Table
7-2

BAS-SVX49A-EN

Start Up Troubleshooting

Symptom

Possible cause

Test

Solution

Application problem

Perform startup procedures. Check

If current is too high, reduce the load

panel output motor current at full

on the motor.

speed and check for excessive over
current.
Repeated

Panel problem

fuse or circuit
breaker fault.
Power problem

Perform startup procedures. Check

If current is too high, reduce the load

panel input current at full load and
verify it is within acceptable range.

on the motor.

Monitor incoming power for surges,

Correct any problems found.

sags and overall quality.
Motor problem

Test motor for correct function.

Improper voltage applied

See pre-startup check list.

Repair or replace motor if a problem is
found.
Correct voltage mismatch. This could
potentially damage the panel. Use
caution when applying power.

Customer wires incorrectly terminated
Open control
fuse

Control ground fault

Control short
Improper voltage applied

See the customer connection drawing

Correct any wrong connections. This

and make sure the wires are connected

could potentially cause damage to the

to the correct terminals.

panel.

Check all control wires for a short to

Correct any ground faults found. This

ground.

could potentially cause damage to the
panel.

Check control wires for a short in

Correct any shorts. This could

supply voltage.

potentially cause damage to the panel.

See pre-startup check list.

Correct voltage mismatch. This could
potentially damage the panel. Use
caution when applying power.

Open SMPS

Customer wires incorrectly terminated

fuse

See the customer connection drawing

Correct any wrong connections. This

and make sure the wires are connected

could potentially cause damage to the

to the correct terminals.

panel.

Check all control wires for a short to

Correct any ground faults found. This

ground.

could potentially cause damage to the

Control short

Check control wires for a short in

Correct any shorts. This could

supply voltage.

potentially cause damage to the panel.

Motor

Rotation incorrect in bypass, drive or

Motor rotation is backwards in drive

Perform motor rotation procedure in

rotation

both

mode, bypass mode, or both.

4 Start Up.

Control ground fault

panel.

incorrect

BAS-SVX49A-EN

7-3

Start Up Troubleshooting

Symptom

Possible cause

Test

Solution

Motor overloaded

Motor is drawing too much current for

Perform startup and verify motor current

the application.

is within specifications. If not, reduce the
load on the motor.

Loose connections
Overload trips
OL not set correctly

Look for signs of overheating on

Perform pre-startup check for loose

connections to OL.

connections and tighten. Replace any
overheated components and wires.

An improperly set OL can cause the OL

Set correct motor current on OL.

to trip too soon. See pre-startup
procedure for correct setting.
Contamination

Contactor fails

Defective coil

to pull in
Auxiliary contact binding action
Contamination

Contactor fails

Defective coil

to drop out

Remove contactor and check for

If contamination is found, repair or

contamination.

replace.

Compare coil resistance to contactor

If readings are not the same or if there

specification. Inspect the coil for signs

are visible signs of damage, replace the

of overheating and damages.

coil or contactor.

Remove auxiliary contacts and test

If contactor operates with auxiliaries

contactor action.

removed, replace auxiliary contacts.

Remove the contactor and check for

If contamination is found, repair or

contamination.

replace.

Compare coil resistance to functional

If readings are not the same or there are

contactors of the same size.

visible signs of damage, replace the coil
or contactor.

Auxiliary contact binding action
Problem with mains power
Mains current

Remove auxiliary contacts and test

If the contactor operates with auxiliaries

contactor action.

removed, replace auxiliary contacts.

Rotate incoming power leads into

If the imbalanced leg follows the wire, it

option panel one position; A to B, B to

is a power problem. Causes can vary.

C, and C to A.

Contact an electrician or power expert
for a solution.

imbalance
greater than

Problem with option panel

3%

Rotate incoming power leads into

If the imbalanced leg stays on the same

option panel one position; A to B, B to

option panel input terminal, it is a

C, and C to A.

problem with the option panel. Contact
the factory for assistance.

Problem with motor or motor wiring Rotate outgoing motor leads one
position; U to V, V to W, and W to U.

lead, the problem is in the motor or
wiring to the motor. Causes can vary.
Contact an electrician or motor expert

Motor current
imbalance
greater than
3%

If the imbalanced leg follows the motor

for a solution.
Problem with option panel

Rotate outgoing motor leads one

If the imbalanced leg stays on the same

position; U to V, V to W, and W to U.

option panel output terminal, it is a
problem with the option panel. Contact
the factory for assistance.

7-4

BAS-SVX49A-EN

Appendix

8 Appendix
8.1.1 Dimensions
P2 NONBYPASS

P2 BYPASS

P3 NONBYPASS

P3 BYPASS

P4 NONBYPASS

P4 BYPASS

P5 NONBYPASS

P5 BYPASS

A

8.86 [225.0]

9.11 [231.4]

9.57 [243.0]

9.57 [243.0]

12.69 [322.3]

12.69 [322.2]

15.13 [384.3]

A1

6.66 [169.1]

-

-

-

-

-

-

15.13 [384.2]
-

B

29.92 [759.9]

41.77 [1061.0]

34.33 [872.0]

43.23 [1098.0]

39.58 [1005.4]

54.38 [1381.4]

45.79 [1163.1]

59.64 [1514.9]
18.01 [457.5]

C

11.45 [290.9]

15.94 [405.0]

11.23 [285.2]

17.70 [449.6]

14.78 [375.5]

17.99 [457.0]

14.78 [375.4]

D

-

1.10 [28.0]

0.59 [15.0]

0.59 [15.0]

0.59 [15.0]

0.59 [15.0]

0.59 [15.0]

0.59 [15.0]

a

5.51 [140.0]

7.87 [200.0]

7.87 [200.0]

7.87 [200.0]

10.63 [270.0]

10.63 [270.0]

12.99 [330.0]

12.99 [330.0]

b

28.80 [731.5]

41.02 [1042.0]

32.13 [816.0]

41.18 [1046.0]

37.32 [948.0]

51.89 [1318.0]

43.54 [1106.0]

57.09 [1450.0]

c

0.27 [6.8]

0.27 [6.8]

0.33 [8.5]

0.33 [8.5]

0.33 [8.5]

0.33 [8.5]

0.33 [8.5]

0.33 [8.5]

d

0.39 [10.0]

0.43 [11.0]

0.47 [12.0]

0.39 [10.0]

0.47 [12.0]

0.59 [15.0]

0.47 [12.0]

0.59 [15.0]

e

0.49 [12.5]

0.65 [16.5]

0.72 [18.4]

0.61 [15.5]

0.91 [23.0]

0.75 [19.0]

0.94 [24.0]

0.79 [20.0]

f

0.27 [6.9]

0.27 [6.8]

-

-

-

-

-

-

g

0.47 [12.1]

0.47 [12.0]

-

-

-

-

-

-

h

0.49 [12.5]

0.65 [16.5]

-

-

-

-

-

-

j

0.31 [8.0]

0.31 [8.0]

-

-

-

-

-

-

k

0.32 [8.0]

0.31 [8.0]

-

-

-

-

-

-

BAS-SVX49A-EN

8-1

Appendix

8.1.2 Mechanical Diagrams

Figure 8.1 P2 Bypass

8-2

BAS-SVX49A-EN

Appendix

Figure 8.2 P2 Non-bypass

BAS-SVX49A-EN

8-3

Appendix

Figure 8.3 P3 P4 P5 Bypass

8-4

BAS-SVX49A-EN

Appendix

Figure 8.4 P3 P4 P5 Non-bypass

BAS-SVX49A-EN

8-5

Appendix

8.1.3 Typical Wiring Diagrams

Figure 8.5 EMB2 with Control Relay, Part 1

8-6

BAS-SVX49A-EN

Appendix

Figure 8.6 EMB2 with Control Relay, Part 2

BAS-SVX49A-EN

8-7

Appendix

Figure 8.7 EMB2, Part 1

8-8

BAS-SVX49A-EN

Appendix

Figure 8.8 EMB2, Part 2

BAS-SVX49A-EN

8-9

Appendix

Figure 8.9 ECB, Part 1

8-10

BAS-SVX49A-EN

Appendix

Figure 8.10 ECB, Part 2

BAS-SVX49A-EN

8-11

Appendix

Figure 8.11 ECB with Control Relays, Part 1

8-12

BAS-SVX49A-EN

Appendix

Figure 8.12 ECB with Control Relays, Part 2

BAS-SVX49A-EN

8-13

Appendix

Figure 8.13 Non-bypass

8-14

BAS-SVX49A-EN

 

Operators Guide

TR200 Vertical Bypass/Non Bypass Panel

Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the
leader in creating and sustaining safe, comfortable and energy efficient environments, Trane offers a broad
portfolio of advanced controls and HVAC systems, comprehensive building services, and parts. For more
information, visit www.Trane.com.

SAFETY WARNING
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
© 2011 Trane All rights reserved
BAS-SVX49A-EN 12 August 2011

Only qualified personnel should install and service the equipment. The installation, starting up, and servicing
of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and
training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or
serious injury. When working on the equipment, ovserve all precautions in the literature and on the tags,
stickers, and labels that are attached to the equipment.

August 2011
177R0253

MG14D122

*MG14D122*

Rev. 2011-08-12

BAS-SVX49A-EN



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : Yes
Page Count                      : 86
Page Mode                       : UseNone
XMP Toolkit                     : XMP toolkit 2.9.1-13, framework 1.6
About                           : uuid:6161904e-1223-4534-9764-a604039c166f
Producer                        : Acrobat Distiller 9.4.0 (Windows)
Acces flag                      : T
Alt order nbr                   : 
Alt order nbr type              : 
Bw color                        : B
Hist model                      : 
Date published                  : 08/12/2011
Dept id                         : 14
Topic focused id                : TRANE|EN
Price                           : 0
Cur flag                        : T
Lit class id                    : SV
Lit length                      : 86
Lit order nbr                   : BAS-SVX49A-EN
Lit type id                     : SVX
Media id                        : PPI
Model                           : NONE
Prod class                      : ES
Prod family id                  : NONE
Prod                            : BAS
Restrct flag                    : F
Source date                     : nulldate
Source filename                 : 
Stocking loc id                 : LAXCPY
Supceded by                     : 
Supceded by date                : nulldate
Unit flag                       : T
Branding                        : Trane
Lol language                    : EN
Object id                       : 090102b182b8dc34
Object name                     : BAS-SVX49A-EN_08122011
Chronicle id                    : 090102b182b8dc34
Filename                        : 82b8dc34.pdf
Abstract                        :  This manual is intended to provide detailed information for the installation and operation of the option panel used in conjunction with a Trane variable frequency drive (VFD or drive).
Topic related id                : TRN-FLD|STARTUP|SERVICER|SERV|RRR|OPER|INST|CONST
Creator Tool                    : Adobe Illustrator CS2
Create Date                     : 2011:08:12 08:23:52+02:00
Modify Date                     : 2012:01:26 14:30:34-06:00
Metadata Date                   : 2012:01:26 14:30:34-06:00
Thumbnail Width                 : 256
Thumbnail Height                : 156
Thumbnail Format                : JPEG
Thumbnail Image                 : (Binary data 21564 bytes, use -b option to extract)
Document ID                     : uuid:987F669386A9DD11846DFAA89F0A0DAA
Instance ID                     : uuid:aa04fc12-9123-493a-84d0-ec7f36b1379c
Derived From Instance ID        : uuid:E230769885A9DD11846DFAA89F0A0DAA
Derived From Document ID        : uuid:E130769885A9DD11846DFAA89F0A0DAA
N Pages                         : 86
Format                          : application/pdf
Creator                         : sa_kgu
Title                           : BAS-SVX49A-EN 08/12/2011 TR200 Vertical Bypass/Non Bypass Panel / Operators Guide
Author                          : sa_kgu
Acces Flag                      : T
Alt Order Nbr                   : 
Alt Order Nbr Type              : 
Bw Color                        : B
Hist Model                      : 
Date Published                  : 08/12/2011
Dept Id                         : 14
Topic Focused Id                : TRANE|EN
Cur Flag                        : T
Lit Class Id                    : SV
Lit Length                      : 86
Lit Order Nbr                   : BAS-SVX49A-EN
Lit Type Id                     : SVX
Media Id                        : PPI
Prod Class                      : ES
Prod Family Id                  : NONE
Topic Related Id                : TRN-FLD|STARTUP|SERVICER|SERV|RRR|OPER|INST|CONST
Restrct Flag                    : F
Source Date                     : nulldate
Source Filename                 : 
Stocking Loc Id                 : LAXCPY
Supceded By                     : 
Supceded By Date                : nulldate
Unit Flag                       : T
Lol Language                    : EN
Object Id                       : 090102b182b8dc34
Object Name                     : BAS-SVX49A-EN_08122011
Chronicle Id                    : 090102b182b8dc34
EXIF Metadata provided by EXIF.tools

Navigation menu