Ademco 8DL5808W3AP Photoelectric Smoke/Heat Detector User Manual 5808W3 Manual indd

Honeywell International Inc. Photoelectric Smoke/Heat Detector 5808W3 Manual indd

Users Manual Revised

INSTALLATION  AND  MAINTENANCE  INSTRUCTIONS5808W3AP Photoelectronic Smoke/Heat Detector with Built-in Wireless TransmitterD100-100-00  1  I56-2768-000Before  installing  detectors,  please  thoroughly  read  these installation  instructions  and  Manual  I56-407,  Guide  for Proper  Use  of  System  Smoke  Detectors,  which  provides detailed information on detector spacing, placement, zon-ing, wiring, and special applications. Copies of this manual are available from Honeywell.NOTICE: This manual should be left with the owner/user of this equipment.IMPORTANT: This detector must be tested and maintained regularly  following  NFPA  72  requirements.  The  detector should be cleaned at least once a year.General DescriptionThe 5808W3AP photoelectronic  smoke/heat  detector  with built-in  wireless  transmitter  is  intended  for  use  with wireless  alarm  systems  that  support  5800  series  devices. Refer  to  control/communicator  installation  instructions for  compatibility.  The 5808W3AP smoke/heat  detector  can be used  with 5881  series (L,  M, H)  and 5881EH receivers for  residential  installations.  For  commercial  installations, the  5881EH  receiver  should  be  used.  The  transmitter  can send alarm, tamper, maintenance (when control panels are equipped to process maintenance signals), and battery con-dition messages to the system’s receiver. The maintenance signal fully  complies with  the sensitivity  test requirement specified in NFPA 72, 7-2.2. Refer to the wireless system’s instructions for the maximum number of transmitters that can be supported.The 5808W3AP incorporates a state-of-the-art optical sensing chamber and  an advanced microprocessor. The micropro-cessor allows the detector to automatically  adjust its  sen-sitivity back  to the factory setting when it becomes  more sensitive  due  to  contaminants  settling  in  its  chamber.  In order for this feature to work properly, the chamber must never  be  opened  while  power  is  applied  to  the  smoke detector.  This  includes  cleaning,  maintenance  or  screen replacement.  All  models  also  feature  a  restorable,  built-in, fixed temperature (135°F) thermal detector and is also capable of sensing a freeze condition if the temperature is below 41°F.The 5808W3 contains a piezoelectric horn which generates the ANSI S3.41 temporal pattern in an alarm condition. In alarm, a message is also sent to the wireless control panel and  the  smoke  detector’s  ID  number  is  displayed  at  the console. The alarm message is transmitted every 4 seconds until  the  smoke  or  heat  condition  has  cleared  and  the detector has reset. During an alarm condition, pressing the detectors test switch will silence the piezoelectric horn for 5 minutes. Once the detector has reset, a RESTORE message is transmitted to the control panel and the ID number can be cleared from the panel. The built-in Drift Compensation algorithm  automatically  maintains  the  sensitivity  of  the detector. Once the detector reaches its limit of compensa-tion,  it  transmits  a  maintenance  signal  to  the  panel.  The mounting base installation  is simplified by the incorpora-tion of features compatible with drywall fasteners.Two LEDs on the detector provide a local visual indication of the detector’s status:Table 1: Detector LED ModesGreen LED Red LED Piezoelectric HornPower-up Blink 5 sec Blink 5 sec OffNormal (standby) Blink 10 sec — OffOut of sensitivity — Blink 5 sec OffFreeze Trouble — Blink 10 sec OffSmoke Alarm — Blink 1 sec Temporal PatternThermal Alarm --- Blink 4 sec Temporal PatternLow Battery --- Blink 45 sec Chirp 45 secDuring an initial power-up delay, the red and green LEDs will  blink  synchronously  once  every  five  seconds.  It  will take approximately 20 seconds for the detector to finish the power-up cycle (see Table 2).After power-up has completed and the detector is function-ing  normally  within  its  listed  sensitivity  range,  the  green LED  blinks  once  every  ten  seconds.  If  the  detector  is  in need  of  maintenance  because  its  sensitivity  has  shifted outside the listed limits, the red LED blinks once every five seconds. When alarm has been activated by smoke, the red LED blinks every 1 second. During a thermal alarm condi-tion  (>135°F)  the  red LED blinks once every 4 seconds. The  LED  indication must not be used in lieu of the  tests specified under Testing. In a freeze trouble condition, the red LED will blink once every 10 seconds (refer to Table 1). February 22, 20053825 Ohio Avenue, St. Charles, Illinois 60174800/736-7672, FAX: 630/377-6495www.systemsensor.comFCC ID & FCC PART 15STATMENT ON LAST PAGE
D100-100-00  7  I56-2768-000©2005 ADEMCOPlease refer to insert for the Limitations of Fire Alarm SystemsSmoke detectors shall be replaced after being in service for 10 years. However, any smoke detector, fire alarm equipment, or any component of that system which fails prior to that shall be repaired or replaced as soon as possible. Batteries shall be replaced upon indication of a pre-low battery condition.HONEYWELL One-Year Limited WarrantyHoneywell International Inc. (“Seller”), 165 Eileen Way, Syosset, NY 11791, warrants its security equipment (the “product”) to be free from defects inmaterials and workmanship for one year from date of original purchase, under normal use and service. Seller’s obligation is limited to repairing orreplacing, at its option, free of charge for parts, labor, or transportation, any part proven to be defective in materials or workmanship under normaluse and service. Seller shall have no obligation under this warranty otherwise if the product is altered or improperly repaired or serviced by anyoneother than the seller. In case of defect, contact the security professional who installed and maintains your security system or the Seller for productrepair.This one year Limited Warranty is in lieu of all other express warranties, obligations, or liabilities. THERE ARE NO EXPRESS WARRANTIES WHICH EXTEND  BEYOND  THE  FACE  HEREOF.  ALL  IMPLIED  WARRANTIES,  OBLIGATIONS,  OR  LIABILITIES  MADE  BY  SELLER  IN  CONNECTION  WITH THIS PRODUCT, INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY, OR FITNESS FOR A PARTICULAR PURPOSE OR OTHERWISE, ARE LIMITED IN DURATION TO A PERIOD OF ONE YEAR FROM THE DATE OF ORIGINAL PURCHASE. ANY ACTION OR BREACH OF ANY WARRANTY, INCLUDING BUT  NOT  LIMITED TO  ANY  IMPLIED WARRANTY  OF MERCHANTABILITY, MUST  BE BROUGHT WITHIN  18 MONTHS OF  DATE  OF ORIGINAL PURCHASE. IN NO CASE SHALL SELLER BE LIABLE TO ANYONE FOR ANY CONSEQUENTIAL OR INCIDENTAL DAMAGES FOR BREACH OF THIS OR ANY OTHER WARRANTY, EXPRESS OR IMPLIED, OR UPON ANY OTHER BASIS OF LIABILITY WHATSOEVER, EVEN IF THE LOSS OR DAMAGE IS CAUSED BY THE SELLER’S OWN NEGLIGENCE OR FAULT. Some states do not allow limitations on how long an implied warranty lasts or the exclusion of incidental or consequential damages, so above limitation or exclusion may not apply to you.Seller does not represent that the product may not be compromised or circumvented; that the product will prevent any personal injury or property loss by burglary, robbery, fire or otherwise; or that the product will in all cases provide adequate warning or protection. Buyer understands that a properly installed and maintained alarm my only reduce the risk of a burglary, robbery, or fire occurring without providing an alarm, but it is not insurance or a guarantee that such will not occur or that there will be no personal injury or property loss as a result. CONSEQUENTLY, SELLER SHALL HAVE NO LIABILITY FOR ANY PERSONAL INJURY, PROPERTY DAMAGE, OR OTHER LOSS BASED ON A CLAIM THAT THE PRODUCT FAILED TO GIVE WARNING. However, if seller is held liable, whether directly or indirectly, for any loss or damage arising under this Limited Warranty or otherwise, regardless of cause or origin, Seller’s maximum liability shall not in any case exceed the purchase price of the product, and shall be the complete and exclusive remedy against Seller. This warranty gives you specific legal rights, and you may also have other rights which vary from state to state. No increase or alteration, written or verbal, to this warranty is authorized.FCC ID: CFS8DL5808W3AP                                                                           This device complies with part 15 of the FCC Rules.                                                                                    Operation is subject to the following two conditions:                                                                                    (1) This device may not cause harmful interference,                                                                                    and (2) this device must accept any interference                                                                                    received, including interference that may cause                                                                                    undesired operation.             NOTE: Changes or modifications not expressly approved by the manufacturer could void the user’s authority to operate the equipment.             SpecificationsPower Source:  One 3-volt CR123A Lithium Batteries (included). (Replace with Duracell DL123A, Sanyo CR123A, Panasonic CR123A or ADEMCO 466.)Height:  2.3 inches (58 mm)Diameter:  5.3 inches (135 mm) with mounting baseWeight:  8.5 oz. (241 g) without batteryOperating Ambient Temperature Range:  0° to 38°C (32° to 100°F)Operating Humidity Range:  0% to 95% Relative HumidityHeat Sensor:  135° F Fixed Temperature Electronic Thermistors Freeze Trouble:  41°F (5°C)Agency Listings:  UL 268 – Commercial and Residential Installations

Navigation menu