manufacturer supplied seismic installation instructions. This certification excludes all non-factory supplied accessories, including but not limited to mufflers, isolation/restraint devices, remote control panels, remote radiators, pumps and other electrical/mechanical components. VMA-51070-01C (Revision 06) Issue Date: July 03, 2015

IBC Seismic Certificate of Compliance - Electric Generators ...

Expiration Date: 01/31/2020. Certification Parameters: The nonstructural products (mechanical and/or electrical components) listed on this certificate are ...

certificate of compliance - Electric Generators Direct

2021-06-05 — The above referenced equipment is APPROVED for seismic application when properly installed3, used as intended, and contains a Seismic.

cummins-power-generation-0eb1f66374ad0549442cc49eceb9ba6e
CERTIFICATE OF COMPLIANCE
SEISMIC DESIGN OF NONSTRUCTURAL COMPONENTS AND SYSTEMS
Certification No.
VMA-51070-01C (Revision 06)
Expiration Date: 01/31/2020
Certification Parameters:
The nonstructural products (mechanical and/or electrical components) listed on this certificate are CERTIFIED1 FOR SEISMIC APPLICATIONS in accordance with the following building code2 releases.
IBC 2012, 2015
The following model designations, options, and accessories are included in this certification. Reference report number VMA-51070-01 as issued by The VMC Group for a complete list of certified models, included accessories/options, and certified installation methods.
Cummins Power Generation, Inc. Gas Generator Sets, C20-150N6 Series
The above referenced equipment is APPROVED for seismic application when properly installed3, used as intended, and contains a Seismic Certification Label referencing this Certificate of Compliance4. As limited by the tabulated values, below grade, grade, and roof-level installations, installations in essential facilities, for life safety applications, and/or of equipment containing hazardous contents are permitted and included in this certification with an Equipment Importance Factor assigned as IP=1.5. The equipment is qualified by successful seismic shake table testing at the nationally recognized Dynamic Certification Laboratories under the review of the ISO Accredited Product Certification Agency, The VMC Group.

Certified IBC
Test Datum AC156

Certified Seismic Design Levels

Importance IP  1.5 Soil Classes A-E
Risk Categories I-IV Design Categories A-F

SDS  2.500 g z/h = 0.0

Horizontal



De s ign5

ISO 17025 Laboratory Pre/Post-Shake Functionality Tri-axial, 5% Damping SRS

AFLEX-H  4.000 g ARIG-H  3.000 g ZPAH  2.700 g

Certified Seismic Installation Methods
Rigid mounting from unit base to rigid structure

SDS  2.500 g z/h  1.0
1.875 g
AFLEX-V  1.667 g ARIG-V  0.667 g ZPAV  0.600 g

102S-103387 Rev 9

Page 1 of 3

CERTIFICATE OF COMPLIANCE
SEISMIC DESIGN OF NONSTRUCTURAL COMPONENTS AND SYSTEMS

Certified Product Table:
Model
C20N6 C22N6 C25N6 C30N6H C30N6 C36N6H C36N6 C40N6H C40N6 C45N6H C45N6 C50N6H C50N6 C60N6H C60N6 C70N6 C80N6 C100N6 C125N6 C150N6

Max Rating [ kW ]
20 22 25 30 30 36 36 40 40 45 45 50 50 60 60 70 80 100 125 150

Depth 82 82 82 82 104 104 104 104 104 104 136 104 136 104 136 136 136 136 160 160

Max Dimensions [ in ] Width 34 34 34 34 34 34 34 34 34 34 40 34 40 34 40 40 40 40 40 40

Height 46 46 46 46 46 46 46 46 46 46 58 46 58 46 58 58 58 58 72 72

Max Weight [ lbs ]
1110 1150 1150 1120 1300 1270 1380 1420 1400 1420 2580 1420 2600 1540 2900 2870 3030 3170 3770 4350

Note: "H" indicates high speed (3600RPM, as opposed to the standard 1800RPM) Note: Dimensions and Weight include sound level 2 (SL2) enclosure baffle
This certification includes the open generator set and the enclosed generator set. The generator set and included options shall be a catalogue design and factory supplied. The generator set and applicable options shall be installed an attached to the building structure per the manufacturer supplied seismic installation instructions. This certification excludes all non-factory supplied accessories, including but not limited to mufflers, isolation/restraint devices, remote control panels, remote radiators, pumps and other electrical/mechanical components.

102S-103387 Rev 9

VMA-51070-01C (Revision 06) Issue Date: July 03, 2015
Revision Date: September 19, 2018 Expiration Date: January 31, 2020
Page 2 of 3

CERTIFICATE OF COMPLIANCE
SEISMIC DESIGN OF NONSTRUCTURAL COMPONENTS AND SYSTEMS
Notes and Comments:
1. All equipment listed herein successfully passed the seismic acceptance criteria for shake testing non-structural components and systems as set forth in the ICC
AC-156. The Test Response Spectrum (TRS) enveloped the Required Response Spectrum (RRS) for all units tested. The units cited in this certification were representative sample(s) of a contingent of models and all remained captive and structurally sound after the seismic shake simulation. The units also remained functionally operational after the simulation testing as functional testing was completed by the equipment manufacturer before and after the seismic simulations. Although a seismic qualified unit inherently contains some wind resisting capacity, that capacity is undetermined and is excluded from this certification. Snow/Ice loads have been neglected and thus limit the unit to be installed both indoors (covered by an independent protective structure) and out of doors (exposed to accumulating snow/ice) for ground snow loads no greater than 30 psf for all applications.
2. The following building codes are addressed under this certification:
IBC 2015 ­ referencing ASCE7-10 and ICC AC-156 IBC 2012 ­ referencing ASCE7-10 and ICC AC-156
3. Refer to the manufacturer supplied installation drawings for anchor requirements and mounting considerations for seismic applications. Required anchor
locations, size, style, and load capacities (tension and shear) may be specified on the installation drawings or specified by a 3rd party. Mounting requirement details such as anchor brand, type, embedment depth, edge spacing, anchor-to-anchor spacing, concrete strength, special inspection, wall design, and attachment to non-building structures must be outlined and approved by the Engineer of Record for the project or building. Structural walls, structural floors, and housekeeping pads must also be seismically designed and approved by the project or building Structural Engineer of Record to withstand the seismic anchor loads as defined on the installation drawings. The installing contractor is responsible for observing the installation detailed in the seismic installation drawings and the proper installation of all anchors and mounting hardware.
4. For this certificate and certification to remain valid, this certificate must correspond to the "Seismic Certification Label" found affixed to the unit by the factory.
The label ensures the manufacturer built the unit in conformance to the IBC seismic design criteria set forth by the Certified Seismic Qualification Agency, The VMC Group, and meets the seismic design levels claimed by this certificate.
5. Mechanical, Electrical, and Plumbing connections to the equipment must be flexibly attached as to not transfer load through the connection. The structural
integrity of any conduit, cable trays, piping, ductwork and/or flexible connections is the responsibility of others. This certification does not guarantee the equipment will remain compliant to NEMA, IP, UL, or CSA standards after a seismic event.
6. This certificate applies to units manufactured at:
Cummins Power Generation Inc., 1400 73rd Ave. NE, Minneapolis, MN 55432

VMA-51070-01C (Revision 06) Issue Date: July 03, 2015 Revision Date: September 19, 2018 Expiration Date: January 31, 2020
102S-103387 Rev 9

John P. Giuliano, PE President, The VMC Group
Page 3 of 3

