Ademco 20152824 E7 Thermostat User Manual 31 00093 03 BACnet Fixed Function Thermostat

Honeywell International Inc E7 Thermostat 31 00093 03 BACnet Fixed Function Thermostat

Contents

  • 1. User manual.pdf
  • 2. User manual_e7 Install Instructions and Regulatory information_Rev 1.pdf.pdf

User manual_e7 Install Instructions and Regulatory information_Rev 1.pdf.pdf

REQUIRED TOOLS AND SOFTWARE36-00012-01INNCOM e7 Installation RequirementsREAD ME FIRST Required Installation Hardware:• Four #6/32, 1" Philip's Pan Head Screws• e7 Smart Wall Mounting Plate• e7 Power and HVAC signal Harness• Phillips Screw driver• Wire cutters / strippers• Orange wire nuts Optional Installation Hardware:• e7 Spacer Ring• 3 wires for low voltage / S5bus in-room communications (typically CAT-5 or CAT-3 wiring)• Door, window, balcony switch and harness (wired to H2); see property specific documentation for remote door, window and balcony switch requirements• Remote thermistor (04-1096.FL, wired to H2)Required Installation SoftwareDO NOT THROW THIS UNIT AWAY: One PC-503 USB Commissioning Tool and USB cable per property / project is shipped to the site.This tool is used in conjunction with Honeywell's engINN commissioning software when advanced commissioning of the e7 is required by a trained and certified INNCOM technician. DO NOT THROW THIS UNIT AWAY. Contact Honeywell technical support for more information. PC-503 USB Commissioning Tool and Cable
INSTALLATION INSTRUCTIONShttps://pages1.honeywell.com/e7_Install_Instructions.htmlINNCOM e7 Thermostat Installation Instructions  FOR ALL UNITS IN CARTON.  DO NOT THROW AWAY!CAUTIONDisconnect the power supply before beginning installation to prevent electrical shock or equipment damage. All wiring must comply with local codes and ordinances.• Read instructions carefully. Failure to follow them could damage the product or create a hazard.• Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.• Installer must be a trained, experienced service technician.• After installation is complete, check product operation as indicated in instructions.• For variations of these systems, refer to the installation instructions of the controlled equipment.INSTALLATIONLocationSelect a location about 1.5m (5ft.) above the floor with good air circulation at average temperature. Do not mount thermostat where it may be affected by:• Drafts or dead spots behind doors or in corners.• Hot or cold air from ducts.• Radiant heat from sun or appliances.• Concealed pipes or chimneys.• Unheated (un-cooled) areas behind the thermostat.• If RF equipped, do not install near other RF sources/transmitters.• When the thermostat is equipped with PIR, consider view angle, range characteristics, and mounting position for proper coverage.MountingThe INNCOM e7 thermostat is typically mount on a standard double-gang (4 x 4) junction box. The installation kit provides a Smart Wall Mounting Plate and an optional Spacer Ring. The optional Spacer Ring is only required when a standard double-gang (4 x 4) junction box is not available, or when more space is required for wiring.  If mounted on a single-gang box, the right side (keypad side) of the e7 overlaps the wall area to the right. A low-voltage mounting plate, mud ring, or low-voltage caddy may be used for mounting 24 volt applications.To mount the e7, complete the following steps: 1. Position the optional spacer ring (if used) and Smart Wall Mounting Plate as shown in Fig. 1. 2. Ensure the optional spacer ring (if used) and Smart Mounting Plate are oriented with the raised arrow point-ing UP. Attach them to the junction box using the mount-ing screws provided.3. Use wire nuts to connect the Power and HVAC wiring harness to the power and valve/fan control signal wires within the electrical box. See the pre-defined commission-ing document for application-specific wire connections. 4. To connect the unit to the input power and the relays to the loads, plug the pre-wired power and HVAC signal har-ness connector into the female receptacle at the back of the e7 (H1). When using mixed voltage, voltage separation must be maintained. Line voltage must reside in the left side of the gang box. Low voltage must reside in the right side of the gang box.5. Hook the tabs at the top rear of the e7 housing into the matching depressions at the top of the Smart Mounting Plate and rotate the bottom of the housing toward the wall until it snaps into place.6. Secure the housing to the Smart Mounting Plate with the two small captive screws at the bottom of the housing.7. Apply power to the e7 by closing the applicable supply breaker. Verify that the e7 powers up. Values should begin appearing on the LCD display.Fig. 1. e7 Exploded View Assembly ReferenceOptional Spacer Ring4 Junction Box Smart Mounting RingPower/HVAC signal harness to thermostat
INNCOM E7 THERMOSTAT INSTALLATION INSTRUCTIONS36-00012—01 2WIRINGWiring DiagramsNOTE: If the HVAC configuration for your application is not shown here, refer to the document: e7 Wiring Configurations found online at:  https://pages1.honeywell.com/e7_Install_Instructions.htmlGeneric FCU:24 VAC  Generic FCU: 110-220 VAC Table 1. H1 Red Connector: 24 VAC Power/HVAC Sig-nalsPin Color Typical Function1 Green Ground2 Red 24 VAC3 Black Common4Blue High Fan5 Brown Medium Fan or Second Stage Heat6 Yellow Cold Water Valve (FCU) or Compressor Signal (Heat Pump)7 White Hot Water Valve (FCU) or Reversing Valve (Heat Pump)8Grey Valve Power9 Violet Fan Power10 Orange Low FanTable 2. H1 White Connector: 110-220 VAC Power/HVAC SignalsPin Color Typical Function1 Green Ground2 Black Line3 White Neutral4 Yellow High Fan5 Orange Medium Fan or Second Stage Heat6 Red Cold Water Valve (FCU) or Compressor Signal (Heat Pump)7 Brown Hot Water Valve (FCU) or Reversing Valve (Heat Pump)8Grey Valve Power9 Violet Fan Power10 Blue Low FanH1FCC ID: HS9-201528Niantic, CT 06357Country of Origin: MexicoPatent PendingAI110AODIN3DIN2DIN1S5bus12VDCGNDIC: 573R-201528BLEH4RS485H1H3H2Honeywell GmbHBoeblinger Str. 1771101 SchoenaichGermanyE361577Sensing ControlH2 - Low Voltage Signals H1 - Power/HVAC SignalsTable 3. H2 Low Voltage SignalsPin Color Signal Typical Function 1 Green GND Ground2 Black VEE 12 VDC3 White S5bus Communications4 Yellow DIN1 Entry Door, 2 transitions to active5 Orange DIN2 Balcony Door/Window, 2 transitions to active6 Red DIN3 External PIR/Motion Sensor, 2 transitions to active7 Brown AO 0-10 V VFD Fan8 Grey AI Remote Thermistor
INNCOM E7 THERMOSTAT INSTALLATION INSTRUCTIONS336-00012—01HpB Single-Stage Heat: 24 VAC HpB Single-Stage Heat: 100-220 VAC HpO Single-Stage Heat: 110-220 VAC HpO Two-Stage Heat: 24 VAC INITIAL SETUPIMPORTANT: Before going through the initial setup sequences, ensure the thermostat is mounted and connected to the Smart Wall Plate. NOTE: Prior to completing Initialization Mode, or pushing the thermostat configuration from engINN, the thermostat is configured with factory defaults to disable any call for heat, cool, or low, medium and high fan speeds to protect the HVAC equipment. • When properly connected, the thermostat will proceed into INTIALIZATION MODE and display rId. • When not properly connected to the Smart Wall Plate, the unit will display the alert message SWp and the alert icon will illuminate until the Smart Wall Plate is connected. SETUP ROOM ID  1. Once rid is displayed, press MODE. The default Room ID value (65535) is displayed and will begin scrolling across the screen one numerical setting at a time, from highest to lowest (left most to right most value). Note that the five-digit number is comprised of three fields: highest digit, mid-dle two digits, lowest two digits. Three settings must be made. 2. Scrolling will stop at the highest digit first. Use the UP/DOWN arrow buttons to change this value (range is 0-6). Press FAN to continue.3. Set the next two values in the sequence using the UP/DOWN arrow buttons (range is 0-99). Press MODE to continue. Repeat this step for the lowest two values (range is 0-99) and press MODE. Press MODE to accept the value. 4. The new ID number scrolls across the display. The unit beeps  when the value is stored to memory. Once the scroll-ing is completed, Press the DOWN arrow button to dis-play HVAC (HAC) menu.
36-00012—01 4SETUP HVAC TYPE1. After HAC is displayed, press MODE. 2. Set the HVAC type desired using the UP/DOWN arrow buttons to choose one of the following options:00:Not DefinedFC4:  4 pipe fan coil unitFW2: 2 pipe fan coil unit with W2FC2: 2 pipe fan coil unitPAC:PTAC unitHbW: Heat Pump B with W2 assistHpB: Heat Pump B with W2 replaceHoW: Heat Pump O with W2 assistHpO: Heat Pump O with W2 replace3. Press MODE to accept the value. The unit beeps to con-firm the value has been set.4. The display will show - -. Press the DOWN arrow button to display the Fan speed (FAN) menu.SETUP FAN SPEED1. Once FAN is displayed, use the Up/DOWN arrow buttons to choose the fan speed:00:Not DefinedLo: Low Speed (single speed)LH:Low / HighLMh:Low / Medium* / High*For heat pump models utilizing reversing valve, medium heat and medium fan speed will not be available.2. Press MODE to execute the setting, the unit beeps to con-firm it is set.EXIT INITIALIZATION MODEWhen setup is complete, exit INITIALIZATION MODE by pressing the F/C key. Str is displayed, indicating the setup values are stored in memory, the unit reboots and begins operating the HVAC equipment as configured. RESETTING INITIALIZATION MODEIf the user needs to return to the settings made in INITIALIZATION MODE, do the following:1. Enter SERVICE MODE:2. 1. Press and hold F/C.3. 2. Press and hold MODE.4. 3. Press and hold FAN.5. 4. Release F/C.6. Use the UP/DOWN arrow buttons to display rst, then press MODE.7. Use the DOWN button to select 255.8. Press FAN.9. The unit will reset, clear all previous values, and enter INI-TIALIZATION MODE again.
INNCOM E7 THERMOSTAT INSTALLATION INSTRUCTIONSThe material in this document is for information purposes only. The content and the product it describes are subject to change without notice. Honeywell makes no representations or warranties with respect to this document. In no event shall Honeywell be liable for technical or editorial omissions or mistakes in this document, nor shall it be liable for any damages, direct or incidental, arising out of or related to the use of this document. No part of this document may be reproduced in any form or by any means without prior written permission from Honeywell.Copyright © 2017 by Honeywell International, Inc. All Rights Reserved.Honeywell | 277 West Main Street | Niantic, CT 06357 | Phone: 1.860-739-4468 | www.INNCOM.comCONTRACTOR MODEContractor mode allows conditioning a space during the construction phase to a defined set temperature and locking out the key pad to prevent tampering. To configure this mode, do the following:1. Enter SERVICE MODE:(1) Press and hold F/C.(2) Press and hold MODE.(3) Press and hold FAN.(4) Release F/C.2. Use the UP/DOWN arrow buttons to select ctr.3. Use the UP/DOWN arrow buttons to select the targettemperature (range: Off - 80 degrees F).4. Press FAN to continue. Once FAN is pressed, the displayscrolls the set temperature and the unit beeps to confirmthe value has been set.5. Press F/C to exit SERVICE MODE. The unit dis-plays the target and measured temperature, and thealert icon. Any key press to change set temperature,fan speed or mode are locked out.EXIT CONTRACTOR MODE1. Enter SERVICE MODE (Step 1 in the previous section).2. Use the UP/ DOWN arrows to display - - then press FANto turn off CONTRACTOR MODE.3. Press F/C to exit SERVICE MODE.Property Specific ConfigurationsOnce initial setup is completed, the e7 can support a range of expanded Integrated Room Automation System functionality. This additional functionality is deployed using Honeywell's software tools INNtool and engINN. Training for INNtool and engINN for system design and commissioning is now included in the Level 2 and Level 3 classes. INNCOM Authorized Systems Integrators should contact their respective E&ES Regional Support Teams to inquire about enrolling in upcoming training sessions. If you have already received training or you are a Honeywell employee supporting the INNCOM business, you can download the software here: https://www.inncom.com/loginREGULATORY COMPLIANCEUL ListingThis device meets UL 60730-2-9, CAN/CSA-E60730-9 Standard for Automatic Electrical Controls - Part 2-9: Particular Requirements for Temperature Sensing Control Federal Communications Commission (FCC)Changes or modifications not expressly approved by Honeywell International, Inc. could void the user’s authority to operate the equipment.This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules.  These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications.  However, there is no guarantee that interference will not occur in a particular installation.  If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one of the following measures:- Reorient or relocate the receiving antenna.- Increase the separation between the equipment and receiver.- Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.- Consult the dealer or an experienced radio/TV technician for help. This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.This device complies with FCC and IC radiation exposure limits set forth for an uncontrolled environment. This device should be installed and operated with minimum distance of 20cm between the radiator and your body. This device must not be co-located or operating in conjunction with any other antenna or transmitter.This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.Tout changement ou modification n’ayant pas été expressément approuvé par Honeywell International, Inc. pourrait annuler l’autorisation de l’utilisateur d’utiliser l’équipement.Cet équipement a subi des tests prouvant sa conformité aux limites prescrites pour les appareils numériques de classe B, selon la partie 15 des règlements de la FCC. Ces limites ont été conçues pour fournir une protection raisonnable contre les interférencesnuisibles lorsque l’appareil est utilisé dans un environnement résidentiel. Cet équipement génère, utilise et peut émettre de l’énergie radioélectrique et, s’il n’est pas installé et utilisé conformément aux instructions, peut causer des interférences nuisibles aux communications radio. Toutefois, il n’y a aucune garantie que ces interférences ne puissent survenir dans une installation donnée. Si cet équipement cause des interférences nuisibles à la réception de signaux de radio ou de télévision, ce qui peut être déterminé en l’éteignant et en l’allumant, l’utilisateur peut essayer de corriger ces interférences par les mesures suivantes :- Réorienter ou déplacer l’antenne réceptrice.- Augmenter la distance entre l’équipement et le récepteur.- Brancher l’équipement sur un circuit différent de celui sur lequel le récepteur est branché.- Consulter le détaillant ou un technicien expérimenté en radio/télévision pour de l’aide. Cet équipement a subi des tests prouvant sa conformité aux limites prescrites pour les appareils numériques de classe A, selon la partie 15 des règlements de la FCC. Ces limites ont été conçues pour fournir une protection raisonnable contre les interférences nuisibles lorsque l’appareil est utilisé dans un environnement commercial. Cet équipement génère, utilise et peut émettre de l’énergie radioélectrique et, s’il n’est pas installé et utilisé conformément aux instructions, peut causer des interférences nuisibles aux communications radio. L’utilisation de cet équipement dans une zone résidentielle est susceptible de causer des interférences nuisibles auquel cas l’utilisateur sera tenu de corriger ces interférences à ses propres fraisCet équipement est conforme aux limites d’exposition aux rayonnements FCC et IC établies pour un environnement non contrôlé. Cet équipement doit être installé et utilisé avec un minimum de 20cm de distance entre la source de rayonnement et votre corps. Cet appareil ne doivent pas être placés à côté de ou fonctionner en conjonction avec toute autre antenne ou transmetteur.Industry Canada (IC) This device complies with Industry Canada licence-exempt RSS standard(s). Operation is subject to the following two conditions: (1) this device may not cause interference, and (2) this device must accept any interference, including interference that may cause undesired operation of the device.Le présent appareil est conforme aux CNR d'Industrie Canada applicables aux appareils radio exempts de licence. L'exploitation est autorisée aux deux conditions suivantes : (1) l'appareil ne doit pas produire de brouillage, et (2) l'appareil doit accepter tout brouillage radioélectrique subi, même si le brouillage est susceptible d'en compromettre le fonctionnement.

Navigation menu