Instructions for digitrip models 520v and 520mcv for use only in cutler-hammer type VCP-T, VCP-TR and T-VAC, T-VACR circuit breakers - IL66A7534H04

instructions-for-digitrip-models-520v-and-520mcv-il66a7534h04
I.L. 66A7534H04

I.L. 66A7534PHag0e41

Instructions for Digitrip Models 520V and 520MCV for use only in Cutler-Hammer Type VCP-T, VCP-TR and T-VAC, T-VACR Circuit Breakers

Table of Contents

1.0 General Description of Digitrip Trip Units ................. 2 1.1 Protection ............................................................... 3 1.2 Mode of Trip and Status Information ........................ 3 1.3 Installation and Removal .......................................... 3
1.3.1 Installation of the Trip Unit ............................ 3 1.3.2 Installation of the Rating Plug ....................... 3 1.3.3 Trip Unit/Rating Plug Removal ...................... 4 1.4 Installing the CH Type-V Curent Sensors ................. 5 1.4.1 Installation of the Rating Plug ...................... 5 1.4.2 CH Type-V Current Sensor Functiionality .... 5 1.5 Plexiglass Cover ..................................................... 5 1.6 Ground Alarm/Power Supply Module (520MCV) ....... 5 1.6.1 Auxilary Power ............................................ 7 1.6.2 Ground Alarm .............................................. 7 1.6.3 Ground Fault Trip ........................................ 7 1.6.4 Ground Fault Alarm ..................................... 7 1.7 Display Feature (520MCV) ...................................... 7 1.8 UL, CSA and CE Recognition .................................. 8
2.0 General Description of VCP-T, VCP-TR and T-VAC, T-VACR Circuit Breakers ....................... 8
2.1 General ................................................................... 8 2.2 Low Energy Trip Actuator ........................................ 9 2.3 Ground Fault Protection .......................................... 9
2.3.1 General ........................................................ 9 2.3.2 Zero Sequence Sensing ............................... 9 2.3.3 Residual Sensing ......................................... 9 2.3.4 Ground Fault Settings ................................ 10
3.0 Principles of Operation .......................................... 12 3.1 General ................................................................. 12 3.2 Trip and Operation Indicators ................................. 12 3.3 Zone Interlocking ............................................. 12, 28
4.0 Protection Settings ............................................... 14 4.1 General ................................................................. 14 4.2 Long Delay Current Setting ................................... 14 4.3 Long Delay Time Setting ....................................... 14 4.4 Short Delay Current Setting................................... 15 4.5 Short Delay Time Setting ...................................... 15 4.6 Instantaneous Current Setting ............................... 15 4.7 Ground Fault Current Setting ................................. 16 4.8 Ground Fault Time Delay Setting .......................... 16 4.9 INCOM (520MCV) .................................................. 16
4.9.1 Breaker Interface Module (BIM) .................. 16 4.9.2 Remote Master Computer .......................... 16 4.9.3 INCOM Network Interconnections .............. 17

5.0 Test Procedures .................................................... 18 5.1 Test Precautions ................................................... 18 5.2 When to Test ........................................................ 18 5.3 Functional Field Testing ........................................ 18
5.3.1 Field Test Kit ............................................... 18 5.3.2 Handheld Functional Test Kit ...................... 19
5.3.2.1 Description of Handheld Test Kit ...... 19 5.3.2.2 Test Procedure ................................ 19 5.3.2.3 Currents .......................................... 19 5.3.2.4 Batteries ......................................... 19 5.4 Performance Testing of Digitrip Trip Units .............. 19 5.4.1 General ...................................................... 19 5.4.2 Testing using MS-2 MultiAMP® Tester ....... 19 5.4.2.1 Description of MS-2 Tester .............. 19 5.4.2.2 Primary Injection Testing ................. 20 5.4.2.3 Secondary Injection Testing ............. 21
6.0 Battery ................................................................. 23 6.1 General ................................................................. 23 6.2 Battery Check ....................................................... 23 6.3 Battery Installation and Removal ........................... 23
7.0 Frame Ratings (Sensor Ratings and Rating Plugs) ....................... 24
8.0 Record Keeping .................................................... 24
9.0 References ............................................................ 24 9.1 Medium Voltage Type VCP Circuit Breakers .......... 24 9.2 Time-Current Curves .............................................. 24
Appendix A Zone Interlocking Examples ..................... 28
Appendix B Troubleshooting Guide ............................ 30
Appendix C Typical Breaker Master Connection Diagram ................................ 32
Appendix D MODBUS Translator Wiring .................... 33
Manufacturer's Statement ............................................. 34

Effective 8/2006

Page 2
WARNING
DO NOT ATTEMPT TO INSTALL OR PERFORM MAINTENANCE ON EQUIPMENT WHILE IT IS ENERGIZED. DEATH OR SEVERE PERSONAL INJURY CAN RESULT FROM CONTACT WITH ENERGIZED EQUIPMENT. ALWAYS VERIFY THAT NO VOLTAGE IS PRESENT BEFORE PROCEEDING. ALWAYS FOLLOW SAFETY PROCEDURES. CUTLER-HAMMER IS NOT LIABLE FOR THE MISAPPLICATION OR MISINSTALLATION OF ITS PRODUCTS.

I.L. 66A7534H04

WARNING
OBSERVE ALL RECOMMENDATIONS, NOTES, CAUTIONS, AND WARNINGS RELATING TO THE SAFETY OF PERSONNEL AND EQUIPMENT. OBSERVE AND COMPLY WITH ALL GENERAL AND LOCAL HEALTH AND SAFETY LAWS, CODES, AND PROCEDURES.

NOTE: The recommendations and information contained herein are based on experience and judgement, but should not be considered to be all inclusive or to cover every application or circumstance which may arise.

NOTE: If you have any questions or need additional information or instructions concerning the operation or installation of this device, please contact your local representative or the Cutler Hammer Customer Support
Center.

Figure 1.1 Digitrip Trip Unit with Rating Plug

1.0 GENERAL DESCRIPTION OF DIGITRIP TRIP UNITS

The Digitrip Trip Unit is a breaker subsystem that provides the protective functions for a circuit breaker. The trip units are in removable housings, installed in the circuit breaker, and can be replaced or upgraded in the field by the customer.
This instruction book specifically covers the application of the Digitrip Trip Units (See Figure 1.1) installed in Type VCP-T, VCP-TR, T-VAC or T-VACR Medium Voltage Circuit Breakers.

The Digitrip 520V and 520MCV trip units may be applied on both 50 and 60 Hertz systems. It detects the power and frequency and adjusts itself automatically.
The Digitrip 520V and 520MCV are self powered and self protecting trip units designed to function only with the associated CH Type-V current sensors.

Effective 8/2006

I.L. 66A7534H04

Page 3

CAUTION

Status LED will also blink at a faster rate if the Digitrip is in a "Long Pick-up" (overload) mode.

CONNECTING THIS TRIP UNIT TO CURRENT SENSORS OTHER THAN CH TYPE-V MIGHT DAMAGE OR DESTROY IT.
All trip unit models are microprocessor-based AC protection devices that provide true RMS current sensing for the proper coordination with the thermal characteristics of conductors and equipment. The primary function of this Digitrip trip unit is circuit protection. The Digitrip analyzes the secondary current signals from the CH Type-V current sensors and, when preset current levels and time delay settings are exceeded, will send an initiating trip signal to the Trip Actuator of the circuit breaker, causing it to "open."

Four red LEDs on the face of the trip units flash to indicate the cause of trip for an automatic trip operation... i.e.: Long Delay (overload), Short Delay, Instantaneous or Ground (Earth) Fault. A battery, inside the rating plug compartment of the Digitrip unit, maintains the trip indication until the Reset/Battery Test button is pushed. The battery is satisfactory if its Battery Check LED lights green when the Battery Check button is pushed (See Section 6).
NOTE: The Digitrip unit provides all protection functions independant of the status of the battery. The battery is used only to maintain the automatic trip indication.

In addition to the basic protection function, the Digitrip

520V and 520MCV provide modes of trip indication such

as:

·

Long Time trip (overload)

·

Short Time trip

·

Instantaneous trip

·

Ground (Earth) Fault trip

The CH Type-V current sensors provide the power to the trip unit. As current begins to flow through the breaker, the sensors generate a secondary current which powers the trip unit. No auxilary power is needed to trip the circuit
breaker.

The Digitrip 520V and 520MCV trip units have five phase and two ground (time-current) curve shaping adjustments. To satisfy the protection needs of any specific installation, the exact selection of the available protection function adjustments is necessary. The short delay and ground fault pick-up adjustments can be set for either FLAT or I2t response. A pictorial representation of the applicable timecurrent curves for the selected protection functions is provided, for user reference, on the face of the trip unit as shown in Figure 1.1. The user chooses the settings according to the needs of his application. (See Sections 4.0 & 9.2)

1.3 Installation and Removal
1.3.1 Installation of the Trip Unit
Align the Digitrip unit with the guide pins and spring clip of the circuit breaker. Press the unit into the breaker until the pins on the trip unit seat firmly into the connector housing and the unit clicks into place (see Figure 1.2).
1.3.2 Installation of the Rating Plug
Insert the rating plug into the cavity on the right-hand side of the trip unit. Carefully align the three pins on the plug with the sockets in the cavity. The plug should fit with a slight insertion force.
WARNING
DO NOT CLOSE THE CIRCUIT BREAKER WHEN THE DIGITRIP IS REMOVED OR DISCONNECTED. DAMAGE TO ASSOCIATED CURRENT TRANSFORMERS MAY OCCUR DUE TO AN OPEN CIRCUIT CONDITION. THERE IS NO PROTECTION FOR THE LOAD CIRCUIT.

1.1 Protection
The Digitrip trip system; including associated CH Type-V current sensors, require no external control power to operate their protection systems. They operate from current signal levels derived through the CH Type-V current sensors.
1.2 Mode of Trip and Status Information
A green light emitting diode (LED), labeled Unit Status in Figure 1.1, blinks approximately once each second to indicate that the trip unit is operating normally. This Unit

CAUTION
IF A RATING PLUG IS NOT INSTALLED IN THE TRIP UNIT, THE UNIT WILL INITIATE A TRIP WHEN IT IS ENERGIZED. IN ADDITION THE INSTANTANEOUS LED OF THE DIGITRIP TRIP UNIT WILL LIGHT DUE TO A MISSING OR BAD RATING PLUG.

Effective 8/2006

Page 4

I.L. 66A7534H04

J3 (3 point) J4 (4 point) Connectors
Ground Alarm/Power Supply Module (520MCV option only)
Trip Actuator

Mounting Boss Steel Mounting Plate Guide / Rejection Pin Digitrip 520V / 520MCV
Dimple
Pin 1 Connector K2
M-4 x 80mm Mounting Screw
Rating Plug (3 Pins)
Pin 1 - Connector K1

Wires with Connectors

Connector I1

Figure 1.2 Installation of the Digitrip Unit into Breaker (Side View)

0.045 Dia. Pins Exiting Digitrip Housing
Spring Clip

CAUTION
THE M4 SCREW SHOULD BE TIGHTENED ONLY UNTIL IT IS SNUG BECAUSE THERE IS NO STOP. DO NOT USE A LARGE SCREWDRIVER. A 1/8" (3mm) WIDE SCREWDRIVER BLADE IS ADEQUATE.
1.3.3 Trip Unit/Rating Plug Removal
To remove the rating plug from the trip unit, make sure the circuit breaker is open. Now open the left side of the rating plug door. Use a 1/8" (3mm) wide screwdriver to loosen and remove the M4x80mm mounting screw. Pull the rating plug from the trip unit.
To remove the trip unit from the circuit breaker, remove the breaker cover screws using a 10mm driver. Deflect the spring clip under the trip unit to release the unit from the steel mounting plate. Pull the unit straight forward to disengage the two 9-pin connectors from the circuit breaker control circuit. (See Figure 1.2).

CAUTION

DO NOT FORCE THE RATING PLUG INTO THE CAVITY. USE A 1/8" (3MM) WIDE SCREWDRIVER TO TIGHTEN THE M4 SCREW AND SECURE THE PLUG AND THE TRIP UNIT TO THE CIRCUIT BREAKER (See Figure 1.3). CLOSE THE RATING PLUG DOOR.

Figure 1.3 Installating the Rating Plug & Mounting Screw

Effective 8/2006

I.L. 66A7534H04

Page 5

1.4 Installing the CH Type-V Current Sensors
The internal components of the circuit breaker, and how they are wired out to the breaker secondary contacts are shown in Figures 1.4, 1.5, 1.6 and 2.3. Also refer to the master connection diagram provided in Appendix C.
1.4.1 Installation Procedure
The CH Type-V Current Sensors/Rating Plug Kit supplied with this breaker must be installed and wired by the user. The installation steps are as follows:
a. PRIMARY - Mount one CH Type-V current sensor on the insulated bushing behind the circuit breaker. The bushing must be rated for the system Lightning Impulse Withstand Voltage (LIWV), and the ground (earth) shield terminal or ground (earth) shield surface must be connected to the ground (earth) bus. Confirm that the polarity mark (red dot) on the front of the current sensor faces the circuit breaker.
b. SECONDARY - Connect secondary terminals of the current sensor to the correct terminals in the switchgear control circuit using #14 AWG Type SIS wire. Terminal X1 is the one nearest to the polarity mark. Refer to Appendix C for distinction between Fixed and Drawout variations. Consult manufacturer if length of wire to device exceeds 12 feet (3.7m).
c. Use ring terminals on current sensor terminals. Use AMP #66598-2 female sockets to connect to breaker's secondary connector.
d. Ground (Earth) the non polarity terminal of each sensor. Also Ground the bushing shield surfaces.

circuit breaker when functional protection settings are exceeded.
If the CH Type-V current sensors and circuit breaker enclosure label are changed to a different ratio, the rating plug must also be changed. The associated rating plug must match the current sensors installed and as specified on the circuit breaker enclosure label. Refer to Figure 2.3 for CH Type-V current sensors available.
1.5 Plexiglass Cover
A clear, tamper-proof, plexiglass door sits on the breaker cover. This door allows the settings to be viewed but not changed, except by authorized personnel. The plexiglass cover meets applicable tamper-proof requirements. The cover is held in place by two screws. Security is insured by the insertion of a standard meter seal through the holes in both of the cover retention screws. The plexiglass cover has an access hole for the Reset/Battery Test push button.
1.6 Ground Alarm/Power Supply Module (520MCV Models Only)
The Ground Alarm/Power Supply Module (See Figure 1.7) is a required accessory to enable communications on the Digitrip 520MCV model. The module can be installed beneath the metal mounting plate of the trip unit in the Magnum Circuit Breaker. The module covers the following input voltage ratings: 120 VAC (7802C83G11), 230 VAC (7802C83G12), 24-48 VDC (7802C82G12) and 125VDC (7802C8213). The burden of the Power/Relay Module is 10VA.

e. Install rating plug into the Digitrip 520V and 520MCV trip units for the matching CH Type-V current sensors. Also attach the additional rating plug label to the circuit breaker enclosure as a future reference indicating which CH Type-V current sensors used in this application.

1.4.2 CH Type-V Current Sensor Functionality
The three CH Type-V current sensors are installed external to the circuit breaker over the main circuit conductors by means of bushings equipped with a ground shield. The current sensor rating defines the breaker rating (In)... i.e. 1200A:1A sensors are used on a 1200A rated breaker. There are four auxiliary current transformers with a ratio of 10:1 which further step down the rated current to 100 milliamperes, which is equivalent to 100% (In) to the Digitrip.

The primary current sensors produce an output signal proportional to the load current and furnish the Digitrip trip units with the information and energy required to trip the

Figure 1.4 CH Type-V Current Sensor Installation

Effective 8/2006

Page 6

I.L. 66A7534H04

Figure 1.5 Secondary Block "A" Connections

Figure 1.6 Secondary Block "B" Connections

Effective 8/2006

I.L. 66A7534H04

Page 7

1.6.1 Auxiliary Power
When the module is wired as shown in Figure 1.8, it will provide an auxiliary power supply so that the 520MCV liquid crystal display (LCD) will be functional even when the circuit breaker has no load. A Digitrip 520MCV tripunit without auxiliary power will not display data until load current reaches approximately 30% 1 phase or 10% 3 phase of the (In) rating.

1.6.2 Ground Alarm
A second function of the module is to provide either a ground trip or ground alarm only output contact via the relay supplied in the module. An LED on the front of the unit also provides an indication of ground fault trip.

1.6.3 Ground Fault Trip
When the Ground Alarm/Power Supply module is used, this unit will provide ground fault trip contacts when the circuit breaker trips on a ground fault. You must then push the Reset button on the Digitrip in order to reset the contacts (See Figure 1.8, Note 3).

1.6.4 Ground Fault Alarm
A ground fault alarm alerts a user to a ground fault condition without tripping the circuit breaker. A red Alarm Only LED on the front of the trip unit will indicate the presence of a ground fault condition that exceeds the programmed setting.

The ground fault alarm relay is energized when the ground current continuously exceeds the ground fault pickup setting for a time in excess of a 0.1 second delay. The alarm relay will reset automatically if the ground current is less than the ground fault pickup (See Figure 1.8, Note 4).
1.7 Display Feature (520MCV only)
The Digitrip 520MCV model has a user interface in addition to the green and red LED trip indicators. This seven element display performs a metering function and can be used to monitor load currents.
When the Step button on the face of the trip unit is pressed and released, the display will show PH 1, for Phase 1 or A, and the current value. If the Step button is not pressed again, the display will continue to show the current value for Phase 1. Each time that the Step button is pressed, the next monitored function will be displayed. The other real time readings can be displayed in the following sequence:

Figure 1.7 Ground Alarm/Power Supply Module for the 520MCV Trip Unit

PH 2 Phase 2 (B)

PH 3 Phase 3 (C)

PH 4 Neutral

PH 5 Ground

HI

Highest phase current

OL Overload (Digitrip in overload mode)

Pushing the Step button while the unit is in the OL mode will have the unit again display the overload current value.

HELP

This message can indicate more than one problem with the trip unit. If the rating plug is missing, a HELP message and an Instantaneous trip LED light will be observed. The rating plug needs to be installed and the Instantaneous trip LED must be cleared by pressing the Reset/Battery Test button.

Effective 8/2006

Page 8

I.L. 66A7534H04

This message could also indicate that the trip unit is out of calibration and should be replaced at the earliest opportunity.

Control Voltage
2

Remote

Ground 3 Fault Trip

Ground Fault Alarm

1.8 UL, CSA and CE Recognition
The Digitrip 520V and 520MCV Trip Units are a UL® (Underwriters Laboratories, Inc.) Recognized Component under File E146559 for use in Type VCP-T, VCP-TR and Type T-VAC, T-VACR Medium Voltage Circuit Breakers. They have also been tested by the Canadian Standards Association (CSA).
This Digitrip 520V and 520MCV have also passed the IEC 947-2 test program which includes radiated and conducted emissions testing. As a result, all units carry the CE mark.

ATR COM A-15 J4-1

ATR Volt. A14 J4-2

A-11

G-ALM 1 A-10 J4-4

G-ALM 2 J4-3

G -A la rm J3-1 J3-2 Output J3-3 Output +

1
Ground Alarm / Power Supply Module

K2-1 K2-3 K2-6

Digitrip 520MCV

Available

Style 2

Input Voltages Number

120 VAC 7802C83G01

230 VAC 7802C83G02

24-48 VDC 7802C82G02

125 VDC 7802C82G03

1 Contact Rating (resistive load) AC 0.5A @ 230VAC AC 1A @ 120VAC DC 1A @ 48VDC DC 0.35A@ 125VDC
2 Verify input voltage rating before energizing circuit.
3 When used in conjunction with a T. U. Cat. 5ARMVLSIG will indicate GF trip.

2.0 GENERAL DESCRIPTION of VCP-T, VCP-TR or T-VAC, T-VACR CIRCUIT BREAKERS

Figure 1.8 Wiring Diagram for 520MCV with Ground Alarm/Power Supply Module
In addition, the Digitrip 520MCV will display and freeze the magnitude of the trip value after a trip event if auxilary power is available. Use the Step pushbutton to view each phase value. The highest value that can be presented is 9999. Any fault currents greater than this value will be shown as "HI." Pushing the Reset pushbutton will clear this data.
Also related to the phase value after a trip event are four dashes "----". This message means that the microprocessor could not complete its writing of the trip event's magnitude into its non volatile memory. A possible cause of this would be the lack or loss of auxilary power during the trip event.

2.1 General
The circuit breakers are tripped automatically on overload and fault current conditions by the combined action of three components:
1. The sensors, which measure the current level
2. The Digitrip Trip Unit, which provides a tripping signal to the Trip Actuator, when current and time delay settings are exceeded.
3. The low-energy Trip Actuator, which actually trips the circuit breaker.
This arrangement provides a very flexible system, covering a wide range of tripping characteristics described by the time-current curves referenced in Section 9.2.

Effective 8/2006

I.L. 66A7534H04

Page 9

2.2 Low-Energy Trip Actuator

2.3.2 Zero Sequence Sensing

The mechanical force required to initiate the tripping action of the circuit breaker is provided by a special low-energy Trip Actuator. This device is located behind the molded platform on which the Digitrip units are supported. (See Figure 1.2) The Trip Actuator contains a permanent magnet assembly, moving and stationary core assemblies, a spring, and a coil. Nominal coil resistance is 25 ohms and the black lead is positive. The circuit breaker mechanism automatically resets the Trip Actuator each time the circuit breaker opens.

Zero Sequence Sensing, also referred to as vectorial summation, is applicable to mains, feeders, and special schemes involving zone protection. An optional CH Type-V Zero Sequence current transformer (See Figure 2.1), having taps for 100A and 200A ratings is available for this application. The torroidal sensor has a 4.8" I.D. (12.192cm) with a 7.6" O.D. (19.304cm). Its style number 69C3016G01. (See Figure 2.3 and Appendix C)

When the Trip Actuator is reset by the operating mechanism, the moving core assembly is held in readiness against the force of the compressed spring by the permanent magnet. When a tripping action is initiated, the lowenergy Trip Actuator coil receives a tripping pulse from the Digitrip trip unit. This pulse overcomes the holding effect of the permanent magnet, and the moving core is released to upset the trip latch of the circuit breaker mechanism.

2.3 Ground Fault Protection

2.3.1 General

When employing a ground fault scheme, the distribution system characteristics (i.e. system grounding, number of sources, number and location of ground points, etc.) must be considered along with the manner and location in which the circuit breaker is applied to the system. These elements are discussed in Sections 2.3.2 through 2.3.4.

The Digitrip uses two modes of sensing to detect ground fault currents: residual and zero sequence (See Table 2.1). The breaker's secondary contact inputs B-6, B-7, that were shown in Figure 1.6, are used to configure the breaker cell positions for the two schemes. Having no jumper from B-6 to B-7 programs the unit for a residual ground fault scheme, while installing a jumper from B-6 to B-7 programs the unit for zero sequence configuration. If present, this jumper resides on the stationary side of the switchgear assembly. The proper current sensor input is required on the external sensor input terminals B-4, B-5 of the breaker secondary contacts.

Ground (Earth) Fault
Sensing Method Residual
Zero Sequence

Breaker Secondary Contacts Req'd
No Jumper Jumper B6 to B7

Figure Ref 2.2
2.3

Digitrip GF Sensing
Element Used element R5
element R4

Figure 2.1 Zero Sequence Current Transformer
2.3.3 Residual Sensing
Residual is the standard operating mode of ground fault sensing. This mode utilizes one current sensor on each phase conductor (See Figure 2.2). If the system neutral is grounded, but no phase to neutral loads are used, the Digitrip includes all of the components necessary for ground fault protection. This mode of sensing vectorily sums the outputs of the three or four individual CH Type-V current sensors. Residual ground fault sensing features are adaptable to main and feeder breaker applications.

Table 2.1 Digitrip Sensing Modes

Effective 8/2006

Page 10

I.L. 66A7534H04

2.3.4 Ground Fault Settings
The adjustment of the ground fault functional settings (FLAT response or I2t) is discussed in Section 4.8. The effect of these settings is illustrated in the ground fault time-current curve referenced in Section 9. The residual ground fault pick-up settings are from 0.25x, 0.3x, 0.35x, 0.4x, 0.5x, 0.6x, 0.75x and OFF.

CAUTION
IF THE PHASE CONNECTIONS ARE INCORRECT, A NUISANCE TRIP MAY OCCUR. ALWAYS OBSERVE THE POLARITY MARKINGS ON THE INSTALLATION DRAWINGS. TO INSURE CORRECT GROUND FAULT EQUIPMENT PERFORMANCE, CONDUCT FIELD TESTS TO INSURE PROPER GROUND FAULT FUNCTIONALITY.

Source

LA

LB

LC

+ Trip Actuator -

Black K1-2 K1-3

Digitrip 520V or 520MCV

A-4 CSA1

10:1 K1-9

A-19 A-5

CSA2 CSB1

K1-8 K1-7

R/1

1

A-20 CSB2

K1-6

K1-5

A-6 CSC1

R/1 A-21 CSC2

K1-4

R5

B-5 X1

K2-9

B-4 X2

K2-8 10:1 AUX. CT

Load
Notes: 1 In this scheme, all breaker secondary currents (at the 100 mA level) are summed together at the PC
board donut transformer to sense ground fault via element R5.

2 Do not jumper secondary contacts B-6, B-7. This will defeat the residual ground fault protection.

Figure 2.2 Breaker Using Residual GF Sensing

Effective 8/2006

I.L. 66A7534H04

Page 11

R/1 R/1

Figure 2.3 Zero Sequence Sensing Scheme

2 x 10-32 Brass Slot Head Terminal Screws

POLARITY MARK SECONDARY "X1" POLARITY MARK PRIMARY "H1"

LABEL
A 0.75

B

C

DESCRIPTION
100A 69C3011H01 200A 69C3011H02
250A 69C3011H25 300A 69C3011H03 400A 69C3011H04 600A 69C3011H06 630A 69C3011H63
800A 69C3011H08 1000A 69C3011H10 1200A 69C3011H12 1250A 69C3011H13 1600A 69C3011H16 2000A 69C3011H20 2500A 69C3011H52

A (min) 3.42 3.42
3.42 3.42 3.42 3.42 3.42
3.42 3.42 3.42 3.42 3.42 3.42 3.42

B (max) 5.35 5.35
5.35 5.35 5.35 5.35 5.35
5.35 5.35 5.35 5.35 5.35 5.35 5.35

Figure 2.4 Digitrip Phase Sensor (CH Type-V)

C (max) 1.55 1.55
1.55 1.55 1.55 1.55 1.55
1.55 1.55 1.55 1.55 1.55 1.55 1.55

WIRE GAUGE 2 X 17 17
18 18 17 18 18
19 19 19 19 20 21 21

2.0

LABEL INFORMATION: CUTLER-HAMMER PART NUMBER RATING C-H Type V CURRENT SENSOR DATE CODE (YR MO DY LOC)

RATIO 1:100 1: 200 1: 250 1: 300 1: 400 1: 600 1: 630 1: 800 1:1000 1:1200 1:1250 1:1600 1: 2000 1: 2500

Rdc (Ohms +/-15%) 0.09 0.31
0.47 0.56 0.61 1.17 1.21
1.87 2.29 2.93 3.06 4.67 7.25 8.90

Effective 8/2006

Page 12

I.L. 66A7534H04

3.0 PRINCIPLES OF OPERATION
3.1 General
The Digitrip 520V and 520MCV trip units are designed for circuit breaker environments where the ambient tempera-
tures can range from ­30°C to +85°C, but rarely exceed 70° to 75°C. If, however, temperatures in the neighborhood of the trip unit exceed 85°C, the trip unit performance may
be degraded. In order to insure that the tripping function is not compromised due to an over-temperature condition, the Digitrip trip unit has a built-in over-temperature protection feature, factory set to trip the breaker if the chip temperature is excessive. If over-temperature is the reason for the trip the red "Long Delay Time" LED will flash.

The green Unit Status LED, shown in Figure 1.1, flashes at one second intervals to indicate the operational status of the trip unit. Once the load current through the circuit breaker exceeds approximately 10 percent (3 phase power) of the current sensor rating, the green LED will flash on and off once each second to indicate that the trip unit is energized and operating properly.
NOTE: A steady green Unit Status LED typically indicates that a low level of load current, on the order of 5% of full load, exists.
3.3 Zone Interlocking

The Digitrip 520V and 520MCV use an integrated circuit that includes a microcomputer to perform its numeric and logic functions. The principles of operation of the trip unit are shown in Figure 3.1.
All power required to operate the protection function is derived from the CH Type-V current sensors in the enclosure behind the circuit breaker. (See Figure 1.4) The secondary currents from these sensors provide the correct input information for the protection functions, as well as tripping power, whenever the circuit breaker is carrying current. These current signals develop analog voltages across the "current viewing" resistors. The resulting analog voltages are digitized by the microprocessor.
The microcomputer continually digitizes these signals. This data is used to calculate true RMS current values, which are then continually compared with the protection settings. The embedded software then determines whether to initiate protection functions, including tripping the breaker through the Trip Actuator.
3.2 Trip and Operation Indicators
The LEDs on the face of the trip unit, shown in Figures 1.1 flash red to indicate the reason for any automatic trip operation. Each LED is strategically located in the related segment of the time-current curve depicted on the face of the trip unit. The reason for the trip is identified by the segment of the time-current curve where the LED is illuminated. Following an automatic trip operation, the backup battery continues to supply power to the LEDs as shown in Figure 3.1. The LED pulse circuit, shown in Figure 3.1, is provided to reduce battery burden and will supply a quick flash of the trip LED approximately every 4 seconds. It is therefore important to view the unit for at least 5 seconds to detect a flashing cause of trip indicator.
Following a trip operation, push the Reset/Battery Test button, shown in Figure 1.1, to turn off the LEDs and reset the trip unit.

CAUTION
IF ZONE INTERLOCKING IS NOT TO BE USED (I.E., ONLY STANDARD TIME-DELAY COORDINATION IS INTENDED), THE ZONE INTERLOCKING TERMINALS MUST BE CONNECTED BY A JUMPER FROM TERMINAL B8 TO B9 OF THE BREAKER SECONDARY TERMINALS SO THAT THE TIME-DELAY SETTINGS WILL PROVIDE THE INTENDED COORDINATION.
Zone Selective Interlocking (or Zone Interlocking) is standard for the Digitrip trip unit on the "Short Delay" and "Ground Fault" protection functions (See Figure 3.1). The zone interlocking signal is wired via a single set of wires labeled Zone In (Zin) and Zone Out (Zout) along with a "Zone Common" wire. The Zone Selective Interlocking function on the Digitrip has combined the logic interlocking of "Short Delay" and "Ground Fault." A zone out signal is sent whenever the ground fault pick-up is exceeded or when the short delay pickup is exceeded. Zone Selective Interlocking provides the fastest possible tripping for faults within the zone of protection of the circuit breaker and yet also provides positive coordination among all breakers in the system (mains, ties, feeders, and downstream breakers) to limit a power outage to only the affected parts of the system. When Zone Interlocking is employed, a fault within the zone of protection of the circuit breaker will cause the Digitrip 520V and 520 MCV to simultaneously:
1) Trip the affected circuit breaker immediately
2) Send a signal to upstream Digitrip units to restrain from
tripping immediately. The restraining signal causes the upstream breakers to follow their set coordination times, so that the service is only minimally disrupted while the fault is cleared in the shortest time possible.
For an example of how Zone Selective Interlocking may be used, see Appendix A of this Instructional Leaflet.

Effective 8/2006

I.L. 66A7534H04

Effective 8/2006

ABC
Current Sensors
(See Section 1.4)

Trip
Actuator TA
(See Section 2.2)
FET

Bridge Circuits

Internal Power Supply

Unit Status LED

(See Section 3.2)

Integrated Processor
Custom Designed

Trip

Trip LEDs
(See Section 1.2)

4 bit Latch Chip

LED Pulse Circuit

Battery + 3V
(See Section 6.0)

Residual Ground Detection
(See Section 2.3)
AUX CTs
Typical Phase or Ground Sensing Resistor

Protection Setting
(See Section 4.0)

Zone Interlock Circuitry
(See Section 3.3)

ZOut ZIn

Rating Plug
(See Section 7.0)

Page 13

Figure 3.1 Block Diagram with Breaker Interface

Page 14

I.L. 66A7534H04

4.0 PROTECTION SETTINGS
4.1 General
Before placing any circuit breaker in operation, set each trip unit protection setting to the values specified by the engineer responsible for the installation. Each setting is made by turning a rotary switch, using a small screwdriver. The selected setting for each adjustment appears on the trip unit label.

4.3 Long Delay Time Setting
There are eight available Long Delay Time Settings, as illustrated in Figure 4.2, ranging from 2 to 24 seconds. These settings are the total clearing times when the current value equals 6 times (Ir).

NOTE: The installed rating plug must match the CH TypeV current sensors which establish the maximum continuous current rating of the circuit breaker (In). Instantaneous and ground current settings are defined in multiples of (In).

To illustrate the effect of each protection curve setting, simulated time-current curves are pictured on the face of the trip unit. Each rotary switch is located nearest the portion of the simulated time-current curve that it controls. Should an automatic trip occur (as a result of the current exceeding the pre-selected value), the LED in the appropriate segment of the simulated time-current curve will light red, indicating the reason for the trip.
The available settings, along with the effects of changing the settings, are given in Figures 4.1 through 4.8. Sample settings are represented in box.
4.2 Long Delay Current Setting
There are eight available "Long Delay Settings" as illustrated in Figure 4.1. Each setting, called (Ir), is expressed as a multiple (ranging from .4 to 1) of the current (In). The nominal current pickup value is 110% of the setting.
NOTE: (Ir) is also the basis for the "Short Delay Current Setting" (see Section 4.4).

Figure 4.2 Long Delay Time Settings
NOTE: In addition to the standard "Long Delay Protection Element," trip units also have a "Long Time Memory" (LTM) function, which protects load circuits from the effects of repeated overload conditions. If a circuit breaker is reclosed soon after a Long Delay Trip, and the current again exceeds the Long Delay Setting, (Ir), the LTM automatically reduces the time to trip to allow for the fact that the load circuit temperature is already higher than normal because of the prior overload condition. Each time the overload condition is repeated, the LTM causes the breaker to trip in a progressively shorter time. When the load current returns to normal, the LTM begins to reset; after about 10 minutes it will have reset fully, so the next Long Delay trip time will again correspond to the setting value.

NOTE: In certain applications, it may be desirable to disable the LTM function. Open the test port located at the lower left-hand front of the trip unit and use small, longnose pliers to move the LTM jumper inside the test port (See Figure 4.3) to its Inactive position. (The LTM function can be enabled again at any time by moving the LTM jumper back to its original active position.)

Figure 4.1 Long Delay Current Settings

Effective 8/2006

I.L. 66A7534H04

Page 15

Digitrip Test Kit Port

Test

Test

Kit

Connector

Kit

(Storage)

"LTM Active"

Notch

Connector (Bridging) "LTM Inactive"
(Also Recommended Position for Field Testing)

Figure 4.3 Long Time Memory (LTM) Jumper

The action of the LTM must be considered when performing multiple Long Delay Time tests (See Section 5.4).

4.4 Short Delay Current Setting
There are eight available "Short Delay Current Settings," as illustrated in Figure 4.4. Seven settings are in the range from 1.5 to 10 times (Ir). However there exists an additional maximum setting M1 that is based on (In).It is set for 14x (In) for all rating plugs up to 1250A and 12X for 2000A, 2500A.

REMINDER: (Ir) is the "Long Delay Current Setting."

.1,.3,.4, st1,st2
PLUG st1 st2 100A 0.5 0.5
200-400A 0.5 1.0 600-2500A 1.0 2.0

Short Delay Setting
2 x Ir

Available Settings 1.5, 2, 3, 4, 6, 8, 10, M1
In Multiples of Long Delay Setting (Ir)

M1 Value is Specified on Rating Plug Figure 4.4 Short Delay Current Settings

Figure 4.5 Short Delay Time Settings
Five FLAT (.1, .3, .4, .st1,st2 seconds) and three I2t (.1*, .3*, .5* seconds) response time delay settings are available. The I2t response settings are identified by an asterisk (*). The time settings labeled st1 and st2 are based on the rating plug. For 100A st1 and st2 =0.5s. For 200A through 400A, st1 = 0.5s and st2 = 1s. For rating plugs 600A and greater, st1 =1s and st2 = 2s.The I2t response is applicable to currents less than 8 times the ampere value of Ir rating. For currents greater than 8 x (Ir) the I2t response reverts to the FLAT response.

NOTE: Also see Section 3.3 - Zone Interlocking.

4.5 Short Delay Time Setting
As illustrated in Figure 4.5, there are two different "Short Delay" response curve shapes: fixed time (FLAT) and I2t. The shape selected depends on the type of selective coordination chosen. The I2t response curve will provide a longer time delay for current below 8 x Ir than will the FLAT response curve.

4.6 Instantaneous Current Setting
There are eight available Instantaneous current settings, as illustrated in Figure 4.6. Six settings are in the range from 2 to 10 x (In) the rating plug value, and the other two settings are M1 x (In) and Off. The value that M1 has depends upon the plug rating of the circuit breaker and is specified both on the rating plug label and on the applicable time-current curves referenced in Section 9.

Effective 8/2006

Page 16

I.L. 66A7534H04

Setting Inst. 6 x In
M1 value is specified on rating plug.

Available Settings
2, 3, 4, 6, 8, 10, M1, OFF
In Multiples of Rating Plug Amperes (In)

Figure 4.6 Instantaneous Current Settings

4.7 Ground Fault Current Setting
The eight "Ground Fault Current Settings" are labeled with values from .25 to .75 x (In) and the other one is OFF. (See Figure 4.7). The specific "Ground Current Settings" for each model are listed in Figure 4.7 and on the applicable time-current curve for the circuit breaker.

Gnd-Fault Setting
.4 x In

Available Settings
0.25, .3, .35, .4, .5, .6, .75, OFF

Figure 4.8 Ground Fault Time Delay Settings

Figure 4.7 Ground Fault Current Settings
4.8 Ground Fault Time Delay Setting
As illustrated in Figure 4.8, there are two different Ground Fault curve shapes: fixed time (FLAT) or I2t response. The shape selected depends on the type of selective coordination chosen. The I2t response will provide a longer time delay for current below 0.625 x In than will the FLAT response.

4.9 INCOM (Digitrip 520MCV Models only)
INCOM communication to a host computer or a BIM is possible with the Digitrip 520MCV unit. The address range is 001 through 999. The factory default address is 999 hex.
To set the desired address or to view the address, depress and hold the RESET/BATTERY TEST button for five seconds. Depress the STEP button to select a new address. Users may simultaneously depress and hold in the STEP and RESET/BATTERY TEST buttons for fast advance.

Five FLAT (.1, .2, .3, .4, .5 seconds) and three I2t (.1*, .3*, .5* seconds) response time delay settings are available. The I2t response settings are identified by an asterisk (*). The I2t response is applicable to currents less than 0.625 times the ampere rating of the installed rating plug (In). For currents greater than 0.625 x In the I2t response reverts to the FLAT response.

4.9.1 Breaker Interface Module (BIM)
The Breaker Interface Module (BIM) can be used to monitor up to 31 Digitrip 520MCV trip units. The acceptable addresses are 001 through 031.
4.9.2 Remote Master Computer

NOTE: Also see Section 3.3 - Zone Interlocking.

When desired, Digitrip 520MCV Trip Units can communicate with a BIM or remote master computer (IBM PC compatible with Cutler Hammer Inc. CONI card or MINT ) and using PowerNet communication software version 3.20 or greater. (See Figure 4.9 for typical wiring.)

Effective 8/2006

I.L. 66A7534H04

Page 17

4.9.3 INCOM Network Interconnections
INCOM sends bursts of data on a 92 to 115.2 kHz carrier at a 9600 baud rate over twisted pair conductors to interconnect the many devices comprising the network.
The Digitrip 520MCV will light the red LED shown in Figure 1.1 when transmitting on INCOM.
Recommended cable specifications:
· Cutler-Hammer Inc. cable catalog #IMPCABLE, Style #2A95705G01
· Belden 9463 cable family · Identical Commscope or Quabbin cables

These bursts of data can be captured and used in a variety of ways depending upon the manner in which the master computer software program is written. For example, all the settings can be viewed via the master computer. Another example is that the data for the individual phase current values are available on the network, but the software must select the appropriate data, decode it and display it in a useful manner. Following an over-current trip operation, the sequence of coded data varies slightly. The cause of trip, the value, the phase (or ground) current responsible for the trip are available on the network.

Typical IBM Compatible Computer
2 3 C-H Coni. Card

Breaker Interface Monitor (BIM)
3
See View A

Twisted Pair. No. 18 AWG.

Cut-off Shield or connect to

unused customer

1

terminal -- Do not Ground.

(Y) (BL)
View A

0 0 1
Typical Magnum Circuit Breaker with Digitrip 520MCV Trip Unit

0 0 2

H = 9600 Baud

3 Digit INCOM Address as displayed on Tripunit

Notes: 1 Refer to Master Circuit Breaker Connection Diagrams in Appendix C.
2 Modular telephone connector, Type RJ11, supplied by user.
3 Ground shielding at computer and BIM as shown. Where devices are daisy-chained, interconnect shielding, but do not ground the connection.
100 ohm 1/2 watt carbon terminating resistor required at last breaker. See T.D. 17-513.
See Section 4.9 for programming INCOM function.

Figure 4.9 INCOM Network with Remote Master Computer or BIM

Effective 8/2006

Page 18

I.L. 66A7534H04

5.0 TEST PROCEDURES
5.1 Test Precautions
WARNING
DO NOT ATTEMPT TO INSTALL, TEST, OR PERFORM MAINTENANCE ON EQUIPMENT WHILE IT IS ENERGIZED. DEATH OR SEVERE PERSONAL INJURY CAN RESULT FROM CONTACT WITH ENERGIZED EQUIPMENT.
DE-ENERGIZE THE CIRCUIT AND DISCONNECT THE CIRCUIT BREAKER BEFORE PERFORMING MAINTENANCE OR TESTS.

CAUTION
PERFORMING TESTS WITHOUT THE CUTLERHAMMER- APPROVED TEST KIT MAY DAMAGE THE DIGITRIP UNIT.
5.3 Functional Field Testing
5.3.1 Field Test Kit

WARNING
ANY TRIPPING OPERATION WILL CAUSE DISRUPTION OF SERVICE AND POSSIBLE PERSONAL INJURY, RESULTING IN THE UNNECESSARY SWITCHING OF CONNECTED EQUIPMENT.

Use the test receptacle to verify a functional load test of a major portion of the electronic circuitry of the Digitrip trip unit and the mechanical trip assembly of the circuit breaker. The testing can determine the accuracy of the desired trip settings by performing Long Delay, Short Delay, and Ground Fault functional tests. The CutlerHammer approved test kit is listed below.

CAUTION
TESTING A CIRCUIT BREAKER WHILE IT IS IN-SERVICE AND CARRYING LOAD CURRENT IS NOT RECOMMENDED.
TESTING OF A CIRCUIT BREAKER THAT RESULTS IN THE TRIPPING OF THE CIRCUIT BREAKER SHOULD BE DONE ONLY WITH THE CIRCUIT BREAKER IN THE TEST OR DISCONNECTED CELL POSITIONS OR WHILE THE CIRCUIT BREAKER IS ON A TEST BENCH.

Model
Digitrip 520V and 520MCV

Test Kit
Test Kit (140D481G02R, 140D481G02RR, 140D481G03, or G04) with Test Kit Adapter 8779C02G04

The test port is located on the front left-hand corner of the trip unit (See Figure 1.1). To access the port, remove the plexiglass cover from the front of the circuit breaker. Using a small screwdriver, gently pry up on the test port cover to remove this item.

CAUTION

5.2 When to Test
For Draw-Out Breakers, testing of the Digitrip trip unit prior to start-up can best be accomplished with the circuit breaker out of its cell or in the Test, Disconnected, or Withdrawn (or Removed) cell positions.
NOTE: Since time-current settings are based on desired system coordination and protection schemes, the protection settings selected and preset in accordance with Section 4.0 should be reset to their as-found conditions if altered during any routine test sequence.

BEFORE PLUGGING A TEST KIT INTO THE TEST PORT, PLACE THE LTM JUMPER IN THE INACTIVE POSITION (See Figure 4.3). AFTER TESTING, RETURN THE LTM JUMPER TO ITS ORIGINAL POSITION.
The test kit authorized by Cutler-Hammer for use with the Digitrip 520V and 520MCV, plugs into the test port of the trip unit and provides a secondary injection AC test current that simulates the CH Type-V current sensors. Test kits styles 140D481G02R, 140D481G02RR, 140D481G03 or G04, along with the Test Kit Adapter 8779C02G04, can be used to test the trip unit and circuit breaker.

Effective 8/2006

I.L. 66A7534H04

Page 19

5.3.2 Handheld Functional Test Kit
5.3.2.1 Description of Handheld Test Kit
A battery powered test kit is also available and capable of testing trip elements for Digitrip 520V and 520MCV units, including power up, Instantaneous Trip, Short Delay Trip, and Ground (Earth) Fault Trip. These test selections are chosen with the switch labeled Select Test located in the upper right hand corner of the test kit (See Figure 5.1). The test currents are DC currents set at the factory and are not adjustable.
The style number of this device is # 70C1056G52 (120VAC) or #70C1056G53 (230VAC).
5.3.2.2 Test Procedure
Complete procedural instructions for the Cutler Hammer Mini Test Kit can be found in I.L. # 5721D13 which is packaged with each test kit.

5.3.2.3 Currents
Each test chosen by the Select Test switch on the test kit supplies a fixed milliampere current value.
NOTE: The Long Delay Setting will affect the per unit (Ir) current value.
5.3.2.4 Batteries
This Functional Test Kit contains a total of seven 9-Volt batteries. A lithium ion cell is the preferred battery type for Battery Voltage (A) and is attached to the main pc board of the test kit. This battery has a much longer life span to accurately perform the selected tests. The remaining six batteries are located on a separate board in the test kit and serve to power up the Digitrip trip unit.
Battery status LED's A and B function to represent sufficient voltage from both the single lithium cell and the six Alkaline batteries, respectively. If either LED does not light or lights dimly, replace the appropriate battery or batteries within the test kit case. To do this, open the back of the case using a screwdriver and remove the battery or batteries from their respective locations. For best results, replace lithium battery (Battery A) with ULTRALIFE® U9VL Battery. When replacing battery six-pack (Battery B), replace all batteries at the same time using standard 9V alkaline batteries.

5.4 Performance Testing of Digitrip 520V and 520MCV Trip Units

Figure 5.1 Functional Test Kit NOTE: After completion of testing,
1. Disconnect secondary connector with jumper

5.4.1 General The complete circuit breaker should be tested after sensor wiring is completed. The AVO Multi-Amp® model MS-2 or equivalent current source can be used to perform this test (See Figure 5.2).
5.4.2 Testing using MS-2 Multi AMP® Tester

2. Disconnect test input cable

5.4.2.1 Description of MS-2 Tester

3. Reposition all trip unit settings to "as found" 4. Reposition the LTM (Long Time Memory) jumper 5. Reinstall the test port cover on the Digitrip 6. Reinstall plexiglass cover to circuit breaker

The portable (33lb/15kg) AVO Multi AMP® tester, model MS-2 can be used to check out Digitrip 520V. There are two levels of testing that can be done. A primary or secondary injection test can be done. The primary injection test is good for verifying both CH Type-V current sensor polarity and hookup through the circuit breaker's secondary

Effective 8/2006

Page 20

I.L. 66A7534H04

contacts and into the Digitrip trip unit. This is a complete system checkout and is strongly recommended after initial setup and before enerizating of the gear. Although the MS2 source is limited to 600 amperes (momentary), it can verify that the trip unit powers up properly and perform a ground fault trip of the circuit breaker. This testing at the primary injection level is able to verify that the breaker's response to each primary phase current is correct. The secondary injection current source is able to deliver up to 5x (1 ampere is 1 per unit) into the breaker's secondary contacts. This can produce a 300% overload test and a 400% Short Time or Instantaneous test.

The following extra components are desirable additions for the testing.

1. For the primary injection testing, three separate flexable (welding type) cables (#2 AWG or larger) and each about 3' (.914m) long, are required to be fabricated. Connectors, with tabs, need to be attached on each end to connect to the tester's terminal studs. The flat tab extension will also provide a surface to attached to the gear's bus conductors using C-clamps. A typical connector style would be an ILSCO style SLS125.
2. For secondary injection tests, a separate True RMS ammeter with a "peak hold" feature is required (See Figure 5.5). The built in meter of the MS-2 tester is not True RMS and does not provide an accurate measurement of the secondary injection current. This is because of the trip unit's "chopper" power supply. The peak hold feature will hold the trip current level when an auxilary switch from the circuit breaker is wired back to the tester's terminals (white posts) labeled Contacts.

Figure 5.2 AVO MultiAmp® MS-2 Test Source
b. Set Digitrip Ground Setting to "0.4" and remove (if any) jumpers connected on secondary points B-6, B-7 (See Figure 1.6).
c. Connect one end of the primary current cables to the 240A and Common posts of the MS-2 test source. Connect the other ends to the line and load side of the breaker's left pole(Phase "A"). This will provide a primary current through CH Type-V current sensor for the test.
d. Set MS-2 built-in meter to 750A scale.

3. Also when performing low current secondary injection tests (less than 2 Amperes) it is desirable to insert an additional 25 ohm impedance (resistor or inductor) rated at 25 or 50 watts in series with the 5A terminal post. This will provide proper impedance for the "chopper" and is useful in stablizing the current (See Figure 5.5).

IMPORTANT: Do the following test even if ground fault is to be set to OFF or Zero Sequence Sensing is chosen for the final application.

5.4.2.2 Primary Injection Testing

Preliminary hookup:

a. Connect an Aux Switch or unused unused circuit breaker pole to the Contacts input terrminals of the MS-2 current source to hold current ramp value level and to stop the timer.

Effective 8/2006

I.L. 66A7534H04

Page 21

Suitable Conductors

A

B

C

Note: For circuit breakers with 100A thru 400A sensors the Ground Fault Setting could be raised or turned OFF and either "Long Time" or "Short Time" tests could be conducted. Adjusting the Long Delay Setting to 0.4x would help to minimize the current requirements to simulate to overload levels.

Low-Voltage ac Current Source

Polarity & Identification

The above test essentually proves out the sensor wiring, the rating, the rating plug as well as polarity of the CH Type-V current sensors and tripping of the circuit breaker.

Suitable Conductors

A

B

C

Figure 5.3 Connection Details to verify a trip (Ground) Test Procedure:

Low-Voltage ac Current Source

Polarity & Identification

TEST 1. Close circuit breaker and ramp up current using the Output Control knob of MS-2 and by setting selector switch to the Maintain position. At about 30% of the Rating Plug value, check for the green Unit Status LED to flash consistently at a one second interval. (See Figure 1.1)

Shorting Conductors
Figure 5.4 Connection Details to verify Sensor Polarities
5.4.2.3 Secondary Injection Testing

TEST 2. Continue ramping up current and the circuit breaker should trip via ground element between 40 to 50% of plug rating.
This test arrangement checks both the phase current sensor and the residual ground element since a single pole is energized. (See Figure 5.3)
TEST 3. Repeat Test 1 and 2 on other two poles.
TEST 4. Connect primary current circuit such that two circuit breaker poles (See Figure 5.4) are in series and ramp current up to 40% of plug rating. The Digitrip's Unit Status LED should now flash at about 15% rating plug value with two poles energized. Continue ramping up current toward 40%. The circuit breaker should not trip. If the CH Type-V current sensor's polarities are incorrectly wired, the circuit breaker will trip out on ground fault at about 20%. If a ground fault trip occurs, check secondary wiring of CH Type-V current sensors for proper polarity.

If desired, further testing can be done by injecting test current across the CH Type-V current sensor's output terminal screws or injecting directly into the circuit breaker's secondary contacts (A-4, A-19) or (A-5, A-20) or (A-6, A-21) (See Figures 1.5 and 5.5)
Note: If the circuit breaker is out of the cell, it may be beneficial to make a test harness. The test harness will have female AMP sockets (#66598-2) in one housing on the one end. The other should consist of spade terminations that connect to the 5A and Common posts on the MS-2 current source.
An inductor (Signal Transformer CL-1-2) or 25 ohm resistor should be placed in series with the red terminal post to stablize the output for currents less than 1.5 amperes. Attach the separate True RMS ammeter in series with this component. The rest of the wiring is direct to the phase input secondary contacts.
Hook up a circuit breaker Aux Switch to the MS-2 tester's Contacts terminals to stop the clock and the source of current.

Effective 8/2006

Page 22

I.L. 66A7534H04

5A
Current Source (AVO Type MS-2
or equivalent)

25 Ohm - 25W
Stabilizing Resistor

Contacts (Binding Posts)

Com

Ammeter
RMS Ammeter with Peak Hold

To Secondary Terminals of Phase A, B or C A = A-4 & A-19 B = A-5 & A-20 C = A-6 & A-21
Circuit Breaker

Circuit Breaker AUX Switch
Figure 5.5 Secondary Injection Test Setup

Test Procedure:

Equation for trip time @ 300%

TEST 1. Turn power switch ON and ramp up current slowly looking for the Digitrip's Unit Status LED to flash consistently at one second intervals. This power up should occur at 25 to 35% (about 0.3A for this single phase input).

"Max. Long Time" trip(sec) = Long DelayTime setting X 4 "Min. Long Time" trip(sec) = Long Delay Time setting X 2.8

TEST 2. Keep increasing current and note where the flashing Unit Status LED is about four times faster. This point is the "Long Delay Pickup Point" and is nominally 1.1x Long Delay Setting.
NOTE: The AVO MS-2 Test Source is not a perfect source, particularly when it encounters the "chopper" power supply of the Digitrip so the exact point may be difficult to determine.

The breaker should trip within the above range and "Long Time" trip LED should flash. Check battery if this cause of trip LED does not flash.
TEST 4. The "Short Delay" or "Instantaneous" trip elements (set @ 4x) can also be checked by ramping current. Close circuit breaker. Place the separate meter in the "Hold" mode. Ramp current until trip the circuit breaker trips (expected range of 3.6 to 4.4 A). Appropriate trip LED should flash.

TEST 3. Set the current to 300% which is 3A (+/- 0.1). Remove or short out the series resistor for the trip tests.
NOTE: Three Amperes is truly 300% only when the Long Delay Setting is set to 1x. Other 300% test current levels will need to be calculated if the Long Delay Setting is set other than 1x. Set Ground Setting to OFF, Instantaneous to 4x and Short Delay Setting to 8x.
Run 300% overload to trip the circuit breaker on "Long Time."

NOTE: As the MS-2 tester has limited current source capabilities, testing of the Digitrip 520V and 520MCV could be assisted by the handheld tester shown on page 16. The handheld unit, when its connector is plugged into the test kit input pins of the Digitrip, provides external power to the trip unit to stabilize the "chopper" power supply. Use the Power Up switch position of the handheld and make sure there is a feedback Aux Switch present. This is required to shut off the MS-2 current source when tripping occurs. This will also enable higher per unit testing levels.

Effective 8/2006

I.L. 66A7534H04

Page 23

6.0 TRIP UNIT BATTERY

Company

Model

6.1 General
The battery plays no part in the protection function of the trip unit.

VARTA Batteries, Inc. 300 Elmsford Boulevard Elmsford, N.Y. USA 10523 1-914-592-2500 (www.varta.com)

Activate the battery by removing the Battery Insulating Tab by taking out the battery and then removing and discarding the tab. (See Figure 6.1).
As indicated in Figure 3.1, the battery is provided to maintain the red LED indication of the "cause of trip" in the Digitrip. The battery is located behind the rating plug door. A Reset/Battery Test pushbutton and a green Battery Check LED are located on the trip unit.

Duracell, Inc. Berkshire Corporate Park Bethel, CT USA 06801 1-800-551-2355 (www.duracell.com)
Sanyo Energy Corporation 2055 Sanyo Avenue San Ysidro, CA USA 92173 1-619-661-6620 (www.sanyo.com)

CR 1/3N DL 1/3N CR 1/3N

Insulating Tab

Rating Plug door flipped open

6.3 Battery Installation and Removal

USE TYPE 1/3 N LITHIUM BATTERY ONLY
Pull to Remove Battery
Figure 6.1 Battery located behind Rating Plug
6.2 Battery Check
The battery is a long-life, lithium, camera-type cell. Check the status of the battery at any time by pressing the Reset/Battery Test pushbutton and observing the green LED. If the Battery Check LED does not light green, replace the battery. The condition of the battery has no effect on the protection function of the trip unit. Even with the battery removed, the unit will still trip the breaker in accordance with its settings. However, without the battery, the "cause of trip" LED will not flash red. If the battery is replaced, one or more of the "cause of trip" LEDs may be illuminated. Push the Reset/Battery Test button to turn off the indicators. The trip unit will now be ready to indicate the next cause of trip.
NOTE: The battery can be replaced at any time, even while the circuit breaker is in service, without affecting the operation of the circuit breaker or its protection functions.
The replacement battery should be the same type as found in in the trip unit or proper equivalent. Acceptable 3.0 volt lithium batteries may be obtained from the following companies:

The 3-volt lithium cell battery (See Figure 6.1) can easily be removed and replaced. The battery is located in the cavity adjacent to the rating plug mounting screw, but is not part of the rating plug. Insert a small screwdriver at the left side of the rating plug and to the left of the word OPEN. Cover door should now flip open. Remove the old battery by pulling up on the removal tab that wraps under the cell. When inserting the new battery, pay special attention to ensure that the proper polarity is observed. The main body of the battery is the positive (+) side.
CAUTION
EXERCISE CARE WHEN REPLACING THE BATTERY TO ENSURE THAT THE CORRECT POLARITIES ARE OBSERVED. POLARITY MARKINGS ARE SHOWN ON THE RATING PLUG WHEN THE HINGED COVER IS OPEN. ACCIDENTALLY INSTALLING THE BATTERY IN THE REVERSE DIRECTION WILL NOT HARM EITHER THE TRIP UNIT OR THE BATTERY, BUT WILL DEFEAT THE FUNCTION OF THE BATTERY.

Effective 8/2006

Page 24

I.L. 66A7534H04

7.0 FRAME RATINGS (SENSOR RATINGS AND RATING PLUGS)

WARNING

The frame rating of a circuit breaker is the maximum RMS current it can continuously carry. The maximum shortcircuit current rating of the circuit breaker is usually related to the frame rating as well.
There are two frame ratings for this circuit breaker using the Digitrip 520V and 520MCV trip units as follows:
A current value, (In), that is less than the full frame rating may be chosen to be the basis for the coordination of the protection function of the breaker without affecting its short-circuit current capability. For Digitrip units, this is implemented by changing the CH Type-V current sensors and the corresponding rating plug. These sensors and rating plugs are available in kit form.
The CH Type-V current sensor rating is the maximum current the circuit breaker can carry with the specified sensors installed. Their rating can be the same or less than the frame rating, but not greater.

BEFORE YOU FIT THE RATING PLUG INTO THE TRIP UNIT, BE SURE TO CHECK THAT EACH BREAKER POLE HAS AN EXTERNALLY MOUNTED SENSOR THAT IS WIRED TO THE CIRCUIT BREAKER'S SECONDARY CONTACTS. THESE SENSOR RATINGS MUST MATCH THAT PRINTED ON THE RATING PLUG. INSTALLING A RATING PLUG THAT DOES NOT MATCH THE SENSOR RATING CAN PRODUCE SERIOUS MISCOORDINATION AND/OR FAILURE OF THE PROTECTION SYSTEM.
8.0 RECORD KEEPING
Use the forms shown in Figures 8.1 and 8.2 for record keeping. Fill in these forms, giving the indicated reference information and initial time-current trip function settings. If desired, make a copy of the form and attach it to the interior of the breaker cell door or another visible location. Figure 8.3 provides a place for recording test data and actual trip values.

This value, (In), is the basis for the trip unit current settings:
1. The Instantaneous Current Settings are multiples of (In) (See Sections 4.6).

Ideally, sheets of this type should be used and maintained by those personnel in the user's organization that have the responsibility for protection equipment.

2. The Ground Current Settings are multiples of (In) (See Section 4.7). The one exception would be if the Zero Sequence sensor is employed. It is a tapped sensor with 100A and 200A selections.
3. The Long Delay Current Setting, (Ir), is a fractional multiple of (In): Long Delay Current Setting = (Ir) = LD x (In) (See Section 4.2).

9.0 REFERENCES

9.1 Medium Voltage Type VCP Circuit Breakers

I.B. #69C3067

ANSI Breaker Instructions

I.B. #69C3066

IEC Breaker Instructions

4. The Short Delay Current Setting is a multiple of (Ir): Short Delay Current Setting = SD x (Ir) = SD x [LD x (In)] (See Section 4.4).

9.2 Time-Current Curves
The Time-Current Curves are listed below for particular trip unit models. All protection function time-current settings should be made following the recommendations of the specifying engineer in charge of the installation.

#5720B80 #5720B81 #5720B82 #5721B77

Digitrip 520V/520MCV (LS) Curve Digitrip 520V/520MCV (I) Curve Digitrip 520V/520MCV (G) Curve Digitrip 520MCV Maintenance Mode Trip Curve

Effective 8/2006

I.L. 66A7534H04

Page 25

Circuit No./Address

DIGITRIP
TRIP FUNCTION SETTINGS
Breaker Shop Order Reference

Rating Plug Amperes (In)

PER UNIT MULTIPLIERS
Ir Continuous Ampere Rating = LDS x In

Trip

Per Unit

Function

Setting

Multi

Inst.

In

Long Delay

In

Short Delay

Ir

Ground Fault Date

In By

Ampere Equivalent
Setting

Time Delay

Sec. Sec. Sec.

Figure 8.1 Typical Trip Function Record Nameplate
Effective 8/2006

Page 26

Circuit No./Address

DIGITRIP
AUTOMATIC TRIP OPERATION RECORD
Breaker Shop Order Reference

I.L. 66A7534H04

Trip Function
Instantaneous Long Delay Setting Long Delay Time Short Setting Short Time Ground Fault Setting Ground Fault Time

Orig. 0

Date of Trip

Trip Mode Indicator

Settings Reference

Rev. 1

Rev. 2

Rev. 3

Setting Ref.

Setting Change Made

Investigated By

Figure 8.2 Automatic Trip Operation Record

Effective 8/2006

I.L. 66A7534H04

GROUND FAULT TEST RECORD FORM

Ground Fault Test Record should be retained by those in charge of the building's electrical installation in order to be available to the authority having jurisdiction.

Test Date

Circuit Breaker Number

Results

Tested by

Page 27

Figure 8.3 Typical Performance Test Record Form
Effective 8/2006

Page 28
APPENDIX A Zone Interlocking Examples

I.L. 66A7534H04

NOTICE
THE PROVISION FOR ZONE INTERLOCKING IS STANDARD ON CIRCUIT BREAKERS WITH DIGITRIP 520V TRIP UNITS FOR SHORT TIME AND GROUND FAULT FUNCTIONS. THE APPROPRIATE JUMPER TO TERMINAL B8 AND B9 MUST BE ADDED ON THE BREAKER IF ZONE INTERLOCKING IS NOT DESIRED OR IF FIELD TESTING IS DESIRED.
EXAMPLE 1: There is no Zone Selective Interlocking. (Standard time delay coordination is used.)
Assume that a ground fault of 2000 Amperes occurs and refer to Figure A.1.
Fault at location 3 The branch breaker will trip, clearing the fault in 0.1 seconds.
Fault at location 2 The feeder breaker will trip, clearing the fault in 0.3 seconds.
Fault at location 1 The main breaker will trip, clearing the fault in 0.5 seconds.

EXAMPLE 2: There is Zone Selective Interlocking.
Assume a ground fault of 2000 Amperes occurs and refer to Figure A.1.
Fault at location 3 The branch breaker trip unit will initiate the trip in .045 seconds to clear the fault and the branch will send a restraint signal to the feeder trip unit; the feeder will send a restraint interlocking signal to Z1.
Main and feeder trip units will begin to time out and, in the event that the branch breaker does not clear the fault, the feeder breaker will clear the fault in 0.3 seconds (as above). Similarly, in the event that the feeder breaker does not clear the fault, the main breaker will clear the fault in 0.5 seconds (as above).
Fault at location 2 The feeder breaker trip unit will initiate the trip in 0.045 seconds to clear the fault and will send an interlocking signal to the main trip unit. The main trip unit will begin to time out and, in the event that the feeder breaker Z2 does not clear the fault, the main breaker will clear the fault in 0.5 seconds (as above).
Fault at location 1 There are no interlocking signals. The main breaker trip unit will initiate the trip in 0.045 seconds.
Figure A.2 presents a Zone Selective Interlocking connection diagram for a system with two main breakers from incoming sources and a bus tie breaker. Note that the blocking diode D1 is needed so that the feeder breakers can send interlocking signals to both the main and the tie breakers and prevent the tie breaker from sending an interlocking signal to itself.

Effective 8/2006

I.L. 66A7534H04
1200A 800A 200A

Page 29
NOTES: A1: Wiring to be twisted pair of AWG #14 to #20. Route Zone
Interlocking wiring separate from power conductors. DO NOT GROUND (EARTH) any Zone Interlock Wiring. A2: The maximum distance between two farthest breakers on different zones (from the ZO downstream to ZI upstream terminals) is 250 feet (76m). A3: A maximum of 20 breakers may be connected in parallel in one zone.
Is desired with other downstream breakers.
- B7 Contact - B9 Contact - B8 Contact

Figure A.1 Typical Zone Interlocking

See Note A4

F11 C ZO ZI
0.1 Sec

M1 C ZO ZI
0.5 Sec

T C ZO ZI
0.3 Sec

M2 C ZO ZI
0.5 Sec

F12 D1 C ZO ZI
0.1 Sec

1N4004

F21 C ZO ZI
0.1 Sec

F22 C ZO ZI
0.1 Sec

F23 C ZO ZI
0.1 Sec

Figure A.2 Typical Zone Interlocking Connections with Two Main Breakers (M1, M2) and a Tie Breaker (T)

Effective 8/2006

Page 30
Appendix B Troubleshooting Guide

I.L. 66A7534H04

Symptom

Probable Cause

Possible Solution(s)

References

Unit status LED is not blinking Current through breaker is <25% of sensor rating

No problem. Status LED will not operate with breaker currents <25% of sensor rating

Unit Status LED is steady on

Trip unit is malfunctioning Light loading

Trip unit is malfunctioning.

Replace trip unit
No problem. Unit Status LED will not flash until 25% of sensor rating
Replace trip unit

See Note in Section 3.2

As soon as current starts to flow through the breaker, it trips and the Instantaneous trip LED comes on

Rating plug is not installed or is loose
Rating plug is open internally
Trip unit is malfunctioning

Install rating plug and/or check for loose connections
Replace rating plug
Replace trip unit.

LED does not come on when battery check button is pressed
Breaker trips on ground fault

Battery installed backwards
Dead battery
Trip unit is malfunctioning
There actually is a ground fault
CH Type-V current sensors in one or more phases have incorrect polarity

Install correctly Replace battery Replace trip unit Find location of the fault
Verify circuit breaker wiring

Refer to Appendix C

Breaker trips too rapidly on ground fault or short delay (Zone Selective Interlocking not used)
Breaker trips too rapidly on long delay

Trip unit is malfunctioning
High inrush phase currents may cause fictitious ground pickup momentarily
Connection from Zout to Zin is missing
Trip unit settings are not correct
Trip unit is malfunctioning
Long Time Memory selected
Trip unit settings are not correct

Replace trip unit Connect Zout to Zin jumper to provide some time delay
Make connections B8 to B9
Change settings
Replace trip unit. Turn off Long Time Memory Change settings. Long Time Delay setting is based on 6×Ir

See Caution in Section 3.3 Refer to Appendix A
Refer to Section 4.3

Effective 8/2006

I.L. 66A7534H04

Page 31

Symptom Cause of Trip LEDs flashing and breaker is closed
A Cause of Trip LED keeps retriggering in the application (Digitrip 520MCV)

Probable Cause
Trip Unit was not reset from previous event or test.
Battery voltage too low to reset latch chip and LEDs
Digitrip Memory Buffer not completely reset

LCD Display is not energized. Light load.

No auxiliary power unit.

Circuit breaker containing Digitrip 520MCV* does not communicate with PowerNet or BIM.

Wrong Address No Power

* Only Digitrip 520MCV styles have communication features. Hardware Problem

Possible Solution(s)

References

Depress Reset Pushbutton to clear LED flashing

Replace battery

See Section 6.2

Need to reset Digitrip unit when Status LED is operational. Possibly do this by temporarily ( or permanently) adding Aux Power and then depress Reset pushbutton to fully clear trip buffer.

See also Note in Section 5.3.2.2

Check breaker ordering information.

Refer to Sections 1.6 and 1.6.1

Check voltage input terminals Refer to Sections 1.6 and

A14 ­ A15.

1.6.1

Check Address

See Section 4.9

Check for Aux. Power ­ A14, A15
Check Status LED and Transmit LED
Check Communications Wiring ­ B1, B2
Missing Termination Resistor

See Figure 1.1 and Refer to Section 1.6
See Appendix C See Figure 4.9

Effective 8/2006

Effective 8/2006

A

B

C

ZONE_COM B-7

SEE NOTE 3
SEE NOTE 4
X1 ZERO SEQUENCE GF
50:1 or 100:1, 200:1

B-8 B-9
B-6 B-5 B-4

ZONE_IN ZONE_OUT
GF_SGND X1 X2

BLACK

B-1 B-2
A-12

WHITE

K2-1

Z_COM

GREEN
1 (COM)

RED 52b 3 MCR (N/O)

K2-2 K2-3

BRKCLSD +32VDC INPUT

BROWN ACTN

K2-4 K2-5 K2-6
K2-7 K2-9

10:1
BLACK +

K2-8 K1-1 K1-2

TA

24 OHM

K1-3

I1-1 I1-2 I1-3 I1-9

Z_IN Z_OUT G_ALARM
GF_SGND N1 N2 DGND
ST1
ST-
INCOM N INCOM P MM-ALARM MM-ENABLE

Rating Plug

NOTES:
1. ALL AUX. SWITCHES SHOWN WITH CIRCUIT BREAKER IN OPEN POSITION AND WITH SPRING NOT CHARGED AND WITH TRIP UNIT IN "NON-TRIPPED" STATE (OTS SWITCHES).
2. THE SPRING RELEASE ACCESSORY CONSISTS OF AN "SR" COIL AND A P.C. BOARD. THE PRINTED CIRCUIT PROVIDES A .20 SECOND PULSE FOR THE CLOSING OPERATION. VOLTAGE MUST BE REMOVED AND THEN REAPPLIED FOR SUBSEQUENT OPERATION.
THE LATCH CHECK SWITCH (LCS) ACTS AS A "LOGIC" INPUT TO THE "SR" DEVICE. THE CLOSE SIGNAL PULSE WILL NOT BE SENT UNTIL THE CIRCUIT BREAKER IS RESET.
3. TO PROVIDE SELECTED TIME DELAYS FOR SHORT TIME AND/OR GROUND TIME FUNCTIONS FOR TESTING OR FOR NON-ZONE INTERLOCKING APPLICATIONS, A JUMPER FROM B-8 TO B-9 IS REQUIRED.
4. ON CIRCUIT BREAKERS HAVING THE GROUND FAULT ACTIVE, A JUMPER INSTALLED FROM B-6 TO B-7 WILL ENABLE SOURCE GROUND FAULT SENSING AND DISABLE RESIDUAL GROUND FAULT SENSING, INPUTS B-4 AND B-5 WILL BE REASSIGNED FOR ZERO SEQUENCE GROUND SENSOR INPUTS.
5. MOTOR OPERATOR SWITCH SHOWN WITH CIRCUIT BREAKER CLOSING SPRING DISCHARGED.
SECOND SHUNT TRIP MAY BE INSTALLED (USING A-7, A-8 CONTACTS) IN PLACE OF UVR. AUX. SWITCH NOT AVAILABLE WITH SECOND SHUNT TRIP.

LOAD

H

X1

R/1

FIELD WIRING OF CURRENT SENSORS FOR FIXED BREAKERS REQUIRES A MAXIMUM LENGTH OF 12 FEET (3.66 METERS) OF #14 AWG WIRE.
NOTE: SEE DETAIL ON RIGHT FOR DRAWOUT CIRCUIT BREAKER INFORMATION.

H

X1

R/1

H

X1

R/1

BRN

A-4 CSA1

WHT

ACTA

K1-9

A-19

CSA2

10:1 BRN

K1-8 K1-7

A-5

CSB1

ACTB

A-20

CSB2

10:1 BRN

K1-6 K1-5

DIGITRIP 520MCV Trip Unit

A1

A2

B1

B2

C1

C2

A-6

CSC1 WHT

A-21

CSC2

K1-4

WHT ACTC 10:1

GROUND ALARM POWER SUPPLY
MODULE
MAINTENANCE MODE

J3-1 J3-2 J3-3 J4-6 J4-5 J4-4 J4-3
J4-2 J4-1

G_ALARM OUTPUTOUTPUT+ MM_ALARM MM_ALM RELAY _C OM G_ALM

SR-LCS SR
SEE NOTE 2

PCB AC
AC
ATR_ALARM 2 ATR_REL_COM ATR_ALARM 1 ATR_VOLT ATR V_COM

ELECTRIC OPERATOR

(OPT.)

BRIDGE RECTIFIER (WHEN REQ.)
AC

MOTOR

MOTOR CUT-OFF SWITCH

AC

RESISTOR

(WHEN REQ.)

SC M OTOR+
MOTOR-

SEE NOTE 6

2

52a

1

ST

SEE NOTE 6

ST

ST AC

UVR UVR
AC

B-13 CLOSE COIL B-12 CLOSE CONTA CT SEE NOTE 2
A-9 A-10 A-11 A-14 A-15
A-16 B-15
B-14
B-10 B-11 A-7

AC

AC

UVR

A-8

AUXILIARY SWITCH

A-23

A-24 2
A-25

3

4

A-26 A-27

DETAIL (PARTIAL) FOR DRAWOUT BREAKER

5

7

8

10

A-28 A-29
A-30 B-19
B-20 B-21

1

12

B-22 B-23

13

14

B-24 B-25

15

17

B-26 B-27

16

18

B-28 B-29

19

20

B-30

DRAWOUT GEAR UMBILICAL CABLING R/1
WIRE LENGTH MAXIMUM FOR DRAWOUT GEAR IS 10 FEET (3.05 METERS) #14 AWG.

Page 32
Appendix C Typical Breaker Master Connection Diagram

I.L. 66A7534H04

I.L. 66A7534H04
Appendix D MODBUS TRANSLATOR Wiring

Page 33

The Digitrip 520MCV in a Medium Voltage Circuit Breaker can communicate its data using Modbus RTU protocol by employing an mMINT device to act as a translator from INCOM communication to MODBUS communications. A Modbus master device is shown wired to gather data.
The mMINT module CAT #MMINT use DIN rail mounting. Connector types are plug-in-Phoenix. . Power is 5 pin. INCOM network uses a 3 pin. The RS-485 MODBUS uses a 4 pin connector which consist of signals A, B, COMmon and SHielD.
Three Baud rates of 1200, 9600 or 19200 are selectable via programming switch for the MODBUS network. The INCOM Baud rate is fixed at 9600 Baud.

B-1

B-2

Digitrip 520 M CV

COM Inv Non Invert Input
Modbus Master

2

B-1

B-2

Digitrip 520MCV

A B COM SHD
MMINT

1

3

Circuit Breaker

Circuit Breaker

Notes:

1 Control voltage is 120 VAC ± 20% or 48 - 125VDC.
2 Communication Cable is C-H style 2A957805G01 or Belden 9463 cable. 3 The overall network will support up to 32 devices with any addresses from 1 to 247 4 Terminating resistor is 121 ohm 1 watt. Use the mMINT switches to insert these terminators at the mMINT device.

Effective 8/2006

Page 34
DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY
The information recommendations, descriptions and safety notations in this document are based on Eaton's experience and judgment and may not cover all contingencies. If further information is required an Eaton sales office should be consulted.
Sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton Electrical Inc. selling policies or other contractual agreement between Eaton and the purchaser.
THERE ARE NO UNDERSTANDINGS, AGREEMENTS, WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES. ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON ELECTRICAL INC. THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES.
IN NO EVENT WILL EATON ELECTRICAL INC. BE RESPONSIBLE TO THE PURCHASER OR USER IN CONTRACT, IN TORT (INCLUDING NEGLIGENCE), STRICT LIABILITY OR OTHERWISE FOR ANY SPECIAL, INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGE OR LOSS WHATSOEVER, INCLUDING BUT NOT LIMITED TO DAMAGE TO OR LOSS OF USE OF EQUIPMENT, PLANT OR POWER SYSTEM, LOSS OF PROFITS OR REVENUES, OR CLAIMS AGAINST THE PURCHASER OR USER BY ITS CUSTOMERS RESULTING FROM THE USE OF THE PRODUCTS OR INFORMATION, RECOMMENDATIONS AND DESCRIPTIONS CONTAINED HEREIN.
Eaton Electrical, Inc. 1000 Cherrington Parkway Moon Township, PA 15108-4312 United States Tel.: 1-800-525-2000 www.EatonElectrical.com

I.L. 66A7534H04
Cutler-Hammer is a federally registered trademark of Eaton Corporation. Digitrip is a trade-
mark of Eaton Corporation. © 2006 Eaton Corporation All Rights Reserved Printed in USA
Publication No. I.L. 66A7534 August 2006
Effective 8/2006


Acrobat Distiller 6.0.1 (Windows)