York Z Millennium R410A Technical Guide Y TG 25 40 Ton Millennium, Synthesys Unitary Controller

2015-09-09

: York Z-Millennium-R410A-Technical-Guide york-z-millennium-r410a-technical-guide-812246 york pdf

Open the PDF directly: View PDF PDF.
Page Count: 8

282525-YTG-A-1206
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
ACRONYMS DESCRIPTION AND POINT
LISTING FOR YORK SYNTHESYS™ CV AND
V
AV/VFD CONTROLS.
N2 COMMUNICATION PROTOCOL
TECHNICAL
GUIDE
TECHNICAL
GUIDE
DESCRIPTION
A number of acronyms are used throughout the York
Synthesys™ Application and Installation manual. These
are specific to the Synthesys™ control. Acronyms are
used to refer to input and output hardware points and
software parameters such as timing delays and set
points. The acronyms used in the Synthesys™ manuals
are listed below.
TABLE 1: ACRONYM DESCRIPTIONS
Inputs:
APS - Air Proving Switch (Fan Status)
AQ - Air Quality (CO2 Sensor)
BS - Building Static Pressure
CS1-6 - Compressor Status
DF - Dirty Filter Status
DS - Duct Static Pressure
FS1/2 - Freeze Stat
FZR - Hot Water Coil Freeze Input
G - Thermostat input for Fan
LAR - Low Ambient Resistor
OAT - Outside Air Temperature
OCC - Building Occupied Status
P - Building Purge input
RAT - Return Air Temperature
SAT - Supply Air Temperature
SD - System Shutdown input
SO - Outside Air Enthalpy
SR - Return Air Enthalpy
SSA - Setpoint Adjust
ST - Space Temperature
W1 - First Stage Heating call from thermostat
W2 - Second Stage Heating from Tstat
Y1 - First Stage Cooling from Tstat
T2 - Second Stage Cooling from Tstat
Outputs:
C1-C4 - Cooling Outputs 1 through 4
CF1&2 - Condenser Fan Outputs
EC - Economizer Control Output
EAD - Exhaust Air Damper
EF - Exhaust Fan relay output
Fan - Supply Fan relay output
H1&H2 - Heating Stages 1 and 2 output
HW - Hot Water Valve output
PE - Power Exhaust System output
VC - VFD or IGV output
X - Relay for Alarm Status output
Miscellaneous:
AI - Analog Input
AO - Analog Output
BI - Binary Input same as
BO - Binary Output
CAV - Constant Air Volume
VAV - Variable Air Volume
VFD - Variable Frequency Drive
IGV - Inlet Guide Vane
IAQ - Indoor Air Quality
PI - Proportional-Integral Control
282525-YTG-A-1206
2Unitary Products
TABLE OF CONTENTS
DESCRIPTION
POINTS MAPPING LIST FOR YORK SYNTHESYS- CV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
POINTS MAPPING LIST FOR YORK SYNTHESYS- VAV/VFD. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
282525-YTG-A-1206
Unitary Products 3
Points Mapping List for York Synthesys- CV
The list below provides point, address and long name description of accessible
I/O’s for the N2 communication option on the Synthesys control.
Points Mapping List for York Synthesys- CV (Constant Volume
V
ersion)- Control support for YK-UNT400-2. The points listed
below are available VIA N2 communication only !!
A
NALOG INPUTS (* Denotes OPERATO
R
-DEFINED AI)
Point Point
Type Address Long Name
---- ------- ------------------------
AI 1 Zone Temp
AI 2 Space Temp SP Offset
AI 3 IAQ Sensor
AI 5 Return Air Temp
AI 6 RA Rel Humid
AI 9 Tstat Interface
AI 10 LAR FZR
AI 11 SAT
AI 12 Building Static Pressure
AI 13 Outdoor Air Temp
AI 14 OA Rel Humid
BINARY INPUTS (* Denotes OPERATOR-DEFINED BI)
Point Point
Type Address Long Name
---- ------- ------------------------
BI 1 Compressor 1 Status
BI 2 Compressor 2 Status
BI 3 Compressor 3 Status
BI 4 Compressor 4 Status
BI 6 G
BI 7 BI Occupied
BI 8 FreezeStat 1
BI 9 FreezeStat 2
BI 10 Dirty Filter Switch
BI 11 Air Proving Switch
BI 13 BI Shutdown
BI 14 BI Purge
A
NALOG OUTPUTS (* Denotes OPERATO
R
-DEFINED AO)
Point Point
Type Address Long Name
---- ------- ------------------------
AO 1 Econ Damper
AO 2 Exhaust Damper
AO 4 Hot Water Valve
BINARY OUTPUTS (* Denotes OPERATOR-DEFINED BO)
Point Point
282525-YTG-A-1206
4Unitary Products
Type Address Long Name
---- ------- ------------------------
BO 1 Cool 1
BO 2 Cool 2
BO 3 Cool 3
BO 4 Cool 4
BO 5 Condensor Fan 1
BO 6 Condensor Fan 2
BO 8 Heat 1
BO 9 Heat 2
BO 11 SUPPLY FAN
BO 12 EXHAUST FAN
BO 13 X
PARAMETERS (* Denotes MONITOR ONLY Parameters)
Point Point
Type Address Long Name Short Name Value
----- ------- ------------------------ ---------- -------
Sensor Enables
BD 70 Space Sensor Enable SpcSnsEn 0
Fan
BD 80 Fan Overrun FanOver 0
BD 79 FanOnSensorMode FanOnSen 1
UnoccOvrdTime
ADF 92 Unoccupied O
v
rd Time UnOvrdTm 60
Limits
ADF 65 Cooling Lockout On OAT ClgLckOA 45.0
ADF 66 Heating Lockout On OAT HtgLckOA 75.0
ADF 74 Comp 1 Trip Limit Cmp1
T
rip 45.0
ADF 75 Comp 2 Trip Limit Cmp2Trip 50.0
ADF 76 Comp 3 Trip Limit Cmp3Trip 50.0
ADF 77 Comp 4 Trip Limit Cmp4Trip 50.0
Economizer
ADF 78 OA Enth Number OAEntH 27.0
ADF 67 Econ First Stage Setpt 1stStgSP 55.0
ADF 68 Econ Second Stage Setpt 2ndStgSP 50.0
BD 71 EconLdgToCntrlSAT EcnLdg 1
ADF 81 MinPos MinPos 20.0
ADF 71 MaxEconPosForDemandVent MxEcnDV 50.0
ADF 98 Econ Ldg Of Heating SP EcnLdgHt 150.0
Power Exhaust
ADF 207 Maximum EF Off Time MaxEFOff 40.0
ADF 79 EF Turn On Setpoint EFOnSP 60.0
ADF 80 EF Turn Off Setpoint EFOffSP 20.0
ADF 201 Maximum EF On Time MaxEFOn 6.0
ADF 72 Bldg Pressure Setpoint BldgSP 0.1
ADF 90 EAD Turn On SP EADOnSP 80.0
ADF 91 EAD Turn Off SP EADOffSp 20.0
282525-YTG-A-1206
Unitary Products 5
Points Mapping List for York Synthesys- VAV/VFD
Setpoints
ADF 82 Occ Cooling Setpoint OccClgSP 72.0
ADF 83 Unocc Cooling Setpoint UnClgSP 85.0
ADF 84 Occ Heating Setpoint OccHtgSP 68.0
ADF 85 Unocc Heating Setpoint UnHtgSP 60.0
ADF 70 Space Setpoint Offset SpcSPOff 3.0
ADF 86 Demand Ventilation Setpt DmdVntSP 1000
ADF 87 IAQ Sensor Range IAQSnsRg 5000
ADF 88 Hydronic 1st Stg SP Hyd1stSP 130.0
ADF 89 Hydronic 2nd Stg SP Hyd2ndSP 145.0
ADF 93 SAT Alarm SP for Clg SATAmClg 100
ADF 94 SAT Alarm SP for Htg SATAmHtg 0
M
odes
BD 67 SAT Cntrl For Cooling SATClg 1
BD 84 Dirty Filter Sw Option DrtyFltr 0
BD 83 Alarm Input AlarmInp 0
BD 73 Cooling Mode Enable ClgMdEnb 1
BD 74 Heating Mode Enable HtgMdEnb 1
Sensor Fault Enable
BD 75 OAH Sensor Enable OAHSnsEn 0
BD 76 RAH Sensor Enable RAHSnsEn 0
BD 77 RAT Sensor Enable RATSnsEn 0
BD 87 BldgStatic Sensor Enable BldgSnsE 0
Comfort Ventilation
ADF 95 CVM Max Economizer Posn CVMMaxDp 80
BD 82 ComfortVentilationMode CVMode 0
ADF 96 CVM SAT Band Hi Setpt CVMHiSP 80.0
ADF 97 CVM SAT Band Low Setpt CVMLoSP 70.0
Points Mapping List for York Synthesys- VAV/VFD ( Variable
volume version)- Control support for YK-UNT401-2 The points
listed are available VIA N2 communication only !!
A
NALOG INPUTS (* Denotes OPERATO
R
-DEFINED AI)
Point Point
Type Address Long Name
---- ------- ------------------------
AI 1 Zone Temp
AI 2 Space Temp SP Offset
AI 3 IAQ Sensor
AI 4 Duct Static Pressure
AI 5 Return Air Temp
AI 6 RA Rel Humid
AI 9 Tstat Interface
AI 10 LAR FZR
AI 11 SAT
AI 12 Building Static Pressure
AI 13 Outdoor Air Temp
AI 14 OA Rel Humid
282525-YTG-A-1206
6Unitary Products
BINARY INPUTS (* Denotes OPERATOR-DEFINED BI)
Point Point
Type Address Long Name
---- ------- ------------------------
BI 1 Compressor 1 Status
BI 2 Compressor 2 Status
BI 3 Compressor 3 Status
BI 4 Compressor 4 Status
BI 6 G
BI 7 BI Occupied
BI 8 FreezeStat 1
BI 9 FreezeStat 2
BI 10 Dirty Filter Switch
BI 11 Air Proving Switch
BI 13 BI Shutdown
BI 14 BI Purge
A
NALOG OUTPUTS (* Denotes OPERATOR-DEFINED AO)
Point Point
Type Address Long Name
---- ------- ------------------------
AO 1 Econ Damper
AO 2 Exhaust Damper
AO 3 VFD IGV Command
AO 4 Hot Water Valve
BINARY OUTPUTS (* Denotes OPERATOR-DEFINED BO)
Point Point
Type Address Long Name
---- ------- ------------------------
BO 1 Cool 1
BO 2 Cool 2
BO 3 Cool 3
BO 4 Cool 4
BO 5 Condensor Fan 1
BO 6 Condensor Fan 2
BO 8 Heat 1
BO 9 Heat 2
BO 11 SUPPLY FAN
BO 12 EXHAUST FAN
BO 13 X
PARAMETERS (* Denotes MONITOR ONLY Parameters)
Point Point
Type Address Long Name Short Name Value
----- ------- ------------------------ ---------- -------
Sensor Enables
BD 70 Space Sensor Enable SpcSnsEn 0
282525-YTG-A-1206
Unitary Products 7
Fan
BD 80 Fan Overrun FanOver 0
UnoccOvrdTime
ADF 92 Unoccupied Ovrd Time UnOvrdTm 60
Limits
ADF 65 Cooling Lockout On OAT ClgLckOA 45.0
ADF 66 Heating Lockout On OAT HtgLckOA 75.0
ADF 74 Comp 1 Trip Limit Cmp1Trip 45.0
ADF 75 Comp 2 Trip Limit Cmp2Trip 50.0
ADF 76 Comp 3 Trip Limit
mp3Trip 50.0
ADF 77 Comp 4 Trip Limit Cmp4Trip 50.0
Economizer
ADF 78 OA Enth Number OAEntH 27.0
BD 71 EconLdgToCntrlSAT EcnLdg 1
ADF 81 MinPos MinPos 20.0
ADF 71 MaxEconPosForDemandVent MxEcnDV 50.0
ADF 98 Econ Ldg Of Heating SP EcnLdgHt 150.0
Power Exhaust
ADF 207 Maximum EF Off Time MaxEFOff 40.0
ADF 79 EF Turn On Setpoint EFOnSP 60.0
ADF 80 EF Turn Off Setpoint EFOffSP 20.0
ADF 201 Maximum EF On Time MaxEFOn 6.0
ADF 72 Bldg Pressure Setpoint BldgSP 0.1
ADF 90 EAD Turn On SP EADOnSP 80.0
ADF 91 EAD Turn Off SP EADOffSp 20.0
Setpoints
ADF 82 Occ Cooling Setpoint OccClgSP 72.0
ADF 83 Unocc Cooling Setpoint UnClgSP 85.0
ADF 84 Occ Heating Setpoint OccHtgSP 68.0
ADF 85 Unocc Heating Setpoint UnHtgSP 60.0
ADF 70 Space Setpoint Offset SpcSPOff 3.0
ADF 86 Demand Ventilation Setpt DmdVntSP 1000
ADF 87 IAQ Sensor Range IAQSnsRg 5000
ADF 88 Hydronic 1st Stg SP Hyd1stSP 130.0
ADF 89 Hydronic 2nd Stg SP Hyd2ndSP 145.0
ADF 93 SAT Alarm SP f
o
r Clg SATAmClg 100
ADF 94 SAT Alarm SP for Htg SATAmHtg 0
M
odes
BD 67 SAT Cntrl For Cooling SATClg 1
BD 84 Dirty Filter Sw Option DrtyFltr 0
BD 83 Alarm Input AlarmInp 0
BD 73 Cooling Mode Enable ClgMdEnb 1
BD 74 Heating Mode Enable HtgMdEnb 1
Sensor Fault Enable
BD 75 OAH Sensor Enable OAHSnsEn 0
BD 76 RAH Sensor Enable RAHSnsEn 0
BD 77 RAT Sensor Enable RATSnsEn 0
BD 87 BldgStatic Sensor Enable BldgSnsE 0
Subject to change without notice. Printed in U.S.A. 282525-YTG-A-1206
Copyright © by Unitary Products 2006. All rights reserved. Supersedes: 036-21498-001-A-0203
Unitary 5005 Norman
Products York OK
Group Drive 73069
For additional detailed information on the “Synthesys” control system
please refer to the Millennium/Synthesys Technical application and
programming guide. PN # 036-18201-000.
V
AV
ADF 110 Max MWU Time MxMWTm 120
ADF 100 VAV Setpt for SAT Reset VAVReset 72.0
ADF 101 VAV Low SAT
S
P for Clg VAVLowSP 55.0
ADF 102 VAV High SAT SP for Clg VAVHiSP 60.0
ADF 103 MWU RAT Setpoint MWRATSP 70.0
ADF 104 Duct Static High Limit DctHiLm 4.5
BD 110 NW MWU Command TBD 0
BD 111 Morning Warm Up MWU 0
ADF 105 Duct Static Prop Band DctPB -10.0
ADF 106 Duct Static Integ Time DctInt 50.0
ADF 107 Duct Static Pressure SP DctSP 1.5
BD 112 VAV Operation with Tstat VAVTstat 0
BD 113 VAV Occupied Heatin
g
VAVOccHt 0