Ademco 04007500 Microwave/PIR motion sensor User Manual

Honeywell International Inc. Microwave/PIR motion sensor Users Manual

Users Manual

DT7500SN V-PlexTM DUAL TEC Motion Sensor  - Installation Instructions                              WTTV- V+OPEN / OUVERTURE / APERTURA / APERTURA / OPENLOCATION / EMPLACEMENT / POSIZIONAMENTO / LOCALIZACIÓN / LOCATION  MOUNT / INSTALLATION / MONTAGGIO / MONTAJE / MOUNT3Range AdjustmentRéglage de la portée hyper Regolazione della portata Ajuste del rango de detecciónRange Adjustment 52.1 - 2.4 m(7 - 8 ft)162WIRE / CABLAGE / COLLEGAMENTO / CABLEADO / WIREIDENTIFY COMPONENTS AND SELECT APPROPRIATE SETTINGS / IDENTIFICATION DES COMPOSANTS ET SÉLECTION DES PARAMÈTRES APPROPRIÉS / IDENTIFICARE I COMPONENTI E SELEZIONARE LE IMPOSTAZIONI APPROPRIATE / IDENTIFICAR LOS COMPONENTES Y SELECCIONAR LA CONFIGURACIÓN ADECUADA / IDENTIFY COMPONENTS AND SELECT APPROPRIATE SETTINGS1Polling Loop9 - 13VDCSMB-10TTAMPER24 VDC, 10mA0.3-1.3mm2(22-16 AWG)Cover Tamper SwitchContact AP du capot Interruttore tamper sul     coperchio Tamper de la cubierta Cover Tamper Switch32Rear Tamper Breakaway TabRear Tamper Breakaway TabRear Tamper Breakaway TabRear Tamper Breakaway TabRear Tamper Breakaway TabWWith SMB10T With SMB10T With SMB10T With SMB10T With SMB10T With SMB10T ONOFF1234525%50% 75%100%TT+-WONOFF12345Pulse Count 2Low SensitivityLED Disabled Microwave Walk Test OFFAnti-Mask OFFPulse Count 1High SensitivityLED EnabledMicrowave Walk Test ONAnti-Mask ONLEDREPLACE CIRCUIT BOARD / REMISE EN PLACE DU PCB / RIPOSIZIONARE IL CIRCUITO / VOLVER A COLOCAR LA PLACA DE CIRCUITO IMPRESO / REPLACE CIRCUIT BOARD4If installed with a Smart V-PlexTM Panel:The sensor will not transmit or indicate intrusion alarms when the panel is disarmed; in the armed state, the sensor will respond to all communications to or with the host panel.If installed with a Standard V-PlexTM Panel: The sensor will respond to all communications with the host panel armed or disarmed.ONOFF12345Pulse Count 2Low SensitivityLED Disabled Microwave Walk Test OFFAnti-Mask OFFPulse Count 1High SensitivityLED EnabledMicrowave Walk Test ONAnti-Mask ON<FR> If installed with a Smart V-PlexTM Panel:  The sensor will not transmit or indicate intrusion alarms when the panel is disarmed; in the armed state, the sensor will respond to all communications to or with the host panel.If installed with a Standard V-PlexTM Panel:   The sensor will respond to all communications with the host panel, armed or disarmed.Use these holes when mounting to a standard U.S. electrical junction boxONOFF12Lowest Sensitivity: 3 - 5 Steps; Up to 45 kg (100 lb) Pet ImmunityLowest Sensitivity: 3 - 5 Steps; Up to 45 kg (100 lb) Pet ImmunityLowest Sensitivity: 3 - 5 Steps; Up to 45 kg (100 lb) Pet ImmunityLowest Sensitivity: 3 - 5 Steps; Up to 45 kg (100 lb) Pet ImmunityLowest Sensitivity: 3 - 5 Steps; Up to 45 kg (100 lb) Pet ImmunityONOFF12Low Sensitivity: 2 - 4 Steps; Up to 23 kg (50 lb) Pet ImmunityLow Sensitivity: 2 - 4 Steps; Up to 23 kg (50 lb) Pet ImmunityLow Sensitivity: 2 - 4 Steps; Up to 23 kg (50 lb) Pet ImmunityLow Sensitivity: 2 - 4 Steps; Up to 23 kg (50 lb) Pet ImmunityLow Sensitivity: 2 - 4 Steps; Up to 23 kg (50 lb) Pet ImmunityONOFF12Medium Sensitivity: 1 - 3 Steps; No Pet ImmunityMedium Sensitivity: 1 - 3 Steps; No Pet ImmunityMedium Sensitivity: 1 - 3 Steps; No Pet ImmunityMedium Sensitivity: 1 - 3 Steps; No Pet ImmunityMedium Sensitivity: 1 - 3 Steps; No Pet ImmunityONOFF12High Sensitivity: 1 - 2 Steps; No Pet ImmunityHigh Sensitivity: 1 - 2 Steps; No Pet ImmunityHigh Sensitivity: 1 - 2 Steps; No Pet ImmunityHigh Sensitivity: 1 - 2 Steps; No Pet ImmunityHigh Sensitivity: 1 - 2 Steps; No Pet ImmunityLook-Down Mask (install as shown when using Pet Immune Lens)Look-Down Mask (install as shown when using Pet Immune Lens)Look-Down Mask (install as shown when using Pet Immune Lens)Look-Down Mask (install as shown when using Pet Immune Lens)Look-Down Mask (install as shown when using Pet Immune Lens)aONOFF12345Pulse Count 2Low SensitivityLED Disabled Microwave Walk Test OFFAnti-Mask OFFPulse Count 1High SensitivityLED EnabledMicrowave Walk Test ONAnti-Mask ON<IT> If installed with a Smart V-PlexTM Panel:  The sensor will not transmit or indicate intrusion alarms when the panel is disarmed; in the armed state, the sensor will respond to all communications to or with the host panel.If installed with a Standard V-PlexTM Panel:   The sensor will respond to all communications with the host panel, armed or disarmed.ONOFF12345Pulse Count 2Low SensitivityLED Disabled Microwave Walk Test OFFAnti-Mask OFFPulse Count 1High SensitivityLED EnabledMicrowave Walk Test ONAnti-Mask ON<ES> If installed with a Smart V-PlexTM Panel:  The sensor will not transmit or indicate intrusion alarms when the panel is disarmed; in the armed state, the sensor will respond to all communications to or with the host panel.If installed with a Standard V-PlexTM Panel:   The sensor will respond to all communications with the host panel, armed or disarmed.ONOFF12345Pulse Count 2Low SensitivityLED Disabled Microwave Walk Test OFFAnti-Mask OFFPulse Count 1High SensitivityLED EnabledMicrowave Walk Test ONAnti-Mask ON<PT> If installed with a Smart V-PlexTM Panel:  The sensor will not transmit or indicate intrusion alarms when the panel is disarmed; in the armed state, the sensor will respond to all communications to or with the host panel.If installed with a Standard V-PlexTM Panel:   The sensor will respond to all communications with the host panel, armed or disarmed.Wide Angle Lens (installed)Wide Angle Lens (installed)Wide Angle Lens (installed)Wide Angle Lens (installed)Wide Angle Lens (installed)Pet Immune Lens (included)Pet Immune Lens (included)Pet Immune Lens (included)Pet Immune Lens (included)Pet Immune Lens (included)
DT7500SN V-PlexTM DUAL TEC Motion Sensor  - Installation Instructions                              - Page 2 -  !!!!b  FOR PET IMMUNITY •  Mount the center of the sensor at 2.3 m (7.5 feet) high. •  Set the sensor to the Lowest or Low sensitivity (see step 6a). •  Install Pet Immune lens (5-532-489-01 - see Lens Change Instructions on page 3). •  Install the look-down mask (see Step 6a). •  Install the sensor where pets cannot come within 1.8 m (6 ft) of the sensor by climbing on furniture or other objects. •  Aim the sensor away from stairways, furniture or other objects that can be climbed on by pets. •  TEST the installation site to determine the exact level of attainable animal immunity. Note: Pet immunity characteristics for this sensor have not been verified by Underwriter’s Laboratories, Inc.  """"  PROGRAM SENSOR SERIAL NUMBER ID Each sensor has a factory-assigned serial number which must be entered into the control panel during the zone programming procedure.  The unique serial number can be found on a bar code label on the sensor PCB.  The serial number can be entered into the control panel in one of the following methods:  A. Download it through software (Zone definition screen of Compass software).  This is recommended for large installations and installations where foot traffic cannot be controlled.   B. Enter the number through the keypad at the “INPUT S/N” prompt during manual zone programming.  Ensure no other polling devices are activated when manually entering the sensor serial number. C. Activate the sensor twice while at the “INPUT S/N” prompt during manual zone programming. To enter the sensor’s serial number for option B or C:  Refer to the control panel’s manual for programming instructions. For all V-PlexTM panels, enter INT FOLLOWER 04 for the Zone Type and “06” for SL (Serial Polling Device) at the “INPUT TYPE” prompt.  For Smart V-PlexTM panels press “1” (Yes) for SMART CONTACT. At the “INPUT S/N” prompt, either enter the serial number (and “1” for the loop number), or fault the sensor (wave your hand in front of the sensor or activate the tamper), then wait 3-6 seconds and fault the sensor again. The keypad will beep after each fault to confirm the signal. The sensor should now be enrolled. If a “1” does not appear under the “L” on the zone summary screen, press [*] and enter the loop number manually at the next screen. ####  NORMAL WALK TEST – 10 MINUTES Normal walk test mode activates after power up mode and remains active for 10 minutes.  For an additional 10 minutes of walk test time, remove and replace the front cover.  In walk test mode, the LED is always enabled, regardless of the LED DIP switch setting.  [Note: if the panel is not a Smart V-PlexTM panel, walk test can also be done by enabling the LED (DIP switch 3 = ON.]  Walk through the detection area and observe the LED.  If necessary, adjust the microwave range, pulse count or sensitivity setting. (For LED activation meaning, refer to the LED Indicator table below.) $$$$  MICROWAVE WALK TEST – 10 MINUTES 1.  Set the Microwave Walk Test DIP switch to ON, or toggle it ON and OFF. 2.  Set Range Adjustment potentiometer to 25% and replace the cover.   3.  Walk through the detection area and observe the LED.  4.  If necessary, adjust the potentiometer until desired detection range is obtained. (For LED activation meaning, refer to the LED Indicator table below.) Power UpTrouble or Anti-Mask Fast Blinking Red (LED Enabled or Disabled)Condition Indicator LEDSlow Blinking Red (will finish within 60 seconds)Indicator LEDsNormal Walk Test Red ON for 3 seconds if AlarmYellow ON for 2 seconds if Microwave event detectedGreen ON for 2 seconds if PIR event detectedMicrowave Walk Test Red ON if Microwave is set too highGreen ON if Microwave is set correctlyOFF if Microwave is set too low %%%%  ANTI-MASK When DIP switch 5 is set to ON, the sensor indicates a mask condition (see LED Indicator table above) when a variety of materials and reflective objects are placed in front of it.  Follow the mounting guidelines in step 1 to avoid false mask alarms. To clear a mask condition, visually inspect the sensor and remove any materials blocking the sensor’s view.  The sensor will clear an anti-mask condition when three valid alarms are detected.  After a mask condition is cleared, fully walk test the required detection area. TROUBLESHOOTING RED LED flashing rapidly during normal operation indicates a trouble or an anti-mask condition.  If the sensor is not masked (see step 10), either a microwave, PIR, or temperature compensation fault is present. Solution:  Momentarily power down the sensor.  If the trouble does not clear, replace the sensor.  (Please check the power, all wiring and that the sensor is not masked before replacing the sensor.)     !!!!b  FOR PET IMMUNITY          <FRENCH> • Mount the center of the sensor at 2.3 m (7.5 feet) high. • Set the sensor to the Lowest or Low sensitivity (see step 6a). • Install Pet Immune lens (5-532-489-01 - see Lens Change Instructions on page 3). • Install the look-down mask (see Step 6a). • Install the sensor where pets cannot come within 1.8 m (6 ft) of the sensor by climbing on furniture or other objects. • Aim the sensor away from stairways, furniture or other objects that can be climbed on by pets. • TEST the installation site to determine the exact level of attainable animal immunity. Note: Pet immunity characteristics for this sensor have not been verified by Underwriter’s Laboratories, Inc.  """"  PROGRAM SENSOR SERIAL NUMBER ID Each sensor has a factory-assigned serial number which must be entered into the control panel during the zone programming procedure.  The unique serial number can be found on a bar code label on the sensor PCB.  The serial number can be entered into the control panel in one of the following methods:  A. Download it through software (Zone definition screen of Compass software).  This is recommended for large installations and installations where foot traffic cannot be controlled.   B. Enter the number through the keypad at the “INPUT S/N” prompt during manual zone programming.  Ensure no other polling devices are activated when manually entering the sensor serial number. C. Activate the sensor twice while at the “INPUT S/N” prompt during manual zone programming. To enter the sensor’s serial number for option B or C:  Refer to the control panel’s manual for programming instructions. For all V-PlexTM panels, enter INT FOLLOWER 04 for the Zone Type and “06” for SL (Serial Polling Device) at the “INPUT TYPE” prompt.  For Smart V-PlexTM panels press “1” (Yes) for SMART CONTACT. At the “INPUT S/N” prompt, either enter the serial number (and “1” for the loop number), or fault the sensor (wave your hand in front of the sensor or activate the tamper), then wait 3-6 seconds and fault the sensor again. The keypad will beep after each fault to confirm the signal. The sensor should now be enrolled. If a “1” does not appear under the “L” on the zone summary screen, press [*] and enter the loop number manually at the next screen. ####  NORMAL WALK TEST – 10 MINUTES Normal walk test mode activates after power up mode and remains active for 10 minutes.  For an additional 10 minutes of walk test time, remove and replace the front cover.  In walk test mode, the LED is always enabled, regardless of the LED DIP switch setting.  [Note: if the panel is not a Smart V-PlexTM panel, walk test can also be done by enabling the LED (DIP switch 3 = ON.]  Walk through the detection area and observe the LED.  If necessary, adjust the microwave range, pulse count or sensitivity setting. (For LED activation meaning, refer to the LED Indicator table below.) $$$$  MICROWAVE WALK TEST – 10 MINUTES 1.  Set the Microwave Walk Test DIP switch to ON, or toggle it ON and OFF. 2.  Set Range Adjustment potentiometer to 25% and replace the cover.   3.  Walk through the detection area and observe the LED.  4.  If necessary, adjust the potentiometer until desired detection range is obtained. (For LED activation meaning, refer to the LED Indicator table below.) Power UpTrouble or Anti-Mask Fast Blinking Red (LED Enabled or Disabled)Condition Indicator LEDSlow Blinking Red (will finish within 60 seconds)Indicator LEDsNormal Walk Test Red ON for 3 seconds if AlarmYellow ON for 2 seconds if Microwave event detectedGreen ON for 2 seconds if PIR event detectedMicrowave Walk Test Red ON if Microwave is set too highGreen ON if Microwave is set correctlyOFF if Microwave is set too low %%%%  ANTI-MASK When DIP switch 5 is set to ON, the sensor indicates a mask condition (see LED Indicator table above) when a variety of materials and reflective objects are placed in front of it.  Follow the mounting guidelines in step 1 to avoid false mask alarms. To clear a mask condition, visually inspect the sensor and remove any materials blocking the sensor’s view.  The sensor will clear an anti-mask condition when three valid alarms are detected.  After a mask condition is cleared, fully walk test the required detection area. TROUBLESHOOTING RED LED flashing rapidly during normal operation indicates a trouble or an anti-mask condition.  If the sensor is not masked (see step 10), either a microwave, PIR, or temperature compensation fault is present. Solution:  Momentarily power down the sensor.  If the trouble does not clear, replace the sensor.  (Please check the power, all wiring and that the sensor is not masked before replacing the sensor.)     !!!!b  FOR PET IMMUNITY          <ITALIAN> • Mount the center of the sensor at 2.3 m (7.5 feet) high. • Set the sensor to the Lowest or Low sensitivity (see step 6a). • Install Pet Immune lens (5-532-489-01 - see Lens Change Instructions on page 3). • Install the look-down mask (see Step 6a). • Install the sensor where pets cannot come within 1.8 m (6 ft) of the sensor by climbing on furniture or other objects. • Aim the sensor away from stairways, furniture or other objects that can be climbed on by pets. • TEST the installation site to determine the exact level of attainable animal immunity. Note: Pet immunity characteristics for this sensor have not been verified by Underwriter’s Laboratories, Inc.  """"  PROGRAM SENSOR SERIAL NUMBER ID Each sensor has a factory-assigned serial number which must be entered into the control panel during the zone programming procedure.  The unique serial number can be found on a bar code label on the sensor PCB.  The serial number can be entered into the control panel in one of the following methods:  A. Download it through software (Zone definition screen of Compass software).  This is recommended for large installations and installations where foot traffic cannot be controlled.   B. Enter the number through the keypad at the “INPUT S/N” prompt during manual zone programming.  Ensure no other polling devices are activated when manually entering the sensor serial number. C. Activate the sensor twice while at the “INPUT S/N” prompt during manual zone programming. To enter the sensor’s serial number for option B or C:  Refer to the control panel’s manual for programming instructions. For all V-PlexTM panels, enter INT FOLLOWER 04 for the Zone Type and “06” for SL (Serial Polling Device) at the “INPUT TYPE” prompt.  For Smart V-PlexTM panels press “1” (Yes) for SMART CONTACT. At the “INPUT S/N” prompt, either enter the serial number (and “1” for the loop number), or fault the sensor (wave your hand in front of the sensor or activate the tamper), then wait 3-6 seconds and fault the sensor again. The keypad will beep after each fault to confirm the signal. The sensor should now be enrolled. If a “1” does not appear under the “L” on the zone summary screen, press [*] and enter the loop number manually at the next screen. ####  NORMAL WALK TEST – 10 MINUTES Normal walk test mode activates after power up mode and remains active for 10 minutes.  For an additional 10 minutes of walk test time, remove and replace the front cover.  In walk test mode, the LED is always enabled, regardless of the LED DIP switch setting.  [Note: if the panel is not a Smart V-PlexTM panel, walk test can also be done by enabling the LED (DIP switch 3 = ON.]  Walk through the detection area and observe the LED.  If necessary, adjust the microwave range, pulse count or sensitivity setting. (For LED activation meaning, refer to the LED Indicator table below.) $$$$  MICROWAVE WALK TEST – 10 MINUTES 1.  Set the Microwave Walk Test DIP switch to ON, or toggle it ON and OFF. 2.  Set Range Adjustment potentiometer to 25% and replace the cover.   3.  Walk through the detection area and observe the LED.  4.  If necessary, adjust the potentiometer until desired detection range is obtained. (For LED activation meaning, refer to the LED Indicator table below.) Power UpTrouble or Anti-Mask Fast Blinking Red (LED Enabled or Disabled)Condition Indicator LEDSlow Blinking Red (will finish within 60 seconds)Indicator LEDsNormal Walk Test Red ON for 3 seconds if AlarmYellow ON for 2 seconds if Microwave event detectedGreen ON for 2 seconds if PIR event detectedMicrowave Walk Test Red ON if Microwave is set too highGreen ON if Microwave is set correctlyOFF if Microwave is set too low %%%%  ANTI-MASK When DIP switch 5 is set to ON, the sensor indicates a mask condition (see LED Indicator table above) when a variety of materials and reflective objects are placed in front of it.  Follow the mounting guidelines in step 1 to avoid false mask alarms. To clear a mask condition, visually inspect the sensor and remove any materials blocking the sensor’s view.  The sensor will clear an anti-mask condition when three valid alarms are detected.  After a mask condition is cleared, fully walk test the required detection area. TROUBLESHOOTING RED LED flashing rapidly during normal operation indicates a trouble or an anti-mask condition.  If the sensor is not masked (see step 10), either a microwave, PIR, or temperature compensation fault is present. Solution:  Momentarily power down the sensor.  If the trouble does not clear, replace the sensor.  (Please check the power, all wiring and that the sensor is not masked before replacing the sensor.)      DETECTION PATTERNS / COUVERTURE DE DETECTION / DIAGRAMMA DI COPERTURA /  PATRON DE DETECCIÓN / DETECTION PATTERNS  50’ / 15m Wide Angle Lens (P/N 5-532-439-01 – Installed) Top View / VUE DE DESSUS / Vista in pianta / VISTA DESDE ARRIBA / Top View   Side View / VUE DE COTE / Vista in sezione /  VISTA LATERAL / Side View   LENS MASKING / LENS MASKING / LENS MASKING / LENS MASKING / LENS MASKING  5-532-489-01TOP25 / 35FT
DT7500SN V-PlexTM DUAL TEC Motion Sensor  - Installation Instructions                              - Page 3 -  !!!!b  FOR PET IMMUNITY          <SPANISH> • Mount the center of the sensor at 2.3 m (7.5 feet) high. • Set the sensor to the Lowest or Low sensitivity (see step 6a). • Install Pet Immune lens (5-532-489-01 - see Lens Change Instructions on page 3). • Install the look-down mask (see Step 6a). • Install the sensor where pets cannot come within 1.8 m (6 ft) of the sensor by climbing on furniture or other objects. • Aim the sensor away from stairways, furniture or other objects that can be climbed on by pets. • TEST the installation site to determine the exact level of attainable animal immunity. Note: Pet immunity characteristics for this sensor have not been verified by Underwriter’s Laboratories, Inc.  """"  PROGRAM SENSOR SERIAL NUMBER ID Each sensor has a factory-assigned serial number which must be entered into the control panel during the zone programming procedure.  The unique serial number can be found on a bar code label on the sensor PCB.  The serial number can be entered into the control panel in one of the following methods:  A. Download it through software (Zone definition screen of Compass software).  This is recommended for large installations and installations where foot traffic cannot be controlled.   B. Enter the number through the keypad at the “INPUT S/N” prompt during manual zone programming.  Ensure no other polling devices are activated when manually entering the sensor serial number. C. Activate the sensor twice while at the “INPUT S/N” prompt during manual zone programming. To enter the sensor’s serial number for option B or C:  Refer to the control panel’s manual for programming instructions. For all V-PlexTM panels, enter INT FOLLOWER 04 for the Zone Type and “06” for SL (Serial Polling Device) at the “INPUT TYPE” prompt.  For Smart V-PlexTM panels press “1” (Yes) for SMART CONTACT. At the “INPUT S/N” prompt, either enter the serial number (and “1” for the loop number), or fault the sensor (wave your hand in front of the sensor or activate the tamper), then wait 3-6 seconds and fault the sensor again. The keypad will beep after each fault to confirm the signal. The sensor should now be enrolled. If a “1” does not appear under the “L” on the zone summary screen, press [*] and enter the loop number manually at the next screen. ####  NORMAL WALK TEST – 10 MINUTES Normal walk test mode activates after power up mode and remains active for 10 minutes.  For an additional 10 minutes of walk test time, remove and replace the front cover.  In walk test mode, the LED is always enabled, regardless of the LED DIP switch setting.  [Note: if the panel is not a Smart V-PlexTM panel, walk test can also be done by enabling the LED (DIP switch 3 = ON.]  Walk through the detection area and observe the LED.  If necessary, adjust the microwave range, pulse count or sensitivity setting. (For LED activation meaning, refer to the LED Indicator table below.) $$$$  MICROWAVE WALK TEST – 10 MINUTES 1.  Set the Microwave Walk Test DIP switch to ON, or toggle it ON and OFF. 2.  Set Range Adjustment potentiometer to 25% and replace the cover.   3.  Walk through the detection area and observe the LED.  4.  If necessary, adjust the potentiometer until desired detection range is obtained. (For LED activation meaning, refer to the LED Indicator table below.) Power UpTrouble or Anti-Mask Fast Blinking Red (LED Enabled or Disabled)Condition Indicator LEDSlow Blinking Red (will finish within 60 seconds)Indicator LEDsNormal Walk Test Red ON for 3 seconds if AlarmYellow ON for 2 seconds if Microwave event detectedGreen ON for 2 seconds if PIR event detectedMicrowave Walk Test Red ON if Microwave is set too highGreen ON if Microwave is set correctlyOFF if Microwave is set too low %%%%  ANTI-MASK When DIP switch 5 is set to ON, the sensor indicates a mask condition (see LED Indicator table above) when a variety of materials and reflective objects are placed in front of it.  Follow the mounting guidelines in step 1 to avoid false mask alarms. To clear a mask condition, visually inspect the sensor and remove any materials blocking the sensor’s view.  The sensor will clear an anti-mask condition when three valid alarms are detected.  After a mask condition is cleared, fully walk test the required detection area. TROUBLESHOOTING RED LED flashing rapidly during normal operation indicates a trouble or an anti-mask condition.  If the sensor is not masked (see step 10), either a microwave, PIR, or temperature compensation fault is present. Solution:  Momentarily power down the sensor.  If the trouble does not clear, replace the sensor.  (Please check the power, all wiring and that the sensor is not masked before replacing the sensor.)     !!!!b  FOR PET IMMUNITY          <PORTUGUESE> • Mount the center of the sensor at 2.3 m (7.5 feet) high. • Set the sensor to the Lowest or Low sensitivity (see step 6a). • Install Pet Immune lens (5-532-489-01 - see Lens Change Instructions on page 3). • Install the look-down mask (see Step 6a). • Install the sensor where pets cannot come within 1.8 m (6 ft) of the sensor by climbing on furniture or other objects. • Aim the sensor away from stairways, furniture or other objects that can be climbed on by pets. • TEST the installation site to determine the exact level of attainable animal immunity. Note: Pet immunity characteristics for this sensor have not been verified by Underwriter’s Laboratories, Inc.  """"  PROGRAM SENSOR SERIAL NUMBER ID Each sensor has a factory-assigned serial number which must be entered into the control panel during the zone programming procedure.  The unique serial number can be found on a bar code label on the sensor PCB.  The serial number can be entered into the control panel in one of the following methods:  A. Download it through software (Zone definition screen of Compass software).  This is recommended for large installations and installations where foot traffic cannot be controlled.   B. Enter the number through the keypad at the “INPUT S/N” prompt during manual zone programming.  Ensure no other polling devices are activated when manually entering the sensor serial number. C. Activate the sensor twice while at the “INPUT S/N” prompt during manual zone programming. To enter the sensor’s serial number for option B or C:  Refer to the control panel’s manual for programming instructions. For all V-PlexTM panels, enter INT FOLLOWER 04 for the Zone Type and “06” for SL (Serial Polling Device) at the “INPUT TYPE” prompt.  For Smart V-PlexTM panels press “1” (Yes) for SMART CONTACT. At the “INPUT S/N” prompt, either enter the serial number (and “1” for the loop number), or fault the sensor (wave your hand in front of the sensor or activate the tamper), then wait 3-6 seconds and fault the sensor again. The keypad will beep after each fault to confirm the signal. The sensor should now be enrolled. If a “1” does not appear under the “L” on the zone summary screen, press [*] and enter the loop number manually at the next screen. ####  NORMAL WALK TEST – 10 MINUTES Normal walk test mode activates after power up mode and remains active for 10 minutes.  For an additional 10 minutes of walk test time, remove and replace the front cover.  In walk test mode, the LED is always enabled, regardless of the LED DIP switch setting.  [Note: if the panel is not a Smart V-PlexTM panel, walk test can also be done by enabling the LED (DIP switch 3 = ON.]  Walk through the detection area and observe the LED.  If necessary, adjust the microwave range, pulse count or sensitivity setting. (For LED activation meaning, refer to the LED Indicator table below.) $$$$  MICROWAVE WALK TEST – 10 MINUTES 1.  Set the Microwave Walk Test DIP switch to ON, or toggle it ON and OFF. 2.  Set Range Adjustment potentiometer to 25% and replace the cover.   3.  Walk through the detection area and observe the LED.  4.  If necessary, adjust the potentiometer until desired detection range is obtained. (For LED activation meaning, refer to the LED Indicator table below.) Power UpTrouble or Anti-Mask Fast Blinking Red (LED Enabled or Disabled)Condition Indicator LEDSlow Blinking Red (will finish within 60 seconds)Indicator LEDsNormal Walk Test Red ON for 3 seconds if AlarmYellow ON for 2 seconds if Microwave event detectedGreen ON for 2 seconds if PIR event detectedMicrowave Walk Test Red ON if Microwave is set too highGreen ON if Microwave is set correctlyOFF if Microwave is set too low %%%%  ANTI-MASK When DIP switch 5 is set to ON, the sensor indicates a mask condition (see LED Indicator table above) when a variety of materials and reflective objects are placed in front of it.  Follow the mounting guidelines in step 1 to avoid false mask alarms. To clear a mask condition, visually inspect the sensor and remove any materials blocking the sensor’s view.  The sensor will clear an anti-mask condition when three valid alarms are detected.  After a mask condition is cleared, fully walk test the required detection area. TROUBLESHOOTING RED LED flashing rapidly during normal operation indicates a trouble or an anti-mask condition.  If the sensor is not masked (see step 10), either a microwave, PIR, or temperature compensation fault is present. Solution:  Momentarily power down the sensor.  If the trouble does not clear, replace the sensor.  (Please check the power, all wiring and that the sensor is not masked before replacing the sensor.)     ACCESSORIES / ACCESSOIRES / ACCESSORI / ACCESORIOS / ACCESSORIES SMB-10 (P/N 0-000-110-01) Swivel Mount Bracket Rotule de montage Snodo da parete Rotula de montaje a pared Swivel Mount Bracket   SMB-10C (P/N 0-000-111-01) Swivel Mount Ceiling Bracket  Rotule de plafond Snodo da soffitto Rotula de montaje a techno Swivel Mount Ceiling Bracket   SMB-10T (P/N 0-000-155-01) EN 50131-1 & EN50131-2-4  NCompliant Swivel Mount Bracket w/Tamper Rotule de montage avec autoprotection Snodo da parete con tamper Rotula de montaje a pared con tamper Swivel Mount Bracket w/Tamper  DT7000-LRLK 15 m x 3 m (50’ x 10’) Long Range Lens Kit Kit lentille longue portée Kit lenti a lunga portata Kit de lentes de largo alcance Long Range Lens Kit  DT7000-HSLK 11 m x 12 m (35’ x 40’) High Security Lens Kit High Security Lens Kit High Security Lens Kit High Security Lens Kit High Security Lens Kit  DT7000-PALK 11 m x 12 m (35’ x 40’) Pet Alley Lens Kit Pet Alley Lens Kit Pet Alley Lens Kit Pet Alley Lens Kit Pet Alley Lens Kit   LENS CHANGE INSTRUCTIONS / LENS CHANGE INSTRUCTIONS / LENS CHANGE INSTRUCTIONS / LENS CHANGE INSTRUCTIONS / LENS CHANGE INSTRUCTIONS    DETECTION PATTERNS / COUVERTURE DE DETECTION / DIAGRAMMA DI COPERTURA /  PATRON DE DETECCIÓN / DETECTION PATTERNS  35’ / 11m Pet Immune Lens (P/N 5-532-489-01 – Included) Top View / VUE DE DESSUS / Vista in pianta / VISTA DESDE ARRIBA / Top View   LENS MASKING / LENS MASKING / LENS MASKING / LENS MASKING / LENS MASKING  5-532-489-01TOP25 / 35FT Side View / VUE DE COTE / Vista in sezione /  VISTA LATERAL / Side View   Install Look Down Mask to block look down zones. Install Look Down Mask to block look down zones. Install Look Down Mask to block look down zones. Install Look Down Mask to block look down zones. Install Look Down Mask to block look down zones.
DT7500SN V-PlexTM DUAL TEC Motion Sensor  - Installation Instructions                              - Page 4 - SPECIFICATIONS CARACTERISTIQUES  <FRENCH> SPECIFICHE TECNICHE  <ITALIAN> ESPICIFICACIONES  <SPANISH> SPECIFICATIONS  <PORTUGUESE> Range:  50’ x 60’ (15 m x 18 m) [installed] 35’ x 40’ (11 m x 12 m) [included]  Portée:  15 m x 18 m [installed] (11 m x 12 m) [included]  Portata:  50’ x 60’ (15 m x 18 m) [installed];  35’ x 40’ (11 m x 12 m) [included] Covertura:  15 m x 18 m [installed] (11 m x 12 m) [included]  Range:  50’ x 60’ (15 m x 18 m) [installed] 35’ x 40’ (11 m x 12 m) [included] Tamper Switch:  (NC) 10 mA,  24 VDC  Autoprotection:  (NC) 10 mA,  24 VDC  Interruttori antimanomissione:  (NC) 10 mA, 24 VDC  Salida de tamper:  (NC) 10 mA,  24 VDC  Tamper Switch:  (NC) 10 mA,  24 VDC Power Requirements:  9 - 13 VDC @ polling loop terminals with reverse polarity detection; nominal 11.0 VDC polling loop  Alimentation:  9 - 13 VDC @ polling loop terminals with reverse polarity detection; nominal 11.0 VDC polling loop Alimentazione:  9 - 13 VDC @ polling loop terminals with reverse polarity detection; nominal 11.0 VDC polling loop Requerimientos de alimentación:  9 - 13 VDC @ polling loop terminals with reverse polarity detection; nominal 11.0 VDC polling loop Power Requirements:  9 - 13 VDC @ polling loop terminals with reverse polarity detection; nominal 11.0 VDC polling loop  Current:  3.0 mA nominal (with LED disabled); 6.0 mA nominal (with LED enabled); 6.5 mA max. (during warm up) Current:  2.5 mA nominal (with LED disabled; 5.0 mA nominal (with LED enabled Current:  2.5 mA nominal (with LED disabled; 5.0 mA nominal (with LED enabled Current:  2.5 mA nominal (with LED disabled; 5.0 mA nominal (with LED enabled Current:  3.0 mA nominal (with LED disabled); 6.0 mA nominal (with LED enabled); 6.5 mA max. (during warm up) Frequency:  24.125 GHz (K-band)  Hyperfréquence:  24.125 GHz  (K-band)  Frequenza microonda:  24.125 GHz (K-band)  Frecuencias Microondas:  24.125 GHz (K-band)  Frequency:  24.125 GHz (K-band) PIR White Light Immunity:  6,500 Lux typical  Immunity à la lumière blanche:  6,500 Lux Typique  Immunita PIR alla luce bianca:  6,500 Lux tipica  Immunidad contra luces blancas:  6,500 Lux typical  PIR White Light Immunity:  6,500 Lux typical Fluorescent Light Filter:  50 Hz or 60 Hz, auto-detection  Filtre lumière Fluorescente:  50 Hz or 60 Hz, sélectionnable  Filtro luce Fluorescente:  50Hz o 60Hz, selezionabile  Filtro Luz Fluorescente:  50 Hz or 60 Hz, selectable  Fluorescent Light Filter:  50 Hz or 60 Hz, auto-detection Operating Temperature:  -4° to 131° F  (-20° to 55° C), 5% - 95% relative humidity (non-condensing) Température de fonctionnement:   -20° à 55° C; Humidité relative:  5% à 95% sans condensation Temperatura di esercizio: da -20° a 55° C;  5% - 95% umidità relative (non-condensansante) Temperatura de funcionamiento: -4° to 131° F (-20° to 55° C); Humedad relativa:  5% to 95% sin condensación Operating Temperature:  -4° to 131° F  (-20° to 55° C), 5% - 95% relative humidity (non-condensing) Self-Tests:   Microwave supervision; End-to-End PIR self-test; Temperature Compensation Auto-Tests:   Supervision hyperfréquences; IRP;  Compensation en température Auto-Tests:   Supervisione Microonda; Auto-test PIR; Comp. Temperatura  Auto-Test:   Supervisión Microondas; Test PIR; Comp. Temp.  Self-Tests:   Microwave supervision; End-to-End PIR self-test; Temperature Compensation Temperature Compensation:  Advanced Dual Slope  Compensation en température:  A double pente  Compensazione Temperatura:  Avanzata a doppio gradiente  Compensación de temperatura:  Doble pendiente avanzada  Temperature Compensation:  Advanced Dual Slope PIR Fields of View:  Wide Angle Lens (P/N 5-532-439-00) 44 long range zones 12 intermediate zones 6 lower zones 4 look-down zones Pet Immune Lens (P/N 5-532-489-00) 44 long range zones 36 intermediate zones 18 lower zones 4 look-down zones Champ de détection IRP:  Grand Angle Lens (P/N 5-532-439-00)  44 faisceaux longs 12 intermediaires 6 courts 4 verticaux Pet Immune Lens (P/N 5-532-489-00)  44 faisceaux longs 36 intermediaires 18 courts 4 verticaux Zone PIR:  Wide Angle Lens (P/N 5-532-439-00) 44 lunga portata 12 intermedie  6 inferiori 4 antistrisciamento Pet Immune Lens (P/N 5-532-489-00) 44 lang bereik zones 36 midden 18 laag 4 kruipzones Zonas de detección:  Wide Angle Lens (P/N 5-532-439-00) 44 zonas de largo alcance 12 zonas intermedias 6 zonas de corto alcance 4 zonas de angulo cero  Pet Immune Lens (P/N 5-532-489-00) 44 lang bereik zones 36 midden 18 laag 4 kruipzones PIR Fields of View:  Wide Angle Lens (P/N 5-532-439-00) 44 long range zones 12 intermediate zones 6 lower zones 4 look-down zones Pet Immune Lens (P/N 5-532-489-00) 44 long range zones 36 intermediate zones 18 lower zones 4 look-down zones Dimensions:  4.93” x 2.93” x 1.68” (12.5cm x 7.5cm x 4.3cm)  Dimensions:   12.5cm x 7.5cm x 4.3cm  Dimensioni:  12.5cm x 7.5cm x 4.3cm  Dimensiones:  12.5cm x 7.5cm x 4.3cm  Dimensions:  4.93” x 2.93” x 1.68” (12.5cm x 7.5cm x 4.3cm) Weight:  149.0 g (5.26 oz) Packaged:  205.0 g (7.23 oz)  Masse:  149.0 g Emballé: 205.0 g  Peso:  149.0 g Impachettato: 205.0 g  Peso:  149.0 g Embalaje del producto: 205.0 g  Weight:  149.0 g (5.26 oz) Packaged:  205.0 g (7.23 oz)    APPROVAL LISTINGS  / AGREMENT / OMOLOGAZIONI / HOMOLOGACIONES / APPROVAL LISTINGS  •  FCC part 15, Class B verified •  IC, RSS-210, Class B verified • CE   ,      C-Tick,     cULus Listed,      INCERT,      IMQ •  EN 50131-1 and EN 50131-2-4 Security Grade 2, Environment Class II. •  EN 50131-1 en EN 50131-2-4 Security Grade 2; Environmental Class II.   •  EN 50131-1 et EN 50131-2-4, grade 2, classe enironnementale II. •  EN 50131-1 e EN 50131-2-4 Grado di Sicurezza 2; Classe Ambientale II. •  EN50131-1 y EN 50131-2-4  Grado de Seguridad 2, Clase ambiental II.  •   COMPLIANCE NOTES •  For EN 50131-2-4 compliant installations, mount sensor at 2.3m (7.5ft), set pulse count to 1, set sensitivity to High, and install cover screw. •  Suitable for connection to an EN60950 Class II Limited Power Source in European installations. UL COMPLIANCE NOTES • Product must be tested once each year. •  Wiring the terminals incorrectly may damage this unit, and/or the equipment wired to it.   NOTES DE CONFORMITÉ • En référentiel TS 50131-2-4, installation à  2.30 m, choisir la sensibilité haute, et mettre en place la vis de capot (fournie).. •  Compatible pour un raccordement à une alimentation régulée EN 60950 Classe II.  NOTE DI CONFORMITA’  •  Per installazioni TS 50131-2-4, montare il sensore a 2.3 m, impostare il sensore in alta sicurezza e bloccare il coperchio con una vite (Inclusa). •  Per connessioni con alimentatori compatibili EN 60950 Classe II in contesto EU.  NOTAS DE CONFORMIDAD •  Para instalaciones que cumplen TS50131-2-4: monte el detector a una altura de 2.3m (7’6”), seleccione alta sensibilidad y coloque el tornillo de la tapa. •  Adecuado para conectarlo con una fuente de alimentación EN60950 Clase II en instalaciones Europeas.  COMPLIANCE NOTES  <PORTUGUESE> •  For EN 50131-2-4 compliant installations, mount sensor at 2.3m (7.5ft), set pulse count to 1, set sensitivity to High, and install cover screw. •  Suitable for connection to an EN60950 Class II Limited Power Source in European installations.               To obtain applicable EU compliance Declaration of Conformities for this product, please refer to our Website, http://www.security.honeywell.com/hsce/international/index.html.   For any additional information regarding the compliance of this product to any EU specific requirements, please contact: Les déclarations de conformité aux normes Européennes de ce produit sont disponibles sur notre site Internet à l’adresse http://www.security.honeywell.com/hsce/international/index.html. Toutes informations complémentaires relatives à la conformité de ce produit à des normes Européennes particulières peuvent être obtenues auprès de notre département «Assurance Qualité»: Per ottenere una copia della Dichiarazione di conformità CE applicabile di questo prodotto, si prega di fare riferimento al nostro sito Web, http://www.security.honeywell.com/hsce/international/index.html. Per ogni ulteriore informazione relativa alla conformità di questo prodotto alle normative specifiche CE, siete pregati di contattare: Para obtener la conformidad con la normativa EU y declaración de conformidad de este producto, por favor visite nuestra Website, http://www.security.honeywell.com/hsce/international/index.html.  Para cualquier información adicional sobre este producto u otras especificaciones EU, por favor contacte con: <PT>  To obtain applicable compliance Declaration of Conformities for this product, please refer to our Website, http://www.security.honeywell.com/hsce/international/index.html.   For any additional information regarding the compliance of this product to any EU specific requirements, please contact: Quality Assurance Department, Honeywell Security & Custom Electronics, Newhouse Industrial Estate Motherwell, Lanarkshire ML1 5SB, Scotland, United Kingdom. Tel:  +44(0)1698 738200 Email:  UK64Sales@Honeywell.com FCC NOTICE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules.  These limits are designed to provide reasonable protection against harmful interference in a residential installation.  This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications.  However, there is no guarantee that interference will not occur in a particular installation.  If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:   −  Reorient or relocate the receiving antenna.   −  Increase the separation between the equipment and receiver.   −  Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.   −  Consult the dealer or an experienced radio/television technician for help. The user is cautioned that changes or modifications not expressly approved by Honeywell could void the user’s authority to operate this equipment. IC NOTICE:  This Class B digital device complies with RSS-210 of the IC Rules.  Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. Cet appareil numérique de la Classe B est conforme à la norme CNR-210 des règles d’IC.  L'utilisation de ce dispositif est autorisée seulement aux deux conditions suivantes : (1) il ne doit pas produire de brouillage, et (2) l'utilisateur du dispositif doit être prêt à accepter tout brouillage radioélectrique reçu, même si ce brouillage est susceptible de compromettre le fonctionnement du dispositif.          2007 Honeywell International Inc.  Honeywell, IntelliSense and DUAL TEC are registered trademarks of Honeywell International Inc.   All other trademarks are the properties of their respective owners.  All rights reserved.    Made in China.   For the latest U.S. warranty information, please go to:  www.honeywell.com/security/hsc/resources/wa  or Please contact your local authorised Honeywell representative for product warranty information.  Contacter un revendeur Honeywell autorisé pour obtenir des informations sur la garantie de ce produit.  Contatti il suo rappresentante Honeywell per ulteriori informazioni su prodotti e garanzia.  Por favor contacte con su distribuidor Honeywell Security para información sobre la garantía del producto. <PT>  Please contact your local authorised Honeywell representative for product warranty information.      P/N P800-01643  Rev A

Navigation menu