York Mini Split Air Conditioner Technical Guide 923178 UTG B 0114

2015-09-09

: York Mini-Split-Air-Conditioner-Technical-Guide york-mini-split-air-conditioner-technical-guide-812458 york pdf

Open the PDF directly: View PDF PDF.
Page Count: 34

DownloadYork Mini-Split-Air-Conditioner-Technical-Guide 923178-UTG-B-0114  York-mini-split-air-conditioner-technical-guide
Open PDF In BrowserView PDF
923178-UTG-B-0114

TECHNICAL
GUIDE
LX SERIES
DUCTLESS SINGLE-SPLIT
AIR CONDITIONERS AND HEAT PUMPS
16 SEER – 1 PHASE
3/4 THRU 2 NOMINAL TONS

MODELS: DCMF/DHMF

Due to continuous product improvement, specifications
are subject to change without notice.
Visit us on the web at

www.upgnet.com
Additional rating information can be found at

www.ahridirectory.org
WARRANTY SUMMARY*
Standard 2-Years limited parts warranty.
Standard 6-Years limited compressor warranty.

DESCRIPTION
The Single-Split Series are ductless climate systems. They are
designed with a matching indoor unit for optimum performance and efficiency. These climate systems are supported with accessories and documents to serve specific functions.

FEATURES
Variable Frequency Rotary Compressor - Twin rotary inverter compressor
on all models features high efficiency operation that modulates down to 15
Hz and as high as 120 Hz for reduced vibration and quiet operation. Brushless DC motor uses powerful Neodymium magnets that are approximately
15-20 times stronger than ferrite magnets used in conventional AC compressors. The DC Inverter Control provides continuous operation, while adjusting
capacity according to room temperature. The accurate sensing of cooling or
heating loads prevents frequent changes in capacity and ensures efficient,
economical operation.
Low Ambient Cooling Operation Down to 5 °F - This feature allows for a
space to be air-conditioned even in outdoor temperatures as low as 5 °F.
This cooling ability is important when dealing with server equipment rooms,
surveillance mechanical rooms, restaurant kitchens, fitness centers, and
more.
Load Variation Management System - The outdoor coil thermistor continuously monitors the temperature and communicates with the microprocessor.
Depending on the temperature measured, the compressor will be allowed to
increase the frequency if needed to meet the load or reduce frequency as
the load is reduced.
High Pressure Discharge Temperature - The compressor discharge line
thermistor continuously monitors the temperature and communicates with
the microprocessor. Depending on the temperature measured, the compressor will be allowed to increase the frequency to meet the load or is forced to
run at the current or reduced frequency. If the temperature gets excessively
high, the compressor will be de-energized.
Defrost Control (Heat Pump Models) - Defrost cycle is automatically
enabled if there is a build-up of frost on the outdoor coil. Outdoor fan and
indoor blower operation is terminated during the defrost cycle. H1 is displayed on the indoor unit panel on the front cover during a defrost cycle.
Reversing Valve (Heat Pump Models) - 4-way interchange reversing valve
effects a rapid change in direction of refrigerant flow resulting in quick
changeover from cooling to heating and vice versa. Valve operates on system pressure differential between outdoor unit and indoor unit.
R-410A Refrigerant - Unit is pre-charged with R410A refrigerant that uses
PVE refrigerant oil. Polyvinyl ether (PVE) is an innovative refrigerant oil specially formulated for hydrofluorocarbon (HFC) refrigeration systems. In addition to providing lubricating properties, it also has a number of other applied
advantages that help to increase the reliability of the refrigeration systems
where it is applied.
Refrigerant Line Connections, Service Valve - Outdoor units are designed
with easy service and maintenance in mind. Maintenance points are located
behind easy-access panels, to make installation and service a breeze for a
trained technician. Flare connection lines are located on side of unit cabinet.
Fully serviceable brass service valve prevents corrosion and provide access
to refrigerant system. Shut-off valve that can be fully shut off while 2-way
suction/vapor valve (with service port) may be front seated to manage refrigerant charge while servicing system.
Air Deflection Louvers - Horizontal louvers default to the cooling or heating
position when the unit is operating. Horizontal louvers can be set to a preset
oscillating range or fixed position from the wireless remote control. Full oscillating is the default setting when button is pushed. Vertical louvers can be
manually adjusted to direct the airflow for optimal comfort.
Indoor Coil Freeze Protection - The indoor coil thermistor monitors the coil
temperature continuously. Any time the coil temperature drops below 30°F,
the compressor and the outdoor fan (30 seconds later) will be switched off
until the coil temperature rises above 43°F and the compressor has been off
for a minimum of 3 minutes.
I FEEL Function - When I FEEL is activated, the system will satisfy the cooling or heating temperature setpoint where the remote control is located.
When I FEEL is deactivated, the system will satisfy the cooling or heating
temperature setpoint where the indoor unit is located. This feature provides
homeowners with optimum comfort whether they are near or far from the
indoor unit.
Hot Heat Pump (cold air prevention) - In heating mode, the indoor fan will
be delayed from 1 to 3 minutes to allow refrigerant to warm up and avoid
cold blow. This may occur during:
• Initial start-up of a heating cycle
• Immediately after completion of an Auto mode operation
• Heating under extremely low indoor temperatures

FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

923178-UTG-B-0114

2

Johnson Controls Unitary Products

923178-UTG-B-0114

SPECIFICATIONS
AIR CONDITIONERS
DCMF09NWM42Q1

DCMF12NWM42Q1

DCMF18NWM42Q1

DCMF24NWM42Q1

DCMF09CSM42Q1

DCMF12CSM42Q1

DCMF18CSM42Q1

DCMF24CSM42Q1

Function

Cooling

Cooling

Cooling

Cooling

Rated Voltage

208/230

208/230

208/230

208/230

Model (Indoor/Outdoor)

Frequency (Hz)
Total Capacity (BTUH) (High/Standard/Low)
Total Capacity (W) (High/Standard/Low)

60Hz

60Hz

60Hz

60Hz

11500/9000/3800

12500/12000/3300

21000/18000/4500

24000/22000/6400
7032/6446/1875

3370/2637/1114

3663/3516/967

6155/5276/1319

Rated Power Input (W)

882

1224

1621

2200

Nominal Input Current (A)

4.01

5.56

7.37

10.00

SEER

16.00

16.00

16.00

16.00

Air Flow Volume (CFM) (H/M/L)

330/300/260/210

340/300/260/210

470/400/330/270

590/440/300/200

Air Flow Volume (m3/h) (H/M/L)

560/510/440/370

580/520/440/370

800/680/560/460

1000/750/520/350

Dehumidifying Volume (cu.ft./h)

0.028

0.049

0.064

0.075

Dehumidifying Volume (l/h)

0.80

1.40

1.80

2.13

EER

10.2

9.8

11.1

10

Model of Indoor Unit

DCMF09NWM42Q1

DCMF12NWM42Q1

DCMF18NWM42Q1

DCMF24NWM42Q1

Fan Motor Speed (r/min) (SH/H/M/L)

1450/1180/1000/850

1300/1100/900/700

1350/1150/950/750

1400/1150/1000/850

Output of Fan Motor (w)

15

15

20

36

Fan Motor Capacitor (uF)

1.2

1.2

1.5

2.5

Fan Motor RLA (A)

0.19

0.19

0.32

0.45

Cross-flow - 1

Cross-flow - 1

Cross-flow - 1

Cross-flow - 1

Diameter-Length (inch)

3.6 × 23.4

3.6 × 23.4

3.9 × 25.6

3.9 × 30.1

Diameter-Length (mm)

92 × 594

92 × 595

98 × 650

98 × 765

Fan Type-Piece

Indoor Unit

Evaporator

Aluminum Fin-copper Tube Aluminum Fin-copper Tube Aluminum Fin-copper Tube Aluminum Fin-copper Tube

Pipe Diameter (inch)

Φ 0.276

Φ 0.276

Φ 0.276

Pipe Diameter (mm)

φ7

φ7

φ7

φ7

Row-Fin Gap (inch)

2 - 0.055

2 - 0.055

2 - 0.055

2 - 0.059

Row-Fin Gap (mm)

2-1.4

2-1.4

Coil length (L) x height (H) x coil width (W) (inch)

24.0 × 11.6 × 0.9

24.0 x 11.6 × 0.9

Coil length (L) x height (H) x coil width (W) (mm)

2-1.4
25.9 × 12.0 × 1.0

Φ 0.276

2-1.5
30.1 × 13.5 × 1.0

610 × 24 × 294

610 × 24 × 294

657 × 25.4 × 304.8

Output of Swing Motor (W)

1.5

1.5

2

765 × 25.4 × 342.9
3

Fuse (A)

3.15

3.15

3.15

3.15

Sound Pressure Level dB (A)(SH/H/M/L)

43 / 38 / 32 / 26

44 / 39 / 33 / 28

48 / 43 / 38 / 34

49 / 43 / 39 / 34

Sound Power Level dB (A)(SH/H/M/L)

53 / 48 / 42 / 36

54 / 49 / 43 / 38

58 / 53 / 48 / 43

59 / 53 / 49 / 44

Dimension (W/D/H) (inch)

30.3 × 7.9 × 11.1

30.3 × 7.9 × 11.1

34.1 × 8.5 × 12.0

39.7 × 8.7 × 12.4

Dimension (W/D/H) (mm)

770 × 201 × 282

770 × 201 × 282

865 × 216 × 305

1008 × 221 × 315

Dimension of Package (L/W/H) (inch)

33.3 × 10.9 × 13.9

33.3 × 10.9 × 13.9

37.3 × 12.2 × 15.1

42.2 × 12.3 × 15.6

Dimension of Package (L/W/H) (mm)

847 × 276 × 352

847 × 276 × 352

948 × 310 × 383

1073 × 313 × 395

Net Weight /Gross Weight (lbs)

19 / 25

20 / 27

27 / 35

33.0 / 44.0

Net Weight /Gross Weight (kg)

8.6 / 11.5

9.0 / 12

12.0 / 16

15 / 20

Continued on next page.

Johnson Controls Unitary Products

3

923178-UTG-B-0114
AIR CONDITIONERS (Continued)
Model of Outdoor Unit

DCMF09CSM42Q1

DCMF12CSM42Q1

DCMF18CSM42Q1

GREE

GREE

MITSUBISHI

SANYO

Inverter Rotary

Inverter Rotary

Inverter Rotary

Inverter Rotary

L.R.A. (A)

16.50

16.50

27

41

Compressor RLA (A)

6.22

6.22

10.86

11.38
1630

Compressor Manufacturer/trademark
Compressor Type

Compressor Power Input (W)
Throttling Method
Working Temp Range (oF)
Working Temp Range (°C)
Condenser

1245
Capillary

EXV

5 ~ 115

5 ~ 115

5 ~ 115

5 ~ 115

-15 ~ 46

-15 ~ 46

-15 ~ 46

-15 ~ 46

Aluminum Fin-copper Tube Aluminum Fin-copper Tube Aluminum Fin-copper Tube Aluminum Fin-copper Tube
Φ 0.276

Φ 0.276

Φ 0.276

φ7

φ7

φ7

φ7

Rows-Fin Gap (inch)

1 - 0.055

2 - 0.055

2 - 0.055

2 - 0.055

Φ 0.276

1-1.4

2-1.4

2-1.4

2-1.4

Coil length (L) x height (H) x coil width (L) (inch)

25.5 × 20.8 × 0.8

25.5 × 20.8 × 1.5

33.0 × 26.0 × 1.5

33.6 × 26.0 × 1.5

Coil length (L) x height (H) x coil width (L) (mm)

647 × 19.05 × 528

647 × 38.1 × 528

837 × 38.1 × 660

853 × 38.1 × 660

Fan Motor Speed (rpm)

880±20

880±20

690

690

Output of Fan Motor (W)

21

21

60

60

0.25

0.25

0.62

0.62

Fan Motor Capacitor (uF)
Fuse (A)
Outdoor Unit

950
Capillary

Pipe Diameter (mm)

Fan Motor RLA (A)

2

2

3

3.5

15A

15A

25A

25A

Air Flow Volume of Outdoor Unit (CFM)

944

944

1887

1887

Air Flow Volume of Outdoor Unit (m3/h)

1600

1600

3200

3200

Fan Type-Piece

Axial-flow-1

Axial-flow-1

Axial-flow-1

Axial-flow-1

Fan Diameter (inch)

14.6

14.6

20.5

20.5

Fan Diameter (mm)

370

370

520

520

Defrosting Method

Automatic Defrosting

Automatic Defrosting

Automatic Defrosting

Automatic Defrosting

Climate Type

T1

T1

T1

T1

Permissible Excessive Operating
Pressure for the Discharge Side (PSI)

624

624

624

624

Permissible Excessive Operating
Pressure for the Discharge Side (MPa)

4.3

4.3

4.3

4.3

Permissible Excessive Operating
Pressure for the Suction Side (PSI)

363

363

363

363

Permissible Excessive Operating
Pressure for the Suction Side (MPa)

2.5

2.5

2.5

2.5
56

Sound Pressure Level dB (A)

49

52

56

Sound Power Level dB (A)

59

62

66

66

Dimension (W/D/H) (mm)

28.0 × 12.5 × 21.7

28.0 × 12.5 × 21.7

37.9 × 15.6 × 27.6

37.9 × 15.6 × 27.6

Dimension (W/D/H) (mm)

Connection Pipe

950
Capillary

Pipe Diameter (inch)

Rows-Fin Gap (mm)

4

DCMF24CSM42Q1

711 × 318 × 551

711 × 318 × 551

963 × 396 × 701

963 × 396 × 701

Dimension of Package (L/W/H) (inch)

30.4 × 13.7 × 23.3

30.4 × 13.7 × 23.3

40.4 × 17.9 × 28.9

40.4 × 17.9 × 28.9

Dimension of Package (L/W/H) (mm)

771 × 348 × 592

771 × 348 × 592

1026 × 455 × 735

1026 × 455 × 735

Net Weight /Gross Weight (lbs)

64 / 73

68 / 77

104 / 115

112 / 123

Net Weight /Gross Weight (kg)

29 / 33

31 / 35

47 / 52

51 / 56

Refrigerant Charge (oz)

26.1

35.3

44.1

54.7

Refrigerant Charge (kg)

0.74

1.00

1.25

1.55

MCA

10.0

10.0

15.0

16.0

MOP

15.0

15.0

25.0

25.0

Length (ft)

25

25

25

25

Length (m)

7.5

7.5

7.5

7.5

Gas additional charge (oz/ft)

0.2

0.2

0.2

0.2

Gas additional charge (g/m)

15

15

15

15

Φ 1/4

Φ 1/4

Φ 1/4

Φ 1/4

Outer Diameter Liquid Pipe (inch)

φ6

φ6

φ6

φ6

Outer Diameter Gas Pipe (inch)

Φ 3/8

Φ 3/8

Φ 1/2

Φ 1/2

Outer Diameter Gas Pipe (mm)

φ9.52

φ9.52

φ12

φ12

32.8

32.8

32.8

32.8
9.9

Outer Diameter Liquid Pipe (mm)

Max Height Distance (ft)
Max Height Distance (m)

9.9

9.9

9.9

Max Length Distance (ft)

49.2

49.2

82

82

Max Length Distance (m)

14.9

14.9

24.9

24.9

Johnson Controls Unitary Products

923178-UTG-B-0114
HEAT PUMPS
Model (Indoor/Outdoor)
Function

DHMF09NWM42Q1

DHMF12NWM42Q1

DHMF18NWM42Q1

DHMF09CSM42Q1

DHMF12CSM42Q1

DHMF18CSM42Q1

Cooling

Rated Voltage

Heating

Cooling

208/230

Frequency (Hz)

60Hz

Heating

Cooling

Heating

DHMF24NWM42Q1
DHMF24CSM42Q1
Cooling

Heating

208/230

208/230

208/230

60Hz

60Hz

60Hz

Total Capacity (Btu/h) (High/Standard/Low)

11500/9000/
3800

11500/9000/
3300

12500/12000/
3300

12500/12000/ 21000/18000/ 23000/19200/ 24000/22000/ 26600/26600/
3400
4500
4000
6400
4100

Total Capacity (W) (High/Standard/Low)

3370/2637/
1114

3370/2637/
967

3663/3516/
967

3663/3516/
996

6155/5276/
1319

6741/5276/
1172

7032/6446/
1875

7796/6446/
1202

Rated Power Input (W)

882

799

1224

1065

1621

2123

2200

3118

Nominal Input Current (A)

4.01

3.63

5.56

4.84

7.37

9.65

10.00

14.17

16.00

8

16

9.5

SEER/HSPF
Air Flow Volume (CFM) (H/M/L)

16.00

8.5

16.00

8.5

330/300/260/210

330

340/300/260/210

341

470/400/330/270

590/440/300/200

580/520/440/370

580

Air Flow Volume (m3/h) (H/M/L)

560/510/440/370

800/680/560/460

1000/750/520/350

Dehumidifying Volume (cu.ft./h)

0.028

0.049

0.064

0.075

Dehumidifying Volume (l/h)

0.80

1.40

1.80

EER / C.O.P
Model of Indoor Unit
Fan Motor Speed (r/min) (SH/H/M/L)

3.32

DHMF09NWM42Q1
1300/1100/
900/700

1300/1150/
980/820

9.8

3.3

DHMF12NWM42Q1
1350/1150/
950/750

1350/1190/
1020/850

11.1

2.13
2.65

DHMF18NWM42Q1
1400/1150/
1000/850

1450/1250/
1100/950

10

2.5

DHMF24NWM42Q1
1400/1180/
1000/850

1450/1380/
1200/1150

Output of Fan Motor (w)

15

15

20

36

Fan Motor Capacitor (uF)

1.2

1.2

1.5

2.5

Fan Motor RLA(A)

0.19

0.19

0.32

0.45

Cross-flow - 1

Cross-flow - 1

Cross-flow - 1

Cross-flow - 1

Diameter-Length (inch)

3.6 × 23.4

3.6 × 23.4

3.9 × 25.6

3.9 × 30.1

Diameter-Length (mm)

92 × 594

92 × 595

98 × 650

98 × 765

Aluminum Fin-copper Tube

Aluminum Fin-copper Tube

Pipe Diameter (inch)

Φ 0.276

Φ 0.276

Φ 0.276

Pipe Diameter (mm)

φ7

φ7

φ7

φ7

Row-Fin Gap (inch)

2 - 0.055

2 - 0.055

2 - 0.055

2 - 0.059

Row-Fin Gap (mm)

Fan Type-Piece

Evaporator

Indoor Unit

10.2

Aluminum Fin-copper Tube Aluminum Fin-copper Tube
Φ 0.276

2-1.4

2-1.4

2-1.4

2-1.5

Coil length (L) x height
(H) x coil width (W) (inch)

24.0 × 11.6 × 0.9

24.0 × 11.6 × 0.9

25.9 × 12.0 × 1.0

30.1 × 13.5 × 1.0

Coil length (L) x height
(H) x coil width (W) (mm)

610 × 24 × 294

610 × 24 × 294

657 × 25.4 × 304.8

765 × 25.4 × 342.9

Output of Swing Motor (W)

1.5

1.5

2

3

Fuse (A)

3.15

3.15

3.15

3.15
49 / 43 / 39 / 34

Sound Pressure Level dB (A) (SH/H/M/L)

43 / 38 / 32 / 26

44 / 39 / 33 / 28

48 / 43 / 38 / 34

Sound Power Level dB (A)(SH/H/M/L)

53 / 48 / 42 / 36

54 / 49 / 43 / 38

58 / 53 / 48 / 43

59 / 53 / 49 / 44

30.3 × 7.9 × 11.1

30.3 × 7.9 × 11.1

34.1 × 8.5 × 12.0

39.7 × 8.7 × 12.4

Dimension (W/D/H) (inch)
Dimension (W/D/H) (mm)

770 × 201 × 283

770 × 201 × 283

865 × 215 × 305

1008 × 221× 315

Dimension of Package (L/W/H) (inch)

33.3 ×10.9 × 13.9

33.3 × 10.9 × 13.9

37.3 × 12.2 × 15.1

42.2 × 12.3 × 15.6

Dimension of Package (L/W/H) (mm)

847 × 276 × 352

847 × 276 × 352

948 × 310 × 383

1073 × 313 × 395

Net Weight /Gross Weight (lbs)

19 / 25

20 / 27

27 / 35

33.0 / 44.0

Net Weight /Gross Weight (kg)

8.6 / 11.5

9.0 / 12.0

12.0 / 16.0

15 / 20

Continued on next page.

Johnson Controls Unitary Products

5

923178-UTG-B-0114
HEAT PUMPS (Continued)
Model of Outdoor Unit

DHMF09CSM42Q1

DHMF12CSM42Q1

DHMF18CSM42Q1

GREE

GREE

MITSUBISHI

SANYO

Inverter Rotary

Inverter Rotary

Inverter Rotary

Inverter Rotary

L.R.A. (A)

16.50

16.50

27

41

Compressor RLA(A)

6.22

6.22

10.86

11.38
1630

Compressor Manufacturer/trademark
Compressor Type

Compressor Power Input (W)
Throttling Method

EXV

14 ~ 75

5 ~ 115

14 ~ 75

5 ~ 115

14 ~ 75

5 ~ 115

14 ~ 75

Working Temp Range (°C)

-15 ~ 46

-10 ~ 24

-15 ~ 46

-10 ~ 24

-15 ~ 46

-10 ~ 24

-15 ~ 46

-10 ~ 24

Aluminum Fin-copper Tube

Aluminum Fin-copper Tube

Pipe Diameter (inch)

Φ 0.276

Φ 0.276

Φ 0.276

Pipe Diameter (mm)

φ7

φ7

φ7

φ7

Rows-Fin Gap (inch)

1 - 0.055

2 - 0.055

2 - 0.055

2 - 0.055

Aluminum Fin-copper Tube Aluminum Fin-copper Tube
Φ 0.276

1-1.4

2-1.4

2-1.4

2-1.4

Coil length (l) x height (H) x
coil width (L) (inch)

25.5 × 20.8 × 0.8

25.5 × 20.8 × 1.5

33.0 × 26.0 × 1.5

33.6 × 26.0 × 1.5

Coil length (l) x height (H) x
coil width (L) (mm)

647 × 19.05 × 528

647 × 38.1 × 528

837 × 38.1 × 660

853 × 38.1 × 660

Fan Motor Speed (rpm)

880±20

880±20

690

690

Output of Fan Motor (W)

21

21

60

60

0.25

0.25

0.62

0.62

Fan Motor RLA(A)
Fan Motor Capacitor (uF)
Outdoor Unit

1245
Capillary

5 ~ 115

Rows-Fin Gap (mm)

Connection Pipe

950
Capillary

Working Temp Range (oF)
Condenser

6

950
Capillary

DHMF24CSM42Q1

Fuse (A)

2

2

3

3.5

15A

15A

25A

25A

Air Flow Volume of Outdoor Unit (CFM)

944

944

1887

1887

Air Flow Volume of Outdoor Unit (m3/h)

1600

1600

3200

3200

Fan Type-Piece

Axial-flow-1

Axial-flow-1

Axial-flow-1

Axial-flow-1

Fan Diameter (inch)

14.6

14.6

20.5

20.5

Fan Diameter (mm)

370

370

520

520

Defrosting Method

Automatic Defrosting

Automatic Defrosting

Automatic Defrosting

Automatic Defrosting

Climate Type

T1

T1

T1

T1

Permissible Excessive Operating
Pressure for the Discharge Side (PSI)

624

624

624

624

Permissible Excessive Operating
Pressure for the Discharge Side (MPa)

4.3

4.3

4.3

4.3

Permissible Excessive Operating
Pressure for the Suction Side (PSI)

363

363

363

363

Permissible Excessive Operating
Pressure for the Suction Side (MPa)

2.5

2.5

2.5

2.5

Sound Pressure Level dB (A)

49

52

56

56

Sound Power Level dB (A)

59

62

66

56

Dimension (W/D/H) (mm)

28.0 × 12.5 × 21.7

28.0 × 12.5 × 21.7

37.9 × 15.6 × 27.6

37.9 × 15.6 × 27.6

Dimension (W/D/H) (mm)

711 × 318 × 551

711 × 318 × 551

963 × 396 × 701

963 × 396 × 701

Dimension of Package (L/W/H) (inch)

30.4 × 13.7 × 23.3

30.4 × 13.7 × 23.3

40.4 × 17.9 × 28.9

40.4 × 17.9 × 28.9

Dimension of Package (L/W/H) (mm)

771 × 348 × 592

771 × 348 × 592

1026 × 455 × 735

1026 × 455 × 735

Net Weight /Gross Weight (lbs)

64 / 73

68 / 77

106 / 117

115 / 126

Net Weight /Gross Weight (kg)

29 / 33

31 / 35

48 / 53

52 / 57

Refrigerant Charge (oz)

26.1

35.3

44.1

54.7

Refrigerant Charge (kg)

0.74

1.00

1.25

1.55

MCA

10.0

10.0

15.0

16.0

MOP

25.0

15.0

15.0

25.0

Length (ft)

25

25

25

25

Length (m)

7.5

7.5

7.5

7.5

Gas additional charge (oz/ft)

0.2

0.2

0.2

0.2

Gas additional charge (g/m)

20

20

20

20

Φ 1/4

Φ 1/4

Φ 1/4

Φ 1/4

Outer Diameter Liquid Pipe (inch)

φ6

φ6

φ6

φ6

Outer Diameter Gas Pipe (inch)

Φ 3/8

Φ 3/8

Φ 1/2

Φ 1/2

Outer Diameter Gas Pipe (mm)

φ9.52

φ9.52

φ12

φ12

32.8

32.8

32.8

32.8
9.9

Outer Diameter Liquid Pipe (mm)

Max Height Distance (ft)
Max Height Distance (m)

9.9

9.9

9.9

Max Length Distance (ft)

49.2

49.2

82

82

Max Length Distance (m)

14.9

14.9

24.9

24.9

Johnson Controls Unitary Products

923178-UTG-B-0114

PRODUCT OPERATION CHARACTERISTIC CURVES
09K 12K
Cooling

Heating

10

8

9

7

8
6
7
5

Current(A)

Current(A)

6
5
4
Condition
Indoor:DB 80.6°F WB66.2°F
Indoor air flow: Super High
Pipe length:24.6ft

3
2

4

3
Condition
Indoor:DB 68°F
Indoor air flow: Super High
Pipe length:24.6ft

2

1

1

0

0
0

20

40

60

80

100

0

120

20

40

Compressor Frequency(Hz)

60

80

100

120

Compressor Frequency(Hz)

18K
Cooling
10
9

Heating

8
12
7
10

Current(A)

Current(A)

6
5
4
Condition
Indoor:DB 80.6°F WB66.2°F
Indoor air flow: Super High
Pipe length:24.6ft

3
2

8

6
Condition
Indoor:DB 68°F
Indoor air flow: Super High
Pipe length:24.6ft

4

2
1
0

0
0

20

40
60
80
Compressor Frequency(Hz)

Johnson Controls Unitary Products

100

120

0

20

40

60

80

100

120

Compressor Frequency(Hz)

7

923178-UTG-B-0114

24K
Cooling

Heating

14

14

12

12

10

10

8

8

6

6

4
2

2
0

0
0

20

40

Condition
Indoor:DB 68°F
Indoor air flow: Super High
Pipe length:24.6ft

4

Condition
Indoor:DB 80.6°F WB66.2°F
Indoor air flow: Super High
Pipe length:24.6ft

0

60

20

40

60

80

100

120

Compressor Frequency(Hz)

Compressor Frequency(Hz)

PRODUCT CAPACITY VARIATION RATIO
09K 12K
Heating

110

120

100

100

90

80

Capacity ratio(%)

Capacity ratio(%)

Cooling

80

70
Condition
Indoor:DB 80.6°F WB66.2°F
Indoor air flow: Super High
Pipe length:24.6ft

60

60

40
Condition
Indoor:DB 68°F
Indoor air flow: Super High
Pipe length:24.6ft

20

0

50

90

95

100

105

110

115

5

10

15

Outdoor temp. (°F)

20

25

30

35

40

45

50

Outdoor temp. (°F)

18K 24K




110

105
100

100

90
85
80
75
70

Conditions
Indoor: DB 80.6°F WB66.2°F
Indoor air flow : High
Pipe length : 24.6ft

65
60
55

95

100

Outdoor temp. (˚F)

8

90
80
70
60

Condition
Indoor:DB 68°F
Indoor air flow: Super High
Pipe length:24.6ft

50
40

50

90

Capacity ratio (%)

Capacity ratio (%)

95

105

110

5

10

15

20

25

30

35

40

45

50

Outdoor temp. (˚F)

Johnson Controls Unitary Products

923178-UTG-B-0114

OPERATION DATA
Temperature Condition (°F)

Model name

Standard
Pressure
P (MPa)

Heat Exchanger
Pipe Temperature
T1 (°F)
T2 (°F)

Indoor Fan
Mode

Outdoor Fan Compressor
Mode
Frequency (Hz)

Indoor

Outdoor

80/66.9
80/66.9
80/66.9
80/66.9

95/75
95/75
95/75
95/75

09K
12K
18K
24K

0.9 to 1.1
0.9 to 1.1
0.9 to 1.1
0.9 to 1.1

COOLING
53.6 to 57.2
53.6 to 57.2
53.6 to 57.2
53.6 to 57.2

158 to 104
158 to 104
176 to 104
176 to 104

Super High
Super High
Super High
Super High

High
High
High
High

73
71
75
89

70/60
70/60
70/60
70/60

46.9/43
46.9/43
46.9/43
46.9/43

09K
12K
18K
24K

2.5 to 2.7
2.5 to 2.7
2.2 to 2.4
2.2 to 2.4

HEATING
158 to 95
158 to 95
158 to 104
158 to 104

35.6 to 39.2
35.6 to 39.2
33.8 to 41.0
33.8 to 41.0

Super High
Super High
Super High
Super High

High
High
High
High

76
76
90
87

Notes:
Measure surface temperature of heat exchanger pipe around center of heat exchanger path U bent. (Thermistor thermometer).
Connecting piping condition: 24.6 ft.
P: pressure of air pipe connected to the indoor and outdoor units (gas valve side),
T1: Inlet and outlet temperature for evaporator,
T2: Inlet and outlet temperature for condenser.

SOUND DATA

09K 12K
Indoor side noise when blowing

Outdoor side noise

60

60

40

Noice/dB(A)

Noice/dB(A)

50

30
20

50
40
30

10
20

0
low

High

Middle

0

Super High

Indoor Fan Motor Rotating Speed
09K

20

40

60

80

100

Compressor frequency/Hz

12K

09K

12K

18K 24K

Indoor side noise when blowing

Outdoor side noise

60

60
50

40

Noice/dB(A)

Noice/dB(A)

50

30
20
10
0
low

Middle

High

Super High

Indoor Fan Motor Rotating Speed

18K

Johnson Controls Unitary Products

24K

40
30
20
0

20

40

60

80

100

Compressor frequency/Hz

18 24K

9

923178-UTG-B-0114

PRODUCT CONSTUCTION VIEW & DIMENSIONS
A

09K 12K

B

5.0

21.6

3.7

C

18K

5.5

21.3

7.2

24K

5.1

7.6

27.0

Indoor Unit Dimensions
Model Size

Unit Gross Weight

A

B

C

30.3 (770)

7.9 (201)

11.1 (282)

18K

34.1 (866)

8.5 (216)

24K

39.7 (1008)

8.7 (221)

09K
12K

Air Conditioner

Heat Pump

25 lbs (11.5 kg)

25 lbs (11.5 kg)

27 lbs (12 kg)

27 lbs (12 kg)

12.0 (305)

35 lbs (16 kg)

35 lbs (16 kg)

12.4 (315)

44 lbs (20 kg)

44 lbs (20 kg)

E

F

C

D

G

B

A

Outdoor Unit Dimensions
Model Size
09K
12K
18K
24K

10

A

B

28.0 (711 ) 12.5 (318)
37.9 (963) 15.6 (396 )

C

D

E

F

G

21.7 (551)

11.8 (300)

10.8 (274)

25.9 (658)

18.5 (470)

27.6 (701)

14.4 (366)

13.4 (340)

35.0 (889)

22.0 (559)

Unit Gross Weight
Air Conditioner

Heat Pump

73 lbs (33 kg)

73 lbs (33 kg)

77 lbs (35 kg)

77 lbs (35 kg)

115 lbs (52 kg)

117 lbs (53 kg)

123 lbs (56 kg)

126 lbs (57 kg)

Johnson Controls Unitary Products

923178-UTG-B-0114

REFRIGERANT SYSTEM DIAGRAM
09K/12K/18K Cooling Only Models

INDOOR UNIT

OUTDOOR UNIT

GAS SIDE
3-WAY VALVE

Muffler

Discharge

HEAT
EXCHANGE
(EVAPORATOR)

Accumlator

Suction

COMPRESSOR
HEAT
EXCHANGE
(CONDENSER)

LIQUID SIDE
2-WAY VALVE

Capillary

Strainer

COOLING
See Page 12 for notes.

09K/12K/18K Heat Pumps

INDOOR UNIT

OUTDOOR UNIT

GAS SIDE
3-WAY VALVE

4-Way valve
Muffler
Discharge

HEAT
EXCHANGE
(EVAPORATOR)

Suction

Accumlator

COMPRESSOR
HEAT
EXCHANGE
(CONDENSER)

LIQUID SIDE
2-WAY VALVE

Strainer

Capillary

Strainer

COOLING
HEATING
See Page 12 for notes.

Johnson Controls Unitary Products

11

923178-UTG-B-0114
24K Cooling Only Models

INDOOR UNIT

OUTDOOR UNIT

GAS SIDE
3-WAY VALVE

Muffler

Discharge

HEAT
EXCHANGE
(EVAPORATOR)

Accumlator

Suction

COMPRESSOR
HEAT
EXCHANGE
(CONDENSER)

LIQUID SIDE
Electron expansion valve

2-WAY VALVE

Strainer

COOLING
See below for notes.

24K Heat Pumps

INDOOR UNIT

OUTDOOR UNIT

GAS SIDE
3-WAY VALVE

4-Way valve
Muffler
Discharge

HEAT
EXCHANGE
(EVAPORATOR)

Suction

Accumlator

COMPRESSOR

LIQUID SIDE
2-WAY VALVE

HEAT
EXCHANGE
(CONDENSER)

Strainer Electron expansion valve Strainer

COOLING
HEATING
NOTES:
Refrigerant pipe diameter
Liquid: 1/4” (0.24 inch)
Gas: 3/8” (0.37 inch)(09K 12K)
Gas: 1/2” (0.47 inch)(18K 24K)

12

Johnson Controls Unitary Products

923178-UTG-B-0114

WIRING DIAGRAM
Electrical Data
Symbol

Color Symbol

Symbol

Color Symbol

Symbol

Part Name

BU

BlUE

BN

BROWN

YE

YELLOW

GN

GREEN

/

/

RD

RED

BK

BLACK

/

/

YEGN

YELLOW GREEN

/

/

/

/

Symbol

Part Name

Symbol

Color Symbol

Symbol

Color Symbol

C1

CBB61

BN

BROWN

WH

WHITE

C2

CBB65

BU

BLUE

YE

YELLOW

INDOOR UNIT
PROTECTIVE EARTH

OUTDOOR UNIT

SAT

OVERLOAD

BK

BLACK

RD

RED

COMP

COMPRESSOR

OG

ORANGE

YEGN

YELLOW GREEN

PROTECTIVE EARTH

WH

WHITE

/

/

Electrical Wiring

09K & 12K Outdoor Air Conditioners

Johnson Controls Unitary Products

13

923178-UTG-B-0114

09K & 12K Indoor Air Conditioners

18K & 24K Outdoor Air Conditioners

14

Johnson Controls Unitary Products

923178-UTG-B-0114

18K & 24K Indoor Air Conditioners

09K & 12K Outdoor Heat Pumps

Johnson Controls Unitary Products

15

923178-UTG-B-0114

09K & 12K Indoor Heat Pumps

18K & 24K Outdoor Heat Pumps

16

Johnson Controls Unitary Products

923178-UTG-B-0114

18K

24K

18K & 24K Indoor Heat Pumps

DESCRIPTION OF EACH CONTROL
OPERATION
Temperature & Current Parameters
•
•
•
•
•
•
•

Indoor preset temperature (Tpreset)
Indoor ambient temperature (Tamb.)
Evaporator coil temperature (Tevap)
Condenser coil temperature (Toutdoor pipe)
Defrost compensation temperature (Tcompensation)
Outdoor ambient temperature (Toutdoor amb)
Measured temperature of outdoor condensing coil under
cooling mode and measured temperature of indoor evaporator coil under heating mode (Ttube).
• Indoor ambient temperature (Tindoor amb)

Basic Functions
Once energized, the compressor should never be restarted
within less than 3 minutes. In a situation where memory function is available when energized for the first time, if the compressor is at stop before de-energized, it will re-start without a
3-minute lag. If it has been in operation before de- energized,
the compressor will start with a 3-minute lag. Once started, the
compressor will not be stopped within 6 minutes regardless of
changes in room temperature.
Cooling Mode
1. Cooling Mode Operation
• When Tamb Tpreset, cooling mode is activated. The indoor
fan, outdoor fan and the compressor will operate simultaneously. The indoor fan will run at preset speed.
• When Tamb Tpreset - 3.6,°F the compressor will stop, the
outdoor fan will stop with a time lag of 60 seconds, and the
indoor fan will run at preset speed.
• When Tpreset - 3.6°F < Tamb. < Tpreset + 1.8°F, the unit will
remain at its previous state.
In cooling mode, the four-way valve will be de-energized and
temperature can be set within a range from 61 to 86°F. If the
compressor stops running, the indoor fan and the swing device
will operate at original state.

Johnson Controls Unitary Products

Tamb.

Start cooling

Tpreset
Original working state
Tpreset +3.6 ºF

Stop cooling
6 minutes

3 minutes

6 minutes

Compressor
Outdoor fan
Indoor fan

Preset fan speed
Run

Stop

2. Protection – Cooling Mode
• Antifreeze protection - In cooling and dehumidification
mode, antifreeze protection is activated 6 minutes after the
compressor has started if one of followings occur:
 T evap 35.6 °F, the compressor will operate at reduced
frequency.
 T evap 30.2 °F is detected for a duration of 3 minutes,
the compressor will stop and after 60 seconds, the outdoor fan will stop. In cooling mode, the indoor fan and the
swing motor will remain at the original state.
 T evap.  42.8 °F and the compressor has remained in
OFF mode for at least 3 minutes, the compressor will
resume its original operation state.
• Total current up and frequency down protection if the followings occur:
 Itotal  16A, the compressor frequency will start to
increase
 Itotal 17A, the compressor frequency will not increase
 Itotal 18A, the compressor will run at reduced frequency
 Itotal 20A, the compressor will immediately stop and the
outdoor fan will stop after 60 seconds

17

923178-UTG-B-0114
Dehumidification Mode
1. Dehumidification Mode Operation
• When Tamb > Tpreset + 1.8 °F, cooling and dehumidification
mode will be activated. The compressor and the outdoor
fan will operate while the indoor fan runs at low speed.
• When Tpreset - 3.6 °F Tamb Tpreset + 1.8°F, the compressor remains at its original operation state.
• When Tamb. < Tpreset - 3.6°F, the compressor will stop, the
outdoor fan will stop after 60 seconds and the indoor fan
will operate at low speed.
2. Protection – Dehumidification Mode
Protection is the same as that under cooling mode section.
Heating Mode
1. Heating Mode Operation
• When Tamb.  Tpreset + 3.6°F, heating mode is activated.
The four-way valve, the compressor and the outdoor fan
will operate simultaneously. The indoor fan will run at preset speed defined under “cold air prevention”.
• When Tamb.  Tpreset + 9°F, the compressor will stop, the
outdoor fan will stop after 60 seconds, and the indoor fan
will continue to run at low speed for 60 seconds more.
• When Tpreset + 3.6°F35.6°F, Tcompensation = 0°F;
Toutdoor pipe ≤35.6°F, Tcompensation = 5.4°F

When in defrost mode the following will occur in the order
described:
a. The indoor fan and compressor stop running
b. The outdoor fan will stop running after 60 seconds.
c. 30seconds later, the four-way valve will close.
d. After 30 seconds, the compressor’s frequency is
increased to defrost frequency.
e. When the compressor has operated in defrost mode for
10 minutes, or Toutdoor pipe ≥ 50°F, the compressor will
adjust to 46Hz.
f. After 30 seconds, the compressor will stop.
g. After another 30 seconds, the four-way valve will open.

18

h. After 60 seconds, the compressor and the outdoor unit fan
will start running. The indoor fan will run under preset cold
air prevention conditions. H1 will be displayed on the
indoor unit display. Defrost frequency is 70Hz.
3. Protection – Heating Mode
• Cold air prevention (Hot Heat Pump) - In heating mode,
after the compressor is energized the indoor fan is delayed
under these conditions to prevent discharging cold air:
 When Tindoor amb.<75°F if:
 Ttube≤104°F, the indoor fan will not run. The indoor fan
will start running at low speed after 2 minutes.
 Within 2 minutes, if Ttube>104°F, the indoor fan will start
running at low speed.
 After 1minute of operation at low speed, the indoor fan
will run at preset speed.
 Within 1-minute of low speed operation or 2-minute
non-operation, if Ttube>108°F, the fan will run at present
speed.
 When Tindoor amb.≥75°F if:
 Ttube≤108°F, the indoor fan will run at low speed. After
one minute of operation, the indoor fan will run at preset speed.
 Within one-minute of low speed operation, if
Ttube>104°F, the indoor fan will run at preset speed.
 Total current up and frequency down protection occurs:
 When Itotal≤16A, compressor frequency can increase
 When Itotal≥17A, compressor frequency is not allowed
to increase
 When Itotal≥18A, the compressor runs at reduced frequency
 When Itotal≥20A, the compressor stops running and the
outdoor fan stops running after 60 seconds.

Fan Mode
In this mode, the indoor fan will run at preset speed. The compressor, the outdoor fan and the four-way valve will not be running.
1. In fan mode, temperature can be set within a range of 61 86°F.

AUTO Mode
1. AUTO Mode Operation
In AUTO mode, the default cooling setpoint temperature Tpreset
is 77°F and the default heating setpoint temperature Tpreset is
68°F. Once activated, the following will occur under these conditions:
• When Tamb.≤71.6°F, heating mode is activated.
• When 71.6°F< Tamb.<78.8°F, fan mode is activated and the
fan icon is displayed on the indoor unit display.
• When Tamb.≥78.8°F, cooling mode is activated.
• When Tamb.≥Tpreset +1.8°F, the system runs in cooling
mode. The preset temperature is 77°F;
• When Tamb. ≤Tpreset-1.8°F, the compressor stops running,
the outdoor fan stops running after 1 minute, and the indoor
fan continues to run at a preset speed.
• When Tpreset -1.8°F< Tamb.< Tpreset+1.8°F, the system continues to run normally.
• When Tamb.≤Tpreset+3.6°F, heating mode is activated.
• Tamb.≥Tpreset +9°F, the compressor stops running, the outdoor fan stops running after 1 minute, and the indoor fan
continues to run for about 30 seconds before it stops.

Johnson Controls Unitary Products

923178-UTG-B-0114
• When Tpreset +3.6°F< Tamb.< Tpreset+41°F, the system continues to run normally
• When 71.6°F
Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.7
Linearized                      : No
Author                          : ckobyk
Create Date                     : 2014:01:10 15:00:21-06:00
Modify Date                     : 2014:01:20 08:07:00-06:00
XMP Toolkit                     : Adobe XMP Core 5.2-c001 63.139439, 2010/09/27-13:37:26
Producer                        : Acrobat Distiller 10.0.0 (Windows)
Creator Tool                    : PScript5.dll Version 5.2.2
Metadata Date                   : 2014:01:20 08:07-06:00
Format                          : application/pdf
Title                           : 923178-UTG-B-0114.fm
Creator                         : ckobyk
Document ID                     : uuid:339f37be-3f1f-4d54-b1f5-759729433b4a
Instance ID                     : uuid:a50b4dcc-e3b4-4ed2-84fc-c54593e21c29
Page Layout                     : OneColumn
Page Mode                       : UseThumbs
Page Count                      : 34
EXIF Metadata provided by EXIF.tools

Navigation menu