User Manual for weishaupt models including: WPM 6.0, Heat Pump Manager, WPM 6.0 Heat Pump Manager, Pump Manager, Manager

Waermepumpenmanager WPM 6.0 Software GB FD0107 wsh.book

manuela.laxson

Waermepumpenmanager WPM 6.0 Software GB FD0107 wsh

452117.66.20-EN · 1/2021-07 · Rei 6-76 Operating manual Heat pump manager WPM 6.0 1 User instructions 1 User instructions 1.1 General The installation and operating instructions must be observed during installation, operation

Waermepumpenmanager WPM 6.0 Software GB FD0107 wsh.book

Not Your Device? Search For Manuals / Datasheets:

File Info : application/pdf, 76 Pages, 2.97MB

Document
Current View
83323202
Operating manual

Heat pump manager WPM 6.0

83323202  1/2021-07

Operating manual Heat pump manager WPM 6.0

1 User instructions .................................................................................. 6
1.1 General ................................................................................................ 6 1.2 Regulations and safety notes! .............................................................. 6 1.3 Symbols ............................................................................................... 6
2 Operation............................................................................................. 7
2.1 Display and operating unit.................................................................... 7 2.2 Display ................................................................................................. 8
3 Favourites level ................................................................................... 9
4 User level........................................................................................... 11
4.1 Information ......................................................................................... 11 4.1.1 System ........................................................................................ 11 4.1.2 Heating/cooling circuit 1/2/3 ........................................................ 11 4.1.3 Cooling ........................................................................................ 12 4.1.4 Domestic hot water ..................................................................... 12 4.1.5 Pool ............................................................................................. 12 4.1.6 Heat pump................................................................................... 13
4.2 System functions ................................................................................ 13 4.3 Heating/cooling circuit 1 ..................................................................... 14 4.4 Heating/cooling circuit 2/3 .................................................................. 15 4.5 Domestic hot water ............................................................................ 16 4.6 Pool .................................................................................................... 18 4.7 Statistic............................................................................................... 18 4.8 Quantity of thermal energy ................................................................. 19 4.9 Compressor circuits ........................................................................... 20 4.10 Settings .............................................................................................. 21
5 Expert level........................................................................................ 23
5.1 System ............................................................................................... 23 5.2 Heating/cooling circuit 1/2/3 ............................................................... 23 5.3 Passive cooling .................................................................................. 24 5.4 Domestic hot water ............................................................................ 24 5.5 Pool .................................................................................................... 24 5.6 Heat pump.......................................................................................... 25 5.7 Error history........................................................................................ 26 5.8 Block history ....................................................................................... 28 5.9 Version overview ................................................................................ 30 5.10 System function.................................................................................. 31 5.11 Heat pump.......................................................................................... 31 5.12 2nd heat generator ............................................................................. 32 5.13 Heating/Cooling.................................................................................. 34 5.14 Heating/cooling circuit 1 ..................................................................... 35 5.15 Heating/cooling circuit 2/3 .................................................................. 36 5.16 Domestic hot water ............................................................................ 37 5.17 Pool .................................................................................................... 38 5.18 Pump control ...................................................................................... 39 5.19 Outputs............................................................................................... 41 5.20 Inputs ................................................................................................. 43

452117.66.20-EN · 1/2021-07 · Rei

3-76

Operating manual Heat pump manager WPM 6.0

5.21 Special functions ................................................................................ 44 5.21.1 Quick start ................................................................................... 44 5.21.2 Switch off lower operating limit.................................................... 44 5.21.3 Commissioning............................................................................ 44 5.21.4 System check.............................................................................. 45 5.21.5 Screed program .......................................................................... 45 5.21.6 Function check ............................................................................ 46
5.22 Installation .......................................................................................... 46
6 Commissioning assistant....................................................................47
7 Energy-efficient operation ..................................................................50
7.1 Outside temperature-dependent heating curve.................................. 50 7.1.1 Setting examples......................................................................... 51 7.1.2 Optimisation of the heating curve................................................ 52
7.2 Room temperature control.................................................................. 52 7.2.1 Setting examples......................................................................... 53 7.2.2 Optimisation of the room temperature control............................. 53
7.3 Fixed value regulation ........................................................................ 53
8 Domestic hot water preparation .........................................................53
8.1 Basic heating...................................................................................... 54 8.1.1 Achievable domestic hot water temperatures ............................. 54 8.1.2 Heat source-dependent domestic hot water temperatures ......... 54
8.2 Reheating ........................................................................................... 55 8.3 Thermal disinfection ........................................................................... 55 8.4 Domestic hot water lower time ........................................................... 55
9 Program description ...........................................................................56
9.1 Limit temperature ............................................................................... 56 9.2 Blocking requests ............................................................................... 56
9.2.1 Utility block .................................................................................. 56 9.2.2 Line load...................................................................................... 57 9.2.3 Minimum pause time ................................................................... 57 9.2.4 Switch cycle block ....................................................................... 57 9.3 2nd heat generator ............................................................................. 57 9.3.1 Control of immersion heaters ...................................................... 57 9.3.2 Control pipe heating .................................................................... 57 9.3.3 Constant control boiler ................................................................ 57 9.3.4 Sliding control boiler.................................................................... 58 9.3.5 Special program for older boilers and central storage systems .. 58 9.3.6 Bivalent-parallel........................................................................... 58 9.3.7 Bivalent-alternative...................................................................... 58 9.3.8 Bivalent-renewable...................................................................... 58 9.4 Power control ..................................................................................... 59 9.4.1 Heat pumps with one compressor............................................... 60 9.4.2 Heat pumps with two compressors ............................................. 60 9.4.3 High temperature air-to-water heat pumps ................................. 60 9.5 Hysteresis........................................................................................... 61 9.6 Control of the circulating pumps......................................................... 61

452117.66.20-EN · 1/2021-07 · Rei

4-76

Operating manual Heat pump manager WPM 6.0
9.6.1 Frost protection ........................................................................... 61 9.6.2 Heat circulating pump ................................................................. 62 9.6.3 Domestic hot water circulating pump .......................................... 62 9.6.4 Swimming pool circulating pump................................................. 62 9.6.5 Auxiliary circulating pump ........................................................... 63 9.6.6 Primary pump for heat source..................................................... 63 9.6.7 Circulation pump ......................................................................... 63 9.7 Building management system ............................................................ 64 9.7.1 BMS interface.............................................................................. 64 9.7.2 Compressor control via digital inputs .......................................... 64 9.7.3 External block.............................................................................. 66 9.7.4 Switching heating/cooling............................................................ 66
10 Commissioning of air-to-water heat pumps ....................................... 66
11 Initial heating program (screed drying) .............................................. 67
11.1 Implementation of the directive for a heat pump heating system ....... 67 11.2 Heating function program in accordance with DIN EN 1264-4........... 68 11.3 Line heating to dry out the screed ...................................................... 68
11.3.1 General notes.............................................................................. 68 11.3.2 Standard program line heating.................................................... 69 11.3.3 Individual program line heating ................................................... 70
12 Extended installation instructions for the heat pump manager heating/ cooling ............................................................................................... 71
12.1 Active cooling ..................................................................................... 71 12.1.1 Heat pumps without additional heat exchanger .......................... 71 12.1.2 Additional heat exchanger for waste heat recovery .................... 71
12.2 Passive cooling .................................................................................. 72 12.3 Program description cooling............................................................... 72
12.3.1 Cooling operating mode .............................................................. 72 12.3.2 Activating the cooling functions................................................... 72 12.3.3 Circulating pumps in cooling operation ....................................... 73 12.3.4 Silent and dynamic cooling ......................................................... 73 12.4 Room temperature control ................................................................. 74

452117.66.20-EN · 1/2021-07 · Rei

5-76

Operating manual Heat pump manager WPM 6.0 1 User instructions
1 User instructions
1.1 General
The installation and operating instructions must be observed during installation, operation and maintenance. This device may only be installed and repaired by trained specialists. Incorrect repairs can result in significant danger for the user. According to the valid regulations, the installation and operating instructions must be available at all times and be handed over to the specialist for their information when working on the device. We therefore ask that the instructions be handed over to the new tenant or owner when moving house. If there is visible damage on the device, it must not be connected. In this case, always consult with the supplier. Ensure that only genuine spare parts are used to avoid consequential damage. Environmentally-relevant requirements with regard to recovery, reuse and disposal of operating materials and components in accordance with the valid standards must be observed.
1.2 Regulations and safety notes!
 Adjustment work inside the device may only be carried out by an approved installer.
 The heat pump manager may only be operated in dry rooms with temperatures between 0 °C and 35 °C. Condensation is not permitted.
 In order to guarantee the frost protection function of the heat pump, the heat pump manager must not be deenergised and the heat pump must have flow through.
1.3 Symbols
Immediate danger with high risk. Failure to observe will result in severe injury or death.

DANGER WARNING CAUTION

Danger with moderate risk. Failure to observe can result in environmental damage, severe injury or death.
Danger with low risk. Failure to observe can result in material damage or minor to moderate injury.
Important note

452117.66.20-EN · 1/2021-07 · Rei

6-76

Operating manual Heat pump manager WPM 6.0 2 Operation
2 Operation
The heat pump manager is essential for the function of air-, brine- and water-to-water heat pumps. It controls a bivalent, monovalent or monoenergy heat pump heating system and monitors the safety units of the refrigeration circuit. Depending on the heat pump type, the heat pump manager is installed in the heat pump casing or is delivered as a wall-mounted controller with the heat pump and is responsible for controlling the heating system and the heat source system.
2.1 Display and operating unit

452117.66.20-EN · 1/2021-07 · Rei

7-76

Operating manual Heat pump manager WPM 6.0 2 Operation
2.2 Display
Start screen

Friday
Flow temperature 1
4

3

Summer Domestic hot water

5

2 6

 Information
 Outside temperature  Domestic hot water temperature  Elapsed time  Return temperature
 Level selection



Favourites level



User level



Expert level

 Status and operating mode display

 Flow temperature

 Hotter/colder
Heating curve shift





Compressor "On"



Compressor and 2nd heat generator "On"



2nd heat generator "On"

452117.66.20-EN · 1/2021-07 · Rei

8-76

Operating manual Heat pump manager WPM 6.0
3 Favourites level

Oper. mode
Party Holiday Hot water setp. temperature Lower times

3 Favourites level

Selection of the operating mode. The "Auto" operating mode can only be selected if the outside temperature-dependant operating mode switching is activated in the expert level.
Duration of a party mode in hours. After this time has elapsed, the system switches back to the previous operating mode automatically. The value for the raise is set in the menu 1. Heat circuit Increase times - Increase value. Duration of a holiday mode in days. After this time has elapsed, the system switches back to the previous operating mode automatically. The value for the lower is set in the menu 1. Heat circuit - Lower times - Lower value. Setting the desired domestic hot water set temperature.

Auto Summer Winter
Party Holiday 2nd heat generator Cooling
0 ... 4 hours ... 72
0 ... 15 days ... 150
30 ...50 °C ... 85

Setting the desired domestic hot water lower time.

Lower time 1 Lower time 2 Lower value
Room setp. temperature Increase times 1.Heat circuit
Increase time 1 Increase time 2 Increase value
Increase times 1.Heat circuit
Lower time 1 Lower time 2 Lower value
Increase times 2.Heat circuit
Increase time 1 Increase time 2

Setting the domestic hot water lower times.

00:00 ... 23:59 Mon ... Sun

00:00 ... 23:59 Mon ... Sun

Setting the desired domestic hot water set temperature, which

0 ... 10 °C ...

is also to be maintained during an active domestic hot water lower Domestic hot water set

time.

temperature

Setting the desired room set temperature in heating operation with room temperature control selected.

15.0 ... 20.0 °C ... 30.0

Settings for increasing the heating characteristic curve heating circuit 1.

Setting of the times when an increase for heating circuit 1 should take place.

00:00 ... 23:59 Mon ... Sun

00:00 ... 23:59 Mon ... Sun

Setting of the difference value by which the heating characteristic curve or room temperature heating circuit 1 should be raised during an increase.
Settings for setting back the heating characteristic curve heating circuit 1.

0 ... 2 K ... 19 0 ... 2 K ... 5

Setting of the times when a lower for heating circuit 1 should take place.

00:00 ... 23:59 Mon ... Sun

00:00 ... 23:59 Mon ... Sun

Setting of the difference value by which the heating characteristic curve or room temperature heating circuit 1 should be set back during a lower time.
Settings for increasing the heating characteristic curve heating circuit 2.

0 ... 2 K ... 19 0 ... 2 K ... 5

Setting of the times when an increase for heating circuit 2 should take place.

00:00 ... 23:59 Mon ... Sun

00:00 ... 23:59 Mon ... Sun

452117.66.20-EN · 1/2021-07 · Rei

9-76

Operating manual Heat pump manager WPM 6.0
3 Favourites level

Increase value
Increase times 2.Heat circuit
Lower time 1 Lower time 2 Lower value
Increase times 3.Heat circuit
Increase time 1 Increase time 2 Increase value
Increase times 3.Heat circuit
Lower time 1 Lower time 2 Lower value

Setting of the difference value by which the heating characteristic curve or room temperature heating circuit 2 should be raised during an increase. Settings for setting back the heating characteristic curve heating circuit 2. Setting of the times when a lower for heating circuit 2 should take place.
Setting of the difference value by which the heating characteristic curve or room temperature heating circuit 2 should be set back during a lower time. Settings for increasing the heating characteristic curve heating circuit 3. Setting of the times when an increase for heating circuit 3 should take place.
Setting of the difference value by which the heating characteristic curve or room temperature heating circuit 3 should be raised during an increase. Settings for setting back the heating characteristic curve heating circuit 3. Setting of the times when a lower for heating circuit 3 should take place.
Setting of the difference value by which the heating characteristic curve or room temperature heating circuit 3 should be set back during a lower time.

0 ... 2 K ... 19 0 ... 2 K ... 5
00:00 ... 23:59 Mon ... Sun
00:00 ... 23:59 Mon ... Sun 0 ... 2 K ... 19 0 ... 2 K ... 5
00:00 ... 23:59 Mon ... Sun
00:00 ... 23:59 Mon ... Sun 0 ... 2 K ... 19 0 ... 2 K ... 5
00:00 ... 23:59 Mon ... Sun
00:00 ... 23:59 Mon ... Sun 0 ... 2 K ... 19 0 ... 2 K ... 5

452117.66.20-EN · 1/2021-07 · Rei

10-76

Operating manual Heat pump manager WPM 6.0 4 User level
4 User level
4.1 Information
4.1.1 System

Info

System

Information External temperature
Heating/cooling demand
Heating/cooling setp. temperature
Heating/cooling act. temperature
Storage temperature renewable

Description The outside temperature is used, among other things, for calculating the return set temperature, for frost protection functions and for defrosting. Shows whether and from which heating/cooling circuit there is a heating/cooling requirement. Even if there is a requirement, the heat pump may not be running (e.g. down times, scavenging times). This block is indicated with the lock symbol. Display of the calculated return set temperature for heating/cooling.
Display of the measured return temperature for heating/cooling
Display of the measured temperature in the renewable cylinder.

4.1.2 Heating/cooling circuit 1/2/3

1.Heat/

2.Heat/

3.Heat/

Info

cool circuit

cool circuit

cool circuit

Information Status
Mixer Setp. temperature

Description
Shows whether there is an active heating/cooling requirement. Even if there is a requirement, the heat pump may not be running (e.g. down times, scavenging times). This block is indicated with the lock symbol.
If a mixer is used, the last and current status is indicated by a symbol (open, closed, open, close).
Display of the calculated setpoint temperature for heating/cooling circuit 1/2/3.

Act. temperature Display of the measured actual temperature for heating/cooling circuit 1/2/3.

Dewpoint

Display of the calculated dew point temperature without dew point distance.

Room humidity

Display of the measured humidity when using a room climate station or RTM Econ.

Room setp. temperature
Room temperature

Display of the room set temperature.
Display of the measured room temperature when using a room climate station, RTM Econ or room temperature sensor.

452117.66.20-EN · 1/2021-07 · Rei

11-76

Operating manual Heat pump manager WPM 6.0 4 User level
4.1.3 Cooling

Passive

Info

cooling

Information Flow temperature

Description
Display of the measured flow temperature on the passive cooling station during cooling operation.

Return temperature Display of the measured return temperature on the passive cooling station during cooling operation.

4.1.4 Domestic hot water

Hot

Info

water

Information Demand
Setp. temperature

Description
Shows whether there is an active domestic hot water request. Even if there is a requirement, the heat pump may not be running (e.g. programmed shut-off time, operating limits, heat up). This block is indicated with the lock symbol.
Display of the current domestic hot water set temperature.

Act. temperature Display of the measured domestic hot water temperature.

4.1.5 Pool

Info

Pool

Information Demand
Setp. temperature

Description
Shows whether there is an active swimming pool request. Even if there is a requirement, the heat pump may not be running (e.g. programmed shut-off time, operating limits, heat up). This block is indicated with the lock symbol.
Display of the current swimming pool set temperature.

Temperature

Display of the current swimming pool temperature.

452117.66.20-EN · 1/2021-07 · Rei

12-76

Operating manual Heat pump manager WPM 6.0 4 User level
4.1.6 Heat pump

Heat

Info

pump

Information Status

Description
Shows the current status of the heat pump. Off, Heating, Hot water, Pool, Cooling, Defrost, Throughput monitoring, Operating mode change-over, Block

Flow temperature

Display of the measured flow temperature. This temperature is used for the frost protection functions, operating limits and for air-to-water heat pumps as a safeguard for defrosting.

Return temperature Display of the measured return temperature

Heat source inlet
Heat source outlet

Display of the heat source inlet temperature on brine and water-to-water heat pumps. Display of the heat source outlet temperature on brine and water-to-water heat pumps.

4.2 System functions

Setting Oper. mode
Party Holiday

System functions

Description

Setting range

Selection of the operating mode. The "Auto" operating mode can only be selected if the outside temperature-dependant operating mode switching is activated in the expert level.

Auto Summer Winter
Party Holiday 2nd heat generator Cooling

Duration of a party mode in hours. After this time has elapsed, the system switches back to the previous operating mode automatically. The value for the raise is set in the menu 1. Heat circuit Increase times - Increase value.

0 ... 4 hours ... 72

Duration of a holiday mode in days. After this time has elapsed, the system switches back to the previous operating mode automatically. The value for the lower is set in the menu 1. Heat circuit - Lower times - Lower value.

0 ... 15 days ... 150

452117.66.20-EN · 1/2021-07 · Rei

13-76

Operating manual Heat pump manager WPM 6.0 4 User level
4.3 Heating/cooling circuit 1

1.Heat/ cool circuit
During commissioning, the heating characteristic curve is adapted according to the local and structural conditions. This heating characteristic curve can be adjusted to the individual temperatures requirements with the hotter / colder arrow keys in the main display.
The plus key is used to increase the temperature, the bar display moves to the right.
The minus key is used to reduce the temperature, the bar display moves to the left.
For heating circuit 2/3, this setting takes place in the menu "2./3. Heat circuit".
The set heating characteristic curves can be lowered or raised on a time-controlled basis. E.g. the heating characteristic curve can be lowered at night in poorly insulated buildings or excessive cooling of the heating surfaces can be prevented by raising heating characteristic curve before the shut-off time.
If the raise and lower overlap, the raise function has priority.
TIP
For energy efficient operation of the heat pump heating system, the temperature level to be achieved by the heat pump should be as low as possible. In well-insulated buildings, an even heating operation without lower times usually results in lower energy costs, as power leaks with high flow temperatures are avoided and the same level of comfort is achieved with lower temperatures. Shut-off times can be compensated for with a raise - which commences approx. 1 hour before the shut-off time.

Setting Room setp. temperature Lower times
Lower time 1 Lower time 2 Lower value
Increase times
Increase time 1 Increase time 2 Increase value
Silent cooling

Description
Setting the desired room set temperature in heating operation with room temperature control selected.

Setting range 15.0 ... 20.0 °C ... 30.0

Settings for setting back the heating characteristic curve heating circuit 1.

Setting of the times when a lower for heating circuit 1 should take place.

00:00 ... 23:59 Mon ... Sun

00:00 ... 23:59 Mon ... Sun

Setting of the difference value by which the heating characteristic curve or room temperature heating circuit 1 should be set back during a lower time.
Settings for increasing the heating characteristic curve heating circuit 1.

0 ... 2 K ... 19 0 ... 2 K ... 5

Setting of the times when an increase for heating circuit 1 should take place.

00:00 ... 23:59 Mon ... Sun

00:00 ... 23:59 Mon ... Sun

Setting of the difference value by which the heating characteristic curve or room temperature heating circuit 1 should be raised during an increase.
Setting the room set temperature with silent cooling The actual value is measured on the room climate station 1.

0 ... 2 K ... 19 0 ... 2 K ... 5
15.0 ... 20 °C ... 30.0

452117.66.20-EN · 1/2021-07 · Rei

14-76

Operating manual Heat pump manager WPM 6.0
4 User level

Setting Dynamic cooling
Blocking time 1 Blocking time 2

Description

Setting range

Setting the desired return set temperature with dynamic cooling selected. The return set value is adapted on a linear basis depending on the outside temperature. A characteristic curve is used for this, which is set at two specific operating points. The return set value is defined with the fixed outside temperatures of 15 °C and 35 °C.

10 ... 15 °C ... 30 10 ... 15 °C ... 30

4.4 Heating/cooling circuit 2/3

2./3.Heat/ cool circuit

Setting Lower times
Lower time 1 Lower time 2 Lower value
Increase times
Increase time 1 Increase time 2 Increase value
Silent cooling

Description

Setting range

Settings for setting back the heating characteristic curve heating circuit 2/3.

Setting of the times when a lower for heating circuit 2/3 should take place.

00:00 ... 23:59 Mon ... Sun

00:00 ... 23:59 Mon ... Sun

Setting of the difference value by which the heating characteristic curve or room temperature heating circuit 2/3 should be set back during a lower time.
Settings for increasing the heating characteristic curve heating circuit 2/3

0 ... 2 K ... 19 0 ... 2 K ... 5

Setting of the times when an increase for heating circuit 2/3 should take place.

00:00 ... 23:59 Mon ... Sun

00:00 ... 23:59 Mon ... Sun

Setting of the difference value by which the heating characteristic curve or room temperature heating circuit 2/3 should be raised during an increase.
Setting the room set temperature with silent cooling The actual value is measured on the room climate station 1/2.

0 ... 2 K ... 19 0 ... 2 K ... 5
15.0 ... 20.0 °C ... 30.0

452117.66.20-EN · 1/2021-07 · Rei

15-76

Operating manual Heat pump manager WPM 6.0 4 User level
4.5 Domestic hot water
Hot water
The heat pump manager determines the maximum possible domestic hot water temperature in heat pump operation automatically. The desired domestic hot water temperature can be set in the menu "Hot water - Hot water setp. temperature".
TIP
Because the domestic hot water preparation takes place with high flow temperatures, which can result in high energy costs, it is advisable to adapt the domestic hot water preparation to the user behaviour. This can be achieved with domestic hot water set temperatures optimally adapted to the requirements, with corresponding domestic hot water lower times and a large hysteresis.
Domestic hot water temperature HP maximum
In order to achieve the highest possible heat pump proportion for domestic hot water preparation, the heat pump manager automatically determines the maximum achievable domestic hot water temperature in heat pump operation depending on the current heat source temperature. The lower the heat source temperature (e.g. outside temperature, brine temperature), the higher the achievable domestic hot water temperature.
Domestic hot water preparation without flange heater
If the domestic hot water set temperature is higher than the maximum domestic hot water temperature that can be achieved by the heat pump, the domestic hot water preparation is interrupted as soon as "HP maximum temperature" is reached.
Domestic hot water preparation with flange heater
If the domestic hot water set temperature is higher than the maximum domestic hot water temperature that can be achieved by the heat pump, the domestic hot water preparation takes place via the installed flange heater from the "HP maximum temperature".
Reheating with flange heater After domestic hot water preparation with the heat pump, reheating for higher temperatures can take place with systems with a flange heater. The next domestic hot water heating only takes place once the temperature drops below the HP maximum temperature so that the basic heating can take place via the heat pump.
Domestic hot water lower times
Block times for the hot water heating can be programmed in the "Hot water lower times" menu item. During this time, the hot water heating is only carried out with minimal temperature.
If a sufficiently large storage system is available, it is advisable to switch the hot water heating or reheating to overnight in order to use the low-tariff periods that are often cheaper.
Thermal disinfection
In the menu item "Hot water - Thermal disinfection", on bivalent systems or with domestic hot water cylinders with installed flange heater, thermal disinfection can take place with domestic hot water temperatures of up to 85 °C. The thermal disinfection can take place at a start time that can be set for each weekday.

452117.66.20-EN · 1/2021-07 · Rei

16-76

Operating manual Heat pump manager WPM 6.0
4 User level

Circulation
In the menu item "Hot water - Circulation", the actuation of the circulation pump can be programmed. A maximum of two time windows can be defined. A maximum of two circulation times can be assigned to each weekday. Exceeding demands are activated or deactivated at midnight.
TIP
A circulation line uses large amounts of energy. To save on energy costs, circulation should not be used. If this is unavoidable, it is advisable to adapt the time window to the optimal conditions. A better approach is to have the circulation running via an impulse for a specific time. This function is also possible with the heat pump manager.

Setting Hot water setp. temperature Hot water lower times Lower time 1 Lower time 2 Lower temperature
Thermal disinfection
Start time

Description Setting the desired domestic hot water set temperature.
Setting the desired domestic hot water lower time.

Setting range 30 ... 50 °C ... 85

Setting the domestic hot water lower times.

00:00 ... 23:59 Mon ... Sun

00:00 ... 23:59 Mon ... Sun

Setting the desired domestic hot water set temperature, which is

0 ... 10 °C ...

also to be maintained during an active domestic hot water lower Domestic hot water set

time.

temperature

Thermal disinfection results in a one-off domestic hot water heating up to the desired temperature. The status is ended automatically when thetemperature is reached, at 24:00 or at the latest after 4 hours.

Setting the start time for thermal disinfection.

00:00 ... 23:59

Temperature
Circulation
Time program 1 Time program 2 Impulse time

Setting the desired domestic hot water set temperature to be achieved with thermal disinfection. The circulation pump is actuated by a time function or an impulse input. Setting the circulation pump actuation times.
Setting the runtime of the circulation pump with activation after an impulse.

60 °C ... 85
00:00 ... 23:59 Mon ... Sun
00:00 ... 23:59 Mon ... Sun
1 ... 5 minutes ... 15

452117.66.20-EN · 1/2021-07 · Rei

17-76

Operating manual Heat pump manager WPM 6.0 4 User level
4.6 Pool

Pool

Setting Setp. temperature

Description Setting the desired swimming pool set temperature.

Setting range 5 ... 25 °C ... 60

Blocking time Blocking time 1 Blocking time 2 Temperature
Priority Start time Priority hours

Setting the time programs for blocking the swimming pool preparation. Setting the times for a swimming pool block.
Setting the desired swimming pool set temperature, which is also to be maintained during an active swimming pool block. Setting the time programs for prioritising the swimming pool preparation. Setting the start time for swimming pool priority.
Setting the desired number of hours for swimming pool priority.

00:00 ... 23:59 Mon ... Sun
00:00 ... 23:59 Mon ... Sun 0 ... 10 °C ...
Pool set temperature
00:00 ... 23:59 Mon ... Sun
1 ...1 hours ... 10

4.7 Statistic

Statistic

Run times

Setting Compressor 1
Compressor 1 total

Description Runtime compressor 1 The runtime can be reset.
The total runtime can not be reset.

Compressor 2 Compressor 2 total

Runtime compressor 2 The runtime can be reset.
The total runtime can not be reset.

Fan Fan total

Fan runtime The runtime is lower than the sum of the compressor runtimes due to defrosting. The runtime can be reset.
The total runtime can not be reset.

Primary pump
Primary pump total 2.heat generator

Runtime of the primary pump or the well pump The runtime is higher than the sum of the compressor runtimes due to pump flow and pump delay. The runtime can be reset. The total runtime can not be reset.
Runtime 2nd heat generator The runtime can be reset.

452117.66.20-EN · 1/2021-07 · Rei

18-76

Operating manual Heat pump manager WPM 6.0
4 User level

Setting 2.heat generator total Heating pump
Heating pump total

Description The total runtime can not be reset.
Runtime heat circulating pump The runtime can be reset. The total runtime can not be reset.

Add. pump

Runtime auxiliary circulating pump The runtime can be reset.

Add. pump total

The total runtime can not be reset.

Hot water pump

Runtime domestic hot water circulating pump The runtime can be reset.

Hot water pump total The total runtime can not be reset.

Flange heating

Runtime flange heater The runtime can be reset.

Flange heating total The total runtime can not be reset.

Pool pump Pool pump total

Runtime swimming pool circulating pump The runtime can be reset.
The total runtime can not be reset.

Renewable
Renewable total Cooling
Cooling total

Runtime renewable The runtime can be reset. The total runtime can not be reset.
Runtime of the compressor in cooling operation The runtime can be reset. The total runtime can not be reset.

4.8 Quantity of thermal energy

Setting Heat pump
Heat pump total Heating
Heating total

Statistic

Heat quantity

Description The quantity of thermal energy emitted from the heat pump is added up and displayed. The quantity of thermal energy can be reset.
The total quantity of thermal energy can not be reset.

Display of the emitted quantity of thermal energy from the heat pump in heating operating mode. For parallel operation (with additional heat exchanger: domestic hot water and heating), the quantity of thermal energy is included in the calculation here. The quantity of thermal energy can be reset. The quantity of thermal energy heating can be reset.
The total quantity of thermal energy heating can not be reset.

452117.66.20-EN · 1/2021-07 · Rei

19-76

Operating manual Heat pump manager WPM 6.0
4 User level

Setting Hot water
Hot water total Pool
Pool total Environm. energy
Environm. energy total

Description Display of the emitted quantity of thermal energy from the heat pump in domestic hot water operating mode. The quantity of thermal energy can be reset. The quantity of thermal energy domestic hot water can be reset. The total quantity of thermal energy heating can not be reset.
Display of the emitted quantity of thermal energy from the heat pump in swimming pool operating mode. The quantity of thermal energy can be reset. The quantity of thermal energy swimming pool can be reset. The total quantity of thermal energy swimming pool can not be reset.
Display of the environmental energy used The quantity of environmental energy can be reset.
The total quantity of environmental energy can not be reset.

4.9 Compressor circuits

Statistic

Compressor circuits

Setting

Description

Compressor 1 total Display of the switchings compressor 1 total.

Compressor 1 Heating Display of the switchings compressor 1 in heating operation.

Compressor 1 Hot water
Compressor 1 Pool

Display of the switchings compressor 1 during domestic hot water preparation. Display of the switchings compressor 1 in swimming pool preparation.

Compressor 1 Cooling Display of the switchings compressor 1 in cooling operation.

Compressor 2 total Display of the switchings compressor 2 total.

Compressor 2 Heating Display of the switchings compressor 2 in heating operation.

Compressor 2 Hot water
Compressor 2 Pool

Display of the switchings compressor 2 during domestic hot water preparation. Display of the switchings compressor 2 in swimming pool preparation.

Compressor 2 Cooling Display of the switchings compressor 2 in cooling operation.

452117.66.20-EN · 1/2021-07 · Rei

20-76

Operating manual Heat pump manager WPM 6.0 4 User level
4.10 Settings

Settings

Parameters

Setting
Setting the desired language. Depending on the software version, not all languages listed may be available.

Language

Setting of the time.

Time
Setting of the day, month, year and weekday.

Date Time change

Automatic switching between summer and winter time can be selected.

Setting range Deutsch English Français
Nederlands Italiano Svenska Dansk Magyar Ceský
Slovenský Hrvatski Slovenski Norsk
00:00 ... 23:59
04.02.19 Mon ... Sun
Yes / No

452117.66.20-EN · 1/2021-07 · Rei

21-76

Parameters Setting Protocol

Network

Address

Baud rate

NWPM Settings
Display

Parity
Stop bits
IP address Netmask Gateway DNS1 DNS2 Brightness Light strip
Reboot

Operating manual Heat pump manager WPM 6.0
4 User level

Setting range

The Protocol setting is used to define the type of interface installed and the transmission protocol.

LAN Modbus RTU
EIB / KNX Modbus TCP

When Modbus is used, every terminal device in the network must be assigned an address. This address is used to communicate with the desired terminal device.

000 ... 001 ... 199

When Modbus is used, the baud rate must be adapted to the system baud rate. It is important to ensure that the same baud rate is set on both sides of the communication.

1200 2400 4800 9600 19200

If Modbus is selected, the parity can be selected here.

None Even Odd

If Modbus is selected, the stop bits can be selected here.

1

2

Reading out the IP address Reading out the subnet mask Reading out the gateway address Reading out the DNS1 address Reading out the DNS2 address

000 ... 255 000 ... 255 000 ... 255 000 ... 255 000 ... 255

Setting the display brightness Setting whether the light strip should be "Permanent On" and therefore lights up green or "Permanent Off". The display can be restarted manually, without disconnecting the power supply to the heat pump completely.

0 ... 255 On / Off
Yes

452117.66.20-EN · 1/2021-07 · Rei

22-76

Operating manual Heat pump manager WPM 6.0 5 Expert level
5 Expert level
5.1 System

Parameters 1.1.1 External temperature 1.1.2 Heat circuit
1.1.3 Cool circuit
1.1.4 Heating return setp. temperature 1.1.5 Heating return temperature 1.1.6 Cooling return setp. temperature 1.1.7 Cooling return temperature 1.1.8 Storage temperature Renewable

Info

System

Description
The outside temperature is used, among other things, for calculating the return set temperature, for frost protection functions and for defrosting.
Shows whether and from which heating circuit there is a heating request. Even if there is a requirement, the heat pump may not be running (e.g. down times, scavenging times). This block is indicated with the lock symbol.
Shows whether and from which heating/cooling circuit there is a cooling requirement. Even if there is a requirement, the heat pump may not be running (e.g. down times, scavenging times). This block is indicated with the lock symbol.
Display of the calculated return set temperature in heating operation.

Display of the measured return temperature in heating operation.

Display of the calculated return set temperature in cooling operation.

Display of the measured return temperature in cooling operation.

Display of the measured temperature in the renewable cylinder.

5.2 Heating/cooling circuit 1/2/3

Parameters 1.2.1/1.3.1/1.4.1 Heating/Cooling
1.2.2/1.3.2/1.4.2 Setp. temperature 1.2.3/1.3.3/1.4.3 Act. temperature 1.2.4/1.3.4/1.4.4 Dewpoint 1.2.5/1.3.5/1.4.5 Dewpoint

1.Heat/

2.Heat/

3.Heat/

Info

cool circuit

cool circuit

cool circuit

Description
Shows the current operating mode of the relevant circuit. If the circuit is blocked for an operating mode, this is indicated by a lock symbol. A mixer symbol indicates the current status of the mixer.
Display of the calculated setpoint temperature for heating/cooling circuit 1/2/3.

Display of the measured actual temperature for heating/cooling circuit 1/2/3.

Display of the calculated dew point temperature without dew point distance when using room controller RTM Econ.
Display of the calculated dew point temperature without dew point distance when using a room climate station.

452117.66.20-EN · 1/2021-07 · Rei

23-76

Operating manual Heat pump manager WPM 6.0
5 Expert level

Parameters 1.2.6/1.3.6/1.4.6 Room humidity
1.2.7/1.3.7/1.4.7 Room setp. temperature
1.2.8/1.3.8/1.4.8 Room temperature

Description Display of the measured humidity when using a room climate station or RTM Econ.
Display of the room set temperature.
Display of the measured room temperature when using a room climate station, RTM Econ or room temperature sensor.

5.3 Passive cooling

Parameters 1.5.1 Flow temperature
1.5.2 Return temperature

Passive

Info

cooling

Description
Display of the measured flow temperature on the passive cooling station during cooling operation.
Display of the measured return temperature on the passive cooling station during cooling operation.

5.4 Domestic hot water

Parameters 1.6.1 Demand
1.6.2 Setp. temperature 1.6.3 Act. temperature

Hot

Info

water

Description
Shows whether there is an active domestic hot water request. Even if there is a requirement, the heat pump may not be running (e.g. programmed shut-off time, operating limits, heat up). This block is indicated with the lock symbol.
Display of the current domestic hot water set temperature.

Display of the measured domestic hot water temperature.

5.5 Pool

Parameters 1.7.1 Demand
1.7.2 Setp. temperature 1.7.3 Act. temperature

Info

Pool

Description
Shows whether there is an active swimming pool request. Even if there is a requirement, the heat pump may not be running (e.g. programmed shut-off time, operating limits, heat up). This block is indicated with the lock symbol.
Display of the current swimming pool set temperature.

Display of the current swimming pool temperature.

452117.66.20-EN · 1/2021-07 · Rei

24-76

Operating manual Heat pump manager WPM 6.0 5 Expert level
5.6 Heat pump

Parameters 1.8.1 Status
1.8.2 Return temperature
1.8.3 Flow temperature
1.8.4 Heat source inlet temperature
1.8.5 Heat source outlet temperature
1.8.6 Brine temperature
1.8.7 High pressure sensor
1.8.8 Low pressure sensor
1.8.9 Load stage Heating
1.8.10 Load stage Cooling

Heat

Info

pump

Description Shows the current status of the heat pump. Off, Heating, Hot water, Pool, Cooling, Defrost, Throughput monitoring, Operating mode change-over, Block
Display of the measured return temperature

Display of the measured flow temperature. This temperature is used for the frost protection functions, operating limits and for air-to-water heat pumps as a safeguard for defrosting.
Display of the heat source inlet temperature on brine and water-to-water heat pumps.

Display of the heat source outlet temperature on brine and water-to-water heat pumps.

Display of the measured shared brine temperature with reversible brine-to-water heat pumps with active/passive combination (R24). Display of the measured high pressure value.
Display of the measured low pressure value.
Display of the calculated load stage for heating.

Display of the calculated load stage for cooling.

452117.66.20-EN · 1/2021-07 · Rei

25-76

Operating manual Heat pump manager WPM 6.0 5 Expert level
5.7 Error history

Fault

Info

history

In the event of faults, the heat pump is blocked. With bivalent systems, the second heat generator takes over the heating and the domestic hot water preparation. With mono energy systems, the domestic hot water preparation is stopped. The immersion heater maintains the minimum permissible return temperature.
The heat pump manager displays the active faults in plain text. The heat pump is blocked. Once the fault has been remedied, the heat pump can be commissioned again by actuating
the key. (Switching off the control voltage also acknowledges an active fault.)

With mono energy systems, switching to the operating mode 2nd heat generator enables the heating to be taken over the by the immersion heater and the domestic hot water preparation by the flange heater.

Low pressure switch brine
If a "low pressure switch brine" available as a special accessory is installed in the primary circuit of a brine-to-water heat pump, a fault is triggered if there is a drop in brine pressure.

Diagnosis faults - alarm - block

The menu "Info - Error history/Block history" documents the last 10 causes for a fault and block. The documentation takes place with date, time, heat source temperature, flow temperature, return temperature andthe status message.

Error code F1 F2 F3 F5 F6
F7
F8 F10 F12
F15
F16 F19

Error

Message

Measure

Expansion N17.1 Expansion N17.2 Expansion N17.3 Expansion N17 Electronic expansion valve Room controller RTH Econ Expansion ODU Expansion WPIO Error inverter
Sensor technology
Brine pressure switch Primary circuit

The expansion module "Cooling general" is not recognised · Connection cable

The expansion module "Cooling active" is not recognised. The expansion module "Cooling passive" is not recognised.

check - Cable interrupted - Connector loose

The expansion module "Cooling" is not recognised.

- Individual wires mixed up

The electronic expansion valve is not recognised.

Power supply check

The reference room modulator is not recognised.

The refrigeration circuit controller is not recognised

The inverter reports an error. There is a wide range of pos- · sible causes.
An error has occurred on the required sensor technology, · the exact cause is shown in the plain text.

The brine pressure switch in the brine circuit has switched. ·

Fault due to motor protection primary pump or fan

·

·

Inform after-sales service
Connection cable check - Cable interrupted - Connector loose - Individual wires mixed up
Power supply check Check the brine pressure
Motor protection primary pump or fan Check the setting or function

452117.66.20-EN · 1/2021-07 · Rei

26-76

Operating manual Heat pump manager WPM 6.0
5 Expert level

Error code F20
F21 F22
F23
F24 F25
F26 F28
F29
F30 F31

Error

Message

Measure

Defrost

Defrosting of the air-to-water heat pump could not be initi- ·

ated or could not be ended correctly. There is a wide range

of possible causes for this message.

·

·

Brine pressure switch Domestic hot water

· The brine pressure switch in the brine circuit has switched. ·
Domestic hot water temperatures in heat pump operation · under 35 °C

· ·

Load compressor Coding

Direction of rotation incorrect

·

Phase failure

·

Start-up current of the compressor too high

·

Undervoltage operating current of compressor too high

Overtemperature soft starter

Mains frequency incorrect

Coding does not match the heat pump type

·

Low pressure

The heat source supplies too little energy

·

·

·

·

·

Frost protection High pressure

The flow temperature in heating operating mode is

·

below 7 °C.

The heat pump was switched off by the high pressure · sensor or pressure switch.
·

·
Temperature difference The temperature difference between the flow and return · for defrosting is too large (>12 K) or negative. ·

Hot gas thermostat Throughput

·
·
The heat pump was switched off due to a lack of flow in the · primary or secondary circuit.
·

·

Check the heating water flow rate Check the heating water pressure Check the flow and return temperature Inform after-sales service
Check the brine pressure
Throughput of the domestic hot water circulating pump too low Check valve heating faulty Check the domestic hot water sensor
Check the rotary field Check the supply voltage Inform after-sales service
The detected heat pump type is shown in the Version overview menu
Clean the filter in the dirt trap Purge the heat source system Check the brine or water flow Inform after-sales service Evaporator iced over or system temperatures too low (return < 18 °C)
Increase the heating water temperature
Lower the heating curve setting Raise the heating water flow rate Check the overflow valve
Check the heating water flow rate Check the overflow valve and pump size Flow and return mixed up
Inform after-sales service
Water flow well or brine circuit too low Water flow in the secondary circuit too low Flow direction incorrect

452117.66.20-EN · 1/2021-07 · Rei

27-76

Operating manual Heat pump manager WPM 6.0 5 Expert level
5.8 Block history

Info

Block code S5 S7 S8
S9 S10

Block
Function check System check Delay Operating mode change-over Pump supply Minimum pause time

S11 Line load

S12 Switch cycle block

S13 Domestic hot water reheating S14 Renewable
S15 Utility block S16 Soft starter S17 Throughput
S18 2nd heat generator
S19 High pressure S20 Low pressure S21 Operating limit S22 4-way valve S23 System limit S24 Primary circuit load
S25 External block
S26 WPIO
S29 Inverter
S30 Maximum blocks
S31 Heat

Block history
Brief description
The check function has been activated by a user.
The system check was activated by a user for approx. 24 hours.
The delay time protects the heat pump from a quick temperature change with a cooling and domestic hot water demand. The heat pump starts after the set pump flow has elapsed
The heat pump starts after the minimum pause time has elapsed in order to fulfil a pending demand. The minimum pause time protects the heat pump and can last for up to 5 minutes. The heat pump starts after the line switch-on load in order to fulfil a pending demand. The line switch-on load is a requirement from the utility companies and can last for up to 200 seconds after the voltage is restored or utility blocks. The heat pump starts after the switch cycle block in order to fulfil a pending demand. The switch cycle block is a requirement from the utility companies and can last for up to 20 minutes. The domestic hot water reheating via the flange or pipe heating is active
If "bivalent-renewable" operating mode is selected, the temperature in the cylinder is high enough to process the active demand. There is an active utility block.
Switch-off of the heat pump due to soft starter
The heat pump was switched off due to a lack of flow in the primary or secondary circuit. The message is reset automatically after 4 minutes. The heat pump has been blocked due to the outside temperature being too low and the 2nd heat generator has been activated The permissible high-pressure values for the heat pump have been exceeded.
The permissible low-pressure values for the heat pump have not been reached.
The heat source temperature is below the operating limit for the heat pump.
The 4-way valve has not switched back to the initial state after defrosting.
The system temperatures are too low to operate the heat pump.
The heat pump was blocked due to the fan motor protection. The heat pump restarts automatically. The system was switched to blocked state by an external blocking signal on input ID4. The function can be configured in the menu. The communication between the heat pump manager and refrigeration circuit controller WPIO is interrupted. If no connection can be established, a fault is triggered. The inverter was blocked. There is a wide range of possible causes. An attempt is made to remove the block automatically. The maximum number of daily approved blocks has been exceeded. The block will be lifted automatically after 00:00. The "Heat" function is intended to prevent an excessive concentration of liquid refrigerant in the oil when the compressor starts up. The maximum heat time can be up to 9 hours!

452117.66.20-EN · 1/2021-07 · Rei

28-76

Operating manual Heat pump manager WPM 6.0
5 Expert level

Block code S32
S33 S34

Block

Brief description

Maximum operating mode switch- The number of permitted daily operating mode switchings has been exceeded.

ing

The block will be lifted automatically after 00:00.

EvD initialisation

The communication with the electronic expansion valve is established

2nd heat generator

The operating mode 2nd heat generator has been selected. The heat pump is switched off. The heat generation takes place exclusively via the 2nd heat generator

452117.66.20-EN · 1/2021-07 · Rei

29-76

Parameters 1.9.1 Heat pump type
1.9.2 Heat pump code
1.9.3 WPM Software
1.9.4 WPM BIOS
1.9.5 WPM BOOT
1.9.6 WPM Hardware
1.9.7 IO Software
1.9.8 IO BIOS
1.9.9 IO BOOT
1.9.10 IO Hardware
1.9.11 pGD Software
1.9.12 pGD Run Time
1.9.13 pGD Main OS

Operating manual Heat pump manager WPM 6.0 5 Expert level
5.9 Version overview

Version

Info

overview

Description Display of the heat pump type.

Display of the heat pump code.

Display of the heat pump manager software version.

Display of the heat pump manager BIOS version.

Display of the heat pump manager BOOT version.

Display of the heat pump manager hardware version.

IO is an additional extension. If an IO extension is present, the software version is shown here.
Display of the IO extension BIOS version.

Display of the IO extension BOOT version.

Display of the IO extension hardware version.

Display of the pGDx display software version.

Display of the pGDx display run time version.

Display of the pGDx display main OS version.

452117.66.20-EN · 1/2021-07 · Rei

30-76

Operating manual Heat pump manager WPM 6.0 5 Expert level
5.10 System function

Parameters 2.1 Automatic oper. mode change-over 2.2 Oper. mode change-over
2.3 External temperature Heating < 2.4 External temperature Cooling >

System functions

Setting

Setting range

Setting whether operating mode switching should take place automatically.

Yes / No

If the outside temperature-dependent operating mode switching is activated, the operating mode is changed automatically depending on an adjustable limit temperature. A change takes place if the limit temperatures are exceeded or not reached in a row for the set time.
Limit temperatures at which the operating mode of the heat pump is switched automatically. The summer operating mode is active between the limit temperatures.

1 h ...150
-30 ... 15 °C ... 40 -30 ... 25 °C ... 40

5.11 Heat pump

Parameters 3.1 Compressor qty.
3.2 Fan lower times
3.2.1 Lower time 1 3.2.2 Lower time 2
3.2.3 Lower value 3.3 Heat pump code 3.4 Freeze protection

Heat pump

Setting

Setting range

The setting for the number of compressors is dependent on the

heat pump type, the relevant quantity can be found in the operating the installation instructions for the heat pump or the heat pump

1 / 2

type plate.

Settings for lowering the fan speed. The lowering results in an output reduction by approx. 15%.

Setting the times for lowering the fan speed. It can be selected separately for each weekday whether lower time 1 and/or lower time 2 for the fan speed should be activated. Lowers extending beyond a weekday are activated or deactivated at midnight.
Value for lowering the fan speed during cooling. A fixed value applies during heating.

00:00 ... 23:59 MON ...SUN
0.0 ... 1.0 V ... 1.5

The 4-digit heat pump code printed on the type plate can be corrected with these settings.

Setting of the lower operating limit for using the heat source ground water or waste heat recovery via intermediate heat exchanger. Depending on the heat pump type, the usage range (brine) of the heat source can be expanded as required. In this case, the minimum brine concentration must be adapted to 30 %.

15 ... -9 °C ... -13

452117.66.20-EN · 1/2021-07 · Rei

31-76

Operating manual Heat pump manager WPM 6.0
5 Expert level

Parameters 3.5 Primary pump M11 3.6 Primary pump manual

Setting

Setting range

Setting the speed of the electronically regulated primary circulating pump heat source (M11).

manual Stage 1 Stage 2 Stage 3 automatic

3.7 Flow switch secondary circuit
3.8 Flow rate switch Primary circuit

Does flow rate monitoring take place in the secondary circuit? Does flow rate monitoring take place in the primary circuit?

20 ... 50 ... 100 Yes / No
Yes / No

5.12 2nd heat generator

Parameters 4.1 Limit temperature parallel
4.2 Limit temperature alternative 4.3 Operating mode
4.4 Mixer run time
4.5 Mixer hysteresis
4.6 EVU block release

2.heat exchanger

Setting

Setting range

The limit temperature of the 2nd heat generator must be selected according to the design of the heat pump heating system. Below the limit temperature parallel, the heat pump runs and the 2nd heat generator for heating the building. The 2nd heat generator is only switched on from temperatures below the set limit temperature parallel and load stage 3. If parallel operation is not desired, the limit temperature parallel should be adapted to the limit temperature alternative.

Limit temperature alternative ... -5 °C ...
Limit temperature 2nd compressor

If the value falls below the limit temperature alternative and load stage 3, only the 2nd heat generator is used to heat the building. The heat pump is blocked from this time

Lower operating limit ... -10 °C ...
Limit temperature parallel

A sliding regulated 2nd heat generator has its own regulation and is flowed through with the full volume flow if necessary. A constantly regulated 2nd heat generator is set to a constant temperature, the mixer regulation is active.

Sliding (valve) Constant (mixer)

The runtime between the end positions OPEN and CLOSED is different depending on the mixer used. To achieve an optimal temperature regulation of the bivalent heat generator, the mixer runtime must be set.

1 ... 4 minutes ... 6

The hysteresis of the mixer forms the neutral zone for the operation of the bivalent heat generator. If the set temperature plus hysteresis is reached, a mixer closed signal is given. If the set temperature minus hysteresis is not reached, a mixer open signal is given

0.5 ...2K

This setting indicates the behaviour of the 2nd heat generator during a utility block (interruption of the supply voltage). Load stage 3: The 2nd heat generator is only released in load stage 3 during the utility block. On mono energy systems, the immersion heater is always blocked. Permanent: The 2nd heat generator is released during the utility block. Limit temp. dependent: The 2nd heat generator is released during the utility block if the limit temperature is also not reached.

Load stage 3 Permanent Limit temp. dependent

452117.66.20-EN · 1/2021-07 · Rei

32-76

Parameters 4.7 EVU block limit temperature 4.8 Special program
4.9 Mixer run time
4.10 Mixer hysteresis
4.11 Heating Bivalent-Renewable temperature 4.12 Heating Bivalent-Renewable
4.13 Hot water Bivalent-Renewable
4.14 Pool Bivalent-Renewable 4.15 Voltage Burner off 4.16 Voltage minimum
4.17 Voltage maximum
4.18 System temperature minimum 4.19 System temperature maximum

Operating manual Heat pump manager WPM 6.0
5 Expert level

Setting
Limit temperature for releasing the 2nd heat generator if Limit temp. dependent is set.

Setting range -10 ... 0 °C ... +10

The special program should be used for old boilers or bivalent systems with central storage systems to prevent corrosion through condensation. When the 2nd heat generator is released, it remains in operation for at least the number of hours set.
The runtime between the end positions OPEN and CLOSED is different depending on the mixer used. To achieve an optimal temperature regulation of the bivalent-renewable heat generator, the mixer runtime must be set.
The hysteresis of the mixer forms the neutral zone for the operation of the bivalent-renewable heat generator. If the set temperature plus hysteresis is reached, a mixer closed signal is given. If the set temperature minus hysteresis is not reached, a mixer open signal is given
Temperature difference between the storage renewable and flow temperature, which must be exceeded for the heat pump to be blocked if a heating request is present. Comfort: A renewable heating block is only active if the temperature in the storage renewable is higher than the current return set temperature minus hysteresis. Energy optimised: A renewable heating block is independent from the return set temperature.
Temperature difference between the storage renewable and domestic hot water temperature, which must be exceeded for the heat pump to be blocked if a domestic hot water request is present.
Temperature of the storage renewable, which must be exceeded for the heat pump to be blocked if a swimming pool request is present.

0 ... 1 hours ... 99
1 ... 4 minutes ... 6
0.5 ...2K
2 ... 10 K ... 20 Comfort / Energy opti-
mised
2 ... 5 K ... 50 10 ... 35 °C ... 50

Target value specification of a bivalent heat generator via a 0-10V signal. Setting of the voltage for burner off.

0.2 ... 2.5 V ... Voltage minimum

Setting value for the minimum voltage for the minimum system temperature
Setting value for the maximum voltage for the maximum system temperature
Setting value for the minimum system temperature at minimum voltage.
Setting value for the maximum system temperature at maximum voltage.

Voltage burner off ... 3.0 V ...
Voltage maximum
Voltage minimum ... 3.0 V ...
Voltage maximum
8 °C ... System temperature
maximum
System temperature minimum ... 80 °C

452117.66.20-EN · 1/2021-07 · Rei

33-76

Operating manual Heat pump manager WPM 6.0 5 Expert level
5.13 Heating/Cooling

Parameters 5.1 Heating hysteresis return setp. temperature
5.2 Cooling hysteresis return setp. temperature
5.3 Cooling 2.refriger. unit 5.4 Cooling limit ext. temperature 5.5 Cool. passive hysteresis 5.6 Heating room control I-portion minimal 5.7 Heating room control I-portion maximum 5.8 Heating room control ventilation reset 5.9 Cooling room control I-portion 5.10/5.11 Heating compressor 2 limit temperature
5.12/5.13 Cooling compressor 2 limit temperature

Heating/ Cooling

Setting

Setting range

The hysteresis of the return set temperature forms the neutral zone for the heating operation of the heat pump. If the "return set temperature plus hysteresis" is reached, the heat pump switches off. If the "return set temperature minus hysteresis" is reached, the heat pump switches on.

0.5 ... 2.0 K ... 5.0

The hysteresis of the return set temperature forms the neutral zonefor the cooling operation of the heat pump. If the "return set temperature minus hysteresis" is reached, the heat pump switches off. If the "return set temperature plus hysteresis" is reached, the heat pump switches on.

0.5 ... 2.0 K ... 5.0

Setting for whether a 2nd refrigerator is to be used on the installation.

No / Yes

Setting of the outside temperature, below which the cooling is stopped with reversible brine-to-water heat pump or passive cooling.
If the current cooling return set temperature minus hysteresis passive is higher than the current brine temperature, passive cooling takes place.
Settings for control with room temperature control selected during heating I * gain factor minimum number of minutes / maximum number of minutes P * gain factor (grade rule) value after voltage is restored in % between 18 °C and 50 °C

-20 ... 3 °C ... 35 0.1 ... 2.0 K ... 9.9
0 ... 4 ... 9

Reset of the room control, detection of an open window.

No / Yes

Setting of the I-portion with selected room temperature control during cooling

001 ... 060 ... 999

The limit temperature of the 2nd compressor must be selected according to the design of the heat pump heating system. Below the limit temperature of the 2nd compressor, the heat pump runs with 2 compressors for heating the building. The 2nd compressor is only switched on from temperatures below the set limit temperature parallel and load stage 2.
The limit temperature of the 2nd compressor must be selected according to the design of the heat pump heating system. Below the limit temperature of the 2nd compressor, the heat pump runs with 2 compressors for heating the building. The 2nd compressor is only switched on from temperatures below the set limit temperature parallel and load stage 2.

Limit temperature parallel
... +35 °C ... +99
15 ... +15 °C ... +99

452117.66.20-EN · 1/2021-07 · Rei

34-76

Operating manual Heat pump manager WPM 6.0 5 Expert level
5.14 Heating/cooling circuit 1

1.Heat/ cool circuit

Parameters

Setting

Setting range

6.1

The heating curve end point must be set according to the design

Heating curve end point (-20°C)

of the heat pump heating system. The maximum return set temperature must be entered here, which is determined based on the calculated maximum flow temperature, minus the temperature difference in the heating system (spread).

20 ... 30 °C ... 70

6.2

Setting the desired return set temperature with fixed value

Fixed value reg. return regulation selected

setp. temperature

min. setp. temp. ... 40 °C ... 60

6.3

Setting the desired room set temperature and the I-portion with

Room control Room setp. room temperature control selected

temperature

15.0 ... 20.0 °C ... 30.0

6.5 Return temperature minimal Heating 6.6 Return temperature minimal Heating manual

Setting the minimum return set temperature for heating operation.

If room control is activated, it is possible to select whether the min-

imum return set temperature is adapted automatically to the set manual / automatic

room set temperature.

minimum ... 20 °C ... 30

6.7 Return temperature maximum Heating 6.8 Return temperature maximum Heating manual 6.9 Return temperature maximum Heating automatic

For panel and radiator heating systems, different maximum temperatures are permitted. The upper limit of the return set temperature can be set between 25 °C and 70 °C.

manual / automatic minimum ... 50 °C ... 70
1 ... 10 K ... 20

6.10 Mixer hysteresis
6.11 Mixer run time
6.12 Room control limit temperature

The hysteresis of the mixer forms the neutral zone for the operation of heating/cooling circuit 1. If the set temperature plus hysteresis is reached, a mixer closed signal is given. If the set temperature minus hysteresis is not reached, a mixer open signal is given.
The runtime between the end positions OPEN and CLOSED is different depending on the mixer used. To achieve optimal temperature regulation in heating/cooling circuit 1, the mixer runtime must be set.
Below the set limit temperature, the rooms with a lower room set temperature are not taken into account for overheating with activated Smart-Grid function.

0.5 ... 2.0 K ... 5.0 1 ... 4 minutes ... 6 15 ... 19 °C ... 30

6.13 Room control hysteresis bottom
6.14 Room control hysteresis top

To prevent unnecessary cycling of the control valves, the hysteresis for opening and closing the control valves can be adapted to the room actual temperature depending on the room set temperature.

0.0 ... 0.3 K ... 2.0 0.0 ... 0.8 K ... 2.0

452117.66.20-EN · 1/2021-07 · Rei

35-76

Operating manual Heat pump manager WPM 6.0
5 Expert level

Parameters 06:15 Room control flow 6.16 Room control flow manual

Setting
It is possible to select whether the flow temperature required for the mixer during room control takes place automatically via the determined spread of the system, or manually via a fixed set value.

Setting range
manual / automatic 0 ... 5 K ... 10

6.17

Increase of the minimum permissible flow temperature, calculated

Silent cooling dewpoint from the measured values of room climate station 1. An increased

diff.

value reduces the risk of condensate formation.

1.5 ... 3.5 K ... 5.0

06:18 Heating M13 6.19 Heating M13 manual

Setting the speed for the electronically regulated circulating pump (M13) in heating operation.

manual Stage 1 Stage 2 Stage 3 automatic

6.20 Cooling M13 6.21 Cooling M13 manual

Setting the speed for the electronically regulated circulating pump (M13) in cooling operation

30 ... 50 % ... 100
manual Stage 1 Stage 2 Stage 3 automatic

30 ... 50 % ... 100

5.15 Heating/cooling circuit 2/3

2.Heat/ cool circuit

3.Heat/ cool circuit

Parameters

Setting

Setting range

7.1/8.1

Is the sensor for heating circuit 2/3 installed in the flow and

Temperature sensor

return? When return is set, the calculated heating circuit 2 setpoint is also used for heat pump heating request. When

Return / Flow

flow is set, only for mixer activation.

7.2/8.2 Heating curve end point (-20°C)

The heating curve end point must be set according to the design of the heat pump heating system. The maximum flow or return temperature must be entered here depending on the sensor positioning.

20 ... 30 °C ... 70

7.3/8.3 Heating curve parallel shift

Parallel shift of the set heating curve for heating circuit 2/ 3. Pressing the arrow keys once shifts the heating curve up (hotter) or down (colder) by 1K.

-19 ... 0 K ... 19

7.4/8.4 Fixed value reg. return setp. temperature/Flow setp. temperature

Setting the desired set temperature with fixed value regulation selected

min. setp. temp. ... 40 °C ... 60

7.5/7.6 8.5/8.6 Return setp. temp./Flow setp. temperature minimal Heating

Setting the minimum return set temperature for heating operation. If room control is activated, it is possible to select whether the minimum return set temperature is adapted automatically to the set room set temperature.

manual / automatic 15 ... 20 °C ... 30

452117.66.20-EN · 1/2021-07 · Rei

36-76

Operating manual Heat pump manager WPM 6.0
5 Expert level

Parameters 7.7/8.7 Return setp. temp./ Flow setp. temperature maximum Heating 7.8/8.8 Return setp. temp./ Flow setp. temperature maximum Heating manual 7.9/8.9 Return setp. temp./ Flow setp. temperature maximum Heating automatic

Setting

Setting range

For panel and radiator heating systems, different maximum temperatures are permitted. The upper limit of the set temperature can be set between 25 °C and 70 °C.

manual / automatic 30 ... 50 °C ... 70
1 ... 10 K ... 20

7.10/8.10 Mixer hysteresis
7.11/8.11 Mixer run time
7.12/8.12 Room control limit temperature

The hysteresis of the mixer forms the neutral zone for the operation of heating/cooling circuit 2/ 3. If the set temperature plus hysteresis is reached, a mixer closed signal is given. If the set temperature minus hysteresis is not reached, a mixer open signal is given.
The runtime between the end positions OPEN and CLOSED is different depending on the mixer used. To achieve optimal temperature regulation in heating/cooling circuit 2/3, the mixer runtime must be set.
Below the set limit temperature room control, the rooms with a lower room set temperature are not taken into account for overheating with activated Smart-Grid function.

0.5 ... 2.0 K ... 5.0 1 ... 4 minutes ... 6 15 ... 19 °C ... 30

7.13/8.13 Room control hysteresis bottom
7.15/8.15 Room control flow 7.16/8.16 Room control flow manual

To prevent unnecessary cycling of the control valves, the hysteresis for opening and closing the control valves can be adapted to the room actual temperature depending on the room set temperature.
It is possible to select whether the flow temperature required for the mixer during room control takes place automatically via the determined spread of the system, or manually via a fixed set value.

0.0 ... 0.5 K ... 2.0
manual / automatic 0 ... 5 K ... 10

7.17/8.17

Increase of the minimum permissible flow temperature, calculated

Silent cooling dewpoint from the measured values of room climate station 1/2. An

diff.

increased value reduces the risk of condensate formation.

1.5 ... 3.5 K ... 5.0

5.16 Domestic hot water

Parameters 9.1 Change-over compressor 2 9.2 Hysteresis
9.3 Parallel cooling hot water

Hot water

Setting
Setting of the outside temperature below which the domestic hot water preparation takes place with 2 compressors with 2 compressor heat pumps.

Setting range -30 ... -25 °C ... 35 (10)

The hysteresis of the domestic hot water set temperature forms the neutral zone which, if not reached, triggers a domestic hot water request.
Is parallel operation of cooling and domestic hot water possible due to the hydraulic decoupling of cooling circuit and domestic hot water circuit?

2 ... 7 K ... 15 No / Yes

452117.66.20-EN · 1/2021-07 · Rei

37-76

Operating manual Heat pump manager WPM 6.0
5 Expert level

Parameters 9.4 Setp. temperature 9.5 Minimum temperature
9.6 Maximum temperature 9.7 Reheating
9.8 Circulation shut-off delay 9.9 Hot water reset maximum 9.10 Maximum temperature 1 compressor 9.11 Maximum temperature 2 compressor 9.12 Hot water pump 9.13 Hot water manual

Setting Setting the desired domestic hot water set temperature.

Setting range 30 ... 50 °C ... 85

Setting the desired domestic hot water set temperature which is also to be maintained during an active domestic hot water lower time or external domestic hot water block.
Setting the desired domestic hot water set temperature to be achieved in parallel operation.

0 ... 10 °C ... Domestic hot water set
temperature
30 ... 60 °C ... 85

Setting for whether the existing flange heater should also be used for reheating. If "No" is set, the domestic hot water preparation only takes place up to the current heat pump maximum temperature depending on the heat source temperature.
The circulation pump is switched by a paddle switch, for example. When the paddle switch switches back again, the circulation pump continues to run for the set time.

No / Yes
1 ... 5 minutes ... 15

If reset Yes is set, the determined maximum domestic hot water temperatures in heat pump operation are reset to the value 65 °C. The setting value is returned automatically to No.

No / Yes

Display of the determined maximum domestic hot water temperatures depending on the heat source temperature.

Setting the speed of the electronically regulated domestic hot water circulating pump (M18).

automatic Stage 1 Stage 2 Stage 3 manual 30 ...50 %...100

5.17 Pool

Pool

Parameters 10.1 Change-over compressor 2 10.2 Hysteresis
10.3 Setp. temperature 10.4 Minimum temperature

Setting

Setting range

Setting of the outside temperature below which the swimming pool preparation takes place with 2 compressors with 2 compres- -30 ... -25 °C ... 35 (10) sor heat pumps

The hysteresis of the swimming pool set temperature forms the neutral zone which, if not reached, triggers a swimming pool request.
Setting the desired swimming pool set temperature.

0.0 ... 5 K ... 20 5 ... 25 °C ... 60

Setting the desired swimming pool set temperature, which is also

0 ... 10 °C ...

to be maintained during an active swimming pool block.

Pool set temperature

10.5 Maximum temperature
10.6 Waste heat utilisation cooling

Setting the desired swimming pool set temperature to be achieved as a maximum.
Setting for whether the waste heat recovery during cooling should take place depending on the thermostat switching state or in continuous operation.

30 ... 60°C ... 85 No / Yes

452117.66.20-EN · 1/2021-07 · Rei

38-76

Operating manual Heat pump manager WPM 6.0
5 Expert level

Parameters 10.7 Pool reset maximum
10.8 Maximum temperature 1 compressor
10.9 Maximum temperature 2 compressor
10:10 Pool pump 10:11 Pool pump manual

Setting
With the reset Yes setting, the determined maximum swimming tool temperatures in heat pump operation are reset to the value 65 °C. The setting value is returned automatically to No.

Setting range No / Yes

Display of the determined maximum swimming pool temperatures depending on the heat source temperature.

Setting the speed of the electronically regulated swimming pool circulating pump (M19).
5.18 Pump control

automatic Stage 1 Stage 2 Stage 3 manual 30 ...50 %...100

Pump control

The settings must be selected based on the system hydraulics.

Parameters

M16 function M13
Optimisation heating pump

11.2.1 Heating limit temperature 1

11.2.2 Heating limit temperature 2
11.2.3 Cooling limit temperature 1
11.2.4 Cooling limit temperature 2

Pump supply secondary pump
Pump run-on secondary pump

Setting
Should the auxiliary circulating pump M16 take over the function of the heating circulating pump M13?

Setting range Yes / No

The heating limit temperature refers to the outside temperature. Below heating limit temperature 1, the heating pump is permanently on. At temperatures between heating limit temperature 1 and 2, the heating pump runs in pump optimisation.

- 10 ... 15 °C ... Heating limit temp. 2

Above heating limit temperature 2, the heating pump is

permanently off. Above the heating limit temperature, Heating limit temp. 1 ...

the heating pump only runs with a scavenging time

25 °C ... 35

request. This results in a demand-based scavenging.

Below cooling limit temperature 1, the heating pump is permanently off. Above the cooling limit temperature, the heating pump only runs with a scavenging time request. This results in a demand-based scavenging.

- 10 ... 15 °C ... Cooling limit temp. 2

Above cooling limit temperature 2, the heating pump is

permanently on. At temperatures between cooling limit Cooling limit temp. 1 ...

temperature 1 and 2, the heating pump runs in pump

15 °C ... 35

optimisation.

Setting of the lead time of the secondary pump before the compressor starts.

10 ... 60 s ... 420

Setting of the delay time of the secondary pumps after the compressor is switched off

0 ... 5 s ... 420

452117.66.20-EN · 1/2021-07 · Rei

39-76

Operating manual Heat pump manager WPM 6.0
5 Expert level

Parameters 11.5.1 Pump function

.9

11.5.2 Pump type
11.5.3 Pump stop

.9

11.6.1 Pump function
11.6.2 Pump type 11.6.3 Pump stop

.9

11.7.1 Pump function
11.7.2 Pump type 11.7.3 Pump stop

.9

11.8.1 Pump function
11.8.2 Pump type 11.8.3 Pump stop

.9

11.9.1 Pump function
11.9.2 Pump type 11.9.3 Pump stop

.9

11.10.1 Pump function
11.10.2 Pump type 11.10.3 Pump stop

Setting

Setting range

Display/setting of which pump function is output as the -- / M11 / M12 / M13 /

control voltage on the analogue output N1/Y1

M14 / M15 / M16 / M17 /

M18 / M19 / M20 / M23 /

M24 / H5 / M2 / E10.2

Display of the pump type on analogue output N1/Y1.

0-10V

Setting of the voltage value for pump stop on the analogue output N1/Y1, see technical data from the pump manufacturer.

0.1 ... 0.7 V ... 1.0

Display/setting of which pump function is output as the -- / M11 / M12 / M13 /

control voltage on the analogue output N1/Y2

M14 / M15 / M16 / M17 /

M18 / M19 / M20 / M23 /

M24 / H5 / M2 / E10.2

Display of the pump type on analogue output N1/Y2.

0-10V

Setting of the voltage value for pump stop on the analogue output N1/Y2, see technical data from the pump manufacturer.

0.1 ... 0.7 V ... 1.0

Display/setting of which pump function is output as the -- / M11 / M12 / M13 /

control voltage on the analogue output N1/Y3

M14 / M15 / M16 / M17 /

M18 / M19 / M20 / M23 /

M24 / H5 / M2 / E10.2

Display of the pump type on analogue output N1/Y3.

0-10V PWM

Setting of the voltage value for pump stop on the analogue output N1/Y3, see technical data from the pump manufacturer.

0.1 ... 0.7 V ... 1.0 0.1 ... 99.9 % ... 99.9

Display/setting of which pump function is output as the -- / M11 / M12 / M13 /

control voltage on the analogue output N1/Y4

M14 / M15 / M16 / M17 /

M18 / M19 / M20 / M23 /

M24 / H5 / M2 / E10.2

Display of the pump type on analogue output N1/Y4.

0-10V PWM

Setting of the voltage value for pump stop on the analogue output N1/Y4, see technical data from the pump manufacturer.

0.1 ... 0.7 V ... 1.0 0.1 ... 99.9 % ... 99.9

Display/setting of which pump function is output as the -- / M11 / M12 / M13 /

control voltage on the analogue output N1/Y5

M14 / M15 / M16 / M17 /

M18 / M19 / M20 / M23 /

M24 / H5 / M2 / E10.2

Display of the pump type on analogue output N1/Y5.

0-10V

Setting of the voltage value for pump stop on the analogue output N1/Y5, see technical data from the pump manufacturer.

0.1 ... 0.7 V ... 1.0

Display/setting of which pump function is output as the -- / M11 / M12 / M13 /

control voltage on the analogue output N1/Y6

M14 / M15 / M16 / M17 /

M18 / M19 / M20 / M23 /

M24 / H5 / M2 / E10.2

Display of the pump type on analogue output N1/Y6.

0-10V

Setting of the voltage value for pump stop on the analogue output N1/Y6, see technical data from the pump manufacturer.

0.1 ... 0.7 V ... 1.0

452117.66.20-EN · 1/2021-07 · Rei

40-76

Operating manual Heat pump manager WPM 6.0
5 Expert level

Parameters 11.11.1 Pump function

.9

11.11.2 Pump type
11.11.3 Pump stop

.9

11.12.1 Pump function
11.12.2 Pump type 11.12.3 Pump stop

.9

11.13.1 Pump function
11.13.2 Pump type 11.13.3 Pump stop

.9

11.14.1 Pump function
11.14.2 Pump type 11.14.3 Pump stop

Setting

Setting range

Display/setting of which pump function is output as the -- / M11 / M12 / M13 /

control voltage on the analogue output N17.1/Y1

M14 / M15 / M16 / M17 /

M18 / M19 / M20 / M23 /

M24 / H5 / M2

Display of the pump type on analogue output N17.1/Y1.

0-10V

Setting of the voltage value for pump stop on the analogue output N17.1/Y1, see technical data from the pump manufacturer.

0.1 ... 0.7 V ... 1.0

Display/setting of which pump function is output as the -- / M11 / M12 / M13 /

control voltage on the analogue output N17,2/Y1

M14 / M15 / M16 / M17 /

M18 / M19 / M20 / M23 /

M24 / H5 / M2

Display of the pump type on analogue output N17.2/Y1.

0-10V

Setting of the voltage value for pump stop on the analogue output N17.2/Y1, see technical data from the pump manufacturer.

0.1 ... 0.7 V ... 1.0

Display/setting of which pump function is output as the -- / M11 / M12 / M13 /

control voltage on the analogue output N17,3/Y1

M14 / M15 / M16 / M17 /

M18 / M19 / M20 / M23 /

M24 / H5 / M2

Display of the pump type on analogue output N17.3/Y1.

0-10V

Setting of the voltage value for pump stop on the analogue output N17.3/Y1, see technical data from the pump manufacturer.

0.1 ... 0.7 V ... 1.0

Display/setting of which pump function is output as the -- / M11 / M12 / M13 /

control voltage on the analogue output N17,4/Y1

M14 / M15 / M16 / M17 /

M18 / M19 / M20 / M23 /

M24 / H5 / M2

Display of the pump type on analogue output N17.4/Y1.

0-10V

Setting of the voltage value for pump stop on the analogue output N17.4/Y1, see technical data from the pump manufacturer.

0.1 ... 0.7 V ... 1.0

5.19 Outputs

Parameters 12.1 Compressor 1
12.2 Compressor 2
12.3 Fan/M11
12.4 M11 Primary pump
12.5 Internal 4-way valve

Outputs
Description

452117.66.20-EN · 1/2021-07 · Rei

41-76

Operating manual Heat pump manager WPM 6.0
5 Expert level
12.6 Nozzle ring heating
12.7 M16 Add. circulation pump
12.8 Y12 External 4-way valve
12.9 H5 Remote fault indicator
12:10 M12 Primary pump cooling mode
12:11 M17 Cool. circulation pump
12:12 Y5 3-way valve
12:13 E10.1 Immersion heater
12:14 M21 Mixer Bivalent
12:15 M21 Mixer renewable
12:16 M13 Heating circulation pump
12:17 M21 Mixer 2.Heat circuit
12:18 M15 Heating circulation pump
12:19 M22 Mixer 2.Heat circuit
12:20 M20 Heating circulation pump
12:21 M21 Mixer 3.Heat circuit
12:22 N9 Room thermostat
12:23 E13 2.Refrig. unit
12:24 M18 Hot water pump
12:25 E9 Flange heating
12:26 M24 Circulation pump
12:27 M19 Pool pump

452117.66.20-EN · 1/2021-07 · Rei

42-76

Operating manual Heat pump manager WPM 6.0 5 Expert level
5.20 Inputs

Inputs

Parameters 13.1 Pressure stat Low pressure

Description
Low pressure contact open = error (Setting low pressure switch NC contact)

13.2 Pressure stat High pressure

High pressure contact open = error (Setting high pressure switch NC contact)

13.3 Pressure stat Defrost

Contact closed = defrost end

13.4 Brine press. switch

Contact open = error

13.5 Throughput switch primary

Contact open = error

13.6 Throughput switch secondary

Contact open = error

13.7 Thermostat Hot gas

Contact open = error

13.8 Thermostat Freeze protection

Contact open = error

13.9 Thermostat Hot water

Contact closed = domestic hot water demand

13:10 Thermostat Pool

Contact closed = swimming pool demand

13:11 Motor protect. compressor

Contact open = error

13:12 Motor protect. primary pump

Contact open = error

13:13 Motor protect. fan

Contact open = error

13:14 EVU block

Contact open = utility company block

13:15 External block

Contact open = external block

13:16

Contact closed = circulation pump demand

Demand circulation pump

452117.66.20-EN · 1/2021-07 · Rei

43-76

Parameters 14.1 Quick start
Parameters 14.2 Switch off UEG
Parameters 14.3 Commissioning mode

Operating manual Heat pump manager WPM 6.0 5 Expert level
5.21 Special functions
5.21.1 Quick start

Special functions

Quick start

Setting

Setting range

Activating the "quick start" function means that the heat pump can start after the safety-relevant times have elapsed. A switch cycle block is ignored.

No / Yes

5.21.2 Switch off lower operating limit

Special functions

Switch of UEG

Setting

Setting range

Activating the "Switch off lower application limit" function means that the heat pump can start after the safety-relevant times have elapsed. The monitoring for compliance with the lower operating limit is switched off.

No / Yes

5.21.3 Commissioning

Special functions

Commissioning

Setting

Setting range

When this function is activated, the defrost with air-to-water heat pumps is suppressed for one hour and the 2nd heat generator is released. If a defrost process is already running, it is cancelled.

No / Yes

452117.66.20-EN · 1/2021-07 · Rei

44-76

Operating manual Heat pump manager WPM 6.0 5 Expert level
5.21.4 System check

Parameters 14.4 System check
14.4.1 Output M11 14.4.2 Output M18 14.4.3 Output M24
14.4.4 Output M13/M15/M16
14.4.5 Mixer M21/M22

Special functions

System check

Setting System control on pumps and mixers

Setting range

When this function is activated, the pumps on the primary side are switched on permanently for a period of 24 hours. The heat pump remains blocked during this time.

No / Yes

When this function is activated, the mixers are first switched to the OPEN direction for the set mixer runtime, and then to CLOSED.
5.21.5 Screed program

No / Yes

Parameters

Special functions
Setting

Screed drying

Setting range

15.1 Maximum temperature

Setting of the maximum return temperature to be achieved during initial heating.

15.2 Hot water/ Pool

If this function is selected, a potential domestic hot water or swimming pool demand is permitted during the initial heating.

15.3 Function heating

Activation of the heating function program.

15.4 Standard program line heating

Activation of the standard program for screed drying

15.5 Individual program line heating

15.5.1 Heat-up duration

Setting the duration for the individual steps of the heat-up phase.

15.5.2 Hold duration

Setting the hold time.

15.5.3

Setting the duration for the individual steps of the cool-down phase.

Duration Cool down

25 ... 35 °C ... 50 No / Yes No / Yes No / Yes
1 ... 24 ... 120 1 ... 24 ... 480 1 ... 24 ... 120

452117.66.20-EN · 1/2021-07 · Rei

45-76

Operating manual Heat pump manager WPM 6.0
5 Expert level

Parameters

Setting

Setting range

15.5.4

Setting the temperature difference between two steps in the heat-

Differential

up phase.

temperature heat-up

1 ... 5K ... 10

15.5.5 Differential temperature Cool down

Setting the temperature difference between two steps in the cooldown phase.

1 ... 5K ... 10

15.5.6 Individual program line heating

Activation of the individual program for screed drying

No / Yes

5.21.6 Function check

Parameters 14.5 Function check
14.5.1 Function check
14.5.2 Activation time
14.5.3 Run time

Special functions

Function check

During the function check, the connected actuators (pump, mixer, etc.) can be switched manually for testing purposes. The function check is active for a set activation time. The actuators are active for the set runtime. If a function check is activated, the actuators can be switched manually in the Outputs menu.

Setting Function for the installer

Setting range

Activating this function activates a function check for a selectable number of minutes. During this time, individual output functions can be activated in the Outputs menu. The heat pump remains blocked during this time.

No / Yes 1 ... 30 minutes ... 60

1 ... 10 seconds ... 99

5.22 Installation

Parameters 16.1 Flex input ID1 + ID2
16.2 Flex input ID4

Installation

Setting

Setting range

Is the digital input ID1 + ID2 used? What function should be assigned to this input?

Thermostat Load stage Smart-Grid

Is the digital input ID4 used? What function should be carried out when this input is opened?

Frost protection Holiday
Hot water block Summer operating
mode

452117.66.20-EN · 1/2021-07 · Rei

46-76

Operating manual Heat pump manager WPM 6.0 6 Commissioning assistant
6 Commissioning assistant

Commissioning

The commissioning assistant guides you automatically through the settings of all system settings relevant for operation. The menu items available for selection are based on the heat pump type used and hardware. The commissioning assistant must be run through entirely and completed. It is not possible to cancel the process during the commissioning!

Parameters Language

Description
Setting the desired language. Depending on the software version, not all languages listed may be available.

Heat pump code Functions

The 4-digit heat pump code printed on the type plate can be corrected with these settings.
The setting for the desired function should be selected based on the system hydraulics. Note, the function direct circuit and mixer circuit 1 are mutually exclusive. The maximum possible number of available functions is dependent on the hardware used

Function blocks The colour assignment of the function must be selected based on the functions wired on the controller.

Setting range
Deutsch English Français Nederlands Italiano Svenska Dansk Magyar Ceský Slovenský Hrvatski Slovenski Norsk
Domestic hot water Direct circuit Mixer circuit 1 Mixer circuit 2 Mixer circuit 3 Bivalent Renewable
Swimming pool Active cooling Passive cooling
Yellow Green Red ------------

To assign a function to the function blocks "Blue" and "Orange", the extension

controller WPM 6.0 with two function blocks is required.

2.heat generator Is a pipe heater installed in the system hydraulics? Is an immersion heater installed in the buffer, which is used for heating

support?

Hot water Demand

Does domestic hot water preparation take place with the heat pump? Is a thermostat or a sensor used for this?

Hot water

Is a pipe heater installed in the system hydraulics, which can be used for

2.heat generator hot water reheating?

Is a flange heater installed in the domestic hot water cylinder for reheating and thermal disinfection?

Hot water

Is a circulation pump in place and is it actuated via the heat pump manager?

circulation

Is it actuated via an impulse or a time function?

1.Circuit

How is heating circuit 1 used?

Blue Orange
Pipe heater Immersion heater
Sensor Thermostat
Pipe heater Flange heater
Impulse time
Heating Cooling

452117.66.20-EN · 1/2021-07 · Rei

47-76

Operating manual Heat pump manager WPM 6.0
6 Commissioning assistant

Parameters 1.Heat circuit control
1.Heat circuit room control
1.Cool circuit control
1.Cool circuit room control 1.Circuit number RTM Econ 2.Circuit
2.Heat circuit control
2.Heat circuit room control 2.Cool circuit control 2.Cool circuit room control 2.Circuit number RTM Econ 3.Circuit
3.Heat circuit control
3.Heat circuit Room controller

Description Which regulation option is to be used for heating circuit 1? · Outside: Return temperature control depending on the outside tempera-
ture and set heating curve · Fixed-setpoint: Return temperature control via a fixed-setpoint · Room temperature: Return temperature control depending on the room
temperature of a reference room What hardware is used for the room control heating?
Which regulation option is to be used for cooling circuit 1? · Fixed-setpoint: Return temperature control via a fixed-setpoint · Silent cooling: Return temperature control depending on the room
temperature of a reference room What hardware is used for the room control cooling?
How many RTM Econ are used for circuit 1?
How is heating circuit 2 used?
Which regulation option is to be used for heating circuit 2? · Outside: Return temperature control depending on the outside
temperature and set heating curve · Fixed-setpoint: Return temperature control via a fixed-setpoint · Room temperature: Return temperature control depending on the room
temperature of a reference room What hardware is used for the room control heating?
Which regulation option is to be used for cooling circuit 2? · Silent cooling: Return temperature control depending on the room
temperature of a reference room What hardware is used for the room control cooling?
How many RTM Econ are used for circuit 2?
How is heating circuit 3 used?
Which regulation option is to be used for heating circuit 3? · Outside: Return temperature control depending on the outside
temperature and set heating curve · Fixed-setpoint: Return temperature control via a fixed-setpoint · Room temperature: Return temperature control depending on the room
temperature of a reference room What hardware is used for the room control heating?

Setting range
Outside Fixed-setpoint Room temperature
RTM Econ RTH ECon
R13 BMS
Fixed-setpoint Silent cooling
RTM Econ RKS BMS
1 ... 10
Heating Cooling
Outside Fixed-setpoint Room temperature
RTM Econ BMS
Silent cooling
RTM Econ BKS BMS
1 ... 10
Heating Cooling
Outside Fixed-setpoint Room temperature
RTM Econ BMS

452117.66.20-EN · 1/2021-07 · Rei

48-76

Operating manual Heat pump manager WPM 6.0
6 Commissioning assistant

Parameters 3.Cool circuit control 3.Cool circuit room control 3.Circuit number RTM Econ
Pool Demand Cooling 4-way valve
Function M16

Description Which regulation option is to be used for cooling circuit 3? · Silent cooling: Return temperature control depending on the room
temperature of a reference room What hardware is used for the room control cooling?
How many RTM Econ are used for circuit 3?

Setting range
Silent cooling
RTM Econ RKS BMS
1 ... 10

Does swimming pool heating take place with the heat pump? Is a thermostat or a sensor used for this?

Sensor Thermostat

Is a 2nd refrigerator used in the installation?

2nd refrigerator

Is an external 4-way valve installed in the system hydraulics for optimized heating and cooling operation? What function is the 4-way valve used for?

Without 4-way valve (cooling and heating)
With 4-way valve (cooling and heating) Without 4-way valve
(heating)

What function is the auxiliary circulating pump used for in the system hydraulics?

Heating Cooling Domestic hot water
Pool 2nd heat generator
Renewable

452117.66.20-EN · 1/2021-07 · Rei

49-76

Operating manual Heat pump manager WPM 6.0 7 Energy-efficient operation
7 Energy-efficient operation
If heating operation takes place depending on the outside temperature, the heat pump manager calculates a return set temperature from the set heating characteristic curve and the current outside temperature. The heating curve should be set to the calculated maximum return temperature of the heating
system. Via the plus and minus keys, the heating curve can be moved up or down in parallel on a customer-specific basis to achieve the actual desired room temperatures.

Regulation via the return temperature
Regulating a heat pump heating system via the return temperature has the following advantages: 1) Long runtimes of the heat pump with demand-based heating of the entire circulated heating
volume. 2) Recording of the disturbance variables of the heating system. 3) Reducing the temperature spread results in lower flow temperatures with a constant return
temperature, thus achieving a more efficient operation.
TIP
The heating curve should be set as high as necessary and as low as possible!

7.1 Outside temperature-dependent heating curve
The heating curve must be adapted to the local and structural conditions - separately for heating circuits 1, 2 and 3 - so that the desired room temperature is achieved even with changing outside temperatures. If the outside temperature rises, the return set temperature is lowered, thus ensuring energy-efficient operation of the heating system.
1) In the settings, the maximum required return temperature is entered at ­20 °C outside temperature. The goal is to achieve an average, constant room temperature even with changing outside temperatures.
2) All heating characteristic curves meet at an outside temperature of +20 °C and a return temperature of +20 °C, so that heat output is no longer required in this operating point. The bar display (plus and minus keys) can be used to shift this operating point between 5 °C and 30 °C along the inclined marked axis. This shifts the entire heating curve in parallel upwards or downwards by a constant value of 1K per bar unit. The user can carry out this setting according to their individual desired temperature.
3) Each heating curve is limited by the maximum set value. Each heating curve has a lower limit of 18 °C (air-to-water HP) or 15 °C (brine or water-to-water HP).

60
Heating curve parallel shift (warmer) with 55
heating curve maximum 50°C 50
Heating curve e.g. radiators
45

40

35

Heating curve 30 e.g. underfloor
25 Heating curve parallel shift (colder)
20

15

Return set temperature
in °C

10

5

0

-20

-15

-10

-5

Colder 5

Warmer 30
25 20 15 10

0

5

10

15

20

25

30

35

40

Outside temperature in °C

452117.66.20-EN · 1/2021-07 · Rei

50-76

Operating manual Heat pump manager WPM 6.0
7 Energy-efficient operation

7.1.1 Setting examples
Standard outside air temperature °C Required flow temperature (with standard design temperature) Temperature spread flow/return Required return temperature (with standard design temperature) Setting for heating curve end point

Underfloor heating 35 °C / 28 °C
-12 -14 -16

Radiators 55 °C / 45 °C
-12 -14 -16

35 °C 35 °C 35 °C 55 °C 55 °C 55 °C

7 °C 7 °C 7 °C 10 °C 10 °C 10 °C

28 °C 28 °C 28 °C 45 °C 45 °C 45 °C

30 °C 29 °C 29 °C 48 °C 47 °C 46 °C

Example 1

Example 2

A heat distribution system (e.g. underfloor heating) is designed for a maximum flow temperature with a specific standard outside temperature. This is dependent on the location of the heat pump and is between -12 and -18 °C in Germany.
The max. return temperature to be set on the heating controller must be entered with an outside temperature of ­20 °C. For this, the maximum return temperature with the specified standard outside temperature in Abb. auf S. 51 must be entered. Via the array of curves, the setting value at -20 °C can be read.
Step 1: Adjustment of the heating curve to local and structural conditions by setting the gradient (heating curve end point) Step 2: Setting of the desired temperature level through parallel shifting of the heating curve up or down (bar display)

Heating curves

62

60

58

56 E.g.2: Heating curve 54 end point 48°C 52
50 48 46

E.g.1: Return with standard outside temp. 45°C

Return set temperature
in °C

44

42

40

38

E.g.1: 36 Heating curve 34 end point 29°C 32
30
28

E.g.1: Return with standard outside temp. 28°C

26

24

22

20 -20 -18 -16 -14 -12 -10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18 20 22

E.g.1: Standard design temperature -16°C

E.g.2: Standard design temperature -12°C

External wall temperature in °C

452117.66.20-EN · 1/2021-07 · Rei

51-76

If
too cold too hot

Operating manual Heat pump manager WPM 6.0
7 Energy-efficient operation

7.1.2 Optimisation of the heating curve

There are two setting options for optimising the heating curve:

 Changing the gradient with a higher or lower "heating curve end point"  Raising or lowering the entire heating curve with the plus and minus keys

outside temperature

below -7 °C

-7 to +7 °C

"Heating curve end point" value 2 °C Plus

to 3 °C higher

1 °C to 2 °C scale markings higher

"Heating curve end point" value 2 °C Minus

to 3 °C lower

1 °C to 2 °C scale markings lower

over +7 °C
Plus 1 °C to 2 °C higher and value "Heating curve end point" 2 °C to 3 °C lower
Minus 1 °C to 2 °C scale markings lower and value "Heating curve end point" 2 °C to 3 °C higher

7.2 Room temperature control
With highly insulated houses and open design in particular, or when heating individual large rooms, the calculation of the return set temperature can take place via the room temperature of a reference room.
Control behaviour
The larger the deviation between the room and the room set temperature, the faster the return set temperature is adapted.
Where necessary, the response time can be changed via the adjustable interval value (I-value). The larger the interval value, the slower the adjustment of the room set temperature.
The minimum return set temperature adjusts automatically to the set room temperature. If this is not desired, there is the option of switching from "automatic" to "manual" in the menu "Heat circuit - Return temperature minimal".
Requirements:
 For systems with silent cooling, the room climate station or reference room modulator RTH Econ/RTM Econ is used for room temperature recording. For all others, an additional room sensor (R13) must be connected on the analogue input X3/R13.
 Deactivation of an existing individual room control in the reference room
 The required return temperature is recommended as an input for a maximum return set temperature with standard design temperature.
 Even room set temperature, mostly free from increases and decreases
When the room temperature control is activated or the room set temperature is changed, the room temperature may initially be overshot.

452117.66.20-EN · 1/2021-07 · Rei

52-76

Operating manual Heat pump manager WPM 6.0
8 Domestic hot water preparation

7.2.1 Setting examples

Recommended settings for room set temperature 22 °C
Surface heating (35/28 °C) (underfloor, wall, ceiling
Low temperature radiators (45/38 °C)
Radiators (55/45 °C)

Minimum return temperature
22 °C 25 °C 30 °C

Maximum return temperature
30 °C 40 °C 50 °C

For optimal regulation, the regulation range between the minimum and maximum return temperature should be as small as possible. The automatic operating mode switching enables the heating operation to be blocked from a selectable outside temperature.

7.2.2 Optimisation of the room temperature control

1st measure

Building too warm

Reduce the room set temperature

Building not getting warm

Increase the room set temperature, Increase the volume flow

Reference room warm, individual rooms (e.g. bathroom) too cold

Hydraulic alignment (reduce volume flow in the reference room)

Reference room not reaching the room set Hydraulic alignment (increase volume temperature, individual rooms (e.g. bathroom) flow in the reference room) are warm

2nd measure
Increase the maximum return temperature
Increase the maximum return temperature

7.3 Fixed value regulation
For special cases (e.g. charging a buffer to constant temperature), an outside temperaturedependent characteristic curve can be set. When the room temperature control is activated or the room set temperature is changed, the room temperature may initially be overshot.

8 Domestic hot water preparation
For domestic hot water preparation, domestic hot water cylinders with sufficiently large heat exchange surfaces must be used, that are able to transfer the maximum heat output of the heat pump permanently.
The regulation takes place via a sensor (R3) installed in the domestic hot water cylinder, which is connected to the heat pump manager.
The achievable temperatures in pure heat pump operation are below the maximum flow temperature of the heat pump.
For higher domestic hot water temperatures, the heat pump manager offers the option of actuating a flange heater.
Alternatively, regulation can take place via a thermostat. In this application, targeted reheating via a flange heater is not possible.

452117.66.20-EN · 1/2021-07 · Rei

53-76

Operating manual Heat pump manager WPM 6.0 8 Domestic hot water preparation
8.1 Basic heating
A domestic hot water request is detected if the current domestic hot water temperature is < domestic hot water set temperature - domestic hot water hysteresis.
A domestic hot water request is ended if the domestic hot water set temperature or the heat source-dependent determined heat pump maximum temperature is reached.
The domestic hot water preparation can be interrupted by defrosting or by the high pressure protection program.

Menu Preconfiguration Preconfiguration

Submenu Domestic hot water preparation
Flange heater

Setting Yes with sensor
No

8.1.1 Achievable domestic hot water temperatures
The maximum domestic hot water temperature that can be achieved in pure heat pump operation depends on:
 The heat output of the heat pump
 The the heat exchanger surface installed in the cylinder
 The volume flow depending on the pressure drop and delivery rate of the circulating pump.

8.1.2 Heat source-dependent domestic hot water temperatures
The heat pump manager automatically determines the maximum possible domestic hot water temperature, referred to as the heat pump maximum temperature.
The heat pump maximum temperature is also dependent on the current temperature of the heat source air, brine or water. To ensure that the maximum possible domestic hot water temperature is always achieved, the permissible range of the heat source temperature is divided into temperature ranges. A specific heat pump maximum temperature is assigned to each range, each heat pump maximum temperature is set to 65 °C as the default value.
If the high pressure switch is triggered during domestic hot water preparation with the heat pump, the current heat source temperature is recorded and the corresponding heat pump maximum temperature is determined as follows: 1 K is deducted from the current measured domestic hot water temperature and saved as the heat pump maximum temperature.

452117.66.20-EN · 1/2021-07 · Rei

54-76

Operating manual Heat pump manager WPM 6.0
8 Domestic hot water preparation

Menu Preconfiguration Preconfiguration
Settings

8.2 Reheating

Reheating means that the heat pump takes over the domestic hot water preparation until the heat pump maximum temperature is reached. Another heat generator then takes over the domestic hot water preparation until the desired domestic hot water set temperature is reached. Reheating is only activated if the desired set temperature is higher than the current heat pump maximum temperature.

Reheating is started if
 the domestic hot water temperature is higher than the maximum temperature that can be achieved with the heat pump.
If the domestic hot water temperature falls below the domestic hot water set temperature hysteresis hot water during reheating, the reheating is stopped and basic heating is started via the heat pump.

The selection of the relevant heat generator for the domestic hot water generation depends on the mode of operation of the heat pump heating system, the configurations and the current statuses of the system.

The reheating must be released in the menu "Settings ­ Hot water reheating".

Submenu Domestic hot water preparation
Flange heater Domestic hot water reheating

Setting Yes with sensor
Yes Yes

8.3 Thermal disinfection
A start time is specified for thermal disinfection. When the thermal disinfection is started, the system immediately attempts to reach the set temperature. The selection of the heat generator used for this depends on the mode of operation of the heat pump heating system, the configurations and the current statuses of the system. Thermal disinfection is ended when the set temperature is reached.
For the thermal disinfection setting menu to be released, a bivalent heating system and/or flange heater must be set with "Yes" in the preconfiguration.
If the set temperature is not reached after 4 hours, the thermal disinfection is cancelled. The set start time can be activated or deactivated individually for each weekday.

8.4 Domestic hot water lower time
A domestic hot water lower time can be set for two different times and weekdays. Despite a domestic hot water lower time, a minimum domestic hot water temperature can be defined for comfort purposes. The minimum domestic hot water temperature is always maintained during a domestic hot water block. A domestic hot water request takes place if the minimum domestic hot water temperature hysteresis is not reached.

452117.66.20-EN · 1/2021-07 · Rei

55-76

Operating manual Heat pump manager WPM 6.0 9 Program description
9 Program description
9.1 Limit temperature
The outside temperature at which the heat pump just covers the heat consumption is known as limit temperature 2nd heat generator or bivalence point. This point is marked by the transition from pure heat pump operation to bivalent operation together with immersion heater or boiler.
The theoretical bivalence point can deviate from the optimal point. Particularly in transition periods (cold nights/ warm days), a lower bivalence point can reduce the energy consumption according to the wishes and habits of the operator. Therefore, a limit temperature for releasing the 2nd heat generator can be set in the menu "2. heat generator ­ Limit temperature".
Usually, the limit temperature is only used with mono energy systems with air-to-water heat pumps or with bivalent systems in combination with boilers.
In mono energy operation, a limit temperature of ­5 °C is strived for. The limit temperature is determined from the outside temperature-dependent building heat consumption and the heat pump heat output curves.
9.2 Blocking requests
Different statuses and settings can result in the heat pump request being blocked. The indicated blocks are reset automatically or are removed once they have been addressed.
9.2.1 Utility block
The utility company (Energie-Versorgungs-Unternehmen - EVU) can make a temporary switch off of the heat pump a condition for low-cost electricity tariffs. During a utility block, the voltage on terminal X3/A1 is interrupted.
For systems without utility block, the link cable provided must be inserted on the relevant terminal points.
The utility block is set in the menu "2. heat generator ­ EVU block".
With bivalent systems, different responses to a utility block are possible:
Load stage 3 only
Heat pump blocked, the 2nd heat generator is only released in load stage 3.
Permanent:
The 2nd heat generator is always released in the event of a heat request during a utility block.
Limit temperature dependent
Heat pump blocked, the 2nd heat generator is released below the selectable limit temperature EVU3.
For mono energy and monovalent systems, the 2nd heat generator is generally blocked during a utility block. The setting for the utility block is hidden.
For an external heat pump operation block that does not reset automatically after max. 2 hours, the external disable contactor (contact X3/A2) must be used. If the minimum permissible return temperature is not met, the heat pump is also released when a blocking signal is present.

452117.66.20-EN · 1/2021-07 · Rei

56-76

Operating manual Heat pump manager WPM 6.0 9 Program description
9.2.2 Line load
The line switch-on load is a requirement of the utility companies. It can last for up to 200 seconds after the voltage is restored or after utility block. The line load can not be bypassed.
9.2.3 Minimum pause time
To ensure adequate pressure compensation in the refrigeration circuit and to protect the heat pump, it can take up to 5 minutes to switch on the compressor again. The heat pump starts after the minimum pause time has elapsed in order to fulfil a pending demand. The minimum pause time can not be bypassed.
9.2.4 Switch cycle block
According to the connection conditions of the utility companies, the heat pump may only switch on 3 times per hour. The heat pump manager will therefore only allow a switch-on every 20 minutes as a maximum.
9.3 2nd heat generator
9.3.1 Control of immersion heaters
In mono energy systems, electrical additional heating systems are used. They are switched on or off depending on the heat consumption requirements, if "mono energy" operating mode is selected in the preconfiguration menu and the set limit temperature is not met.
9.3.2 Control pipe heating
An electrical pipe heating can be used in mono energy systems. The electrical pipe heating is selected in "Preconfiguration - Electric heating - Pipe heating Heating/DHW/SP" and switched on or off based on demand in heating, domestic hot water or swimming pool mode.
9.3.3 Constant control boiler
With this type of boiler, the boiler water is constantly heated to a fixed set temperature (e.g. 70 °C) if a release from the heat pump manager is in place. The set temperature must be set high enough that the domestic hot water preparation can also take place via the boiler if necessary. The mixer is controlled by the heat pump manager, which issues a request to the boiler as necessary and adds enough hot boiler water to reach the desired return set temperature or domestic hot water temperature. The boiler is requested via the output 2nd heat generator of the heat pump manager and the operating mode of the 2nd heat generator must be coded to "constant".

452117.66.20-EN · 1/2021-07 · Rei

57-76

Operating manual Heat pump manager WPM 6.0 9 Program description
9.3.4 Sliding control boiler
In contrast to a constant control boiler, the sliding control boiler delivers the heating water temperature to match the outside temperature directly. The 3-way reversing valve has no control function and is only responsible for guiding the heating water flow past the boiler circuit or through the boiler depending on the operating mode.
In pure heat pump operation, the heating water is directed past the boiler to avoid losses due to the heat emission of the boiler. If a weather-compensated burner regulation is already in place, the power supply for the burner regulation must be interrupted during exclusive heat pump operation. For this, the control of the boiler must be connected to the output 2nd heat generator of the heat pump manager and the operating mode of the 2nd heat generator must be coded to "sliding". The characteristic curve of the burner regulation is set according to the heat pump manager.
9.3.5 Special program for older boilers and central storage systems
If a request was issued to the second heat generator and the special program is activated in the menu "2. heat generator", the 2nd heat generator remains in operation for at least 30 hours. If the heat consumption reduces in this time, the second heat generator enters "standby mode" (2nd heat generator connected to voltage, but mixer CLOSED). It is only switched off completely if no request is issued for the 2nd heat generator or 30 hours.
This function can be used for bivalent systems as follows: 1. With older oil or gas boilers to prevent corrosion damage due to frequent dropping below
the dew point. 2. With central storage systems so that the storage charging is guaranteed for the following
day irrespective of the current heat consumption.
9.3.6 Bivalent-parallel
In "2. heat generator", the "Limit temperature parallel" is defined. If the limit temperature parallel is not met, a parallel request is sent to the heat pump and the 2nd heat generator if required.
9.3.7 Bivalent-alternative
In the menu "2. heat generator", the "Limit temperature alternative" is defined. If the limit temperature alternative is not met, the heat pump is blocked and the 2nd heat generator is released for both heating and domestic hot water preparation.
If alternative operation rather than parallel is always desired, the limit temperatures alternative and parallel must be given the same value.
9.3.8 Bivalent-renewable
When integrating a renewable heat source (e.g. solar, wood), it must be given priority over heat pump operation. To this end, bivalent-renewable is coded in the preconfiguration. While the renewable storage is cold, the system behaves like a mono energy system.
The sensor of the renewable storage is connected to analogue input N1-B8. The mixer outputs of the bivalence mixer are active.
For heat pumps without an integrated flow sensor, one must be retrofitted (N1-B5).

452117.66.20-EN · 1/2021-07 · Rei

58-76

Operating manual Heat pump manager WPM 6.0 9 Program description
Basic function:
The temperature in the renewable storage is recorded and compared with the flow temperature of the relevant request (domestic hot water, heating or swimming pool). If the temperature is higher than the conditions listed below, the heat pump is blocked, the renewable storage is used as a 2nd heat generator and the bivalence mixer is controlled accordingly.
Block by heating request:
If the temperature in the storage is 2-20 K higher than the current flow temperature, the heat pump is blocked in the event of a heating request. It is only released again when the difference between the renewable storage and the flow is less than half of the switching value.
For solar integrations, the selectable overtemperature must be set to the maximum value to prevent the heat pump from cycling.
Block by domestic hot water request:
If the temperature in the storage is 2-5 K higher than the current domestic hot water temperature, the heat pump is blocked in the event of a domestic hot water request. It is only released again when the difference between the renewable storage and the domestic hot water is less than half of the switching value.
Block by swimming pool request:
If the temperature in the storage is higher than 35 °C (value can be set in the menu - Settings - 2. heat generator overtemperature of 10­50 °C), the pump is blocked in the event of a swimming pool request. It is only released when the temperature in the parallel buffer is 5K below the switching temperature again.
As soon as one of the three blocks outlined above is in place, the heat pump is blocked and the display shows: HP waiting, block BR. The output 2nd heat generator is not actuated.
Mixer control:
If no bivalent-renewable block is in place, the mixer is controlled permanently CLOSED.
If a bivalent-renewable block is in place due to domestic hot water or swimming pool, the mixer is controlled permanently OPEN.
If a bivalent-renewable block due to heating is in place, the mixer regulation is active.
9.4 Power control
The heat pump manager defines a maximum of 3 load stages, L1, L2 and L3, which it switches depending the heat consumption. If the heat consumption rises, it switches to the next highest load stage and if the heat consumption falls, it switches to the next lowest load stage.
L1: Heat pump runs with one compressor
L2: Heat pump runs with two compressors
L3: Heat pump runs and 2nd heat generator is active (not with monovalent systems)
 After commissioning or after a power failure, the heat pump manager always starts in load stage L1.
 The load stages are not redefined during defrosting, swimming pool preparation, domestic hot water request, or during a utility block.

452117.66.20-EN · 1/2021-07 · Rei

59-76

Load stage Stage L1 Stage L2 Stage L3
Defrost Hot water heating
Swimming pool heating

Operating manual Heat pump manager WPM 6.0
9 Program description

9.4.1 Heat pumps with one compressor
Criteria for switching:
 from L1 to L3, if the heat pump manager requests "more heat" for longer than 60 minutes and, at the same time, the outside temperature is below the limit temperature of the 2nd heat generator for longer than 60 minutes
 from L3 to L1, if the heating controller requests "less heat" for longer than 15 minutes or the limit temperature is exceeded.
9.4.2 Heat pumps with two compressors
Criteria for switching:
 from L1 to L2, if the heat pump manager requests "more heat" for longer than 25 minutes,
 from L2 to L3, if the heat pump manager requests "more heat" for longer than 60 minutes and, at the same time, the outside temperature is below the limit temperature for longer than 60 minutes,
 from L3 to L2 or L1, if the heat pump manager requests "less heat" for longer than 15 minutes or the limit temperature is exceeded,
 from L2 to L1, if the heat pump manager requests "less heat" for longer than 15 minutes.
In load stage L1, a compressor of the heat pump is switched on or off according to the "more" or "less" signals of the heat pump manager. In stage L2, a compressor of the heat pump runs constantly to cover the basic load. The second compressor is switched on or off in accordance with the "more" or "less" signals of the heat pump manager. In stage L3, both compressors run constantly to cover the increased basic load, the second heat generator is regulated. There is only ever one compressor running during defrosting.

Heat pump with one compressor

Heat pump with two compressors

only one compressor cycling

only one compressor cycling

-

1 compressor basic load, 1 compressor cycling

one compressor and second heat both compressors and second heat generator generator if necessary

Compressor running

One compressor running

Compressor running

One or two compressors are running depending on the outside temperature

Compressor running

One or two compressors are running depending on the outside temperature

9.4.3 High temperature air-to-water heat pumps
With outside temperatures over 10 °C, there is generally only 1 compressor running. If the outside temperature is below 10 °C and the flow temperature is higher than 50 °C, both compressors are released:
Compressor 1 is switched on first, followed shortly after by compressor 2. If the request disappears or a block becomes active, both compressors are switched off at the same time.
With regard to the load stage, the high temperature heat pump behaves like a 1-compressor heat pump in this temperature range, regardless of the selection in the Configuration menu, i.e. there is no load stage 2.
If the outlined conditions for switching to load stage 3 are fulfilled, the 2nd heat generator is released.

452117.66.20-EN · 1/2021-07 · Rei

60-76

CAUTION

Operating manual Heat pump manager WPM 6.0 9 Program description
9.5 Hysteresis
The so-called hysteresis can be set for different requirements in the menu. The hysteresis forms a "neutral zone" around the relevant set temperature. If the current temperature is lower than the set temperature reduced by the hysteresis, a request is detected. This remains in place until the current temperature has exceeded the upper limit of the neutral zone. This results in a switch cycle around the setpoint.
Hysteresis return set temperature
For the heating request, a hysteresis can be set around the return set temperature.
If the hysteresis is large, the heat pump runs for longer and the temperature fluctuations in the return are correspondingly high. With a small hysteresis, the compressor run times are reduced and the temperature fluctuations are lower. For surface heating systems with relatively flat characteristic curves, a hysteresis of approx. 1 K must be set, as an excessively large hysteresis can prevent the heat pump from switching on.
9.6 Control of the circulating pumps
The control of the heating, domestic hot water or swimming pool circulating pump determines where the heat generated by the heat pump should flow. The separate processing of different requests enables the heat pump to always work with the minimum possible flow temperature, thus ensuring energy-efficient operation.
With heat pumps for heating and cooling, additional cooling circulating pumps can be controlled. Pump assemblies with check valves guarantee defined flow directions.
In the summer operating mode, the heating pump runs for 1 minute every 150 hours (this prevents the heating pump from jamming at the start of the heating period).
9.6.1 Frost protection
Irrespective of the heat circulating pump settings, they always run in heating, defrost mode and when there is a risk of frost. For systems with multiple heating circuits, the 2nd/3rd heat circulating pump has the same function. In order to guarantee the frost protection function of the heat pump, the heat pump manager must not be deenergised and the heat pump must have flow through.

452117.66.20-EN · 1/2021-07 · Rei

61-76

Operating manual Heat pump manager WPM 6.0 9 Program description
9.6.2 Heat circulating pump
For the heat circulating pump (M13, M15, M20), an outside temperature-dependent heating pump optimisation is set in the menu "Pump control - Optimisation heating pump".
If the selected limit temperature is not reached, the heating pump optimisation is inactive. The heat circulating pumps are permanently in operation, except during domestic hot water, swimming pool preparation and in "Summer", operating mode.
If the selected limit temperature is exceeded, the heating pump optimisation is active. The heat circulating pumps run after a mains switch-on and for 30 minutes after the heat pump is switched off. If the heat circulating pumps had been switched off for longer than 40 minutes or if the return set temperature has intentionally been increased via a raise, the heat circulating pumps are activated for a 7 minute scavenging time to supply the representative temperature of the heating circuits to the return sensor (R2, R2.1) again.
If a switch takes place from heating to domestic hot water or swimming pool preparation, the heat circulating pump carries out an after-run.
The heat circulating pumps are permanently in operation if the minimum system temperatures are not met and with temperatures below 10 °C on the frost protection sensor (R9) of the air-to-water heat pumps.
In Summer operating mode, the circulating pump runs for 1 minute every 150 hours. This prevents the shaft from jamming.
9.6.3 Domestic hot water circulating pump
The domestic hot water circulating pump (M18) runs during domestic hot water preparation. If a domestic hot water request is issued during heating operation, the heat circulating pump is deactivated while the heat pump is running and the domestic hot water circulating pump is activated.
9.6.4 Swimming pool circulating pump
The swimming pool circulating pump (M19) runs during swimming pool preparation. A running swimming pool preparation is interrupted at any time by a domestic hot water request, defrosting process or by an increase in the heating characteristic curve (e.g. after night lowering), but not by a heat pump manager "more" signal. If the request is still in place after a 60-minute swimming pool preparation, the swimming pool circulating pump is deactivated for 7 minutes and the heat circulating pump is activated for a 7-minute scavenging time to supply the representative temperature of the heating circuit to the return sensor again. If the heat pump manager generates a "more" signal during these 7 minutes, the heating request is processed first.
In Summer operating mode, the swimming pool preparation is not interrupted by a scavenging time after 60 minutes.

452117.66.20-EN · 1/2021-07 · Rei

62-76

Operating manual Heat pump manager WPM 6.0 9 Program description
9.6.5 Auxiliary circulating pump
The auxiliary circulating pump output (M16) can be configured to achieve parallel operation of the auxiliary circulating pump with the compressor of the heat pump. A configuration for heating, domestic hot water and swimming pool preparation is possible. It also runs if the minimum system temperatures are not met.
In Summer operating mode, the circulating pump runs for 1 minute every 150 hours. This prevents the shaft from jamming.

9.6.6 Primary pump for heat source
The primary pump (M11) supplies the energy of the heat source to the heat pump

Heat pump type Air-to-water heat pump Brine-to-water heat pump Water-to-water heat pump

Primary pump Fan Brine circulating pump Well pump

The well water pump or brine circulating pump always runs if the heat pump is switched on. It starts up 1 minute before the compressor and switches off 1 minute after the compressor.
For air-to-water heat pumps, the fan is switched off during defrosting.
9.6.7 Circulation pump
If there is the option of connecting a circulation pump (M24), it can be requested via an impulse input or via time programs.
If the circulation pump is requested via the impulse input (X3/G - ID17), the delay time can be defined in the menu "Hot water circulation". If the request takes place via a time program, it can be set for two different times and weekdays.
TIP
A circulation line uses large amounts of energy. To save on energy costs, circulation should not be used. If this is unavoidable, it is advisable to adapt the time window to the optimal conditions. A better approach is to have the circulation running via an impulse for a specific time. This function is also possible with the heat pump manager.

452117.66.20-EN · 1/2021-07 · Rei

63-76

CAUTION

Operating manual Heat pump manager WPM 6.0 9 Program description
9.7 Building management system
From software version L09, there are two options for connecting the heat pump to a building management system.
 Transferring the set values on an interface via the BMS (Building Management System). Different protocols and interfaces are available for this.
 Wiring digital inputs with the option of influencing the described power control on the heat pump manager. There is also the option of switching the operating mode via digital inputs both from heating to cooling and influencing it via a parametrizable external block (frost protection/domestic hot water/holiday/summer).
In all cases, the primary pump (M11) and the secondary pump (M16), or the heat circulating pump (M13) depending on the hydraulic integration, must be connected to the heat pump manager. This is the only way to ensure that the pump flow and afteruns required for operation are observed and the necessary safety measures are effective.
9.7.1 BMS interface
On the BMS interface, the extensions available as special accessories for connection to:
 LAN
 KNX
 Modbus
are provided.
Via these extensions, the operating data and history can be read out and settings such as Modus or setpoint specifications can be made, among other things.
In general, a request from the heat pump in conjunction with the building management system should be favoured over an interface.
If an interface such as this is used, the following programming is suggested on the heat pump manager. Depending on the number of heating or cooling circuits, they are set to a fixed value regulation. The set temperature calculated by the building management system is transferred to the heat pump manager as the fixed value temperature. The heat pump is also switched to the Auto, Summer and Cooling mode via the building management system.
Further information on these options can be found in the description for the relevant product.
9.7.2 Compressor control via digital inputs
In addition to the setpoint specification via the building management system, the compressor can also be controlled via digital inputs.

452117.66.20-EN · 1/2021-07 · Rei

64-76

Load stage Stage L1 Stage L2 Stage L3

Operating manual Heat pump manager WPM 6.0
9 Program description

Load stages The load stages (L) are influenced via the digital inputs N1-J5/ID1 and N1-J5/ID2. An overview of the load stage switching is shown in the table.

Load stage Stage L1 Stage L2 Stage L3

N1-J5/ID1-X3/G closed open closed

N1-J5/ID2-H§/G open closed closed

The load stage switching takes place as described in load stage controls.

It must be noted here that the building management system can increase and reduce the load stages within the operating limits. The TAB of the utility companies are still in effect here. The set temperatures set on the heat pump manager are ignored. In extreme cases, the heat pump is only blocked via the operating limits (high and low pressure, flow and return temperature) or switched off by the safety functions.

The table shows the load stage switchings and their impact on the compressors and 2nd heat generator or refrigerator.

Switching the load stages
With parallel connections of heat pumps, it is advisable to set up and program the load stages as a ring connection. This means that, depending on the required output, heat pump 1 is released with L1, then heat pump 2 with L1 and heat pump 3 with L1. If additional power is required, heat pump 1 is released with L2, followed by heat pump 2 with L2 and heat pump 3 with L3. Switching back takes place in the same way. Firstly, heat pump 1 is switched in L1, heat pump 2 in L1 and then heat pump 3 in L1. This means that the compressors not only receive the same runtimes, but the heat pumps are also operated in the most efficient way with this measure.

Description
Set temperature - hysteresis Set temperature + hysteresis Set temperature - hysteresis Set temperature + hysteresis Set temperature - hysteresis Set temperature + hysteresis

Compressor 1
on off always on always on always on always on

Compressor 2
off off on off always on always on

2nd heat generator/ refrigerator off off off off on off

When programming the load stage switching via the building management system, it is important to note the heat-pump relevant minimum pause time, switch cycle block and the utility block where applicable.

452117.66.20-EN · 1/2021-07 · Rei

65-76

Operating manual Heat pump manager WPM 6.0
10 Commissioning of air-to-water heat pumps

9.7.3 External block
The heat pump can be blocked or released for one of the following functions via the digital input N1-J5/ID4-X3/G (external block):
 Frost protection - Heat pump maintains minimum system temperatures, domestic hot water and swimming pool preparation is blocked
 Domestic hot water block - Heat pump is released, minimum domestic hot water temperature is maintained
 Holiday mode - Heat pump maintains lower value, domestic hot water is blocked
 Summer mode - Heat pump maintains minimum system temperature, domestic hot water and swimming pool preparation is released

External block active inactive

N1-J5/ID4-X3/G open closed

Frost protection is guaranteed in all cases.

If the functions "Load stage switching" and "External block" are to be used, these functions must be activated by after-sales service during the commissioning of the heat pump.

9.7.4 Switching heating/cooling
With heat pumps for heating and cooling, the switching of the operating mode takes place via a digital input on the expansion mode N17.1-J4/ID4-X3/G.

Operating mode Heating Cooling

N17.1-J4/ID4-X3/G open closed

10 Commissioning of air-to-water heat pumps
To guarantee the defrosting with air-to-water heat pumps, the return temperature must be at least 18 °C to prevent the defrosting from being cancelled due to the value falling below the minimum permissible temperature on the frost protection sensor.
Activating the commissioning function (special function) releases the 2nd heat generator for one hour, suppresses a defrosting process or cancels a defrosting process currently in progress.
The heat circulating pump runs permanently during commissioning and a domestic hot water or swimming pool request is ignored.
With low heating water temperatures, the buffer tank must be heated up first before the individual heating circuits are opened one after the other.

452117.66.20-EN · 1/2021-07 · Rei

66-76

Operating manual Heat pump manager WPM 6.0 11 Initial heating program (screed drying)
11 Initial heating program (screed drying)
The initial heating of a screed takes place in accordance with defined standards and directives, which have, however, been adapted to the requirements of a heat pump heating system.
The individual programs are activated in the menu "Special functions - Screed drying").
The following applies during initial heating:
 The heat circulating pumps for heating circuits 1, 2 and 3 run permanently
 Programmed lowers or increases are ignored, a fixed hysteresis of ± 0.5 K applies (regardless of the configuration in the menu)
 Limit temperature for the 2nd heat generator fixed at +35 °C (regardless of the configuration in the menu)
 The calculated set temperature applies for all heating circuits
 The mixer of heating circuit 2/3 is controlled with permanently open
 In the event of a fault or an interruption in voltage, the selected program is only interrupted. Once the voltage is restored or the fault is acknowledged, the selected program is continued.
If there are no special requirements from the manufacturer, the use of the standard program line heating is recommended (max. return temperature 35-40 °C).
If no key is pressed 3 minutes after an initial heating program is activated, the display switches every minute. The current heat up step, set temperature, elapsed hours and required hours are shown in the bottom display line.
11.1 Implementation of the directive for a heat pump heating system
The directive is based on whole days for which a defined temperature is to be reached or maintained.
With high humidity levels in the screed, the defined temperatures are often not reached in the specified time. For sufficient drying, however, it is essential that the temperature level is maintained for a specific period of time.
For this reason, the days described in the standard are converted to program steps, where one program step corresponds to the combination of the number of days or hours and the relevant temperature.
Depending on the ratio of heat output from the heat pump and heated living area, the specified minimum heat up times can also be significantly exceeded, as the required minimum number of hours is only totalled up after the set temperature is reached.
The relevant standards and directives describe the flow temperature of the heating system in each case. The return temperature is key for controlling the heat pump.
The maximum return temperature must be entered for the initial heating program. This is calculated from the maximum flow temperature, minus the temperature spread (e.g. 7 K).

452117.66.20-EN · 1/2021-07 · Rei

67-76

Operating manual Heat pump manager WPM 6.0
11 Initial heating program (screed drying)

11.2 Heating function program in accordance with DIN EN 1264-4

This program serves as a function test for underfloor heating and is only carried out after the specified rest time of the screed.

This is designed to highlight any faults in the screed and in the underfloor heating.

1). Step:

A constant return temperature of 20 °C must be maintained for 72 hours (3 days).

2). Step: The maximum return temperature (selectable) must be maintained for 96 hours

(4 days).

3). Step:

The heat pump remains off until the return temperature has dropped below 20 °C.

The duration of step 3 is limited to a maximum of 72 hours, as, in high outside temperatures, the return temperature may not fall below 20 °C.
The heating function program should be carried out to check the function of the underfloor heating system. With cement screed, this may take place after 21 days at the earliest, with calcium sulphate screed, after 7 days at the earliest after the screed work is complete.

Once the screed has been created, after the required rest time and after the heating function program, the readiness for further processing must be confirmed before applying the upper floor covering.

11.3 Line heating to dry out the screed
11.3.1 General notes
This program reduces the humidity in the screed to a level where the floor covering can be applied.
The moisture content must be measured, however, and additional drying carried out where necessary.
The guidelines for drying the screed specify a fixed number of steps with defined temperatures and durations. This sequence can be selected in the menu as "Standard program line heating".
The standard program should be used in most cases in agreement with the screed installer. The sequence defined for the standard program should only be individually adapted if there are special requirements for the heating. In this case, select "Individual program line heating" in the menu.

452117.66.20-EN · 1/2021-07 · Rei

68-76

Operating manual Heat pump manager WPM 6.0
11 Initial heating program (screed drying)

11.3.2 Standard program line heating

This program consists of 8 steps and is usually suitable for all underfloor heating systems. Before activation, the maximum permissible return temperature must be entered (e.g. 32 °C).

Step 1-4: Step 5: Step 6-8:

Heat up processes Hold Cool down processes

Steps 1 to 4 are heat up processes lasting 24 hours each. With each step, the return set temperature is increased from 20 °C to the maximum return temperature.

To end a program step, two conditions must be met. The corresponding set temperature must have been reached or exceeded and the duration of 24 hours must have elapsed. If the temperature is reached before the 24 hours have elapsed, the heat pump maintains the relevant set temperature for the remaining duration. No evaluation takes place of how long this temperature was actually reached for.

In step 5, the maximum return temperature should be maintained for a period of 264 hours.

The duration for which the maximum return temperature was actually reached is totalled up. Upper limit open, lower limit setpoint - hysteresis.

Only when the totalled time has reached the value of 264 hours is this program step ended.

Steps 6 to 8 are cool down steps lasting 24 hours each. The return set temperature is lowered with each step from the maximum return temperature to 20 °C.

To end a program step, two conditions must be met. The value must be lower than the corresponding set temperature and the duration of 24 hours must have elapsed. If the value drops below the temperature before the 24 hours have elapsed, the heat pump maintains the corresponding set temperature for the remaining duration. No evaluation takes place of how long this temperature was actually reached for, however.

The duration of the cool down processes is limited to a maximum of 72 hours, as, in high outside temperatures, the value may not drop below the required return temperature.

Example:

Max. return temperature: 32 °C

Step 1-4: Step 5: Step 6-8:

20 / 24 / 28 / 32 °C Hold 28 / 24 / 20 °C

452117.66.20-EN · 1/2021-07 · Rei

69-76

Operating manual Heat pump manager WPM 6.0 11 Initial heating program (screed drying)
11.3.3 Individual program line heating
This program enables the following settings to be made:
 Differential temperature heat-up: Starting from the initial temperature 20 °C through to the set maximum temperature, the set temperature is increased by the set difference with each program step. The number of steps is therefore based on these factors.
 Heat-up duration: The number of hours in which the relevant set temperature must be reached and maintained (function as described above) can be entered here.
 Hold duration: The number of hours for which the maximum set temperature must be maintained can be entered here.
 Differential temperature Cool down: Starting from the set maximum temperature through to the initial temperature 20 °C, the set temperature is reduced by the set difference with each program step. The number of steps is therefore based on these factors.
 Duration Cool down: The number of hours in which the relevant set temperature must be reached and should be maintained can be entered here.

452117.66.20-EN · 1/2021-07 · Rei

70-76

Operating manual Heat pump manager WPM 6.0 12 Extended installation instructions for the heat pump manager heating/cooling
12 Extended installation instructions for the heat pump manager heating/ cooling
12.1 Active cooling
12.1.1 Heat pumps without additional heat exchanger
The cold generation takes place actively via heat pump process reversal. The switching of the refrigeration circuit from heating to cooling operation takes place via an internal four-way reversing valve.
When switching from heating to cooling operation, the heat pump is blocked for 10 minutes so that the different pressures of the refrigeration circuit can balance out.
The requests are processed as follows:
 Domestic hot water before
 Cooling before
 Pool
During domestic hot water or swimming pool preparation, the heat pump works as in heating operation.
12.1.2 Additional heat exchanger for waste heat recovery
Via an additional heat exchanger in the hot gas, the waste heat generated during cooling can be used for domestic hot water or swimming pool preparation. This requires "Yes" to be set in the Heat exchanger menu item.
The requests are processed as follows:
 Cooling before
 Domestic hot water before
 Pool
In the "Hot water" menu item, the hot water maximum temperature is set. While the domestic hot water temperature is below this limit, the domestic hot water circulating pump also runs during cooling. After the set maximum temperature is reached, the domestic hot water circulating pump is switched off and the swimming pool circulating pump is switched on (regardless of the swimming pool thermostat input).
If no cooling requirement is in place, domestic hot water or swimming pool requests can be processed. However, these functions are cancelled after a maximum of 60 minutes uninterrupted runtime to give priority to processing an active cooling requirement.

452117.66.20-EN · 1/2021-07 · Rei

71-76

Operating manual Heat pump manager WPM 6.0 12 Extended installation instructions for the heat pump manager heating/cooling
12.2 Passive cooling
Deep down, groundwater and the ground are significantly colder than the ambient temperature in summer. A plate heat exchanger installed in the groundwater or brine circuit transfers the refrigeration capacity to the heating/cooling circuit. The compressor of the heat pump is not active and is therefore available for domestic hot water preparation. The parallel operation of cooling and domestic hot water preparation can be activated in the menu item "Hot water- Parallel cooling hot water". For parallel operation of cooling and domestic hot water preparation, special requirements for the hydraulic integration must be guaranteed (see planning documents).
12.3 Program description cooling
12.3.1 Cooling operating mode
The functions for cooling are activated manually as a 6th operating mode. An outside temperature-dependent switching of the "cooling" operating mode is also possible. External switching via the input N17.1-J4-ID4 is possible.
The "Cooling" operating mode can only be activated if the cooling function (active or passive) is released in the preconfiguration.
Switching off the cold generation
The following limits are in place for protection:
 The flow temperature is below a value of 7 °C  Triggering of the dew point monitor in sensitive parts of the cooling system  Reaching the dew point with purely silent cooling
12.3.2 Activating the cooling functions
When cooling operation is activated, special control functions are carried out. These cooling functions are carried out by the cooling controller separately from the other control functions.
The following can prevent the activation of the cooling function:
 The outside temperature is below 3 °C (risk of frost)  The outside temperature is below the cooling operating limit with reversible air-to-water
heat pumps.  The cooling controller is not in place or the connection is faulty (I/O extension).  Neither silent nor dynamic cooling was selected in the heating/cooling circuit settings
In these cases, the Cooling operating mode remains active, but the control behaves as in the Summer operating mode.

452117.66.20-EN · 1/2021-07 · Rei

72-76

Operating manual Heat pump manager WPM 6.0 12 Extended installation instructions for the heat pump manager heating/cooling
12.3.3 Circulating pumps in cooling operation
With a heat pump heating system, which circulating pumps are activated or deactivated in which operating mode is defined in the preconfiguration of the relevant heating circuits.
The heat circulating pump of heating circuit 1 (M14) is not active in cooling operation if pure silent cooling is configured.
The heat circulating pump of heating/cooling circuit 2 (M15) is not active if only "heating" is selected.
The heat circulating pump of heating/cooling circuit 3 (M20) is not active if only "heating" is selected.
Heating components can be switched in heating or cooling operation via the floating contact N17.2 / N04 / C4 / NC4 (e.g. room temperature controller)
Passive cooling
The supply for the cooling system can take place via the existing heat circulating pump (M13) and via an additional cooling circulating pump (M17).
The cooling circulating pump (M17) runs permanently in "Cooling" operating mode.
Depending on the hydraulic integration with passive cooling, the running behaviour of the heat circulating pump (M13) can be changed under "Settings - Pump control".
12.3.4 Silent and dynamic cooling
Different system configurations can be achieved depending on the integration diagram. The selection takes place in the menu "Settings ­ Cooling".
 Pure dynamic cooling (e.g. fan convectors) The control corresponds to a fixed value regulation. The relevant desired return set temperature is set in the menu item Settings.
 Pure silent cooling (e.g. underfloor, wall surface or ceiling cooling) The control takes place based on the room temperature. The key factor is the temperature of the room where the room climate station 1 is connected according to the connection diagram. The relevant desired room temperature is set in the menu item Settings. The maximum transferable cooling capacity is heavily dependent on the relative humidity during silent cooling. A high humidity reduces the maximum cooling capacity, as the flow temperature is not reduced further once the calculated dew point is reached.
 Combination of dynamic and silent cooling The control takes place separately in two control circuits. The control of the dynamic circuit corresponds to a fixed value regulation (as described under dynamic cooling). The control for silent cooling takes place based on the room temperature (as described under silent cooling) by activating the mixer of heating circuit 2/3 (silent heating/cooling circuit).
If the refrigerator switches off because the minimum flow temperature of 7 °C is reached, either the water flow must be increased or a higher return set temperature (e.g. 16 °C) must be set.

452117.66.20-EN · 1/2021-07 · Rei

73-76

Operating manual Heat pump manager WPM 6.0 12 Extended installation instructions for the heat pump manager heating/cooling
12.4 Room temperature control
Heating technology systems are usually equipped with automatic mechanisms for controlling the room temperature on a room-by-room basis.
In heating operation, the room thermostats record the current temperature and open the controller (e.g. actuator) if the value is below the specified set temperature.
In cooling operation, the room thermostats must either be deactivated or replaced by ones suitable for heating and cooling.
In this case the room thermostat behaves in the opposite way in cooling operation, meaning that the controller opens when the set temperature is exceeded.

452117.66.20-EN · 1/2021-07 · Rei

74-76

Operating manual Heat pump manager WPM 6.0
12 Extended installation instructions for the heat pump manager heating/cooling

452117.66.20-EN · 1/2021-07 · Rei

75-76

Max Weishaupt GmbH · 88475 Schwendi Weishaupt close by? Addresses, telephone numbers etc. can be found at www.weishaupt.de We reserve the right to make changes. All rights reserved.
76
The complete program: Reliable technology and prompt, professional service

W Burners

up to 700 kW

The compact burners, proven millions of times over, are economical and reliable. Available as gas, oil and dual fuel burners for domestic and commercial applications.

Wall-hung condensing boilers

for gas

up to 800 kW

The wall-hung condensing boilers WTC-GW have been developed to meet the highest demands in ease of operation and efficiency. Modulating operation means these units operate quietly and economically.

monarch® WM Burners and Industrial Burners

up to 12,000 kW

These legendary industrial burners are durable and versatile. Numerous variations of oil, gas and dual fuel burners meet a wide range of applications and capacity requirements.

Floor-standing condensing boilers

for oil and gas

up to 1,200 kW

The floor-standing condensing boilers WTC-GB (up to 300 kW) and WTC-OB (up to 45 kW) are efficient, low in pollutants and versatile in use. Even the largest capacities can be covered by cascading up to four gas condensing boilers.

WKmono 80 Burners

up to 17,000 kW

The WKmono 80 burners are the most powerful monoblock burners from Weishaupt. They are available as oil, gas or dual fuel burners and are designed for tough industrial application.

Solar systems
The stylish flat-plate collectors are the ideal complement for any Weishaupt heating system. They are suitable for solar water heating and for combined heating support. With versions for on-roof, in-roof and flat roof installations, solar energy can be utilised on almost any roof.

WK Burners

up to 32,000 kW

These industrial burners of modular construction are adaptable, robust and powerful. Even on the toughest industrial applications these oil, gas and dual fuel burners operate reliably.

Water heaters/Energy storage
The diverse program of potable water and energy storage for various heat sources includes storage volumes of 70 to 3,000 litres. In order to minimize storage losses, potable water cylinders from 140 to 500 litres are available with highly efficient insulation using vacuum insulation panels.

MCR Technology / Building Automation from Neuberger
From control panels to complete building management systems - at Weishaupt you can find the entire spectrum of modern control technology. Future orientated, economical and flexible.

Heat pumps

up to 180 kW (Single device)

The heat pump range offers solutions for the utilisation of heat from the air, the soil or ground water. Some systems are also suitable for cooling buildings.

Service
Weishaupt customers can be assured that specialist knowledge and tools are available whenever they are needed. Our service engineers are fully qualified and have extensive product knowledge, be it for burners, heat pumps, condensing boilers or solar collectors.

Geothermal probe drilling
With its daughter company, BauGrund Süd, Weishaupt also offers geothermal probe and well drilling. With the experience of more than 17,000 systems and more than 3.2 million meters of drilling, BauGrund Süd offers a comprehensive service program.

83323202 · 1/2021-07 · Rei

