Digital Display
Zone Sensor
Figure 1: Digital Display Zone Sensor

The digital display zone sensor has the
functionality of the full-featured Trane
DDC zone sensor with a liquid crystal
display (LCD). The zone sensor is
compatible withTrane VAV and VariTrac®
controllers.The display can be toggled in
the field from zone temperature to zone
setpoint and can be viewed in either
Fahrenheit or Celsius. A communications
jack is provided forTrane portable edit
terminal devices. Additionally, the On/
Cancel buttons allow the system to run in
the occupied mode during nighttime
operation. The ability to override to
maximum and minimum airflow or
position for field balancing is included in
the sensor. Please visit trane.com or
contact a localTrane representative for
more information.

Features
— LCD Readout of Zone Temperature
or Setpoint
— Selectable °F or °C Display
— Communication Jack
— Occupied Mode Override
— Maximum and Minimum Override

Table 1: Sensor Specifications

©2002 American Standard, Inc. All rights reserved

Thermistor Resistance Rating

10k OHM at 77°F (25°C)

Accuracy at 77°F (25°C)

0.4°F (0.2°C)

Setpoint Resistance Rating

500 Ohms at 70°F (21.2°C)

Display Zone Temperature Range

40 to 99°F (10 to 35°C)

Display Setpoint Range

50 to 90°F (10 to 32°C)

Operating Temperature

0 to 120°F (-18 to 49°C)

Storage Temperature

-20 to 130°F (-29 to 54°C)

Humidity Range

5 to 95% non-condensing

Power Supply

24 VAC

Maximum VA load

4 VA

Housing Material

Rigid Vinyl

Dimensions

4.5” x 2.8” x 1.1”
(114 mm x 71 mm x 28 mm)

VAV-SLB007-EN

Table 2: Wiring Terminations at Sensor

AVOID areas such as:

Placement of the Sensor

— Behind doors

Choose a mounting location on an
interior wall near the return air grille,
about five feet above the floor level,
where air circulates freely and is of
average temperature for the zone.

— On outside walls or walls facing
uncontrolled areas
— In direct sunlight, or sources of radiant
heat that could effect temperature
measurement
— In line with discharge air from unit being
controlled

TB1-1

24 VAC Power Supply

TB1-2

24 V Ground

TB2-1

Zone Temperature

TB2-2

Zone Sensor Ground

TB2-3

Zone Setpoint

TB3-1

Communication +

TB3-2

Communication -

Figure 2: Dimensional Data
2.8”
(71 mm)

˚F
˚C
MAX

OVERRIDE
UNNOCSETPOINT

3.3”
(84 mm)

4.5”
(114 mm)

2.1”

ON

(53 mm)
CANCEL

1.1”
(28 mm)

Trane
An American Standard Company
www.trane.com
For more information contact
your local district office or
e-mail us at comfort @trane.com

Literature Order Number

VAV-SLB007-EN

File Number

SB-TD-VAV-000-SLB007-EN-0602

Supersedes

New

Stocking Location

La Crosse

Trane has a policy of continuous product and product data improvement and reserves the right to change design
and specifications without notice.



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.2
Linearized                      : No
Page Count                      : 2
Create Date                     : 1910:30:20 51:41:44
Producer                        : Acrobat Distiller 3.01 for Windows
Author                          : lahke
Creator                         : PageMaker 6.5
Title                           : VAV-SLB007-EN.p65
EXIF Metadata provided by EXIF.tools

Navigation menu