Product Manual 9113 Temperature / mA Converter

To the extent the instructions in this manual are not strictly observed, the custom er cannot advance a demand against PR electronics A/S that would otherwise ...

PDF A700000006470365
Product Manual 9113 Temperature / mA Converter

PERFORMANCE MADE
SMARTER

CCOE
T E M P E R AT U R E | I . S . I N T E R FA C E S | CO M M U N I C AT I O N I N T E R FA C E S | M U LT I F U N C T I O N A L | I S O L AT I O N | D I S P L AY
No. 9113V107-UK Product version: 9113-004

6 Product Pillars to meet your every need
Individually outstanding, unrivalled in combination
With our innovative, patented technologies, we make signal conditioning smarter and simpler. Our portfolio is composed of six product areas, where we offer a wide range of analog and digital devices covering over a thousand applications in industrial and factory automation. All our products comply with or surpass the highest industry standards, ensuring reliability in even the harshest of environments and have a 5-year warranty for greater peace of mind.

Temperature I.S. Interface

Our range of temperature transmitters and sensors provides the highest level of signal integrity from the measurement point to your control system. You can convert industrial process temperature signals to analog, bus or digital communications using a highly reliable point-to-point solution with a fast response time, automatic selfcalibration, sensor error detection, low drift, and top EMC performance in any environment.
We deliver the safest signals by validating our products against the toughest safety standards. Through our commitment to innovation, we have made pioneering achievements in developing I.S. interfaces with SIL 2 Full Assessment that are both efficient and cost-effective. Our comprehensive range of analog and digital intrinsically safe isolation barriers offers multifunctional inputs and outputs, making PR an easy-to-implement site standard. Our backplanes further simplify large installations and provide seamless integration to standard DCS systems.

Communication

We provide inexpensive, easy-to-use, future-ready communication interfaces that can access your PR installed base of products. All the interfaces are detachable, have a built-in display for readout of process values and diagnostics, and can be configured via push-buttons. Product specific functionality includes communication via Modbus and Bluetooth and remote access using our PR Process Supervisor (PPS) application, available for iOS and Android.

Multifunction

Our unique range of single devices covering multiple applications is easily deployable as your site standard. Having one variant that applies to a broad range of applications can reduce your installation time and training, and greatly simplify spare parts management at your facilities. Our devices are designed for long-term signal accuracy, low power consumption, immunity to electrical noise and simple programming.

Isolation Display

Our compact, fast, high-quality 6 mm isolators are based on microprocessor technology to provide exceptional performance and EMC-immunity for dedicated applications at a very low total cost of ownership. They can be stacked both vertically and horizontally with no air gap separation between units required.
Our display range is characterized by its flexibility and stability. The devices meet nearly every demand for display readout of process signals, and have universal input and power supply capabilities. They provide a real-time measurement of your process value no matter the industry, and are engineered to provide a user-friendly and reliable relay of information, even in demanding environments.

Temperature / mA Converter
9113B
Table of contents
Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Symbol identification  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 How to demount system 9000  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Advanced features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Technical characteristics  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 PR 4511/4501 display / programming front  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Mounting / demounting the PR 4511/4501 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Order  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Accessories  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Electrical specifications  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Configuration of sensor error check  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Input signal outside range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Sensor error detection  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Error indications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Block diagram  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Signal error and cable fault indications without display front . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Configuration / operating the function keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Routing diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Routing diagram, advanced settings (ADV.SET) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Help text overview  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 IECEx Installation Drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 ATEX Installation Drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 FM Installation Drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Desenho de instalaçao INMETRO . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 Document history . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

9113 - Product version 9113-004

3

Warning
The following operations should only be carried out on a disconnected device and under ESD-safe conditions:
General mounting, wire connection and disconnection. Troubleshooting the device. Repair of the device and replacement of circuit breakers must be done by PR electronics A/S only.
Warning
Do not open the front plate of the device as this will cause damage to the connector for the display / programming front PR 4511/4501. This device contains no DIP-switches or jumpers.
Symbol identification
Triangle with an exclamation mark: Read the manual before installation and commissioning of the device in order to avoid incidents that could lead to personal injury or mechanical damage. Warning/ demand. Potentially lethal situations.
The CE mark proves the compliance of the device with the essential requirements of the directives.
The double insulation symbol shows that the device is protected by double or reinforced insulation.
Ex devices have been approved acc. to the ATEX directive for use in connection with installations in explosive areas. See installation drawings in appendix.

Safety instructions
Definitions Hazardous voltages have been defined as the ranges: 75 to 1500 Volt DC, and 50 to 1000 Volt AC. Technicians are qualified persons educated or trained to mount, operate, and also trouble-shoot technically correct and in accordance with safety regulations. Operators, being familiar with the contents of this manual, adjust and operate the knobs or potentiometers during normal operation.
Receipt and unpacking Unpack the device without damaging it and check whether the device type corresponds to the one ordered. The packing should always follow the device until this has been permanently mounted.
Environment Avoid direct sun light, dust, high temperatures, mechanical vibrations and shock, and rain and heavy moisture. If necessary, heating in excess of the stated limits for ambient temperatures should be avoided by way of ventilation. The device must be installed in pollution degree 2 or better. The device is designed to be safe at least under an altitude up to 2 000 m.

4

9113 - Product version 9113-004

Mounting Only technicians, who are familiar with the technical terms, warnings, and instructions in the manual and who are able to follow these, should connect the device. Should there be any doubt as to the correct handling of the device, please contact your local distributor or, alternatively,
PR electronics A/S www.prelectronics.com The use of stranded wires is not permitted for mains wiring except when wires are fitted with cable ends. Descriptions of input / output and supply connections are shown in the block diagram and on the side label. The device is provided with field wiring terminals and shall be supplied from a Power Supply having double / reinforced insulation. A power switch shall be easily accessible and close to the device. The power switch shall be marked as the disconnecting unit for the device. For installation on Power Rail 9400 the power is supplied by Power Control Unit 9410. Year of manufacture can be taken from the first two digits in the serial number. Calibration and Adjustment During calibration and adjustment, the measuring and connection of external voltages must be carried out according to the specifications of this manual. The technician must use tools and instruments that are safe to use. Normal operation Operators are only allowed to adjust and operate devices that are safely fixed in panels, etc., thus avoiding the danger of personal injury and damage. This means there is no electrical shock hazard, and the device is easily accessible. Cleaning When disconnected, the device may be cleaned with a cloth moistened with distilled water. Liability To the extent the instructions in this manual are not strictly observed, the customer cannot advance a demand against PR electronics A/S that would otherwise exist according to the concluded sales agreement.
How to demount system 9000
Picture 1: By lifting the bottom lock, the device is detached from the DIN rail.

9113 - Product version 9113-004

5

Temperature / mA Converter 9113B
· Input for RTD, TC and mA · Active / passive mA output via the same two terminals · 1 or 2 channels · Can be supplied separately or installed on power rail, PR type 9400 · SIL 2-certified via Full Assessment
Advanced features ·Configuration and monitoring by way of detachable display front (PR 4511/4501); process calibration and signal
simulation. · Copying of the configuration from one device to others of the same type via the display front. ·TC inputs can use either the internal CJC or a terminal with a built-in Pt100 sensor (PR 5910Ex, channel 1 / PR 5913Ex,
channel 2) for higher accuracy. · Advanced monitoring of internal communication and stored data. · SIL 2 functionality is optional and must be activated in a menu point. Application ·The device can be mounted in the safe area and in zone 2 / cl. 1 div. 2 and receive signals from zone 0, 1, 2 and zone 20,
21, 22 including M1 / Class I/II/III, Div. 1, Gr. A-G. · Conversion and scaling of temperature (Pt, Ni and TC) and active current signals. ·The 9113 has been designed, developed and certified for use in SIL 2 applications according to the requirements of IEC
61508. Technical characteristics · 1 green and 2 red front LEDs indicate operation status and malfunction. · 2.6 kVAC galvanic isolation between input, output and supply.

6

9113 - Product version 9113-004

Applications

Input signals:

Channel 1
Current

RTD

Connection,

wires

44

TC

+*

43

-

42

*Order separately: CJC connetor 5910Ex/5913Ex

41 Power rail

Output signals:

Analog, 0/4...20 mA

Channel 2

2-wire supply -

14 +

mA

mA

13

-

+

2-wire supply -

12 +

mA

mA

11

-

+

Channel 1

Error signal

Rail, supply + Rail, supply No connection

No connection

Channel 2
Current
TC
*

RTD Connection,
wires

*Order separately: CJC connetor 5910Ex/5913Ex
Zone 0, 1, 2, 20, 21, 22, M1 & Cl. I/II/III, Div. 1
gr. A-G

54 53 52 51
Same power rail as above

Power connection:
Supply -
31
Supply +19.2...31.2 VDC
32
Device status
33
N.C.
34
Device status

Zone 2 & Cl. 1, Div. 2, gr. A-D or Safe Area

9113 - Product version 9113-004

7

PR 4511/4501 display / programming front
Functionality The simple and easily understandable menu structure and the explanatory help texts guide you effortlessly and automatically through the configuration steps, thus making the product very easy to use. Functions and configuration options are described in the section "Configuration / operating the function keys".
Application · Communications interface for modification of operational parameters in 9113. ·Can be moved from one 9113 device to another and download the configuration of the first unit to
subsequent units. · When mounted in the process, the display shows process values and device status.
Technical characteristics · LCD display with 4 lines:
Line 1 (H=5.57 mm) shows input status Line 2 and 3 (H=3.33 mm) show analog input / output value or TAG no. and units. Line 4 shows status for communication and whether the device is SIL-locked. Static dot = SIL-locked and flashing dot = not SIL-locked. ·Programming access can be blocked by assigning a password. The password is saved in the device in order to ensure a high degree of protection against unauthorised modifications to the configuration.

Mounting / demounting the PR 4511/4501
1: Insert the tabs of the PR 4511/4501 into the holes at the top of the device. 2: Hinge the PR 4511/4501 down until it snaps into place.
Demounting of the PR 4511/4501 3: Push the release button on the bottom of the PR 4511/4501 and hinge the the PR 4511/4501 out and up. 4: With the PR 4511/4501 hinged up, remove from holes at the top of the device.
3

1

4

 2

OK

3

4501

4





8

9113 - Product version 9113-004

Order

Type

Channels

9113B Single

: A

Double

: B

Example: 9113BB

Accessories
4501 = Display / programming front 4511 = Communication enabler 5910Ex = CJC connector, channel 1 5913Ex = CJC connector, channel 2 9400 = Power rail 9404 = Module stop for rail 9410 = Power control unit 9421 = Power supply 24 V - Ex nA nC

Electrical specifications
Environmental conditions: Operating temperature  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . -20°C to +60°C Storage temperature  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  -20°C to +85°C Calibration temperature  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  20...28°C Relative humidity  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  < 95% RH (non-cond.) Protection degree  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . IP20 Installation in   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  Pollution degree 2 & overvoltage category II.
Mechanical specifications: Dimensions (HxWxD) .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  109 x 23.5 x 104 mm Dimensions (HxWxD) w/ 4501 / 4511  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 109 x 23.5 x 116 / 131 mm Weight approx.  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 250 g Weight incl. 4501 / 4511 (approx.)  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 265 g / 350 g DIN rail type  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  DIN EN 60715 - 35 mm Wire size   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  0.13...2.08 mm2 / AWG 26...14 stranded wire Screw terminal torque  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  0.5 Nm Vibration  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  IEC 60068-2-6
2...13.2 Hz  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  ±1 mm 13.2...100 Hz   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  ±0.7 g
Common electrical specifications: Supply voltage  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 19.2...31.2 VDC Fuse .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  400 mA SB / 250 VAC

9113 - Product version 9113-004

9

Type
9113xA 9113xB

Description
1 channel 2 channels

Max. power dissipation
 0.8 W
 1.4 W

Max. required power  0.8 W
 1.4 W

Max. required power is the maximum power needed at terminals 31 and 32. Max. power dissipation is the maximum power dissipated by the device. If the 9113 is used with the 4511 / 4501, then add 40 mW to the max. power dissipation and 70 mW to the max. required power for each device with the 4511 / 4501.

Isolation - test / working: Input to any  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  2.6 kVAC / 300 VAC reinforced isolation Analog output to supply  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 2.6 kVAC / 300 VAC reinforced isolation Status relay to supply   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  1.5 kVAC / 150 VAC reinforced isolation
Communications interface  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . Communication enabler 4511 / Programming front 4501
Signal dynamics, input / output  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 24 bit / 16 bit Signal / noise ratio   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  Min. 60 dB (0...100 kHz) Response time (0...90%, 100...10%):
Temperature input, programmable .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  1...60 s mA / V input, programmable  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 0.4...60 s Accuracy, the greater of the general and basic values:
General values

Input type All

Absolute accuracy  ±0.1% of span

Temperature coefficient  ±0.01% of span / °C

Input type
mA
Pt100, Pt200, Pt 1000
Pt500, Ni100, Ni120, Ni 1000 Pt50, Pt400, Ni50
Pt250, Pt300
Pt20
Pt10
TC type: E, J, K, L, N, T, U TC type: R, S, W3, W5, LR TC type: B 160...400°C TC type: B 400...1820°C

Basic values Basic accuracy
 ±16 A  ±0.2°C
 ±0.3°C  ±0.4°C  ±0.6°C  ±0.8°C  ±1.4°C
 ±1°C
 ±2°C
 ±4.5°C
 ±2°C

Temperature coefficient  ±1.6 A / °C  ±0.02°C/°C
 ±0.03°C/°C  ±0.04°C/°C  ±0.06°C/°C  ±0.08°C/°C  ±0.14°C/°C
 ±0.1°C/°C
 ±0.2°C/°C
 ±0.45°C/°C
 ±0.2°C/°C

10

9113 - Product version 9113-004

EMC - immunity influence  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  < ±0.5% of span Extended EMC immunity: NAMUR NE 21, A criterion, burst  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  < ±1% of span
RTD input:

Input type

Min. value

Max. value

Standard

Pt100 Ni100

-200°C -60°C

+850°C +250°C

IEC 60751 DIN 43760

Input for RTD types: Pt10*, Pt20*, Pt50*, Pt100, Pt200, Pt250, Pt300, Pt400, Pt500, Pt1000 Ni50, Ni100, Ni120, Ni1000
Cable resistance per wire (max.)  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  50  Sensor current  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . Nom. 0.2 mA Effect of sensor cable resistance (3- / 4-wire)  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  < 0.002  /  Sensor error detection  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  Programmable ON / OFF Sensor error current:
when detecting  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  < 2 A else  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  0 A * No short circuit detection for Pt10, Pt20 and Pt50

TC input:

Type

Min. value

Max. value

Standard

B

0°C

+1820°C

IEC 60584-1

E

-100°C

+1000°C

IEC 60584-1

J

-100°C

+1200°C

IEC 60584-1

K

-180°C

+1372°C

IEC 60584-1

L

-200°C

+900°C

DIN 43710

N

-180°C

+1300°C

IEC 60584-1

R

-50°C

+1760°C

IEC 60584-1

S

-50°C

+1760°C

IEC 60584-1

T

-200°C

+400°C

IEC 60584-1

U

-200°C

+600°C

DIN 43710

W3

0°C

+2300°C

ASTM E988-90

W5

0°C

+2300°C

ASTM E988-90

LR

-200°C

+800°C

GOST 3044-84

Cold junction compensation (CJC): via external sensor in connector 5910  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  20...28°C  ±1°C -20...20°C and 28...70°C  ±2°C via internal CJC sensor  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  ±(2.0°C + 0.4°C * t)
t = internal temperature - ambient temperature Sensor error detection  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  Programmable ON or OFF
(only wire breakage) Sensor error current:
when detecting  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  Nom. 2 A else  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  0 A
Current input: Measurement range  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 0...23 mA Programmable measurement ranges  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 0...20 and 4...20 mA Input resistance .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  Nom. 20  + PTC 50  Sensor error detection  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  Programmable ON / OFF
Only 4...20 mA (NAMUR)

Current output: Signal range (span)  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  0...23 mA Programmable signal ranges   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  0...20 / 4...20 / 20...0 and 20...4 mA Load .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .   600  Load stability  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  0.01% of span / 100 

9113 - Product version 9113-004

11

Sensor error detection  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  0 / 3.5 / 23 mA / none NAMUR NE 43 Upscale/Downscale  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  23 mA / 3.5 mA Output limitation:
on 4...20 and 20...4 mA signals .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  3.8...20.5 mA on 0...20 and 20...0 mA signals .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  0...20.5 mA Current limit  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .   28 mA
Passive 2-wire output installation: Max. external 2-wire supply  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 26 VDC Max. load resistance []  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  (Vsupply - 3.5) / 0.023 A Effect of external 2-wire supply voltage variation   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  < 0.005% of span / V
Status relay in safe area: Max. voltage  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  125 VAC / 110 VDC Max. current  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  0.5 AAC / 0.3 ADC Max. AC power  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 62.5 VA / 32 W
of span = of the currently selected measurement range
Observed authority requirements: EMC  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  2014/30/EU ATEX  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 2014/34/EU LVD   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  2014/35/EU RoHS  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 2011/65/EU
Approvals: DNV-GL, Ships & Offshore  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  Standard for Certification No. 2.4 ClassNK .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  TA18527M c UL us, Standard for Safety  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . UL 61010-1 EAC   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  TR-CU 020/2011
I.S. / Ex: ATEX  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . KEMA 07ATEX0148 X IECEx   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  IECEx KEM 09.0052X c FM us  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  3038279-C INMETRO  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  DEKRA 16.0003 X CCOE  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . P337349/3 EAC Ex TR-CU 012/2011   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  RU C-DK.GB08.V.00410
Functional Safety: SIL2 Certified & Fully Assessed acc. to IEC 61508

12

9113 - Product version 9113-004

Device: 9113

Configuration of sensor error check

Sensor error check: Configuration OUT.ERR=NONE.
Else:

Sensor error detection: OFF ON

Input CURR TEMP
Input All

Visualisation in the 4511/4501 of:

Input signal outside range

Outside range readout (IN.LO, IN.HI): If the valid range of the A/D converter or the polynomal is exceeded

Range

Readout

Limit

0...20 mA / 4...20 mA

IN.LO IN.HI

< -1.05 mA > 25.05 mA

TC / RTD

IN.LO IN.HI

< temperature range -2°C > temperature range +2°C

Display readout below min. / above max. (-1999, 9999):

Range

Readout

Limit

-1999

Display readout <-1999

All

9999

Display readout >9999

Input CURR
TEMP

Sensor error detection

Sensor error detection (SE.BR, SE.SH):

Range

Readout

Loop break (4...20 mA)

SE.BR

TC

SE.BR

RTD: 2-, 3- and 4-wire For Pt10, Pt20, Pt50, Pt100, Pt200, Ni50 and
Ni120

SE.BR SE.SH

RTD: 2-, 3- and 4-wire for Pt250, Pt300, Pt400, Pt500, Pt1000 and
Ni1000

SE.BR SE.SH

Limit
<= 3.6 mA; > = 20.75 mA
> 10 k...165 k
> 900...1000  (cable > 50 )
< app. 15  > 10...12 k (cable > 50 )
< app. 15 

9113 - Product version 9113-004

13

Error indications

Readout at hardware error

Error search

Readout

Cause

CJC sensor error - check device temperature

CJ.ER

Defect internal CJC sensor or CJC temperature out of allowed range**

CJC connector error - check CJC-connector block CJ.ER

Defect (or missing) CJC-connector or temperature out of allowed range**

Input error - check input connection and reset power

IN.ER

Signal levels on input beyond limits or connected to wrong terminals*

Output error - check output connections and reset power

AO.ER

Error in analog output current (SIL mode only)*

No communication

NO.CO

No communication with (4511/4501)

Flash memory error - check configuration
Invalid configuration type or version
Hardware error Hardware error Hardware error Hardware error Hardware error Hardware error Hardware error Hardware error Hardware error Hardware error Hardware error Hardware error Hardware error Hardware error Hardware error Hardware error Hardware error

FL.ER CO.ER
TY.ER
RA.ER IF.ER SW.ER AD.ER AO.SU CA.ER CM.ER II.ER RS.ER IC.ER M1.ER M2.ER MC.ER MF.ER MR.ER MS.ER MP.ER

FLASH error (configuration invalid)***
Configuration read from EEprom has invalid type or rev. no. RAM error*
Internal Flash error* SW monitor error* A/D converter error* Analog output supply error* Factory calibration error* Main CPU error* Initialisation check error*
Reset error* Input communication error*
Main CPU to Ch.1 error* Main CPU to Ch.2 error* Main CPU config. error* Main CPU Flash error*
Main CPU RAM error* Main CPU supply error* Main CPU ProgFlow error*

!

All error indications in the display flash once per second. The help text explains the error. If the error is a sensor error, the display backlight flashes as well - this is acknowledged (stopped) by pushing the 3 button.

* Error is acknowledged by resetting the device power.

** Error can be disregarded by selecting input type different than TC.

*** Error is acknowledged by stepping through the basic setup.

14

9113 - Product version 9113-004

Channel 1 Channel 2 Channel 1 Channel 2

Connections

Power rail connections
91 92 93 94 95

Supply and status relay
31 32 33 34
N.C.

Error signal Supply + Supply NC NC Supply Supply +

NC = no connection
RTD, 2-wire
41 42 43 44

Inputs:

RTD, 3- / 4-wire
41 42 43 44

TC, internal CJC sensor
41 42 43 44

*TC, CJC connector
41 42 43 44

RTD, 2-wire
51 52 53 54

RTD, 3- / 4-wire
51 52 53 54

+-
TC, internal CJC sensor
51 52 53 54

+-
*TC, CJC connector
51 52 53 54

Current
41 42 43 44

-

+

+-
Current
51 52 53 54

-

+

+-
* Order separately: CJC connector 5910Ex (ch. 1) / 5913Ex (ch. 2).

Current (Active output)
11 12 13 14
- mA +

Outputs:

2-wire transmitter (Passive output)
11 12 13 14

Current (Active output)
11 12 13 14

mA +

- mA +

2-wire transmitter (Passive output)
11 12 13 14
+ mA

Channel 1 Channel 2

9113 - Product version 9113-004

15


12 mA 100C

Current

Current

-

+

-

+

Block diagram
Power Rail connections

Supply + Supply -

NC* NC*

Device status, Green CPU
Ch. 1 status, Red

Ch. 2 status, Red

FLASH

RTD, conn. wires
432

TC
44

43
*
42

-

+

41

RTD, conn. wires
432

TC
54

Channel 1

-

53
*
52
51

Channel 2
9113

+

31 Supply 32 Supply +24 VDC 33
Status relay N.C.
34 Status relay N.C.

12 I+

mA

mA
11
Gnd.

14 I+

mA

mA
13
Gnd.
* NC = no connection

16

9113 - Product version 9113-004

Signal error and cable fault indications without display front

Condition
Device OK No supply Device defective

List of LED and error signal indications

Green LED

Ch. 1: Red LED

Ch. 2: Red LED

Status relay, N.C.

Flashing

OFF

OFF

Energized

OFF

OFF

OFF

De-energized

OFF

ON

ON

De-energized

Power rail signal status
Open Closed Closed

Ch. 1 defective (ch. 2 OK) Ch. 2 defective (ch. 1 OK)

Flashing

ON

Flashing

OFF

OFF

De-energized

ON

De-energized

Closed Closed

Channel 1, signal OK Ch. 1, wire short / break
Channel 2, signal OK Ch. 2, wire short / break

Flashing Flashing
Flashing Flashing

OFF Flashing
OFF OFF

OFF OFF
OFF Flashing

Energized De-energized
Energized De-energized

Open Closed (if activateded)
Open Closed (if activateded)

9113 - Product version 9113-004

17

Configuration / operating the function keys
Documentation for routing diagram.
In general When configuring the 9113, you will be guided through all parameters and you can choose the settings which fit the application. For each menu there is a scrolling help text which is automatically shown in line 3 on the display.
Configuration is carried out by use of the 3 function keys: 1 will increase the numerical value or choose the next parameter 2 will decrease the numerical value or choose the previous parameter 3 will save the chosen value and proceed to the next menu
When configuration is completed, the display will return to the default state 1.0. Pressing and holding 3 will return to the previous menu or return to the default state (1.0) without saving the changed values or parameters.
If no key is activated for 1 minute, the display will return to the default state (1.0) without saving the changed values or parameters.
Further explanations Password protection: Programming access can be blocked by assigning a password. The password is saved in the device in order to ensure a high degree of protection against unauthorised modifications to the configuration. Default password 2008 allows access to all configuration menus.
Selection of units By selection of temperature input you can choose which process units should be shown in the display (see table). The process value is always displayed in Celsius or Fahrenheit. This is selected in the menu point after selection of temperature input.
CJC In the CJC menu you can choose between CJC connector and internal cold junction compensation. The CJC connecter (PR 5910Ex/PR 5913Ex) must be ordered separately.
Signal and sensor error indication via display front 4511/4501 Sensor error (see limits in the table) is displayed as SE.BR (sensor break) or SE.SH (sensor short). Signals outside the selected range (not sensor error, see table for limits) are displayed as IN.LO indicating low input signal or IN.HI indicating high input signal. The error indication is displayed as text in line 2 for channel 1 and line 3 for channel 2 and at the same time the backlight flashes. Line 4 of the display is a status line which shows whether the device is SIL-locked (static dot = SIL-locked and flashing dot = not SIL-locked) as well as status for communication COM (running circle) indicating correct functioning of 4511/4501.
Signal and sensor error indication without display front Status of the unit can also be read from the 3 LEDs in the front of the device.
Green flashing LED indicates normal operation. No light in the green LED indicates lack of supply voltage or error in the device. Steady red LED indicates fatal error. Flashing red LED indicates sensor error.
Advanced functions The unit gives access to a number of advanced functions which can be reached by answering "Yes" to the point "ADV.SET".
Display setup: Here you can adjust the brightness contrast and the backlight. Setup of TAG numbers with 5 alphanumerics. Selection of functional readout in line 2 and 3 of the display - choose between readout of analog input, analog output or tag no or alternating display.
Two-point process calibration: The device can be process-calibrated in 2 points to fit a given input signal . A low input signal (not necessarily 0%) is applied and the actual value is entered. Then a high signal (not necessarily 100%) is applied and the actual value is entered. If you accept to use the calibration, the device will work according to this new adjustment. If you later reject this menu point or choose another type of input signal the device will return to factory calibration.

18

9113 - Product version 9113-004

Process simulation function: In the menu point "EN.SIM" it is possible to simulate an input signal by means of the arrow keys and thus control the output signal up or down. You must exit the menu by pressing 3 (no time-out). The simulation function exits automatically, if the 4511/4501 is detached.
Password: Here you can choose a password between 0000 and 9999 in order to protect the unit against unauthorised modifications to the configuration. The unit is delivered default without password.
Memory: In the memory menu you can save the configuration of the device in the 4511/4501, and then move the 4511/4501 onto another device of the same type and download the configuration in the new device.
Language: In the menu "LANG" you can choose between 7 different language versions of help texts that will appear in the menu. You can choose between UK, DE, FR, IT, ES, SE and DK.
Power rail: In the menu "RAIL" you can choose if sensor errors are transmitted to the central surveillance in the PR 9410 power control unit.
Safety Integrity Level (SIL): See Safety Manual for details.

9113 - Product version 9113-004

19

Routing diagram
If no key is activated for 1 minute, the display will return to the default state 1.0 without saving configuration changes. 1 Increase value / choose next parameter 2 Decrease value / choose previous parameter 3 Save the chosen value and proceed to the next menu Hold 3 Back to previous menu / return to menu 1.0 without saving.

Power up

If SIL-locked directly to [EN.SIL]

0000

NO

CURR

9999

YES

TEMP

 

12

12

12

12 mA
100 1
*1.0

3
0000 3
PASSW. Txt 1
*1.1

NO 3
ADV.SET Txt 2

CURR 3
CH1 TYPE Txt 3

4-20 0-20 12
4-20 3
I.RANGE Txt 4

20-4 20-0 4-20 0-20
12

23mA 0/3.5mA
NONE
12

4-20 3
O.RANGE Txt 12

23 3
OUT.ERR Txt 13
*1.2
@F @C
12

3 @C
UNIT Txt 11

TEMP 3
CH1 TYPE Txt 3

Pt Ni TC 12
Pt 3
SENSOR Txt 5

1000 10
12
100 3
Pt TYPE Txt 6

4W 3W 2W 12
3W 3
CONNEC. Txt 9

Ni 3
SENSOR Txt 5

1000 50
12
100 3
Ni TYPE Txt 7

4W 3W 2W 12
3W 3
CONNEC. Txt 9

NO YES 12
YES 3
ADV.SET Txt 2

TC.Lr TC.W5 TC.W3 TC.U TC.T TC.S TC.R TC.N TC.L TC.WK TC.J TC.E
12

TC 3
SENSOR Txt 5

TC.K 3
TC TYPE Txt 8

Continued on the page Routing diagram ADV.SET

CONN INT 12
INT 3
CJC Txt 36

*1.0 Default state. Line 1 shows input status Line 2 and 3 show analog input / output value or TAG no. and units. Line 4 shows status for communication and whether the device is SIL-locked. Static dot = SIL-locked and flashing dot = not SIL-locked.
*1.1 Only if password-protected.
20

*1.2 Not valid for 0...20 mA input signal. *1.3 Only if input signal is temperature.
Min. and max. acc. to selected sensor type *1.4 Only if the configuration is not protected by a password.
9113 - Product version 9113-004

Red text signifies safety parameters in a SIL configuration. See safety manual for details

999.9 -199.9
12
0.0 3
OUT.LO Txt 14
*1.3

999.9 -199.9
12
150.0 3
OUT.HI Txt 15
*1.3

0 60 12
0.0 3
RESP. Txt 35

Configuration of 3
CH2 identical to CH1

To default state 1.0

9113 - Product version 9113-004

21

Routing diagram, advanced settings (ADV.SET)

MEM, DISP, CAL, SIM, PASS, LANG, RAIL, SIL
12

SAVE LOAD
12

MEM 3 SAVE 3

SETUP

MEMORY

Txt 17

Txt 18

ALT

TAG

9

9

9

9

A.OUT

0

0

A

A

A.IN

12

12

12

12

12

DISP 3
SETUP Txt 17

33
CONTRA Txt 19

93
LIGHT Txt 20

TAG1 3
VALVE 5 Txt 21

TAG2 3
TEMP 4 Txt 21

A.OUT 3
DISP Txt 22

YES

9999

NO

0000

12

12

PASS 3
SETUP Txt 17

NO 3
EN.PASS Txt 23

0000 3
NEW.PAS Txt 24

NO
DE, DK, ES, FR, IT, SE, UK 12

LANG 3
SETUP Txt 17

UK 3
LANGUA Txt 25

CH.1

YES

-200

YES

-200

CH.2

NO

850

NO

850

12

12

12

12

12

CAL 3
SETUP Txt 17

CH.1 3
CAL Txt 26

NO 3
CAL.LO Txt 27

20.0 3
@C Txt 28

YES 3
CAL.HI Txt 29

100.0 3
@C Txt 30

YES NO
12

RAIL 3
SETUP Txt 17

YES 3
RAIL.ER Txt 16

SIM 3
SETUP Txt 17

CH.1 CH.2 12
CH.1 3
SIM Txt 32

-200 850 12
25.0 3
@C Txt 33

2.0 In the submenu simulation (SIM) you must press 3 to return to the default state 1.0.

YES

0000

LOCK

NO

9999

OPEN

12

12

12

SIL 3
SETUP Txt 17

NO 3 2008 3 LOCK 3 3 3

EN.SIL Txt 34

NEW.PAS Txt 24

CONFIG Txt 38

NO
*1.4

3
SIL.OK

22

9113 - Product version 9113-004

YES NO 12
YES 3
USE.CAL Txt 31

To default state 1.0

Help text overview

[01] Set correct password [02] Enter advanced setup menu? [03] Select temperature input
Select current input [04] Select 0-20 mA input range
Select 4-20 mA input range [05] Select TC sensor type
Select Ni sensor type Select Pt sensor type [06] Select Pt10 sensor type Select Pt20 sensor type Select Pt50 sensor type Select Pt100 sensor type Select Pt200 sensor type Select Pt250 sensor type Select Pt300 sensor type Select Pt400 sensor type Select Pt500 sensor type Select Pt1000 sensor type [07] Select Ni50 sensor type Select Ni100 sensor type Select Ni120 sensor type Select Ni1000 sensor type [08] Select TC-B sensor type Select TC-E sensor type Select TC-J sensor type Select TC-K sensor type Select TC-L sensor type Select TC-N sensor type Select TC-R sensor type Select TC-S sensor type Select TC-T sensor type Select TC-U sensor type Select TC-W3 sensor type Select TC-W5 sensor type Select TC-Lr sensor type [09] Select 2-wire sensor connection Select 3-wire sensor connection Select 4-wire sensor connection [11] Select Celsius as temperature unit Select Fahrenheit as temperature unit [12] Select 0-20 mA output range Select 4-20 mA output range Select 20-0 mA output range Select 20-4 mA output range [13] Select no error action - output undefined at error Select downscale at error Select NAMUR NE43 downscale at error Select NAMUR NE43 upscale at error

[14] Set temperature for analog output low [15] Set temperature for analog output high [16] Enable Rail status signal output? [17] Enter SIL setup
Enter simulation mode Enter RAIL setup Perform process calibration Enter language setup Enter password setup Enter display setup Perform memory operations [18] Load saved configuration into 9113 Save 9113 configuration in 4501 [19] Adjust LCD contrast [20] Adjust LCD backlight [21] Write a 5-character channel TAG [22] Show analog input value in display Show analog output value in display Show TAG in display Alternate shown information in display [23] Enable password protection? [24] Set new password [25] Select language [26] Select channel to calibrate [27] Calibrate input low to process value? [28] Set value for low calibration point [29] Calibrate input high to process value? [30] Set value for high calibration point [31] Use process calibration values? [32] Select channel to simulate [33] Set the input simulation value [34] Enable SIL configuration lock? 0-20 mA is not a valid output range for SIL operation [35] Set Analog output response time in seconds [36] Select internal temperature sensor Select CJC connector (accessory) [37] ...is channel using process-compensated calibration data? [38] Configuration SIL status (Open / Locked) [40] Sensor wire breakage [41] Sensor short circuit [42] Input underrange [43] Input overrange [44] Input error - check input connections and reset power [45] Output error - check connections and reset power [46] Flash memory error - check configuration [47] Invalid configuration type or version [48] Hardware error [49] CJC sensor error - check device temperature [50] CJC error - check CJC connector block [51] No communication

9113 - Product version 9113-004

23

Appendix
IECEx installation drawing ATEX Installation Drawing
FM Installation Drawing Desenho de Instalaçao INMETRO
Safety Manual

24

9113 - Product version 9113-004

LERBAKKEN 10, 8410 RØNDE DENMARK

9113QI01

IECEx Installation drawing
For safe installation of 9113 the following must be observed. The module shall only be installed by by qualified personnel who are familiar with the national and international laws, directives and standards that apply to this area. Year of manufacture can be taken from the first two digits in the serial number.

For Installation in Zone 2 the following must be observed. The 4501 programming module is to be used solely with PR electronics modules. It is important that the module is undamaged and has not been altered or modified in any way. Only 4501 modules free of dust and moisture shall be installed.

IECEx Certificate: Marking 9113Bx:
Marking 9113Ax

KEM 09.0052 X [Ex ia Ga] IIC/IIB/IIA Ex nA nC IIC T4 Gc [Ex ia Da] IIIC [Ex ia Ma] I II 3 G Ex nA nC IIC T4 Gc

Standards:

IEC60079-0:2011, IEC60079-11:2011, IEC60079-15:2010

Supply terminal (31,32)

Voltage :

19.2 ­ 31.2 VDC

Status Relay. terminal (33,34)

Voltage max: Power max: Current max:

125 VAC / 110 VDC 62,5 VA / 32 W 0.5 A AC / 0.3 ADC

Zone 2 Installation 32 VAC / 32 VDC 16 VA / 32 W 0.5 A AC / 1 ADC

Installation notes: Install in pollution degree 2, overvoltage category II as defined in IEC60664-1. Do not separate connectors when energized and an explosive gas mixture is present. Do not mount or remove modules from the Power Rail when an explosive gas mixture is present. Disconnect power before servicing. The wiring of unused terminals is not allowed. In type of protection [Ex ia Da] the parameters for intrinsic safety for gas group IIB are applicable. For installation in Zone 2, the module shall be installed in an enclosure in type of protection Ex n or Ex e, providing a degree of protection of at least IP54. Cable entry devices and blanking elements shall fulfill the same requirements. For installation on Power Rail in Zone 2, only Power Rail type 9400 supplied by Power Control Unit type 9410 (Type Examination Certificate IECEx KEM 08.0025X) is allowed.

Revision date: 2016-04-07

Version Revision: V5 R0

Prepared by: PB

Page: 1/4

9113 - Product version 9113-004

25

LERBAKKEN 10, 8410 RØNDE DENMARK

9113Bx Installation: Hazardous area Zone 0,1,2, 20, 21, 22

Non Hazardous area or Zone 2

9113QI01

-20 Ta  +60ºC
44 43 42 41

4501 34 33 32 31

54

14

53

13

52

12

51

11

9113 91 92 93 94 95

Ex input

CH1 (terminal 41,42,43,44)

CH2 (terminal 51,52,53,54)

Uo:

8.7 V

Io:

18.4 mA

Po:

40 mW

Lo/Ro

892 H/

Power Rail

IIC

IIB

IIA or I

Co.

5 F

50 F

1000 F

Lo.

100 mH 300 mH 700 mH

Ui:

10 V

Ii:

30 mA

Ci:

30 nF

Li.

820 nH

Revision date: 2016-04-07
26

Version Revision: V5 R0

Prepared by: PB

9113 - Product version 9113-004

Page: 2/4

LERBAKKEN 10, 8410 RØNDE DENMARK

9113Bx Installation: Hazardous area Zone 0,1,2, 20, 21, 22

Non Hazardous area or Zone 2 -20 Ta  +60ºC

4501

44

34

+

43

33

42 CH1

32

41

31

9113QI01

54

14

-

53 52

CH2

13 12

51

11

9113 91 92 93 94 95

Power Rail

Ex input

CH1 (terminal 43 +)

CH2 (terminal 52 - )

Uo:

17.4 V

Io:

18.4 mA

Po:

80 mW

Lo/Ro

445 H/

IIC

IIB

Co.

0.3 F

1.6 F

Lo.

80 mH 250 mH

Ui:

10 V

Ii:

30 mA

Ci:

15 nF

Li.

1.7 H

IIA 8 F 600 mH

Um: 253 V max. 400 Hz Supply / Output: (terminal 11,12,13,14) (terminal 31,32,33,34) (terminal 91,92,93,94,95)

Revision date: 2016-04-07

Version Revision: V5 R0

Prepared by: PB

9113 - Product version 9113-004

Page: 3/4
27

LERBAKKEN 10, 8410 RØNDE DENMARK

9113Ax Installation:

Non Hazardous area or Zone 2

-20  Ta  60ºC

9113QI01

4501

44

34

43

33

42

32

41

31

54 53 52 51
Supply: 19.2 ­ 31.2 VDC (terminal 31,32) (terminal 91,92,93,94,95) Input CH1 (terminal 41,42,43,44) CH2 (terminal 51,52,53,54)

14 13 12 11

9113 91 92 93 94 95

Power Rail

Output: (terminal 11,12,13,14)

Status Relay. terminal (33,34)

Voltage max: Power max: Current max:

125 VAC / 110 VDC 62,5 VA / 32 W 0.5 A AC / 0.3 ADC

Zone 2 Installation 32 VAC / 32 VDC 16V A / 32 W 0.5 A AC / 1 ADC

For installation in Zone 2, the module shall be installed in an enclosure in type of protection Ex n or Ex e, providing a degree of protection of at least IP54. Cable entry devices and blanking elements shall fulfill the same requirements.

For installation on Power Rail in Zone 2, only Power Rail type 9400 supplied by Power Control Unit type 9410 (Type Examination Certificate IECEx KEM 08.0025X) is allowed.

For Installation in Zone 2 the following must be observed. The 4501 programming module is to be used solely with PRelectronics modules. It is important that the module is undamaged and has not been altered or modified in any way. Only 4501 modules free of dust and moisture shall be installed.

Revision date: 2016-04-07

Version Revision: V5 R0

Prepared by: PB

Page: 4/4

28

9113 - Product version 9113-004

LERBAKKEN 10, 8410 RØNDE DENMARK
ATEX Installation drawing

9113QA01

For safe installation of 9113 the following must be observed. The module shall only be installed by qualified personnel who are familiar with the national and international laws, directives and standards that apply to this area. Year of manufacture can be taken from the first two digits in the serial number.

For Installation in Zone 2 the following must be observed. The 4501 programming module is to be used solely with PR electronics modules. It is important that the module is undamaged and has not been altered or modified in any way. Only 4501 modules free of dust and moisture shall be installed.

ATEX Certificate:

KEMA 07ATEX 0148 X

Marking 9113Bx: Marking 9113Ax

II (1) G [Ex ia Ga] IIC/IIB/IIA II 3 G Ex nA nC IIC T4 Gc II (1) D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I II 3 G Ex nA nC IIC T4 Gc

Standards

EN 60079-0 : 2012, EN 60079-11 : 2012, EN 60079-15 : 2010

Supply terminal (31,32)

Voltage :

19.2 ­ 31.2 VDC

Status Relay, terminal (33,34)

Voltage max: Power max: Current max:

125 VAC / 110 VDC 62.5 VA / 32 W 0.5 A AC / 0.3 ADC

Zone 2 Installation 32 VAC / 32 VDC 16 VA / 32 W 0.5 A AC / 1 ADC

Installation notes: Install in pollution degree 2, overvoltage category II as defined in EN60664-1.

Do not separate connectors when energized and an explosive gas mixture is present. Do not mount or remove modules from the Power Rail when an explosive gas mixture is present. Disconnect power before servicing. The wiring of unused terminals is not allowed.

In type of protection [Ex ia Da] the parameters for intrinsic safety for gas group IIB are applicable.

For installation in Zone 2, the module shall be installed in an enclosure in type of protection Ex n or Ex e, providing a degree of protection of at least IP54. Cable entry devices and blanking elements shall fulfill the same requirements.

For installation on Power Rail in Zone 2, only Power Rail type 9400 supplied by Power Control Unit type 9410 (Type Examination Certificate KEMA 07ATEX0152 X) is allowed.

Revision date: 2016-04-07

Version Revision: V5 R0

Prepared by: PB

Page: 1/4

9113 - Product version 9113-004

29

LERBAKKEN 10, 8410 RØNDE DENMARK
9113Bx Installation:

Hazardous area Zone 0,1,2, 20, 21, 22

Non Hazardous area or Zone 2 -20 Ta  +60ºC

4501

44

34

43

33

42

32

41

31

9113QA01

54

14

53

13

52

12

51

11

9113 91 92 93 94 95

Ex input

CH1 (terminal 41,42,43,44)

CH2 (terminal 51,52,53,54)

Uo:

8.7 V

Io:

18.4 mA

Po:

40 mW

Lo/Ro

892 H/

Power Rail

Um: 253 V max. 400 Hz Supply / Output: (terminal 11,12,13,14) (terminal 31,32,33,34) (terminal 91,92,93,94,95)

IIC

IIB

IIA or I

Co.

5 F

50 F 1000 F

Lo.

100 mH 300 mH 700 mH

Ui:

10 V

Ii:

30 mA

Ci:

30 nF

Li.

820 nH

Revision date: 2016-04-07

Version Revision: V5 R0

Prepared by: PB

Page: 2/4

30

9113 - Product version 9113-004

LERBAKKEN 10, 8410 RØNDE DENMARK
9113Bx Installation:

9113QA01

Hazardous area Zone 0,1,2, 20, 21, 22
+

Non Hazardous area or Zone 2 -20 Ta  +60ºC

44 43 42 CH1 41

4501 34 33 32 31

-

Ex input

CH1 (terminal 43)

CH2 (terminal 52)

Uo:

17.4 V

Io:

18.4 mA

Po:

80 mW

Lo/Ro

445 H/

IIC

IIB

Co.

0.3 F

1.6 F

Lo.

80 mH 250 mH

Ui:

10 V

Ii:

30 mA

Ci:

15 nF

Li.

1.7 H

54

14

53 52

CH2

13 12

51

11

9113 91 92 93 94 95

Power Rail

Um: 253 V max. 400 Hz

Supply / Output: (terminal 11,12,13,14) (terminal 31,32,33,34) (terminal 91,92,93,94,95)

IIA or I 8 F 600 mH

Revision date: 2016-04-07

Version Revision: V5 R0

Prepared by: PB

Page: 3/4

9113 - Product version 9113-004

31

LERBAKKEN 10, 8410 RØNDE DENMARK
9113Ax Installation:

Non Hazardous area or Zone 2

-20  Ta  60ºC

9113QA01

4501

44

34

43

33

42

32

41

31

54 53 52 51
Supply: 19.2 ­ 31.2 VDC (terminal 31,32) (terminal 91,92,93,94,95) Input CH1 (terminal 41,42,43,44) CH2 (terminal 51,52,53,54)

14 13 12 11

9113 91 92 93 94 95

Power Rail

Output: (terminal 11,12,13,14)

Status Relay, terminal (33,34)

Voltage max: Power max: Current max:

125 VAC / 110 VDC 62.5 VA / 32 W 0.5 A AC / 0.3 ADC

Zone 2 Installation 32 VAC / 32 VDC 16 VA / 32 W 0.5 A AC / 1 ADC

For installation in Zone 2, the module shall be installed in an enclosure in type of protection Ex n or Ex e, providing a degree of protection of at least IP54. Cable entry devices and blanking elements shall fulfill the same requirements.

For installation on Power Rail in Zone 2, only Power Rail type 9400 supplied by Power Control Unit type 9410 (Type Examination Certificate KEMA 07ATEX0152 X) is allowed.

For Installation in Zone 2 the following must be observed. The 4501 programming module is to be used solely with PRelectronics modules. It is important that the module is undamaged and has not been altered or modified in any way. Only 4501 modules free of dust and moisture shall be installed.

Revision date: 2016-04-07

Version Revision: V5 R0

Prepared by: PB

Page: 4/4

32

9113 - Product version 9113-004

LERBAKKEN 10, 8410 RØNDE DENMARK

9113QF01

FM Installation drawing
9113 For safe installation of 9113B the following must be observed. The module shall only be installed by qualified personnel who are familiar with the national and international laws, directives and standards that apply to this area. Year of manufacture can be taken from the first two digits in the serial number.

4501 For Installation in Zone 2 / Division 2 the following must be observed. The 4501 programming module is to be used solely with PRelectronics modules. It is important that the module is undamaged and has not been altered or modified in any way. Only 4501 modules free of dust and moisture shall be installed.

c-FM-us Certificate: ....................................................3038279

Hazardous Classified Location Class I/II/III, Division 1, Group A,B,C,D,E,F,G or Class I, Zone 0/1 Group IIC, [AEx ia] IIC or Class I, Zone 0/1 Group IIC, [Ex ia] IIC

Unclassified Location or Hazardous Classified Location Class I, Division 2, Group A,B,C,D T4 or Class I, Zone 2 Group IIC T4

Intrinsically safe apparatus entity parameters: Vmax (Ui)  Vt (Uo) Imax (Ii)  It (Io) Pi  Po Ca  Ccable + Ci La  Lcable + Li The sum of capacitance and inductance of cable and intrinsic safe equipment must be less or equal to Ca and La

-20  Ta  60ºC 44 43 42 41

4501 34 33 32 31

54

14

53

13

52

12

51

11

9113

9192 9394 95 Power Rail

(terminal 11,12,13,14) (terminal 31,32,33,34) (terminal 91,92,93,94,95) Um: 253 V, max 400 Hz

Revision date: 2012-06-07

Version Revision: V4 R0

Prepared by: PB

9113 - Product version 9113-004

Page: 1/3
33

LERBAKKEN 10, 8410 RØNDE DENMARK

Ex input

CH1 (terminal 41,42,43,44)

CH2 (terminal 51,52,53,54)

Vt (Uo):

8.7 V

It (Io):

18.4 mA

Po:

40 mW

Lo/Ro

892 H/

Ca / Co. La / Lo.
Ui: Ii: Ci: Li.

IIC / Group A,B 5 F 100 mH

IIB / Group C,E,F 50 F 300 mH

IIA / Group D,G 1000 F 700 mH

10 V 30 mA 30 nF 820 nH

9113QF01

Status Relay. terminal (33,34) Voltage max: Power max: Current max:

125 VAC / 110 VDC 62.5 VA / 32 W 0.5 A AC / 0.3 ADC

Zone 2 installation: Voltage max: Power max: Current max:

32 VAC / 32 VDC 16 VA / 32 W 0.5 A AC / 1 ADC

Installation notes: The installation and wiring shall be in accordance with the Canadian Electrical Code for Canada and National Electrical Code NFPA 70, Article 500 or 505 for installation in USA. The module must be supplied from a Power Supply having double or reinforced insulation. The use of stranded wires is not permitted for mains wiring except when wires are fitted with cable ends. For installation on the 9400 Power Rail the power must be supplied from Power Control Module Unit 9410. Install in pollution degree 2, overvoltage category II. The module must be installed in an enclosure suitable for the environment for which it is used. For installation in Zone 2 or Division 2, the module must be installed in a suitable outer enclosure according to the regulations in the CEC for Canada or NEC for USA. The module is galvanic isolated and does not require grounding. Use 60 / 75 ºC Copper Conductors with wire Size AWG: (26-14). Warning: Substitution of components may impair intrinsic safety. Warning: To prevent ignition of the explosive atmospheres, disconnect power before servicing and do not separate connectors when energized and an explosive gas mixture is present. Warning: Do not mount or remove modules from the Power Rail when an explosive gas mixture is present.

Revision date: 2012-06-07

Version Revision: V4 R0

Prepared by: PB

Page: 2/3

34

9113 - Product version 9113-004

LERBAKKEN 10, 8410 RØNDE DENMARK

9113QF01

Hazardous Classified Location Class I/II/III, Division 1, Group A,B,C,D,E,F,G or Class I, Zone 0/1 Group IIC, [AEx ia] IIC or Class I, Zone 0/1 Group IIC, [Ex ia] IIC

Unclassified Location or Hazardous Classified Location Class I, Division 2, Group A,B,C,D T4 or Class I, Zone 2 Group IIC T4

-20  Ta  60ºC

Intrinsically safe apparatus entity parameters:

Vmax (Ui)  Vt (Uo)

+

Imax (Ii)  It (Io)

Pi  Po

Ca  Ccable + Ci

La  Lcable + Li The sum of capacitance and

inductance of cable and

intrinsic safe equipment must

be less or equal to Ca and La

-

Ex input

CH1 (terminal 42,43)

CH2 (terminal 52,53)

Vt (Uo):

17.4 V

It (Io):

18.4 mA

Po:

80 mW

Lo/Ro

445 H/

Ca / Co. La / Lo.

IIC / Group A,B 0.3 F 80 mH

IIB / Group C,E,F 1.6 F 250 mH

IIA / Group D,G 8 F 600 mH

Ui:

10 V

Ii:

30 mA

Ci:

15 nF

Li.

1.7H

44 43 42 CH1 41

4501 34 33 32 31

54

14

53 52

CH2

13 12

51

11

9113 91 92 93 94 95

Power Rail

(terminal 11,12,13,14) (terminal 31,32,33,34) (terminal 91,92,93,94,95) Um: 253 V, max 400 Hz

Revision date: 2012-06-07

Version Revision: V4 R0

Prepared by: PB

9113 - Product version 9113-004

Page: 3/3
35

LERBAKKEN 10, 8410 RØNDE DENMARK

9113QB01

INMETRO Desenhos para Instalação
Para instalação segura do 9113B o manual seguinte deve ser observado. O módulo deve ser instalado somente por profissionais qualificados que estão familiarizados com as leis nacionais e internacionais, diretrizes e normas que se aplicam a esta área. Ano de fabricação pode ser obtido a partir dos dois primeiros dígitos do número de série.

4501 Para a instalação na Zona 2 o seguinte deve ser observado. O módulo de programação de 4501 deve ser utilizado apenas com os módulos PRelectronics. É importante que o módulo esteja intacto e não tenha sido alterado ou modificado de qualquer maneira. Apenas os módulos 4501 livres de poeira e umidade devem ser instalados.

INMETRO Certificado ............ DEKRA 16.0003X

Marcasão:
Normas: Instalação 9113Bx 2 Circuitos

[E[[[E[[EEEEEExxxxxxxxnniiiiiiaaaAaaaAMGDGMDnnaCaaCaaa]]]]]]IIIIIIIIIIIIIICCICICCC//TTIIII44BB/G/GIIIIAcAc ABNT NBR IEC 60079-0:2013, ABNT NBR IEC60079-11:2013, ABNT NBR IEC60079-15:2012.

Área de classificada Zona 0,1,2, 20, 21, 22

Área de nao classificada ou Zona 2 -20 Ta  +60ºC
4501

(terminais 11,12,13,14) (terminais 31,32,33,34) (terminais91,92,93,94,95) Um: 253 V, máx. 400 Hz

44

34

43

33

42

32

41

31

54

14

53

13

52

12

51

11

9113 91 92 93 94 95
TRILHO DE ENERGIA

Revision date: 2016-10-12
36

Version Revision: V5 R0

Prepared by: PB

9113 - Product version 9113-004

Page: 1/3

LERBAKKEN 10, 8410 RØNDE DENMARK

Entrada Ex

CN1 (terminais 41,42,43,44)

CN2 (terminais 51,52,53,54)

Uo:

8,7 V

Io:

18,4 mA

Po:

40 mW

Lo/Ro

892 H/

IIC

IIB

IIA

Co.

5 F

50 F

1000 F

Lo.

100 mH 300 mH 700 mH

Ui:

10 V

Ii:

30 mA

Ci:

30 nF

Li.

820 nH

I 1000 F 700 mH

9113QB01

Relê de estado, terminais (33,34)

Voltagem máx.: Potencia máx.: Corrente máx.:

125 VAC / 110 VDC 62,5 VA / 32 W 0,5 A AC / 0,3 ADC

Instalação Zone 2: Voltagem máx.: Potência máx.: Corrente máx.:

32 VAC / 32 VDC 16 VA / 32 W 0,5 A AC / 1 ADC

Notas de Instalação: Instalação em grau de poluição 2, categoria de sobretensão II conforme definido no IEC 60664-1. Os circuitos não intrinsecamente seguros só pode ser connectado para sobretensão limitado ao categoria I/II como definido na IEC 60664-1. Não separe conectores quando energizado ou quando uma mistura de gás explosivo estiver presente. Não monte ou remova módulos do trilho de alimentação quando uma mistura explosiva de gás estiver presente. Desligue a alimentação antes da manutenção. A fiação de terminais sem uso não é permitida. A fonte de Loop e terminais de entrada de corrente para o mesmo canal não deve ser aplicada ao mesmo tempo. Em tipo de proteção [Ex ia Da] os parâmetros para a segurança intrínseca para grupo de gás IIB são aplicáveis. Para a instalação em Zona 2, o módulo deve ser instalado em um invólucro conformidade com o tipo de proteção `Ex n' ou `Ex e', fornecendo no mínimo grau de proteçao IP54. Dispositivos de entrada de cabo e elementos de vedação devem cumprir com os mesmos requisitos.

Para a instalação de trilho de energia na Zona 2, apenas o trilho de alimentação Rail 9400 fornecido pela Unidade de Controle de Potência 9410 é permitido.

Revision date: 2016-10-12

Version Revision: V5 R0

Prepared by: PB

9113 - Product version 9113-004

Page: 2/3
37

LERBAKKEN 10, 8410 RØNDE DENMARK

9113QB01

Instalação 9113Bx 2 Circuitos combinado

Área de classificada Zona 0,1,2, 20, 21, 22

Área de nao classificada ou Zona 2

-20 Ta  +60ºC

4501

44

34

+

43

33

42 CH1

32

41

31

54

14

-

53 52

CH2

13 12

51

11

9113 91 92 93 94 95

TRILHO DE ENERGIA

Entrada EX

CN1 (terminais 43 +)

CN2 (terminais 52 -)

Uo:

17,4 V

Io:

18,4 mA

Po:

80 mW

Lo/Ro

445 H/

IIC

IIB

IIA

I

Co.

0,3 F 1,6 F 8 F

8 F

Lo.

80 mH 250 mH 600 mH 600 mH

Ui:

10 V

Ii:

30 mA

Ci:

15 nF

Li.

1,7 H

(terminais 11,12,13,14) (terminais 31,32,33,34) (terminais 91,92,93,94,95) Um: 253 V, máx. 400 Hz

Revision date: 2016-10-12
38

Version Revision: V5 R0

Prepared by: PB

9113 - Product version 9113-004

Page: 3/3

Document history

The following list provides notes concerning revisions of this document.

Rev. ID 107

Date 1722

Notes Specifications for max. required power added New ATEX, IECEX and INMETRO certificates and installation drawings

9113 - Product version 9113-004

39

We are near you, all over the world

Our trusted red boxes are supported wherever you are

All our devices are backed by expert service and a 5-year warranty. With each product you purchase, you receive personal technical support and guidance, day-to-day delivery, repair without charge within the warranty period and easily accessible documentation.
We are headquartered in Denmark, and have offices and authorized partners the world over. We are a local

business with a global reach. This means that we are always nearby and know your local markets well. We are committed to your satisfaction and provide PERFORMANCE MADE SMARTER all around the world.
For more information on our warranty program, or to meet with a sales representative in your region, visit prelectronics.com.

Benefit today from PERFORMANCE MADE SMARTER
PR electronics is the leading technology company specialized in making industrial process control safer, more reliable and more efficient. Since 1974, we have been dedicated to perfecting our core competence of innovating high precision technology with low power consumption. This dedication continues to set new standards for products communicating, monitoring and connecting our customers' process measurement points to their process control systems. Our innovative, patented technologies are derived from our extensive R&D facilities and from having a great understanding of our customers' needs and processes. We are guided by principles of simplicity, focus, courage and excellence, enabling some of the world's greatest companies to achieve PERFORMANCE MADE SMARTER.
www.prelectronics.com


Adobe PDF Library 15.0 Adobe InDesign CC 14.0 (Windows)