Ademco 8DLLYNXTOUCH1 Wireless Control / Communicator User Manual 800 06834 ii
Honeywell International Inc. Wireless Control / Communicator 800 06834 ii
Ademco >
Contents
- 1. Installers Manual
- 2. Users Manual
Installers Manual
PLEASE USE BOOKMARKS TO GO TO VARIOUS AGENCY STATEMENTS LYNX Touch Series Security Systems Installation and Setup Guide ARMED 800-06834 1/11 Rev. A READY LYNX Touch Installation and Setup Guide RECOMMENDATIONS FOR PROPER PROTECTION The Following Recommendations for the Location of Fire and Burglary Detection Devices Help Provide Proper Coverage for the Protected Premises. Recommendations for Smoke and Heat Detectors With regard to the number and placement of smoke/heat detectors, we subscribe to the recommendations contained in the National Fire Protection Association's (NFPA) Standard #72 noted below. • Early warning fire detection is best achieved by the installation of fire detection equipment in all rooms and areas of the household as follows: For minimum protection a smoke detector should be installed outside of each separate sleeping area, and on each additional floor of a multi-floor family living unit, including basements. The installation of smoke detectors in kitchens, attics (finished or unfinished), or in garages is not normally recommended. • For additional protection the NFPA recommends that you install heat or smoke detectors in the living room, dining room, bedroom(s), kitchen, hallway(s), attic, furnace room, utility and storage rooms, basements and attached garages. In addition, we recommend the following: • Install a smoke detector inside every bedroom where a smoker sleeps. • Install a smoke detector inside every bedroom where someone sleeps with the door partly or completely closed. Smoke could be blocked by the closed door. Also, an alarm in the hallway outside may not wake up the sleeper if the door is closed. • Install a smoke detector inside bedrooms where electrical appliances (such as portable heaters, air conditioners or humidifiers) are used. • Install a smoke detector at both ends of a hallway if the hallway is more than 40 feet (12 meters) long. • Install smoke detectors in any room where an alarm control is located, or in any room where alarm control connections to an AC source or phone lines are made. If detectors are not so located, a fire within the room could prevent the control from reporting a fire or an intrusion. THIS CONTROL COMPLIES WITH NFPA REQUIREMENTS FOR TEMPORAL PULSE SOUNDING OF FIRE NOTIFICATION APPLIANCES. KITCHEN DINING BEDROOM BEDROOM TV ROOM KITCHEN DINING BDRM LIVING ROOM BDRM BEDROOM BEDROOM LIVING ROOM Smoke Detectors for Minimum Protection Smoke Detectors for Additional Protection Heat-Activated Detectors BEDROOM BEDROOM TO BR BEDROOM KTCHN LVNG RM CLOSED DOOR GARAGE BASEMENT floor_plan-001-V1 Recommendations For Proper Intrusion Protection • For proper intrusion coverage, sensors should be located at every possible point of entry to a home or premises. This would include any skylights that may be present, and the upper windows in a multi-level building. • In addition, we recommend that radio backup be used in a security system. This will ensure that alarm signals can be sent to the alarm monitoring station in the event that the telephone lines are out of order (alarm signals are normally sent over the phone lines, if connected to an alarm monitoring station). -2- LYNX Touch Installation and Setup Guide Table of Contents System Features.....................................................................................................................................................5 Mounting the Control ...........................................................................................................................................6 Wall Mounting ....................................................................................................................................................6 Desktop Mounting ..............................................................................................................................................6 Wiring Overview .................................................................................................................................................6 Wiring Connections...............................................................................................................................................7 AC Power and Backup Battery ..........................................................................................................................9 Installing/Configuring Communications Modules ......................................................................................10 General ..............................................................................................................................................................10 Connecting and Configuring Communications Modules ...............................................................................10 Installing Wireless Zones...................................................................................................................................12 General Information.........................................................................................................................................12 5800 Series Transmitter Loop Numbers.........................................................................................................12 Mechanics of Programming ..............................................................................................................................15 Navigating Menus ............................................................................................................................................15 General Programming Information.................................................................................................................16 Programming ....................................................................................................................................................17 Loading Factory Defaults.................................................................................................................................17 Exiting programming Mode .............................................................................................................................17 Zone Response Type Definitions .....................................................................................................................18 General ..............................................................................................................................................................18 Programming the Control .................................................................................................................................20 Change Installer Code......................................................................................................................................20 System Type......................................................................................................................................................21 Program Date and Time...................................................................................................................................23 Program the Communications Module ...........................................................................................................24 Program Zones ..................................................................................................................................................26 Program Keys ...................................................................................................................................................28 Reporter.............................................................................................................................................................30 Sounder .............................................................................................................................................................36 System Settings ................................................................................................................................................37 Communications Diagnostics...........................................................................................................................40 Remote Programming/Control (Downloading) ............................................................................................46 General Information.........................................................................................................................................46 Remote Programming Information .................................................................................................................46 System Operation ................................................................................................................................................48 Key/Touchscreen Operation.............................................................................................................................48 Panic key/Icons .................................................................................................................................................48 Security Codes ..................................................................................................................................................48 “Follow Me” System Announcement Feature .................................................................................................50 “Follow Me” Reminder Feature .......................................................................................................................51 -3- LYNX Touch Installation and Setup Guide Table of Contents (Continued) Remote Phone Control Feature .......................................................................................................................51 System Displays................................................................................................................................................52 Zone Status Displays........................................................................................................................................52 Audio alarm Verification (Two-Way Voice Feature) ......................................................................................53 Testing the System ..............................................................................................................................................55 Event Log ..........................................................................................................................................................54 Contact ID & SIA Event Log Codes ................................................................................................................54 Test Mode ..........................................................................................................................................................55 Armed System Test ..........................................................................................................................................55 LYNX Touch Programming Default Tables...................................................................................................56 LYNX Touch SIA Programming Default Tables...........................................................................................59 Zone Programming Default Tables .................................................................................................................60 Regulatory Agency Statements........................................................................................................................63 Limitations of this System Statement ............................................................................................................64 UL Notices .............................................................................................................................................................65 SIA Quick Reference Guide ..............................................................................................................................65 Specifications .......................................................................................................................................................66 Contacting Technical Support .........................................................................................................................67 Glossary .................................................................................................................................................................68 Index .......................................................................................................................................................................69 Summary of Connections Diagram .................................................................................................................71 Warranty Information ........................................................................................................................ Rear Cover -4- LYNX Touch Installation and Setup Guide System Features The LYNX Touch control is a self-contained, rechargeable wireless control/communicator that features easy installation and usage. A built-in speaker provides voice annunciation of system status along with voice descriptors of each zone. An internal module (if provided) allows the LYNX Touch to communicate with the Central Station via the Internet or GSM Cellular Wireless. UL LYNX Touch is not intended for UL985 Household Fire applications unless a 24-hour backup battery (P/N 300-03866/LYNXRCHKIT-SHA) is installed. Features Alarm Output • Built-in sounder • Steady output for burglary/panic • Temporal (3) pulse output for fire alarms • Temporal (4) pulse output for carbon monoxide alarms • Long range radio (GSM)/audio alarm verification • Trigger output System Features • 4.7-inch color graphic touch screen • Message center (for user recorded messages) • Voice announcement of system and zone status • Voice chime • Reminders • Automatic stay arming • Remote phone control • Speaker phone operation • “Follow me” reminder and system announcements • 16 User Codes (Installer, Master, Babysitter, Duress) • 3 Panic Functions • 16 Programmable reminders Programming • Options stored in EEROM • Can be uploaded, downloaded or controlled via IBM-compatible computer using Compass downloader software and specified HAYES or Honeywell CIA modem or via capable GSM or IP communications module • Flash downloading Zones and Devices • 64 total zones including 1 Hardwire (EOLR, N/C, N/O) zone and up to 63 wireless zones (5800 Series transmitters) • 2 Resident Monitor Zone Types • Supports wireless keypads • Built-in Case tamper Other Features • Exit error feature (detects difference between an actual alarm and exit alarm caused by leaving a door open after the exit delay expires) • Event log stores up to 128 events • RF jam detection • Two installer programmable user phone numbers Communication • ADEMCO Contact ID • SIA (DC-03) • Internet central station communication • GSM cellular central station communication • Two-way voice communication • Supports AlarmNet remote services System Power • Primary Power: Plug-in Power Supply, 110VAC to 9VDC, 2.7A output 300-04705 or 300-04065 (300-04063 in Canada) • Backup battery: Rechargeable nickel-metal hydride battery pack rated at 7.2Vdc. (P/N 30003864-1/LYNXRCHKIT-SC or 30003866/LYNXRCHKIT-SHA) -5- LYNX Touch Installation and Setup Guide Mounting the Control Wall Mounting MOUNTING HOOKS (HINGES) 1. Release the front case from the back case by depressing the two locking tabs at the top of the unit with the blade of a medium size screwdriver. TIE WRAP POINT (3) 2. Separate the front and back case assemblies by rotating the front case so that it is perpendicular to the back case and unsnapping (releasing) the two hooks from the back case. BACK CASE 3. Feed the field wiring through the appropriate openings in the back case. Use tie-wraps to secure the wiring to the built-in wire loops as needed. MOUNTING HOLES (4) 4. Mount the back case to a sturdy wall. ROTATE FRONT CASE UPWARD TO RELEASE HOOKS 5. Attach the front and back cases by connecting the hooks on the front case to the attachments on the back case. Once attached, the hooks will support the front case and allow you to make the wiring connections. 6. After all wiring connections have been made, snap the front case and back case closed and ensure that the case is secured by the locking tabs. TIE WRAP POINTS (2) FRONT CASE LOCKING TABS 5000-100-091-V0 Desktop Mounting For desktop mounting, the optional mounting base (model L5000DM, purchased separately) must be used. 1. Slide the control panel onto the mounting base locking tabs. 2. Bring all wiring through the bottom of the mounting base, using one of the wire entry locations, before making connections to the control panel. 3. Use tie-wraps to secure the wiring to the built-in wire loops as needed. ARMED READY 4. Use the supplied screws to secure the control panel to the mounting base. 5000-100-092-V0 Wiring Overview The following summarizes the connections required. Refer to the Wiring Connections paragraph and the Summary of Connections diagram on the inside back cover when making connections. TELEPHONE CONNECTION SUPER HIGH CAPACITY BATTERY CONNECTION STANDARD CAPACITY BATTERY CONNECTION POWER SUPPLY RECEPTACLE TELEPHONE CONNECTIONS TERMINAL STRIP GSMVLP5/ILP5 RECEPTACLE TAMPER SWITCH 5000-100-087-V0 -6- LYNX Touch Installation and Setup Guide Wiring Connections INCOMING PHONE LINE 1. Make Earth Ground Connection - The designated earth ground terminal EGND must be terminated in a good earth ground for the lightning transient protective devices in this product to be effective. The following are examples of good earth grounds available at most installations: RING TIP RED Metal Cold Water Pipe - Secure a non-corrosive metal strap (copper is recommended) to the pipe that is electrically connected and secured to which the ground lead is electrically connected and secured. TO PREMISES PHONES RJ31X GREY AC Power Outlet Ground - Available from 3-prong, 120VAC power outlets only. To test the integrity of the ground terminal, use a threewire circuit tester with neon lamp indicators, such as the UL Listed Ideal Model 61-035, or equivalent, available at most electrical supply stores. a. Connect terminal EGND to a good earth ground as shown on the Summary of Connections. RING TIP BROWN DIRECT CONNECT CORD INCOMING PHONE LINE GREY H/S R BROWN H/S T RED RING GREEN OR OR TIP 2. Make Phone Line Connections - For local or full line seizure follow the appropriate steps below. Local Seizure a. Connect the incoming phone line to either the 8 position jack or terminals TIP and RING on the LYNX Touch as shown on the Summary of Connections. b. Connect the handset phone lines to terminals H/S T (TIP) and H/S R (RING) as shown on the Summary of Connections. terminals as shown in the diagram or plug into the 8-position Full Line Seizure: The control must be placed in series with the incoming phone line. Plugging the Direct Connect Cord directly into the RJ31X jack, allows the control to seize the phone line when an alarm occurs and normal phone line usage by the premises phones if the plug needs to be removed. c. Cut the incoming RING and TIP phone lines (typically red and green, respectively) and connect them to RJ31X terminals 4 (red) and 5 (green). GREEN 8-POSITION JACK TO PREMISES PHONES FULL LINE SEIZURE CONNECTIONS d. Connect the premises end of the cut RING and TIP wires to RJ31X terminals 1 (grey) and 8 (brown) respectively. e. Wire the flying leads of a Direct Connect Cord to the control's phone terminals as shown in the diagram or plug into the 8position jack. f. Plug the Direct Connect Cord into the RJ31X jack. HARDWIRED ZONE: If the EOLR is not at the end of the loop, the zone will not be properly supervised, and the system may not respond to an open circuit on the zone. 3. Hardwired Zone Connections - One EOLR supervised zone supports both open circuit and closed circuit devices and has a response time of 350msec. Maximum zone resistance: 300 ohms, plus EOLR Note: The hardwire zone cannot be used as a fire zone. a. Connect sensors/contacts to the hardwired zone terminals GND (-) and HWZ1 (+). Refer to the Summary of Connections diagram. b. Connect closed circuit devices in series in the high (+) side of the loop. The EOL resistor must be connected in series with the devices, following the last device. c. Connect open circuit devices in parallel across the loop. The 2000-ohm EOLR must be connected across the loop at the last device. WIRING TABLE DISTANCE BETWEEN POWER SUPPLY AND CONTROL 4. AC Power Connections - Connect the Power Supply to the receptacle on the LYNX Touch. OR Connect wires from the Power Supply to +9VDC and EGND terminals as shown on the summary of connections diagram. Up to 75 feet 75 to 150 feet WIRE GAUGE # 20 # 18 5000-100-094-V1 -7- LYNX Touch Installation and Setup Guide Wiring Connections Installing the L5000-RJ31X in the LYNX Touch Control An auxiliary L5000-RJ31X receptacle can be installed in the LYNX Touch that will allow the telephone cable to be disconnected without requiring the unit to be opened up. 1. 2. 3. 4. 5. 6. 7. Using a wire cutter or knife cut the plastic tabs that secure the receptacle knockout from the left side of the LYNX Touch back case. Connect four wires between the L5000-RJ31X receptacle terminal strip and the incoming phone line and the premises telephones as shown on the figure below. Install the L5000-RJ31X receptacle into the slot on the back case. Connect one end of the L5000-RJ31X cable to the 8-position jack on the LYNX Touch PC board. Route the cable through the opening in the back case and along the wire channel in the back case. Connect the other end of the cable to the L5000-RJ31X receptacle on the side of the back case as shown below. Secure the wires to the tie wrap points on LYNX Touch front and back case with the provided tie wraps. To allow flush wall or desk mounting of the control, ensure that L5000-RJ31X cable is routed through the channel in the case back. Ensure enough slack is left in the wires to allow the case to close without pinching the wires. INCOMING / PREMISES TELEPHONE WIRING L5000-RJ31X L5000-RJ31X CABLE REMOVE KNOCKOUT TIE WRAP POINT REFER TO WIRING SCHEMATIC FOR CONNECTIONS L5000-RJ31X WIRING TO PREMISES TELEPHONES TIP RING HS RING HS TIP L5000-RJ31X TERMINAL STRIP INCOMING PHONE LINE TIE WRAP POINT 5000-100-155-V1 -8- LYNX Touch Installation and Setup Guide AC Power and Backup Battery The system is powered by a 9 Volt DC, 2.7 Amp Plug-in Power Supply, 300-04705 or 300-04065 (300-04063 in Canada). Refer to the wiring table below for wire gauge and length. In the event of an AC power loss, the system is supported by a long life backup battery that is supervised for connection and for low voltage conditions. If the battery is missing, or a low battery condition is detected, a “low battery” message is displayed and a report is sent to the central station. In addition, the system will beep once every 45 seconds to audibly indicate a low battery condition (press any key to stop the beeping). Use only the provided 300-04705 or 300-04065 (300-04063 Canada) Power Supply. Wiring to the Power Supply must not exceed 300 feet using 16-gauge wire. Do not plug the power supply into the AC outlet until after all wiring connections have been made. Ensure the cover is snapped closed prior to applying AC power The LYNX Touch is equipped with an integral, replaceable, rechargeable battery pack rated at 7.2Vdc. Select the appropriate battery pack, based on the installation’s requirement, and install the battery pack. Installing the Rechargeable Backup Battery 1. Remove battery retainer. 2. Insert battery pack into back case. 3. Route cable through channel (cutout) on left side of compartment. 4. Install battery retainer. 5. Secure battery retainer with the provided screw. 6. Secure battery wiring in the wire routing clips (3). 7. Connect the battery connector to the receptacle on the PC board. 8. After the wiring connection has been made, snap the front and the back case closed. 9. Plug the power supply into a 24-hour, 110VAC unswitched outlet. Upon powerup, the system will display "Please Wait Checking System Integrity". SCREW SCREW RETAINER RETAINER BATTERY PACK (P/N 300-03866/ LYNXRCHKIT-SHA) BATTERY PACK (P/N 300-03864-1/ LYNXRCHKIT-SC) OR Replacing the Rechargeable Backup Battery 1. When battery replacement is required, unplug the transformer from the wall outlet, and open the control panel cover. 2. Remove the screw that secures the battery retainer. 3. Remove the battery retainer and disconnect the battery pack connector from the receptacle on the PC Board. 4. Remove the battery pack from the back case. 5. Install a replacement battery pack (P/N 300-03864-1/ LYNXRCHKIT-SC or P/N 300-03866/LYNXCHKIT-SHA) into the back case. 6. Route cable through channel (cutout) on left side of compartment. 7. Install the battery retainer. 8. Secure battery retainer with the provided screw. Secure battery wiring in the wire routing clips (3). 9. Connect the battery connector to the receptacle on the PC board. 10. After the wiring connection has been made, snap the front and the back case closed. 11. Plug the power supply into a 24-hour, 110VAC unswitched outlet. Upon powerup, the system will display "Please Wait Checking System Integrity". Ensure the control panel assembly is snapped closed prior to applying AC power. Rechargeable batteries may take up to 48-hours to fully charge. The "Low Battery" message should clear within four hours or by entering an OFF sequence. BATTERY CABLE CHANNEL BATTERY WIRE ROUTING CLIPS (3) Battery Selection The LYNX Touch is equipped with an integral, replaceable, rechargeable battery pack rated at 7.2Vdc. Select the appropriate battery pack, based on the installation's requirement, and install the battery pack. Battery Part Number Battery StandbyTime 300-03864-1/ LYNXRCHKIT-SC 4-hours (minimum) Approximately 1-hour before battery depletion 300-03866/ LYNXRCHKIT-SHA 24-hours (minimum) At least 1-hour before batter y depletion Low Battery Notification 5000-100-093-V0 -9- LYNX Touch Installation and Setup Guide Installing/Configuring Communication Modules General This LYNX Touch control supports central station reporting using wireless (GSM) and hardwire (IP) communications modules. It also supports upload/download programming capability via the Internet or a Private local area network (Intranet). This allows site maintenance independent of central station monitoring, and modification to sites globally via the Internet or through a private LAN. Refer to the instructions provided with the LRR/IP Communications Module being installed for additional information regarding its installation, programming, and registration. The control is compatible with the following AlarmNet Communications Modules: • GSMVLP5 GSM Communication Module • ILP5 Ethernet Communications Module Communications Module 24-Hour Standby Power If you require 24-hour standby, you must install the Super High Capacity battery P/N LYNX-RCHB-SHA in the control. RF Exposure WARNING: The LYNX Touch must be installed to provide a separation distance of at least 7.8 in (20 cm) from all persons and not co-located or operated in conjunction with any other transmitter. Connecting and Configuring Communication Modules Connect and configure the communications module as follows: Installing the GSMVLP5 in the LYNX Touch Control Ensure that SIM card and the connector board are securely installed in the GSMVLP5 before installing the communications module in the LYNX Touch. 1. 2. 3. Install the GSMVLP5 into the LYNX Touch control front case. Ensure that the connector board is properly seated into the receptacle on the control. Secure the GSMVLP5 with the three provided screws. Enable the GSMVLP5 device, configure alarm reporting and module supervision and register the device. Refer to the “Program the Communications Module” and “Communications Diagnostics” sections. The communications module must be registered with AlarmNet before downloading or alarm reporting can take place. SCREW CONNECTOR BOARD CONNECTOR BOARD SIM CARD ROTATED 180 GSMVLP5 RECEPTACLE LYNX TOUCH 5000-100-151-V0 - 10 - LYNX Touch Installation and Setup Guide Installing/Configuring Communication Modules Installing the ILP5 in the LYNX Touch Control Ensure that the connector board and cable are securely installed in the ILP5 before installing the communications module in the LYNX Touch. 1. 2. 3. 4. 5. 6. 7. 8. Using a wire cutter or knife cut the plastic tabs that secure the ILP5 spacer from to the back case of the LYNX Touch. Remove the ILP5 receptacle knockout from the left side of the LYNX Touch back case. Install the ILP5 into the LYNX Touch control front case. Ensure that the connector board is properly seated into the receptacle on the control. Secure the ILP5 with the three provided screws. Insert the ILP5 receptacle and spacer into the slot on the back case. Secure the communications cable to the tie wrap point on the ILP5 with the provided tie wrap. Connect the Ethernet cable to the RJ45 receptacle. Enable the ILP5 and configure alarm reporting and module supervision and register the device. Refer to the “Program the Communications Module” and “Communications Diagnostics” sections. Alternate Installation (Refer to the Alternate Installation as shown on the figure below) 1. 2. 3. 4. 5. 6. Install the ILP5 into the LYNX Touch control front case. Ensure that the connector board is properly seated into the receptacle on the control. Secure the ILP5 with the three provided screws. Insert the ILP5 receptacle into the slot on the back case as shown on the figure below. Secure the communications cable to the tie wrap point on the ILP5 with the provided tie wrap. Connect the Ethernet cable to the RJ45 receptacle. Enable the ILP5 and configure alarm reporting and module supervision and register the device. Refer to the “Program the Communications Module” and “Communications “Diagnostics” sections. The communications module must be registered with AlarmNet before downloading or alarm reporting can take place. ETHERNET CABLE TO ILP5 RJ45 RECEPTACLE LYNX TOUCH ALTERNATE INSTALLATION REMOVE ILP5 KNOCKOUT REMOVE ILP5 SPACER ILP5 SPACER RJ45 RECEPTACLE CONNECTOR BOARD ROTATED 180 TIE WRAP (1) TIE WRAP POINT CONNECTOR BOARD SCREW (3) ILP5 RECEPTACLE LYNX TOUCH 5000-100-154-V0 - 11 - LYNX Touch Installation and Setup Guide Installing Wireless Zones General Information Zones The control supports up to 64 total wireless zones using 5800 Series transmitters, and wireless buttons. Range The built-in RF receiver can detect signals from wireless transmitters within a nominal range of 200 feet. Transmitters 5800 Series transmitters have built-in serial numbers that must be entered into the system using the “Zones” programming section, or input to the control via the downloader. 5800 Series transmitters (except the 5800RL) do not have DIP switches. Each transmitter's zone number is also programmed into the system in the “Zones” programming section. Some transmitters, such as the 5816 and 5817, can support more than one "zone" (referred to as loops or inputs). On the 5816, for example, the wire connection terminal block is loop 1; the reed contact is loop 2. Each loop must be assigned a different zone number. For button transmitters (RF "keys") such as the 5804, you must assign a unique zone number to each individual button used on the transmitter. Each button on the transmitter also has a pre-designated loop or input number, which is automatically displayed. UL The 5816 and 5817 Transmitters do not have EOL supervision of their loop wiring, which must not exceed 3 feet. The 5800RL, 5802MN, 5802MN2, 5804, 5804BD, 5804BDV, 5804E, 5814, 5816TEMP, 5819, 5819S(WHS & BRS), 5828/5828V and 5850(GBD) transmitters have not been evaluated by UL. House Identification If you are using a 5804BD/5804BDV Wireless Keypad with the system, you must program a House ID Code (01–31) as described in the “SYSTEM TYPE” programming section to establish proper communication, and the keypad must be set to the same ID. House ID 00 disables all wireless keypads. An RF House ID is not necessary for other 5800 Series transmitters; the entry should be left at “00” (default) in those cases. Transmitter Supervision With the exception of some transmitters/keypads that may be carried off-premises (5804, 5804BD, 5804BDV, 5804E and 5805-6), each transmitter is supervised by a check-in signal that is sent to the receiver at 70–90 minute intervals. If at least one check-in is not received from each supervised transmitter within a 12-hour period, the "missing" transmitter zone number(s) and "Supervision" will be displayed. The supervision for a particular transmitter in the system that may also be carried off the premises (5802/5802MN2, 5802MN) may be turned off by entering it as a Unsupervised RF (UR) type, as described in the “ZONES” programming section. 5800 Series transmitters have built-in tamper protection and will annunciate as a fault condition if covers are removed. Transmitter Input Types Each of the transmitters has one or more unique factory-assigned input (loop) ID codes. Each of the inputs requires a programming zone (e.g., a 5804's four inputs require four button zones). Transmitters can be entered as one of the following types (see transmitter’s instructions for appropriate input type): Type Supervised RF ("RF") Unsupervised RF ("UR") Unsupervised Button RF ("BR") Description Sends periodic check-in signals, as well as fault, restore, and low battery signals. The transmitter must remain within the receiver's range. Sends all the signals that the "RF" type does, but the control does not supervise the check-in signals. The transmitter may therefore be carried off-premises. Sends only fault signals. They do not send low battery signals until they are activated. The transmitter may be carried off-premises. Transmitter Battery Life • Batteries in the wireless transmitters may last from 4–7 years, depending on the environment, usage, and the specific wireless device being used. Factors such as humidity, high or low temperatures, as well as large swings in temperature may all reduce the actual battery life in a given installation. The wireless system can identify a true low battery situation, thus allowing the dealer or user of the system time to arrange a change of battery and maintain protection for that point within the system. • Button-type transmitters should be periodically tested for battery life. The 5802MN, 5802MN2, 5804, 5804BD, 5804BDV, and 5804E button transmitters have replaceable batteries. - 12 - LYNX Touch Installation and Setup Guide Installing Wireless Zones RF Sniffer Test Mode This mode is used after all transmitters have been entered to check that all transmitters have been properly programmed. Sniffer mode does not automatically expire. You must manually exit Sniffer mode by selecting Off and entering the Installer Code to return to normal operation. SCREEN ACTION Test 5000-100-096-V0 RF Sniffer Test 5000-100-102-V0 Notes: (1) (2) (3) (4) 1. At the Tools Screen, select “Test”. The following options are displayed. Walk Test RF Sniffer Test Go-No-Go Test Dialer Test 2. Select “RF Sniffer Test” from the options. Note: If the communicator is in the process of sending a report to the central station, the system will not go into the Sniffer mode. If so, wait a few minutes and try again. 3. The system displays all programmed zone numbers and zone descriptors, which have a non-zero Zone Type. Fault each transmitter in turn, causing each one to send a signal. As the system receives a signal from each of the transmitters, the zone number of that transmitter disappears from the display. The transmitters may be checked upon installation, or in an installed system. The system will beep once every 30-40 seconds while the RF Sniffer Test mode is active. 4. When all transmitters have been checked, Exit RF Sniffer Test mode by depressing the Off key and entering the Installer or a User Code. All button-type (BR) units must physically be activated to clear the display, since they do not automatically send check-in signals. When one button of a button type, supervised or unsupervised RF transmitter (RF, UR, or BR) is activated, all zones assigned to other buttons on that transmitter are cleared. This also applies to 5816 and 5817 transmitters that have multiple loops (zones). Any transmitter that is not “entered” will not turn off its zone number. For SIA installations, the following devices may be used as specified for panic (24-hour) alarm response: • wireless keys which have two-button panic pairs available (e.g., 5804BDV), on which only the two-button panic pairs may be programmed for any 24-hour alarm response • wireless keypads (e.g., 5828/5828V) keypads that have a two-second delay on the special function keys, or two-button panic pairs • built-in keypad panic key Go/No Go Test Mode Conducting this test with your hand wrapped around the transmitter will cause inaccurate results. On button type transmitters that have been programmed to set ARM AWAY, ARM STAY, or DISARM, pressing a button will take the system out of the Go/No Go Test mode causing the programmed action to occur. The Go/No Go tests will verify adequate RF signal strength from the proposed transmitter location, and allow you to reorient or relocate transmitters if necessary, before mounting the transmitters permanently. This mode is similar to the transmitter Test mode, except that the wireless receiver gain is reduced. This will enable you to make sure that the RF signal from each transmitter is received with sufficient signal amplitude when the system is in the normal operating mode. SCREEN ACTION 1. At the Tools Screen, select “Test”. The following options are displayed. Test 5000-100-096-V0 2. 3. Go-No-Go Test 5000-100-103-V0 4. 5. 6. Walk Test RF Sniffer Test Go-No-Go Test Dialer Test Select “Go-No-Go Test”. Once you have placed transmitters in their desired locations, and the approximate length of wire to be run to sensors is connected to the transmitter's screw terminals (if used), fault each transmitter. a. The keypad beeps three times indicating signal reception, displays the appropriate zone number and announced the zone description. b. If the keypad does not beep, reorient or move the transmitter to another location. Usually a few inches in either direction is all that is required. If each transmitter produces the proper keypad response when faulted, they can be permanently mounted according to their respective instructions. The system will beep once every 30-40 seconds while the Go-No-Go Test mode is active. Exit Go-No-Go Test mode by depressing the Off key and entering the Installer or a User Code. - 13 - LYNX Touch Installation and Setup Guide Installing Wireless Zones 5800 Series Transmitter Loop Numbers (Refer to this information when programming transmitters) The following illustration shows the compatible transmitters, their associated input types and loop designations. LOOP LOOP 1 LOOP LOOP 1 (LOW SENSITIVITY LOOP 1 (LOW SENSITIVITY LOOP 2 (HIGH SENSITIVITY) LOOP 2 (HIGH SENSITIVITY) LOOP 3 (TEMP) LOOP 3 (TEMP) LOOP 4 (TAMPER) LOOP 4 (TAMPER) 5800CO ENROLL AS "RF" 5800Micra ENROLL AS "RF" 5800PIR-RES ENROLL AS "RF" 5800PIR/ 5800PIR-COM ENROLL AS "RF" 5800RL SET HOUSE ID 5800PIR-OD ENROLL AS "RF" LOOP 3 ON LOOP 4 5800SS1 E N RO L L A S " R F " 5 8 0 0 WAV E P RO G R A M HOUSE ID SERIAL #1 LOOP 3 ON LOOP 1 5804/5804E ENROLL AS "BR" 5802MN2 ENROLL AS "UR" OR "RF" 5802MN ENROLL AS "UR" OR "RF" LOOP 1 • •• ••• ••• • • • •• 5 8 0 4 B D / 5 8 0 4 B DV ENROLL AS "BR" PROGRAM HOUSE ID SERIAL #1 LOOP 2 OF LOOP 2 (REED) SERIAL #1 LOOP 1 SERIAL #2 LOOP 3 LOOP 1 LOOP 1 LOOP 1 SERIAL #2 LOOP 2 5806/5806W3/5807 5808/5808LST/5808W3 ENROLL AS "RF" 5809 ENROLL AS "RF" 5811 ENROLL AS "RF" LOOP 1 (PRIMARY) LOOP 2 (REED) LOOP 1 (TERMINALS) LOOP 3 (AUX. RIGHT) 5817 ENROLL AS "RF" LOOP 1 (TERMINALS) 5819 ENROLL AS "RF" 5818 ENROLL AS "RF" SERIAL #2 LOOP 3 MIC LOOPS 1-3 MESSA LOOP 1 LOOP 2 (STANDARD SECURITY) SERIAL #1 LOOP 1 SERIAL #2 LOOP 2 5828/5828V P RO G R A M HOUSE ID LOOP 1 LOOP 1 (INTERNAL SHOCK SENSOR 5819S (WHS & BRS) ENROLL AS "RF" LOOP 1 (HIGH SECURITY) SERIAL #2 LOOP 4 GE SERIAL #1 LOOP 4 5821 ENROLL AS "RF" LOOP 2 (REED) SERIAL #1 LOOP 2 AR AD 5816 ENROLL AS "RF" 5820L ENROLL AS "RF" SERIAL #2 LOOP 1 SERIAL #1 LOOP 3 ME 5814 ENROLL AS "RF" LOOP 3 (TERMINALS) LOOP 3 (TERMINALS) LOOP 1 5816TEMP ENROLL AS "RF" 5816MN ENROLL AS "RF" LOOP 2 (REED) LOOP 2 (AUX. CENTER) LOOP 1 (TEMP SENSOR) ALTERNATE POSITION FOR LOOP 2 RE LOOP 1 (TERMINALS) LOOP 1 SERIAL #2 - LOOP 1 = ON + 4 BUTTONS LOOP 4 = 3 + 4 BUTTONS 5805-6 ENROLL AS "BR" 5834-4 ENROLL AS "BR" LOOP 3 (TILT MODE) 5853 ENROLL AS "RF" LOOP 1 (MOTION) 5870API ENROLL AS "RF" LOOP 4 (TAMPER) SERIAL #1 LOOP 3 AW AY SERIAL #1 LOOP 4 ST AY SERIAL #2 LOOP 3 SERIAL #1 LOOP 2 SERIAL #1 LOOP 1 SERIAL #2 LOOP 2 5878 ENROLL AS "BR" LOOP 1 (LOW SENSITIVITY) LOOP 1 5890/5890PI ENROLL AS "RF" LOOP 4 LOOP 5894PI ENROLL AS "RF" LOOP 2 (HIGH SENSITIVITY) LOOP 1 5897 ENROLL AS "RF" 5898 ENROLL AS "RF" 5800-002-V0 SERIAL #1 LOOP 4 LOOP 1 LOOP LOOP 2 LOOP 2 LOOP 1 •• • •• LOOP OFF Notes: (1) The 5806W3 smoke detector must be used in SIA applications. (2) Button type (BR) devices send only fault and low battery signals; no restore or check-in signals. Supervised RF (RF) devices send periodic check-in signals, faults, restore and low battery signals. Unsupervised RF (UR) devices send periodic check-in signals, faults, restore and low battery signals but the control does not supervise the check-in signals. (3) If an external sounder is required, the 5800WAVE should be used. UL The 5800RL, 5802MN, 5802MN2, 5804, 5804BD, 5804BDV, 5814, 5816TEMP, 5819, 5819S(WHS & BRS), and 5828/5828V wireless transmitters have not been evaluated by UL. - 14 - LYNX Touch Installation and Setup Guide Mechanics of Programming Navigating Menus Touch-screen Display LYNX Touch’s Liquid Crystal Display (LCD) touch-screen displays variable icons and text on “screens”. The screen displays status icons and associated text, the current time, system status information and menu choices. The Menu area includes a list of commands, or choices that apply to the current selection. The status area provides information about various system events and a colored bar also provides an indication of system status. A “Home Screen” is displayed whenever power is applied to the system. In addition the green “READY” LED is lit when the system is ready or flashes when it is not. SYSTEM STATUS Ready To Arm SYSTEM/ZONE STATUS Zones Arm Away Delay LEDs Arm Stay Message 10:18 AM June 8, 2010 ARMED System Phone More READY FUNCTION KEYS 5000-100-054-V0 Home Screen (page 1) Navigation Keys Navigating through the screens is accomplished by lightly touching the menu item on the touch-screen. Once activated, the control will take you to the next screen. Selecting the “Home” (cancel) key or the “2” Key will return you to the previous screen at any time unless System Programming mode is active. By Touching (selecting) an icon or key the system, depending on the function, advances to another screen, toggles between options or scrolls through multiple options that can be selected. The system provides a prompt when a specific input is required. Note: You may find it convenient to adjust the volume setting before entering the Program Mode. This will allow you to clearly hear the feedback announcements or system beeps from the system’s built-in speaker. To adjust the volume, select “More” on the “home Screen” and then select “Settings”. Adjust the volume using the slide displayed on the Settings screen and then select “Save” to accept. Upon exiting the Program Mode, the system resets the volume to the default value (mid level). Menu Screens System Status is displayed at the top of each screen. The time and date are displayed at the bottom of the Home Screen. The Home Screen consists of two pages. The first page displays the system status and eight selection “buttons” and “tabs”. Selection Zones System Arm Away Arm Stay Message Phone Delay/Instant More Function Provides access to Zone information and options. Provides information about system status Used to Arm the system in Away mode (displayed on both Home Screen pages). Used to Arm the system in Stay mode (displayed on both Home Screen pages). Provides access to Message Center. Provides access to Speaker Phone mode. (if programmed) Used to toggle between exit delay and instant arming options (displayed on Home Screen pages). Advances system to second page of the Home Screen. - 15 - LYNX Touch Installation and Setup Guide Mechanics of Programming The second page also displays the system status in and six selection “buttons” and “tabs”. Selection Tools Arm Away Arm Stay Settings Delay/Instant Back Function Provides access to Installer and User Programming Menus (Master User Code required for access). Used to Arm the system in Away mode (displayed on both Home Screen pages). Used to Arm the system in Stay mode (displayed on both Home Screen pages). Provides access to various keypad functions (i.e.; Brightness, Contrast, Volume, Voice, Chime & Ringer). Used to toggle between exit delay and instant arming options (displayed on both Home Screen pages). Returns system to first page of the Home Screen. Installer Tools Menu The Tools/Installer Menu provides access to the Installer configurable features and displays six options. Entering the Installer Code is required to access the Installer Menu. Ready To Arm Program Test Devices Events Initiate Download Schedules 5000-100-043-V0 Installer Menu Page User Tools Menu The User Menu provides access to the User configurable features and displays eight options. Entering the Master User Code is required to access the User Menu. Ready To Arm Users Devices Schedules Test Date Time Events Reminders Slide Show Back 5000-100-070-V0 User Menu Page General Programming Information When power cycling the control, remove AC power first and wait approximately 1 minute before disconnecting battery. Programming options are stored in non-removable, electrically erasable, nonvolatile EEROM memory. The system can be programmed at any time, even at the installer's premises prior to the actual installation. Simply apply power temporarily to the Control and then program the unit as desired. The system can also be programmed remotely, using an IBM PC compatible Personal Computer, and Compass Downloader and modem or via capable GSM or IP communications modules. See the Remote Programming/Control (Downloading) section. - 16 - LYNX Touch Installation and Setup Guide Mechanics of Programming Programming If the system is Armed or in Alarm, the Tools icon will not be functional. The system must first be disarmed. To enter Installer Programming Mode: SCREEN ACTION Ready To Arm Zones Arm Away Arm Stay Message System At the Home Screen select “More”. Select “Tools”. The system displays a virtual keypad. Enter the Installer Code 4112. The System Programming Screen is displayed. Select “Program” to display the following options: Installer Code Date Time Zones Keys Phone 10:18 AM June 8, 2010 Delay 1. 2. 3. 4. More 5000-100-006-V0 System Type Communications Comm. Diagnostics Reporter Use the down T arrow to scroll to the next page of options. Sounder Default Config. 5. System Settings Selecting an option advances to that Programming screen. Loading Factory Defaults To load the factory defaults, enter the Installer Programming Mode and advance to second page of the System Programming and refer to following procedure. Refer to the Programming Default Tables section of this manual to view the Default Tables. If a default table is loaded, any data that has already been programmed into the system will be changed according to the default table selected! To Select a Default Configuration SCREEN ACTION 1. Select “Default Configuration” to display the following options: System Programming... Sounder System Settings Default Config. 5000-100-035-V0 Default Config 2 Default Config 1 Default Config 4 Default Config 3 Default Downloader Note: For a list of the pre-programmed defaults refer to the Default Tables section. 2. Select the desired Default Configuration. 3. A Confirmation screen is displayed. 4. If “Yes” is selected, the System beeps three times and returns to the Default option screen. 5. If “No” is selected, the System returns to the Default option screen. Exiting Program Mode 1. Select the “2” key to exit the current screen. The system returns to the previous screen. 2. Select the “2” key as required until system displays a Confirmation screen. 3. Select “Yes” to allow the installer to re-enter Programming mode or “No” to prevent re-entry. If “No” is selected, you can still re-enter Program Mode by powering down the unit (remove AC and battery power) and entering Program Mode within 30 seconds of powering up. 4. Select the “2” key again to return to the Home Screen. - 17 - LYNX Touch Installation and Setup Guide Zone Response Type Definitions General Information During programming, you must assign a zone type to each zone, which defines the way in which the system responds to faults in that zone. Zone types are defined below. Type Function Characteristics • • • • • Not Used Entry/Exit 1 (Burglary) Used to program a zone that is not used. Usually assigned to sensors or contacts on primary entry and exit doors. Entry/Exit 2 (Burglary) Usually assigned to sensors or contacts on secondary entry and exit doors that might be further from the keypad (typically used for a garage, loading dock, or basement door). Perimeter (Burglary) Interior, Follower 24-hour Silent Alarm Usually assigned to all sensors or contacts on exterior doors and windows Usually assigned to a zone covering an entry area (i.e.: foyer, lobby, or hallway) that one must pass upon entry (after faulting the entry/exit zone) to reach the keypad. It provides an instant alarm if the entry/exit zone is not violated first, and protects an area in the event an intruder has hidden on the premises before the system is armed, or gains access to the premises through an unprotected area. Usually assigned to a zone that covers a sensitive area (i.e.: stock room, drug supply room, etc.) It can also be used on a sensor or contact in an area where immediate notification of an entry is desired. Usually assigned to a zone containing an Emergency button (silent emergency). 24-hour Audible Alarm Usually assigned to a zone containing an Emergency button (audible emergency). 24-hour Auxiliary Alarm Usually assigned to a zone containing a button for use in personal emergencies or to a zone containing monitoring devices (i.e.: water or temperature sensors, etc.). Can be assigned to any wireless zone used as a fire zone. This zone type is always active and cannot be bypassed. Bypassed when the panel is armed in the STAY or STAY INSTANT mode. Trouble by Day/ Alarm by Night Fire No Verification Interior with Delay Monitor Can be assigned to any wireless zone used for asset protection. Works as a dynamic monitor of a zone fault/trouble (not alarm). 24-hour Carbon Monoxide Monitor Can be assigned to any wireless zone with a carbon monoxide detector. This zone type is always active and cannot be bypassed. - 18 - • • • • • • • • • • • None Entry delay #1 is programmable. Exit delay is independently programmable. Exit and entry delays when armed in AWAY or STAY mode. No entry delay when armed in STAY INSTANT or AWAY INSTANT mode. Exit delay regardless of the arming mode selected. Entry delay #2 is programmable. Exit delay is independently programmable. Secondary entry delay, if armed in the AWAY or STAY mode. No entry delay when armed in the STAY INSTANT or AWAY INSTANT mode. Exit delay begins regardless of the arming mode selected. Instant alarm, when armed in AWAY, STAY, STAY NO DELAY, or AWAY INSTANT mode. Delayed alarm (using the programmed entry/exit time) if entry/exit (types 01 or 02) or interior-with-delay (type 10) zone is faulted first. Instant alarm in all other situations. Active when armed in AWAY or AWAY INSTANT mode. Bypassed automatically when armed in STAY or STAY INSTANT mode. • Instant alarm, when armed in AWAY, STAY, STAY INSTANT, or AWAY INSTANT (night) mode. • Provides a latched trouble sounding from the keypad and, if desired, a central station report when disarmed (day). • Sends a report to the central station but provides no keypad display or sounding. • In disarmed state sends a report to the central station displays "Not Ready to Arm" on the keypad and “AWAY”, “STAY” and “TOOLS” buttons are disabled. • Follows sounder timeout • Sends a report to the central station, and provides alarm sounds at the keypad. • Sends a report to the central station and provides an alarm sound at the keypad. (There is no keypad timeout.) • Alarm sound will pulse when this zone type is alarmed. • Entry delay #1 (with programmed entry time) when armed in the AWAY mode. • Entry delay begins whenever sensors in this zone are violated, regardless of whether an entry/exit delay zone was tripped first. • No entry delay when armed in the AWAY INSTANT mode. • Exit delay regardless of the arming mode selected. • No reports to the central station. • Fault/restore events are logged by the system. • Activity Zone No. and Zone Descriptor displayed on LCD. • Restore will be stored in event log. • No keypad sounding or chime • System can still be armed • Local keypad and detector will sound when this zone type is alarmed. (Pulse Temporal 4) LYNX Touch Installation and Setup Guide Zone Response Type Definitions Function Characteristics Fire with Verification Type Can be assigned to any wireless zone used as a fire zone. Fire with verification is available with smoke detector device type. It can not be used with heat detectors, combination heat/smoke detectors, wireless sensors or fire pull stations. This zone type is always active and cannot be bypassed. Arm–Stay Special-purpose zone type used with 5800 Series wireless pushbutton units. Arm–Away Special-purpose zone type used with 5800 Series wireless pushbutton units. • Alarm sound will pulse when this zone type is alarmed. Only after the alarm has been verified. • System verifies alarm by delaying reporting and control panel alarm sounding for 30 seconds after alarm is detected. If the zone remains faulted after 30 seconds a fire alarm is provided. If any other fire zone is faulted during the 30 second delay window a fire alarm is immediately provided for that zone. An alarm for original fire zone will also be provided if that zone is still faulted afterward. If there are no fire alarms after the 30 second delay expires, the system will open a 60 second window. If any fire zone is faulted during that window a fire alarm will immediately be provided for that zone. • Exit delay regardless of the arming mode selected. • System is armed in the STAY mode when the zone is activated. • System is armed in the AWAY mode when the zone is activated. Disarm Special-purpose zone type used with 5800 Series wireless pushbutton units. Assigned when no-alarm response is required No Alarm Response Silent Burglary Usually assigned to sensors or contacts on exterior doors and windows where sirens are NOT desired. General Monitor Assigned sensors or contacts on doors and windows or asset protection within the premises. Used to track activity of the occupant and alert occupant of the activity of others. General Response Assigned sensors or contacts on doors and windows or asset protection within the premises. Used to track activity of the occupant and alert occupant of the activity of others. • Disarms the system when the zone is activated. • • • • • • • • • • • • • • • • • Resident Monitor Used to monitor a resident in an area deemed to be dangerous by a caregiver. • • • • • Resident Response Used to monitor a resident in an area deemed to be dangerous by a caregiver. Requires acknowledgement by caregiver. • • • • • • • • - 19 - No reports to the central station. Activity Zone No. and Zone Descriptor displayed on LCD. No keypad sounding or chime System can still be armed No display on the screen Instant alarm, with NO audible indication when is armed in the AWAY, STAY, STAY NO DELAY, or AWAY INSTANT mode. Report sent to the central station. No reports to the central station. Fault/restore events are logged by the system. Monitors entry into a monitored area. Activates a one-time unique chime sound and announcement when faulted. Activity Zone No. and Zone Descriptor displayed on LCD. Restore will be stored in event log. No reports to the central station. Fault/restore events are logged by the system. Monitors entry into a monitored area. Activates a unique chime sound and zone announcement when faulted. Activity Zone No. and Zone Descriptor displayed on LCD. System re-triggers audible sounding every ten seconds until acknowledged (Off sequence or wireless key button). No reports to the central station. Monitors entry into a monitored area. Activates a unique chime sound and zone announcement when faulted. Activity Zone No. and Zone Descriptor displayed on LCD. If programmed, triggers a voice message (follow me) report. If triggered by a PIR, the system remains latched until another Monitor or Response zone has been tripped or a specified time interval has elapsed. Fault/Restore events are not logged by the system. No reports to the central station. Monitors entry into a monitored area. Activates a unique chime sound and zone announcement when faulted. Activity Zone No. and Zone Descriptor displayed on LCD. If programmed, triggers a voice message (follow me) report. If triggered by a PIR, the system remains latched until another Monitor or Response zone has been tripped or a specified time interval has elapsed. System re-triggers audible sounding every ten seconds until acknowledged (Off sequence or wireless key button). Fault/Restore events are not logged by the system LYNX Touch Installation and Setup Guide Programming the Control After entering the System Programming mode select from the options provided on the First and Second Installer Programming screens as shown in the accompanying figure. System Programming... System Programming... Installer Code System Type Sounder Date Time Communicator Default Config. Zones Comm. Diagonostics Keys Reporter System Settings Save 5000-100-035-V0 5000-100-013-V0 Page 1 Page 2 Change Installer Code The factory default Installer Code for the LYNX Touch Control is set to 4-1-1-2. SCREEN ACTION Installer Code 1. Select “Installer Code”. 2. Enter a new four-digit Installer Code on the displayed keypad The system will display the new code on the left side of the screen. Select “Done” when you are finished. The system returns to the “System Programming” Screen. 5000-100-129-V0 3. 4. - 20 - LYNX Touch Installation and Setup Guide Programming the Control System Type The following system options are programmed in this section: Option RF Jam Speaker Phone Two Way Voice RF House Code Phone Notification Phone Detect Time Remote Phone Events Non-Security Remote Access Serial Multi Mode Serial Function Enable or disable RF Jam Log and Reporting Enable or disable Speaker Phone mode. (End User feature) Enable or disable Two Way Voice communication with the Central Station. Set RF House Code. (Bi-directional RF Devices) Enable or disable Phone Notification mode. (Phone Line-cut) Select a delay period between phone line-cut & system response (allows phone to restore) Enable or disable Remote Phone Control mode. (End User feature) Enable or disable multiple options for event logging (i.e.; alarms, troubles, open/close) Enable or disable non-security event logging Enable or disable end user to access their system via a website Enable or disable transmission of panel status events via email (Active only when Remote Access Serial is enabled) Note: If applicable, preprogrammed defaults for the LYNX Touch Control are shown on the screen unless otherwise noted. Screen ACTION System Type 5000-100-130-V0 System Type Note: If applicable, the pre-programmed default will be displayed beneath the option. 1. Select “System Type” from the following options: RF Jam Speaker Phone Two Way Voice RF House Code Phone Notification Remote Phone Phone Detect Time Use the down T arrow to scroll to the next page of options. Events – Log All Events – Log Alarm Events – Log Bypass Events – Log Open/Close Events – Log Trouble Non-Security Remote Access Serial Multi Mode Serial Speaker Phone Enabled Two Way Voice Disabled RF House Code Phone Notification Disabled Phone Detect Time 2 Minutes 3. Select “Speaker Phone”. The System toggles between the following: Disabled Enabled 4. Select “Two-Way Voice” .The System toggles between the following: Disabled Enabled 5. Select “RF House Code”. 6. After entering a code (00-31) on the displayed keypad, select “Done”. 7. Select “Phone Notification” (phone line cut). The System scrolls between the following options: Disabled Keypad Trouble If “Keypad” or “Trouble is selected proceed to Step 8. 8. If Keypad or Trouble was selected in Step 7, the “Phone Detect Time” option is displayed. Select “Phone Detect Time”. The system scrolls between the following options: 1 Minute 2 Minutes 3 Minutes 4 Minutes - 21 - LYNX Touch Installation and Setup Guide Programming the Control Screen Remote Phone Enabled Events - Log All Press To Log All Events – Log Alarm Enabled ACTION 9. Select “Remote Phone”. The System toggles between the following options: Disabled Enabled Use the down T arrow to scroll to the next page of options. 10. Select “Events - Log All”. The system displays “Press To Log All”. Selecting this option programs the system to log all events and “Log All Set” is displayed. Additionally all of the options listed below are enabled. Events – Log Alarm Events – Log Bypass Events – Log Open/Close Events – Log Trouble Non-Security OR Proceed to step 11 and select the options individually. 11. Select “Events – Log Alarm”. The System toggles between “Enabled” and “Disabled. 12. Select “Events – Log Bypass”. The System toggles between “Enabled” and “Disabled”. 13. Select “Events – Log Open/Close”. The System toggles between “Enabled” and “Disabled”. 14. Select “Events – Log Trouble”. The System toggles between “Enabled” and “Disabled”. Remote Access Serial Disabled Non Security 15. Select “Remote Access Serial”. The System toggles between “Enabled” and “Disabled”. If the Remote Access Serial” option is enabled, the “Multi Mode Serial” option is displayed. 16. Select “Non Security”. The System toggles between “Enabled” and “Disabled”. Disabled Multi Mode Serial Disabled 17. Select “Multi Mode Serial”. The System toggles between “Enhanced Reports” and “Disabled”. 18. Select “Save” when complete. - 22 - LYNX Touch Installation and Setup Guide Programming the Control Program Date and Time Note: If applicable, preprogrammed defaults for the LYNX Touch Control are shown on the screen unless otherwise noted. SCREEN ACTION Note: If you are installing a GSMVLP5 or ILP5 Communication Module, the time and date will be programmed and updated automatically via Central Station. You must still program the correct Time Zone below. 1. Select “Date Time”. Date Time 5000-100-131-V0 System Programming... June SUN 2. Using the left W and right X arrows select the Month and Year then select the date. Select the T key to advance to the next screen. 3. To set the correct time, touch the “Clear” button. 4. Enter the correct time and then select AM or PM. Select the T key to advance to the next screen or select “Save” to return to the System Programming Screen. 2010 MON TUE WED THU FRI SAT 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 Save 5000-100-016-V0 System Programming Enter Time Clear 10:21 AM AM / PM Save 5000-100-010-V0 Time Zone Eastern (EST) Day Light Savings Time Yes Start Month March Start Week Second End Month November End Week First 6. Select “Time Zone”. The system scrolls between the following options: Eastern (EST) Mountain (MST) Central (CST) Pacific (PST) Hawaii (HAST) Alaska (AKST) 6. Select “Day Light Savings Time”. The system toggles between “Yes” and “No”. If “Yes” is selected the following options will become active. 7. Select “Start Month”. The system displays the following options. January February March April May June July August Use the down T arrow to scroll to the next page of options. September October November December 8. Select “Start Week”. The system scrolls between the following options. First Fourth 3rd from Last Second Last Third Next to Last 9. Select “End Month”. The system displays the following options. January February March April May June July August Use the down T arrow to scroll to the next page of options. September October November December 10. Select “End Week”. The system will scrolls through the available weeks. First Fourth 3rd from Last Second Last Third Next to Last 11. After programming these options, select the “Save” key. - 23 - LYNX Touch Installation and Setup Guide Programming the Control Program the Communications Module The following system options are programmed in this section: Option Communications Path Primary City Id Primary Central Station Id Primary Subscriber Id Supervision Old Alarm Time Remote Acc. IP or GSM Multi Mode IP or GSM IP Fault Time Use DHCP NIC IP Address Subnet Mask Gateway IP Address DNS Server IP Address GSM Fault Time GSM Rollover GSM 24 Hour Test Function Selects type of Communications Module Enter Central Station Primary City ID Enter Primary Central Station ID Enter Central Station Primary Subscriber ID Selects how often the Communications Module sends a supervisory message to the Central Station. Selects how long an undeliverable alarm delivery is retried to the Central Station. Enables or disables user remote access via internet and/or GSM. (appears only if Remote Access IP or GSM is enabled.) Enables or disables multi mode feature. (Appears only if IP is enabled in Communications Path field.) Selects time delay before the Communications Module notifies the control panel of a loss of contact with the internet. Dynamically selects the IP addresses (Appears only if “No” is selected in Use DHCP field.) Enter NIC IP Address. (Appears only if “No” is selected in Use DHCP field.) Enter Subnet Address. (Appears only if “No” is selected in Use DHCP field.) Enter Gateway IP Address (Appears only if “No” is selected in Use DHCP field.) Enter Domain Name Server IP Address. (Appears only if GSM is enabled in Communications Path field.) Selects time delay before the Communications Module notifies the control panel of a loss of contact with the network. Allows messages to be sent over GSM in the event that contact with the internet is lost. Enables daily test of GSM module operation. Note: If applicable, preprogrammed defaults for the LYNX Touch Control are shown on the screen unless otherwise noted. Remote Access (Total Connect) and Multi Mode (PSD) over IP or GSM cannot be enabled in the panel alone. Availability of this service is controlled via the web-based programming tool on the AlarmNet Direct website. These features must to be enabled through the AlarmNet Direct website first and transferred to the device. SCREEN ACTION Communicator 5000-100-132-V0 Communicator 1. Select “Communicator” The System displays the following options: Communications Path Primary City Id Pri Central Station Id Primary Subscriber Id Supervision Old Alarm Time Remote Acc. IP or GSM Multi Mode IP or GSM Use the down T arrow to scroll to the next page of options. GSM Fault Time OR IP Fault Time 2. Select “Communications Path”. The system scrolls between the following options: None IP GSM Primary City Id 3. Select “Primary City Id”. Enter the 2-digit Primary City ID (Decimal). Options 01-99 Pri Central Station Id 4. Select “Pri Central Station Id”. Enter the 2-digit Primary Central Station ID (HEX). Options 01-FE Primary Subscriber Id 5. Select “Primary Subscriber Id”. Enter the 4-digit Subscriber Account Number (Decimal). Options 0001-9999 Communications Path None - 24 - LYNX Touch Installation and Setup Guide Programming the Control SCREEN Supervision ACTION 6. Select “Supervision”. The system scrolls between the following options: 24 Hours None 30 Days 7. Select “Old Alarm Time”. The system scrolls between the following options: 10 Minutes 15 Minutes 30 Minutes 1 Hour 2 Hours 4 Hours 8 Hours 12 Hours Use the down T arrow to scroll to the next page of options. 24 Hours 8. Select “Remote Acc. IP or GSM”. The system toggles between “Disabled” and “Enabled”. 24 Hours Old Alarm Time 10 Minutes Remote Acc. IP or GSM Disabled Multi Mode IP or GSM Disabled IP Fault Time 00 Use DHCP Yes NIC IP Address 9. If “Remote Access IP or GSM” was enabled in the previous step, the “Multi Mode IP or GSM” option is displayed. The system scrolls between the following options. Disabled Relay Reports Enhanced Reports 10. Use the down T arrow to scroll to the next page of options. If IP or IP & GSM was selected in step 2, proceed to step 11. If GSM was selected in step 2, proceed to step 19. 11. Select “IP Fault Time”. Enter the time delay (in minutes) on the displayed keypad. Options 00-99 13. Select “Use DHCP”. The system toggles between “Yes” and “No”. If “No” is selected the system displays four additional options. If “Yes” is selected, skip to step 18. 14. Select “NIC IP Address”. Enter the 4-part address on the displayed keypad. 255.255.255.255 Subnet Mask 15. Select “Subnet Mask”. Enter the 4-part address on the displayed keypad. 255.255.255.255 Gateway IP Address 16. Select “Gateway IP Address”. Enter the 4-part address on the displayed keypad. 255.255.255.255 255.255.255.255 17. Select “DNS Server IP Address”. Enter the 4-part address on the displayed keypad. 18. If “IP” was selected in step 2, select “Save” and then select “OK” when the “Programming Done” screen appears. Proceed to “Diagnostics” section in order to register the device. GSM Fault Time 19. Select “GSM Fault Time”. Enter the time delay (in minutes) on the displayed keypad. DNS Server IP Address 00 Options 00-99 20. If “GSM” was selected in step 2, select “Save” and then select “OK” when the “Programming Done” screen appears. Proceed to “Diagnostics” section in order to register the device. - 25 - LYNX Touch Installation and Setup Guide Programming the Control Program Zones The following system options are programmed in this section: Option Serial Number Loop Number Zone Description 1/2 Device Type Response Type Alarm Report Chime Supervision Function Manually enter device serial number or enroll via RF transmission Manually enter device loop number or enroll via RF transmission Enter Zone Descriptors for the device being enrolled Select the type of device being enrolled Select the alarm response for the device being enrolled (refer to Zone Response Type Table) Activate reporting option for the device being enrolled Enable/disable chime mode for specific device being enrolled (applies to Entry/ Exit, Perimeter, and Interior Response types only) Select supervision for device being enrolled Note: If applicable, preprogrammed defaults for the LYNX Touch Control are shown on the screen unless otherwise noted. SCREEN ACTION Zones 5000-100-133-V0 Serial Number Loop Number Zone Description 1 1. Select “Zones” The System displays the following options: 1. New 2. Front Door 3. Back Door 4.Window 5. Motion Sensor 6.New 2. Use the down T arrow to scroll to the next page of options. Use the S arrow to return to the previous page. 7. – 48. New 49. – 56. 4 Button 57. – 64. New 95. Fire 96. Medical 99. Police 3. Select a zone and then select “Edit” or “Add New” to program the next available zone. The following options are displayed (dependant upon Zone Type): Serial Number Loop Number Zone Description 1 Zone Description 2 Device Type Response Type Alarm Report Chime Supervision 4. Select an option to display the next programming field. Serial Number When “Serial Number” has been selected “Enter Serial Number or Activate” is displayed. The transmitter serial number and loop number can be enrolled via RF transmission OR manually. Enroll via RF Learning To enroll the device using RF Learning mode three transmissions (open/close) of the device will be required. The initial transmission activates the RF Learning mode and the system will emit a single beep. A second transmission enrolls the serial number and the system beeps two times and displays “Activate Sensor Again To Confirm”. A third transmission will confirm the serial number. The system beeps two times and returns to the Zone programming Screen. Enroll Manually Enter the 7-digit serial number printed on the transmitter using the displayed keypad and select “Done”. The system beeps one time and returns to the Zone programming Screen. Loop Number Select “Loop Number” to toggle between 1, 2, 3 and 4. Enter Save. Zone Description 1 Select “Zone Description 1”. Using the displayed keypad enter Zone Description 1. The system announces the Zone Description. Enter “Done”, when you are finished. The system returns to the Zone Programming page. Zone Description 2 Select “Zone Description 2”. Using the displayed keypad enter Zone Description 2. The system announces the Zone Description. Enter “Done”, when you are finished. The system returns to the Zone Programming page. - 26 - LYNX Touch Installation and Setup Guide Programming the Control SCREEN ACTION Device Type Device Type Select “Device Type”. The system displays the following options (dependant upon the Zone): New Door Window Motion Sensor Glass Break Smoke Detector Heat Sensor Carbon Mono. Det. Use the down T arrow to scroll to the next page of options: Temperature Flood Environmental Medical Fire Police Other Response Type Response Type 1. Select “Response Type”. The system displays the following options (dependant upon the Zone): Not Used Entry Exit 1 Entry Exit 2 Perimeter Interior Follower Trouble Alarm 24 Hour Silent 24 Hour Audible 2. Use the down T arrow to scroll to the next page of options. Use the S arrow to return to the previous page. 24 Hour Auxiliary Fire No Verification Interior With Delay Monitor Carbon Monoxide Trouble Arm Stay Arm Away Not Used Disarm No Response Silent Burglary Resident Monitor Resident Response General Monitor General Response Fire With Verification 3. Select Response Type and select “Save”. The system will return to the Zone screen Alarm Report Yes Chime No Supervision Supervised Alarm Report Note: This field is for Alarms. If Response Type “Trouble” is set up and Alarm Report is set to “No” the system will still report if Report Alarms was enabled in the Reporter programming. Select “Report” to toggle between “No” or “Yes”. Select “Save”. Chime Note: Chime only applies to entry/exit, perimeter and interior zone types. Select “Chime” to toggle between “No” or “Yes”. Select “Save”. Supervision Select “Supervision” to scroll between the following options: Hardwire – Normally Open Hardwire – Normally Closed Hardwire – End of Line RF – Supervised RF – Unsupervised After making a Supervision selection, select “Save”. - 27 - LYNX Touch Installation and Setup Guide Programming the Control Program Keys The following system options are programmed in this section: Option Key Type User Serial Number Zone Button Key * - Zn * Function Select the specific type of key being entered or enrolled Associates the Key with a specific User Manually enter key serial number or enroll via RF transmission Manually enter key zone number (between 49 and 64) or enroll via RF transmission Associate the selected button with a specific function * Key number and Zn number are dependant upon the Key Type selected. Note: If applicable, preprogrammed defaults for the LYNX Touch Control are shown on the screen unless otherwise noted. SCREEN Keys Key Type 4 Button key User ACTION 1. Select “Keys” The System displays the following options: Edit Add New Delete 2. Select “Add New”. 3. The following options are displayed (dependant upon the “Key Type” selected): Key Type User Serial Number Zone Button Key 1 – Zn 49 Button Key 2 – Zn 50 Button Key 3 – Zn 51 Button Key 4 – Zn 52 Button Key 5 – Zn 53 Button Key 6 – Zn 54 Button Key 7 – Zn 55 Button Key 8 – Zn 56 4. Select an option to display the next programming field. Key Type Select “Key Type”. The system scrolls between the following: 1 Button key 6 Button key 2 Button key 8 Button key 4 Button key User 4. Select “User” then select from the following options (or the list of Users that have been programmed): Master Babysitter Duress User 3 User 4 User 5 User 6 User 7 Use the down T arrow to scroll to the next page. The system displays options for User 8 through 14. Note: The Key must be associated with a specific User/User Code in order for it to operate. Refer to the LYNX Touch User Guide for additional Information regarding User Codes. Serial Number Serial Number When “Serial Number” has been selected “Enter Serial Number or Activate” is displayed. The transmitter serial number and loop number can be enrolled via RF transmission OR manually. Enroll via RF Learning To enroll the device using RF Learning mode three transmissions (open/close) of the device will be required. The initial transmission activates the RF Learning mode. A second transmission enrolls the serial number and the system beeps two times and displays “Activate Sensor Again To Confirm”. A third transmission will confirm the serial number. The system beeps three times and returns to the Zone programming Screen. Enroll Manually Enter the 7-digit serial number printed on the transmitter using the displayed keypad and select “Done”. The system beeps one time and returns to the Zone programming Screen. Zone 49 Zone The system displays the next available key Zone number. Select “Zone” to manually enter a specific Zone Number on the displayed keypad (49-64). If the desired Zone Number is not available, the system returns to the previous screen. Select ”Done”. The system returns to the previous screen. Repeat the previous step to enter another Zone Number. - 28 - LYNX Touch Installation and Setup Guide Programming the Control SCREEN Button Key * - Zn * ACTION Button Key * Zn * Select the desired Button Key and enter a function for each button key. The system displays the following options: Disarm Arm Away Arm Stay No Response 24 Hour Silent 24 Hour Audible 24 Hour Auxiliary Silent Burglary Fire No Verification * Options are the same for each Button/Zone combination. - 29 - LYNX Touch Installation and Setup Guide Programming the Control Reporter When Compass service is required and GSM or IP are the only reporting channels: As part of Primary Central Station programming; the “Phone Type” must be set to any selection other than “None”, the “Communicator Type” must be set to GSM or IP, as applicable, and must match the compass value; “Phone number” field must be left blank and an “Account number” must be programmed. The following system options are programmed in this section: Option Prim. or Sec. Central Station Phone Type Phone Number Communicator Type Account Number Dynamic Priority Dynamic Delay Report All Report Alarms Report Troubles Report Open/Close Report Tests Phone 1 or Phone 2 Phone Type Phone Number Report All Report Alarms Report Troubles Report Open/Close Report Tests Report Selection Options PBX Call Wait Cancel Number of Reports Alarm Report Delay Swinger Shutdown Abort Window First Offset Report Report Frequency Downloader Phone Answer Modem Speed Ans. Machine Defeat Ring Counter Callback Number Flexible Callback Number Function Enroll information pertaining to the Primary and/or Secondary Central Station. Select the Report Format that will be used to send reports to the Primary or Secondary Central Station, as applicable. Enter the Phone Number for the Primary or Secondary Central Station, as applicable. Select the type of Communications Module that will be used to communicate with the Primary or Secondary Central Station, as applicable. Enter the account number for the Primary or Secondary Central Station, as applicable. Select the primary method for sending Reports to the Primary or Secondary Central Station, as applicable. Selects delay between switching between reporting methods. Active if Dynamic Delay feature has been set to Preferred Telco or Preferred Radio. Enable All Reports to be sent to the Primary or Secondary Central Station, as applicable. Enable Alarm Reporting to the Primary or Secondary Central Station, as applicable. Enable Trouble Reporting to the Primary or Secondary Central Station, as applicable. Enable Open/Close Reporting to the Primary or Secondary Central Station, as applicable. Enable Test Reporting to the Primary or Secondary Central Station, as applicable. Enroll information Primary and/or Secondary telephone numbers for “Follow Me” Announcements and/or Reminders. Enter Number for Phone 1 or Phone 2, as applicable. Enter Primary and/or Secondary telephone numbers for “Follow Me” Announcements and/or Reminders. Enable All Reports to be sent to the Phone 1 or Phone 2, as applicable. Enable Alarm Reporting to the Phone 1 or Phone 2, as applicable. Enable Trouble Reporting to the Phone 1 or Phone 2, as applicable. Enable Open/Close Reporting to the Phone 1 or Phone 2, as applicable. Enable Test Reporting to the Phone 1 or Phone 2, as applicable. Enable Reporting of Specific Events Enter the digits required to access an outside line, if applicable Enter the digits required to cancel call waiting, if applicable Limit the number of messages sent to the Central Station during an armed period. (applies to LYNX Touch only) Disable or select the time delay for alarm reporting (applies to LYNX Touch only) Select the number of times reports are sent and sounder sounds for non-fire alarms before the system ignores subsequent alarms (applies to LYNX Touch SIA only) Select the time delay for alarm reporting (applies to LYNX Touch SIA only) Select the time for the first test report following power-up/programming or downloading Select the test report frequency Enable or disable to allow control to answer incoming phone line. (Future Use) Enable to defeat answering machine mode. (Active if Phone Answer is enabled.) Enter the number of rings before control picks up phone line. (Active if Ans. Machine Defeat is not enabled.) Enter the phone number the control will use to call back the downloading computer. (Active if Phone Answer is enabled.) Allows Download operator to temporarily change the callback number by the number of digits selected. Active if Phone Answer is enabled Enter the number of flexible callback numbers that will be used. Active if Flexible Callback is enabled. - 30 - LYNX Touch Installation and Setup Guide Programming the Control Notes: If applicable, preprogrammed defaults for the LYNX Touch Control are shown on the screen unless otherwise noted. When GSM is used as the Primary Communications channel for any Total Connect service, the GSM Radio must be selected as the Primary Reporting Path (Preferred Radio). SCREEN Reporter Primary Central Station Phone Type Contact Id: 4 Digit Phone Number Communicator Type None ACTION Select “Reporter” The System displays the following options: Primary Central Station Secondary Central Station Phone 1 Phone 2 Report Selection Options Downloader Select “Primary Central Station”. The System displays the following options: Phone Type Communicator Type Select “Phone Type”. The System scrolls though the following options: None Contact Id: 4 Digit Contact Id: 10 Digit SIA If any option other than “None” is selected in “Phone Type” The “Phone Number” option will be displayed. Select “Phone Number”. Enter the Primary Central Station Phone Number on the displayed keypad. Select “Communicator Type”. The System scrolls though the following options: None GSM IP Note: The system will display the communications (GSM or IP) path that was selected in Communications Programming. The Communication Path selection can be enabled for either Primary Central Station or Secondary Central Station but not both. If it is enabled in one it will not be available for the other Central Station. Account Number FFFF Dynamic Priority Redundant Reports Dynamic Delay 30 Seconds If any option other than “None” is selected in “Phone Type” The “Account Number” option will be displayed. Select “Account Number”. Enter the Primary Central Station Account Number on the displayed keypad. If any option other than “None” is selected in “Communicator Type” The “Dynamic Priority” option will be displayed. “Select “Dynamic Priority”. The system scrolls between “Redundant Reports”, “Preferred Telco” and Preferred Radio”. If any option other than “Redundant Reports” is selected in “Dynamic Priority” The “Dynamic Delay” option will be displayed. “Select “Dynamic Delay”. The system scrolls between “15 Seconds”, “30 Seconds”, “60 Seconds” and “90 Seconds”. Note: If GSM is selected as the primary reporting channel Dynamic Delay should be set to minimum of 60 seconds. Report All Press to Report All Select “Report All”. The System toggles between “Press to Report All” and “Report All Set”. If “Report All” is selected all reporting options will be “Enabled”. Select the “Save” key to return to the Reporter options screen. Report Alarms Disabled Select “Report Alarms”. The System toggles between “Disabled” and “Enabled”. SIA: The LYNX Touch SIA default is “Enabled”. Report Troubles Disabled Select “Report Troubles”. The System toggles between “Disabled” and “Enabled”. SIA: The LYNX Touch SIA default is “Enabled”. Report Open/Close Disabled Select “Open/Close”. The System toggles between “Disabled” and “Enabled”. Report Tests Disabled Select “Report Tests”. The System toggles between “Disabled” and “Enabled”. Secondary Central Station Select “Secondary Central Station”. The System displays the following options: Phone Type Communicator Type - 31 - LYNX Touch Installation and Setup Guide Programming the Control SCREEN Phone Type None Communicator Type None ACTION Select “Phone Type”. The System displays the following options: None Contact Id: 4 Digit Contact Id: 10 Digit SIA Select “Communicator Type”. The System displays the following options: None GSM or IP Note: The system will display the communications path (GSM or IP) selected in Communications Programming. The path can be enabled for either primary Central Station or Secondary Central Station but not both. If it is enabled in one it will not be available for the other Central Station. Phone Number Account Number FFFF Dynamic Priority Redundant Reports If any option other than “None” is selected in “Phone Type”, the “Phone Number” option will be displayed. Select “Phone Number”. Enter the Secondary Central Station Phone Number on the displayed keypad. If any option other than “None” is selected in “Phone Type” The “Account Number” option will be displayed. Select “Account Number”. Enter the Secondary Central Station Account Number on the displayed keypad. If any option other than “None” is selected in “Communicator Type” The “Dynamic Priority” option will be displayed. “Select “Dynamic Priority”. The system scrolls between “Redundant Reports”, “Preferred Telco” and Preferred Radio”. 30 Seconds If any option other than “Redundant Reports” is selected in “Dynamic Priority” The “Dynamic Delay” option will be displayed. “Select “Dynamic Delay”. The system scrolls between “15 Seconds”, “30 Seconds”, “60 Seconds” and “90 Seconds”. Note: If GSM is selected as the primary reporting channel Dynamic Delay should be set to minimum of 60 seconds. Report All Press to Report All Select “Report All”. The System toggles between “Press to Report All” and “Report All Set”. If “Report All” is selected all reporting options will be “Enabled”. Select the “Save” key to return to the Reporter options screen. Dynamic Delay Report Alarms Disabled Select “Report Alarms”. The System toggles between “Disabled” and “Enabled”. Report Troubles Disabled Select “Report Troubles”. The System toggles between “Disabled” and “Enabled”. Report Open/Close Disabled Select “Open/Close”. The System toggles between “Disabled” and “Enabled”. Report Tests Disabled Select “Report Tests”. The System toggles between “Disabled” and “Enabled”. Phone 1 Phone Type None Phone Number Report All Press to Report All Select “Phone 1” to program the “Follow Me” Reminder telephone number 1 Select “Phone Type”. The System toggles between “None” and “Follow Me”. Select “Phone Number”. Enter the “Follow Me” Phone Number 1 on the displayed keypad. Select “Report All”. The System toggles between “Press to Report All” and “Report All Set”. If “Report All” is selected all reporting options will be “Enabled”. Select the “Save” key to return to the Reporter options screen. Report Alarms Disabled Select “Report Alarms”. The System toggles between “Disabled” and “Enabled”. Report Troubles Disabled Select “Report Troubles”. The System toggles between “Disabled” and “Enabled”. - 32 - LYNX Touch Installation and Setup Guide Programming the Control SCREEN ACTION Report Open/Close Disabled Select “Open/Close”. The System toggles between “Disabled” and “Enabled”. Report Tests Disabled Select “Report Tests”. The System toggles between “Disabled” and “Enabled”. Phone 2 Phone Type None Select “Phone 2” to program the “Follow Me” Reminder telephone number 2. Select “Phone Type”. The System toggles between “None” and “Follow Me”. Phone Number Select “Phone Number”. Enter the “Follow Me” Phone Number 2 on the displayed keypad. Report All Press to Report All Select “Report All”. The System toggles between “Press to Report All” and “Report All Set”. If “Report All” is selected all reporting options will be “Enabled”. Select the “Save” key to return to the Reporter options screen. Report Alarms Disabled Select “Report Alarms”. The System toggles between “Disabled” and “Enabled”. Report Troubles Disabled Select “Report Troubles”. The System toggles between “Disabled” and “Enabled”. Report Open/Close Disabled Select “Open/Close”. The System toggles between “Disabled” and “Enabled”. Report Tests Disabled Select “Report Tests”. The System toggles between “Disabled” and “Enabled”. Report Selection Select “Report Selection”. The System displays the following options: Arm Away Arm Stay Disarm Exit Error Recent Closing Event Log Full Trouble Trouble Restore Use the down T arrow to scroll to the next page of options. Alarm Restore Alarm Cancel Test Test Restore Bypass Bypass Restore AC Loss AC Loss Restore Use the down T arrow to scroll to the next page of options. Low Battery Low Battery Restore RF Low Battery RF Low Battery Restore Arm Away Enabled Select “Arm Away”. The System toggles between “Disabled” and “Enabled”. Arm Stay Enabled Select “Arm Stay”. The System toggles between “Disabled” and “Enabled”. Disarm Enabled Select “Disarm”. The System toggles between “Disabled” and “Enabled”. Exit Error Enabled Select “Exit Error”. The System toggles between “Disabled” and “Enabled”. Recent Closing Enabled Select “Recent Closing”. The System toggles between “Disabled” and “Enabled”. Note: In the LYNX Touch SIA control, this field is always “Enabled”. Event Log Full Enabled Select “Event Log Full”. The System toggles between “Disabled” and “Enabled”. - 33 - LYNX Touch Installation and Setup Guide Programming the Control SCREEN Trouble Enabled Trouble Restore Enabled ACTION Select “Trouble”. The System toggles between “Disabled” and “Enabled”. Select “Trouble Restore”. The System toggles between “Disabled” and “Enabled”. Alarm Restore Enabled Select “Alarm Restore”. The System toggles between “Disabled” and “Enabled”. Alarm Cancel Enabled Select “Alarm Cancel”. The System toggles between “Disabled” and “Enabled”. Test Enabled Test Restore Enabled Bypass Enabled Bypass Restore Enabled AC Loss Enabled AC Loss Restore Enabled Low Battery Enabled Low Battery Restore Enabled RF Low Battery Enabled RF Low Battery Restore Enabled Options PBX Call Wait Cancel Number of Reports Unlimited Select “Test”. The System toggles between “Disabled” and “Enabled”. Select “Test Restore”. The System toggles between “Disabled” and “Enabled”. Select “Bypass”. The System toggles between “Disabled” and “Enabled”. Select “Bypass Restore”. The System toggles between “Disabled” and “Enabled”. Select “AC Loss”. The System toggles between “Disabled” and “Enabled”. Select “AC Loss Restore”. The System toggles between “Disabled” and “Enabled”. Select “Low Battery”. The System toggles between “Disabled” and “Enabled”. Select “Low Battery Restore”. The System toggles between “Disabled” and “Enabled”. Select “RF Low Battery”. The System toggles between “Disabled” and “Enabled”. Select “RF Low Battery Restore”. The System toggles between “Disabled” and “Enabled”. Select “Options”. The System displays the following options: LYNX Touch Control PBX Call Wait Cancel Number of Reports Alarm Report Delay First Report Offset Report Frequency LYNX Touch SIA Control PBX Call Wait Cancel First Report Offset Swinger Shutdown Abort Window Report Frequency Select “PBX”, and enter PBX Prefix on the displayed keypad. Select “Call Wait Cancel”, and enter Call Wait Cancel Prefix on the displayed keypad Note: This field applies only to the LYNX Touch control. Select “Number of Reports”, the system toggles between “Unlimited” and “10 Reports”. - 34 - LYNX Touch Installation and Setup Guide Programming the Control SCREEN Alarm Report Delay No Delay Swinger Shutdown 2 Reports Abort Window 30sec First Report Offset 6 Hrs Report Frequency Never Downloader Phone Answer ACTION Note: This field applies only to the LYNX Touch control. Select “Alarm Report Delays”. The System scrolls between the following options: 15sec 30sec 45sec No delay Note: This field applies only to the LYNX Touch SIA control. Select “Swinger Shutdown”, the system toggles between “1 Report” and “2 Reports”. Note: This field applies only to the LYNX Touch SIA control. Select “Abort Window”. The System scrolls between the following options: 15sec 30sec 45sec SIA The burglary abort window must be set to a minimum of 15 seconds. The sum of the burglary abort window and the entry delays should not exceed 1 minute. Note: The LYNX Touch SIA control validates the data entered in this field. If the selection is not valid the control will emit a single long beep indicating that the selection has been rejected. The control replaces the selection with the default value “30sec. Select “First Report Offset” for the Test Report. The System scrolls between the following options: 6 Hrs 12 Hrs 18 Hrs 24 Hrs Select “Report Frequency” for the Test Report. The System scrolls between the following options: Never Every Day Every 7 Days Every 30 Days Select “Downloader”. The System displays the following options: Phone Answer Modem Speed Ans.Machine Defeat Callback Number Ring Counter Flexible Callback Number Select “Phone Answer”, the system toggles between “Yes” and “No”. Yes Modem Speed (Future Use) Slow Ans. Machine Defeat Select “Ans. Machine Defeat”, the system toggles between “Yes” and “No”. Yes Callback Number Ring Counter Flexible Callback Select “Callback Number” and enter callback number on the displayed keypad. This option only appears if Answering Machine defeat is set to “No”. Enter ring counter (1 – 14 rings) on the displayed keypad. Select “Flexible Callback”, the system toggles between “Yes” and “No”. No Number This option only appears if “Flexible Callback” is set to “Yes”. The system scrolls between options 1, 2 and 3. - 35 - LYNX Touch Installation and Setup Guide Programming the Control Sounder The following system options are programmed in this section: Option Burglary Alarm Sound Burglary Alarm Timeout Fire Bell Timeout Arm Confirm Alarm Options Function Switches the full 110 dB alarm sound for burglary On/Off. Select the time for timeout of the Burglary Alarm sounder. Select the time for timeout of the Fire Alarm sounder. Enable sounder “ding” when system is armed via the selected RF device. Select a limit for the number of times an alarm can sound for a specific zone. Note: This option does not apply to the LYNX Touch SIA control. Note: If applicable, preprogrammed defaults for the LYNX Touch Control are shown on the screen unless otherwise noted. SCREEN Sounder Burglary Alarm Sound ACTION Select “Sounder” The System displays the following options: Burglary Alarm Sound Burglary Bell Timeout Fire Bell Timeout Arm Confirm Alarm Options Select “Burglary Alarm Sound”. The System toggles between Yes* and No: Yes Burglary Bell Timeout 4 Minutes Fire Bell Timeout 4 Minutes Arm Confirm None Alarm Options Unlimited Select “Burglary Bell Timeout”. The System scrolls between the following options: No 4 Minutes 8 Minutes 12 Minutes 16 Minutes Select “Fire Bell Timeout”. The System scrolls between the following options: No 4 Minutes 8 Minutes 12 Minutes 16 Minutes Note: This option does not apply to the LYNX Touch Control. Select “Arm Confirm”. The System scrolls between the following options: None All RF RF Key Fob RF Keypad Select “Alarm Options”. The System scrolls between the following options: Unlimited 10 Select “Save”. - 36 - LYNX Touch Installation and Setup Guide Programming the Control System Settings The following system options are programmed in this section: Option Function Entry Delay1/Entry Delay 2 Selects an Entry Delay time in seconds. The system will wait the time entered before sounding alarm upon entering if system is not disarmed. Note: The Default values differ for the LYNX Touch and LYNX Touch SIA controls. Exit Delay Selects an Exit Delay time in seconds for both Entry Delay 1 and 2 Zone Types. The system will wait the time entered before sounding an alarm if the exit door is left open after the system has been armed. Note: The Default values differ for the LYNX Touch and LYNX Touch SIA controls. Backlight Timeout Enable or disable display backlight turnoff after 30 seconds. Quick Arm Enables or disables Quick Arm Mode. If enabled, security code is not required to arm the system. The user simply presses and holds down the AWAY button or ICON and then selects the ARM button on the displayed keypad to arm the system. Quick Exit Enables or disables Quick Exit Mode. If enabled allows the user restart the exit delay to allow entry or exit when the system is armed Restart Exit Time Enables or disables Restart Exit Time Mode. This option allows the control to restart the exit delay time after arming in STAY mode by entering the User Code and pressing the STAY key (if quick arming is disabled) or by pressing the STAY key (if quick arming is enabled). This option also enables automatic exit delay reset, which resets exit delay if the entry/exit door is re-opened and closed before exit delay time expires after arming. Force Bypass Enables or disables Force Bypass Mode. All zones bypassed by this function will be displayed after the bypass is initiated. The Fire and CO Zones are not bypassed in the LYNX Touch. Exit Warning Enables or disables Exit Warning sound. Audible Exit Warning sound consists of slow continuous beeps until last 5 seconds, when it changes to fast beeps. The warning sound will end at the termination of exit delay. Note: This field is not programmable in the LYNX Touch SIA and is always enabled. Auto Stay Arming Enables or disables Auto Stay Arming Mode. If this feature is enabled and the control panel has been armed “Armed Away” at the LYNX Touch keypad or RF keypad, the system will switch to the “Armed Stay” mode if the Exit Time has expired and no exit has been made. Lack of Usage Notify Enables or disables Lack of Usage Notification feature. If enabled, notifies the central station if an end user is not operating their security system by sending a System Inactivity report 654. The report will be sent only to the Primary phone number and only if Contact ID® format was selected. Power-Up in Previous Enables or disables Power-Up in Previous Mode feature. When the system powers up armed, an alarm will occur 1 minute after arming if a zone is faulted. For the LYNX Touch control any bypassed zones will be unbypassed. For the LYNX Touch SIA any bypassed zones will remain bypassed. Display Alarm Cancel Enables or disables display of Cancelled Alarm. Display Exit Time Enables or disables display of Exit Time. Cross Zone Delay Sets the maximum amount of time in which two zones must be tripped in an armed system to send an alarm message to the Central Station. If only one cross zone is tripped during this time, a trouble message (CID code 380) for that zone is sent to the Central Station. Cross Zone 1/Cross Zone 2 Select the zones that will be used for Cross Zoning - 37 - LYNX Touch Installation and Setup Guide Programming the Control Note: If applicable, preprogrammed defaults for the LYNX Touch Control are shown on the screen unless otherwise noted. SCREEN System Settings Entry Delay 1 30 Seconds ACTION Select “System Settings” The System displays the following options: Entry Delay 1 Entry Delay 2 Exit Delay Backlight Timeout Quick Arm Quick Exit Restart Exit Time Force Bypass Exit Warning Auto Stay Arming Use the down T arrow to scroll to the next page of options. Use the S arrow to return to the previous page: Lack of Usage Notify Power-Up In Previous Display Alarm Cancel Display Exit Time Cross Zone Delay Cross Zone 1 Cross Zone 2 Select “Entry Delay 1”. The System scrolls between the following options: LYNX Touch LYNX Touch SIA None 30 Seconds 15 Seconds 45 Seconds 30 Seconds 60 Seconds 45 Seconds 90 Seconds 60 Seconds 2 Minutes 90 Seconds 3 Minutes 2 Minutes 4 Minutes UL installations: The Entry Delay must be set for a maximum of 45 seconds SIA: The Entry delay must be set to a minimum of 30 seconds. The sum of entry delay 1 and the burglary abort window should not exceed 1 minute. Entry Delay 2 60 Seconds Select “Entry Delay 2”. The System scrolls between the following options: LYNX Touch LYNX Touch SIA None 30 Seconds 15 Seconds 45 Seconds 30 Seconds 60 Seconds 45 Seconds 90 Seconds 60 Seconds 2 Minutes 90 Seconds 3 Minutes 2 Minutes 4 Minutes UL installations: The Entry Delay must be set for a maximum of 45 seconds SIA: The Entry delay must be set to a minimum of 30 seconds. The sum of entry delay 2 and the burglary abort window should not exceed 1 minute. The LYNX Touch SIA default is “60 Seconds”. Exit Delay 60 Seconds Select “Exit Delay”. The System toggles between the following options: LYNX Touch LYNX Touch SIA None 45 Seconds 15 Seconds 60 Seconds 30 Seconds 90 Seconds 45 Seconds 2 Minutes 60 Seconds 90 Seconds 2 Minutes UL installations: Exit Delay must be set for a maximum of 60 seconds SIA: The Exit Delay must be set to a minimum of 45 seconds. Backlight Timeout Select “Backlight Timeout”. The System toggles between No and 30 Seconds. No Quick Arm Select “Quick Arm”. The System toggles between Yes and No. Yes - 38 - LYNX Touch Installation and Setup Guide Programming the Control SCREEN Quick Exit ACTION Select “Quick Exit”. The System toggles between Yes and No. Yes Restart Exit Time No Force Bypass No Exit Warning No Auto Stay Arming No Lack of Usage Notify Disabled Power-Up In Previous Yes Select “Restart Exit Time”. The System toggles between Yes and No. SIA: The LYNX Touch SIA default is “Yes”. Select “Force Bypass”. The System toggles between Yes and No. UL installations: must be NO (no forced bypass) Select “Exit Warning”. The System toggles between Yes and No. Note: This option is not selectable in the LYNX Touch SIA control and is always enabled. Select “Auto Stay Arming”. The System toggles between Yes and No. SIA: The LYNX Touch SIA default is “Yes”. Select “Lack of Usage Notify”. The System scrolls between the following options: Disabled 1 Day 7 Days 27 Days 90 Days 180 Days 365 Days Select “Power-Up In Previous”. The System toggles between Yes and No. Note: If the previous state was Armed Away or Stay, the system will not respond to sensor changes for 1 minute. This allows time for sensors such as PIRs to stabilize. UL installations: must be 1 (power up in previous state) Display Alarm Cancel Select “Display Alarm Cancel”. The System toggles between Yes and No. No Display Exit Time Select “Display Exit Time”. The System toggles between Yes and No. Yes Cross Zone Delay 3 Minutes Cross Zone 1 Disabled Cross Zone 2 Disabled Select “Cross Zone Delay”. The System toggles between the following: None 30 Seconds 1 Minute 90 Seconds 2 Minutes 3 Minutes 4 Minutes Select “Cross Zone 1”. The System toggles between the following: Disabled Note: If Cross Zone Delay is enabled the system will display the zones that are programmed with the following Zone Types: Day/Night, Interior Follower and perimeter. Select “Cross Zone 2”. The System toggles between the following: Disabled Note: If Cross Zone Delay is enabled the system will display the zones that are programmed with the following Zone Types: Day/Night, Interior Follower and perimeter. - 39 - LYNX Touch Installation and Setup Guide Programming the Control Communications Diagnostics Communications Status – The system provides a status of the IP or GSM communications paths and performs a self-test of the AES encryption algorithm as follows: Message GSM: Encryption: Alarmnet Registration: Meaning OK Fault Reported! Not Connected Not Registered! No Physical Link AES Passed! AES Failed! No Encryption! Registered Not Registered Normal; No fault. (IP or GSM) No network connectivity and fault time has expired. (IP or GSM) No network connectivity over IP and fault time has NOT yet expired. No network connectivity over GSM and fault time has NOT yet expired. No network connectivity over IP and fault time is set to 0. Test successful. Test failed. No encryption algorithm set. Communication Device is Registered with AlarmNet. Communication Device is not Registered with AlarmNet. Ethernet Information – Displays IP information, if IP communication path is enabled. Physical Link: DHCP: Indicates status of the physical connection to the internet. DHCP (Dynamic Host Configuration Protocol) indicated server is performing satisfactorily. NIC IP Address: Displays the IP address assigned to this device Subnet Mask: Displays the 32-bit address mask used to indicate the portion (bits) of the IP address that is being used for the subnet address. Displays the IP address assigned to the Gateway. Displays the IP address assigned to the DNS (Domain Name System) server. Gateway IP Address: DNS Server IP Address: Message Physical Link DHCP Meaning 10 Mbps or 100 Mbps Bad OK Bad Off Link speed of physical connection No physical connection DHCP address resolved DHCP address not resolved DHCP disabled GSM Information – Displays GSM information if GSM communication path is enabled. Status GSM Registered GSM Not Registered Message Cell Registration: Home Roaming Primary RSSI: -xxdBm* GPRS: Yes No Country: xxx Network: xxx LAC xxxxx Cell: xxxx Base Station: xx Channel: xxx Second Site RSSI: -xxdBm* Searching For Coverage! SIM Error! Cell Registration: SIM Not Active Cell Registration: Not Registered Meaning Registered Home Registered Roaming Primary Site RSSI level in dBm GPRS Service availability GPRS is not available Country Code Network Code Local Area Code Base Station ID Base Station Antenna Sector Control Channel in use Secondary Site RSSI level in dBm Searching for cell network. No SIM card present or SIM card faulty SIM is not activated Not registered with cell network * RSSI = Communications Module’s Signal Level. Displayed in dBm, where: xx = -01 to -93 Indicates Good signal level xx = -94 to -95 Indicates Poor signal level. Unit should be relocated for better signal level. xx = -96 (and lower) Indicates fail signal level. Move unit for better signal level. If “FAIL” condition persists, do not install. - 40 - LYNX Touch Installation and Setup Guide Programming the Control Communications ID Numbers – Displays programmed SIM card information Message MAC: MAC CRC: SCID:* IMEI:* xxxxxxxxxxxx xxxx xxxxxxxxxxxxxxxxxxxx xxxxxxxxxxxxxxx Meaning MAC Address indicates the unique identification number MAC CRC number Displays the ID number assigned to the installed SIM card (SCID) Displays the ID number assigned to the installed GSM module. * Displayed if GSM communication path is enabled. Test Communications – Performs network diagnostics and sends test alarms to AlarmNet. The following tests are available depending on the type of communications module installed. Test Ethernet This test is available if IP communication path is enabled. The network diagnostic process tests the integrity of the links between the LYNX Touch and the various connection points of AlarmNet Control that are known as “Redirectors”. If a physical link is detected and is ready, the following diagnostics are performed. Testing Gateway… Traces the connection to the Gateway and displays the following: Testing Gateway – Successful! A successful trace to Gateway. OR Testing Gateway – Failed! Failed to reach Gateway. Testing Redirector * Sequentially traces the connection to Redirector 1, 2 and 3 at AlarmNet Control. The following will be displayed. Redirector * – Service OK Service at AlarmNet Control on Redirector 1, 2 or 3 is functioning. OR Redirector * – Failed Error occurred on Redirector 1, 2 or 3. * = Number of the director being tested is displayed A summary of the tests is displayed after Redirector 3 is tested. The example shows that the tests of all three connection points, or Redirectors, were successful. If an error occurred at any point, the summary will display “Failed” next to the faulty Redirector. Redirector 1 – Service OK Redirector 2 – Service OK Redirector 3 – Service OK If no physical link is detected, the test is aborted and one of the following is displayed: No Physical Link No physical link is detected. Link Not Ready There is a link but it is not ready (address not resolved). Send Any If both IP and GSM communication paths are enabled and the LYNX Touch is registered, a Test alarm is sent over IP path. If that is not successful, it sends the alarm over GSM path and the following message is displayed: Test Message Sent If the device is not registered, the following is displayed: Test Message Failed – Not Registered Send GSM Message If GSM communication path is enabled and the LYNX Touch is registered, a Test alarm to AlarmNet over the GSM path. The following message is displayed: Test Message Sent If the device is not registered, the following message is displayed: Test Message Failed – Not Registered Send Ethernet Message If IP communication path is enabled and the LYNX Touch is registered, a Test alarm to AlarmNet over the IP path. The following message is displayed: Test Message Sent If the device is not registered, the following message is displayed: Test Message Failed – Not Registered Setup Communication – Performs registration of the LYNX Touch and its associated communication module with AlarmNet updates configuration files or reset factory defaults. Registering the LYNX Touch Once the LYNX Touch is initialized and a communications module is programmed, it must be registered to enable the account. Upon completion of the registration process, the LYNX Touch transmits a registration message and receives a registration validation indicating that the account is now enabled. Wait for the “Registration Success” message to appear, regardless of which registration method is used. You can register the communications module by one of the following methods: • Through the AlarmNet Direct website • By Phone • Through the LYNX Touch Diagnostics - 41 - LYNX Touch Installation and Setup Guide Programming the Control Register through AlarmNet Direct Website If you have programmed the communications module through AlarmNet Direct, you must then transfer the data to the module, and register the module. To do this, please go to: https://services.alarmnet.com/AlarmNetDirect/userlogin.aspx. Log in and follow the on-screen prompts. If you are not signed up for this service, click on “Dealer Signup” from the login screen to gain access to the Honeywell web-based programming. Dealer Sign-Up Direct Link: https://services.alarmnet.com/AlarmNetDirectP_Sign-Up. You will be instructed how to proceed upon completing the sign-up form. Only one sign-up per dealer is required. Once an initial user is established, additional logins may be created by that user. Please have the following information available when programming the device: 1. Primary City ID (two-digit number) 2. Primary Central Station ID (two-digit hexadecimal number) 3. Primary Subscriber ID (four-digit number) 4. MAC ID and MAC CRC number (located on outside of box and on label inside module – location to be confirmed). Once module is registered, you may log out of the AlarmNet Direct website. Register by Phone You can register the module by calling the AlarmNet Technical Assistance Center (TAC) at 1-800-222-6525. You will need the following information: • MAC number (found on the label). • Subscriber information (provided by the central station), including a city code, CSID, and a subscriber ID. • When instructed to do so, select Register Device in the LYNX Touch Diagnostics to complete the registration. Register through LYNX Touch Diagnostics You can register the module using the LYNX Touch Diagnostics by the following the following procedure. SCREEN Comm. Diagnostics Setup Communication ACTION 1. Select “Comm. Diagnostics” The System displays the following options depending upon the communication device that is installed: Communication Ethernet GSM Status Information Information Communication Test Setup ID Numbers Communication Communication 2. Select “Setup Communication”. The System advances to the Registration screen and the following options are displayed: Register Register Device Device With PIN Update Factory Server Defaults 3. Select “Register Device”. The registration message is sent and the unit waits for the acknowledgement. (Refer to the table below for applicable registration messages.) Note: Register Device can be cancelled by selecting “Cancel”. The registration process is aborted and the message Registration Cancelled! is displayed. - 42 - LYNX Touch Installation and Setup Guide Programming the Control During the registration process the following messages may be displayed: Message Getting Configuration File… Registering… Registration Successful! Registering – Try Later! Registration Failed! Invalid Configuration! Timed Out. Central Station Database Full. Primary Sub ID Bad. Primary ID – Need PIN. Account Disabled. Meaning The configuration file is obtained from AlarmNet if the module was programmed through AlarmNet Direct or a previously programmed module was defaulted. The registration message is sent and the unit is waiting for the acknowledgement. The module is registered and is now in full service and available for alarm reporting to the central station. Error Message indicates the module is busy. Error message followed by one of the messages below: Indicates the configuration is invalid. Displayed if no response to the registration request is received. Indicates CS database has more than 1000 subscribers. Indicates the city, central station, or customer number for the labeled account is not accepted. The ID information was either entered incorrectly, or the central station failed to pre-authorize programmed ID numbers with AlarmNet customer service. Indicates the city, central station, or customer number for the labeled account is not accepted. The ID information was either entered incorrectly, or the central station failed to pre-authorize programmed ID numbers with AlarmNet customer service. See the Register Device With PIN section. Displayed if the account is disabled in AlarmNet. Register Device With PIN This procedure is used to replace one LYNX Touch module with another. SCREEN Comm. Diagnostics Setup Communication ACTION 1. Select “Comm. Diagnostics” The System displays the following options depending upon the communication device that is installed: Communication Ethernet GSM Status Information Information Communication Test Setup ID Numbers Communication Communication 2. Select “Setup Communication”. The System advances to the Registration screen and the following options are displayed: Register Register Device Device With PIN Update Factory Server Defaults 3. Select “Register Device With PIN”. Enter a 4-digit alphanumeric PIN number (provided by your central station, your dealer or an authorized AlarmNet representative) on the displayed keypad then select “Done”. (Refer to the table below for applicable registration messages.) Note: Register Device With PIN can be cancelled by selecting “Cancel”. The registration process is aborted and the message Registration Cancelled! is displayed. During the registration process the following messages may be displayed: Message Registering… Registration Successful! Registering – Try Later! Registration Failed! Invalid Configuration! Timed Out. Primary ID – Need PIN. Meaning The registration message is sent and the unit is waiting for the acknowledgement. The PIN number is valid and module is registered and is now in full service and available for alarm reporting to the central station. The old module is unregistered. Additionally, AlarmNet sends a substitution alarm to the central station. Error Message indicates the module is busy. Error message followed by one of the messages below: Indicates the configuration is invalid. Displayed if no response to the registration request is received. Indicates PIN that was entered is invalid. - 43 - LYNX Touch Installation and Setup Guide Programming the Control Update Server This procedure is used to upload the Configuration File to the Server. SCREEN Comm. Diagnostics Setup Communication Yes ACTION 1. Select “Comm. Diagnostics” The System displays the following options depending upon the communication device that is installed: Communication Ethernet GSM Status Information Information Communication Test Setup ID Numbers Communication Communication 2. Select “Setup Communication”. The System advances to the Registration screen and the following options are displayed: Register Register Device Device With PIN Update Factory Server Defaults 3. Select “Update Server” and select “Yes” when the confirmation screen appears. The device uploads its entire configuration file to the server. Selecting “No” will cancel the operation. (Refer to the table below for applicable registration messages.) During the upload process the following messages may be displayed: Message Updating Root File… Programming Done Updating Configuration – Try Later! Cannot Upload – Try Later! Update Root File – Failed! Meaning The root file is being uploaded. Indicates the root file has been successfully uploaded. Error message indicates the module is busy Error message indicates the communication path(s) is not available. Error message indicates an error while uploading root file.. - 44 - LYNX Touch Installation and Setup Guide Programming the Control Factory Defaults This procedure resets the programming options to factory-default values. SCREEN Comm. Diagnostics Setup Communication ACTION 1. Select “Comm. Diagnostics” The System displays the following options depending upon the communication device that is installed: Communication Ethernet GSM Status Information Information Communication Test Setup ID Numbers Communication Communication 2. Select “Setup Communication”. The System advances to the Registration screen and the following options are displayed: Register Register Device Device With PIN Update Factory Server Defaults 3. Select “Factory Defaults” and select “Yes” when the confirmation screen appears. The device is reset to factory default values. Selecting “No” will cancel the operation. (Refer to the table below for applicable registration messages.) The following messages may be displayed: Message Default Configuration – Successful! Default Configuration Failed – Access Denied Default Configuration – Try Later! Meaning Indicates all programmed values are reset to the original factory settings. Error message indicates the device does not have local programming access. Error message indicates the module is busy. - 45 - LYNX Touch Installation and Setup Guide Remote Programming/Control (Downloading) General Information The control panel can be remotely programmed from an IBM-compatible Personal Computer (PC), Compass Downloader, a HAYES compatible Modem or via a capable GSM or IP Communications Module. When connected to the COMPASS Downloader – “SERVICE UPDATE” appears on touch screen. UL Downloading may only be performed if a technician is at the site. Multiple security levels protect remote programming against compromise by attempts to defeat the system. 1. Security Code Handshake: A download ID code is verified for authenticity before connection is established. 2. Site-Initiated Remote Programming: The installer initiates downloading by selecting the “Initiate Download” button on the Installer programming screen. 3. Station-Initiated Remote Programming: The operator calls the site from your office to initiate the download call. The Control hangs up and then calls back the PC via the preprogrammed telephone number. The unit can then be uploaded, downloaded, or controlled from your office. 4. Data Encryption: Data passed between the PC and the Control is encrypted for security so that it is very difficult for a foreign device tapped into the phone line to take over communication and substitute system-compromising information. Equipment required to download to a system at the premises • Compass Downloader for Windows (at revision level supporting LYNX Touch). Flexible Callback: If enabled in Installer Programming, the download operator can temporarily change the last 1, 2, or 3 digits (depending on selection) of the call back number. This allows the control to call back a computer other than the one programmed, which may be helpful at times of high computer traffic. Remote Programming Information If using Remote Programming, the LYNX Touch must be connected to the telephone line, GSM Cellular or to the Internet, as applicable. The downloading system can perform many functions when in communication with the Control. Besides uploading and downloading, the status of the system can be observed and various commands can be initiated, as follows: • Arm the system in the away mode; disarm the system. • Bypass a zone. • Force the system to accept a new program download. • Shut down communication functions (for nonpayment of monitoring fees in an owned system). • Shut down all security system functions (for nonpayment for a leased system). • Inhibit local keypad programming (prevents account takeover). • Command the system to upload a copy of its resident program to the office. • Set the time • View/Modify • Read: arming status, AC power status, lists of faulted zones, bypassed zones, zones currently in alarm, zones currently in trouble, and RF sensors with low battery conditions; read control’s time. Notes: (1) (2) After the control and the PC have established valid communication, “Service Update” will be displayed on the LCD. The detailed operation of the download functions is covered in the installation instructions for the Compass Downloader for Windows. - 46 - LYNX Touch Installation and Setup Guide Remote Programming/Control (Downloading) Remote Programming Advisory Notes • A copy of the program downloaded may be printed using the IBM PC-compatible computer’s internal report generator, when an optional printer is connected (consult your PC manual for proper printer and connections). • The approximate time for program upload or download for a complete program is shown below: Communication Method PSTN GSM IP Approx. Time 380 secs. 75 secs. 30 secs. - 47 - LYNX Touch Installation and Setup Guide System Operation Key/Touchscreen Operation The keys and touchscreen allows the user to arm and disarm the system, and perform other system functions, such as bypassing zones. Zone and system conditions (ALARM, trouble, bypass) are displayed on the display. When an alarm occurs, console sounding and external sounding will occur, and the zone(s) in alarm will be displayed on the display. Pressing any key will silence the keypad sounder for 10 seconds (only once). Disarming the system will silence both console and external sounders. When the system is disarmed, any zones that were in an alarm condition during the armed period will be displayed (memory of alarm). To clear this display, simply repeat the disarm sequence by pressing the OFF key and entering the Security Code. The console also features chime annunciation, and three panic key icons for silent, audible, fire or personal emergency alarms. These keys can notify the central station of an alarm condition, if that service is connected. Panic Key/Icons There are three panic key icons that, if programmed, are displayed on the virtual keypad when the “PANIC” key is depressed for four seconds. The panic key screen will timeout if a selection is not made within ten seconds. The keys can be used to manually initiate alarms and send a report to the central station. Each can be individually programmed for 24-hour silent, audible, personal or fire emergency responses. The panic function is activated when the respective keys is pressed. The panic functions are identified by the system as follows: Zone 95 96 99 Function Fire Emergency Medical Emergency Police Emergency Important: For the silent panic functions to be of practical value, the system must be connected to a central station. Security Codes Installer Code The installer programs the 4-digit Installer Code initially as part of the programming procedure. The factory default Installer Code is 4-1-1-2, but may be changed in the Installer Code programming field. The Installer Code is the only code that allows entry into Installer Programming mode. Master Code In normal operation mode, the Master Code is used to enter the 4-digit User Security Codes. Enter/change the Master code by installer. The factory default Master Code for the LYNX Touch Control is set to 1-2-3-4. The Master Code is used to enter the 4-digit User Security Codes. SCREEN ACTION Ready To Arm Users Devices Schedules Test Date Time Events Reminders Slide Show 1. After entering the User Tools/Programming Menu, select the “Users” icon on the User Menu screen. The system displays the User Code Programming screen 2. Select “Master”, then select “Edit”. 3. Enter a new four-digit Master Code on the displayed keypad The system will display the new code on the left side of the screen. Select “Done” when you are finished. The system returns to the User Code Programming screen. Back 5000-100-070-V0 Master **** 4. 5. - 48 - LYNX Touch Installation and Setup Guide System Operation Secondary User Codes In normal operation mode, the Master Security Code can be used to assign up to 14 secondary 4-digit security codes, including a Babysitter Code and a Duress Code. The Master Code can also be used to remove secondary codes from the system (individually). Refer to the LYNX Touch User Manual for additional information. Security Code Notes • • • • • The Master and Secondary security codes permit access to the system for arming, disarming, etc. The Installer Code can disarm the system only if it was used to arm it. In addition, the Installer Code cannot disarm the system if it was armed by pressing and holding a Quick-Arm button. The Babysitter Code can disarm the system only if it was used to arm it. In addition, the Babysitter Code cannot disarm the system if it was armed by pressing and holding a Quick-Arm button. Duress code sends a special code to the monitoring station when used to perform any system operation. Instruct users to be careful not to use this code for normal usage. Opening/closing reports are sent for the Installer Code, with the appropriate subscriber number. Master Code and set of secondary user codes are sent as Nos. 02 and 03–14, respectively, in Contact ID® format (with the appropriate user number). - 49 - LYNX Touch Installation and Setup Guide System Operation “Follow Me” System Announcement Feature This feature allows the LYNX Touch to deliver a voice system message to the user phone numbers programmed by the installer. The LYNX Touch will first transmit reports to the Central Station and after receiving its kiss-off the system will dial the user phone numbers and begin transmitting the welcome message “System Message, Press Star to Play”. The system will dial the user phone numbers a maximum of eight times. The “Follow Me” System announcements feature is only supported if PSTN line is available. The announcements are individually sent to the User 1 and/or User 2 phone numbers which are programmed as Phone 1 and Phone 2 respectively in the Reporter Programming section. System Follow Me announcements are triggered by a system event that belongs to one of the Event Groups enabled by Installer individually for User 1 and User 2. The groups are listed below. • All Bypassing actions by a user • Any Open/Close (arming/disarming status changes) • Any Alarms • Any Alarm Restores • Alarm Cancel by the user • Any System Troubles • Any Test • Non-security Events If User 1 does not press a “*” key, LYNX Touch will hang up and will redial the User 1 number in 20 seconds. The control will make eight attempts before unsuccessfully ending the System “Follow Me” session and erasing all the events in the User 1’s queue. The next call will be triggered by a new event from the Event Group enabled for User 1. If User 1 presses a “*” key, LYNX Touch will play back a sequence of System “Follow Me” announcements from the User 1’s queue in chronological order starting with the oldest one. The announcements will include “End of Message” at the end of the “Follow Me” announcements. If a “*” key is pressed again during playback or within 15 seconds following the end of the playback, the control will repeat the sequence. Otherwise the system will hang up, successfully ending the System “Follow Me” session. Because the “*” key was pressed LYNX Touch will not redial the User 1 again. The next call will be triggered by a new event from the Event Group enabled for User 1. Note: The follow me system announcement will be terminated if any other event requires the system to send a report to the Central Station. Once the PSTN line is available the session will be resumed and the control will again make up to 8 delivery attempts. Follow Me Event Triggers AC Loss Audible Panic Automatic Disarmed Battery Failed Under Load Burglary Zone Bypass Carbon Monoxide Detected Disarmed From AWAY or STAY Emergency Alarm Entry/Exit Alarm Exit Error Alarm (zone) Expansion Module Tamper Expansion Module Failure Expansion Module Tamper Alarm Expansion Module Tamper Trouble Fire Alarm Fire Trouble Interior Alarm Follow Me Announcement AC Loss Panic Alarm Disarmed System Low Battery Zone ** Bypassed Carbon Monoxide Alarm Disarmed Emergency Alarm Perimeter Alarm Perimeter Alarm Tamper Alarm System Trouble Tamper Alarm Tamper Alarm Fire Alarm System Trouble Interior Alarm Follow Me Event Triggers Keypad Panic Manual Test Medical Alarm Opening Keyswitch Perimeter Alarm Remote Disarm RF Sensor Lost Sensor Low Battery or Tamper Silent Burglary Siren Tamper System Inactivity System Low Battery Water Leakage Alarm Zone Bypass Zone Tamper (Alarm) Zone Trouble ** = Zone Number - 50 - Follow Me Announcement Panic Alarm System Test Emergency Alarm Disarmed Perimeter Alarm Disarmed System Trouble Sensor Trouble Silent Burglary Tamper Alarm No Check In System Low Battery Auxiliary Alarm Zone ** Bypassed Tamper Alarm System Trouble LYNX Touch Installation and Setup Guide System Operation “Follow Me” Reminder Feature This feature allows the user to schedule a time driven message. When activated, the system will dial the User 1 and/or User 2 phone numbers, which are programmed as Phone 1 and Phone 2 respectively by the installer (in the Reporter Programming section), and deliver a recorded message. The LYNX Touch will immediately begin transmitting the voice message and will repeat the message for 45 seconds. If the message has timed out, the system will redial the programmed number a maximum of seven additional times or until it is acknowledged. Pressing any key on the LYNX Touch keypad will terminate (acknowledge) both the “Follow Me” reminder and the local reminder announcements. Notes: (1) This feature is only supported if it has been programmed. (2) The follow me reminder will be terminated if any other event requires the system to dial out, however, delivery of the local schedule reminder message will continue. (3) If a Central Station report must be sent, the “Follow Me” Reminder message will be suspended. Once the PSTN line is available the session will be resumed and the control will again make up to 8 delivery attempts. Remote Phone Control Feature The remote phone control feature, which must be enabled, allows the user to access the security system from any off-site touch-tone telephone. The control will pick up the incoming call, based on the specified ring count, and will announce “SYSTEM ENTER CODE” every three seconds for the next nine seconds. During this period the panel will wait for a valid User Code to be entered. If a valid User Code is not entered or the nine second period expires a modem tone will be generated for remote programming (Compass Downloading). If a valid User Code has been entered, the control will announce the current system status and/or beeping sounds. Refer to the User Guide for additional information regarding this feature. - 51 - LYNX Touch Installation and Setup Guide System Operation System Displays The following icons will be displayed on the Home screen along with specific zone status information (if applicable) to indicate system status. DISPLAY DEFINITION DISPLAY DEFINITION AC Loss Door Open Alarm (intrusion) Window Open Armed Away Exit Active Armed Stay Fire Battery Low Flood Check Zones Glass Break CO Alarm Medical Alarm Disarmed Not Ready to Arm Motion Disarmed Ready to Arm Temperature 90 RF Jam Cover Tamper 94 Phone Line Cut Reporter Failure 103 Comm. Trouble Zone Status Displays The following icons will be displayed on the Zone Status screen along with specific zone status information when a zone has been Faulted, Bypassed or in Alarm. DISPLAY DEFINITION Alarm Fault (Yellow) DISPLAY DEFINITION Ready Trouble (red) - 52 - DISPLAY DEFINITION Bypass LYNX Touch Installation and Setup Guide System Operation UL Audio alarm verification has not been evaluated by UL. Audio Alarm Verification (Two-Way Voice Feature) This feature allows the central station operator to listen, talk to or conduct a two-way conversation with an individual(s) at the premises. It also assists the operator in gathering information about the nature and location of the alarm that may be helpful in responding to police and fire departments. All LYNX Touch control panels are capable of supporting the Two-Way Voice feature. The LYNX Touch does not make system announcements when the Two-Way voice feature is active. Activation Fire and CO alarms will prevent the LYNX Touch from starting an AAV session. A new Fire or CO alarm will end an AAV session that is in progress. The LYNX Touch sends the “alarm message” followed by a “Listen-in-to-Follow message” (Contact ID® code 606) to the Central Station. The Listen-in-to-Follow message causes the Central Station’s digital receiver to temporarily hold the phone line for approximately 1-minute. When the LYNX Touch receives the “kissoff” from the central station, indicating that the alarm message has been received, the Two-Way Voice (AAV) feature is activated in the (default) “Listen Mode” and sirens and keypad sounds are discontinued. The LYNX Touch transmits a beep acknowledgment to the Central Station, once per second. The beep alternates between two tones and indicates that the LYNX Touch is waiting for a session command from the Central Station operator. Once a command is issued the beep acknowledgement is discontinued, however, if a command is not issued within two minutes the system will “time out” and the call will be terminated. Operator Commands The Central Station operator begins the session, which last 5 minutes, by entering one of the valid AAV commands shown in the table below. The session may be extended 5 minutes, without changing the operating mode, by pressing the [7] key on the touch-tone phone. Selecting another operating mode also resets the session an additional 5 minutes. During the last minute of the 5 minute, session, the LYNX Touch generates two beeps every 30 seconds to alert the Central Station operator that the session is about to time out. The Central Station operator may then extend the session by pressing the [7] key on the touch-tone phone. If the session is not extended the phone line is disconnected, and the session is ended. Sessions may be ended at any time by pressing the [9] key on the touch-tone phone. The AAV modes are described as follows: Note: When entering AAV commands make sure the Central Station receiver has been disconnected from the phone line, otherwise AAV commands may not go through. Key Function Talk Mode: Pressing the [1] key on the touch tone phone, enables one-way voice communication from the central station to the violated premises, and allows the operator to talk communicate through the LYNX Touch speaker. In this mode the ARMED (red) and READY (green) LEDs blink alternately. VOX (Voice) Mode: Pressing the [2] key on the touch-tone phone, enables two-way voice communications between the central station and the violated premises. In this mode the ARMED (red) and READY (green) LEDs blink alternately. Listen Mode: Pressing the [3] key on the touch-tone phone, enables one-way audio from the violated premises to the central station. The Listen Mode is the start up default mode of the voice feature and allows the operator to listen through the LYNX Touch microphone. This mode does not affect the existing LED pattern. Extends the session 5 minutes without changing its operating mode. Ends the session and disconnects the phone line. - 53 - LYNX Touch Installation and Setup Guide System Operation Event Log The LYNX Touch Series event log is capable of recording and displaying up to 128 system events. The type of events that can be recorded is selectable and is programmed in the System Type programming field. The event log can be reviewed by entering the Installer Programming or Master User Programming mode. Refer to the LYNX Touch Series User Manual for additional information. Note: In the unlikely condition that the backup battery becomes fully discharged when AC power is lost, any system activity performed after the low battery notification will not be saved in the event log. Additionally, the panel will revert to the status condition as before the low battery notification. Contact ID® & SIA Event Log Codes CID SIA Definition Definition Code Code 110 Alarm, Fire AT/AR AC Trouble/AC Restoral 121 Alarm, Duress BA/BR Burglary Alarm/Burglary Restoral 122 Alarm, Silent BB/BU Burglary Bypass/Burglary Unbypass 123 Alarm, Audible CA/CD Automatic Closing/Closing Delinquent 131 Alarm, Perimeter CI Fail to Close 132 Alarm, Interior CL Closing Report 134 Alarm, Entry/Exit CQ Remote Closing 135 Alarm, Day/Night CR Recent Closing 137 Alarm, Tamper CS Closing Keyswitch 145 Expansion Module Tamper DF/DR Door Forced/Door Restoral 146 Silent Burglary EA Exit Alarm 150 24-Hour Non-Burglary EM/EN Expansion Device Missing/Expansion Missing Restore 162 Carbon Monoxide Detected ES/EJ Expansion Device Tamper/Expansion Tamper Restore 301 Trouble, AC Loss ET Expansion Trouble 302 Trouble, Low System Battery FA Fire Alarm 305 Trouble, System Reset FT/FJ Fire Trouble/Fire Trouble Restore 341 Trouble, Case Tamper FT/FJ Fire Trouble/Fire Trouble Restore 344 Trouble, RF Receiver Jam Detect HA/HR Holdup Alarm/Holup Restoral 351 Trouble, Telco 1 Fault JL Log Threshold 353 Trouble, Long Range Radio Transmitter Fault LB/LX Local Progr./Local Progr. End (Logged in Event Log ) 354 Trouble, Failure to Communicate Event LT/LR Phone Line Trouble/Phone Line Restoral 373 Trouble, Fire Trouble MA/MR Medical Alarm/ Medical Restoral 374 Trouble, Exit Error Alarm OA Automatic Opening 380 Trouble, Sensor OC Cancel Report 381 Trouble, Loss of Supervision RF OP Opening Report 383 Trouble, Sensor Tamper OQ Remote Opening 384 RF Low Battery OS Opening Keyswitch 401 Open/Close by User PA Panic Alarm 403 Open/Close Automatic RP Automatic Test 406 Cancel RS Remote Program Success 407 Remote Arm/Disarm RX Manual Test 408 Quick Arm TA/TH Tamper Alarm/Tamper Alarm Restore 409 Open/Close Keyswitch TJ Tamper Trouble Restore 412 Successful Download TS/TE Test Start/Test End 441 Armed Stay TT Tamper Trouble 442 Keyswitch Armed STAY UA Untyped Zone Alarm 455 Auto-Arm Failed UB/UU Untyped Zone Bypass/Untyped Zone Unbypass 459 Recent Close WA/WR Water Alarm/Water Restoral 570 Zone/Sensor Bypass XQ/XH RF Interference/RF Interference Restore 601 Manual Trigger Test Report XT/XR Transmitter Battery Trouble/Transmitter Battery Restoral 602 Periodic Test Report YC/YK Communications Fail/Communications Restoral 606 Listen-in to follow YM System Battery Missing 607 Walk Test YT/YR System Battery Trouble/System Battery Restoral 623 Event Log 80% Full 627 Program Mode Entry (Logged in Event Log Only) 628 Program Mode Exit (Logged in Event Log Only) 654 System Inactivity 759 Resident Monitor Zone Response 760 Resident Response Zone Response 761 General Monitor Zone Response 762 General Response Zone Response Note: LRR/IP Communications Module Low Battery and Low Battery restore reports are sent real time. LRR/IP Communications Module trouble restore report is sent after two OFF Sequences (only if physically restored). - 54 - LYNX Touch Installation and Setup Guide Testing the System Test Mode After installation is completed, the security system should be carefully tested, as follows. 1. With the system in the disarmed state, check that all zones are intact. If the READY LED is not lit, select the Zones icon to display the faulted zone(s). If necessary, restore faulted zone(s) so that the READY LED lights. Fault and restore every sensor individually to assure that it is being monitored by the system. Armed System Test Alarm messages will be sent to the central station during the following tests 1 and 2. Notify the Central Station in advance that tests will be in progress. 1. Arm the system and fault one or more zones. After 15 seconds (if optional dialer delay is selected), silence alarm sounder(s) by pressing OFF and entering the security code. Check entry/exit delay zones. 2. Check the keypad-initiated alarms that are in the system by selecting the Panic key. If the system has been programmed for audible emergency, the keypad will emit a steady alarm sound, and “ALARM” and zone number will be displayed. For LYNX Touch, silence the alarm pressing OFF and entering the security code. For LYNX Touch SIA configuration, silence the alarm by entering the security code. If the system has been programmed for silent emergency, there will be no audible alarms or displays, but a report will be sent to the central station. 3. Notify the central station when all tests are finished, and verify results with them. 4. To test the wireless part of the system and the RF receiver, perform the two additional tests described in the Installing Wireless Zones section: Sniffer mode and Go/No Go Test. Note: System Test mode and Go/No Go Test will be automatically terminated after 3-1/2 to 4 hours if the installer or user does not manually terminate it. This ensures that fire and panic zones will not remain disabled. However, Sniffer mode does not automatically expire. You must manually exit (by entering an OFF Sequence) Sniffer mode to return to normal operation. During the final 5 minutes the system will emit double beeps indicating that the end of Test mode is nearing. Dialer Test The Dialer Test checks that the phone connection to the central station is working properly. Notify the Central Station in advance that tests will be in progress. 1. With the System in the Installer Programming mode, select the “Test” button and then select the “Dialer Test” button. 2. If the test is successful the system will send the Manual Trigger Test Report (E601) to the Central Station. The test will not be recorded in the Event Log. 3. The system will make 8 attempts to test the dialer for both the Primary and Secondary Central Station, as applicable. If the test is unsuccessful the system will display a “Reporter Failure” trouble message after 1-17 minutes. TO THE INSTALLER Regular maintenance and inspection (at least annually) by the installer and frequent testing by the user are vital to continuous satisfactory operation of any alarm system. The installer should assume the responsibility of developing and offering a regular maintenance program to the user as well as acquainting the user with the proper operation and limitations of the alarm system and its component parts. Recommendations must be included for a specific program of frequent testing (at least weekly) to ensure the system’s proper operation at all times. - 55 - LYNX Touch Installation and Setup Guide LYNX Touch Programming Default Tables Program Function Installer Code System Type RF Jam Speaker Phone Two Way Voice RF House Code Phone Notification Remote Phone Phone Detect Time Events - Log All Events - Log Alarm Events - Log Bypass Events - Log Open/Close Events - Log Trouble Non Security Remote Access Serial Multi Mode Serial Date Time Calendar Enter Time Time Zone Day Light Savings time Start Month Start Week End Month End Week Communicator Communications Path Primary City Id Pri Central Station Id Primary Subscriber Id Supervision Old Alarm Time Remote Acc. IP or GSM Multi Mode IP or GSM GSM Fault Time IP Fault Time Use DHCP NI IP Address Subnet Mask Gateway IP Address DNS Server IP Address Zones Reporter Primary Central Station Phone Type Communicator Type Phone Number Account Number Dynamic Priority Dynamic Delay Report All Report Alarms Report Troubles Report Open/Close Report Tests Table 1 Table 2 Table 3 Table 4 4112 4112 4112 4112 Disabled Enabled Disabled Disabled Enabled 2 Minutes Press To Log All Enabled Disabled Disabled Enabled Disabled Disabled Disabled Disabled Enabled Disabled Disabled Enabled 2 Minutes Log All Set Enabled Enabled Enabled Enabled Enabled Disabled Disabled Disabled Enabled Disabled Disabled Enabled 2 Minutes Log All Set Enabled Enabled Enabled Enabled Disabled Disabled Disabled Disabled Enabled Disabled Disabled Enabled 2 Minutes Log All Set Enabled Enabled Enabled Enabled Disabled Disabled Disabled January 1, 2011 10:00AM Eastern (EST) Yes March Second November First January 1, 2011 10:00AM Eastern (EST) Yes March Second November First January 1, 2011 10:00AM Eastern (EST) Yes March Second November First January 1, 2011 10:00AM Eastern (EST) Yes March Second November First None None None None 24 Hours 10 Minutes Disabled Disabled 00 00 Yes 255.255.255.255 255.255.255.255 255.255.255.255 255.255.255.255 None None None None None None None None 24 Hours 24 Hours 10 Minutes 10 Minutes Disabled Disabled Disabled Disabled 00 00 00 00 Yes Yes 255.255.255.255 255.255.255.255 255.255.255.255 255.255.255.255 255.255.255.255 255.255.255.255 255.255.255.255 255.255.255.255 See Zone Programming Default Tables None None None None 24 Hours 10 Minutes Disabled Disabled 00 00 Yes 255.255.255.255 255.255.255.255 255.255.255.255 255.255.255.255 Contact Id: 4 Digit None None FFFF None None Report All Set Enabled Enabled Enabled Enabled Contact Id: 4 Digit None None FFFF None None Report All Set Enabled Enabled Enabled Enabled Contact Id: 4 Digit None None FFFF None None Press To Report All Disabled Disabled Disabled Disabled - 56 - Contact Id: 4 Digit None None FFFF None None Report All Set Enabled Enabled Enabled Enabled LYNX Touch Installation and Setup Guide LYNX Touch Programming Default Tables Program Function Secondary Central Station Phone Type Communicator Type Phone Number Account Number Dynamic Priority Dynamic Delay Report All Report Alarms Report Troubles Report Open/Close Report Tests Phone 1 Phone Type Phone Number Report All Report Alarms Report Troubles Report Open/Close Report Tests Phone 2 Phone Type Phone Number Report All Report Alarms Report Troubles Report Open/Close Report Tests Report Selection Arm Away Arm Stay Disarm Exit Error Recent Closing Event Log Full Trouble Trouble Restore Alarm Restore Alarm Cancel Test Test Restore Bypass Bypass Restore AC Loss AC Loss Restore Low Battery Low Battery Restore RF Low Battery RF Low Battery Restore Options PBX Call Wait Cancel Number of Reports Alarm Report Delay First Report Offset Report Frequency Table 1 Table 2 Table 3 Table 4 Contact Id: 4 Digit None None FFFF None None Press To Report All Disabled Disabled Disabled Disabled Contact Id: 4 Digit None None FFFF None None Report All Set Enabled Enabled Enabled Enabled Contact Id: 4 Digit None None FFFF None None Report All Set Enabled Enabled Enabled Enabled Contact Id: 4 Digit None None FFFF None None Report All Set Enabled Enabled Enabled Enabled None None Press To Report All Disabled Disabled Disabled Disabled None None Press To Report All Disabled Disabled Disabled Disabled None None Press To Report All Disabled Disabled Disabled Disabled None None Press To Report All Disabled Disabled Disabled Disabled None None Press To Report All Disabled Disabled Disabled Disabled None None Press To Report All Disabled Disabled Disabled Disabled None None Press To Report All Disabled Disabled Disabled Disabled None None Press To Report All Disabled Disabled Disabled Disabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Disabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Disabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Blank Blank Unlimited No Delay 6 Hrs Never Blank Blank Unlimited 15 Seconds 12 Hrs 30 Days Blank Blank Unlimited No Delay 12 Hrs Never Blank Blank Unlimited No Delay 12 Hrs Never - 57 - LYNX Touch Installation and Setup Guide LYNX Touch Programming Default Tables Program Function Downloader Phone Answer Ans. Machine Defeat Modem Speed (Future Use) Ring Counter Callback Number Flexible Callback Number Sounder Burglary Alarm Sound Burglary Bell Timeout Fire Bell Timeout Arm Confirm Alarm Options System Settings Entry Delay 1 Entry Delay 2 Exit Delay Backlight Timeout Quick Arm Quick Exit Restart Exit Time Force Bypass Exit Warning Auto Stay Arming Lack Of Usage Notify Power-Up In Pervious Display Alarm Cancel Display Exit Time Cross Zone Delay Cross Zone 1 Cross Zone 2 Table 1 Table 2 Table 3 Table 4 Yes Yes Slow Blank No Yes Yes Slow Blank No Yes Yes Slow Blank No Yes Yes Slow Blank No Yes 4 Minutes 4 Minutes None Unlimited Yes 4 Minutes 4 Minutes None Yes 4 Minutes 4 Minutes None Yes 4 Minutes 4 Minutes None 30 Seconds 60 Seconds 60 Seconds No Yes Yes No No No No Disabled Yes No Yes 3 Minutes Disabled Disabled 45 Seconds 60 Seconds 60 Seconds No Yes Yes Yes No Yes Yes Disabled Yes Yes Yes None Disabled Disabled 30 Seconds 60 Seconds 60 Seconds No Yes Yes Yes No Yes Yes Disabled Yes Yes Yes None Disabled Disabled 30 Seconds 60 Seconds 60 Seconds No Yes Yes Yes No Yes Yes Disabled Yes Yes Yes None Disabled Disabled - 58 - LYNX Touch Installation and Setup Guide LYNX Touch SIA Programming Default Tables Program Function Installer Code System Type RF Jam Speaker Phone Two Way Voice RF House Code Phone Notification Remote Phone Phone Detect Time Events - Log All Events - Log Alarm Events - Log Bypass Events - Log Open/Close Events - Log Trouble Non Security Remote Access Serial Multi Mode Serial Date Time Calendar Enter Time Time Zone Day Light Savings time Start Month Start Week End Month End Week Communicator Communications Path Primary City Id Pri Central Station Id Primary Subscriber Id Supervision Old Alarm Time Remote Acc. IP or GSM Multi Mode IP or GSM GSM Fault Time IP Fault Time Use DHCP NI IP Address Subnet Mask Gateway IP Address DNS Server IP Address Zones Reporter Primary Central Station Phone Type Communicator Type Phone Number Account Number Dynamic Priority Dynamic Delay Report All Report Alarms Report Troubles Report Open/Close Report Tests Table 1 Table 2 Table 3 Table 4 4112 4112 4112 4112 Disabled Enabled Disabled Disabled Enabled 2 Minutes Press To Log All Enabled Disabled Disabled Enabled Disabled Disabled Disabled Disabled Enabled Disabled Disabled Enabled 2 Minutes Log All Set Enabled Enabled Enabled Enabled Enabled Disabled Disabled Disabled Enabled Disabled Disabled Enabled 2 Minutes Log All Set Enabled Enabled Enabled Enabled Disabled Disabled Disabled Disabled Enabled Disabled Disabled Enabled 2 Minutes Log All Set Enabled Enabled Enabled Enabled Disabled Disabled Disabled January 1, 2011 10:00AM Eastern (EST) Yes March Second November First January 1, 2011 10:00AM Eastern (EST) Yes March Second November First January 1, 2011 10:00AM Eastern (EST) Yes March Second November First January 1, 2011 10:00AM Eastern (EST) Yes March Second November First None None None None 24 Hours 10 Minutes Disabled Disabled 00 00 Yes 255.255.255.255 255.255.255.255 255.255.255.255 255.255.255.255 None None None None None None None None 24 Hours 24 Hours 10 Minutes 10 Minutes Disabled Disabled Disabled Disabled 00 00 00 00 Yes Yes 255.255.255.255 255.255.255.255 255.255.255.255 255.255.255.255 255.255.255.255 255.255.255.255 255.255.255.255 255.255.255.255 See Zone Programming Default Tables None None None None 24 Hours 10 Minutes Disabled Disabled 00 00 Yes 255.255.255.255 255.255.255.255 255.255.255.255 255.255.255.255 Contact Id: 4 Digit None None FFFF None None Report All Set Enabled Enabled Enabled Enabled Contact Id: 4 Digit None None FFFF None None Report All Set Enabled Enabled Enabled Enabled Contact Id: 4 Digit None None FFFF None None Report All Set Enabled Enabled Enabled Enabled - 59 - Contact Id: 4 Digit None None FFFF None None Report All Set Enabled Enabled Enabled Enabled LYNX Touch Installation and Setup Guide LYNX Touch SIA Programming Default Tables Program Function Secondary Central Station Phone Type Communicator Type Phone Number Account Number Dynamic Priority Dynamic Delay Report All Report Alarms Report Troubles Report Open/Close Report Tests Phone 1 Phone Type Phone Number Report All Report Alarms Report Troubles Report Open/Close Report Tests Phone 2 Phone Type Phone Number Report All Report Alarms Report Troubles Report Open/Close Report Tests Report Selection Arm Away Arm Stay Disarm Exit Error Recent Closing Event Log Full Trouble Trouble Restore Alarm Restore Alarm Cancel Test Test Restore Bypass Bypass Restore AC Loss AC Loss Restore Low Battery Low Battery Restore RF Low Battery RF Low Battery Restore Options PBX Call Wait Cancel Swinger Shutdown Abort Window First Report Offset Report Frequency Table 1 Table 2 Table 3 Table 4 Contact Id: 4 Digit None None FFFF None None Report All Set Enabled Enabled Enabled Enabled Contact Id: 4 Digit None None FFFF None None Report All Set Enabled Enabled Enabled Enabled Contact Id: 4 Digit None None FFFF None None Report All Set Enabled Enabled Enabled Enabled Contact Id: 4 Digit None None FFFF None None Report All Set Enabled Enabled Enabled Enabled None None Press To Report All Disabled Disabled Disabled Disabled None None Press To Report All Disabled Disabled Disabled Disabled None None Press To Report All Disabled Disabled Disabled Disabled None None Press To Report All Disabled Disabled Disabled Disabled None None Press To Report All Disabled Disabled Disabled Disabled None None Press To Report All Disabled Disabled Disabled Disabled None None Press To Report All Disabled Disabled Disabled Disabled None None Press To Report All Disabled Disabled Disabled Disabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Disabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Blank Blank 30 Seconds 6 Hrs Never Blank Blank 30 Seconds 12 Hrs 30 Days Blank Blank 30 Seconds 12 Hrs Never Blank Blank 30 Seconds 12 Hrs Never - 60 - LYNX Touch Installation and Setup Guide LYNX Touch SIA Programming Default Tables Program Function Downloader Phone Answer Ans. Machine Defeat Modem Speed (Future Use) Ring Counter Callback Number Flexible Callback Number Sounder Burglary Alarm Sound Burglary Bell Timeout Fire Bell Timeout Arm Confirm System Settings Entry Delay 1 Entry Delay 2 Exit Delay Backlight Timeout Quick Arm Quick Exit Restart Exit Time Force Bypass Exit Warning Auto Stay Arming Lack Of Usage Notify Power-Up In Pervious Display Alarm Cancel Display Exit Time Cross Zone Delay Cross Zone 1 Cross Zone 2 Table 1 Table 2 Table 3 Table 4 Yes Yes Slow Blank No Yes Yes Slow Blank No Yes Yes Slow Blank No Yes Yes Slow Blank No Yes 4 Minutes 4 Minutes None Yes 4 Minutes 4 Minutes None Yes 4 Minutes 4 Minutes None Yes 4 Minutes 4 Minutes None 30 Seconds 30 Seconds 60 Seconds No Yes Yes Yes No Yes Yes Disabled Yes No Yes 3 Minutes Disabled Disabled 30 Seconds 30 Seconds 60 Seconds No Yes Yes Yes No Yes Yes Disabled Yes Yes Yes None Disabled Disabled 30 Seconds 30 Seconds 60 Seconds No Yes Yes Yes No Yes Yes Disabled Yes Yes Yes None Disabled Disabled 30 Seconds 30 Seconds 60 Seconds No Yes Yes Yes No Yes Yes Disabled Yes Yes Yes None Disabled Disabled Zone Programming Default Tables Zone Assignment/Alarm Report Codes for Table 1 Zone Loop Supervision/ Device Type Response Type Report Chime Zone Descriptor Number Number Input Type --New n/a yes no EOLR n/a Door Entry Exit 1 yes yes RF Supervised Front Door Door Entry Exit 1 yes yes RF Supervised Back Door Window Perimeter yes yes RF Supervised n/a Motion Sensor Interior w/Delay yes no RF Supervised n/a 49 4 Button Key Arm Away yes no Button n/a 50 4 Button Key Disarm yes no Button n/a 51 4 Button Key Arm Stay yes no Button n/a 52 4 Button Key No Response no no Button n/a 53 4 Button Key Arm Away yes no Button n/a 54 4 Button Key Disarm yes no Button n/a 55 4 Button Key Arm Stay yes no Button n/a 56 4 Button Key No Response no no Button n/a 92 ------yes no Duress Trigger n/a 95 --Fire Fire No Verification yes no Panic Trigger n/a 96 --Medical n/a yes no Panic Trigger n/a 97 ------yes no Cover Tamper n/a 99 --Police 24-Hour Silent yes no Panic Trigger n/a NOTE: Zone 1 is a hardwire zone; Zone 2 to 48 are RF zones; Zone 92 is Duress; Zone 99 is keypad panic - 61 - LYNX Touch Installation and Setup Guide Zone Programming Default Tables Zone Assignment/Alarm Report Codes for Table 2 Zone Loop Supervision/ Device Type Response Type Report Chime Zone Descriptor Number Number Input Type --New n/a yes no EOLR n/a Door Entry Exit 1 yes yes RF Supervised Front Door Door Entry Exit 1 yes yes RF Supervised Back Door Door Entry Exit 1 yes yes RF Supervised Garage Door Motion Sensor Interior w/Delay yes no RF Supervised n/a Smoke Detector Fire No verification yes no RF Supervised n/a 49 4 Button Key Arm Away yes no Button n/a 50 4 Button Key Disarm yes no Button n/a 51 4 Button Key Arm Stay yes no Button n/a 52 4 Button Key No Response no no Button n/a 53 4 Button Key Arm Away yes no Button n/a 54 4 Button Key Disarm yes no Button n/a 55 4 Button Key Arm Stay yes no Button n/a 56 4 Button Key No Response no no Button n/a 92 ------yes no Duress Trigger n/a 95 --Fire Fire No Verification yes no Panic Trigger n/a 96 --Medical 24-Hour Auxiliary yes no Panic Trigger n/a 97 ------yes no Cover Tamper n/a 99 --Police 24-Hour Audible yes no Panic Trigger n/a NOTE: Zone 1 is a hardwire zone; Zone 2 to 48 are RF zones; Zone 92 is Duress; Zone 99 is keypad panic Zone Assignment/Alarm Report Codes for Tables 3 and 4 Zone Loop Supervision/ Device Type Response Type Report Chime Zone Descriptor Number Number Input Type --New n/a yes no EOLR n/a Door Entry Exit 1 yes yes RF Supervised Front Door Door Entry Exit 1 yes yes RF Supervised Back Door Window Perimeter yes no RF Supervised n/a Window Perimeter yes no RF Supervised n/a Window Perimeter yes no RF Supervised n/a Window Perimeter yes no RF Supervised n/a Motion Sensor Interior w/Delay yes no RF Supervised n/a Smoke Detector Fire No Verification yes no RF Supervised n/a 49 4 Button Key Arm Away yes no Button n/a 50 4 Button Key Disarm yes no Button n/a 51 4 Button Key No Response yes no Button n/a 52 4 Button Key No Response no no Button n/a 53 4 Button Key Arm Away yes no Button n/a 54 4 Button Key Disarm yes no Button n/a 55 4 Button Key No Response yes no Button n/a 56 4 Button Key No Response no no Button n/a 92 ------yes no Duress Trigger n/a 95 --Fire Fire No Verification yes no Panic Trigger n/a 96 --Medical n/a yes no Panic Trigger n/a --yes no 97 --Cover Tamper n/a 99 --Police 24-Hour Silent yes no Panic Trigger n/a NOTE: Zone 1 is a hardwire zone; Zone 2 to 48 are RF zones; Zone 92 is Duress; Zones 95, 96 and 99 are keypad panics - 62 - LYNX Touch Installation and Setup Guide Regulatory Agency Statements Federal Communications Commission (FCC) Part 15 The user shall not make any changes or modifications to the equipment unless authorized by the Installation Instructions or User's Manual. Unauthorized changes or modifications could void the user's authority to operate the equipment. CLASS B DIGITAL DEVICE STATEMENT NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: • Reorient or relocate the receiving antenna. Increase the separation between the equipment and receiver. Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. Consult the dealer or an experienced radio/TV technician for help. • • • This Class B digital apparatus complies with Canadian ICES-003. Cet appareil numérique de la classe B est conforme à la norme NMB-003 du Canada. FCC IC Statement This device complies with Part 15 of FCC Rules and RSS 210 of Industry Canada. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) This device must accept any interference received, including interference that may cause undesired operation. Cet appareil est conforme à la partie 15 des règles de la FCC & de RSS 210 des Industries Canada. Son fonctionnement est soumis aux conditions suivantes: (1) Cet appareil ne doit pas causer d' interferences nuisibles. (2) Cet appareil doit accepter toute interference reçue y compris les interferences causant une reception indésirable. TELEPHONE/MODEM INTERFACE Federal Communications Commission (FCC) Part 68 This equipment complies with Part 68 of the FCC rules. On the front cover of this equipment is a label that contains the FCC registration number and Ringer Equivalence Number (REN). You must provide this information to the telephone company when requested. This equipment uses the following USOC jack: RJ31X This equipment may not be used on telephone-company-provided coin service. Connection to party lines is subject to state tariffs. This equipment is hearing-aid compatible. Industry Canada NOTICE: The Industry Canada Label identifies certified equipment. This certification means that the equipment meets telecommunications network protective, operational and safety requirements as prescribed in the appropriate Terminal Equipment Technical Requirements document(s). The Department does not guarantee the equipment will operate to the user’s satisfaction. Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of the local telecommunications company. The equipment must also be installed using an acceptable method of connection. The customer should be aware that compliance with the above conditions may not prevent degradation of service in some situations. Repairs to certified equipment should be coordinated by a representative designated by the supplier. Any repairs or alterations made by the user to this equipment, or equipment malfunctions, may give the telecommunications company to request the user to disconnect the equipment. Users should ensure for their own protection that the electrical ground connections of the power utility, telephone lines and internal metallic water pipe system, if present, are connected together, This precaution may be particularly important in rural areas. Caution: Users should not attempt to make such connections themselves but should contact appropriate electric inspection authority, or electrician, as appropriate. AVIS: l’étiquette d’Industrie Canada identifie le matériel homologué. Cette étiquette certifie que le matériel est conforme aux normes de protection, d’exploitation et de sécurité des réseaux de télécommunications, comme le prescrivent les documents concernant les exigences techniques relatives au matériel terminal. Le Ministère n’assure toutefois pas que le matériel fonctionnera à la satisfaction de l’utilisateur. Avant d’installer ce matériel, l’utilisateur doit s’assurer qu’il est permis de le raccorder aux installations de l’enterprise locale de télécommunication. Le matériel doit également être installé en suivant une méthode acceptée da raccordement. L’abonné ne doit pas oublier qu’il est possible que la conformité aux conditions énoncées ci-dessus n’empêche pas la dégradation du service dans certaines situations. Les réparations de matériel nomologué doivent être coordonnées par un représentant désigné par le fournisseur. L’entreprise de télécommunications peut demander à l’utilisateur da débrancher un appareil à la suite de réparations ou de modifications effectuées par l’utilisateur ou à cause de mauvais fonctionnement. Pour sa propre protection, l’utilisateur doit s’assurer que tous les fils de mise à la terre de la source d’energie électrique, de lignes téléphoniques et des canalisations d’eau métalliques, s’il y en a, sont raccordés ensemble. Cette précaution est particulièrement importante dans les régions rurales. Avertissement : L’utilisateur ne doit pas tenter de faire ces raccordements lui-même; il doit avoir racours à un service d’inspection des installations électriques, ou à un électricien, selon le cas. Ringer Equivalence Number Notice: The Ringer Equivalence Number (REN) assigned to each terminal device provides an indication of the maximum number of terminals allowed to be connected to a telephone interface. The termination on an interface may consist of any combination of devices subject only to the requirement that the sum of the Ringer Equivalence Numbers of all the devices does not exceed 5. AVIS : L’indice d’équivalence de la sonnerie (IES) assigné à chaque dispositif terminal indique le nombre maximal de terminaux qui peuvent être raccordés à une interface. La terminaison d’une interface téléphonique peut consister en une combinaison de quelques dispositifs, à la seule condition que la somme d’indices d’équivalence de la sonnerie de tous les dispositifs n’excède pas 5. RF Exposure WARNING: The LYNX Touch must be installed to provide a separation distance of at least 7.8 in (20 cm) from all persons and not co-located or operated in conjunction with any other transmitter. - 63 - LYNX Touch Installation and Setup Guide WARNING THE LIMITATIONS OF THIS ALARM SYSTEM While this System is an advanced design security system, it does not offer guaranteed protection against burglary, fire or other emergency. Any alarm system, whether commercial or residential, is subject to compromise or failure to warn for a variety of reasons. For example: • Intruders may gain access through unprotected openings or have the technical sophistication to bypass an alarm sensor or disconnect an alarm warning device. • Intrusion detectors (e.g., passive infrared detectors), smoke detectors, and many other sensing devices will not work without power. Battery-operated devices will not work without batteries, with dead batteries, or if the batteries are not put in properly. Devices powered solely by AC will not work if their AC power supply is cut off for any reason, however briefly. • Signals sent by wireless transmitters may be blocked or reflected by metal before they reach the alarm receiver. Even if the signal path has been recently checked during a weekly test, blockage can occur if a metal object is moved into the path. • A user may not be able to reach a panic or emergency button quickly enough. • While smoke detectors have played a key role in reducing residential fire deaths in the United States, they may not activate or provide early warning for a variety of reasons in as many as 35% of all fires, according to data published by the Federal Emergency Management Agency. Some of the reasons smoke detectors used in conjunction with this System may not work are as follows. Smoke detectors may have been improperly installed and positioned. Smoke detectors may not sense fires that start where smoke cannot reach the detectors, such as in chimneys, in walls, or roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level of a residence or building. A second floor detector, for example, may not sense a first floor or basement fire. Finally, smoke detectors have sensing limitations. No smoke detector can sense every kind of fire every time. In general, detectors may not always warn about fires caused by carelessness and safety hazards like smoking in bed, violent explosions, escaping gas, improper storage of flammable materials, overloaded electrical circuits, children playing with matches, or arson. Depending on the nature of the fire and/or location of the smoke detectors, the detector, even if it operates as anticipated, may not provide sufficient warning to allow all occupants to escape in time to prevent injury or death. • Passive Infrared Motion Detectors can only detect intrusion within the designed ranges as diagrammed in their installation manual. Passive Infrared Detectors do not provide volumetric area protection. They do create multiple beams of protection, and intrusion can only be detected in unobstructed areas covered by those beams. They cannot detect motion or intrusion that takes place behind walls, ceilings, floors, closed doors, glass partitions, glass doors, or windows. Mechanical tampering, masking, painting or spraying of any material on the mirrors, windows or any part of the optical system can reduce their detection ability. Passive Infrared Detectors sense changes in temperature; however, as the ambient temperature of the protected area approaches the temperature range of 90° to 105°F (32° to 40°C), the detection performance can decrease. • Alarm warning devices such as sirens, bells or horns may not alert people or wake up sleepers if they are located on the other side of closed or partly open doors. If warning devices are located on a different level of the residence from the bedrooms, then they are less likely to waken or alert people inside the bedrooms. Even persons who are awake may not hear the warning if the alarm is muffled by noise from a stereo, radio, air conditioner or other appliance, or by passing traffic. Finally, alarm warning devices, however loud, may not warn hearing-impaired people. • Telephone lines needed to transmit alarm signals from a premises to a central monitoring station may be out of service or temporarily out of service. Telephone lines are also subject to compromise by sophisticated intruders. • Even if the system responds to the emergency as intended, however, occupants may have insufficient time to protect themselves from the emergency situation. In the case of a monitored alarm system, authorities may not respond appropriately. • This equipment, like other electrical devices, is subject to component failure. Even though this equipment is designed to last as long as 10 years, the electronic components could fail at any time. The most common cause of an alarm system not functioning when an intrusion or fire occurs is inadequate maintenance. This alarm system should be tested weekly to make sure all sensors and transmitters are working properly. The security keypad (and remote keypad) should be tested as well. Wireless transmitters (used in some systems) are designed to provide long battery life under normal operating conditions. Longevity of batteries may be as much as 4 to 7 years, depending on the environment, usage, and the specific wireless device being used. External factors such as humidity, high or low temperatures, as well as large swings in temperature, may all reduce the actual battery life in a given installation. This wireless system, however, can identify a true low battery situation, thus allowing time to arrange a change of battery to maintain protection for that given point within the system. Installing an alarm system may make the owner eligible for a lower insurance rate, but an alarm system is not a substitute for insurance. Homeowners, property owners and renters should continue to act prudently in protecting themselves and continue to insure their lives and property. We continue to develop new and improved protection devices. Users of alarm systems owe it to themselves and their loved ones to learn about these developments. - 64 - LYNX Touch Installation and Setup Guide UL NOTICES 1. For UL Residential Burglar Alarm installations with line security, total exit delay time must not exceed 60 seconds. For UL Burglar Alarm installations without line security, total exit delay time must not exceed 120 seconds. 2. Periodic testing (see scheduling mode) must be at least every 24 hours. 3. Remote downloading without an alarm company technician on-site (unattended downloading) is not permissible for UL installations. 4. Auto-disarming is not a UL Listed feature. 5. As SIA limits for delay of alarm reporting and sounding can exceed UL limits for commercial and residential applications, the following UL requirements per UL681 are provided: The maximum time that a control unit shall be programmed to delay the transmission of a signal to a remote monitoring location, or to delay the energizing of a local alarm sounding device to permit the alarm system user to enter and disarm the system, or to arm the system and exit shall not exceed: a) 60 seconds for a system with standard line security or encrypted line security, b) 120 seconds for a system without standard line security or encrypted line security, or c) 120 seconds for a system that does not transmit an alarm signal to a remote monitoring location. SIA Quick Reference Guide 1. 2. 3. 4. 7. 5. 6. 7. 8. 9. 10. 11. 12. 13. Report Alarms: Default is “Enabled” Report Troubles: Default is “Enabled” Exit Error: Default is “Enabled”. Recent Closing: Default is “Enabled”. Alarm Cancel: Default is “Enabled”. Call Wait Cancel: If call waiting is used, a call waiting cancel prefix must be entered. Swinger Shutdown: Options for “alarm sounding per zone” include 1 report or 2 reports. Default is “2 Reports”. Abort Window: Options include 15, 30 and 45 seconds. Default is 30 seconds. Entry Delay 1 and 2: Options include 30, 45, 60 and 90 seconds and 2, 3 or 4 minutes. Minimum entry delay is 30 seconds. When added together the entry delay plus the dialer delay should not exceed 1 minute. Exit Delay: Options include 45, 60, 90 seconds and 2 minutes. Minimum exit delay is 45 seconds. Restart Exit Time: Default is “Yes”. Exit Warning: Always enabled. This field is not programmable Auto Stay Arming: Default is “Yes”. Cross Zone Delay: Options include None or selections between 30 seconds and 2 minutes (in 30 second increments), 3 minutes and 4 minutes. Default is 3 minutes. - 65 - LYNX Touch Installation and Setup Guide Specifications LYNX Touch Series Security Controls Physical: Dimensions: 8.5” W x 6” H x 1.875” D Electrical: Voltage Input: 9 Vdc from plug-in 2.7A power supply Rechargeable Backup Battery: Nickel-metal hydride battery pack rated at 7.2 Vdc Communication: Formats Supported: ADEMCO Contact ID® Reporting, 10 characters/sec., DTMF (TouchTone) Data Tones, 1400/2300Hz Handshake, 1400Hz Kissoff. Line Seize: SIA/DCS Format, 2225Hz Handshake, Data Tones, 2025/2235Hz, baud Double Pole Ringer Equivalence: 0.5B ACTA Registration No.: US: AC3AL05BL5000 Hardwire Zone: 2K ohms, End of Line Resistor (EOLR), 200 ohms max wire resistance, dry contacts only Trigger Output: 1k ohms to ground when closed (output low) 3ma - 66 - LYNX Touch Installation and Setup Guide Contacting Technical Support PLEASE, before you call Technical Support, be sure you: • READ THE INSTRUCTIONS! • Check all wiring connections. • Determine that the power supply and/or backup battery are supplying proper voltages. • Verify your programming information where applicable. • Note the proper model number of this product, and the version level (if known) along with any documentation that came with the product. • Note your Honeywell customer number and/or company name. Having this information handy will make it easier for us to serve you quickly and effectively. Technical Support: ........................................................................................................ 1-800-645-7492 (8 a.m.-10 p.m. E.S.T.) MyWebTech: ..............................................................................http:// www.honeywell.com/security/hsc/resources/MyWebTech - 67 - LYNX Touch Installation and Setup Guide Glossary AES – Advanced Encryption Standard DHCP – Dynamic Host Configuration Protocol, which provides a mechanism for allocating IP addresses dynamically so that addresses can be reused when hosts no longer need them. DNS – Domain Name System, which is a distributed hierarchical naming system used to resolve domain names (e.g., www.yahoo.com) into numerical IP addresses (e.g., 204.17.25.1). Gateway IP Address – A gateway (sometimes called a router) is a computer and/or software used to connect two or more networks (including incompatible networks) and translates information from one network to the other. The Gateway IP address is the IP address for the gateway. GPRS – (General Packet Radio Service) GSM – Global System for Mobile communications, which is an international standard for digital mobile phone systems used for cellular communication. IMEI – International Mobile Equipment Identity number IP – Internet Protocol IP Address – A unique number consisting of four parts separated by periods, sometimes called a "dotted quad.," for example: 204.17.29.11, assigned to every computer/workstation connected to the Internet. IP numbers can be "static" (assigned and unchanging) or "dynamic," assigned via DHCP at each and every startup. ISP – Internet Service Provider MAC ID – Media Access Code; located on the module label. NIC – Network Interface Card. RSSI – Received Signal Strength Indication. SCID – SIM Card ID Subnet Mask – A Subnet is a portion of a network that shares a network address with other portions of the network, and is distinguished by a subnet number. The Subnet Mask is a 32-bit address mask used in IP to indicate the bits of an IP address that are being used for the subnet address. - 68 - LYNX Touch Installation and Setup Guide – Index – Features .................................................................... 5 Flexible Callback .................................................... 46 Follow Me Reminder Feature ................................ 51 Follow Me System Announcement ........................ 50 Force Bypass........................................................... 37 General Programming Information....................... 16 Go/No Go Test......................................................... 13 GSM Information.................................................... 40 GSMVLP5 ......................................................... 10, 23 House Identification ............................................... 12 ILP5................................................................... 10, 11 Installer Code ......................................................... 48 Installer Menu ........................................................ 16 Installing Wireless Zones................................. 13, 14 Key/Touchscreen Operation ................................... 48 Keys......................................................................... 12 L5000DM .................................................................. 6 Lack of Usage Notify .............................................. 37 Liquid Crystal Display (LCD) Touch-Screen ........ 15 Loading Factory Defaults....................................... 17 LYNXRCHKIT-SC.................................................... 5 LYNXRCHKIT-SHA................................................. 5 Master Code............................................................ 48 Master Security Code ....................................... 20, 48 Memory of Alarm.................................................... 48 Menu Screens ......................................................... 15 Mounting Base.......................................................... 6 Navigating Menus .................................................. 15 Navigation Keys ..................................................... 15 Operator Commands .............................................. 53 Panic Key/Icons ...................................................... 48 Plug-in Power Supply............................................... 9 Power-Up in Previous............................................. 37 Program Date And Time ........................................ 23 Program Keys ......................................................... 28 Program the Communications Module.................. 24 Program Zones................................ 26, 28, 30, 36, 37 Programming Default Tables... 56, 57, 58, 59, 60, 61 Quick Arm............................................................... 37 Quick Exit ............................................................... 37 Range ...................................................................... 12 Register by Phone................................................... 42 Register Device with PIN....................................... 43 Register Through Alarmnet Direct Website ......... 42 Register Through LYNX Touch Diagnostics ......... 42 Registering The LYNX Touch ................................ 41 Regulatory Agency Statements.............................. 63 Remote Phone Control............................................ 51 Remote Programming ............................................ 46 Remote Programming/Control ............................... 46 Reporter ............................................................ 30, 31 Resident Monitor Zone Types .................................. 5 RF Sniffer Test Mode ............................................. 13 Secondary User Codes ............................................ 49 Security Code Handshake...................................... 46 Security Codes .................................................. 37, 48 Setup Communication............................................ 41 SIA (DC-03)............................................................... 5 SIA Event Code ...................................................... 54 24-Hour Silent Alarm .............................................48 300-03864-1...............................................................5 300-03866..................................................................5 300-04063..............................................................5, 9 300-04065..............................................................5, 9 300-04705..............................................................5, 9 5800 Series Transmitter Loop Numbers ...............14 5800 Series Transmitters ...................................5, 12 5802MN...................................................................12 5802MN2.................................................................12 5804 .........................................................................12 5804BD....................................................................12 5804BDV .................................................................12 5804E ......................................................................12 5805-6......................................................................12 5806 .........................................................................14 5816 .........................................................................12 5817 .........................................................................12 AC Power ..................................................................9 AC Power Loss ..........................................................9 ADEMCO Contact ID .........................................5, 66 Armed System Test ................................................55 Audio Alarm Verification (Two-Way Voice Feature) .......................................53 Auto Stay Arming ...................................................37 Babysitter Code ......................................................49 Backup Battery............................................... 3, 9, 66 Button Transmitters...............................................12 Case Tamper .............................................................5 Change Installer Code............................................20 Communication Modules........................................10 Communications ID Numbers ...............................41 Communications Status .........................................40 Installing/Configuring Communication Modules..10 Contact ID® Codes .................................................54 Contact ID Event Codes .........................................54 Contact ID Reporting .............................................66 Contacting Technical Support................................67 Cross Zone 1/Cross Zone 2......................................37 Cross Zone Delay ...................... 37, 38, 39, 58, 61, 65 Data Encryption .....................................................46 Desktop Mounting ....................................................6 Diagnostics........................................................40, 41 Dialer Delay ......................................................55, 65 DIP Switches...........................................................12 Display Alarm Cancel.............................................37 Display Exit Time...................................................37 Duress Code ............................................................49 Enter Installer Programming Mode ......................17 Enter/Change the Master Code .............................48 Entry Delay1/Entry Delay 2 ..................................37 Entry/Exit Burglary ...............................................18 Ethernet Information .............................................40 Event Log Codes .....................................................54 Exit Delay ............................. 5, 15, 16, 18, 37, 55, 65 Exit Door .................................................................37 Exit Warning ..........................................................37 Exiting Program Mode ...........................................17 Factory Defaults .....................................................45 FCC Statement .......................................................63 - 69 - LYNX Touch Installation and Setup Guide Touch-Screen Display .............................................15 Transmitter Battery Life........................................12 Transmitter Input Type .........................................12 Transmitter Loop Numbers....................................14 Transmitter Supervision ........................................12 Unsupervised Button..............................................12 Unsupervised RF ....................................................12 Update Server .........................................................44 User Menu...............................................................16 Wall Mounting ..........................................................6 Wireless Buttons.....................................................12 Wireless Keypads..........................................5, 12, 13 Wireless Zones ........................................................12 Wiring Connections ..................................................6 World Wide Web Address .......................................67 Zone Programming Default Tables ..................61, 62 Zone Response Type Definitions ............................18 Silent Burglary .......................................................19 Site-Initiated Remote Programming......................46 Sniffer Mode ............................................................55 Sounder ...................................................................36 Specifications ..........................................................66 Station-Initiated Remote Programming ................46 Super High Capacity Battery .................................10 Supervised RF .........................................................12 System Displays......................................................52 System Features .......................................................5 System Operation .............................................48, 49 System Settings ......................................................37 Technical Support ...................................................67 Test Communications .............................................41 Test Ethernet ..........................................................41 Test Mode ................................................................55 Testing the System .................................................55 - 70 - - 71 - EDGE CONNECT (FUTURE USE) REPLACE EVERY FOUR YEARS P/N 300-03864-1/LYNXRCHKIT-SC P/N 300-03866/LYNXRCHKIT-SHA THE LYNX TOUCH CONTROLS ARE COMPATIBLE WITH THE FOLLOWING INTEGRAL RECHARGEABLE BATTERY PACKS: EGND EARTH GROUND STANDARD CAPACITY BATTERY CONNECTOR SUPER HIGH CAPACITY BATTERY CONNECTOR ZONES 2K OHM EOLR HARD WIRED ZONE WEEKLY TESTING IS REQUIRED TO ENSURE PROPER OPERATION OF THIS SYSTEM TAMPER SWITCH GSMVLP5/ILP5 RECEPTACLE TELCO JACK INCOMING PHONE LINE WARNING CONTROL UNIT DELAY-SEC 30 seconds CIRCUIT (ZONE) 02 - 48 ZT16 5806W3 5000-100-SOC-V0 10 seconds SMOKE DETECTOR MODEL DELAY-SEC THIS UNIT MAY BE PROGRAMMED TO INCLUDE AN ALARM VERIFICATION FEATURE THAT WILL RESULT IN A DELAY OF THE SYSTEM ALARM SIGNAL FROM THE INDICATED FIRE CIRCUITS. THE TOTAL DELAY (CONTROL UNIT PLUS SMOKE DETECTORS) SHALL NOT EXCEED 60 SECONDS. NO OTHER INITIATING DEVICES SHALL BE CONNECTED TO THESE CIRCUITS UNLESS APPROVED BY THE LOCAL AUTHORITY HAVING JURISDICTION. EDGE CONNECT (FUTURE USE) POWER SUPPLY CONNECTOR 300-04705 or 300-04065 (300-04063 CANADA) POWER SUPPLY 9V, 2.7A Be sure to observe polarity when connecting the power supply to the terminal strip. IMPORTANT THIS DEVICE COMPLIES WITH PART 15 OF FCC RULES. OPERATION IS SUBJECT TO THE FOLLOWING TWO CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE, AND (2) THIS DEVICE MUST ACCEPT ANY INTERFERENCE RECEIVED, INCLUDING INTERFERENCE THAT MAY CAUSE UNDESIRED OPERATION. POWER GND LYNX TOUCH SERIES SUMMARY OF CONNECTIONS TIP TIP PHONE RING TIP RING RING COMPLIES WITH FCC RULES, PART 68 FCC REGISTRATION No. AC3AL05BL5000 RINGER EQUIVALENCE: 0.5B UL INSTALLATIONS THE MINIMUM WIRE SIZE USED FOR TELEPHONE INSTALLATIONS MUST BE #26 GAGE H/S T PREMISES TELEPHONE H/S R INCOMING PHONE LINE GND NOTE: THE HARDWIRE ZONE CANNOT BEUSED AS A FIRE ZONE. HWZ1 WARNING TO PREVENT RISK OF SHOCK, DISCONNECT TELEPHONE LINE AT TELECOM JACK BEFORE SERVICING THIS UNIT TRIG TRIGGER OUTPUT (NEG) (3ma) LYNX TOUCH SERIES ALSO COMPLIES WITH THE FOLLOWING: CANADIAN STANDARDS ASSOCIATION (CSA) C22.1, CANADIAN ELECTRICAL CODE, PART 1, SAFETY STANDARD FOR ELECTRICAL INSTALLATIONS AND CAN/ULC-S540 INSTALLATION OF RESIDENTIAL FIRE WARNING SYSTEMS. +9VDC THIS EQUIPMENT SHOULD BE INSTALLED IN ACCORDANCE WITH THE NATIONAL FIRE PROTECTION ASSOCIATION STANDARDS ANSI/NFPA 70 NATONAL ELECTRIC CODE AND NFPA 72 NATIONAL FIRE ALARM CODE, CHAPTER 2 (NATIONAL FIRE PROTECTION ASSOC., BATTERY MARCH PARK, QUINCY, MA 02169). PRINTED INFORMATION ESCRIBING PROPER INSTALLATION, EVACUATION PLANNING AND REPAIR SERVICE IS TO BE PROVIDED WITH THIS EQUIPMENT. LYNX Touch Installation and Setup Guide Notes: Connection of the fire alarm signal to a fire alarm headquarters or a central station shall be permitted with the approval of the local authority having jurisdiction. The burglar alarm signal shall not be connected to a police emergency number. The System must be checked by a qualified technician once every three years WARRANTY INFORMATION Fort the latest warranty information, please visit: www.honeywell.com/security/hsc/resources/wa 2 Corporate Center Drive, Suite 100 P.O. Box 9040, Melville, NY 11747 Copyright © 2011 Honeywell International Inc. www.honeywell.com/security Ê800-06834MŠ 800-06834 1/11 Rev. A
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.6 Linearized : Yes Author : E652388 Create Date : 2011:03:08 16:29:04Z Modify Date : 2011:03:10 09:16:16-05:00 Has XFA : No XMP Toolkit : Adobe XMP Core 4.2.1-c043 52.372728, 2009/01/18-15:08:04 Format : application/pdf Creator : E652388 Title : Microsoft Word - 800-06834_ii.doc Creator Tool : PScript5.dll Version 5.2.2 Metadata Date : 2011:03:10 09:16:16-05:00 Producer : Acrobat Distiller 4.05 for Windows Document ID : uuid:a328a0b0-2e07-4230-a80a-719991276046 Instance ID : uuid:17505d8d-7f15-42a6-a9ba-112aacfb7101 Page Count : 72EXIF Metadata provided by EXIF.tools