ADC Telecommunications DNXSMR1A Digivance® NXD SMR 900 MHz System User Manual 75210

ADC Telecommunications Inc Digivance® NXD SMR 900 MHz System 75210

User Manual 3

ADCP-75-210 • Issue 1 • November 2006Page 49© 2006, ADC Telecommunications, Inc.2. Install the compression nut and an appropriate sized split ring and bushing over the cableend. Note that the beveled side of the split ring should face toward the compression nut.3. Insert the end of the cable into the fiber entry opening on the bottom of the cabinet andpull the cable into the cabinet. 4. Connect fiber to the LC receptor located on the SIF electronic module. For location, referto Figure 11 on Page 16.5. Pull back any excess fiber from within the NXD cabinet. 6. Tighten the compression nut on the fiber entry connector body to secure the cable. 7. Seal all connections. 2.7.5 Installing AC PowerPrime power for the RAN is 240 VAC, 20 Amps, single phase. A separate service disconnectand lightning arrestor for each RAN must be installed with proper grounding. An electric meteris optional depending on local agreements. A non-connectorized #14 AWG 3-wire power cable is provided with the RAN cabinet for theAC power connections. The power cable is connected to a wiring harness within the cabinet andis approximately 20 feet (6 meters) long. The stub end of the cable must be routed out of thecabinet through conduit to an external junction box (not provided). At the junction box, thepower cable must be connected to the AC power system wiring. The RAN electrical input fittingis located on the right rear of the cabinet, labeled “AC.”The AC power cable provides three wire leads for Line, Neutral, and Ground connections. AllAC wires must be run within conduit. The interface at the RAN is a 1 in. (2.54 cm) 90 degreereceptor elbow.For installation of AC power, the following materials are required (customer provided):• Electrical conduit• Conduit fittings• Connector sealant materialThe following tools are required to perform this procedure:• Wire cutters• Wire strippers• Conduit cutter• Conduit benderNote: The fiber should not have armored jacketing which may be a source for Electro-Magnetic Interference (EMI).Note: Power interfacing for the RAN must be performed by a licensed electrician.
ADCP-75-210 • Issue 1 • November 2006Page 50© 2006, ADC Telecommunications, Inc.Use the following procedure to install the AC power wiring:1. Install outdoor conduit between the the AC power junction box and the AC power fitting(rigid 90 degree receptor elbow) on the back of the cabinet. 2. Use a UL approved outdoor conduit connector (not provided) to connect the conduit to theAC power junction box.3. Route the AC power cable through the conduit to the AC junction box.4. Install the required AC power supply wires between the AC junction box and the ACcircuit breaker box (by the junction box not within the RAN).5. Strip off the insulation from the AC power cable wire leads and from the AC supply wiresand connect the AC power cable wires to the AC supplier cable.6. Connect the AC power to the AC wiring harness.7. At the AC circuit breaker box, connect the AC power supply load wire(s) to a 20 Ampcircuit breaker.8. Place the circuit breaker in the ON position and then test the connectorized AC powercable within the cabinet for proper voltage levels and correct polarity.9. Place the circuit breaker in the OFF position when testing is complete. 2.7.6 Installing Backup Batteries (Extended or Glitch)Backup batteries for the RAN may be either two-hours-extended or five minutes glitch. Thebatteries will need to be installed and under charge before they will be able to provide fullservice. Battery storage life is one year in an environmentally controlled area. Batteries shouldbe checked prior to installation. Each battery should measure 12.6 V or greater across terminals.Any battery that measures less should not be used. Refer to the battery manufacturer’s manualfor specific information including charging recommendations, tests, and maintenance.2.7.6.1 Battery Safety RulesFor safety purposes, observe the following DO’s and DON’T’s when installing the batteries orperforming battery tests and maintenance: • DO use qualified personnel only for battery maintenance• DO follow all battery and charger manufacturer maintenance instructionsNote:  All electrical work must comply with local codes and requirements. A locallylicensed electrical contractor is best qualified to perform this work. For operation at lessthan 20 Amps, consult with ADC Technical Service.Danger: Use extreme caution when working with high voltage AC power. Ensure all power isdisconnected before working on power circuits. Note: A reducer fitting must be provided to accommodate any size change to the conduit.
ADCP-75-210 • Issue 1 • November 2006Page 51© 2006, ADC Telecommunications, Inc.• DO wear protective equipment (face shield, goggles, gloves) when working with oraround battery systems.• DO use proper lifting techniques when working with batteries.• DO use insulated tools when working on batteries.• DO remove all rings and metal watchbands before working on batteries.• DON’T service batteries individually. Replace pack as a unit.• DON’T replace a defective pack with an alternate type. Use only the replacement packsprovided by ADC.• DON’T lift batteries by their terminals. • DON’T place tools, unconnected cables, or metal objects to rest on top of the batteries. • DON’T use any chemical cleaners (ammonia, bleach, etc.) to clean batteries. • DON’T remove vent caps or add anything to sealed, maintenance-free batteries. • DON’T smoke, cause sparks, or carry an open flame near any battery system. • DON’T approach any energized battery system that shows signs of over-charging or overdischarging (severe swelling, cover deformation, vent caps popping off). Disconnect andisolate the battery system from all charging and discharging circuitry before approachingthe system. • DON’T circumvent any device installed by the battery or charger manufacturer for thepurpose of protecting the battery system. These devices include fuses, circuit breakers,disconnects, switches, etc. 2.7.6.2 Battery InstallationUse the following procedure to install the batteries:1. Open the RAN door.2. Turn off the battery disconnect switch (labeled DISC) on the low voltage disconnect unitin the RAN chassis. For location, refer to Figure 19 on Page 24. The LVD LED will lightup (red) when the batteries are disconnected.3. Move the gravity latch in the battery drawer to the up position. Refer to Figure 34.Warning:  Do not short battery connections together or to ground. The battery pack has highcurrent capacity and can cause burns or serious personal injury when shorted.Warning: To avoid personal injury or fire damage, do not incinerate or mutilate the battery. Donot short the battery terminals and do not store or operate the battery in an airtight container.Warning:  The batteries contain hazardous materials. Deliver defective batteries to anauthorized disposal center for disposal or recycling.Caution: Before connecting batteries, be sure to turn off the low voltage connect switch locatedon the rectifier. The LED will be OFF.
ADCP-75-210 • Issue 1 • November 2006Page 52© 2006, ADC Telecommunications, Inc.4. Pull out the battery drawer.5. Move the gravity latch to the down position. Lock the telescopic slide into the locked outposition.6. Install the batteries in the drawer as follows, referring to Figure 35 for extended batteriesand Figure 36 for extended batteries:a. Place the batteries in the drawer in the configuration shown.b. Wire the batteries in series as shown.c. Find the wiring harness coiled up on the floor of the battery back up drawer and plugthe Anderson connectors together as shown.7. Move the gravity latch up, push the battery drawer in, and move the gravity latch down.8. Reconnect the battery disconnect switch (DISC) on the LVD unit. For location, refer toFigure 19 on Page 24. The LVD LED on the low voltage disconnect unit should will turnoff when the batteries are reconnected.Figure 34. Open Battery Drawer21277-AGRAVITYLATCHBATTERYDRAWER
ADCP-75-210 • Issue 1 • November 2006Page 53© 2006, ADC Telecommunications, Inc. Figure 35. Extended Batteries in Drawer Figure 36. Glitch Batteries in Drawer21288-A70 AMPFUSEANDERSONCONNECTOR21289-A70 AMPFUSEANDERSONCONNECTORNOTE:CUSTOMER TO COVEREXPOSED TERMINALSWITH ELECTRICAL TAPE.
ADCP-75-210 • Issue 1 • November 2006Page 54© 2006, ADC Telecommunications, Inc.3 INSTALLING AN EXTENSION RAN (POLE MOUNT)Two RANs can be installed at the same location to provide up to eight bands at that locationusing a common antenna. Each RAN requires its own separate power and RF cables and fiberoptical cable. Figure 37 shows a typical dual RAN pole mount installation.Figure 37. Typical Dual RAN Pole-Mount InstallationMaterials Required (Customer Supplied):• Three galvanized steel bolts with tensile strength of 20,500 lbs. or greater, 3/4 inchdiameter, of a length appropriate to pole diameter21295-AANTENNAPRIMARY POWERSECONDARY  POWER LINEFIBER SPLICE CANFIBER OPTIC LINEFRONTVIEW31.25 IN.(79.4 CM)1.5 IN. SCHEDULE 40POLE RISER FORFIBER OPTIC LINESCARLTON PT. NO.59010N OREQUIVALENT3 IN. SCHEDULE 40CONDUIT FOR RF CABLESCARLTON PT. NO.49013-010 OREQUIVALENTRF CABLESTO RAN(5 REQUIRED)ANTENNAANTENNAMOUNTINGBRACKET100 IN.(254 CM)GROUND WIRETO ANTENNAPRIMARYPOWERSECONDARYPOWERFIBER2 IN. SCHEDULE 40CONDUIT FOR POWER INCARLTON PT. NO.49011-010 OREQUIVALENTSIDEVIEW27.5 IN.(69.85 CM)7 FT. (2.1 M)TYPICALJUNCTIONBOX#6 AWG COPPERGROUND WIRE TOMETER BOX, RAN,AND ANTENNA6 FT. (1.8 M)TYPICAL10 FT. (3 M)TYPICAL38.6 FT.(11.8 M)TYPICALCOPPERGROUNDROD
ADCP-75-210 • Issue 1 • November 2006Page 55© 2006, ADC Telecommunications, Inc.• Three nuts, three flat washers, three 3 in. square curved washers, and three split ringwashers for boltsMaterials Required, ADC Supplied:• RAN fixturing angle P/N 1001509P001 (X2)• 1/4-20 X 3/4 hex bolts (X4)• 2 in. through hull bulkhead fitting• Flexible grommetUse the following procedure to install an expansion RAN. Refer to Figure 38.1. Open the existing RAN door.2. Remove the solar shield from the existing RAN. Refer to the solar shield installationprocedure in Section 2.7.1 on Page 43 and do the steps in a reverse order.Figure 38. Dual RAN Pole MountNote:  This procedure assumes that the expansion RAN is installed on a utility poledirectly above the existing RAN.21296-A1.50 IN.(3.8 CM)2 IN. (5.08 CM)BULKHEAD FITTINGSUPPLIED WITHEXTENSION RANKENNARDFLEXIBLE GROMMETSUPPLIED WITHEXTENSION RAN
ADCP-75-210 • Issue 1 • November 2006Page 56© 2006, ADC Telecommunications, Inc.3. If RF cables will be routed from the existing RAN M/MCPLR or P/MCPLR module to theextension RAN, remove the hole seal plugs located on the top right of the existing RANand on the bottom right of the extension RAN.4. Bolt the fixturing angle to each side the expansion RAN pole mount bracket bottom holesusing the two 1/4-20 X 3/4 hex bolts.5. Raise the assembly above the existing RAN and align the bottom of the fixturing anglewith the top of the existing pole mount bracket.6. Bolt the fixturing angle to each side of the existing RAN pole mount bracket top holesusing the two 1/4-20 X 3/4 hex bolts.7. Install the extension RAN pole mount bracket, RAN cabinet, and rain shields followingthe instructions in Section 2.5.3 on Page 36, Section 2.5.4 on Page 38, and Section 2.5.5on Page 38, respectively.8. Install a solar shield on the extension RAN following the instructions in Section 2.7.1 onPage 43.9. Install a grounding wire on the extension RAN following the instructions in Section 2.7.2on Page 44.10. Install the RF cables from the antenna to the extension RAN following the instructions inSection 2.7.3 on Page 45.11. Install the fiber optic cable from the Hub to the extension RAN following the instructionsin Section 2.7.4 on Page 47.12. Install AC power in the extension RAN following the instructions in Section 2.7.5 on Page49.13. Install backup batteries in the extension RAN following the instructions in Section 2.7.6on Page 50.14. Close and secure both RANs.Note: In this case, the multicoupler modules, the PAAs, and the GPS in the existing RANwill be providing input into the extension RAN RDC module, the PAAs, and the STFmodule (ANT input) for some or all of bands 5-8. The associated RF cables from themulticouplers will be routed out of the top of the existing RAN and into the bottom of theextension RAN.
ADCP-75-210 • Issue 1 • November 2006Page 57© 2006, ADC Telecommunications, Inc.4 NON-STANDARD INSTALLATION PROCEDURESThis section contains other installation procedures that are not typically done at a RANinstallation. These procedures cover field installation of electronic modules and othercomponents like the RAN chassis fans.4.1 Installing an Electronic ModuleIf installing an electronic module in the field, refer to the appropriate procedure in this section.There is a procedure for each type of electronic module. For a comprehensive description of theelectronic modules including function, controls, and indicators, refer to the appropriate topic inSection 1.7 on Page 10.Typically, the RAN chassis is shipped populated with the appropriate modules based on the pre-ordered system configuration. Installation of electronic modules is only required wheninstalling a new electronic module or when changing the the system configuration.The electronic modules install into predetermined slots in the chassis identified by the labels onthe fan access panel above the chassis. For an illustration of the fan access panel labels and alisting of the slots, refer to Section 1.7 on Page 10.The interconnection diagram shown in Figure 39 and Figure 40 on the next two pagessummarizes the interconnections between the RAN chassis electronic modules and otherelectronic components of the RAN such as rectifiers and PAAs. Note: Not all options and features are supported in combination.Warning:  Electronic components can be damaged by static electrical discharge. To preventESD damage, always wear an ESD wrist strap when handling electronic components.Note:  The interconnection diagram shows a typical configuration. Other configurationsare possible that would be interconnected slightly differently.
ADCP-75-210 • Issue 1 • November 2006Page 58© 2006, ADC Telecommunications, Inc.Figure 39. RAN Interconnection Diagram Part 121372-A
ADCP-75-210 • Issue 1 • November 2006Page 59© 2006, ADC Telecommunications, Inc.Figure 40. RAN Interconnection Diagram Part 221373-A
ADCP-75-210 • Issue 1 • November 2006Page 60© 2006, ADC Telecommunications, Inc.4.1.1 Installing a Central Processing Unit (CPU) ModuleThe Central Processing Unit (CPU) module installs into Slot 5 of the RAN chassis. Only oneCPU may be installed in the RAN chassis. Use the following procedure to install the CPU module (Figure 41):1. Open the RAN door.2. Locate the designated slot for the CPU module. The CPU module installs into Slot 5,which is identified with a red colored card guide.3. Remove the CPU module from the anti-static packaging and orient the module forinstallation as shown in the figure.4. Slide the CPU module into the designated slot within the RAN chassis. 5. Lock the IEL handles on the top and bottom of the CPU module into the cPCI chassis. 6. Tighten the two Phillips head screws inside the handles. 7. Connect the short CAT5e jumper (cable 1001478P001) between the “ENET” port on theCPU module the “10BT” port on the SIF module.                                                                                                                                                                                                 21250-AXFigure 41. Installing a CPU ModuleNote: For a description of the CPU module including function, controls, and indicators,refer to Section 1.7.2 on Page 13. For a RAN chassis interconnection diagram, refer toFigure 39 on Page 58.Note:  If there are two SIF modules present, connect the cable to the first SIF module(leftmost SIF module when viewed from the front of the chassis).
ADCP-75-210 • Issue 1 • November 2006Page 61© 2006, ADC Telecommunications, Inc.4.1.2 Installing a Systems Interface (STF2) ModuleThe System Interface module (STF2) is installed into Slot 6 of the RAN Chassis. Only oneSTF2 module may be installed per RAN chassis.Use the following procedure to install the STF2 module (Figure 42):1. Open the RAN door.2. Locate the designated slot for the STF2 module. The module installs into Slot 6.3. Remove the STF2 module from the anti-static packaging and orient for installation.4. Slide the STF2 module into the designated slot within the RAN chassis. 5. Lock the IEL handles on the top and bottom of the STF2 module into the cPCI chassis andtighten the handle screws.6. Using cable 1001474P001, connect the RAN door switch to the RJ-45 connector labeledDA (Door Alarm) on the front of the STF2 module.7. Using cable 1955000P084, connect the GPS antenna to the SMA connector labeled ANT(Antenna) in the center of the module. 8. Using cable 1001476P001, connect the RECT port on the STF2 module to the unlabeled9-pin port on the Low Voltage Disconnect (LVD) unit. For location of the LVD port, referto Section 1.8.2 on Page 24.                                                                                                                                                                                                 21252-AXFigure 42. Installing an STF2 ModuleNote: For a description of the STF2 module including function, controls, and indicators,refer to Section 1.7.3 on Page 14. For a RAN chassis interconnection diagram, refer toFigure 39 on Page 58.
ADCP-75-210 • Issue 1 • November 2006Page 62© 2006, ADC Telecommunications, Inc.4.1.3 Installing a Synchronous Interface (SIF) ModuleThe Synchronous Interface Module (SIF) is installed into Slot 7 or Slot 8 of the RAN chassis.One SIF module is required for each two bands installed in the RAN. For the first two bands useSlot 7. For the second two bands, use Slot 8.Use the following procedure to install the SIF module (Figure 43):1. Open the RAN door.2. Locate the designated slot for the SIF module. The module installs into Slot 7 or Slot 8.Refer to the introductory text above for more information. 3. Remove the SIF from the anti-static packaging and orient for installation.4. Slide the SIF into the designated slot within the RAN chassis. 5. Lock the IEL handles on the top and bottom of the SIF module into the cPCI chassis andtighten handle screws.                                                                                                                                                                                                  21252-AXFigure 43. Installing an SIF Module6. If this SIF module is being installed into Slot 7, connect the short CAT5e jumper (cable1001478P001) between the “10BT” port on the SIF and the “ENET” port on the CPUmodule. (For a slot 8 SIF, no cable is required.)7. Carefully route the internal fibers to the front of the SIF module.Note: For a description of the SIF module, including function, controls, and indicators,refer to Section 1.7.4 on Page 15. For a RAN chassis interconnection diagram, refer toFigure 39 on Page 58.
ADCP-75-210 • Issue 1 • November 2006Page 63© 2006, ADC Telecommunications, Inc.8. If the optical transceiver is mounted into the SIF module, then connect the fiber to the dualLC connector. If optical transceiver is not mounted into the SIF module, follow the SFPinstallation procedure in Section 4.1.4 on Page 63.4.1.4 Installing a Small Form-Factor Optical Transceiver (SFP)The SFP installs in the front center of the SIF module. Use the following procedure to install an SFP:-1. Locate the transceiver socket on the front of the SIF and remove the port cover from thesocket. 2. The color of the transceiver extractor handle corresponds to the optical specifications ofthe SFP and CWDM designations. Select the optical transceiver that is to be used tocommunicate with the target RAN.  3. Remove the transceiver from the anti-static packaging and orient for installation.4. Insert the optical transceiver into the socket until it locks into place.5. Connect fiber or replace the optical transceiver dust cap if it was removed for installation.4.1.5 Installing a RAN Down Converter (RDC or RDC2) ModuleThe RAN Down Converter (RDC) module may be installed into any of four slots in the RANchassis, depending on the band for which the module will be used. One RDC module is requiredfor each band. The four slots are:• Slot 10 (labeled RDC A1): used for first band• Slot 12 (labeled RDC A3): used for second band• Slot 13 (labeled RDC A4): used for third band• Slot 15 (labeled RDC A6): used for fourth bandUse the following procedure to install an RDC or RDC2 module (Figure 44):1. Identify the slot designated RAN chassis slot for the RDC module. This will be Slot 10,12, 13, or 15. For more information, refer to the introductory text above.2. Remove the RDC module from the anti-static packaging and orient the module forinstallation. Note:  For a description of the SFP, refer to Section 1.7.5 on Page 17. See also thedescription of the SIF module faceplate in Section 1.7.4 on Page 15. Note:  For CWDM systems, it is extremely important that the correct wavelength beinstalled in each SIF. Consult the site fiber plan for detailsNote: For a description of the module including function, controls, and indicators, refer toSection 1.7.6 on Page 17. For a RAN chassis interconnection diagram, refer to Figure 39on Page 58.

Navigation menu