DESCRIPTION
YORK Sunline Magnum™ units are convertible single package air conditioners with a common cabinet and a common
roof curb for the 3, 4 and 5 ton sizes. The units were
designed for light commercial and commercial applications.
They can easily be installed on a roof curb, slab, roof jack or
frame.

TECHNICAL GUIDE

SINGLE PACKAGE GAS/ELECTRIC UNITS

All units include:

AND SINGLE PACKAGE

•

Powder Paint finish that meets ASTM-B-117 750 hour salt
spray standards

•

Permanently lubricated motors

•

Bottom or side air discharge configuration capability
(field convertible)

•

Manufactured under the quality standards of ISO9001

•

Simplicity® Control Board

•

Copper tube/aluminum fin coils

•

Easy access to all components

•

Rigging holes in base rails for lifting

•

Fork lift slots on three sides

•

Single point power connection

•

Complete factory package - tested, charged and wired

•

CSA agency listing on all units

AIR CONDITIONERS
DY 036, 048 & 060
3, 4 & 5 NOMINAL TONS
14.00 SEER

WARRANTY
•

Factory Limited Parts Warranty

•

One-year parts warranty

•

A Five-year parts warranty on the compressor and
electric heat elements.

•

Ten-year parts warranty on the gas-fired heat
exchangers.

FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

343615-YTG-B-0308

TABLE OF CONTENTS
DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

Tbl. #

PRODUCT NOMENCLATURE . . . . . . . . . . . . . . . . . 3

8

FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
FACTORY-INSTALLED OPTIONS . . . . . . . . . . . . . . 6
FIELD-INSTALLED ACCESSORIES. . . . . . . . . . . . . 7

9
10

GUIDE SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . 32
11

LIST OF FIGURES
Fig. #

Pg. #

12

1

UNIT CUTAWAY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

2

TYPICAL FIELD POWER & CONTROL WIRING . . . . . 25

3

UNIT DIMENSIONS (3 - 5 TON COOLING ONLY/
ELECTRIC HEAT) FRONT VIEW . . . . . . . . . . . . . . . . . 26

14

4

UNIT DIMENSIONS (3 - 5 TON COOLING/GAS
HEAT) FRONT VIEW . . . . . . . . . . . . . . . . . . . . . . . . . . 26

15

5

UNIT WITH ECONOMIZER RAINHOOD . . . . . . . . . . . 27

6

UNIT WITH FIXED OUTDOOR AIR/MOTORIZED
DAMPER RAINHOOD. . . . . . . . . . . . . . . . . . . . . . . . . . 27

7

UNIT DIMENSIONS (REAR VIEW). . . . . . . . . . . . . . . . 28

16
17
18
19

8

DISCONNECT/BLOWER ACCESS LOCATION. . . . . . 28

9

TYPICAL APPLICATIONS . . . . . . . . . . . . . . . . . . . . . . 29

10 FOUR AND SIX POINT LOADING . . . . . . . . . . . . . . . . 30

13

20

11 ROOF CURB DIMENSIONS . . . . . . . . . . . . . . . . . . . . . 31

LIST OF TABLES
Tbl. #
1
2
3
4
5
6
7

2

Pg. #

CAPACITY RATINGS - (ARI 210/240) . . . . . . . . . . . . . . 8
GAS HEAT RATINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2 STAGE GAS HEAT RATINGS . . . . . . . . . . . . . . . . . . . 8
DY036 INDOOR SOUND POWER LEVELS
(HORIZONTAL DUCTED INLET) . . . . . . . . . . . . . . . . . . 9
DY036 INDOOR SOUND POWER LEVELS
(HORIZONTAL DUCTED DISCHARGE) . . . . . . . . . . . . 9
DY036 INDOOR SOUND POWER LEVELS
(VERTICAL DUCTED INLET) . . . . . . . . . . . . . . . . . . . . 10
DY036 INDOOR SOUND POWER LEVELS
(VERTICAL DUCTED DISCHARGE) . . . . . . . . . . . . . . 10

21
22
23
24
25
26
27
28
29
30
31
32

Pg. #

DY048 INDOOR SOUND POWER LEVELS
(HORIZONTAL DUCTED INLET) . . . . . . . . . . . . . . . . . 11
DY048 INDOOR SOUND POWER LEVELS
(HORIZONTAL DUCTED DISCHARGE) . . . . . . . . . . . 11
DY048 INDOOR SOUND POWER LEVELS
(VERTICAL DUCTED INLET). . . . . . . . . . . . . . . . . . . . 12
DY048 INDOOR SOUND POWER LEVELS
(VERTICAL DUCTED DISCHARGE) . . . . . . . . . . . . . . 12
DY060 INDOOR SOUND POWER LEVELS
(HORIZONTAL DUCTED INLET) . . . . . . . . . . . . . . . . . 13
DY060 INDOOR SOUND POWER LEVELS
(HORIZONTAL DUCTED DISCHARGE) . . . . . . . . . . . 13
DY060 INDOOR SOUND POWER LEVELS
(VERTICAL DUCTED INLET). . . . . . . . . . . . . . . . . . . . 14
DY060 INDOOR SOUND POWER LEVELS
(VERTICAL DUCTED DISCHARGE) . . . . . . . . . . . . . . 14
DY036 COOLING CAPACITIES (3 TON) . . . . . . . . . . . 15
DY048 COOLING CAPACITIES (4 TON) . . . . . . . . . . . 16
DY060 COOLING CAPACITIES (5 TON) . . . . . . . . . . . 17
SUPPLY AIR BLOWER PERFORMANCE
(DY036, 048, & 060 DIRECT DRIVE)
SIDE DUCT APPLICATION . . . . . . . . . . . . . . . . . . . . . 18
SUPPLY AIR BLOWER PERFORMANCE
(DY036, 048, & 060 DIRECT DRIVE)
BOTTOM DUCT APPLICATION. . . . . . . . . . . . . . . . . . 18
STATIC RESISTANCES. . . . . . . . . . . . . . . . . . . . . . . . 19
ELECTRIC HEAT CFM LIMITATIONS . . . . . . . . . . . . . 19
ELECTRICAL DATA - DY036, 048 & 060 DIRECT
DRIVE W/O POWERED CONVENIENCE OUTLET. . . 20
ELECTRICAL DATA - DY036, 048 & 060 DIRECT
DRIVE W/ POWERED CONVENIENCE OUTLET . . . . 22
DY PHYSICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . 24
ELECTRIC HEAT CORRECTION FACTORS . . . . . . . 24
VOLTAGE LIMITATIONS . . . . . . . . . . . . . . . . . . . . . . . 24
UTILITIES ENTRY . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
MINIMUM CLEARANCES . . . . . . . . . . . . . . . . . . . . . . 28
DY 4 AND 6 POINT LOADS WEIGHT
DISTRIBUTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
CENTER OF GRAVITY . . . . . . . . . . . . . . . . . . . . . . . . 30
OPERATING WEIGHTS (LBS.) . . . . . . . . . . . . . . . . . . 31

Johnson Controls Unitary Products

343615-YTG-B-0308

PRODUCT NOMENCLATURE

3-5 Ton Sunline Magnum™ Model Number Nomenclature
D Y 048 N04 A 2 A AA 2 0 1 2 4 A
Product Category

Product Style

D = A/C, Single Pkg., R-22

A = Style A

Product Identifier

Configuration Options (not required for all units)
These four digits will not be assigned until a quote is requested, or an order placed.

Y = 14.0 SEER

SS Drain Pan
CPC Controller, DFS, APS
Johnson Controller, DFS, APS

Nominal Cooling Capacity

Honeywell Controller, DFS, APS
036 = 3.0 Ton
048 = 4.0 Ton
060 = 5.0 Ton

Novar Controller, DFS, APS
Simplicity IntelliComfort Controller
Simplicity IntelliComfort Controller w/ModLinc
2" Pleated filters

Heat Type and Nominal Heat Capacity

BAS Ready Economizer (2-10 V.D.C. Actuator without a Controller)
Any Combination of Additional Options that Don’t Have an Option Code Pre-assigned

C00 = Cooling Only. Suitable for Field
Installed Electric Heat

Product Generation
Gas Heat Options
2 = Second Generation
N04 = 40 MBH Output Aluminized Steel, 1 Stage (036)
N06 = 60 MBH Output Aluminized Steel, 1 Stage (048)
N08 = 80 MBH Output Aluminized Steel, 1 Stage
(036, 060)
N10 = 100 MBH Output Aluminized Steel, 1 Stage
(048, 060)
D06 = 60 MBH Output Aluminized Steel, 2 Stage
(036, 048, 060)
D10 = 100 MBH Output Aluminized Steel, 2 Stage
(036*, 048, 060)
S04 = 40 MBH Output Stainless Steel, 1 Stage (036)
S06 = 60 MBH Output Stainless Steel, 1 Stage (048)
S08 = 80 MBH Output Stainless Steel, 1 Stage
(036, 060)
S10 = 100 MBH Output Stainless Steel, 1 Stage
(048, 060)
T06 = 60 MBH Output Stainless Steel, 2 Stage
(036, 048, 060)
T10 = 100 MBH Output Stainless Steel, 2 Stage
(036*, 048, 060)

Additional Options
Standard Cabinet

Hinged Filter Door & Toolless Access Cabinet

AA = None
AB = Phase Monitor
AC = Coil Guard
AD = Dirty Filter Switch
AE = Phase Monitor & Coil Guard
AF = Phase Monitor & Dirty Filter Switch
AG = Coil Guard & Dirty Filter Switch
AH = Phase Monitor, Coil Guard & Dirty Filter Switch
AS = Bottom Drain Connection
RC = Coil Guard & American Flag
TA = Technicoat Condenser Coil
TJ = Technicoat Evaporator Coil
TS = Technicoat Evaporator and Condenser Coil

BA = Hinged Filter Door & Toolless Access Panels
BB = Phase Monitor, Hinged Filter Door & Toolless
Access Panels
BC = Coil Guard, Hinged Filter Door & Toolless
Access Panels
BD = Dirty Filter Switch, Hinged Filter Door &
Toolless Access Panels
BE = Phase Monitor & Coil Guard, Hinged Filter
Door & Toolless Access Panels
BF = Phase Monitor & Dirty Filter Switch, Hinged
Filter Door & Toolless Access Panels
BG = Coil Guard & Dirty Filter Switch, Hinged Filter
Door & Toolless Access Panels
BH = Phase Monitor, Coil Guard & Dirty Filter Switch,
Hinged Filter Door & Toolless Access Panels

Electric Heat Options
ZZ = If desired option combination is not listed above, ZZ will be assigned and configuration options will be
located in digits 15-18.

E05 = 5 KW
E07 = 7 KW
E10 = 10 KW
E15 = 15 KW
E20 = 20 KW
E30 = 30 KW

Installation Options

*(D, T)10 = 92 MBH Output on 036 Models
Airflow
A = Direct Drive
B = Direct Drive/Single Input Economizer
D = Direct Drive/Motorized Damper

Voltage
1 = 208/230-1-60
2 = 208/230-3-60
4 = 460-3-60
5 = 575-3-60

A = No Options Installed
B = Option 1
C = Option 2
D = Options 1 & 2
E = Option 3
F = Option 4
G = Options 1 & 3
H = Options 1 & 4
J = Options 1, 2 & 3
K = Options 1, 2, & 4
L = Options 1,3 & 4
M = Options 1, 2, 3, & 4
N = Options 2 & 3
P = Options 2 & 4
Q = Options 2, 3, & 4
R = Options 3 & 4
S = Option 5
T = Options 1 & 5
U = Options 1, 3, & 5
V = Options 1, 4, & 5
W = Options 1, 3, 4, & 5
X = Options 3 & 5
Y = Options 4 & 5
Z = Options 3, 4 & 5
Options
1 = Disconnect
2 = Non-Pwr'd Conv. Outlet
3 = Smoke Detector S.A.
4 = Smoke Detector R.A.
5 = Pwr'd Conv. Outlet

Johnson Controls Unitary Products

3

343615-YTG-B-0308

FEATURES

gas valve, if applicable, and the temperature limit
switch on gas heat units. The unit control board will
alarm on ignition failures, compressor lockouts and
repeated limit switch trips.

All models are available with a wide variety of factorymounted options such as stainless steel heat exchangers,
electric heaters, phase monitor, convenience outlet, dirty filter
switch, disconnect switch, smoke detectors, and coil guard to
make them suitable for almost every application.
All units are self-contained and assembled on full perimeter
base rails with forklift holes on three sides and holes for overhead rigging. Every unit is completely piped, wired, charged
and tested at the factory to simplify the field installation and to
provide years of dependable operation.
All models (including those with an economizer) are suitable
for either bottom or horizontal duct connections. For bottom
duct, remove the sheet metal panels from the supply and
return air openings through the base of the unit. For horizontal duct, remove the supply and return air panels on the rear
of the unit.

•

Nuisance Trip Protection- To prevent nuisance
trouble calls, the control board uses a “three strikes,
you’re out” philosophy. The high and low-pressure
switches and the freezestats must trip three times
within two hours before the unit control board will
lock out the compressor.

•

On Board Diagnostics - Each alarm will energize a
trouble light on the thermostat, if so equipped, and
flash an alarm code on the control board LED. Each
high and low-pressure switch alarm as well as each
freezestat alarm has its own flash code. The control
board saves the five most recent alarms in memory,
and these alarms can be reviewed at any time.
Alarms and programmed values are retained
through the loss of power.

All models are available with these “factory mounted” outdoor
air damper options:

All units have long lasting powder paint cabinets with 750 hour
salt spray test approval under ASTM-B117 procedures.

•

Single enthalpy economizer

All models are CSA listed.

•

Motorized outdoor air damper

•

Warranty - All models include a one-year limited parts
warranty on the complete unit. Compressors and electric
heater elements carry a five-year warranty. Gas heat
exchangers carry a 10-year parts warranty.

•

Gas Heat Operation - All single phase models with gas
heat have minimum annual fuel utilization efficiency
(AFUE) of 80%. All three phase models with gas heat
have minimum steady state efficiency of 80%. Each section includes a durable heat exchanger with aluminized
steel or optional stainless steel tubes, a redundant gas
valve, spark ignition, power venting, an ignition module
for 100% shut-off and all of the safety controls required
to meet the latest ANSI standards.

Supply air blowers are equipped with a 5 speed direct drive
motor that can be adjusted to meet the exact requirements of
the job.
All compressors are equipped with internal pressure relief.
Every refrigerant circuit includes a liquid line filter-drier, a high
pressure switch and a suction line with a freezestat and low
pressure/loss of charge switch to protect all system components.
•

Simplicity® Controls - Simplicity® control boards have
standardized a number of features previously available
only as options or by utilizing additional controls.
•

•

•

•

4

Low Ambient - An integrated low-ambient control
allows all units to operate in the cooling mode down
to 0ºF outdoor ambient without additional assistance. Optionally, the control board can be programmed to lockout the compressors when the
outdoor air temperature is low or when free cooling
is available.

The gas supply piping can be routed into the heating
compartment through a hole in the base pan of the unit
or through a knockout in the piping panel on the front of
the unit.
•

Anti-Short Cycle Protection - To aid compressor
life, an anti-short cycle delay is incorporated into the
standard controls. Compressor reliability is further
ensured by programmable minimum run times. For
testing, the anti short cycle delay can be temporarily
overridden with the push of a button.
Fan Delays - Fan on and fan off delays are fully programmable and are independent of one another. All
units are programmed with default values based
upon their configuration of cooling and heat.
Safety Monitoring - The control board monitors the
high and low-pressure switches, the freezestats, the

Electric Heat Operation - All electric heat models are
wired for a single power source and include a bank of
nickel chromium elements mounted at the discharge of
the supply air blower to provide a high velocity and uniform distribution of air across the heating elements.
Every element is fully protected against excessive temperature by thermal limit switches.
The power supply wiring can be routed into the control
box through a threaded pipe connection (field supplied)
in the base pan of the unit or through a knockout in the
wiring panel on the side of the unit.

•

BAS Controls - York’s Sunline™ series units offer factory
mounted BAS controls such as Simplicity® INTELLI-Comfort™, Novar, Honeywell, Johnson, and CPC.

Johnson Controls Unitary Products

343615-YTG-B-0308

Gas/Electric
20 Gauge aluminized
steel tubular heat exchanger
HACR
breaker

Electric heat
accessory location
Power ventor motor with
post purge cycle

Direct drive
blower

High efficiency
compressor

Economizer
hood

Copper tube/
aluminum fin
condensing coil
Knockout
for side
power entry
Slide-in
economizer

Smoke
detector
Full perimeter baserails
with forklift slots and
lifting holes
Knockout for side
gas supply entry

3/4" PVC female
condensate drain
GFCI
convenience outlet

Simplicity® Lite™
control board

Knockout
for side
control entry

Electric/Electric and Heat Pump

Knockout
for side
power entry

HACR
breaker

Direct drive
blower
High efficiency
compressor

Economizer
hood

Copper tube/
aluminum fin
condensing coil
Slide-in
economizer
Smoke
detector

Full perimeter baserails
with forklift slots and
lifting holes
3/4" PVC female
condensate drain

Electric Heat
accessory location

GFCI
convenience outlet

Simplicity® Lite™
control board
Knockout
for side
control entry

FIGURE 1 - UNIT CUTAWAY

Johnson Controls Unitary Products

5

343615-YTG-B-0308

FACTORY-INSTALLED OPTIONS
•

scheduling is built-in. Two different modes of demand
ventilation are achieved through the INTELLI-Comfort™
using CO2 sensors. It uses an inside CO2 sensor to perform Demand Ventilation. It can also use an Outside
CO2 sensor to perform Differential Demand Ventilation.
It uses a Patented Comfort Ventilation algorithm to provide comfortable ventilation air temperature. The patented economizer-loading algorithm will protect the
equipment when harsh operating conditions exist.
Humidity in the occupied space or return duct can be
monitored and controlled via humidity sensors and the
on-board connection for hot gas re-heat system. It uses
the INTELLI-Start™ algorithm to maximize energy savings by recovering the building from the Unoccupied Setpoints to the Occupied Setpoints just in time for the
Occupied Time Period to begin. The Simplicity®
INTELLI-Comfort™ balances space temperature, ventilation air temperature, CO2 and humidity for ultimate
comfort.

SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZERS - Includes a slide-in / plug-in damper assembly
with fully modulating spring-return motor actuator capable of introducing up to 100% outdoor air with nominal
1% leakage type dampers.
The enthalpy system contains one sensor that monitors
the outdoor air and determines when the air is cool
enough and dry enough to provide free cooling.
The rainhood is painted to match the basic unit and must
be field-assembled before installing.

•

MOTORIZED OUTDOOR AIR INTAKE DAMPER Includes a slide-in / plug-in damper assembly with a 2position, spring return motor actuator which opens to a
pre-set position whenever the supply air blower is operating and will drive fully closed when the blower unit
shuts down.
The rain hood is painted to match the basic unit and
must be field assembled before installing.

•

PHENOLIC COATED EVAPORATOR AND CONDENSER COILS - Special coating process that utilizes
Technicoat 10-1TM processes. Coating is applied by total
immersion of the complete coil for maximum protection.

•

ELECTRIC HEATERS - Wired for single point power
supply. These nickel chromium heater elements are provided with limit and automatic reset capability to prevent
operation at excessive temperatures.

•

FILTER OPTIONS - Standard units are shipped with 1”
throw-away filters installed. 2” pleated filters are offered
as a factory installed option.

•

CONVENIENCE OUTLET - This 110 volt outlet can be
“powered” by the unit with a stepdown transformer or the
unit may be ordered with a “non-powered” convenience
outlet that can be wired in the field.

•

•

6

DISCONNECT SWITCH - For gas heat units and cooling
units with electric heat, a HACR breaker sized to the unit
is provided. For cooling only units, a switch sized to the
largest electric heat available for the particular unit is
provided. Factory installed option only.
BAS - Building Automation System Controls
Simplicity® INTELLI-Comfort™ CONTROL - The York®
Simplicity® INTELLI-Comfort™ control is factory
installed. It includes a supply air sensor, a return air sensor, and an outside air sensor. There are provisions for a
field installed dirty filter indicator switch, an air-proving
switch, an Outside Air Humidity sensor, a Return Air
Humidity sensor, an Inside IAQ sensor, and an Outside
Air IAQ sensor. Construction mode operation, 365-day
real time clock with 7 day programming plus holiday

•

Simplicity® INTELLI-Comfort™ with MOD LINK CONTROL - The York® Simplicity® INTELLI-Comfort™ with
Mod Link control is factory installed. It includes all the
features of the INTELLI-Comfort™ control with an additional control to translate communications from MODBUS to the BACnet MSTP protocol.

•

Novar® BAS CONTROL - The Novar® ETC-3 building
automation system controller is factory installed.
Includes supply air sensor, return air sensor, dirty filter
indicator switch, and air proving switch.

•

JOHNSON CONTROLS BAS CONTROL - The Johnson
Control YK-UNT-1126 building automation system controller is factory installed. Includes supply air sensor,
return air sensor, dirty filter indicator switch, and air proving switch.

•

CPC BAS CONTROL - The Computer Process Controls
Model 810-3060 ARTC Advanced Rooftop building automation system controller is factory installed. Includes
supply air sensor, return air sensor, dirty filter indicator
switch and air proving switch.

•

HONEYWELL BAS CONTROL - The Honeywell
W7750C building automation system controller is factory
installed. Includes air supply sensor, return air sensor,
dirty filter indicator switch, and air proving switch.

•

SMOKE DETECTORS - (supply air & return air) The
smoke detectors stop operation of the unit by interrupting
power to the control board if smoke is detected within the
air compartment.

•

COIL GUARD - Customers can purchase a coil guard kit
to protect the condenser coil from damage. This is not a
hail guard kit.

Johnson Controls Unitary Products

343615-YTG-B-0308

•

Factory installed Smoke Detectors in the Return
Air, may be subjected to freezing temperatures
during "off" times due to Out Side Air infiltration.
These Smoke Detectors have an operational limit
of 32°F to 131°F. Smoke Detectors installed in
areas that could be out side those limitations will
have to be moved to prevent having false alarms.
•

STAINLESS STEEL HEAT EXCHANGER - For applications in corrosive environments, this option provides a
full stainless steel heat exchanger assembly.

MOTORIZED OUTDOOR AIR INTAKE DAMPER Includes a slide-in / plug-in damper assembly with a 2position, spring return motor actuator which opens to
some pre-set position whenever the supply air blower is
operating and will drive fully closed when the blower unit
shuts down.
The rain hood is painted to match the basic unit and
must be field assembled before installing.

•

ELECTRIC HEATERS wired for single point power supply. These nickel chromium heater elements are provided with limit and automatic reset capability to prevent
operation at excessive temperatures.

•

ROOF CURBS - Eight and fourteen-inch high roof curbs
provide a water-tight seal between the unit and the finished
roof. These full perimeter curbs meet the requirements of
the National Roofing Contractors Association (NRCA) and
are shipped knocked-down for field assembly.

•

STAINLESS STEEL DRAIN PAN - An optional rustproof stainless steel drain pan is available to provide
years of trouble-free operation in corrosive environments.

•

BOTTOM DRAIN CONNECTION - An optional bottom
drain connection is available for inside the curb connections for applications in cold environments to reduce
freezing drain lines.

•

PHASE MONITORS - Designed to prevent unit damage.
The phase monitor will shut the unit down in an out-ofphase condition.

HIGH ALTITUDE NATURAL GAS - Burner orifices and
pilot orifices are provided for proper furnace operation at
altitudes up to 6,000 feet.

•

DIRTY FILTER SWITCH - This kit includes a differential
pressure switch that energizes the fault light on the unit
thermostat, indicating that there is an abnormally high
pressure drop across the filters. Factory installed option
or field installed accessory.

PROPANE - Burner orifices, pilot orifices and gas valve
parts are provided to convert a natural gas furnace to
propane.

•

HINGED FILTER DOOR/“TOOLLESS” BLOWER AND
ACCESS PANELS (not hinged) - This option allows for
easy access and maintenance.

HIGH ALTITUDE PROPANE - Burner orifices and pilot
orifices are provided for proper furnace operation at altitudes up to 6,000 feet. This accessory supplements the
basic propane conversion kit.

•

LOW NOX KIT - Required to reduce the emission of
nitrogen oxides below 40 nano grams per joule.

•

POWER EXHAUST - Our single input economizer
options are available with power exhaust. Whenever the
outdoor air intake dampers are opened for free cooling,
the exhaust fan will be energized to prevent the conditioned space from being over-pressurized during economizer operation.

•

•

•

NOTE:Knobs are shipped inside the unit to prevent shipping damage. These must be field installed for
tool-less operation.

Roof curbs are designed to fit inside the base rails of the
unit and include both a wood nailing strip and duct
hanger supports.

FIELD-INSTALLED ACCESSORIES
•

SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZERS - Includes a slide-in / plug-in damper assembly
with fully modulating spring-return motor actuator capable of introducing up to 100% outdoor air with nominal
1% leakage type dampers.
The enthalpy system contains one sensor that monitors
the outdoor air and determines when the air is cool
enough and dry enough to provide free cooling.
The rainhood is painted to match the basic unit and must
be field-assembled before installing.

Johnson Controls Unitary Products

The power exhaust option can only be used on bottom duct configurations.
•

BAROMETRIC RELIEF DAMPER - This damper accessory can be used to relieve internal building air pressure
on units with an economizer without power exhaust. This
accessory includes a rain hood, a bird screen and a fully
assembled damper. With bottom duct connections, the
damper should be mounted over the opening in the
return air panel. With horizontal ductwork, the accessory
should be mounted on the return air duct.

7

343615-YTG-B-0308

•

ENTHALPY ACCESSORY CONTROL KIT - This kit
contains the required components to convert a single
enthalpy economizer to dual enthalpy.

•

CO2 SENSOR - Senses CO2 levels and automatically
overrides the economizer when levels rise above the
present limits.

•

BURGLAR BARS - Mount in the supply and return
openings to prevent entry into the duct work.

•

COIL GUARD - Customers can purchase a coil guard kit
to protect the condenser coil from damage. This is not a
hail guard kit.

•

FLUE EXHAUST EXTENSION KIT - In locations with
wind or weather conditions which may interfere with
proper exhausting of furnace combustion products, this
kit can be installed to prevent the flue exhaust from
entering nearby fresh air intakes.

•

HAIL GUARD - Hail Guard kit is available to prevent unit
from hail damage. This is a sloped hood that fits above
the coil.

•

GAS PIPING KIT - This kit supplies all necessary fittings
and shut off valve.

TABLE 1:

CAPACITY RATINGS - (ARI 210/240)1

TABLE 2:

MODEL

MBH

EER2

SEER3

CFM

SOUND
RATING
(Db)4

DY036
DY048
DY060

35.6
46.0
59.0

12
12
11.6

14
14
14

1200
1600
1750

84
83
81

1. 80/67°F Indoor and 95°F outdoor.
2. EER = Energy Efficiency Ratio at full load - the cooling
capacity in Btu’s per hour (Btuh) divided by the power
input in watts, expressed in Btuh per watt (Btuh/watt).
3. SEER = Seasonal Energy Efficiency Ratio.
4. Rated in accordance with ARI 270 Standard.

TABLE 3:

GAS HEAT RATINGS1

MODEL

MBH
INPUT

MBH
OUTPUT

AFUE
(%)

TEMP
RISE ºF

50
100

40
80

80.9
80.5

15 - 45
45 - 75

75
125

60
100

80.9
80.3

25 - 70
45 - 75

100
125

80
100

80.5
80.3

25 - 55
30 - 75

DY036N04
DY036N08
DY048N06
DY048N10
DY060N08
DY060N10

1. All units are single-stage heating.

2 STAGE GAS HEAT RATINGS

MODEL1
DY036D06
DY036D10
DY048D06
DY048D10
DY060D06
DY060D10

MBH INPUT
MBH OUTPUT
STEADY STATE EFFICIENCY
2ND STAGE
1ST STAGE 2ND STAGE 1ST STAGE 2ND STAGE 1ST STAGE
45
69
45
75
45
75

75
115
75
125
75
125

35.8
55.2
35.7
60.4
35.8
60.4

60.8
92
60.8
100.6
60.8
100.6

79.4
80.0
79.4
80.5
79.4
80.5

81.1
80.2
81.1
80.5
81.1
80.5

RISE
MIN. MAX.
35
55
25
45
20
35

70
90
70
75
55
75

MINIMUM HEATING
AIRFLOW (CFM)
790
950
790
1230
1010
1230

1. Models are 3Ø only.

8

Johnson Controls Unitary Products

343615-YTG-B-0308

TABLE 4:

DY036 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED INLET)

UNIT DESCRIPTION / MODEL
CONFIGURATION
Indoor Blower Speed (RPM)
Blower Static Pressure (IWG)
Airflow (CFM)
Blower Motor BHP
Octave Center Freq.
63
125
250
500
1000
2000
4000
8000

630
0.2
1116
0.41
Cooling
ID Blower
Operation2
Only (dB)
(dB)
80
82
76
77
56
59
50
50
40
43
41
42
41
41
45
45

DY036 / 3 Ton
Horizontal Ducted Inlet
631
879
885
0.3
0.2
0.7
928
1979
1020
0.37
0.76
0.53
Cooling
Cooling
Cooling
ID Blower
ID Blower
ID Blower
Operation2
Operation2
Operation2
Only (dB)
Only (dB)
Only (dB)
(dB)
(dB)
(dB)
80
82
78
83
81
85
76
77
82
83
81
82
56
60
60
61
58
60
49
50
54
54
51
52
39
42
49
50
44
45
40
42
49
49
43
44
41
41
49
49
41
41
45
45
47
47
45
45

1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment .
2. Cooling Operation – ID blower, compressor and outdoor fan operating.
3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).
4. Test duct termination is flush with reverberation room wall.
5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.

TABLE 5:

DY036 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED DISCHARGE)

UNIT DESCRIPTION / MODEL
CONFIGURATION
Indoor Blower Speed (RPM)
Blower Static Pressure (IWG)
Airflow (CFM)
Blower Motor BHP
Octave Center Freq.
63
125
250
500
1000
2000
4000
8000

630
0.2
1116
0.41
Cooling
ID Blower
Operation2
Only (dB)
(dB)
80
84
74
77
58
61
48
51
41
45
39
41
41
41
45
45

DY036 / 3 Ton
Horizontal Ducted Discharge
631
879
885
0.3
0.2
0.7
928
1979
1020
0.37
0.76
0.53
Cooling
Cooling
Cooling
ID Blower
2 ID Blower
2 ID Blower
Operation
Operation2
Operation
Only (dB)
Only (dB)
Only (dB)
(dB)
(dB)
(dB)
80
83
85
87
84
87
74
76
80
82
80
83
58
61
68
68
63
65
47
50
58
58
53
54
39
43
55
55
49
50
37
39
53
53
46
47
38
38
55
55
49
49
44
44
52
53
47
47

1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment .
2. Cooling Operation – ID blower, compressor and outdoor fan operating.
3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).
4. Test duct termination is flush with reverberation room wall.
5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.

Johnson Controls Unitary Products

9

343615-YTG-B-0308

TABLE 6:

DY036 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED INLET)

UNIT DESCRIPTION / MODEL
CONFIGURATION
Indoor Blower Speed (RPM)
Blower Static Pressure (IWG)
Airflow (CFM)
Blower Motor BHP
Octave Center Freq.
63
125
250
500
1000
2000
4000
8000

632
0.2
1069
0.36
Cooling
ID Blower
Operation2
Only (dB)
(dB)
78
82
70
75
55
60
47
50
40
43
37
40
36
37
44
44

DY036 / 3 Ton
Vertical Ducted Inlet
632
881
883
0.3
0.2
0.7
870
1903
917
0.33
0.71
0.49
Cooling
Cooling
Cooling
ID Blower
ID Blower
ID Blower
Operation2
Operation2
Operation2
Only (dB)
Only (dB)
Only (dB)
(dB)
(dB)
(dB)
78
82
80
85
80
84
70
74
71
80
71
79
55
60
59
61
58
62
47
50
52
53
49
52
39
43
50
51
45
46
37
39
45
46
41
43
36
37
45
46
40
40
44
44
45
47
44
44

1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment .
2. Cooling Operation – ID blower, compressor and outdoor fan operating.
3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).
4. Test duct termination is flush with reverberation room wall.
5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.

TABLE 7:

DY036 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED DISCHARGE)

UNIT DESCRIPTION / MODEL
CONFIGURATION
Indoor Blower Speed (RPM)
Blower Static Pressure (IWG)
Airflow (CFM)
Blower Motor BHP
Octave Center Freq.
63
125
250
500
1000
2000
4000
8000

632
0.2
1069
0.36
Cooling
ID Blower
Operation2
Only (dB)
(dB)
80
83
78
79
55
60
48
51
41
44
37
40
38
39
44
45

DY036 / 3 Ton
Vertical Ducted Discharge
632
881
883
0.3
0.2
0.7
870
1903
917
0.33
0.71
0.49
Cooling
Cooling
Cooling
ID Blower
2 ID Blower
2 ID Blower
Operation
Operation2
Operation
Only (dB)
Only (dB)
Only (dB)
(dB)
(dB)
(dB)
80
83
83
86
82
85
77
78
80
83
79
82
54
59
63
63
58
62
46
50
58
59
52
53
39
43
54
55
48
49
35
38
50
50
42
44
36
37
52
53
44
44
44
44
49
50
45
45

1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment .
2. Cooling Operation – ID blower, compressor and outdoor fan operating.
3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).
4. Test duct termination is flush with reverberation room wall.
5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.

10

Johnson Controls Unitary Products

343615-YTG-B-0308

TABLE 8:

DY048 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED INLET)

UNIT DESCRIPTION / MODEL
CONFIGURATION
Indoor Blower Speed (RPM)
Blower Static Pressure (IWG)
Airflow (CFM)
Blower Motor BHP
Octave Center Freq.
63
125
250
500
1000
2000
4000
8000

766
0.2
1484
0.67
Cooling
ID Blower
Operation2
Only (dB)
(dB)
74
97
70
86
53
58
49
55
42
42
40
44
38
44
42
43

DY048 / 4 Ton
Horizontal Ducted Inlet
769
1077
1087
0.5
0.4
1.0
993
2270
1406
0.54
1.24
0.90
Cooling
Cooling
Cooling
ID Blower
ID Blower
ID Blower
Operation2
Operation2
Operation2
Only (dB)
Only (dB)
Only (dB)
(dB)
(dB)
(dB)
74
95
77
90
77
90
69
86
73
78
72
77
52
57
60
61
58
61
47
54
54
56
51
53
38
39
50
55
45
45
38
43
48
51
45
46
36
41
48
52
43
45
42
44
45
48
44
45

1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment .
2. Cooling Operation – ID blower, compressor and outdoor fan operating.
3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).
4. Test duct termination is flush with reverberation room wall.
5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.

TABLE 9:

DY048 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED DISCHARGE)

UNIT DESCRIPTION / MODEL
CONFIGURATION
Indoor Blower Speed (RPM)
Blower Static Pressure (IWG)
Airflow (CFM)
Blower Motor BHP
Octave Center Freq.
63
125
250
500
1000
2000
4000
8000

766
0.2
1484
0.67
Cooling
ID Blower
Operation2
Only (dB)
(dB)
77
97
72
86
60
62
53
56
47
47
45
46
46
47
47
47

DY048 / 4 Ton
Horizontal Ducted Discharge
769
1077
1087
0.5
0.4
1.0
993
2270
1406
0.54
1.24
0.90
Cooling
Cooling
Cooling
ID Blower
2 ID Blower
2 ID Blower
Operation
Operation
Operation2
Only (dB)
Only (dB)
Only (dB)
(dB)
(dB)
(dB)
75
95
84
91
82
91
69
85
81
83
78
80
57
59
71
71
66
67
49
54
60
61
55
56
42
43
58
59
52
52
40
43
54
55
50
50
40
42
57
58
52
52
45
45
54
54
48
49

1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment .
2. Cooling Operation – ID blower, compressor and outdoor fan operating.
3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).
4. Test duct termination is flush with reverberation room wall.
5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.

Johnson Controls Unitary Products

11

343615-YTG-B-0308

TABLE 10: DY048 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED INLET)
UNIT DESCRIPTION / MODEL
CONFIGURATION
Indoor Blower Speed (RPM)
Blower Static Pressure (IWG)
Airflow (CFM)
Blower Motor BHP
Octave Center Freq.
63
125
250
500
1000
2000
4000
8000

791
0.2
1408
0.54
Cooling
ID Blower
Operation2
Only (dB)
(dB)
76
95
68
84
54
57
48
53
43
44
40
43
38
43
43
43

DY048 / 4 Ton
Vertical Ducted Inlet
794
1084
1095
0.5
0.2
1.0
1000
2336
1275
0.42
1.12
0.73
Cooling
Cooling
Cooling
ID Blower
ID Blower
ID Blower
Operation2
Operation2
Operation2
Only (dB)
Only (dB)
Only (dB)
(dB)
(dB)
(dB)
77
93
80
91
79
91
67
82
76
84
73
80
52
56
63
61
57
59
46
53
54
57
50
53
40
41
52
52
47
47
38
42
49
51
44
46
36
40
49
54
43
45
43
43
45
47
44
44

1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment .
2. Cooling Operation – ID blower, compressor and outdoor fan operating.
3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).
4. Test duct termination is flush with reverberation room wall.
5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.

TABLE 11: DY048 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED DISCHARGE)
UNIT DESCRIPTION / MODEL
CONFIGURATION
Indoor Blower Speed (RPM)
Blower Static Pressure (IWG)
Airflow (CFM)
Blower Motor BHP
Octave Center Freq.
63
125
250
500
1000
2000
4000
8000

791
0.2
1408
0.54
Cooling
ID Blower
Operation2
Only (dB)
(dB)
78
95
73
84
56
58
51
54
46
46
42
44
43
45
44
44

DY048 / 4 Ton
Vertical Ducted Discharge
794
1084
1095
0.5
0.2
1.0
1000
2336
1275
0.42
1.12
0.73
Cooling
Cooling
Cooling
ID Blower
2 ID Blower
2 ID Blower
Operation
Operation
Operation2
Only (dB)
Only (dB)
Only (dB)
(dB)
(dB)
(dB)
77
93
85
92
82
91
72
82
84
87
78
82
53
56
68
68
60
61
48
53
61
62
54
55
43
44
57
57
50
50
38
42
53
54
46
48
39
41
55
57
49
50
43
43
52
52
46
47

1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment .
2. Cooling Operation – ID blower, compressor and outdoor fan operating.
3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).
4. Test duct termination is flush with reverberation room wall.
5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.

12

Johnson Controls Unitary Products

343615-YTG-B-0308

TABLE 12: DY060 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED INLET)
UNIT DESCRIPTION / MODEL
CONFIGURATION
Indoor Blower Speed (RPM)
Blower Static Pressure (IWG)
Airflow (CFM)
Blower Motor BHP
Octave Center Freq.
63
125
250
500
1000
2000
4000
8000

840
0.2
1695
0.67
Cooling
ID Blower
Operation2
Only (dB)
(dB)
77
84
71
71
57
58
53
53
50
50
49
49
49
49
49
49

DY060 / 5 Ton
Horizontal Ducted Inlet
845
1166
1188
0.6
0.3
1.3
1100
2618
1323
0.50
1.51
0.80
Cooling
Cooling
Cooling
ID Blower
ID Blower
ID Blower
Operation2
Operation2
Operation2
Only (dB)
Only (dB)
Only (dB)
(dB)
(dB)
(dB)
77
84
81
85
79
84
72
73
74
75
71
72
55
56
66
66
60
61
51
51
60
60
55
55
45
46
60
60
53
53
43
44
58
58
50
50
42
43
59
59
47
47
48
48
54
54
47
47

1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment .
2. Cooling Operation – ID blower, compressor and outdoor fan operating.
3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).
4. Test duct termination is flush with reverberation room wall.
5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.

TABLE 13: DY060 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED DISCHARGE)
UNIT DESCRIPTION / MODEL
CONFIGURATION
Indoor Blower Speed (RPM)
Blower Static Pressure (IWG)
Airflow (CFM)
Blower Motor BHP
Octave Center Freq.
63
125
250
500
1000
2000
4000
8000

840
0.2
1695
0.67
Cooling
ID Blower
Operation2
Only (dB)
(dB)
82
87
75
76
69
69
64
64
59
60
55
55
58
58
55
55

DY060 / 5 Ton
Horizontal Ducted Discharge
845
1166
1188
0.3
1.3
0.6
2618
1323
1100
0.80
0.50
1.51
Cooling
Cooling
Cooling
ID Blower
2 ID Blower
2 ID Blower
Operation2
Operation
Operation
Only (dB)
Only (dB)
Only (dB)
(dB)
(dB)
(dB)
79
88
88
89
82
87
72
74
82
83
78
78
66
66
79
79
73
73
60
60
72
72
66
66
55
56
68
68
61
61
50
50
65
65
57
57
52
52
68
68
60
60
49
49
66
67
56
56

1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment .
2. Cooling Operation – ID blower, compressor and outdoor fan operating.
3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).
4. Test duct termination is flush with reverberation room wall.
5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.

Johnson Controls Unitary Products

13

343615-YTG-B-0308

TABLE 14: DY060 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED INLET)
UNIT DESCRIPTION / MODEL
CONFIGURATION
Indoor Blower Speed (RPM)
Blower Static Pressure (IWG)
Airflow (CFM)
Blower Motor BHP
Octave Center Freq.
63
125
250
500
1000
2000
4000
8000

834
0.2
1525
0.61
Cooling
ID Blower
Operation2
Only (dB)
(dB)
77
86
69
70
56
63
50
52
48
51
43
47
47
49
46
47

DY060 / 5 Ton
Vertical Ducted Inlet
840
1171
1194
0.6
0.2
1.3
1019
2624
1256
0.44
1.43
0.83
Cooling
Cooling
Cooling
ID Blower
ID Blower
ID Blower
Operation2
Operation2
Operation2
Only (dB)
Only (dB)
Only (dB)
(dB)
(dB)
(dB)
79
88
81
86
83
87
70
72
71
73
72
72
56
58
64
72
63
69
48
49
57
59
53
56
44
45
57
58
49
52
39
41
54
57
47
50
40
41
55
61
47
52
44
45
51
57
47
49

1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment .
2. Cooling Operation – ID blower, compressor and outdoor fan operating.
3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).
4. Test duct termination is flush with reverberation room wall.
5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.

TABLE 15: DY060 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED DISCHARGE)
UNIT DESCRIPTION / MODEL
CONFIGURATION
Indoor Blower Speed (RPM)
Blower Static Pressure (IWG)
Airflow (CFM)
Blower Motor BHP
Octave Center Freq.
63
125
250
500
1000
2000
4000
8000

834
0.2
1525
0.61
Cooling
ID Blower
Operation2
Only (dB)
(dB)
83
88
78
78
66
67
59
60
57
58
51
52
54
54
52
52

DY060 / 5 Ton
Vertical Ducted Discharge
840
1171
1194
0.6
0.2
1.3
1019
2624
1256
0.44
1.43
0.83
Cooling
Cooling
Cooling
ID Blower
2 ID Blower
2 ID Blower
Operation
Operation2
Operation
Only (dB)
Only (dB)
Only (dB)
(dB)
(dB)
(dB)
82
88
91
91
85
88
75
76
85
85
79
79
62
62
77
78
70
72
54
54
70
70
61
61
51
51
68
68
57
58
45
45
62
63
52
53
47
47
65
66
55
56
46
47
65
66
52
53

1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment .
2. Cooling Operation – ID blower, compressor and outdoor fan operating.
3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).
4. Test duct termination is flush with reverberation room wall.
5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.

14

Johnson Controls Unitary Products

343615-YTG-B-0308

TABLE 16: DY036 COOLING CAPACITIES (3 TON)
Temperature of Air on Condenser Coil

Air on Evaporator Coil
CFM

900

1050

1200

1350

1500

900

1050

1200

1350

1500

900

1050

1200

1350

1500

75°F

85°F

Sensible Capacity (MBH)1
Return Dry Bulb (°F)

Sensible Capacity (MBH)1
Return Dry Bulb (°F)

WB
(°F)

Total
Cap.1
(MBH)

Total2

Total2

Input
(kW)

86

83

80

77

74

71

68

86

83

72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57

44
42
40
39
44
42
40
39
44
43
40
39
45
43
41
40
46
44
42
41

2.3
2.3
2.3
2.3
2.2
2.3
2.3
2.3
2.2
2.3
2.3
2.3
2.2
2.3
2.3
2.3
2.3
2.3
2.3
2.3

24
30
40
39
26
33
40
39
28
35
40
39
30
37
41
40
32
40
42
41

21
28
35
37
23
30
38
38
25
32
40
39
26
33
41
40
27
35
42
41

16
23
30
32
17
24
32
34
18
25
33
36
18
25
35
36
18
26
37
36

14
20
28
30
14
21
29
31
14
21
30
32
14
21
31
32
14
22
33
32

18
25
27
18
26
28
18
26
29
18
27
28
17
28
27

15
23
25
15
23
25
14
23
25
14
23
24
13
24
23

41
38
35
35
42
39
35
35
43
40
36
36
43
40
37
36
44
41
37
37

2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5

23
29
35
35
25
31
35
35
27
34
36
36
29
36
37
36
31
39
37
37

20
26
32
34
22
28
34
35
24
31
36
36
25
32
37
36
27
34
37
37

72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57

38
35
30
30
39
36
31
31
41
37
32
32
41
37
32
33
42
38
33
33

2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7

21
27
30
30
24
30
31
31
26
33
32
32
28
35
32
33
30
38
33
33

19
24
29
30
21
27
31
31
23
30
32
32
24
31
32
33
26
33
33
33

14
19
24
25
15
21
26
27
16
23
29
29
16
23
28
29
17
24
28
29

11
17
22
22
12
18
23
24
12
19
25
25
12
19
24
25
12
20
24
24

14
19
19
15
20
21
16
22
22
15
20
21
15
19
20

12
17
17
12
17
18
12
18
18
11
16
17
11
15
15

35
31
27
27
36
32
28
28
37
33
29
29
37
33
29
29
37
33
29
29

3.0
2.9
3.0
3.0
3.0
2.9
2.9
2.9
2.9
2.8
2.9
2.9
3.0
2.9
2.9
2.9
3.1
2.9
3.0
3.0

20
25
27
27
22
28
28
28
25
31
29
29
27
32
29
29
28
33
29
29

17
23
26
27
19
25
28
28
21
28
29
29
23
29
29
29
24
31
29
29

72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57

32
27
24
25
32
28
25
25
33
29
25
26
33
29
25
26
33
28
25
25

3.3
3.1
3.2
3.2
3.3
3.0
3.1
3.1
3.2
3.0
3.1
3.1
3.3
3.1
3.2
3.2
3.4
3.2
3.3
3.3

18
23
24
25
21
26
25
25
23
29
25
26
25
29
25
26
27
28
25
25

16
21
23
25
18
23
24
25
20
26
25
26
21
27
25
26
22
28
25
25

19
25
33
35
20
27
35
37
21
28
37
39
22
29
39
40
23
31
42
41
95°F
16
22
27
27
18
24
30
30
19
26
32
32
20
27
32
33
21
29
33
33
115°F
13
18
21
23
15
20
23
25
16
22
25
27
17
23
25
26
18
25
25
25

11
16
18
20
12
17
20
22
13
19
22
24
13
19
21
22
13
20
20
21

8
13
16
17
9
14
17
19
9
15
18
20
9
15
17
18
9
16
16
16

11
13
15
11
14
16
12
15
17
11
13
14
11
11
12

8
11
12
8
11
13
8
11
13
8
9
10
7
7
8

28
24
21
22
29
24
21
22
29
25
22
22
29
24
21
22
28
24
21
22

3.7
3.3
3.5
3.5
3.5
3.2
3.4
3.4
3.4
3.1
3.3
3.3
3.6
3.2
3.4
3.4
3.8
3.4
3.6
3.6

17
22
21
22
19
24
21
22
21
25
22
22
23
24
21
22
25
24
21
22

14
19
20
22
16
22
21
22
18
24
22
22
19
24
21
22
20
24
21
22

Total
Cap.1 Input
(MBH) (kW)

80
18
24
30
31
19
25
32
33
20
27
34
36
21
28
36
36
22
30
37
37
105°F
15
20
24
25
16
22
26
27
18
24
29
30
19
25
29
30
20
27
29
29
125°F
12
17
18
20
13
18
20
22
14
20
22
22
15
21
21
22
16
23
21
22

77

74

71

68

15
21
27
28
16
22
29
30
17
24
31
32
17
24
32
32
18
25
33
32

12
18
25
26
13
19
26
27
13
20
27
29
13
20
28
28
13
21
28
28

16
22
23
16
23
24
17
24
25
16
24
24
16
24
23

13
20
21
13
20
21
13
20
22
12
20
20
12
19
19

12
18
21
22
13
19
23
24
14
21
25
26
15
21
25
26
15
22
24
25

10
15
19
20
10
16
20
21
11
17
22
23
11
17
21
22
11
18
20
20

12
16
17
13
17
18
14
18
19
13
17
18
13
15
16

10
14
15
10
14
15
10
15
16
9
13
14
9
11
11

9
14
15
18
10
15
17
19
11
17
18
21
11
17
17
19
11
18
16
17

7
11
13
15
7
12
14
16
7
13
15
18
7
13
13
15
7
14
12
13

9
10
13
9
11
13
10
11
14
10
9
11
9
7
8

6
8
10
6
8
10
6
8
11
6
5
7
5
3
4

1. The capacities are gross ratings. For net capacity, deduct indoor blower motor, MBH=3.415 x kW. Refer to the appropriate Blower Performance table for the kW of the supply air blower motor.

2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

Johnson Controls Unitary Products

15

343615-YTG-B-0308

TABLE 17: DY048 COOLING CAPACITIES (4 TON)
Temperature of Air on Condenser Coil

Air on Evaporator Coil
CFM

1200

1400

1600

1800

2000

1200

1400

1600

1800

2000

1200

1400

1600

1800

2000

75°F

85°F

Sensible Capacity (MBH)1
Return Dry Bulb (°F)

Sensible Capacity (MBH)1
Return Dry Bulb (°F)

WB
(°F)

Total
Cap.1
(MBH)

Total2

Total2

Input
(kW)

86

83

80

77

74

71

68

86

83

72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57

58
57
53
51
58
56
53
51
57
56
53
51
57
56
53
51
57
55
52
50

2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8

32
43
53
51
34
45
53
51
36
48
53
51
39
52
53
51
41
55
52
50

28
39
47
51
30
41
50
51
32
43
53
51
33
46
53
51
35
48
52
50

22
32
40
45
22
33
41
47
22
34
43
48
23
35
45
46
23
36
46
44

18
29
37
42
18
29
37
43
18
29
38
43
17
30
39
41
17
30
40
38

26
33
38
25
33
39
25
33
39
24
34
36
24
34
32

22
30
35
21
29
34
20
29
34
19
29
30
18
28
26

54
51
47
46
55
52
48
46
55
52
48
47
55
52
48
47
55
52
48
46

3.1
3.1
3.0
3.0
3.1
3.1
3.0
3.0
3.1
3.1
3.1
3.0
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1

30
40
47
46
33
43
48
46
36
46
48
47
38
49
48
47
41
52
48
46

27
36
44
46
29
39
46
46
31
42
48
47
33
44
48
47
35
47
48
46

72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57

50
45
41
40
52
47
42
42
54
49
44
43
53
48
44
43
53
48
43
42

3.3
3.4
3.3
3.3
3.4
3.4
3.3
3.3
3.4
3.4
3.3
3.3
3.4
3.4
3.3
3.3
3.4
3.4
3.3
3.3

29
37
41
40
32
41
42
42
35
45
44
43
38
46
44
43
41
48
43
42

25
33
41
40
28
37
42
42
30
40
44
43
33
43
44
43
35
46
43
42

18
27
34
33
20
29
37
36
21
31
39
39
22
32
38
38
23
34
37
37

15
23
31
30
16
25
33
32
16
26
35
34
17
27
33
32
17
28
31
31

20
27
26
20
29
28
21
30
29
22
28
27
22
25
25

16
24
23
16
24
24
17
25
25
16
22
22
16
19
19

45
39
36
35
47
41
37
37
49
43
39
39
49
43
39
38
48
42
38
38

3.7
3.7
3.6
3.6
3.7
3.7
3.6
3.6
3.7
3.7
3.6
3.6
3.7
3.7
3.6
3.7
3.7
3.7
3.7
3.7

27
34
36
35
30
38
37
37
33
41
39
39
36
42
39
38
39
42
38
38

23
31
36
35
26
34
37
37
28
37
39
39
31
39
39
38
33
41
38
38

72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57

40
34
31
30
42
36
32
32
45
38
34
34
44
37
34
33
43
36
33
33

4.0
3.9
3.9
3.9
4.0
4.0
3.9
3.9
4.0
4.0
3.9
4.0
4.0
4.0
4.0
4.0
4.1
4.0
4.0
4.0

25
32
31
30
28
35
32
32
31
38
34
34
34
37
34
33
37
36
33
33

21
28
31
30
24
32
32
32
27
35
34
34
29
36
34
33
31
36
33
33

25
36
44
49
26
37
46
51
27
39
47
53
28
40
50
52
29
42
52
50
95°F
22
30
37
37
24
33
41
40
26
35
44
43
27
38
44
43
29
40
43
42
115°F
18
25
28
28
20
28
31
31
22
30
34
34
24
33
34
33
25
35
33
33

14
21
25
24
16
24
27
27
17
26
30
29
18
27
28
28
19
29
27
27

11
18
21
21
12
20
23
23
13
21
25
25
13
22
23
23
13
23
21
21

15
18
17
16
19
19
16
20
20
17
18
17
17
15
15

11
14
14
11
15
15
12
16
15
11
12
12
11
9
9

35
28
26
25
38
30
28
27
40
32
29
29
39
31
29
29
39
31
28
28

4.3
4.2
4.2
4.2
4.3
4.3
4.2
4.3
4.3
4.3
4.2
4.3
4.4
4.3
4.3
4.3
4.4
4.3
4.3
4.3

23
28
26
25
26
30
28
27
29
32
29
29
32
31
29
29
35
31
28
28

19
26
26
25
22
29
28
27
25
32
29
29
27
31
29
29
29
31
28
28

Total
Cap.1 Input
(MBH) (kW)

80
23
33
41
43
25
35
43
45
26
37
46
48
28
39
47
47
29
41
48
46
105°F
20
27
33
32
22
30
36
35
24
33
39
39
25
35
39
38
27
37
38
38
125°F
16
22
23
23
18
25
26
26
20
28
29
29
22
30
29
29
23
31
28
28

77

74

71

68

20
29
37
39
21
31
39
41
22
32
41
43
22
34
41
42
23
35
42
40

17
26
34
36
17
27
35
37
17
28
36
39
17
28
36
37
17
29
36
34

23
30
32
23
31
33
23
32
34
23
31
31
23
30
28

19
27
29
19
27
29
18
27
29
18
25
26
17
24
23

16
24
29
29
18
26
32
31
19
28
34
34
20
30
33
33
21
31
32
32

13
21
26
25
14
22
28
27
14
24
30
29
15
24
28
27
15
25
26
26

17
22
22
18
24
23
19
25
25
19
23
22
19
20
20

14
19
19
14
20
19
14
20
20
14
17
17
14
14
14

13
19
20
20
14
21
22
22
15
23
25
24
16
25
23
23
17
27
22
22

9
15
16
16
10
17
18
18
11
19
20
20
11
20
18
18
11
21
16
16

12
13
13
13
14
14
14
15
15
14
13
13
15
10
10

9
10
9
9
10
10
9
11
10
9
8
7
9
4
4

1. The capacities are gross ratings. For net capacity, deduct indoor blower motor, MBH=3.415 x kW. Refer to the appropriate Blower
Performance table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
16

Johnson Controls Unitary Products

343615-YTG-B-0308

TABLE 18: DY060 COOLING CAPACITIES (5 TON)
Temperature of Air on Condenser Coil

Air on Evaporator Coil
CFM

1500

1750

2000

2250

2500

1500

1750

2000

2250

2500

1500

1750

2000

2250

2500

75°F

85°F

Sensible Capacity (MBH)1
Return Dry Bulb (°F)

WB
(°F)

Total
Cap.1
(MBH)

Total2
Input
(kW)

86

83

72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57

73.9
67.1
60.7
57.7
76.2
69.2
62.7
59.6
78.6
71.4
64.6
61.4
79.1
71.9
65.0
61.8
79.6
72.3
65.5
62.2

3.7
3.7
3.6
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.8
3.7
3.7
3.7

39.9
50.5
60.7
57.7
44.3
55.9
62.7
59.6
48.7
61.3
64.6
61.4
52.5
66.8
65.0
61.8
56.3
72.3
65.5
62.2

35.6
46.3
55.2
57.7
39.2
50.9
59.9
59.6
42.8
55.5
64.6
61.4
45.8
59.2
65.0
61.8
48.8
62.9
65.5
62.2

72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57

64.6
59.2
54.6
53.0
66.4
60.8
56.1
54.5
68.2
62.5
57.6
55.9
68.5
62.8
57.8
56.2
68.8
63.0
58.1
56.4

4.8
4.7
4.6
4.7
4.8
4.7
4.6
4.7
4.8
4.7
4.7
4.7
4.8
4.8
4.7
4.7
4.9
4.8
4.7
4.8

37.4
47.3
54.6
53.0
41.5
52.2
56.1
54.5
45.6
57.2
57.6
55.9
49.3
60.1
57.8
56.2
53.0
63.0
58.1
56.4

33.1
43.0
52.1
53.0
36.4
47.2
54.8
54.5
39.7
51.4
57.6
55.9
42.6
55.0
57.8
56.2
45.5
58.6
58.1
56.4

72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57

57.9
52.2
48.5
47.8
59.0
53.1
49.3
48.7
60.0
54.1
50.2
49.6
59.9
54.0
50.2
49.5
59.9
53.9
50.1
49.4

6.0
6.0
5.9
5.9
6.0
6.0
5.9
5.9
6.0
5.9
5.9
5.9
6.1
6.0
5.9
6.0
6.1
6.0
6.0
6.0

33.8
43.8
48.5
47.8
37.5
48.4
49.3
48.7
41.3
53.0
50.2
49.6
45.0
53.5
50.2
49.5
48.8
53.9
50.1
49.4

29.5
39.6
48.0
47.8
32.5
43.4
49.1
48.7
35.4
47.2
50.2
49.6
38.4
50.6
50.2
49.5
41.3
53.9
50.1
49.4

80
31.3
42.0
50.9
54.1
34.1
45.8
55.6
59.0
37.0
49.6
60.2
63.9
39.2
52.6
62.8
63.1
41.4
55.5
65.5
62.2
95°F
28.8
38.7
47.8
49.2
31.3
42.1
52.0
53.6
33.9
45.5
56.3
57.9
36.0
48.4
57.2
57.2
38.1
51.2
58.1
56.4
115°F
25.3
35.3
43.7
43.8
27.4
38.3
47.4
47.6
29.6
41.3
51.2
51.4
31.7
44.3
50.6
50.4
33.9
47.3
50.1
49.4

Sensible Capacity (MBH)1
Return Dry Bulb (°F)

Total2

Total
Cap.1 Input
(MBH) (kW)

77

74

71

68

86

83

27.0
37.7
46.7
49.8
29.1
40.8
50.5
53.9
31.2
43.8
54.3
58.1
32.5
45.9
56.2
56.4
33.9
48.0
58.0
54.8

22.8
33.4
42.4
45.5
24.0
35.7
45.4
48.9
25.3
38.0
48.5
52.2
25.9
39.3
49.5
49.8
26.5
40.6
50.6
47.3

29.2
38.1
41.3
30.6
40.4
43.8
32.1
42.7
46.4
32.6
42.9
43.1
33.1
43.1
39.9

24.9
33.8
37.0
25.6
35.3
38.8
26.3
36.9
40.6
26.0
36.3
36.5
25.7
35.7
32.4

69.2
63.1
57.6
55.4
71.3
65.0
59.4
57.0
73.4
66.9
61.1
58.7
73.8
67.3
61.4
59.0
74.2
67.7
61.8
59.3

4.3
4.2
4.1
4.2
4.3
4.2
4.1
4.2
4.3
4.2
4.2
4.2
4.3
4.2
4.2
4.2
4.3
4.3
4.2
4.2

38.6
48.9
57.6
55.4
42.9
54.1
59.4
57.0
47.1
59.2
61.1
58.7
50.9
63.5
61.4
59.0
54.6
67.7
61.8
59.3

34.3
44.6
53.6
55.4
37.8
49.0
57.4
57.0
41.3
53.4
61.1
58.7
44.2
57.1
61.4
59.0
47.2
60.8
61.8
59.3

24.5
34.4
43.5
44.9
26.3
37.1
47.0
48.5
28.1
39.7
50.4
52.1
29.3
41.7
50.5
50.5
30.6
43.7
50.6
49.0

20.2
30.2
39.3
40.7
21.2
32.0
41.9
43.4
22.2
33.9
44.6
46.2
22.7
35.1
43.9
43.9
23.2
36.3
43.2
41.5

25.9
35.0
36.4
27.0
36.9
38.4
28.1
38.8
40.4
28.4
37.2
37.2
28.8
35.7
34.1

21.6
30.7
32.1
21.9
31.8
33.3
22.2
32.9
34.6
21.8
30.6
30.6
21.4
28.3
26.6

61.3
55.7
51.5
50.4
62.7
57.0
52.7
51.6
64.1
58.3
53.9
52.8
64.2
58.4
54.0
52.8
64.3
58.5
54.1
52.9

5.4
5.3
5.3
5.3
5.4
5.3
5.3
5.3
5.4
5.3
5.3
5.3
5.4
5.4
5.3
5.3
5.5
5.4
5.3
5.4

35.6
45.6
51.5
50.4
39.5
50.3
52.7
51.6
43.4
55.1
53.9
52.8
47.1
56.8
54.0
52.8
50.9
58.5
54.1
52.9

31.3
41.3
50.0
50.4
34.4
45.3
52.0
51.6
37.6
49.3
53.9
52.8
40.5
52.8
54.0
52.8
43.4
56.3
54.1
52.9

21.0
31.0
39.4
39.6
22.4
33.3
42.4
42.5
23.8
35.5
45.3
45.5
25.1
37.7
44.0
43.7
26.4
39.9
42.6
42.0

16.7
26.7
35.1
35.3
17.3
28.2
37.3
37.5
17.9
29.7
39.5
39.7
18.5
31.0
37.3
37.1
19.0
32.4
35.2
34.5

22.5
30.9
31.0
23.1
32.3
32.4
23.8
33.7
33.9
24.4
30.7
30.5
25.0
27.7
27.1

18.2
26.6
26.7
18.1
27.2
27.4
18.0
27.9
28.0
17.8
24.1
23.8
17.5
20.3
19.6

54.6
48.7
45.4
45.2
55.3
49.3
46.0
45.8
55.9
49.9
46.5
46.4
55.7
49.7
46.3
46.1
55.4
49.4
46.1
45.9

6.7
6.6
6.6
6.6
6.7
6.6
6.5
6.6
6.6
6.5
6.5
6.5
6.7
6.6
6.6
6.6
6.7
6.6
6.6
6.6

32.0
42.1
45.4
45.2
35.6
46.5
46.0
45.8
39.1
49.9
46.5
46.4
42.9
49.7
46.3
46.1
46.7
49.4
46.1
45.9

27.8
37.8
45.4
45.2
30.5
41.5
46.0
45.8
33.3
45.1
46.5
46.4
36.3
48.3
46.3
46.1
39.2
49.4
46.1
45.9

80
30.1
40.4
49.4
51.6
32.7
44.0
53.8
56.3
35.4
47.6
58.2
60.9
37.6
50.5
60.0
60.1
39.7
53.3
61.8
59.3
105°F
27.0
37.0
45.8
46.5
29.4
40.2
49.7
50.6
31.7
43.4
53.7
54.6
33.9
46.3
53.9
53.8
36.0
49.2
54.1
52.9
125°F
23.5
33.6
41.6
41.1
25.5
36.4
45.1
44.6
27.4
39.2
46.5
46.4
29.6
42.3
46.3
46.1
31.8
45.4
46.1
45.9

77

74

71

68

25.8
36.1
45.1
47.4
27.7
38.9
48.7
51.2
29.6
41.8
52.4
55.1
30.9
43.8
53.4
53.5
32.3
45.9
54.3
51.9

21.5
31.8
40.8
43.1
22.6
33.9
43.7
46.2
23.8
35.9
46.6
49.2
24.3
37.2
46.7
46.8
24.8
38.4
46.9
44.4

27.5
36.5
38.8
28.8
38.6
41.1
30.1
40.7
43.4
30.5
40.1
40.2
31.0
39.4
37.0

23.2
32.3
34.5
23.8
33.6
36.1
24.3
34.9
37.6
23.9
33.4
33.6
23.5
32.0
29.5

22.8
32.7
41.5
42.2
24.3
35.2
44.7
45.5
25.9
37.6
47.9
48.8
27.2
39.7
47.3
47.1
28.5
41.8
46.6
45.5

18.5
28.4
37.2
38.0
19.3
30.1
39.6
40.5
20.1
31.8
42.1
43.0
20.6
33.1
40.6
40.5
21.1
34.3
39.2
38.0

24.2
32.9
33.7
25.1
34.6
35.4
25.9
36.2
37.1
26.4
34.0
33.9
26.9
31.7
30.6

19.9
28.6
29.4
20.0
29.5
30.4
20.1
30.4
31.3
19.8
27.3
27.2
19.4
24.3
23.1

19.2
29.3
37.3
36.9
20.4
31.3
40.1
39.6
21.6
33.4
42.8
42.2
23.0
35.7
40.7
40.4
24.3
37.9
38.6
38.5

14.9
25.0
33.1
32.6
15.4
26.3
35.0
34.5
15.8
27.6
37.0
36.4
16.3
29.0
34.1
33.7
16.9
30.5
31.2
31.0

20.7
28.8
28.3
21.2
30.0
29.4
21.7
31.1
30.6
22.4
27.4
27.1
23.0
23.7
23.6

16.5
24.5
24.0
16.2
24.9
24.4
15.9
25.3
24.7
15.7
20.8
20.4
15.6
16.3
16.1

1. The capacities are gross ratings. For net capacity, deduct indoor blower motor, MBH=3.415 x kW. Refer to the appropriate Blower Performance table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

Johnson Controls Unitary Products

17

343615-YTG-B-0308

TABLE 19: SUPPLY AIR BLOWER PERFORMANCE (DY036, 048, & 060 DIRECT DRIVE) SIDE DUCT APPLICATION

WATTS

CFM

WATTS

CFM

WATTS

CFM

WATTS

CFM

WATTS

CFM

WATTS

CFM

WATTS

1.0

CFM

0.9

WATTS

53

AVAILABLE EXTERNAL STATIC PRESSURE - IWG2
0.5
0.6
0.7
0.8

CFM

43

0.4

WATTS

33

HI
MED/HI
MED
MED/LOW
LOW
HI
MED/HI
MED
MED/LOW
LOW
HI
MED/HI
MED
MED/LOW
LOW

0.3

CFM

UNIT
MOTOR1
TONNAGE SPEED

0.2

1582
1488
1339
1233
1081
2056
1866
1680
1582
1300
2256
2145
2020
1757
1570

320
263
208
171
130
636
539
408
362
223
883
771
637
413
327

1538
1440
1292
1184
997
2017
1832
1641
1541
1258
2258
2127
1999
1713
1536

335
276
221
183
134
696
557
426
380
237
931
784
656
432
339

1496
1396
1247
1135
935
1978
1795
1594
1495
1202
2247
2119
1985
1677
1499

349
290
234
195
145
714
571
438
391
247
950
808
675
451
356

1458
1354
1201
1082
863
1942
1754
1558
1465
2223
2089
1947
1639
-

363
303
246
207
158
734
585
455
406
964
826
696
468
-

1418
1309
1152
1026
1906
1722
1517
1426
2182
2051
1910
1597
-

376
316
258
220
749
602
472
423
979
844
715
479
-

1381
1263
1102
957
1864
1679
1469
1377
2125
2014
1876
1559
-

390
329
272
235
764
619
490
440
971
859
730
497
-

1338
1214
1036
895
1815
1636
1415
1326
2044
1965
1832
1521
-

403
343
288
248
769
638
505
455
940
861
740
513
-

1298
1158
967
1728
1582
1370
1292
1958
1896
1793
1472
-

417
358
303
743
653
521
469
898
843
756
523
-

1255
1085
924
1582
1508
1337
1247
1864
1801
1725
-

430
374
313
685
639
536
485
854
806
748
-

1. Factory set on medium speed tap.
2. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCES Table for resistance values.
3. Side Duct application (230 Volts)

TABLE 20: SUPPLY AIR BLOWER PERFORMANCE (DY036, 048, & 060 DIRECT DRIVE) BOTTOM DUCT APPLICATION

WATTS

CFM

WATTS

CFM

WATTS

CFM

WATTS

CFM

WATTS

CFM

WATTS

CFM

WATTS

1.0

CFM

0.9

SPEED

WATTS

53

AVAILABLE EXTERNAL STATIC PRESSURE - IWG2
0.5
0.6
0.7
0.8

CFM

43

0.4

WATTS

33

0.3

CFM

UNIT
TONNAGE

0.2

MOTOR1

HI
MED/HI
MED
MED/LOW
LOW
HI
MED/HI
MED
MED/LOW
LOW
HI
MED/HI
MED
MED/LOW
LOW

1527
1437
1293
1191
1045
1985
1802
1622
1528
1256
2177
2071
1950
1697
1516

320
263
208
171
130
636
539
408
362
223
883
771
637
413
327

1485
1391
1248
1144
964
1947
1768
1585
1489
1216
2179
2053
1929
1654
1484

335
276
221
183
134
696
557
426
380
237
931
784
656
432
339

1445
1349
1205
1097
904
1909
1733
1539
1444
1161
2169
2045
1916
1619
1448

349
290
234
195
145
714
571
438
391
247
950
808
675
451
356

1408
1308
1161
1046
1875
1694
1505
1415
2145
2016
1880
1583
-

363
303
246
207
734
585
455
406
964
826
696
468
-

1370
1265
1114
992
1840
1662
1465
1377
2106
1980
1844
1542
-

376
316
258
220
749
602
472
423
979
844
715
479
-

1334
1221
1065
926
1800
1621
1419
1330
2051
1944
1811
1506
-

390
329
272
235
764
619
490
440
971
859
730
497
-

1292
1174
1002
866
1752
1580
1367
1281
1973
1897
1768
1469
-

403
343
288
248
769
638
505
455
940
861
740
513
-

1254
1120
935
1668
1528
1324
1248
1890
1830
1731
-

417
358
303
743
653
521
469
898
843
756
-

1213
1049
894
1528
1456
1291
1205
1800
1739
1665
-

430
374
313
685
639
536
485
854
806
748
-

1. Factory set on medium speed tap.
2. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCES Table for resistance values.
3. Bottom Duct application (230 Volts)

18

Johnson Controls Unitary Products

343615-YTG-B-0308

TABLE 21: STATIC RESISTANCES
RESISTANCE, IWG
DESCRIPTION

CFM
1000

1200

1400

1600

1800

2000

2200

2400

2600

2800

3000

0.07

0.08

0.09

0.11

0.13

0.15

0.17

0.20

0.23

0.26

0.30

7-15KW

0.04

0.05

0.06

0.07

0.08

0.10

0.12

0.14

0.16

0.19

0.22

20-30KW

0.06

0.07

0.08

0.09

0.11

0.13

0.15

0.17

0.20

0.23

0.26

0.08

0.10

0.12

0.14

0.16

0.18

0.20

0.23

0.26

0.29

0.32

ECONOMIZER1,3
ELECTRIC
HEATERS1
COOLING ONLY2

1. Deduct these resistance values from the available external static pressure shown in SUPPLY AIR BLOWER PERFORMANCE Tables.
2. Add these resistance values to the available static resistance values on SUPPLY AIR BLOWER PERFORMANCE Tables.
3. The pressure through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct system is less than
0.25 IWG, the unit will deliver less CFM during full economizer operation.

TABLE 22: ELECTRIC HEAT CFM LIMITATIONS
Size
(Tons)

3

4

5

Minimum Supply Air (CFM)
Voltage

Heater kW
5

7

10

15

20

30

208/230-1-60

900

900

900

900

900

-

208/230-3-60

900

900

900

900

900

-

460-3-60

-

900

900

900

900

-

600-3-60

-

-

900

900

900

-

208/230-1-60

1200

1200

1200

1200

1200

-

208/230-3-60

1200

1200

1200

1200

1200

-

460-3-60

-

1200

1200

1200

1200

-

600-3-60

-

-

1200

1200

1200

-

208/230-1-60

1500

1500

1500

1500

1500

1500

208/230-3-60

1500

1500

1500

1500

1500

1500

460-3-60

-

1500

1500

1500

1500

1500

600-3-60

-

-

1500

1500

1500

1500

Johnson Controls Unitary Products

19

343615-YTG-B-0308

TABLE 23: ELECTRICAL DATA - DY036, 048 & 060 DIRECT DRIVE W/O POWERED CONVENIENCE OUTLET
Size
(Tons)

Volt

Compressors
(each)
RLA LRA

MCC

OD Fan
Motors
(each)

Supply
Blower
Motor

Pwr
Conv
Outlet

FLA

FLA

FLA

208-1-60 11.3

68.0

17.5

2.3

6.0

0.0

230-1-60 11.3

68.0

17.5

2.3

6.0

0.0

208-3-60 8.3

68.0

13.0

2.3

6.0

0.0

230-3-60 8.3

68.0

13.0

2.3

6.0

0.0

460-3-60 5.1

34.0

8.0

1.3

6.0

0.0

575-3-60 3.2

26.0

5.0

1.3

6.0

0.0

208-1-60 15.4

86.0

24.0

2.3

7.6

0.0

230-1-60 15.4

86.0

24.0

2.3

7.6

0.0

208-3-60 11.5

84.0

18.0

2.3

7.6

0.0

230-3-60 11.5

84.0

18.0

2.3

7.6

0.0

460-3-60 5.8

42.0

9.0

1.3

7.6

0.0

575-3-60 5.1

34.0

8.0

1.3

7.6

0.0

036
(3.0)

048
(4.0)

20

Electric Heat Option

MCA1
(Amps)

Model

kW

Stages

Amps

None
E05
E07
E10
E15
E20
None
E05
E07
E10
E15
E20
None
E05
E07
E10
E15
E20
None
E05
E07
E10
E15
E20
None
E07
E10
E15
E20
None
E10
E15
E20
None
E05
E07
E10
E15
E20
None
E05
E07
E10
E15
E20
None
E05
E07
E10
E15
E20
None
E05
E07
E10
E15
E20
None
E07
E10
E15
E20
None
E10
E15
E20

4.0
5.6
8.0
11.9
15.9
5.3
7.5
10.6
15.9
21.2
4.0
5.6
8.0
11.9
15.9
5.3
7.5
10.6
15.9
21.2
6.8
10.1
13.6
19.5
10.6
15.9
21.2
4.0
5.6
8.0
11.9
15.9
5.3
7.5
10.6
15.9
21.2
4.0
5.6
8.0
11.9
15.9
5.3
7.5
10.6
15.9
21.2
6.8
10.1
13.6
19.5
10.6
15.9
21.2

1
1
1
2
2
1
1
1
2
2
1
1
1
2
2
1
1
1
2
2
1
1
2
2
1
1
2
1
1
1
2
2
1
1
1
2
2
1
1
1
2
2
1
1
1
2
2
1
1
2
2
1
1
2

19.2
26.9
38.5
57.2
76.4
23.0
32.6
46.1
69.1
92.2
11.1
15.5
22.2
33.0
44.1
13.3
18.8
26.6
39.9
53.2
8.5
12.7
17.1
24.5
10.6
16.0
21.3
19.2
26.9
38.5
57.2
76.4
23.0
32.6
46.1
69.1
92.2
11.1
15.5
22.2
33.0
44.1
13.3
18.8
26.6
39.9
53.2
8.5
12.7
17.1
24.5
10.6
16.0
21.3

22.4
31.5
41.2
55.6
79.0
103.1
22.4
35.1
46.6
62.7
90.3
117.9
18.7
21.4
26.9
35.3
48.8
62.7
18.7
23.4
30.1
39.4
55.3
71.2
10.7
14.0
18.9
24.2
33.1
7.4
15.7
22.1
28.5
29.1
33.5
43.2
57.6
81.0
105.1
29.1
37.1
48.6
64.7
92.3
119.9
24.3
24.3
28.9
37.3
50.8
64.7
24.3
25.4
32.1
41.4
57.3
73.2
12.4
15.0
19.9
25.2
34.1
10.5
16.5
22.9
29.3

Max
Fuse2/
Breaker3
Size
(Amps)
30
35
45
60
80
110
30
40
50
70
100
125
25
25
30
40
50
70
25
25
35
40
60
80
15
15
20
25
35
15
15
25
30
35
40
45
60
90
110
35
40
50
70
100
125
30
30
35
40
60
70
30
35
35
45
60
80
15
15
20
25
35
15
20
25
30

Johnson Controls Unitary Products

343615-YTG-B-0308

TABLE 23: ELECTRICAL DATA - DY036, 048 & 060 DIRECT DRIVE W/O POWERED CONVENIENCE OUTLET (CONT)
Size
(Tons)

Volt

Compressors
(each)
RLA LRA

MCC

OD Fan
Motors
(each)

Supply
Blower
Motor

Pwr
Conv
Outlet

FLA

FLA

FLA

208-1-60 28.8 145.0 45.0

2.3

7.6

0.0

230-1-60 28.8 145.0 45.0

2.3

7.6

0.0

208-3-60 17.3 123.0 27.0

2.3

7.6

0.0

230-3-60 17.3 123.0 27.0

2.3

7.6

0.0

460-3-60 9.6

70.0

15.0

1.3

7.6

0.0

575-3-60 7.4

53.0

11.5

1.3

7.6

0.0

060
(5.0)

Electric Heat Option

MCA1
(Amps)

Model

kW

Stages

Amps

None
E05
E07
E10
E15
E20
E30
None
E05
E07
E10
E15
E20
E30
None
E05
E07
E10
E15
E20
E30
None
E05
E07
E10
E15
E20
E30
None
E07
E10
E15
E20
E30
None
E10
E15
E20
E30

4.0
5.6
8.0
11.9
15.9
22.2
5.3
7.5
10.6
15.9
21.2
29.6
4.0
5.6
8.0
11.9
15.9
22.2
5.3
7.5
10.6
15.9
21.2
29.6
6.8
10.1
13.6
19.5
28.8
10.6
15.9
21.2
30.4

1
1
1
2
2
2
1
1
1
2
2
2
1
1
1
2
2
2
1
1
1
2
2
2
1
1
2
2
2
1
1
2
2

19.2
26.9
38.5
57.2
76.4
106.7
23.0
32.6
46.1
69.1
92.2
128.7
11.1
15.5
22.2
33.0
44.1
61.6
13.3
18.8
26.6
39.9
53.2
74.3
8.5
12.7
17.1
24.5
36.1
10.6
16.0
21.3
30.5

45.9
45.9
45.9
57.6
81.0
105.1
142.9
45.9
45.9
48.6
64.7
92.3
119.9
163.7
31.5
31.5
31.5
37.3
50.8
64.7
86.5
31.5
31.5
32.1
41.4
57.3
73.2
98.5
17.1
17.1
19.9
25.2
34.1
48.1
13.3
16.5
22.9
29.3
40.4

Max
Fuse2/
Breaker3
Size
(Amps)
50
50
50
60
90
110
150
50
50
50
70
100
125
175
35
35
35
40
60
70
90
35
35
35
45
60
80
100
20
20
20
25
35
50
15
20
25
30
40

1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.

Johnson Controls Unitary Products

21

343615-YTG-B-0308

TABLE 24: ELECTRICAL DATA - DY036, 048 & 060 DIRECT DRIVE W/ POWERED CONVENIENCE OUTLET
Size
(Tons)

Volt

Compressors
(each)
RLA LRA

MCC

OD Fan
Motors
(each)

Supply
Blower
Motor

Pwr
Conv
Outlet

FLA

FLA

FLA

208-1-60 11.3

68.0

17.5

2.3

6.0

10.0

230-1-60 11.3

68.0

17.5

2.3

6.0

10.0

208-3-60 8.3

68.0

13.0

2.3

6.0

10.0

230-3-60 8.3

68.0

13.0

2.3

6.0

10.0

460-3-60 5.1

34.0

8.0

1.3

6.0

5.0

575-3-60 3.2

26.0

5.0

1.3

6.0

4.0

208-1-60 15.4

86.0

24.0

2.3

7.6

10.0

230-1-60 15.4

86.0

24.0

2.3

7.6

10.0

208-3-60 11.5

84.0

18.0

2.3

7.6

10.0

230-3-60 11.5

84.0

18.0

2.3

7.6

10.0

460-3-60 5.8

42.0

9.0

1.3

7.6

5.0

575-3-60 5.1

34.0

8.0

1.3

7.6

4.0

036
(3.0)

048
(4.0)

22

Electric Heat Option

MCA1
(Amps)

Model

kW

Stages

Amps

None
E05
E07
E10
E15
E20
None
E05
E07
E10
E15
E20
None
E05
E07
E10
E15
E20
None
E05
E07
E10
E15
E20
None
E07
E10
E15
E20
None
E10
E15
E20
None
E05
E07
E10
E15
E20
None
E05
E07
E10
E15
E20
None
E05
E07
E10
E15
E20
None
E05
E07
E10
E15
E20
None
E07
E10
E15
E20
None
E10
E15
E20

4.0
5.6
8.0
11.9
15.9
5.3
7.5
10.6
15.9
21.2
4.0
5.6
8.0
11.9
15.9
5.3
7.5
10.6
15.9
21.2
6.8
10.1
13.6
19.5
10.6
15.9
21.2
4.0
5.6
8.0
11.9
15.9
5.3
7.5
10.6
15.9
21.2
4.0
5.6
8.0
11.9
15.9
5.3
7.5
10.6
15.9
21.2
6.8
10.1
13.6
19.5
10.6
15.9
21.2

1
1
1
2
2
1
1
1
2
2
1
1
1
2
2
1
1
1
2
2
1
1
2
2
1
1
2
1
1
1
2
2
1
1
1
2
2
1
1
1
2
2
1
1
1
2
2
1
1
2
2
1
1
2

19.2
26.9
38.5
57.2
76.4
23.0
32.6
46.1
69.1
92.2
11.1
15.5
22.2
33.0
44.1
13.3
18.8
26.6
39.9
53.2
8.5
12.7
17.1
24.5
10.6
16.0
21.3
19.2
26.9
38.5
57.2
76.4
23.0
32.6
46.1
69.1
92.2
11.1
15.5
22.2
33.0
44.1
13.3
18.8
26.6
39.9
53.2
8.5
12.7
17.1
24.5
10.6
16.0
21.3

32.4
44.0
53.7
68.1
91.5
115.6
32.4
47.6
59.1
75.2
102.8
130.4
29.1
33.9
39.4
47.8
61.3
75.2
29.1
35.9
42.6
51.9
67.8
83.7
15.7
20.2
25.2
30.4
39.3
11.6
20.7
27.1
33.5
39.1
46.0
55.7
70.1
93.5
117.6
39.1
49.6
61.1
77.2
104.8
132.4
34.3
35.9
41.4
49.8
63.3
77.2
34.3
37.9
44.6
53.9
69.8
85.7
17.4
21.2
26.2
31.4
40.3
14.5
21.5
27.9
34.3

Max
Fuse2/
Breaker3
Size
(Amps)
40
45
60
70
100
125
40
50
60
80
110
150
35
35
40
50
70
80
35
40
45
60
70
90
20
20
25
30
40
15
20
30
35
50
50
60
80
100
125
50
50
70
80
110
150
45
45
45
50
70
80
45
45
45
60
70
90
20
20
25
30
40
15
20
30
35

Johnson Controls Unitary Products

343615-YTG-B-0308

TABLE 24: ELECTRICAL DATA - DY036, 048 & 060 DIRECT DRIVE W/ POWERED CONVENIENCE OUTLET (CONT)
Size
(Tons)

Volt

Compressors
(each)
RLA LRA

MCC

OD Fan
Motors
(each)

Supply
Blower
Motor

Pwr
Conv
Outlet

FLA

FLA

FLA

208-1-60 28.8 145.0 45.0

2.3

7.6

10.0

230-1-60 28.8 145.0 45.0

2.3

7.6

10.0

208-3-60 17.3 123.0 27.0

2.3

7.6

10.0

230-3-60 17.3 123.0 27.0

2.3

7.6

10.0

460-3-60 9.6

70.0

15.0

1.3

7.6

5.0

575-3-60 7.4

53.0

11.5

1.3

7.6

4.0

060
(5.0)

Electric Heat Option

MCA1
(Amps)

Model

kW

Stages

Amps

None
E05
E07
E10
E15
E20
E30
None
E05
E07
E10
E15
E20
E30
None
E05
E07
E10
E15
E20
E30
None
E05
E07
E10
E15
E20
E30
None
E07
E10
E15
E20
E30
None
E10
E15
E20
E30

4.0
5.6
8.0
11.9
15.9
22.2
5.3
7.5
10.6
15.9
21.2
29.6
4.0
5.6
8.0
11.9
15.9
22.2
5.3
7.5
10.6
15.9
21.2
29.6
6.8
10.1
13.6
19.5
28.8
10.6
15.9
21.2
30.4

1
1
1
2
2
2
1
1
1
2
2
2
1
1
1
2
2
2
1
1
1
2
2
2
1
1
2
2
2
1
1
2
2

19.2
26.9
38.5
57.2
76.4
106.7
23.0
32.6
46.1
69.1
92.2
128.7
11.1
15.5
22.2
33.0
44.1
61.6
13.3
18.8
26.6
39.9
53.2
74.3
8.5
12.7
17.1
24.5
36.1
10.6
16.0
21.3
30.5

55.9
55.9
55.9
70.1
93.5
117.6
155.4
55.9
55.9
61.1
77.2
104.8
132.4
176.2
41.5
41.5
41.5
49.8
63.3
77.2
99.0
41.5
41.5
44.6
53.9
69.8
85.7
111.0
22.1
22.1
26.2
31.4
40.3
54.3
17.3
21.5
27.9
34.3
45.4

Max
Fuse2/
Breaker3
Size
(Amps)
60
60
60
80
100
125
175
60
60
70
80
110
150
200
45
45
45
50
70
80
100
45
45
45
60
70
90
125
25
25
25
30
40
60
20
20
30
35
45

1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.

Johnson Controls Unitary Products

23

343615-YTG-B-0308

TABLE 25: DY PHYSICAL DATA
DY

MODELS
EVAPORATOR
BLOWER
EVAPORATOR
COIL
CONDENSER
FANS
CONDENSER
COILS
COMPRESSOR
AIR
FILTERS
CHARGE

036

048

060

Centrifugal Blower (Dia. x Wd. in.)

12 X 10

12 X 10

12 X 10

Fan Motor HP (Direct Drive)

3/4

1

1

Rows Deep

3

4

4

Fins Per Inch

13

13

13
5.1

Face Area (Ft.2)

5.1

5.1

Propeller Dia. (in.)

24

24

24

Fan Motor HP

1/2

1/2

1/2
4200

Nom. CFM

4200

4200

Rows Deep

2

2

2

Fins Per Inch

18

18

18

Face Area (Ft.2)

17.1

17.1

17.1

Quantity

1

1

1

Type

Recip.

Recip.

Scroll

Quantity Per Unit (15” X 20” X 1” or 2“)

2

2

2

Quantity Per Unit (14” X 25” X 1” or 2“)

1

1

1

Total Face Area (Ft.2)

6.3

6.3

6.3

Refrigerant 22 (lbs./oz.)

9/4

9/8

11/8

TABLE 26: ELECTRIC HEAT CORRECTION FACTORS
NOMINAL VOLTAGE

VOLTAGE

kW CAP. MULTIPLIER

TABLE 27: VOLTAGE LIMITATIONS1
VOLTAGE

POWER SUPPLY
MIN.

MAX.

208/230-1-60

187

252

208

208

1.00

240

230

0.92

480

460

0.92

208/230-3-60

187

252

600

575

0.92

460-3-60

432

504

575-3-60

540

630

1. Utilization Range “A” in accordance with ARI Standard
110.

24

Johnson Controls Unitary Products

343615-YTG-B-0308

TYPICAL POWER WIRING

REFER TO THE ELECTRICAL DATA
TABLES TO SIZE THE DISCONNECT
SWITCH, OVERCURRENT PROTECTION AND WIRING.

TYPICAL CONTROL WIRING
COOLING ONLY (24 VOLT THERMOSTAT)
THERMOSTAT
TERMINALS

1

COOLING / HEATING (24 VOLT THERMOSTAT)
THERMOSTAT 1
TERMINALS

UNIT TERMINAL
STRIP TB1
R

RV

24 VOLT
TRANSFORMER

Y1

YC

ADD
JUMPER

Y2

UNIT TERMINAL
STRIP TB1

RC

R

Y

Y1

24 VOLT
TRANSFORMER

Y2

G

GF

W

C

1

RH

W1
W2

24 VOLT THERMOSTAT 2TH07701024. TO CONTROL THE ECONOMIZER
ON SECOND STAGE COOLING, USE THE THERMOSTAT 2TH0401224.

G

G
C

COOLING / HEATING (ELECTRONIC THERMOSTAT)
MULTI STAGE
THERMOSTAT1
TERMINALS
ADD
JUMPER

RC

UNIT TERMINAL
STRIP TB1

RH

R

Y1

Y1

2

Y2
W1

4

3

G
B

ADD
JUMPER

THERMOSTAT1
TERMINALS

W2

RH

C
X

NOT
USED

OCC

ADD
JUMPER

4

A1

T

UNIT TERMINAL
STRIP TB1

RC

R

Y

Y1

W

W1

G

G
C

A2
T

24 VOLT
TRANSFORMER

TO REMOTE SENSOR
2TH040702224 IF USED

1

ELECTRONIC PROGRAMMABLE THERMOSTAT 2ET04700224 (INCLUDES SUBBASE).

2

SECOND STAGE COOLING IS NOT REQUIRED ON UNITS LESS ECONOMIZER.

3

SECOND STAGE HEATING IS ONLY REQUIRED ON UNITS WITH A TWO STAGE
ELECTRIC HEATER OR 2 STAGE GAS HEAT.

4

COOLING / HEATING (ELECTRONIC THERMOSTAT)
SINGLE STAGE

G

LED 1
COM

Y2

24 VOLT THERMOSTAT 2ET07701024. TO CONTROL THE ECONOMIZER ON THE SECOND
STAGE COOLING OR TO HAVE AN ELECTRIC HEAT ACCESSORY WITH TWO STAGES OF
HEAT, USE THERMOSTAT 2TH0471024.

W1

W2

LED 2

24 VOLT
TRANSFORMER

1

1 ELECTRONIC

PROGRAMMABLE THERMOSTAT 2ET07701024 (INCLUDES SUBBASE).
TO CONTROL THE ECONOMIZER ON SECOND STAGE COOLING, USE THERMOSTAT
2TH04700224.

REMOVE JUMPER J2 FROM TERMINALS 4 AND 9 ON JUMPER PLUG CONNECTOR
P6 ON UNITS WITH ECONOMIZER. TERMINALS A1 AND A2 PROVIDE A RELAY
OUT-PUT TO CLOSE THE OUTDOOR ECONOMIZER DAMPERS WHEN THE
THERMOSTAT SWITCHES TO THE SET-BACK POSITION.

FIGURE 2 - TYPICAL FIELD POWER & CONTROL WIRING

Johnson Controls Unitary Products

25

343615-YTG-B-0308

FIGURE 3 - UNIT DIMENSIONS (3 - 5 TON COOLING ONLY/ELECTRIC HEAT) FRONT VIEW

FIGURE 4 - UNIT DIMENSIONS (3 - 5 TON COOLING/GAS HEAT) FRONT VIEW

26

Johnson Controls Unitary Products

343615-YTG-B-0308

DETAIL “A”
FIGURE 5 - UNIT WITH ECONOMIZER RAINHOOD

DETAIL “B”

FIGURE 6 - UNIT WITH FIXED OUTDOOR AIR/MOTORIZED DAMPER RAINHOOD

Johnson Controls Unitary Products

27

343615-YTG-B-0308

FIGURE 7 - UNIT DIMENSIONS (REAR VIEW)
TABLE 29: MINIMUM CLEARANCES
Filter Access

LOCATION

CLEARANCE

Front

24” (Cooling/Electric Heat)
32” (Gas Heat)

Rear

12” (Less Economizer)
36” (With Economizer or Fixed
Air/Motorized Damper)

Left Side (Filter Access)

24” (Less Economizer)
36” (With Economizer)

Right Side (Cond. Coil)

24”

Blower Motor Access
Dot Plugs

Field-Supplied Disconnect
Switch Location
Mounting Bracket for
Disconnect Switch
A,B
(Field Supplied)
Wiring Entry
(See Detail “B”)

Control Box Access

Disconnect Switch Location
and Motor Access Panel for
Unit with “Belt-Drive” Option

FIGURE 8 - DISCONNECT/BLOWER ACCESS LOCATION
TABLE 28: UTILITIES ENTRY
HOLE

OPENING SIZE (DIA.)

USED FOR

A

7/8” KO1

Control Wiring2

B

2” KO1

Power Wiring

C

1-5/8” KO

Gas Piping (Front)

D

1-1/2” KO

Gas Piping (Bottom)

Side

Below

Unit1

0”

Above

Unit2

72” (For
Condenser Air Discharge)

1. Units may be installed on combustible floors made
from wood or class A, B, or C roof covering material.
2. Units must be installed outdoors. Overhanging structures or shrubs should not obstruct condenser air discharge outlet.

Bottom
Side
Bottom

1. Opening in the bottom to the unit can be located by the
side in the insulation.
2. Do not remove the 2” knockout ring.

28

Johnson Controls Unitary Products

343615-YTG-B-0308

FIGURE 9 - TYPICAL APPLICATIONS

Johnson Controls Unitary Products

29

343615-YTG-B-0308

BACK OF UNIT

A

447/8

821/4

BACK OF UNIT

A

447/8

821/4

B

F

D

X

X
B

APPROXIMATE
CENTER OF GRAVITY

C

FRONT OF UNIT

APPROXIMATE
CENTER OF GRAVITY

CONDENSER COIL
END OF UNIT

Y

C

E
D

FRONT OF UNIT

CONDENSER COIL
END OF UNIT

Y

FIGURE 10 -FOUR AND SIX POINT LOADING
TABLE 30: DY 4 AND 6 POINT LOADS WEIGHT DISTRIBUTION
UNIT

TOTAL

4-Point Loading (lb)

6-Point Loading (lb)

A

B

C

D

A

B

C

D

E

F

DY036 Cooling/ Electric

575

132

125

155

164

89

85

82

102

106

110

DY036N04

615

141

133

166

175

95

91

88

110

114

118

DY036D06

625

143

135

168

178

96

93

89

111

115

120

DY036N08

635

145

138

171

181

98

94

91

113

117

122

DY036D10

645

148

140

174

184

99

96

92

115

119

124

DY048 Cooling/ Electric

585

134

127

158

167

90

87

84

104

108

112

DY048(D,N)06

635

145

138

171

181

98

94

91

113

117

122

DY048(D,N)10

655

150

142

177

187

101

97

94

117

121

125

DY060 Cooling/ Electric

590

135

128

159

168

91

88

84

105

109

113

DY060D06

640

147

139

173

182

99

95

92

114

118

123

DY060N08

650

149

141

175

185

100

97

93

116

120

125

DY060(D,N)10

660

151

143

178

188

102

98

95

118

122

126

TABLE 31: CENTER OF GRAVITY
DIMENSION

3 - 5 TON

X

40”

Y

20”

30

Johnson Controls Unitary Products

343615-YTG-B-0308

TABLE 32: OPERATING WEIGHTS (LBS.)
MODEL SIZE

3 TON

4 TON

5 TON

575

585

590

N04

615

-

-

N06

-

635

-

N08

635

-

650

DY (Cooling Only)

BASIC
UNIT

DY
(Gas/Electric)

N10

-

655

660

D06

625

635

640

D10

645

655

660

Economizer

50

Motorized Damper

OPTIONS
Electric Heater

26
5 - 7 kW

18

10 - 15 kW

23

20 - 30 kW

ACCY.

28

Roof Curb

92

Barometric Relief / Fixed Air Damper

10

FIGURE 11 -ROOF CURB DIMENSIONS

Johnson Controls Unitary Products

31

343615-YTG-B-0308

GUIDE SPECIFICATIONS
GENERAL
Units shall be manufactured by York International Unitary
Products Group in an ISO 9001 certified facility.
York's Sunline Magnum™ units are convertible single package units. Although the units are primarily designed for curb
mounting on a roof, they can also be slab-mounted at ground
level or set on steel beams above a finished roof. Cooling
only, cooling with gas heat and cooling with electric heat
models are available with a wide variety of factory-mounted
options and field-installed accessories to make them suitable
for almost every application. All units are self-contained and
assembled on full perimeter base rails with holes in the four
corners for overhead rigging. Every unit is completely piped,
wired, charged and tested at the factory to simplify the field
installation and to provide years of dependable operation. All
models (including those with an economizer) are suitable for
either bottom or horizontal duct connections. Models with
power exhaust are suitable for bottom duct connections only.
For bottom duct, remove the sheet metal panels from the
supply and return air openings through the base of the unit.
For horizontal duct, remove the supply and return air panels
on the rear of the unit.
All non-Scroll compressors include crankcase heaters and all
compressors have internal pressure relief. Every refrigerant
circuit includes a liquid line filter-drier, a discharge line high
pressure switch and a suction line with a freezestat and low
pressure/loss of charge switch.The unit control circuit
includes a 75 VA transformer, a 24-volt circuit breaker and a
relay board with a compressor lockout circuit, a terminal strip
for thermostat wiring, plus an additional set of pin connectors
to simplify the interface of additional field controls. All models
are CSA listed. All models include a 1-year limited warranty
on the complete unit. Compressors and electric heater elements carry a 5-year warranty. Aluminized steel and Stainless
steel tubular heat exchangers carry a 10-year warranty.

DESCRIPTION
Units shall be factory-assembled, single packaged, Electric
Cooling/Gas Heat, Electric Cooling/Optional Electric Heat
and designed for outdoor mounted installation.
The 3 ton, 4 ton and 5 ton units shall have minimum SEER
rating of 14. They shall have built-in field convertible duct
connections for down discharge supply/return or horizontal
discharge supply/return, and be available with factory
installed options or field installed accessories. The units shall
be factory wired, piped, charged with R-22 refrigerant and
factory tested prior to shipment. All unit wiring shall be both
numbered and color coded. All units the cooling performance
shall be rated in accordance with DOE and ARI test procedures. Units shall be CSA listed, classified to ANSI Z21.47,
UL 1995/CSA No. 236 standards.

32

UNIT CABINET
Unit cabinet shall be constructed of a combination of G60 and
G90 galvanized steel, with exterior surfaces coated with a
non-chalking, powdered paint finish, certified at 750 hours
salt spray test per ASTMB117 standards. Indoor blower section shall be insulated with a minimum 1/2” thick insulation,
coated on the airside. Aluminum foil faced insulation shall be
used in the furnace compartment and be fastened with ridged
fasteners to prevent insulation from entering the air stream.
Cabinet panels shall be “large” size, easily removable for servicing and maintenance. Full perimeter base rails shall be
provided to assure reliable transit of equipment, overhead rigging and proper sealing on roof curb applications. Disposable
1" filters shall be furnished and be accessible through a
removable access door, sealed airtight. Units filter track shall
be designed to accommodate either 1" or 2" filters. Fan performance measuring ports shall be provided on the outside of
the cabinet to allow accurate air measurements of evaporator
fan performance without removing panels or creating air bypass of the coils. Condensate pan shall be internally sloped
and conform to ASHRAE 62-89 self-draining standards. Condensate connection shall be a minimum of 3/4” I.D. female
and be a ridged mount connection.
INDOOR (EVAPORATOR) FAN ASSEMBLY
The indoor fan shall be a factory installed direct drive. Job
site selected (B.H.P.) brake horsepower shall not exceed the
motors nameplate horsepower rating, plus the service factor.
Units shall be designed not to operate above service factor.
Fan wheel shall be double-inlet type with forward-curved
blades, dynamically balanced to operate smoothly throughout
the entire range of operation. Airflow design shall be constant
air volume. Bearings shall be sealed and permanently lubricated for longer life and no maintenance.
OUTDOOR (CONDENSER) FAN ASSEMBLY
The outdoor fan shall be of the direct-driven propeller type,
discharge air vertically, have aluminum blades riveted to a
corrosion resistant steel spider bracket and shall be dynamically balanced for smooth operation. The outdoor fan motor
shall be totally enclosed with permanently lubricated bearings, internally protected against overload conditions and
staged independently.
REFRIGERANT COMPONENTS
Compressor:
a.

Shall be internally protected with internal high-pressure relief and over temperature protection.

b.

Shall have internal spring isolation and sound muffling to minimize vibration and noise, and be externally isolated on a dedicated, independent mounting.

Johnson Controls Unitary Products

343615-YTG-B-0308

Coils:
a.

Evaporator and condenser coils shall have aluminum plate fins mechanically bonded to seamless
internally enhanced copper tubes with all joints
brazed. Special Phenolic coating shall be available
as a factory option.

b.

Evaporator and Condenser coils shall be of the
direct expansion, draw-thru, design.

Refrigerant Circuit and Refrigerant Safety Components shall
include:
a.

Independent fixed-orifice or thermally operated
expansion devices.

b.

Filter drier/strainer to eliminate any moisture or foreign matter.

c.

Accessible service gage connections on both suction and liquid lines to charge, evacuate, and measure refrigerant pressure during any necessary
servicing or troubleshooting, without losing charge.

d.

The refrigeration system shall provide at least 15°F
of sub-cooling at design conditions.

UNIT CONTROLS

dant main gas valve. Venter wheel shall be constructed of
stainless steel for corrosion resistance. The heat exchanger
shall be of the tubular type, constructed of T1-40 aluminized
steel for corrosion resistance and allowing minimum mixed
air entering temperature of 25°F. Burners shall be of the
inshot type, constructed of aluminum coated steel and contain air mixture adjustments. All gas piping shall enter the unit
cabinet at a single location through either the side or curb
without any field modifications. Integrated control boards
shall provide timed control of evaporator fan functioning and
burner ignition. Heating section shall be provided with the following minimum protection:
a.

Primary and auxiliary high-temperature limit switches.

b.

Induced draft motor speed sensor.

c.

Flame roll out switch.

d.

Flame proving controls.

e.

If any of the above safety devices trip, a LED (lightemitting diode) indicator shall flash a diagnostic
code that indicates which safety switch has tripped.

ELECTRIC HEATING SECTION

a.

Unit shall be complete with self-contained low-voltage control circuit protected by a resetable circuit
breaker on the 24-volt transformer side.

b.

Unit shall incorporate a lockout circuit which provides reset capability at the space thermostat or
base unit, should any of the following standard
safety devices trip and shut off compressor.

c.

Loss-of-charge/Low-pressure switch.

An electric heating section, with nickel chromium elements,
shall be provided in a range of 5 thru 30 KW, offering two
stages of capacity - 16 KW and above on 208/230 volt heaters
and 20 KW and above on 460 and 575 volt heaters. The heating section shall have a primary limit control(s) and automatic
reset to prevent the heating element system from operating at
an excessive temperature. The heating section assembly
shall slide out of the unit for easy maintenance and service.
Units with Electric Heating shall be wired for a single point
power supply with branch circuit fusing (where required).

d.

High-pressure switch.

UNIT OPERATING CHARACTERISTICS

e.

Freeze-protection thermostat, evaporator coil.

f.

Unit shall incorporate “AUTO RESET” compressor
over temperature, over current protection.

g.

Unit shall operate with conventional thermostat
designs and have a low voltage terminal strip for
easy hook-up.

h.

Unit control board shall have on-board diagnostics
and fault code display.

i.

Standard controls shall include anti-short cycle and
low voltage protection, and permit cooling operation
down to 0°F.

j.

Control board shall monitor each refrigerant safety
switch independently.

k.

Control board shall retain last 5 fault codes in non
volatile memory which will not be lost in the event of
a power loss.

a.

Unit shall be capable of starting and running at 125°F
outdoor temperature, exceeding maximum load criteria of ARI Standard 210/240. The compressor, with
standard controls, shall be capable of operation
down to 0°F outdoor temperature. Unit shall be provided with fan time delay to prevent cold air delivery
before heat exchanger warms up (Gas heat only).

ELECTRICAL REQUIREMENTS
All unit power wiring shall enter unit cabinet at a single factory
provided location and be capable of side or bottom entry, to
minimize roof penetrations and avoid unit field modifications.
Separate side and bottom openings shall be provided for the
control wiring.
STANDARD LIMITED WARRANTIES
•

Compressor 5 Years

•

Heat Exchanger 10 Years

GAS HEATING SECTION (SINGLE OR 2 STAGE)

•

Electric Heat Element 5 Years

Shall be designed with induced draft combustion with post
purge logic, energy saving direct spark ignition, and redun-

•

Other Parts 1 Year

Johnson Controls Unitary Products

33

343615-YTG-B-0308

OPTIONAL OUTDOOR AIR (Shall be made available by
either/or):
•

•

ELECTRONIC ENTHALPY AUTOMATIC ECONOMIZER- Outdoor and return air dampers that are interlocked and positioned by a fully-modulating, spring
return damper actuator. The maximum leakage rate for
the outdoor air intake dampers shall not exceed 2%
when dampers are fully closed and operating against a
pressure differential of 0.5 IWG. A unit-mounted potentiometer shall be provided to adjust the outdoor and return
air damper assembly to take in CFM of outdoor air to
meet the minimum ventilation requirement of the conditioned space during normal operation. During economizer operation, a mixed-air temperature control shall
modulate the outdoor and return air damper assembly to
prevent the supply air temperature from dropping below
55°F. Changeover from compressor to economizer operation shall be provided by an integral electronic enthalpy
control that feeds input into the basic module. The outdoor intake opening shall be covered with a rain hood
that matches the exterior of the unit. Water eliminator/filters shall be provided. Simultaneous economizer/compressor operation is also possible. Dampers shall fully
close on power loss.
MOTORIZED OUTDOOR AIR DAMPERS - Outdoor air
dampers are positioned by a 2-position, spring-return
damper actuator. The maximum leakage rate for the outdoor air intake dampers shall not exceed 2% when
dampers are fully closed and operating against a pressure differential of 0.5 IWG. A unit-mounted potentiometer shall be provided to adjust the outdoor damper
assembly to take in the design CFM of outdoor air to
meet the ventilation requirements of the conditioned
space during normal operation. Whenever the indoor fan
motor is energized, the dampers open up to one of two
pre-selected positions - regardless of the outdoor air
enthalpy. Dampers return to the fully closed position
when the indoor fan motor is de-energized. Dampers
shall fully close on power loss.

OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE
•
•

•

•

34

ROOF CURB - 14"and 8” high, full perimeter curb with
wood nailer (shipped knocked-down).
BAROMETRIC RELIEF DAMPER - Contains a rain
hood, air inlet screen, exhaust damper and mounting
hardware. Used to relieve internal air pressure through
the unit.
PROPANE CONVERSION KIT - Contains new orifices
and gas valve parts to convert from natural to L.P. gas.
One per unit required.
HIGH ALTITUDE - NATURAL GAS - Contains orifices
required for applications between 2000 and 6000 feet
altitude.

•

HIGH ALTITUDE - PROPANE GAS - Contains orifices
required for applications between 2000 and 6000 feet
altitude. Must be used with propane conversion kit.

•

LOW NOX - Required to reduce the emission of nitrogen
oxides below 40 nanograms per joule.

•

GAS PIPING - Contains 1/2” pipe nipples, fittings and
gas cock (including panel assess gaskets) required for
bottom gas supply connection with external shut off.

•

POWER EXHAUST OPTION - To work in conjunction
with economizers.

•

ELECTRIC HEATERS

•

ECONOMIZER/MOTORIZED DAMPER RAIN HOOD Contains all hood panels and the hardware for assembling.

•

MANUAL OUTDOOR AIR DAMPER

•

COIL GUARD KIT - Guard for cooling coil.

•

HAIL GUARD

•

FLUE EXHAUST EXTENSION

OTHER FACTORY INSTALLED OPTIONS
•

POWER EXHAUST OPTION - To work in conjunction
with economizers.

•

STAINLESS STEEL HEAT EXCHANGER

•

STAINLESS STEEL DRAIN PAN

•

BOTTOM DRAIN CONNECTION

•

TECHNICOAT PHENOLIC COATED CONDENSER
AND EVAPORATOR COIL

•

ELECTRONIC SINGLE ENTHALPY ECONOMIZER

•

DIRTY FILTER SWITCH

•

PHASE MONITOR

•

COIL GUARD

•

POWERED GFI CONVENIENCE OUTLET

•

NON-POWERED GFI CONVENIENCE OUTLET

•

BAS CONTROLS (Simplicity® INTELLI-Comfort™,
CPC, JOHNSON, HONEYWELL, NOVAR)

•

BAS READY ECONOMIZER (2-10 V.D.C. ACTUATOR
WITHOUT A CONTROLLER)

•

HINGED FILTER DOOR ACCESS AND TOOLESS
ACCESS PANELS

•

2" PLEATED FILTERS

•

DISCONNECT SWITCH

•

SUPPLY AIR SMOKE DETECTOR

•

RETURN AIR SMOKE DETECTOR

Johnson Controls Unitary Products

343615-YTG-B-0308

Johnson Controls Unitary Products

35

Subject to change without notice. Printed in U.S.A.
Copyright © 2008 by Johnson Controls, Inc. All rights reserved.
Johnson Controls Unitary Products
5005 York Drive
Norman, OK 73069

343615-YTG-B-0308
Supersedes: 343615-YTG-A-0807



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : No
Page Mode                       : UseThumbs
XMP Toolkit                     : 3.1-702
Producer                        : Acrobat Distiller 7.0.5 (Windows)
Creator Tool                    : FrameMaker 8.0
Modify Date                     : 2008:03:14 17:16:56-05:00
Create Date                     : 1999:12:07 14:27:40Z
Metadata Date                   : 2008:03:14 17:16:56-05:00
Format                          : application/pdf
Title                           : Y-TG-Single Package Gas/Elec Units and Single Package AC
Creator                         : amaxwell
Document ID                     : uuid:52e7a455-4c79-4036-bfff-a218db9d5eab
Instance ID                     : uuid:15d44e5a-6ec4-46b7-b083-263e113b9a36
Page Count                      : 36
Page Layout                     : OneColumn
Author                          : amaxwell
Warning                         : [Minor] Ignored duplicate Info dictionary
EXIF Metadata provided by EXIF.tools

Navigation menu