Millennium TM
AIR COOLED SCREW LIQUID CHILLERS
(STYLE F)
WIRING DIAGRAM

Supersedes: 201.18-W1 (798)

Form 201.18-W1 (1298)

MODELS YCAS0130 THRU YCAS0230

28971A(r)

WARNING
HIGH VOLTAGE
is used in the operation of this equipment
DEATH OR SERIOUS INJURY
may result if personnel fail to observe precautions.
Work on electronic equipment should not be undertaken unless the individual(s) has (have) been
trained in the proper maintenance of the equipment and is (are) familiar with its potential hazards.
Shut off power supply to equipment before beginning work and follow lockout procedures. When
working inside equipment with power off, take special care to discharge every capacitor likely to
hold dangerous potential.
Be careful not to contact high voltage connections when installing or operating this equipment.

LOW VOLTAGE
DO NOT be misled by the term “low voltage”. Voltages as low as 50 volts
may cause death.

2

YORK INTERNATIONAL

FORM 201.18-W1

NOMENCLATURE
The Model Number denotes the following characteristics of the unit:
YC

A

S

0140

YORK Chiller
YC = YORK Chiller
Air-Cooled
Compressor Type
S = Screw
Nominal Capacity
Unit Designator
S = Standard Unit
E = High Efficiency

YORK INTERNATIONAL

E

C

17

Y

F
Design Series
Type Start
Y = Star (WYE)-Delta
X = Across-the-Line

Voltage Code
17 = 200-3-60
28 = 230-3-60
40 = 380-3-60
46 = 460-3-60
58 = 575-3-60
Refrigerant
C = R-22

3

ELECTRICAL DATA
MULTIPLE POINT POWER SUPPLY CONNECTION

(Each of Two Field Provided Power Supply Circuits individually protected with Branch Circuit Protection.
Field Connections to Factory provided Terminal Block (Std), Disconnects (Opt), or Breakers(Opt) in each of the two Motor Control Centers.)
MODEL
D.E. FUSE
C.B.
VOLTS
MIN NF
YCAS
MCA1
2
3
4
5
DISC SW MIN. MAX. MIN. MAX.6

0130EC

0140EC

0150EC

0160EC

0170EC

0180EC

0200EC

0210EC

0230EC

200
230
380
460
575
200
230
380
460
575
200
230
380
460
575
200
230
380
460
575
200
230
380
460
575
200
230
380
460
575
200
230
380
460
575
200
230
380
460
575
200
230
380
460
575

340
299
181
150
119
366
321
195
161
128
402
351
213
176
141
402
351
213
176
141
434
380
230
191
152
434
380
230
191
152
469
412
250
206
164
509
445
270
224
178
509
445
270
224
178

400
400
200
150
150
400
400
200
200
150
400
400
250
200
150
400
400
250
200
150
600
400
250
200
150
600
400
250
200
150
600
400
250
200
200
600
600
400
250
200
600
600
400
250
200

450
400
225
200
150
450
400
250
200
175
500
450
300
225
175
500
450
300
225
175
600
450
300
250
200
600
450
300
250
200
600
500
300
250
200
700
600
350
300
225
700
600
350
300
225

600
600
350
300
225
700
600
350
300
225
700
700
400
350
250
700
700
400
350
250
800
700
400
350
300
800
700
400
350
300
1000
800
450
400
300
1000
800
500
400
350
1000
800
500
400
350

450
400
225
200
150
450
400
250
200
175
500
450
300
225
175
500
450
300
225
175
600
450
300
250
200
600
450
300
250
200
600
500
300
250
200
700
600
350
300
225
700
600
350
300
225

600
600
350
300
225
700
600
350
300
225
700
700
400
350
250
700
700
400
350
250
800
700
400
350
300
800
700
400
350
300
1000
800
450
400
300
1000
800
500
400
350
1000
800
500
400
350

SYSTEM #1 FIELD-SUPPLIED WIRING
FACTORY PROVIDED (LUGS) WIRE RANGE7
STD. TERMINAL OPT. NF SVC.
OPT. C.B.
BLOCK
DISC SW.
(2) # 2 - 300
(2) 3/0-250
(3) 2/0-400
(2) # 2 - 300
(2) 3/0-250
(2) 3/0-250
# 2 - 300
# 6 AWG - 350
# 6 AWG - 350
# 2 - 4/0
# 6 AWG - 350
# 6 AWG - 350
# 2 - 4/0
# 6 AWG - 350
# 6 AWG - 350
(2) # 2 - 300
(2) 3/0-250
(3) 2/0-400
(2) # 2 - 300
(2) 3/0-250
(2) 3/0-250
# 2 - 300
# 6 AWG - 350
# 6 AWG - 350
# 2 - 300
# 6 AWG - 350
# 6 AWG - 350
# 2 - 4/0
# 6 AWG - 350
# 6 AWG - 350
(2) # 1 - 500
(2) 3/0-250
(3) 2/0-400
(2) # 2 - 300
(2) 3/0-250
(3) 2/0-400
# 1 - 500
# 6 AWG - 350
(2) 3/0-250
# 2 - 300
# 6 AWG - 350
# 6 AWG - 350
# 2 - 4/0
# 6 AWG - 350
# 6 AWG - 350
(2) # 1 - 500
(2) 3/0-250
(3) 2/0-400
(2) # 2 - 300
(2) 3/0-250
(3) 2/0-400
# 1 - 500
# 6 AWG - 350
(2) 3/0-250
# 2 - 300
# 6 AWG - 350
# 6 AWG - 350
# 2 - 4/0
# 6 AWG - 350
# 6 AWG - 350
(2) # 1 - 500
(3) 2/0-400
(3) 2/0-400
(2) # 1 - 500
(2) 3/0-250
(3) 2/0-400
# 1 - 500
# 6 AWG - 350
(2) 3/0-250
# 2 - 300
# 6 AWG - 350
# 6 AWG - 350
# 2 - 4/0
# 6 AWG - 350
# 6 AWG - 350
(2) # 1 - 500
(3) 2/0-400
(3) 2/0-400
(2) # 1 - 500
(2) 3/0-250
(3) 2/0-400
# 1 - 500
# 6 AWG - 350
(2) 3/0-250
# 2 - 300
# 6 AWG - 350
# 6 AWG - 350
# 2 - 4/0
# 6 AWG - 350
# 6 AWG - 350
(2) # 1 - 500
(3) 2/0-400
(3) 2/0-400
(2) # 1 - 500
(2) 3/0-250
(3) 2/0-400
# 1 - 500
# 6 AWG - 350
(2) 3/0-250
# 1 - 500
# 6 AWG - 350
# 6 AWG - 350
# 2 - 300
# 6 AWG - 350
# 6 AWG - 350
(2) # 1 - 500
(3) 2/0-400
(3) 2/0-400
(2) # 1 - 500
(3) 2/0-400
(3) 2/0-400
# 1 - 500
(2) 3/0-250
(2) 3/0-250
# 1 - 500
# 6 AWG - 350
(2) 3/0-250
# 2 - 300
# 6 AWG - 350
# 6 AWG - 350
(2) # 1 - 500
(3) 2/0-400
(3) 2/0-400
(2) # 1 - 500
(3) 2/0-400
(3) 2/0-400
# 1 - 500
(2) 3/0-250
(2) 3/0-250
# 1 - 500
# 6 AWG - 350
(2) 3/0-250
# 2 - 300
# 6 AWG - 350
# 6 AWG - 350

COMPRESSOR
RLA

Y-LRA

X-LRA

246
214
130
107
86
267
232
140
116
93
295
256
155
128
103
295
256
155
128
103
321
279
169
140
112
321
279
169
140
112
342
298
181
149
119
374
325
197
163
130
374
325
197
163
130

444
386
234
193
154
444
386
234
193
154
656
571
360
285
238
656
571
360
285
238
656
571
360
285
238
656
571
360
285
238
656
571
360
285
238
656
571
360
285
238
656
571
360
285
238

1332
1158
701
579
463
1332
1158
701
579
463
1969
1712
1081
856
715
1969
1712
1081
856
715
1969
1712
1081
856
715
1969
1712
1081
856
715
1969
1712
1081
856
715
1969
1712
1081
856
715
1969
1712
1081
856
715

FANS
FLA (EA)
8.2
7.8
4.8
4.0
3.1
8.2
7.8
4.8
4.0
3.1
8.2
7.8
4.8
4.0
3.1
8.2
7.8
4.8
4.0
3.1
8.2
7.8
4.8
4.0
3.1
8.2
7.8
4.8
4.0
3.1
8.2
7.8
4.8
4.0
3.1
8.2
7.8
4.8
4.0
3.1
8.2
7.8
4.8
4.0
3.1

See page 6 for notes.

4

YORK INTERNATIONAL

FORM 201.18-W1

MODEL
D.E. FUSE
C.B.
VOLTS
MIN NF
YCAS
MCA1
2
3
4
3
DISC SW MIN. MAX. MIN. MAX.4

0130EC

0140EC

0150EC

0160EC

0170EC

0180EC

0200EC

0210EC

0230EC

200
230
380
460
575
200
230
380
460
575
200
230
380
460
575
200
230
380
460
575
200
230
380
460
575
200
230
380
460
575
200
230
380
460
575
200
230
380
460
575
200
230
380
460
575

340
299
181
150
119
366
321
195
161
128
363
319
193
160
127
402
351
213
176
141
402
351
213
176
141
434
380
230
191
152
469
412
250
206
164
469
412
250
206
164
509
445
270
224
178

YORK INTERNATIONAL

400
400
200
150
150
400
400
200
200
150
400
400
200
150
150
400
400
200
200
150
400
400
200
200
150
600
400
250
200
150
600
400
250
200
200
600
400
250
200
200
600
600
400
250
200

450
400
225
200
150
450
400
250
200
175
450
400
250
200
175
500
450
300
225
175
500
450
300
225
175
600
450
300
250
200
600
500
300
250
200
600
500
300
250
200
700
600
350
300
225

600
600
350
300
225
700
600
350
300
225
700
600
350
300
225
700
700
400
350
250
700
700
400
350
250
800
700
400
350
300
1000
800
450
400
300
1000
800
450
400
300
1000
800
500
400
350

450
400
225
200
150
450
400
250
200
175
450
400
250
200
175
500
450
300
225
175
500
450
300
225
175
600
450
300
250
200
600
500
300
250
200
600
500
300
250
200
700
600
350
300
225

600
600
350
300
225
700
600
350
300
225
700
600
350
300
225
700
700
400
350
250
700
700
400
350
250
800
700
400
350
300
1000
800
450
400
300
1000
800
450
400
300
1000
800
500
400
350

SYSTEM #2 FIELD-SUPPLIED WIRING
FACTORY PROVIDED (LUGS) WIRE RANGE7
STD. TERMINAL OPT. NF SVC.
OPT. C.B.
BLOCK
DISC SW.
(2) # 2 - 300
(2) 3/0-250
(3) 2/0-400
(2) # 2 - 300
(2) 3/0-250
(2) 3/0-250
# 2 - 300
# 6 AWG - 350
# 6 AWG - 350
# 2 - 4/0
# 6 AWG - 350
# 6 AWG - 350
# 2 - 4/0
# 6 AWG - 350
# 6 AWG - 350
(2) # 2 - 300
(2) 3/0-250
(3) 2/0-400
(2) # 2 - 300
(2) 3/0-250
(2) 3/0-250
# 2 - 300
# 6 AWG - 350
# 6 AWG - 350
# 2 - 300
# 6 AWG - 350
# 6 AWG - 350
# 2 - 4/0
# 6 AWG - 350
# 6 AWG - 350
(2) # 2 - 300
(2) 3/0-250
(3) 2/0-400
(2) # 2 - 300
(2) 3/0-250
(2) 3/0-250
# 2 - 300
# 6 AWG - 350
# 6 AWG - 350
# 2 - 300
# 6 AWG - 350
# 6 AWG - 350
# 2 - 4/0
# 6 AWG - 350
# 6 AWG - 350
(2) # 1 - 500
(2) 3/0-250
(3) 2/0-400
(2) # 2 - 300
(2) 3/0-250
(3) 2/0-400
# 1 - 500
# 6 AWG - 350
(2) 3/0-250
# 2 - 300
# 6 AWG - 350
# 6 AWG - 350
# 2 - 4/0
# 6 AWG - 350
# 6 AWG - 350
(2) # 1 - 500
(2) 3/0-250
(3) 2/0-400
(2) # 2 - 300
(2) 3/0-250
(3) 2/0-400
# 1 - 500
# 6 AWG - 350
(2) 3/0-250
# 2 - 300
# 6 AWG - 350
# 6 AWG - 350
# 2 - 4/0
# 6 AWG - 350
# 6 AWG - 350
(2) # 1 - 500
(3) 2/0-400
(3) 2/0-400
(2) # 1 - 500
(2) 3/0-250
(3) 2/0-400
# 1 - 500
# 6 AWG - 350
(2) 3/0-250
# 2 - 300
# 6 AWG - 350
# 6 AWG - 350
# 2 - 4/0
# 6 AWG - 350
# 6 AWG - 350
(2) # 1 - 500
(3) 2/0-400
(3) 2/0-400
(2) # 1 - 500
(2) 3/0-250
(3) 2/0-400
# 1 - 500
# 6 AWG - 350
(2) 3/0-250
# 1 - 500
# 6 AWG - 350
# 6 AWG - 350
# 2 - 300
# 6 AWG - 350
# 6 AWG - 350
(2) # 1 - 500
(3) 2/0-400
(3) 2/0-400
(2) # 1 - 500
(2) 3/0-250
(3) 2/0-400
# 1 - 500
# 6 AWG - 350
(2) 3/0-250
# 1 - 500
# 6 AWG - 350
# 6 AWG - 350
# 2 - 300
# 6 AWG - 350
# 6 AWG - 350
(2) # 1 - 500
(3) 2/0-400
(3) 2/0-400
(2) # 1 - 500
(3) 2/0-400
(3) 2/0-400
# 1 - 500
(2) 3/0-250
(2) 3/0-250
# 1 - 500
# 6 AWG - 350
(2) 3/0-250
# 2 - 300
# 6 AWG - 350
# 6 AWG - 350

COMPRESSOR
RLA

Y-LRA

X-LRA

246
214
130
107
86
267
232
140
116
93
265
230
139
115
92
295
256
155
128
103
295
256
155
128
103
321
279
169
140
112
342
298
181
149
119
342
298
181
149
119
374
325
197
163
130

444
386
234
193
154
444
386
234
193
154
444
386
234
193
154
656
571
360
285
238
656
571
360
285
238
656
571
360
285
238
656
571
360
285
238
656
571
360
285
238
656
571
360
285
238

1332
1158
701
579
463
1332
1158
701
579
463
1332
1158
701
579
463
1969
1712
1081
856
715
1969
1712
1081
856
715
1969
1712
1081
856
715
1969
1712
1081
856
715
1969
1712
1081
856
715
1969
1712
1081
856
715

FANS
FLA (EA)
8.2
7.8
4.8
4.0
3.1
8.2
7.8
4.8
4.0
3.1
8.2
7.8
4.8
4.0
3.1
8.2
7.8
4.8
4.0
3.1
8.2
7.8
4.8
4.0
3.1
8.2
7.8
4.8
4.0
3.1
8.2
7.8
4.8
4.0
3.1
8.2
7.8
4.8
4.0
3.1
8.2
7.8
4.8
4.0
3.1

5

ELECTRICAL DATA (Continued)
OPTIONAL SINGLE-POINT POWER SUPPLY WITH INTERNAL CIRCUIT BREAKERS

(One Field Provided Power Supply Circuit to the chiller. Field connections to Power Terminal Block or Non-Fused Disconnect in ‘Option Panel’.
Internal Branch Circuit Protection (Breakers) per Motor Control Center)

MODEL
YCAS

0130EC

0140EC

0150EC

0160EC

0170EC

0180EC

0200EC

0210EC

0230EC

VOLTS
MCA1
200
230
380
460
575
200
230
380
460
575
200
230
380
460
575
200
230
380
460
575
200
230
380
460
575
200
230
380
460
575
200
230
380
460
575
200
230
380
460
575
200
230
380
460
575

619
544
330
273
217
666
584
354
293
234
699
612
371
307
246
729
638
387
320
257
762
667
405
335
268
788
690
419
347
277
852
749
455
375
299
892
782
475
393
313
924
809
491
407
324

FIELD-SUPPLIED WIRING
FIELD PROVIDED POWER SUPPLY
FACTORY PROVIDED (LUGS) WIRE RANGE
MIN NF
D.E. FUSE
C.B.
TERMINAL BLOCK
NF SERVICE DISC SW
DISC SW2
MIN.3 MAX.4
MIN.3
MAX.4
(LUGS) WIRE RANGE7
RATING2
(LUGS) WIRE RANGE7
RATING2
800
700
1000
700
1000
(3) # 1 - 500
1140
(3) 2/0-400
800
600
600
800
600
800
(2) # 1 - 500
760
(3) 2/0-400
600
400
400
500
400
500
(2) # 2 - 300
550
(2) 3/0-250
400
400
300
400
300
400
# 1 - 500
380
(2) 3/0-250
400
250
250
350
250
350
# 1 - 500
380
# 6 AWG - 350
250
800
800
1000
800
1000
(3) # 1 - 500
1140
(3) 2/0-400
800
800
700
1000
700
1000
(3) # 1 - 500
1140
(3) 2/0-400
600
400
400
500
400
500
(2) # 2 - 300
550
(2) 3/0-250
400
400
350
450
350
450
(2) # 2 - 300
550
(2) 3/0-250
400
250
300
350
300
350
# 1 - 500
380
# 6 AWG - 350
250
800
800
1000
800
1000
(3) # 1 - 500
1140
(3) 2/0-400
800
800
700
1000
700
1000
(3) # 1 - 500
1140
(3) 2/0-400
800
400
450
600
450
600
(2) # 1 - 500
760
(2) 3/0-250
400
400
350
450
350
450
(2) # 2 - 300
550
(2) 3/0-250
400
400
300
350
300
350
# 1 - 500
380
(2) 3/0-250
400
800
1000
1200
1000
1200
(3) # 1 - 500
1140
(3) 2/0-400
800
800
800
1000
800
1000
(3) # 1 - 500
1140
(3) 2/0-400
800
600
450
600
450
600
(2) # 1 - 500
760
(3) 2/0-400
600
400
400
450
400
450
(2) # 2 - 300
550
(2) 3/0-250
400
400
300
400
300
400
# 1 - 500
380
(2) 3/0-250
400
800
1000
1200
1000
1200
(3) # 1 - 500
1140
(3) 2/0-400
800
800
800
1000
800
1000
(3) # 1 - 500
1140
(3) 2/0-400
800
600
450
600
450
600
(2) # 1 - 500
760
(3) 2/0-400
600
400
400
500
400
500
(2) # 2 - 300
550
(2) 3/0-250
400
400
300
400
300
400
# 1 - 500
380
(2) 3/0-250
400
1000
1000
1200
1000
1200
(3) # 1 - 500
1140
(4) 4/0-500
1000
800
800
1000
800
1000
(3) # 1 - 500
1140
(3) 2/0-400
800
600
500
600
500
600
(2) # 1 - 500
760
(3) 2/0-400
600
400
400
500
400
500
(2) # 2 - 300
550
(2) 3/0-250
400
400
350
400
350
400
(2) # 2 - 300
550
(2) 3/0-250
400
1000
1000
1200
1000
1200
(3) # 1 - 500
1140
(4) 4/0-500
1000
800
1000
1200
1000
1200
(3) # 1 - 500
1140
(3) 2/0-400
800
600
600
700
600
700
(2) # 1 - 500
760
(3) 2/0-400
600
400
450
600
450
600
(2) # 1 - 500
760
(2) 3/0-250
400
400
350
450
350
450
(2) # 2 - 300
550
(2) 3/0-250
400
1000
1000
1600
1000
1600
(3) # 1 - 500
1140
(4) 4/0-500
1000
1000
1000
1200
1000
1200
(3) # 1 - 500
1140
(4) 4/0-500
1000
600
600
700
600
700
(2) # 1 - 500
760
(3) 2/0-400
600
600
450
600
450
600
(2) # 1 - 500
760
(3) 2/0-400
600
400
350
450
350
450
(2) # 2 - 300
550
(2) 3/0-250
400
1000
1200
1600
1200
1600
(3) # 1 - 500
1140
(4) 4/0-500
1000
1000
1000
1200
1000
1200
(3) # 1 - 500
1140
(4) 4/0-500
1000
600
600
700
600
700
(2) # 1 - 500
760
(3) 2/0-400
600
600
450
600
450
600
(2) # 1 - 500
760
(3) 2/0-400
600
400
400
500
400
500
(2) # 2 - 300
550
(2) 3/0-250
400

See page 6 for notes.

6

YORK INTERNATIONAL

FORM 201.18-W1

MODEL
YCAS

0130EC

0140EC

0150EC

0160EC

0170EC

0180EC

0200EC

0210EC

0230EC

VOLTS
200
230
380
460
575
200
230
380
460
575
200
230
380
460
575
200
230
380
460
575
200
230
380
460
575
200
230
380
460
575
200
230
380
460
575
200
230
380
460
575
200
230
380
460
575

YORK INTERNATIONAL

SYSTEM #1
COMPRESSOR DATA

FAN DATA

FACTORY
C.B.

RLA

Y-LRA

X-LRA

600
400
250
250
160
600
400
250
250
160
600
600
400
250
250
600
600
400
250
250
600
600
400
250
250
600
600
400
250
250
600
600
400
250
250
600
600
400
400
250
600
600
400
400
250

246
214
130
107
86
267
232
140
116
93
295
256
155
128
103
295
256
155
128
103
321
279
169
140
112
321
279
169
140
112
342
298
181
149
119
374
325
197
163
130
374
325
197
163
130

444
386
234
193
154
444
386
234
193
154
656
571
360
285
238
656
571
360
285
238
656
571
360
285
238
656
571
360
285
238
656
571
360
285
238
656
571
360
285
238
656
571
360
285
238

1332
1158
701
579
463
1332
1158
701
579
463
1969
1712
1081
856
715
1969
1712
1081
856
715
1969
1712
1081
856
715
1969
1712
1081
856
715
1969
1712
1081
856
715
1969
1712
1081
856
715
1969
1712
1081
856
715

SYSTEM #2
COMPRESSOR DATA

FAN DATA

FLA (EA)

FACTORY
C.B.

RLA

Y-LRA

X-LRA

FLA (EA)

8.2
7.8
4.8
4.0
3.1
8.2
7.8
4.8
4.0
3.1
8.2
7.8
4.8
4.0
3.1
8.2
7.8
4.8
4.0
3.1
8.2
7.8
4.8
4.0
3.1
8.2
7.8
4.8
4.0
3.1
8.2
7.8
4.8
4.0
3.1
8.2
7.8
4.8
4.0
3.1
8.2
7.8
4.8
4.0
3.1

600
400
250
250
160
600
400
250
250
160
600
400
250
250
160
600
600
400
250
250
600
600
400
250
250
600
600
400
250
250
600
600
400
250
250
600
600
400
250
250
600
600
400
400
250

246
214
130
107
86
267
232
140
116
93
265
230
139
115
92
295
256
155
128
103
295
256
155
128
103
321
279
169
140
112
342
298
181
149
119
342
298
181
149
119
374
325
197
163
130

444
386
234
193
154
444
386
234
193
154
444
386
234
193
154
656
571
360
285
238
656
571
360
285
238
656
571
360
285
238
656
571
360
285
238
656
571
360
285
238
656
571
360
285
238

1332
1158
701
579
463
1332
1158
701
579
463
1332
1158
701
579
463
1969
1712
1081
856
715
1969
1712
1081
856
715
1969
1712
1081
856
715
1969
1712
1081
856
715
1969
1712
1081
856
715
1969
1712
1081
856
715

8.2
7.8
4.8
4.0
3.1
8.2
7.8
4.8
4.0
3.1
8.2
7.8
4.8
4.0
3.1
8.2
7.8
4.8
4.0
3.1
8.2
7.8
4.8
4.0
3.1
8.2
7.8
4.8
4.0
3.1
8.2
7.8
4.8
4.0
3.1
8.2
7.8
4.8
4.0
3.1
8.2
7.8
4.8
4.0
3.1

7

ELECTRICAL DATA (Continued)
OPTIONAL SINGLE POINT POWER SUPPLY CONNECTION TO FACTORY CIRCUIT BREAKER
(One Field Provided Power Supply Circuit to the chiller. Field Connection to Circuit Breaker in ‘Option Panel’.
No internal Branch Circuit Protection per Motor Control Center.)

MODEL
YCAS
0130EC
0140EC
0150EC
0160EC
0170EC
0180EC
0200EC
0210EC
0230EC

VOLTS
460
575
460
575
460
575
460
575
460
575
460
575
460
575
460
575
460
575

MCA1
273
217
293
234
307
246
320
257
335
268
347
277
375
299
393
313
407
324

FIELD SUPPLIED WIRING
FACTORY SUPPLIED BREAKER
WIRE RANGE7 (LUGS)
RATING2
400
(2) 3/0-250
250
# 6 AWG - 350
400
(2) 3/0-250
400
(2) 3/0-250
400
(2) 3/0-250
400
(2) 3/0-250
400
(2) 3/0-250
400
(2) 3/0-250
400
(2) 3/0-250
400
(2) 3/0-250
400
(2) 3/0-250
400
(2) 3/0-250
630
(3) 2/0-400
400
(2) 3/0-250
630
(3) 2/0-400
400
(2) 3/0-250
630
(3) 2/0-400
400
(2) 3/0-250

SYSTEM #1
COMPRESSOR
RLA
X-LRA
107
579
86
463
116
579
93
463
128
856
103
715
128
856
103
715
140
856
112
715
140
856
112
715
149
856
119
715
163
856
130
715
163
856
130
715

FANS
FLA (EA)
4.0
3.1
4.0
3.1
4.0
3.1
4.0
3.1
4.0
3.1
4.0
3.1
4.0
3.1
4.0
3.1
4.0
3.1

SYSTEM #2
COMPRESSOR
RLA
X-LRA
107
579
86
463
116
579
93
463
115
579
92
463
128
856
103
715
128
856
103
715
140
856
112
715
149
856
119
715
149
856
119
715
163
856
130
715

FANS
FLA (EA)
4.0
3.1
4.0
3.1
4.0
3.1
4.0
3.1
4.0
3.1
4.0
3.1
4.0
3.1
4.0
3.1
4.0
3.1

NOTE: Wye-Delta Compressor Start not available with this option.

NOTES (pages 2 - 7)
1. Minimum circuit ampacity (MCA) is based on 125% of the rated load amps for the largest motor plus 100% of the rated load amps for all
other loads included in the circuit, per N.E.C. Article 430-24. If a Factory Mounted Control Transformer is provided, add the following to
the system #2 MCA values in the YCAS Tables: -17, add 10 amps; -28, add 9 amps; -40, add 5 amps; -46, add 4 amps; -58, add 3 amps.
2. The recommendation disconnect switch is based on a minimum of 115% of the summation rated load amps of all the loads included in the
circuit, per N.E.C. 440 - 12A1.
3. Minimum fuse size is based on 150% of the largest motor RLA plus 100% of the remaining RLAs (U.L. Standard 1995, Section 36.1).
Minimum fuse rating = (1.5 x largest compressor RLA) + other compressor RLAs + (# fans x each fan motor FLA).
4. Maximum dual element fuse size is based on 225% maximum plus 100% of the rated load amps for all other loads included in the circuit,
per N.E.C. 440-22. Maximum fuse rating = (2.25 x largest compressor RLA) + other compressor RLAs + (# fans x each fan motor FLA).
5. Minimum circuit breaker is 150% maximum plus 100% of rated load amps included in the circuit, per circuit per U.L. 1995 Fig. 36.2.
Minimum circuit breaker rating = (1.5 x largest compressor RLA) + other compressor RLAs + (# fans x each fan motor FLA).
6. Maximum circuit breaker is based on 225% maximum plus 100% of the rated load amps for all loads included in the circuit, per circuit, per
U.L. 1995 Fig. 36.2. Maximum circuit breaker rating = (2.25 x largest compressor RLA) + other compressor RLAs + ( # fans x each fan
motor FLA).
7. The Incoming Wire Range is the minimum and maximum wire size that can be accommodated by unit wiring lugs. The (1), (2), or (3)
indicate the number of termination points or lugs which are available per phase. Actual wire size and number of wires per phase must be
determined based on ampacity and job requirements using N.E.C. wire sizing information. The above recommendations are based on the
National Electric Code and using copper connectors only. Field wiring must also comply with local codes.
8. A ground lug is provided for each compressor system to accommodate field grounding conductor per N.E.C. Article 250-54. A control
circuit grounding lug is also supplied. Incoming ground wire range is #6 - 350 MCM.
9. The field supplied disconnect is a “Disconnecting Means” as defined in N.E.C. 100.B, and is intended for isolating the unit from the
available power supply to perform maintenance and troubleshooting. This disconnect is not intended to be a Load Break Device.
10. Units equipped with Star-Delta compressor motor start must also include Factory provided circuit breakers in each motor control center.
11. The wiring recommendations are based on the National Electrical Code using copper connectors only. Field wiring must also comply with
local codes.

8

YORK INTERNATIONAL

FORM 201.18-W1

OPTIONAL SINGLE POINT POWER SUPPLY CONNECTION WITH FIELD SUPPLIED CIRCUIT PROTECTION
(One Field Provided Power Supply Circuit to the chiller. Field Connection to Power Terminal Block or Disconnect Switch in the ‘Option Panel’.
No internal Branch Circuit Protection per Motor Control Center.)

FIELD SUPPLIED WIRING
SYSTEM #1
MODEL
FIELD PROVIDED POWER SUPPLY
FACTORY PROVIDED (LUGS) WIRE RANGE
COMPRESSOR FANS
VOLTS
YCAS
MIN NF
D.E. FUSE
TERMINAL BLOCK
NF SERV DISC SW
DATA
DATA
MCA1
DISC SW2 MIN3 MAX4 (LUGS) WIRE RANGE7 RATING2 (LUGS) WIRE RANGE7 RLA X-LRA FLA (EA)
460
273
400
300
400
# 1 - 500
400
(2) 3/0-250
107
579
4.0
0130EC
575
217
250
250
350
# 1 - 500
250
# 6 AWG - 350
86
463.2
3.1
460
293
400
350
450
(2) # 2 - 300
400
(2) 3/0-250
116
579
4.0
0140EC
575
234
250
300
350
# 1 - 500
250
# 6 AWG - 350
93
463.2
3.1
460
307
400
350
450
(2) # 2 - 300
400
(2) 3/0-250
128
856
4.0
0150EC
575
246
400
300
350
# 1 - 500
250
# 6 AWG - 350
103
715
3.1
460
320
400
400
450
(2) # 2 - 300
400
(2) 3/0-250
128
856
4.0
0160EC
575
257
400
300
400
# 1 - 500
400
(2) 3/0-250
103
715
3.1
460
335
400
400
500
(2) # 2 - 300
400
(2) 3/0-250
140
856
4.0
0170EC
575
268
400
300
400
# 1 - 500
400
(2) 3/0-250
112
715
3.1
460
347
400
400
500
(2) # 2 - 300
400
(2) 3/0-250
140
856
4.0
0180EC
575
277
400
350
400
(2) # 2 - 300
400
(2) 3/0-250
112
715
3.1
460
375
400
450
600
(2) # 1 - 500
400
(2) 3/0-250
149
856
4.0
0200EC
575
299
400
350
450
(2) # 2 - 300
400
(2) 3/0-250
119
715
3.1
460
393
600
450
600
(2) # 1 - 500
400
(2) 3/0-250
163
856
4.0
0210EC
575
313
400
350
450
(2) # 2 - 300
400
(2) 3/0-250
130
715
3.1
460
407
600
450
600
(2) # 1 - 500
630
(3) 2/0-400
163
856
4.0
0230EC
575
324
400
400
500
(2) # 2 - 300
400
(2) 3/0-250
130
715
3.1

LEGEND
ACR-LINE
C.B.
D.E.
DISC SW
FACT MOUNT CB
FLA
HZ
MAX
MCA
MIN
MIN NF
RLA
S.P. WIRE
UNIT MTD SERV SW
WYE-DELTA
X-LRA
Y-LRA

SYSTEM #2
COMPRESSOR FANS
DATA
DATA
RLA X-LRA FLA (EA)
107
579
4.0
86
463
3.1
116
579
4.0
93
463
3.1
115
579
4.0
92
463
3.1
128
856
4.0
103
715
3.1
128
856
4.0
103
715
3.1
140
856
4.0
112
715
3.1
149
856
4.0
119
715
3.1
149
856
4.0
119
715
3.1
163
856
4.0
130
715
3.1

ACROSS THE LINE START
CONTROL POWER SUPPLY
CIRCUIT BREAKER
CONTROL
MIN
MAX DUAL NON-FUSED
UNIT
DUAL ELEMENT FUSE
POWER
CIRCUIT
ELEMENT DISC. SW.
DISCONNECT SWITCH
VOLTAGE
SUPPLY AMPACITY FUSE SIZE
SIZE
FACTORY-MOUNTED CIRCUIT BREAKER
Standard
FULL LOAD AMPS
Models w/o 115-1-60
20A
20A
30A
HERTZ
Transformers
MAXIMUM
MINIMUM CIRCUIT AMPACITY
MINIMUM
MINIMUM NON-FUSED
VOLTAGE CODE
RUNNING LOAD AMPS
-17 = 200-3-60
SINGLE-POINT WIRING
-28 = 230-3-60
UNIT-MOUNTED SERVICE (NON-FUSED DISCONNECT SWITCH)
-40 = 380-3-60
WYE-DELTA START
-46 = 460-3-60
ACROSS-THE-LINE INRUSH LOCKED ROTOR AMPS
-58 = 575-3-60
WYE-DELTA INRUSH LOCKED ROTOR AMPS

YORK INTERNATIONAL

9

WIRING DIAGRAM
ACROSS-THE-LINE START
NOTES:
1. Field wiring to be in accordance with the current
edition of the National Electrical Code as well as all
other applicable codes and specifications.
2. Numbers along the right side of a diagram are line
identification numbers. The numbers at each line
indicate the line number location of relay contacts.
An unlined contact location signifies a normally closed
contact. Numbers adjacent to circuit lines are the
circuit identification numbers.
3. Any customer supplied contacts must be suitable
for switching 24VDC. (Gold contacts recommended.) Control Wiring must not be run in the same
conduit with any line voltage wiring.
4. To cycle unit on and off automatically with contact
shown, install a cycling device in series with the
flow switch (FSLW). See Note 3 for contact rating
and wiring specifications. Also refer to cautions on
the following page.
5. To stop unit (Emergency Stop) with contacts other
than those shown, install the stop contact between
5 and 1. If a stop device is not installed, a jumper
must be connected between terminals 5 and 1. Device must have a minimum contact rating of 100VA
at 115 volts A.C.
6. Alarm contacts are for annunciating alarm/unit malfunction. Contacts are rated at 115V, 100VA, resistive load only, and must be suppressed at load by
user.

LD03226

7. See Installation, Operation and Maintenance Manual
when optional equipment is used.
8. Control panel to be securely connected to earth
ground.
9. Us 2KVA transformer in optional transformer kit unless there are optional oil separator sump heaters
which necessitates using a 3KVA transformer.

LD03227

LEGEND
TS

Transient Voltage Suppression
Terminal Block for Customer Connections
Terminal Block for Customer Low Voltage
(Class 2) Connections. See Note 2
Terminal Block for YORK Connections Only
Wiring and Components by YORK
Optional Equipment
Wiring and/or Components by Others

FIG. 1 – ELEMENTARY DIAGRAM – ACROSS-THE-LINE START

10

YORK INTERNATIONAL

FORM 201.18-W1

WIRING DIAGRAM
ACROSS-THE-LINE START

LD03228

YORK INTERNATIONAL

11

ELEMENTARY DIAGRAM

FIG. 1 – CONTINUED

12

YORK INTERNATIONAL

FORM 201.18-W1

LD03279

ELEMENTARY DIAGRAM

CAUTION:
No Controls (relays, etc.) should
be mounted in the Smart Panel
enclosure or connected to power
supplies in the control panel.
Additionally, control wiring not
connected to the Smart Panel
should not be run through the
cabinet. This could result in nuisance faults.
CAUTION:
Any inductive devices (relays)
wired in series with the flow
switch for start/stop, into the
Alarm circuitry, or pilot relays
for pump starters wired through
motor contactor auxiliary contacts must be suppressed with
YORK P/N 031-00808-000 suppressor across the relay/
contactor coil.
Any contacts connected to flow
switch inputs or BAS inputs on
terminals 13 - 19 or TB3, or any
other terminals, must be suppressed with a YORK P/N 03100808-000 suppressor across
the relay/contactor coil.
CAUTION:
Control wiring connected to the
control panel should never be
run in the same conduit with
power wiring.

CONTROL POWER SUPPLY
UNIT
VOLTAGE
ALL MODELS
W/O TRANS.
MODELS
-17
WITH
-28
TRANS.
-46
*
-58

CONTROL
POWER
SUPPLY

MIN
CIRCUIT
AMP.

MAX DUAL
ELEMENT
FUSE SIZE

NON-FUSED
DISC.
SWITCH SIZE

115-1-50/60

20A

20A 250V

30A 240V

200-1-60
230-1-60
400-1-60
575-1-60

15A
15A
8A
8A

15A 250V
15A 250V
8A 600V
8A 600V

30A
30A
30A
30A

240V
240V
480V
600V

* All primary and secondary wiring between transformer and control panel included.

YORK INTERNATIONAL

13

WIRING DIAGRAM
WYE-DELTA START
NOTES:
1. Field wiring to be in accordance with the current
edition of the National Electrical Code as well as all
other applicable codes and specifications.
2. Numbers along the right side of a diagram are line
identification numbers. The numbers at each line
indicate the line number location of relay contacts.
An unlined contact location signifies a normally closed
contact. Numbers adjacent to circuit lines are the
circuit identification numbers.
3. Any customer supplied contacts must be suitable
for switching 24VDC. (Gold contacts recommended.) Control Wiring must not be run in the same
conduit with any line voltage wiring.
4. To cycle unit on and off automatically with contact
shown, install a cycling device in series with the
flow switch (FSLW). See Note 3 for contact rating
and wiring specifications. Also refer to cautions on
the following page.
5. To stop unit (Emergency Stop) with contacts other
than those shown, install the stop contact between
5 and 1. If a stop device is not installed, a jumper
must be connected between terminals 5 and 1. Device must have a minimum contact rating of 100VA
at 115 volts A.C.
6. Alarm contacts are for annunciating alarm/unit malfunction. Contacts are rated at 115V, 100VA, resistive load only, and must be suppressed at load by
user.

LD03226

7. See Installation, Operation and Maintenance Manual
when optional equipment is used.
8. Control panel to be securely connected to earth
ground.
9. Us 2KVA transformer in optional transformer kit unless there are optional oil separator sump heaters
which necessitates using a 3KVA transformer.

LD03227

LEGEND
TS

Transient Voltage Suppression
Terminal Block for Customer Connections
Terminal Block for Customer Low Voltage
(Class 2) Connections. See Note 2
Terminal Block for YORK Connections Only
Wiring and Components by YORK
Optional Equipment
Wiring and/or Components by Others

FIG. 1 – ELEMENTARY DIAGRAM – WYE-DELTA START

14

YORK INTERNATIONAL

FORM 201.18-W1

WIRING DIAGRAM
WYE-DELTA START

LD03229

YORK INTERNATIONAL

15

ELEMENTARY DIAGRAM

FIG. 1 – CONTINUED

16

YORK INTERNATIONAL

FORM 201.18-W1

LD03279

ELEMENTARY DIAGRAM

CAUTION:
No Controls (relays, etc.) should
be mounted in the Smart Panel
enclosure or connected to power
supplies in the control panel.
Additionally, control wiring not
connected to the Smart Panel
should not be run through the
cabinet. This could result in nuisance faults.
CAUTION:
Any inductive devices (relays)
wired in series with the flow
switch for start/stop, into the
Alarm circuitry, or pilot relays
for pump starters wired through
motor contactor auxiliary contacts must be suppressed with
YORK P/N 031-00808-000 suppressor across the relay/
contactor coil.
Any contacts connected to flow
switch inputs or BAS inputs on
terminals 13 - 19 or TB3, or any
other terminals, must be suppressed with a YORK P/N 03100808-000 suppressor across
the relay/contactor coil.
CAUTION:
Control wiring connected to the
control panel should never be
run in the same conduit with
power wiring.

CONTROL POWER SUPPLY
UNIT
VOLTAGE
ALL MODELS
W/O TRANS.
MODELS
-17
WITH
-28
TRANS.
-46
*
-58

CONTROL
POWER
SUPPLY

MIN
CIRCUIT
AMP.

MAX DUAL
ELEMENT
FUSE SIZE

NON-FUSED
DISC.
SWITCH SIZE

115-1-50/60

20A

20A 250V

30A 240V

200-1-60
230-1-60
400-1-60
575-1-60

15A
15A
8A
8A

15A 250V
15A 250V
8A 600V
8A 600V

30A
30A
30A
30A

240V
240V
480V
600V

* All primary and secondary wiring between transformer and control panel included.

YORK INTERNATIONAL

17

18

YORK INTERNATIONAL

FORM 201.18-W1

LD03280

YORK INTERNATIONAL

19

LEGEND

LD03281

20

YORK INTERNATIONAL

FORM 201.18-W1

LD03282

LD03283

LD03284

YORK INTERNATIONAL

21

CONNECTION DIAGRAM (SYSTEM WIRING)

LD03230

LD03231

LD03232

22

YORK INTERNATIONAL

FORM 201.18-W1

COMPRESSOR TERMINAL BOX

LD03233

YORK INTERNATIONAL

23

MULTI-POINT POWER SUPPLY WIRING – STANDARD UNIT

LD03254

SINGLE POINT POWER SUPPLY – WIRING WITH CIRCUIT BREAKERS

LD03255

24

YORK INTERNATIONAL

FORM 201.18-W1

SINGLE POINT POWER WIRING WITH FIELD SUPPLIED CIRCUIT PROTECTION

LD03256

SINGLE POINT POWER WIRING WITH CIRCUIT BREAKERS

LD03257

YORK INTERNATIONAL

25

ELECTRICAL POWER WIRING – OPTIONS: TERMINAL BLOCKS

LD03258

ELECTRICAL POWER WIRING – OPTIONS: NON FUSED DISCONNECT SWITCH

LD03259

ELECTRICAL POWER WIRING – OPTIONS: TERMINAL BLOCKS

LD03260

26

YORK INTERNATIONAL

FORM 201.18-W1

LD03286

YORK INTERNATIONAL

27

LD03286

P.O. Box 1592, York, Pennsylvania USA 17405-1592
Copyright © by York International Corporation 1998
Form 201.18-W1 (1298)
Supersedes: 201.18-W1 (798)

Subject to change without notice. Printed in USA
ALL RIGHTS RESERVED



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : Yes
Page Count                      : 28
Page Mode                       : UseOutlines
Page Layout                     : SinglePage
XMP Toolkit                     : XMP toolkit 2.9.1-13, framework 1.6
About                           : uuid:913073de-d1e7-434b-853c-89856f7a695a
Producer                        : Acrobat Distiller 3.0 for Windows
Keywords                        : Form 201.18-W1 (1298), Millennium Air Cooled Screw Liquid Chillers (Style F), Wiring Diagram
Create Date                     : 1998:11:24 10:21:49Z
Modify Date                     : 2003:06:30 17:00:31-04:00
Metadata Date                   : 2003:06:30 17:00:31-04:00
Document ID                     : uuid:371d50b2-9741-4550-8bba-ac8fa8c811cb
Format                          : application/pdf
Title                           : Form 201.18-W1 (1298), Millennium Air Cooled Screw Liquid Chillers (Style F), Wiring Diagram
Description                     : Form 201.18-W1 (1298), Millennium Air Cooled Screw Liquid Chillers (Style F), Wiring Diagram
Creator                         : York International Corporation
Author                          : York International Corporation
Subject                         : Form 201.18-W1 (1298), Millennium Air Cooled Screw Liquid Chillers (Style F), Wiring Diagram
EXIF Metadata provided by EXIF.tools

Navigation menu