MITSUBISHI Cylinder unit EHPT20X-MHEDW User Manual
File info: application/pdf · 36 pages · 4.00MB
Cylinder unit - Library - Mitsubishi Electric
Safety Notices .................................................................................. 2. 2. Introduction .
Cylinder unit
Installation manual
Packaged Cylinder for Ecodan Monobloc - Easy Heat Pumps
Full PDF Document
If the inline viewer fails, it will open the original document in compatibility mode automatically. You can also open the file directly.
Extracted Text
Cylinder unit
EHPT20X-MHEDW
INSTALLATION MANUAL
FOR INSTALLER
English
Contents
For safe and correct use, read this manual and the outdoor unit installation manual thoroughly before installing the cylinder unit. English is the original language. The other language versions are translations of the original.
1. Safety Notices.................................................................................. 2 2. Introduction...................................................................................... 3 3. Technical Information ..................................................................... 4 4. Installation........................................................................................ 8
4.1 Location ....................................................................................... 8 4.2 Water Quality and System Preparation ........................................... 9 4.3 Water Pipe Work.......................................................................... 9 4.4 Safety Device Discharge Arrangements (G3)......................... 13 4.5 Electrical Connection ............................................................... 14 5. System Set Up ............................................................................... 16 5.1 DIP Switch Functions ............................................................... 16 5.2 Connecting inputs/outputs ...................................................... 17 5.3 Wiring for 2-zone temperature control ................................... 18 5.4 Indoor unit only operation (during installation work) ........... 19 5.5 Smart grid ready ....................................................................... 19 5.6 Using SD memory card ............................................................ 19 5.7 Main remote controller ............................................................. 20 en 6. Commissioning.............................................................................. 26 7. Service and Maintenance.............................................................. 27
http://www.mitsubishielectric.com/ldg/ibim/
If you want more information that is not written in this manual, go to the above website to download manuals, select model name, then choose language.
Contents of website manual � Energy monitor � Component parts (detail) � Water circuit diagram (170 L) � Room thermostat � Filling the system � Simple 2 zone system � Independent electrical power source � Smart grid ready � Remote controller options � Service menu (special setting) � Supplementary information
Accessories (Included) Adjustable feet
Immersion heater boss tool EHPT20X-MHEDW model only
SD memory card
Copper liner for DHW pipe
4
1
1
2
Abbreviations and glossary
No. Abbreviations/Word
1 Compensation curve mode 2 COP 3 Cylinder unit 4 DHW mode 5 Flow temperature 6 Freeze stat. function 7 FTC 8 Heating mode 9 Legionella 10 LP mode 11 Packaged model 12 PRV 13 Return temperature 14 Split model 15 TRV 16 Cooling mode
Description
Space heating incorporating outdoor ambient temperature compensation Coefficient of Performance the efficiency of the heat pump Indoor unvented DHW tank and component plumbing parts Domestic hot water heating mode for showers, sinks, etc Temperature at which water is delivered to the primary circuit Heating control routine to prevent water pipes freezing Flow temperature controller, the circuit board in charge of controlling the system Space heating through radiators or Underfloor heating Bacteria potentially found in plumbing, showers and water tanks that may cause Legionnaires disease Legionella prevention mode � a function on systems with water tanks to prevent the growth of legionella bacteria Plate heat exchanger (Refrigerant - Water) in the outdoor heat pump unit Pressure relief valve Temperature at which water is delivered from the primary circuit Plate heat exchanger (Refrigerant - Water) in the indoor unit Thermostatic radiator valve � a valve on the entrance or exit of the radiator panel to control the heat output Space cooling through fan-coils or underfloor cooling
1
1 Safety Notices
Please read the following safety precautions carefully.
WARNING: Precautions that must be observed to prevent injuries or death.
CAUTION: Precautions that must be observed to prevent damage to unit.
This installation manual along with the user manual should be left with the product after installation for future reference. Mitsubishi Electric is not responsible for the failure of locally-supplied parts.
� Be sure to perform periodical maintenance. � Be sure to follow your local regulations. � Be sure to follow the instructions provided in this manual.
MEANINGS OF SYMBOLS DISPLAYED ON THE UNIT
WARNING
(Risk of fire)
This mark is for R32 refrigerant only. Refrigerant type is written on nameplate of outdoor unit.
In case that refrigerant type is R32, this unit uses a flammable refrigerant. If refrigerant leaks and comes in contact with fire or heating part, it will create harmful gas and there is risk of fire.
Read the OPERATION MANUAL carefully before operation.
Service personnel are required to carefully read the OPERATION MANUAL and INSTALLATION MANUAL before operation.
Further information is available in the OPERATION MANUAL, INSTALLATION MANUAL, and the likes.
en
WARNING
Mechanical
The cylinder unit and outdoor unit must not be installed, disassembled, relocated, altered or repaired by the user. Ask an authorised installer or technician. If the unit is installed improperly or modified after installation, water leakage, electric shock or fire may result. The outdoor unit should be securely fixed to a hard level surface capable of bearing its weight. The cylinder unit should be positioned on a hard level surface capable of supporting its filled weight to prevent excessive sound or vibration. Do not position furniture or electrical appliances below the outdoor unit or cylinder unit. The discharge pipework from the emergency devices of the cylinder unit should be installed according to local law. Only use accessories and replacement parts authorised by Mitsubishi Electric ask a qualified technician to fit the parts.
Electrical
All electrical work should be performed by a qualified technician according to local regulations and the instructions given in this manual. The units must be powered by a dedicated power supply and the correct voltage and circuit breakers must be used. Wiring should be in accordance with national wiring regulations. Connections must be made securely and without tension on the terminals. Earth unit correctly.
General
Keep children and pets away from both the cylinder unit and outdoor unit. Do not use the hot water produced by the heat pump directly for drinking or cooking. This could cause illness to the user. Do not stand on the units. Do not touch switches with wet hands. Annual maintenance checks on both the cylinder unit and the outdoor unit should be conducted by a qualified person. Do not place containers with liquids on top of the cylinder unit. If they leak or spill onto the cylinder unit damage to the unit and/or fire could occur. Do not place any heavy items on top of the cylinder unit. When installing, relocating, or servicing the cylinder unit, use only the heat pump's specified refrigerant to charge the refrigerant lines. Do not mix it with any other refrigerant and do not allow air to remain in the lines. If air is mixed with the refrigerant, then it can be the cause of abnormal high pressure in the refrigerant line, and may result in an explosion and other hazards. The use of any refrigerant other than that specified for the system will cause mechanical failure or system malfunction or unit breakdown. In the worst case, this could lead to a serious impediment to securing product safety. In heating mode, to avoid the heat emitters being damaged by excessively hot water, set the target flow temperature to a minimum of 2�C below the maximum allowable temperature of all the heat emitters. For Zone2, set the target flow temperature to a minimum of 5�C below the maximum allowable flow temperature of all the heat emitters in Zone2 circuit. Do not install the unit where combustible gases may leak, be produced, flow, or accumulate. If combustible gas accumulates around the unit, fire or explosion may result. Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacturer. The appliance shall be stored in a room without continuously operating ignition sources (for example: open flames, an operating gas appliance or an operating electric heater). Do not pierce or burn. Be aware that refrigerants may not contain an odour. Pipe-work shall be protected from physical damage. The installation of pipe-work shall be kept to a minimum. Compliance with national gas regulations shall be observed. Keep any required ventilation openings clear of obstruction. Do not use low temperature solder alloy in case of brazing the refrigerant pipes.
2
1 Safety Notices
CAUTION
Use clean water that meets local quality standards on the primary circuit. The outdoor unit should be installed in an area with sufficient airflow according to the diagrams in the outdoor unit installation manual. The cylinder unit should be located inside to minimise heat loss. Water pipe-runs on the primary circuit between outdoor and indoor unit should be kept to a minimum to reduce heat loss. Ensure condensate from outdoor unit is piped away from the base to avoid puddles of water. Remove as much air as possible from the primary and DHW circuits. Refrigerant leakage may cause suffocation. Provide ventilation in accordance with EN378-1. Be sure to wrap insulation around the piping. Direct contact with the bare piping may result in burns or frostbite. Never put batteries in your mouth for any reason to avoid accidental ingestion. Battery ingestion may cause choking and/or poisoning. Do not transport the cylinder unit with water inside the DHW tank. This could cause damage to the unit. If power to the cylinder unit is to be turned off (or system switched off) for a long time, the water should be drained. If unused for a long period, before operation is resumed, DHW tank should be flushed through with potable water. Preventative measures should be taken against water hammer, such as installing a Water Hammer Arrestor on the primary water circuit, as directed by the manufacturer. As for the handling of refrigerant, refer to the outdoor unit installation manual.
en
2 Introduction
The purpose of this installation manual is to instruct competent persons how to safely and efficiently install and commission the cylinder unit system. The target readers of this manual are competent plumbers and/or refrigeration engineers
who have attended and passed the requisite Mitsubishi Electric product training and have appropriate qualifications for installation of an unvented hot water cylinder unit specific to their country.
3
3 Technical Information
Product specification
Model name
EHPT20X-MHEDW
Nominal domestic hot water volume
200 L
Overall unit dimensions (Height � Width � Depth)
1600 � 595 � 680 mm
Weight (empty)
94 kg
Weight (full)
300 kg
Water volume of heating circuit in the unit *1
3.7 L
Unvented expansion ves- Nominal volume
--
sel (Primary heating)
Charge pressure
--
Primary circuit
Control thermistor Pressure relief valve Flow sensor
80�C 0.3 MPa (3bar) Min. flow 5.0 L/min (See table 4.3.1 about water flow rate range)
Safety device
Booster heater
BH manual reset thermostat BH thermal Cut Off Control thermistor
-- -- 75�C
DHW tank Connections
IH manual reset thermostat
Temperature/ Pressure relief valve
Water
Primary circuit) DHW circuit
Refrigerant (R32/ R410A)
Liquid Gas
--
90�C / 0.7 MPa (7 bar)
�28 mm
en
�22 mm
--
--
Operating range
Heating Cooling
Room temperature Flow temperature Room temperature Flow temperature
10 - 30�C 20 - 60�C
-- --
Guaranteed operating range *2
Ambient
Outdoor temperature
Heating Cooling
0 - 35�C ( 80 %RH) See outdoor unit spec table.
--
Maximum allowable hot water temperature
70�C
Declared load profile
L
DHW tank performance
Average climate
Water heater energy efficiency class
A+
Time to reheat 70% of DHW tank to 65�C *4
24.8 min
Time to raise DHW tank temp. 15 - 65�C *4
29.5 min
Control board (Including 4 pumps)
Power supply (Phase, voltage, frequency)
Input
Current
~/N, 230 V, 50 Hz
0.30 kW 1.95 A
Breaker
10 A
Power supply (Phase, voltage, frequency)
--
Electrical data
Booster heater
Capacity
--
Current
--
Breaker
--
Immersion heater *3
Power supply (Phase, voltage, frequency)
Capacity
Current
~/N, 230 V, 50 Hz
3 kW 13 A
Breaker
16 A
Sound power level (PWL)
40 dB(A)
<Table 3.1>
*1 Volume of sanitary water circuit, primary DHW circuit (from 3-way valve to confluent point with heating circuit), piping to expansion vessel, and expansion vessel are not included in this value.
*2 The environment must be frost-free. *3 Do not fit immersion heaters without thermal cut-out. Use only Mitsubishi Electric service parts as a direct replacement. *4 Tested under BS7206 conditions.
4
3 Technical Information
Technical Drawings <EHPT20X-MHEDW> (Packaged model system)
en
HANDLE
680
100�20
D
C 0 67.8
F 442.3 542.3
E
552.7 546.8 412.1 242.7 182.7 0
0
A B
515.7 J
226.7 181.7 136.7
91.7 46.7
0
AIR VENT 595
MANOMETER
TEMPERATURE &
PRESSURE
MAIN
RELIEF VALVE
CONTROLLER
TERMINAL BLOCK
CPF 15mm
1600 456 120�20
FRONT PANEL
<Unit: mm>
Letter Pipe description
Connection size/type
A DHW outlet connection
22 mm/Compression
B Cold water inlet connection
22 mm/Compression
C Space heating/cooling RETURN connection
28 mm/Compression
D Space heating/cooling FLOW connection
28 mm/Compression
E Flow connection FROM heat pump (No plate heat exchanger) 28 mm/Compression
F Return connection TO heat pump (No plate heat exchanger) 28 mm/Compression
G
Refrigerant (GAS) (With plate heat exchanger)
H
Refrigerant (LIQUID) (With plate heat exchanger)
12.7 mm/Flare (E*ST**D-*) 15.88 mm/Flare (E*ST**C-*)
6.35 mm/Flare (E*ST**D-*) 9.52 mm/Flare (E*ST**C-*)
Warning
� Refrigerant pipes connection shall be accessible for maintenance purposes.
� In case of reconnecting the refrigerant pipes after detaching, make the flared part of pipe re-fabricated.
Electrical cable inlets
J
12345
For inlets , and , run low-voltage wires including external input wires and thermistor wires. For inlets and , run high-voltage wires including power cable, indoor-outdoor cable, and external output wires. *For a wireless receiver (option) cable and ecodan Wi-Fi interface (option) cable, use inlet .
<Table 3.2>
5
3 Technical Information
Component Parts
No.
Part name
<EHPT20X-MHEDW> (Packaged model system)
A DHW outlet pipe B Cold water inlet pipe C Water pipe (Space heating/cooling return connection)
D Water pipe (Space heating/cooling flow connection)
E Water pipe (Flow from heat pump connection)
C D BA
F Water pipe (Return to heat pump connection) G Refrigerant pipe (Gas)
H Refrigerant pipe (Liquid)
9
1 Control and electrical box
2 Main remote controller
3 Plate heat exchanger (Refrigerant - Water)
4 Booster heater 1,2
5 3-way valve
F
6 Drain cock (Primary circuit)
7 Manometer
E
1
8 Pressure relief valve (3bar)
9 Automatic air vent
5
10 Expansion vessel (Primary circuit) (Local supply)
7
11 Flow sensor
20 12 Strainer valve
2
13 Water circulation pump 1 (Primary circuit)
14 Pump valve
en
15 DHW tank
16 Plate heat exchanger (Water - Water)
17 Scale trap
15
18 Water circulation pump (Sanitary circuit)
11
19 Immersion heater
20 Temperature and pressure relief valve
4
18
21 Pressure relief valve (10bar) (DHW Tank)
19
22 Drain cock (DHW tank)
23 Drain cock (Sanitary circuit)
24 Flow water temp. thermistor (THW1)
22
25 Return water temp. thermistor (THW2)
17
26 DHW tank upper water temp. thermistor (THW5A)
12
27 DHW tank lower water temp. thermistor (THW5B)
16
28 Refrigerant liquid temp. thermistor (TH2)
13
23
29 Pressure sensor
30 Drain pan
14
31 Outdoor unit
32 Drain pipe (Local supply)
6
33 Back flow prevention device (Local supply)
34 Isolating valve (Local supply)
<Figure 3.1>
35 Magnetic filter (Local supply) (Recommended) 36 Strainer (Local supply)
Note: For installation of all EHPT20X-MHEDW models, make sure to install a suitably sized primary-side expansion vessel. (See figure 3.2 and 4.3.2 for further guidance)
37 Pressure relief valve (Outdoor unit) 38 Inlet control group *1 39 Filling loop (Ball valves, check valves and flexible hose) *1 40 Potable expansion vessel *1
41 Air vent (Local supply)
Water circuit diagram
*1 Supplied with UK model ONLY. Please refer to PACWK02UK-E Installation Manual for more information on accessories.
<Table 3.3>
<EHPT20X-MHEDW> (UK model system) <Example>
Note: Do not attach an additional pressure relief valve to the heating (cooling) circuit on E*PT**X model to keep fire safety.
10
40
38
Cold water
B
36 9
A 32
Drain
7
Pa
32
Drain
20
18
17 16
15 26 27
19
5
22
23 6
24 31 37 3 34 41*b
36 34
6 6
14 13 12
25 11
Cylinder unit
<Figure 3.2>
DHW
Water pipe
34 Local system *a
35 34
Drain
Flexible hose (Temporary connection)
39 Mains water supply
*a Refer to the following section `Local system' on the `Paper-based manual'.
*b If the outdoor unit is higher than the indoor unit, or if there is a location where air gets trapped in the upper part of the water pipe, consider adding this part.
Note (Figure 3.2) � To enable draining of the cylinder unit an isolat-
ing valve should be positioned on both the inlet and outlet pipework. No valve should be fitted between the expansion valve (item 38) and the cylinder unit (safety matter). � For space heating (primary) circuit a suitable expansion vessel MUST be supplied and fitted by installer. (See figure 4.3.2) � Be sure to install a strainer on the inlet pipework to the cylinder unit. � Suitable drain pipework should be attached to the relief valves instructed to be connected to it in Figure 3.2 in accordance with your country's regulations. � When using components made from different metals or connecting pipes made of different metals insulate the joints to prevent any corrosive reaction taking place which may damage any pipework. � Filling loop's flexible hose must be removed following the filling procedure. Item provided with unit as loose accessory. � Install the inlet control group (item 38) above the level of the T&P relief valve (item 20). This will ensure DHW tank will not require drain down to service/maintain the inlet control group.
6
3 Technical Information
Local system 1-zone temperature control
Zone1
1
3 5
4 2
Zone1 1
en 2-zone temperature control
Zone1 3
4
5
1
6
9
Zone2
2
7
8 10
2-zone temperature control & Buffer tank control
1-zone temperature control with boiler
11
13 3
5
4 2
Zone1 1
1-zone temperature control (2-zone valve ON/OFF control)
12 *1
2
3
4
5
6
9
7
8
Zone1
1 Zone2
10
Zone1 14
16 1
Zone2 15
10
1. Zone1 heat emitters (e.g. radiator, fan coil unit) (local supply)
2. Mixing tank (local supply)
3. Zone1 flow water temp. thermistor (THW6) Optional part : PAC-TH011-E
4. Zone1 return water temp. thermistor (THW7)
5. Zone1 water circulation pump (local supply)
6. Motorized mixing valve (local supply)
7. Zone2 flow water temp. thermistor (THW8) Optional part : PAC-TH011-E
8. Zone2 return water temp. thermistor (THW9)
9. Zone2 water circulation pump (local supply)
10. Zone2 heat emitters (e.g. underfloor heating) (local supply) 11. Boiler flow water temp. thermistor (THWB1)
Optional part : PAC-TH012HT(L)-E 12. Mixing tank thermistor (THW10) *1 13. Boiler (local supply) 14. Zone1 2-way valve (local supply) 15. Zone2 2-way valve (local supply) 16. Bypass valve (local supply)
*1 ONLY Buffer tank control (heating/cooling) applies to "Smart grid ready".
7
4 Installation
<Preparation before the installation and service>
Prepare the proper tools. Prepare the proper protection. Allow parts to cool before attempting any maintenance. Provide adequate ventilation. After stopping the operation of the system, turn off the power-supply breaker and remove the power plug. Discharge the capacitor before commencing work involving the electric parts.
<Precautions during service>
Do not perform work involving electric parts with wet hands. Do not pour water or liquid into the electric parts. Do not touch the refrigerant. Do not touch the hot or cold surfaces in the refrigerant cycle. When the repair or the inspection of the circuit needs to be carried out without turning off the power, exercise great caution NOT to touch any LIVE parts.
4.1 Location
Transportation and Handling
Front
Front
Handle
Legs
<Figure 4.1.1>
Cylinder unit is delivered on a wooden pallet base with cardboard protection.
Care should be taken when transporting the cylinder unit that the casing is not damaged by impact. Do not remove the protective packaging until cylinder unit has reached its final location. This will help protect the structure and control panel.
� The cylinder unit can be transported either vertically or horizontally. If transported horizontally the panel marked `Front' must be facing UPWARDS <Figure 4.1.1>.
� The cylinder unit should ALWAYS be moved by a minimum of 3 people. � When carrying the cylinder unit use the handles provided. � Before using the handles, make sure they are securely attached. � Please remove front handle, fixing legs, wooden base and any other pack-
aging once the unit is in installation location. � Keep the handles for future transportation.
Suitable Location
Before installation the cylinder unit should be stored in a frost-free weatherproof location. Units must NOT be stacked.
� The cylinder unit should be installed indoors in a frost free weather proof location.
� Install the cylinder unit where it is not exposed to water/excessive moisture. � The cylinder unit should be positioned on a level surface capable of supporting
it's FILLED weight. (Adjustable feet (accessory parts) can be used to ensure unit is level) � When using the adjustable feet, ensure that the floor is strong enough. � Care should be taken that minimum distances around and in front of the unit for service access are observed <Figure 4.1.2>. � Secure the cylinder unit to prevent it being knocked over.
Service access diagrams
en
Service access
Parameter a b c (distance behind unit not visible
in Figure 4.1.2) d
Dimension (mm) 300* 150
10
500
<Table 4.1.1>
Sufficient space MUST be left for the provision of discharge pipework as detailed in National and Local Building Regulations.
a
b
b
* An additional 300 mm of space (total 600 mm) is required , when installing the optional 2-zone kit (PAC-TZ02-E) on top of the cylinder unit.
d
<Figure 4.1.2> Service access
The cylinder unit must be located indoors and in a frost-free environment, for example in a utility room, to minimise heat loss from stored water.
Repositioning
If you need to move the cylinder unit to a new position FULLY DRAIN the cylinder unit before moving to avoid damage to the unit.
8
4 Installation
4.2 Water Quality and System Preparation
General
� The water in both primary and sanitary circuit should be clean and with pH value of 6.5-8.0
� The followings are the maximum values; Calcium: 100 mg/L, Ca hardness: 250 mg/L Chloride: 100 mg/L, Copper: 0.3 mg/L
� Other constituents should be to European Directive 98/83 EC standards. � In known hard water areas, to prevent/minimise scaling, it is beneficial to restrict
the routine stored water temperature (DHW max. temp.) to 55�C.
Anti-Freeze
Anti-freeze solutions should use propylene glycol with a toxicity rating of Class 1 as listed in Clinical Toxicology of Commercial Products, 5th Edition. Notes: 1. Ethylene glycol is toxic and should NOT be used in the primary water
circuit in case of any cross-contamination of the potable circuit. 2. For 2-zone valve ON/OFF control, propylene glycol should be used.
New Installation (primary water circuit) en � Before connecting outdoor unit, thoroughly cleanse pipework of building debris,
solder etc using a suitable chemical cleansing agent. � Flush the system to remove chemical cleanser. � For all packaged model systems add a combined inhibitor and anti-freeze
solution to prevent damage to the pipework and system components. � For split model systems the responsible installer should decide if anti-freeze
solution is necessary for each site's conditions. Corrosion inhibitor however should ALWAYS be used.
Existing Installation (primary water circuit)
� Before connecting outdoor unit the existing heating circuit MUST be chemically cleansed to remove existing debris from the heating circuit.
� Flush the system to remove chemical cleanser. � For all packaged model systems, and the split model or PUMY system without
booster heater, add a combined inhibitor and anti-freeze solution to prevent damage to the pipework and system components. � For split model systems the responsible installer should decide if anti-freeze solution is necessary for each site's conditions. Corrosion inhibitor however should ALWAYS be used.
When using chemical cleansers and inhibitors always follow manufacturer's instructions and ensure the product is appropriate for the materials used in the water circuit
Minimum amount of water required in the space heating/cooling circuit
Outdoor heat pump unit
*Additional required water amount [L]
Indoor unit containing
Average / Warmer climate**
water
With
Without
Colder
amount [L] booster booster climate**
heater
heater
Packaged PUZ-WM50 model PUZ-WM60
0
2
24
1
4
29
PUZ-WM85
5
4
7
32
PUZ-WM112
8
11
43
PUZ-HWM140
12
15
55
Split model
SUZ-SWM40 SUZ-SWM60
0
1
12
0
2
21
SUZ-SWM80
1
4
29
PUD-S(H)WM60
1
4
21
PUD-S(H)WM80
4
6
29
PUD-S(H)WM100
6
10
38
PUD-S(H)WM120
9
12
47
PUD-SHWM140
12
15
55
PUHZ-FRP71
11
6
27
PUHZ-SW75
5
3
6
37
PUHZ-SW100
6
9
38
PUHZ-SW120
9
12
47
PUHZ-SHW80
4
6
29
PUHZ-SHW112
8
11
43
PUHZ-SHW140
12
15
55
PUMY-P112
22
-
75
PUMY-P125
22
-
75
PUMY-P140
22
-
75
<Table 4.2.1> * If there is a bypass circuit, above table means minimum water
amount in case of bypass. ** Please refer to 2009/125/EC: Energy-related Products Directive and
Regulation (EU) No 813/2013 to confirm your climate zone.
Case 1. No division between primary and secondary circuit
� Please ensure the required water amount according to the table 4.2.1 by water pipe and radiator or underfloor heating.
Case 2. Separate primary and secondary circuit � If the interlock operation of primary and secondary pump is not available, please ensure required additional water in only primary circuit according to the table 4.2.1. � If the interlock operation of primary and secondary pump is available, please ensure total water amount of primary and secondary circuit according to the table 4.2.1. In case of the shortage of required water amount, please install buffer tank.
4.3 Water Pipe Work
Hot Water Pipework
The cylinder unit is UNVENTED. When installing unvented hot water systems building regulations part G3 (England and Wales), P3 (Scotland) and P5 (Northern Ireland) should be adhered to. If outside of the UK please adhere to your own country's regulations for unvented hot water systems.
Connect the flow for the DHW to pipe A (Figure 3.1). The function of the following safety components of the cylinder unit should be checked on installation for any abnormalities; � Pressure relief valve (Primary circuit and Tank) � Expansion vessel pre-charge (gas charge pressure)
The instruction on the following pages regarding safe discharge of hot water from Safety devices should be followed carefully. � The pipework will become very hot, so should be insulated to prevent burns. � When connecting pipework, ensure that no foreign objects such as debris or the
like enter the pipe.
Cold Water Pipework
Cold water to the suitable standard (see section 4.2) should be introduced to the system by connecting pipe B (Figure 3.1) using appropriate fittings.
9
Negative pressure prevention
To prevent negative pressure effecting DHW tank, installer should install appropriate pipework or use appropriate devices.
Hydraulic filter work (ONLY E*PT series)
Install a hydraulic filter or strainer (local supply) at the water intake ("Pipe E" in Fig.3.1)
Pipework Connections
Connections to the cylinder unit should be made using the 22 mm or 28 mm compression as appropriate. When connecting DHW pipes using compression fittings, insert copper liner for DHW pipe (accessory parts) into the pipes and tighten them from 0.75 to 1.25 turns. Do not over-tighten compression fittings as this will lead to deformation of the olive ring and potential leaks. Note: Before brazing pipes in the field, protect pipes on the cylinder unit using
wet towels etc as "heat shield".
Insulation of Pipework
� All exposed water pipework should be insulated to prevent unnecessary heat loss and condensation. To prevent condensate entering the cylinder unit, the pipework and connections at the top of the cylinder unit should be carefully insulated.
� Cold and hot water pipework should not be run close together where possible, to avoid unwanted heat transfer.
� Pipework between outdoor heat pump unit and cylinder unit should be insulated with suitable pipe insulation material with a thermal conductivity of 0.04 W/m.K.
4 Installation
Drain Pipework (ONLY ER series)
The optional part 'Drain pan stand' does not need to be set because the drain pan is installed.The drain should be set from the drain socket at left rear of the unit. The drain pipe should be installed to drain condensed water during cooling mode. � To prevent dirty water from draining directly onto the floor next to cylinder unit,
please connect appropriate discharge pipework from the cylinder drain pan. � Securely install the drain pipe to prevent leakage from the connection. � Securely insulate the drain pipe to prevent water dripping from the locally
supplied drain pipe. � Install the drain pipe at a down slope of 1/100 or more. � Do not place the drain pipe in drain channel where sulphuric gas exists. � After installation, check that the drain pipe drains water properly from the outlet of
the pipe to suitable discharge location.
<Installation> 1. The drain socket (inside diameter 26mm) is left rear of the cylinder unit. (Figure
4.3.1) 2. Fix the drain pipe (VP-20) which fits the drain socket with the polyvinyl chloride
type adhesive. 3. Set the drain pipework up to the outlet with the down grade of more than one
hundredth. Note: Securely support the locally supplied drain pipe to avoid the drain pipe falling
from the drain socket.
Drain hose
en
Drain socket
<Figure 4.3.1>
Sizing Expansion Vessels
Expansion vessel volume must fit the local system water volume. To size an expansion vessel for the heating circuit the following formula and graph can be used. When the necessary expansion vessel volume exceeds the volume of an built-in expansion vessel, install an additional expansion vessel so that the sum of the volumes of the expansion vessels exceeds the necessary expansion vessel volume. * For installation of an E**T***-*M*ED* model, provide and install a suitable
primary-side expansion vessel and additional 3 bar rated pressure relief valve in the field as the model DOES NOT come fitted with a primary-side expansion vessel.
V
=
1
-
� G P� + 0.098 P� + 0.098
Where;
V : Necessary expansion vessel volume [L]
: Water expansion coefficient G : Total volume of water in the system [L]
P� : Expansion vessel setting pressure [MPa] P� : Max. pressure during operation [MPa]
Graph to the right is for the following values
: at 70�C = 0.0229
P� : 0.1 MPa P� : 0.3 MPa *A 30% safety margin has been added.
Expansion vessel volume [L]
Expansion vessel sizing
25
20
15
10
5
0
0
50 100 150 200 250 300 350 400
System water volume [L]
<Figure 4.3.2>
Filling the System (Primary Circuit)
1. Check and charge expansion vessel. 2. Check all connections including factory fitted ones are tight. 3. Insulate pipework between cylinder unit and outdoor unit. 4. Thoroughly clean and flush, system of all debris. (see section 4.2 for instruction.) 5. Fill cylinder unit with potable water. Fill primary heating circuit with water and
suitable anti-freeze and inhibitor as necessary. Always use a filling loop with double check valve when filling the primary circuit to avoid back flow contamination of water supply. 6. Check for leakages. If leakage is found, retighten the screws onto the connections.
� Anti-freeze should always be used for packaged model systems (see section 4.2 for instruction). It is the responsibility of the installer to decide if anti-freeze solution should be used in split model systems depending on each site's conditions. Corrosion inhibitor should be used in both split model and packaged model systems. Figure 4.3.3 shows freezing temperature against anti-freeze concentration. This figure is an example for FERNOX ALPHI-11. For other anti-freeze, please refer to relevant manual.
� When connecting metal pipes of different materials insulate the joints to prevent a corrosive reaction taking place which will damage the pipework.
7. Pressurise system to 1 bar. 8. Release all trapped air using air vents during and following heating period. 9. Top up with water as necessary. (If pressure is below 1 bar) 10. After removing the air, automatic air vent MUST be closed.
5
Freezing temperature [�C]
0
-5
-10
-15
-20
-25 0
10
20
30
40
50
Anti-freeze concentration [%]
<Figure 4.3.3>
10
4 Installation
Water Circulation Pump Characteristics
1. Primary circuit Pump speed can be selected by main remote controller setting (see <Figure 4.3.4 to 4.3.8> ). Adjust the pump speed setting so that the flow rate in the primary circuit is appropriate for the outdoor unit installed (see Table 4.3.1). It may be necessary to add an additional pump to the system depending on the length and lift of the primary circuit. For outdoor unit model not listed in the <Table 4.3.1>, refer to Water flow rate range in the specification table of outdoor unit Data Book.
<Second pump > If a second pump is required for the installation please read the following carefully. If a second pump is used in the system it can be positioned in 2 ways. The position of the pump influences which terminal of the FTC the signal cable should be wired to. If the additional pump(s) have current greater than 1A please use appropriate relay. Pump signal cable can either be wired to TBO.1 1-2 or CNP1 but NOT both.
Option 1 (Space heating/cooling only)
If the second pump is being used for the heating circuit only then the signal cable
en
should be wired to TBO.1 terminals 3 and 4 (OUT2). In this position the pump can be run at a different speed to the cylinder unit's in-built pump.
Option 2 (Primary circuit DHW and space heating/cooling) If the second pump is being used in the primary circuit between the cylinder unit and the outdoor unit (Package system ONLY) then the signal cable should be wired to TBO.1 terminals 1 and 2 (OUT1). In this position the pump speed MUST match the speed of the cylinder unit's in-built pump. Note: Refer to 5.2 Connecting inputs/outputs.
Water circulation pump characteristics
E*PT17X series 80
External static pressure [kPa]
70
60
50
40
30
20
10
0
0
5 10 15 20 25
Flow rate [L/min]
<Figure 4.3.4>
Speed 5 (Default setting) Speed 4 Speed 3 Speed 2 Speed 1
30 35 40
External static pressure [kPa]
80 70 60 50 40 30 20 10
0 0
E*ST17/20D series
Speed 5 (Default setting) Speed 4 Speed 3 Speed 2 Speed 1
5 10 15 20 25 30 35 40
Flow rate [L/min] <Figure 4.3.6>
External static pressure [kPa]
80 70 60 50 40 30 20 10
0 0
11
E*ST20/30C series
Speed 5 (Default setting) Speed 4 Speed 3 Speed 2 Speed 1
5 10 15 20 25 30 35 40
Flow rate [L/min] <Figure 4.3.8>
External static pressure [kPa]
External static pressure [kPa]
Outdoor heat pump unit
Packaged model PUZ-WM50
PUZ-WM60
PUZ-WM85
PUZ-WM112
PUZ-HWM140
Split model
SUZ-SWM40
SUZ-SWM60
SUZ-SWM80
PUD-S(H)WM60
PUD-S(H)WM80
PUD-S(H)WM100
PUD-S(H)WM120
PUD-SHWM140
PUHZ-FRP71
PUHZ-SW75
PUHZ-SW100
PUHZ-SW120
PUHZ-SHW80
PUHZ-SHW112
PUHZ-SHW140
PUMY-P112
PUMY-P125
PUMY-P140
Water flow rate range [L/min] 6.5 - 14.3 8.6 - 17.2 10.8 - 24.4 14.4 - 32.1 17.9 - 36.9 6.5 - 11.4 7.2 - 17.2 7.8 - 21.5 9.0 - 22.9 9.0 - 22.9 14.3 - 34.4 14.3 - 34.4 14.3 - 34.4 11.5 - 22.9 10.2 - 22.9 14.4 - 32.1 20.1 - 36.9 10.2 - 22.9 14.4 - 32.1 17.9 - 36.9 17.9 - 35.8 17.9 - 35.8 17.9 - 35.8
<Table 4.3.1>
* If the water flow rate is less than the minimum flow rate setting of the flow
sensor(default 5.0 L/min), the flow rate error will be activated. If the water flow rate exceeds 36.9 L/min (E**T20/30 series) or 25.8 L/min
(E**T17 series), the flow speed will be greater than 2.0 m/s, which could erode the pipes.
2. Sanitary circuit Default setting: Speed 2 DHW circulation pump MUST be set to speed 2.
80 70 60 50 40 30 20 10
0 0
80 70 60 50 40 30 20 10
0 0
E*PT20/30X series
Speed 5 (Default setting) Speed 4 Speed 3 Speed 2 Speed 1
5 10 15 20 25 30 35 40
Flow rate [L/min] <Figure 4.3.5> E*ST30D series
Speed 5 (Default setting) Speed 4 Speed 3 Speed 2 Speed 1
5 10 15 20 25 30 35 40
Flow rate [L/min] <Figure 4.3.7>
*For installation of E*PT series, set its pump speed with a pressure drop between the cylinder unit and the outdoor unit factored into the external static
pressure.
4 Installation
Immersion heater
When an immersion heater is fitted, do NOT energise the heater until the DHW tank is full of water. Also do NOT energise any immersion heater if any sterilisation chemicals remain in the DHW tank as this will cause premature failure of the heater.
Safety Device Connections
The expansion relief valve on the secondary hot water side, and the temperature and pressure (T&P) relief valve (*A), both need appropriate discharge pipework. There must be no valve fitted between the expansion relief valve and the tank.
*A EHPT20X-MHEDW is equipped with T & P relief valve on the tank (2). Any other models are equipped with Pressure relief valve, fitted to the DHW pipework (3).
Note : 1. Do not secure the screws excessively when connecting the Discharge pipe, otherwise it may result in damage to the cylinder unit.
<For UK> The right side panel has a plate (*B) so that connection can be made to the factory fitted temperature and pressure relief valve. If you wish to make the connection in a different position you will have to cut a hole in the side panel yourself. However it remains necessary that the drainage parameters outlined in the appropriate Building Regulations are complied with.
*B Unscrew the plate on the right-side panel, connect the Pressure relief valve to the discharge pipework, and refit the plate. Always replace the plate so that no gaps exist between the plate and side panel and the plate and drain pipe to avoid heat loss. In accordance with Building Regulations a tundish must be fitted into the pipework within 500 mm of the safety device (also see Figure 4.4.1). Due to the distance between the two safety devices it may be necessary to fit each safety device with its own tundish before you run the pipework together to a safe discharge (see Figure 4.3.9).
Note : 2. Alternatively the discharges from the expansion relief valve and T&P relief valve may commonly discharge to a singular tundish, so long as this tundish is located within 500 mm of the T&P relief valve in UK. When connecting discharge pipes to the safety devices, beware not to strain the inlet connections.
Diagram Description part No.
1
Expansion relief valve (part of inlet control group)
2
T&P relief valve
Connection size 15 mm
15 mm /G 1/2
3 Pressure relief valve
G 1/2
<Table 4.3.2>
Connection type Compression
Compression/ Female Female
<UK model> EHPT20X-MHEDW
DHW
1 Cold water inlet
2
en
Tundish
<Other models>
3 DHW
The expansion vessel on the sanitary water side shall be installed as necessary in accordance with your local regulations.
Cold water inlet
Always refer to local regulations when installing discharge pipework. Install discharge pipework in a frost-free environment. It is necessary to provide appropriate drainage from the pressure relief valve situated on top of the cylinder unit to prevent damage to the unit and the surrounding area from any steam or hot water released. Relief valves MUST NOT be used for any other purpose.
For UK use WK02UK-E kit, for other countries please see below; � Any discharge pipework should be capable of withstanding discharge of hot
water. Discharge pipework should be installed in a continuously downward direction. Discharge pipework must be left open to the environment.
<Figure 4.3.9>
Piping diagram for 2-zone temperature control
Connect the pipe work and locally supplied parts according to the relevant circuit diagram shown in Section 3. Technical Information, of this manual. For more details on wiring, refer to "5.3 Wiring for 2-zone temperature control".
Note: Do not install the thermistors on the mixing tank. This could affect correct monitoring of flow and return temperatures through each zone. Install the Zone2 flow temp. thermistor (THW8) near the mixing valve.
12
4 Installation
4.4 Safety Device Discharge Arrangements (G3)
The following instructions are a requirement of UK Building Regulations and must be adhered to. For other countries please refer to local legislation. If you are in any doubt please seek advice from local building planning office.
1. Position the inlet control group so that discharge from both safety valves can be joined together via a 15 mm end feed Tee.
2. Connect the tundish and route the discharge pipe as shown in Figure 4.4.1. 3. The tundish should be fitted vertically and as close to the safety device as pos-
sible and within 500 mm of the device. 4. The tundish should be visible to occupants and positioned away from electrical
devices. 5. The discharge pipe (D2) from the tundish should terminate in a safe place
where there is no risk to persons in the vicinity of the discharge, be of metal construction and:
A) Be at least one pipe size larger than the nominal outlet size of the safety de-
vice unless its total equivalent hydraulic resistance exceeds that of a straight
pipe 9 m long i.e. discharge pipes between 9 m and 18 m equivalent resist-
ance length should be at least two sizes larger than the nominal outlet size
en
of the safety device, between 18 and 27 m at least 3 sizes larger, and so on.
Bends must be taken into account in calculating the flow resistance. Refer to
Figure 4.4.1, Table 4.4.1 and the worked example. An alternative approach
for sizing discharge pipes would be to follow BS 6700: 1987 specification for
design installation, testing and maintenance of services supplying water for
domestic use within buildings and their cartilages.
B) Have a vertical section of pipe at least 300 mm long, below the tundish before any elbows or bends in the pipework.
C) Be installed with a continuous fall.
D) Have discharges visible at both the tundish and the final point of discharge but where this is not possible or is practically difficult there should be clear visibility at one or other of these locations. Examples of acceptable discharge arrange-
ments are:
Metal discharge pipe (D1) temperature relief valve to tundish
Safety device (e.g. temperature
relief valve)
500 mm maximum
Tundish
300 mm minimum
Metal discharge pipe (D2) from tundish, with continuous fall. See Point 5.D i-iv, Table 4.4.1 and worked example
i. Ideally below a fixed grating and above the water seal in a trapped gully.
ii. Downward discharges at low level; i.e. up to 100 mm above external surfaces such as car parks, hard standings, grassed areas etc. are acceptable providing that where children may play or otherwise come into contact with discharges a wire cage or similar guard is positioned to prevent contact, whilst maintaining visibility.
iii. Discharges at high level; e.g. into a metal hopper and metal down pipe with the end of the discharge pipe clearly visible (tundish visible or not) or onto a roof capable of withstanding high temperature discharges of water and 3 m from any plastic guttering system that would collect such discharges (tundish visible).
iv. Where a single pipe serves a number of discharges, such as in blocks of flats, the number served should be limited to not more than 6 systems so that any installation discharging can be traced reasonably easily. The single common discharge pipe should be at least one pipe size larger than the largest individual discharge pipe (D2) to be connected. If unvented hot water storage systems are installed where discharges from safety devices may not be apparent i.e. in dwellings occupied by blind, infirm or disabled people, consideration should be given to the installation of an electronically operated device to warn when discharge takes place.
Note: The discharge will consist of scalding water and steam. Asphalt, roofing felt and nonmetallic rainwater goods may be damaged by such discharges.
Worked example: The example below is for a G� temperature relief valve with a discharge pipe (D2) having 4 No. elbows and length of 7 m from the tundish to the point of discharge.
From Table 4.4.1: Maximum resistance allowed for a straight length of 22 mm copper discharge pipe (D2) from a G� temperature relief valve is: 9.0 m subtract the resistance for 4 No. 22 mm elbows at 0.8 m each = 3.2 m. Therefore the maximum permitted length equates to: 5.8 m. 5.8 m is less than the actual length of 7 m, therefore calculate the next largest size. Maximum resistance allowed for a straight length of 28 mm pipe (D2) from a G� temperature relief valve equates to: 18 m Subtract the resistance for 4 No. 28 mm elbows at 1.0 m each = 4 m. Therefore the maximum permitted length equates to: 14 m. As the actual length is 7 m, a 28 mm (D2) copper pipe will be satisfactory.
Discharge below fixed grating (Point 5.D gives alternative points of discharge)
Fixed grating
Trapped gulley
<Figure 4.4.1>
Valve outlet Minimum size of
size
discharge pipe D1
G 1/2
15 mm
G 3/4
22 mm
G1
28 mm
Minimum size of discharge pipe D2 from tundish
22 mm 28 mm 35 mm 28 mm 35 mm 42 mm 35 mm 42 mm 54 mm
Maximum resistance allowed, expressed as a length of straight pipe (no elbows or bends)
Up to 9 m Up to 18 m Up to 27 m Up to 9 m Up to 18 m Up to 27 m Up to 9 m Up to 18 m Up to 27 m
<Table 4.4.1>
Resistance created by each elbow or bend
0.8 m 1.0 m 1.4 m 1.0 m 1.4 m 1.7 m 1.4 m 1.7 m 2.3 m
13
4 Installation
4.5 Electrical Connection
All electrical work should be carried out by a suitably qualified technician. Failure to comply with this could lead to electrocution, fire, and death. It will also invalidate product warranty. All wiring should be according to national wiring regula-
tions.
Breaker abbreviation ECB1 ECB2 TB1
Meaning Earth leakage circuit breaker for booster heater Earth leakage circuit breaker for immersion heater Terminal block 1
ECB1 ECB2
ECB1
A
A
E
B
F
E B
D
C
TB1 <1 phase (with immersion heater)>
D
C
TB1 <3 phase (without immersion heater)>
The cylinder unit can be powered in two ways. 1. Power cable is run from the outdoor unit to the cylinder unit. 2. Cylinder unit has independent power source
Connections should be made to the terminals indicated in the figures to the left below depending on the phase.
Booster heater and immersion heater should be connected independently from one another to dedicated power supplies.
Locally supplied wiring should be inserted through the inlets situated on the
top of the cylinder unit. (Refer to <Table 3.2>.)
Wiring should be fed down the right hand side of the control and electrical
box and clamped in place using clips provided.
The wires should be inserted individually through the cable inlets as below.
2 Outputs wire
8
3 Indoor-Outdoor wire
7
5 Power line(B.H.)/ Power line(I.H.)(Option)
7 Signal input wires
1 23
456
Connect the outdoor unit � cylinder unit connecting cable to TB1.
Connect the power cable for the booster heater to ECB1.
en
If immersion heater is present, connect the power cable to ECB2.
� Avoid contact between wiring and parts ( ). � Make sure that ECB1 and ECB2 are ON. � On completion of wiring ensure main remote controller cable is con-
nected to the relay connector.
Cylinder unit powered via outdoor unit
(If you want to use independent source, go to the Mitsubishi website.)
<1 phase>
Affix label A that is included with the manuals near each wiring diagram for cylinder unit and outdoor units.
Power supply ~/N 230 V 50 Hz
Earth leakage circuit breaker
*1 ,*2
Wiring circuit breaker
or Isolating switch
Outdoor unit
L
S1
N
S2
S3
Cylinder unit
TB1
L N
To control board S1 S2 S3
Power supply ~/N 230 V 50 Hz
Power supply ~/N 230 V 50 Hz
Wiring circuit breaker or Isolating switch
Wiring circuit breaker or Isolating switch
ECB1
For
L booster
N
heater (Primary circuit)
ECB2
For L immersion
N
heater (DHW tank)
<Figure 4.5.1> Electrical connections 1 phase
*1. If the installed earth leakage circuit breaker does not have an over-current protection function, install a breaker with that function along the same power line.
*2. A breaker with at least 3.0 mm contact separation in each pole shall be provided. Use earth leakage breaker (NV). The breaker shall be provided to ensure disconnection of all active phase conductors of the supply.
*3. Max. 45 m If 2.5 mm� used, Max. 50 m If 2.5 mm� used and S3 separated, Max. 80 m
*4. The values given in the table above are not always measured against the ground value.
Description
Power supply
Booster heater (Primary circuit) ~/N 230 V 50 Hz
Immersion heater (DHW tank) ~/N 230 V 50 Hz
Capacity
2 kW 6 kW 3 kW
Breaker
16 A *2 32 A *2 16 A *2
Wiring
2.5 mm� 6.0 mm� 2.5 mm�
Wiring
Circuit
Wiring No.
rating
� size (mm�)
Cylinder unit - Outdoor unit
*3
Cylinder unit - Outdoor unit earth *3
Cylinder unit - Outdoor unit S1 - S2 *4
Cylinder unit - Outdoor unit S2 - S3 *4
3 � 1.5 (polar) 1 � Min. 1.5 230 V AC 24 V DC
Notes:
1. Wiring size must comply with the applicable local and national codes.
2. Indoor unit/outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord. (Design 60245 IEC 57) Indoor unit power supply cords shall not be lighter than polychloroprene sheathed flexible cord. (Design 60227 IEC 53)
3. Install an earth longer than other cables.
4. Please keep enough output capacity of power supply for each heater. Insufficient power supply capacity might cause chattering.
14
4 Installation
<3 phase>
Affix label A that is included with the manuals near each wiring diagram for cylinder unit and outdoor units.
Outdoor unit
Power supply 3N~ 400 V 50 Hz
Earth leakage circuit breaker
*1, *2
Wiring circuit breaker
or Isolating switch
L1
S1
L2
S2
L3
S3
N
Power supply 3~ 400 V 50 Hz (E**T***-YM9*D) 3~ 230 V 50 Hz (E**T***-TM9*D)
Wiring circuit breaker
or Isolating switch
en
Power supply ~/N 230 V 50 Hz
Wiring circuit breaker
or Isolating switch
Cylinder unit
TB1
L N
To control board S1 S2 S3
ECB1
L1 For
L2
booster heater
L3 (Primary circuit)
ECB2
For L immersion
heater N (DHW tank)
<Figure 4.5.2> Electrical connections 3 phase
Description Booster heater (Primary circuit) Immersion heater (DHW tank)
Power supply
3~ 400 V 50 Hz 3~ 230 V 50 Hz ~/N 230 V 50 Hz
Capacity (Indoor unit Ref.) Breaker
9 kW
16 A *2
9 kW
32 A *2
3 kW
16 A *2
Wiring
2.5 mm� 6.0 mm� 2.5 mm�
Wiring Wiring No. � size (mm�)
Cylinder unit - Outdoor unit
*3
3 � 1.5 (polar)
Cylinder unit - Outdoor unit earth *3
1 � Min. 1.5
Circuit rating
Cylinder unit - Outdoor unit S1 - S2 *4
230 V AC
Cylinder unit - Outdoor unit S2 - S3 *4
24 V DC
*1. If the installed earth leakage circuit breaker does not have an over-current protection function, install a breaker with that function along the same power line.
*2. A breaker with at least 3.0 mm contact separation in each pole shall be provided. Use earth leakage breaker (NV). The breaker shall be provided to ensure disconnection of all active phase conductors of the supply.
*3. Max. 45 m If 2.5 mm� used, Max. 50 m If 2.5 mm� used and S3 separated, Max. 80 m
*4. The values given in the table above are not always measured against the ground value.
Notes:
1. Wiring size must comply with the applicable local and national codes.
2. Indoor unit/outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord. (Design 60245 IEC 57) Indoor unit power supply cords shall not be lighter than polychloroprene sheathed flexible cord. (Design 60227 IEC 53)
3. Install an earth longer than other cables.
4. Please keep enough output capacity of power supply for each heater. Insufficient power supply capacity might cause chattering.
15
5 System Set Up
SW5
5.1 DIP Switch Functions
SW4
The DIP switch number is printed on the circuit board next to the relevant switches. The word ON is printed on the circuit board and on the DIP switch block itself. To move the switch you will need to use a pin or the corner of a thin metal ruler or similar.
DIP switch settings are listed below in Table 5.1.1. Only an authorised installer can change DIP switch setting under one's own responsibility according to the installation condition. Make sure to turn off both indoor unit and outdoor unit power supplies before changing the switch settings.
SW3
SW2 SW1 SW6
<Figure 5.1.1>
DIP switch
Function
OFF
ON
Default settings: Indoor unit model
SW1 SW1-1 Boiler SW1-2 Heat pump maximum outlet water temperature SW1-3 DHW tank
WITHOUT Boiler 55�C WITHOUT DHW tank
WITH Boiler 60�C WITH DHW tank
OFF ON *1 ON
SW1-4 Immersion heater
WITHOUT Immersion heater
WITH Immersion heater
OFF: Except EHPT20X-MHEDW
ON : EHPT20X-MHEDW
SW1-5 Booster heater
WITHOUT Booster heater
WITH Booster heater
OFF: E**T***-M**D* ON : E**T***-*M 2/6/9*D
SW1-6 Booster heater function
For heating only
For heating and DHW
OFF: E**T***-M**D*
en
ON : E**T***-*M 2/6/9*D
SW1-7 Outdoor unit type
Split type
Packaged type
OFF: E*ST***-*M**D ON : E*PT**X-*M**D*
SW1-8 Wireless remote controller
WITHOUT Wireless remote controller WITH Wireless remote controller
OFF
SW2 SW2-1 Room thermostat 1 input (IN1) logic change
Zone1 operation stop at thermostat short Zone1 operation stop at thermostat open OFF
SW2-2 Flow switch 1 input (IN2) logic change
Failure detection at short
Failure detection at open
OFF
SW2-3 Booster heater capacity restriction
Inactive
Active
OFF: Except E**T***-VM2*D
ON : E**T***-VM2*D
SW2-4 Cooling mode function
Inactive
Active
OFF: EH*T***-*M**D* ON : ER*T***-*M**D
SW2-5
Automatic switch to backup heat source operation (When outdoor unit stops by error)
Inactive
Active *2
OFF
SW2-6 Mixing tank
WITHOUT Mixing tank
WITH Mixing tank
OFF
SW2-7 2-zone temperature control
Inactive
Active *6
OFF
SW2-8 Flow sensor
WITHOUT Flow sensor
WITH Flow sensor
ON
SW3 SW3-1 Room thermostat 2 input (IN6) logic change
Zone2 operation stop at thermostat short Zone2 operation stop at thermostat open OFF
SW3-2 Flow switch 2 and 3 input logic change
Failure detection at short
Failure detection at open
OFF
SW3-3 3-way valve type SW3-4 Electric energy meter
AC motor WITHOUT Electric energy meter
Stepping motor WITH Electric energy meter
OFF: Except E**T17X/17D/20D*M**D*
ON: E**T17X/17D/20D-*M**D
OFF
SW3-5 Heating mode function *3
Inactive
Active
ON
SW3-6 2-zone valve ON/OFF control
Inactive
Active
OFF
SW3-7 Heat exchanger for DHW
Coil in tank
External plate HEX
ON
SW3-8 Heat meter
WITHOUT Heat meter
WITH Heat meter
OFF
SW4 SW4-1
--
--
--
OFF
SW4-2
--
--
--
OFF
SW4-3
--
--
--
OFF
SW4-4 Indoor unit only operation (during installation work) *4 Inactive
Active
OFF
SW4-5 Emergency mode (Heater only operation)
Normal
Emergency mode (Heater only operation) OFF *5
SW4-6 Emergency mode (Boiler operation)
Normal
Emergency mode (Boiler operation) OFF *5
SW5 SW5-1
--
--
--
OFF
SW5-2 Advanced auto adaptation
Inactive
Active
ON
SW5-3
Capacity code
SW5-4
SW5-3 SW5-4 SW5-5 SW5-6 SW5-7
SW5-5 SW5-6 SW5-7
E**T**C-*M**D E**T**D-*M**D E**T**X-*M**D*
ON ON OFF
ON OFF OFF
ON OFF OFF
ON ON OFF
OFF OFF OFF
SW5-8
--
--
--
OFF
SW6 SW6-1
--
--
--
OFF
SW6-2
--
SW6-3 Pressure sensor
SW6-4 Analog output signal (0-10 V)
-- Inactive Inactive
-- Active Active
OFF OFF: Except E*ST**D-*M**D ON: E*ST**D-*M**D OFF
SW6-5
--
--
--
OFF
<Table 5.1.1>
Notes:
*1. When the cylinder unit is connected with a PUMY-P outdoor unit of which maximum outlet water temperature is 55�C, DIP SW1-2 must be changed to OFF.
*2. External output (OUT11) will be available. For safety reasons, this function is not available for certain errors. (In that case, system operation must be stopped and only the water circulation pump keeps running.)
*3. This switch functions only when the cylinder unit is connected with a PUHZ-FRP outdoor unit. When another type of outdoor unit is connected, the heating mode function is active regardless of the fact that this switch is ON or OFF.
*4. Space heating and DHW can be operated only in indoor unit, like an electric heater. (Refer to "5.4 Indoor unit only operation". ) *5. If emergency mode is no longer required, return the switch to OFF position. *6. Active only when SW3-6 is set to OFF.
16
5 System Set Up
5.2 Connecting inputs/outputs
en
1 TBO.1
2
3
1
4 3
5
6 1
1 TBO.2
2
3
3
4
5
6
1
1 TBO.3 3
2
5
3
4
5
6
7
8
1 TBO.4
2
3
4
5
6
7
8
1
3
1
1
CNBC
3 (GY) 3
1
3 CNBH 5 (WH)
7
CNP1 (WH) CNP4 (RD)
CNV1 (WH)
CNIH (OG) CNBHT
(BK)
1
SW5
8 1 SW4 6 1
SW3
8 1
SW2
8 1
SW1
8
1 SW6
5
TAB1
F2 LED1
LED2 LED3
1 CN01 (BK) 3
5
F1
CN3C 1 (BU) 3
CNPWM 1 (WH) 3
1
CN851 (BK)
8
1 CNRF (WH)
5
1 CN105
(RD) 5
1 CNIT (BU)
5
CN22 1 (BU) 2
LED4
CN108
Wiring specification and local supply parts
Item Signal input
Name Signal input
Model and specifications Use sheathed vinyl coated cord or cable.
function
wire
Max. 30 m
Wire type: CV, CVS or equivalent
Wire size: Stranded wire 0.13 mm� to 0.52 mm�
Switch
Solid wire: �0.4 mm to �0.8 mm Non-voltage "a" contact signals Remote switch: minimum applicable load 12 V DC, 1 mA
Note: Stranded wire should be processed with insulation-covered bar terminal (DIN46228-4 standard compatible type).
CN401 (WH)
1
CN1A (WH)
1
4
4
CNW5 CNW12
(BU) (RD)
1
1
CN21 (YE)
1
4
4
3
CN20 (RD)
1
2
8765 43 21 8765 43 21 8765 43 21 876543 21 8765 43 21 876543 21
TBI.1
TBI.2
TBI.3
TBI.4
TBI.5
TBI.6
<Figure 5.2.1>
Signal inputs
Name Terminal block Connector Item
IN1 TBI.1 7-8
-- Room thermostat 1 input *1
IN2 TBI.1 5-6
-- Flow switch 1 input
IN3 TBI.1 3-4
-- Flow switch 2 input (Zone1)
IN4 TBI.1 1-2
-- Demand control input
IN5 TBI.2 7-8
-- Outdoor thermostat input *2
IN6 TBI.2 5-6
-- Room thermostat 2 input *1
IN7 TBI.2 3-4
-- Flow switch 3 input (Zone2)
IN8 TBI.3 7-8
-- Electric energy meter 1
IN9 TBI.3 5-6
-- Electric energy meter 2
IN10 TBI.2 1-2
-- Heat meter
IN11 TBI.3 3-4 IN12 TBI.3 1-2
-- --
Smart grid ready input
INA1 TBI.4 1-3
CN1A
Flow sensor
OFF (Open)
ON (Short)
Refer to SW2-1 in <5.1 DIP Switch Functions>.
Refer to SW2-2 in <5.1 DIP Switch Functions>.
Refer to SW3-2 in <5.1 DIP Switch Functions>.
Normal
Heat source OFF/ Boiler operation *3
Standard operation Heater operation/ Boiler operation *3
Refer to SW3-1 in <5.1 DIP Switch Functions>.
Refer to SW3-2 in <5.1 DIP Switch Functions>.
*4
*5
--
--
*1. Set the ON/OFF cycle time of the room thermostat for 10 minutes or more; otherwise the compressor may be damaged. *2. If using outdoor thermostat for controlling operation of heaters, the lifetime of the heaters and related parts may be reduced. *3. To turn on the boiler operation, use the main remote controller to select "Boiler" in "External input setting" screen in the service menu. *4. Connectable electric energy meter and heat meter
Pulse type Pulse duration
Possible unit of pulse
Voltage free contact for 12 VDC detection by FTC (TBI.2 1pin ,TBI.3 5 and 7 pins have a positive voltage.)
Minimum ON time: 40 ms Minimum OFF time: 100 ms
0.1 pulse/kWh
1 pulse/kWh
10 pulse/kWh
100 pulse/kWh
1000 pulse/kWh
Those values can be set by the main remote controller. (Refer to the menu tree in "Main remote controller".) *5. As for the SG ready, refer to "5.5 Smart grid ready".
Thermistor inputs
Name Terminal block Connector
TH1
--
CN20
TH2
--
CN21
THW1
--
CNW12 1-2
THW2
--
CNW12 3-4
THW5A
--
CNW5 1-2
THW5B
--
CNW5 3-4
THW6 TBI.5 7-8
--
THW7 TBI.5 5-6
--
THW8 TBI.5 3-4
--
THW9 TBI.5 1-2
--
THWB1 TBI.6 7-8
--
THW10 TBI.6 5-6
--
Item Thermistor (Room temp.) (Option) Thermistor (Ref. liquid temp.) Thermistor (Flow water temp.) Thermistor (Return water temp.) Thermistor (DHW tank upper water temp.) Thermistor (DHW tank lower water temp.) Thermistor (Zone1 flow water temp.) (Option) *1 Thermistor (Zone1 return water temp.) (Option) *1 Thermistor (Zone2 flow water temp.) (Option) *1 Thermistor (Zone2 return water temp.) (Option) *1 Thermistor (Boiler flow water temp.) (Option) *1 Thermistor (Mixing tank water temp.) (Option) *1
Optional part model PAC-SE41TS-E
-- -- -- -- --
PAC-TH011-E
PAC-TH011-E
PAC-TH012HT-E(5 m)/ PAC-TH012HTL-E(30 m)
Ensure to wire thermistor wirings away from the power line and/or OUT1 to 16 wirings. *1. The maximum length of the thermistor wiring is 30 m.
The length of the optional thermistors are 5 m. If you need to splice and extend the wirings, following points must be carried out. 1) Connect the wirings by soldering. 2) Insulate each connecting point against dust and water. Stranded wire should be processed with insulation-covered bar terminal (DIN46228-4 standard compatible type).
17
5 System Set Up
Outputs
Name Terminal block Connector Item
OFF ON Signal/Max current
Max. total current
OUT1 TBO.1 1-2
CNP1
Water circulation pump 1 output (Space heating/cooling & DHW)
OFF ON
230 V AC 1.0 A Max. (Inrush current 40 A Max.)
OUT2 TBO.1 3-4 OUT3 TBO.1 5-6
--
Water circulation pump 2 output (Space heating/cooling for Zone1) OFF ON
230 V AC 1.0 A Max. (Inrush current 40 A Max.)
Water circulation pump 3 output (Space heating/cooling for Zone2) *1 OFF ON 230 V AC 1.0 A Max.
4.0 A (a)
-- 2-way valve 2b output *2
(Inrush current 40 A Max.)
OUT14
--
CNP4
Water circulation pump 4 output (DHW)
OFF ON
230 V AC 1.0 A Max. (Inrush current 40 A Max.)
TBO.2 4-6 OUT4
--
CNV1 CN851
3-way valve (2-way valve) output 3-way valve output
Heating DHW 230 V AC 0.1 A Max.
TBO.2 1-2 OUT5
TBO.2 2-3
-- Mixing valve output *1
Stop
Close 230 V AC 0.1 A Max.
Open
OUT6
--
CNBH 1-3 Booster heater 1 output
OFF ON 230 V AC 0.5 A Max. (Relay)
OUT7
--
OUT8 TBO.4 7-8
OUT9 TBO.4 5-6
OUT11 TBO.3 5-6
OUT12 TBO.3 7-8
OUT13 TBO.4 3-4
CNBH 5-7 --
CNIH -- -- --
Booster heater 2 output Cooling signal output Immersion heater output Error output Defrost output 2-way valve 2a output *2
OFF ON OFF ON
230 V AC 0.5 A Max. (Relay) 3.0 A (b)
230 V AC 0.5 A Max.
OFF ON 230 V AC 0.5 A Max. (Relay)
Normal Error 230 V AC 0.5 A Max.
Normal Defrost 230 V AC 0.5 A Max.
OFF ON 230 V AC 0.1 A Max.
en
OUT15 TBO.4 1-2
-- Comp ON signal
OFF ON 230 V AC 0.5 A Max.
OUT10 TBO.3 1-2 OUT16 TBO.3 3-4
-- Boiler output -- Heating/Cooling thermo ON signal
OFF ON OFF ON
non-voltage contact �220 - 240 V AC (30 V DC) 0.5 A or less �10 mA 5 V DC or more
--
OUTA1 TBI.4 7-8
-- Analog output
0 - 10 V 0 - 10 V DC 5 mA max.
--
Do not connect to the terminals that are indicated as "--" in the "Terminal block" field. *1 For 2-zone temperature control. *2 For 2-zone valve ON/OFF control.
NLNLNL
NLL N
NLNL
NL NLNLNL
TBO.1 1 2 3 4 5 6 TBO.2 1 2 3 4 5 6 TBO.3 1 2 3 4 5 6 7 8 TBO.4 1 2 3 4 5 6 7 8 TBI.4 8 7
OUT1 OUT2 OUT3
Close Open
OUT5
OUT4
OUT10 OUT16OUT11 OUT12
OUT15 OUT13 OUT9 OUT8
OUTA1
How to use TBO.1 to 4
Wiring specification and local supply parts
Tool Tool
Item
Name
Model and specifications
External output function Outputs wire
Use sheathed vinyl coated cord or cable. Max. 30 m Wire type: CV, CVS or equivalent Wire size: Stranded wire 0.25 mm� to 1.5 mm�
Solid wire: �0.57 mm to �1.2 mm
Conductor Outline view
Conductor Top view
Connect them using either way as shown above.
Notes:
<Figure 5.2.2>
1. When the cylinder unit is powered via outdoor unit, the maximum grand total current of (a)+(b) is 3.0 A.
2. Do not connect multiple water circulation pumps directly to each output (OUT1, OUT2, and OUT3). In such a case, connect them via (a) relay(s).
3. Do not connect water circulation pumps to both TBO.1 1-2 and CNP1 at the same time.
4. Connect an appropriate surge absorber to OUT10 (TBO.3 1-2) depending on the load at site.
5. Stranded wire should be processed with insulation-covered bar terminal (DIN46228-4 standard compatible type).
6. Use the same thing as the Signal input wire for OUTA1 wiring.
5.3 Wiring for 2-zone temperature control
Connect the pipe work and locally supplied parts according to the relevant circuit diagram shown "Local system" in Section 3, of this manual.
<Mixing valve> Connect the signal line to open Port A (hot water inlet port) to TBO. 2-3 (Open), the signal line to open Port B (cold water inlet port) to TBO. 2-1 (Close) , and the neutral terminal wire to TBO. 2-2 (N).
<Thermistor> � Do not install the thermistors on the mixing tank. � Install the Zone2 flow temp. thermistor (THW8) near the mixing valve. � The maximum length of the thermistor wiring is 30 m. � The length of the optional thermistors are 5 m. If you need to splice and extend the wirings, following points must be carried out. 1) Connect the wirings by soldering. 2) Insulate each connecting point against dust and water.
NL FTC TBO.2 1 2 3
from mixing tank A
to mixing tank
to Zone2 heat emitter
Motorized mixing
B
valve
from Zone2 heat emitter
Close N Open
18
5 System Set Up
5.4 Indoor unit only operation (during installation work)
In the case when DHW or heating operation is required prior to connection of the
2. To end operation*2
outdoor unit; i.e. during installation work, an electric heater in indoor unit (*1) can be used. *1 Model with electric heater only.
Turn OFF the indoor unit power supply. Turn DIP switch 4-4 and 4-5 OFF. *2 When the indoor unit only operation is ended, ensure to check over the settings
after outdoor unit is connected.
1. To start operation Check if the indoor unit power supply is OFF, and turn DIP switch 4-4 and 4-5 ON. Turn ON the indoor unit power supply.
Note: Prolonged running of this operation may affect the life of the electric heater.
5.5 Smart grid ready
In DHW or heating operation, the commands in the table below can be used.
IN11 OFF (open) ON (short) OFF (open) ON (short)
IN12 OFF (open) OFF (open) ON (short) ON (short)
Meaning Normal operation Switch-on recommendation Switch-off command Switch-on command
TBI.3 4 3 2 1
IN11 IN12
en 5.6 Using SD memory card
The cylinder unit is equipped with an SD memory card interface in FTC. Using an SD memory card can simplify main remote controller settings and can store operating logs. *1
*1 To edit main remote controller settings or to check operating data, an Ecodan service tool (for use with PC) is required.
<Handling precautions> (1) Use an SD memory card that complies with the SD standards. Check that the
SD memory card has a logo on it of those shown to the right. (2) SD memory cards to the SD standards include SD, SDHC, mini SD, micro SD,
and micro SDHC memory cards. The capacities are available up to 32 GB. Choose that with a maximum allowable temperature of 55�C. (3) When the SD memory card is a mini SD, mini SDHC, micro SD, or micro SDHC memory card, use an SD memory card converter adapter. (4) Before writing to the SD memory card, release the write-protect switch.
(5) Before inserting or ejecting an SD memory card, make sure to power off the system. If an SD memory card is inserted or ejected with the system powered on, the stored data could be corrupted or the SD memory card be damaged. *An SD memory card is live for a short duration after the system is powered off. Before insertion or ejection wait until the LED lamps on the FTC control board are all off.
(6) The read and write operations have been verified using the following SD memory cards, however, these operations are not always guaranteed as the specifications of these SD memory cards could change.
Manufacturer Verbatim SanDisk Panasonic Arvato Arvato SanDisk Verbatim Verbatim VANTASTEK
Model #44015 SDSDB-002G-B35 RP-SDP04GE1K 2GB PS8032 TSB 24nm MLC 2GB PS8035 TSB A19nm MLC SDSDUN-008G-G46 #43961 #44018 VSDHC08
Tested in Mar. 2012 Oct. 2011 Oct. 2011 Jun. 2012 Jul. 2014 Oct. 2016 Oct. 2016 Oct. 2016 Sep. 2017
Before using a new SD memory card (including the card that comes with the unit), always check that the SD memory card can be safely read and written to by the FTC controller. <How to check read and write operations>
a) Check for correct wiring of power supply to the system. For more details, refer to section 4.5. (Do not power on the system at this point.)
b) Insert an SD memory card. c) Power on the system. d) The LED4 lamp lights if the read and write operations are successfully
completed. If the LED4 lamp continues blinking or does not light, the SD memory card cannot be read or written to by the FTC controller.
19
(7) Make sure to follow the instruction and the requirement of the SD memory card's manufacturer.
(8) Format the SD memory card if determined unreadable in step (6). This could make it readable. Download an SD card formatter from the following site. SD Association homepage: https://www.sdcard.org/home/
(9) FTC supports FAT file system but not NTFS file system. (10) Mitsubishi Electric is not liable for any damages, in whole or in part, including
failure of writing to an SD memory card, and corruption and loss of the saved data, or the like. Back up saved data as necessary. (11) Do not touch any electronic parts on the FTC control board when inserting or ejecting an SD memory card, or else the control board could fail.
Logos
Capacities 2 GB to 32 GB *2 SD speed classes All � The SD Logo is a trademark of SD-3C, LLC. The mini SD logo is a trademark of SD-3C, LLC. The micro SD logo is a trademark of SD-3C, LLC.
*2 A 2 GB SD memory card stores up to 30 days of operation logs.
5 System Set Up
5.7 Main remote controller
To change the settings of your heating/cooling system please use the main remote controller located on the front panel of the cylinder unit or hydrobox. The following is a guide to viewing the main settings. Should you require more information please contact your installer or local Mitsubishi Electric dealer. Cooling mode is available for ERS series only. However, Cooling mode is not available when the indoor unit is connected to PUHZ-FRP.
A
F1 F2 F3 F4
E
B
C
D
12 15 14 11 1 17 2
3 16
10
9
8
7
6
5
Main screen
<Main remote controller parts>
Letter Name
Function
A Screen
Screen in which all information is displayed
B Menu C Back D Confirm E Power/Holiday
F1-4 Function keys
Access to system settings for initial set up and modifications. Return to previous menu.
Used to select or save. (Enter key)
If system is switched off pressing once will turn system ON. Pressing again when system is switched on will enable Holiday Mode. Holding the button down for 3 seconds will turn the system off. (*1) Used to scroll through menu and adjust settings. Function is determined by the menu screen visible on screen A.
*1 When the system is switched off or the power supply is disconnected, the cylinder unit protection functions (e.g. freeze stat. function) will NOT operate. Please beware that without these safety functions enabled the cylinder unit may potentially become exposed to damage.
en
<Main screen icons>
Icon 1 Legionella
prevention 2 Heat pump
Description When this icon is displayed `Legionella prevention mode' is active.
`Heat pump' is running.
Defrosting
Emergency heating
`Quiet mode' is activated.
3 Electric heater When this icon is displayed the `Electric heaters'
(booster or immersion heater) are in use.
4 Target temperature
Target flow temperature Target room temperature
Compensation curve
5 OPTION
Pressing the function button below this icon will dis-
play the option screen.
6+
Increase desired temperature.
7-
Decrease desired temperature.
8 Z1 Z2
Pressing the function button below this icon switch-
13
es between Zone1 and Zone2.
Information
Pressing the function button below this icon displays
the information screen.
4
9 Space heating/
cooling mode
Heating mode Zone1 or Zone2
Cooling mode
Zone1 or Zone2
10 DHW mode
Normal or ECO mode
11 Holiday mode When this icon is displayed `Holiday mode' activated.
12
Timer
Prohibited
Server control
Stand-by
Stand-by (*2)
Stop
Operating
13 Current temperature
Current room temperature Current water temperature of DHW tank
14
The Menu button is locked or the switching of the
operation modes between DHW and Heating opera-
tions are disabled in the Option screen.(*3)
15
SD memory card is inserted. Normal operation.
SD memory card is inserted. Abnormal operation.
16 Buffer tank control
When this icon is displayed 'Buffer tank control' is active.
17
Smart grid ready
When this icon is displayed, 'Smart grid ready' is active.
*2 This unit is in Stand-by whilst other indoor unit(s) is in operation by priority.
*3 To lock or unlock the Menu, press the BACK and CONFIRM keys simultaneously for 3 seconds.
20
5 System Set Up
[Initial setting wizard]
When the main remote controller is switched on for the first time, the screen automatically goes to Language setting screen , Date/Time setting screen and Main settings menu screen in order. Enter the desired number using the function keys and press CONFIRM.
Note: <HEATER CAPACITY RESTRICTION> This setting restricts the booster heater capacity. It is NOT possible to change the setting after starting up. If you do not have any special requirements (such as building regulations) in your country, skip this setting (select "No").
� [Hot water (DHW/Legionella)] � [Heating]/[Cooling] � [Operation (ON/Prohibited/Timer)] � [Pump speed] � [Heat pump flow rate range] � [Mixing valve control] � [HEATER CAPACITY RESTRICTION]
Initial settings wizard
en
DHW SETTINGS Operation mode
Main Settings Menu
The main settings menu can be accessed by pressing the MENU button. To reduce the risk of untrained end users altering the settings accidentally there are two access levels to the main settings; and the service section menu is password protected.
User Level � Short press If the MENU button is pressed once for a short time the main settings will be displayed but without the edit function. This will enable the user to view current settings but NOT change the parameters.
Installer Level � Long press
If the MENU button is pressed down for 3 seconds the main settings will be dis-
played with all functionality available.
The color of
buttons is inverted, as per figure on right. <Fig. 5.7.1>
The following items can be viewed and/or edited (dependent on access level). � [Domestic Hot water (DHW)] � [Heating/Cooling] � [Schedule timer] � [Holiday mode] � [Initial settings] � [Service (Password protected)]
Skip Comfirm
Main menu Long Press
<Fig 5.7.1>
21
5 System Set Up
<Main Controller Menu Tree> Initial
Main screen
* Short press for 1 Zone system.
F1 *
Information
F4
Option
F1 Forced DHW
F2 DHW
F3 Heating/Cooling
F4 Energy monitor
Menu
Menu
Main menu
Main menu
Hot Water (DHW)
F1 DHW
F3 Legionella
F2 ( EDIT) DHW
Legionella F4 ( EDIT)
ON ( )/OFF
ON ( )/Prohibited ( )/Timer ( )
ON ( )/Prohibited ( )/Timer ( )
Consumed electrical energy
Delivered energy Normal/Eco Active/Non active DHW max. temp. DHW max. temp. drop DHW max. operation time DHW mode restriction DHW recharge Hot water temp. Frequency Start time Max. operation time Duration of max. temp.
Unrestricted access Installer only
Long press
en
F1 (Zone1)
Heating room temp.( ) / Heating flow temp.( ) / Heating compensation curve( ) / Cooling flow temp.
Heating/Cooling
F2 (Zone2) F3 (PREVIEW) F4 ( EDIT)
Heating room temp.( ) / Heating flow temp.( ) / Heating compensation curve( ) / Cooling flow temp.
Compensation curve preview
F1
Compensation curve edit Zone1/2 select
Zone1
F2 F3 F4
Curve parameters Adjustment
Zone2
F2 F3 F4
Curve parameters Adjustment
Schedule2 period preview screen
Schedule timer
F4 ( EDIT)
Schedule2 period setting screen1 F2 F3
F1
Zone1/2 select
Heating
Term setting
F4
F4 Schedule timer preview Day
Zone1
select
F4 Schedule timer preview Zone2
Day select
Schedule1/2 select
Schedule1
F1
Zone1/2 select
Cooling
F4 Schedule timer preview Zone1
F4 Schedule timer preview Zone2
F4 Schedule timer preview
DHW
F1
Zone1/2 select
Heating
F4 Schedule timer preview Zone1
F4 Schedule timer preview Zone2
Day select
Day select
Day select
Day select
Day select
Holiday mode
F3 ( EDIT)
Date/Time
Schedule2
F1
Zone1/2 select
Cooling
F4 Schedule timer preview Zone1
F4 Schedule timer preview Zone2
F4 Schedule timer preview
DHW
DHW
Active/Non active
Heating/
Active/Non active
Cooling Holiday mode setting
F1 F2
Zone1/2 select
Zone1 Zone2
yyyy/mm/dd/hh:mm
Heating room temp.
Heating flow temp. Cooling flow temp. Heating room temp.
Heating flow temp. Cooling flow temp.
Day select
Day select
Day select
save
Time select Temp.setting save
Time select Temp.setting save
Time select Temp.setting save
Time select Temp.setting save
Time select
save
Time select Temp.setting
save
Time select
Temp.setting
save
Time select Temp.setting
save
Time select Temp.setting
save
Time select
save
Language
EN/FR/DE/SV/ES/IT/DA/NL/FI/NO/PT/BG/PL/CZ/RU/TR/SL
Summer time
OFF/ON
Temp. display
OFF/Room/Tank/Room&Tank
Contact number
Initial settings
<Continued to next page.>
Time display �C/�F
Room sensor settings
hh:mm/hh:mm AM/AM hh:mm �C/�F Room RC zone select
F1 F2
Sensor setting Zone1/2 select
Zone1 Zone2
Sensor setting Select Time/Zone Sensor setting Select Time/Zone
TH1/Main RC/ Room RC1-8/ "Time/ Zone" Time setting Sensor setting
TH1/Main RC/ Room RC1-8/ "Time/ Zone" Time setting Sensor setting
22
5 System Set Up
<Continued from the previous page.> <Main Controller Menu Tree>
Initial
Main screen Menu
Main menu
Service
Password protected
en
23
Manual operation Function settings Thermistor adjustment
Auxiliary settings
Heat source setting Pump speed Heat pump settings Operation settings
Unrestricted access Installer only
Long press
Economy settings for pump
ON/OFF Delay
Electric heater (Heating)
ON/OFF Delay
Electric heater (DHW)
ON/OFF (Booster heater/Immersion heater) Delay
Mixing valve control
Running Interval
Flow sensor
Minimum Maximum
Analog output
Priority Interval
Standard (Heat pump & electric heater)/Heater (Electric heater only)/ Boiler/Hybrid (Heat pump & heater/Boiler)
Heat pump flow rate range
Quiet mode
Heating operation
Flow temp.range
Minimum Maximum
Minimum.temp. Maximum.temp.
Room temp.control
H/P thermo diff.adjust
Freeze stat function
Flow t. Ambient
Mode Interval
ON/OFF Lower limit Upper limit
Simultaneous operation
ON/OFF Ambient
Cold weather function Boiler settings *1
ON/OFF Ambient Hybrid settings
Intelligent settings
Outdoor ambient temp.
Priority Energy price
Ambient/ Cost /CO2
Electricity
Boiler
Schedule CO2 emission
Electric Boiler Heat pump capacity
Heat source
Boiler efficiency Booster heater 1 capacity
Booster heater 2 capacity
Smart grid ready
F1 Floor dry up function
(For more details,
refer to Page 26. F4
(
DHW Heating Cooling
Pump cycles ON/OFF Target temp.
Flow temp. (Increase) Flow temp. (Decrease)
ON/OFF Target temp. ON/OFF Target temp. ON/OFF Target temp.
ON/OFF(Heating) ON/OFF(Cooling) Interval
Start & Finish Max. temp. Max. temp. period Temp. increase step Increase interval
Temp. decrease step Decrease interval
Summer mode
ON/OFF
Summer mode
Ambient temp. Judgement time
Ambient(Heating ON) Ambient(Heating OFF) Time(Heating ON) Time(Heating OFF)
Forced heating ON
Ambient
Water flow control
ON/OFF
*1 For more details, refer to the installation manual of PAC-TH012HT-(L)E.
5 System Set Up
<Continued from the previous page.> <Main Controller Menu Tree>
Initial
Main screen Menu
Main menu
Service
Password protected
Unrestricted access Installer only
Long press
Energy monitor settings
Electric heater capacity
Water pump input Delivered energy adjustment Electric energy meter
Booster heater 1 capacity Booster heater 2 capacity Immersion heater Analog output
Pump 1 Pump 2 Pump 3 Pump 4
Heat meter
External input settings Thermo ON output
Demand control (IN4) Outdoor thermostat (IN5) Zone1/Zone2/Zone1&2
OFF (Heat source)/Boiler Heater/Boiler
Commissioning wizard
en
Running information
Thermistor reading
Summary of settings
Error history
Password protection Manual reset
Main controller FTC
Yes/No Yes/No
SD card
SD Main RC Main RC SD
F1 F2 F3 F1 F2 F3
Select download data Select upload data
Domestic Hot Water (DHW)/Legionella Prevention
The domestic hot water and legionella prevention menus control the operation of DHW tank heat ups.
<DHW mode settings> 1. Highlight the hot water icon and press CONFIRM. 2. Use button F1 to switch between Normal and ECO heating modes. 3. To edit the mode, press down the MENU button for 3 seconds, then select "hot
water". 4. Press F2 key to display the Hot Water (DHW) SETTING menu. 5. Use F2 and F3 keys to scroll through the menu selecting each component in
turn by pressing CONFIRM. See the table below for description of each setting. 6. Enter the desired number using the function keys and press CONFIRM.
Menu subtitle
Function
Range Unit
DHW max. temp.
Desired temperature of stored hot water
40 - 60 �C
DHW max. temp. drop Difference in temperature between DHW max. temp. and the temperature at which DHW mode restarts 5 - 30 * �C
DHW max. operation time Max. time allowed for stored water heating DHW mode
30 - 120 min
DHW mode restriction The time period after DHW mode when space heating has priority over DHW mode temporarily pre-
venting further stored water heating
30 - 120 min
(Only when DHW max. operation time has passed.)
* When the DHW max. temp is set over 55�C, the temperature at which DHW mode restarts must be less than 50�C to protect the device.
Default value 50 10 60
30
<Eco mode> DHW mode can run in either `Normal' or `Eco' mode. Normal mode will heat the water in the DHW tank more quickly using the full power of the heat pump. Eco mode takes a little longer to heat the water in the DHW tank but the energy used is reduced. This is because heat pump operation is restricted using signals from the FTC based on measured DHW tank temperature.
Note: The actual energy saved in Eco mode will vary according to outdoor ambient temperature.
<[DHW recharge]> Select the amount of DHW. If you need much hot water, select LARGE, but increase operating costs.
Return to the DHW/legionella prevention menu.
24
5 System Set Up
Legionella Prevention Mode settings (LP mode)
1. Use button F3 to choose legionella mode active YES/NO. 2. To edit the legionella function, press down the MENU button for 3 seconds
and select "hot water", then press F4 key. 3. Use F1 and F2 keys to scroll through the menu selecting each subtitle in turn
by pressing CONFIRM. See the table below for description of each setting. 4. Enter the desired number using the function keys and press CONFIRM.
During Legionella Prevention Mode the temperature of the stored water is increased above 60�C to inhibit legionella bacteria growth. It is strongly recommended that this is done at regular intervals. Please check local regulations for the recommended frequency of heat ups.
Please note that LP mode uses the assistance of electric heaters to supplement the energy input of the heat pump. Heating water for long periods of time is not efficient and will increase running costs. The installer should give careful consideration to the necessity of legionella prevention treatment whilst not wasting energy by heating the stored water for excessive time periods. The end user should understand the importance of this feature. ALWAYS COMPLY WITH LOCAL AND NATIONAL GUIDANCE FOR YOUR COUNTRY REGARDING LEGIONELLA PREVENTION.
Note: When failures occur on the hydrobox, the LP mode may not function normally.
Menu subtitle
Hot water temp. Frequency Start time Max. operation time
en Duration of max. temp.
Function
Desired temp. of stored hot water Time between LP mode DHW tank heat ups Time when LP mode will begin Maximum time allowed for LP mode DHW tank heat The time period after LP mode desired water temp. has been reached
Range
60 - 70 1 - 30 0:00 - 23:00 1 - 5 1 - 120
Unit
�C day
hour min
Default value
65 15 03:00 3 30
[Initial Settings]
From the Initial settings menu the installer can set the following. � [Date/Time] *Be sure to set it to the local standard time. � [Language] � [Summer time] � [Temp. display] � [Contact number] � [Time display] � [�C/�F] � [Room sensor settings]
Follow the procedure described in General Operation for the set up operation. <[Room sensor settings]> For room sensor settings it is important to choose the correct room sensor depending on the heating mode the system will operate in.
Time/Zone schedule setting screen
Menu subtitle Description
Room RC zone select
When 2-zone temperature control is active and wireless remote controllers are available, from Room RC zone select screen, se-
lect zone no. to assign to each main remote controller.
Sensor setting
From sensor setting screen, select a room sensor to be used for monitoring the room temperature from Zone1 and Zone2 separately.
Control option Corresponding initial settings room sensor
(Website manual)
Zone1
Zone2
A
Room RC 1-8 (one each for Zone1 and Zone2)
*1
B
TH1
*1
C
Main remote controller
*1
D
*1
*1
When different
room sensors are used according to
Time/ Zone*2
*1
the time schedule
*1. Not specified (if a locally-supplied room thermostat is used) Room RC 1-8 (one each for Zone1 and Zone2) (if a wireless remote controller is used as a room thermostat)
*2. From sensor setting screen, select Time/Zone to make it possible to use different room sensors according to the time schedule set in the Select Time/ Zone menu. The room sensors can be switched up to 4 times within 24 hours.
[Service] Menu
The service menu provides functions for use by installer or service engineer. It is NOT intended the home owner alters settings within this menu. It is for this reason password protection is required to prevent unauthorised access to the service settings.
The factory default password is "0000". Follow the procedure described in General Operation for the set up operation.
Many functions can not be set whilst the indoor unit is running. The installer should turn off the unit before trying to set these functions. If the installer attempts to change the settings whilst the unit is running the main remote controller will display a reminder message prompting the installer to stop operation before continuing. By selecting "Yes" the unit will cease operation.
<[Manual operation]> During the filling of the system the primary circuit circulation pump and 3-way valve can be manually overridden using manual operation mode. When manual operation is selected a small timer icon appears in the screen. When selected, this function will only remain in manual operation for a maximum of 2 hours. This is to prevent accidental permanent override of the FTC.
Example Pressing F3 button will switch manual operation mode ON for the main 3-way valve. When filling of the DHW tank is complete the installer should access this menu again and press F3 to deactivate manual operation of the part. Alternatively after 2 hours manual operation mode will no longer be active and FTC can resume control of the cylinder unit.
Selected
Running
Error indication
Manual operation menu screen
25
5 System Set Up
Manual operation and heat source setting can not be selected if the system is running. A screen will be displayed asking the installer to stop the system before these modes can be activated. The system automatically stops 2 hours after last operation.
Target flow temp. (�C)
(g) 45
40
(h) (d) (e)
<[Floor dry up function]> The Floor dry up function automatically changes the target hot water temperature in stages to gradually dry concrete when this particular type of underfloor heating system is installed.
Upon completion of the operation the system stops all the operations except the Freeze stat. operation. For Floor dry up function, the target flow temp. of Zone1 is the same as that of Zone2.
35 (c) (b)
30 (f)
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 Days
� This function is not available when a PUHZ-FRP outdoor unit is connected. � Disconnect wiring to external inputs of room thermostat, demand control, and
outdoor thermostat, or the target flow temperature may not be maintained.
Functions
Symbol Description
Option/Range Unit Default
Floor dry up function
a
Set the function to ON and power on the controller, and the dry up heating operation
system using will start.
the
main
remote
On/Off
-- Off
en
Flow temp.
Flow temp. increase step
b Sets the increase step of the target flow temperature.
+1 to +10 �C +5
(increase)
Increase interval
c Sets the period for which the same target flow temperature is maintained. 1 to 7
day 2
Flow temp.
Flow temp. decrease step
d Sets the decrease step of the target flow temperature.
-1 to -10 �C -5
(decrease)
Decrease interval
e Sets the period for which the same target flow temperature is maintained. 1 to 7
day 2
Start & Finish
f Sets the target flow temperature at the start and the finish of the operation. 20 to 60
�C 30
Target temperature Max. target temp. Max. temp. period
g Sets the maximum target flow temperature.
20 to 60
h
Sets the tained.
period
for
which
the
maximum
target
flow
temperature
is
main-
1 to 20
�C 45 day 5
<[Password protection]> Password protection is available to prevent unauthorised access to the service menu by untrained persons.
Resetting the password If you forget the password you entered, or have to service a unit somebody else installed, you can reset the password to the factory default of 0000.
1. From the main settings menu scroll down the functions until Service Menu is highlighted.
2. Press CONFIRM. 3. You will be prompted to enter a password. 4. Hold down buttons F3 and F4 together for 3 seconds 5. You will be asked if you wish to continue and reset the password to default set-
ting. 6. To reset press button F3. 7. The password is now reset to 0000.
<[Manual reset]> Should you wish to restore the factory settings at any time you should use the manual reset function. Please note this will reset ALL functions to the factory default settings.
Password input screen Password verify screen
6 Commissioning
Pre-commissioning exercises- potable/DHW circuit
Initial fill procedure: Ensure all pipe joints and fittings are tight and secure. Open the most distant DHW tap/outlet. Slowly/gradually open the mains water supply to begin filling unit and DHW pipework. Allow most distant tap to run free and release/purge residual air from installation. Close tap/outlet to retain fully charged system. Note: When an immersion heater is fitted, do NOT energise the heater until the DHW tank is full of water. Also do NOT energise any immersion heater if any
sterilisation chemicals remain in the DHW tank as this will cause premature failure of the heater.
Initial flush procedure: Energise system to heat-up cylinder unit contents to a temperature of approx. 30 - 40�C. Flush/drain the water contents to remove any residue/impurities resulting from the installation works. Use the cylinder unit drain cock to safely discharge the warmed water to drain via a suitable hose. On completion, close drain cock, re-fill system and resume system commissioning.
26
7 Service and Maintenance
Error Codes
Code Error
Action
L3
Circulation water temperature overheat protection
Flow rate may be reduced. Check for; � Water leakage � Strainer blockage � Water circulation pump function (Error code may display during filling of
primary circuit, complete filling and reset error code.)
L4
DHW tank water temperature overheat protection
Check the immersion heater and it's contactor.
L5
Indoor unit temperature thermistor (THW1, THW2, THW5A, THW5B, THW6, THW7, THW8, THW9) failure
Check resistance across the thermistor.
L6
Circulation water freeze protection
See Action for L3.
L8
Heating operation error
Check and re-attach any thermistors that may have become dislodged.
L9
Low primary circuit flow rate detected by flow sensor or flow switch (flow switches 1, 2, 3)
See Action for L3. If the flow sensor or flow switch itself does not work, replace it. Caution: The pump valves may be hot, please take care.
LA
en LB
Pressure sensor failure High pressure protection
Check pressure sensor cable for damage or loose connections.
� Flow rate of the heating circuit may be reduced. Check water circuit. � Plate heat exchanger may be clogged. Check the plate heat exchanger. � Outdoor unit failure. Refer to outdoor unit service manual.
Check if the setting temperature of the Boiler for heating exceeds the restriction. (See the manual of the thermistors "PAC-TH012HT-E")
LC
Boiler circulation water temperature overheat protection
Flow rate of the heating circuit from the boiler may be reduced. Check for � water leakage, � strainer blockage � water circulation pump function.
LD
Boiler temperature thermistor (THWB1) failure
Check resistance across the thermistor.
LE
Boiler operation error
See Action for L8. Check the status of the boiler.
LF
Flow sensor failure
Check flow sensor cable for damage or loose connections.
LH
Boiler circulation water freeze protection
LJ
DHW operation error (type of external plate HEX)
LL
Setting errors of DIP switches on FTC control board
LP
Out of water flow rate range for outdoor heat pump unit
P1
Thermistor (Room temp.) (TH1) failure
Flow rate of the heating circuit from the boiler may be reduced. Check for � water leakage � strainer blockage � water circulation pump function.
� Check for disconnection of DHW tank water lower temp. thermistor (THW5B). � Flow rate of the sanitary circuit may be reduced. � Check for water circulation pump function. (primary / sanitary)
For boiler operation, check that DIP SW1-1 is set to ON (With Boiler) and DIP SW2-6 is set to ON (With Mixing Tank). For 2-zone temperature control, check DIP SW2-7 is set to ON (2-zone) and DIP SW2-6 is set to ON (With Mixing Tank).
Check the installation Table 4.3.1 Check remote controller settings (Service menu / heat pump flow rate range) See Action for L3.
Check resistance across the thermistor.
P2
Thermistor (Ref. liquid temp.) (TH2) failure
Check resistance across the thermistor.
P6
Anti-freeze protection of plate heat exchanger
See Action for L3. Check for correct amount of refrigerant.
J0
Communication failure between FTC and wireless receiver
Check connection cable for damage or loose connections.
J1 - J8 Communication failure between wireless receiver and wireless remote controller
Check wireless remote controller's battery is not flat. Check the pairing between wireless receiver to wireless remote controller. Test the wireless communication. (See the manual of wireless system)
E0 - E5 Communication failure between main remote controller and FTC
Check connection cable for damage or loose connections.
E6 - EF Communication failure between FTC and outdoor unit
Check that the outdoor unit has not been turned off. Check connection cable for damage or loose connections. Refer to outdoor unit service manual.
E9
Outdoor unit receives no signal from indoor unit.
Check both units are switched on. Check connection cable for damage or loose connections. Refer to outdoor unit service manual.
EE U*, F*
Combination error between FTC and outdoor unit Outdoor unit failure
Check combination of FTC and outdoor unit. Refer to outdoor unit service manual.
A*
M-NET communication error
Refer to outdoor unit service manual.
Note: To cancel error codes please switch system off (Press button F4(RESET) on main remote controller).
27
7 Service and Maintenance
Annual Maintenance
It is essential that the cylinder unit is serviced at least once a year by a qualified individual. Any required parts should be purchased from Mitsubishi Electric. NEVER bypass safety devices or operate the unit without them being fully operational. For more details, refer to service handbook.
Notes Within the first couple of months of installation, remove and clean the cylinder unit's strainer plus any additional filter items that are fitted external to the
cylinder unit. This is especially important when installing on an old/existing pipe work system. The PRV valve and T&P valve (No. 8, 20 and 21 on Figure 3.1) should be checked annually by turning the knob manually so that the medium is discharged,
thus cleaning the seal seat.
In addition to annual servicing it is necessary to replace or inspect some parts after a certain period of system operation. Please see tables below for detailed instructions. Replacement and inspection of parts should always be done by a competent person with relevant training and qualifications.
Parts which require regular replacement
Parts Pressure relief valve (PRV) Manometer Inlet control group (ICG)*
Replace every Possible failures
6 years
Water leakage
* OPTIONAL PARTS for UK
Parts which require regular inspection
Parts
Check every
Possible failures
Pressure relief valve (3bar) 1 year
PRV would be fixed and
Temperature and pressure ( t u r n i n g t h e k n o b expansion vessel would
relief valve
manually)
burst
Immersion heater
Water circulation pump (Primary circuit)
Earth leakage causing
2 years
circuit breaker to activate
(Heater is always OFF)
en
20,000 hrs (3 years)
Water circulation pump failure
Parts which must NOT be re-used when servicing * O-ring * Gasket
Note: � Always replace the gasket for pump with a new one at each regular main-
tenance (every 20,000 hours of use or every 3 years).
<Draining the cylinder unit and its sanitary heating circuit (local)> WARNING: DRAINED WATER MAY BE VERY HOT 1. Before attempting to drain the cylinder unit isolate from the electrical supply to prevent the immersion and booster heaters burning out. 2. Isolate cold water feed to DHW tank. 3. Open a hot water tap to allow draining without creating a vacuum. 4. Attach a hose to the DHW tank drain cocks (No. 22 and 23 on Figure 7.1). The hose should be able to withstand heat as the draining water could be very hot. The hose
should drain to a place lower than the DHW tank bottom to encourage siphoning. Begin draining by opening drain cock. 5. When the DHW tank is drained close drain cock and hot tap. 6. For primary circuit, attach hose to water circuit drain cocks (No. 6 on Figure 3.1). The hose should be able to withstand heat as the draining water could be very hot. The
hose should drain to a place lower than the drain cock to encourage siphoning. Open the pump valves and the strainer valves. 7. Water remains in the strainer still after the cylinder unit was drained.
Drain the strainer by removing the strainer cover.
22
23
<Figure 7.1>
28
7 Service and Maintenance
Engineers Forms
Should settings be changed from default, please enter and record new setting in `Field Setting' column. This will ease resetting in the future should the system use change or the circuit board need to be replaced.
Commissioning/Field settings record sheet
Main remote controller screen Main
Option Setting DHW
Zone1 heating room temp. Zone2 heating room temp. *1 Zone1 heating flow temp. Zone2 heating flow temp. *2 Zone1 cooling flow temp. *3 Zone2 cooling flow temp. *3 Zone1 heating compensation curve Zone2 heating compensation curve *2 Holiday mode Forced DHW operation DHW Heating/Cooling *3 Energy monitor Operation mode DHW max. temp. DHW temp. drop DHW max. operation time DHW mode restriction
Parameters
Default setting
10�C to 30�C
20�C
10�C to 30�C
20�C
20�C to 60�C
45�C
20�C to 60�C
35�C
5�C to 25�C
15�C
5�C to 25�C
20�C
-9�C to + 9�C
0�C
-9�C to + 9�C
0�C
Active/Non active/Set time
--
On/Off
--
On/Off/Timer
On
On/Off/Timer
On
Consumed electrical energy/Delivered energy
--
Normal/Eco *4
Normal
40�C to 60�C *5
50�C
5�C to 30�C
10�C
30 to 120 min
60 min
30 to 120 min
30 min
DHW recharge
Large/Standard
Standard
en
Legionella prevention
Active
Yes/No
Yes
Hot water temp.
60�C to 70�C *5
65�C
Frequency
1 to 30 days
15 days
Start time
00:00 to 23:00
03:00
Max. operation time
1 to 5 hours
3 hours
Duration of maximum temp.
1 to 120 min
30 min
Heating/Cooling *3
Zone1 operation mode
Heating room temp./ Heating flow temp./ Heating Room temp.
compensation curve/ Cooling flow temp.
Zone2 operation mode *2
Heating room temp./ Heating flow temp./ Heating Compensation
compensation curve/ Cooling flow temp.
curve
Compensation Hi flow temp. set Zone1 outdoor ambient temp.
-30�C to +33�C *6
-15�C
curve
point
Zone1 flow temp. Zone2 outdoor ambient temp. *2
20�C to 60�C -30�C to +33�C *6
50�C -15�C
Zone2 flow temp. *2
20�C to 60�C
40�C
Lo flow temp. set Zone1 outdoor ambient temp.
-28�C to +35�C *7
35�C
point
Zone1 flow temp.
20�C to 60�C
25�C
Zone2 outdoor ambient temp. *2
-28�C to +35�C *7
35�C
Zone2 flow temp. *2
20�C to 60�C
25�C
Adjust
Zone1 outdoor ambient temp.
-29�C to +34�C *8
--
Zone1 flow temp.
20�C to 60�C
--
Zone2 outdoor ambient temp. *2
-29�C to +34�C *8
--
Zone2 flow temp. *2
20�C to 60�C
--
Holiday
DHW
Active/Non active
Non active
Heating/Cooling *3
Active/Non active
Active
Zone1 heating room temp.
10�C to 30�C
15�C
Zone2 heating room temp. *1
10�C to 30�C
15�C
Zone1 heating flow temp.
20�C to 60�C
35�C
Zone2 heating flow temp. *2
20�C to 60�C
25�C
Zone1 cooling flow temp. *3
5�C to 25�C
25�C
Zone2 cooling flow temp. *3
5�C to 25�C
25�C
Initial settings
Language
EN/FR/DE/SV/ES/IT/DA/NL/FI/NO/PT/BG/PL/ EN
�C/�F
CZ/RU/TR/SL
�C/�F
�C
Summer time
On/Off
Off
Temp. display
Room/DHW tank/Room&DHW tank /Off
Off
Time display
hh:mm/hh:mm AM/AM hh:mm
hh:mm
Room sensor settings for Zone1
TH1/Main RC/Room RC1-8/"Time/Zone"
TH1
Room sensor settings for Zone2 *2
TH1/Main RC/Room RC1-8/"Time/Zone"
TH1
Room RC zone select *2
Zone1/Zone2
Zone1
Service menu
Thermistor
THW1
-10�C to +10�C
0�C
adjustment
THW2
-10�C to +10�C
0�C
THW5A
-10�C to +10�C
0�C
THW5B
-10�C to +10�C
0�C
THW6
-10�C to +10�C
0�C
THW7
-10�C to +10�C
0�C
THW8
-10�C to +10�C
0�C
THW9
-10�C to +10�C
0�C
THW10
-10�C to +10�C
0�C
THWB1
-10�C to +10�C
0�C
Auxiliary settings Economy settings for On/Off *9
On
pump. Electric heater
Delay (3 to 60 min) Space heating: On (used)/Off (not used)
10 min On
(Heating) Electric heater (DHW)
Mixing valve control
Flow sensor *10
Analog output
Electric heater delay timer (5 to 180 min)
30 min
Booster heater DHW: On (used)/Off (not used) On
Immersion heater DHW: On (used)/Off (not used) On
Electric heater delay timer (15 to 30 min)
15 min
Running (10 to 240 sec)
120 sec
Interval (1 to 30 min)
2 min
Minimum (0 to 100 L/min)
5 L/min
Maximum (0 to 100 L/min)
100 L/min
Interval (1 to 30 min)
5 min
Priority (Normal/High)
Normal
Field setting Notes
(Continued to next page.)
29
7 Service and Maintenance
Engineers Forms
Commissioning/Field settings record sheet (continued from the previous page)
Main remote controller screen
Parameters
Default setting
Field setting
Notes
Setting Service menu Pump speed
DHW
Pump speed (1 to 5)
5
Heating/Cooling
Pump speed (1 to 5)
5
Heat source setting
Standard/Heater/Boiler/Hybrid *11
Standard
Heat pump setting
Heat pump flow rate range Minimum (0 to 100 L/min)
5 L/min
Maximum (0 to 100 L/min)
100 L/min
Quiet mode
Day (Mon to Sun)
--
Time
0:00 to 23:45
Quiet level (Normal/ Level1/ Level2)
Normal
Operation Heating operation Flow temp.range
settings
*13
Minimum.temp. (20 to 45�C) Maximum.temp. (35 to 60�C)
30�C 50�C
Room temp.control Mode (Normal/Fast)
Normal
*14
Interval (10 to 60 min)
10 min
Heat pump thermo On/Off *9
On
diff.adjust
Lower limit (-9 to -1�C)
-5�C
Upper limit (+3 to +5�C)
5�C
Freeze stat function *15
Outdoor ambient temp. (3 to 20�C) / **
5�C
Simultaneous operation (DHW/Heating) On/Off *9 Outdoor ambient temp. (-30 to +10�C) *6
Off -15�C
en
Cold weather function
On/Off *9
Off
Outdoor ambient temp. (-30 to -10�C) *6
-15�C
Boiler operation
Hybrid settings Outdoor ambient temp.
-15�C
(-30 to +10�C) *6
Priority mode (Ambient/Cost/
Ambient
CO2) *16 Outdoor ambient temp. rise
+3�C
(+1 to +5�C)
Intelligent set- Energy Electricity
0.5 */kWh
tings
price (0.001 to 999 */kWh)
*17
Boiler
0.5 */kWh
(0.001 to 999 */kWh)
CO2 emission
Electricity (0.001 to 999 kg -CO2/ kWh)
0.5 kg -CO2/kWh
Boiler
0.5 kg -CO2/kWh
(0.001 to 999 kg -CO2/
kWh)
Heat Heat pump capacity 11.2 kW
source (1 to 40 kW)
Boiler efficiency
80%
(25 to 150%)
Booster heater 1
2 kW
capacity
(0 to 30 kW)
Booster heater 2
4 kW
capacity
(0 to 30 kW)
Smart grid ready
DHW
On/Off
Off
Target temp (+1 to +20�C) / -- (Non active)
--
Heating
On/Off
Off
Target temp. Switch-on recommendation (20 to 60�C) 50�C
Switch-on command (20 to 60�C) 55�C
Cooling
On/Off
Off
Target temp. Switch-on recommendation (5 to 25�C) 15�C
Switch-on command (5 to 25�C) 10�C
Pump cycles
Heating (On/Off)
On
Cooling (On/Off)
On
Interval (10 to 120 min)
10 min
Floor dry up function
On/Off *9
Off
Target temp. Start&Finish (20 to 60�C)
30�C
Max. temp. (20 to 60�C)
45�C
Max. temp. period (1 to 20 days) 5 days
Flow temp.
Temp. increase step (+1 to +10�C) +5�C
(Increase)
Increase interval (1 to 7 days) 2 days
Flow temp. (Decrease)
Temp. decrease step (-1 to -10�C) -5�C Decrease interval (1 to 7 days) 2 days
Summer mode
On/Off Outdoor ambient temp.
Heating ON (4 to 19�C) Heating OFF (5 to 20�C)
Off 10�C 15�C
Judgement time
Heating ON (1 to 48 hours) Heating OFF (1 to 48 hours)
6 hours 6 hours
Forced heating ON (-30 to 10�C)
5�C
Water flow control
On/Off
Off
(Continued to next page.)
30
7 Service and Maintenance
Engineers Forms
Commissioning/Field settings record sheet (continued from the previous page)
Main remote controller screen
Parameters
Service menu
Energy monitor settings
Electric heater capacity
Booster heater 1 capacity Booster heater 2
0 to 30 kW 0 to 30 kW
capacity
Immersion heater 0 to 30 kW
capacity
Analog output
0 to 30 kW
Delivered energy adjustment Water pump input Pump 1
-50 to +50% 0 to 200 W or ***(factory fitted pump)
Pump 2
0 to 200 W
Pump 3
0 to 200 W
Pump 4
0 to 200 W
Electric energy meter *12
0.1/1/10/100/1000 pulse/kWh
Heat meter *12
0.1/1/10/100/1000 pulse/kWh
External in- Demand control (IN4) put settings
Heat source OFF/Boiler operation
Outdoor thermostat (IN5)
Heater operation/Boiler operation
en
Default setting
Field setting
Notes
2 kW
4 kW
0 kW
0 kW 0% *** 0 W 0 W 72 W 1000 pulse/kWh 1000 pulse/kWh Boiler operation Boiler operation
Thermo ON output
Zone1/Zone2/Zone1&2
Zone1&2
*1 The settings related to Zone2 can be switched only when 2-zone temperature control or 2-Zone valve ON/OFF control is active. *2 The settings related to Zone2 can be switched only when 2-zone temperature control is enabled (when DIP SW2-6 and SW 2-7 are ON). *3 Cooling mode settings are available for ER model only. *4 When the cylinder unit is connected with a PUMY-P outdoor unit, the mode is fixed to "Normal". *5 For the model without both booster and immersion heater, it may not reach the set temperature depending on the outside ambient temperature. *6 The lower limit is -15�C depending on the connected outdoor unit. *7 The lower limit is -13�C depending on the connected outdoor unit. *8 The lower limit is -14�C depending on the connected outdoor unit. *9 On: the function is active; Off: the function is inactive. *10 Do not change the setting since it is set according to the specification of flow sensor attached to the cylinder unit. *11 When DIP SW1-1 is set to OFF "WITHOUT Boiler" or SW2-6 is set to OFF "WITHOUT Mixing tank", neither Boiler nor Hybrid can be selected. *12 The default setting is 1 pulse/kWh depending on the connected indoor unit. *13 Valid only when operating in Heating room temperature. *14 When DIP SW5-2 is set to OFF, the function is active. *15 If asterisk (**) is chosen freeze stat function is deactivated. (i.e. primary water freeze risk) *16 When the cylinder unit is connected with a PUMY-P outdoor unit, the mode is fixed to "Ambient". *17 "*" of "*/kWh" represents currency unit (e.g. or � or the like)
31
EC DECLARATION OF CONFORMITY EG-KONFORMIT�TSERKL�RUNG D�CLARATION DE CONFORMIT� CE EG-CONFORMITEITSVERKLARING DECLARACI�N DE CONFORMIDAD CE DICHIARAZIONE DI CONFORMIT� CE
DECLARA��O DE CONFORMIDADE CE
EU-OVERENSSTEMMELSESERKL�RING
EG-DEKLARATION OM �VERENSST�MMELSE EC DEKLARACJA ZGODNOCI WE
CE-ERKL�RING OM SAMSVAR
EY-VAATIMUSTENMUKAISUUSVAKUUTUS ES PROHL�SEN� O SHOD VYHL�SENIE O ZHODE ES EK MEGFELELS�GI NYILATKOZAT IZJAVA O SKLADNOSTI ES
DECLARAIE DE CONFORMITATE CE E� VASTAVUSDEKLARATSIOON EK ATBILSTBAS DEKLARCIJA EB ATITIKTIES DEKLARACIJA
EC IZJAVA O SUKLADNOSTI
EZ IZJAVA O USAGLASENOSTI
MITSUBISHI ELECTRIC AIR CONDITIONING SYSTEMS EUROPE LTD. NETTLEHILL ROAD, HOUSTOUN INDUSTRIAL ESTATE, LIVINGSTON, EH54 5EQ, SCOTLAND, UNITED KINGDOM
hereby declares under its sole responsibility that the heating system components described below for use in residential, commercial and light-industrial environments: erkl�rt hiermit auf seine alleinige Verantwortung, dass die unten beschriebenen Zubeh�rteile f�r das Heizungs-System zur Benutzung im h�uslichen, kommerziellen und leicht-industriellen Umfeld: d�clare par la pr�sente et sous son enti�re responsabilit� que les composants du syst�me de chauffage d�crits ci-dessous pour l'utilisation dans des environnements r�sidentiels, commerciaux et d'industrie l�g�re : verklaart hierbij als enige verantwoordelijke dat de componenten van het verwarmingssteem die hieronder worden beschreven, bedoeld zijn voor gebruik in woonomgevingen en in commerci�le en licht industri�le omgevingen: declara por la presente bajo su responsabilidad exclusiva que los componentes del sistema de calefacci�n descritos a continuaci�n para su uso en zonas residenciales, comerciales y para la industria ligera: con la presente dichiara, sotto la sua esclusiva responsabilit�, che i componenti dell'impianto di riscaldamento descritto di seguito, destinato all'uso in ambienti residenziali, commerciali e industriali: , . atrav�s da presente declara sob sua �nica responsabilidade que os componentes do sistema de aquecimento abaixo descritos para uso residencial, comercial e de ind�stria ligeira: erkl�rer hermed under eneansvar, at de herunder beskrevne komponenter til opvarmning til brug i privat boligbyggeri, erhvervsomr�der og inden for let industri: intygar h�rmed att uppv�rmningssystemkomponenterna som beskrivs nedan �r f�r anv�ndning i bost�der, kommersiella milj�er och l�tt industri: , - , : niniejszym owiadcza na swoj wylczn odpowiedzialno, e klimatyzatory i pompy ciepla opisane poniej, s przeznaczone do zastosowa w rodowisku mieszkalnym, handlowym i lekko uprzemyslowionym: erkl�rer hermed som sitt ansvar, ene og alene, at komponentene i varmesystemet som beskrives nedenfor og som er beregnet for bruk i bolig-, forretnings- og lettindustrimilj�er: vakuuttaa t�ten asiasta yksin vastuussa, ett� alla kuvatut l�mmitysj�rjestelm�n osat, jotka on tarkoitettu k�ytett�viksi asuin-, toimisto- ja kevyen teollisuuden ymp�rist�iss�: t�mto na vlastn� odpovdnost prohlasuje, ze n�ze popsan� klimatizacn� jednotky a tepeln� cerpadla pro pouzit� v obytn�ch prosted�ch, komercn�ch prosted�ch a prosted�ch lehk�ho prmyslu: t�mto vyhlasuje na vlastn� zodpovednos, ze komponenty vykurovacieho syst�mu op�san� nizsie pre pouzitie v obytn�ch, komercn�ch a ahk�ch priemyseln�ch oblastiach: ezennel kiz�r�lagos felelss�ggel kijelenti, hogy az al�bbiakban le�rt, lak�-, kereskedelmi �s k�nnyipari k�rnyezetben haszn�lhat� ftrendszer alkatr�szei: s tem izrecno izjavljamo, da so spodaj opisane komponente ogrevalnega sistema za uporabo v stanovanjskih, poslovnih in lahkoindustrijskih okoljih: Prin prezentul document, compania declar pe propria rspundere c piesele sistemului de �nclzire descrise mai jos sunt potrivite pentru utilizarea �n medii rezideniale, comerciale i uor industriale: kinnitab oma ainuvastutusel, et allpool kirjeldatud k�ttes�steemi komponendid on m�eldud kasutamiseks elu-, kaubandus- ja kerget��stuskeskkonnas: ar so pilnb atbild par to, ka tlk apraksttie apsildes sistmas komponenti, kas izmantojami dzvojams, komercils un viegls industrils vids: prisiimdamas vis atsakomyb pareiskia, kad zemiau aprasyti sildymo sistemos komponentai skirti naudoti gyvenamojoje, komercinje ir lengvosios pramons aplinkose: ovime izjavljuje pod iskljucivo svojom odgovornosu da dolje opisane komponente sustava za grijanje za upotrebu u stambenim, komercijalnim i lakoindustrijskim okruzenjima: ovim izjavljujemo pod svojom iskljucivom odgovornosu da su opisane komponente sistema grejanja za upotrebu u stambenim, poslovnim i lakim industrijskim okruzenjima:
MITSUBISHI ELECTRIC, EHPT20X-MHEDW
Note: Its serial number is on the nameplate of the product.
Hinweis: Die Seriennummer befindet sich auf dem Kennschild des Produkts. Remarque : Le num�ro de s�rie de l'appareil se trouve sur la plaque du produit.
Opmerking: het serienummer staat op het naamplaatje van het product.
Nota: El n�mero de serie se encuentra en la placa que contiene el nombre del producto.
Nota: il numero di serie si trova sulla targhetta del prodotto.
: . Nota: o n�mero de s�rie encontra-se na placa que cont�m o nome do produto.
Bem�rk: Serienummeret st�r p� produktets fabriksskilt.
Obs: Serienumret finns p� produktens namnpl�t. : . Uwaga: Numer seryjny znajduje si na tabliczce znamionowej produktu.
Directives Richtlinien Directives Richtlijnen Directivas Direttive
Directivas
Direktiver
Direktiv
Dyrektywy
2014/35/EU: Low Voltage 2006/42/EC: Machinery 2014/30/EU: Electromagnetic Compatibility 2009/125/EC: Energy-related Products Directive and Regulation (EU) No 813/2013 2011/65/EU, (EU) 2015/863 and (EU) 2017/2102: RoHS Directive
Merk: Serienummeret befinner seg p� navneplaten til produktet. Huomautus: Sarjanumero on merkitty laitteen arvokilpeen.
Pozn�mka: P�slusn� s�riov� c�slo se nach�z� na st�tku produktu. Pozn�mka: V�robn� c�slo sa nach�dza na typovom st�tku v�robku. Megjegyz�s: A sorozatsz�m a term�k adatt�bl�j�n tal�lhat�. Opomba: serijska stevilka je zapisana na tipski ploscici enote. Not: Numrul de serie este specificat pe plcua indicatoare a produsului. M�rkus. Seerianumber asub toote andmesildil.
Piezme. Srijas numurs ir nordts uz ierces datu plksntes. Pastaba. Serijos numeris nurodytas gaminio vardini duomen lentelje. Napomena: serijski broj nalazi se na natpisnoj plocici proizvoda. Napomena: Serijski broj nalazi se na nazivnoj plocici proizvoda.
Direktiver
Direktiivit
Smrnice Smernice
Ir�nyelvek Direktive
Directive Direktiivid Direktvas Direktyvos Direktive Direktive
Issued UNITED KINGDOM
1 August 2020
Atsushi EDAYOSHI Manager, Quality Assurance Department
Please be sure to put the contact address/telephone number on this manual before handing it to the customer.
RG79F364L04
HEAD OFFICE: TOKYO BUILDING, 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
Printed in the UNITED KINGDOM
