CENTERLINE 2100 Mtor Control Centers Selection Checklist

CENTERLINE, 2100, MCC, motor control centers, EtherNet/IP, DeviceNet, NEMA, IntelliCENTER, SecureConnect, ArcShield

Rockwell Automation

CENTERLINE 2100 Motor Control Centers

Original Instructions CENTERLINE 2100 Motor Control Centers Use this checklist to help you configure your CENTERLINE 2100 Motor Control Center. You can type in the fields that are provid ed and check the checkboxes to select your preferences. For further details on each step, see the CENTERLINE 2100 Motor Control Centers Sele ction Guide,

2100-sr003 -en-p
Selection Checklist
Original Instructions

CENTERLINE 2100 Motor Control Centers

Use this checklist to help you configure your CENTERLINE® 2100 Motor Control Center. You can type in the fields that are provided and check the checkboxes to select your preferences. For further details on each step, see the CENTERLINE 2100 Motor Control Centers Selection Guide, publication 2100-SG003. When you have completed the form, click Submit at the end of the document and send the form to your local solution consultant.

Customer: Prepared by:

User: Office:

Step 1: Review MCC Technical Specifications and Certifications

Certifications
 UL  CSA (c-UL)

 NEMA  Service entrance

 ICS Specification No. __________________________  Other ______________________________________

Step 2: Select Network Technology

Network Technology
IntelliCENTER® Technology (embedded network and preconfigured software)
IntelliCENTER Technology (embedded network only)

 Integrated EtherNet/IPTM network + preconfigured software
Stratix® 5700 switch mounting:  Unit-mounted switches
Ethernet cabling method:  Homerun (direct switch-to-device)  Integrated DeviceNet® network + preconfigured software  Integrated EtherNet/IP network
Stratix 5700 switch mounting:  Unit-mounted switches
Ethernet cabling method:  Homerun (direct switch-to-device)  Integrated DeviceNet network

 Horizontal wireway-mounted
switches
 Vertical wireway adapters
 Horizontal wireway-mounted
switches
 Vertical wireway adapters

CENTERLINE 2100 Motor Control Centers Selection Checklist

Step 3: Select Structure

Structure NEMA Type Depth
Options

 Type 1  Type 12  Type 4 (stainless steel only)  Front only  Back-to-back  Space heater with thermostat  9 in. vertical wireway  Master nameplate

ArcShieldTM

 Yes

 Type 1 with gasket

 Drip hood

 Type 3R non-walk-in

 Bottom plates

 12 in. pullbox

 Other __________________________

 15 in. (381 mm)

 20 in. (508 mm)

 30 in. (762 mm)

 40 in. (1016 mm)

 Corner section

 External mounting channels

 Special paint (describe) ________________________________________________

 Other_______________________________________________________________

 No

Step 4: Select Power Bus and Ground Bus System

Bus

Power Bus Bracing (amperes rms

 42 kA (std)

 65 kA

symmetrical)

 100 kA

 100 kA series coordinated

Material
Horizontal Power Plating Bus
Rating

 Aluminum (600 A and 800 A

only)

 Tin

 Silver (copper bus only)

 600 A

 800 A

 1200 A

 Copper  1600 A

Insulation (up to 1600 A only)

 Yes

 No

Vertical Power Bus

 300 A (600 A effective)

 600 A (1200 A effective)

Horizontal ground bus

 1/4 in. x 1 in. (6.25 x 25 mm)  1/4 in. x 2 in. (6.25 x 50 mm)

 Top mounted  Bottom mounted

Ground Bus

Vertical ground  Plug-in

bus

 Load

 Steel (standard) Copper

 Copper

Plating

 Unplated copper

 Tin-plated copper

 2000 A

 2500 A

 Top and bottom mounted

 3000 A

IMPORTANT: The vertical ground bus is unplated or tin-plated to match the horizontal ground bus.

 Full rated  All sections  Half rated  Main section only

 Main and adjacent ___ 1, ___ 2, ___ 3 sections

Neutral Bus

 Termination plate only, no bus (400 A and smaller mains only)

 Neutral loads  No

 Yes, Specify
___________________________________

 Number of loads_____

 Vertical neutral bus (requires horizontal neutral bus and 9 in. vertical wireway)

Rating:

 200 A

 300 A

 600 A

Neutral Load

In section:

Connection Options (select one)

 Neutral connection plate

 All sections  Sections _______________________________

In horizontal wireway:

 Top

 Bottom

In section:

 All sections  Sections _______________________________

Stab openings:  Manual shutters

 Automatic shutters

 Protective caps

Options

 Unit isolating barriers (nylon barriers in vertical wireway to unit openings)

 Other ______________________________________________________________________________________

2

Rockwell Automation Publication 2100-SR003J-EN-P - September 2020

Step 5: Select Unit Design

SecureConnect Technology

SecureConnectTM (Withdrawable power

 All units

stabs with door closed)

 Contactor starters only  Drives only

CENTERLINE 2100 Motor Control Centers Selection Checklist
 Soft starters only  Feeders only

Incoming Line Termination Main Lug (MLO) Main Circuit Breaker (MCB)
Main Fusible Disconnect (MFD)

Located in section No. __________

No. of cables per phase ________ Cable size ____________

 Lugs by others

 Mechanical lugs

 Top  Copper  Crimp compression lugs

 Bottom  Aluminum

Notes ______________________________________________________________________________________

Located in section No. __________

 Top

 Bottom

No. of cables per phase __________

Cable size ____________

Ampere rating, frame ________

Interrupting rating at 480V

 < 35 kA

 Internal ground fault protection

 Auxiliary contacts - Qty. _____ N.O. _____N.C.

Located in section No. __________

Ampere rating, trip __________

 35...65 kA

 > 65 kA

 Shunt-trip

 Other options _______________________________

 Top

 Bottom

No. of cables per phase __________

Cable size ____________

Ampere rating ________________ Fuse class ____________

Fuse rating ___________

 Auxiliary contacts - Qty. _____ N.O. _____N.C.

 Other options _______________________________

Fuses

 Factory supplied and installed  Supplied and installed by others

Combination Contactor/Starter Units

Wiring

NEMA wiring class  I

NEMA wiring type

 A

 IS  B-T

 II  B-D

 IIS

Contactor/Starter Types

 Full Voltage Lighting Contactor

 Full Voltage Non-Reversing

 Full Voltage Reversing

 Other ______________________________________________________________________________________

Disconnecting Means - Fuse clip class

Fusible

Fuses

 Class CC

 Class J

 Factory supplied and installed

 Class R

 Class H

 Supplied and installed by others

 Class L

Disconnecting Means -  Motor circuit protector (magnetic/instantaneous only)

 Circuit breaker (thermal-magnetic/inverse-time)

Circuit Breaker

Accessories ________________________________________________________________________________________________

 E100TM

 E300TM

Overload Relays Unit Nameplate

Communication type (E300 only)

 Ethernet

 DeviceNet

 None

N.O. alarm contact required

 Yes

 No

 None, screws only  Cardholder

 Engraved acrylic lamacoid

Colors:

 Black letters on white  White letters on black

 Other ______________

Rockwell Automation Publication 2100-SR003J-EN-P - September 2020

3

CENTERLINE 2100 Motor Control Centers Selection Checklist

Combination Contactor/Starter Units

 Separate control ____ Volts

 Common (line voltage) control

 Transformer control (120V AC)

 Control circuit transformer (fused primary and secondary) in each unit

 Standard VA

 Extra capacity VA

 Master control power transformer (fused secondary)

 Starter auxiliary contacts - Qty. _____ N.O. and N.C. pair

Starter Options

 Pilot devices

 Push buttons, describe function (such as start/stop)____________________________________  Selector switches, describe function (such as off-on, hand-off-auto)

__________________________________________________________________________________

 Pilot lights

 LED - Qty. ________, Colors _______________________________________________________  Push-to-Test

 Relays or timers, describe __________________________________________________________________________________

 Withdrawable power stabs with door closed (SecureConnect)

 Others, describe _________________________________________________________________________________________

Plug-in Metering Unit Metering Options

No. of current transformers required _______________

No. of potential transformers required ______________

 Ammeter  Voltmeter

 Ammeter switch  Voltmeter switch

 PowerMonitorTM 5000

Communication options:
 DeviceNet  EtherNet/IP

Unit options:
 Withdrawable power stabs with door
closed (SecureConnect)

Feeder Units Fused Switch
Circuit Breaker (thermal magnetic)

Fuse clip class

 Class CC

 Class J

 Class R

 Class H

 Class L

 Dual-mounted (30 A, 60 A, 100 A only)

 0.5 Space factor (30 A only, Class CC or J)

Fuse rating _______________

 Factory supplied and installed

 Supplied and Installed by others

 Withdrawable power stabs with door closed (SecureConnect)

Other options ______________________________________________________________________________________________

Interrupting rating ______

Ampere rating, frame ________

Ampere rating, trip __________

 Dual-mounted (125 A frame only,
100 A trip max)

 0.5 Space factor (125 A or 250 A frame only, 200 A trip max)

 Withdrawable power stabs with door closed (SecureConnect)

(not available on 0.5 SF, horizontal handle, or dual-mounted units)

Other Options __________________________________________________________________________________

4

Rockwell Automation Publication 2100-SR003J-EN-P - September 2020

CENTERLINE 2100 Motor Control Centers Selection Checklist

Other Unit / Apparatus
 Lighting Transformer
 Panelboard

Describe _______________________________________________________________________________________

Voltage ______________

Phase _______________

 Main lug

IC rating_____________

Wire ________________

 Main breaker

Quantity and pole configuration ___________________________________________________________________

 Soft Starters

 SMCTM-3

 Inverse Time Circuit Breakers

 SMCTM Flex

(fusing required)
 Fusible Disconnect

Describe _______________________________________________________________________________________

 Drives  Inverse Time Circuit Breakers
(fusing optional)
 Fusible Disconnect

 PowerFlex® 523  PowerFlex 525

 PowerFlex 70  PowerFlex 755

 PowerFlex 753

 Programmable Controllers

 ControlLogix®
No. of slots ______

 CompactLogixTM
Power supply _________

Describe _____________________________

 Separate source of 110/120V AC

 Fusible switch with control
transformer

 Circuit breaker with control
transformer

 Non-redundant

 Network Power Supply
(8 A, Class 1)

 Redundant (dual power modules  With or  Without intelligent I/O device (to monitor redundant power supply)

within a unit)

(DeviceNet only)

 Two-branch redundant power unit with the following 24V DC inputs (Ethernet only)

 Two Rockwell Automation power
supply units in MCC

 Two customer-supplied 24V DC
inputs

 One Rockwell Automation power
supply in MCC and one customer-supplied 24V DC input

 Network access port on unit door

 DeviceNet Bridge
(DeviceNet only)

 DeviceNet to ControlNet®  Separate source of 110/120V AC

 DeviceNet to Ethernet  Fusible switch with control transformer

 Withdrawable power stabs with door closed (SecureConnect)

 Other units, options, or modification Describe _______________________________________________________________________________________

 Extra space for future units

Describe _______________________________________________________________________________________

Comments / Additional Notes

Rockwell Automation Publication 2100-SR003J-EN-P - September 2020

5

Rockwell Automation Support

Use these resources to access support information.

Technical Support Center Knowledgebase Local Technical Support Phone Numbers Literature Library Product Compatibility and Download Center (PCDC)

Find help with how-to videos, FAQs, chat, user forums, and product notification updates. Access Knowledgebase articles. Locate the telephone number for your country. Find installation instructions, manuals, brochures, and technical data publications. Download firmware, associated files (such as AOP, EDS, and DTM), and access product release notes.

rok.auto/support rok.auto/knowledgebase rok.auto/phonesupport rok.auto/literature
rok.auto/pcdc

Documentation Feedback
Your comments help us serve your documentation needs better. If you have any suggestions on how to improve our content, complete the form at rok.auto/docfeedback.

To send for review, click Submit.

Submit
Clear Form

Allen-Bradley, ArcShield, CENTERLINE, CompactLogix, ControlLogix, expanding human possibility, FactoryTalk, IntelliCENTER, PowerFlex, Rockwell Automation, SecureConnect, SMC, and Stratix are trademarks of Rockwell Automation, Inc. ControlNet, DeviceNet, and EtherNet/IP is a trademark of ODVA, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies.
Rockwell Automation maintains current product environmental compliance information on its website at rok.auto/pec.
Rockwell Otomasyon Ticaret A.. Kar Plaza  Merkezi E Blok Kat:6 34752, çerenköy, stanbul, Tel: +90 (216) 5698400 EEE Yönetmeliine Uygundur

Publication 2100-SR003J-EN-P - September 2020