Adams Rite 80 0180 421_D 4300 Series Electrified Deadlatch Installation Instructions 421 D
User Manual: Adams Rite 4300 Series Electrified Deadlatch Installation Instructions Installation Instructions
Open the PDF directly: View PDF .
Page Count: 2
PRODUCT MUST BE INSTALLED
ACCORDING TO ALL APPLICABLE
BUILDING AND LIFE SAFETY CODES
[20.32]
.182
[15.52]
.611
[3.0]
R.120
"A"
"A"
"A"
BEVEL
RADIUS
FLAT
C
L
C
L
C
L
C
L
C
L
C
L
FOR OPTIMUM LOCK PERFORMANCE, THE
GAP BETWEEN THE DOOR AND FRAME MUST
MEET INDUSTRY STANDARDS OF AN 1/8"
1.010
-
.000
+
.015
25.7 0
+
0.4
"A"
[40.48]
1.594
[174.9]
6.885
STILE PREPARATION
+.38
-.00
R.156
[3.96]
TYP.
+.005
-.000
4.635
117.7
[1.5]
.06
.570
14.5
5.375
136.5
[36.5]
1.437
[70.3]
2.769
RADIUS WEATHER STRIP
RADIUS
FLAT
AVAILABLE FACEPLATES
Adjustable Mounting Tube Bracket
may be removed for mounting on
bridges, tabs, or either methods.
C
L
C
L
CYLINDER
C
L
C
L
DOOR
C
L
TO JAMB EDGE
Drill and c'sk for
#10-32 X 1/2"
Flat Head
Machine Screws
4581
Cam Plug Assy.
(included with 4300)
INSTALLATION
C
L
4581
FRONT VIEW
(Must use a Face Plate for installation)
"A"
.62
15.7
.42
10.6
6.81
173
5.80
147.3
1.587
40.3
1.437
36.5
2.769
70.3
6.38
162
.980
24.9
.63
15.9
1.00
25.4
"B"
6.38
162.1
C
L
BACK OF STILE
2x
#10-32
UNC-2B
Flat Face Plate can be
adjusted for right or left
beveled edge doors.
Radius Weather Strip is
optional.
HOW BACKSET
IS MEASURED
CAM TOLERANCE:
±.005
( ±.13 )
CYLINDER
C
L
DIMENSIONS
Inches
(Millimeters)
Turning Key / Handle / Paddle
DOES NOT pull Main Latch Assy.
OPERATION INSTRUCTION
Press Aux Latch to secure
Main Latch. Turn key, apply
voltage, or operate Paddle/Handle
to unlock Main Latch.
As door opens, Main Latch
pivots and collapses.
[20.32]
.182
[15.52]
.611
[3.0]
R.120
Page of
1
2
INSTALLATION INSTRUCTIONS
Rev.
Appvd: MP
ECN:11899
Date: 03/16/12
D
4300 SERIES ELECTRIFIED DEADLATCH
80-0180-421
Adams Rite Manufacturing Co.
260 Santa Fe Street,
Pomona, CA 91767
Phone: 909-632-2300
Fax: 909-632-2369
www.adamsrite.com
PRODUCT MUST BE INSTALLED
ACCORDING TO ALL APPLICABLE
BUILDING AND LIFE SAFETY CODES
Black = Common
White = N.O. contact (Dry)
Red = N.C. contact (Dry)
Unused wires must be cut
such that no exposed wire
will touch any metallic surface
EXAMPLE WIRING DIAGRAM WITH N.O. MONITORING
Access
Control
System
X
4300
MONITOR
Black
White
Red
4300 WIRING DIAGRAM
INTERMITTENT / CONTINUOUS DUTY 12 / 24V DC
SOLENOID SPECIFICATION
SOLENOID AVAILABLE VOLTAGES
12V DC CONTINUOUS DUTY,
24V DC CONTINUOUS DUTY.
120V AC
LINE
VOLTAGE
4605 / 4606 -24V AC
40 VA TRANSFORMER
RED -
4603
2-AMP
RECTIFIER
RED -
BLACK (-)
4300
ELECTRIFIED DEADLATCH
WHITE (+)
ORANGE
BLUE
YELLOW
BROWN
12V DC
4300
4300
YELLOW
24V DC
ORANGE
BLUE
BROWN
Bevel
Tab
Fig. 4
Yoke
#8-32 x 5/16"
Truss Head Screw
Fig. 3
RHR BEVEL POSITION
LHR BEVEL POSITION
Fig. 5
Dim.
Depth
Inside Stile
wall
Fig. 1
Depth Dim.
3/16"
Hex Key
Mounting
Plate
Tube
Spacer
Fig. 2
FLAT FACE PLATE
NEUTRAL POSITION
Screwdriver
Remove
Bevel
Tabs
Fig. 6
RADIUS WEATHERSEAL
FACEPLATES ONLY
WIRES
BUNDLE
VOLTAGE
ADAPTOR CABLE
4300 SERIES
ELECTRIFIED DEADLATCH
Fig. 7
MONITORING (OPTIONAL)
MONITORED DEADLATCH CONTAINS AN INTERNALLY
MOUNTED SWITCH. THIS SWITCH IS ACTIVATED WHEN
THE DOOR IS IN CLOSE POSITION. ALL UNUSED LEADS
FROM THE MONITOR SWITCH MUST BE INSULATED.
Common contact - Black
Normally Open contact (N.O.) - White
Normally Closed contact (N.C.) - Red
Maximum switching current - 0.1 Amps @ 125 VAC
- LOOP THE WIRES BUNDLE FROM 4300
ELECTRIFIED 'S SOLENOID UNDER AND
AROUND ITS HOUSING AS SHOWN (Fig.7).
- EXTEND THE WIRES RUN FROM THE
POWER SOURCE AND THROUGH THE
STILE PREPARATION.
- CONNECT THE WIRE TO THE VOLTAGE
ADAPTOR CABLE.
- ATTACH VOLTAGE ADAPTOR CABLE
TO 4300 WIRES BUNDLE AS SHOWN.
SOLENOID WIRING DIAGRAM
Note: NOT intend to be a Rex switch.
Page of
2 2
INSTALLATION INSTRUCTIONS
Rev.
Appvd: MP
ECN: 11899
Date: 03/16/12
D
4300 SERIES ELECTRIFIED DEADLATCH
80-0180-421
Adams Rite Manufacturing Co.
260 Santa Fe Street,
Pomona, CA 91767
Phone: 909-632-2300
Fax: 909-632-2369
www.adamsrite.com