Adt Security Services Unimode 9600 Users Manual Adtuni9600_combenglC0
51336 51336 AlarmHow.net Library
9600 to the manual c714076d-578e-4935-baa5-43f0e6098e67
2015-02-02
: Adt-Security-Services Adt-Security-Services-Unimode-9600-Users-Manual-413053 adt-security-services-unimode-9600-users-manual-413053 adt-security-services pdf
Open the PDF directly: View PDF
.
Page Count: 148
| Download | |
| Open PDF In Browser | View PDF |
ADT Security Services, Inc. One Town Center Road Boca Raton, FL 33431 Phone: (561) 988-3600 FAX: (561) 988-3675 Unimode9600 Addressable Fire Alarm Control Panel Programming, Installation, Maintenance and Operating Instruction Manual IMPORTANT! The Signaling Line Circuit Wiring Manual Document #51520 must be referenced in addition to this manual when installing or servicing the Fire Alarm Control Panel. Document #51336 11/06/01 Revision: P/N 51336:C C ECN 01-535 Fire Alarm System Limitations While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance! An automatic fire alarm system–typically made up of smoke detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control with remote notification capability–can provide early warning of a developing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire. Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Rate-of-rise heat detectors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested at least once per year by a qualified fire protection specialist. Heat detectors are designed to protect property, not life. The Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premise following the recommendations of the current edition of the National Fire Protection Association Standard 72 (NFPA 72), manufacturer's recommendations, State and local codes, and the recommendations contained in the Guide for Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers. A study by the Federal Emergency Management Agency (an agency of the United States government) indicated that smoke detectors may not go off in as many as 35% of all fires. While fire alarm systems are designed to provide early warning against fire, they do not guarantee warning or protection against fire. A fire alarm system may not provide timely or adequate warning, or simply may not function, for a variety of reasons: Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in or behind walls, on roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a building. A second-floor detector, for example, may not sense a first-floor or basement fire. Particles of combustion or "smoke" from a developing fire may not reach the sensing chambers of smoke detectors because: • Barriers such as closed or partially closed doors, walls, or chimneys may inhibit particle or smoke flow. • Smoke particles may become "cold," stratify, and not reach the ceiling or upper walls where detectors are located. • Smoke particles may be blown away from detectors by air outlets. • Smoke particles may be drawn into air returns before reaching the detector. The amount of "smoke" present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the detectors will not go into alarm. Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic sensing chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire. Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches (especially in bedrooms), smoking in bed, and violent explosions (caused by escaping gas, improper storage of flammable materials, etc.). LimWarLg.p65 01/10/2000 IMPORTANT! Smoke detectors must be installed in the same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling, and/or power. If detectors are not so located, a developing fire may damage the alarm system, crippling its ability to report a fire. Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building. Any warning device may fail to alert people with a disability or those who have recently consumed drugs, alcohol or medication. Please note that: • Strobes can, under certain circumstances, cause seizures in people with conditions such as epilepsy. • Studies have shown that certain people, even when they hear a fire alarm signal, do not respond or comprehend the meaning of the signal. It is the property owner's responsibility to conduct fire drills and other training exercise to make people aware of fire alarm signals and instruct them on the proper reaction to alarm signals. • In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss. A fire alarm system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have been properly maintained and replaced regularly. Equipment used in the system may not be technically compatible with the control. It is essential to use only equipment listed for service with your control panel. Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled. For added protection against telephone line failure, backup radio transmission systems are recommended. The most common cause of fire alarm malfunction is inadequate maintenance. To keep the entire fire alarm system in excellent working order, ongoing maintenance is required per the manufacturer's recommendations, and UL and NFPA standards. At a minimum, the requirements of Chapter 7 of NFPA 72 shall be followed. Environments with large amounts of dust, dirt or high air velocity require more frequent maintenance. A maintenance agreement should be arranged through the local manufacturer's representative. Maintenance should be scheduled monthly or as required by National and/ or local fire codes and should be performed by authorized professional fire alarm installers only. Adequate written records of all inspections should be kept. Installation Precautions Adherence to the following will aid in problem-free installation with long-term reliability: WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all sources of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until this manual is read and understood. CAUTION - System Reacceptance Test after Software Changes. To ensure proper system operation, this product must be tested in accordance with NFPA 72 Chapter 7 after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring. All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified. This system meets NFPA requirements for operation at 0-49° C/32-120° F and at a relative humidity of 85% RH (noncondensing) at 30° C/86° F. However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and all peripherals be installed in an environment with a nominal room temperature of 15-27° C/60-80° F. Verify that wire sizes are adequate for all initiating and indicating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage. Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to lightning-induced transients. Although no system is completely immune from lightning transients and interferences, proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Services Department if any problems are anticipated or encountered. Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits. Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, and printed circuit board location. Do not tighten screw terminals more than 9 in-lbs. Over-tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal. Though designed to last many years, system components can fail at any time. This system contains static-sensitive components. Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body. Use static-suppressive packaging to protect electronic assemblies removed from the unit. Follow the instructions in the installation, operating, and programming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation by authorized personnel. FCC Warning WARNING: This equipment generates, uses, and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual, may cause interference to radio communications. It has been tested and found to comply with the limits for class A computing device pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference, in which case the user will be required to correct the interference at his own expense. Canadian Requirements This digital apparatus does not exceed the Class A limits for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications. Le present appareil numerique n'emet pas de bruits radioelectriques depassant les limites applicables aux appareils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edicte par le ministere des Communications du Canada. LimWarLg.p65 01/10/2000 Notes 4 Unimode 9600 PN 51336:C 11/06/01 Table of Contents SECTION 1: Product Description ........................................................................................................................12 1.1: Inventory .....................................................................................................................................................12 1.2: Features and Options ...................................................................................................................................12 1.3: Specifications ..............................................................................................................................................14 1.3.1: Current Availability...........................................................................................................................15 1.4: Controls and Indicators ...............................................................................................................................16 1.5: Circuits ........................................................................................................................................................17 1.6: Components.................................................................................................................................................17 1.6.1: Intelligent Addressable Detectors: Newer Series..............................................................................18 1.6.2: Intelligent Addressable Modules: Newer Series ...............................................................................19 1.6.3: 300 Series Intelligent Addressable Devices......................................................................................20 1.6.4: Addressable Device Accessories.......................................................................................................20 1.7: Optional Modules ........................................................................................................................................20 1.8: Accessories..................................................................................................................................................21 1.8.1: PK-9600 Programming Utility..........................................................................................................21 1.8.2: Dress Panel........................................................................................................................................21 1.8.3: Battery Box .......................................................................................................................................21 1.8.4: ADT-CHG-120 Battery Charger.......................................................................................................22 1.8.5: Annunciators .....................................................................................................................................22 1.9: Getting Started.............................................................................................................................................23 SECTION 2: Installation .......................................................................................................................................24 2.1: Mounting .....................................................................................................................................................24 2.2: Power...........................................................................................................................................................27 2.2.1: AC Power and Earth Ground Connection.........................................................................................27 2.2.2: Battery Power....................................................................................................................................27 2.2.3: DC Power Output Connection ..........................................................................................................27 2.3: Relays ..........................................................................................................................................................28 2.4: Notification Appliance Circuits ..................................................................................................................28 2.5: UL Power-limited Wiring Requirements ....................................................................................................29 2.6: Optional Modules and Devices ...................................................................................................................30 2.6.1: 4XTMF Transmitter Module Installation..........................................................................................31 2.6.2: Auxiliary Trouble Input (J16 & J17).................................................................................................32 2.6.3: SLC-2 Expander Module ..................................................................................................................33 2.6.4: Printer/PC..........................................................................................................................................34 2.6.5: Digital Communicator and Annunciators .........................................................................................35 2.6.5.1 ADT-UDACT Digital Alarm Communicator/Transmitter .....................................................35 2.6.5.2 ADT-ACM-8R Relay Control Module ...................................................................................35 2.6.5.3 BRKT-9600 Universal Bracket Installation ............................................................................35 2.6.5.4 ADT-ACS and ADT-AFM Series Annunciators ....................................................................37 SECTION 3: Programming ...................................................................................................................................38 3.1: Programming Data Entry ............................................................................................................................38 3.2: User Programming ......................................................................................................................................39 3.3: Initial Power-up...........................................................................................................................................40 3.4: Programming Screens Description..............................................................................................................40 3.5: Programming and Passwords ......................................................................................................................40 3.6: Master Programming Level.........................................................................................................................42 3.6.1: Point Program ...................................................................................................................................43 3.6.1.1 Detector Programming ............................................................................................................43 3.6.1.1.1 Add Detector ........................................................................................................................43 3.6.1.1.2 Delete Detector ....................................................................................................................44 3.6.1.1.3 Edit Detector ........................................................................................................................44 3.6.1.2 Module Programming .............................................................................................................53 Unimode 9600 P/N: 51336:C 11/06/01 5 Table of Contents 3.6.1.2.1 Add Module .........................................................................................................................53 3.6.1.2.2 Delete Module ......................................................................................................................54 3.6.1.2.3 Edit Module Screen for Monitor Module .............................................................................54 3.6.1.2.4 Edit Module Screen for Control Modules ............................................................................63 3.6.2: Zone Setup.........................................................................................................................................70 3.6.2.1 Enable ......................................................................................................................................70 3.6.2.2 Disable .....................................................................................................................................71 3.6.2.3 Zone 97, 98 and 99 ..................................................................................................................71 3.6.2.4 Zones Installed ........................................................................................................................72 3.6.2.5 Zones Enabled .........................................................................................................................72 3.6.2.6 Zones Disabled ........................................................................................................................72 3.6.2.7 Zone Type ...............................................................................................................................73 3.6.3: Loop Setup ........................................................................................................................................74 3.6.3.1 Style .........................................................................................................................................74 3.6.3.2 Loop Protocol ..........................................................................................................................74 3.6.4: System Setup .....................................................................................................................................75 3.6.4.1 Trouble Reminder ...................................................................................................................75 3.6.4.2 Banner .....................................................................................................................................76 3.6.4.3 Time-Date ...............................................................................................................................77 3.6.4.3.1 Time .....................................................................................................................................77 3.6.4.3.2 Date ......................................................................................................................................78 3.6.4.3.3 Clock Format ........................................................................................................................78 3.6.4.3.4 Daylight Savings Time .........................................................................................................78 3.6.4.4 Timers .....................................................................................................................................79 3.6.4.4.1 PAS (Positive Alarm Sequence) Delay ................................................................................79 3.6.4.4.2 Pre-signal Delay ...................................................................................................................80 3.6.4.4.3 Waterflow Delay ..................................................................................................................80 3.6.4.4.4 AC Loss Delay .....................................................................................................................81 3.6.4.5 NAC (Notification Appliance Circuit) ....................................................................................81 3.6.4.5.1 Enabled .................................................................................................................................82 3.6.4.5.2 Type ......................................................................................................................................83 3.6.4.5.3 Silenceable ...........................................................................................................................83 3.6.4.5.4 Auto Silence .........................................................................................................................84 3.6.4.5.5 Coding ..................................................................................................................................84 3.6.4.5.6 Zone ......................................................................................................................................85 3.6.4.5.7 Silence Inhibited ...................................................................................................................85 3.6.4.5.8 Synced Type .........................................................................................................................85 3.6.4.6 Relays ......................................................................................................................................86 3.6.5: Autoprogram .....................................................................................................................................87 3.6.6: Verify Loops ......................................................................................................................................88 3.6.7: History...............................................................................................................................................88 3.6.7.1 View Events ............................................................................................................................89 3.6.7.2 Erase History ...........................................................................................................................89 3.6.8: Walktest .............................................................................................................................................90 3.6.9: Option Modules................................................................................................................................91 3.6.9.1 Annunciators/UDACT ............................................................................................................91 3.6.9.2 Printer/PC ................................................................................................................................92 3.6.10: Password Change ............................................................................................................................93 3.6.11: Clear Program..................................................................................................................................94 3.6.12: Program Check................................................................................................................................95 3.7: Maintenance Programming Level ...............................................................................................................97 3.7.1: Disable Point .....................................................................................................................................98 3.7.2: History...............................................................................................................................................99 3.7.3: Program Check..................................................................................................................................100 3.7.4: Walktest .............................................................................................................................................101 6 Unimode 9600 P/N: 51336:C 11/06/01 Table of Contents 3.7.5: System ...............................................................................................................................................101 3.7.6: Zone Setup ........................................................................................................................................103 SECTION 4: Operating Instructions ....................................................................................................................105 4.1: Panel Control Buttons .................................................................................................................................105 4.1.1: Acknowledge/Step ............................................................................................................................105 4.1.2: Alarm Silence....................................................................................................................................105 4.1.3: Drill/Hold 2 Sec ................................................................................................................................105 4.1.4: Reset..................................................................................................................................................105 4.2: LED Indicators ............................................................................................................................................106 4.3: Normal Operation........................................................................................................................................107 4.4: Trouble Operation .......................................................................................................................................107 4.5: Alarm Operation..........................................................................................................................................109 4.6: Supervisory Operation.................................................................................................................................110 4.7: Process Monitor Operation..........................................................................................................................111 4.8: Hazard Condition Operation .......................................................................................................................111 4.9: Medical Alert Condition Operation.............................................................................................................111 4.10: NAC Operation .........................................................................................................................................111 4.11: Programmed Zone Operation ....................................................................................................................112 4.12: Disable/Enable Operation .........................................................................................................................112 4.13: Waterflow Circuits Operation ...................................................................................................................112 4.14: Detector Functions ....................................................................................................................................112 4.15: Time Functions: Real-Time Clock ............................................................................................................112 4.16: Synchronized NAC Operation ..................................................................................................................113 4.17: Coded Operation .......................................................................................................................................113 4.18: Presignal ....................................................................................................................................................113 4.19: Positive Alarm Sequence ..........................................................................................................................114 4.20: Special System Timers ..............................................................................................................................115 4.20.1: Silence Inhibit Timer.......................................................................................................................115 4.20.2: Autosilence Timer ...........................................................................................................................115 4.20.3: Trouble Reminder ...........................................................................................................................115 4.20.4: Waterflow Retard Timer..................................................................................................................115 4.20.5: Alarm Verification (None or Two Minutes)....................................................................................116 4.21: Walktest .....................................................................................................................................................116 4.22: Read Status ................................................................................................................................................117 4.22.1: System Point ...................................................................................................................................118 4.22.2: Zones ...............................................................................................................................................119 4.22.3: Power...............................................................................................................................................120 4.22.4: Trouble Reminder ...........................................................................................................................120 4.22.5: Timers..............................................................................................................................................121 4.22.6: NAC ................................................................................................................................................121 4.22.7: Relays..............................................................................................................................................122 4.22.8: Program Check................................................................................................................................122 4.22.9: History.............................................................................................................................................122 4.22.10: Annunciators .................................................................................................................................123 4.22.11: Printer/PC ......................................................................................................................................123 4.22.12: Print ...............................................................................................................................................124 4.22.13: Time-Date......................................................................................................................................126 SECTION 5: Power Supply Calculations .............................................................................................................127 5.1: Overview .....................................................................................................................................................127 5.2: Calculating the AC Branch Circuit .............................................................................................................127 5.3: Calculating the System Current Draw.........................................................................................................128 5.3.1: Overview ...........................................................................................................................................128 5.3.2: How to Use Table 5.3 on page 129 to Calculate System Current Draw ...........................................128 5.4: Calculating the Battery Size ........................................................................................................................130 Unimode 9600 P/N: 51336:C 11/06/01 7 Table of Contents 5.4.1: NFPA Battery Requirements .............................................................................................................130 5.4.2: Selecting and Locating Batteries.......................................................................................................130 APPENDIX A: Software Zones ............................................................................................................................131 A.1: Correlations ...............................................................................................................................................131 APPENDIX B: Default Programming .................................................................................................................139 APPENDIX C: Wire Requirements .....................................................................................................................140 8 Unimode 9600 P/N: 51336:C 11/06/01 It is imperative that the installer understand the requirements of the Authority Having Jurisdiction (AHJ) and be familiar with the standards set forth by the following regulatory agencies: • • • Underwriters Laboratories Standards NFPA 72 National Fire Alarm Code CAN/ULC - S527M Standard for Control Units for Fire Alarm Systems Before proceeding, the installer should be familiar with the following documents. NFPA Standards NFPA 72 National Fire Alarm Code NFPA 70 National Electrical Code Underwriters Laboratories Documents: UL 38 Manually Actuated Signaling Boxes UL 217 Smoke Detectors, Single and Multiple Station UL 228 Door Closers–Holders for Fire Protective Signaling Systems UL 268 Smoke Detectors for Fire Protective Signaling Systems UL 268A Smoke Detectors for Duct Applications UL 346 Waterflow Indicators for Fire Protective Signaling Systems UL 464 Audible Signaling Appliances UL 521 Heat Detectors for Fire Protective Signaling Systems UL 864 Standard for Control Units for Fire Protective Signaling Systems UL 1481 Power Supplies for Fire Protective Signaling Systems UL 1610 Central Station Burglar Alarm Units UL 1638 Visual Signaling Appliances UL 1971 Signaling Devices for Hearing Impaired CAN/ULC - S524M Standard for Installation of Fire Alarm Systems CAN/ULC S527M Standard for Control Units for Fire Alarm Systems Other: EIA-232E Serial Interface Standard EIA-485 Serial Interface Standard NEC Article 250 Grounding NEC Article 300 Wiring Methods NEC Article 760 Fire Protective Signaling Systems Applicable Local and State Building Codes Requirements of the Local Authority Having Jurisdiction (LAHJ) ADT Documents: ADT Device Compatibility Document ADT-SLC Wiring Manual ADT-AFM-16AT & AFM-32A ADT-AFM-16A Annunciator ADT-ACS Series Annunciators ADT-UDACT Communicator/Transmitter ADT-CHG-120 Battery Charger ADT-LDM Series Lamp Driver Modules LCD-80F Remote Fire Annunciator ADT-ACM-8R Relay Control Module Unimode 9600 PN 51336:C 11/06/01 Document #51352 Document #51520 Document #A15048 Document #A15207 Document #51353 Document #50934 Document #50938 Document #51351 Document #51338 Document #51356 9 10 Unimode 9600 PN 51336:C 11/06/01 9600lay3.cdr CAUTION! 2 1 + + - B A A B B A A B + + - - + + - - J17 DISABLE GND FLT JP2 TB4 4XTMF OPT BD 120 VAC, 60 HZ, 3.2 amps HOT NEUT EARTH TB1 LCD DISPLAY A Fail Safe Trouble NC NO C relay switches to the NO position during trouble conditions and under loss of all power. J8 OPT DACT KEYPAD I/F J2 JP5 TB7 Cut this jumper to enable Supervisory relay when 4XTMF module is installed shield Connector for Optional 2nd Signalling Line Circuit Module PS2 Keyboard Interface Flash Memory Load Enable Switch. UP is normal position for switch. DOWN position allows loading of factory software upgrades J7 SW1 Cut this jumper to supervise the 4XTMF module when installed (see JP10 & JP11) 24 VDC, 25 Amp Hour maximum Battery +BATTERY- TB2 J6 JP6 CUT TO MONITOR 4XTMF J11 TB6 (*Factory default relay programming as shown on circuit board) TB5 DB9F 9 8 7 6 5 4 3 2 1 OR 5 4 3 2 1 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 For EDP-listed equipment or personal computer with FACP Upload/Download Utility. 50 foot maximum within same room. EIA-232 to printer or personal computer J3 OPT SLC TB8 (option to DB-25) T R D G XC T N V R D TERM Red (EIA-485) ACS (EIA-485) White to LCD-80F TB7 to ACS Annunc. Green or UDACT-F Black (power-limited, supervised) T R D G I I O O X C T N N N U U V R D + - T T B A B AA B Alarm* Trouble Supervisory* + + - + + NO NC C NC NO C NO NC C Contacts shown below in normal condition (AC power with no alarm, trouble or supervisory activity). Contact Ratings: 2.0 amps @ 30 VDC (resistive) 0.5 amps @ 30 VAC (resistive) 2 Programmable Relays & 1 Fixed Trouble Relay Connectors for 4XTMF option module J16 CB1 + + + Cut this jumper to disable the FACP battery charger when using external charger. - J10 + + + + ELR 4.7K, ½W NAC #2 NAC #1 Style Y or Style Y (shown) Style Z (shown) or Style Z 3.0 amps max. 3.0 amps max. Notification Appliance Circuits To disable ground fault detection, remove jumper/shunt from JP2 - 6 5 CUT TO DISABLE LOCAL CHARGER JP3 TB3 4 3 HIGH VOLTAGE Resettable Power - 24 VDC filtered, power-limited (3.00 amps maximum) to smoke detectors (IDC). Supervision required. Nonresettable Power #1 - 24 VDC filtered, power-limited (3.00 amps maximum) Supervision required. Suitable for powering annunciators. Nonresettable Power #2 - 24 VDC filtered, power-limited (3.00 amps maximum) Supervision required. Suitable for powering annunciators. Supervise with a power supervision relay A77-716B DC Power Outputs (24 VDC) MS-9600 Basic System Connections SLC Loop Refer to the SLC Wiring Manual for detailed information on wiring addressable devices for Style 4, 6 and 7. Peripheral Devices and Their Documents: ADT-AFM-16AT & ADT-AFM-32A Doc. # A15048 ADT-ACS Series Doc. # 51353 ADT-ACM-8R Doc. # 51356 ACS (EIA-485) Annunciators ADT-AFM-16A Doc. # A15207 Ack/Step TERM (EIA-485) Annunciators Silence Drill Hold 2 sec. ADT-LDM-32 Doc. # 51351 Reset ADT-LCD-80F Doc. # 51589 Unimode 9600 Doc. # 51336 1 SLC Loop 9600peri.cdr ADT-UDACT Doc. # 50934 Addressable Devices and SLC Wiring Doc. # 51309 Battery Connector ADT-CHG-120 Charger Doc. # 50938 Unimode 9600 PN 51336:C 11/06/01 11 3URGXFW'HVFULSWLRQ ,QYHQWRU\ Product Description SECTION 1 The ADT Unimode 9600 is a compact, cost effective, intelligent addressable FACP (Fire Alarm Control Panel) with an extensive list of powerful features. The combination of newer series devices and legacy 300 Series devices, along with the Unimode 9600 FACP, offer the latest in fire protection technology. The power supply and all electronics are contained on a single circuit board housed in a metal cabinet, providing a complete fire control system for most applications. Optional modules, which plug into the main circuit board, are available for special functions. Available accessories include LED, graphic and LCD annunciators, reverse polarity/city box transmitter, digital alarm communicator/ transmitter, SLC expansion module, local and remote upload/download software and remote power expansion. 1.1 Inventory When the Unimode 9600 shipment is received, check to make certain that all parts have been included in the shipment. The Unimode 9600 shipment should consist of one of each of the following: ✓ ✓ ✓ ✓ main circuit board with display backbox with door plastic bag containing screws, cables, key, etc. manual 1.2 Features and Options • Single standard addressable SLC loop which meets NFPA Style 4, 6 and 7 requirements • Optional module for adding a second SLC loop which meets NFPA Style 4, 6 and 7 requirements • 318 addressable device capacity for each SLC loop (159 detectors and 159 control/ monitor modules) • 99 software zones • Two onboard NACs (Notification Appliance Circuits) with additional NAC capability using control modules • 6.0 amps total power for NACs and 24 VDC auxiliary power outputs • 7.2 amps total system power (includes battery charger) • Two programmable relay outputs and one fixed trouble relay • EIA-232 Printer/PC interface (variable baud rate) • 80-character LCD display (backlit) • Real-time clock/calendar with daylight savings time control • History file with 1,000 event capacity • Advanced fire technology features: • ✓ Automatic drift compensation ✓ Maintenance alert ✓ Detector sensitivity test capability (NFPA 72 compliant) ✓ Automatic device type-code verification ✓ Point trouble identification Waterflow selection per module point • Alarm verification selection per detector point • Walktest, silent or audible • PAS (Positive Alarm Sequence) and Pre-signal per point (NFPA 72 compliant) 8QLPRGH31& Features and Options Product Description • Annunciators: • ✓ ADT-AFM-LED Zone Annunciator Series ✓ ADT-LDM Graphic Annunciator Series ✓ ADT-LCD-80F Liquid Crystal Display point annunciator ✓ ADT-ACM-8R Relay Module Silence inhibit timer option per NAC • Autosilence timer option per NAC • Continuous, March Time, Temporal or California code for main circuit board NACs with two-stage capability • Selectable strobe synchronization per NAC • Remote Acknowledge, Alarm Silence, Reset and Drill via addressable modules, ADT-AFM annunciators or ADT-LCD-80F Remote annunciator • Auto-program (learn mode) reduces installation time. Reports two devices set to the same address • Password and key-protected nonvolatile memory • User programmable password • Fully programmable from local keypad or keyboard or local PC • SLC operates up to 10,000 ft. (3,000 m) with twisted, shielded wire or 3,000 ft (900 m) with untwisted, unshielded wire • Compatible with newer series devices (CLIP Mode) ✓ CP350: addressable Ionization Smoke Detector ✓ SD350(T): addressable Photo Smoke Detector (T= with Thermal Sensor) ✓ H350(R): Fast Response Heat Detector (R=Rate-of-Rise option) ✓ D350P(R): addressable Photo Duct Detector (R=alarm relay option) ✓ B501BH & B501BHT Sounder Bases ✓ BB224RB Relay Base ✓ BB224BI Isolator Base ✓ MMF-300: Monitor Module ✓ MDF-300: Dual Monitor Module (uses two consecutive SLC addresses) ✓ MMF-301: Miniature Monitor Module ✓ MMF-302: 2-wire Detector Module ✓ CMF-300: Control Module ✓ CRF-300: Relay Module ✓ ADT-BG-12LX: Manual Pull Station ✓ I300: Isolator Module • Compatible with legacy 300 Series devices (CLIP Mode only): ✓ CP300: addressable Ionization Smoke Detector ✓ SD300(T): addressable Photoelectric Smoke Detector (T= Thermal Sensor) ✓ C304: Control Module ✓ M300: Monitor Module ✓ M301: Miniature Monitor Module ✓ M302: 2-wire Detector Module ✓ ADT-BG-10LX: Manual Pull Station • Unimode 9600 PN 51336:C 11/06/01 Optional 4XTMF module (conventional reverse polarity/city box transmitter) 13 Product Description Specifications 1.3 Specifications AC Power - TB1 120 VAC, 60 Hz, 3.2 amps Wire size: minimum 14 AWG (2.00 mm2) with 600 V insulation Battery (Lead Acid Only) - TB2 Maximum Charging Circuit: Normal Flat Charge - 27.6 VDC @ 1.00 amp Maximum Battery Charger Capacity: 25 Amp Hour (Unimode 9600 cabinet holds maximum of two 18 Amp Hour batteries. For greater than 25 Amp Hour up to 120 Amp Hour batteries, use the ADT-CHG-120 Battery Charger and BB-55F Battery Box. Note: Jumper JP3, on the FACP main circuit board, must be cut to disable the FACP battery charger when using the ADT-CHG-120. Communication Loop - (Standard ) TB8 and (Optional SLC Expander Module) J3 24 VDC nominal, 27.6 VDC maximum Maximum length is 10,000 ft. (3,000 m) total twisted, shielded pair length Maximum loop current is 400 mA (short circuit) or 100 mA (normal) Maximum loop resistance is 40 ohms Supervised and power-limited Refer to SLC Loop manual for wiring information Notification Appliance Circuits - TB4 Power-limited circuitry Maximum voltage drop in wiring: 2.0 VDC Nominal operating voltage: 24 VDC Current-limit: fuseless, electronic, power-limited circuitry Maximum signaling current per circuit: 3.00 amps (see Figure 1.1 on page 15) End-of-Line Resistor: 4.7 kΩ, ½ watt (P/N 71252 UL listed) for NACs Refer to ADT Device Compatibility Document for listed compatible devices Two Programmable and One Fixed Output Relay - TB5 Contact rating: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive) Form-C relays Refer to Figure 2.5 on page 28 for information on power-limited wiring for relay circuits Four-Wire Resettable Smoke Detector Power (24 VDC nominal) - TB3, Terminals 1 (+) & 2 (-) Maximum ripple voltage: 10 mVRMS Up to 3.0 amps is available for powering 4-wire smoke detectors (see Figure 1.1) Power-limited circuit Refer to ADT Device Compatibility Document for listed compatible devices Nonresettable Power #1 (24 VDC Nominal) - TB3, Terminals 3 (+) & 4 (-) Maximum ripple voltage: 10mVRMS Total DC current available from each output is up to 3.00 amps (see Figure 1.1) Power-limited circuit Nonresettable Power #2 (24 VDC Nominal) - TB3, Terminals 5 (+) & 6 (-) Maximum ripple voltage: 10mVRMS Total DC current available from each output is up to 3.00 amps (see Figure 1.1) Power-limited circuit 14 Unimode 9600 PN 51336:C 11/06/01 Specifications Product Description EIA-485 (ACS) - TB6 ACS annunciator connector, Terminal 1 (+) and Terminal 2 (-) EIA-485 (TERM) - TB7 Terminal Mode annunciator connector, Terminal 5 (In +), 6 (In -), 7 (Out +), 8 (Out -) EIA-232 (ACS) - TB7 PC/Printer Connector, Terminal 1 (Transmit), 2 (Receive), 3 (DTR), 4 (Ground) Auxiliary Trouble Inputs - J16 & J17 Two-pin connectors which can be used to monitor trouble conditions on auxiliary equipment. They can be connected to the trouble bus of a peripheral such as the ADTCHG-120 or to the normally-open dry contacts of a trouble relay. CAUTION! Do not connect power to these connectors since circuit damage may result. 1.3.1 Current Availability The following figure illustrates the maximum current that is possible for each panel circuit and the total current available from the FACP power supply. TB3 Resettable Power for 4-Wire Smoke Detectors 1 3 amps max per circuit 2 3 Nonresettable Power # 1 3 amps max per circuit 4 5 Nonresettable Power # 2 6 Standby 6 amps max per panel 3 amps max per circuit Alarm 7 amps max 1 2 NAC # 1 3 amps max per panel per circuit 3 4 5 6 NAC # 2 7 3 amps max per circuit 8 TB4 Refer to the battery calculations section for additional information. Figure 1.1 Current Availability Unimode 9600 PN 51336:C 11/06/01 15 Product Description Controls and Indicators 1.4 Controls and Indicators LCD Display The FACP uses an 80-character (4 lines X 20 characters) high viewing angle LCD display. The display includes a long life LED backlight that remains illuminated. If AC power is lost and the system is not in alarm, the LED backlight will turn off to conserve batteries. SYSTEM ALL NORMAL 10:00A 010101 LED Indicators LED indicators are provided to annunciate the following conditions: • • • • • • • • • AC Power (green) Fire Alarm (red) Supervisory (yellow) Trouble (yellow) Maintenance/presignal (yellow) Alarm Silenced signals (yellow) Disabled (yellow) Battery fault (yellow) Ground fault (yellow) Key Panel Mounted on the main circuit board, the key panel includes a window for the LCD display and LED indicators as listed above. The key panel, which is visible with the cabinet door closed, has 25 keys, including a 16 key alpha-numeric pad similar to a telephone keypad. Function keys: Acknowledge/Step Alarm Silence Drill Reset (lamp test) Service/program keys: • • • • • • • • • • AC POWER MAINTENANCE FIRE ALARM ALARM SILENCED SUPERVISORY DISABLED TROUBLE BATTERY GROUND 2 1 4 5 ACK/STEP 1st 3 DEF ABC 6 EVENT ALARM SILENCE CLR Keys labeled 1 to 9 7 8 9 * key 0 # # key * -/. 0 (recall) key 1st Event key Figure 1.2 Membrane/Display Panel Clear key Escape key Mode key Four cursor keys (up, down, left and right) Enter key GHI JKL MNO PRS TUV WXY ENTER ESC DRILL HOLD 2 SEC MODE RESET QZ RECALL 9600kypd.cdr • • • • Local Piezo Sounder A piezo sounder provides separate and distinct pulse rates for alarm, trouble and supervisory conditions. 16 Unimode 9600 PN 51336:C 11/06/01 Circuits Product Description 1.5 Circuits SLC Communication Loop Reference Manual One SLC loop is provided standard on the FACP main circuit board. A second SLC loop is available by plugging the optional SLC module into connector J3 on the main circuit board. SLC loops, configurable for NFPA Style 4, 6 or 7, provide communication to addressable detectors, monitor (initiating device) and control (output device) modules. Refer to the ADT SLC Wiring Manual for information on wiring devices. Output Circuits The following output circuits are available on the FACP: • 24 VDC Resettable (smoke detector power) output - 3.00 amps maximum • 24 VDC Nonresettable power output #1 - 3.00 amps maximum • 24 VDC Nonresettable power output #2 - 3.00 amps maximum • 24 VDC Battery Charger (up to 25 AH batteries) NAC (Notification Appliance Circuits) Two NACs, configurable for Style Y (Class B) or Style Z (Class A), are provided with various programmable features. Relays One fixed and two fully programmable Form-C dry contact relays are provided. The fixed fail-safe relay monitors system trouble and the two programmable relays are factory default programmed for system alarm and system supervisory. Contacts are rated 2.0 amps @ 30 VDC (resistive) and 0.5 amps @ 30 VAC (resistive). The programmable relays can be programmed for the following operations: • • • • • • • • • • fire alarm trouble supervisory supervisory auto-resettable DACT communication failure process monitor process monitor auto-resettable hazard alert medical alert AC loss Auxiliary Trouble Inputs Auxiliary Trouble Inputs can be connected to trouble bus outputs from auxiliary equipment, such as power supplies, or normally-open dry contacts of a trouble relay to allow monitoring by the Unimode 9600. 1.6 Components Main Circuit Board See Page Unimode 9600 PN 51336:C The main circuit board contains the system’s CPU, power supply, other primary components and wiring interface connectors. Optional modules plug in and are mounted to the main circuit board. The circuit board is delivered in the Unimode 9600 kit and must be mounted to the backbox. Refer to the circuit board illustration on Page 10. 11/06/01 17 Product Description Components Cabinet uni-600.cdr The Unimode 9600 cabinet is red with a navy blue front overlay. The backbox provides space for two batteries (up to 18 Amp Hour). Ample knockouts are provided for system wiring. Also included is a standard dress panel, which mounts to the inside of the cabinet (required on the ULC version). The dress panel must be installed to meet FM requirements. Batteries The Unimode 9600 cabinet provides space for two batteries (up to 18 Amp Hour). Batteries larger than 18 Amp Hour up to 25 Amp Hour require use of UL listed battery cabinet. The ADT-CHG-120 can be used for charging 25 to 120 AH batteries and the BB-55F can be used for housing the batteries. Batteries must be ordered separately. 1.6.1 Intelligent Addressable Detectors: Newer Series Intelligent, addressable detectors provide information to the control panel on an SLC Signaling Line Circuit (refer to the ADT SLC Wiring Manual for detailed information on device installation, wiring and operation). This allows the control panel to continually process the information to determine the status (alarm, trouble, maintenance or normal) of each detector. Each detector responds to an SLC address that is set in the detector head using built-in rotary decimal switches with the ability to select up to 159 addresses. Note that a blinking LED on an intelligent detector indicates communication between the detector and the control panel. Refer to the ADT Device Compatibility Document for a list of approved detectors. Smoke Detectors (Photoelectric) The SD350 is an intelligent, addressable low profile photoelectric smoke detector which provides smoke sensing technology. The SD350T includes a 135o fixed thermal sensor. Smoke Detector (Ionization) The CP350 is an intelligent, addressable low profile ionization smoke detector which measures the level of combustion products in its chamber using the ‘ionization principle.’ Smoke Detector (Duct) The D350P is an intelligent, addressable photoelectric duct smoke detector. The D350RP includes an alarm relay. Heat Detectors The H350 is an intelligent heat detector with a thermistor sensing circuit for fast response, designed to provide open area protection with 50 foot (15 m) spacing capability. The H350R incorporates a thermal Rate-of-Rise circuit of 15oF (9.4oC). Detector Bases The B501BH is a standard sounder base and the B501BHT is a temporal tone sounder base for intelligent, addressable smoke detectors. The B224RB is a relay base with one Form-C relay for intelligent, addressable smoke detectors. It may be used to control auxiliary functions. The B224BI is an isolator base for intelligent, addressable smoke detectors. It functions similar to the I300 isolator module which allows loops to operate under fault conditions and automatically restore when the fault is removed. 18 Unimode 9600 PN 51336:C 11/06/01 Components Product Description 1.6.2 Intelligent Addressable Modules: Newer Series Reference Manual The newer series of Control Modules and Monitor Modules provide an interface between the control panel and conventional notification and initiating devices. Each module can be set to respond to an address with built-in rotary switches with the ability to select up to 159 addresses (a tab on the address switch must be broken off to use addresses 100-159). A blinking LED on a monitor module indicates communication between the module and the control panel. These devices can also be used in CLIP Mode (Classic Loop Interface Protocol) when installed on older systems. Refer to the ADT Device Compatibility Document for a list of approved notification and initiating devices. Monitor Modules The MMF-300, MDF-300 and MMF-302 are addressable monitor modules for monitoring conventional initiating devices. The MMF-300 is used for normally open contact alarm initiating devices, such as manual pull stations, four-wire smoke detectors, heat detectors, waterflow, security contacts and supervisory devices. The MDF-300 is a dual monitor module (Class B only) which occupies two consecutive SLC addresses, with each module functionally the same as the MMF-300. The MMF-302 is used primarily for two-wire smokes detectors in addition to normally open contact devices. The supervised IDCs (Initiating Device Circuits) can be wired to the modules as NFPA Style B (Class B) or Style D (Class A) circuits. The modules are supplied with a thermoplastic cover for mounting to a 4-inch mounting box. Monitor Module (miniature) The MMF-301 is an addressable module that is functionally similar to an MMF-300 but offered in a smaller package for mounting directly in the electrical box of the device being monitored. Control Module The CMF-300 is an addressable Control Module used to connect NACs (Notification Appliance Circuits) to power and supervise compatible, UL-listed notification appliances. The NACs can be wired to the module as supervised NFPA Style Y (Class B) or Style Z (Class A) circuits. The modules are supplied with a thermoplastic cover for mounting to a 4-inch square mounting box. Relay Module The CRF-300 is a Control Relay Module which is functionally similar to the CMF-300 but used as a Form-C relay module. Isolator Module The I300 loop isolator module is an automatic switch which opens the circuit voltage to the SLC loop branch(es) whenever a wire-to-wire short circuit is detected on that loop. The remainder of the communications loop leading up to the I300 will continue to operate, unaffected by the short. The isolator module is bidirectional, meaning that it can detect a fault condition between the input SLC terminals or output SLC terminals. The I300 is required to meet NFPA Style 7 requirements. Detector Annunciator The RA400Z is a remote single LED annunciator that can be wired directly to an addressable detector for annunciation of that detector’s alarm status. Manual Pull Station The ADT-BG-12LX is an addressable manual pull station featuring a key-lock reset. The pull station responds to an address set by the installer using the built-in rotary decimal switches on the pull station. The manual pull station includes an ADT key. Unimode 9600 PN 51336:C 11/06/01 19 Product Description Optional Modules 1.6.3 300 Series Intelligent Addressable Devices ADT’s 300 Series Intelligent Addressable Devices are fully compatible with the Unimode 9600 FACP. The devices must be configured for CLIP Mode operation if the control panel is installed in an existing system with 300 Series devices. The address of 300 Series devices cannot be set above 99. Compatible devices include: • • • • • • • • SD300 Photoelectric Detector SD300T Photoelectric Detector with Thermal Sensor CP300 Ionization Detector M300 Monitor Module M301 Miniature Monitor Module M302 2-wire Monitor Module C304 Control/Relay Module ADT-BG-10LX Manual Pull Station 1.6.4 Addressable Device Accessories End-of-Line Resistor Assembly P/N R-47K The 47 kΩ End-of-Line Resistor assembly (P/N: R-47K) is used to supervise the MMF300, MDF-300, MMF-301 and CMF-300 module circuits. The 3.9 kΩ End-of-Line Resistor assembly is used to supervise the MMF-302 module circuit. The resistors are included with each module. Power Supervision Relay The UL listed End-of-Line power supervision relay is used to supervise the power to 4wire smoke detectors and notification appliances. N-ELR Mounting Plate The N-ELR is a single End-of-Line resistor plate which is required for use in Canada. An ELR, which is supplied with each module and fire alarm control panel, is mounted to the ELR plate. Resistors mounted to the N-ELR plate can be used for the supervision of a monitor and control module circuit. 1.7 Optional Modules The Unimode 9600 main circuit board includes option module connectors for the following modules: 4XTMF Transmitter Module The 4XTMF provides a supervised output for local energy municipal box transmitter, alarm and trouble reverse polarity. It includes a disable switch and disable trouble LED. A jumper on the module is used to select an option which allows the reverse polarity circuit to open with a system trouble condition if no alarm condition exists. The module plugs into connectors J10 and J11 which are located near the top center of the main circuit board. When the 4XTMF module is installed, Jumper JP6, on the main circuit board, must be cut to allow supervision of the module. SLC-2 Expander Module The SLC-2 Expander Module allows expansion of the Unimode 9600 from one SLC circuit to two SLC circuits. The module plugs into connector J3 which is located in the lower right corner of the main circuit board. The wiring for the second SLC connects to terminals located on the expander module. 20 Unimode 9600 PN 51336:C 11/06/01 Accessories Product Description 1.8 Accessories 1.8.1 PK-9600 Programming Utility The PK-9600 Programming Utility can be used to program an Unimode 9600 directly from most IBM compatible computers, including laptops and portables, equipped with a serial port. Unimode 9600 program files can also be created and stored on the PC and then downloaded to the control panel. The PK-9600 Kit includes the Windows-based Programming Utility software on CD-ROM with on-line help file. A serial cable (P/N: PRT/PK-CABLE), which must be purchased separately, is required for connection of the PC to the RS-232 (PC/Printer) terminals at TB7 of the Unimode 9600 main circuit board. Refer to the illustration on page 10 and the section titled "Printer/PC" on page 34, for the location and connections to this terminal. 1.8.2 Dress Panel A dress panel is provided standard with the Unimode 9600 (required for Canadian installations). The dress panel restricts access to the system wiring while allowing access to the key panel. Note that the Unimode 9600 FACP, installed with the dress panel, has received Factory Mutual (FM) approval. FM approval is contingent on the proper installation of the dress panel. CAUTION: HIGH VOLTAGE UNDER PANEL !! WARNING !! dp9600.cdr SEVERAL DIFFERENT SOURCES OF POWER CAN BE CONNECTED TO THIS CONTROL UNIT DISCONNECT ALL SOURCES OF POWER BEFORE SERVICING 1.8.3 Battery Box BB-17F bb-17f.cdr The BB-17F battery box may be used to house up to two 18 AH batteries in the event that room is not available in the main cabinet due to the use of a ADT-UDACT, 411UD, etc. The battery box mounts directly below the FACP cabinet. The battery box is red and is provided with knockouts. Unimode 9600 PN 51336:C 11/06/01 21 Product Description Accessories BB-55F bb-55f.cdr The BB-55F battery box may be used to house two 25 AH batteries, two 60 AH batteries or one 100 AH battery. When the ADT-CHG-120 is mounted in the BB-55F, two 25 AH or one 60 AH battery may also be housed in the battery box. 1.8.4 ADT-CHG-120 Battery Charger Reference Manual The ADT-CHG-120 is capable of charging up to 120 AH lead-acid batteries with the Unimode 9600 FACP. The FACP battery charger must be disabled when using the ADT-CHG-120. The batteries and charger can be housed in the BB-55F battery box which can be mounted up to 20 feet away from the control panel. Note that when using the BB-55F for housing the charger and batteries greater than 25AH, multiple BB-55Fs are required. Refer to the ADT-CHG-120 Manual for additional information. 1.8.5 Annunciators ADT-ACS Series LED Zone Type Annunciators The ADT-ACS Series Annunciators remotely display alarm and trouble status as well as system status. In addition, they can provide remote Acknowledge, Silence, Reset and Drill functions. For more detailed information, refer to the appropriate ADT-ACS annunciator manual. Following is a list of annunciators which can be used with the Unimode 9600. Reference Manual • • • • • • • 22 ADT-ACM-16AT Annunciator Control Module annunciates 16 zones with 16 red alarm LEDs and 16 yellow trouble LEDs. In addition, it has a System Trouble LED, an On Line/Power LED and a local piezo sounder. It also has switches for FACP Acknowledge, Silence, Reset and Drill. It has rotary address switches and will accept up to three AEM-16AT Expanders AEM-16AT Annunciator Expander Module annunciates 16 zones with 16 red alarm LEDs and 16 yellow trouble LEDs ADT-AFM-16AT Annunciator Fixed Module annunciates 16 zones with 16 red alarm LEDs and 16 yellow trouble LEDs. In addition, it has a System Trouble LED, an On Line/Power LED and a local piezo sounder. It also has switches for FACP Acknowledge, Silence, Reset and Drill. It is fixed at address ‘1’ ADT-ACM-32A Annunciator Control Module annunciates 32 alarm zones with 32 red LEDs. In addition, it has a System Trouble LED, an On Line/Power LED and a local piezo sounder. It also has a switch for local piezo silence. It has rotary address switches and will accept one AEM-32A Expander AEM-32A Annunciator Expander Module annunciates 32 alarm zones with 32 red LEDs ADT-AFM-16A Annunciator Fixed Module annunciates 16 alarm zones with 16 red alarm LEDs. In addition, it has a System Trouble LED, an On Line/Power LED and a local piezo sounder. It also has a switch for local piezo silence. It is fixed at address ‘1’ ADT-AFM-32A Annunciator Fixed Module annunciates 32 alarm zones with 32 red LEDs Unimode 9600 PN 51336:C 11/06/01 Getting Started Product Description ADT-LCD-80F Remote Fire Annunciator The ADT-LCD-80F annunciator is a compact 80-character backlit LCD remote fire annunciator that is capable of displaying English language text. It mimics the display on the control panel and will annunciate device type, point alarm, trouble or supervisory condition, zone assignment plus any custom alpha labels programmed into the FACP. The annunciator also provides system status LEDs to display AC Power, Alarm, Trouble, Supervisory and Alarm Silenced conditions. Additionally, the ADT-LCD-80F is capable of remotely performing critical system functions such as Acknowledge, Silence, Reset and Drill. Reference Manual Reference Manual Communications between the control panel and the annunciator is accomplished over a serial interface employing the EIA-485 communication standard. Up to 32 ADT-LCD80F annunciators may be connected to the EIA-485 circuit. The annunciators may be powered from the host FACP or a remote UL listed filtered power supply such as the FCPS Series. For more detailed information, refer to the ADT-LCD-80F manual. ADT-LDM Series Lamp Driver Modules (Graphic Annunciator) The ADT-LDM Series Lamp Driver Modules, which consist of the ADT-LDM-32 master and ADT-LDM-E32 expander modules, are used to provide an interface to a custom graphic LED annunciator. The master module provides power and control for a maximum of three expander modules. The ADT-LDM-32 and ADT-LDM-E32 have output connectors which are used to drive lamps or LEDs and input connectors which are used for remote switch functions. Refer to the ADT-LDM Series Lamp Driver Modules manual for a complete description. 1.9 Getting Started The following is a brief summary of the minimal steps involved in bringing an Unimode 9600 on-line: • Install Backbox and Main Circuit Board (refer to "Mounting" on page 24) • Address and Install Intelligent Devices (refer to the SLC Wiring Manual) • Enter Autoprogramming (refer to "Autoprogram" on page 87) • Resolve Programming Conflicts Go to Point Program to Enter Specific Data (refer to "Point Program" on page 43). Use the right and left arrow keys to navigate between devices. Unimode 9600 PN 51336:C 11/06/01 23 Installation Mounting Installation SECTION 2 The cabinet may be either semi-flush or surface mounted. The cabinet mounts using two key slots and two 0.250” (6.35 mm) diameter holes located in the backbox. The key slots are located at the top of the backbox and the two securing holes at the bottom. Carefully unpack the system and check for shipping damage. Mount the cabinet in a clean, dry, vibration-free area where extreme temperatures are not encountered. The area should be readily accessible with sufficient room to easily install and maintain the panel. Locate the top of the cabinet approximately 5 feet (1.5 m) above the floor with the hinge mounting on the left. Determine the number of conductors required for the devices to be installed. Sufficient knockouts are provided for wiring convenience. Select the appropriate knockout(s) and pull the conductors into the box. All wiring should be in accordance with the National and/or Local codes for fire alarm systems. 2.1 Mounting ! See Page The circuit board contains static-sensitive components. Always ground yourself with a proper wrist strap before handling any boards so that static charges are removed from the body. Use static suppressive packaging to protect electronic assemblies. ✓ Mark and predrill holes in the wall for the top two keyhole mounting bolts using the dimensions illustrated in Figure 2.2 on page 25 ✓ Install two upper fasteners in the wall with the screw heads protruding ✓ Using upper ‘keyholes,’ place backbox over the two screws, level and secure ✓ Mark and drill the lower two holes ✓ Mount backbox, install remaining fasteners and tighten ✓ Screw supplied standoffs onto mounting studs in locations indicated below ✓ When the location is dry and free of construction dust, install the main circuit board by aligning the 10 mounting holes in the circuit board with the 10 mounting standoffs in the backbox as illustrated below ✓ Secure the circuit board to the standoffs with the supplied screws and male/ female standoff as indicated in following figure Unimode 9600 Main Circuit Board IMPORTANT! Secure circuit board to this standoff with supplied male/female standoff TB3 TB5 TB4 TB6 TB7 TB8 JP3 CUT TO DISABLE LOCAL CHARGER JP5 4XTM OPT BD JP11 JP10 J2 OPT DACT OPT SLC CUT TO MONITOR 4XTM J17 J16 JP6 J8 J6 LCD DISPLAY TB1 TB2 SW1 KEYPAD I/F J3 CB1 mounting studs HOT NEUT EARTH +BATTERY- J7 96brdmnt.cdr JP2 DISABLE GND FLT mounting studs Unimode 9600 Backbox Figure 2.1 Unimode 9600 Main Circuit Board Installation 24 Unimode 9600 PN 51336:C 11/06/01 Mounting Installation 1.75“ 5.1 cm 2.00“ 2.00“ 2.00“ 2.00“ 2.00“ 2.00“ 4.45 cm 1.75“ 1.50“ (3.81 cm) 3.79 cm 1.49“ 4.1 cm 1.62“ 15.5“ (39.37 cm) 1.62“ (4.11 cm) 3.81 cm 1.50“ 12.00“ (30.48 cm) 4.1cm 1.62“ 1.453“ (3.69 cm) 10.0“ 25.4 cm 47.0cm 18.5“ 4.45cm 1.75“ 17.35 cm 6.83“ 4.45cm 1.75“ 4.1cm 1.583“ 1.50“ 3.81 cm 4.37“ 11.1 cm 9600encl.cdr 11.1 cm 4.37“ 1.50“ (3.81 cm) 1.75“ 4.45 cm Figure 2.2 Unimode 9600 Cabinet Mounting Unimode 9600 PN 51336:C 11/06/01 25 Installation Mounting Depth = 4.37" (11.1 cm) Top Depth = 4.425" (11.24 cm) Door = 15.78" (40.08 cm) Backbox = 15.5" (39.37 cm) Door = 18.67" (47.43 cm) Backbox = 18.5" (47.0 cm) Left Side Right Side Bottom 18.620" (47.3 cm) Depth = 4.75" (12.07 cm) 15.625" (39.688 cm) 21.620" (54.92 cm) Battery Box = 8.5" (21.59 cm) 9600cab.cdr 18.625" (47.308 cm) Trim Ring P/N:FC-TR Battery Box = 14.34" (36.42 cm) Figure 2.3 Unimode 9600 Cabinet Dimensions 26 Unimode 9600 PN 51336:C 11/06/01 Power Installation 2.2 Power WARNING: Several different sources of power can be connected to this panel. Disconnect all sources of power before servicing. The panel and associated equipment may be damaged by removing and/or inserting cards, modules or interconnecting cables while this unit is energized. 2.2.1 AC Power and Earth Ground Connection LCD DISPLAY Primary power required for the FACP is 120 VAC, TB1 TB2 60 Hz, 3.2 amps. Overcurrent protection for this circuit must comply with Article 760 of the National Electrical Code (NEC) and/or local codes. Use 14 AWG (2.00 mm2) or larger wire with 600 volt CB1 HOT NEUT EARTH +BATTERYinsulation rating. Make certain that the AC mains circuit breaker is off before making any wiring connections between the mains and the control panel. Connect the wiring from the AC mains to TB1 on the FACP, being careful to observe proper connections. Connect a wire from the grounding stud in the cabinet to a known solid earth ground. This connection is vital for maintaining the control panel’s immunity to unwanted transients generated by lightning and electrostatic discharge. Apply AC power to the panel only after the system is completely installed and visually checked. Note that AC power must be applied to the panel before installing the battery interconnect cable (refer to the following section). 2.2.2 Battery Power Interconnect Cable + See Page Before connecting the batteries to the FACP, make certain that the interconnect cable between the batteries is not connected. Do not connect the interconnect cable until the system is completely installed. Observe polarity when connecting the batteries. Connect the battery cable to TB2 on the main circuit board. Refer "Power Supply Calculations" on page 127, for calculation of the correct battery rating. + - WARNING: Battery contains sulfuric acid which can cause severe burns to the skin and eyes and can destroy fabrics. If contact is made with sulfuric acid, immediately flush the skin or eyes with water for 15 minutes and seek immediate medical attention. 2.2.3 DC Power Output Connection All DC power outputs are power-limited. Power-limited Resettable Power 3.0 amperes max., 24 VDC nominal filtered, resettable power can be drawn from TB3 Terminals 1(+) and 2(-) Power-limited Nonresettable Power #1 3.0 amperes max. , 24 VDC nominal filtered, nonresettable power can be drawn from TB3 Terminals 3(+) and 4(-) Power-limited Nonresettable Power #2 3.0 amperes max. , 24 VDC nominal filtered, nonresettable power can be drawn from TB3 Terminals 5(+) and 6(-) 1 2 3 4 5 6 9600tb3.cdr + - + - + - Figure 2.4 Power Outputs - 24 VDC Unimode 9600 PN 51336:C 11/06/01 27 Installation Relays 2.3 Relays The FACP provides two programmable Form-C relays and one fixed fail-safe Form-C trouble relay, all with contacts rated for 2.0 amps @ 30 VDC (resistive) or 0.5 amps @ 30 VAC (resistive). The Alarm and Supervisory silk-screen labels reflect the factory default programming for the two programmable relays. Note that relay connections may be power-limited or nonpower-limited, provided that 0.25” spacing is maintained between conductors of power-limited and nonpower-limited circuits. Refer to UL Power-limited wiring requirements. ALARM TROUBLE SUPV RELAY RELAY RELAY Note that the relays labeled as Alarm Relay (Relay 1) and Supervisory Relay (Relay 3) reflect the factory default programming for these relays which are programmable. The relay labeled Trouble Relay (Relay 2) is fixed and cannot be changed. It is a failsafe relay which will transfer on any trouble or total power failure. NO NC C NC NO C NO NC C 9600reyp.cdr TB5 Relay contacts shown with power applied to panel and no active troubles, alarms or supervisories Figure 2.5 Relay Terminals 2.4 Notification Appliance Circuits See Page Reference Manual The control panel provides two NAC (Notification Appliance Circuits) configurable for Style Y/Class B or Style Z/Class A. Each circuit is capable of 3.0 amps of current. Total system current cannot exceed 7.2 amps (refer to "Calculating the System Current Draw" on page 128). Use UL listed 24 VDC notification appliances only. Circuits are supervised and power-limited. Refer to the ADT Device Compatibility Document for a listing of compatible notification appliances. The two NACs, which are located on the main circuit board, may be expanded via the FCPS Series field charger/power supplies. Surge protection for notification appliances may be provided by using one of the UL listed compatible surge suppressors listed in the ADT Device Compatibility Document. Style Y (Class B) Notification Appliance Circuit, supervised and power-limited - 4.7 kohm, ½ watt P/N:71252 UL listed Polarized Bell + Polarized Strobe Polarized Horn Notification Appliance Circuit polarity shown in alarm state TB4 1 + 2 3 4 5 + Polarized Bell + Polarized Horn + Polarized Horn 6 7 8 Dummy Load all unused circuit B+ A+ A- B- B+ A+ A- B- Figure 2.6 NAC Connections 28 Unimode 9600 PN 51336:C 9600nac.cdr Style Z (Class A) Notification Appliance Circuit, supervised and power-limited 11/06/01 UL Power-limited Wiring Requirements Installation 2.5 UL Power-limited Wiring Requirements Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” (6.35 mm) away from any nonpower-limited circuit wiring and nonpower-limited circuit wiring must enter and exit the cabinet through different knockouts and/or conduits. A typical wiring diagram for the Unimode 9600 is shown below. Powe r-l i m ited C ircuit s Nonp ower -li Circu mited its Powe r -limi ted C ir cuits 4XTMF To E IA 24 V -485 and DC p ow route d beh er i board nd AC Nonp Power ower -limi ted To B at Powe rCircu limited its SLC-2 teries Nonp ower -li Circu mited its ms-9600wireroute.cdr ADT-UDACT Powe rCircu limited its Figure 2.7 Typical UL Power-limited Wiring Requirements Unimode 9600 PN 51336:C 11/06/01 29 Installation Optional Modules and Devices 2.6 Optional Modules and Devices WARNING! Disconnect all sources of power (AC and DC) before installing or removing any modules or wiring. Unimode 9600 Keypad/Display Removal Removal of the keypad/display is normally not necessary. If, however, it becomes necessary to replace the keypad/display, access the auxiliary trouble bus connectors at J16 and J17 or install future option modules, the Keypad/Display can be removed by inserting a Phillips screwdriver into each of the three holes located in the flexible covering of the Keypad/Display and loosening the three mounting screws. Note that it is not necessary to disconnect the cables between the Keypad/Display and the main circuit board unless the unit itself is being replaced. Carefully lift the Keypad/Display and rest the unit at the bottom of the main circuit board. Mounting Screw Access Hole TB3 TB4 TB5 TB6 TB7 TB8 JP3 CUT TO DISABLE LOCAL CHARGER JP6 JP5 4XTM OPT BD JP10 MAINTENANCE AC POWER FIRE ALARM ALARM SILENCED SUPERVISORY DISABLED TROUBLE BATTERY GROUND JP2 5 DEF 6 JP7 EVENT 9 JP6 J168 TUV PRS * 0 TB1 -/. QZ ALARM SILENCE OPT DACT OPT SLC ENTER DRILL ESC J8 J6 WXY LCD DISPLAY # J2 CLR CUT TO JKLMONITORMNO 4XTM GHI J17 7 ACK/STEP 3 JP8 1st ABC MODE TB2 KEYPAD I/F JP4 HOLD 2 SEC 1 2 RESET3 J3 RECALL CB1 HOT NEUT EARTH J7 +BATTERY- Mounting Screw Access Holes Figure 2.8 Keypad/Display Removal 30 Unimode 9600 PN 51336:C 96dact1.cdr 2 1 DISABLE GND FLT 4 11/06/01 2SWLRQDO0RGXOHVDQG'HYLFHV ,QVWDOODWLRQ 2.6.1 4XTMF Transmitter Module Installation The 4XTMF provides a supervised output for a local energy municipal box transmitter in addition to alarm and trouble reverse polarity. A jumper option allows the reverse polarity circuit to open with a system trouble condition if no alarm condition exists. A disable switch allows disabling of the transmitter output during testing to prevent accidental calling of the monitoring service. Local Energy Municipal Box Service (NFPA 72 Auxiliary Fire Alarm Systems): Supervisory Current: 5.0 mA Trip Current: 350 mA (subtracted from notification appliance power) Coil Voltage: 3.65 VDC Maximum Coil Resistance: 14.6 ohms Maximum allowable wire resistance between panel and trip coil: 3 ohms Municipal Box wiring can leave the building Remote Station Service (NFPA 72 Remote Station Fire Alarm Systems) - Intended for connection to a polarity reversal circuit or a Remote Station receiving unit having compatible ratings: Maximum load for each circuit: 10 mA Reverse polarity output voltage: 24 VDC Remote Alarm and Remote Trouble wiring can leave the building Before installing the module, place the disconnect switch to the right (disconnect) position to prevent accidental activation of the municipal box. Note that a Disconnect LED will illuminate after the module is installed in the Unimode 9600. In addition, the System Trouble LED will turn on to indicate the Disconnect condition. Note: 4XTMF Module is not suitable for transmitting reverse polarity supervisory signal. }Remote Alarm (power-limited)* }Remote Trouble (power-limited)* * Wiring from these terminals can exit the protected premises. Dummy load terminals No connection 6 and 7 (4.7kΩ, ¼ watt resistor) if Municipal Municipal Box (nonpower-limited)* Box is not connected. } + - + 1 2 3 4 5 + 6 7 Polarities are shown for module activation 4xtmfl.cdr Disconnect LED Disconnect Switch shown in disconnect position TBL Jumper Connect to FACP J10 & J11 Figure 2.9 4XTMF Transmitter Module 8QLPRGH31& ,QVWDOODWLRQ 2SWLRQDO0RGXOHVDQG'HYLFHV The following steps must be followed when installing the 4XTMF module: 1. Remove all power (AC and DC) from the FACP before installing 4XTMF 2. Cut jumper JP6 on the main circuit board to allow the control panel to supervise the 4XTMF module 3. Carefully plug the connectors on the 4XTMF module into connectors J10 and J11 on the Unimode 9600 main circuit board, being careful not to bend any pins 4. Secure 4XTMF module to standoffs with supplied screws. 5. Reapply power to the FACP 6. For proper 4XTMF operation, the output relays must be programmed for the factory default settings as shown on the PC board silkscreen: Alarm Relay, Trouble Relay and Supervisory Relay 7. When the installation has been complete, enable the 4XTMF module by sliding the disconnect switch to the left 8. Test system for proper operation Standoff Standoff TB3 TB4 TB5 TB6 TB7 JP3 JP5 CUT TO MONITOR 4XTM Cut Jumper JP6 JP6 4XTM OPT BD J10 & J11 Connectors J11 J10 4XTMF J2 OPT DACT J16 TB1 Unimode 9600 CB1 J8 J6 LCD DISPLAY HOT NEUT EARTH TB2 SW1 KEYPAD I/F +BATTERY- J7 9604xtm1.cdr J17 Figure 2.10 4XTMF Connectors to Unimode 9600 Connectors NOTE: Jumper JP5 on the Unimode 9600 main circuit board can be used to configure the FACP supervisory relay for operation with the 4XTMF module. The supervisory relay must be programmed as shown on the main circuit board silkscreen (TB5, Terminals 4, 5 & 6). Cutting JP5 will allow the 4XTMF to generate a trouble if the supervisory contact opens Leaving JP5 in will prevent generation of a trouble if the supervisory contact opens 2.6.2 Auxiliary Trouble Input (J16 & J17) Auxiliary Trouble Inputs 1 (J17) and 2 (J16), which are located on the Unimode 9600 main circuit board, can be used to monitor for trouble conditions on auxiliary equipment such as power supplies. J16 and/or J17 can be connected to any open collector trouble output on the auxiliary equipment. The Unimode 9600 control panel will indicate a trouble condition if a trouble is sensed at the Auxiliary Trouble Inputs. If the 4XTMF Module is installed and jumper JP6 on the Unimode 9600 has been cut to supervise it, Auxiliary Trouble Input 1 (J17) will monitor the 4XTMF for trouble conditions. 8QLPRGH31& 2SWLRQDO0RGXOHVDQG'HYLFHV ,QVWDOODWLRQ 2.6.3 SLC-2 Expander Module Reference Manual The optional SLC-2 Expander Module provides a second SLC loop for the Unimode 9600 control panel. This allows connection of an additional 318 addressable devices, bringing the total to 636 addressable devices which can be connected to the FACP. Refer to the SLC Manual for information on connecting devices to the SLC. The following steps must be followed when installing the SLC-2 Expander Module: 1. Remove all power (AC and DC) from the FACP before installing the SLC-2 module 2. Carefully plug connector J3 on the SLC-2 module into connector J3 on the Unimode 9600 main circuit board, being careful not to bend any pins 3. Secure the SLC-2 Expander Module to the four standoffs on the FACP main circuit board with the supplied screws 4. Connect the SLC wiring and devices to TB8 on the SLC Expander Module. Refer to the SLC Manual for wiring information 5. Reapply power to the control panel See Page 6. Program the addressable devices connected to the SLC-2 Expander Module as detailed in "Master Programming Level" on page 42 7. Test the system for proper operation SLC Loop 1 Shield B Shield A SLC ASLC BSLC A+ SLC B+ SLC Loop 2 Shield B Shield A SLC ASLC BSLC A+ SLC B+ TB8 TB8 OPT SLC J3 J3 SLC-2 Expander Module 96optslc.cdr TB7 Unimode 9600 Figure 2.11 SLC-2 Expander Module Installation 8QLPRGH31& ,QVWDOODWLRQ 2SWLRQDO0RGXOHVDQG'HYLFHV 2.6.4 Printer/PC A serial printer or a PC (personal computer) may be connected to TB7 Terminals 1 - 4 on the FACP. The printer can be used to provide a hard-copy printout of real-time events, history file and walktest data. An IBM compatible PC can be connected to provide local FACP programming capabilities using the PK-9600 programming utility. Installation of either device requires panel programming to allow the FACP to communicate with the device. ! CAUTION! Do not connect a printer or PC to the Unimode 9600 FACP if a ground fault exists on the control panel. Circuit damage may result. Remove all power (AC and DC) before installing or removing any wiring. Installation Remote printers and PCs require separate primary power. Also required is the PRT/ PK-CABLE which is an interface cable prewired to a DB9F connector. Wire the PRT/PKCABLE to TB7 Terminals 1 - 4 as illustrated in the following figure. Connect the DB9F connector to the printer or PC serial EIA-232 port. If a nine-pin serial connector is not available on the printer or PC, use a DB25 adapter. Make certain that the DB25 adapter does not swap the Transmit and Receive lines. Apply power to the FACP and printer or PC. Note that a ground fault may occur on the FACP, dependent on the printer or PC being used, due to this connection. For this reason, it is important that there be no preexisting ground fault on the panel. Note that the printer may or may not be supervised as determined by user programming. Refer to "Printer/PC" on page 92. Red 5 4 3 2 1 White 9 8 7 6 Green Black PRT/PK-CABLE TX RCV DTR GRND T B 6 SLC RS-232 PC/PRINTER XMT RCV DTR GRND T B 7 SLC B+ A+ B- A- SHIELD B A T B 8 Figure 2.12 Serial Printer and Computer Connections 9600tb7a.cdr ACS 1 COMM 2 Printer Configuration Refer to the documentation supplied with the printer for pertinent information about printer setup. Set the printer’s options as listed in the following table: COMMUNICATION SETUP BUFFER: DATA BITS: PARITY: STOP BIT: BAUD RATE: AUTOMATIC LINE FEED AUTOMATIC CARRIAGE RETURN LARGE 7 EVEN 1 STOP 2400/4800/9600 NO NO PC Configuration The Windows-based PK-9600 Programming Utility Kit contains CD-ROM with on-line help file. 8QLPRGH31& 2SWLRQDO0RGXOHVDQG'HYLFHV ,QVWDOODWLRQ 2.6.5 Digital Communicator and Annunciators 2.6.5.1 ADT-UDACT Digital Alarm Communicator/Transmitter Reference Manual See Page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elay Control Module Reference Manual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niversal Bracket Installation 7KHRSWLRQDO%5.78QLYHUVDO%UDFNHWFDQEHXVHGWRPRXQWVSHFLILFPRGXOHV LQVLGHWKH8QLPRGHFDELQHW7KH%5.7PRXQWVWRWZRVWXGVORFDWHGLQWKH ORZHUULJKWFRUQHURIWKHFRQWUROSDQHOFDELQHWDVLOOXVWUDWHGEHORZ,WLVVHFXUHGWRWKH 3(0VWXGVRQWKHEDFNZDOORIWKHFDELQHWZLWKWZRVXSSOLHGKH[QXWV ,03257$17:KHQWKH%5.7LVLQVWDOOHGWKH8QLPRGHFDELQHWFDQ KROGDPD[LPXPRIWZR$PS+RXUEDWWHULHVZLWKWKHRULHQWDWLRQLOOXVWUDWHGEHORZ TB3 TB5 TB4 TB6 TB7 TB8 JP3 CUT TO DISABLE LOCAL CHARGER JP5 4XTM OPT BD JP11 JP10 AC POWER MAINTENANCE FIRE ALARM ALARM SILENCED SUPERVISORY DISABLED BATTERY TROUBLE GROUND JP2 DISABLE GND FLT 4 DEF AB C 5 6 JP7 EVENT 9 JP6 J168 TUV PRS OPT SLC DRILL J8 J6 WXY TB1 ALARM SILENCE OPT DACT ENTER ESC LCD DISPLAY MO DE # 0 * J2 CLR CUT TO MNO MONITOR 4XTM JKL GHI J17 7 ACK/STEP 3 JP8 1st TB2 KEYPAD I/F JP4 HOLD 2 SEC 1 2 RESET3 -/. QZ J3 RECALL CB1 HOT NEUT EARTH +BATTERY- J7 J12 Mount BRKT-9600 to PEM studs on back of cabinet using supplied hex nuts. Unimode 9600 Cabinet 96brkmnt.cdr 2 1 Figure 2.13 BRKT-9600 Bracket Installation 8QLPRGH31& ,QVWDOODWLRQ 2SWLRQDO0RGXOHVDQG'HYLFHV 0RGXOH,QVWDOODWLRQRQ%5.7 7KHIROORZLQJPRGXOHVFDQEHLQVWDOOHGLQVLGHWKH8QLPRGHFDELQHWXVLQJWKH %5.78QLYHUVDO%UDFNHW ✓ ADT-UDACT Digital Alarm Communicator/Transmitter - installs at standoff location (A) ✓ ADT-ACM-8R Annunciator Control Module (Relay) - installs at standoff location (A) 5HIHUWRWKHDSSURSULDWHPRGXOHPDQXDOIRUGHWDLOHGLQIRUPDWLRQRQPRGXOHRSHUDWLRQ DQGZLULQJ 1. Install the two supplied standoffs in location (A) as indicated in Step 1 of the following illustration 2. Position the module bottom in the slot located in the bottom of the BRKT-9600 as indicated in Step 2 of the following illustration 3. Secure the module to the standoffs installed in the top of the BRKT-9600 with two mounting screws as indicated in Step 3 of the following illustration 4. Refer to the appropriate module manual for detailed information on wiring the module for power, communication, etc. 5. Install a maximum of two 12 Amp Hour batteries with the orientation illustrated in Figure 2.13. Larger batteries require a separate UL listed battery box 1RWH'RQRWEULQJZLULQJRUFRQGXLWLQWRWKHERWWRPRIWKHFDELQHWIRUWKLV DSSOLFDWLRQ BRKT-9600 BRKT-9600 (A) (A) BRKT-9600 standoffs mounting screws Step 1 module 96brcksd.cdr 9600brkt.cdr module Slot Step 2 Step 3 Figure 2.14 BRKT-9600 Module Installation Steps 8QLPRGH31& 2SWLRQDO0RGXOHVDQG'HYLFHV ,QVWDOODWLRQ 2.6.5.4 ADT-ACS and ADT-AFM Series Annunciators $'7$&6DQG$'7$)06HULHV$QQXQFLDWRUVSURYLGHYLVXDOLQGLFDWLRQVRI)$&3 VWDWXVLQUHPRWHORFDWLRQV5HIHUWRWKHDSSURSULDWHDQQXQFLDWRUPDQXDOIRU LQIRUPDWLRQRQLQVWDOODWLRQZLULQJDQGRSHUDWLRQ $'7$&6DQQXQFLDWRUDGGUHVVLQJLVVSHFLILFWRWKH8QLPRGHFRQWUROSDQHO7KH IROORZLQJWDEOHGHVFULEHVWKH$'7$&6DQQXQFLDWRUDGGUHVVHVDQGWKHFRUUHVSRQGLQJ DGGUHVVDEOHGHYLFHVWKDWZLOOEHDQQXQFLDWHGDWHDFKDQQXQFLDWRUDGGUHVV ADT-ACS Annunciator Address 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 Annunciator Displays the Following Points 8 General System Status Points & Zones 1 - 56 Zones 57 - 99 & 2 NACs Loop 1, Module Addresses 1 - 64 Loop 2, Module Addresses 1 - 64 Loop 1, Module Addresses 65 - 128 Loop 2, Module Addresses 65 - 128 Loop 1, Module Addresses 129 - 159 & Loop 2 Module Addresses 129 - 159 Loop 1, Detector Addresses 1 - 64 Loop 2, Detector Addresses 1 - 64 Loop 1, Detector Addresses 65 - 128 Loop 2, Detector Addresses 65 - 128 Loop 1 Detector Addresses 129 - 159 & Loop 2 Detector Addresses 129 - 159 not used not used not used not used not used not used not used 8 General System Status Points & Zones 1 - 56 Zones 57 - 99 & 2 NACs Loop 1, Module Addresses 1 - 64 Loop 2, Module Addresses 1 - 64 Loop 1, Module Addresses 65 - 128 Loop 2, Module Addresses 65 - 128 Loop 1, Module Addresses 129 - 159 & Loop 2 Module Addresses 129 - 159 Loop 1, Detector Addresses 1 - 64 Loop 2, Detector Addresses 1 - 64 Loop 1, Detector Addresses 65 - 128 Loop 2, Detector Addresses 65 - 128 Loop 1 Detector Addresses 129 - 159 & Loop 2 Detector Addresses 129 - 159 not used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• • • • • • • • 8QLPRGH31& General Alarm General Trouble General Supervisory Alarm Silenced System Off Normal AC Loss Battery Fault NAC Fault 3URJUDPPLQJ SECTION 3 3URJUDPPLQJ'DWD(QWU\ Programming 3.1 Programming Data Entry Programming can be accomplished using the Unimode 9600 keypad or by connecting an optional standard computer keyboard. The keyboard can be connected to the PS-2 connector J7 on the control panel main circuit board. The information presented in this section refers to programming the Unimode 9600 via the onboard keypad. If an optional computer keyboard is connected to the Unimode 9600 main circuit board, the following table describes the keyboard keys which correspond to the onboard keypad keys. Keypad Keys Computer Keyboard Keys 1st Event Home CLR Delete ESC Esc RECALL Insert * * # # A-Z A-Z 0-9 0-9 (on QZ key) Space bar — — / / • • ENTER Enter Note: The main keypad function keys (ACK/STEP, ALARM SILENCE, DRILL and RESET) are not available on the keyboard. 8QLPRGH31& 8VHU3URJUDPPLQJ 3URJUDPPLQJ 3.2 User Programming !! The Unimode 9600 is completely field programmable and requires no special software skills. While programming the Unimode 9600, the fire protection capabilities of the control panel are enabled. Site-specific programming may be accomplished in three ways: • Autoprogramming Feature - This is a convenient method for quickly bringing the FACP addressable SLC devices on-line without the necessity of programming each device individually. Refer to "Autoprogram" on page 87 for a detailed description of Autoprogramming • Manual programming or editing, using the FACP keypad or a PC keyboard • Off-line Programming and Editing Feature - allows creation and editing of sitespecific custom programs using a Windows-based computer. For programs requiring a large amount of data entry, this method may be preferred. A PK-9600 programming kit can be ordered for this purpose The System All Normal screen will be displayed in a programmed system with no active alarms, troubles or supervisories, as illustrated below: SYSTEM@ALL@NORMAL 10:00A@010801 Programming and Read Status mode can be entered while the panel is in any mode of operation. If the panel is in alarm, the alarm condition must be acknowledged before entering other modes. To access any of the programming or read status features, the Enter or Mode key must be pressed, which will cause the LCD to display the following: 1=READ@STATUS 2=PROGRAMMING See Page Pressing 1, while this screen is being displayed, will cause the control panel to enter the Read Status feature which allows the user to view the programmed features and status of the control panel The Read Status feature is not password protected. Refer to "Read Status" on page 117 for a detailed description of this feature. Pressing 2 will select user Programming which may only be accomplished by an authorized person. After pressing 2, a screen will prompt for a password. After entering the correct password, the user may select from a list of programming options. Exit Programming or Read Status The programmer can exit Read Status or Programming mode by repeatedly pressing the keypad ESC (Escape) key until the display reads System All Normal. Note that the data which is entered during Programming mode is not saved until the programmer exits this mode by repeatedly pressing the ‘ESC’ key. If the Reset key is pressed or power is lost before exiting Programming mode, all data which was just entered will be lost. 8QLPRGH31& 3URJUDPPLQJ ,QLWLDO3RZHUXS User Programming Levels There are two user programming levels: • User Master Program Level 1 is used for programming panel specific data relating to device types, zoning, messages, control panel functions, etc. • User Maintenance Program Level 2 is used by a qualified operator to access features such as Disable/Enable, View and Clear History, Walktest and System Time Change. 3.3 Initial Power-up The following sections describe the initial programming procedures for a new system. The same procedures are used to modify programming in an existing system. After completing the wiring of addressable devices to the SLC, apply power to the control panel. If the addressable devices have not yet been programmed into the FACP, their LEDs will not flash and the following trouble message will be displayed. TROUBL@IN@SYSTEM NO@DEVICES@INSTALLED 09:03A@010801 3.4 Programming Screens Description See Page Two main options are available when the Enter key is pressed: Read Status and Programming. Each option has multiple functions or features which may be chosen. To view all of the choices, it is necessary that the programmer scroll through a number of additional subscreens. These selections are displayed on multiple screens to make them more readable for the programmer. Refer to "Master Programming Level" on page 42, for additional information on the various screens. The title of the main option screen will always be displayed at the top of the subscreens for the programmer’s convenience. If additional subscreens exist, an Up or Down arrow will be displayed in the upper right corner of the screen being viewed. The programmer can then press the keypad Up or Down arrow key to view the new subscreen. To select one of the choices in a screen, the programmer presses the keypad numerical key corresponding to the desired choice. Note that subscreens may also have multiple options which require viewing more than one screen. The same process, as detailed in the previous paragraphs, is followed to view all option choices. 3.5 Programming and Passwords See Page There are two factory set programming passwords which will access the Programming screens as indicated in the following examples. From either of the screens, access to specific system and device features or programming may be obtained. All user programming entries are stored in nonvolatile memory. The factory set passwords can be changed by the user as described in "Password Change" on page 93. If an invalid password is entered, the blinking cursor will return to the first password character position. To exit Programming or Read Status mode at any time, press the ESC (Escape) key repeatedly. Note that Programming mode must be exited using the ESC key in order to store the program data entered during this mode. If the Reset key is pressed or power is lost before exiting Programming mode, the data just entered will not be saved. 8QLPRGH31& 3URJUDPPLQJDQG3DVVZRUGV 3URJUDPPLQJ To access user Programming mode, press the Enter or Mode key. The LCD will display the following: 1=READ@STATUS 2=PROGRAMMING To enter the user Programming mode, press 2. The display will read as follows: PROGRAMMING ENTER@PASSWORD ***** Entering the Master level password (default 00000) will cause the following screen to appear: @@@@PROGRAMMING 1=POINT@PROGRAM 2=ZONE@SETUP 3=LOOP@SETUP If the Maintenance level password (default 11111) is entered, the following screen will appear: @@@@PROGRAMMING 1=POINT PROGRAM 2=HISTORY 3=PROGRAM CHECK Note that in the two preceding screens, an arrow appears to inform the programmer that additional options can be viewed by pressing the keypad down arrow key. 8QLPRGH31& 3URJUDPPLQJ 0DVWHU3URJUDPPLQJ/HYHO 3.6 Master Programming Level When the Master Program Level password is entered, the control panel will enter user Programming mode. In this mode, the piezo sounder remains off, the trouble relay is activated and the system Trouble LED flashes until Programming mode is exited. The following display will appear: @@@@PROGRAMMING 1=POINT@PROGRAM 2=ZONE@SETUP 3=LOOP@SETUP Programming Screen #1 The down arrow which appears in the display indicates that additional programming choices can be viewed by pressing the down arrow key on the keypad. If a down and up arrow appear in the display, pressing the ‘down’ arrow key will display the subsequent Programming Screens as illustrated below while pressing the ‘up’ arrow key will display the previous screen. @@@@PROGRAMMING 1=SYSTEM@SETUP 2=AUTOPROGRAM 3=VERIFY@LOOPS Programming Screen #2 @@@@PROGRAMMING 1=HISTORY 2=WALKTEST 3=OPTION@MODULES Programming Screen #3 @@@@PROGRAMMING 1=PASSWORD@CHANGE 2=CLEAR@PROGRAM 3=PROGRAM@CHECK Programming Screen #4 8QLPRGH31& 0DVWHU3URJUDPPLQJ/HYHO 3URJUDPPLQJ 3.6.1 Point Program PROGRAMMING 1=POINT PROGRAM 2=ZONE SETUP 3=LOOP SETUP Programming Screen #1 The Point Program option allows the programmer to add a new addressable device to an SLC loop, delete an existing device from a loop or change the programming for an existing device. Pressing 1, while viewing Programming Screen #1, will select the Point Program option and display the following screen: @@@POINT@PROGRAM @@@@SELECT@LOOP 1=LOOP@1 2=LOOP@2 Point Program Screen #1 The programmer selects the desired SLC loop by pressing 1 or 2 in Point Program Screen #1, which causes the panel to display the following screen: @@@POINT@PROGRAM @@@@SELECT@TYPE 1=DETECTOR 2=MODULE Point Program Screen #2 3.6.1.1 Detector Programming 3UHVVLQJZKLOHYLHZLQJ3RLQW3URJUDP6FUHHQZLOODOORZWKHSURJUDPPHUWRDGG GHOHWHRUFKDQJHWKHSURJUDPPLQJRIDQDGGUHVVDEOHGHWHFWRU7KHIROORZLQJVFUHHQ ZLOOEHGLVSOD\HGE\WKHFRQWUROSDQHO @@@@@@DETECTOR 1=ADD 2=DELETE 3=EDIT Detector Screen 3.6.1.1.1 Add Detector 3UHVVLQJZKLOHYLHZLQJWKH'HWHFWRU6FUHHQZLOOGLVSOD\WKHIROORZLQJVFUHHQZKLFK DOORZVWKHSURJUDPPHUWRDGGDQHZGHWHFWRUDGGUHVVWRSURJUDPPLQJ @@@@ADD@DETECTOR ENTER@DETECTOR# *** Add Detector Screen $IODVKLQJFXUVRUZLOODSSHDULQWKHSRVLWLRQRIWKHILUVWDVWHULVNWRWKHOHIW7KH SURJUDPPHUNH\VLQWKHWKUHHGLJLWGHWHFWRUDGGUHVVVXFKDV 8QLPRGH31& 3URJUDPPLQJ 0DVWHU3URJUDPPLQJ/HYHO :KHQWKHODVWGLJLWLVNH\HGLQWKHIROORZLQJVFUHHQZLOOEHGLVSOD\HG @@@@ADD@DETECTOR DETECTOR#@@@@@@@005 IS@ADDED 7KHSURJUDPPHUFDQFRQWLQXHDGGLQJGHWHFWRUVE\SUHVVLQJWKH(6&RUOHIWDUURZNH\ ZKLFKZLOOUHWXUQWKHGLVSOD\WRWKH$GG'HWHFWRU6FUHHQ DETECTOR 1=ADD 2=DELETE 3=EDIT Detector Screen 3.6.1.1.2 Delete Detector 3UHVVLQJLQWKH'HWHFWRU6FUHHQZLOOGLVSOD\WKH'HOHWH'HWHFWRU6FUHHQZKLFKDOORZV WKHSURJUDPPHUWRGHOHWHDVSHFLILFGHWHFWRU @@DELETE@DETECTOR ENTER@DETECTOR# *** Delete Detector Screen $IODVKLQJFXUVRUZLOODSSHDULQWKHSRVLWLRQRIWKHILUVWDVWHULVNWRWKHOHIW7KH SURJUDPPHUNH\VLQWKHWKUHHGLJLWGHWHFWRUDGGUHVVVXFKDV:KHQWKHODVWGLJLW LVNH\HGLQWKHIROORZLQJVFUHHQZLOOEHGLVSOD\HG @@DELETE@DETECTOR DETECTOR#@@@@@@@005 IS@DELETED 7KHSURJUDPPHUFDQFRQWLQXHGHOHWLQJGHWHFWRUVE\SUHVVLQJWKH(6&RUOHIWDUURZNH\ ZKLFKZLOOUHWXUQWKHGLVSOD\WRWKH'HOHWH'HWHFWRU6FUHHQ 3.6.1.1.3 Edit Detector TKHSURJUDPPHUFDQFKDQJHDGHWHFWRUVH[LVWLQJRUIDFWRU\GHIDXOWSURJUDPPLQJE\ SUHVVLQJLQWKH'HWHFWRU6FUHHQ7KHIROORZLQJVFUHHQZLOOEHGLVSOD\HG @@EDIT@DETECTOR ENTER@POINT@ADDRESS *** Edit Detector Screen $IODVKLQJFXUVRUZLOODSSHDULQWKHSRVLWLRQRIWKHILUVWDVWHULVNWRWKHOHIW7KH SURJUDPPHUNH\VLQWKHWKUHHGLJLWGHWHFWRUDGGUHVVVXFKDV 8QLPRGH31& 0DVWHU3URJUDPPLQJ/HYHO 3URJUDPPLQJ :KHQWKHODVWGLJLWLVNH\HGLQLIWKHVHOHFWHGDGGUHVVKDVQRWEHHQDGGHGWR SURJUDPPLQJDVFUHHQVKRZLQJLQIRUPDWLRQDERXWDGHYLFHZLWKWKHKLJKHVWDGGUHVV WKDWLVLQVWDOOHGZLOOEHGLVSOD\HG ,IQRGHWHFWRUVKDYHEHHQLQVWDOOHGRQWKHORRSWKHIROORZLQJZLOOEHGLVSOD\HG @@@@NO@DETECTOR @@@@@INSTALLED Edit Detector Screen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dit Detector Screen #1 ,IWKHVHOHFWHGDGGUHVVKDVEHHQDGGHGWRSURJUDPPLQJDQGDGHWHFWRUVXFKDVD SKRWRHOHFWULFGHWHFWRUZLWKWKHVHOHFWHGDGGUHVVLVSK\VLFDOO\LQVWDOOHGRQWKH6/&DQG LVFRPPXQLFDWLQJZLWKWKHFRQWUROSDQHOWKHIROORZLQJZLOOEHGLVSOD\HG @NORMAL@SMOKE@(PHOTO) @********************* @@@@@@@@@@@@@@@@ZNNN @@@@@@@@@@@@@V@@@1D017 Edit Detector Screen #1 7RFKDQJHWKHSURJUDPPLQJIRUWKHGLVSOD\HGGHWHFWRUSUHVVWKHNH\ERDUGµGRZQ¶ DUURZNH\WRYLHZWKH(GLW'HWHFWRUVFUHHQV ,QWKHSUHFHGLQJH[DPSOH ✓ Normal - indicates that the detector with the selected address is physically installed on the SLC and communicating with the control panel (enabled) ✓- represents the adjective and noun, which have been programmed, describing the location of the displayed device ✓ ZNNN - represents the first of five possible software zones that the detector is assigned to (NNN = the three digit zone number from 000 - 099) ✓ V or * - indicates whether or not alarm verification is enabled (V = alarm verification enabled and * = alarm verification disabled) ✓ 1D017 - represents the Loop, Device type and Device address (1 = SLC Loop 1, D=Detector and 017 = Detector Address 017) 8QLPRGH31& 3URJUDPPLQJ 0DVWHU3URJUDPPLQJ/HYHO 7KHIROORZLQJH[DPSOHVVKRZWKHHGLWLQJRIDSKRWRHOHFWULFsmoke detector with address 017, located on the first SLC loop: EDIT@DETECTOR@1D017 1=ENABLED@@@@@@@@YES 2=TYPE@@SMOKE(PHOTO) 3=VERIFICATION@@@OFF Edit Detector Screen #2 EDIT@DETECTOR@1D017 1=WALKTEST@@@@@@@@NO 2=PAS@@@@@@@@@@@@@NO 3=PRE-SIGNAL@@@@@@NO Edit Detector Screen #3 EDIT@DETECTOR@1D017 1=ZONE@ASSIGNMENT @@@@00@**@**@**@** Edit Detector Screen #4 EDIT@DETECTOR@1D017 1=NOUN/ADJECTIVE 2=DESCRIPTION ******************** Edit Detector Screen #5 (QDEOH'LVDEOH'HWHFWRU EDIT DETECTOR 1=ENABLED 2=TYPE 3=VERIFICATION Edit Detector Screen #2 7R(QDEOHRU'LVDEOHWKHGHWHFWRUSUHVVWKHNH\ZKLOHYLHZLQJWKH(GLW'HWHFWRU 6FUHHQ(DFKSUHVVRIWKHNH\ZLOOWRJJOHWKHVFUHHQEHWZHHQ(QDEOHG @@@@@@@@@@@@@@@@ZNNN @@@@@@@@@@@@@@@1M012 ,IWKHVHOHFWHGDGGUHVVKDVEHHQDGGHGWRSURJUDPPLQJDQGDPRGXOHVXFKDVD PRQLWRUPRGXOHZLWKWKHVHOHFWHGDGGUHVVLVSK\VLFDOO\LQVWDOOHGRQWKH6/&DQGLV FRPPXQLFDWLQJZLWKWKHFRQWUROSDQHOWKHIROORZLQJVFUHHQZLOOEHGLVSOD\HG @NORMAL@MONITOR @@@@@@@ @@@@@@@@@@@@@@@@@ZNNN @@@@@@@@@@@@@@@@1M012 7RFKDQJHWKHSURJUDPPLQJIRUWKHGLVSOD\HGPRGXOHSUHVVWKHNH\ERDUGGRZQDUURZ NH\WRYLHZWKHIROORZLQJ(GLW0RQLWRUVFUHHQV,QWKHSUHFHGLQJH[DPSOH ✓ Normal - indicates that the module with the selected address is physically installed on the SLC and communicating with the control panel (enabled) ✓ - represents the adjective and noun, which have been programmed, describing the location of the displayed device ✓ ZNNN - represents the first of five possible software zones that the module is assigned to (NNN = the two digit zone number from 000 - 099) ✓ 1M012 - represents the Loop, Device type and Device address (1 = SLC Loop 1, M=Module and 012 = Module Address 012) See Page ,IWKHVHOHFWHGDGGUHVVFRUUHVSRQGVWRDFRQWUROPRGXOHDVFUHHQGLVSOD\LQJ LQIRUPDWLRQDERXWWKHFRQWUROPRGXOHZLWKWKHVHOHFWHGDGGUHVVZLOOEHGLVSOD\HGDV VKRZQLQ(GLW0RGXOH6FUHHQIRU&RQWURO0RGXOHVRQSDJH 8QLPRGH31& 3URJUDPPLQJ 0DVWHU3URJUDPPLQJ/HYHO ,IWKHVHOHFWHGDGGUHVVFRUUHVSRQGVWRDPRQLWRUPRGXOHDVFUHHQGLVSOD\LQJ LQIRUPDWLRQDERXWWKHPRGXOHZLWKWKHVHOHFWHGDGGUHVVZLOOEHGLVSOD\HGDVLOOXVWUDWHG LQWKHIROORZLQJ @NORMAL@MONITOR @@@@@@ @@@@@@@@@@@@@@@@@ZNNN @@@@@@@@@@@@@@@@1M012 EDIT@MONITOR@@1M012 1=ENABLED@@@@@@@@YES 2=TYPE@@MONITOR Edit Monitor Screen #2 EDIT@MONITOR@@1M012 1=PRE-SIGNAL@@@@@@NO 2=PAS@@@@@@@@@@@@@NO Edit Monitor Screen #3 EDIT@MONITOR@@1M012 1=WALKTEST@@@@@@@YES 2=ZONE@ASSIGNMENT 00@**@**@**@** Edit Monitor Screen #4 EDIT@MONITOR@@1M012 1=ADJECTIVE/NOUN 2=DESCRIPTION ******************** Edit Monitor Screen #5 8QLPRGH31& 0DVWHU3URJUDPPLQJ/HYHO 3URJUDPPLQJ (QDEOH'LVDEOH0RGXOH 7R(QDEOHRU'LVDEOHWKHPRQLWRUPRGXOHSUHVVWKHNH\ZKLOHYLHZLQJWKH(GLW 0RGXOH6FUHHQ(DFKSUHVVRIWKHNH\ZLOOWRJJOHWKHVFUHHQEHWZHHQ(QDEOHG @@@@@@@@@@SW@@ZNNN @@@@@@@@@@@@@@1M002 Edit Control Screen #1 ,QWKHSUHFHGLQJH[DPSOH ✓ Normal - indicates that the module with the selected address is physically installed on the SLC and communicating with the control panel (enabled) ✓ - represents the adjective and noun, which have been programmed, describing the location of the displayed device ✓ Control - indicates that the selected module is a control module ✓ S or * - represents Silenceable (S) or Nonsilenceable (*) ✓ W or * - represents Waterflow Timer Delay (W = Waterflow Timer Delay enabled, * = Waterflow Timer Delay disabled) ✓ ZNNN - represents the first of five possible software zones that the module is assigned to (NNN = the three digit zone number from 000 - 099) ✓ 1M002 - represents the Loop, Device type and Device address (1 = SLC Loop 1, M=Module and 002 = Module Address 02) 8QLPRGH31& 3URJUDPPLQJ 0DVWHU3URJUDPPLQJ/HYHO 7RFKDQJHWKHSURJUDPPLQJIRUWKHGLVSOD\HGPRGXOHSUHVVWKHNH\ERDUGGRZQDUURZ NH\WRYLHZWKHIROORZLQJ(GLW&RQWUROVFUHHQV EDIT@CONTROL 1=ENABLED@@@@@@@@YES 2=TYPE@@CONTROL 3=SILENCEABLE@@@@YES Edit Control Screen #2 EDIT@CONTROL 1=WALKTEST@@@@@@@YES 2=ZONE@ASSIGNMENT 00@**@**@**@** Edit Control Screen #3 EDIT@CONTROL 1=NOUN/ADJECTIVE 2=DESCRIPTION ******************** Edit Control Screen #4 EDIT CONTROL 1=ENABLED 2=TYPE 3=SILENCEABLE Edit Control Screen #2 (QDEOH'LVDEOH0RGXOH 7R(QDEOHRU'LVDEOHWKHFRQWUROPRGXOHSUHVVWKHNH\ZKLOHYLHZLQJWKH(GLW &RQWURO6FUHHQ(DFKSUHVVRIWKHNH\ZLOOWRJJOHWKHVFUHHQEHWZHHQ(QDEOHG @ @@@@@@@@@@@@@@@Z000 @10*00A@010801@1M001 After completion of the Walktest, press the Esc (Escape) key to exit Walktest Mode and return to the Walktest Screen. The results of the Walktest can now be viewed by pressing 3 while viewing the Walktest Screen. The following screen will be displayed: @@WALKTEST@RESULTS View Result Screen Use the up and down arrow keys to view all of the walktest results which will be displayed as illustrated in the preceding screen. Note that the Walktest log is stored in RAM. If all power (AC and DC) is removed from the FACP, the Walktest log information will be lost. This information is also overwritten when subsequent walktests are performed. 8QLPRGH31& 0DVWHU3URJUDPPLQJ/HYHO 3URJUDPPLQJ 3.6.9 Option Modules PROGRAMMING 1=HISTORY 2=WALKTEST 3=OPTION MODULES Programming Screen #3 Options available for the Unimode 9600 include ADT-ACS Series, Graphic and LCD annunciators, ADT-UDACT Digital Alarm Communicator/Transmitter (with software #UDACT02.0 and above), printer connection for acquiring hardcopy printouts of panel data and PC (Personal Computer) connection for uploading and downloading panel data. Pressing 3 while viewing Programming Screen #3 will display the following screen: @@@OPTION@MODULES 1=ANNUNCIATORS/UDACT 2=(NOT@USED) 3=PRINTER/PC@@PR4800 Options Screen Note that PR4800 in the display indicates that a supervised printer, configured for 4800 baud, has been previously programmed into the system. 3.6.9.1 Annunciators/UDACT 3UHVVLQJZKLOHYLHZLQJWKH2SWLRQV6FUHHQZLOOFDXVHWKHFRQWUROSDQHOWRGLVSOD\WKH IROORZLQJVFUHHQV @@@@ANNUNCIATOR 1=TERM@ENABLED@@@YES 2=ACS@ENABLED@@@@YES 3=UDACT@@@@@@@@@@YES Annunciator Screen #1 @@@@ANNUNCIATOR 1=ACS@INSTALLED Annunciator Screen #2 $7HUPLQDO0RGHDQQXQFLDWRU $&60RGHDQQXQFLDWRUDQGUHPRWH8'$&7FDQEH LQVWDOOHGLQWKH8QLPRGHV\VWHP7RHQDEOHDQ\RIWKHVHGHYLFHVSUHVVWKH QXPEHUFRUUHVSRQGLQJWRWKHVHOHFWHGGHYLFHVKRZQLQ$QQXQFLDWRU6FUHHQVRWKDW SYSTEM ALL NORMAL 10:00A 010801 The Unimode 9600 performs the following functions at regular intervals while in Normal mode: ✓ Monitors AC input voltage and battery voltage ✓ Monitors and reports status of SLC loop(s), option cards and control panel ✓ Polls all devices on the SLC loop(s) and flashes each device LED while checking for valid replies, alarms, troubles, etc. ✓ Refreshes LCD display and updates time ✓ Scans control panel keypad for key presses ✓ Performs autotest for all SLC devices ✓ Tests memory ✓ Updates and reads all communications busses (EIA-485, EIA-232, etc.) 4.4 Trouble Operation With no alarms in the system, the detection of a trouble will cause the following: • The piezo to pulse 1 second On and 1 second Off • The system Trouble LED to flash one second On and one second Off • The trouble relay to activate • TROUBL with device type, noun/adjective, address and trouble description will appear on the LCD display • The same message, along with the time and date, is sent to the optional printer and the history buffer. Note that specific troubles will initiate additional actions; for example, loss of AC power will turn off the AC Power LED, a ground fault will turn on the Ground LED, etc. 8QLPRGH31& 2SHUDWLQJ,QVWUXFWLRQV 7URXEOH2SHUDWLRQ Addressable Smoke Detectors, Monitor Modules and Control Modules For addressable devices connected to the SLC loop, the following is a typical message that could appear on the LCD display for a device trouble: TROUBL SMOKE (PHOTO) INVREP 10:00A 010801 1D001 The information displayed in the above example provides the following information: • First line in display: ✓ The type of event; in this example TROUBL indicating a device trouble ✓ Device type identifier; in this example, SMOKE (PHOTO) indicates a Photoelectric smoke detector. Other device type identifiers which can be displayed include SMOKE (ION) for Ionization Detector, HEAT for Heat Detector, CONTROL for Control Module and MONITOR for Monitor Module, PULL STATION for a manual pull box, etc. Refer to "Edit Detector" on page 44, "Edit Module Screen for Monitor Module" on page 54 and "Edit Module Screen for Control Modules" on page 63 for information on additional device types. • Second line in display: ✓ ; refers to the user programmed adjective descriptor from library list resident in the control panel or custom entry via PC. ✓ ; refers to the user programmed noun descriptor from library list resident in the control panel or custom entry via PC. • Third line in display: INVREP indicates an invalid reply from the addressable device. Other possible troubles include: ❒ SHORT - indicating a shorted circuit on an addressable device ❒ OPEN - indicating an open circuit on an addressable device ❒ DIRTY1 - maintenance alert indicating that a detector is near but below the allowed alarm limit and is in need of maintenance before the performance is compromised ❒ DIRTY2 - maintenance alert indicating that a detector needs immediate maintenance since it has been within 80% of its alarm threshold for 24 hours ❒ INVREP - maintenance alert indicating a hardware problem in the detector ❒ TEST F - indicating a detector has failed the automatic test operation which functionally checks its sensing chamber and electronics ❒ INV ID - indicating that an incorrect device code (Type ID) has been programmed for an installed device (for example, Photo has been programmed but an Ion detector has been installed) ❒ SW TBL - indicating a module has failed the testing of its Class A switching relay • Fourth line in display: ✓ Time; the current time in this example is 10:00A which represents 10:00 AM ✓ Date; the current month, day and year in this example is 01 for January, 08 for the 8th day of the month and 01 for the year 2001 ✓ Device Address; 1D001 in this example 1 represents SLC Loop1, D represents a detector and 001 represents device address 001 8QLPRGH31& $ODUP2SHUDWLRQ 2SHUDWLQJ,QVWUXFWLRQV Pressing the Acknowledge/Step or Alarm Silence key will cause the pulsing piezo to silence and the system Trouble LED to change from flashing to on steady. This block acknowledgment occurs regardless of the number of troubles, alarms and supervisory events active in the system. When the Acknowledge/Step key is pressed and at least one new alarm or trouble exists in the system, the ‘acknowledge’ message is sent to the printer and history file. If the trouble clears, either before or after the Acknowledge/Step key is pressed, the ‘clear trouble’ message is sent to the printer and history file. If all troubles clear and there are no supervisory or fire conditions active in the system, the system returns to normal mode operation and the System All Normal message is shown on the LCD display and sent to the history and printer files. The auto-restore feature will restore cleared troubles even if the troubles were never acknowledged. Note that pressing the Alarm Silence key when only troubles exist in the system will have the same effect as pressing the Acknowledge/Step key except the Alarm Silenced LED will light. If multiple trouble conditions exist in the system, they will be automatically scrolled on the LCD display at a three second rate. If a combination of alarms, troubles and/or supervisory conditions simultaneously occur in the system, only the alarms are scrolled on the display. 4.5 Alarm Operation Alarm operation is similar to trouble operation with the following differences: • • • • • • • • • The piezo sounder produces a steady output as opposed to a pulsed output The Fire Alarm LED flashes 1 second On and 1 second Off The LCD displays Alarm along with the device name, type, address, adjective/noun, associated zones and time/date Alarms latch and are not allowed to clear automatically Alarms activate software zones if so programmed Timers for Silence Inhibit, Autosilence and Trouble Reminder are started Alarms activate the general alarm relay and general alarm zone Z00 The trouble relay is not activated Store event in history buffer A typical alarm display would be as illustrated below: ALARM PULL STATION Z000 10:00A 010801 1M001 Note that the device type, which in this example is PULL STATION, can be any other programmable alarm type. The information displayed in the above example provides the following information: • First line in display: ✓ The type of event; in this example ALARM indicating an alarm condition ✓ Device type identifier; in this example, PULL STATION indicates a manual pull box. Other device type identifiers which can be displayed include SMOKE (ION) for Ionization Detector, HEAT for Heat Detector, CONTROL for Control Module and MONITOR for Monitor Module, PULL STATION for a manual pull box, etc. Refer to "Edit Detector" on page 44, "Edit Module Screen for Monitor Module" on page 54 and "Edit Module Screen for Control Modules" on page 63 for information on additional device types. 8QLPRGH31& 2SHUDWLQJ,QVWUXFWLRQV 6XSHUYLVRU\2SHUDWLRQ • Second line in display: ✓ ; refers to the user programmed adjective descriptor from library list resident in the control panel or custom entry via PC. ✓ ; refers to the user programmed noun descriptor from library list resident in the control panel or custom entry via PC. • Third line in display: Z000 indicates the zone programmed to this device which, in this example, is general alarm Zone 000. Note that a single device can be programmed to five different zones but only the first zone will be displayed. • Fourth line in display: ✓ Time; the current time in this example is 10:00A which represents 10:00 AM ✓ Date; the current month, day and year in this example is 01 for January, 08 for the 8th day of the month and 01 for the year 2001 ✓ Device Address; 1M001 in this example 1 represents SLC Loop1, M represents a module and 001 represents device address 001 4.6 Supervisory Operation Supervisory operation is similar to alarm operation but with the following differences: • The piezo sounder pulses ½ second On and ½ second Off • The Supervisory LED flashes ½ second On and ½ second Off • The LCD displays the status label Active Supervisory along with the device name, type, address, adjective/noun, associated zones and time/date • The supervisory relay is activated • The alarm relay is not activated • Silenced alarms are not resounded • Timers are not started • Store event in history buffer A typical Supervisory event would be displayed as illustrated in the following: ACTIVE SUPERVISORY Z000 10:00A 010801 1M001 Note that, like alarms, supervisory signals latch (except when programmed for supervisory autoresettable) and can be assigned to software zones. Supervisory alarms do not cause resound as do other alarm conditions. Open circuits in supervisory wiring are processed by the control panel the same way as other trouble conditions. Refer to "Alarm Operation" on page 109, for a description of the information displayed on the control panel LCD. 8QLPRGH31& 3URFHVV0RQLWRU2SHUDWLRQ 2SHUDWLQJ,QVWUXFWLRQV 4.7 Process Monitor Operation Process Monitor operation will initiate the following events: • The piezo sounder pulses ¼ second On and ¼ second Off • The LCD displays a process monitor message along with the device name, type, address, adjective/noun, associated zones and time/date • Relays programmed for process monitoring will be activated • The alarm relay is not activated • Silenced alarms are not resounded • Timers are not started • Store event in history buffer Note that, like supervisories, process monitor signals latch (except when programmed for process monitor autoresettable) and can be assigned to software zones. 4.8 Hazard Condition Operation Hazard Condition operation will initiate the following events: • The piezo sounder turns on steady • The LCD displays a hazard message along with the device name, type, address, adjective/noun, associated zones and time/date • Relays programmed for process monitoring will be activated • The alarm relay is not activated • Silenced alarms are not resounded • Timers are not started • Store event in history buffer Hazard conditions do not latch and will therefore clear when the hazard condition is cleared. They can be assigned to software zones. 4.9 Medical Alert Condition Operation Medical Alert Condition operation will initiate the following events: • The piezo sounder turns on steady • The LCD displays a medical alert message along with the device name, type, address, adjective/noun, associated zones and time/date • Relays programmed for medical alert will be activated • The alarm relay is not activated • Silenced alarms are not resounded • Timers are not started • Store event in history buffer Medical alert conditions do not latch and will therefore clear when the medical alert condition is cleared. They can be assigned to software zones. 4.10 NAC Operation There are two programmable NACs (Notification Appliance Circuits) resident on the Unimode 9600 main circuit board. Both NACs may be programmed as silenceable or nonsilenceable and may also be programmed for steady or coded operation. Coded operation provides a choice between March Time, Temporal or California coding. 8QLPRGH31& 2SHUDWLQJ,QVWUXFWLRQV 3URJUDPPHG=RQH2SHUDWLRQ 4.11 Programmed Zone Operation Each addressable detector and monitor module can be assigned to a maximum of five software alarm zones. A general alarm zone Z00 may be listed for output (control) points, but it is not necessary to list Z00 for input points, since this is the default zone for all alarm input devices. Zone Z00 is not activated by supervisory points. When an input device alarms and is not disabled, it activates all software zones assigned to it. An output device that is not disabled is turned on when any of the software zones to which it is programmed become active. 4.12 Disable/Enable Operation Input points which are disabled do not cause an alarm or any zone activation. Disabled output points are held in the off state. All disabled points are treated as if they were in trouble, with the exception being the status label that will be displayed is DISABL. 4.13 Waterflow Circuits Operation If an alarm exists from a monitor module point that has a waterflow type code and its mapped NAC control module outputs are programmed for nonsilenceable operation, the Alarm Silence key will not function. 4.14 Detector Functions Maintenance Alert Each addressable detector is monitored by the control panel for its maintenance status. If a detector is near but below the allowed alarm limit, a ‘maintenance alert’ message will automatically be displayed, signaling that the detector is in need of servicing. Automatic Test Operation An automatic test of an addressable detector is performed each minute, resulting in a complete SLC loop test in approximately 2 hours and 40 minutes (if the loop has the maximum number of devices installed). The detector’s sensing chamber and electronics are functionally tested for normal, safe operation. A trouble message is displayed upon failure of this test. A System Reset will clear this trouble. Type Code Supervision The control panel monitors addressable hardware device codes at slow intervals. Mismatch of any type code, compared to the system program, will cause a device trouble. System Alarm Verification The control panel may be programmed to perform alarm verification to help eliminate the nuisance of false alarms. Alarm verification applies to smoke detectors only. Smoke Detector Data Smoke detector data is monitored by the FACP, eliminating the need to test the sensitivity of each detector at its location. A printout of each detector’s data can be retrieved from the FACP using an optional printer. Detector sensing ability can decrease with age and should be monitored as part of a system’s routine maintenance. 4.15 Time Functions: Real-Time Clock The Unimode 9600 includes a crystal-based clock that provides time of day, date and day of week. Time is displayed as 12 or 24 hour time with month/day/year and is stored in RAM. Daylight savings time change-over is programmable and automatic. If both AC and battery are lost, the time must be reset. 8QLPRGH31& 6\QFKURQL]HG1$&2SHUDWLRQ 2SHUDWLQJ,QVWUXFWLRQV 4.16 Synchronized NAC Operation Synchronization is a panel feature that controls the activation of notification appliances in such a way that all devices will turn on and off at exactly the same time. This is particularly critical when activating strobes which must be synchronized to avoid random activation and a potential hazard or confusion. The FACP can be programmed to operate with a variety of manufacturer’s devices. Important: When a Notification Appliance Circuit with a mix of audible and visual devices is programmed for silenceable and the synchronization feature is selected, only the audible devices will be turned off if the Silence key is pressed. The visual devices (strobes, etc.) will continue to operate. 4.17 Coded Operation The two NAC circuits resident on the control panel main circuit board can be programmed for coded operation. The available pulse rates which can be programmed for coded operation are as follows: • • • Continuous: March Time: Temporal Code: • • California Code: Two-Stage Steady output with no pulsing Pulses at 120 ppm (pulses per minute) Pulses at ½ second On, ½ second Off, ½ second On, ½ second Off, ½ second On, 1½ second Off 10 seconds On, 5 seconds Off Pulses at 20 ppm (pulses per minute) for 5 minutes and then changes to on steady 4.18 Presignal Presignal option programs an initiating device to delay the activation of NACs and/or control modules while allowing visual verification by a person. Once a detector or monitor module triggers an alarm, the onboard piezo sounds immediately, but the NACs are not activated for a user programmed time duration of up to three minutes. Note that the alarm relay and communicator will respond to the initial alarm immediately. In addition, Zone 98 will activate. This zone can be programmed to a control module which may be used to activate a sounder or indicator which the installer designates as a Presignal indication. 'RQRWDVVLJQ=RQHWRD1RWLILFDWLRQ$SSOLDQFH&LUFXLWZKHQXVLQJWKLV ]RQHWRLQGLFDWHD3UHVLJQDOFRQGLWLRQ After the programmed delay, the NACs will activate if the source of the alarm is not cleared. Note that if a second alarm occurs during the programmed time delay, the alarm will be processed immediately, causing activation of the appropriate output zones. The events which occur upon Presignal activation are as follows: ✓ ✓ ✓ ✓ onboard piezo sounds immediately control panel LCD display will indicate a presignal event and the active point control points programmed to Zone 98 will activate annunciators (if enabled) will sound the local piezo, and pulse the alarm LED and zone LED ✓ outputs (NACs and control modules) of associated zones will be inhibited from activating for a user programmed time delay of up to three minutes ✓ second alarm occurring anytime during the time delay will cause immediate activation of all associated outputs Presignal does not affect monitor modules programmed as waterflow, supervisory, process monitoring or remote switches. Presignal operation requires the approval of the local Authority Having Jurisdiction. 8QLPRGH31& 2SHUDWLQJ,QVWUXFWLRQV 3RVLWLYH$ODUP6HTXHQFH 4.19 Positive Alarm Sequence PAS (Positive Alarm Sequence) option will program an initiating device to delay panel activation (including alarm relay and communicator) for a period of 15 seconds. Zone 97, however, will activate immediately and may be used to connect a signaling device to indicate PAS activation. 'RQRWDVVLJQ=RQHWRD1RWLILFDWLRQ$SSOLDQFH&LUFXLWZKHQ XVLQJWKLV]RQHWRLQGLFDWHD3$6FRQGLWLRQ When a detector or monitor module triggers an alarm, the onboard piezo sounds immediately, but the NACs are prevented from activating for 15 seconds. This inhibit time is factory set and cannot be changed. Pressing the Alarm Silence or Acknowledge/ Step key during the 15 second inhibit time will silence the piezo sounder and start a timer which prevents activation of NACs for an additional time duration which can be user programmed for up to three minutes. After the programmed delay, the NACs will activate if the source of the alarm is not cleared. Note that if a second alarm occurs during either time delay, the alarm will be processed immediately, causing activation of the appropriate output zones. The events which occur upon PAS activation are as follows: ✓ onboard piezo sounds immediately ✓ control panel LCD display will indicate a presignal event and the active point ✓ control points programmed to Zone 97 will activate ✓ annunciators (if enabled) will sound the local piezo, and pulse the alarm LED and zone LED ✓ outputs (NACs and control modules) of associated zones will be inhibited from activating for a factory set duration of 15 seconds ✓ pressing the Alarm Silence or Acknowledge/Step key will start a timer which inhibits output activation for additional time delay of up to three minutes which is user programmable ✓ second alarm occurring anytime during either time delay will cause immediate activation of all associated outputs PAS does not affect monitor modules programmed as waterflow, supervisory, process monitoring or remote switches. PAS operation requires the approval of the local Authority Having Jurisdiction. Note that the PAS BYPASS monitor type code, when activated, will inhibit the PAS capability until the PAS BYPASS monitor is deactivated. While PAS is inhibited, signaling devices will immediately place the control panel into alarm. This feature may be employed by wiring a normally open device, such as a switch, to a monitor module which has been programmed for PAS BYPASS. 8QLPRGH31& 6SHFLDO6\VWHP7LPHUV 2SHUDWLQJ,QVWUXFWLRQV 4.20 Special System Timers 4.20.1 Silence Inhibit Timer This option, if selected, prevents the Alarm Silence key from functioning for 60 seconds following an alarm. A new alarm during the initial 60 seconds will cause the timer to restart with a new 60 seconds. Silence Inhibit operation requires the approval of the local Authority Having Jurisdiction. 4.20.2 Autosilence Timer If Autosilence is selected, the notification appliances, programmed as silenceable, will automatically be silenced after a programmable duration of from 5 to 30 minutes. Pressing the Drill key will restart the timer. Autosilence operation requires the approval of the local Authority Having Jurisdiction. 4.20.3 Trouble Reminder If selected, this feature causes a reminding ‘beep’ every 15 seconds during an alarm (after the Alarm Silence key is pressed) and every two minutes during a trouble condition (after the Acknowledge/Step or Alarm Silence key is pressed). The ‘beeps’ from the onboard piezo sounder will occur until the alarm or fault is cleared. Note that if the trouble is not cleared within 24 hours, the piezo will resound, indicating that the trouble condition still exists. 4.20.4 Waterflow Retard Timer If selected, this option will delay the activation of a waterflow type alarm for a programmable time duration from 1 to 90 seconds. This delay is in addition to any time delay inherent in the waterflow device. This feature requires the approval of the local Authority Having Jurisdiction. 8QLPRGH31& 2SHUDWLQJ,QVWUXFWLRQV :DONWHVW 4.20.5 Alarm Verification (None or Two Minutes) If alarm verification is selected, an addressable smoke detector's alarm is ignored for a retard time of 13 seconds and the detector's alarm condition is automatically reset. There will be no alarm indication at the FACP during the Retard period. A confirmation period of one minute and 47 seconds follows, during which a subsequent alarm from the same detector will cause the panel to immediately activate the appropriate outputs and indicate the alarm condition at the FACP. If a different detector alarms any time during the first detector's verification period, the panel will immediately activate all appropriate outputs and indicate the alarm condition at the FACP. If no additional detector alarms occur within two minutes of the first alarm (13 second retard plus one minute and 47 second confirmation), the timer resets and the panel is ready to verify any new detector alarms which may occur. 0 sec. Detector Alarm Verification (Retard + Confirmation) Detector Goes Into Alarm 13 sec. 120 sec. CONFIRMATION RETARD Alarm Ignored Control Panel Processes Alarm if Same Detector is Still in Alarm Control Panel Immediately Processes Alarm Different Detector Alarms During First Detector's Verification Period Note: Alarm Verification is available only for addressable smoke detectors, not conventional smoke detectors. 4.21 Walktest Walktest is a feature which allows one person to test the fire alarm system. An audible walktest will momentarily sound the Notification Appliance Circuits in the building and store the walktest information in a file at the panel. A silent walktest will not sound the NACs but will store the walktest information in a file which can be viewed at the panel. Disabled NAC devices will not activate during walktest. Alarm/Shorted Condition When in audible Walktest, the panel responds to each new alarm and activates its programmed control outputs for four seconds, if those outputs have been programmed for silenceable activation. It also stores each alarm in the walktest history file which can be sent to an optional printer. The stored display will be the same as if the device actually activated except the colon (:) in the time stamp is replaced with an asterisk (*). Open Condition Addressable devices as well as both main circuit board NACs are monitored for fault conditions during Walktest mode. When a new trouble condition occurs, the FACP will activate all NACs and control modules programmed for Walktest, then shut them off after eight seconds. While in Walktest, the trouble relay is activated and the system Trouble LED flashes (as in all of the Program and status change operations). The alarm relay is not activated. 8QLPRGH31& 5HDG6WDWXV 2SHUDWLQJ,QVWUXFWLRQV 4.22 Read Status Read Status functions do not require a password. The control panel will continue to provide fire protection while in Read Status mode. This mode can be entered while the control panel is in alarm or trouble. If a new alarm or trouble occurs during these functions, the Read Status is exited to prevent confusion. Read Status Entry When the operator presses the control panel Enter key, the LCD will display the following: 1=READ STATUS 2=PROGRAMMING Pressing 1, while this screen is being displayed, will cause the control panel to enter the Read Status mode which allows the user to view and print the programmed features and status of the control panel. The following screens will be displayed: READ STATUS 1=SYSTEM POINT 2=ZONES 3=POWER Read Status Screen #1 READ STATUS 1=TROUBLE REMINDER 2=TIMERS 3=NAC Read Status Screen #2 READ STATUS 1=ANNUNCIATORS 2=FUTURE USE 3=FUTURE USE Read Status Screen #4 READ STATUS 1=FUTURE USE 2=PRINTER/PC 3=PRINT Read Status Screen #5 READ STATUS 1=RELAYS 2=PROGRAM CHECK 3=HISTORY READ STATUS 1=TIME-DATE Read Status Screen #3 Read Status Screen #6 8QLPRGH31& 2SHUDWLQJ,QVWUXFWLRQV 5HDG6WDWXV 4.22.1 System Point READ STATUS 1=SYSTEM POINT 2=ZONES 3=POWER Pressing 1 while viewing Read Status Screen #1 will cause the following screen to be displayed: Read Status Screen #1 READ SYSTEM POINT SELECT LOOP 1=LOOP 1 2=LOOP 2 The operator selects the loop containing the device to be read by pressing 1 for Loop 1 or 2 for Loop 2. The following screen will then be displayed: READ SYSTEM POINT SELECT TYPE 1=DETECTOR 2=MODULE The operator now selects the type of device which is to be viewed by pressing 1 for Detector or 2 for Module. If 1 is pressed, the display will change to the following screen: READ SYSTEM POINT ENTER DETECTOR# *** Entering the three digit detector address will cause the control panel to display the current status of the selected device. For example, if a detector with address 001 on loop 1 is entered, a display similar to the following will appear: NORMAL SMOKE(PHOTO) NORTH CLASSROOM Z005 1D001 The information in the preceding display includes: • NORMAL - the present status (could also be ALARM, TROUBL, DISABL, etc.) • SMOKE (PHOTO) - the device type which is a photoelectric smoke detector (could also be ION for ionization smoke detector) • NORTH CLASSROOM - the Adjective/Noun label for this device • Z005 - the first of five possible assigned software zones • 1D001 - 1 = Loop 1, D = Detector, 001 = Address 001 8QLPRGH31& 5HDG6WDWXV 2SHUDWLQJ,QVWUXFWLRQV Pressing the down arrow key, while viewing the screen shown above, will allow the operator to view additional programming information about the selected device, such as: • Enable/Disable Status • Device Type • Alarm Verification On/Off • Walktest Yes/No • PAS (Positive Alarm Sequence) Yes/No • Pre-Signal Yes/No • Zone Assignments (five maximum) • Adjective/Noun descriptor 4.22.2 Zones READ STATUS 1=SYSTEM POINT 2=ZONES 3=POWER Pressing 2 while viewing Read Status Screen #1 will cause the following screens to be displayed: Read Status Screen #1 ZONES 1=ZONES INSTALLED 2=ZONES ENABLED 3=ZONES DISABLED Zones Screen #1 ZONES 1=SPECIAL PURPOSE 2=ZONE TYPE Zones Screen #2 From the preceding screens, the control panel operator can view: • Zones Installed - all software zones programmed into the system (99 maximum) • Zones Enabled - all software zones that are enabled • Zones Disabled - all software zones that have been disabled • Special Purpose - on or off programming for Special Purpose Zones 97 reserved for PAS, 98 reserved for Pre-signal and 99 reserved for future use • Zone Type - the Type assigned to each installed zone (default is Alarm) 8QLPRGH31& 2SHUDWLQJ,QVWUXFWLRQV 5HDG6WDWXV 4.22.3 Power Pressing 3 while viewing Read Status Screen #1 will cause the following screens to be displayed: POWER BATTERY 24 V RST 24 V NRST 27.21V 25.31 25.31 Zones Screen #1 CHARGER NAC 1 NAC 2 POWER 28.36V 2.39V 2.39V Zones Screen #2 A real-time display of the control panel voltages can be used to determine if a problem exists in the system. The following table lists the circuit being measured, possible conditions and their respective voltage ranges: Circuit Condition Voltage Range Normal Battery (nominal) 27.05 - 28.15 VDC Low Battery 20.0 - 20.8 VDC No Battery 0 - 18.36 VDC 24V Resettable Normal 21.25 - 27.50 VDC 24V Nonresettable Normal 21.25 - 27.50 VDC Charger Normal 27.05 - 28.15 VDC Normal 1.37 - 1.43 VDC Open Circuit 2.30 - 2.40 VDC Short Circuit 0 - 1.0 VDC Battery NAC 1 or NAC 2 4.22.4 Trouble Reminder READ STATUS 1=TROUBLE REMINDER 2=TIMERS 3=NAC Read Status Screen #2 Pressing 1 while viewing Read Status Screen #2 will display the following screen: TROUBLE REMINDER TROUBLE REM ON The screen indicates whether the Trouble Reminder feature is On or Off. 8QLPRGH31& 5HDG6WDWXV 2SHUDWLQJ,QVWUXFWLRQV 4.22.5 Timers Pressing 2 while viewing Read Status Screen #2 will cause the following Timer screens to be displayed: TIMERS PAS DELAY PRE SIGNAL WATERFLOW TIMERS AC LOSS DELAY 000 000 000 4 These screens will indicate the delay time, in seconds, for each of four possible delay options. 4.22.6 NAC Pressing 3 while viewing Read Status Screen #2 will display the following screen: 1=NAC 1 2=NAC 2 NAC The operator can press 1 to view the programmed options for NAC 1 or 2 to view the programmed options for NAC 2. The resulting screens will display the following information: • Enable/Disable Status • Circuit Type (Bell, Strobe, etc.) • Silenceable/Nonsilenceable • Auto Silence Enable/Disable and time delay • Coding Selection (Temporal, Steady, etc.) • Zone Assignments • Silence Inhibit Enabled/Disabled • Synchronization Type (System Sensor, Wheelock or Gentex) 8QLPRGH31& 2SHUDWLQJ,QVWUXFWLRQV 5HDG6WDWXV 4.22.7 Relays READ STATUS 1=RELAYS 2=PROGRAM CHECK 3=HISTORY Pressing 1 while viewing Read Status Screen #3 will display the following screen: RELAY 1=RELAY 1 2=RELAY 2 3=RELAY 3 Read Status Screen #3 The operator can view the programmed option for each relay by pressing the corresponding number key. 4.22.8 Program Check Pressing 2 while viewing Read Status Screen #3 will cause a screen similar to the following to be displayed: PROGRAM CHECK 1=NACS NO INPUT 2=ZONES NO INPUT 3=ZONES NO OUTPUT Pressing 1 while viewing the Program Check screen will display a screen which will indicate if any input zones have not been programmed to one of the Notification Appliance Circuits. Use the up and down arrow keys to view both NACs. Pressing 2 while viewing the Program Check screen will display a screen which will indicate if any output zones have not been programmed to at least one input zone. Use the up and down arrow keys to view all zones. Pressing 3 while viewing the Program Check screen will display a screen which will indicate if any input zones have not been programmed to at least one output zone. Use the up and down arrow keys to view all zones. 4.22.9 History Pressing 3 while viewing Read Status Screen #3 will display the following screen: HISTORY 1=VIEW ALL 2=VIEW ALARMS 3=VIEW OTHER EVENTS The operator can view all events which have been stored in the history file, only alarms or other events, such as troubles or supervisories, by pressing the corresponding number key. 8QLPRGH31& 5HDG6WDWXV 2SHUDWLQJ,QVWUXFWLRQV 4.22.10 Annunciators READ STATUS 1=ANNUNCIATORS 2=FUTURE USE 3=FUTURE USE Pressing 1 while viewing Read Status Screen #4 will display the following screens: ANNUNCIATORS TERM ENABLED YES ACS ENABLED YES UDACT ENABLED NO Read Status Screen #4 Annunciator Screen #1 ANNUNCIATORS 1=ACS ADDRESS Annunciator Screen #2 Annunciator Screen #1 indicates if Terminal Mode, ACS Mode and UDACT options are enabled or disabled. Pressing ‘1’ while viewing Annunciator Screen #2 allows the operator to view the ACS Mode Annunciator addresses which have been programmed into the control panel. 4.22.11 Printer/PC READ STATUS 1=FUTURE USE 2=PRINTER/PC 3=PRINT Pressing 2 while viewing Read Status Screen #5 will display the following screens: PRINTER PC PRINTER PC PR4800 START BIT STOP BIT Read Status Screen #5 PRINTER PC DATA BITS PARITY The display will inform the operator as to whether the control panel is configured for a printer or a PC. In the example above, PR4800 indicates that the panel is configured for a printer with a baud rate of 4,800. 8QLPRGH31& 2SHUDWLQJ,QVWUXFWLRQV 5HDG6WDWXV 4.22.12 Print To print program data or control panel status, press 3 while viewing Read Status Screen #5. The following screens will be displayed: PRINT 1=HISTORY 2=WALKTEST LOG 3=DETECTOR DATA Print Screen #1 PRINT 1=EXIT PRINTING Print Screen #2 Pressing 1 while viewing Print Screen #1 allows the user to print the History file which will detail all of the system activities since the file was last cleared from memory. Pressing 2 while viewing Print Screen #1 allows the user to print the Walktest log which will detail all of the system activations during walktest since the log was last cleared. Refer to "Walktest" on page 90 for additional information on the display. Pressing 3 while viewing Print Screen #1 allows the user to print the data of each addressable smoke detector connected to the system. A printout, similar to the following example, will be generated if an optional printer is connected to the FACP. DEVICE# DEVICE TYPE 1D001 1D002 1D003 1D004 1D005 1D006 1D007 1D008 1D009 SMOKE (PHOTO) SMOKE (PHOTO) SMOKE (PHOTO) SMOKE (PHOTO) SMOKE (PHOTO) SMOKE (PHOTO) SMOKE (PHOTO) SMOKE (PHOTO) SMOKE (PHOTO) %DRIFT COMP 20 20 21 20 21 20 20 20 20 CHAMBER 1281 1281 1259 1309 1281 1322 1280 1215 1310 TIME/DATE 12:01AM 01-08-2001 12:01AM 01-08-2001 12:01AM 01-08-2001 12:02AM 01-08-2001 12:02AM 01-08-2001 12:02AM 01-08-2001 12:02AM 01-08-2001 12:02AM 01-08-2001 12:02AM 01-08-2001 Chamber Value The Chamber value should be within the indicated range for the following smoke detectors: • SD350(T), D350P(R) and SD300(T) Addressable Photoelectric Smoke Detectors: 405 - 2100 (obscuration of 1.00%/ft. to 3.66%/ft.) • CP350 and CP300 Addressable Ionization Smoke Detectors: 750 - 2100 (obscuration of 0.50%/ft. to 1.44%/ft.) If the addressable smoke detector’s Chamber reading is not within the acceptable range, clean the detector and check the Chamber value again. If the reading is still not within the acceptable range, immediately replace the detector. 8QLPRGH31& 5HDG6WDWXV 2SHUDWLQJ,QVWUXFWLRQV Drift Compensation Drift compensation uses software algorithms that identify and compensate for long-term changes in the data readings from each addressable smoke detector. These long-term changes in detector data readings are typically caused by dirt and dust accumulation inside the smoke chamber. Drift compensation performs the following functions: • Allows a smoke detector to retain its original ability to detect actual smoke and resist false alarms, even as dirt and dust accumulate • Reduces maintenance requirements by allowing the control panel to automatically perform the periodic sensitivity measurements required by NFPA Standard 72 The FACP software also provides smoothing filters to remove transient noise signals, usually caused by electrical interference. Maintenance Alert The software determines when the drift compensation for a detector reaches an unacceptable level that can compromise detector performance. When a detector reaches an unacceptable level, the control panel indicates a maintenance alert. Table 4.1 summarizes the three levels of maintenance alert: Maintenance Level FACP Status Display Indicates Low Chamber Value INVREP A hardware problem in the detector Maintenance Alert DIRTY1 Dust accumulation that is near but below the allowed limit. DIRTY 1 indicates the need for maintenance before the performance of the detector is compromised Maintenance Urgent DIRTY2 Dust accumulation above the allowed limit. Table 4.1 Maintenance Alert Levels Figure 4.1 illustrates a graphic representation of the maintenance levels: Maintenance Urgent DIRTY Maintenance Alert Acceptable Range Low Chamber Reading LOW VALUE Figure 4.1 Diagram of Maintenance Levels 8QLPRGH31& 2SHUDWLQJ,QVWUXFWLRQV 5HDG6WDWXV 4.22.13 Time-Date READ STATUS 1=TIME-DATE The operator can view the daylight savings time and the month and week when daylight savings time will begin and end. Pressing 1 while viewing Read Status Screen #6 will display the following screens: Read Status Screen #6 DAYLIGHT SAVINGS ENABLED YES START MONTH APR START WEEK WEEK-1 DAYLIGHT SAVINGS END MONTH OCT END WEEK LAST-W 8QLPRGH31& Overview Power Supply Calculations Power Supply Calculations SECTION 5 5.1 Overview This section contains instructions and tables for calculating power supply currents in alarm and standby conditions. This is a four-step process, consisting of the following: 1. Calculating the total amount of AC branch circuit current required to operate the system 2. Calculating the power supply load current for non-fire and fire alarm conditions and calculating the secondary (battery) load 3. Calculating the size of batteries required to support the system if an AC power loss occurs 4. Selecting the proper batteries for your system 5.2 Calculating the AC Branch Circuit The control panel requires connection to a separate, dedicated AC branch circuit, which must be labeled FIRE ALARM. This branch circuit must connect to the line side of the main power feed of the protected premises. No other non-fire alarm equipment may be powered from the fire alarm branch circuit. The branch circuit wire must run continuously, without any disconnect devices, from the power source to the control panel. Overcurrent protection for this circuit must comply with Article 760 of the National Electrical Codes as well as local codes. Use 14 AWG (2.00 mm2) wire with 600 volt insulation for this branch circuit. Use Table 5.1 , to determine the total amount of current, in AC amperes (A), that must be supplied to the system. Table 5.1 120 VAC Branch Circuit Requirements Device Type Number of Devices Unimode 9600 ADT-CHG-120 1 Current Draw (AC amps) X 3.2 = [ ] X 2.0 = [ ] X [ ] Sum Column for AC Branch Current Required Unimode 9600 PN 51336:C 11/06/01 Total Current per Device 3.2 = = 127 3RZHU6XSSO\&DOFXODWLRQV &DOFXODWLQJWKH6\VWHP&XUUHQW'UDZ 5.3 Calculating the System Current Draw 5.3.1 Overview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µ3ULPDU\¶UHIHUVWRWKHPDLQSRZHUVRXUFHIRUWKHFRQWUROSDQHO µ6HFRQGDU\¶UHIHUVWRWKHFRQWUROSDQHO¶VEDFNXSEDWWHULHV $OOFXUUHQWVDUHJLYHQLQDPSHUHV$7DEOHVKRZVKRZWRFRQYHUWPLOOLDP SHUHVDQGPLFURDPSHUHVWRIXOODPSHUHV Table 5.2 Converting to Full Amperes 7RFRQYHUW 0XOWLSO\ 0LOOLDPSHUHVP$WR DPSHUHV$ P$[ 0LFURDPSHUHV$WR DPSHUHV$ $[ ([DPSOH P$[ $ $[ $ 5.3.2 How to Use Table 5.3 on page 129 to Calculate System Current Draw Use Table 5.3 on page 129 to calculate current draws as follows: 1. Enter the quantity of devices in all three columns 2. Enter the current draw where required. Refer to the ADT Device Compatibility Document for compatible devices and their current draw 3. Calculate the current draws for each in all columns 4. Sum the total current for each column 5. Copy the totals from Column 2 and Column 3 to Table 5.4 on page 130 Following are the types of current that can be entered into Table 5.3 on page 129: ✓ Calculation Column 1 - The primary supply current load that the control panel must support during a non-fire alarm condition, with AC power applied. ✓ Calculation Column 2 - The primary supply current load that the control panel must support during a fire alarm condition, with AC power applied. ✓ Calculation Column 3 - The standby current drawn from the batteries in a nonfire alarm condition during a loss of AC power. 8QLPRGH31& &DOFXODWLQJWKH6\VWHP&XUUHQW'UDZ 3RZHU6XSSO\&DOFXODWLRQV Table 5.3 contains columns for calculating current draws. For each column, calculate the current and enter the total (in amperes) in the bottom row. When finished, copy the totals from Calculation Column 2 and Calculation Column 3 to Table 5.4 on page 130. Table 5.3 System Current Draw Calculations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able Footnote 1. All eight ADT-ACM-8R relays activated on a single module. 2. All annunciator LEDs on 3. ADT-UDACT actively making phone call to central station. If the normally open contact is used, current consumption increases to 100 mA. 4. ADT-LDM-32 with LEDs on 5. If using the Reverse Polarity Alarm output, add 0.005 amps; if using the Reverse Polarity Trouble output, add another 0.005 amps. 6. Refer to the Device Compatibility Document for standby current. 7. Must use compatible listed Power Supervision Relay. 8. Maximum alarm current for each sounder base is 0.015 amps which must be supplied by aux. 24 VDC source. 9. Current limitation of Terminal TB4 circuits is 3.00 amps per NAC. 10.The total standby current must include both the resettable (TB3 Terminals 1 & 2) and nonresettable (TB3 Terminals 3 & 4, 5 & 6) power. Caution must be taken to ensure that current drawn from these outputs during alarm does not exceed maximum ratings specified. Current limitations of TB3 circuits is 3.0 amps per output 11.Total current draw listed above cannot exceed 7.2 amps. 8QLPRGH31& 3RZHU6XSSO\&DOFXODWLRQV &DOFXODWLQJWKH%DWWHU\6L]H 5.4 Calculating the Battery Size Use Table 5.4 to calculate the total Standby and Alarm load in ampere hours (AH). This total load determines the battery size (in AH), required to support the control panel under the loss of AC power. Complete Table 5.4 as follows: 1. Enter the totals from Table 5.3 on page 129, Calculation Columns 2 and 3 where shown 2. Enter the NFPA Standby and Alarm times (refer to ‘NFPA Requirements’ below) 3. Calculate the ampere hours for Standby and Alarm, then sum the Standby and Alarm ampere hours 4. Multiply the sum by the derating factor of 1.2 to calculate the proper battery size (in AH) 5. Write the ampere hour requirements on the Protected Premises label located inside the cabinet door Table 5.4 Total Secondary Power Requirements at 24 VDC 6HFRQGDU\6WDQGE\/RDG WRWDOIURP7DEOH&DOFXODWLRQ &ROXPQ >@ 5HTXLUHG6WDQGE\7LPH RUKRXUV 3ULPDU\$ODUP/RDG WRWDOIURP7DEOH&DOFXODWLRQ &ROXPQ 5HTXLUHG$ODUP7LPH IRUPLQHQWHU IRUPLQHQWHU >@ ;>@ ;>@ 6XPRI6WDQGE\DQG$ODUP$PSHUH+RXUV 0XOWLSO\E\WKH'HUDWLQJ)DFWRU %DWWHU\6L]H7RWDO$PSHUH+RXUV5HTXLUHG $+ $+ $+ ; $+ 5.4.1 NFPA Battery Requirements • NFPA 72 Local and Proprietary Fire Alarm Systems require 24 hours of standby power followed by 5 minutes in alarm • NFPA 72 Central, Auxiliary and Remote Station Fire Alarm Systems require 60 hours of standby followed by 5 minutes in alarm. Batteries installed in a system powered by a generator need to provide at least 4 hours of standby power • NFPA requires 24 hours of standby plus 15 minutes activation for audio systems. The total ampere hours required cannot exceed 25 AH with an internal charger 5.4.2 Selecting and Locating Batteries Select batteries that meet or exceed the total ampere hours calculated in Table 5.4 . The control panel can charge batteries in the 7 AH to 25 AH range. The control panel cabinet is capable of housing batteries up to 18 AH. Batteries larger than 18 AH require the BB55F or other UL listed external battery cabinet. 8QLPRGH31& &RUUHODWLRQV 6RIWZDUH=RQHV 6RIWZDUH=RQHV APPENDIX A A.1 Correlations Setup and configuration of an addressable system is different than a conventional system. In a conventional system, assignment of input devices (smoke detectors, pull stations, heat detectors, etc.) to zones is accomplished through wiring. The wiring is direct from clearly marked panel terminals to any device assigned to a particular zone. Connection of output devices (horns, bells, strobes, etc.) in a conventional system is accomplished by direct wiring of the output devices to Notification Appliance Circuit terminals. In an addressable system, a minimum of a single pair of wires (SLC communication loop) is used to connect all addressable input and output devices. Communications between the FACP (Fire Alarm Control Panel) and all addressable devices takes place over the wire pair which originates from the FACP. Software programming is used to configure the system as opposed to direct wiring. Zone assignments are created via software means, hence the term software zones. Setup of an Unimode 9600 software zone is accomplished by panel programming. Each addressable device can be assigned to a maximum of five software zones. Each software zone, however, may have from 1 to 99 addressable input devices assigned to it and from 1 to 99 addressable output devices assigned to it. Monitor and control modules comprise one group of 99 addresses, with each module having a unique address from 1 to 99. Detectors comprise a separate group of 99 addresses, each detector having a unique address from 1 to 99 in its group. Be careful not to duplicate addresses within any one group (modules and detectors). Refer to the following page for an example of zoning. In the example on the following page: • Zone 01 has the following addressable devices assigned to it: ✓ SD350 smoke detectors with addresses 01 and 02 ✓ MMF-300 monitor module with address 01 ✓ MMF-302 monitor module with address 02 and 03 ✓ CMF-300 control modules with addresses 05, 06, 07, 09 and 13 • Zone 02 has the following addressable devices assigned to it: ✓ MMF-302 monitor module with addresses 02 and 03 ✓ CP350 smoke detectors with addresses 03 and 04 ✓ CMF-300 control modules with addresses 08, 09 and 10 • Zone 03 has the following addressable devices assigned to it: ✓ SD350 smoke detectors with addresses 05, 06 and 07 ✓ MMF-302 control module with address 04 ✓ CMF-300 control modules with addresses 09, 11 and 12 The example points out some of the key assignment features of the Unimode 9600. Addresses of detectors are not duplicated. Addresses of monitor and control modules are not duplicated. The control module with address 09 is assigned to three software zones (providing floor above and floor below). Be careful to properly plan the installation prior to installing any devices. CLIP or Classic Loop Interface Protocol devices (modules and detectors) can only have unique addresses of 1 to 99. Newer modules can have unique addresses of 1 to 159 which means each zone can have up to 159 input and output devices assigned to it. 8QLPRGH31& 6RIWZDUH=RQHV &RUUHODWLRQV Correlation of Input and Output Zones Input Devices Zones SD350 01 Output Devices CMF-300 13 SD350 02 CMF-300 05 ZONE 01 MMF-300 01 CMF-300 06 MMF-302 02 CMF-300 07 CMF-300 09 MMF-302 03 CP350 03 ZONE 02 CMF-300 08 CMF-300 10 CP300 04 SD350 05 CMF-300 11 SD350 06 SD350 07 MMF-302 04 ZONE 03 CMF-300 12 The zone correlations which are shown graphically above are also presented in Table A.1 on page 133 and Table A.2 on page 134. 8QLPRGH31& &RUUHODWLRQV 6RIWZDUH=RQHV 7DEOH$'HWHFWRU3URJUDPPLQJ6KHHW([DPSOH Address 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 Device Type SD350 SD350 CP350 CP350 SD350 SD350 SD350 8QLPRGH31& Zone Number 1 1 2 2 3 3 3 DETECTOR ZONE ASSIGNMENT ADJ/NOUN Address Device Type FIRST HALL 51 ELEV. LOBBY 52 2ND FLOOR 53 ROOM 210 54 3RD FLOOR 55 MEZZANINE 56 MECH. ROOM 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 Zone Number ADJ/NOUN 6RIWZDUH=RQHV &RUUHODWLRQV 7DEOH$0RGXOH3URJUDPPLQJ6KHHW([DPSOH Address 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 Device Type MMF-300 MMF-302 MMF-302 MMF-302 CMF-300 CMF-300 CMF-300 CMF-300 CMF-300 CMF-300 CMF-300 CMF-300 CMF-300 MONITOR/CONTROL MODULE ZONE ASSIGNMENT Zone ADJ/ Address Device Zone Number NOUN Type Number 1 51 1, 2 52 1, 2 53 3 54 1 55 1 56 1 57 2 58 1, 2, 3 59 2 60 3 61 3 62 1 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 ADJ/NOUN 8QLPRGH31& &RUUHODWLRQV 6RIWZDUH=RQHV 7DEOH$%ODQN'HWHFWRU3URJUDPPLQJ6KHHWRI Address Device Type 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 8QLPRGH31& Zone Number DETECTOR ZONE ASSIGNMENT ADJ/ Address Device NOUN Type 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 Zone Number ADJ/NOUN 6RIWZDUH=RQHV &RUUHODWLRQV 7DEOH$%ODQN'HWHFWRU3URJUDPPLQJ6KHHWRI Address 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 Device Type Zone Number DETECTOR ZONE ASSIGNMENT ADJ/ Address Device NOUN Type 151 152 153 154 155 156 157 158 159 Zone Number ADJ/NOUN 8QLPRGH31& &RUUHODWLRQV 6RIWZDUH=RQHV 7DEOH$%ODQN0RGXOH3URJUDPPLQJ6KHHWRI Address Device Type 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 8QLPRGH31& MONITOR/CONTROL MODULE ZONE ASSIGNMENT Zone ADJ/ Address Device Zone Number NOUN Type Number 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 ADJ/NOUN 6RIWZDUH=RQHV &RUUHODWLRQV 7DEOH$%ODQN0RGXOH3URJUDPPLQJ6KHHWRI Address 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 Device Type MONITOR/CONTROL MODULE ZONE ASSIGNMENT Zone ADJ/ Address Device Zone Number NOUN Type Number 151 152 153 154 155 156 157 158 159 ADJ/NOUN 8QLPRGH31& &RUUHODWLRQV 'HIDXOW3URJUDPPLQJ 'HIDXOW3URJUDPPLQJ APPENDIX B The following table provides a list of the programming options and their factory default settings. Program Option Factory Default Program Option Factory Default Detector Programming Not Installed Daylight Savings Yes Detector Type Smoke-Photo Month Start Daylight Savings April Detector Verification Off Week Start Daylight Savings 1st Week Detector Walktest Yes Month End Daylight Savings October Detector PAS No Week End Daylight Last Week Detector Presignal No Verification No Detector Zone Assign. 000 only (future) Detector Adj/Noun none PAS Timer 0 Module Programming Not Installed Presignal Timer 0 Module Type Monitor Waterflow Retard Timer 0 Module Walktest Yes NAC 1 & 2 Enable Enabled Module PAS No NAC 1 & 2 Silenceable Yes Module Presignal No NAC 1 & 2 Type Bell Module Zone Assign. 000 only NAC 1 & 2 Sync Type System Sensor Module Adj/Noun none NAC 1 & 2 Autosilence 0 Zone 0 Enable Enabled NAC 1 & 2 Coding Steady Zone 1 Enable Enabled NAC 1 & 2 Zones Zone 000 only Zone 2 Enable Enabled NAC 1 & 2 Silence Inhibit 0 Zone 3 Enable Enabled Relay 1 Alarm .........................through.......... ..................... Relay 2 Trouble Zone 96 Enable Enabled Relay 3 Supervisory Zones 97, 98 & 99 Enabled (future) No Annunciator Terminal Mode No (future) Loop 1 & 2 Style Style 4 Annunciator ACS Mode Loop 1 & 2 Protocol CLIP UDACT No Trouble Reminder Off ACS Installed No Banner Fire•Lite Printer-PC No Time Format 12 Hr Printer Baud 9600 Hours Setting 12 Minutes Setting 00 Second Settings 00 AM-PM Setting AM Month Setting 01 Day Setting 01 Year Setting 00 8QLPRGH31& :LUH5HTXLUHPHQWV &RUUHODWLRQV :LUH5HTXLUHPHQWV APPENDIX C T-tapping of the SLC loop wiring is allowed for 2-wire (Style 4) configurations. The total resistance of any branch cannot exceed 40 ohms. The total wire length of all branches cannot exceed 10,000 feet (3,000 m). Connecting external system accessories to the Unimode 9600 main circuits must be carefully considered to ensure proper operation. It is important to use the correct type of wire, wire gauge and wire run length for each Unimode 9600 circuit. Reference the chart below to specify wire requirements and limitations for each Unimode 9600 circuit. Note: If the SLC loop is to be run in conduit with Notification Appliance Circuits, the risk of encountering problems can be greatly reduced by exclusively employing electronic sounders (such as MA/SS-24D) instead of more electronically noisy notification appliances such as electromechanical bells or horns. 7DEOH&8QLPRGH:LUH6SHFLILFDWLRQV CIRCUIT CONNECTIONS WIRE REQUIREMENTS Circuit Type Circuit Function Wire Type and Limitations SLC loop (power-limited) Connects to Addressable Devices Twisted, shielded pair, 40 ohms maximum per length of Style 6 and 7 loops. 40 ohms per branch maximum for Style 4 loops1 ACS/TERM (EIA-485) (power-limited) Connects to annunciator modules and ADT-UDACT connects to remote printer and PC computer Initiating Device Circuit EIA-232 (power-limited) MMF-300 and MMF-301 (power-limited) Wire Gauge and Compatible Brands Untwisted, unshielded pair Twisted, shielded pair with a characteristic impedance of 120 ohms 3,000 (900 m) 6,000 (1,800 m) 12 AWG (3.25 mm): Genesis 4410, Signal 98230, Belden 9583, WPW999 14 AWG (2.00 mm):Genesis 4408 & 4608 Signal 98430, Belden 9581, WPW995 16 AWG (1.30 mm): Genesis 4406 & 4606 Signal 98630, Belden 9575, WPW991 Direct Burial Cable Isotec NP713110VNQ-S 18 AWG (0.75 mm): Genesis 4402 & 4602 Signal 98300, Belden 9574, WPW975 Direct Burial Cable Isotec NP714110VNQ-S 12-18 AWG (3.25 - 0.75 mm) 18 AWG (0.75 mm) Twisted, shielded pair 50 (15 m) 18 AWG (0.75 mm) minimum 2,500 (760 m) 12-18 AWG (3.25 - 0.75 mm) 2,500 (760 m) 12-18 AWG (3.25 - 0.75 mm) Distance limitation set by 1.2 volt maximum line drop Distance limitation set by 1.2 volt maximum line drop Distance limitation set by 1.2 volt maximum line drop 20 (6 m) 12-18 AWG (3.25 - 0.75 mm) MMF-302 (power-limited) Initiating Device Circuit CMF-300 (power-limited) Notification Appliance Circuit Maximum loop wire resistance is 40 ohms for the MMF-300 and 20 ohms for the MMF-301 No more than a 2.4 volt drop allowed at end of circuit. Maximum loop wire resistance is 25 ohms In alarm, no more than a 1.2 volt drop allowed at end of circuit 24 VDC filtered resettable (power-limited) 24 VDC nonresettable (power-limited) Connects to 4-wire smoke detectors No more than 1.2 volt drop allowed from supply source to end of any branch Connects to control modules, annunciators and accessories Remote secondary power source No more than 1.2 volt drop allowed from supply source to end of any branch CHG-120F Recommended Max. Distance Feet (meters) 10,000 (3,000 m) 8,000 (2,400 m) 4,875 (1,450 m) 3,225 (980 m) 12 AWG (3.25 mm) in conduit 12-18 AWG (3.25 - 0.75 mm) 12-18 AWG (3.25 - 0.75 mm) 12-18 AWG (3.25 - 0.75 mm) Table Footnote 1. When using untwisted, unshielded wire, full conduit is recommended for optimum EMI/RFI protection. 8QLPRGH31& Index Numerics 300 Series addressable devices 20 4XTMF module coil resistance 31 current 31 installation 31 installation steps 32 see also Transmitter Module 13, 20 voltage 31 A AC Branch Circuit calculations 127 AC Loss Delay 81 AC Power 27 current 14 current, maximum 27 voltage 14 wiring 14, 27 Acknowledge/Step 16, 105 ACM-8RF 13 contact rating 35 ACS LED annunciator 13 add Detector 43 add Module 53 address range 19 addressable 12 addressable detectors see also detectors 13 Addressable Device Accessories 20 addressable modules 19 see also modules 13 addressing annunciators 37 see also module or detector addressing 19 Adjective control module 67 monitor module 60 multiple entries 52 Adjective list 50 ADT-ACM-16A Annunciator 22 ADT-ACM-32A Annunciator 22 ADT-ACM-8R 35 mounting to BRKT-9600 36 see also Relay Control Module 35 ADT-ACS LED annunciator 37 ADT-ACS Series see also annunciator 22 ADT-AFM annunciator 37 ADT-AFM-16A Annunciator 22 ADT-AFM-16AT Annunciator 22 ADT-AFM-32A Annunciator 22 ADT-BG-10LX see also manual pull station 20 ADT-BG-12LX Unimode 9600 PN 51336:C 09/19/01 see also manual pull station 19 ADT-CHG-120 see also battery charger 22 see also remote battery charger 14 ADT-LCD-80F annunciator 13, 23 ADT-LDM Series annunciator 23 ADT-UDACT mounting to BRKT-9600 36 programming 35 see also Digital Alarm Communicator/Transmitter 35 AEM-16AT Annunciator 22 AEM-32A Annunciator 22 Alarm 109 Alarm Silence 16, 105 alarm verification 12, 47, 112, 116 annunciator 22 ACS 13 ADT-ACM-8R 13 ADT-ACS 37 ADT-LCD-80F 13 LDM Graphic 13 annunciator addressing 37 annunciator, graphic see also ADT- LDM Series 23 annunciator, remote see also ADT- LCD-80F 23 annunciatorADTAFM 37 Auto Silence NAC 84 Automatic Test Operation 112 Autoprogramming 13, 39, 87 Autosilence 13, 115 auxiliary DC power 27 Auxiliary Trouble Input 17, 32 B backbox 18 see also cabinet 26 Banner 75 Banner setting 76 battery 18 cable connection 27 charger 17 charger capacity 14 Charging Circuit 14 see also secondary power 14, 27 battery box 21, 22 battery charger 22 disable 14 external 22 baud rate 92 BB-17F see also battery box 21 BB-55F see also battery box 18, 22 BRKT-9600 bracket installation 35, 36 see also Universal Bracket 35 C C304 Control/Relay Module 20 cabinet 18 dimensions 25, 26 cabinet mounting 24 Calculate System Current Draw 128 Calculating the Battery Size 130 Class A 19, 28 Class B 19, 28 Classic Loop Interface Protocol 19 CLIP Mode see also Classic Loop Interface Protocol 19 Clock Format 78 CMF-300 control module 19 Coded Operation 113 Coding NAC 84 Control Buttons 105 control module 19 description display 69 display 63 edit 63 enable/disable 64 noun 68 noun/adjective 66, 67 silenceable 65 type 65 type codes 65 Correlations 131 CP300 Ionization Detector 20 CP350 18 CRF-300 relay module 19 current AC Power 27 availability 15 maximum 15 Current Draw Calculations 129 D D350P 18 D350R 18 data printout 124 see also smoke detector sensitivity 112 Data Entry via computer keyboard 38 via keypad 38 Date setting 78 Daylight Savings Time 78 DC power nonresettable 27 resettable 27 141 Index see also auxiliary DC power 27 Default Programming 139 Delete Detector 44 Delete Module 54 Description control module 69 detector label 52 monitor module 62 Detector 13 add 43 adding description 49 delete 44 edit 44 enable/disable 46 screen display 45 type 47 verification 47 Detector Annunciator 19 detector data 124, 125 acceptable range 124 Detector Programming 43 Digital Alarm Communicator/ Transmitter see also ADT- UDACT 35 dimensions cabinet 25 DIRTY1 125 DIRTY2 125 Disable 71 Disable Point Maintenance Level 98 dress panel 18, 21 drift compensation 12 definition 125 Drill 16, 105 E earth ground 27 edit control module 63 detector 44 detector screens 45 module, monitor 54 EIA-232 34 for PC/Printer connection 15 see also Printer/PC interface 12 EIA-485 for ACS annunciators 15 for LCD-80F 15 Enable 70 Enable/Disable control module 64 detector 46 module, monitor 57 End-of-Line Resistor Assembly 20 Enter key 41 Erase History 89 exiting 142 programming 39, 40 Read Status 39, 40 Expander Module 33 see also SLC-2 20 F FACP see also Fire Alarm Control Panel 12 Features 12 Fire Alarm Control Panel see also FACP 12 Form-C relay 17, 28, 35 G general alarm zone 59 see also zone Z00 49 ground fault 34 H H350 18 H350R 18 Hazard Condition 111 History 88 erase 89 Maintenance Level 99 view events 89 History file 12 I I300 see also Isolator Module 19 Indicators 16 Installation 24 intelligent 12 Inventory 12 INVREP 125 Isolator Module 19 K Key Panel 16 function keys 16 service/program keys 16 keyboard and keypad 38 Keypad/Display removal and installation 30 L lamp test 16 LCD display 12, 16 LDM-32 Graphic Annunciator 13 LED AC Power 106 Alarm Silenced 106 Battery 106 Disabled 106 Fire Alarm 106 Ground 106 Maintenance 106 see also Indicators 16 Supervisory 106 Trouble 106 LED annunciator 22 Local Energy Municipal Box Service 31 Loop Setup 74 M M300 Monitor Module 20 M301 Miniature Monitor Module 20 M302 2-wire Monitor Module 20 main circuit, mounting 24 Maintenance Alert 12, 112 maintenance alert 125 levels 125 Maintenance Program Level 2 40, 97 Manual programming 39 Manual Pull Station 19 Master Program Level 1 40, 42 MDF-300 monitor module 19 Medical Alert 111 MMF-300 monitor module 19 MMF-301 monitor module (miniature) 19 MMF-302 monitor module 19 Mode key 41 Module 13 add 53 addressing 19 delete 54 edit monitor 54 enable/disable 57 see also addressable modules 19 Module Programming 53 Monitor module adjective 60 enable/disable 57 noun 61 noun/adjective 59 type 57 type action 58 Type list 57 type selection 58 monitor module 19 Mounting cabinet 24 main circuit board 24 municipal box transmitter see also 4XTMF module 31 N NAC 14, 17, 81, 111 Auto Silence 84 coded 113 coding 84 current 14 End-of-Line Resistor 14 power 12 see also Notification Appliance Unimode 9600 PN 51336:C 09/19/01 Index Circuit 12, 28 silence inhibit 85 silenceable 83 synchronized 113 type codes 83 voltage drop 14 voltage, operating 14 wiring diagram 28 wiring Style 28 NAC enable/disable 82 NAC options 75 NAC type 83 N-ELR Mounting Plate 20 NFPA Battery Requirements 130 nonpower-limited relay connections 28 Nonresettable Power 17, 27 current 14, 27 Normal 107 normal display 39 Notification Appliance Circuit 14, 81 see also NAC 12, 28 Noun monitor module 61 multiple entries 52 Noun list 51 Noun/Adjective 49, 51 control module 66 monitor module 59 O Off-line Programming 39 Operating Instructions 105 Operation alarm 109 disable/enable 112 hazard condition 111 medical alert 111 NAC 111 normal 107 process monitor 111 programmed zone 112 supervisory 110 trouble 107 waterflow 112 Option Modules 20, 30, 91 annunciators/UDACT 91 Printer/PC 92 Options 12 Output Circuits 17 P PAS 48, 71, 114 see also Positive Alarm Sequence 12, 47 selection 59 PAS BYPASS 114 PAS timer 79 Unimode 9600 PN 51336:C 09/19/01 Password 13, 40 change 93 Maintenance Level 2 41, 97 password Master Level 1 41 PC (personal computer) configuration 34 connection 34 ground fault 34 Piezo see also sounder 16 PK-9600 Programming Utility 21 Point Program 43 Positive Alarm Sequence 47, 114 see also PAS 12 power NAC 12 nonresettable 14 resettable smoke 14 system 12 power supply calculations 127 power-limited relay connections 28 Power-up first time 40 Pre-signal 12, 48, 71 function 113 selection 59 Pre-signal Delay timer 80 Pre-signal timer 79 primary power see also AC Power 27 printer baud rate 92 configuration 34 connection 34 ground fault 34 setup 34 Printer/PC interface 12 Process Monitor 111 Program check 95 check correlations 95 clear 94 Program Check Maintenance Level 100 program keys see also Key Panel 16 Programming 38, 39 autoprogramming 39 exiting 39 factory default 139 Level 1 40 Level 2 40 manual 39 Master Level 1 42 modules 53 off-line computer 39 via computer keyboard 38 via panel keypad 38 Programming Levels 40 Programming Screens 40 Programming Sheet 133, 134, 135, 136, 138 Programming Utility see also PK-9600 21 PRT/PK-CABLE for PC/Printer connection 34 R RA400Z see also detector annunciator 19 Read Status 39, 117 annunciators 123 exiting 39 history 122 NAC 121 power 120 Print 124 printer/PC 123 program check 122 relay 122 system point 118 Time-Date 126 timers 121 trouble reminder 120 zones 119 Real-Time Clock 112 Recall/Increment Function 52, 62, 69 Relay 14, 17, 28, 86 connections 28 contact rating 14, 17, 28 fixed 28 Form-C 14, 86 programmable 12, 17, 28 programming 86 selections 86 trouble 12, 17, 28 Relay Control Module see also ADT-ACM-8R 35 relay module 19 Relay options 75 Remote Station Service 31 remote switch functions 13 Reset 16, 105 Resettable Power 17, 27 current 27 see also Smoke Detector Power 14 S SD300 Photoelectric Detector 20 SD300T Photoelectric Detector 20 SD350 18 SD350T 18 143 Index Secondary Power Requirements 130 sensitivity 112 see also detector sensitivity 12 Signal rate 13 Signaling Line Circuit 14 Silence Inhibit 13, 85, 115 Silenceable control module 65 NAC 83 SLC 13, 14, 17 current 14 reference manual 14 resistance 14 see also Signaling Line Circuit 12 Style 17 voltage 14 wiring length 14 SLC Loop Protocol 74 SLC loop selection 43 SLC Style 74 SLC-2 33 installation 33 wiring 33 SLC-2 Expander Module 20 smoke detector chamber reading 124 data 124 sensitivity 112 Smoke Detector Power current 14 smoke detector sensitivity 12 Software Zones 12, 131 sounder 16 Specifications 14 strobe synchronization 13 Style 12 Style B 19 Style D 19 Style Y 19, 28 Style Z 19, 28 subscreen 40 Supervisory 110 sync programming 82 see also synchronization 85 synchronization 113, 121 by manufacturer 85 programming 85 see also strobe synchronization 13 Synchronized Signals 113 System Maintenance Level 101 System Point 118 system power 12 System Setup 75 144 T The 35 Time and Date Maintenance Level 102 Time setting 77 Time-Date setting 75, 77 Timers 75 Transmitter Module 31 see also 4XTMF module 20 Trouble 107 trouble display 108 trouble relay 12 Trouble Reminder 75, 115, 120 trouble responses 108 Type control module 65 detector 47 monitor module 57 NAC 83 type code control module 65 supervision 112 type-code verification 12 U UL power-limited wiring requirements 29 see also power-limited and nonpower-limited 28 Universal Bracket see also BRKT-9600 35 V Verification detector 47 Verify Loops 88 View Events 89 voltage measurements 120 ranges 120 W Walktest 12, 47, 66, 90 audible 90 Maintenance Level 101 operation 116 selection 59 silent 90 Waterflow Delay timer 79, 80 Waterflow Retard Timer 115 Wire Requirements 140 wiring AC Power 27 earth ground 27 SLC-2 33 wiring control modules see also Style Y or Style Z 19 wiring modules see also Style B or Style D 19 wiring Style 12 Z Z00 49, 59 Z97 PAS zone 48 Z98 48 Zone 97 71 Zone 98 71 Zone Assignment 49, 59 control module 66 Zone assignment 85 Zone Setup 70 Maintenance Level 103 zone type 73 list 73 Zone Z97 48 Zone Z98 pre-signal zone 48 Zones 119, 131 see also software zones 12 Zones Disabled 72 Zones Enabled 72 Zones Installed 72 zones per device 49 Unimode 9600 PN 51336:C 09/19/01 Notes 8QLPRGH31& Notes 8QLPRGH31& Notes 8QLPRGH31&
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.4 Linearized : Yes Encryption : Standard V1.2 (40-bit) User Access : Print, Copy, Fill forms, Extract, Assemble, Print high-res Create Date : 2001:11:06 14:34:29Z Modify Date : 2001:12:11 14:07:49-05:00 Page Count : 148 Creation Date : 2001:11:06 14:34:29Z Mod Date : 2001:12:11 14:07:49-05:00 Producer : Acrobat Distiller 5.0 (Windows) Author : PaulG Metadata Date : 2001:12:11 14:07:49-05:00 Creator : PaulG Title : adtuni9600_combenglC0.fmEXIF Metadata provided by EXIF.tools