Tyco Safety Software House PH Proximity Card Reader HID i CLASS Compatible User Manual rm1 ICP quick install

Tyco Safety Products / Software House Proximity Card Reader HID i CLASS Compatible rm1 ICP quick install

users manual

Download: Tyco Safety Software House PH Proximity Card Reader HID i CLASS Compatible User Manual rm1 ICP quick install
Mirror Download [FCC.gov]Tyco Safety Software House PH Proximity Card Reader HID i CLASS Compatible User Manual rm1 ICP quick install
Document ID678032
Application IDKBDZVtqP/77GfFkR8SW8PQ==
Document Descriptionusers manual
Short Term ConfidentialNo
Permanent ConfidentialNo
SupercedeNo
Document TypeUser Manual
Display FormatAdobe Acrobat PDF - pdf
Filesize128.9kB (1611290 bits)
Date Submitted2006-07-06 00:00:00
Date Available2006-07-06 00:00:00
Creation Date2004-09-13 07:37:39
Producing SoftwareAcrobat Distiller 7.0.5 (Windows)
Document Lastmod2006-04-19 13:05:15
Document Titlerm1-ICP_quick_install.fm
Document CreatorFrameMaker 7.0
Document Author: t_wood

RM-iC Series
Quick Start
Installation Guide
Version E0
Part Number UM-068
April 2006
PRODUCT The RM-iC series readers provide an enclosed RM-4 board and attached iCLASS read
OVERVIEW head, available in the following styles:
„
RM1-iC - enclosed RM-4 and attached iCLASS read head
„
RM2-iC - enclosed RM-4 with keypad and attached iCLASS read head
„
RM2L-iC - enclosed RM-4 with keypad, LCD display, and attached iCLASS read
head.
The RM-iC Quick Start Installation Guide provides a synopsis of installation and
connection information for RM-iC series readers. Refer to the Readers, Inputs, and
Outputs (RIO) Guide for in-depth technical and installation information.
Specifications
The following specifications apply to all RM-iC series readers:
„
Power: 12VDC, 300 mA
„
Cable: Belden 9841
„
Cable distance from iSTAR or apC: 4,000 ft.
„
Temperature
„
NOTE
Standards
‹
Indoor: 32° F to 120° F (0° C to 49° C)
‹
Outdoor: -31° F to 151 ° F (-35 ° C to 66° C)
Qualified on 26-bit, 35-bit, 37-bit, and 32-bit MIFARE serial number formats.
UL has only evaluated the 26-bit HID card format for this unit.
RM-iC series readers are Underwriters Laboratories Inc. (UL), Listed to Standard UL
294, Access Control System Units, Fifth Edition. RM-iC series readers must be wired in
accordance with the National Electrical Code (ANSI/NFPA 70), local codes, and the
authorities having jurisdiction.
Installation
INSTALLATION Installing an RM-iC series reader involves:
1. Installing the mount plate
2. Wiring the components
3. Connecting and grounding the cable shields on the reader bus
4. Setting the RM-4 (reader) address
5. Installing the ARM-1 relay board (optional)
6. Installing the heater kit. (optional)
Installing the Mount
Plate
Figure 1 shows RM-iC standard housing, mount plate, and gasket. All RM-iC series
readers conform to the same housing, mount plate, and gasket dimensions.
Standard Housing
Housing
screws
Standard mount plate
Requires a security screwdriver
Gasket
FIGURE 1. Standard Housing and Mount Plate
Figure 2 shows mount plate dimensions.
5.45"
Wiring
access
4.11"
3.66"
4.94"
2.47"
1.29"
.83"
1.54"
1.82"
8x
2.73"
3.64"
Mounting hole
0.156" Thru, 0.280” Countersink
3.92"
FIGURE 2. Mount Plate Dimensions
Installation
This device has been approved for outdoor use when properly installed with RM
Heater Kit Installation (P.N. 130-915) and the supplied gasket material. Position
the gasket with the RM plate so that the mounting holes are properly aligned.
Ensure that the gasket is placed between the mounting surface and mating
surface of the RM plate. Fasten the RM plate to the mounting surface with the
gasket material in between. Install the gasket so that no gaps or wrinkles are
present.
Wiring the Inputs,
Outputs, Reader Bus
Figure 3 shows RM-4 P1 and P5 wiring.
FIGURE 3. RM-4 Wiring Requirements
Installation
Wiring the Reader
Figure 4 shows RM-4 P1 and P5 wiring.
FIGURE 4. RM-4 Reader Wiring
Installation
Grounding and
Shielding
When bus wiring more than one RM-iC reader (Figure 5 ):
1. Attach the shields along the bus together (insulate each connection). Snip off the
shield wire at the end of the bus.
2. Attach the shield to the ground at only one point, the ground stud inside the cabinet
adjacent to the knockout.
3. Attach a local earth ground (18 or 22 gauge) wire to the J5 component.
Ground stud
Twist shield wires together and insulate
(do not ground)
Shield wire
Shield wire
ACM module
Snip off shield
wire at end of
bus
Knockout
RS-485 connector on a reader
(bus configuration)
Enclosure/cabinet
FIGURE 5. Reader Shield Wiring
Setting Module
Address and
EOL Termination
To set the module address, set SW1 (16 position rotary switch) to a number from one to
eight. Every RM-iC series reader on a bus must have a unique address.
Installing the ARM-1
Relay
Two ARM-1 relay components can be connected to the RM-iC series reader through the
P5 connector (Table 1 ).
To set RS-485 EOL termination, set SW3-5 to the On (closed) position if the module is
the last unit in the bus. If the module is not last, SW3-5 should be Off (open).
„
P5-1 is the common (+12 VDC) pin for either ARM-1.
„
P5-2 is the output drive (GND) for the first relay.
„
P5-3 is the output drive (GND) for the second relay.
TABLE 1. ARM-1 Wiring
Module
Wiring
ARM-1 Relay
P2-1 to RM P5-1, P2-2 to RM P5-2
ARM-2 Relay
P2-1 to RM P5-1, P2-2 to RM P5-3
Installation
NOTE
Installing the Heater
The ARM-1 has not been evaluated by UL.
RM-iC readers require a heater kit (Model 130-915) when installed outdoors in an
environment and where temperatures may drop below 40° F (5° C).
The Model 130-915 heater kit contains the following parts:
TABLE 2. Heater Parts
Quantity
Description
Transformer 12 VAC 40VA
Heater Strips
Thermostat (turns on at 40 ° F)
Wire nuts
6-32 x 1/4” screws to mount thermostat to RM plate.
Part # 130-915A is supplied without a transformer. A UL Listed Class 2 transformer
rated output 12 VAC, 40 VA is required for proper installation.
Figure 6 shows RM/heater wiring.
FIGURE 6. RM/Heater Wiring
Installation
Figure 7 shows RM installation
FIGURE 7. RM Installation
Heater Strip Application
To avoid problems such as placing the strips too far away from the thermostat, not
allowing the thermostat to shut off, or locating the strips too close to the PCB and
causing component over-temperature concerns, follow mounting diagram and
heater strip application instructions.
To apply the heater strip:
1. Clean the attachment surface of the back plate with a solvent such as alcohol (use all
required precautions when handling solvents).
2. Carefully remove the release film from the adhesive.
3. Locate the heater on the clean surface of the back plate exactly as shown in Figure 6.
4. Gently roll in place to remove air bubbles.
5. Allow to remain for 72 hours before use, for maximum adhesion.
Air gaps or bubbles under the heater cause localized overheating and possible heater
burnout. Also, application of adhesives at temperatures below 50° F is not
recommended.
Installing the Thermostat
To install the thermostat:
1. Fasten the thermostat to the RM plate with the body of the device facing the junction
box and the face sitting flat against the RM plate surface.
2. With the back (or outside) surface facing up, align the thermostat such that the screw
holes of the thermostat allow for the 6-32 x 1/4" screws to secure the device to the
RM plate.
Testing with apC or iSTAR hardware
3. Use two (Quantity 2) 6-32 x 1/4" screws to mount the thermostat to the RM Plate.
Tighten the screws allowing the thermostat to be sufficiently secured to the plate. Do
not over tighten the screws.
TESTING WITH APC To test an RM-iC series reader with an apC or iSTAR:
OR ISTAR 1. Measure the supply voltage to the RM-4.
HARDWARE
The voltage can be measured between pin 1 (+12 VDC supply) and pin 4 (ground)
on the P4 connector. The voltage must be +12 VDC (+/-5%).
2. Check the RM-iC reader address setting.
The RM-iC must be set to an unused address, between 1 and 8, when connected to
the apC or iSTAR. Use rotary switch SW1 to set the reader address.
3. Check the RM-4 for communications to the apC or iSTAR. Observe LED2 and
LED3.
4. Check the supervised inputs. Configure the inputs on the apC or iSTAR.
With no switches or resistors connected to the supervised input 1 and 2 lines, the C•
CURE 800/8000 Monitoring Program should report inputs as “Open Loop”. When
you connect the 1,000-ohm resistor to the input terminals, the C• CURE 800/8000
Monitoring Program should report that the input as “Deactivated”. Supervised
inputs #1 is found at pins 4 and 5 of P5. Supervised input #2 is found at pins 6 and 7
of P5.
5. Check the outputs.
The outputs can be functionally tested by using the “momentary activate” feature in
the C• CURE 800/8000 Monitoring Program. When the outputs are momentarily
activated, the signal will change state for a few seconds. A 1,000 ohm resistor and an
LED can be connected to the output to obverse the functionality. Connect the
resistor to pin 1 of P5 (+12VDC). Connect the anode of the LED to the resistor and
connect the cathode to pin 2 of P5 for output #1 and to pin 3 of P5 for output #2.
6. Check the reader interface.
The reader interface can only be tested with the reader chosen for the installation.
Reading a card will cause the display to show “Access Granted” or “Access
Denied”, depending upon the clearance of the card.
Testing Readers with iSTAR PRO Hardware
TESTING READERS To test an RM-iC series reader with iSTAR Pro, use the iSTAR Pro S4 switch, positions
WITH 5 through 8.
ISTAR PRO
Table 3 shows S4 settings for Positions 5 through 8.
HARDWARE
TABLE 3. S4 Diagnostic Settings
Switch Setting
Description
Position 5
Position 6
Position 7
Position 8
Off
Off
Off
Off
Display status messages (ICU Block Off)
On
On
On
On
Display status messages (ICU Block On)
Off
Off
Off
On
Display card data
Off
On
Off
On
Display card data in fast mode
Off
Off (2 second
LCD display)
On
Off
Test inputs
On (1 second
LCD display)
Off
Off
On
On
Manual output test (RMs and R/8s)
Off
On
Off
Off
Automatic ACM output test
Off
On
On
On
Automatic output test (including RMs and R/8s)
On
Off
Off
Off
Ethernet/PCMCIA port and device test
On
On
Off
Off
DIMM memory test
On
Off
Off
On
Battery charger test
Canadian Radio Emissions Requirements
CANADIAN RADIO This digital apparatus does not exceed the Class A limits for radio noise emissions from
EMISSIONS digital apparatus set out in the Radio Interference Regulations of the Canadian
REQUIREMENTS Department of Communications.
Le present appareil numerique n’emet pas de bruits radioelectriques depassant les
limites applicables aux appareils numeriques de la class A prescrites dans le Reglement
sur le brouillage radiolelectrique edicte par le ministere des Communications du
Canada.
FCC DIGITAL Radio and Television Interference
DEVICE
LIMITATIONS This equipment has been tested and found to comply with the limits for a digital
device, pursuant to Part 15 of the FCC rules. These limits are designed to provide
reasonable protection against harmful interference when the equipment is
operated in a commercial environment. This equipment generates, uses, and can
radiate radio frequency energy and, if not installed and used in accordance with
the instruction manual, may cause harmful interference to radio communications.
Operation of this equipment in a residential area is likely to cause harmful
interference, in which case the user will be required to correct the interference at
his own expense.
Operation is subject to the following two conditions: (1) This device may not cause
harmful interference, and (2) this device must accept any interference received,
including interference that may cause undesired operation.
In order to maintain compliance with FCC regulations, shielded cables must be
used with this equipment. Operation with non-approved equipment or unshielded
cables is likely to result in interference to radio and television reception.
Caution: Changes or modifications not expressly approved by the manufacturer
could void the user’s authority to operate this equipment.
10

Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : No
Page Count                      : 10
Page Mode                       : UseOutlines
XMP Toolkit                     : XMP toolkit 2.9.1-13, framework 1.6
About                           : uuid:23e417a9-9e6f-4383-a6be-ef207dc13c2d
Producer                        : Acrobat Distiller 7.0.5 (Windows)
Creator Tool                    : FrameMaker 7.0
Modify Date                     : 2006:04:19 13:05:15-04:00
Create Date                     : 2004:09:13 07:37:39Z
Metadata Date                   : 2006:04:19 13:05:15-04:00
Document ID                     : uuid:f1990614-5a97-4b3b-b570-907e5e8364c4
Instance ID                     : uuid:ec46a0e6-e2fd-4217-9022-443fca9ebb42
Format                          : application/pdf
Title                           : rm1-ICP_quick_install.fm
Creator                         : t_wood
Author                          : t_wood
EXIF Metadata provided by EXIF.tools
FCC ID Filing: SZC-PH

Navigation menu