APC XS 1500 BX1500BP_EN_REV01 User Manual To The E2f62543 0382 4465 Ad3c 47fe24f655f5
User Manual: APC XS 1500 to the manual
Open the PDF directly: View PDF .
Page Count: 2
CONNECT TVSS
User’s Manual
Back-UPS® XS 1500
12 4
CONNECT BATTERY CARTRIDGE OPERATING ENVIRONMENT
3
7CONNECT EQUIPMENT / POWER
Monitor
Printer or Scanner FAX
External Disk or
CD / DVD Drive
Input: 120V~
12A, 60Hz
Circuit Breaker
Push to Reset
SURGE
ONLY
BATTERY BACKUP
Computer
8CHECK BUILDING WIRING
FAULT INDICATOR
Building
Wiring Fault
Wall
Outlet
Modem/
Phone/Fax
TVSS GND
Building Wiring
Fault Indicator
6
Phone Jack
Computer
Modem Port
CONNECT PHONE/
TVSS GND
Wall
Outlet
Modem/
Phone/Fax
9
To Computer USB
Port
CONNECT INTERFACE CABLE
Data Port BR24BP Battery Pack
Computer
12 INSTALL SOFTWARE ON
COMPUTER There are four status indicators (lights) on the front
panel of the Back-UPS (On Line, On Battery, Overload,
and Replace Battery).
On Line (green) - is lit whenever utility power is
powering the Battery Backup outlets.
On Battery (yellow) - is lit whenever the battery of
the Back-UPS is powering equipment connected to the
Battery Backup Outlets.
Four Beeps Every 30 Seconds - this alarm is
sounded whenever the Back-UPS is running On
Battery. Consider saving work in progress.
Overload (red) - is lit whenever power demand has
exceeded the capacity of the Back-UPS.
Continuous Tone - this alarm is sounded
whenever the Battery Backup outlets are
overloaded.
Circuit Breaker - the circuit breaker button
located on the rear panel of the Back-UPS will
stick out if an overload condition forces the Back-
UPS to disconnect itself from utility power. If the
button sticks out, disconnect non-essential
equipment. Reset the circuit breaker by pushing
the button inward.
Replace Battery (red) - is lit whenever the battery is
near the end of its useful life, or if the battery is not con-
nected (see above). A battery that is near the end of its use-
ful life has insufficient run-time and should be replaced.
Chirps for 1 Minute Every 5 Hours - this
alarm is sounded whenever the battery has failed
the automatic diagnostic test.
Note: Allow the Back-UPS to charge for a full
eight (8) hours prior to use.
Press the front panel Power ON/OFF switch and
observe that the following events occur after
pressing and releasing the switch:
• The green On Line indicator flashes.
• The yellow On Battery indicator lights while
a Self-Test is being performed.
• When Self-Test has successfully completed,
only the green On Line indicator will be lit.
• If the battery cartridges are not connected (see
Step 3 above), the green On Line indicator
and red Replace Battery indicators will light.
The Back-UPS will also emit a chirping
sound.
Continuous Beeping - this alarm is sounded
whenever a low battery condition is reached.
Battery run-time is very low. Promptly save any
work in progress and exit all open applications.
Shutdown the operating system, computer and
the Back-UPS.
NOTE: Macintosh Users - for full USB performance,
use OS 9.22 or higher.
If Autoplay is not enabled on the computer, proceed
as follows:
1. On the computer desktop of the display, double-
click on My Computer.
2. Double-click on the CD-ROM drive icon and
follow the on-screen instructions.
If the rear panel Building Wiring Fault (red) indicator
is lit, a potential shock hazard exists due to one of the
following conditions:
• Open or high resistance ground
• Hot or neutral polarity reversed
• Overloaded neutral circuit
Improper building wiring should be corrected by a
qualified electrician. Do not use the Back-UPS until
the condition that caused the fault is corrected.
Note: Improper building wiring will not prevent the
Back-UPS from operating, but it will limit its
protection capability.
11 SWITCH ON THE BACK-UPS
10 ORIENTATION
13 GROUND
The Back-UPS features a transient
voltage surge-suppression (TVSS)
screw for connecting the ground
lead on additional surge
suppression devices such as
network and data line surge
protectors.
Wal l
Outlet
Modem/
Phone/Fax
TVSS GND
From Data Line
TVSS
Follow the
on-screen
instructions.
On Line
On Battery
Overload
Replace Battery
w
w
w
.apc.com
®
RJ-45USB
STATUS INDICATORS AND ALARMS
32 - 104oF (0 - 40oC)
✘✔✔
A
3
✔
✘
24 inches
60 cm
✔
5CONNECT BACK-UPS TO
BATTERY PACK
Data Port
Buildi ng
Wiring Fa ult
Wal l
Outlet
Mod em/
Phone/Fax
TVSS GND
BR24 BP Bat tery Pack
MODEM/FAX
INSTALL PEDESTAL
EXTENDER
Align
Slide Together
INSTALL BACK-UPS AND
BATTERY PACK IN PEDESTAL
B
SPECIFICATIONS
Item Specification
On-line Input Voltage Range
(default setting)
88 - 139 Vac
Automatic Voltage Regulation (AVR) +12%
On-line Frequency Range 47 - 63 Hz (autosensing)
On-battery Waveshape Stepped Sine Wave
Maximum Load 1500 VA - 865 W
Typical Recharge Time 24 Hours
Operating Temperature 32o to 104oF
0o to 40oC
Storage Temperature 23o to 113oF
-5o to 45oC
Operating / Storage Relative Humidity 0 to 95% non-condensing
Size (H x W x D) 14.6 x 6.8 x 13.1 inch
37.1 x 17.2 x 33.3 cm
Weight 52.5 lbs (23.5 kg)
Shipping Weight 58.5 lbs (26.5 kg)
EMI Classification FCC / DOC Class B Certified
On Battery Run-Time See http://www.apc.com/product
TROUBLESHOOTING
Problem Possible Cause Corrective Action
Back-UPS will not switch on. Back-UPS not connected to AC power source. Ensure the Back-UPS is securely connected to an AC outlet.
Back-UPS circuit breaker “tripped”. Disconnect non-essential equipment from the Back-UPS. Reset
(push in) the rear panel circuit breaker. Switch on the Back-UPS
and plug in devices one at a time. If the circuit breaker trips
again, disconnect the device that caused the breaker to trip.
Utility input voltage quality is out of range. Consider adjusting the transfer voltage and sensitivity. See
Transfer Voltage and Sensitivity Adjustment.
Back-UPS does not power
essential equipment during an
outage.
Equipment plugged into a Surge Only outlet. Unplug device from 'Surge Only' outlet and move to a 'Battery
Backup' outlet.
Back-UPS operates on battery
although utility power exists.
Back-UPS circuit breaker “tripped”. Disconnect non-essential equipment from the Back-UPS. Reset
(push in) the rear panel circuit breaker. Switch the Back-UPS on
and plug equipment in one-at-a-time. If the circuit breaker trips
again, disconnect the device that caused the breaker to trip.
Utility input voltage quality is out of range. Consider adjusting the transfer voltage and sensitivity. See
Transfer Voltage and Sensitivity Adjustment.
Back-UPS does not provide
expected backup time.
Back-UPS is heavily loaded. Unplug non-essential equipment (printers, scanners, etc) from
the Battery Backup outlets and plug into 'Surge Only' outlets.
Back-UPS battery cartridge is discharged due to
recent power outage and has not had time to
recharge.
Charge the battery cartridge for 8 hours. Back-UPS runtime is
reduced until the battery cartridge is fully charged.
Battery has reached the end of its life. Replace battery cartridge (see Order Replacement Battery
Cartridge).
Red Replace Battery indicator is
flashing. Green On Line indicator
is on.
Internal battery cartridge is not connected. Connect battery cartridge (see Connect Battery Cartridge).
Red Replace Battery indicator is
on.
Battery has reached the end of its life. Replace the battery cartridge (see Order Replacement Battery
Cartridge).
Red Overload indicator is on or
flashing.
Connected equipment is drawing more power than
the Back-UPS can provide.
Move one or more equipment power plugs from Battery Backup
outlets to Surge Only outlets.
Green On Line indicator is on and
all other front panel indicators are
flashing.
Internal UPS fault. Contact APC Technical Support (see Contact Information).
Battery
Cartridge
REPLACE BATTERY CARTRIDGE
SERVICE
If the Back-UPS arrived damaged, notify the carrier.
If the Back-UPS requires service, do not return it to the dealer. The following
steps should be taken:
1. Consult the Troubleshooting section to eliminate common problems.
2. If the problem persists, go to http://www.apc.com/support/.
3. If the problem still persists, contact APC Technical Support.
• Have the Back-UPS model number, serial number and date of purchase
available. Be prepared to troubleshoot the problem with an APC Technical
Support representative. If this is not successful, APC will issue a Return
Merchandise Authorization (RMA) number and a shipping address.
CONTACT INFORMATION
Technical Support http://www.apc.com/support
Internet http://www.apc.com
USA / Canada 1.800.800.4272
Mexico 292.0253 / 292.0255
Brazil 0800.12.72.1
Worldwide +1.401.789.5735
LIMITED WARRANTY
The standard warranty is two (2) years from the date of purchase. APC’s standard
procedure is to replace the original unit with a factory reconditioned unit.
Customers who must have the original unit back due to the assignment of asset
tags and set depreciation schedules must declare such a need at first contact with
an APC Technical Support representative. APC will ship the replacement unit
once the defective unit has been received by the repair department, or cross-ship
upon the receipt of a valid credit card number. The customer pays for shipping the
unit to APC. APC pays ground freight transportation costs to ship the replacement
unit to the customer.
In situations where the Back-UPS or connected equipment appears too sensitive to input
voltage, it may be necessary to adjust the transfer voltage. This is a simple task requiring
use of the front panel pushbutton. To adjust the transfer voltage, proceed as follows:
1. Plug the Back-UPS into the utility power source. The Back-UPS will be in a Standby
Mode (no indicators lit).
2. Press the front panel pushbutton fully inward for 10 seconds. All indicators on the
Back-UPS will flash to acknowledge going into Programming Mode.
3. The Back-UPS will then indicate its current Lower Transfer Voltage, as shown in the
following table.
4. To select 78 volts as the Lower Transfer Voltage, press the pushbutton until 1 indicator
is flashing.
5. To select 83 volts as the Lower Transfer Voltage, press the pushbutton until 2
indicators are flashing.
6. To select 88 volts as the Lower Transfer Voltage, press the pushbutton until 3
indicators are flashing.
7. Once in Programming Mode, if the pushbutton is not pressed within 5 seconds, the
Back-UPS will exit Programming Mode; all indicators will extinguish.
Indicators Lit Lower Transfer Voltage
Sensitivity
Use When
1 78 Vac
Low
Use only for extreme conditions of low
input voltage. Not recommended for
computer loads.
2 83 Vac
Medium
Back-UPS frequently goes On Battery
due to low input voltage.
3 88 Vac
High
(factory default)
Connected equipment is sensitive to
low voltage (recommended).
TRANSFER VOLTAGE AND SENSITIVITY
ORDER REPLACEMENT BATTERY CARTRIDGE
The battery cartridge in the Back-UPS typically lasts 3-6 years, shorter if subjected to frequent outages or elevated temperatures. Note: Batteries in
the battery pack are not user-replaceable. The battery cartridge and battery pack can be ordered online at www.apc.com. For the Back-UPS, order part
number RBC33; for the battery pack order BR24BP. Please recycle spent battery cartridges.
990-2121 1/03 Copyright © 2003 American Power Conversion All rights reserved.
APC, PowerChute plus Personal Edition, and Back-UPS are registered trademarks of American Power Conversion.
All other trademarks are the property of their respective owners.
ADJUSTMENT