DESCRIPTION
These Category IV, highly efficient, compact, condensing
type furnaces are designed for residential and commercial
installations in a basement, closet, alcove, recreation room or
garage where the ambient temperature is above 32°F, or
higher. They may be either side wall or thru-roof vented using
approved plastic type combustion air and vent piping. All
units are factory assembled, wired and tested to assure
dependable and economical installation and operation.

TECHNICAL GUIDE

WARRANTY

AFFINITY
MODELS: PT9

Lifetime limited warranty on both heat exchangers to the original purchaser; a 20-year limited warranty from original installation date to subsequent purchaser.

GAS-FIRED
CONDENSING / HIGH EFFICIENCY
DOWNFLOW/HORIZONTAL
TWO STAGE FURNACES

10-year warranty on commercial applications.

NATURAL GAS
60 - 120 MBH INPUT

EFFICIENCY
RATING
CERTIFIED

ISO 9001
Certified Quality
Management System

Due to continuous product improvement,
specifications are subject to change without notice.
Visit us on the web at www.york.com for the most
up-to-date technical information.
Additional rating information can be found at
www.gamanet.org.

5-year limited parts warranty.

FEATURES
• Two stage heating operation includes:
- Two stage gas valve
- Two stage inducer operation
• Provides increased comfort level & very quiet unit operation.
• Adjustable delay timer allows two stage operation with single stage thermostat.
• Compact, easy to install, ideal height 40" cabinet.
• Blower-off delay for cooling SEER improvement.
• Easy to connect power/control wiring.
• Built-in, high level self diagnostics with fault code display.
• Low unit amp requirement for easy replacement application.
• Integrated control module for reliable, economical operation.
• May be installed as either two-pipe (sealed combustion) or
single pipe vent (using indoor combustion air).
• Top intake & vent connection allows installation in narrow
locations.
• Electronic Hot Surface Ignition saves fuel cost with
increased dependability and reliability.
• Induced combustion system with inshot main burners for
quiet, efficient operation.
• No special vent termination kit required.
• 100% shut off main gas valve for extra safety.
• PSC - four speed, direct drive motor with large, quiet
blower.
• 24V, 40 VA control transformer and blower relay supplied
for add-on cooling.
• Hi-tech tubular aluminized steel primary heat exchanger.
• Secondary (condensing) heat exchanger of 29-4C highgrade stainless steel.
• Timed on, adjustable off blower capability for maximum
comfort.
• Independent door removal for greater durabilty and ease
of access.
• Easy access from front of unit for cleaning, maintenance or
service.
• Protection from intake, exhaust or condensate blockage.
• Insulated blower compartment for quiet operation.
• 3-way transition facilitates fresh air piping.

FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

246782-YTG-B-0407
22-3/4
A

7/8

T-STAT WIRING 7/8” K.O.

7/8

T-STAT WIRING 7/8” K.O.

HORIZONTAL CONDENSATE
DRAIN OPENING 1-3/4”

13-7/8

HORIZONTAL CONDENSATE
DRAIN OPENING 1-3/4”

40

HORIZONTAL CONDENSATE
DRAIN OPENING 2”
JUNCTION BOX
HOLE 7/8”

22-3/4
GAS PIPE ENTRY 1-1/2”

HORIZONTAL
CONDENSATE
DRAIN OPENING 1-3/4”

29

29

CONDENSATE DRAIN
HOLE 7/8”

JUNCTION BOX
HOLE 7/8”

22-3/4

21-5/8

21-1/4
18-1/2

18-1/2
11-3/4
7-1/2

SIDE PIPING HOLE 3-3/8”

GAS PIPE
ENTRY 1-1/2”

9-1/8
8-1/2

CONDENSATE DRAIN
HOLE 7/8”

2-1/4
22-1/4
25-3/8
26-1/2
27-1/8
30-1/8

FRONT

23-11/16

23-5/8
1-1/4

19-1/4

LEFT SIDE

RIGHT SIDE

5/8

1-1/4
E

5/8

D
B

C
20
2-1/4
23-1/4
BOTTOM IMAGE
SUPPLY END

TOP IMAGE
RETURN END

CABINET AND DUCT DIMENSIONS
CABINET DIMENSION

Models

CFM

CABINET
SIZE

A (IN.)

B (IN.)

C (IN.)

D (IN.)

E (IN.)

PT9B12N060DH11

1200

B

17-1/2

16-1/4

15

1-3/4

2-3/8

PT9B12N080DH11

1200

B

17-1/2

16-1/4

15

1-3/4

2-3/8

PT9C16N080DH11

1600

C

21

19-3/4

18-1/2

2-1/8

2-3/4

PT9C20N100DH11

2000

C

21

19-3/4

18-1/2

2-1/8

2-3/4

PT9D20N120DH11

2000

D

24-1/2

23-1/4

22

2-1/2

3

ELECTRICAL AND PERFORMANCE DATA
Models

Input
(High/Low)

Output
(High/Low)

MBH

MBH

PT9B12N060DH11

60 / 39

56 / 36

Nominal
Airflow

Air Temp.
Rise

Cabinet
Width

Total Unit

CFM

In.

Amps

%

°F

1200

17-1/2

9

92

35 - 65
35 - 65

AFUE

PT9B12N080DH11

80 / 52

75 / 49

1200

17-1/2

9

92

PT9C16N080DH11

80 / 52

75 / 49

1600

21

12

92

35 - 65

PT9C20N100DH11

100 / 65

93 / 61

2000

21

14

92

35 - 65

PT9D20N120DH11

120 / 78

112 / 74

2000

24-1/2

14

92

35 - 65

Models

Input
(High/Low)

Max. Outlet
Air Temp.

Blower

Blower
Size

°F

HP

Amps

In.

Min. Wire Size
(awg) @ 75 ft.
One Way

Operating
Weight

MBH

Max.
Over-current
Protect

PT9B12N060DH11

60 / 39

165

1/2

7.0

11 x 8

20

14

136

PT9B12N080DH11

80 / 52

165

1/2

7.0

11 x 8

20

14

143

PT9C16N080DH11

80 / 52

165

3/4

10.2

11 x 10

20

14

159

PT9C20N100DH11

100 / 65

165

1

12.7

11 x 11

20

12

164

PT9D20N120DH11

120 / 78

165

1

12.7

11 x 11

20

12

182

Lbs.

Annual Fuel Utilization Efficiency (AFUE) numbers are determined in accordance with DOE Test procedures.
Wire size and over current protection must comply with the National Electrical Code (NFPA-70-latest edition) and all local codes.
The furnace shall be installed so that the electrical components are protected from water.
* Wire size and overcurrent protection must comply with the National Electric Code.

NOTES:
1. For altitudes above 2000 ft. reduce capacity 4% for each 1000 ft. above sea level.
2. Wire size based on copper conductors, 60°C, 3% voltage drop.
3. Continuous return air temperature must not be below 55°F.
4. All filters must be high velocity cleanable type.

2

Unitary Products Group

246782-YTG-B-0407
BLOWER PERFORMANCE CFM
AIRFLOW WITH TOP RETURN - WITHOUT FILTERS
EXTERNAL STATIC PRESSURE, INCHES W.C.
Speed
Tap

0.1
CFM

CFM

CFM

High

1687

1652

1631

Medium High

1193

1183

1173

Medium Low

933

933

921

Models

PT9B12N060DH11

PT9B12N080DH11

PT9C16N080DH11

PT9C20N100DH11

PT9D20N120DH11

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

CFM

CFM

CFM

CFM

1595

1557

1511

1456

CFM

CFM

CFM

1382

1313

1162

1142

1115

1076

1036

982

1211
950

911

902

872

825

793

771

712

Low

752

745

731

718

698

652

602

580

536

496

High

1686

1658

1623

1572

1534

1465

1391

1305

1202

1091

Medium High

1257

1223

1218

1203

1177

1142

1094

1026

939

874

Medium Low

977

982

976

955

934

899

843

791

738

686

Low

775

777

757

733

698

663

627

584

549

490

High

2071

2026

1981

1935

1864

1796

1713

1625

1532

1401

Medium High

1583

1590

1569

1554

1532

1502

1457

1409

1327

1221

Medium Low

1256

1275

1275

1288

1275

1265

1232

1187

1126

1023

Low

937

939

936

945

942

936

912

874

810

726

High

2404

2320

2225

2138

2034

1924

1816

1692

1559

1422

Medium High

2018

1955

1883

1815

1750

1670

1586

1497

1394

1246

Medium Low

1626

1581

1531

1488

1418

1363

1291

1225

1123

964

Low

1336

1291

1249

1205

1155

1091

1018

951

884

759

High

2520

2432

2353

2251

2152

2042

1947

1815

1701

1525

Medium High

2018

1979

1945

1911

1863

1779

1705

1599

1493

1353

Medium Low

1586

1545

1501

1457

1407

1351

1287

1216

1081

926

Low

1321

1266

1213

1163

1111

1071

987

864

763

700

NOTES:
1. Airflow expressed in standard cubic feet per minute.
2. Motor voltage at 115 V.

Unitary Products Group

3

246782-YTG-B-0407

FILTER PERFORMANCE
The airflow capacity data published in the “Blower Performance” table listed above represents blower performance
WITHOUT filters. To determine the approximate blower performance of the system, apply the filter drop value for the filter being used or select an appropriate value from the “Filter
Performance” table shown.
NOTE: The filter pressure drop values in the “Filter Performance” table shown are typical values for the type of filter
listed and should only be used as a guideline. Actual pressure drop ratings for each filter type vary between filter manufacturer.
RECOMMENDED FILTER SIZES
CFM

Cabinet
Size

Top Return
Filter in

60

1200

B

(2) 14 x 20

80

1200

B

(2) 14 x 20

80

1600

C

(2) 14 x 20

100

2000

C

(2) 14 x 20

120

2000

D

(2) 14 x 20

Input
BTU/H

APPLYING FILTER PRESSURE DROP TO
DETERMINE SYSTEM AIRFLOW
To determine the approximate airflow of the unit with a filter in
place, follow the steps below:
Select the filter type.

2.

Determine the External System Static Pressure (ESP)
without the filter.

Select a filter pressure drop from the table based upon
the number of return air openings or return air opening
size and add to the ESP from Step 3 to determine the
total system static.

4.

If total system static matches a ESP value in the airflow
table (i.e. 0.20, 0.60, etc,) the system airflow corresponds to the intersection of the ESP column and Model/
Blower Speed row.

5.

If the total system static falls between ESP values in the
table (i.e. 0.58, 0.75, etc.), the static pressure may be
rounded to the nearest value in the table determining the
airflow using Step 5 or calculate the airflow by using the
following example.

Example: For a 120,000 Btuh furnace operating on high
speed blower, it is found that total system static is 0.58" w.c.
To determine the system airflow, complete the following
steps:
1. Obtain the airflow values at 0.50" & 0.60" ESP.
Airflow @ 0.50": 2152CFM
Airflow @ 0.60": 2042 CFM
2. Subtract the airflow @ 0.50" from the airflow @ 0.60" to
obtain airflow difference.
2042 - 2152 = -110 CFM
Subtract the total system static from 0.50" and divide this
difference by the difference in ESP values in the table, 0.60" 0.50", to obtain a percentage.
(0.58 - 0.50) / (0.60 - 0.50) = 0.8
3. Multiply percentage by airflow difference to obtain airflow
reduction.
(0.8) x (-110) = -88
4. Subtract airflow reduction value to airflow @ 0.50" to
obtain actual airflow @ 0.58" ESP.
2152 - 88 = 2064

NOTES:
1. Air velocity through throwaway type filters may not exceed 300
feet per minute. All velocities over this require the use of high
velocity filters.

1.

3.

FILTER PERFORMANCE - PRESSURE DROP INCHES W.C.
Filter Type

Airflow Range

Minimum
Opening Size

Disposable

Washable Fibers

Pleated

CFM

in2

In W.C.

In W.C.

In W.C.

0 - 750

230

0.01

0.01

0.15

751 - 1000

330

0.05

0.05

0.20

1001 - 1250

330

0.10

0.10

0.20

1251 - 1500

330

0.10

0.10

0.25

1501 - 1750

380

0.15

0.14

0.30

1751 - 2000

380

0.19

0.18

0.30

2001 & Above

463

0.19

0.18

0.30

UNIT CLEARANCES TO COMBUSTIBLES
Top

Front

Rear

Left Side

Right Side

Flue

Floor/Bottom

In.

In.

In.

In.

In.

In.

In.

Downflow

1

3

0

0

0

0

Horizontal

0

3

0

1

1

0

1*
0

Application

*

4

Closet

Alcove

Attic

Line
Contact

Yes

Yes

Yes

NA

Yes

Yes

Yes

Yes2

Combustible floor base or air conditioning coil required for use on combustible floor.

Unitary Products Group

Unitary Products Group
Thermostat Installer Setup
Number 0170 - System Type must be set to 8 - 2 Heat/2 Cool
Multistage Conventional

Thermostat Installer Setup
Number 1 - System Type must be set to 6 2 Heat/2 Cool Conventional

Thermostat Installer Setup
Number 15 - Compressor
Protection - must be set to 5

Connection of the "C" Termainal,
24-Volt Common, is optional
when used with batteries

Connection of the "C" Termainal,
24-Volt Common, is optional
when used with batteries

Step 1 of Thermostat User
Configuration Menu must be
set to MS 2

Connection of the "C"
Termainal, 24-Volt Common,
is optional when used with
batteries

G
Fan

G
Fan

Connection of the "C"
Termainal, 24-Volt Common,
is optional when used with
batteries

W2
Second Stage Heat

W2
Second Stage Heat
G
Fan

E/W1
First Stage Heat

E/W1
First Stage Heat

G
Fan

RC
24-Volt Hot (Cool XFMR)

RC
24-Volt Hot (Cool XFMR)

R
24-Volt Hot

W2
Second Stage Heat

R
24-Volt Hot

R
24-Volt Hot (Heat XFMR)

R
24-Volt Hot (Heat XFMR)

Y2
Second Stage Cool

W2
Second Stage Heat

Y2
Second Stage Cool

Y2
Second Stage Cool

Y2
Second Stage Cool

Y1
First Stage Cool

E/W1
First Stage Heat

Y
First Stage Cool

Y
First Stage Cool

Y
First Stage Cool

C
24-Volt Common

W
First Stage Heat

C
24-Volt Common

C
24-Volt Common

Step 16 of Thermostat User
Configuration Menu must be set
to ON to use Comfort Alert
Features

Step 1 of Thermostat User
Configuration Menu must be set
to MLTI STG

HM
Humidistat

L
Malfunction Light

G
Fan

W2
Second Stage Heat

E/W1
First Stage Heat

R
24-Volt Hot

Y2
Second Stage Cool

Y1
First Stage Cool

C
24-Volt Common

*PP32U72124

*PP32U71124

*DP22U70124

C
24-Volt Common

THERMOSTAT

THERMOSTAT

*PP32U70124

*DN22U00124

*DN22C00124

THERMOSTAT

THERMOSTAT

THERMOSTAT

AC9 2 Stage Scroll A/C w/2 Stage Furnace, 2 Stage Cooling Ready- PT8/9; (F,L)*8/9T, (G,L)*8/9T, XYG8S-*, XYF8S-*, XYG9S-*, XYF9S-*

G
Fan

W2
Second Stage Heat

W/W1
Single/First Stage Heat

Y1
First Stage Cool
Y/Y2
Single/Second Stage
Cool
R
24-Volt Hot

C
24-Volt Common

2 STAGE PSC
FURNACE CONTROL

24V HUMIDIFIER
(Optional)

Comfort Alert
Interface

R
24-Volt Hot

Y2
Second Stage Cool

Y1
First Stage Cool

C
24-Volt Common

TWO STAGE
AIR CONDITIONING

For additional connection diagrams for all UPG equipment refer to “Low Voltage System Wiring” document available online at www.upgnet.com
in the Product Catalog Section.

246782-YTG-B-0407

Thermostat Chart - AC

5

HP23

6

Thermostat Installer Setup Number 0210 External Fossil Fuel Kit - must be set to 0 External Fossil Fuel Kit is Controlling
Heat Pump Backup Heat

Thermostat Installer Setup Number 0200
- Backup Heat Source - must be set to 1 - Heat
Pump Backup Heat Source is Fossil Fuel

Step 1 of Thermostat User
Configuration Menu must be
set to Heat Pump 2

W2
Second Stage Auxiliary Heat

Thermostat Installer Setup Number 0190 Reversing Valve (O/B) Operation - must be set to 0
- O/B Terminal Energized in Cooling

E/W1
First Stage Auxiliary Heat

AUX
Auxiliary Heat

Selection of GAS/ELEC switch on
thermostat not necessary

W2
Second Stage Auxiliary Heat

Y2
Second Stage Heat/Cool

Y2
Second Stage Heat/Cool

Thermostat Installer Setup Number 0170
- System Type - must be set to
12 - 3 Heat/2 Cool Heat Pump

E/W1
First Stage Auxiliary Heat

L
Malfunction Light

L
Malfunction Light

Step 1 of Thermostat User Configuration
Menu must be set to Heat Pump 2

HM
Humidistat

Y2
Second Stage Heat/Cool

L
Malfunction Light

O
Reversing Valve–Energized in Cool

O
Reversing Valve–Energized in Cool

O/B
Reversing Valve

G
Fan

G
Fan

DHM
Dehumidistat
G
Fan

E
Emergency Heat

R
24-Volt Hot

Y1
First Stage Heat/Cool

Y1
First Stage Cool

C
24-Volt Common

Set W2 Delay on furnace to OFF

24V HUMIDIFIER
(Optional)

Bonnet Sensor
(Optional)

G
Fan

W2
Second Stage Heat

W/W1
Single/First Stage Heat

R
24-Volt Hot

R
24-Volt Hot

Y1
First Stage Heat/Cool

Y
First Stage Heat/Cool

C
24-Volt Common

*PP32U72124

PSC-2 STAGE
COOLING READY
FURNACE CONTROL

R
24-Volt Hot (Heat XFMR)

C
24-Volt Common

C
24-Volt Common

*PP32U71124

THERMOSTAT

Y/Y2
Single/Second Stage Cool

*DN22H00124
*DP22U70124

*PP32U70124

RC
24-Volt Hot (Cool XFMR)

THERMOSTAT

THERMOSTAT

Two Stage H/P - H*5B, YZE - w/Two Stage Furnace, 2 Stage Cooling Ready - PT8/9, (F,L)*8/9T, (G,L)*8/9T, XYG8S-*, XYF8S-*, XYG9S-*, XYF9S-*
W/031-01996- Series Demand Control; Hot Heat Pump Mode OR Conventional

Change FFuel Jumper on
Heat Pump to ON

BS
Bonnet Sensor

BSG
Bonnet Sensor

W
Auxiliary Heat

Y2
Second Stage Heat/Cool

X/L
Malfunction Light

O
Reversing Valve–Energized in Cool

W2 OUT
Second Stage Auxiliary Heat Output

W1 OUT
First Stage Auxiliary Heat Output

R
24-Volt Hot

Y2 OUT
Second Stage Cool Output

Y1
First Stage Heat/Cool

C
24-Volt Common

TWO STAGE
HEAT PUMP

246782-YTG-B-0407

Thermostat Chart - HP

Unitary Products Group

246782-YTG-B-0407

ACCESSORIES
PROPANE (LP) CONVERSION KIT 1NP0347 - All units
This accessory conversion kit may be used to convert natural
gas units for propane (LP) operation. Conversions must be
made by qualified distributor or dealer personnel.
CONCENTRIC VENT TERMINATION 1CT0302 (2")
1CT0303 (3")
For use through rooftop, sidewall. Allows combustion air to
enter and exhaust to exit through single common hole. Eliminates unslightly elbows for a cleaner installation.
SIDEWALL VENT TERMINATION KIT 1HT0901 (3")
1HT0902 (2")
For use on sidewall, two-pipe installations only. Provide a
more attractive termination for locations where the terminal is
visable on the side of the home.
COMBUSTIBLE FLOOR BASE 1CB0317 - 17 1/2” Cabinet
1CB0321 - 21” Cabinet
1CB0324 - 24-1/2” Cabinet
COIL TRANSITION KIT 1TK0917 - 17-1/2” Furnace
1TK0921 - 21” Furnace
1TK0924 - 24-1/2” Furnace
These kits are required in downflow application when using
G*F* series coils. These kits are not required with MC/FC
series coils, but please ensure that the coil and furnace are
secured and that there are no air leaks.

Unitary Products Group

CONDENSATE NEUTRALIZER KIT - 1NK0301
Neutralizer cartidge has a 1/2" plastic tube fittings for installation in the drain line. Calcium carbonate refill media is also
avaiable from the Source 1 Parts (p/n 026-30228-000).
HIGH ALTITUDE PRESSURE SWITCHES For installation where the altitude is less than 8,000 feet it is
not required that the pressure switch be changed. For altitudes above 8,000 feet see kits below. Conversion must be
made by qualified distributor or dealer personnel.
1PS0507 - 060 MBH
1PS0508 - 080/1200 MBH
1PS0509 - 080/1600 MBH
1PS0510 - 100 MBH
1PS0511 - 120 MBH
ROOM THERMOSTATS - A wide selection of compatible
thermosets are available to provide optimum performance
and features for any installation.
1H/1C, manual change-over electronic non-programmable
thermostat.
1H/1C, auto/manual changeover, electronic programmable,
deluxe 7-day, thermostat.
1H/1C, auto/manual changeover, electronic programmable.
* For the most current accessory information, refer to the
price book or consult factory.

7

Subject to change without notice. Printed in U.S.A.
Copyright © by York International Corp. 2007. All rights reserved.

Unitary
Products
Group

246782-YTG-B-0407
Supersedes: 246782/035-21633-002 Rev. A (1205)

5005
York
Drive

Norman
OK
73069



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : No
Page Mode                       : UseThumbs
XMP Toolkit                     : 3.1-702
About                           : uuid:b8404917-bfbc-418f-8a97-39e584bf58c0
Producer                        : Acrobat Distiller 6.0.1 (Windows)
Creator Tool                    : PScript5.dll Version 5.2.2
Modify Date                     : 2007:04:25 15:57:36-05:00
Create Date                     : 2007:04:18 10:14:06-05:00
Metadata Date                   : 2007:04:25 15:57:36-05:00
Document ID                     : uuid:80b2883e-9bdb-45eb-a379-750a9ad16c20
Instance ID                     : uuid:29864942-9f57-450b-9595-968ca1b07c15
Format                          : application/pdf
Title                           : 246782-YTG-B-0407.fm
Creator                         : csardom
Page Count                      : 8
Page Layout                     : OneColumn
Author                          : csardom
EXIF Metadata provided by EXIF.tools

Navigation menu