Relay and Timer Specifications Technical Data

Rockwell Automation

Relay and Timer Specifications Technical Data - Literature ...

Rockwell Automation Publication 700-TD552F-EN-P - January 2021 ... Options: LED, push-to-test and manual override, socket-mounted surge ...

Relay and Timer Specifications Technical Data

4 Rockwell Automation Publication 700-TD552F-EN-P - January 2021. Relay and Timer Specifications. Contact Data Tables.

PDF preview unavailable. Download the PDF instead.

700-td552 -en-p
Technical Data
Original Instructions

Relay and Timer Specifications
Bulletin 700

Topic

Page Topic

Page

Summary of Changes

2

Solid-state Relays

233

General Information

3

700-SA Tube Base Relays

237

General Purpose Relays

9

700-SC Ice Cube Relays

240

700-HA General-purpose Relay

12 700-SF Square Base Relays

245

700-HB Square Base Relay

22 700-SH Hockey Puck Relays

249

700-HD Flange Mount Square Base Relay

28 700-SK Slim Line Relays

258

700-HF Square Base Relay

32

700-HC Miniature Ice Cube Relay

39

700-HK Slim Line Relay

44

700-HL Terminal Block Relay

50

700-HL 2-pole Terminal Block Relay

56

700-HLF Terminal Block Timing Relay

60

700-HP Slim Line Relay

64

700-HPS Safety Control Relay

65

700-HJ Magnetic Latching Relay

71

700-HG Power Relay

75

700-HHF Flange Mount Power Relay

80

700-HTA Alternating Relay

83

General Purpose Electronic Timers and Counters

89

700-FE Economy Timing Relay

92

700-FS High Performance Timing Relay

96

700-HNC Miniature Timing Relay

103

700-HNK Ultra-Slim Timing Relay

109

700-HR Dial Timing Relays

116

700-HT Plug-in Timing Relay

128

700-HV Timing Relay

133

700-HX Multi-Function Digital Timing Relay

138

NEMA Industrial Relays

149

700-P Industrial Relays

151

700S-P and 700S-PK -- Heavy-Duty Safety Control Relays

167

700-N Industrial Relays

172

700-R Sealed Switch Relays

176

700-RTC -- Solid-State Timing Relay

181

IEC Control Relays

187

700-CF Control Relay

188

700S-CF Control Relays

208

700-EF Control Relay

213

700S-EF Control Relays

221

700-K Miniature Control Relays

225

Relay and Timer Specifications Technical Data

Summary of Changes

This publication contains the following new or updated information. This list includes substantive updates only and is not intended to reflect all changes.

Topic

Page

Added 700-EF Control Relay

213

Added 700S-EF Control Relays

221

2

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

General Information
Contact Data Tables

Relay Contact

Contact

Type Arrangement Style

Contact Material

NEMA Pilot Duty(1)

AC and DC Switching Capability

1 mA

20 50 mA mA

100 mA

1A 3A

5 A 10 A 20 A 25 A 30 A 35 A

700-CF

Up to 8 form X or 8 form Y

cross stamped Ag

A600 P600

24V

700S-CF

Up to 8 form X or 8 form Y

cross stamped Ag

A600 24 P600 V

AC DC
AC DC

IEC Relays

700-K

Up to 8 form X or 8 form Y

bifurcated

AgCu

A300 Q300

17V

AC
DC

700-P

Up to 12 form X or 8 form Y

bifurcated

NiAg

A600 P600

700-PK

Up to 12 form X or 8 form Y

single

AgCdO

2X A600 2X P600

NEMA Relays

700-PH

Up to 6 form X or 4 form Y

tandem

AgCdO

A600 P600

700-R

Up to 8 form A or form B

sealed sw.

W

B300 C600 5V P300

700-RTC

Up to 4 form A or form B

sealed sw.

W

700S-P

Up to 12 form X or 8 form Y

bifurcated

NiAg

(1) See NEMA Ratings and Test Values on page 5

B600 P300

5V

A600 P600

10V 10V 10V
10V

AC DC

DC

AC

(20 A Lighting Load)

AC

DC

(35 A Lighting Load)

AC DC

AC DC
AC

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

3

Relay and Timer Specifications

Contact Data Tables

Relay Contact

Contact

Type Arrangement Style

Contact Material

NEMA Pilot Duty

1 mA

10 50 mA mA

AC and DC Switching Capability

100 mA

1A 3A

5 A 10 A 20 A 25 A 30 A 35 A

Timing Relays

General Purpose Relays

700-FE 1 N.O.

single AgCdO D300

10V

700-FS 1, 2 form C single AgCdO B300

10V

700-HA 2, 3 form C single AgNi B300

10V

700-HAX 2, 3 form C bifurcated Au/AgNi B300 6V

700-HB 2, 3 form C single AgNi B300

10V

700-HC14 4 form C 700-HC22 2 form C 700-HC24 4 form C

single

Ag/Au

C300 Q300 10V

single

AgNi

B300 Q300

10V

single

AgNi

C300 Q300

10V

700-HD 2, 3 form C single AgCdO B300

10V

700-HF 2, 3, 4 form C single

700-HG
700HHF45

1 form X, 1 form C, 2 form A, 2 single
form C

1 form X

single

700HHF62

2 form C

single

700HHF73

3 form C

single

AgCdO B300 AgNi A600 AgNi A600 AgNi B600 AgNi B300

700-HJ 1, 2 form C single AgCdO --

700-HK36 1 form C

700-

1 form C

700-HK32 2 form C

700-

2 form C

single AgNi B300 single Au/AgNi B300 single AgNi B300 single Au/AgNi B300

10V 10V 10V 10V
10V 10V 10V 5V

AC DC (24V Max.)
AC DC (24V Max.)
AC DC (24V Max)
AC DC (24V Max)
AC DC (24VMax.)
AC DC (30V Max.)
AC DC
AC DC (30V Max.)
AC DC (24V Max)
AC DC (30V Max)
AC DC (28V Max)
AC DC (28V Max)
AC DC (28V Max)
AC DC (28V Max)
AC DC (24V Max.)
AC DC (30V Max)
AC DC (30V Max)

4

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

Contact Data Tables

Relay Type

Contact Arrangement

Contact Style

Contact Material

NEMA Pilot Duty

AC and DC Switching Capability

1 mA

10 50 mA mA

100 mA

1A 3A

5 A

10 A

20 A 25 A 30 A 35 A

General Purpose Relays (continued)

700-HLS 700-HLT 700-HLT_ _X 700-HP 700-HPX

Solid-State 1 N.O.

--

1 Form C

single

1 Form C

single

2 Form C

single

2 Form C

single

--

--

AgSnO B300 R300

AgSnO B300 R300

AgNi

B300

Q300

AgNi + B300 Gold Q300

3V
12V
8V
5V (300 mW) 5V (50 mW)

700-HS

2 Form C

single AgCdO B300

10V

AC/ DC

6 A

AC/DC

6 A

AC/DC

8 A

AC/DC

8 A

AC/DC

AC (30V DC Max)

700-HT

2 form C

single AgNi B300

10V

AC

(30V

DC

Max)

NEMA Ratings and Test Values
NEMA Ratings and Test Values for AC Control Circuit Contacts at 50 or 60 Hz

Maximum Current [A]

NEMA Contact Rating Thermal Continuous 120V

Designation

Test Current [A]

Make

A150

10

60

A300

10

60

A600

10

60

B150

5

30

B300

5

30

B600

5

30

C150

2.5

15

C300

2.5

15

C600

2.5

15

D150

1.0

3.60

D300

1.0

3.60

D600

0.5

1.80

2X A300

20

120

2X A600

20

120

Break
6.00 6.00 6.00 3.00 3.00 3.00 1.50 1.50 1.50 0.60 0.60 0.30 12 12

240V

Make Break

--

--

30

3.00

30

3.00

--

--

15

1.50

15

1.50

--

--

7.5

0.75

7.5

0.75

--

--

1.8

0.30

--

--

60

6.00

60

6.00

480V

Make Break

--

--

--

--

15

1.50

--

--

--

--

7.5

0.75

--

--

--

--

3.75

0.375

--

--

--

--

--

--

--

--

30

3.00

600V

Make Break

--

--

--

--

12

1.20

--

--

--

--

6

0.60

--

--

--

--

3

0.30

--

--

--

--

--

--

--

--

24

2.40

VA

Make Break

7200

720

7200

720

7200

720

3600

360

3600

360

3600

360

1800

180

1800

180

1800

180

432

72

432

72

216

36

14400 1440

14400 1440

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

5

Relay and Timer Specifications

NEMA Ratings and Test Values for DC Control Circuit Contacts

Maximum Current [A]

NEMA Contact Rating Designation Thermal Continuous Test Current [A] 5...28V

125V

250V

301...600V

N150

10

N300

10

N600

10

P150

5.0

P300

5.0

P600

5.0

Q300

2.5

Q600

2.5

2X P600

10

10

2.2

--

--

10

2.2

1.1

--

10

2.2

1.1

0.40

5.0

1.1

--

--

5.0

1.1

0.55

--

5.0

1.1

0.55

0.20

2.5

0.55

0.27

0.11

2.5

0.55

0.27

0.11

10

2.2

1.1

0.40

Make or Break at 300V or less [VA]
275 275 275 138 138 138 69 69 275

NEMA Definitions for Contact Arrangements

Contact

Description

Arrangement

Form A

A Form A contact arrangement is one that has single-pole, single-throw, normally open contacts. The function of this arrangement is to close a circuit when actuated.

Diagram

Form B

A Form B contact arrangement is one that has single-pole, single-throw, normally closed contacts. The function of this arrangement is to open a circuit when actuated.

Form C

A Form C contact arrangement is one that has single-pole, double-throw contacts with three terminals - one for normally open, one for normally closed, and one common. The function of this arrangement is to transfer a circuit when actuated.

Form X

A Form X contact arrangement is one that has single-pole, single-throw, normally open double-make contacts. The function of this arrangement is to close a circuit when actuated.

or

Form Y

A Form Y contact arrangement is one that has single-pole single-throw normally closed double-break contacts. The function of this arrangement is to open a circuit when actuated.

or

Form Z

A Form Z contact arrangement is one that has single-pole, double-throw, contacts with four terminals -- two for normally open and two for normally closed. The function of this arrangement is to open one circuit and close the other.

6

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

Timing Relay Selection Criteria
Single Function Timers: Timers that have only 1 timing mode (for example, ON-Delay or OFF-Delay). Multi-Function Timers: Timers that have 4...8 timing modes that are selected by turning the mode selection switch.
RESET

ON-Delay or (Delay on Operate)
When power is applied continuously (or when power and a start signal are applied), the timing cycle begins. The output contacts change state after the time delay is completed. The contacts will return to their normal state when a reset signal is applied or power is removed.

POWER

ON

OFF

START SIGNAL

ON

OFF

OUTPUT CHANGED STATE NORMAL STATE

TIME DELAY

RESET

OFF-Delay or (Delay on Release)
Power is applied continuously. When a start signal is applied, the output contacts change state immediately. When the start signal is removed, the timing cycle begins. The output contacts will return to their normal state once the time delay is completed. Reset will occur when a reset signal is applied or power is removed.

POWER

ON

OFF

START SIGNAL

ON

OFF

OUTPUT CHANGED STATE NORMAL STATE

TIME DELAY

RESET

One Shot or (Repeat Cycle)
Power is applied continuously. When a start signal is applied, the output contacts change state immediately and the timing cycle begins. The output contacts will return to their normal state once the time delay is completed. Reset will occur when a reset signal is applied or power is removed.

POWER

ON

OFF

START SIGNAL

ON

OFF

OUTPUT CHANGED STATE NORMAL STATE

TIME DELAY

Repeat Cycle or (Flicker)
Power is applied continuously. When a start signal is applied, the timing cycle begins. When the time delay is completed, the output contacts change state and the next timing cycle begins. This cycle will repeat until a reset signal is applied or power is removed.

POWER

ON

OFF

START SIGNAL

ON

OFF

OUTPUT CHANGED STATE NORMAL STATE

RESET

OFF ON OFF ON OFF TIME TIME TIME TIME TIME

Flexibility
Mounting -- Timing relays are available in several different models. They can be plugged into the same socket as the relay, or use a separate plug-in socket mounting.
Contacts -- The contacts are of various types and ratings. See the appropriate specification pages for more details.
Functionality -- Timing relays with multi-range and multi-function capability are available. Allowing you to stock one relay to cover a wide variety of applications.
External Trigger Switch -- OFF-Delay, One-Shot, and other timer functions require an external trigger switch (from a relay or push button) to control the timing function. The external trigger switch will cause the timing function to start. In OFF-Delay, the trigger switch closes to energize the output and when the trigger switch opens the OFF-Delay starts to time out. At the end of the time delay, the output is de-energized and the output contacts return to their shelf state

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

7

Relay and Timer Specifications
Surge Suppression Information
Photo
700-CF Relay

Cat. No.

For use with

Suppression Technique

700-ADR 700-ADL1 700-ADL1R 700-ADL2 700-ADL2R 700-ADL3 700-ADL3R 700-AR1 700-AR2 700-AV1R 700-AV3R 700-CF built-in 100-FSC 100-FSV
100-FSD

700-HA, -HB,-HK, -HP (6...220V DC) 700-HC (6...24V DC) 700-HB, -HA, -HK, -HP (6...24V DC) 700-HC (28...60V DC) 700-HB, -HA, -HK, -HP (28...60V DC) 700-HC (110...220V DC) 700-HB, -HA, -HK, -HP (110...220V DC) 700-HB, -HA, -HC,-HK, -HP (6...24V AC/DC) 700-HB,-HA, -HC,-HK, -HP (110...240V AC/DC) 700-HB,-HA, -HC,-HK, -HP (6...24V AC) 700-HB, -HA, -HC, -HK, -HP (110...240V AC) -- 100C, 700-CF 100C, 700-CF

Diode Diode + LED Diode + LED Diode + LED Diode + LED Diode + LED Diode + LED RC RC Varistor + LED Varistor + LED Diode R-C Ckt MOV

100C, 700-CF

Diode

Max. Relay Contact Dropout Time
3X 3X 3X 3X 3X 3X 3X No Effect No Effect No Effect No Effect -- No Effect No Effect

Max. Transient Voltage Relative to System Voltage
-- -- -- -- -- -- -- 3 -- -- -- 6...10X 3X --

70...95 ms 6...10X

100-JE

100C, 700-CF

Diode

5X

6...10X

700-R Relay
8

700-N5

700-P, 700-N

RC

No effect 3X

700-N24

700-P, 700-N

RC

700-R built-in

--

Diode

199-FSMA1, FSMA2 700-P, 700-H, 700-CF, 700DC-R

RC

199-FSMA9, 10, 11 700-P, 700-H, 700-CF, 700DC-R

MOV

199-FSMZ

700-P, 700-H, 700-CF, 700DC-R

Diode

No effect 3X

-- No effect No effect

6...10X 3X --

5X

--

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

General Purpose Relays
Product Overview

Relay and Timer Specifications

Bulletin No. Type
Features
Contact Ratings Contact Form Contact Type Contact Material Operating Current, Under Resistant Load, Max Permissible Load, min Coil Ratings
Coil Voltage
Permissible Coil Voltage Variation Electrical Ratings Dielectric Withstand Voltage Electrical Service Life (Cycles) Reference Certifications Socket Catalog Numbers Page

700-HA
General-purpose Relay
· Pin-style terminals · Standard ON/OFF flag indicator · Electrical schematic on face · Clear cover for visual inspection · Optional push-to-test and manual
override · Optional LED

700-HB

700-HD

700-HF

General-purpose Relay

General-purpose Relay

General-purpose Relay

· Blade-style quick connect terminals · Standard ON/OFF flag indicator · Electrical schematic on face · Clear cover for visual inspection · Optional push-to-test and manual
override · Optional LED

· Flange-mounted · Blade-style quick connect terminals · Clear cover for visual inspection

· Square-base · Plug-in quick connect solder terminals · Optional push-to-test · Optional LED

DPDT, 3PDT Single AgNi, AgNi + Gold
700-HA: 10 A 700-HAX: 6 A
700-HA: 10V, 5 mA 700-HAX: 6V 1 mA

DPDT, 3PDT Single AgCdO 15 A
10V, 10 mA

DPDT, 3PDT Single AgCdO 15 A
10V, 10 mA

DPDT, 4 PDT Single AgCdO 10 A
5V, 100 mA

AC: 6, 12, 24, 48, 110, 120, 230, 240, 277V
DC: 6, 12, 24, 36, 48, 60, 80, 110, 125, 140, 220V

AC: 6, 12, 24, 120, 240V DC: 6, 12, 24, 48, 110V

80...110% of nom voltage at 50 Hz 80...110% of nom voltage at 60 Hz 80...110% of nom voltage at DC

AC: 6, 12, 24, 120, 208, 240V DC: 6, 12, 24, 48, 110V

AC: 6, 12, 24, 120, 240V DC: 6, 12, 24, 48, 110V
85...110% of nom voltage at 50 Hz 85...110% of nom voltage at 60 Hz 80...110% of nom voltage at DC

Pole-to-pole: 2000V Contact-to-coil: 2000V Contact-to-frame: 2000V
100,000 min

Pole-to-pole: 2500V Contact-to-coil: 4000V Contact-to-frame: 2500V
100,000 min

Pole-to-pole: 2500V Contact-to-coil: 4000V Contact-to-frame: 2500V
100,000 min

Pole-to-pole: 1500V Contact-to-coil: 1500V Contact-to-frame: 1500V
200,000 min 500,000 min (DPDT)

CE, cULus, cURus, CSA, Lloyds

CE, cULus, cURus, CSA, Lloyds

700-HN100, 700-HN101, 700-HN125, 700-HN126, 700-HN204, 700-HN205

700-HN153, 700-HN154

12

22

CE, UR, CSA, Lloyds --
28

CE, UR, CSA 700-HN262, 700-HN264
32

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

9

Relay and Timer Specifications

Bulletin Number 700-HC

700-HK

700-HL

700-HP

Type

Interposing/Isolation Relay

Interposing/Isolation Relay

Interposing/Isolation Relay

Interposing/Isolation Relay

Features

· Blade-style terminals · Standard ON/OFF flag indicator · Electrical schematic on face · Clear cover for visual inspection · Optional push-to-test and
manual override · Optional LED

· Optional pilot light · Retainer clip (comes with socket) · Low switching capacity · Push-to-test and manual override

· Ideal for PLC Interfaces · Built-in Coil Surge Protection · Fully Assembled Relay/Sockets · Standard LED · Relay or Solid-state Output · Optional: Leakage Current · Suppression Solution

· PCB "Pin Style" mounting · 5 mm pin spacing

Contact Ratings

Contact Form

DPDT, 4PDT

SPDT, DPDT

SPDT 1 N.O. (SSR)

DPDT

Contact Type

Single

Single

Single

Single

Contact Material AgNi, AgNi + Gold

AgNi, AgNi + Gold

AgSnO

AgNi, AgNi + Gold

Operating Current, 10 A (DPDT)

Under Resistant Load, Max

7 A (4PDT)

8 A (DPDT), 16 A (SPDT)

6 A (SPDT), 2 A (SSR DC output), 2 A (SSR AC output)

8 A

Permissible Load, 10V, 10 mA (Gold),5V, 10 mA or

min

25V, 2 mA (Silver)

5V 60 mA (Silver), 5V 10 mA (Gold)

12V 6 mA (72 mW) Silver 8V, 2.5 mA (20 mW)Gold

5V 5 mA (50 mW) Gold, 5V 5 mA (300 mW) Silver

Coil Ratings

Coil Voltage

AC: 6, 12, 24, 120, 240V DC: 6, 12, 24, 48, 110V

AC: 6, 12, 24, 120, 240V DC: 6, 12, 24, 48, 110V

AC: 12, 24, 48, 110, 120, 230, 240V AC: 6, 12, 24, 120, 240V

DC: 12, 24, 48, 125, 230, 240V

DC: 6, 12, 24, 48, 110V

Permissible Coil Voltage Variation

80...110% of nom voltage at 50 Hz 80...110% of nom voltage at 50 Hz 85...110% of nom voltage at 50 Hz 80...110% of nom voltage at 50 Hz 80...110% of nom voltage at 60 Hz 80...110% of nom voltage at 60 Hz 85...110% of nom voltage at 60 Hz 80...110% of nom voltage at 60 Hz 80...110% of nom voltage at DC 73...110% of nom voltage at DC 80...110% of nom voltage at DC 73...150% of nom voltage at DC

Electrical Ratings

Pole-to-pole: 1000V

Dielectric Withstand Voltage

Contact-to-coil: 2000V

Contact-to-frame: 2000V

Pole-to-pole: 1500V Contact-to-coil: 1500V Contact-to-frame: 1500V

Pole-to-pole: 1000V Contact-to-coil: 4000V Contact-to-frame: 1500V

Pole-to-pole: 2000V Contact-to-coil: 5000V

Electrical Service Life (Cycles)

100,000 min

100,000 min

100,000 min

100,000 min

Reference

Certifications

CE, cULus, cURus, CSA, Lloyds

CE, UL, UR, CSA

CE, cURus, cULus, ABS

CE, cULus, cURus, CSA, Lloyds

Socket Catalog Numbers

700-HN103, 700-HN128, 700-HN104

700-HN121, 700-HN221, 700-HN122, 700-HN222, 700-HN223, 700-HN224

--

700-HN123, 700-HN230

Page Number

39

44

50

64

10

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

Bulletin Number 700-HJ

Type

Magnetic Latching Relay

Features

· Socket mounted · Ideal for lighting applications

Contact Ratings

Contact Form

SPDT,DPDT(Singleor Dual Coil)

Contact Type

Single

Contact Material AgCdO

Operating Current, Under Resistant 10 A Load, Max

Permissible Load, min

10V 50 mA

Coil Ratings

Coil Voltage

AC: 24V, 120V, 240V DC: 12V, 24V

Permissible Coil Voltage Variation

85...110% of nom voltage at 50 Hz 85...110% of nom voltage at 60 Hz 80...110% of nom voltage at DC

Electrical Ratings

Dielectric

Pole-to-pole: 1500V AC Contact-to-coil: 1500V

Withstand Voltage AC Contact-to-frame: 1500V AC

Electrical Service Life (Cycles)

100,000 minimum

Reference

Certifications

CE, UR, CSA

Socket Catalog Numbers

700-HN153, 700-HN154

Page Number

71

700-HG Power Relay · Panel mount with screw terminals · Optional magnetic blowouts for switching DC
loads · Optional snap action switch
SPST-N.O.-DM, SPDT, DPST-N.O., DPDT Single AgNi
40 A
10V 50 mA
AC: 24V, 120V, 240V, 277V, 480V DC: 12V, 24V, 48V, 110V, 220V, 250V 85...110% of nom voltage at 50 Hz 85...110% of nom voltage at 60 Hz 80...110% of nom voltage at DC
Pole-to-pole: 2200V AC Contact-to-coil: 2200V AC Contact-to-frame: 2200V AC 100,000 minimum
CE, UL, CSA -- 75

700-HHF Power Relay
· Flange mounted · Optional LED
SPST-NO-DM, DPDT, 3PDT Single AgNi
20 A (3PDT), 25 A (DPDT), 30 A (SPDT)
10V 50 mA 10V 100 mA (3PDT)
AC: 24V, 120V, 240V DC: 6V,12V,24V 85...110% of nom voltage at 50 Hz 85...110% of nom voltage at 60 Hz 80...110% of nom voltage at DC
Pole-to-pole: 2200V AC Contact-to-coil: 2200V AC Contact-to-frame: 2200V AC 100,000 minimum
CE, UR, CSA -- 80

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

11

Relay and Timer Specifications

700-HA General-purpose Relay
· 10 A contact rating · DPDT, 3PDT · Pin-style terminals · Standard ON/OFF flag indicator · Options: LED, push-to-test and manual override, socket-mounted surge suppressor module, or
multi-function timer · Contact choices: standard silver nickel, or bifurcated silver nickel with gold plating
Tube Base Relay with PIN Terminals (Single Contact) -- Mechanical ON/OFF Indicator Included(1)

Description

Contact Rating

Wiring Diagrams

U.S./Canada

International

Coil Voltage

Cat. No.(1)

6V AC

700-HA32A06

12V AC

700-HA32A12

24V AC

700-HA32A24

120V AC

700-HA32A1

240V AC

700-HA32A2

DPDT

2-pole

2 Form C Single AgNi Contact

10 A B300

277V AC 6V DC 12V DC 24V DC 36V DC

700-HA32A27 700-HA32Z06 700-HA32Z12 700-HA32Z24 700-HA32Z36

48V DC

700-HA32Z48

60V DC

700-HA32Z60

80V DC

700-HA32Z80

110V DC

700-HA32Z1

125V DC

700-HA32Z01

Sockets

700-HN125

700-HN100 700-HN204

140V DC 220V DC

700-HA32Z3 700-HA32Z2

6V AC

700-HA33A06

12V AC

700-HA33A12

24V AC

700-HA33A24

120V AC

700-HA33A1

3PDT

3-pole

3 Form C Single AgNi Contact

10 A B300

240V AC 6V DC 12V DC 24V DC 48V DC

700-HA33A2 700-HA33Z06 700-HA33Z12 700-HA33Z24 700-HA33Z48

60V DC

700-HA33Z60

80V DC

700-HA33Z80

110V DC

700-HA33Z1

125V DC

700-HA33Z01

Sockets

700-HN126

700-HN101 700-HN205

140V DC 220V DC

700-HA33Z3 700-HA33Z2

(1) LED Option: Add suffix (-4) to the selected 700-HA Relay Cat. No., except for the 240V AC Units, add (-4L). Push-to-test, Manual Override, and LED Option: Add suffix (-3-4) to the selected 700-HA Relay Cat. No., except for the 240V AC units, add (-3-4L). Push-to-test and Manual Override option: Add suffix (-3) to the selected 700-HA relay. LED not available for 220V DC and 277V AC coils.

(1) For Time Modules and Surge Suppressor Modules, see Accessories.

12

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

Tube Base Relay with PIN Terminals (Bifurcated Contacts with Gold Overlay) -- Mechanical ON/OFF Indicator Included

Description

Contact Rating

Wiring Diagrams U.S./Canada

International

DPDT 2-Pole 2 Form C Bifurcated AgNi Contacts with Gold Plating 6 A

Sockets

700-HN125

700-HN100 700-HN204

3PDT 3-Pole 3 Form C Bifurcated AgNi Contacts with Gold Plating 6 A

Sockets

700-HN126

700-HN101 700-HN205

Coil Voltage
6V AC 12V AC 24V AC 120V AC 240V AC 277V AC 6V DC 12V DC 24V DC 36V DC 48V DC 110V DC 125V DC 140V DC 6V AC 12V AC 24V AC 120V AC 240V AC 6V DC 12V DC 24V DC 48V DC 110V DC 125V DC 140V DC

Cat. No
700-HAX2A06 700-HAX2A12 700-HAX2A24 700-HAX2A1 700-HAX2A2 700-HAX2A27 700-HAX2Z06 700-HAX2Z12 700-HAX2Z24 700-HAX2Z36 700-HAX2Z48 700-HAX2Z1 700-HAX2Z01 700-HAX2Z3 700-HAX3A06 700-HAX3A12 700-HAX3A24 700-HAX3A1 700-HAX3A2 700-HAX3Z06 700-HAX3Z12 700-HAX3Z24 700-HAX3Z48 700-HAX3Z1 700-HAX3Z01 700-HAX3Z3

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

13

Relay and Timer Specifications

Accessories - 700-HA Relays

Photo

Description

Pkg. Qty.

Cat. No.

Screw Terminal Tube Base Socket -- Panel or DIN Rail Mounting; Guarded Terminal Construction. 8-Pin for use with DPDT 700-HA Relays, -HX Timing Relays, -HT (On-Delay), and -HRM, -HRC 10 and -HV (Repeat Cycle) Timing Relays.

700-HN100

Screw Terminal Tube Base Socket -- Panel or DIN Rail Mounting; Open Style Construction. 8-Pin for

use with DPDT 700-HA Relays, -HT (On-Delay) and -HRM, -HRC, and -HV (Repeat Cycle) Timing Relays. No

10

retainer clip required.

700-HN125

Photo 14

Screw Terminal Tube Base Sockets -- Panel or DIN Rail Mounting; Guarded Terminal Construction. 11-pin for use with 3PDT 700-HA relays.

10

700-HN101

Screw Terminal Tube Base Sockets -- Panel or DIN Rail Mounting; Open Style Terminal Construction. 11-pin for use with 3PDT 700-HA relays. No retainer clip required.

10

700-HN126

8-Pin Socket -- Can Be Used With or Without Timing Attachment or Surge Suppressor Screw Terminal Tube Base Sockets -- panel or DIN Rail mounting. Guarded terminal construction. Used with 10 DPDT 700-HA Relays.

11-Pin Socket -- Can Be Used With or Without Timing Module or Surge Suppressor. Screw Terminal

Tube Base Sockets -- panel or DIN Rail mounting. Guarded terminal construction.

10

Used with 3PDT 700-HA relays.

700-HN204 700-HN205

DIN (#3) symmetrical hat rail 35 x 7.5 x 1 m

10

199-DR1

Description

Pkg. Qty. Cat. No.

Diode Surge Suppressor Voltage Range: 6...220V DC used with 700-HN204 and 700-HN205 socket

10

700-ADR

Diode with LED Surge Suppressor Voltage Range: 6...24V DC used with 700-HN204 and 700-HN205 socket 10

700-ADL1R

Diode with LED Surge Suppressor Voltage Range: 28...60V DC used with 700-HN204 and 700-HN205 socket

10

700-ADL2R

Diode with LED Surge Suppressor Voltage Range: 110...220V DC used with 700-HN204 and 700-HN205 socket

10

700-ADL3R

Varistor with LED Surge Suppressor Voltage Range: 6...24V AC used with 700-HN204 and 700-HN205 socket

10

700-AV1R

Varistor with LED Surge Suppressor Voltage Range: 110...240V AC used with 700-HN204 and 700-HN205 socket

10

700-AV3R

RC Surge Suppressor Voltage Range: 6...24V AC/DC used with 700-HN204 and 700-HN205 socket

10

700-AR1

RC Surge Suppressor Voltage Range: 110...240V AC/DC used with 700-HN204 and 700-HN205 socket

10

700-AR2

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Photo

Description
Timing Module On-Delay or One-Shot selectable voltage range: 12...24V AC/DC used with sockets that accept plug-in accessory modules.
Timing Module On-Delay or One-Shot selectable voltage range: 110...125V AC used with sockets that accept plug-in accessory modules.
Timing Module On-Delay or One-Shot selectable voltage range: 230...240V AC used with sockets that accept plug-in accessory modules.

On-Delay

U (A1/A2)

LED & R

t

One-Shot
U (A1/A2) t
LED & R

1. 1 s

0.05...1 s

2. 10 s

0.5...10 s

3. 100 s

5...100 s

4. 10 min

0.5...10 min

5. 100 min

5...100 min

6. 10 hours

0.5...10 h

7. 100 hours

8. LED Indicator

Socket and Retainer Clip Reference

Relay Type
700-HA32 700-HAX2
700-HA33 700-HAX3

Socket
700-HN100 700-HN125 700-HN204
700-HN101 700-HN126 700-HN205

5...100 h
Retainer Clip 700-HN157 Not Required 700-HN157 700-HN157 Not Required 700-HN157

Relay and Timer Specifications

Pkg. Qty. Cat. No.

1

700-AT3

1

700-AT3A1

1

700-AT3A2

1

700-HT3

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

15

Relay and Timer Specifications

Specifications - 700-HA Relays
Attribute

Pilot Duty Rating (1) Rated Thermal Current (Ith) Rated Insulation Voltage (Ui)

Inductive

Contacts

120V AC 240V AC

General-purpose

Resistive

Min. Low Energy Permissible Load

Permissible Coil Voltage Variation

AC Coils

Coil Consumption ±10%

Inrush Sealed

DC Coils

Must Dropout Voltage

Max. Contact Resistance

Design Specification/Test Requirements

Pole-to-Pole Contact to Coil Electrical Life (Operating)

Degree of Protection (Open Type) IEC 529

Mechanical Lifecycles (AC/DC)

Switching Frequency Operations

Coil Voltages

Operating Time

Pickup Dropout

Maximum Operating Rate

Vibration

Endurance Operational

Shock

Endurance Operational

Temperature Altitude

Operating Storage

Insulating Material Enclosure Contact Material
Terminal Markings on Socket Sockets Certifications
Standards
(1) See NEMA Ratings and Test Values on page 5.

700-HA

Electrical Ratings

NEMA B300

HA = 10 A ­ 120V, 240V; HAX = 6 A ­ 120V, 240V

250V IEC ­ 300V UL/CSA

Make

Break

Hp

30 A

3 A

1/3

15 A

1.5 A

1

10 A, 240V AC

10 A, 30V DC

HA = 10V, 5 mA HAX = 5V, 2 mA

Pickup: 80...110% of nom voltage at 50 Hz, 80...110% of nom voltage at 60 Hz, 80...110% of nom voltage at DC

50 Hz

60 Hz

3.3VA

2.85VA

2.2VA

1.9VA

1.3 W

20% of nom V AC; 10% of nom V DC

50 M (700-HA), 30 M (700-HAX)

Electrical

2000V

2000V

100,000 min.

Mechanical

IP 40 > 20 x 106/ 50 x 106

3600/HR

See Product Selection

12 ms

12 ms

4 Ops/s

5 G

2.5 G

50 G

9 G

Environmental

AC/DC

­40...+70 °C (­40...+158 °F)

AC/DC

­40...+100 °C (­40...+212 °F)

2000 m (6560 ft)

Construction

Molded High-Dielectric Material

Transparent Dust Cover

700-HA:

10 A ­ AgNi

700-HAX:

6 A ­ Bifurcated/Gold Plating AgNi

In accordance with EN50 0005

8-Pin Socket -- 700-HN100, -HN125, -HN204, 11-Pin Socket -- 700-HN101, -HN126, -HN205

cURus Recognized (File No. E3125, Guide NLDX2/NLDX8), cULus Listed when used with 700-HN sockets noted (File No. E3125, Guide NLDX/NLDX7), CE Marked, CSA Certified, UR Certified (File 229473)

UL508, CSA C22.2 No. 14, EN 61810-1

16

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay Performance Graphs

Relay and Timer Specifications

Cycles Max. Switching Current (A)
k Reduction Factor

Load (kVA) Contact life vs. AC1 load at 1,800 cycles/h

Specifications - 700-HT3 Time Module
Attribute
Operating Voltage Range Power Consumption
Degree of Protection of Input (B1) Terminal Input Terminal Wire Range Input Terminal Torque Range Status Indicator Repeat Accuracy (1) Recovery Time Selectable Timing Ranges

Selectable Timing Modes

Adjustable Trimmer Scale Accuracy

Environmental

Temperature

Operating Storage

Altitude

Enclosure Mounting with Socket Only Sockets Certifications Standards
(1) At constant voltage and temperature.

Voltage DC (V)
Breaking capacity for DC1 load at 1,800 cycles/h A = load applied to one contact B = load applied to two contacts in series C = load applied to three contacts in series

COS  Load reduction factor vs. cos 

700-HT3

Electrical Ratings

12...240V AC (50/60 Hz) 12...240V DC

0.1 W (12V) 1.0 W(230V)

Mechanical

IP 20 (Guarded Terminal) 1.0 x 0.2 mm2...2.5 mm2 (24 ...14 AWG) 2.0 x 0.2 mm2...1.5 mm2 (24...16 AWG)

0.45...0.8 N·m (4...7 lb·in)

Red

±1%

<50 ms

Three DIP switches, seven ranges (set from 5...100% of range): 1 s, 10 s, 100 s, 10 min, 100 min, 10 h, 100 h

Three DIP switches, eight modes: 1. PowerOn­Delay
2. Power On One-Shot 3. Power On Repeat Cycle, On Start 4. Signal On-Delay and Signal Off-Delay

5. Signal Off-Delay 6. Signal On-One-Shot 7. Signal Off-One-Shot 8. Signal On and Signal Off Watchdog Monitor

±5% of Time Range

­20...+50 °C (­4 ...+122 °F) ­55...+85 °C (­67...+185 °F)
2000 m (6560 ft) Construction
Gray Plastic Housing 8- or 11-Pin Socket with Module Plug 700-HN204 (8-Pin with Plug), 700-HN205 (11-Pin with Plug) cURus Recognized (File No. E14843, Guide NRNT2/NRNT8), CE Marked UL508, CSA C22.2 No. 14, EN 61810-1

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

17

Relay and Timer Specifications

Timing Charts - 700-HT3 Multi-function Time Module (t = Time Range 0.05 s...100 h)

Terms: U is Power Input R is Relay Output S Signal, +A1 Socket, B1 Timer t is the resulting Time Delay (Red light-emitting diode)
1. Power On-delay Apply power (U) to timer. Relay contacts (R) change state after time delay (t) is complete. Contacts return to their shelf state when power is removed. Terminal B1 is not used in this mode.

3. Power On Repeat Cycle, On Start
Apply power (U) to timer. Relay contacts (R) change state immediately and the time delay (t) begins. When the time delay is complete, the contacts return to their shelf state for time delay (t) (time on = time-off). This cycle repeats until the power is removed. Terminal B1 is not used in this mode.

2. Power On One-shot
Apply power (U) to timer. Relay contacts (R) change state immediately and the time delay begins. When the time delay (t) is complete, contacts return to their shelf state. Contacts return to their shelf state when power is removed. Terminal B1 is not used in this mode.

4. Signal On-delay and Signal Off-delay
Apply power (U) to timer. When the signal (S) is closed the time delay (t) begins, after the time delay is completed the relay contacts (R) change state. Opening the signal starts the time delay, after the time delay is completed the contacts return to their shelf state. If the signal is closed or opened before the time delay is complete, the time delay is reset. Contacts return to their shelf state when power is removed.

Timing Charts -Cat. No. 700-HT3 Timing Modes, Time Description, Timing Charts, and DIP Switch Selections

Terms: U is Power Input R is Relay Output S Signal, +A1 Socket, B1 Timer t is the resulting Time Delay (Red light-emitting diode)
5. Signal Off-delay Apply power (U) to timer. When the signal (S) is closed, the relay contacts (R) change state immediately. When the signal is opened, the time delay (t) begins. If the signal is closed before the time delay is complete, the time delay is reset and the relay remains energized. When the time delay is complete, the contacts return to their shelf state. Contacts return to their shelf state when power is removed.

7. Signal Off One-shot
Apply power (U) to timer. When the signal (S) is closed and then opened, the relay contacts (R) change state immediately and the time delay (t) begins. After the time delay begins, opening or closing the signal will not reset the time delay. When the time delay is complete, the contacts return to their shelf state. Contacts return to their shelf state when power is removed.

6. Signal On One-shot
Apply power (U) to timer. When the signal (S) is closed, the relay contacts (R) change state immediately and the time delay (t) begins. After the time delay begins, opening or closing the signal will not reset the time delay. When the time delay is complete, the contacts return to their shelf state. Contacts return to their shelf state when power is removed.

8. Signal On and Signal Off Watchdog Monitor
Apply power (U) to timer. When the signal (S) is closed, the relay contacts (R) energize immediately and the time delay (t) begins. If the signal is opened before the time delay is complete, the relay remains energized and the time delay is reset. When the time delay is completed, the contacts return to their shelf state. If the signal is opened after the time delay is complete, the relay contacts energize immediately and the same time delay begins. Continuous cycling of the signal at a rate that is faster than the time delay causes the relay contacts to remain energized. Contacts return to their shelf state when power is removed.

18

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications
Dimensions -700-HA Relays
Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.
54.1 (2-1/8)

5.2 (13/64)

36.5 (1-9/20)
50 (1-63/64)

700-HA Relay

32.8 (1-3/10)

6.2

12.5

(15/64)

(1/2)

1000 (39-3/8)
Cat. No. 199-DR1 DIN Mounting Rail Series B Cat. No. 199-DR4 DIN Mounting Rail Series B Has No Mounting Holes

1.0 (0.04)
35.0 (1.38)
7.5 (0.3)

27.0 (1.06)

Cat. No.

A

B

C

D

199-DR1

35 (1-3/8)

27 (1-1/16)

7.5 (19/64)

1.02 (1/64)

199-DR4

35 (1-3/8)

27 (1-1/16)

15 (19/32)

2.3 (3/32)

Approx. Shipping Wt.
1.85 kg (4.07 lb) (10/pkg)
3.68 kg (8 lb) (5/pkg)

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

19

Relay and Timer Specifications

Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.

30.0 (1-3/16)
65.0 (2-35/64)

26 (1-1/32)

38.0 (1-1/2)

#4­40 M3

Cat. No. 700-HN100

Panel Mounting

Wire Size: 2 x 2.5 mm2 Single Wire ­ Up to #12 AWG Double Wire ­ 2 x 2.5 mm2 (#2-14 AWG... #2-20 AWG)
(Either Solid or Stranded) Strip Length: 9 mm (3/8 in.) ­ Torque: 0.8 N·m (7 lb·in)

40.1 (1-37/64)

24.6 (31/32)
20.8 (53/64)

24.9 (63/64)
4.2 (5/32)

54.9 (2-5/32)
51.1 (2-1/64)

33.0 (1-19/64)

Cat. No. 700-HN125

14.7 (37/64)

Wire Size: 2 x 2.5 mm2 Single Wire ­ Up to 12 AWG Double Wire ­ 2 x 2.5 mm2 (#2­14 AWG...#2­20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in.) ­ Torque: 0.8 N·m (7 lb·in)

65.0 (2-35/64)

30 (1-3/16)

38.0 (1-1/2)

26 (1-1/32)
#4-40 M3

Cat. No. 700-HN101

Panel Mounting

Wire Size: 2 x 2.5 mm2 Single Wire ­ Up to #12 AWG Double Wire ­ 2 x 2.5 mm2 (#2­14 AWG...#2­20 AWG)
(Either Solid or Stranded) Strip Length: 9 mm (3/8 in.) ­ Torque: 0.8 N·m (7 lb·in)

Cat. No. 700-HN126
Wire Size: 2 x 2.5 mm2 Single Wire ­ Up to #12 AWG Double Wire ­ 2 x 2.5 mm2 (#2­14 AWG...#2­20 AWG)
(Either Solid or Stranded) Strip Length: 9 mm (3/8 in.) ­ Torque: 0.8 N·m (7 lb·in)

20

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.

77.5 (3.05)

3.2 (0.13)

33.5 (1.32)
26.9 (1.06)

11.0 (0.43)
49.7 (1.96)

20.4 (0.80)
35.5 (1.40)

77.5 (3.05)

3.2 (0.13)

33.5 (1.32)
26.9 (1.06)

11.0 (0.43)
49.7 (1.96)

20.4 (0.80)
35.5 (1.40)

38.0 (1.50)

16.8 (0.66)

21.6 (0.85)
4.0 (0.16)

Cat. No. 700-HN204
Wire Size: 2 x 2.5 mm2 Single Wire ­ Up to #12 AWG Double Wire ­ 2 x 2.5 mm2 (14 AWG... 20 AWG) Qty. 2 wires
(Either Solid or Stranded) Strip Length: 9 mm (3/8 in.) ­ Torque: 0.8 N·m (7 lb·in)

38.0 (1.50)

16.8 (0.66)

21.6 (0.85)
4.0 (0.16)

Cat. No. 700-HN205

Wire Size: 2 x 2.5 mm2 Single Wire ­ Up to #12 AWG Double Wire ­ 2 x 2.5 mm2 (14 AWG ...20 AWG) Qty. 2 wires
(Either Solid or Stranded) Strip Length: 9 mm (3/8 in.) ­ Torque: 0.8 N·m (7 lb·in)

38.0 (1.50)

54 (2.13)

Cat. No. 700-HT3

6.3 (0.25) 10.5
(0.41)

Wire Size: 2 x 1.5 mm2 (#2 ­ 16 AWG...#1­20 AWG) (Either Solid or Stranded)
Strip Length: 9 mm (3/8 in.) ­ Torque: 0.8 N·m (7 lb·in)

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

21

Relay and Timer Specifications

700-HB Square Base Relay

· 15 A contact rating · DPDT, 3PDT · Blade-style quick connect /solder terminals (Faston 187 - 4.8 x 0.5 mm) · Standard ON/OFF flag indicator · Options: LED, push-to-rest, and manual override

Photo

Description

Contact Rating

Wiring Diagrams U.S./Canada

International

DPDT

2-Pole

2 Form C

15 A

Single AgCdO Contact

B300

Sockets

32 34 31
Input

700-HN154

700-HN153

3PDT

3-Pole

3 Form C

15 A

Single AgCdO Contact

B300

Input

Sockets

700-HN154

700-HN153

(1) LED Option: Add suffix (-4) to the selected 700-HB Relay Cat. No., except for the 240V AC Units, add (-4L). Push-to-test, Manual Override, and LED Option: Add suffix (-3-4) to the selected 700-HB Relay Cat. No., except for the 240V AC units, add (-3-4L) Push-to-test and Manual Override option: Add suffix (-3) to the selected 700-HB relay.

Coil Voltage
6V AC 12V AC 24V AC 120V AC 240V AC 6V DC 12V DC 24V DC

Cat. No.(1)
700-HB32A06 700-HB32A12 700-HB32A24 700-HB32A1 700-HB32A2 700-HB32Z06 700-HB32Z12 700-HB32Z24

48V DC 700-HB32Z48

110V DC 6V AC 12V AC 24V AC 120V AC 240V AC 6V DC 12V DC 24V DC

700-HB32Z1 700-HB33A06 700-HB33A12 700-HB33A24 700-HB33A1 700-HB33A2 700-HB33Z06 700-HB33Z12 700-HB33Z24

48V DC 700-HB33Z48

110V DC 700-HB33Z1

22

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

Accessories - 700-HB Relays

Photo

Description

Pkg. Qty. Cat. No.

Diode Surge Suppressor Voltage Range: 6...220V DC used with 700-HN204 and 700-HN205 socket

10

700-ADR

Diode with LED Surge Suppressor Voltage Range: 6...24V DC used with 700-HN204 and 700-HN205 socket 10

700-ADL1R

Diode with LED Surge Suppressor Voltage Range: 28...60V DC used with 700-HN204 and 700-HN205 socket

10

700-ADL2R

Diode with LED Surge Suppressor Voltage Range: 110...220V DC used with 700-HN204 and 700-HN205 socket

10

700-ADL3R

Varistor with LED Surge Suppressor Voltage Range: 6...24V AC used with 700-HN204 and 700-HN205 socket

10

700-AV1R

Varistor with LED Surge Suppressor Voltage Range: 110...240V AC used with 700-HN204 and 700-HN205 socket

10

700-AV3R

RC Surge Suppressor Voltage Range: 6...24V AC/DC used with 700-HN204 and 700-HN205 socket

10

700-AR1

RC Surge Suppressor Voltage Range: 110...240V AC/DC used with 700-HN204 and 700-HN205 socket

10

700-AR2

Timing Module
On-Delay or One-Shot selectable voltage range: 12...24V AC/DC used with sockets that accept plug-in accessory modules.

On-Delay

U (A1/A2)

LED & R

t

1

700-AT3

Timing Module
On-Delay or One-Shot selectable voltage range: 110...125V AC used with sockets that accept plug-in accessory modules.
Timing Module On-Delay or One-Shot selectable voltage range: 230...240V AC used with sockets that accept plug-in accessory modules.

One-Shot
U (A1/A2) t
LED & R

1

700-AT3A1

1

700-AT3A2

1. 1 s

0.05 s...1 s

2. 10 s

0.5 s...10 s

3. 100 s 4. 10 min 5. 100 min

5 s...100 s
0.5 min...10 min
5 min...100 min

1

700-HT3

6. 10 hours

0.5 h...10 h

7. 100 hours 8. LED Indicator

5 h...100 h

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

23

Relay and Timer Specifications

Photo

Description

Pkg. Qty.

Cat. No.

Screw Terminal Socket -- Panel or DIN Rail Mounting. Guarded Terminal Construction 11-blade socket for use with 700-HB relays. This socket has coil and contact separation as well as the 10 ability to use optional plug-in modules (700-A__ accessories, LED, surge suppression, timing modules).

700-HN153

Screw Terminal Base Socket -- Panel or DIN Rail Mounting. Open Style Construction 11-blade for use with 700-HB relays.

10

700-HN154

DIN (#3) symmetrical hat rail 35 x 7.5 x 1 m

10

Retainer Clip

For Cat. Nos. 700-HN154 Sockets with 700-HB Relays

10

Secures relay in socket. Order must be for 10 clips or multiples of 10.

Retainer Clip

For Cat. Nos. 700-HN153 Sockets with 700-HB Relays

10

Secures relay in socket. Order must be for 10 clips or multiples of 10.

Relay Identification Snap-in Markers Snap-in markers fit on top of product covers. The following are blank cards. Squares slip into molded slot 100 on top of product covers.

Pre-Printed Identification Tags -- contains 10 sheets of pre-printed and blank tags. Each sheet contains 13 sets of the markings CR...9CR, TR...9TR, M...9M, F, R, 1S, and 117 blank tags. Tags are 10 peel-off with sticky backing for easy placement on relays.
Blank Identification Tags -- contains 10 sheets of blank identification tags for customer specialized printing. Each sheet contains 546 blank tags. Tags are peel-off with sticky backing for easy placement on 10 relays.

Socket and Retainer Clip Reference

Relay Type 700-HB

Socket Cat. No.
700-HN153 700-HN154

Retainer Clip Cat. No.
700-HN158 700-HN156

199-DR1
700-HN156
700-HN158 1492-MS5X12 1492-MS6X9 1492-MS6X12 1492-MS8X9 1492-MS8X12 1492-MP-Blank 700-N40
700-N41

24

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Specifications - 700-HB Relays
Attribute
Pilot Duty Rating (1) RatedThermal Current (Ith)
Rated Insulation Voltage (Ui)
Inductive

Contacts

120V AC

240V AC

General-purpose

Resistive

Min. Low Energy Permissible Load

Permissible Coil Voltage Variation

Coil Consumption ±10%

AC Coils Inrush Sealed DC Coils

Max. Allowable Leakage

Max. Contact Resistance

Dielectric Withstand Voltage Pole-to-Pole Contact to Coil

Degree of Protection (Open Type) IEC 529

Mechanical lifecycles (AC/DC)

Switching Frequency Operations

Coil Voltages

Pickup Operating Time (ms)
Dropout

Maximum Operating Rate

Vibration

Endurance Operational

Endurance Shock
Operational

Temperature Altitude

Operating Storage

Insulating Material Enclosure Contact Material Terminal Markings on Socket Sockets Certifications Standards
(1) See NEMA Ratings and Test Values on page 5.

Relay and Timer Specifications

700-HB

Electrical Ratings

NEMA B300

15 A ­ 120V, 240V

250V IEC-300V UL/CSA

Make

Break

Hp

2 -Pole

3 -Pole

2 -Pole

3 -Pole

60 A

30 A

6 A

3 A

3/4

30 A

15 A

3 A

1.5 A

2

15 A, 240V AC

15 A, 30V DC

1000 mW (10V, 10 mA)

80...110% of Nominal Voltage at 50 Hz

80...110% of Nominal Voltage at 60 Hz

80...110% of Nominal Voltage at DC

50 Hz

60 Hz

3.3VA

2.85VA

2.2VA

1.9VA

1.3 W

25% of VA

10% of W

50 M

Design Specification/Test Requirements

2500V

4000V

Mechanical

IP 40 > 10 x 106/30 x 106

3600/HR

See Overview/Product Selection

20 ms

4 ms

4 Ops/s

5 G

1.5 G

50 G

15 G

Environmental

AC/DC

­40...+70 °C (­40...+158 °F)

AC/DC

­40...+100 °C (­40...+212 °F)

2000 m (6560 ft)

Construction

Molded High Dielectric Material

Transparent Dust Cover

AgCdO

In accordance with EN50 0005

700-HN153, -HN154

cURus Recognized (File No. E3125, Guide NLDX2/NLDX8), cULus Listed when used with 700-HN sockets noted

UL508, CSA C22.2 No. 14, EN 61810-1

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

25

Cycles

Relay and Timer Specifications
Technical Data - 700-HB Relays
Load (kVA)
Contact life versus AC1 load at 600 cycles/h.

Maximum Switching Current (A)

Voltage DC (V)
Breaking capacity for DC1 load at 600 cycles/h. Load applied to one contact. A = for N.O. types B= other types

Reduction Factor

(Highly Resistive) COS  Load Reduction factor versus cos 

(Inductive)

26

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

Dimensions - 700-HB Relays
Approximate Dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.

60.9 (2.40)

30.25

35.8

38.2

(1.19)

(1.41)

(1.50)

40

27.0

(1.57)

(1.06)

51.4 (2.02)
700-HB Relay

Ø 3.2 (0.13)

34.3 (1.35)

46.3 (1.82)

91.3 (3.59)
95.3 (3.75)

35.4 (1.39)
21.6 (0.85)

35.5 (1.40)

32.0 (1.26)

Cat. No. 700-HN153

Wire Size: 2 x 2.5 mm2 Single Wire ­ Up to #12 AWG Double Wire ­ 2 x 2.5 mm2 (14 AWG... 20 AWG), Qty. 2 wires
(Either Solid or Stranded) Strip Length: 9 mm (3/8 in.) ­ Torque: 0.8 N·m (7 lb·in)

49.5 (1.95)
35.4 (1.40)

25.6 (1.01)

84.85 (3.34)
84.3 (3.32)

41.5 (1.63)

4.0 (0.16)

Cat. No. 700-HN154

Wire Size: 2 x 2.5 mm2 Single Wire ­ Up to #12 AWG Double Wire ­ 2 x 2.5 mm2 (14 AWG... 20 AWG), Qty. 2 wires
(Either Solid or Stranded) Strip Length: 9 mm (3/8 in.) ­ Torque: 0.8 N·m (7 lb·in)

38.0 (1.50)
54 (2.13)
6.3 (0.25) 10.5
(0.41)
Cat. No. 700-HT3
Wire Size: 2 x 1.5 mm2 (#2 ­ 16 AWG...#1­20 AWG) (Either Solid or Stranded)
Strip Length: 9 mm (3/8 in.) ­ Torque: 0.8 N·m (7 lb·in)

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

27

Relay and Timer Specifications

700-HD Flange Mount Square Base Relay

· Flange-mounted/panel-mounted · 15 A contact rating · DPDT, 3PDT · Blade-style quick connect terminals (0.187 x 0.020)
· Solder terminals (no socket required)

Photo

Contact Rating

Wiring Diagrams U.S./Canada

DPDT

2-Pole 2 Form C

15 A

AgCdO Contacts

Input

3PDT

3-Pole 3 Form C

15 A

AgCdO Contacts

Input

International
32 34 31

Coil Voltage Cat. No.

6V AC 12V AC 24V AC 120V AC 208V AC 240V AC 6V DC 12V DC 24V DC 48V DC 110V DC 6V AC 12V AC 24V AC 120V AC 208V AC 240V AC 6V DC 12V DC 24V DC 48V DC 110V DC

700-HD32A06 700-HD32A12 700-HD32A24 700-HD32A1 700-HD32A20 700-HD32A2 700-HD32Z06 700-HD32Z12 700-HD32Z24 700-HD32Z48 700-HD32Z1 700-HD33A06 700-HD33A12 700-HD33A24 700-HD33A1 700-HD33A20 700-HD33A2 700-HD33Z06 700-HD33Z12 700-HD33Z24 700-HD33Z48 700-HD33Z1

Accessories - 700-HD Relays

Photo

Description

Pkg. Qty.

Cat. No.

Relay Identification Snap-in Markers Snap-in markers fit on top of product covers. The following are blank cards. Squares slip into molded slot on top of 100 product covers.
Pre-Printed Identification Tags -- contains 10 sheets of pre-printed and blank tags. Each sheet contains 13 sets of the markings CR...9CR, TR...9TR, M...9M, F, R, 1S, and 117 blank tags. Tags are peel-off with sticky backing for 10 easy placement on relays.

1492-MS5X12 1492-MS6X9 1492-MS6X12 1492-MS8X9 1492-MS8X12 1492-MP-Blank
700-N40

Blank Identification Tags -- contains 10 sheets of blank identification tags for customer specialized printing. Each sheet contains 546 blank tags. Tags are peel-off with sticky backing for easy placement on relays.

10 700-N41

28

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

Specifications - 700-HD Relays

Attribute

700-HD

Pilot Duty Rating (1) Rated Thermal Current (Ith)

NEMA B300 15 A(2) ­ 120V 15 A (2) ­ 240V,

Electrical Ratings

Rated Insulation Voltage(Ui) Inductive

250V IEC-300V UL/CSA
Make

Break

Hp

2-Pole

3-Pole

2-Pole

3-Pole

Contacts

120V AC 240V AC

60 A

30 A

6 A

3 A

3/4

30 A

15 A

3 A

1.5 A

2

General-purpose

15 A, 240V AC

Resistive

15 A, 30V DC

Min. Low Energy Permissible Load

1000 mW (10V, 10 mA)

Permissible Coil Voltage Variation

80...110% of Nominal Voltage at 50 Hz 80...110% of Nominal Voltage at 60 Hz 80...110% of Nominal Voltage at DC

AC Coils

50 Hz

60 Hz

Coil Consumption

Inrush

3.3VA

±10%

Sealed

2.2VA

2.85VA 1.9VA

DC Coils

1.3 W

Maximum Contact Resistance

50 M

Must Dropout Voltage

20% of Nominal V AC 10% of Nominal V DC

Design Specification/Test Requirements

Electrical

Dielectric Withstand Pole-to-Pole

2500V

Voltage

Contact to Coil

4000V

Mechanical

Degree of Protection (Open Type) IEC 529

IP 40

Mechanical lifecycles (AC/DC)

See Overview/Product Selection

Switching Frequency Operations Coil Voltages

3600/HR > 10 x 106 / 30 x 106

Pickup

20 ms

Operating Time

Dropout

4 ms

Maximum Operating Rate

4 Ops/s

Minimum Low Energy Permissible Load

1000 mN (10V, 10 mA)

Environmental

Temperature

Operating Storage

­40...+70 °C (­40...+158 °F) ­40...+100 °C (­40...+212 °F )

Altitude

2000 m (6560 ft)

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

29

Relay and Timer Specifications

Attribute

700-HD

Construction

Insulating Material

Molded High Dielectric Material

Enclosure

Transparent Dust Cover

Contact Material

Silver Cad. Ox.

Terminal Markings

In accordance with EN50 0005

Certifications

cURs Recognized (File No. E3125, Guide NLDX2/NLDX8), CSA Certified (File No. 229473), CE Marked, UR Certified

Standards

UL 508, CSA C22.2 No. 14, EN 61810-1

(1) See NEMA Ratings and Test Values on page 5. (2) 3-pole relays have a 20 A maximum total current rating for all three poles.

Maximum Switching Current (A)

Cycles

Reduction Factor

Load (kVA)
Contact life versus AC1 load at 600 cycles/h.

Voltage DC (V)
Breaking capacity for DC1 load at 600 cycles/h.
Load applied to one contact. A = for N.O. types B = other types

(Highly Resistive) COS 

(Inductive)

Load Reduction factor versus cos 

30

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications
Dimensions - 700-HD Relays
Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes. 35.9 (1.41)

68 (2.67)

63 (2.48)

700-HD Relay

38.2 (1.50)

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

31

Relay and Timer Specifications

700-HF Square Base Relay
· 12 A contact rating · DPDT, 4PDT · Plug-in quick connect/solder terminals · Options: LED, push-to-test manual override operator · Blade size: 4.8 x 0.5 mm (0.19 x 0.02 in.)

Photo

Description

Contact Rating

Wiring Diagrams U.S./Canada

International

DPDT

2-pole

2 Form C

AgCdO Contacts

12 A

Socket

700-HN116 700-HN262

700-HN116 700-HN262

4PDT
4-pole
4 Form C AgCdO Contact 12 A

Socket

700-HN139 700-HN264

700-HN139 700-HN264

(1) Pilot Light Option: Add suffix (-4) to the selected 700-HF Relay Cat. No. except for the 240V AC units, add (-4L). Manual Operator and LED Option: Add suffix (-3-4) to the selected 700-HF Relay Cat. No., except for the 240V AC units, add (-3-4L).

Coil Voltage
6V AC 12V AC 24V AC 120V AC 240V AC 6V DC 12V DC 24V DC 48V DC
110V DC
6V AC 12V AC 24V AC 120V AC 240V AC 6V DC 12V DC 24V DC 48V DC
110V DC

Cat. No.(1)
700-HF32A06 700-HF32A12 700-HF32A24 700-HF32A1 700-HF32A2 700-HF32Z06 700-HF32Z12 700-HF32Z24 700-HF32Z48
700-HF32Z1
700-HF34A06 700-HF34A12 700-HF34A24 700-HF34A1 700-HF34A2 700-HF34Z06 700-HF34Z12 700-HF34Z24 700-HF34Z48
700-HF34Z1

32

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

Accessories - 700-HF Relays

Photo

Description

Pkg. Qty. Cat. No.

Pre-Printed Identification Tags -- contains 10 sheets of pre-printed and blank tags. Each sheet contains 13 sets of the markings CR...9CR, TR...9TR, M...9M, F, R, 1S, and 117 blank tags. Tags are peel-off with sticky 10 backing for easy placement on relays.

700-N40

Blank Identification Tags -- contains 10 sheets of blank identification tags for customer specialized printing. Each sheet contains 546 blank tags. Tags are peel-off with sticky backing for easy placement on relays.

10

700-N41

Screw Terminal Socket -- Panel or DIN Rail Mounting 8-blade miniature socket for use with DPDT HF relays.

10

700-HN116

Screw Terminal Socket -- Panel or DIN Rail Mounting, Guarded Terminal Construction 8-blade socket for use with DPDT 700-HF relays. The socket has the ability to use optional plug-in modules (Cat. 10 No. 700-A_ _ accessories, LED, surge suppression, timing modules).

700-HN262

Screw Terminal Socket -- Panel or DIN Rail Mounting, Guarded Terminal Construction 14-blade socket for use with 4PDT 700-HF relays.

10

700-HN139

Screw Terminal Socket -- Panel or DIN Rail Mounting, Guarded Terminal Construction 14-blade socket for use with 4PDT 700-HF relays. The socket has coil and contact separation and the ability to use 10 optional plug-in modules (Cat. No. 700-A_ _ accessories, LED, surge suppression, timing modules).

700-HN264

DIN (#3) symmetrical hat rail 35 x 7.5 x 1 m

10

199-DR1

Retainer Clip for Cat. Nos. 700-HN103, -HN104 and -HN128 Sockets with 700-HC Relays and Cat. Nos.

700-HN116, 700-HN262 Sockets with 700-HF DPDT Relays§

10

Secures relay in socket. Order must be for 10 clips or multiples of 10.

Retainer Clip for Cat. Nos. 700-HN139 and -HN264 Sockets with 700-HF 4PDT Relays§ Secures relay in socket. Order must be for 10 clips or multiples of 10.

10

700-HN114 700-HN266

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

33

Relay and Timer Specifications

Accessories - 700-HF Relays

Photo

Description

Diode with LED Surge Suppressor Voltage Range: 6...24V DC used with sockets that accept plug-in accessory modules.

Diode with LED Surge Suppressor Voltage Range: 28...60V DC used with sockets that accept plug-in accessory modules.

Diode with LED Surge Suppressor Voltage Range: 110...220V DC used with sockets that accept plug-in accessory modules.

Varistor with LED Surge Suppressor Voltage Range: 6...24V AC used with sockets that accept plug-in accessory modules.

Varistor with LED Surge Suppressor Voltage Range: 110...240V AC used with sockets that accept plug-in accessory modules.

RC Surge Suppressor Voltage Range: 6...24V AC/DC used with sockets that accept plug-in accessory modules.

RC Surge Suppressor Voltage Range: 110...240V AC/DC used with sockets that accept plug-in accessory modules.

Timing Module On-Delay or One-Shot selectable voltage range: 12...24V AC/DC used with sockets that accept plug-in accessory modules.

Timing Module On-Delay or One-Shot selectable voltage range: 110...125V AC used with sockets that accept plug-in accessory modules.

Timing Module On-Delay or One-Shot selectable voltage range: 230...240V AC used with sockets that accept plug-in accessory modules.

Socket, and Retainer Clip Reference

Relay Type 700-HF32 700-HF34

Cat. No. Socket
700-HN116 700-HN262
700-HN139 700-HN264

Cat. No. Retainer Clip 700-HN114 700-HN266

Pkg. Qty. Cat. No.

10

700-ADL1

10

700-ADL2

10

700-ADL3

10

700-AV1R

10

700-AV3R

10

700-AR1

10

700-AR2

700-AT3

700-AT3A1 1

700-AT3A2

34

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

Specifications- 700-HF Relays
Electrical Ratings

Contacts

Inductive V AC

230V AC 120V AC

VDC

DC-1

Resistive Operating Range Rated Power Holding Voltage Must Drop Out Voltage Insulation Voltage

AC DC AC DC AC (50 Hz) DC AC DC AC DC

Dielectric Withstand Voltage
Mechanical Degree of Protection Mechanical Life Operations Switching Frequency Operations Coil Voltages Operating Time at nom voltage at 20 °C
Maximum Operating Rate Vibration Shock

Pole-to-Pole Contact to Pole
Pickup Dropout

Temperature Altitude

Operating Storage

Insulating Material Enclosure Contact Material Terminal Markings on Socket Sockets
Certifications
Standards

700-HF 2 Pole AC 15 @ 700 VA AC-1 @ 3000 VA 1 Hp @ 240V AC 1/2 Hp @ 120V AC 12 A @ 30V DC 0.5 A @ 110V DC 0.25 A @ 220V DC
12 A @ 250 V AC (per pole) 12 A @ 30 V DC (per pole) 80...110% nom voltage 80...110% nom voltage 1.5 VA 1 W
80% nom voltage 60% nom voltage 20% nom voltage 10% nom voltage
250V AC Design Specification/Test Requirements
2500V AC 2500V AC

700-HF 4 Pole
85...110% nom voltage 2 VA 1.3 W

Open Type (Sockets) 20 x 106

3600/hr

See Product Selection

8 ms

10 ms

3 ms

4 ms

4 Ops/s

15 G

15 G

Environmental

­40...+70 °C (­40...+268 °F)

­50...+80 °C (­89...+176 °F)

2000 m (6560 ft)

Construction

Molded High-Dielectric Material

Transparent Dust Cover

Silver Cad. Oxide

In accordance with EN50 0005

8-Blade Socket (DPDT) Cat. No. 700-HN116 & 700-HN262, 14-Blade Socket (4PDT) Cat. No. 700-HN139 & 700-HN264

CSA Certified (File No. 229473), UL Recognized (File No. E3125, Guide NLDX2/NLDX8), CE Marked, UL Listed when used with sockets shown above, (File No. E3125, Guide NLDX/NLDX 7), LR Certified, RINA Certified, IMQ Certified

UL 508, CSA 22.2 No. 14, EN-61810-1

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

35

Relay and Timer Specifications
Dimensions -700-HF Relays
Approximate Dimensions are shown in millimeters (inches). Approximate Dimensions are not intended to be used for manufacturing purposes.
700-HF Relay (DPDT)

700-HF (4PDT)

Cat. No. 199-DR1 DIN Mounting Rail Series B Cat. No. 199-DR4 DIN Mounting Rail Series B Has No Mounting Holes

Cat. No. 199-DR1 199-DR4

A

B

C

D

Approx. Shipping Wt.

35

27

7.5

1.02 1.85 kg

(1-3/8) (1-1/16) (19/64) (1/64) (4.07 lb) (10/pkg)

35

27

15

2.3

3.68 kg

(1-3/8) (1-1/16) (19/32) (3/32) (8 lb) (5/pkg)

36

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications
Dimensions - 700-HF Relays
Approximate Dimensions are shown in millimeters (inches). Approximate Dimensions are not intended to be used for manufacturing purposes.
Cat. No. 700-HN116 Wire Size: 2 x 2.5 mm Single Wire ­ Up to #12 AWG Double Wire ­ 2.5 mm (14 ... 20 AWG), Qty. 2 wires (Either Solid or Stranded) Strip Length: 9 mm (3/8 in.) ­ Torque: 0.8 N·m (7 lb·in)

Cat. No. 700-HN262 Wire Size: Solid - 1x6/ 2 x 2.5 mm
1x10 / 2 x 14 AWG Stranded - 1x4 / 2x2.5 mm
1x12 / 2x14 AWG Length: 9 mm (3/8 in.) - Torque: 0.8 N·m (7 lb· in)
300V AC, 12 A, 50 °C

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

37

Relay and Timer Specifications

Cat. No. 700-HN139 Wire Size: 2 x 2.5 mm Single Wire ­ Up to #12 AWG Double Wire ­ 2.5 mm (14 ... 20 AWG), Qty. 2 wires (Either Solid or Stranded) Strip Length: 9 mm (3/8 in.) ­ Torque: 0.8 N·m (7 lb·in)

Cat. No. 700-HN264 Wire Size: Solid - 1x6/ 2 x 2.5 mm
1x10 / 2x14 AWG Stranded - 1x4 / 2x2.5 mm
1x12 / 2x14 AWG Length: 9 mm (3/8 in.) - Torque: 0.8 N·m (7 lb·in)
300V AC, 10 A, 70 °C

38

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

700-HC Miniature Ice Cube Relay

· 7 or 10 A contact ratings · 2PDT or 4PDT · Standard ON/OFF flag indicator · Blade-style terminals (2.0 x 0.5 mm) · Choice of standard silver nickel contacts, or silver nickel with gold-plated contacts for low-energy applications · Options: LED, push-to-test with manual override option · Tungsten UL Approvals
· 4-Pole: 5A @ 24V DC · 2-Pole: 10A @ 24V DC

Photo

Contact Rating

Wiring Diagrams U.S./Canada

International

2PDT

10 A

2-Pole

C300

2 Form C

R300

Contacts:

Low energy rating;

10 A = AgNi (10V, 10 mA)

Contacts

100 mW

Input

Coil Voltage Cat. No.(1)

12V DC 24V DC 24V AC

700-HC22Z12 700-HC22Z24 700-HC22A24

120V AC

700-HC22A1

700-HN128

700-HN103 700-HN104

4PDT 4-Pole 4 Form C Contacts:
7A = AgNiAu Gold Plated Contacts

7 A Low energy rating; (5V, 10 mA or 25V, 2 mA) 50 mW

Input

4PDT 4-Pole 4 Form C Contacts:
7A = AgNi Silver Contacts

7 A C300 R300 Low energy rating; (10V, 10 mA) 100 mW

700-HN128

700-HN103 700-HN104

(1) LED Option: Add suffix (-4) to the selected 700-HC Relay catalog number, except for the 240V AC units, add (-4L). Push-to-test, Manual Override, and LED Option: Add suffix (-3-4) to the selected 700-HC catalog number, except for the 240V AC units, add (-3-4L). Push-to-test and Manual Override option: Add suffix (-3) to the selected 700-HC relay catalog number.

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

240V AC
6V AC 12V AC 24V AC 120V AC 240V AC 6V DC 12V DC 24V DC 48V DC 110V DC 6V AC 12V AC 24V AC 120V AC 240V AC 6V DC 12V DC 24V DC 48V DC 110V DC

700-HC22A2
700-HC14A06 700-HC14A12 700-HC14A24 700-HC14A1 700-HC14A2 700-HC14Z06 700-HC14Z12 700-HC14Z24 700-HC14Z48 700-HC14Z1 700-HC24A06 700-HC24A12 700-HC24A24 700-HC24A1 700-HC24A2 700-HC24Z06 700-HC24Z12 700-HC24Z24 700-HC24Z48 700-HC24Z1

39

Relay and Timer Specifications

Accessories - 700-HC Relays

Photo

Description

Diode with LED Surge Suppressor Voltage Range: 6...24V DC used with 700-HN104 socket
Diode with LED Surge Suppressor Voltage Range: 28...60V DC used with 700-HN104 socket
Diode with LED Surge Suppressor Voltage Range: 110...220V DC used with 700-HN104 socket
Varistor with LED Surge Suppressor Voltage Range: 6...24V AC used with 700-HN104 socket
Varistor with LED Surge Suppressor Voltage Range: 110...240V AC used with 700-HN104 socket
RC Surge Suppressor Voltage Range: 6...24V AC/DC used with 700-HN104 socket
RC Surge Suppressor Voltage Range: 110...240V AC/DC used with 700-HN104 socket
Timing Module On-Delay or One-Shot selectable voltage range: 12...24V AC/DC used with sockets that accept plug-in accessory modules.
Timing Module On-Delay or One-Shot selectable voltage range: 110...125V AC used with sockets that accept plug-in accessory modules.
Timing Module On-Delay or One-Shot selectable voltage range: 230...240V AC used with sockets that accept plug-in accessory modules.

Pkg. Qty.

Cat. No.

10

700-ADL1

10

700-ADL2

10

700-ADL3

10

700-AV1R

10

700-AV3R

10

700-AR1

10

700-AR2

700-AT3

1

700-AT3A1

700-AT3A2

Screw Terminal Socket -- Panel or DIN Rail Mounting; Guarded Terminal Construction.Ith = 10 A per pole. 14-blade miniature socket for use with 700-SC Relays.

10

700-HN103

Screw Terminal Socket -- Panel or DIN Rail Mounting; Guarded Terminal Construction Ith = 10 A per pole. 14-blade miniature socket for use with 700-HC relays. This socket has coil and contact separation as well as the ability to plug in 10 optional plug in modules (700-A__ accessories: LED, Surge Suppression, Timing Modules)

700-HN104

Screw Terminal Base Socket -- Panel or DIN Rail Mounting; Open-Style Construction Ith = 10 A per pole. 14-blade miniature socket for use with 700-HC Relays.

10

700-HN128

40

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

Photo

Description

Pkg. Qty.

Cat. No.

DIN (#3) symmetrical hat rail 35 x 7.5 x 1 m

10

199-DR1

Retainer Clip for Cat. Nos. 700-HN103, -HN104 and -HN128 Sockets with 700-HC Relays. Secures relay in socket.(1)
Plastic Retainer and Ejection Lever For use with the 700-HN104 Sockets for 700-HC relays. Built-in ability to accept 1492 Snap-in Markers
(1) See 700-HC Miniature Square Base Relay, Socket, and Retainer Clip Reference Chart.

10

700-HN114

10

700-HN124

Photo

Description
Relay Identification Snap-in Markers Snap-in markers fit on top of product covers. Squares slip into molded slot on top of product cover.
Pre-Printed Identification Tags -- contains 10 sheets of pre-printed and blank tags. Each sheet contains 13 sets of the markings CR...9CR, TR...9TR, M...9M, F, R, 1S, and 117 blank tags. Tags are peel-off with sticky backing for easy placement on relays.

Pkg. Qty. Cat. No.

5

1492-MS5X12

5

1492-MS6X9

5

1492-MS6X12

5

1492-MS8X9

5

1492-MS8X12

100

1492-MP-Blank

10

700-N40

Markers -- Used for terminal identification

50

700-N41

Socket and Retainer Clip Reference

Relay Type 700-HC

Socket Cat. No. 700-HN103 700-HN128 700-HN104

Retainer Clip Cat. No. 700-HN114 700-HN114 700-HN114 or 700-HN124

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

41

Relay and Timer Specifications

Specifications- 700-HC Relays
Attribute

Pilot Duty Rating (1) Rated Thermal Current (Ith) Rated Insulation Voltage (Ui)

Inductive

700-HC

Electrical Ratings

NEMA C300, R300

7 A and 10 A

250V IEC ­ 300V UL/CSA

700-HC_4

Hp

700-HC22

Hp

Make

Break

Make

Break

Contacts

120V AC 240V AC

15 A

1.5 A

1/8

7.5 A

0.75 A

1/3

15 A

1.5 A

1/3

7.5 A

0.75 A

3/4

General-purpose

7 A, 277V AC

10 A, 277V AC

Resistive

7 A, 30V DC

10 A, 24V DC

Min. Low Energy Permissible Load

100 mW (10V, 10 mA) - Silver Contacts 50 mW (5V, 10 mA, or 25V, 2 mA) - Gold Contacts

Permissible Coil Voltage Variation

Pickup:

80...110% of nom voltage at 50 Hz 80...110% of nom voltage at 60 Hz 80...110% of nom voltage at DC

Must Dropout Voltage:

20% of nom voltage at AC 10% of nom voltage at DC

Coil Consumption
±10%

AC Coils DC Coils

Max. Allowable Leakage

Inrush Sealed

Dielectric Withstand Voltage Electrical Life (Cycles)

Pole-to-Pole Contact to Coil

Degree of Protection (Open Type) IEC 529

Mechanical lifecycles

Switching Frequency Operations

Coil Voltages

Operating Time

Pickup Dropout

Maximum Operating Rate

Temperature
Altitude Insulating Material Enclosure Contact Material Terminal Markings on Socket Sockets
Certifications

Operating Storage

50 Hz

60 Hz

2.2VA

1.6VA

1.3VA

1.1VA

1.0 W

20% of VA (AC)

10% of W (DC)

Design Specification/Test Requirements

Electrical

2000V

2000V

100,000 min

Mechanical

IP 20 (Guarded Terminal Sockets) 20 x 106 (AC), 50 x 106 (DC)

1800/HR

See Product Selection

10 ms

3 ms

8 cycles/s

Environmental

­30...+55 °C (­22...+131 °F)

­55...+85 °C (­67...+185 °F)

2000 m (6560 ft)

Molded High Dielectric Material

Transparent Dust Cover

AgNi(700-HC2), AgNi + 5 m All (700-HC1)

In accordance with EN50 0005

700-HN103, -HN128, -HN104

cURus Recognized (File No. E14843, Guide NRNT2/NRNT8), cULus Listed when used with 700- HN103, -HN104, and -HN128 sockets (File No. E14843, Guide NRNT/NRNT7), CE Marked, LR Certified

Standards

UL 508, CSA 22.2 No. 14, EN 61810-1

(1) See General Information on page 3.

42

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications
Dimensions, 700-HC Relays
Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.

36.7 (1.44)

37.2 (1.46)

20.7 (0.82)

6.1 (0.24)

27.7 (1.09)

700-HC Relay (Two-Pole)

27.0 (1.06)

20.7 (0.82)

27.7 (1.09)

700-HC Relay (Four-Pole)

5.6 (0.22)

60.9 (2.40)

21.5 (0.85)

76.0 (2.99)
34.9 (1.37)

3.2 (0.13)
2.5 (0.10)

35.6 (1.40)

32.0 (1.26)
35.5 (1.40)

18.9 (0.74)

Cat. No. 700-HN104
Single Wire: 0.2 mm2...2.5 mm2 (24 AWG...14 AWG), Double Wire: 0.2 ...2.5 mm2 (24 AWG...14 AWG), Qty. 2 wires Wire Type: solid or stranded, copper only, Strip Length: 7 mm (9/32 in.), Torque: 0.5 N·m (4.4 lb·in)

Panel Mounting
24.5 (31/32)

28.9 (1-9/64)

30.0 (1-3/16)
6.1 (15/64)
8765
4321

24.9 (57/64)
21.1 (53/64)

67.0 (2-5/8)

30.0 (1-11/64)

#4-40 M3

Cat. No. 700-HN103
Single Wire: 0.2 mm2...2.5 mm2 (#24 AWG...14 AWG) Double Wire: 0.2...2 x 1.5 mm2 (24 AWG...16 AWG), Qty. 2 wires
Wire Type: Solid or Stranded, Copper only Strip Length: 8 mm (5/16 in.), Torque: 0.5 N·m (4.4 lb·in)

4.2 (5/32) 62.0
(2-15/64)

14

13

12 11 10 9

65.0 (2-9/16)

26.0 (1-1/64)
Cat. No. 700-HN128
Wire Size: 2 x 1.5 mm2 (#2-16 AWG...#1-20 AWG) (Either Solid or Stranded)
Strip Length: 9 mm (3/8 in.) ­ Toque: 0.8 N·m (7 lb·in)

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

43

Relay and Timer Specifications

700-HK Slim Line Relay

· 8 A/16 A contact ratings · DPDT/SPDT · Plug-in blade-style terminals (2.5 x 0.5 mm) · Retainer clip with sockets · Options: LED, push-to-test and manual override, socket-mounted surge suppressor module, or
timer module · Standard ON/OFF flag indicator · Relay faceplate accepts optional Bulletin1492 snap-in markers · Choice of standard silver/nickel contacts or silver/nickel with gold plated contacts · Maximum duty version available

Photo

Description

Contact Rating

Wiring Diagrams U.S./Canada

International

Coil Voltage Cat. No.(1)

6V AC

700-HK36A06

12V AC

700-HK36A12

24V AC

700-HK36A24

SPDT

1-Pole

1 Form C

AgNi Contacts

16 A

120V AC 240V AC 6V DC

700-HK36A1 700-HK36A2 700-HK36Z06

12V DC

700-HK36Z12

Input

24V DC

700-HK36Z24

48V DC

700-HK36Z48

Socket

700-HN121, 700-HN221, 700-HN223

700-HN121, 700-HN221, 700-HN223

110V DC

700-HK36Z1

6V AC

700-HK32A06

12V AC

700-HK32A12

24V AC

700-HK32A24

DPDT

2-Pole

2 Form C

AgNi Contacts

8 A

120V AC 240V AC 6V DC

700-HK32A1 700-HK32A2 700-HK32Z06

12V DC

700-HK32Z12

Input

24V DC

700-HK32Z24

48V DC

700-HK32Z48

Socket

700-HN122, 700-HN222, 700-HN224

700-HN122, 700-HN222, 700-HN224

110V DC

700-HK32Z1

(1) Options Pilot Light: Add suffix (-4) to the selected 700-HK Relay catalog number except for the 240V AC units, add (-4L). Manual Operator and LED: Add suffix (-3-4) to the selected 700-HK Relay catalog number, except for the 240V AC units, add (-3-4L). AgNi Contact with Gold plating: Replace"3"with "X"om catalog number. For example, if catalog number 700-HK36A1 is required with gold plating, the new catalog number is 700-HKX6A1. For high inductive, Tungsten, or Capacitive load applications, replace the"3"with a "M"in the catalog number. Only available in a SPDT configuration and with 24V DC, 120V AC, or 240V AC coil voltages.

44

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Accessories- 700-HK Relays

Photo

Description

Relay and Timer Specifications Pkg. Qty. Cat. No.

Screw Terminal Socket -- Panel or DIN Rail Mounting 5-blade miniature socket with 10 A rating for use with 1-pole, 700-HK relays. Accepts forked lug conductors. Socket includes a retainer clip.

10

700-HN121

Screw Terminal Socket -- Panel or DIN Rail Mounting 5-blade miniature socket with 16 A rating for use with 1-pole, 700-HK relays. Retainer clips are packaged separately with socket. Guarded terminal 10 construction and compatible with optional plug-in module accessories.

Spring Clamp Terminal Socket -- Panel or DIN Rail Mounting 5-blade miniature socket for use with 1-pole, 700-HK relays.

10

700-HN221 700-HN223

Screw Terminal Socket -- Panel or DIN Rail Mounting 8-blade miniature socket with 5 A rating for use with 2-pole, 700-HK relays. Accepts forked lug conductors. This socket includes a retainer clip.

10

700-HN122

Screw Terminal Socket -- Panel or DIN Rail Mounting

8-blade miniature socket with 8 A rating for use with 2-pole, 700-HK relays. Retainer clips are packaged separately with socket. Guarded terminal construction and compatible with optional plug-in module

10

accessories.

Spring Clamp Terminal Socket -- Panel or DIN Rail Mounting 8-blade miniature socket for use with 2-pole 700-HK relays.

10

700-HN222 700-HN224

Flange Mount Adapter Used for panel-mounting bulletin 700-HK relays. Order must be for 10 adapters or multiples of 10.

10

700-HN226

35 mm Rail Mount Adapter Mounts bulletin 700-HK relays to a 35 mm rail. Order must be for 10 adapters or multiples of 10.

10

700-HN227

Socket Retainer Clip and Ejection Lever For use with 700-HN22, -HN222, -HN223, and -HN224 sockets. Orders must be for 10 clips or multiples of 10.

10

700-HN229

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

45

Relay and Timer Specifications

Specifications- 700-HK Relays

Attribute Rated Thermal Current (Ith) Rated Insulation Voltage (Ui)
Inductive V AC

Contacts

Inductive V DC

Resistive
Make, Break , and Continuous

Min. Permissible Contact Ratings

Permissible Coil Voltage Variation
Power Consumption Coil Voltages

Pickup: holding Voltage: Must Dropout Voltage:

Dielectric Withstand Voltage

Poleto Pole(VRMS) Contact to Coil (VRMS)

Degree of Protection Mechanical Life Operations

Electrical Lifecycles

Switching Frequency

Operating Time at Nominal Pickup

Voltage at 20 °C (ms)

Dropout

Vibration

Operational Non-Operational

Shock

Operational Non-Operational

Temperature Altitude

Operating Storage

Insulating Material Enclosure Contact Material Terminal Markings on Socket

700-HK
120V AC
240V AC 230V AC 24V DC 125V DC 250V DC 230V AC 277V AC

Electrical Ratings

1-Pole, 1 CO, SPDT -- 16 A

250V IEC, 300V UL/CSA

AC-15, 6.2 A B300 Pilot Duty, 3 A A300 (700-HKM_)
1/3 Hp (0.24 kW) 1-phase

120V AC

AC-15, 3.1 A B300 Pilot Duty, 1.5 A A300(700-HKM_)
3/4 Hp (0.55 kW), 1-phase

240V AC

0.55 kW, 1-phase

230V AC

DC-13, 5.0 A

24V DC

DC-13, 0.2 A / R300 Pilot Duty, 0.22 A

125V DC

DC-13, 0.1 A / R300 Pilot Duty, 0.11 A

5 A, 250V AC

AC-1, 16 A

230V AC

16 A, General Use

277V AC

2-Pole, 2 CO, DPDT -- 8 A
AC-15, 2.9 A B300 Pilot Duty, 3.0 A 1/4 Hp (0.18 kW), 1-phase
AC-15, 1.4 A B300 Pilot Duty, 1.5 A 1/2 Hp (0.37 kW), 1-phase
0.37 kW, 1-phase DC-13, 3.0 A
DC-13, 0.2 A / R300 Pilot Duty, 0.22 A DC-13, 0.1 A / R300 Pilot Duty, 0.11 A
AC-1, 8 A 8 A, General Use

30V DC

DC-1, 12 A / 10 A, Resistive

30V DC

DC-1, 6 A / 6 A, Resistive

300 mW (5V/60 mA or 60V/5 mA) for AgNi Contacts (700-HK3_) 50 mW (5V/10 mA or 25V/2 mA) for AgNi + Gold Contacts (700-HKX_) 500 mW (100V/5 mA or 5V/100 mA) for AgSnO2 Contacts (700-HKM_)
80...110% of Nominal Voltage at 50/60 Hz, 73...110% of Nominal Voltage at DC 80% of Nominal V AC at 50/60 Hz, 40% of Nominal V DC 20% of Nominal V AC at 50/60 Hz, 10% Nominal V DC

1.2V A (V AC Coils), 0.5 W (V DC Coils) See Overview/Product Selection
Design Specification/Test Requirements

2000V AC 4000V AC

Mechanical

IP 20 (guarded terminal sockets), RT II -- Flux-proof (Relay) 10 x 106

230V AC, 16 A Resistive: 100 000 min. 277V AC, 16 A Resistive: 30 000 min. 30V DC, 10 A Resistive: 30 000 min.
B300, R300, Hp (kW): 6000 min. A300 (700-HKM_): 100,000 min.

230V AC, 8 A Resistive: 100 000 min. 277V AC, 8 A Resistive: 30 000 min. 30V DC, 6 A Resistive: 30 000 min. B300, R300, Hp (kW): 6000 min.

Mechanical: 18,000 cycles/hr. Electrical: 900 cycles/hr.

15 ms

5 ms

10...2000 Hz, 0.76 mm (0.03 in.) 2.5 G 10...2000 Hz, 0.76 mm (0.03 in.) 5.0 G

15 G 50 G

Environmental

­40...+70 °C (­40...+158 °F) ­40...+85 °C (­40...+185 °F)

2000 m (6560 ft)

Construction

Molded High Dielectric Material

Transparent Dust Cover

700-HK3_: Silver nickel (AgNi); 700-HKX_: Silver Nickel + Gold Plating (AgNi + Au); 700-HKM_: Silver Tin Oxide(AgSnO2) In accordance with EN 50005

46

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

Attribute Sockets

Screw Terminal Spring Clamp

Certifications Standards
Dimensions- 700-HK Relays

700-HK

1-Pole

2-Pole

700-HN121 (10 A @ 70 °C) 700-HN221 (16 A @ 50 °C, 12 A @ 70 °C)

700-HN122 (2 x 5 A @ 70 °C) 700-HN222 (2 x 8 A @ 70 °C)

700-HN223 (15 A @ 40 °C with 2 conductors per terminal) (10 A @ 70 °C with 1 conductor per terminal)

700-HN224 (2 x 8 A@ 70 °C)

Approvals

CSA Certified, File 75088, UL Recognized, File E3125 Guide NLDX2/NLCX8, cULus Listed with Allen-Bradley sockets (File No. 3125 Guide NLDX/NLDX7), CE Marked

EN61810-1, CSA 22.2 No. 14, UL 508

Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.

12.4

29.0

(1/2)

(1-9/64)

12.4

29.0

(1/2)

(1-9/64)

32.8 (1-19/64)

30.1 (1-3/16)

6.5 (1/4)

4.75 (3/16)
A1 5

0.5 (1/32)
COM 11 4

A2 1

NC 12 NO 14

2

3

Cat. No. 700-HK36_ (SPDT)

COM 11 NO 14 NC 12

3

4

2

COM 21 NO 24 NC 22

6

5

7

Cat. No. 700-HN224

A1 8
15.8 (5/8)
A2 1

COM 11 NO 14 NC 12

A1

4

3

2

5

15.8 (5/8)

A2 1
Cat. No. 700-HN223

32.8 (1-19/64)

30.1 (1-3/16)

6.5 (1/4)

2.5 (3/32)

0.5 (1/32)

COM 11

A1 NC 12 3 NO 14

8

2

4

A2 NC 22

NO 24

17

5

COM 21

6

Cat. No. 700-HK32_ (DPDT)

COM 11 NO 14 NC 12 3 42

A1 8
15.8 (5/8)

COM 21 NO 24 NC 22

A2

6 57

1

Cat. No. 700-HN222

COM 11 NO 14 NC 12

4

3

2

A1 5
15.8 (5/8)

A2 1
Cat. No. 700-HN221

44.7 (1-3/4)

32.5 22.6 (1-9/32) (57/64)

34.7 (1-3/8)
95.6 (3-49/64)
Cat. No. 700-HN223, 700-HN224 Wire Size: 0.2 mm2...1.5 mm2 (#24 AWG....#14 AWG)
Either Solid or Stranded Strip Length: 8 mm (5/16 in)

64.9 (2-9/16)

35.3 (1-25/64)

35.4 (1-13/32)
82.85 (3-17/64)
Cat. No. 700-HN221, 700-HN222 Wire Size: 0.2 mm2...2.5 mm2 (#24 AWG....#12 AWG)
Either Solid or Stranded Strip Length: 8 mm (5/16 in), Torque: 0.8Nm (7.0 lb.-in.)

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

47

Relay and Timer Specifications

Dimensions - 700-HK Relays
Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.

3.6 (9/64)

46.0 (1-13/16)
38.0 (1-1/2)

14.4 (37/64)

46.9 (1-27/32)

14.4 (37/64)

36.6 (1-11/16)
2.0 (5/64)

18.1 (23/32)

Cat. No. 700-HN226

42.4 (1-43/64)
39.8 (1-37/64)
34.8 (1-3/8) Cat. No. 700-HN227

Cat. No. 199-DR1 199-DR4

5.2 (13/64)
A 35 (1-3/8) 35 (1-3/8)

50 (1-63/64)

12.5

6.2

(1/2)

(15/64)

1.0 (0.04)

35.0 (1.38)

27.0 (1.06)

1000 (39-3/8)

7.5 (0.30)

Cat. No. 199-DR4 DIN Mounting Rail Series B Has No Mounting Holes Cat. No. 199-DR1 DIN Mounting Rail Series B

B

C

D

27

7.5

1.02

(1-1/16)

(19/64)

(1/64)

27

15

2.3

(1-1/16)

(19/32)

(3/32)

Approx. Shipping Wt.
1.85 kg (4.07 lb) (10/pkg)
3.68 kg (8 lb) (5/pkg)

48

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

7.11

11

(9/32)

Five M3.5

4

x 0.315 Screws

14 3
84.1 (3-5/16)

12 2
3.0 Ø (1) (1/8) Use M3 Screws

5 (+) (A1)
1 (-) (A2)

2.03 (5/64)
4.06 (5/32)
39.5 (1-17/32) 35.5 (1-13/32)

21 6
22 7 24 5
84.1 (3-5/16)
8 (+) (A1)

7.11

(9/32)

11

3

Eight M3.5 x 0.315 Screws
12 14 2 4 3.0 Ø (1) (1/8) Use M3 Screws

4.06 (5/32)
15.6 (5/8)

29.9 (1-3/16)
54.1 (2-1/8)

4.06 (5/32)

1 (-) (A2)
15.6 (5/8)

2.03 (5/64)
4.06 (5/32)
39.5 (1-17/32) 35.5 (1-13/32)
29.9 (1-3/16) 54.1 (2-1/8)

Cat. No. 700-HN121 Wire Size: 2 x 2.5 mm2 Single Wire ­ Up to #14 AWG Double Wire ­ 2 x 2.5 mm2 (14 AWG... 20 AWG) Qty. 2 wires (Either Solid or Stranded) Strip Length: 9 mm (3/8 in.) ­ Torque: 0.8 N·m (7 lb·in)

Cat. No. 700-HN122 Wire Size: 2 x 2.5 mm2 Single Wire ­ Up to #14 AWG Double Wire ­ 2 x 2.5 mm2 (14 AWG... 20 AWG) Qty. 2 wires (Either Solid or Stranded) Strip Length: 9 mm (3/8 in.) ­ Torque: 0.8 N·m (7 lb·in)

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

49

Relay and Timer Specifications

700-HL Terminal Block Relay
· Relay and socket assembled interface modules for high density interposing or isolation applications
· Screw terminal and spring-clamp bases · 6 A relay, choice of silver or gold contacts · 2 A solid-state relay -- DC output · 2 A solid-state relay -- AC output · SPDT (relay), 1 N.O. (solid-state) · Built-in retainer clip and snap-in marker lever · Standard LED, reverse polarity protection, and surge protection · Externally replaceable relay modules · Unique leakage current suppression version to address industry concerns of nuisance coil turn-on or contact non-drop out when connecting
to PLCs with leakage current · Available with hazardous location certification

Standard built-in Features: · LED · Reverse Polarity Protection
for DC Inputs · Coil Surge Protection(1)

Cat. No. 700-HLT1Z24

Specifications

Cat. No. 700-HLT2Z24

Cat. No. 700-HLS1Z24 (3)

Cat. No. 700-HLS11Z24

Output Type
Recommended Tightening Torque
Wire Range

SPDT (1 C/O); Ith = 6A(2)

1 N.O. solid-state; Ith = 2 A, 24V DC or Ith = 2 A, 240V AC

0.5 N· m max. (4.4 lb· in)

Screw Terminal: 0.14 mm2...2.5 mm2 (#26...#14 AWG), Spring Terminal: 0.2 mm2...2.5 mm2 (#24...#14 AWG)

Approvals

UL, cULus, cURus, ABS, CE

(1) Diode surge protection provided. (2) For Gold-plated contacts: Add the letter"X"at the end of the catalog number. For example: if Cat. No. 700-HLT1Z24 is required with gold plating, the new cat. no. is 700-HLT1Z24X. (3) Reverse polarity on the output terminals of the solid-state relay will result in the output being "ON" regardless of the state of the input voltage.

Input Voltage
12V DC 24V DC 48V DC 12V AC/DC 24V AC/DC 48V AC/DC 110/125V AC/DC 220...240V AC/DC 240V AC

Pkg. Qty.

Cat. No. (Screw Terminals)

Cat. No. (Spring Clamp Terminals)

10

(2) 700-HLT1Z12 700-HLT2Z12

10

(2) 700-HLT1Z24 700-HLT2Z24

10

(2) 700-HLT1Z48 700-HLT2Z48

10

700-HLT1U12

700-HLT2U12

10

700-HLT1U24

700-HLT2U24

10

700-HLT1U48

700-HLT2U48

10

700-HLT1U1

700-HLT2U1

10

700-HLT1U2

700-HLT2U2

10

700-HLT1A2

--

Cat. No. Pkg. Quantity (Screw Terminals)
(DC Output)

--

--

10

(2) 700-HLS1Z24

10

(2) 700-HLS1Z48

--

--

--

--

--

--

10

(2) 700-HLS1U1

10

(2) 700-HLS1U2

--

--

Cat. No. (Spring Clamp Terminals) (DC Output) -- 700-HLS2Z24 700-HLS2Z48 -- -- -- 700-HLS2U1 700-HLS2U2 --

Cat. No. (Screw Terminals) (AC Output)
-- 700-HLS11Z24 700-HLS11Z48 -- -- -- 700-HLS11U1 700-HLS11U2 --

50

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

Input Voltage

Pkg. Qty.

Cat. No. (Screw Terminals)

Cat. No. (Spring Clamp Terminals)

Built-in LCSC (leakage

current suppression circuit)

10

120V AC and 125V DC(1)

(2) 700-HLT1L1 --

Built-in LCSC (leakage current suppression 10 circuit) 240V AC (1)

(2) 700-HLT1L2 --

Hazardous Location Certification 24V DC

10

700-HLT1Z24-EX --

Hazardous Location Certification 12V DC

10

700-HLT1Z12-EX --

Hazardous Location Certification 110/125V 10 AC/DC

700-HLT1U1-EX --

(1) Leakage current suppression up to 2.2 mA off state current. (2) Electromechanical relay to solid-state relay interchangeability is possible.

Cat. No. Pkg. Quantity (Screw Terminals)
(DC Output)

Cat. No. (Spring Clamp Terminals) (DC Output)

10

(2) 700-HLS1L1

--

10

(2) 700-HLS1L2

--

10

700-HLS1Z24-EX

--

10

--

--

10

700-HLS1U1-EX

--

Accessories - 700-HLT, -HLS Relays

Photo

Description
Replacement Relays(1) Order must be for 20 relays or multiples of 20.

Pkg. Quantity

Socket Input Voltage

12V AC/DC

24V AC/DC

20

48V AC/DC

110/125V AC/DC 220...240V AC/DC

Replacement SSR 4-blade miniature relay for use with 1 N.O. SSR DC output. 20 Order multiples of 20.

24V DC
48V DC, 110/125V AC/DC 220...240V AC/DC

Replacement SSR 4-blade miniature relay for use with 1 N.O. SSR AC output. 20 Order multiples of 20.

24V DC

Replacement SSR 4-blade miniature relay for use with 1 N.O. SSR AC output. 20 Order must be for 20 relays or multiples of 20.

20-Way Jumper Can be cut to required length. Ith = 36 A max per 20-way jumper.

1

48V DC 110/125V AC/DC 220...240V AC/DC Color Red Grey
Blue

Cat. No. (Screw Terminals) (AC Output)
700-HLS11L1
700-HLS11L2 -- -- --
Cat. No. 700-TBR12 700-TBR24 700-TBR48 700-TBR60 700-TBS24 700-TBS60
700-TBS124
700-TBS160
700-TBJ20R 700-TBJ20G 700-TBJ20B

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

51

Relay and Timer Specifications

Photo

Description
End Barrier Used for visual inspection of groups, safe separation of neighboring 700-HL modules that end with jumpers.

Pkg. Quantity

Socket Input Voltage

10

Black

Snap-in Marker These snap-in markers have a 6 x 10 mm surface and snap into the ejection lever for the relay. For custom markers, contact your local 100
Rockwell Automation sales office or Allen-Bradley distributor for more
information.

Blank

(1) For gold-plated contacts: Add the letter"X"at the end of the catalog number. For example: if Cat. No. 700-TBR24 is required with gold plating, the new cat. no. is 700-TBR24X.
Dimensions - 700-HL Relays

Cat. No. 700-HN177
1492-MC6X10

700-HL Spring Terminal Design Single Wire: 0.2 mm2...2.5 mm2 (#24 AWG...#14 AWG ) Wire Type: Solid or stranded, copper only.Strip Length: 9 mm (11/32 in.)

Cat. No. 199-DR1 DIN Mounting Rail Series B, Cat. No. 199-DR4 DIN Mounting Rail Series B has no mounting holes.
Specifications - 700-HLT Relays

Pilot Duty Rating Rated Thermal Current (Ith) Rated Insulation Voltage(Ui)
Contacts
Inductive Load 52

Cat. No. 700-HLT... (Relay Output) Electrical Ratings B 300, R 300

1-Pole -- 6 A 250V IEC, 300V UL/CSA
1-Pole

24V AC, 1-phase

30 A

5 A

Inductive V AC 120VAC, 1-phase

30 A

3 A

Make

Break

240VAC, 1-phase

15 A

1.5 A

Inductive V DC
Resistive Make, Break, and Continuous

24V DC 125V DC 240V DC 24V DC 250V AC 240V DC

DC-13, 1.0 A DC-13, 0.2 A DC-13, 0.1 A
6.0 A 6.0 A 0.1 A AC-15 250V, 3 A N.O. Contact, 1.5 A N.C. Contact DC-13 24V, 1 A N.O., and N.C. Contact

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

Cat. No. 700-HLT... (Relay Output)

Min. Permissible Contact Ratings

12V, 6 mA (72 mW) for Silver Contacts, 8V, 2.5 mA (20 mW) for Gold Contacts

Permissible Coil Voltage Variation

Pickup:

85...110% of Nominal Voltage at 50 Hz 85...110% of Nominal Voltage at 60 Hz 80...110% of Nominal Voltage at DC

Must Dropout 10% of Nominal Voltage at AC

Voltage:

5% of Nominal Voltage at DC

Power Consumption ±10%

AC DC

0.3VA 0.2 W

Design Specification / Test Requirements

Pole to Pole (VRMS)

1000V

Dielectric Withstand Voltage

Contact to Coil (VRMS)

4000V

Input Voltage

12V AC/DC

24V AC/DC

48V AC/DC 120V AC/DC 240V AC/DC 120VLCSC 240VLCSC

Impedance (Ohms)

1K

2 K

6 K

26 K

56 K

16 K

35 K

Mechanical

Degree of Protection Mechanical Life Operations

IP20 1 x 107

Electrical Life Operations

6 A Resistive: 100 000 min. 24V DC, 1 A Inductive: 200 000 min. 120V AC 1 A Inductive: 300 000 min.

Switching Frequency Operations (no-load)

10 cycles/sec

Coil Voltages

See Overview/Product Selection

Pickup

7 ms

Operating Time at Nominal Voltage at 20 °C (ms)

Dropout

3 ms

Maximum Operating Rate (full load = 6 A)

6 cycles/min.

Coil Surge Protection

Per EN 61000-4.5; Surge Immunity (801-5) Class III: 2 kV common and 1 kV differential mode

Environmental

Temperature

Operating Storage

­40...+55 °C ­40...+100 °C

Altitude

2000 m (6560 ft)

Construction

Insulating Material

Molded High Dielectric Material

Enclosure

Relay IP67

Contact Material Terminal Markings on Socket

Silver Tin Ox, AgSnO2 or Silver with Gold Plating, AgSnO2 + Au In accordance with EN50 0005

Certifications

cULus Listed (File No. E3125, E14843 Guide NLDX/NLDX7) with Allen-Bradley socket, CE Marked, ABS (American Bureau of Shipping)

Standards

EN 61810-1, CSA 22.2,UL 508,NEMA IEE MAC Compliant, ICS-2 Compliant

Class 1, Zn 2, Groups IIC, Ex nC IIC T5 Ta < 55 °C

Hazardous Location Approvals

UL Listed (UL 60079-15)
CSA Certified (1) (CAN/CSA E60079-15)

700-HLT1Z12-EX (12V DC supply) 700-HLT1Z24-EX, 700-HLS1Z24-EX (24V DC supply) 700-HLT1U1-EX, 700-HLS1U1-EX (110V/125V AC/DC supply)
700-HLT1Z12-EX (12V DC supply) 700-HLT1Z24-EX, 700-HLS1Z24-EX (24V DC supply)

(1) Product shall be installed in an enclosure providing at least IP54 protection. Provisions shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 40%.

Rated Thermal Current (Ith) Rated Insulation Voltage(Ui)

Cat. No. 700-HLS... (Solid-state Output) Electrical 2 A (DC output) 250V IEC, 300V UL/CSA

2 A (AC output)

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

53

Relay and Timer Specifications

Cat. No. 700-HLS... (Solid-state Output)

Min. Control Voltage

80% nominal voltage

Maximum Control Voltage

110% nominal voltage

Control Circuit

Control Current Release Voltage

9 mA ±10% (24V) 4 mA ±10% (120/240V) 0.4 x nominal voltage (24V), 0.35 x nominal voltage (120/240V)

Min. Control Circuit Resistance

3200 ohms (24V), 16k ohms (120V), 32k ohms (240V)

2500 ohms (24V), 12k ohms (120V), 24k ohms (240V)

Load Voltage Range

0...24V DC

24...240V AC

Max. Repetitive Blocking Voltage

33V

600V

Outputs

Max. Switching Current (inductive/ resistive)
On State Voltage Drop @ Max. Switching Current

2 A DC <120 mV DC

1 A AC <1V AC

Leakage Current

max. 100 A (@U = 24V)

AC
Power Consumption ±10% DC

0.6VA(120V),1VA(240V)

0.2 W

0.3 W

Design Specification/Test Requirements

Pole to Pole (VRMS)

2500V

Dielectric Withstand Voltage

Contact to Coil (VRMS)

2500V

Input Voltage

24V DC

48V DC

120V AC/DC 240V AC/DC

120V LCSC

240V LCSC

Impedance (Ohms)

2K

9 K

26 K

58 K

16 K

35 K

Mechanical

Degree of Protection

IP20

Input Voltages

See Overview/Product Selection

Operating Time at Nominal Voltage at Turn on Time

20 °C (ms)

Drop Out Time

30 s (DC only input voltage), 7 ms (AC/DC input voltage) 350 s (DC only input voltage), 10 ms (AC/DC input voltage)

Maximum Operating Rate

300 Hz

Environmental

Temperature

Operating Storage

­20...+55 °C ­40...+70 °C

Altitude

2000 m (6560 ft)

Construction

Insulating Material

Molded High-Dielectric Material

Enclosure

Relay IP67

Terminal Markings on Socket

In accordance with EN50 0005

Certifications

cULus Listed (File No. E14843, Guide NLDX/NLDX7), CE Marked, ABS (American Bureau of Shipping)

Standards

UL 508, CSA C22.2 No. 14, EN 61810-1

Class 1, Zn 2, Groups IIC, Ex nC IIC T5 Ta < 55 °C

Hazardous Location Approvals

UL Listed (UL 60079-15)
CSA Certified (1) (CAN/CSA 60079-15)

700-HLT1Z24-EX, 700-HLS1Z24-EX (24V DC supply) 700-HLT1U1-EX, 700-HLS1U1-EX (110V/125V AC/DC supply)
700-HLT1Z24-EX, 700-HLS1Z24-EX (24V DC supply)

(1) Product shall be installed in an enclosure providing at least IP54 protection. Provisions shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 40%.

54

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications
Dimensions - 700-HLT, -HLS Relays
Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.

76.0 (2.99)

76.0 (2.99)

88.0 (3.46)

6.2 (0.24)

93.0 (3.66)

6.2 (0.24)

700-HLT / -HLS Screw Terminal Design Single Wire: 0.14 mm2...2.5 mm2 (#26 AWG...#14 AWG) Double Wire: 2 x 0.14 mm2...2 x 1.5 mm2 (2 x #26 AWG...2 x #16 AWG)
Wire Type: Solid or stranded, copper only Strip Length: 9 mm (11/32 in). Torque: 0.5 N·m (4.4 lb·in)

700-HLT / -HLS Spring Terminal Design Single Wire: 0.2 mm2...2.5 mm2 (#24 AWG...#14 AWG)
Wire Type: Solid or stranded, copper only Strip Length: 9 mm (11/32 in.)

Dimensions - 700-HLT, -HLS Relay Accessories

5.2 (13/64)

50 (1-63/64)

6.2

12.5

(15/64)

(1/2)

1.0 (0.04)
35.0 (1.38)

27.0 (1.06)

1000

7.5

(39-3/8)

(0.3)

Cat. No. 199-DR1 DIN Mounting Rail Series B Cat. No. 199-DR4 DIN Mounting Rail Series B Has No Mounting Holes

Cat. No. 199-DR1 199-DR4

A 35 (1-3/8) 35 (1-3/8)

B 27 (1-1/16) 27 (1-1/16)

C 7.5 (19/64) 15 (19/32)

D 1.02 (1/64) 2.3 (3/32)

Approx. Shipping Wt. 1.85 kg (4.07 lb) 3.68 kg (8 lb)

Pkg. Qty. 10/pkg 5/pkg

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

55

Relay and Timer Specifications
700-HL 2-pole Terminal Block Relay
· Relay and socket assembled interface modules for high density interposing or isolation applications · Screw terminal and spring-clamp bases · 10 A relay, choice of silver or gold contacts · DPDT (relay) · Built-in retainer clip and snap-in marker lever · Standard LED, reverse polarity protection, and surge protection · Externally replaceable relay modules

Output Type Recommended Tightening Torque Wire Range Approvals

DPDT (2 C/O); Ith = 10 A 0.6 N·m max. (5.3 lb·in.) Screw Terminal: 0.2...2.5 mm2 (#24...14 AWG), Spring Terminal: 0.2...2.5 mm2 (#24...14 AWG) cULus, cURus, CE

Input Voltages

Pkg. Quantity

Cat. No.(1) (Screw Terminals)

Cat. No.(Spring Clamp Terminals)

12V DC

10

700-HLT12Z12

700-HLT22Z12

24V DC

10

700-HLT12Z24

700-HLT22Z24

48V DC

10

700-HLT12Z48

700-HLT22Z48

24V AC/DC

10

700-HLT12U24

700-HLT22U24

110/125V AC/DC

10

700-HLT12U1

700-HLT22U1

220...240V AC/DC

10

700-HLT12U2

700-HLT22U2

(1) For Gold-plated contacts: Add the letter "X" at the end of the catalog number. Example: Cat. No. 700-HLT12Z24 with gold plated contacts is Cat. No. 700-HLT12Z24X. The following relays are available with the gold-plated contact option: 700-HLT_2Z24, 700-HLT_2U24, 700-HLT_2U1, and 700-HLT_2U2. Not available on 12V and 48V DC products.

Accessories - 700-HL Relays (2- pole)

Photo

Description

Pkg. Qty.

Replacement Relays Order must be for 20 relays or multiples 20 of 20.

8-Way Jumper Can be cut to required length. Ith = 1 10 A max per 8-way jumper.

Socket Input Voltage/Color
12V DC 24V AC/DC 48V DC 110/125V AC/DC, 220...240V AC/DC Red Grey Blue

End Barrier

Used for visual inspection of groups, safe separation of neighboring 700-HL

10

Black

modules that end with jumpers.

Snap-in Marker(1)

These snap-in markers have a 6 x 12 mm surface and snap into the ejection

100

Blank

lever for the relay.

(1) For custom markers, contact your local Rockwell Automation sales office or Allen-Bradley distributor for more information.

Cat. No. 700-TBR212 700-TBR224 700-TBR248 700-TBR2110 700-TBJ08R 700-TBJ08G 700-TBJ08B
700-HN177
1492-MS6X12

56

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

Specifications - 700-HL Relays (2-Pole)

Pilot Duty Rating Rated Thermal Current (Ith) Rated Insulation Voltage(Ui)

Cat. No. 700-HLT...2-Pole (Relay Output)
Electrical Ratings
B 300, R 300 2-Pole -- 10 A 250V IEC, 300V UL/CSA

Contacts
Min. Permissible Contact Ratings Permissible Coil Voltage Variation
Dielectric Withstand Voltage
Input Voltage Impedance (Ohms) Power Consumption ±10% Degree of Protection Mechanical Life Operations Electrical Life Operations Switching Frequency Operations (no-load) Coil Voltages Operating Time at Nominal Voltage at 20 °C (ms) Maximum Operating Rate (full load = 6 A)

Inductive V AC UL

120V AC 240V AC

AC-15, 3.0A B 300, 3.0 A
AC-15, 3.0 A B 300, 1.5 A

1/4 HP (186 W), 1-phase 1/2 HP (373 W), 1-phase

24V DC

DC-13, 2.0 A

Inductive V DC

125V DC

DC-13, 0.3 A

250V DC

DC-13, 0.2 A

250V AC

10 A

Resistive Make,

Break, and

24V DC

10 A

Continuous

250V DC

0.28 A

12V, 10 mA (120 mW) for Silver Contacts, 5V, 1 mA (50 mW) for Gold Contacts

Pickup:

85...110% of Nominal Voltage at 50 Hz 85...110% of Nominal Voltage at 60 Hz 80...110% of Nominal Voltage at DC

Must Dropout Voltage:

10% of Nominal Voltage at AC
5% of Nominal Voltage at DC

Design Specification/Test Requirements

Pole to Pole (VRMS)

1000V

Contact to Coil (VRMS)

5000V

Adjacent

Contacts

2500V

(VRMS)

12V AC/DC 24V AC/DC

48V DC

120V AC/DC

240V AC/DC

1 K

2 K

3 K

34 K

72 K

AC

N/A

0.5V A

N/A

0.4V A

0.8V A

DC

0.4 W

0.5 W

0.8 W

0.5 W

0.7 W

Mechanical

IP20 3 x 107

250V AC/24V DC, 8 A Resistive: 100 000 min. 24V DC, 10 A Resistive: 6000 min. 250V DC, 0.28 A Resistive: 6000 min. 250V AC, 10 A Resistive: 30 000 min.

1200 cycles/sec

See Overview/Product Selection

Pickup

typical 10 ms

Dropout

typical 10 ms

6 cycles/min.

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

57

Relay and Timer Specifications

Cat. No. 700-HLT...2-Pole (Relay Output)

Temperature

Environmental
Operating Storage

­40...+60 °C ­40...+100 °C

Altitude

2000 m (6560 ft)

Insulating Material

Construction

Molded High-Dielectric Material

Enclosure

Relay RT II -- flux-proof, pollution degree 2 installation environment

Contact Material

AgNi 90/10 or AgNi 90/10 + Au

Terminal Markings on Socket

In accordance with EN50 0005

Certifications

cULus Listed (File No. E3125, Guide NRNT/NRNT7), CE Marked

Standards

UL 508, CSA C22.2 No. 14, EN 61810-1

Dimensions - 700-HL (2-pole)

Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.

87.7 (3.45)

14 (0.55)

92.8 (3.65)

14 (0.55)

75 (2.95)

75 (2.95)

Bulletin 700-HL Screw Terminal Design Single Wire: 0.14 mm2...2.5 mm2 (#26 AWG...14 AWG) Double Wire: 2 x 0.14 mm2...2 x 1.5 mm2 (2 x #26 AWG...2 x 16 AWG)
Wire Type: Solid or stranded, copper only
Strip Length: 9 mm (11/32 in). Torque: 0.5 N·m (4.4 lb·in)

Bulletin 700-HL Spring Terminal Design Single Wire: 0.2 mm2...2.5 mm2 (#24 AWG...#14 AWG)
Wire Type: Solid or stranded, copper only
Strip Length: 9 mm (11/32 in)

97.8 (3.85)

Bulletin 700-TBJ08_ 8-Way Jumper

58

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

Cat. No. 199-DR1 199-DR4

5.2 (13/64)
A 35 (1-3/8) 35 (1-3/8)

50 (1-63/64)

6.2

12.5

(15/64)

(1/2)

1.0 (0.04)

35.0 (1.38)

27.0 (1.06)

1000

7.5

(39-3/8)

(0.3)

Cat. No. 199-DR1 DIN Mounting Rail Series B Cat. No. 199-DR4 DIN Mounting Rail Series B Has No Mounting Holes

B

C

D

27

7.5

1.02

(1-1/16)

(19/64)

(1/64)

27

15

2.3

(1-1/16)

(19/32)

(3/32)

Approx. Shipping Wt.
1.85 kg (4.07 lb) (10/pkg)
3.68 kg (8 lb) (5/pkg)

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

59

Relay and Timer Specifications

700-HLF Terminal Block Timing Relay
· Relay and socket assembled modules for high-density applications · Screw terminal bases · 6 A relay, choice of silver or gold contacts · SPDT (relay) · Four timing functions · Time range from 0.1 sec...6 hr · Built-in retainer clip and snap-in marker lever · Standard LED, reverse polarity protection, and surge protection · Externally replaceable relay modules

Wiring Diagram

A2 A1 16 15 18

Output Type Recommended Tightening Torque Wire Range Approvals

SPDT (1 C/O); Ith = 6A§ 0.5 N·m max. (4.4 lb·in) Screw Terminal: 0.14 mm2...2.5 mm2 (#26...#14 AWG) cULus, cURus, CE

Assembled Device Input Voltage 24V AC/DC
(1) For gold-plated contacts add an X after the catalog number listed.

Pkg. Quantity 10

Accessories - 700-HLF Relays
Terminal block timing relay bases are not sold separately.

Photo

Description

Cat. No.(1) 700-HLF1U24

Pkg. Quantity

Socket Input Voltage

Cat. No.

Replacement Relays Order must be for 20 relays or multiples of 20.

20

24V AC/DC

700-TBR24(1)

20-Way Jumper Can be cut to required length. Ith = 36 A max per 20-way 1 jumper.

End Barrier

Used for visual inspection of groups, safe separation of

10

neighboring 700-HL modules that end with jumpers.

Color

Red

700-TBJ20R

Grey

700-TBJ20G

Blue

700-TBJ20B

Black

700-HN177

Snap-in Marker

These snap-in markers have a 6 x 10 mm surface and snap into 100

Blank

the ejection lever for the relay.

(1) For gold-plated contacts: Add the letter"X"at the end of the catalog number. For example: if Cat. No. 700-TBR24 is required with gold plating, the new cat. no. is 700-TBR24X.

1492-MC6X10

60

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Function and Connection Diagrams - 700-HLF Relays

Relay and Timer Specifications

U (A1/A2)

R

t

LED

U (A1/A2) t
R
LED

U (A1/A2) R
LED

t 0.5s

U (A1/A2)
t
R
LED

tt

A1
A2
On-Delay
A1
A2
One Shot
A1
A2
Pulse
A1
A2
Flasher

15 1 c/o (SPST)
18 16
15 1 c/o (SPST)
18 16
15 1 c/o (SPST)
18 16
15 1 c/o (SPST)
18 16

Specifications- 700-HLF Relays

Pilot Duty Rating Rated Thermal Current (Ith) Rated Insulation Voltage (Ui)
Contacts
Inductive Load Min. Permissible Contact Ratings

Cat. No. 700-HLF... (Relay Output) (1)

Electrical Ratings

B 300, R 300

1-Pole -- 6 A

250V IEC, 300V UL/CSA

Inductive

1-Pole

24V AC, 1-phase

30 A

5 A

120VAC, 1phase

30 A

3 A

240VAC, 1phase

15 A

1.5 A

24V DC

1.0 A

Make, Break and Continuous V DC

120V DC

0.2 A

240V DC

0.1 A

AC-15 250V, 3 A N.O. Contact, 1.5 A N.C. Contact DC-13 24V, 1 A N.O. and N.C. Contact

12V, 6 mA (72 mW) for Silver Contacts, 8V, 2.5 mA (20 mW) for Gold Contacts

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

61

Relay and Timer Specifications

Permissible Coil Voltage Variation

Pickup:

85...110% of Nominal Voltage at 50 Hz 85...110% of Nominal Voltage at 60 Hz 80...110% of Nominal Voltage at DC

Must Dropout Voltage:

10% of Nominal Voltage at AC,
5% of Nominal
Voltage at DC

Power Consumption ±10%

AC/DC

0.5VA

Design Specification/Test Requirements

Pole to Pole (VRMS)

1000V

Dielectric Withstand Voltage

Contact to Coil (VRMS)

4000V

Input Voltage

24V AC/DC

Impedance (Ohms)

2 K

Mechanical

Degree of Protection Mechanical Life Operations

IP20 1 x 107

Electrical Life Operations

6 A Resistive: 100,000 min. 24V DC, 1 A Inductive: 200,000 min. 120V AC 1 A Inductive: 300,000 min.

Switching Frequency Operations (no-load)

10 cycles/sec

Coil Voltages

See Overview/Product Selection

Timer Functions

On-Delay, One Shot, Pulse, and Flasher

Timer Settings

0.1...3 s, 3...60 s, 1...20 min, and 0.3...6 hr

Timer Adjustments

Min and Max adjustments with Potentionmeter

Timer Accuracy

Repeatability 1%, Recovery Time < 50 ms, Setting Accuracy Full Range 5%

Coil Surge Protection

Per EN 61000-4.5; Surge Immunity (801-5) Class III: 2 kV common and 1 kV differential mode

Environmental

Temperature

Operating Storage

­40...+55 °C (­40...+131 °F) ­40...+100 °C (­40...+212 °F)

Altitude

2000 m (6560 ft)

Construction

Insulating Material

Molded High Dielectric Material

Enclosure

Relay IP67

Contact Material Terminal Markings on Socket

Silver Tin Ox, AgSnO2 or Silver with Gold Plating, AgSnO2 + Au In accordance with EN50 0005

Certifications

cULus Listed (File No. E3125, Guide NLDX/NLDX7) with Allen-Bradley socket, CE Marked

Standards

EN60947-4-1,EN60947-5-1,CSA 22.2,UL 508,NEMA IEE MAC Compliant, ICS-2 Compliant

(1) Product shall be installed in an enclosure providing at least IP54 protection. Provisions shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 40%.

62

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

Dimensions- 700-HLF Relays
Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.

6.20 (0.24)

76.0 (2.99)

88.0 (3.46)

5.2 (13/64)

Cat. No. 199-DR1 199-DR4

A 35 (1-3/8) 35 (1-3/8)

700-HLF Screw Terminal Design Single Wire: 0.14 mm2...2.5 mm2 (#26 AWG...14 AWG) Double Wire: 2 x 0.14 mm2...2 x 1.5 mm2 (2 x #26 AWG...2 x 16 AWG)
Wire Type: Solid or stranded, copper only Strip Length: 9 mm (11/32 in.). Torque: 0.5 N·m (4.4 lb·in)

50 (1-63/64)

6.2

12.5

(15/64)

(1/2)

1.0 (0.04)

35.0 (1.38)

27.0 (1.06)

1000

7.5

(39-3/8)

(0.3)

Cat. No. 199-DR1 DIN Mounting Rail Series B Cat. No. 199-DR4 DIN Mounting Rail Series B Has No Mounting Holes

B 27 (1-1/16) 27 (1-1/16)

C 7.5 (19/64) 15 (19/32)

D 1.02 (1/64) 2.3 (3/32)

Approx. Shipping Wt. 1.85 kg (4.07 lb) (10/pkg)
3.68 kg (8 lb) (5/pkg)

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

63

Relay and Timer Specifications

700-HP Slim Line Relay

· 8 A contact ratings · DPDT/ (2 c/o) contacts · Plug-in PIN style (PCB) terminals (5 mm pinning) · Choice of standard silver nickel contacts, or silver nickel with gold-plated contacts · Available with mechanically linked contacts (Type B) · Safety Control Relay Version (700-HPS)

Photo

Description

Contact Wiring Diagrams Rating U.S./Canada

International

DPDT 2-Pole 2 Form C AgNi + Au Gold Plated Contacts
8 A
DPDT 2-Pole 2 Form C AgNi Contacts

Sockets

700-HN123

700-HN123

Coil Voltage

Pkg. Qty.

Cat. No.

6V AC 10 700-HPX2A06 12V AC 10 700-HPX2A12 24V AC 10 700-HPX2A24 120V AC 10 700-HPX2A1 240V AC 10 700-HPX2A2 6V DC 10 700-HPX2Z06 12V DC 10 700-HPX2Z12 24V DC 10 700-HPX2Z24 48V DC 10 700-HPX2Z48 110V DC 10 700-HPX2Z1 6V AC 10 700-HP32A06 12V AC 10 700-HP32A12 24V AC 10 700-HP32A24 120V AC 10 700-HP32A1 240V AC 10 700-HP32A2 6V DC 10 700-HP32Z06 12V DC 10 700-HP32Z12 24V DC 10 700-HP32Z24 48V DC 10 700-HP32Z48 110V DC 10 700-HP32Z1

64

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

700-HPS Safety Control Relay

Photo

Description

Contact Wiring Diagrams Rating U.S./Canada

International

DPDT 2-Pole 2 Form C AgNi + Au Gold Plated Mechanically Linked Contacts
8 A
DPDT 2-Pole 2 Form C AgNi Mechanically Linked Contacts

700-HPS DPDT

Sockets

700-HN123

700-HN123

Accessories - 700-HP, -HPS

Photo

Description
Diode Surge Suppressor Voltage Range: 6...220V DC used with 700-HN123 socket
Diode with LED Surge Suppressor Voltage Range: 6...24V DC used with 700-HN123 socket
Diode with LED Surge Suppressor Voltage Range: 28...60V DC used with 700-HN123 socket
Diode with LED Surge Suppressor Voltage Range: 110...220V DC used with 700-HN123 socket
Diode with LED Surge Suppressor Voltage Range: 6...24V AC used with 700-HN123 socket
Varistor with LED Surge Suppressor Voltage Range: 110...240V AC used with 700-HN123 socket
RC Surge Suppressor Voltage Range: 6...24V AC/DC used with 700-HN123 socket
RC Surge Suppressor Voltage Range: 110...240V AC/DC used with 700-HN123 socket
Timing Module On-Delay or One-Shot selectable voltage range: 12...24V AC/DC used with sockets that accept plug-in accessory modules.
Timing Module On-Delay or One-Shot selectable voltage range: 110...125V AC used with sockets that accept plug-in accessory modules.
Timing Module On-Delay or One-Shot selectable voltage range: 230...240V AC used with sockets that accept plug-in accessory modules.

Relay and Timer Specifications

Coil Pkg. Voltage Qty.
6V DC 10 12V DC 10 24V DC 10 48V DC 10 60V DC 10 110V DC 10 125V DC 10 6V DC 10 12V DC 10 24V DC 10 48V DC 10 60V DC 10 110V DC 10 125V DC 10

Cat. No.
700-HPSXZ06 700-HPSXZ12 700-HPSXZ24 700-HPSXZ48 700-HPSXZ60 700-HPSXZ1 700-HPSXZ01 700-HPS2Z06 700-HPS2Z12 700-HPS2Z24 700-HPS2Z48 700-HPS2Z60 700-HPS2Z1 700-HPS2Z01

Pkg. Qty.

Cat. No.

10 700-ADR

10 700-ADL1R

10 700-ADL2R

10 700-ADL3R

10 700-AV1R

10 700-AV3R

10 700-AR1 10 700-AR2

700-AT3

1 700-AT3A1

700-AT3A2

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

65

Relay and Timer Specifications

Photo

Description

Pkg. Qty.

Cat. No.

Screw Terminal Socket -- Panel or DIN Rail Mounting 8-pin miniature socket for use with 2-pole, 700-HP relays. Incorporates coil and contact separation.

10 700-HN123

8-Way Jumper can be cut to required length. Rated 10 A ­ 250V
Plastic Retainer and Ejection Lever For use with the 700-HN123 sockets Built-in ability to accept 1492 snap-in markers
Spring Clamp Terminal Socket -- Panel or DIN Rail Mounting 8-pin miniature socket for use with 2-pole, 700-HP relays. Incorporates coil and contact separation.
Plastic Retainer and Ejection Lever For use with the 700-HN230 sockets Built-in ability to accept 1492 snap-in markers

Red Gray 1 Blue

700-TBJ20R 700-TBJ20G 700-TBJ20B

10 700-HN119

10 700-HN230

10 700-HN232

DIN (#3) symmetrical hat rail 35 x 7.5 x 1 m

10 199-DR1

Relay Identification Snap-in Markers Note - These markers can only be used when the Plastic Retainer and Ejection Lever accessory (part # 700HN119) is used because the markers snap into the Ejection Lever (and not into the relay itself).

5 1492-MS5X12 5 1492-MS6X9 5 1492-MS6X12 5 1492-MS8X9 5 1492-MS8X12 100 1492-MP-Blank
700-N40

Pre-Printed Identification Tags -- contains 10 sheets of pre-printed and blank tags. Each sheet contains 13 sets of the markings CR...9CR, TR...9TR, M...9M, F, R, 1S, and 117 blank tags. Tags are peel-off with sticky 10 backing for easy placement on relays.

700-N41

Socket, and Retainer Clip Reference

Relay Type

Socket Cat. No.

700-HPX2

700-HN123

700-HP32

700-HN123

700-HPS2

700-HN123

700-HPSX

700-HN123

Retainer Clip Cat. No. 700-HN119 700-HN119 700-HN119 700-HN119

66

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

Specifications (1) - 700-HP Relays
Cat. No. 700-HP...

Contacts

Inductive

Resistive

Minimum Load

Nominal Coil Power (AC/DC)

Operating Range (AC/DC)

Holding Voltage (AC/DC)

Must Drop Out Voltage (AC/DC)

Insulation Voltage

Design Specification/Test Requirements

Dielectric Withstand Voltage for 1 minute

Pole to Pole (VRMS) Contact to Coil (VRMS)

Mechanical

Degree of Protection

Mechanical lifecycles

Switching Frequency Operations

Coil Voltages

Operating Time at Nominal Voltage at 20 °C (ms)

Pickup Dropout

Maximum Operating Rate

Vibration

Enclosure Fragility

Endurance
Shock Fragility

Max. Socket Torque

Environmental

Temperature

Operating Storage

Altitude

Cat. No. 700-HP3..., 700-HPX

Cat. No. 700-HPS...

AC 15 @ 500V AC

C300

B300

V AC

1/3 Hp @ 240V AC

1/2 Hp @ 240V AC

1/6 Hp @ 120V AC

1/3 Hp @ 120V AC

AC-1 2000VA

R300

--

DC-1: 8A @ 30V DC

V DC

DC-1: 0.3A @ 110V DC

DC-1: 0.65A @ 110V DC

DC-1: 0.1A @ 220V DC

DC-1: 0.2A @ 220V DC

AC

8 A @ 277V AC (per pole)

DC

8 A @ 30V DC (per pole)

700-HP32: 300mW (5V, 5 mA) 700-HPX2: 50mW (5V, 5 mA)

700-HPS2: 500 mW (10V, 10 mA) 700-HPSX: 50 mW (5V, 5 mA)

1.2 VA / 0.65 W

0.7 W

80...110% / 73...150% Nominal Voltage

75...120% Nominal Voltage DC

80 / 40% Nominal Voltage

40% Nominal Voltage DC

20 / 10% Nominal Voltage

10% Nominal Voltage DC

250V AC

700-HP3, 700-HPX

700-HPS

2000V AC

4000V AC

Open Type (Sockets)

10 x 106 (AC Coils), 20 x 106 (DC coils)

10 x 106 (DC Coils)

1800/hr (no load)

900/hr (no load)

See Overview/Product Selection

12

10

4

16 Ops/s (full load)

8 Ops/s (full load)

5 G

2.5 G

50 G

15 G

0.5 N·m (4.4 lb·in)

­40...+85 °C (­40...+185 °F) ­40...+70 °C (­40...+158 °F) ­45...+100 °C (­49...+212 °F) ­50...+80 °C (­40...+176 °F)
2000 m (6560 ft)

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

67

Relay and Timer Specifications
Specifications (1) - 700-HP Relays
Construction Insulating Material Enclosure Contact Material Terminal Markings on Socket Sockets Approvals
Certifications
Standards
(1) The inrush VA equals 1.5 times the sealed VA.

Molded High-Dielectric Material

Transparent Dust Cover

Red Transparent Dust Cover

Silver Nickel, (AgNi) (700-HP32 and 700-HPS2), Silver Nickel + Gold Plating (AgNi + Au) (700-HPX2 and 700-HPSX)

In accordance with EN50 0005

2-Pole

700-HN123

cURus Recognized (File No. E3125, Guide NLDX2/NLDX8), cULus Listed when used with 700-HN123 socket (File No. E3125, Guide NLDX/NLDC7), CSA Certified (files 229473), CE Marked, LR Certified (700-HP), IMQ & TÜV Certified (700- HPS)
UL 508, CSA 22.2 No. 14, EN 61810-1, EN 50205 (700-HPS)

68

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications
Dimensions - 700-HP Relays
Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.

29.0 (1.14)

5.2 (13/64)

Cat. No. 199-DR1 199-DR4

A
35 (1-3/8)
35 (1-3/8)

12.4 (0.49)

700-HP Relay

25.0 (0.98)

50 (1-63/64)

6.2

12.5

(15/64)

(1/2)

1000 (39-3/8)
Cat. No. 700-HN123 Single Wire: 0.2.....2.5 mm2 (#24.....14 AWG) Double Wire: 2 X 0.2.....2 X 2.5 mm2 (#2 X 24....2 X 14 AWG)
Wire Type: solid or stranded, copper only Strip Length: 7 mm (9/32 in.), Torque: 0.5 N·m (4.4 lb·in)

B

C

D

27

7.5

1.02

(1-1/16)

(19/64)

(1/64)

27

15

2.3

(1-1/16)

(19/32)

(3/32)

1.0 (0.04)
35.0 (1.38)
7.5 (0.3)

27.0 (1.06)

Approx. Shipping Wt.
1.85 kg (4.07 lb) (10/pkg)
3.68 kg (8 lb) (5/pkg)

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

69

Relay and Timer Specifications

Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.

60.9

(2.40)

21 6

11 3

17.5 (0.69)

17.5 (0.69)

24

14

5

4

22

12

7

2

21.6 (0.85)

78.6 (3.09)

Ø 3.2 (0.12)
Use M3 Screws

35.4 (1.39)

1 (-)

8 (+)

A2

A1

4.0 (0.16)

15.8 (0.62)

Cat. No. 700-HN123 Single Wire: 0.2.....2.5 mm2 (#24.....14 AWG) Double Wire: 2 X 0.2.....2 X 2.5 mm2 (#2 X 24....2 X 14 AWG)
Wire Type: solid or stranded, copper only Strip Length: 7 mm (9/32 in.), Torque: 0.5 N·m (4.4 lb·in)

21.6 (0.85)

Cat. No. 700-HN230 Min wire size: 0.5mm2 (21 AWG.) Max wire size: 2 x 1.5 and 1 x 2.5 mm2 (2 x18 / 1 x 14 AWG)
Wire Type: solid or stranded, copper only
Stripe Length: 8mm (10/32 in.)

70

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

700-HJ Magnetic Latching Relay

· 10 A Contact Rating · SPDT · DPDT Single Coil · DPDT Dual Coil · Blade Style Quick Connect Terminals

Photo

Description

Contact Wiring Diagrams

Rating AC(2)

DC(3)

SPDT

1-Pole

1 Form C

AgCdO Contacts (Single Coil

10 A

AC or DC)

Sockets

700-HN153

700-HN154

DPDT

2-Pole

2 Form C

AgCdO Contacts (Single Coil

10 A

AC or DC)

Sockets

700-HN153

700-HN154

Relay and Timer Specifications

Coil Voltage Cat. No.

24V AC 120V AC

700-HJ36A24 700-HJ36A1

24V DC

700-HJ36Z24

24V AC 120V AC 240V AC

700-HJ32A24 700-HJ32A1 700-HJ32A2

12V DC

700-HJ32Z12

24V DC

700-HJ32Z24

DPDT 2-Pole 2 Form C AgCdO Contacts (Dual Coil(1)

10 A DC Only

24V DC

700-HJD32Z24

Sockets
(1) Available only in DC Coil with DPDT contacts. (2) AC Relays include internal diodes. (3) For DC operation, polarity must be observed.

700-HN153 or 700-HN154

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

71

Relay and Timer Specifications

Accessories-700-HJ Relays

Photo

Description

Pkg. Qty. Cat. No.

Screw Terminal Socket -- Panel or DIN Rail Mounting. Guarded Terminal Construction 11-blade socket for use with 700-HB relays. This socket has coil and contact separation as well as the 10 ability to use optional plug-in modules ( 700-A__ accessories, LED, surge suppression, timing modules).

700-HN153

Screw Terminal Base Socket -- Panel or DIN Rail Mounting. Open Style Construction 11-blade for use with 700-HB relays.

10

700-HN154

DIN (#3) symmetrical hat rail 35 x 7.5 x 1 m

10

199-DR1

Retainer Clip

For Cat. Nos. 700-HN153 and -HN154 Sockets with 700-HJ Relays

10

Secures relay in socket. Order must be for 10 clips or multiples of 10.

Pre-Printed Identification Tags -- contains 10 sheets of pre-printed and blank tags. Each sheet contains 13 sets of the markings CR...9CR, TR...9TR, M...9M, F, R, 1S, and 117 blank tags. Tags are 10 peel-off with sticky backing for easy placement on relays.
Blank Identification Tags -- contains 10 sheets of blank identification tags for customer specialized printing. Each sheet contains 546 blank tags. Tags are peel-off with sticky backing for easy placement on 10 relays.

Socket and Retainer Clip Reference

Relay Type 700-HJ

Socket Cat. No. 700-HN153 700-HN154

Retainer Clip Cat. No. 700-HN159 700-HN159

700-HN159 700-N40 700-N41

Specifications - 700-HJ Relays
Attribute Pilot Duty Rating Rated Thermal Current (Ith) Rated Insulation Voltage(Ui)
Contacts
Permissible Coil Voltage Variation

Inductive
120V AC 240V AC DC

700-HJ

Electrical Ratings

--

10 A

250V IEC, 300V UL/CSA

Make

Break

Hp

30 A

3 A

1/4

15 A

1.5 A

1/3

24V DC, 10 A

85...110% of Nominal Voltage at 50 Hz 85...110% of Nominal Voltage at 60 Hz 80...110% of Nominal Voltage at DC

72

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

Specifications - 700-HJ Relays

Coil Consumption ±10%

AC Coils DC Coils

Dielectric Withstand Voltage

Degree of Protection Mechanical Life Operations Switching Frequency Operations Coil Voltages Operating Time at Nominal Voltage at 20 °C Maximum Operating Rate
Temperature
Altitude
Insulating Material Enclosure Contact Material Terminal Markings on Socket Sockets Certifications Standards

Single AC Coil

Single DC Coil

Dual DC Coil

Inrush Sealed

1.44 VA 1.44 VA

--

--

--

1.2 W

12V 1.63 W 24V 1.67 W

Design Specification/Test Requirements

Pole-to-Pole

1500V AC

Contact-to-Pole

1500V AC

Contact-to-Frame

1500V AC

Mechanical

Open Type (Guarded Terminal Sockets)
10 x 106

1800/HR

See Product Selection

Pickup

25 ms

Dropout

25 ms

--

Environmental

Operating

­45...+50 °C (­49...+122 °F)

Storage

­45...+100 °C (­49...+212 °F)

2000 m (6560 ft)

Construction

Molded High Dielectric Material

Transparent Dust Cover

Silver Cad. Ox.

In accordance with EN50 0005

11-Blade Socket Cat. No. 700-HN153 Cat. No. 700-HN154

CSA Certified, File LR700026, UL Recognized, File E3125, Guide NLDX 2

UL 508, CSA 22.2 No. 14, EN/IEC 60947-4-1, -5-1

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

73

Relay and Timer Specifications
Dimensions - 700-HJ Relays
Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.

700-HJ Relay

Cat. No. 700-HN153 Wire Size: 2 x 2.5 mm2 Single Wire ­ Up to #12 AWG Double Wire ­ 2 x 2.5 mm2 (#2­14 AWG... #2­20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in) ­ Torque: 0.8 N·m (7 lb·in

Cat. No. 700-HN154 Wire Size: 2 x 2.5 mm2 Single Wire ­ Up to #12 AWG Double Wire ­ 2 x 2.5 mm2 (#2­14 AWG... #2­20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in) ­ Torque: 0.8 N·m (7 lb·in)

5.2 (13/64)

50 (1-63/64)

6.2

12.5

(15/64)

(1/2)

1.0 (0.04)
35.0 (1.38)

27.0 (1.06)

1000

7.5

(39-3/8)

(0.3)

Cat. No. 199-DR1 DIN Mounting Rail Series B Cat. No. 199-DR4 DIN Mounting Rail Series B Has No Mounting Holes

Cat. No. 199-DR1 199-DR4

A 35 (1-3/8) 35 (1-3/8)

B 27 (1-1/16) 27 (1-1/16)

C 7.5 (19/64) 15 (19/32)

D 1.02 (1/64) 2.3 (3/32)

Approx. Shipping Wt. 1.85 kg (4.07 lb) (10/pkg)
3.68 kg (8 lb) (5/pkg)

74

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

700-HG Power Relay

· 40 A Contact Ratings · SPST-NO-DM, SPDT, DPST-NO, DPDT · Panel Mounted · Options: Magnetic Blowout for High DC Loads, Auxiliary Snap Action Switch · Screw Terminals #6-32 for Coil, #8-32 for Contacts

Description

Contact Ratings Wiring Diagrams

SPST-NO-DM 1 Form X AgCdO Contacts

40 A (A600)

SPDT 1-pole 1 Form C AgCdO Contacts

40 A (A600)

DPST-NO 2-pole 2 Form A AgCdO Contacts

40 A (A600)

DPDT 2-pole 2 Form C AgCdO Contacts

40 A (A600)

(1) Auxiliary Snap Switch Option: Add suffix (-5) to the selected 700-HG relay Cat. No., except for the 220V DC add (-5L). Magnetic Blowout Option: Add suffix (-6) to the selected 700-HG relay Cat. No. (suppresses the arc when switching DC loads ­ ratings listed below).

Coil Voltage 24V AC 120V AC 240V AC 277V AC 480V AC 12V DC 24V DC 48V DC 110V DC 24V AC 120V AC 240V AC 12V DC 24V DC 48V DC 110V DC 24V AC 120V AC 240V AC 480V AC 12V DC 24V DC 48V DC 110V DC 24V AC 120V AC 240V AC 277 AC 12V DC 24V DC 48V DC 110V DC 220V DC 250V DC

Cat. No.(1) 700-HG45A24 700-HG45A1 700-HG45A2 700-HG45A27 700-HG45A4 700-HG45Z12 700-HG45Z24 700-HG45Z48 700-HG45Z1 700-HG46A24 700-HG46A1 700-HG46A2 700-HG46Z12 700-HG46Z24 700-HG46Z48 700-HG46Z1 700-HG47A24 700-HG47A1 700-HG47A2 700-HG47A4 700-HG47Z12 700-HG47Z24 700-HG47Z48 700-HG47Z1 700-HG42A24 700-HG42A1 700-HG42A2 700-HG42A27 700-HG42Z12 700-HG42Z24 700-HG42Z48 700-HG42Z1 700-HG42Z2 700-HG42Z25

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

75

Relay and Timer Specifications

Accessories - 700-HG Relays

Photo

Description

Pkg. Qty.

Pre-Printed Identification Tags -- contains 10 sheets of pre-printed and blank tags. Each sheet contains 13 sets of the markings CR...9CR, TR...9TR, M...9M, F, R, 1S, and 117 blank tags. 10 Tags are peel-off with sticky backing for easy placement on relays.

Blank Identification Tags -- contains 10 sheets of blank identification tags for customer specialized printing. Each sheet contains 546 blank tags. Tags are peel-off with sticky backing for 10 easy placement on relays.

Cat. No. 700-N40 700-N41

Type 1 Enclosure For use with any of the listed relays. Knockouts for 1/2 in. and 3/4 in. conduit connections. The enclosure exceeds the minimum clearances required by U.S. standards, resulting 1 in generous wiring spaces.

700-HN120

Auxiliary Snap Action Switch

Contact SPDT (1 Form C)

Material Silver Cad. Ox.

Rating 10 A at 120 or 240 Resistive

Dielectric Withstand V (1 Min.) 1500V AC RMS Contact to Frame

76

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

Specifications - 700-HG Relays

Attribute
Electrical Ratings Pilot Duty Rating (1) Rated Thermal Current (Ith) Rated Insulation Voltage(Ui)
Contact Ratings: AC Ratings SPST-NO-DM

700-HG
A600 40 A 600V UL Contact Ratings: AC Ratings SPDT, DPST - NO and DPDT

Inductive

Resistive -

Inductive

Resistive -

Volts

Make

Break

Make/Break

Continuous

and Continuous

HP Volts

Make

Break

Make/Break

Continuous

and Continuous

HP (2)

120

60 A

6 A

10 A

40 A

120 60 A

6 A

10 A

40 A

2

1 - 1/2

240

30 A

3 A

10 A

40 A

240 30 A

3 A

10 A

40 A

480V

15 A

1.5 A

10 A

12 A

480 15 A

1.5 A

10 A

5 A

2

1 - 1/2

600V

12 A

1.2 A

10 A

10 A

600 15 A

1.2 A

10 A

5 A

DC Ratings: Without Magnetic Blowouts - 28V 40 A - Make, Break and Continuous Est Drop 125V 1.2...3 A

DC Ratings: With Magnetic Blowouts:

SPST - NO DM

SPDT, DPST - NO and DPDT

110V

20 A

10 A

220V

8 A

4 A

Make, Break, and Continuous

325V

4 A

2 A

500V

2 A

--

80...100% of Nominal Voltage at 50 Hz

Permissible Coil Voltage Variation

85...110% of Nominal Voltage at 60 Hz

80...110% of Nominal Voltage at DC

50 HZ

60 HZ

Inrush

13 VA

16 VA

AC Coils

Coil Consumption ±10%

Sealed

10 VA

11 VA

DC Coils

2.0 W

Design Specification/Test Requirements

Dielectric Withstand Voltage

Pole-to-Pole Contact to Pole Contact to Frame

2200V AC 2200V 2200V AC

Mechanical

Degree of Protection Mechanical Life Operations

Open Type 5 x 106

Switching Frequency Operations

1600/Hr

Coil Voltage

See Overview/Product Selection

Operating Time at Nominal

Pickup

40 ms

Voltage at 20 °C (68 °F)

Dropout

35 ms

Maximum Operating Rate

--

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

77

Relay and Timer Specifications

Specifications - 700-HG Relays

Temperature Altitude

Operating Storage

Insulating Material
Enclosure Contact Material Terminal Markings on Socket Sockets Certifications Standards
(1) See NEMA Ratings and Test Values on page 5. (2) For DPDT only: 2 Hp Switching 2 Poles, 200...600V AV, 50/60 Hz.

Environmental 30...+55 °C (-22...+149 °F) -30...+65 °C (-22...+149 °F) 2000 m (6560 ft)
Construction Molded Thermo Setting Plastic --
Silver Cadmium Oxide -- --
CSA Certified, File 225674, UL Listed, File E3125, Guide NLDX, CE Marked UL 508, CSA 22.2 No. 14, EN/IEC 60947-1, -5-1

78

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications
Dimensions - 700-HG Relays
Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.
700-HG Relay, SPST-NO-DM
700-HG Relay

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

79

Relay and Timer Specifications

700-HHF Flange Mount Power Relay

· Flange-Mounted · Blade Style 0.250 x 0.032 Quick Connect/Solder (no socket) Terminals · Solder Terminals (no socket)

Description

Contact Rating

Wiring Diagrams U.S./Canada

International

SPST-NO-DM 1 Form X AgCdO Contacts

30 A (A600)

Coil Voltage 120V AC

Cat. No. 700-HHF45A1

24V DC

700-HHF45Z24

DPDT 2-Pole 2 Form C AgCdO Contacts

25 A (B600)

24V AC 120V AC 240V AC 12V DC
24V DC

700-HHF62A24 700-HHF62A1 700-HHF62A2 700-HHF62Z12
700-HHF62Z24

3PDT 3-Pole 3 Form C AgCdO Contacts

20 A (B300)

120V AC

700-HHF73A1

Specifications - 700-HHF Relays
Attribute Electrical Ratings

Pilot Duty Rating (1)

Rated Thermal Current (Ith) Rated Insulation Voltage(Ui)

Inductive

Contacts

120V AC 240V AC DC

700-HHF...

SPST-NO-DM

NEMA A600

DPDT

NEMA B600

3PDT

NEMA B300

SPST-NO-DM 30 A, DPDT 25A, 3PDT 20 A

250V IEC-300V UL/CSA

SPST-NO-DM

Hp

DPDT

Hp

3PDT

Hp

60 A

6 A

1

30 A

3 A

1

30 A

3 A

1/2

30 A

3.0 A

1-1/2

15 A

1.5 A 1-1/2

15 A

1.5 A

--

28V DC, 30 A

28V DC, 13 A

--

80

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

Specifications - 700-HHF Relays

Attribute

700-HHF...

85...110% of Nominal Voltage at 50 Hz

Permissible Coil Voltage Variation

85...110% of Nominal Voltage at 60 Hz

80...110% of Nominal Voltage at DC

SPST-NO-DM

DPDT

3PDT

50 Hz

60 Hz

50 Hz

60 Hz

50 Hz

Coil Consumption ±10%

AC Coils DC Coils

Inrush Sealed

7.2 VA

6.3 VA

7.2 VA

6.3 VA

7.2 VA

4.8 VA

4.2 VA

4.8 VA

4.2 VA

4.8 VA

1.4 W

Max. Allowable Leakage

25% of VA 10% of W

Design Specification/Test Requirements

Dielectric Withstand Voltage

Pole-to-Pole Contact-to-Pole Contact-to-Frame

2200V AC 2200V AC 1600V AC

Mechanical Mechanical Life Operations

5 x 106

Switching Frequency Operations

3600/Hr

Coil Voltages

See Overview/Product Selection

Operating Time at Nominal Pickup

20 ms

Voltage at 20 °C

Dropout

15 ms

Maximum Operating Rate

4 Ops/s.

Environmental

Temperature

Operating Storage

­30...+50 °C (­22...+122 °F) ­30...+100 °C (­22...+212 °F)

Altitude

2000 m (6560 ft)

Construction

Insulating Material

Molded High Dielectric Material

Enclosure

Transparent Dust Cover

Contact Material

Silver Cadmium Oxide

Terminal Markings Sockets

In accordance with EN50 0005
(2)

Certifications

cURus Recognized, File E3125,Guide NLDX2/NLDX8, CE Marked

Standards

UL 508, CSA 22.2 No.14, EN/IEC 60947-1, -5-1

(1) See NEMA Ratings and Test Values on page 5. (2) 700-HHF relay wiring and terminals are the quick connect / solder type 6.35 x 0.82 mm (0.250 x 0.032 in) termination.

60 Hz 6.3 VA 4.2 VA

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

81

Relay and Timer Specifications
Dimensions - 700-HHF Relays
Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.

35.7 (1-13/32)

3.97 (5/32)
38.9 (1-17/32)

700-HHF Relay

63.5 (2-1/2)
73.8 (2-29/32)

82

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

700-HTA Alternating Relay
· Alternating Relay · Rugged Pin Style Socket Mounting · 10 A, SPDT, DPDT, and Cross Wired · Excellent for Pump Panel Applications

700 ­ HTA

2

A12

7

a

b

c

d

e

Catalog Number Explanation - 700-HTA Relays

a Bulletin Number -

b Relay Type

c Model Type

1 - SPDT

700

HTA - Tube Base Alternating Relay

2 - DPDT

3 -Cross-Wired

Alternating Relays with Pin-Style Terminations

700-HTA

Alternating Relay

Wiring Diagrams U.S./Canada

d Coil Voltage
A12 - 12V AC 50/60 Hz A24 - 24V AC 50/60 Hz A1 - 120V AC 50/60 Hz A2 - 240V AC 50/60 Hz

e Gold Plated Contacts Option
Blank - Without switch 7 - With switch

International

SPDT Form C Contact

SPDT

DPDT 2 Form C Contact

DPDT

Cross-Wired DPDT 2 Form C Contacts

Cross-Wired

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

83

Relay and Timer Specifications

Accessories - 700-HTA Relays

Photo

Description

Pkg. Qty. Cat. No.

Screw Terminal Tube Base Socket -- Panel or DIN Rail Mounting; Guarded Terminal Construction. 8-Pin for use with 700-HTA1A or -HTA3A alternating relays. Order ten or multiples of ten.

10

700-HN100

Screw Terminal Tube Base Socket -- Panel or DIN Rail Mounting; Open Style Construction. 8-Pin for use with 700-HTA1A or -HTA3A alternating relays. Order ten or multiples of ten. No retainer clip required.

10

700-HN125

Screw Terminal Tube Base Sockets -- Panel or DIN Rail Mounting; Guarded Terminal Construction. 11pin for use with 700-HTA2A alternating relays. Order in multiples of 10.

10

700-HN101

Screw Terminal Tube Base Sockets -- Panel or DIN Rail Mounting; Open Style Terminal Construction. 11-pin for use with 700-HTA2A alternating relays. Order in multiples of 10. No retainer clip required.

10

700-HN126

DIN (#3) symmetrical hat rail 35 x 7.5 x 1 m

10

199-DR1

Retainer Clip for Cat. Nos. 700-HN100 and -HN101 Sockets with 700-HT Timing Relays, and 700-HTA

Alternating Relays

10

Secures relay in socket. Order must be for 10 clips or multiples of 10.

700-HN110

Pre-Printed Identification Tags -- contains 10 sheets of pre-printed and blank tags. Each sheet contains 13 sets of the markings CR...9CR, TR...9TR, M...9M, F, R, 1S, and 117 blank tags. Tags are peel-off with sticky backing for 10 easy placement on relays.

700-N40

Blank Identification Tags -- contains 10 sheets of blank identification tags for customer specialized printing. Each sheet contains 546 blank tags. Tags are peel-off with sticky backing for easy placement on relays.

10

700-N41

84

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

Specifications - 700-HTA Relays
Attribute
Pilot Duty Rating (1) Rated Thermal Current (Ith) Rated Insulation Voltage(Ui)

Electrical Ratings

Inductive

Make

700-HTA

NEMA B300 AC 15

10 A

250V IEC, 300V UL/CSA

Break

HP

Contacts

120V AC

30 A

3 A

1/3

240V AC

15 A

1.5 A

1/2

Resistive 30V DC

10 A

10 A

--

Permissible Coil Voltage Variation

85...110% of Nominal Voltage at 50 Hz 85...110% of Nominal Voltage at 60 Hz

24V AC

2 VA

Power Consumption ±10%

AC

120V AC

4 VA

240V AC

4 VA

Design Specification/Test Requirements

Pole-to-Pole, same circuit (VRMS)

1000V AC

Dielectric Withstand Voltage

Pole-to-Pole, different circuits (VRMS)

2000V AC

Contact-to-Coil (VRMS)

2000V AC

Electrical Life Operations

100,000 minimum

Switching Frequency Operations

1800/hr

Coil Voltages

See product selection

Mechanical

Degree of Protection Mechanical Life Operations

Open Type (Guarded Terminal Sockets) 10 x 106

Switching Frequency Operations

18,000/hr

Start-up Time (max. time from power application until unit is timing)

0.05 sec

Max. Function Time (max. time power can drop out and unit continues timing)

0.01 sec

Min. Cycle Time

100 ms on release of the control switch

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

85

Relay and Timer Specifications
Specifications - 700-HTA Relays
Attribute
Temperature
Altitude Insulating Material Enclosure Contact Material Terminal Markings on Socket Sockets
Certifications Standards
(1) See NEMA Ratings and Test Values on page 5.

Operating Storage

700-HTA
Environmental
­28...+65 °C (50 °C max., 240V AC coil) (­18...+149 °F) (122 °F max., 240V AC coil)
­55...+85 °C (­67...+185 °F)
2000 m (6560 ft)
Construction
Molded High Dielectric Material
Impact Resistant Dust Cover
Silver Tin Oxide
In accordance with EN50 005
8- or 11-Pin Socket 700-HN100, -HN125 700-HN101, -HN126
CSA Certified, File 223833, UL Recognized (File E3125 Guide NLDX2/NLDX8), cULus Listed with 700-HN100, 700-HN101, 700-HN125, and 700-HN126
Sockets (File No. E3125 Guide NLDX/NLDX7), CE-Marked (per EU Low Voltage Directive)
EN 61812-1, CSA 22.2 No. 14, UL 508

86

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

Trigger Signal Cat. Nos. 700-HTA
Contact closure provides signal to timer. The 700-HTA alternating relay generates a low energy signal. For optimum reliability, use contacts designed for low energy switching (10V, 1 mA) (Example: Bul. 800F-X_V, 800T-X_V). No external voltage can be connected to the contact signal.
Load Diagrams - 700-HTA Relays

Common Input/Output SPDT/DPDT
B1 Load A Load B LED A LED B Power

Socket Pinout Map
SPDT
Relay Socket A1 4
A2 3

Socket Pinout Map
DPDT
Relay Socket A1 4
A2 8

Note: pin out in wiring diagram may not match actual printed socket see pinout map for wiring up the power source

Cross Wired Lead/Lag/Lag/lead Sequence
Lead Lag
Load A Load B LED A LED B Power
Socket Pinout Map Cross-Wired Relay Socket A1 3 A2 6
Note: pin out in wiring diagram may not match actual printed socket see pinout map for wiring up the power source

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

87

Relay and Timer Specifications
Dimensions - 700-HTA Relays
Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.

74 (2-29/32)

79 (3-7/64)

60 (2-23/64)
43 (1-11/16)

30.0 (1-3/16)
65.0 (2-35/64)

26 (1-1/32)

38.0 (1-1/2)

#4­40 M3

Cat. No. 700-HN100 Panel Mounting
Double Wire -- 2 x 2.5 mm2 (#2 ­ 14 AWG...#2 ­ 20 AWG) (Either Solid or Stranded)
Strip Length: 9 mm (3/8 in) ­ Torque: 0.8 N·m (7 lb·in)

40.1 (1-37/64)

24.6 (31/32)
20.8 (53/64)

24.9 (63/64)
4.2 (5/32)

54.9 (2-5/32)
51.1 (2-1/64)

33.0 (1-19/64)

14.7 (37/64)

Cat. No. 700-HN125 Wire Size: 2 x 2.5 mm2 Single Wire -- Up to #12 AWG Double Wire -- 2 x 2.5 mm2 (#2 ­ 14 AWG... #2 ­ 20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in) -- Torque: 0.8 N·m (7 lb·in)

65.0 (2-35/64)

30 (1-3/16)

26 (1-1/32)

38.0 (1-1/2)

#4-40 M3

Cat. No. 700-HN101 Panel Mounting
Double Wire ­ 2 x 2.5 mm2 (#2 ­ 14 AWG...#2 ­ 20 AWG) (Either Solid or Stranded)
Strip Length: 9 mm (3/8 in) ­ Torque: 0.8 N·m (7 lb·in)

59.2 (2-1/3)
7.9 (0.31)

26.9 (1.06)

24.6 (31/32)
20.8 (53/64)

54.9 (2-5/32)

4.2 (5/32)

51.1 (2-1/64)

52.3 (2.06)
Cat. No. 700-HN126 Wire Size: 2 x 2.5 mm2 Single Wire -- Up to 12 AWG Double Wire -- 2 x 2.5 mm2 (#2 ­ 14 AWG...#2 ­ 20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in) -- Torque: 0.8 N·m (7 lb·in)

88

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

General Purpose Electronic Timers and Counters
Product Overview

Relay and Timer Specifications

Bulletin No. Type
Features
Control Outputs: Time Limit Instantaneous
Operation Modes:
Time Range Supply Voltage Contact Rating at 120V AC Certifications Socket Cat. No(s). Page

700-FE
DIN Rail Timer
· Only 17.5 mm wide · 5 A contact rating · Multifunction or single
function · No additional socket
required
1 N.O. or SPDT timed
On-delay Off-delay One shot Repeat cycle-pulse Fleeting off-delay Pulse converter
0.05 s...10 hr 24V AC/DC 110...240V AC 24...48V AC/DC 24...240V AC
5 A
CE, cULus
DIN Rail or panel mount
92

700-FS
DIN Rail Timer
· Only 22.5 mm wide · 8 A contact rating · Multifunction or single
function · No additional socket
required · Optional: · Star-delta timing
function · True off-delay timing
function · Hazardous location
certification
SPDT or DPDT or 2 N.O. + 1 common
11 timing modes
0.05 s...60 hr
12V DC 24V...48V DC 24V...240V AC
8 A
CE, cULus
DIN Rail or panel mount
96

700-HR52, -HRP, -HRS, -HRT, -HRV

700-HRM/-HRC

700-HRF

Multifunction Timer

On-Delay Timer

Twin Timer

· Dial timing relays · 5 A contact rating · Multiple programmable
timing ranges · Tube base pin style
terminals · Multi-voltage inputs · Timed contacts and
instantaneous contacts · Transistor outputs · Single function and
multi-function · 7 different operating
modes

· Dial timing relays · 5 A contact rating · Multiple programmable
timing ranges · Tube base pin-style
terminals · Multi-voltage inputs · Timed contacts and
instantaneous contacts · Transistor outputs · Single function and
multi-function

· Independent ON and OFF settings
· 14 time ranges · 8-pin models available · Dial timing relays · UL508

DPDT Timed, Transistor SPDT Timed/Instantaneous

DPDT Timed, Transistor SPDT Timed/Instantaneous

DPDT Timed

On-Delay Off-Delay One Shot Repeat Cycle Off Start Repeat Cycle On Start Signal On/Off-Delay On-Delay One Shot
0.05 s...300 h
12...48V DC 24...48V AC 100...240V AC 100...125V DC

On-Delay
0.05 s...300 h 12...48V DC 24...48V AC 100...240V AC 100...125V DC

Repeat Cycle Off Start Repeat Cycle On Start
0.05 s...300 h 12V DC 24V AC/DC 48...125V DC 100...240V AC

5 A

5 A

5 A

cURus, CE, C-Tick

cURus, CE, C-Tick

700-HN100 OR 700-HN101 700-HN100 700-HN125 OR 700-HN126 700-HN125

116

117

cURus, CE, C-Tick
700-HN100 700-HN125
117

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

89

Relay and Timer Specifications

Bulletin No. Type

700-HRY Star-Delta Timer

700-HRQ True Off-Delay Timer

Features

· A wide star-time range (up to 120 s)
· Star-delta transfer time range (up to 0.5 s)
· UL Recognized

· Dial timing relays · Long power Off-delay times · 11-pin and 8-pin models are
available · UL Recognized

Control Outputs: Time Limit Instantaneous

SPST (Star, Delta) Timed SPST - NO Instantaneous

Operation Modes: Star-Delta

Time Range

0.5 s...120 s

Supply Voltage

100...120V AC 200...240V AC

Contact Rating at 120V AC Certifications
Socket Cat. No(s).
Page

5 A
cURus, CE, C-Tick 700-HN100 700-HN125 117

DPDT Timed
True OFF-delay Timer True OFF-delay Timer w/reset
0.05 s...12 min 48V DC 24V AC/DC 100...240V AC 100...125V DC
5 A
cURus, CE, C-Tick 700-HN100 OR 700-HN101 700-HN125 OR 700-HN126 118

700-HNC

700-HNK

Miniature Timer

Ultra-Slim Timer

· Four different operating modes · DIN Rail mount with socket · Pin configuration same as 700-HC
relay

· Ultra-slim timing relay · Four different operating
modes · Three operating voltages · DIN Rail mount with
socket · Pin configuration same as
700-HK relay

4PDT

SPDT, DPST-NO

On-Delay One Shot Repeat Cycle Off Start Repeat Cycle On Start
0.1 s...10 h
12V DC 24V AC/DC 48...125V DC 100...240V AC
5 A
cURus, CSA, CE, C-Tick
700-HN103 700-HN128
103

On-Delay One Shot Repeat Cycle Off Start Repeat Cycle On Start
0.1 s...10 h
12V DC 24V DC 24V AC
5 A
cURus, CE, ACA
700-HN121 700-HN122
109

90

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

Bulletin No.
Type

700-HT Tube Base Timing Relay

700-HV Repeat-Cycle Timing Relay

Features

· Pin-style terminals · Single range or fixed timers · Available as ON- or OFF-Delays

· Pin-style terminals · Single-range timer · Repeat cycle

Control Outputs: Time Limit Instantaneous

DPDT

DPDT

Timing Operation Modes:

On-Delay Off-Delay

Repeat Cycle

Time Range
Supply Voltage
Contact Rating at 120V AC Certifications
Socket Cat. No(s). Page

0.1 s...30 min.
12V DC 24V DC 24V AC 120V AC 240V AC
10 A
UR, UL, CSA, CE
700-HN100 OR 700-HN101 700-HN125 OR 700-HN126
128

0.1 s...30 min.
24V DC 24V AC 120V AC 240V AC
10 A
UR, UL, CSA, CE
700-HN100 700-HN125
133

700-HX
Digital Timer
· Digital timer · 5 A contact rating · Negative transmissive LCD display · 10 functions or modes · Environmentally friendly--flash memory, no
battery · NEMA B300 rated · NEMA 4/IP66 · DIN Rail or panel mount capable
SPDT
Signal On-Delay 1 and 2 Signal Off-Delay One Shot Repeat Cycle Off Start Repeat Cycle On Start Signal On/Off-Delay Power On-Delay 1 and 2 Twin Timer Cumulative
0.05 s...300 h
12...24V DC 24V AC 100...240V AC
5 A
cURus, CE, C-Tick
700-HN100 700-HN125
138

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

91

Relay and Timer Specifications

700-FE Economy Timing Relay
· Adjustable function and timing range timing relays · DIN Rail mounted without cost of socket · 17.5 mm wide, multi-function or single function · Available as 1 N.O. or SPDT contact output, 5 A · Timing ranges from 0.05 s...10.0 hr · Coil surge protection

Multi-Function

This device offers you the flexibility of selecting one of 4 single timing functions.

Operating Mode

Contact Output

Timing Range(1)

ON-delay, OFF-delay, One Shot, Flasher (repeat cycle starting with pulse)

1 N.O.

0.05 s...10 hr (6 settings)

ON-delay, OFF-delay, One Shot, Flasher (repeat cycle starting with pulse)

SPDT (1 C/O)

(1) Time ranges: 0.05 s...1 s, 0.5...10 s, 0.05...1 min, 0.5...10 min, 0.05...1 hr, 0.5...10 hr. (2) Voltage is either 24V AC/DC 50/60 Hz.

0.05 s...10 hr (6 settings)

Input Voltage
24V AC/DC (2) 110...240V AC 50/60 Hz
24V...48V AC/DC 24...240V AC 50/60 Hz

Cat. No. 700-FEM1TU22 700-FEM3TU23

Single-Function

This device offers you one specific timing function.

Operating Mode Contact Output

Timing Range(1)

ON-delay

1 N.O. SPDT (1 C/O)

0.05 s...10 hr (6 settings) 0.05 s...10 hr (6 settings)

OFF-delay

1 N.O. SPDT (1 C/O)

0.05 s...10 hr (6 settings) 0.05 s...10 hr (6 settings)

One Shot

1 N.O. SPDT (1 C/O)

0.05 s...10 hr (6 settings) 0.05 s...10 hr (6 settings)

Fleeting OFF-delay SPDT (1 C/O)

0.05 s...10 hr (6 settings)

Flasher (repeat cycle starting with pulse)

1 N.O. SPDT (1 C/O)

0.05 s...10 hr (6 settings) 0.05 s...10 hr (6 settings)

Pulse Converter

SPDT (1 C/O)

0.05 s...10 hr (6 settings)

(1) Time ranges: 0.05 s...1 s, 0.5...10 s, 0.05...1 min, 0.5...10 min, 0.05...1 hr, 0.5...10 hr. (2) Voltage is either 24V AC 50/60 Hz or 24V DC.

Input Voltage
24V AC/DC 110...240V AC 50/60 Hz(2)
24V...48V AC/DC 24...240V AC 50/60 Hz
24V AC/DC 110...240V AC 50/60 Hz(2)
24V...48V AC/DC 24...240V AC 50/60 Hz
24V AC/DC 110...240V AC 50/60 Hz(2)
24V...48V AC/DC 24...240V AC 50/60 Hz
24V...48V AC/DC 24...240V AC 50/60 Hz
24V AC/DC 110...240V AC 50/60 Hz(2)
24V...48V AC/DC 24...240V AC 50/60 Hz
24V...48V AC/DC 24...240V AC 50/60 Hz

Cat. No. 700-FEA1TU22 700-FEA3TU23 700-FEB1TU22 700-FEB3TU23 700-FED1TU22 700-FED3TU23 700-FEE3TU23 700-FEF1TU22 700-FEF3TU23 700-FEL3TU23

Special Functions

Operating Mode Star-Delta

Contact Output 2 N.O. with 1 Common

Timing Range(1) 0.15 s...10 min (4 settings)

Input Voltage
24V...48V AC/DC 24...240V AC 50/60 Hz

(1) Time ranges: 0.15...3 s, 0.5...10 s, 3 s...1 min, 30 s...10 min.

92

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Cat. No. 700-FEY2QU23

Relay and Timer Specifications

Accessories - 700-FE Relays
Description

Pkg. Quantity

Cat. No.

Panel Mounting Adapter For surface mounting according to drilling plan EN 50 002

5

199-FSA

Label Sheet 105 self-adhesive paper labels each, 6 x 17 mm
Function and Connection Diagrams - 700-FE Relays

10

100-FMS

(A) On-Delay
U Output t
LED

A1/A2
18 15

A1/A3

15

A2

18

1 N.O. (SPST)

U Output t
LED
(D) One Shot

A1/A2 151186

A1

15

A2

18 16

1 C/O (SPDT)

(B) Off-Delay

U

S

Output

t

LED

A1/A2 A1/B1
18 15
1 N.O. (SPST)

A1 B1 S 15

A2

18

U

S

Output

t

LED

A1/A2
A1/B1 18
15 16

A1 B1 S 15

A2

18 16

1 C/O (SPDT)

(F) Flasher (Repeat Cycle Starting with Pulse)

U Output t
LED

A1/A2 1518

A1

15

A2

18

1 N.O. (SPST)

U Output
LED

A1/A2

t

t

t

t

18 t 15

A1

15

A2

18

1 N.O. (SPST)

U
Output t LED

A1/A2 151186

A1

15

A2

18 16

1 C/O (SPDT)

(E) Fleeting Off-Delay

U Output
LED

t tt

A1/A2

t

t

18 1516

A1

15

A2

18 16

1 C/O (SPDT)

(L) Pulse Converter

A1/A2 B1 t
LED
1 C/O (SPDT)
(Y) Star-Delta Timing Relay

1)

S

A1 B1

15

A2

18 16

U S Output t LED

A1/A2
A1/B1 t 151186

1)

S

A1 B1

15

A2

18 16

U

A1/A2

t

17/18



17/28

tu = 50...65 ms

LED

A1

17

A2

18 28



Bi-color light-emitting diode: 1 C/O (SPDT) or 1 N.O. Contact Timers

Single Color light-emitting diode: 2 N.O. with Common

LED U = green: Supply voltage available. LED Relay = red: Output is energized.

ON = green OFF = red

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

93

Relay and Timer Specifications

Specifications - 700-FE Relays(1)

Attribute

700-FE

1 N.O.

SPDT

Setting Accuracy Repeatability Tolerance

Supply Voltage AC
Voltage Tolerance DC
Power Consumption Time Energized Reset Time Cable Length (Supply Voltage Control)
Impulse Duration Input Voltage Input Current
Cable Length

Contact Type
Dielectric Withstand Voltage

Contact-to-coil Power

Switching Capacity

According to IEC 9475-1

According to UL 508 Short circuit Resistance
Mechanical Life
Electrical
State Indicator Certifications Standards
Insulation Characteristics

EMC/Interference Immunity
EMC / Emission
(1) Time Characteristics (according to VDE 0435, part 2021)

±5% of full scale

±1% of setting (typical)

By voltage: ±0.01%/%U By temperature: ±0.25%/°C

By voltage: ±0.001%/%U By temperature: ±0.025%/°C

Supply 24V AC/DC(1) and 110...240V AC, 50/60 Hz

24...48V DC and 24...240V AC, 50/60 Hz

­15%/+10%

­15%/+20%

0.5 W at 24V DC, 5VA at 240V AC

100%

100 ms

Max. 250 m (750 feet)

Pulse Control (B1)

 250 ms

 50 ms (AC),  30 ms (DC)

supply voltage range

1 mA

Max. 250 m without parallel load between B1 and A2 Max. 50 m with load (< 3 k between B1 and A2

Outputs

1 N.O. contact

1 Form C ­ SPDT contact

4000V

1250VA

AC-1

5 A /250V AC (resistive load)

AC-14

1 A/250V AC (inductive load)

DC-13

1 A/24V DC (inductive load)

NEMA D300 - 1 A/300V AC

6 A gL (Fast Blow Fuse)

20 million operations

0.4 million at 1 A/250V AC, resistive 0.4 million at 0.5 A/250V AC, cos  = 0.4
0.4 million at 1 A/24V DC, resistive

1 bicolor light-emitting diode (Supply; Relay)

cULus Listed (File No. E14840, Guide NKCR/NKCR7), CE Marked

EN/IEC 60947-1, EN/IEC 60947-5-1, UL 508, CSA 22.2 No. 14

2 kV AC/50 Hz test voltage according to VDE 0435 and 4 kV 1.2/50 s surge voltage according to IEC 60947-1 between all inputs and outputs

The following requirements are fulfilled: Surge capacity of the supply voltage according to IEC 61000-4-5: Level 3
Burst according to IEC 61000-4-4: Level 3 ESD discharge according to IEC 61000-4-2: Level 3

electromagnetic fields according to EN 55 022: Class B

94

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

Attribute Safe Isolation Climatic Withstand Vibration Resistance Shock Resistance Protection Class IEC 60947-1 Weight Certifications
Ambient Temperature
Connections
Mounting Disposal
(1) Voltage is either 24V DC or AC 50/60 Hz.

700-FE

according to VDE 0106 T 101

56 cycles (24 hr) at 25...40 °C and 95% relative humidity according to IEC 60068-2-30

4 g in three axes at 10...500 Hz, test FC according to IEC 60068-2-6

50 g according to IEC 68-2-27

Enclosure: IP40 Terminal: IP 20

60 g

60 g

cULus, CE Certified

cULus, Germanischer Lloyd, CE Certified

Open: ­25...+60 °C
Enclosed: ­25...+45 °C Storage: ­40...+85 °C

Screw terminal M3 for Pozidriv No.1, Philips, and slotted screws No.2. suitable for power screwdriver.
Rated tightening torque 8.8 lb.-in. (max. 1.0 Nm) For terminal cross-sections of 1 x 0.5 mm2...2 x 1.5 mm2 (solid) or 2 x 1.5 mm2 (stranded with sleeve), #20...14 AWG. Finger
protection according to EN 50274

For surface mounting in any position; snap-on mounting on 35 mm DIN Rail or by adapter and two screws (M4 type)

Synthetic materials without dioxin according to EC/EFTA-Notification No. 93/0141/D electrical contacts are AgCdO

Dimensions - 700-FE Relays
Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.

80.0 (3-5/32)

43.0 (1-11/16)
45.0 (1-25/32)

17.5 (11/16)

66.0 (2-9/16)
70.0 (2-49/64)
Cat. No. 700-FE...

22.5 (0.89)

13 (0.51)

4.3 (0.17)

75.0
(2.95) 35.0
(1.38)58.0
(2.28)

4.3 (0.17)
9.0 (0.35)

17 12 (0.67) (0.47)

2.0 (0.08)

5.5 (0.22)

Cat. No. 199-FSA...

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

95

Relay and Timer Specifications
700-FS High Performance Timing Relay
· Adjustable function and timing range timing relays · DIN Rail mounted without cost of socket · 22.5 mm wide multi-function or single functions · Available as SPDT or DPDT contact output, 8 A · Timing Ranges From 0.05 s...60 hr · Coil surge protection · Hazardous location version available
Catalog Number Explanation - 700-FS Relays

700 ­ FS

H

a

b

c

3

U ­ U23

d

e

f

a

b

Bulletin - Type of

Number

Relay

c Operating Mode

A­On-delay

B­Off-delay

C­On- and off-delay

D­One shot

E­Fleeting off-delay

700

FS

F­Flasher (repeat cycle starts with pulse)

G­Flasher (repeat cycle starts with pause)

I­On-delay pulse generator

J­On-delay (pulse controlled)

K­One shot/watch dog (pulse controlled)

L­Pulse converter

d Contact Output

e Timing Range

f Input Voltage

3­One changeover contact (SPDT)1 C/O

A­0.05...1 s B­0.15...3 s C­0.5...10 s D­1.5...30 s E­0.05...1 min F­0.15...3 min G­0.5...10 min H­1.5...30 min I­0.05...1 hr J­0.15...3 hr K­0.5...10 hr L­3.0...60 hr U­0.05 s...60 hr (1)

Z12­12V DC U23­24...48V DC | 24...240V AC 50/60 Hz

(1) Valid for functions "A" and "B" only.

Single Function (With 2PDT 2 C/O contacts)

Operating Mode On-delay

Contact Output (DPDT) 2 C/O

Timing Range(1)

On-delay Off-delay

(DPDT) 2 C/O (DPDT) 2 C/O

0.05 s...60 hr

Off-delay

(DPDT) 2 C/O

(1) The time range of "0.05 s...60 hr" is selectable in 12 smaller ranges plus an ON and OFF function for maintenance needs.

Input Voltage
12V DC
24...48V DC 24...240V AC, 50/60 Hz
12V DC
24...48V DC 24...240V AC, 50/60 Hz

Single Function With Hazardous Location Certification(1) (With SPDT 1 C/O contacts)

Operating Mode
One Shot / Watch Dog (Pulse Controlled)

Contact Output (SPDT) 1 C/O

Timing Range 0.05 s...1 s 0.5 s...10 s

Input Voltage
24...48V DC 24...240V AC 50/60 Hz

Cat. No. 700-FSA4UZ12 700-FSA4UU23 700-FSB4UZ12 700-FSB4UU23
Cat. No. 700-FSK3AU23-EX 700-FSK3CU23-EX

96

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

Multi-Function
This device allows the flexibility of selecting one of 8 single timing functions.

Operating Mode

Contact Output (SPDT) 1 C/O

Multi-function timing relays 8 Single-functions: A, B, C, D, E, F, I, and L ON and OFF function additional (for installation and maintenance) note: See connection diagrams for further description.

(SPDT) 1 C/O (DPDT) 2 C/O (DPDT) 2 C/O

Timing Range 0.05 s...60 hr

Input Voltage
12V DC
24...48V DC 24...240V AC 50/60 Hz
12V DC
24...48V DC 24...240V AC 50/60 Hz

Cat. No. 700-FSM3UZ12 700-FSM3UU23 700-FSM4UZ12 700-FSM4UU23

Multi-Function With Hazardous Location Certification (1)

This device allows the flexibility of selecting one of 8 single timing functions.

Operating Mode
M Multi-function timing relays 8 Single-functions: A, B, C, D, E, F, I, and L ON and OFF function additional (for installation and maintenance) Note: See connection diagrams for further description.

Contact Output (SPDT) 1 C/O
(DPDT) 2 C/O

(1) The time range of "0.05 s...60 hr" is selectable in 12 smaller ranges plus an ON and OFF function for maintenance needs.

Timing Range(1) 0.05 s...60 h

Input Voltage
24...48V DC 24...240V AC 50/60 Hz

Cat. No. 700-FSM3UU23-EX
700-FSM4UU23-EX

Special Function
Operating Mode

Contact Output

Timing Range

Flasher (repeat cycle starting with pulse or pause)

(SPDT) 1 C/O

0.05 s...60 hr (2) 2 x 0.05 s...60 hr (2 ranges)

OFF-delay without supply voltages (True OFF-delay)(1)

(SPDT) 1 C/O (DPDT) 2 C/O

0.15 s...10 min(3)

0.5 s...10 s

1.5...30 s

Star-Delta

2 N.O. + 1 Common 0.05 s...1 min

0.15...3 min

0.5...10 min

(1) Due to shock during shipment, the state of the contacts should be verified before initial use. Minimum power on time is 800 msec. (2) The time range of "0.05 s...60 hr" is selectable in 12 smaller ranges plus an ON and OFF function for maintenance needs. (3) This time range is selectable in four smaller ranges: 0.15 s...2.5 s, 0.5 s...10 s, 4 s...80 s, 30 s...10 min.

Input Voltage
12V DC
24...48V DC 24...240V AC 50/60 Hz
12V DC
24...48V DC 24...240V AC, 50/60 Hz
24...240V DC 24...240V AC 50/60 Hz
24...48V DC
24...240V AC 50/60 Hz

Cat. No. 700-FSH3UZ12
700-FSH3UU23
700-FSH3VZ12 700-FSH3VU23 700-FSQ3QU18 700-FSQ4QU18 700-FSY2CU23 700-FSY2DU23 700-FSY2EU23 700-FSY2FU23 700-FSY2GU23

(1) Temp. Code T4A 2A 32VDC MAX.: II 3 G, EEx nL IIC T4 DEMKO 04 ATEX 0404974X 2A 32VDC MAX. Ta 70 °C Ind. Cont. Eq. for Hazardous Location Listed 87SL Class 1, Div. 2, Groups A,B,C,D Class 1, Zn 2, Group IIC
Subject devices are to be installed in an ATEX Certified IP54 (as defined in IEC 60529) enclosure and accessible only by the use of a tool.

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

97

Relay and Timer Specifications

Multi-Function Timing Relay Function and Time Range Settings - 700-FS Relays

Description

SPDT

DPDT

(1) For installation and maintenance.

Multi-function timing relays 700-FSM3U includes 10 setting functions:

Multi-Time Setting Range 0.05 s...60 h

(A)On-Delay

(B)Off-Delay (C)On- and Off-Delay (D)One shot (E)Fleeting Off-Delay (F)Flasher (repeat cycle starts with pulse) (I)On-Delay pulse generator (L)Pulse converter (On)ON-Function (1) (Off)OFF-Function(1)

(1 s) 0.05...1 s (3 s) 0.15...3 s (10 s) 0.5...10 s (1 min) 0.05...1 min (3 min) 0.15...3 min (10 min) 0.5...10 min (1 hr) 0.05...1 hr (3 hr) 0.15...3 hr (10 hr) 0.5...10 hr (60 hr) 3....60 hr

Note: Switch  is on DPDT relays only. When switch is down, one contact is instantaneous and one is timed. When switch is up, both contacts are timed.

Accessories - 700-FS Relays

Description

Pkg. Quantity

Cat. No.

Setting Knob with Scale (for time setting without tools)

10

700-FSK

Panel Mounting Adapter For surface mounting according to drilling plan EN 50 002

5

199-FSA

Label Sheet 105 self-adhesive paper labels each, 6 x 17 mm

10

100-FMS

Marking Tag Sheet 160 perforated paper labels each, 6 x 17 mm, to be used with a transparent 10 cover

100-FMP

Transparent Cover To be used with marking tag sheets

100

100-FMC

Marking Tag Adapters To be used with marking tag: System 1492 W

100

(1) 100-FMA2

(1) Cat. No. 100-FMA2 is only a marking tag carrier. Please refer to the Terminal Block Accessories section, Marking Solutions of this publication for appropriate marker cards to be used with this carrier.

IMPORTANT Versatile Mounting: The 700-FS timing relay can be panel or DIN rail mounted. For best long-term performance, allow at least 5 mm (0.2 in.) of space on each side of the relay for proper ventilation.

98

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Function and Connection Diagrams - 700-FS Relays
(A) On-Delay

Relay and Timer Specifications (G) Flasher (Repeat Cycle Starts with Pause)

Output

(B) Off-Delay (Min. Pulse AC 50 ms...DC 30 ms)

(C) On- and Off-Delay
Output LED
(D) One Shot

(1) (3)

Output (3)
(E) Fleeting Off-Delay (Min. Pulse AC 50 ms...DC 30 ms)

(1)

Output

t

LED (3)

(F) Flasher (Repeat Cycle Starts with Pulse)

(I) On-Delay Pulse Generator

Output LED
(3)
(J) On-Delay (Pulse Controlled)
(1)
Output LED
(K) One Shot/Watch Dog (Pulse Controlled)

(1)
Output LED
(On) ON-Function (Off) OFF-Function

Output 1 Output 2
LED

Output 1 Output 2
LED

(L) Pulse Converter (Min. Pulse AC 50 ms...DC 30 ms)

(1)
Output LED
(3)

Output
(1)

Cleverly Designed Function Display light-emitting diode (Green)
(3) Output in Rest Position, No Timing Output in Rest Position, Time Running Output in Operation Position, No Time Running Output in Operation Position, Time Running

(1) A voltage other than the supply voltage can be used at B1, but must be within voltages specified on timer. (2) Output 2 is selectable as instantaneous contact with sliding switch () on front panel (instantaneous when switch is down, timed when switch is up). (3) Available on multifunction "M," and single function "A" or "B" option timing relays along with code "4" (2PDT contacts).
Bridge or potentiometer 10 k, 0.25 W min. (low voltage) for external time setting. Set timer dial to 0.0.

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

99

Relay and Timer Specifications

Special Function Flasher Timing Relay

Description

1 Range Setting
700-FSH3U

t2 Setting

Up Down

Switch

Seperate Range Settings

t1 Setting
700-FSH3V

Supply Voltages (A1/A2) Z12 12V DC U23 24...48V DC, 24...240V AC, 50/60 Hz

Function Diagram / Connection Diagram(1)

(H) Flasher (Repeat Cycle Starting with Pulse or Pause)
The repeat cycle timer permits different settings for on and off times. The following operating modes are possible: · Oscillating mode; repeat cycle starts with voltage that is applied at A1 and B1, and continues to repeat until voltage is off. · One cycle mode; started by energizing B1 with voltage on A1 and A2. · Output starts with pulse or pause (switch  Up or Down). · 700-FSH3U provides (1) range setting for t1 and t2
700-FSH3V provides (2) range settings for t1 and t2

Supply Voltage Controlled, Oscillating Mode Starting with Pause -- Switch  Is up

Supply Voltage Controlled, Oscillating Mode Starting with Pulse -- Switch  is Down

U

A1/A2

S

A1/B1

t2

t2

Output t1

t1

151186

LED

A1 B1 15

A2

18 16

U

A1/A2

S t1

t1 A1/B1

Output

t2

t2

15

18 16

LED

A1 B1 15

A2

18 16

Pulse Controlled, Output Starts With Pause (Min. Pulse AC 50 ms -- DC 30 ms) -- Switch  is Up One Cycle Mode -- Voltage Supplied at A1 and A2, then Pulsing "s" to Energize B1 will
Initiate One Cycle.

Pulse Controlled, Output Starts with Pulse (Min. Pulse AC 50 ms -- DC 30 ms) -- Switch  is Down One Cycle Mode -- Voltage Supplied at A1 and A2, then Pulsing "s" to Energize B1 will
Initiate One Cycle.

U S
Output LED

A1/A2

A1/B1

t2

t1

t1 t2 151186

S A1 B1 15

A2

18 16

U S
Output LED

t1 t2

A1/A2 A1/B1 t1 t2 151186

s A1 B1 15

A2

18 16

(1) If B1 is pulsed, a one full time cycle consisting of t1 and t2 is completed.

LED Operation Chart Ñ Green LED

LED

Output at Shelf State, No Timing - LED OFF

LED

Output at Shelf State, Time is Running - LED Flashing

LED

Output NO Contact is Closed, No Timing - LED On

LED

Output NO Contact is Closed, Time is Running - LED Long Flashing

100

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

Function Diagram / Connection Diagram(1)
(Q) Off-Delay without Supply Voltage (True Off-Delay) · When input power is turned on, the output contact changes state. When the power is removed, the time delay begins. The output contact returns to shelf state at the end of the
time delay.

U

tp

Output

t

LED

A1/A2 151186

A1

15

A2

18 16

U

tp

Output 1

t

Output 2

t

LED

A1/A2

A1

18 15 16

25

28 26

A2

15 25 18 16 28 26

(Y) Star-Delta Timing Relay
· When power is applied, the output contact 17/18(Y) changes state. After the time setting, the output contact 17/18(Y) returns to shelf state. After the fixed time (50... 60 ms), the output contact 17/28 changes state. Both output contacts return to shelf state whenever the power is removed.

(1) Min. pulse (tp) required: 800 ms

U

A1/A2

t

17/18

17/28 tu = 50...65 ms
LED

A1 17 A2 18 28

Specifications - 700-FS Relays(1)

Attribute Setting Accuracy Repeatability
Tolerance

Value
±5% of full scale
±0.2% of the setting values Voltage: ±0.001%/%U Temperature: ±0.025%/°C

Supply

Attribute Supply Voltages Voltage Tolerance Power Consumption Time Energized Reset Time Voltage Interruption Input Impedance Cable Length (Supply Voltage Control)
Pulse Control (B1)

Value 24...48V DC and 24...240V AC, 50/60 Hz (multi voltage) ­20...+20% (DC), ­15...+10% (AC) 0.5 W at 24V DC, 5 VA at 240V AC 100% 50 ms 20 ms without reset (supply voltage) Relay ON: 3K-13K ohms, Relay OFF: 0.7K-4K ohms
Max. 250 m (800 ft)

Attribute Pulse Duration Input Voltage

Value 50 ms (AC), 30 ms (DC) Supply voltage range

Input Current Max. Leakage Current Cable Length

1 mA
400 micro Amps
Max. 250 m (800 ft) without parallel load between B1 and A2, Max.50m(160ft)withload(<3 k) betweenB1andA2

Outputs

Contact Type Dielectric Coil to Contact
Switching Capacity
Short-Circuit Resistance

Relay as changeover switch 5000 V
Voltage: 440V AC Current Ith (AC-1): 8 A (5 A for 700- FSQ)
Power: 2000 VA According to IEC 947-5-1: 3 A/440V AC (inductive load, AC 14) 3 A/250V AC (inductive load, AC 15) 1 A/24V DC (inductive load, DC 13)
According to UL 508: 1.5 A/250V AC (B300) 3 A/120V AC (B300)
10 A gL

(1) Time Characteristics (according to VDE 0435, Part 2021)

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

101

Relay and Timer Specifications

Life State Indicator

Mechanical: 30 million operations Electrical operations:
4 mil at 1 A/250V AC, cos  = 1 0.2 mil at 6 A/250V AC, cos  = 1 1.5 mil at 1 A/250V AC, cos  = 0.3 0.3 mil at 3 A/250V AC, cos  = 0.3 0.5 mil at 6 A/24V DC, resistive
2 mil at 4 A/24V DC, resistive 2 mil at 0.2 A/230V DC, resistive 1 mil at 0.4 A/24V DC, L/R = 20 ms 1 mil at 0.2 A/110V DC, L/R = 20 ms 1 mil at 0.1 A/230V DC, L/R = 20 ms
1 LED, combination signal

General Data- 700-FS Relays
Insulation Characteristics
EMC/Interference Immunity
EMC/Emission Safe Isolation Climatic Withstand Vibration Resistance Shock Resistance Protection Class Weight Approval Ambient Temperature
Terminals
Mounting Disposal Certifications Standards

2 kVAC/50 Hz test voltage according to VDE 0435 and 6 kV 1.2/50 s surge voltage according to IEC 947-1 between all inputs and outputs
Performance of following requirements: Surge capacity of the supply voltage according to IEC 1000-4-5: 4 kV 1.2/50 s
Burst according to IEC 1000-4-4: 6 kV 6/50 ns ESD discharge according to IEC 1000- 4-2: Contact 8 kV, air 8 kV
Electromagnetic HF field according to IEC 801-3 and conducted electromagnetic HF signal according to IEC 801-6: Level 3
Electromagnetic fields according to EN 55 022: class B
According to VDE 106, part 101
56 Cycles (24 hr) at 25...40 °C and 95% relative humidity according to IEC 68-2-30 and IEC 68-2-3
4 g in three axes at 10...500 Hz, test FC according to IEC 68-2-6
50 g according to IEC 68-2-27
Enclosure: IP40 IP 30 (Single-function) Terminal: IP 20 according to IEC 947-1
100 g
UL, C-UL
Open: ­25...+60 °C Enclosed: ­25...+45 °C Storage: ­40...+85 °C
Screw terminal M3.5 for Number 2 Posidriv, Philips, and slotted screws. Suitable for power screwdriver. Rated tightening torque 8.8 lb.-in. (0.8 N·m, max. 1.2 N·m).
Dual-chamber system for terminal cross-sections of 1 x 0.5 mm2...2 x 2.5 mm2 (solid) or stranded 2 x 2.5 mm2 (flexible with sleeve), #20...14 AWG. Finger protection according to VDE 0106.
Front mounting; For snap-on mounting on 35 mm DIN Rail or screw fixing by adapter and 2 screws (M4 type)
Synthetic material without dioxin according to EC/EFTA notification Number 93/0141/D electrical contacts with cadmium
cULus Listed (File No. E14840, Guide NKCR/NKCR7), CE Marked
EN/IEC 60947-1, EN/IEC 60947-5-1, UL 508, CSA 22.2 No. 14

Temp. Code T4A 2A 32VDC MAX.
Mounting: Product shall be installed in an enclosure constructed in accordance with the requirements of EN50021.

102

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

700-HNC Miniature Timing Relay

· Miniature timer, perfect for converting 700-HC "Ice Cube" relays into timing relays · 4 operating modes · 4PDT contact output · Timing range from 0.1 s...10 hr · Socket mounted

Model Cat. No. 700-HNC

Timing Mode

Contact Output

On-Delay

One Shot Repeat cycle, OFF-start

4PDT

Repeat cycle, ON-start

Input Voltages 12V DC 24V DC 48V DC 100...110V DC 125V DC 24V AC 100...120V AC 200...230V AC

Timing Range 0.1 s...10 min .1 min...10 hr 0.1 s...10 min 0.1 min....10 hr 0.1 s...10 min 0.1 min....10 hr 0.1 s...10 min 0.1 min....10 hr 0.1 s...10 min 0.1 min....10 hr 0.1 s...10 min 0.1 min....10 hr 0.1 s...10 min 0.1 min....10 hr 0.1 s...10 min 0.1 min....10 hr

Socket Type
700-HN103 700-HN128

Cat. No. 700-HNC44AZ12 700-HNC44BZ12 700-HNC44AZ24 700-HNC44BZ24 700-HNC44AZ48 700-HNC44BZ48 700-HNC44AZ11 700-HNC44BZ11 700-HNC44AZ25 700-HNC44BZ25 700-HNC44AA24 700-HNC44BA24 700-HNC44AA12 700-HNC44BA12 700-HNC44AA23 700-HNC44BA23

Accessories - 700-HNC Relays

Photo

Description

Pkg. Quantity Cat. No.

Screw Terminal Socket -- Panel or DIN Rail Mounting. Guarded Terminal Construction 14-Blade miniature socket for use with 700-HNC timers.

10

700-HN103

Screw Terminal Base Sockets -- Panel or DIN Rail Mounting.

Open Style Construction

10

14-blade miniature socket for use with 700-HNC timers.

Screw Terminal Socket ­ Panel or DIN Rail Mounting. Guarded Terminal Construction 14-blade miniature socket for use with 700-HNC timers. This socket has coil 10 and contact separation.

Retainer Clip for Cat. Nos. 700-HN103, -HN104 and -HN128 Sockets with 700-HNC Timers. Secures Timer in Socket.

10

700-HN128 700-HN104 700-HN263

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

103

Relay and Timer Specifications
Specifications - 700-HNC Relays
Attribute Pilot Duty Rating Pin type Operating voltage range Reset voltage

Power consumption

Control outputs

Characteristics

Make

120V AC

240V AC

Break

120V AC

240V AC

Hp at 120V AC

Hp at 240V AC

Accuracy of operating time

Setting error

Reset time

Influence of voltage

Influence of temperature

Insulation resistance

Dielectric strength

Vibration resistance Shock resistance Ambient temperature
104

700-HNC

NEMA B300

Plug-in 85%...110% of rated supply voltage (12V DC: 90%...110% of rated supply voltage) (1)

10% min. of rated supply voltage

24V AC:

Relay ON: Relay OFF:

1.5 VA(1.1 W) (at 24V AC, 60 Hz) 0.2 VA(0.1 W) (at 24V AC, 60 Hz)

100...120V AC:

Relay ON: Relay OFF:

1.5 VA(1.3 W) (at 120V AC, 60 Hz) 0.8 VA(0.5 W) (at 120V AC, 60 Hz)

200...230V AC:

Relay ON: Relay OFF:

1.8 VA(1.5 W) (at 230V AC, 60 Hz) 1.2 VA(0.9 W) (at 230V AC, 60 Hz)

12V DC:

Relay ON: Relay OFF:

0.9 W (at 12V DC) 0.07 W (at 12V DC)

24V DC:

Relay ON: Relay OFF:

0.9 W (at 24V DC) 0.07 W (at 24V DC)

48V DC:

Relay ON: Relay OFF:

1.0 W (at 48V DC) 0.2 W (at 48V DC)

100...110V DC:

Relay ON: Relay OFF:

1.3 W (at 110V DC) 0.3 W (at 110V DC)

125V DC:

Relay ON: Relay OFF:

1.3 W (at 125V DC) 0.3 W (at 125V DC)

4PDT: 5 A at 250V AC, resistive load (cos  = 1)

30 A 15 A 3 A 1.5 A 1/6 Hp 1/6 Hp ±1% FS max. (1 s range: ±1%±10 ms max.) ±10%±50 ms FS max. Min. power-opening time: 0.1 s max. (including halfway reset) ±2% FS max. ±2% FS max. 100 m min. (at 500V DC) 2000V AC, 50/60 Hz for 1 min (between current-carrying terminals and exposed non-current-carrying metal parts)
(2)
2000V AC, 50/60 Hz for 1 min (between operating power circuit and control output) 2000V AC, 50/60 Hz for 1 min (between different pole contacts; 2-pole model) 1500V AC, 50/60 Hz for 1 min (between different pole contacts; 4-pole model) 1000V AC, 50/60 Hz for 1 min (between non-continuous contacts) Malfunction: 10...55 Hz, 0.5 mm single amplitude Malfunction: 100 m/s2 (approx. 10G) Operating: -10 °C...50 °C (with no icing) Storage: -25 °C...65 °C (with no icing)
Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

Attribute

700-HNC

Ambient humidity

Operating: 35%...85%

Life expectancy

Mechanical: 10 000 000 operations min. (under no load at 1800 operations/hr) Electrical: 4PDT: 200 000 operations min. (3 A at 250V AC, resistive load at 1800 operations/hr)

Noise immunity

±1.5 kV, square-wave noise by noise simulator (pulse width: 100 ns / 1 s, 1- ns rise)

Static immunity Enclosure rating

Destruction:8 kV Malfunction:4 kV IP40

Weight

Approx. 50 g

Emission Enclosure:EN55011 Group 1 class A

Emission AC Mains:EN55011 Group 1 class A

Immunity ESD:EN61000-4-2:4 kV contact discharge (level 2) 8 kV air discharge (level 3)

EMC

Immunity RF-interference:ENV50140:10 V/m (amplitude modulated, 80 MHz to 1 GHz) (level 3) 10 V/m (pulse

modulated, 900 MHz)

Immunity Conducted Disturbance:ENV50141:10 V (0.15...80 MHz) (level 3)

Immunity Burst:EN61000-4-4:2 kV power-line (level 3) 2 kV I/O signal-line (level 4)

Standards

UL 508, CSA 22.2 No. 14, EN/IEC 61812-1

Certifications

cURus Recognized (File No. E14843, Guide NRNT2/NRNT8), CSA Certified (File 224268), CE Marked, C- Tick Marked

(1) Single-phase, full-wave-rectified power supplies can be used. (2) When using the 700-HNC continuously in any place where the ambient temperature is in a range of 45 °C...50 °C, supply 90%...110% of the rated supply voltages supply 95%...110% with 12V DC type).

General Timer Functions

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

105

Relay and Timer Specifications
Timing Charts - 700-HNC Relays
IMPORTANT t: Set time, Rt:Reset time

Operating Mode
ON-Delay
Power
t
Output

One shot Power Output

Repeat Cycle OFF-Start

Power Output

t

t

t

Repeat Cycle ON-Start

Power

t

t

t

Output

General Timer Functions

Output Indicator (Orange) (Lit: Output ON)
Main Dial Set the desired time according to time range selectable by DIP switch.

Timing Charts / Wiring Diagram

t Power (13-14) Time limit contact NC (9-1, 10-2, 11-3, 12-4) Time limit contact NO (9-5, 10-6, 11-7, 12-8)
Run / Power Indicator (PW)
Output Indicator (UP)

Rt

t

Power (13-14) Time limit contact NC (9-1, 10-2, 11-3, 12-4) Time limit contact NO (9-5, 10-6, 11-7, 12-8)
Run / Power Indicator (PW)
Output Indicator (UP)

Power (13-14) Time limit contact NC (9-1, 10-2, 11-3, 12-4) Time limit contact NO (9-5, 10-6, 11-7, 12-8)
Run / Power Indicator (PW)
Output Indicator (UP)

t

t

t

t

t

t

t

t

Power (13-14)
Time limit contact NC (9-1, 10-2, 11-3, 12-4)
Time limit contact NO (9-5, 10-6, 11-7, 12-8)

Run / Power Indicator (PW)

Output Indicator (UP)

Timer Circuit
UP PW

Pulse Operation

A pulse output for a certain period can be obtained with a random external input signal. Use the 700-HNC timing relay in interval mode as shown in the following timing charts.

Run/Power Indicator (Green) (Lit: Power ON)

1

2

3

4

5

6

7

8

9 10 11 12

13 Timer

14

(--) Circuit

(+)

(~)

(~)

UP FW

External Input
~

( )

Power (9-14)
External short circuit (5-13) External input (9-13)
Time limit contact NO (10-6, 11-7, 12-8) Time limit contact NC (10-2, 11-3, 12-4) Run/Power indicator (PW) Output indicator (UP)

50 ms min.

Note: t: Set time Rt: Reset time

106

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

DIP Switch Settings - 700-HNC Relays
Time Ranges

Cat. No.
700-HNC44AZ12 700-HNC44AZ24 700-HNC44AZ48 700-HNC44AZ11 700-HNC44AZ25 700-HNC44AA24 700-HNC44AA12 700-HNC44AA23

Time Range 1 s 10 s 1 min
10 min

700-HNC44BZ12 700-HNC44BZ24 700-HNC44BZ48 700-HNC44BZ11 700-HNC44BZ25 700-HNC44BA24 700-HNC44BA12 700-HNC44BA23

1 min 10 min 1 hr 1 hr

Note: The top two DIP switch pins are used to select the time ranges.

Time Setting Range 0.1 s...1 s 1 s...10 s 0.1 s...1 min 1...10 min 0.1...1 min 1...10 min 0.1...1 hr 1...10 hr

Relay and Timer Specifications

Setting

Factory-Set Yes No No No Yes No No No

Operating Mode ON-delay One Shot
Repeat Cycle OFF-start Repeat Cycle ON-start
Note: The top two DIP switch pins are used to select the time ranges.

Setting

Factory-set Yes No No No

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

107

Relay and Timer Specifications

Dimensions - 700-HNC Relays
Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.

4.0 (0.15)

Fourteen 3 x 1.2 mm Elliptic Holes

52.6 (2.07) 63.0 (2.48)

6.4 (0.25)
Cat. No. 700-HNC...

28 (1.10) 6.3 (.024)
21.5 max (084)

Panel Mounting
24.5 (31/32)

28.9 (1-9/64)

67.0 (2-5/8)

30.0 (1-11/64)

#4-40 M3

Cat. No. 700-HN103 Single wire: 0.2...2.5 mm2 (#24 AWG...14 AWG) Double wire: 2 x 0.2 mm2...2 x 1.5 mm2 (2 x 24 AWG...2 x 16 AWG)
Wire type: solid or stranded, copper only Strip length: 8 mm (5/16 in.), Torque: 0.5 N·m (4.4 lb·in)
(1) Total height of 700-HN128 + 700-HNC is 82.5 mm.

30.0 (1-3/16)
6.1 (15/64)
8765
4321

24.9 (57/64)
21.1 (53/64)

4.2 (5/32) 62.0
(2-15/64)

14

13

12 11 10 9

65.0 (2-9/16)

26.0 (1-1/64)
Cat. No. 700-HN128 (1) Wire Size: 2 x 1.5 mm2 (#2-16 AWG...#1-20 AWG)
(Either Solid or Stranded) Strip Length: 9 mm (3/8 in.) - Torque: 0.8 N·m (7 lb·in)

27.0 (1.06)

60.9 (2.40)

21.5 (0.85)

76.0 (2.99)
34.9 (1.37)

3.2 (0.13)
2.5 (0.10)

35.6 (1.40)

32.0 (1.26)
35.5 (1.40)

18.9 (0.74)

Cat. No. 700-HN104 Single Wire: 0.2...2.5 mm2 ( #24 AWG...14 AWG) Double Wire: 2 x 0.2 mm2...2 x2.5 mm2 (2 x 24 AWG...2 x 14 AWG)
Wire Type: solid or stranded, copper only Strip Length: 7 mm (9/32 in.), Torque: 0.5 N·m (4.4 lb·in)

108

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

700-HNK Ultra-Slim Timing Relay

· The ultra-slim timing relay is the smallest relay available · It is perfect for converting 700-HK relays into a timing relay · SPDT and DPST-NO contact output · Socket-mounted · Timing range From 0.1 s...10 hr

Photo

Timing Mode

Socket Type

Contact Output

700-HN121
On-Delay One Shot Repeat Cycle, OFF-start Repeat Cycle, ON-start
700-HN122

SPDT (1) DPST-NO(2)

(1) 5-blade terminal type only. (2) 8-blade terminal type only.
Accessories - 700-HNK Relays
Description

Timing Range 0.1 s...10 min 0.1 min...10 hr 0.1 s...10 min 0.1 min...10 hr

Input Voltage 12V DC 24V DC 24V AC 12V DC 24V DC 24V AC 12V DC 24V DC 24V AC 12V DC 24V DC 24V AC

Cat. No. 700-HNK41AZ12 700-HNK41AZ24 700-HNK41AA24 700-HNK41BZ12 700-HNK41BZ24 700-HNK41BA24 700-HNK42AZ12 700-HNK42AZ24 700-HNK42AA24 700-HNK42BZ12 700-HNK42BZ24 700-HNK42BA24

Pkg. Quantity Cat. No.

Screw Terminal Socket -- Panel or DIN Rail Mounting 5-blade miniatue socket. For use with 1-pole type 700-HNK41 timers. Socket includes a retainer clip.

10

700-HN121

Screw Terminal Socket -- Panel or DIN Rail Mounting 8-blade miniature socket for use with 2-pole, 700-HNK42 timers. This socket includes a retainer clip.

10

700-HN122

Sockets and Retainer Clip Reference

Timer Type 700-HNK

Socket Cat. No. 700-HN121 700-HN122

Retainer Clip Cat. No. Provided Provided

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

109

Relay and Timer Specifications

Specifications - 700-HNK Relays
Attribute
Pilot Duty Rating Rated Supply Voltage Pin Type Operating Mode Operating Voltage Range
Power Consumption

Control Outputs

Characteristics

Make

120V AC

240V AC

Break

120V AC

240V AC

Hp at 240V AC

Accuracy of Operating Time

Setting Error

Reset Time

Influence of Voltage Influence of Temperature Insulation Resistance

Dielectric Strength

Vibration Resistance Shock Resistance

Ambient Temperature

Ambient Humidity

Life Expectancy

Impulse Withstand Voltage Noise Immunity

Static Immunity

Enclosure Rating Weight

700-HNK
NEMA B300
24V AC; 12, 24V DC
Plug-in
ON-delay, One Shot, Repeat Cycle OFF start, or Repeat Cycle ON start selectable with DIP switch. 85%...110% of rated supply voltage (12 VDC: 90%...110% of rated supply voltage) (1)
24V AC:Relay ON:approx. 0.8 VA (at 24 VAC, 60 Hz) Relay OFF:0.5 VA (at 24V AC, 60 Hz) 12V DC:Relay ON:approx. 0.4 W (at 12V DC) Relay OFF:0.1 W (at 12V DC) 24V DC:Relay ON:approx. 0.5 W (at 24V DC) Relay OFF:0.2 W (at 24V DC)
5 A at 250V AC, resistive load (cos  = 1) The minimum applicable load is 10 mA at 5 VDC (P reference value).

30 A

15 A

3 A

1.5 A

1/6 Hp

±1% FS max. (1 s range: +1% ±10 ms max.)

±15% +50 ms FS max.

Min. power-opening time:

12, 24V DC: 0.1 s max. (including halfway reset) 24V AC: 0.5 s max. (including halfway reset)

±2% FS max.

±2% FS max.

100 m min.(at500VDC)

2000V AC, 50/60 Hz for 1 min (between operating circuit and control output, or contacts of different poles) 1000V AC, 50/60 Hz for 1 min (between non-continuous contacts)

Malfunction: 10...55 Hz, 0.5 mm single amplitude Malfunction: 100 m/s2 (approx. 10G)

Operating: -10 °C...50 °C (with no icing) Storage: -25 °C...65 °C (with no icing)

Operating: 35...85%

Mechanical: 10 000 000 operations min. (under no load at 1800 operations/hr) Electrical: 100 000 operations min. (3 A at 250V AC, resistive load at 1800 operations/hr)

Between power terminals: 1 kV

±1.5 kV, square-wave noise by noise simulator (pulse width: 100 ns/1 s, 1-ns rise)

Destruction: 8 kV Malfunction: 4 kV

IP20

Approx. 18 g

110

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

Attribute

700-HNK

Emission Enclosure: EN55011 Group 1 class A Emission AC Mains: EN55011 Group 1 class A

Immunity ESD: EN61000-4-2:4 kV contact discharge (level 2) 8 kV air discharge (level 3)

EMC

Immunity RF-interference: ENV50140: 10 V/m (amplitude modulated, 80 MHz...1GHz) (level 3) 10 V/m (pulse

modulated, 900 MHz)

Immunity Conducted Disturbance: ENV50141:10 V (0.15...80 MHz) (level 3) Immunity Burst: EN61000-4-4:2 kV power-line (level 3) 2 kV I/O signal-line (level 4)

Standards

UL508, CSA C22.2 No. 14, EN/IEC 60947-5-1, EN/IEC 61812-1

Certifications

cURus Recognized Component (File No. E14843, Guide NRNTZ/NRNT8), CE Marked, C-Tick Marked

(1) When using 700-HNK timer in any place where the ambient temperature is more than 50 °C, supply 90...110% of the rated voltages (12V DC: 95...11% of the rated voltage).

IMPORTANT t: Set time, Rt:Reset time
General Timer Functions
Run/Power Indicator (Green) (Lit: Power ON)
Output Indicator (Orange) (Lit: Output ON)

Main Dial Set the desired time according to time range selectable by DIP switch.

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

111

Relay and Timer Specifications

Operating Mode
ON-Delay Power
t
Output

Power (1-5)
Time limit contact NC (4-2)
Time limit contact NO (4-3) Run/ Power Indicator (PW)
Output Indicator (OUT)

700-HNK41...

Timing Charts / Wiring Diagram

700-HNK42...

t

Rt

t

Power (1-8)
Time limit contact NO 4-3, 5-6
Run/Power indicator (PW)
Output indicator (OUT)

t

Rt

t

One shot Power Output

Repeat Cycle OFF-Start

Power Output

t

t

t

Repeat Cycle ON-Start

Power

t

t

t

Output

Power (1-5)
Time limit contact NC (4-2)
Time limit contact NO (4-3) Run/ Power Indicator (PW)
Output Indicator (OUT)
Power (1-5)
Time limit contact NC (4-2)
Time limit contact NO (4-3) Run/ Power Indicator (PW)
Output Indicator (OUT)

t

t

Power (1-5)

t

t

Time limit contact NC (4-2)

Time limit contact NO (4-3) Run/ Power
Indicator (PW)

Output Indicator (OUT)

t

t

t

t

t Power (1-8)
Time limit contact NO (4-3, 5-6)
Run/Power indicator (PW)
Output indicator (OUT)

Rt

t

Power (1-8)
Time limit contact NO (4-3, 5-6)
Run/Power indicator (PW)
Output indicator (OUT)

t

t

t

t

Power (1-8)
Time limit contact NO (4-3, 5-6)
Run/Power indicator (PW)
Output indicator (OUT)

t

t

t

t

112

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Wiring- 700-HNK Relays

Relay and Timer Specifications

3

4

5

4

3

6

Timer

~ ~ 1 Circuit
( )

8 ( )

( ) OUT PW ( )

Cat. No. 700-HNK42...

2

Timer

1 Circuit 5

( )

( )

( ~ ) OUT PW ( ~ )

Cat. No. 700-HNK41...

A pulse output for a certain period can be obtained with a random external input signal. Use the 700-HNK in interval mode as shown in the following timing chart.

4

5

3

6

1 Timer

8

~( ) Circuit
( )
OUT PW

( )
( ~)

~ External Input
( )

Mode Pulse Operation Operating mode; One shot and all other modes

Power (3-8)
External Short Circuit (1-4)
External Input (1-3)
Time Limit Contact NO (6-5) Run/Power Indicator (PW) Output Indicator (OUT)

Rt

Rt

t

t

t

50 ms min.

Note:t:Set time Rt: Reset time
Terminals Power supply between 3 and 8 Short-circuit between 4 and 1 Input signal between 3 and 1 Power supply between 1 and 8

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

113

Relay and Timer Specifications

Time Ranges- 700-HNK Relays

Cat. No.
700-HNK41AZ12 700-HNK41AZ24 700-HNK41AA24 700-HNK42AZ12 700-HNK42AZ24 700-HNK42AA24

Time Range 1 s 10 s 1 min
10 min

700-HNK41BZ12 700-HNK41BZ24 700-HNK41BA24 700-HNK42BZ12 700-HNK42BZ24 700-HNK42BA24

1 min 10 min 1 hr 10 hr

Note: The left two DIP switch pins are used to select the time ranges.

Time Setting Range 0.1...1 s 1...10 s
0.1 s...1 min 1...10 min 0.1...1 min 1...10 min 0.1...1 hr 1...10 hr

Setting

Factory-Set Yes No No No Yes No No No

Operating Modes - 700-HNK Relays
Operating Mode On-delay One Shot
Repeat Cycle Off-start Repeat Cycle On-start
Note: The right two DIP switch pins are used to select the operating modes.

Setting

114

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Factory-set Yes No No No

Relay and Timer Specifications

Dimensions - 700-HNK Relays
Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.

12.8 (0.50)
28.8 (1.30) 31.2 (1.22)

47.4 (1.86) 46.0 (1.81)

6 (0.23)

12.8 (0.50) 31.2 (1.22) 28.8 (1.13)

47.0 (1.86) 46.0
(1.81)

6.0 (0.23)

700-HNK41 SPDT Contact

7.11

11

(9/32)

Five M3.5

4

x 0.315 Screws

14 3
84.1 (3-5/16)

12 2
3.0 Ø (1) (1/8) Use M3 Screws

5 (+) (A1)
1 (-) (A2)

2.03 (5/64)
4.06 (5/32)
39.5 (1-17/32) 35.5 (1-13/32)

4.06 (5/32)
15.6 (5/8)

29.9 (1-3/16)

54.1 (2-1/8)

Cat No. 700-HN121 Wire Size: 2 x 2.5 mm2 Single Wire ­ Up to #12 AWG Double Wire ­ 2 x 2.5 mm2 (#2­14 AWG... #2­20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in.) ­ Torque: 0.8 N·m (7 lb·in) Total height: 700-HN121 + 700-HNK41 is 78.0 mm.
(1) Holes required for mounting [3 mm (1/8 in.) diameter].

700-HNK42 DPST-NO Contact

21 6
22 7 24 5
84.1 (3-5/16)
8 (+) (A1)

7.11

(9/32)

11

3

Eight M3.5 x 0.315 Screws
12 14 2 4 3.0 Ø (1) (1/8) Use M3 Screws

2.03 (5/64)
4.06 (5/32)
39.5 (1-17/32) 35.5 (1-13/32)

4.06 (5/32)

1 (-) (A2)
15.6 (5/8)

29.9 (1-3/16)
54.1 (2-1/8)

Cat No. 700-HN122 Wire Size: 2 x 2.5 mm2 Single Wire ­ Up to #12 AWG Double Wire ­ 2 x 2.5 mm2 (#2­14 AWG... #2­20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in.) ­ Torque: 0.8 N·m (7 lb·in) Total height: 700-HN122 + 700-HNK42 is 78.0 mm.

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

115

Relay and Timer Specifications

700-HR Dial Timing Relays
· Socket- or panel-mounted · 5 A contact ratings or transistor outputs · Single- or Multi-Function · Timing range from 0.05 s...300 hr · Multi-voltage inputs

Multi-Function Timing Relays with Trigger and Reset Switch Options

· Socket or Panel Mounted · Timing Range From 0.05 s...300 hr · 11-pin base for socket cat. nos. 700-HN101, -HN126, -HN129 · Trigger: Power on or optional trigger signal · Reset: Power off or optional reset signal

Timing Mode

Supply Voltage

On-Delay (A) OFF-Delay (D) One Shot (E) Repeat cycle OFF-Start (B) Repeat Cycle ON-Start (B2) Signal ON/OFF-delay (C) Delayed One Shot (J) Signal ON/OFF - Delay (G)

24...48V AC 12...48V DC
100...240V AC 100...125V DC

Trigger Options
1. Power On 2. Start Signal - contact closure (zero volts) - NPN transistor 3. Gate Signal (pause)
1. Power On 2. Start Signal - contact closure (voltage) - NPN transistor - PNP transistor
1. Power On 2. Start Signal - contact closure (zero volts) 3. Gate Signal (pause)
1. Power On 2. Start Signal - contact closure (voltage)

(1) Voltage input connection to high signal instead of OV signal.

Reset Options 1. Power Off 2. Reset Signal - contact closure (zero volts) - NPN transistor
Power Off
1. Power Off 2. Reset Signal - contact closure (zero volts)
Power Off

Outputs DPDT Transistor
DPDT
DPDT DPDT

Cat. No. 700-HR52TU24 (1) 700-HRT6TTU24
700-HRV52TU24
700-HR52TA17
(1)
700-HRV52TA17

Multi-Function Timing Relays with Power On Trigger

· Socket or Panel Mounted · Timing Range From 0.05 s...300 hr · 8-pin base for socket cat. nos. 700-HN100, -HN125, -HN108 · Trigger: Power on · Reset: Power off

Timing Mode

Supply Voltage

ON-Delay (A) One Shot (E) Repeat Cycle OFF-Start (B) Repeat Cycle ON-Start (B2) Delayed One Shot (J)

24...48V AC 12...48V DC
24...48V AC/DC
100...240V AC 100...125V DC

Trigger Options Power On Power On Power On

Reset Options Power Off

Outputs DPDT Transistor

Power Off

SPDT Timed + Instantaneous Contact

Power Off

SPDT Timed + Instantaneous Contact DPDT

(1) Voltage input connection to high signal instead of OV signal.

Cat. No. 700-HRS42TU24
700-HRT4TTU24 (1) 700-HRP42TU24 700-HRP42TA17 700-HRS42TA17

116

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

ON-Delay Timing Relays

· Socket or Panel Mounted · Timing Range From 0.05 s...300 h · 8-pin base for socket cat. nos. 700-HN100, -HN125, -HN108 · Trigger: Power on · Reset: Power off

Timing Mode Supply Voltage 24...48V AC/DC
ON-Delay (A) 24...48V AC, 12...48V DC 100...240V AC

Trigger Options Power On
Power On

Reset Options Power Off
Power Off

Outputs SPDT Timed + Instantaneous Contact DPDT DPDT SPDT Timed + Instantaneous Contact

Timing Mode Description

Cat. No. 700-HRC12TU24 700-HRM12TU24 700-HRM12TA17 700-HRC12TA17

700-HRF Repeat Cycle Timing Relays
· Socket or Panel Mounted · Independently adjustable on- and off-time · 8-Pin base for socket cat. nos. 700-HN100, -HN125, and -HN108 · DPDT contact outputs · Trigger: Power on · Reset: Power off · Hazardous location version available

Catalog Number Explanation

700 ­ HRF

7

2

D

U26

a

b

c

d

e

f

a Bulletin Number

b Type of Relay

700

HRF­Repeat cycle with adjustable ON/OFF times

c Function
7­Repeat cycle with OFF start 8­Repeat cycle with ON start

d Contact Output

e Timing Range

2- DPDT

D­0.05 s...300 hr

f Supply Voltage
U26 - 12...48V DC, 24...48V AC U27 - 100...125V DC, 100...240V AC

700-HRY Star-Delta Timing Relays

· 8-Pin base for socket cat. nos. 700-HN100, -HN125, and -HN108 · SPDT timed + instantaneous contact outputs · Trigger: Power on · Reset: Power off

700 ­ HRYY

6

a

b

c

Catalog Number Explanation

F

A12

d

e

a Bulletin Number

b Type of Relay

700

HRYY­YStar-Delta timer

c Function
6­SPDT timed + SPDT instant

d Timing Range
F­Star: 0.5...120 s Delta: 0.05, 0.1, 1.25, 0.5, 0.75, 1.0 s

e Supply Voltage
A12­100...120V AC, 50/60 Hz A22­200...240V AC, 50/60 Hz

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

117

Relay and Timer Specifications

700-HRQ True Off-Delay Timing Relays

· 11-Pin base for use with reset option -- socket cat. nos. 700-HN101, -HN126, and -HN129 · 8-Pin base for use without reset option -- socket cat. nos. 700-HN100, -HN125, and -HN108 · DPDT contact outputs · Trigger: Power off
· Reset: optional reset signal

700 ­ HRQ

N

2

G A12

a

b

c

d

e

f

Catalog Number Explanation

a
Bulletin Number

b - Type of Relay

c Function

d
Contact Output

e Timing Range

700

HRQ­True OffDelay Timer

N­No reset option, 8-pin terminals R­Reset option, 11-pin terminals

2­DPDT

G­0.05...12 s H­0.05...12 min

Accessories - 700-HR Relays

Photo

Description

f Supply Voltage
A12­100...120V AC, 50/60 Hz A22­200...240V AC, 50/60 Hz U25­24V AC, 50/60 Hz; 24V DC
Z48­48V DC Z11­100...125V DC
Pkg. Qty. Cat. No.

Screw Terminal Tube Base Socket -- Panel or DIN Rail Mounting; Guarded Terminal Construction. 8-Pin for use with 700-HR and -HX timing relays.

10

700-HN100

Screw Terminal Tube Base Socket -- Panel or DIN Rail Mounting; Open Style Construction. 8-Pin for use with 700-HR and -HX timing relays. No retainer clip required.

10

700-HN125

Screw Terminal Tube Base Sockets -- Panel or DIN Rail Mounting; Guarded Terminal Construction. 11-pin for use with 3PDT 700-HA relays.

10

700-HN101

Screw Terminal Tube Base Sockets -- Panel or DIN Rail Mounting; Open Style Terminal Construction. 11-pin for use with 3PDT 700-HA relays. No retainer clip required.

10

700-HN126

DIN (#3) symmetrical hat rail 35 x 7.5 x 1 m

10

199-DR1

118

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

Photo

Description

Pkg. Qty. Cat. No.

Specialty Socket 8-pin backwired socket with solder terminals for use with 700-HR timing relays. Order 10 or 10 multiples of 10.

700-HN108

Specialty Socket 11-pin back-wired socket with solder terminals for use with 700-HR timing relays.

10

700-HN129

Frame Adapter For flush or door mounting of all 700-HR and -HX timers.

1

700-HN130

Retainer Clip for Cat. Nos. 700-HN100 and -HN101 Sockets with all 700-HR Timing

Relays

Secures timer in socket.

10

Note: Not required for installation

700-HN131

Protective Cover

Helps prevent tampering of timing and mode settings. Provides a degree of protection against water and dirt from entering the front of the relay. For use with all 700-HRs and -HX timing

1

relays.

Pre-Printed Identification Tags -- contains 10 sheets of pre-printed and blank tags. Each sheet contains 13 sets of the markings CR...9CR, TR...9TR, M...9M, F, R, 1S, and 117 blank 10 tags. Tags are peel-off with sticky backing for easy placement on relays.
Blank Identification Tags -- contains 10 sheets of blank identification tags for customer specialized printing. Each sheet contains 546 blank tags. Tags are peel-off with sticky backing 10 for easy placement on relays.

700-HN132 700-N40 700-N41

Timer Type
700-HR52, -HRT6, -HRV, -HRQR
700-HRS, -HRT4, -HRP, -HRC, -HRM, -HRF, -HRY, -HRQN
(1) 11 pins. (2) 8 + pins. (3) Design of these sockets holds the timing relays securely and does not require retainer clips.

Socket Cat. No. 700-HN101
(1) 700-HN126 700-HN129 700-HN100
(2) 700-HN108 700-HN125

Retainer Clip Cat. No. 700-HN131 Not Required (3) Not Applicable 700-HN131(See note above) Not Applicable Not Required(3)

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

119

Relay and Timer Specifications

Specifications - 700-HR Relays

Electrical Ratings Pilot Duty Rating

Thermal Current (Ith)

Make

120V AC

240V AC

Break

120V AC

240V AC

Hp at 120V

Hp at 240V Resistive Load Inductive Load Accuracy of Operating Time Setting Error Influence of Voltage Influence of Temperature Permissible Leakage Current Power Consumption
240V AC, Output ON 240V AC, Output OFF 24V DC, Output ON 24V DC, Output OFF Design Specifications

Dielectric Strength

Mechanical Vibration Resistance
Shock Resistance
Environmental
Noise Immunity
Static Immunity
Ambient Temperature
Ambient Humidity Construction Life Rxpectancy (Min. Operations)

700-HR, 700-HRS, 700-HRV

700-HRP

700-HRC

700-HRM 700-HRF 700-HRY

700-HRQ

700-HRT (Transistor Outputs)

NEMA B300

--

5 A

100 mA @ 30V DC max.

30 A

--

15 A

--

3 A

--

1.5 A

--

1/6 Hp (0.12 kW)

1/4 Hp (0.18 kW)

1/6 Hp (0.12 kW)

1/4 Hp (0.18 1/6 Hp (0.12

kW)

kW)

--

1/3 Hp (0.25 kW)

--

5 A at 250V AC/30V DC

AC-15 @ 250V AC, 3 A/DC-13 @ 30V DC, 0.5 A

±0.2% FS max. (±0.2% ±10 ms max. in a range of 1.2 s)

±5 % FS ±50 ms (The value is ±5% FS +100 ms to -0 ms max. when the C or D mode signal of the 700-HRVs are OFF.)

±0.2% FS max. (±0.2% ±10 ms max. in a range of 1.2 s)

±1% FS max. (±1% ±10 ms max. in a range of 1.2 s)

-HR52, -HRS

-HRV

-HRP, -HRC

-HRM

-HRF

-HRY

-HRQ

-HRT

2.1 VA

2.5 VA

2.0 VA

2.1 VA

10 VA

12 VA

0.4 VA

--

1.3 VA

1.8 VA

2.0 VA

1.3 VA

10 VA

12 VA

0.4 VA

--

0.8 W

0.9 W

0.9 W

0.8 W

1.0 W

--

0.2 W

0.3 W

0.2 W

0.3 W

0.9 W

0.2 W

1.0 W

--

0.2 W

0.2 W

2000V AC (1000V AC for 700-HRT), 50/60 Hz for 1 min (contact to frame) 2000V AC (1000V AC for 700-HRT), 50/60 Hz for 1 min (between control output terminals and operating circuit)
2000V AC, 50/60 Hz for 1 min (pole-to-pole) 1000V AC, 50/60 Hz for 1 min (between contacts not located next to each other)
2000V AC, 50/60 Hz for 1 min (contact to coil)

Malfunction: 10...55 Hz with 0.5 mm double amplitude each in three directions for ten minutes each

Malfunction: 100 m/s2 (10 G)

98 m/s2 (10 G)

294 m/s2 (10 G)

98 m/s2 (10 G)

100 m/s2 (10 G)

±1.5 kV for ±600V DC

±400V for 12V DC

Malfunction: 8 kV
Operating: -10...+55 °C ( 14...131 °F) with no icing Storage: -25...+65 °C ( 13...149 °F) with no icing
Operating: 35...85 %

Mechanical:20 000 000. (under no load at 1800 operations/h) Electrical: 100 000 (5 A at 250V AC, resistive load at 1800 operations/h)

±1kV for 48V DC

±1.5 kV for ±600V DC

Mech: 107 Electrical: 104

120

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

EMC
Degree of Protection Weight Certifications Standards

Relay and Timer Specifications

700-HR, 700-HRS, 700-HRV

700-HRP 700-HRC 700-HRM 700-HRF 700-HRY 700-HRQ

700-HRT (Transistor Outputs)

(EMI) EN50081-2 Emission Enclosure: EN55011 Group 1 class A Emission AC Mains: EN55011 Group 1 class A
(EMS) EN50082-2 Immunity ESD:EN61000-4-2: 4 kV contact discharge (level 2); 8 kV air discharge (level 3) Immunity RF-interference from AM Radio Waves: ENV50140:10 V/m (80 MHz...1 GHz) (level 3) Immunity RF-interference from Pulse-modulated Radio Waves: ENV50204:10 V/m (900 ±5 MHz) (level 3)
Immunity Conducted Disturbance: ENV50141: 10V (0.15...80 MHz) (level 3) Immunity Burst: EN61000-4-4:2 kV power-line (level 3) Immunity Surge: EN61000-4-52 kV I/O signal-line (level 4) 1 kV line to line; 2 kV line to ground (level 3)

IP40 (panel surface)

Approx. 90 g

CSA Certified (File No. 70751), UL Recognized (File No. E14843 Guide No. NRNT2), CE Marked, C-Tick Marked

UL 508, CSA C22.2 No. 14, EN 61812-1, EN 61000-6-2, -6-4

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

121

Relay and Timer Specifications

Timer Functions - 700-HR Relays

700-HR Multifunction Timer

Power indicator (green) (Flashes when Timer operates; lit when Timer stops operating) Operating mode display window

Output indicator (orange) (Lit when energized)

Operating mode selector Select a mode from: A, B, B2, C, D, E, J, and G (700-HR52, -HRV, and HRT 6) A, E, B2, J, and B (800-HRS, -HRP, and -HRT4)

Scale range display windows

Time Range selector (select one from 1.2, 3, 12, and 30 at full scale.)
700-HRC -HRM On-Delay Timer

Time setting knob (set time)

Time unit display window Time unit selector (select one from sec, 10 s, min, 10 m, hrs, and 10 h)

Power indicator (green) (Flashes when Timer operates; lit when Timer stops operating)

Output indicator (orange) (Lit when energized)

700-HRF Twin Timer

Time Range selector (select one from 1.2, 3, 12, and 30 at full scale.)

Time setting knob (set time)

Scale range display windows Time unit display window Time unit selector (select one from sec, 10 s, min, 10 m, hrs, and 10 h)

OFF indicator (green) Lit when the output is OFF.
ON indicator (orange) Lit when the output is ON.
Scale range display windows

700-HRY Star-Delta Timer

Time range selector (select one from 1.2, 3, 12, and 30 at full scale.)

OFF-time unit display OFF-time unit selector (select one from sec, 10 s, min., 10 m, hrs, and 10 h)
ON-time setting knob (with orange pointer) For ON-time setting OFF-time setting knob (with green pointer) For OFF-time setting
ON-time unit display
ON-time unit selector (select one from sec, 10 s, min., 10 m, hrs, and 10 h)

Star operation indicator (green)
Delta operation indicator (orange)
Scale range display windows

Star operation time range selector (select one from 6, 12, 60 and 120 at full scale.)
700-HRQ True Off-Delay Timer

Star-delta transfer time unit display

Time unit display (sec. is fixed)
Time setting knob (for setting star operation time)
Star-delta transfer time selector (select one from 0.05 s, 0.1 s, 0.25 s, 0.5 s, 0.75 s and 1.0 s)

Scale range display windows

Output indicator (red)
Time range selector (select one from 0.6, 1.2, 6, and 12 at full scale.)

Time setting knob (for setting OFF-delay time) True OFF-Delay time unit display

122

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

Specifications for Start, Gate, Reset Signal (Cat. Nos. 700-HR52, -HRT6, -HRV, -HRQR) Start, Reset, and Gate signals are typically contact closures or signals from a solid-state sensor.

(R) Reset Signal The reset signal is not required for normal operation. Reset can be accomplished by removing power from the timing relay. To reset the timer without removing power, a signal must be applied which resets the timing cycle and returns the output contacts to their shelf state. The reset signal will override both the start signal and gate signal. The reset signal can be either momentary or maintained.
(G) Gate Signal The gate signal is not required for normal operation. The gate signal provides a pause or retentive timing function. When the gate signal is applied the timing cycle is momentarily interrupted. When the signal is removed, the timing cycle resumes timing at the point the cycle was interrupted and will continue timing until the time delay is completed or the gate signal is re-applied.
Contact Signal -- Cat. Nos. 700-HR52, -HRT6, -HRQR Contact closure provides signal to timer. A low energy signal is generated by the 700-HR timing relay. For optimum reliability, use contacts designed for low energy switching (5V, 1 mA) (Bul. 800F-X V, 800T-X V). No external voltage should be connected to the contact signal.
Contact Signal -- Cat. No. 700-HRV For use in applications where it is not possible to use contacts designed for low energy switching. Contact closure provides signal to timer. A signal is generated by the 700-HR timing relay, and is the same potential as the supply voltage of the timing relay. No external voltage should be connected to contact signal. 700HRV52TU24 supply voltage: 24...48V AC, 12...48V DC / 700-HRV52TA17 supply voltage: 100...240V AC, 100...125V DC.
Solid-State Signal -- Cat. Nos. 700-HR52, -HRT6 Timing relay is suitable for use with a 3-wire NPN 12...24V DC sensor. Supply voltage potential of sensor must be the same as the supply voltage potential of the timing relay. Permissible off-state leakage current from sensor: 0.01 mA max.

t1< T t1
Power to Timing Relay Reset Signal Timing Cycle
Timing Relay Output
t1 Power to Timing Relay
Gate (pause) Timing Cycle Timing Relay Output
R S G
5v, 1mA

T

t2

t1+t2 = T

S

U

U

( )

( + )

+ 12...24V DC COM

0.1mA

R S

G

COM ( )

(+) 12...24V DC

Solid-State Signal -- Cat. No. 700-HRV
Timing relay is suitable for use with a 3-wire NPN or PNP 12...24V DC sensor. Supply voltage potential of sensor must be the same as the supply voltage potential of the timing relay. Permissible off-state leakage current from sensor: 0.01 mA max.

+ 12...24V DC COM
S

+ 12...24 V DC COM
S

PNP Wiring Diagram

COM( ) (+) 12...24V DC

NPN Wiring Diagram

COM( ) (+) 12...24V DC

Circuit Impedance Power-OFF Reset Signal Duration
Signal Options

Signal Specifications

Circuit impedance can be used to calculate the maximum wiring distance from the signal switch to the timing relay, for example. Permissiblesignal-ONimpedance:1 k max.
Permissible signal-OFF impedance: 100 k min.

Min. power-off time: 0.1 s, Reset Voltage: 10% max. of rated voltage

Min. pulse width: 0.05 s

700-HR52

700-HRT6

700-HRV5

700-HRQR

Start

X

X

X

NA

Reset

X

X

NA

X

Gate

X

X

NA

NA

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

123

Relay and Timer Specifications

Timing Charts - 700-HR Relays

Mode A -- ON-Delay a. Needs continuous input power applied. b. Timing is initiated by the leading edge of the start signal. c. Contacts change state after timing is complete. d. Additional start signals during timing don't reset timing or contacts. e. When the input power is removed contacts return to shelf state.

T Power Start
Output (N.C.)
Output (N.O.)

Basic Operation
T Power
Start Output

Power LED

Mode B -- Repeat Cycle, Off Start a. Need continuous input power applied. b. Timing is initiated by the leading edge of the start signal. Additional start signals during timing do not reset timing or contacts. c. For the first time period the contacts remain in their shelf state. When that time period is complete contacts change state for the same time period (time on = time off). d. This cycle repeats itself until input power is removed or reset signal is applied. When the input power is removed or reset signal is applied contacts return to the shelf state.

Basic Operation

Power Start
Output (N.C.) Output (N.O.)
Power LED

T

T

T

Power Start
Output

T

T

T

Mode B2 --Repeat Cycle On start a. Need continuous input power applied. b. Timing is initiated by the leading edge of the start signal. Additional start signals during timing do not reset timing or contacts. c. For the first time period the contacts change state. When that time period is complete contacts return to the shelf state for the same time period (time on = time off). d. This cycle repeats itself until input power is removed or reset signal is applied. When the input power is removed or reset signal is applied contacts return to the shelf state.

Basic Operation

Power Start Output (N.C.)
Output (N.O.) Power LED

TTT

Power Start
Output

T

T

T

Mode C -- Watchdog monitor (Trigger = Signal On/Off ) a. Need continuous input power applied. b. Contacts change state immediately when start signal is applied or when start signal is removed (only if timing cycle was complete). c. Timing is initiated at the leading edge of the start signal. After the first timing cycle is complete, timing is initiated by the trailing edge of the start signal. d. At the end of the time period contacts return to the shelf state. e. Relay timing is reset when additional start signals are applied while the relay is timing. Contacts remain in energized state. f. When the input power is removed contacts return to the shelf state.

Power Start
Output (N.C.) Output (N.O.)
Power LED

T

T

t<T

t

T

Basic Operation

Power

T

T

Start

Output

124

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Mode D -- Off-Delay (Trigger = Signal Off) a. Need continuous input power applied. b. Contacts change state immediately when start signal is applied. c. Timing is initiated by the trailing edge of the start signal. d. At the end of the time period contacts return to the shelf state. e. Relay timing is reset when additional start signals are applied while the relay is timing. Contacts remain in energized state. f. When the input power is removed contacts return to the shelf state.

Power Start Output (N.C.)
Output (N.O.) Power LED

Basic Operation

T

t

t<T Power

T

Start

Output

Mode E -- One-Shot (Trigger = Signal On) 700-HR52, -HRV, and -HRT6 a. Need continuous input power applied. b. Timing is initiated by the leading edge of the start signal. c. Contacts change state immediately when start signal is applied. d. At the end of the time period contacts return to the shelf state. e. Relay timing is reset when additional start signals are applied while the relay is timing. Contacts remain in energized state. f. When the input power is removed contacts return to shelf state.

Power Start Output (N.C.) Output (N.O.) Power LED

T

tT

Mode E -- One-Shot (Trigger = Power On) 700-HRS, -HRP, and -HRT4 a. Need continuous input power applied. b. iming is initiated when the input power is applied. c. At the end of the time period contacts return to the shelf state. d. Relay timing is reset when input power is removed.

Basic Operation

t<T

T

Power

Start

Output

T Power

Basic Operation

t<T

Power

T

Timed Output (N.C.)
Timed Output (N.O.) Power LED

Output

Mode G -- Watchdog Monitor (Trigger=Signal ON/OFF)
a. Need continuous input power applied. b. Timing is initiated by the landing edge of the start signal. c. After the first timing cycle is complete the contacts change state and timing is initiated by the trailing edge of the start signal. d. At the end of the time period the contacts return to the shelf state. e. Relay timing is reset when additional start signals are applied while the relay is timing. f. When the power is removed contacts return to the shelf state.

Relay and Timer Specifications

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

125

Relay and Timer Specifications

Mode J -- Delayed One-Shot (Trigger = Power On) a. Need continuous input power applied. b. No start signal applied. c. Timing is initiated when input power is applied. d. Contacts change state after the timing for a fixed time of 1s +/-0.5s e. At the end of the 1 sec period the contacts return to the shelf state. f. When the input power is removed contacts return to the shelf state.

T Power
Output (N.C.)
Output (N.O.) Power LED

1s ±0.5s

Basic Operation

T Power
Output (N.O.)
Power LED

1s ±0.5s

Mode Star-Delta a. Need continuous input power applied. b. No start signal required. Timing is initiated when input power is applied. c. Star ouput contact changes state when input power is applied. d. After timing is complete star output contact returns to the shelf state then both the star & delta contacts remain in shelf states until transfer time setting is complete. e. Delta output contact changes state after transfer time is complete. f. Instantaneous contact changes state when input power is applied. g. All contacts return to the shelf state when input power is removed.

Power Output (N.C.) Output (N.O.) Output 8-5, LED Output 8-6, LED

t1

t2

Power Instantaneous Output
Output 8-5, LED Output 8-6, LED

Basic Operation

t1

t2

Mode True Off-Delay (Trigger = Power Off) a. Continuous input power is NOT required. b. No start signal applied. c. Contacts change state immediately when input power is applied. d. Timing starts when input power is removed. e. At the end of the time period contacts return to the shelf state. f. Relay timing is reset when input power is reapplied while the relay is timing. Contacts remain in energized state.

Power Output (N.C.) Output (N.O.) Relay On LED

t<T

T

t

T

Basic Operation

T Power

Output

Relay On LED

126

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications
Dimensions - 700-HR Relays
Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

127

Relay and Timer Specifications

700-HT Plug-in Timing Relay
· Timing Relay (On-Delay or Off-Delay) · Rugged Pin Style Socket Mounting · 10 A, DPDT Contact Ratings · 0.1 s...30 min Fixed Timing Relay · 0.1 s...3 min Single Adjustable Timing Relay · Single or Fixed Timing

Single Range Timing Relay with Pin Style Terminations

700 ­ HT

2

a

b

c

Catalog Number Explanation - 700-HT Relays

a Bulletin Number

b Type of Relay

c Operating Mode

d Number of Poles

HT -

1­On-delay

700

Tube Base Adjustable

2­Off-delay

Timing Relay

2 - 2PDT

2

A A2

d

e

f

e Timing Range
A­ 0.1...10 s B­ 1.0...100 s C­ 0.1...10 min D­ 1.0...100 min E ­ 0.1...10 hr

Operating Mode

Wiring Diagrams U.S./Canada

International

f Coil Voltage
U12­ 12V DC U24­ 24V AC/DC, 50/60 Hz U120­ 120V AC/DC, 50/60 Hz A2 ­ 240V AC, 50/60 Hz

On-Delay

Socket

700-HN125 or 700-HN100

700-HN100

Off-Delay

700-HT DPDT 2-Pole -- 2 Form C Contacts

Socket

700-HN126 or 700-HN101

700-HN101

128

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications
Fixed Timing Relays
700-HTF Fixed Timing Relays feature a plug-in tube base. Construction is the same as the 700-HT relay except that the adjustment knob has been removed to help prevent unwanted tampering. The timing and output specifications are identical to those of the 700-HT relay. Setting time will be ±5% of the time ordered.

700 ­ HTF

2

2

025

S

A2

a

b

c

d

e

f

g

Catalog Number Explanation - 700-HTF Relays

a Bulletin Number

b Type of Relay

HTF-

700

Tube Base Fixed Timing

Relay

c Operating
Mode
1­On-delay 2­Off-delay

d Number of
Poles
2 - 2PDT

e Timing Range
001...999 ­ The three digit code represents a numeric
value with one decimal place. For example: code 001 is 0.1, code 025 is 2.5,
and code 999 is 99.9 The acceptable range for each time unit is
listed below: Seconds - 001...999 Minutes - 001...999 Hours - 001...100

f Timing Units
S ­Seconds M ­Minutes H ­Hours

g Coil Voltage
U12­ 12V DC U24­ 24V AC/DC, 50/60 Hz U120­ 120V AC/DC, 50/60 Hz A2 ­ 240V AC, 50/60 Hz

Socket and Retainer Clip Reference

Relay Type

Socket Cat. No.

700-HT12

700-HN100 700-HN125

700-HT22

700-HN101 700-HN126

(1) Design of these sockets holds the relays securely and does not require retainer clips.

Retainer Clip Cat. No. 700-HN110 Not Required(1) 700-HN110 Not Required(1)

Accessories - 700-HT Relays

Description

Pkg. Qty. Cat. No.

Screw Terminal Tube Base Socket -- Panel or DIN Rail Mounting; Guarded Terminal Construction. 8-Pin for use with DPDT 700-HA Relays, -HX Digital Timing Relays, -HT (On-Delay) 10 and -HRM, -HRC and -HV (Repeat Cycle) Timing Relays. Order ten or multiples of ten

700-HN100

Screw Terminal Tube Base Socket -- Panel or DIN Rail Mounting; Open Style

Construction. 8-Pin for use with DPDT 700-HA Relays, -HT (On-Delay) and -HRM, -HRC and -HV (Repeat Cycle) Timing Relays. Order must be for 10 sockets or multiples of 10. No retainer clip

10

required.

700-HN125

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

129

Relay and Timer Specifications

Description

Pkg. Qty. Cat. No.

Screw Terminal Tube Base Sockets -- Panel or DIN Rail Mounting; Guarded Terminal Construction. 11-pin for use with 3PDT 700-HA relays.

10

700-HN101

Screw Terminal Tube Base Sockets -- Panel or DIN Rail Mounting; Open Style Terminal Construction. 11-pin for use with 3PDT 700-HA relays. No retainer clip required.

10

700-HN126

DIN (#3) symmetrical hat rail 35 x 7.5 x 1 m

10

199-DR1

Retainer Clip for Cat. Nos. 700-HN100 and -HN101 Sockets with 700-HT Timing Relays(1)Secures relay in socket. Order must be for 10 clips or multiples of 10.

10

700-HN110

Pre-Printed Identification Tags -- contains 10 sheets of pre-printed and blank tags. Each sheet contains 13 sets of the markings CR...9CR, TR...9TR, M...9M, F, R, 1S, and 117 blank 10 tags. Tags are peel-off with sticky backing for easy placement on relays.

700-N40

Blank Identification Tags -- contains 10 sheets of blank identification tags for customer specialized printing. Each sheet contains 546 blank tags. Tags are peel-off with sticky backing for 10 easy placement on relays.

700-N41

(1) Refer to 700-HT Timing Relay, Socket, and Retainer Clip Reference Chart.

130

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

Specifications - 700-HT

Pilot Duty Rating (1)
Rated Thermal Current (Ith)
Rated Insulation Voltage (Ui)

Inductive

Cat. No. 700-HT...

Cat. No. 700-HTF...

Electrical Ratings

NEMA B300

10 A

250V IEC, 300V UL/CSA

Make

Break

HP

Make

Break

HP

Contacts

120V AC 240V AC Resistive 28V DC

Permissible Coil Voltage Variation

Power Consumption ±10%

24V AC AC 120V AC
240V AC DC

Pole-to-Pole, same circuit (VRMS)
Dielectric Withstand Voltage Pole-to-Pole, different circuits (VRMS)
Contact-to-Coil (VRMS)
Electrical Life Operations
Switching Frequency Operations
Coil Voltages

Degree of Protection

Mechanical Life Operations

Switching Frequency Operations

Timing

Duty Cycle

Repeat Accuracy (constant voltage and temperature)

Repeat Accuracy (variable voltage and temperature)

Fixed Time Setting Accuracy

Scale Tolerance Reset Time

High End of Range Low End of Range ON Delay OFF Delay

30 A

3 A

1/2 N.O. 1/3 N.C

30 A

3 A

1/3

15 A

1.5 A

1/2 N.O. 1/3 N.C

15 A

1.5 A

1/2

10 A

10 A

--

10 A

10 A

--

85...110% of Nominal Voltage at 50 Hz 85...110% of Nominal Voltage at 60 Hz 80...110% of Nominal Voltage at DC

2 VA

4 VA

4 VA

1.3 W

Design Specification/Test Requirements

1000V AC

Mechanical
-- +5% -50%

2000V AC
2000V AC 100,000 minimum
1800/hr See product selection

Open Type (Guarded Terminal Sockets) 10 x 106
18,000/hr
Continuous
±2% (Time Delay: 0.1...2 s) ±1% (Time Delay: >2 s)

±10%

100 ms 40 ms

±5% (Time Delay: 0.1...2 s) ±1% (Time Delay: >2 s)
--
--

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

131

Relay and Timer Specifications

Environmental
Temperature
Altitude Construction Insulating Material Enclosure Contact Material Terminal Markings on Socket

Operating Storage

Sockets

Certifications Standards
(1) See NEMA Ratings and Test Values on page 5.

Cat. No. 700-HT...

Cat. No. 700-HTF...

­28...+65 °C (50 °C max., 240V AC coil) (­18...+149 °F) (122 °F max., 240V AC coil)
­55...+85 °C (­67...+185 °F)
2000 m (6560 ft)

Molded High Dielectric Material
Impact Resistant Dust Cover
Silver Cadmium Oxide
In accordance with EN50 005
8- or 11-Pin Socket (On = 8, Off = 11) 700-HN100, -HN125 700-HN101, -HN126
CSA Certified, File 223833, UL Recognized, File E3125 Guide NLDX 2,UL Listed,whe used with 700-HN100, 700-HN101, 700-HN125, and 700-HN126 Sockets, File No. E3125 Guide NLDX, CE Marked
EN 61812-1, CSA 22.2 No. 14, UL 508

Trigger Signal Cat. Nos. 700-HT
Contact closure provides signal to timer. A low energy signal is generated by the 700-HT timing relay. For optimum reliability, use contacts designed for low energy switching (10V, 1 mA) (Bul. 800F-X__V, 800T-X__V). No external voltage should be connected to the contact signal.

Timing Diagrams - 700-HT Relays

ON Delay

OFF Delay

132

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

700-HV Timing Relay
· Repeat Cycle Timing Relay · 10 A Contact Rating · DPDT · Pin Style Terminals · 0.1 s...30 min. · Repeat Cycle Adjustable Timing
· Two Timing Adjustments T1  T2
Repeat Cycle Timing Relays with Pin Style Terminations with 2 Adjustments (T1  T2)
Operating Mode

Relay and Timer Specifications

Wiring Diagrams U.S./Canada

International

Repeat Cycle

700-HV Repeat Cycle Timing Relay DPDT 2-Pole -- 2 Form C Contacts

Socket

700-HN125 or 700-HN100

700-HN100

700 ­ HV

3

2

A

A

A2

a

b

c

d

e

f

g

Catalog Number Explanation - 700-HV Relays

a Bulletin Number

b Type of Relay

c
Operating Mode

d
Number of Poles

e
Timing Range OFF Time

Code OFF Time -- Type HV

3 ­Power ON

A ­ 0.1...10 s

Repeat Cycle,

B ­ 1.0...100 s

700

HV ­ Tube Base Repeat OFF Start Cycle Timing Relay (Repeat Cycle,

2 - 2PDT

C ­ 0.1...10 min

OFF/ON

D ­ 1.0...100 min

Delay)

E ­0.1...10 hr

f Timing Range
ON Time
Code ON Time -- Type HV A 0.1...10 s B 1.0...100 s C 0.1...10 min
D 1.0...100 min E 0.1...10 hr

g Coil Voltage
U12 ­12V DC U24 ­24V AC/DC, 50/60 Hz U120 ­ 120V AC/DC, 50/60 Hz
A2 ­240V AC, 50/60 Hz

Socket and Retainer Clip Reference

Relay Type

Socket Cat. No.

Retainer Clip Cat. No.

700-HV

700-HN100 700-HN125

700-HN110 Not Required(1)

(1) Design of these sockets holds the relays securely and does not require retainer clips.

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

133

Relay and Timer Specifications

Accessories - 700-HV Relays

Photo

Description

Pkg. Qty.

Cat. No.

Screw Terminal Tube Base Socket -- Panel or DIN Rail Mounting; Guarded Terminal Construction. 8-Pin for use with DPDT 700-HA Relays, -HX Digital Timing Relays, -HT (On-Delay) and - 10 HRM, -NRC and -HV (Repeat Cycle) Timing Relays. Order ten or multiples of ten

700-HN100

DIN (#3) symmetrical hat rail 35 x 7.5 x 1 m

10

199-DR1

Screw Terminal Tube Base Socket -- Panel or DIN Rail Mounting; Open Style Construction. 8Pin for use with DPDT 700-HA Relays, -HT (On-Delay) and -HRM, -HRC and -HV (Repeat Cycle) Timing 10 Relays. Order must be for 10 sockets or multiples of 10. No retainer clip required.
Pre-Printed Identification Tags -- contains 10 sheets of pre-printed and blank tags. Each sheet contains 13 sets of the markings CR...9CR, TR...9TR, M...9M, F, R, 1S, and 117 blank tags. Tags are 10 peel-off with sticky backing for easy placement on relays.
Blank Identification Tags -- contains 10 sheets of blank identification tags for customer specialized printing. Each sheet contains 546 blank tags. Tags are peel-off with sticky backing for easy placement on 10 relays.

700-HN125 700-N40 700-N41

134

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

Specifications - 700-HV Relays

Pilot Duty Rating Rated Thermal Current (Ith) Rated Insulation Voltage (Ui)

Inductive

Cat. No. 700-HV...

Electrical Ratings

NEMA B300

10 A

250V IEC, 300V UL/CSA

Make

Break

Hp

Contacts

Permissible Coil Voltage Variation

Power Consumption

AC

±10%

DC

Dielectric Withstand Voltage
Electrical Life Operations Switching Frequency Operations Coil Voltages
Degree of Protection Mechanical Life Operations Switching Frequency Operations Timing Repeat Accuracy (constant voltage and temperature) Repeat Accuracy (variable voltage and temperature) Scale Tolerance Reset Time
Temperature
Altitude Construction Insulating Material Enclosure

120V AC

30 A

3 A

1/2 N.O. 1/3 N.C.

240V AC

15 A

1.5 A

1/2 N.O. 1/3 N.C.

Resistive 28V DC

10 A

10 A

--

85...110 of Nominal Voltage at 50 Hz 85...110 of Nominal Voltage at 60 Hz 80...110 of Nominal Voltage at DC

24V AC

2 VA

120V AC

4 VA

240V AC

4 VA

1.3 W

Design Specification/Test Requirements

Pole-to-Pole, same circuit (VRMS)

1000V AC

Pole-to-Pole, different circuits (VRMS)

2000V AC

Contact-to-Coil (VRMS)

2000V AC

100,000 minimum

1800/hr

See product selection

Mechanical

Open Type (Guarded Terminal Sockets) 10 x 106

18,000/hr

Duty Cycle

Continuous

±2% (Time Delay: 0.1...2 s) ±1% (Time Delay: >2 s)

±10%

High End of Range Low End of Range
Operating Storage

Environmental

+5% -50% 100 ms
­28...+65 °C (50 °C max., 240V AC coil) (­18...+149 °F) (122 °F max., 240V AC coil)
­55...+85 °C (­67...+185 °F) 2000 m (6560 ft.)

Molded High Dielectric Material Impact Resistant Dust Cover

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

135

Relay and Timer Specifications
Contact Material Terminal Markings on Socket Sockets Certifications Standards
Timing Diagram- 700-HV Relays

Silver Cadmium Oxide
In accordance with EN50 005
8-Pin Socket Cat. No. 700-HN100, -HN125
CSA Certified, File 223833; UL Recognized, File E3125; Guide NLDX 2; cULus Listed when used with 700-HN100 and 700HN125 sockets; CE Marked
EN 61812; CSA 22.2 No. 14; UL 508

Dimensions - 700-HV Relays
Approximate Dimensions are shown in millimeters (inches). Approximate Dimensions are not intended to be used for manufacturing purposes.

700-HV Timing Relay

Cat. No. 199-DR1 DIN Mounting Rail Series B Cat. No. 199-DR4 DIN Mounting Rail Series B Has No Mounting Holes

Cat. No. 199-DR1 199-DR4

A

B

C

D

Approx. Shipping Wt.

35

27

7.5

1.02 1.85 kg

(1-3/8) (1-1/16) (19/64) (1/64) (4.07 lbs.) (10/pkg)

35

27

15

2.3

3.68 kg

(1-3/8) (1-1/16) (19/32) (3/32) (8 lbs.) (5/pkg)

136

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

Cat. No. 700-HN100 Panel Mounting
Double Wire--2 x 2.5mm2 (#2-14 AWG...#2-20 AWG) (Either Solid or Stranded)
Strip Length: 9 mm (3/8 in) - Torque: 0.8 N·m (7 ib·in)

Cat. No. 700-HN125 Wire Size: 2 x 2.5 mm2 Single Wire--Up to #12 AWG Double Wire--2 x 2.5mm2 (#2-14 AWG...#2-20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in) - Torque: 0.8 N·m (7 ib·in)

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

137

Relay and Timer Specifications

700-HX Multi-Function Digital Timing Relay

· Digital timing relay with LCD display · Socket- or panel-mounted (NEMA 4X/IP66) · 5A, B300, SPDT contact ratings · 10 Functions or modes
· Environmentally friendly -- flash memory, no battery

Photo

Operating Mode

Timing Range

A mode: Signal ON-Delay 1 A-1 mode: Signal ON-Delay 2 A-2 mode: Power ON-Delay 1 A-3 mode: Power On-Delay 2 B mode: Repeat Cycle 1 B-1 mode: Repeat Cycle 2 D mode: Signal OFF-delay E mode: One Shot F mode: Cumulative Z mode: On/Off duty adjustable repeat cycle S mode:stop watch toff: Flicker OFF start 1 ton: Flicker ON start 1 toff-1: Flicker OFF start 2 ton-1: Flicker ON start 2

0.000...9.999 s 0.000...99.99 s 0.000...999.9 s 0.000...9999 s 0.000...99 min 59 s 0.000...999.9 min 0.000...9999 min 0.000...99 hr 59 min 0.000...999.9 hr 0.000...9999 hr

Socket Type
700-HN100 700-HN125

Contact Output

No. of Pins

SPDT

8

Input Voltage Cat. No. 100...240V AC 700-HX86SA17

24V AC 12...24V DC

700-HX86SU24

Socket and Retainer Clip Reference

Timer Type

Socket Cat. No.

Retainer Clip Cat. No.

700-HX

700-HN100 700-HN108

700-HN131 Not Required (1)

700-HN125

Not Required

(1) Design of socket holds the relay securely and does not require retainer clips.

Accessories - 700-HX Relays
Photo

Description

Pkg. Quantity Cat. No.

Screw Terminal Tube Base Socket -- Panel or DIN Rail Mounting; Guarded Terminal Construction. 8-Pin for use with 700-HX Timing Relays. Order ten or multiples of ten

10

700-HN100

Screw Terminal Tube Base Socket -- Panel or DIN Rail Mounting; Open Style

Construction. 8-Pin for use with 700-HX Timing Relays. Order must be for 10 sockets or

10

multiples of 10. No retainer clip required.

DIN (#3) symmetrical hat rail 35 x 7.5 x 1 m

10

700-HN125 199-DR1

138

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Photo

Description
Specialty Socket 8-pin backwired socket with solder terminals. For use with 700-HX Timing Relays.

Relay and Timer Specifications Pkg. Quantity Cat. No.

10

700-HN108

Retainer Clip for Cat. Nos. 700-HN100 Sockets with all 700-HX Timing Relays

Secures timer in socket.

10

Note: Not required for installation

700-HN131

Frame Adapter For flush or door mounting of all 700-HR and -HX timers.

1

700-HN130

Protective Cover

Helps prevent tampering of timing and mode settings. Provides a degree of protection against water and dirt from entering the front of the relay. For use with all 700-HR and -HX timing

1

relays.

700-HN132

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

139

Relay and Timer Specifications

General Timer Functions- 700-HX Relays

Display Section

Operation Key

1. Key Protect Indicator (orange)

4

8. Mode Key

2. Control Output Indicator (orange) 1

3. Reset Indicator (orange)

2 3

8

4. Present Value Display (Main display) 9
(Character height: 12 mm, red *)

5

(Changes modes and setting items)

6

7

9. Reset Key

10

(Resets present value and output)

11

10. Up Keys 1 to 4

* Characters on models with screw terminals

Front View

11. Down Keys 1 to 4

can be switched between red, green, and orange.

12

5. Time Unit Indicators

Switches

(Color is same as present value display.)
(If the time range is 0 min, 0 h, 0.0 h, or 0 h 0 min, these indicators flash to indicate timing
operation.)

12. Key-protect Switch

(Default setting)

OFF (Disabled)

ON (Enabled)

6. Set Value Display (Sub-display) (Character height: 6 mm, green)

7. Set Value 1, 2 Indicator (green)

Character Size for Present Value Display

Character Size for Set Value Display

12 mm

6 mm

140

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Specifications - 700-HX Relays
Attribute

Pilot Duty Rating Rated supply voltage Operating voltage range Power consumption
Inrush Current
Make
Break Hp at 120V AC Hp at 240V AC

100...240V AC 24V AC/12...24V DC 100...240V AC 24V AC/12...24V DC 120V AC 240V AC 120V AC 240V AC

Mounting Method Display Digits
Timer
Inputs
Control output External Power Supply Key Protect Memory Backup

Time ranges
Timer modes Output modes Input signals Input method Start, reset, gate Power reset

Accuracy of Operating Time and Setting Error (1)

(1) The values are based on the set value. (2) The value is applied for a minimum pulse width of 1 ms.

Relay and Timer Specifications
700-HX
Electrical Ratings NEMA B300
100 to 240V AC, 24V AC/12 to 24V DC (50/60Hz) (permissible ripple: 20%(p-p) max.) 85...110% of rated supply voltage 4.3VA 3.4VA/1.7 W 3 A 5 A 30 A 15 A 3 A 1.5 A 1/4 Hp 1/3 Hp
Mechanical Flush mounting, surface mounting, DIN mounting Seven-segment, negative transmissive LCD; Present value (red, 12 mm high characters); Set value (green, 6 mm high characters) Four digits
0.000...9.999 s, 0.00...99.99 s, 0.0...999.9 s, 0...9999 s, 0 min 00 s...99 min 59 s, 0.0...999.9 min, 0 hr 00 min...99 hr 59 min, 0.0 hr...999.9 hr, 0 hr...9999 hr Elapsed time (Up), remaining time (Down), selectable A, A-1, A-2, A-3, B, B-1, D, E, F, Z, S, tOFF, tON, tOFF-1, or tON-1 Start, reset No-voltage input via:NPN transistor or switching of contact Minimum input signal width: 1 or 20 ms (selectable) Minimum power-opening time: 0.5 s (Except for A-3, B-1, and F mode) SPDT contact output: 5 A at 250V AC, resistive load (cosine=1) Minimum applied load: 10 mA at 5 V DC (failure level: P, reference value) No Yes EEP-ROM (overwritten 100 000 times min), which can store data for 10 years min. Power-ON start: +-0.01% +-50 ms max. (1)to be rated against set value Signal start: +- 0.005% +-30 ms max. (1)to be rated against set value Signal start at transistor output model: +- 0.005% +-3 ms max. (2) If the set value is within the sensor waiting time (250 ms max.)

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

141

Relay and Timer Specifications

Attribute

700-HX

Environmental

Installation environment

Setup category II, pollution degree 2 (as per IEC61010-1)

Ambient temperature

-10...+55 °C (14...141 °F ), Avoid freezing or condensation

Ambient humidity

25...85 %

Storage temperature

-25...+65 °C (-13...+149 °F ), Avoid freezing or condensation

Altitude, max
Insulation Resistance

Characteristics (1)

2,000 m
100 m min.(at500VDC)

Dielectric Strength

2000V AC, 50/60Hz for 1 min between current-carrying terminals and non-current- carrying metal parts (1000V AC for 24V AC/12 to 24V DC type), 1000 VAC, 50/60 Hz for 1 min between non-
continuous contacts

Noise Immunity

±1.5 kV (between power terminals) for 100 to 240 VAC, ±480V for 24VAC/12 to 24VDC, and
±600V (between input terminals), square-wave noise by noise simulator (pulse width: 100 ns/ 1 s, 1-ns rise)

Static Immunity

±8 kV (malfunction), ±15 kV (destruction)

Vibration Resistance Shock Resistance

Malfunction Malfunction

10...55 Hz with 0.35 mm single amplitude each in three directions for 10 min 98 m/s2 (approx. 10 G) each in three directions

Life Expectancy

Mechanical Electrical

10 million operations min. (under no load at 18 000 operation/hr) 100 000 operations min. (5 A at 250V AC, resistive load at 1800 operation/hr)

(EMI)

EN61812-1

Emission Enclosure:

EN55011 Group1 class A

Emission AC mains:
EMC (EMS)

EN55011 Group1 class A EN61812-1

Immunity ESD:

EN61000-4-2: 4 kV contact discharge (level2) 8 kV air discharge (level3)

Enclosure Ratings

Immunity RF-interference:

EN61000-4-3: 10 V/m Panel surface:IP66 and NEMA Type 4 (indoors) (2)

Weight

Approx. 100 g

Certifications

CE Certified; cURus (File No. E14843, Guide NRNTZ/NRNT8), C-Tick Marked

Standards

EN61010-1, EN 61326, VDE0106/P 100, CSA C22.2 No. 14, UL 508

(1) More information in the 700-HX User Manual, publication 700-UM002. (2) An attached waterproof packing is necessary to ensure IP66 waterproofing between the 700-HX and installation pan.

142

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

Timing Charts- 700-HX Relays

One-Shot

One-shot outputs can be set to

Sustained Output 0.1s, 0.5 s, 1 s, 5 s, 10 s, or 20 s.

Power Start signal
Gate*

Output Mode A Mode: Signal ON-Delay (Timer resets when power comes ON.)
Timing starts when the start signal goes ON. While the start signal is ON, the timer starts when power comes ON or when the reset input goes OFF. The control output is controlled using a sustained or one-shot time period.
Basic Operation

Reset t
Control output

Set value

UP Timing

0

diagram

Set value

DOWN

0

t

t

Power Start Signa**l
Input

Timing

Output
*Output is instantaneous when setting is 0. ** Start signal input is enabled during timing.

Power

Start signal

Gate* Reset

Control output

Set value

UP Timing

0

diagram

Set value

DOWN

0

Power Start signal
Gate * Reset

Output Mode A-1: Signal ON-Delay 2 (Timer resets when power comes ON.)
Timing starts when the reset input goes ON and is reset when the start signal goes OFF. While the start signal is ON, the timer starts when the power comes ON or when the reset input goes OFF. The control output is controlled using a sustained or one-shot time period.
Basic Operation
Power

Start Signal

Input

Timing

Output

*Output is instantaneous when setting is 0.

Output Mode A-2: Power ON Delay 1 (Timer resets when power comes ON)

Timing starts when the reset input goes OFF. The start signal disables the timing function (i.e., same function as the gate input). The control output is controlled using a sustained or one-shot time period.
Basic Operation

Control output

Set value

UP Timing

0

diagram

Set value

DOWN

0

Power

Timing

Output *Output is instantaneous when setting is 0.

Output Mode A-3 Power ON Delay 2 (Timer does not reset when power comes ON)

Power Start signal
Gate * Reset

Timing starts when the reset input goes OFF. The start signal disables the timing function (i.e., same function as the gate input). The control output is controlled using a sustained or one-shot time period.
Basic Operation

Control output

Set value

UP Timing

0

diagram

Set value

DOWN

0

Power Output

Timing Sustained

*Output is instantaneous when setting is 0.

Gate not included on any mode of this relay.

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

143

Relay and Timer Specifications

Sustained Output

Power

Start signal

Gate* Reset

Control output

Set value

UP Timing

0

diagram

Set value

DOWN

0

One-Shot Output
Power Start Signal

Gate* Reset Control Output

Set Value

Timing UP

0

Diagram

Set Value DOWN 0

Output Mode B: Repeat Cycle (Timer resets when power comes ON.)
Timing starts when the start signal goes ON. The status of the control output is reversed when time is up (OFF at start). While the start signal is ON, the timer starts when the power comes ON or when the reset input goes OFF.
Basic Operation

Power
Start Sign*a*l Input

Timing Timing Timing Timing

Output

* Normal output operation will not be possible if the set time is too short. Set the value to at least 100 ms (contact output type). ** Start signal input is disabled diring timing.
Timing starts when the start signal goes ON. The control output is turned ON when time is up. While the start signal is ON, the timer starts when the power cones ON or when the reset input goes OFF.
Basic Operation

Power Start Signa**l
Input
Output

Timing Timing Timing Timing

* Normal output operation will not be possible if the set time is too short. Set the value to at least 100 ms (contact output type). ** Start signal input is disabled during timing.

Sustained Output

Power

Start signal

Gate* Reset

Control output

Set value

UP Timing

0

diagram

Set value

DOWN

0

One-Shot Output

Power

Start signal

Gate* Reset

Control output

Set value

UP Timing

0

diagram

Set value

DOWN

0

Output Mode B-1: Repeat Cycle 2 (Timer does not reset when power comes ON)
Timing starts when the start signal goes ON. The status of the control output is reversed when time is up (OFF at the start). While the start signal is ON, the timer starts when the power comes ON or when the rest input goes OFF.
Basic Operation

Power
Start Signa**l Input

Timing Sustained

Timing

Output
* Normal output operation will not be possible if the set time is too short Set the value to at least 100 ms (contact output type).
** Start signal input is disabled during.
Timing starts when the start signal goes ON. The control output comes ON when time is up. While the start signal is ON, the timer starts when the power comes ON or when the reset input goes OFF.
Basic Operation

Power
Start Sign*a*l Input

Timing

Timing

Output

Sustaining

* Normal outout operation will not be possible if the set time is too short. Set the value to at least 100 ms (contact output type). ** Start signal input is disabled during timing.

Gate not included on any mode of this relay.

144

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

Power

Start signal

Gate* Reset

Control output

Set value

UP Timing

0

diagram

Set value

DOWN

0

Power

Start signal

Gate* Reset

Control output

Set value

UP Timing

0

diagram

Set value

DOWN

0

Output Mode D: Signal OFF-Delay (Timer resets when power comes ON.)
The control output is ON when the start signal is ON (except when the power is OFF or the reset is ON). The timer is reset when the time is up.
Basic Operation

Power

Start Signa**l

Input

Timing

Output

* Output functions only during start signal input when setting is 0.
** Start signal input is enabled during timing.
Output Mode E: Interval (Timer resets when power comes ON.)

Timing starts when the start signal comes ON. The control output is reset when time is up. While the start signal is ON, the timer starts when power comes ON or when the reset input goes OFF.
Basic Operation

Power

Start Signa**l Input

Timing

Output

* Output is disabled when the setting is 0. ** Start signal input is enabled during timing.

Output Mode F: Cumulative (Timer does not reset when power comes ON)

Start signal enables timing (timing is stopped when the start signal is OFF or when the power is OFF). A sustained control output is used.
Basic Operation

Gate not included on any mode of this relay.

Power Start Signal
Input Output

Timing

Timing

Sustained

*Output is instantaneous when setting is 0.

Z Mode
Output quantity can be adjusted by changing the cycle time set in the adjustment level to 1 and by changing the ON duty (%) set value. The set value shows the ON duty (%) and can be set to a value between 0 and 100 (%). When the cycle time is 0, the output will always be OFF. When the cycle time is not 0 and when ON duty has been set to 0 (%), the output will always be OFF. When ON duty has been set to 100 (%), the output will always be ON.

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

145

Relay and Timer Specifications

Power Start signal
* Gate

Z mode: ON/OFF-duty Adjustable Repeat Cycle
Timing starts when the start signal goes ON. The status of the control output is reversed when time is up (ON at start). While the start signal is ON, the timer starts when power comes ON or when the reset input goes OFF.
Basic Operation
Power

Reset

Control Output Cycle time

Timing diagram

ON duty setting (%) ON time

UP

0

Cycle time

ON duty setting (%) ON time

DOWN

0

Start sign*a*l input

Timing (cycle time)

Timing (cycle time)

Timing ON duty (%)

Timing ON duty (%)

Output
* Normal output operation will not be possible if the set time is too short. Set the value to at least 100 ms (contact output type).
** Start signal input is enabled during timing.
Output Mode S: Stop Watch (Timer resets when power comes ON)

Timing diagram

Power
Start signal
Gate/Reset 9999
Set time UP
0 Set time DOWN
0 Output

Sustained Output
Power

Start signal * Gate

Reset

Control Output

OFF Time UP ON Time

Timing

0

diagram

OFF Time DOWN ON Time
0

Gate not included on any mode of this Relay.

The signal starts and stops timing. The display is held and timing is continued if the reset or gate input is received during timing operation. The timer resets if the reset or gate input is received when the timing operation is stopped.
Basic Operation
Power

Start signal input
Gate/Reset

Timing

Display (for elapsed
time)

* * RST flashes

Note: Output is instantaneous when setting is 0.

Output Mode T OFF: Twin Timer OFF start

Timing starts when the start signal goes ON. The status of the control output is reversed when time is up (OFF at start). While the start signal is ON, the timer starts when power comes ON or when the reset input goes OFF.

Basic Operation

Power Start Signa**l
Input
Output

Timing Timing Timing Timing

OFF

ON

OFF

ON

* Normal output operation will not be possible if the ON/OFF set time is too short. Set the value to at least 100 ms (contact output type).
** Start signal input is disabled during timing.

146

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Sustained Output
Power

Start signal * Gate

Reset

Control Output

OFF Time UP ON Time

Timing

0

diagram

OFF Time DOWN ON Time
0

Power
Start signal
Gate
Reset
Control output
OFF time UP
ON time 0
OFF time DOWN
ON time 0

Timing diagram

Relay and Timer Specifications

Output Mode T ON: Twin Timer ON start
Timing starts when the start signal goes ON. The status of the control output is reversed when time is up (ON at start). While the start signal is ON, the timer starts when power comes ON or when the reset input goes OFF.
Basic Operation

Power Start Signa**l
Input
Output

Timing Timing Timing Timing

ON

OFF

ON

OFF

* Normal output operation will not be possible if the ON/OFF set time is too short. Set the value to at least 100 ms (contact output type).
** Start signal input is disabled during timing.
Output Mode TOFF-1: Flicker OFF start 2 (Timer does not reset when power comes ON)

Timing starts when the start signal goes ON. The status of the control output is reversed when time is up (OFF at start). While the start signal is ON, the timer starts when the power comes ON or when the reset input goes OFF.
Basic Operation

Power

Start signa*l

input

Timing OFF

Timing ON

Timing OFF

a

b

Output

(a + b = ON time)

* Start signal input is disabled during timing.

Note: Normal output operation will not be possible if the set time is too short. Set the value to at least 100 ms (contact output type).

Output Mode TON-1: Flicker ON start 2 (Timer does not reset when power comes ON)
Timing starts when the start signal goes ON. The status of the control output is reversed when time is up (ON at start). While the start signal is ON, the timer starts when the power comes ON or when the reset input goes OFF.
Basic Operation

Power

Start signa*l

input

Timing ON

Timing OFF

Timing ON

a

b

Output

(a + b = OFF time)

* Start signal input is disabled during timing.

Note: Normal output operation will not be possible if the set time is too short.

Gate not included on any mode of this Relay.

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

147

Relay and Timer Specifications

Dimensions- 700-HX Relays
Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.

48×48

7.5

14.3 63.7

44.8×44.8

60 min.

45

+0.6 -0

45

+0.6 -0

60 min. 15 min.

Cat. No. 700-HX... Panel Cutout

5.2 (13/64)
Terminal Arrangement

50 (1-63/64)

6.2 (15/64)

12.5 (1/2)

1000 (39-3/8)
Cat. No. 199-DR1 DIN Mounting Rail Series B Cat. No. 199-DR4 DIN Mounting Rail Series B Has No Mounting Holes

1.0 (0.04)
35.0 (1.38)
7.5 (0.3)

27.0 (1.06)

Signal Reset

Internal circuit

4 3
2 1
0V

5 6
7 8

(­) (+) Cat. No. 700-HX...

148

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

NEMA Industrial Relays
Product Overview

Relay and Timer Specifications

Bulletin No. Type

700-P Heavy-duty control relay

Features

· Convertible contacts · Up to 600V AC & DC · Very long life · Timer & latch options · Mechanically linked

Contact Form Contact Type Contact Material Electrical Max. Current AC Resistive Min. load
Coil Voltage
Coil Voltage Pickup Dielectric Withstand Reference Electric Service Life (cycles) Certifications Sockets Product Selection

2...12 poles, double break Bifurcated double break Bifurcated silver nickel
10 A 10V, 50 mA 1 mA, 5V with 700-CPR 24...600V AC 6...600V DC 85...110% AC coils, 80...110% DC coils 2640V
10 million at 10 A 120V AC cULus, CE DIN Rail, relay rail, or panel mount 151

700S-P Heavy-duty control relay
· Convertible contacts · Up to 600V AC & DC · Very long life · Timer & latch options · Mechanically linked
2...12 poles, double break Bifurcated double break Bifurcated silver nickel
10 A 10V, 50 mA 1 mA, 5V with 700-CPR 24...600V AC 6...600V DC 85...110% AC coils, 80...110% DC coils 2640V
10 million at 10 A 120V AC cULus, CE DIN Rail, relay rail, or panel mount 151

700-N Industrial Relay · Contact cartridges convertible from N.O. to
N.C. and vice versa · NEMA A300 AC · 24...250V AC coils · Pneumatic timing unit · Solid-state timing unit · Overlap contacts · Logic reed contacts 2- or 4-poles -- Silver
10 A
--
--
--
--
-- UL, CSA, CE -- 172

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

149

Relay and Timer Specifications
Product Overview

Bulletin No. Type
Features
Contact Form Contact Type Contact Material Electrical Max. Current AC Resistive Min. load Coil Voltage
Coil Voltage Pickup Dielectric Withstand Reference Electric Service Life (cycles) Certifications Sockets Timing Relay Information Control Outputs: Time Limit Instantaneous Timing Operation Modes: Time Range
Supply Voltage
Product Selection

700-R Sealed Switch · Hazardous location ratings · Long life in dirty environment · Timer and latch options · Switch 600V AC, 300V DC 2...8 Poles Sealed Switch Sealed Switch
5 A 1 mA, 5V 24...240V AC 24...250V DC 85...110% AC Coils 80...110% DC Coils 2640V
1.5 million at 5 A 120V AC UL, CSA, CE Panel or rail mount
--
-- --
--
176

700-RTC Solid-state Timing Relay
· Timed and instantaneous contacts. · Sealed contacts for harsh environments and
hazardous locations.
-- -- -- -- -- --
--
--
--
-- -- --
Four output contacts
On-Delay Off-Delay 0.05 s...64 min 24V AC 110...120V AC 220...240V AC 24V DC 120V DC 240V DC 181

150

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications
700-P Industrial Relays
700-P -- Direct DriveTM Convertible Contact Cartridge Relays
· NEMA and IEC ratings · 600V maximum AC/DC · Accessories for field installation: contact cartridges, adder decks, time delay, latching, surge suppressors, mounting strip · Contact Ratings: (10 A) 700-CP1, (20 A) 700-CPM, (35 A) 700-CPH, (Low Power) 700-CPR · For machine tool and other heavy-duty applications · Can accommodate ring tongue terminals · Integral DIN Rail mount on AC relays · Finger-safe protection standard · Factory supplied standard at 120V AC and 24V DC - user configurable for field assembly · Blank relays are available in all coil voltages for field custom configuration · Contact cartridge is convertible from N.O. to N.C. by simply turning cartridge over. The 700/700DC-P family of Direct Drive Industrial Relays offers switching solutions ranging from 200 mA in Low Energy Circuits to 35 A in Heavy Duty Circuits. All of the contacts can easily be changed from the standard N.O. to N.C. configuration. The relays can be accessorized to meet the application needs with the use of time delayed contacts, mechanical latches and NEMA enclosures. All devices are available in the most popular AC and DC control voltages. Combining different cartridges into one relay can yield a custom-tailored application solution. Relays are available without contact cartridges in all of the available AC and DC coil voltages for maximum flexibility. 700/700DC-P relays use standard (10 A) contact cartridges with a double-break and bifurcated design. Bifurcation provides excellent contact reliability and low-contact bounce, while the double-break contact design reduces the possibility of contacts welding and enhances the relay's ability to break DC circuits. These relays can be configured with a maximum of 12 contacts (only 8 may be N.C.).
A Modular Approach to Control Circuit Solutions
The 700-P AC control relay is factory assembled with a standard 10 A contact cartridges with all contacts as N.O.in either 2, 4, 8, or 12 pole configurations with a 120 volt operating coil. Four pole relays are also available at 240 and 480 VAC and can have up to eight contacts added by using adder decks. The 700DC-P control relay is factory assembled with a standard 10 A contact cartridges with all contacts as N.O. in either 4 or 8 poles with a 24 volt operating coil. The 4 pole is also available with a 120 VDC operating coil. For control relays that require different contact ratings or control voltages we offer a modular design that are easily field configurable. A base blank relay (either AC or DC control), a variety of contact kits, adder decks, and operating coils can be used to make an infinite number of custom control relay solutions.
· Master Control 700-PMCKIT master control cartridges provide (20 A) switching capability with large single-contact pads on each side of the spanner for twice the current rating to control heavy loads and provide for master control of a system. The cartridge also has the same double-break design as the standard 700-P relay contact cartridge. Relays can be configured with up to a maximum of 12 contacts (only 8 may be N.C.). Time delay and latching attachments are compatible with master cartridges.
· Heavy Duty Control 700-PHDKIT contact cartridges provide (35 A) switching capability through tandem contact cartridges. A jumper allows two (20 A) master contact cartridges to be connected in parallel. A maximum of six poles can be configured in a relay, only four of which can be normally closed. Time delay and latch attachments are available.
· Low Energy Control Logic Reed 700-PLRKIT contact cartridges provide switching to 200 mA @ 30 VDC. These contacts are matched with standard control (10 A) contact cartridges for low energy switching applications.
· Overlapping Contact 700-POLKIT contact cartridges provide (10 A) switching capabilities with the same rating as the standard contact. These cartridge used in pairs operate with the N.O. contact closing before the N.C. contact opens on pick-up and vice versa on the dropout.

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

151

Relay and Timer Specifications

AC-Operated Relays - In-stock Contact Configurations

Photo

Contacts N.O.(1)

Contact Arrangement and Markings

0

4-Pole Relay

Open Type, DIN Rail, or Relay Rail Mount (700-MP)

120V AC

240V AC

480V AC

700-P000A1

--

--

2

4-Pole Relay

4-Pole

4

Relay

700-P200A1

--

--

700-P400A1

700-P400A2

700-P400A4

8

8-Pole Relay

700-P800A1

--

--

12

12-Pole Relay

700-P1200A1

--

--

(1) Factory assembled N.O. contacts can be easily to N.C. in the field.

DC-Operated Relays - In-stock Contact Configurations

Photo

Contacts N.O. (1)

Contact Arrangement and Markings

4-Pole

0

Relay

Open Type Relay Rail Mount (2)

24V DC

120V DC

Cat. No.

Cat. No.

700DC-P000Z24

--

4-Pole

4

Relay

700DC-P400Z24

700DC-P400Z1

8
(1) Factory assembled N.O. contacts can be easily to N.C. in the field. (2) For DIN Rail mounting, order Cat. No. 700-DRA.

8-Pole Relay

700DC-P800Z24

--

152

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Base Blank Relay - Factory Assembled
Photo

Relay and Timer Specifications

Type of Control Circuit

Cat. No.

AC

700-P000

DC

700DC-P000

 AC Coil Voltage Code

Hz

24

50

--

60

A24

DC Coil Voltage Code
24 Z24

110 A1 --
48 Z48

115-120 -- A1

200-208 -- A20

230-240 -- A2

72

115-125

Z72

Z1

277

460-480

575-600

--

--

--

A27

A4

A6

230-250 Z2

575-600 Z6

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

153

Relay and Timer Specifications

Master (20 A) and Heavy Duty (35 A) Contact Cartridge Options

Follow this process to order a relay that utilizes: 20 A master contact cartridges or 35 A heavy duty contact cartridges.

Base Blank Relay

+ Cartridge Kit

+ Adder Decks

Base Blank Relay

Type of Control Circuit
AC

+ Coil
Cat. No.
700-P000A1

DC

700DC-P000Z24

+

Contact Cartridge Kits

Photo

Description

Contents

Master Contact Cartridge AC Rating Twice NEMA A600 DC Rating NEMA N150 P600

4 Master Cartridges (Cat. No. 700-CPM)

Continuous Carrying Current [A]

Cat. No.

20

700-PMCKIT

Heavy Duty Contact Kit

4 Master Cartridges and two sets of jumper terminals, rating label (makes two 35 A poles)

35

700-PHDKIT

+

Adder Decks

Do you have more than four circuits or more than two 35 A circuits in the relay?

Device Description

Adder Decks Required Cat. No.

8 Pole Device

700-PB00

12 Pole Device

700-PB00 700-PC00
(Qty 1 of each)

Additional Cartridge Kits Required 1 additional kit
2 additional kits

EXAMPLE

Heavy Duty circuit (35 A) application that requires 4 circuits and 240 AC control circuit:
· Base Unit: Cat. No. 700-P000A1 · Cartridge Kits: Cat. No. 700-PHDKIT - Qty 2 (Each kit makes two circuits) · Adder Deck: Cat. No. 700-PB00 · Coil: Cat. No. PA254

IMPORTANT If required, see Operating Coils for coil selection.

154

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

Logic Reed and Overlapping Contact Cartridge Option

Follow this process to order a relay that utilizes: low energy contact cartridges or overlapping late make or late break cartridges.

Base Blank Relay

+ Cartridge Kit

+ Adder Decks

+ Coil

Base Blank Relay

Type of Control Circuit
AC

Cat. No.
700-P000A1

DC

700DC-P000Z24

+

Contact Cartridge Kits

Photo

Description

Contents

Logic Reed Cartridge for Low Energy Circuits 150V AC 500 mA 25 VA Max. 30V DC 200 mA 6W Max.

2 Logic Reed Cartridges (Cat. No. 700-CPR) 2 Standard Cartridges (Cat. No. 700-CP1)

Overlap Contact Cartridges
Overlapping
Used in pairs. N.O. contact closes before N.C. contact opens on pick-up and vice versa on drop-out.

4 Overlapping Cartridges (Cat. No. 700-CP11Z)

+

Adder Decks

Do you have more than four circuits or more than two 35 A circuits in the relay?

Device Description

Adder Decks Required Cat. No.

8 Pole Device

700-PB00

12 Pole Device

700-PB00 700-PC00
(Qty 1 of each)

Continuous Carrying Current [A] 500 mA 150V AC 200 mA 30V DC
10

Cat. No. 700-PLRKIT

10

700-POLKIT

Additional Cartridge Kits Required 1 additional kit
2 additional kits

EXAMPLE

Logic Reed and Overlapping Contact Cartridge Option:
· Low Voltage Circuit 24V DC less than 200 mA · Base Unit: Cat. No. 700-P000A1 · Cartridge Kits: Cat. No. 700-PLRKIT - Qty 1 · Coil: Cat. No. PA254

IMPORTANT If required, see Operating Coils for coil selection.

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

155

Relay and Timer Specifications

Accessories - 700-P Relays
Adder Decks

Photo

Description

No. of N.O. Contacts

Continuous Carrying Current [A]

Arrangement

Second Deck (0-pole) 0

--

Second Deck (4-pole) 4

10

Third Deck (0-pole) 0

0

Third Deck (4-pole) 4

10

Cat. No. 700-PB00 700-PB40 700-PC00 700-PC40

156

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

Operating Coils

Bulletin 700-P Relays -- Bulletin 700-PLL-PKLL Mechanical Latch Attachments

Coil Volts(2)
24 48 72 110 (3)

Bulletin 700-P, 2...12-pole, AC control Bulletin 700-PLL­PKLL AC Mechanical Latch Attachment

60 Hz PA013 -- -- --

50 Hz PA407 -- -- PA236

60 Hz PL013 -- -- --

50 Hz PL407 -- -- PL236

DC PM714 PM724 PM730 --

Bulletin 700DC-P 2...12-pole, DC control
--
PD714
PD724
PD730
PD733 (100...110)

115...120(3)

PA236

--

PL236

--

--

--

110...115(1)
Bulletin 700-P Operating Coil

--

PA322

--

PL322

--

115...125

--

--

--

--

120§

PA322

--

PL322

--

130...140

--

--

--

--

200...208

PA249

--

--

--

220...230

PA251

PA339

--

--

230...240

PA254

PA342

PL254

--

230...250

--

--

--

--

277

PA260

--

--

--

380

--

PA354

--

--

415

--

PA357

--

--

440...460

--

PA360

--

--

460...480

PA273

--

--

--

Bulletin 700-PL

Unlatch Coil and

500

--

--

--

--

Magnet Assembly

575...600

PA278

--

--

--

(1) This coil is optimized for 110...115V, 50 Hz applications and will operate satisfactorily at 120V, 60 Hz. (2) Coils for AC relays cannot be used in DC relays and vice versa. (3) This coil is optimized for 115...120V, 60 Hz applications and will operate satisfactorily at 110V, 50 Hz.

-- PM735 -- -- -- -- -- PM748 -- -- --
--
-- -- --

PD735 -- -- -- -- -- PD748 -- -- --
--
-- -- PD758

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

157

Relay and Timer Specifications

Contact Cartridges (Convertible from N.O. to N.C. and N.C. to N.O.)

Photo

Description

Continuous Carrying Current [A]

Arrangement

Standard Contact Cartridge

AC Rating NEMA A600

10

DC Rating NEMA P600

Overlap Contact Cartridges Overlapping Used in pairs. N.O. contact closes before N.C. contact opens on pickup and vice versa on drop-out. (1)

AC Rating NEMA A600

10

DC Rating

NEMA P150 125V DC, 138 VA

5

Make and Break

Pkg. Quantity Cat. No.

1

700-CP1

2

700-CP11Z

Master Contact Cartridge

AC Rating Twice NEMA A600

20

DC Rating NEMA N150 P600

1

700-CPM

Logic Reed Cartridge for Low Energy Circuits 150V AC 500 mA 25 VA Max. 30V DC 200 mA 6W Max. (2)

Maximum 150V AC

500 mA

Maximum 30V DC

200 mA

1

700-CPR

(1) Not Direct Drive (2) The 700-CPR Logic Reed cartridge must be installed only in the 2nd deck (B1X - B4X, B1Y - B4Y position) or 3rd deck (C1X - C4X, C1Y - C4Y position) of the Bulletin 700 Type P relay. It is not recommended that the 700-CPR cartridge
be installed in the single deck (A1X - A4X, A1Y - A4Y position) because this may lead to improper operation.

158

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Electrically Held Relays -- Typical Wiring Diagrams

Relay and Timer Specifications

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

159

Relay and Timer Specifications

Pneumatic Time-Delay Unit
· Timing Range -- 0.1...60 s · 0, 2, or 4 instantaneous contacts · Two timed contacts -- both ON Delay or both OFF Delay · Convertible from ON Delay to OFF Delay and vice versa · Standard contact cartridges rated NEMA A600 (AC) and P600 (DC) · Master contact cartridges rated 2X NEMA A600 (AC) and N150 P600 (DC)

Photo

Operating Mode
On-Delay Off-Delay

No. of Timed Contacts (1)

N.O.

N.C.

Continuous Carrying Current [A]

10

1

1

20

Arrangement

Timing Range

Open Type
Without Enclosure(2)

Cat. No.

700-PT

0.1...60 s

700-PKT

(1) In addition to instantaneous cartridges on the relay (2) Mounts on 4-pole Bulletin 700-P or -PK relay or 2-pole Bulletin 700-PH relay.

Mechanical Latch Units
Photo

Description

Arrangement

AC-Operated Latch Units

DC-Operated Latch Units

Continuous Carrying Current [A]
No cartridge 10 20 No cartridge 10
20

Cat. No.
700-PLL 700-PLL11 700-PKLL11 700DC-PLL 700DC-PLL10
700DC-PKLL10

AC Coil Voltage Code

The Cat. No. as listed is incomplete. Select a voltage suffix code from the table below to complete the Cat. No. Example: Cat. No. 700-PLL becomes Cat. No. 700-PLLA1.

Hz 24 110 110-115 115-120 120

200-208 220-230 230-240 277 347 380 415 440-480 460-480 500 575-600

50 B24 A1 (1) B11 (2) --

--

--

--

--

-- -- -- -- --

--

-- --

60 A24 -- --

A1 (1)

B11(2)

--

--

A2

-- -- -- -- --

--

-- --

(1) Optimized for 115...120V, 60 Hz. Operates satisfactorily at 110V, 50 Hz. (2) Optimized for 110...115V, 50 Hz. Operates satisfactorily at 120V, 60 Hz.

DC Coil Voltage Code

The Cat. No. as listed is incomplete. Select a voltage suffix code from the table below to complete the Cat. No. Example: Cat. No. 700DC-PLL becomes Cat. No. 700DC-PLLZ24.

24

48

64

72

115-125 230-250 575-600

Z24

Z48

--

Z72

Z1

Z2

Z6

160

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Accessories
Photo

Relay and Timer Specifications

Description

Relays per Strip

4

Relay Rail

Simplifies panel layout. These indexed strips are easily cut to the

8

required length and bolted, riveted, or spot-welded in place. Relays are installed adjacent to one another on the mounting strip with the

12

captive mounting screws provided. Rows of relays on Relay Rail form

their own wiring trough.

Can be used with the following relays: 700P, 700DC-P, 700S-P, 700N, 16

700-R, 700-RTC

Pkg. Quantity
5 5 5
5

Cat. No.
700-MP4 700-MP8 700-MP12
700-MP16

DIN Rail Adapter Can be used with the following relays: Bulletin 700-P, 700DC-P, 700S-P, 700-N, 700-R, 700-RTC

1

700-DRA

DIN (#3) symmetrical hat rail 35 x 7.5 x 1 m

10

Type 1 Enclosure -- Use for all Bulletin 700-P relays except 10- and 12-pole DC relays or 6-pole DC Bulletin 700-PH relays.

1

Type 4/4X Enclosure -- For 2- and 4-pole Bulletin 700-P, -N, and -R relays and 2-pole heavy duty relays.

1

Type 7 & 9 Enclosure -- For 2- and 4-pole Bulletin 700-P, -N, and -R relays and 2-pole heavy duty relays. 1 conduit hub; top and bottom.

1

199-DR1
700-N31 700-N39 700-N33

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

161

Relay and Timer Specifications
Accessories
Photo

Description

Pkg. Quantity

Cat. No.

Surge Suppressors (RC Circuit) -- Surge suppressors reduce the high transient voltages generated when the coil circuit is opened. These suppressors can be used with Bulletin 700-P, -PH, -PK, and -N relays, and other electromechanical devices. They contain a resistor and capacitor. Maximum ratings: 150V, AC or DC, 35 VA. Cat. No. 700-N5 requires 1 in. additional depth of enclosure.

Mounting behind relay

1

Mounting on coil terminal

1

Surge Suppressor

24...48V AC/DC 1

When the circuit to a DC operating coil is opened, the inductive energy stored in

the coil can generate very high transient voltages. With the addition of the appropriate surge suppressor, the stored energy is absorbed and dissipated

50...120V AC/ DC

1

limiting the voltage spikes. A surge suppressor is not required with AC 700-R or -

RM relays because the AC operating coil transients are suppressed by a full wave rectifier connected to the coil.

130...250V AC/ DC

1

Diode Surge Suppressor -- for 6...300V DC voltage coils. Used on Bulletin 700-P, -PH, -PK, -N, -F, and -R relays.

1

35 A Jumper Kit ­ CSA Approved, UL Listed

This 35 A Jumper Kit can be used with any Bulletin 700-P and -PK AC or DC relay, Time-Delay relay or

Latch Unit equipped with 20 A Master Cartridges. It does not require any additional panel space.

Jumper Kit terminals are designed for one #8 AWG wire or two #10 AWG wires. When connecting the two 20 A Master Cartridges in parallel, it is important that they be the same configuration (Normally

1

Open or Normally Closed).

Jumpers can be added to any contact cartridge location on a relay except the two center poles

because of the wide spacing. An adhesive label is included with each kit listing the contact ratings.

700-N5
700-N24 199-FSMA9 199-FSMA10 199-FSMA11 199-FSMZ-1
700-CPH

Cat. No. 700-N3

Jumpers (Not applicable for Bulletin 700-PH or -PK relays) ­ For connection Jumper ­ For
between a middle pole and an outer pole on the left or right side of the relay. outer poles 50

Cat. No. 700-N4

Jumpers (Not applicable for Bulletin 700-PH or -PK relays) ­ For connection between two middle poles.

Jumper ­ For middle poles

Check Out Tool -- Mechanically maintains the Bulletin 700-P, -PH, or -PK relay in the energized position for troubleshooting purposes.

1 Adapter Plate -- Simplified relay conversion. Allows you to use the existing mounting holes when
you replace a Bulletin 700-B, -BR, -BX, or -D relay with a Bulletin 700-P, -PH, or -PK relay.

700-N3
700-N4 700-N23 700-N34

162

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

IP 2X Finger-Safe Cover Accessories

Photo

Description

Pkg. Quantity

Top Covers (Covering Top Level Contact Screws)

IP2X Top Cover for 700-P

1

Timer Top Cover Kit

1

Latch Top Cover Kit (for Relays with Mechanical Latch Attachment)

1

Timer Top Cover Kit, (for Master Cont. Relays with Pneumatic Timer)

1

Latch Top Cover Kit (for Master Cont. Relays with Mechanical Latch)

1

Deck Covers (Covering all terminals not on top deck, only for multi-deck relays)

IP2X Deck Cover for all AC & DC Relays in the 700P Range

1

Coil Covers

IP2X Coil Cover for all AC Relays in the 700P Range

1

IP2X Coil Cover for all DC Relays in the 700P Range

1

Cat. No.
700-PFSC 700-PFSTC 700-PFSLCK 700-PFSKTC 700-PFSKLCK
700-PFSDEK
700-PFSACC 700-PFSDCC

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

163

Relay and Timer Specifications

Specifications - 700-P Relays

Type

Standard Cartridge

Master Cartridge

Heavy duty

Bulletin No.

700-P

700-PMCKIT

700-PHDKIT

Electrical

Contact Rating Continuous

10 A @ 600V AC ; 5 A @ 600V DC

20 A @ 600V AC; 10 A @ 600V DC

35 A @ 600V AC; 20 A @ 600V DC

AC Ratings Make/Break
DC

NEMA A600 NEMA P600

2 x NEMA A600 N150 P600

2 x NEMA A600 N150 P600

Additional Contact Ratings for AC single-phase loads

3 Hp @ 240V AC - N.O.

5 Hp @ 240V AC - N.O.

2 Hp @ 240V AC - N.O./N.C.

3 Hp @ 240V AC - N.O./N.C.

--

1 Hp @ 120V AC - N.O./N.C.

2 Hp @ 120V AC - N.O./N.C.

20 A Resistive Heating to 600V AC

35 A General Use At 0.75 PF to 600V AC

20 A Tungsten Lighting Load to 480V AC

35 A Tungsten Lighting Load to 480V AC

DC Current Ratings Make/Break

Cartridge Cat. No. 700-CP1

Cartridge Cat. No. 700-CPM

Cartridge Cat. No. 700-CPH

Volts DC

DC Switching Inductive Load

Contacts in Series
1

24 64 125 250 500 600 24 64 125 250 500 600 24 64 125 250 500 600 480 480 275 138 135 120
W W W WW W
5 A 2.2 A 1.1 A .55 A .24 A .2 A 10 A 5 A 2.2 A .55 A .24 A .2 A 10 A 5 A 2.2 A .55 A .24 A .2 A

2

10 A 10 A 5 A 2 A .7 A .5 A 20 A 10 A 5 A 2 A .7 A .5 A 20 A 10 A 5 A 2 A .7 A .5 A

3

-- -- 7 A 3 A 1.5 A 1.0 A -- 15 A 7 A 3 A 1.5 A 1.0 A -- 15 A 7 A 3 A 1.5 A 1.0 A

4

-- -- 10 A 5 A 2.5 A 1.5 A -- 20 A 10 A 5 A 2.5 A 1.5 A -- 20 A 10 A 5 A 2.5 A 1.5 A

AC

85...110%

85...110%

85...110%

Coil Voltage Range DC

80...110%

80...110%

80...110%

Battery

85...115%

85...115%

85...115%

Inrush

Coil Consumption

AC

Sealed

Inrush DC
Sealed

PLL - PKLL AC Latch Unit

Inrush Sealed

PLL - PKLL DC Latch Unit

Unlatch Intermittent

50 Hz 132VA (2) 19.3VA (2)
15VA (2) 5.4VA (2)

12.7VA (2) 12.7VA (2)
35VA (2) 35 W (2)

60 Hz 138VA (2) 19VA (2)
15.6VA (2) 5.5VA (2)

50 Hz 132VA (2) 19.3 VA (2)
5VA (2) 5.4VA (2)

12.7VA (2) 12.7VA (2)
35VA (2) 35 W (2)

60 Hz 138VA (2) 19VA (2)
15.6VA (2) 5.5VA (2)

50 Hz 132VA (2) 19.3VA (2)
15VA (2) 5.4VA (2)

12.7VA (2) 12.7VA (2)

60 Hz 138VA (2) 19VA (2)
15.6VA (2) 5.5VA (2)

--

--

Reset Time

PT ­ PKT

75 ms

75 ms

--

Minimum Pulse

PLL­PKLL

75 ms

75 ms

--

Mechanical

Operating Time

Pickup Dropout

AC ­ 10...20 ms / DC ­ 30...50 ms AC ­ 10...20 ms / DC ­ 20...33 ms

AC ­ 10...20 ms / DC ­ 30...50 ms AC ­ 10...20 ms / DC ­ 20...33 ms

AC ­ 10...20 ms / DC ­ 30...50 ms AC ­ 10...20 ms / DC ­ 20...33 ms

Mechanical Life

10 million operations

Construction

Contact Arrangement

Up to 12 Poles, Convertible to N.O. or N.C. (8 N.C. Maximum)

Up to 6 Poles, Convertible to N.O. or N.C. (4 N.C. Maximum)

Contact Material

Silver Nickel

Silver Cadmium Oxide

Silver Cadmium Oxide

Mounting

Panel, Strip Mount, or DIN Rail Horizontal Mounting Recommended

Temperature

Operating (1) Storage

­20...+65 °C (­4...+149 °F) ­40...+65 °C (­40...+149 °F)

Environmental ­20...+65 °C (­4...+149 °F) ­40...+65 °C (­40...+149 °F)

­20...+65 °C (­4...+149 °F) ­40...+65 °C (­40...+149 °F)

Wire Terminations

Wire size per UL/CSA

#18 AWG...(2) #12 AWG

Tightening Torque

8...12 lb·in (0.9...1.4 N·m)

Standards Compliance

UL 508, CSA C22.2, No. 14, EN/IEC 60947-1, -5-1

Certifications

cULus Listed (File No. E14840, Guide NKCR/NKCR7), CE Marked, ABS

(1) Temperature inside the panel. (2) Average value for all coils within range. For values on a specific coil voltage, contact your local Rockwell Automation sales office or Allen-Bradley distributor.

164

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

International Symbol for Mechanically Linked Contacts

Dimensions - 700-P Relays with standard, master contact, or heavy-duty contact cartridge
Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.

103.43 (4-5/64)

-- 171.68 (6-49/64)

1/2
2.77 (7/64)
2- and 4-pole 700-P Relay Approx Shipping Weight: AC ­ 0.68 kg (1.5 lb), DC ­ 1.34 kg (2.95 lb)
AC 136.75 (5-25/64)

2.77 (7/64)
2- and 4-pole 700-P with Pneumatic Time Delay Attachment Approx Shipping Weight: AC ­ 0.85 kg (1.88 lb), DC ­ 1.5 kg (3.33 lb)
171.68 (6-49/64)

2.77 (7/64)
6- and 8-pole 700-P Relay with one -PB adder deck Approx Shipping Weight: AC ­ 0.79 kg (1.75 lb), DC ­ 1.45 kg (3.20 lb)
AC 136.75 (5-25/64)

2.77 (7/64)
700-P Relay with Mechanical Latch Attachment Approx Shipping Weight: AC ­ 0.97 kg (2.13 lb), DC ­ 1.62 kg (3.58 lb)
Cat. No. 700

2.77 (7/64)
700-P Relay, up to 12 poles with -PB and -PC adder decks Approx Shipping Weight: AC ­ 1.02 kg (2.25 lb), DC ­ 1.68 kg (3.7 lb)

#8 Screws (Captive)
Relay Rail for 700-P, -N, -NM, -R, -RM, -RT, -RTA Relays Secure the mounting strip with two screws at each end relay position. Use a minimum of one screw at the 3rd, 5th, 7th, etc., relay positions.
Alternate between upper and lower horizontal slots.

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

165

Relay and Timer Specifications
178.60 (7-1/32)

Cat. No. 700-N31, Type 1 Enclosure for 700-P, -RTC Relays
Approximate Shipping Weight: 1.26 kg (2.8 lb)

5.2 (13/64)

50 (1-63/64)
1000 (39-3/8)

6.2

12.5

(15/64)

(1/2)

1.0 (0.04)
35.0 (1.38)
7.5 (0.3)

27.0 (1.06)

Cat. No. 199-DR1 DIN Mounting Rail Series B Cat. No. 199-DR4 DIN Mounting Rail Series B Has No Mounting Holes

AC ­ 170.49 (6-23/32) DC ­ 187 (7-25/64)
700-PS Timer
700-PS Timer Mounted on a 700-P Relay Approximate Shipping Weight: AC ­ 0.68 kg (1.5 lb) without 700-PS,
DC ­ 1.34 kg (2.9 lb) without 700-PS

3.98 (0.16)

2.25

0.5

(0.09)

(.02)

0.5 (.02)

DIN Rail Adapter

166

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

700S-P and 700S-PK -- Heavy-Duty Safety Control Relays
· Mechanically linked contacts meet IEC 947-5-1-L · 2...12 poles ­ all mechanically linked · Red cover for easy identification of safety circuits · Tamper resistant cover helps prevent changes which could jeopardize safety · IEC mechanically linked contacts symbol displayed on front · Visual indication of contact state · Ideal for use in safety circuits

700S-P (10 A) Safety Control Relays -- AC and DC Coil Voltages

Contacts

AC Coils

24V DC Coils

Open Type Panel Mount Relay Rail Mount Open Type Panel Mount Relay Rail Mount

Open Type DIN Rail Mount

N.O.

N.C.

Cat. No.

3

1

700S-P310

2

2

700S-P220

7

1

700S-P710

6

2

700S-P620

5

3

700S-P530

4

4

700S-P440

3

5

700S-P350

10

2

700S-P1020

Cat. No.
700S-DCP310Z24 700S-DCP220Z24 700S-DCP710Z24 700S-DCP620Z24 700S-DCP530Z24 700S-DCP440Z24 700S-DCP350Z24 700S-DCP1020Z24

Cat. No.
700S-DCP310DZ24 700S-DCP220DZ24 700S-DCP710DZ24 700S-DCP620DZ24 700S-DCP530DZ24 700S-DCP440DZ24 700S-DCP350DZ24 700S-DCP1020DZ24

AC Coil Voltage Code(1)

The Cat. No. as listed is incomplete. Select a coil voltage code from the table below to complete the Cat. No. Example: Cat. No. 700S-P310 becomes Cat. No. 700S-P310A1 for a 120V AC coil.

[V]

24

60 Hz

A24

115-120 A1

230-240 A2

460-480 A4

IEC 947-5-1 Annex L has 2 requirements for a relay to meet for mechanically linked contacts: 1.) If a N.O. contact welds, all the N.C. contacts will remain open and meet a 2500V impulse test. 2.) If a N.C. contact welds, all the N.O. contacts will remain open and meet a 2500V impulse test. 700S-P and 700S-DCP relays meet these requirements including the 2500V impulse test.
The relays shown on this page are shipped from the factory with the 700-CPS safety cartridge installed and cannot be converted to N.O. or N.C. in the Field.

(1) For other coil voltages, consult your local Rockwell Automation sales office or Allen-Bradley distributor.

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

167

Relay and Timer Specifications

700S-PK (20 A) Safety Control Relays

Contacts

N.O.

N.C.

7

1

6

2

5

3

4

4

3

5

10

2

3

1

7

1

6

2

5

3

4

4

3

5

10

2

3

1

Coil Voltage
110V AC 110V AC 110V AC 110V AC 110V AC 110V AC 110V AC 24V DC 24V DC 24V DC 24V DC 24V DC 24V DC 24V DC

Cat. No.
700S-PK710A1 700S-PK620A1 700S-PK530A1 700S-PK440A1 700S-PK350A1 700S-PK1020A1 700S-PK310A1 700S-DCPK710Z24 700S-DCPK620Z24 700S-DCPK530Z24 700S-DCPK440Z24 700S-DCPK350Z24 700S-DCPK1020Z24 700S-DCPK310Z24

168

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

Specifications - 700S-P Relays

Type

700S-P

Electrical

Contact Rating Continuous

10 A @ 600V AC 5 A @ 600V DC

AC Ratings Make/ Break
DC

NEMA A600 NEMA P600

Minimum Contact Switching Ratings

10V, 50 mA

Contacts in Series 24V

Volts DC

64V

125V

250V

500V

DC

1

Switching

Inductive Load

2

5 A

2.2 A

1.1 A

0.55 A

0.24 A

10 A

10 A

5 A

2 A

0.7 A

3

--

--

7 A

3 A

1.5 A

4

--

--

10 A

5 A

2.5 A

Contact Electrical Life-- Resistive Loads

1.5 million operations at 10A break at 120V AC 14 million operations at 1A break at 120V AC 6 million operations at 1A break at 24V DC

AC

Coil Voltage Range (1)

DC

85...110% 80...110%

Battery Charging

85...115%

Coil Consumption

50 Hz

60 Hz

Inrush AC
Sealed

132 VA 19.3 VA

138 VA 19 VA

Inrush DC
Sealed

12.7 W 12.7 W

Mechanical

Mechanically Linked Contacts

All contacts are mechanically linked per IEC 947- 5-1 annex L for 2 to 12 poles

Operating Time

Pickup Dropout

AC ­ 10...20 ms DC ­ 30...50 ms
AC ­ 10...20 ms DC ­ 20...33 ms

Mechanical Life

10 million operations

Construction

Contact Arrangement

2...12 Poles, Double Break Contacts N.O. or N.C. (8 N.C. Maximum)

Contact Material/Design

Silver Nickel/Bifurcated

Mounting

Panel mount or mount on 700-MP Relay or DIN Rail Horizontal Mounting Recommended

Environmental
Operating Temperature (2)

-20...+65 °C (-4...+149 °F)

Storage Temperature

-40...+65 °C (-40...+149 °F)

Wire Terminations

Wire size per UL/CSA

#18 AWG...(2) #12 AWG

Tightening Torque

8...12 lb·in (0.9...1.4 N·m)

Standards Compliance

UL 508, CSA C22.2, No. 14, EN/IEC 60947-1, -5-1

Certifications

cULus Listed (File No. E14840, Guide NKCR/NKCR7), CE Marked, ABS

(1) Coil voltage required for proper operation (percent of rated coil voltage). (2) Temperature inside the panel.

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

600V 0.2 A 0.5 A 1.0 A 1.5 A
169

Relay and Timer Specifications

Specifications - 700S-PK Relays

Type

700S-PK

Electrical

Contact Rating Continuous

20 A @ 600V AC 10 A @ 600V DC

AC Ratings Make/ Break
DC

NEMA A600 NEMA P600

Additional Contact Ratings for AC Single-Phase Loss

3 Hp @ 240V AC - N.O. 2 Hp @ 240V AC - N.O./N.C. 1 HP @ 120V AC - N.O./N.C. 20 A resistive heating to 600V AC 20 A Tungsten lighting load to 480V AC

DC Current Ratings Make/Break

Cartridge Cat. No. 700-CMS

Contacts in Series

Volts DC

24V

64V

125V

250V

500V

600V

DC

1

Switching

2

10 A

5 A

2.2 A

0.55 A

0.24 A

0.2 A

20 A

10 A

5 A

2 A

0.7 A

0.5 A

3

--

15 A

7 A

3 A

1.5 A

1.0 A

4

--

20 A

10 A

5 A

2.5 A

1.5 A

AC

Coil Voltage Range (1)

DC

85...110% 80...110%

Battery Charging

85...115%

Coil Consumption

50 Hz

60 Hz

Inrush
AC Sealed

132 VA 19.3 VA

138 VA 19 VA

Inrush DC
Sealed

12.7 W 12.7 W

Mechanical

Mechanically Linked Contacts

All contacts are mechanically linked per IEC 947-5-1 annex L for 2 to 12 poles

Operating Time

Pickup Dropout

AC ­ 10...20 ms, DC ­ 30...50 ms AC ­ 10...20 ms, DC ­ 20...33 ms

Construction

Contact Arrangement Contact Material/Design Mechanical (Mechanically-Linked Contacts)

2...12 Poles, Double Break Contacts N.O. or N.C. (8 N.C. Maximum) Silver Cadmium Oxide
All contacts, are mechanically linked per IEC 947-5-1 Annex L for 2 to 12 poles

Mounting

Panel mount or strip mount recommended

Environmental Operating Temperature (2)
Storage Temperature

-20...+65 °C (-4...+149 °F) -40...+65 °C (-40...+149 °F)

Wire Terminations

Wire size per UL/CSA Tightening Torque
Standards Compliance

UL 508, CSA C22.2, No. 14, EN/IEC 60947-1, -5-1

#18 AWG...(2) #12 AWG 8...12 lb·in (0.9...1.4 N·m)

Certifications

cULus Listed (File No. E14840, Guide NKCR/NKCR7), CE Marked, ABS

(1) Coil voltage required for proper operation (percent of rated coil voltage). (2) Temperature inside the panel.

170

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

Dimensions - 700S-P Relays
Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.

103.43 (4-5/64)

AC 136.75 (5-25/64)

1/2
2.77 (7/64)
2- and 4-pole 700S-P Relay Approximate Shipping Weight: AC ­ 0.68 kg (1.5 lb), DC ­ 1.34 kg (2.95 lb)
170.10 (6-45/64)

2.77 (7/64)
6- and 8-pole 700S-P Relay Approximate Shipping Weight: AC ­ 0.79 kg (1.75 lb), DC ­ 1.45 kg (3.20 lb)
Cat. No. 700

2.77 (7/64)
10- and 12-pole 700S-P (Captive) Approximate Shipping Weight: AC ­ 1.02 kg (2.25 lb), DC ­ 1.68 kg (3.7 lb)

5.2 (13/64)

50 (1-63/64)

6.2

12.5

(15/64)

(1/2)

1000 (39-3/8)
DIN Rail

1.0 (0.04)
35.0 (1.38)
7.5 (0.3)

27.0 (1.06)

Relay Rail

#8 Screws (Captive)

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

171

Relay and Timer Specifications

700-N Industrial Relays
· Contact cartridges convertible from N.O. to N.C. and vice versa · NEMA A300 AC · 24...250V AC coils · Pneumatic timing unit · Solid-state timing unit · Overlap contacts · Logic reed contacts · 4-...8-pole

AC-Operated Relays
Photo

Contacts

N.O.

N.C.

Contact Arrangement

4

--

Open Type Cat. No.
700-N400

Type NM Relay 2 Poles§

2

--

700-NM200

 AC Coil Voltage Code

The Cat. No. as listed is incomplete. Select a coil voltage code from the table below to complete the cat. no. Example: Cat. No. 700-N200 becomes Cat. No. 700-N200A24 for 24V 60 Hz. For other coil voltages, contact your local Rockwell Automation sales office or Allen-Bradley distributor.

[V]
50 Hz 60 Hz

24
-- A24

110
A1 --

120
-- A1

208
-- A20

220
A2 --

240
-- A2

IMPORTANT

· NORMALLY CLOSED CONTACTS: Listed relays are supplied with all contacts normally open. These contacts can be readily converted to normally closed in the field.
· OVERLAP CONTACTS: Overlap contacts (normally open contact closes before the normally closed contact opens) can be supplied. See for information on kits for field installation of overlap contact cartridges.
· Location of contacts in 2-pole relays
· Permanent Magnet Latch AC Relay. Minimum Operating Time - Type NM - For reliable operation, power to the latch circuit must be maintained for a minimum time of 75 milliseconds and power to the unlatch circuit must be maintained for minimum time of 50 milliseconds.

172

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Operating Coils

Photo

Coil Voltage
24 110 120 208 220 240

700-NT Pneumatic Timing Unit

Photo

Description
Timing Unit Only (for 700-N, 2...4-pole)

Relay and Timer Specifications

700-N Relay · 2-...8-Pole 60 Hz 84AB27 84AB01 84AB86 84AB113 84AB06 84AB83

50 Hz 84AB28 84AB86 -- -- 84AB83 --

Timed Contacts

Contact Arrangement

Open Type

N.O.

N.C.

ON-Delay mode is

1

1

standard. Timer is easily converted to

OFF-Delay mode.

Cat. No. 700-NT

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

173

Relay and Timer Specifications

Specifications - 700-N Relays

Attribute

Electrical Ratings

Rated Thermal Current Ith Rated Insulation Voltage

Contact Rating

Coil Voltage Range

AC

DC

Coil Consumption

AC Mechanical

Inrush Sealed

Max. Operating Time
Timing Range Repeat Accuracy Reset Time Timing Mode

Pickup Drop Out

Construction

Contact Arrangement

Contact Material

Mounting

Environmental

Ambient Temperature (Outside Enclosure)

Operating Storage

Operating Temperature Rise (Inside Enclosure)

Wire Terminations

Wire size per UL/CSA

Tightening Torque

Standards Compliance

Certifications

Bul. 700-N

Bul. 700-NT

10 A

300V

10 A @ 300V AC, NEMA A300

85...110%

--

80...110%

--

50 Hz

60 Hz

--

120 VA

133 VA

--

24 VA

20 VA

--

AC 14 ms 13 ms -- -- --
--

-- -- -- 0.2...60 s ±15% of setting 75 ms On-Delay -- convertible to OFF Delay, up to 2 poles convertible to N.O. or N.C.

Up to 8 Poles, Convertible to N.O. or N.C. Silver
Panel or strip mount Horizontal mounting recommended

-- Silver On relay only

­20...+40 °C (­4...+104 °F)

­40...+60 °C (­40...+140 °F)

+25 °C Max

--

#18 AWG...(2) #12 AWG 8...12 lb·in. (0.9...1.4 N·m)
UL 508, CSA C22.2, No. 14 cULus Listed (File No. E14840, Guide NKCR/NKCR7)

174

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

Dimensions - 700-N Relays
Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.

Type of Relay
700 N
700
N with Pneumatic 700
Timer N
with Solid-State 700 Timer

No. of Poles
Drawing Number

Open Type Without Enclosure

A

B

C

Wide High Deep

Approx

Type 1

. Ship.

General Purpose Enclosure

Wt. kg

D

(lbs.)

A

B

C

D

Wide High Deep

Approx

. Ship.

Wt. kg

E

(lbs.)

2...4

1

57.15 (2-1/4)

88.90 (3-1/2)

82.55 (3-1/4)

79.38 (3-1/8)

0.68 (1-1/2)

107.95 (4-1/4)

185.74 (7-5/ 16)

103.19 (4-1/ 16)

146.05 (5-3/4)

85.73 (3-3/8)

1.59 (3-1/2)

6...8

2

57.15 (2-1/4)

88.90 (3-1/2)

106.36 (4-3/ 16)

79.38 (3-1/8)

0.79 (1-3/4)

112.71 (4-7/ 16)

228.60 (9)

120.65 (4-3/4)

206.38 (8-1/8)

92.08 (3-5/8)

2.27 (5)

2...4

3

57.15 (2-1/4)

88.90 (3-1/2)

138.11 (5-7/ 16)

79.38 (3-1/8)

0.91 (2)

--

--

--

--

--

--

2...4

3

57.15 (2-1/4)

88.90 (3-1/2)

160.34 (6-5/ 16)

79.38 (3-1/8)

1.02 (2-1/4)

--

--

--

--

--

--

C

A

C

A

C

A

DB

DB

DB

Drawing Number 1
178.60 (7-1/32)

Drawing Number 2

Cat. No. 700

Drawing Number 3

5.2 (13/64)

50 (1-63/64)
1000 (39-3/8)

6.2 (15/64)

12.5 (1/2)

#8 Screws (Captive)

1.0 (0.04)
35.0 (1.38)
7.5 (0.3)

27.0 (1.06)

3.98 (0.16)

2.25

0.5

(0.09)

(.02)

0.5 (.02)

DIN Rail Adapter

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

175

Relay and Timer Specifications

700-R Sealed Switch Relays

· Sealed contacts · Extremely long mechanical and electrical life · Hazardous locations Class 1, Div 2 Groups A, B, C, D · Harsh environments · Suitable for applications with shock and vibration · High reliability circuit integrity

Electrically Held No.

of

Contacts

Contact Arrangement

Poles

and Markings

N.O. N.C.

0

0

0

Relay without Contact

2

0

2

1

1

0

2

4

0

3

1

4

2

2

1

3

0

4

6

0

5

1

4

2

6

3

3

2

4

1

5

0

6

8

0

7

1

6

2

5

3

8

4

4

3

5

2

6

1

7

0

8

 Arrangement displays all N.O. contacts.  Location of contacts in 6-pole relays.  Polarity must be observed for DC voltage (700 DC) relays.
 Location of contacts in 2-pole relays.

AC-Operated Relay Only Open Type Cat. No. 700-R000 700-R200 700-R110 700-R020 700-R400 700-R310 700-R220 700-R130 700-R040 700-R600  700-R510  700-R420  700-R330  700-R240  700-R150  700-R060  700-R800  700-R710  700-R620  700-R530  700-R440  700-R350  700-R260  700-R170  700-R080 

DC-Operated Relay Only Open Type Cat. No. 700DC-R000 700DC-R200 700DC-R110 700DC-R020 700DC-R400 700DC-R310 700DC-R220 700DC-R130 700DC-R040 700DC-R600  700DC-R510  700DC-R420  700DC-R330  700DC-R240  700DC-R150  700DC-R060  700DC-R800  700DC-R710  700DC-R620  700DC-R530  700DC-R440  700DC-R350  700DC-R260  700DC-R170 700DC-R080 

Coil Voltage Code

The Cat. No. as listed is incomplete. Select a voltage code from the table below to complete the Cat. No. Example: Cat. No. 700-R000 becomes Cat. No. 700-R000A24.

Type of Relay AC DC

[V] 25, 50, 60 Hz --

Coil Volts

24

48

110

115-125 120

220

230-250 240

--

--

A1

--

--

A2

--

--

A24

--

--

--

A1

--

--

A2

Z24

Z48

--

Z1

--

--

Z2

--

176

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Accessories - 700-R Relays
Photo

Relay and Timer Specifications

Description

Relay Rail Simplifies panel layout. These indexed strips are easily cut to the required length and bolted, riveted, or spot-welded in place. Relays are installed adjacent to one another on the mounting strip with the captive mounting screws provided. Rows of relays on Relay Rail form their own wiring trough. Can be used with the following relays: 700P, 700DC-P, 700S-P, 700N, 700-R, 700-RTC

4 Relays per Strip 8 Relays per Strip 12 Relays per Strip
16 Relays per Strip

DIN (#3) symmetrical hat rail 35 x 7.5 x 1 m

Pkg. Qty.

Cat. No.

5

700-MP4

5

700-MP8

5

700-MP12

5

700-MP16

10 199-DR1

DIN Rail Adapter Can be used with the following relays: 700-P, 700DC-P, 700S-P, 700-N, 700-R, 700-RTC

1

700-DRA

Front Deck A front deck can be attached to 700 2-, 3-, or 4pole AC and DC Type R relays.

Front Deck with one N.O. Contact Cartridge (700-R Relay)

1

Front Deck with one N.C. Contact Cartridge (700-R Relay)

1

Front Deck with one N.O. Contact Cartridge (700-RM Relay)

1

Front Deck with one N.C. Contact Cartridge (700-RM Relay)

1

Contact Cartridges

N.O. Contact Cartridge - Green

These cartridges are used to increase the number (700-R Relay)

1

of poles of a relay. A dummy cartridge is also

available to fill empty space not occupied by a contact cartridge.

N.C. Contact Cartridge - Yellow (700-R Relay)

1

700-RA10 700-RA01 700-RB10 700-RB01 700-CR5 700-CR6

Cat. No. 700-CR5

Cat. No. 700-CR6

Cat. No. 700-CR9

"DUMMY"Cartridge - Black (700-R Relay)

1

Surge Suppressor

12V DC (700-R Relay)

1

When the circuit to a DC operating coil is opened, 24V DC (700-R Relay)

1

the inductive energy stored in the coil can

generate very high transient voltages. With the 48V DC (700-R Relay)

1

addition of the appropriate surge suppressor, the stored energy is absorbed and dissipated

115...125V DC (700-R Relay)

1

limiting the voltage spikes. A surge suppressor is

not required with AC 700-R relays because the AC

operating coil transients are suppressed by a full 230...250V DC (700-R Relay) 1

wave rectifier connected to the coil.

700-CR9
199-FSMA9 199-FSMA10 199-FSMA11

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

177

Relay and Timer Specifications

Specifications - 700-R
Application Data ­ Because of the inherent characteristics of this device, the normally open contacts may close before the normally closed contacts open on energization and the normally closed contacts may close before the normally open contacts open on de-energization.
Ratings

NEMA Rating Designation

Voltage

AC Voltage Make

120V

30

B300 Up to 300V AC

240V

15

480V

3.75

C600 Above 300V AC

600V

3.0

Maximum Allowable Off-State Leakage Current

Break
3 1.5 0.375 0.30

Continuous NEMA Rating Carrying Designation Current [A]

DC Voltage Volts DC Make/Break

Continuous Carrying Current [A]

5

46...300

138 VA

5

NEMA P300

2.5

5...46

3 A

5

24V DC 24V AC 120V AC
Relay Data

Voltage

Maximum Off-State Leakage Current [mA] Type R 23 23 5

Type Contact Arrangement Contact Material

Coil Voltage Range

Coil Power

Sealed Voltage Range: ­15... +10%
Inrush

Pickup Time Dropout Time Operating Temperature Mounting Haz. Loc. Ratings
Standards Compliance Certifications

700-R
Up to 8 poles, available in any combination of N.O. or N.C. contacts
W (tungsten in a controlled gas atmosphere) 24...250V AC 24...250V DC 5.5 VA, 50/60 Hz 5.5 W DC 5.5 VA, 50/60 Hz 5.5 W DC 30 ms
30 ms ­40...+60 °C (­40...+140 °F)
Panel mount
Class I, Division 2, Groups A, B, C, and D ISA 12.12, CSA C22.2, No. 213, EN/IEC 60947-1, -5-1 cULus Listed (File No. E10314, Guide NOIV/NOIV7), CE Marked

178

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

700-R Operating Coils

Coil Volts
24 48 110 115...125 120 208 220 240 230...250

60 Hz 77AB27 77AB134 77AB86
-- 77AB86
-- 77AB83 77AB83
--

700-R 2-...8-Pole AC

50 Hz 77AB27 77AB134 77AB86
-- 77AB86
-- 77AB83 77AB83
--

700-R 2-...8-Pole DC
77D152 77D166
-- 77D155
-- -- -- -- 77D156

Dimensions - 700-R

Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.

Type of Relay

R

700 and 700DC

No. of Poles
2...4 5...8

Drawing Number
1
2

700-R Relays

Open Type Without Enclosures

A

B

C

D

Wide High Deep

55.56 (2-3/ 16)

88.90 (3-1/2)

92.25 (3-3/8)

79.38 (3-1/8)

55.56 (2-3/ 16)

88.90 (3-1/2)

111.13 (4-3/8)

79.38 (3-1/8)

Approx . Ship Wt. [kg (lb)]
0.91 (2)
1.02 (2-1/4)

A Wide
104.78 (4-1/8)
112.71 (4-7/ 16)

Type 1 General Purpose Enclosure

B

C

D

High Deep

185.74 (7-5/ 16)

103.19 (4-1/ 16)

146.05 (5-3/4)

228.60 120.65 206.38 (9) (4-3/4) (8-1/8)

Approx . Ship E Wt. [kg (lb)]
85.73 1.81 (3-3/8) (4)
92.08 2.49 (3-5/8) (5)

C

A

C

A

B

D

B

D

700-R400...

A

C

D

B

E Type 1 Enclosure

700-R800...

3.98 (0.16)

2.25

0.5

(0.09)

(.02)

0.5 (.02)

DIN Rail Adapter

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

179

Relay and Timer Specifications

Cat. No. 700

#8 Screws (Captive)
Relay Rail

Secure the mounting strip with 2 screws at each end relay position. Use a minimum of one screw at the 3rd, 5th, 7th, etc., relay positions. Alternate between upper and lower horizontal slots.

5.2 (13/64)

50 (1-63/64)

6.2

12.5

(15/64)

(1/2)

1.0 (0.04)
35.0 (1.38)

27.0 (1.06)

1000

7.5

(39-3/8)

(0.3)

Cat. No. 199-DR1 DIN Mounting Rail Series B

180

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

700-RTC -- Solid-State Timing Relay

· Timing functions · 8 ON-delay · 8 OFF-delay · Timing ranges · Seconds: 0.05...2, 0.2...8, 0.4...30, 2...120 · Minutes: 0.015...1, 0.06...4, 0.25...16 and 1...64 · AC, 50/60 Hz or DC · 600V AC maximum · 300V DC maximum · Relays with fixed time delay · Sealed contacts · Harsh environments · Hazardous locations Class I, Div. 2, Groups A, B, C and D
700-RTC Relay with Adjustable Time Delay ­ Relays with Provision for Instantaneous Contacts
Relays listed below have slots for two timed contacts and two instantaneous contacts. Unused slots are equipped with removable dummy cartridges.

Number of Contact Cartridges

Instantaneous

Total

N.O.

N.C.

0

0

0

1

0

0

0

0

0

0

1

0

0

1

2

0

0

1

0

0

1

0

0

1

0

2

0

0

1

1

1

1

0

3

2

0

0

2

0

1

1

1

1

0

0

2

0

1

Timed

N.O.

N.C.

0

0

1

0

0

1

2

0

1

0

1

0

1

1

0

1

0

1

0

2

2

0

1

0

2

0

1

0

1

1

0

1

1

0

1

1

0

1

0

2

0

1

0

2

Open Type Without Enclosure
Cat. No.
700-RTC00000
700-RTC00100 700-RTC00010 700-RTC00200 700-RTC10100 700-RTC01100 700-RTC00110 700-RTC10010 700-RTC01010 700-RTC00020 700-RTC10200 700-RTC20100 700-RTC01200 700-RTC11100 700-RTC10110 700-RTC20010 700-RTC02100 700-RTC01110 700-RTC11010 700-RTC10020 700-RTC02010 700-RTC01020

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

181

Relay and Timer Specifications

Number of Contact Cartridges

Instantaneous

Total

N.O.

N.C.

2

0

1

1

2

0

0

2

4

1

1

2

0

1

1

0

2

0

2

 Coil Voltage Code

Timed

N.O.

N.C.

2

0

2

0

1

1

2

0

1

1

0

2

0

2

1

1

0

2

Open Type Without Enclosure
Cat. No.
700-RTC20200 700-RTC11200 700-RTC20110 700-RTC02200 700-RTC11110 700-RTC20020 700-RTC11020 700-RTC02110 700-RTC02020

The Cat. No. as listed is not complete. Select a voltage code from the table below to complete the Cat. No. Example: Cat. No. 700-RTC00100 becomes Cat. No. 700-RTC00100U24. For other voltages consult your local Rockwell Automation sales office or Allen-Bradley distributor.

[V] 50/60 Hz

24V DC, 24V AC U24

120V DC, 110/120V AC U1

700-RTC Relays with Fixed Time Delay-- Relays with Provision for Instantaneous Contacts

Relays listed below have slots for two timed and two instantaneous contacts. Unused slots are equipped with removable dummy cartridges.

Number of Contact Cartridges

Timed

Total

N.O.

N.C.

0

0

0

1

1

0

0

1

2

0

1

0

1

0

2

1

1

0

1

0

1

0

2

2

0

1

0

2

0

1

0

1

1

3

0

1

1

0

1

1

0

1

0

2

0

1

0

2

Instantaneous

N.O.

N.C.

0

0

0

0

0

0

0

0

1

0

0

1

0

0

1

0

0

1

0

0

1

0

2

0

0

1

1

1

1

0

2

0

0

2

0

1

1

1

1

0

0

2

0

1

Open Type Without Enclosure
Cat. No.
700-RTC00#0 700-RTC10#0 700-RTC20#0 700-RTC40#0 700-RTC11#0 700-RTC12#0 700-RTC30#0 700-RTC21#0 700-RTC22#0 700-RTC50#0 700-RTC41#0 700-RTC14#0 700-RTC42#0 700-RTC13#0 700-RTC31#0 700-RTC24#0 700-RTC15#0 700-RTC32#0 700-RTC23#0 700-RTC51#0 700-RTC25#0 700-RTC52#0

182

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

Number of Contact Cartridges

Timed

Total

N.O.

N.C.

2

0

2

0

1

1

2

0

4

1

1

0

2

1

1

0

2

0

2

# Operating Mode

Instantaneous

N.O.

N.C.

2

0

1

1

2

0

0

2

1

1

2

0

0

2

1

1

0

2

Open Type Without Enclosure
Cat. No.
700-RTC44#0 700-RTC43#0 700-RTC34#0 700-RTC45#0 700-RTC33#0 700-RTC54#0 700-RTC35#0 700-RTC53#0 700-RTC55#0

Replace the # in the cat. no. with the appropriate letter and numbers to indicate the operating mode and the fixed time delay value. Refer to operating mode table below.

Digit Operating Mode

S

On-Delay ­ s

Z

Off-Delay ­ s

Y

On-Delay ­ Min.

I

Off-Delay ­ Min.

Fixed Time Delay
Seconds ­Two digits indicating the fixed time delay in seconds. Three digits indicating the fixed time delay (first digit indicates seconds, next two digits indicate 1/100 seconds).
Minutes ­Two digits indicating the fixed time delay in minutes. Three digits indicating the fixed time delay (first digit indicates minutes, next two digits indicate 1/100 minutes).

EXAMPLE

Cat. No. 700-RTC00Y200U1 is for a relay without contact cartridges."Y20"indicates an On-Delay timer with a 20 minute fixed time delay. This is a"standard relay."Order the contact cartridges separately.
Cat. No. 700-RTC42S020U1 is for a relay with 2 N.O. cartridges in the timed position and 1 N.C. cartridge in the instantaneous position. "S02" indicates an On-Delay timer with a 2 second fixed time delay.

Coil Voltage Code

The cat. no. as listed is not complete. To complete the cat. no., add a coil code selected from the table below.

[V] 50/60 Hz

24V DC, 24V AC U24

120V DC, 110/120V AC U1

Accessories - 700-RTC Relays
Photo

Cat. No. 700-CRT5

Cat. No. 700-CRT6

Cat. No. 700-CR9

Description

Cartridge Type Color

N.O.

Grey

Contact Cartridges ­ These cartridges are used to add contacts

to timing relays having unused slots. The N.O., N.C., and Dummy

cartridges are interchangeable and can be used in timed or

N.C.

instantaneous contact slots. Dummy cartridges should be placed in

unused cartridge slots to guard against entrance of foreign

material.

Orange

Dummy Cartridge Black

Cat. No. 700-CRT5 700-CRT6
700-CR9

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

183

Relay and Timer Specifications Photo

Description

Cartridge Type Color

Cat. No.

Type 1 Enclosure -- Use for all 700-P relays except 10- and 12-pole DC relays or 6-pole DC 700-PH relays.

700-N31

Relay Rail Simplifies panel layout. These indexed strips are easily cut to the required length and bolted, riveted, or spot-welded in place. Relays are installed adjacent to one another on the mounting strip with the captive mounting screws provided. Rows of relays on Relay Rail form their own wiring trough. Can be used with the following relays: 700P, 700DC-P, 700S-P, 700N, 700-R, 700-RTC

Relays per Strip 4 8 12 16

Pkg. Quantity
700-MP4 5

5

700-MP8

5

700-MP12

5

700-MP16

DIN (#3) symmetrical hat rail 35 x 7.5 x 1 m

10

199-DR1

DIN Rail Adapter Can be used with the following relays: 700-P, 700DC-P, 700S-P, 700-N, 700-R, 700-RTC

1

700-DRA

Specifications - 700-RTC Relays

Voltage and Power Requirements

AC Voltage +10% ­15% 50/60 Hz
24V AC
110/120V AC

Total Power Required
8 VA 9 VA

Initiate Terminal Power
4 VA 4 VA

Maximum Allowable Leakage Current
10 mA
2.4 mA

Coil Code
U24 U1

DC Voltage +10% ­20%
24V DC
120V DC

Total Power Required
10 W 11 W

Initiate Terminal Power
5 W 5 W

Maximum Allowable Leakage Current
10 mA
2.4 mA

Coil Code
U24 U1

Type Contact Rating
Contact Arrangement Contact Material Operating Mode

700-RTC
NEMA B600 600V AC, 5 A NEMA P300 300V DC, 5 A
1...4 poles. Max. of 2 timed and 2 instantaneous. Available in any combination of N.O. and N.C. contacts
W (tungsten in a controlled gas atmosphere)
Convertible to ON-Delay or OFF-Delay

184

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

Type

700-RTC

Timing Range

0.015...64 minutes; 0.05...120 seconds

Reset Time

25 ms

Repeat Accuracy

±1% (or ±50 ms) at constant voltage and temperature

Mounting

Panel or strip mount

Surge Suppression

Not required. Timers have internal suppression

Haz. Loc. Ratings

Class I, Division 2, Groups A, B, C, and D

Maximum Allowable Leakage Current Ambient Temperature (1)

24V AC/DC
110/120V AC, 120V DC

10 mA 2.4 mA

Operating:

­20...+60 °C (­4...+140 °F)

Storage:

­20...+60 °C (­4...+140 °F)

Standards Compliance

ISA 12.12, CSA C22.2, No. 213

Certifications

cULus Listed (File No. E10314, Guide NOIV/NOIV7)

(1) Continuous duty units placed close to each other (3 in a row) have a temperature range of ­20...+45 °C (­4...+113 °F) or should have air circulated around the units. Approximate space of 3/4 in (mm) on all sides is needed.

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

185

Relay and Timer Specifications

Typical Wiring Diagram - 700-RTC Relays

External L1 Initiating Contact
(N.O. or N.C.)
Timed Contacts Any Combination of N.O. and N.C.

L2 P TIMED INST

Instantaneous Contacts Any Combination of N.O. and N.C.

L1 +

L2

Dimensions - 700-RTC Relays
Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.

5.2 (2-13/64) Dia. Mounting Holes
Approximate Shipping Weight 0.92 kg (2.1 lb.)

NEMA Type 1 Enclosure for RTC Relays Approximate Shipping Weight 1.26 kg (2.8 lb.)

186

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

IEC Control Relays
Product Overview

Relay and Timer Specifications

Bulletin No.

700-CF and 700S-CF

Type

Control Relay

Features

· Mechanically linked contacts · Timer and latch operations · Switch up to 690V AC and DC · 700S-CF for safety circuits

Contact Form

4...12 poles, double break

Contact Type

Cross stamp or bifurcated

Contact Material

Silver, gold

Electrical

Max. Current AC Resistive

20 A (relay) 10 A (adder deck)

Min. load

17V, 10 mA (Silver) 5V, 3 mA (Gold)

Coil Voltage

12...600V AC 9...250V DC

Coil Voltage Pickup

85...110% AC coils, 80...110% DC coils

Dielectric Withstand 2.5 kV

Electric Service Life (cycles)

1.2 million at 10 A

Certifications

CE, cULus, CCC

Sockets

DIN Rail or panel mount

Page

188

700-EF and 700S-EF Control Relay · Mechanically linked contacts · Timer and latch operations · Switch up to 690V AC and DC · 700S-EF for safety circuits 4...8 poles -- Silver
16 A (relay) 16 A (adder deck)
12V, 3 mA (Silver)
24...500V AC 12...500V DC 85...110% AC coils, 80...110% DC coils 2.5 kV
1.2 million at 6 A
CE, cULus, CCC DIN Rail or panel mount 188

700-K Miniature Control Relay · Smallest size · Long life · Low power consumption · Switch up to 690V AC and DC 4...8 Poles Double Break Bifurcated Silver
10 A
15V, 2 mA (700-K)
12...600V AC 9...250V DC 85...110% AC Coils, 80...110% DC Coils 2640V
800K at 10 A 120V AC
CE, cULus, CCC DIN Rail or panel mount 225

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

187

Relay and Timer Specifications

700-CF Control Relay
· IEC industrial relays · Mechanically linked contact performance per IEC 60947-5-1 · Gold plated, bifurcated version for low level switching applications · Master control relay version rated 15 A (AC-15) · Solid-state and pneumatic timing modules · 4-...10 Poles

4-Pole AC Coil Voltage (Ratings for 700-CF Only)

AC-12

AC-15

Ith [A]

Ie [A]

Connection Diagrams

40 °C 60 °C 24/48V 120V 240V 400V 500V 600V 690V

Contacts

Standard Contacts(1)

Gold Plated
Bifurcated Contacts(2)

Master Contacts(2)

N.O. N.C. Cat. No.

Cat. No.

Cat. No.

2 2 700-CF220 700-CFB220 700-CFM220

20 20 10

10 10 6 2.5 1 1

3 1 700-CF310 700-CFB310 700-CFM310 4 0 700-CF400 700-CFB400 700-CFM400

0 4 700-CF040 700-CFB040 --

(1) For spring clamp terminals, insert R after 700-C. Example: Cat. No. 700-CRF220D. (2) All Cat. Nos. are factory-stocked.
 ACoil Voltage Code

The cat. no. as listed is incomplete. Select a coil voltage code from the table below to complete the cat. no. Example: Cat. No. 700-CF220 becomes Cat. No. 700-CF220D for 120V, 60 Hz.

[V]

12

24

32

36

42

48

100

100... 110

110

120

127

200

200... 220

208

208... 240

220... 230

230

230... 240

240

50 Hz R K V W X Y KP -- D P S KG L

---- F

-- VA T

60 Hz Q J -- V -- X -- KP -- D -- -- KG H L

-- ---- A

50/60 Hz

--

KJ

-- -- -- KY

KP

--

KD -- -- KG KL

-- -- KL

KF -- KA

[V]

277

347

380

380... 400

50 Hz

--

--

--

N

60 Hz

T

I

E

--

50/60 Hz --

--

--

--

400

400... 415

--

G

--

--

KN

--

440

480

500

550

600

B

--

M

C

--

N

B

--

--

C

KB

--

--

--

--

188

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

4-Pole DC Coil Voltage (Ratings for 700-CF Only)

AC-12

AC-15

Ith[A]

Ie [A]

Connection Diagrams

40 °C 60 °C 24/48V 120V 240V 400V 500V 600V 690V

Contacts

Standard Contacts(1)

Gold Plated
Bifurcated Contacts(2)

Master Contacts(2)

N.O. N.C. Cat. No.
2 2 700-CF220 

Cat. No.

Cat. No.

700-CFB220 700-CFM220

20 20 10

10 10 6 2.5 1 1

3 1 700-CF310 700-CFB310 700-CFM310

4 0 700-CF400 700-CFB400 700-CFM400

(1) For spring clamp terminals, insert R after 700-C. Example: Cat. No. 700-CRF220D. (2) All Cat. Nos. are factory-stocked.
 DC Coil Voltage Code

The cat. no. as listed is incomplete. Select a coil voltage code from the table below to complete the cat. no. example: Cat. No. 700-CF220 becomes Cat. No. 700-CF220EJ for 24V DC, electronic with diode.

[V]

9

12

24

36

48

48... 72

60

64

72

80

110

110... 125

115

125

220

220... 250

230

250

Electronic with diode

--

EQ

EJ

EW -- EY -- -- -- -- -- ED

-- -- -- EA

-- --

Electronic with diode/ Quick -- -- QJ Pick-up

------------------

-- -- -- --

-- --

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

189

Relay and Timer Specifications

6- and 8-pole Relays

Control Relays with Overlapping Side-Mounted Contacts

AC-12 Ith [A]

AC-15 Ie [A]

Left Relay

Contacts Right

Aux. Arrangement Aux.

Overlapping SideMounted Contacts

Cat. No.

40 60 24/ 120 240 400 500 600 690 °C °C 48V V V V V V V

N.O. N.C. N.O. N.C.

Main Relay

20 20 10 10 10 6 2.5 1 1

4 0 1 1 700-CFZ1510 3 1 1 1 700-CFZ1420

2 2 1 1 700-CFZ1330

Side Contacts

10 10 6

6 5 3 1.6 1 1

4 0 2 2 700-CFZ2620 3 1 2 2 700-CFZ2530

2 2 2 2 700-CFZ2440

190

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

Control Relays with Standard Side-mounted Contacts

AC-12

AC-15

Ith [A]

Ie [A]

Left

Aux.

40 60 24/ °C °C 48V

120V 240V 400V 500V 600V 690V

Relay Arrangement

Standard

Right Aux.

Contacts

SideMounted Contacts

Cat. No. (1)

N.O. N.C. N.O. N.C.

4

0

1

1

700CFZ0510

Main Relay

20 20 10

10 10 6 2.5 1 1

3

1

1

1

700CFZ0420

2

2

1

1

700CFZ0330

4

0

2

2

700CFZ0620

Side Contacts

10

10

6

6 5 3 1.6 1 1

3

1

2

2

700CFZ0530

2

2

2

2

700CFZ0440

(1) All Cat. Nos. are factory stocked.
 AC Coil Voltage Code

The cat. no. as listed is incomplete. Select a coil voltage code from the table below to complete the cat. no. Example: Cat. No. 700-CFZ051 becomes Cat. No. 700-CFZ0510F.

[V]

12

24

32

36

42

48

100

100... 110

110

120

127

200

200... 220

208

208... 240

220... 230

230

230... 240

240

50 Hz R K V W X Y KP -- D P S KG L

---- F

-- VA T

60 Hz Q J -- V -- X -- KP -- D -- -- KG H L

-- ---- A

50/60 Hz

--

KJ

-- -- -- KY

KP

--

KD -- -- KG KL

-- -- KL

KF -- KA

[V]

277

347

380

380... 400

50 Hz

--

--

--

N

60 Hz

T

I

E

--

50/60 Hz --

--

--

--

400

400... 415

--

G

--

--

KN

--

440

480

500

550

600

B

--

M

C

--

N

B

--

--

C

KB

--

--

--

--

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

191

Relay and Timer Specifications

Assignment of Contacts

Device Combinations in Accordance with IEC 60947-1 / -4-1

Auxiliary Contact Blocks Circuit Diagram

Control

FrontMounting (1)

100-FA02

51 61 52 62

100-FA11

53 61 54 62

100-FA20

53 63 54 64

100-FA22

53 61 71 83 54 62 72 84

100-FA31

53 61 73 83 54 62 74 84

100-FA40

53 63 73 83 54 64 74 84

100-FAL22

53 61 75 87

54 62 76 88

(1) Control relay and auxiliary contact block AC/DC max. 4 N. C.

AC/DC AC/DC AC/DC AC/DC AC/DC AC/DC AC/DC

Control Relays 700-CF (AC and DC Control)

700-CF220

700-CF310

700-CF400

22E + 02E = 24Y 22E + 11E = 33Y 22E + 20E = 42Y 22E + 22E = 44Y 22E + 31E = 53Y 22E + 40E = 62Y 22E + L22E = L44Y

31E + 02E = 33Y 31E + 11E = 42Y 31E + 20E = 51Y 31E + 22E = 53Y 31E + 31E = 62Y 31E + 40E = 71Y 31E + L22E = L53Y

40E + 02E = 42Y 40E + 11E = 51Y 40E + 20E = 60Y 40E + 22E = 62Y 40E + 31E = 71Y 40E + 40E = 80Y 40E + L22E = L62Y

192

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

Auxiliary Contacts

Photo

Description

N.O. N.C. Connection Diagrams

0

2

1

1

Auxiliary Contact Blocks for Front 2

0

Mounting§ 2- and 4-pole

1L 1L

Quick and easy mounting without tools 0

4

Electronic-compatible contacts down to

17V, 5 mA Mechanically linked performance

1

3

between N.O. and N.C. poles and to the 2

2

main relay poles (except for L types)

Models with equal function with several 3

1

terminal numbering choices 1L = Late break N.C./early make N.O.

4

0

Bifurcated version for switching down to

5V, 3 mA

1+1L 1+1L

For Use With

Standard Contacts (1)
Cat. No.

100-FA02

100-FA11

100-FA20

100-FAL11

100-FA04

100-FA13 700-CF 100-FA22

100-FA31

100-FA40

Bifurcated Contacts Cat. No. 100-FAB02 100-FAB11 100-FAB20 -- 100-FAB04 100-FAB13 100-FAB22 100-FAB31 100-FAB40

100-FAL22

--

(1) For spring clamp terminals, insert CR after 100-. Example: Cat. No. 100-CRFA02.

Photo Description

N.O. N.C. Connection Diagrams

0

1

1

0

0

2

1

1

Auxiliary Contact Blocks for Side Mounting without

2

0

Sequence Terminal Designations§

1- and 2-pole

Two-way numbering for right or left mounting on the contactor

Quick and easy mounting without tools

Electronic-compatible contacts down to 17V, 10 mA

Mirror contact performance to the main relay poles

1L = Late break N.C./early make N.O.

1L 1L

For Use With Cat. No. 100-SA01 100-SA10 100-SA02 100-SA11 100-SA20
700-CF
100-SAL11

IMPORTANT For maximum number of contacts, see the following tables.

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

193

Relay and Timer Specifications

700-CF (AC electronic coils), vertical mounting, 60 °C(1)

Cat. No. 700...

Max. N.O. Side Aux.

Max. N.C. Side Aux.

Max. N.O. Front Aux.

Max. N.C. Front Aux.

CF400

2

4

4

4

CF310

2

4 (2)

4

4(3)

CF220

4

4 (2)

4

2

CF040

2

2

4

0

(1) For other operating conditions, please contact your local Rockwell Automation sales office or Allen-Bradley distributor. (2) With no front auxiliary contacts installed. Otherwise 3 N.C. Maximum (3) With no side auxiliary contacts installed. Otherwise 3 N.C. Maximum

Max. N.O. Front + Side Aux.
6 6 8 6

Max. N.C. Front + Side Aux.
7 5 5 2

Max. N.O. + N.C. Front + Side Aux.
8 8 8 6

700-CF (DC conventional coils), vertical mounting, 60 °C(1)

Cat. No. 700...

Max. N.O. Side Aux.

Max. N.C. Side Aux.

Max. N.O. Front Aux.

Max. N.C. Front Aux.

CF400

2

2

4

4 (2)

CF310

2

2

4

4 (2)

CF220

2

2

4

2

(1) For other operating conditions, please contact your local Rockwell Automation sales office or Allen-Bradley distributor. (2) With no side auxiliary contacts installed. Otherwise 3 N.C. Maximum

Max. N.O. Front + Side Aux.
6 6 6

Max. N.C. Front + Side Aux.
5 5 4

Max. N.O. + N.C. Front + Side Aux.
8 8 8

194

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

Control Modules

Photo

Description

Connection Diagrams

Pneumatic Timing Modules(1) ON-Delay Pneumatic timing element contacts switch after the delay time. The contacts on the main control relay continue to operate without delay.

Pneumatic Timing Modules OFF-Delay Pneumatic timing element contacts switch after the delay time. The contacts on the main control relay continue to operate without delay.

Electronic Timing Modules -- On-Delay Delay of the control relay coil assembly. The control relay is energized at the end of the delay time.

Electronic Timing Modules -- Off-Delay Delay of the control relay coil assembly. After interruption of the control signal, the control relay is deenergized at the end of the delay time.

(1) On-Delay modules cannot be used with side-mounted auxiliary contacts on DC coil relays.

Photo

Description

Reset Repeat

Time

Accuracy

Delay

For Use With

0.3...30 s

Cat. No. 100-FPTA30

25...90 ms for AC Coils
47...85 ms for DC coils

+/-10%

1.8...180 s
700-CF all (1) 0.3...30 s

100-FPTA180 100-FPTB30

1.8...180 s

100-FPTB180

100 ms +/-1% 100 ms +/-1%

0.1...3 s 1...30 s 10...180 s 0.1...3 s 1...30 s
10...180 s

700-CF 110...240V AC coils
700-CF 24...48V DC coils

0.3...3 s 1...30 s 10...180 s 0.3...3 s 1...30 s
10...180 s

700-CF 110...240V AC coils
700-CF 24V AC coils

100-ETA3 100-ETA30 100-ETA180 100-ETAZJ3 100-ETAZJ30 100-ETAZJ180 100-ETB3 100-ETB30 100-ETB180 100-ETBKJ3 100-ETBKJ30
100-ETBKJ180

Connection Diagrams

For Use With Cat. No.

Mechanical Latch Following relay latching, the relay coil is immediately de-energized (off) by the N.C. auxiliary contact (65-66). Electrical or manual release 1 N.O. + 1 N.C. auxiliary contacts

700-CF with AC coils

100-FL11

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

195

Relay and Timer Specifications

Photo

Description

Connection Diagrams

RC Module AC Operating Mechanism

24...48V 50/60 Hz
110...280V 50/60 Hz
380...480V 50/60 Hz

Surge Suppressors For limitation of coil switching transients. Plug-in, coil mounted

Varistor Module AC/DC Operating Mechanism

12...55V AC/ 12...77V DC
56...136V AC/ 78...180V DC
137...277V AC/ 181...350V DC

278...575V AC

Diode Module DC Operating Mechanism Dropout Time 70...95 ms

12...250V DC

(1) For spring clamp terminals, insert CR after 100-. Example: Cat. No. 100-CRFSC48.

Coil Voltage Code

For Use With 700-CF with AC coils
700-CF all

Cat. No. (1) 100-FSC48 100-FSC280 100-FSC480 100-FSV55 100-FSV136 100-FSV277 100-FSV575

700-CF with Conventional DC coils

100-FSD250

The cat. no. as listed is incomplete. Select a coil voltage code from the table below to complete the cat. no. Example: Cat. No. 100-FL11 becomes Cat. No. 100-FL11J.

[V] (1)

24

48

100

110

120

230...240 240

277

380...400 400...415 440

480

50 Hz K

Y

KP

D

--

VA

T

--

N

G

B

--

60 Hz J

--

--

--

D

--

A

T

--

--

N

B

(1) For special voltages, consult your local Rockwell Automation sales office or Allen-Bradley distributor.

Photo

Description (Relays)
DC Interface (electronic) Interface between the DC control signal (PLC) and the AC operating mechanism of the control relay. Control (input) voltage 12V DC 24V DC 48V DC Requires no additional surge suppression on the relay coils

Input: 24V DC Output: 110...240V AC
Input: 12V DC Output: 110...240V AC
Input: 48V DC Output: 110...240V AC

Connection Diagrams

For Use With (Relays)

Cat. No. 100-JE

700-CF with 110...240V AC coils

100-JE12

100-JE48

196

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

Specifications 100-J... DC Interfaces

Electrical Input Voltage Input Voltage Range Output Voltage Power Consumption Minimum Actuation Mechanical Finger Protection
Pickup Time

Dropout Time
Max. Cycles Per Second Isolation/Breakdown Voltage Rated Impulse Withstand Voltage Environmental Ambient Temperature Range Storage Temperature Range Operating Life Construction

Flexible wire

Wire Size Range

Solid wire

Solid and Stranded Tightening Torque Type of Light
(1) To consider the maximum operations/hour of the relays.

1 Wire 2 Wire 1 Wire 2 Wire

Assembly Components

Photo

Description

Cat. No. 100-JE

Cat. No. 100-JE12

Cat. No. 100-JE48

24V DC 18...30V DC 110...240V AC 0.1...0.4 W 5V DC, 2 mA DC

12V DC 6...12V DC 110...240V AC 0.02...0.12 W 5V DC, 2 mA DC

48V DC 35...48V DC 110...240V AC 0.2...0.5 W 5V DC, 2 mA DC

IP20
0...10 ms + pickup time of the contactor
0...10 ms + dropout time of the contactor 2 (1)
In: 50V, Out: 250V
4 kV

IP20
0...10 ms + pickup time of the contactor
0...10 ms + dropout time of the contactor 2 (1)
In: 50V, Out: 250V
4 kV

IP20
0...10 ms + pickup time of the contactor
0...10 ms + dropout time of the contactor 2 (1)
In: 50V, Out: 250V
4 kV

-25...+60 °C -50...+80 °C 100 + million ops

-25...+60 °C -50...+80 °C 100 + million ops

-25...+60 °C -50...+80 °C 100 + million ops

0.5...2.5 mm2 0.75...2.5 mm2 1.0...2.5 mm2 1.0...2.5 mm2 18...14 AWG 1...1.5 N·m / 7...15 lb·in
LED

0.5...2.5 mm2 0.75...2.5 mm2 1.0...2.5 mm2 1.0...2.5 mm2 18...14 AWG 1...1.5 N·m / 7...15 lb·in
LED

0.5...2.5 mm2 0.75...2.5 mm2 1.0...2.5 mm2 1.0...2.5 mm2 18...14 AWG 1...1.5 N·m / 7...15 lb·in
LED

For Use With

Pkg Qty. (1)

Cat. No.

Protective Covers Provides protection against unintended manual operation

700-CF all

1

100-SCCA

Protective Covers · Provides protection against unintended manual operation · For contactors and front-mounted auxiliary contacts, pneumatic timers,
and latches
(1) All Cat. Nos. are factory stocked.

100-FA, -FB, -FC, -FP, -FL; 10

100-SCFA

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

197

Relay and Timer Specifications

Accessories
Uniform labeling materials for contactors, motor startup equipment, relays, and circuit breakers.

Photo

Description

Label Sheet 105 self-adhesive paper labels each, 6 x 17 mm

Marking Tag Sheet 160 perforated paper labels each, 6 x 17 mm, to be used with a transparent cover Transparent Cover To be used with marking tag sheets

Marking Tag Adapters To be used with marking tag: System V4/V5 System 1492 W
(1) Must be ordered in multiples of package quantities. (2) Marker for 100-FMA1 must be purchased from a third party.

Pkg. Qty. (1)
10

Cat. No.
100-FMS

10

100-FMP

100

100-FMC

100

100-FMA1 (2)

100-FMA2

198

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Coils
Photo

Relay and Timer Specifications

AC Coil Code
Q R J K KJ V W X Y KY KP D KD P S KG H L KL A F KF VA T KA I E N KN G B KB M C

50Hz -- 12V -- 24V -- 32V 36V 42V 48V -- 100V 110V -- 120V 127V 200V -- 200 - 220V -- 220V 220 - 230V -- 230 - 240V 240V -- -- -- 380 - 400V -- 400-415V 440V -- 500V 550V

AC Voltages 60Hz 12V -- 24V -- -- 36V -- 48V -- --
100 - 110V 120V -- -- --
200 - 220V 208V
208 - 240V -- 240V 260V -- -- 277V -- 347V 380V 440V -- -- 480V -- -- 600V

50/60Hz -- -- -- -- 24V -- -- -- -- 48V 100V -- 110V -- -- 200V -- --
200 - 230V -- -- 230V -- -- 240V -- -- -- 400V -- -- 440V -- --

Cat. No. 700-CF
TA006 TA404 TA013 TA407 TA855 TA481 TA410 TA482 TA414 TA860 TA861 TA473 TA856 TA425 TA428 TA862 TA049 TA296 TA864 TA474 TA441 TA851 TA440 TA480 TA858 TA065 TA067 TA071 TA863 TA457 TA475 TA859 TA479 TA476

DC Coil Code DC Voltages Cat. No. 700-CF

EQ

12V TC708E

EJ

24 V TC714E

QJ

24V TC714Q

EY

48...72V TC724E

EW

36...48 TC719E

ED

110...125 TC733E

EA

220...250 TC747E

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

199

Relay and Timer Specifications

Specifications - 700-CF..., 700S-CF Relays

Contact Ratings -- NEMA Min. Contact Rating
Contact Ratings -- IEC AC-15 (solenoids, contactors) at rated voltage IEC 60947-5-1
40 °C AC-12 (Control of resistive loads) IEC 60947-5-1
60 °C
DC-12 Switching DC Loads L/R < 1ms, Resistive Loads IEC 60947-5-1
DC-13 IEC 60947-5-1, Solenoids and contactors

24V 48V 120V 240V 400V 480V/500V 600V 690V Ith 230V 400V 690V Ith 230V 400V 690V 24V 48V 110V 220V 440V 24V 48V 110V 220V 440V

Main Relay Cat. Nos. 700-CF, 700S- CF A600, P600 17V, 10 mA
10 A 10 A 10 A 10 A 6 A 2.5 A 1 A 1 A 20 A 8 kW 14 kW 24 kW 20 A 8 kW 14 kW 24 kW 15 A 10 A 6 A 1 A 0.4 A 5 A 3 A 1.2 A 0.6 A 0.3 A

Front Mounted Standard Auxiliary Contacts A600, Q600 17V, 5 mA 6 A 6 A 6 A 5 A 3 A 1.6 A 1 A 1 A
10 A
6 A
10 A 9 A 3.5 A 0.7 A 0.2 A 5 A 3 A 1.2 A 0.6 A 0.15 A

Main Relay Cat. No. 700-CFB, 700S- CFB A600, Q600 8V, 5 mA 3 A 3 A 3 A 3 A 2 A 1.2 A 0.7 A 0.7 A
10 A
6 A
6 A 3.2 A 1 A 0.5 A 0.2 A 2.5 A 1.5 A 0.6 A 0.3 A 0.15 A

Master Relay Cat. No. 700-CFM
2 x A600, P600 -- 15 A 15 A 15 A 15 A 7.5 A 5 A 2 A 2 A

Front Mounted Bifurcated Auxiliary Contacts A600, Q600 5V, 3 mA 3 A 3 A 3 A 3 A 2 A 1.2 A 0.7 A 0.7 A

Side-mounted Auxiliary Contacts
A600, Q600 17V, 10 mA
6 A 6 A 6 A 5 A 3 A 1.6 A 1 A 1 A

20 A

10 A

10 A

20 A

6 A

6 A

20 A

6 A

6 A

20 A

3.2 A

3.2 A

8 A

1 A

1 A

1.5 A

0.5 A

0.5 A

0.4 A

0.2 A

0.2 A

5 A

2.5 A

5 A

3 A

1.5 A

2.5 A

1.2 A

0.6 A

0.68 A

0.6 A

0.3 A

0.32 A

0.3 A

0.15 A

0.15 A

Location of welded N.O. contacts

State of N.C. Contacts if N.O. contact welds

Main

Front aux.

Main

Open

Open

Mechanically Linked Contacts (1)

Front aux.

Open

Open

(1) Side mounted auxiliary contacts provide"mirror contact"performance with main poles only. (2) Defined in IEC 60947-5-1 annex L. Mechanically linked is a relationship between contacts of opposite types (i.e., N.O. and N.C.).

Side aux. Open (2)
--

200

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Attribute

Mechanical Life Electrical Life Weight Terminal Cross-Sections

AC-15 (240V, 3 A)
AC Coil

Terminal Type

Terminal Size per IEC60 947-1

Solid/Stranded
(1)

1 Conductor 2 Conductor

Max. Wire Size per UL/CSA

Tightening Torque

Tightening Torque

(1) For 16 or more strands, end ferrule is required.

Cat. No. 700-CF

[Mil]

15

Aux./Pneumatic Timer Contact (Front mounted)
5

[Mil]

1.5

1.5

[g]

390

--

[mm2] [mm2]
[AWG] [lb·in] [N·m]

2 x A4 1.5...6 1.5...6 16...10 13.3...17.7 1.5...2.0

2 x A4 0.5...2.5 0.75...2.5 18...14 8.9...13.3 1...1.5

DC Switching Ratings for 700-CF Main Poles in Series (Resistive Load at 60 °C)

Attribute

1 pole

2 poles

3 poles

24/48V

15/10 A

25 A

25 A

125V

6 A

25 A

25 A

220V

1 A

6 A

25 A

440V

0.4 A

1 A

3 A

Relay and Timer Specifications

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

201

Relay and Timer Specifications

Control Circuit
Operating Voltage AC 50/60 Hz DC (conventional) (1) DC (electronic EQ, EW) DC (electronic EY) DC (electronic ED) DC (electronic EA) Coil Consumption AC 50/60 Hz DC (conventional) DC (electronic EQ, EJ) DC (electronic EY) DC (electronic ED) DC (electronic EA) Operating Times AC 50/60 Hz DC (conventional) With integrated diode With external diode DC (electronic- EQ, EJ) DC (electronic - EW EY, ED, EA) DC (electronic- QJ)

Attribute
Pickup Dropout Pickup Dropout Pickup Dropout Pickup Dropout Pickup Dropout Pickup Dropout
Inrush Sealed Inrush Sealed Inrush (avg./ peak) Sealed Inrush (avg./ peak) Sealed Inrush (avg./ peak) Sealed Inrush (avg./ peak) Sealed
Pickup Time Dropout Time Pickup Time Dropout Time Opening Delay Opening Delay Closing Delay Opening Delay Closing Delay Opening Delay Closing Delay Opening Delay

[x Us] [x Us] [x Us] [x Us] [x Us] [x Us] [x Us] [x Us] [x Us] [x Us] [x Us] [x Us]
[VA] [VA/W]
[W] [W] [W] [W] [W] [W] [W] [W] [W] [W]
[ms] [ms] [ms] [ms] [ms] [ms] [ms] [ms] [ms] [ms] [ms] [ms]

Cat. No. 700-CF
0.85...1.1 0.3...0.6 0.8...1.1 0.1...0.6 0.7...1.25 0.3...0.4 0.8...1.25 0.3...0.4 0.7...1.12 (2) 0.3...0.4 0.8...1.1 0.3...0.4
75 9.5/2.7
7.7 6.3 10/17 1.7 10/17 1.9 12/19 2.1 14/22 3.0
15...30 10...60 40...70 7...15 14...20 70...125 25...50 27...45 25...50 23...33 20...50 15...22

202

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Attribute

Min OFF time

Max. ripple

Latch Attachment Release, 100-FL

AC
Coil Consumption DC

Contact Signal Duration

Timing Attachment

Reset Time, 100- ETA, 100-ETB

at min. time setting at max. time setting

Repeat Accuracy

(1) For 9V DC, code ZR, use operating voltage 0.65...1.3 x Us. For 24V DC, code ZJ, DJ, or EJ use operating voltage 0.7...1.25 x Us.
(2) At 110V DC, coil code ED has an operating voltage range of 0.7...1.25 x Us.

[ms]
[VA/W] [W]
[min./max]
[ms] [ms]

Cat. No. 700-CF 50
± 15%
45/40 25
0.03...15 s
10 70 ± 10%

Relay and Timer Specifications

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

203

Relay and Timer Specifications

General Specifications - 700-CF Relays

Rated Insulation Voltage Ui IEC UL; CSA Rated Impulse Strength Uimp High Test Voltage 1 minute (per IEC 60947Rated Voltage Ue AC DC
Rated Frequency Ambient Temperature Storage Operation at nominal current 15% current reduction for AC-12 at > 60 °C Corrosion Resistance Altitude Type of Protection IP2X (IEC 60529 and DIN 40050) Shock Resistance Vibration Resistance Standards Compliance Certifications

Cat. No. 700-CF
690V 600V 6 kV 2500V
115, 230, 400, 500, 690V 24, 48, 110, 220, 440V Short-Circuit Protection gG Fuse 20 A
50/60 Hz, DC
­55...+80 °C (­67...+176 °F) ­25...+60 °C (­13...+140 °F) ­25...+70 °C (­13...+158 °F) humid-alternating climate, cyclic, per IEC 60068-2-30 and DIN 50 016, 56 cycles 2000 m above mean sea level, per IEC 60 947-4
in connected state IEC 60068-2: Half sinusoidal shock 11 ms, 30 G (in 3 directions) IEC 60068-2: Static >2 G, in normal position no malfunction <5 G UL 508, CSA C22.2 No. 14, EN/IEC 60947-1, -5-1, Meets the material restrictions for European Directive 2002/95/EC - EUcULus Listed (File No. E14840, Guide NKCR/NKCR7), CE Marked, CCC Certified

Utilization Category Table from EN 60947-5-1

Verification of Making and Breaking Capacities of Switching Elements Under Normal Conditions Corresponding to the Utilization Categories (1)

Normal Condition of Use

Utilization Category
AC-12 (2) AC-13 (2) AC-14 (2) AC-15 (2)

Make (3)
I/Ie
1 2 6 10

U/Ue
1 1 1 1

Break (3)

cos 
0.9 0.65 0.3 0.3

I/Ie
1 1 1 1

U/Ue
1 1 1 1

cos 
0.9 0.65 0.3 0.3

Number and Rate of Making and Breaking operations

No.
operating cycles (5)

Operating cycles per minute

ON time [s]
(6)

6050

6

0.05

6050

6

0.05

6050

6

0.05

6050

6

0.05

DC

--

--

T0.95

--

--

T0.95

--

--

--

DC-12

1

1

1 ms

1

1

1 ms

6050

6

0.05 (6)

DC-13

1

1

6 x P (4)

1

1

6 x P (4)

6050

6

0.05 (6)

DC-14 (2)

10

1

15 ms

1

1

15 ms

6050

--

0.05 (6)

(1) See sub-clause 8.3.3.5.2. (2) Where the break current differs from the make current value, the ON time refers to the make current value after which the current is reduced to the break current value for a suitable period e.g., 0.05 s. (3) For tolerances on test quantities, see sub-clause 8.3.2.2. (4) The value "6 x P"results from an empirical relationship which is found to represent most DC magnetic loads to an upper limit of P = 50 W, e.g., 6 x P = 300 W. (5) The first 50 operating cycles shall be run at U/Ue = 1.1 with the loads set at Ue. (6) The ON time shall be at least equal to T0.95. Ie Rated operational current, I Current to be made or broken Ue Rated operational voltage, U Voltage before make PUeIe Steady-state power consumption (W) T0.95 Time to reach 95% of the steady-state current (ms)

204

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

Contact Rating Table from EN 60947-5-1

Examples of Contact Rating Designation Based on Utilization Categories

NEMA Designation
(1)

IEC Utilization Category

Conventional Thermal
Current Ithe (A)

Rated Operational Current Ie (A) at Rated Operational Voltage Ue

AC

120V

240V

380V

480V

500V

600V

A150

AC-15

10

6

--

--

--

--

--

A300

AC-15

10

6

3

--

--

--

--

A600

AC-15

10

6

3

1.9

1.5

1.4

1.2

B150

AC-15

5

3

--

--

--

--

--

B300

AC-15

5

3

1.5

--

--

--

--

B600

AC-15

5

3

1.5

0.95

0.75

0.72

0.6

C150

AC-15

2.5

1.5

--

--

--

--

--

C300

AC-15

2.5

1.5

0.75

--

--

--

--

C600

AC-15

2.5

1.5

0.75

0.47

0.375

.035

0.3

D150

AC-15

1.0

0.6

--

--

--

--

--

D300

AC-14

1.0

0.6

0.3

--

--

--

--

E150

AC-14

0.5

0.3

--

--

--

--

--

DC

125V

250V

440V

500V

600V

--

N150

DC-13

10

2.2

--

--

--

--

--

N300

DC-13

10

2.2

1.1

--

--

--

--

N600

DC-13

10

2.2

1.1

0.63

0.55

0.4

--

P150

DC-13

5

1.1

--

--

--

--

--

P300

DC-13

5

1.1

0.55

--

--

--

--

P600

DC-13

5

1.1

0.55

0.31

0.27

0.2

--

Q150

DC-13

2.5

0.55

--

--

--

--

--

Q300

DC-13

2.5

0.55

0.27

--

--

--

--

Q600

DC-13

2.5

0.55

0.27

0.15

0.13

0.1

--

R150

DC-13

1.0

0.22

--

--

--

--

--

R300

DC-13

1.0

0.22

0.1

--

--

--

--

(1) This letter stands for the conventional thermal current and identifies AC or DC: for example, B=5 A AC. The number that follows is the rated insulation voltage.

VA Rating

Make

Break

7200

720

7200

720

7200

720

3600

360

3600

360

3600

360

1800

180

1800

180

1800

180

432

72

432

72

216

36

Make

Break

275

275

275

275

275

275

138

138

138

138

138

138

69

69

69

69

69

69

28

28

28

28

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

205

Relay and Timer Specifications
Dimensions - 700-CF... Relays
Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.
Mounting Position
AC and DC Control Relay with DC Electronic Coil

(1)
(1) May be mounted to 35 mm EN 50 022 DIN Rail.

Front View

Side View

DC Control Relay

Front View

Side View

All AC Control Relays and DC Control Relays with 12V or 24V DC Electronic Coil

Type 700-CF, -CFB, -CFM

a
45 (1-25/32)

b
81 (3-3/16)

c
80.5 (3-11/64)

c1
75.5 (3-3/32)

c2
6 (1/4)

Ød
2 screws 4.5 (3/16)

d1
60 (2-23/64)

d2
35 (1-25/64)

DC Control Relays with 48...72V, 110...125V or 220...250V DC Electronic Coil

Type 700-CF, -CFB, -CFM

a
45 (1-25/32)

b
105 (4-1/8)

c
80.5 (3-11/64)

c1
75.5 (3-3/32)

c2
6 (1/4)

Ød
2 screws 4.5 (3/16)

d1
60 (2-23/64)

d2
35 (1-25/64)

DC Control Relays with Conventional Coil

Type 700-CF, -CFB, -CFM

a
45 (1-25/32)

b
81 (3-3/16)

c
106.5 (4-3/16)

c1
101.5 (4)

c2
6 (1/4)

Ød
2 screws 4.5 (3/16)

d1
60 (2-23/64)

d2
35 (1-25/64)

206

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

Accessories - 700-CF Relays

Relay with

Auxiliary Contact for Front Mounting Auxiliary Contact for Side Mounting
Pneumatic Timing Module Solid-state Timing Module
Mechanical Latching DC Interface
Surge Suppressor Labelling with:
-- -- --

2- or 4-pole 1- or 2-pole
-- on coil terminal side
-- on coil terminal side on coil terminal side
label sheet marking tag with cover marking tag carrier for System V4/V5 marking tag carrier for System Bull. 1492W

AC Control Relay

mm

(inches)

c/c1 + 39 (c/c1 + 1 ­ 37/64)

a + 9

(a + 23/64)

c/c1 + 58 (c/c1 + 2 ­ 23/64)

b + 24

(b + 15/16)

c/c1 + 61 (c/c1 + 2 ­ 31/64)

b + 9

(b + 23/64)

b + 3

(b + 1/8)

+0

(+0)

+0

(+0)

+5.5

(+7/32)

+5.5

(+7/32)

DC Control Relay

mm

(inches)

c/c1 + 39 c/c1 + 1 ­ 37/64)

a + 9

(a + 23/64)

--

--

b + 24

(b + 15/16)

--

--

--

--

b + 3

(b + 1/8)

+0

(+0)

+0

(+0)

+5.5

(+7/32)

+5.5

(+7/32)

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

207

Relay and Timer Specifications

700S-CF Control Relays
The 700S-CF Safety Control Relay provides mechanically or mirror contact performance, which are required in feedback circuits for safety applications. Bifurcated contacts are ideal for low energy feedback safety circuits where high contact reliability is required.
· IEC industrial safety relay · Mechanically linked contacts as per IEC 60947-5-1 · Third party certification SUVA · Red cover and mechanically linked contact symbol on front face · Gold plated, bifurcated version for low level switching applications · Permanently fixed front mounted auxiliary contact block

Type CF and CFB Safety Control Relays -- 8-Pole AC Coil Voltage (Ratings for 700S-CF Only)

AC-12

AC-15

Connection Diagrams

Ith [A]

Ie [A]

40 60 24/ °C °C 48V
20 20 10

Main Contacts 120 240 400 500 600 690 V V V V V V
10 10 6 2.5 1 1

Main Contacts

Auxiliary Contacts

Contacts

Standard Contacts (Main) Gold-Plated Bifurcated (Front) Cat. No.

Gold-Plated
Bifurcated,
All Contacts Cat. No. (1)

N.O. N.C.

4

4

700S-

700S-

CF440BC CFB440C

5

3

700S-

700S-

CF530BC CFB530C

Adder 10 6 6
Deck Contacts

6 5 3 1.6 1 1

(1) Ratings for 700S-CFB are on Specifications

6 2 700S-

700S-

CF620BC CFB620C

 AC Coil Voltage Code
The cat. no. as listed is incomplete. Select a coil voltage code from the table below to complete the cat. no. Example: Cat. No. 700S-CF440BC becomes Cat. No. 700S-CF440DBC for 120V, 60 Hz.

[V] 12 24

50 Hz R

K

60 Hz Q

J

50/60 -- KJ Hz

32 36 42 48

V

W X

Y

-- V

-- X

-- -- -- KY

100 100... 110 120 127 200 200... 208 208... 220...

110

220

240 230

KP -- D

P

S

KG L

-- -- F

-- KP -- D

-- -- KG H

L

--

KP -- KD -- -- KG KL -- -- KL

[V]

230 230... 240

277 347 380 380... 400 400... 440 480

500 550 600

240

400

415

50 Hz --

VA

T

--

--

--

N

--

G

B

--

M

C

--

60 Hz --

--

A

T

I

E

--

--

--

N

B

--

--

C

50/60 Hz KF

--

KA

--

--

--

--

KN

--

KB

--

--

--

--

208

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

Type CF and CFB Safety Control Relays -- 8-Pole DC Coil Voltage (Ratings for 700S-CF Only)

AC-12 Ith [A]

AC-15 Ie [A]

Connection Diagrams

Main Contacts

40 °C

60 °C

24/48V

120V

240V

400V

500V

600V

690V

20 20 10 10 10 6 2.5 1 1

Main Contacts

Auxiliary Contacts

Contacts

No. of N.O. Contacts

No. of N.C. Contacts

Standard Contacts (Main) GoldPlated Bifurcated (Front) Cat. No.

Gold Plated Bifurcated All Contacts Cat. No.(1)

4

4

700S-

700S-

CF440BC CFB440C

5

3

700S-

700S-

CF530BC CFB530C

Adder 10 6 6
Deck Contacts

6 5 3 1.6 1 1

(1) Ratings for 700S-CFB are on Specifications

6

2

700S-

700S-

CF620BC CFB620C

 DC Coil Voltage Code

The cat. no. as listed is incomplete. Select a coil voltage code from the table below to complete the cat. no. Example: Cat. No. 700S-CFB440C becomes Cat. No. 700S-CFB440EJC for 24V DC, electronic with diode.

[V]

9 12 24

Electronic with diode

--

EQ

EJ

Electronic with diode/ Quick -- -- QJ Pick-up

36

48

48... 72

60

64

72

80

110

110... 125

115

125

220

220... 250

230

250

EW -- EY -- -- -- -- -- ED -- -- -- EA -- --

------------------ -------- ----

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

209

Relay and Timer Specifications

Assignment of Contacts
Safety Control Relays with Front-mount Auxiliary Contacts, 8-Pole AC or DC Coil Voltage

53 61 71 81

53 61 71 83

53 61 73 83

54 62 72 82
A1 13 21 33 43 K1
A2 14 22 34 44
700S-CF440... 700S-CFB440...

54 62 72 84
A1 13 21 33 43 K1
A2 14 22 34 44
700S-CF530... 700S-CFB530...

54 62 74 84
A1 13 21 33 43 K1
A2 14 22 34 44
700S-CF620... 700S-CFB620...

Specifications - 700S-CF Relays
For more 700S-CF Specifications, see Specifications - 700-CF..., 700S-CF Relays on page 200.

Mechanical Life Electrical Life Weight Terminal Cross-Sections Terminal Type Terminal Size per IEC 947-1
Solid/ Stranded (1)
Max. Wire Size per UL/CSA Tightening Torque Tightening Torque

AC-15 (240V, 3 A) AC Coil
1 Conductor 2 Conductor

Standards Compliance

Certifications
(1) For 16 or more strands, end ferrule is required

[Mil] [Mil] [g]
[mm2] [mm2]
[AWG] [lb·in] [N·m]

Cat. No. 700S-CF
15 1.5 390

Aux. Contact (Front-mounted)
15 1.5 --

2 x A4

2 x A4

1.5...6

0.5...2.5

1.5...6

0.75...2.5

16...10

18...14

13.3...22

8.9...13.3

1.5...2.5

1...1.5

UL 508, CSA C22.2 No. 14, EN/IEC 60947-1, -5-1, Meets the material restrictions for European Directive 2002/95/EC - EU-RoHS

cULus Listed (File No. E14840, Guide NKCR/NKCR7), CE Marked, CCC Certified

210

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications
Dimensions - 700S-CF Relays
Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.
c2

AC and DC Safety Control Relays with 12V or 24V DC Electronic Coil

Cat. No. 700S-CF

a 45
(1-25/32)

b 81
(3-3/16)

c 119.5 (4-3/4)

c1 114.5
(4-43/64)

c1 c
c2 6
(1/4)

DC Safety Control Relays with 48...72V, 110...125V or 220...250V DC Electronic Coil

Cat. No. 700S-CF

a 45
(1-25/32)

b 105
(4-1/8)

c 119.5 (4-3/4)

c1 114.5
(4-43/64)

c2 6
(1/4)

DC Safety Control Relays with Conventional Coil

Cat. No. 700S-CF

a 45
(1-25/32)

b 81
(3-3/16)

c 145.5
(5-49/64)

c1 140.5
(5-37/64)

c2 6
(1/4)

Accessories - 700S-CF Relays
Safety Control Relays with
Auxiliary contact block for side mounting 1- or 2-pole Electronic Timing Module on coil terminal side Interface Module on coil terminal side Surge Suppressor on coil terminal side Labeling with label sheet Marking tag sheet with clear cover Marking tag adapter for System Bul. 1492W

Ød 2 - 4.5 (2 - 3/16)

d1 60
(2-23/64)

d2 35
(1-25/64)

Ød 2 - 4.5 (2 - 3/16)

d1 60
(2-23/64)

d2 35
(1-25/64)

Ød 2 - 4.5 (2 - 3/16)

d1 60
(2-23/64)

d2 35
(1-25/64)

mm
a + 9 b + 24 b + 9 b + 3 + 0 + 0 + 5.5

[in.]
(a + 23/64) (b + 15/16) (b + 23/64) (b + 1/8)
(+ 0) (+ 0) (+ 7/32)

Mounting Position

AC and DC E Safety Control Relays

DC Safety Control Relays

Front View

Side View

Front View

Side View

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

211

Relay and Timer Specifications
Safety Relay Circuit With 5 Safety Outputs
· Use for E-stop control. E-stop will work properly if any one fault occurs (a fault could be one welded contact or one undesired open connection such as a loose wire).
· High output switching capability and long contact life. · Circuit complies with EN 954 categories 1, 2, 3, 4. · Helps prevent restart of the 5 safety outputs if there is a single fault anywhere in the system. · Use (3) 700S-CF relays and this diagram to construct the circuit
Basic Circuit (1) Output Circuit (3 Relays, 9 Terminal Blocks)
Start
Push To Stop Pull To Reset
Included in factory wired units
LOAD 1 (5) Output Circuit (3 Relays, 17 Terminal Blocks)
LOAD 2 LOAD 3 LOAD 4 LOAD 5
* Numbers shown are the line numbers where the contacts for this relay appear. Contact your local Rockwell Automation sales office or Allen-Bradley distributor for availability.

212

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

700-EF Control Relay
· IEC industrial relays · Electronic coils · Mechanically linked contact performance per IEC 60947-5-1 · Wide control voltage range · Built-in surge protection · Add-on auxiliary contact blocks - front or side mount

4-Pole AC Coil Voltage

AC-12

AC-15

Ith [A] Ie [A]

Connection Diagrams

 40 °C 24/48V

120V 240V 400V 500V 690V

Contacts

Standard Contacts(1)

N.O. N.C. Cat. No.

2

2

700-EF220

16

6

6

4

3

2

2

(1) All catalog numbers are factory stocked.

3

1

700-EF310

4

0

700-EF400

Voltage Codes.

The catalog number listed is incomplete. Select a coil voltage from the table below to complete the catalog number. Example 700-EF220KJ.

Voltage(1)

12...20V DC

24V DC

24...60V AC 20...60V DC

48...130V AC/DC 100...250V AC/DC 250...500V AC/DC

Standard AC/DC

--

--

KJ

KY

KD

KN

Low Consumption AC/DC

EQ

--

EJ

--

--

--

Low Consumption/Faster Drop-out DC

--

QJ

--

--

--

--

(1) AC Voltages are a 50/60 Hz.

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

213

Relay and Timer Specifications

Accessories
Auxiliary Contact Blocks with Standard Auxiliary Contacts

Description
Auxiliary Contact Blocks for Front Mounting · 1-pole · Quick and easy mounting without tools · Screw connection terminals · Switching down to 12V, 3mA · Mirror contact performance to the main relay poles · L= Late break N.C./early make N.O.
Auxiliary Contact Blocks for Front Mounting · 4-pole · Quick and easy mounting without tools · Screw connection terminals · Switching down to 12V 3mA · Mirror contact performance to the main relay poles

Connection Diagrams

N.O. N.C.

10

-3

-1

NO

NC

01

-4

-2

1L 0

-7

-5

NO

NC

0 1L

-8

-6

53

61

71

83

2

2

NO

NC

NC

NO

54

62

72

84

53

61

73

83

3

1

NO

NC

NO

NO

54

62

74

84

53

63

73

83

4

0

NO NO

NO

NO

54

64

74

84

53

61

71

81

1

3 NO

NC

NC

NC

54

62

72

82

51

61

71

81

0

4

NC

NC

NC

NC

52

62

72

82

Auxiliary Contact Blocks for Side Mounting · 2-pole · Two-way numbering for right or left mounting on the relay · With or without sequence terminal designations · Quick and easy mounting without tools · Screw connecting terminals · Switching down to 12V, 3mA · Mirror contact performance to the main relay poles

11

-3

-1

NO

NC

-4

-2

For Use With
700-EF220 700-EF310 700-EF220 700-EF310
700-EF220
700-EF220 700-EF310

Cat. No.
100-EFA10 100-EFA01 100-EFAL10 100-EFAL01 100-EFA22 100-EFA31 100-EFA40 100-EFA13 100-EFA04
100-ESA11

Electronic Timers
Description
Electronic Timing Module--ON-Delay · Delay of the relay solenoid · The relay is energized at the end of the delay time
Electronic Timing Module--OFF-Delay · Delay of the relay solenoid · After interruption of the control signal, the relay is de-
energized a the end of the delay time

ON-Delay 0.1...1 s 1...10 s 10...100 s
OFF-Delay 0.1...1 s 1...10 s 10...100 s

N.O. N.C.
11
11

Connection Diagrams
55NC 67NO A1 KM1 A2
56NC 68NO
55NC 67NO A1 KM1 A2
56NC 68NO

For Use With
700-EF220 700-EF310
700-EF220 700-EF310

Cat. No.
100-ETA 100-ETB

214

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

DC Interface Module

Description
DC Interface · Receives 24V DC signals from PLCs or other low output power sources and switches AC
control power to operate the coils of the relay. · Coil voltage: 24...250V AC 50/60 Hz · Rated control circuit voltage Uc: 24VDC

For Use With
700-EF

Pkg. Qty.
1
10

Cat. No.
100-EJE
100-EJEM

Mechanical Latch

Description
Mechanical Latch · Ensures contactor or relay is switched on even if
there is a voltage failure · Opening controlled either electrically by AC or
DC impulse or manually by button · Front mounting

Rated Voltage [V]

Connection

V AC, 50/60 Hz V DC

Diagram

24...60 24...60

48...130 48...130

100...250 100...250
A1

E1 U
c
E2

250...500 250...500 A2

For Use With
700-EF

Additional Coil Terminal Block

Description

Additional Coil Terminal Block · Allows bottom access to the coil terminals in addition to top access

For Use With
700-EF

Pkg. Qty.
10

Cat. No.
100-EFL11EJ 100-EFL11EY 100-EFL11ED 100-EFL11EN
Cat. No.
100-ECT

Functional Markers

Description
Functional Markers · 256 markers (16 per card) printable on HTP500 thermal transfer printer and
AMS 500 marking table · 7 x 20 mm (0.276 x 0.787 in)

For Use With
700-EF

Pkg. Qty.
16

Cat. No.
100-EFMS

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

215

Relay and Timer Specifications

Auxiliary Contacts

700-EF
Cat. No. 700...
EF310 EF220 EF400

Max 2 Pole Side Aux.
1 (L) 1 (L) 1 (R) --

Max 1 Pole Front Aux.
2 4 --

Max 4 Pole Front Aux.
-- 1 --

Timer
1 1 --

Mechanical Latch
1 1 --

Mechanically Linked Contacts (1)

Location of welded N.O. contacts
Main Front aux.

State of N.C. Contacts if N.O. contact welds

Main

Front aux.

Open

Open

Open

Open

(1) Side mounted auxiliary contacts provide"mirror contact"performance with main poles only. (2) Defined in IEC 60947-5-1 annex L. Mechanically linked is a relationship between contacts of opposite types (i.e., N.O. and N.C.).
Contacts

Switching of AC Loads Rated Insulation voltage Ui Rated operational voltage Ue Rated impulse withstand voltage Uimp AC-12 Ith
AC-15 at rated voltage of
Switching of DC Loads
DC-13 switching electromagnets at
Fuse gG Load Carrying Capacity per UL/CSA Rated voltage Continuous rating Switching capacity Rated voltage Continuous rating Switching capacity

at 40 °C at 60 °C
24V 42/48V 120V 230V 240V 400V 415V 500V 690V
24V DC 48V DC 110V DC 220V DC 440V DC

700-EF

690V

690V

6kV

[A]

16

[A]

--

[A]

6

[A]

6

[A]

6

[A]

4

[A]

4

[A]

3

[A]

3

[A]

2

[A]

2

[A]

6

[A]

2.8

[A]

0.55

[A]

0.27

[A]

0.13

AC

[V]

600

40 °C

[A]

10

AC

A 600

DC

[V]

600

40 °C

[A]

2.5

DC

Q 600

100-EF
690V 690V 6kV 16 --
6 6 6 4 4 3 3 2 2
6 2.8 0.55 0.27 0.13
600 10 A 600 600 2.5 Q 600

Side aux. Open (2)
--
100-ESA
690V 690V 6kV 16 --
6 6 6 4 4 3 3 2 2
6 2.8 0.55 0.27 0.13
600 10 A 600 600 2.5 Q 600

216

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

General Specifications - 700-EF Relays
Rated Insulation Voltage Ui IEC UL; CSA Rated Impulse Strength Uimp Rated Voltage Ue AC DC
Rated Frequency Ambient Temperature Storage Operation at nominal current Altitude Mechanical Life Electrical Life Type of Protection IP2X (IEC 60529 and DIN 40050) Shock Resistance Vibration Resistance Standards Compliance Certifications

Cat. No. 700-EF
690V 600V 6 kV
24, 48, 120, 230, 400, 500, 690V 24, 48, 110, 220, 440V
Short-Circuit Protection gG Fuse 10 A
50/60 Hz, DC
­60...+80 °C (­76...+176 °F) ­40...+70 °C (­40...+158 °F)
3000 m 20 Mil 1.5 Mil (AC-15 240V, 3A)
in connected state IEC 60068-2: Half sinusoidal shock 11 ms, 25G (in 3 directions) IEC 60068-2: Static >2 G, in normal position no malfunction <5 G
UL 508, CSA C22.2 No. 14, EN/IEC 60947-1, -5-1, RoHS cULus Listed, CE Marked, CCC Certified

Conductors

Cross Sections, Screw Type Terminals

700-EF/ 700S-EF

Conductor Cross Sections--Main Contacts Terminal Type

1 conductor 2 conductors 1 conductor 2 conductors

[mm2] [mm2] [mm2] [mm2]

Recommended torque

[N·m]

Cross Section per UL/CSA

[AWG]

Recommended torque

[lb·in]

Conductor Cross Sections- Coil and Auxiliary Contact Terminal Type

1 conductor 2 conductors 1 conductor 2 conductors

[mm2] [mm2] [mm2] [mm2]

Recommended torque

[N·m]

Cross Section per UL/CSA

[AWG]

Recommended torque

[lb-in]

(1) Pozidriv No. 2 / Blade No. 3 screw

(1)
0.75...6 0.75...6 1...6 1...6
1.5 16...10
13
(1)
0.75...2.5 0.75...2.5 1...2.5 1...2.5
1.2 18...14
11

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

217

Relay and Timer Specifications
Coil Data
Operating Limits 50/60Hz DC Control Standard Coil 24-60V AC, 20-60V DC (KJ) 48...130V AC/DC (KY) 100...250V AC/DC (KD) 250...500V AC/DC (KN) Operating Times Energy-efficient Coil 12-20V DC (EQ) 24-60V AC, 20-60V DC (EJ) Operating Times High Energy Efficient Coil 24V DC (QJ) Operating Times

700-EF/ 700S-EF
pick-up dropout pick-up dropout
pick-up hold-in pick-up hold-in pick-up hold-in pick-up hold-in closing delay opening delay
pick-up hold-in pick-up hold-in closing delay opening delay
pick-up hold-in closing delay opening delay

[x Us] 0.85...1.1 [x Us]  0.60 [x Us] 0.80...1.1 [x Us]  0.60

[VA]/[W] [VA]/[W] [VA]/[W] [VA]/[W] [VA]/[W] [VA]/[W] [VA]/[W] [VA]/[W]
[ms] [ms]

50/50 2.2/2 50/50 2.2/2 50/50 2.2/2 50/50 2.2/2 40...95 11...95

[W] 12...16 [W] 1.7 [VA]/[W] 16/12...16 [VA]/[W] 1.7/1.7 [ms] 40...95 [ms] 11...95

[W] 6 [W] 1.7 [ms] 27...53 [ms] 17...29

218

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

Contact Rating Table from EN 60947-5-1

Examples of Contact Rating Designation Based on Utilization Categories

NEMA Designation
(1)

IEC Utilization Category

Conventional Thermal
Current Ithe (A)

Rated Operational Current Ie (A) at Rated Operational Voltage Ue

AC

120V

240V

380V

480V

500V

600V

A150

AC-15

10

6

--

--

--

--

--

A300

AC-15

10

6

3

--

--

--

--

A600

AC-15

10

6

3

1.9

1.5

1.4

1.2

B150

AC-15

5

3

--

--

--

--

--

B300

AC-15

5

3

1.5

--

--

--

--

B600

AC-15

5

3

1.5

0.95

0.75

0.72

0.6

C150

AC-15

2.5

1.5

--

--

--

--

--

C300

AC-15

2.5

1.5

0.75

--

--

--

--

C600

AC-15

2.5

1.5

0.75

0.47

0.375

.035

0.3

D150

AC-15

1.0

0.6

--

--

--

--

--

D300

AC-14

1.0

0.6

0.3

--

--

--

--

E150

AC-14

0.5

0.3

--

--

--

--

--

DC

125V

250V

440V

500V

600V

--

N150

DC-13

10

2.2

--

--

--

--

--

N300

DC-13

10

2.2

1.1

--

--

--

--

N600

DC-13

10

2.2

1.1

0.63

0.55

0.4

--

P150

DC-13

5

1.1

--

--

--

--

--

P300

DC-13

5

1.1

0.55

--

--

--

--

P600

DC-13

5

1.1

0.55

0.31

0.27

0.2

--

Q150

DC-13

2.5

0.55

--

--

--

--

--

Q300

DC-13

2.5

0.55

0.27

--

--

--

--

Q600

DC-13

2.5

0.55

0.27

0.15

0.13

0.1

--

R150

DC-13

1.0

0.22

--

--

--

--

--

R300

DC-13

1.0

0.22

0.1

--

--

--

--

(1) This letter stands for the conventional thermal current and identifies AC or DC: for example, B=5 A AC. The number that follows is the rated insulation voltage.

VA Rating

Make

Break

7200

720

7200

720

7200

720

3600

360

3600

360

3600

360

1800

180

1800

180

1800

180

432

72

432

72

216

36

Make

Break

275

275

275

275

275

275

138

138

138

138

138

138

69

69

69

69

69

69

28

28

28

28

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

219

Relay and Timer Specifications
Approximate Dimensions

Dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.

Mounting Position 700-EF Relays

Position 2

+30° -30°

Position 4

Position 3

Position 1

Position 1 ± 30°

Position 5

700-EF Relays
700-EF Relays with Standard Coils

6 (0.24)

45 (1.77)

77 (3.03) 71 (2.80) 5.5 (0.22)

80 (3.15)

35 mm EN/IEC 60715

5.5 (0.22)

700-EF Relays with Standard Coils and Side-mounted Auxiliary Contact

12 (0.47)

45 (1.77)

6 (0.24)

77 (3.03) 71 (2.80) 5.5 (0.22)

69.4 (2.73)

80 (3.15)
35 mm EN/IEC 60715

For relays with QJ coils, add 20 mm (0.79 in.) to the depth

700-EF Relays with Low-consumption Coils

77 (3.03)

6 (0.24)

45 (1.77)

71 (2.80) 5.5 (0.22)

(0
For relays with QJ coils, add 20 mm (0.79 in.) to the depth
10
(0.3 700-EF Relays with Low-consumption Coils and Front-mounted Auxiliary Contact

6 (0.24)

45 (1.77)

110.5 (4.35) 71 (2.80)
5.5 (0.22)

80 (3.15)

35 mm EN/IEC 60715

5.5 (0.22)

80 (3.15)

5.5 (0.22) (1

35 mm

EN/IEC 60715

10 (0.39)
For relays with QJ coils, add 20 mm (0.79 in.) to the depth

1 (0.3
For relays with QJ coils, add 20 mm (0.79 in.) to the depth

700-EF Relays with Standard Coils and Front-mounted Auxiliary Contact

6 (0.24)

45 (1.77)

110.5 (4.35) 71 (2.80)
5.5 (0.22)

700-EF Relays with Low-consumption Coils and Side-mounted Auxiliary Contact

77 (3.03)

12 (0.47)

45 (1.77)

6 (0.24)

71 (2.80) 5.5 (0.22)

69.4 (2.73)

80 (3.15)
35 mm EN/IEC 60715

80 (3.15)

5.5 (0.22) (

35 mm

EN/IEC 60715

10 (0.39)
For relays with QJ coils, add 20 mm (0.79 in.) to the depth

10 (0.3
For relays with QJ coils, add 20 mm (0.79 in.) to the depth

220

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

700S-EF Control Relays

The 700S-EF Safety Control Relay provides mechanically or mirror contact performance, which are required in feedback circuits for safety applications.
· IEC industrial safety relay · Electronic coils · Mechanically linked contacts as per IEC 60947-5-1 · Red cover and mechanically linked contact symbol on front face · Permanently fixed front mounted auxiliary contact block

AC-12

AC-15

Contacts

Connection Diagrams

Ith [A]

Ie [A]

Main Contacts
40 °C 24/48V 120V 240V 400V 500V 690V

16 6

6

4

3

2

2

Main Contacts

Auxiliary Contacts

Standard Contacts Cat. No.

N.O. N.C.

4

4

700S-EF440C

5

3

700S-EF530C

Adder 16 6
Deck Contacts

6

4

3

2

2

6 2 700S-EF620C

Voltage Codes

The catalog number listed is incomplete. Select a coil voltage from the table below to complete the catalog number. Example 700-EF220KJ.

Voltage(1)

12...20V DC

24V DC

24...60V AC 20...60V DC

48...130V AC/DC 100...250V AC/DC 250...500V AC/DC

Standard AC/DC

--

--

KJ

KY

KD

KN

Low Consumption AC/DC

EQ

--

EJ

--

--

--

Low Consumption/Faster Drop-out DC

--

QJ

--

--

--

--

(1) AC Voltages are a 50/60 Hz.

Accessories
Additional Coil Terminal Block

Description

For Use With

Pkg. Qty.

Cat. No.

Additional Coil Terminal Block · Allows bottom access to the coil terminals in addition to top access

700-EF

10

100-ECT

Functional Markers

Description

For Use With

Functional Markers · 256 markers (16 per card) printable on HTP500 thermal transfer printer and
AMS 500 marking table · 7 x 20 mm (0.276 x 0.787 in)

700-EF

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Pkg. Qty.
16

Cat. No.
100-EFMS 221

Relay and Timer Specifications

Assignment of Contacts
Safety Control Relays with Front-mount Auxiliary Contacts, 8-Pole AC or DC Coil Voltage

53 61 71 81

53 61 71 83

54 62 72 82
A1 13 21 33 43 K1
A2 14 22 34 44
700S-EF440...

54 62 72 84
A1 13 21 33 43 K1
A2 14 22 34 44
700S-EF530...

53 61 73 83
54 62 74 84 A1 13 21 33 43 K1 A2 14 22 34 44
700S-EF620...

Specifications - 700S-EF Relays
See General Specifications - 700-EF Relays on page 217 for additional specifications.

Mechanical Life Electrical Life Standards Compliance Certifications

AC-15 (240V, 3 A)

Cat. No. 700S-EF

Aux. Contact (Front-mounted)

[Mil]

20

20

[Mil]

1.5

1.5

UL 508, CSA C22.2 No. 14, EN/IEC 60947-1, -5-1, Meets the material restrictions for European Directive 2002/95/EC - EU-RoHS

cULus Listed , CE Marked, CCC Certified

Conductors

Cross Sections, Screw Type Terminals

700-EF/ 700S-EF

Conductor Cross Sections--Main Contacts Terminal Type

1 conductor 2 conductors 1 conductor 2 conductors

[mm2] [mm2] [mm2] [mm2]

Recommended torque

[N·m]

Cross Section per UL/CSA

[AWG]

Recommended torque

[lb·in]

Conductor Cross Sections- Coil and Auxiliary Contact Terminal Type

1 conductor 2 conductors 1 conductor 2 conductors

[mm2] [mm2] [mm2] [mm2]

Recommended torque

[N·m]

Cross Section per UL/CSA

[AWG]

Recommended torque

[lb-in]

(1) Pozidriv No. 2 / Blade No. 3 screw

(1)
0.75...6 0.75...6 1...6 1...6
1.5 16...10
13
(1)
0.75...2.5 0.75...2.5 1...2.5 1...2.5
1.2 18...14
11

222

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

Approximate Dimensions

Dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.

Mounting Position for 700S-EF Relays

Position 2

+30° -30°

Position 4

Position 3

Position 1

Position 1 ± 30°

Position 5

700S-EF Relays

700S-EF Relays with Standard Coils and Front-mounted Auxiliary Contact

6 (0.24)

45 (1.77)

110.5 (4.35) 71 (2.80)
5.5 (0.22)

80 (3.15)

35 mm EN/IEC 60715

5.5 (0.22)

43 (1.69)

10 (0.39)
For relays with QJ coils, add 20 mm (0.79 in.) to the depth

700S-EF Relays with Low-consumption Coils and Front-mounted Auxiliary Contact

6 (0.24)

45 (1.77)

110.5 (4.35) 71 (2.80)
5.5 (0.22)

80 (3.15)

35 mm EN/IEC 60715

5.5 (0.22)

43 (1.69)

10 (0.39)
For relays with QJ coils, add 20 mm (0.79 in.) to the depth

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

223

Relay and Timer Specifications
Safety Relay Circuit With 5 Safety Outputs
· Use for E-stop control. E-stop will work properly if any one fault occurs (a fault could be one welded contact or one undesired open connection such as a loose wire).
· High output switching capability and long contact life. · Circuit complies with EN 954 categories 1, 2, 3, 4. · Helps prevent restart of the 5 safety outputs if there is a single fault anywhere in the system. · Use (3) 700S-EF relays and this diagram to construct the circuit
Start
E
Push To Stop Pull To Reset

(5) Output Circuit (3 Relays, 17 Terminal Blocks)

Included in factory wired units E
E
LOAD 1
LOAD 2 LOAD 3 LOAD 4 LOAD 5

224

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

700-K Miniature Control Relays
· IEC compact industrial relay · IP2X Finger Protection · Bifurcated contacts for low-level signals · Optional integrated coil protection diode

4-Pole AC or DC Coil Voltage

AC-12

AC-15 (B600)

Ith [A]

Ie [A]

Connection Diagrams

40 °C 60 °C 24/48V 120V 240V 400V 500V 600V 690V

Contacts

Pkg. Qty.(2) Cat. No.

N.O. N.C.

4

0

1

700-K40E-

10 6 3

3

2

1

1

0.6 0.6

3

1

1

700-K31Z-

2

2

1

700-K22Z-

1+1L (1) 1+1L 1

700-KL22Z-

(1) 1L = Late Break N.C. / Early Make N.O. (2) May be ordered in package quantities of 20. Add letter M to the end of the cat. no. Example: 700-K40E-ZJM.

 Coil Voltage Codes

The cat. no. as listed is incomplete. Select a coil voltage code from the table below to complete the cat. no. Example: 230V, 50/60 Hz: Cat. No. 700K40E- becomes Cat. No. 700-K40E-KF. For other voltages, consult your local Rockwell Automation sales office or Allen-Bradley distributor.

For Screw Type Terminal Versions

[V] 12 24 110 120 125 220 230 240 250 400 440 480 525 600

AC, 50 Hz

-- -- D

-- -- -- -- -- -- -- B

-- VC --

AC, 60 Hz

------ D

-- -- -- -- -- -- -- B

-- VC

AC, 50/60 Hz

-- KJ -- -- -- -- KF KA -- KN -- -- -- --

Standard Standard diode

ZQ ZJ ZD -- ZS ZA -- -- ZT -- -- -- -- -- DC
-- DJ -- -- -- -- -- -- -- -- -- -- -- --

For Spring Clamp Type Terminal Versions

AC, 50 Hz

-- -- D

-- -- -- -- -- -- -- -- -- -- --

AC, 60 Hz

------ D

-- -- -- -- -- -- -- -- -- --

AC, 50/60 Hz

-- KJ -- -- -- -- KF -- -- -- -- -- -- --

Standard Standard diode

-- ZJ ZD -- -- -- -- -- -- -- -- -- -- --
DC -- DJ -- -- -- -- -- -- -- -- -- -- -- --

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

225

Relay and Timer Specifications

Assignment of Contacts
Device Combinations in Accordance with IEC 60947-1 / -4-1 Table valid for: AC / DC = 0.85...1.1 x Us, Tamb. = -25 °C...+60 °C, normal position (horizontal rail mounting). Also valid for 700-KR relays and 100-KR auxiliary contacts. (3)

Auxiliary Contact Blocks

Cat. No.

Circuit Diagram

Control

Front Mounting

100-KFA02E

51 61 52 62

AC/DC

100-KFA11E

53 61 54 62

AC/DC

100-KFA20E

53 63 54 64

AC/DC

100-KFA04E 100-KFA13E

51 61 71 81 52 62 72 82 53 61 71 81 54 62 72 82

AC/DC AC/DC

100-KFA22Z

53 83 61 71 54 84 62 72

AC/DC

100-KFA31Z

53 73 83 61 54 74 84 62

AC/DC

100-KFA40E

53 63 73 83 54 64 74 84

AC/DC

(1) Tamb. max. +40 °C (2) Tamb. max. +40 °C and only allowed for coil voltage 24V DC or 230V AC (3) For other operating limits, please contact our technical consultant.

Control Relays 700-K (AC and DC Control)

700-K22Z-

700-K31Z-

700-K40E-

A1 13 43 21 31

A1 13 33 43 21

A1 13 23 33 43

A2 14 44 22 32

A2 14 34 44 22

A2 14 24 34 44

--

31Z + 02E = 33Y (1)

40E + 02E = 42Y

22Z + 11E = 33Y

31Z + 11E = 42Y

40E + 11E = 51Y

22Z + 20E = 42Y

31Z + 20E = 51Y

40E + 20E = 60Y

--

--

40E + 04E = 44Y (1)

--

31Z + 13E = 44Y (1)

40E + 13E = 53Y

--

31Z + 22Z = 53Y (1)

40E + 22Z = 62Y

--

--

40E + 31Z = 71Y (2)

22Z + 40E = 62Y

31Z + 40E = 71Y

40E + 40E = 80Y

700-KL22Z-
A1 13 47 21 35 A2 14 48 22 36
-- L22Z + 11E = L33Y L22Z + 20E = L42Y
-- -- -- -- L22Z + 40E = L62Y

226

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

Auxiliary Contact Blocks

Photo

Description

Connection Diagrams

For Use With Pkg. Qty.
(1)

Screw Type Terminals

Spring Clamp Terminals

N.O. N.C.

Cat. No.

Cat. No.

51 61

100/104-K,

0

2

700-K

1 100-KFA02E 100-KRFA02E

52 62

Front-mounted auxiliary contacts · Auxiliary Contact Blocks · 2- and 4-pole versions · Choice of contact configurations · Snap on, no tools required · Electronic-compatible bifurcated contacts
for signals down to 15V / 2 mA

53 61
1
54 62
53 63
2
54 64
51 61 71 81
0
52 62 72 82
53 61 71 81
1
54 62 72 82
53 83 61 71
2
54 84 62 72
53 73 83 61
3
54 74 84 62

1

100/104-K, 700-K

1 100-KFA11E

100-KRFA11E

0

100/104-K, 700-K

1 100-KFA20E

100-KRFA20E

4

100/104-K, 700-K

1 100-KFA04E

100-KRFA04E

3

100/104-K, 700-K

1 100-KFA13E

100-KRFA13E

2

100/104-K, 700-K

1 100-KFA22Z

100-KRFA22Z

1

100/104-K, 700-K

1 100-KFA31Z

100-KRFA31Z

53 63 73 83
4
54 64 74 84
(1) May be ordered in package quantities of 10. Add letter M to the end of the cat. no. Example: 100-KFA02EM.
Control Modules

0

100/104-K, 700-K

1 100-KFA40E

100-KRFA40E

Photo

Description

Mechanical Interlock · For interlocking of two adjacent contactors · No added width to contactor assembly · Front mount plug-in type · Optional auxiliary contact blocks and suppressor modules mount
onto the interlock

24...48V AC

RC Suppressor

110...280V AC

380...480V AC

Surge Suppressor · Plug-in type · Limits surge voltage on
coil drop-off

MOV Suppressor

12...55V AC, 12...77V DC
56...136V AC, 78...180V DC
137...277V AC, 181...250V DC

Diode Suppressor

12...250V DC

(1) May be ordered in package quantities of 10. Add letter M to the end of the cat. no. Example: 100-KFSC50M.

Connection Diagrams

For Use With Pkg. Qty.

Cat. No.

100/104-K/KR,
700-K/- KR

1 100-KMCH

100/104-K/KR,
700-K/- KR
100/104-K/KR,
700-K/- KR
100/104-K/KR,
700-K/- KR

1 (1) 100-KFSC50 1 (1) 100-KFSC280 1 (1) 100-KFSC480 1 (1) 100-KFSV55
1 (1) 100-KFSV136
1 (1) 100-KFSV277
1 (1) 100-KFSD250

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

227

Relay and Timer Specifications

Accessories
Photo

Description
Label Sheet 105 self-adhesive paper labels each, 6 x 17 mm

Snap-In Marker Card

Pkg. Qty.

Cat. No.

10

100-FMS

5

1492-M6X12

228

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

IEC Specifications - 700-K... Relays

AC-12 Rated Thermal Current Ambient temperature 40°C

Ith

24...240V

230...500V

230...690V

Ambient temperature 60°C

Ith

24...240V

230...500V

230...690V

AC-15/B600 Switching of Solenoids and contactors

Ie

24V

48V

120V

230V

240V

400V

480V

500V

600V

690V

Short-circuit Protection

Fuse gG

Min. Switching Capacity 15V

Resistance and Power Dissipation

Main current circuit resistance, 1 pole

Power dissipation, 4 poles

Total power dissipation

AC control, warm

DC control, warm

Lifespan

Mechanical

Electrical AC-15 (240V / 2 A)

Weight

AC control

DC control

Load Carrying Capacity per UL/CSA

Rated voltage

AC

Continuous rating

40 °C

Switching capacity

AC

Rated voltage

DC

Switching capacity

DC

[A] [A] [A]
[A] [A] [A]
[A] [A] [A] [A] [A] [A] [A] [A] [A] [A]
[A]
[mA]
[m] [W]
[W] [W]
[Mio. op.] [Mio. op.]
kg (lbs.) kg (lbs.)
[V] [A] [A] [V] [A]

Relay and Timer Specifications

700-K 10

10 10 10
6 6 6
3 3 3 2 2 1.2 1 1 0.6 0.6
10
2
6.5 2.6
4.4 5.2
15 0.7
0.16 (0.35) 0.2 (0.44)
max. 600
B 600 max. 600
Q 600

700-KR 6

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

229

Relay and Timer Specifications

DC-13/Q600 1 pole

24V

[A]

48V

[A]

110V

[A]

125V

[A]

220V

[A]

250V

[A]

400V

[A]

440V

[A]

600V

[A]

Cross Sections

Conductor Cross Sections - Main Contacts, Auxiliary Contacts, and Coil Terminals

700-K

Terminal type

Fine stranded with ferrule (1) Conductor [mm2] (2) Conductors [mm2]

Solid or coarse stranded

(1) Conductor [mm2] (2) Conductors [mm2]

Recommended torque
Cross section per UL/CSA
Recommended torque
(1) Pozidriv No. 2 / Blade No. 3 screw (2) Use same cross sections (3) Stranded wire only

[Nm] [AWG] [lb-in]

(1)
0.75...2.5 0.75...2.5
1...4 1...2.5 + 1...4
1.2 18...12 (2)
10.6

700-K
2.3 1 0.55 0.55 0.27 0.27 0.15 0.15 0.1
700-KR
0.50...2.5 0.50...2.5 0.75...2.5 (3) 0.75...2.5 (3)
-- 18...14 (3)
--

230

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Coil Data
Operating Limits AC control 50 Hz, 60 Hz, 50/60 Hz
DC control
Coil Consumption AC control 50 Hz, 60 Hz, 50/60 Hz
DC control Operating Times AC With RC module DC With integrated diode With external diode

pick-up dropout pick-up dropout
pick-up hold-in pick-up hold-in
closing delay opening delay opening delay closing delay opening delay closing delay opening delay

[x Us] [x Us] [x Us] [x Us]
[VA/W] [VA/W]
[W] [W]
[ms] [ms] [ms] [ms] [ms] [ms] [ms]

Relay and Timer Specifications
700-K
0.85...1.1 0.2...0.75 0.8...1.1 9, 12, 24, 110V DC: 0.7...1.25 0.1...0.75
35/32 5/1.8 cold 3.0, warm 2.6 cold 3.0, warm 2.6
15...40 15...33 15...28 18...40 6...12 8...12 35...50

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

231

Relay and Timer Specifications
Dimensions - 700-K... Relays
Approximate dimensions are shown in millimeters. To convert millimeters to inches multiply by 0.0394. Dimensions are not intended to be used for manufacturing purposes.

(mm)

25° 25°

180°

50 56 54

35

4

35.2

45

49

79

12 *) *) -Minimum distance to grounded parts or walls

232

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Solid-state Relays
Product Overview

Relay and Timer Specifications

Bulletin No. Type
Features
Load Type
Load Voltage Range Load Current Max. (Continuous)
Max. Leakage Current to Load
Zero Cross Load Switching Equivalent Electromechanical Relay Contact Arrangement
Rated Control (Input) Voltage
LED Indicator Mounting Method Dielectric Strength Certification Max. Ambient Operating Temperature Page

700-SA

700-SC

Tube Base, Socketed

Miniature, Ice Cube Socketed

Compatible with 700-HN100, 125,108, and 204 socket, LED Compatible with 700-HN103 or 128 socket, LED Status, and Zero-

status, zero-cross switching

cross AC Switching Options

AC (47...63 Hz)

DC

AC (47...63 Hz)

DC

75...264V AC

3...125V DC

75...264V AC

3...52.8V DC or 3...125V DC

5 A

3 A

3 A

3 A @ 48V DC or 2 A @ 110V DC

5 mA @ 100V, 10 mA @ 200V 5 mA @ 125V

5 mA @ 100V AC

10 mA @ 200V AC, 5 mA @ 50V DC or 0.1 mA @ 100V DC

Yes

Not Applicable

Yes (optional)

Not Applicable

Form A

Form A

5...24V DC
Yes Panel or DIN with socket 1500V AC, 50/60 Hz, 1 min. cURus, CE, VDE -30...+80 °C (no condensation) 235

5...24V DC, 100...110V AC, 200/220V AC

5...24V DC

Yes (optional)

Yes (optional for 48V DC)

Panel or DIN with socket

1500V AC, 50/60 Hz, 1 min.

cURus, CE, VDE

-30...+80 °C (no condensation)

240

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

233

Relay and Timer Specifications
Product Overview

Bulletin No. Type Features (1)

700-SF
Square Base, Socketed
Compatible with 700-HN116 socket, LED status, zero-cross AC switching

Load Type AC (47...63 Hz) DC

Load Voltage Range

75...264V AC

3 ... 52.8V DC

Load Current

Max.

3 A

(Continuous)

Max. Leakage

Current to

5 mA @ 100V AC, 10 mA @ 200V AC

5 mA @ 50V DC

Load

Zero Cross

Load

Yes

Switching

Not Applicable

Equivalent Electromecha nical Relay Contact Arrangement

Form A

Rated Control

(Input)

4V DC or 24V DC

Voltage

LED Indicator Yes

Mounting Method

Panel or DIN with socket

Dielectric Strength

1500V AC, 50/60 Hz, 1 min.

Certification cURus, CE, VDE

Max. Ambient Operating -30...+80 °C (no condensation) Temperature

Page

245

(1) See Solid-state Relay Glossary on page 235 for term definitions.

700-SH Hockey Puck Panel/DIN Mount, High Current, Protective Cover, LED Status
AC (47...63 Hz) 3...60V DC
3...50V DC, 24...265V AC 42...530V AC, 42...265V AC, 42...660V AC
10 A/100 A
<3 mA

700-SK

Slim Line, Socketed

Compatible with 700-HN121 socket. Supports Input (sensor) module or Output (SSR) module

Output Module

Input Module

AC (47...63 Hz)

DC

AC (47...63 Hz) DC

75 ... 264V AC

4 ... 60V DC, 40 ... 200V DC

Field Input: 60... Field Input:

264V AC

6.6... 32V DC

2 A

2 A @ 60V, 1.5 A @ 200V

Supply Current: 0.1...100 mA

Supply Current: 0.1...100 mA

1.5 mA

1 mA

5 A

5 A

Yes

Yes (optional) N/A

No

N/A

Form A

Form A

3...32V DC, 4...32V DC, 80...130V AC, 20...260V AC 20...280V AC/22...48V DC

5... 24 V DC

Yes

Yes

Panel without heat sink, Panel, or DIN with heat sink

Panel or DIN with socket

>4000V AC RMS

4000V AC, 50/60 Hz, 1 min.

cURus, CE, CSA

cURus, CE, TÜV

-20...+70 °C (no condensation) -30...+80 °C (no condensation)

249

258

234

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

Solid-state Relay Glossary

Terms Insulation Circuit functions Input
Output

Meaning

Basic insulation

Insulation for basic protection from electric shock (IEC950 1.2.9.2)

Supplemental insulation

Independent insulation that is provided outside of basic insulation to protect from electric shock when the basic insulation breaks down (IEC950 1.2.9.3)

Reinforced insulation

A single-layer of insulation (IEC950 1.2.9.5) that provides the same protection from electric shock as double insulation (insulation including both basic and supplemental insulation) according to conditions stipulated in IEC950 standards

Zero cross circuit

A circuit that starts operation with the AC load voltage at close to zero-phase.

Trigger circuit

A circuit for controlling the triac or thyristor trigger signal, which turns the load current ON and OFF.

Isolated input circuit

If the external circuit is prone to generating noise, or if wires from external sources are prone to the influence of inductive noise, in order to prevent malfunctions due to noise, it is necessary to electrically isolate internal circuits and external circuits (output circuits). An isolated input circuit is a circuit that isolates inputs and outputs by using components that are not connected electrically but that can transmit signals, such as contact relays or photocouplers.

Photocoupler

A component that runs the electric signal into a light emitter (for example, LED), changes it to a light signal, and then returns it to an electric signal using a photoelectric conversion element, such as a photo transistor. The space that is used for transferring the light signal is isolated thus providing good insulation and a high propagation speed.

Rated voltage

The voltage that serves as the standard value of an input signal voltage

Pickup (must-operate) voltage Minimum input voltage when the output status changes from OFF to ON.

Input impedance

The impedance of the input circuit and the resistance of current-limiting resistors used. Impedance varies with the input signal voltage in case of the constant current input method.

Operating voltage

The permissible voltage range within which the voltage of an input signal voltage may fluctuate.

Dropout (Reset) voltage

Maximum input voltage when the output status changes from ON to OFF.

Input current

The current value when the rated voltage is applied.

Load voltage

This is the effective value for the power supply voltage that can be used for load switching or in the continuous-OFF state.

Maximum load current (continuous)

The effective value of the maximum current that can continuously flow into the output terminals under specified cooling conditions (i.e., the size, materials, thickness of the heat sink, and an ambient temperature radiating condition).

Leakage current

The effective value of the current that can flow into the output terminals when a specified load voltage is applied to the SSR with the output turned OFF.

Output ON voltage drop

The effective value of the AC voltage that appears across the output terminals when the maximum load current flows through the SSR under specified cooling conditions (such as the size, material, and thickness of heat sink, ambient temperature radiation conditions, etc.).

Minimum load current (continuous)

The minimum load current at which the SSR can operate normally.

Snubber circuit

A circuit consisting of a resistor R and capacitor C, which prevents faulty ignition from occurring in the SSR triac by suppressing a sudden rise in the voltage that is applied to the triac.

Semiconductor output

This is a generic name for semiconductors such as the thyristor, triac, power transistor, and power MOS FET. In

element (switching element) particular, triacs are often used in SSRs because they allow switching to be performed with one element.

Repetitive peak OFF-state voltage (VDRM)

This is a rating for an output semiconductor that used in an SSR for AC loads.

Collector-emitter voltage (VCEO)

This is a rating for an output semiconductor that used in an SSR for DC loads.

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

235

Relay and Timer Specifications

Terms Characteristics Others

Meaning

Operating (pick-up) time

A time lag between the moment a specified signal voltage is imposed to the input terminals and the output is turned ON.

Release (drop-out) time

A time lag between the moment the imposed signal input is turned OFF and the output is turned OFF.

Insulation resistance

The resistance between the input and output terminals or I/O terminals and metal housing (heat sink) when DC voltage is imposed.

Dielectric strength

The effective AC voltage that the SSR can withstand when it is applied between the input terminals and output terminals or I/O terminals and metal housing (heat sink) for more than 1 minute.

Ambient temperature and humidity (operating)

The ranges of temperature and humidity in which the SSR can operate normally under specified cooling, input/output voltage, and current conditions.

Storage temperature

The temperature range in which the SSR can be stored without voltage imposition.

Inrush current resistance

A current, which can be applied for short periods of time to the electrical element.

Counter-electromotive force Extremely steep voltage rise which occurs when the load switched or turned OFF.

Recommended applicable load

The recommended load capacity which takes into account the safety factors of ambient temperature and inrush current.

Bleeder resistance

The resistance connected in parallel to the load in order to increase apparently small load currents, so that the ON/OFF of minute currents functions normally. (It is also used to shunt leakage currents.)

Solid-state Relay Switching Capacity

Solid-State

Equivalent EM Relay Type Relay Contact
Configuration

700-SA

Form A

700-SC

Form A

700-SF 700-SH *

Form A Form A

700-S KO

Form A

Load Voltage

Zero-Cross

Load

Maximum AC an d DC Switching Capability

Switching 1 mA 10 mA 50 mA 100 mA 1 A 3 A 5 A 10 A 2 0 A 25 A

De vice

30 A

35 A

AC

Yes

Triac

DC

N/A Transistor

AC

Yes

Triac

DC

N/A Transistor

(2 A)

AC

Yes

Triac

DC

N/A Transistor

AC

Yes

Thyristor or Triac

DC

N/A Transistor

AC

Yes

Triac

(2 A)

DC

N/A Transistor

100 A

IMPORTANT * Requires a heat sink to reach maximum current value.

236

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

700-SA Tube Base Relays

· 5 A (resistive) max. continuous load (output) current · 264V AC or 125V DC max. load voltage options · Photocoupler isolation between control and load voltage · LED indicator (standard) for input/logic ON/OFF status monitoring · 700-HN100, -HN125, -HN 202, or -HN108 specialty socket compatible · 700-HT2 timing module

Input-to-Output Isolation Method

Zero Cross Function

Status Indicator

Photocoupler

Yes Yes
Not Applicable

Output (Load) Max. Continuous Current and Rated Voltage Range
5 A @ 100...240V AC (47...63 Hz)
3 A @ 5...110V DC

Rated Input (Control) Voltage
5...24V DC

Cat. No. 700-SAZY5Z25 700-SANY3Z25

Accessories - 700-SA Relays

Photo

Description

Pkg. Quantity 10

Cat. No. 700-HN100

Screw Terminal Tube Base Socket -- Panel or DIN Rail Mounting; Guarded Terminal Construction. 8 Pin for use with DPDT 700-HA Relays.

10 Specialty Socket 8 Pin back wired socket with solder terminals
10
Screw Terminal Tube Base Socket -- Panel or DIN Rail Mounting; Open Style Construction. 8 Pin for use with DPDT 700-HA Relays. No retainer clip required.

10 DIN (#3) symmetrical hat rail 35 x 7.5 x 1 m

Pre-Printed Identification Tags -- contains 10 sheets of pre-printed and blank tags. Each sheet contains 10 13 sets of the markings CR...9CR, TR...9TR, M...9M, F, R, 1S, and 117 blank tags. Tags are peel-off with sticky backing for easy placement on relays.

Blank Identification Tags -- contains 10 sheets of blank identification tags for customer specialized

10

printing. Each sheet contains 546 blank tags. Tags are peel-off with sticky backing for easy placement on

relays.

10 Retainer Clip for Sockets with 700-SA AND 700-HB Relays. Secures relay in socket.

10
8-Pin Socket -- Can Be Used With or Without Timing Module or Surge Suppressor. Screw Terminal Tube Base Sockets -- panel or DIN Rail mounting. Guarded terminal construction. Used with DPDT 700-HA Relays.

700-HN108 700-HN125
199-DR1 700-N40 700-N41 700-HN158 700-HN204

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

237

Relay and Timer Specifications

Specifications - 700-SA Relays
Control/Input Ratings

Cat. No.
700-SAZY5Z25 700-SANY3Z25

Rated Control Voltage
5...24V DC

Max. Operating Control
Voltage Range
4...32V DC
4...30V DC

Max. Reverse Control Voltage
-32V DC
-30V DC

Impedance
15 mA max. (1) 1.5 k (+20% -10%)

Control Voltage Levels Pick-up Voltage Drop-out Voltage

4V DC max.

1V DC min.

Load/Output Ratings

Cat. No.
700-SAZY5Z25 700-SANY3Z25

Rated Load Voltage
100...240V AC 5...110V DC

Maximum Load Voltage Range
75...264V AC 3...125V DC

Continuous Load Current (Resistive) [A]

Min.

Max. (2)

0.1

5.0

0.1

3.0

Max. Inrush Current (3)
80 A, @ 50/60 Hz for 1 cycle
12 A (10 ms)

Characteristics

Description

Cat. No. 700-SAZY5Z25

Cat. No. 700-SANY3Z25

Load Switching Method/Device Pick-up Time Drop-out Time

Triac 1/2 cycle of load power source cycle time (4) + 1 ms max. 1/2 cycle of load power source cycle time (4) + 1 ms max.

Transistor 0.5 ms max. 2.5 ms max.

Output ON Voltage Drop

1.6V (RMS) max.

1.5V max.

Output Leakage Current

5 mA max. (at 100V AC); 10 mA max. (at 200V AC)

5 mA max. (at 125V DC)

Output VDRM VCEO (V)
Output di/dt (V/uS)

600

150

50

--

Output dv/dt (V/uS) Output I2t (A2S)

500

--

41.6

--

Output Tj (ºC) Max.

125

150

Insulation Resistance

100 M min. (at 500V DC)

Dielectric Strength

1500V AC, 50/60 Hz for 1 min

Vibration Resistance (Max.) Shock Resistance (max.)

10...55 Hz, 1.5 mm double amplitude (10 G) 1000 m/s2 (100 G)

Ambient Temperature

Operating Storage

­30...+80 °C (­22...+176 °F) with no icing or condensation ­30...+100 °C (­22...+212 °F) with no icing or condensation

Ambient Humidity

45...85% (no condensation)

Standards Compliance

UL 508, CSA C22.2 No. 14, EN 60947-1, -4-3

Certifications

cURus Recognized (File No. E96956, Guide NMFT2/NMFT8), CE Marked, VDE Certified

Weight

Approx. 70 g

(1) With constant current input system. SSR input impedance varies with a change in input (control) voltage. (2) See the following graph"Load Current Vs. Ambient Temperature Characteristics"for additional load current details. (3) If the SSR operation is continuous ON/OFF, this value should be reduced by 50%. See"Inrush Current Resistivity"graph. (4) 60 Hz full cycle time = 16.6 ms, 50 Hz full cycle time = 20 ms.

Load Current [A]
-30 -20
0 20 40 60 80 100
Inrush Current [A. Peak]
10 30 50 100 200 500 1000 5000

Load Current vs. Ambient Temperature Characteristics
700-SA
700-SAZY5Z25 5 4
700-SANY3Z25 3 2
1 0

Inrush Current Resistivity (1)

700-SA

80

70 60

50

40 700-SAZY5Z25
30

20

10

700-SANY3Z25

0

Ambient Temperature [° C]

Energizing Time [ms]

(1) Inrush current resistivity is the ability of an SSR to withstand a large surge current for a short period. Surges are considered non-repetitive (max. repeatability once every 5 seconds). Keep the inrush current to half the rated value if it

occurs repetitively. Exceeding the non-repetitive inrush current will damage the SSR.

238

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Terminal Arrangement (Bottom View)

Relay and Timer Specifications

Load
Load power supply

Load Input

Input voltage Note: The plus and minus symbols shown in parentheses
are for DC loads.
Basic Application Considerations
High Density Mounting of Multiple Solid-state Relays (SSRs)
If multiple SSRs are installed side by side,, the outer case wall of the SSR serves to dissipate heat. Install the relays so that they are adequately ventilated. If poor ventilation is unavoidable, reduce the load current to half.
Protective Component
When controlling AC inductive loads, connect an inrush/surge absorbing device (varistor) across the SSR load terminals. If the SSR has built- in surge suppression (s 700-SE and 700-SH) and additional surge suppression is required, connect the varistor across the terminals of the load device. Select a varistor that meets the conditions of the load voltage that is outlined in the table.

Load Voltage 100...120V AC 200...240V AC 380...480V AC

Varistor Voltage [V] 240...270 440...470 820...1000

Varistor Surge Resistance 1000 A min.

TIP For additional details on solid-state relays, see the Solid-State Relay Application Guide, publication 700-AT001.

For a DC inductive load, a diode should be connected parallel to the load to absorb the counter electromotive force (OFF) of the load.

Input

SSR

Load

Load power supply

EMC Directive Compliance
1. AC-switching models comply with EMC Directives under the following conditions:
3 m max. Load
Input 700-SA Output

Varistor: 470 V, 0.6 W Film Capacitor: 1µ F, 250 VAC

Varistor Film Capacitor

· Connect a varistor between the output terminals. · Connect a film capacitor to the load power supply. · The input cable must be less than 3 m.

2. DC-switching models comply with EMC Directives under the following conditions:
Less than 10 m Load
Input 700-SA Output

· The input cable must be less than 10 m.
Dimensions - 700-SA Relays
All units in millimeters unless otherwise indicated. To convert millimeters to inches multiply by 0.0394. Dimensions are not intended to be used for manufacturing purposes. 700-SA (1)

+

35 max.

+

35

52.5

max.

max.

(1) 700-SA is compatible with Cat. Nos. 700-HN100, -108, -125, and -204 (sockets).

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

239

Relay and Timer Specifications

700-SC Ice Cube Relays

· 3 A (resistive) max. continuous load (output) current · 264V AC, 48V DC or 125V DC max. load voltage options · 5...24V DC or 110/220V AC control (input) voltage options · LED indicator (optional) for input/logic On/Off status monitoring · 700-HN103, 700-HN104, or 700-HN128 socket compatible · Compatible with 700-AT1 or 700-AT2 timer modules

Input-to-Output Isolation Method

Zero Cross Function

Status Indicator

Photocoupler
Phototriac Photocoupler Phototriac Photocoupler

Yes Yes
No Not Applicable Yes No
No Not Applicable

Output (Load) Max. Continuous Current and Rated Voltage Range 3 A @ 100...240V AC(1)
2 A @ 100...240V AC(1)
3 A @ 100...240V AC (1) 3 A @ 4...48V DC
3 A @ 100...240V AC (1)
3 A @ 4...48V DC 2 A @ 5...110V DC

Rated Input (Control) Voltage 5...24V DC 100/110V AC 200/220V AC 24V DC 5...24V DC 4...24V DC 24V DC 4...24V DC 5...24V DC

Cat. No.
700-SCZY3Z25 700-SCZY2A1 700-SCZY2A2 700-SCTY3Z24 700-SCNY3Z25 700-SCZN3Z26 700-SCTN3Z24 700-SCNN3Z26 700-SCNN2Z25

(1) 47...63 Hz .

Accessories - 700-SC Relays

Photo

Description

Pkg. Quantity Cat. No.

Screw Terminal Socket -- Panel or DIN Rail Mounting; Guarded Terminal Construction.Ith = 10 A per pole. 14-blade miniature socket for use with 700-SC Relays.

10

700-HN103

Screw Terminal Socket -- Panel or DIN Rail Mounting; Guarded Terminal Construction Ith =

10 A per pole. 14-blade miniature socket for use with 700-SC relays. This socket has coil and contact separation and the ability to plug in optional plug-in modules (700-A__ accessories: LED,

10

Surge Suppression, Timing Modules)

700-HN104

Screw Terminal Base Socket -- Panel or DIN Rail Mounting; Open-Style Construction Ith = 10 A per pole. 14-blade miniature socket for use with 700-SC Relays.

10

700-HN128

DIN (#3) symmetrical hat rail 35 x 7.5 x 1 m

10

199-DR1

240

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

Photo

Description

Pkg. Quantity

Pre-Printed Identification Tags -- contains 10 sheets of pre-printed and blank tags. Each sheet contains 13 sets of the markings CR...9CR, TR...9TR, M...9M, F, R, 1S, and 117 blank tags. 10 Tags are peel-off with sticky backing for easy placement on relays.

Blank Identification Tags -- contains 10 sheets of blank identification tags for customer specialized printing. Each sheet contains 546 blank tags. Tags are peel-off with sticky backing for 10 easy placement on relays.

Retainer Clip for Cat. Nos. 700-HN103, -HN104, and -HN128 Sockets with 700-HC Relays. Secures relay in socket.

10

Cat. No. 700-N40
700-N41
(1)
700-HN114

(1) Series B retainer clip must be used with 700-SC.
Specifications- 700-SC Relays

Control/Input Ratings

Cat. No. 700-SCZY3Z25

Rated Control Voltage
5...24V DC

Max. Operating Control Voltage
Range
4...28V DC

Max. Reverse Control Voltage [V]
-28.8

Impedance 15 mA max. (1)

Control Voltage Levels Pick-up Voltage Drop-out Voltage

4V DC max.

1V DC min.

700-SCZY2A1

100/110V AC

75...125V AC

NA

41 k ±20%

75V AC max.

20V AC min.

700-SCZY2A2 700-SCTY3Z24
700-SCNY3Z25

200/220V AC 24V DC
5...24V DC

150...250V AC 19.2...28.8V DC
4...28V DC

NA

72 k ±20%

150V AC max.

40V AC min.

-28.8

2 k ±20%

19.2V DC max.

-28

1.5 k +20%/ -10%
(2)

4V DC max.

700-SCZN3Z26

4...24V DC

3...28V DC

-28.8

700-SCTN3Z24

24V DC

19.2...28.8V DC

-28.8

15mAmax. (1) 2 k ±20%

3V DC max. 19.2V DC max.

1V DC min.

700-SCNN3Z26 700-SCNN2Z25

4...24V DC 5...24V DC

3...28V DC

-28

1.5 k +20%/ -10%
(2)

3V DC max.

-28.8

Load/Output Ratings

Cat. No.

Rated Control Voltage

Max. Load Voltage Range

Continuous Load Current (Resistive) [A]

Min.

Max. (3)

Max. Inrush Current (4)

700-SCZY3Z25

700-SCTY3Z24 700-SCZN3Z26 700-SCTN3Z24

100...240V AC

75...264V AC

0.1

3

45 A (@50/60 Hz,

1 cycle)

700-SCZY2A1 700-SCZY2A2

0.1

2

700-SCNN3Z26 700-SCNY3Z25

4...48V DC

3...52.8V DC

0.1

3

18 A (10 ms)

700-SCNN2Z25

5...110V DC

3...125V DC

0.1

2

10 A (10 ms)

(1) With constant current input circuit system. SSR impedance varies with a change in input (control) voltage. (2) Input impedance attains its maximum at the operating voltage. (3) If the SSR operation is continuous ON/OFF, this value should be reduced by 50%. See"Inrush Current Resistivity"graphs on page 112 for details (4) See Load Current Versus Ambient Temperature Characteristics on page 242 for additional load current details.

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

241

Relay and Timer Specifications

Characteristics

Description

Cat. No. 700-SCZ...

Cat. No. 700-SCT

Cat. Nos. 700-SCNY, 700SCNN3...

Cat. Nos. 700-SCNN2...

Load Switching Method/Device

Triac

Transistor

Pick-up time

1/2 of load power source cycle time (1) + 1 ms max. (DC input)
3/2 of load power source cycle time (1) + 1 ms max. (AC input)

Drop-out time

1/2 of load power source cycle time (1) + 1 ms max. (DC input) 3/2 of load power source cycle time (1) + 1 ms max. (AC input)

1/2 of load power source cycle time (1) + 1 ms max.

2 ms max.

2.5 ms max.

Output On Voltage Drop

1.6V (RMS) max.

1.6V (RMS)

1.5V max.

1.5V max.

Output Leakage Current

5 mA max (@ 100V AC) 10 mA max (@ 200V AC)

2.5 mA max (@ 100V AC) 5 mA max (at 200V AC)

5 mA max (@ 50V DC)

0.1 mA max (@ 100V DC)

Output VDRM, VCEO (V)

600

600

80

80

Output di/dt (A/uS)

50

50

--

--

Output dv/dt (V/uS)

250

250

--

--

Output I2t (A2S)

18

18

--

--

Output Tj (°C) Max.

125

125

150

150

Insulation Resistance

100 M min (@500V DC)

Dielectric Strength

1500V AC, 50/60 Hz for 1 minute

Vibration Resistance (max.) Shock Resistance (max.)

10...55 Hz, 1.5 mm double amplitude (10 G) 1000 m/s2 (100 G)

Ambient Temperature

Operating: -30...+80 °C (-22...+176 °F) with no icing or condensation Storage: -30...+100 °C (-22...+212 °F) with no icing or condensation

Standards Compliance

UL 508, CSA C22.2 No. 14, EN/IEC 60950, EN 50011, EN 61000-6-2, EN/IEC 60947-1, -4-3

Certifications

cURus Recognized (File No. E96956, Guide NMFT2/NMFT8), CE Marked, VDE Certified

Ambient Humidity

Operating: 45...85% (no condensation)

Weight

Approx. 50 g

(1) 60 Hz full cycle time = 16.6 ms, 50 Hz full cycle time = 20 ms
Load Current Versus Ambient Temperature Characteristics

700-SC_ _3...

700-SC_ _2...

5

5

4

4

Load Current [A]
-30 -20
0 20 40 60 80 100
Load Current [A]
-30 -20
0 20 40 60 80 100

3

3

2

2

1 0
Ambient Temperature [° C]

1 0
Ambient Temperature [° C]

242

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

Inrush Current [A. Peak]
10 30 50 100 200 500 1000 5000
Inrush Current [A. Peak]
10 20 30 50 70 100 200 300 500 1000 2000
Inrush Current [A. Peak]
10 20 30 50 100 300 500 1000 3000 5000

Inrush Current Resistivity (1)

700-SCZ....

700-SCT...

50

40

30

20

10 0

700-SCNN3...
30
28 26 24 22 20 18 16 14 12 10 8 6 4 2 0

700-SCNY3

700-SCNN2...
12 10
8 6 4 2 0

Energizing Time [ms]

Energizing Time [ms]

Energizing Time [ms]

(1) Inrush current resistivity is the ability of an SSR to withstand a large surge current for a short period. Surges are considered non-repetitive (max. repeatability once every 2...5 seconds). Keep the inrush current to half the rated value if it occurs repetitively. Exceeding the non-repetitive inrush current will damage the SSR.

EMC Directive Compliance

1. AC-switching models comply with EMC Directives under the following conditions

3 m max. Load
Input 700-SC Output

Varistor: 470 V, 0.6 W Film capacitor: 1µ F, 250 VAC

Varistor

Film capacitor

· Connect a varistor between the output terminals. · Connect a film capacitor to the load power supply. · The input cable must be less than 3 m.

2. DC-switching models comply with EMC Directives under the following conditions
Less than 10 m Load
Input 700-SC Output

· The input cable must be less than 10 m.

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

243

Relay and Timer Specifications

Dimensions - 700-SC Relays
All units in millimeters unless otherwise indicated. To convert millimeters to inches multiply by 0.0394. Dimensions are not intended to be used for manufacturing purposes.

28 max. 21.5 max.
(1) 700-SC is compatible with Cat. Nos. 700-HN103, -HN104, and -HN128 socket.
Basic Application Considerations for 700-SC

36.5 max. 42.5 max.

Terminal Arrangement/ Internal Connections (Bottom View)

1

4

5

8(+)

9 Load 12(­)

Load

13 Input 14

­

+

­

Input voltage +

(+) Load power supply
(­)

Cat. No 700-SC... (1)

Note: The plus and minus symbols shown in parentheses are for DC loads.

High-density Mounting of Multiple Solid-state Relays (SSRs)

If multiple relays are mounted side by side, the outer wall of each SSR works as a radiator. The SSR casing serves to dissipate heat. Install the relays so that they are adequately ventilated. If poor ventilation is unavoidable, reduce the load current by half.
Connection

For DC Load Switching, 700-SC will operate properly if the load is connected to either the positive or negative SSR load terminal.

Protective Component

When controlling AC inductive loads, connect an inrush/surge absorbing device (varistor) across the SSR load terminals. If the SSR has built- in surge suppression (s 700-SE and 700-SH) and additional surge suppression is required, connect the varistor across the terminals of the load device.
Select a varistor that meets the conditions of the load voltage that is outlined in the table below.

Load Voltage [V AC] 100...120 200...240 380...480

Varistor Voltage [V] 240...270 440...470 820...1000

Varistor Surge Resistance 1000 A min.

TIP For additional details on solid-state relays, see the Solid-State Relay Application Guide, publication 700-AT001.

Input

SSR

Load

Load power supply

244

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

700-SF Square Base Relays

· 3 A (resistive) max. continuous load (output) current · 264V AC or 52.8V DC max. load voltage options · 4...24V DC control/input voltage · Photocoupler or phototriac isolation option between control and output voltage · LED Indicator for input/logic ON/OFF status monitoring · 700-HN116 socket compatible

Input-to-Output Isolation Method

Zero Cross Function Status Indicator

Photocoupler Phototriac Photocoupler

Yes

No

Yes

Not Applicable

Output (Load) Max. Continuous Current and Rated Voltage Range
3 A @ 100...240V AC (47...63 Hz)
3 A @ 4...48V DC

Rated Input Control Voltage

Cat. No.

5...24V DC 24V DC 4...24V DC

700-SFZY3Z25 700-SFTY3Z24 700-SFNY3Z25

Accessories-700-SF Relays

Photo

Description

Pkg. Quantity Cat. No.

Screw Terminal Socket -- Panel or DIN Rail Mounting 8-blade miniature socket for use with DPDT HF relays. 10

700-HN116

DIN (#3) symmetrical hat rail 35 x 7.5 x 1 m

10

Pre-Printed Identification Tags -- contains 10 sheets of pre-printed and blank tags. Each sheet contains 13 sets of the markings CR...9CR, TR...9TR, M...9M, F, R, 1S, and 117 blank tags. Tags are peel-off with sticky backing for 10 easy placement on relays.

Blank Identification Tags -- contains 10 sheets of blank identification tags for customer specialized printing. Each sheet contains 546 blank tags. Tags are peel-off with sticky backing for easy placement on relays.

10

Retainer Clip for Cat. Nos. 700-HN103, -HN104, and -HN128 Sockets with 700-HC Relays. Secures relay in socket.

10

(1) 700-SF must use Cat. No. 700-HN114 series B retainer clip.

199-DR1 700-N40 700-N41 700-HN114(1)

Specifications- 700-FS Relays

Control/Input Ratings

Cat. No.

Rated Control Voltage

700-SFZY3Z25 700-SFTY3Z24 700-SFNY3Z25

5...24V DC 24V DC
5...24V DC

Max. Operating Control Voltage Range [V DC]
4...28V DC 19.2...28.8V DC
4...28V DC

Max. Reverse Control Voltage [V]

Impedance

­32

15 mA max. (1)

­28.8

2 k ± 20%

­28.8

1.5 k + 20%/­ 10% (2)

Control Voltage Levels Pick-up Voltage Drop-out Voltage

4V DC max. 19.2V DC max.

1V DC min. 1V DC min.

4V DC max.

1V DC min.

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

245

Relay and Timer Specifications

Load/Output Ratings

Cat. No.

Rated Control Voltage

700-SFZY3Z25 700-SFTY3Z24 700-SFNY3Z25

100...240V AC 4...48V DC

Max. Load Voltage Range
75...264V AC 3...52.8V DC

Continuous Load Current (Resistive) [A]

Min.

Max. (3)

0.1

3

0.1

3

0.1

3

Max. Inrush Current (4)
45 A @ 50/60 Hz, 1 cycle
18 A (10 ms)

Characteristics
Description Load Switching Method/Device Pick-up Time
Drop-out Time Output ON Voltage Drop Output Leakage Current
Output VDRM, VCEO (V) Output di/dt (A/uS) Output dv/dt (V/uS) Output I2t (A2S) Output Tj (°C) Max. Insulation Resistance Dielectric Strength Vibration Resistance (Max.) Shock Resistance (Max.)
Ambient Temperature
Ambient Humidity Standards Compliance Certifications Weight

Cat. No. 700-SFZY3Z25

Cat. No. 700-SFTY3Z24

Triac

Transistor

1/2 cycle of load power source cycle time (5) +1msmax.

1 ms max.

1/2 cycle of load power source cycle time (5) + 1 ms max.

Cat. No. 700-SFNY3Z25
0.5 ms max. 2 ms max.

1.6V (RMS) max.
5 mA max. (@ 100V AC); 10 mA max. (@ 200V AC) 600

2.5 mA max. (@ 100V AC); 5 mA max. (@ 200V AC)
600

1.5V max. 5 mA max. (@ 50V DC) 80

50

50

--

250

250

--

18

18

--

125

125

150

100 M min.(at500VDC)

1,500V AC, 50/60 Hz for 1 min

10...55 Hz, 1.5 mm double amplitude (10 G) 1000 m/s2 (100 G)

Operating: ­30...+80 °C (­22...+176 °F) with no icing or condensation Storage: ­30...+100 °C (­22...=+212 °F) with no icing or condensation 45...85% (no condensation) UL 508, CSA C22.2 No. 14, EN/IEC 60947-1, -4-3, EN/IEC 60950 cURus Recognized (File No. E96956, Guide NMFT2/NMFT8), CE Marked, VDE Certified Approx. 50 g

(1) With constant current input circuit system, SSR impedance varies with a change in input voltage.
(2) Input impedance reaches its maximum at the operating voltage. (3) If the SSR operation is continuous ON/OFF, this value should be reduced by 50%. See the "Inrush Current Resistivity"graphs on page 116 for more details. (4) See"Load Current vs. Ambient Temperature Characteristics"on page 116 for additional load current details. (5) 60 Hz full cycle time = 16.6 ms, 50 Hz full cycle time 20 ms.

IMPORTANT

This data is non-repetitive. Keep the inrush current to half the rated value if it occurs repetitively. Inrush current resistivity is the ability of an SSR to withstand a large surge current for a short period.
Surges are considered non-repetitive (max. repeatability once every 2...5 seconds). Keep the inrush current to half the rated value if it occurs repetitively. Exceeding the non-repetitive inrush current will damage the SSR.

246

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

Load Current [A]
-30 -20
0 20 40 60 80 100
Inrush Current [A Peak]
10 30 50 100 200 500 1000 5000
Inrush Current [A]
10 20 30 50 70 100 200 300 500 1000 2000

Load Current vs. Ambient Temperature Characteristics
700-SF

Inrush Current Resistivity (1) 700-SFZ... 700SFT...

Inrush Current Resistivity (1) 700-SFN...

4

50

30 28

26

3

40

24 22

20

30

18 16

2

14

20

12 10

1

8

10

6

4

2

0

0

0

Ambient Temperature [° C]

Energizing Time [ms]

Energizing Time [ms]

(1) Inrush current resistivity is defined as the ability of an SSR to withstand a large surge current for a short period. Surges are considered non-repetitive (max. repeatability once every 2...5 seconds). Keep the inrush current to half the rated value if it occurs repetitively. Exceeding the non-repetitive inrush current will damage the SSR.

EMC Directive Compliance

1. AC-switching models comply with EMC Directives under the following conditions

3 m max. Load
Input 700-SF Output

Varistor: 470 V, 0.6 W Film capacitor: 1µ F, 250 VAC

Varistor

Film capacitor

· Connect a varistor between the output terminals. · Connect a film capacitor to the load power supply. · The input cable must be less than 3 m.

2. DC-switching models comply with EMC Directives under the following conditions
Less than 10 m Load
Input 700-SF Output

· The input cable must be less than 10 m.

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

247

Relay and Timer Specifications

Dimensions - 700-SF Relays

All units in millimeters unless otherwise indicated. To convert millimeters to inches multiply by 0.0394. Dimensions are not intended to be used for manufacturing purposes.

28 max
21.5 max

36.5 max 42.5 max

Terminal Arrangement/Input Connections (Bottom View)

1

2

3

4(+)

(+) Load

5

Load 6(-)

(-)

7 Input 8

-

+

- Input Voltage +

Notes: 1. The plus and minus symbols shown in parentheses are for DC loads.
2. The coil has no polarity.

IMPORTANT 700-SF is compatible with Cat. No. 700-HN116 socket.

Basic Application Considerations of 700-SF

High-density Mounting of Multiple Solid-state Relays (SSRs)

If multiple SSRs are mounted side by side, the outer case wall of the SSR acts as a radiator. The SSR case serves to dissipate heat. Install the relays so that they are adequately ventilated. If poor ventilation is unavoidable, reduce the load current by half.

Connection

For DC load switching, the Bul. 700-SF SSR will operate properly if the load is connected to either the positive or negative load terminals.

Protective Component to Extend SSR Life

When controlling AC inductive loads, connect an inrush/surge absorbing device (varistor) across the SSR load terminals. If the SSR has built- in surge suppression (700-SE and 700-SH) and additional surge suppression is required, connect the varistor across the terminals of the load device.
Select a varistor that meets the conditions of the load voltage that is outlined in the table.

Load Voltage [V AC] 100...120 200...240 380...480

Varistor Voltage [V] 240...270 440...470 820...1000

Varistor Surge Resistance 1000 A min.

TIP For additional details on solid-state relays, see the Solid-State Relay Application Guide, publication 700-AT001.

For a DC inductive load, a diode should be connected parallel to the load to absorb the counter electromotive force (OFF) of the load.

Input

SSR

Load

Load power supply

248

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

700-SH Hockey Puck Relays

· 100 A max. continuous load (output) current with appropriate heat sink · 264V AC, 530V AC, or 660V AC max. load voltage options · 3...32V DC, 4...32V DC, 80...130V AC, 200...260V AC, 20...280V AC/22...48V DC control (input) voltage options · LED indicator for input/logic ON/OFF status monitoring · Protective cover for added safety

Photo

Input-toOutput Isolation Method
Optocoupler

Zero Cross Function

Status Indicator

Yes

Yes

Yes

No

Yes

Yes

Output (Load) Max. Continuous Current and Rated Voltage Range (1) 10 A @ 42...265V AC 10 A @ 42...265V AC 10 A @ 42...265V AC 10 A @ 42...530V AC 25 A @ 42...530V AC 25 A @ 24...265V AC
25 A @ 24...265V AC 50 A @ 24...265V AC
50 A @ 24...265V AC
50 A @ 42...530V AC 25 A @ 42...660V AC
25 A @ 42...660V AC
50 A @ 42...660V AC 50 A @ 42...660V AC
75 A @ 42...530V AC 75 A @ 42...660V AC 75 A @ 42...530V AC
75 A @ 42...660V AC
100 A @ 42...530V AC 100 A @ 42...530V AC
100 A @ 42...660V AC
100 A @ 42...660V AC
5 A @ 3...60V DC 25 A @ 90...280V AC 50 A @ 90...280V AC

Rated Input Control Voltage

Cat. No.(2)

3...32V DC
80...130V AC
200...260V AC
4...32V DC
4...32V DC
3...32V DC
20...280V AC/ 22...48V DC
3...32V DC
20...280V AC/ 22...48V DC
4...32V DC
4...32V DC
20...280V AC/ 22...48V DC
4...32V DC
20...280V AC/ 22...48V DC
4...32V DC
4...32V DC
20...280V AC/ 22...48V DC
20...280V AC/ 22...48V DC
4...32V DC
20...280V AC/ 22...48V DC
4...32V DC
20...280V AC/ 22...48V DC
3...32V DC
4...20 mA DC
4...20 mA DC

700-SH10JZ24 700-SH10JA12 700-SH10JA22 700-SH10HZ25 (Series B) 700-SH25HZ25 (Series B) 700-SH25GZ24 700-SH25GA24 700-SH50GZ24 700-SH50GA24 700-SH50HZ25 700-SH25VZ25 700-SH25VA24 700-SH50VZ25 700-SH50VA24 700-SH75HZ25 700-SH75VZ25 700-SH75HA24
700-SH75VA24 700-SH100HZ25 700-SH100HA24 700-SH100VZ25 700-SH100VA24 700-SH5FZ24 700-SH25WA25 700-SH50WA25

(1) When used with heat sink. (2) All catalog numbers are Series A unless noted.

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

249

Relay and Timer Specifications

Accessories - 700-SH Relays
Photo

Description

Heat Sink-- Panel or DIN Rail Mount

Pkg. Quantity 1

Cat. No. 700-SN10

Heat Sink-- Panel or DIN Rail Mount

1

700-SN25

Heat Sink-- Panel or DIN Rail Mount

1

700-SN50

Heat Sink-- Panel or DIN Rail Mount

1

700-SN50HC

Heat Sink-- Panel or DIN Rail Mount

1

700-SN50VHC

DIN (#3) symmetrical hat rail 35 x 7.5 x 1 m
Thermal Conductive Pads Plastic Covers -- for DC output version Thermal Adapters - for 100 A Wire

10

199-DR1

50

700-SHCPAD

25

700-SHCOV

10

700-SHTRMA

250

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

Specifications- 700-SH Relays

Control/Input Ratings

Cat. No.

Operating Voltage

700-SH10J...
700-SH_ _ H...
700-SH_ _ G...
700-SH_ _ V... 700-SH_ _ W... 700-SH_ _ F...
(1) When specified heatsink is used.
Output Ratings

3...32V DC 80...130V AC 200...280V AC 4...32V DC 20...280V AC/22...48V DC 3...32V DC 20...280V AC/22...48V DC 4...32V DC 20...280V AC/22...48V DC Current Control 3...32V DC

700-SH5FZ24 700-SH10J... 700-SH10H... 700-SH25G... 700-SH25H... 700-SH25V... 700-SH25W... 700-SH50G... 700-SH50H... 700-SH50V... 700-SH50W... 700-SH75H... 700-SH75V... 700-SH100H... 700-SH100V...
(2) AC unless indicated.

Cat. No.

Input Current @ Max. Voltage 12 mA 13 mA 13 mA 12 mA 20 mA 12 mA 20 mA 12 mA 20 mA 4...20 mA 12 mA

Voltage Level Pickup Voltage
2.75V DC max. 70V AC max. 190V AC max. 4V DC max. 18V AC/DC
2.5V DC -32V DC 3.5V DC 18V AC/DC
-- 3V DC max.

Drop-out Voltage
1.2V DC min. 30V AC min. (1) 90V AC min.
1V DC min. 6V AC/DC 1.2V DC 6V AC/DC 1.2V DC 6V AC/DC
-- 1.0V DC

Load Voltage Range 3...60V DC 42...265V AC 42...530V AC 24...265V AC 42...530V AC 42...660V AC 90...280V AC 24...265V AC 42...530V AC 42...660V AC 90...280V AC 42...530V AC 42...660V AC 42...530V AC 42...660V AC

Applicable Load Current with Heat Sink [A] (2) 0.001...5 A DC 0.15...10 0.15...10 0.15...25 0.15...25 0.15...25 0.15...25 0.15...50 0.15...50 0.15...50 0.15...50 0.15...75 0.15...75 0.15...100 0.15...100

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

251

Relay and Timer Specifications
Characteristics Description
Pick-up Time Drop-out Time Output ON Voltage Drop Output Leakage Current
Insulation Resistance Dielectric Strength Vibration Resistance Shock Resistance
Ambient Temperature
Ambient Humidity Standards Compliance Certifications Weight

Cat. Nos. 700-SH10, 25, 50 (not including 700-SH_ _W)

Cat. Nos. 700-SH75, 100

1/2 of load power source cycle time(DC input) / 1 of load power source cycle time (AC input)

1/2 of load power source cycle time (DC input) / 2 of load power source cycle time (AC input)

1.6V (RMS) max.

<3 mARMS 100M min(@500VDC)

100M min.(at500VDC)

>4000V ACRMS Malfunction: 10...55 Hz, 1.5 mm double amplitude Malfunction: 1000 m/s2

Operating: ­20...+70 °C (­4...+158 °F) with no icing or condensation

Storage: ­40...+100 °C (­40...+212 °F) with no icing or condensation

0...95% no condensing

UL 508, CSA C22.2 No. 14, EN/IEC 60947-1, -4-2, -4-3, EN 61000-6-2, EN 61000-6-4

cURus Recognized (File No. E14843, Guide NPNT2), CSA Certified (File No. 240924)

Approx. 60 g

Approx. 100 g

Pick-up Current Drop-out Current Voltage Drop Leakage Current Insulation Voltage Vibration Resistance Shock Resistance Ambient Temperature Ambient Humidity
Standards Compliance
Certifications Weight

Description

Cat. No. 700-SH_ _W 4.2 mA 4.1 mA
<10V DC @ 20 mA <3 mA
<4000 VRMS Malfunction: 10...55 Hz, 1.5 mm double amplitude
Malfunction: 1000 m/s2 Operating: ­20...+70 °C (­4...+158 °F) with no icing or condensation
0...95% no condensing UL 508, CSA C22.2 No. 14, EN/IEC 60947-1, -4-2, -4-3,
EN 61000-6-2, EN 61000-6-4 cURus Recognized (File No. E14843, Guide NPNT2), CSA Certified (File No. 24024)
Approx. 60 g

Description Pick-up Voltage Drop-out Voltage Activating Frequency Input Impedance Response Time Pick-up @ Vin > 5V Response Time Drop-out On-state Voltage Drop @ Rated Current

Cat. No. 700-SH5FZ24 <3V DC >1V DC <100 Hz 1 k <4000 uS <1 mS <1.5V

252

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

Description Off-state Current Drop @ Rated Voltage Insulation Voltage Vibration Resistance Shock Resistance Ambient Temperature Ambient Humidity Standards Compliance Certifications Weight
Surge Current vs. Ambient Temperature Characteristics

Cat. No. 700-SH5FZ24 <1 mA <1 mA
Malfunction: 10...55 Hz, 1.5 mm double amplitude Malfunction: 1,000 m/s2
Operating: ­20...+70 °C with no icing or condensation 0...95% no condensing
UL 508, CSA C22.2 No. 14, EN/IEC 60947-1, -4-2, -4-3, EN 61000-6-2, EN61000-6-4 cURus Recognized (File No. E14843, Guide NPNT2), CSA Certified (File No. 240924) Approx. 60 g

Inrush current (Apk)

350A 300A 250A 200A 150A 100A
50A 0A 10ms
1200A 1000A
800A 600A 400A 200A
0A 10ms

Surge current resistivity for 700-SH10, 25....

100ms

Energizing time (ms)

1000ms

Surge current resistivity for 700-SH75....

100ms

Energizing time (ms)

1000ms

10000m s 10000m s

Inrush current (Apk)

Inrush current (Apk)

700A
600A
500A
400A
300A
200A
100A
0A 10ms
2000A 1800A 1600A 1400A 1200A 1000A
800A 600A 400A 200A
0A 10ms

Surge current resistivity for 700-SH50....

100ms

Energizing time (ms)

1000ms

Surge current resistivity for 700SH100....

100ms

Energizing time (ms)

1000ms

10000m s 10000m s

Inrush current (Apk)

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

253

Relay and Timer Specifications

Load Current (A)

Load Current (A)

Load current vs. ambient temperature characteristics for 700-SH10.... 12

700-SN50VHC

10

700-SN50HC

700-SN10 700-SN25

8 700-SN50

6

4 No heatsink
2

0

-20

-10

0

10

20

30

40

50

60

70

80

Ambient temperature (ºC)

Load current vs. ambient temperature characteristics for 700-SH50.... 6 0

5 0
4 0 7 0 0 - S N 1 0
3 0

7 0 0 - S N 2 5

7 0 0 - S N 5 0

7 0 0 - S N 5 0 V H C 7 0 0 - S N 5 0 H C

2 0

1 0
0 - 2 0

No heatsink

- 1 0

0

1 0

2 0

3 0

4 0

5 0

6 0

7 0

8 0

Ambient temperature (ºC)

Load current vs. ambient temperature characteristics for 700-SH100.... 120

100

700-SN50

700-SN50HC

700-SN50VHC

80

60
700-SN10 40

700-SN25

20

No heatsink

0

-20

-10

0

10

20

30

40

50

60

70

80

Ambient temperature (ºC)

Load Current (A)

Load Current (A)

Load Current (A)

Load Current (A)

Load current vs. ambient temperature characteristics for 700-SH25.... 30

25

700-SN50(V)HC

700-SN10

700-SN25

700-SN50

20

15

10

5

No heatsink

0

-20

-10

0

10

20

30

40

50

60

70

80

Ambient temperature (ºC)

80 70 60 50 40 30 20 10
0 -20

Load current vs. ambient temperature characteristics for 700-SH75....
700-SN50VHC 700-SN50HC

700SN10

700-SN25

700-SN50

No heatsink

-10

0

10

20

30

40

50

60

70

80

Ambient temperature (ºC)

Load current vs. ambient temperature characteristics for 700-SH5..... 6

700-SN50(V) HC 5

700-SN10 700-SN25

700-SN50

4

No heatsink 3

2

1

0

-20

-10

0

10

20

30

40

50

60

70

80

Ambient temperature (ºC)

254

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications
Mounting Considerations (1) (2) (3) (4)
All units are in millimeters unless otherwise indicated. To convert to inches multiply by 0.0394. Dimensions are not intended for manufacturing purposes.
45.5

58.2 30.0
47.5 24.5

5.3 2 x M5 Screws 2 x M3 Screws

Mounting Holes (Bottom View)

Terminal Arrangement/ Internal Connections
(Top View)

Load Load

Power

Load

Supply

47.5

Two Ø 4.4 or M4 Holes

L1

T1

A2

A1

Input

13.0 25 45.5
Cat. No. 700-SH5F...
44.8

28.8

47.5

58.2

12.3
2 X M5 Screws

8.6

Operating Indicator
2 X M3 Screws

APPLY HEATSINK COMPOUND

5.2 5.25
25
45.5
Cat. No. 700-SH10, -SH25, -SH50, -SH75, -SH100

Two Ø 4.4 or M4 Holes
47.5

(1) The proper mounting orientation of the heat sink is so the heat fins run perpendicular to the floor (vertical) to maximize ventilation flow. If the fins do not run perpendicular to the floor, a 30% current derating is required. (2) When attaching a heat sink to 700-SH, apply a thin layer of heat conductive grease (approximately 0.002 in. thick) on the heat sink to maximize heat transfer between the SSR and the heat sink.
Recommended types: Silicon based, Dow Corning 340, Toshiba YG6240; Non-silicon based, AOS company type 53300 (Cat. No. 46801-010-01). (3) Tighten the SSR panel/heat sink mounting screws to a torque of 0.78...0.98 N·m (6.9...8.7 lb·in). (4) Tighten the SSR terminal wiring screws as follows M4: 0.98...1.37 N·m (8.67...12.12 lb·in), M5: 1.57...2.35 N·m (13.89...20.8 lb·in).

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

255

Relay and Timer Specifications

700-SN10

700-SN25

700-SN50

700-SN50HC

700-SN50VHC

67

12

47
45

27

28,5
Cat. No.700-SHTRMA

27,5
Cat. No. 700-SHCOV

256

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

Load Connection

· For an AC load, use a power supply that is rated at 50 Hz. or 60 Hz. The maximum operating frequency is 10 Hz. · The 700-SH has a built-in varistor for surge/inrush protection of AC loads. If additional suppression is required, connect an external
varistor across the load device terminals. Select a varistor, which meets the load voltage condition that is outlined in the table.

Load Voltage [V AC] 100...120 200...240 380...480

Varistor Voltage [V] 240...270 440...470 820...1000

Varistor Surge Resistance 1000 A min.

TIP For additional details on solid-state relays, see the Solid-State Relay Application Guide, publication 700-AT001.

Zero Cross Function
An SSR with a zero cross function operates when an AC load voltage reaches the zero point or its vicinity. This reduces clicking noises when the load is switched and minimizes the influence of an inductive load, (such as, lamp, heater, or motor) on the power supply because the inrush current of the load is reduced. This can also minimize the scale of the inrush current protection circuit.

Output (load voltage)

Input

ON OFF

At a low applied voltage (for example, 24V AC) the load current is not fully supplied. When the unit is switched ON, the voltage required to power the unit deprives the output signal of the necessary voltage level and thus creates loss time. The lower the load voltage is, the greater the loss time is. This condition, however, will not create any serious problems.

Loss time
For a DC inductive load, a diode should be connected parallel to the load to absorb the counter electromotive force (OFF) of the load.

Input

SSR

Load

Load power supply

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

257

Relay and Timer Specifications

700-SK Slim Line Relays

· High-response speed models · Input sensor module to allow high voltage 100...240V AC or 12...24V DC sensor · Interface to low voltage (logic) device such as a PC output module for typical SSR applications · LED indicator · Input modules and output modules can be used with the 700-HN121 or 700-HN221 sockets

Input/Sensor Module Input-to-Output Isolation Method
Photocoupler

Status Indicator Yes

Response Frequency
10 Hz 1 kHz

Logic Level Supply Voltage Supply Current

4...32V DC

0.1...100 mA

Rated Input Sensor Voltage
100...240V AC (1) 12...24V DC

(1) 47...63 Hz

Cat. No.
700-SKICA18 700-SKICZ24

Output/SSR Module

Input-to-Output Isolation Zero Cross

Method

Function

Yes
Phototriac No

Photocoupler

Not Applicable

(1) 47...63 Hz

Status Indicator Yes

Output (Load) Max. Continuous Current and Rated Voltage Range
2 A @ 100...240V AC (1)
2 A @ 5...48V DC 1.5 A @ 48...200V DC

Rated Input Control Voltage
5...24V DC

Cat. No.
700-SKOZ2Z25 700-SKON2Z25 700-SKOC2Z25 700-SKOC1Z25

Accessories - 700-SK Relays

Photo

Description

Pcs./Pkg.

Cat. No.

Screw Terminal Socket -- Panel or DIN Rail Mounting 5-blade miniature socket with 10 A rating for use with 1pole, 700-HK relays. Accepts forked lug conductors. Socket includes a retainer clip.

10

700-HN121

DIN (#3) symmetrical hat rail 35 x 7.5 x 1 m

10

Pre-Printed Identification Tags -- contains 10 sheets of pre-printed and blank tags. Each sheet contains 13 sets of the markings CR...9CR, TR...9TR, M...9M, F, R, 1S, and 117 blank tags. Tags are peel-off with sticky backing for easy 10 placement on relays.

Blank Identification Tags -- contains 10 sheets of blank identification tags for customer specialized printing. Each sheet contains 546 blank tags. Tags are peel-off with sticky backing for easy placement on relays.

10

199-DR1 700-N40 700-N41

258

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

Specifications - 700-SK Relays

Input Sensor Module

Input Sensor Ratings Cat. No.
700-SKICZ24 700-SKICA18

Rated Input Voltage
12...24V DC 100...240V AC

Max. Operating Input Voltage Range
6.6...32V DC
60...264V AC

Input Current
8 mA max. 15 mA max.

Pick-up Voltage
6.6V DC max. 60V AC max.

Drop-out Voltage
3.6V DC min. 20V AC min.

Output Logic Ratings

700-SKICZ24 700-SKICA18

Cat. No.

Characteristics

Logic Level Supply Voltage 4...32V DC

Logic Level Supply Current Draw 0.1...100 mA

Description

Pick-up time

Drop-out time

Response frequency

Output ON voltage drop

Leakage current (from SSR)

Output VDRM, VCEO (V)
Output di/dt (A/uS)

Output dv/dt (V/uS) Output I2t (A2S)

Output Tj (°C) Max.

Insulation Resistance

Dielectric Strength

Vibration Resistance (Max.)

Shock Resistance (Max.)

Ambient Temperature

Operating Storage

Standards Compliance

Certifications

Ambient humidity Operating

Weight

Cat. No. 700-SKICA18

Cat. No. 700-SKICZ24

20 ms max.

0.1 ms max.

20 ms max.

0.1 ms max.

10 Hz

100 Hz

1.6V max.

5 A max.

80 (ref. value)

80 (ref. value)

--

--

--

--

--

--

150

150

100 M min. between input and output

4000V AC, 50/60 Hz for 1 min between input and output

10...55 Hz, 1.5 mm double amplitude (10 G) 1000 m/s(100 G)

­30...+80 °C (­22...+176 °F) with no icing or condensation

­30...+100 °C (­22...+212 °F) with no icing or condensation

UL 508, CSA C22.2 No. 14, EN/IEC 60950

cURus Recognized (File No. E96956, Guide NMFT2/NMFT8), CE Marked, TÜV Certified

45...85% (no condensation)

Approx. 18 g

Output SSR Module

Control/Input Ratings

Cat. No.

Rated Control Voltage

700-SKOZ2Z25 700-SKON2Z25 700-SKOC2Z25 700-SKOC1Z25

5...24V DC

Max. Operating Control Voltage
Range
4...32V DC

Max. Reverse Control Voltage
-32V DC

Impedance (1)

Pick-up Voltage Drop-out Voltage

15 mA max. at 25 °C (77 °F)
8 mA max.

4V DC max.

1V DC min.

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

259

Relay and Timer Specifications

Load/Output Ratings

Cat. No.
700-SKOZ2Z25 700-SKON2Z25 700-SKOC2Z25 700-SKOC1Z25

Rated Load Voltage
100...240V AC 5...48V DC 48...200V DC

Maximum Load Voltage Range
75...264V AC
4...60V DC 40...200V DC

Continuous Load Current (Resistive) [A]

Min.

Max. (2)

0.05

2

0.1

2

0.1

1.5

(1) With a constant current input system. SSR impedance varies with a change in input voltage. (2) See Load Current Versus Ambient Temperature Characteristics for additional details. (3) If the SSR operation is continuous ON/OFF, this value should be reduced by 50%. See the "Inrush Current Resistivity"graphs on page 126 for more details.

Characteristics

Max. Inrush Current (3)
30 A (@50/60 Hz, One cycle) 8 A (10 ms) 8 A (10 ms)

Description

Cat. No. 700-SKOZ2Z25 Cat. No. 700-SKON2Z25 Cat. No. 700-SKOC2Z25

Cat. No. 700-SKOC1Z25

Load Switching Method/Device Pick-up Time Drop-out Time

Triac 1/2 cycle of load power source cycle time (1) + 1 ms max.
1/2 of load power source cycle time (1) + 1 ms max.

Transistor 1 ms max. 2 ms max.

Response Frequency

20 Hz

100 Hz

Output ON Voltage Drop

1.6V max.

2.5V max.

Leakage Current (from SSR)

1.5 mA max.

1 mA max.

Output VDRM, VCEO (V)
Output di/dt (A/uS)

600 (ref.value) 30

600 (ref.value) 30

80 (ref.value) --

400 (ref.value) --

Output dv/dt (V/uS) Output I2t (A2S)

300

300

--

--

10.4

10.4

--

--

Output Tj (°C) Max. Insulation Resistance

125

125

150

150

100 M min. between input and output

Dielectric Strength

4000V AC, 50/60 Hz for 1 min between input and output

Vibration Resistance (Max.) Shock Resistance (Max.)

10...55 Hz, 1.5 mm double amplitude (10 G) 1000 m/s2 (100 G)

Ambient Temperature

Operating Storage

­30...+80 °C (­22...+176 °F) with no icing or condensation ­30...+100 °C (­22...+212 °F) with no icing or condensation

Standards Compliance

UL 508, CSA C22.2 No. 14, EN/IEC 60950

Certifications

cURus Recognized (File No. E96956, Guide NMFT2/NMFT8), CE Marked, TÜV Certified

Ambient Humidity Operating

45...85% (no condensation)

Weight

Approx. 18 g

(1) 60 Hz cycle time = 16.6 ms, 50 Hz cycle time = 20 ms.

Load Current vs. Ambient Temperature Characteristics

For 2 A Versions

Maximum Load Current (A) -20
0 20 40 60 80 100
Maximum Load Current (A) -20
0 20 40 60 80 100

2 1.5
1 0.5
Ambient Temperature [° C]

2 1.5
1 0.5
Ambient Temperature [° C]

260

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Relay and Timer Specifications

Inrush Current (A)
10 30 50 100 200 500 1000 5000
Inrush Current (A)
10 30 50 100 300 500 1000 2000
Inrush Current (A)
10 30 50 100 300 500 1000 2000

Inrush Current Resistivity (2)
700-SKOZ/SKON
30
20
10

700-SKOC2
10 9 8 7 6 5 4 3 2 1 0

700-SKOZ/SKOC1
10 9 8 7 6 5 4 3 2 1 0

Energizing Time (ms)

Energizing Time (ms)

Energizing Time (ms)

(2) Inrush current resistivity is the ability of an SSR to withstand a large surge current for a short period. Surges are considered non-repetitive (max. repeatability once every 2...5 seconds). Keep the inrush current to half the rated value if it occurs repetitively. Exceeding the non-repetitive inrush current will damage the SSR.

Dimensions - 700-SK Relays
All units are in millimeters unless otherwise indicated. To convert to inches multiply by 0.0394. Dimensions are not to be used for manufacturing purposes.

IMPORTANT The input module (700-SKI) and output module (700-SKO) are compatible with the Cat. No. 700-HN121 socket.

29 max.

1
0.5 4.75

5.2
3 4 9.6
17.4

15

13 max. 4
10

28 max.
2 20

5

7.5

4.7

0.5 4.75

Terminal Arrangement/ Internal Connections (Bottom View)
(+) 3
(­)
4
Load

Input

1

5

(­)

(+)

Application Considerations of the700-SK Relay
Connection
For DC load switching, 700-SK SSR will operate properly if the load is connected to either the positive or negative SSR load terminal. The load can be connected to either positive or negative output terminals of the SSR.
Protective Element (to extend SSR life)
Since the SSR does not incorporate a surge absorption component, be sure to connect a surge absorption component when using the SSR to control an inductive load.
TIP For additional details on solid-state relays, see the Solid-State Relay Application Guide, publication 700-AT001.

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

261

Relay and Timer Specifications
Notes:

262

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

Additional Resources

Relay and Timer Specifications Technical Data

These documents contain additional information concerning related products from Rockwell Automation.

Resource General Purpose, Interposing, Solid-State and Specialty Relays Brochure publication 700-BR018 Solid-state Relay Application Guide, publication 700-AT001 EtherNet/IP Network Devices User Manual, ENET-UM006 Ethernet Reference Manual, ENET-RM002
System Security Design Guidelines Reference Manual, SECURE-RM001
Industrial Components Preventive Maintenance, Enclosures, and Contact Ratings Specifications, publication IC-TD002
Safety Guidelines for the Application, Installation, and Maintenance of Solid-state Control, publication SGI-1.1
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 Product Certifications website, rok.auto/certifications.

Description
Provides product overview and applications for Bul 700 relay line.
Provides methods for applying and troubleshooting Solid-state relays. Describes how to configure and use EtherNet/IP devices to communicate on the EtherNet/IP network. Describes basic Ethernet concepts, infrastructure components, and infrastructure features. Provides guidance on how to conduct security assessments, implement Rockwell Automation products in a secure system, harden the control system, manage user access, and dispose of equipment. Provides a quick reference tool for Allen-Bradley industrial automation controls and assemblies. Designed to harmonize with NEMA Standards Publication No. ICS 1.1-1987 and provides general guidelines for the application, installation, and maintenance of solid-state control in the form of individual devices or packaged assemblies incorporating solid-state components. Provides general guidelines for installing a Rockwell Automation industrial system. Provides declarations of conformity, certificates, and other certification details.

You can view or download publications at rok.auto/literature.

Rockwell Automation Publication 700-TD552F-EN-P - January 2021

263

Rockwell Automation Support

Use these resources to access support information.

Technical Support Center Knowledgebase Local Technical Support Phone Numbers Literature Library Product Compatibility and Download Center (PCDC)

Find help with how-to videos, FAQs, chat, user forums, and product notification updates. Access Knowledgebase articles. Locate the telephone number for your country. Find installation instructions, manuals, brochures, and technical data publications. Download firmware, associated files (such as AOP, EDS, and DTM), and access product release notes.

rok.auto/support rok.auto/knowledgebase rok.auto/phonesupport rok.auto/literature
rok.auto/pcdc

Documentation Feedback
Your comments help us serve your documentation needs better. If you have any suggestions on how to improve our content, complete the form at rok.auto/docfeedback.

Allen-Bradley, expanding human possibility, and Rockwell Automation are trademarks of Rockwell Automation, Inc. EtherNet/IP is a trademark of ODVA, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies.
Rockwell Automation maintains current product environmental compliance information on its website at rok.auto/pec.
Rockwell Otomasyon Ticaret A.. Kar Plaza  Merkezi E Blok Kat:6 34752, çerenköy, stanbul, Tel: +90 (216) 5698400 EEE Yönetmeliine Uygundur

Publication 700-TD552F-EN-P - January 2021
Supersedes Publication 700-TD552E-EN-P - June 2020

Copyright © 2021 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.


Acrobat Distiller 11.0 (Windows)