SmartLine Technical Information STR800 SmartLine Remote Diaphragm Seals Specification 34-ST-03-88, October 2020 . Introduction . Part of the SmartLine family of products, the STR800 is a

Download PDF File STR800 SmartLine Remote Diaphragm Seals Specification 34-ST-03-88, October 2020

STR82D-21CC1C0-AFCAA21BS-A-BHS-11C-B-11A0-F1,F5 | Honeywell | STR800 (DP, GP & AP) Remote Seals

STR87G
SmartLine
Technical Information
STR800 SmartLine Remote Diaphragm Seals Specification 34-ST-03-88, October 2020

Introduction

Part of the SmartLine® family of products, the STR800 is a series of high performance pressure transmitters hydraulically matched and optimized with a complete set of remote diaphragm seals. Utilizing the same high performance sensor technology of the ST 800 product line Honeywell has optimized the mechanical and hydraulic designs in order to minimize the typical effects of temperature on remote seal systems. The SmartLine family is also fully tested and compliant with Experion® PKS providing the highest level of compatibility assurance and integration capabilities. SmartLine easily meets the most demanding application needs for pressure measurement applications.

Best in Class Features: · Accuracies of up to 0.0375% of span · Automatic static pressure & temperature compensation · Rangeability up to 100:1 · Multiple local display capabilities · External zero, span, & configuration capability · Polarity insensitive electrical connections · Comprehensive on-board diagnostic capabilities · Integral Dual Seal design for highest safety based on ANSI/NFPA 70-202 and ANSI/ISA 12.27.0 · World class overpressure protection · Full compliance to SIL 2/3 requirements. · Modular design characteristics · Available with additional 15-year warranty
Typical Diaphragm Seal applications · High Process Temperatures
· Viscous or Suspended Solids
· Highly Corrosive Process Materials
· Sanitary Applications
· Applications with Hydrogen Permeation Possibilities
· Level Applications with Maintenance Intensive Wet Legs
· Applications requiring remote Transmitter Mounting
· Tank Applications with Density or Interface Measurements

Figure 1 ­ STR800 Remote Diaphragm Seal Unit

Communications/Output Options: · Honeywell Digitally Enhanced (DE) · HART ® (version 7.0) · FOUNDATIONTM Fieldbus
All transmitters are available with the above listed communications protocols.

Span & Range Limits:

Model

URL

"H2O (mbar)

STR82D

400 (1000)

Model

psid (bar)

STR83D

100 (7.0)

Model

psig (bar)

STR84G

500 (35.0)

STR87G

3000 (210)

Model

psia (bara)

STR84A

500 (35)

LRL "H2O (mbar) -400 (-1000)
psid (bar) -100 (-7.0) psig (bar) -14.7 (-1.0) -14.7 (-1.0) psig (bara)
0 (0)

Min Span "H2O (mbar)
4.0 (10) psid (bar)
1 (0.07) psig (bar)
5 (0.35) 30 (2.1) psig (bara) 5 (0.35)

2

STR800 Smart Pressure Transmitter

Description
The SmartLine family of gauge pressure, differential pressure, and absolute pressure transmitters is designed around a high performance piezo-resistive sensor. This one sensor actually integrates multiple sensors linking process pressure measurement with on-board static pressure (DP Models) and temperature compensation measurements resulting in the best total performance available. This level of performance allows the ST 800 to replace virtually any competitive transmitter available today.
Unique Indication/Display Options The ST 800 modular design accommodates a basic alphanumeric LCD display or a unique advanced graphics LCD display with many unparalleled features.
Basic Alphanumeric LCD Display Features
· Modular (may be added or removed in the field) · 0, 90,180, & 270 degree position adjustments · Configurable (HART only) and standard (Pa, KPa,
MPa, KGcm2, Torr, ATM, inH2O, mH2O, bar, mbar, inH2O, inHG, FTH2O, mmH2O, mm HG, & psi) measurement units · 2 Lines 16 Characters (4.13H x 1.83W mm) · Square root output indication ()
Advanced Graphics LCD Display Features
· Modular (may be added or removed in the field) · 0, 90, 180, & 270 degree position adjustments · Standard and custom measurement units available. · Up to eight display screens with 3 formats are
possible · (Large PV with Bar Graph or PV with Trend Graph) · Configurable screen rotation timing · Display Square Root capabilities may be set
separately from the 4-20mA dc output signal · Unique "Health Watch" indication provides instant
visibility of diagnostics · Multiple language capability. (EN, DE, FR, IT, ES,
RU, TR, CN, JP)
Diagnostics SmartLine transmitters all offer digitally accessible diagnostics which aid in providing advanced warning of possible failure events minimizing unplanned shutdowns, providing lower overall operational costs

Configuration Tools Integral Three Button Configuration Option Suitable for all electrical and environmental requirements, SmartLine offer the ability to configure the transmitter and display via three externally accessible buttons when either display option is selected. Zero/span capabilities are also optionally available via these buttons with or without selection of a display option.
Hand Held Configuration SmartLine transmitters feature two-way communication and configuration capability between the operator and the transmitter. All Honeywell transmitters are designed and tested for compliance with the offered communication protocols and are designed to operate with any Standards compliant handheld configuration device.
Personal Computer Configuration Honeywell's SCT 3000 Configuration Toolkit provides an easy way to configure Digitally Enhanced (DE) instruments using a personal computer as the configuration interface. Field Device Manager (FDM) Software and FDM Express are also available for managing HART & Fieldbus device configurations.
System Integration o SmartLine communications protocols all meet the most
current published standards for HART/DE/Fieldbus. o Integration with Honeywell's Experion PKS offers the
following unique advantages. o Transmitter messaging o Maintenance mode indication o Tamper reporting o FDM Plant Area Views with Health summaries o All ST 800 units are Experion tested to provide the
highest level of compatibility assurance
Modular Design To help contain maintenance & inventory costs, all STR800 transmitters are modular in design supporting the user's ability to replace or add indicators, terminal connections or electronic modules without affecting overall performance or approval body certifications
Modular Features o Exchange/replace electronics/comms modules* o Add or remove integral indicators* o Add or remove lightning protection (terminal connection)*
* Field replaceable in all electrical environments (including IS) except flameproof without violating agency approvals.
With no performance effects, Honeywell's unique modularity results in lower inventory needs and lower overall operating costs.

STR800 Smart Pressure Transmitter

3

Performance Specifications
Reference Accuracy (conformance to +/-3 Sigma)

Model STR82D STR83D STR84G STR87G STR84A

URL

LRL

Min Span

400 in H2O (1000 mbar) 100 psid (7.0 bar) 500 psi (35 bar) 3000 psi (210 bar) 500 psia (35 bara)

-400 in H2O (-1000 mbar) -100 psi (-7.0 bar) -14.7 (-1.0 bar) -14.7 psi (-1.0 bar) 0 psia (0 bara)

4 in H2O (10 mbar) 1 in psi (0.07 bar)
5 psi (0.35 bar) 30 psi (2.1 bar) 5 psia (0.35 bara)

Maximum Turndown
Ratio
100:1 100:1 100:1 100:1 100:1

Reference Accuracy1,2
(% Span)
0.0375 0.0375 0.0375 0.0375 0.0375

Zero and span may be set anywhere within the listed (URL/LRL) range limits

Accuracy at Specified Span, Temperature and Static Pressure: (conformance to +/-3 Sigma)

Standard Accuracy

Accuracy1,2 (% of Span)

Model
STR82D STR83D STR84G STR87G STR84A

URL
400 in H2O (1000mbar) 100 psid (7.0 bar) 500 psi (35 bar) 3000 psi (210 bar) 500 psia (35 bara)

Reference A Turndown

C B (see URL
units)

8:1
3.33:1 25:1 10:1 25:1

0.005

0.0325

50 (125)
30 (2.1) 20 (1.4) 300 (2.1) 20 (1.4)

Turn Down Effect

Combined Zero & Span Temperature Effect3 (% Span/ 28oC (50oF))

F

D

E

(see URL

units)

0.175 0.025

1.000 0.280

200 (500) 30 (2.1)

Temp Effect

Total Performance (% of Span):
Total Performance = +/- ( Accuracy)2 + (Temp Effect)2

Total Performance Examples: (standard accuracy, 5:1 Turndown, up to 50 oF shift)

STR82D @ 80"H2O: 2.68% of span

STR83D @ 20 psid: 0.45% of span

Typical Calibration Frequency: Calibration verification is recommended every four (4) years

Notes:
1.Terminal Based Accuracy ­ Includes combined effects of linearity, hysteresis, and repeatability. Analog output adds 0.005% of span. 2. For zero based spans and reference conditions of 25oC (77oF). 0 psi static pressure for DP, >= 0 psia for GP, 10 to 55% R.H, and 316 Stainless Steel barrier diaphragms
3. Specification applies to transmitter with 2 balanced remote seals. Apply a 1.5 factor for temperature effect for capillary lengths greater
than 10 feet.

4

STR800 Smart Pressure Transmitter

Operating Conditions ­ All Models

Parameter

Reference Condition (at zero static)

Rated Condition

Operative Limits Transportation and Storage

Ambient Temperature1

°C

°F

°C

25±1

77±2

-

°F

°C

°F

°C

°F

-

-

-

-55 to 90 -67 to 194

Humidity

%RH

10 to 55

0 to 100

0 to 100

0 to 100

Vacuum Region, Minimum Pressure
mmHg absolute

Atmospheric (See Figure 4 for vacuum limitation)

Supply Voltage, Current, and Load Resistance

10.8 to 42.4 Vdc at terminals (IS versions limited to 30 Vdc) 0 to 1,440 ohms (as shown in Figure 2)

Maximum Allowable Working Pressure (MAWP)4
(ST 800 products are rated to Maximum Allowable Working Pressure. MAWP depends on Approval Agency and transmitter materials of construction.)

MAWP is minimum of Body Rating or Seal Rating (See Model Selection Guide for Seal

Body STR82D

MAWP 2,500 psig (172 bar) Bolted Process Heads

STR83D

2,500 psig (172 bar) Bolted Process Heads

STR82D

1,450 psig (100 bar) All Welded Process

STR83D

1,450 psig (100 bar) All Welded Process

STR84G

500 psig (35 bar)

STR87G

3,000 psig (207 bar)

STR84A

500 psia (35 bara)

1 Ambient Temperature Limit is a function of Process Interface Temperature and fill fluid. (See Figure 3 & Figure 4)

LCD Display operating temperature -20°C to +70°C . Storage temperature -30°C to 80°C 4 Consult factory for MAWP of ST 800 transmitters with CRN approval.

Figure 2 - Supply voltage and loop resistance

STR800 Smart Pressure Transmitter

5

Maximum Ambient Temperature (°F)

200

185

180

165

160

140

140

120

100

80

60

40

20

0

200

350

450

Process Interface Temperature (°F)

Figure 3 - Ambient temperature limits

Figure 4 - STR800 Remote Seals operable limits for pressure vs. temperature

6

STR800 Smart Pressure Transmitter

Performance Under Rated Conditions ­ All Models

Parameter

Description

Analog Output

Two-wire, 4 to 20 mA (HART & DE Transmitters only)

Digital Communications:

Honeywell DE, HART 7 protocol or FOUNDATION Fieldbus ITK 6.0.1 compliant

All transmitters, irrespective of protocol have polarity insensitive connection.

HART & DE Output Failure Modes
(NAMUR for DE Units requires selecting display and configuration buttons or factory configuration)

Compliance: Normal Limits: Failure Mode:

Honeywell Standard:
3.8 ­ 20.8 mA  3.6 mA and  21.0 mA

NAMUR NE 43
3.8 ­ 20.5 mA  3.6 mA and  21.0 mA

Supply Voltage Effect

0.005% span per volt.

Transmitter Turn on Time (includes power up & test algorithms)

HART or DE: 2.5 sec.

Foundation Fieldbus: Host dependant

Damping Time Constant

HART: Adjustable from 0 to 32 seconds in 0.1 increments. Default: 0.50 seconds DE: Discrete values 0, .16, .32, .48, 1, 2, 4, 8, 16, 32 seconds. Default: 0.48 seconds

Electromagnetic Compatibility IEC 61326-3-1

Lightning Protection Option

Leakage Current: 10uA max @ 42.4VDC 93C

Impulse rating: 8/20uS

5000A (>10 strikes)

10/1000uS 200A (> 300 strikes)

10000A (1 strike min.)

Materials Specifications (see Model Selection Guide for availability/restrictions with various

models)

Parameter

Description

Process Interface

See Model Selection Guide for Material Options for desired seal type.

Seal Barrier Diaphragm 316L Stainless Steel, Monel®, Hastelloy® C, Tantalum

Seal Gasket Materials Klinger C-4401 (non-asbestos), Grafoil®, Teflon®, Gylon 3510®

Mounting Bracket

Carbon Steel (Zinc-Chromate plated) or 304 Stainless Steel or 316 Stainless Steel

Fill Fluid (Meter Body)

Silicone 200 CTFE (Chlorotrifluoroethylene) Silicone 704 NEOBEE M-20®

S.G. @ 25°C = 0.94 S.G. @ 25°C = 1.89 S.G. @ 25°C = 1.07 S.G. @ 25°C = 0.93

Fill Fluid (Secondary)

Silicone Oil 200
CTFE (Chlorotrifluoroethylene)
Silicone Oil 704 Syltherm 800® NEOBEE M-20®

S.G. @ 25°C = 0.94 S.G. @ 25°C = 1.89 S.G. @ 25°C = 1.07 S.G. @ 25°C = 0.90 S.G. @ 25°C = 0.93

Electronic Housing

Pure Polyester Powder Coated Low Copper (<0.4%)-Aluminum. Meets NEMA 4X, IP66, & P67. All stainless steel housing is optional.

Capillary Tubing

Material: Armored Stainless Steel or PVC Coated Armored Stainless Steel. Length: 5, 10, 15, 20, 25, and 35 feet (1.5, 3, 4.6, 6.1, 7.5, and 10.7 meters). A 2 inch (51 millimeter) S.S. close-coupled nipple is also available. See Model Selection Guide. Refer to Note: The minimum span is the higher of the higher of the value from the table above or the value defined under the Performance Conditions for the range transmitter.

Figure 5 for guide to maximum capillary length vs. diaphragm diameter.

Wiring

Accepts up to 16 AWG (1.5 mm diameter)

Mounting

See Figure 6

Dimensions

Transmitter: See Figure 7 and Figure 8. Seal: See Figure 9 through Figure 17

Net Weight

Transmitter: 8.3 pounds (3.8 Kg). With Aluminum Housing. Total weight is dependent on seal

NOTE: Pressure transmitters that are part of safety equipment for the protection of piping (systems) or vessel(s) from exceeding allowable pressure limits, (equipment with safety functions in accordance with Pressure Equipment Directive 97/23/EC article 1, 2.1.3), require separate examination.

STR800 Smart Pressure Transmitter

7

Minimum recommended span for STR82D and STR83D Transmitter with two Remote Seals

Diaphragm

Capillary Length (Feet)

Size (Inches)

5

10

15

20

25

35

2.4

7.2 psi

2.9

3.6 psi

4.5 psi

5.4 psi

6.3 psi

3.5

0.6 psi

0.7 psi

0.9 psi

1.0 psi

1.2 psi 1.4 psi

4.1

0.4 psi

0.5 psi

0.6 psi

0.8 psi

0.9 psi 1.1 psi

Maximum Capillary Length (Feet)
5 20 35 35

Minimum recommended span for STR82D and STR83D Transmitter with one Remote Seal

Diaphragm Direct

Capillary Length (Feet)

Size (Inches) Mount

5

10

15

20

25

35

2.4

20 psi 30 psi

2.9

10 psi 15 psi 20 psi

25 psi

30 psi

3.5

1.8 psi 2.9 psi 3.6 psi 4.3 psi 5.0 psi 5.8 psi 7.2 psi

4.1

1.4 psi 2.2 psi 2.9 psi 3.6 psi 4.3 psi 5.0 psi 5.8 psi

Maximum Capillary Length (Feet)
5 20 35 35

Minimum recommended span for STR84G, STR84A and STR87G Transmitter

Diaphragm Direct

Size (Inches) Mount

5

Capillary Length (Feet)

10

15

20

25

Maximum Capillary

35

Length (Feet)

1.9

25 psi 30 psi 40 psi

50 psi

15

2.4

10 psi 15 psi 20 psi

25 psi

30 psi

35 psi

50 psi

35

2.9

8 psi

9 psi

10 psi

11 psi

12 psi

13 psi

15 psi

35

3.5

5 psi

5 psi

5 psi

5 psi

5 psi

6 psi

8 psi

35

4.1

5 psi

5 psi

5 psi

5 psi

5 psi

6 psi

8 psi

35

Note: The minimum span is the higher of the higher of the value from the table above or the value defined under the

Performance Conditions for the range transmitter.

Figure 5 ­ Typical Maximum capillary length and diaphragm size chart

Figure 6 - STR800 transmitter with remote diaphragm seals shown mounted on a tank

8
Reference Dimensions Horizontal Mounting

STR800 Smart Pressure Transmitter

STR800 Smart Pressure Transmitter

9

Reference Dimensions Horizontal Mounting (cont'd)

Figure 7 -- Approximate horizontal mounting dimensions for Remote Seal Transmitter
Reference Dimensions Vertical Mounting

10
Reference Dimensions Vertical Mounting (cont'd)

STR800 Smart Pressure Transmitter

Figure 8 -- Approximate vertical mounting dimensions for Remote Seal Transmitter

STR800 Smart Pressure Transmitter
Reference Dimensions (cont'd)
Flush Flanged Seal Dimensions

11
Figure A Figure B

Figure C

Figure D

Figure 9-- Seal Dimensions (Flush Flanged)

12
Reference Dimensions (cont'd)
Flush Flanged Seal with Lower

STR800 Smart Pressure Transmitter

Flush Flanged Seal with Lower

Flush Flanged Seal with Lower
Nte: 0.90 dimension is 0.70 for 4.1" Dia Diaphragm

Figure 10 -- Seal Dimension (Flush Flanged)

STR800 Smart Pressure Transmitter

13

Reference Dimensions (cont'd)

Flanged Seal with Extended Diaphragm

Pancake Seal

Figure 11 -- Seal Dimensions (Extended Diaphragms)

Figure 12-- Seal Dimensions (Pancake) Chemical Tee "Taylor Wedge" Seal

Figure 13-- Seal Dimensions (Chemical TEE "Taylor Wedge" Seals

14 Seal with Threaded Process Connection

STR800 Smart Pressure Transmitter

Figure 14-- Seal Dimensions (Threaded Process Connection Seals) Sanitary Seal

Figure 15- Seal Dimensions (Sanitary Seals)

STR800 Smart Pressure Transmitter

15

Saddle Seal

Figure 16 -- Seal Dimensions (3" Saddle Seal)

Calibration Ring

Figure 17-- Seal Dimensions (4" Saddle Seal)

Figure 18-- Calibration Ring

16

Communications Protocols & Diagnostics

HART Protocol

Version:

HART 7

Power Supply Voltage: 10.8 to 42.4Vdc at terminals Load: Maximum 1440 ohms See Figure 2. Minimum Load: 0 ohms. (For handheld communications a minimum load of 250 ohms is required) Foundation Fieldbus (FF)

Power Supply Requirements Voltage: 9.0 to 32.0Vdc at terminals Steady State Current: 17.6mAdc Software Download Current: 27.4mAdc

Available Function Blocks

Block Type

Qty

Execution Time

Resource

1

n/a

Transducer

1

n/a

Diagnostic

1

Analog Input

1*

n/a 30 ms

PID w/Autotune

1

Integrator

1

45 ms 30 ms

Signal Char (SC)

1

LCD Display

1

30 ms n/a

Flow Block

1

Input Selector

1

30 ms 30 ms

Arithmetic

1

30 ms

* AI block may have two (2) additional instantiations.

All available function blocks adhere to FOUNDATION

Fieldbus standards. PID blocks support ideal & robust PID

algorithms with full implementation of Auto-tuning.

Link Active Scheduler Transmitters can perform as a backup Link Active Scheduler and take over when the host is disconnected. Acting as a LAS, the device ensures scheduled data transfers typically used for the regular, cyclic transfer of control loop data between devices on the Fieldbus.

Number of Devices/Segment Entity IS model: 6 devices/segment

Schedule Entries 18 maximum schedule entries Number of VCR's: 24 max Compliance Testing: Tested according to ITK 6.0.1

STR800 Smart Pressure Transmitter
Software Download Utilizes Class-3 of the Common Software Download procedure as per FF-883 which allows the field devices of any manufacturer to receive software upgrades from any host. Honeywell Digitally Enhanced (DE) DE is a Honeywell proprietary protocol which provides digital communications between Honeywell DE enabled field devices and Hosts. Power Supply Voltage: 10.8 to 42.4Vdc at terminals Load: Maximum 1440 ohms See Figure 2. Standard Diagnostics ST 800 top level diagnostics are reported as either critical or non-critical and readable via the DD/DTM tools or integral display as shown below.
Refer to ST 800 diagnostics tech note for additional level diagnostics. Other Certification Options Materials o NACE MRO175, MRO103, ISO15156

Hazardous Areal Certification:

MSG CODE

AGENCY

TYPE OF PROTECTION

COMM. ELECTRICAL AMBIENT TEMP

OPTION PARAMETERS

(Ta)

Explosionproof:

Class I, Division 1, Groups A, B, C, D;

Dust Ignition Proof:

Class II, III, Division 1, Groups E, F, G;

All

T6..T5

Class l, Zone 0/1, AEx db IIC T6..T5 Ga/Gb

Class ll, Zone 21, AEx tb IIIC T95o Db

Note 1

T5: -50 ºC to 85ºC T6: -50 ºC to 65ºC

Intrinsically Safe: Class I, II, III, Division 1, Groups A, B, C, D,

4-20 mA / DE/ HART

Note 2a

-50 ºC to 70ºC

E, F, G: T4

A

FM

Class l, Zone 0, AEx ia IIC T4 Ga

ApprovalsTM FISCO Field Device (Only for FF Option)

USA Ex ia IIC T4 Ga; Ex ic IIC T4 Gc

Foundation Fieldbus

Note 2b

-50 ºC to 70ºC

Nonincendive: Class I, Division 2, Groups A, B, C, D locations, T4 Class l, Zone 2, AEx nA IIC T4 Gc

4-20 mA / DE/ HART/ Foundation Fieldbus

Note 1

-50 ºC to 85ºC

Enclosure: Type 4X/ IP66/ IP67

All

All

-

STANDARDS: FM Class 3600:2011; FM Class 3610: 2010; FM Class 3611: 2004; FM Class 3615: 2006; FM Class 3616: 2011; FM Class 3810: 2005; ANSI/ISA 60079-0: 2013; ANSI/UL 60079-1: 2015; ANSI/UL 60079-11: 2014; ANSI/ISA 60079-15: 2012; ANSI/UL 60079-26: 2017; ANSI/UL 60079-31: 2015; ANSI/NEMA 250: 2003; ANSI/ IEC 60529: 2004

Explosion Proof: Class I, Division 1, Groups A, B, C, D; Class II, Division 1, Groups E, F, G; Class III, Division 1, T6..T5 Class I Zone 1 AEx db IIC T6..T5 Ga/Gb Ex db IIC T6..T5 Ga/Gb Zone 22 AEx tb IIIC T95o Db Ex tb IIIC T95o Db

All

Note 1

T5: -50oC TO 85oC T6: -50oC TO 65oC

Intrinsically Safe: Class I, II, III, Division 1, Groups A, B, C, D; Class II, Division 1, Groups E, F, G;

4-20 mA / DE/ HART

Note 2

Canadian Class III, Division 1, T4

Standards Class I Zone 0, AEx ia IIC T4 Ga

B

Association (CSA)
USA and Canada

Class I Zone 2, AEx ic IIC T4 Gc Ex ia IIC T4 Ga Ex ic IIC T4 Gc FISCO Field Device (Only for FF Option)

Foundation Fieldbus

Note 2

Ex ia IIC T4 Ga;

Ex ic IIC T4 Gc

-50oC TO 70oC -50oC TO 70oC

Nonincendive: Class I, Division 2, Groups A, B, C, D; Class II, Division 2, Groups F, G; Class III, Division 2, T4 Class I Zone 2 AEx nA IIC T4 Gc Ex nA IIC T4 Gc

4-20 mA / DE/ HART/ Foundation Fieldbus

Note 1

-50oC to 85oC

Enclosure: Type 4X/ IP66/ IP67

All

All

-

STANDARDS: CSA C22.2 No. 0-10; CSA C22.2 No. 94-M91; CSA C22.2 No. 25-1966; CSA C22.2

MSG CODE
C
D

AGENCY
ATEX
IECEx World

TYPE OF PROTECTION

COMM. ELECTRICAL AMBIENT TEMP

OPTION PARAMETERS

(Ta)

No. 30-M1986; CSA C22.2 No. 142-M1987; CSA C22.2 No. 157-92; CSA C22.2 No. 213-M1987; CSA-C22.2 No. 60529:05; CSA-C22.2 No. 60079-0:11; CSA-C22.2 No. 60079-1:11; CSA-C22.2 No. 60079-11:11; CSA-C22.2 No. 60079-15:12; CSA-C22.2 No. 60079-31:12; ISA 12.12.012010; ISA 60079-0: 2009; ISA 60079-11: 2011; ISA 60079-15: 2009; ISA 60079-26: 2008; ISA60079-27:2007 (12.02.04)-2006 (R2011); UL 913 Ed. 6; UL 916:1998; ANSI/ISA-12.27.01-2011

Flameproof: SIRA 12ATEX2233X II 1/2 G Ex db IIC T6..T5 Ga/Gb II 2 D Ex tb IIIC T95oC...T120oC Db

All

Note 1

T5: -50oC TO 85oC T6: -50oC TO 65oC

Intrinsically Safe: SIRA 12ATEX2233X II 1 G Ex ia IIC T4 Ga FISCO Field Device (Only for FF Option) II 1 G Ex ia IIC T4 Ga

4-20 mA / DE/ HART
Foundation Fieldbus

Note 2 Note 2

-50oC TO 70oC -50oC TO 70oC

Zone 2, Increase Safety: SIRA 12ATEX4234X II 3 G Ex ec IIC T4 Gc

4-20 mA / DE/ HART/

Note 1

-50oC TO 85oC

Zone 2, Intrinsically Safe: SIRA 12ATEX4234X II 3 G Ex ic IIC T4 Gc FISCO Field Device (Only for FF Option) II 3 G Ex ic IIC T4 Gc

4-20 mA / DE/ HART/
Foundation Fieldbus

Note 2

-50oC TO 85oC

Enclosure: IP66/ IP67

All

All

-

STANDARDS: EN 60079-0: 2012/A11: 2013; EN 60079-1: 2014; EN 60079-7: 2015; EN 6007911: 2012; EN 60079-26: 2015; EN 60079-31: 2009

Flameproof: IECEx SIR 12.0100X
Ex db IIC T6..T5 Ga/Gb Ex tb IIIC T95oC...T120oC Db

All

Note 1

T5: -50oC TO 85oC T6: -50oC TO 65oC

Intrinsically Safe: IECEx SIR 12.0100X Ex ia IIC T4 Ga FISCO Field Device (Only for FF Option) Ex ia IIC T4 Ga; Ex ic IIC T4 Gc

4-20 mA / DE/ HART
Foundation Fieldbus

Note 2 Note 2

-50oC TO 70oC -50oC TO 70oC

Zone 2, Increase Safety: IECEx SIR 12.0100X Ex ec IIC T4 Gc

4-20 mA / DE/ HART/
Foundation Fieldbus

Note 1

-50oC TO 85oC

Zone 2, Intrinsically Safe: IECEx SIR 12.0100X Ex ic IIC T4 Gc FISCO Field Device (Only for FF Option) Ex ic IIC T4 Gc

4-20 mA / DE/ HART/
Foundation Fieldbus

Note 2

-50oC TO 85oC

Enclosure: IP66/ IP67

All

All

-

STANDARDS: IEC 60079-0: 2011; IEC 60079-1: 2014; IEC 60079-7: 2017; IEC 60079-11: 2011; IEC 60079-26: 2014; IEC 60079-31: 2013

Flameproof : Ex d IIC T6...T5 Ga/Gb Ex tb IIIC T95oC...T120oC Db

All

Note 1

T5: -50oC TO 85oC T6: -50oC TO 65oC

Intrinsically Safe: Ex ia IIC Ga T4 FISCO Field Device (Only for FF Option) Ex ia IIC T4 Ga; Ex ic IIC T4 Gc

4-20 mA / DE/ HART
Foundation Fieldbus

Note 2 Note 2

E

SAEx

Zone 2, Increase Safety:

South Africa II 3 G Ex ec IIC T4 Gc

4-20 mA / DE/ HART/
Foundation Fieldbus

Note 1

-50oC TO 70oC -50oC TO 70oC -50oC TO 85oC

Zone 2, Intrinsically Safe: Ex ic IIC T4 Gc FISCO Field Device (Only for FF Option) Ex ic IIC T4 Gc

4-20 mA / DE/ HART/
Foundation Fieldbus

Note 2

-50oC TO 85oC

Enclosure: IP66/ IP67

All

All

-

Flameproof: Ex db IIC T6..T5 Ga/Gb Ex tb IIIC T95oC...T120oC Db

All

Note 1

T5: -50oC TO 85oC T6: -50oC TO 65oC

Intrinsically Safe: Ex ia IIC T4 Ga

4-20 mA / DE/ HART

Note 2a

-50oC TO 70oC

INMETRO

FISCO Field Device (Only for FF Option) Ex ia IIC T4 Ga; Ex ic IIC T4 Gc

Foundation Fieldbus

Note 2b

-50oC TO 70oC

F

Brazil

Zone 2, Increase Safety:

II 3 G Ex ec IIC T4 Gc

4-20 mA / DE/ HART/
Foundation

Note 1

-50oC TO 85oC

Fieldbus

Zone 2, Intrinsically Safe: Ex ic IIC T4 Gc FISCO Field Device (Only for FF Option) Ex ic IIC T4 Gc

4-20 mA / DE/ HART/
Foundation Fieldbus

Note 2

-50oC TO 85oC

Enclosure : IP 66/67

All

All

-

Flameproof:
Ex db IIC T6..T5 Ga/Gb Ex tb IIIC T 95oC Db

All

Note 1

T5: -50oC TO 85oC T6: -50oC TO 65oC

Intrinsically Safe: Ex ia IIC T4 Ga FISCO Field Device (Only for FF Option) Ex ia IIC T4 Ga; Ex ic IIC T4 Gc

4-20 mA / DE/ HART
Foundation Fieldbus

Note 2 Note 2

-50oC TO 70oC -50oC TO 70oC

G

NEPSI CHINA

Zone 2, Increase Safety: II 3 G Ex ec IIC T4 Gc

4-20 mA / DE/ HART/
Foundation Fieldbus

Note 1

-50oC TO 85oC

Zone 2, Intrinsically Safe: Ex ic IIC T4 Gc FISCO Field Device (Only for FF Option) Ex ic IIC T4 Gc

4-20 mA / DE/ HART/
Foundation Fieldbus

Note 2

-50oC TO 85oC

Enclosure : IP 66/67

All

All

-

Flameproof :

Ex d IIC T4, T5, T6

All

Ex tD A21 IP66/IP67 T95oC...T120 oC

H

KOSHA Korea

Intrinsically Safe:

Ex ia IIC T4

4-20 mA / DE/ HART
Foundation Fieldbus

Enclosure: IP66/ IP67

All

Flameproof:

Ga/Gb Ex d IIC T6..T5

All

Ex tb IIIC Db T 85oC

Intrinsically Safe:

Ga Ex ia IIC T4 X

FISCO Field Device

(Only for FF Option)

EAC

Ga Ex ia IIC T4 X

I

Russia, Belarus and
Kazakhstan

Zone 2, Non Sparking: 2 Ex nA IIC T4 Gc X

4-20 mA / DE/ HART
Foundation Fieldbus
4-20 mA / DE/ HART/ Foundation Fieldbus

Zone 2, Intrinsically Safe: Ga Ex ic IIC T4 X FISCO Field Device (Only for FF Option) 2 Ex ic IIC T4 Gc X

4-20 mA / DE/ HART/ Foundation Fieldbus

Enclosure : IP 66/67

All

Flameproof: Ex d IIC T6..T5 Ga/Gb

All

Intrinsically Safe: Ex ia IIC T4 Ga

4-20 mA / DE/ HART

J

CCoE INDIA

FISCO Field Device (Only for FF Option) Ex ia IIC T4 Ga; Ex ic IIC T4 Gc

Foundation Fieldbus

Non Sparking

4-20 mA / DE/

Ex nA IIC T4 Gc

HART/

Foundation

Fieldbus

Enclosure: IP66/ IP67

All

Flameproof:

II 1/2 G Ex db IIC T6..T5 Ga/Gb

All

II 2 D Ex tb IIIC T95oC...T120oC Db

K

UATR UKRAINE

Intrinsically Safe: II 1 G Ex ia IIC T4 Ga

4-20 mA / DE/ HART

FISCO Field Device (Only for FF Option) II 1 G Ex ia IIC T4 Ga

Foundation Fieldbus

Enclosure: IP66/ IP67

All

Notes:

1. Operating Parameters:

Voltage= 11 to 42 V DC

Current= 4-20 mA Normal

= 10 to 30 V (FF)

= 30 mA (FF)

Note 1 Note 2 Note 2
All Note 1 Note 2 Note 2
Note 1
Note 2
All Note 1 Note 2 Note 2
Note 1 All
Note 1 Note 2 Note 2
All

T4: -50oC TO 85oC T5: -50oC TO 85oC T6: -50oC TO 65oC Ta= -50 ºC to 70ºC Ta= -50 ºC to 70ºC
T5: -50oC TO 85oC T6: -50oC TO 65oC
-50oC TO 70oC -50oC TO 70oC
-50oC TO 85oC
-50oC TO 85oC
T5: -50oC TO 85oC T6: -50oC TO 65oC
-50oC TO 70oC -50oC TO 70oC
-50oC TO 85oC
T5: -50oC TO 85oC T6: -50oC TO 65oC
-50oC TO 70oC -50oC TO 70oC
-

2. Intrinsically Safe Entity Parameters

a. Analog/ DE/ HART Entity Values:

Vmax= Ui = 30V

Imax= Ii= 105mA

Ci = 4.2nF

Li =984 uH

Pi =0.9W

Transmitter with Terminal Block Revision E or Later

Vmax= Ui = 30V

Imax= Ii= 225mA

Ci = 4.2nF

Li = 0

Pi =0.9W

Note : Transmitter with Terminal Block Revision E or later

The revision is on the label that is on the module. There will be two lines of text on the label:

· First is the Module Part #: 50049839-001 or 50049839-002

· Second line has the supplier information, along with the REVISION:

XXXXXXX-EXXXX, THE "X" is production related, THE POSITION of the "E" IS THE REVISION.

b. Foundation Fieldbus- Entity Values

Vmax= Ui = 30V

Imax= Ii= 180mA

Ci = 0nF

Li = 984 uH

Pi =1W

Transmitter with Terminal Block Revision F or Later

Vmax= Ui = 30V

Imax= Ii= 225mA

Ci =0nF

Li = 0

Pi =1 W

FISCO Field Device

Imax= Ii= 380 mA

Ci = 0nF

Li = 0

Pi =5.32 W

Vmax= Ui = 17.5V

Note : Transmitter with Terminal Block Revision F or later

The revision is on the label that is on the module. There will be two lines of text on the label:

· First is the Module Part #: 50049839-003 or 50049839-004

· Second line has the supplier information, along with the REVISION:

XXXXXXX-EXXXX, THE "X" is production related, THE POSITION of the "E" IS THE REVISION

. Approval Certifications:

This certificate defines the certifications covered for the SmartLine Pressure Transmitter family of

products, including the SMV SmartLine Multivariable Transmitter. It represents the compilation of

the five certificates Honeywell currently has covering the certification of these products into marine

applications.

American Bureau of Shipping (ABS) - 2009 Steel Vessel Rules 1-1-4/3.7, 4-6-2/5.15, 4-8-3/13 &

Marine Certificates

13.5, 4-8-4/27.5.1, 4-9-7/13. Certificate number: 04-HS417416-PDA Bureau Veritas (BV) - Product Code: 389:1H. Certificate number: 12660/B0 BV

Det Norske Veritas (DNV) - Location Classes: Temperature D, Humidity B, Vibration A, EMC B,

Enclosure C. For salt spray exposure; enclosure of 316 SST or 2-part epoxy protection with 316

SST bolts to be applied. Certificate number: A-11476

Korean Register of Shipping (KR) - Certificate number: LOX17743-AE001

Lloyd's Register (LR) - Certificate number: 02/60001(E1) & (E2)

SIL 2/3 Certification IEC 61508 SIL 2 for non-redundant use and SIL 3 for redundant use according to EXIDA and TÜV

Nord Sys Tec GmbH & Co. KG under the following standards: IEC61508-1: 2010; IEC 61508-2:

MEASUREMENT INTRUMENTS DIRECTIVE (MID) 2004/ 22/ EC

2010; IEC61508-3: 2010.

Certificate Issued by NMI Certin B.V.

Mechanical Class: M3

Electromagnetic Environment: E3

Ambient Temperature Range: -25 oC to + 55 oC

Unit

Custom Calibration

STD820

0 to 1000 mBar

STD830

0 to 7 Bar

STA84L

0 to 35 Bar A

STG84L

0 to 35 Bar

STD870

0 to 100 Bar

STA87L

0 to 100 Bar A

STG87L

0 to 100 Bar

Application Data
Liquid Level: Closed Tank Determine the minimum and maximum pressure differentials to be measured (Figure 19). PMin = (SGp x a) - (SGf x d)
= LRV when HP at bottom of tank = ­URV when LP at bottom of tank PMax = (SGp x b) - (SGf x d) = URV when HP at bottom of tank = ­LRV when LP at bottom of tank Where: minimum level at 4mA maximum level at 20 mA a = distance between bottom tap and minimum level b = distance between bottom tap and maximum level d = distance between taps SGf = Specific Gravity of capillary fill fluid (See Page 6 "Material Specifications" for values.) SGp = Specific Gravity of process fluid
Figure 19--Closed tank liquid level measurement distance

Application Data (Cont'd)
Density or Interface* Calculate the minimum and maximum pressure differentials to be measured (Figure 20).
Pmin = (SGmin ­ SGf) x (d); minimum density, 4mA output
Pmax = (SGmax ­ SGf) x (d); maximum density, 20mA output
Where:
d = distance between the taps
SGmax = maximum Specific Gravity
SGmin = minimum Specific Gravity

SGf = Specific Gravity of capillary fill fluid (See Page 6 "Material Specifications" for values.)

Figure 20--Density, direct acting transmitter configuration
Seal Configurations
.

Figure 21--Flush Flange Seals and with left lower
Flush Flange Seals can be used with differential, gauge and absolute pressure transmitters and are available with 3" ANSI Class 150, ANSI Class 300 and DIN DN80-PN40 process connections. Flush flange seals can also be provided with Lowers. Lowers are essentially calibration rings, which allow flushing connections if needed.

Figure 23--Pancake Seals Pancake Seals can be used with differential, gauge and absolute pressure transmitters and are available with 3" ANSI Class 150, 300 and 600 process connections.

Figure 22-- Flange Seal with Extended Diaphragm
Flange Seal with Extended Diaphragm can be used with differential, gauge and absolute pressure transmitters and are available with 3" and 4" ANSI Class 150, ANSI Class 300, DIN DN80-PN40 and DIN DN100-PN40 process connections. 2", 4" and 6" extension lengths are available

Figure 24-- Chemical Tee "Taylor" Wedge Chemical Tee "Taylor" Wedge can be used with differential pressure transmitters and are available with Taylor Wedge 5" O.D. process connection.

Seal Configurations (cont'd)

Figure 25-- Seals with Threaded Process Connections
Seals with Threaded Process Connections can be used with differential, gauge and absolute pressure transmitters and are available with ½", ¾" and 1" NPT Female process connections.

Figure 29-- Stainless Steel Armor and PVC Coated Stainless Steel Armor Capillaries
Stainless Steel Armor and PVC Coated Stainless Steel Armor Capillaries are available with Honeywell Remote Seal Solutions.

Figure 26-- Sanitary Seals Sanitary Seals can be used with differential, gauge and absolute pressure transmitters and are available with 3" and 4" Tri-Clover-Tri-Clamp process connections.

Figure 30-- 2" Stainless Steel Nipples 2" Stainless Steel Nipples are available for CloseCoupled remote seal solutions

Figure 27-- Saddle Seals Saddle Seals can be used with differential, gauge and absolute pressure transmitters and are available with 3" and 4" (6 bolt or 8 bolt designs) process connections.

Figure 31-- Welded Meter Body for All-Welded Remote Seal Solution
Welded Meter Body for All-Welded Remote Seal Solution. The welded ST 800 meter body is an important part of an All-Welded Remote Seal Solution, which is commonly used in Vacuum applications.

Figure 28-- Calibration Rings Calibration Rings are available with Flush Flange Seals and Pancake Seals. Flushing ports (1/4" or ½") are available with calibration rings.

Model Selection Guide
Model Selection Guides are subject to change and are inserted into the specifications as guidance only.

Model STR800 (DP, GP & AP) Remote Seals

Model Selection Guide
34-ST-16-88 Issue 26

Instructions  Select the desired Key Number. The arrow to the right marks the selection available.  Make selections from each Table (I, II and IX) using the column below the proper arrow .  A () denotes unrestricted availability. A letter denotes restricted availability.  Restrictions follow Table IX.

Key Number STR _ _ _

I

II

III

IV

V

VI

VII

VIII

- _______ - _________ - _ - ___ - ___ - _ - ____ - __ +

IX 0 0 0 0

KEY NUMBER
Measurement Range Std Accuracy

URL 400 (1000)
100 (7) 500 (35) 500 (35) 3000 (210)

LRL -400 (-1000)
-100 (-7) 5.7 (0.39) -14.7 (-1.0) 14.7 (-1.0)

Max Span 400 (1000)
100 (7) 500 (35) 500 (35) 3000 (210)

Min Span 4 (10) 1 (0.07) 5 (0.35) 5 (0.35) 30 (2.1)

Units " H2O (mbar)
psi (bar) psia (bar A)
psi (bar) psi (bar)

Note: Remote seal system pressure rating is body rating or seal rating, w hichever is less.

Selection STR82D STR83D STR84A STR84G STR87G

TABLE I

Description

a. Number of Seals
b. Primary Fill Fluid
(Meter body)

1 Remote Seal (High Side) 2 Remote Seals
1 Remote Seal (Low Side) Silicone Oil 200
Fluorinated Oil CTFE
Silicone Oil 704 NEOBEE® M-20 11

c. Construction

Non-Wetted Adapter Head Materials

In-Line Gauge/ Absolute
Dual Head DP

316 SS Bonnet 316 SS Bonnet for Close-Couple
316 SS (bolt-on heads) 316 SS for Close-Couple 316 SS with all-welded meter body

None

d. Bolts and Nuts

Carbon Steel Bolts and Nuts

for Transmitter

316 SS Bolts and Nuts

Heads

A286 SS (NACE) Bolts and 304 SS (NACE) Nuts

B7M (NACE) Bolts and 7M (NACE) Nuts

Meter Body & Capillaries

No Fill Fluid

e. Secondary Fill Fluid (capillary &
seal)**

Silicone Oil 200 Fluorinated Oil CTFE
Silicone Oil 704 Neobee® M20 11

Syltherm® 800 12

No Capillary, No Nipple (Specify for VAM Unit Only)

5 feet

1.5 m

10 feet 3.0 m

f. Connection

15 feet 20 feet 25 feet

4.5 m 6.1 m 7.5 m

SS Armor

of Remote

Capillary 35 feet 10.7 m

Seal to Meter Length

5 feet

1.5 m

Body**

10 feet 15 feet

3.0 m 4.5 m

PVC Coated SS

20 feet 6.1 m

Arm or

25 feet 7.5 m

35 feet 10.7 m

2 inch long SS nipple close-coupled

None

g. Seal Option** Std Gold Plated Seal Diaph. = 50 µin

Teflon Coated Seal Diaphragm - only for anti-sticking ** Refer to 34-ST-00-128 for additional options, consult factory 11 Limited vacuum availability. 12 Minimum static pressure requirement. No vacuum allow ed. See Specifications 34-ST-03-88 Figure 15

Selection 1 _ _ _ _ _ _ 2 _ _ _ _ _ _ 3 _ _ _ _ _ _ _ 1 _ _ _ _ _ _ 2 _ _ _ _ _
_ 3 _ _ _ _ _
_ 4 _ _ _ _ _
_ _ A_ _ _ _ _ _ B _ _ _ _ _ _ C _ _ _ _ _ _ D _ _ _ _ _ _ E _ _ _ _ _ _ _ 0 _ _ _
_ _ _ C _ _ _
_ _ _ S _ _ _
_ _ _ N _ _ _
_ _ _ B _ _ _ _ _ _ _ 0 _ _ _ _ _ _ 1 _ _ _ _ _ _ 2 _ _ _ _ _ _ 3 _ _ _ _ _ _ 4 _ _ _ _ _ _ 5 _ _ _ _ _ _ _ 0 _ _ _ _ _ _ A_ _ _ _ _ _ B _ _ _ _ _ _ C _ _ _ _ _ _ D _ _ _ _ _ _ E _ _ _ _ _ _ F _ _ _ _ _ _ G _ _ _ _ _ _ H _ _ _ _ _ _ J _ _ _ _ _ _ K _ _ _ _ _ _ L _ _ _ _ _ _ M_ _ _ _ _ _ 2 _ _ _ _ _ _ _ 0 _ _ _ _ _ _ 1 _ _ _ _ _ _ 4

Availability
    22  
 3  3 4 22      55      55             66  77 77

26

STR800 Smart Pressure Transmitter

In-Line Gauge

Dual Head DP

Note: When selecting required seal, you must specify only the 9 selections within the required s eal type.

TABLE II Seals

Description

No Seal Attached to Core Transm itter (Specify for VAM Unit Only)

Seal Type

Diaphragm Diameter

Flange Size

Flange Pressure Rating 1

3" 3.5"
80mm

ANSI Class 150 ANSI Class 300 DIN DN80-PN40

Diaphragm

Upper Insert

Wetted Material
Non-Wetted Material (upper)

316L SS Hastelloy® C-276 Hastelloy® C-276

316L SS
316L SS Hastelloy® C-276

Monel 400® Tantalum 5

Monel 400® 316L SS

CS (Nickel Plated)

316L SS

Flush Flanged Seal**

Seal-Capillary Connection
Calibration Rings

Flus hing

Center Seal Side Seal
None 316L SS Hastelloy® C-276 Monel 400®
None

Connections and Plugs 4 (Metal plug material

One 1/4" with plastic plug One 1/4" with metal plug Two 1/4" with plastic plugs

w ill be the same as

Two 1/4" with metal plugs

Cal. ring material if

One 1/2" with plastic plug

metal plug is chosen )

One 1/2" with metal plug

Two 1/2" with plastic plugs

Two 1/2" with metal plugs

** Refer to 34-ST-00-128 for additional options, consult factory 1 Standard facing 125-250 AARH RF (raised face) serrated surface finish. 4 Plastic Plugs are TEMPORARY ONLY to protect threads and MUST be REMOVED before installation 5 Tantalum Upper insert has Tantalum w etted parts and 316 SS or CS non-w etted parts
Note: Remote seal system pressure rating is body rating or seal rating, w hichever is less.

All welded STR84G & 87G & 84A STR82D & 83D
Selection

0 0 0 0 0 0 0 0 0

21 21

Se le ction

AFA _ _ _ _ _ _ AFC _ _ _ _ _ _

 

AFM _ _ _ _ _ _ Se le ction



_ _ _ AA _ _ _ _



_ _ _ AB _ _ _ _



_ _ _ AC _ _ _ _



_ _ _ AE _ _ _ _

88

_ _ _ AF _ _ _ _

88

_ _ _ _ _ 1 _ _ _



_ _ _ _ _ 2 _ _ _



_ _ _ _ _ _ 1 _ _



_ _ _ _ _ _ 2 _ _

99

_ _ _ _ _ _ _ A_



_ _ _ _ _ _ _ B _

10 10

_ _ _ _ _ _ _ C _

10 10

_ _ _ _ _ _ _ D _

10 10

_ _ _ _ _ _ _ _ 0



_ _ _ _ _ _ _ _ H

11 11

_ _ _ _ _ _ _ _ J

11 11

_ _ _ _ _ _ _ _ M

11 11

_ _ _ _ _ _ _ _ N

11 11

_ _ _ _ _ _ _ _ P

11 11

_ _ _ _ _ _ _ _ Q

11 11

_ _ _ _ _ _ _ _ R

11 11

_ _ _ _ _ _ _ _ S

11 11

Table II continued next page

STR84G & 87G & 84A STR82D & 83D

TABLE II

Descripton

Selection

Seal Type

Diaphragm Diameter

Flange Size

Flange
Pr e s s ur e Rating 1

Const. - See Spec. Figure 34-ST-03-88

Construction - See Spec. Figure 34-ST-03-88

ANSI 150

22

1"

ANSI 300

22

BCA _ _ _ _ _ _ BCC _ _ _ _ _ _

12  12 

1-1/2"

ANSI 150

22

ANSI 300

22

2.4"

2"

ANSI 150

22

ANSI 300

22

BGA _ _ _ _ _ _ BGC _ _ _ _ _ _ BDA _ _ _ _ _ _ BDC _ _ _ _ _ _

12  12  12  12 

ANSI 150

22

3"

ANSI 300

22

BFA _ _ _ _ _ _ BFC _ _ _ _ _ _

12  12 

1/2"

ANSI 150

23

CAA _ _ _ _ _ _



ANSI 150

23

1"

ANSI 300

23

CCA _ _ _ _ _ _ CCC _ _ _ _ _ _

 

2.9"

1-1/2"

ANSI 150

22

ANSI 300

22

CGA _ _ _ _ _ _ CGC _ _ _ _ _ _

 

2"

ANSI 150

22

ANSI 300

22

CDA _ _ _ _ _ _ CDC _ _ _ _ _ _

 

1/2"

ANSI 150

22

DAA _ _ _ _ _ _



1"

ANSI 150

23

ANSI 300

23

DCA _ _ _ _ _ _ DCC _ _ _ _ _ _

 

1-1/2"

ANSI 150

23

4.1"

ANSI 300

23

DGA _ _ _ _ _ _ DGC _ _ _ _ _ _

 

2"

ANSI 150

23

ANSI 300

22

DDA _ _ _ _ _ _ DDC _ _ _ _ _ _

 

Seals (continued)

Flush Flanged Seal
with Lower**

3" Wetted Material

ANSI 150
ANSI 300 Diaphragm 316L SS Hastelloy® C-276 Hastelloy® C-276 Monel 400® Tantalum Tantalum

22
22
Low er 316L SS 316L SS Hastelloy® C-276 Monel 400® 316L SS Hastelloy® C-276

DFA _ _ _ _ _ _ DFC _ _ _ _ _ _
Selection _ _ _ BA _ _ _ _ _ _ _ BB _ _ _ _ _ _ _ BC _ _ _ _ _ _ _ BE _ _ _ _ _ _ _ BF _ _ _ _ _ _ _ BG _ _ _ _

 
   88 88 88

Tantalum

Tantalum Clad

_ _ _ BH _ _ _ _

13 13

Non-Wetted Material (upper, upper insert)
Bolts 6

Uppe r

Upper Insert

316L SS

316L SS

Carbon Steel

316L SS

No Selection

Selection _ _ _ _ _ 4 _ _ _ _ _ _ _ _ 5 _ _ _ _ _ _ _ _ _ 0 _ _

  

Flus hing Connections and Plugs4 (Metal plug material w ill be the same as Low er material, if metal plug is chosen (SS Plug for CS Low er and Tantalum Clad)
Gas ket

None One 1/4" with plastic plug One 1/4" with metal plug Two 1/4" with plastic plugs Two 1/4" with metal plugs One 1/2" with plastic plug One 1/2" with metal plug Two 1/2" with plastic plugs Two 1/2" with metal plugs Klinger® C-4401 (non-asbestos) Grafoil® Teflon® Gylon® 3510

_______0 _ _ _ _ _ _ _ _ H _ _______J _ _ _ _ _ _ _ _ M_ _ _ _ _ _ _ _ N _ _ _ _ _ _ _ _ P _ _ _ _ _ _ _ _ Q _ _ _ _ _ _ _ _ R _ _ _ _ _ _ _ _ S _ _ _ _ _ _ _ _ _ K _ _ _ _ _ _ _ _ G _ _ _ _ _ _ _ _ T _ _ _ _ _ _ _ _ L

             
15 15

Table II continued next page
** Refer to 34-ST-00-128 for additional options, consult factory 1 Standard facing 125-250 AARH RF (raised face) serrated surface finish. 6 Bolt material w ill be same as Upper Material. How ever, if Table I bolts/nuts material is NACE or B7M, seal bolt material w ill be 304 SS NACE. 4 Plastic Plugs are TEMPORARY ONLY to protect threads and MUST be REMOVED before installation

Note: Remote seal system pressure rating is body rating or seal rating, w hichever is less.

28

STR800 Smart Pressure Transmitter

TABLE II Seals (continued)

Seal Type
Flange Seal with Extended Diaphragm **
No Selection

Descripton

Diaphragm Diameter

Flange Size

Flange Pressure Rating 1

3"

2.8"

(2.8" OD

ANSI Class 150 ANSI Class 300

extension) 4"
3.5" (3.70" OD

DIN DN80-PN40 ANSI Class 150 ANSI Class 300

extension

DIN DN100-PN40

Diaphragm

Ext. Tube

Wetted Material

316L SS Hastelloy® C-276 Hastelloy® C-276

316L SS 316L SS Hastelloy® C-276

Non-Wetted

CS (Nickel Plated)

Material (flange)

316L SS

Bolts

No Selection

2"

Extension Length

4"

6"

No Selection

No Selection

TABLE II

Descripton

Seal Type

Diaphragm Diameter

Flange Flange Pressure Rating Dependent

Size

on Custom er Flange 1

3.5"

3"

Wetted Material

ANSI Class 150/300/600

Diaphragm

Body

316L SS Hastelloy® C-276 Hastelloy® C-276

316L SS
316L SS Hastelloy® C-276

Monel 400® Tantalum

Monel 400® Tantalum 7

Non-Wetted Material

No Selection

Seals (continued)

Bolts Calibration Rings

No Selection None

Pancake Seal Flus hing

316L SS Hastelloy® C-276
Monel 400® None

Connections

One 1/4" with plastic plug

and Plugs4 (Metal plug material

One 1/4" with metal plug Two 1/4" with plastic plugs

w ill be the same as

Two 1/4" with metal plugs

Cal. Ring material, if

One 1/2" with plastic plug

metal plug is chosen)

One 1/2" with metal plug

Two 1/2" with plastic plugs

Two 1/2" with metal plugs
** Refer to 34-ST-00-128 for additional options, consult factory 1 Standard facing 125-250 AARH RF (raised face) serrated surface finish. 4 Plastic Plugs are TEMPORARY ONLY to protect threads and MUST be REMOVED before installation 7 Tantalum Body has Tantalum w etted parts and 316 SS non-w etted parts

Note: Remote seal system pressure rating is body rating or seal rating, w hichever is less.

STR84G & 87G & 84A STR82D & 83D

Se le ction
EFA _ _ _ _ _ _ EFC _ _ _ _ _ _ EFM _ _ _ _ _ _ FGA _ _ _ _ _ _ FGC _ _ _ _ _ _ FGP _ _ _ _ _ _
Selection _ _ _ EA _ _ _ _ _ _ _ EB _ _ _ _ _ _ _ EC _ _ _ _ _ _ _ _ _ 7 _ _ _ _ _ _ _ _ 8 _ _ _ _ _ _ _ _ _ 0 _ _ _______2 _ _ _ _ _ _ _ _ 4 _ _ _ _ _ _ _ _ 6 _ _ _ _ _ _ _ _ _ 0

     
         

STR84G & 87G & 84A STR82D & 83D

Se le ction
GFA _ _ _ _ _ _
_ _ _ GA _ _ _ _ _ _ _ GB _ _ _ _ _ _ _ GC _ _ _ _ _ _ _ GE _ _ _ _ _ _ _ GG _ _ _ _
_ _ _ _ _ 0 _ _ _
_ _ _ _ _ _ 0 _ _ _ _ _ _ _ _ _ A_ _ _ _ _ _ _ _ B _ _ _ _ _ _ _ _ C _ _ _ _ _ _ _ _ D _ _ _ _ _ _ _ _ _ 0 _ _ _ _ _ _ _ _ H _ _ _ _ _ _ _ _ J _ _ _ _ _ _ _ _ M _ _ _ _ _ _ _ _ N _ _ _ _ _ _ _ _ P _ _ _ _ _ _ _ _ Q _ _ _ _ _ _ _ _ R _ _ _ _ _ _ _ _ S


   88 88

  10 10 10 10 10 10  11 11 11 11 11 11 11 11 11 11 11 11 11 11 11 11

TABLE II Seals (continued)

Seal Type
Chemical Tee "Taylor" Wedge

Descripton

Diaphragm Diameter

Flange Size

Flange Pressure Rating 1

Taylor

3.5"

Wedge

5" O.D.

750 psi

Wetted Material
Non-Wetted Material Bolts Styles
No Selection

Diaphragm

Body

316L SS Hastelloy® C-276

316L SS 316L SS

Hastelloy® C-276 Hastelloy® C-276

No Selection

No Selection

No Selection

No Selection

STR84G & 87G & 84A STR82D & 83D

Se le ction

HM0 _ _ _ _ _ _

16

Selection

_ _ _ HA _ _ _ _



_ _ _ HB _ _ _ _



_ _ _ HC _ _ _ _



_ _ _ _ _ 0 _ _ _



_ _ _ _ _ 0 _ _



_______0 _



_ _ _ _ _ _ _ _ 0



Table II continued below

STR84G & 87G & 84A

TABLE II

Descripton

STR82D &83D

Seal Type

Diaphragm Diameter

Threaded Process Connection Size (NPT Fem ale)

Pressure Rating

CS Bolts

304 SS Bolts

Selection

2.4"

1/2 NPT 3/4 NPT

2,500 psi

1,250 psi

JJG _ _ _ _ _ _ JKG _ _ _ _ _ _

12  12 

1 NPT

JLG _ _ _ _ _ _

12 

2.9"

1/2 NPT 3/4 NPT

2,500 psi

1,250 psi

KJG _ _ _ _ _ _ KKG _ _ _ _ _ _

 

1 NPT

KLG _ _ _ _ _ _



4.1"

1/2 NPT 3/4 NPT

1,500

750

psi

psi

LJG _ _ _ _ _ _ LKG _ _ _ _ _ _

 

1 NPT

LLG _ _ _ _ _ _



Diaphragm

Low er

Selection

Seals (continued)

Seal with Threaded Proces s Connection

Wetted Material
Non-Wetted Material (upper)

316L SS

Carbon Steel

316L SS Hastelloy® C-276 Hastelloy® C-276

316L SS
316L SS Hastelloy® C-276

Monel 400®

Monel 400®

Tantalum Tantalum

316L SS Hastelloy® C-276

CS (Nickel Plated)

316 Stainless Steel

_ _ _ JA _ _ _ _ _ _ _ JB _ _ _ _ _ _ _ JC _ _ _ _ _ _ _ JD _ _ _ _ _ _ _ JE _ _ _ _ _ _ _ JF _ _ _ _ _ _ _ JG _ _ _ _ _ _ _ _ _ A_ _ _ _ _ _ _ _ C _ _ _

    88
88
88
 17 17

Bolts 8
Flus hing Connections and Plugs4
(Metal plug material w ill be the same as
Low er material, if

Carbon Steel 304 SS None
One 1/4" with plastic plug One 1/4" with metal plug Two 1/4" with plastic plugs Two 1/4" with metal plugs One 1/2" with plastic plug

_ _ _ _ _ _ C _ _ _ _ _ _ _ _ D _ _ _______0 _ _ _ _ _ _ _ _ H _ _______J _ _ _ _ _ _ _ _ M_ _ _ _ _ _ _ _ N _ _ _ _ _ _ _ _ P _

       18 18

metal plug is chosen -

One 1/2" with metal plug

_ _ _ _ _ _ _ Q _

18 18

(SS Plug for CS Low er Two 1/2" with plastic plugs

_ _ _ _ _ _ _ R _

18 18

and Tantalum Clad)

Two 1/2" with metal plugs

Gas ket

Klinger® C-4401 (non-asbestos) Grafoil® Teflon®

Gylon® 3510

_ _ _ _ _ _ _ S _ _ _ _ _ _ _ _ _ K _ _ _ _ _ _ _ _ G _ _ _ _ _ _ _ _ T _ _ _ _ _ _ _ _ L

18 18      15 15

1 Standard facing 125-250 AARH RF (raised face) serrated surface finish. 4 Plastic Plugs are TEMPORARY ONLY to protect threads and MUST be REMOVED before installation 8 If Table I Bolts and Nuts material option is NACE, Bolts and Nuts w ill ship w ith Alloy Steel NACE and MAWP may change.

Note: Remote seal system pressure rating is body rating or seal rating, w hichever is less.

30

STR800 Smart Pressure Transmitter

TABLE II Seals (continued)

Seal Type Sanitary Seal 9

Descripton

Diaphragm Diameter

Flange Size

Pressure Rating

1.9"

2"

2.4"

2-1/2"

2.9"

3"

Customer clamp rating or 600 psi, whichever is less

4.1"

4"

Wetted Material

Diaphragm 316L SS

Body 316L SS

Non-Wetted Material

No Selection

Bolts Styles Gas ket

No Selection Tri-Clover Tri-Clamp®
No Selection

TABLE II

Descripton

Seal Type

Diaphragm Diameter

Size and Bolt
Patte r n

Seal Pressure Rating

C.S. Bolts

316 SS Bolts

2.4" 8-Bolt Design 2.4" 6-Bolt Design

for 3" Pipe  4" pipe
for 3" Pipe  4" pipe

2,500 psi
2,000 psi Diaphragm 316L SS

1,250 psi
1,000 psi Low er Housing Carbon Steel

Seals (continued)

Saddle Seal

Wetted Material

316L SS Hastelloy® C-276 Hastelloy® C-276
316L SS Hastelloy® C-276
Body

316L SS
316L SS Hastelloy® C-276 N/A-Body Only 10 N/A-Body Only 10
Bolts 10,11

Non-Wetted Material Carbon Steel 316L SS

Carbon Steel 316 SS

Bolts

No Selection

Styles

No Selection

Klinger® C-4401 (non-asbestos)

Gas ket

Grafoil® Teflon®

Gylon® 3510
9 All sanitary seals have dairy grade 3A approval. 10 Bolts are not included w ith "body only" selection. 11 If Table I Bolts and Nuts material option is NACE, seal bolt material w ill be 304 SS NACE.

Note: Remote seal system pressure rating is body rating or seal rating, w hichever is less.

STR84G & 87G & 84A STR82D & 83D

Selection

MD0 _ _ _ _ _ _

19

NE0 _ _ _ _ _ _

20 19

PF0 _ _ _ _ _ _

19 19

QG0 _ _ _ _ _ _

19 19

Selection

_ _ _ N A_ _ _ _ _ _ _ _ _ 0 _ _ _ _ _ _ _ _ _ 0 _ _ _______8 _

   

_ _ _ _ _ _ _ _ 0



Table II continued below

STR84G & 87G & 84A STR82D & 83D

Selection
RFK _ _ _ _ _ _
RGK _ _ _ _ _ _
RPK _ _ _ _ _ _
RQK _ _ _ _ _ _ Selection
_ _ _ RA _ _ _ _ _ _ _ RB _ _ _ _ _ _ _ RC _ _ _ _ _ _ _ RD _ _ _ _ _ _ _ SB _ _ _ _ _ _ _ SC _ _ _ _
Selection _ _ _ _ _ B _ _ _ _ _ _ _ _ C _ _ _ _ _ _ _ _ _ 0 _ _ _ _ _ _ _ _ _ 0 _ _ _ _ _ _ _ _ _ K _ _ _ _ _ _ _ _ G _ _ _ _ _ _ _ _ T _ _ _ _ _ _ _ _ L

12 
12 
12 
12 
     
88       

STR84G & 87G & 84A STR82D & 83D

TABLE III Approvals

Agency Approvals (see data sheet for Approval Code Details) No Approvals Required FM Explosion proof, Intrins ically Safe, Non-incendive, & Dus tproof CSA Explos ion proof, Intrins ically Safe, Non-incendive, & Dus tproof ATEX Explos ion proof, Intrins ically Safe & Non-incendive IECEx Explosion proof, Intrins ically Safe & Non-incendive SAEx Explosion proof, Intrins ically Safe & Non-incendive INMETRO Explosion proof, Intrins ically Safe & Non-incendive NEPSI Explosion proof, Intrins ically Safe & Non-incendive KOSHA Explos ion proof, Intrins ically Safe & Non-incendive EAC Custom s Union(Russ ia,Belarus,Kazakhstan) Ex Approval,Flam eproof, Intrinsically Safe CCoE Explosion proof, Intrins ically Safe & Non-incendive UATR Flam eproof, Intrins ically Safe & Dustproof

0



A



B



C



D



E



F



G



H



I



J



K



TABLE IV

TRANSMITTER ELECTRONIC SELECTIONS

M ate r ial

Conne ction

Lightning Protection

Polyester Powder Coated Aluminum

1/2 NPT

None

Polyester Powder Coated Aluminum

a. Electronic Polyester Powder Coated Aluminum

Housing Material

& Connection Polyester Powder Coated Aluminum

Type

316 Stainless Steel (Grade CF8M)

316 Stainless Steel (Grade CF8M)

M20 1/2 NPT
M20 1/2 NPT
M20

None Yes Yes None None

316 Stainless Steel (Grade CF8M)

1/2 NPT

Yes

316 Stainless Steel (Grade CF8M)

M20

Yes

Analog Output

Digital Protocol

b. Output/ Protocol

4-20m A dc 4-20m A dc

HART Protocol DE Protocol

Indicator

none

p

g

Buttons

Foundation Fieldbus Language s

None

None

None

None

Yes (Zero/Span Only)

None

c. Customer

Bas ic

None

Englis h

Interface Selections

Bas ic Advanced

Yes None

Englis h EN,GR,IT, FR,SP,RU, TU

Advanced

Yes

EN,GR,IT, FR,SP,RU, TU

Advanced

None

EN, CH, JP

Advanced

Yes

EN, CH, JP

A _ _ B _ _ C _ _ D _ _ E _ _ F _ _ G _ _ H _ _
_ H _ _ D _ _ F _
_ _ 0 _ _ A _ _ B _ _ C _ _ D _ _ E _ _ H _ _ J

       
  
 ff      

TABLE V

CONFIGURATION SELECTIONS

a. Application Software Standard Diagnostics

Diagnostics

Write Protect

Fail Mode

High & Low Output Lim its3

Disabled

High> 21.0mAdc

Honeywell Std (3.8 - 20.8 mAdc)

b. Output Limit, Failsafe & Write Protect Settings

Disabled Enabled Enabled

Low< 3.6mAdc High> 21.0mAdc Low< 3.6mAdc

Honeywell Std (3.8 - 20.8 mAdc) Honeywell Std (3.8 - 20.8 mAdc) Honeywell Std (3.8 - 20.8 mAdc)

Enabled

N/A

N/A Fieldbus or Profibus

Disabled

N/A

N/A Fieldbus or Profibus

c. General Configuration

Factory Standard Custom Configuration (Unit Data Required from customer)

1 _ _
_ 1 _ _ 2 _ _ 3 _ _ 4 _ _ 5 _ _ 6 _ _ _ S _ _ C


ff ff ff ff gg gg  

TABLE VI
Accuracy and Calibration

Accuracy NA
Standard Standard

CALIBRATION & ACCURACY SELECTIONS

Calibrated Range

Calibration Qty

None

None

Factory Std

Single Calibration

Custom (Unit Data Required)

Single Calibration

3 NAMUR Output Limits 3.8 - 20.5mAdc can be conf igured by the customer or select custom conf iguration Table Vc

0

21 21

A

23 23

B

23 23

32

TABLE VII

ACCESSORY SELECTIONS

a. Mounting Bracket

Bracket Type None
Angle Bracket Angle Bracket Angle Bracket Marine Approved Bracket Marine Approved Bracket (In Line)
Marine Approved Bracket Marine Approved Bracket (In Line)
Flat Bracket Flat Bracket Flat Bracket

M ate r ial None
Carbon Steel 304 SS 316 SS
Carbon Steel Carbon Steel
304 SS 304 SS Carbon Steel 304 SS 316 SS

b. Customer Tag

Custom er Tag Type
No customer tag One Wired Stainless Steel Tag (Up to 4 lines 26 char/line) Two Wired Stainless Steel Tag (Up to 4 lines 26 char/line)

Unassem bled Conduit Plugs & Adapters

c. Unassembled No Conduit Plugs or Adapters Required

Conduit

1/2 NPT Male to 3/4 NPT Female 316 SS Certified Conduit Adapter

Plugs & 1/2 NPT 316 SS Certified Conduit Plug

Adapters

M20 316 SS Certified Conduit Plug Minifast® 4 pin (1/2 NPT)

Minifast® 4 pin (M20)

TABLE VIII
Certifications & Warranty

OTHER Certifications & Options : (String in sequence comma delimited (XX, XX, XX,....) None - No additional options NACE MR0175; MR0103; ISO15156 (FC33338) Process wetted parts only NACE MR0175; MR0103; ISO15156 (FC33339) wetted and non-wetted parts Marine (DNV,ABS,BV,KR,LR) EN10204 Type 3.1 Material Traceability (FC33341) Certificate of Conformance (F3391) Calibration Test Report & Certificate of Conformance (F3399) Certificate of Origin (F0195) FMEDA (SIL 2/3) Certification (FC33337) Over-Pres s ure Leak Tes t Certificate (1.5X MAWP) (F3392) Cert Clean for O2 or CL2 service per ASTM G93
Extended Warranty Additional 1 year Extended Warranty Additional 2 years Extended Warranty Additional 3 years Extended Warranty Additional 4 years Extended Warranty "LifeTim e" Additional 15 years

TABLE IX Factory

Manufacturing Specials Factory Identification

STR800 Smart Pressure Transmitter

STR84G & 87G & 84A STR82D & 83D

0 _ _ _ 1 _ _ _ 2 _ _ _ 3 _ _ _ 8 _ _ _ 9 _ _ _ 4 _ _ _ A_ _ _ 5 _ _ _ 6 _ _ _ 7 _ _ _
_ 0 _ _ _ 1 _ _ _ 2 _ _
_ _ A0 _ _ A2 _ _ A6 _ _ A7 _ _ A8 _ _ A9

    y
 y
   
  
 nn nn mm nn mm

00

**

FG F7

** cc

b

MT

dd

FX



F3 F1

 

b

F5



FE

jj

TP



OX

ee

01



02



03



b

04



15



0 0 0 0



MODEL RESTRICTIONS

Restriction

Letter

Table

b

d

IVa

c

Id

e

Ib

f

g

j

IVb

m

IVa

n

IVa

y

2

Ie

3

If

4

I

Available Only With

Not Available With

Selection(s)

Table

Selection(s)

Select only one option from this group

C, D,G,H _ _

VIIa

1,2,3,5,6,7 _ _ _

_ _ _ 0, N, B _ _ _

_ 2 _ _ 2 _ _
_ H _ B, D, F, H _ _ A, C, E, G _ _
_ _ _ _ 0 _ _ _ _ _ _ 2 _ _ _ _ _ _ 4 _ _ _ _ _ _ _ 2 _

IVb

_ F _

IVb

_ H, D _

Vb

_ 1,2,6 _

Ic

_ _ E _ _ _ _

Ia

2 _ _ _ _ _ _

2 _ _ 0 _ _ _

5

II

000000000

VIII

FG, F7, FX, OX,TP,MT,F1

6

I

7

8

9

II

10

11

12

If

13

II

15

II

16

I

17

18

19
If 20

_ _ B,D _ _ _ _
_ _ _ AA2_ _ _ _ _ _ AB2_ _ _ _ _ _ _ _ A, G, 2 _ _ _ _ _ _ _ _ 0 _ _ _ _ BF _ _ _ _ _ _ _ BG _ _ _ _ _ _ _ BH _ _ _ _ _ _ _ JF _ _ _ _ _ _ _ JG _ _ _ _ 2 _ _ _ _ _ _
_ _ _ _ _ A,G _

Ia

2 _ _ _ _ _ _

_ _ _ AF _ _ _ _

_ _ _ BF _ _ _ _

_ _ _ BG _ _ _ _

II

_ _ _ BH _ _ _ _

_ _ _ GG _ _ _ _

_ _ _ JF _ _ _ _

_ _ _ JG _ _ _ _

VIII

FG, F7

II

_ _ _ _ _ _ _ _ 0

II

_ _ _ _ _ _ _ A_

II

_ _ _ _ _ _ _ _ T

VIII

FG, F7

II

_ _ _ JA _ _ _ _

JJG _ _ _ _ _ _

II

JKG _ _ _ _ _ _

JLG _ _ _ _ _ _

If

_ _ _ _ _ 2 _

21

I

_ _ _ _ 000

22

Ic

_ _ E _ _ _ _

23

II

FM ApprovalsSM is a service mark of FM Global

Hastelloy® is a registered trademark of Haynes International

Monel 400® is a registered trademark of Special Metals Corporation.

HART® is a registered trademark of HART Communication Foundation.

FOUNDATIONTM Fieldbus is a registered trademark of Fieldbus Foundation.

Teflon® is a registered trademark of DuPont.

Neobee® is a registered trademark of Stepan Company.

Syltherm® 800 is a Trademark of Dow Corning Corporation

Klinger® C-4401 is a registered trademark of THERMOSEAL, INC

GRAFOIL® is a registered trademarks of GrafTech International Holdings Inc Gylon® 3510 is registered trademark of Garlock Sealing Technologies

Tri-Clover Tri-Clamp® is a registered trademark of Alf a-Laval DC® 200 and DC® 704 are registered trademarks of Dow Corning

000000000

34
FIELD INSTALLABLE REPLACEMENT PARTS Description
Integrally Mounted Bas ic Indicator Kit (Com patible with all Electronic Modules ) Integrally Mounted Advanced Indicator Kit (Com patible with all Electronic Modules) Terminal Strip w/Lightning Protection Kit for HART or DE Modules Terminal Strip w/Lightning Protection Kit for FFB Module Terminal Strip w/o Lightning Protection for HART or DE Modules Terminal Strip w/o Lightning Protection FFB Module HART Electronics Module HART Electronics Module w/connection for external configuration buttons DE Electronics Module DE Electronics Module w/connection for external configuration buttons FFB Electronics Module Kit FFB Electronics Module w/connection for external configuration buttons
PRODUCT MANUALS Description
Paper Manual ST 800 Smart Transmitter User Manual - English Paper Manual ST 800 Smart Transmitter HART/DE Communications Manual - English Paper Manual ST 800 Sm art Trans m itter Safety Manual - English Paper Manual ST 800 Smart Transmitter Foundation Fieldbus Manual - English Paper Manual ST 800 Smart Transmitter Function Block Manual - English All product documentation is available at www.honeywellprocess.com.

STR800 Smart Pressure Transmitter
Kit Number 50049911-501 50049846-501 50075472-532 50075472-534 50075472-531 50075472-533 50049849-501 50049849-502 50049849-503 50049849-504 50049849-507 50049849-508
Part Number 34-ST-25-35 34-ST-25-38 34-ST-25-37 34-ST-25-39 34-ST-25-42

Sales and Service
For application assistance, current specifications, ordering, pricing, and name of the nearest Authorized Distributor, contact one of the offices below.

ASIA PACIFIC
Honeywell Process Solutions, Phone: + 800 12026455 or +44 (0) 1202645583 (TAC) hfs-tacsupport@honeywell.com
Australia Honeywell Limited Phone: +(61) 7-3846 1255 FAX: +(61) 7-3840 6481 Toll Free 1300-36-39-36 Toll Free Fax: 1300-36-04-70
China ­ PRC - Shanghai Honeywell China Inc. Phone: (86-21) 5257-4568 Fax: (86-21) 6237-2826
Singapore Honeywell Pte Ltd. Phone: +(65) 6580 3278 Fax: +(65) 6445-3033
South Korea Honeywell Korea Co Ltd Phone: +(822) 799 6114 Fax: +(822) 792 9015

EMEA
Honeywell Process Solutions, Phone: + 800 12026455 or +44 (0) 1202645583
Email: (Sales) FP-Sales-Apps@Honeywell.com or (TAC) hfs-tac-support@honeywell.com
Web Knowledge Base search engine http://bit.ly/2N5Vldi

AMERICAS
Honeywell Process Solutions, Phone: (TAC) (800) 423-9883 or (215) 641-3610 (Sales) 1-800-343-0228
Email: (Sales) FP-Sales-Apps@Honeywell.com or (TAC) hfs-tac-support@honeywell.com
Web Knowledge Base search engine http://bit.ly/2N5Vldi

Specifications are subject to change without notice.

For more information To learn more about SmartLine Pressure Transmitters, visit www.honeywellprocess.com Or contact your Honeywell Account Manager

Process Solutions Honeywell 1250 W Sam Houston Pkwy S Houston, TX 77042
Honeywell Control Systems Ltd Honeywell House, Skimped Hill Lane Bracknell, England, RG12 1EB
Shanghai City Centre, 100 Jungi Road Shanghai, China 20061
www.honeywellprocess.com

34-ST-03-88 October 2020