UTC Fire and Security Americas 778A-SMOKE Smoke Detector User Manual

UTC Fire & Security Americas Corporation, Inc. Smoke Detector Users Manual

Users Manual

1ESL Universal Wireless Smoke Alarm/Detector 4300 SeriesWireless Smoke DetectorFigure 1 - Alarm/Detector FeaturesDescriptionThe ESL smoke alarm/detector is a Learn Mode, wirelesssensor that uses photoelectric technology with a selfcontained alarm siren, a low battery annunciator, and astatus LED. The smoke alarm/detector is part of a security/fire alarm system and communicates with the systemcontrol panel.Depending on the model, the smoke alarm/detectorprovides the following features:Self-diagnostics.  The ESL Universal Series smokes monitortheir own sensitivity and operational status. If the smokealarm/detector drifts out of the UL listed sensitivity rangeor fails internal diagnostics, it extinguishes its LED andsends a trouble signal to the control panel.Base tamper switch sends a trouble signal transmission tothe control panel when the smoke alarm/detector isremoved from its mounting base.Integrated fixed 135°F temperature and rate of rise heatdetector trips an alarm based on high temperature detectedor rapidly rising temperature rate (15° minimum) (models562STU and 572STU only).Transmitted Signal OutputsDepending on the model, the smoke alarm/detectortransmits the following signals to the control panel:• Alarm• Alarm restore• TamperWirelessESLUniversal WirelessSmoke Alarm/DetectorNX SeriesWireless Smoke Alarm/DetectorULLISTED• Low battery• Trouble signal• SupervisorySelecting a LocationSelecting a suitable location is critical to the operation ofsmoke alarms/detectors.  This equipment should beinstalled in accordance with the National Fire ProtectionAssociation’s (NFPA) Standard 72.  See Figure 2.    56X - UL 217 Smoke Alarm Series     57X - UL 268 Smoke Detector SeriesInstallation Instructions LEDTest/Silence buttonSounderA-8-1.2.1.a  Where to Locate the Required SmokeAlarms/Detectors in Existing Construction.The major threat from fire in a family living unit occurs atnight when everyone is asleep. The principal threat topersons in sleeping areas comes from fires in theremainder of the unit. Therefore, a smoke alarm/detector(s) is best located between the bedroom areasand the rest of the unit. In units with only one bedroomarea on one floor, the smoke alarm/detector(s) should belocated as shown in Figure 2 A.In family living units with more than one bedroom area orwith more than one floor, more than one smoke alarm/detector is required, as shown in Figure 2 B.In addition to smoke alarms/detectors outside of thesleeping areas, the installation of a smoke alarm/detectoron each additional story of the family living unit,including the basement, is required. These installationsare shown in Figure 2 C. The living area smoke alarm/detector should be installed in the living room or nearthe stairway to the upper level, or in both locations. Thebasement smoke alarm/detector should be installed inclose proximity to the stairway leading to the floorabove. Where installed on an open-joisted ceiling, thealarm/detector should be placed on the bottom of thejoists. The detector should be positioned relative to thestairway to intercept smoke coming from a fire in thebasement before the smoke enters the stairway.Optional temperature sensorCopy of Preliminary 11/27/00
2ESL Universal Wireless Smoke Alarm/DetectorDining RoomBasementBedroom BedroomLiving Room= Required smoke alarms/detectors= Additional smoke alarms/detectors required for new constructionFigure 2 B - Alarm/Detector PlacementFigure 2 A - Alarm/Detector PlacementFigure 2 C - Alarm/Detector PlacementDiningRoom Kitchen BedroomBedroomBedroomLiving RoomTV RoomDiningRoom Kitchen BedroomBedroomBedroomLiving RoomA-8-1.2.1.b  Where to Locate the Required Smoke Alarms/Detectors in New Construction.All of the smoke alarms/detectors specified in A-8-1.2.1.a forexisting construction are required and, in addition, a smokealarm/detector is required in each bedroom.A-8-1.2.1.c  Are More Smoke Alarms/Detectors Desirable?The required number of smoke alarms/detectors might notprovide reliable early warning protection for those areasseparated by a door from the areas protected by therequired smoke alarms/detectors. For this reason, it isrecommended that the householder consider the use ofadditional smoke alarms/detectors for those areas forincreased protection. The additional areas include thebasement, bedrooms, dining room, furnace room, utilityroom, and hallways not protected by the required smokealarms/detectors. The installation of smoke alarms/detec-tors in kitchens, attics (finished or unfinished), or garagesis not normally recommended, as these locations occasion-ally experience conditions that can result in improperoperation.Important !Regulations pertaining to smoke alarm/detector installa-tions vary from state to state. For more information, contactyour local fire department or local authority havingjurisdiction.In addition to NFPA 72, use the following location guide-lines to optimize performance and reduce the chance offalse alarms from the alarm/detector:•   Locate ceiling-mounted smoke alarms/detectors in thecenter of a room or hallway at least 4 inches from anywalls or partitions.• Locate wall-mounted smoke alarms/detectors so the topof the alarms/detector is 4 to 12 inches below the ceiling.• Locate in a suitable environment as follows:- Temperature between 40°F (4.4°C) and 100°F (37.8°C)- Humidity between 0 and 95% non-condensing• Locate away from air conditioners, heating registers andany other ventilation source that may interfere withsmoke entering the alarm/detector.• Mount smoke alarms/detectors on a firm permanentsurface, typically a stud or metal runner.• Locate away from large metallic objects.
3ESL Universal Wireless Smoke Alarm/Detector3. Making sure that the unit is removed from its base, put thepanel in program mode/Learn Mode.4. Remove the red plastic dust cover from the alarm/detector.The alarm/detector is shipped with a dust cover forprotection on construction sites with dusty environments.5. Press the test/silence button until the panel indicates thatthe sensor has been enrolled.6. Disconnect the alarm notification appliances, servicerelease devices, and extinguishing systems and test thecommunication between the control panel and each smokealarm/detector before permanently mounting the alarms/detectors as follows:- Press the test/silence button on the alarm/detector for 2 seconds. The alarm/detector sends a test signal to the control panel.- At the control panel, verify the test signal was received and the RF signal strength is adequate. If no signal is received or the RF signal is low, relocate the alarm/detector and retest.7. Using the two screws and anchors provided, mountthe base.8. Attach the alarm/detector to the mounting base asfollows:- Line up the raised tab on the lip of the alarm/detector  with the slot on the lip of the mounting base.  See Figure 3.- Insert the alarm/detector into the base and turn clockwise  approximately 15 degrees. It should snap firmly into place.9. Test the communication between the control paneland each smoke alarm/detector as follows:- One at a time, press the test/silence button on the alarm/detector for 2 seconds. The alarm/detector sends a test signal to the control panel.- At the control panel, verify the test signal was received.10. Test each alarm/detector (see Smoke Testing the Alarm/Detector) and reconnect all alarm notification appliances, service release devices, and extinguishing systems.Important !The control panel alarm and all auxiliary functions should beverified for a complete test of the system.Smoke Testing the Alarm/DetectorSmoke alarms/detectors should be tested in place annuallyusing smoke or Smoke! in a Can. Follow the instructions onthe canned smoke or use the following steps to test thealarm/detector with smoke:1. Hold a smoldering punk or cotton wick close to thesmoke entry openings.2. Gently direct the smoke into the alarm/detector for 20seconds or until an alarm is indicated.BE SURE TO PROPERLY EXTINGUISH THE SMOKESOURCE AFTER TESTING! The alarm/detector LED shouldremain on while the built-in transmitter sends an alarmsignal to the control panel. The alarm/detector will sound atemporal rhythm until the test/silence button is pressed.The alarm/detector automatically resets when smoke is nolonger present.Figure 3 - Alarm/Detector-to-Base AlignmentInstalling the Alarm/Detector1. Slide the battery compartment cover away from the alarm/detector to unsnap it and lift it off. See Figure 3.2. Observing proper polarity, insert the two lithium batteriesprovided into the alarm/detector battery compartment andreplace the battery compartment cover. TabSlotBatterycompartment
4ESL Universal Wireless Smoke Alarm/DetectorFigure 4 - Removing Alarm/Detector Cappanel to determine what action to take. If the unit has ahardware fault, it will stop reporting supervision signals tothe panel.Attaching and Removingthe Alarm/DetectorTo remove the alarm/detector from the mounting base,grasp the alarm/detector and turn it counterclockwiseapproximately 15 degrees. The alarm/detector should snapoff of the mounting base.Attach the smoke alarm/detector to its mounting baseas follows:- Line up the raised tab on the lip of the smoke alarm/detector with slot on the lip of the mounting base. SeeFigure 3.- Insert the smoke alarm/detector into the base and turnclockwise approximately 15 degrees. It should snap firmlyinto place.When to Replace the BatteriesWhen the batteries are low, the alarm/detector sends a lowbattery signal to the control panel, waits several days andthen chirps every 30 seconds until the batteries are re-placed. The sounder can be silenced for 24 hours bypushing the test/silence button. See Specifications forbattery type list.Testing the Alarm/DetectorSensitivityThe ESL Universal Wireless Series provides a sensitivitylevel test mode that allows you to check the alarm/detectorsensitivity using the test/silence button and the LEDindicator on the alarm/detector as follows:1. Press the test/silence button on the alarm/detector for 2seconds. The alarm/detector performs a test, and theLED flashes one to nine times.2. Count the number of LED flashes and use the followingtable to determine the status of the alarm/detectorsensitivity and what action to take, if any.Understanding the Test/SilenceButtonDepending on the model, the test/silence button on thesmoke alarm/detector performs three functions as follows:Testing = Press the test/silence button for 2 seconds. Thealarm/detector performs a sounder test (UL 217 modelsonly) and a sensitivity test and then sends a test signal tothe control panel.Silence alarm = Press to silence the sounder during analarm. After a few minutes, the sounder will resume lowbattery if smoke is still present.Silence low battery chirp = Press to silence a low batterychirp. The low battery chirp resumes after 24 hours if thecondition is not corrected.Understanding the LEDThe LED on the ESl Universal Wireless Series indicates thestatus of the alarm/detector as follows:FLASHING = Flashes every 9 seconds to indicate normaloperation.ON = Detects smoke, sending an alarm.OFF = Trouble. Maintenance is required. Check the controlAfter the flashes, if the sensitivity is within limits and allother tests pass, the smoke alarm/detector goes intoalarm and sends a test signal to the panel, then resets after5 seconds.If the sensitivity is not within limits, or an unserviceablehardware fault is detected, the LED extinguishes until thealarm/detector is serviced and the built-in transmitter sendsa trouble signal to the control panel.sehsalF noitarucsbO )xorppA( noitacidnI noitcA1A/NelbaecivresnU tluaferawdrah .detcetedgnivomerybtinuteseR nurerdnaseirettab rorreehtfI.tsetytivitisnes .tinuehtecalper,stsisrep3-2A/NsirotceteD/mralA evitisneston .hguonetinuteseR.tinuehtnaelC dnaseirettabgnivomeryb fI.tsetytivitisnesnurer ecalper,stsisreprorreeht .tinueht4 tf/%1.3 sirotceteD/mralA lamronnihtiw .egnarytivitisnesA/N5 tf/%6.26 tf/%1.27 tf/%6.19-8A/NsirotceteD/mralA .evitisnesoot ekomsehttahtyfireV deppanssirebmahc .tinunaelC.ylerucesnwod
5ESL Universal Wireless Smoke Alarm/DetectorReplacing the BatteriesUse only 3V lithium batteries listed in Specifications in thealarm/detector.1. Remove the alarm/detector from the mounting base. SeeAttaching and Removing the Alarm/Detector.2. Slide the battery compartment cover away from the alarm/detector to unsnap it and lift it off. See Figure 3.3. Remove the batteries and dispose of properly.4. Observing correct polarity, insert two new 3V lithiumbatteries into the battery compartment and replace thecover.5. Reattach the alarm/detector to the mounting base. SeeAttaching and Removing the Alarm/Detector.6. Test the system.Cleaning the Alarm/DetectorClean the alarm/detector cover with a dry or damp (water)cloth as needed to keep it free from dust and dirt.When necessary, clean the alarm/detector interior andreplace the smoke chamber as follows:1. Disconnect the alarm notification appliances, servicerelease devices and extinguishing systems.2. Remove the alarm/detector from its mounting base. SeeAttaching and Removing the Alarm/Detector.3. Remove the batteries. See Replacing the Batteries.4. Slide a flat-blade screwdriver in the slot on the alarm/detector cap and gently push the handle down to pry thealarm/detector cap up and off. See Figure 4.5. Press in on the sides of the field replaceable opticalchamber and pull it up and away from the optical baseand discard. See Figure 5.6. Blow out or use a soft-bristled brush to remove all dustand dirt from the optical base.7. Line the new field replaceable optical chamber up withthe optical base and snap into place both sides of theoptical chamber.8. Replace the alarm/detector cap as follows:-Line the alarm/detector cap up with the smoke alarm/detector.-Insert the alarm/detector cap into the smoke alarm/detector and turn clockwise approximately 15 degrees. Itshould snap firmly into place.9. Observing the proper polarity, put the batteries backin the alarm/detector and replace the batterycompartment cover.Smokechamber latchOptical baseFigure 5 - Alarm/Detector Parts10.Reattach the alarm/detector to its mounting base. SeeAttaching and Removing the Alarm/Detector.11.Test the alarm/detector sensitivity and reconnect allalarm notification appliances, service release devices andextinguishing systems. See Testing the Alarm/DetectorSensitivity.The control panel alarm and all auxiliary functions should beverified for a complete test of the system.Maintaining the Alarm/DetectorThe ESL Universal Wireless Series smoke alarms/detectorsare designed for easy field service and maintenance.When installed and used properly, they requireminimal maintenance.The smoke alarm/detector should be tested weekly. SeeTesting the Alarm/Detector Sensitivity and Smoke Testingthe Alarm/Detector.When the alarm/detector requires maintenance, it extin-guishes its LED and sends a signal to the control panel asdescribed in the following table.langiS deriuqerecnanetniaMlangiselbuorT.purewoptatsetflesdeliafrotceted/mralA eeS.tsetytivitisnesamrofreP ehtgnitseTytivitisneSrotceteD/mralA melborpehtfI. .rotceted/mralaehtecalper,stsisrepfotuosiytivitisnesrotceted/mralaekomS .gninaelcsdeenrotceted/mralaehtdnaegnar eeS rotceteD/mralAehtgninaelC .yrettabwoLecalpeR.wolerarotceted/mralaehtniseirettaB .seirettabehtImportant !SQUEEZEHEREAlarm/Detector capOptical chamberIndentation
6ESL Universal Wireless Smoke Alarm/DetectorFire Prevention and EscapeThe purpose of an early warning smoke alarm/detector is todetect the presence of fire in its early stages and sound analarm giving the occupants time to exit the premises safely.Avoid Fire HazardsNo detection device can protect life in all situations.Therefore, safeguards should be taken to avoid potentiallydangerous situations as follows:• Do not smoke in bed.• Do not leave children home alone.• Never clean with flammable liquids such as gasoline.• Properly store materials. Use general good housekeepingtechniques to keep your home neat and tidy.  A clutteredbasement, attic, or other storage area is an open invita-tion to fire.• Use combustible materials and electrical appliancescarefully and only for their intended uses. Do notoverload electrical outlets• Do not store explosive and/or fast burning materials inyour home.• Even after proper precautions have been taken, fires canstart. Be prepared.In Case of FireIn the event of a fire, you should do the following:• Leave immediately. Don’t stop to pack or search forvaluables.• In heavy smoke, hold your breath and stay low, crawl ifnecessary. The clearest air is usually near the floor.• If you have to go through a closed door, carefully feelthe door and door knob to see if undue heat is present. Ifthey seem cool, brace your foot against the bottom ofthe door with your hip against the door and one handagainst the top edge. Open it slightly. If a rush of hot airis felt, slam the door quickly and latch it. Unvented firetends to build up considerable pressure. Be sure allmembers of the household realize and understand thisdanger.• Use your neighbor’s phone or a street fire alarm box tocall the fire department. The job of extinguishing the fireshould be left to the professionals.Be PreparedPractice the following steps to prepare you and your familyin the event of a fire:• Perform fire drills regularly. Use them to assure recogni-tion of an alarm signal.• Draw a floor plan and show two exits from each room. Itis important that children be instructed carefully, becausethey tend to hide in times of crisis.• Establish one meeting place outside the home. Insistthat everyone meet there during an alarm. This willeliminate the tragedy of someone reentering the housefor a missing member who is actually safe.• If you have children and/or physically challengedpeople residing in your household, use window decalsto help emergency personnel identify the sleepingquarters of these individuals.Limited WarrantyESL is a brand of Interlogix, Inc. The manufacturerwarrants this smoke alarm/detector (except batteries) to befree from defects in material and workmanship underconditions of normal use for a term of 3 years from thedate of manufacture.During the warranty period, if an Interlogix product or anyof its components becomes defective, it will be repaired orreplaced without charge.Out-of-warranty units will be repaired at the discretion ofthe manufacturer or, if not, a card will be forwarded to thecustomer suggesting a replacement unit and the cost ofthat unit.This warranty does not apply to units which have beensubject to abuse, misuse, negligence or accident, or towhich any modifications, alterations or repairs have beenmade or attempted.This warranty is extended only to the original purchaser ofthe smoke alarm/detector and may be enforced only bysuch person. During the warranty period, if the alarm/detector or any warranted components thereof becomesdefective, it will be replaced or repaired without charge atthe manufacturer’s discretion if returned in accordancewith the following instructions:Obtain a Return Authorization Number by calling 1-800-648-7422 or 503-692-4052, then carefully pack it in a wellpadded and insulated carton and return, postal chargesprepaid to:Customer ServiceInterlogix Security & Life Safety Group12345 SW Leveton DriveTualatin, OR 97062-9938A note should be included advising the nature of themalfunction. Care must be exercised in the proper packingof alarms/detectors returned under this warranty asInterlogix will not be responsible for warranty repairs toequipment damaged because of improper packing.Detach and leave with the end user
7ESL Universal Wireless Smoke Alarm/DetectorTHE ABOVE WARRANTY IS IN LIEU OF ALL OTHEREXPRESS WARRANTIES, AND IMPLIED WARRAN-TIES OF MERCHANTABILITY AND FITNESS FOR APARTICULAR PURPOSE ARE LIMITED IN DURA-TION FOR A PERIOD OF THREE YEARS FROMTHE DATE OF MANUFACTURE. UNDER NO CIR-CUMSTANCES SHALL MANUFACTURER BE LIABLETO THE PURCHASER OR ANY OTHER PERSONFOR INCIDENTAL OR CONSEQUENTIAL DAMAGESOF ANY NATURE, INCLUDING WITHOUT LIMITA-TION DAMAGES FOR PERSONAL INJURY ORDAMAGES TO PROPERTY, AND HOWEVER OCCA-SIONED, WHETHER ALLEGED AS RESULTINGFROM BREACH OF WARRANTY BY MANUFAC-TURER, THE NEGLIGENCE OF MANUFACTUREROR OTHERWISE. MANUFACTURER’S LIABILITYWILL IN NO EVENT EXCEED THE PURCHASEPRICE OF THE PRODUCT. SOME STATES DO NOTALLOW LIMITATIONS ON HOW LONG AN IMPLIEDWARRANTY LASTS, OR THE EXCLUSION ORLIMITATION OF INCIDENTAL OR CONSEQUENTIALDAMAGES, SO THE ABOVE LIMITATIONS ANDEXCLUSIONS MAY NOT APPLY TO YOU. UNLESS ALONGER PERIOD IS REQUIRED BY APPLICABLELAW, ANY ACTION AGAINST MANUFACTURER INCONNECTION WITH THIS SMOKE ALARM/DETEC-TOR MUST BE COMMENCED WITHIN ONE YEARAFTER THE CAUSE OF ACTION HAS OCCURRED.No agent, employee or representative of the Manufacturernor any other person is authorized to modify this warrantyin any respect. Repair or replacement as stated above is theexclusive remedy of the purchase hereunder. This warrantygives you specific legal rights and you also have otherrights which vary from state to state.Warning! Limitations of SmokeAlarms/DetectorsWireless smoke alarms/detectors are very reliable, but maynot work under all conditions. No fire alarm/detectorprovides total protection of life or property. Smoke alarms/detectors are not a substitute for life insurance.Smoke alarms/detectors require a source of power towork.This smoke alarm/detector will not operate and the alarm willnot sound if batteries are dead or not installed properly.Unreliable transmission or receiving of radio frequency(RF) signals may occur if the system is not installed,located, serviced and repaired properly.RF signals sent by this alarm/detector may be blocked orreflected by metal objects.  Adjacent devices or systemsusing radio frequency signals may interfere with theoperation of this alarm/detector.  Test the system often to besure that signals are being sent and received properly.Smoke alarms/detectors may not be heard.  A soundsleeper or someone who has taken drugs or alcohol may notmay not awaken if the alarm/detector is installed outside abedroom. Closed or partially closed doors and distance canblock sound. This alarm/detector is not designed for thehearing impaired.Smoke alarms/detectors may not always activate andprovide warning early enough. Smoke alarms/detectors onlyactivate when enough smoke reaches the detector.  If a firestarts in a chimney, wall, roof, on the other side of closeddoors, or on a different level of the property enough smokemay not reach the detector for it to alarm.SMOKE ALARMS/DETECTORS ARE A SIGNIFICANTHELP IN REDUCING LOSS, INJURY AND EVENDEATH. HOWEVER, NO MATTER HOW GOOD ADETECTION DEVICE IS, NOTHING WORKS PER-FECTLY UNDER EVERY CIRCUMSTANCE AND WEMUST WARN YOU THAT YOU CANNOT EXPECT ASMOKE ALARM/DETECTOR TO ENSURE THAT YOUWILL NEVER SUFFER ANY DAMAGE OR INJURY.Detach and leave with the end userWARNINGSmoke alarms/detectors CANNOT providewarnings for fires resulting from explosions,smoking in bed or other furniture, ignition offlammable liquids, vapors and gases, childrenplaying with matches or lighters.FCC ComplianceThis device complies with Part 15 of the FCC rules.Operation is subjuect to the following two conditions:(1) this device may not cause harmful interference,and (2) this device must accept any interferencereceived, including interference that may causeundesired operation.FCC ID:  B4Z-778A-Smoke
8ESL Universal Wireless Smoke Alarm/DetectorSpecificationsVoltage............................................................3VDCTypical average standby current ........................ 25µATypical test current............................................ 2mATypical alarm current ....................................... 70mABattery type .................. Duracell® 3V lithium, DL123A              .......................Duracell® 3V lithium, MN1500              ........................Panasonic®  lithium, CR123A              ..............................Sanyo®  lithium, CR123A              .................Eveready Energizer®  lithium, E91Low battery threshold...2.70V causes low battery signalSounder ......................... 85dB at 10' temporal patternLow battery beep rate ............1 every 30 sec. ± 2 sec.Sensitivity ............................................ 2.3% ± 0.8%Operating temperature ................40°-100°F (4.4°-37.8°C)Operating humidity range ......... 0-95% non-condensingRFI Immunity ................ 20V/m minimum; 0-1000MHzColor ...............................................................whiteAlarm/Detector dimensions........................ 5.5" x 2.3"                                             (14 cm x 5.6 cm)Base dimensions ...........4.88" x 0.38" (12.3 cm x 0.95 cm)Drift compensation adjustment .............. 0.5%/ft. max.Heat detector specifications:Rate of rise.......15°F/min>105°F (8.3°C/min>40.6°C)Fixed .........................135°F ± 5°F (57.2°C ± 2.8°C)RF frequency............................................319.5 MHzTransmitter ID............Pre-programmed, 1 Million codesModulation type...................................................AMSignal format....................................................PWMSignal types:Outputs....................alarm, restore, tamper, low battery,                                              trouble,1 hour supervisoryListings:560 Series..........................................UL 217570 Series..........................................UL 268FCC ID...............................B4Z-778A-SmokeCanada.......................................... XXXXX1034595 Rev A   11/00Patents: 4,855,713 & 4,864,636 & 5,686,885 & 5,686.896

Navigation menu