2 Siemens P1 DXR2.T18 A6V11524148 Building Technologies 2019-07-15 Features Proven, pre-loaded applications. Operational modes (Comfort, Standby, Economy, Protection, and so on).

download?A6V11524149
Desigo Room Automation
DXR2.T18
P1 DXR

Automation station which migrates P1 TEC controller technology to the latest Desigo DXR2 platform. Using existing P1 network wiring and panels, the device's firmware generates P1 TEC points for the configured template.
 P1 Protocol Communication  KNX PL-Link bus to connect sensors, actuators, and operator units  USB interface  Operating voltage AC 24V

A6V11524148 2019-07-15

Building Technologies

Features

 Proven, pre-loaded applications.  Operational modes (Comfort, Standby, Economy, Protection, and so on).

Preconfigured Applications Fan Coil Unit (FCU)  FAN COIL 2-Pipe CW/HW and HW Valves  FAN COIL 4-Pipe CW and HW Valves  FAN COIL staged Cooling and staged Heating  FAN COIL with CW and staged Electric Heat  FAN COIL­UNIT VENT with CW, HW and Outside Air Damper (OAD) control  FAN COIL­UNIT VENT with CW, ELEC and OAD control  FAN-COIL-UNIT VENT with DX, HW and OAD control  FAN COIL-UNIT VENT with DX, ELEC and OAD control Heat Pump  HP Variable Speed, Two Stage Elec Heat and One Stage Elec Rad with OAD  HP Variable Speed, Water Source, HW Heat and Modulating Elec Rad with OAD  HP Single Stage, One Stage Elec Heat and HW Rad with OAD  HP Multi Stage, Two Stage Elec Heat and HW Rad with OAD  HP Multi Stage, Hot Gas Reheat, One Stage Elec Heat and HW Rad with OAD  HP Multi Stage, Ground Source, Hot Gas Reheat, One Stage Elec Heat and HW Rad with OAD

Additional Applications  Chilled Beam: cooling only, cooling and heating (4-pipe) or cooling/heating (2-pipe)  Radiator/Baseboard: hot water, steam or electric stages

Pre-loaded Application Options  Demand Control Ventilation with separate flow setpoints for each operational mode.  Chilled beams and Radiator control.  Single, multiple or variable speed terminal fan control.  Optional terminal DX, chilled water, hot water or chilled/heated valve (2-pipe or 4-pipe).  Configurable operating modes (heating, cooling, warm up, cool down, flush/purge, and so on).

Functions

The selected application and its parameters, as well as input and output configuration, determine the room automation station's functionality.
Communication  RS 485 P1 Protocol  USB connection for service and commissioning, application and firmware download.  The following functions are available with the KNX PL-Link bus:
­ Communication with room operator units, sensors, actuators. ­ Plug-and-play connection of Siemens field devices with KNX PL-Link.

2 Siemens Building Technologies

P1 DXR2.T18

A6V11524148 2019-07-15

Type Summary
Product Number DXR2.T18-101B

SSN

Description

S55376-C124 DXR2.T18 Room Automation Station

Inputs 2 DI, 4 UI

Outputs
8 DO Triacs, 4 AO: 0 to 10 V

Accessories

Product Number 985-124

Designation 499 OHM Resistor Kit

Product Documentation
Topic Installation and mounting Global datasheet Setup and commissioning TEC Migration
Room Unit Datasheet

Title
P1 DXR Room Automation Station Installation Instructions
DXR2 24 V IP DXR2 24 V MS/TP
DXR2 VAV Start-up Procedures DXR2 FPB Start-up Procedures DXR2 FCU Start-up Procedures DXR2 Balancing Procedure
P1 DXR - TEC Variable Air Volume and Fan Powered Box Migration (PDF) P1 DXR - TEC Variable Air Volume and Fan Powered Box Migration (HTML Help) P1 DXR - TEC Fan Coil Unit Migration Guide (PDF) P1 DXR - TEC Fan Coil Unit Migration Guide (HTML Help) P1 DXR - TEC Heat Pump Migration Guide (PDF) P1 DXR - TEC Heat Pump Migration Guide (HTML Help)
Wall-mounted sensors and room operator units for KNX PL-Link, KNX S-mode and KNX LTE-Mode

Document ID: A6V11516808
N9205 N9207 A6V10665935 A6V10665938 A6V10665941 A6V10665943 A6V11504404
A6V11546425
A6V11504410
A6V11546427
A6V11504412
A6V11546428
A6V10394781

Technical Data
Dimensions Weight

7.09 in. (180 mm) x 4.11 in. (104.5 mm) x 2.34 in. (59.5 mm) approximately 3 lb (1.35 kg)

Power Data

Power Supply Operating voltage Frequency Class 2 Power Source

AC 24V -15%/+20% 50/60 Hz 4 A (96 VA) (maximum)

Siemens Building Technologies

P1 DXR2.T18

3 A6V11524148
2019-07-15

Apparent Power (VA) for Transformer Design

Base Model

Base Load

Max. Load Triac Output
AC 24V~ 0.25 A Each

DXR2.T18

6

8 x 6 = 48

Max. Load all Aux. Outputs
AC 24V~

Max. Load KNX PL-Link
(at 50 mA)

18

4

Max. Load DC 24V+ (2.4
W))
6

Max. Allowed Power
Consumption Including Connected
Field Devices
70

Power for the Triac outputs must be reduced if the max. load of 18 VA is required for AC 24 V field supply on the DXR2.x18.

NOTE: To calculate the total VA, add the Base Load + number of Triacs + field supplies+ KNX PL-Link. This cannot exceed the maximum power consumption. See Wiring Guidelines for Field Panels and Equipment Controllers (125-3002) for more information.

Inputs Outputs

Analog Inputs Resistance Sensor AI 1000  AI 2500  AI 10 K AI 100 K
1) Configurable default.

Temperature Measurement AI PT1K 375 AI PT1K 385 AI Ni1000 1) AI Ni1000 DIN AI NTC3K AI NTC10K 1) AI NTC100K 1)

Voltage Measurement AI 0 to 10V AI 0 to 10V (0 to 100%)

Digital Inputs Contact query voltage Contact query current Contact resistance for closed contacts Contact resistance for open contacts

DC 17 V typical 1.5 mA typical, 7 mA initial current Less than 100  Greater than 50 k

Analog Outputs 0 to 10V
Digital Outputs Type (Switching outputs triacs)
Switching voltage Permissible load Protection

1.5 mA maximum
High side The Triac closes the contact to AC 24V AC 24V 250 mA/6VA per output Short-circuit proof

4 Siemens Building Technologies

P1 DXR2.T18

A6V11524148 2019-07-15

DC 24V output for field devices (1: V+) Output voltage Permissible load Protection against overload

DC 24V 100 mA/2.4 W Short-circuit proof

Connections

Interfaces P1 Network

USB (2.0)

KNX PL-Link

Interface type: RS485 Galvanic isolation: Yes Baud rates: 4800 Protocol: P1 Protocol
Plug: Type B Galvanic isolation: No, use isolator for connection to grounded USB host, see Accessories [ 3] Data rate: 12 Mbps Full Speed USB 1.1 and USB 2.0 compatible
Type: KNX TP1 PL-Link, galvanic isolation Baud rate: 9600 bps Bus power: 50 mA Protection against faulty wiring at maximum AC 24V

Wiring Connections Pluggable screw terminals
Slotted screws Wiring lengths for signals

Copper wire or copper strands with ferrules 1 x 0.6 mm diameter to 2.5 mm2 (22 to 14 AWG) or 2 x 0.5 mm diameter to 1 mm2 (24 to 18 AWG) Copper strands without ferrules 1 x 0.6 mm diameter to 2.5 mm2 (22 to 14 AWG) or 2 x 0.5 mm diameter to 1.5 mm2 (24 to 16 AWG)
Small 1/8 inch blade, tightening torque 0.6 Nm (0.44 lb ft)
KNX PL-Link 80 m (263 ft) with internal bus power P1 3,280 ft 1,000 m Signal lines 263 ft (80 m)

KNX/PL-Link Network and Power Wiring 1)

Cable configuration

1 or 2 twisted pair  Pair 1 red/black  Pair 2 yellow/white

Gauge

20 AWG (solid bare copper)

Twists per foot

4 Minimum

Capacitance

30 pF/foot or less

Shields

100% foil with drain wire

UL type

300 Vrms, CMP (75 C or higher)

CSA type

300 Vrms, FT6 (75 C or higher)

1) Substitute 18 AWG STP CMP (Belden 6320FE 8771000).

Siemens Building Technologies

P1 DXR2.T18

5 A6V11524148
2019-07-15

Conformity

CAUTION
National safety regulations Failure to comply with national safety regulations may result in personal injury and property damage. Observe national provisions and comply with the appropriate safety regulations.

Ambient Conditions and Protection Classification Climatic ambient conditions  Transport and storage
 Operation

 Temperature -25°C...70°C (-13°F... 158°F) Air humidity 5 rh...95% rh
 Temperature -5°C...50°C (23°F... 122°F) Air humidity 5 rh...95% rh

Standards, directives and approvals UL Listing Suitable for plenum area installation Federal Communications Commission CSA Compliance and cUL certification Environmental compatibility - RoHS Compliant
ASHRAE 90.1 Supported Quality

UL916 UL1995 FCC CFR 47 Part 15 Class B C22.2 No. 205 The product environmental declaration contains data on environmentally compatible product design and assessments (composition, packaging, environmental benefit, disposal).
ISO 9001 (Quality)

6 Siemens Building Technologies

P1 DXR2.T18

A6V11524148 2019-07-15

Issued by Siemens Industry, Inc. Building Technologies Division 1000 Deerfield Pkwy Buffalo Grove IL 60089 Tel. +1 847-215-1000

Siemens Building Technologies
Document ID A6V11524148(AA)

Edition

2019-07-15

© Siemens Industry, Inc., 2019 Technical specifications and availability subject to change without notice.

P1 DXR2.T18

7 A6V11524148
2019-07-15 Datasheet


Microsoft Word for Office 365