Retro-Line - Heat-Line

manual included with your GFA-STAT unit. G. Double check that the wires have been connected correctly. H. Establish power to the circuit and test/reset the ...

Retro-Line

PDF Retro-Line-Manual
Retro-Line®
Internal Freeze Protected Water Supply Systems

Retro-Line (Standard model)
Retro-Line IP
Retro-Line NI
Table of Contents
Retro-Line Standard Installation .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 2 Retro-Line IP Installation.  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 6 Retro-Line NI Installation.  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 10

Installation Instructions
General Information
Retro-Line systems are an internal (in-pipe) freeze protected, potable, domestic water supply line systems adaptable to ALL areas where natural frost protection cannot be achieved. These are high performance products designed to work in cold and harsh environments. Retro-Line products are uniquely adaptable to many types of applications. System requirements will vary a great deal in accordance to ground conditions.
It is recommended that the Retro-Line installation be made by a qualified tradesperson. This will ensure that optimum performance is achieved in each installation. Variables include: shallow burial in rocky geography - free air/ above ground and thermostatic control.
Thermostatic controls are optional but should be considered for every application for further energy savings if applicable. The use of insulation should also be considered for cold weather reliability and energy efficiency.
A. This heating cable set shall be installed in accordance with the National Electrical Code (USA) or the Canadian Electrical Code.
B. It is imperative that for all installations where the pipes are exposed to the outside ambient temperature that weatherproof insulation be used. (Wall thickness ½ inch minimum). Heat-Line offers closed cell foam types, foil/ air bubble type and others. Other types of weather-proof insulations may also be used.
C. Retro-Line can be used even when there is no water in the pipe. Retro-Line WILL NOT melt your water pipe. In the event of power failure your system may freeze. The system will however re-energize immediately following power restoration and will thaw out again. In most cases no damage to pipes will be encountered.
Retro-Line is a technically advanced product. Handle it with proper care and be sure not to damage the outer sheath or jacket of the cable.
Read the Safety Instructions and Installation Instructions completely before installing this product.
Approvals
Usage P and X Installation Type D USA
Drinking Water
NSF/ANSI 61
Electrical System Connection .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 14 Control Devices and Insulation Installation .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 16 Limited Warranty 17 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . Extended Warranty Application Form .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 19

Important Safety Instructions and Rules for safe Installation and Operation
A. Read these rules and instructions carefully. Failure to follow them could result in serious bodily injury and/or property damage.
B. Check your local building, plumbing and electrical codes before installing. You must comply with their rules. Retro-Line is cCSAus Drinking Water NSF/ANSI 61 approved for use in Canada and the USA.
C. Before installing this product have the electrical outlet checked by an electrician to make sure it is properly installed and grounded.
D. Do not install the Retro-Line tee connection junction point in a manner that would render the system nonserviceable.

E. Do not bury the connection point underground or in a location that may become flooded.
F. Before installing or servicing your Retro-Line BE CERTAIN that the power source is disconnected.
G. Do not use extension cords.
H. Heat-Line does not recommend the use of non-certified or non-industry standard polyethylene pipe when using the Retro-Line standard model or Retro-Line NI. The Philmac compression fittings supplied as part of the Retro-Line Standard and NI model products are cCSAus certified for use with certified polyethylene pipes. If non-certified or non-industry standard piping is installed, such as thin wall polyethylene, a licensed trades-person should observe the installation and certify that the Philmac fitting has made a secure compression.

Pressure testing the system prior to service is highly recommended to ensure a proper connection. I. Retro-Line is NOT approved or designed for use in sewer or waste systems. For sewer and waste systems use Heat-Line Paladin, EXT Series, Retro-DWS, Retro-FM or CARAPACE systems. J. Never tamper with or alter the electrical apparatus associated with your Retro-Line system. K. Check unoccupied residences regularly to ensure that all systems are operating properly. WHEN PERFORMING WORK OR REPAIRS ON YOUR WATER SYSTEM BE SURE TO UNPLUG YOUR RETROLINE SYSTEM FROM THE POWER SUPPLY.
1 of 20

Retro-Line Installation

Retro-Line® (Standard Model)
Internal Freeze Protected Water Supply Systems

Installation Instructions

Cord-Set Model
Must be protected with GFCI (Ground Fault Circuit Interrupter)
Retro-Line Ordering Chart

Description
The Retro-Line standard model is supplied with a compression tee fitting of a specific size to interface into ID or OD polyethylene pipe. Fitting for OD polyethylene pipe is available in CTS and IPSOD sizes. Pipe size must be determined at time of order. See part numbers below.
Kit Contents Qty Description 1 Retro-Line ­ Predetermined length (GFC shown) 1 Optional Cord-Set (CS) power connection
Optional Accessories HLA-120 NEMA 1 General Purpose 120V only plug-in Thermostat GFA-STAT NEMA 4X Ground Fault Protected Adjustable Thermostat
120V/240V 30 amp MA-10 GFCI/ELCI Electrical Equipment Protection Device INSUL-1.00 Closed cell polyethylene insulation sleeve for 1" ID pipe
(6' long, 1 5/8" ID, ¾" thick wall) INSUL-1.25 Closed cell polyethylene insulation sleeve for 1 1/4" ID pipe
(6' long, 1 7/8" ID, ¾" thick wall) INSUL-2.00 Closed cell polyethylene insulation sleeve for 2" ID pipe
(6' long, 2 5/8" ID, ¾" thick wall)

Example: RL ­ 125 ­ 100 ­ CTS ­ GFC

Product
RL RL2

120 volt Retro-Line 240 volt Retro-Line

Cord-Set Type
GFC Ground fault protected 5-15P 120V / 6-15P 240V

Pipe Size
075 Pipe size 0.75" 100 Pipe size 1.00" 125 Pipe size 1.25" 150 Pipe size 1.50" 200 Pipe size 2.00" *
* ID and ODIPS pipes only

CS Cord connected (No GFCI)
Pipe Size Type
ID Internal Pipe Diameter I.D. CTS Copper Tubing Size IPS Outside Dimension I.P.S.O.D.
Length of Heater
6 ­ 230 feet 3 watt /120V systems 6 ­ 550 feet 3 watt /240V systems

NOTE: The heating cable is measured and cut to the length of system ordered. Some of this length will remain within the interface fitting.

2 of 20

Retro-Line Standard Installation 1
· Carefully remove your Retro-Line system. It comes complete with all parts as required pre-assembled, enclosed inside of the reel. Units less than 40 feet not supplied on reel.

Retro-Line Installation
· It is recommended that a single circuit (15 amp) be installed by a qualified electrician for dedicated use of the Retro-Line system. Do not use extension cords.

OFF OFF OFF OFF OFF ON ON ON ON ON
OFF OFF OFF OFF OFF ON ON ON ON ON

240V 15A circuit

120V 15A circuit

2

· Determine point of entry into the pipe. Your Retro-Line system is ordered by system (pipe) length. (See Retro-Line Ordering Instructions on page 2).
· Cut out a section of the pipe to gain access, preferably on the inside of the building and near your power supply. (Reference chart below)
CAUTION: Care must be taken not to cut the pipe too short as it is necessary to draw the pipe into the fitting when making a joint.

Pipe Diameter

3/4" ID

1"

ID

1 1/4" ID

1 1/2" ID

2"

ID

3/4" CTS/IPSOD

1"

CTS/IPSOD

1 1/4" CTS/IPSOD

1 1/2" CTS/IPSOD

2"

IPSOD

Section of pipe to be removed 6 1/4"
6 1/4" 6 1/4" 6 1/2" 7 1/2" As per "PIPE # STOP" lines on tee As per "PIPE # STOP" lines on tee As per "PIPE # STOP" lines on tee As per "PIPE # STOP" lines on tee As per "PIPE # STOP" lines on tee (IPSOD only)

Note: Do not install the Retro-Line tee connection junction point in a manner that would render the system non-serviceable. Consult Heat-Line with questions regarding installation parameters with respect to serviceability.
Remove section of pipe Important: Cut pipe square

3
· Short Retro-Line systems may be pushed in without the use of a fish tape or rope. Longer systems may require the use of a fish tape or other installation method. For long systems a vacuum can be used to draw a sponge ""mouse" through the pipe with a 1/8" mason line attached. These sponges can be hand made or purchased from Heat-Line. Extra long systems may require "cutting in" a coupling or series of couplings to provide access points to pull in the Retro-Line. When this is required it is important to use a Philmac® coupling furnished by Heat-Line.
· A 6 foot leader is provided with all Retro-Line systems over 90 feet. This leader is your point of attachment for pulling in the Retro-Line. If the leader is not required, remove it and simply push in the Retro-Line into the pipe.
· A non-toxic, water based (potable) lubricant can be used to make cable insertion or pushing of long lengths easier.
NOTE: Retro-Line systems in reasonably straight runs up to 150 feet can most often be pushed all the way in without pulling. The Retro-Line leader is only provided as an aid to pulling. It is unable to withstand extremely hard pulls and will break if over stressed. Heat-Line will not be responsible should this occur.

Fish Tape Method

6 ft leader

Fish tape

Heating cable

Vacuum Method
Vacuum hose

Sponge (mouse)

1/8" Mason line

6 ft leader Inside Outside

3 of 20

Retro-Line Installation
4
· Slowly push/pull the Retro-Line into the pipe off of the reel. Upon total heater insertion, break open the reel at perforations, or lift tabs to remove lid as shown. Do not use sharp instruments. Finish insertion of the Retro-Line until the Philmac fitting comes up tight.

5
· Install Philmac fitting onto pipe. (Refer to installation steps 5A for ID pipe applications or 5B for CTS/IPSOD pipe applications).
(1" ID Philmac fitting shown.)

5.1A Installing an ID Philmac Fitting
· Remove nut and split collet from central fitting and slide over pipe.
NOTE: Ensure the taper or split collet faces toward the nut.
Nut Reducing cone

Nut
Reducing cone Collet Insert O-ring

Collet Insert

O-ring
Insert Collet
Reducing cone Nut

5.2A Installing an ID Philmac Fitting
· Tap insert into pipe preferably with a forked flat object. Ensure 0-ring is correctly positioned on the insert. Take care not to hit or nick cable jacket.

5.3A Installing an ID Philmac Fitting
· Push fitting onto pipe with insert and 0-ring. Slide split collet and nut up to the fitting and engage thread. Tighten with a wrench.

4 of 20

Insert
O-ring Forked flat object

5.4A Installing an ID Philmac Fitting
· Repeat for other side.
NOTE: DO NOT tighten nut where electrical comes out as this is done in factory.

Retro-Line Installation
5.1B Installing an CTS/IPSOD Philmac Fitting
· Cut pipe square and deburr.
· Loosen nuts to expose 2 threads but do not remove from tee.

5.2B Installing an CTS/IPSOD Philmac Fitting
· Push pipe into Philmac body to stop mark indicated on outside of tee. Tighten nut with wrench.

Loosen nuts ONLY. Do not remove.
6
· If used, remove the 6' leader. Cut off the knot and remove from pipe by pulling on the side that moves easiest. Remove (see inset).
Removing the 6 foot leader

7
· After all plumbing fittings have been completely installed, a licensed trades-person should observe the installation and certify that the Philmac fitting has made a secure compression. Pressure testing the system prior to service is highly recommended to ensure a proper connection.
Refer to control devices and insulation installation on page 16.
· It is now time to energize your RetroLine system. Carefully follow the Electrical System Check instructions on Page 14/15.

Ground-faulted plug-in (GFC) model shown.

Cord set (CS) model shown. GFCI circuit protection required.

5 of 20

Retro-Line Installation

Retro-Line IP
Internal Freeze Protected Water Supply Systems

Installation Instructions

Cord-Set Model
Must be protected with GFCI (Ground Fault Circuit Interrupter)
Retro-Line IP Ordering Chart

Description
The Retro-Line IP is supplied with a male adapter (MIPT) of a specific thread size to interface into any pipe material such as polyethylene, PEX, copper, PVC, ABS, iron or galvanized through a tee or wye fitting. Thread size must be determined at time of order. See part numbers below. Note: For pipe diameters larger than 2" ID see Heat-Line's Retro-FM system.
Kit Contents Qty Description 1 Retro-Line IP ­ Predetermined length (GFC shown) 1 Optional Cord-Set (CS) power connection
Optional Accessories HLA-120 NEMA 1 General Purpose 120V only plug-in Thermostat GFA-STAT NEMA 4X Ground Fault Protected Adjustable Thermostat
120V/240V 30 amp MA-10 GFCI/ELCI Electrical Equipment Protection Device INSUL-1.00 Closed cell polyethylene insulation sleeve for 1" ID pipe
(6' long, 1 5/8" ID, ¾" thick wall) INSUL-1.25 Closed cell polyethylene insulation sleeve for 1 1/4" ID pipe
(6' long, 1 7/8" ID, ¾" thick wall) INSUL-2.00 Closed cell polyethylene insulation sleeve for 2" ID pipe
(6' long, 2 5/8" ID, ¾" thick wall)

Example: RL ­ 100 ­ 100 ­ IP ­ CS

Product

RL

120 volt Retro-Line

RL2

240 volt Retro-Line

Fitting Size

100

Male adapter thread size 1.00" NPT

125

Male adapter thread size 1.25" NPT

150

Male adapter thread size 1.50" NPT

200

Male adapter thread size 2.00" NPT

Cord-Set Type
GFC Ground fault protected 5-15P 120V / 6-15P 240V
CS Cord connected (No GFCI)
IP Denotes male adapter fitting
Length of Heater
6 ­ 230 feet 3 watt / 120V systems 6 ­ 550 feet 3 watt / 240V systems

NOTE: The heating cable is measured and cut to the length of system ordered. Some of this length will remain within the interface fitting.

For pipe diameter 3/4" ID, order with a 1" male adapter NPT thread. For pipe diameters larger than 2" ID see Heat-Line's Retro-FM system.

6 of 20

Retro-Line IP Installation 1
· Carefully remove your Retro-Line system. It comes complete with all parts as required pre-assembled, enclosed inside of the reel. Units less than 40 feet not supplied on reel.

Retro-Line Installation

· It is recommended that a single circuit (15 amp) be installed by a qualified person for dedicated use of the Retro-Line system. Do not use extension cords.

240V 15A circuit

120V 15A circuit

OFF OFF OFF OFF OFF ON ON ON ON ON
OFF OFF OFF OFF OFF ON ON ON ON ON

2
· Install tee fitting with appropriate female thread (FIPT) to interface to supplied Retro-Line (MIPT) thread.
· Smooth and deburr all connections, tube and pipe.
· It is recommended that the heating cable to be installed straight through the tee as shown (water flows through at 90 degrees) instead of installing heating cable through branch.
Note: Do not install the Retro-Line fitting connection junction point in a manner that would render the system non-serviceable. Consult Heat-Line with questions regarding installation parameters with respect to serviceability.

To appliances

Water flow

Supply from source to protect

Tee

3
· Short Retro-Line systems may be pushed in without the use of a fish tape or rope. Longer systems may require the use of a fish tape or other installation method. For long systems a vacuum can be used to draw a sponge "mouse" through the pipe with a 1/8" mason line attached. These sponges can be hand made or purchased from Heat-Line. Extra long systems may require "cutting in" a coupling or series of couplings to provide access points to pull in the Retro-Line. When this is required it is important to use a Philmac® coupling furnished by Heat-Line.
· A 6 foot leader is provided with all Retro-Line systems over 90 feet. This leader is your point of attachment for pulling in the Retro-Line. If the leader is not required, remove it and simply push in the Retro-Line into the pipe.
· A non-toxic (potable) lubricant can be used to make cable insertion or pushing of long lengths easier.
NOTE: Retro-Line systems in reasonably straight runs up to 150 feet can most often be pushed all the way in without pulling. The Retro-Line leader is only provided as an aid to pulling. It is unable to withstand extremely hard pulls and will break if over stressed. Heat-Line will not be responsible should this occur.

Fish Tape Method

6 ft leader

Fish tape

Heating cable

Vacuum Method
Vacuum hose

Sponge (mouse)

1/8" Mason line

6 ft leader Inside Outside
7 of 20

Retro-Line Installation
4
· Slowly push/pull the Retro-Line into the pipe off of the reel. Upon total heater insertion, break open the reel at perforations, or lift tabs to remove lid as shown.
· Do not use sharp instruments. Finish insertion of the Retro-Line until the Philmac fitting comes up tight. A non-toxic (potable) lubricant can be used to make cable insertion or pushing of long lengths easier. If the pipe is straight and downhill the systems can often be pushed more than 150 feet.

5
· Remove nut from male adapter body · Install Teflon tape or thread compound on
thread
CAUTION: Be sure there are no sharp edges deburr all.
· Thread male adapter body into tee fitting · Apply non-toxic lubricant or grease to top
section of rubber sealing grommet. · Slide remaining heater into pipe and tighten
nut onto adapter.

Teflon tape or thread compound
RL compression seat Non Toxic Grease

Male adapter

Retro-Line Sealing grommet RL compression collar
Nut

Apply grease ONLY to the top tapered edge of
the sealing grommet

6
· Tighten nut until RL compression collar stands proud 3/16".
IMPORTANT: Ensure that the heating cable does not twist in the sealing grommet as the nut is tightened.
Note: Do not over tighten! Should be tightened by hand however a wrench can be used if assistance is required.

Water flow

Water flow

3/16"

8 of 20

7
· If used, remove the 6' leader. Cut off the knot and remove from pipe by pulling on the side that moves easiest.
· After all plumbing fittings have been completely installed, check the operation of the pressure system.

Retro-Line Installation
Removing the 6 foot leader

8
· After all plumbing fittings have been completely installed, a licensed trades-person should observe the installation and certify that the Philmac fitting has made a secure connection. Pressure testing the system prior to service is highly recommended to ensure a proper connection.
Refer to control devices and insulation installation on page 16.
· It is now time to energize your RetroLine system. Carefully follow the Electrical System Check instructions on Page 14/15.

Ground-faulted plug-in (GFC) model shown.

Cord set (CS) model shown. GFCI circuit protection required.

9 of 20

Retro-Line Installation

Retro-Line NI
Freeze Protected Water Supply Systems

Cord-Set Model
Must be protected with GFCI (Ground Fault Circuit Interrupter)

Installation Instructions
Description
The Retro-Line NI is supplied with a compression tee fitting and inserts to interface into 1" or 1 1/4" ID polyethylene pipe. See part numbers below.
Kit Contents Qty Description 1 Retro-Line NI ­ Predetermined length (GFC shown) 1 Optional Cord-Set (CS) power connection Optional Accessories HLA-120 NEMA 1 General Purpose 120V only plug-in Thermostat GFA-STAT NEMA 4X Ground Fault Protected Adjustable Thermostat
120V/240V 30 amp MA-10 GFCI/ELCI Electrical Equipment Protection Device INSUL-1.00 Closed cell polyethylene insulation sleeve for 1" ID pipe
(6' long, 1 5/8" ID, ¾" thick wall) INSUL-1.25 Closed cell polyethylene insulation sleeve for 1 1/4" ID pipe
(6' long, 1 7/8" ID, ¾" thick wall)

Retro-Line NI Ordering Chart

Example: RL ­ 125 ­ 100 ­ NI ­ GFC

Product
RL 120 volt Retro-Line RL2 240 volt Retro-Line
Fitting Size
125 Pipe insert size 1.00" and 1.25"

Cord-Set Type
GFC Ground fault protected 5-15P 120V / 6-15P 240V
CS Cord connected (No GFCI)
NI Denotes tee fitting adaptable to fit both
1.00" ID and 1.25" ID polyethylene pipe
Length of Heater
6 ­ 230 feet 3 watt / 120V systems 6 ­ 550 feet 3 watt / 240V systems

NOTE: The heating cable is measured and cut to the length of system ordered. Some of this length will remain within the interface fitting.

10 of 20

Retro-Line NI Installation 1
· Carefully remove your Retro-Line NI system. It comes complete with all parts enclosed inside the box, the tee body is enclosed inside the reel. Units less than 40 feet are not supplied on reel.

Retro-Line Installation
· It is recommended that a single circuit (15 amp) be installed by a qualified person for dedicated use of the Retro-Line system. Do not use extension cords.

1" Kit

240V 15A circuit

120V 15A circuit

OFF OFF OFF OFF OFF ON ON ON ON ON
OFF OFF OFF OFF OFF ON ON ON ON ON

1 ¼" Kit

2
· Determine point of entry into the pipe. Your Retro-Line system is ordered by system (pipe) length. (See Retro-Line Ordering Instructions on page 10).
· Cut out a section of the pipe to gain access, preferably on the inside of the building and near your power supply. (Reference chart below)
CAUTION: Care must be taken not to cut the pipe too short as it is necessary to draw the pipe into the fitting when making a joint.
Note: Do not install the Retro-Line tee connection junction point in a manner that would render the system non-serviceable. Consult Heat-Line with questions regarding installation parameters with respect to serviceability.

Remove 6 1/4" section of pipe
Important: Cut pipe square

3
· Measure the internal diameter of the polyethylene pipe and determine if it is 1 inch or 1-1/4 inch.

1

2 3 4

Measure inside diameter of pipe

5

6

7

8

9

10 11 12

4
· Select the appropriate inserts for the pipe size but DO NOT insert them at this time.
1" Kit C

B
A
A 2 Red inserts B 2 Red collets C 2 Reducing cones

1 ¼" Kit B
A

A 2 Red inserts B 2 Red collets

11 of 20

Retro-Line Installation
5
· Slide the large black nut, reducing cone (1" only), and the red collet onto the pipe being freeze protected.

· If the pipe is within a sleeve coming up through the floor be sure to fill the conduit void with a rag during this process to prevent the nut from sliding into the conduit. You may not be able able to get it back!

Pipe Sleeve

Nut Reducing cone (1" only) Collet
Rag

6
· Press in both inserts.

Insert O-ring
Flat object

Reducing cone (1" only)
Collet

7
· Short Retro-Line systems may be pushed in without the use of a fish tape or rope. Longer systems may require the use of a fish tape or other installation method. For long systems a vacuum can be used to draw a sponge "mouse" through the pipe with a 1/8" mason line attached. These sponges can be hand made or purchased from Heat-Line. Extra long systems may require "cutting in" a coupling or series of couplings to provide access points to pull in the Retro-Line. When this is required it is important to use a Philmac® coupling furnished by Heat-Line.
· A 6 foot leader is provided with all Retro-Line systems over 90 feet. This leader is your point of attachment for pulling in the Retro-Line. If the leader is not required, remove it and simply push in the Retro-Line into the pipe.
· A non-toxic (potable) lubricant can be used to make cable insertion or pushing of long lengths easier.
NOTE: Retro-Line systems in reasonably straight runs up to 150 feet can most often be pushed all the way in without pulling. The Retro-Line leader is only provided as an aid to pulling. It is unable to withstand extremely hard pulls and will break if over stressed. Heat-Line will not be responsible should this occur.
8
· Slowly push/pull the Retro-Line into the pipe off of the reel. Upon total heater insertion, break open the reel at perforations, or lift tabs to remove lid as shown.
· Do not use sharp instruments. Finish insertion of the Retro-Line until the Philmac fitting comes up tight.

Fish Tape Method

6 ft leader

Fish tape

Heating cable

Vacuum Method
Vacuum hose

Sponge (mouse)

1/8" Mason line

6 ft leader Inside Outside

12 of 20

9 Installing a Philmac Fitting
· Push fitting onto pipe with insert and 0-ring. Slide split collet and nut up to the fitting and engage thread.
NOTE: DO NOT tighten nut where electrical comes out as this is done in factory.

Retro-Line Installation
10
· Engage Tee fitting into place and tighten the black nut hand tight. Then tighten with a wrench. Do not over tighten. It is an O-ring fitting.
NOTE: DO NOT tighten nut where electrical comes out as this is done in factory.

11
· If used, remove the 6' leader. Cut off the knot and remove from pipe by pulling on the side that moves easiest.
· After all plumbing fittings have been completely installed, check the operation of the pressure system.

Removing the 6 foot leader

12
· After all plumbing fittings have been completely installed, a licensed trades-person should observe the installation and certify that the Philmac fitting has made a secure compression. Pressure testing the system prior to service is highly recommended to ensure a proper connection.
Refer to control devices and insulation installation on page 16.
· It is now time to energize your Retro-Line system. Carefully follow the Electrical System Check instructions on Page 14/15.

13 of 20

Retro-Line Installation
Electrical System Connection
Electrical Connection for GFC (Ground Fault Plug-in) Models
A. Unpack the Retro-Line system plug from its protective package. B. Plug into your dedicated outlet. 120V 5-15R outlet for 120V
systems or 240V 6-15R outlet for 240V systems. C. Push reset button on the cord set ground fault device until light
comes ON. If light does not illuminate check power to outlet. Do not remove or tamper with the cord set. If used with a thermostat it may be necessary to bypass the thermostat control and plug directly into receptacle to perform test. D. Push test button and light will go OFF. This indicates that the electrical circuit is intact and fully protected. E. Push reset button again and light will come ON. This indicates that your Retro-Line is working. F. Follow this test procedure before each season and monthly while in use. Your Retro-Line is now fully functional. If at any time your Retro-Line system fails to work call your local electrician or HeatLine for assistance at 1-800-584-4944.
Unplug when not in use.

(120V 15A example shown)
Pilot light
RESET TEST Note: GFCI model supplied may be different than the one shown.

Electrical Connection for CS (Cord-Set) Models into Junction Box

Note: The "CS" version is designed to be installed by a qualified electrician and must be inspected by the governing electrical authority following completion of installation.
A. Ensure the Retro-Line system will be operated on a dedicated ground fault protected circuit with over-current protection appropriate for the circuit conductor size and heating cable length.
B. Confirm power is disconnected at the power supply prior to proceeding.
C. Remove approved junction box cover.
D. Route the Retro-Line cord-set wires into box with the supplied strain relief fitting.
E. Connect appropriate wires together using approved wire nuts. Match wires white to white, black to black, and green to green. In the case of a metal junction box/enclosure, match green to ground screw and confirm screw is tight and secured afterward.

F. Double check that the wires have been connected correctly and tight.
G. Install junction box cover.
H. Establish power to the circuit and test/reset the ground fault device for proper operation.
I. Test the GFCI at the breaker before each season and monthly while in use.
Your Retro-Line system is now fully functional.
If at any time your Retro-Line system fails to work call your local electrician or Heat-Line for assistance at 1-800-584-4944.

Non-Metal Junction Box

Metal Junction Box

Ground (green)

G (green) L2/N (white)

Ground

GFP Fault

ZSCT

Protection

ST

L (black)

Enclosure ground
Ground (green)

G (green) L2/N (white)

Ground

GFP Fault

ZSCT

Protection

ST

L (black)

14 of 20

Retro-Line Installation

Electrical Connection for CS models installed with the optional GFA-STAT (FPT-130)

A. Ensure the Retro-Line system will be operated on a dedicated circuit with over-current protection appropriate for the circuit conductor size and heating cable length. Note: GFA-STAT (FPT-130) includes ground fault protection.
B. Confirm power is disconnected at the power supply prior to proceeding.
C. Remove front cover of the GFA-STAT. D. Remove black strain relief from the Retro-Line power cord. E. Route the Retro-Line cord-set wires through strain relief fitting
supplied with the GFA-STAT. F. Follow electrical guidelines per the GFA-STAT (FPT-130)
manual included with your GFA-STAT unit. G. Double check that the wires have been connected correctly. H. Establish power to the circuit and test/reset the ground fault
device for proper operation. I. Test the GFA-STAT GFCI before each season and monthly while in use. Your Retro-Line system is now fully functional. If at any time your Retro-Line system fails to work call your local electrician or Heat-Line for assistance at 1-800-584-4944.

GFA-STAT

Input power

Heating cable

L2/N (white) Ground L2/N (white)

L (black)

(green)

L (black)

Optional alarm
Temperature sensor

Input power

Black

Heating cable
White Black Alarm Temperature sensor

15 of 20

Retro-Line Installation
Control Devices and Insulation Installation
Control devices are not required to operate the heating cable system. They can be added for energy efficiency.
Thermostats are used to duty cycle the system in an on/off operation saving power consumption and maintain a certain pipe temperature. A sensor lead must be placed on the coldest section of pipe.
Timers are used to duty cycle the system in an on/off operation based on preset time intervals to save on power consumption.
Insulation is recommended for all new pipe installations, even where the pipe is to be buried.
For existing pipe applications, insulation is only required where the pipe is exposed to ambient outdoor temperatures, and/or where the pipe is above the ground. Insulation aids in heat retention making the heating cable more energy efficient and providing cold weather reliability.

Above Ground

Mount thermostat sensor on pipe,

beneath insulation 10 to 20 feet

Wall

away from building. Entire pipe

Wall

above ground must be insulated.

Building 1

Thermostat

Insulation

Pipe

sensor

Ground

Deep Buried Underground Near Building
Mount thermostat sensor beneath insulation where pipe emerges from ground Wall for ambient air temperature reading. Wall

Building 1

Insulation

Thermostat

Pipe

sensor

Ground

Building 2

Building 2 Building 1

HLA-120 thermostat
GFC model shown

Shallow Buried

Mount thermostat sensor on pipe,

beneath insulation (if insulation present)

Wall

at the coldest section of pipe.

Wall

Shallowest /

coldest

Pipe

exposure point

Ground

Thermostat sensor

Building 2

16 of 20

Retro-Line Installation

Limited Warranty

During the time periods and subject to the conditions hereinafter set forth. Heat-Line will repair or replace to the original user any portion of your Retro-Line product which proves defective in materials or workmanship of Heat-Line. Contact Heat-Line or your installer for warranty service.
At all times Heat-Line shall have and possess the sole right and option to determine whether to repair or replace defective equipment, parts or components. Damage due to natural events or conditions beyond the control of HeatLine are NOT COVERED BY THIS WARRANTY.
STANDARD WARRANTY PERIOD: 60 months from date of purchase or 63 months from date of manufacture, which ever occurs first.
EXTENDED WARRANTY PERIOD: 120 months from date of purchase or 123 months from date of manufacture, which ever occurs first.
ACCESSORIES, COMPONENTS, ELECTRONICS: Not manufactured by Heat-Line, are warranted only to the extent of original manufacturer's warranty.
LABOUR, COSTS, ETC.: Heat-Line shall in NO EVENT be responsible or liable for the cost of field labour or other charges incurred by any customer in removing and/or reaffixing any Heat-Line product, part or component thereof.

THIS WARRANTY WILL NOT APPLY:
(a) to defects or malfunctions resulting from failure to properly install, operate or maintain the unit in accordance with printed instructions provided,
(b) to failures resulting from abuse, accident or negligence;
(c) to normal maintenance services and
(d) to parts not used in accordance with applicable local codes, ordinance and good trade practices;
(e) if the unit is moved from its original installation location or
(f) if the unit is used for purposes other than for what it was designed and manufactured,
(g) to the integral ground fault device and related electronics.
PRODUCT IMPROVEMENTS: Heat-Line reserves the right to change or improve its products or any component thereof without being obligated to provide such a change or improvement for units sold and/or shipped prior to such change or improvement.
WARRANTY EXCLUSIONS: As to any Heat-Line product after the expiration of the time period of the warranty applicable thereto as set forth above. There will be no warranties including any implied warranties of merchantability or fitness for any particular purpose. No warranties or representations at any time made by any representative of Heat-Line, shall vary or expand the provisions hereof.
LIABILITY LIMITATION: In no event shall Heat-Line be liable or responsible for consequential, incidental or special damages resulting from or related in any manner to any Heat-Line product or parts thereof. In the absence of suitable proof of the purchase date, the effective date of this warranty will be based upon the date of manufacture plus 90 days.

17 of 20

Retro-Line Installation
Page intentionally left blank

© 2019 Heat-Line a division of Christopher MacLean Ltd. 08/19

Heat-Line Freeze Protection Systems 1095 Green Lake Road Algonquin Highlands, ON Canada K0M 1J1 Tel: 1-705-754-4545
1-800-584-4944 Fax: 1-705-754-4567 info@heatline.com www.heatline.com
18 of 20

Heat-Line and Retro-Line are registered trademarks of Heat-Line Corporation. Philmac is a registered trademark of Philmac Pty Ltd.
Important: All information, including illustrations, is believed to be reliable. Users, however, should independently evaluate the suitability of each product for their particular application. Heat-Line a Division of Christopher MacLean Ltd. makes no warranties as to the accuracy or completeness of the information, and disclaims any liability regarding its use. Heat-Line's only obligations are those in the Heat-Line Standard Terms and Conditions of Sale for this product, and in no case will Heat-Line be liable for any incidental, indirect, or consequential damages arising from the sale, resale, use, or misuse of the product. Specifications are subject to change without notice. In addition, Heat-Line reserves the right to make changes--without notification to Buyer-- to processing or materials that do not affect compliance with any applicable specification.

Retro-Line®
Warranty Form

CONGRATULATIONS! You have just purchased the most advanced internal freeze-protection system available on the market, backed by the finest warranty offered in the industry. Your Retro-Line system comes with a standard
5 year limited warranty with an optional 10 year limited warranty available.
~ The warranty applies only to the original purchaser of the product and is not transferable at any time for any reason. The warranty form must be filled out and returned to Heat-Line within 6 months of invoice date or unit manufactured date plus
9 months to be eligible for the 10 year extended warranty. ~

OWNER MAILING ADDRESS
Name Address

INSTALLATION ADDRESS (if different than mailing)
Name Address

City
Prov/State ¨ Canada
Country ¨ USA
Home Phone
Email

Postal/ZIP ¨ Other:

City Prov/State
Country Work/Cell

Postal/ZIP

PRODUCT INFORMATION
Product Cat.# Serial #
Length
WARRANTY INFORMATION
5 Year Limited Warranty: INCLUDED!

Installation Type:

¨ Lake/River ¨ Well ¨ Municipal ¨ Other:

¨ 10 Year Limited Warranty: $1.75 / foot ($75.00 minimum)

PAYMENT DETAILS FOR 10 YEAR LIMITED WARRANTY

System Length*
Units 1 to 550 feet = $1.75 per foot OR $75.00 minimum
* For custom lengths involving inches, round up to the nearest foot
Taxes and Currency

If Canadian Address: Provincial Tax %:

Subtotal: Tax Due:

Total in CDN Currency:

System Length*

x $ 1.75/ft

= Subtotal

If U.S. Address or Other Country: No Taxes Apply
Total in US Currency:

PAYMENT METHOD ¨ Cheque
Enclose and make out to Heat-Line for full amount

Credit Card:

¨ Mastercard or

¨ Visa

Name on Card:

Card Number: __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __

Expiration Date: __ __ __ __

19 of 20

LIMITED WARRANTY
During the time periods and subject to the conditions hereinafter set forth. Heat-Line will repair or replace to the original user any portion of your Retro-Line product which proves defective in materials or workmanship of Heat-Line. Contact Heat-Line or your installer for warranty service.
At all times Heat-Line shall have and possess the sole right and option to determine whether to repair or replace defective equipment, parts or components. Damage due to natural events or conditions beyond the control of Heat-Line are NOT COVERED BY THIS WARRANTY.
STANDARD WARRANTY PERIOD: 60 months from date of purchase or 63 months from date of manufacture, which ever occurs first.
EXTENDED WARRANTY PERIOD: 120 months from date of purchase or 123 months from date of manufacture, which ever occurs first.
ACCESSORIES, COMPONENTS, ELECTRONICS: Not manufactured by Heat-Line, are warranted only to the extent of original manufacturer's warranty.
LABOUR, COSTS, ETC.: Heat-Line shall in NO EVENT be responsible or liable for the cost of field labour or other charges incurred by any customer in removing and/or reaffixing any Heat-Line product, part or component thereof.
THIS WARRANTY WILL NOT APPLY: (a) to defects or malfunctions resulting from failure to properly install, operate
or maintain the unit in accordance with printed instructions provided,

(b) to failures resulting from abuse, accident or negligence; (c) to normal maintenance services and (d) to parts not used in accordance with applicable local codes, ordinance
and good trade practices; (e) if the unit is moved from its original installation location or (f) if the unit is used for purposes other than for what it was designed and
manufactured, (g) to the integral ground fault device and related electronics.
PRODUCT IMPROVEMENTS: Heat-Line reserves the right to change or improve its products or any component thereof without being obligated to provide such a change or improvement for units sold and/or shipped prior to such change or improvement.
WARRANTY EXCLUSIONS: As to any Heat-Line product after the expiration of the time period of the warranty applicable thereto as set forth above. There will be no warranties including any implied warranties of merchantability or fitness for any particular purpose. No warranties or representations at any time made by any representative of Heat-Line, shall vary or expand the provisions hereof.
LIABILITY LIMITATION: In no event shall Heat-Line be liable or responsible for consequential, incidental or special damages resulting from or related in any manner to any Heat-Line product or parts thereof. In the absence of suitable proof of the purchase date, the effective date of this warranty will be based upon the date of manufacture plus 90 days.

PROOF OF PURCHASE
If a proof of purchase copy is submitted with this warranty application form, the warranty period will be effective as of invoice date. In the absence of suitable proof of purchase, the effective date of this warranty will be based upon the date of unit manufacture plus 3 months.
Proof of purchase (invoice) attached: ¨ Yes ¨ No
By signing below you acknowledge you have read and understand the full limited warranty document.

Signed:

Dated:
The warranty form must be filled out and returned to Heat-Line within 6 months of invoice date or unit manufactured date plus 9 months to be eligible for 10 year extended warranty.

© 2019 Heat-Line a division of Christopher MacLean Ltd. 08/19

Heat-Line Freeze Protection Systems 1095 Green Lake Road / Algonquin Highlands, / ON Canada
20 of 20

K0M 1J1

Heat-Line and Retro-Line are registered trademarks of Heat-Line Corporation.
/ info@heatline.com / www.heatline.com


Adobe PDF Library 15.0 Adobe InDesign 14.0 (Macintosh)