Ademco THM4000R02 Programmable Thermostat User Manual 69 2426 01 System Installation Guide

Honeywell International Inc Programmable Thermostat 69 2426 01 System Installation Guide

Manual

© 2010 Mitsubishi Electric & Electronics USA, Inc.Suwanee, GA 30024 All Rights Reserved.The three diamond logo is a registered trademarkof Mitsubishi Electric Corporationwww.mitsubishipro.comController Kit Installation ManualMIFH1, MRCH1, MCCH1, MOS169-2426-01Installation guide for:• WirelessReceiverandCable(MIFH1)• RemoteController(MRCH1)• PortableCentralController(MCCH1)• OutdoorAirSensor(MOS1)DISCONNECT POWER BEFORE BEGINNING INSTALLATION. Can cause electrical shock or equipment damage.Must be installed by a trained, experienced technician. Read these instructionscarefully.Failuretofollowtheseinstructionscandamagetheproductorcause a hazardous condition.Installation at a glanceThis document covers linking and installation procedures for the Mitsubishi Split-Zoning Ductless and Ducted Systems' RedLINK™ control devices and accessories.Before you begin, you must attach the cable to the CN105 connector on the indoor unit control board, then follow the steps in this document.Remote controllers are linked to specific indoor units. Each indoor unit must have a dedicated remote controller and wireless receiver.Wireless receiverWireless outdoor air sensorPortable central controllerM32309Remote controller
Wireless System Installation Guide69-2426—01  2M284741 Install batteries in wireless devicesInstallbatteriesinalldevices.Makesurebatteriesareinsertedproperly(seepolaritymarksonthedevices).2 Install cable and receiverM28472ARemote ControllerPortable Central Controller (optional): Install 3 fresh AA batteriesOutdoor air sensor (optional): Install 2 fresh AA lithium batteriesInstall 2 fresh AA batteriesInstall quick reference card1  Before mounting indoor unit, connect cable to the 5-pin CN105 connector on the control board in the indoor unit.2  Mount indoor unit. Route cable to preferred location of the wireless receiver.3  Route cable through hole in base of wireless receiver and attach to 5 pin connector on receiver board.4 Pushtheexcesscablebackthroughtheindoorunit or behind the wireless receiver. Do not cut or modify the cable. Use zip tie connections on back of receiver if needed.5 Mountwirelessreceivernexttotheindoorunit(seebelow)orinaremotelocation.  Mount in the orientations shown. Do not block vents.MCR31400XXOR OR
  3  69-2426—013 Link all devices to wireless network1  Remove cover from wireless receiver.2 VerifyPOWERlightissolidgreen.3 PressandreleasetheCONNECT button.4 IfCONNECTlightdoesnotflash,anotherreceiver or RedLINK wireless adapter may be in wirelesssetupmode.Exitwirelesssetupattheother device.M28925Wireless SetupNextM32308ConnectBackWireless SetupM32307DoneConnectedWireless SetupLink remote controller to wireless networkZone namePresss or t to change the name or location of this zone, then press NEXT.Example:67=MeetingRoomSee complete zone list on page 8.PressCONNECT to establish a link to the wireless network.If E0 or E1 appears, see error codes on page 10.After a brief pause, the confirmation screen at left should be displayed to verify that the wireless connection has been established.PressDONE to display the home screen.POWER LEDSolid Green:Poweredandcommunicationis established.Slow Flashing Green (1 flash/second): Receiver is powered. Waitapproximately30secondsforcommunication to be established between the wireless receiver and the indoor unit. Check cable connection if flashing does not stop after 30 seconds.Fast Flashing Green (5 flashes/second): Error in communication between wireless receiver and the indoor unit. Check cable connection.CONNECT LEDFlashing Green: In wireless setup mode.Solid Green: RedLINK communication is established.Yellow:Pleasewait.Red: RedLINK device is not communicating.Flashingstatuslighttimesoutafter15minutesofinactivity.PressCONNECT again if necessary.
Wireless System Installation Guide69-2426—01  4Link Portable Central Controller to RedLINK™ network (optional)Link outdoor sensor to RedLINK™ network (optional)CONNECTWIRELESS SETUPM28481M28483NOYESCONNECT MORE?M284821 MakesuretheCONNECTlightonthewireless receiver is flashing.2 PressCONNECTatthePortableCentralController. There will be a short delay as the PortableCentralControllerseeksasignalfrom the wireless network.3 Whenthescreendisplays"Connected,"press DONE.4 PressNOatthenextscreentosaveandexit.(OrpressYES and repeat steps 1-4 to link anotherreceiver.)1 MakesuretheCONNECTlightonthewireless receiver is flashing.2 PressandreleasetheCONNECT button on the back of the sensor.3  Check remote controller to verify that the outdoor sensor is working. After about 15 seconds, the remote controller should display outdoor temperature and humidity.Presstolinkanother receiverPresstosaveandexitIf E1 appears, see error codes on page 10.The linking procedure may time out if there is no keypress within 15 minutes. To begin again, press and holdtheblankspace(orarrow,ifpresent)inthelowerrightcornerofthescreenuntilthedisplaychanges(about3seconds).Pressandrelease
  5  69-2426—01Exit wireless setup4 Customize remote controller (installer setup)PressandreleasetheCONNECTbuttonatthewirelessreceivertoexitwirelesssetup(lightshouldstopflashingandremainsolid).Replacecoveronwirelessreceiver.Followthestepsbelowtobegininstallersetup.Ateachfunctionscreen,presss or t to change the setting as desired, then press NEXTtoadvancetothenextfunctionscreen.Seetablesonpages6-8foradescriptionofoptionsforeachfunction.Presss or t to change setting(seetablesonpages6-8).PressNEXTtodisplaynextfunction screen.Note:Thewirelessreceiverwillautomaticallyexitwirelesssetupafter15minutesof inactivity.Note:Ifinstallingmorethanonereceiver,youmustexitwirelesssetupbeforeinstalling remote controller and additional receiver.To begin, press and hold the FAN and s buttonsuntilthedisplaychanges."WAIT"will be displayed for up to 40 seconds.FunctionPressDONEtosave&exit.SettingM28927BackDoneNextM28488AM289871Fan
Wireless System Installation Guide69-2426—01  6Installer setup tablesSetup function Settings & options (factory default in bold)101 Unit automatically restarts after power  outage1OFF2ON3 Not Supported103 Ventilation Air 1 Not Supported2IDUdoesnotintakeoutdoorairthroughLOSSNAY3IDUdoesintakeoutdoorairthroughLOSSNAY104 Power Voltage 1 230V2 208V3 Not Supported105 Auto energy-savings operation1ON2OFF3 Not Supported107 Change Filter Duration 1100Hours22500Hours3OFF108 Auto Fan (speed setting) 1 Quiet2 Standard3HighCeiling109 No. of Air Outlets (PLA only)1 4 directions2 3 directions3 2 directions110 High Performance Filter Installed1NO2YES3 Not Supported111 Airflow Direction Settings1NoVanes(orVane#3forPLA)2Vane#1Setting(typicallykeptatthedefaultsetting)3Vane#2Setting(typicallykeptatthedefaultsetting)115 Indoor Unit Coil Frost Prevention Temperature136°F(2°C)237°F(3°C)3 Not Supported117 Defrost Control 1 Standard2HighHumidity3 Not Supported123 Airflow Oscillate Mode 1 Not Available2 Available3 Not Supported124 Heating Mode Temperature Offset1ON2OFF3 Not Supported125 Thermal Off Fan Operation (Heat Mode)1ExtraLow2 Stop3SelectableFanSpeed127 Thermal Off Fan Operation (Cool Mode)1SelectableFanSpeed2 Stop3 Not Supported128 Display System Error 1ON2OFF3 Not SupportedDefaultsettingsforSetupfunctions101-128areautomaticallydeterminedbytheHVACequipment.Itmaytakeupto40secondstoentersetup,and30secondstoexitsetup.
  7  69-2426—01Installer setup tablesSetup function Settings & options (factory default in bold)134 Central Controller  (AG-150 or similar) Present0 Not Installed 1 Installed 136 Residential/Commercial 1 Commercial0 Residential138 Permanent Hold Lock (Non-programmable)0 OFF (Programmable)1ON(Non-programmable)139 Fahrenheit/Celsius Display0 Fahrenheit1 Celsius140 Commercial Override Duration3 3 Hours0OFF1–12 1–12Hours142 System Type 0 Heat & Cool (Heat Pump)1CoolOnly144 System Changeover 1 System Changeover (Auto, Heat, Off, Cool)0ManualChangeover(Heat,Off,Cool)2SystemChangeoverOnly(AutoOnly)3 System Changeover Single Setpoint - only with AG-150 or similar(Auto,Heat,Off,Cool)145 System Changeover Deadband Value3 3 °F (2 °C)2–8 2–8°F(1.5–4.5°C)146 Drying Mode 0 OFF1ON148 Schedule Format 0 5-21 5-1-1150 Optimal Start 1 ON0OFF152 Scheduled Off 0 Not Shown  * See page 9 for feature information1 Shown154 Power Off Timer ("Sleep Timer")0 Not Shown1Resumeoperationatnextscheduledperiod2PermanentlyOffuntiluserchangesSystemmode160 Full Lockout 0 No1Yes162 Lockout On/Off 0 No1Yes164 Lockout System Mode (Heat, Cool, Auto, Drying)0 No1Yes165 Lockout Fan Mode 0 No1Yes166 Lockout Setpoint 0 No1Yes168 Lockout Set Clock/Day/Schedule0 No1Yes170 Max Heat Setpoint 90 90 °F (32 °C)  *  Subject to40–89 40to89°F(4.5to31.5°C)   HVAC Equipment172 Min Cool Setpoint 50 50 °F (10 °C)  *  Subject to51–99 51to99°F(10.5to37°C)    HVAC Equipment173 Sensing Location 1 Sense at Remote Controller0 Sense at Indoor Unit174 Indoor Temperature Display Offset0 0 °F (0 °C)-3to3°F(-1.5to1.5°C)
Wireless System Installation Guide69-2426—01  8Installer setup tablesSetup function Settings & options (factory default in bold)176 Outdoor Temperature Display Offset0 0 °F (0 °C)-5to5°F(-2.5to2.5°C)178 Outdoor Humidity Display Offset3 0%0 -15%1 -10%2 -5%4 5%5 10%615%192 Zone Name 52 THERMOSTAT 34 MASTER BED1 BASEMENT 35 MEDIAROOM2BATHROOM 36 MUSICROOM3BATHROOM1 37 NURSERY4BATHROOM2 38 OFFICE5BATHROOM3 39 OFFICE16 BEDROOM 40 OFFICE27 BEDROOM1 41 PANTRY8BEDROOM2 42 PLAYROOM9BEDROOM3 43 POOLROOM10 BEDROOM4 44 PORCH11 BOATHOUSE 45 RECROOM12 BONUSROOM 46 SEWINGROOM13 COMPUTERROOM 47 SPA14 DEN 48 STORAGEROOM15 DININGROOM 49 STUDIO16 EXERCISEROOM 50 SUNROOM17 FAMILYROOM 51 THEATER18 FIREPLACE 52 THERMOSTAT19 FOYER 53 UPPERLEVEL20 GAMEROOM 54 UTILITYROOM21 GARAGE 55 WALKINCLOSET22 GREATROOM 56 WINECELLAR23 GUESTROOM 57 WORKSHOP24 GYM Commercial Names25 KID’SROOM 64 CONFERENCERM26 KITCHEN 65 DRESSINGROOM27 KITCHEN1 66 MACHINEROOM28 KITCHEN2 67 MEETINGROOM29 LAUNDRYROOM 68 OPENAREA130 LIBRARY 69 OPENAREA231 LIVINGROOM 70 SERVER 132 LOWERLEVEL 71 SERVER 233 MASTERBATH 72 STOCKROOM194 Wireless Setup 1 Remote controller is connected to wireless system0 Disconnect Remote controller from wireless system198 Reset Schedule to Factory Defaults0 No1Yes199 Reset Installer Setup to Factory Defaults0 No1Yes
  9  69-2426—01Special functionsInstaller testFollowtheprocedurebelowtotestforproperoperation.M28488ATo begin, press and hold the s and t buttons untilthedisplaychanges(about3seconds).Presss or t to check system statusPressNEXT to advancetonexttestPressDONE to terminate system testM32306NextBackDoneSystem test number System statusSystem test  System status 02  Wireless test 0 Off1 Testradiosignal(afterabriefpause,screendisplays5-10toshowsignalstrength;5orhigherrecommended) 50  Cool/Heat test 0 Off1  Cool2 Heat 70  Configuration Data 1 (remotecontroller)71 Softwarerevisionnumber(majorrevisions)72 Softwarerevisionnumber(minorrevisions)73 Configurationidentificationcode(major)74 Configurationidentificationcode(minor)75 Productionconfigurationdatecode(week)76 Productionconfigurationdatecode(year) 80  Configuration Data 2 (remotecontroller)81 Softwarerevisionnumber(majorrevisions)82 Softwarerevisionnumber(minorrevisions)83 Softwarerevisionnumber(buildrevisions) 90  Configuration Data 1 (wirelessreceiver)91 Softwarerevisionnumber(majorrevisions)92 Softwarerevisionnumber(minorrevisions)93 Softwarerevisionnumber(buildrevisions) 95  Configuration Data 2 (wirelessreceiver)95 Softwarerevisionnumber(majorrevisions)96 Softwarerevisionnumber(minorrevisions)97 Softwarerevisionnumber(buildrevisions)Commercial Override (SetupFunction140):Allowsanemployeeduringanunoccupiedperiodto temporarily activate an occupied temperature. Each press of HOLDextendstheoccupiedtemperatureout1hour(orasinstalled).Optimal Start (SetupFunction150):Allowstheremotecontrollerto“learn”howlongtheequipment will take to reach programmed temperature settings, so the temperature is reached at the scheduled time.Scheduled Off (SetupFunction152):Allowstheusertoscheduleaperiodwherethesplit-zoningsystemiscompletelyoffandresumesoperationatthenextscheduledperiod.Power Off Timer (SetupFunction154):Allowsusertoscheduleindoorunitcompletelyoffforoneinstance: FollowScheduleOption:indoorunitwillresumeoperationatthenextscheduledperiod. PermanentlyOffOption:indoorunitwillremainoffindefinitelyuntiltheuserchangesthesystemmode.
Wireless System Installation Guide69-2426—01  10Outdoor sensor (optional)5 Mount remote controller & outdoor sensor1  Separate the wallplate from the remote controller.2  Mount the wallplate using the included screws and anchors 5 feet from the floor on an interior wall. If the remote controller is configured to sense indoor temperature, mount in the same room as the indoor unit. Drill3/16"holesfordrywall. Drill7/32"holesforplaster.3  Snap the remote controller to the wallplate on the wall.M28491M28492Mountthesensoronaverticalexteriorwall,atleast6inchesbelowanyoverhang. Choose a location protected from direct sunlight.Placesensorsecurelyin bracket, facing away from wall.RedLINK™ error codesE0 27  Verify device temperature is within operating range. If within range for at least 30 minutes and problem persists, replace Remote Controller.E0 91  Communication was established between wireless receiver and the indoor unit, but communication has been lost for 10 minutes. Check cable connection. Try replacing the cable.E1 29  Attempting to connect incompatible wireless devices.E1 34  Low signal strength. Move wireless device to a different location and try again.E1 38  Make sure Connect light on wireless receiver is flashing and you are 2+ feet away from wireless receiver.E1 54  Indoor unit does not support wireless receiver.Forfulllistoferrorcodes,pleaserefertoyourequipment'stechnicalservicemanual.
  11  69-2426—01Replacing system componentsNote:OnlyuseMitsubishiElectriccomponentsorotherdesignatedcomponentsforinstallation.Failuretocomplymaydamagetheproductorcauseahazardouscondition.Remote ControllerTo replace a remote controller, install batteries and follow the procedures on page 3tolinkittothewirelessnetwork.Ifnecessary,modifysettingsasneeded(seetablesonpages6–8).Portable Central Controller & outdoor sensorToreplaceaPortableCentralControlleroroutdoorairsensor,installbatteriesandfollow the procedures on page 4 to link it to the wireless network.Wireless receiverAfter installing a new wireless receiver, you must re-set the remote controller and PortableCentralControllertocommunicatewiththenewequipment,asdescribedbelow.Removing all wireless devices:1 Pressandhold the CONNECT button on the wireless receiver for 10 seconds.2  To reconnect, see procedure on page 3.Attheremotecontroller:1 Pressandhold the FAN and s buttons for 3 seconds until display changes. "WAIT"willbedisplayedforupto17seconds.2 PressNEXTuntilFunction194isdisplayed(wirelesssetup).3 PressttochangeFunction194settingto0(disconnectfromoldwirelessreceiver).4 Followtheproceduresonpage3tolinktonewwirelessreceiver.AtthePortableCentralController:1 Pressandholdtheblankspace(orarrowifpresent)inthelowerrightcornerofthescreenuntilthedisplaychanges(about3seconds).2 PressREMOVE, then YES to disconnect from old wireless receiver.3 Followtheprocedureonpage4tolinktonewwireless receiver.
© 2010 Mitsubishi Electric & Electronics USA, Inc.Suwanee, GA 30024 All Rights Reserved.The three diamond logo is a registered trademarkof Mitsubishi Electric Corporation69-2426—01M.S.11-10PrintedinU.S.A.Regulatory informationFCC Compliance Statement (Part 15.19) (USA only) ThisdevicecomplieswithPart15oftheFCCRules.Operationissubjecttothefollowingtwoconditions:1  This device may not cause harmful interference, and2  This device must accept any interference received, including interference that may cause undesired operation.FCC Warning (Part 15.21) (USA only) Changesormodificationsnotexpresslyapprovedbythepartyresponsibleforcompliancecouldvoidtheuser’sauthoritytooperate the equipment.FCC Interference Statement (Part 15.105 (b)) (USA only) ThisequipmenthasbeentestedandfoundtocomplywiththelimitsforaClassBdigitaldevice,pursuanttoPart15oftheFCCRules.Theselimitsaredesignedtoprovidereasonableprotectionagainstharmfulinterferenceinaresidentialinstallation.This equipment generates uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions,maycauseharmfulinterferencetoradiocommunications.However,thereisnoguaranteethatinterferencewillnotoccur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one of the following measures:• Reorientorrelocatethereceivingantenna.• Increasetheseparationbetweentheequipmentandreceiver.• Connecttheequipmentintoanoutletonacircuitdifferentfromthattowhichthereceiverisconnected.• Consultthedealeroranexperiencedradio/TVtechnicianforhelp.Wireless receiver, remote controller and outdoor sensor TocomplywithFCCandIndustryCanadaRFexposurelimitsforgeneralpopulation/uncontrolledexposure,theantenna(s)usedfor these transmitters must be installed to provide a separation distance of at least 20 cm from all persons and must not be co-locatedoroperatinginconjunctionwithanyotherantennaortransmitter.Portable Central Controller ThisportabletransmitterwithitsantennacomplieswithFCCandIndustryCanadaRFexposurelimitsforgeneralpopulation/uncontrolledexposure.Thisdevicemustnotbeco-locatedoroperatinginconjunctionwithanyotherantennaortransmitter.Section 7.1.5 of RSS-GEN Operationissubjecttothefollowingtwoconditions:1  this device may not cause interference, and2  this device must accept any interference, including interference that may cause undesired operation of the device.Specifications & replacement partsOperating Ambient TemperatureRemote Controller:32to120°F(0to48.9°C)Portable Central Controller:32to120°F(0to48.9°C)Wireless receiver:-40to165°F(-40to73.9°C)Outdoor air sensor:-40to140°F(-40to60°C)Operating Relative HumidityRemote Controller:5%to90%(non-condensing)Portable Central Controller:5%to90%(non-condensing)Wireless receiver:5%to95%(non-condensing)Outdoor air sensor:0%to100%(condensing)Physical Dimensions(height,width,depth)Remote Controller:3-9/16x5-13/16x1-1/2inches(91x147x38mm)Wireless receiver:6-7/16x3-1/4x1-5/16inches(164x82.5x34mm)Outdoor air sensor:5x3-1/2x1-11/16inches(127x89x43mm)Portable Central Controller:6-1/4x3-1/8x1-5/8inches(158.2x79.9x42mm)Item  Part NumberPortableCentralController MCCH1Outdoorairsensor MOS1RemoteController MRCH1ReceiverandCable MIFH1Cable  MRC1Accessories & Replacement Parts

Navigation menu