SmartLine Technical Information STR800 SmartLine Remote Diaphragm Seals Specification 34-ST-03-88, October 2020 . Introduction . Part of the SmartLine family of products, the STR800 is a
STR82D-21CC1C0-AFCAA21BS-A-BHS-11C-B-11A0-F1,F5 | Honeywell | STR800 (DP, GP & AP) Remote Seals
SmartLine Technical Information STR800 SmartLine Remote Diaphragm Seals Specification 34-ST-03-88, October 2020 Introduction Part of the SmartLine® family of products, the STR800 is a series of high performance pressure transmitters hydraulically matched and optimized with a complete set of remote diaphragm seals. Utilizing the same high performance sensor technology of the ST 800 product line Honeywell has optimized the mechanical and hydraulic designs in order to minimize the typical effects of temperature on remote seal systems. The SmartLine family is also fully tested and compliant with Experion® PKS providing the highest level of compatibility assurance and integration capabilities. SmartLine easily meets the most demanding application needs for pressure measurement applications. Best in Class Features: · Accuracies of up to 0.0375% of span · Automatic static pressure & temperature compensation · Rangeability up to 100:1 · Multiple local display capabilities · External zero, span, & configuration capability · Polarity insensitive electrical connections · Comprehensive on-board diagnostic capabilities · Integral Dual Seal design for highest safety based on ANSI/NFPA 70-202 and ANSI/ISA 12.27.0 · World class overpressure protection · Full compliance to SIL 2/3 requirements. · Modular design characteristics · Available with additional 15-year warranty Typical Diaphragm Seal applications · High Process Temperatures · Viscous or Suspended Solids · Highly Corrosive Process Materials · Sanitary Applications · Applications with Hydrogen Permeation Possibilities · Level Applications with Maintenance Intensive Wet Legs · Applications requiring remote Transmitter Mounting · Tank Applications with Density or Interface Measurements Figure 1 STR800 Remote Diaphragm Seal Unit Communications/Output Options: · Honeywell Digitally Enhanced (DE) · HART ® (version 7.0) · FOUNDATIONTM Fieldbus All transmitters are available with the above listed communications protocols. Span & Range Limits: Model URL "H2O (mbar) STR82D 400 (1000) Model psid (bar) STR83D 100 (7.0) Model psig (bar) STR84G 500 (35.0) STR87G 3000 (210) Model psia (bara) STR84A 500 (35) LRL "H2O (mbar) -400 (-1000) psid (bar) -100 (-7.0) psig (bar) -14.7 (-1.0) -14.7 (-1.0) psig (bara) 0 (0) Min Span "H2O (mbar) 4.0 (10) psid (bar) 1 (0.07) psig (bar) 5 (0.35) 30 (2.1) psig (bara) 5 (0.35) 2 STR800 Smart Pressure Transmitter Description The SmartLine family of gauge pressure, differential pressure, and absolute pressure transmitters is designed around a high performance piezo-resistive sensor. This one sensor actually integrates multiple sensors linking process pressure measurement with on-board static pressure (DP Models) and temperature compensation measurements resulting in the best total performance available. This level of performance allows the ST 800 to replace virtually any competitive transmitter available today. Unique Indication/Display Options The ST 800 modular design accommodates a basic alphanumeric LCD display or a unique advanced graphics LCD display with many unparalleled features. Basic Alphanumeric LCD Display Features · Modular (may be added or removed in the field) · 0, 90,180, & 270 degree position adjustments · Configurable (HART only) and standard (Pa, KPa, MPa, KGcm2, Torr, ATM, inH2O, mH2O, bar, mbar, inH2O, inHG, FTH2O, mmH2O, mm HG, & psi) measurement units · 2 Lines 16 Characters (4.13H x 1.83W mm) · Square root output indication () Advanced Graphics LCD Display Features · Modular (may be added or removed in the field) · 0, 90, 180, & 270 degree position adjustments · Standard and custom measurement units available. · Up to eight display screens with 3 formats are possible · (Large PV with Bar Graph or PV with Trend Graph) · Configurable screen rotation timing · Display Square Root capabilities may be set separately from the 4-20mA dc output signal · Unique "Health Watch" indication provides instant visibility of diagnostics · Multiple language capability. (EN, DE, FR, IT, ES, RU, TR, CN, JP) Diagnostics SmartLine transmitters all offer digitally accessible diagnostics which aid in providing advanced warning of possible failure events minimizing unplanned shutdowns, providing lower overall operational costs Configuration Tools Integral Three Button Configuration Option Suitable for all electrical and environmental requirements, SmartLine offer the ability to configure the transmitter and display via three externally accessible buttons when either display option is selected. Zero/span capabilities are also optionally available via these buttons with or without selection of a display option. Hand Held Configuration SmartLine transmitters feature two-way communication and configuration capability between the operator and the transmitter. All Honeywell transmitters are designed and tested for compliance with the offered communication protocols and are designed to operate with any Standards compliant handheld configuration device. Personal Computer Configuration Honeywell's SCT 3000 Configuration Toolkit provides an easy way to configure Digitally Enhanced (DE) instruments using a personal computer as the configuration interface. Field Device Manager (FDM) Software and FDM Express are also available for managing HART & Fieldbus device configurations. System Integration o SmartLine communications protocols all meet the most current published standards for HART/DE/Fieldbus. o Integration with Honeywell's Experion PKS offers the following unique advantages. o Transmitter messaging o Maintenance mode indication o Tamper reporting o FDM Plant Area Views with Health summaries o All ST 800 units are Experion tested to provide the highest level of compatibility assurance Modular Design To help contain maintenance & inventory costs, all STR800 transmitters are modular in design supporting the user's ability to replace or add indicators, terminal connections or electronic modules without affecting overall performance or approval body certifications Modular Features o Exchange/replace electronics/comms modules* o Add or remove integral indicators* o Add or remove lightning protection (terminal connection)* * Field replaceable in all electrical environments (including IS) except flameproof without violating agency approvals. With no performance effects, Honeywell's unique modularity results in lower inventory needs and lower overall operating costs. STR800 Smart Pressure Transmitter 3 Performance Specifications Reference Accuracy (conformance to +/-3 Sigma) Model STR82D STR83D STR84G STR87G STR84A URL LRL Min Span 400 in H2O (1000 mbar) 100 psid (7.0 bar) 500 psi (35 bar) 3000 psi (210 bar) 500 psia (35 bara) -400 in H2O (-1000 mbar) -100 psi (-7.0 bar) -14.7 (-1.0 bar) -14.7 psi (-1.0 bar) 0 psia (0 bara) 4 in H2O (10 mbar) 1 in psi (0.07 bar) 5 psi (0.35 bar) 30 psi (2.1 bar) 5 psia (0.35 bara) Maximum Turndown Ratio 100:1 100:1 100:1 100:1 100:1 Reference Accuracy1,2 (% Span) 0.0375 0.0375 0.0375 0.0375 0.0375 Zero and span may be set anywhere within the listed (URL/LRL) range limits Accuracy at Specified Span, Temperature and Static Pressure: (conformance to +/-3 Sigma) Standard Accuracy Accuracy1,2 (% of Span) Model STR82D STR83D STR84G STR87G STR84A URL 400 in H2O (1000mbar) 100 psid (7.0 bar) 500 psi (35 bar) 3000 psi (210 bar) 500 psia (35 bara) Reference A Turndown C B (see URL units) 8:1 3.33:1 25:1 10:1 25:1 0.005 0.0325 50 (125) 30 (2.1) 20 (1.4) 300 (2.1) 20 (1.4) Turn Down Effect Combined Zero & Span Temperature Effect3 (% Span/ 28oC (50oF)) F D E (see URL units) 0.175 0.025 1.000 0.280 200 (500) 30 (2.1) Temp Effect Total Performance (% of Span): Total Performance = +/- ( Accuracy)2 + (Temp Effect)2 Total Performance Examples: (standard accuracy, 5:1 Turndown, up to 50 oF shift) STR82D @ 80"H2O: 2.68% of span STR83D @ 20 psid: 0.45% of span Typical Calibration Frequency: Calibration verification is recommended every four (4) years Notes: 1.Terminal Based Accuracy Includes combined effects of linearity, hysteresis, and repeatability. Analog output adds 0.005% of span. 2. For zero based spans and reference conditions of 25oC (77oF). 0 psi static pressure for DP, >= 0 psia for GP, 10 to 55% R.H, and 316 Stainless Steel barrier diaphragms 3. Specification applies to transmitter with 2 balanced remote seals. Apply a 1.5 factor for temperature effect for capillary lengths greater than 10 feet. 4 STR800 Smart Pressure Transmitter Operating Conditions All Models Parameter Reference Condition (at zero static) Rated Condition Operative Limits Transportation and Storage Ambient Temperature1 °C °F °C 25±1 77±2 - °F °C °F °C °F - - - -55 to 90 -67 to 194 Humidity %RH 10 to 55 0 to 100 0 to 100 0 to 100 Vacuum Region, Minimum Pressure mmHg absolute Atmospheric (See Figure 4 for vacuum limitation) Supply Voltage, Current, and Load Resistance 10.8 to 42.4 Vdc at terminals (IS versions limited to 30 Vdc) 0 to 1,440 ohms (as shown in Figure 2) Maximum Allowable Working Pressure (MAWP)4 (ST 800 products are rated to Maximum Allowable Working Pressure. MAWP depends on Approval Agency and transmitter materials of construction.) MAWP is minimum of Body Rating or Seal Rating (See Model Selection Guide for Seal Body STR82D MAWP 2,500 psig (172 bar) Bolted Process Heads STR83D 2,500 psig (172 bar) Bolted Process Heads STR82D 1,450 psig (100 bar) All Welded Process STR83D 1,450 psig (100 bar) All Welded Process STR84G 500 psig (35 bar) STR87G 3,000 psig (207 bar) STR84A 500 psia (35 bara) 1 Ambient Temperature Limit is a function of Process Interface Temperature and fill fluid. (See Figure 3 & Figure 4) LCD Display operating temperature -20°C to +70°C . Storage temperature -30°C to 80°C 4 Consult factory for MAWP of ST 800 transmitters with CRN approval. Figure 2 - Supply voltage and loop resistance STR800 Smart Pressure Transmitter 5 Maximum Ambient Temperature (°F) 200 185 180 165 160 140 140 120 100 80 60 40 20 0 200 350 450 Process Interface Temperature (°F) Figure 3 - Ambient temperature limits Figure 4 - STR800 Remote Seals operable limits for pressure vs. temperature 6 STR800 Smart Pressure Transmitter Performance Under Rated Conditions All Models Parameter Description Analog Output Two-wire, 4 to 20 mA (HART & DE Transmitters only) Digital Communications: Honeywell DE, HART 7 protocol or FOUNDATION Fieldbus ITK 6.0.1 compliant All transmitters, irrespective of protocol have polarity insensitive connection. HART & DE Output Failure Modes (NAMUR for DE Units requires selecting display and configuration buttons or factory configuration) Compliance: Normal Limits: Failure Mode: Honeywell Standard: 3.8 20.8 mA 3.6 mA and 21.0 mA NAMUR NE 43 3.8 20.5 mA 3.6 mA and 21.0 mA Supply Voltage Effect 0.005% span per volt. Transmitter Turn on Time (includes power up & test algorithms) HART or DE: 2.5 sec. Foundation Fieldbus: Host dependant Damping Time Constant HART: Adjustable from 0 to 32 seconds in 0.1 increments. Default: 0.50 seconds DE: Discrete values 0, .16, .32, .48, 1, 2, 4, 8, 16, 32 seconds. Default: 0.48 seconds Electromagnetic Compatibility IEC 61326-3-1 Lightning Protection Option Leakage Current: 10uA max @ 42.4VDC 93C Impulse rating: 8/20uS 5000A (>10 strikes) 10/1000uS 200A (> 300 strikes) 10000A (1 strike min.) Materials Specifications (see Model Selection Guide for availability/restrictions with various models) Parameter Description Process Interface See Model Selection Guide for Material Options for desired seal type. Seal Barrier Diaphragm 316L Stainless Steel, Monel®, Hastelloy® C, Tantalum Seal Gasket Materials Klinger C-4401 (non-asbestos), Grafoil®, Teflon®, Gylon 3510® Mounting Bracket Carbon Steel (Zinc-Chromate plated) or 304 Stainless Steel or 316 Stainless Steel Fill Fluid (Meter Body) Silicone 200 CTFE (Chlorotrifluoroethylene) Silicone 704 NEOBEE M-20® S.G. @ 25°C = 0.94 S.G. @ 25°C = 1.89 S.G. @ 25°C = 1.07 S.G. @ 25°C = 0.93 Fill Fluid (Secondary) Silicone Oil 200 CTFE (Chlorotrifluoroethylene) Silicone Oil 704 Syltherm 800® NEOBEE M-20® S.G. @ 25°C = 0.94 S.G. @ 25°C = 1.89 S.G. @ 25°C = 1.07 S.G. @ 25°C = 0.90 S.G. @ 25°C = 0.93 Electronic Housing Pure Polyester Powder Coated Low Copper (<0.4%)-Aluminum. Meets NEMA 4X, IP66, & P67. All stainless steel housing is optional. Capillary Tubing Material: Armored Stainless Steel or PVC Coated Armored Stainless Steel. Length: 5, 10, 15, 20, 25, and 35 feet (1.5, 3, 4.6, 6.1, 7.5, and 10.7 meters). A 2 inch (51 millimeter) S.S. close-coupled nipple is also available. See Model Selection Guide. Refer to Note: The minimum span is the higher of the higher of the value from the table above or the value defined under the Performance Conditions for the range transmitter. Figure 5 for guide to maximum capillary length vs. diaphragm diameter. Wiring Accepts up to 16 AWG (1.5 mm diameter) Mounting See Figure 6 Dimensions Transmitter: See Figure 7 and Figure 8. Seal: See Figure 9 through Figure 17 Net Weight Transmitter: 8.3 pounds (3.8 Kg). With Aluminum Housing. Total weight is dependent on seal NOTE: Pressure transmitters that are part of safety equipment for the protection of piping (systems) or vessel(s) from exceeding allowable pressure limits, (equipment with safety functions in accordance with Pressure Equipment Directive 97/23/EC article 1, 2.1.3), require separate examination. STR800 Smart Pressure Transmitter 7 Minimum recommended span for STR82D and STR83D Transmitter with two Remote Seals Diaphragm Capillary Length (Feet) Size (Inches) 5 10 15 20 25 35 2.4 7.2 psi 2.9 3.6 psi 4.5 psi 5.4 psi 6.3 psi 3.5 0.6 psi 0.7 psi 0.9 psi 1.0 psi 1.2 psi 1.4 psi 4.1 0.4 psi 0.5 psi 0.6 psi 0.8 psi 0.9 psi 1.1 psi Maximum Capillary Length (Feet) 5 20 35 35 Minimum recommended span for STR82D and STR83D Transmitter with one Remote Seal Diaphragm Direct Capillary Length (Feet) Size (Inches) Mount 5 10 15 20 25 35 2.4 20 psi 30 psi 2.9 10 psi 15 psi 20 psi 25 psi 30 psi 3.5 1.8 psi 2.9 psi 3.6 psi 4.3 psi 5.0 psi 5.8 psi 7.2 psi 4.1 1.4 psi 2.2 psi 2.9 psi 3.6 psi 4.3 psi 5.0 psi 5.8 psi Maximum Capillary Length (Feet) 5 20 35 35 Minimum recommended span for STR84G, STR84A and STR87G Transmitter Diaphragm Direct Size (Inches) Mount 5 Capillary Length (Feet) 10 15 20 25 Maximum Capillary 35 Length (Feet) 1.9 25 psi 30 psi 40 psi 50 psi 15 2.4 10 psi 15 psi 20 psi 25 psi 30 psi 35 psi 50 psi 35 2.9 8 psi 9 psi 10 psi 11 psi 12 psi 13 psi 15 psi 35 3.5 5 psi 5 psi 5 psi 5 psi 5 psi 6 psi 8 psi 35 4.1 5 psi 5 psi 5 psi 5 psi 5 psi 6 psi 8 psi 35 Note: The minimum span is the higher of the higher of the value from the table above or the value defined under the Performance Conditions for the range transmitter. Figure 5 Typical Maximum capillary length and diaphragm size chart Figure 6 - STR800 transmitter with remote diaphragm seals shown mounted on a tank 8 Reference Dimensions Horizontal Mounting STR800 Smart Pressure Transmitter STR800 Smart Pressure Transmitter 9 Reference Dimensions Horizontal Mounting (cont'd) Figure 7 -- Approximate horizontal mounting dimensions for Remote Seal Transmitter Reference Dimensions Vertical Mounting 10 Reference Dimensions Vertical Mounting (cont'd) STR800 Smart Pressure Transmitter Figure 8 -- Approximate vertical mounting dimensions for Remote Seal Transmitter STR800 Smart Pressure Transmitter Reference Dimensions (cont'd) Flush Flanged Seal Dimensions 11 Figure A Figure B Figure C Figure D Figure 9-- Seal Dimensions (Flush Flanged) 12 Reference Dimensions (cont'd) Flush Flanged Seal with Lower STR800 Smart Pressure Transmitter Flush Flanged Seal with Lower Flush Flanged Seal with Lower Nte: 0.90 dimension is 0.70 for 4.1" Dia Diaphragm Figure 10 -- Seal Dimension (Flush Flanged) STR800 Smart Pressure Transmitter 13 Reference Dimensions (cont'd) Flanged Seal with Extended Diaphragm Pancake Seal Figure 11 -- Seal Dimensions (Extended Diaphragms) Figure 12-- Seal Dimensions (Pancake) Chemical Tee "Taylor Wedge" Seal Figure 13-- Seal Dimensions (Chemical TEE "Taylor Wedge" Seals 14 Seal with Threaded Process Connection STR800 Smart Pressure Transmitter Figure 14-- Seal Dimensions (Threaded Process Connection Seals) Sanitary Seal Figure 15- Seal Dimensions (Sanitary Seals) STR800 Smart Pressure Transmitter 15 Saddle Seal Figure 16 -- Seal Dimensions (3" Saddle Seal) Calibration Ring Figure 17-- Seal Dimensions (4" Saddle Seal) Figure 18-- Calibration Ring 16 Communications Protocols & Diagnostics HART Protocol Version: HART 7 Power Supply Voltage: 10.8 to 42.4Vdc at terminals Load: Maximum 1440 ohms See Figure 2. Minimum Load: 0 ohms. (For handheld communications a minimum load of 250 ohms is required) Foundation Fieldbus (FF) Power Supply Requirements Voltage: 9.0 to 32.0Vdc at terminals Steady State Current: 17.6mAdc Software Download Current: 27.4mAdc Available Function Blocks Block Type Qty Execution Time Resource 1 n/a Transducer 1 n/a Diagnostic 1 Analog Input 1* n/a 30 ms PID w/Autotune 1 Integrator 1 45 ms 30 ms Signal Char (SC) 1 LCD Display 1 30 ms n/a Flow Block 1 Input Selector 1 30 ms 30 ms Arithmetic 1 30 ms * AI block may have two (2) additional instantiations. All available function blocks adhere to FOUNDATION Fieldbus standards. PID blocks support ideal & robust PID algorithms with full implementation of Auto-tuning. Link Active Scheduler Transmitters can perform as a backup Link Active Scheduler and take over when the host is disconnected. Acting as a LAS, the device ensures scheduled data transfers typically used for the regular, cyclic transfer of control loop data between devices on the Fieldbus. Number of Devices/Segment Entity IS model: 6 devices/segment Schedule Entries 18 maximum schedule entries Number of VCR's: 24 max Compliance Testing: Tested according to ITK 6.0.1 STR800 Smart Pressure Transmitter Software Download Utilizes Class-3 of the Common Software Download procedure as per FF-883 which allows the field devices of any manufacturer to receive software upgrades from any host. Honeywell Digitally Enhanced (DE) DE is a Honeywell proprietary protocol which provides digital communications between Honeywell DE enabled field devices and Hosts. Power Supply Voltage: 10.8 to 42.4Vdc at terminals Load: Maximum 1440 ohms See Figure 2. Standard Diagnostics ST 800 top level diagnostics are reported as either critical or non-critical and readable via the DD/DTM tools or integral display as shown below. Refer to ST 800 diagnostics tech note for additional level diagnostics. Other Certification Options Materials o NACE MRO175, MRO103, ISO15156 Hazardous Areal Certification: MSG CODE AGENCY TYPE OF PROTECTION COMM. ELECTRICAL AMBIENT TEMP OPTION PARAMETERS (Ta) Explosionproof: Class I, Division 1, Groups A, B, C, D; Dust Ignition Proof: Class II, III, Division 1, Groups E, F, G; All T6..T5 Class l, Zone 0/1, AEx db IIC T6..T5 Ga/Gb Class ll, Zone 21, AEx tb IIIC T95o Db Note 1 T5: -50 ºC to 85ºC T6: -50 ºC to 65ºC Intrinsically Safe: Class I, II, III, Division 1, Groups A, B, C, D, 4-20 mA / DE/ HART Note 2a -50 ºC to 70ºC E, F, G: T4 A FM Class l, Zone 0, AEx ia IIC T4 Ga ApprovalsTM FISCO Field Device (Only for FF Option) USA Ex ia IIC T4 Ga; Ex ic IIC T4 Gc Foundation Fieldbus Note 2b -50 ºC to 70ºC Nonincendive: Class I, Division 2, Groups A, B, C, D locations, T4 Class l, Zone 2, AEx nA IIC T4 Gc 4-20 mA / DE/ HART/ Foundation Fieldbus Note 1 -50 ºC to 85ºC Enclosure: Type 4X/ IP66/ IP67 All All - STANDARDS: FM Class 3600:2011; FM Class 3610: 2010; FM Class 3611: 2004; FM Class 3615: 2006; FM Class 3616: 2011; FM Class 3810: 2005; ANSI/ISA 60079-0: 2013; ANSI/UL 60079-1: 2015; ANSI/UL 60079-11: 2014; ANSI/ISA 60079-15: 2012; ANSI/UL 60079-26: 2017; ANSI/UL 60079-31: 2015; ANSI/NEMA 250: 2003; ANSI/ IEC 60529: 2004 Explosion Proof: Class I, Division 1, Groups A, B, C, D; Class II, Division 1, Groups E, F, G; Class III, Division 1, T6..T5 Class I Zone 1 AEx db IIC T6..T5 Ga/Gb Ex db IIC T6..T5 Ga/Gb Zone 22 AEx tb IIIC T95o Db Ex tb IIIC T95o Db All Note 1 T5: -50oC TO 85oC T6: -50oC TO 65oC Intrinsically Safe: Class I, II, III, Division 1, Groups A, B, C, D; Class II, Division 1, Groups E, F, G; 4-20 mA / DE/ HART Note 2 Canadian Class III, Division 1, T4 Standards Class I Zone 0, AEx ia IIC T4 Ga B Association (CSA) USA and Canada Class I Zone 2, AEx ic IIC T4 Gc Ex ia IIC T4 Ga Ex ic IIC T4 Gc FISCO Field Device (Only for FF Option) Foundation Fieldbus Note 2 Ex ia IIC T4 Ga; Ex ic IIC T4 Gc -50oC TO 70oC -50oC TO 70oC Nonincendive: Class I, Division 2, Groups A, B, C, D; Class II, Division 2, Groups F, G; Class III, Division 2, T4 Class I Zone 2 AEx nA IIC T4 Gc Ex nA IIC T4 Gc 4-20 mA / DE/ HART/ Foundation Fieldbus Note 1 -50oC to 85oC Enclosure: Type 4X/ IP66/ IP67 All All - STANDARDS: CSA C22.2 No. 0-10; CSA C22.2 No. 94-M91; CSA C22.2 No. 25-1966; CSA C22.2 MSG CODE C D AGENCY ATEX IECEx World TYPE OF PROTECTION COMM. ELECTRICAL AMBIENT TEMP OPTION PARAMETERS (Ta) No. 30-M1986; CSA C22.2 No. 142-M1987; CSA C22.2 No. 157-92; CSA C22.2 No. 213-M1987; CSA-C22.2 No. 60529:05; CSA-C22.2 No. 60079-0:11; CSA-C22.2 No. 60079-1:11; CSA-C22.2 No. 60079-11:11; CSA-C22.2 No. 60079-15:12; CSA-C22.2 No. 60079-31:12; ISA 12.12.012010; ISA 60079-0: 2009; ISA 60079-11: 2011; ISA 60079-15: 2009; ISA 60079-26: 2008; ISA60079-27:2007 (12.02.04)-2006 (R2011); UL 913 Ed. 6; UL 916:1998; ANSI/ISA-12.27.01-2011 Flameproof: SIRA 12ATEX2233X II 1/2 G Ex db IIC T6..T5 Ga/Gb II 2 D Ex tb IIIC T95oC...T120oC Db All Note 1 T5: -50oC TO 85oC T6: -50oC TO 65oC Intrinsically Safe: SIRA 12ATEX2233X II 1 G Ex ia IIC T4 Ga FISCO Field Device (Only for FF Option) II 1 G Ex ia IIC T4 Ga 4-20 mA / DE/ HART Foundation Fieldbus Note 2 Note 2 -50oC TO 70oC -50oC TO 70oC Zone 2, Increase Safety: SIRA 12ATEX4234X II 3 G Ex ec IIC T4 Gc 4-20 mA / DE/ HART/ Note 1 -50oC TO 85oC Zone 2, Intrinsically Safe: SIRA 12ATEX4234X II 3 G Ex ic IIC T4 Gc FISCO Field Device (Only for FF Option) II 3 G Ex ic IIC T4 Gc 4-20 mA / DE/ HART/ Foundation Fieldbus Note 2 -50oC TO 85oC Enclosure: IP66/ IP67 All All - STANDARDS: EN 60079-0: 2012/A11: 2013; EN 60079-1: 2014; EN 60079-7: 2015; EN 6007911: 2012; EN 60079-26: 2015; EN 60079-31: 2009 Flameproof: IECEx SIR 12.0100X Ex db IIC T6..T5 Ga/Gb Ex tb IIIC T95oC...T120oC Db All Note 1 T5: -50oC TO 85oC T6: -50oC TO 65oC Intrinsically Safe: IECEx SIR 12.0100X Ex ia IIC T4 Ga FISCO Field Device (Only for FF Option) Ex ia IIC T4 Ga; Ex ic IIC T4 Gc 4-20 mA / DE/ HART Foundation Fieldbus Note 2 Note 2 -50oC TO 70oC -50oC TO 70oC Zone 2, Increase Safety: IECEx SIR 12.0100X Ex ec IIC T4 Gc 4-20 mA / DE/ HART/ Foundation Fieldbus Note 1 -50oC TO 85oC Zone 2, Intrinsically Safe: IECEx SIR 12.0100X Ex ic IIC T4 Gc FISCO Field Device (Only for FF Option) Ex ic IIC T4 Gc 4-20 mA / DE/ HART/ Foundation Fieldbus Note 2 -50oC TO 85oC Enclosure: IP66/ IP67 All All - STANDARDS: IEC 60079-0: 2011; IEC 60079-1: 2014; IEC 60079-7: 2017; IEC 60079-11: 2011; IEC 60079-26: 2014; IEC 60079-31: 2013 Flameproof : Ex d IIC T6...T5 Ga/Gb Ex tb IIIC T95oC...T120oC Db All Note 1 T5: -50oC TO 85oC T6: -50oC TO 65oC Intrinsically Safe: Ex ia IIC Ga T4 FISCO Field Device (Only for FF Option) Ex ia IIC T4 Ga; Ex ic IIC T4 Gc 4-20 mA / DE/ HART Foundation Fieldbus Note 2 Note 2 E SAEx Zone 2, Increase Safety: South Africa II 3 G Ex ec IIC T4 Gc 4-20 mA / DE/ HART/ Foundation Fieldbus Note 1 -50oC TO 70oC -50oC TO 70oC -50oC TO 85oC Zone 2, Intrinsically Safe: Ex ic IIC T4 Gc FISCO Field Device (Only for FF Option) Ex ic IIC T4 Gc 4-20 mA / DE/ HART/ Foundation Fieldbus Note 2 -50oC TO 85oC Enclosure: IP66/ IP67 All All - Flameproof: Ex db IIC T6..T5 Ga/Gb Ex tb IIIC T95oC...T120oC Db All Note 1 T5: -50oC TO 85oC T6: -50oC TO 65oC Intrinsically Safe: Ex ia IIC T4 Ga 4-20 mA / DE/ HART Note 2a -50oC TO 70oC INMETRO FISCO Field Device (Only for FF Option) Ex ia IIC T4 Ga; Ex ic IIC T4 Gc Foundation Fieldbus Note 2b -50oC TO 70oC F Brazil Zone 2, Increase Safety: II 3 G Ex ec IIC T4 Gc 4-20 mA / DE/ HART/ Foundation Note 1 -50oC TO 85oC Fieldbus Zone 2, Intrinsically Safe: Ex ic IIC T4 Gc FISCO Field Device (Only for FF Option) Ex ic IIC T4 Gc 4-20 mA / DE/ HART/ Foundation Fieldbus Note 2 -50oC TO 85oC Enclosure : IP 66/67 All All - Flameproof: Ex db IIC T6..T5 Ga/Gb Ex tb IIIC T 95oC Db All Note 1 T5: -50oC TO 85oC T6: -50oC TO 65oC Intrinsically Safe: Ex ia IIC T4 Ga FISCO Field Device (Only for FF Option) Ex ia IIC T4 Ga; Ex ic IIC T4 Gc 4-20 mA / DE/ HART Foundation Fieldbus Note 2 Note 2 -50oC TO 70oC -50oC TO 70oC G NEPSI CHINA Zone 2, Increase Safety: II 3 G Ex ec IIC T4 Gc 4-20 mA / DE/ HART/ Foundation Fieldbus Note 1 -50oC TO 85oC Zone 2, Intrinsically Safe: Ex ic IIC T4 Gc FISCO Field Device (Only for FF Option) Ex ic IIC T4 Gc 4-20 mA / DE/ HART/ Foundation Fieldbus Note 2 -50oC TO 85oC Enclosure : IP 66/67 All All - Flameproof : Ex d IIC T4, T5, T6 All Ex tD A21 IP66/IP67 T95oC...T120 oC H KOSHA Korea Intrinsically Safe: Ex ia IIC T4 4-20 mA / DE/ HART Foundation Fieldbus Enclosure: IP66/ IP67 All Flameproof: Ga/Gb Ex d IIC T6..T5 All Ex tb IIIC Db T 85oC Intrinsically Safe: Ga Ex ia IIC T4 X FISCO Field Device (Only for FF Option) EAC Ga Ex ia IIC T4 X I Russia, Belarus and Kazakhstan Zone 2, Non Sparking: 2 Ex nA IIC T4 Gc X 4-20 mA / DE/ HART Foundation Fieldbus 4-20 mA / DE/ HART/ Foundation Fieldbus Zone 2, Intrinsically Safe: Ga Ex ic IIC T4 X FISCO Field Device (Only for FF Option) 2 Ex ic IIC T4 Gc X 4-20 mA / DE/ HART/ Foundation Fieldbus Enclosure : IP 66/67 All Flameproof: Ex d IIC T6..T5 Ga/Gb All Intrinsically Safe: Ex ia IIC T4 Ga 4-20 mA / DE/ HART J CCoE INDIA FISCO Field Device (Only for FF Option) Ex ia IIC T4 Ga; Ex ic IIC T4 Gc Foundation Fieldbus Non Sparking 4-20 mA / DE/ Ex nA IIC T4 Gc HART/ Foundation Fieldbus Enclosure: IP66/ IP67 All Flameproof: II 1/2 G Ex db IIC T6..T5 Ga/Gb All II 2 D Ex tb IIIC T95oC...T120oC Db K UATR UKRAINE Intrinsically Safe: II 1 G Ex ia IIC T4 Ga 4-20 mA / DE/ HART FISCO Field Device (Only for FF Option) II 1 G Ex ia IIC T4 Ga Foundation Fieldbus Enclosure: IP66/ IP67 All Notes: 1. Operating Parameters: Voltage= 11 to 42 V DC Current= 4-20 mA Normal = 10 to 30 V (FF) = 30 mA (FF) Note 1 Note 2 Note 2 All Note 1 Note 2 Note 2 Note 1 Note 2 All Note 1 Note 2 Note 2 Note 1 All Note 1 Note 2 Note 2 All T4: -50oC TO 85oC T5: -50oC TO 85oC T6: -50oC TO 65oC Ta= -50 ºC to 70ºC Ta= -50 ºC to 70ºC T5: -50oC TO 85oC T6: -50oC TO 65oC -50oC TO 70oC -50oC TO 70oC -50oC TO 85oC -50oC TO 85oC T5: -50oC TO 85oC T6: -50oC TO 65oC -50oC TO 70oC -50oC TO 70oC -50oC TO 85oC T5: -50oC TO 85oC T6: -50oC TO 65oC -50oC TO 70oC -50oC TO 70oC - 2. Intrinsically Safe Entity Parameters a. Analog/ DE/ HART Entity Values: Vmax= Ui = 30V Imax= Ii= 105mA Ci = 4.2nF Li =984 uH Pi =0.9W Transmitter with Terminal Block Revision E or Later Vmax= Ui = 30V Imax= Ii= 225mA Ci = 4.2nF Li = 0 Pi =0.9W Note : Transmitter with Terminal Block Revision E or later The revision is on the label that is on the module. There will be two lines of text on the label: · First is the Module Part #: 50049839-001 or 50049839-002 · Second line has the supplier information, along with the REVISION: XXXXXXX-EXXXX, THE "X" is production related, THE POSITION of the "E" IS THE REVISION. b. Foundation Fieldbus- Entity Values Vmax= Ui = 30V Imax= Ii= 180mA Ci = 0nF Li = 984 uH Pi =1W Transmitter with Terminal Block Revision F or Later Vmax= Ui = 30V Imax= Ii= 225mA Ci =0nF Li = 0 Pi =1 W FISCO Field Device Imax= Ii= 380 mA Ci = 0nF Li = 0 Pi =5.32 W Vmax= Ui = 17.5V Note : Transmitter with Terminal Block Revision F or later The revision is on the label that is on the module. There will be two lines of text on the label: · First is the Module Part #: 50049839-003 or 50049839-004 · Second line has the supplier information, along with the REVISION: XXXXXXX-EXXXX, THE "X" is production related, THE POSITION of the "E" IS THE REVISION . Approval Certifications: This certificate defines the certifications covered for the SmartLine Pressure Transmitter family of products, including the SMV SmartLine Multivariable Transmitter. It represents the compilation of the five certificates Honeywell currently has covering the certification of these products into marine applications. American Bureau of Shipping (ABS) - 2009 Steel Vessel Rules 1-1-4/3.7, 4-6-2/5.15, 4-8-3/13 & Marine Certificates 13.5, 4-8-4/27.5.1, 4-9-7/13. Certificate number: 04-HS417416-PDA Bureau Veritas (BV) - Product Code: 389:1H. Certificate number: 12660/B0 BV Det Norske Veritas (DNV) - Location Classes: Temperature D, Humidity B, Vibration A, EMC B, Enclosure C. For salt spray exposure; enclosure of 316 SST or 2-part epoxy protection with 316 SST bolts to be applied. Certificate number: A-11476 Korean Register of Shipping (KR) - Certificate number: LOX17743-AE001 Lloyd's Register (LR) - Certificate number: 02/60001(E1) & (E2) SIL 2/3 Certification IEC 61508 SIL 2 for non-redundant use and SIL 3 for redundant use according to EXIDA and TÜV Nord Sys Tec GmbH & Co. KG under the following standards: IEC61508-1: 2010; IEC 61508-2: MEASUREMENT INTRUMENTS DIRECTIVE (MID) 2004/ 22/ EC 2010; IEC61508-3: 2010. Certificate Issued by NMI Certin B.V. Mechanical Class: M3 Electromagnetic Environment: E3 Ambient Temperature Range: -25 oC to + 55 oC Unit Custom Calibration STD820 0 to 1000 mBar STD830 0 to 7 Bar STA84L 0 to 35 Bar A STG84L 0 to 35 Bar STD870 0 to 100 Bar STA87L 0 to 100 Bar A STG87L 0 to 100 Bar Application Data Liquid Level: Closed Tank Determine the minimum and maximum pressure differentials to be measured (Figure 19). PMin = (SGp x a) - (SGf x d) = LRV when HP at bottom of tank = URV when LP at bottom of tank PMax = (SGp x b) - (SGf x d) = URV when HP at bottom of tank = LRV when LP at bottom of tank Where: minimum level at 4mA maximum level at 20 mA a = distance between bottom tap and minimum level b = distance between bottom tap and maximum level d = distance between taps SGf = Specific Gravity of capillary fill fluid (See Page 6 "Material Specifications" for values.) SGp = Specific Gravity of process fluid Figure 19--Closed tank liquid level measurement distance Application Data (Cont'd) Density or Interface* Calculate the minimum and maximum pressure differentials to be measured (Figure 20). Pmin = (SGmin SGf) x (d); minimum density, 4mA output Pmax = (SGmax SGf) x (d); maximum density, 20mA output Where: d = distance between the taps SGmax = maximum Specific Gravity SGmin = minimum Specific Gravity SGf = Specific Gravity of capillary fill fluid (See Page 6 "Material Specifications" for values.) Figure 20--Density, direct acting transmitter configuration Seal Configurations . Figure 21--Flush Flange Seals and with left lower Flush Flange Seals can be used with differential, gauge and absolute pressure transmitters and are available with 3" ANSI Class 150, ANSI Class 300 and DIN DN80-PN40 process connections. Flush flange seals can also be provided with Lowers. Lowers are essentially calibration rings, which allow flushing connections if needed. Figure 23--Pancake Seals Pancake Seals can be used with differential, gauge and absolute pressure transmitters and are available with 3" ANSI Class 150, 300 and 600 process connections. Figure 22-- Flange Seal with Extended Diaphragm Flange Seal with Extended Diaphragm can be used with differential, gauge and absolute pressure transmitters and are available with 3" and 4" ANSI Class 150, ANSI Class 300, DIN DN80-PN40 and DIN DN100-PN40 process connections. 2", 4" and 6" extension lengths are available Figure 24-- Chemical Tee "Taylor" Wedge Chemical Tee "Taylor" Wedge can be used with differential pressure transmitters and are available with Taylor Wedge 5" O.D. process connection. Seal Configurations (cont'd) Figure 25-- Seals with Threaded Process Connections Seals with Threaded Process Connections can be used with differential, gauge and absolute pressure transmitters and are available with ½", ¾" and 1" NPT Female process connections. Figure 29-- Stainless Steel Armor and PVC Coated Stainless Steel Armor Capillaries Stainless Steel Armor and PVC Coated Stainless Steel Armor Capillaries are available with Honeywell Remote Seal Solutions. Figure 26-- Sanitary Seals Sanitary Seals can be used with differential, gauge and absolute pressure transmitters and are available with 3" and 4" Tri-Clover-Tri-Clamp process connections. Figure 30-- 2" Stainless Steel Nipples 2" Stainless Steel Nipples are available for CloseCoupled remote seal solutions Figure 27-- Saddle Seals Saddle Seals can be used with differential, gauge and absolute pressure transmitters and are available with 3" and 4" (6 bolt or 8 bolt designs) process connections. Figure 31-- Welded Meter Body for All-Welded Remote Seal Solution Welded Meter Body for All-Welded Remote Seal Solution. The welded ST 800 meter body is an important part of an All-Welded Remote Seal Solution, which is commonly used in Vacuum applications. Figure 28-- Calibration Rings Calibration Rings are available with Flush Flange Seals and Pancake Seals. Flushing ports (1/4" or ½") are available with calibration rings. Model Selection Guide Model Selection Guides are subject to change and are inserted into the specifications as guidance only. Model STR800 (DP, GP & AP) Remote Seals Model Selection Guide 34-ST-16-88 Issue 26 Instructions Select the desired Key Number. The arrow to the right marks the selection available. Make selections from each Table (I, II and IX) using the column below the proper arrow . A () denotes unrestricted availability. A letter denotes restricted availability. Restrictions follow Table IX. Key Number STR _ _ _ I II III IV V VI VII VIII - _______ - _________ - _ - ___ - ___ - _ - ____ - __ + IX 0 0 0 0 KEY NUMBER Measurement Range Std Accuracy URL 400 (1000) 100 (7) 500 (35) 500 (35) 3000 (210) LRL -400 (-1000) -100 (-7) 5.7 (0.39) -14.7 (-1.0) 14.7 (-1.0) Max Span 400 (1000) 100 (7) 500 (35) 500 (35) 3000 (210) Min Span 4 (10) 1 (0.07) 5 (0.35) 5 (0.35) 30 (2.1) Units " H2O (mbar) psi (bar) psia (bar A) psi (bar) psi (bar) Note: Remote seal system pressure rating is body rating or seal rating, w hichever is less. Selection STR82D STR83D STR84A STR84G STR87G TABLE I Description a. Number of Seals b. Primary Fill Fluid (Meter body) 1 Remote Seal (High Side) 2 Remote Seals 1 Remote Seal (Low Side) Silicone Oil 200 Fluorinated Oil CTFE Silicone Oil 704 NEOBEE® M-20 11 c. Construction Non-Wetted Adapter Head Materials In-Line Gauge/ Absolute Dual Head DP 316 SS Bonnet 316 SS Bonnet for Close-Couple 316 SS (bolt-on heads) 316 SS for Close-Couple 316 SS with all-welded meter body None d. Bolts and Nuts Carbon Steel Bolts and Nuts for Transmitter 316 SS Bolts and Nuts Heads A286 SS (NACE) Bolts and 304 SS (NACE) Nuts B7M (NACE) Bolts and 7M (NACE) Nuts Meter Body & Capillaries No Fill Fluid e. Secondary Fill Fluid (capillary & seal)** Silicone Oil 200 Fluorinated Oil CTFE Silicone Oil 704 Neobee® M20 11 Syltherm® 800 12 No Capillary, No Nipple (Specify for VAM Unit Only) 5 feet 1.5 m 10 feet 3.0 m f. Connection 15 feet 20 feet 25 feet 4.5 m 6.1 m 7.5 m SS Armor of Remote Capillary 35 feet 10.7 m Seal to Meter Length 5 feet 1.5 m Body** 10 feet 15 feet 3.0 m 4.5 m PVC Coated SS 20 feet 6.1 m Arm or 25 feet 7.5 m 35 feet 10.7 m 2 inch long SS nipple close-coupled None g. Seal Option** Std Gold Plated Seal Diaph. = 50 µin Teflon Coated Seal Diaphragm - only for anti-sticking ** Refer to 34-ST-00-128 for additional options, consult factory 11 Limited vacuum availability. 12 Minimum static pressure requirement. No vacuum allow ed. See Specifications 34-ST-03-88 Figure 15 Selection 1 _ _ _ _ _ _ 2 _ _ _ _ _ _ 3 _ _ _ _ _ _ _ 1 _ _ _ _ _ _ 2 _ _ _ _ _ _ 3 _ _ _ _ _ _ 4 _ _ _ _ _ _ _ A_ _ _ _ _ _ B _ _ _ _ _ _ C _ _ _ _ _ _ D _ _ _ _ _ _ E _ _ _ _ _ _ _ 0 _ _ _ _ _ _ C _ _ _ _ _ _ S _ _ _ _ _ _ N _ _ _ _ _ _ B _ _ _ _ _ _ _ 0 _ _ _ _ _ _ 1 _ _ _ _ _ _ 2 _ _ _ _ _ _ 3 _ _ _ _ _ _ 4 _ _ _ _ _ _ 5 _ _ _ _ _ _ _ 0 _ _ _ _ _ _ A_ _ _ _ _ _ B _ _ _ _ _ _ C _ _ _ _ _ _ D _ _ _ _ _ _ E _ _ _ _ _ _ F _ _ _ _ _ _ G _ _ _ _ _ _ H _ _ _ _ _ _ J _ _ _ _ _ _ K _ _ _ _ _ _ L _ _ _ _ _ _ M_ _ _ _ _ _ 2 _ _ _ _ _ _ _ 0 _ _ _ _ _ _ 1 _ _ _ _ _ _ 4 Availability 22 3 3 4 22 55 55 66 77 77 26 STR800 Smart Pressure Transmitter In-Line Gauge Dual Head DP Note: When selecting required seal, you must specify only the 9 selections within the required s eal type. TABLE II Seals Description No Seal Attached to Core Transm itter (Specify for VAM Unit Only) Seal Type Diaphragm Diameter Flange Size Flange Pressure Rating 1 3" 3.5" 80mm ANSI Class 150 ANSI Class 300 DIN DN80-PN40 Diaphragm Upper Insert Wetted Material Non-Wetted Material (upper) 316L SS Hastelloy® C-276 Hastelloy® C-276 316L SS 316L SS Hastelloy® C-276 Monel 400® Tantalum 5 Monel 400® 316L SS CS (Nickel Plated) 316L SS Flush Flanged Seal** Seal-Capillary Connection Calibration Rings Flus hing Center Seal Side Seal None 316L SS Hastelloy® C-276 Monel 400® None Connections and Plugs 4 (Metal plug material One 1/4" with plastic plug One 1/4" with metal plug Two 1/4" with plastic plugs w ill be the same as Two 1/4" with metal plugs Cal. ring material if One 1/2" with plastic plug metal plug is chosen ) One 1/2" with metal plug Two 1/2" with plastic plugs Two 1/2" with metal plugs ** Refer to 34-ST-00-128 for additional options, consult factory 1 Standard facing 125-250 AARH RF (raised face) serrated surface finish. 4 Plastic Plugs are TEMPORARY ONLY to protect threads and MUST be REMOVED before installation 5 Tantalum Upper insert has Tantalum w etted parts and 316 SS or CS non-w etted parts Note: Remote seal system pressure rating is body rating or seal rating, w hichever is less. All welded STR84G & 87G & 84A STR82D & 83D Selection 0 0 0 0 0 0 0 0 0 21 21 Se le ction AFA _ _ _ _ _ _ AFC _ _ _ _ _ _ AFM _ _ _ _ _ _ Se le ction _ _ _ AA _ _ _ _ _ _ _ AB _ _ _ _ _ _ _ AC _ _ _ _ _ _ _ AE _ _ _ _ 88 _ _ _ AF _ _ _ _ 88 _ _ _ _ _ 1 _ _ _ _ _ _ _ _ 2 _ _ _ _ _ _ _ _ _ 1 _ _ _ _ _ _ _ _ 2 _ _ 99 _ _ _ _ _ _ _ A_ _ _ _ _ _ _ _ B _ 10 10 _ _ _ _ _ _ _ C _ 10 10 _ _ _ _ _ _ _ D _ 10 10 _ _ _ _ _ _ _ _ 0 _ _ _ _ _ _ _ _ H 11 11 _ _ _ _ _ _ _ _ J 11 11 _ _ _ _ _ _ _ _ M 11 11 _ _ _ _ _ _ _ _ N 11 11 _ _ _ _ _ _ _ _ P 11 11 _ _ _ _ _ _ _ _ Q 11 11 _ _ _ _ _ _ _ _ R 11 11 _ _ _ _ _ _ _ _ S 11 11 Table II continued next page STR84G & 87G & 84A STR82D & 83D TABLE II Descripton Selection Seal Type Diaphragm Diameter Flange Size Flange Pr e s s ur e Rating 1 Const. - See Spec. Figure 34-ST-03-88 Construction - See Spec. Figure 34-ST-03-88 ANSI 150 22 1" ANSI 300 22 BCA _ _ _ _ _ _ BCC _ _ _ _ _ _ 12 12 1-1/2" ANSI 150 22 ANSI 300 22 2.4" 2" ANSI 150 22 ANSI 300 22 BGA _ _ _ _ _ _ BGC _ _ _ _ _ _ BDA _ _ _ _ _ _ BDC _ _ _ _ _ _ 12 12 12 12 ANSI 150 22 3" ANSI 300 22 BFA _ _ _ _ _ _ BFC _ _ _ _ _ _ 12 12 1/2" ANSI 150 23 CAA _ _ _ _ _ _ ANSI 150 23 1" ANSI 300 23 CCA _ _ _ _ _ _ CCC _ _ _ _ _ _ 2.9" 1-1/2" ANSI 150 22 ANSI 300 22 CGA _ _ _ _ _ _ CGC _ _ _ _ _ _ 2" ANSI 150 22 ANSI 300 22 CDA _ _ _ _ _ _ CDC _ _ _ _ _ _ 1/2" ANSI 150 22 DAA _ _ _ _ _ _ 1" ANSI 150 23 ANSI 300 23 DCA _ _ _ _ _ _ DCC _ _ _ _ _ _ 1-1/2" ANSI 150 23 4.1" ANSI 300 23 DGA _ _ _ _ _ _ DGC _ _ _ _ _ _ 2" ANSI 150 23 ANSI 300 22 DDA _ _ _ _ _ _ DDC _ _ _ _ _ _ Seals (continued) Flush Flanged Seal with Lower** 3" Wetted Material ANSI 150 ANSI 300 Diaphragm 316L SS Hastelloy® C-276 Hastelloy® C-276 Monel 400® Tantalum Tantalum 22 22 Low er 316L SS 316L SS Hastelloy® C-276 Monel 400® 316L SS Hastelloy® C-276 DFA _ _ _ _ _ _ DFC _ _ _ _ _ _ Selection _ _ _ BA _ _ _ _ _ _ _ BB _ _ _ _ _ _ _ BC _ _ _ _ _ _ _ BE _ _ _ _ _ _ _ BF _ _ _ _ _ _ _ BG _ _ _ _ 88 88 88 Tantalum Tantalum Clad _ _ _ BH _ _ _ _ 13 13 Non-Wetted Material (upper, upper insert) Bolts 6 Uppe r Upper Insert 316L SS 316L SS Carbon Steel 316L SS No Selection Selection _ _ _ _ _ 4 _ _ _ _ _ _ _ _ 5 _ _ _ _ _ _ _ _ _ 0 _ _ Flus hing Connections and Plugs4 (Metal plug material w ill be the same as Low er material, if metal plug is chosen (SS Plug for CS Low er and Tantalum Clad) Gas ket None One 1/4" with plastic plug One 1/4" with metal plug Two 1/4" with plastic plugs Two 1/4" with metal plugs One 1/2" with plastic plug One 1/2" with metal plug Two 1/2" with plastic plugs Two 1/2" with metal plugs Klinger® C-4401 (non-asbestos) Grafoil® Teflon® Gylon® 3510 _______0 _ _ _ _ _ _ _ _ H _ _______J _ _ _ _ _ _ _ _ M_ _ _ _ _ _ _ _ N _ _ _ _ _ _ _ _ P _ _ _ _ _ _ _ _ Q _ _ _ _ _ _ _ _ R _ _ _ _ _ _ _ _ S _ _ _ _ _ _ _ _ _ K _ _ _ _ _ _ _ _ G _ _ _ _ _ _ _ _ T _ _ _ _ _ _ _ _ L 15 15 Table II continued next page ** Refer to 34-ST-00-128 for additional options, consult factory 1 Standard facing 125-250 AARH RF (raised face) serrated surface finish. 6 Bolt material w ill be same as Upper Material. How ever, if Table I bolts/nuts material is NACE or B7M, seal bolt material w ill be 304 SS NACE. 4 Plastic Plugs are TEMPORARY ONLY to protect threads and MUST be REMOVED before installation Note: Remote seal system pressure rating is body rating or seal rating, w hichever is less. 28 STR800 Smart Pressure Transmitter TABLE II Seals (continued) Seal Type Flange Seal with Extended Diaphragm ** No Selection Descripton Diaphragm Diameter Flange Size Flange Pressure Rating 1 3" 2.8" (2.8" OD ANSI Class 150 ANSI Class 300 extension) 4" 3.5" (3.70" OD DIN DN80-PN40 ANSI Class 150 ANSI Class 300 extension DIN DN100-PN40 Diaphragm Ext. Tube Wetted Material 316L SS Hastelloy® C-276 Hastelloy® C-276 316L SS 316L SS Hastelloy® C-276 Non-Wetted CS (Nickel Plated) Material (flange) 316L SS Bolts No Selection 2" Extension Length 4" 6" No Selection No Selection TABLE II Descripton Seal Type Diaphragm Diameter Flange Flange Pressure Rating Dependent Size on Custom er Flange 1 3.5" 3" Wetted Material ANSI Class 150/300/600 Diaphragm Body 316L SS Hastelloy® C-276 Hastelloy® C-276 316L SS 316L SS Hastelloy® C-276 Monel 400® Tantalum Monel 400® Tantalum 7 Non-Wetted Material No Selection Seals (continued) Bolts Calibration Rings No Selection None Pancake Seal Flus hing 316L SS Hastelloy® C-276 Monel 400® None Connections One 1/4" with plastic plug and Plugs4 (Metal plug material One 1/4" with metal plug Two 1/4" with plastic plugs w ill be the same as Two 1/4" with metal plugs Cal. Ring material, if One 1/2" with plastic plug metal plug is chosen) One 1/2" with metal plug Two 1/2" with plastic plugs Two 1/2" with metal plugs ** Refer to 34-ST-00-128 for additional options, consult factory 1 Standard facing 125-250 AARH RF (raised face) serrated surface finish. 4 Plastic Plugs are TEMPORARY ONLY to protect threads and MUST be REMOVED before installation 7 Tantalum Body has Tantalum w etted parts and 316 SS non-w etted parts Note: Remote seal system pressure rating is body rating or seal rating, w hichever is less. STR84G & 87G & 84A STR82D & 83D Se le ction EFA _ _ _ _ _ _ EFC _ _ _ _ _ _ EFM _ _ _ _ _ _ FGA _ _ _ _ _ _ FGC _ _ _ _ _ _ FGP _ _ _ _ _ _ Selection _ _ _ EA _ _ _ _ _ _ _ EB _ _ _ _ _ _ _ EC _ _ _ _ _ _ _ _ _ 7 _ _ _ _ _ _ _ _ 8 _ _ _ _ _ _ _ _ _ 0 _ _ _______2 _ _ _ _ _ _ _ _ 4 _ _ _ _ _ _ _ _ 6 _ _ _ _ _ _ _ _ _ 0 STR84G & 87G & 84A STR82D & 83D Se le ction GFA _ _ _ _ _ _ _ _ _ GA _ _ _ _ _ _ _ GB _ _ _ _ _ _ _ GC _ _ _ _ _ _ _ GE _ _ _ _ _ _ _ GG _ _ _ _ _ _ _ _ _ 0 _ _ _ _ _ _ _ _ _ 0 _ _ _ _ _ _ _ _ _ A_ _ _ _ _ _ _ _ B _ _ _ _ _ _ _ _ C _ _ _ _ _ _ _ _ D _ _ _ _ _ _ _ _ _ 0 _ _ _ _ _ _ _ _ H _ _ _ _ _ _ _ _ J _ _ _ _ _ _ _ _ M _ _ _ _ _ _ _ _ N _ _ _ _ _ _ _ _ P _ _ _ _ _ _ _ _ Q _ _ _ _ _ _ _ _ R _ _ _ _ _ _ _ _ S 88 88 10 10 10 10 10 10 11 11 11 11 11 11 11 11 11 11 11 11 11 11 11 11 TABLE II Seals (continued) Seal Type Chemical Tee "Taylor" Wedge Descripton Diaphragm Diameter Flange Size Flange Pressure Rating 1 Taylor 3.5" Wedge 5" O.D. 750 psi Wetted Material Non-Wetted Material Bolts Styles No Selection Diaphragm Body 316L SS Hastelloy® C-276 316L SS 316L SS Hastelloy® C-276 Hastelloy® C-276 No Selection No Selection No Selection No Selection STR84G & 87G & 84A STR82D & 83D Se le ction HM0 _ _ _ _ _ _ 16 Selection _ _ _ HA _ _ _ _ _ _ _ HB _ _ _ _ _ _ _ HC _ _ _ _ _ _ _ _ _ 0 _ _ _ _ _ _ _ _ 0 _ _ _______0 _ _ _ _ _ _ _ _ _ 0 Table II continued below STR84G & 87G & 84A TABLE II Descripton STR82D &83D Seal Type Diaphragm Diameter Threaded Process Connection Size (NPT Fem ale) Pressure Rating CS Bolts 304 SS Bolts Selection 2.4" 1/2 NPT 3/4 NPT 2,500 psi 1,250 psi JJG _ _ _ _ _ _ JKG _ _ _ _ _ _ 12 12 1 NPT JLG _ _ _ _ _ _ 12 2.9" 1/2 NPT 3/4 NPT 2,500 psi 1,250 psi KJG _ _ _ _ _ _ KKG _ _ _ _ _ _ 1 NPT KLG _ _ _ _ _ _ 4.1" 1/2 NPT 3/4 NPT 1,500 750 psi psi LJG _ _ _ _ _ _ LKG _ _ _ _ _ _ 1 NPT LLG _ _ _ _ _ _ Diaphragm Low er Selection Seals (continued) Seal with Threaded Proces s Connection Wetted Material Non-Wetted Material (upper) 316L SS Carbon Steel 316L SS Hastelloy® C-276 Hastelloy® C-276 316L SS 316L SS Hastelloy® C-276 Monel 400® Monel 400® Tantalum Tantalum 316L SS Hastelloy® C-276 CS (Nickel Plated) 316 Stainless Steel _ _ _ JA _ _ _ _ _ _ _ JB _ _ _ _ _ _ _ JC _ _ _ _ _ _ _ JD _ _ _ _ _ _ _ JE _ _ _ _ _ _ _ JF _ _ _ _ _ _ _ JG _ _ _ _ _ _ _ _ _ A_ _ _ _ _ _ _ _ C _ _ _ 88 88 88 17 17 Bolts 8 Flus hing Connections and Plugs4 (Metal plug material w ill be the same as Low er material, if Carbon Steel 304 SS None One 1/4" with plastic plug One 1/4" with metal plug Two 1/4" with plastic plugs Two 1/4" with metal plugs One 1/2" with plastic plug _ _ _ _ _ _ C _ _ _ _ _ _ _ _ D _ _ _______0 _ _ _ _ _ _ _ _ H _ _______J _ _ _ _ _ _ _ _ M_ _ _ _ _ _ _ _ N _ _ _ _ _ _ _ _ P _ 18 18 metal plug is chosen - One 1/2" with metal plug _ _ _ _ _ _ _ Q _ 18 18 (SS Plug for CS Low er Two 1/2" with plastic plugs _ _ _ _ _ _ _ R _ 18 18 and Tantalum Clad) Two 1/2" with metal plugs Gas ket Klinger® C-4401 (non-asbestos) Grafoil® Teflon® Gylon® 3510 _ _ _ _ _ _ _ S _ _ _ _ _ _ _ _ _ K _ _ _ _ _ _ _ _ G _ _ _ _ _ _ _ _ T _ _ _ _ _ _ _ _ L 18 18 15 15 1 Standard facing 125-250 AARH RF (raised face) serrated surface finish. 4 Plastic Plugs are TEMPORARY ONLY to protect threads and MUST be REMOVED before installation 8 If Table I Bolts and Nuts material option is NACE, Bolts and Nuts w ill ship w ith Alloy Steel NACE and MAWP may change. Note: Remote seal system pressure rating is body rating or seal rating, w hichever is less. 30 STR800 Smart Pressure Transmitter TABLE II Seals (continued) Seal Type Sanitary Seal 9 Descripton Diaphragm Diameter Flange Size Pressure Rating 1.9" 2" 2.4" 2-1/2" 2.9" 3" Customer clamp rating or 600 psi, whichever is less 4.1" 4" Wetted Material Diaphragm 316L SS Body 316L SS Non-Wetted Material No Selection Bolts Styles Gas ket No Selection Tri-Clover Tri-Clamp® No Selection TABLE II Descripton Seal Type Diaphragm Diameter Size and Bolt Patte r n Seal Pressure Rating C.S. Bolts 316 SS Bolts 2.4" 8-Bolt Design 2.4" 6-Bolt Design for 3" Pipe 4" pipe for 3" Pipe 4" pipe 2,500 psi 2,000 psi Diaphragm 316L SS 1,250 psi 1,000 psi Low er Housing Carbon Steel Seals (continued) Saddle Seal Wetted Material 316L SS Hastelloy® C-276 Hastelloy® C-276 316L SS Hastelloy® C-276 Body 316L SS 316L SS Hastelloy® C-276 N/A-Body Only 10 N/A-Body Only 10 Bolts 10,11 Non-Wetted Material Carbon Steel 316L SS Carbon Steel 316 SS Bolts No Selection Styles No Selection Klinger® C-4401 (non-asbestos) Gas ket Grafoil® Teflon® Gylon® 3510 9 All sanitary seals have dairy grade 3A approval. 10 Bolts are not included w ith "body only" selection. 11 If Table I Bolts and Nuts material option is NACE, seal bolt material w ill be 304 SS NACE. Note: Remote seal system pressure rating is body rating or seal rating, w hichever is less. STR84G & 87G & 84A STR82D & 83D Selection MD0 _ _ _ _ _ _ 19 NE0 _ _ _ _ _ _ 20 19 PF0 _ _ _ _ _ _ 19 19 QG0 _ _ _ _ _ _ 19 19 Selection _ _ _ N A_ _ _ _ _ _ _ _ _ 0 _ _ _ _ _ _ _ _ _ 0 _ _ _______8 _ _ _ _ _ _ _ _ _ 0 Table II continued below STR84G & 87G & 84A STR82D & 83D Selection RFK _ _ _ _ _ _ RGK _ _ _ _ _ _ RPK _ _ _ _ _ _ RQK _ _ _ _ _ _ Selection _ _ _ RA _ _ _ _ _ _ _ RB _ _ _ _ _ _ _ RC _ _ _ _ _ _ _ RD _ _ _ _ _ _ _ SB _ _ _ _ _ _ _ SC _ _ _ _ Selection _ _ _ _ _ B _ _ _ _ _ _ _ _ C _ _ _ _ _ _ _ _ _ 0 _ _ _ _ _ _ _ _ _ 0 _ _ _ _ _ _ _ _ _ K _ _ _ _ _ _ _ _ G _ _ _ _ _ _ _ _ T _ _ _ _ _ _ _ _ L 12 12 12 12 88 STR84G & 87G & 84A STR82D & 83D TABLE III Approvals Agency Approvals (see data sheet for Approval Code Details) No Approvals Required FM Explosion proof, Intrins ically Safe, Non-incendive, & Dus tproof CSA Explos ion proof, Intrins ically Safe, Non-incendive, & Dus tproof ATEX Explos ion proof, Intrins ically Safe & Non-incendive IECEx Explosion proof, Intrins ically Safe & Non-incendive SAEx Explosion proof, Intrins ically Safe & Non-incendive INMETRO Explosion proof, Intrins ically Safe & Non-incendive NEPSI Explosion proof, Intrins ically Safe & Non-incendive KOSHA Explos ion proof, Intrins ically Safe & Non-incendive EAC Custom s Union(Russ ia,Belarus,Kazakhstan) Ex Approval,Flam eproof, Intrinsically Safe CCoE Explosion proof, Intrins ically Safe & Non-incendive UATR Flam eproof, Intrins ically Safe & Dustproof 0 A B C D E F G H I J K TABLE IV TRANSMITTER ELECTRONIC SELECTIONS M ate r ial Conne ction Lightning Protection Polyester Powder Coated Aluminum 1/2 NPT None Polyester Powder Coated Aluminum a. Electronic Polyester Powder Coated Aluminum Housing Material & Connection Polyester Powder Coated Aluminum Type 316 Stainless Steel (Grade CF8M) 316 Stainless Steel (Grade CF8M) M20 1/2 NPT M20 1/2 NPT M20 None Yes Yes None None 316 Stainless Steel (Grade CF8M) 1/2 NPT Yes 316 Stainless Steel (Grade CF8M) M20 Yes Analog Output Digital Protocol b. Output/ Protocol 4-20m A dc 4-20m A dc HART Protocol DE Protocol Indicator none p g Buttons Foundation Fieldbus Language s None None None None Yes (Zero/Span Only) None c. Customer Bas ic None Englis h Interface Selections Bas ic Advanced Yes None Englis h EN,GR,IT, FR,SP,RU, TU Advanced Yes EN,GR,IT, FR,SP,RU, TU Advanced None EN, CH, JP Advanced Yes EN, CH, JP A _ _ B _ _ C _ _ D _ _ E _ _ F _ _ G _ _ H _ _ _ H _ _ D _ _ F _ _ _ 0 _ _ A _ _ B _ _ C _ _ D _ _ E _ _ H _ _ J ff TABLE V CONFIGURATION SELECTIONS a. Application Software Standard Diagnostics Diagnostics Write Protect Fail Mode High & Low Output Lim its3 Disabled High> 21.0mAdc Honeywell Std (3.8 - 20.8 mAdc) b. Output Limit, Failsafe & Write Protect Settings Disabled Enabled Enabled Low< 3.6mAdc High> 21.0mAdc Low< 3.6mAdc Honeywell Std (3.8 - 20.8 mAdc) Honeywell Std (3.8 - 20.8 mAdc) Honeywell Std (3.8 - 20.8 mAdc) Enabled N/A N/A Fieldbus or Profibus Disabled N/A N/A Fieldbus or Profibus c. General Configuration Factory Standard Custom Configuration (Unit Data Required from customer) 1 _ _ _ 1 _ _ 2 _ _ 3 _ _ 4 _ _ 5 _ _ 6 _ _ _ S _ _ C ff ff ff ff gg gg TABLE VI Accuracy and Calibration Accuracy NA Standard Standard CALIBRATION & ACCURACY SELECTIONS Calibrated Range Calibration Qty None None Factory Std Single Calibration Custom (Unit Data Required) Single Calibration 3 NAMUR Output Limits 3.8 - 20.5mAdc can be conf igured by the customer or select custom conf iguration Table Vc 0 21 21 A 23 23 B 23 23 32 TABLE VII ACCESSORY SELECTIONS a. Mounting Bracket Bracket Type None Angle Bracket Angle Bracket Angle Bracket Marine Approved Bracket Marine Approved Bracket (In Line) Marine Approved Bracket Marine Approved Bracket (In Line) Flat Bracket Flat Bracket Flat Bracket M ate r ial None Carbon Steel 304 SS 316 SS Carbon Steel Carbon Steel 304 SS 304 SS Carbon Steel 304 SS 316 SS b. Customer Tag Custom er Tag Type No customer tag One Wired Stainless Steel Tag (Up to 4 lines 26 char/line) Two Wired Stainless Steel Tag (Up to 4 lines 26 char/line) Unassem bled Conduit Plugs & Adapters c. Unassembled No Conduit Plugs or Adapters Required Conduit 1/2 NPT Male to 3/4 NPT Female 316 SS Certified Conduit Adapter Plugs & 1/2 NPT 316 SS Certified Conduit Plug Adapters M20 316 SS Certified Conduit Plug Minifast® 4 pin (1/2 NPT) Minifast® 4 pin (M20) TABLE VIII Certifications & Warranty OTHER Certifications & Options : (String in sequence comma delimited (XX, XX, XX,....) None - No additional options NACE MR0175; MR0103; ISO15156 (FC33338) Process wetted parts only NACE MR0175; MR0103; ISO15156 (FC33339) wetted and non-wetted parts Marine (DNV,ABS,BV,KR,LR) EN10204 Type 3.1 Material Traceability (FC33341) Certificate of Conformance (F3391) Calibration Test Report & Certificate of Conformance (F3399) Certificate of Origin (F0195) FMEDA (SIL 2/3) Certification (FC33337) Over-Pres s ure Leak Tes t Certificate (1.5X MAWP) (F3392) Cert Clean for O2 or CL2 service per ASTM G93 Extended Warranty Additional 1 year Extended Warranty Additional 2 years Extended Warranty Additional 3 years Extended Warranty Additional 4 years Extended Warranty "LifeTim e" Additional 15 years TABLE IX Factory Manufacturing Specials Factory Identification STR800 Smart Pressure Transmitter STR84G & 87G & 84A STR82D & 83D 0 _ _ _ 1 _ _ _ 2 _ _ _ 3 _ _ _ 8 _ _ _ 9 _ _ _ 4 _ _ _ A_ _ _ 5 _ _ _ 6 _ _ _ 7 _ _ _ _ 0 _ _ _ 1 _ _ _ 2 _ _ _ _ A0 _ _ A2 _ _ A6 _ _ A7 _ _ A8 _ _ A9 y y nn nn mm nn mm 00 ** FG F7 ** cc b MT dd FX F3 F1 b F5 FE jj TP OX ee 01 02 03 b 04 15 0 0 0 0 MODEL RESTRICTIONS Restriction Letter Table b d IVa c Id e Ib f g j IVb m IVa n IVa y 2 Ie 3 If 4 I Available Only With Not Available With Selection(s) Table Selection(s) Select only one option from this group C, D,G,H _ _ VIIa 1,2,3,5,6,7 _ _ _ _ _ _ 0, N, B _ _ _ _ 2 _ _ 2 _ _ _ H _ B, D, F, H _ _ A, C, E, G _ _ _ _ _ _ 0 _ _ _ _ _ _ 2 _ _ _ _ _ _ 4 _ _ _ _ _ _ _ 2 _ IVb _ F _ IVb _ H, D _ Vb _ 1,2,6 _ Ic _ _ E _ _ _ _ Ia 2 _ _ _ _ _ _ 2 _ _ 0 _ _ _ 5 II 000000000 VIII FG, F7, FX, OX,TP,MT,F1 6 I 7 8 9 II 10 11 12 If 13 II 15 II 16 I 17 18 19 If 20 _ _ B,D _ _ _ _ _ _ _ AA2_ _ _ _ _ _ AB2_ _ _ _ _ _ _ _ A, G, 2 _ _ _ _ _ _ _ _ 0 _ _ _ _ BF _ _ _ _ _ _ _ BG _ _ _ _ _ _ _ BH _ _ _ _ _ _ _ JF _ _ _ _ _ _ _ JG _ _ _ _ 2 _ _ _ _ _ _ _ _ _ _ _ A,G _ Ia 2 _ _ _ _ _ _ _ _ _ AF _ _ _ _ _ _ _ BF _ _ _ _ _ _ _ BG _ _ _ _ II _ _ _ BH _ _ _ _ _ _ _ GG _ _ _ _ _ _ _ JF _ _ _ _ _ _ _ JG _ _ _ _ VIII FG, F7 II _ _ _ _ _ _ _ _ 0 II _ _ _ _ _ _ _ A_ II _ _ _ _ _ _ _ _ T VIII FG, F7 II _ _ _ JA _ _ _ _ JJG _ _ _ _ _ _ II JKG _ _ _ _ _ _ JLG _ _ _ _ _ _ If _ _ _ _ _ 2 _ 21 I _ _ _ _ 000 22 Ic _ _ E _ _ _ _ 23 II FM ApprovalsSM is a service mark of FM Global Hastelloy® is a registered trademark of Haynes International Monel 400® is a registered trademark of Special Metals Corporation. HART® is a registered trademark of HART Communication Foundation. FOUNDATIONTM Fieldbus is a registered trademark of Fieldbus Foundation. Teflon® is a registered trademark of DuPont. Neobee® is a registered trademark of Stepan Company. Syltherm® 800 is a Trademark of Dow Corning Corporation Klinger® C-4401 is a registered trademark of THERMOSEAL, INC GRAFOIL® is a registered trademarks of GrafTech International Holdings Inc Gylon® 3510 is registered trademark of Garlock Sealing Technologies Tri-Clover Tri-Clamp® is a registered trademark of Alf a-Laval DC® 200 and DC® 704 are registered trademarks of Dow Corning 000000000 34 FIELD INSTALLABLE REPLACEMENT PARTS Description Integrally Mounted Bas ic Indicator Kit (Com patible with all Electronic Modules ) Integrally Mounted Advanced Indicator Kit (Com patible with all Electronic Modules) Terminal Strip w/Lightning Protection Kit for HART or DE Modules Terminal Strip w/Lightning Protection Kit for FFB Module Terminal Strip w/o Lightning Protection for HART or DE Modules Terminal Strip w/o Lightning Protection FFB Module HART Electronics Module HART Electronics Module w/connection for external configuration buttons DE Electronics Module DE Electronics Module w/connection for external configuration buttons FFB Electronics Module Kit FFB Electronics Module w/connection for external configuration buttons PRODUCT MANUALS Description Paper Manual ST 800 Smart Transmitter User Manual - English Paper Manual ST 800 Smart Transmitter HART/DE Communications Manual - English Paper Manual ST 800 Sm art Trans m itter Safety Manual - English Paper Manual ST 800 Smart Transmitter Foundation Fieldbus Manual - English Paper Manual ST 800 Smart Transmitter Function Block Manual - English All product documentation is available at www.honeywellprocess.com. STR800 Smart Pressure Transmitter Kit Number 50049911-501 50049846-501 50075472-532 50075472-534 50075472-531 50075472-533 50049849-501 50049849-502 50049849-503 50049849-504 50049849-507 50049849-508 Part Number 34-ST-25-35 34-ST-25-38 34-ST-25-37 34-ST-25-39 34-ST-25-42 Sales and Service For application assistance, current specifications, ordering, pricing, and name of the nearest Authorized Distributor, contact one of the offices below. ASIA PACIFIC Honeywell Process Solutions, Phone: + 800 12026455 or +44 (0) 1202645583 (TAC) hfs-tacsupport@honeywell.com Australia Honeywell Limited Phone: +(61) 7-3846 1255 FAX: +(61) 7-3840 6481 Toll Free 1300-36-39-36 Toll Free Fax: 1300-36-04-70 China PRC - Shanghai Honeywell China Inc. Phone: (86-21) 5257-4568 Fax: (86-21) 6237-2826 Singapore Honeywell Pte Ltd. Phone: +(65) 6580 3278 Fax: +(65) 6445-3033 South Korea Honeywell Korea Co Ltd Phone: +(822) 799 6114 Fax: +(822) 792 9015 EMEA Honeywell Process Solutions, Phone: + 800 12026455 or +44 (0) 1202645583 Email: (Sales) FP-Sales-Apps@Honeywell.com or (TAC) hfs-tac-support@honeywell.com Web Knowledge Base search engine http://bit.ly/2N5Vldi AMERICAS Honeywell Process Solutions, Phone: (TAC) (800) 423-9883 or (215) 641-3610 (Sales) 1-800-343-0228 Email: (Sales) FP-Sales-Apps@Honeywell.com or (TAC) hfs-tac-support@honeywell.com Web Knowledge Base search engine http://bit.ly/2N5Vldi Specifications are subject to change without notice. For more information To learn more about SmartLine Pressure Transmitters, visit www.honeywellprocess.com Or contact your Honeywell Account Manager Process Solutions Honeywell 1250 W Sam Houston Pkwy S Houston, TX 77042 Honeywell Control Systems Ltd Honeywell House, Skimped Hill Lane Bracknell, England, RG12 1EB Shanghai City Centre, 100 Jungi Road Shanghai, China 20061 www.honeywellprocess.com 34-ST-03-88 October 2020 2020 Honeywell International Inc.Steve Kennedy Adobe PDF Library 15.0