Aclara Power Line Systems Y72160-301 Wireless Meter Reading System User Manual RF

Aclara Power-Line Systems Inc. Wireless Meter Reading System RF

Users Manual

Download: Aclara Power Line Systems Y72160-301 Wireless Meter Reading System User Manual RF
Mirror Download [FCC.gov]Aclara Power Line Systems Y72160-301 Wireless Meter Reading System User Manual RF
Document ID672869
Application IDgC8eII6dLDwW+dmXvON9+g==
Document DescriptionUsers Manual
Short Term ConfidentialNo
Permanent ConfidentialNo
SupercedeNo
Document TypeUser Manual
Display FormatAdobe Acrobat PDF - pdf
Filesize252.07kB (3150832 bits)
Date Submitted2006-06-23 00:00:00
Date Available2006-06-21 00:00:00
Creation Date2006-06-09 07:45:51
Producing SoftwareAcrobat Distiller 7.0.5 (Windows)
Document Lastmod2006-06-09 08:02:21
Document TitleRF.book
Document CreatorFrameMaker 7.2
Document Author: bakers

DRAFT
TWACS - ORION FOR CENTRON METER
USER GUIDE
Y10426-TUM
DRAFT
Proprietary Notice
Information contained in this document is private to Distribution Control Systems, Inc., St. Louis,
Missouri (DCSI). This information may not be published, reproduced, or otherwise disseminated without
the express written authorization of DCSI.
Any software or firmware described in this document is furnished under a license and may be used or
copied only in accordance with the terms of such license.
Disclaimer
The information in this document is subject to change without notice and should not be construed as a
commitment by DCSI. DCSI assumes no responsibility for any errors that may appear in this document.
Changes not expressly approved by the party responsible for compliance could void the user's authority to
operate the equipment.
DRAFT
No responsibility is assumed for the use or reliability of software on equipment that is not supplied by
DCSI.
TWACS, the TWACS logo, and the DCSI logo are registered trademarks of Distribution Control Systems,
Inc., St. Louis, Mo. All other registered trademarks are property of their respective owners.
TWACS®
Two-Way Automatic Communication System,
a product of
Distribution Control Systems, Inc.
Confidential and Proprietary
Copyright 2006 All Rights Reserved
TWACS® - ORION® for CENTRON® Meter User Guide
(Y10426-TUM)
DRAFT
Table of Contents
Figures and Tables
iii
Using this Manual
Purpose . . . . . . .
Warnings . . . . . . .
Icon Definitions . . . .
Related Documentation
Support . . . . . . .
Let Us Know How We’re
. . .
. . .
. . .
. . .
. . .
Doing
Chapter 1: Installation and Operation
DRAFT
System Overview . . . . . . . . . . . . . . . .
Theory of Operation . . . . . . . . . . . . . . .
Electric Meter Transceiver (EMTR-2) . . . . . . .
Badger Meter, Inc. ORION® Transmitter . . . . .
Hand Held Transceiver - Low Power (HHTR-LP) . .
Navigating the HHTR-LP Screens . . . . . . .
HHTR-LP Menus . . . . . . . . . . . . . . .
RF Hardware Installation. . . . . . . . . . . . .
Pre-Installation Field Survey . . . . . . . . . .
Environmental Conditions . . . . . . . . . .
Installing a New EMTR-2 Module . . . . . . . . .
ORION Equipment Installation . . . . . . . . . .
ORION Equipment Replacement . . . . . . . . .
Installing a Replacement EMTR-2 Module . . . . .
Replace the Remt List In the EMTR-2. . . . . . .
ORION and EMTR-2 Communication Setup . . . . .
Install the ORION (Linking the ORION and EMTR-2)
Confirm ORION Installation . . . . . . . . . .
No ORION Data Received During the Install . . .
Delete the ORION from the Remt List . . . . . .
Chapter 2: Testing, Troubleshooting, and Maintenance
Troubleshooting and Error Messages.
TNS Troubleshooting . . . . . . .
Field Troubleshooting. . . . . . .
Configuration/Installation Status
HHTR-LP Displayed Error Codes .
Meter Shop Test System . . . . . .
Maintenance . . . . . . . . . . .
Warranty . . . . . . . . . . . . .
Return Procedures. . . . . . . . .
Chapter 3: Specifications
.6
.7
.8
.9
10
11
11
13
13
13
15
16
16
16
16
20
20
22
22
23
27
28
28
28
29
32
34
35
35
35
37
Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . 38
Electrical Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Compliance Specifications . . . . . . . . . . . . . . . . . . . . . . . 38
TWACS® - ORION® for CENTRON® Meter User Guide
Table of Contents
Environmental Specifications . . . . . . . . . . . . . . . . . . . . . . . 39
Physical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . 39
41
Glossary
45
Index
53
DRAFT
Acronyms
ii
TWACS® - ORION® for CENTRON® Meter User Guide
Figures and Tables
Electric Meter Transceiver . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
ORION transmitters for water, gas, and remote . . . . . . . . . . . . . . 9
ORION transmitter specifications. . . . . . . . . . . . . . . . . . . . . . . . 9
Hand Held Transceiver keypad functions. . . . . . . . . . . . . . . . . . 10
Error Code Description and Solution. . . . . . . . . . . . . . . . . . . . . 32
Return address label . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Electrical ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Compliance specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Environmental specifications . . . . . . . . . . . . . . . . . . . . . . . . . 39
Physical specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Labeling requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
DRAFT
Figure 1.1
Figure 1.2
Table 1.1
Figure 1.3
Table 2.1
Figure 2.1
Table 3.1
Table 3.2
Table 3.3
Table 3.4
Table 3.5
TWACS® - ORION® for CENTRON® Meter User Guide
iii
DRAFT
Figures and Tables
iv
TWACS® - ORION® for CENTRON® Meter User Guide
USING THIS MANUAL
DRAFT
This section contains information that helps you understand and use this
manual.
TWACS® - ORION® for CENTRON® Meter User Guide
Purpose
Purpose
This TWACS® - ORION ®for CENTRON® Meter User Guide contains
theory of operation, pre-installation considerations, hardware installation
procedures, and instructions for using an Hand Held Transceiver - Low
Power (HHTR-LP) tool to establish the communication link between the
ORION® and EMTR-2.
DRAFT
Warnings
TWACS® - ORION® for CENTRON® Meter User Guide
Using this Manual
Icon Definitions
Icon
Definition
HAZARD
Indicates electrical equipment hazards and resulting death or
serious injury from misuse.
WARNING
Indicates a potentially hazardous situation which - if
precautions are not taken - could result in death or serious
personal injury.
DRAFT
CAUTION
Indicates a potentially hazardous situation which- if
precautions are not taken - may result in minor or moderate
injury.
IMPORTANT Provides information that is important, but will not result in
NOTE
physical injury if not followed.
Provides additional information or tips on the process.
Related Documentation
The following publications are referenced in this manual. The DCSI
documents listed below plus the latest version of all other DCSI technical
publications are available through the TWACS® Portal (https://
portal.twacs.com/).
• Electronic Metering Transponder for CENTRON Meter User Guide
(Y10317TM)
• TNS End User Guide (Y10285TM)
• Returned Merchandise Packing Requirement Service Advisory
(Y10377TM)
• Stationary RCE Test Unit Technical Manual (Y103018-1TM)
• Portable RCE Test Unit Technical Manual (Y10327-3TM)
• CENTRON Meter Technical Reference (RES-CEN-0025-08.02)
• Pit ORION Installation Data (ORI-I-36)
• Universal 1 Tranamitter Installation Data (ORI-I-39)
• Recordall Transmitter Register Remote ORION 3-Wire Installation Data
(ORI-I-35)
• ORION Integral Transmitter for Gas Meters Installation and Operation
Manual (ORI-IOM-39)
• ORION Equipped Gas Meters Using the Badger-Radix Programming Tool
Installation and Operation Manual (ORI-IOM-40)
• ORION Programming Software Installation and Operation Manual
(ORI-IOM-38)
TWACS® - ORION® for CENTRON® Meter User Guide
Support
Support
Please address your questions to Customer Care as follows:
E-mail:
care@twacs.com
Phone:
1-800-892-9008
Address: Distribution Control Systems, Inc.
945 Hornet Drive
Hazelwood, MO 63042
USA
DRAFT
Let Us Know How We’re Doing
In an ongoing effort to produce effective documentation, the Technical
Publications department at DCSI welcomes any feedback you can offer
regarding this manual.
Please relay feedback, including suggestions for improvement or to alert us
to corrections, by sending an email to techpubs@twacs.com or calling
Customer Care at 1-800-892-9008.
TWACS® - ORION® for CENTRON® Meter User Guide
CHAPTER
CHAPTER 0
INSTALLATION AND OPERATION
CHAPTER0
DRAFT
This chapter provides a brief overview of the TWACS-ORION system,
explains how the TWACS-ORION system interfaces with the TWACS
system, and describes the functions of the EMTR-2, HHTR-LP, and ORION
transmitter. It is useful for installers and personnel who would benefit
from an overview of the entire system.
TWACS® - ORION® for CENTRON® Meter User Guide
System Overview
System Overview
The TWACS - ORION system utilizes radio frequency (RF) transmission
communication between a RF-enabled auxiliary meter and a RF-enabled
CENTRON meter. Data relative to energy usage from auxiliary gas, water,
or another electric meter can be gathered and retrieved in this manner. The
system provides selectable Total Consumption data and Present
Consumption data based on the hourly interval meter reading.
Information is retrieved across the Two-Way Automatic Communication
System (TWACS) network by the TWACS Net Server (TNS) located at the
utility company.
DRAFT
The TWACS - ORION system solution is comprised of the following RF
devices:
NOTE
• Electric Meter Transceiver (EMTR-2)
• Hand Held Transceiver - Low Power (HHTR-LP)
• Electronic Metering Transponder (EMT-3C-MP)
Also part of the system, but not provided or installed by DCSI, is the
Badger Meter, Inc. ORION transmitter that is installed at the auxiliary
meter and converts the meter information into electronic signals.
RF communication links the ORION (located at the auxiliary meter) to the
EMTR-2 (located inside a nearby electric meter.) This communication
enables successful operation of the Automatic Meter Reading (AMR)
system.
AUXILIARY
METER
RF
COMMUNICATION
UP TO 400 FEET
LINE-OF-SIGHT
ORION
TRANSMITTER
ELECTRIC
METER
ELECTRIC
METER
TRANSCEIVER
(EMTR)
TWACS® - ORION® for CENTRON® Meter User Guide
Installation and Operation
Theory of Operation
The DCSI TWACS® - ORION® system operates within the 916.450 MHz
UHF radio frequency range on channel 43A. This unlicensed frequency band
is known as the ISM (Industrial, Science, and Medical) band. All components
in the DCSI TWACS® - ORION®system comply with FCC (Federal
Communications Commission) rules and regulations for radio devices
operating in this frequency range.
DRAFT
This band provides up to 79 channels; the TWACS® - ORION® system uses
51 of these channels. A channel is defined as a pair of adjacent frequencies
used for transmission and for reception. Refer to the note below.
Because the FCC limits the amount and duration of channel energy that can
be emitted during RF transmission, the TWACS® - ORION® system employs
transmission Frequency Shift Keying (FSK). This modulation and frequency
hopping technology serves to:
• Comply with FCC regulations
• Reduce potential interference to and from other devices operating in the
same band
• Reduce the potential for eavesdropping
• Minimize the effects of signal reduction
NOTE
Frequency hopping employs an algorithm that provides a half duplex (one
transmission direction at a time [send or receive]), pseudo-random
sequence of frequencies for the two-way radio link.
Frequency Shift Keying modulation controls data transmission by
“frequency shifting” between two frequencies (a channel). One
frequency is used to represent the logical “1” and a different frequency
represents the logical “0”.
Five channels provide link acquisition with the HHTR-LP while the
remaining 45 channels are used for data transmission after a successful link is
established. The one remaining channel is used for TWACS-ORION
communication.
The EMTR-2 retains data until new data is uploaded during an ORION
session. If an ORION transmitter is removed from the Remt List table stored
in the EMTR-2, the previously loaded data (for the removed ORION
transmitter) is automatically deleted.
TWACS® - ORION® for CENTRON® Meter User Guide
Theory of Operation
Electric Meter Transceiver (EMTR-2)
The EMTR-2 is an electronic module assembly (EMA) that is installed in a
TWACS-enabled CENTRON meter. The EMTR-2 is connected to the
EMT-3C-MP transponder during meter/transponder integration. The
EMTR-2 adds functionality to the host EMT-3C-MP. It does not
communicate over the power line, but uploads the data to the EMT-3C-MP
that has power line TWACS capabilities.
DRAFT
The EMTR-2 can communicate with up to four ORION transmitters. Data
from the ORION transmitter is relayed to the EMA. This data is accessed
by the TNS across the TWACS network.
Near the top of the hour, the EMTR-2 listens (for 12.5 seconds) for
communication from an ORION transmitter. Then, for 8.5 seconds the
EMTR-2 listens for an HHTR-LP. This pattern cycles 35 times. No further
communication occurs until the next top of the hour. The top of the hour is
set in TNS. Refer to Metering Maintenance in the TNS User Guide for
instructions.
Figure 1.1 Electric Meter Transceiver
TWACS® - ORION® for CENTRON® Meter User Guide
Installation and Operation
Badger Meter, Inc. ORION® Transmitter
The DCSI RF TWACS System and the Badger Meter, Inc. ORION
transmitter are capable of data communication. The ORION module uses the
RF bubble-up broadcast mode to communicate (one way) from the auxiliary
meter to the electric meter. The ORION transmitter sends customer usage
data (at 100Kbps) every five seconds on the 916.450 MHz frequency channel.
The RF TWACS system receives this data and transmits it to the EMTR-2.
Then it is retrieved by the utility, across power distribution lines.
Figure 1.2 ORION transmitters for water, gas, and remote
GAS
ORION
DRAFT
WATER
ORION
REMOTE
ORION
Specifications:
Table 1.1
ORION transmitter specifications
ORION
Specification
Description
Power
Functional Life Expectancy
3.6 VDC embedded battery
Minimum: 10 years
Expected: 15 years
916.450 MHz
Burst mode fixed length
packet, simplex
3-of-6
100 Kbps + 1 Kbps
None
Frequency Shift Keying (FSK)
Non Return to Zero (NRZ)
Single channel (43A)
400 ft. clear line of sight affected by installation and
conditions; less if pit installed
Frequency
Data Communications
Data Format
Data Rate
Data Encryption
Modulation
Packet Encoding
Channels
Range
TWACS® - ORION® for CENTRON® Meter User Guide
Theory of Operation
Hand Held Transceiver - Low Power (HHTR-LP)
The DCSI Hand Held Transceiver - Low Power (HHTR-LP) is used to
configure and setup the EMTR-2 (installed in the electric meter). The
HHTR-LP is also used to create the communication link between the
EMTR-2 and the ORION transmitter and can be used to test the radio link.
DRAFT
Figure 1.3 Hand Held Transceiver keypad functions
10
TWACS® - ORION® for CENTRON® Meter User Guide
Installation and Operation
Navigating the HHTR-LP Screens
Use the arrow buttons to navigate through the HHTR-LP screens.
Table 1.2
HHTR-LP screen navigation buttons
Button Number Graphic Function
DRAFT
NOTE
Move left
Move up
Move right
Move down
When pressing the 7, 8, 9, or 0 numeric button, the HHTR-LP
automatically determines whether the numeric or scroll functionality of
the button is required.
Adjust the display contrast by using the number 2 and 3 buttons as follows:
• Increase the contrast - Hold down the Shift button and repeatedly press
the number 2 button.
• Decrease the contrast - Hold down the Shift button and repeatedly press
the number 3 button.
Esc button functionality:
• Press once to end the current procedure and return to the previous menu.
• Repeatedly press to “back out” to previous menus.
HHTR-LP Menus
The following list describes the menus and selections available from the
HHTR-LP.
Main Menu Item
Order - Main menu selection.
• New/Go - Presents screens that allow entry of an order number.
Remote - Main menu selection.
• Orion - Top-level Orion menu.
•
Install (See page 20).
TWACS® - ORION® for CENTRON® Meter User Guide
11
Theory of Operation
•
Com Stat - Presents configuration status screens (See page 29).This
status information is read from the EMTR-2.
• RMTR - RMTR menu. Not used in the TWACS-ORION System.
EMTR - Main menu selection.
• Status - Presents EMTR-2 status data screens.
• Replace - Presents screens that enable replacement of the EMTR-2 (See
page 16).
• Delete - Presents screens that enable removal of the ORION from the Remt
List (See page 16).
• Remt List - Displays list of linked ORION transmitters.
DRAFT
Serial Com - Not used.
12
TWACS - Main menu selection.
• HRTS - Enables configuration of meter auxiliary ports.
• TWACS Modem - Not used.
HHTR Config - Main menu selection.
• Setup - Presents screens that enable selection of HHTR-LP options.
• Status - Not used.
• Power - Presents screens that enable selection of Power options.
• Diags - Presents screens that enable selection of Diagnostic options.
TWACS® - ORION® for CENTRON® Meter User Guide
Installation and Operation
RF Hardware Installation
This section provides instructions for installing the RF hardware onsite. A
functioning network can be created and its functionality verified before
leaving the site.
Pre-Installation Field Survey
DRAFT
The field survey is used to review the environmental conditions present at any
particular location and lay out the system to maximize performance. DCSI
recommends that you conduct a field survey before performing the actual
hardware installation.
As with all RF devices, certain environmental conditions must be present to
optimize RF communications. Be aware of the factors that affect the radio
transmission between the ORION and the EMTR-2 when performing the
field survey, such as:
• Metal objects
• Thick walls or foliage
• Local radio interference
• Position of the ORION and/or EMTR-2
Factor in all environmental conditions when planning the location of the
meter/EMTR-2 assembly.
NOTE
A clear line of sight between the ORION transmitter and receiver is
preferred, but is not always attainable.
The following section discusses the environmental conditions that may affect
RF transmissions between the ORION and EMTR-2.
Environmental Conditions
Optimal RF communication between the ORION and the EMTR-2 is affected
by many environmental conditions. Vehicular traffic, parked vehicles in the
signal path, weather conditions, construction, and even the growth of foliage
may affect or degrade RF communication.
Gradual loss of communication from the ORION (caused by an aging battery
for example) can be detected through system checks by the TWACS Net
Server (TNS) Master Station. Persistent loss of communication may indicate
environmental interference and require a site visit to determine the cause.
NOTE
Sites that continue to experience persistent loss of communication may
require a wired solution to ensure reliable operation.
TWACS® - ORION® for CENTRON® Meter User Guide
13
RF Hardware Installation
The following environmental factors or conditions may affect RF
transmission between the ORION unit and the EMTR-2 located at the
electric meter.
• Metal Objects
Metal objects significantly reduce the strength of the signals reaching
the receiver. Ensure that no metal cladding, cabling, mirrors, water
tanks, refrigerators, pipes, etc. are near the ORION or EMTR-2. The
straight-line path between both units should be as unobstructed as
possible.
NOTE
A small, single item, such as a pipe situated half-way between the
transmitter and receiver, is less likely to have any affect on the signal
strength than a larger item(s).
DRAFT
• Thick walls or foliage
NOTE
Thick walls or foliage between the transmitter and receiver can
reduce the signal strength. Brick, aluminum siding, thick stone walls,
and concrete can impede signal reception.
Avoid dense foliage between the RF units and, when possible,
provide a reserve “growth” clearance to accommodate the growth of
foliage on bushes and trees during spring and summer.
Radio signals can pass more easily through plasterboard walls,
fiberglass, and wood paneling than the previously listed materials.
• Local radio interference
The close proximity of a cell phone mast, a taxi operator's base
station, or large electrical equipment may provide strong radio
interference. The AMR radio devices should be relocated if these
interferences are present.
• Position of the ORION and/or EMTR-2
These are important factors in RF deployment. The ORION antenna
is omni-directional. The signal radiates 360 degrees. The EMTR-2
antenna alignment is parallel to the front cover of the electric meter,
and is the most sensitive RF reception surface.
Face the front of the meter/EMTR-2 toward the ORION transmitter
when possible; even on opposite sides of a building. This allows
maximum communication surface and distance between the units.
Allow for some additional power margin in the signal strength to
accommodate seasonal or other changes in environmental conditions.
In the future, after installation, the site owner should inform you of any
alterations to the site that could affect radio performance.
14
TWACS® - ORION® for CENTRON® Meter User Guide
Installation and Operation
Installing a New EMTR-2 Module
This procedure installs an EMTR-2 module by installing an RF-equipped
CENTRON meter.
Technicians must install this equipment in accordance with all National and
Local Code provisions.
WARNING WARNING - EXPLOSIVE HAZARD - Substitution of components may impair
suitability for Class I, Division 2.
DRAFT
CAUTION
Wear all safety equipment according to your utility rules before opening
the meter base: hard hats, safety face shield, fire retardant clothing,
high voltage rated gloves, safety rated shoes.
WARNING Any work on or near energized meters, meter sockets, or other metering
equipment can present a danger of electrical shock. Such shock could cause
serious injury or death.
To field install a new EMTR-2-equipped CENTRON meter, refer to the
Electronic Metering Transponder for CENTRON Meter User Guide
(Y10317TM).
To complete the installation process, the meter must be configured into the
TNS (refer to the TNS End User Guide for directions). In order to complete
this next step in the installation process, record the location of the meter by
collecting the following information:
•
•
•
•
•
•
•
TWACS Serial number (required)
Substation (required)
Bus
Feeder
Phase
Detection
Signal
The TNS operator uses this location information to search for the meter. The
more pieces of location information available, the less time TNS will take to
search for the meter.
Refer to the TNS End User Guide for data retrieval instructions.
TWACS® - ORION® for CENTRON® Meter User Guide
15
RF Hardware Installation
ORION Equipment Installation
Follow the Badger Meter, Inc.equipment installation instructions to install
the ORION transmitter.
Installers must install the ORION equipment in accordance with all
National and Local Code provisions.
ORION Equipment Replacement
Follow the Badger Meter, Inc.equipment instructions to remove and
replace an existing ORION transmitter.
Installers must perform these procedures in accordance with all National
and Local Code provisions.
DRAFT
Installing a Replacement EMTR-2 Module
NOTE
This procedure is the same as installing a new EMTR-2-equipped meter.
Previous usage data must be retrieved and ORION/EMTR-2 linkage
information must be reassigned to the replacement EMTR-2.
1.
Refer to Installing a New EMTR-2 Module on page 15 for
installation instructions.
2.
Refer to ORION and EMTR-2 Communication Setup on page 20 for
linkage assignment instructions.
Refer to the TNS End User Guide for data retrieval instructions.
Replace the Remt List In the EMTR-2
This procedure downloads the Remt List from the existing EMTR-2 to the
HHTR-LP so the Remt List can be uploaded to the replacement EMTR-2.
Two important conditions apply to this procedure:
1.
NOTE
If communication is not possible, this procedure can not be performed.
Replace the existing meter according to your utility procedures, and
perform Install the ORION (Linking the ORION and EMTR-2) on
page 20 to install the individual ORION transmitters.
2.
16
The existing EMTR-2 must be able to communicate with the
ORION for the Remt List to be downloaded to the HHTR-LP to
simplify reinstalling applicable ORIONs.
This procedure requires the physical removal of the existing
installed meter and installation of a replacement meter/EMTR-2
combination.
TWACS® - ORION® for CENTRON® Meter User Guide
Installation and Operation
Perform the following procedure to replace an EMTR-2.
If you pressed the HHTR-LP On/Off button at the end of any previous
procedure, begin with step 1.
-ORIf you pressed the Esc button, begin with step 2.
1.
Press the On/Off button on the HHTR-LP.
Main Menu
Order
Serial Com
REMOTE
TWACS
HHTR Config
EMTR
DRAFT
2.
Press the down arrow button to position the cursor in front of the
REMOTE option.
Main Menu
Order
Serial Com
REMOTE
TWACS
HHTR Config
EMTR
3.
Press the down arrow button to position the cursor in front of the
EMTR option.
Main Menu
Order
Serial Com
REMOTE
TWACS
HHTR Config
EMTR
4.
Press the Enter button. The EMTR menu appears.
EMTR Menu
Select
Replace
Delete
Status
Remt. List
5.
Press the Enter button. The following screen appears.
EMTR: Replacement
Select:
Read Old EMTR
Write New EMTR
6.
Press the Enter button. The following screen appears.
TWACS® - ORION® for CENTRON® Meter User Guide
17
RF Hardware Installation
EMTR: Replacement
Verify Order #
XXXXX
ESC: No, Enter: Yes
7.
Enter an Order number if different from that displayed and press
Enter to Accept.
The following screen appears.
DRAFT
EMTR: Replacement
Enter Serial Number
Old S/N: _________
Enter To Accept
8.
Press the Enter button. The following two screens appear.
EMTR: Replacement
EMTR S/N 1234567890
Receiving Remote Lst,
EMTR: Replacement
EMTR S/N 1234567890
Success!
NOTE At this point in the procedure, the technician must replace the “old”
utility meter with a replacement integrated meter/EMTR-2 combination.
Refer to Installing a New EMTR-2 Module on page 15.
9.
Press the Esc button once and the following screen appears.
EMTR: Replacement
Select:
Read Old EMTR
Write New EMTR
10.
Press the Enter button. The Order Number screen appears.
EMTR: Replacement
Verify Order #
XXXXX
ESC: No, Enter: Yes
11.
18
Enter the order number and press the Enter button. The following
screen appears.
TWACS® - ORION® for CENTRON® Meter User Guide
Installation and Operation
EMTR: Replacement
Enter Serial Number
New S/N: ___________
Enter To Accept
12.
Press the Enter button. The following two screens appear.
EMTR: Replacement
DRAFT
Verifying New EMTR,
Please Wait...
EMTR: Replacement
EMTR S/N 1234567890
Success!
13.
Press the Esc button three times to return to the Main Menu screen.
-ORPress the On/Off button.
TWACS® - ORION® for CENTRON® Meter User Guide
19
ORION and EMTR-2 Communication Setup
ORION and EMTR-2 Communication Setup
This section describes the steps required to use the HHTR-LP to configure,
link, and remove/replace an ORION or EMTR-2.
RF equipment setup procedures consist of configuring the EMTR-2 and
making the RF communication link between the ORION and EMTR-2.
You may also view the communication statistics (Refer to
Field Troubleshooting on page 28), or test the link between the ORION and
EMTR-2 by reading the Total Consumption register for the applicable port
and verifying the reading on the auxiliary meter dials.
Install the ORION (Linking the ORION and EMTR-2)
Complete the following steps to link the ORION to a nearby EMTR-2.
DRAFT
1.
Press the On/Off button on the HHTR-LP. The “flash” screen
appears momentarily displaying the software version number.
Firmware Vn.n is replaced with the firmware version number
installed in your HHTR-LP.
DCSI: HHTR-LP
Y72160-301
Firmware Vn.n
Www.twacs.com
The Main Menu screen appears.
Main Menu
Order
Serial Com
REMOTE
TWACS
HHTR Config
EMTR
2.
Press the down arrow once to position the arrow cursor in front of
the REMOTE option.
Main Menu
Order
Serial Com
REMOTE
TWACS
HHTR Config
EMTR
3.
Press the Enter button.
Remote Menu
Select:
ORION
4.
20
Press the Enter button to accept the default selection.
TWACS® - ORION® for CENTRON® Meter User Guide
Installation and Operation
Orion Menu
Select:
Install
Com Stat
5.
Press the Enter button to accept Install.
Orion Install Menu
Enter Serial Number
Orion S/N 123456
Enter To Accept
DRAFT
6.
NOTE
Enter the ORION serial number in the spaces provided, if it is not
automatically entered for you.
The EMTR recognizes only 6-digit numbers. ORION serial numbers (from
BadgerMeter, Inc.) may have more than 6 numbers in the serial number.
Enter only the last 6 digits of the serial number or the EMTR will NOT
recognize the ORION transmitter.
7.
Press the Enter button.
Orion Install Menu
Select:
Water
Nat Gas
Propane
Electric
8.
Press the Enter button.
Orion Install Menu
Enter Serial Number
EMTR S/N 123456
Enter To Accept
9.
Press the Enter button.
Orion Install Menu
EMTR S/N 123456
Orion S/N 123456
EMTR checking tables
Orion Install Menu
EMTR S/N 123456
Orion S/N 123456
EMTR writing tables
TWACS® - ORION® for CENTRON® Meter User Guide
21
ORION and EMTR-2 Communication Setup
Orion Install Menu
EMTR S/N 123456
Orion S/N 123456
EMTR trying Orn. Acq.
DRAFT
Orion Install Menu
EMTR S/N 123456
Orion S/N 123456
EMTR checking EnrTbl
NOTE
Orion Install Menu
EMTR S/N 123456
Orion S/N 123456
Success!
10.
Press any key and the following screen displays.
Orion Install Menu
Success!
Reading: 01234567890
RSSI: 255
11.
Press the Esc button to return to the ORION Menu.
If you receive a message from the Error Codes list, press the Esc
button, then repeat steps 5-9. Refer to HHTR-LP Displayed Error
Codes on page 32 for error code description and resolution.
Your previously selected options will appear on the screens when you
repeat steps 5-9. Make new selections or entries, or press the Enter
button to accept each correct entry.
Confirm ORION Installation
You may confirm that the ORION transmitter was successfully installed by
performing a Remote List query.
No ORION Data Received During the Install
If you receive the following message after step 9. of the Install
procedure...
Orion Install Menu
EMTR S/N 123456
Orion S/N 123456
SSI=0 Esc:OK Ent:Rpt
22
TWACS® - ORION® for CENTRON® Meter User Guide
Installation and Operation
12.
Press the Enter button to recheck. The EMTR-2 attempts to reacquire
the ORION signal. If the EMTR-2 is successful, the “success” screen
shown in step 9 displays.
13.
Press the ESC button and the following two screens display.
Orion Install Menu
EMTR S/N 123456
Orion S/N 123456
Warn: No Orion Data
DRAFT
Orion Install Menu
Warn: No Orion Data
Reading: 0
RSSI: 0
14.
Press the ESC button to return to the ORION Menu
Refer to Troubleshooting and Error Messages on page 28.
Delete the ORION from the Remt List
If your ORION and EMTR-2 are not communicating, or if you need to
replace a malfunctioning ORION module, this procedure provides the
instructions to delete the ORION from the Remt List stored in the EMTR-2.
Complete the following steps to delete the ORION from the EMTR-2.
1.
Press the On/Off button on the HHTR-LP.
Main Menu
Order
Serial Com
REMOTE
TWACS
HHTR Config
EMTR
2.
Press the down arrow button twice to position the cursor in front of
the EMTR option.
Main Menu
Order
Serial Com
REMOTE
TWACS
HHTR Config
EMTR
3.
Press the Enter button.
EMTR Menu
Select
Status
Delete
Remt List
Replace
TWACS® - ORION® for CENTRON® Meter User Guide
23
ORION and EMTR-2 Communication Setup
Use the arrow buttons to select Delete.
5. Press the Enter button. The Remote Menu appears.
4.
Remote Menu
Select:
ORION
6.
Press the Enter button.
DRAFT
EMTR: Delete Orion
Enter Serial Number
EMTR S/N:_______
Enter To Accept
7.
Enter the serial number of the EMTR-2 in the EMTR-2 S/N field, if
it is not automatically entered for you.
8.
Press the Enter button.
EMTR: Delete Orion
Enter Serial Number
Orn. S/N:_______
Enter To Accept
9.
Enter the Orion serial number in the Orn. S/N field, if it is not
automatically entered for you.
10.
Press Enter to accept.
The following two screens display briefly.
EMTR: Delete Orion
EMTR S/N 123456
Orion S/N 123456
Receiving Remote List
EMTR: Delete Orion
EMTR S/N 123456
Orion S/N 123456
Found Orion, Del’ing
The Success! screen displays, indicating that the ORION has been
successfully removed from the Remt List table stored in the
EMTR-2.
24
TWACS® - ORION® for CENTRON® Meter User Guide
Installation and Operation
EMTR: Delete Orion
EMTR S/N 123456
Success!
Press the Esc button twice to return to the Main Menu screen.
DRAFT
11.
TWACS® - ORION® for CENTRON® Meter User Guide
25
DRAFT
ORION and EMTR-2 Communication Setup
26
TWACS® - ORION® for CENTRON® Meter User Guide
CHAPTER
TESTING, TROUBLESHOOTING, AND
MAINTENANCE
DRAFT
This chapter explains how to test and manage typical TWACS-ORION
system problems. It is useful for installers and meter shop personnel.
TWACS® - ORION® for CENTRON® Meter User Guide
27
Troubleshooting and Error Messages
Troubleshooting and Error Messages
The following troubleshooting information can be used to determine the
cause of improper operation of the TWACS-ORION system.
TNS Troubleshooting
The TNS system can be used to check module and meter communication.
The TNS system includes error flags in returned messages that aid in issue
identification.
For error codes, refer to the Troubleshooting chapter in the TNS End User
Guide.
DRAFT
For information about TNS Trouble Server Applications, refer to the
Trouble Server Applications in the TNS End User Guide.
Field Troubleshooting
Distribution Control Systems, Inc. has developed various software and
hardware products for testing TWACS-enabled devices in the field and the
meter shop. See the Meter Shop Test System section of this chapter for
information regarding use of this system.
The EMTR-2 has no field serviceable parts. It can only install, delete, or
query installed ORION transmitters.
When necessary, the HHTR can be used to • Install the Orion transmitter (HHTR can not communicate with
Orion)
• Query the EMTR for a remote installed list
• Delete Orion from the EMTR installed list
• Check EMTR status (Hardware & Firmware version, and RCE Type
& Model)
A remote list query by the HHTR gives port-specific information for each
installed Orion transmitter as follows:
• Serial Number
• Present Total Consumption (not current total consumption, but rather
last RF communication total consumption, usually < 1 hr old)
• Leak Detect (tripped by water meter, will reset on its own, or can be
manually reset in the field; see the meter manufacturer
documentation for trip and reset conditions)
• Tamper Detect (must be field reset at water meter)
• RSSI (snapshot-from last check in)
• Acquisition Failures
28
TWACS® - ORION® for CENTRON® Meter User Guide
Chapter 2 • Testing, Troubleshooting, and Maintenance
• 24 Hr Acq Log
If there is a problem, the applicable error code is displayed. For RF
communication, and HHTR-LP or user error codes, refer to HHTR-LP
Displayed Error Codes.
Configuration/Installation Status
You can view additional information about configuration and link status by
selecting Com Stat from the ORION Menu screen. Although this
information is read from the EMTR-2, check the RF Link Data: Acq Log
(refer to step 16. of this procedure) to verify recent successful ORION/EMTR
communication.
Complete the following steps to view configuration and link status data.
DRAFT
1.
Press the On/Off button on the HHTR-LP. The “flash” screen appears
momentarily displaying the software version number. Firmware
Vn.n is replaced with the firmware version number installed in your
HHTR-LP.
DCSI: HHTR-LP
Y72160-301
Firmware Vn.n
Www.twacs.com
The Main Menu screen appears.
Main Menu
Order
Serial Com
REMOTE
TWACS
HHTR Config
EMTR
2.
Press the down arrow once to position the arrow cursor in front of the
REMOTE option.
Main Menu
Order
Serial Com
REMOTE
TWACS
HHTR Config
EMTR
3.
Press the Enter button.
Remote Menu
Select:
ORION
4.
Press the Enter button to accept the ORION default selection.
TWACS® - ORION® for CENTRON® Meter User Guide
29
Troubleshooting and Error Messages
Orion Menu
Select:
Install
Com Stat
5.
Press the down arrow once to position the arrow cursor in front of
the Com Stat option.
Orion Menu
Select:
Install
Com Stat
DRAFT
6.
Press the Enter button.
Orion Com Status
Enter the Serial #,
Orn S/N:_______
Enter To Accept
7.
Enter the ORION serial number in the spaces provided.
8.
Press the Enter button.
Orion Com Status
Enter the Serial #,
EMTR S/N:_______
Enter To Accept
9.
Enter the EMTR-2 serial number in the spaces provided.
10.
Press the Enter button.
The following two screens appear.
Orion Com Status
Collecting data from
EMTR.
Please Wait...
Orion Com Status
EMTR S/N _________
Orion S/N _________
Success!
11.
Press the down arrow or the Enter button.
The following status screen appears.
30
TWACS® - ORION® for CENTRON® Meter User Guide
Chapter 2 • Testing, Troubleshooting, and Maintenance
Orion Com Status
Reading: 1234567890
Battery: N/A
N/V Memory: N/A
•
Reading: displays the number on the ORION. A correct number
(0000000000-9999999999) here verifies proper equipment
operation.
Press the down arrow or the Enter button.
12.
DRAFT
Orion Com Status
Meter Com: N/A
Hist MTR Com: N/A
LeakDet: N
Tamper: N
•
Ignore Meter Com.
•
Ignore the Hist MTR Com entry for installation purposes.
•
LeakDet options are Y or N (Water only). If Y, a site visit is
required to locate the leak. Clear error and reset the meter onsite after
correcting the leak.
Leak detect trips at the meter if total consumption is continuously
incremented. After no continuous consumption for a period of time
(determined by the meter manufacturer) the meter will automatically
reset.
• Tamper options are Y or N. Clear error and reset the meter onsite
after correcting tamper source.
Press the down arrow or the Enter button.
13.
Orion Com Status
RF Link Data:
PA: N/A
RSSI: 123
Link: N/A
•
RSSI (Received Signal Strength Indicator) displays the received
signal strength. The range is 0-255 with 255 being the highest
strength.
14.
Press the down arrow or the Enter button
Orion Com Status
RF Link Data:
Last Ch: N/A
Acq Failures: 0
Ignore this screen for installation purposes.
TWACS® - ORION® for CENTRON® Meter User Guide
31
Troubleshooting and Error Messages
15.
Press the down arrow or the Enter button
Orion Com Status
RF Link Data:
Lnk Abandonment: N/A
Error Code: N/A
Ignore this screen for installation purposes.
16.
Press the down arrow or the Enter button
DRAFT
Orion Com Status
RF Link Data: 24 Hr
Acq Log:00000000
00000000 00000000
The Acq Log displays 24 bits (in three groups of eight) representing
the hourly check-in for the last 24 hours. A one (1) indicates that the
hourly check-in was successful and a zero (0) indicates that it was
not. The least significant bit (bottom right) indicates the past hour
check-in status. Each hour the bits are shifted one position to the
left. In the example below, the ORION successfully checked in the
past hour, but did not for each of the previous three hours.
Acq Log: 11111111
11111101 11110001
17.
Press the On/Off button to turn the HHTR-LP Off.
HHTR-LP Displayed Error Codes
Table 2.1
Error
The following table lists the error code number and error message text that
the HHTR-LP displays when the specific error is encountered while using
the HHTR-LP to communicate with the TWACS-ORION system.
Error Code Description and Solution
Description
The following error codes are RF communication errors.
01 RF Error
General error.
02 Service Not Supported
Service is not supported.
03 Not used
04 Operation Not Possible
RF error.
05 Inappropriate Action
RF error.
Requested
06 RF Device Busy
RF error.
07 Data From Device Not
RF error. (Usually memory)
Ready
31 RF Device Sent NAK
RF error
32
Solution
Retry the command.
Retry the command.
Retry the command.
Retry the command.
Retry the command.
Retry the command.
Retry the command.
TWACS® - ORION® for CENTRON® Meter User Guide
Chapter 2 • Testing, Troubleshooting, and Maintenance
Table 2.1
Error Code Description and Solution
Error
Description
DRAFT
32 Can not acquire an RF Link RF error
33 Operation Timed Out
Operation time expired without
success.
The following error codes are internal HHTR-LP or user
errors.
101 RF PIC sends a NAK
The RFPIC isn't ready or doesn't
understand the command. The RF
PIC internal to the HHTR-LP has
failed.
102 RF PIC is busy
RFPIC is performing another
operation and is currently busy.
The RF PIC internal to the
HHTR-LP was in the middle of
another command.
103 No response from RF PIC The RFPIC isn't responding to the
on HHTR-LP
UI. No Response from the RF
PIC. The RF PIC didn't respond
to the UI processor.
104 RF PIC send invalid
The RFPIC sent an invalid
response
response to the UI. The
HHTR-LP UI processor didn't
recognize the response from the
RF PIC.
105 Operation canceled
Indicates the Esc button was
pressed during an operation.
106 ORION-EMTR session
The HHTR-LP timed out waiting
failed
for the RMTR to respond back to
the HHTR-LP.The HHTR-LP
was unable to link to the
requested EMTR-2.
107 No Space Available in
The EMTR is at capacity. It can
EMTR. The Table is Full. not accept additional Remotess.
112 EMTR already has
Remotes assigned
113 The New EMTR can not
accept xx Number of
Remotes.
114 An order needs to be
created first. Use the order
menu
Can not program a new EMTR
with the data from an old EMTR
because the new EMTR already
has Remotes assigned.
Can not program a new EMTR
with the data from an old EMTR
because the new EMTR can not
store as many Remote as the old
EMTR.
When replacing an EMTR, the
HHTR-LP needs to store the
Remt list. An “order number”
needs to be assigned so that the
HHTR-LP has a location to store
the list.
TWACS® - ORION® for CENTRON® Meter User Guide
Solution
Retry the command.
Retry the command.
Retry the command.
Retry the command.
Retry the command.
Retry the command.
The user aborted the last
command.
Verify the serial number
and retry the command.
A Remote must be
removed before adding
another.
Remove all Remotes from
the new EMTR first.
Select “order” from the
main menu, select “new”
and enter a number.
33
Meter Shop Test System
Table 2.1
Error Code Description and Solution
Error
Description
208 ORION S/N Already
exists in the EMTR Table.
Can not install the selected
ORION because it is already
installed.
Can not remove the ORION nor
perform a Com Status because
that ORION is not installed to the
selected EMTR.
This service in the EMTR is at
capacity. It can not accept
additional Orions.
209 The Selected ORION is
NOT in the EMTR Table.
DRAFT
211 Service is Full, Can not
add ORION to the EMTR
List.
215 The Selected Remt. is
NOT an Orion.
Solution
Check serial number and
try again.
An ORION must be
removed from this service
before adding another.
If you are unable to resolve a problem with the TWACS-ORION system,
return the meter to your integrator or DCSI. See Return Procedures.
Refer to the Electronic Metering Transponder for CENTRON Meter User
Guide (Y10317TM) Rev. A for transponder-related troubleshooting
information.
Refer to the CENTRON Meter Technical Reference Guide for additional
meter information.
Meter Shop Test System
Use the Meter Shop Test System to test TWACS signaling, read select
transponder registers, zero select transponder registers, and perform
various other transponder functions on a TWACS-enabled CENTRON
meter. For complete details on the Meter Shop Test System, see the Meter
Shop Test System Help (accessed by clicking the Help button on the Meter
Shop Test Tool main menu) or contact your Program Manager or DCSI
Customer Care at care@twacs.com or 1-800-892-9008.
Because of the various test equipments available for use with DCSI
products and the configuration requirements/options, the Meter Shop Test
System Set-Up Guide (Y10030TM), will guide you through initial
equipment selection and setup for meter/module testing.
This user guide contains all the module-specific information necessary to
test the RF TWACS-ORION System installed in the CENTRON meter.
EMT-3C module TWACS serial number and meter-specific information is
available on the meter label. Refer to Figure 2.1. Additional information,
such as module Type and Model, can be found in Chapter 1 of this user
guide.
If you are unable to resolve a problem with the TWACS-ORION System,
return the meter to your integrator or DCSI. See Return Proceduresbelow.
34
TWACS® - ORION® for CENTRON® Meter User Guide
Chapter 2 • Testing, Troubleshooting, and Maintenance
Maintenance
The TWACS-ORION system requires no maintenance.
Warranty
Refer to contract terms for warranty information.
DRAFT
Return Procedures
DCSI equipment which has been integrated or retrofitted by a third party,
must be returned to the third party. Please do not return third party integrated
equipment to DCSI. Contact the third party to obtain their “Return
Authorization Number” and shipping instructions and return the equipment
directly to the integrator/retrofitter.
If you are a DCSI certified integrator and the product cannot be repaired in
the meter shop, remove the module and complete the following procedure.
NOTE
Before returning an item to DCSI, refer to your contract terms for
warranty information. If an item is out of warranty, a diagnostic fee may
apply. Please send an email to rma@twacs.com for a diagnostic estimate.
If you have any questions regarding returns, send an email to
rma@twacs.com.
1.
Send an email to rma@twacs.com with the information listed below.
Within 24 hours, excluding weekends and holidays, you will receive
an email acknowledging receipt of your request. After DCSI processes
your request, you will receive a Return Material Authorization (RMA)
number with the shipping instructions. To expedite the process, be
sure to include all the information requested below:
• Company name [Distributor name and location (city and state) if
applicable]
• Ship To name and address
• Contact name, phone number, and email address
• DCSI part number of each item
• Serial number of each item
• Description of each item
• Total quantity (by DCSI part number) for each item
• Specific reason for return of each item
• Manufacturer number (number starting with A/M/V/C/W) of each
RCE item
2.
Once you receive an RMA number, package the IMT-XM according to
the shipping instructions received and following the notes below.
TWACS® - ORION® for CENTRON® Meter User Guide
35
Return Procedures
IMPORTANT
Items should be properly packaged to avoid shipping/handling damage
during transit. Items must be packaged in individual anti-static or
static dissipative bags and packed in sturdy, appropriately sized
commercial boxes with packing material (styrofoam peanuts,
bubblewrap, paper, etc.) arranged to prevent movement; in single
layers; with the appropriate packaging between layers. Original
packaging with dividers should be retained, reused, and re-identified if
possible.
IMPORTANT
Items not packaged in accordance with DCSI packing requirements will
not be accepted and will be returned freight collect. Please refer to
the Returned Merchandise Packing Requirement Service Advisory
(Y10377TM) for DCSI approved methods and materials. Contact DCSI
Customer Care at care@twacs.com to receive a copy of this service
advisory.
DRAFT
3.
36
Mark the outside of the shipping container with the RMA number
on the address label as shown in the following example.
Figure 2.1 Return address label
Upon shipment, send an email to rma@twacs.com with the shipping
information (Carrier Name, Waybill/Pro/Tracking Number, and Date item
left your facility) so DCSI can track the shipment.
TWACS® - ORION® for CENTRON® Meter User Guide
CHAPTER
SPECIFICATIONS
DRAFT
This chapter contains electrical, environmental, and physical specifications
for the EMTR-2 and HHTR-LP.
TWACS® - ORION® for CENTRON® Meter User Guide
37
Electrical Specifications
Electrical Specifications
The electrical specifications include:
• Electrical ratings
• Compliance Specifications
Electrical Ratings
The following table provides the electrical ratings.
Electrical ratings
DRAFT
Table 3.1
Parameter
Rating
Voltage
Quiescent power
Maximum input surge
Internal fusing
Grounding
Electronics connection
6V<=V<=12V
25mA approximate
100mA maximum
None
None
The EMTR-2 is connected to the
EMT-3C-MP transponder during
meter/transponder integration.
Electronics isolation
Refer to the Electronic Metering Transponder
for CENTRON Meter User Guide Y10317TM.
Compliance Specifications
NOTE
The following table provides the compliance specifications.
ANSI C12.1-2001 is the referring standard for tests listed in tables 5.2,
5.3, and 5.4.
Table 3.2
Compliance specifications
Test Title
Applicable Specification
EMI/RFI Emission
conducted/radiated
ANSI C12.1-2001 Test No. 27- “Radio
Frequency Conducted and Radiated Emissions”
per CFR 47 Part 15, Class A and B. (See also
ANSI C63.4)
ANSI C12.1-2001 Test No. 26- “Effect of Radio
Frequency Interference”
ANSI C12.1-2001/IEEE C62.41-1991 Test No.
17- “Effect of High Voltage Line Surges”
ANSI C12.1-2001 Test No. 25- “Electrical Fast
Transient/Burst” (Testing at 100 and 400 KHz is
required) IEC 801-4: 1988
ANSI/IEEE C.37.90.1 - 2002
EMI/RFI Susceptibility
AC line surge
Electrical fast transient
Surge withstand
capability FT and OSC
38
TWACS® - ORION® for CENTRON® Meter User Guide
Chapter 3 • Specifications
Table 3.2
Compliance specifications
Test Title
Applicable Specification
High voltage isolation on
meter chassis
Voltage interruption test
ANSI C12.1-2001 Test No. 15- “Insulation”
Effect of electrostatic
discharge
Effect of Variation of
Frequency
Effect of Variation of
Voltage on the Metering
Device
DRAFT
NOTE
ANSI C12.1-2001 Test No. 16- “Voltage
Interruption”
ANSI C12.1-2001 Test No. 28- “Effect of
Electric Discharge (ESD)”
ANSI C12.1-2001. Test #6
ANSI C12.1-2001. Test #5.
Per Measurement Canada, Specifications/Standards LMG-EG-07 &
PS-E-09-E are used to verify compliance with Canadian criteria.
Environmental Specifications
The following table provides the environmental specifications.
Table 3.3
Environmental specifications
Thermal
Effect of operating temperature
Per ANSI C12.1-2001 Test No. 30
Humidity
Effect of relative humidity, both
operational and storage
Per ANSI C12.1-2001 Test No. 31
Physical Specifications
The following table provides the physical specifications.
Table 3.4
Physical specifications
Parameter
Specification
Size, weight, form factor
Integrated dimensions
Installation instructions
Meter-specific
Provided with shipping package. One per
TWACS-enabled meter carton.
Compliance Testing Specifications
Mechanical tests
•
•
•
•
Mechanical Shock
Mechanical Vibration
Transportation Drop Test
Transportation Vibration
Per relevant sections of ANSI C12.1 - 2001
described below:
•
•
•
•
Test #32, per IEC 60068 part 2-27
Test #34, per IEC 60068 part 2-6
Test #33, per ISTA Test Procedure 1A
Test #35, per ISTA Test Procedure 1A
TWACS® - ORION® for CENTRON® Meter User Guide
39
Physical Specifications
Table 3.4
Physical specifications
Parameter
Specification
Physical Tamper Protection
Meter seal
Supported
Table 3.5
Labeling requirements
Labeling Requirements and Serial Number
DRAFT
HHTR-LP
Labeling per ANSI C12.10-1987 for:
40
•
•
•
•
DCSI/customer name
DCSI/customer logo
TWACS serial number
Barcode
TWACS® - ORION® for CENTRON® Meter User Guide
Acronyms
Asynchronous Data Link Control
AMR
Automatic Meter Reading
AP
Alternate Pathmaps
ASCII
American Standard Code for Information Interchange
BPA
Backplane Assembly
CCA
Card Cage Assembly
CCE
Central Control Equipment
CIS
Customer Information System
DRAFT
ADLC
CLI
Command Line Interface
CMT
Commercial Meter Transponder
CPSA
CRU Power Supply Assembly
CRA
Correlation Receiver Assembly
CRMA
Correlation Receiver Multiplexer Assembly
CRPA
Correlation Receiver Processor Assembly
CRU
Control and Receiving Unit
CT
Current Transformer
DCPA
Direct Current Power Assembly
DCSI
Distribution Control Systems, Inc.
DP
Diagnostic Pending
DPA
Distribution Panel Assembly
DS
Diagnostic Set
DSI
Disconnect Switch Interbase
EMA
Electronic Metering Assembly
EMTR
Electronic Meter Transceiver
EOM
End of Message
FEP
Front-End Processor
FCC
Federal Communication Commission
FSK
Frequency Shift Keying
GUI
Graphical User Interface
HHTR-LP
Hand Held Transceiver - Low Power
IC
Incomplete IMT/CMT Data
ILS
Integrated Load Survey
TWACS® - ORION® for CENTRON® Meter User Guide
41
Acronyms
Inbound Multiplexer Assembly
IMT
Integrated Metering Transponder
IP
In Progress
IPU
Inbound Pickup Unit
ISM
Industrial, Science, and Medical
KWH
Kilowatt Hours
LCT
Load Control Transponder
LS
Load Survey
MIT
Meter Interface Transponder
MS
Master Station
MSFE
Master Station Field Equipment
DRAFT
IMA
MTU
Modulation Transformer Unit
NA
Invalid Data
NS
Register Not Supported
ODBC
Open Database Connectivity
OFIA
Outbound Fiber Optics Interface Assembly
OK
Successful Read
OMU
Outbound Modulation Unit
OPA
Outbound Processor Assembly
PD
Partial Data
PE
Pending
PR
Pending Retry
QC
Quality Code
RC
Reasonability Check Failed
RCE
Remote Communications Equipment
RF
Radio Frequency
RI
Reset In Progress
RL
Register Length Invalid
RM
Read Meter
RMTR
Remote Meter Transceiver
RO
Retry Override
RPA
Receiver Processor Assembly
RSSI
Received Signal Strength Indicator
SCADA
Supervisory Control and Data Acquisition
SCE
Substation Communications Equipment
42
TWACS® - ORION® for CENTRON® Meter User Guide
Acronyms
Substation Communications Processor Assembly
SDC
Service Disconnect/Connect
SP
Substation Status
STS
Substation Test Set
TC
Total Consumption
TD
Total Demand
TNS
TWACS Net Server
TOU
Time of Use
TP
Tamper Pending
TS
Tamper Set
TWACS
Two-Way Automatic Communication System
DRAFT
SCPA
UHF
Ultra High Frequency
ZC
Zero Crossing
TWACS® - ORION® for CENTRON® Meter User Guide
43
DRAFT
Acronyms
44
TWACS® - ORION® for CENTRON® Meter User Guide
Glossary
American National Standards Institute (ANSI)
An independent, U.S.-based technical standards organization.
AMR
See Automatic Meter Reading.
ANSI
See American National Standards Institute.
Automatic Meter Reading (AMR)
DRAFT
Electronic accumulation and transport of meter data.
billing demand information
Consists of the demand reset count, which increments, and the demand previous billing.
billing read
Defines the registers used during one-time scheduled reads and on-request reads.
DSHTBill read (Daily Shift Billing)
Defines the registers used during recurring scheduled reads; normally used to create
billing files.
blink count
See power-down count.
bus identification
Identifies the substation bus to which DCSI’s equipment is connect.
CCE
See Central Control Equipment.
Central Control Equipment (CCE)
The top level of the TWACS system hierarchy, also referred to as the Master Station. The
CCE typically resides at the utility home office, providing system control and data
storage for the TWACS system.
CIS
See Customer Information System.
TWACS® - ORION® for CENTRON® Meter User Guide
45
Glossary
CMT
See Commercial Metering Transponder.
Customer Information System (CIS)
A computer database that utilities use to keep track of their customer information
(name, address, phone, meter serial number). Often includes bill printing
functionality.
Commercial Metering Transponder (CMT)
An electronic assembly integrated into a commercial application electric meter to add
TWACS communications capability to the meter.
Daylight Saving Time (DST)
DRAFT
Daylight Saving Time is the practice of turning the clock ahead in the Spring and back
again in the Fall.
delay
The number of minutes after the interval has occurred before the SCE attempts to send
a time sync command to the RCE.
demand
The rate at which power is delivered over a specified period of time; the rate of
consumption. Demand is expressed in kilowatts.
demand interval
The specified interval of time on which a demand measurement is based. Intervals are
commonly specified as 15, 30, and 60 minutes.
demand meter
A metering device that indicates or records demand, maximum demand, or both.
detection point
Identifies the specific conductor on which the inbound signal is detected. This point is
identified as either A phase, B phase, C phase, or neutral.
dial encoder
A device that encodes or converts the position of metering dials (normally used in
water meters) into an electrical signal for subsequent processing and transmission.
DST
See Daylight Saving Time
46
TWACS® - ORION® for CENTRON® Meter User Guide
Electronic Metering Assembly (EMA)
An electronic assembly integrated into an electric meter to add TWACS communications
capability to the meter.
Electronic Meter Transceiver (EMTR)
An electronic communication device that transmits and receives using RF transmission.
EMA
See Electronic Metering Assembly.
EMTR
See Electronic Meter Transceiver.
DRAFT
Federal Communication Commission (FCC)
The Federal Communications Commission (FCC) is an independent United States
government agency, directly responsible to Congress, and is charged with regulating
interstate and international communications by radio, television, wire, satellite and cable.
Among its duties, the FCC is responsible for rating personal computers and other
electronic equipment as either Class A or Class B. The ratings indicate how much
radiation a particular device emits.
feeder identification
Identifies which feeders are connected to which bus(es).
firing angle
The place on the sine wave where the RTS places the TWACS signal.
frequency shift keying
A data transmission control method that modulates, i.e. “shifts” between two radio
frequencies.
hand held transceiver - Low Power (HHTR-LP)
A control device used to set up, link, and establish communication between the EMTR
and Badger components of the TWACS RF system.
industrial, science, and medical (ISM)
An unlicensed radio frequency band.
interval
A relatively short time period over which energy use data is recorded by the transponder.
The interval may be set for 15, 30, or 60 minutes, depending on the transponder type.
Interval data is recorded for each consecutive interval.
TWACS® - ORION® for CENTRON® Meter User Guide
47
Glossary
interval data
A breakdown of consumption over specific intervals of time.
ISM
See Industrial, Science, and Medical.
load profile
Recording, storing, and analyzing consumption data over a period of time for a
particular installation.
master station
See Central Control Equipment (CCE).
DRAFT
maximum demand
The highest demand measured over a selected period of time, such as one month.
Meter Integration and Meter Test (MIMT)
A department within DCSI that reviews utility meter programming files and
determines register programming requirements.
MIMT
See Meter Integration and Meter Test.
nonvolatile memory
A physical data storage area that maintains its content when the power is turned off.
on-demand reads
An unscheduled command to read a register.
ORION Transmitter
A one-way (simplex) radio frequency transmitter, manufactured by Badger Meter Inc.,
that allows retrieval of metering data from pit-set water, water, and gas meters. It
periodically broadcasts a data packet.
PCB
See Printed Circuit Board.
peak demand
See maximim demand.
48
TWACS® - ORION® for CENTRON® Meter User Guide
phase
The current supply conductors, other than the neutral conductor of a polyphase circuit,
that usually carry the designation A phase, B phase, C phase.
power-down count
A voltage interruption greater than 0.1 seconds that the module will count as a power
outage and will increase the power-down count register by one. Sometimes referred to as
blink count.
previous billing demand
The maximum kW, or demand, as recorded at the time of the last reset. This value is
normally used for billing purposes.
DRAFT
previous interval demand
The demand value stored in the meter that reflects the demand prior to the last reset.
Printed Circuit Board (PCB)
A thin plate on which electronic components are placed.
pulser
An electronic or magnetic device that generates electric pulses in a quantity that is
proportional to the physical variable under measurement and which the pulses represent.
rate class
A rate class is a set of registers read for a particular class of customer with a particular
meter model. It defines registers used for Billing and DSHTBill reads.
RCE
See Remote Communication Equipment.
received signal strength indicator (RSSI)
A value indicating the strength of the received radio frequency signal.
registers
Data storage locations on the transponder microprocessor that contain a variety of
information that is retrievable by the master station. The type of data in registers includes
consumption and demand data
TWACS® - ORION® for CENTRON® Meter User Guide
49
Glossary
Remote Communication Equipment (RCE)
The base of the TWACS system hierarchy. RCEs consist of the DCSI family of
transponder products. RCEs are located at customer sites and interface TWACS
communication with various end devices such as meters, water heaters, and air
conditioning units to enable automatic meter reading (AMR), load management, or
other functions.
Remote Test Set (RTS)
A TWACS communications test device used at a remote site to communicate locally,
using TWACS, to a transponder over the power line.
Remote Meter Transceiver (RMTR)
DRAFT
An electronic communication device that transmits accumulated data using RF
transmission. Not used with the TWACS-ORION System.
Remote Acquisition List
A list of Remote Meter Transceivers stored in the EMTR.
RSSI
See Received Signal Strength Indicator.
RTS
See Remote Test Set.
SCE
See Substation Communication Equipment.
Serial Time Unit (STU)
A 2.5 seconds interval of time and the unit of measure of DCSI’s Serial Time system.
The intervals of time begin at 12:00 midnight on a cyclic 24-hour basis. Example:
1:00 a.m. would in serial time:
signal mode
Identifies the path combination used during outbound communications. This
combination can be either line-to-ground or line-to-line.
STU
See Serial Time Unit
50
TWACS® - ORION® for CENTRON® Meter User Guide
Substation Communications Equipment (SCE)
The middle tier of the TWACS system hierarchy, consisting of all TWACS substation
equipment (CRU, OMU, IPU, and MTU). The SCE transmits and receives data between
CCE and RCE.
time-of-use (TOU)
A multiple tiered billing technique based on when the consumer uses the energy.
TNS
See TWACS Net Server.
TOU
DRAFT
See time-of-use
transponders
Two-way field devices that can receive and send messages to and from the substation.
TWACS
See Two-Way Automatic Communication System.
TWACS Net Server (TNS)
Chief component of the entire Two-Way Automatic Communication System. Manages
all collected metering and interval data as well as the connection between the utility and
the consumer’s premises.
Two-Way Automatic Communication System (TWACS)
A patented technology that allows the utility to send and retrieve information to and from
meters and other devices using the utility’s power lines as a communication network.
Ultra High Frequency (UHF)
A frequency range in the radio frequency spectrum between 300 MHz and 3.0 GHz.
window
The amount of time in minutes available after the delay has occurred for the SCE to send
a date/time command.
TWACS® - ORION® for CENTRON® Meter User Guide
51
DRAFT
Glossary
52
TWACS® - ORION® for CENTRON® Meter User Guide
Index
acquisition list, Remt 12, 23, 24
acronyms 41
ANSI 45
labeling requirements 40
line of sight 6, 13
linking, ORION and EMTR 20
Badger Meter, Inc 6
maintenance 35
menus, HHTR
EMTR 12
delete 12
Remt list 12
replace 12
status 12
HHTR Config 12
diags 12
power 12
setup 12
status 12
Remote 11
RMTR 12
TWACS 12
HRTS 12
TWACS modem
care@twacs.com 4
communication 13
compliance specifications 38
current configuration 23
customer care 4
DRAFT
Delete 23
electric meter transceiver 6, 8, 25
electrical ratings 38
electrical specifications 38
EMTR
See electric meter transceiver
environmental specifications 39
error codes 29
FCC
Meter Shop Test System 34
ORION 16, 20, 31
ORION transmitter 9
Com Stat 12
Install 11
See federal communications commission
federal communications commission 7
frequency hopping 7
frequency shift keying 7
FSK
See frequency shift keying
glossary 45
hand held transceiver 6, 10
keypad functions
menus 11
physical specifications 39
purpose 7
radio frequency range 7
return material authorization (RMA) 35
return procedures 35
RF equipment installation
environmental conditions 13
field installing a replacement EMTR module
10
16
HHTR
See hand held transceiver
industrial, science, and medical band 7
ISM band
See industrial, science, and medical band
12
pre-installation field survey
rma@twacs.com 35, 36
RSSI 31
13
safety equipment 15
specifications 37
compliance
TWACS® - ORION® for CENTRON® Meter User Guide
38
53
Index
electrical 38
environmental
physical 39
39
Troubleshooting
Field 32
TNG 28
TWACS - ORION system
electric meter transceiver
hand held transceiver 6
TWACS Net Server (TNS) 6
Two-Way Automatic Communication System (TWACS) 6
DRAFT
warnings 2
warranty 35
54
TWACS® - ORION® for CENTRON® Meter User Guide

Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.6
Linearized                      : No
Page Mode                       : UseOutlines
XMP Toolkit                     : 3.1-702
Producer                        : Acrobat Distiller 7.0.5 (Windows)
Create Date                     : 2006:06:09 07:45:51Z
Creator Tool                    : FrameMaker 7.2
Modify Date                     : 2006:06:09 08:02:21-05:00
Metadata Date                   : 2006:06:09 08:02:21-05:00
Format                          : application/pdf
Creator                         : bakers
Title                           : RF.book
Document ID                     : uuid:25dfc160-231b-434c-97e3-fdccbd9eae92
Instance ID                     : uuid:92d59574-4e5b-45e4-9ad2-95cd8a2f0385
Has XFA                         : No
Page Count                      : 62
Author                          : bakers
EXIF Metadata provided by EXIF.tools
FCC ID Filing: PN3Y72160-301