Utica Boilers Hl Operation And Installation Manual

2015-05-20

: Utica-Boilers Utica-Boilers-Hl-Operation-And-Installation-Manual-719577 utica-boilers-hl-operation-and-installation-manual-719577 utica-boilers pdf

Open the PDF directly: View PDF PDF.
Page Count: 16

DownloadUtica-Boilers Utica-Boilers-Hl-Operation-And-Installation-Manual-  Utica-boilers-hl-operation-and-installation-manual
Open PDF In BrowserView PDF
P.O. Box 4729
Utica, NY 13504-4729
www.ecrinternational.com

HOTLINE
INDIRECT
WATER HEATER
MODELS HL30SK, HL40SK, HL50SK,
HL80SK, HL119SK

SET-UP, OPERATING &
MAINTENANCE
INSTRUCTION MANUAL
3 Twice the recovery of a standard gas-fired water
heater and four times the recovery of an electric
water heater.
3 Counterflow design increases heat transfer by
50% for better temperature mixing.

3 Unique, smooth tube heating coil resists lime
buildup that commonly reduces the life of other indirect water heaters.
3 Steel coil increases heat transfer for faster recovery and the luxury of never running out of hot
water.

3 Coils and tank lining are coated with the finest
porcelain enamel available. Its extra cobalt makes
our heaters highly resistant to damage from aggressive water.
3 Two-inch layer of environmentally-friendly CFCfree foam insulation enhances efficiency and cuts
fuel bills.
3 Commercial quality at residential prices.

WATER HEATERS

MADE IN THE U.S.A.
Page 1

To the Installer:

To the Consumer:

Please attach these instructions
next to the water heater.

Please read these and all component
instructions and keep for future reference.

Indirect Coil Tank Water Heater
Instruction Manual

Warranty, Registration Card and Parts List are included.
Homeowner: Please remember to return the Registration Card!

WARNING

INSTALLER RESPONSIBILITIES

Improper installation, adjustment, alteration,
service or maintenance can cause serious
injury or property damage. Refer to this
manual. For assistance or additional
information, consult a qualified installer or
service agency.

Please read all instructions thoroughly before
installing or placing the heater into service.
This unit must be installed by licensed or
authorized installers, or technical personnel
that service water heating equipment. The
heater must be installed in accordance with all
local codes and ordinances.
These instructions are a guide for the correct
installation of the water heater. The
manufacturer will not be liable for damages
caused by failure to comply with the installation
and operating instructions outlined on the
following pages.

CAUTION
The recommended temperature for normal
residential use is 120°F. The dial on the
aquastat does not always reflect the outcoming water temperature, which could
occasionally exceed 120°F. The variation in outcoming temperature could be based on factors
including but not limited to usage patterns and
type of installation. Test your water at the tap
nearest to the water heater.

WARNING
Hotter water increases the risk of scald injury.
Before adjusting the water temperature setting,
read this instruction manual. Temperatures at
which injury occurs vary with the person’s age
and the length of exposure.
The slower reaction time of children, elderly,
and physically or mentally challenged persons
increases the scalding hazard to them. It is
recommended that lower water temperatures
be used where these exposure hazards exist.
Such households may require a temperature
setting less than 120°F to prevent accidental
contact with hot water.
To lower water temperature use point-of-use
temperature limiting devices.

WARNING
Water heater blankets are not recommended
and will void the warranty.
THIS MANUAL HAS BEEN PREPARED
TO ACQUAINT YOU WITH THE INSTALLATION,
OPERATION, AND MAINTENANCE OF
YOUR WATER HEATER AND TO PROVIDE
IMPORTANT SAFETY INFORMATION.

#23945

CAUTION
The recommended water temperature setting for
normal residential use is 120°F/49°C.

HANDLING
Before uncrating, check for shipping damage.
Report any damage to your carrier. Note damage
on bill of lading or delivery receipt and file a
claim.
FAILURE TO FOLLOW THESE INSTRUCTIONS
OR ALL APPLICABLE BUILDING CODES AND
REGULATIONS VOIDS THE WARRANTY
ON THIS WATER HEATER.
Read all instructions thoroughly before
attempting installation or operation of your
water heater. Keep these instructions for future
reference.
Local plumbing and electrical codes must be
followed in the installation of this water
heater. In the absence of a local code use the
UNIFORM PLUMBING CODE and the NFPA
Code. Local codes may supersede instructions
in this installation manual.
These instructions are a guide for the correct
installation of the water heater. The
manufacturer will not be liable for damages
caused by failure to comply with the
installation and operating instructions
outlined on the following pages.

Rev 2 4/06

TABLE OF CONTENTS

Section I: Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Section II: General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Section III: Pre-Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Section IV: Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Section V: Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Section VI: Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Section VII: Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Section VIII: Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

Page 3

SECTION I: SPECIFICATIONS
Anode
Rod
Hot Outlet/
Anode Rod,
3/4" NPT

Hot Outlet,
1 1/2" NPT

Cold Inlet,
3/4" NPT

Anode
Rod

Anode
Rod

T&P Relief
Valve

T&P Relief
Valve

From Boiler
Supply, 1" NPT
From Boiler
Supply, 1" NPT

Aquastat

B

B
C

Aquastat

C

Drain
Valve

D

E

To Boiler
Return, 1"
NPT

D
To Boiler
Return,
1"NPT

G
E

F

F
Drain
Valve

H

A

G

A

Cold Inlet,
1" NPT

Figure 2: HL80SK, HL119SK

Figure 1: HL30SK, HL40SK, HL50SK
Table 1: Dimensions

Model

A

B

C

D

E

F

G

H

D i m e n s i o n s

HL30SK

22´´

35 3⁄4´

27 3⁄4´

19 1⁄2´

11 3⁄4´

6 1⁄2´

4 1⁄2´

n/a

HL40SK

22´´

42 3⁄4´

34 3⁄4´

31 1⁄2´

16 3⁄4´

6 1⁄2´

4 1⁄2´

n/a

HL50SK

22´´

48 3⁄4´

39 3⁄4´

31 1⁄2´

16 3⁄4´

6 1⁄2´

4 1⁄2´

n/a

HL80SK

24´´

64 3⁄4´

57 1⁄8´

33´´

19 1⁄4´

8´´

5´´

5´´

HL119SK

28´´

65 1⁄4´

57 3⁄4´

33 3⁄4´

16 1⁄4´

8 3⁄4´

5´´

6 1⁄2´

Foam insulation standard on Indirect models. Pressures, all: Test pressure, 300 PSI Working pressure, 150 PSI
Standard voltage, all: 120V, 60Hz, 1P. T&P valve installed; nipples supplied for top connection.
WARNING: Installation should be in accordance with all national and/or local codes.
CAUTION: The recommended water temperature setting for normal residential use is 120°F. ECR recommends a tempering
valve or anti-scald valve be installed and used according to the manufacturer's directions to prevent scalding.

Page 4

SECTION I: SPECIFICATIONS (cont.)
Table 2: Capacity & Performance

Con
Rat tinuous
ing
(GP Draw
H)*
Firs
t
Rat Draw
ing
(gal
)*

30

1.38

110

85

25

55,000

1.3

2.0

HL40SK

38

2.30

153

120

33

77,000

1.1

3.0

HL50SK

45

2.30

160

120

40

77,000

1.0

3.0

HL80SK

75

2.76

200

130

70

83,000

0.9

5.0

HL119SK

110

2.76

232

130

102

83,000

1.2

5.0

Coi
l
(gal Volum
e
)

HL30SK

Model

Act
u
Volu al Tank
me
(gal
)

Firs
t
Rat Hour
ing
(gal
)*

Capacities

Min
i
Out mum C
put
o
(BT il
U/H
r)**
Sta
n
Rat dby Lo
ing
(°F/ ss
hr)
Hea
t
Los Source
s (ft
. w.c Friction
.)

P e r f o r m a n c e

NOTES:
* Based on 77°F rise with 58°F potable water inlet temperature at 8 GPM heat source flow rate. Heat source temperature was 180°F.
** Minimum Coil output based on continuous boiler operation over 30 minutes. See Section III for additional considerations.
All data obtained through testing in accordance with GAMA INDIRECT-FIRED WATER HEATER TESTING STANDARD IWH-TS-1_MARCH 2003

Table 3: Performance (cont.)

20
12 0°F
GP
M*

20
10 0°F
GP
M*

20
8 G 0°F
PM
*

20
6 G 0°F
PM
*

18
12 0°F
GP
M*

18
10 0°F
GP
M*

Model

18
6 G 0°F
PM
*

FIRST HOUR RATING (gal) @ Coil Output (Btu/hr)

HL30SK 107 @ 53,000 114 @ 57,000 117 @ 59,000 129 @ 67,000 132 @ 69,000 136 @ 71,000 139 @ 73,000
HL40SK 141 @ 69,000 165 @ 84,000 177 @ 92,000 171 @ 88,000 183 @ 96,000 195 @ 104,000 207 @ 111,000
HL50SK 148 @ 69,000 172 @ 84,000 184 @ 92,000 178 @ 88,000 190 @ 96,000 202 @ 104,000 214 @ 111,000
HL80SK 188 @ 76,000 212 @ 91,000 224 @ 98,000 221 @ 97,000 233 @ 104,000 245 @ 112,000 257 @ 119,000
HL119SK 220 @ 76,000 244 @ 91,000 256 @ 98,000 253 @ 97,000 265 @ 104,000 277 @ 112,000 289 @ 119,000
NOTES:
First Hour Rating = First Draw + Continuous Draw
* Coil Input (temperature, flow rate). Ratings based on 77°F rise with 58°F inlet potable water.
All data obtained through testing in accordance with GAMA INDIRECT-FIRED WATER HEATER TESTING STANDARD IWH-TS-1_MARCH 2003

Page 5

SECTION II: GENERAL INFORMATION
LOCATION
The indirect coil tank water heater should be located in a central location to the piping
system, as close as practical to the boiler and in an area not subject to freezing temperatures.
Leave sufficient space for servicing and maintaining the heater.
Note: Long heating supply runs can lengthen recovery times.

WATER TREATMENT/FILTRATION
In areas where poor water conditions are suspected (i.e. lime, iron, and other minerals), it is
essential that the water be tested and appropriate action taken to prevent damage to the
indirect heater and ensure the quality of the water.

TEMPERATURE CONTROL
Water temperature from the heat source / boiler to the indirect coil tank water heater is
controlled by an immersion aquastat. This control operates the circulator, and provides
limited control for domestic hot water temperature. The proper temperature setting for
domestic hot water use is 120°F/49°C. If hotter water is required a tempering device or
anti-scald device must be installed at the domestic hot water outlet of the heater or at the
point of use.

CAUTION: Hot water in excess of 120°F
can cause scalding!
HotLine recommends a tempering valve or anti-scald valve be installed and used according
to the manufacturer’s directions to prevent scalding. Many state and local codes now require
installation of these devices. The tempering valve or anti-scald valve will ensure potable
water temperatures at the desired set point with a higher degree of accuracy.

IMMERSION CONTROL
HL30SK • HL40SK • HL50SK
HL80SK • HL119SK
APPROXIMATE
TEMPERATURE/TIME
RELATIONSHIPS TO
SCALDING

Page 6

120°F

More than 5 minutes

125°F

1 1⁄2 to 2 minutes

130°F

About 30 seconds

135°F

About 10 seconds

140°F

Less than 5 seconds

145°F

Less than 3 seconds

150°F

About 1 1⁄2 seconds

155°F

About 1 second

SECTION II: GENERAL INFORMATION (cont.)
ANODE RODS
The anode rod is used as a sacrificial element within the volume of the storage tank. The
purpose of the magnesium anode rod is to protect the inside of the tank against corrosion.
Anode rods should be inspected twice in the first year and at least yearly once a time interval
for inspection has been developed. Water conditions can influence the consumption rate of
the anode rods. Please see the Maintenance section of this manual for instructions on how to
change the anode rods in your Hot Line water heater.
CAUTION: Hydrogen gas is produced in a hot water system served by this heater that has not been used for
a long period of time (2 weeks or more). Hydrogen gas is extremely flammable. To reduce the risk of injury
under these conditions, it is recommended that the hot water faucet be opened for several minutes at the
kitchen sink before using any electrical appliance connected to the hot water system. When hydrogen is
present, there will probably be an unusual sound such as air escaping through the pipe as the water begins to
flow. There should be no smoking or open flame near the faucet at the time it is open (UL 174).

TEMPERAURE AND PRESSURE RELIEF VALUE (T&P)
The T&P valve is factory installed. A discharge drain tube must be installed (responsibility of
the installer) and shall terminate plain, not threaded, 6 inches above the floor drain. The
drain tube material must be approved for temperatures of 120°F or greater, and a pressure of
150 PSI or greater.

BACK-FLOW PREVENTOR (CLOSED LOOP SYSTEM)
Some local municipal codes and ordinances require the use of these devices on potable
(domestic) water lines. Where back-flow preventors are required, it will be necessary to
install a thermal expansion tank (designed for used with potable water) in order to prevent
pressure build up in the indirect heater and associated piping, which could cause the T&P
valve to discharge. Follow the expansion tank manufacturer’s recommendations when
selecting a tank for your hot water system.
Note: Working pressure of the water heater is 150 PSI. Do not exceed 150 PSI.

Page 7

SECTION III: PRE-INSTALLATION
BOILER AND CIRCULATOR SIZING
The ratings published in this manual for your HotLine Indirect Coil Tank Water Heater can
be obtained through proper selection of boiler output and circulator capacity. As noted, the
ratings in Table 2 are based on a 77°F rise with 58°F potable water inlet temperature at a
circulator pump flow rate of 8 GPM. The boiler was set at 180°F. See Table 3 for additional
first hour ratings at pump flow rates of 6, 8, 10 and 12 GPM with 180°F and 200°F boiler
water.
To determine the appropriate circulator for your system, follow these three steps:
1) Calculate the pressure drop of all straight pipe and fittings on the supply and return at the
desired flow rate.
2) Add the pressure drop from Step 1 to the pressure drop through the indirect coil tank
water heater coil (see Table 2 for friction loss) to obtain a total pressure drop.
3) Select a circulator pump that will provide adequate flow at the total pressure drop.
A pump performance curve should accompany every circulator pump. Figures 3-5 contain
performance curves for Taco and Grundfos circulator pumps, recommended by HotLine.

Figure 3: Taco 00 Series performance curves

Page 8

SECTION III: PRE-INSTALLATION (cont.)

UP 15-42F/FR
Closed Systems, 60 Hz

Figure 4: GRUNDFOS UP 15-42F performance curve

UP 26-64F
Closed Systems, 60 Hz

Figure 5: GRUNDFOS UP 26-64F performance curve
Note: Zone valves on the heat source supply to the indirect heater are not recommended
and will drastically reduce performance.
System performance can also vary based on the heating capacity of the boiler. If the
minimum coil output (assume coil output = boiler output) listed in Tables 2 and 3 is not met,
the output (first hour rating) of the water heater will not be met at the selected flow rate.
To approximate the reduction in first hour rating as a result of low boiler capacity, use the
following formula:
New first hour rating = (First hour rating) * (Actual boiler output)/(Minimum coil output)
For example, the first hour rating of a 50SK at a 77°F rise with an 8 GPM heat source flow rate
using a boiler having a DOE heating capacity (output) of 60,000 BTU/Hr would be:
New first hour rating = (160 gal) * (60,000 BTU/Hr)/(77,000 BTU/Hr) = 125 gal

Page 9

SECTION IV: INSTALLATION
WATER CONNECTIONS
All piping between the boiler and the indirect heater should be new copper with a
minimum size of 3/4” ID for models HL30SK, HL40SK, and HL50SK. Use 1” minimum copper
for models HL80SK and HL119SK. Elbows should be minimized. A flow check valve must be
installed on the return line.
All piping to the inlet (cold) and outlet (hot) domestic water connections should be new
copper with a minimum size of 1/2” ID for models HL30SK, HL40SK, and HL50SK. Use 3/4”
ID minimum for models HL80SK and HL119SK.
All piping should conform to local codes and ordinances. At a minimum, refer to IHLR 84
code if local codes are not in place. It is recommended that all piping be adequately
insulated with approved material to ensure minimum heat loss. If a re-circulation line is
used for domestic water, be certain that all lines are well insulated and the circulator is
temperature controlled. Install isolation valves to permit proper servicing. It is also
BOILER
SYSTEM
recommended to install a union on the domestic outlet to
facilitate
replacement of the
hot
3/4"
SUPPLY
3/4"
COLD
CIRCULATOR
DOMESTIC
outlet / anode nipple on models HL30SK, HL40SK, and HL50SK.
INLET
PUMP
HOT OUT
See Figures 6 and 7 for proper water connection installation.
INDIRECT
WATER HEATER

3/4"
DOMESTIC
HOT OUT

BOILER
SYSTEM
SUPPLY

3/4"
COLD
INLET

BOILER

CIRCULATOR
PUMP

FROM
BOILER
1" NPT

TO
BOILER
1" NPT

INDIRECT
WATER HEATER

BOILER
SYSTEM
RETURN

CHECK
VALVE

BOILER
FROM
BOILER
1" NPT

TO
BOILER
1" NPT

BOILER
SYSTEM
RETURN

CHECK
VALVE

BOILER
SYSTEM
SUPPLY
CIRCULATOR
PUMP

HL

Figure 6: HL30SK, HL40SK, HL50SK
water connections

1 1/2"
DOMESTIC
HOT OUT

INDIRECT
WATER HEATER
BOILER
SYSTEM
SUPPLY

BOILER

CIRCULATOR
PUMP

Note: Indirect may be connected to a steam
boiler provided that all piping to and from
the boiler are below the water line of the boiler.
Boiler INDIRECT
must also be protected by a low water
WATER HEATER
safety device.
cut off

1 1/2"
DOMESTIC
HOT OUT

FROM
BOILER
1" NPT

1"
COLD
INLET

TO
BOILER
1" NPT

CHECK
VALVE

BOILER
SYSTEM
RETURN

BOILER

Figure 7: HL80SK, HL119SK water connections

FROM
BOILER
1" NPT

1"
COLD
INLET

Page 10

TO
BOILER
1" NPT

CHECK
VALVE

BOILER
SYSTEM
RETURN

SECTION IV: INSTALLATION (cont.)
See Figure 8 for piping your HotLine Indirect Coil Tank Water Heater to a low-mass boiler
(diagram recommended by boiler manufacturer).

TO
HEATING
ZONE

FROM
HEATING
ZONE

CHECK
VALVES
ZONE
CIRCULATORS
ISOLATION
VALVES
ISOLATION
VALVES

AIR
SEPARATOR

LESS THAN (4)
PIPE DIAMETERS

AIR VENT

ADDITIONAL
ZONES

ADDITIONAL
ZONES

BOILER
CIRCULATOR

INDIRECT
CIRCULATOR

EXPANSION
TANK

INDIRECT WATER
HEATER

COLD
WATER
INLET

BOILER

Figure 8: HotLine Indirect with Low-Mass Boiler

Page 11

SECTION IV: INSTALLATION (cont.)
ELECTRICAL CONNECTIONS

Figure 9: Boiler Maintaining 180°F

Figures 9 and 10 are general wiring diagrams.
For a maintaining temperature boiler, Figure 9
should closely match your system. For cold start
boilers your wiring may resemble Figure 10, but
will vary depending on the boiler type and
controls or relays used. It is not possible to list all
wiring variations here. When connecting to a cold
start boiler, always remember that in principle an
indirect coil tank heater operates as another
heating zone. The difference is when the indirect
calls for heat, the indirect coil tank heater
circulator must start rather than opening a zone
valve; the system circulator stays off; and the
boiler must light to reach high limit.
WIRING NOTES:
1. Dashed lines indicate low voltage (24 VAC)
2. Use jumper wire between terminals #1 and #3
on R845 relay
THERMOSTAT SPECIFICATIONS:
Thermostats can operate at low or line voltages.
24 volt

N/A

120 volt

8 amp

240 volt

5 amp

This equipment must be properly grounded to
prevent a potential shock hazard, and to reduce
deterioration of the anode due to electrolysis.
Refer to local electrical codes and ordinances.

Figure 10: Cold Start Boiler

Page 12

SECTION V: MAINTENANCE
WATER PIPING
On an annual basis, all piping should be checked for leakage at joints, shut-off valves, and
unions.

T&P RELIEF VALVE
On an annual basis, the temperature and pressure relief valve should be checked for proper
operation. First, attach a drain line to the valve to direct the water discharge to an open
drain. This is very important because the temperature of the discharge could be very hot.
Second, lift the lever at the end of the valve several times. The valve should operate freely
and return to its original position properly. If water does not flow out of the valve, remove
and inspect for corrosion or obstructions. Replace with a new valve if necessary. Do not
repair the faulty valve as this may cause improper operation.

ANODE RODS
Anode rods should be inspected twice in the first year and at least yearly once a time interval
for inspection has been developed. It is recommended to check the rod(s) six months after
the heater is installed. If the anode rod had reduced in size by two-thirds of its original
diameter of 3/4” or shows signs of pitting, it is time for replacement. Take the following
steps when changing the anode rod(s):
1. Shut off water supply.
2. Open any faucet to relieve tank pressure.
3. Remove caps on water heater top; push insulation aside.
4. Use a 1 1/16” six-sided socket wrench and a breaker bar. Snap hard to break the anode
rod seal.
5. Remove rod(s) and replace with new rod(s).
6. Turn water supply back on and leave faucet open until air is out of line.
7. Turn faucet off and check that new rod(s) doesn’t leak.
8. Snap caps back into place.

FLUSH THE TANK
The indirect coil tank water heater is glass lined. Elements in the water such as lime, iron
and other minerals may accumulate in the heater. It is recommended that the tank be
drained and flushed thoroughly once a year to prevent buildup in the tank.

Page 13

SECTION VI: TROUBLESHOOTING
PROBLEM
CAUSE
No hot water at faucet Boiler does not
operate

Circulator does not
operate
Improper aquastat
setting
Electrical problem
(relay, wiring, etc.)
Scale build-up

Water at faucet too
hot

Insufficient hot water

Electrolysis or air
introduced by water
supply
Reduction in recovery Dip tube broken or
compromised by high
chlorine in water
Inlet/Outlet fitting
Galvanic corrosion of
corrosion
dissimilar metals
T&P Valve dripping
Excessive water
water
pressure (above 150
psi)
T&P gushing water

Page 14

Check fused disconnect
Check power supply
Replace as necessary
Check aquastat setting
Turn tank aquastat to safe
temperature setting
Check fuse and replace
Check circuit breaker and
reset (if applicable)
Check power supply
If boiler, circulator, and tank
are operating satisfactorily,
coil may have scale coating.
See Section VI for tank
flushing procedure.

Aquastat set too high Lower aquastat setting to
safe level
Tempering valve not Check manufacturers
properly set or
instructions
defective
Aquastat set too low Raise aquastat setting to
safe level. See Section III
Undersized boiler with Rewire for priority
no priority to
domestic hot water
Peak use of hot water Determine peak usage,
is greater than tank
compare to tank capacity,
storage capacity
and add additional storage
(storage tank) if necessary
Faulty tank aquastat
Replace aquastat

Boiler cycles more
Excessive demand
than 5 times per day
during hotest months Faulty aquastat
Boiler high limit set
too low
Scale, hard white
Lime, water hardness
particles from faucets, above 7 grainspopping sound from 120ppm
tank
Rust staining; bad
Iron/minerals in water
taste and odor in
supply
water
Rotten egg odor
Hydrogen Sulfide
Air from hot water
fixture

SOLUTION
Refer to boiler installation
instructions
Check main service switch

Reduce demand or consider
larger tank
Replace aquastat
Increase boiler high limit
setting
Water treatment; softener;
etc.
Filtration
Flush tank with chlorine
solution and install
alumninum anode rod(s)
Properly ground heater &
replace anode rod(s). Check
well pump system.
Replace dip tube
Install dielectric unions
Check incoming water
supply pressure; closed loop
system (System Plus)
requires expansion tank

Excessive water temp. Adjust or replace aquastat
(above 210 °F)
and T&P valve

SECTION VII: PARTS LIST

#

Item #

Qty

1
1
1
2
2
2
3
3A
4
5
5
6
6
7
8
9
10
11
12
13
14
15

ST00301
ST00701
ST00901
ST00401
ST00801
ST01301

1
2
2
1
1
1

ST00601
ST01001

1
1

ST01101

1

INDIRECT COIL TANK WATER HEATERS
HL30SK, HL40SK, HL50SK, HL80SK, HL119SK
Description
Magnesium Anode Rod 3/4" x 30"
Magnesium Anode Rod 3/4" x 36"
Magnesium Anode Rods 3/4" x 40"
Dip Tube 3/4 x 3 x 33"
Dip Tube 3/4 x 3 x 44"
Dip Tube 3/4 x 3 x 38"
Nipple 3/4 x 3", Hot Out or T&P
Nipple, 1 1/2"
Cap, Magnesium Anode Rod
Leak Detector Fitting
Leak Detector Fitting
T&P Relief Valve 3/4" LL100XL
T&P Relief Valve 140X-5 (use with 15370)
Drain Valve 3/4 x 2 1/4"
Cold Water Inlet Bushing 1"
Well - PNW-3SE 1.5PL (use with 21575)
Ring, Snap-in
Aquastat L4080B-1352
Steel Ring 5-3/8
Nipple, 1 x 3 , plastic lined
Finish Ring, plastic
Nipple 3/4 x 3", Hot Out with Anode

Applicable Models

HL30SK, HL40SK, HL50SK
HL80SK
HL119SK
HL30SK
HL50SK
HL40SK
HL80SK, HL119SK
HL80SK, HL119SK
HL30SK, HL40SK, HL50SK, (3) HL80SK, (3) HL119SK
HL30SK, HL40SK
HL50SK, HL80SK, HL119SK
HL30SK, HL40SK, HL50SK
HL80SK, HL119SK
HL30SK, HL40SK, HL50SK, HL80SK, HL119SK
HL80SK, HL119SK
HL30SK, HL40SK, HL50SK, HL80SK, HL119SK
HL30SK, HL40SK, HL50SK
HL30SK, HL40SK, HL50SK, HL80SK, HL119SK
HL80SK, HL119SK
HL30SK, HL40SK, HL50SK, HL80SK, HL119SK
HL30SK, HL40SK, HL50SK, HL80SK, HL119SK
HL30SK, HL40SK, HL50SK

Page 15

SECTION VIII: WARRANTY
LIMITED LIFETIME WARRANTY
GENERAL CONDITIONS
Hot Line Water Heaters, ECR International, warrants that the
Hot Line tank shall be free of defects in material and workmanship during normal use and service for as long as the original
residential purchaser owns the home in which the unit was originally installed. For the purposes of this Limited Warranty, residential purchaser is defined as the owner of a single family
home in which the purchaser resides on a permanent basis.
If at the time of a request for warranty the original residential
purchaser can not provide a copy of the original sales receipt,
deed, or equivalent document, then the warranty period for the
Hot Line shall be seven (7) years from the date of manufacture
of the unit. The Limited Warranty on the tank shall be reduced
to a period of three (3) years if the purchaser is a business, partnership or corporation, or if the water heater is used for a commercial or multi-family residential property application.
Should a leak develop within this Limited Warranty period due
to defective materials or workmanship and such leak having
been verified by an authorized company representative, ECR
International will repair the unit or furnish a replacement Hot
Line heater or the nearest comparable model available at the
time of replacement.
ECR International shall not be liable for any water damage
arising directly or indirectly from any defect in the water
heater or component part(s) or from the use thereof or any
service call not involving malfunction or defects in materials or
workmanship.

THIS WARRANTY IS VOID AND SHALL NOT APPLY IF:
1) The unit is not correctly installed according to the installation instructions provided with the unit.
2) The residential indirect-fired water heater is installed in
buildings other than one or two family dwelling units, unless
the buildings contain individual indirect-fired water heaters
for each dwelling unit.
3) The indirect-fired water heater is operated at water temperatures of more than 125 degrees F. and water pressure of
more than 150 PSI.
4) The failure or malfunction results from improper or negligent operation, accident, abuse (including freezing), misuse,
unauthorized alteration, improper repair or maintenance,
excessive pressure or leaks at water connections or any other
similar cause.
5) The failure or malfunction results from failure to keep the
unit full of potable water, free to circulate at all times; or failure due to water sediment or scale deposits.
6) The original serial number of the water heater cannot
readily be determined.
Page 16

7) ECR International Hot Line is installed outside of the
United States or Canada.
8) ECR International Hot Line is repaired or altered without
prior written approval of ECR International and this service adversely affects the product’s reliability.
9) The malfunction or repairs result from the use of ECR International Hot Line for purposes other than that for which it
was designed or any malfuction resulting from flood, fire,
wind or lightning.
ECR International will provide, under the Limited Warranty,
only a replacement water heater, repairs, or parts for defective units. The Limited Warranty does not cover any component of ECR International Hot Line that has to be replaced
during the warranty period as a result of reasonable wear
and tear, labor costs, shipping charges, delivery expenses,
nor administrative fees incurred by the customer in removing
or reinstalling the Hot Line.
In no event shall ECR International be liable for incidental or
consequential damages. Some states do not allow the exclusion
or limitation of incidental or consequential damages, so the
above limitation or exclusion may not apply to you.
In order to gain coverage under this Limited Lifetime Warranty, the consumer is required to fill out and mail the Limited
Warranty registration card provided with the unit by registered mail within 30 days of purchase.
To submit a warranty claim, contact the dealer who sold the
Hot Line covered by this Limited Warranty. If the dealer cannot be located, contact ECR International at the address
shown below. Whenever any inquiry or service request is
made, please include the Hot Line model number, serial number, date of installation, and dealer’s name.
No warranty, express or implied, other than the foregoing Limited Warranty is authorized by ECR International and no representative of ECR International or of the manufacturer of any
component has the authority to amend, extend, modify, enlarge
or contract the foregoing Limited Warranty and the disclaimers
of the Limited Warranty in any manner whatsoever.

WATER HEATERS

MADE IN THE U.S.A.

ECR International
P.O. Box 4729 • Utica, NY 13504-4729
www.ecrinternational.com



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : No
XMP Toolkit                     : 3.1-701
Create Date                     : 2006:05:01 07:46:01Z
Creator Tool                    : QuarkXPress(tm) 6.5
Modify Date                     : 2006:05:10 15:14:11-05:00
Metadata Date                   : 2006:05:10 15:14:11-05:00
Producer                        : QuarkXPress(tm) 6.5
X Press Private                 : %%DocumentProcessColors:.%%EndComments
Format                          : application/pdf
Title                           : Layout 1
Document ID                     : uuid:d237d56a-df81-11da-8bf4-000393c3788a
Instance ID                     : uuid:8bdffe2e-e061-11da-8ac7-000393c36e0e
Has XFA                         : No
Page Count                      : 16
Creator                         : QuarkXPress(tm) 6.5
EXIF Metadata provided by EXIF.tools

Navigation menu