DATa sheet

Input/Output Modules
Features That Make a Difference:
	Provides cost-effective expansion of input and output capacity
	Compatible with full range of Software House® iSTAR and apC
access control panels
	Locate modules up to 1,220 m (4,000 ft) away from controllers using
flexible two-wire RS-485 RM bus
	Reduces length of sensor and control wiring to save installation
costs
	I8 provides eight Class A supervised inputs
	R8 provides eight Form C relay outputs
	I8-CSI, configurable supervised input model, allows use of existing
input wiring without changing end-of-line (EOL) resistors
	Three status LEDs per input (red/yellow/green) and one per output
enable quick diagnostics and troubleshooting
	Small, modular size requires minimal panel space
	Dedicated tamper input included on each module
	Optional UL-listed enclosure available

The Software House I8, R8, and I8-CSI modules provide a
flexible, cost-effective means to expand the input and output
functionality of any iSTAR or apC access controller. Common
applications include alarm monitoring and control and elevator
control.
The I8 input module provides eight Class A supervised inputs.
Three LEDs per input help the installer commission and
troubleshoot each input circuit – red if the input is in alarm,
green for normal, and yellow for a supervision error. LEDs may
be turned off via a DIP switch setting.
The I8-CSI module enhances the functionality of the standard
I8 module by supporting numerous supervised circuit types and
EOL resistance values. This allows the I8-CSI to accommodate
existing field wiring without changing EOL resistors. More
than 20 different circuit types are supported. The circuit type
is selected via a bank of DIP switches and applies to all eight
inputs on the I8-CSI.

The R8 output module provides eight Form C dry contact relay
outputs. A red status LED per output shows the state of the
relay.
All modules feature a dedicated input for an external cabinet
tamper switch and mount easily in the Software House RM-CAN
or RM-DCM-CAN enclosure. The modules communicate with
iSTAR or apC controllers via the two-wire RM bus that allows
total wiring distances of up to 1,220 m (4,000 ft). Up to eight I8s
and eight R8s can be connected to each apC, iSTAR eX, and
iSTAR Pro eight-reader model; up to 16 of each module can be
connected to the iSTAR Pro 16-reader model.
The modules are fully compatible with both C•CURE® 800/8000
and C•CURE 9000.

s p e c ifi c atio n s

General

R8 Output Module

Dimensions (H x W) . . . . . 11.0 x 15.0 cm (4.3 x 5.9 in)
Environmental  . . . . . . . . . 0° to 50° C (32° to 122° F); 5 to 85% relative
humidity, non-condensing
Power Input Voltage  . . . . 12 VDC +/- 10%
Tamper . . . . . . . . . . . . . . . Dedicated input for external tamper switch
Weight . . . . . . . . . . . . . . . 0.23 kg (8 oz)
Regulatory . . . . . . . . . . . . UL 294, UL 1076, FCC Part A
CE, EN 50133, ROHS

Power Requirements . . . . 45 mA @ 12 VDC plus 32 mA per active relay
Outputs . . . . . . . . . . . . . . Eight Form C dry contact relays
LED per Output . . . . . . . . Red (relay active)
Relay Contact Ratings . . . 30 VDC, 2.0 A resistive
30 VDC, 1.0 A inductive
125 VAC, 4.0 A

Optional Metal Enclosures with Tamper Switch
RM-DCM-CAN
Dimensions . . . . . . . . . . 356 x 305 x 89 mm (14 x 12 x 3.5 in)
Capacity  . . . . . . . . . . . . Up to four input or output modules

I8 Input Module

Power Requirements . . . . 180 mA @ 12 VDC
Inputs . . . . . . . . . . . . . . . . Eight Class A supervised
LEDs per Input . . . . . . . . . Red (alarm), green (normal), and yellow
(supervision error)

RM-CAN
Dimensions . . . . . . . . . . 210 x 184 x 83 mm (8.25 x 7.25 x 3.25 in)
Capacity  . . . . . . . . . . . . One input or output module

I8-CSI Input Module

Model Numbers

Power Requirements . . . . 80 mA @ 12 VDC
Inputs . . . . . . . . . . . . . . . . Eight Class A supervised, configurable via DIP switch
LEDs per Input . . . . . . . . . Red (alarm), green (normal) and yellow
(supervision error)
Circuits Supported . . . . . . Single resistor: 1K, 5K, 10K
Double resistor: 1K, 5K, 10K,
1K/2K, 6.8K/18K, 200/10K
Unsupervised: NO, NC

AS0073-001  . . . . . . . . . . I8 input module
AS0073-CSI . . . . . . . . . . . I8-CSI input module
AS0074-000 . . . . . . . . . . .R8 output module
RM-DCM-CAN . . . . . . . . . Large metal enclosure with tamper switch
RM-CAN  . . . . . . . . . . . . . Small metal enclosure with tamper switch

Wiring Summary
Signal

From

To

Belden #

Gauge

# of Pairs

Shielded

Maximum Length

Comm
(two-wire RS485)

apC/iSTAR

I8/R8

9841*

24

1

Yes

1,220 m
(4,000 ft)

Power

apC/iSTAR

I8/R8

9841*

24

1

No

Based on
voltage drop

Control Point

R8

Strike, Siren, etc.

8442/8461

18

1

No

Based on
voltage drop

Supervised Input

I8

REX or Door Contact

8442/8461

22/18

1

No

610 m (2,000 ft)

Sample System Configuration: Combination Bus/Star Wiring Diagram

(*) For plenum or underground applications, use Belden 89182 for one pair 22 AWG, 100 ohm 12.95 pf/ft.
Note: Control, supervised, and unsupervised input cables must be shielded for FCC Class B operation.
Product offerings and specifications are subject to change without notice. Actual products may vary from photos. Not all products include all features. Availability varies
by region; contact your sales representative. Certain product names mentioned herein may be trade names and/or registered trademarks of other companies.

© 2008 Tyco International Ltd. and its respective companies. All rights reserved. SH0146-DS-200810-R01-LT-EN

www.swhouse.com

1
ON

INH

DS24
DS23

DS2

S3

S3

P7

1

DS26

P2

P8

DS25

4

3 4

3

2

2

GND

S1

DS27

1
DS22

DS7

U3

ING

Y1

DS6

DS21
DS20

DS5
FOR SWH STD 1K DUAL S2:3-4, S3:1-4 = OFF
SEE QUICKSTART DOC FOR OTHER SETTINGS
CYCLE POWER AFTER SETTING

P3

P6
1

DS19

"WARNING Damage may result from incorrectly
wiring power terminals, input and output lines, and
central-supervising station lines. Check all
connections before powering the unit."

DS8

INF

DS18
DS17
S2

S2

P5

1

P4

3 4

DS9

2

DS10

DS16
DS15

DS12
SW1
DS11

ASSEMBLED IN USA
C

1

ON

1
DS13

INE

I8-CSI Input Module Configuration

R8 Output Module Configuration

NOTE: All mounting holes are 1/8" dia.
Max. component height 1/2".

P10

SW1

P5
1
2
3

1

-D

1

2 3 4 56
1
7
8
0
F
9
E DC B A

P6
1
2
3

+D

DS3

IND

3
2
1

2
3

+12V

S1

1

P4

TAMPER
INPUT

P7
1

GND

DS4

INC

3
2
1

1
2
3

1

P3

R8 OUTPUT MODULE
AS-0074-000 REV.A
SOFTWARE HOUSE
MADE IN USA

NO
NC
C
NO
NC
C
NO
NC
C
NO
NC
C

TS

DS1

S1-1 ON = LED Power
S1-2 ON = Disable Tamper
S1-3 ON = Not Used
S1-4 ON = 485 Termination

1

1

P1

INB

3
2
1

W1

P8

NO

P2

C
NC
NO
C
NC
NO
C
NC
NO
C
NC
NO

P9

1

3
2
1

1 2 3 4

P9

P1

INA

I8 Input Module Configuration

Wiring Configuration Diagram

COPYRIGHT 2007

TYCO

SOFTWARE HOUSE®

18–CSI BOARD
0312–5008–01 Rev.

Input Rating P9
12VDC 125mA

DS14

Refer to Quick Start Installation Guide,
P/N UM-218, Rev B0, July 2008

Pb
Pb-Free



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : No
Page Mode                       : UseThumbs
XMP Toolkit                     : Adobe XMP Core 4.0-c316 44.253921, Sun Oct 01 2006 17:08:23
Instance ID                     : uuid:b3ab2a59-10b0-d946-9322-12a4703d81a4
Document ID                     : adobe:docid:indd:f6c8d5a1-a333-11dd-a693-fcbb1a3caf90
Rendition Class                 : proof:pdf
Derived From Instance ID        : 4bcca074-a1d1-11dd-b9dd-fa7d23252c9c
Derived From Document ID        : adobe:docid:indd:f8de7f20-9acd-11dd-8ff0-ed084a1f3f68
Manifest Link Form              : ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream
Manifest Placed X Resolution    : 72.00, 300.00, 72.00, 300.00, 72.00, 72.00, 72.00
Manifest Placed Y Resolution    : 72.00, 300.00, 72.00, 300.00, 72.00, 72.00, 72.00
Manifest Placed Resolution Unit : Inches, Inches, Inches, Inches, Inches, Inches, Inches
Manifest Reference Instance ID  : uuid:DEC18F48257411DC8A5CE70314FDCB65, uuid:E7296BA0E497DD1186EBE4EF0515491B, uuid:DEC18F48257411DC8A5CE70314FDCB65, uuid:22c3b72c-b7e3-11d9-bf6d-f7c04b46cb8b, uuid:E4D42CC1B79DDD11A704916A7228BB62, uuid:E1D42CC1B79DDD11A704916A7228BB62, uuid:7F772F53AC9DDD11A704916A7228BB62
Manifest Reference Document ID  : uuid:DEC18F46257411DC8A5CE70314FDCB65, uuid:A5A12035E297DD1186EBE4EF0515491B, uuid:DEC18F46257411DC8A5CE70314FDCB65, adobe:docid:photoshop:22c3b72b-b7e3-11d9-bf6d-f7c04b46cb8b, uuid:E3D42CC1B79DDD11A704916A7228BB62, uuid:80772F53AC9DDD11A704916A7228BB62, uuid:7E772F53AC9DDD11A704916A7228BB62
Create Date                     : 2008:10:24 08:09:03-07:00
Modify Date                     : 2008:10:24 08:12:02-07:00
Metadata Date                   : 2008:10:24 08:12:02-07:00
Creator Tool                    : Adobe InDesign CS3 (5.0.3)
Thumbnail Format                : JPEG
Thumbnail Width                 : 256
Thumbnail Height                : 256
Thumbnail Image                 : (Binary data 11362 bytes, use -b option to extract)
Format                          : application/pdf
Title                           : Input/Output Modules Data Sheet
Creator                         : ACVS Marketing
Producer                        : Adobe PDF Library 8.0
Trapped                         : False
Page Count                      : 2
Page Layout                     : SinglePage
Author                          : ACVS Marketing
Warning                         : [Minor] Ignored duplicate Info dictionary
EXIF Metadata provided by EXIF.tools

Navigation menu