Viessmann Vitotronic 200 300 Technical Manual 5167 888 V1.1
2015-08-26
: Viessmann Viessmann-Vitotronic-200-300-Technical-Manual-802299 viessmann-vitotronic-200-300-technical-manual-802299 viessmann pdf
Open the PDF directly: View PDF .
Page Count: 8
Certified as a component part
of Viessmann boilers only
VITOTRONIC 200
Weather-responsive indoor/outdoor, digital boiler control
for heating systems with one or more heating circuits
Vitotronic 200
Model KW2, Part No. Z001 230
For operation with modulating boiler water temperatures,
and single-stage, two-stage or modulating burners
With DHW tank temperature sensor and integrated
diagnostic system
Operating module with clear text LCD display
Remote control interface with room temperature sensor
(optional)
Viessmann quick-connect plug-in system
Technical Data Manual
5167 888 v1.1 11/2002
Product Information/Standard Equipment/
Application
2
Product Information
The benefits at a glance:
HEasy and uniform operation:
–Different programming levels for
system user and heating contractor.
–Large, clear text LCD display format
facilitates legibility of all data.
–Illuminated operating mode and
heating circuit keys.
–Easy-to-program switching times.
–Digital tracking of day and week.
Programmed times for domestic hot
water production and recirculation
pump are adjusted automatically
when heating program is altered.
–Plug & Work quick-connect system for
automatic sensor and system
recognition and adaptation.
–Automatic resetting to daylight
savings time.
–Service interval display for
demand-related maintenance.
–Fuel consumption display.
HProgram selection for controlled drying
of concrete floor in radiant floor heating
application.
HShort installation time,start-upand
maintenance due to Rast-5 connector
system, plug-in function modules and
integrated diagnostic system.
Vitotronic 200, Model KW2
HWeather-responsive indoor/outdoor,
digital boiler and heating system
control:
–for heating systems with one boiler
–for heating circuits without and
heating circuits with a mixing valve
–for single-stage, 2-stage and
modulating burners
–with DHW tank temperature sensor
–with digital tracking of day and week
–with separate switching times for
room heating, domestic hot water
heating and recirculation pump
–with integrated diagnostic system
Standard Equipment
Vitotronic 200, Model KW2
(Part No. Z001 230)
with
Hoperating module with clear text LCD
display
Houtdoor temperature sensor
Hboiler water temperature sensor
HDHW tank temperature sensor
HPower/Pump Module
For the heating circuit with a mixing
valve, a mixing valve actuator accessory
kit is required. Due to the low return
water temperature of condensing boilers
only 3-way mixing valves should be
installed. The circulation pump with a
flow check valve for DHW tank
temperature control must be ordered
separately.
Heating system with underfloor heating
The underfloor heating circuit requires an
accessory kit for operation with a mixing
valve.
A temperature control with high limit
must be installed in the heating supply of
the radiant floor heating application.
The underfloor heating circuit must not
be controlled by a remote control with
room temperature sensor.
Application
In conjunction with the following Viessmann boilers
Boiler Model and Series
Fuel Minimum boiler water
temperature
without low
limit
with low limit
(average temp.)
Oil-fired hot water
heating boiler with
power burner
Vitorond 200 Oil 104 ºF/40 ºC
Oil-/gas-fired hot water
heating boiler with
power burner
Vitola 200 Oil/Gas x
Atmospheric
gas-/propane-fired hot
water heating boiler
Vitogas 050, RS Series Gas 120 ºF/49 ºC
Atmospheric gas-fired
hot water heating boiler
Vitogas 100, GS1 up to 240 MBH / 70 kW
Vitogas 100, GS10 up to 380 MBH / 111 kW
Gas
Gas
104 ºF/40 ºC
120 ºF/49 ºC
5167 888 v1.1
OTS
STS
Structure and Operation
3
Structure and Operation
Modular structure
The complete control consists of a
control base, control unit
(electronic/operating modules) and a
Power/Pump Module.
The control unit comprises:
Power on/off switch, an electronic high
limit, a temperature gage and a low
temperature control
–adjustable high limit
–fixed high limit
TUV test switch, override switch,
buttons for:
–holiday program
–party and economy modes
–reduced operating mode temperature
–domestic hot water temperature
–programming of heating curves for
boiler water temperature and/or mixing
valve circuit temperature
–heating circuit selection,
a selector knob for normal operating
temperatures and a digital timer.
Heat-demand-controlled circuit pump and
burner activation, adjusting of a variable
temperature limit, pump cycling,
integrated diagnostic system and flue gas
monitoring in connection with flue gas
temperature sensor (optional) and
maintenance display.
Boiler-specific functions
The Vitotronic control modulates the
boiler water temperature.
It gradually regulates the boiler water
temperature (= the supply temperature
of the direct-connected heating circuit) as
well as the supply water temperature of a
mixing valve circuit. The control contains
an adaptive tank temperature control
logic with priority switching (heat pump
off, mixing valve closed).
An additional function for domestic hot
water heating (short-term heating to an
increased temperature) can be selected.
The Vitotronic 200 is an ideal control
option for your heating system with
mixing valve circuit. It is the perfect
solution for your underfloor heating
circuit with supply and return water
temperature sensor or for controlled
drying of a concrete floor.
Control characteristics
–Boiler circuit control unit (high
temperature)
–Heating circuit control with mixing
valve
Dead zone: ±1.80 ºF/1ºC
–Adjustable high limit factory default
setting: 167 ºF/75 ºC
–Adjustment of the fixed high limit:
230 ºF/110 ºC
adjustable to
212 ºF/100 ºC
–Adjustment range of heating curve:
Slope: 0.2 to 3.5
Shift: –23 ºF to +72 ºF/
–13 ºC to +40 ºC
High limit: 68 to 266 ºF/
20 to 130 ºC
Low limit: 34 to 261 ºF/
1 to 127 ºC
Differential temperature for heating
circuit with mixing valve: 0 to 72 ºF/
0to40ºC
–Adjustment range for domestic hot
water setpoint temperature:
50 to 140 ºF/
10 to 60 ºC
adjustable to
50 to 203 ºF/
10 to95 ºC
Technical data
Rated voltage: 120 VAC
Rated frequency: 60 Hz
Rated current: 6 A
Power consumption: 5 W
Maximum ambient
temperature
–at operation: 32 to 104 ºF/
0to 40 ºC
(in rooms and
installation sites
with normal
ambient
conditions)
–when storing or transporting:
–4 to +149 ºF/
–20 to +65 ºC
Relay output rating in conjunction with a
Power/Pump Module:
–Heating circuit
pumps: 3 FLA/120 VAC*1
–DHW tank heating
circulation pump: 3 FLA/120 VAC*1
–Domestic hot water
recirculation pump:3 FLA/120 VAC*1
–Mixing valve
actuator: 0.1 FLA/120 VAC*1
Operating time approx. 2 minutes
–Burner plug : 2 FLA/120 VAC
–2-stage burner
plug *2: 0.5 FLA/120 VAC
–Total: max. 12 A/120 VAC
*1Total 12 A/120 VAC
*2Available only with extension module
for 2-stage burner (included in boiler
package).
Boiler coding card
Adapts the control to the specific boiler
model being used (included in boiler
package).
Connections
–Sensors, burner and Power/Pump
Module are connected to the back of
the control unit via system plugs.
–Pumps, power supply and mixing valve
are connected to the Power/Pump
Module via screw terminals or system
plugs.
Operating unit
–With digital timer
–Clear text LCD display
–Temperature and fault display
–Coding via display of operating unit
–All adjustments and basic coding
information in clear text format.
5167 888 v1.1
Structure and Operation
4
Structure and Operation (continued)
Digital timer of operating unit
A digital timer with day and week
feature, calendar, automatic resetting to
daylight savings time and automatic
functions for domestic hot water heating
and recirculation pump.
Time, day and standard switching times
for room heating, domestic hot water
heating and domestic hot water
recirculation pump are factory preset
(individually programmable), max. four
time switch intervals programmmable per
day.
Shortest interval: 10 minutes
Power reserve: 5 years
Adjusting the operating system
All operating programs feature freeze-up
protection*1 for the heating system.
With the program selector buttons the
following can be selected:
–heating and domestic hot water
–domestic hot water only
–standby operation
*1 See Freeze-up Protection Function
below.
Freeze-up protection function
The freeze-up protection function is
–activated when the outside temperature
drops to +34 ºF/1ºC.
The freeze-up protection function
activates the circulation pumps and
keeps the boiler water temperature at
the reduced operation setpoint level, at
a minimum temperature of approx.
68 ºF/20 ºC (for heating boilers with
low limit the respective temperature
will be maintained).
–deactivated when the outside
temperature exceeds +37 ºF/3ºC.
When the freeze-up protection function
is deactivated, heating boiler and
circulation pumps are turned off.
Summer economy mode
(Domestic hot water heating only,
program selector switch ” ”)
The burner only activates if domestic hot
water needs to be produced (as required
by DHW setpoint).
Heating curve adjustment
The weather-responsive Vitotronic 200
regulates the boiler water temperature
(= supply water temperature of the
heating circuit without mixing valve) and
the supply temperature of the heating
circuit with a mixing valve.
The required supply temperature for a
certain room temperature depends on the
heating system and the insulation of the
building in question.
The adjustment of both heating curves
individually allows for the boiler water
temperature and the supply temperature
of the mixing valve circuit to be adjusted
to the respective conditions.
Heating curves:
Low temperature heating system,
e.g. radiant floor heating
Medium temperature heating system,
e.g. cast iron radiation, staple-up
radiant floor heating
High temperature heating system,
e.g. fintube radiation, fan coils
The maximum boiler water temperature is
restricted by both the adjustable high
limit and the electronic maximum
temperature limit.
The supply water temperature cannot
exceed the boiler water temperature.
Boiler water temperature sensor
Cable length 5.2 ft./1.6 m, ready to plug
in.
Maximum ambient temperature
– at operation: 32 to 266 ºF/
0 to 130 ºC
– when storing or transporting:
–4 to +158 ºF/
–20 to +70 ºC
Outdoor temperature sensor
Installation site:
–North or northwest side of building
–6.6 to 8.2 ft./2 to 2.5 m above ground,
for multi-storey buildings mount sensor
on upper half of second storey.
Connection:
–2-wire cable, cable length 115 ft./
35 m with a wire size of min. AWG 16
copper.
–the cable to the outdoor sensor must
not be laid near line voltage wiring
(120/240 V).
Maximum ambient temperature at
operation,
when storing or
transporting: – 40 to +158 ºF/
–40to +70ºC
Domestic hot water tank temperature
sensor
Cable length 19 ft./5.8 m, ready to plug
in.
Maximum ambient temperature
– at operation: 32 to 194 ºF/
0to 90ºC
– when storing or transporting:
–4 to +158 ºF/
–20 to +70 ºC
5167 888 v1.1
Accessories
5
Accessories
Note on the room temperature sensing
function (RS function)*1 when using a
remote control
Due to the slow response of the
underfloor heating, the RS function must
not influence the underfloor heating
circuit.
For heating boilers with a low limit, the
RS function must not influence the
heating circuit without a mixing valve.
*1RS function = remote control with
room sensor function
*2WS function = remote control only, no
room sensor function
Vitotrol 200,
Part No. 7133 378
The Vitotrol 200 remote control takes
care of the room temperature setpoint
adjustment at normal operation and
determines the heating program from any
given room.
The Vitotrol 200 features illuminated
heating program selector buttons as well
as a party and an economy button.
Fault messages are displayed on the
boiler control.
A remote control can be connected for
each heating circuit.
WS function*2: Allows for installation at
any given place in the building.
RS function*1: The remote control is to
be installed on an inside wall of the main
living area, across from radiators, but not
on shelves, in niches, in the close vicinity
of doors or heat sources of any kind (e.g.
direct sunlight, fireplace, TV, etc.).
The installed sensor measures room
temperature and, if necessary, takes
corrective action and initiates fast
heat-up at the outset of the heating
operation (if coded).
Connection:
–2-wire cable, cable length
max. 164 ft./50 m (also for the
connection of several remote controls).
–The cable must not be placed together
with line voltage wiring.
–Low voltage plug is included.
Rated voltage: 33 VAC
Rated current: 10 mA
Power consumption: 3.3 W
Maximum ambient
temperature
– at operation: 32 to 104 ºF/
0to 40ºC
–when storing
or transporting: –4 to+149 ºF/
–20 to +65 ºC
Adjustment range of
room temperature
setpoint: 50 to 86 ºF/
10 to 30 ºC
adjustable to
37 to 73 ºF/
3to23ºC
or
63 to 99 ºF/
17 to 37 ºC
Adjustment of the room temperature
setpoint at reduced operation takes place
at the Vitotronic 200.
Vitotrol 300,
Part No. 7133 382
The Vitotrol 300 remote control takes
care of the room temperature setpoint
adjustment at normal and reduced
operation for the heating program,
switching times for room heating,
domestic hot water heating and the
domestic hot water recirculation pump.
The Vitotrol 300 features illuminated
heating program selector buttons, a party
and an economy button, an automatic
reset function to daylight savings time,
buttons for the holiday program, day of
the week and time.
WS function*2: Allows for installation at
any given place in the building.
RS function*1: The remote control is to
be installed on an inside wall of the main
living area, across from radiators, but not
on shelves, in niches, in the close vicinity
of doors or heat sources of any kind (e.g.
direct sunlight, fireplace, TV, etc.).
The installed sensor measures room
temperature and, if necessary, takes
corrective action and initiates fast
heat-up at the outset of the heating
operation (if coded).
Connection:
–2-wire cable, cable length
max. 164 ft./50 m (also for the
connection of several remote controls).
–The cable must not be placed together
with line voltage wiring.
–Low voltage plug is included.
Rated voltage: 33 VAC
Rated current: 10 mA
Power consumption: 3.3 W
Maximum ambient
temperature
– at operation: 32 to 104 ºF/
0to 40ºC
–when storing
or transporting: –4 to +149 ºF/
–20 to +65 ºC
Adjustment range of
room temp. setpoint:
– at normal operation: 50 to 86 ºF/
10 to 30 ºC
adjustable to
37 to 73 ºF/
3to23ºC
or
63 to 99 ºF/
17 to 37 ºC
– at reduced operation: 37 to 99 ºF/
3to37ºC
5167 888 v1.1
Accessories
6
Accessories (continued)
Room temperature sensor,
Part No. 7133 379
A separate room temperature sensor as
an addition to the Vitotrol 200 or 300; to
be used when the Vitotrol 200 or 300
remote controls cannot be placed in the
main living area or in a position suitable
for monitoring the room temperature.
The room temperature sensor must be
installed on an inside wall of the main
living area, across from radiators, but not
on shelves, in niches or in the close
vicinity of doors or heat sources of any
kind (e.g. direct sunlight, fireplace, TV,
etc.).
The room temperature sensor is to be
connected with the Vitotrol 200 or 300.
Connection:
–2-wire cable with a wire diameter of
AWG 16 copper.
–Cable length between control unit,
remote control and room temperature
sensor must not exceed 115 ft./35 m.
–Cable must not be placed together with
line voltage wiring.
Maximum ambient
temperature
–at operation: 32 to 104 ºF/
0to 40ºC
–when storing
or transporting:
–4 to +149 ºF/
–20 to +65 ºC
KM-BUS Expansion Module,
Part No. 7133 393
With cable (10 ft./3 m long) and low
voltage plug.
To connect up to 6 devices to the single
KM-BUS connection of the boiler control
(Vitotrol, Switching Module-V etc.).
Switching Module-V,
Part No. 7133 387
With cable (10 ft./3 m long) and low
voltage plug.
With the Switching Module-V the
following additional functions are
feasible:
–external burner activation upon heat
demand (influences burner, possible
pumps and mixing valves), e.g. pool
heating, ventilation equipment etc.
–external disabling of burner
–remote switching of heating/operating
program, separate for each heating
circuit
–external error message input
–output of error message (SPDT contact)
–connection for short-term operation of
domestic hot water recirculation pump
(e.g. by external button)
5167 888 v1.1
Accessories
7
Accessories (continued)
Mixing valve actuator accessory kit,
Part No. 7133 390
consisting of a mixing valve actuator and
supply temperature sensor (strap-on
sensor)
Mixing valve actuator
The mixing valve actuator is to be
installed directly onto the Viessmann ¾
to 2½“ mixing valve.
The mixing valve actuator is a
bi-directional, single-phase, synchronous
motor with gear system and two limit
switches.
Rated voltage: 120 VAC
Rated frequency: 60 Hz
Power consumption: 4 W
Maximum ambient
temperature
– at operation: 32 to 104 ºF/
0to 40ºC
– when storing
or transporting: –4 to +149 ºF/
0to 65ºC
Torque: 3 Nm
Operating time
for 90º∢: 2 minutes
Strap-on sensor (included with mixing
valve actuator accessory kit),
Part No. 7133 895
To determine the supply temperature of
the mixing valve circuit.
Installed with a strapping band.
Cablelength19ft./5m,readytoplugin.
Maximum ambient
temperature
– at operation: 32 to 212 ºF/
0 to 100 ºC
–when storing
or transporting: –4 to +158 ºF/
–20 to +70 ºC
5167 888 v1.1
Viessmann Manufacturing Company Inc.
750 McMurray Road
Waterloo, Ontario •N2V 2G5 •Canada
Tel. (519) 885-6300 •Fax (519) 885-0887
www.viessmann.ca •mail@viessmann.ca
Viessmann Manufacturing Company (U.S.) Inc.
45 Access Road
Warwick, Rhode Island •02886 •USA
Tel. (401) 732-0667 •Fax (401) 732-0590
www.viessmann-us.com •mail@viessmann-us.com
8