Visonic DUO200E CEILING MOUNTED DUAL TECHNOLOGY DETECTOR User Manual USERS MANUAL
Visonic Inc. CEILING MOUNTED DUAL TECHNOLOGY DETECTOR USERS MANUAL
Visonic >
USERS MANUAL
DUO 200 Dual-Technology Microwave/PIR Intrusion Detector Installation Instructions 1. INTRODUCTION DUO 200 is a state-of-the-art microcomputer controlled dualtechnology intrusion detector. Its operation is based on two physical phenomena - the infrared (IR) radiation emitted by the human body and the Doppler frequency shift caused by a person moving in a microwave (MW) field. The IR and MW technologies, when combined in a single detector, complement each other to assure the most reliable detection and immunity to false alarms. The superiority of the DUO 200 over other dual detectors has been achieved by the advent of the True Motion Recognition™ algorithm (patented). This advanced motion analysis method provides the DUO 200 with the ability to distinguish between the true motion of a human body and any other disturbances which invariably cause false alarms. Another unique feature of the DUO 200 is the MW Motion Simulator circuit (patents applied for), which simulates the effect created by a human body moving in the MW field. The simulation routine is carried out periodically for self-testing, supervision and assurance that the MW detector operates properly. Figure 1. DUO 200 General View 2. SPECIFICATIONS Input Voltage: 9 to 16 VDC Current Drain: About 23 mA @ 12 VDC PIR SECTION (see Figure 2) Detector: Low noise dual-element pyroelectric sensor Trip Indication: Green LED flashes for up to 5 seconds True Motion Event Verification Counter: Selectable, 1 or 2 motion events Lens Data No. of Beams: 34 Field of View: 90° Max. Coverage: 12 x 12 m (40 x 40 ft) Vertical Adjustment: +2° to –12°, by sliding the circuit board along a calibrated scale. MW SECTION Oscillator: Microstrip DRO-stabilized type Frequency: 2.45 GHz Detection Range: Adjustable from 25% to 100% (3 m to 12 m) Trip Indication: Green LED illuminates for up to 5 seconds ALARM, TAMPER & TROUBLE DATA Alarm Indication: Red LED illuminates for 1.3 to 5 seconds if both detectors trip Relay Contacts: Normally closed, 0.1 A resistive/30 VDC; 18 Ω resistor in series with contacts Alarm Duration: 1.3 to 5 seconds (red LED lights and output relay contacts open) Tamper Contacts: Normally closed, 0.1A resistive / 30 VDC Trouble Output: Open-collector, 100 mA max., with 47 Ω resistor in series PHYSICAL CHARACTERISTICS Dimensions (H x W x D): 104 x 60 x 32 mm (2.4 x 4.1 x 1.3 in.) Weight: 80 g (2.8 oz) MOUNTING Direct: Surface or corner without bracket, up to 2.5 m (8 ft) Figure 2. PIR and MW Coverage Pattern ACCESSORIES (see Figure 4) BR-1: Surface mounted swivel bracket, adjustable 30° down and 45° left/45° right. BR-2: BR-1 with a corner adapter (kit) BR-3: BR-1 with a ceiling adapter (kit) ENVIRONMENTAL CONDITIONS Operating Temperature: –10°C to 50°C (14°F to 122°F) Storage Temperature: –20°C to 60°C (–4°F to 140°F) RFI Protection: Greater than 30 V/m (20 MHz to 1000 MHz) PATENTS U.S. Patents: 5,237,330 and 5,693,943; Des. 346,567 Compliance with Standards: EN 50131-1 Grade 2 Class II ATTENTION! Detection occurs only in areas in which the MW and PIR patterns overlap DE1821 3. INSTALLATION 3.1 General Guidelines A few important rules must be observed before selecting a mounting location: A. Microwave radiation passes through glass and non-metallic walls. Be sure to adjust the MW range so that it does not exceed the room limits, or else a rotating ceiling fan in the next room, or moving traffic along the outer side of the wall will cause the MW detector to alarm. B. Large reflecting objects (especially metals) in the coverage area can distort the microwave detector's coverage pattern. C. Install the unit so that the expected motion of an intruder is perpendicular to the zones of protection. D. Although the DUO 200 is extremely immune to false alarms, it is recommended to avoid installation in a room with very strong air turbulence or close to high-power electrical cables. E. If two DUO 200 units are installed in the same room or on opposite sides of a shared wall, they should not face each other and must be mounted at least 2 meters apart. F. For best performance at high ambient temperatures, it is advisable to aim the unit towards the coolest place in the protected area. G. Always mount the unit on a firm and stable surface at a height that renders optimum coverage of the protected area. Increasing the vertical angle at a certain height will increase the coverage range. H. Do not install the DUO 200 in places where one of the two detector circuits alarms constantly or intermittently, due to environmental interference. C. Select the mounting location in accordance with the guidelines in Section 3.1. D. Temporarily remove the PC board from the base. Take care not to lose the fastening screw. E. Use the base as a template for marking the drilling points. F. Drill mounting holes and insert masonry anchors if required. G. Pass the wires through the punched-out wiring inlet(s) and mount the base in place using two screws. H. Seal all openings in the base with RTV to prevent insects from entering the unit. I. Remount the PC board and secure it with its vertical adjustment screw. 3.3 Optional Swivel Brackets The BR-1 is a general purpose swivel bracket used for vertical and horizontal positioning of the DUO 200. With the BR-1, the unit can be tilted down from 0° to -30° and swivelled 45° left or right (see Fig. 4). The BR-2 is a swivel bracket kit for room corner installations, consisting of the BR-1 and a corner adapter. The BR-3 is a swivel bracket kit for ceiling installations. It consists of the BR-1 and a ceiling mounting adapter. 3.2 Direct Mounting The unit can be installed directly on the wall or in a room corner using the mounting knockouts. Optional swivel brackets permit greater flexibility when adjusting the coverage area (Section 3.8). A. Loosen and remove the screw at the bottom of the case (see Figure 1) and then take the cover off. B. Punch out the appropriate mounting and wiring knockouts in the base. Figure 4. Optional Swivel Brackets Caution! When a swivel bracket is used, the forward detection range may be reduced and the dead zone may be affected too. 3.4 Wiring Connect wires to the terminal block in the following order: Terminal: TAMP (tamper switch) Connect to: A normally closed 24-hour tamper zone of the control panel. Details: When the cover is removed, the tamper switch contacts open. Figure 3. Printed Circuit Board Layout Notes: 1. For wall surface mounting, use the two elongated knockouts at the middle of the base. For corner mounting, use two diagonally opposite knockouts at the angled sides of the base (see Figure 3). 2. To route the wiring to a lower conduit, use the two wiring knockouts at the bottom of the base (see Figure 3). To route the wires under the base towards the ceiling, use the wiring channel and its associated knockout. Terminal: NC (alarm relay) Connect to: Normally closed burglar protection zones of the control panel. Details: Upon alarm or power failure, the output relay's normally closed contacts open. Terminal: TRB (trouble output) Connect to: 24-hour trouble zone, parallel to an E.O.L. resistor (see Figure 5). Details: The TRB open collector output will be grounded upon detector malfunction, causing disturbance in the trouble zone of the associated alarm system. DE1821 Alternative: a buzzer or an interface relay may be connected across the TRB output and the 12 VDC (+) terminals. Terminals: 12VDC (+) and (–) Connect to: A power source within the range of 9 VDC to 16 VDC. Take care not to reverse the polarity. Details: It is advisable to connect the power source only after all other connections have been completed and rechecked. Disconnect the AC mains from the alarm control panel and verify that the voltage supplied to the detector is above 9 Volts with the backup battery as the only power source. IMPORTANT: To comply with CE safety requirements, connect to CE-approved control panels with current-limited DC output. Note: Use RTV to seal the base opening(s) to prevent insects from entering the detector. Table 2. Mode Selector Switch functions Switch SW-1 State Function OFF One motion event trips the PIR ON Two motion events trip the PIR SW-2 OFF Alarm walk test is disabled* ON Alarm walk test is enabled SW-3 OFF MW/PIR walk test is disabled* ON MW/PIR walk test is enabled SW-4 OFF Output relay opens upon alarm ON Output relay opens upon alarm and when trouble is detected. Default ON ON ON OFF *Setting SW-2 and SW-3 to OFF does not disable the trouble indication (flash / flash). 3.8 Adjusting the Vertical Angle The vertical adjustment scale for the PIR detector is located at the upper right edge of the PC board (refer to Figure 3). An adjustment screw in the middle of the board allows fast and easy adjustment from +2° to –12°. All DUO 200 units are pre-adjusted in the factory to –5°. Table 3 below provides recommended vertical adjustment angles for various combinations of mounting height and coverage range. Table 3. Vertical Angle Adjustment Figure 5. Terminal Block Wiring 3.5 The Power-up Process After connecting the (+) and (–) terminals to the power source, the DUO 200 starts a 60-second warm-up period, indicated by alternate flashing of the green and red LEDs. Caution! If the alternate flashing of the LEDs does not stop within 60 seconds, a failure has been detected by the self-test circuitry. 3.6 LED Indications The two LEDs (see Figure 1) are used to signal various alarm and trouble messages as shown in Table 1 below: Table 1. Interpreting the LED Indications State of LEDs GREEN Off On Flashes Off Flashes RED Off Off Off On Flashes Significance No detection MW walk-test detection PIR walk-test detection Alarm: MW + PIR detection - Trouble is being detected by the self test circuitry, or - Initial warm-up routine (stops 60 seconds after power up). Notes: 1. During walk testing, the first LED to respond is the green one. It illuminates steadily (MW detection) or flashes (PIR detection), depending on which one of the two detectors discovered the movement first. Upon subsequent discovery of the movement by the other detector, the green LED will go off and the red LED will illuminate (alarm). 2. If the green and red LEDs continue to flash beyond the warm-up period, a malfunction has been diagnosed. Replace the unit without delay. 3.7 Mode Selector The DIP switch mode selector is mounted on the unit’s PC board (see Figure 3). It controls four functions as demonstrated in Figure 6 and as detailed in Table 2. A. Use Table 3 to find the optimum angle for the coverage you require. For example, if a coverage range of 9 m (30 ft) is required and the detector is installed at a height of 1.8 m (6 ft) above the floor, set the vertical angle to -6°. B. Loosen the vertical adjustment screw, slide the PC board along the vertical slot until the pointer indicates the required angle on the scale. C. Tighten the adjustment screw firmly. Note: Since the adjustment screw also fastens the PC board to the base, vertical adjustment should be repeated if the PC board is replaced. 3.9 Setting the Motion Event Counter If you wish to set the PIR detector for maximum false alarm immunity, shift DIP switch No. 1 (SW-1) to ON. In this position, two consecutive motion events are required to trip the PIR detector. For faster catch performance, shift SW-1 to OFF. In this position, only one motion event is required to trip the PIR detector. 3.10 PIR Walk Test A. Rotate the MW RANGE control all the way towards MIN. B. Verify that DIP switch SW-3 is set to ON (the green walk-test LED is enabled). C. Mount the front cover in place. D. Walk into the detector's field of view at the expected far edge of the coverage area. The green LED should flash for up to 5 seconds each time your motion is detected. Note: If the green LED illuminates steadily, your motion has been detected by the MW detector. E. If PIR detection is not obtained at the far end of the coverage area, remove the front cover and re-adjust the vertical angle. Replace the cover and retest. 3.11 MW Walk Test Figure 6. DIP Switch Mode Selector DE1821 A. Remove the front cover. B. Verify that the MW range control is set to MIN and that DIP switch SW-3 is set to ON (green walk-test LED is enabled). C. Close the front cover. D. Start by moving into the coverage area at the far edge. The green LED should light steadily for up to 5 seconds each time your motion is detected. E. If your motion was not detected at the far edge of the coverage area, advance the MW RANGE control slightly toward MAX and try again until your motion is detected reliably at the far edge. Caution! The MW detection range must not exceed the far edge of the desired coverage area. F. Walk across the coverage area at various ranges and verify that your motion is consistently detected. Note: If PIR trips interfere with your test, disable the PIR by inserting a small piece of cardboard in front of the sensor. 3.12 Alarm Walk Test A. Set DIP switches SW-2 and SW-3 to ON (both LEDs are enabled). B. Install the front cover in place. C. Walk across the detector’s field of view in different directions, at various distances from the detector, and verify proper detection throughout the detector's coverage area (the red LED will illuminate for 1.3 to 5 seconds). D. When done, remove the cover and set DIP switches SW-2 and SW-3 to OFF to prevent unauthorized people from tracing the coverage pattern. E. Remount the cover and fasten it to the base using the small screw at the bottom. Attention! To assure proper function of the detector, the range and coverage area should be checked at least twice a year. Furthermore, it is recommended to perform a walk test at the far end of the coverage pattern to assure an alarm signal prior to each time the alarm system is armed. 4. SPECIAL NOTES 4.1 Product Limitations Although this detector is a highly reliable device, it does not guarantee complete protection against intrusion. Even the most sophisticated detectors can sometimes be defeated or may fail to warn because: A. The detector will not function if the DC power supplied to it is incorrect or improperly connected. B. Detection is confined to the area covered by the detection pattern as adjusted by the installer. C. A PIR detector does not provide full volumetric coverage of the protected area. It can only detect motion that disturbs the sensitive beam array spread within the protected space. D. Motion will not be detected by PIRs if it takes place behind closed doors, floors, walls, ceilings, glass partitions, windows and shutters. E. The detection ability of the PIR detector may be reduced by malicious masking or by spraying various materials on the lens or by mechanical tampering with the optical system. F. As the ambient temperature of the protected area approaches the range of 32°C - 40°C (90°F - 105°F), the PIR detector's performance can decrease. G. The protection pattern provided by the microwave detector may be altered by metal objects or foil-covered insulation. H. Even the most reliable electrical devices, including this detector, may go wrong because of an unexpected failure of a component part. The above list includes the most common reasons for failure to detect intrusion, but it is by no means comprehensive. It is therefore recommended that the detector and the entire alarm system be checked weekly, to ensure proper performance. An alarm system should not be regarded as a substitute for insurance. Home and property owners or renters should be prudent enough to continue insuring their lives and property, even though they are protected by an alarm system. 4.2 Compliance with Standards This device complies with FCC Rules Part 15. Operation is subject to two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference that may be received or that may cause undesired operation. WARNING! Changes or modifications to this unit not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment. This device complies with the essential requirements and provisions of Directive 1999/5/EC of the European Parliament and of the Council of 9 March 1999 on radio and telecommunications terminal equipment. WARRANTY Visonic Ltd. and/or its subsidiaries and its affiliates ("the Manufacturer") warrants its products hereinafter referred to as "the Product" or "Products" to be in conformance with its own plans and specifications and to be free of defects in materials and workmanship under normal use and service for a period of twelve months from the date of shipment by the Manufacturer. The Manufacturer's obligations shall be limited within the warranty period, at its option, to repair or replace the product or any part thereof. The Manufacturer shall not be responsible for dismantling and/or reinstallation charges. To exercise the warranty the product must be returned to the Manufacturer freight prepaid and insured. This warranty does not apply in the following cases: improper installation, misuse, failure to follow installation and operating instructions, alteration, abuse, accident or tampering, and repair by anyone other than the Manufacturer. This warranty is exclusive and expressly in lieu of all other warranties, obligations or liabilities, whether written, oral, express or implied, including any warranty of merchantability or fitness for a particular purpose, or otherwise. In no case shall the Manufacturer be liable to anyone for any consequential or incidental damages for breach of this warranty or any other warranties whatsoever, as aforesaid. This warranty shall not be modified, varied or extended, and the Manufacturer does not authorize any person to act on its behalf in the modification, variation or extension of this warranty. This warranty shall apply to the Product only. All products, accessories or attachments of others used in conjunction with the Product, including batteries, shall be covered solely by their own warranty, if any. The Manufacturer shall not be liable for any damage or loss whatsoever, whether directly, indirectly, incidentally, consequentially or otherwise, caused by the malfunction of the Product due to products, accessories, or attachments of others, including batteries, used in conjunction with the Products. The Manufacturer does not represent that its Product may not be compromised and/or circumvented, or that the Product will prevent any death, personal and/or bodily injury and/or damage to property resulting from burglary, robbery, fire or otherwise, or that the Product will in all cases provide adequate warning or protection. User understands that a properly installed and maintained alarm may only reduce the risk of events such as burglary, robbery, and fire without warning, but it is not insurance or a guarantee that such will not occur or that there will be no death, personal damage and/or damage to property as a result. The Manufacturer shall have no liability for any death, personal and/or bodily injury and/or damage to property or other loss whether direct, indirect, incidental, consequential or otherwise, based on a claim that the Product failed to function. However, if the Manufacturer is held liable, whether directly or indirectly, for any loss or damage arising under this limited warranty or otherwise, regardless of cause or origin, the Manufacturer's maximum liability shall not in any case exceed the purchase price of the Product, which shall be fixed as liquidated damages and not as a penalty, and shall be the complete and exclusive remedy against the Manufacturer. Warning: The user should follow the installation and operation instructions and among other things test the Product and the whole system at least once a week. For various reasons, including, but not limited to, changes in environmental conditions, electric or electronic disruptions and tampering, the Product may not perform as expected. The user is advised to take all necessary precautions for his/her safety and the protection of his/her property. 6/91 W.E.E.E. Product Recycling Declaration For information regarding the recycling of this product you must contact the company from which you orignially purchased it. If you are discarding this product and not returning it for repair then you must ensure that it is returned as identified by your supplier. This product is not to be thrown away with everyday waste. Directive 2002/96/EC Waste Electrical and Electronic Equipment. VISONIC LTD. (ISRAEL): P.O.B 22020 TEL-AVIV 61220 ISRAEL. PHONE: (972-3) 645-6789, FAX: (972-3) 645-6788 VISONIC INC. (U.S.A.): 65 WEST DUDLEY TOWN ROAD, BLOOMFIELD CT. 06002-1376. PHONE: (860) 243-0833, (800) 223-0020 FAX: (860) 242-8094 VISONIC LTD. (UK): 7 COPPERHOUSE COURT, CALDECOTTE, MILTON KEYNES. MK7 8NL. PHONE: (0870) 7300800 FAX: (0870) 7300801 INTERNET: www.visonic.com ©VISONIC LTD. 2008 DUO-200 0122 DE1821- (preparation for revision 6. , 4/08) DE1821
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.4 Linearized : No Page Count : 4 XMP Toolkit : XMP toolkit 2.9.1-13, framework 1.6 About : uuid:13c5229b-3164-4fcd-92b7-ab6834f642d9 Producer : Acrobat Distiller 6.0 (Windows) Create Date : 2008:04:27 09:05:37+03:00 Creator Tool : PScript5.dll Version 5.2.2 Modify Date : 2008:04:27 09:05:37+03:00 Document ID : uuid:72fb5448-1f5d-4c14-a809-ecd1926099f9 Format : application/pdf Title : Microsoft Word - DE1821- preparation for revision 6_w2002_.doc Creator : emceng7 Author : emceng7EXIF Metadata provided by EXIF.tools