YORK Furnace/Heater, Gas Manual L0611119

User Manual: YORK YORK Furnace/Heater, Gas Manual YORK Furnace/Heater, Gas Owner's Manual, YORK Furnace/Heater, Gas installation guides

Open the PDF directly: View PDF PDF.
Page Count: 12

DownloadYORK  Furnace/Heater, Gas Manual L0611119
Open PDF In BrowserView PDF
®
%

'_i
Iso

,;_ _
9001

Certified
Quality
Management
System

TABLE OF CONTENTS
CONTACT INFORMATION ................................
USER'S INFORMATION
...................................
SAFETY ..............................................
INSTRUCTIONS FOR EXAMINING THE FURNACE
INSTALLATION .........................................
HOW YOUR GAS FURNACE WORKS
......................
START-UP AND SHUTDOWN INSTRUCTIONS
...............

1
1
1

Read the Instructions Below Before Trying to Start the Furnace..
Operating Instructions: ..................................
To Turn Offthe Appliance: ...............................
FURNACE USER MAINTENANCE ..........................
Blower Care ..........................................
Air Filters ............................................
Removing Filters ......................................
Motor Lubrication ......................................
SERVICE AND MAINTENANCE MANUAL .....................
SAFETY SECTION ......................................
FURNACE MAINTENANCE SECTION .......................

3
3
3
4
4
4
4
5
6
5
5

CONTACT

2
3
3

SEQUENCE OF OPERATION
.............................
Continuous Blower .....................................

5
5

Intermittent Blower - Cooling .............................
Heating Cycle .........................................
Hot Surface Ignition System ..............................
FURNACE CLEANING SECTION ...........................

5
5
6
6

Burner Removal/Cleaning
...............................
Cleaning the Heat Exchanger
............................
Cleaning the Secondary Heat Exchanger
...................
Cleaning the Vent / Air Intake System ......................
TROUBLESHOOTING
...................................
FURNACE CONTROL DIAGNOSTICS
.......................
DIAGNOSTIC FAULT CODE STORAGE AND RETRIEVAL
REPLACEMENT PARTS LIST ..............................
REPLACEMENT PART CONTACT INFORMATION .............
WIRING DIAGRAM
......................................
LIMITED WARRANTY
....................................

......

6
6
6
6
6
6
7
8
10
11
12

INFORMATION

•

Go to website at www.york.com

•

Contact us by mail:

click on "contact", then click on "contact form" and follow the instructions.
York International
Consumer Relations
5006 York Drive
Norman, OK 73069

The

manufacturer

tions of this
ence.

recommends

manual

FIRE OR EXPLOSION
warnings
exactly could
erty damage.

and

keep

that
the

the

user

manual

read

for future

all secrefer-

SECTION

h USER'S

INFORMATION

SAFETY
1.

The furnace area must be kept clear and free of combustible
rials, gasoline and other flammable vapors and liquids.

2.

Insulating materials may be combustible. The furnace must be
kept free and clear of insulating materials. The furnace area must
be examined when installed in an attic or other insulated space or
when insulation is added to be sure that the insulation material has

HAZARD
- Failure
to follow safety
result in serious injury, death, or prop-

mate-

been kept away from the furnace.
-- Do not store
and liquids
ance.
--

WHAT

or use gasoline
in the vicinity

or other flammable
vapors
of this or any other
appli-

TO DO IF YOU SMELL

3.

The furnace needs air for combustion in order to operate properly
and safely. Do not block or obstruct air openings on the furnace,
air openings to the area where the furnace is installed, or spaces
around the furnace.

4.

Follow the instructions exactly as shown on the OPERATING
INSTRUCTION LABEL or the Start-up and Shutdown Instructions
on Page 3 of this manual when lighting the furnace or turning the
furnace off.

5.

Should the gas supply fail to shut off or if overheating occurs, shut
off the gas valve to the furnace before shutting off the electrical
supply.

6.

Do not use this furnace if any part has been under water. A flooddamaged furnace is extremely dangerous. Attempts to use the furnace can result in fire or explosion. A qualified service agency
should be contacted to inspect the furnace and replace alI gas
controls, control system parts, electrical parts that have been wet
or the furnace if deemed necessary.

GAS:

Do not try to light any appliance.
Do not touch any electrical switch; do not use any phone
(including
cell phone) in your building.
Leave

the building

immediately.

Immediately
call your gas supplier from a neighbor's
phone. Follow the gas supplier's
instructions.
If you cannot
ment.
--

reach

your gas supplier,

call the fire depart-

Installation
and service must be performed
by a qualified installer,
service
agency or the gas supplier.

167808-UUM-A-1205

167808-UUM-A-1205

INSTRUCTIONS

CONDENSATE

BLOWER
ACCESS-PANEL

THE

FURNACE

1.

Examine the heat exchanger, through a field installed access
panel located on the supply air plenum. Visually examine the exterior sections of the vent/combustion
air piping and the vent connectors to be sure that they are physically sound without holes or
excessive corrosion.

2.

Examine the vent pipe making sure it is firmly in place, that it
slopes slightly upward and is physically sound without holes and
all of the connections are secure.

3.

Examine the return-air duct connections to make sure they are
physically sound, sealed to the furnace casing, and the ducts terminate outside the space containing the furnace.

4.

Examine the furnace casing making sure the physical support is
sound without sagging, cracks or gaps. Examine the furnace base
making sure it is physically sound without cracks, gaps or sagging
and has a good seal.

5.

Examine the furnace casing for obvious signs of deterioration.

6.

Examine the burner flames to make sure they are in good adjustment. Refer to the pictorial sketch shown in Figure 2 as a comparison to the actual flame.

7.

Examine the furnace as outlined above in steps 1 - 6 before each
heating season. Use Figure 3 for visual reference.

RAIN
UTTER

--

INDUCER
PRESSURE
SWITCH
TUBING

INDUCER
MOTOR

PRESSURE
SWITCHES-_

CONDENSATE
DRAIN HOSE
_CONDENSATE
TRAP

GAS -VALVE

_LIMIT
GAS
REFERENCE
HOSE

_\
BURNER

SWITCH
BOX

FIGURE 1: Component Locations
7.

EXAMINING

It is the owner% responsibility to ensure that an annual inspection of the
entire heating portion of the unit is made by a qualified service agency.

CONTROL
BOARD-TRANSFORMER

FOR

INSTALLATION

COMBUSTION
AIR PIPE

NEVER . . .Store flammable materials of any kind near your furnace. Gasoline, solvents, and other volatile liquids should be
stored only in approved containers outside your home.
materials vaporize easily and are extremely dangerous.

These
MAIN

8.

NEVER...Store
cleaning materials near your furnace. Materials
such as bleaches, detergents, powdered cleansers, etc., can
cause corrosion of the heat exchangers.

9.

NEVER...
Use the area around your furnace as a storage area
for items which could block the normal flow of air. This flow of air is

BURNER

END OF
BURNER

MANIFOLD

\

\

_

I

I

_

BURNER

I

FLAME

_

L

YELLOW
_

required for ventilation of the various furnace components.

INNER

FLAME

CONES
(B_ue Flame)

FIRE OR EXPLOSION

COMBUSTION
-_- TRANSITION

HAZARD

AIR

(not shown)

This furnace is designed and approved for use with Natural Gas and (LP) Propane Gas ONLY. DO NOT BURN
ANY LIQUID FUEL OR SOLID FUEL IN THIS FURNACE.
Burning any unapproved fuel will result in damage to the
furnace heat exchanger, which could result in Fire, Personal Injury, and/or Property Damage.

FIGURE 2: Burner Flame Drawing

3 EXAMINE RETURN AIR
i_y

DUCT CONNECTION
_"

.
O

BLOWER DOOR

L-"
"

o
O
o

q

o

2 REMOVE
THIS PANEL
TO EXAMINE
VENT PIPE

[]

"©
4 EXAMINE
FURNACE
CASING

4 EXAMINE

6 REMOVE THIS
PANELTO
-EXAMINE THE
BURNER FLAMES

(_)

5 EXAMINE CASING
FOR DETERIORATION
O

FIGURE 3: Furnace Examination

2

©.

b.

1 PLACE A FIELD
INSTALLED ACCESS
BURNER DOOR1
//
PANEL LOCATED IN
THE DOWNFLOW
PLENUM TO EXAMINE
THE HEAT EXCHANGER

FURNACE
CASING

oO
5 EX/_MINECASING
FOR DETERIORATION

Checkpoints

Unitary

Products

Group

167808-UUM-A-1205

HOW

YOUR

GAS

FURNACE

WORKS

To Turn Off the Appliance:

Your furnace is a very easy appliance to take for granted. Season after
season, it sits there in your home, keeping you warm and comfortable.
For this reason, you may never have given much thought to the way
your furnace operates. In order to get the safest and most efficient operation from your furnace, you should understand how your furnace does
its job.
When you set your thermostat to provide more heat in your home, you
are starting the heating cycle of the furnace. First, the inducer motor
starts to purge the heat exchanger of any remaining gases. Next, the
hot surface igniter glows and after a warm-up period the gas valve
opens and ignition occurs. A short time later, the blower starts and distributes the warm air throughout the home. When the temperature setting on your thermostat is reached, the gas valve closes, the main
burners are turned off, and the blower continues to run until the remaining warm air in the system is distributed. When the blower stops, the
heating cycle has ended.
START-UP

AND

SHUTDOWN

Read the
Furnace

Instructions

Below

INSTRUCTIONS
Before

Trying

to Start

the

_WARNING
If you do not follow these instructions exactly, a fire or
explosion may result causing property damage, personal
injury, and/or loss of fife.
A.

B.

C.

D.

This appliance does not have a pilot. It is equipped with an ignition
device which automatically lights the burner. Do not try to light the
burner by hand.
BEFORE OPERATING; smell all around the appliance area for
gas. Be sure to smell next to the floor because some gas is
heavier than air and will settle on the floor.
Use only your hand to push the gas control switch to the "on" position. Never use tools. If the switch will not operate by hand, don't
try to repair it, call a qualified service technician.
Force or
attempted repair may result in a fire or explosion.
Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance
and to replace any part of the control system and any gas control,
which has been under water.

Operating

1.

Set the thermostat to lowest setting.

2.

Turn off all electric power to the appliance
formed.

3.

Remove burner access panel.

4.

Move gas control switch to the "OFF" position. See Figure 4.

5.

Replace burner access panel.

Should overheating occur, or the gas valve fail to shut off,
turn the external manual gas valve in the gas supply line to
the furnace to the "off" position and let the furnace cool off
before shutting off the electrical power supply. Refer to
Figures 5 & 6.

OUTLET
PRESSURE

[_L

PORT

_

1.

STOP! Read the safety information

2.

Set the thermostat to the lowest setting.

above.

3.
4.

Turn off all electric power to the appliance.
Remove burner door.

5.

Move gas control switch to the "OFF" position. Do not force. See
Figure 4.

6.

Wait five (5) minutes to clear out any gas. If you then smell gas,
STOP! Follow "B" in the safety information above. If you don't
smell gas, go to next step.

4

I

I"

I

1

BOSS
,NLET/
PRESSURE
PORT

EXTERNAL
MANUAL
SHUTOFF VALVE

TO GAS
SUPPLY

TO GAS
SUPPLY

GROUNDED
JOINT UNION
MAY BE INSTALLED
INSIDE OR OUTSIDE
UNIT.

FIGURE 5: Downflow Gas Piping
MANUAL
SHUT-OFF
VALVE
_DRIP
LEG
--GAS
-- GAS

8.

Replace burner door.

9.

Turn on all electric power to the appliance.

DRIP_UAL

10.

Set thermostat to the desired setting. Burner wilI light, which may
take 30-60 seconds.

LEG

11.

After three (3) trials for ignition, if the appliance will not operate follow the instructions, "TO TURN OFF THE APPLIANCE" and call
your service technician or gas supplier.

Group

REGULATOR
ADJUSTMENT

FIGURE 4: Gas Valve - White Rodgers

Move gas control switch to the "ON" position. Do not force. See
Figure 4.

Products

OUTLET
_N

ON/OFF SWITCH
(Shown in ON position)

7.

Unitary

NT PORT

WRENCH J _

DRIP_"
LEG

Instructions:

if service is to be per-

SHUT-OFF

BURNERS
VALVE

VALVE

FIGURE 6: Horizontal Gas Piping
NOTE: The spring-loaded safety cut-off switch, mounted on the blower
deck, behind the indoor fan access panel will automatically cut
off the electrical power supply to the furnace when the blower
panel is removed. As a safety precaution, all electrical power
and the gas supply to the furnace should be turned off before
servicing.

3

167808-UUM-A-1205
FURNACE

USER

MAINTENANCE

Removing

Filters

Some downflow furnaces have their filters located on the top of the furnace in an external filter rack. To check filters you should:
Before proceeding,
be sure the area is well ventilated. Turn
the thermostat OFF. If the blower is running, wait until it
stops automatically. Turn OFF the gas and electrical power
supplies to the furnace. Check all metal parts and surfaces
to be sure they have cooled to room temperature before
you begin.
Blower

Care

Even with good filters properly in place, blower wheels and motors will
become dust laden after long months of operation. The entire blower
assembly should be inspected annually. If the motor and wheel are
heavily coated with dust, they can be brushed and cleaned with a vacuum cleaner. If the blower cannot be properly cleaned without removing
it from the furnace, then this service must be performed by a qualified
service agency.
The blower can be serviced/removed
through the blower access panel
on the inside of the furnace. If there is a combustion air pipe installed
inside the furnace, it may have to be removed to access the blower
access panel. After the combustion air pipe is removed, it is easy to
remove the inside blower access panel by removing the screws of the
access panel. Blower is now ready to be serviced through the opening.
If the blower has to be removed through the inside blower access panel,
then the top and bottom angles will have to be removed to slide the
blower out of the furnace.

Follow the instructions to turn off the appliance

2.

Filters are installed in the return air plenum above the blower
assembly. An "A" frame assembly supports the filters. Lift the filter
slightly and remove for service.

3.

Follow the instructions
TER".

4.

Reverse the procedure to reinstall filters.

5.

Follow the operating instructions to place appliance

Externally

FIL-

in operation.

Air Filters

Some installations may have the air filter in a rack attached to the casing of the furnace or placed in the return air duct. You can gain access
to the filter by pulling on the door or unscrewing the retaining screw,
then slide the filter(s) out of its channel. Replace throw away filter(s)
with the same size new filter(s). Throw away filter(s) may be replaced
with cleanabIe filter(s) at this time. Cleanable filter(s) may be cleaned as
described in the manufacturer instructions or as described below and
then re-installed.
How to Clean your Filter
High-velocity filters may be cleaned with a vacuum cleaner or washed
with a garden hose. Be sure to shake off excess water and allow filter to
completely dry before re-installing the filter.
To replace the filter after cleaning you must do the following:

2.

Snap the door on or place the door in position and tighten the
retaining screws, if provided.

the clip-on weight on the

3.

Make sure the door is secure to the end of the filter rack.

indoor fan wheel when cleaning the wheel. This weight is
used to balance the wheel. Moving the weight will cause
the fan wheel to vibrate.

4.

For filter grilles, place the filter into the grilles, close the grille cover
and tighten the retaining screw.

Filters

weeks after that, especially if the indoor fan is running continuously.
When replacing the filter(s), refer to Table 1 to be sure you install the
right size filter for your furnace. Dirty filters greatly restrict the flow of air
and may cause damage to the moving parts of the furnace. If the filters

Every time the filters are changed the following items should be visually
inspected:
•
•
•
•

become clogged the heat exchangers and blower motor could overheat
resulting in a potentially dangerous situation.
Use the following procedure to determine the filter size.
1.
Measure the furnace width and use that measurement
mine the cabinet width.
•
•

A 14-1/2" wide cabinet is a _'A"cabinet.
A 17-1/2" wide cabinet is a _'B"cabinet.

•
•

A 21" wide cabinet is a _'C"cabinet.
A 24-1/2" wide cabinet is a _'D"cabinet.

Check combustion air and vent pipe for blockage or leakage.
Check all components to be sure they are in good condition and
that there are no obvious signs of deterioration.
Check the drain lines to make sure there are no cracks or leaks.
Check for dirt or lint on any surfaces or on components. Do not try
to clean any of the surfaces or components. Cleaning of the furnace and its components must be done by a qualified service professional.

If, during the inspection
conditions:

Never operate your furnace without a suitable air filter.

4

"HOW TO CLEAN YOUR FURNACE'S

Slide filter into place.

The filters should be checked every 3 months. On new construction,
check the filters every week for the first four weeks and every three

2.

Mounted

before servicing.

1.

Make sure you DO NOT move

Air

1.

to deter-

After you determine the cabinet size and what return configuration
you have, look up the recommended filter size from Table 1.

of your furnace, you find any of the following

•

Excessive amounts of dust and lint on components.

•
•

Damaged or deteriorated components or surfaces.
Leaks or blockage in the vent pipe passages.

• Water on any surface inside or outside of the furnace.
Do not operate the furnace, call a certified dealer / servicing contractor
to check and / or clean your furnace, or for more information if you have
questions about the operation of your furnace.
If all components appear to be in good operating condition, replace the
front panels. Turn ON the gas and electrical power supplies to the furnace, and set thermostat to the desired temperature.

Unitary

Products

Group

167808-UUM-A-1205

Motor Lubrication
The motors in these furnaces
require periodic oiling.

Intermittent
are permanently

lubricated,

and do not

TABLE 1: Fitter Sizes
Input/Output
BTU/H (kW)

Blower

- Cooling

Cooling/heating thermostats have a fan switch that has an ON and
AUTO position. In the AUTO position the thermostat circuit is completed
between terminals R and G when there is a call for cooling. The motor
will operate on the speed tap wire that is connected to the HI COOL terminal on the control board. The fan off setting is fixed at 60 seconds for
SEER enhancement.

CFM

Cabinet

Top Return Filter

(m3/min)

Size

in (cm)

40/37(1 ! .72/10.84)

1200(34)

A

(2) 14 x2O (36x 51)

Heating

60/55(17.57/16.10)

1200(34)

a

(2) 14 x20 (36x51)

80/75(23.42/2!

.96)

1200(34)

a

(2) 14 x20 (36x51)

80/75(23.42/2!

.96)

When the thermostat switch is set on HEAT and the fan is set on AUTO,
and there is a call for heat, a circuit is completed between terminals R
and W of the thermostat. When the proper amount of combustion air is
being provided, the pressure switch will close, the ignition control provides a 17-second warm-up period, the gas valve then opens, the gas
starts to flow, ignition occurs and the flame sensor begins its sensing
function. The blower motor will energize 30 seconds after the gas valve
opens, if a flame is detected. Normal furnace operation will continue
until the thermostat circuit between R and W is opened, which causes
the ignition system and gas valve to de-energize and the burner flames
to be extinguished. The vent motor will operate for 15 seconds and the
blower motor will operate for the amount of time set by the fan-off delay
jumper located on the control board. See Figure 7. The heating cycle is
complete, and ready for the start of the next heating cycle.

1600(45)

C

(2) 14 x 20 (36 x 51)

100/95(29.28/27.82)

1600(45)

C

(2) 14 x 20 (36 x 51)

100/95(29.28/27.82)

2000(57)

C

(2) 14 x 20 (36 x 51)

120/112(35.14/32.80)

2000(57)

U

(2) 14 x20 (36 x51)

SECTION
MANUAL
SAFETY

Ih SERVICE

AND

MAINTENANCE

SECTION

The following
furnace,

safety rules must be followed

when servicing

the

Cycle

RED

- LOW

YELLOW

ELECTRIC

SHOCK, FIRE OR EXPLOSION

SPEED

- MED

LOW

SPEED

HAZARD

Failure to follow safety warnings
exactly could result in
dangerous operation, serious injury, death or property
damage.
Improper servicing could result in dangerous
serious injury, and death or property damage.

operation,

•

Before servicing, disconnect
nace.

•

When servicing controls, label all wires prior to disconnecting. Reconnect wires correctly.

•

Verify proper operation after servicing.

FURNACE

MAINTENANCE

all electrical power to the fur-

SECTION

The furnace should be cleaned and adjusted by a certified dealer or
qualified service contractor once a year or before the start of every
heating season. The following items must be cleaned and serviced or
replaced if there are signs of deterioration.
1.

The vent terminal screen (if applicable).

2.

The furnace vent and combustion air intake passageways. Should
it be necessary to service the vent!air intake system, the manufacturer recommends this service be conducted by a qualified service
agency. The operation of this appliance requires the reassembty
and resealing of the vent/air intake system.

3.

The furnace burners, ignitor and flame sensor.

4.

The condensate collection and disposal system. If any disassembly of components containing flue or vent gases is required, a
qualified service agency must perform the service.

SEQUENCE

OF

OPERATION

The following describes the sequence of operation of the furnace. Refer
to Figure 1 for component location.
Continuous

Blower

Cooling/heating thermostats have a fan switch that has an ON and
AUTO position. In the ON position the thermostat circuit is completed
between terminals R and G.

Unitary

Products

Group

FAN OFF
-_ADJUSTMENT
JUMPER

0

_

FIGURE 7: Typical Heat/Cool Speed Tap Connections
If the flame is not detected within 7 seconds of the gas valve opening,
the gas valve is shut off and a retry operation begins. If the flame is lost
for 2 seconds during the 10-second stabilization period, the gas valve is
shut off and a retry operation begins. During a retry operation, the vent
motor starts a 15 second inter-purge and the ignitor warm-up time is
extended to 27 seconds. If the flame is established for more than 10
seconds after ignition during a retry, the control will clear the ignition
attempt (retry) counter. If three retries occur during a call for heat, the
furnace will shut down for one hour. If at the end of the one hour shut
down there is a call for heat, the furnace will initiate a normal start cycle.
If the problem has not been corrected the furnace will again lockout
after three retries.
A momentary loss of gas supply, flame blowout, or a faulty flame probe
circuit will result in a disruption in the flame and be sensed within 1 second. The gas valve will de-energize and the control will begin a recycle
operation. A normal ignition sequence will begin after a 15 second interpurge. If during the five recycles the gas supply does not return, or the
fault condition is not corrected the ignition control will lockout for 60 mintues.
During burner operation, a momentary loss of power for 50 milliseconds
or longer will de-energize the gas valve. When the power is restored,
the gas valve will remain de-energized and the ignition sequence will
immediately restart.

5

167808-UUM-A-1205
Hot Surface Ignition System

_WARNING

3.

Using a stiff wire brush, remove the loose scale or soot from each
tube.

4.

Vacuum the secondary heat exchanger.

5.

Finish the cleaning procedure
cleaning the Heat Exchanger.

HOT SURFACE IGNITION SYSTEM
Do not attempt to light this furnace by hand (with a
match or any other means). There may be a potential
shock hazard from the components of the hot surface
ignition system. The furnace can only be lit automatically
by its hot surface ignition system.
FURNACE

CLEANING

Cleaning

steps

9 - !1 under

System

Should it be necessary to service the vent / air intake system, the manufacturer recommends this service be conducted by a qualified service
agency.

SECTION

NOTE: The cleaning operations listed below must be performed only by
a qualified service agency.

The operation of this appliance requires the reassembly and resealing
of the vent / air intake system as specified in the "Combustion
Air and
Vent System" located in the Installation Manual.
TROUBLESHOOTI

NG

The following visual checks should be made before troubleshooting:

CAUTION
Label all wires prior to disconnection
when servicing
controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.
Burner

the Vent / Air Intake

by following

Removal/Cleaning

The main burners should be checked periodically for dirt accumulation.
If cleaning is required, follow this procedure:

1.

Check to see that the power to the furnace and the ignition control
module is ON.

2.

The manual shut-off valves in the gas Iine to the furnace must be
open.

3.

Make sure all wiring connections

4.

Review the sequence of operation. Start the system by setting the
thermostat above the room temperature. Observe the system's
response. Then use the troubleshooting section in this manual to
check the system's operation.

are secure.

1.

Turn off the electrical power to the unit.

2.

Turn off the gas supply at the external
loosen the ground union joint.

3.

Remove the upper access panel and remove the burner box cover.

4.

Disconnect wires from flame sensor, rollout switch and HSl igniter.
Remove igniter carefully, as it is easily broken.

Never bypass pressure switch to allow furnace operation. To do so will allow furnace to operate under potentially hazardous conditions.

5.

Remove the screws that hold the burner box assembly to the vest
panel and remove the assembly.

Do not try to repair controls.
with UPG Source I Parts.

6.

Remove burners from the burner assembly.

7.

Burners may be cleaned by rinsing in hot water.

FURNACE

8.

Reassemble

The furnace has built-in, self-diagnostic capability. If a system problem
occurs, a blinking LED shows a fault code. The LED can flash red,
green or amber to indicate various conditions. It is located behind a
clear view port in the blower compartment door.

Cleaning

manual shut-off valve and

the Heat Exchanger

1.

Turn off the electrical power to the unit.

2.

Turn off the gas supply at the external
loosen the ground union joint.

3.

Remove the upper access panel and remove the burner box cover.

4.

Disconnect wires from flame sensor, rollout switch and HSl igniter.
Remove igniter carefully, as it is easily broken.

5.

Remove the screws that hold the burner box assembly to the vest
panel and remove the assembly.

manual shut-off valve and

6.

Remove the vent pipe assembly, vent blower and condensate

7.

The heat exchanger

8.

With a long flexible wire brush, clean inside each tube at both the
top and bottom. The brush must pass around the rear heat
exchanger tubes. Then vacuum loose the scale and dirt from each
tube.

10.

Restore electrical power and gas supply to the furnace.

11.

Check furnace operation.

Cleaning

pan.

is now exposed.

Replace all components

the Secondary

in reverse order. Reconnect all wiring.

Heat Exchanger

1.

Follow steps 1 - 7 under cleaning the Heat Exchanger.

2.

Remove the vent piping from the vent blower housing. Disconnect
the drain lines from the vent blower housing and from the condensate drain pan. Remove the vent blower housing blower and the
condensate pan.

6

Replace defective

controls

Never adjust pressure switch to allow furnace operation.

the burners in the reverse order.

9.

AWARNING

CONTROL

DIAGNOSTICS

The control continuously monitors its own operation and the operation
of the system. If a failure occurs, the LED will indicate the failure code. If
the failure is internal to the control, the light will stay on continuously. In
this case, the entire control should be replaced, as the control is not
field repairable.
Flash sequence codes 1 through !0 are as follows: LED will turn "on"
for 1/4 second and "off' for 1/4 second. This pattern will be repeated the
number of times equal to the code. For example, six "on" flashes equals
a number 6 fault code. All flash code sequences are broken by a 2 second "off" period.
SLOW GREEN FLASH: Normal operation.
SLOW AMBER

FLASH: Normal operation with call for heat.

RAPID RED FLASH:
twinning wiring.

Twinning

error, incorrect

24V phasing.

Check

RAPID AMBER FLASH: Flame sense current is below 1.5 microamps.
Check and clean flame sensor. Check for proper gas flow.
1 RED FLASH: This indicates that flame was sensed when there was
not a call for heat. With this fault code the control will turn on both the
inducer motor and supply air blower. A gas valve that leaks through or
is slow closing would typically cause this fault.
2 RED FLASHES:
This indicates that the normally open pressure
switch contacts are stuck in the closed position. The control confirms
these contacts are open at the beginning of each heat cycle. This would
indicate a faulty pressure switch or miswiring.

Unitary

Products

Group

167808-UUM-A-1205

3 RED FLASHES: This indicates the normally open pressure switch
contact did not close after the inducer was energized. This could be
caused by a number of problems: faulty inducer, blocked vent pipe, broken pressure switch hose or faulty pressure switch.

STEADY ON RED: Control failure. Replace control board.
60-MINUTE

4 RED FLASHES: This indicates that a primary or auxiliary limit switch
has opened its normally closed contacts. With this fault code the control
will operate the supply air blower and inducer. This condition may be
caused by: dirty filter, improperly sized duct system, incorrect blower
speed setting, incorrect firing rate or faulty blower motor.

DIAGNOSTIC
RETRIEVAL

established. This no-light condition occurred 3 times (2 retries) during
the call for heat before locking out. Low gas pressure, faulty gas valve,
dirty or faulty flame sensor, faulty hot surface ignitor or burner problem
may cause this.

Gas flow with no call for heat. Check gas valve and

I

L ON

Ca[[ir_

FAULT

CODE

STORAGE

AND

If there are no error codes in memory, the LED will flash two
flashes. To clear the memory, push the LAST ERROR button and
for more than five seconds. The LED will flash three green flashes
the memory has been cleared, then will resume the normal slow
flash after a five-second pause.

4 AMBER FLASHES: Y present with no G call. Normally, both Y and G
are energized on a call for cooling. If a Y signal is present with no G signal, check to see that the wire from the G terminal on the board to the
wall thermostat has not broken or disconnected.

Thermostat

period.

To retrieve the error codes, push the LAST ERROR button. The LED on
the control will then flash the error codes that are in memory, starting
with the most recent. There will be a two-second pause between each
flash code. After the error codes have all been displayed, the LED wilI
resume the normal slow green flash after a five second pause. To
repeat the series of error codes, push the button again.

11 RED FLASHES: This indicates that a primary or auxiliary limit switch
has opened its normally-closed
contacts and has remained open for
more than five minutes. This condition is usually caused by a failed
blower motor or blower wheel. Cycle power (24 VAC) to the contro! to
reset the hard lockout condition after correcting the failure condition.

17

control

The control stores up to five separate error codes. If more than five
error codes have occurred since the last reset, only the five most recent
wilI be retained. The furnace control board has a button, labeled "LAST
ERROR" that is used to retrieve error codes. This function will only work
if there are no active thermostat signals. So any call for heating, cooling
or continuous fan must be terminated before attempting to retrieve error
codes.

9 RED FLASHES: Indicates reversed line voltage polarity or grounding
problem. Both heating and cooling operations will be affected. Check
polarity at furnace and branch. Check furnace grounding including the
transformer ground. Check that flame probe is not shorted to chassis.

:_

This

The control in this furnace is equipped with memory that will store up to
five error codes to allow a service technician to diagnose problems
more easily. This memory will be retained even is power to the furnace
is lost. This feature should only be used bv a aualified service technician.

8 RED FLASHES: This fault is indicated if the flame is lost 5 times (4
recycles) during the heating cycle. This could be caused by low gas
pressure, dirty or faulty flame sensor or faulty gas valve. The furnace
will Iock out for one hour and then restart.

02

LOCKOUT:

IGNITION CONTROL (P/N 03!-0!972-000)
Normal flame sense current is approximately
3.7 microamps DC (pa)
Low flame signal warning starts at 1.5 microamps.
Low flame signal control lockout point is
0.9 microamps DC (pa)

This fault code indicates that the flame could not be

(Seconds}

FROM

second and then enters a flame stabilization

6 RED FLASHES: This indicates that after the unit was operating, the
pressure switch opened 4 times during the call for heat. If the main
blower is in a "Delay on" mode it will complete it, and any subsequent
delay off period. The furnace wilI Iock out for one hour and then restart.

10 RED FLASHES:
gas valve wiring.

RESET

NOTE: If a flame is detected the control flashes the LED for !/8 of a

5 RED FLASHES: This fault is indicated if the normally closed contacts
in the rollout switch opens. The rollout control is manually reset. If it has
opened, check for proper combustion air, proper inducer operation, and
primary heat exchanger failure or burner problem. Be sure to reset the
switch after correcting the failure condition.

7 RED FLASHES:

AUTOMATIC

includes a "watchdog" type circuit that will reset from a lockout condition
after 60 minutes. Operational faults 6,7,8 will be reset. This provides
protection to an unoccupied structure if a temporary condition exists
causing a furnace malfunction. An example would be a low incoming
gas supply pressure preventing unit operation. When the gas pressure
is restored, at some point the "watchdog" would restart the unit and provide heat for the house.

for

Heat

_

Thermostat

green
hold it
when
green

Sat[stied

THERMOSTAT

INDUCER

IGNITOR

MAIN

VALVE

OFF:

I

iON
I

HUMIDIFER
OFF

I

ELECTRONIC
AIR

CLEANER
OFF

OFF

I

i
CIRCU
BLOWER

LATIN

I

G

_EF ........................................................................
gEE......

60, 9o,12o, 18oSEC _gEE
Se[ec_able

Fan

off

Delay

FIGURE 8: Furnace Control Event Schedule

Unitary

Products

Group

7

167808-UUM-A-1205
SECTION

II1: REPLACEMENT

PARTS

LIST
32
17

J

27

43

11

34
.......

26

44 _

56,57_

22
5

49
42

o

36

6

19j
\

30

65

4t

33

\79

\
10

28
9,37
45
14

8

23

Unitary

Products

Group

167808-UUM-A-1205

ITEM I
MOTOR

ITEM

DESCRIPTION

1
MOTOR,DIRECT DRIVE BLOWER
2
MOTOR, NDUCER ASS Y
ELECTRICAL
CAPACITOR,
CAPACITOR,

RUN (7.5MFD/370V)
RUN (10MFD/370V)

DESCRIPTION

41
42

PLUG, WINDOW, CLEAR - 1.5"
COMBUSTION AIR TRANSITION

43

TUBING,SILICONE

44
45

TUBING, SILICONE (Preformed)
TUBING,SILICONE (Gray, .188 ID, 1.25ft. Req'd)

(Gray,

.188 ID,2.83 ft. Req'd)

46

GASKET, COMBUSTION

BLOWER

4
5

SWITCH, LIMIT (INDUCER)
LIMIT, TEMPERATURE (Primary)

47

GASKET, CONDENSATE

PAN

48

GASKET,UPPER CONDENSATE PAN (2 Req'd)

6

LIMIT, FLAME ROLL-OUT

49

GASKET, GAS CONTROLS

7

CONTROL,

50

GASKET,

8*
9

FUSE
IGNITER

51

GASKET, COMBUSTION AIR TRANSITION

10
11

SENSOR, FLAME
SWITCH, PRESSURE

52
53

GASKET, MOUNTING BRKT (Burner Box)
COMBUSTION AIR INTAKE ASSEMBLY

12
13

SWITCH, DOOR
TRANSFORMER

54
55

VENT PIPE 2" X 15.25" LG.
RUBBER SLEEVE 2.5" X 4" LG.

56

GROMMET, MOTOR (3 Req'd)

57
58

FERRULE (3 Req'd)
COMBUSTION BLWR RESTRICTOR

FURNACE

MODULE

14
VALVE, GAS
AIR MOVING
15

CONDENSING

COIL

59

HOUSING, BLOWER

60

WASHER, FLAT FIBERGLASS (2

61

HANDLE, DOOR (2 Req'd)

62
63

CLAMP, HOSE (2 Req'd)
HARNESS, MAIN WIRING

64

MOUNT, ! PC. MOTOR

65
66
67

ORIFICE, BURNER (Natural #45)
TRAP, CONDENSATE
WIRING DIAGRAM

68

45 DEG STREET ELBOW 2"

SHIELD, PAN

69

DRAIN TUBE, CONDENSATE

TRAP

25
26

PAN, CONDENSATE
PANEL, LOWER ACCESS

70

DRAIN TUBE, COMBUSTION

BLOWER

71

DRAIN TUBE, CONDENSATE

PAN

27

PANEL, UPPER ACCESS

28

WRAPPER,

72
73

DRAIN TUBE, STRAIGHT 21" LG.
DRAIN TUBE, RAIN GUTTER

29

CHANNEL, TOE PLATE

74

DRAIN HOSE ASSEMBLY

30

COVER, GAS CONTROL

3!

PANEL, BOTTOM

75
76

LOCKNUT, CONDUIT (!/2")
ADAPTER, INSERT

32

PANEL, TOP

77

BUSHING, THREADED

33

SUPPORT, BURNER

78

DRAIN TUBE, VENT PIPE

34
35

WRAPPER, CABINET
BRACKET, FILTER

79

BAFFLE, BURNER BOX

36

PLATE, DIFFUSER

80
81

GROMMET, MANIFOLD
VENT PIPE ASSEMBLY

37

BRACKET, IGNITER

38

BRACKET, DOOR SWITCH

82
83

DRAIN TUBE, VENT PIPE
LOGO/BEZEL PLATE ASSEMBLY

39

BRACKET, DOOR

84

FILTER (20 X 14 X .75) (2 Req'd)

16
WHEEL, BLOWER
FABRICATED PARTS
17

PANEL, BLOWER COVER

18

BRACKET, CONDENSATE TRAP

19
20

BURNER, MAIN GAS
COIL, CONDENSING

21

SHELF, BLOWER

22

HEAT EXCHANGER

23

MANIFOLD,

24

ASS'Y

GAS

BURNER BOX

Req'd)

40
BOTTOM PANEL, BURNER BOX
MISCELLANEOUS

NOTE:

*Not Shown
Major components

Unitary

Products

Group

and suggested

stocking items are shown with shaded

item number

9

167808-UUM-A-1205
FIELD

MODEL
NO.
1NP0347
1CT0302
1CT0303
1PS0904
1PS0901
1PS0902
1PS0903
1NK0301
1HT0901
1CB0314
1CB0317
1CB0321
1CB0324
1TK0914
1TK0917
1TK0921
1TK0924
1VK0901
1BR0!14
1BR0214
1BR0!17
1BR0217
1BR012!
1BR0221
1BR0124
1BR0224
REPLACEMENT

INSTALLED

ACCESSORIES

- NON-ELECTRICAL

DESCRIPTION

USED

PROPANE (LP) CONVERSION
CONCENTRIC INTAKENENT
CONCENTRIC

INTAKE/VENT

WITH

ALL MODELS

KIT
2"

ALL MODELS EXCEPT 120 MBH

3"

ALL MODELS

SWITCH KIT

60/100/120

40
HIGH ALTITUDE

PRESSURE

(Does Not Include Orifices)

80/1200
80/1600

CONDENSATE

NEUTRALIZER

KIT

SIDEWALL VENT TERMINATION

ALL MODELS

KIT

ALL MODELS
14-1/2" CABINET

COMBUSTIBLE

17-1/2" CABINET

FLOOR BASE

21" CABINET
24 !/2" CABINET
14-1/2" CABINET
COIL TRANSITION

17-1/2" CABINET

KIT

21" CABINET
24 112" CABINET

3-WAY TRANSITION

KIT

All MODELS

BOTTOM RETURN FILTER KIT 1" FILTER
BOTTOM

14-1/2" CABINETS

RETURN FILTER KIT 1-4" FILTER

!4-1/2" CABINETS

BOTTOM RETURN FILTER KIT 1" FILTER
BOTTOM

17-1/2" CABINETS

RETURN FILTER KIT 1-4" FILTER

!7-1/2" CABINETS

BOTTOM RETURN FILTER KIT 1" FILTER
BOTTOM

21" CABINETS

RETURN FILTER KIT 1-4" FILTER

21" CABINETS

BOTTOM RETURN FILTER KIT 1" FILTER
BOTTOM

24-1/2" CABINETS

RETURN FILTER KIT 1-4" FILTER

24-1/2" CABINETS

PART CONTACT INFORMATION

This is a generic parts list. To request a complete parts list, refer to the contact information
• Visit our website at www.sourcelparts.com

below:

for the following information:

1. Search for a part or browse the catalog.
2. Find a dealer or distributor.
3. Customer Service contact information.
a. Click on the "Brand Links" button
b. Click on the "Customer Service" button
• You can contact us by mail. Just send a written request to:
York International
Consumer Relations
5006 York Drive
Norman, OK 73069

10

Unitary

Products

Group

167808-UUM-A-1205

SECTION

IV: WIRING

DIAGRAM

i
z_,
w

_-

B

8

W

<
w

8_
8
c_

FIGURE 9: Wiring Diagram

Unitary

Products

Group

11

L imited Warranty
UPG warrants

this product

to be free from

defects

in factory

workmanship

and material

under normal

use and service

and will,

at its option,

This warranty

UPG warrants the primary heat exchangers
its option, repair or furnish a replacement

workmanship
and material under normal use and service and will at
that meets the intended fit, use and function of the original heat

in the product to be free from defects in factory
heat exchanger,
either new or reconditioned,

covers only the equipment

repair or replace

any parts that prove to have such defects according to the terms outlined on this warranty.
Model Number and Serial Number listed on the Warranty Registration
Card.

described

by the Product

exchanger for any heat exchanger furnished by UPG which proves to have such defects within the duration of warranty coverage. Alternatively,
U PG may, at its
option, extend a replacement
allowance
to be applied toward the purchase
of a new furnace or packaged unit marketed by UPG. The exact amount of the
allowance will be determined at the discretion
of UPG, based upon current market conditions,
but in no case shall this allowance
exceed thirty (30) percent of
the original consumer purchase
price of the furnace, excluding such items as ductwork, wiring, piping and installation costs. UPG shall have no responsibility
hereunder for installation,
shipping, handling or other charges except as specifically provided herein.
For your benefit and protection,
return the Warranty Registration
Card to UPG promptly after installation.
contact
UPG.

you, should

it become

This warranty extends
UPG recommendations

necessary.

In the absence

only to the original
and specifications,

original installation.
The warranty
side of this warranty

of a recorded

Registration

Card,

This wil! initiate

the warranty

parts provided

TYPE

hereunder

Residential

shall not extend beyond

GY9 / GM9

recommends

regular

periodic

preventative

maintenance

the warranty

applies

only to products

This warranty

does not cover any:

from

installed

in the United

period stated

on the reverse

PARTS

10

5

20

10

5

on this equipment.

to
of

Applications

The person

most familiar

with the equipment

a UPG dealer. The UPG dealer can ensure your maintenance
program meets the conditions of the "UPG Warranty",
maximize
and service your unit within the mandated guidelines with regard to unlawful discharge of refrigerants
into the atmosphere.
This warranty

and allow us to

Lifetime

GF9
UPG strongly

period

upon product shipment

HEAT EXCHANGER
Applications
Non-Residential

Original Owner
90%

the warranty

period wil! begin

consumer
purchaser and is non-transferable.
For this warranty to apply, the product must be installed according
and in accordance
with all local, state, and national codes; and the product must not be removed from its place

period for repair or replacement

FURNACE

Warranty

in your HVAC system is

the efficiency

of the equipment,

States and Canada.

EXCLUSIONS
1.
2.

Shipping,
Damages

labor or material charges.
resulting from transportation,

3.

Damages
resulting from accident,
serve to void this warranty).

4.
5.

Damages
Damages

6.
7.

Cleaning or replacement
of filters.
Damages resulting from failure to properly

8.

Damages resulting from: (I) freezing of condenser water or condensate;
or restriction of the water circuit by foreign material or like causes.

9.

Damages

10.
1I.

Damages resulting from use of components
Increase in fuel or electric cost.

resulting
resulting

resulting

THIS WARRANTY
ITY AND FITNESS

from
from

installation,

or servicing.

abuse, fire, flood,

alteration,

use of the product in a corrosive atmosphere.
inadequacy
or interruption of electrical service

from

operation

and regularly

with inadequate

SOME

STATES

DO NOT ALLOW

SOME

STATES

ALLOW

WARRANTY.
WARRANTY

clean air and/or water

supply

of air or water.
not approved

THE DISCLAIMER

ONLY A PARTIAL

by UPG (vent dampers,

WARRANTY,

ON IMPLIED

IN SUCH STATES, THE DURATION
ON THE FACE HEREOF.

INCLUDING

TO LIMIT THE

OF IMPLIED

conditions,

the product

blown fuses,

or other

serial

number

will

like damages.

water supply;

(Ill) use of corrosive

water;

(IV) fouling

etc.).

SO THAT THE ABOVE

WARRANTIES

or removing

and evaporator.

or interrupted

OR IMPLIED,

defacing

voltage

side of condenser

(ll) inadequate

EXPRESSED

OF IMPLIED

LIMITATION

altering,

or fuel supply, improper

or accessories

IS IN LIEU OF ALL OTHER WARRANTIES,
FOR A PARTICULAR
PURPOSE.

TION OF THE EXPRESS
TION OF THE EXPRESS

or acts of God (tampering,

THE IMPLIED

DISCLAIMER

DURATION

WARRANTIES

WARRANTIES

MAY NOT APPLY

OF IMPLIED

IS HEREBY

OF MERCHANTABIL-

TO YOU.

WARRANTIES

EXPRESSLY

LIMITED

TO THE DURATO THE DURA-

IN NO EVENT, WHETHER
AS A RESULT OF BREACH OF WARRANTY
OR CONTRACT,
TORT (INCLUDING
NEGLIGENCE)
STRICT LIABILITY OR OTHERWISE, SHALL UPG BE LIABLE FOR SPECIAL, INCIDENTAL,
OR CONSEQUENTIAL
DAMAGES,
INCLUDING
BUT NOT LIMITED TO LOSS OF USE OF
THE EQUIPMENT
OR ASSOCIATED
TRICITY. THE ABOVE LIMITATIONS
CONSEQUENTIAL

DAMAGES

EQUIPMENT,
LOST REVENUES
OR PROFITS, COST OF SUBSTITUTE
EQUIPMENT
SHALL INURE TO THE BENEFIT OF UPG'S SUPPLIERS
AND SUBCONTRACTORS.

SHALL

NOT APPLY

TO INJURIES

TO PERSONS

IN THE CASE

OF CONSUMER

SOME STATES DO NOT ALLOW THE EXCLUSION
OR LIMITATION
OF LIABILITY FOR CONSEQUENTIAL
LIABILITY IN TORT, SO THAT THE ABOVE EXCLUSIONS
AND LIMITATIONS
MAY NOT APPLY TO YOU.
UPG DOES NOT ASSUME,
THIS WARRANTY
GIVES
For Owner's Information:

OR AUTHORIZE
YOU SPECIFIC

PRODUCT MODEL. NO.
UNIT SERIAL NO.

ANY OTHER
LEGAL

RIGHTS.

PERSON

TO ASSUME

YOU MAY ALSO

INSTALLATION
INSTALLING

FOR UPG, ANY OTHER

HAVE OTHER

GOODS.

OR INCIDENTAL

LIABILITY

WHICH

DAMAGES,

OR FOR STRICT

FOR THE SALE OF THIS

VARY FROM

PRODUCT.

STATE TO STATE.

DATE
DEALER

Subject to change without notice. Printed in U.S.A.
Copyright t-: by Unitary Products Group 2005. All rights reserved.
Unitary
Products
Group

RIGHTS

OR COST OF FUEL OR ELECTHE ABOVE LIMITATION
ON

167808-UUM-A-!205
Supersedes: 127236-UUM-A-0605
5005
York
Drive

Norman
OK
73069



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.2
Linearized                      : No
Page Count                      : 12
Page Layout                     : SinglePage
Page Mode                       : UseNone
Producer                        : Goby Monitor Application version 3, 2, 1, 4
Create Date                     : Thu Apr 05 07:18:59 2007
Author                          : 
Title                           : 
Subject                         : 
EXIF Metadata provided by EXIF.tools

Navigation menu