York Dm072 Users Manual Y TG, Single Package Gas/Elec Units And Sgl Pkg AC, DM036, 048, 060 & 072
DM 048 to the manual aaeb408b-961d-499f-96e5-d9505822227a
2015-02-02
: York Dm072-Users-Manual york-dm072-users-manual-455085 york pdf
Open the PDF directly: View PDF .
Page Count: 40
Download | |
Open PDF In Browser | View PDF |
036-21502-002-A-0303 ® DESCRIPTION YORK Sunline 2000™ units are convertible single package air conditioners with a common cabinet and a common roof curb for the 3, 4, 5 and 6 ton sizes. The units were designed for light commercial and commercial applications. They can easily be installed on a roof curb, slab, roof jack or frame. TECHNICAL GUIDE SINGLE PACKAGE GAS/ELECTRIC UNITS AND SINGLE PACKAGE AIR CONDITIONERS DM 036, 048, 060 & 072 3, 4, 5 & 6 NOMINAL TONS 10.0 SEER (3, 4 & 5 TONS), 9.0 EER (6 TONS) All units include: • Powder Paint finish that meets ASTM-B-117 750 hour salt spray standards • Permanently lubricated motors • Bottom or side air discharge configuration capability (field convertible) • Manufactured under the quality standards of ISO9001 • SimplicityTM Control Board • Copper tube/aluminum fin coils • Easy access to all components • Rigging holes in base rails for lifting • Fork lift slots on three sides • Single point power connection • Complete factory package - tested, charged and wired • CSA agency listing on all units WARRANTY • Factory Limited Parts Warranty • One-year parts warranty • A Five-year parts warranty on the compressor and electric heat elements. • Ten-year parts warranty on the gas-fired heat exchangers. FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE 036-21502-002-A-0303 TABLE OF CONTENTS DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 PRODUCT NOMENCLATURE. . . . . . . . . . . . . . . . . . 3 FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 FACTORY-INSTALLED OPTIONS . . . . . . . . . . . . . . 9 FIELD-INSTALLED ACCESSORIES . . . . . . . . . . . . 10 9 SUPPLY AIR BLOWER PERFORMANCE (4 TON BELT DRIVE) - SIDE DUCT APPLICATION . . . . 17 10 SUPPLY AIR BLOWER PERFORMANCE (5 TON BELT DRIVE) - SIDE DUCT APPLICATION . . . . 18 11 SUPPLY AIR BLOWER PERFORMANCE (6 TON BELT DRIVE) - SIDE DUCT APPLICATION . . . . 19 GUIDE SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . 38 12 SUPPLY AIR BLOWER PERFORMANCE (3 - 6 TON DIRECT DRIVE) . . . . . . . . . . . . . . . . . . . . 20 LIST OF FIGURES 13 BELT DRIVE MOTOR AND DRIVE DATA . . . . . 20 Fig. # Pg. # 14 STATIC RESISTANCES . . . . . . . . . . . . . . . . . . . 21 1 UNIT CUTAWAY . . . . . . . . . . . . . . . . . . . . . . . . . . 9 15 ELECTRIC HEATER CFM LIMITATIONS. . . . . . 21 2 TYPICAL FIELD POWER & CONTROL WIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 16 ELECT DATA - DM036 & 048 DIRECT DRIVE WITHOUT POWR’D CONVENIENCE OUTLET . 22 3 UNIT DIMENSIONS (3 - 6 TON COOLING ONLY/ ELECTRIC HEAT) FRONT VIEW . . . . . . . . . . . . 32 17 ELECT DATA - DM060 & 072 DIRECT DRIVE WITHOUT POWR’D CONVENIENCE OUTLET . 23 4 UNIT DIMENSIONS (3 - 6 TON COOLING/GAS HEAT) FRONT VIEW . . . . . . . . . . . . . . . . . . . . . 32 18 ELECTRICAL DATA - DM036 & 048 BELT DRIVE WITHOUT POWR’D CONVENIENCE OUTLET . 24 5 UNIT WITH ECONOMIZER RAINHOOD . . . . . . 33 19 ELECTRICAL DATA - DM060 & 072 BELT DRIVE WITHOUT POWR’D CONVENIENCE OUTLET . 25 6 UNIT WITH FIXED OUTDOOR AIR/MOTORIZED DAMPER RAINHOOD. . . . . . . . . . . . . . . . . . . . . 33 7 UNIT DIMENSIONS (REAR VIEW). . . . . . . . . . . 34 8 DISCONNECT/BLOWER ACCESS LOCATION . 34 9 TYPICAL APPLICATIONS . . . . . . . . . . . . . . . . . 35 10 FOUR AND SIX POINT LOADING . . . . . . . . . . . 36 20 ELECTRICAL DATA - DM036 & 048 DIRECT DRIVE WITH POWR’D CONVENIENCE OUTLET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 21 ELECTRICAL DATA - DM060 & 072 DIRECT DRIVE WITH POWR’D CONVENIENCE OUTLET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 11 ROOF CURB DIMENSIONS . . . . . . . . . . . . . . . . 37 22 ELECTRICAL DATA - DM036 & 048 BELT DRIVE WITH POWR’D CONVENIENCE OUTLET . . . . . 28 LIST OF TABLES 23 ELECTRICAL DATA - DM060 & 072 BELT DRIVE WITH POWR’D CONVENIENCE OUTLET . . . . . 29 Tbl. # Pg. # 24 PHYSICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . 30 1 SOUND POWER RATING . . . . . . . . . . . . . . . . . 11 25 ELECTRIC HEAT CORRECTION FACTORS . . 30 2 CAPACITY RATINGS - (ARI 210/240) . . . . . . . . 11 26 VOLTAGE LIMITATIONS . . . . . . . . . . . . . . . . . . 30 3 GAS HEAT RATINGS . . . . . . . . . . . . . . . . . . . . . 11 27 UTILITIES ENTRY . . . . . . . . . . . . . . . . . . . . . . . 34 4 DM036 COOLING CAPACITIES (3 TON). . . . . . 12 28 MINIMUM CLEARANCES . . . . . . . . . . . . . . . . . . 34 5 DM048 COOLING CAPACITIES (4 TON). . . . . . 13 29 DM 4 POINT LOADS WEIGHT DISTRIBUTION . 36 6 DM060 COOLING CAPACITIES (5 TON). . . . . . 14 30 DM 6 POINT LOADS WEIGHT DISTRIBUTION . 36 7 DM072 COOLING CAPACITIES (6 TON). . . . . . 15 31 CENTER OF GRAVITY . . . . . . . . . . . . . . . . . . . . 36 8 SUPPLY AIR BLOWER PERFORMANCE (3 TON BELT DRIVE) - SIDE DUCT APPLICATION . . . . 16 32 OPERATING WEIGHTS (LBS.) . . . . . . . . . . . . . 37 2 Unitary Products Group 036-21502-002-A-0303 PRODUCT NOMENCLATURE 3-6 Ton Sunline Model Number Nomenclature D M 048 N04 A 2 A AA 1 Product Generation Product Catagory 1 = First Generation D = Air Cond., Single Package B = Heat Pump, Single Package Voltage Product Identifier 1 = 208/230-1-60 2 = 208/230-3-60 4 = 460-3-60 5 = 575-3-60 M = R-22 Standard Efficiency (DCG/DCE) F = R-22 Medium Efficiency (DEG/DEE) H = R-22 High Efficiency (DHG/DHE) Q = R-22 Std. Effic Heat Pump (BCH) Nominal Cooling Capacity - MBH Installation Options A = No Options Installed B = Option 1 C = Option 2 D = Options 1 & 2 E = Option 3 F = Option 4 G = Options 1 & 3 H = Options 1 & 4 J = Options 1, 2 & 3 K = Options 1, 2, & 4 L = Options 1,3 & 4 M = Options 1, 2, 3, & 4 N = Options 2 & 3 P = Options 2 & 4 Q = Options 2, 3, & 4 R = Options 3 & 4 S = Option 5 T = Options 1 & 5 U = Options 1, 3, & 5 V = Options 1, 4, & 5 W = Options 1, 3, 4, & 5 X = Options 3 & 5 Y = Options 4 & 5 Z = Options 3, 4, & 5 036 = 3 Ton 048 = 4 Ton 060 = 5 Ton 072 = 6 Ton Heat Type & Nominal Heat Capacity C00 = Cooling Only. Suitable for field installed electric heat Gas Heat Options N04 = 40 MBH Output Aluminized Steel (036) N06 = 60 MBH Output Aluminized Steel (048) N08 = 79 MBH Output Aluminized Steel (036,060,072) N10 = 99 MBH Output Aluminized Steel (048,060,072) S04 = 40 MBH Output Stainless Steel (036) S06 = 60 MBH Output Stainless Steel (048) S08 = 79 MBH Output Stainless Steel (036,060,072) S10 = 99 MBH Output Stainless Steel (048,060,072) Electric Heat Options E05 = 5 kW Electric Heat E07 = 7 kW Electric Heat E10 = 10 kW Electric Heat E15 = 15 kW Electric Heat E20 = 20 kW Electric Heat E30 = 30 kW Electric Heat Additional Options (See Next Page) Options 1 = Disconnect 2 = Non-Pwr'd Conv Oultet 3 = Smoke Detector S.A. 4 = Smoke Detector R.A. 5 = Pwr'd Conv. Outlet Airflow A= Direct Drive B = Direct Drive/Single Input Econo D = Direct Drive/Motorized Damper L = Direct Drive/BAS Ready Econ (No BAS Controller)/2" Pleated Filters/Extra xfrmr & circuit bkr. N = Belt Drive P = Belt Drive/Single Input Econo R = Belt Drive/Motorized Damper Y = Belt Drive/BAS Ready Econ (No BAS Controller) w/2" Pleated Filters Unitary Products Group 3 036-21502-002-A-0303 PRODUCT NOMENCLATURE - Continued 3-6T Sunline Model Number Nomenclature Additional Options AA None AB Phase Monitor AC Coil Guard AD Dirty Filter Switch AE Phase Monitor & Coil Guard AF Phase Monitor & Dirty Filter Switch AG Coil Guard & Dirty Filter Switch AH Phase Monitor, Coil Guard, & Dirty Filter Switch AS Bottom Condensate Pan BA Hinged Filter Door & Toolless Access Panels BB Phase Monitor, Hinged Filter Door & Toolless Access Panels BC Coil Guard, Hinged Filter Door & Toolless Access Panels BD Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels BE Phase Monitor & Coil Guard, Hinged Filter Door & Toolless Access Panels BF Phase Monitor & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels BG Coil Guard & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels BH Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels CA CPC Controller with Dirty Filter Switch & Air Proving Switch CB CPC Controller, DFS, APS & Phase Monitor CC CPC Controller, DFS, APS & Coil Guard CD CPC Controller, DFS, APS, Phase Monitor, & Coil Guard CE CPC Controller, DFS, APS & Technicoat Cond. Coil CF CPC Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor CG CPC Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard CH CPC Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard CJ CPC Controller, DFS, APS & Technicoat Evap. Coil CK CPC Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor CL CPC Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard CM CPC Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard CN CPC Controller, DFS, APS & Technicoat Evap. & Cond Coils CP CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor CQ CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard CR CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard DA CPC Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels DB CPC Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels DC CPC Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels DD CPC Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels DE CPC Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels DF CPC Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels DG CPC Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels DH CPC Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels DJ CPC Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels DK CPC Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels DL CPC Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels DM CPC Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels DN CPC Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels DP CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Panels DQ CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels DR CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels 4 Unitary Products Group 036-21502-002-A-0303 Additional Options EA Johnson UNT Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels EB Johnson UNT Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels EC Johnson UNT Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels ED Johnson UNT Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels EE Johnson UNT Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels EF Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels EG Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels EH Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels EJ Johnson UNT Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels EK Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels EL Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels EM Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels EN Johnson UNT Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels EP Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Panels EQ Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels ER Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels GA Honeywell Excel 10 Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels GB Honeywell Excel 10 Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels GC Honeywell Excel 10 Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels GD Honeywell Excel 10 Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels GE Honeywell Excel 10 Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels GF Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels GG Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels GH Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels GJ Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels GK Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels GL Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels GM Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels GN Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels GP Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Panels GQ Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels GR Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels HA Honeywell Excel 10 Controller with Dirty Filter Switch & Air Proving Switch HB Honeywell Excel 10 Controller, DFS, APS & Phase Monitor HC Honeywell Excel 10 Controller, DFS, APS & Coil Guard HD Honeywell Excel 10 Controller, DFS, APS, Phase Monitor, & Coil Guard HE Honeywell Excel 10 Controller, DFS, APS & Technicoat Cond. Coil HF Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor HG Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard HH Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard HJ Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. Coil HK Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor HL Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard HM Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard HN Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. & Cond Coils HP Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor HQ Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard HR Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard Unitary Products Group 5 036-21502-002-A-0303 Additional Options JA Johnson UNT Controller with Dirty Filter Switch & Air Proving Switch JB Johnson UNT Controller, DFS, APS & Phase Monitor JC Johnson UNT Controller, DFS, APS & Coil Guard JD Johnson UNT Controller, DFS, APS, Phase Monitor, & Coil Guard JE Johnson UNT Controller, DFS, APS & Technicoat Cond. Coil JF Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor JG Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard JH Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard JJ Johnson UNT Controller, DFS, APS & Technicoat Evap. Coil JK Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor JL Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard JM Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard JN Johnson UNT Controller, DFS, APS & Technicoat Evap. & Cond Coils JP Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor JQ Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard JR Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard NA Novar ETC-3 Controller with Dirty Filter Switch & Air Proving Switch NB Novar ETC-3 Controller, DFS, APS & Phase Monitor NC Novar ETC-3 Controller, DFS, APS & Coil Guard ND Novar ETC-3 Controller, DFS, APS, Phase Monitor, & Coil Guard NE Novar ETC-3 Controller, DFS, APS & Technicoat Cond. Coil NF Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor NG Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard NH Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard NJ Novar ETC-3 Controller, DFS, APS & Technicoat Evap. Coil NK Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor NL Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard NM Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard NN Novar ETC-3 Controller, DFS, APS & Technicoat Evap. & Cond Coils NP Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor NQ Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard NR Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard PA Novar ETC-3 Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels PB Novar ETC-3 Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels PC Novar ETC-3 Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels PD Novar ETC-3 Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels PE Novar ETC-3 Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels PF Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels PG Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels PH Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels PJ Novar ETC-3 Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels PK Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels PL Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels PM Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels PN Novar ETC-3 Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels PP Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Panels PQ Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels PR Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels TA Technicoat Condenser Coil TB Technicoat Condenser Coil & Phase Monitor TC Technicoat Condenser Coil & Coil Guard 6 Unitary Products Group 036-21502-002-A-0303 Additional Options TD Technicoat Condenser Coil & Dirty Filter Switch TE Technicoat Condenser Coil, Phase Monitor, & Coil Guard TF Technicoat Condenser Coil, Phase Monitor, & Dirty Filter Switch TG Technicoat Condenser Coil, Coil Guard, & Dirty Filter Switch TH Technicoat Condenser Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch TJ Technicoat Evaporator Coil TK Technicoat Evaporator Coil & Phase Monitor TL Technicoat Evaporator Coil & Coil Guard TM Technicoat Evaporator Coil & Dirty Filter Switch TN Technicoat Evaporator Coil, Phase Monitor, & Coil Guard TP Technicoat Evaporator Coil, Phase Monitor, & Dirty Filter Switch TQ Technicoat Evaporator Coil, Coil Guard, & Dirty Filter Switch TR Technicoat Evaporator Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch TS Technicoat Evaporator & Condenser Coils TT Technicoat Evaporator & Condenser Coils & Phase Monitor TU Technicoat Evaporator & Condenser Coils & Coil Guard TV Technicoat Evaporator & Condenser Coils & Dirty Filter Switch TW Technicoat Evaporator & Condenser Coils, Phase Monitor, & Coil Guard TX Technicoat Evaporator & Condenser Coils, Phase Monitor, & Dirty Filter Switch TY Technicoat Evaporator & Condenser Coils, Coil Guard, & Dirty Filter Switch TZ Technicoat Evaporator & Condenser Coils, Phase Monitor, Coil Guard, & Dirty Filter Switch UA Technicoat Condenser Coil, Hinged Filter Door & Toolless Access Panels UB Technicoat Condenser Coil & Phase Monitor, Hinged Filter Door & Toolless Access Panels UC Technicoat Condenser Coil & Coil Guard, Hinged Filter Door & Toolless Access Panels UD Technicoat Condenser Coil & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels UE Technicoat Condenser Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels UF Technicoat Condenser Coil, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels UG Technicoat Condenser Coil, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels UH Technicoat Condenser Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels UJ Technicoat Evaporator Coil, Hinged Filter Door & Toolless Access Panels UK Technicoat Evaporator Coil & Phase Monitor, Hinged Filter Door & Toolless Access Panels UL Technicoat Evaporator Coil & Coil Guard, Hinged Filter Door & Toolless Access Panels UM Technicoat Evaporator Coil & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels UN Technicoat Evaporator Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels UP Technicoat Evaporator Coil, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels UQ Technicoat Evaporator Coil, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels UR Technicoat Evaporator Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels US Technicoat Evaporator & Condenser Coils, Hinged Filter Door & Toolless Access Panels UT Technicoat Evaporator & Condenser Coils & Phase Monitor, Hinged Filter Door & Toolless Access Panels UU Technicoat Evaporator & Condenser Coils & Coil Guard, Hinged Filter Door & Toolless Access Panels UV Technicoat Evaporator & Condenser Coils & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels UW Technicoat Evaporator & Condenser Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels UX Technicoat Evaporator & Condenser Coils, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels UY Technicoat Evaporator & Condenser Coils, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels UZ Technicoat Evaporator & Condenser Coils, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels Unitary Products Group 7 036-21502-002-A-0303 FEATURES gas valve, if applicable, and the temperature limit switch on gas heat units. The unit control board will alarm on ignition failures, compressor lockouts and repeated limit switch trips. All models are available with a wide variety of factorymounted options such as stainless steel heat exchangers, phase monitor, dirty filter switch, and coil guard to make them suitable for almost every application. All units are self-contained and assembled on full perimeter base rails with forklift holes on three sides and holes for overhead rigging. Every unit is completely piped, wired, charged and tested at the factory to simplify the field installation and to provide years of dependable operation. All models (including those with an economizer) are suitable for either bottom or horizontal duct connections. For bottom duct, remove the sheet metal panels from the supply and return air openings through the base of the unit. For horizontal duct, remove the supply and return air panels on the rear of the unit. All models are available with these “factory mounted” outdoor air damper options: • Nuisance Trip Protection- To prevent nuisance trouble calls, the control board uses a “three strikes, you’re out” philosophy. The high and low-pressure switches and the freezestats must trip three times within two hours before the unit control board will lock out the compressor. • On Board Diagnostics - Each alarm will energize a trouble light on the thermostat, if so equipped, and flash an alarm code on the control board LED. Each high and low-pressure switch alarm as well as each freezestat alarm has its own flash code. The control board saves the five most recent alarms in memory, and these alarms can be reviewed at any time. Alarms and programmed values are retained through the loss of power. • Single enthalpy economizer All units have long lasting powder paint cabinets with 750 hour salt spray test approval under ASTM-B117 procedures. • Motorized outdoor air damper All models are CSA listed. Supply air blowers are equipped with either a direct drive or a belt drive that can be adjusted to meet the exact requirements of the job. All compressors are equipped with internal pressure relief. Every refrigerant circuit includes a liquid line filter-drier, a high pressure switch and a suction line with a freezestat and low pressure/loss of charge switch to protect all system components. • Simplicity Warranty - All models include a one-year limited parts warranty on the complete unit. Compressors and electric heater elements carry a five-year warranty. Gas heat exchangers carry a 10-year parts warranty. • Gas Heat Operation - All gas heat units have a minimum AFUE of 80%. Each section includes a durable heat exchanger with aluminized steel or optional stainless steel tubes, a redundant gas valve, spark ignition, power venting, an ignition module for 100% shut-off and all of the safety controls required to meet the latest ANSI standards. Simplicity ™ Controls ™ control boards have standardized a number of features previously available only as options or by utilizing additional controls. • • • • 8 • Low Ambient - An integrated low-ambient control allows all units to operate in the cooling mode down to 0ºF outdoor ambient without additional assistance. Optionally, the control board can be programmed to lockout the compressors when the outdoor air temperature is low or when free cooling is available. The gas supply piping can be routed into the heating compartment through a hole in the base pan of the unit or through a knockout in the piping panel on the front of the unit. • Anti-Short Cycle Protection - To aid compressor life, an anti-short cycle delay is incorporated into the standard controls. Compressor reliability is further ensured by programmable minimum run times. For testing, the anti short cycle delay can be temporarily overridden with the push of a button. Fan Delays - Fan on and fan off delays are fully programmable and are independent of one another. All units are programmed with default values based upon their configuration of cooling and heat. Safety Monitoring - The control board monitors the high and low-pressure switches, the freezestats, the Electric Heat Operation - All electric heat models are wired for a single power source and include a bank of nickel chromium elements mounted at the discharge of the supply air blower to provide a high velocity and uniform distribution of air across the heating elements. Every element is fully protected against excessive temperature by thermal limit switches. The power supply wiring can be routed into the control box through a threaded pipe connection (field supplied) in the base pan of the unit or through a knockout in the wiring panel on the side of the unit. • BAS Controls - York’s Sunline™ series units offer factory mounted BAS controls such as Novar, Honeywell, Johnson, and CPC. Unitary Products Group 036-21502-002-A-0303 FIGURE 1: UNIT CUTAWAY FACTORY-INSTALLED OPTIONS • SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZERS - Includes a slide-in / plug-in damper assembly with fully modulating spring-return motor actuator capable of introducing up to 100% outdoor air with nominal 1% leakage type dampers. The enthalpy system contains one sensor that monitors the outdoor air and determines when the air is cool enough and dry enough to provide free cooling. • ELECTRIC HEATERS wired for single point power supply. These nickel chromium heater elements are provided with limit and automatic reset capability to prevent operation at excessive temperatures. • FILTER OPTIONS - Standard units are shipped with 1” throw-away filters installed. 2” pleated filters are offered as a factory installed option. • CONVENIENCE OUTLET - This 110 volt outlet can be “powered” by the unit with a stepdown transformer or the unit may be ordered with a “non-powered” convenience outlet that can be wired in the field. • DISCONNECT SWITCH - For gas heat units and cooling units with electric heat, a HACR breaker sized to the unit is provided. For cooling only units, a switch sized to the largest electric heat available for the particular unit is provided. Factory installed option only. • BAS - See “Additional Options” section in the product nomenclature. • SMOKE DETECTORS - (supply air & return air) The smoke detectors stop operation of the unit by interrupting power to the control board if smoke is detected within the air compartment. The rainhood is painted to match the basic unit and must be field-assembled before installing. • MOTORIZED OUTDOOR AIR INTAKE DAMPER Includes a slide-in / plug-in damper assembly with a 2position, spring return motor actuator which opens to a pre-set position whenever the supply air blower is operating and will drive fully closed when the blower unit shuts down. The rain hood is painted to match the basic unit and must be field assembled before installing. • PHENOLIC COATED EVAPORATOR AND CONDENSER COILS - Special coating process that utilizes Technicoat 10-1TM processes. Coating is applied by total immersion of the complete coil for maximum protection. Unitary Products Group 9 036-21502-002-A-0303 Roof curbs are designed to fit inside the base rails of the unit and include both a wood nailing strip and duct hanger supports. • COIL GUARD - Customers can purchase a coil guard kit to protect the condenser coil from damage. This is not a hail guard kit. • STAINLESS STEEL HEAT EXCHANGER - For applications in corrosive environments, this option provides a full stainless steel heat exchanger assembly. • HIGH ALTITUDE NATURAL GAS - Burner orifices and pilot orifices are provided for proper furnace operation at altitudes up to 6,000 feet. • PHASE MONITORS - Designed to prevent unit damage. The phase monitor will shut the unit down in an out-ofphase condition. • PROPANE - Burner orifices, pilot orifices and gas valve parts are provided to convert a natural gas furnace to propane. • DIRTY FILTER SWITCH - This kit includes a differential pressure switch that energizes the fault light on the unit thermostat, indicating that there is an abnormally high pressure drop across the filters. Factory installed option or field installed accessory. • HIGH ALTITUDE PROPANE - Burner orifices and pilot orifices are provided for proper furnace operation at altitudes up to 6,000 feet. This accessory supplements the basic propane conversion kit. • • HINGED FILTER DOOR/“TOOLLESS” BLOWER AND ACCESS PANELS (not hinged) - This option allows for easy access and maintenance. LOW NOX KIT- Required to reduce the emission of nitrogen oxides below 40 nanograms per joule. • POWER EXHAUST - Our single input economizer options are available with power exhaust. Whenever the outdoor air intake dampers are opened for free cooling, the exhaust fan will be energized to prevent the conditioned space from being over-pressurized during economizer operation. NOTE:Knobs are shipped inside the unit to prevent shipping damage. These must be field installed for tool-less operation. FIELD-INSTALLED ACCESSORIES • SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZERS - Includes a slide-in / plug-in damper assembly with fully modulating spring-return motor actuator capable of introducing up to 100% outdoor air with nominal 1% leakage type dampers. The power exhaust option can only be used on bottom duct configurations. • BAROMETRIC RELIEF DAMPER - This damper accessory can be used to relieve internal building air pressure on units with an economizer without power exhaust. This accessory includes a rain hood, a bird screen and a fully assembled damper. With bottom duct connections, the damper should be mounted over the opening in the return air panel. With horizontal ductwork, the accessory should be mounted on the return air duct. • ENTHALPY ACCESSORY CONTROL KIT - This kit contains the required components to convert a single enthalpy economizer to dual enthalpy. • BURGLAR BARS - Mount in the supply and return openings to prevent entry into the duct work. • FLUE EXHAUST EXTENSION KIT - In locations with wind or weather conditions which may interfere with proper exhausting of furnace combustion products, this kit can be installed to prevent the flue exhaust from entering nearby fresh air intakes. • CO 2 SENSOR - Senses CO 2 levels and automatically overrides the economizer when levels rise above the present limits. • COIL GUARD - Customers can purchase a coil guard kit to protect the condenser coil from damage. This is not a hail guard kit. The enthalpy system contains one sensor that monitors the outdoor air and determines when the air is cool enough and dry enough to provide free cooling. The rainhood is painted to match the basic unit and must be field-assembled before installing. • MOTORIZED OUTDOOR AIR INTAKE DAMPER Includes a slide-in / plug-in damper assembly with a 2position, spring return motor actuator which opens to some pre-set position whenever the supply air blower is operating and will drive fully closed when the blower unit shuts down. The rain hood is painted to match the basic unit and must be field assembled before installing. • • 10 ELECTRIC HEATERS wired for single point power supply. These nickel chromium heater elements are provided with limit and automatic reset capability to prevent operation at excessive temperatures. ROOF CURBS - Eight and fourteen-inch high roof curbs provide a water-tight seal between the unit and the finished roof. These full perimeter curbs meet the requirements of the National Roofing Contractors Association (NRCA) and are shipped knocked-down for field assembly. Unitary Products Group 036-21502-002-A-0303 TABLE 1: SOUND POWER RATING1 UNIT SIZE ESP SOUND POWER (db 10-12 Watts) BLOWER Octave Band Centerline Frequency (Hz) CFM IWG SPEED KW 63 125 250 500 1,000 2,000 4,000 8,000 SWL dB(A) dB(A) @ 10Ft.2 036 1,200 0.6 LOW 0.60 84 84 74 67 69 62 57 52 74 41 048 1,600 0.55 HIGH 0.80 85 85 75 68 70 63 58 53 75 42 060 2,000 0.45 HIGH 1.00 86 86 76 69 71 64 59 54 76 43 072 2,200 0.3 HIGH 1.35 87 87 77 70 72 65 60 55 77 44 1. These values have been accessed using a model of sound propagation from a point source into the hemispheric\free field. The dBA values provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan manufacture has no way of knowing the details of each system. This constitutes and expectation to any specification or guarantee requiring a dBA value or sound data in any other form than sound power level ratings. 2. At a distance of 10 feet from the blower. TABLE 2: CAPACITY RATINGS - (ARI 210/240)1 MODEL MBH EER2 SEER3 DM036 36.0 9.1 10.0 DM048 47.4 9.0 10.0 DM060 59.0 9.1 10.0 DM072 72.0 9.0 - 1. 80/67°F Indoor and 95°F outdoor. 2. EER = Energy Efficiency Ratio at full load - the cooling capacity in Btu’s per hour (Btuh) divided by the power input in watts, expressed in Btuh per watt (Btuh/watt). 3. SEER = Seasonal Energy Efficiency Ratio. TABLE 3: GAS HEAT RATINGS1 MODEL MBH INPUT MBH OUTPUT AFUE (%) TEMP RISE ºF DM036N04 DM036N08 50 100 40 79 80.9 80.5 15 - 45 40 - 70 DM048N06 DM048N10 75 125 59 99 80.9 80.3 25 - 55 45 - 75 DM060N08 DM060N10 100 125 79 99 80.5 80.3 25 - 55 35 - 65 DM072N08 DM072N10 100 125 79 99 80.5 80.3 25 - 55 35 - 65 1. All units are single-stage heating. Unitary Products Group 11 036-21502-002-A-0303 TABLE 4: DM036 COOLING CAPACITIES (3 TON) TEMPERATURE OF AIR ON CONDENSER COIL AIR ON EVAPORATOR COIL 85°F TOTAL 1 CFM 1750 1475 1200 1050 900 POWER CAP. MBH INPUT2 kW WB °F 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 45 43 39 40 44 41 38 39 42 40 36 37 41 38 35 36 39 37 34 34 3.1 3.0 3.0 2.9 3.1 3.0 3.0 2.9 3.1 3.0 3.0 2.9 3.1 3.0 3.0 2.9 3.1 3.0 3.0 2.9 95°F SENSIBLE CAPACITY1 ENTERING DRY BULB, °F TOTAL 1 SENSIBLE CAPACITY1 ENTERING DRY BULB, °F POWER 83 80 77 74 71 68 CAP. MBH INPUT2 kW 86 35 43 39 40 31 39 38 39 28 35 36 37 26 32 35 36 24 30 34 34 30 38 39 40 28 35 38 39 25 32 36 37 23 30 35 36 21 27 33 34 26 34 39 40 24 31 37 39 22 28 35 37 20 27 33 35 19 25 30 33 21 29 34 35 20 27 33 35 18 25 31 34 17 24 30 32 16 22 28 30 17 25 30 31 16 23 29 31 15 22 28 31 14 21 27 29 14 20 25 27 20 25 26 19 25 27 18 25 27 18 24 26 17 23 25 16 21 22 16 21 23 15 21 24 15 21 23 15 20 22 43 41 36 38 42 39 36 37 41 38 35 36 39 37 33 34 38 36 32 33 3.3 3.3 3.3 3.2 3.3 3.3 3.3 3.2 3.3 3.2 3.3 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.1 86 83 80 77 74 71 68 35 41 36 38 31 37 36 37 28 34 35 36 26 32 33 34 23 29 32 33 30 38 36 38 27 35 36 37 24 31 35 36 23 29 33 34 21 26 31 33 26 34 36 38 23 31 35 36 21 28 34 35 20 26 31 32 18 24 29 30 21 29 32 33 20 27 31 32 18 25 30 32 17 23 28 30 16 21 26 27 17 25 27 29 16 23 27 28 14 21 27 28 14 20 25 27 13 19 24 25 21 23 24 19 23 25 18 24 25 17 22 24 16 21 22 16 18 20 15 19 21 15 20 22 14 20 21 14 19 20 TEMPERATURE OF AIR ON CONDENSER COIL AIR ON EVAPORATOR COIL 105°F TOTAL 1 CFM 1750 1475 1200 1050 900 POWER CAP. MBH INPUT2 kW WB °F 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 41 38 34 35 40 37 33 34 39 36 32 33 37 35 31 32 36 33 30 31 3.7 3.7 3.7 3.6 3.7 3.6 3.7 3.6 3.7 3.6 3.6 3.6 3.6 3.6 3.6 3.5 3.6 3.6 3.6 3.5 115°F SENSIBLE CAPACITY1 ENTERING DRY BULB, °F TOTAL 1 SENSIBLE CAPACITY1 ENTERING DRY BULB, °F POWER 83 80 77 74 71 68 CAP. MBH INPUT2 kW 86 34 38 34 35 30 36 33 34 27 34 32 33 25 31 31 32 22 28 30 31 29 37 34 35 26 34 33 34 24 30 32 33 22 28 31 32 20 25 29 30 25 33 34 35 23 30 33 34 20 27 32 33 19 25 29 30 17 23 27 28 20 28 30 31 19 26 29 30 17 24 29 29 16 22 27 27 15 20 24 25 16 24 25 26 15 22 25 26 14 20 25 26 13 19 24 24 12 18 22 22 19 21 22 18 21 22 17 22 23 16 21 21 15 19 20 15 16 17 14 17 18 14 19 19 13 18 18 13 17 17 39 36 32 33 38 35 31 32 37 34 30 31 36 32 29 30 34 31 28 28 4.1 4.0 4.0 4.0 4.1 4.0 4.0 4.0 4.1 4.0 4.0 3.9 4.1 4.0 4.0 3.9 4.0 4.0 4.0 3.9 86 83 80 77 74 71 68 33 36 32 33 30 34 31 32 26 33 30 31 24 30 29 30 21 27 28 28 28 36 32 33 26 33 31 32 23 30 30 31 21 27 29 29 19 24 28 28 24 32 32 33 22 29 31 32 20 26 30 31 18 24 28 28 16 22 25 25 19 27 27 28 18 25 27 28 16 23 27 27 15 21 25 25 14 19 22 23 15 23 23 24 14 21 23 24 13 20 24 24 12 18 22 22 11 17 20 20 18 18 19 17 19 20 16 20 21 15 19 19 14 17 17 14 14 15 13 15 16 13 17 17 12 16 16 11 15 15 1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE Table, multiply this value by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit. 2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input is 0.36kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor. NOMINAL RATING 12 Unitary Products Group 036-21502-002-A-0303 TABLE 5: DM048 COOLING CAPACITIES (4 TON) TEMPERATURE OF AIR ON CONDENSER COIL AIR ON EVAPORATOR COIL TOTAL INPUT2 kW CFM WB °F CAP.1 MBH 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 60 55 51 49 58 53 49 47 56 51 47 46 54 49 45 44 52 47 43 42 4.1 4.1 4.0 3.9 4.1 4.1 4.0 3.9 4.1 4.1 4.0 3.9 4.1 4.1 4.0 3.9 4.1 4.1 4.0 3.9 2000 1800 1600 1400 1200 85°F 95°F SENSIBLE CAPACITY1 ENTERING DRY BULB, °F POWER TOTAL 86 83 80 77 74 71 68 CAP.1 MBH 44 53 51 49 41 49 49 47 38 46 47 46 35 42 45 44 32 39 43 42 39 48 51 49 36 45 49 47 34 41 47 46 31 38 45 44 29 35 43 42 33 42 51 49 31 40 48 47 29 37 45 46 27 34 42 43 25 32 39 39 28 37 45 44 26 35 43 43 25 32 41 41 23 30 38 39 22 28 36 36 23 32 40 39 21 30 38 38 20 28 36 37 19 26 34 35 18 25 32 32 26 34 33 25 33 33 24 32 32 22 30 31 21 29 29 21 29 28 20 28 28 19 27 28 19 26 27 18 25 25 60 52 48 47 57 50 46 45 55 48 44 44 53 47 43 42 51 45 41 41 SENSIBLE CAPACITY1 ENTERING DRY BULB, °F POWER INPUT2 kW 4.5 4.5 4.4 4.3 4.5 4.5 4.4 4.3 4.6 4.5 4.4 4.4 4.5 4.5 4.4 4.3 4.5 4.4 4.3 4.3 86 83 80 77 74 71 68 44 52 48 47 41 49 46 45 38 45 44 44 35 41 43 42 32 38 41 41 39 47 48 47 36 44 46 45 33 40 44 44 31 38 43 42 28 35 41 41 33 42 48 47 31 39 46 45 29 36 44 44 27 34 41 41 25 31 38 38 28 36 42 42 26 34 41 40 24 31 40 39 23 30 37 37 21 28 35 34 23 31 37 36 21 29 36 36 20 27 35 35 19 26 33 33 18 24 31 31 25 32 31 24 31 31 23 31 30 22 29 29 21 28 27 20 26 26 19 26 26 18 26 26 18 25 25 17 24 24 TEMPERATURE OF AIR ON CONDENSER COIL AIR ON EVAPORATOR COIL 105°F TOTAL 1 CFM 2000 1800 1600 1400 1200 POWER CAP. MBH INPUT2 kW WB °F 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 56 49 45 44 55 48 43 43 53 46 42 41 51 44 40 40 49 42 38 38 5.1 5.0 4.9 4.9 5.0 5.0 4.9 4.9 5.0 4.9 4.9 4.8 5.0 4.9 4.8 4.8 4.9 4.9 4.8 4.8 115°F SENSIBLE CAPACITY1 ENTERING DRY BULB, °F TOTAL 1 SENSIBLE CAPACITY1 ENTERING DRY BULB, °F POWER 83 80 77 74 71 68 CAP. MBH INPUT2 kW 86 42 49 45 44 39 47 43 43 36 44 42 41 33 41 40 40 30 37 38 38 37 46 45 44 34 43 43 43 32 40 42 41 29 37 40 40 27 34 38 38 31 40 45 44 29 38 43 43 28 35 42 41 26 33 39 38 23 30 36 35 26 35 39 39 24 33 38 38 23 31 37 37 22 29 35 34 20 27 32 32 21 29 34 33 20 28 33 33 19 26 33 32 18 25 31 30 16 23 29 28 24 28 28 23 28 28 22 28 28 21 27 26 20 25 25 19 23 22 18 23 23 17 24 23 17 23 22 16 22 21 53 46 41 41 52 45 40 40 51 44 39 39 48 42 37 37 46 39 35 35 5.6 5.5 5.4 5.4 5.5 5.4 5.4 5.4 5.5 5.4 5.3 5.3 5.5 5.3 5.3 5.3 5.4 5.3 5.3 5.3 86 83 80 77 74 71 68 40 46 41 41 38 45 40 40 35 44 39 39 32 40 37 37 29 36 35 35 35 44 41 41 33 42 40 40 31 39 39 39 28 36 37 37 26 33 35 35 29 39 41 41 28 37 40 40 26 35 39 39 24 32 36 36 22 29 33 33 24 33 36 35 23 32 35 35 22 30 35 34 20 28 32 32 19 26 29 29 19 28 30 30 18 27 30 30 17 26 30 30 16 24 28 28 15 22 26 26 23 25 25 22 26 25 21 26 25 20 24 24 19 22 22 17 20 19 17 21 20 17 21 21 16 20 20 15 19 19 1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE Table, multiply this value by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit. 2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input is 0.36kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor. NOMINAL RATING Unitary Products Group 13 036-21502-002-A-0303 TABLE 6: DM060 COOLING CAPACITIES (5 TON) TEMPERATURE OF AIR ON CONDENSER COIL AIR ON EVAPORATOR COIL TOTAL INPUT2 kW CFM WB °F CAP.1 MBH 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 68 62 57 55 67 62 56 54 66 61 55 53 63 58 53 51 60 56 51 49 4.9 4.8 4.7 4.7 4.9 4.8 4.7 4.7 4.9 4.8 4.7 4.6 4.8 4.7 4.6 4.6 4.8 4.7 4.6 4.6 2500 2250 2000 1750 1500 85°F 95°F SENSIBLE CAPACITY1 ENTERING DRY BULB, °F POWER TOTAL 86 83 80 77 74 71 68 CAP.1 MBH 50 62 57 55 48 59 56 54 45 55 55 53 41 51 53 51 37 46 51 49 44 56 57 55 42 53 56 54 39 50 55 53 36 46 53 51 33 42 51 49 38 50 57 55 36 47 56 54 34 44 55 53 31 41 51 49 29 38 47 45 32 43 51 48 30 41 50 48 29 39 50 48 27 36 47 44 25 34 43 41 25 37 44 42 24 35 45 42 23 34 45 42 22 32 42 40 21 30 39 37 31 38 36 30 39 36 28 39 37 27 37 35 26 35 33 24 32 29 24 33 31 23 34 32 22 32 30 21 31 29 65 60 53 51 65 59 53 50 64 58 52 50 61 56 50 47 58 53 47 45 SENSIBLE CAPACITY1 ENTERING DRY BULB, °F POWER INPUT2 kW 5.6 5.3 5.3 5.4 5.4 5.2 5.2 5.3 5.3 5.1 5.1 5.2 5.4 5.1 5.2 5.2 5.4 5.2 5.2 5.3 86 83 80 77 74 71 68 50 60 53 51 47 57 53 50 44 54 52 50 40 49 50 47 36 44 47 45 43 54 53 51 41 51 53 50 39 48 52 50 35 44 50 47 32 40 47 45 37 48 53 51 35 45 53 50 33 43 52 50 31 39 48 46 28 36 44 42 31 42 47 44 29 40 47 44 28 38 47 44 26 35 43 41 24 32 40 38 24 35 41 38 23 34 41 39 22 32 42 39 21 30 39 36 20 28 36 34 29 34 32 28 35 33 27 36 34 25 34 32 24 32 29 23 28 25 22 29 27 22 31 28 21 29 27 20 27 25 TEMPERATURE OF AIR ON CONDENSER COIL AIR ON EVAPORATOR COIL 105°F TOTAL 1 CFM 2500 2250 2000 1750 1500 POWER CAP. MBH INPUT2 kW WB °F 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 61 55 49 47 61 54 48 46 60 54 48 46 57 51 45 43 54 48 43 41 6.1 5.9 5.9 5.9 6.0 5.9 5.8 5.8 6.0 5.8 5.7 5.8 6.0 5.8 5.7 5.8 6.0 5.8 5.7 5.8 115°F SENSIBLE CAPACITY1 ENTERING DRY BULB, °F TOTAL 1 SENSIBLE CAPACITY1 ENTERING DRY BULB, °F POWER 83 80 77 74 71 68 CAP. MBH INPUT2 kW 86 48 55 49 47 45 53 48 46 42 52 48 46 38 47 45 43 34 42 43 41 41 52 49 47 39 49 48 46 37 47 48 46 34 42 45 43 30 38 43 41 35 46 49 47 33 44 48 46 32 41 48 46 29 38 44 42 26 34 39 38 29 39 42 40 28 38 42 40 26 36 43 41 24 33 39 37 22 30 35 34 22 33 36 34 22 32 37 35 21 31 37 35 19 28 34 32 18 26 31 30 27 30 28 26 31 29 25 32 30 24 30 28 22 27 26 20 23 21 20 25 23 20 27 25 19 25 23 18 23 21 57 50 44 42 57 50 44 42 57 50 44 42 53 46 41 39 49 43 38 37 6.7 6.6 6.5 6.5 6.6 6.5 6.4 6.4 6.6 6.5 6.4 6.3 6.5 6.4 6.3 6.3 6.5 6.4 6.3 6.2 86 83 80 77 74 71 68 46 50 44 42 43 50 44 42 41 50 44 42 37 45 41 39 33 40 38 37 39 50 44 42 38 47 44 42 36 45 44 42 32 41 41 39 28 36 38 37 33 43 44 42 32 42 44 42 30 40 44 42 27 36 39 38 24 32 35 34 27 37 38 36 26 36 38 36 25 34 38 37 23 31 35 33 20 28 31 30 20 31 31 30 20 30 32 31 20 29 33 32 18 26 30 29 16 24 27 26 24 25 23 24 26 25 24 28 26 22 25 24 20 23 22 18 19 17 18 20 19 18 22 21 17 21 19 16 19 18 1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE Table, multiply this value by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit. 2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input is 0.36kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor. NOMINAL RATING 14 Unitary Products Group 036-21502-002-A-0303 TABLE 7: DM072 COOLING CAPACITIES (6 TON) TEMPERATURE OF AIR ON CONDENSER COIL AIR ON EVAPORATOR COIL TOTAL INPUT2 kW CFM WB °F CAP.1 MBH 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 80 80 70 68 82 82 71 69 83 83 73 71 79 79 69 67 74 74 65 63 5.7 5.7 5.5 5.6 5.7 5.7 5.5 5.6 5.7 5.7 5.5 5.6 5.7 5.7 5.5 5.6 5.6 5.6 5.4 5.5 2700 2550 2400 2100 1800 85°F 95°F SENSIBLE CAPACITY1 ENTERING DRY BULB, °F POWER TOTAL 86 83 80 77 74 71 68 CAP.1 MBH 63 76 70 68 60 73 71 69 58 70 73 71 54 65 69 67 50 60 65 63 55 68 70 68 53 65 71 69 51 63 73 71 48 59 69 67 44 55 65 63 47 60 70 68 46 58 70 69 44 56 70 71 41 53 66 67 39 50 62 63 40 53 62 60 38 51 62 62 37 49 63 64 35 47 60 61 34 44 57 58 32 45 55 52 31 43 55 55 30 42 56 57 29 40 54 54 28 39 51 52 37 47 45 36 48 47 35 49 50 34 47 48 34 46 47 30 39 37 29 41 40 28 42 43 28 41 42 28 41 42 77 77 71 71 76 76 70 70 75 75 69 69 73 73 67 67 71 71 65 65 SENSIBLE CAPACITY1 ENTERING DRY BULB, °F POWER INPUT2 kW 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.2 6.3 86 83 80 77 74 71 68 63 75 71 71 60 73 70 70 58 70 69 69 53 65 67 67 49 59 65 65 55 68 71 71 53 66 70 70 51 64 69 69 47 59 66 66 43 54 63 63 47 60 71 71 46 58 69 70 44 57 68 68 41 52 63 63 38 48 58 58 40 53 63 63 39 51 62 62 37 50 61 61 35 46 57 57 33 43 53 53 32 45 56 56 31 44 55 55 30 43 54 54 29 40 51 51 27 38 47 47 37 48 48 36 48 48 36 47 47 34 45 45 32 42 42 30 40 40 29 40 40 29 40 40 28 38 39 27 37 37 TEMPERATURE OF AIR ON CONDENSER COIL AIR ON EVAPORATOR COIL 105°F TOTAL 1 CFM 2700 2550 2400 2100 1800 POWER CAP. MBH INPUT2 kW WB °F 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 76 71 64 64 76 71 64 64 75 70 64 64 73 68 61 61 70 65 59 59 7.1 7.1 7.0 7.0 7.1 7.1 7.0 7.0 7.1 7.1 7.0 7.0 7.1 7.1 7.0 7.0 7.1 7.0 7.0 6.9 115°F SENSIBLE CAPACITY1 ENTERING DRY BULB, °F TOTAL 1 SENSIBLE CAPACITY1 ENTERING DRY BULB, °F POWER 83 80 77 74 71 68 CAP. MBH INPUT2 kW 86 61 70 64 64 59 69 64 64 56 68 64 64 52 63 61 61 47 57 59 59 53 66 64 64 51 64 64 64 49 61 64 64 45 56 61 61 41 51 58 58 45 58 64 64 44 56 64 64 43 54 63 63 39 50 58 58 36 46 54 53 38 50 56 56 37 49 56 56 36 48 56 56 33 44 52 52 31 41 48 48 30 43 49 49 29 42 49 49 29 41 49 49 27 38 46 46 25 35 43 43 35 41 41 34 42 42 34 42 42 32 40 40 30 38 37 27 34 34 27 35 34 27 35 35 26 34 34 25 32 32 75 65 57 57 76 66 58 58 76 66 59 59 73 63 56 56 69 60 53 53 7.9 7.8 7.8 7.7 7.9 7.9 7.8 7.7 8.0 7.9 7.8 7.7 7.9 7.8 7.7 7.7 7.8 7.8 7.7 7.6 86 83 80 77 74 71 68 59 65 57 57 57 66 58 58 55 66 59 59 50 61 56 56 45 55 53 53 51 64 57 57 49 61 58 58 48 59 59 59 44 54 56 56 40 49 53 53 43 56 57 57 42 54 58 58 41 52 59 58 37 48 54 53 34 44 49 49 36 48 50 50 35 47 51 50 34 45 52 51 31 42 48 47 29 39 44 44 28 41 42 42 27 40 43 43 27 38 45 44 25 36 42 41 23 33 39 38 33 34 34 32 36 36 32 38 37 30 35 35 28 33 33 25 27 27 25 29 29 25 31 30 24 29 29 23 28 27 1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE Table, multiply this value by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit. 2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input is 0.36kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor. NOMINAL RATING Unitary Products Group 15 036-21502-002-A-0303 TABLE 8: SUPPLY AIR BLOWER PERFORMANCE (3 TON BELT DRIVE) - SIDE DUCT APPLICATION UNIT SIZE (MBH) 0361 2 UNIT SIZE (MBH) 0361 2 AVAILABLE EXTERNAL STATIC PRESSURE-IWG3 0.60 0.40 0.50 AIR FLOW CFM RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM 1700 835 705 880 745 923 795 969 860 1013 970 - - - - 1600 811 655 854 695 898 740 942 790 986 840 1029 900 - - 1500 782 610 827 650 871 685 917 730 960 775 1003 825 1046 905 1400 - - 798 595 844 640 889 680 932 720 975 765 1018 790 1300 - - - - 816 590 862 635 907 675 951 715 995 750 1200 - - - - - - 834 585 881 630 927 665 970 705 1100 - - - - - - 809 550 855 590 900 625 942 665 1000 - - - - - - 782 510 829 545 872 858 919 625 900 - - - - - - - - 797 500 843 540 890 580 0.20 0.30 0.70 AVAILABLE EXTERNAL STATIC PRESSURE-IWG3 1.10 1.20 1.30 0.80 WATTS AIR FLOW CFM RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 1700 - - - - - - - - - - - - - - 1600 - - - - - - - - - - - - - - 1500 - - - - - - - - - - - - - - 1400 1055 875 - - - - - - - - - - - - 1300 1036 780 1066 850 - - - - - - - - - - 1200 1011 735 1047 765 1075 800 - - - - - - - - 1100 987 690 1028 720 1060 750 1084 775 - - - - - - 1000 963 655 1005 680 1040 695 1068 715 1089 735 - - - - 900 936 615 980 645 1020 660 1050 670 1053 680 1090 690 - - 0.90 1.00 1.40 1.50 1. 230/460/575 Volts 2. For 208 Volts multiply values by 0.95. 3. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to ACCESSORY STATIC RESISTANCE Table for resistance values on applications other than gas / electric units with side duct airflows. 16 Unitary Products Group 036-21502-002-A-0303 TABLE 9: SUPPLY AIR BLOWER PERFORMANCE (4 TON BELT DRIVE) - SIDE DUCT APPLICATION UNIT SIZE (MBH) 0481 2 UNIT SIZE (MBH) 0481 2 AVAILABLE EXTERNAL STATIC PRESSURE-IWG3 0.60 0.40 0.50 AIR FLOW CFM RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 2000 843 860 880 925 919 1005 956 1065 993 1145 1030 1195 1067 1235 1900 817 775 854 850 893 920 930 995 970 1065 1008 1125 1046 1170 1800 790 700 828 760 867 840 906 905 944 980 985 1040 1025 1100 1700 - - 802 670 840 745 881 815 920 900 961 970 1001 1030 1600 - - - - 818 665 858 740 898 820 940 890 980 950 1500 - - - - - - 842 695 882 755 922 835 962 895 1400 - - - - - - 833 650 867 705 904 765 942 820 1300 - - - - - - - - 858 665 893 725 932 785 1200 - - - - - - - - 847 640 880 680 916 730 0.20 0.30 0.70 AVAILABLE EXTERNAL STATIC PRESSURE-IWG3 1.10 1.20 1.30 0.80 AIR FLOW CFM RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 2000 1103 1270 - - - - - - - - - - - - 1900 1085 1210 - - - - - - - - - - - - 1800 1064 1145 1102 1180 - - - - - - - - - - 1700 1040 1075 1081 1115 1121 1140 - - - - - - - - 1600 1020 1005 1060 1050 1100 1085 - - - - - - - - 1500 1003 945 1044 995 1086 1035 - - - - - - - - 1400 982 880 1024 920 1067 965 1107 1000 - - - - - - 1300 970 835 1010 870 1053 920 1099 960 - - - - - - 1200 953 780 992 815 1034 855 1080 905 - - - - - - 0.90 1.00 1.40 1.50 1. 230/460/575 Volts 2. For 208 Volts multiply values by 0.95. 3. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to ACCESSORY STATIC RESISTANCE Table for resistance values on applications other than gas / electric units with side duct airflows. Unitary Products Group 17 036-21502-002-A-0303 TABLE 10: SUPPLY AIR BLOWER PERFORMANCE (5 TON BELT DRIVE) - SIDE DUCT APPLICATION UNIT SIZE (MBH) 0601 2 UNIT SIZE (MBH) 0601 2 AVAILABLE EXTERNAL STATIC PRESSURE-IWG3 0.60 0.40 0.50 AIR FLOW CFM RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 2500 1059 1560 1077 1590 1095 1630 1114 1650 1134 1660 1158 1685 1181 1720 2400 1032 1405 1054 1470 1074 1525 1094 1560 1116 1595 1140 1620 1167 1640 2300 1005 1260 1024 1275 1049 1370 1069 1440 1090 1475 1116 1505 1142 1535 2200 980 1160 1002 1170 1022 1190 1044 1250 1066 1350 1090 1410 1117 1440 2100 930 1060 957 1070 983 1080 1010 1100 1039 1160 1064 1260 1092 1340 2000 877 950 908 975 941 1000 976 1020 1009 1050 1040 1100 1070 1225 1900 - - - - 894 885 940 940 980 980 1014 1020 1047 1095 1800 - - - - 855 815 903 860 950 905 988 940 1022 970 1700 - - - - - - 884 815 925 850 964 880 1001 910 1600 - - - - - - 864 770 908 805 948 835 987 870 1500 - - - - - - - - 882 740 926 780 965 830 0.20 0.30 0.70 AVAILABLE EXTERNAL STATIC PRESSURE-IWG3 1.10 1.20 1.30 0.80 AIR FLOW CFM RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 2500 - - - - - - - - - - - - - - 2400 1193 1665 - - - - - - - - - - - - 2300 1170 1580 1202 1620 - - - - - - - - - - 2200 1148 1480 1180 1530 - - - - - - - - - - 2100 1121 1385 1155 1425 1190 1475 - - - - - - - - 2000 1100 1285 1133 1340 1169 1385 1205 1445 - - - - - - 1900 1079 1180 1110 1240 1143 1280 1178 1330 1222 1375 - - - - 1800 1058 1060 1090 1135 1122 1190 1158 1240 1196 1295 - - - - 1700 1035 960 1071 1030 1103 1100 1134 1140 1164 1175 1197 1205 - - 1600 1020 900 1056 965 1088 1035 1118 1065 1145 1105 1170 1130 1198 1150 1500 1004 860 1038 880 1070 925 1101 980 1130 1045 1158 1075 1184 1110 0.90 1.00 1.40 1.50 1. 230/460/575 Volts 2. For 208 Volts multiply values by 0.95. 3. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to ACCESSORY STATIC RESISTANCE Table for resistance values on applications other than gas / electric units with side duct airflows. 18 Unitary Products Group 036-21502-002-A-0303 TABLE 11: SUPPLY AIR BLOWER PERFORMANCE (6 TON BELT DRIVE) - SIDE DUCT APPLICATION UNIT SIZE (MBH) 12 072 UNIT SIZE (MBH) 12 072 AVAILABLE EXTERNAL STATIC PRESSURE-IWG3 0.60 0.40 0.50 AIR FLOW CFM RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM 3200 1150 2325 1182 2425 1212 2525 - - - - - - - - 3000 1100 2010 1129 2090 1157 2150 1185 2225 1215 2290 1242 2360 - - 2800 1045 1700 1074 1780 1102 1850 1131 1940 1160 2025 1190 2075 1217 2130 2600 985 1425 1015 1475 1045 1540 1075 1630 1103 1715 1135 1760 1163 1825 2400 930 1240 958 1300 990 1350 1020 1400 1051 1430 1081 1490 1111 1600 2200 - - 905 1070 933 1160 965 1210 997 1250 1028 1285 1060 1325 2000 - - - - - - 919 1025 950 1100 982 1130 1014 1160 1800 - - - - - - - - 909 925 939 1005 968 1030 0.20 0.30 0.70 AVAILABLE EXTERNAL STATIC PRESSURE-IWG3 1.10 1.20 1.30 0.80 WATTS AIR FLOW CFM RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 3200 - - - - - - - - - - - - - - 3000 - - - - - - - - - - - - - - 2800 1245 2190 - - - - - - - - - - - - 2600 1193 1920 1222 1990 1250 2060 - - - - - - - - 2400 1142 1675 1173 1730 1205 1800 1234 1885 - - - - - - 2200 1090 1380 1124 1450 1155 1550 1186 1640 1217 1710 1249 1775 - - 2000 1045 1175 1077 1200 1109 1275 1140 1360 1170 1460 1205 1545 1235 1600 1800 998 1050 1028 1060 1058 1060 1087 1075 1118 1150 1148 1250 1176 1360 0.90 1.00 1.40 1.50 1. 230/460/575 Volts 2. For 208 Volts multiply values by 0.95. 3. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to ACCESSORY STATIC RESISTANCE Table for resistance values on applications other than gas / electric units with side duct airflows. Unitary Products Group 19 036-21502-002-A-0303 TABLE 12: SUPPLY AIR BLOWER PERFORMANCE (3 - 6 TON DIRECT DRIVE) - SIDE DUCT APPLICATION UNIT SIZE (MBH) AVAILABLE EXTERNAL STATIC PRESSURE-IWG2 MOTOR SPEED 0361 0481 0601 0721 UNIT SIZE (MBH) 0.20 0481 0601 0721 0.40 0.50 0.60 WATTS CFM WATTS CFM WATTS CFM WATTS CFM HI - - - - 1699 825 1650 785 1570 755 MED 1684 800 1631 780 1582 750 1524 720 1410 690 LOW 1487 710 1464 690 1421 670 1367 650 1315 620 HI 1996 960 1933 936 1868 910 1795 880 1722 845 MED 1804 838 1765 810 1714 785 1650 765 1589 735 LOW 1681 760 1640 738 1604 715 1541 695 1490 670 HI 2400 1155 2338 1125 2274 1095 2167 1045 2096 1010 WATTS 950 MED 2290 1105 2214 1065 2145 1030 2071 990 1990 LOW 2150 1020 2100 990 2029 950 1965 910 1905 880 HI 2461 1480 2402 1440 2361 1395 2260 1350 2178 1305 MOTOR SPEED 0361 0.30 CFM AVAILABLE EXTERNAL STATIC PRESSURE-IWG2 0.80 0.90 0.70 1.00 CFM WATTS CFM WATTS CFM WATTS CFM WATTS HI 1430 725 1360 700 1280 680 1180 655 MED 1324 650 1260 630 1185 610 1100 590 LOW 1246 605 1185 590 1110 570 1020 545 HI 1635 820 1544 790 1419 765 1300 740 MED 1508 705 1407 675 1306 645 1195 625 LOW 1416 645 1337 620 1230 595 1120 575 HI 1990 980 1887 945 1771 905 1629 855 MED 1911 920 1828 885 1724 835 1604 798 LOW 1816 838 1724 800 1644 770 1531 710 HI 2101 1260 2000 1205 1914 1155 1830 1110 1. Side Duct application (230/460/575 Volts) 2. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCES Table for resistance values TABLE 13: BELT DRIVE BLOWER MOTOR AND DRIVE DATA MOTOR1 ADJUSTABLE MOTOR PULLEY BELT (NOTCHED) FIXED BLOWER PULLEY MODEL SIZE BLOWER RANGE (RPM) HP FRAME DESIGNATION OUTSIDE DIA. (IN.) PITCH DIA. (IN.) BORE (IN.) DESIGNATION OUTSIDE DIA. (IN.) PITCH DIA. (IN.) BORE (IN.) DESIGNATION PITCH LENGTH (IN.) QTY. 3 TON 790/1120 1 1/2 56 1VL40 2.7-3.7 2.4-3.4 5/8 AK61 5.9 5.7 1 A36 37.3 1 4 TON 790/1120 1 1/2 56 1VL40 2.7-3.7 2.4-3.4 5/8 AK61 5.9 5.7 1 A36 37.3 1 5 TON 850/1220 1 1/2 56 1VL40 2.7-3.7 2.4-3.4 5/8 AK56 5.4 5.2 1 A36 37.3 1 6 TON 900/1250 1 1/2 56 1VL44 3.1-4.1 2.8-3.8 7/8 AK56 5.4 5.2 1 A36 37.3 1 1. All motors have solid bases and are inherently protected. these motors can be selected to operate into their service factor because they are located in the moving air, upstream of any heating device. 20 Unitary Products Group 036-21502-002-A-0303 TABLE 14: STATIC RESISTANCES RESISTANCE, IWG DESCRIPTION CFM 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800 0.07 0.08 0.09 0.11 0.13 0.15 0.17 0.20 0.23 0.26 0.30 5-15KW 0.04 0.05 0.06 0.07 0.08 0.10 0.12 0.14 0.16 0.19 0.22 20-30KW ECONOMIZER1 2 ELECTRIC HEATERS3 3000 0.06 0.07 0.08 0.09 0.11 0.13 0.15 0.17 0.20 0.23 0.26 BOTTOM DUCT CONNECTIONS1 0.06 0.07 0.08 0.09 0.10 0.11 0.12 0.14 0.16 0.19 0.22 COOLING ONLY2 0.08 0.10 0.12 0.14 0.16 0.18 0.20 0.23 0.26 0.29 0.32 1. Deduct these resistance values from the available external static pressure shown in SUPPLY AIR BLOWER PERFORMANCE Tables. 2. The pressure through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation. 3. Add these resistance values to the available static resistance values on SUPPLY AIR BLOWER PERFORMANCE Tables. TABLE 15: ELECTRIC HEATER CFM LIMITATIONS UNIT MODEL SIZE NOMINAL TONS 3 4 5 6 Unitary Products Group MINIMUM SUPPLY AIR CFM VOLTAGE HEATER SIZE NOMINAL KW 5 7 10 15 20 30 208/230-1-60 1100 1100 1200 1200 1300 - 208/230-3-60 1100 1100 1200 1200 1300 - 460-3-60 - 1100 1200 1200 1300 - 575-3-60 - - 1200 1200 1300 - 208/230-1-60 1300 1300 1300 1300 1300 - 208/230-3-60 1300 1300 1300 1300 1300 - 460-3-60 - 1300 1300 1300 1300 - 575-3-60 - - 1300 1300 1400 - 208/230-1-60 1600 1600 1600 1600 1600 1600 208/230-3-60 1600 1600 1600 1600 1600 1600 460-3-60 - 1600 1600 1600 1600 1600 575-3-60 - - 1600 1600 1600 1800 208/230-1-60 1800 1800 1800 1800 1800 1800 208/230-3-60 1800 1800 1800 1800 1800 1800 460-3-60 - 1800 1800 1800 1800 1800 575-3-60 - - 1800 1800 1800 1800 21 036-21502-002-A-0303 TABLE 16: ELECTRICAL DATA - DM036 & 048 DIRECT DRIVE WITHOUT POWR’D CONVENIENCE OUTLET Model Tonnage Compressors Voltage RLA Each LRA Each OD Fan Motor FLA ID Blower Motor FLA Conv Outlet Amps 208-1-60 19.2 87 2.3 4.4 0.0 230-1-60 19.2 87 2.3 4.4 0.0 208-3-60 14.1 110 2.3 4.4 0.0 230-3-60 14.1 110 2.3 4.4 0.0 460-3-60 7.1 54 1.3 2.2 0.0 575-3-60 5.8 44 1.3 2.2 0.0 208-1-60 25.0 135 2.3 5.0 0.0 230-1-60 25.0 135 2.3 5.0 0.0 208-3-60 14.7 130 2.3 5.0 0.0 230-3-60 14.7 130 2.3 5.0 0.0 460-3-60 7.7 64 1.3 2.2 0.0 575-3-60 6.4 52 1.3 2.2 0.0 3 4 Electric Heater Model No. Heater kW Heater Amps Minimum Circuit Ampacity Amps Max Fuse / 1 BRKR Size Amps NONE 2CE04510506 2CE04510706 2CE04511006 2CE04511506 2CE04512006 NONE 2CE04510506 2CE04510706 2CE04511006 2CE04511506 2CE04512006 NONE 2CE04510525 2 2CE04510725 2 2CE04511025 2CE04511525 2CE04512025 NONE 2CE04510525 2CE04510525 2 2 2CE04510725 2CE04511525 2CE04512025 NONE 2CE04510746 2 2CE04511046 2 2 2CE04511546 2 2CE04512046 NONE 2CE04511058 2CE04511558 2CE04512058 NONE 2CE04510506 2CE04510706 2CE04511006 2CE04511506 2CE04512006 NONE 2CE04510506 2CE04510706 2CE04511006 2CE04511506 2CE04512006 NONE 2CE04510525 2 2 2CE04510725 2CE04511025 2CE04511525 2CE04512025 NONE 2CE04510525 2 2 2CE04510725 2CE04511025 2CE04511525 2CE04512025 NONE 2CE04510746 2 2CE04511046 2 2CE04511546 2 2 2CE04512046 NONE 2CE04511058 2CE04511558 2CE04512058 0.0 4.0 5.6 8.0 11.9 15.9 0.0 5.3 7.5 10.6 15.9 21.2 0.0 4.0 5.6 8.0 11.9 15.9 0.0 5.3 7.5 10.6 15.9 21.2 0.0 6.8 10.1 13.6 19.5 0.0 10.6 15.9 21.2 0.0 4.0 5.6 8.0 11.9 15.9 0.0 5.3 7.5 10.6 15.9 21.2 0.0 4.0 5.6 8.0 11.9 15.9 0.0 5.3 7.5 10.6 15.9 21.2 0.0 6.8 10.1 13.6 19.5 0.0 10.6 15.9 21.2 0.0 19.2 26.9 38.5 57.2 76.4 0.0 22.1 31.3 44.2 66.3 88.3 0.0 11.1 15.5 22.2 33.0 44.1 0.0 12.7 18.0 25.5 38.2 51.0 0.0 8.2 12.1 16.4 23.5 0.0 10.2 15.3 20.4 0.0 19.2 26.9 38.5 57.2 76.4 0.0 22.1 31.3 44.2 66.3 88.3 0.0 11.1 15.5 22.2 33.0 44.1 0.0 12.7 18.0 25.5 38.2 51.0 0.0 8.2 12.1 16.4 23.5 0.0 10.2 15.3 20.4 30.7 30.7 39.2 53.6 77.0 101.1 30.7 33.1 44.6 60.7 88.3 115.9 24.3 24.3 24.9 33.3 46.8 60.7 24.3 24.3 28.1 37.4 53.3 69.2 12.4 13.0 17.9 23.2 32.1 10.1 14.9 21.3 27.7 38.5 38.5 39.9 54.3 77.8 101.8 38.5 38.5 45.3 61.5 89.1 116.7 25.7 25.7 25.7 34.0 47.5 61.4 25.7 25.7 28.8 38.1 54.1 70.0 13.1 13.1 17.9 23.2 32.1 10.8 14.9 21.3 27.7 45 45 45 60 80 110 45 45 45 70 90 125 35 35 35 35 50 70 35 35 35 40 60 70 15 15 20 25 35 15 15 25 30 60 60 60 60 80 110 60 60 60 70 90 125 40 40 40 40 50 70 40 40 40 40 60 70 20 20 20 25 35 15 15 25 30 1. HACR Type per NEC. 2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories 2FB04700825 and 2FB04700846 are available for field installation. 22 Unitary Products Group 036-21502-002-A-0303 TABLE 17: ELECTRICAL DATA - DM060 & 072 DIRECT DRIVE WITHOUT POWR’D CONVENIENCE OUTLET Model Tonnage Compressors Voltage RLA Each LRA Each OD Fan Motor FLA ID Blower Motor FLA Conv Outlet Amps 208-1-60 28.9 165 1.3 6.6 0.0 230-1-60 28.9 165 1.3 6.6 0.0 208-3-60 16.0 125 1.3 6.6 0.0 230-3-60 16.0 125 1.3 6.6 0.0 460-3-60 8.0 66.5 0.8 3.3 0.0 575-3-60 6.4 50 0.8 3.3 0.0 208-3-60 18.9 146 1.3 6.8 0.0 230-3-60 18.9 146 1.3 6.8 0.0 460-3-60 9.5 73 0.8 3.6 0.0 575-3-60 7.6 58.4 0.8 3.6 0.0 5 6 Electric Heater Model No. Heater kW Heater Amps Minimum Circuit Ampacity Amps NONE 2CE04510506 2CE04510706 2CE04511006 2CE04511506 2CE04512006 2CE04513006 NONE 2CE04510506 2CE04510706 2CE04511006 2CE04511506 2CE04512006 2CE04513006 NONE 2CE04510525 2 2 2CE04510725 2CE04511025 2CE04511525 2CE04512025 2CE04513025 NONE 2CE04510525 2 2CE04510725 2 2CE04511025 2CE04511525 2CE04512025 2CE04513025 NONE 2CE04510746 2 2CE04511046 2 2 2CE04511546 2CE04512046 2 2CE04513046 2 NONE 2CE04511058 2CE04511558 2CE04512058 2CE04513058 NONE 2CE04510525 2 2CE04510725 2 2CE04511025 2CE04511525 2CE04512025 2CE04513025 NONE 2CE04510525 2 2 2CE04510725 2CE04511025 2CE04511525 2CE04512025 2CE04513025 NONE 2CE04510746 2 2 2CE04511046 2CE04511546 2 2 2CE04512046 2CE04513046 2 NONE 2CE04511058 2CE04511558 2CE04512058 2CE04513058 0.0 4.0 5.6 8.0 11.9 15.9 22.2 0.0 5.3 7.5 10.6 15.9 21.2 29.6 0.0 4.0 5.6 8.0 11.9 15.9 22.2 0.0 5.3 7.5 10.6 15.9 21.2 29.6 0.0 6.8 10.1 13.6 19.5 28.8 0.0 10.6 15.9 21.2 30.4 0.0 4.0 5.6 8.0 11.9 15.9 22.2 0.0 5.3 7.5 10.6 15.9 21.2 29.6 0.0 6.8 10.1 13.6 19.5 28.8 0.0 10.6 15.9 21.2 30.4 0.0 19.2 26.9 38.5 57.2 76.4 106.7 0.0 22.1 31.3 44.2 66.3 88.3 123.3 0.0 11.1 15.5 22.2 33.0 44.1 61.6 0.0 12.7 18.0 25.5 38.2 51.0 71.2 0.0 8.2 12.1 16.4 23.5 34.6 0.0 10.2 15.3 20.4 29.3 0.0 11.1 15.5 22.2 33.0 44.1 61.6 0.0 12.7 18.0 25.5 38.2 51.0 71.2 0.0 8.2 12.1 16.4 23.5 34.6 0.0 10.2 15.3 20.4 29.3 44.0 44.0 44.0 56.3 79.8 103.8 141.7 44.0 44.0 47.3 63.5 91.1 118.7 162.4 27.9 27.9 27.9 36.0 49.5 63.4 85.3 27.9 27.9 30.8 40.1 56.1 72.0 97.3 14.1 14.3 19.3 24.6 33.4 47.4 11.3 16.0 22.4 28.8 39.9 31.7 31.7 31.7 36.3 49.8 63.7 85.5 31.7 31.7 31.7 40.4 56.3 72.2 97.5 16.3 16.3 19.7 24.9 33.8 47.8 13.0 16.3 22.7 29.1 40.2 Max Fuse / BRKR1 Size Amps 70 70 70 70 80 110 150 70 70 70 70 100 125 175 40 40 40 40 50 70 90 40 40 40 45 60 80 100 20 20 20 25 35 50 15 20 25 30 40 50 50 50 50 50 70 90 50 50 50 50 60 80 100 25 25 25 25 35 50 15 20 25 30 40 1. HACR Type per NEC. 2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories 2FB04700825 and 2FB04700846 are available for field installation. Unitary Products Group 23 036-21502-002-A-0303 TABLE 18: ELECTRICAL DATA - DM036 & 048 BELT DRIVE WITHOUT POWR’D CONVENIENCE OUTLET Model Tonnage Compressors Voltage RLA Each LRA Each OD Fan Motor FLA ID Blower Motor FLA Conv Outlet Amps 208-1-60 18.0 105 1.3 7.6 0.0 230-1-60 18.0 105 1.3 7.6 0.0 208-3-60 11.4 90 1.3 5.2 0.0 230-3-60 11.4 90 1.3 5.2 0.0 460-3-60 6.2 45 0.8 2.6 0.0 575-3-60 5.0 36 0.8 2 0.0 208-1-60 24.4 140 1.3 7.6 0.0 230-1-60 24.4 140 1.3 7.6 0.0 208-3-60 14.1 105 1.3 5.2 0.0 230-3-60 14.1 105 1.3 5.2 0.0 460-3-60 7.1 55 0.8 2.6 0.0 575-3-60 5.8 44 0.8 2 0.0 3 4 Electric Heater Model No. Heater kW Heater Amps Minimum Circuit Ampacity Amps NONE 2CE04510506 2CE04510706 2CE04511006 2CE04511506 2CE04512006 NONE 2CE04510506 2CE04510706 2CE04511006 2CE04511506 2CE04512006 NONE 2 2CE04510525 2 2CE04510725 2CE04511025 2CE04511525 2CE04512025 NONE 2 2CE04510525 2CE04510725 2 2CE04511025 2CE04511525 2CE04512025 NONE 2 2CE04510746 2 2CE04511046 2 2CE04511546 2 2CE04512046 NONE 2CE04511058 2CE04511558 2CE04512058 NONE 2CE04510506 2CE04510706 2CE04511006 2CE04511506 2CE04512006 NONE 2CE04510506 2CE04510706 2CE04511006 2CE04511506 2CE04512006 NONE 2 2CE04510525 2CE04510725 2 2CE04511025 2CE04511525 2CE04512025 NONE 2 2CE04510525 2 2CE04510725 2CE04511025 2CE04511525 2CE04512025 NONE 2 2CE04510746 2CE04511046 2 2 2CE04511546 2 2CE04512046 NONE 2CE04511058 2CE04511558 2CE04512058 0.0 4.0 5.6 8.0 11.9 15.9 0.0 5.3 7.5 10.6 15.9 21.2 0.0 4.0 5.6 8.0 11.9 15.9 0.0 5.3 7.5 10.6 15.9 21.2 0.0 6.8 10.1 13.6 19.5 0.0 10.6 15.9 21.2 0.0 4.0 5.6 8.0 11.9 15.9 0.0 5.3 7.5 10.6 15.9 21.2 0.0 4.0 5.6 8.0 11.9 15.9 0.0 5.3 7.5 10.6 15.9 21.2 0.0 6.8 10.1 13.6 19.5 0.0 10.6 15.9 21.2 0.0 19.2 26.9 38.5 57.2 76.4 0.0 22.1 31.3 44.2 66.3 88.3 0.0 11.1 15.5 22.2 33.0 44.1 0.0 12.7 18.0 25.5 38.2 51.0 0.0 8.2 12.1 16.4 23.5 0.0 10.2 15.3 20.4 0.0 19.2 26.9 38.5 57.2 76.4 0.0 22.1 31.3 44.2 66.3 88.3 0.0 11.1 15.5 22.2 33.0 44.1 0.0 12.7 18.0 25.5 38.2 51.0 0.0 8.2 12.1 16.4 23.5 0.0 10.2 15.3 20.4 31.4 33.5 43.2 57.6 81.0 105.1 31.4 37.1 48.6 64.7 92.3 119.9 20.8 20.8 25.9 34.3 47.8 61.7 20.8 22.4 29.1 38.4 54.3 70.2 11.1 13.5 18.4 23.7 32.6 8.5 14.7 21.1 27.5 39.4 39.4 43.2 57.6 81.0 105.1 39.4 39.4 48.6 64.7 92.3 119.9 24.1 24.1 25.9 34.3 47.8 61.7 24.1 24.1 29.1 38.4 54.3 70.2 12.3 13.5 18.4 23.7 32.6 9.5 14.7 21.1 27.5 Max Fuse / BRKR1 Size Amps 45 45 45 60 90 110 45 45 50 70 100 125 30 30 30 35 50 70 30 30 30 40 60 80 15 15 20 25 35 15 15 25 30 60 60 60 60 90 110 60 60 60 70 100 125 35 35 35 35 50 70 35 35 35 40 60 80 15 15 20 25 35 15 15 25 30 1. HACR Type per NEC. 2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories 2FB04700825 and 2FB04700846 are available for field installation. 24 Unitary Products Group 036-21502-002-A-0303 TABLE 19: ELECTRICAL DATA - DM060 & 072 BELT DRIVE WITHOUT POWR’D CONVENIENCE OUTLET Model Tonnage Compressors Voltage RLA Each LRA Each OD Fan Motor FLA ID Blower Motor FLA Conv Outlet Amps 208-1-60 28.9 165 1.3 7.6 0.0 230-1-60 28.9 165 1.3 7.6 0.0 208-3-60 16.0 125 1.3 5.2 0.0 230-3-60 16.0 125 1.3 5.2 0.0 460-3-60 8.0 66.5 0.8 2.6 0.0 575-3-60 6.4 50 0.8 2 0.0 208-3-60 18.9 146 1.3 5.0 0.0 230-3-60 18.9 146 1.3 5.0 0.0 460-3-60 9.5 73 0.8 2.5 0.0 575-3-60 7.6 58.4 0.8 2 0.0 5 6 Electric Heater Model No. Heater kW Heater Amps Minimum Circuit Ampacity Amps NONE 2CE04510506 2CE04510706 2CE04511006 2CE04511506 2CE04512006 2CE04513006 NONE 2CE04510506 2CE04510706 2CE04511006 2CE04511506 2CE04512006 2CE04513006 NONE 2CE04510525 2 2CE04510725 2 2CE04511025 2CE04511525 2CE04512025 2CE04513025 NONE 2CE04510525 2 2CE04510725 2 2CE04511025 2CE04511525 2CE04512025 2CE04513025 NONE 2CE04510746 2 2CE04511046 2 2CE04511546 2 2 2CE04512046 2CE04513046 2 NONE 2CE04511058 2CE04511558 2CE04512058 2CE04513058 NONE 2CE04510525 2 2CE04510725 2 2CE04511025 2CE04511525 2CE04512025 2CE04513025 NONE 2CE04510525 2 2 2CE04510725 2CE04511025 2CE04511525 2CE04512025 2CE04513025 NONE 2CE04510746 2 2CE04511046 2 2CE04511546 2 2 2CE04512046 2 2CE04513046 NONE 2CE04511058 2CE04511558 2CE04512058 2CE04513058 0.0 4.0 5.6 8.0 11.9 15.9 22.2 0.0 5.3 7.5 10.6 15.9 21.2 29.6 0.0 4.0 5.6 8.0 11.9 15.9 22.2 0.0 5.3 7.5 10.6 15.9 21.2 29.6 0.0 6.8 10.1 13.6 19.5 28.8 0.0 10.6 15.9 21.2 30.4 0.0 4.0 5.6 8.0 11.9 15.9 22.2 0.0 5.3 7.5 10.6 15.9 21.2 29.6 0.0 6.8 10.1 13.6 19.5 28.8 0.0 10.6 15.9 21.2 30.4 0.0 19.2 26.9 38.5 57.2 76.4 106.7 0.0 22.1 31.3 44.2 66.3 88.3 123.3 0.0 11.1 15.5 22.2 33.0 44.1 61.6 0.0 12.7 18.0 25.5 38.2 51.0 71.2 0.0 8.2 12.1 16.4 23.5 34.6 0.0 10.2 15.3 20.4 29.3 0.0 11.1 15.5 22.2 33.0 44.1 61.6 0.0 12.7 18.0 25.5 38.2 51.0 71.2 0.0 8.2 12.1 16.4 23.5 34.6 0.0 10.2 15.3 20.4 29.3 45.0 45.0 45.0 57.6 81.0 105.1 142.9 45.0 45.0 48.6 64.7 92.3 119.9 163.7 26.5 26.5 26.5 34.3 47.8 61.7 83.5 26.5 26.5 29.1 38.4 54.3 70.2 95.5 13.4 13.5 18.4 23.7 32.6 46.6 10.2 14.7 21.1 27.5 38.6 29.9 29.9 29.9 34.0 47.5 61.4 83.3 29.9 29.9 29.9 38.1 54.1 70.0 95.3 15.2 15.2 18.3 23.6 32.4 46.4 11.7 14.7 21.1 27.5 38.6 Max Fuse / BRKR1 Size Amps 70 70 70 70 90 110 150 70 70 70 70 100 125 175 40 40 40 40 50 70 90 40 40 40 40 60 80 100 20 20 20 25 35 50 15 15 25 30 40 45 45 45 45 50 70 90 45 45 45 45 60 70 100 20 20 20 25 35 50 15 15 25 30 40 1. HACR Type per NEC. 2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories 2FB04700825 and 2FB04700846 are available for field installation. Unitary Products Group 25 036-21502-002-A-0303 TABLE 20: ELECTRICAL DATA - DM036 & 048 DIRECT DRIVE WITH POWR’D CONVENIENCE OUTLET Model Tonnage Compressors Voltage RLA Each LRA Each OD Fan Motor FLA ID Blower Motor FLA Conv Outlet Amps 208-1-60 18.0 105 1.3 4.4 10.0 230-1-60 18.0 105 1.3 4.4 10.0 208-3-60 11.4 90 1.3 4.4 10.0 230-3-60 11.4 90 1.3 4.4 10.0 460-3-60 6.2 45 0.8 2.2 5.0 575-3-60 5.0 36 0.8 2.2 4.0 208-1-60 24.4 140 1.3 5.0 10.0 230-1-60 24.4 140 1.3 5.0 10.0 208-3-60 14.1 105 1.3 5.0 10.0 230-3-60 14.1 105 1.3 5.0 10.0 460-3-60 7.1 55 0.8 2.2 5.0 575-3-60 5.8 44 0.8 2.2 4.0 3 4 Electric Heater Model No. Heater kW Heater Amps Minimum Circuit Ampacity Amps NONE 2CE04510506 2CE04510706 2CE04511006 2CE04511506 2CE04512006 NONE 2CE04510506 2CE04510706 2CE04511006 2CE04511506 2CE04512006 NONE 2CE04510525 2 2CE04510725 2 2CE04511025 2CE04511525 2CE04512025 NONE 2CE04510525 2 2CE04510725 2 2CE04511025 2CE04511525 2CE04512025 NONE 2CE04510746 2 2CE04511046 2 2CE04511546 2 2CE04512046 2 NONE 2CE04511058 2CE04511558 2CE04512058 NONE 2CE04510506 2CE04510706 2CE04511006 2CE04511506 2CE04512006 NONE 2CE04510506 2CE04510706 2CE04511006 2CE04511506 2CE04512006 NONE 2CE04510525 2 2CE04510725 2 2CE04511025 2CE04511525 2CE04512025 NONE 2CE04510525 2 2 2CE04510725 2CE04511025 2CE04511525 2CE04512025 NONE 2CE04510746 2 2CE04511046 2 2CE04511546 2 2CE04512046 2 NONE 2CE04511058 2CE04511558 2CE04512058 0.0 4.0 5.6 8.0 11.9 15.9 0.0 5.3 7.5 10.6 15.9 21.2 0.0 4.0 5.6 8.0 11.9 15.9 0.0 5.3 7.5 10.6 15.9 21.2 0.0 6.8 10.1 13.6 19.5 0.0 10.6 15.9 21.2 0.0 4.0 5.6 8.0 11.9 15.9 0.0 5.3 7.5 10.6 15.9 21.2 0.0 4.0 5.6 8.0 11.9 15.9 0.0 5.3 7.5 10.6 15.9 21.2 0.0 6.8 10.1 13.6 19.5 0.0 10.6 15.9 21.2 0.0 19.2 26.9 38.5 57.2 76.4 0.0 22.1 31.3 44.2 66.3 88.3 0.0 11.1 15.5 22.2 33.0 44.1 0.0 12.7 18.0 25.5 38.2 51.0 0.0 8.2 12.1 16.4 23.5 0.0 10.2 15.3 20.4 0.0 19.2 26.9 38.5 57.2 76.4 0.0 22.1 31.3 44.2 66.3 88.3 0.0 11.1 15.5 22.2 33.0 44.1 0.0 12.7 18.0 25.5 38.2 51.0 0.0 8.2 12.1 16.4 23.5 0.0 10.2 15.3 20.4 38.2 42.0 51.7 66.1 89.5 113.6 38.2 45.6 57.1 73.2 100.8 128.4 29.9 31.9 37.4 45.8 59.3 73.2 29.9 33.9 40.6 49.9 65.8 81.7 15.8 19.2 24.2 29.4 38.3 12.7 19.9 26.3 32.7 46.8 46.8 52.4 66.8 90.3 114.3 46.8 46.8 57.8 74.0 101.6 129.2 33.9 33.9 38.2 46.5 60.0 73.9 33.9 34.7 41.3 50.6 66.6 82.5 16.9 19.2 24.2 29.4 38.3 13.7 19.9 26.3 32.7 Max Fuse / BRKR1 Size Amps 50 50 60 70 90 125 50 50 60 80 110 150 40 40 40 50 60 80 40 40 45 50 70 90 20 20 25 30 40 15 20 30 35 70 70 70 70 100 125 70 70 70 80 110 150 45 45 45 50 70 80 45 45 45 60 70 90 20 20 25 30 40 15 20 30 35 1. HACR Type per NEC. 2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories 2FB04700825 and 2FB04700846 are available for field installation. 26 Unitary Products Group 036-21502-002-A-0303 TABLE 21: ELECTRICAL DATA - DM060 & 072 DIRECT DRIVE WITH POWR’D CONVENIENCE OUTLET Model Tonnage Compressors Voltage RLA Each LRA Each OD Fan Motor FLA ID Blower Motor FLA Conv Outlet Amps 208-1-60 28.9 165 1.3 6.6 10.0 230-1-60 28.9 165 1.3 6.6 10.0 208-3-60 16.0 125 1.3 6.6 10.0 230-3-60 16.0 125 1.3 6.6 10.0 460-3-60 8.0 66.5 0.8 3.3 5.0 575-3-60 6.4 50 0.8 3.3 4.0 208-3-60 18.9 146 1.3 6.8 10.0 230-3-60 18.9 146 1.3 6.8 10.0 460-3-60 9.5 73 0.8 3.6 5.0 575-3-60 7.6 58.4 0.8 3.6 4.0 5 6 Electric Heater Model No. Heater kW Heater Amps Minimum Circuit Ampacity Amps NONE 2CE04510506 2CE04510706 2CE04511006 2CE04511506 2CE04512006 2CE04513006 NONE 2CE04510506 2CE04510706 2CE04511006 2CE04511506 2CE04512006 2CE04513006 NONE 2CE04510525 2 2 2CE04510725 2CE04511025 2CE04511525 2CE04512025 2CE04513025 NONE 2CE04510525 2 2CE04510725 2 2CE04511025 2CE04511525 2CE04512025 2CE04513025 NONE 2CE04510746 2 2CE04511046 2 2 2CE04511546 2CE04512046 2 2CE04513046 2 NONE 2CE04511058 2CE04511558 2CE04512058 2CE04513058 NONE 2CE04510525 2 2CE04510725 2 2CE04511025 2CE04511525 2CE04512025 2CE04513025 NONE 2CE04510525 2 2 2CE04510725 2CE04511025 2CE04511525 2CE04512025 2CE04513025 NONE 2CE04510746 2 2 2CE04511046 2CE04511546 2 2 2CE04512046 2CE04513046 2 NONE 2CE04511058 2CE04511558 2CE04512058 2CE04513058 0.0 4.0 5.6 8.0 11.9 15.9 22.2 0.0 5.3 7.5 10.6 15.9 21.2 29.6 0.0 4.0 5.6 8.0 11.9 15.9 22.2 0.0 5.3 7.5 10.6 15.9 21.2 29.6 0.0 6.8 10.1 13.6 19.5 28.8 0.0 10.6 15.9 21.2 30.4 0.0 4.0 5.6 8.0 11.9 15.9 22.2 0.0 5.3 7.5 10.6 15.9 21.2 29.6 0.0 6.8 10.1 13.6 19.5 28.8 0.0 10.6 15.9 21.2 30.4 0.0 19.2 26.9 38.5 57.2 76.4 106.7 0.0 22.1 31.3 44.2 66.3 88.3 123.3 0.0 11.1 15.5 22.2 33.0 44.1 61.6 0.0 12.7 18.0 25.5 38.2 51.0 71.2 0.0 8.2 12.1 16.4 23.5 34.6 0.0 10.2 15.3 20.4 29.3 0.0 11.1 15.5 22.2 33.0 44.1 61.6 0.0 12.7 18.0 25.5 38.2 51.0 71.2 0.0 8.2 12.1 16.4 23.5 34.6 0.0 10.2 15.3 20.4 29.3 54.0 54.0 54.4 68.8 92.3 116.3 154.2 54.0 54.0 59.8 76.0 103.6 131.2 174.9 37.9 37.9 40.2 48.5 62.0 75.9 97.8 37.9 37.9 43.3 52.6 68.6 84.5 109.8 19.1 20.6 25.6 30.8 39.7 53.7 15.3 21.0 27.4 33.8 44.9 41.7 41.7 41.7 48.8 62.3 76.2 98.0 41.7 41.7 43.6 52.9 68.8 84.7 110.0 21.3 21.3 25.9 31.2 40.1 54.1 17.0 21.3 27.7 34.1 45.2 Max Fuse / BRKR1 Size Amps 80 80 80 80 100 125 175 80 80 80 80 110 150 175 50 50 50 50 70 80 100 50 50 50 60 70 90 110 25 25 30 35 40 60 20 25 30 35 45 60 60 60 60 70 80 100 60 60 60 60 70 90 125 30 30 30 35 45 60 20 25 30 35 45 1. HACR Type per NEC. 2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories 2FB04700825 and 2FB04700846 are available for field installation. Unitary Products Group 27 036-21502-002-A-0303 TABLE 22: ELECTRICAL DATA - DM036 & 048 BELT DRIVE WITH POWR’D CONVENIENCE OUTLET Model Tonnage Compressors Voltage RLA Each LRA Each OD Fan Motor FLA ID Blower Motor FLA Conv Outlet Amps 208-1-60 18.0 105 1.3 7.6 10.0 230-1-60 18.0 105 1.3 7.6 10.0 208-3-60 11.4 90 1.3 5.2 10.0 230-3-60 11.4 90 1.3 5.2 10.0 460-3-60 6.2 45 0.8 2.6 5.0 575-3-60 5.0 36 0.8 2 4.0 208-1-60 24.4 140 1.3 7.6 10.0 230-1-60 24.4 140 1.3 7.6 10.0 208-3-60 14.1 105 1.3 5.2 10.0 230-3-60 14.1 105 1.3 5.2 10.0 460-3-60 7.1 55 0.8 2.6 5.0 575-3-60 5.8 44 0.8 2 4.0 3 4 Electric Heater Model No. Heater kW Heater Amps Minimum Circuit Ampacity Amps NONE 2CE04510506 2CE04510706 2CE04511006 2CE04511506 2CE04512006 NONE 2CE04510506 2CE04510706 2CE04511006 2CE04511506 2CE04512006 NONE 2 2CE04510525 2 2CE04510725 2CE04511025 2CE04511525 2CE04512025 NONE 2 2CE04510525 2CE04510725 2 2CE04511025 2CE04511525 2CE04512025 NONE 2 2CE04510746 2 2CE04511046 2 2CE04511546 2 2CE04512046 NONE 2CE04511058 2CE04511558 2CE04512058 NONE 2CE04510506 2CE04510706 2CE04511006 2CE04511506 2CE04512006 NONE 2CE04510506 2CE04510706 2CE04511006 2CE04511506 2CE04512006 NONE 2 2CE04510525 2CE04510725 2 2CE04511025 2CE04511525 2CE04512025 NONE 2 2CE04510525 2 2CE04510725 2CE04511025 2CE04511525 2CE04512025 NONE 2 2CE04510746 2CE04511046 2 2 2CE04511546 2 2CE04512046 NONE 2CE04511058 2CE04511558 2CE04512058 0.0 4.0 5.6 8.0 11.9 15.9 0.0 5.3 7.5 10.6 15.9 21.2 0.0 4.0 5.6 8.0 11.9 15.9 0.0 5.3 7.5 10.6 15.9 21.2 0.0 6.8 10.1 13.6 19.5 0.0 10.6 15.9 21.2 0.0 4.0 5.6 8.0 11.9 15.9 0.0 5.3 7.5 10.6 15.9 21.2 0.0 4.0 5.6 8.0 11.9 15.9 0.0 5.3 7.5 10.6 15.9 21.2 0.0 6.8 10.1 13.6 19.5 0.0 10.6 15.9 21.2 0.0 19.2 26.9 38.5 57.2 76.4 0.0 22.1 31.3 44.2 66.3 88.3 0.0 11.1 15.5 22.2 33.0 44.1 0.0 12.7 18.0 25.5 38.2 51.0 0.0 8.2 12.1 16.4 23.5 0.0 10.2 15.3 20.4 0.0 19.2 26.9 38.5 57.2 76.4 0.0 22.1 31.3 44.2 66.3 88.3 0.0 11.1 15.5 22.2 33.0 44.1 0.0 12.7 18.0 25.5 38.2 51.0 0.0 8.2 12.1 16.4 23.5 0.0 10.2 15.3 20.4 41.4 46.0 55.7 70.1 93.5 117.6 41.4 49.6 61.1 77.2 104.8 132.4 30.8 32.9 38.4 46.8 60.3 74.2 30.8 34.9 41.6 50.9 66.8 82.7 16.1 19.7 24.7 29.9 38.8 12.5 19.7 26.1 32.5 49.4 49.4 55.7 70.1 93.5 117.6 49.4 49.6 61.1 77.2 104.8 132.4 34.1 34.1 38.4 46.8 60.3 74.2 34.1 34.9 41.6 50.9 66.8 82.7 17.3 19.7 24.7 29.9 38.8 13.5 19.7 26.1 32.5 Max Fuse / BRKR1 Size Amps 50 50 60 80 100 125 50 50 70 80 110 150 40 40 40 50 70 80 40 40 45 60 70 90 20 20 25 30 40 15 20 30 35 70 70 70 80 100 125 70 70 70 80 110 150 45 45 45 50 70 80 45 45 45 60 70 90 20 20 25 30 40 15 20 30 35 1. HACR Type per NEC. 2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories 2FB04700825 and 2FB04700846 are available for field installation. 28 Unitary Products Group 036-21502-002-A-0303 TABLE 23: ELECTRICAL DATA - DM060 & 072 BELT DRIVE WITH POWR’D CONVENIENCE OUTLET Model Tonnage Compressors Voltage RLA Each LRA Each OD Fan Motor FLA ID Blower Motor FLA Conv Outlet Amps 208-1-60 28.9 165 1.3 7.6 10.0 230-1-60 28.9 165 1.3 7.6 10.0 208-3-60 16.0 125 1.3 5.2 10.0 230-3-60 16.0 125 1.3 5.2 10.0 460-3-60 8.0 66.5 0.8 2.6 5.0 575-3-60 6.4 50 0.8 2 4.0 208-3-60 18.9 146 1.3 5.0 10.0 230-3-60 18.9 146 1.3 5.0 10.0 460-3-60 9.5 73 0.8 2.5 5.0 575-3-60 7.6 58.4 0.8 2 4.0 5 6 Electric Heater Model No. Heater kW Heater Amps Minimum Circuit Ampacity Amps NONE 2CE04510506 2CE04510706 2CE04511006 2CE04511506 2CE04512006 2CE04513006 NONE 2CE04510506 2CE04510706 2CE04511006 2CE04511506 2CE04512006 2CE04513006 NONE 2CE04510525 2 2 2CE04510725 2CE04511025 2CE04511525 2CE04512025 2CE04513025 NONE 2CE04510525 2 2CE04510725 2 2CE04511025 2CE04511525 2CE04512025 2CE04513025 NONE 2CE04510746 2 2CE04511046 2 2 2CE04511546 2CE04512046 2 2CE04513046 2 NONE 2CE04511058 2CE04511558 2CE04512058 2CE04513058 NONE 2CE04510525 2 2CE04510725 2 2CE04511025 2CE04511525 2CE04512025 2CE04513025 NONE 2CE04510525 2 2 2CE04510725 2CE04511025 2CE04511525 2CE04512025 2CE04513025 NONE 2CE04510746 2 2 2CE04511046 2CE04511546 2 2 2CE04512046 2CE04513046 2 NONE 2CE04511058 2CE04511558 2CE04512058 2CE04513058 0.0 4.0 5.6 8.0 11.9 15.9 22.2 0.0 5.3 7.5 10.6 15.9 21.2 29.6 0.0 4.0 5.6 8.0 11.9 15.9 22.2 0.0 5.3 7.5 10.6 15.9 21.2 29.6 0.0 6.8 10.1 13.6 19.5 28.8 0.0 10.6 15.9 21.2 30.4 0.0 4.0 5.6 8.0 11.9 15.9 22.2 0.0 5.3 7.5 10.6 15.9 21.2 29.6 0.0 6.8 10.1 13.6 19.5 28.8 0.0 10.6 15.9 21.2 30.4 0.0 19.2 26.9 38.5 57.2 76.4 106.7 0.0 22.1 31.3 44.2 66.3 88.3 123.3 0.0 11.1 15.5 22.2 33.0 44.1 61.6 0.0 12.7 18.0 25.5 38.2 51.0 71.2 0.0 8.2 12.1 16.4 23.5 34.6 0.0 10.2 15.3 20.4 29.3 0.0 11.1 15.5 22.2 33.0 44.1 61.6 0.0 12.7 18.0 25.5 38.2 51.0 71.2 0.0 8.2 12.1 16.4 23.5 34.6 0.0 10.2 15.3 20.4 29.3 55.0 55.0 55.7 70.1 93.5 117.6 155.4 55.0 55.0 61.1 77.2 104.8 132.4 176.2 36.5 36.5 38.4 46.8 60.3 74.2 96.0 36.5 36.5 41.6 50.9 66.8 82.7 108.0 18.4 19.7 24.7 29.9 38.8 52.8 14.2 19.7 26.1 32.5 43.6 39.9 39.9 39.9 46.5 60.0 73.9 95.8 39.9 39.9 41.3 50.6 66.6 82.5 107.8 20.2 20.2 24.6 29.8 38.7 52.7 15.7 19.7 26.1 32.5 43.6 Max Fuse / BRKR1 Size Amps 80 80 80 80 100 125 175 80 80 80 80 110 150 200 50 50 50 50 70 80 100 50 50 50 60 70 90 110 25 25 25 30 40 60 20 20 30 35 45 50 50 50 50 70 80 100 50 50 50 60 70 90 110 25 25 25 30 40 60 20 20 30 35 45 1. HACR Type per NEC. 2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories 2FB04700825 and 2FB04700846 are available for field installation. Unitary Products Group 29 036-21502-002-A-0303 TABLE 24: PHYSICAL DATA DM MODELS Centrifugal Blower (Dia. x Wd. in.) EVAPORATOR BLOWER EVAPORATOR COIL CONDENSER FANS CONDENSER COILS COMPRESSOR (Qty. Per Unit) AIR FILTERS CHARGE VOLTAGE 12 X 11 3/4 1 1 1 1/2 1 1/2 1 1/2 Rows Deep 3 3 3 4 Fins Per Inch 13 13 13 13 Face Area (Sq. Ft.) 3.6 4.3 5.1 5.1 Propeller Dia. (in.) 24 24 24 24 Fan Motor Hp 1/4 1/4 1/4 1/4 3400 Nom. CFM 3400 3400 3400 Rows Deep 1 1 1 2 Fins Per Inch 16 16 22 16 Face Area (Sq. Ft.) 17.1 17.1 17.1 16.7 Scroll Type 1 1 1 1 Quantity Per Unit (15” X 20” X 1” or 2“) 2 2 2 2 Quantity Per Unit (14” X 25” X 1” or 2“) 1 1 1 1 Total Face Area (sq. ft.) 6.3 6.3 6.3 6.3 Refrigerant 22 (lbs./oz.) 5/8 6/8 6/8 10/0 kW CAP. MULTIPLIER TABLE 26: VOLTAGE LIMITATIONS1 VOLTAGE POWER SUPPLY MIN. MAX. 208/230-3-60 187 253 0.92 460-3-60 414 506 0.92 575-3-60 518 506 240 230 0.92 575 12 X 10 1/2 1.00 600 072 12 X 10 1 1/2 208 460 060 12 X 10 Fan Motor HP (Belt Drive) 208 480 048 Fan Motor HP (Direct Drive) TABLE 25: ELECTRIC HEAT CORRECTION FACTORS NOMINAL VOLTAGE 036 1. Utilization Range “A” in accordance with ARI Standard 110. 30 Unitary Products Group 036-21502-002-A-0303 TYPICAL POWER WIRING REFER TO THE ELECTRICAL DATA TABLES TO SIZE THE DISCONNECT SWITCH, OVERCURRENT PROTECTION AND WIRING. TYPICAL CONTROL WIRING COOLING / HEATING (24 VOLT THERMOSTAT) COOLING ONLY (24 VOLT THERMOSTAT) THERMOSTAT1 TERMINALS UNIT TERMINAL STRIP TB1 THERMOSTAT1 TERMINALS RV R YC Y1 UNIT TERMINAL STRIP TB1 RH ADD JUMPER 24 VOLT TRANSFORMER RC R Y Y1 Y2 Y2 W1 W G GF 24 VOLT TRANSFORMER W2 C G G 1 24 VOLT THERMOSTAT 2TH07701024. TO CONTROL THE ECONOMIZER ON SECOND STAGE COOLING, USE THE THERMOSTAT 2TH0401224. C 1 24 VOLT THEROMSTAT 2ET07701024. TO CONTROL THE ECONOMIZER ON THE SECOND STAGE COOLING OR TO HAVE AN ELECTRIC HEAT ACCESSORY WITH TWO STAGES OF HEAT, USE THERMOSTAT 2TH0471024. COOLING / HEATING (ELECTRONIC THEROMSTAT) MULTI STAGE THERMOSTAT1 TERMINALS RC RH ADD JUMPER 4 ADD JUMPER Y1 Y2 W1 W2 G 2 3 Y1 Y2 W1 W2 G C X OCC RH ADD JUMPER UNIT TERMINAL STRIP TB1 RC R Y Y1 W1 W G G C 24 VOLT TRANSFORMER 1 ELECTRONIC PROGRAMMABLE THEROMSTAT 2ET07701024 (INCLUDES SUBBASE). TO CONTROL THE ECONOMIZER ON SECOND STAGE COOLING, USE THERMOSTAT 2TH04700224. 2TH040702224 IF USED 1 ELECTRONIC PROGRAMMABLE THEROMSTAT 2TH04700224 (INCLUDES SUBBASE). 2 SECOND STAGE COOLING IS NOT REQUIRED ON UNITS LESS ECONOMIZER. 3 SECOND STAGE HEATING IS ONLY REQUIRED ON UNITS WITH A TWO STAGE ELECTRIC HEATER. FIGURE 2: THERMOSTAT1 TERMINALS UNIT TERMINAL STRIP TB1 24 VOLT R TRANSFORMER B LED 1 LED 2 NOT USED COM 4 A1 A2 TO REMOTE SENSOR T T COOLING / HEATING (ELECTRONIC THEROMSTAT) SINGLE STAGE TYPICAL FIELD POWER & CONTROL WIRING Unitary Products Group 31 036-21502-002-A-0303 FIGURE 3: UNIT DIMENSIONS (3 - 6 TON COOLING ONLY/ELECTRIC HEAT) FRONT VIEW FIGURE 4: UNIT DIMENSIONS (3 - 6 TON COOLING/GAS HEAT) FRONT VIEW 32 Unitary Products Group 036-21502-002-A-0303 DETAIL “A” FIGURE 5: UNIT WITH ECONOMIZER RAINHOOD DETAIL “B” FIGURE 6: UNIT WITH FIXED OUTDOOR AIR/MOTORIZED DAMPER RAINHOOD Unitary Products Group 33 036-21502-002-A-0303 FIGURE 7: UNIT DIMENSIONS (REAR VIEW) TABLE 28: MINIMUM CLEARANCES FILTER ACCESS BLOWER MOTOR ACCESS LOCATION CLEARANCE Front 24” (Cooling/Electric Heat) 32” (Gas Heat) Back 12” (Less Economizer) 36” (With Economizer or Fixed Air/Motorized Damper) Left Side (Filter Access) 24” (Less Economizer) 36” (With Economizer) Right Side (Cond. Coil) 24” FIELD-SUPPLIED DISCONNECT SWITCH LOCATION MOUNTING BRACKET FOR DICONNECT SWITCH (Shipped attached to the blower housing inside the blower compartment) Below A,B WIRING ENTRY (See Detail “B”) Above Unit 2 CONTROL BOX ACCESS DISCONNECT SWITCH LOCATION AND MOTOR ACCESS PANEL FOR UNIT WITH “BELT-DRIVE” OPTION FIGURE 8: Unit1 DISCONNECT/BLOWER ACCESS LOCATION 0” 72” (For Condenser Air Discharge) 1. Units may be installed on combustible floors made from wood or class A, B, or C roof covering material. 2. Units must be installed outdoors. Overhanging structures or shrubs should not obstruct condenser air discharge outlet. TABLE 27: UTILITIES ENTRY HOLE OPENING SIZE (DIA.) USED FOR A 7/8” KO1 Control Wiring2 B 2” KO1 Power Wiring C 1-5/8” KO Gas Piping (Front) D 1-1/2” KO Gas Piping (Bottom) Side Bottom Side Bottom 1. Opening in the bottom to the unit can be located by the side in the insulation. 2. Do not remove the 2” knockout ring. 34 Unitary Products Group 036-21502-002-A-0303 FIGURE 9: TYPICAL APPLICATIONS Unitary Products Group 35 036-21502-002-A-0303 BACK OF UNIT A 447/8 BACK OF UNIT A 447/8 821/4 821/4 D B F X X B APPROXIMATE CENTER OF GRAVITY CONDENSER COIL END OF UNIT C Y FRONT OF UNIT C E APPROXIMATE CENTER OF GRAVITY D Y FRONT OF UNIT CONDENSER COIL END OF UNIT FIGURE 10: FOUR AND SIX POINT LOADING TABLE 29: DM 4 POINT LOADS WEIGHT DISTRIBUTION UNIT TOTAL A B C D DM036 Cooling/ Electric 565 125 123 157 160 DM036N04 625 140 133 172 180 DM036N08 635 140 138 177 180 DM048 Cooling/ Electric 615 137 135 170 173 DM048N06 675 152 145 185 193 DM048N10 685 152 150 190 193 DM060 Cooling/ Electric 640 143 140 177 180 DM060N08 700 158 150 192 200 DM060N10 710 158 155 197 200 DM072 Cooling/ Electric 720 164 189 196 171 DM072N08 775 179 201 209 186 DM072N10 785 179 206 214 186 TABLE 30: DM 6 POINT LOADS WEIGHT DISTRIBUTION UNIT TOTAL A B C D E F 107 DM036 Cooling/ Electric 565 84 83 82 104 105 DM036N04 625 93 92 91 115 117 118 DM036N08 635 94 93 92 117 119 120 DM048 Cooling/ Electric 615 91 90 89 113 115 116 DM048N06 675 100 99 98 124 126 128 DM048N10 685 102 100 99 126 128 129 DM060 Cooling/ Electric 640 95 94 93 118 119 121 DM060N08 700 104 103 101 129 131 132 DM060N10 710 105 104 103 131 133 134 DM072 Cooling/ Electric 720 107 117 129 134 122 111 DM072N08 775 115 126 139 144 131 120 DM072N10 785 117 128 141 146 133 121 TABLE 31: CENTER OF GRAVITY DIMENSION 3 - 5 TON 6 TON X 40-¾” 44” Y 19-¾” 22” 36 Unitary Products Group 036-21502-002-A-0303 TABLE 32: OPERATING WEIGHTS (LBS.) MODEL SIZE 3 TON 4 TON 5 TON 6 TON 565 615 640 720 N04 625 - - - N06 - 675 - - N08 635 - 700 775 N10 - 685 710 785 DM (Cooling Only) BASIC UNIT DM (Gas/Electric) Economizer 50 Motorized Damper OPTIONS Electric Heater ACCY. 26 5 - 7 kW 18 10 - 15 kW 23 20 - 30 kW 28 Roof Curb 92 Barometric Relief / Fixed Air Damper 10 Belt-Drive Blower 5 FIGURE 11: ROOF CURB DIMENSIONS Unitary Products Group 37 036-21502-002-A-0303 GUIDE SPECIFICATIONS GENERAL Units shall be manufactured by York International Unitary Products Group in an ISO 9001 certified facility. York's Sunline 2000TM units are convertible single packageunits. Although the units are primarily designed for curb mounting on a roof, they can also be slab-mounted at ground level or set on steel beams above a finished roof. Cooling only, cooling with gas heat and cooling with electric heat models are available with a wide variety of factory-mounted options and field-installed accessories to make them suitable for almost every application. All units are self-contained and assembled on full perimeter base rails with holes in the four corners for overhead rigging. Every unit is completely piped, wired, charged and tested at the factory to simplify the field installation and to provide years of dependable operation. All models (including those with an economizer) are suitable for either bottom or horizontal duct connections. Models with power exhaust are suitable for bottom duct connections only. For bottom duct, remove the sheet metal panels from the supply and return air openings through the base of the unit. For horizontal duct, remove the supply and return air panels on the rear of the unit. All non-Scroll compressors include crankcase heaters and all compressors have internal pressure relief. Every refrigerant circuit includes a liquid line filter-drier, a discharge line high pressure switch and a suction line with a freezestat and low pressure/loss of charge switch.The unit control circuit includes a 75 VA transformer, a 24-volt circuit breaker and a relay board with a compressor lockout circuit, a terminal strip for thermostat wiring, plus an additional set of pin connectors to simplify the interface of additional field controls. All units have long lasting powder paint cabinets with 750 hour salt spray test approval under ASTMB117 procedures. All models are CSA listed. All models include a 1-year limited warranty on the complete unit. Compressors and electric heater elements carry a 5-year warranty. Aluminized steel and Stainless steel tubular heat exchangers carry a 10-year warranty. DESCRIPTION Units shall be factory-assembled, single packaged, Electric Cooling/Gas Heat, Electric Cooling/Optional Electric Heat and designed for outdoor mounted installation. UNIT CABINET Unit cabinet shall be constructed of G90 galvanized steel, with exterior surfaces coated with a non-chalking, powdered paint finish, certified at 750 hours salt spray test per ASTMB117 standards. Indoor blower section shall be insulated with a minimum 1/2” thick insulation, coated on the airside. Aluminum foil faced insulation shall be used in the furnace compartment and be fastened with ridged fasteners to prevent insulation from entering the air stream. Cabinet panels shall be “large” size, easily removable for servicing and maintenance. Full perimeter base rails shall be provided to assure reliable transit of equipment, overhead rigging and proper sealing on roof curb applications. Disposable 1" filters shall be furnished and be accessible through a removable access door, sealed airtight. Units filter track shall be designed to accommodate either 1” or 2” filters. Fan performance measuring ports shall be provided on the outside of the cabinet to allow accurate air measurements of evaporator fan performance without removing panels or creating air bypass of the coils. Condensate pan shall be internally sloped and conform to ASHRAE 62-89 self-draining standards. Condensate connection shall be a minimum of 3/4” I.D. female and be a ridged mount connection. INDOOR (EVAPORATOR) FAN ASSEMBLY The indoor fan shall be direct drive, multi-speed, or a factory installed belt drive assembly that includes an adjustable pitch motor pulley. Job site selected (B.H.P.) brake horsepower shall not exceed the motors nameplate horsepower rating, plus the service factor. Units shall be designed not to operate above service factor. Fan wheel shall be double-inlet type with forward-curved blades, dynamically balanced to operate smoothly throughout the entire range of operation. Airflow design shall be constant air volume. Bearings shall be sealed and permanently lubricated for longer life and no maintenance. OUTDOOR (CONDENSER) FAN ASSEMBLY The outdoor fan shall be of the direct-driven propeller type, discharge air vertically, have aluminum blades riveted to a corrosion resistant steel spider bracket and shall be dynamically balanced for smooth operation. The outdoor fan motor shall be totally enclosed with permanently lubricated bearings, internally protected against overload conditions and staged independently. REFRIGERANT COMPONENTS The 3 thru 5 ton units shall have minimum SEER ratings of 10.0 and the 6 ton units shall have minimum EER ratings of 9.0. They shall have built-in field convertible duct connections for down discharge supply/return or horizontal discharge supply/return, and be available with factory installed options or field installed accessories. The units shall be factory wired, piped, charged with R-22 refrigerant and factory tested prior to shipment. All unit wiring shall be both numbered and color coded. All units the cooling performance shall be rated in accordance with DOE and ARI test procedures. Units shall be CSA listed, classified to ANSI Z21.47, UL 1995/CSA No. 236 standards. 38 Compressor: a. Shall be internally protected with internal high-pressure relief and over temperature protection. b. Shall have internal spring isolation and sound muffling to minimize vibration and noise, and be externally isolated on a dedicated, independent mounting. Coils: a. Evaporator and condenser coils shall have aluminum plate fins mechanically bonded to seamless Unitary Products Group 036-21502-002-A-0303 internally enhanced copper tubes with all joints brazed. Special Phenolic coating shall be available as a factory option. b. Evaporator and Condenser coils shall be of the direct expansion, draw-thru, design. Refrigerant Circuit and Refrigerant Safety Components shall include: a. Independent fixed-orifice expansion devices. b. Filter drier/strainer to eliminate any moisture or foreign matter. c. Accessible service gage connections on both suction and liquid lines to charge, evacuate, and measure refrigerant pressure during any necessary servicing or troubleshooting without losing charge. d. dant main gas valve. Venter wheel shall be constructed of stainless steel for corrosion resistance. The heat exchanger shall be of the tubular type, constructed of T1-40 aluminized steel for corrosion resistance and allowing minimum mixed air entering temperature of 25°F. Burners shall be of the inshot type, constructed of aluminum coated steel and contain air mixture adjustments. All gas piping shall enter the unit cabinet at a single location through either the side or curb, without any field modifications. An integrated control board shall provide timed control of evaporator fan functioning and burner ignition. Heating section shall be provided with the following minimum protection: The refrigeration system shall provide at least 15°F of sub-cooling at design conditions. UNIT CONTROLS a. Unit shall be complete with self-contained low-voltage control circuit protected by a resetable circuit breaker on the 24-volt transformer side. b. Unit shall incorporate a lockout circuit which provides reset capability at the space thermostat or base unit, should any of the following standard safety devices trip and shut off compressor. c. Loss-of-charge/Low-pressure switch. d. High-pressure switch. e. Freeze-protection thermostat, evaporator coil. f. If any of the above safety devices trip, a LED (lightemitting diode) indicator shall flash a diagnostic code that indicates which safety switch has tripped. g. Unit shall incorporate “AUTO RESET” compressor over temperature, over current protection. h. Unit shall operate with conventional thermostat designs and have a low voltage terminal strip for easy hook-up. i. Unit control board shall have on-board diagnostics and fault code display. j. Standard controls shall include anti-short cycle and low voltage protection, and permit cooling operation down to 0°F. k. Control board shall monitor each refrigerant safety switch independently. l. Control board shall retain last 5 fault codes in non volatile memory, which will not be lost in the event of a power loss. a. Primary and auxiliary high-temperature limit switches. b. Induced draft motor speed sensor. c. Flame roll out switch (manual reset). d. Flame proving controls. ELECTRIC HEATING SECTION An electric heating section, with nickel chromium elements, shall be provided in a range of 5 thru 30 KW, offering two stages of capacity - 16 KW and above on 208/230 volt heaters and 20 KW and above on 460 and 575 volt heaters. The heating section shall have a primary limit control(s) and automatic reset to prevent the heating element system from operating at an excessive temperature. The heating section assembly shall slide out of the unit for easy maintenance and service. Units with Electric Heating shall be wired for a single point power supply with branch circuit fusing (where required). UNIT OPERATING CHARACTERISTICS a. Unit shall be capable of starting and running at 125°F outdoor temperature, exceeding maximum load criteria of ARI Standard 210/240. The compressor, with standard controls, shall be capable of operation down to 0°F outdoor temperature. Unit shall be provided with fan time delay to prevent cold air delivery before heat exchanger warms up (Gas heat only). ELECTRICAL REQUIREMENTS All unit power wiring shall enter unit cabinet at a single factory provided location and be capable of side or bottom entry, to minimize roof penetrations and avoid unit field modifications. Separate side and bottom openings shall be provided for the control wiring. STANDARD LIMITED WARRANTIES • Compressor 5 Years • Heat Exchanger 10 Years GAS HEATING SECTION • Electric Heat Element 5 Years Shall be designed with induced draft combustion with post purge logic, energy saving direct spark ignition, and redun- • Other Parts 1 Year Unitary Products Group 39 OPTIONAL OUTDOOR AIR (Shall be made available by either/or): • • ELECTRONIC ENTHALPY AUTOMATIC ECONOMIZER- Outdoor and return air dampers that are interlocked and positioned by a fully-modulating, spring return damper actuator. The maximum leakage rate for the outdoor air intake dampers shall not exceed 2% when dampers are fully closed and operating against a pressure differential of 0.5 IWG. A unit-mounted potentiometer shall be provided to adjust the outdoor and return air damper assembly to take in CFM of outdoor air to meet the minimum ventilation requirement of the conditioned space during normal operation. During economizer operation, a mixed-air temperature control shall modulate the outdoor and return air damper assembly to prevent the supply air temperature from dropping below 55°F. Changeover from compressor to economizer operation shall be provided by an integral electronic enthalpy control that feeds input into the basic module. The outdoor intake opening shall be covered with a rain hood that matches the exterior of the unit. Water eliminator/filters shall be provided. Simultaneous economizer/compressor operation is also possible. Dampers shall fully close on power loss. MOTORIZED OUTDOOR AIR DAMPERS - Outdoor air dampers are positioned by a 2-position, spring-return damper actuator. The maximum leakage rate for the outdoor air intake dampers shall not exceed 2% when dampers are fully closed and operating against a pressure differential of 0.5 IWG. A unit-mounted potentiometer shall be provided to adjust the outdoor damper assembly to take in the design CFM of outdoor air to meet the ventilation requirements of the conditioned space during normal operation. Whenever the indoor fan motor is energized, the dampers open up to one of two pre-selected positions - regardless of the outdoor air enthalpy. Dampers return to the fully closed position when the indoor fan motor is de-energized. Dampers shall fully close on power loss. • HIGH ALTITUDE - PROPANE GAS - Contains orifices required for applications between 2000 and 6000 feet altitude. Must be used with propane conversion kit. • LOW NOX - Required to reduce the emission of nitrogen oxides below 40 nanograms per joule. • GAS PIPING - Contains 1/2” pipe nipples, fittings and gas cock (including panel assess gaskets) required for bottom gas supply connection with external shut off. • POWER EXHAUST OPTION - To work in conjunction with economizers. • ELECTRIC HEATERS • ECONOMIZER/MOTORIZED DAMPER RAIN HOOD Contains all hood panels and the hardware for assembling. • MANUAL OUTDOOR AIR DAMPER • COIL GUARD KIT - Guard for cooling coil. • HAIL GUARD • FLUE EXHAUST EXTENSION OTHER FACTORY INSTALLED OPTIONS • POWER EXHAUST OPTION - To work in conjunction with economizers. • STAINLESS STEEL HEAT EXCHANGER • TECHNICOAT PHENOLIC COATED CONDENSER AND EVAPORATOR COIL • ELECTRONIC SINGLE ENTHALPY ECONOMIZER • DIRTY FILTER SWITCH • PHASE MONITOR • COIL GUARD • POWERED GFI CONVENIENCE OUTLET OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE • NON-POWERED GFI CONVENIENCE OUTLET • ROOF CURB - 14"and 8” high, full perimeter curb with wood nailer (shipped knocked-down). • BAS CONTROLS (CPC, JOHNSON, HONEYWELL, NOVAR) • BAROMETRIC RELIEF DAMPER - Contains a rain hood, air inlet screen, exhaust damper and mounting hardware. Used to relieve internal air pressure through the unit. • BAS READY ECONOMIZER (BELIMO ACTUATOR WITHOUT A CONTROLLER) • HINGED FILTER DOOR ACCESS AND TOOLESS ACCESS PANELS • 2" PLEATED FILTERS • DISCONNECT SWITCH • SUPPLY AIR SMOKE DETECTOR • RETURN AIR SMOKE DETECTOR • • PROPANE CONVERSION KIT - Contains new orifices and gas valve parts to convert from natural to L.P. gas. One per unit required. HIGH ALTITUDE - NATURAL GAS - Contains orifices required for applications between 2000 and 6000 feet altitude. Subject to change without notice. Printed in U.S.A. Copyright © by Unitary Products 2003. All rights reserved. Unitary Products Group 036-21502-002-A-0303 Supersedes: 036-21502-001-A-0103 5005 York Drive Norman OK 73069
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.4 Linearized : No Create Date : 2003:03:10 11:19:27Z Creator : PScript5.dll Version 5.2 Modify Date : 2003:03:10 11:21:03-06:00 Page Count : 40 Page Mode : UseThumbs Creation Date : 2003:03:10 11:19:27Z Producer : Acrobat Distiller 4.05 for Windows Mod Date : 2003:03:10 11:21:03-06:00 Metadata Date : 2003:03:10 11:21:03-06:00 Title : Y-TG, Single Package Gas/Elec Units and Sgl Pkg AC, DM036, 048, 060 & 072EXIF Metadata provided by EXIF.tools