Tyco Safety Canada 113G3070 ALARM COMMUNICATOR User Manual USERS MANUAL

Digital Security Controls Ltd. ALARM COMMUNICATOR USERS MANUAL

USERS MANUAL

Download: Tyco Safety Canada 113G3070 ALARM COMMUNICATOR User Manual USERS MANUAL
Mirror Download [FCC.gov]Tyco Safety Canada 113G3070 ALARM COMMUNICATOR User Manual USERS MANUAL
Document ID1596300
Application IDfVAzal6U6e1NlPY1NIkJyQ==
Document DescriptionUSERS MANUAL
Short Term ConfidentialNo
Permanent ConfidentialNo
SupercedeNo
Document TypeUser Manual
Display FormatAdobe Acrobat PDF - pdf
Filesize71.18kB (889726 bits)
Date Submitted2011-12-06 00:00:00
Date Available2011-12-06 00:00:00
Creation Date2011-08-12 17:08:16
Producing SoftwareAcrobat Distiller 9.4.2 (Windows)
Document Lastmod2011-08-12 17:08:16
Document Title29008181R001_NOVA_3G3070_V3.5_IM_NA_ULC_UL_DRAFT_03.book
Document CreatorPScript5.dll Version 5.2.2
Document Author: mmarkovic

3G3070
3G-GPRS INTERFACE
INSTALLATION MANUAL
V3.5
WARNING: This manual contains information on limitations regarding product
use and function and information on the limitations as to liability of the manufacturer. The entire manual should be carefully read.
TABLE OF CONTENTS - NEW 3G3070
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Identification of Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Installing the 3G3070 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Connecting the 3G3070 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Status LEDS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Operating Principles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Simulated Landline Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Panel Transmission Monitoring (PTM) . . . . . . . . . . . . . . . . . . . . . . . . .6
GPRS Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Activating the Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Swinger Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Hardware Default . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Low Power Radio Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
CONNECT 24 Remote Programming . . . . . . . . . . . . . . . . . . . . . . . . .8
Troubleshooting Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
3G3070 Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
IMPORTANT
The equipment is fixed, wall-mounted and shall be installed in the position specified in
these instructions. The equipment enclosure must be fully assembled and closed, with
all the necessary screws/tabs and secured to a wall before operation. Internal wiring
must be routed in a manner that prevents:
- Excessive strain on wire and on terminal connections
- Loosening of terminal; connections
- Damage of conductor insulation
WARNING: Never install this equipment during a lightning storm!
Instruct the end-user to:
- Not attempt to service this product. Opening or removing covers may expose the user
to dangerous voltages or other risks. Any servicing shall be referred to trained service
personnel only.
- Use authorized accessories only with this equipment.
Do not dispose of the battery in fire or water. Disposing of the battery in a fire will cause
rupture and explosion.
Do not dispose of the waste battery as unsorted municipal waste. Consult your local
regulations and /or laws regarding recycling with regard to this lithium battery pack. Doing
so will help protect the environment. Some of the materials that are found within the battery could become toxic if not disposed of properly and may affect the environment.
ii
Introduction
The 3G3070 is a wireless communicator that sends alarm system information to an SG-System III, SGSystem II, or SG-System I receiver through a GSM/GPRS wireless network. This wireless communicator can
be used with UL/ULC Listed compatible control units, as indicated in the manufacturer's installation
instructions.
NOTE: The 3G3070 is designed to work with the Contact ID communication format as described in SIA DC05 Standard. Before completing the field installation of the alarm monitoring system please ensure communication with the supervising central station is successful by sending several events and getting confirmation that they have been received.
Features
• Compatible with 4-digit or 10-digit Contact ID communication format as described in SIA DC-05
Standard. Example of suitable compatible alarm panels: DSC Models PC1864, PC1832, PC1616,
PC4020.
• Simulates landline
• Switches automatically to the GSM network in the event of landline trouble (e.g., line down)
• GSM Signal Indicator
• Four programmable outputs
• Contains one 12V - 1.2 Ah battery
• Case Tamper Output
• Landline overvoltage protection
• Dual-band GSM radio
• Four programmable inputs
• GPRS/Internet communication with Sur-Gard System III / II
• Panel transmission monitoring for up to four phone numbers
Technical Specifications
The input voltage to the 3G3070 can be drawn from the UL/ULC Listed control panel or provided by an
external UL/ULC Listed power supply rated for the application (external power-limited source).
NOTE: The power supply must be Class II, Power Limited. For residential applications a suitable power adaptor is model DSC ADP1310-NAU (for USA) and model DSC ADP1310-NA (for Canada).
Ratings
Power Supply Ratings - Input Voltage (for long-term operation)
JP3-OFF with internal battery: . . . . . . . . . . . . . . . . . . . . . . . . . . . 13.8VDC required
JP3-ON without internal battery: . . . . . . . . . . . . . . . . . . . . . . . 13.8VDC recommended
NOTE: When the input voltage drops below 13.5VDC, the internal battery supplied with the 3G3070
will not be charged. In order to maintain a charged level for the internal battery, the power supply
must have a minimum voltage of 13.5VDC to ensure a sufficient battery charge in all conditions of use.
Current Consumption
JP3-OFF with internal battery: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120mA*
JP3-ON without internal battery: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 500mA*
* Plus any current drawn from the 3G3070 AUX+ terminal
Working Voltage Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-14VDC
Battery: . . . . . . . . sealed, rechargeable type, rated 12V/1.2Ah or 12VAh (for 24hr standby time)
Battery charging voltage: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13.5VDC
Battery charging current: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50mA
NOTE: Battery must be replaced every 3-5 years.
Operating frequency: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 850/1900MHz
Antenna gain: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.0dBi
Environmental Specifications
Operating temperature: . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0°C-49°C (32°F-120°F)
Humidity: . . . . . . . . . . . . . . . . . . . . . . . . . . . .93%RH Maximum (non-condensing)
Mechanical Specifications
Dimensions (metal enclosure, painted): . . . . . . . . 138mm x 224mm x 55mm / 5.4” x 8.8” x 2.2”
Weight (without battery): . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 900g / 3.2oz
Internal Event Buffer (communications): . . . . . . . . . . . . . . . . . . 256 Events (not viewable)
Simulated Telco Loop specifications (TIP/RING)
On-Hook Voltage: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35VDC
Loop Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25mA
Loop Resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 600 Ohms
Alternate construction
Dimensions (enclosure 3G3070RF): . . . . . . . . . . 165mm x 257mm x 76mm / 6.3” x 10.1” x 3”
Weight (alternate construction enclosure without battery): . . . . . . . . . . . . . . 1300g / 2.8lbs
Identification of Parts
Figure 1 - Parts
14
54
16
17
LOCK
JP3
OPEN
OFF ON
NOTE: For UL/ULC installations, connections between
the alarm control panel outputs (telephone interface
Tip/Ring, output relay contacts) and 3G3070 inputs
(Tip/Ring, Z1-Z4) shall be
run in a mechanical protective conduit within 20ft (6m)
of one another and in the
same room.
JP3
10
TIP RNG T1
LE
LI
R1
10
11 12 13
14
COM PGM1 PGM2 PGM3 PGM4 AUX+ TAMPER COM
O1 O2 O3 O4 +OC AS
15
Z1
16
Z2
17
Z3
18
Z4
19 20
+ DC IN -
L1 L2 L3 L4 +12V-
11
tie wrap
13
12
15
3G3070
All circuits are classified for UL installations as Power Limited/Class II Power Limited except for the battery leads which are not power limited. Do not route any wiring over circuit boards. Maintain at least 1”
(25.4mm) separation. A minimum 1/4” (6.4mm) of separation must be maintained at all points between
Power Limited wiring and all other non-Power Limited wiring. Route wires as indicated above.
Table 1: Parts
Parts
10
11
12
13
14
15
16
17
Metal Casing
GSM Antenna
GSM Antenna Mounting Hardware
Anchor Screw Holes (3mm)
GSM Antenna Connector
SIM Card
Status LEDs (see page 5)
JP3 Current Limitation Jumper (refer to Ratings Section)
PC-Link Connector
Tamper Switch
Terminal Blocks
Battery Leads
Cable Entry
Earth Ground Wire
12V - 1.2Ah Battery
GSM Radio Module
SIM Card Holder
This equipment 3G3070 is fixed and shall be installed by Service Persons only (Service Person is
defined as a person having the appropriate technical training and experience necessary to be
aware of hazards to which that person may be exposed in performing a task, and of measures
available to minimize the risks to that person or other persons). It shall be installed and used
within an environment that provides the pollution degree max 2, over voltages category II, in
non-hazardous, indoor locations only. This manual shall be used with the Installation Manual of
the relevant alarm control panel. All instructions specified within that manual must be observed.
Description
This 3G3070 manages transmissions to a central station and can simulate the landline in the event of
trouble (e.g., landline down) or even substitute the landline completely in areas where the GSM service
is provided and a landline is not available.
The 3G3070 has the capability of communicating alarm signals via the GPRS data network. This
capability ensures a fast, reliable path to central stations equipped with a Sur-Gard System III or System
II receiver. By connecting a 3G3070 to a control panel's standard PSTN interface, telephone-based
Contact ID signals are decoded and seamlessly routed through the GPRS network to any of the
compatible receiver options.
The performance of the 3G3070 depends greatly on GSM network coverage. Therefore, it should not
be mounted without first performing placement tests to determine the best location for reception
(minimum of one green LED ON). Optional antenna kits – GS15/25/50-ANT (15ft/4.6m, 25ft/7.6m or
50ft/15.2m) – are available.
The 3G3070 requires enrollment with CONNECT 24 to operate. Dealer application forms and
additional information on the CONNECT 24 Voice Response Unit (VRU) and web user interface can
be found at www.connect24.com, or at the following telephone numbers:
USA 1-888-251-7458 CANADA 1-888-955-5583
For UL Residential Fire and Burglary installations, the 3G3070 is listed as a sole means of communication
or as a back up when used in conjunction with a POTS line (dialer). For UL Residential Fire installations,
when installed in the alternate enclosure model 3G3070RF, the 3G3070 has provisions for 24-hour
standby power.
For UL Commercial Burglary installations, the 3G3070 is listed as a sole means of communication
(supervision window of 200s required at monitoring station) or as a back-up when used in conjunction
with a POTS line (dialer).
The 3G3070 shall be powered from any compatible listed control unit or compatible listed power supply that
complies with the ratings specified on page 1. The power supply shall be listed for burglary applications and
provide a minimum of 4 hours standby power capabilities. An example of a suitable listed compatible control
unit is the DSC Model PC1864 with an AUX output rated 11.1 - 12.6VDC. An example of a suitable Listed
power supply is DSC Model PC5204 with an AUX output rated 11.6 - 12.6VDC.
For ULC Commercial Fire Monitoring installations the 3G3070 is listed as a passive communication
system when used in conjunction with a POTS line (dialer). Fire alarms shall be sent simultaneously over
both communication methods (GSM network and PSTN).
For ULC Commercial Burglary installations the 3G3070 is listed as a passive communication system with
communication line security level P2 when used as a back up in conjunction with a POTS line (dialer).
For ULC Residential Fire and Burglary installations the 3G3070 is listed as a sole means communication
or as a back up when used in conjunction with a POTS line (dialer).
ATTENTION: The 3G3070 is equipped with a current limiter that limits current demand on the
12VDC power input to 120mA. The current limiter is enabled by default (see Part #8 in 'Identification of Parts’ on page 3) with JP3 in the OFF position. The current limiter can be disabled
(bypassed) with JP3 in the ON position. When the 3G3070 12VDC power input is supplied by the
Alarm Panel Aux+ output, DSC recommends that the current limiter be active to limit the demand
from the panel. If the alarm panel is intended to supply all of the current demand, you must
ensure that the panel can supply 500mA and that the current limiter is disabled. When the 3G3070
is transmitting, the current demand exceeds 120mA (500mA). With the current limiter in place,
the additional current demand is supplied by the 3G3070 battery.
NOTE: With the current limiter active, there is a risk of discharging the 3G3070 battery when
transmission frequency is high. The back up battery must always be connected to the device when
the current limiter is enabled.
If power to the 3G3070 is supplied by an external power supply (recommended 13.8 VDC, 0.7A), the
current limiter must be disabled to allow the full current demand to be supplied. In this configuration
the 3G3070 battery is not required.
Installing the 3G3070
CONNECT 24 Enrolment Information
Only authorized dealers can enrol a 3G3070 with CONNECT 24. Dealer application forms and additional
information on the CONNECT 24 Voice Response Unit can be found at the CONNECT 24 website
www.connect24.com. Please contact CONNECT 24 at the number below for assistance:
USA 1-888-251-7458 CANADA 1-888-955-5583
NOTE: Steps 1 and 2 should be completed before turning on the 3G3070 unit.
NOTE: Before inserting or removing the SIM card, please ensure the unit is turned off.
STEP 1 - Activate Your SIM Card
Your SIM card must be activated with Connect 24 prior to use. Please call the Voice Response Unit
(VRU) at least 24 hrs prior to installation at 1-866-910-3865.
STEP 2 - Initialize the 3G3070 with Connect 24
Call the VRU at the toll-free number. Follow the voice prompts and enter your profile number, installer
ID number, installer PIN number and central station number. Ensure that all information is available and
at hand before calling the VRU. This information can be found in your VRU Enrollment Package.
STEP 3 - Determine the Best Signal Location
1. Unscrew the four screws securing the front panel to the cabinet. Remove the front panel.
2. Fit the GSM antenna [2]. Ensure the GSM antenna mounting hardware is fastened securely [3].
3. Attach the GSM radio module with the GSM antenna connector. Ensure that the connector is secure.
4. Turn on the 3G3070 and check the signal strength.
5. Connect the battery to the RED and BLK battery leads.
6. Connect the DC power source to +/- 12V terminals.
7. Allow the unit to power up.
NOTE: The green LEDs will indicate the signal strength. The bottom green LED must be on for the
location to be acceptable. Please refer to the ‘Status LEDs’ section for more information.
8. Power down the 3G3070 by removing the DC power source and battery leads.
STEP 4 - Connect the 3G3070
1. Using the cabinet, mark the four screw locations. Drill the anchor screw holes.
NOTE: Check for cable conduits and water pipes before drilling.
2. Using anchor screws (not provided), mount the cabinet to the wall.
3. Run the cables through the cable entry [13] or through the cabinet knockouts.
4. Complete the connections on the terminal blocks [11].
NOTE: Ensure that power and Telco circuit connections are made only after the cabinet has been
secured to the building or structure, and has been connected to the protective earth ground.
Descriptions of the terminals can be found in the ‘Connecting the 3G3070’ section.
5. Reattach the front cover [1] securely to the cabinet.
NOTE: Please refer to Figure 2 at the end of this manual for wiring diagram.
Connecting the 3G3070
(1) Earth Ground - This terminal must be connected to the Mains Earth, in order to comply with the
Telecommunications Network Safety Standards (Overvoltage Protection Requirements).
TIP (2) / RNG (3) External Telephone Line - These terminals must be connected directly to the
incoming telephone line.
T1 (4) / R1 (5) Internal Telephone Line - These terminals must be connected to the TIP and RING of
the control panel.
COM (6,14) Common - This terminal is connected internally to Power Ground.
PGM1 (7), PGM2 (8), PGM3 (9), PGM4 (10) Programmable Open-collector Outputs - These
outputs can be activated by programmed events. Refer to ‘Activating the Outputs’ for details. The
maximum current sink of each output must not exceed 50mA.
AUX+ (11) Auxiliary 12V Output - +12V Output, 200mA PTC Protected.
NOTE: Electrical current drawn from this terminal is drawn directly from the power supply. This
must be added to the 3G3070 current when determining the total draw on the host panel or
power supply. Jumper JP3 does not limit the electrical current available on this output.
Tamper (12-13) - These terminals are connected in series to the Tamper switch [10]. They will close
when the cabinet is properly closed, and will open when the front cover is removed.
Z1-Z4 (15-16-17-18) Programmable Inputs - These terminals can be set up to trigger events. Refer
to ‘Inputs’ for details.
12V (19), COM (20) Device Power Supply - hese terminals must be connected to a rated power
supply. Once the connections are completed, connect the battery leads (Red and Black wires, [12] in
Figure 1) to a 12V, 7Ah battery.
Jumper JP3
JP3 ON - Full power, including standby capacity, comes from the host panel or external power
supply. Supply must be capable of up to 700mA. The 3G3070 battery must not be connected.
JP3 OFF - Current limiting mode, the host panel or external supply provides standby current. Supply
must be capable of 120mA plus any current drawn from AUX+ terminal. 3G3070 battery must be
installed for proper operation.
NOTE: The power supply must have a minimum voltage of 13.5V to ensure a sufficient battery
charge. An example of a suitable power supply is the DSC Model ADP1310-NA with DC output
rated 13.8 VDC, 1Amp. This is to be used in conjunction with a 12V/7Ah rated battery for UL/ULC
listed residential installations.
NOTE: This mode of operation must not be used for ULC Listed Fire Monitoring installations.
NOTE: When disposing of batteries, follow the instructions and precautions printed on the batteries, and contact your municipal offices for information on the disposal of used batteries.
Status LEDs
The 3G3070 interface has four status LEDs. The following describes the control panel status LEDs.
NOTE: The top two LEDs blink during the Initializing and Programming phases.
RED - This LED is normally Off; but, it will flash in the event of a trouble. This LED will switch on
within three minutes in the event of GSM Module [16] trouble, or when the GSM Network is
unavailable, ‘No Service’. If this LED flashes, the following list indicates the specific trouble based on
the number of flashes, by priority. When turned on, the 3G3070 checks for the trouble conditions to
be restored in the order listed below. The 3G3070 indicates the status of the highest priority,
unrestored trouble condition with the corresponding number of flashes of the red LED. Once the
highest priority trouble condition has been cleared, the next highest priority trouble condition is
displayed.
1 flash - Battery Trouble (Battery with low voltage output)
2 flashes - Radio/SIM Trouble (Battery absent or SIM Card disconnected)
3 flashes - GSM Network Problem (SIM not active, poor signal strength, antenna not connected)
4 flashes - Insufficient Signal Strength (poor location)
5 flashes - Connect 24 Configuration SMS Trouble (Improper VRU programming. Once the configuration is ready, turn off power for 2-3 seconds to allow the unit to restart and request again)
6 flashes - Receiver not available (Improper VRU programming, receiver absent)
7 flashes - Power Supply Trouble (DC power supply absent)
Off - No Troubles
YELLOW - When this LED is On (solid), a Phone Line Trouble condition exists. This LED switches
on when the interface switches to the GSM Network (due to a Landline trouble condition). This
LED flashes slowly in the event of an incoming or outgoing voice call (regardless of the operating
status of the landline). This LED can also flash quickly once (GPRS TX) or twice (GPRS RX).
GREEN (Top) - When this LED is On, the reception is optimal. This LED switches On only when
the other Green LED is on.
GREEN (Bottom) - If this LED is Off and the Red LED is On, the GSM Network service is
unavailable (NO SERVICE). This LED flashes when the GSM Network reception is poor. If this LED
is on, the 3G3070 is able to communicate with the GSM network.
Operating Principles
Simulated Landline Mode
The simulated landline provides the alarm control panel (with dialer interface) with a back up line in the
event of PSTN line trouble. If the voltage on the landline terminals (TIP/RNG) drops below 2.8V for a
period of between 10 seconds and 45 seconds - depending on the device connected to the T1/R1
terminals- the 3G3070 switches the connected telephone device to the GSM network. After waiting
between 30 and 40 seconds, it checks the landline for one of the following:
• If the landline has been restored, the 3G3070 switches the connected device back to the landline,
OR
• If the landline is still down, the 3G3070 continues the simulation until the landline is restored. The
3G3070 will not switch during ongoing calls.
NOTE: When the landline is down, the 3G3070 provides a dial tone to any device connected to
T1 and R1, including any telephones on the premises. The phones on the premises will not, however, be able to dial out over the 3G3070.
Panel Transmission Monitoring (PTM)
The 3G3070 can also monitor the panel’s attempt to communicate with the central station. If it
determines that the panel is having difficulty, it switches the line to the GSM network. This feature is
only active when the 3G3070 is configured as a back up communicator. This feature is in addition to the
regular line voltage detection.
The 3G3070 monitors the phone line for four consecutive failed attempts within a 12-minute window. A
failed attempt is assumed to have occurred when a line seizure takes place during dialing (either the alarm
panel or the customer telephone), but no 1400Hz tone (or Contact Kiss-off) is sent from the receiver.
Once the conditions for a failed attempt are met, the 3G3070 connects the panel to the GSM network
to communicate the events. When the 3G3070 switches the line it stays in this mode until the panel
hangs up. On the next event the 3G3070 restarts the error detection sequence before switching.
The 3G3070 performs this sequence on any phone number that is detected on the line. Specific central
station phone numbers can be programmed into the 3G3070 if desired. Up to four, 20-digit numbers
can be added to your installer profile at Connect 24. If programmed, the 3G3070 will only look for
Contact ID Kiss-off after these numbers are dialed. A Telephone Line Monitoring trouble (PGM output
activation and/or reporting code if applicable) is also activated and/or transmitted when the PTM is
activated. A restoral is sent at the end of the call.
GPRS Sequence
• When an alarm is triggered, the control panel goes off-hook.
• The 3G3070 asserts a dial tone.
• The Control panel dials the number of the central station. Ensure that the alarm panel inserts a
minimum one second pause, or has Dial Tone Search enabled before dialing the number.
• The 3G3070 detects the DTMF dialing and stops dial tone.
NOTE: The 3G3070 is unable to decode pulse dialing.
• The 3G3070 sends the required Contact ID dual-tone handshake to the panel.
• After receiving the handshake, the control panel transmits an alarm message in Contact ID format.
• The 3G3070 decodes and transforms the Contact ID digits into an IP packet and sends it to the
central station receiver over the GPRS network.
• The central station receiver acknowledges the alarm and sends a command to the 3G3070 to generate the corresponding 1400Hz Kiss-off signal for a minimum of 800msec.
After the 3G3070 generates a Kiss-off signal, it sends the next alarm or, if no further alarms need to be
sent, the control panel goes on-hook.
Inputs
The 3G3070 has four inputs that can be used to trigger specific communications. These events will
transmit using Contact ID format with Inputs 1-4 reporting as [991] to [994] respectively.
Default settings are:
INPUT 1- FIRE
INPUT 3 - BURGLARY
INPUT 2 - PANIC ALARM
INPUT 4 - SYSTEM TROUBLE
These inputs are normally open and will activate when a short condition is detected between the
terminal and the COM. Refer to the 3G3070 Wiring Diagram (Figure 2) at the back of this manual.
NOTE: These inputs communicate using Contact ID format.
NOTE: For UL/ULC installations, connections between alarm panel outputs and 3G3070 inputs must
be run in protective mechanical conduits. To reduce interference with the antenna, it is recommended that the metal conduit is not connected to the knock-outs in the top of the cabinet.
Outputs
The 3G3070 has four programmable outputs to activate in response to the associated events. Refer
to the 3G3070 Wiring Diagram (Figure 2) at the back of this manual.
Activating the Outputs
The 3G3070 has four open collector outputs capable of a maximum of 50mA. Internal events on the
3G3070 can trigger the outputs to turn on an LED or activate an input on the host panel. The default
settings are as follows.
OUTPUT 1 Landline Trouble - Output is normally high and will switch to ground when the
telephone line is down.
OUTPUT 2 GSM Module or Network Trouble - Output is normally high and will switch to ground
when the 3G3070 can not communicate with the GSM network.
OUTPUT 3 Power Supply or Battery Trouble - Output is normally high and will switch to ground
when there is a problem with the power source.
OUTPUT 4 General Module Trouble - Output is normally low and will switch to high when a GSM
Trouble, Power Supply/Battery Trouble, and/or a Failure to Communicate (FTC) trouble is detected.
NOTE: PGM4 must be connected to the control panel as shown in Figure 4. Program the control
panel input Zone/Point as 24hr ‘Supervisory’ with keypad-only notification when activated.
Output 4 on the 3G3070 must be set as ‘Active High’.
NOTE: Once an output has been activated automatically, it will not restore its state until all the
causes of activation are cleared.
Contact ID
Events Description
Event Codes
INPUT 1 ACTIVATION: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E110 FIRE ZONE 001 991
INPUT 1 RESTORAL: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .R110 FIRE ZONE 001 991
INPUT 2 ACTIVATION: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E120 PANIC ALARM ZONE 002 992
INPUT 2 RESTORAL: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R120 PANIC ALARM ZONE 002 992
INPUT 3 ACTIVATION: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E130 BURGLARY ZONE 003 993
INPUT 3 RESTORAL: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R130 BURGLARY ZONE 003 993
INPUT 4 ACTIVATION: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .E300 SYSTEM TROUBLE ZONE 004 994
INPUT 4 RESTORAL: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R300 SYSTEM TROUBLE ZONE 004 994
PSTN LINE DOWN:. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E351 TELCO 1 FAULT 000
PSTN LINE RESTORAL: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R351 TELCO 1 FAULT 000
12V INPUT LOSS: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .E337 EXP. MOD. DC LOSS 000
12V INPUT RESTORAL: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R337 EXP. MOD. DC LOSS 000
LOW BATTERY ALERT: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E338 EXP. MOD. LOW BAT 000
LOW BATTERY RESTORAL: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R338 EXP. MOD. LOW BAT 000
PERIODIC REPORT: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E603 PERIODIC RF XMISSION 000
PERIODIC REPORT WITH OFF-NORMAL CONDITION: . . .E608 PERIODIC TEST XMISSION SYSTEM TROUBLE PRESENT 000
GSM UNIT ACTIVATION: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R552 RADIO XMITTER DISABLED 000
GSM INTERNAL BUFFER FULL: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E624 EVENT LOG OVERFLOW 000
FTC RESTORAL:. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R354 FAILURE TO COMMUNICATE 000
Swinger Shutdown
Swinger Shutdown is followed by a PSTN line trouble, limiting this event to a maximum of 3 trouble
reports every 24 hours (including the PSTN line trouble sent when PTM is active). The condition will
restore at midnight at which point the counter is reset.
Hardware Default
To perform a hardware default and force the unit to get the latest configuration from Connect 24,
follow these steps:
• Power down the unit.
• Place a short between the PGM1 and Input 1 terminals.
• Power up the unit. This will perform a hardware default and request the configuration from
Connect 24.
• Remove the short between PGM1 and Input 1.
NOTE: A Hardware default must be performed when the SIM card is being swapped.
Low Power Radio Shutdown
When the battery voltage reaches the low battery threshold of 10.5V, the unit turns off the radio to
prevent unnecessary network registrations. In this state, the unit does not communicate any events.
Radio shutdown is indicated by the LEDs as follows:
• for 1 second -- red is on, yellow is off, green 1 is off, and green 2 is off.
• for 1 second -- red is off, yellow is on, green 1 is on, and green 2 is on.
This LED sequence will continue to be displayed until the low battery voltage is restored and the radio
enabled again.
Connect 24 Remote Programming
The inputs, outputs, and other features can be remotely programmed through Connect 24 (C 24) for
fast and convenient installation using the internet.
NOTE: This programming option has not been investigated by UL.
Troubleshooting Guide
Powering up the 3G3070 – when powering up the 3G3070, always connect the battery first before
connecting primary DC power from the control panel or transformer.
Wiring Primary – R-1/T-1 of 3G3070 to RING/TIP of control panel, DC power from control panel or DC
transformer to DC input, backup battery if JP3 OFF.
Wiring Backup – Incoming line to RING/TIP on 3G3070, R-1/T-1 of 3G3070 to RING/TIP of control
panel, R-1/T-1 of control panel to house phones, DC power from control panel or DC transformer to DC
input, backup battery if JP3 OFF.
Testing Communications – when the 3G3070 transmits a signal for the control panel, or for an
internal transmission, the YELLOW light will flash one time when the signal is transmitted and two times
when it gets a kiss-off.
SIM – the SIM should be activated at least 24 hours prior to installation. The 3G3070 will not show
signal strength until the SIM is active.
Panel Programming – the control panel should be programmed to communicate Contact ID exactly
the same way it would be programmed to communicate Contact ID over the telephone line.
Green Light
Status
What it means:
Both Green Lights ON Excellent Signal
Strength
Signal Strength Status
• Unit can be installed in the current mounting
location
One Green Light ON
Good Signal Strength
• Unit can be installed in the current mounting
location
Bottom Green Light
FLASHING
Poor Signal Strength
• Ensure the antenna cable is plugged securely
into the radio connector
• If the SIM is active, connect a battery to the
unit and test various locations for good/excellent signal strength
• Connect an antenna extension kit (GS-15ANT,
GS-25ANT or GS-50ANT)
Both Green Lights
OFF
No Signal Strength
• If the red light is also FLASHING, refer to the
RED light chart
• Verify SIM card is activated
• Ensure the antenna cable is plugged securely
into the radio connector
• If the SIM is active, connect a battery to the
unit and test various locations for good/excellent signal strength
• Connect an antenna extension kit (GS-15ANT,
GS-25ANT or GS-50ANT)
Yellow Light
Status
What It Means: GSM Status/Communication Indicator
Yellow Light ON
• When used as the primary communicator, the yellow light will always be
ON.
• When used as a backup communicator, the yellow light will be ON when
there is a no phone line connected to the 3G3070 TIP and RING, or the line
voltage goes below 2.8VDC.
Yellow Light OFF
• Indicates a good phone line is connected to the 3G3070. (more than 2.8
VDC detected across the 3G3070 TIP and RING terminals).
Yellow Light
FLASHING
• The yellow light will flash one time when the 3G3070 transmits a signal
and two times when a kisoff is received.
Red Light
Status
What it means:
Trouble Status
Trouble Status - Troubleshooting Steps
One Flash
3G3070 Low Battery
• Measure the battery under load and verify it is
charged to at least 12.5 VDC. If not, wait at least 1
hour for the battery to charge
• Remove the battery and measure the voltage across
the two battery leads; the voltage should be at least
13.5 VDC
• Verify the input DC supply is rated at 13.8VDC @
120mA minimum
• Ensure the 3G3070 jumper J3 is OFF
Two Flashes
SIM/Radio Trouble
• Ensure the SIM Card is inserted correctly and firmly
• Ensure the antenna cable is plugged securely into the
radio connector
• Ensure the power source connected to the 3G3070 is
providing 13.8VDC @ 120mA and that the battery is
fully charged
Three
Flashes
GSM Network Problem
• Ensure the SIM card has been activated
• The antenna cable should be plugged securely into
the radio connector
• Ensure there is good signal strength (at least one
green light ON)
• Verify the installation area is not experiencing a network outage
Four Flashes
Insufficient Signal
Strength
• Ensure there is good signal strength (at least one
3G3070 green light ON)
• Ensure the antenna cable is plugged securely into the
radio connector
Five Flashes
Configuration Trouble
• Ensure the SIM card is activated
Six Flashes
Receiver Not Available
• Contact the monitoring station to verify that the
3G3070 programming is correct (port, IP address,
DNIS)
• Contact your central station to verify they are not
experiencing any receiver issues
Seven
Flashes
DC Supply Trouble
• Ensure the power source connected to the 3G3070 is
providing 13.8VDC @ 120mA
The Red light will flash to indicate various trouble conditions outlined previously. If multiple trouble
conditions are present, the red light will flash according to the highest priority trouble. For example, if
both a 3G3070 low battery trouble (one flash) and an insufficient signal strength trouble (four flashes)
are present; the red light will flash one time. Once the 3G3070 low battery trouble condition is
corrected, the red light will then begin flashing four times.
General Troubles With Your System
The control panel is displaying a telephone line trouble condition
• Ensure T1 and R1 of the 3G3070 are wired to the TIP
and RING terminals of the control panel
• If the 3G3070 is being used as the primary communicator, the yellow light will always be ON
• If the 3G3070 red light is FLASHING, refer to the Red
Light Status Chart
The control panel displays a communication trouble condition
• Ensure the panel is programmed for Contact ID
• Ensure the control panel does not indicate a TLM trouble condition
• If the 3G3070 red light is FLASHING refer to the Red
Light Status chart in this guide
No signals are received at the central
station but no trouble condition is
displayed
• Ensure the control panel has a central station phone
number programmed
• Ensure the control panel has the correct account number programmed
• Verify the reporting codes are programmed or the auto
Contact ID option is enabled
• Ensure the control panel communicator is enabled
• Connect a handset to T1 and R1 of the 3G3070 in monitor mode to verify the control panel is trying to communicate
Not receiving internal signals generated directly from the 3G3070
• Ensure the 3G3070 was initialized with the correct
account number. This can be checked by logging into
the Connect 24 website
• Ensure that there are no trouble conditions on the
3G3070
The 3G3070 Yellow and Red lights
flash constantly
• Ensure there is good signal strength (at least one
3G3070 green light ON)
• Ensure the SIM card is activated. Depending on signal
strength and network activity it can take up to 10 minutes for the network to program the unit; wait at least
15 minutes for the programming to be completed
• Cycle power and verify SIM and signal
The phone line is seized when the
3G3070 is connected
• Verify correct phone line wiring
• Ensure the Ringer Equivalency Number (REN) is not
being exceeded on the line
General Information
Removing/Connecting the antenna
• To remove the antenna from the 3G3070, place your
thumb on the end of the connector at the modem, then
place a screwdriver between the modem and connector.
Gently turn the screwdriver away to ‘pop’ out the connector from the modem
• To install the antenna, firmly push the the connector
into the modem until it ‘snaps’ into place
10
General Information
Enrolling a 3G3070
• The 3G3070 can be enrolled by going through the
GVRU voice prompt, and completing the activation of
the SIM card, and the initialization of the 3G3070
• The 3G3070 can also be enrolled using the Connect 24
website (www.connect24.com)
SIM card activation period
• A SIM card can take up to 24 hours to be activated by
the provider. However, it typically takes less than an
hour for the SIM card to be activated
Checking SIM status
• Go to www.connect24.com and login. A search can be
performed for a specific account and its current status
• SIM status can also be checked through the GVRU
New Features for V3.16
Critical Shutdown on 3G3070
backup battery
• If the 3G3070 backup battery is used and is below
10.5VDC, the unit will go into critical shutdown
• The critical shutdown state will be displayed by the red
light flashing followed by the yellow and two green
lights flashing
• The lights will continue to flash in this sequence until the
battery is charged above 12.4VDC
Swinger Shutdown for Telephone
Line Monitor (TLM) transmissions for
backup units
• If the 3G3070 is configured as a backup, it can send a
maximum of 3 TLM troubles and restorals per day
• TLM Swinger Shutdown only affects signal transmissions, not the functionality of the 3G3070 lights or PGM
outputs
11
GROUND
CONNECTION
RJ-45
Earth-ground
Ground wire
from building
electrical installation
2 LE 3
Optional
use of PGM
output (See
Programming)
12
For ULC Fire Monitoring installations fire alarm signals shall be sent
simultaneously over POTS line (using the dialler) and over the GSM
network (using 3G3070). Connect alarm output from control panel (PGM)
to the input on the 3G3070 that is programmed as a Fire Alarm Input.
Examples of Control Units/Subscribers Units or Power Supplies compatible
models: DSC PC1864, PC1832, PC1616, PC5204, etc.
Typical battery charge: 30-50 mA
Recommended Model: 12V/1.2Ah or
12V/7Ah (for order code 3G3070-RF only)
Inputs to be connected
to dry contact outputs
Panel Aux Power
or External Power
from alarm control panel
9-14VDC/ *700mA (max) Supply (13.8VDC
*Refer to Jumper 3 section required for normal,
long-term operation)
for current rating
Sealed Rechargeable
12V / 1.2Ah
BATTERY
Battery not required
if JP3 is ON
Tamper
Output
WARNING: Incorrect connections may result in PTC failure or improper operation. Inspect wiring and ensure connections are correct before turning on.
All circuits are classified for UL installations as Power Limited/Class II Power Limited except for the battery leads which are not Power Limited. Do not route any wiring
over circuit boards. Maintain at least 1” (25.4mm) separation. A minimum 1/4” (6.4mm) separation must be maintained at all points between Power Limited wiring
and all other Non-Power Limited wiring. Route wires as indicated in the diagram.
NOTE: For ULC Commercial Fire and Burglary Installation requirements please refer to Figures 5, 6, 7 & 8 and to the ULC Installation Guide P/N 29002157R009.
RM1-UL Installations
RM1C-ULC Installations
Connect relay contacts to
a zone input on the alarm
control panel for 3G3070
troubles supervision
(24hr-type zone)
Supervision
Relay
1K5
6 O1
7 O2
8 O3
9 O4+OC
10 11 12 AS13 14 15 L116L217L3 18
L4 1912V20
COM6 PGM1
PGM411
AUX+ TAMPER
Z1 15Z216Z317 Z4
DC 20
IN 7 PGM2
8 PGM3
9 10
18+19
12 13 COM 14
3G3070
WARNING!
HIGH VOLTAGE. DISCONNECT AC
POWER & TELEPHONE LINES
PRIOR TO SERVICING
Alarm Control Panel with
Dialler Interface
(Supports Contact ID format)
4LI 5
3 4T1 5R1
1 TIP
2 RNG
Telephone Line
Connection
(Use No. 26 AWG wires for
the connection to PSTN)
Tighten nut to break paint &
make good connection to
the cabinet.
Nut
Lock washer
Nut
Lock washer
Star washer
Cabinet
Bolt
DG009655
This Connection is necessary
3G3070 Wiring Diagrams
Figure 2 - Wiring Diagram
3G3070 Wiring Diagrams - statFmHere-8/9-09.00
Figure 3 - Telephone Connection
CONTROL PANEL
RJ-31X
RING
TIP
TI
TIP RNG T1
RI
RI
BROWN (T)
TI
RING
TIP
GRAY (R)
RED (R)
GREEN (T)
Incoming
Handset Phone line
3G3070
R1
Figure 4 - Power Supply and Supervision Wiring Diagram
CONTROL PANEL
ZONE
TERMINALS
(See Note 1)
Aux Power
2. The power Supervision relay, RM-2 is only used
when the 3G3070 is not powered by the control
panel. When the Radio is powered by the control
panel the relay is not required since a loss of input
power will generate a signal to the CMC.
+12VDC
GND
NOTES
1. Program the Zone/Point as “Supervisory” type
with keypad only annunciation when in Alarm. Do
NOT use a point that is normally used for
2-Wire Smoke detectors.
3. Output 4 on the 3G3070 must be set as “Active
High” (default).
4. When powering the 3G3070 Radio by an
Auxiliary Power supply that has its own backup
battery, insert JP3 jumper on the radio and remove
the 1.2AH battery that came with the radio.
9 10 11 12 13 14 15 16 17 18 19 20
PGM PGM PGM
PGM
AUX
TAMPER
+ 12 13
COM
DC IN
Z1 Z2 Z3 Z4 19 20
+ -
KSAD1380100W1US
Power Adaptor
COM
(BLK ) GND
Control
Panel
EOL
Resistor
See Note 3
(BLK/WHT) +13.8VDC
NC
DSC
RM-2
NO
RELAY
DSC
Supervision
Relay
See Note 2
3G3070
The following wiring diagrams (Figures 5 to 8) are examples of ULC Listed Fire Monitoring Installation
connections.
13
3G3070 Wiring Diagrams
Figure 5 - Fire Alarm Control Unit and GSM Transmitter
Wiring Diagram for Fire Alarm Control Unit (with dialler) and GSM Transmitter (Passive Communication System)
Fire Alarm
Control Unit
AUX Power
(12V/700mA)
GSM Transmitter
GSM Network GPRS (IP Data)
GS3055-I
3G3070
TIP/RING
T1/R1
TIP/RING
PSTN
Zone Input
Zone
Inputs
Outputs
Fire
Trouble
PGM4
Output
RM1C ULC
Relay
3G3070 cabinet
AC Input
NOTES:
- Power for 3G3070 shall be provided from Fire
Alarm Control Unit or separately Listed power supply
rated for the application, 12V/700mA (Jumper JP3
shall be set to on for Fire Monitoring).
- All wiring connections must be run in a protective
conduit.
- For local supervision of the GSM transmitter connect
PGM output from 3G3070 to one zone input on the
Fire Alarm Control Unit.
- Dry Contact Trouble output from ULC Listed Fire
Alarm Control Unit must be connected to zone input
on the 3G3070 for supervision of Tip/Ring connection.
- Fire Alarms must be sent over both communication
channels. Fire output from Fire Alarm Control Unit
must be connected to the Input 1 on the 3G3070.
- 24h Test Transmission must be enabled on the dialler
and on the 3G3070.
Figure 6 - DSC Subscribers’ Unit Fire and GSM Transmitter Mounted in the Same Room
Wiring Diagram for DSC Subscribers’ Unit Fire and GSM Transmitter
(Passive Communication System)
Fire Alarm
Control Unit
DSC
Subscribers’
Unit Fire
Outputs
Fire
Supervisory
Trouble
Zone
Inputs
TIP
PC4020
PC1864
PC1832
PC1616
TIP
RING
AUX Power
12V/700mA
GSM Network GPRS (IP Data)
GSM
Transmitter
GS3055-I
3G3070
T1/R1
TIP/RING
Zone
Input
PGM4
PGM1
RM1C ULC
Relay
RM1C ULC
Relay
PC5003C
PC4050CR
cabinet
AC Input
3G3070 cabinet
AC Input
DSC Keypad
LCD4501
PK55XX
14
PSTN
NOTES:
- Power for 3G3070 must be provided from Fire
Alarm Control Unit or separately listed power
supply rated for the application (12V/700mA)
(Jumper JP3 shall be on for Fire Monitoring).
- All wiring connections must be run in a protective conduit.
- Phone Line Monitoring (TLM) must be enabled.
- Phone Line trouble is indicated by Yellow LED on 3G3070.
- Connect PGM4 output from 3G3070 (Trouble
Conditions) to a zone input on the Subscriber Unit
for supervision of the GSM Transmitter.
- 24hr Test Transmission over phone line (PSTN) and
3G3070 must be enabled.
- Fire Alarms must be sent over both communication
channels.
- On the Subscribers’ Unit, program PGM1 for
PC1616/PC1832/PC1864 as System Event (Section
[009] as type 10; Section [501] Fire Event option 2
ON). An alternate option is to program PGM1 as Zone
Follower (Sec [009] = 29) and assign Fire Zone to PGM1
in Section [551]. Ensure Bit 3 is on in [501]. In this case,
a restored fire alarm condition does not require the DSC
control panel to be reset.
For PC4020 program PGM1 as type 49 Steady Fire ([00070049]).
- Dry contact outputs from ULC Listed Fire Alarm
Control Unit must be connected to zone inputs on
the ULC Listed DSC Subscribers’ Unit Fire.
- Refer to detailed diagrams in Figure 7.
3G3070 Wiring Diagrams
Figure 7 - DSC Subscribers’ Unit Fire and GSM Transmitter Mounted Remotely
Alternate Wiring Diagram for DSC Subscribers’ Unit Fire and GSM Transmitter
Passive Communication System -Using Phone Line Supervision Relay
Fire Alarm
Control Unit
DSC
Subscribers’
Unit Fire
Outputs
Fire
Supervisory
Trouble
Zone
Inputs
AUX Power
12V/700mA
PSTN
T1/R1
Zone
Input
TIP/RING
PGM1
PGM4
PGM1
RM1C ULC
Relay
RM1C ULC
Relay
RM1C ULC
Relay
PC5003C
PC4050CR
cabinet
AC Input
GSM Network
GPRS
(IP Data)
GS3055-I
3G3070
TIP
RING
PC4020
PC1864
PC1832
PC1616
GSM
Transmitter
AC Input
DSC Keypad
LCD4501
PK55XX
GS30XX cabinet
NOTES:
- Connect PGM output from 3G3070 (Phone Line Trouble)
to a zone input on the subscriber unit for supervision of the
phone line voltage.
- When the 3G3070 is installed remotely from the DSC
Control Panel, it is required to monitor the Phone Line
Trouble condition at the keypad by using an additional
RM1C Relay.
- Refer to detailed diagrams in Figure 8.
PLEASE NOTE THAT EITHER RM1C ULC OR RM2 RELAYS
CAN BE USED FOR ULC INSTALLATIONS
15
3G3070 Wiring Diagrams
Figure 8 -Connection Details for GSM Supervision Relay and Redundant Fire Alarm Transmission
Connection Details for GSM Supervision Relay & Redundant Fire Alarm Transmission
3G3070
1 2 LE 3 4LI 5
6 O1
7 O2
8 O3
9 O4+OC
10 11 12 AS
13 14 15 L116L217L3 18
L4 1912V20
Z1 15Z216Z317 Z4
DC 20
IN COM
PGM411
AUX+ TAMPER
7 PGM2
8 PGM3
9 10
18+19
3 4T1 5R1
6 PGM1
12 13 COM 14
1 TIP
2 RNG
GSM
Supervision
Relay
5.6 KOhm
Redundan
Fire Alarm
Initiation
PC1864
PC1832
Only
PC1864
Only
AUX+
BELL+
PGM1
PGM3
AUXBELL- RED BLK YEL GRN
PGM2
PGM4 Z1 COM Z2
Z3 COM Z4
Z5 COM Z6
Z7 COM Z8 EGND
RING
TIP
R-1
T-1
DG009656
AC AC
NOTE: Use EOL resistor in series with N.O. contacts of the relay connected to PGM4
Connection Details for GSM Supervision Relay & Redundant Fire Alarm Transmission
3G3070
1 2 LE 3 4LI 5
7 O2
8 O3
9 O4+OC
10 11 12 AS
13 14 15 L116L217L3 18
L4 1912V20
O1
COM
PGM411
AUX+ TAMPER
Z1 15Z216Z317 Z4
DC 20
IN 7 PGM2
8 PGM3
9 10
18+19
3 4T1 5R1
6 PGM1
12 13 COM 14
2 RNG
1 TIP
Redundant
Fire Alarm
Initiation
GSM
Supervision
Relay
5.6 KOhm
PC1864
PC1832
Only
PC1864
Only
AUX+
BELL+
PGM1
PGM3
AUXBELL- RED BLK YEL GRN
PGM2
PGM4 Z1 COM Z2
Z3 COM Z4
Z5 COM Z6
Z7 COM Z8 EGND
RING
TIP
R-1
T-1
DG009657
AC AC
NOTE: Use EOL resistor in parallel with N.C. contacts of the relay connected to PGM4
16
3G3070 Wiring Diagrams
Figure 9 - Connection Details for GSM Supervision Relay, Phone Line Supervision and Redundant Fire
Alarm Transmission
Connection Details for GSM Supervision Relay, Phone Line Supervision Relay
and Redundant Fire Alarm Transmission
3G3070
2 LE 3 4LI 5
3 4T1 5R1
2 RNG
1 TIP
6 O1
7 O2
8 O3
9 O4+OC
10 11 12 AS13 14 15 L116L217L3 18
L4 1912V20
COM6 PGM1
PGM411
AUX+ TAMPER
Z1 15Z216Z317 Z4
DC 20
IN 7 PGM2
8 PGM3
9 10
18+19
12 13 COM 14
Redundant
Fire Alarm
Initiation
5.6 KOhm
GSM
Supervision
Relay
5.6 KOhm
Phone Line
Supervision
Relay
PC1864
PC1832
Only
PC1864
Only
AUX+
BELL+
PGM1
PGM3
AUXBELL- RED BLK YEL GRN
PGM2
PGM4 Z1 COM Z2
Z3 COM Z4
Z5 COM Z6
Z7 COM Z8 EGND
RING
TIP
R-1
T-1
DG009658
AC AC
NOTE: Use EOL resistor in series with N.O. contacts of the relay connected to PGM4
Connection Details for GSM Supervision Relay, Phone Line Supervision Relay
and Redundant Fire Alarm Transmission
3G3070
1 2 LE 3 4LI 5
6 O1
7 O2
8 O3
9 O4+OC
10 11 12 AS
13 14 15 L116L217L3 18
L4 1912V20
COM
PGM411
AUX+ TAMPER
Z1 15Z216Z317 Z4
DC 20
IN 7 PGM2
8 PGM3
9 10
18+19
3 4T1 5R1
6 PGM1
12 13 COM 14
2 RNG
1 TIP
GSM
Supervision
Relay
Phone Line
Supervision
Relay
5.6
KOhm
5.6
KOhm
PC1864
PC1832
Only
PC1864
Only
AUX+
BELL+
PGM1
PGM3
AUXBELL- RED BLK YEL GRN
PGM2
PGM4 Z1 COM Z2
Z3 COM Z4
Z5 COM Z6
Z7 COM Z8 EGND
RING
TIP
R-1
T-1
DG009659
AC AC
Redundant
Fire Alarm
Initiation
NOTE: Use EOL resistor in parallel with N.C. contacts of the relay connected to PGM4
17
IMPORTANT READ CAREFULLY: DSC Software purchased with or without Products and Components is copyrighted and is purchased under the
following license terms:
• This End User License Agreement ("EULA") is a legal agreement
3. COPYRIGHT
between You (the company, individual or entity who acquired the Software and any related Hardware) and Digital Security Controls, a division of Tyco Safety Products Canada Ltd. ("DSC"), the manufacturer of
the integrated security systems and the developer of the software and
any related products or components ("HARDWARE") which You
acquired.
• If the DSC software product ("SOFTWARE PRODUCT" or "SOFTWARE")
is intended to be accompanied by HARDWARE, and is NOT accompanied by new HARDWARE, You may not use, copy or install the
SOFTWARE PRODUCT. The SOFTWARE PRODUCT includes computer software, and may include associated media, printed materials,
and "online" or electronic documentation.
• Any software provided along with the SOFTWARE PRODUCT that is
associated with a separate end user license agreement is licensed to
You under the terms of that license agreement.
• By installing, copying, downloading, storing, accessing or otherwise
using the SOFTWARE PRODUCT, You agree unconditionally to be
bound by the terms of this EULA, even if this EULA is deemed to be a
modification of any previous arrangement or contract. If You do not
agree to the terms of this EULA, DSC is unwilling to license the SOFTWARE PRODUCT to You, and You have no right to use it.
All title and intellectual property rights in and to the SOFTWARE PRODUCT (including but not limited to any images, photographs, and text
incorporated into the SOFTWARE PRODUCT), the accompanying
printed materials, and any copies of the SOFTWARE PRODUCT, are
owned by DSC or its suppliers. You may not copy the printed materials
accompanying the SOFTWARE PRODUCT. All title and intellectual property rights in and to the content which may be accessed through use of
the SOFTWARE PRODUCT are the property of the respective content
owner and may be protected by applicable copyright or other intellectual property laws and treaties. This EULA grants You no rights to use
such content. All rights not expressly granted under this EULA are
reserved by DSC and its suppliers.
SOFTWARE PRODUCT LICENSE
6. ARBITRATION
The SOFTWARE PRODUCT is protected by copyright laws and international copyright treaties, as well as other intellectual property laws and
treaties. The SOFTWARE PRODUCT is licensed, not sold.
All disputes arising in connection with this Agreement shall be determined by final and binding arbitration in accordance with the Arbitration
Act, and the parties agree to be bound by the arbitrator's decision. The
place of arbitration shall be Toronto, Canada, and the language of the
arbitration shall be English.
1. GRANT OF LICENSE. This EULA grants You the following rights:
(a) Software Installation and Use - For each license You acquire, You
may have only one copy of the SOFTWARE PRODUCT installed.
(b) Storage/Network Use - The SOFTWARE PRODUCT may not be
installed, accessed, displayed, run, shared or used concurrently on or
from different computers, including a workstation, terminal or other digital electronic device ("Device"). In other words, if You have several workstations, You will have to acquire a license for each workstation where
the SOFTWARE will be used.
(c) Backup Copy - You may make back up copies of the SOFTWARE
PRODUCT, but You may only have one copy per license installed at any
given time. You may use the back up copy solely for archival purposes.
Except as expressly provided in this EULA, You may not otherwise make
copies of the SOFTWARE PRODUCT, including the printed materials
accompanying the SOFTWARE.
2. DESCRIPTION OF OTHER RIGHTS AND LIMITATIONS
(a) Limitations on Reverse Engineering, Decompilation and Disassembly
- You may not reverse engineer, decompile, or disassemble the SOFTWARE PRODUCT, except and only to the extent that such activity is
expressly permitted by applicable law notwithstanding this limitation.
You may not make any changes or modifications to the Software, without
the written permission of an officer of DSC. You may not remove any
proprietary notices, marks or labels from the Software Product. You shall
institute reasonable measures to ensure compliance with the terms and
conditions of this EULA.
(b) Separation of Components - The SOFTWARE PRODUCT is licensed
as a single product. Its component parts may not be separated for use
on more than one HARDWARE unit.
(c) Single INTEGRATED PRODUCT - If You acquired this SOFTWARE
with HARDWARE, then the SOFTWARE PRODUCT is licensed with the
HARDWARE as a single integrated product. In this case, the SOFTWARE PRODUCT may only be used with the HARDWARE as set forth in
this EULA.
(d) Rental - You may not rent, lease or lend the SOFTWARE PRODUCT.
You may not make it available to others or post it on a server or web site.
(e) Software Product Transfer - You may transfer all of Your rights under
this EULA only as part of a permanent sale or transfer of the HARDWARE, provided You retain no copies, You transfer all of the SOFTWARE
PRODUCT (including all component parts, the media and printed materials, any upgrades and this EULA), and provided the recipient agrees
to the terms of this EULA. If the SOFTWARE PRODUCT is an upgrade,
any transfer must also include all prior versions of the SOFTWARE
PRODUCT.
(f) Termination - Without prejudice to any other rights, DSC may terminate this EULA if You fail to comply with the terms and conditions of this
EULA. In such event, You must destroy all copies of the SOFTWARE
PRODUCT and all of its component parts.
(g) Trademarks - This EULA does not grant You any rights in connection
with any trademarks or service marks of DSC or its suppliers.
4. EXPORT RESTRICTIONS
You agree that You will not export or re export the SOFTWARE PRODUCT to any country, person, or entity subject to Canadian export restrictions.
5. CHOICE OF LAW: This Software License Agreement is governed by
the laws of the Province of Ontario, Canada.
7. LIMITED WARRANTY
(a) NO WARRANTY
DSC PROVIDES THE SOFTWARE "AS IS" WITHOUT WARRANTY. DSC
DOES NOT WARRANT THAT THE SOFTWARE WILL MEET YOUR
REQUIREMENTS OR THAT OPERATION OF THE SOFTWARE WILL BE
UNINTERRUPTED OR ERROR-FREE.
(b) CHANGES IN OPERATING ENVIRONMENT
DSC shall not be responsible for problems caused by changes in the
operating characteristics of the HARDWARE, or for problems in the interaction of the SOFTWARE PRODUCT with non-DSC-SOFTWARE or
HARDWARE PRODUCTS.
(c) LIMITATION OF LIABILITY; WARRANTY REFLECTS ALLOCATION OF
RISK
IN ANY EVENT, IF ANY STATUTE IMPLIES WARRANTIES OR CONDITIONS NOT STATED IN THIS LICENSE AGREEMENT, DSC'S ENTIRE
LIABILITY UNDER ANY PROVISION OF THIS LICENSE AGREEMENT
SHALL BE LIMITED TO THE GREATER OF THE AMOUNT ACTUALLY
PAID BY YOU TO LICENSE THE SOFTWARE PRODUCT AND FIVE
CANADIAN DOLLARS (CAD$5.00). BECAUSE SOME JURISDICTIONS
DO NOT ALLOW THE EXCLUSION OR LIMITATION OF LIABILITY FOR
CONSEQUENTIAL OR INCIDENTAL DAMAGES, THE ABOVE LIMITATION MAY NOT APPLY TO YOU.
(d) DISCLAIMER OF WARRANTIES
THIS WARRANTY CONTAINS THE ENTIRE WARRANTY AND SHALL BE
IN LIEU OF ANY AND ALL OTHER WARRANTIES, WHETHER
EXPRESSED OR IMPLIED (INCLUDING ALL IMPLIED WARRANTIES OF
MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE) AND
OF ALL OTHER OBLIGATIONS OR LIABILITIES ON THE PART OF DSC.
DSC MAKES NO OTHER WARRANTIES. DSC NEITHER ASSUMES NOR
AUTHORIZES ANY OTHER PERSON PURPORTING TO ACT ON ITS
BEHALF TO MODIFY OR TO CHANGE THIS WARRANTY, NOR TO
ASSUME FOR IT ANY OTHER WARRANTY OR LIABILITY CONCERNING
THIS SOFTWARE PRODUCT.
(e) EXCLUSIVE REMEDY AND LIMITATION OF WARRANTY
UNDER NO CIRCUMSTANCES SHALL DSC BE LIABLE FOR ANY SPECIAL, INCIDENTAL, CONSEQUENTIAL OR INDIRECT DAMAGES
BASED UPON BREACH OF WARRANTY, BREACH OF CONTRACT,
NEGLIGENCE, STRICT LIABILITY, OR ANY OTHER LEGAL THEORY.
SUCH DAMAGES INCLUDE, BUT ARE NOT LIMITED TO, LOSS OF
PROFITS, LOSS OF THE SOFTWARE PRODUCT OR ANY ASSOCIATED
EQUIPMENT, COST OF CAPITAL, COST OF SUBSTITUTE OR REPLACEMENT EQUIPMENT, FACILITIES OR SERVICES, DOWN TIME, PURCHASERS TIME, THE CLAIMS OaF THIRD PARTIES, INCLUDING CUSTOMERS, AND INJURY TO PROPERTY.
WARNING: DSC recommends that the entire system be completely
tested on a regular basis. However, despite frequent testing, and due to,
but not limited to, criminal tampering or electrical disruption, it is possible for this SOFTWARE PRODUCT to fail to perform as expected.
18
FCC COMPLIANCE STATEMENT
CAUTION: Changes or modifications not expressly approved by
Digital Security Controls could void your authority to use this
equipment. This equipment generates and uses radio frequency energy
and if not installed and used properly, in strict accordance with the
manufacturer's instructions, may cause interference to radio and
television reception. It has been type tested and found to comply with
the limits for Class B device in accordance with the specifications in
Subpart "B" of Part 15 of FCC Rules, which are designed to provide
reasonable protection against such interference in any residential
installation. However, there is no guarantee that interference will not
occur in a particular installation. If this equipment does cause
interference to television or radio reception, which can be determined
by turning the equipment off and on, the user is encouraged to try to
correct the interference by one or more of the following measures:
• Re-orient the receiving antenna
• Relocate the alarm control with respect to the receiver
• Move the alarm control away from the receiver
• Connect the alarm control into a different outlet so that alarm control
and receiver are on different circuits.
If necessary, the user should consult the dealer or an experienced radio/
television technician for additional suggestions. The user may find the
following booklet prepared by the FCC helpful: "How to Identify and
Resolve Radio/Television Interference Problems". This booklet is
available from the U.S. Government Printing Office, Washington, D.C.
20402, Stock # 004-000-00345-4.
IMPORTANT INFORMATION
This equipment complies with Part 68 of the FCC Rules. On the side of
this equipment is a label that contains, among other information, the
FCC registration number and ringer equivalence number (REN) for this
equipment. If requested, this number must be provided to the
Telephone Company.
3G3070 Product IdentifierUS: F53MO00B3G3070
REN:0.0B
USOC Jack:RJ-31X
Telephone Connection Requirements
A plug and jack used to connect this equipment to the premises wiring
and telephone network must comply with the applicable FCC Part 68
rules and requirements adopted by the ACTA. A compliant telephone
cord and modular plug is provided with this product. It is designed to
be connected to a compatible modular jack that is also compliant. See
installation instructions for details.
Ringer Equivalence Number (REN)
The REN is used to determine the number of devices that may be
connected to a telephone line. Excessive RENs on a telephone line may
result in the devices not ringing in response to an incoming call.
In most but not all areas, the sum of RENs should not exceed five (5.0).
To be certain of the number of devices that may be connected to a line,
as determined by the total RENs, contact the local Telephone
Company. For products approved after July 23, 2001, the REN for this
product is part of the product identifier that has the format. US:
AAAEQ##TXXXX. The digits represented by ## are the REN without
a decimal point (e.g., 03 is a REN of 0.3). For earlier products, the REN
is separately shown on the label.
Incidence of Harm
If this equipment 3G3070 causes harm to the telephone network, the
telephone company will notify you in advance that temporary
discontinuance of service may be required. But if advance notice is not
practical, the Telephone Company will notify the customer as soon as
possible. Also, you will be advised of your right to file a complaint with
the FCC if you believe it is necessary.
Changes in Telephone Company Equipment or Facilities
The Telephone Company may make changes in its facilities,
equipment, operations or procedures that could affect the operation of
the equipment. If this happens the Telephone Company will provide
advance notice in order for you to make necessary modifications to
maintain uninterrupted service.
Equipment Maintenance Facility
If trouble is experienced with this equipment for repair or warranty
information, please contact the facility indicated below. If the
equipment is causing harm to the telephone network, the Telephone
Company may request that you disconnect the equipment until the problem
is solved. This equipment is of a type that is not intended to be repaired by
the end user.
DSC c/o APL Logistics, 757 Douglas Hill Rd., Lithia Springs, GA 30122
Additional Information
Connection to party line service is subject to state tariffs. Contact the state
public utility commission, public service commission or corporation
commission for information.
Alarm dialling equipment must be able to seize the telephone line and place
a call in an emergency situation. It must be able to do this even if other
equipment (telephone, answering system, computer modem, etc.) already
has the telephone line in use. To do so, alarm dialling equipment must be
connected to a properly installed RJ-31X jack that is electrically in series
with and ahead of all other equipment attached to the same telephone line.
Proper installation is depicted in the figure below. If you have any
questions concerning these instructions, you should consult your telephone
company or a qualified installer about installing the RJ-31X jack and alarm
dialling
equipment
for
you.
Customer Premises Equipment and Wiring
Network
Service
Provider's
Facilities
Computer
RJ-31X
Jack
Alarm Dialing
Equipment
Unused
RJ-11 Jack
Telephone
Line
Telephone
Network
Demarcation
Point
Fax Machine
Telephone
Answering
System
Unused
RJ-11 Jack
Telephone
Industry Canada Compliance Statement
This Equipment meets the applicable Industry Canada Terminal Equipment
Technical Specifications. This is confirmed by the registration number.
The abbreviation, IC, before the registration number signifies that
registration was performed based on a Declaration of Conformity
indicating that Industry Canada technical specifications were met. It does
not imply that that Industry Canada approved the equipment. The Ringer
Equivalence Number (REN) for this terminal equipment is 0.0. The REN
assigned to each terminal equipment provides an indication of the
maximum number of terminals allowed to be connected to a telephone
interface. The termination on an interface may consist of any combination
of devices subject only to the requirement that the sum of the Ringer
Equivalence Numbers of all devices does not exceed 5.
Cet équipement est conforme aux spécifications techniques applicables aux
équipements terminaux d'Industrie Canada. Ceci est confirmé par le
numéro d'enregistrement. L'abréviation IC précédant le numéro
d'enregistrement signifie que l'enregistrement a été effectué sur la base de
la Déclaration de conformité indiquant que le produit est conforme aux
spécifications techniques d'Industrie Canada. Ceci n'implique pas que le
produit ait été approuvé par Industrie Canada.
Le nombre équivalent de sonneries (REN) de cet appareil terminal est 0.0.
Le REN attribué à chaque équipement terminal fournit une indication sur
le nombre maximum de terminaux pouvant être connectés sur une interface
téléphonique. La terminaison sur une interface peut constituer en n'importe
quelle combinaison d'appareils, à la condition seulement que la somme des
Nombres équivalents de sonneries de tous les appareils ne soit pas
supérieure à 5.
This Class B digital apparatus meets all requirements of the Canadian
interference-causing equipment regulations. Cet appareil numérique de la
Classe B respecte toutes les exigences de règlement sur le matériel
brouilleur du Canada.
The term “IC:” before the radio certification number only signifies
that Industry Canada technical specifications were met.
WARNING: To satisfy FCC RF exposure requirements for mobile transmitting devices, a separation distance of 20cm
or more must be maintained between the antenna of this device and persons during device operation.
Limited Warranty
Digital Security Controls warrants the original purchaser
that for a period of twelve months from the date of
purchase, the product shall be free of defects in materials
and workmanship under normal use. During the warranty
period, Digital Security Controls shall, at its option, repair
or replace any defective product upon return of the product to its factory, at no charge for labour and materials.
Any replacement and/or repaired parts are warranted for
the remainder of the original warranty or ninety (90) days,
whichever is longer. The original purchaser must
promptly notify Digital Security Controls in writing that
there is defect in material or workmanship, such written
notice to be received in all events prior to expiration of
the warranty period. There is absolutely no warranty on
software and all software products are sold as a user
license under the terms of the software license agreement included with the product. The Customer assumes
all responsibility for the proper selection, installation,
operation and maintenance of any products purchased
from DSC. Custom products are only warranted to the
extent that they do not function upon delivery. In such
cases, DSC can replace or credit at its option.
International Warranty
The warranty for international customers is the same as
for any customer within Canada and the United States,
with the exception that Digital Security Controls shall not
be responsible for any customs fees, taxes, or VAT that
may be due.
Warranty Procedure
To obtain service under this warranty, please return the
item(s) in question to the point of purchase. All authorized distributors and dealers have a warranty program.
Anyone returning goods to Digital Security Controls must
first obtain an authorization number. Digital Security
Controls will not accept any shipment whatsoever for
which prior authorization has not been obtained.
Conditions to Void Warranty
This warranty applies only to defects in parts and workmanship relating to normal use. It does not cover:
• damage incurred in shipping or handling;
• damage caused by disaster such as fire, flood, wind,
earthquake or lightning;
• damage due to causes beyond the control of Digital
Security Controls such as excessive voltage, mechanical
shock or water damage;
• damage caused by unauthorized attachment, alterations, modifications or foreign objects;
• damage caused by peripherals (unless such peripherals
were supplied by Digital Security Controls);
• defects caused by failure to provide a suitable installation environment for the products;
• damage caused by use of the products for purposes
other than those for which it was designed;
• damage from improper maintenance;
• damage arising out of any other abuse, mishandling or
improper application of the products.
Items Not Covered by Warranty
In addition to the items which void the Warranty, the
following items shall not be covered by Warranty: (i)
freight cost to the repair centre; (ii) products which are
not identified with DSC's product label and lot number or
serial number; (iii) products disassembled or repaired in
such a manner as to adversely affect performance or
prevent adequate inspection or testing to verify any warranty claim. Access cards or tags returned for replacement under warranty will be credited or replaced at DSC's
option. Products not covered by this warranty, or otherwise out of warranty due to age, misuse, or damage shall
be evaluated, and a repair estimate shall be provided. No
repair work will be performed until a valid purchase order
is received from the Customer and a Return Merchandise
Authorisation number (RMA) is issued by DSC's Customer
Service.
Digital Security Controls’ liability for failure to repair the
product under this warranty after a reasonable number of
attempts will be limited to a replacement of the product,
as the exclusive remedy for breach of warranty. Under no
circumstances shall Digital Security Controls be liable for
any special, incidental, or consequential damages based
upon breach of warranty, breach of contract, negligence,
strict liability, or any other legal theory. Such damages
include, but are not limited to, loss of profits, loss of the
product or any associated equipment, cost of capital, cost
of substitute or replacement equipment, facilities or services, down time, purchaser’s time, the claims of third
parties, including customers, and injury to property. The
laws of some jurisdictions limit or do not allow the disclaimer of consequential damages. If the laws of such a
jurisdiction apply to any claim by or against DSC, the
limitations and disclaimers contained here shall be to the
greatest extent permitted by law. Some states do not
allow the exclusion or limitation of incidental or consequential damages, so that the above may not apply to
you.
Disclaimer of Warranties
This warranty contains the entire warranty and shall be in
lieu of any and all other warranties, whether expressed or
implied (including all implied warranties of merchantability or fitness for a particular purpose) and of all other
obligations or liabilities on the part of Digital Security
Controls Digital Security Controls neither assumes
responsibility for nor authorizes any other person purporting to act on its behalf to modify or to change this
warranty, nor to assume for it any other warranty or
liability concerning this product.
This disclaimer of warranties and limited warranty are
governed by the laws of the province of Ontario, Canada.
WARNING: Digital Security Controls recommends that
the entire system be completely tested on a regular
basis. However, despite frequent testing, and due to,
but not limited to, criminal tampering or electrical
disruption, it is possible for this product to fail to
perform as expected.
Out of Warranty Repairs
Digital Security Controls will at its option repair or replace
out-of-warranty products which are returned to its factory according to the following conditions. Anyone
returning goods to Digital Security Controls must first
obtain an authorization number. Digital Security Controls
will not accept any shipment whatsoever for which prior
authorization has not been obtained.
Products which Digital Security Controls determines to be
repairable will be repaired and returned. A set fee which
Digital Security Controls has predetermined and which
may be revised from time to time, will be charged for
each unit repaired.
© 2011 Tyco International Ltd. and its Respective Companies. All Rights Reserved.
The trademarks, logos, and service marks displayed on this document are registered in the United States [or other
countries]. Any misuse of the trademarks is strictly prohibited and Tyco International Ltd. will aggressively enforce its
intellectual property rights to the fullest extent of the law, including pursuit of criminal prosecution wherever necessary. All
trademarks not owned by Tyco International Ltd. are the property of their respective owners, and are used with permission
or allowed under applicable laws.
Product offerings and specifications are subject to change without notice. Actual products may vary from photos. Not all
products include all features. Availability varies by region; contact your sales representative.
Printed in Canada
2 9 0 0 8 1 8 1 R0 0 1

Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.5
Linearized                      : Yes
Author                          : mmarkovic
Create Date                     : 2011:08:12 17:08:16-04:00
Modify Date                     : 2011:08:12 17:08:16-04:00
XMP Toolkit                     : Adobe XMP Core 4.2.1-c043 52.372728, 2009/01/18-15:08:04
Creator Tool                    : PScript5.dll Version 5.2.2
Producer                        : Acrobat Distiller 9.4.2 (Windows)
Format                          : application/pdf
Title                           : 29008181R001_NOVA_3G3070_V3.5_IM_NA_ULC_UL_DRAFT_03.book
Creator                         : mmarkovic
Document ID                     : uuid:16e08633-6543-4ed8-a032-7b2d201430f5
Instance ID                     : uuid:c7f3c013-8543-404c-a4c9-4cadbe6b526c
Page Count                      : 23
EXIF Metadata provided by EXIF.tools
FCC ID Filing: F53113G3070

Navigation menu