2018 Catalog
Easergy P3
Network Protection Relays

PM106568

General Contents

Range description

6

Easergy P3 Standard

28

Easergy P3 Advanced

48

Easergy digital experience

78

Additional modules and accessories

88

Schneider Electric service

98

Ordering

102

schneider-electric.com

Easergy P3 Catalog | 3

Take the Easergy P3 further with EcoStruxtureTM

450,000
EcoStruxureTM systems deployed since 2007 with the support of our 9,000 system integrators.
Efficient asset management
Boost your efficiency and reduce downtime using predictive maintenance tools.

EcoStruxureTM architecture and interoperable technology platform bring together energy, automation, and software. This provides you with enhanced value through greater safety, reliability, efficiency, sustainability, and connectivity.
Turn data into action
EcoStruxureTM architecture lets you maximize the value of your data.
It helps you:: � Translate data into actionable intelligence and better business decisions � Make informed decisions to secure uptime and operational efficiency thanks to
real-time control platforms � Get visibility into your electrical distribution by measuring, collecting,
aggregating, and communicating data

24/7 connectivity
Make better informed decisions with real-time data that's available everywhere, anytime.
Increased safety
Enhance your people and equipment's safety with embedded arc flash protection that's based on proven designs and experience.

Connect

Collect

Analyze

Take action

Connect everything, from shop floor to top floor

Capture critical data at every level,
from sensor to cloud

Convert data into meaningful analytics

Drive action through real-time information and
business logic

CLOSE THE LOOP

End-to-End Cybersecurity Cloud and/or
On Premise

EcoStruxure Platform

Building

Data Center

Industry

Apps, analytics, and services Edge control
Connected products

Infrastructure

EcoStruxureTM Building

EcoStruxureTM Power

EcoStruxureTM IT

EcoStruxureTM Machine

EcoStruxureTM Plant

EcoStruxureTM Grid

4 | Easergy P3 Catalog

schneider-electric.com

PM106574 PM106572

Easergy P3 at a glance

What is Easergy P3?
Easergy P3 is a complete range of protection relays for medium voltage applications, including feeder, motor, transformer, and generator protection. It embeds all the latest communication protocols on serial or Ethernet links.
Based on more than 100 years of experience in network protection relays, Easergy P3 benefits from the reliability of Sepam, MiCOM and Vamp.

Unparalleled Efficiency

Better Connectivity

Enhanced Safety

� Simple selection and ordering with EcoReal MV
� Simplified configuration with the new eSetup Easergy Pro setting tool
� Faster delivery with on-the-shelf availability of standard configurations

� Simpler operation and maintenance with the Easergy SmartApp
� 9 communication protocols in one box, including IEC 61850
� Increased number of inputs and outputs for more possibilities

� Embedded arc protection � Built-in virtual injection testing � Compliant with international
standards (i.e. IEC 60255-1)

Range overview

P3G30/P3G32
Generator di erential

P3U30
Universal

P3T32
Transformer di erential

P3U30
Universal

P3F30/P3L30
Directional & Line di .

P3U30
Universal

P3M30/P3M32
Motor di erential

T
GG U
T

UL

L

F

U

U

U

U

UU

M

UL

L

GU M M

DM105528

schneider-electric.com

Easergy P3 Catalog | 5

Easergy P3 Range description

6 | Easergy P3 Catalog

schneider-electric.com

Easergy P3 Range description

Overview

8

Selection guide

9

Selection guide by application

12

Arc flash application

12

Feeder/incomer application

13

Motor application

15

Transformer application

16

Generator application

18

Capacitor application

19

Communication Examples of network architectures

21

schneider-electric.com

Easergy P3 Catalog | 7

PM106572

PM106574

Range description
Easergy P3 Standard Easergy P3 Advanced

Overview
Easergy P3 is a family of digital protection relays for distribution networks dedicated to:
� Buildings and Industry: �� Retail �� Hotels �� Healthcare �� Education and research �� Transportation �� Industrial buildings �� Data Center
� Utilities - Energy distribution � Large sites:
�� Oil and Gas �� Mining �� Mineral and Metals �� Water
Easergy P3 protection relay is based on proven technology concepts and developed in close cooperation with customers, so it's built to meet your toughest demands. It's available in two sizes to best fit your needs: � The Easergy P3 Standard combines protection functions such as directional
earth fault for feeder and motor protection in a one-box solution. � The Easergy P3 Advanced features a modular design that allows user-defined
conventional protection and arc flash protection solutions in both new and existing power distribution systems.
Easergy products are designed to be user friendly, a feature that is proven in our customer reports day after day. You'll benefit from features that include: � A complete set of protection functions, related to the application � Arc detection (Easergy P3 Advanced) � Dedicated circuit breaker control with single-line diagram, push buttons,
programmable function key and LEDs, and a customizable alarm � Multilingual HMI for customized messaging � Settings tool relay management software for setting parameters, configuring,
and network fault simulation � Both serial and Ethernet communication, including redundancy � IEC 61850 standard Ed.1 & Ed.2

8 | Easergy P3 Catalog

schneider-electric.com

Range description

Selection guide

Easergy P3 contains
Two main devices, each with specific functions to address your needs in a one-box design, regardless of application.

Easergy P3 Standard

Easergy P3 Advanced

Feeder

Transformer

Motor

Generator
Characteristics Phase current

Measuring inputs Residual current

Voltage

Arc-flash sensor input

Digital

Input Output

Analogue

Input Output

Temperature sensor input

Front port

Nominal power supply

Ambient temperature, in service

Communication

Rear ports RS232, IRIG/B, RS485, Ethernet

IEC61850 ed1 & ed2

IEC 60870-5-101 & 103

DNP3 over Ethernet

DNP3 serial

Protocols

Modbus serial Modbus over Ethernet

Ethernet IP

DeviceNet

Profibus DP

SPAbus

Redundancy protocols (RSTP/PRP)

Others

Control

Logic (Matrix + Logic equation) Withdrawable CT connector with shorting Remote HMI Hardware dimensions (W/H/D)

P3U10

P3U20

P3U30
with directional O/C with voltage protection

1/5A CT (x3)

1/5A CT or 0.2/1A CT

VT (x1)

VT (x4)

-

2

10

16

5 + SF

5 + SF

8 + SF

-

0 or 4 (1)

-

0 or 4 (1)

-

0 or 8 or 12 (1)

USB type B

24V dc or 48-230V ac/dc

-40 to 60�C (-40 to 140�F)

P3F30
with directional
P3L30
line diff. & distance
-
P3M30
P3G30

-
P3T32
with differencial
P3M32
with differencial
P3G32
with differencial

1/5A CT (x3)

1/5A CT (x6)

1/5A CT & 1A CT or
1A CT & 0.2A CT

1/5ACT (x2) & 1A CT or
1/5A CT & 1A CT & 0.2A CT

VT (x4)

VT (x4)

4 point sensor (1) (2)

4 point sensor (1)

6 to 36

6 to 16

10 to 21 + SF

10 to 13 + SF

0 or 4 (1)

0 or 4 (1)

0 or 8 or 12 (1)

USB type B

24 to 48V dc or 110-240V ac/dc

-40 to 60�C (-40 to 140�F)

-
-

1 object mimic

6 controlled + 2 monitored objects mimic

6 controlled + 2 monitored objects mimic

171 x 176 x 214(3) mm / 6.73 x 6.93 x 8.43 in

-
264 x 177 x 208 mm / 10.39 x 6.97 x 8.19 in (1) Depends on optional module (2) Arc flash protection option not available on Easergy P3L30 (3) 226 mm (8.90 in) with ring-lug connectors

schneider-electric.com

Easergy P3 Catalog | 9

Range description

Selection guide

Standard (P3U)

Advanced (P3x)

Protection functions

ANSI code

P3U10 P3U30 P3U20

P3F30 P3L30 P3M30 P3M32 P3G30 P3G32 P3T32

Distance Under-impedance Fault locator Overfluxing Synchro-check Undervoltage Positive sequence undervoltage Stator earth-fault detection Directional active underpower Phase undercurrent Temperature monitoring Loss of field Under-reactance Negative sequence overcurrent (motor, generator) Cur. unbalance, broken conductor Incorrect phase sequence Excessive start time, locked rotor Thermal overload Phase overcurrent Earth fault overcurrent Breaker failure Switch On To Fault (SOTF) Capacitor bank unbalance Voltage dependant overcurrent Overvoltage Capacitor overvoltage Neutral voltage displacement CT supervision VT supervision Stator earth fault Frequent start inhibition Directional phase overcurrent Directional earth-fault o/c Transient intermittent Magnetizing inrush detection Fifth harmonic detection Pole slip Auto-recloser Over or under frequency Rate of change of frequency Under frequency Lockout Line differential Machine differential Transformer differential Programmable stages Arc-flash detection stages Cold load pick-up Programmable curves Setting groups (3)

21 21G 21FL 24 25 27 27P 27TN/64G 32 37 38/49T 40 21/40
46
46BC 47 48/51LR 49 50/51 50N/51N 50BF 50HS 51C 51V 59 59C 59N 60 60FL 64S 66 67 67N 67NI 68F2 68H5 78PS 79 81 81R 81U 86 87L 87M 87T 99

-
-
1 12 (0)(1) -
2
1 1 1 3 5 1 1 1 1 3 1 1 3 1 1 1 5 1 8 1 3 4

1 2 3 2 1 12 (1) -
2
1 1 1 3 5 1 1 1 1 3 1 3 1 1 1 4 3 1 1 1 5 2/2 1 2 1 8 1 3 4

1 2 3 2 12 (1) -
-
1 1 3 5 1 1 2 1 3 1 2 1 1 4 3 1 1 1 5 2/2 1 2 1 8 8 1 3 4

1 1 2 3 2 12 (1) -
-
1 1 3 5 1 1 2 1 3 1 2 1 1 4 3 1 1 1 5 2/2 1 2 1 2 8 1 3 4

2 3 2 1 12 (1) -
2
1 1 1 3 5 1 1 2 3 2 1 1 1 4 3 1 1 2/2 1 2 1 8 8 1 3 4

2 3 2 1 12 (1) -
2
1 1 1 3 5 1 1 2 3 2 1 1 1 4 3 1 1 2/2 1 2 1 2 8 8 1 3 4

2 1 2 3 2 1 2 12 (1) 1 2
2
1 3 5 1 1 2 1 3 2 1 1 1 4 3 1 1 1 2/2 1 2 1 8 8 1 3 4

2 1 2 3 2 1 2 12 (1) 1 2
2
1 3 5 1 1 2 1 3 2 2 1 1 4 3 1 1 1 2/2 1 2 1 2 8 8 1 3 4

1 2 3 2 12 (1) -
2
1 3 5 1 1 2 3 2 2 1 4 3 1 1 2/2 1 2 1 2 8 8 1 3 4

(0) No temperature sensors for P3U10 and 12 optional for P3U20 (1) Using external RTD module

(2) P3U10 and P3U20 offer one voltage input. Function availability depends on the connection of the voltage input (3) Not all protection functions have 4 setting groups. See details in the manual.

10 | Easergy P3 Catalog

schneider-electric.com

Range description

Selection guide

Control functions Switchgear control and monitoring Switchgear monitoring only Programmable switchgear interlocking Local control on single-line diagram Local control with O/I keys Local/remote function Function keys Custom logic (logic equations) Control with Smart App
Measurement
RMS current values RMS voltage values RMS active, reactive and apparent power Frequency Fundamental frequency current values Fundamental frequency voltage values Fundamental frequency active, reactive and apparent power values Power factor Energy values active and reactive Energy transmitted with pulse outputs Demand values: phase currents Demand values: active, reactive, apparent power and power factor Min and max demand values: phase currents Min and max demand values: RMS phase currents Min and max demand values: active, reactive, apparent power and power factor Maximum demand values over the last 31 days and 12 months: active, reactive, apparent power Minimum demand values over the last 31 days and 12 months: active, reactive power Max and min values: currents Max and min values: voltages Max and min values: frequency Max and min values: active, reactive, apparent power and power factor Harmonic values of phase current and THD Harmonic values of voltage and THD Voltage sags and swells
Logs and Records Sequence of event record Disturbance record Tripping context record
Monitoring functions Trip circuit supervision (ANSI 74) Circuit breaker monitoring Relay monitoring
(1) Function available on both sets of CT inputs

Standard (P3U)

P3U10 P3U30 P3U20

1/6

6

2

2

2

2

-
-
-
-

1

1

1

1

Advanced (P3x) P3F30 P3L30

6

6

2

2

2

2

1

1

1

1

P3M30 6 2 2
1 1

P3M32 6 2 2
(1) (1)
(1)
1 1

P3G30 6 2 2
1 1

P3G32 6 2 2
(1) (1)
(1)
1 1

P3T32 6 2 2
(1) (1)
(1)
1 1

schneider-electric.com

Easergy P3 Catalog | 11

Range description

Selection guide by application
Arc flash application

Busbar arc protection

� Arc protection, activated by overcurrent and light signals, or light signals alone

Centralized busbar arc protection

De-centralized busbar arc protection

DM105536

DM105535

P3F30 P3G30 P3T32 P3G32

P3F30 P3G30 P3T32 P3G32

� Up to 4 light point sensors to monitor the busbar

P3F30 P3T32

P3M30 P3M32

� Up to 4 light point sensors in each relay � Transmission of light detection signals via digital I/O or
IEC 61850 GOOSE messages

Zone arc protection � Up to 8 arc protection stages in each relay

DM105537

Zone 1

P3F30 P3G30 P3T32 P3G32

Zone 1 light detection signal

Zone 2 Zone 3.1

P3F30 P3T32

Zone 3.2

P3M30 P3M32

� Light detection in zone 1: signal sent to upstream relay for tripping
� Light detection in zone 2: incomer Easergy P3 trips, if fault confirmed by overcurrent
� Light detection in zone 3: corresponding outgoing Easergy P3 trips, if fault confirmed by overcurrent

12 | Easergy P3 Catalog

schneider-electric.com

Range description

Selection guide by application
Feeder/incomer application

Outgoing protection
� Feeder overcurrent protection � Feeder overload protection
Protection of low-capacitance feeders in impedance-earthed or solidly-earthed neutral systems

Protection of high-capacitance feeders in impedance-earthed or compensated or isolated neutral systems

Protection of feeders with metering

DM105538 DM105539 DM105540

P3U10 P3U20 P3U30

P3F30

� Feeder earth-fault overcurrent

P3U10 P3U20 P3U30

P3F30

� Directional earth-fault overcurrent � Transient intermittent earth-fault

Incomer protection � Busbar overcurrent protection Incomer protection without voltage monitoring

DM105542

DM105541

P3U10 P3U20 P3U30

P3F30

P3U10 P3U20 P3U30

P3F30

P3U30

P3F30

� Power and energy measurement � Min and max demand values over the last
31 days and 12 months

Incomer protection with voltage and frequency monitoring

DM105543

P3U30

P3F30

� Earth-fault overcurrent
Incomer protection with power quality monitoring

� Neutral voltage displacement protection for isolated system
Parallel incomer protection

� Under/over voltage � Frequency, rate of change of frequency

DM105545

DM105544

P3U30

P3F30

P3U30

P3F30

P3U30

P3F30

� Voltage and frequency min and max values � Voltage harmonic values and THD � Voltage sags and swells

� Directional phase overcurrent � Directional earth-fault overcurrent

schneider-electric.com

Easergy P3 Catalog | 13

Range description

Selection guide by application
Feeder/incomer application

Line protection

� Overcurrent and earth-fault protection (directional and non-directional) � Feeder overload protection

Overhead line protection

Incomer protection with fault locator

Line protection with line differential and distance functions

DM105546 DM105547 DM105548

P3U30

P3F30 P3L30

� Recloser � Feeder fault locator

P3F30
� Incomer fault locator

P3L30
� Line differential protection � Distance protection

14 | Easergy P3 Catalog

schneider-electric.com

Range description

Selection guide by application
Motor application

Motor protection

� Motor overcurrent and earth-fault overcurrent � Thermal overload � Motor start-up supervision � Motor restart inhibition

Motor protection without voltage monitoring

Motor protection with voltage monitoring

Motor protection with differential function

DM105549 DM105550 DM105551

P3U20 P3U30

P3M30

RTD module

P3U30

P3M30

P3M32

� Temperature measurement (stator, bearings)

� Undervoltage protection

� Differential protection

Motor-transformer unit protection
� Motor-transformer overcurrent � Transformer earth-fault overcurrent � Thermal overload � Motor start-up supervision � Motor restart inhibition � External trip from thermostat/Buchholz
Motor-transformer unit protection

Motor-transformer unit protection with differential function

DM105552 DM105553

P3U30

P3M30

26 63 49T
RTD module

� Temperature measurement (stator, bearings)
� Motor neutral point displacement

P3M32 26 63 49T
� Differential protection � Motor earth-fault overcurrent

schneider-electric.com

Easergy P3 Catalog | 15

Range description

Selection guide by application
Transformer application

Transformer feeder protection

� Transformer overcurrent and earth-fault overcurrent protection � Thermal overload protection � External trip from thermostat/Buchholz

Transformer feeder protection

Transformer feeder protection without voltage monitoring

Transformer feeder protection with voltage monitoring

DM105554 DM105555 DM105556

P3U10 P3U20 P3U30
26 63 49T

P3F30

P3U20 P3U30
26 63

P3F30

RTD module

� Directional earth-fault overcurrent for impedance earthed or compensated neutral systems

� Temperature measurement (ambient, oil)

Transformer feeder protection with additional current measurement

P3U30
26 63 49T

P3F30

� Over and undervoltage protection

Transformer feeder protection with differential function

DM105557 DM105558 DM105559

P3F30 26 63 49T
� Tank earth-leakage protection

P3F30
26 63 49T

P3T32
26 63 49T

� Earth-fault overcurrent on the secondary side

� Differential protection � Restricted earth-fault protection
(high impedance)

16 | Easergy P3 Catalog

schneider-electric.com

Range description

Selection guide by application
Transformer application

Transformer incomer protection � Busbar overcurrent protection � Inter-trip from primary CB protection Transformer incomer protection without voltage monitoring

Transformer feeder protection with voltage monitoring

DM105560 DM105561 DM105562

P3U10 P3U20 P3U30

P3F30

P3U10 P3U20 P3U30

P3F30

P3U30

P3F30

� Transformer earth-fault overcurrent

� Earth-fault overcurrent for transformer and back-up protection

Parallel transformer incomer protection

� Over and undervoltage protection � Power and energy measurement � Min and max demand values over the last
31 days and 12 months
Transformer incomer protection with differential function overcurrent

DM105563 DM105564

P3U30

P3F30

P3U30

P3F30

� Directional phase overcurrent

P3T32
� Transformer differential overcurrent � Restricted earth-fault overcurrent
(high impedance)

schneider-electric.com

Easergy P3 Catalog | 17

Range description

Selection guide by application
Generator application

Small generator transformer unit protection
� Overcurrent protection of the supplied network � Voltage and frequency monitoring � External trip from thermostat/Buchholz
Protection of a stand-alone generator-transformer unit

DM105565

26 63 49T

P3U30

P3G30

DM105566

26 63 49T

P3U30

P3G30

� Earth-fault overcurrent protection of the supplied network Note: monitoring of generator insulation must be ensured by another device

� Earth-fault overcurrent protection of the generator � Earth-fault overcurrent protection of the supplied network

Protection of a generator-transformer unit coupled to another source

DM105568

DM105567

26 63 49T

P3U30

P3G30

26 63 49T
P3G30

� Earth-fault overcurrent protection of the transformer � Neutral voltage displacement to detect transformer earth-fault
when CB is open � Synchro-check
Note: monitoring of generator insulation must be ensured by another device

� Earth-fault overcurrent protection of the generator and the transformer
� Neutral voltage displacement to detect transformer earth-fault when CB is open
� Synchro-check

18 | Easergy P3 Catalog

schneider-electric.com

Range description

Selection guide by application
Generator application

Mid-size generator protection
� Under-impedance � Loss of field � Voltage and frequency monitoring
Protection of a generator coupled to another source

Generator protection with differential function

Generator-transformer unit protection with differential function

DM105569 DM105570 DM105571

P3G30

P3G32

26 63 49T
P3G32

� Earth-fault overcurrent protection of the generator when coupled
� Neutral voltage displacement to detect generator earth-fault when CB is open
� Synchro-check

� Stator earth-fault detection � Differential protection

� Stator earth-fault detection � Differential protection � Restricted earth-fault protection
(high impedance)

schneider-electric.com

Easergy P3 Catalog | 19

Range description

Selection guide by application
Capacitor application

Capacitor bank protection

� Capacitor bank overcurrent and earth-fault protection � Capacitor bank overload protection

Capacitor bank protection without voltage monitoring

Capacitor bank protection with voltage monitoring

Protection of harmonic filters

DM105572 DM105573 DM105574

P3U10 P3U20 P3U30

P3F30

P3U30

P3U10 P3U20 P3U30

� Capacitor overvoltage protection, based on current measurement and harmonics
� Current harmonic values and THD

� Capacitor bank unbalance � Overvoltage � Current and voltage harmonic values
and THD

� Overvoltage � Capacitor bank unbalance � Capacitor overvoltage protection, based
on current measurement and harmonics � Current harmonic values and THD

20 | Easergy P3 Catalog

schneider-electric.com

DM105575

Range description

Communication
SCADA system

HMI/ SCADA
Serial link
Relay 1

Daisy chain Relay 2

Connection to SCADA using serial line

Relay n (n max= 32)

This architecture allows you to connect HMI/SCADA to a set of Easergy protection relays using a multi-drop serial communication link with master-slave communication.
Available protocols: � Modbus RTU � IEC 60870-5-101 � IEC 60870-5-103 � DNP3 � DeviceNet � Profibus � SPAbus

Time synchronisation protocol: � IRIG-B � Minute pulse

HMI/ SCADA

Ethernet switch

Ethernet Network
Ethernet switch

SubNetwork

Connection to SCADA using Ethernet
This architecture allows you to connect a set of Easergy protection relays directly to an Ethernet network.
Available protocols: � IEC 61850 � IEC 60870-5-101 � DNP3 � Modbus � EtherNet/IP
Note: It is possible to mix on the same Ethernet network the IEC 61850 protocol with any of the 4 other protocols.
This allows you to use the GOOSE messages between relays together with another protocol for communication to SCADA.
It is also possible to connect an Easergy relay to 2 different control systems, using the same Ethernet communication port and IEC 61850 protocol for one of them and any available protocol for the other one.
The Easergy P3 relay handles the IEC 61850 station bus, in compliance with standards IEC 61850-6, 7-1, 7-2, 7-3, 7-4 and 8-1 Ed.1 or Ed.2, according to configuration.
Other available Ethernet protocols: � FTP for file transfer � SNTP for time synchronization � HTTP for web server

DM105576

schneider-electric.com

Easergy P3 Catalog | 21

DM102975

DM105575

Range description

Communication
Example of communication

Panel HMI

Ethernet switch

Ethernet
GOOSE messages

GOOSE messages

Easergy Pro

Architecture example 1
Switchboard internal network
This architecture allows fast GOOSE communication between Easergy protection relays of the switchboard, thus avoiding costly wiring. Typical uses are logic discrimination, load shedding, etc.
In addition, a panel HMI featuring a web browser can be used to monitor and control the entire switchboard.
A spare connection on the panel Ethernet switch can also be provided for connecting the Easergy Pro.

HMI/ SCADA
Serial link
Relay 1

Daisy chain Relay 2

Relay n (n max= 32)

Architecture example 2
Connection to SCADA using serial lines and legacy protocols
This architecture allows you to connect HMI/SCADA to a set of Easergy protection relays using a multi-drop serial communication link with master-slave communication protocols such as Modbus-RTU, DNP3, or IEC 61870-5-103.
The RS485 serial communication port of the Easergy protection relay enables simple daisy chaining wiring thanks to its 2 RJ45 connectors, suited for 2-wire or 4-wire cabling. A termination module is plugged into the last connection. As an alternative, the fiber optic serial communication port can be used.

HMI/ SCADA

Ethernet switch

Ethernet Network
Ethernet switch

Architecture example 3
Connection to HMI/SCADA using Ethernet with redundant paths
When using an Ethernet infrastructure for the system network, redundant paths are often created. This is usually a deliberate action to improve communication availability, but can also result from non-mastered and overly complicated network architectures.
Redundant paths, however, can result in loops that are not compatible with normal Ethernet operation because they permit frames to propagate endlessly, inducing a phenomenon known as "frame storm." Using such network topologies therefore requires the use of special management techniques.

SubNetwork

DM105576

22 | Easergy P3 Catalog

schneider-electric.com

DM105577

Range description

Communication
SCADA system

HMI/ SCADA
Ethernet switch
Ethernet switch

Ethernet switch

RSTP (Rapid Spanning Tree Protocol)
The principle of RSTP is to virtually cut all links that are not necessary at a given time, changing the meshed topology into a tree topology.
The main advantage of RSTP is that it is widespread and works on any network topology. On the other hand, RSTP takes milliseconds or seconds to reconfigure the network in case of network interruption.

Ethernet switch

HMI/ SCADA
Network A

Network B

PRP (Parallel Redundancy Protocol)
The principle of PRP is to transmit frames in parallel on two independent network infrastructures: A and B. The receiving device is in charge of eliminating the redundant frame if it is received. PRP features a 0 ms recovery time in case of failure. PRP is supported by Easergy P3 relays.

DM105578

schneider-electric.com

Easergy P3 Catalog | 23

Range description
Protocol Real-time data Measurement Alarms and status Controls Time-stamped events Historical data Disturbance records Setting management Setting group change
Protocol Real time data Measurement Alarms and status Controls Time-stamped events Historical data Disturbance records Sequence of event record files Setting management Setting group change Settings

Communication
Data exchanged between Easergy P3 and SCADA

Ethernet ports

IEC 61850

Ethernet/IP

FTP

-

-

-

Serial Ports

IEC 60870-5-103

DeviceNet

Profibus

SPAbus

-

-

-

-

-

-

-

-

-

24 | Easergy P3 Catalog

schneider-electric.com

Range description
Protocol Real-time data Measurement Alarms and status Controls Time-stamped events Setting management Setting group change

Communication
Data exchanged between Easergy P3 and SCADA

Ethernet or Serial ports

DNP3

IEC 60870-5-101

Modbus

schneider-electric.com

Easergy P3 Catalog | 25

DM105579

Range description

eSetup Easergy Pro Easergy web-HMI
Ethernet

Easergy SmartApp

Easergy Pro

Safe Repository and Schneider Electric web

Communication
Engineering system and System configuration
Engineering system
eSetup Easergy Pro eSetup Easergy Pro can be connected to a single Easergy protection relay on the front USB port or to a group of Easergy protection relays via Ethernet. eSetup Easergy Set allows you to prepare the configuration of the relay without having any physical relay. For this purpose, eSetup Easergy Pro provides the latest version of the configuration description file directly from the web.
Easergy SmartApp Easergy SmartApp can be connected to the Easergy protection relays using a Wi-Fi router. Easergy SmartApp is also connected to the safe repository, allowing you to access todocuments and store files downloaded from the relay.
Easergy web-HMI In addition to eSetup Easergy Pro, most of the resources of the relay can be accessed with a standard web browser, using the web pages embedded into the relay.

Safe Repository and Schneider Electric web

.icd file

System configurator

System configuration according to IEC 61850
The methodology described in IEC 61850-6 standard can be applied with Easergy protection relays to build a protection and control system based on this standard.
.icd file When the configuration of an Easergy protection relay is done, setting tool can generate IED capability file. This file can be used by the system configurator.

eSetup Easergy Pro

DM105580

26 | Easergy P3 Catalog

schneider-electric.com

Range description

Communication
Arc flash protection system by network communication
Arc flash protection system: Application example
In this application example, the arc flash sensor for zone 4.1 is connected to Device 1. If the arc flash sensor awakens and simultaneously Device 3 sends a current signal, the zone 4.1 is isolated by the outgoing feeder breaker. The arc flash sensor for zone 4.2 is connected to Device 2 and operates the same way. The arc flash sensors for zone 3 are connected to Device 1, 2, or 3. If a sensor awakens in zone 3, the light-only signal is transferred to Device 3, which then trips the main circuit breaker. An eventual arc flash fault in zone 1 or 2 does not necessarily activate the current element in Device 2. However, arc detection can be achieved by using the light-only principle. If an arc flash occurs in cable termination, zone 1, or zone 2, the fault is cleared by the upstream circuit breaker.
ZONE 1

DM105581

= Arc Sensor

ZONE 2

ZONE 3 ZONE 4.1

ZONE4.2

schneider-electric.com

Ethernet

IEC 61850 with GOOSE message Easergy P3 Catalog | 27

Easergy P3 Standard

28 | Easergy P3 Catalog

schneider-electric.com

Easergy P3 Standard

Presentation

30

Functional view

32

Base unit presentation

35

Local HMI

35

Rear panel connections

36

Base unit dimensions

37

Dimensions

37

Cut-out and mounting

37

Base unit characteristics

38

Technical characteristics

38

Environmental characteristics

39

Communication protocols

41

Programmable stages

42

Circuit breaker control

43

Connection diagram

44

Model selection

47

schneider-electric.com

Easergy P3 Catalog | 29

Easergy P3 Standard

Presentation

The Easergy P3 Standard protection relay has been developed to meet your standard protection needs for building, distribution utilities, and industrial applications. Thanks to its optimized and flexible design, the Easergy P3 Standard provides an excellent solution for various protection applications.

The user-friendly Easergy P3 Standard brings greater efficiency to your operations by enabling rapid ordering, configuration, and operations for an unparalleled digital experience

Easergy P3 Standard at a glance
Universal � All-in-one box with feeder, transformer, and motor protections � All communication protocols embedded on serial and Ethernet links
including IEC 61850 ed.1 and ed. 2
Robust � Best-in class reliability based on 100+ years of experience in Sepam,
MiCOM and Vamp relays � Strong tests performed in international laboratories � Compliant to IEC electro-mechanical standards
Efficient and connected � Easy to order with 10 standard configurations delivered off the shelf in
less than 7 days (location dependent) � Easy to configure with the unique eSetup Easergy Pro setting software � Easy to test with the virtual simulation test for direct injection of current
and voltage from eSetup Easergy Pro � Easy to install with withdrawable rear connectors with CT shortening � Easy to use and maintain with the embedded web-HMI and Easergy
SmartApp for direct access on site via your laptop, smartphone, or tablet.

PM106572

Easergy P3 Standard with panel seal cover REL52833

30 | Easergy P3 Catalog

schneider-electric.com

Easergy P3 Standard

Presentation

DM105529

Easergy P3 is designed to cover all the standard applications with only one device: the Universal Protection.

U

Feeder

U

U

U

U

U


Capacitor

M
Motor


Feeder


Transformer

Easergy P3 Standard is available in 3 models:

Model

Communication

Easergy P3U10 � 4 CT / 1VT � 2 DI / 5 DO

Stand-alone device, without communication ports

Easergy P3U20 � 4 CT / 1VT � 10 DI / 5 DO
Easergy P3U30 � 4 CT / 4VT � 16 DI / 8 DO

Open communication protocols on serial or Ethernet links, with IEC 61850
Open communication protocols on serial or Ethernet links, with IEC 61850

Main advantages
Simplicity, while allowing the latest features, like single-line diagrams (mimics), programmable protection stages, logics and function keys
Openness to IEC 61850, while keeping the core functionnalities of Easergy P3 Standard relay
Wide scope of possibilities, with the directional protection, synchro-check, fault location, and increased number of input and outputs

A common set of functions extends the possibilities of protection and control: � Single-line diagrams (mimic) in the display � Programmable protection stages � Programmable logics � 2 programmable function keys � Synchro-check function � Direct-access USB port � Up to 6 objects controlled

schneider-electric.com

Easergy P3 Catalog | 31

DM105583

Easergy P3 Standard

Functional view
Easergy P3U10

HMI interface
Function key F1

0 1
Control buttons

LED F1 ON LED A LED C LED E LED G

Programmable Logic

Inputs

AND

TIMER

Setting groups:4
H2/H5

Mimic Diagram
I1: 0.0A I2: 0.0A I3: 0.0A P : 0.0W V : 0.0V

F2
LED F2 Service LED B LED D LED F LED H

USB Local Port

OR

COUNTER

XOR

Output

SOTF

79

74

86

60

99

CLPU

48

37

51LR

66

REL52822

59C

50BF 59N

50

67NI

51 67N
51C

50N

49

50G

51N

46

51G

I1 / I2 / I3

Io

V/V0

Analog measurement card

Current input

Voltage input

I1 I2 I3 Io - V1 - - -

X3 Connector
DI1 DI2 SF T1 T2 T3 T4 A1
Power Supply

eSetup Easergy Pro

Circuit Breaker controls

32 | Easergy P3 Catalog

schneider-electric.com

DM105584 RS232 RS232 RS232

Easergy P3 Standard

Functional view
Easergy P3U20

HMI interface
Function key F1

0 1
Control buttons

LED F1 ON LED A LED C LED E LED G

Programmable Logic

Inputs

AND

TIMER

Mimic Diagram
I1: 0.0A I2: 0.0A I3: 0.0A P : 0.0W V : 0.0V

F2
LED F2 Service LED B LED D LED F LED H

USB Local Port

OR

COUNTER

XOR

Output

Setting groups:4
H2/H5

SOTF

79

74

CLPU

T

38

E

49T

M

P

86

60

99

Comm. interface - X4

Protocols
� Modbus � DNP3.0 � IEC-103 � SPAbus

RS485

48

37

51LR

66

REL52822

eSetup Easergy Pro

Comm. interface - X4

Redundancy

Protocols

� RSTP � PRP
Two protocols at the same time

WebServer

� IEC 61850 � Modbus � DNP3.0 � IEC-101 � Ethernet/IP

Comm. interface - X4

Redundancy

LC

LC

Protocols

� RSTP

� IEC 61850

� PRP

� Modbus

Two protocols at the same time

WebServer

� DNP3.0 � IEC-101 � Ethernet/IP

OR

Protocols
� IEC 61850 � Modbus � DNP3.0 � IEC-101 � Ethernet/IP

Comm. interface - X4

LC

Two protocols at the same time

RS232 +

WebServer

IRIG-B

Protocols
� IEC 61850 � Modbus � DNP3.0 � IEC-101 � Ethernet/IP

Comm. interface - X4

Two protocols at the same time
WebServer

RS232 + IRIG-B

59C

50BF 59N

50

67NI

51 67N
51C

50N

49

50G

51N

46

51G

I1 / I2 / I3

Io

V/V0

Analog measurement card

Current input

Voltage input

I1 I2 I3 Io - V1 - - -

X4 Connector
DI3 DI4 DI5 DI6 DI7 DI8 DI9 DI10
X3 Connector
DI1 DI2 SF T1 T2 T3 T4 A1
Power Supply

Other type of controls

Other type of controls

Circuit Breaker controls

REL52820

Connect to RS232 port
REL52816 REL52819

REL52821

Protocols Modbus DNP3.0 IEC-103
RS485

Protocols
Modbus DNP3.0 IEC-103 SPAbus

Protocols DeviceNet
RS485

Serial
Serial network

OR

REL52812
RS485

RTD CH01 RTD CH02 RTD CH03 RTD CH04 RTD CH05 RTD CH06 RTD CH07 RTD CH08 RTD CH09 RTD CH10 RTD CH11 RTD CH12

OR

REL52813 REL52814
RS485 Rx

Tx
Fiber Rx
Tx

PTC RTD CH01

RTD CH02 mA In1
RTD CH03 mA In2
RTD CH04 mA In3
RTD CH05
mA In4 RTD CH06

RTD CH07 mA OUT1
RTD CH08 mA OUT2
RTD CH09 mA OUT3
RTD CH10 mA OUT4
RTD CH11

RTD CH12

schneider-electric.com

Easergy P3 Catalog | 33

DM105585 RS232 RS232 RS232

Easergy P3 Standard

Functional view
Easergy P3U30

HMI interface
Function key F1

0 1
Control buttons

LED F1 ON LED A LED C LED E LED G

Programmable Logic

Inputs

AND

TIMER

Mimic Diagram
I1: 0.0A I2: 0.0A I3: 0.0A P : 0.0W V : 0.0V

F2
LED F2 Service LED B LED D LED F LED H

USB Local Port

OR

COUNTER

XOR

Output

Setting groups:4
H2/H5

SOTF

79

74

CLPU

T

38

E

49T

M

P

86

60

99

Comm. interface - X4

Protocols
� Modbus � DNP3.0 � IEC-103 � SPAbus

RS485

48

37

51LR

66

REL52822

eSetup Easergy Pro

Comm. interface - X4

Redundancy

Protocols

� RSTP � PRP
Two protocols at the same time

WebServer

� IEC 61850 � Modbus � DNP3.0 � IEC-101 � Ethernet/IP

Comm. interface - X4

Redundancy

LC

LC

Protocols

� RSTP

� IEC 61850

� PRP

� Modbus

Two protocols at the same time

WebServer

� DNP3.0 � IEC-101 � Ethernet/IP

OR

Protocols
� IEC 61850 � Modbus � DNP3.0 � IEC-101 � Ethernet/IP

Comm. interface - X4

LC

Two protocols at the same time

RS232 +

WebServer

IRIG-B

Protocols
� IEC 61850 � Modbus � DNP3.0 � IEC-101 � Ethernet/IP

Comm. interface - X4

Two protocols at the same time
WebServer

RS232 + IRIG-B

67

21FL

37P

50BF 50 51 51C

67NI 67N

59C

X5 Connector

DI13

DI16

59N

T5 T6 T7 DI11 DI12 DI14 DI15

81R 25

X4 Connector

81

DI3 DI4 DI5 DI6 DI7 DI8 DI9 DI10

81U

50N

49

50G

59

51N

46

51G

27

X3 Connector
DI1 DI2
SF T1 T2 T3 T4 A1

I1 / I2 / I3

Io

V / V0 V4

Analog measurement card

Current input

Voltage input

I1 I2 I3 Io

V1 V2 V3 V0

Power Supply

Other type of controls

Other type of controls

Circuit Breaker controls

REL52820

Connect to RS232 port
REL52816 REL52819

REL52821

Protocols Modbus DNP3.0 IEC-103
RS485

Protocols
Modbus DNP3.0 IEC-103 SPAbus

Protocols DeviceNet
RS485

Serial
Serial network

OR

REL52812
RS485

RTD CH01 RTD CH02 RTD CH03 RTD CH04 RTD CH05 RTD CH06 RTD CH07 RTD CH08 RTD CH09 RTD CH10 RTD CH11 RTD CH12

OR

REL52813 REL52814
RS485 Rx

Tx
Fiber Rx
Tx

PTC RTD CH01

RTD CH02 mA In1
RTD CH03 mA In2
RTD CH04 mA In3
RTD CH05
mA In4 RTD CH06

RTD CH07 mA OUT1
RTD CH08 mA OUT2
RTD CH09 mA OUT3
RTD CH10 mA OUT4
RTD CH11

RTD CH12

34 | Easergy P3 Catalog

schneider-electric.com

DM105586

Easergy P3 Standard

Base unit presentation
Local HMI

Mimic Diagram I1: 0.0A I2: 0.0A I3: 0.0A P : 0.0W V : 0.0V
Single-line diagram of the power system

Comprehensive data for fast and easier operation
All the data required for a local equipment operation may be displayed on demand: � Display the single-line diagram and freely assignable analog values � Display of all measurements � Display of operation and alarm messages � Display and setting of all parameters � Entry of password to protect parameter and protection settings
Ergonomic data presentation
� Keypad keys identified by pictograms for intuitive navigation � Graphical 128x64 LCD screen to display any character or symbol � Excellent display quality under all lighting conditions � Control buttons (0/1) to operate the circuit breaker and/or other controlled object � 8 freely programmable LEDs to identify easily the message showed � Labels are printed on a transparent film allowing customization of the relay � Programmable function key (F1 / F2)

PM106367

Front panel: Control and push-buttons
INFO push-button for viewing additional information, entering the password view, and adjusting the LCD contrast
F1 Programmable function push-button

F2 Programmable function push-button
ENTER push-button for activating or OK confirming a function
UP navigation push-button for moving up in the menu or increasing a numerical value
DOWN navigation push-button for moving down in the menu or decreasing a numerical value
LEFT navigation push-button for moving backwards in a parallel menu or selecting a digit in a numerical value
RIGHT navigation push-button for moving forwards in a parallel menu or selecting a digit in a numerical value
O Circuit breaker OFF push-button

128 x 64 LCD Object control buttons

Local port Navigation push-buttons
LED indicators

Circuit breaker ON push-button
HOME/CANCEL push-button for returning to the previous menu. To return to the first menu item in the main menu, press the button for at least three seconds

Working language
All the texts and messages displayed on the Easergy P3U are available in two languages at the same time. Consult us for availability.

schneider-electric.com

Easergy P3 Catalog | 35

Easergy P3 Standard
Rear panels views

Base unit presentation
Rear panel connections

PM106500 PM106501 PM106338

Easergy P3U10
Withdrawable connectors

Easergy P3U20

Easergy P3U30

DM105587 DM105588
PM106500

Optional terminal X1: Pluggable screw clamp connector

Optional terminal X1: Pluggable ring-lug connector

36 | Easergy P3 Catalog

schneider-electric.com

Easergy P3 Standard

Base unit dimensions

Weight (maximum) Easergy P3U10 / P3U20 / P3U30 2.5 Kg (5.519 Ib)
Degree of protection (IEC 60529) IP54 Front panel / IP20 Rear side

With screw connector
With ring-lug connector

A 214 mm / 8.43''

B 192 mm / 7.6''

226 mm / 8.90'' 204 mm / 8.0''

Cut-out and mounting

Cut-out accuracy must be complied with to ensure good withstand.

DM105590

mm in

103.5.225

09..3265
12.81.25 09.3.57
51.3497 41.2702

154.649.541.2966
2

09.3.57 Panel mounting

0.014.0--100.39

DM105638

A

2.5

155

0.1

6.10

5.0 0.2
Easergy
OK F2
F1 O I
124.5 4.90

137

B

5.39

With screw connector
With ring-lug connector

A 214 mm / 8.43''

B 147 mm / 8.8''

226 mm / 8.90'' 159 mm / 6.2''

DM105639

Projection mounting with the raising frame REL52834
A 110 4.3
B 137 5.39

124.5 4.90

2.5 0.1
Raising frame REL52834

Raising frame REL52834

schneider-electric.com

Easergy P3 Catalog | 37

Easergy P3 Standard

Base unit characteristics
Technical characteristics

Analog inputs

Phase Current Input 5A CT Configurable for CT secondaries 1 to 10A
Residual Current Input (I0) 5A CT Configurable for CT secondaries 0.1 to 10A
Residual Current Input (I0) 1A CT Configurable for CT secondaries 0.1 to 10.0A
Residual Current Input (I0) 0.2A CSH sensor Configurable for CT secondaries 0.1 to 10.0A
Voltage Input Configurable for VT secondaries 50 to 120V

Analog temperature input and Analog output

Type of temperature sensor

Maximum distance between sensor and module

Analog Output

Minimum current Maximum current

Operating temperature: Power supply

REL52811 / REL52812 REL52813 REL52814

Measuring range

Input Impedance

Consumption

0.05 � 250 A 0.003 Ohm 0.075 VA

0.015 � 50 A 0.003 Ohm 0.075 VA

0.003 � 10 A 0.02 Ohm

0.02 VA

0.0006 � 2 A 0.02 Ohm

0.02 VA

0.5 � 190 V n.a. (100 V / 110 V)

< 0.5 VA

Rated thermal withstand
20 A (Continuously)
20 A (Continuously)
4 A (Continuously)
0.8 A (Continuously)
250V (Continuously)

1-second overload 500 A 500 A 100 A 20 A n.a.

10-second overload 100 A 100 A 20 A 4 A 600 V

Pt100 up to 2,000 m (1)

Ni100

Ni120

up to 2,000 m (1)

up to 2,000 m (1)

0 mA

20 mA

0�C (32�F) to +55�C (131�F)

24 to 230 Vac/dc, 50/60 Hz 24 Vdc
48 to 230 ac/dc, 50/60 Hz

Cu10 up to 2,000 m (1)

Digital Input Nominal operation voltage Typical switching threshold
Input limit voltage
Frequency Typical consumption Voltage withstand

DI1 to DI16
At state 1 At state 0

Digital Output

Type of contact

Rated Voltage

Continuous current

AC

Breaking capacity

DC (L/R=40ms)

Making capacity
Minimum making capacity Typical operation time Contact material

at 48 V dc at 110 V dc at 220 V dc < 0.5 s < 3.0 s

Power supply Nominal Voltage Range

Inrush current (DC)

Power consumption

Normal conditions Output relays activated

Acceptable momentary outages

(1) 78,750 in

24 to 230 V ac/dc
12 V dc  19.2 V dc < 10.0 V dc 45 to 65 Hz

110 to 230 V ac/dc 75 V dc  88 V dc < 60 V dc
45 to 65 Hz <4 mA (typical approx. 3 mA)
255 V ac/dc

220 to 230 V ac/dc
155 V dc  176 V dc < 140 V dc 45 to 65 Hz

Control and Trip contact, Tx
250 V ac/dc
5 A 2.000 VA
1.15 A 0.5 A 0.25 A 30 A 15 A 100 mA @ 24 Vac/dc
<8 ms
AgNi 90/10

Signal contact, A1
250 V ac/dc
5 A 2.000 VA
1 A 0.3 A 0.15 A 30 A 15 A 100 mA @ 24 Vac/dc
-
AgNi 0.15 gold plated

Signal Contact, SF
250 V ac/dc
5 A 2.000 VA
1 A 0.3 A 0.15 A
100 mA @ 24 Vac/dc
-
AgNi 0.15 gold plated

48 to 230 Vac/dc

24 Vdc

-20% / +10% (40 to 253 Vac/dc)

-20% / +20% (19.2 to 28.8 Vdc)

25 A with time constant of 1000 �s 25 A with time constant of 750 �s 15 A with time constant of 500 �s
<15 W (<30 VA) <25 W (<50 VA)

<50 ms (110 V dc)

38 | Easergy P3 Catalog

schneider-electric.com

Easergy P3 Standard

Base unit characteristics
Environmental characteristics

Electromagnetic compatibility

Emission tests Conducted Emitted Immunity 1 Mhz damped oscillatory wave

Standard and test class/level IEC/EN 60255-26 (ed3) EN 55022, Class A / CISPR 22 EN 55011, Class A / CISPR 11 IEC/EN 60255-26 (ed3) IEC/EN 61000-4-18

Static discharge (ESD)

IEC/EN 61000-4-2 Level 4

Emitted HF field Fast transients (EFT) Surge

IEC/EN 61000-4-3 Level 3 IEC/EN 61000-4-4 Level 4 IEC/EN 61000-4-5 Level 3

Conducted HF field Power-frequency magnetic field Pulse magnetic field ac and dc voltage dips

IEC/EN 61000-4-6 Level 3 IEC/EN 61000-4-8 IEC/EN 61000-4-9 Level 5 IEC/EN 61000-4-29, IEC/EN 61000-4-11

ac and dc voltage interruptions Voltage alternative component

IEC/EN 61000-4-29, IEC/EN 61000-4-11 IEC/EN 61000-4-17

Mechanical robustness

In operation Vibrations Shocks Seismic De-energized Vibrations Shocks Bump

Standard and test class/level
IEC 60255-21-1, Class II / IEC 60068-2-6, Fc IEC 60255-21-2, Class II / IEC 60068-2-27, Ea IEC 60255-21-3 Method A, Class II
IEC 60255-21-1, Class II / IEC 60068-2-6, Fc IEC 60255-21-2, Class II / IEC 60068-2-27, Ea IEC 60255-21-2, Class II / IEC 60068-2-27, Ea

Test value
0.15 � 30 MHz 30 � 1000 MHz
�2.5kVp CM �2.5kVp DM �8 kV contact �15 kV air 80 - 2700 MHz, 10 V/m �4 kV, 5/50 ns, 5 kHz �2 kV, 1.2/50 �s, CM �1 kV, 1.2/50 �s, DM 0.15 - 80 MHz, 10 Vrms 300 A/m (continuous) 1000 A/m 1 � 3s 1000A/m, 1.2/50 �s 0% of rated voltage
� ac:  0.5 cycle � dc:  10 ms 40% of rated voltage � ac: 10 cycles � dc: 200 ms 70% of rated voltage � ac: 25 cycles � dc: 500 ms 100% interruption � ac: 250 cycles � dc: 5 s 15% of operating voltage (dc) / 10 min
Test value
1 Gn, 10 Hz � 150 Hz 10 Gn / 11 ms 2G horizontal / 1G vertical , 1�35 Hz
2 Gn, 10 Hz � 150 Hz 30 Gn / 11 ms 20 Gn / 16 ms

schneider-electric.com

Easergy P3 Catalog | 39

Easergy P3 Standard

Base unit characteristics
Environmental characteristics

Environment tests
In operation Dry heat Cold Damp heat, cyclic

Standard and test class/level
EN / IEC 60068-2-2, Bd EN / IEC 60068-2-1, Ad EN / IEC 60068-2-30, Db

Damp heat, static

EN / IEC 60068-2-78, Cab

Change of temperature

IEC / EN 60068-2-14, Nb

In storage Dry heat Cold

EN / IEC 60068-2-2, Bb EN / IEC 60068-2-1, Ab

Test value
70�C (158�F) -40�C (-40�F) From 25�C (77�F) to 55�C (131�F) From 93% RH to 98% RH Testing duration: 6 days 40�C (104�F) 93% RH Testing duration: 10 days Lower temp -40�C (-40�F) Upper temp 70�C (158�F) 5 cycles
70�C (158�F) -40�C (-40�F)

Environmental conditions

Ambient temperature, in-service Ambient temperature, storage Relative air humidity Maximum operating altitude

-40 � 60�C (-40 � 140�F) -40 � 70�C (-40 � 158�F) < 95%, no condensation allowed 2000 m (6561.68 ft)

Safety
Electrical safety tests Impulse voltage withstand Dielectric test Insulation resistance Protective bonding resistance Clearance and creepage distance Power supply burden

Standard and test class/level
IEC/EN 60255-27
IEC/EN 60255-27
IEC/EN 60255-27 IEC/EN 60255-27 Design criteria for distances as per IEC 60255-27 Annex C (pollution degree 2, overvoltage category 3) IEC 60255-1

Test value
5 kV, 1.2/50 �s, 0.5 J 1 kV, 1.2/50 �s, 0.5 J Communication 2 kV, 50 Hz 0.5 kV, 50 Hz Communication

40 | Easergy P3 Catalog

schneider-electric.com

PM106362

Easergy P3 Standard

Communication protocols

Easergy P3 Standard can be connected to networks, thus providing access to the following type of data:
� Events � Status information � Measurements � Control commands � Clock synchronizing � Settings
(SPA-bus and embedded SPA-bus only)
Easergy SmartApp.

Main protocols

Easergy P3 Standard can be connected directly to serial and/or Ethernet protocols with two different protocols at the same time, selected by eSetup Easergy Pro software.

Communication protocols:

Communication ports:

Serial protocols - RS232 / RS485 / serial Fiber Optic (*) port Modbus RTU DNP3.0 IEC 60870-5-101 IEC 60870-5-103 DeviceNet (*) ProfibusDP (*) SPA-Bus (*) Ethernet protocols RJ45 / LC port IEC61850 ed1 & ed2 Modbus TCP DNP3.0 IEC60870-5-101 Ethernet IP

Redundancy � RSTP � PRP
Two protocols at the same time

Comm. interface - X4

LC

LC

WebServer

Protocols
� IEC 61850 � Modbus � DNP3.0 � IEC-101 � Ethernet/IP

Protocols
� IEC 61850 � Modbus � DNP3.0 � IEC-101 � Ethernet/IP

Comm. interface - X4

LC

RS232 + IRIG-B

Two protocols at the same time
WebServer

Redundancy � RSTP � PRP
Two protocols at the same time

Comm. interface - X4
WebServer

Protocols
� IEC 61850 � Modbus � DNP3.0 � IEC-101 � Ethernet/IP

Protocols � IEC 61850 � Modbus � DNP3.0 � IEC-101 � Ethernet/IP
Protocols � Modbus � DNP3.0 � IEC-103 � SPAbus

Comm. interface - X4
RS232 + IRIG-B Two protocols at the same time WebServer
Comm. interface - X4
RS485

*Need external accessories to connect.

Easergy web-HMI

Redundancy protocols (RSTP or PRP)
When the devices are connecting in Ethernet link and demand for higher availability, Easergy P3 Standard can use Rapid Spanning Tree Protocol (RSTP) or Parallel Redundancy Protocol (PRP) to recover from a network failure.
Easergy P3 web-HMI
A webserver is available in Easergy P3 Standard to get information from the device to monitor all data, send commands, and change protection settings.

PM106576

schneider-electric.com

Easergy P3 Catalog | 41

Easergy P3 Standard

Programmable stages
Programmable protection function
Personalize your protection function
Easergy P3 Standard allows you to create or personalize the protection function when you need to achieve specific levels of protection. There are now eight stages available to use with various applications. Each stage can monitor any analog (measured or calculated) signal and issue start and trip signals. Programmable stages extend the protection functionality of the manager series to a new level. The Programmable stage has the possibility of comparing two freely selectable signals between each other. Using this feature you can create a comparison function using the relay's own measured or calculated signals. One or both of the signals can be connected to the comparison function over GOOSE. For example, if four stages of frequency are not enough, it is possible to reach a maximum of 12 using programmable stages. Other examples include using the stages to issue an alarm when there are too many harmonics (THD) or indicating reverse power condition by GOOSE. .

EM100170

42 | Easergy P3 Catalog

schneider-electric.com

Easergy P3 Standard

Circuit breaker control

With Easergy P3 Standard, you get intuitive functionality to protect your electrical network system.
Main CB functions are: � Trip circuit supervision (ANSI 74) � CT/VT supervision (ANSI 60/60FL) � Latching (ANSI 86) � CB close/open order � Number of operations � Cumulative breaking current � Personalized functions

Maximize circuit breaker control
Easergy P3 Standard is a simple protection relay with a single-line diagram with control buttons (open and close), two personalized function keys, and eight configurable tricolor LEDs. You can manage the control without external or additional component.
Example of implementation The schematic is structured for typical use in MV switchgears, 100% adapted for your use case. You are free to change the internal logic to adapt the Easergy P3 Standard to follow your needs. If a problem occurs, clear and complete information puts you able to make the right decisions immediately.

MV network
CT
This electrical schematic can facilitate the IEC 61850 implementation because all the logics are determined by the protection unit that will make the decisions and if necessary can send GOOSE messages to other units.

DM105591

HMI interface
Function key F1

0 I
Control buttons

LED F1 ON LED A LED C LED E LED G

Mimic Diagram
I1: 0.0A I2: 0.0A I3: 0.0A P : 0.0W V : 0.0V

F2
LED F2 Service LED B LED D LED F LED H

USB Local Port

Inputs

AND

TIMER

Latching contact ANSI 86

Trip control Order contact

OR

COUNTER

Trip Circuit Supervision

XOR

Output

Nominal voltage
Alarm contact for Trip circuit failure

T2
Close contact Order contact
T3
0 1
Open/Close Mechanical command

A1

T1

Digital Input 2

Digital Input 1

Trip circuit supervision

Trip circuit supervision

Trip circuit failure alarm

DI 2

DI 1

52a

CLOSE COIL

OPEN COIL

52b
Circuit Breaker

schneider-electric.com

Easergy P3 Catalog | 43

Easergy P3 Standard

Connection diagrams
Easergy P3U30 example

DANGER
HAZARD OF ELECTRIC SHOCK, ELECTRIC ARC OR BURNS
- only qualified personnel should install this equipment. Such work should be performed only after reading this entire set of instructions.
- NEVER work alone.
- turn off all power supplying this equipment before working on or inside it. Consider all sources of power, including the possibility of backfeeding.
- always use a properly rated voltage sensing device to confirm that all power is off.
- start by connecting the device to the protective earth and to the functional earth.
- screw tight all terminals, even those not in use.
Failure to follow these instructions will result in death or serious injury.

DM105593

Application with 3 phase CTs, 1 earth CT, 1 VT and CB control

1 0

3

20

4

DI1

V1

19

5

USB

18

6

DI2

Local Port V2

17 16

17

T1

V3

15

16 15
14 13
12 11
10
8 9 7 19 20 18
1

T2
X3
T3

T5

14

13

T6

12

11

X5 T7

10

T4

9

8

DI16

7

A1

DI15

Easergy DI14

6 5

SF P3U30

4

DI13

3

DI12

2

X1

DI11

1

2

I1

3

4

I2

5

6

I3

7

8

5 A

9

OR

Io

OR

10

1 A

14

DI10

13

DI9

12

11

DI8

10

DI7

9

8

DI6

X4

7 6

DI5 5

1

2

V4

3
X2
4

4 DI4
3 2 DI3 1

X4
COM

Serial communication port

44 | Easergy P3 Catalog

schneider-electric.com

Easergy P3 Standard

Connection diagrams
Easergy P3U30 example

DANGER
HAZARD OF ELECTRIC SHOCK, ELECTRIC ARC OR BURNS
- only qualified personnel should install this equipment. Such work should be performed only after reading this entire set of instructions.
- NEVER work alone.
- turn off all power supplying this equipment before working on or inside it. Consider all sources of power, including the possibility of backfeeding.
- always use a properly rated voltage sensing device to confirm that all power is off.
- start by connecting the device to the protective earth and to the functional earth.
- screw tight all terminals, even those not in use.
Failure to follow these instructions will result in death or serious injury.

DM105594

Application with 3 phase CTs, 1 earth CT, 3 VTs, synchro-check and CB control

1 0

3

20

4

DI1

V1

19

5

USB

18

Local Port V2

6

DI2

17 16

17

T1

V3

15

16 15
14 13
12 11
10
8 9 7 19 20 18
1

T2
X3
T3

T5

14

13

T6

12

11

X5 T7

10

T4

9

8

DI16

7

A1

DI15

Easergy DI14

6 5

SF P3U30

4

DI13

3

DI12

2

X1

DI11

1

2

I1

3

4

I2

5

6

I3

7

8

5 A

9

OR

Io

OR

10

1 A

14

DI10

13

DI9

12

11

DI8

10

DI7

9

8

DI6

X4

7 6

DI5 5

1

2

V4

3

X2

4

4 DI4
3 2 DI3 1

X4

Redundant Ethernet Network - RSTP or PRP

schneider-electric.com

Easergy P3 Catalog | 45

Easergy P3 Standard

Connection diagrams
Easergy P3U30 example

DANGER
HAZARD OF ELECTRIC SHOCK, ELECTRIC ARC OR BURNS
- only qualified personnel should install this equipment. Such work should be performed only after reading this entire set of instructions.
- NEVER work alone.
- turn off all power supplying this equipment before working on or inside it. Consider all sources of power, including the possibility of backfeeding.
- always use a properly rated voltage sensing device to confirm that all power is off.
- start by connecting the device to the protective earth and to the functional earth.
- screw tight all terminals, even those not in use.
Failure to follow these instructions will result in death or serious injury.

DM105595

Application with 3 phase CTs, 1 earth CT, 4 VTs and CB control

1 0

3

20

4

DI1

V1

19

5

USB

18

Local Port V2

6

DI2

17 16

17

T1

V3

15

16 15
14 13
12 11
10
8 9 7 19 20 18
1

T2
X3 T3

T5

14

13

T6

12

11

X5 T7

10

T4

9

8

DI16

7

A1

DI15

Easergy DI14

6 5

SF P3U30

4

DI13

3

DI12

2

X1

DI11

1

2

I1

3

4

I2

5

6

I3

7

8

5 A

9

OR

Io

OR 10

1 A

14

DI10

13

DI9

12

11

DI8

10

DI7

9

8

DI6

X4

7 6

DI5 5

1

2

V4

3

X2

4

4 DI4
3 2 DI3 1

X4

Go to X2 Slot (pin 1 & 2)

Redundant Ethernet Network - RSTP or PRP

46 | Easergy P3 Catalog

schneider-electric.com

Easergy P3 Standard

PM106367

PM106367

PM106367

Model selection
Selecting product

Please, consult the "Ordering" section to choose specific characteristics in the relays for your system:

P3U10 Standard application

Page 106

P3U20 Standard application

Page 107

P3U30 Standard application

Page 108

Or use our web configuration tool:
Go to web configurator

schneider-electric.com

Easergy P3 Catalog | 47

Easergy P3 Advanced

48 | Easergy P3 Catalog

schneider-electric.com

Easergy P3 Advanced

Presentation

50

Functional view

52

Base unit presentation

59

Integrated arc flash protection

59

Local HMI

60

Rear panel

61

Remote HMI

63

Base unit dimensions

64

Dimensions

64

Cut-out and mounting

65

Base unit characteristics

66

Technical characteristics

66

Environmental characteristics

67

Communication

69

Communication protocols

69

Programmable stages

70

Circuit breaker control

71

Power quality measurements

72

Connection diagrams

73

Model selection

76

schneider-electric.com

Easergy P3 Catalog | 49

Easergy P3 Advanced

Presentation

The Easergy P3 Advanced protection relay has been developed to cover demanding protection needs for building, distribution utilities, and industrial applications. Thanks to its wide scope of functionalities, the Easergy P3 Advanced range provides an excellent solution for your high-end protection applications.

Protect your staff and equipment and ensure safer operations with Easergy P3 Advanced's built-in arc flash detection and protection functions.
You will experience greater operational efficiency with rapid ordering, configuration, and operations for an unparalleled digital experience provided with Easergy P3.

Easergy P3 Advanced at a glance
Extended capabilities � Extended protection functions, including differential of line, transformer,
motor, and generator � Arc flash detection � All communication protocols embedded on serial and Ethernet links,
including IEC 61850 ed.1 and ed. 2 � Increased number of inputs and outputs
Robust � Best-in class reliability based on 100+ years of experience in Sepam,
MiCOM and Vamp relays � Strong tests performed in international laboratories � Compliant with IEC electro-mechanical standards

Efficient and connected � Easy to configure with the unique eSetup Easergy Pro setting software � Easy to test with the virtual simulation test for direct injection of current
and voltage from eSetup Easergy Pro � Easy to use and maintain with the embedded web-HMI and Easergy
SmartApp for direct access on site via your laptop, smartphone, or tablet � Easy to install with withdrawable rear connectors with CT shortening

PM106370

50 | Easergy P3 Catalog

schneider-electric.com

Easergy P3 Advanced

Presentation

DM105530

Easergy P3 is designed to cover a large scope of applications

Line Di erential & Distance
L
U
Feeder


M
M Motor Di erential

G

G

Generator Di erential

T

Transformer Di erential


Easergy P3 Advanced is designed in 7 models, per application:

Model

Function

Easergy P3F 30

Feeder

Protection

Easergy P3L 30

Line

Differential and Distance

30 Easergy P3M
32

Motor

Protection Differential

30 Easergy P3G
32

Generator

Protection Differential

Easergy P3T 32

Transformer Differential

A common set of functions extends the possibilities of protection and control: � Single-line diagrams (mimic) in the display � Programmable protection stages � Programmable logics � 2 programmable function keys � Synchro-check function � Direct-access USB port � Up to 6 objects controlled � Arc flash protection

schneider-electric.com

Easergy P3 Catalog | 51

Easergy P3 Advanced

Functional view
Easergy P3F30

DM105596b
RS232 RS232 RS232

HMI interface

I

0

Control buttons

Function key F1

ON
LED A LED C LED E LED G LED I LED K LED M
LED F1

Programmable Logic

Inputs

AND

TIMER

Mimic Diagram
I1: 0.0A I2: 0.0A I3: 0.0A P : 0.0W V : 0.0V

Service
LED B LED D LED F LED H LED J LED L LED N
LED F2

USB Local Port
F2

OR

COUNTER

XOR

Output

Setting groups:4

H2/H5

38

49T

60

99

SOTF 79

74

86

CLPU

AFD

Comm. interface - Slot 9

T

E

Protocols

RS232

M P

� Modbus � DNP3.0 � IEC-103

� SPAbus

Option card - Slot 6

Arc 1
A

Arc 2
A

Arc 3
A

Arc 4
A

OR

67 21FL 37P

I/O card G - Slot 5
DI19 DI20 DI21 DI22 DI23 DI24
T25 T26 T27 T28

50BF 50 51 51C 49 46

59N 67NI

I/O card G - Slot 4
DI13 DI14 DI15 DI16 DI17 DI18
T21 T22 T23 T24

81R

I/O card G - Slot 3

67N

25

DI7 DI8 DI9 DI10 DI11 DI12

81 81U

50N

50G

59

51N 51G
27

T17 T18 T19 T20
I/O card G - Slot 2
DI1 DI2 DI3 DI4 DI5 D6 T13 T14 T15 T16

Analog measurement card - Slot 8

Current input

Voltage input

I1 I2 I3 Io1 Io2 V1 V2 V3 V0

Power Supply - Slot 1
T9 T10 T11 T12

T1 A1

SF

Other types of control

Arc sensor: See list of
Accessories REL52801
to REL52810

Circuit Breaker controls Arc Flash sensors

REL52822

eSetup Easergy Pro

Comm. interface - Slot 9

Redundancy

Protocols

� RSTP � PRP
Two protocols at the same time

WebServer

� IEC 61850 � Modbus � DNP3.0 � IEC-101 � Ethernet/IP

Comm. interface - Slot 9

Redundancy

LC

LC

Protocols

� RSTP

� IEC 61850

� PRP

� Modbus

Two protocols at the same time

WebServer

� DNP3.0 � IEC-101 � Ethernet/IP

Comm. interface - Slot 9

Protocols
� IEC 61850 � Modbus � DNP3.0 � IEC-101

LC

RS232 + IRIG-B

Two protocols

at the

same time

� Ethernet/IP WebServer

Comm. interface - Slot 9

Protocols
� IEC 61850 � Modbus � DNP3.0 � IEC-101 � Ethernet/IP

RS232 + IRIG-B Two protocols at the same time
WebServer

REL52820

Connect to RS232 port
REL52816 REL52819

REL52821

Protocols Modbus DNP3.0 IEC-103
RS485

Protocols
Modbus DNP3.0 IEC-103 SPAbus

Protocols DeviceNet
RS485

Serial
Serial network

OR

REL52812
RS485

RTD CH01 RTD CH02 RTD CH03 RTD CH04 RTD CH05 RTD CH06 RTD CH07 RTD CH08 RTD CH09 RTD CH10 RTD CH11 RTD CH12

OR

REL52813 REL52814
RS485 Rx

Tx
Fiber Rx
Tx

PTC RTD CH01

RTD CH02 mA In1
RTD CH03 mA In2
RTD CH04 mA In3
RTD CH05
mA In4 RTD CH06

RTD CH07 mA OUT1
RTD CH08 mA OUT2
RTD CH09 mA OUT3
RTD CH10 mA OUT4
RTD CH11

RTD CH12

52 | Easergy P3 Catalog

schneider-electric.com

Easergy P3 Advanced

Functional view
Easergy P3M30

DM105597b
RS232 RS232 RS232

HMI interface

I

0

Control buttons

Function key F1

ON
LED A LED C LED E LED G LED I LED K LED M
LED F1

Programmable Logic

Inputs

AND

TIMER

Mimic Diagram
I1: 0.0A I2: 0.0A I3: 0.0A P : 0.0W V : 0.0V

Service
LED B LED D LED F LED H LED J LED L LED N
LED F2

USB Local Port
F2

OR

COUNTER

XOR

Output

Setting groups:4

H2/H5 SOTF

38

49T

60

99

74

86

CLPU

AFD

37

66

48 51LR

67

37P

Comm. interface - Slot 9

T

E

Protocols

RS232

M P

� Modbus � DNP3.0 � IEC-103

� SPAbus

Option card - Slot 6

Arc 1
A

Arc 2
A

Arc 3
A

Arc 4
A

I/O card G - Slot 5
DI19 DI20 DI21 DI22 DI23 DI24
T25 T26 T27 T28

50BF 50

I/O card G - Slot 4

59N

DI13 DI14 DI15 DI16 DI17 DI18

T21 T22 T23 T24

51

81R

I/O card G - Slot 3

67N

25

DI7 DI8 DI9 DI10 DI11 DI12

51C

81

81U

50N

49

50G

59

51N

46

51G

27

T17 T18 T19 T20
I/O card G - Slot 2
DI1 DI2 DI3 DI4 DI5 D6 T13 T14 T15 T16

Analog measurement card - Slot 8

Current input

Voltage input

I1 I2 I3 Io1 Io2 V1 V2 V3 V0

Power Supply - Slot 1
T9 T10 T11 T12

T1

A1

SF

Other types of control

Arc sensor: See list of
Accessories REL52801 to
REL52810

M
Circuit Breaker controls Arc Flash sensors

OR

REL52822

eSetup Easergy Pro

Comm. interface - Slot 9

Redundancy

Protocols

� RSTP � PRP
Two protocols at the same time

WebServer

� IEC 61850 � Modbus � DNP3.0 � IEC-101 � Ethernet/IP

Comm. interface - Slot 9

Redundancy

LC

LC

Protocols

� RSTP

� IEC 61850

� PRP

� Modbus

Two protocols at the same time

WebServer

� DNP3.0 � IEC-101 � Ethernet/IP

Comm. interface - Slot 9

Protocols
� IEC 61850 � Modbus � DNP3.0 � IEC-101

LC

RS232 + IRIG-B

Two protocols

at the

same time

� Ethernet/IP WebServer

Comm. interface - Slot 9

Protocols
� IEC 61850 � Modbus � DNP3.0 � IEC-101 � Ethernet/IP

RS232 + IRIG-B Two protocols at the same time
WebServer

REL52820

Connect to RS232 port
REL52816 REL52819

REL52821

Protocols Modbus DNP3.0 IEC-103
RS485

Protocols
Modbus DNP3.0 IEC-103 SPAbus

Protocols DeviceNet
RS485

Serial
Serial network

OR

REL52812
RS485

RTD CH01 RTD CH02 RTD CH03 RTD CH04 RTD CH05 RTD CH06 RTD CH07 RTD CH08 RTD CH09 RTD CH10 RTD CH11 RTD CH12

OR

REL52813 REL52814
RS485 Rx

Tx
Fiber Rx
Tx

PTC RTD CH01

RTD CH02 mA In1
RTD CH03 mA In2
RTD CH04 mA In3
RTD CH05
mA In4 RTD CH06

RTD CH07 mA OUT1
RTD CH08 mA OUT2
RTD CH09 mA OUT3
RTD CH10 mA OUT4
RTD CH11

RTD CH12

schneider-electric.com

Easergy P3 Catalog | 53

Easergy P3 Advanced

Functional view
Easergy P3M32

DM105598b
RS232 RS232 RS232

HMI interface

I

0

Control buttons

Function key F1

ON
LED A LED C LED E LED G LED I LED K LED M
LED F1

Programmable Logic

Inputs

AND

TIMER

Mimic Diagram
I1: 0.0A I2: 0.0A I3: 0.0A P : 0.0W V : 0.0V

Service
LED B LED D LED F LED H LED J LED L LED N
LED F2

USB Local Port
F2

OR

COUNTER

XOR

Output

Setting groups:4

H2/H5 SOTF

60

99

74

86

CLPU

37

66

48 51LR

67

37P

38 49T
AFD 87M

Comm. interface - Slot 9
T

E

M P

� Modbus � DNP3.0 � IEC-103

RS232

� SPAbus

Option card - Slot 6

Arc 1
A

Arc 2
A

Arc 3
A

Arc 4
A

I/O card 4 - Slot 5 Slot reserved

50BF 50

I/O card 3 - Current input
59N
IL1 IL2 IL3 Io3

51

81R

I/O card G - Slot 3

67N

25

DI7 DI8 DI9 DI10 DI11 DI12

51C

81

81U

50N

49

50G

59

51N

46

51G

27

T17 T18 T19 T20
I/O card G - Slot 2
DI1 DI2 DI3 DI4 DI5 D6 T13 T14 T15 T16

Analog measurement card - Slot 8

Current input

Voltage input

IL1 IL2 IL3 Io1 Io2 V1 V2 V3 V0

Power Supply - Slot 1
T9 T10 T11 T12

T1 A1

SF

Other types of control

Arc sensor: See list of
Accessories REL52801 to
REL52810

M
Circuit Breaker controls Arc Flash sensors

OR

REL52822

eSetup Easergy Pro

Comm. interface - Slot 9

Redundancy

Protocols

� RSTP � PRP
Two protocols at the same time

WebServer

� IEC 61850 � Modbus � DNP3.0 � IEC-101 � Ethernet/IP

Comm. interface - Slot 9

Redundancy

LC

LC

Protocols

� RSTP

� IEC 61850

� PRP

� Modbus

Two protocols at the same time

WebServer

� DNP3.0 � IEC-101 � Ethernet/IP

Comm. interface - Slot 9

Protocols
� IEC 61850 � Modbus � DNP3.0 � IEC-101

LC

RS232 + IRIG-B

Two protocols

at the

same time

� Ethernet/IP WebServer

Comm. interface - Slot 9

Protocols
� IEC 61850 � Modbus � DNP3.0 � IEC-101 � Ethernet/IP

RS232 + IRIG-B Two protocols at the same time
WebServer

REL52820

Connect to RS232 port
REL52816 REL52819

REL52821

Protocols Modbus DNP3.0 IEC-103
RS485

Protocols
Modbus DNP3.0 IEC-103 SPAbus

Protocols DeviceNet
RS485

Serial
Serial network

OR

REL52812
RS485

RTD CH01 RTD CH02 RTD CH03 RTD CH04 RTD CH05 RTD CH06 RTD CH07 RTD CH08 RTD CH09 RTD CH10 RTD CH11 RTD CH12

OR

REL52813 REL52814
RS485 Rx

Tx
Fiber Rx
Tx

PTC RTD CH01

RTD CH02 mA In1
RTD CH03 mA In2
RTD CH04 mA In3
RTD CH05
mA In4 RTD CH06

RTD CH07 mA OUT1
RTD CH08 mA OUT2
RTD CH09 mA OUT3
RTD CH10 mA OUT4
RTD CH11

RTD CH12

54 | Easergy P3 Catalog

schneider-electric.com

Easergy P3 Advanced

Functional view
Easergy P3T32

DM105599b
RS232 RS232 RS232

HMI interface

I

0

Control buttons

Function key F1

ON
LED A LED C LED E LED G LED I LED K LED M
LED F1

Programmable Logic

Inputs

AND

TIMER

Mimic Diagram
I1: 0.0A I2: 0.0A I3: 0.0A P : 0.0W V : 0.0V

Service
LED B LED D LED F LED H LED J LED L LED N
LED F2

USB Local Port
F2

OR

COUNTER

XOR

Output

Setting groups:4

H2/H5 SOTF

38

49T

60

99

74

86

CLPU

AFD

Comm. interface - Slot 9

T

E

Protocols

RS232

M P

� Modbus � DNP3.0 � IEC-103

� SPAbus

Option card - Slot 6

Arc 1
A

Arc 2
A

Arc 3
A

Arc 4
A

87T

I/O card 4 - Slot 5

67 50BF 50

37P 24
59N

Slot reserved
I/O card 3 - Current input IL'1 IL'2 IL'3 Io3

81R

51

67N

25

81 81U

50N

49

50G

59

51N

46

51G

27

27P

Analog measurement card - Slot 8

Current input

Voltage input

IL1 IL2 IL3 Io1 Io2 V1 V2 V3 V0

I/O card G - Slot 3
DI7 DI8 DI9 DI10 DI11 DI12
T17 T18 T19 T20

I/O card G - Slot 2
DI1 DI2 DI3 DI4 DI5 D6
T13 T14 T15 T16

Power Supply - Slot 1
T9 T10 T11 T12

T1 A1

SF

Other types of control

Arc sensor: See list of
Accessories REL52801 to
REL52810

Circuit Breaker controls Arc Flash sensors

OR

REL52822

eSetup Easergy Pro

Comm. interface - Slot 9

Redundancy

Protocols

� RSTP � PRP
Two protocols at the same time

WebServer

� IEC 61850 � Modbus � DNP3.0 � IEC-101 � Ethernet/IP

Comm. interface - Slot 9

Redundancy

LC

LC

Protocols

� RSTP � PRP
Two protocols at the same time

WebServer

� IEC 61850 � Modbus � DNP3.0 � IEC-101 � Ethernet/IP

Comm. interface - Slot 9

Protocols
� IEC 61850 � Modbus � DNP3.0 � IEC-101

LC

RS232 + IRIG-B

Two protocols

at the

same time

� Ethernet/IP WebServer

Comm. interface - Slot 9

Protocols
� IEC 61850 � Modbus � DNP3.0 � IEC-101 � Ethernet/IP

Two protocols at the same time
WebServer

RS232 + IRIG-B

REL52820

Connect to RS232 port
REL52816 REL52819

REL52821

Protocols Modbus DNP3.0 IEC-103
RS485

Protocols
Modbus DNP3.0 IEC-103 SPAbus

Protocols DeviceNet
RS485

Serial
Serial network

OR

REL52812
RS485

RTD CH01 RTD CH02 RTD CH03 RTD CH04 RTD CH05 RTD CH06 RTD CH07 RTD CH08 RTD CH09 RTD CH10 RTD CH11 RTD CH12

OR

REL52813 REL52814
RS485 Rx

Tx
Fiber Rx
Tx

PTC RTD CH01

RTD CH02 mA In1
RTD CH03 mA In2
RTD CH04 mA In3
RTD CH05
mA In4 RTD CH06

RTD CH07 mA OUT1
RTD CH08 mA OUT2
RTD CH09 mA OUT3
RTD CH10 mA OUT4
RTD CH11

RTD CH12

schneider-electric.com

Easergy P3 Catalog | 55

Easergy P3 Advanced

Functional view
Easergy P3L30

DM105600b
RS232 RS232 RS232

HMI interface

I

0

Control buttons

Function key F1

ON
LED A LED C LED E LED G LED I LED K LED M
LED F1

Programmable Logic

Inputs

AND

TIMER

Mimic Diagram
I1: 0.0A I2: 0.0A I3: 0.0A P : 0.0W V : 0.0V

Service
LED B LED D LED F LED H LED J LED L LED N
LED F2

USB Local Port
F2

OR

COUNTER

XOR

Output

Setting groups:4

H2/H5

38

49T

60

99

SOTF

79

74

86

CLPU

87L

67 21FL 37P

21

Comm. interface - Slot 9

T

E

Protocols

RS232

M P

� Modbus � DNP3.0 � IEC-103

� SPAbus

Option card 1 - Slot 6

Device B
Communication link

I/O card G - Slot 5
DI19 DI20 DI21 DI22 DI23 DI24

T25 T26 T27 T28

50BF 50 51 51C 49 46

59N 67NI

I/O card G - Slot 4
DI13 DI14 DI15 DI16 DI17 DI18
T21 T22 T23 T24

81R

I/O card G - Slot 3

67N

25

DI7 DI8 DI9 DI10 DI11 DI12

81 81U

50N

50G

59

51N 51G
27

T17 T18 T19 T20
I/O card G - Slot 2
DI1 DI2 DI3 DI4 DI5 D6 T13 T14 T15 T16

Analog measurement card - Slot 8

Current input

Voltage input

I1 I2 I3 Io1 Io2 V1 V2 V3 V0

Power Supply - Slot 1
T9 T10 T11 T12

T1 A1

SF

Other types of control
Circuit Breaker control

REL52822

eSetup Easergy Pro

OR

Comm. interface - Slot 9

Redundancy

Protocols

� RSTP � PRP
Two protocols at the same time

WebServer

� IEC 61850 � Modbus � DNP3.0 � IEC-101 � Ethernet/IP

Comm. interface - Slot 9

Redundancy

LC

LC

Protocols

� RSTP � PRP
Two protocols at the same time

WebServer

� IEC 61850 � Modbus � DNP3.0 � IEC-101 � Ethernet/IP

Comm. interface - Slot 9

Protocols
� IEC 61850 � Modbus � DNP3.0 � IEC-101

LC

RS232 + IRIG-B

Two protocols

at the

same time

� Ethernet/IP WebServer

Comm. interface - Slot 9

Protocols
� IEC 61850 � Modbus � DNP3.0 � IEC-101 � Ethernet/IP

RS232 + IRIG-B Two protocols at the same time
WebServer

REL52820

Connect to RS232 port
REL52816 REL52819

REL52821

Protocols Modbus DNP3.0 IEC-103
RS485

Protocols
Modbus DNP3.0 IEC-103 SPAbus

Protocols DeviceNet
RS485

Serial
Serial network

OR

REL52825
RS485

RTD CH01 RTD CH02 RTD CH03 RTD CH04 RTD CH05 RTD CH06 RTD CH07 RTD CH08 RTD CH09 RTD CH10 RTD CH11 RTD CH12

OR

REL52826

RS485 Rx
Tx
Fiber Rx
Tx

PTC RTD CH01

RTD CH02 mA In1
RTD CH03 mA In2
RTD CH04 mA In3
RTD CH05
mA In4 RTD CH06

RTD CH07 mA OUT1
RTD CH08 mA OUT2
RTD CH09 mA OUT3
RTD CH10 mA OUT4
RTD CH11
RTD CH12

56 | Easergy P3 Catalog

schneider-electric.com

Easergy P3 Advanced

Functional view
Easergy P3G30

DM105601b
RS232 RS232 RS232

HMI interface

I

0

Control buttons

Function key F1

ON
LED A LED C LED E LED G LED I LED K LED M
LED F1

Programmable Logic

Inputs

AND

TIMER

Mimic Diagram
I1: 0.0A I2: 0.0A I3: 0.0A P : 0.0W V : 0.0V

Service
LED B LED D LED F LED H LED J LED L LED N
LED F2

USB Local Port
F2

OR

COUNTER

XOR

Output

Setting groups:4

H2/H5 SOTF

38

49T

60

99

74

86

CLPU

AFD

Comm. interface - Slot 9

T

E

Protocols

RS232

M P

� Modbus � DNP3.0 � IEC-103

� SPAbus

Option card - Slot 6

Arc 1
A

Arc 2
A

Arc 3
A

Arc 4
A

67

21B 37P

I/O card G - Slot 5
DI19 DI20 DI21 DI22 DI23 DI24
T25 T26 T27 T28

50BF 50

I/O card G - Slot 4

59N

DI13 DI14 DI15 DI16 DI17 DI18

T21 T22 T23 T24

81R

51

67N

25

27N

81

64G

81U

50N

49

50G

51V

59

51N

46

51G

40

27

32Q

27P

Analog measurement card - Slot 8

Current input

Voltage input

I1 I2 I3 Io1 Io2 V1 V2 V3 V0

I/O card G - Slot 3
DI7 DI8 DI9 DI10 DI11 DI12
T17 T18 T19 T20

I/O card G - Slot 2
DI1 DI2 DI3 DI4 DI5 D6
T13 T14 T15 T16

Power Supply - Slot 1
T9 T10 T11 T12

T1 A1

SF

Other types of control

Arc sensor: See list of
Accessories REL52801 to
REL52810

G
Circuit Breaker controls

OR

REL52822

eSetup Easergy Pro

Comm. interface - Slot 9

Redundancy

Protocols

� RSTP � PRP
Two protocols at the same time

WebServer

� IEC 61850 � Modbus � DNP3.0 � IEC-101 � Ethernet/IP

Comm. interface - Slot 9

Redundancy

LC

LC

Protocols

� RSTP

� IEC 61850

� PRP

� Modbus

Two protocols at the same time

WebServer

� DNP3.0 � IEC-101 � Ethernet/IP

Comm. interface - Slot 9

Protocols
� IEC 61850 � Modbus � DNP3.0 � IEC-101

LC

RS232 + IRIG-B

Two protocols

at the

same time

� Ethernet/IP WebServer

Comm. interface - Slot 9

Protocols
� IEC 61850 � Modbus � DNP3.0 � IEC-101 � Ethernet/IP

RS232 + IRIG-B Two protocols at the same time
WebServer

REL52820

Connect to RS232 port
REL52816 REL52819

REL52821

Protocols Modbus DNP3.0 IEC-103
RS485

Protocols
Modbus DNP3.0 IEC-103 SPAbus

Protocols DeviceNet
RS485

Serial
Serial network

OR

REL52812
RS485

RTD CH01 RTD CH02 RTD CH03 RTD CH04 RTD CH05 RTD CH06 RTD CH07 RTD CH08 RTD CH09 RTD CH10 RTD CH11 RTD CH12

OR

REL52813 REL52814
RS485 Rx

Tx
Fiber Rx
Tx

PTC RTD CH01

RTD CH02 mA In1
RTD CH03 mA In2
RTD CH04 mA In3
RTD CH05
mA In4 RTD CH06

RTD CH07 mA OUT1
RTD CH08 mA OUT2
RTD CH09 mA OUT3
RTD CH10 mA OUT4
RTD CH11

RTD CH12

schneider-electric.com

Easergy P3 Catalog | 57

Easergy P3 Advanced

Functional view
Easergy P3G32

DM105602b
RS232 RS232 RS232

HMI interface

I

0

Control buttons

Function key F1

ON
LED A LED C LED E LED G LED I LED K LED M
LED F1

Programmable Logic

Inputs

AND

TIMER

Mimic Diagram
I1: 0.0A I2: 0.0A I3: 0.0A P : 0.0W V : 0.0V

Service
LED B LED D LED F LED H LED J LED L LED N
LED F2

USB Local Port
F2

OR

COUNTER

XOR

Output

Setting groups:4

H2/H5 SOTF

38

49T

60

99

74

86

CLPU

AFD

Comm. interface - Slot 9

T

E

Protocols

RS232

M P

� Modbus � DNP3.0 � IEC-103

� SPAbus

Option card - Slot 6

Arc 1
A

Arc 2
A

Arc 3
A

Arc 4
A

87M

67

21B 37P

I/O card 4 - Slot 5 Slot reserved

50BF 50

I/O card 3 - Current input
59N
IL'1 IL'2 IL'3 Io3

81R

51

67N

25

27N

81

64G

81U

50N

49

50G

51V

59

51N

46

51G

40

27

32Q

27P

Analog measurement card - Slot 8

Current input

Voltage input

IL1 IL2 IL3 Io1 Io2 V1 V2 V3 V0

I/O card G - Slot 3
DI7 DI8 DI9 DI10 DI11 DI12
T17 T18 T19 T20

I/O card G - Slot 2
DI1 DI2 DI3 DI4 DI5 D6
T13 T14 T15 T16

Power Supply - Slot 1
T9 T10 T11 T12

T1 A1

SF

Other types of control

Arc sensor: See list of
Accessories REL52801 to
REL52810

G
Circuit Breaker controls

OR

REL52822

eSetup Easergy Pro

Comm. interface - Slot 9

Redundancy

Protocols

� RSTP � PRP
Two protocols at the same time

WebServer

� IEC 61850 � Modbus � DNP3.0 � IEC-101 � Ethernet/IP

Comm. interface - Slot 9

Redundancy

LC

LC

Protocols

� RSTP � PRP
Two protocols at the same time

WebServer

� IEC 61850 � Modbus � DNP3.0 � IEC-101 � Ethernet/IP

Comm. interface - Slot 9

Protocols � IEC 61850 � Modbus � DNP3.0 � IEC-101 � Ethernet/IP

LC

RS232 + IRIG-B

Two protocols

at the

same time

WebServer

Comm. interface - Slot 9

Protocols � IEC 61850 � Modbus � DNP3.0 � IEC-101 � Ethernet/IP

Two protocols at the same time
WebServer

RS232 + IRIG-B

REL52820

Connect to RS232 port
REL52816 REL52819

REL52821

Protocols Modbus DNP3.0 IEC-103
RS485

Protocols
Modbus DNP3.0 IEC-103 SPAbus

Protocols DeviceNet
RS485

Serial
Serial network

OR

REL52812
RS485

RTD CH01 RTD CH02 RTD CH03 RTD CH04 RTD CH05 RTD CH06 RTD CH07 RTD CH08 RTD CH09 RTD CH10 RTD CH11 RTD CH12

OR

REL52813 REL52814
RS485 Rx

Tx
Fiber Rx
Tx

PTC RTD CH01

RTD CH02 mA In1
RTD CH03 mA In2
RTD CH04 mA In3
RTD CH05
mA In4 RTD CH06

RTD CH07 mA OUT1
RTD CH08 mA OUT2
RTD CH09 mA OUT3
RTD CH10 mA OUT4
RTD CH11

RTD CH12

58 | Easergy P3 Catalog

schneider-electric.com

PM106502 DM102188

Easergy P3 Advanced

Base unit presentation
Integrated arc flash protection

Easergy P3 Advanced measures fault current, and with arc protection, also light via arc sensor channels that provide monitoring for the whole switchgear.
An arc flash is a mass of heat and pressure caused by a switchgear fault. It not only causes power outages but can also result in loss of business and extensive material damage. If an arc fault occurs in the switchgear, the arc protection system prevents the fault from spreading by tripping the circuit breaker within less than 10 ms.
Easergy P3 Advanced relays can connect up to four arc flash sensors that have continuous self-supervision to check the sensor status.

Arc flash sensors Easergy P3 Advanced

1

2

3

4

Example of application
The four arc flash sensors can be installed in specific parts of the switchgear: 1. Busbars compartment 2. Circuit breaker compartment 3. Current/voltage transformers compartment 4. Cables connections compartment

Cable
4
CB
2

DM105582

CB 2

IEC 61850 (GOOSE) or by wire
1
BB
CB 2

Cable
3

Cable
3

schneider-electric.com

Easergy P3 Catalog | 59

DM105603

Easergy P3 Advanced

Base unit presentation
Local HMI

Mimic Diagram
I1: 0.0A I2: 0.0A I3: 0.0A P : 0.0W V : 0.0V

Comprehensive data for easier and faster operation
All the data you require for a local equipment operation can be displayed on demand: � Display the single line diagram and freely assignable analog values � Display of all measurements � Display of operation and alarm messages � Display and setting of all parameters � Password entry to protect parameter and protection settings

Single line diagram of the power system
INFO push-button for viewing additional information, entering the password view, and adjusting the LCD contrast F1 Programmable function push-button

PM106371

Ergonomic data presentation
� Keypad keys identified by pictograms for intuitive navigation � Graphical 128x128 LCD screen displays any character or symbol � Excellent display quality under all lighting conditions � Control buttons (0/1) to operate the circuit breaker and/or others controlled
object � 14 freely programmable LEDs with 3 different colors (red, yellow, and green) to
identify easily the message shown � Labels are printed on a transparent film allowing customisation of the relay � 2 programmable function keys (F1 / F2)
LED indicators

F2 Programmable function push-button

ENTER push-button for activating or OK confirming a function
UP navigation push-button for moving up in the menu or increasing a numerical value
DOWN navigation push-button for moving down in the menu or decreasing a numerical value
LEFT navigation push-button for moving backwards in a parallel menu or selecting a digit in a numerical value
RIGHT navigation push-button for moving forwards in a parallel menu or selecting a digit in a numerical value
O Circuit Breaker OFF push-button
Circuit Breaker ON push-button

128 x 128 LCD

Object control buttons

Navigation push-buttons

Local port

HOME/CANCEL push-button for returning to the previous menu. To return to the first menu item in the main menu, press the button for at least three seconds

Working language
All the texts and messages displayed on the Easergy P3 Advanced are available in two languages at the same time.

60 | Easergy P3 Catalog

schneider-electric.com

Easergy P3 Advanced

Base unit presentation
Rear panel

Rear panel example

Slot 1 2 3 4 5 6

8

PM106504

Easergy P3F30, P3M30 and P3G30

9

Slot 1 2 3 4 & 5 6

8

PM106503

Easergy P3M32, P3T32 and P3G32

9

Slot 1 2 3 4 & 5 6

8

PM106342

Easergy P3L30

9

Slots description for P3x30 models
Slot 1 - Power supply and output contacts Slot 2 - I/O card 1 Slot 3 - I/O card 2 Slot 4 - I/O card 3 Slot 5 - I/O card 4 Slot 6 - Option card 1 Slot 8 - Analog measurement card 1 Slot 9 - Communication interface
Slots description for P3x32 models
Slot 1 - Power supply and output contacts Slot 2 - I/O card 1 Slot 3 - I/O card 2 Slot 4/5 - Analog measurement card 2 Slot 6 - Option card 1 Slot 8 - Analog measurement card 1 Slot 9 - Communication interface
Slots description for P3L30 models
Slot 1 - Power supply and output contacts Slot 2 - I/O card 1 Slot 3 - I/O card 2 Slot 4 - I/O card 3 Slot 5 - I/O card 4 Slot 6 - Option card 1- Line differential com. Slot 8 - Analog measurement card 1 Slot 9 - Communication interface

schneider-electric.com

Easergy P3 Catalog | 61

Easergy P3 Advanced
Description of the optional boards
C = 5 x DO heavy duty, A1, SF D = 5 x DO heavy duty, A1, SF A = None G = 6DI+4DO (6 x DI, 4 x DO) H = 6DI+4DO (6 x DI, 4 x DO(NC)) I = 10DI (10 x DI)

Base unit presentation
Rear panel

Digital input and output capability

The Easergy P3 Advanced has a modular concept in term of digital inputs and outputs.

Number of

Input

Output

6

11

12

15

18

19

24

23

22

16

32

16

28

19

16

11

26

11

36

11

Slot 1 C/D C/D C/D C/D C/D C/D C/D C/D C/D C/D

Type of I/O card � P3X30

Slot 2

Slot 3

Slot 4

G

None

None

G

G or H

None

G

G or H G or H

G

G or H G or H

G

G or H

I

G

G or H

I

G

G or H G or H

G

I

None

G

I

I

G

I

I

Slot 5 None None None G or H None
I I None None I

PM106504

62 | Easergy P3 Catalog

P3x30 units

Number of

Input

Output

6

11

12

15

16

11

Slot 1 C/D C/D C/D

Type of I/O card � P3X32

Slot 2

Slot 3

Slot 4

G

None

None

G

G or H

None

G

I

None

Slot 5 None None None

PM106503

The slots 4 and 5 are used to receive the analog current input when Easergy P3 is used with differential overcurrent (ANSI 87).

P3x32 units schneider-electric.com

Easergy P3 Advanced

Base unit presentation
Remote HMI
This mounting technique allows for a lighter door because the relay's frame is installed in the back of the secondary compartment. Communication, DI, and DO cabling is easier, too, as the door movement does not need to be considered. In this case, only the communication between IED base and display has to be wired.

DM105604

Easergy

schneider-electric.com

Easergy P3 Catalog | 63

Easergy P3 Advanced
Conventional HMI

DM105605

Base unit dimensions
Dimensions

mm in
Easergy

264 10.37

177 6.97

208 8.18 183 7.20
150 5.91

Remote HMI

DM105606

199 7.83
180 7.09

247 9.72
180 7.09

199 7.81
150 5.91

Weight (maximum) Easergy P3 Advanced

4.2 Kg (9.272 Ib) or higher (depends of options)

Degree of protection (IEC 60529) IP54 Front panel / IP20 Rear side

64 | Easergy P3 Catalog

schneider-electric.com

Easergy P3 Advanced

Base unit dimensions
Cut-out and mounting

Cut-out accuracy must be complied with to ensure good withstand.

Mounting
In case the depth dimension behind the compartment door is limited, the IED can be equipped with a frame (REL52832) around the collar. This arrangement reduces the depth inside the compartment by 45 mm (1.77 in).

DM105607

Projection mounting with the raising frame REL52832
225 8.86

Panel mounting
EaEsaesregrygy

152 5.98

Easergy

1.0-60

Raising frame REL52832

269

10.59

224 8.82

45 1.77

Raising frame REL52832

152 5.98
177 7.0

153 6.02 183 7.20

223.33 9.17

253.40 9.97

Mounting frame

24.60 0.97

Wall mounting with remote HMI

DM105608

210 8.27 �5 0.2

mm

100

in

3.94

MTo4rxx2T0-20 1.5Nm

18 0.71

11.5

0.45

20 34

0.79 1.34

Easergy

T max. 1.2Nm 10.6 lb.in

T max. 0.5...0.6Nm 4.4...5.3 lb.in

3 180 7.09 � 7 0.28
180 7.09

min. 2.5mm2 � 5-8mm
Nut M5 1.5 Nm, 13.3 Ib in

schneider-electric.com

Easergy P3 Catalog | 65

Easergy P3 Advanced

Base unit characteristics
Technical characteristics

Analog inputs

Rated phase current

Phase Current Input (I) Slot 8

1 A CT 5 A CT

Residual Current Input (I0) Slot 8 - 5 A CT Configurable for CT secondaries 0.1 to 10A

Residual Current Input (I0') Slot 8 - 1 A CT Configurable for CT secondaries 0.1 to 10.0A

Residual Current Input (I0') Slot 8 - 0.2 A CSH sensor Configurable for CT secondaries 0.1 to 10.0A

Phase Current Input - (I') Slot 4 (Only for device with differential overcurrent)

1A CT 5A CT

Residual Current Input (I0'') Slot 4 (Only for device with differential overcurrent)

1A CT 5A CT

Voltage Input Configurable for VT secondaries 50 to 120 V

Measuring range
0.02 � 50 A 0.05 � 250 A
0.015 � 50 A
0.003 � 10 A
0.0006 � 2 A
0.02 � 50 A 0.05 � 250 A 0.02 � 50 A 0.05 � 250 A 0.5 � 190 V (100V / 110 V)

Input Impedance
0.02 Ohm 0.003 Ohm
0.003 Ohm
0.02 Ohm
0.02 Ohm
0.02 Ohm 0.003 Ohm 0.02 Ohm 0.003 Ohm
n.a.

Consumption
0.02 VA 0.075 VA

Rated thermal withstand
4 A
20 A

0.075 VA

20 A

0.02 VA

4 A

0.02 VA
0.02 VA 0.075 VA 0.02 VA 0.075 VA < 0.5 VA

0.8 A
4 A 20 A 4 A 20 A 250 V (Continuously)

1-second overload
100 A 500 A
500 A
100 A
20 A
100 A 500 A 100 A 500 A n.a.

10-second overload
20 A 100 A
100 A
20 A
4 A
20 A 100 A 20 A 100 A 600 V

Analog temperature input / Analog output

Type of temperature sensor

Maximum distance between sensor and module

Analog Output

Minimum current

Maximum current

Pt100 up to 2,000 m(1)

Ni100

Ni120

up to 2,000 m (1)

up to 2,000 m (1)

0 mA

20 mA

Cu10 up to 2,000 m (1)

Operating temperature: Power supply

Digital Input
Nominal operation voltage Typical switching threshold Input limit voltage

Frequency Typical consumption Voltage withstand

Digital Output

Type of contact

Rated Voltage

Continuous current

Breaking

AC

capacity

DC

(L/R=40ms)

Making capacity

Minimum making capacity Typical operation time Contact material

REL52811 / REL52812 REL52813 REL52814
DI1 to DI16 At state 1 At state 0
at 48 V dc at 110 V dc at 220 V dc < 0.5 s < 3.0 s

0�C (32�F) to +55�C (131�F) 24 to 230 Vac/dc, 50/60 Hz
24 Vdc 48 to 230 Vac/dc, 50/60 Hz

24 to 230 Vac/dc 12 Vdc
 19.2 Vdc < 10.0 Vdc 45 to 65 Hz

110 to 230 Vac/dc 75 Vdc  88 Vdc < 60 Vdc
45 to 65 Hz <4 mA (typical approx. 3 mA)
255 V ac/dc

Control and Trip contact, Tx 250 Vac/dc 5 A 2.000 VA 1.15 A 0.5 A 0.25 A 30 A 15 A
100 mA @ 24 Vac/dc <8 ms
AgNi 90/10

Signal contact, A1 250 Vac/dc 5 A 2.000 VA 1 A 0.3 A 0.15 A 30 A 15 A
100 mA @ 24 Vac/dc -
AgNi 0.15 gold plated

220 to 230 Vac/dc 155 Vdc  176 Vdc < 140 Vdc
45 to 65 Hz
Signal Contact, SF 250 Vac/dc 5 A 2.000 VA 1 A 0.3 A 0.15 A -
100 mA @ 24 Vac/dc -
AgNi 0.15 gold plated

Power supply Nominal Voltage Range Inrush current (DC)
Power consumption
Acceptable momentary outages (1) 78,740 in

110-240 V ac/dc

24-48 Vdc

-20% / +10% (88 to 264 Vac/dc)

-20% / +20% (19.2 to 57.6 Vdc)

25 A with time constant of 1000 �s

25 A with time constant of 750 �s

15 A with time constant of 500 �s

Power consumption increases when more I/O or optional I/O or communication cards are used

Max. 50 W

<50 ms (110 Vdc)

66 | Easergy P3 Catalog

schneider-electric.com

Easergy P3 Advanced

Base unit characteristics
Environmental characteristics

Emission Conducted Emitted Immunity 1 Mhz damped oscillatory wave Static discharge (ESD) Emitted HF field Fast transients (EFT) Surge Conducted HF field Power-frequency magnetic field Pulse magnetic field ac and dc voltage dips
ac and dc voltage interruptions
Voltage alternative component
In operation Vibrations Shocks Seismic De-energized Vibrations Shocks Bump

Standard and test class/level IEC/EN 60255-26 (ed3) EN 55022, Class A / CISPR 22 EN 55011, Class A / CISPR 11 IEC/EN 60255-26 (ed3) IEC/EN 61000-4-18 IEC/EN 61000-4-2 Level 4 IEC/EN 61000-4-3 Level 3 IEC/EN 61000-4-4 Level 4 IEC/EN 61000-4-5 Level 4 IEC/EN 61000-4-6 Level 3 IEC/EN 61000-4-8 IEC/EN 61000-4-9 Level 5 IEC/EN 61000-4-29, IEC/EN 61000-4-11
IEC/EN 61000-4-29, IEC/EN 61000-4-11
IEC/EN 61000-4-17

Disturbance tests
Test value
0.15 � 30 MHz 30 � 1000 MHz
�2.5kVp CM �2.5kVp DM �8 kV contact �15 kV air 80 - 2700 MHz, 10 V/m �4 kV, 5/50 ns, 5 kHz �4 kV, 1.2/50 �s, CM �2 kV, 1.2/50 �s, DM 0.15 - 80 MHz, 10 Vrms 300A/m (continuous) 1000 A/m 1 � 3 s 1000A/m, 1.2/50 �s 0% of rated voltage
� ac:  0.5 cycle � dc:  10 ms 40% of rated voltage � ac: 10 cycles � dc: 200 ms 70% of rated voltage � ac: 25 cycles � dc: 500 ms 100% interruption � ac: 250 cycles � dc: 5 s 15% of operating voltage (dc) / 10 min

Standard and test class/level
IEC 60255-21-1, Class II / IEC 60068-2-6, Fc IEC 60255-21-2, Class II / IEC 60068-2-27, Ea IEC 60255-21-3 Method A, Class II
IEC 60255-21-1, Class II / IEC 60068-2-6, Fc IEC 60255-21-2, Class II / IEC 60068-2-27, Ea IEC 60255-21-2, Class II / IEC 60068-2-27, Ea

Mechanical robustness
Test value
1 Gn, 10 Hz � 150 Hz 10 Gn / 11 ms 2G horizontal / 1G vertical , 1�35 Hz
2 Gn, 10 Hz � 150 Hz 30 Gn / 11 ms 20 Gn / 16 ms

schneider-electric.com

Easergy P3 Catalog | 67

Easergy P3 Advanced

Base unit characteristics
Environmental characteristics

In operation Impulse voltage withstand Dielectric test Insulation resistance Protective bonding resistance Clearance and creepage distance Power supply burden
In operation Dry heat Cold Damp heat, cyclic
Damp heat, static
Change of temperature
In storage Dry heat Cold

Standard and test class/level

Electrical safety
Test value

IEC/EN 60255-27
IEC/EN 60255-27
IEC/EN 60255-27 IEC/EN 60255-27 Design criteria for distances as per IEC 60255-27 Annex C (pollution degree 2, overvoltage category 3) IEC 60255-1

5 kV, 1.2/50 �s, 0.5 J 1 kV, 1.2/50 �s, 0.5 J Communication
2 kV, 50 Hz 0.5 kV, 50 Hz Communication

Standard and test class/level EN / IEC 60068-2-2, Bd EN / IEC 60068-2-1, Ad EN / IEC 60068-2-30, Db
EN / IEC 60068-2-78, Cab
IEC / EN 60068-2-14, Nb
EN / IEC 60068-2-2, Bb EN / IEC 60068-2-1, Ab

Environmental tests
Test value
70�C (158�F) -40�C (-40�F) From 25�C (77�F) to 55�C (131�F) From 93% RH to 98% RH Testing duration: 6 days 40�C (104�F) 93% RH Testing duration: 10 days Lower temp -40�C (-40�F) Upper temp 70�C (158�F) 5 cycles
70�C (158�F) -40�C (-40�F)
Environmental conditions

Ambient temperature, in-service Ambient temperature, storage Relative air humidity Maximum operating altitude

-40�C � 60�C (-40�F � 140�F) (1) -40�C � 70�C (-40�F � 158�F) < 95%, no condensation allowed 2000 m (6561.68 ft)

(1) with 1 x raising frame -> maximum ambient temperature 55�C (+131�F) with 2 x raising frame -> maximum ambient temperature 50�C (+122�F)

68 | Easergy P3 Catalog

schneider-electric.com

PM106362

Easergy P3 Advanced

Communication
Communication protocols

Easergy P3 Advanced can be connected to networks, providing access to the following type of data:
� Events � Status information � Measurements � Control commands � Clock synchronizing � Settings
(SPA-bus and embedded SPA-bus only)
Easergy SmartApp.

Main Protocols

Easergy P3 Advanced can be connected directly to serial and/or Ethernet protocols with two different protocols at the same time, selected by eSetup Easergy Pro software.

Communication protocols:

Communication ports:

Serial protocols - RS232 / RS485 / serial Fiber Optic (*) port Modbus RTU DNP3.0 IEC 60870-5-101 IEC 60870-5-103 DeviceNet (*) ProfibusDP (*) SPA-Bus (*) Ethernet protocols RJ45 / LC port IEC61850 ed1 & ed2 Modbus TCP IEC60870-5-101 DNP3.0 Ethernet IP

Comm. interface - Slot 9

Redundancy

LC

LC

� RSTP � PRP

Two protocols at the same time

WebServer

Protocols
� IEC 61850 � Modbus � DNP3.0 � IEC-101 � Ethernet/IP

Protocols
� IEC 61850 � Modbus � DNP3.0 � IEC-101 � Ethernet/IP

Comm. interface - Slot 9

LC

RS232 + IRIG-B

Two protocols at the same time
WebServer

Comm. interface - Slot 9
Redundancy � RSTP � PRP

Two protocols at the same time

WebServer

Protocols
� IEC 61850 � Modbus � DNP3.0 � IEC-101 � Ethernet/IP

Protocols � IEC 61850 � Modbus � DNP3.0 � IEC-101 � Ethernet/IP
Protocols � Modbus � DNP3.0 � IEC-103 � SPAbus

Comm. interface - Slot 9
RS232 + IRIG-B
Two protocols at the same time WebServer
Comm. interface - Slot 9
RS232

*Need external accessories to connect.

Redundancy protocols (RSTP or PRP)
When the devices are connecting in Ethernet link and demand for higher availability, Easergy P3 Advanced can use Rapid Spanning Tree Protocol (RSTP) or Parallel Redundancy Protocol (PRP) to recover from a network failure.

Easergy P3 web-HMI

Easergy P3 web-HMI
A webserver is available in all Easergy P3 Advanced to get information from the device to monitoring all data, send command and change protection setting.

PM106576

schneider-electric.com

Easergy P3 Catalog | 69

Easergy P3 Advanced

Programmable stages
Programmable protection function
Personalize your protection function
Easergy P3 Standard enables you to create or personalize the protection function when you need to achieve specific levels of protection. There are now eight stages available to use with various applications. Each stage can monitor any analog (measured or calculated) signal and issue start and trip signals. Programmable stages extend the protection functionality of the manager series to a new level. The Programmable stage has the possibility of comparing two freely selectable signals between each other. Using this feature you can create a comparison function using the relay's own measured or calculated signals. One or both of the signals can be connected to the comparison function over GOOSE. For example, if four stages of frequency are not enough, it is possible to reach a maximum of 12 using programmable stages. Other examples include using the stages to issue an alarm when there are too many harmonics (THD) or indicating reverse power condition by GOOSE.

EM100170

70 | Easergy P3 Catalog

schneider-electric.com

Easergy P3 Advanced

Circuit breaker control

With Easergy P3 Advanced, you get intuitive functionality to protect your electrical network system.
Main CB functions are: � Trip circuit supervision (ANSI 74) � CT/VT supervision (ANSI 60/60FL) � Latching (ANSI 86) � CB close/open order � Number of operations � Circuit breaker operating time � Charging time � Cumulative breaking current � Personalized functions

Maximize circuit breaker control
Easergy P3 Advanced is the simplest protection relay with mimic diagram with control buttons (open and close), two personalized function keys and 14 configurable tricolor LEDs. You can manage the control without external or additional components.
Example of implementation The schematic is structured for typical use in MV switchgear, 100% adapted for your use case. You can change the internal logic to adapt the Easergy P3 to meet your needs.
If a problem occurs, clear and complete information allows you to make the right decisions immediately.

MV network
CT
This electrical schematic can facilitate the IEC 61850 implementation because all the logics are done by the protection unit that will make the decisions and, if necessary, send GOOSE messages to other units.

DM105592

HMI interface

I

0

Control buttons

Function key F1

ON
LED A LED C LED E LED G LED I LED K LED M
LED F1

Mimic Diagram
I1: 0.0A I2: 0.0A I3: 0.0A P : 0.0W V : 0.0V

Service
LED B LED D LED F LED H LED J LED L LED N
LED F2

USB Local Port
F2

Inputs

AND

TIMER

Latching contact ANSI 86

Trip control Order contact

OR

COUNTER

Trip Circuit Supervision

XOR

Output

Nominal voltage
Alarm contact for Trip circuit failure

T2
Close contact Order contact
T3
0 1
Open/Close Mechanical command

A1

T1

Digital Input 2

Digital Input 1

Trip circuit supervision

Trip circuit supervision

Trip circuit failure alarm

DI 2

DI 1

52a

CLOSE COIL

OPEN COIL

52b
Circuit Breaker

schneider-electric.com

Easergy P3 Catalog | 71

DM105651

Easergy P3 Advanced

Power quality measurements

Power quality
The power quality of electrical networks has become increasingly important in modern society. Sophisticated loads, such as computers and automation systems, require an uninterrupted supply of "clean" electricity. Easergy P3 Advanced provides integrated power quality measuring and analysis functions, which help to reduce variations in the quality of the distributed power. The terminal supervises the harmonics of phase currents and voltages from the 2nd to the 15th order and the THD (total harmonic distortion)..
One of the most important power quality functions is the monitoring of voltage sags and swells. Easergy P3 Advanced provides separate monitoring logs for sags and swells. The fault log comprises four registers for voltage sags and another four for voltage swells.
The disturbance recorder functionality can be used for recording measured currents and voltages and for recording status information of digital inputs and outputs, also including the signals of the arc protection system. The time stamped recordings provide indispensable information for the subsequent analysis of a fault situation.

Example of harmonics content and voltage sag/swell registration (obtained from an Easergy P3 Advanced protection relay)
Many functions in modern society rely heavily on electrical energy, so the quality of the energy supply is gaining increased importance..

Power Quality data in Easergy P3 Advanced

THD of IL1, IL2 and IL3 Total harmonic distortion of phase currents

H of IL1, Il2 and IL3

Harmonics phase current up to 15th

THD of U

Total harmonic distortion of phase to phase or phase to ground voltages

H of U

Harmonic of phase to phase or phase to ground voltage up to 15th

Sag and swell

Voltage interruptions

72 | Easergy P3 Catalog

schneider-electric.com

Easergy P3 Advanced

Connection diagrams
Easergy P3x30

DM105609b

DANGER
HAZARD OF ELECTRIC SHOCK, ELECTRIC ARC OR BURNS
- only qualified personnel should install this equipment. Such work should be performed only after reading this entire set of instructions.
- NEVER work alone.
- turn off all power supplying this equipment before working on or inside it. Consider all sources of power, including the possibility of backfeeding.
- always use a properly rated voltage sensing device to confirm that all power is off.
- start by connecting the device to the protective earth and to the functional earth.
- screw tight all terminals, even those not in use.
Failure to follow these instructions will result in death or serious injury.

Arc Flash Sensor

Arc Flash Sensor

Arc Flash Sensor

Arc Flash Sensor
1 0

1

1

2

DI1

V1

2

3

2

USB

3

4

DI2

Local Port

V2

4 5

5

V3

6

DI3 6

8/2

7

8

DI4

9

DI5 10

11 DI6
12

13

T13

14

15

T14

16

17

T15

18

19

T16

20

1
2 3
4 5
6
7 8 5A 9 10 11 1 A 12

P3x30
I1 I2 I3
8/1 IIoo Io

3

DI7 DI8 DI9 DI10 DI11

4 1

2

1

DI13

3

2

5 1

4 DI14

3

DI19

2

5

4

3

6 DI15

5

DI20

4

7

6

5

8

7

DI21

9

DI16

8

6 7

10 DI17 11

DI22 10

8

DI12 T17

12 13

DI18

11 12

14

T21

13

T18 15

14

16 T19 17
18

T22

15

16

T23

17

T20 19

18

20

T24 19

20

DI23 10

11 DI24
12

T25

13

14 T26 15

16 T27 17

18 T28 19

7

20

8

V4

8/2

A

Arc 1

A

Arc 2

A Arc

6

3

A Arc 4

T12 20

19 T11 18

17 T10 16

15

T9

14

T1, T9, T10, T11 and T12: 5 heavy duty trip relay for arc protection

13

T1

12

11

A1

10 9

8

SF

7 6

5

1

2

1

9

Redundant Ethernet Network - RSTP or PRP

schneider-electric.com

Easergy P3 Catalog | 73

Easergy P3 Advanced

Connection diagrams
Easergy P3x32

DM105610b

DANGER
HAZARD OF ELECTRIC SHOCK, ELECTRIC ARC OR BURNS
- only qualified personnel should install this equipment. Such work should be performed only after reading this entire set of instructions.
- NEVER work alone.
- turn off all power supplying this equipment before working on or inside it. Consider all sources of power, including the possibility of backfeeding.
- always use a properly rated voltage sensing device to confirm that all power is off.
- start by connecting the device to the protective earth and to the functional earth.
- screw tight all terminals, even those not in use.
Failure to follow these instructions will result in death or serious injury.

Arc Flash Sensor

Arc Flash Sensor

Arc Flash Sensor

Arc Flash Sensor
1 0

1

1

2

DI1

V1

2

3

2

USB

3

Local Port

V2

4

DI2

4 5

5
DI3 6
7

V3

6

8/2

8

DI4

9

DI5 10

11 DI6
12

13

T13

14

15

T14

16

17

T15

18

19

T16

20

3

1 DI7
2

3

P3x32

DI8

4

5 DI9
6
7
DI10 8 9
DI11 10

11 DI12
12

1

2

I1

3

4

I2

5

6

I3

T17

13

14

T18

15

16

T19

17

7 8 5A 9
10 11 1 A 12

8/1 IIoo1
Io2

18

T20

19

20

7

8

V4

8/2

A

Arc 1

A

Arc 2

A Arc

6

3

A Arc 4

T12 20

19 T11 18

17 T10 16

15

T9

14

4

1

2 1A 3

I'1

4

5 1A 6

I'2

7

8 1A 9

I'3

10

11 1 A 12

Io3

13

T1

12

11

A1

10 9

8

SF

7 6

5

1

2

1

9

T1, T9, T10, T11 and T12: 5 heavy duty trip relay for arc protection

Redundant Ethernet Network - RSTP or PRP

74 | Easergy P3 Catalog

schneider-electric.com

Easergy P3 Advanced

Connection diagrams
Easergy P3L30

DM105611b

DANGER
HAZARD OF ELECTRIC SHOCK, ELECTRIC ARC OR BURNS
- only qualified personnel should install this equipment. Such work should be performed only after reading this entire set of instructions.
- NEVER work alone.
- turn off all power supplying this equipment before working on or inside it. Consider all sources of power, including the possibility of backfeeding.
- always use a properly rated voltage sensing device to confirm that all power is off.
- start by connecting the device to the protective earth and to the functional earth.
- screw tight all terminals, even those not in use.
Failure to follow these instructions will result in death or serious injury.

1 0

Line Diff. Network

1

1

2

DI1

V1

2

3

2

USB

3

4

DI2

Local Port V2

4 5

5
DI3 6
7

V3

6

8/2

8

DI4

9 DI5
10

11 DI6
12

13

T13

14

15

T14

16

17

T15

18

19

T16

20

P3L30

1
2 3
4 5
6
7 8 5A 9 10 11 1 A 12
7

I1 I2 I3
8/1 IIoo
Io

3

DI7 DI8 DI9 DI10 DI11

4

1

5

2

1

DI13

3

2

1

4 DI14

3

DI19

2

5

4

3

6 DI15

5

DI20

4

7

6

5

8

7

DI21

9

DI16

8

6 7

10 DI17 11

DI22 10

8

DI12 T17

12 13 DI18

11

DI23

12

10 11

14

T21

13

DI24

T18 15 16

14

T22

15

12

T25

13

T19 17 18

16

T23

17

14

T26

15

T20 19 20

18

T24

19

16

T27

17

20

18

T28

19

20

8

V4

8/2

T12 20

19 T11 18

17 T10 16

15

T9

14

T1, T9, T10, T11 and T12: 5 heavy duty trip relay for arc protection

13

T1

12

Diff. Comms. Card

RX

6

TX

11

A1

10 9

8

SF

7 6

5

1

2

1

9

Redundant Ethernet Network - RSTP or PRP

schneider-electric.com

Easergy P3 Catalog | 75

Easergy P3 Advanced

PM106371

PM106371

Model selection
Selecting product

Please, consult the "Ordering" section to choose specific characteristics in the relays for your system:

P3F30 Feeder application
P3L30 Line application
P3M30 Motor application
P3G30 Generator application

Page 109 Page 110 Page 111 Page 112

P3T32 Transformer Page 113
with differiential application P3M32 Motor
Page 114 with differential application P3G32 Generator
Page 115 with differrential application

Or use our web configuration tool:
Go to web configurator

76 | Easergy P3 Catalog

schneider-electric.com

Notes

schneider-electric.com

Easergy P3 Catalog | 77

Easergy digital experience

78 | Easergy P3 Catalog

schneider-electric.com

Easergy digital experience

Easergy P3 software

80

Presentation

80

eSetup Easergy Pro

82

eSetup Easergy Pro during engineering

82

eSetup Easergy Pro during commissioning

83

eSetup Easergy Pro during operation

84

Easergy web-HMI

85

Easergy SmartApp

86

schneider-electric.com

Easergy P3 Catalog | 79

Easergy digital experience

Easergy P3 software
Presentation

Minimum requirements for running eSetup Easergy Pro:
� Windows 7 or higher � 512 MB RAM � 50 MB Disk space

eSetup Easergy Pro
eSetup Easergy Pro offers full facilities to set up Easergy relays. Intuitive and simple, eSetup Easergy Pro is a user-oriented interface to assist you during the engineering, commissioning and operation of Easergy protection relays. ts streamlined workflow and graphical representations has been designed to smooth your configuration process. The software is available for download on the Schneider Electric website.

DM105612 DM105613 DM105614

eSetup Easergy Pro

eSetup Easergy Pro

eSetup Easergy Pro

Use eSetup Easergy Pro in standalone mode during engineering to prepare the configuration.

Connect the PC running eSetup Easergy Pro to the USB port of the Easergy protection relay during commissioning to adjust the settings and test the relay.

For connection to Easergy P3, use the REL52822 connection cord

Connect the PC running eSetup Easergy Pro to the Ethernet network during operation to retrieve data from the relays and update the system.

80 | Easergy P3 Catalog

schneider-electric.com

DM105615
Engineering

Easergy digital experience

Easergy P3 software
Presentation

eSetup Easergy Pro at each step of the digital life

Commiss

ioning

Operation

schneider-electric.com

Easergy P3 Catalog | 81

Easergy digital experience

eSetup Easergy Pro
During engineering

� Create the configuration of the Easergy P3 relay: select the appropriate options and receive the order code
� Set the characteristics of the CTs, VTs, or sensors connected to the relay, and select the protection functions that will be activated and their settings
� Build a specific logic, if required, using a graphic editor � Map the digital inputs of the relay and different internal signals to the relevant
functions, LEDs, and digital outputs, using a straightforward matrix format. � Draw the single-line diagram that will appear on the front display of the relay for
switchgear control and select the measurements that will be displayed. If any, build the interlocking logic using a matrix format � For IEC 61850 protocol, configure the data set and the report control blocks that will be published and select the GOOSE data to which you want to subscribe � Complete the setting of additional functions (disturbance recorder, event logging system, clock synchronization, etc.).

EM106160

EM106161

EM106162

82 | Easergy P3 Catalog

schneider-electric.com

Easergy digital experience

eSetup Easergy Pro
During commissioning

� Connect to the front panel of one single relay or access several relays by connecting to Ethernet
� Open the Digital Inputs menu to check the status of inputs. Reverse the polarity or add a filtering delay if necessary
� Open the Relays menu and force the status change of the output relays in order to check the wiring.
� Open the Phasor Diagram menu to see in real time the phasor of injected currents and voltages and the value
� Use virtual injection for testing protection settings and circuit breaker tripping and for checking LEDs and connected outputs
� Open the Logic or the Matrix menu if the logic needs to be tested. The active signals appear in a different color and are updated in real time. Changes in the logic or in the matrix can be made and applied to the relay smoothly.

EM106163

EM106164

EM106165

schneider-electric.com

Easergy P3 Catalog | 83

Easergy digital experience

eSetup Easergy Pro
During operation

� Connect to the front panel of a single relay or gain access to several relays by connecting to Ethernet
� During normal operation, get the most of the metering capabilities of the Easergy protection relay: �� Open the different Measurements menus to access the power monitoring and power quality data.
�� Open the disturbance recorder menu to get a waveform capture or program the recording of a power trend.
� After a trip, use eSetup Easergy Pro to understand the fault: �� Check the fault log of the protection that has tripped the circuit breaker
�� Download the disturbance record from the Easergy P3 and display it with a disturbance recorder evaluation tool, eg. Wavewin.

EM106166

EM106168 EM106167

84 | Easergy P3 Catalog

schneider-electric.com

Easergy digital experience

Easergy web-HMI
Description

Enhance operational efficiency
� Direct access to protection and communication settings
� Control and monitoring of circuit breakers and switches
� Mirror HMI function � Direct access to measurements including
the graphic phasors � Device diagnosis � MATRIX status � Access to logs and other information

Boost operational efficiency with the embedded web-HMI
Quickly and conveniently configure, monitor, and operate your Easergy P3 protection relay with our web-HMI. The web-HMI, accessible online via IP address of the relay, doesn't require you to install specific computer software - simply use your web browser to connect to the device. You only need to enable the web server service during the initial configuration of Easergy P3 with eSetup Easergy Pro. The web-HMI is based on the same page design as eSetup Easergy Pro, making it easy to use!

schneider-electric.com

Easergy P3 Catalog | 85

Easergy digital experience

Easergy SmartApp
Description

Discover how the Easergy SmartApp can simplify your daily operations
Use the Easergy SmartApp to control Easergy P3 to improve safety, simplify operations and maintenance, and save valuable operational time(1).
Safety
The Easergy SmartApp improves safety by allowing the operator to stay away from the circuit-breaker during operations.
Simplicity
The Easergy SmartApp provides easy access to device status, control, and monitoring of the circuit breaker, measurements, settings, events and other functions, through the mirror HMI or a simplified view.
� Mirror HMI: Duplicate the device display in the Easergy SmartApp to perform actions more easily and safely.
� Simplified view: The Easergy SmartApp gives you an organized view of all the device's functionalities for simpler access to the data. You benefit from a clearer overview of the switchgear's health, faster issue resolution, and safer operations.
Easergy SmartApp screens example

Free download on:

86 | Easergy P3 Catalog

(1) Wi-Fi is not embedded in Easergy P3, a separate Wi-Fi router connected to an Ethernet port of the device is required.
schneider-electric.com

Notes

schneider-electric.com

Easergy P3 Catalog | 87

Additional modules and accessories

88 | Easergy P3 Catalog

schneider-electric.com

Additional modules and accessories

Connection cables

90

Communication modules

92

Temperature and analogue input and output modules

94

Arc flash sensors

96

schneider-electric.com

Easergy P3 Catalog | 89

PM106970

PM106980

PM106969

Additional modules and accessories

Connection cables
Description

Cables for Easergy P3 Standard

The cables can be used for connecting external option modules to the Easergy P3 Standard. The device is equipped with I/O communication model E or F, where RS232 interface is available.

REL52825

A remote port is available when a REL52825 cable is used. The cable contains a connector for the RS-232 interface of the Easergy P3 Standard and a D9connector for the external option module.

Length

2.5 m (78.74 in)

REL52827
The cable contains a connector for the RS-232 interface of the Easergy P3 Standard and a D9-connector for the REL52815 Profibus interface module. An extension port is available for the REL52827 in Easergy P3 Standard.

Length

3.0 m (118.11 in)

REL52826
Remote and extension ports are available, in addition to IRIG-B clock synchronization, when the REL52826 cable is used. The REL52826 cable contains a connector for the RS-232 interface of the Easergy P3 Standard and a 3-piece D9-connector for the external option module and IRIG-B.

Length

2.5 m (78.74 in)

90 | Easergy P3 Catalog

schneider-electric.com

PM106978

PM106979

PM106978

Additional modules and accessories

Connection cables
Description

Cables for Easergy P3 Advanced
The cables can be used for connecting external option modules to the Easergy P3 Advanced.The device is equipped with I/O communication model B, C or D, where RS232 interface is available.
REL52823
Remote and extension ports are available in addition to IRIG-B clock synchronization when the REL52823 cable is used. The REL52823 cable contains a connector for the RS232 interface of Easergy P3 Advanced and 3-piece D9-connector for the external option module and IRIG-B.

Length

3.0 m (118.11 in)

REL52824
The cable contains a connector for the RS232 interface of Easergy P3 Advanced and D9-connector for the REL52815 Profibus interface module. An extension port is available for the REL52824 in Easergy P3 Advanced.

Length

3.0 m (118.11 in)

Cables for all Easergy P3 models
Front face USB Cable - REL52822 The Easergy P3 protection relays have a USB-connector in the front panel. Use eSetup Easergy Pro setting software with USB cable to set the device.

Length

3.0 m (118.11 in)

schneider-electric.com

Easergy P3 Catalog | 91

PM106586

PM106581

Additional modules and accessories

Communication modules
Network interface modules

RS232 to RS485 network � REL52820

The external RS485 interface REL52820 is used to connect Easergy P3 devices to the RS485 network. With the RS485 serial interface module it is possible to have following serial protocols in use.

Characteristics

Distance (maximum)

200 m (7,874.02 in)

Devices (maximum)

32

Type of fiber optic connector PIN (3)

Type of RS232 connector

9-pin DSUB connector

RS485 type

2-wire

Serial protocols

Modbus, DNP3.0, IEC870-5-103 and SpaBus

Power supply

From RS232 port or external � 12Vdc

To connect the interface with: Easergy P3 Standard devices, use REL52825 cable Easergy P3 Advanced devices, use REL52823 cable if needed

RS232 to fiber optic network � REL52816 to REL52819

An external fiber optic interface is used to connect Easergy P3 devices to a fiber optic loop or a fiber optic star network. The options include two different types of serial fiber optic modules.

Characteristics

REL52819

REL52816

Distance (maximum)

30 m (1,181 in)

1,000 m (39,370 in)

Type of fiber optic

Plastic-Plastic

Glass-Glass

FO diameter

1 mm

62.5/125 uM

Devices (maximum)

32

32

Type of fiber optic connector HP Versalink Snap-in

ST

connector

Interface

9-pin DSUB connector

Serial protocols

Modbus, DNP3.0, IEC870-5-103 and SpaBus

Power supply

From RS232 port or external � 12 Vdc

To connect the interface with: Easergy P3 Standard devices, use REL52825 cable Easergy P3 Advanced devices, use REL52823 cable if needed

92 | Easergy P3 Catalog

schneider-electric.com

PM106585

PM106580

Additional modules and accessories

Communication modules
Network interface modules

DeviceNet network interface � REL52821
External RS485 DeviceNet interface REL52821 is used to connect Easergy P3 devices to RS485 network using DeviceNet protocol.

Characteristics

Distance (maximum)

200 m (7,874.02 in)

Devices (maximum)

32

Type of output connector PIN

Type of RS232 connector 9-pin DSUB connector

Serial protocols

DeviceNet

Power supply

Need power feed from both RS232 port and external 24 Vdc

To connect the interface with: Easergy P3 Standard devices, use REL52825 cable Easergy P3 Advanced devices, no additional cable required

Profibus network interface � REL52815
External Profibus interface REL52815 is used to connect Easergy P3 devices to the Profibus network.

Characteristics

Interface

9-pin DSUB connector (Female)

Transfer method

RS485, Half-duplex

Transfer cable

Twisted pair (1 pair and shield)

Electrical isolation

500 Vdc

Serial protocols

Profibus DP

Baud rate

9.6 kBaud to 12 Mbaud

Power supply Easergy P3 Standard: Easergy P3 Advanced:

External � 12Vdc From RS232 port or external � 12Vdc

To connect the interface with: Easergy P3 Standard devices, use REL52827 cable Easergy P3 Advanced devices, use REL52824 cable

schneider-electric.com

Easergy P3 Catalog | 93

Additional modules and accessories

Temperature and analog input/output modules
For Easergy P3

The temperature module is supplied ready for operation with:
� Easergy P3U20, P3U30 with RS485 communication port direct
� Easergy P3U20, P3U30, and P3X3x with RS232 communication port by REL52820 external RS485 interface
� Easergy P3U20, P3U30, and P3X3x with RS232 communication port by REL52816 to REL52819 external fiber optic interface

Function
The temperature modules can be used to connect temperature sensors from the field to the Easergy P3 devices using a communication port RS485 by twist-pair or fiber optic. The temperature measurement is utilized by the following protection functions in transformer and motor application: � Thermal overload � Temperature monitoring � Customized logic or custom protection function
The modules REL52813 and REL52814 have analog input and output to use in the special controls functions.

DM105626

REL52811
Fiber Rx Tx
RTD CH01 RTD CH02 RTD CH03 RTD CH04 RTD CH05 RTD CH06 RTD CH07 RTD CH08 RTD CH09 RTD CH10 RTD CH11 RTD CH12
94 | Easergy P3 Catalog

REL52812
RS485 Rx Tx
RTD CH01 RTD CH02 RTD CH03 RTD CH04 RTD CH05 RTD CH06 RTD CH07 RTD CH08 RTD CH09 RTD CH10 RTD CH11 RTD CH12

REL52813 REL52814

RS485 Rx

Tx
Fiber Rx
Tx

PTC
RTD CH01

RTD CH02 mA In1
RTD CH03 mA In2
RTD CH04 mA In3
RTD CH05
mA In4 RTD CH06

RTD CH07 mA OUT1
RTD CH08 mA OUT2
RTD CH09 mA OUT3
RTD CH10 mA OUT4
RTD CH11

RTD CH12

schneider-electric.com

Additional modules and accessories

Temperature and analog input/output modules

Temperature input modules � REL52811 / REL52812 / REL52813 / REL52814

Characteristics Interface
Distance (maximum) Quantity of Temperature sensors
Supported RTD types Measuring range Measuring resolution Measuring accuracy Sensor distance Power Supply
Operating Temperature Mounting Type Degree of protection

REL52811

REL52812

REL52813

REL52814

Glass fiber (ST)

RS485 Twisted Pair

Glass fiber (ST) OR RS485,TP

2,000 m (78,740 in)

1,200 m* (47,244 in)

2 000 m / 1 200 m*

12 channels, 3-wire

12 channels, 3-wire and 1 PTC channel 2-wire

Pt100, Ni00, Ni120 and Cu10

1 - 400

0.10

�0.3

50 (corresponds to 2 000 m at 0.75 )

24 - 230 Vac/dc 50/60 Hz

24 Vdc

48 - 230 Vac/dc 50/60 Hz

0�C (32�F) to 55�C (131�F)

DIN Rail

IP20

* The value may decrease according to the conditions of use

Analog Input / Output modules � REL52811 / REL52812 / REL52813 / REL52814

Characteristics Analog Input (mA) Input Range Input accuracy Input resolution

REL52811 0 -

REL52812 0 -

REL52813 4
0-25 mA �1%
6uA (12-bits)

REL52814 4
0-25 mA �1%
6uA (12-bits)

Input impedance Analog Output (mA) Output range Output accuracy Output resolution Galvanic isolation Max. Load/output PTC Input Measuring accuracy

-

-

100

100

0

0

4

4

-

-

0-25 mA

0-25 mA

-

-

�1%

�1%

-

-

6uA (12-bits)

6uA (12-bits)

-

-

1000 V

1000 V

-

-

750

750

-

-

1

1

-

-

�10% (<10 k )

�10% (<10 k )

* The value may decrease according to the conditions of use

schneider-electric.com

Easergy P3 Catalog | 95

Additional modules and accessories

Arc flash sensors
For Easergy P3 Advanced only

Arc flash sensors

Sensors description
The sensor is used by an arc flash protection device (Easergy P3 Advanced) or system to detect the light coming from the arc flash incident. The Easergy P3 Advanced arc sensor is activated by strong light. The sensor transforms the light information into the current signal, which is used by the protection device to indicate arc flash.

REL52801 REL52802 REL52803 REL52804 REL52805 REL52806 REL52807 REL52808 REL52809 REL52810

Characteristics

Material

Plastic

Type

Standard

Weight

1,000 g 1,300 g 1,300 g 300 g 400 g 400 g 1,000 g

2.20 lb 2.87 lb 2.87 lb 0.66 lb 0.88 lb 0.88 lb 2.20 lb

Cable length (m)

6

20

20

6

6

6

20

Shielded cable

-

-

-

-

-

Halogen free

-

-

-

-

-

Environment

Pollution Degree 2

Operation temperature

-25�C (-13�F) to +70�C (+158�F)

Light spectrum sensitive area

400 � 1100 nm

Detection time

1 ms

Light sensitivity

8 000 � 10 000 lux

Loop supervision

Yes

To connect the interface in the Easergy P3 Standard devices, use REL52883 cable.

Pipe

1,300 g 300 g

2.87 lb 0.66 lb

20

6

-

-

-

400 g 0.88 lb
6
-

DM105632

REL52801 - 52806 dimensions

mm

22.2

in

0.83

14

0.55

20 0.79

10 0.39

46.4 1.83

Sensitivity area

REL52807 - 52810 dimensions

mm

11

in

0.43

62 2.44

25 0.98
8 0.31 4.2 0.17

DM105635

DM105636

96 | Easergy P3 Catalog

Arc Flash sensor: Pipe type

schneider-electric.com

Additional modules and accessories

Arc flash sensors
For Easergy P3 Advanced only

Direct mounting on switchgear
Setting the light sensor in the switchgear requires either special supports type REL52828 (mounting plate for sensor Z-shape) or REL52829 (mounting plate for sensor L-shape), or it can be mounted in customer drilled holes.

Mounting options

REL52829 dimensions

mm in

10

0.39

PM106972 DM105637

PM106971

15

59

15

0.59

2.32

0.59

DM105633

Before

3 0.12
30 1.18

30 1.18

Mounting plate for sensor L-shape

DM105634 DM105637

After

REL52828 dimensions

mm

50

in

15

1.97

0.59

51 25 2.0 0.98

59 2.32
42 1.65
7 0.28

2.5 0.1

10

0.39

15

50

0.59

1.97

Mounting plate for sensor Z-shape

schneider-electric.com

Easergy P3 Catalog | 97

Schneider Electric Service

98 | Easergy P3 Catalog

schneider-electric.com

Schneider Electric Service

Providing peace of mind throughout your installation life cycle

100

Endorsing the most eco-friendly products in the industry: Green PremiumTM

101

schneider-electric.com

Easergy P3 Catalog | 99

DM408843

Schneider Electric Service

Providing peace of mind throughout your installation life cycle

How can you cut costs and improve performance at the same time?
When it comes to your electrical distribution infrastructure, the answer is straight-forward - get professional expertise.

Plan
We help you plan the full design and execution of your solution, looking at securing your process and optimizing your time:
� Technical feasibility studies: Accompany you to design a solution in your given environment
� Preliminary design: Accelerate turnround time to come to a final solution design

Life Life cycle Cycle services Services
Plan
What are my options?
Install
How do I install and commission?
Operate
How do I operate and maintain?
Optimize
How do I optimize?

Install
We help you install efficient, reliable, and safe solutions based on your plans: � Project management:
Designed to help you complete your projects on time and within budget � Commissioning:
Ensure your actual performance versus design, through on-site testing and commissioning, tools, and procedures
Operate
We help you maximize your installation uptime and control your capital expenditures through our service offering: � Asset operation solutions � Advantage service plans � On-site maintenance services � Spare parts management � Technical training

Renew
How do I renew my solution?
When it comes to your electrical distribution installation, we can help you:
� Increase productivity, reliability, and safety � Mitigate risk and limit downtime � Keep equipment up to date and extend its
lifespan � Cut costs and increase savings � Improve your return on investment
CONTACT US! www.schneider-electric.com/ electricaldistributionservices

Optimize
We provide recommendations to improve your safety, availability, reliability, and quality: � MP4 electrical assessment:
Define your improvement and risk management program
Renew
We extend the life of your system while providing upgrades and offers to take full responsibility for the end-of-life processing of old electrical equipment: � Retrofit:
Keep up to date and improve the performance of your electrical installations (LV, MV, Protection Relays, etc.) � MV product end of life: Recycle and recover your outdated equipment with end-of-life services

100 | Easergy P3 Catalog

schneider-electric.com

Schneider Electric Service

Endorsing the most eco-friendly products in the industry

Green Premium is the only label that allows you to effectively develop and promote an environmental policy whilst preserving your business efficiency. This ecolabel guarantees compliance with the most up-to-date environmental regulations, but it does more than this.

Our Green Premium ecolabel is committed to offering transparency by disclosing extensive and reliable information related to the environmental impact of its products:
RoHS Our products are subject to RoHS requirements at a worldwide level, even for the many products that are not required to comply with the terms of the regulation. Compliance certificates are available for products that fulfill the criteria of this European initiative, which aims to eliminate hazardous substances.
REACh We apply the strict REACh regulation to our products at a worldwide level and disclose extensive information concerning the presence of SVHC (Substances of Very High Concern) in all of these products.
PEP: Product Environmental Profile Asumption data, for each of the lifecycle phases on all of our products, in compliance with the ISO 14025 PEP ecopassport program. PEP is especially useful for monitoring, controlling, saving energy, and/or reducing carbon emissions.
EoLI: End of Life Instructions Available at the click of a button, these instructions provide: � Recyclability rates for our products. � Guidance for mitigating personnel hazards during the dismantling of
your products and before recycling operations. � P arts identification for recycling or for selective treatment, to mitigate
environmental hazards/incompatibility with standard recycling processes.

Discover what we mean by green ....
Check your products!

75% Over

of

our manufactured products

have been awarded the

Green Premium ecolabel

schneider-electric.com

Easergy P3 Catalog | 101

Ordering

102 | Easergy P3 Catalog

schneider-electric.com

Ordering
Fast Ordering Code Easergy P3 Standard
Easergy P3U10 configuration Easergy P3U20 configuration Easergy P3U30 configuration
Easergy P3 Advanced
Easergy P3F30 configuration Easergy P3L30 configuration Easergy P3M30 configuration Easergy P3M32 configuration Easergy P3T32 configuration Easergy P3G30 configuration Easergy P3G32 configuration
Accessories

104
107
108 108 109
110
110 111 112 113 114 115 116
117

schneider-electric.com

Easergy P3 Catalog | 103

Ordering

Fast ordering code
Easergy P3 Standard

Easergy P3 Standard

Commercial Ref. Product Reference

REL52001 REL52002 REL52003 REL52004 REL52005 REL52006 REL52007 REL52008 REL52009 REL52010 REL52011 REL52012 REL52013 REL52014 REL52015 REL52016 REL52017 REL52018 REL52019 REL52020 REL52021 REL52022 REL52023 REL52024 REL52025 REL52026 REL52027 REL52028 REL52029 REL52030 REL52031 REL52032 REL52033

P3U30-5AAA3BCAA P3U30-5AAA3BBAA P3U30-5AAA1BCAA P3U30-5AAA2BCAA P3U30-5AAA1BBAA P3U30-5ABA1BBAA P3U30-5AAA1BDAA P3U30-6AAA2BCAA P3U30-5ABA1BCAA P3U30-5AAA2BDAA P3U20-5ABA1ACAA P3U30-5AAA2BBAA P3U20-5AAA1ACAA P3U30-5ABA1BDAA P3U20-6AAA2ACAA P3U30-6AAA2BBAA P3U30-6AAA3BCAA P3U20-5AAA2ACAA P3U30-5AAA1BFAA P3U30-6ABA1BBAA P3U30-6AAA2BDAA P3U30-6AAA1BCAA P3U20-6ABA1ADAA P3U20-5ABA1ADAA P3U30-5BAA2BCAA P3U10-5AAA1AAAA P3U10-6AAA1AAAA P3U10-5AAA2AAAA P3U10-6AAA2AAAA P3U10-5AAA3AAAA P3U10-6AAA3AAAA P3U20-5AAA1ABAA P3U20-5AAA1ADAA

Nominal Power Supply
Power A 48-230 V Power A 48-230 V Power A 48-230 V Power A 48-230 V Power A 48-230 V
Power B 24 V Power A 48-230 V Power A 48-230 V
Power B 24 V Power A 48-230 V
Power B 24 V Power A 48-230 V Power A 48-230 V
Power B 24 V Power A 48-230 V Power A 48-230 V Power A 48-230 V Power A 48-230 V Power A 48-230 V
Power B 24 V Power A 48-230 V Power A 48-230 V
Power B 24 V Power B 24 V Power A 48-230 V Power A 48-230 V Power A 48-230 V Power A 48-230 V Power A 48-230 V Power A 48-230 V Power A 48-230 V Power A 48-230 V Power A 48-230 V

Nominal Digital Input Voltage
220-230 Vac/dc 220-230 Vac/dc 24-230 Vac/dc 110-230 Vac/dc 24-230 Vac/dc 24-230 Vac/dc 24-230 Vac/dc 110-230 Vac/dc 24-230 Vac/dc 110-230 Vac/dc 24-230 Vac/dc 110-230 Vac/dc 24-230 Vac/dc 24-230 Vac/dc 110-230 Vac/dc 110-230 Vac/dc 220-230 Vac/dc 110-230 Vac/dc 24-230 Vac/dc 24-230 Vac/dc 110-230 Vac/dc 24-230 Vac/dc 24-230 Vac/dc 24-230 Vac/dc 110-230 Vac/dc 24-230 Vac/dc 24-230 Vac/dc 110-230 Vac/dc 110-230 Vac/dc 220-230 Vac/dc 220-230 Vac/dc 24-230 Vac/dc 24-230 Vac/dc

Voltage Nbr. Digital Input Input/Output

4

16 DI / 8 DO

4

16 DI / 8 DO

4

16 DI / 8 DO

4

16 DI / 8 DO

4

16 DI / 8 DO

4

16 DI / 8 DO

4

16 DI / 8 DO

4

16 DI / 8 DO

4

16 DI / 8 DO

4

16 DI / 8 DO

1

10 DI / 5 DO

4

16 DI / 8 DO

1

10 DI / 5 DO

4

16 DI / 8 DO

1

10 DI / 5 DO

4

16 DI / 8 DO

4

16 DI / 8 DO

1

10 DI / 5 DO

4

16 DI / 8 DO

4

16 DI / 8 DO

4

16 DI / 8 DO

4

16 DI / 8 DO

1

10 DI / 5 DO

1

10 DI / 5 DO

4

16 DI / 8 DO

1

2 DI / 5 DO

1

2 DI / 5 DO

1

2 DI / 5 DO

1

2 DI / 5 DO

1

2 DI / 5 DO

1

2 DI / 5 DO

1

10 DI / 5 DO

1

10 DI / 5 DO

Option
Screw connector Screw connector Screw connector Screw connector Screw connector Screw connector Screw connector Ring-lug connector Screw connector Screw connector Screw connector Screw connector Screw connector Screw connector Ring-lug connector Ring-lug connector Ring-lug connector Screw connector Screw connector Ring-lug connector Ring-lug connector Ring-lug connector Ring-lug connector Screw connector Screw connector Screw connector Ring-lug connector Screw connector Ring-lug connector Screw connector Ring-lug connector Screw connector Screw connector

Com. Port
2 x RJ45 RS485 2 x RJ45 2 x RJ45 RS485 RS485 2 x LC 2 x RJ45 2 x RJ45 2 x LC 2 x RJ45 RS485 2 x RJ45 2 x LC 2 x RJ45 RS485 2 x RJ45 2 x RJ45 LC + RS232 RS485 2 x LC 2 x RJ45 2 x LC 2 x LC 2 x RJ45 none none none none none none RS485 2 x LC

104 | Easergy P3 Catalog

schneider-electric.com

Ordering

Fast ordering code
Easergy P3 Standard

Easergy P3 Standard

Commercial Ref. Product Reference

REL52034 REL52035 REL52036 REL52037 REL52038 REL52039 REL52040 REL52041 REL52042 REL52043 REL52044 REL52045 REL52046 REL52047 REL52048 REL52049 REL52050 REL52051

P3U20-6AAA1ABAA P3U20-6AAA1ACAA P3U20-6AAA1ADAA P3U20-5AAA2ABAA P3U20-5AAA2ADAA P3U20-6AAA2ABAA P3U20-6AAA2ADAA P3U20-5AAA3ABAA P3U20-5AAA3ACAA P3U20-5AAA3ADAA P3U20-6AAA3ABAA P3U20-6AAA3ACAA P3U20-6AAA3ADAA P3U30-6AAA1BBAA P3U30-6AAA1BDAA P3U30-5AAA3BDAA P3U30-6AAA3BBAA P3U30-6AAA3BDAA

Nominal Power Supply
Power A 48-230 V Power A 48-230 V Power A 48-230 V Power A 48-230 V Power A 48-230 V Power A 48-230 V Power A 48-230 V Power A 48-230 V Power A 48-230 V Power A 48-230 V Power A 48-230 V Power A 48-230 V Power A 48-230 V Power A 48-230 V Power A 48-230 V Power A 48-230 V Power A 48-230 V Power A 48-230 V

Nominal Digital Input Voltage
24-230 Vac/dc 24-230 Vac/dc 24-230 Vac/dc 110-230 Vac/dc 110-230 Vac/dc 110-230 Vac/dc 110-230 Vac/dc 220-230 Vac/dc 220-230 Vac/dc 220-230 Vac/dc 220-230 Vac/dc 220-230 Vac/dc 220-230 Vac/dc 24-230 Vac/dc 24-230 Vac/dc 220-230 Vac/dc 220-230 Vac/dc 220-230 Vac/dc

Voltage Nbr. Digital Input Input/Output

1

10 DI / 5 DO

1

10 DI / 5 DO

1

10 DI / 5 DO

1

10 DI / 5 DO

1

10 DI / 5 DO

1

10 DI / 5 DO

1

10 DI / 5 DO

1

10 DI / 5 DO

1

10 DI / 5 DO

1

10 DI / 5 DO

1

10 DI / 5 DO

1

10 DI / 5 DO

1

10 DI / 5 DO

4

16 DI / 8 DO

4

16 DI / 8 DO

4

16 DI / 8 DO

4

16 DI / 8 DO

4

16 DI / 8 DO

Option
Ring-lug connector Ring-lug connector Ring-lug connector
Screw connector Screw connector Ring-lug connector Ring-lug connector Screw connector Screw connector Screw connector Ring-lug connector Ring-lug connector Ring-lug connector Ring-lug connector Ring-lug connector Screw connector Ring-lug connector Ring-lug connector

Com. Port
RS485 2 x RJ45
2 x LC RS485 2 x LC RS485 2 x LC RS485 2 x RJ45 2 x LC RS485 2 x RJ45 2 x LC RS485 2 x LC 2 x LC RS485 2 x LC

For more configuration or options, please use our web configurator or see:
page 107 for Easergy P3U10 page 108 for Easergy P3U20 page 109 for Easergy P3U30
Go to web configurator
schneider-electric.com

Easergy P3 Catalog | 105

Ordering

Fast ordering code
Easergy P3 Advanced

Easergy P3 Advanced

Commercial Ref.
REL52101 REL52102 REL52103 REL52104 REL52105 REL52106 REL52107 REL52108 REL52109 REL52110 REL52111 REL52112 REL52113 REL52114 REL52115 REL52116 REL52117 REL52118 REL52119 REL52120

Product Reference

Nominal Power Supply

P3F30-CGGGG-AAENA-BAAAA Power C 110-230 V

P3F30-CGGGI-AAENA-BBAAA Power C 110-230 V

P3F30-CGGGI-DAECA-BBAAA Power C 110-230 V

P3F30-CGGIA-AAEBA-BCAAA Power C 110-230 V

P3F30-CGGIA-AAECA-BAAAA Power C 110-230 V

P3F30-CGGIA-AAENA-BAAAA Power C 110-230 V

P3F30-CGGIA-AAEOA-BBAAA Power C 110-230 V

P3F30-CGGIA-DAENA-BAAAA Power C 110-230 V

P3F30-CGIAA-AAECA-BAAAA Power C 110-230 V

P3F30-CGIAA-AAEDA-BBAAA Power C 110-230 V

P3F30-CGIAA-DAENA-BAAAA Power C 110-230 V

P3F30-CGIIA-AAENA-BAAAA Power C 110-230 V

P3F30-DGGGG-AAENA-BAAAA Power D 24-48 V

P3F30-DGGGI-AAENA-BAAAA Power D 24-48 V

P3F30-DGGIA-AAECA-BAAAA Power D 24-48 V

P3F30-DGGIA-AAENA-BAAAA Power D 24-48 V

P3F30-DGGIA-DAENA-BAAAA Power D 24-48 V

P3F30-DGIAA-AAENA-BAAAA

Power D 24-48 V

P3F30-DGIAA-DAENA-BAAAA

Power D 24-48 V

P3F30-DGIIA-AAENA-BAAAA

Power D 24-48 V

Nominal Digital Input Voltage
24-230 Vac/dc 110-230 Vac/dc 110-230 Vac/dc 220-230 Vac/dc 24-230 Vac/dc 24-230 Vac/dc 110-230 Vac/dc 24-230 Vac/dc 24-230 Vac/dc 110-230 Vac/dc 24-230 Vac/dc 24-230 Vac/dc 24-230 Vac/dc 24-230 Vac/dc 24-230 Vac/dc 24-230 Vac/dc 24-230 Vac/dc 24-230 Vac/dc 24-230 Vac/dc 24-230 Vac/dc

Voltage Nbr. Digital Input Input/Output

4

24 DI / 21 DO

4

28 DI / 17 DO

4

28 DI / 17 DO

4

22 DI / 13 DO

4

22 DI / 13 DO

4

22 DI / 13 DO

4

22 DI / 13 DO

4

22 DI / 13 DO

4

16 DI / 9 DO

4

16 DI / 9 DO

4

16 DI / 9 DO

4

26 DI / 9 DO

4

24 DI / 21 DO

4

28 DI / 17 DO

4

22 DI / 13 DO

4

22 DI / 13 DO

4

22 DI / 13 DO

4

16 DI / 9 DO

4

16 DI / 9 DO

4

26 DI / 9 DO

Option

Com. Port

4 Arc sensors 4 Arc sensors 4 Arc sensors 4 Arc sensors 4 Arc sensors 4 Arc sensors 4 Arc sensors -

2 x RJ45 2 x RJ45 RS232 + RJ45 RS232 RS232 + RJ45 2 x RJ45
2 x LC 2 x RJ45 RS232 + RJ45 RS232 + LC 2 x RJ45 2 x RJ45 2 x RJ45 2 x RJ45 RS232 + RJ45 2 x RJ45 2 x RJ45 2 x RJ45 2 x RJ45 2 x RJ45

For more configuration or options,

please use our web configurator or see:

page 110 for Easergy P3F30

page 113 for Easergy P3M32

page 111 for Easergy P3L20

page 114 for Easergy P3T32

page 112 for Easergy P3M30

page 115 for Easergy P3G30

page 116 for Easergy P3G32

Go to web configurator

106 | Easergy P3 Catalog

schneider-electric.com

Ordering

Easergy P3 Standard
Easergy P3U10 configuration

U10
X1 X1 X2
A
X5 A X4 A
A A

Application

U10 Feeder & Motor, 4xI, 1xU. 2DI, 5DO

Phase currents & voltage input, X1

5

1 A / 5 A & 1U (100/110 V), pluggable clamp connector

6

1 A / 5 A & 1U (100/110 V), pluggable ring lug connector

Earth-fault current input

A 1A/5A

B 0,2 A / 1 A

Nominal power supply voltage [V]

A Power A 48 - 230 V (range: 40 ... 265 Vac/dc)

B Power B 24 V (range: 18 ... 36 Vdc)

Future option

A None

Digital input treshhold voltage (V)

1

24 Vac/dc

2

110 Vac/dc

3

220 Vac/dc

Voltage measurements + I/O, X5

A None

I/O with comms, X4

A None

Product version

A Version 2.1

Region

A International

1. Choose your option 2. Mark your choice in the box below

3. Check your order code:

Easergy P3 U10

Slot numbers

X1

X1

A
X2

AAAA
X5 X4

schneider-electric.com

Easergy P3 Catalog | 107

Ordering

Easergy P3 Standard
Easergy P3U20 configuration

U20
X1 X1 X2
A
X5 A
X4
A A

Application

U20 Feeder & Motor, 4xI, 1xU. 2DI, 5DO

Phase currents & voltage input, X1

5

1 A/ 5 A & 1U (100/110 V), pluggable clamp connector

6

1 A / 5 A & 1U (100/110 V), pluggable ring lug connector

Earth-fault current input, X1

A 1A/5A

B 0,2 A / 1 A

Nominal Supply Voltage [V], X2

A Power A 48 - 230 V (range: 40 ... 265 Vac/dc)

B Power B 24 V (range: 18 ... 36 Vdc)

Future option

A None

Digital input treshhold voltage (V)

1

24 Vac/dc

2

110 Vac/dc

3

220 Vac/dc

Voltage measurements + I/O, X5

A None

I/O with comms, X4

B RS-485 + 8DI

C 2 x RJ-45 + 8DI

D 2 x LC + 8DI

E

RJ + 232 + 8DI with IRIG-B

F

LC + 232 + 8DI with IRIG-B

Product version

A Version 2.1

Region

A International

1. Choose your option 2. Mark your choice in the box below

3. Check your order code::

Easergy P3 U20

Slot numbers

X1

X1

A
X2

A

AA

X5 X4

108 | Easergy P3 Catalog

schneider-electric.com

Ordering

Easergy P3 Standard
Easergy P3U30 configuration

U30
X1 X1 X2
A
X5 B
X4
A A

Application

U30 Feeder & Motor, 4xI, 4xU. 2DI, 5DO

Phase currents & voltage input, X1

5

1 A/ 5 A & 1U (100/110 V), pluggable clamp connector

6

1 A / 5 A & 1U (100/110 V), pluggable ring lug connector

Earth-fault current input, X1

A 1A/5A

B 0,2 A / 1 A

Nominal Supply Voltage [V], X2

A Power A 48 - 230 V (range: 40 ... 265 Vac/dc)

B Power B 24 V (range: 18 ... 36 Vdc)

Future option

A None

Digital input treshhold voltage (V)

1

24 Vac/dc

2

110 Vac/dc

3

220 Vac/dc

Voltage measurements + I/O, X5

B 3U (100 / 110 V) + 6DI + 3DO

I/O with comms

B RS-485 + 8DI

C 2 x RJ-45 + 8DI

D 2 x LC + 8DI

E

RJ + 232 + 8DI with IRIG-B

F

LC + 232 + 8DI with IRIG-B

Product version

A Version 2.1

Region

A International

1. Choose your option 2. Mark your choice in the box below

3. Check your order code:

Easergy P3 U30

Slot numbers

X1

X1

A
X2

B

AA

X5 X4

schneider-electric.com

Easergy P3 Catalog | 109

Ordering

Easergy P3 Advanced
Easergy P3F30 configuration

1. Choose your option 2. Mark your choice in the box below 3. Check your order code:

F30
1
2G
3
4
5
6
7A
8 9
10 A
A A A

Application

F30 Feeder protection relay

Nominal Supply Voltage [V]

C Power C 110 - 230 V (80 .. 265 Vac/dc, 5 x DO heavy duty, A1, SF)

D Power D 24 - 48 V (18 .. 60 Vdc, 5 x DO heavy duty, A1, SF)

I/O Card I

G 6DI+4DO (6 x DI, 4 x DO)

I/O Card II

A None

G 6DI+4DO (6 x DI, 4 x DO)

H 6DI+4DO (6 x DI, 4 x DO(NC))

I

10DI (10 x DI)

I/O Card III

A None

G 6DI+4DO (6 x DI, 4 x DO)

H 6DI+4DO (6 x DI, 4 x DO(NC))

I

10DI (10 x DI)

I/O Card IV

A None

G 6DI+4DO (6 x DI, 4 x DO)

H 6DI+4DO (6 x DI, 4 x DO(NC))

I

10DI (10 x DI)

Option card I

A None

D 4Arc (4 x Arc sensor)

K RS232 (RS232)

Future option

A None

Analog measurement card (See application)

E

3L(5 A)+4U+2Io (5/1 A+1/0,2 A)

F

3L(1A)+4U+2Io (5/1 A+1/0,2 A)

Communication interface I

A None

B RS232 (RS232, IRIG-B)

C RS232+RJ (RS232, IRIG-B + Ethernet RJ-45 100 Mbs)

D RS232+LC (RS232, IRIG-B + Ethernet LC 100 Mbs)

N 2xRJ (Ethernet RJ 100 Mbs, RSTP, PRP)

O 2xLC (Ethernet LC 100 Mbs, RSTP, PRP)

P

PP (Plastic / Plastic serial fibre)

R GG (Glass / Glass serial fibre)

Reserved

A

Display type

B 128x128 (128 x 128 LCD matrix)

C

128x128Ext (128 x 128 LCD matrix, detachable) (1

Digital input treshhold voltage (V)

A 24 Vdc/ac, with conformal coating

B 110 Vdc/ac, with conformal coating

C 220 Vdc/ac, with conformal coating

Product version

A Version 2.1

Future option

A None

Region

A International

(1 By default cable length is 2 m. In case other legth is needed order separately VX001-1, Vx001-3 or VX001-5 for 1 m, 3 m and 5 m respectively.

Easergy P3 F30

G

-

A

A-

AAA

Slot numbers

1

2

3

4

5-6

7

8

9 10

110 | Easergy P3 Catalog

schneider-electric.com

Ordering

Easergy P3 Advanced
Easergy P3L30 configuration

1. Choose your option 2. Mark your choice in the box below 3. Check your order code:

L30
1
2G
3
4
5
6
7A
8 9
10 A
A A A

Application

L30 Feeder protection relay with Line differential and distance protection

Nominal Supply Voltage [V]

C Power C 110 - 230 V (80 .. 265 Vac/dc, 5 x DO heavy duty, A1, SF)

D Power D 24 - 48 V (18 .. 60 Vdc, 5 x DO heavy duty, A1, SF)

I/O Card I

G 6DI+4DO (6 x DI, 4 x DO)

I/O Card II

A None

G 6DI+4DO (6 x DI, 4 x DO)

H 6DI+4DO (6 x DI, 4 x DO(NC))

I

10DI (10 x DI)

I/O Card III

A None

G 6DI+4DO (6 x DI, 4 x DO)

H 6DI+4DO (6 x DI, 4 x DO(NC))

I

10DI (10 x DI)

I/O Card IV

A None

G 6DI+4DO (6 x DI, 4 x DO)

H 6DI+4DO (6 x DI, 4 x DO(NC))

I

10DI (10 x DI)

Option card I

A None, Distance protection included

S

Line diff and distance FW with integrated optical diff comms. card

T

Line diff and distance FW with RS232 for external diff comms. converter

Future option

A None

Analog measurement card (See application)

E

3L(5 A)+4U+2Io (5/1 A+1/0,2 A)

F

3L(1A)+4U+2Io (5/1 A+1/0,2 A)

Communication interface I

A None

B RS232 (RS232, IRIG-B)

C RS232+RJ (RS232, IRIG-B + Ethernet RJ-45 100 Mbs)

D RS232+LC (RS232, IRIG-B + Ethernet LC 100 Mbs)

N 2xRJ (Ethernet RJ 100 Mbs, RSTP)

O 2xLC (Ethernet LC 100 Mbs, RSTP)

P

PP (Plastic / Plastic serial fibre)

R GG (Glass / Glass serial fibre)

Reserved

A

Display type

B 128x128 (128 x 128 LCD matrix)

C 128x128Ext (128 x 128 LCD matrix, detachable) (1

Digital input treshhold voltage (V)

A 24 Vdc/ac, with conformal coating

B 110 Vdc/ac, with conformal coating

C 220 Vdc/ac, with conformal coating

Product version

A Version 2.1

Future option

A None

Region

A International

(1 By default cable length is 2 m. In case other length is needed order separately VX001-1, VX001-3 or VX001-5 for 1 m, 3 m and 5 m respectively.

Easergy P3 L30

G

-

A

A-

AAA

Slot numbers

1

2

3

4

5-6

7

8

9 10

schneider-electric.com

Easergy P3 Catalog | 111

Ordering

Easergy P3 Advanced
Easergy P3M30 configuration

1. Choose your option 2. Mark your choice in the box below 3. Check your order code:

M30
1
2G
3
4
5
6
7A
8 9
10 A
A A A

Application

M30 Motor protection relay

Nominal Supply Voltage [V]

C Power C 110 - 230 V (80 .. 265 Vac/dc, 5 x DO heavy duty, A1, SF)

D Power D 24 - 48 V (18 .. 60 Vdc, 5 x DO heavy duty, A1, SF)

I/O Card I

G 6DI+4DO (6 x DI, 4 x DO)

I/O Card II

A None

G 6DI+4DO (6 x DI, 4 x DO)

H 6DI+4DO (6 x DI, 4 x DO(NC))

I

10DI (10 x DI)

I/O Card III

A None

G 6DI+4DO (6 x DI, 4 x DO)

H 6DI+4DO (6 x DI, 4 x DO(NC))

I

10DI (10 x DI)

I/O Card IV

A None

G 6DI+4DO (6 x DI, 4 x DO)

H 6DI+4DO (6 x DI, 4 x DO(NC))

I

10DI (10 x DI)

Option card I

A None

D 4Arc (4 x Arc sensor)

K RS232 (RS232)

Future option

A None

Analog measurement card (See application)

E

3L(5 A)+4U+2Io (5/1 A+1/0,2 A)

F

3L(1A)+4U+2Io (5/1 A+1/0,2 A)

Communication interface I

A None

B RS232 (RS232, IRIG-B)

C RS232+RJ (RS232, IRIG-B + Ethernet RJ-45 100 Mbs)

D RS232+LC (RS232, IRIG-B + Ethernet LC 100 Mbs)

N 2xRJ (Ethernet RJ 100 Mbs, RSTP)

O 2xLC (Ethernet LC 100 Mbs, RSTP)

P

PP (Plastic / Plastic serial fibre)

R GG (Glass / Glass serial fibre)

Reserved

A

Display type

B 128x128 (128 x 128 LCD matrix)

C

128x128Ext (128 x 128 LCD matrix, detachable) (1

Digital input treshhold voltage (V)

A 24 Vdc/ac, with conformal coating

B 110 Vdc/ac, with conformal coating

C 220 Vdc/ac, with conformal coating

Product version

A Version 2.1

Future option

A None

Region

A International

(1 By default cable length is 2 m. In case other length is needed order separately VX001-1, VX001-3 or VX001-5 for 1 m, 3 m and 5 m respectively.

Easergy P3 M30

G

-

A

A-

AAA

Slot numbers

1

2

3

4

5-6

7

8

9 10

112 | Easergy P3 Catalog

schneider-electric.com

Ordering

Easergy P3 Advanced
Easergy P3M32 configuration

M32
1
2G
3
4T 5A
6
7A
8 9
10 A
A A A

Application

M32 Motor protection relay with differential protection

Nominal Supply Voltage [V]

C Power C 110 - 230 V (80 .. 265 Vac/dc, 5 x DO heavy duty, A1, SF)

D Power D 24 - 48 V (18 .. 60 Vdc, 5 x DO heavy duty, A1, SF)

I/O Card I

G 6DI+4DO (6 x DI, 4 x DO)

I/O Card II

A None

G 6DI+4DO (6 x DI, 4 x DO)

H 6DI+4DO (6 x DI, 4 x DO(NC))

I

10DI (10 x DI)

I/O Card III

T

3xI (5/1A) + Io (5/1A) for motor differential protection

I/O Card IV

A None

Option card I

A None

D 4Arc (4 x Arc sensor)

K RS232 (RS232)

Future option

A None

Analog measurement card (See application)

E

3L(5 A)+4U+2Io (5/1 A+1/0,2 A)

F

3L(1A)+4U+2Io (5/1 A+1/0,2 A)

Communication interface I

A None

B RS232 (RS232, IRIG-B)

C RS232+RJ (RS232, IRIG-B + Ethernet RJ-45 100 Mbs)

D RS232+LC (RS232, IRIG-B + Ethernet LC 100 Mbs)

N 2xRJ (Ethernet RJ 100 Mbs, RSTP)

O 2xLC (Ethernet LC 100 Mbs, RSTP)

P

PP (Plastic / Plastic serial fibre)

R GG (Glass / Glass serial fibre)

Reserved

A

Display type

B 128x128 (128 x 128 LCD matrix)

C 128x128Ext (128 x 128 LCD matrix, detachable) (1

Digital input treshhold voltage (V)

A 24 Vdc/ac, with conformal coating

B 110 Vdc/ac, with conformal coating

C 220 Vdc/ac, with conformal coating

Product version

A Version 2.1

Future option

A None

Region

A International

(1 By default cable length is 2 m. In case other length is needed order separately VX001-1, VX001-3 or VX001-5 for 1 m, 3 m and 5 m respectively.

1. Choose your option

2. Mark your choice in the box below

3. Check your order code:

Easergy P3 M32

G

T A-

A

A-

Slot numbers

1

2

3

4

5-6

7

8

9 10

AAA

schneider-electric.com

Easergy P3 Catalog | 113

Ordering

Easergy P3 Advanced
Easergy P3T32 configuration

T32
1
2G
3
4T 5A
6
7A
8 9
10 A
A A A

Application

T32 Transformer protection relay with differential protection

Nominal Supply Voltage [V]

C Power C 110 - 230 V (80 .. 265 Vac/dc, 5 x DO heavy duty, A1, SF)

D Power D 24 - 48 V (18 .. 60 Vdc, 5 x DO heavy duty, A1, SF)

I/O Card I

G 6DI+4DO (6 x DI, 4 x DO)

I/O Card II

A None

G 6DI+4DO (6 x DI, 4 x DO)

H 6DI+4DO (6 x DI, 4 x DO(NC))

I

10DI (10 x DI)

I/O Card III

T

3xI (5/1A) + Io (5/1A) for transformer differential protection

I/O Card IV

A None

Option card I

A None

D 4Arc (4 x Arc sensor)

K RS232 (RS232)

Future option

A None

Analog measurement card (See application)

E

3L(5 A)+4U+2Io (5/1 A+1/0,2 A)

F

3L(1A)+4U+2Io (5/1 A+1/0,2 A)

Communication interface I

A None

B RS232 (RS232, IRIG-B)

C RS232+RJ (RS232, IRIG-B + Ethernet RJ-45 100 Mbs)

D RS232+LC (RS232, IRIG-B + Ethernet LC 100 Mbs)

N 2xRJ (Ethernet RJ 100 Mbs, RSTP)

O 2xLC (Ethernet LC 100 Mbs, RSTP)

P

PP (Plastic / Plastic serial fibre)

R GG (Glass / Glass serial fibre)

Reserved

A

Display type

B 128x128 (128 x 128 LCD matrix)

C 128x128Ext (128 x 128 LCD matrix, detachable) (1

Digital input treshhold voltage (V)

A 24 Vdc/ac, with conformal coating

B 110 Vdc/ac, with conformal coating

C 220 Vdc/ac, with conformal coating

Product version

A Version 2.1

Future option

A None

Region

A International

(1 By default cable length is 2 m. In case other length is needed order separately VX001-1, VX001-3 or VX001-5 for 1 m, 3 m and 5 m respectively.

1. Choose your option 2. Mark your choice in the box below

3. Check your order code:

Easergy P3 T32

G

T A-

A

A-

Slot numbers

1

2

3

4

5-6

7

8

9 10

AAA

114 | Easergy P3 Catalog

schneider-electric.com

Ordering

Easergy P3 Advanced
Easergy P3G30 configuration

1. Choose your option 2. Mark your choice in the box below 3. Check your order code:

G30
1
2G
3
4
5
6
7A
8 9
10 A
A A A

Application

G30 Generator protection

Nominal Supply Voltage [V]

C Power C 110 - 230 V (80 .. 265 Vac/dc, 5 x DO heavy duty, A1, SF)

D Power D 24 - 48 V (18 .. 60 Vdc, 5 x DO heavy duty, A1, SF)

I/O Card I

G 6DI+4DO (6 x DI, 4 x DO)

I/O Card II

A None

G 6DI+4DO (6 x DI, 4 x DO)

H 6DI+4DO (6 x DI, 4 x DO(NC))

I

10DI (10 x DI)

I/O Card III

A None

G 6DI+4DO (6 x DI, 4 x DO)

H 6DI+4DO (6 x DI, 4 x DO(NC))

I

10DI (10 x DI)

I/O Card IV

A None

G 6DI+4DO (6 x DI, 4 x DO)

H 6DI+4DO (6 x DI, 4 x DO(NC))

I

10DI (10 x DI)

Option card I

A None

D 4Arc (4 x Arc sensor)

K RS232 (RS232)

Future option

A None

Analog measurement card (See application)

E

3L(5 A)+4U+2Io (5/1 A+1/0,2 A)

F

3L(1A)+4U+2Io (5/1 A+1/0,2 A)

Communication interface I

A None

B RS232 (RS232, IRIG-B)

C RS232+RJ (RS232, IRIG-B + Ethernet RJ-45 100 Mbs)

D RS232+LC (RS232, IRIG-B + Ethernet LC 100 Mbs)

N 2xRJ (Ethernet RJ 100 Mbs, RSTP)

O 2xLC (Ethernet LC 100 Mbs, RSTP)

P

PP (Plastic / Plastic serial fibre)

R GG (Glass / Glass serial fibre)

Reserved

A

Display type

B 128x128 (128 x 128 LCD matrix)

C 128x128Ext (128 x 128 LCD matrix, detachable) (1

Digital input treshhold voltage (V)

A 24 Vdc/ac, with conformal coating

B 110 Vdc/ac, with conformal coating

C 220 Vdc/ac, with conformal coating

Product version

A Version 2.1

Future option

A None

Region

A International

(1 By default cable length is 2 m. In case other length is needed order separately VX001-1, VX001-3 or VX001-5 for 1 m, 3 m and 5 m respectively.

Easergy P3 G30

G

-

A

A-

AAA

Slot numbers

1

2

3

4

5-6

7

8

9 10

schneider-electric.com

Easergy P3 Catalog | 115

Ordering

Easergy P3 Advanced
Easergy P3G32 configuration

G32
1
2G
3
4T 5A
6
7A
8 9
10 A
A A A

Application

G32 Generator protection with differential protection

Nominal Supply Voltage [V]

C Power C 110 - 230 V (80 .. 265 Vac/dc, 5 x DO heavy duty, A1, SF)

D Power D 24 - 48 V (18 .. 60 Vdc, 5 x DO heavy duty, A1, SF)

I/O Card I

G 6DI+4DO (6 x DI, 4 x DO)

I/O Card II

A None

G 6DI+4DO (6 x DI, 4 x DO)

H 6DI+4DO (6 x DI, 4 x DO(NC))

I

10DI (10 x DI)

I/O Card III

T

3xI (5/1A) + Io (5/1A) for generator differential protection

I/O Card IV

A None

Option card I

A None

D 4Arc (4 x Arc sensor)

K RS232 (RS232)

Future option

A None

Analog measurement card (See application)

E

3L(5 A)+4U+2Io (5/1 A+1/0,2 A)

F

3L(1A)+4U+2Io (5/1 A+1/0,2 A)

Communication interface I

A None

B RS232 (RS232, IRIG-B)

C RS232+RJ (RS232, IRIG-B + Ethernet RJ-45 100 Mbs)

D RS232+LC (RS232, IRIG-B + Ethernet LC 100 Mbs)

N 2xRJ (Ethernet RJ 100 Mbs, RSTP)

O 2xLC (Ethernet LC 100 Mbs, RSTP)

P

PP (Plastic / Plastic serial fibre)

R GG (Glass / Glass serial fibre)

Reserved

A

Display type

B 128x128 (128 x 128 LCD matrix)

C 128x128Ext (128 x 128 LCD matrix, detachable) (1

Digital input treshhold voltage (V)

A 24 Vdc/ac, with conformal coating

B 110 Vdc/ac, with conformal coating

C 220 Vdc/ac, with conformal coating

Product version

A Version 2.1

Future option

A None

Region

A International

(1 By default cable length is 2 m. In case other length is needed order separately VX001-1, VX001-3 or VX001-5 for 1 m, 3 m and 5 m respectively.

1. Choose your option 2. Mark your choice in the box below

3. Check your order code:

Easergy P3 G32

G

T A-

A

A-

Slot numbers

1

2

3

4

5-6

7

8

9 10

AAA

116 | Easergy P3 Catalog

schneider-electric.com

Ordering

Accessories

Arc point sensors

Comm. Ref REL52801 REL52802 REL52803 REL52804 REL52805 REL52806 REL52807 REL52808 REL52809 REL52810

Description VA1DA-20 VA1DA-20S-HF VA1DA-20S VA1DA-6 VA1DA-6S-HF VA1DA-6S VA1EH-20 VA1EH-20S VA1EH-6 VA1EH-6S

RTD Modules

Comm. Ref REL52811 REL52812 REL52813 REL52814

Description VIO12AASE VIO12ABSE VIO12ACSE VIO12ADSE

Communication Port

Comm. Ref REL52815 REL52820 REL52821

Description VPA3CGSE VSE002 VSE009

Fiber optic modules

Reference REL52816 REL52817 REL52818 REL52819

Description VSE001-GGSE VSE001-GPSE VSE001-PGSE VSE001-PPSE

Others accessories

Reference REL52822 REL52828 REL52829 REL52831 REL52832 REL52823 REL52824 REL52834 REL52833 REL52825 REL52826 REL52827 REL52835

Description USB cable VYX001 VYX002 VYX301 VYX695 VX067 VX072 VYX860 P3UPSC VX082 VX083 VX084 VX085

Arc sensor, 20m Arc sensor, 20m, shielded, halogen free Arc sensor, 20m, shielded Arc sensor, 6m connect cable Arc sensor, 6m, halogen free Arc sensor, 6m, shielded Arc sensor, 20m pipe sensor Arc sensor, 20m pipe sensor, shielded Arc sensor, 6m pipe sensor Arc sensor, 6m pipe sensor, shielded
RTD module, 12pcs RTD inputs, Optical Tx RTD module, 12pcs RTD inputs, RS485 RTD module, 12pcs RTD inputs, mA in/out RTD module, 12pcs RTD inputs, mA in/out
Profibus interface module PM106585 RS485 module PM106581 DeviceNet module PM106580
Fiber optic module (Glass - Glass) PM106586 Fiber optic module (Glass - Plastic) PM106586 Fiber optic module (Plastic - Glass) PM106586 Fiber optic module (Plastic - Plastic) PM106586
USB programming cable (Easergy Pro) Mounting plate for arc sensor Z-shape Mounting plate for arc sensor L-shape VSE00x wall fastening module Raising frame, P3x, 45 mm Split cable for COM 1-2 & COM 3-4 ports Profibus cable Raising frame, P3U, 45 mm P3U panel seal cover RS232 - VSE (1xD9) cable RS232 - Remote/Ext. (3xD9) cable RS232 - VPA 3CG cable (Profibus) P3U (RS232) - VSE009 cable

Used on
P3F3x / P3M3x P3T3x / P3G3x
Used on P3Ux0 / P3F3x P3L3x / P3M3x P3T3x / P3G3x
Used on P3Ux0 / P3F3x P3L3x / P3M3x P3T3x / P3G3x
Used on P3Ux0 / P3F3x P3L3x / P3M3x P3T3x / P3G3x
Used on P3Ux0 / P3F3x P3L3x / P3M3x P3T3x / P3G3x
P3F3x P3L3x / P3M3x P3T3x / P3G3x
P3Ux0

schneider-electric.com

Easergy P3 Catalog | 117

Notes

118 | Easergy P3 Catalog

schneider-electric.com

Notes

schneider-electric.com

Easergy P3 Catalog | 119

Schneider Electric Industries SAS 35 rue Joseph Monier 92500 Rueil-Malmaison, France Tel : +33 (0)1 41 29 70 00 www.schneider-electric.com
NRJCAT17764EN_v14c �2018 Schneider Electric SE. All Rights Reserved. All Schneider Electric trademarks and service marks are the property of Schneider Electric SE, its subsidiaries and affiliated companies.