Ademco 8DL5808W3AP Photoelectric Smoke/Heat Detector User Manual 5808W3 Manual indd

Honeywell International Inc. Photoelectric Smoke/Heat Detector 5808W3 Manual indd

Users Manual Revised

Download: Ademco 8DL5808W3AP Photoelectric Smoke/Heat Detector User Manual 5808W3 Manual indd
Mirror Download [FCC.gov]Ademco 8DL5808W3AP Photoelectric Smoke/Heat Detector User Manual 5808W3 Manual indd
Document ID801198
Application IDB5ftlHjUtIPNo/n2ODzh2w==
Document DescriptionUsers Manual Revised
Short Term ConfidentialNo
Permanent ConfidentialNo
SupercedeNo
Document TypeUser Manual
Display FormatAdobe Acrobat PDF - pdf
Filesize28.14kB (351750 bits)
Date Submitted2007-06-07 00:00:00
Date Available2007-06-08 00:00:00
Creation Date2004-10-21 08:37:50
Producing SoftwareAdobe PDF Library 6.0
Document Lastmod2007-06-07 12:06:24
Document Title5808W3 Manual.indd
Document CreatorAdobe InDesign CS (3.0.1)

FCC ID & FCC PART 15
STATMENT ON LAST
INSTALLATION AND PAGE
MAINTENANCE INSTRUCTIONS
Febr
uary
5808W3AP Photoelectronic Smoke/Heat 2,
Detector with Built-in Wireless Transmitter
2 0 0 5 3825 Ohio Avenue, St. Charles, Illinois 60174
800/736-7672, FAX: 630/377-6495
www.systemsensor.com
alarm, a message is also sent to the wireless control panel
and the smoke detector’s ID number is displayed at the
console. The alarm message is transmitted every 4 seconds
until the smoke or heat condition has cleared and the
detector has reset. During an alarm condition, pressing the
detectors test switch will silence the piezoelectric horn for 5
minutes. Once the detector has reset, a RESTORE message
is transmitted to the control panel and the ID number can
be cleared from the panel. The built-in Drift Compensation
algorithm automatically maintains the sensitivity of the
detector. Once the detector reaches its limit of compensation, it transmits a maintenance signal to the panel. The
mounting base installation is simplified by the incorporation of features compatible with drywall fasteners.
Before installing detectors, please thoroughly read these
installation instructions and Manual I56-407, Guide for
Proper Use of System Smoke Detectors, which provides
detailed information on detector spacing, placement, zoning, wiring, and special applications. Copies of this manual
are available from Honeywell.
NOTICE: This manual should be left with the owner/user
of this equipment.
IMPORTANT: This detector must be tested and maintained
regularly following NFPA 72 requirements. The detector
should be cleaned at least once a year.
General Description
The 5808W3AP photoelectronic smoke/heat detector with
built-in wireless transmitter is intended for use with
wireless alarm systems that support 5800 series devices.
Refer to control/communicator installation instructions
for compatibility. The 5808W3AP smoke/heat detector can
be used with 5881 series (L, M, H) and 5881EH receivers
for residential installations. For commercial installations,
the 5881EH receiver should be used. The transmitter can
send alarm, tamper, maintenance (when control panels are
equipped to process maintenance signals), and battery condition messages to the system’s receiver. The maintenance
signal fully complies with the sensitivity test requirement
specified in NFPA 72, 7-2.2. Refer to the wireless system’s
instructions for the maximum number of transmitters that
can be supported.
Two LEDs on the detector provide a local visual indication
of the detector’s status:
Table 1: Detector LED Modes
Green LED
Red LED
Piezoelectric Horn
Power-up
Blink 5 sec
Blink 5 sec
Off
Normal (standby)
Blink 10 sec
—
Off
Out of sensitivity
—
Blink 5 sec
Off
Freeze Trouble
—
Blink 10 sec
Off
Smoke Alarm
—
Blink 1 sec
Temporal Pattern
Thermal Alarm
---
Blink 4 sec
Temporal Pattern
Low Battery
---
Blink 45 sec
Chirp 45 sec
During an initial power-up delay, the red and green LEDs
will blink synchronously once every five seconds. It will
The 5808W3AP incorporates a state-of-the-art optical sensing take approximately 20 seconds for the detector to finish the
chamber and an advanced microprocessor. The micropro- power-up cycle (see Table 2).
cessor allows the detector to automatically adjust its sensitivity back to the factory setting when it becomes more After power-up has completed and the detector is functionsensitive due to contaminants settling in its chamber. In ing normally within its listed sensitivity range, the green
order for this feature to work properly, the chamber must LED blinks once every ten seconds. If the detector is in
never be opened while power is applied to the smoke need of maintenance because its sensitivity has shifted
detector. This includes cleaning, maintenance or screen outside the listed limits, the red LED blinks once every five
replacement. All models also feature a restorable, built- seconds. When alarm has been activated by smoke, the red
in, fixed temperature (135°F) thermal detector and is also LED blinks every 1 second. During a thermal alarm condicapable of sensing a freeze condition if the temperature is tion (>135°F) the red LED blinks once every 4 seconds.
below 41°F.
The LED indication must not be used in lieu of the tests
specified under Testing. In a freeze trouble condition, the
red LED will blink once every 10 seconds (refer to Table 1).
The 5808W3 contains a piezoelectric horn which generates
the ANSI S3.41 temporal pattern in an alarm condition. In
D100-100-00
I56-2768-000
Specifications
Power Source:
One 3-volt CR123A Lithium Batteries (included). (Replace with Duracell
DL123A, Sanyo CR123A, Panasonic CR123A or ADEMCO 466.)
Height:
2.3 inches (58 mm)
Diameter:
5.3 inches (135 mm) with mounting base
Weight:
8.5 oz. (241 g) without battery
Operating Ambient Temperature Range: 0° to 38°C (32° to 100°F)
Operating Humidity Range:
0% to 95% Relative Humidity
Heat Sensor:
135° F Fixed Temperature Electronic Thermistors
Freeze Trouble:
41°F (5°C)
Agency Listings:
UL 268 – Commercial and Residential Installations
Please refer to insert for the Limitations of Fire Alarm Systems
Smoke detectors shall be replaced after being in service for 10 years. However, any smoke detector, fire alarm equipment, or any component of that system
which fails prior to that shall be repaired or replaced as soon as possible. Batteries shall be replaced upon indication of a pre-low battery condition.
HONEYWELL One-Year Limited Warranty
Honeywell International Inc. (“Seller”), 165 Eileen Way, Syosset, NY 11791, warrants its security equipment (the “product”) to be free from defects in
materials and workmanship for one year from date of original purchase, under normal use and service. Seller’s obligation is limited to repairing or
replacing, at its option, free of charge for parts, labor, or transportation, any part proven to be defective in materials or workmanship under normal
use and service. Seller shall have no obligation under this warranty otherwise if the product is altered or improperly repaired or serviced by anyone
other than the seller. In case of defect, contact the security professional who installed and maintains your security system or the Seller for product
repair
This one year Limited Warranty is in lieu of all other express warranties, obligations, or liabilities. THERE ARE NO EXPRESS WARRANTIES WHICH
EXTEND BEYOND THE FACE HEREOF. ALL IMPLIED WARRANTIES, OBLIGATIONS, OR LIABILITIES MADE BY SELLER IN CONNECTION WITH
THIS PRODUCT, INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY, OR FITNESS FOR A PARTICULAR PURPOSE OR OTHERWISE, ARE
LIMITED IN DURATION TO A PERIOD OF ONE YEAR FROM THE DATE OF ORIGINAL PURCHASE. ANY ACTION OR BREACH OF ANY WARRANTY,
INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTY OF MERCHANTABILITY, MUST BE BROUGHT WITHIN 18 MONTHS OF DATE OF
ORIGINAL PURCHASE. IN NO CASE SHALL SELLER BE LIABLE TO ANYONE FOR ANY CONSEQUENTIAL OR INCIDENTAL DAMAGES FOR BREACH
OF THIS OR ANY OTHER WARRANTY, EXPRESS OR IMPLIED, OR UPON ANY OTHER BASIS OF LIABILITY WHATSOEVER, EVEN IF THE LOSS OR
DAMAGE IS CAUSED BY THE SELLER’S OWN NEGLIGENCE OR FAULT. Some states do not allow limitations on how long an implied warranty lasts or
the exclusion of incidental or consequential damages, so above limitation or exclusion may not apply to you.
Seller does not represent that the product may not be compromised or circumvented; that the product will prevent any personal injury or property loss
by burglary, robbery, fire or otherwise; or that the product will in all cases provide adequate warning or protection. Buyer understands that a properly
installed and maintained alarm my only reduce the risk of a burglary, robbery, or fire occurring without providing an alarm, but it is not insurance
or a guarantee that such will not occur or that there will be no personal injury or property loss as a result. CONSEQUENTLY, SELLER SHALL HAVE
NO LIABILITY FOR ANY PERSONAL INJURY, PROPERTY DAMAGE, OR OTHER LOSS BASED ON A CLAIM THAT THE PRODUCT FAILED TO GIVE
WARNING. However, if seller is held liable, whether directly or indirectly, for any loss or damage arising under this Limited Warranty or otherwise,
regardless of cause or origin, Seller’s maximum liability shall not in any case exceed the purchase price of the product, and shall be the complete and
exclusive remedy against Seller. This warranty gives you specific legal rights, and you may also have other rights which vary from state to state. No
increase or alteration, written or verbal, to this warranty is authorized.
FCC ID: CFS8DL5808W3AP
This device complies with part 15 of the FCC Rules.
Operation is subject to the following two conditions:
(1) This device may not cause harmful interference,
and (2) this device must accept any interference
received, including interference that may cause
undesired operation.
NOTE: Changes or modifications not expressly approved by the manufacturer could void the user’s authority to operate the equipment.
D100-100-00
I56-2768-000
©2005 ADEMCO

Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.5
Linearized                      : No
Page Count                      : 2
Has XFA                         : No
XMP Toolkit                     : XMP toolkit 2.9.1-13, framework 1.6
About                           : uuid:c5ac832e-c924-4c48-94e9-e017a8276a0c
Create Date                     : 2004:10:21 08:37:50Z
Modify Date                     : 2007:06:07 12:06:24-04:00
Metadata Date                   : 2007:06:07 12:06:24-04:00
Creator Tool                    : Adobe InDesign CS (3.0.1)
Thumbnail Format                : JPEG
Thumbnail Width                 : 256
Thumbnail Height                : 256
Thumbnail Image                 : (Binary data 11612 bytes, use -b option to extract)
Version ID                      : 1
Rendition Class                 : proof:pdf
Document ID                     : adobe:docid:indd:3cab1292-2379-11d9-9bb0-b5cd14159aee
Format                          : application/pdf
Title                           : 5808W3 Manual.indd
Trapped                         : False
Creator                         : Adobe InDesign CS (3.0.1)
Producer                        : Adobe PDF Library 6.0
EXIF Metadata provided by EXIF.tools
FCC ID Filing: CFS8DL5808W3AP

Navigation menu