Technical Data
Original Instructions
PowerFlex 70 Adjustable Frequency AC Drive
Catalog Number 20A

Topic

Page

Summary of Changes

2

Product Overview

3

Catalog Number Explanation

6

Product Selection

7

Factory-installed Options

12

User Installed Options

14

Installation Power Wiring

22

Terminal Blocks

23

Cable Recommendations

28

Power Ratings and Branch Circuit Protection

30

Mounting

34

Approximate Dimensions and Weights

35

PowerFlex 70 Configured Drives

40

Standard Drive Certifications and Specifications

42

Derating Guidelines

47

Summary of Changes

This publication contains the following new or updated information. This list includes substantive updates only and is not intended to reflect all changes.

Topic Added statements about conformal coat on the drive and enclosure Changed the Catalog Number Explanation section Changed the explanations of where internal EMC filters are used Added the Product Selection section Changed the Isolation Transformers section

Page 3, 6 6 6, 13, 26 7...8 18

2

Rockwell Automation Publication 20A-TD001L-EN-P - December 2020

Product Overview
PowerFlex� 70 drives are designed to worldwide standards providing out-of-the-box performance around the globe. Available ratings include these options:
� 0.5...25 Hp output at 240V AC input � 0.5...50 Hp output at 480V AC input � 0.5...50 Hp output at 600V AC input
The PowerFlex 70 drive can be used with a full featured LCD human interface module (HIM) that provides multilingual text for startup, metering, programming, and troubleshooting.
The PowerFlex 70 can be programmed for either volts per Hertz, sensorless vector, or vector control with FORCETM Technology to cover a wide range of applications from fans to extruders.
Optional internal communication modules provide fast and efficient control and/or data exchange with host controllers over popular interfaces. These interfaces include: Connected Components WorkbenchTM software, DeviceNet�, Ethernet�, ControlNet�, serial communications, and other open control and communication networks. Computer tools such as DriveExplorerTM and DriveToolsTM SP assist with programming, monitoring, and troubleshooting the PowerFlex 70.
DriveTools SP Software has been upgraded to Connected Components Workbench software. DriveTools support can be found at the Product Compatibility and Download Center rok.auto/pcdc, but is no longer available for sale.
Flexible Packaging and Mounting
� IP20, NEMA / UL Type 1 � For conventional mounting inside or outside a control cabinet. Conduit plate is vertically removable for easy installation and replacement without disturbing conduit.
� IP66, NEMA / UL Type 4X/12 (indoor use) � For mounting directly in the production environment. Listed by UL to resist dust, dirt, other contaminants, and to survive high-pressure water spray. Also certified by NSF International to verify conformity with international food equipment standards.
� Flange Type � For mounting heatsink through back of an enclosure, thus removing a large portion of the heat inside a cabinet. The backside is rated IP66, NEMA / UL Type 4X/12 for both indoor and outdoor use.
� Zero-StackingTM Drive - Drives can be mounted directly next to one another with no reduction of ambient temperature rating (50 �C [122 �F] for IP20, NEMA / UL Type 1, and Flange Mount; 40 �C [104 �F] for IP66, NEMA / UL Type 4X/12).
� Conformal Coating - The drive is coated in an insulator, or non-conducting substance, that helps protect it from moisture, fungus, dust, corrosion, abrasion, and other environmental stresses caused by highly polluted atmospheres. The coating improves product lifetime expectancy when exposure to corrosive environment is present. It helps maintain long-term surface insulation resistance, ensuring operational integrity of the assembly.
Space Saving Hardware Features
� Integral electromagnetic compatibility (EMC) filtering provides a compact, all-in-one package solution for meeting EMC requirements, including CE in Europe.
� Integral dynamic brake transistor delivers a cost-effective means of switching regenerative energy without costly external chopper circuits.
� Internal dynamic brake resistor requires no extra panel space, and supplies a large amount of braking torque for short periods. � Internal Communications allow you to integrate the drive into the manufacturing process. Status indicators for all internal
communication options are visible on the cover for easy setup and monitoring of drive communications. You can easily manage information from shop floor to top floor and seamlessly integrate their complete system as they control, configure, and collect data.

Rockwell Automation Publication 20A-TD001L-EN-P - December 2020

3

Easy to Use Human Interface Tools
The PowerFlex 7-Class AC drives provide common human interface tools that are familiar and easy to use. These tools include the LCD human interface modules and computer-based configuration tools.
The LCD HIMs provide these features and functions: � Large and easy to read 7-line x 21-character backlit display � Variety of languages (English, French, German, Italian, Spanish, Portuguese, Dutch) � Alternate function keys for shortcuts to common tasks � `Calculator-like' number pad for fast and easy data entry (full numeric version only) � Control keys for local start, stop, speed, and direction � Remote versions for panel mount application
Outstanding Control and Performance
� Volt/Hertz Control for simple Fan and Pump applications � Vector Control with FORCE Technology provides outstanding torque and speed regulation, with or without encoder feedback. � Sensorless Vector Control develops high torque over a wide speed range, and adapts to individual motor characteristics.

Drives Features
� Fast acting Current Limit and Bus Voltage Regulation result in maximum acceleration and deceleration without tripping.
� Flying Start delivers smooth connection into rotating loads, regardless of commanded direction, without the need for any speed feedback device.
� PI Control can eliminate the need for a separate process loop controller.
� Inertia Ride-Through offers tripless operation during a prolonged power outage by using the rotating energy that is stored in high-inertia, low-friction loads.
� User Sets, allowing up to three complete sets of parameter data, can be individually loaded for different batch processes.
� Slip compensation delivers minimum of 0.5% open-loop speed regulation across a wide speed range, eliminating the need for speed feedback devices in some applications.
� Safe Torque Off, the first offering available within the DriveGuard� series of safety solutions, helps prevent a drive from delivering rotational energy to motors by integrating a safety circuit with the power switching signals of the drive. This solution meets EN ISO 13849-1, Category 3.
� Droop Control for load sharing applications.
� Sleep/Wake Control for analog control of start and stop.

4

Rockwell Automation Publication 20A-TD001L-EN-P - December 2020

Unsurpassed Capability in Network Communications
PowerFlex drives are fully compatible with the wide variety of Allen-Bradley� DPITM (drive peripheral interface) communication adapters, offering the following benefits.
Availability By Communication Adapter
Benefits and Description

BACnet DeviceNet ControlNet EtherNet/IP Dual-Port EtherNet/IP RS-485 DF1 PROFIBUS DP LonWorks Modbus RTU Modbus TCP Metasys N2 Siemens P1 FLN

Unconnected Messaging: permits other network devices (for example, PanelViewTM) to communicate directly to a drive without routing the communication through the network scanner.

XXXX

Adapter Routing: plug personal computer into one drive and talk to other Allen-Bradley drives on same network, without being routed through network scanner.

X

X

X

X

X

X

X

Access all parameters: provides access to 100% of parameters over the network.

XXXXXXXXXXXX

Autobaud: makes initial connections less problematic.

XX XX X

Change of state: significantly reduces network traffic by configuring control messages to be sent only upon customer defined states. Flexible configuration for each node (for example, reference must change by more than 5%).

X

Peer Control: provides leader/follower type control between drives, where one or more follower drives (consumers) can run based on the status of a leader drive (producer). The leader drive can also significantly reduce network traffic.

X XX

Automatic Device Replacement (ADR): saves significant time and effort when replacing a drive, by allowing the scanner to be configured to automatically detect a new drive and download the required parameter settings.

X

Flexible Fault Configuration: adapters can be programmed to take fault-based actions such as ramp to stop, cost to stop, and

hold last state, and send user configurable logic control and speed reference values. In addition, different actions can be taken based on whether the network experienced a serious problem (broken cable) versus a network idle condition (PLC set to

X

X

X

X

X

X

X

X

X

X

X

X

`Program.')

Rockwell Automation Publication 20A-TD001L-EN-P - December 2020

5

Catalog Number Explanation

1...3

4

5...7 8

9

10

11

12

13

14

15

16

20A B 2P2 A 3 A Y Y N N C 0

a

b

c

a

Drive

Code

Type

20 A

PowerFlex 70

b

Voltage Rating

Code

Voltage

Ph.

B

240V AC

3 (6 pulse)

C

400V AC

3 (6 pulse)

D

480V AC

3 (6 pulse)

E

600V AC

3 (6 pulse)

c1

PowerFlex 70 ND Rating

208V, 60 Hz Input

Code 208V amps kW

Hp

2P2

2.5

0.37

0.5

4P2

4.8

0.75

1.0

6P8

7.8

1.5

2.0

9P6

11

2.2

3.0

015

17.5

4.0

5.0

022

25.3

5.5

7.5

028

32.2

7.5

10

042

43

11

15

054

56

15

20

070

78.2

18.5

25

c2

Frame A B C D
E

PowerFlex 70 ND Rating

240V, 60 Hz Input

Code Amps

kW

Hp Frame

2P2

2.2

0.37

0.5

A

4P2

4.2

0.75

1.0

6P8

6.8

1.5

2.0

B

9P6

9.6

2.2

3.0

015

15.3

4.0

5.0

C

022

22

5.5

7.5

028

28

7.5

10

D

042

42

11

15

054

54

15

20

070

70

18.5

25

E

c3

PowerFlex 70 ND Rating

400V, 50 Hz Input

Code Amps

kW

Hp Frame

1P3

1.3

0.37

0.5

2P1

2.1

0.75

1.0

A

3P5

3.5

1.5

2.0

5P0

5.0

2.2

3.0

B

8P7

8.7

4.0

5.0

011

11.5

5.5

7.5

C

015

15.4

7.5

10

022

22

11

15

030

30

15

20

D

037

37

18.5

25

043

42

22

30

060

60

30

40

072

72

37

50

E

de

f

gh

i

j

c4

PowerFlex 70 ND Rating

480V, 60 Hz Input

Code Amps

kW

Hp Frame

1P1

1.1

0.37

0.5

2P1

2.1

0.75

1.0

A

3P4

3.4

1.5

2.0

5P0

5.0

2.2

3.0

8P0

8.0

3.7

5.0

B

011

11

5.5

7.5

014

14

7.5

10

C

022

22

11

15

027

27

15

20

034

34

18.5

25

D

040

40

22

30

052

52

30

40

E

065

65

37

50

c5

PowerFlex 70 ND Rating

600V, 60 Hz Input(1)

Code Amps

kW

Hp Frame

0P9

0.9

0.37

0.5

1P7

1.7

0.75

1.0

A

2P7

2.7

1.5

2.0

3P9

3.9

2.2

3.0

6P1

6.1

4.0

5.0

B

9P0

9.0

5.5

7.5

011

11

7.5

10

C

017

17

11

15

022

22

15

20

027

27

18.5

25

D

032

32

22

30

041

41

30

40

E

052

52

37

50

(1) 600V class drives are declared to meet the Low Voltage Directive. It is the responsibility of the user to determine compliance to the EMC Directive.
d

Enclosure

Code

Enclosure(1)

A(2)

Panel Mount - IP 20, NEMA/UL Type 1

C(2)

Wall/Machine Mount = IP66, NEMA/UL Type 4X/ 12 for indoor use only

Flange Mount - Front Chassis = IP 20, NEMA/UL

F

Type 1; Rear Heatsink = IP66, NEMA/UL Type

4X/12 for indoor use only

G Wall/Machine Mount - IP54, NEMA/UL Type 12(3)

(1) All enclosures come with conformal coating standard. (2) IP20 and IP66 frame E drives are manufactured with a
flange-like heat heatsink with mounting holes. (3) Only available on Frame E.
e

HIM

Code

Interface Module

0

Blank Cover

3

Full Numeric LCD

5

Prog. Only LCD(1)

(1) Only available with NEMA 4X, enclosure C.

kl f

Documentation

Code

Type

A

Manual

N

No manual

g

Brake IGBT

Code

w/Brake

Y

Yes

h

Internal Brake Resistor

Code

w/ Resistor

Y

Yes

N

No

i

Emission Class(1)

Code

Rating

A

Filtered

N

Not Filtered

(1) For additional information, see the following table.

Emission Class by Frame Current Rating (A...E) and Voltage

A(1)(2)

B(2)

C

D

E

240V A or N A or N A

A

A

400V A or N A or N A

A

A

480V A or N A or N A

A

A

600V N

N

N

N

A

(1) If a filter is used with a Frame A current rating, the drive with internal filter is supplied in the B Frame to accommodate the additional size.
(2) "A or N" indicates that filtering is optional.

j

Comm Slot

Code

Network Type

C

ControlNet (Coax)

D

DeviceNet

E

EtherNet/IP

N

None

k

Control and I/O

Code

Control

Safe Torque Off(1)

N(2)

Standard

N/A

C

Enhanced

No

G

Enhanced

Yes

(1) Safe Torque Off is not available user-installed for 600V drives.
(2) No longer available for sale.
l

Feedback(1)

Code

Feedback

0

No Feedback - Enhanced Control

1

5V/12V Encoder w/Enhanced Control

(1) Drive is not CE EMC certified when the encoder interface option is installed.

6

Rockwell Automation Publication 20A-TD001L-EN-P - December 2020

Product Selection
This section provides product selection information for the following: � Panel Mount - IP20, NEMA/UL Type 1, No HIM � Wall/Machine Mount - IP66, NEMA/UL Type 4X/12 for Indoor Use with HIM on page 9 � Wall/Machine Mount - IP54, NEMA/UL Type 12, with HIM on page 10 � Flange Mount, Front Chassis = IP20, NEMA/UL Type 1, Heatsink = IP66, NEMA/UL Type 4X/12, No HIM on page 11

Panel Mount - IP20, NEMA/UL Type 1, No HIM

200...240V AC, Three-phase Drives

Output Amps Cont. 60 s 3 s

240V AC Input
Normal Heavy Duty Hp Duty Hp

Cat. No.

20AB2P2A0AYNNNC0

2.2

2.4

3.3

0.5

0.33

20AB2P2A0AYNANC0

20AB4P2A0AYNNNC0

4.2

4.8

6.4

1

0.75

20AB4P2A0AYNANC0

20AB6P8A0AYNNNC0

6.8

9

12

2

1.5

20AB6P8A0AYNANC0

9.6 10.6 14.4

3

20AB9P6A0AYNNNC0 2
20AB9P6A0AYNANC0

15.3 17.4 23.2

5

3

20AB015A0AYNANC0

22 24.2 33

7.5

5

20AB022A0AYNANC0

28

33

44

10

7.5

20AB028A0AYNANC0

42 46.2 63

15

10

20AB042A0AYNANC0

54

63

84

20

15

20AB054A0AYNANC0

70

81

108

25

20

20AB070A0AYNANC0

(1) Drive must be programmed to lower voltage to obtain the currents shown.

Output Amps Cont. 60 s 3 s

208V AC Input(1)
Normal Heavy Duty kW Duty kW

2.5

2.7

3.7

0.37

0.25

4.8

5.5

7.4

0.75

0.55

7.8 10.3 13.8

1.5

1.1

11

12.1 16.5

2.2

1.5

17.5 19.2 26.2

4

3

25.3 27.8 37.9

5.5

4

32.2 37.9 50.6

7.5

5.5

43 55.5 74

11

7.5

62.1 72.4 96.6

15

11

78.2 93.1 124

18.5

15

Cat. No.
20AB2P2A0AYNNNC0 20AB2P2A0AYNANC0 20AB4P2A0AYNNNC0 20AB4P2A0AYNANC0 20AB6P8A0AYNNNC0 20AB6P8A0AYNANC0 20AB9P6A0AYNNNC0 20AB9P6A0AYNANC0 20AB015A0AYNANC0 20AB022A0AYNANC0 20AB028A0AYNANC0 20AB042A0AYNANC0 20AB054A0AYNANC0 20AB070A0AYNANC0

With Frame Filter Size

No

A

Yes

B

No

A

Yes

No

Yes

B

No

C

Yes

D

E

Rockwell Automation Publication 20A-TD001L-EN-P - December 2020

7

380...480V AC, Three-phase Drives

Output Amps

Cont.

60 s

1.1

1.2

2.1

2.4

3.4

4.5

5

5.5

8

8.8

11

12.1

14

16.5

22

24.2

27

33

34

40.5

40

51

52

60

65

78

480V AC Input
Normal Heavy 3 s Duty Hp Duty Hp

1.6

0.5

0.33

3.2

1

0.75

6

2

1.5

7.5

3

2

12

5

3

16.5

7.5

5

22

10

7.5

33

15

10

44

20

15

54

25

20

68

30

25

80

40

30

104

50

40

Cat. No.
20AD1P1A0AYNNNC0 20AD1P1A0AYNANC0 20AD2P1A0AYNNNC0 20AD2P1A0AYNANC0 20AD3P4A0AYNNNC0 20AD3P4A0AYNANC0 20AD5P0A0AYNNNC0 20AD5P0A0AYNANC0 20AD8P0A0AYNNNC0 20AD8P0A0AYNANC0 20AD011A0AYNANC0 20AD014A0AYNANC0 20AD022A0AYNANC0 20AD027A0AYNANC0 20AD034A0AYNANC0 20AD040A0AYNANC0 20AD052A0AYNANC0 20AD065A0AYNANC0

Output Amps Cont. 60 s 3 s

1.3

1.4

1.9

2.1 2.4 3.2

3.5 4.5

6

5

5.5 7.5

8.7 9.9 13.2

11.5 13 17.4

15 17.2 23.1

22 24.2 33

30

33

45

37

45

60

43

56

74

60

66

90

72

90

120

400V AC Input
Normal Heavy Duty kW Duty kW

Cat. No.

With Frame Filter Size

20AC1P3A0AYNNNC0 No

A

0.37

0.25

20AC1P3A0AYNANC0 Yes

B

20AC2P1A0AYNNNC0 No

A

0.75

0.55

20AC2P1A0AYNANC0 Yes

B

20AC3P5A0AYNNNC0 No

A

1.5

1.1

20AC3P5A0AYNANC0 Yes

B

20AC5P0A0AYNNNC0 No

2.2

1.5

B

20AC5P0A0AYNANC0 Yes

20AC8P7A0AYNNNC0 No

4

3

B

20AC8P7A0AYNANC0

5.5

4

20AC011A0AYNANC0

C

7.5

5.5 20AC015A0AYNANC0

C

11

7.5 20AC022A0AYNANC0

D

15

11

20AC030A0AYNANC0 Yes

D

18.5

15

20AC037A0AYNANC0

D

22

18.5 20AC043A0AYNANC0

D

30

22 20AC060A0AYNANC0

E

37

30

20AC072A0AYNANC0

E

500...600V AC, Three-phase Drives

Output Amps

Cont.

60 s

3 s

0.9

1

1.4

1.7

1.9

2.6

2.7

3.6

4.8

3.9

4.3

5.8

6.1

6.7

9.1

9

9.9

13.5

11

13.5

18

17

18.7

25.5

22

25.5

34

27

33

44

32

40.5

54

41

48

64

52

61.5

82

600V AC Input

Normal Duty Hp Heavy Duty Hp

0.5

0.33

1

0.75

2

1

3

1.5

5

3

7.5

5

10

7.5

15

10

20

15

25

20

30

25

40

30

50

40

Cat. No.

With Filter

20AE0P9A0AYNNNC0 20AE1P7A0AYNNNC0 20AE2P7A0AYNNNC0 20AE3P9A0AYNNNC0 20AE6P1A0AYNNNC0 20AE9P0A0AYNNNC0 20AE011A0AYNNNC0 No 20AE017A0AYNNNC0 20AE022A0AYNNNC0 20AE027A0AYNNNC0 20AE032A0AYNNNC0 20AE041A0AYNANC0 20AE052A0AYNANC0

Frame Size A B C D E

8

Rockwell Automation Publication 20A-TD001L-EN-P - December 2020

Wall/Machine Mount - IP66, NEMA/UL Type 4X/12 for Indoor Use with HIM

200...240V AC, Three-phase Drives

Output Amps Cont. 60 s 3 s

240V AC Input
Normal Heavy Duty Hp Duty Hp

Cat. No.

Output Amps Cont. 60 s 3 s

208V AC Input(1)
Normal Heavy Duty kW Duty kW

Cat. No.

With Filter

Frame Size

2.2 2.4 3.3

0.5

20AB2P2C3AYNNNC0

0.33

2.5 2.7 3.7

0.37

20AB2P2C3AYNANC0

20AB2P2C3AYNNNC0 No 0.25
20AB2P2C3AYNANC0 Yes

4.2 4.8 6.4

1

6.8

9

12

2

20AB4P2C3AYNNNC0

20AB4P2C3AYNNNC0 No

0.75

4.8 5.5 7.4

0.75

0.55

20AB4P2C3AYNANC0

20AB4P2C3AYNANC0 Yes

B

20AB6P8C3AYNNNC0

20AB6P8C3AYNNNC0 No

1.5

7.8 10.3 13.8

1.5

1.1

20AB6P8C3AYNANC0

20AB6P8C3AYNANC0 Yes

9.6 10.6 14.4

3

20AB9P6C3AYNNNC0

2

11

12.1 16.5

2.2

20AB9P6C3AYNANC0

20AB9P6C3AYNNNC0 No 1.5
20AB9P6C3AYNANC0

15.3 17.4 23.2

5

3

20AB015C3AYNANC0 17.5 19.2 26.2

4

3

20AB015C3AYNANC0

22 24.2 33

7.5

28

33

44

10

5 20AB022C3AYNANC0 25.3 27.8 37.9

5.5

7.5 20AB028C3AYNANC0 32.2 37.9 50.6

7.5

4 20AB022C3AYNANC0 D
5.5 20AB028C3AYNANC0 Yes

42 46.2 63

15

10 20AB042C3AYNANC0 43 55.5 74

11

7.5 20AB042C3AYNANC0

54

63

84

20

15 20AB054C3AYNANC0 62.1 72.4 96.6

15

11 20AB054C3AYNANC0

E

70

81

108

25

20 20AB070C3AYNANC0 78.2 93.1 124

18.5

15 20AB070C3AYNANC0

(1) The drive must be programmed to lower voltage to obtain the currents shown.

380...480V AC, Three-phase Drives

Output Amps Cont. 60 s 3 s

1.1

1.2

1.6

2.1 2.4 3.2

3.4 4.5

6

5

5.5 7.5

8

8.8

12

11

12.1 16.5

14 16.5 22

22 24.2 33

27

33

44

34 40.5 54

40

51

68

52 60 80

65

78 104

480V AC Input
Normal Heavy Duty Hp Duty Hp

0.5

0.33

1

0.75

2

1.5

3

2

5

3

7.5

5

10

7.5

15

10

20

15

25

20

30

25

40

30

50

40

Cat. No.
20AD1P1C3AYNNNC0 20AD1P1C3AYNANC0 20AD2P1C3AYNNNC0 20AD2P1C3AYNANC0 20AD3P4C3AYNNNC0 20AD3P4C3AYNANC0 20AD5P0C3AYNNNC0 20AD5P0C3AYNANC0 20AD8P0C3AYNNNC0 20AD8P0C3AYNANC0 20AD011C3AYNANC0 20AD014C3AYNANC0 20AD022C3AYNANC0 20AD027C3AYNANC0 20AD034C3AYNANC0 20AD040C3AYNANC0 20AD052C3AYNANC0 20AD065C3AYNANC0

Output Amps Cont. 60 s 3 s
1.3 1.4 1.9

2.1 2.4 3.2

3.5 4.5

6

5

5.5 7.5

8.7 9.9 13.2

11.5 13 17.4

15 17.2 23.1

22 24.2 33

30 33 45

37 45 60

43 56 74

60 66 90

72

90 120

400V AC Input
Normal Heavy Duty kW Duty kW

Cat. No.

With Frame Filter Size

20AC1P3C3AYNNNC0 No

0.37

0.25

20AC1P3C3AYNANC0 Yes

20AC2P1C3AYNNNC0 No

0.75

0.55

20AC2P1C3AYNANC0 Yes

20AC3P5C3AYNNNC0 No

1.5

1.1

B

20AC3P5C3AYNANC0 Yes

20AC5P0C3AYNNNC0 No

2.2

1.5

20AC5P0C3AYNANC0 Yes

20AC8P7C3AYNNNC0 No

4

3

20AC8P7C3AYNANC0

5.5

4

20AC011C3AYNANC0

7.5

5.5 20AC015C3AYNANC0

11

7.5 20AC022C3AYNANC0

D

15

11 20AC030C3AYNANC0 Yes

18.5

15 20AC037C3AYNANC0

22

18.5 20AC043C3AYNANC0

30

22 20AC060C3AYNANC0

E

37

30 20AC072C3AYNANC0

Rockwell Automation Publication 20A-TD001L-EN-P - December 2020

9

500...600V AC, Three-phase Drives

Output Amps

Cont. 60 s 3 s

0.9

1

1.4

1.7 1.9 2.6

2.7 3.6 4.8

3.9 4.3 5.8

6.1 6.7 9.1

9

9.9 13.5

11 13.5 18

17 18.7 25.5

22 25.5 34

27

33

44

32 40.5 54

41

48

64

52 61.5 82

600V AC Input

Normal Heavy Duty Hp Duty Hp

0.5

0.33

1

0.75

2

1

3

1.5

5

3

7.5

5

10

7.5

15

10

20

15

25

20

30

25

40

30

50

40

Cat. No.
20AE0P9C3AYNNNC0 20AE1P7C3AYNNNC0 20AE2P7C3AYNNNC0 20AE3P9C3AYNNNC0 20AE6P1C3AYNNNC0 20AE9P0C3AYNNNC0 20AE011C3AYNNNC0 20AE017C3AYNNNC0 20AE022C3AYNNNC0 20AE027C3AYNNNC0 20AE032C3AYNNNC0 20AE041C3AYNANC0 20AE052C3AYNANC0

With Frame Filter Size
B
No D
E

Wall/Machine Mount - IP54, NEMA/UL Type 12, with HIM

200...240V AC, Three-phase Drives

240V AC Input

208V AC Input(1)

Output Amps Cont. 60 s 3 s

Normal Duty Hp

Heavy Duty Hp

Output Amps Cont. 60 s 3 s

Normal Duty kW

54

63

84

20

15

62.1 72.4 96.6

15

70

81

108

25

20

78.2 93.1 124

18.5

(1) Drive must be programmed to lower voltage to obtain the currents shown.

Heavy Duty kW
11 15

Cat. No.
20AB054G3AYNANC0 20AB070G3AYNANC0

With Filter

Frame Size

Yes

E

380...480V AC, Three-phase Drives

Output Amps

Cont. 60 s 3 s

52 60 80

65

78 104

480V AC Input

Normal Heavy Duty Hp Duty Hp

40

30

50

40

Cat. No.
20AD052G3AYNANC0 20AD065G3AYNANC0

Output Amps

Cont. 60 s 3 s

60 66 90

72

90 120

400V AC Input

Normal Heavy Duty kW Duty kW

30

22

37

30

Cat. No.
20AC060G3AYNANC0 20AC072G3AYNANC0

With Frame Filter Size

Yes

E

500...600V AC, Three-phase Drives

Output Amps

Cont. 60 s 3 s

41

48

64

52 61.5 82

600V AC Input

Normal Heavy Duty Hp Duty Hp

40

30

50

40

Cat. No.
20AE041G3AYNANC0 20AE052G3AYNANC0

With Filter

Frame Size

Yes

E

10

Rockwell Automation Publication 20A-TD001L-EN-P - December 2020

Flange Mount, Front Chassis = IP20, NEMA/UL Type 1, Heatsink = IP66, NEMA/UL Type 4X/12, No HIM

200...240V AC, Three-phase Drives

Output Amps Cont. 60 s 3 s

240V AC Input
Normal Heavy Duty Hp Duty Hp

Cat. No.

Output Amps Cont. 60 s 3 s

208V AC Input(1)
Normal Heavy Duty kW Duty kW

Cat. No.

With Frame Filter Size

2.2 2.4 3.3

0.5

20AB2P2F0AYNNNC0

0.33

2.5 2.7 3.7

0.37

20AB2P2F0AYNANC0

20AB2P2F0AYNNNC0 No

A

0.25

20AB2P2F0AYNANC0 Yes

B

4.2 4.8 6.4

1

20AB4P2F0AYNNNC0

0.75

4.8 5.5 7.4

0.75

20AB4P2F0AYNANC0

20AB4P2F0AYNNNC0 No

A

0.55

20AB4P2F0AYNANC0 Yes

6.8

9

12

2

20AB6P8F0AYNNNC0

1.5

7.8 10.3 13.8

1.5

20AB6P8F0AYNANC0

20AB6P8F0AYNNNC0 No

1.1

20AB6P8F0AYNANC0 Yes

B

9.6 10.6 14.4

3

20AB9P6F0AYNNNC0

2

11 12.1 16.5

2.2

20AB9P6F0AYNANC0

20AB9P6F0AYNNNC0 No 1.5
20AB9P6F0AYNANC0

15.3 17.4 23.2

5

3

20AB015F0AYNANC0 17.5 19.2 26.2

4

3

20AB015F0AYNANC0

C

22 24.2 33

7.5

5

20AB022F0AYNANC0 25.3 27.8 37.9

5.5

4

20AB022F0AYNANC0

28

33

44

10

7.5

20AB028F0AYNANC0 32.2 37.9 50.6

7.5

5.5 20AB028F0AYNANC0 Yes D

42 46.2 63

15

10

20AB042F0AYNANC0 43 55.5 74

11

7.5

20AB042F0AYNANC0

54

63

84

20

15

20AB054F0AYNANC0 62.1 72.4 96.6

15

11

20AB054F0AYNANC0

E

70

81

108

25

20

20AB070F0AYNANC0 78.2 93.1 124

18.5

15

20AB070F0AYNANC0

(1) Drive must be programmed to lower voltage to obtain the currents shown.

380...480V AC, Three-phase Drives

Output Amps Cont. 60 s 3 s

480V AC Input
Normal Heavy Duty Hp Duty Hp

1.1

1.2

1.6

0.5

0.33

2.1 2.4 3.2

1

0.75

3.4 4.5

6

2

1.5

5

5.5 7.5

3

2

8

8.8

12

5

3

11

12.1 16.5

7.5

5

14 16.5 22

10

7.5

22 24.2 33

15

10

27

33

44

20

15

34 40.5 54

25

20

40

51

68

30

25

52 60 80

40

30

65

78 104

50

40

Cat. No.
20AD1P1F0AYNNNC0 20AD1P1F0AYNANC0 20AD2P1F0AYNNNC0 20AD2P1F0AYNANC0 20AD3P4F0AYNNNC0 20AD3P4F0AYNANC0 20AD5P0F0AYNNNC0 20AD5P0F0AYNANC0 20AD8P0F0AYNNNC0 20AD8P0F0AYNANC0 20AD011F0AYNANC0 20AD014F0AYNANC0 20AD022F0AYNANC0 20AD027F0AYNANC0 20AD034F0AYNANC0 20AD040F0AYNANC0 20AD052F0AYNANC0 20AD065F0AYNANC0

Output Amps Cont. 60 s 3 s
1.3 1.4 1.9

2.1 2.4 3.2

3.5 4.5

6

5

5.5 7.5

8.7 9.9 13.2

11.5 13 17.4

15 17.2 23.1

22 24.2 33

30

33

45

37 45 60

43 56 74

60 66 90

72

90 120

400V AC Input
Normal Heavy Duty kW Duty kW

Cat. No.

With Frame Filter Size

20AC1P3F0AYNNNC0 No

A

0.37

0.25

20AC1P3F0AYNANC0 Yes B

20AC2P1F0AYNNNC0 No

A

0.75

0.55

20AC2P1F0AYNANC0 Yes B

20AC3P5F0AYNNNC0 No

A

1.5

1.1

20AC3P5F0AYNANC0 Yes

20AC5P0F0AYNNNC0 No

2.2

1.5

20AC5P0F0AYNANC0 Yes

B

20AC8P7F0AYNNNC0 No

4

3

20AC8P7F0AYNANC0

5.5

4

20AC011F0AYNANC0

C

7.5

5.5

20AC015F0AYNANC0

11

7.5

20AC022F0AYNANC0

15

11

20AC030F0AYNANC0 Yes

D

18.5

15

20AC037F0AYNANC0

22

18.5 20AC043F0AYNANC0

30

22

20AC060F0AYNANC0

E

37

30

20AC072F0AYNANC0

Rockwell Automation Publication 20A-TD001L-EN-P - December 2020

11

500...600V AC, Three-phase Drives

Output Amps

Cont.

60 s

3 s

0.9

1

1.4

1.7

1.9

2.6

2.7

3.6

4.8

3.9

4.3

5.8

6.1

6.7

9.1

9

9.9

13.5

11

13.5

18

17

18.7

25.5

22

25.5

34

27

33

44

32

40.5

54

41

48

64

52

61.5

82

600V AC Input
Normal Duty Hp
0.5 1 2 3 5 7.5 10 15 20 25 30 40 50

Heavy Duty Hp
0.33 0.75
1 1.5 3 5 7.5 10 15 20 25 30 40

Cat. No.
20AE0P9F0AYNNNC0 20AE1P7F0AYNNNC0 20AE2P7F0AYNNNC0 20AE3P9F0AYNNNC0 20AE6P1F0AYNNNC0 20AE9P0F0AYNNNC0 20AE011F0AYNNNC0 20AE017F0AYNNNC0 20AE022F0AYNNNC0 20AE027F0AYNNNC0 20AE032F0AYNNNC0 20AE041F0AYNANC0 20AE052F0AYNANC0

With Filter Frame Size A B C
No D E

Factory-installed Options
This section provides information about optional components that are installed at the factory.

12

Rockwell Automation Publication 20A-TD001L-EN-P - December 2020

Human Interface and Wireless Interface Modules (Position)

IP20, NEMA/UL Type 1 and Flange Type Drives

IP66, NEMA/UL Type 4X/12 Drives

Cat. Code: 0 No HIM (Blank Plate)

Cat. Code: 3 LCD Display, Full Numeric Keypad

Internal Dynamic Brake Resistors

Drive Input Voltage
200...240V AC
380...480V AC
600V AC

Internal Dynamic Brake Resistors

Brake Resistance W

Frame

A

62

B

C

D 22
E

A

115

B

C

D 62
E

A

115

B

C

--

D and E

Cat. Code (Position h)
Y Y Y Y Not Available Y Y Y Y Not Available Y Y Y Not Available

These resistors have a limited duty cycle. See the PowerFlex Dynamic Braking Selection Guide to determine if an internal resistor is sufficient. An external resistor may be required.

Internal EMC Filter

Drive Voltage 200...240V AC
380...480V AC
600V AC (2)

Internal EMC Filter

CE Filter

Frame(1)

Optional

B

Standard

C

Standard

D

Optional

B

Standard

C

Standard

D

Standard

E

Standard

E

Cat. Code (Position i)
A
A
--

(1) Internal CE filters are not available inside of the compact A Frame size. If an A Frame current rating is ordered with an internal filter option, the drive with internal CE filter is supplied in the B Frame to accommodate the additional size.
(2) 600V AC Frames A...D available only without filter.

Cat. Code: 5 LCD Display, Programmer Only

Cat. Code: 0 No HIM (Blank)

Cat. Code: 3 LCD Display, Full Numeric Keypad

Internal Communication Adapters

Internal Communication Adapters
ControlNet Communication Adapter (Coax) DeviceNet Communication Adapter EtherNet/IP Communication Adapter None

Cat. Code (Position j)
C D E N

Control Options

Control Options
Enhanced Control without DriveGuard Safe Torque Off Enhanced Control with DriveGuard Safe Torque Off
Feedback Options

Cat. Code (Position k)
C
G

Feedback Options
None 5V/12V Encoder(1)

Cat. Code (Position k)
0
1

(1) Drive is not CE EMC certified when the encoder interface option is installed.
Documentation

Documentation
Manual No manual

Cat. Code (Position f)
A
N

Rockwell Automation Publication 20A-TD001L-EN-P - December 2020

13

User Installed Options
This section provides information about optional components that you can install.
Human Interface and Wireless Interface Modules

No HIM (Blank Plate) 20-HIM-A0

LCD Display, Full Numeric Keypad
20-HIM-A3

LCD Display, Programmer Only
20-HIM-A5

Enhanced LCD Display, Full Numeric Keypad
20-HIM-A6

Remote (Panel Mount) LCD Display, Full Numeric Keypad 20-HIM-C3S

Remote (Panel Mount) LCD Display,
Programmer Only 20-HIM-C5S

Handheld/Local (Drive Mount)

Description

Cat. No.

No HIM (Blank Plate)

20-HIM-A0

LCD Display, Full Numeric Keypad

20-HIM-A3

LCD Display, Programmer Only

20-HIM-A5

Enhanced LCD Display, Full Numeric Keypad 20-HIM-A6

Remote (Panel Mount) IP66, NEMA/UL Type
4x/12
Cat. No. �
20-HIM-C3S 
20-HIM-C5S 
20-HIM-C6S

For indoor use only.  Includes a 1202-C30 interface cable, 3 m (9.8 ft), for connection to drive.

Enhanced LCD Display, Full Numeric Keypad
20-HIM-C6S

Human Interface Module Accessories

Description Bezel Kit for LCD HIMs, NEMA/UL Type 1  PowerFlex HIM Interface Cable, 1 m (39 in) Cable Kit (Male-Female)
0.33 Meters (1.1 Feet) 1 Meter (3.3 Feet) 3 Meter (9.8 Feet) 9 Meter (29.5 Feet) Comm Option Cable Kit 0.33 Meters (1.1 Feet) 1 Meter (3.3 Feet) 3 Meter (9.8 Feet) 9 Meter (29.5 Feet) DPI Cable Kit with Connectors, Tools and 100 m (328 ft.) Cable
DPI Cable Connector Kit
DPI/SCANportTM One to Two Port Splitter Cable

Cat. No. 20-HIM-B1 20-HIM-H10
1202-H03 1202-H10 1202-H30 1202-H90
1202-C03 1202-C10 1202-C30 1202-C90 1202-CBLKIT-100M 1202-TB-KIT-
SET 1203-S03

 Includes a 1202-C30 interface cable (3 meters) for connection to drive. Required only when HIM is used as handheld or remote. Required in addition to 20-HIM-H10 for distances up to a total maximum of 10 Meters (32.8 Feet).

14

Rockwell Automation Publication 20A-TD001L-EN-P - December 2020

Dynamic Brake Resistors

This section includes Small Duty Internal Dynamic Brake Resistors, Internal Dynamic Brake Resistor Kits, Medium Duty External Dynamic Brake Resistors on page 16, and External Dynamic Brake Resistor Kits on page 16.

Small Duty Internal Dynamic Brake Resistors

Limited duty resistors mount directly to the back surface of the drive and require no extra panel space. Internal resistors are nondestructive and do not require a resistor overheat external safety circuit.

.
PowerFlex 70 AC Drive

Normal Duty kW (Hp)

Heavy Duty kW (Hp)

Min DB Res Ohms �10%

0.37 (0.5) 0.25 (0.33)

33

0.75 (1.0) 0.55 (0.75)

33

1.5 (2.0) 1.1 (1.5)

33

2.2 (3.0) 1.5 (2.0)

33

4.0 (5.0) 3.0 (3.0)

30

5.5 (7.5) 4.0 (5.0)

21

7.5 (10) 5.5 (7.5)

21

0.37 (0.5) 0.25 (0.33)

68

0.75 (1.0) 0.55 (0.75)

68

1.5 (2.0) 1.1 (1.5)

68

2.2 (3.0) 1.5 (2.0)

68

4.0 (5.0) 3.0 (3.0)

68

5.5 (7.5) 4.0 (5.0)

74

7.5 (10) 5.5 (7.5)

74

11 (15)

7.5 (10)

44

15 (20)

11 (15)

31

0.37 (0.5) 0.25 (0.33)

117

0.75 (1.0) 0.55 (0.75)

117

1.5 (2.0) 1.1 (1.5)

117

2.2 (3.0) 1.5 (2.0)

117

4.0 (5.0) 3.0 (3.0)

80

5.5 (7.5) 4.0 (5.0)

80

7.5 (10) 5.5 (7.5)

80

11 (15)

7.5 (10)

48

15 (20)

11 (15)

48

Small Duty Internal DB Resistor

Part Number

Resistance Continuous

Power

Ohms �5%

kW

Max Energy
kJ

Max Braking Torque % of ND Motor

Application Type 1

Braking Torque % of ND Motor

Duty Cycle

200...240 Volt AC Input Drives

20AB-DB1-A 62

0.048

8.3

307%

100%

25.9%

20AB-DB1-A 62

0.048

7.3

300%

100%

12.8%

20AB-DB1-B 62

0.028

0.8

160%

100%

3.7%

20AB-DB1-B 62

0.028

0.8

109%

100%

2.5%

20AB-DB1-C 62

0.040

0.8

60%

60%

3.3%

20AB-DB1-D 22

0.036

0.9

117%

100%

1.3%

20AB-DB1-D 22

0.036

0.9

86%

86%

1.1%

400...480 Volt AC Input Drives

20AD-DB1-A 115

0.048

8.3

320%

100%

25.9%

20AD-DB1-A 115

0.048

9.0

259%

100%

12.8%

20AD-DB1-A 115

0.048

2.4

243%

100%

6.4%

20AD-DB1-B 115

0.028

0.9

206%

100%

2.5%

20AD-DB1-B 115

0.028

0.9

129%

100%

1.4%

20AD-DB1-C 115

0.04

0.9

94%

94%

1.5%

20AD-DB1-C 115

0.04

0.9

69%

69%

1.5%

20AD-DB1-D 62

0.036

0.8

87%

87%

0.8%

20AD-DB1-D 62

0.036

0.8

64%

64%

0.8%

500...600 Volt AC Input Drives

20AD-DB1-A 115

0.048

8.3

287%

100%

25.9%

20AD-DB1-A 115

0.048

9.0

263%

100%

12.8%

20AD-DB1-A 115

0.048

2.4

243%

100%

6.4%

20AD-DB1-B 115

0.028

0.9

202%

100%

2.5%

20AD-DB1-B 115

0.028

0.9

193%

100%

1.4%

20AD-DB1-C 115

0.04

0.9

147%

100%

1.5%

20AD-DB1-C 115

0.04

0.9

108%

100%

1.1%

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

Application Type 2

Braking Torque % of ND Motor

Duty Cycle

150% 150% 150% 109% N/A 117% N/A

17.3% 8.5% 2.5% 2.3% N/A 1.1% N/A

150% 150% 150% 150% 129% N/A N/A N/A N/A

17.3% 8.5% 4.3% 1.7% 1.1% N/A N/A N/A N/A

150% 150% 150% 150% 150% 147% 108% N/A N/A

17.3% 8.5% 4.3% 1.7% 0.9% 1.0% 1.0% N/A N/A

Duty cycle listed is based on full speed to zero speed deceleration. For constant regen at full speed, duty cycle capability is half of what is listed. Application Type 1 represents maximum capability up to 100% braking torque where possible. Application Type 2 represents more than 100% braking torque where possible, up to a maximum of 150%.
Always check resistor ohms against minimum resistance for drive being used.

Internal Dynamic Brake Resistor Kits

Drive Input Voltage
200...240V AC
380...480V AC
600V AC

Brake Resistance 
62 22
115 62
115

Frame A B C D E A B C D E A B C D and E

Cat. No. 20AB-DB1-A 20AB-DB1-B 20AB-DB1-C 20AB-DB1-D Not Available 20AD-DB1-A 20AD-DB1-B 20AD-DB1-C 20AD-DB1-D Not Available 20AD-DB1-A 20AD-DB1-B 20AD-DB1-C Not Available

These resistors have a limited duty cycle. See the PowerFlex Dynamic Braking Resistor Calculator Application Technique, publication PFLEX-AT001, to determine if an internal resistor is sufficient. An external resistor may be required.

Rockwell Automation Publication 20A-TD001L-EN-P - December 2020

15

Medium Duty External Dynamic Brake Resistors

These resistors provide a larger duty cycle capability than the internal type. Includes an internal thermal switch for use in external safety circuit.

PowerFlex 70 AC Drive

Normal Duty kW (Hp)

Heavy Duty kW (Hp)

Min DB Res Ohms �10%

0.37 (0.5) 0.75 (1.0) 1.5 (2.0) 2.2 (3.0) 4.0 (5.0) 5.5 (7.5) 7.5 (10)

0.25 (0.33) 33 0.55 (0.75) 33 1.1 (1.5) 33 1.5 (2.0) 33 3.0 (3.0) 30 4.0 (5.0) 23 5.5 (7.5) 23

0.37 (0.5) 0.75 (1.0) 1.5 (2.0) 2.2 (3.0) 4.0 (5.0) 5.5 (7.5) 7.5 (10) 11 (15)  15 (20) 

0.25 (0.33) 68 0.55 (0.75) 68 1.1 (1.5) 68 1.5 (2.0) 68 3.0 (3.0) 68 4.0 (5.0) 74 5.5 (7.5) 74 7.5 (10)  44 11 (15)  31

0.37 (0.5) 0.75 (1.0) 1.5 (2.0) 2.2 (3.0) 4.0 (5.0) 5.5 (7.5) 7.5 (10) 11 (15)  15 (20) 

0.25 (0.33) 117 0.55 (0.75) 117 1.1 (1.5) 117 1.5 (2.0) 117 3.0 (3.0) 80 4.0 (5.0) 80 5.5 (7.5) 80 7.5 (10)  48 11 (15)  48

Medium Duty External DB Resistor

Part Number

Resistance

Continuous

Ohms

Power

�5%

kW

Max Energy
kJ

Max Braking Torque
% of ND Motor

Application Type 1

Application Type 2

Braking Torque Duty Braking Torque Duty % of ND Motor Cycle % of ND Motor Cycle

200...240 Volt ac Input Drives

AK-R2-091P500 91

0.086

17

293%

100%

46% 150%

31%

AK-R2-091P500 91

0.086

17

218%

100%

23% 150%

15%

AK-R2-091P500 91

0.086

17

109%

100%

11% 109%

11%

AK-R2-047P500 47

0.166

33

144%

100%

15% 144%

11%

AK-R2-047P500 47

0.166

33

79%

79%

11% N/A

N/A

AK-R2-030P1K2 30

0.26

52

90%

90%

10% N/A

N/A

AK-R2-030P1K2 30

0.26

52

66%

66%

10% N/A

N/A

400...480 Volt ac Input Drives

AK-R2-360P500 360

0.086

17

305%

100%

47% 150%

31%

AK-R2-360P500 360

0.086

17

220%

100%

23% 150%

15%

AK-R2-360P500 360

0.086

17

110%

100%

12% 110%

11%

AK-R2-120P1K2 120

0.26

52

197%

100%

24% 150%

16%

AK-R2-120P1K2 120

0.26

52

124%

100%

13% 124%

10%

AK-R2-120P1K2 120

0.26

52

90%

90%

10% N/A

N/A

AK-R2-120P1K2 120

0.26

52

66%

66%

10% N/A

N/A



60

0.52

104 90%

90%

10% N/A

N/A



60

0.52

104 66%

66%

10% N/A

N/A

500...600 Volt ac Input Drives

AK-R2-360P500 360

0.086

17

274%

100%

46% 150%

31%

AK-R2-360P500 360

0.086

17

251%

100%

23% 150%

15%

AK-R2-360P500 360

0.086

17

172%

100%

11% 150%

8%

AK-R2-120P1K2 120

0.26

52

193%

100%

24% 150%

16%

AK-R2-120P1K2 120

0.26

52

185%

100%

13% 150%

9%

AK-R2-120P1K2 120

0.26

52

141%

100%

9% 141%

7%

AK-R2-120P1K2 120

0.26

52

103%

100%

7% 103%

7%



60

0.52

104 141%

100%

9% 141%

7%



60

0.52

104 103%

100%

7% 103%

7%

Duty cycle listed is based on full speed to zero speed deceleration. For constant regen at full speed, duty cycle capability is half of what is listed. Application Type 1 represents maximum capability up to 100% braking torque where possible. Application Type 2 represents more than 100% braking torque where possible, up to a maximum of 150%.
Always check resistor ohms against minimum resistance for drive being used.  For 11 and 15 kW (15 and 20 Hp) applications, use two 7.5 kW (10 Hp) size resistors wired in parallel.

External Dynamic Brake Resistor Kits

Drive Input Voltage
200...240V AC
480...600V AC

Brake Resistance 
30 47 91 120 360

Continuous Power W
260 166 86 260 86

Cat. No. AK-R2-030P1K2 AK-R2-047P500 AK-R2-091P500 AK-R2-120P1K2 AK-R2-360P500

16

Rockwell Automation Publication 20A-TD001L-EN-P - December 2020

Communication Options

The sections that follow describe the communication options that are available.

Communication Option Kits
Description BACnet� MS/TP RS-485 Communication Adapter ControlNet Communication Adapter (Coax) DeviceNet Communication Adapter EtherNet/IP Communication Adapter Dual-port EtherNet/IP Communication Adapter HVAC Communication Adapter CANopen� Communication Adapter LonWorks� Communication Adapter Modbus/TCP Communication Adapter PROFIBUSTM DP Communication Adapter ControlNet Communication Adapter RS-485 DF1 Communication Adapter External Communications Kit Power Supply DPI External Communications Kit External DPI I/O Option Board(1) Compact I/OTM Module (3 Channel) Serial Null Modem Adapter Smart Self-powered Serial Converter (RS-232) includes 1203-SFC and 1202-C10 cables Universal Serial Bus (USB) Converter includes 2 m (6.5 ft) USB, 20-HIM-H10, and 22-HIM-H10 cables
(1) For use only with DPI External Communications Kits 20-XCOMM-DC-BASE.

Cat. No. 20-COMM-B 20-COMM-C 20-COMM-D 20-COMM-E 20-COMM-ER 20-COMM-H 20-COMM-K 20-COMM-L 20-COMM-M 20-COMM-P 20-COMM-Q 20-COMM-S 20-XCOMM-AC-PS1 20-XCOMM-DC-BASE 20-XCOMM-IO-OPT1 1769-SM1 1203-SNM
1203-SSS
1203-USB

Other Options

Description DriveGuard Safe Torque Off Board 5V/12V Encoder(1) 115V AC Interface Frame E Flange Gasket Service Connection Board(2)

Cat. No. 20A-DG01 20A-ENC-1 AK-M9-115VAC-1 AK-M9-GASKET1-E4 SK-M9-SCB1

(1) Drive is not CE EMC certified when the encoder interface option is installed. (2) Provides temporary DPI/HIM connection for NEMA/UL Type 1 and Flange drives with cover removed.

Terminators

Description(1) for use with 3.7 kW (5 HP) and below drives for use with 1.5 kW (2 Hp) and up drives

Cat. No. 1204-TFA1 1204-TFB2

(1) For selection information, see Wiring and Grounding Guidelines for Pulse-width Modulated (PWM) AC Drives, publication DRIVES-IN001, Appendix A.

Reflected Wave Reduction Modules

Description(1) 17 A with Common Mode Choke 9 A without Choke, Book Mount(2) 9 A, without Choke, Stack Mount(2)

Cat. No. 1204-RWC-17-A 1204-RWR2-09-B 1204-RWR2-09-C

(1) For selection information, see Wiring and Grounding Guidelines for Pulse-width Modulated (PWM) AC Drives, publication DRIVES-IN001, Appendix A.
(2) 1321-RWR products replace existing 1204-RWR products, 1204-RWRC modules (RWR and Common Mode Choke assembly) are still available.

Rockwell Automation Publication 20A-TD001L-EN-P - December 2020

17

Reflective Wave Reduction Devices

1321-RWR devices are used at the output of the drive to reduce dv/dt and motor terminal peak voltages

480V, 60 Hz, Three-phase

Drive Cat. No.

kW (Hp)

20AD1P1-ND

0.37 (0.5)

20AD2P1-ND

0.75 (1.0)

20AD3P4-ND

1.5 (2.0)

20AD5P0-ND

2.2 (3.0)

20AD8P0-ND

4.0 (5.0)

20AD011-ND

5.5 (7.5)

20AD014-ND

7.5 (10)

20AD022-ND

11 (15)

20AD027-ND

15 (20)

20AD034-ND

18.5 (25)

20AD040-ND

22 (30)

20AD052-ND

30 (40)

20AD065-ND

37 (50)

RWR Filter Cat. No. -- -- -- -- 1321-RWR8-DP 1321-RWR12-DP 1321-RWR18-DP 1321-RWR25-DP 1321-RWR35-DP 1321-RWR35-DP 1321-RWR45-DP 1321-RWR55-DP 1321-RWR80-DP

600V, 60 Hz, Three-phase

Drive Cat. No.

kW (Hp)

20AE0P9-ND

0.37 (0.5)

20AE1P7-ND

0.75 (1.0)

20AE2P7-ND

1.5 (2.0)

20AE3P9-ND

2.2 (3.0)

20AE6P1-ND

4.0 (5.0)

20AE9P0-ND

5.5 (7.5)

20AE011-ND

7.5 (10)

20AE017-ND

11 (15)

20AE022-ND

15 (20)

20AE027-ND

18.5 (25)

20AE032-ND

22 (30)

20AE041-ND

30 (40)

20AE052-ND

37 (50)

RWR Filter Cat. No. -- -- -- -- 1321-RWR8-EP 1321-RWR12-EP 1321-RWR18-EP 1321-RWR25-EP 1321-RWR35-EP 1321-RWR45-EP 1321-RWR55-EP 1321-RWR80-EP 1321-RWR100-EP

Isolation Transformers

For installations that have specific types of AC supply configurations or require drive protection due to AC line disturbances, isolation transformers are available. The isolation transformers are IP32, NEMA/UL Type 3R Standalone, 4...6% Nominal Impedance.

Motor Rating
kW Hp 0.25 0.33 0.37 0.5 0.55 0.75 0.75 1.0 1.1 1.5 1.5 2.0 2.2 3.0 4.0 5.0 5.5 7.5 7.5 10 11 15 15 20 18.5 25 22 30 30 40 37 50

240V, 60 Hz, Three-phase, 240V Primary, and 240V Secondary Cat. No. -- -- -- -- -- -- -- 1321-3TW007-AA 1321-3TW011-AA 1321-3TW014-AA 1321-3TW020-AA 1321-3TW027-AA 1321-3TW034-AA -- -- --

460V, 60 Hz, Three-phase, 460V Primary, and 460V Secondary Cat. No. 1321-3TW005-BB 1321-3TW005-BB 1321-3TW005-BB 1321-3TW005-BB 1321-3TW005-BB 1321-3TW005-BB 1321-3TW005-BB 1321-3TW007-BB 1321-3TW011-BB 1321-3TW014-BB 1321-3TW020-BB 1321-3TW027-BB 1321-3TW034-BB 1321-3TW040-BB 1321-3TW051-BB 1321-3TH063-BB

575V, 60 Hz, Three-phase, 575V Primary, and 575V Secondary Cat. No. -- 1321-3TW005-CC -- 1321-3TW005-CC -- 1321-3TW005-CC 1321-3TW005-CC 1321-3TW007-CC 1321-3TW011-CC 1321-3TW014-CC 1321-3TW020-CC 1321-3TW027-CC 1321-3TW034-CC 1321-3TW040-CC 1321-3TW051-CC 1321-3TH063-CC

18

Rockwell Automation Publication 20A-TD001L-EN-P - December 2020

Input Line Reactors and Output Line Reactors

For impedance matching, protection from AC line disturbances or motor protection, reactors are available for both the input and output sides of the drive. 240V, 60 Hz, Three-phase, 3% Impedance

Drive Cat. No. Duty

20AB2P2 20AB2P2 20AB4P2 20AB4P2 20AB6P8 20AB6P8 20AB9P6 20AB9P6 20AB015 20AB015 20AB022 20AB022 20AB028 20AB028 20AB042 20AB042 20AB054 20AB054 20AB070 20AB070

Heavy Duty Normal Duty Heavy Duty Normal Duty Heavy Duty Normal Duty Heavy Duty Normal Duty Heavy Duty Normal Duty Heavy Duty Normal Duty Heavy Duty Normal Duty Heavy Duty Normal Duty Heavy Duty Normal Duty Heavy Duty Normal Duty

Input Line Reactor (1)

Output Line Reactor (1)

Hp

IP00 (NEMA / UL Type Open) IP11 (NEMA / UL Type 1) IP00 (NEMA / UL Type Open) IP11 (NEMA / UL Type 1)

Cat. No.

Cat. No.

Cat. No.

Cat. No.

0.33

1321-3R2-D

1321-3RA2-D

1321-3R2-D

1321-3RA2-D

0.5

1321-3R2-D

1321-3RA2-D

1321-3R2-D

1321-3RA2-D

0.75

1321-3R4-A

1321-3RA4-A

1321-3R4-A

1321-3RA4-A

1

1321-3R4-A

1321-3RA4-A

1321-3R4-A

1321-3RA4-A

1.5

1321-3R8-B

1321-3RA8-B

1321-3R8-A

1321-3RA8-A

2

1321-3R8-A

1321-3RA8-A

1321-3R8-A

1321-3RA8-A

2

1321-3R8-A

1321-3RA8-A

1321-3R12-A

1321-3RA12-A

3

1321-3R12-A

1321-3RA12-A

1321-3R12-A

1321-3RA12-A

3

1321-3R12-A

1321-3RA12-A

1321-3R18-A

1321-3RA18-A

5

1321-3R18-A

1321-3RA18-A

1321-3R18-A

1321-3RA18-A

5

1321-3R18-A

1321-3RA18-A

1321-3R25-A

1321-3RA25-A

7.5

1321-3R25-A

1321-3RA25-A

1321-3R25-A

1321-3RA25-A

7.5

1321-3R25-A

1321-3RA25-A

1321-3R35-A

1321-3RA35-A

10

1321-3R35-A

1321-3RA35-A

1321-3R35-A

1321-3RA35-A

10

1321-3R35-A

1321-3RA35-A

1321-3R45-A

1321-3RA45-A

15

1321-3R45-A

1321-3RA45-A

1321-3R45-A

1321-3RA45-A

15

1321-3R45-A

1321-3RA45-A

1321-3R55-A

1321-3RA55-A

20

1321-3R55-A

1321-3RA55-A

1321-3R55-A

1321-3RA55-A

20

1321-3R55-A

1321-3RA55-A

1321-3R80-A

1321-3RA80-A

25

1321-3R80-A

1321-3RA80-A

1321-3R80-A

1321-3RA80-A

(1) Input line reactors were sized based on the NEC Fundamental Motor Amps. Output line reactors were sized based on the VFD rated output currents.
240V, 60 Hz, Three-phase, 5% Impedance

Drive Cat. No. Duty

20AB2P2 20AB2P2 20AB4P2 20AB4P2 20AB6P8 20AB6P8 20AB9P6 20AB9P6 20AB015 20AB015 20AB022 20AB022 20AB028 20AB028 20AB042 20AB042 20AB054 20AB054 20AB070 20AB070

Heavy Duty Normal Duty Heavy Duty Normal Duty Heavy Duty Normal Duty Heavy Duty Normal Duty Heavy Duty Normal Duty Heavy Duty Normal Duty Heavy Duty Normal Duty Heavy Duty Normal Duty Heavy Duty Normal Duty Heavy Duty Normal Duty

Input Line Reactor (1)

Output Line Reactor (1)

Hp

IP00 (NEMA / UL Type Open) IP11 (NEMA / UL Type 1) IP00 (NEMA / UL Type Open) IP11 (NEMA / UL Type 1)

Cat. No.

Cat. No.

Cat. No.

Cat. No.

0.33

1321-3R2-A

1321-3RA2-A

1321-3R2-A

1321-3RA2-A

0.5

1321-3R2-A

1321-3RA2-A

1321-3R2-A

1321-3RA2-A

0.75

1321-3R4-B

1321-3RA4-B

1321-3R4-B

1321-3RA4-B

1

1321-3R4-B

1321-3RA4-B

1321-3R4-B

1321-3RA4-B

1.5

1321-3R8-B

1321-3RA8-B

1321-3R8-B

1321-3RA8-B

2

1321-3R8-B

1321-3RA8-B

1321-3R8-B

1321-3RA8-B

2

1321-3R8-B

1321-3RA8-B

1321-3R12-B

1321-3RA12-B

3

1321-3R12-B

1321-3RA12-B

1321-3R12-B

1321-3RA12-B

3

1321-3R12-B

1321-3RA12-B

1321-3R18-B

1321-3RA18-B

5

1321-3R18-B

1321-3RA18-B

1321-3R18-B

1321-3RA18-B

5

1321-3R18-B

1321-3RA18-B

1321-3R25-B

1321-3RA25-B

7.5

1321-3R25-B

1321-3RA25-B

1321-3R25-B

1321-3RA25-B

7.5

1321-3R25-B

1321-3RA25-B

1321-3R35-B

1321-3RA35-B

10

1321-3R35-B

1321-3RA35-B

1321-3R35-B

1321-3RA35-B

10

1321-3R35-B

1321-3RA35-B

1321-3R45-B

1321-3RA45-B

15

1321-3R45-B

1321-3RA45-B

1321-3R45-B

1321-3RA45-B

15

1321-3R45-B

1321-3RA45-B

1321-3R55-B

1321-3RA55-B

20

1321-3R55-B

1321-3RA55-B

1321-3R55-B

1321-3RA55-B

20

1321-3R55-B

1321-3RA55-B

1321-3R80-B

1321-3RA80-B

25

1321-3R80-B

1321-3RA80-B

1321-3R80-B

1321-3RA80-B

(1) Input line reactors were sized based on the NEC Fundamental Motor Amps. Output line reactors were sized based on the VFD rated output currents.

Rockwell Automation Publication 20A-TD001L-EN-P - December 2020

19

480V, 60 Hz, Three-phase, 3% Impedance

Drive Cat. No. Duty

20AD1P1 20AD1P1 20AD2P1 20AD2P1 20AD3P4 20AD3P4 20AD5P0 20AD5P0 20AD8P0 20AD8P0 20AD011 20AD011 20AD014 20AD014 20AD022 20AD022 20AD027 20AD027 20AD034 20AD034 20AD040 20AD040 20AD052 20AD052 20AD065 20AD065

Heavy Duty Normal Duty Heavy Duty Normal Duty Heavy Duty Normal Duty Heavy Duty Normal Duty Heavy Duty Normal Duty Heavy Duty Normal Duty Heavy Duty Normal Duty Heavy Duty Normal Duty Heavy Duty Normal Duty Heavy Duty Normal Duty Heavy Duty Normal Duty Heavy Duty Normal Duty Heavy Duty Normal Duty

Input Line Reactor (1)

Output Line Reactor (1)

Hp

IP00 (NEMA / UL Type Open) IP11 (NEMA / UL Type 1) IP00 (NEMA / UL Type Open) IP11 (NEMA / UL Type 1)

Cat. No.

Cat. No.

Cat. No.

Cat. No.

0.33

1321-3R1-C

1321-3RA1-C

1321-3R2-B

1321-3RA2-B

0.5

1321-3R1-C

1321-3RA1-C

1321-3R2-B

1321-3RA2-B

0.75

1321-3R2-A

1321-3RA2-A

1321-3R2-A

1321-3RA2-A

1

1321-3R2-A

1321-3RA2-A

1321-3R2-A

1321-3RA2-A

1.5

1321-3R4-C

1321-3RA4-C

1321-3R4-B

1321-3RA4-B

2

1321-3R4-B

1321-3RA4-B

1321-3R4-B

1321-3RA4-B

2

1321-3R4-B

1321-3RA4-B

1321-3R8-C

1321-3RA8-C

3

1321-3R8-C

1321-3RA8-C

1321-3R8-C

1321-3RA8-C

3

1321-3R8-C

1321-3RA8-C

1321-3R8-B

1321-3RA8-B

5

1321-3R8-B

1321-3RA8-B

1321-3R8-B

1321-3RA8-B

5

1321-3R8-B

1321-3RA8-B

1321-3R12-B

1321-3RA12-B

7.5

1321-3R12-B

1321-3RA12-B

1321-3R12-B

1321-3RA12-B

7.5

1321-3R12-B

1321-3RA12-B

1321-3R18-B

1321-3RA18-B

10

1321-3R18-B

1321-3RA18-B

1321-3R18-B

1321-3RA18-B

10

1321-3R18-B

1321-3RA18-B

1321-3R25-B

1321-3RA25-B

15

1321-3R25-B

1321-3RA25-B

1321-3R25-B

1321-3RA25-B

15

1321-3R25-B

1321-3RA25-B

1321-3R25-B

1321-3RA25-B

20

1321-3R35-B

1321-3RA35-B

1321-3R25-B

1321-3RA25-B

20

1321-3R35-B

1321-3RA35-B

1321-3R35-B

1321-3RA35-B

25

1321-3R35-B

1321-3RA35-B

1321-3R35-B

1321-3RA35-B

25

1321-3R35-B

1321-3RA35-B

1321-3R45-B

1321-3RA45-B

30

1321-3R45-B

1321-3RA45-B

1321-3R45-B

1321-3RA45-B

30

1321-3R45-B

1321-3RA45-B

1321-3R55-B

1321-3RA55-B

40

1321-3R55-B

1321-3RA55-B

1321-3R55-B

1321-3RA55-B

40

1321-3R55-B

1321-3RA55-B

1321-3R80-B

1321-3RA80-B

50

1321-3R80-B

1321-3RA80-B

1321-3R80-B

1321-3RA80-B

(1) Input line reactors were sized based on the NEC Fundamental Motor Amps. Output line reactors were sized based on the VFD rated output currents.
480V, 60 Hz, Three-phase, 5% Impedance

Drive Cat. No. Duty

20AD1P1 20AD1P1 20AD2P1 20AD2P1 20AD3P4 20AD3P4 20AD5P0 20AD5P0 20AD8P0 20AD8P0 20AD011 20AD011 20AD014 20AD014 20AD022 20AD022 20AD027
20AD027
20AD034
20AD034 20AD040 20AD040 20AD052 20AD052 20AD065 20AD065

Heavy Duty Normal Duty Heavy Duty Normal Duty Heavy Duty Normal Duty Heavy Duty Normal Duty Heavy Duty Normal Duty Heavy Duty Normal Duty Heavy Duty Normal Duty Heavy Duty Normal Duty Heavy Duty
Normal Duty
Heavy Duty
Normal Duty Heavy Duty Normal Duty Heavy Duty Normal Duty Heavy Duty Normal Duty

Input Line Reactor (1)

Output Line Reactor (1)

Hp

IP00 (NEMA / UL Type Open) IP11 (NEMA / UL Type 1) IP00 (NEMA / UL Type Open) IP11 (NEMA / UL Type 1)

Cat. No.

Cat. No.

Cat. No.

Cat. No.

0.33

1321-3R1-B

1321-3RA1-B

1321-3R2-C

1321-3RA2-C

0.5

1321-3R1-B

1321-3RA1-B

1321-3R2-C

1321-3RA2-C

0.75

1321-3R2-C

1321-3RA2-C

1321-3R2-B

1321-3RA2-B

1

1321-3R2-B

1321-3RA2-B

1321-3R2-B

1321-3RA2-B

1.5

1321-3R4-D

1321-3RA4-D

1321-3R4-D

1321-3RA4-D

2

1321-3R4-D

1321-3RA4-D

1321-3R4-D

1321-3RA4-D

2

1321-3R4-D

1321-3RA4-D

1321-3R8-D

1321-3RA8-D

3

1321-3R8-D

1321-3RA8-D

1321-3R8-D

1321-3RA8-D

3

1321-3R8-D

1321-3RA8-D

1321-3R8-C

1321-3RA8-C

5

1321-3R8-C

1321-3RA8-C

1321-3R8-C

1321-3RA8-C

5

1321-3R8-C

1321-3RA8-C

1321-3R12-C

1321-3RA12-C

7.5

1321-3R12-C

1321-3RA12-C

1321-3R12-C

1321-3RA12-C

7.5

1321-3R12-C

1321-3RA12-C

1321-3R18-C

1321-3RA18-C

10

1321-3R18-C

1321-3RA18-C

1321-3R18-C

1321-3RA18-C

10

1321-3R18-C

1321-3RA18-C

1321-3R25-C

1321-3RA25-C

15

1321-3R25-C

1321-3RA25-C

1321-3R25-C

1321-3RA25-C

15

1321-3R25-C

1321-3RA25-C

1321-3R25-C

1321-3RA25-C

20

1321-3R35-C (2)

1321-3RA35-C (2)

1321-3R25-C

1321-3RA25-C

20

1321-3R35-C (2)

1321-3RA35-C (2)

1321-3R35-C

1321-3RA35-C

25

1321-3R35-C

1321-3RA35-C

1321-3R35-C

1321-3RA35-C

25

1321-3R35-C

1321-3RA35-C

1321-3R45-C

1321-3RA45-C

30

1321-3R45-C

1321-3RA45-C

1321-3R45-C

1321-3RA45-C

30

1321-3R45-C

1321-3RA45-C

1321-3R55-C

1321-3RA55-C

40

1321-3R55-C

1321-3RA55-C

1321-3R55-C

1321-3RA55-C

40

1321-3R55-C

1321-3RA55-C

1321-3R80-C

1321-3RA80-C

50

1321-3R80-C

1321-3RA80-C

1321-3R80-C

1321-3RA80-C

(1) Input line reactors were sized based on the NEC Fundamental Motor Amps. Output line reactors were sized based on the VFD rated output currents. (2) 4% impedance.

20

Rockwell Automation Publication 20A-TD001L-EN-P - December 2020

600V, 60 Hz, Three-phase, 3% Impedance

Drive Cat. No. Duty

20AE0P9 20AE0P9 20AE1P7 20AE1P7 20AE2P7 20AE2P7 20AE3P9 20AE3P9 20AE6P1 20AE6P1 20AE9P0 20AE9P0 20AE011 20AE011 20AE017 20AE017 20AE022 20AE022 20AE027 20AE027 20AE032 20AE032 20AE041 20AE041 20AE052 20AE052

Heavy Duty Normal Duty Heavy Duty Normal Duty Heavy Duty Normal Duty Heavy Duty Normal Duty Heavy Duty Normal Duty Heavy Duty Normal Duty Heavy Duty Normal Duty Heavy Duty Normal Duty Heavy Duty Normal Duty Heavy Duty Normal Duty Heavy Duty Normal Duty Heavy Duty Normal Duty Heavy Duty Normal Duty

Input Line Reactor (1)

Output Line Reactor (1)

Hp

IP00 (NEMA / UL Type Open) IP11 (NEMA / UL Type 1) IP00 (NEMA / UL Type Open) IP11 (NEMA / UL Type 1)

Cat. No.

Cat. No.

Cat. No.

Cat. No.

0.33

1321-3R1-C

1321-3RA1-C

1321-3R1-B

1321-3RA1-B

0.5

1321-3R1-C

1321-3RA1-C

1321-3R1-B

1321-3RA1-B

0.5

1321-3R2-B

1321-3RA2-B

1321-3R2-B

1321-3RA2-B

1

1321-3R2-B

1321-3RA2-B

1321-3R2-B

1321-3RA2-B

1

1321-3R2-A

1321-3RA2-A

1321-3R4-D

1321-3RA4-D

2

1321-3R4-C

1321-3RA4-C

1321-3R4-D

1321-3RA4-D

2

1321-3R4-C

1321-3RA4-C

1321-3R4-C

1321-3RA4-C

3

1321-3R4-C

1321-3RA4-C

1321-3R4-C

1321-3RA4-C

3

1321-3R4-C

1321-3RA4-C

1321-3R8-C

1321-3RA8-C

5

1321-3R8-C

1321-3RA8-C

1321-3R8-C

1321-3RA8-C

5

1321-3R8-C

1321-3RA8-C

1321-3R12-C

1321-3RA12-C

7.5

1321-3R12-C

1321-3RA12-C

1321-3R12-C

1321-3RA12-C

7.5

1321-3R12-C

1321-3RA12-C

1321-3R12-B

1321-3RA12-B

10

1321-3R12-B

1321-3RA12-B

1321-3R12-B

1321-3RA12-B

10

1321-3R12-B

1321-3RA12-B

1321-3R18-B

1321-3RA18-B

15

1321-3R18-B

1321-3RA18-B

1321-3R18-B

1321-3RA18-B

15

1321-3R18-B

1321-3RA18-B

1321-3R25-B

1321-3RA25-B

20

1321-3R25-B

1321-3RA25-B

1321-3R25-B

1321-3RA25-B

20

1321-3R25-B

1321-3RA25-B

1321-3R35-C

1321-3RA35-C

25

1321-3R35-C

1321-3RA35-C

1321-3R35-C

1321-3RA35-C

25

1321-3R35-C

1321-3RA35-C

1321-3R35-B

1321-3RA35-B

30

1321-3R35-B

1321-3RA35-B

1321-3R35-B

1321-3RA35-B

30

1321-3R35-B

1321-3RA35-B

1321-3R45-B

1321-3RA45-B

40

1321-3R45-B

1321-3RA45-B

1321-3R45-B

1321-3RA45-B

40

1321-3R45-B

1321-3RA45-B

1321-3R55-B

1321-3RA55-B

50

1321-3R55-B

1321-3RA55-B

1321-3R55-B

1321-3RA55-B

(1) Input line reactors were sized based on the NEC Fundamental Motor Amps. Output line reactors were sized based on the VFD rated output currents.
600V, 60 Hz, Three-phase, 5% Impedance

Drive Cat. No. Duty

20AE0P9 20AE0P9 20AE1P7 20AE1P7 20AE2P7 20AE2P7 20AE3P9 20AE3P9 20AE6P1 20AE6P1 20AE9P0 20AE9P0 20AE011 20AE011 20AE017 20AE017 20AE022 20AE022 20AE027 20AE027 20AE032 20AE032 20AE041 20AE041 20AE052 20AE052

Heavy Duty Normal Duty Heavy Duty Normal Duty Heavy Duty Normal Duty Heavy Duty Normal Duty Heavy Duty Normal Duty Heavy Duty Normal Duty Heavy Duty Normal Duty Heavy Duty Normal Duty Heavy Duty Normal Duty Heavy Duty Normal Duty Heavy Duty Normal Duty Heavy Duty Normal Duty Heavy Duty Normal Duty

Input Line Reactor (1)

Output Line Reactor (1)

Hp

IP00 (NEMA / UL Type Open) IP11 (NEMA / UL Type 1) IP00 (NEMA / UL Type Open) IP11 (NEMA / UL Type 1)

Cat. No.

Cat. No.

Cat. No.

Cat. No.

0.33

1321-3R1-A

1321-3RA1-A

1321-3R1-B

1321-3RA1-B

0.5

1321-3R1-B

1321-3RA1-B

1321-3R1-B

1321-3RA1-B

0.5

1321-3R1-B

1321-3RA1-B

1321-3R2-C

1321-3RA2-C

1

1321-3R2-C

1321-3RA2-C

1321-3R2-C

1321-3RA2-C

1

1321-3R2-C

1321-3RA2-C

1321-3R4-D (2)

1321-3RA4-D (2)

2

1321-3R4-D (2)

1321-3RA4-D (2)

1321-3R4-D (2)

1321-3RA4-D (2)

2

1321-3R4-D (2)

1321-3RA4-D (2)

1321-3R4-D

1321-3RA4-D

3

1321-3R4-D

1321-3RA4-D

1321-3R4-D

1321-3RA4-D

3

1321-3R4-D

1321-3RA4-D

1321-3R8-D

1321-3RA8-D

5

1321-3R8-D

1321-3RA8-D

1321-3R8-D

1321-3RA8-D

5

1321-3R8-D

1321-3RA8-D

1321-3R12-C (2)

1321-3RA12-C (2)

7.5

1321-3R12-C (2)

1321-3RA12-C (2)

1321-3R12-C (2)

1321-3RA12-C (2)

7.5

1321-3R12-C (2)

1321-3RA12-C (2)

1321-3R12-C

1321-3RA12-C

10

1321-3R12-C

1321-3RA12-C

1321-3R12-C

1321-3RA12-C

10

1321-3R12-C

1321-3RA12-C

1321-3R18-C

1321-3RA18-C

15

1321-3R18-C

1321-3RA18-C

1321-3R18-C

1321-3RA18-C

15

1321-3R18-C

1321-3RA18-C

1321-3R25-C (2)

1321-3RA25-C (2)

20

1321-3R25-C (2)

1321-3RA25-C (2)

1321-3R25-C (2)

1321-3RA25-C (2)

20

1321-3R25-C (2)

1321-3RA25-C (2)

1321-3R35-C (2)

1321-3RA35-C (2)

25

1321-3R35-C (2)

1321-3RA35-C (2)

1321-3R35-C (2)

1321-3RA35-C (2)

25

1321-3R35-C (2)

1321-3RA35-C (2)

1321-3R35-C (2)

1321-3RA35-C (2)

30

1321-3R35-C (2)

1321-3RA35-C (2)

1321-3R35-C (2)

1321-3RA35-C (2)

30

1321-3R35-C (2)

1321-3RA35-C (2)

1321-3R45-C

1321-3RA45-C

40

1321-3R45-C

1321-3RA45-C

1321-3R45-C

1321-3RA45-C

40

1321-3R45-C

1321-3RA45-C

1321-3R55-C

1321-3RA55-C

50

1321-3R55-C

1321-3RA55-C

1321-3R55-C

1321-3RA55-C

(1) Input line reactors were sized based on the NEC Fundamental Motor Amps. Output line reactors were sized based on the VFD rated output currents. (2) 4% impedance.

Rockwell Automation Publication 20A-TD001L-EN-P - December 2020

21

Installation Power Wiring
The PowerFlex 70 has the following built in protective features to help simplify installation: � Ground fault protection during startup and running helps verify reliability � Electronic motor overload protection increases motor life � Removable MOV to ground and common mode capacitors to ground verify compatibility with ungrounded systems. These devices must be disconnected if the drive is installed on an ungrounded, high-resistance, or B phase grounded distribution system. These devices must also be disconnected if a regenerative unit is used as a bus supply or brake. � 6 kV transient protection increased robustness for 380...480V system voltages
There are many other factors that must be considered for optimal performance in any given application. The following block diagram highlights the primary installation considerations. Consult Wiring and Grounding Guidelines for Pulse Width Modulated (PWM) AC Drives, publication DRIVES-IN001, for detailed recommendations on input power conditioning, dynamic braking, reflected wave protection, and motor cables types.

Input Fuses - Page 30 Input Cable Length - Page 34
Removable MOV and Common Mode Capacitors (underneath cover) - See the PowerFlex 70 Adjustable Frequency AC Drive Installation Instructions, publication 20A-IN009, for location and instructions.

Branch Circuit Protective Devices - Page 30
Input Power Conditioning - Page 18 EMC Requirements - See the PowerFlex 70 Adjustable Frequency AC Drive Installation Instructions, publication 20A-IN009.
LCD Human Interface Module - Page 12 Power Terminal Block - See Below
L1 L2 L3 BR1 BR2 T1 T2 T3 PE PE R S T +DC BRK U V W
Dynamic Brake Resistor - Page 12
Reflected Wave Reduction - Page 18 Cable Requirements - Page 28 Integral Class 10 Motor Overload

22

Rockwell Automation Publication 20A-TD001L-EN-P - December 2020

Terminal Blocks
This section includes: � Terminal Block Specifications � Hardware Enable Circuitry on page 25 � Safe Torque Off Board Terminal Block on page 25 � Encoder Interface Terminal Block on page 25 � EMC Filters on page 26 � Other Options on page 26 � I/O Wiring Examples on page 27

Terminal Block Specifications

No. Name

Description

 I/O terminal block Signal and control connections



Power terminal block

Input power and motor connections

 SHLD terminal

Terminating point for wiring shields

Frame

Wire Size Range(1)

Max, mm2 (AWG)

Min, mm2 (AWG)

All

1.5 (16)

0.05 (30)

A, B, and C 3.5 (12)

0.3 (22)

D

8.4 (8)

0.8 (18)

E

25.0 (3)

2.5 (14)

All

--

--

(1) These are the maximum/minimum sizes that the terminal block accepts, not recommendations.

Torque
Max, N�m (lb�in) 0.55 (4.9) 0.66 (5.5) 1.7 (15) 2.71 (24)
1.6 (14)

Recommended, N�m (lb�in)
0.5 (4.4) 0.6 (5) 1.4 (12) 2.71 (24)
1.6 (14)

Terminal
BR1 BR2
+DC �DC
PE
U, V, W
R, S, T

Description
DC brake (+) DC brake (�)
DC bus (+) DC bus (�)
PE ground
U (T1), V (T2), W (T3)
R (L1), S (L2), T (L3)

Notes dB resistor connection - Important: Do not connect both an internal and external dB resistor simultaneously. This can violate the minimum allowed dB resistance and cause drive damage.
 Test point on Frames A...D on the left or right of the power terminal block. Frame E has a dedicated terminal.
-- To the motor AC line input power

Typical Terminal Block Location

Power Terminals

-DC

-DC

L1 L2 L3 BR1 BR2 T1 T2 T3 PE PE R S T +DC BRK U V W
Frames A...D

L1 L2 L3 +DC �DC BR1 BR2 T1 T2 T3

RST

U VW

PE

PE

M6

M6

Frame E

Rockwell Automation Publication 20A-TD001L-EN-P - December 2020

23

Control Terminals

14

26

1

13

No. Signal

1 Digital In 1

2 Digital In 2 3 Digital In 3 4 Digital In 4 5 Digital In 5 6 Digital In 6 7 24V Common 8 Digital In Common

9 +24V DC

10 +10V Pot Reference

11

Digital Out 1 � N.O.(1)

12 Digital Out 1 Common

13 Digital Out 1 � N.C.(1)

Factory Default Stop � CF (CF = clear fault) Start Auto/Man Speed Sel 1 Speed Sel 2 Speed Sel 3 � � � �
NOT Fault
Fault

Description

Related Parameters

11.2 mA at 24V DC

19.2V min on state

3.2V max off state

361...366

Important: Use only 24V DC, not suitable for 115V AC circuitry.(3)

Inputs can be wired as sink or source.

Drive supplied power for digital In1...6 inputs only. Not intended for use on circuits outside of the drive. See examples beginning on page 27. 150 mA max load.
2 k min load.

Max Resistive Load 250V AC / 30V DC 50VA / 60 Watts Min DC Load 10 �A, 10 mV DC

Max Inductive Load 250V AC / 30V DC 25VA / 30 Watts

380...387

14 Analog In 1 (� Volts) 15 Analog In 1 (+ Volts)

(2)

Non-isolated, 0...10V, 10 bit, 100 k input impedance.(4)

Voltage � Reads

16 17 18

Analog In 1 (� Current) Analog In 1 (+ Current) Analog In 2 (� Volts)

value at 14 & 15

Non-isolated, 4...20 mA, 10 bit, 100  input impedance.(4) Isolated, bipolar, differential, 0...10V unipolar (10 bit) or �10V

320...327

19 Analog In 2 (+ Volts)

(2)
Voltage � Reads

bipolar (10 bit and sign), 100 k input impedance.(5)

20 21

Analog In 2 (� Current) Analog In 2 (+ Current)

value at 18 & 19

Isolated, 4...20mA, 10 bit and sign, 100  input impedance.(5)

10V Pot Common

22 Analog Out (� Volts)

Analog Out (� Current)

(2)
Output Freq

23

Analog Out (+ Volts) Analog Out (+ Current)

0...10V, 10 bit, 10 k (2 k min) load. 0...20 mA, 10 bit, 400  max load.(6) Referenced to chassis ground. Common if internal 10V supply (terminal 10) is used.

340...344

24 Digital Out 2 � N.O.(1)

Run

25 Digital Out 2 Common

See description at Numbers 11...13.

380...387

26 Digital Out 2 � N.C.(1)

NOT Run

(1) Contacts shown in unpowered state. Any relay that is programmed as Fault or Alarm is energized (pick up) when power is applied to the drive and de-energize (drop out) when a fault or alarm exists. Relays selected for other functions are energized only when that condition exists and are de-energize when that condition is removed.
(2) These inputs/outputs are dependent on a number of parameters. For information on related parameters, see publication, 20A-UM001. (3) For use with 115V AC circuitry. A 115V AC interface option (AK-M9-115VAC-1) must be used (4) Differential isolation - external source must be less than 10V with respect to PE. (5) Differential isolation - external source must be maintained at less than 160V with respect to PE. Input provides high common mode immunity. (6) Analog output current is only available with enhanced control drives.

24

Rockwell Automation Publication 20A-TD001L-EN-P - December 2020

Hardware Enable Circuitry
By default, you can program a digital input as an enable input. Drive software interprets the status of this input. If the application requires the drive to be disabled without software interpretation, a hardware enable configuration can be used. To set up a hardware enable configuration, use the following procedure:
1. Remove the drive cover. 2. On the main control board, locate and remove the enable jumper (ENBL JMP). 3. Wire the enable input to Digital In 6. 4. Verify that 366 [Digital In6 Sel] is set to option 1 Enable.

Safe Torque Off Board Terminal Block

No. Signal 1 Monitor - N.C.

2 Common - N.C.

4321

3 +24V DC 4 24V common

Description Normally closed contacts for monitoring relay status. Max resistive load: 250V AC / 30V DC / 50V AC / 60 W Max inductive load: 250V AC / 30V DC / 25V AC/ 30 W
Connections for user-supplied power to energize coil.

For detailed connection examples, refer to the DriveGuard Safe Torque Off Option (Series B) for PowerFlex 40P and PowerFlex 70 Enhanced Control AC Drives User Manual, publication PFLEX-UM003.

Encoder Interface Terminal Block

No. Signal

1 5...12V power(1)

2 Power return

3 Encoder B (NOT)

4 Encoder B

16

5 Encoder A (NOT)

6 Encoder A

(1) Jumper selectable +5...12V is available on 20A-ENC-1 encoder boards.

Description Internal power source 250 mA (isolated)
Single channel or quadrature B input.
Single channel or quadrature A input.

Jumper Settings
Receive Voltage = 12V = 5V
= 12V = 5V
Send Voltage

Rockwell Automation Publication 20A-TD001L-EN-P - December 2020

25

Sample Encoder Wiring

I/O

Connection Example

1

Encoder Power �

2

Internal Drive Power 3

Internal (drive) 12V DC, 4

250 mA

5 6

+12V DC (250 mA)
Common
to SHLD

I/O

Connection Example

Encoder Power � External Power Source

to SHLD External Power Supply

+ Common
1 2 3 4 5
6 7 8 9

to Power Supply

Common

1

Encoder Signal �

2

Single-Ended, Dual Channel

3 4 5

B NOT B A NOT

6

A

to SHLD

Encoder Signal � 1

Differential, Dual

2 3

Channel

4

5

6

to SHLD
B NOT B A NOT A

EMC Filters

Description Internal 3-phase 200...480 filter

Factory-installed (Position 13)
A

The following two tables provide the catalog number codes for EMC filters, and the current ratings and voltages where filters are used. These tables are also provided in the Catalog Number Explanation on page 6.

Emission Class

Code

Rating

A

Filtered

N

Not Filtered

Emission Class by Frame Current Rating (A...E) and Voltage

A(1)(2) B(2)

C

D

E

240V A or N A or N A

A

A

400V A or N A or N A

A

A

480V A or N A or N A

A

A

600V N

N

N

N

A

(1) If a filter is used with a Frame A current rating, the drive with internal filter is supplied in the B Frame to accommodate the additional size.
(2) "A or N" indicates that filtering is optional.

Other Options

Description
Service connection board(1) 115V AC interface card Frame E flange gasket

Catalog No. User Installed SK-M9-SCB1 AK-M9-115VAC-1 AK-M9-GASKET1-E4

(1) Provides temporary DPI/HIM connection for NEMA 1 and flange drives with cover removed.

Service Connection Board SK-M9-SCB1

115V Interface Card AK-M9-115VAC-1

26

Rockwell Automation Publication 20A-TD001L-EN-P - December 2020

I/O Wiring Examples
Input/Output
Potentiometer Unipolar Speed Reference 10 k Pot. Recommended (2 k min)
Joystick Bipolar Speed Reference �10V Input
Analog Input Bipolar Speed Reference �10V Input

Connection Example
18 19
22 10

18 19
22 -10V Com+10V Power Source

�

18

+

19

Required Parameter Settings
Select Speed Reference source: Param. 090 = 1 "Analog In 2" Adjust Scaling: Param. 091, 092, 322, 323 Check Results: Param. 016
Set Direction Mode: Param. 190 = 1 "Bipolar" Adjust Scaling: Param. 091, 092, 325, 326 Check Results: Param. 017
Adjust Scaling: Param. 091, 092, 325, 326 Check Results: Param. 017

Analog Input Unipolar Speed Reference 0V...+10V Input
Analog Input, PTC PTC OT set > 5V PTC OT cleared < 4V PTC Short < 0.2V

Common

18

+

19

Ferrite Bead

1.8k

14

PTC

15

22 10
3.32k Ohm

Adjust Scaling: Param. 091, 092, 325, 326 Check Results: Param. 017
Set Fault Config 1: Param. 238, Bit #7 = 1 "Enabled"
Set Alarm Config 1: Param. 259, Bit #11 = 1 "Enabled"

Analog Input Unipolar Speed Reference 4...20 mA Input

Common

20

+

21

Configure Input for Current: Param. 320, Bit #1 = 1 "Current" Adjust Scaling: Param. 091, 092, 325, 326 Check Results: Param. 017

�+

Analog Output Unipolar 0V ...+10V Output. Can Drive a 2 k load (25 mA short circuit limit)
22 23
Internal Supply

2 Wire Control Nonreversing 2 Wire Control Reversing

2 Stop-Run
7 8 9
External Supply
Run Rev 1 2
Run Fwd
8
+24V Common

Select Source Value: Param. 342 Adjust Scaling: Param. 343, 344
Disable Digital Input 1: Param. 361 = 0 "Not Used" Set Digital Input 2: Param. 362 = 7 "Run"
Set Digital Input 1: Param. 361 = 8 "Run Forward" Set Digital Input 2: Param. 362 = 9 "Run Reverse"

Rockwell Automation Publication 20A-TD001L-EN-P - December 2020

27

Input/Output 3 Wire Control
3 Wire Control
Digital Output Form C Relays Energized in Normal State.
Enable Input Shown in enabled state.

Connection Example Internal Supply

Stop 1 2
Start 7 8 9

External Supply

Stop 1 2
Start 8
+24V Common

11 12 13

or

24

25

Power

26

Source

6

Required Parameter Settings Use factory default parameter settings.
Use factory default parameter settings.
Select Source: Param. 380, 384
Configure with parameter 366 For dedicated hardware Enable: Remove Enable Jumper (ENBL JMP) on the Main Control Board.

Cable Recommendations
This section includes: � Cable Types Acceptable for 200...600V Installations � Recommended Shielded Wire on page 29 � Maximum Motor Cable Lengths on page 29

Cable Types Acceptable for 200...600V Installations

Various cable types are acceptable for drive installations. For many installations, unshielded cable is adequate, provided it can be separated from sensitive circuits. As an approximate guide, allow a spacing of 0.3 m (1 ft) for every 10 m (32.8 ft) of length. In all cases, long parallel runs must be avoided. Do not use cable with an insulation thickness less than or equal to 15 mils (0.4 mm/0.015 in.). Use copper wire only. Wire gauge requirements and recommendations are based on 75 C (167 F). Do not reduce wire gauge when using higher temperature wire. See 208/240 Volt AC Three-phase Input Drive Ratings and Input Protection Devices on page 30.

Unshielded

The following wire types are acceptable for drive installation in dry environments, as long as adequate free air space and/or conduit fill rate limits are provided: Thermoplastic High Heat-resistant Nylon-coated (THHN), Thermoplastic Heat and Water-resistant Nylon-coated (THWN), or similar wire. The wire must have a minimum insulation thickness of 15 mils (0.4 mm/0.015 in.) and cannot have large variations in insulation concentricity.

IMPORTANT Do not use THHN or similarly coated wire in wet areas.

28

Rockwell Automation Publication 20A-TD001L-EN-P - December 2020

Shielded/Armored Cable
Shielded cable has the general benefits of multi-conductor cable. It also has the benefit of a copper braided shield that can contain much of the noise that a typical AC Drive generates. Use shielded cable for installations with sensitive equipment such as weigh scales, capacitive proximity switches, and other devices that can be affected by electrical noise in the distribution system. Applications with large numbers of drives in a similar location, imposed EMC regulations, or a high degree of communications/networking are also good candidates for shielded cable.
Shielded cable can also help reduce shaft voltage and induced bearing currents for some applications. In addition, the increased impedance of shielded cable can help extend the distance that the motor can be from the drive without the addition of motor protective devices, such as terminator networks. See Reflected Wave in Wiring and Grounding Guidelines for PWM AC Drives, publication DRIVES-IN001.
Consider the general specifications of the environment of the installation, including temperature, flexibility, moisture characteristics, and chemical resistance. A braided shield can be included. If included, the braided shield is to be specified by the cable manufacturer as having coverage of at least 75%. An additional foil shield can greatly improve noise containment.
A good example of recommended cable is Belden 295xx (xx determines gauge). This cable has four Cross-linked Polyethylene (XLPE) insulated conductors with a 100% coverage foil and an 85% coverage copper braided shield (with drain wire) surrounded by a Polyvinyl Chloride (PVC) jacket.
Other types of shielded cable are available, but the use of these types can limit the allowable cable length. For example, some of the newer cables bundle four conductors of THHN wire and wrap them tightly with a foil shield. This type of construction can greatly increase the cable charging current that is required and reduce the overall drive performance. Unless specified in the individual distance tables as tested with the drive, these cables are not recommended and their performance against the lead length limits is not known.

Recommended Shielded Wire

Location Standard (option 2)
Class I and II; Division I and II

Rating/Type
Tray rated 600V, 90 �C (194 �F) RHH/RHW-2 Anixter OLF-7xxxxx or equivalent
Tray rated 600V, 90 �C (194 �F) RHH/RHW-2 Anixter 7V-7xxxx-3G or equivalent

Description
Three tinned copper conductors with XLPE insulation. 5 mil single helical copper tape (25% overlap min) with three bare copper grounds in contact with the shield. PVC jacket.
Three bare copper conductors with XLPE insulation and impervious corrugated continuously welded aluminum armor. Black sunlight resistant PVC jacket overall. Three copper grounds on #10 AWG and smaller.

ATTENTION: To avoid a possible shock hazard that is caused by induced voltages, unused wires in the conduit must be grounded at both ends. Also, if a drive sharing a conduit is being serviced or installed, disable all of the drives that are using that conduit. Disabling all of the drives that are using that conduit helps minimize the possible shock hazard from cross coupled motor leads.

Maximum Motor Cable Lengths
For information on maximum motor cable lengths, refer to the Wiring and Grounding Guidelines for Pulse Width Modulated (PWM) AC Drives, publication DRIVES-IN001.

Rockwell Automation Publication 20A-TD001L-EN-P - December 2020

29

Power Ratings and Branch Circuit Protection
See the tables in this section for power ratings and branch circuit protection information.

Single-phase Input Power

The PowerFlex 70 drive is typically used with a three-phase input supply. Single-phase operation of the drive is rated under the UL 508C listing. Rockwell Automation has verified that single-phase operation can be performed with output current that is derated by 50% of the three-phase ratings that are identified in the tables in this section.

208/240 Volt AC Three-phase Input Drive Ratings and Input Protection Devices

Cat.No.

Hp

Input

Rating Ratings

Output Amps

ND HD Amps kVA Cont. 60 s 3 s

Frame(1)

208 Volt AC Input 20AB2P2 A 0.5 0.33 2.9 1.1 2.5 2.7 3.7 20AB4P2 A 1 0.75 5.6 2 4.8 5.5 7.4 20AB6P8 B 2 1.5 10 3.6 7.8 10.3 13.8 20AB9P6 B 3 2 14 5.1 11 12.1 16.5 20AB015 C 5 3 16 5.8 17.5 19.2 26.6 20AB022 D 7.5 5 23.3 8.3 25.3 27.8 37.9 20AB028 D 10 7.5 29.8 10.7 32.2 37.9 50.6 20AB042 D 15 10 39.8 14.3 43 55.5 74 20AB054 E 20 15 57.5 20.7 62.1 72.4 96.6 20AB070 E 25 20 72.3 26.0 78.2 93.1 124 240 Volt AC Input 20AB2P2 A 0.5 0.33 2.5 1.1 2.2 2.4 3.3 20AB4P2 A 1 0.75 4.8 2 4.2 4.8 6.4 20AB6P8 B 2 1.5 8.7 3.6 6.8 9 12 20AB9P6 B 3 2 12.2 5.1 9.6 10.6 14.4 20AB015 C 5 3 13.9 5.8 15.3 17.4 23.2 20AB022 D 7.5 5 19.9 8.3 22 24.4 33 20AB028 D 10 7.5 25.7 10.7 28 33 44 20AB042 D 15 10 38.7 16.1 42 46.2 63 20AB054 E 20 15 49.8 20.7 54 63 84 20AB070 E 25 20 64.5 26.8 70 81 108 See page 33 for notes.

Dual Element Time Delay Fuse

Non-time Delay Fuse

Circuit Breaker
(2)

Motor Circuit Protector
(3)

140M Motor Protector with Adjustable Current Range(4)(5)

Min(6) Max(7) Min(6) Max(7) Max(8) Max(8) Available Catalog Numbers(9)

Minimum Enclosure Volume (in.3)(10)

6 6 6 10 15

7

10 10 10 17.5 15

7

15 15 15 30 30

15

20 25 20 40 40

30

20 35 20 70 70

30

30 50 30 100 100 30

40 70 40 125 125 50

60 100 60 175 175 70

80 125 80 200 200 100

90 175 90 300 300 100

140M-C2E-B40 140M-D8E-B40 --

3441

140M-C2E-B63 140M-D8E-B63 --

3441

140M-C2E-C10 140M-D8E-C10 140M-F8E-C10 3441

140M-C2E-C16 140M-D8E-C16 140M-F8E-C16 3441

140M-C2E-C20 140M-D8E-C20 140M-F8E-C20 3441

--

140M-D8E-C25 140M-F8E-C25 5098

--

--

140M-F8E-C32 5098

--

--

140M-F8E-C45 5098

--

--

--

--

--

--

--

--

3 4.5 3 8 15

3

6 9 6 15 15

7

15 15 15 25 25

15

20 20 20 35 35

15

20 30 20 60 60

30

25 45 25 80 80

30

35 60 35 110 110

50

50 90 50 150 150 50

60 100 60 200 200 100

90 150 90 275 275 100

140M-C2E-B25 140M-D8E-B25 --

3441

140M-C2E-B63 140M-D8E-B63 --

3441

140M-C2E-C10 140M-D8E-C10 140M-F8E-C10 3441

140M-C2E-C16 140M-D8E-C16 140M-F8E-C16 3441

140M-C2E-C16 140M-D8E-C16 140M-F8E-C16 3441

--

140M-D8E-C25 140M-F8E-C25 5098

--

--

140M-F8E-C32 5098

--

--

140M-F8E-C45 5098

--

--

--

--

--

--

--

--

400/480 Volt AC Three-phase Input Drive Ratings and Input Protection Devices

Cat.No.

Hp Rating

Input Ratings

Output Amps

ND HD Amps kVA Cont. 60 s 3 s

Frame(1)

400 Volt AC Input 20AC1P3 A 0.37 0.25 1.6 1.1 1.3 1.4 1.9 20AC2P1 A 0.75 0.55 2.5 1.8 2.1 2.4 3.2 20AC3P5 A 1.5 1.1 4.3 3 3.5 4.5 6 20AC5P0 B 2.2 1.5 6.5 4.5 5 5.5 7.5 20AC8P7 B 4 3 11.3 7.8 8.7 9.9 13.2

Dual Element Time Delay Fuse

Non-time Delay Fuse

Circuit Breaker
(2)

Motor Circuit Protector
(3)

140M Motor Protector with Adjustable Current Range(4)(5)

Min(6) Max(7) Min(6) Max(7) Max(8) Max(8) Available Catalog Numbers(9)

Minimum Enclosure Volume (in.3)(10)

3 3 3 5 15

3

4 6 4 8 15

7

6 6 6 12 15

7

10 10 10 20 20

15

15 17.5 15 30 30

15

140M-C2E-B16 --

--

3441

140M-C2E-B25 140M-D8E-B25 --

3441

140M-C2E-B63 140M-D8E-B63 --

3441

140M-C2E-C10 140M-D8E-C10 140M-F8E-C10 3441

140M-C2E-C16 140M-D8E-C16 140M-F8E-C16 3441

30

Rockwell Automation Publication 20A-TD001L-EN-P - December 2020

400/480 Volt AC Three-phase Input Drive Ratings and Input Protection Devices (Continued)

Cat.No.

Hp Rating

Input Ratings

Output Amps

ND HD Amps kVA Cont. 60 s 3 s

Frame(1)

20AC011 C 5.5 4 10.5 7.6 11.5 13 17.4 20AC015 C 7.5 5.5 15.1 10.4 15.4 17.2 23.1 20AC022 D 11 7.5 21.9 15.2 22 24.2 33 20AC030 D 15 11 30.3 21 30 33 45 20AC037 D 18.5 15 35 24.3 37 45 60 20AC043 D 22 18.5 40.7 28.2 43 56 74 20AC060 E 30 22 56.8 39.3 60 66 90 20AC072 E 37 30 68.9 47.8 72 90 120 480 Volt AC Input 20AD1P1 A 0.5 0.33 1.3 1.1 1.1 1.2 1.6 20AD2P1 A 1 0.75 2.4 2 2.1 2.4 3.2 20AD3P4 A 2 1.5 3.8 3.2 3.4 4.5 6 20AD5P0 B 3 2 5.6 4.7 5 5.5 7.5 20AD8P0 B 5 3 9.8 8.4 8 8.8 12 20AD011 C 7.5 5 9.4 7.9 11 12.1 16.5 20AD014 C 10 7.5 12.4 10.4 14 16.5 22 20AD022 D 15 10 19.9 16.6 22 24.2 33 20AD027 D 20 15 24.8 20.6 27 33 44 20AD034 D 25 20 31.2 25.9 34 40.5 54 20AD040 D 30 25 36.7 30.5 40 51 68 20AD052 E 40 30 47.7 39.7 52 60 80 20AD065 E 50 40 59.6 49.6 65 78 104 See page 33 for notes.

Dual Element Time Delay Fuse

Non-time Delay Fuse

Circuit Breaker
(2)

Motor Circuit Protector
(3)

140M Motor Protector with Adjustable Current Range(4)(5)

Min(6) Max(7) Min(6) Max(7) Max(8) Max(8)

15 25 15 45 40

15

20 30 20 60 60

20

30 45 30 80 80

30

40 60 40 120 120 50

50 80 50 125 140 50

60 90 60 150 160 70

80 125 80 225 240 80

90 150 90 250 280 100

Available Catalog Numbers(9)

Minimum Enclosure Volume (in.3)(10)

140M-C2E-C16 140M-D8E-C16 140M-F8E-C16 3441

140M-C2E-C16 140M-D8E-C16 140M-F8E-C16 3441

--

140M-D8E-C25 140M-F8E-C25 5098

--

--

140M-F8E-C32 5098

--

--

140M-F8E-C45 5098

--

--

--

--

--

--

--

--

--

--

--

--

3 3 3 4 15

3

3 6 3 8 15

3

6 6 6 12 15

7

10 10 10 20 20

15

15 15 15 30 30

15

15 20 15 40 40

15

20 30 20 50 50

20

25 45 25 80 80

30

35 60 35 100 100 50

40 70 40 125 125 50

50 90 50 150 150 50

60 110 60 200 200 70

80 125 80 250 250 100

140M-C2E-B16 --

--

3441

140M-C2E-B25 140M-D8E-B25 --

3441

140M-C2E-B40 140M-D8E-B40 --

3441

140M-C2E-B63 140M-D8E-B63 --

3441

140M-C2E-C10 140M-D8E-C10 140M-F8E-C10 3441

140M-C2E-C16 140M-D8E-C16 140M-F8E-C16 3441

140M-C2E-C16 140M-D8E-C16 140M-F8E-C16 3441

--

140M-D8E-C25 140M-F8E-C25 5098

--

--

140M-F8E-C32 5098

--

--

140M-F8E-C45 5098

--

--

140M-F8E-C45 5098

--

--

--

--

--

--

--

--

600 Volt AC Three-phase Input Drive Ratings and Input Protection Devices

Cat.No.

Hp

Input

Rating Ratings

Output Amps

ND HD Amps kVA Cont. 60 s 3 s

Frame(1)

600 Volt AC Input 20AE0P9 A 0.5 0.33 1.3 1.3 0.9 1.1 1.4 20AE1P7 A 1 0.75 1.9 2 1.7 2 2.6 20AE2P7 A 2 1.5 3 3.1 2.7 3.6 4.8 20AE3P9 B 3 2 4.4 4.5 3.9 4.3 5.9 20AE6P1 B 5 3 7.5 7.8 6.1 6.7 9.2 20AE9P0 C 7.5 5 7.7 8 9 9.9 13.5 20AE011 C 10 7.5 9.8 10.1 11 13.5 18 20AE017 D 15 10 15.3 15.9 17 18.7 25.5 20AE022 D 20 15 20 20.8 22 25.5 34 20AE027 D 25 20 24.8 25.7 27 33 44 20AE032 D 30 25 29.4 30.5 32 40.5 54 20AE041 E 40 30 37.6 39.1 41 48 64 20AE052 E 50 40 47.7 49.6 52 61.5 82 See page 33 for notes.

Dual Element Time Delay Fuse

Non-time Delay Fuse

Circuit Breaker
(2)

Motor Circuit Protector
(3)

140M Motor Protector with Adjustable Current Range(4)(5)

Min(6) Max(7) Min(6) Max(7) Max(8) Max(8) Available Catalog Numbers(9)

Minimum Enclosure Volume (in.3)(10)

3 3 3 3.5 15

3

3 6 3 6 15

3

4 6 4 10 15

7

6 8 6 15 15

7

10 12 10 20 20

15

10 20 10 35 35

15

15 20 15 40 40

15

20 35 20 60 60

30

25 45 25 80 80

30

35 60 35 100 100 50

40 70 40 125 125 50

50 90 50 150 150 100

60 110 60 200 200 100

140M-C2E-B16 --

--

3441

140M-C2E-B25 140M-D8E-B25 --

3441

140M-C2E-B40 140M-D8E-B40 �

3441

�

140M-D8E-B63 �

3441

�

140M-D8E-C10 140M-F8E-C10 3441

�

140M-D8E-C10 140M-F8E-C10 3441

�

140M-D8E-C16 140M-F8E-C16 3441

�

�

140M-F8E-C20 5098

�

�

140M-F8E-C25 5098

�

�

140M-F8E-C25 5098

�

�

140M-F8E-C32 5098

�

�

�

�

�

�

�

�

Rockwell Automation Publication 20A-TD001L-EN-P - December 2020

31

208/240 Volt AC Single-phase Input Drive Ratings and Input Protection Devices

Cat.No.

Hp Rating

Input Ratings

Output Amps

ND HD Amps kVA Cont. 60 s 3 s

Frame(1)

208 Volt AC Input 20AB2P2 A 0.5 0.33 2.9 0.6 1.3 1.6 1.9 20AB4P2 A 1 0.75 5.6 1 2.4 2.8 3.7 20AB6P8 B 2 1.5 10 1.8 3.9 5.2 6.9 20AB9P6 B 3 2 14 2.6 5.5 6.1 8.3 20AB015 C 5 3 16 2.9 8.6 9.6 13.3 20AB022 D 7.5 5 23.3 4.2 12.7 13.9 19.0 20AB028 D 10 7.5 29.8 5.4 16.1 19 25.3 20AB042 D 15 10 39.8 7.2 21.5 27.8 37 20AB054 E 20 15 57.5 10.4 31.1 36.2 48.3 20AB070 E 25 20 72.3 13.0 39.1 46.6 62 240 Volt AC Input 20AB2P2 A 0.5 0.33 2.5 0.6 1.1 1.2 1.7 20AB4P2 A 1 0.75 4.8 1 2.1 2.4 3.2 20AB6P8 B 2 1.5 8.7 1.8 3.4 4.5 6 20AB9P6 B 3 2 12.2 2.6 4.8 5.3 7.2 20AB015 C 5 3 13.9 2.9 7.7 8.7 11.6 20AB022 D 7.5 5 19.9 4.2 11 12.2 16.5 20AB028 D 10 7.5 25.7 5.4 14 16.5 22 20AB042 D 15 10 38.7 8.1 21 23.1 31.5 20AB054 E 20 15 49.8 10.4 27 31.5 42 20AB070 E 25 20 64.5 13.4 35 40.5 54 See page 33 for notes.

Dual Element Time Delay Fuse

Non-time Delay Fuse

Circuit Breaker
(2)

Motor Circuit Protector
(3)

140M Motor Protector with Adjustable Current Range(4)(5)

Min(6) Max(7) Min(6) Max(7) Max(8) Max(8) Available Catalog Numbers(9)

Minimum Enclosure Volume (in.3)(10)

6 6 6 10 15

7

10 10 10 17.5 15

7

15 15 15 30 30

15

20 25 20 40 40

30

20 35 20 70 70

30

30 50 30 100 100 30

40 70 40 125 125 50

60 100 60 175 175 70

80 125 80 200 200 100

90 175 90 300 300 100

140M-C2E-B40 140M-D8E-B40 �

3441

140M-C2E-B63 140M-D8E-B63 �

3441

140M-C2E-C10 140M-D8E-C10 140M-F8E-C10 3441

140M-C2E-C16 140M-D8E-C16 140M-F8E-C16 3441

140M-C2E-C20 140M-D8E-C20 140M-F8E-C20 3441

�

140M-D8E-C25 140M-F8E-C25 5098

�

�

140M-F8E-C32 5098

�

�

140M-F8E-C45 5098

�

�

�

�

�

�

�

�

3 4.5 3 8 15

3

6 9 6 15 15

7

15 15 15 25 25

15

20 20 20 35 35

15

20 30 20 60 60

30

25 45 25 80 80

30

35 60 35 110 110 50

50 90 50 150 150 50

60 100 60 200 200 100

90 150 90 275 275 100

140M-C2E-B25 140M-D8E-B25 �

3441

140M-C2E-B63 140M-D8E-B63 �

3441

140M-C2E-C10 140M-D8E-C10 140M-F8E-C10 3441

140M-C2E-C16 140M-D8E-C16 140M-F8E-C16 3441

140M-C2E-C16 140M-D8E-C16 140M-F8E-C16 3441

�

140M-D8E-C25 140M-F8E-C25 5098

�

�

140M-F8E-C32 5098

�

�

140M-F8E-C45 5098

�

�

�

�

�

�

�

�

400/480 Volt AC Single-phase Input Drive Ratings and Input Protection Devices

Cat.No.

Hp Rating

Input Ratings

Output Amps

ND HD Amps kVA Cont. 60 s 3 s

Frame(1)

400 Volt AC Input 20AC1P3 A 0.37 0.25 1.6 0.6 0.7 0.7 1.0 20AC2P1 A 0.75 0.55 2.5 0.9 1.1 1.2 1.6 20AC3P5 A 1.5 1.1 4.3 1.5 1.8 2.3 3 20AC5P0 B 2.2 1.5 6.5 2.3 2.5 2.8 3.8 20AC8P7 B 4 3 11.3 3.9 4.4 5.0 6.6 20AC011 C 5.5 4 11 3.8 5.8 6.5 8.7 20AC015 C 7.5 5.5 15.1 5.2 7.7 8.6 11.6 20AC022 D 11 7.5 21.9 7.6 11 12.1 16.5 20AC030 D 15 11 30.3 10.5 15 16.5 22.5 20AC037 D 18.5 15 35 12.2 18.5 22.5 30 20AC043 D 22 18.5 40.7 14.1 21.5 28 37 20AC060 E 30 22 56.8 19.7 30 33 45 20AC072 E 37 30 68.9 23.9 36 45 60 480 Volt AC Input 20AD1P1 A 0.5 0.33 1.3 0.6 0.6 0.6 0.8 20AD2P1 A 1 0.75 2.4 1 1.1 1.2 1.6

Dual Element Time Delay Fuse

Non-time Delay Fuse

Circuit Breaker
(2)

Motor Circuit Protector
(3)

140M Motor Protector with Adjustable Current Range(4)(5)

Min(6) Max(7) Min(6) Max(7) Max(8) Max(8) Available Catalog Numbers(9)

Minimum Enclosure Volume (in.3)(10)

3 3 3 5 15

3

46

4 8 15

7

6 6 6 12 15

7

10 10 10 20 20

15

15 17.5 15 30 30

15

15 25 15 45 40

15

20 30 20 60 60

20

30 45 30 80 80

30

40 60 40 120 120 50

50 80 50 125 140 50

60 90 60 150 160 70

80 125 80 225 240 80

90 150 90 250 280 100

140M-C2E-B16 �

�

3441

140M-C2E-B25 140M-D8E-B25 �

3441

140M-C2E-B63 140M-D8E-B63 �

3441

140M-C2E-C10 140M-D8E-C10 140M-F8E-C10 3441

140M-C2E-C16 140M-D8E-C16 140M-F8E-C16 3441

140M-C2E-C16 140M-D8E-C16 140M-F8E-C16 3441

140M-C2E-C16 140M-D8E-C16 140M-F8E-C16 3441

�

140M-D8E-C25 140M-F8E-C25 5098

�

�

140M-F8E-C32 5098

�

�

140M-F8E-C45 5098

�

�

�

�

�

�

�

�

�

�

�

�

3 3 3 4 15

3

140M-C2E-B16 �

�

3441

3 6 3 8 15

3

140M-C2E-B25 140M-D8E-B25 �

3441

32

Rockwell Automation Publication 20A-TD001L-EN-P - December 2020

400/480 Volt AC Single-phase Input Drive Ratings and Input Protection Devices (Continued)

Cat.No.

Hp Rating
ND HD

Frame(1)

20AD3P4 A 2 1.5 20AD5P0 B 3 2 20AD8P0 B 5 3 20AD011 C 7.5 5 20AD014 C 10 7.5 20AD022 D 15 10 20AD027 D 20 15 20AD034 D 25 20 20AD040 D 30 25 20AD052 E 40 30 20AD065 E 50 40 See page 33 for notes.

Input Ratings

Output Amps

Amps kVA Cont. 60 s 3 s
3.8 1.6 1.7 2.3 3 5.6 2.4 2.5 2.6 3.8 9.8 4.2 4 4.4 6 9.5 4 5.5 6.1 8.3 12.5 5.2 7 8.3 11 19.9 8.3 11 12.1 16.5 24.8 10.3 13.5 16.5 22 31.2 13 17 20.3 27 36.7 19.9 20 25.5 34 47.7 12.8 26 30 40 59.6 24.8 32.5 39 52

Dual Element Time Delay Fuse

Non-time Delay Fuse

Circuit Breaker
(2)

Motor Circuit Protector
(3)

140M Motor Protector with Adjustable Current Range(4)(5)

Min(6) Max (7) Min(6) Max(7) Max(8) Max(8)

6 6 6 12 15

7

10 10 10 20 20

15

15 15 15 30 30

15

15 20 15 40 40

15

20 30 20 50 50 20

25 45 25 80 80

30

35 60 35 100 100 50

40 70 40 125 125 50

50 90 50 150 150 50

60 110 60 200 200 70

80 125 80 250 250 100

Available Catalog Numbers(9)

Minimum Enclosure Volume (in.3)(10)

140M-C2E-B40 140M-D8E-B40 �

3441

140M-C2E-B63 140M-D8E-B63 �

3441

140M-C2E-C10 140M-D8E-C10 140M-F8E-C10 3441

140M-C2E-C16 140M-D8E-C16 140M-F8E-C16 3441

140M-C2E-C16 140M-D8E-C16 140M-F8E-C16 3441

�

140M-D8E-C25 140M-F8E-C25 5098

�

�

140M-F8E-C32 5098

�

�

140M-F8E-C45 5098

�

�

140M-F8E-C45 5098

�

�

�

�

�

�

�

�

600 Volt AC Single-phase Input Drive Ratings and Input Protection Devices

Cat. No.

Hp Rating

Input Ratings

Output Amps

ND HD Amps kVA Cont. 60 s 3 s

Frame(1)

600 Volt AC Input 20AE0P9 A 0.5 0.33 1.3 0.7 0.5 0.6 0.7 20AE1P7 A 1 0.75 1.9 1 0.9 1 1.3 20AE2P7 A 2 1.5 3 1.6 1.4 1.8 2.4 20AE3P9 B 3 2 4.4 2.3 2 2.2 3 20AE6P1 B 5 3 7.5 3.9 3.1 3.4 4.6 20AE9P0 C 7.5 5 7.7 4 4.5 5 6.8 20AE011 C 10 7.5 9.8 5.1 5.5 6.8 9 20AE017 D 15 10 15.3 8 8.5 9.4 12.8 20AE022 D 20 15 20 10.4 11 12.8 17 20AE027 D 25 20 24.8 12.9 13.5 16.5 22 20AE032 D 30 25 29.4 15.3 16 20.3 27 20AE041 E 40 30 37.6 19.6 20.5 24 32 20AE052 E 50 40 47.7 24.8 26 30.8 41

Dual Element Time Delay Fuse

Non-time Delay Fuse

Circuit Breaker
(2)

Motor Circuit Protector
(3)

140M Motor Protector with Adjustable Current Range(4)(5)

Min(6) Max(7) Min(6) Max(7) Max(8) Max(8) Available Catalog Numbers(9)

Minimum Enclosure Volume (in.3)(10)

3 3 3 3.5 15

3

3 6 3 6 15

3

4 6 4 10 15

7

6 8 6 15 15

7

10 12 10 20 20

15

10 20 10 35 35

15

15 20 15 40 40

15

20 35 20 60 60

30

25 45 25 80 80

30

35 60 35 100 100 50

40 70 40 125 125 50

50 90 50 150 150 100

60 110 60 200 200 100

140M-C2E-B16 �

�

3441

140M-C2E-B25 140M-D8E-B25 �

3441

140M-C2E-B40 140M-D8E-B40 �

3441

�

140M-D8E-B63 �

3441

�

140M-D8E-C10 140M-F8E-C10 3441

�

140M-D8E-C10 140M-F8E-C10 3441

�

140M-D8E-C16 140M-F8E-C16 3441

�

�

140M-F8E-C20 5098

�

�

140M-F8E-C25 5098

�

�

140M-F8E-C25 5098

�

�

140M-F8E-C32 5098

�

�

�

�

�

�

�

�

(1) For IP 66 (NEMA / UL Type 4X/12) enclosures, drives listed as Frame A increase to Frame B and drives listed as Frame C increase to Frame D. (2) Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA. Ratings that are shown are maximum. (3) Motor Circuit Protector - instantaneous trip circuit breaker. For US NEC, minimum size is 125% of motor FLA. Ratings that are shown are maximum. (4) Bulletin 140M with adjustable current range must have the current trip set to the minimum range that the device does not trip. (5) Manual Self-Protected (Type E) Combination Motor Controller, UL Listed for 208 Wye or Delta, 240 Wye or Delta, 480Y/277 or 600Y/347. Not UL Listed for use on 480V or 600V
Delta/Delta, corner ground, or high-resistance ground systems. (6) Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping. (7) Maximum protection device size is the highest rated device that supplies drive protection. For US NEC, minimum size is 125% of motor FLA. Ratings that are shown are
maximum. (8) Maximum allowable rating by US NEC. Exact size must be chosen for each installation. (9) The AIC ratings of the Bulletin 140M Motor Protector Circuit Breakers can vary. See Bulletin 140M Motor Protection Circuit Breakers Application ratings. (10) When using a Manual Self-Protected (Type E) Combination Motor Controller, the drive must be installed in a ventilated or non-ventilated enclosure with the minimum volume that
is specified in this column. Application-specific thermal considerations can require a larger enclosure.

Rockwell Automation Publication 20A-TD001L-EN-P - December 2020

33

Mounting

This section includes information for mounting the drives.

Maximum Surrounding Air Temperature
Enclosure Rating Open Type, IP 20, NEMA / UL Type 1 and flange mount IP 66, NEMA / UL Type 4X/12 IP 54, NEMA / UL Type 12

Temperature Range 0...50 �C (32...122 �F) 0...40 �C (32...104 �F) 0...40 �C (32...104 �F)

IMPORTANT Some drives are equipped with an adhesive label on the top of the chassis. Removing the adhesive label from the drive changes the enclosure rating from NEMA / UL Type 1 Enclosed to Type Open.

Minimum Mounting Clearances
Specified vertical clearance requirements are intended to be from the drive to the closest object that can restrict airflow through the drive heatsink and chassis. The drive must be mounted in a vertical orientation as shown, and must make full contact with the mounting surface. Do not use standoffs or spacers. In addition, inlet air temperature must not exceed the product specification.

76.2 mm (3.0 in.)

76.2 mm (3.0 in.)

Clearances apply to all PowerFlex 70 Drives: � Panel Mount � Flange Mount � NEMA Type 4X/12

PowerFlex 70 Frames Output Power

Output Power

kW ND (HD)

Hp ND (HD)

0.37 (0.25) 0.75 (0.55) 1.5 (1.1) 2.2 (1.5) 4 (3) 5.5 (4) 7.5 (5.5) 11 (7.5) 15 (11) 18.5 (15) 22 (18.5) 30 (22) 37 (30)

0.5 (0.33) 1 (0.75) 2 (1.5) 3 (2) 5 (3) 7.5 (5) 10 (7.5) 15 (10) 20 (15) 25 (20) 30 (25) 40 (30) 50 (40)

Frame Size

208...240V AC Input

Not Filtered Filtered

A

B

A

B

B

B

B

B

�

C

�

D

�

D

�

D

�

E

�

E

�

�

�

�

�

�

76.2 mm (3.0 in.)

76.2 mm (3.0 in.)

IP66 (4X/12) B B B B D D D D E E � � �

400...480V AC Input

Not Filtered Filtered

A

B

A

B

A

B

B

B

B

B

�

C

�

C

�

D

�

D

�

D

�

D

�

E

�

E

IP66 (4X/12) B B B B B D D D D D D E E

600V AC Input

Not Filtered Filtered

A

�

A

�

A

�

B

�

B

�

C

�

C

�

D

�

D

�

�

�

�

�

�

�

�

�

34

Rockwell Automation Publication 20A-TD001L-EN-P - December 2020

Approximate Dimensions and Weights

This section provides the approximate dimensions for the drives.

Frames A...E

\
IP20/66 (NEMA / UL Type 1/4X/12)

A

D

C

Flange Mount

A

C

E

B

B

F
Frame Dimensions, mm (in.)

D

E

Frame Size
A B C D E(1)
B D E(1)(2)
A B C D E

Dimension

A

B

IP20, NEMA / UL Type 1

122.4 (4.82) 225.7 (8.89)

171.7 (6.76) 234.6 (9.24)

185.0 (7.28) 300.0 (11.81)

219.9 (8.66) 350.0 (13.78)

280.3 (11.04) 555.8 (21.88)

IP66, NEMA / UL Type 4X/12

171.7 (6.76) 219.9 (8.66)

239.8 (9.44) 350.0 (13.78)

280.3 (11.04) 555.8 (21.88)

Flange Mount 156.0 (6.14) 225.8 (8.89)

205.2 (8.08) 234.6 (9.24) 219.0 (8.62) 300.0 (11.81)

248.4 (9.78) 350.0 (13.78) 280.3 (11.04) 555.8 (21.88)

C
179.8 (7.08) 179.8 (7.08) 179.8 (7.08) 179.8 (7.08) 207.1 (8.15)
203.3 (8.00) 210.7 (8.29) 219.8 (8.65)
178.6 (7.03) 178.6 (7.03) 178.6 (7.03) 178.6 (7.03) 207.1 (8.15)

D
94.2 (3.71) 122.7 (4.83) 137.6 (5.42) 169.0 (6.65) 200.0 (7.87)
122.7 (4.83) 169.0 (6.65) 200.0 (7.87)
123.0 (4.84) 123.0 (4.84) 123.0 (4.84) 123.0 (4.84) 117.2 (4.61)

E
211.6 (8.33) 220.2 (8.67) 285.6 (11.25) 335.6 (13.21) 491.0 (19.33)
220.2 (8.67) 335.6 (13.21) 491.0 (19.33)
55.6 (2.19) 55.6 (2.19) 55.6 (2.19) 55.6 (2.19) 89.9 (3.54)

(1) IP20 and IP66 frame E drives are manufactured with a flange-like heatsink with mounting holes. (2) Frame E is also available in IP54 NEMA/UL Type 12 as a wall/machine mount. (3) Weights include HIM and standard I/O.

F
5.8 (0.23) 5.8 (0.23) 5.8 (0.23) 5.8 (0.23) 6.9 (0.27)
5.8 (0.23) 5.8 (0.23) 6.9 (0.27)
� � � � �

Weight (3) kg (lb)
2.71 (6.0) 3.60 (7.9) 6.89 (15.2) 9.25 (20.4) 18.60 (41.0)(1)
3.61 (8.0) 9.13 (20.1) 18.60 (41.0)(1)
2.71 (6.0) 3.60 (7.9) 6.89 (15.2) 9.25 (20.4) 18.60 (41.0)

Rockwell Automation Publication 20A-TD001L-EN-P - December 2020

35

IP20, NEMA / UL Type 1 Bottom View Dimensions, mm (in.)

Frame A(1)

34.5 (1.36) 23.9 (0.94)

86.4 (3.40)

22.2 (0.87) Dia. 4 Places

Frame B (1)

43.4 (1.71) 32.8 (1.29)

127.5 (5.02)

22.2 (0.87) Dia. 5 Places

155.2 (6.11)
135.9 (5.35)
129.8 (5.11)
102.4 (4.03)

42.7 (1.68)

55.4 (2.18) 79.3 (3.12) 85.1 (3.35)

Frame C

47.7 (1.88)

112.3 (4.42) 58.4 (2.30)

163.7 (6.45)
22.2 (0.87) Dia. 4 Places

155.2 (6.11)
136.7 (5.38)
126.2 (4.97)
101.6 (4.00)

55.6 (2.19)

75.5 (2.97) 85.7 (3.37) 113.5 (4.47) 123.8 (4.87)

Frame D

22.2 (0.87) Dia. 2 Places

149.7 (5.89) 69.3 (2.73) 58.6 (2.31)

163.7 (6.45)
28.5 (1.12) Dia. 2 Places

Frame E(2)

108.0 (4.25)

210.0 (8.27)

155.2 (6.11)
129.3 (5.09)
101.3 (3.99)

163.5 (6.44)

155.2 (6.11)
134.7 (5.30)
103.2 (4.06)

36.1 (1.42)

56.1 (2.21) 75.2 (2.96) 94.2 (3.71)

(1) Fan existence is dependent on drive rating and package style. (2) Flange style heatsink on NEMA1.

37.5 (1.48)

64.0 (2.52) 93.0 (3.66) 121.0 (4.76)

164.1 (6.46)

181.5 (7.14)
165.0 (6.49)
139.9 (5.50)
126.9 (4.99)

108.0 (4.25) 159.0 (6.26) 210.0 (8.27)

22.2 (0.87)

43.7 (1.72)

IP 66 (NEMA / UL Type 4X/12) Bottom View Dimensions, mm (in.)

Frame B (1)

28.3 (1.11)
22.1 (0.87)

Frame D (1)

28.3 (1.11)

22.1 (0.87)

Frame E (1)(2)

22.5 (0.89)
44.5 (1.75)

138.2 (5.44)
99.6 (3.92)

140.5 (5.53)
138.6 (5.46)
102.9 (4.05)

163.4 (6.43)
139.9 (5.51)
124.9 (4.92)

55.2 (2.17)

77.3 (3.04) 99.6 (3.92) 115.9 (4.56)

31.0 (1.22) 49.1 (1.93)

75.5 (2.97) 102.0 (4.02) 120.1 (4.73)

108.2 (4.26) 157.7 (6.21) 165.7 (6.52) 207.7 (8.18)

(1) DPI Port 2 is not accessible from outside of the drive standard. A service connection board (catalog number SK-M9-SCB1) is required.

(2) Frame E is also available in IP54 NEMA/UL Type 12 as a wall/machine mount.

36

Rockwell Automation Publication 20A-TD001L-EN-P - December 2020

Flange Mount Bottom View Dimensions, mm (in.)

Frame A

51.3 (2.02) 40.7 (1.60)

103.2 (4.06)

22.2 (0.87) Dia. 4 Places

95.9 (3.78)
76.6 (3.02)
70.5 (2.78)
43.2 (1.70)

104.4 (4.11)

59.6 (2.35) 72.4 (2.85) 96.1 (3.78) 101.9 (4.01)

Frame B

60.3 (2.37) 49.7 (1.96)

144.4 (5.69)

95.0 (3.74)
76.6 (3.02)
65.9 (2.59)
41.4 (1.63)

22.2 (0.87) Dia. 5 Places
103.5 (4.07)

Frame C

64.7 (2.55)

129.3 (5.09) 75.4 (2.97)

94.6 (3.72)
68.7 (2.70)
40.6 (1.60)

22.2 (0.87) Dia. 4 Places
102.9 (4.05)

53.1 (2.09)

73.0 (2.87) 92.2 (3.63) 111.2 (4.38)
Frame D

22.2 (0.87) Dia. 2 Places

164.1 (6.46) 83.7 (3.30) 73.0 (2.87)

94.6 (3.27)
74.1 (2.92)
42.3 (1.67)

28.5 (1.12) Dia. 2 Places
103.5 (4.07)

70.9 (2.79) 92.4 (3.64) 102.7 (4.04) 130.5 (5.14) 140.6 (5.54)
94.4 (3.72)
77.9 (3.07)
52.8 (2.08)
39.8 (1.57)

Frame E
108.0 (4.25)

51.9 (2.04)

78.3 (3.08) 107.3 (4.22) 135.5 (5.33)

210.0 (8.27)

22.2 (0.87)

43.7 (1.72)

108.0 (4.25) 159.0 (6.26) 210.0 (8.27)

Rockwell Automation Publication 20A-TD001L-EN-P - December 2020

37

Cutout Dimensions, mm (in.)

Frame A

6,9 (0.27)

156,0 (6.14)
70,7 (2.78)

140,7 (5.54)

127,0 (5.00)

197.9 (7.80)

225,8 (8.89) 210,6 (8.29)
105,3 (4.15)

8x: �3,5 (�0.14)

4x: 3,0R (0.12R)

5.0 (0.20)

58,8 (2.31)

Frame B

6,9 (0.27)

205,2 (8.08)
95,0 (3.74)

190,0 (7.48)

176,3 (6.94)

205,5 (8.09)

234,6 219,3 (9.24) (8.63)
109,7 (4.32)

8x: �3,5 (�0.14)

4x: 3,0R (0.12R)

6,9 (0.27)

58,8 (2.31)

Frame C

6,3 (0.25)

219,0 (8.62)
101,0 (3.98)

202,0 (7.95)

189,4 (7.46)
272,3 (10.72)

12x: �3,5 (�0.14)

4x: 3,0R (0.12R)

300,0 (11.81)
283,0 (11.14)
241,5 (9.51)
141,5 (5.57)
41,5 (1.63)
5,1 (0.20)

58,8 (2.31)

Frame D

4,5 (0.18)

231,4 (9.11)

40,7 (1.60)

115,7 (4.56)

248,4 (9.78)
190,7 (7.51)

222,4 (8.76) 321,4 (12.65)
14x: �3,5 (�0.14)

4x: 3,0R (0.12R)

350,0 (13.78)
333,0 (13.11)
271,5 (10.69)
201,5 (7.93)
131,5 (5.18)
61,5 (2.42)
4,5 (0.18)

58,8 (2.31)

38

Rockwell Automation Publication 20A-TD001L-EN-P - December 2020

Cutout Dimensions, mm (in.) (continued)
Frame E

6.0 (0.24)

56.2 (2.21)

262.4 (10.33)
131.2 (5.16)

280.3 (11.04)
206.2 (8.12)

250.4 (9.86) 525.8 (20.70)
20x: �3.5 (�0.14)

555.8 (21.88)
493.9 (19.44)
418.9 (16.49)
343.9 (13.54)
268.9 (10.59)
193.9 (7.63)
118.9 (4.68)
43.9 (1.73)
6.0 (0.24)

87.1 (3.43)

Rockwell Automation Publication 20A-TD001L-EN-P - December 2020

39

PowerFlex 70 Configured Drives
You can use the PowerFlex 70 packaged drives program to create drive packages that are based on your specific needs. This program enhances standalone drive functionality through additional control, power, and packaging options that are ideal for original equipment manufacturers (OEM) and customers with special installation needs.
Catalog-configured Drives Program
You can use the catalog configured drives program to create drive packages that are based on your specific needs. You can specify a complete drive package by assembling a single catalog number string that includes a base drive and all required options. Packaging is available for 480V requirements in NEMA Type 1 (IP20), NEMA 4/12 (IP65) indoor, and NEMA 3/4 (IP65) outdoor ratings. Focused on higher volume, repeat business, the standard designs provide consistent manufacturing and minimizes customer resources by reducing engineering, manufacturing, and installation time.

NEMA Type 1 NEMA Type 4/12 Indoor NEMA Type 3/4 Outdoor
� Enhanced control � Flange mount drive � Welded construction � 480V rating

All Enclosure Types
� Drive input protection options � Input/Output contactors � Bypass options � Input/Output line reactor options � 115V control power options � Control interface and feedback
options � Human interface modules � Motor interface options � Operator devices � Drawing and test options

Approximate Dimensions
W D
H
Figure 1

W

D

D

H

NEMA Type 1 (Ventilated)
Figure 2

NEMA Type 4

W D
H
Figure 3

40

Rockwell Automation Publication 20A-TD001L-EN-P - December 2020

Maximum Enclosure Dimensions

Ratings

Enclosure Style for Flange Mounted Drives

ND Hp

Drive Frame HD Hp Size

NEMA Type 1, Option Code A

Power

Flex 70 B0, C1, C5, S1,

Flange S9...S13, S16,

Drive P1...P3, Drive Cat. No. Mounted

All Options

Options and All

HIMs

NEMA Type 4 Indoor, Option Code D NEMA Type 12 Indoor, Option Code G

B0, C1, C5, S1,

S9...S13, S16,

P1...P3, Drive Mounted

All Options Less Line Reactor

All Options

Options and All

NEMA 4 HIMs

Figure Style Figure Style Figure Style Figure Style Figure Style

480V AC, Three-phase Drives

0.5 0.33 A

D1P1 1

1

2

3

1

1

2

3

2

3

1.0 0.75 A

D2P1 1

1

2

3

1

1

2

3

2

3

2.0 1.5 A

D3P4 1

1

2

3

1

1

2

3

2

3

3.0 2.0 B

D5P0 1

1

231

1

2324

5.0 3.0 B

D8P0 1

1

231

1

2324

7.5 5.0 C

D011 1

1

231

1

2324

10 7.5 C

D014 1

1

231

1

2324

15 10 D

D022 1

1

241

1

2425

20 15 D 25 20 D 30 25 D 40 30 E 50 40 E

D027 1 D034 1 D040 1 D052 1 D065 1

1

241

1

24

1

1

241

2261

2261

1

2

4

2

5

1

2

4

2

5

1

2

4

2

5

22627

22627

(1) Figure 2, Style 5, when one line reactor is selected. Figure 3, Style 8, when two line reactors are selected

NEMA Type 3/4, Option Code E

B0, C1, C5, S1, S9...S13, S16, P1...P3, Drive Mounted Options

All Options Less Line Reactor

Figure Style Figure Style

1

1

1

1

1

1

1

1

1

1

1

1

1

1

16

1

1

1

1

1

1

1

1

2

1

2

23 23 23 23 23 23 23
24 24 25 25 26 26

All Options

Figure Style

2 2 2 2 2 2 2 or 3(1) 2 or 3(1) 3 3 3 3 3

3 3 4 5 5 5 5 or 8(1) 5 or 8(1) 8 8 8 9 9

Enclosure Dimensions

Figure Style Enclosure Rating

Option Code (Position d)

1

1

NEMA 1

A

1

2 NEMA 1

A

2

3 NEMA 1

A

2

4 NEMA 1

A

2

6 NEMA 1

A

1

1

NEMA 4/12 Indoor, NEMA 4 Outdoor D, G, E

1

2 NEMA 4/12 Indoor, NEMA 4 Outdoor D, G, E

2

3 NEMA 4/12 Indoor, NEMA 4 Outdoor D, G, E

2

4 NEMA 4/12 Indoor, NEMA 4 Outdoor D, G, E

2

5 NEMA 4/12 Indoor, NEMA 4 Outdoor D, G, E

2

6 NEMA 4/12 Indoor, NEMA 4 Outdoor D, G, E

2

7

NEMA 4/12 Indoor, NEMA 4 Outdoor D, G, E

3

8 NEMA 4/12 Indoor, NEMA 4 Outdoor D, G, E

3

9 NEMA 4/12 Indoor, NEMA 4 Outdoor D, G, E

(1) Depth includes 6.35 mm (2.5 in) for operator handle, if ordered.

Dimensions(1) H x W x D (mm) 812.8 x 330.2 x 484.1 1,270.0 x 406.4 x 484.1 812.8 x 609.6 x 484.1 965.2 x 609.6 x 484.1 1,270.0 x 762.0 x 484.1 812.8 x 330.2 x 484.1 1,270.0 x 406.4 x 484.1 812.8 x 609.6 x 484.1 965.2 x 609.6 x 484.1 1,270.0 x 609.6 x 484.1 1,270.0 x 762.0 x 484.1 1,270.0 x 914.4 x 484.1 812.8 x 831.9 x 484.1 1,270.0 x 984.3 x 484.1

H x W x D (in.) 32 x 13 x 19.06 50 x 16 x 19.06 32 x 24 x 19.06 38 x 24 x 19.06 50 x 30 x 19.06 32 x 13 x 19.06 50 x 16 x 19.06 32 x 24 x 19.06 38 x 24 x 19.06 50 x 24 x 19.06 50 x 30 x 19.06 50 x 36 x 19.06 50 x 32.75 x 19.06 50 x 38.75 x 19.06

Rockwell Automation Publication 20A-TD001L-EN-P - December 2020

41

Standard Drive Certifications and Specifications

The tables in this section provide certification information and technical specifications.

Certifications(1)

Certifications(2) Description

Frames

A...E

A...E

240...480V 600V

ABS

American Bureau of Shipping MA Certificate 08-HS303172A-3-PDA for auxiliary services on AB Classed vessels and offshore platforms

X

X

RCM

Certified by Rockwell Automation to be in conformity with the requirements of the applicable Australian legislation and standards that are referenced here: IEC 61800-3

X

c-UL-us

Listed to UL508C and CAN/CSA C22.2 No. 274-13 Configured drives can be listed to UL508A

X

X

Certified by Rockwell Automation to be in conformity with the essential requirements of the applicable European Directives. The following standards have been applied:

--

--

CE

2014/35/EU (Low Voltage Directive) EN 61800-5-1 Electronic Equipment for Use in Power Installations

X

X

2014/30/EU (EMC Directive) EN 61800-3 Adjustable speed electrical power drive systems - Part 3: EMC requirements and specific test methods

X

EAC

Low Voltage TR CU 004/2011 EMC TR CU 020/2011

X

X

EPRI/SEMIF 47 EPRI Quality Star Certificates SEMIF47.116 for SEMI F47 compliance, only 480V units tested

X

T�V Rheinland Certificate 01/205/0665.01/15

Functional Safety Safe Torque Off (STO) complies with the requirements of the relevant standards (Cat. 3 / PLd according to EN ISO 13849-1,

X

SIL CL 2 according to EN ISO 13849-1, and SIL 2 according to EN 62061 / IEC 61508.

Korean KC Registration

KCC-REM-RAA-20A See the certificate of registration for specific drive catalog numbers that have this certification.(2)

X

X

Lloyd's Register Lloyd's Register Type Approval Certificate 08/60014 (E1) (marine certification)

X

Plenum Rating

Listed to UL508C Suitable for installation in a compartment handling conditioned air. (3)

Trentec

Tested by Trentec to be compliant with AC156 Acceptance Criteria for Seismic Qualification Testing of Nonstructural Components and 2003 International Building Code for worst-case seismic level for USA excluding site class F

X

X

IEC 61800-2 � Adjustable speed electrical power drive systems - Part 2: General requirements - Rating specifications for low voltage adjustable frequency AC power drive systems

X

X

Designed to Meet NEMA ICS 7.1 � Safety Standards for Construction and Guide for Selection, Installation, and Operation of Adjustable Speed

Applicable

Drive Systems

X

X

Requirements

NFPA 70 � US National Electric Code

X

X

NSF � Type 4X enclosure NSF Listed to meet Criteria C2 for splash and non-food zones

X

X

(1) See the Rockwell Automation Product Certification page for current certifications, http://www.rockwellautomation.com/global/certification/overview.page (2) See the product certifications website, http://www.rockwellautomation.com/products/certification/ for declarations of conformity, certificates, and other certification details. (3) Flange mount enclosure, Frames A...D only.

42

Rockwell Automation Publication 20A-TD001L-EN-P - December 2020

Specifications

Category Protection
Environment

Specification

Drive

200... 208V

240V

380/400 480V

600V

690V

AC input overvoltage trip

247V AC 285V AC 475V AC 570V AC 690V AC

AC input undervoltage trip

120V AC 138V AC 233V AC 280V AC 345V AC

Bus overvoltage trip

405V DC 405V DC 810VDC 810V DC 1013V DC

Bus undervoltage output shutoff

153V DC 153V DC 305V DC 437V DC 437V DC

Bus undervoltage fault level

160V DC 160V DC 300VDC 300V DC 375V DC

Bus voltage nom

281V DC 324V DC 540VDC 648V DC 810V DC

All Drives

Heatsink thermistor

Monitored by microprocessor overtemp trip

Drive overcurrent trip: � Software current limit � Hardware current limit � Instantaneous current limit

� 20...160% of rated current � 200% of rated current (typical) � 220...300% of rated current (dependent on drive rating)

Line transients

Up to 6000 volts peaks per IEEE C62.41-1991

Control logic noise immunity

Showering arc transients up to 1500V peak

Power ride-through

15 ms at full load

Logic control ride-through

0.5 s min, 2 s typ

Ground fault trip

Phase-to-ground on drive output

Short circuit trip

Phase-to-phase on drive output

Altitude

1000 m (3300 ft) max without derating

Maximum surrounding air temperature without derating: � IP20, NEMA / UL Type 1 � flange mount � IP66, NEMA / UL Type 4X/12 (indoor)

� 0...50 �C (32...122 �F) � 0...50 �C (32...122 �F) � 0...40 �C (32...104 �F)

Cooling fan operation: � Frames A and C � Frames B, D, and E

� Fan operates when power is applied. � Fan operates when power is applied and in Run condition.

Storage temperature (all const.)

�40...+70 �C (�40...+158 �F)

Atmosphere

Important: Drive must not be installed in an area where the ambient atmosphere contains volatile or corrosive gas, vapors, or dust. If the drive is not going to be installed immediately, store the drive where it is not exposed to a corrosive atmosphere.

Relative humidity

5...95% non-condensing

Shock

15 g peak for 11 ms duration (1.0 ms)

Vibration

0.152 mm (0.006 in.) displacement, 1 g peak

Pollution degree of the surrounding

environment:

� Pollution degree 1 and 2

� All enclosures are acceptable for pollution degree 1 and 2.

� Pollution degree 3 and 4

� An enclosure that meets or exceeds IP54, NEMA / UL Type 12, is required

See Pollution Degree Ratings According to for pollution degree 3 and 4.

EN 61800-5-1 for descriptions of pollution

degree rating.

Pollution Degree Ratings According to EN 61800-5-1

Pollution Degree

Description

One of the following is true:

1

� No pollution occurs.

� Only dry non-conductive pollution occurs, and has no influence.

2

Normally only non-conductive pollution occurs. Occasionally a temporary conductivity, caused by condensation, is expected when the drive is out of operation.

At least one of the following is true:

3

� Conductive pollution occurs.

� Dry non-conductive pollution occurs and becomes conductive due to condensation.

4

The pollution generates persistent conductivity that is caused, for example, by conductive dust, rain, or snow.

Rockwell Automation Publication 20A-TD001L-EN-P - December 2020

43

Specifications

Category Electrical
Control

Specification

Voltage tolerance

�10% of minimum, +10% of maximum. See the PowerFlex 70 Adjustable Frequency AC Drives User Manual, publication 20A-UM001, for Full Power and Operating Range.

Input frequency tolerance

47...63 Hz

Input phases Three-phase input provides full rating for all drives. Single-phase operation provides 50% of rated current.

Displacement power factor (all 0.98 across speed range. drives)

Efficiency

97.5% at rated amps, line volts nom.

Short circuit rating max

200,000 amps symmetrical.

Short circuit current rating max (by using the recommended fuse or circuit breaker type)

Maximum short circuit current rating to match specified fuse/circuit breaker capability.

Drive to motor power ratio: � Minimum � Maximum

� Recommended not less than 1:2 ratio � Recommended not greater than 2:1 ratio

Method

Sine coded PWM with programmable carrier frequency. Ratings apply to all drives.

Carrier frequency

2, 3, 4, 5, 6, 7, 8, 9, and 10 kHz Standard.
2, 4, 8, and 12 kHz E C . Drive rating based on 4 kHz.

Output voltage range

0 to rated motor voltage

Output frequency range

0...400 Hz Standard. 0...500 Hz

EC .

Frequency
accuracy: � Digital input � Within 0.01% of set output frequency. � Analog input � Within 0.4% of maximum output frequency.

with slip compensation (Volts per Hertz mode) 0.5% of base speed across 40:1 speed range 40:1 operating range 10 rad/sec bandwidth

with slip compensation (Sensorless Vector mode)

Frequency

0.5% of base speed across 80:1 speed range

control - speed 80:1 operating range

regulation

20 rad/sec bandwidth

with feedback (Sensorless Vector mode) E C 0.001% of base speed across 40:1 speed range 0.1% of base speed across 80:1 speed range 80:1 operating range 20 rad/sec bandwidth

without feedback (Vector Control mode) E C 0.1% of base speed across 120:1 speed range 120:1 operating range
Speed control - 30 rad/sec bandwidth speed regulation with feedback (Vector Control mode) E C
0.001% of base speed across 120:1 speed range 1000:1 operating range 125 rad/sec bandwidth

Torque regulation
Selectable motor control

without feedback +/-10% E C with feedback +/-5% E C
Sensorless Vector with full tuning. Standard VHz with full custom capability and vector control.

Stop modes Multiple programmable stop modes including - Ramp, Coast, DC-Brake, Fast Brake, Ramp to Hold, and S-curve.

Accel/Decel Two independently programmable accel and decel times. Each time can be programmed from 0...3600 seconds in 0.1 second increments

Intermittent overload

110% Overload capability for up to 1 minute 150% Overload capability for up to 3 seconds

Current limit Proactive current limit programmable from 20...160% of rated output current.

capability

Independently programmable proportional and integral gain.

Motor overload Class 10 motor overload protection according to NEC article 430 and motor over-temperature protection according to NEC article 430.126 (A)(2). UL 508C File

protection

E59272.

44

Rockwell Automation Publication 20A-TD001L-EN-P - December 2020

Specifications (Continued)

Category Encoder

Specification

Type

Incremental, dual channel

Supply

5V/12V Configurable �5%

Quadrature 90� �27�

Duty cycle

50% +10%

Requirements(1)

Encoders must be line driver type, quadrature (dual-channel), or pulse (single-channel), single-ended or differential and capable of supplying 10 mA min per channel. The encoder interface board accepts 5V or 12V DC square-wave with a high state voltage of 3.5V DC min (5V mode), and 7.0V DC min (12V mode). Low state voltage max is 1V DC (for both 5V and 12V modes). Input frequency max is 250 kHz.

(1) Drive is not CE EMC certified when the encoder interface option is installed.

Watts Loss (rated load, speed, and PWM) (1)

Voltage 208V 240V 400V 480V 600V

ND Hp
0.5 1.0 2.0 3.0 5.0 7.5 10 15 20 25
0.5 1.0 2.0 3.0 5.0 7.5 10 15 20 25
0.37 0.75 1.5 2.2 4.0 5.5 7.5 11 15 18.5 22 30 37
0.5 1.0 2.0 3.0 5.0 7.5 10 15 20 25 30 40 50
0.5 1.0 2.0 3.0 5.0 7.5 10 15 20 25 30 40 50

External Watts
12.2 30.7 44.6 67.3 141.3 205.7 270.4 385.6 494.6 650.7
12.2 30.7 44.6 67.3 141.3 205.7 270.4 385.6 494.6 650.7
11.5 27.8 43.6 64.6 99.5 140.0 193.3 305.4 432.9 363.8 396.8 500.8 632.0
11.5 27.8 43.6 64.6 99.5 140.0 193.3 305.4 432.9 363.8 396.8 500.8 632.0
11.5 27.8 43.6 64.6 99.5 140.0 193.3 305.4 432.9 281.4 311.9 389.9 501.4

Internal Watts
19.2 20.5 22.6 25.4 33.2 34.2 48.1 40.3 44.9 51.6
19.2 20.5 22.6 25.4 33.2 34.2 48.1 40.3 44.9 51.6
17.9 19.5 21.6 24.0 28.2 27.8 32.0 34.2 42.9 40.5 41.5 50.0 57.7
17.9 19.5 21.6 24.0 28.2 27.8 32.0 34.2 42.9 40.5 41.5 50.0 57.7
17.9 19.5 21.6 24.0 28.2 27.8 32.0 34.2 42.9 42.4 43.4 51.8 59.9

Total Watts Loss
31.4 51.2 67.2 92.7 174.5 239.9 318.5 425.9 539.5 702.3
31.4 51.2 67.2 92.7 174.5 239.9 318.5 425.9 539.5 702.3
29.4 47.3 65.2 88.6 127.7 167.8 225.3 339.6 475.8 404.3 438.3 550.8 689.7
29.4 47.3 65.2 88.6 127.7 167.8 225.3 339.6 475.8 404.3 438.3 550.8 689.7
29.4 47.3 65.2 88.6 127.7 167.8 225.3 339.6 475.8 323.8 355.3 441.7 561.3

(1) Worst case condition including Enhanced Control board, HIM, and Communication Module.

Rockwell Automation Publication 20A-TD001L-EN-P - December 2020

45

Voltage Tolerance

This section provides information to help you determine the voltage tolerance for your drive installation.

Voltage Tolerance(1)

Drive Rating 200...240
380...480 500...600

Line Voltage nom 200 208 240 380 400 480 600

Motor Voltage nom 200(2) 208 230 380(2) 400 460 575(2)

Drive Full Power Range 200...264 208...264 230...264 380...528 400...528 460...528 575...660

Drive Operating Range 180...264
342...528 432...660

(1) Drive full power range = Nominal motor voltage to drive rated voltage +10%. Rated current is available across the entire drive full power range.
(2) Drive operating range = Lowest nominal motor voltage -10% to drive rated voltage +10%. Drive output is linearly derated when actual line voltage is less than the nominal motor voltage.

EXAMPLE:
Calculate the maximum power of a 5 Hp, 460V motor connected to a 480V rated drive supplied with 342V actual line voltage input.
� Actual Line Voltage / Nominal Motor Voltage = 74.3% � 74.3%  5 Hp = 3.7 Hp � 74.3%  60 Hz = 44.6 Hz
At 342V actual line voltage, the maximum power the 5 Hp, 460V motor can produce is 3.7 Hp at 44.6 Hz.

HP @ Motor (Drive Output)

No Drive Output
Nominal Motor Voltage -10% Nominal Motor Voltage
5 HP 3.7 HP

Derated Power Range Full Power Range Drive Operating Range
Drive Rated Voltage Drive Rated Voltage +10%

HP @ Motor (Drive Output)

No Drive Output

342V 460V

480V 528V

Actual Line Voltage (Drive Input)

46

Rockwell Automation Publication 20A-TD001L-EN-P - December 2020

Derating Guidelines
Follow these guidelines for derating your drive installation.
Altitude and Efficiency
Frame Type Derate
100%

% of Drive Rated Amps

90%
Altitude
80%

70%

All

0

1,000

2,000

3,000

4,000

5,000

6,000

Altitude (m)

Efficiency (typical)

% Efficiency

100 vs. Speed

95

90

vs. Load

85

80

75 10 20 30 40 50 60 70 80 90 100 % Speed/% Load

Rockwell Automation Publication 20A-TD001L-EN-P - December 2020

47

Ambient Temperature/Load

240V AC

PowerFlex 70 Power Rating

ND Hp

HD Hp

240 Volts

0.5...3.0

0.33...2.0

5.0

3.0

7.5

5.0

10

7.5

15

10

20

15

Max Ambient Temp (�C)

Max Ambient Temp (�C)

Max Ambient Temp (�C)

Max Ambient Temp (�C)

Max Ambient Temp (�C)

Derating
2 kHz
None
50 45 40 35 30 25 20
40
50 45 40 35 30 25 20
40
50 45 40 35 30 25 20
40
50 45 40 35 30 25 20
40
50 45 40 35 30 25 20
40

50

Max Ambient Temp (�C)

45

40

35

25

20

30

25

20 40

4 kHz

6 kHz

8 kHz

10 kHz

50

60

70

80

90

100

% of Rated Continuous Current

50

60

70

80

90

100

% of Rated Continuous Current

50

60

70

80

90

100

% of Rated Continuous Current

50

60

70

80

90

100

% of Rated Continuous Current

50

60

70

80

90

100

% of Rated Continuous Current

50

60

70

80

90

100

% of Rated Continuous Current

48

Rockwell Automation Publication 20A-TD001L-EN-P - December 2020

400V AC

PowerFlex 70 Power Rating

ND kW

HD kW

400 Volts

0.37...5.5

0.25...4.0

7.5

5.5

11

7.5

15

11

18.5

15

Derating

2 kHz

4 kHz

6 kHz

8 kHz

10 kHz

Max Ambient Temp (�C)

Max Ambient Temp (�C)

Max Ambient Temp (�C)

Max Ambient Temp (�C)

None
50 45 40 35 30 25 20
40
50 45 40 35 30 25 20
40
50 45 40 35 30 25 20
40
50 45 40 35 30 25 20
40

50

60

70

80

90

100

% of Rated Continuous Current

50

60

70

80

90

100

% of Rated Continuous Current

50

60

70

80

90

100

% of Rated Continuous Current

50

60

70

80

90

100

% of Rated Continuous Current

Rockwell Automation Publication 20A-TD001L-EN-P - December 2020

49

400V AC (Continued)

PowerFlex 70 Power Rating

ND kW

HD kW

400 Volts

22

18.5

30

22

37

30

480V AC

PowerFlex 70 Power Rating

ND Hp

HD Hp

480 Volts

0.5...7.5

0.33...5.0

10

7.5

15

10

20

15

50

Derating

2 kHz

4 kHz

6 kHz

8 kHz

10 kHz

Max Ambient Temp (�C)

Max Ambient Temp (�C)

50 45 40 35 30 25 20
40
50 45 40 35 30 25 20
40
50 45 40 35 30 25 20
40

50

60

70

80

90

100

% of Rated Continuous Current

50

60

70

80

90

100

% of Rated Continuous Current

50

60

70

80

90

100

% of Rated Continuous Current

Max Ambient Temp (�C)

Derating
2 kHz

4 kHz

6 kHz

8 kHz

10 kHz

Max Ambient Temp (�C)

Max Ambient Temp (�C)

Max Ambient Temp (�C)

None
50 45 40 35 30 25 20
40
50 45 40 35 30 25 20
40
50 45 40 35 30 25 20
40

50

60

70

80

90

100

% of Rated Continuous Current

50

60

70

80

90

100

% of Rated Continuous Current

50

60

70

80

90

100

% of Rated Continuous Current

Rockwell Automation Publication 20A-TD001L-EN-P - December 2020

480V AC (Continued)

PowerFlex 70 Power Rating

ND Hp

HD Hp

480 Volts

25

20

30

25

40

30

50

40

Derating
2 kHz

4 kHz

6 kHz

8 kHz

10 kHz

Max Ambient Temp (�C)

Max Ambient Temp (�C)

50 45 40 35 30 25 20
40
50 45 40 35 30 25 20
40
50 45 40 35 30 25 20
40
50 45 40 35 30 25 20
40

50

60

70

80

90

100

% of Rated Continuous Current

50

60

70

80

90

100

% of Rated Continuous Current

50

60

70

80

90

100

% of Rated Continuous Current

50

60

70

80

90

100

% of Rated Continuous Current

Max Ambient Temp (�C)

Max Ambient Temp (�C)

600V AC

PowerFlex 70 Power Rating

ND Hp

HD Hp

600 Volts

0.5...5.0

0.33...3.0

7.5

5.0

10

7.5

Derating
2 kHz

4 kHz

6 kHz

8 kHz

10 kHz

Max Ambient Temp (�C)

Max Ambient Temp (�C)

None
50 45 40 35 30 25 20
40
50 45 40 35 30 25 20
40

50

60

70

80

90

100

% of Rated Continuous Current

50

60

70

80

90

100

% of Rated Continuous Current

Rockwell Automation Publication 20A-TD001L-EN-P - December 2020

51

600V AC (Continued)

PowerFlex 70 Power Rating

ND Hp

HD Hp

600 Volts

15

10

20

15

25

20

30

25

40

30

50

40

Derating
2 kHz

4 kHz

6 kHz

8 kHz

10 kHz

Max Ambient Temp (�C)

Max Ambient Temp (�C)

Max Ambient Temp (�C)

50 45 40 35 30 25 20
40
50 45 40 35 30 25 20
40
50 45 40 35 30 25 20
40
50 45 40 35 30 25 20
40
50 45 40 35 30 25 20
40
50 45 40 35 30 25 20
40

50

60

70

80

90

100

% of Rated Continuous Current

50

60

70

80

90

100

% of Rated Continuous Current

50

60

70

80

90

100

% of Rated Continuous Current

50

60

70

80

90

100

% of Rated Continuous Current

50

60

70

80

90

100

% of Rated Continuous Current

50

60

70

80

90

100

% of Rated Continuous Current

Max Ambient Temp (�C)

Max Ambient Temp (�C)

Max Ambient Temp (�C)

52

Rockwell Automation Publication 20A-TD001L-EN-P - December 2020

PowerFlex 70 Adjustable Frequency AC Drive Technical Data

Additional Resources

These documents contain additional information concerning related products from Rockwell Automation.

Resource Preventive Maintenance of Industrial Control and Drive System Equipment, publication DRIVES-TD001
PowerFlex 70 Adjustable Frequency AC Drive User Manual, publication 20A-UM001
PowerFlex 70 EC and 700 VC Reference Manual, publication PFLEX-RM004 PowerFlex 70 and 700 Adjustable Frequency AC drives Reference Manual, publication PFLEX-RM001 PowerFlex 70 Adjustable Frequency AC Drive Installation Instructions, publication 20A-IN009 Wiring and Grounding Guidelines for Pulse Width Modulated (PWM) AC Drives, publication DRIVES-IN001
Communication adapter options, publications 20COMM-UMxxx
PowerFlex DriveGuard Safe Torque Off User Manual - Series B. publication PFLEXUM003
Industry Installation Guidelines for Pulse Width Modulated (PWM) AC Drives, publication DRIVES-AT003
Safety Guidelines for the Application, Installation, and Maintenance of Solid State Control, publication SGI-1.1 Guarding Against Electrostatic Damage, publication 8000-4.5.2
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1

Description
Provides a guide to performing preventive maintenance.
Provides the basic information that is needed to start up and troubleshoot the PowerFlex� 70 Adjustable Frequency AC Drive.
Provides detailed drive information including operation, parameter descriptions, and programming.
Provides detailed information for specifications and dimensions, operation, and dynamic brake selection for the drive.
Provides the five basic steps that are needed to install and perform a basic start up of the PowerFlex 70 drive.
Provides the basic information that is needed to properly wire and ground Pulse Width Modulated (PWM) AC drives.
Provides the information to install the communication option kit based on the 20-COMM-X that is chosen. By searching the specific COMM card, a detailed description of the card features and parameters can be explored. These communication cards are optional and vary depending on configuration.
Provides compatibility information for using the DriveGuard� Safe Torque Off option, with PowerFlex 40P or PowerFlex 70 drives and other safety components.
Provides basic information for enclosure systems and environmental/ location considerations (to help protect against environmental contaminants), and power and grounding considerations that are needed to properly install AC drives.
Provides general guidelines for the application, installation, and maintenance of solid-state control.
Provides practices for guarding against Electrostatic damage (ESD)
Provides general guidelines for installing a Rockwell Automation industrial system.

You can view or download publications at rok.auto/literature.

You can access declarations of conformity, certificates, and other certification details at: https://www.rockwellautomation.com/en-us/support/documentation/product-certifications.html

Rockwell Automation Publication 20A-TD001L-EN-P - December 2020

53

Rockwell Automation Support

Use these resources to access support information.

Technical Support Center Knowledgebase Local Technical Support Phone Numbers Literature Library Product Compatibility and Download Center (PCDC)

Find help with how-to videos, FAQs, chat, user forums, and product notification updates. Access Knowledgebase articles. Locate the telephone number for your country. Find installation instructions, manuals, brochures, and technical data publications. Download firmware, associated files (such as AOP, EDS, and DTM), and access product release notes.

rok.auto/support rok.auto/knowledgebase rok.auto/phonesupport rok.auto/literature
rok.auto/pcdc

Documentation Feedback
Your comments help us serve your documentation needs better. If you have any suggestions on how to improve our content, complete the form at rok.auto/docfeedback.

Waste Electrical and Electronic Equipment (WEEE)

At the end of life, this equipment should be collected separately from any unsorted municipal waste.

Allen-Bradley, Compact I/O, Connected Components Workbench, DriveExplorer, DriveGuard, Drive Peripheral Interface (DPI), DriveTools, expanding human possibility, FORCE, PanelView, Rockwell Automation, and Zero-Stacking are trademarks of Rockwell Automation, Inc. CANopen is a trademark of CAN in Automation LonWorks is a trademark of Echelon Corporation DeviceNet, ControlNet, and EtherNet/IP are trademarks of ODVA, Inc. PROFIBUS is a trademark of PROFIBUS and PROFINET International Trademarks not belonging to Rockwell Automation are property of their respective companies.
Rockwell Automation maintains current product environmental compliance information on its website at rok.auto/pec.
Rockwell Otomasyon Ticaret A.. Kar Plaza  Merkezi E Blok Kat:6 34752, �erenk�y, stanbul, Tel: +90 (216) 5698400 EEE Y�netmeliine Uygundur

Publication 20A-TD001L-EN-P - December 2020
Supersedes Publication 20A-TD001K-EN-P - April 2018

Copyright � 2020 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.