DESCRIPTION
These Category IV, highly efficient, compact, condensing
type furnaces are designed for residential and commercial
installations in a basement, closet, alcove, recreation room or
garage where the ambient temperature is above 32°F, or
higher. They may be either side wall or thru-roof vented using
approved plastic type combustion air and vent piping. All
units are factory assembled, wired and tested to assure
dependable and economical installation and operation.

WARRANTY

TECHNICAL GUIDE
MODELS: GY9S-UP
GAS-FIRED
CONDENSING / HIGH EFFICIENCY
UPFLOW FURNACES

Lifetime limited warranty on both heat exchangers to the original purchaser; a 20-year limited warranty from original installation date to subsequent purchaser.
10-year warranty on the heat exchanger in commercial applications.
5-year limited parts warranty.

FEATURES
•
•
•
•
•

92% TO 94% AFUE
NATURAL GAS
40 - 135 MBH INPUT

•
•
•
•
•
•
•
•
•
•
•
EFFICIENCY
RATING
CERTIFIED

•
•
•
ISO 9001
Certified Quality
Management System

•

Compact, easy to install, ideal height 40" cabinet
Blower-off delay for cooling SEER improvement.
Easy to connect power/control wiring.
Built-in, high level self diagnostics with fault code display.
Low unit amp requirement for easy replacement application.
Integrated control module for reliable, economical operation.
May be installed as either two-pipe (sealed combustion)
or single pipe vent (using indoor combustion air)
Top intake & vent connection allows installation in narrow
locations.
Electronic Hot Surface Ignition saves fuel cost with
increased dependability and reliability.
Induced combustion system with inshot main burners for
quiet, efficient operation.
No special vent termination kit required.
100% shut off main gas valve for extra safety.
PSC four speed, direct drive motor with large, quiet
blower.
24V, 40 VA control transformer and blower relay supplied
for add-on cooling.
Hi-tech tubular aluminized steel primary heat exchanger.
Secondary (condensing) heat exchanger of 29-4C highgrade stainless steel.
Timed on, adjustable off blower capability for maximum
comfort.
Solid removable bottom panel allows easy application.
Easy access from front of unit for cleaning, maintenance
or service.
Protection from intake, exhaust or condensate blockage.

Due to continuous product improvement, specifications
are subject to change without notice.
Visit us on the web at www.york.com for the most
up-to-date technical information.
Additional rating information can be found at
www.gamanet.org.

FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

277805-YTG-A-1106

28-1/2
26-1/2
24-5/8

26-1/2
A

25-3/8

1-1/2” GAS
PIPE ENTRY
1-1/2” GAS
PIPE ENTRY

7/8” JUNCTION
BOX HOLE
T-STAT WIRING
7/8” K.O.
CONDENSATE
DRAIN 7/8” K.O.

28-3/8

21-1/2

OPTIONAL RETURN AIR
CUT-OUT (either side)
FOR USE WITH
EXTERNAL FILTER
FRAME
7/8

7/8” JUNCTION
BOX HOLE

40

30-7/8

21-1/2
T-STAT WIRING
7/8” K.O.

13-7/8
11

11

8

7

23-3/4
LEFT SIDE

FRONT

7/8

RIGHT SIDE
5/8

24-3/8

1-1/2
20

1-1/4

26-3/4

CONDENSATE
DRAIN 7/8” K.O.

5/8

D
B

C

2
24-7/16
TOP IMAGE
SUPPLY END

BOTTOM IMAGE
RETURN END

2

Cabinet Dimension

Models

Nominal
CFM

Cabinet
Size

A (in.)

B (in.)

C (in.)

D (in.)

GY9S040A12UP11

1200

A

14-1/2

13-1/4

11-1/2

6-1/4

GY9S060B12UP11

1200

B

17-1/2

16-1/4

14-1/2

8-1/2

GY9S080B12UP11

1200

B

17-1/2

16-1/4

14-1/2

8-1/2

GY9S080C16UP11

1600

C

21

19-3/4

18

8-7/8

GY9S080C20UP11

2000

C

21

19-3/4

18

8-7/8

GY9S100C16UP11

1600

C

21

19-3/4

18

8-7/8

GY9S100C20UP11

2000

C

21

19-3/4

18

8-7/8

GY9S120D20UP11

2000

D

24-1/2

23-1/4

21-1/2

10-5/8

GY9S135D20UP11

2000

D

24-1/2

23-1/4

21-1/2

10-5/8

Johnson Controls Unitary Products

277805-YTG-A-1106
ELECTRICAL AND PERFORMANCE DATA
Model

Input/
Cabinet

Output

Nominal
Airflow

Cabinet
Width

Total Unit

AFUE

Air Temp. Rise

MBH

MBH

CFM

In.

Amps

%

°F

GY9S040A12UP11

40/A

38

1200

14-1/2

9

94.0

35 - 65

GY9S060B12UP11

60/B

56

1200

17-1/2

9

92.0

40 - 70

GY9S080B12UP11

80/B

74

1200

17-1/2

9

92.0

45 - 75

GY9S080C16UP11

80/C

75

1600

21

12

92.0

45 - 75

GY9S080C20UP11

80/C

75

2000

21

14

92.0

40 - 70

GY9S100C16UP11

100/C

93

1600

21

12

92.0

45 - 75

GY9S100C20UP11

100/C

93

2000

21

14

92.0

40 - 70

GY9S120D20UP11

120/D

112

2000

24-1/2

14

92.0

40 - 70

GY9S135D20UP11

135/D

127

2000

24-1/2

14

92.0

45 - 75

Model

Input/
Cabinet

Max.
Outlet
Air Temp.

Blower

Blower
Size

Max.
Over-current
Protect

Min. Wire Size
(awg) @ 75 ft.
One Way

Operating
Wt

MBH

°F

HP

Amps

In.

GY9S040A12UP11

40/A

165

1/2

7.0

11 x 8

20

14

Lbs.
119

GY9S060B12UP11

60/B

170

1/2

7.0

11 x 8

20

14

133

GY9S080B12UP11

80/B

175

1/2

7.0

11 x 8

20

14

140

GY9S080C16UP11

80/C

175

3/4

10.2

11 x 10

20

14

155

GY9S080C20UP11

80/C

170

1

12.7

11 x 11

20

12

157

GY9S100C16UP11

100/C

175

3/4

10.2

11 x 10

20

14

160

GY9S100C20UP11

100/C

170

1

12.7

11 x 11

20

12

162

GY9S120D20UP11

120/D

170

1

12.7

11 x 11

20

12

178

GY9S135D20UP11

135/D

175

1

12.7

11 x 11

20

12

178

Nominal external static pressure is 0.50” w.c. at furnace outlet ahead of cooling coils.
Annual Fuel Utilization Efficiency (AFUE) numbers are determined in accordance with DOE Test procedures.
Wire size and over current protection must comply with the National Electrical Code (NFPA-70-latest edition) and all local codes.

NOTES:
1. For altitudes above 2000 ft. reduce capacity 4% for each 1000 ft. above sea level.
2. Wire size based on copper conductors, 60°C, 3% voltage drop.
3. Continuous return air temperature must not be below 55°F.

Johnson Controls Unitary Products

3

277805-YTG-A-1106
BLOWER PERFORMANCE CFM
Airflow with Bottom or One Side Return - without Filters (CFM)
MODELS

GY9S040A12UP11

GY9S060B12UP11
GY9S080B12UP11

GY9S080C20UP11
GY9S100C20UP11

GY9S080C16UP11
GY9S100C16UP11

GY9S120D20UP11
GY9S135D20UP11

External Static Pressure, Inches W.C

Speed
Tap

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

HIGH

1635

1590

1535

1480

1415

1340

1280

1185

NR

NR

M-HI

1245

1225

1205

1185

1160

1110

1065

995

NR

NR

M-LO

1005

1000

995

975

955

925

885

825

NR

NR

LOW

775

770

765

750

725

680

655

620

NR

NR

HIGH

1650

1605

1570

1525

1465

1410

1350

1275

1170

1060

M-HI

1165

1185

1175

1165

1150

1140

1100

1050

970

875

M-LO

895

915

935

940

940

920

905

860

815

750

LOW

710

725

725

725

720

700

685

660

625

560

HIGH

2300

2210

2120

2020

1930

1830

1715

1595

1480

1350

M-HI

1950

1900

1830

1755

1680

1595

1500

1390

1270

1155

M-LO

1610

1545

1490

1440

1390

1315

1230

1155

1050

920

LOW

1325

1270

1225

1175

1105

1045

990

905

890

790

HIGH

1960

1955

1925

1890

1830

1765

1695

1615

1600

1485

M-HI

1565

1560

1560

1575

1545

1530

1475

1425

1365

1260

M-LO

1230

1275

1285

1300

1310

1300

1280

1245

1190

1070

LOW

930

945

965

975

975

975

975

950

910

850

HIGH

2560

2485

2410

2320

2220

2135

2035

1920

1785

1650

M-HI

2090

2050

1990

1970

1885

1820

1760

1675

1545

1405

M-LO

1695

1675

1665

1615

1565

1510

1460

1385

1285

1140

LOW

1175

1150

1135

1110

1085

1055

1005

980

970

845

Airflow with Two Side Returns or with Bottom and One Side Return - Without Filters (CFM)
MODELS

GY9S080C20UP11
GY9S100C20UP11

GY9S120D20UP11
GY9S135D20UP11

External Static Pressure, Inches W.C.

Speed
Tap

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

HIGH

2465

2380

2295

2195

2095

1995

1875

1760

1620

1470

M-HI

2085

2035

1960

1880

1800

1705

1605

1485

1360

1235

M-LO

1725

1625

1595

1540

1485

1405

1315

1235

1125

995

LOW

1420

1360

1310

1255

1180

1120

1070

970

950

845

HIGH

2615

2535

2450

2385

2285

2175

2075

1945

1825

1670

M-HI

2055

2045

2015

1985

1932

1855

1785

1730

1605

1470

M-LO

1690

1650

1620

1600

1570

1525

1470

1395

1300

1200

LOW

1345

1335

1335

1285

1250

1230

1180

1115

1010

850

NOTES:
1. Airflow expressed in standard cubic feet per minute (CFM).
2. Return air is through side opposite motor (left side) for one side return (worst case).
3. Airflows above 1800 CFM require either return from two sides or one side plus bottom.
4. Motor voltage at 115 V.
5. NR = Operation at this static pressure is not recommended.

4

Johnson Controls Unitary Products

277805-YTG-A-1106

FILTER PERFORMANCE

RECOMMENDED FILTER SIZES

The airflow capacity data published in the “Blower Performance” table listed above represents blower performance
WITHOUT filters. To determine the approximate blower performance of the system, apply the filter drop value for the filter being used or select an appropriate value from the “Filter
Performance” table shown below.

Nominal CFM Cabinet Size Side Return Filter in.

NOTE: The filter pressure drop values in the “Filter Performance” table shown below are typical values for the type of
filter listed and should only be used as a guideline. Actual
pressure drop ratings for each filter type vary between filter
manufacturer.

Bottom Return
Filter in. (cm)

1200

A

16 x 25

1200

B

16 x 25

14 x 25
16 x 25

1600

C

16 x 25

20 x 25

2000

C

16 x 25

20 x 25

2000

D

(2) 16 x 25

22 x 25

NOTES:
1. Air velocity through throwaway type filters may not exceed 300
feet per minute. All velocities over this require the use of high
velocity filters.
2. Air flows above 1800 CFM require either return from two sides or
one side plus bottom.

FILTER PERFORMANCE - PRESSURE DROP INCHES W.C.
Airflow Range

0 - 750

Filter Type

Minimum Opening Size

Disposable

WASHABLE FIBER

Pleated

1 Opening

2 Openings

1 Opening

2 Opening

1 Opening

2 Opening

1 Opening

2 Opening

Sq. in.

Sq. in.

In w.c.

In w.c.

In w.c.

In w.c.

In w.c.

In w.c.

0.01

230

0.01

0.15

751 - 1000

330

0.04

0.03

0.20

1001 - 1250

330

0.08

0.07

0.20

1251 - 1500

330

1501 - 1750

380

658

0.14

0.08

0.13

0.06

0.30

0.17

1751 - 2000

380

658

0.17

0.09

0.15

0.07

0.30

0.17

2001 & Above

463

658

0.17

0.09

0.15

0.07

0.30

0.17

0.08

0.07

0.25

UNIT CLEARANCES TO COMBUSTIBLES
Application
Upflow

Top

Front

Rear

Left Side

Right Side

Flue

In.

In.

In.

In.

In.

In.

Floor/
Bottom

Closet
Alcove

Attic

1

3

0

0

0

0

Combustible

Yes

Yes

Johnson Controls Unitary Products

5

AC1

6

HP1

C
24-Volt Common
Y
First Stage Cool
RH
24-Volt Hot (Heat XFMR)
RC
24-Volt Hot (Cool XFMR)
W
First Stage Heat
G
Fan

Selection of GAS/ELEC switch
on thermostat not necessary

C
24-Volt Common

Y
First Stage Cool

R
24-Volt Hot (Heat XFMR)

RC
24-Volt Hot (Cool XFMR)

W
First Stage Heat
G
Fan

Thermostat Installer Setup Number 1 System Type - must be set to 0

HM1
Humidistat

G
Fan

W
First Stage Heat

RC
24-Volt Hot (Cool XFMR)

RH
24-Volt Hot (Heat XFMR)

Y
First Stage Cool

Optional w/Batteries

THERMOSTAT
*PP11C70224

G
Fan

W
Single Stage Heat

R
24-Volt Hot

Y/Y2
Single/Second Stage Cool

C
24-Volt Common

PSC
FURNACE CONTROL

N/A

THERMOSTAT
*DN22U00124

N/A

THERMOSTAT
*BP21H50124
*BN21H00124
*DP21H40124
*DN21H00124

C
24-Volt Common
Y/Y2
Single/Second Stage Cool
R
24-Volt Hot

C
24-Volt Common
Y
First Stage Heat/Cool
R
24-Volt Hot

Step 9 of Thermostat User Configuration Menu
must be set to Pump OFF

Step 1 of Thermostat User Configuration Menu
must be set to Heat Pump 1

X/L
Malfunction Light

L
Malfunction Light

W
First Stage Heat
O
Reversing Valve–Energized in Cool

G
Fan

G
Fan

W1/66
First Stage Heat Out

R
24-Volt Hot

Y
Single Stage Heat/Cool

C
24-Volt Common

SINGLE STAGE
HEAT PUMP

24V HUMIDIFIER

Y
Single Stage Cool

C
24-Volt Common

SINGLE STAGE
AIR CONDITIONING

O
Reversing Valve–Energized in Cool

W
Single Stage Heat

E
Emergency Heat

W1
Second Stage Heat

PSC
FURNACE CONTROL

THERMOSTAT
*PP32H70124

Single Stage H/P - E*RD, E*BD, ERHS, HPX13 - w/Single Stage Furnace, 1 Stage Cooling Ready - (G,L)*8/9S, XYF80-U, XYF80-U*L, XYF90-U
W/031-01975- Series Demand Control

Thermostat Installer Setup Number 15 Compressor Protection - must be set to 5

THERMOSTAT
*BP11C50124
*BN11C01124
*DP11C40124
*DN11C00124

THERMOSTAT
*BN11C00124

Single Stage A/C w/Single Stage Furnace, 1 Stage Cooling Ready - (G,L)*8/9S, XYF80-U, XYF80-U*L, XYF90-U

277805-YTG-A-1106

For additional connection diagrams for all UPG equipment refer to “Low Voltage System Wiring” document available online at
www.upgnet.com in the Product Catalog Section.

Thermostat Chart

Johnson Controls Unitary Products

277805-YTG-A-1106

APPLYING FILTER PRESSURE DROP TO
DETERMINE SYSTEM AIRFLOW
To determine the approximate airflow of the unit with a filter in
place, follow the steps below:
1. Select the filter type.
2. Select the number of return air openings or calculate the
return opening size in square inches to determine the
proper filter pressure drop.
3. Determine the External System Static Pressure (ESP)
without the filter.
4. Select a filter pressure drop from the table based upon
the number of return air openings or return air opening
size and add to the ESP from Step 3 to determine the
total system static.
5. If total system static matches a ESP value in the airflow
table (i.e. 0.20, 0.60, etc,) the system airflow corresponds to the intersection of the ESP column and Model/
Blower Speed row.
6. If the total system static falls between ESP values in the
table (i.e. 0.58, 0.75, etc.), the static pressure may be
rounded to the nearest value in the table determining the
airflow using Step 5 or calculate the airflow by using the
following example.
Example: For a 120,000 Btuh furnace with 2 return openings
and operating on high speed blower, it is found that total system static is 0.58" w.c. To determine the system airflow, complete the following steps:
1. Obtain the airflow values at 0.50" & 0.60" ESP.
Airflow @ 0.50": 2285 CFM
Airflow @ 0.60": 2175 CFM
2. Subtract the airflow @ 0.50" from the airflow @ 0.60" to
obtain airflow difference.
2175 - 2285 = -110 CFM
3. Subtract the total system static from 0.50" and divide this
difference by the difference in ESP values in the table,
0.60" - 0.50", to obtain a percentage.
(0.58 - 0.50) / (0.60 - 0.50) = 0.8
4. Multiply percentage by airflow difference to obtain airflow
reduction.
(0.8) x (-110) = -88
5. Subtract airflow reduction value to airflow @ 0.50" to
obtain actual airflow @ 0.58" ESP.
2288 - 88 = 2197

ACCESSORIES
PROPANE (LP) CONVERSION KIT 1NP0347 - All Models
This accessory conversion kit may be used to convert natural
gas units for propane (LP) operation. Conversions must be
made by qualified distributor or dealer personnel.
CONCENTRIC VENT TERMINATION 1CT0302 (2")
1CT0303 (3")
For use through rooftop, sidewall. Allows combustion air to
enter and exhaust to exit through single common hole.
SIDEWALL VENT TERMINATION KIT 1HT0901 (3”) and 1HT0902 (2”)
For use on sidewall, two-pipe installations only. Provides a
more attractive termination for locations where the terminal is
visible on the side of the home.
CONDENSATE NEUTRALIZER KIT - 1NK0301
Neutralizer cartridge has a 1/2" plastic tube fittings for installation in the drain line. Calcium carbonate refill media is also
available from the Source 1 Parts (p/n 026-30228-000).
EXTERNAL SIDE RETURN FILTER RACK 1SF0101 - Fits all cabinet sizes
Attaches to side of furnace cabinet in side return applications.
Holds any 16x25x1 permanent or disposable filter.
SIDE RETURN FILTER 1SR0302 - All Models
1SR0200 - All Models
BOTTOM RETURN FILTER 1BR0114 or 1BR0214 - For 14-1/2” cabinets
1BR0117 or 1BR0217 - For 17-1/2” cabinets
1BR0121 or 1BR0221 - For 21” cabinets
1BR0124 or 1BR0224 - For 24-1/2” cabinets
INTERNAL FILTER WITH FIBER FILTER 1HF0801 - All Models
HIGH ALTITUDE PRESSURE SWITCHES For installation where the altitude is less than 8,000 feet it is
not required that the pressure switch be changed. For altitudes above 8,000 feet see kits below. Conversion must be
made by qualified distributor or dealer personnel.
1PS0307 - 080, 100 MBH
1PS0309 - 060, 120 MBH
1PS0322 - 040, 135 MBH
ROOM THERMOSTATS - A wide selection of compatible
thermosets are available to provide optimum performance
and features for any installation.
1H/1C, manual change-over electronic non-programmable
thermostat.
1H/1C, auto/manual changeover, electronic programmable,
deluxe 7-day, thermostat.
1H/1C, auto/manual changeover, electronic programmable.
* For the most current accessory information, refer to the
price book or consult factory.

Johnson Controls Unitary Products

7

NOTES

Subject to change without notice. Printed in U.S.A.
Copyright © by York International Corp. 2006. All rights reserved.

Unitary
Products
Group

277805-YTG-A-1106
Supersedes: 246716-YTG-B-0806

5005
York
Drive

Norman
OK
73069



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : No
Page Mode                       : UseThumbs
XMP Toolkit                     : 3.1-702
About                           : uuid:ce6e1ca5-2c56-46e3-bb3e-d40b4716124c
Producer                        : Acrobat Distiller 6.0.1 (Windows)
Creator Tool                    : PScript5.dll Version 5.2.2
Modify Date                     : 2006:11:21 10:03:20-06:00
Create Date                     : 2006:11:20 11:04:36-06:00
Metadata Date                   : 2006:11:21 10:03:20-06:00
Document ID                     : uuid:33546374-df52-4ee9-9871-9865b8b59912
Instance ID                     : uuid:e788e532-4741-446e-a0ef-ab1fb871d9fb
Format                          : application/pdf
Title                           : 277805-YTG-A-1106.fm
Creator                         : csardom
Page Count                      : 8
Page Layout                     : OneColumn
Author                          : csardom
EXIF Metadata provided by EXIF.tools

Navigation menu