Trane Voyager 12 5 To 25 Tons Installation And Maintenance Manual Installation, Operation,
2015-04-02
: Trane Trane-Voyager-12-5-To-25-Tons-Installation-And-Maintenance-Manual-684204 trane-voyager-12-5-to-25-tons-installation-and-maintenance-manual-684204 trane pdf
Open the PDF directly: View PDF .
Page Count: 44
Download | |
Open PDF In Browser | View PDF |
Installation, Operation, and Maintenance Packaged Rooftop Air Conditioners Voyager™ – Heat Pump 12½ – 20 Ton, 60/50 Hz Model Numbers WS*150-240 SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and airconditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment. May 2014 RT-SVX33E-EN Warnings, Cautions and Notices Warnings, Cautions and Notices. Note that warnings, cautions and notices appear at appropriate intervals throughout this manual. Warnings are provide to alert installing contractors to potential hazards that could result in personal injury or death. Cautions are designed to alert personnel to hazardous situations that could result in personal injury, while notices indicate a situation that may result in equipment or property-damage-only accidents. Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions. WARNING Personal Protective Equipment (PPE) Required! Installing/servicing this unit could result in exposure to electrical, mechanical and chemical hazards. • Before installing/servicing this unit, technicians MUST put on all PPE required for the work being undertaken (Examples; cut resistant gloves/sleeves, butyl gloves, safety glasses, hard hat/bump cap, fall protection, electrical PPE and arc flash clothing). ALWAYS refer to appropriate Material Safety Data Sheets (MSDS)/Safety Data Sheets (SDS) and OSHA guidelines for proper PPE. • When working with or around hazardous chemicals, ALWAYS refer to the appropriate MSDS/SDS and OSHA/GHS (Global Harmonized System of Classification and Labelling of Chemicals) guidelines for information on allowable personal exposure levels, proper respiratory protection and handling instructions. • If there is a risk of energized electrical contact, arc, or flash, technicians MUST put on all PPE in accordance with OSHA, NFPA 70E, or other country-specific requirements for arc flash protection, PRIOR to servicing the unit. NEVER PERFORM ANY SWITCHING, DISCONNECTING, OR VOLTAGE TESTING WITHOUT PROPER ELECTRICAL PPE AND ARC FLASH CLOTHING. ENSURE ELECTRICAL METERS AND EQUIPMENT ARE PROPERLY RATED FOR INTENDED VOLTAGE. ATTENTION: Warnings, Cautions and Notices appear at appropriate sections throughout this literature. Read these carefully: Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. Indicates a potentially hazardous CAUTIONs situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices. Indicates a situation that could result in NOTICE: equipment or property-damage only WARNING Important Environmental Concerns! Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment. Trane advocates the responsible handling of all refrigerants-including industry replacements for CFCs such as HCFCs and HFCs. Responsible Refrigerant Practices! Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified. The Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them. © 2014 Trane All rights reserved Failure to follow instructions could result in death or serious injury. WARNING Proper Field Wiring and Grounding Required! All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes. Failure to follow code could result in death or serious injury. RT-SVX33E-EN Warnings, Cautions and Notices Overview of Manual Note: One copy of this document ships inside the control panel of each unit and is customer property. It must be retained by the unit’s maintenance personnel. This booklet describes proper installation, operation, and maintenance procedures for air cooled systems. By carefully reviewing the information within this manual and following the instructions, the risk of improper operation and/or component damage will be minimized. It is important that periodic maintenance be performed to help assure trouble free operation. A maintenance schedule is provided at the end of this manual. Should equipment failure occur, contact a qualified service organization with qualified, experienced HVAC technicians to properly diagnose and repair this equipment. Revision Summary RT-SVX33E-EN (27 May 2014) • New Low Leak Economizer & Fault Detection Diagnostics (FDD) Options • Updated Model Number Description Section • Added back Warranty Section RT-SVX33E-EN 3 Table of Contents Model Number Description . . . . . . . . . . . . . . . 5 General Information . . . . . . . . . . . . . . . . . . . . . 7 Unit Inspection . . . . . . . . . . . . . . . . . . . . . . . . 7 Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Unit Clearances . . . . . . . . . . . . . . . . . . . . . . . 7 Unit Description . . . . . . . . . . . . . . . . . . . . . . . 7 ReliaTel™ Control . . . . . . . . . . . . . . . . . . . . . 8 System Input Devices & Functions . . . . . . . 8 Zone Sensors . . . . . . . . . . . . . . . . . . . . . . . . 10 Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . 11 Unit Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Factory-Mounted Unit Options . . . . . . . . . . . 26 Circuit Breaker (FIYUCB) & Unit Disconnect (FIYUDC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 Powered/Unpowered Convenience Outlet 27 Return Air Smoke Detector . . . . . . . . . . . . . 28 Pre-Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 Start Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . 38 ReliaTel Controls . . . . . . . . . . . . . . . . . . . . . 38 System Status Checkout Procedure . . . . . 38 Resetting Cooling and Heating Lockouts . 39 Zone Temperature Sensor (ZTS) Service Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40 Clogged Filter Switch . . . . . . . . . . . . . . . . . 40 Fan Failure Switch . . . . . . . . . . . . . . . . . . . . 40 Condensate Overflow Switch . . . . . . . . . . . 40 Zone Temperature Sensor (ZTS) Tests . . 40 Programmable & Digital Zone Sensor Test 41 Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . 43 Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 Heat Pump . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 4 RT-SVX33E-EN Model Number Description W S D 1 5 0 E 3 R G B * * 1 2 3 4 5 6 7 8 9 10 11 12 13 Digit 15 — Supply Fan/Drive Type/Motor Digit 21 — Communications Options = = = = 0 = 1 = Digit 3 — Airflow Configuration 0 1 3 6 D H 2 = 7 8 = = 6 = 9 A = = B = Digit 1 — Unit Type W = Packaged Cooling, Electric Heat Digit 2 — Efficiency S = = = Standard Efficiency Downflow Horizontal Digit 4, 5, 6 — Nominal Gross Cooling Capacity (MBh) 150 = 155 = 180 = 200 = 240 = 12½ Tons, 60Hz 15 Tons, 50Hz 15 Tons, 60Hz 20 Ton, 50Hz 20 Tons, 60Hz Digit 7 — Major Design Sequence E = R-410A Refrigerant Digit 8 — Voltage Selection 3 4 W T D = = = = = 208-230/60/3 460/60/3 575/60/3 200/50/1 380-415/50/3 Digit 9 — Unit Controls R = Reliatel Digit 10 — Heating Capacity Note: (Applicable to Digit 1 W models only) 0 = No Heat G = 18 kW Electric Heat N = 36 kW Electric Heat P = 54 kW Electric Heat R = 72 kW Electric Heat Digit 11 — Minor Design Sequence Digit 12, 13 — Service Sequence Digit 14 — Fresh Air Selection 0 D = = F = H = K = M = P = No Fresh Air Econ Dry Bulb w/ Barometric Relief1 Econ Reference Enthaply w/ Barometric Relief1 Econ Comparative Enthaply w/ Barometric Relief1 Low Leak Econ w/ Barometric Relief1 Low Leak Econ Reference Enthalpy w/ Barometric Relief1 Low Leak Econ Comparative Enthalpy w/ Barometric Relief1 RT-SVX33E-EN C = D = Standard Motor Oversized Motor2 High Efficiency Motor2 Single Zone Variable Air Volume Standard Motor Multi-Speed Standard Motor Single Zone Variable Air Volume Oversized Motor Multi-Speed Oversized Motor Single Zone Variable Air Volume Standard Motor w/ Shaft Ground Ring Multi-Speed Standard Motor w/ Shaft Ground Ring Single Zone Variable Air Volume Oversized Motor w/ Shaft Ground Ring Multi-Speed Oversized Motor w/ Shaft Ground Ring Digit 16 — Hinged Service Access / Filters 0 = A B = = C = D = E = Standard Panels/Standard Filters13 Hinged Access/Standard Filters13 Standard Panels / 2" MERV 8 Filters2 Hinged Access / 2" MERV 8 Filters2 Standard Panels / MERV 13 Filters2 Hinged Access / MERV 13 Filters2 Digit 22 — Refrigeration System Option 0 = 0 1 = = 0 A B C = = = = D = = 6 = 7 = Digit 18 — Through The Base Provisions A = 0 A D B = C = D = E = Digit 20 — Convenience Outlet Option F = 0 A B G = = = = Standard Coil Standard Coil With Hail Guard Black Epoxy Pre-Coated Coil Black Epoxy Pre-Coated Coil with Hail Guard No Through The Base Provisions Through The Base Electric3 Through The Base Utilities Access Digit 19 — Disconnect Switch/ Circuit Breaker4 0 1 = = 2 = = = = No Disconnect/circuit break Unit Mounted Non-Fused Disconnect Switch Unit Mounted Circuit Breaker Without Convenience Outlet Unpowered Convenience Outlet5 Powered Convenience Outlet5 Without Smoke Detector Return Air Smoke Detector Supply Air Smoke Detector Return/Supply Air Smoke Detector Plenum Smoke Detector9 Digit 25 — System Monitoring Controls6 5 = = = = Without Refrigeration Controls Frostat6 Digit 24 — Smoke Detector7, 8 = = = = = 0 1 2 3 Standard refrigeration system Digit 23 — Refrigeration Controls 0 1 2 3 4 Digit 17 — Condenser Coil Protection Without Communications Options Trane Communications Interface Lontalk Communications Interface Building Automation Control Network Communications Interface No Monitoring Controls Clogged Filter Switch Fan Failure Switch Discharge Air Sensing Clogged Filter Switch and Fan Failure Clogged Switch and Discharge Air Sensing Fan Failure Switch and Discharge Air Sensing Clogged Filter Switch, Fan Failure Switch and Discharge Air Sensing Condensate Drain Pan Overflow Switch Clogged Filter Switch and Condensate Drain Pan Overflow Switch Fan Failure Switch and Condensate Drain Pan Overflow Switch Discharge Air Sensing and Condensate Drain Pan Overflow Switch Clogged Filter Switch, Fan Failure Switch and Condensate Drain Pan Overflow Switch Clogged Filter Switch, Discharge Air Sensing Tube and Condensate Drain Pan Overflow Switch Fan Failure Switch, Discharge Air Sensing Tube and Condensate Drain Pan Overflow Switch 5 Model Number Description H = Digit 26 - System Monitoring Controls 0 A = = B = C = No Monitoring Controls Demand Control Ventilation (CO2)10 FDD (Fault Detection and Diagnostics) FDD (Fault Detection Diagnostics) & Demand Control Ventilation (CO2)10 Digit 27 - Unit Hardware Enhancements 0 1 = = No Enhancements Stainless Steel Drain Pan Digit 28 - Short Circuit Current Rating 0 A = = Standard SCCR 65kA SCCR Option11, 12 Digit 31 - Advanced Unit Controls 0 1 = = Condensate Overflow Switch, Discharge Air Sensing Kit, Frostat, Ventilation Override, Smoke Detector, Dehumidification and Modulating Gas Heat Furnace. Clogged Filter Switch, Fan Failure Switch, Discharge Air Sensing and Condensate Drain Pan Overflow Switch Standard Unit Controls Human Interface14 Note: Most Factory Installed Options available for Downflow Air Discharge units only. Please verify with ordering system for availability. Model Number Notes 1. Some field set up required. 2. Available factory installed on downflow AND horizontal units. Verify with ordering system. 7. Requires ReliaTel Options Module. 8. Option cannot be ordered in conjunction with field installed economizer on downflow units. Must be factory installed. The return air smoke detector may not fit up or work properly on the Voyager units when used in conjunction with 3rd party accessories (such as bolt on heat wheels, economizers, and power exhaust). Do not order the return air smoke detectors when using this type of accessory. 9. Supply and/or return smoke detector may not be used with the plenum smoke detector. 10. Demand Control Ventilation Option includes wiring only. The C02 sensor is a field-installed only option. 11. Only available where MOP is above 60A. 12. 575 VAC option is 25kA. 13. Standard filters are not available with Low Leak Economizers. 14. Human Interface is standard with FDD (Fault Detection Diagnostics). 3. Through-the-base electrical option or Horizontal-Side Access must be ordered with either unit mounted disconnect or circuit breaker. 4. Unit mounted disconnect and circuit breakers are mutually exclusive of each other. 5. Must be ordered with Throughthe-Base Electrical option or Horizontal-Side Access and either Unit Mounted Disconnect or Circuit Breaker. 6. ReliaTel Options Module is required when ordering the following accessories: Clogged Filter Switch, Fan Fail Switch, 6 RT-SVX33E-EN General Information Unit Inspection As soon as the unit arrives at the job site: • Verify that the nameplate data matches the data on the sales order and bill of lading (including electrical data). • Verify that the power supply complies with the unit nameplate specifications. • Visually inspect the exterior of the unit, including the roof, for signs of shipping damage. • Visually inspect the internal components for shipping damage as soon as possible after delivery and before it is stored. Do not walk on the sheet metal base pans. • If concealed damage is discovered, notify the carrier’s terminal of damage immediately by phone and by mail. Concealed damage must be reported within 15 days. Request an immediate joint inspection of the damage by the carrier and the consignee. Do not remove damaged material from the receiving location. Take photos of the damage, if possible. The owner must provide reasonable evidence that the damage did not occur after delivery. • Notify the appropriate sales representative before installing or repairing a damaged unit. WARNING Fiberglass Wool! Product contains fiberglass wool. Disturbing the insulation in this product during installation, maintenance or repair will expose you to airborne particles of glass wool fibers and ceramic fibers known to the state of California to cause cancer through inhalation. You MUST wear all necessary Personal Protective Equipment (PPE) including gloves, eye protection, mask, long sleeves and pants when working with products containing fiberglass wool. Exposition to glass wool fibers without all necessary PPE equipment could result in cancer, respiratory, skin or eye irritation, which could result in death or serious injury. Precautionary Measures First Aid Measures • Eye Contact - Flush eyes with water to remove dust. If symptoms persist, seek medical attention. • Skin Contact - Wash affected areas gently with soap and warm water after handling. Storage Take precautions to prevent condensate from forming inside the unit’s electrical compartments and motors if: 15. The unit is stored before it is installed; or, 16. The unit is set on the roof curb, and temporary heat is provided in the building. Isolate all side panel service entrances and base pan openings (e.g., conduit holes, S/A and R/A openings, and flue openings) from the ambient air until the unit is ready for start-up. Note: Do not use the unit’s heater for temporary heat without first completing the start-up procedure detailed under “Start Up,” p. 33. The manufacturer will not assume any responsibility for equipment damage resulting from condensate accumulation on the unit’s electrical and/or mechanical components. Unit Clearances Figure 1, p. 11 illustrates the minimum operating and service clearances for either a single or multiple unit installation. These clearances are the minimum distances necessary to assure adequate serviceability, cataloged unit capacity, and peak operating efficiency. Providing less than the recommended clearances may result in condenser coil starvation, “short-circuiting” of exhaust and economizer airflows, or recirculation of hot condenser air. Unit Description Before shipment, each unit is leak tested, dehydrated, charged with refrigerant and compressor oil, and run tested for proper control operation. • Avoid breathing fiberglass dust. • Use a NIOSH approved dust/mist respirator. The condenser coils are aluminum fin, mechanically bonded to copper tubing. • Avoid contact with the skin or eyes. Wear long-sleeved, loose-fitting clothing, gloves, and eye protection. Direct-drive, vertical discharge condenser fans are provided with built-in thermal overload protection. • Wash clothes separately from other clothing: rinse washer thoroughly. • Operations such as sawing, blowing, tear-out, and spraying may generate fiber concentrations requiring additional respiratory protection. Use the appropriate NIOSH approved respiration in these situations. The ReliaTel™ Control Module is a microelectronic control system that is referred to as “Refrigeration Module” (RTRM). The acronym RTRM is used extensively throughout this document when referring to the control system network. RT-SVX33E-EN This module through Proportional/Integral control algorithms perform specific unit functions that governs unit operation in response to; zone temperature, supply air 7 General Information temperature, and/or humidity conditions depending on the application. The stages of capacity control for these units are achieved by starting and stopping the compressors. The RTRM is mounted in the control panel and is factory wired to the respective internal components. The RTRM receives and interprets information from other unit modules, sensors, remote panels, and customer binary contacts to satisfy the applicable request for cooling. ReliaTel™ Control Economizer Control Actuator The ECA monitors the mixed air temperature, return air temperature, minimum position setpoint (local or remote), power exhaust setpoint, CO2 setpoint, CO2, and ambient dry bulb/enthalpy sensor or comparative humidity (return air humidity against ambient humidity) sensors, if selected, to control dampers to an accuracy of +/- 5% of stroke. The actuator is spring returned to the closed position any time that power is lost to the unit. It is capable of delivering up to 25 inch pounds of torque and is powered by 24 Vac. RTCI – ReliaTel™ Trane Communication Interface (Optional) This module is used when the application calls for an ICS™ building management type control system. It allows the control and monitoring of the system through an ICS panel. The module can be ordered from the factory or ordered as a kit to be field installed. Follow the installation instruction that ships with each kit when field installation is necessary. RLCI – ReliaTel™ LonTalk Communication Interface (Optional) This module is used when the application calls for an ICS™ building management type control system that is LonTalk. It allows the control and monitoring of the system through an ICS panel. The module can be ordered from the factory or ordered as a kit to be field installed. Follow the installation instruction that ships with each kit when field installation is necessary. RTOM – ReliaTel™ Options Module (Optional) The RTOM monitors the supply fan proving, clogged filter, supply air temperature, exhaust fan setpoint, supply air tempering, Frostat™ and smoke detector. Refer to system input devices and functions for operation. 8 System Input Devices & Functions The RTRM must have a zone sensor or thermostat input in order to operate the unit. The flexibility of having several mode capabilities depends upon the type of zone sensor or thermostat selected to interface with the RTRM. The descriptions of the following basic Input Devices used within the RTRM network are to acquaint the operator with their function as they interface with the various modules. Refer to the unit’s electrical schematics for the specific module connections. The following Controls are Available from the Factory for Field Installation: Supply Fan Failure Input (Optional) The Fan Failure Switch can be connected to sense indoor fan operation: FFS (Fan Failure Switch) If air flow through the unit is not proven by the differential pressure switch connected to the RTOM (factory set point 0.07 “ w.c.) within 40 seconds nominally, the RTRM will shut off all mechanical operations, lock the system out, send a diagnostic to ICS, and the SERVICE output will flash. The system will remain locked out until a reset is initiated either manually or through ICS. Drain Pan Condensate Overflow Switch (Optional) This input incorporates the Condensate Overflow Switch (COF) mounted on the drain pan and the ReliaTel Options Module (RTOM). When the condensate level reaches the trip point for 6 continuous seconds, the RTOM will shut down all unit function until the overflow condition has cleared. The unit will return to normal operation after 6 continuous seconds with the COF in a non-tripped condition. If the condensate level causes the unit to shutdown more than 2 times in a 3 day period, the unit will be locked-out of operation. A manual reset of the diagnostic system through the Zone Sensor or Building Automation System (BAS) will be required. Cycling unit power will also clear the fault." Clogged Filter Switch (Optional) The unit mounted clogged filter switch monitors the pressure differential across the return air filters. It is mounted in the filter section and is connected to the RTOM. A diagnostic SERVICE signal is sent to the remote panel if the pressure differential across the filters is at least 0.5" w.c. The contacts will automatically open when the pressure differential across the filters decreases to approximately 0.4" w.c. The clogged filter output is energized when the supply fan is operating and the clogged filter switch has been closed for at least 2 minutes. RT-SVX33E-EN General Information The system will continue to operate regardless of the status of the filter switch. Please note that on units equipped with factory installed MERV 13 filters, a clogged filter switch with different pressure settings will be installed. This switch will close when the differential pressure is approximately 0.8' w.c. and open when the differential falls to 0.7" w.c. Compressor Disable (CPR1/2) This input incorporates the low pressure control (LPC) of each refrigeration circuit and can be activated by opening a field supplied contact installed on the LTB. If this circuit is open before the compressor is started, the compressor will not be allowed to operate. Anytime this circuit is opened for 1 continuous second during compressor operation, the compressor for that circuit is immediately turned “Off”. The compressor will not be allowed to restart for a minimum of 3 minutes should the contacts close. If four consecutive open conditions occur during the first three minutes of operation, the compressor for that circuit will be locked out, a diagnostic communicated to the remote panel (if installed), and a manual reset will be required to restart the compressor. Low Pressure Control ReliaTel Control When the LPC is opened for 1 continuous second, the compressor for that circuit is turned off immediately. The compressor will not be allowed to restart for a minimum of 3 minutes. If four consecutive open conditions occur during the first three minutes of operation, the compressor will be locked out, a diagnostic communicated to ICS™ if applicable, and a manual reset will be required to restart the compressor. High Pressure Control (Optional) ReliaTel Control The high pressure controls are wired in series between the compressor outputs on the RTRM and the compressor contactor coils. If the high pressure control switch opens, the RTRM senses a lack of current while calling for cooling and locks the compressor out. On dual circuit units, if the high pressure control opens, the compressor on the affected circuit is locked out. A manual reset for the affected circuit is required. Power Exhaust Control (Optional) The power exhaust fan is started whenever the position of the economizer dampers meets or exceed the power exhaust setpoint when the indoor fan is on. The setpoint panel is located in the return air section and is factory set at 25%. RT-SVX33E-EN Lead/Lag Control (Dual Circuit Only) Lead/Lag is a selectable input located on the RTRM. The RTRM is configured from the factory with the Lead/Lag control disabled. To activate the Lead/Lag function, simply cut the wire connected to J3-8 at the RTRM. When it is activated, each time the designated lead compressor is shut off due to the load being satisfied, the lead compressor or refrigeration circuit switches. When the RTRM is powered up, i.e. after a power failure, the control will default to the number one circuit compressor. Evaporator Frost Control This input incorporates the Frostat™ control (FOS) mounted in the indoor coil and can be activated by closing a field supplied contact installed in parallel with the FOS. If this circuit is closed before the compressor is started, the compressor will not be allowed to operate. Anytime this circuit is closed for 1 continuous second during compressor operation, the compressor for that circuit is immediately turned “Off”. The compressor will not be allowed to restart for a minimum of 3 minutes should the FOS open. Smoke Detector Sensor (Optional) This sensor is only applicable on units equipped with a RTOM. It provides high limit “shutdown” of the unit and requires a manual reset. The sensor is used to detect smoke due to fire in the air conditioning or ventilation ducts. The supply and return air smoke detectors are designed to shut off the unit if smoke is sensed in the supply air stream or return air stream. This function is performed by sampling the airflow entering the unit at the return air opening. Follow the instructions provided below to assure that the airflow through the unit is sufficient for adequate sampling. Failure to follow these instructions will prevent the smoke detectors from performing it's design function. Important: Airflow through the unit is affected by the amount of dirt and debris accumulated on the indoor coil and filters. To insure that airflow through the unit is adequate for proper sampling by the return air smoke detector, complete adherence to the maintenance procedures, including recommended intervals between filter changes, and coil cleaning is required. Periodic checks and maintenance procedures must be performed on the smoke detector to insure that it will function properly. For detailed instructions concerning these checks and procedures, refer to the appropriate section(s) of the smoke detector Installation and Maintenance Instructions provided with the literature package for this unit. In order for the supply air smoke detector or return air smoke detector to properly sense smoke in the supply air 9 General Information stream or return air stream, the air velocity entering the smoke detector unit must be between 500 and 4000 feet per minute. Equipment covered in this manual will develop an airflow velocity that falls within these limits over the entire airflow range specified in the evaporator fan performance tables. Zone Sensors Note: Zone sensor required for units configured for Single Zone VAV indoor fan system control to enable Single Zone VAV functionality. Zone Sensor Module (ZSM) (BAYSENS107*) This electronic sensor features three system switch settings (Heat, Cool, and Off) and two fan settings (On and Auto). It is a manual changeover control with single setpoint. (Cooling Setpoint Only) Zone Sensor (BAYSENS109*) This electronic sensor features four system switch settings (Heat, Cool, Auto, and Off) and two fan settings (On and Auto) with four system status LED’s. It is a manual or auto changeover control with dual setpoint capability. It can be used with a remote zone temperature sensor BAYSENS075*. Programmable Zone Sensor (BAYSENS119*) Programmable Night Setback: Auto or manual changeover with seven-day programming. Keyboard selection of Heat, Cool, Fan, Auto, or On. All programmable sensors have System On, Heat, Cool, Service LED/indicators as standard. Night Setback Sensors have one (1) Occupied, one (1) Un-occupied, and one (1) Override program per day. Remote Zone Sensor (BAYSENS073*) This electronic sensor features remote zone sensing and timed override with override cancellation. It is used with a Trane Integrated Comfort™ building management system. Remote Zone Sensor (BAYSENS074*) This electronic sensor features single setpoint capability and timed override with override cancellation. It is used with a Trane Integrated Comfort™ building management system. Remote Zone Sensor (BAYSENS016*) This bullet type temperature sensor can be used for; outside air (ambient) sensing, return air temperature sensing, supply air temperature sensing, remote temperature sensing (uncovered). Wiring procedures vary according to the particular application and equipment 10 involved. Refer to the unit’s wiring diagrams for proper connections. Remote Zone Sensor (BAYSENS075*) This electronic sensor can be used with BAYSENS106*, 108*, 110*, 109* Remote Panels. When this sensor is wired to a BAYSENS109* Remote Panel, wiring must be 18 AWG Shielded Twisted Pair (Belden 8760 or equivalent). Refer to the specific Remote Panel for wiring details. Wireless Zone Sensor (BAYSENS050) This electronic sensor features five system settings (Auto, Off, Cool, Heat, and Emergency Heat) and with On and Auto fan settings. It is a manual or auto changeover control with dual setpoint capability. Other features include a timed override function, lockable system settings, and Fahrenheit or Celsius temperature display. Included with the wireless zone sensor will be a receiver that is to be mounted inside the unit, a mounting bracket, and a wire harness. Thermostat (BAYSTAT150) This thermostat is a multi-stage 3 heat/2 cool, autochangeover digital display thermostat. It is a programmable thermostat, and a 7-day programmable stat with night setback shall be available. In addition, it is wall mounted. Thermostat (BAYSTAT151) This thermostat is a single-stage 1 heat/1 cool, autochangeover digital display thermostat. It is a nonprogrammable, wall-mounted thermostat. Thermostat (BAYSTAT155) This thermostat is a multi-stage 3 heat/2 cool, auto changeover digital display thermostat. It is a nonprogrammable, wall-mounted thermostat, and it can be used for Economizer Operation. Human Interface - 5 Inch Color Touchscreen (Optional) The 5 inch Color Touchscreen Human Interface provides an intuitive user interface to the rooftop unit that speeds up unit commissioning, shortens unit troubleshooting times, and enhances preventative maintenance measures. The human interface includes several features including: • Data trending capabilities by means of time series graphs • Historical alarm messages • Real-time sensor measurements • On board system setpoints • USB port that enables the downloading of component runtime information as well as trended historical sensor data • Customized reports RT-SVX33E-EN Unit Dimensions Figure 1. Typical installation clearances for single & multiple unit applications 5' 8" WITHOUT ECONOMIZER WITH ECONOMIZER 5' 0" RT-SVX33E-EN 11 Unit Dimensions Figure 2. Heat pump models - 12½ - 15 tons 85 5/16" 2167MM 122 5/16" 3107MM 13/16" 20MM FILTER ACCESS DOOR HORIZONTAL 54" 1372MM 1" 25.4MM 6 7/16" 163.51MM DOWNFLOW CONDENSATE DRAIN CONN 1" (25.4MM) NPT 48 1/2" 1231.90MM 56" 1422MM SINGLE POINT POWER ENTRY 33 3/16" 843MM 7/8" (22.23MM) DIA. HOLE (UNIT CONTROL WIRE) 6 13/16" 173MM 121 11/16" 3091MM 8 15/16" 227MM 2 11/16" 68.26MM 84 3/16" 2154MM SERVICE GAUGE PORT ACCESS 3" (76MM) DIA HOLE (UNIT POWER WIRE) * All dimensions are in inches/millimeters. Figure 3. Heat pump models - 12½ - 15 tons * All dimensions are in inches/millimeters. 12 RT-SVX33E-EN Unit Dimensions Figure 4. Heat pump models - 12½ - 15 tons Figure 5. Heat pump models - 12½ - 15 tons 9 1” 25.4 MM CURB FLANGE LONG SIDES SHORT SIDES * All dimensions are in inches/millimeters. * Duct flanges mount 7-7/16" down inside the curb on the 1-1½ curb flanges. Roofcurb is intended for downflow use only. * All dimensions are in inches/millimeters. Figure 6. Heat pump models - 12½ - 15 tons * All dimensions are in inches/millimeters. RT-SVX33E-EN 13 Unit Dimensions Figure 7. Heat pump models - 20 tons 85 5/16" 2167MM 122 5/16" 3107MM 13/16" 20MM FILTER ACCESS DOOR HORIZONTAL 64 1/8" 1629MM 1" 25.4MM 6 7/16" 163.51MM DOWNFLOW CONDENSATE DRAIN CONN 1" (25.4MM) NPT 48 1/2" 1231.90MM 33 3/16" 843MM 56" 1422MM SINGLE POINT POWER ENTRY 7/8" (22.23MM) DIA. HOLE (UNIT CONTROL WIRE) 6 13/16" 173MM 121 11/16" 3091MM 8 15/16" 227MM 2 11/16" 68.26MM 84 3/16" 2154MM SERVICE GAUGE PORT ACCESS 3" (76MM) DIA HOLE (UNIT POWER WIRE) * All dimensions are in inches/millimeters. Figure 8. Heat pump models - 20 tons * All dimensions are in inches/millimeters. 14 RT-SVX33E-EN Unit Dimensions Figure 9. Heat pump models - 20 tons * All dimensions are in inches/millimeters. Figure 10. Heat pump models - 20 tons Figure 11. Heat pump models - 20 tons 9 1” 25.4 MM CURB FLANGE LONG SIDES SHORT SIDES * All dimensions are in inches/millimeters. * Duct flanges mount 7-7/16" down inside the curb on the 1-1½ curb flanges. Roofcurb is intended for downflow use only. * All dimensions are in inches/millimeters. RT-SVX33E-EN 15 Unit Dimensions Figure 12. Downflow & horizontal condensate locations Table 1. Unit dimensions Condensate Drain Location Downflow Only Tons A B C D F G 12½, 15, 20 26 7/16 28 3/4 19 15/16 4 1/4 4 1/4 H 76 5/16 68 11/16 Condensate Drain Size 1 NPT Downflow Horizontal E J E K - 26 3/4 - 5 3/8 Figure 13. Through the base utility locations and access panel swing clearances TOP VIEW SHOWING THROUGH THE BASE ELECTRICAL UTILITY LOCATIONS AND ACCESS PANEL SWING CLEARANCES. B 6 7/8" SWING RADIUS (E) HORIZONTAL FILTER ACCESS PANEL SWING RADIUS (A) ID SECTION ACCESS PANEL SWING RADIUS (D) ID FAN SECTION ACCESS PANEL Table 2. SWING RADIUS (C) OD SECTION ACCESS PANEL THROUGH THE BASE ELECTRICAL Swing clearances Unit Model # A B WSD150-180 42 3/8 48 3/8 WSD240 29 1/2 56 WSH150-180 42 3/8 N/A WSH240 29 1/2 N/A C D E 31 N/A N/A 38 1/2 18 1/2 N/A 31 N/A 12 38 1/2 18 1/2 14 Note: All dimensions are in inches. 16 RT-SVX33E-EN Unit Weights Table 3. Typical unit weights and point loading data Corner Weights (lbs.) Center of Gravity (in.) Unit Description Net Weight A B C D WS*150 1978 633 514 376 455 56 36 WS*155 1982 634 515 377 456 56 36 WS*180 1982 634 515 377 456 56 36 WS*200 2107 674 485 400 590 57 35 WS*240 2107 674 485 400 590 57 35 Length Width 4. Test-lift the unit to ensure it is properly rigged and balanced, make any necessary rigging adjustments. 5. Lift the unit and position it into place. 6. Downflow units; align the base rail of the unit with the curb rail while lowering the unit onto the curb. Make sure that the gasket on the curb is not damaged while positioning the unit. Figure 14. Rigging and center of gravity data Note: Corner weights are given for information only. Unit is to be supported continuously by a curb or equivalent frame support. Rigging Refer to Figure 14 and Table 3 for typical unit operating weights rigging before proceeding. WARNING Heavy Objects! Ensure that all the lifting equipment used is properly rated for the weight of the unit being lifted. Each of the cables (chains or slings), hooks, and shackles used to lift the unit must be capable of supporting the entire weight of the unit. Lifting cables (chains or slings) may not be of the same length. Adjust as necessary for even unit lift. Other lifting arrangements could cause equipment or property damage. Failure to follow instructions above or properly lift unit could result in unit dropping and possibly crushing operator/ technician which could result in death or serious injury. WARNING Improper Unit Lift! Test lift unit approximately 24 inches to verify proper center of gravity lift point. To avoid dropping of unit, reposition lifting point if unit is not level. Failure to properly lift unit could result in unit dropping and possibly crushing operator/technician which could result in death or serious injury and possible equipment or property-only damage. 1. Remove the shipping crate from around the unit. Do not remove the crating from the top of the unit. 2. Rig the unit as shown in Figure 14. Attach adequate strength lifting slings to all four lifting brackets in the unit base rail. Do not use cables, chains, or slings except as shown. 3. Install a lifting bar, as shown in Figure 14, to protect the unit and to facilitate a uniform lift. The minimum distance between the lifting hook and the top of the unit should be 7 feet. RT-SVX33E-EN 17 Installation Foundation All outdoor ductwork between the unit and the structure should be weather proofed after installation is completed. NOTICE: Water Damage! Non-factory penetrations through the base of this unit are not allowed. Any penetration in the base of the unit may affect the water tight integrity of the unit and lead to water leaks into the conditioned space. Failure to follow instructions could result in equipment and property damage. Notes: • For units with optional Condensate Overflow Switch (COF), the switch will not work properly if unit is not level or slightly sloped toward switch. • To assure proper condensate flow during operation the unit and the curb must be level. If the unit is installed at ground level, elevate it above the snow line. Provide concrete footings at each support location with a “full perimeter” support structure or a slab foundation for support. Refer to Table 3, p. 17 for the unit’s operating and point loading weights when constructing a footing foundation. If anchoring is required, anchor the unit to the slab using hold down bolts or isolators. Isolators should be installed to minimize the transmission of vibrations into the building. For rooftop applications, ensure the roof is strong enough to support the combined unit and support structural weight. WARNING Risk of Roof Collapsing! Confirm with a structural engineer that the roof structure is strong enough to support the combined weight of the roofcurb and the unit. Refer to Table 3, p. 17 for typical unit and curb weights. Failure to ensure proper structural roof support could cause the roof to collapse, which could result in death or serious injury and property damage. If anchoring is required, anchor the unit to the roof with hold-down bolts or isolators. Check with a roofing contractor for proper waterproofing procedures. Note: For sound consideration, cut only the holes in the roof deck for the ductwork penetrations. Do not cut out the entire roof deck within the curb perimeter. If a Curb Accessory Kit is Not Used: 1. The ductwork can be attached directly to the factoryprovided flanges around the unit’s supply and return air openings. Be sure to use flexible duct connections at the unit. 2. For “built-up” curbs supplied by others, gaskets must be installed around the curb perimeter flange and the supply and return air opening flanges. General Unit Requirements The checklist listed below is a summary of the steps required to successfully install a commercial unit. This checklist is intended to acquaint the installing personnel with what is required in the installation process. It does not replace the detailed instructions called out in the applicable sections of this manual. • Check the unit for shipping damage and material shortage; file a freight claim and notify appropriate sales representative. • Verify correct model, options and voltage from nameplate. • Verify that the installation location of the unit will provide the required clearance for proper operation. • Assemble and install the roof curb (if applicable). Refer to the latest edition of the curb installers guide that ships with each curb kit. • Fabricate and install ductwork; secure ductwork to curb. • Rigging the unit. • Set the unit onto the curb; check for levelness. • Ensure unit-to-curb seal is tight and without buckles or cracks. • Install and connect a condensate drain line to the evaporator drain connection. Factory Installed Economizer • Ductwork Elbows with turning vanes or splitters are recommended to minimize air noise due to turbulence and to reduce static pressure. When attaching the ductwork to the unit, provide a watertight flexible connector at the unit to prevent operating sounds from transmitting through the ductwork. 18 Ensure the standard economizer has been pulled out into the operating position. Refer to the economizer Installation Instructions for proper setup. Note: Low Leak Economizers do not pull out. Refer to Low Leak Economizers Installation Instructions for proper setup. • Install all access panels. RT-SVX33E-EN Installation Electric Heat Requirements • Verify that the power supply complies with the electric heater specifications on the unit and heater nameplate. • Inspect the heater junction box and control panel; tighten any loose connections. • Check electric heat circuits for continuity. Condensate Drain Configuration An evaporator condensate drain connection is provided on each unit. Refer to “Unit Dimensions,” p. 11 for the appropriate drain location. A condensate trap must be installed at the unit due to the drain connection being on the “negative pressure” side of the fan. Install the P-Trap using the guidelines in Figure 15, p. 19. A condensate drain line must be connected to the P-Trap. Pitch the drain lines at least 1/2 inch for every 10 feet of horizontal run to assure proper condensate flow. Do not allow the horizontal run to sag causing a possible doubletrap condition which could result in condensate backup due to “air lock”. Figure 15. Condensate trap installation Electrical Requirements WARNING Proper Field Wiring and Grounding Required! All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes. Failure to follow code could result in death or serious injury. Main Electrical Power Requirements • Verify that the power supply complies with the unit nameplate specifications. • Inspect all control panel components; tighten any loose connections. • Connect properly sized and protected power supply wiring to a field-supplied/installed disconnect switch and to the main power terminal block (HTB1) in the unit control panel. • Install proper grounding wires to an earth ground. Note: All field-installed wiring must comply with NEC and applicable local codes. Low Voltage Wiring (AC & DC) Requirements • Install the zone thermostat, with or without switching subbase. • Connect properly sized control wiring to the proper termination points between the zone thermostat and the unit control panel. Field Installed Power Wiring Filter Installation Each unit ships with 2 inch filters installed. The quantity of filters is determined by unit size. Access to the filters is obtained by removing the indoor fan access panel. If included, filters are removed by pulling the filter removal tool. Refer to the unit Service Facts (shipped with each unit) for filter requirements. Note: Do not operate the unit without filters. An overall dimensional layout for the standard field installed wiring entrance into the unit is illustrated in the Unit Dimensions section. To insure that the unit’s supply power wiring is properly sized and installed, follow the guidelines outlined below. Note: All field installed wiring must conform to NEC guidelines as well as State and Local codes. Verify that the power supply available is compatible with the unit’s nameplate ratings. The available supply power must be within 10% of the rated voltage stamped on the nameplate. Use only copper conductors to connect the power supply to the unit. NOTICE: Use Copper Conductors Only! Unit terminals are not designed to accept other types of conductors. Failure to use copper conductors could result in equipment damage. RT-SVX33E-EN 19 Installation Note: If the unit is not equipped with an optional factory installed nonfused disconnect switch or circuit breaker, a field supplied disconnect switch must be installed at or near the unit in accordance with the National Electrical Code (NEC latest edition). Figure 16. Through the base electrical option Main Unit Power WARNING Proper Field Wiring and Grounding Required! All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes. Failure to follow code could result in death or serious injury. Standard Wiring The electrical service must be protected from over current and short circuit conditions in accordance with NEC requirements. Protection devices must be sized according to the electrical data on the nameplate. 1. If the unit is not equipped with an optional factory installed nonfused disconnect switch or circuit breaker, a field supplied disconnect switch must be installed at or near the unit in accordance with the National Electrical Code (NEC latest edition). 2. Location of the applicable electrical service entrance is illustrated in the Unit Dimensions section. Complete the unit’s power wiring connections onto either; the main terminal block HTB1 inside the unit control panel, the factory mounted nonfused disconnect switch (UCD) or circuit breaker (UCB), or the electric heat terminal block. Refer to the customer connection diagram that shipped with the unit for specific termination points. 3. Provide proper grounding for the unit in accordance with local and national codes. Optional TBUE Wiring (Through the Base Electrical Option) 1. Location of the applicable electrical service is illustrated in the following illustration. Refer to the customer connection diagram that is shipped with the unit for specific termination points. The termination points, depending on the customer option selected would be a factory mounted nonfused disconnect switch (UDC) or circuit breaker (UCB). 2. Provide proper grounding for the unit in accordance with local and national codes. 20 Field Installed Control Wiring An overall layout of the various control options available with the required number of conductors for each control device is illustrated in Figure 18, p. 22. Note: All field wiring must conform to NEC guidelines as well as state and local codes. Control Power Transformer The 24 volt control power transformers are to be used only with the accessories called out in this manual. Transformers rated greater than 50 Vac are equipped with internal circuit breakers. If a circuit breaker trips, turn “Off” all power to the unit before attempting to reset it. WARNING Hazardous Voltage! Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury. The transformer is located in the control panel. The circuit breaker is located on the left side of the transformer and can be reset by pressing in on the black reset button. Controls Using 24 VAC Before installing any connecting wiring, refer to “Unit Dimensions,” p. 11 for the electrical access locations provided on the unit and Table 4, p. 21 for AC conductor sizing guidelines, and; RT-SVX33E-EN Installation 1. Use copper conductors unless otherwise specified. 2. Ensure that the AC control wiring between the controls and the unit’s termination point does not exceed three (3) ohms/conductor for the length of the run. Figure 17. Reliatel conventional thermostat field wiring diagram RTRM NOTICE: Component Failure! Resistance in excess of 3 ohms per conductor could result in component failure due to insufficient AC voltage supply. 3. Be sure to check all loads and conductors for grounds, shorts, and mis-wiring. 4. Do not run the AC low voltage wiring in the same conduit with the high voltage power wiring. 5. Route low voltage wiring per illustrations on Figure 17, p. 21. Table 4. Electromechanical thermostat 24 Vac conductors with ReliaTel™ Distance from Unit to Control Recommended Wire Size 000 - 460 feet (000 - 140 m) 18 gauge (0.75 mm2) 461 - 732 feet (141 - 223 m) 16 gauge (1.3 mm2) 733 - 1000 feet (224 - 305 m) 14 gauge (2.0 mm2) Controls Using DC Analog Input/Outputs (Standard Low Voltage Multiconductor Wire) Before installing any connecting wiring between the unit and components utilizing a DC analog input\output signal, refer to “Unit Dimensions,” p. 11 for the electrical access locations provided on the unit. 1. Table 5, p. 21 lists the conductor sizing guidelines that must be followed when interconnecting the DC binary output devices and the system components utilizing a DC analog input\output signal to the unit. Note: Resistance in excess of 2.5 ohms per conductor can cause deviations in the accuracy of the controls. 2. Ensure that the wiring between controls and the unit’s termination point does not exceed two and a half (2.5) ohms/conductor for the length of the run. 3. Do not run the electrical wires transporting DC signals in or around conduit housing high voltage wires. Table 5. DC conductors zone sensor module wiring Distance from Unit to Control Recommended Wire Size 0 - 150 feet (0 - 45.7 m) 22 gauge (0.33 mm2) 151 - 240 feet (46 - 73.1 m) 20 gauge (0.50 mm2) 241 -385 feet (73.5 - 117.3 m) 18 gauge (0.75 mm2) 386 - 610 feet (117.7 - 185.9 m) 16 gauge (1.3 mm2) 611 - 970 feet (186.2 - 295.7 m) 14 gauge (2.0 mm2) RT-SVX33E-EN 21 Installation Figure 18. Typical field wiring diagrams for optional controls (ReliaTel™ only) BAYSENS075* ASYSTAT669* BAYSENS107* BAYSTAT023* BAYSENS119* ASYSTAT666* BAYSENS077* ASYSTAT669* BAYSENS075* ASYSTAT669* BAYSENS073* BAYSENS109* BAYSENS075* ASYSTAT669* BAYSENS074* BAYSENS109* 22 RT-SVX33E-EN Installation Space Temperature Averaging Space temperature averaging is accomplished by wiring a number of remote sensors in a series/parallel circuit. Using the BAYSENS016* or BAYSENS075*, at least four sensors are required to accomplish space temperature averaging. Example #1 illustrates two series circuits with two sensors in each circuit wired in parallel. The square of any number of remote sensors is required. Example #2 illustrates three sensors squared in a series/parallel circuit. Using BAYSENS075*, two sensors are required to accomplish space temperature averaging. Example #3 illustrates the circuit required for this senor. Table 6, p. 24 lists the temperature versus resistance coefficient for all sensing. Figure 19. Space temperature averaging examples RT-SVX33E-EN 23 Installation Table 6. Temperature vs. resistance Example: If the voltage readings of the supply power measured 221, 230, and 227, the average volts would be: Temperature 221 + 230 + 227 ----------------------------------------------- = 2.2percent 3 Degrees F° Degrees C° Nominal Resistance -20° -28.9° 170.1 K - Ohms VD (reading farthest from average) = 221 -15° -26.1° 143.5 K - Ohms The percentage of Imbalance equals: -10° -23.3° 121.4 K - Ohms -5° -20.6° 103.0 K - Ohms 0° -17.8° 87.56 K - Ohms 74.65 K - Ohms 226 – 221 100 ---------------------------- = 2.2percent 226 The 2.2% imbalance in this example exceeds the maximum allowable imbalance of 2.0%. This much imbalance between phases can equal as much as a 20% current imbalance with a resulting increase in motor winding temperatures that will decrease motor life. If the voltage imbalance is over 2%, notify the proper agencies to correct the voltage problem before operating this equipment. 5° -15.0° 10° -12.2° 63.80 K - Ohms 15° -9.4° 54.66 K - Ohms 20° -6.7° 46.94 K - Ohms 25° -3.8° 40.40 K - Ohms 30° -1.1° 34.85 K - Ohms 35° 1.7° 30.18 K - Ohms 40° 4.4° 26.22 K - Ohms 45° 7.2° 22.85 K - Ohms 50° 10.0° 19.96 K - Ohms 55° 12.8° 17.47 K - Ohms 60° 15.6° 15.33 K - Ohms 65° 18.3° 13.49 K - Ohms 70° 21.1° 11.89 K - Ohms Proper electrical supply phasing can be quickly determined and corrected before starting the unit by using an instrument such as an Associated Research Model 45 Phase Sequence Indicator and following the steps below: 75° 23.9° 10.50 K - Ohms • 80° 26.7° 9.297 K - Ohms 85° 29.4° 8.247 K - Ohms 90° 32.2° 7.330 K - Ohms Turn the field supplied disconnect switch that provides power to the main power terminal block or to the “Line” side of the optional factory mounted disconnect switch to the “Off” position. 95° 35.0° 6.528 K - Ohms • 100° 37.8° 5.824 K - Ohms Connect the phase sequence indicator leads to the terminal block or to the “Line” side of the optional factory mounted disconnect switch as follows; Electrical Phasing (Three Phase Motors) The compressor motor(s) and the supply fan motor are internally connected for the proper rotation when the incoming power supply is phased as A, B, C. Voltage Imbalance • Black (phase A) to L1 Three phase electrical power to the unit must meet stringent requirements for the unit to operate properly. Measure each leg (phase-to-phase) of the power supply. Each reading must fall within the utilization range stamped on the unit nameplate. If any of the readings do not fall within the proper tolerances, notify the power company to correct this situation before operating the unit. • Red (phase B) to L2 • Close the field supplied main power disconnect switch or circuit protector switch that provides the supply power to the unit. • Excessive three phase voltage imbalance between phases will cause motors to overheat and eventually fail. The maximum allowable voltage imbalance is 2%. Measure and record the voltage between phases 1, 2, and 3 and calculate the amount of imbalance as follows: Observe the ABC and CBA phase indicator lights on the face of the sequencer. The ABC indicator light will glow if the phase is ABC. If the CBA indicator light glows, open the disconnect switch or circuit protection switch and reverse any two power wires. • Restore the main electrical power and recheck the phasing. If the phasing is correct, open the disconnect switch or circuit protection switch and remove the phase sequence indicator. % Voltage Imbalance = AV – VD 100 ----------------------- AV • Yellow (phase C) to L3 where Average Voltage (AV); Volt1 + Volt2 + Volt3 AV = ----------------------------------------------------------------- 3 V1, V2, V3 = Line Voltage Readings VD = Line Voltage reading that deviates the farthest from the average voltage. 24 RT-SVX33E-EN Installation Compressor Crankcase Heaters NOTICE: Compressors Failure! Final Steps Use the checklist provided below in conjunction with the checklist in “General Unit Requirements,” p. 18, to ensure that the unit is properly installed and ready for operation. • Check all electrical connections for tightness and “point of termination” accuracy. • Verify that the condenser airflow is unobstructed. Each compressor is equipped with a crankcase heater. The proper operation of the crankcase heater is important to maintain an elevated compressor oil temperature during the “Off” cycle to reduce oil foaming during compressor starts. Oil foaming occurs when refrigerant condenses in the compressor and mixes with the oil. In lower ambient conditions, refrigerant migration to the compressor could increase. • Verify that the condenser fan and indoor blower turn freely without rubbing and are properly tightened on the shafts. • Check the supply fan belts for proper tension and the fan bearings for sufficient lubrication. If the belts require adjustment, or if the bearings need lubricating, refer to the maintenance section of this manual for instructions. When the compressor starts, the sudden reduction in crankcase pressure causes the liquid refrigerant to boil rapidly causing the oil to foam. This condition could damage compressor bearings due to reduced lubrication and could cause compressor mechanical failures. • Verify that a condensate trap is installed and the piping is properly sized and pitched. • Verify that the correct size and number of filters are in place. • Inspect the interior of the unit for tools and debris and install all panels in preparation for starting the unit. Unit must be powered and crankcase heaters energized at least 8 hours BEFORE compressors are started. This will protect the compressors from premature failure. Before starting the unit in the “Cooling” mode, set the system switch to the “Off” position and turn the main power disconnect to the “On” position and allow the crankcase heater to operate a minimum of 8 hours. Before closing the main power disconnect switch, insure that the “System” selection switch is in the “Off” position and the “Fan” selection switch is in the “Auto” position. Close the main power disconnect switch and the unit mounted disconnect switch, if applicable. ReliaTel Controls Upon power initialization, the RTRM performs selfdiagnostic checks to insure that all internal controls are functional. It also checks the configuration parameters against the components connected to the system. The Liteport LED located on the RTRM module is turned “On” within one second of power-up if internal operation is okay. Use one of the following “Test” procedure to bypass some time delays and to start the unit at the control panel. Each step of unit operation can be activated individually by temporarily shorting across the “Test” terminals for two to three seconds. The Liteport LED located on the RTRM module will blink when the test mode has been initiated. The unit can be left in any “Test” step for up to one hour before it will automatically terminate, or it can be terminated by opening the main power disconnect switch. Once the test mode has been terminated, the Liteport LED will glow continuously and the unit will revert to the “System” control. RT-SVX33E-EN 25 Factory-Mounted Unit Options Circuit Breaker (FIYUCB) & Unit Disconnect (FIYUDC) WARNING Hazardous Voltage w/Capacitors! Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/ tagout procedures to ensure the power cannot be inadvertently energized. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury. For additional information regarding the safe discharge of capacitors, see PROD-SVB06A-EN power conductors to the lugs provided. Connect the ground wire to the unit ground lug. Note: Wire size for the length of run should be determined using the circuit ampacity found on the unit nameplate and the N.E.C. 4. Route low voltage (class II), control wiring through hole in base of unit but not through high voltage conduit. Feed control wiring through bushing provided on side panel and into the flexible conduit provided in the heat section of the unit (Figure 20). Route wires through loose wire ties provided in unit as in Figure 20. 5. Tighten the wire ties. Secure the excess wire bundle under the wire ties in the outdoor section. Do not leave excess wire in the electrical enclosure. Use the unit wiring diagram to make the low voltage connections. Figure 20. Main power entrance for units with factory mounted disconnect or circuit breaker WARNING Proper Field Wiring and Grounding Required! All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes. Failure to follow code could result in death or serious injury. Wire Ties Important: All phases of this installation must comply with NATIONAL, STATE, and LOCAL CODES. In addition to local codes, the installation must comply with National Electric Code - ANSI/NFPA NO. 70 LATEST REVISION. 1. Field connections are made by first removing all access panels on the front of the unit. Unscrew the assembly around the outside of the disconnect switch or circuit breaker. This assembly is located between the evaporator and heat section of the unit (Figure 20, p. 26). For downflow configurations, the hole in the base section is for both high and low voltage power wiring on down flow units. Horizontal units will route through the front plate located directly under the circuit breaker or disconnect panel. The hole is sized for 1 1/2" conduit. Horizontal units will use the front plate located directly under the circuit breaker panel. 2. If the conduit required for your application is larger, remove the termination plate and connect to the larger hole using field supplied reducing washers. 3. Route the power wires and ground conductor through conduit and into the bottom of the factory installed disconnect switch or circuit breaker. Connect the 26 RT-SVX33E-EN Factory-Mounted Unit Options Powered/Unpowered Convenience Outlet WARNING Hazardous Voltage w/Capacitors! Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/ tagout procedures to ensure the power cannot be inadvertently energized. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury. For additional information regarding the safe discharge of capacitors, see PROD-SVB06A-EN WARNING Proper Field Wiring and Grounding Required! All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes. Failure to follow code could result in death or serious injury. Powered Convenience Outlet Powered Option (FIYCOPO) When the powered convenience outlet option is installed, the unit will include a dedicated transformer located in the evaporator section of the unit. Additionally, a service receptacle disconnect switch will be provided on the side wall of the evaporator section. The service receptacle switch is shipped in the OFF position. The powered outlet comes completely wired from the factory except for 208 volt applications. 1. For 208 volt applications, disconnect and tape the blue 230 volt wire. 2. Then connect the brown 208 volt wire. Figure 21. Wiring schematic 12½ through 25 ton options RT-SVX33E-EN 27 Factory-Mounted Unit Options Unpowered Convenience Outlet Unpowered Option (FIYCOUP) 1. When the unpowered convenience outlet option is installed, remove the receptacle. 2. The field wiring should be routed through the hole in the base for downflow applications or front panel for horizontal applications then through holes provided in the “J” box (bottom for EMT and top for flexible conduit). 3. Connect the three (3) wires to terminals inside outlet box. Figure 22. Power options WARNING Hazardous Voltage w/Capacitors! Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/ tagout procedures to ensure the power cannot be inadvertently energized. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury. For additional information regarding the safe discharge of capacitors, see PROD-SVB06A-EN WARNING Proper Field Wiring and Grounding Required! A - Powered B - Powered Return Air Smoke Detector Pre-Requisite All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes. Failure to follow code could result in death or serious injury. 1. Remove the smoke detector assembly from its shipping position in the indoor fan compartment. This assembly is attached with three screws to the indoor fan board near the top of the unit. Note: The following field installation instructions apply to downflow only. Horizontal return air smoke detectors require no field installation. 2. Remove and discard the shipping bracket from the smoke detector assembly. This is the angled piece of sheet metal that secured the smoke detector assembly to the interior parts of the unit during shipment. When a unit is ordered with a downflow economizer and a return air smoke detector as factory installed options, the return air smoke detector cannot be completely installed because the economizer, when it is in the shipping position, is occupying the space where the return air smoke detector is to be installed. 3. Place the end of the smoke detector 16 inch metal exhaust tube provided into the bottom hole in the back of the smoke detector. Line up the tab in the exhaust tube with one of the slots in the detector and insert the tube until the tube can be rotated. Rotate the tube 45 degrees to lock it in place. The partial assembly and set-up required for each factory installed economizer must be completed up to the point where the barometric relief hood is to be installed into the unit. Prior to this operation, go to Step 5 of this instruction and perform the operations described there. After this is completed, the economizer installation is to be completed in its entirety as outlined in the installation guide. Figure 23. Brackets Smoke Detector Installation Important: The shipping screw that holds the barometric relief damper must be removed before proceeding with the smoke detector installation. After completion of the economizer installation as outlined above, proceed with the installation of the return air smoke detector as follows: 28 RT-SVX33E-EN Factory-Mounted Unit Options Figure 24. Return air smoke detector for downflow units TWO PIECE HOOD PLASTIC ELBOW METAL INTAKE TUBE SMOKE DETECTOR COPPER TUBE (FACTORY INSTALLED) VINYL TUBES (7-3/4 INCHES LONG) VINYL TUBES (2 INCHES LONG) METAL EXHAUST TUBE (16.34 INCHES LONG) 4. Slide one 2” piece of the vinyl tubing provided onto the short smoke detector inlet tube which protrudes out of the back side of the smoke detector. Push this piece of vinyl tubing onto the inlet tube until it contacts the end of the plastic extension on the backside of the smoke detector. 5. Slide the long piece of vinyl tubing provided onto one leg of the plastic barbed elbow provided. Slide the other end of this piece of vinyl tubing with the elbow attached approximately 1” onto the end of the copper sampling tube installed in the unit’s return air opening. Position the leg of elbow without the vinyl tubing such that it points toward the front side of the unit (directly out of the unit toward the filter access panel). 6. Mount the smoke detector assembly into the unit. Align the smoke detector (exhaust tube down) with the holes in the outer panel of the barometric relief hood and position the smoke detector flush on the panel. Note: On all units there is a hole with a plastic snap bushing located on the inner vertical side of the barometric relief hood that the long exhaust tube must pass through. Be sure that the exhaust tube is aligned with this hole before positioning the smoke detector flush on the outer panel of the barometric relief hood. 7. Secure the smoke detector to the hood with two #10-16 x 3/4’ sheet metal screws provided. Note: In order to perform the last part of this operation, it will be necessary to remove the barometric relief RT-SVX33E-EN TUBES INSTALL FROM BOTTOM, TOP DOES NOT NEED TO BE REMOVED FROM SMOKE DETECTOR filter, open the barometric relief damper, and reach inside through the barometric relief outlet to access and connect the copper exhaust elbow to the smoke detector exhaust tube. 8. Connect the leg of the plastic elbow without the vinyl tubing attached that was installed in Step 5 to the smoke detector inlet tube pushing it onto the piece of vinyl tubing attached to the inlet tube. 9. Refer to Figure 25, p. 30 for wire connections of return air smoke detector to the unit wiring harness. 10. This completes the installation of the return air smoke detector. If the unit’s air filter(s) and/or barometric relief filter were removed to ease installation of the smoke detector, they need to be replaced at this time. Airflow & Sampling Refer to the instructions provided below regarding unit airflow to assure that the return air smoke detector will function properly. Important: The return air smoke detector is designed to shut off the unit if smoke is sensed in the return air stream. This function is performed by sampling the airflow entering the unit at the return air opening. Follow the instructions provided below to assure that the airflow through the unit is sufficient for adequate sampling. Failure to follow these instructions will prevent the smoke detector from performing its design function. 29 Factory-Mounted Unit Options In order for the return air smoke detector to properly sense smoke in the return air stream, the air velocity entering the unit must be between 500 and 4000 feet per minute. Figure 25. Smoke detector wiring scheme Notes: • Airflow through the unit is affected by the amount of dirt and debris accumulated on the indoor coil and filters. To insure that airflow through the unit is adequate for proper sampling by the return air smoke detector, complete adherence to the maintenance procedures, including recommended intervals between filter changes and coil cleaning, is required. • Periodic checks and maintenance procedures must be performed on the smoke detector to insure that it will function properly. For detailed instructions concerning these checks and procedures, refer to the appropriate section(s) of the smoke detector Installation and Maintenance Instructions provided with the literature package for this unit. Important: 30 Refer to the service literature provided for testing and other information about the smoke detector or if problems are encountered. RT-SVX33E-EN Pre-Start Test Modes There are three methods in which the “Test” mode can be cycled at LTB-Test 1 and LTB-Test 2. 1. Step Test Mode - This method initiates the different components of the unit, one at a time, by temporarily shorting across the two test terminals for two to three seconds. For the initial start-up of the unit, this method allows the technician to cycle a component “On” and have up to one hour to complete the check. 2. Resistance Test Mode - This method can be used for start-up providing a decade box for variable resistance outputs is available. This method initiates the different components of the unit, one at a time, when a specific Table 7. resistance value is placed across the two test terminals. The unit will remain in the specific test mode for approximately one hour even though the resistance is left on the test terminals. 3. Auto Test Mode - This method is not recommended for start-up due to the short timing between individual component steps. This method initiates the different components of the unit, one at a time, when a jumper is installed across the test terminals. The unit will start the first test step and change to the next step every 30 seconds. At the end of the test mode, control of the unit will automatically revert to the applied “System” control method. For unit test steps, test modes, and step resistance values to cycle the various components, refer to Table 7, p. 31. Service test guide for component operation TEST STEP 1 2 MODE Fan Econ2. Comp 1 Comp 2 Heat 1 Heat 2 Fan On Minimum Position Off Setpoint 0% Off Off Off 2.2K Minimum Ventilation On Selectable Off Off Off Off Economizer Test Open On Open Off Off Off Off 3.3K Ohms 3 Cool Stage 1 On Minimum Position On1. Off Off Off 4.7K 43. Cool Stage 2 On Minimum Position On1. On1. Off Off 6.8K 53. Reheat On Minimum On On Off Off 33K 63. Heat Stage 1 On Minimum Off Off On Off 10K 73. Heat Stage 2 On Minimum Off Off On On 15K Notes: 1. The condenser fans will operate any time a compressor is "On" providing the outdoor air temperatures are within the operating values. 2. The exhaust fan will turn on anytime the economizer damper position is equal to or greater than the exhaust fan setpoint. 3. Steps for optional accessories and non-applicable modes in unit will be skipped. RT-SVX33E-EN 31 Pre-Start Verifying Proper Air Flow (Units with Belt Drive Indoor Fan) Much of the systems performance and reliability is closely associated with, and dependent upon having the proper airflow supplied both to the space that is being conditioned and across the evaporator coil. The indoor fan speed is changed by opening or closing the adjustable motor sheave. Before starting the SERVICE TEST, set the minimum position setpoint for the economizer to 0 percent using the setpoint potentiometer located on the Economizer Control (ECA), if applicable. Return Air Smoke Detector The return air smoke detector is designed to shut off the unit if smoke is sensed in the return air stream. Sampling the airflow entering the unit at the return air opening performs this function. In order for the smoke detector to properly sense smoke in the return air stream, the air velocity entering the unit must be between 500 and 4000 feet per minute. Equipment covered in this manual will develop an airflow velocity that falls within these limits over the entire airflow range specified in the evaporator fan performance tables. ReliaTel Control Using the Service Test Guide in Table 7, p. 31, momentarily jump across the Test 1 & Test 2 terminals on LTB1 one time to start the Minimum Ventilation Test. Once the supply fan has started, check for proper rotation. The direction of rotation is indicated by an arrow on the fan housing. With the fan operating properly, determine the total system airflow (CFM) by; 1. Measuring the actual RPM, 2. Measure the amperage at the supply fan contactor and compare it with the full load amp (FLA) rating stamped on the motor nameplate. a. Calculate the theoretical BHP Actual Motor Amps X Motor HP Motor Nameplate Amps b. Using the fan performance tables in the unit Service Facts, plot the actual RPM (step 1) and the BHP (step 2a) to obtain the operating CFM. 3. If the required CFM is too low, (external static pressure is high causing motor HP output to be below table value), a. Relieve supply and/or return duct static. b. Change indoor fan speed and repeat steps 1 and 2. • To Increase Fan RPM; Loosen the pulley adjustment set screw and turn sheave clockwise. • To Decrease Fan RPM; Loosen the pulley adjustment set screw and turn sheave counterclockwise. • If the required CFM is too high, (external static pressure is low causing motor HP output to be above table value), change indoor fan speed and repeat steps 1 and 2. • To stop the SERVICE TEST, turn the main power disconnect switch to the “Off” position or proceed to the next component start-up procedure. Remove electro mechanical test mode connections (if applicable). 32 RT-SVX33E-EN Start Up Economizer Start-Up Using the Service Test Guide in Table 7, p. 31, momentarily jump across the Test 1 & Test 2 terminals on LTB1 one time to start the Minimum Ventilation Test. 1. Set the minimum position setpoint for the economizer to the required percentage of minimum ventilation using the setpoint potentiometer located on the Economizer Control Actuator (ECA). The economizer will drive to its minimum position setpoint, exhaust fans (if applicable) may start at random, and the supply fan will start when the SERVICE TEST is initiated. The Exhaust Fan will start anytime the economizer damper position is equal to or greater than the exhaust fan setpoint. 2. Verify that the dampers stroked to the minimum position. 3. Momentarily jump across the Test 1 & Test 2 terminals on LTB one additional time if continuing from previous component start-up or until the desired start-up component Test is started. 4. Verify that the dampers stroked to the full open position. b. If the electrical phasing is incorrect, before condemning a compressor, interchange any two leads (at the compressor Terminal block) to check the internal phasing. Refer to the following illustration for the compressor terminal/phase identification. If the compressor runs backward for an extended period not to exceed 5 seconds, the compressor will be damaged the motor winding can overheat and cause the motor winding thermostat to open and the oil can turn dark gray. c. Check the compressor oil levels. The oil level in each compressor sight glass should be visible in the compressor sightglass. This only applies to CSHD compressors, SSA and SPA compressors don't have sight glasses. Note: The Copeland, SSA and SPA scroll compressors for R-410A units use Trane OIL00094. The correct Oil for Trane CSHD is Trane OIL00079 or OIL00080. Compressor types are listed in the table below. The appropriate oil charge is also listed below 2. After the compressor and condenser fan have started and operated for approximately 30 minutes, observe the operating pressures. Compare the operating pressures to the operating pressure curve in the Service Facts. 5. To stop the SERVICE TEST, turn the main power disconnect switch to the “Off” position or proceed to the next component start-up procedure. Remove electro mechanical test mode connections (if applicable). 3. Check system superheat. Follow the instruction listed on the superheat charging curve in the Service Facts. Superheat should be within ±5ºF of the superheat chart value. Compressor Start-Up 5. To stop the SERVICE TEST, turn the main power disconnect switch to the “Off” position or proceed to the next component start-up procedure. 1. Attach a set of service gauges onto the suction and discharge gauge ports for each circuit. Refer to the refrigerant circuit illustration in the Service Facts. Using the Service Test Guide in Table 7, p. 31, continue the SERVICE TEST start-up procedure for each compressor circuit. Momentarily jump across the Test 1 & Test 2 terminals on LTB1 one additional time if continuing from previous component start-up or until the desired startup component Test is started. 4. Repeat steps 1 through 4 for each refrigerant circuit. 6. The Copeland, SSA and SPA scroll compressors for R410A units use Trane OIL00094. The correct Oil for Trane CSHD is Trane OIL00079 or OIL00080. Compressor types are listed in the following table. The appropriate oil charge is also listed below. Figure 26. Compressor terminal box Scroll Compressors a. Once each compressor has started, verify that the rotation is correct. To check rotation, use a set of refrigeration gauges hooked up to the suction and discharge pressure port. If the compressor is phased correctly the suction pressure should drop and the discharge pressure should rise when the compressor starts and runs. If a scroll compressor is rotating backwards, it will not pump, the suction and discharge pressure will not rise, and a loud rattling sound can be observed. RT-SVX33E-EN 33 Start Up Table 8. Oil charge Model Circuit 1 Circuit 2 WS*150 56 oz 56 oz WS*155/WS*180 56 oz 56 oz WS*200/WS*240 112 oz 112 oz Table 9. • Verify that all exterior panels including the control panel doors and condenser grilles are secured in place. • Close the main disconnect switch or circuit protector switch that provides the supply power to the unit’s terminal block or the unit mounted disconnect switch. Compressor types Tonnage C1 C2 WS*150 SSA067 SSA067 WS*155/WS*180 SSA083 SSA083 WS*200/WS*240 CSHD125 CSHD125 Heating Start-Up 1. Clamp an amp meter around one of 1st stage heater power wires at the heater contactor. 2. Using the Service Test Guide in Table 7, p. 31, continue the SERVICE TEST start-up procedure for each compressor circuit. Momentarily jump across the Test 1 & Test 2 terminals on LTB one additional time if continuing from previous component start-up or until the desired start-up component Test is started. 3. Verify that the heater stage is operating properly. 4. Clamp an amp meter around one of 2nd stage heater power wires at the heater contactor (if applicable). 5. Using the Service Test Guide in Table 7, p. 31, continue the SERVICE TEST start-up procedure for each compressor circuit. Momentarily jump across the Test 1 & Test 2 terminals on LTB one additional time if continuing from previous component start-up or until the desired start-up component Test is started. 6. Verify that the heater stage is operating properly. 7. To stop the SERVICE TEST, turn the main power disconnect switch to the “Off” position or proceed to the next component start-up procedure. Final System Setup After completing all of the pre-start and start-up procedures outlined in the previous sections (i.e., operating the unit in each of its Modes through all available stages of cooling & heating), perform these final checks before leaving the unit: • Program the Night Setback (NSB) panel (if applicable) for proper unoccupied operation. Refer to the programming instructions for the specific panel. • Verify that the Remote panel “System” selection switch, “Fan” selection switch, and “Zone Temperature” settings for automatic operation are correct. • Inspect the unit for misplaced tools, hardware, and debris. 34 RT-SVX33E-EN Maintenance Make sure all personnel are standing clear of the unit before proceeding. The system components will start when the power is applied. Fan Belt Adjustment - Belt Drive Units Note: Actual belt deflection “force” must not exceed the maximum “force” value shown in Table 10, p. 35. Table 10. Belt tension measurement and deflection ranges Deflection Force (Lbs.) WARNING Rotating Components! Belts Small Cross P.D Section Range The following procedure involves working with rotating components. Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in rotating components cutting and slashing technician which could result in death or serious injury. The fan belts must be inspected periodically to assure proper unit operation. Replacement is necessary if the belts appear frayed or worn. Units with dual belts require a matched set of belts to ensure equal belt length. A B 7. Super Gripbelts Gripnotch Min. Max. Steel Cable Gripbelts Min. Max. Min. Max 3.0 - 3.6 3 4 1/2 3 7/8 5 1/2 3 1/4 4 3.8 - 4.8 3 1/2 5 4 1/2 6 1/4 3 3/4 4 3/4 5.0 - 7.0 4 5 1/2 5 6 7/8 4 1/4 5 1/4 3.4 - 4.2 4 5 1/2 5 3/4 8 4 1/2 5 1/2 4.4 - 5.6 5 1/8 7 1/8 6 1/2 9 1/8 5 3/4 7 1/4 5.8 - 8.8 6 3/8 8 3/4 7 3/8 10 1/8 7 8 3/4 Recheck the belt tension at least twice during the first 2 to 3 days of operation. Belt tension may decrease until the new belts are “run in”. Figure 27. Belt tension gauge When removing or installing the new belts, do not stretch them over the sheaves. Loosen the belts using the belt tension adjustment bolts on the motor mounting base. Once the new belts are installed, using a Browning or Gates tension gauge (or equivalent) illustrated in Figure 27, p. 35; adjust the belt tension as follows; 1. To determine the appropriate belt deflection; a. Measure the center-to-center shaft distance (in inches) between the fan and motor sheaves. b. Divide the distance measured in Step 1a by 64; the resulting value represents the amount of belt deflection that corresponds to the proper belt tension. 2. Set the large O-ring on the belt tension gauge at the deflection value determined in Step 1b. 3. Set the small O-ring at zero on the force scale of the gauge plunger. 4. Place the large end of the gauge at the center of the belt span; then depress the gauge plunger until the large Oring is even with the top of the next belt or even with a straightedge placed across the fan and motor sheaves. Refer to Figure 27, p. 35. 5. Remove the belt tension gauge. The small O-ring now indicates a number other than zero on the plunger’s force scale. This number represents the force (in pounds) required to give the needed deflection. 6. Compare the “force” scale reading (Step 5) with the appropriate “force” value listed in Table 10, p. 35. If the “force” reading is outside the range, readjust the belt tension. RT-SVX33E-EN Monthly Maintenance WARNING Hazardous Voltage! Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury. Before completing the following checks, turn the unit OFF and lock the main power disconnect switch open. Failure to disconnect power before servicing can cause severe personal injury or death. 35 Maintenance Filters • Inspect the return air filters. Clean or replace them if necessary. Refer to the unit Service Facts for filter information. Make sure that all retaining screws are reinstalled in the unit access panels once these checks are complete. • With the unit running, check and record the: ambient temperature; compressor suction and discharge pressures (each circuit); superheat (each circuit); Condensate Overflow Switch During maintenance, the switch float (black ring) must be checked to ensure free movement up and down. Return Air Smoke Detector Maintenance Airflow through the unit is affected by the amount of dirt and debris accumulated on the indoor coil and filters. To insure that airflow through the unit is adequate for proper sampling by the return air smoke detector, complete adherence to the maintenance procedures, including recommended intervals between filter changes, and coil cleaning is required. Periodic checks and maintenance procedures must be performed on the smoke detector to insure that it will function properly. For detailed instructions concerning these checks and procedures, refer to the appropriate section(s) of the smoke detector Installation and Maintenance Instructions provided with the literature package for this unit. Cooling Season Record this data on an “operator’s maintenance log” like the one shown in Table 11, p. 37. If the operating pressures indicate a refrigerant shortage, measure the system superheat. For guidelines, refer to the “Compressor StartUp” section. Note: Do not release refrigerant to the atmosphere! If adding or removing refrigerant is required, the service technician must comply with all federal, state and local laws. Heating Season • Inspect the unit’s air filters. If necessary, clean or replace them. • Check supply fan motor bearings; repair or replace the motor as necessary. • Inspect both the main unit control panel and heat section control box for loose electrical components and terminal connections, as well as damaged wire insulation. Make any necessary repairs. • Verify that the electric heat system operates properly. • Check the unit’s drain pans and condensate piping to ensure that there are no blockages. Coil Cleaning • Inspect the evaporator and condenser coils for dirt, bent fins, etc. If the coils appear dirty, clean them according to the instructions described in “Coil Cleaning” later in this section. • Manually rotate the condenser fan(s) to ensure free movement and check motor bearings for wear. Verify that all of the fan mounting hardware is tight. Regular coil maintenance, including annual cleaning, enhances the unit’s operating efficiency by minimizing: compressor head pressure and amperage draw; evaporator water carryover; fan brake horsepower, due to increase static pressure losses; airflow reduction. • Inspect the F/A-R/A damper hinges and pins to ensure that all moving parts are securely mounted. Keep the blades clean as necessary. • Verify that all damper linkages move freely; lubricate with white grease, if necessary. • Check supply fan motor bearings; repair or replace the motor as necessary. • Check the fan shaft bearings for wear. Replace the bearings as necessary. • Check the supply fan belt. If the belt is frayed or worn, replace it. Refer to the “Fan Belt Adjustment” section for belt replacement and adjustments. • Verify that all wire terminal connections are tight. • Remove any corrosion present on the exterior surfaces of the unit and repaint these areas. • 36 Generally inspect the unit for unusual conditions (e.g., loose access panels, leaking piping connections, etc.) At least once each year, or more often if the unit is located in a “dirty” environment, clean the evaporator and condenser coils using the instructions outlined below. Be sure to follow these instructions as closely as possible to avoid damaging the coils. To clean refrigerant coils, use a soft brush and a sprayer (either a garden pump-up type or a high-pressure sprayer). A high-quality detergent is also required; suggested brands include “SPREX A.C.”, “OAKITE 161”, “OAKITE 166” and “COILOX”. If the detergent selected is strongly alkaline (ph value exceeds 8.5), add an inhibitor. 1. Remove enough panels from the unit to gain access to the coil. Remove the access panel from the roof located next to the rear condenser fan. 2. Protect all electrical devices such as motors and controllers from any over spray. 3. Straighten any bent coil fins with a fin comb. 4. Mix the detergent with water according to the manufacturer’s instructions. If desired, heat the solution to 150° F maximum to improve its cleansing capability. RT-SVX33E-EN Maintenance 8. Inspect both sides of the coil; if it still appears to be dirty, repeat Steps 6 and 7. WARNING Hazardous Pressures! If a heat source is required to raise the tank pressure during removal of refrigerant from cylinders, use only warm water or heat blankets to raise the tank temperature. Do not exceed a temperature of 150°F. Do not, under any circumstances apply direct flame to any portion of the cylinder. Failure to follow these safety precautions could result in a sudden rise of pressure possibly resulting in a violent explosion which could result in death or serious injury. 9. Reinstall all of the components and panels removed in Step 1 and any protective covers installed in step 2. 10. Restore the unit to it’s operational status and check system operation. Final Process For future reference, you may find it helpful to record the unit data requested below in the blanks provided. (1) Complete Unit Model Number: Do not heat the detergent-and-water solution above 150°F. Hot liquids sprayed on the exterior of the coil will raise the coil’s internal pressure and may cause it to burst. Failure to follow proper procedures can result in personal illness or injury or severe equipment damage. _____________________________________________________ __________________ 5. Pour the cleaning solution into the sprayer. If a highpressure sprayer is used: (3) Wiring Diagram Numbers (from unit control panel): a. do not allow sprayer pressure to exceed 600 psi. _____________________________________________________ __________________ — schematic(s) b. the minimum nozzle spray angle is 15 degrees. _____________________________________________________ __________________ c. maintain a minimum clearance of 6" between the sprayer nozzle and the coil. _____________________________________________________ __________________ d. spray the solution perpendicular (at 90 degrees) to the coil face. — connection(s) 6. Spray the leaving-airflow side of the coil first; then spray the opposite side of the coil. Allow the cleaning solution to stand on the coil for five minutes. 7. (2) Unit Serial Number: Rinse both sides of the coil with cool, clean water. Table 11. _____________________________________________________ __________________ _____________________________________________________ __________________ Sample maintenance log Refrigerant Circuit #1 Date Suction Current Compr. Oil Pressure Ambient Level Psig/kPa temp F/C RT-SVX33E-EN Dischcharge Pressure Psig/kpa Refrigerant Circuit #2 Super heat Sub cool F/C F/C Suction Compr. Oil Pressure Level Psig/kPa Dischcharge Pressure Psig/kpa Super heat Sub cool F/C F/C 37 Troubleshooting start the unit. This procedure will allow you to check all of the RTRM outputs, and all of the external controls (relays, contactors, etc.) that the RTRM outputs energize, for each respective mode. Proceed to Step 6. WARNING Hazardous Service Procedures! The maintenance and troubleshooting procedures recommended in this section of the manual could result in exposure to electrical, mechanical or other potential safety hazards. Always refer to the safety warnings provided throughout this manual concerning these procedures. Unless specified otherwise, disconnect all electrical power including remote disconnect and discharge all energy storing devices such as capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. When necessary to work with live electrical components, have a qualified licensed electrician or other individual who has been trained in handling live electrical components perform these tasks. Failure to follow all of the recommended safety warnings provided, could result in death or serious injury. 6. Step the system through all of the available modes, and verify operation of all outputs, controls, and modes. If a problem in operation is noted in any mode, you may leave the system in that mode for up to one hour while troubleshooting. Refer to the sequence of operations for each mode, to assist in verifying proper operation. Make the necessary repairs and proceed to Steps 7 and 8. 7. If no abnormal operating conditions appear in the test mode, exit the test mode by turning the power “Off” at the main power disconnect switch. 8. Refer to the individual component test procedures if other microelectronic components are suspect. ReliaTel Controls System Status Checkout Procedure The RTRM has the ability to provide the service personnel with some unit diagnostics and system status information. “System Status” is checked by using one of the following two methods: Before turning the main power disconnect switch “Off”, follow the steps below to check the ReliaTel Refrigeration Module (RTRM). All diagnostics & system status information stored in the RTRM will be lost when the main power is turned “Off”. To prevent injury or death from electrocution, it is the responsibility of the technician to recognize this hazard and use extreme care when performing service procedures with the electrical power energized. 1. Verify that the Liteport LED on the RTRM is burning continuously. If the LED is lit, go to Step 3. 2. If the LED is not lit, verify that 24 VAC is presence between J1-1 and J1-2. If 24 Vac is present, proceed to Step 3. If 24 Vac is not present, check the unit main power supply, check transformer (TNS1). Proceed to Step 3 if necessary. 3. Utilizing “Method 1” or “Method 2” in the “System Status Checkout Procedure ” section, check the following: If the Zone Sensor Module (ZSM) is equipped with a remote panel with LED status indication, you can check the unit within the space. If the ZSM does not have LED’s, use Method 2. BAYSENS110*, and BAYSENS119* all have the remote panel indication feature. The LED descriptions are listed below. LED 1 (System) “On” during normal operation. “Off” if a system failure occurs or the LED fails. “Flashing” indicates test mode. LED 2 (Heat) “On” when the heat cycle is operating. “Off” when the heat cycle terminates or the LED fails. “Flashing” indicates a heating failure. System status LED 3 (Cool) Heating status “On” when the cooling cycle is operating. Cooling status “Off” when the cooling cycle terminates or the LED fails. If a System failure is indicated, proceed to Step 4. If no failures are indicated, proceed to Step 5. 4. If a System failure is indicated, recheck Steps 1 and 2. If the LED is not lit in Step 1, and 24 VAC is present in Step 2, the RTRM has failed. Replace the RTRM. 5. If no failures are indicated, use one of the TEST mode procedures described in the “Unit Start-Up” section to 38 Method 1 “Flashing” indicates a cooling failure. LED 4 (Service) “On” indicates a clogged filter. “Off” during normal operation. “Flashing” indicates an evaporator fan failure or Condensate Overflow Switch (COF) failure. RT-SVX33E-EN Troubleshooting Below is the complete listing of failure indication causes. Cool Failure System Failure Cool Operating = approximately 32 Vdc Check the voltage between terminals 6 and 9 on J6, it should read approximately 32 Vdc. If no voltage is present, a System failure has occurred. Refer to Step 4 in the previous section for the recommended troubleshooting procedure. Cool Off = less than 1 Vdc, approximately 0.75 Vdc Cooling Failure Measure the voltage between terminals J6-10 & J6-6. 1. Cooling and heating set point (slide pot) on the zone sensor has failed. Refer to the “Zone Sensor Test Procedure” section. 2. Zone temperature thermistor ZTEMP on ZTS failed. Refer to the “Zone Sensor Test Procedure” section. 3. CC1 or CC2 24 Vac control circuit has opened, check CC1 & CC2 coils, and any of the controls below that apply to the unit (HPC1, HPC2). 4. LPC1 has opened during the 3 minute minimum “on time” during 4 consecutive compressor starts, check LPC1 or LPC2 by testing voltage between the J1-8 & J32 terminals on the RTRM and ground. If 24 VAC is present, the LPC’s has not tripped. If no voltage is present, LPC’s has tripped. Service Failure 1. If the supply fan proving switch has closed, the unit will not operate (when connected to RTOM), check the fan motor, belts, and proving switch. 2. Clogged filter switch has closed, check the filters. Simultaneous Heat and Cool Failure 1. Emergency Stop is activated. Method 2 The second method for determining system status is done by checking voltage readings at the RTRM (J6). The system indication descriptions and the approximate voltages are listed below. Measure the voltage between terminals J6-8 & J6-6. Cooling Failure = voltage alternates between 32 Vdc & 0.75 Vdc Service Failure Clogged Filter = Approximately 32 Vdc. Normal = Less than 1 Vdc, approximately 0.75 Vdc Fan Failure = voltage alternates between 32 Vdc & 0.75 Vdc. Note: If the Condensate Overflow Switch is closed, the unit will not operate. Check to make sure the float position is not in a tripped condition and verify an "open" between wires connecting to RTOM J6-1, J6-2. To use LED’s for quick status information at the unit, purchase a BAYSENS110* ZSM and connect wires with alligator clamps to terminals 6 through 10. Connect each respective terminal wire (6 through 10) from the Zone Sensor to the unit J6 terminals 6 through 10. Note: If the system is equipped with a programmable zone sensor, (BAYSENS119*), the LED indicators will not function while the BAYSENS110* is connected. Resetting Cooling and Heating Lockouts Cooling Failures and Heating Lockouts are reset in an identical manner. Method 1 explains resetting the system from the space; Method 2 explains resetting the system at the unit. System Failure Note: Before resetting Cooling Failures and Heating Lockouts check the Failure Status Diagnostics by the methods previously explained. Diagnostics will be lost when the power to the unit is disconnected. Measure the voltage between terminals J6-9 & J6-6. Method 1 Normal Operation = approximately 32 Vdc To reset the system from the space, turn the “Mode” selection switch at the zone sensor to the “Off” position. After approximately 30 seconds, turn the “Mode” selection switch to the desired mode, i.e. Heat, Cool or Auto. System Failure = less than 1 Vdc, approximately 0.75 Vdc Test Mode = voltage alternates between 32 Vdc & 0.75 Vdc Heat Failure Measure the voltage between terminals J6-7 & J6-6. Heat Operating = approximately 32 Vdc Heat Off = less than 1 VDC, approximately 0.75 Vdc Heating Failure = voltage alternates between 32 Vdc & 0.75 Vdc RT-SVX33E-EN Method 2 To reset the system at the unit, cycle the unit power by turning the disconnect switch “Off” and then “On”. Lockouts can be cleared through the building management system. Refer to the building management system instructions for more information. 39 Troubleshooting Zone Temperature Sensor (ZTS) Service Indicator The ZSM SERVICE LED is a generic indicator, that will signal the closing of a Normally Open switch at any time, providing the Indoor Motor (IDM) is operating. This indicator is usually used to indicate a clogged filter, or an air side fan failure. The RTRM will ignore the closing of this Normally Open switch for 2 (±1) minutes. This helps prevent nuisance SERVICE LED indications. The exception is the LED will flash 40 seconds after the fan is turned “On” if the Fan Proving Switch is not made. Clogged Filter Switch Zone Temperature Nominal ZTEMP Nominal CSP or Resistance HSP Resistance 50 F° 10.0 C° 19.9 K-Ohms 889 Ohms 55 F° 12.8 C° 17.47 K-Ohms 812 Ohms 60 F° 15.6 C° 15.3 K-Ohms 695 Ohms 65 F° 18.3 C° 13.49 K-Ohms 597 Ohms 70 F° 21.1 C° 11.9 K-Ohms 500 Ohms 75 F° 23.9 C° 10.50 K-Ohms 403 Ohms 80 F° 26.7 C° 9.3 K-Ohms 305 Ohms 85 F° 29.4 C° 8.25 K-Ohms 208 Ohms 90 F° 32.2 C° 7.3 K-Ohms 110 Ohms Test 2: Cooling Set Point (CSP) and Heating Set Point (HSP) This LED will remain lit the entire time that the Normally Open switch is closed. The LED will be turned off immediately after resetting the switch (to the Normally Open position), or any time that the IDM is turned “Off”. The resistance of these potentiometers are measured between the following ZSM terminals. Refer to the chart above for approximate resistances at the given setpoints. If the switch remains closed, and the IDM is turned “On”, the SERVICE LED will be turned “On” again after the 2 (±1) minute ignore delay. Range = 100 to 900 Ohms approximate This LED being turned “On”, will have no other affect on unit operation. It is an indicator only. Range = 100 to 900 Ohms approximate Fan Failure Switch The combined resistance of the Mode selection switch and the Fan selection switch can be measured between terminals 2 and 4 on the Zone Sensor. The possible switch combinations are listed on the following page with their corresponding resistance values. When the “Fan Failure” switch is wired to the RTOM, the LED will remain flashing the entire time the fan proving switch is closed, indicating a fan failure, and it will shut the unit operations down. Condensate Overflow Switch When the condensate overflow switch is closed, a drain pan overflow condition is indicated and it will shut unit operations down. Zone Temperature Sensor (ZTS) Tests Note: These procedures are not for programmable or digital models and are conducted with the Zone Sensor Module electrically removed from the system. Test 1: Zone Temperature Thermistor (ZTEMP) This component is tested by measuring the resistance between terminals 1 and 2 on the Zone Temperature Sensor. Below are some typical indoor temperatures, and corresponding resistive values. 40 Cool SP = Terminals 2 and 3 Heat SP = Terminals 2 and 5 Test 3: System Mode and Fan Selection Test 4: LED Indicator Test, (SYS ON, HEAT, COOL & SERVICE) Method 1 Testing the LED using a meter with diode test function. Test both forward and reverse bias. Forward bias should measure a voltage drop of 1.5 to 2.5 volts, depending on your meter. Reverse bias will show an over Load, or open circuit indication if LED is functional. Method 2 Testing the LED with an analog Ohmmeter. Connect Ohmmeter across LED in one direction, then reverse the leads for the opposite direction. The LED should have at least 100 times more resistance in reverse direction, as compared with the forward direction. If high resistance in both directions, LED is open. If low in both directions, LED is shorted. Method 3 To test LED’s with ZSM connected to unit, test voltages at LED terminals on ZSM. A measurement of 32 VDC, across an unlit LED, means the LED has failed. RT-SVX33E-EN Troubleshooting Note: Measurements should be made from LED common (ZSM terminal 6 to respective LED terminal). Refer to the Zone Sensor Module (ZSM) Terminal Identification table at the beginning of this section. Programmable & Digital Zone Sensor Test Testing Serial Communication Voltage During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. 1. Verify 24 Vac is present between terminals J6-14 & J611. 2. Disconnect wires from J6-11 and J6-12. Measure the voltage between J6-11 and J6-12; it should be about 32 Vdc. 3. Reconnect wires to terminals J6-11 and J6-12. Measure voltage again between J6-11 and J6-12, voltage should flash high and low every 0.5 seconds. The voltage on the low end will measure about 19 Vdc, while the voltage on the high end will measure from approximately 24 to 38 Vdc. 4. Verify all modes of operation, by running the unit through all of the steps in the “Test Modes” section discussed in “Unit Start-Up”. 5. After verifying proper unit operation, exit the test mode. Turn the fan on continuously at the ZSM, by pressing the button with the fan symbol. If the fan comes on and runs continuously, the ZSM is good. If you are not able to turn the fan on, the ZSM is defective. Table 12. System mode and fan selection chart Local Unit Mode Local Unit Mode Local Fan Mode 43.45K Emergency Heat/ On Emergency Heat On Out of Range (Short) INVALID/Short Invalid (CV), Auto (VAV) Invalid Out of Range (Open) INVALID/Open Invalid (CV), Off (VAV) Invalid If the RTCI loses input from the building management system, the RTRM will control in the default mode after approximately 15 minutes. If the RTRM loses the Heating and Cooling setpoint input, the RTRM will control in the default mode instantaneously. The temperature sensing thermistor in the Zone Sensor Module is the only component required for the “Default Mode” to operate. Unit Operation without a Zone Sensor This procedure is for temporary operation only. The economizer and condenser fan cycling functions are disabled. WARNING Hazardous Voltage! Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury. 1. Open and Lock the unit disconnect switch. 2. Remove the Outside Air Sensor (OAS) from the condenser section of unit. 3. Use two (2) wire nuts, to individually cap the wires. 4. Locate the RTRM (J6). Connect two (2) wires to terminals J6-1 and 2. 5. Connect the sensor (OAS) using two wire nuts to the two (2) field supplied wires that were connected to terminals 1 and 2 on J6. Local Fan Mode 2.32K Off/ Auto Off Auto 4.87K Cool/Auto Cool Auto Auto 7.68K Auto/Auto Auto 10.77K Off/On Off On 13.32K Cool/On Cool On 16.13K Auto/On Auto On 19.48K Heat/Auto Heat Auto 27.93K Heat/On Heat On 35.0K Emergency Heat/ Auto Emergency Heat Auto RT-SVX33E-EN Resistance Zone Sensor Valves (Ohms) Unit/Fan Mode ReliaTel Refrigeration Module (RTRM) Default Chart WARNING Live Electrical Components! Resistance Zone Sensor Valves (Ohms) Unit/Fan Mode Table 12. System mode and fan selection chart 41 Troubleshooting Unit Economizer Control (ECA) Troubleshooting Table 13. Verify economizer status by economizer actuator (ECA) LED indicator: OFF: No Power or Failure ON: Normal, OK to Economize Slow Flash: Normal, Not OK to Economize 1/2 Second On / 2 Seconds Off: Fast Flash: Error Code: Communications Failure Pulse Flash: 2 Second On / 1/2 Second Off: 1 Flash: Actuator Fault Error Code: 2 Flashes: CO2 Sensor 3 Flashes: RA Humidity Sensor 4 Flashes: RA Temp Sensor 5 Flashes: OA Quality Sensor 6 Flashes: OA Humidity Sensor 7 Flashes: OA Temp Sensor 8 Flashes: MA Temp Sensor 9 Flashes: RAM Fault 10 Flashes: ROM Fault 11 Flashes: EEPROM Fault 42 RT-SVX33E-EN Wiring Diagrams Note: Wiring diagrams can be accessed via e-Library by entering the diagram number in the literature order number search field or by contacting technical support. Table 14. Wiring diagrams Type of Airflow Constant Volume Variable Air Volume/ Multi-speed Fans/ Single Zone Variable Air Volume Schematic Type Voltage Diagram Number Power 200-575 2313-1479 WS*150-240, 50/60HZ, Heat Pump with or without Electric Heat Control 200-575 2313-1488 Description WS*150-240, 50/60HZ, Heat Pump with or without Electric Heat, with or without Dehumidification 2313-1495 WS*150-240, 50/60HZ, with or without Dehumidification, Option Modules Raceway Connections 200-575 2313-1515 WS*150-240, 50/60HZ, Heat Pump, with or without Dehumidification Control Box Connections 200-230 2313-1499 WS*150-240, 50/60HZ, Heat Pump, with or without Dehumidification 380-575 2313-1500 WS*150-240, 50/60HZ, Heat Pump, with or without Dehumidification Power 208-575 2313-1483 WS*150-240, 60HZ, Heat Pump with or without Electric Heat Control 208-575 2313-1492 WS*150-240, 60HZ, Heat Pump with or without Electric Heat, with or without Dehumidification 2313-1495 WS*150-240, 60HZ, with or without Dehumidification, Option Modules Raceway Connections Control Box Connections 208-575 2313-1519 WS*150-240, 60HZ, Heat Pump, with or without Dehumidification 208-230 2313-1507 WS*150-240, 60HZ, Heat Pump, with or without Dehumidification 460-575 2313-1508 WS*150-240, 60HZ, Heat Pump, with or without Dehumidification Note: * = Downflow and horizontal airflow Table 15. Wiring diagrams for units with High Short Circuit Rating (SCCR) Type of airflow Schematic Type Power Control Constant Volume Diagram Number Description 208-575 2313-1578 WS*180-300, 60HZ, Heat Pump with or without Electric Heat 208-575 2313-1583 WS*180-300, 60HZ, Heat Pump with or without Electric Heat 208-575 2313-1590 WS*180-300, 60HZ, Heat Pump with or without Electric Heat, Options Modules Raceway Connection 208-575 2313-2020 WS*180-300, 60HZ, Heat Pump with or without Electric Heat Control Box Connections 208-575 2313-2003 WS*180-300, 60HZ, Heat Pump with or without Electric Heat Module Connections 208-575 2313-2049 WS*180-300, 60HZ, Heat Pump with or without Electric Heat Power 208-575 2313-1578 WS*180-300, 60HZ, Heat Pump with or without Electric Heat 208-575 2313-1587 WS*180-300, 60HZ, Heat Pump with or without Electric Heat 208-575 2313-1590 WS*180-300, 60HZ, Heat Pump with or without Electric Heat, Options Modules Raceway Connection 208-575 2313-2024 WS*180-300, 60HZ, Heat Pump with or without Electric Heat Control Box Connections 208-575 2313-2007 WS*180-300, 60HZ, Heat Pump with or without Electric Heat Module Connections 208-575 2313-2053 WS*180-300, 60HZ, Heat Pump with or without Electric Heat Control Multi-speed Fans/ Single Zone Variable Air Volume Voltage Note: * = Downflow and horizontal airflow RT-SVX33E-EN 43 Warranty Heat Pump WSD, WSH (Parts Only) Models Less Than or Equal to 20 Tons for Commercial Use* This warranty is extended by Trane, to the original purchaser and to any succeeding owner of the real property to which the Heat Pump is originally affixed, and applies to products purchased and retained for use within the U.S.A. and Canada. There is no warranty against corrosion, erosion or deterioration. Some states do not allow limitations on how long an implied warranty lasts or do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This warranty gives you specific legal rights, and you may also have other rights which vary from state to state. Trane 2701 Wilma Rudolph Blvd. Clarksville, TN 37040-1008 Attention: Manager, Product Service GW-604-4800 If any part of your Heat Pump fails because of a manufacturing defect within one year from initial start-up or 18 months from date of shipment - whichever is lesserWarrantor will furnish without charge the required replacement part. * This warranty is for commercial usage of said equipment and not applicable when the equipment is used for a residential application. Commercial use is any application where the end purchaser uses the product for other than personal, family or household purposes. In addition, if the sealed motor-compressor fails because of a manufacturing defect within the second through fifth year from the date of original purchase, Warrantor will furnish without charge the required replacement compressor. Warrantor’s obligations and liabilities under this warranty are limited to furnishing F.O.B. Warrantor factory or warehouse replacement parts for Warrantor’s products covered under this warranty. Warrantor shall not be obligated to pay for the cost of lost refrigerant. No liability shall attach to Warrantor until products have been paid for and then liability shall be limited solely to the purchase price of the equipment under warranty shown to be defective. *A 5 year limited warranty is provided for the optional Low Leak Economizer, when combined with the optional FDD (Fault Detection & Diagnostics) option. THE WARRANTY AND LIABILITY SET FORTH HEREIN ARE IN LIEU OF ALL OTHER WARRANTIES AND LIABILITIES, WHETHER IN CONTRACT OR IN NEGLIGENCE, EXPRESS OR IMPLIED, IN LAW OR IN FACT, INCLUDING IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR PARTICULAR USE, AND IN NO EVENT SHALL WARRANTOR BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES. The manufacturer optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in creating and sustaining safe, comfortable and energy efficient environments, the manufacturer offers a broad portfolio of advanced controls and HVAC systems, comprehensive building services, and parts. For more information, visit www.IRCO.com. The manufacturer has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice. © 2014 Trane All rights reserved RT-SVX33E-EN 27 May 2014 Supersedes RT-SVX33D-EN (17 Jan 2014) We are committed to using environmentally conscious print practices that reduce waste.
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.5 Linearized : Yes Author : TCS - Unitary Create Date : 2014:05:27 21:59:24Z Keywords : Voyager, heat pump, IOM, WSD, WSH, installation, operation, maintenance, RT-SVX33E-EN Modify Date : 2014:05:27 22:53:34Z Subject : Packaged Rooftop Unit Voyager - Heat Pump 12.5 - 20 Ton XMP Toolkit : Adobe XMP Core 5.2-c001 63.139439, 2010/09/27-13:37:26 Format : application/pdf Description : Packaged Rooftop Unit Voyager - Heat Pump 12.5 - 20 Ton Title : Installation, Operation, and Maintenance Creator : TCS - Unitary Producer : Acrobat Distiller 10.1.10 (Windows) Creator Tool : FrameMaker 10.0.2 Document ID : uuid:471fd1a7-cb3f-4ab8-b70a-c5107b42a8dc Instance ID : uuid:0b88e5d3-be7d-4f7d-9d6f-b3d37b0ccbd6 Page Mode : UseOutlines Page Count : 44EXIF Metadata provided by EXIF.tools