Adt Security Services Unimode 9600 Users Manual Adtuni9600_combenglC0

51336 51336 AlarmHow.net Library

9600 to the manual c714076d-578e-4935-baa5-43f0e6098e67

2015-02-02

: Adt-Security-Services Adt-Security-Services-Unimode-9600-Users-Manual-413053 adt-security-services-unimode-9600-users-manual-413053 adt-security-services pdf

Open the PDF directly: View PDF PDF.
Page Count: 148

DownloadAdt-Security-Services Adt-Security-Services-Unimode-9600-Users-Manual- Adtuni9600_combenglC0  Adt-security-services-unimode-9600-users-manual
Open PDF In BrowserView PDF
ADT Security Services, Inc.
One Town Center Road
Boca Raton, FL 33431
Phone: (561) 988-3600
FAX: (561) 988-3675

Unimode9600
Addressable Fire Alarm Control Panel

Programming, Installation, Maintenance
and Operating Instruction Manual
IMPORTANT! The Signaling Line Circuit Wiring Manual Document #51520 must be referenced in
addition to this manual when installing or servicing the Fire Alarm Control Panel.

Document

#51336

11/06/01

Revision:

P/N 51336:C

C

ECN 01-535

Fire Alarm System Limitations

While a fire alarm system may lower insurance
rates, it is not a substitute for fire insurance!

An automatic fire alarm system–typically made up of smoke
detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control with remote notification
capability–can provide early warning of a developing fire.
Such a system, however, does not assure protection against
property damage or loss of life resulting from a fire.

Heat detectors do not sense particles of combustion and
alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Rate-of-rise
heat detectors may be subject to reduced sensitivity over time.
For this reason, the rate-of-rise feature of each detector
should be tested at least once per year by a qualified fire protection specialist. Heat detectors are designed to protect
property, not life.

The Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premise following the
recommendations of the current edition of the National Fire
Protection Association Standard 72 (NFPA 72),
manufacturer's recommendations, State and local codes, and
the recommendations contained in the Guide for Proper Use
of System Smoke Detectors, which is made available at no
charge to all installing dealers. A study by the Federal Emergency Management Agency (an agency of the United States
government) indicated that smoke detectors may not go off in
as many as 35% of all fires. While fire alarm systems are designed to provide early warning against fire, they do not guarantee warning or protection against fire. A fire alarm system
may not provide timely or adequate warning, or simply may not
function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot
reach the detectors such as in chimneys, in or behind walls, on
roofs, or on the other side of closed doors. Smoke detectors
also may not sense a fire on another level or floor of a building. A second-floor detector, for example, may not sense a
first-floor or basement fire.
Particles of combustion or "smoke" from a developing fire
may not reach the sensing chambers of smoke detectors because:
• Barriers such as closed or partially closed doors, walls, or
chimneys may inhibit particle or smoke flow.
• Smoke particles may become "cold," stratify, and not reach
the ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air
outlets.
• Smoke particles may be drawn into air returns before
reaching the detector.
The amount of "smoke" present may be insufficient to alarm
smoke detectors. Smoke detectors are designed to alarm at
various levels of smoke density. If such density levels are not
created by a developing fire at the location of detectors, the
detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing
limitations. Detectors that have photoelectronic sensing
chambers tend to detect smoldering fires better than flaming
fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast-flaming fires
better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither
type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate
warning of fires caused by arson, children playing with
matches (especially in bedrooms), smoking in bed, and violent
explosions (caused by escaping gas, improper storage of
flammable materials, etc.).

LimWarLg.p65

01/10/2000

IMPORTANT! Smoke detectors must be installed in the
same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling, and/or power. If detectors are not so located, a developing fire may damage the alarm system, crippling its ability to report a fire.
Audible warning devices such as bells may not alert people
if these devices are located on the other side of closed or
partly open doors or are located on another floor of a building.
Any warning device may fail to alert people with a disability or
those who have recently consumed drugs, alcohol or medication. Please note that:
• Strobes can, under certain circumstances, cause seizures
in people with conditions such as epilepsy.
• Studies have shown that certain people, even when they
hear a fire alarm signal, do not respond or comprehend the
meaning of the signal. It is the property owner's responsibility to conduct fire drills and other training exercise to make
people aware of fire alarm signals and instruct them on the
proper reaction to alarm signals.
• In rare instances, the sounding of a warning device can
cause temporary or permanent hearing loss.
A fire alarm system will not operate without any electrical
power. If AC power fails, the system will operate from standby
batteries only for a specified time and only if the batteries
have been properly maintained and replaced regularly.
Equipment used in the system may not be technically compatible with the control. It is essential to use only equipment
listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a
premise to a central monitoring station may be out of service
or temporarily disabled. For added protection against telephone line failure, backup radio transmission systems are recommended.
The most common cause of fire alarm malfunction is inadequate maintenance. To keep the entire fire alarm system in
excellent working order, ongoing maintenance is required per
the manufacturer's recommendations, and UL and NFPA standards. At a minimum, the requirements of Chapter 7 of NFPA
72 shall be followed. Environments with large amounts of
dust, dirt or high air velocity require more frequent maintenance. A maintenance agreement should be arranged
through the local manufacturer's representative. Maintenance
should be scheduled monthly or as required by National and/
or local fire codes and should be performed by authorized professional fire alarm installers only. Adequate written records
of all inspections should be kept.

Installation Precautions

Adherence to the following will aid in problem-free
installation with long-term reliability:

WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all sources
of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards,
modules, or interconnecting cables while the unit is energized.
Do not attempt to install, service, or operate this unit until this
manual is read and understood.
CAUTION - System Reacceptance Test after Software
Changes. To ensure proper system operation, this product
must be tested in accordance with NFPA 72 Chapter 7 after
any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested.
In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not
directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.
This system meets NFPA requirements for operation at
0-49° C/32-120° F and at a relative humidity of 85% RH (noncondensing) at 30° C/86° F. However, the useful life of the
system's standby batteries and the electronic components
may be adversely affected by extreme temperature ranges
and humidity. Therefore, it is recommended that this system
and all peripherals be installed in an environment with a nominal room temperature of 15-27° C/60-80° F.
Verify that wire sizes are adequate for all initiating and
indicating device loops. Most devices cannot tolerate more
than a 10% I.R. drop from the specified device voltage.

Like all solid state electronic devices, this system may
operate erratically or can be damaged when subjected to lightning-induced transients. Although no system is completely
immune from lightning transients and interferences, proper
grounding will reduce susceptibility. Overhead or outside
aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Services Department if any problems are anticipated or
encountered.
Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing,
reaming, or punching of the enclosure. When possible, make
all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, and printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs.
Over-tightening may damage threads, resulting in reduced
terminal contact pressure and difficulty with screw terminal
removal.
Though designed to last many years, system components
can fail at any time. This system contains static-sensitive
components. Always ground yourself with a proper wrist strap
before handling any circuits so that static charges are removed from the body. Use static-suppressive packaging
to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and
programming manuals. These instructions must be followed
to avoid damage to the control panel and associated
equipment. FACP operation and reliability depend upon
proper installation by authorized personnel.

FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and
used in accordance with the instruction manual, may
cause interference to radio communications. It has
been tested and found to comply with the limits for class
A computing device pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable
protection against such interference when operated in a
commercial environment. Operation of this equipment in
a residential area is likely to cause interference, in which
case the user will be required to correct the interference
at his own expense.

Canadian Requirements
This digital apparatus does not exceed the Class A
limits for radiation noise emissions from digital
apparatus set out in the Radio Interference Regulations
of the Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits
radioelectriques depassant les limites applicables aux
appareils numeriques de la classe A prescrites dans le
Reglement sur le brouillage radioelectrique edicte par le
ministere des Communications du Canada.

LimWarLg.p65

01/10/2000

Notes

4

Unimode 9600 PN 51336:C

11/06/01

Table of Contents

SECTION 1: Product Description ........................................................................................................................12
1.1: Inventory .....................................................................................................................................................12
1.2: Features and Options ...................................................................................................................................12
1.3: Specifications ..............................................................................................................................................14
1.3.1: Current Availability...........................................................................................................................15
1.4: Controls and Indicators ...............................................................................................................................16
1.5: Circuits ........................................................................................................................................................17
1.6: Components.................................................................................................................................................17
1.6.1: Intelligent Addressable Detectors: Newer Series..............................................................................18
1.6.2: Intelligent Addressable Modules: Newer Series ...............................................................................19
1.6.3: 300 Series Intelligent Addressable Devices......................................................................................20
1.6.4: Addressable Device Accessories.......................................................................................................20
1.7: Optional Modules ........................................................................................................................................20
1.8: Accessories..................................................................................................................................................21
1.8.1: PK-9600 Programming Utility..........................................................................................................21
1.8.2: Dress Panel........................................................................................................................................21
1.8.3: Battery Box .......................................................................................................................................21
1.8.4: ADT-CHG-120 Battery Charger.......................................................................................................22
1.8.5: Annunciators .....................................................................................................................................22
1.9: Getting Started.............................................................................................................................................23
SECTION 2: Installation .......................................................................................................................................24
2.1: Mounting .....................................................................................................................................................24
2.2: Power...........................................................................................................................................................27
2.2.1: AC Power and Earth Ground Connection.........................................................................................27
2.2.2: Battery Power....................................................................................................................................27
2.2.3: DC Power Output Connection ..........................................................................................................27
2.3: Relays ..........................................................................................................................................................28
2.4: Notification Appliance Circuits ..................................................................................................................28
2.5: UL Power-limited Wiring Requirements ....................................................................................................29
2.6: Optional Modules and Devices ...................................................................................................................30
2.6.1: 4XTMF Transmitter Module Installation..........................................................................................31
2.6.2: Auxiliary Trouble Input (J16 & J17).................................................................................................32
2.6.3: SLC-2 Expander Module ..................................................................................................................33
2.6.4: Printer/PC..........................................................................................................................................34
2.6.5: Digital Communicator and Annunciators .........................................................................................35
2.6.5.1 ADT-UDACT Digital Alarm Communicator/Transmitter .....................................................35
2.6.5.2 ADT-ACM-8R Relay Control Module ...................................................................................35
2.6.5.3 BRKT-9600 Universal Bracket Installation ............................................................................35
2.6.5.4 ADT-ACS and ADT-AFM Series Annunciators ....................................................................37
SECTION 3: Programming ...................................................................................................................................38
3.1: Programming Data Entry ............................................................................................................................38
3.2: User Programming ......................................................................................................................................39
3.3: Initial Power-up...........................................................................................................................................40
3.4: Programming Screens Description..............................................................................................................40
3.5: Programming and Passwords ......................................................................................................................40
3.6: Master Programming Level.........................................................................................................................42
3.6.1: Point Program ...................................................................................................................................43
3.6.1.1 Detector Programming ............................................................................................................43
3.6.1.1.1 Add Detector ........................................................................................................................43
3.6.1.1.2 Delete Detector ....................................................................................................................44
3.6.1.1.3 Edit Detector ........................................................................................................................44
3.6.1.2 Module Programming .............................................................................................................53
Unimode 9600

P/N: 51336:C 11/06/01

5

Table of Contents

3.6.1.2.1 Add Module .........................................................................................................................53
3.6.1.2.2 Delete Module ......................................................................................................................54
3.6.1.2.3 Edit Module Screen for Monitor Module .............................................................................54
3.6.1.2.4 Edit Module Screen for Control Modules ............................................................................63
3.6.2: Zone Setup.........................................................................................................................................70
3.6.2.1 Enable ......................................................................................................................................70
3.6.2.2 Disable .....................................................................................................................................71
3.6.2.3 Zone 97, 98 and 99 ..................................................................................................................71
3.6.2.4 Zones Installed ........................................................................................................................72
3.6.2.5 Zones Enabled .........................................................................................................................72
3.6.2.6 Zones Disabled ........................................................................................................................72
3.6.2.7 Zone Type ...............................................................................................................................73
3.6.3: Loop Setup ........................................................................................................................................74
3.6.3.1 Style .........................................................................................................................................74
3.6.3.2 Loop Protocol ..........................................................................................................................74
3.6.4: System Setup .....................................................................................................................................75
3.6.4.1 Trouble Reminder ...................................................................................................................75
3.6.4.2 Banner .....................................................................................................................................76
3.6.4.3 Time-Date ...............................................................................................................................77
3.6.4.3.1 Time .....................................................................................................................................77
3.6.4.3.2 Date ......................................................................................................................................78
3.6.4.3.3 Clock Format ........................................................................................................................78
3.6.4.3.4 Daylight Savings Time .........................................................................................................78
3.6.4.4 Timers .....................................................................................................................................79
3.6.4.4.1 PAS (Positive Alarm Sequence) Delay ................................................................................79
3.6.4.4.2 Pre-signal Delay ...................................................................................................................80
3.6.4.4.3 Waterflow Delay ..................................................................................................................80
3.6.4.4.4 AC Loss Delay .....................................................................................................................81
3.6.4.5 NAC (Notification Appliance Circuit) ....................................................................................81
3.6.4.5.1 Enabled .................................................................................................................................82
3.6.4.5.2 Type ......................................................................................................................................83
3.6.4.5.3 Silenceable ...........................................................................................................................83
3.6.4.5.4 Auto Silence .........................................................................................................................84
3.6.4.5.5 Coding ..................................................................................................................................84
3.6.4.5.6 Zone ......................................................................................................................................85
3.6.4.5.7 Silence Inhibited ...................................................................................................................85
3.6.4.5.8 Synced Type .........................................................................................................................85
3.6.4.6 Relays ......................................................................................................................................86
3.6.5: Autoprogram .....................................................................................................................................87
3.6.6: Verify Loops ......................................................................................................................................88
3.6.7: History...............................................................................................................................................88
3.6.7.1 View Events ............................................................................................................................89
3.6.7.2 Erase History ...........................................................................................................................89
3.6.8: Walktest .............................................................................................................................................90
3.6.9: Option Modules................................................................................................................................91
3.6.9.1 Annunciators/UDACT ............................................................................................................91
3.6.9.2 Printer/PC ................................................................................................................................92
3.6.10: Password Change ............................................................................................................................93
3.6.11: Clear Program..................................................................................................................................94
3.6.12: Program Check................................................................................................................................95
3.7: Maintenance Programming Level ...............................................................................................................97
3.7.1: Disable Point .....................................................................................................................................98
3.7.2: History...............................................................................................................................................99
3.7.3: Program Check..................................................................................................................................100
3.7.4: Walktest .............................................................................................................................................101
6

Unimode 9600

P/N: 51336:C 11/06/01

Table of Contents

3.7.5: System ...............................................................................................................................................101
3.7.6: Zone Setup ........................................................................................................................................103
SECTION 4: Operating Instructions ....................................................................................................................105
4.1: Panel Control Buttons .................................................................................................................................105
4.1.1: Acknowledge/Step ............................................................................................................................105
4.1.2: Alarm Silence....................................................................................................................................105
4.1.3: Drill/Hold 2 Sec ................................................................................................................................105
4.1.4: Reset..................................................................................................................................................105
4.2: LED Indicators ............................................................................................................................................106
4.3: Normal Operation........................................................................................................................................107
4.4: Trouble Operation .......................................................................................................................................107
4.5: Alarm Operation..........................................................................................................................................109
4.6: Supervisory Operation.................................................................................................................................110
4.7: Process Monitor Operation..........................................................................................................................111
4.8: Hazard Condition Operation .......................................................................................................................111
4.9: Medical Alert Condition Operation.............................................................................................................111
4.10: NAC Operation .........................................................................................................................................111
4.11: Programmed Zone Operation ....................................................................................................................112
4.12: Disable/Enable Operation .........................................................................................................................112
4.13: Waterflow Circuits Operation ...................................................................................................................112
4.14: Detector Functions ....................................................................................................................................112
4.15: Time Functions: Real-Time Clock ............................................................................................................112
4.16: Synchronized NAC Operation ..................................................................................................................113
4.17: Coded Operation .......................................................................................................................................113
4.18: Presignal ....................................................................................................................................................113
4.19: Positive Alarm Sequence ..........................................................................................................................114
4.20: Special System Timers ..............................................................................................................................115
4.20.1: Silence Inhibit Timer.......................................................................................................................115
4.20.2: Autosilence Timer ...........................................................................................................................115
4.20.3: Trouble Reminder ...........................................................................................................................115
4.20.4: Waterflow Retard Timer..................................................................................................................115
4.20.5: Alarm Verification (None or Two Minutes)....................................................................................116
4.21: Walktest .....................................................................................................................................................116
4.22: Read Status ................................................................................................................................................117
4.22.1: System Point ...................................................................................................................................118
4.22.2: Zones ...............................................................................................................................................119
4.22.3: Power...............................................................................................................................................120
4.22.4: Trouble Reminder ...........................................................................................................................120
4.22.5: Timers..............................................................................................................................................121
4.22.6: NAC ................................................................................................................................................121
4.22.7: Relays..............................................................................................................................................122
4.22.8: Program Check................................................................................................................................122
4.22.9: History.............................................................................................................................................122
4.22.10: Annunciators .................................................................................................................................123
4.22.11: Printer/PC ......................................................................................................................................123
4.22.12: Print ...............................................................................................................................................124
4.22.13: Time-Date......................................................................................................................................126
SECTION 5: Power Supply Calculations .............................................................................................................127
5.1: Overview .....................................................................................................................................................127
5.2: Calculating the AC Branch Circuit .............................................................................................................127
5.3: Calculating the System Current Draw.........................................................................................................128
5.3.1: Overview ...........................................................................................................................................128
5.3.2: How to Use Table 5.3 on page 129 to Calculate System Current Draw ...........................................128
5.4: Calculating the Battery Size ........................................................................................................................130
Unimode 9600

P/N: 51336:C 11/06/01

7

Table of Contents

5.4.1: NFPA Battery Requirements .............................................................................................................130
5.4.2: Selecting and Locating Batteries.......................................................................................................130
APPENDIX A: Software Zones ............................................................................................................................131
A.1: Correlations ...............................................................................................................................................131
APPENDIX B: Default Programming .................................................................................................................139
APPENDIX C: Wire Requirements .....................................................................................................................140

8

Unimode 9600

P/N: 51336:C 11/06/01

It is imperative that the installer understand the requirements of the Authority Having Jurisdiction
(AHJ) and be familiar with the standards set forth by the following regulatory agencies:
•
•
•

Underwriters Laboratories Standards
NFPA 72 National Fire Alarm Code
CAN/ULC - S527M Standard for Control Units for Fire Alarm Systems

Before proceeding, the installer should be familiar with the following documents.
NFPA Standards
NFPA 72 National Fire Alarm Code
NFPA 70 National Electrical Code
Underwriters Laboratories Documents:
UL 38 Manually Actuated Signaling Boxes
UL 217 Smoke Detectors, Single and Multiple Station
UL 228 Door Closers–Holders for Fire Protective Signaling Systems
UL 268 Smoke Detectors for Fire Protective Signaling Systems
UL 268A Smoke Detectors for Duct Applications
UL 346 Waterflow Indicators for Fire Protective Signaling Systems
UL 464 Audible Signaling Appliances
UL 521 Heat Detectors for Fire Protective Signaling Systems
UL 864 Standard for Control Units for Fire Protective Signaling Systems
UL 1481 Power Supplies for Fire Protective Signaling Systems
UL 1610 Central Station Burglar Alarm Units
UL 1638 Visual Signaling Appliances
UL 1971 Signaling Devices for Hearing Impaired
CAN/ULC - S524M Standard for Installation of Fire Alarm Systems
CAN/ULC S527M Standard for Control Units for Fire Alarm Systems
Other:
EIA-232E Serial Interface Standard
EIA-485 Serial Interface Standard
NEC Article 250 Grounding
NEC Article 300 Wiring Methods
NEC Article 760 Fire Protective Signaling Systems
Applicable Local and State Building Codes
Requirements of the Local Authority Having Jurisdiction (LAHJ)
ADT Documents:
ADT Device Compatibility Document
ADT-SLC Wiring Manual
ADT-AFM-16AT & AFM-32A
ADT-AFM-16A Annunciator
ADT-ACS Series Annunciators
ADT-UDACT Communicator/Transmitter
ADT-CHG-120 Battery Charger
ADT-LDM Series Lamp Driver Modules
LCD-80F Remote Fire Annunciator
ADT-ACM-8R Relay Control Module

Unimode 9600 PN 51336:C

11/06/01

Document #51352
Document #51520
Document #A15048
Document #A15207
Document #51353
Document #50934
Document #50938
Document #51351
Document #51338
Document #51356

9

10

Unimode 9600 PN 51336:C

11/06/01

9600lay3.cdr

CAUTION!

2
1
+

+

-

B A A B B A A B
+ + - - + + - -

J17

DISABLE
GND
FLT

JP2

TB4

4XTMF OPT BD

120 VAC, 60 HZ, 3.2 amps

HOT NEUT EARTH

TB1

LCD DISPLAY

A Fail Safe Trouble NC NO C
relay switches to the
NO position during
trouble conditions and
under loss of all power.

J8

OPT DACT

KEYPAD I/F

J2

JP5

TB7

Cut this jumper to enable
Supervisory relay when
4XTMF module is installed

shield

Connector for Optional 2nd
Signalling Line Circuit Module

PS2 Keyboard Interface

Flash Memory Load Enable Switch.
UP is normal position for switch.
DOWN position allows loading of
factory software upgrades

J7

SW1

Cut this jumper to supervise
the 4XTMF module when
installed (see JP10 & JP11)

24 VDC, 25 Amp Hour maximum

Battery

+BATTERY-

TB2

J6

JP6

CUT TO
MONITOR 4XTMF

J11

TB6

(*Factory default relay programming
as shown on circuit board)

TB5

DB9F

9 8 7 6

5 4 3 2 1

OR

5 4 3 2 1

25 24 23 22 21 20 19 18 17 16 15 14

13 12 11 10 9 8 7 6

For EDP-listed equipment or
personal computer with FACP
Upload/Download Utility.
50 foot maximum within same room.

EIA-232
to printer or
personal computer

J3

OPT SLC

TB8

(option to DB-25)

T R D G
XC T N
V R D

TERM
Red
(EIA-485)
ACS (EIA-485) White
to LCD-80F
TB7
to ACS Annunc. Green
or UDACT-F
Black
(power-limited,
supervised)
T R D G I I O O
X C T N N N U U
V R D + - T T B A B AA B
Alarm* Trouble Supervisory*
+ + - + + NO NC C NC NO C NO NC C

Contacts shown below in normal
condition (AC power with no alarm,
trouble or supervisory activity).

Contact Ratings:
2.0 amps @ 30 VDC (resistive)
0.5 amps @ 30 VAC (resistive)

2 Programmable Relays &
1 Fixed Trouble Relay

Connectors for 4XTMF option module

J16

CB1

+

+

+

Cut this jumper to disable the
FACP battery charger when
using external charger.

-

J10

+

+

+

+

ELR 4.7K, ½W

NAC #2
NAC #1
Style Y or
Style Y (shown)
Style Z (shown)
or Style Z
3.0 amps max. 3.0 amps max.

Notification Appliance Circuits

To disable ground fault detection,
remove jumper/shunt from JP2

-

6
5

CUT TO
DISABLE
LOCAL
CHARGER

JP3

TB3

4
3

HIGH VOLTAGE

Resettable Power - 24 VDC filtered, power-limited
(3.00 amps maximum) to smoke detectors (IDC).
Supervision required.

Nonresettable Power #1 - 24 VDC filtered,
power-limited (3.00 amps maximum)
Supervision required. Suitable for
powering annunciators.

Nonresettable Power #2 - 24 VDC filtered,
power-limited (3.00 amps maximum)
Supervision required. Suitable for
powering annunciators.

Supervise with a power supervision relay A77-716B

DC Power Outputs (24 VDC)

MS-9600 Basic System Connections

SLC Loop
Refer to the SLC Wiring
Manual for detailed
information on wiring
addressable devices
for Style 4, 6 and 7.

Peripheral Devices and Their Documents:

ADT-AFM-16AT &
ADT-AFM-32A
Doc. # A15048

ADT-ACS Series
Doc. # 51353

ADT-ACM-8R
Doc. # 51356

ACS (EIA-485)
Annunciators

ADT-AFM-16A
Doc. # A15207

Ack/Step

TERM (EIA-485)
Annunciators

Silence

Drill

Hold 2 sec.

ADT-LDM-32
Doc. # 51351

Reset

ADT-LCD-80F
Doc. # 51589

Unimode 9600
Doc. # 51336
1

SLC Loop

9600peri.cdr

ADT-UDACT
Doc. # 50934

Addressable Devices and SLC Wiring
Doc. # 51309

Battery Connector

ADT-CHG-120 Charger
Doc. # 50938

Unimode 9600 PN 51336:C

11/06/01

11

3URGXFW'HVFULSWLRQ

,QYHQWRU\

Product Description

SECTION 1

The ADT Unimode 9600 is a compact, cost effective, intelligent addressable FACP (Fire
Alarm Control Panel) with an extensive list of powerful features. The combination of
newer series devices and legacy 300 Series devices, along with the Unimode 9600 FACP,
offer the latest in fire protection technology. The power supply and all electronics are
contained on a single circuit board housed in a metal cabinet, providing a complete fire
control system for most applications. Optional modules, which plug into the main circuit
board, are available for special functions. Available accessories include LED, graphic and
LCD annunciators, reverse polarity/city box transmitter, digital alarm communicator/
transmitter, SLC expansion module, local and remote upload/download software and
remote power expansion.

1.1 Inventory
When the Unimode 9600 shipment is received, check to make certain that all parts have
been included in the shipment. The Unimode 9600 shipment should consist of one of each
of the following:
✓
✓
✓
✓

main circuit board with display
backbox with door
plastic bag containing screws, cables, key, etc.
manual

1.2 Features and Options



•

Single standard addressable SLC loop which meets NFPA Style 4, 6 and 7
requirements

•

Optional module for adding a second SLC loop which meets NFPA Style 4, 6 and 7
requirements

•

318 addressable device capacity for each SLC loop (159 detectors and 159 control/
monitor modules)

•

99 software zones

•

Two onboard NACs (Notification Appliance Circuits) with additional NAC
capability using control modules

•

6.0 amps total power for NACs and 24 VDC auxiliary power outputs

•

7.2 amps total system power (includes battery charger)

•

Two programmable relay outputs and one fixed trouble relay

•

EIA-232 Printer/PC interface (variable baud rate)

•

80-character LCD display (backlit)

•

Real-time clock/calendar with daylight savings time control

•

History file with 1,000 event capacity

•

Advanced fire technology features:

•

✓ Automatic drift compensation
✓ Maintenance alert
✓ Detector sensitivity test capability (NFPA 72 compliant)
✓ Automatic device type-code verification
✓ Point trouble identification
Waterflow selection per module point

•

Alarm verification selection per detector point

•

Walktest, silent or audible

•

PAS (Positive Alarm Sequence) and Pre-signal per point (NFPA 72 compliant)

8QLPRGH31&

Features and Options

Product Description
•

Annunciators:

•

✓ ADT-AFM-LED Zone Annunciator Series
✓ ADT-LDM Graphic Annunciator Series
✓ ADT-LCD-80F Liquid Crystal Display point annunciator
✓ ADT-ACM-8R Relay Module
Silence inhibit timer option per NAC

•

Autosilence timer option per NAC

•

Continuous, March Time, Temporal or California code for main circuit board NACs
with two-stage capability

•

Selectable strobe synchronization per NAC

•

Remote Acknowledge, Alarm Silence, Reset and Drill via addressable modules,
ADT-AFM annunciators or ADT-LCD-80F Remote annunciator

•

Auto-program (learn mode) reduces installation time. Reports two devices set to
the same address

•

Password and key-protected nonvolatile memory

•

User programmable password

•

Fully programmable from local keypad or keyboard or local PC

•

SLC operates up to 10,000 ft. (3,000 m) with twisted, shielded wire or 3,000 ft (900
m) with untwisted, unshielded wire

•

Compatible with newer series devices (CLIP Mode)
✓ CP350: addressable Ionization Smoke Detector
✓ SD350(T): addressable Photo Smoke Detector (T= with Thermal Sensor)
✓ H350(R): Fast Response Heat Detector (R=Rate-of-Rise option)
✓ D350P(R): addressable Photo Duct Detector (R=alarm relay option)
✓ B501BH & B501BHT Sounder Bases
✓ BB224RB Relay Base
✓ BB224BI Isolator Base
✓ MMF-300: Monitor Module
✓ MDF-300: Dual Monitor Module (uses two consecutive SLC addresses)
✓ MMF-301: Miniature Monitor Module
✓ MMF-302: 2-wire Detector Module
✓ CMF-300: Control Module
✓ CRF-300: Relay Module
✓ ADT-BG-12LX: Manual Pull Station
✓ I300: Isolator Module

•

Compatible with legacy 300 Series devices (CLIP Mode only):
✓ CP300: addressable Ionization Smoke Detector
✓ SD300(T): addressable Photoelectric Smoke Detector (T= Thermal Sensor)
✓ C304: Control Module
✓ M300: Monitor Module
✓ M301: Miniature Monitor Module
✓ M302: 2-wire Detector Module
✓ ADT-BG-10LX: Manual Pull Station

•

Unimode 9600 PN 51336:C

11/06/01

Optional 4XTMF module (conventional reverse polarity/city box transmitter)

13

Product Description

Specifications

1.3 Specifications
AC Power - TB1
120 VAC, 60 Hz, 3.2 amps
Wire size: minimum 14 AWG (2.00 mm2) with 600 V insulation
Battery (Lead Acid Only) - TB2
Maximum Charging Circuit: Normal Flat Charge - 27.6 VDC @ 1.00 amp
Maximum Battery Charger Capacity: 25 Amp Hour (Unimode 9600 cabinet holds
maximum of two 18 Amp Hour batteries. For greater than 25 Amp Hour up to 120 Amp
Hour batteries, use the ADT-CHG-120 Battery Charger and BB-55F Battery Box.
Note: Jumper JP3, on the FACP main circuit board, must be cut to disable the FACP
battery charger when using the ADT-CHG-120.
Communication Loop - (Standard ) TB8 and (Optional SLC Expander Module) J3
24 VDC nominal, 27.6 VDC maximum
Maximum length is 10,000 ft. (3,000 m) total twisted, shielded pair length
Maximum loop current is 400 mA (short circuit) or 100 mA (normal)
Maximum loop resistance is 40 ohms
Supervised and power-limited
Refer to SLC Loop manual for wiring information
Notification Appliance Circuits - TB4
Power-limited circuitry
Maximum voltage drop in wiring: 2.0 VDC
Nominal operating voltage: 24 VDC
Current-limit: fuseless, electronic, power-limited circuitry
Maximum signaling current per circuit: 3.00 amps (see Figure 1.1 on page 15)
End-of-Line Resistor: 4.7 kΩ, ½ watt (P/N 71252 UL listed) for NACs
Refer to ADT Device Compatibility Document for listed compatible devices
Two Programmable and One Fixed Output Relay - TB5
Contact rating: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive)
Form-C relays
Refer to Figure 2.5 on page 28 for information on power-limited wiring for relay circuits
Four-Wire Resettable Smoke Detector Power (24 VDC nominal) - TB3,
Terminals 1 (+) & 2 (-)
Maximum ripple voltage: 10 mVRMS
Up to 3.0 amps is available for powering 4-wire smoke detectors (see Figure 1.1)
Power-limited circuit
Refer to ADT Device Compatibility Document for listed compatible devices
Nonresettable Power #1 (24 VDC Nominal) - TB3, Terminals 3 (+) & 4 (-)
Maximum ripple voltage: 10mVRMS
Total DC current available from each output is up to 3.00 amps (see Figure 1.1)
Power-limited circuit
Nonresettable Power #2 (24 VDC Nominal) - TB3, Terminals 5 (+) & 6 (-)
Maximum ripple voltage: 10mVRMS
Total DC current available from each output is up to 3.00 amps (see Figure 1.1)
Power-limited circuit

14

Unimode 9600 PN 51336:C

11/06/01

Specifications

Product Description
EIA-485 (ACS) - TB6
ACS annunciator connector, Terminal 1 (+) and Terminal 2 (-)
EIA-485 (TERM) - TB7
Terminal Mode annunciator connector, Terminal 5 (In +), 6 (In -), 7 (Out +), 8 (Out -)
EIA-232 (ACS) - TB7
PC/Printer Connector, Terminal 1 (Transmit), 2 (Receive), 3 (DTR), 4 (Ground)
Auxiliary Trouble Inputs - J16 & J17
Two-pin connectors which can be used to monitor trouble conditions on auxiliary
equipment. They can be connected to the trouble bus of a peripheral such as the ADTCHG-120 or to the normally-open dry contacts of a trouble relay.
CAUTION! Do not connect power to these connectors since circuit damage may result.

1.3.1 Current Availability
The following figure illustrates the maximum current that is possible for each panel circuit
and the total current available from the FACP power supply.

TB3
Resettable Power
for 4-Wire
Smoke Detectors

1

3 amps max
per circuit

2
3

Nonresettable
Power # 1

3 amps max
per circuit

4
5

Nonresettable
Power # 2

6

Standby
6 amps max
per panel

3 amps max
per circuit

Alarm
7 amps max

1
2

NAC # 1

3 amps max

per panel

per circuit

3
4
5
6

NAC # 2

7

3 amps max
per circuit

8

TB4

Refer to the battery calculations section for additional information.

Figure 1.1 Current Availability

Unimode 9600 PN 51336:C

11/06/01

15

Product Description

Controls and Indicators

1.4 Controls and Indicators
LCD Display
The FACP uses an 80-character (4 lines
X 20 characters) high viewing angle
LCD display. The display includes a
long life LED backlight that remains
illuminated. If AC power is lost and the
system is not in alarm, the LED
backlight will turn off to conserve batteries.

SYSTEM ALL NORMAL
10:00A 010101

LED Indicators
LED indicators are provided to annunciate the following conditions:
•
•
•
•
•
•
•
•
•

AC Power (green)
Fire Alarm (red)
Supervisory (yellow)
Trouble (yellow)
Maintenance/presignal (yellow)
Alarm Silenced signals (yellow)
Disabled (yellow)
Battery fault (yellow)
Ground fault (yellow)

Key Panel
Mounted on the main circuit board, the key panel includes a window for the LCD display
and LED indicators as listed above. The key panel, which is visible with the cabinet door
closed, has 25 keys, including a 16 key alpha-numeric pad similar to a telephone keypad.
Function keys:
Acknowledge/Step
Alarm Silence
Drill
Reset (lamp test)

Service/program keys:
•
•
•
•
•
•
•
•
•
•

AC POWER

MAINTENANCE

FIRE ALARM

ALARM
SILENCED

SUPERVISORY

DISABLED

TROUBLE

BATTERY
GROUND

2

1
4

5

ACK/STEP

1st

3
DEF

ABC

6

EVENT

ALARM
SILENCE

CLR

Keys labeled 1 to 9
7
8
9
* key
0
#
# key
*
-/.
0 (recall) key
1st Event key
Figure 1.2 Membrane/Display Panel
Clear key
Escape key
Mode key
Four cursor keys (up, down, left and right)
Enter key
GHI

JKL

MNO

PRS

TUV

WXY

ENTER

ESC

DRILL

HOLD 2 SEC

MODE

RESET

QZ

RECALL

9600kypd.cdr

•
•
•
•

Local Piezo Sounder
A piezo sounder provides separate and distinct pulse rates for alarm, trouble and
supervisory conditions.

16

Unimode 9600 PN 51336:C

11/06/01

Circuits

Product Description

1.5 Circuits
SLC Communication Loop

Reference
Manual

One SLC loop is provided standard on the FACP main circuit board. A second SLC loop
is available by plugging the optional SLC module into connector J3 on the main circuit
board. SLC loops, configurable for NFPA Style 4, 6 or 7, provide communication to
addressable detectors, monitor (initiating device) and control (output device) modules.
Refer to the ADT SLC Wiring Manual for information on wiring devices.
Output Circuits
The following output circuits are available on the FACP:
•

24 VDC Resettable (smoke detector power) output - 3.00 amps maximum

•

24 VDC Nonresettable power output #1 - 3.00 amps maximum

•

24 VDC Nonresettable power output #2 - 3.00 amps maximum

•

24 VDC Battery Charger (up to 25 AH batteries)

NAC (Notification Appliance Circuits)
Two NACs, configurable for Style Y (Class B) or Style Z (Class A), are provided with
various programmable features.
Relays
One fixed and two fully programmable Form-C dry contact relays are provided. The fixed
fail-safe relay monitors system trouble and the two programmable relays are factory
default programmed for system alarm and system supervisory. Contacts are rated 2.0
amps @ 30 VDC (resistive) and 0.5 amps @ 30 VAC (resistive). The programmable
relays can be programmed for the following operations:
•
•
•
•
•
•
•
•
•
•

fire alarm
trouble
supervisory
supervisory auto-resettable
DACT communication failure
process monitor
process monitor auto-resettable
hazard alert
medical alert
AC loss

Auxiliary Trouble Inputs
Auxiliary Trouble Inputs can be connected to trouble bus outputs from auxiliary
equipment, such as power supplies, or normally-open dry contacts of a trouble relay to
allow monitoring by the Unimode 9600.

1.6 Components
Main Circuit Board

See Page

Unimode 9600 PN 51336:C

The main circuit board contains the system’s CPU, power supply, other primary
components and wiring interface connectors. Optional modules plug in and are mounted
to the main circuit board. The circuit board is delivered in the Unimode 9600 kit and must
be mounted to the backbox. Refer to the circuit board illustration on Page 10.

11/06/01

17

Product Description

Components
Cabinet

uni-600.cdr

The Unimode 9600 cabinet is red with a navy blue front overlay.
The backbox provides space for two batteries (up to 18 Amp
Hour). Ample knockouts are provided for system wiring. Also
included is a standard dress panel, which mounts to the inside of
the cabinet (required on the ULC version). The dress panel must
be installed to meet FM requirements.

Batteries
The Unimode 9600 cabinet provides space for two batteries (up to
18 Amp Hour). Batteries larger than 18 Amp Hour up to 25 Amp Hour require use of UL
listed battery cabinet. The ADT-CHG-120 can be used for charging 25 to 120 AH
batteries and the BB-55F can be used for housing the batteries. Batteries must be ordered
separately.

1.6.1 Intelligent Addressable Detectors: Newer Series
Intelligent, addressable detectors provide information to the control panel on an SLC
Signaling Line Circuit (refer to the ADT SLC Wiring Manual for detailed information on
device installation, wiring and operation). This allows the control panel to continually
process the information to determine the status (alarm, trouble, maintenance or normal) of
each detector. Each detector responds to an SLC address that is set in the detector head
using built-in rotary decimal switches with the ability to select up to 159 addresses. Note
that a blinking LED on an intelligent detector indicates communication between the
detector and the control panel. Refer to the ADT Device Compatibility Document for a
list of approved detectors.
Smoke Detectors (Photoelectric)
The SD350 is an intelligent, addressable low profile photoelectric smoke detector which
provides smoke sensing technology. The SD350T includes a 135o fixed thermal sensor.
Smoke Detector (Ionization)
The CP350 is an intelligent, addressable low profile ionization smoke detector which
measures the level of combustion products in its chamber using the ‘ionization principle.’
Smoke Detector (Duct)
The D350P is an intelligent, addressable photoelectric duct smoke detector. The D350RP
includes an alarm relay.
Heat Detectors
The H350 is an intelligent heat detector with a thermistor sensing circuit for fast response,
designed to provide open area protection with 50 foot (15 m) spacing capability. The
H350R incorporates a thermal Rate-of-Rise circuit of 15oF (9.4oC).
Detector Bases
The B501BH is a standard sounder base and the B501BHT is a temporal tone sounder
base for intelligent, addressable smoke detectors.
The B224RB is a relay base with one Form-C relay for intelligent, addressable smoke
detectors. It may be used to control auxiliary functions.
The B224BI is an isolator base for intelligent, addressable smoke detectors. It functions
similar to the I300 isolator module which allows loops to operate under fault conditions
and automatically restore when the fault is removed.

18

Unimode 9600 PN 51336:C

11/06/01

Components

Product Description

1.6.2 Intelligent Addressable Modules: Newer Series

Reference
Manual

The newer series of Control Modules and Monitor Modules provide an interface between
the control panel and conventional notification and initiating devices. Each module can be
set to respond to an address with built-in rotary switches with the ability to select up to
159 addresses (a tab on the address switch must be broken off to use addresses 100-159).
A blinking LED on a monitor module indicates communication between the module and
the control panel. These devices can also be used in CLIP Mode (Classic Loop Interface
Protocol) when installed on older systems. Refer to the ADT Device Compatibility
Document for a list of approved notification and initiating devices.
Monitor Modules
The MMF-300, MDF-300 and MMF-302 are addressable monitor modules for monitoring
conventional initiating devices. The MMF-300 is used for normally open contact alarm
initiating devices, such as manual pull stations, four-wire smoke detectors, heat detectors,
waterflow, security contacts and supervisory devices. The MDF-300 is a dual monitor
module (Class B only) which occupies two consecutive SLC addresses, with each module
functionally the same as the MMF-300. The MMF-302 is used primarily for two-wire
smokes detectors in addition to normally open contact devices. The supervised IDCs
(Initiating Device Circuits) can be wired to the modules as NFPA Style B (Class B) or
Style D (Class A) circuits. The modules are supplied with a thermoplastic cover for
mounting to a 4-inch mounting box.
Monitor Module (miniature)
The MMF-301 is an addressable module that is functionally similar to an MMF-300 but
offered in a smaller package for mounting directly in the electrical box of the device being
monitored.
Control Module
The CMF-300 is an addressable Control Module used to connect NACs (Notification
Appliance Circuits) to power and supervise compatible, UL-listed notification appliances.
The NACs can be wired to the module as supervised NFPA Style Y (Class B) or Style Z
(Class A) circuits. The modules are supplied with a thermoplastic cover for mounting to a
4-inch square mounting box.
Relay Module
The CRF-300 is a Control Relay Module which is functionally similar to the CMF-300 but
used as a Form-C relay module.
Isolator Module
The I300 loop isolator module is an automatic switch which opens the circuit voltage to
the SLC loop branch(es) whenever a wire-to-wire short circuit is detected on that loop.
The remainder of the communications loop leading up to the I300 will continue to operate,
unaffected by the short. The isolator module is bidirectional, meaning that it can detect a
fault condition between the input SLC terminals or output SLC terminals. The I300 is
required to meet NFPA Style 7 requirements.
Detector Annunciator
The RA400Z is a remote single LED annunciator that can be wired directly to an
addressable detector for annunciation of that detector’s alarm status.
Manual Pull Station
The ADT-BG-12LX is an addressable manual pull station featuring a key-lock reset. The
pull station responds to an address set by the installer using the built-in rotary decimal
switches on the pull station. The manual pull station includes an ADT key.

Unimode 9600 PN 51336:C

11/06/01

19

Product Description

Optional Modules

1.6.3 300 Series Intelligent Addressable Devices
ADT’s 300 Series Intelligent Addressable Devices are fully compatible with the Unimode
9600 FACP. The devices must be configured for CLIP Mode operation if the control panel
is installed in an existing system with 300 Series devices. The address of 300 Series
devices cannot be set above 99. Compatible devices include:
•
•
•
•
•
•
•
•

SD300 Photoelectric Detector
SD300T Photoelectric Detector with Thermal Sensor
CP300 Ionization Detector
M300 Monitor Module
M301 Miniature Monitor Module
M302 2-wire Monitor Module
C304 Control/Relay Module
ADT-BG-10LX Manual Pull Station

1.6.4 Addressable Device Accessories
End-of-Line Resistor Assembly P/N R-47K
The 47 kΩ End-of-Line Resistor assembly (P/N: R-47K) is used to supervise the MMF300, MDF-300, MMF-301 and CMF-300 module circuits. The 3.9 kΩ End-of-Line
Resistor assembly is used to supervise the MMF-302 module circuit. The resistors are
included with each module.
Power Supervision Relay
The UL listed End-of-Line power supervision relay is used to supervise the power to 4wire smoke detectors and notification appliances.
N-ELR Mounting Plate
The N-ELR is a single End-of-Line resistor plate which is required for use in Canada. An
ELR, which is supplied with each module and fire alarm control panel, is mounted to the
ELR plate. Resistors mounted to the N-ELR plate can be used for the supervision of a
monitor and control module circuit.

1.7 Optional Modules
The Unimode 9600 main circuit board includes option module connectors for the
following modules:
4XTMF Transmitter Module
The 4XTMF provides a supervised output for local energy municipal box transmitter,
alarm and trouble reverse polarity. It includes a disable switch and disable trouble LED.
A jumper on the module is used to select an option which allows the reverse polarity
circuit to open with a system trouble condition if no alarm condition exists. The module
plugs into connectors J10 and J11 which are located near the top center of the main circuit
board. When the 4XTMF module is installed, Jumper JP6, on the main circuit board, must
be cut to allow supervision of the module.
SLC-2 Expander Module
The SLC-2 Expander Module allows expansion of the Unimode 9600 from one SLC
circuit to two SLC circuits. The module plugs into connector J3 which is located in the
lower right corner of the main circuit board. The wiring for the second SLC connects to
terminals located on the expander module.

20

Unimode 9600 PN 51336:C

11/06/01

Accessories

Product Description

1.8 Accessories
1.8.1 PK-9600 Programming Utility
The PK-9600 Programming Utility can be used to program an Unimode 9600 directly
from most IBM compatible computers, including laptops and portables, equipped with a
serial port. Unimode 9600 program files can also be created and stored on the PC and then
downloaded to the control panel. The PK-9600 Kit includes the Windows-based
Programming Utility software on CD-ROM with on-line help file. A serial cable (P/N:
PRT/PK-CABLE), which must be purchased separately, is required for connection of the
PC to the RS-232 (PC/Printer) terminals at TB7 of the Unimode 9600 main circuit board.
Refer to the illustration on page 10 and the section titled "Printer/PC" on page 34, for the
location and connections to this terminal.

1.8.2 Dress Panel
A dress panel is provided standard with the Unimode 9600 (required for Canadian
installations). The dress panel restricts access to the system wiring while allowing access
to the key panel.
Note that the Unimode 9600 FACP, installed with the dress panel, has received Factory
Mutual (FM) approval. FM approval is contingent on the proper installation of the dress
panel.

CAUTION: HIGH VOLTAGE UNDER PANEL
!! WARNING !!

dp9600.cdr

SEVERAL DIFFERENT SOURCES OF POWER
CAN BE CONNECTED TO THIS CONTROL UNIT
DISCONNECT ALL SOURCES OF POWER BEFORE SERVICING

1.8.3 Battery Box
BB-17F

bb-17f.cdr

The BB-17F battery box may be used to house up to two 18 AH batteries in the event that
room is not available in the main cabinet due to the use of a ADT-UDACT, 411UD, etc.
The battery box mounts directly below the FACP cabinet. The battery box is red and is
provided with knockouts.

Unimode 9600 PN 51336:C

11/06/01

21

Product Description

Accessories
BB-55F

bb-55f.cdr

The BB-55F battery box may be used to house two 25 AH batteries, two 60 AH batteries
or one 100 AH battery. When the ADT-CHG-120 is mounted in the BB-55F, two 25 AH
or one 60 AH battery may also be housed in the battery box.

1.8.4 ADT-CHG-120 Battery Charger

Reference
Manual

The ADT-CHG-120 is capable of charging up to 120 AH lead-acid batteries with the
Unimode 9600 FACP. The FACP battery charger must be disabled when using the
ADT-CHG-120. The batteries and charger can be housed in the BB-55F battery box
which can be mounted up to 20 feet away from the control panel. Note that when using
the BB-55F for housing the charger and batteries greater than 25AH, multiple BB-55Fs
are required. Refer to the ADT-CHG-120 Manual for additional information.

1.8.5 Annunciators
ADT-ACS Series LED Zone Type Annunciators
The ADT-ACS Series Annunciators remotely display alarm and trouble status as well as
system status. In addition, they can provide remote Acknowledge, Silence, Reset and
Drill functions. For more detailed information, refer to the appropriate ADT-ACS
annunciator manual. Following is a list of annunciators which can be used with the
Unimode 9600.
Reference
Manual

•

•
•

•

•
•

•

22

ADT-ACM-16AT Annunciator Control Module annunciates 16 zones with 16 red
alarm LEDs and 16 yellow trouble LEDs. In addition, it has a System Trouble
LED, an On Line/Power LED and a local piezo sounder. It also has switches for
FACP Acknowledge, Silence, Reset and Drill. It has rotary address switches and
will accept up to three AEM-16AT Expanders
AEM-16AT Annunciator Expander Module annunciates 16 zones with 16 red alarm
LEDs and 16 yellow trouble LEDs
ADT-AFM-16AT Annunciator Fixed Module annunciates 16 zones with 16 red
alarm LEDs and 16 yellow trouble LEDs. In addition, it has a System Trouble
LED, an On Line/Power LED and a local piezo sounder. It also has switches for
FACP Acknowledge, Silence, Reset and Drill. It is fixed at address ‘1’
ADT-ACM-32A Annunciator Control Module annunciates 32 alarm zones with 32
red LEDs. In addition, it has a System Trouble LED, an On Line/Power LED and a
local piezo sounder. It also has a switch for local piezo silence. It has rotary
address switches and will accept one AEM-32A Expander
AEM-32A Annunciator Expander Module annunciates 32 alarm zones with 32 red
LEDs
ADT-AFM-16A Annunciator Fixed Module annunciates 16 alarm zones with 16
red alarm LEDs. In addition, it has a System Trouble LED, an On Line/Power LED
and a local piezo sounder. It also has a switch for local piezo silence. It is fixed at
address ‘1’
ADT-AFM-32A Annunciator Fixed Module annunciates 32 alarm zones with 32
red LEDs

Unimode 9600 PN 51336:C

11/06/01

Getting Started

Product Description
ADT-LCD-80F Remote Fire Annunciator
The ADT-LCD-80F annunciator is a compact 80-character backlit LCD remote fire
annunciator that is capable of displaying English language text. It mimics the display on
the control panel and will annunciate device type, point alarm, trouble or supervisory
condition, zone assignment plus any custom alpha labels programmed into the FACP. The
annunciator also provides system status LEDs to display AC Power, Alarm, Trouble,
Supervisory and Alarm Silenced conditions. Additionally, the ADT-LCD-80F is capable
of remotely performing critical system functions such as Acknowledge, Silence, Reset and
Drill.

Reference
Manual

Reference
Manual

Communications between the control panel and the annunciator is accomplished over a
serial interface employing the EIA-485 communication standard. Up to 32 ADT-LCD80F annunciators may be connected to the EIA-485 circuit. The annunciators may be
powered from the host FACP or a remote UL listed filtered power supply such as the
FCPS Series. For more detailed information, refer to the ADT-LCD-80F manual.
ADT-LDM Series Lamp Driver Modules (Graphic Annunciator)
The ADT-LDM Series Lamp Driver Modules, which consist of the ADT-LDM-32 master
and ADT-LDM-E32 expander modules, are used to provide an interface to a custom
graphic LED annunciator. The master module provides power and control for a maximum
of three expander modules. The ADT-LDM-32 and ADT-LDM-E32 have output
connectors which are used to drive lamps or LEDs and input connectors which are used
for remote switch functions. Refer to the ADT-LDM Series Lamp Driver Modules
manual for a complete description.

1.9 Getting Started
The following is a brief summary of the minimal steps involved in bringing an Unimode
9600 on-line:
•

Install Backbox and Main Circuit Board (refer to "Mounting" on page 24)

•

Address and Install Intelligent Devices (refer to the SLC Wiring Manual)

•

Enter Autoprogramming (refer to "Autoprogram" on page 87)

•

Resolve Programming Conflicts

Go to Point Program to Enter Specific Data (refer to "Point Program" on page 43). Use
the right and left arrow keys to navigate between devices.

Unimode 9600 PN 51336:C

11/06/01

23

Installation

Mounting

Installation

SECTION 2

The cabinet may be either semi-flush or surface mounted. The cabinet mounts using two
key slots and two 0.250” (6.35 mm) diameter holes located in the backbox. The key slots
are located at the top of the backbox and the two securing holes at the bottom.
Carefully unpack the system and check for shipping damage. Mount the cabinet in a
clean, dry, vibration-free area where extreme temperatures are not encountered. The area
should be readily accessible with sufficient room to easily install and maintain the panel.
Locate the top of the cabinet approximately 5 feet (1.5 m) above the floor with the hinge
mounting on the left. Determine the number of conductors required for the devices to be
installed. Sufficient knockouts are provided for wiring convenience. Select the
appropriate knockout(s) and pull the conductors into the box. All wiring should be in
accordance with the National and/or Local codes for fire alarm systems.

2.1 Mounting
!

See Page

The circuit board contains static-sensitive components. Always ground yourself with a
proper wrist strap before handling any boards so that static charges are removed from the
body. Use static suppressive packaging to protect electronic assemblies.
✓ Mark and predrill holes in the wall for the top two keyhole mounting bolts using
the dimensions illustrated in Figure 2.2 on page 25
✓ Install two upper fasteners in the wall with the screw heads protruding
✓ Using upper ‘keyholes,’ place backbox over the two screws, level and secure
✓ Mark and drill the lower two holes
✓ Mount backbox, install remaining fasteners and tighten
✓ Screw supplied standoffs onto mounting studs in locations indicated below
✓ When the location is dry and free of construction dust, install the main circuit
board by aligning the 10 mounting holes in the circuit board with the 10
mounting standoffs in the backbox as illustrated below
✓ Secure the circuit board to the standoffs with the supplied screws and male/
female standoff as indicated in following figure
Unimode 9600 Main Circuit Board

IMPORTANT!
Secure circuit board to this standoff
with supplied male/female standoff

TB3

TB5

TB4

TB6

TB7

TB8

JP3
CUT TO
DISABLE
LOCAL
CHARGER

JP5
4XTM OPT BD

JP11

JP10

J2
OPT DACT

OPT SLC

CUT TO
MONITOR 4XTM

J17

J16

JP6
J8

J6
LCD DISPLAY

TB1

TB2

SW1

KEYPAD I/F

J3
CB1

mounting studs

HOT NEUT EARTH

+BATTERY-

J7

96brdmnt.cdr

JP2

DISABLE
GND
FLT

mounting studs

Unimode 9600 Backbox

Figure 2.1 Unimode 9600 Main Circuit Board Installation

24

Unimode 9600 PN 51336:C

11/06/01

Mounting

Installation

1.75“

5.1 cm
2.00“

2.00“

2.00“

2.00“

2.00“

2.00“

4.45 cm
1.75“

1.50“ (3.81 cm)

3.79 cm
1.49“
4.1 cm
1.62“

15.5“ (39.37 cm)
1.62“ (4.11 cm)

3.81 cm
1.50“

12.00“ (30.48 cm)

4.1cm
1.62“

1.453“ (3.69 cm)

10.0“
25.4 cm
47.0cm
18.5“

4.45cm
1.75“

17.35 cm
6.83“

4.45cm
1.75“
4.1cm
1.583“
1.50“
3.81 cm

4.37“
11.1 cm

9600encl.cdr

11.1 cm
4.37“
1.50“ (3.81 cm)
1.75“
4.45 cm

Figure 2.2 Unimode 9600 Cabinet Mounting

Unimode 9600 PN 51336:C

11/06/01

25

Installation

Mounting

Depth = 4.37" (11.1 cm)

Top

Depth =
4.425"
(11.24 cm)

Door = 15.78" (40.08 cm)
Backbox = 15.5" (39.37 cm)

Door = 18.67" (47.43 cm)
Backbox = 18.5" (47.0 cm)

Left Side

Right Side
Bottom
18.620"
(47.3 cm)
Depth = 4.75"
(12.07 cm)

15.625"
(39.688 cm)

21.620"
(54.92 cm)

Battery Box = 8.5"
(21.59 cm)
9600cab.cdr

18.625"
(47.308 cm)

Trim Ring
P/N:FC-TR

Battery Box = 14.34" (36.42 cm)

Figure 2.3 Unimode 9600 Cabinet Dimensions

26

Unimode 9600 PN 51336:C

11/06/01

Power

Installation

2.2 Power
WARNING: Several different sources of power can be connected to this panel.
Disconnect all sources of power before servicing. The panel and associated equipment
may be damaged by removing and/or inserting cards, modules or interconnecting cables
while this unit is energized.

2.2.1 AC Power and Earth Ground Connection
LCD DISPLAY
Primary power required for the FACP is 120 VAC,
TB1
TB2
60 Hz, 3.2 amps. Overcurrent protection for this
circuit must comply with Article 760 of the National
Electrical Code (NEC) and/or local codes. Use 14
AWG (2.00 mm2) or larger wire with 600 volt
CB1 HOT NEUT EARTH +BATTERYinsulation rating. Make certain that the AC mains
circuit breaker is off before making any wiring
connections between the mains and the control panel. Connect the wiring from the AC
mains to TB1 on the FACP, being careful to observe proper connections.

Connect a wire from the grounding stud in the cabinet to a known solid earth ground. This
connection is vital for maintaining the control panel’s immunity to unwanted transients
generated by lightning and electrostatic discharge. Apply AC power to the panel only
after the system is completely installed and visually checked. Note that AC power must be
applied to the panel before installing the battery interconnect cable (refer to the following
section).

2.2.2 Battery Power
Interconnect Cable

+

See Page

Before connecting the batteries to the FACP, make
certain that the interconnect cable between the batteries
is not connected. Do not connect the interconnect cable
until the system is completely installed. Observe
polarity when connecting the batteries. Connect the
battery cable to TB2 on the main circuit board. Refer
"Power Supply Calculations" on page 127, for
calculation of the correct battery rating.

+

-

WARNING: Battery contains sulfuric acid which can cause severe burns to the skin and
eyes and can destroy fabrics. If contact is made with sulfuric acid, immediately flush the
skin or eyes with water for 15 minutes and seek immediate medical attention.

2.2.3 DC Power Output Connection
All DC power outputs are power-limited.
Power-limited Resettable Power
3.0 amperes max., 24 VDC nominal
filtered, resettable power can be drawn
from TB3 Terminals 1(+) and 2(-)

Power-limited Nonresettable Power #1
3.0 amperes max. , 24 VDC nominal
filtered, nonresettable power can be
drawn from TB3 Terminals 3(+) and 4(-)

Power-limited Nonresettable Power #2
3.0 amperes max. , 24 VDC nominal
filtered, nonresettable power can be
drawn from TB3 Terminals 5(+) and 6(-)

1 2 3 4 5 6

9600tb3.cdr

+ - + - + -

Figure 2.4 Power Outputs - 24 VDC

Unimode 9600 PN 51336:C

11/06/01

27

Installation

Relays

2.3 Relays
The FACP provides two programmable Form-C relays and one fixed fail-safe Form-C
trouble relay, all with contacts rated for 2.0 amps @ 30 VDC (resistive) or 0.5 amps @ 30
VAC (resistive). The Alarm and Supervisory silk-screen labels reflect the factory default
programming for the two programmable relays.
Note that relay connections may be power-limited or nonpower-limited, provided that
0.25” spacing is maintained between conductors of power-limited and nonpower-limited
circuits. Refer to UL Power-limited wiring requirements.
ALARM TROUBLE SUPV
RELAY RELAY
RELAY

Note that the relays labeled as Alarm
Relay (Relay 1) and Supervisory Relay
(Relay 3) reflect the factory default
programming for these relays which are
programmable.
The relay labeled Trouble Relay (Relay 2)
is fixed and cannot be changed. It is a failsafe relay which will transfer on any
trouble or total power failure.

NO NC C NC NO C NO NC C

9600reyp.cdr

TB5

Relay contacts shown with power applied to panel and
no active troubles, alarms or supervisories

Figure 2.5 Relay Terminals

2.4 Notification Appliance Circuits

See Page

Reference
Manual

The control panel provides two NAC (Notification Appliance Circuits) configurable for
Style Y/Class B or Style Z/Class A. Each circuit is capable of 3.0 amps of current. Total
system current cannot exceed 7.2 amps (refer to "Calculating the System Current Draw"
on page 128). Use UL listed 24 VDC notification appliances only. Circuits are supervised
and power-limited. Refer to the ADT Device Compatibility Document for a listing of
compatible notification appliances. The two NACs, which are located on the main circuit
board, may be expanded via the FCPS Series field charger/power supplies. Surge
protection for notification appliances may be provided by using one of the UL listed
compatible surge suppressors listed in the ADT Device Compatibility Document.
Style Y (Class B) Notification Appliance Circuit, supervised
and power-limited - 4.7 kohm, ½ watt P/N:71252 UL listed

Polarized Bell

+

Polarized Strobe
Polarized Horn

Notification Appliance Circuit
polarity shown in alarm state

TB4

1

+

2

3 4

5

+

Polarized Bell

+

Polarized Horn

+

Polarized Horn

6

7

8

Dummy Load all unused circuit

B+ A+ A- B- B+ A+ A- B-

Figure 2.6 NAC Connections

28

Unimode 9600 PN 51336:C

9600nac.cdr

Style Z (Class A) Notification Appliance Circuit,
supervised and power-limited

11/06/01

UL Power-limited Wiring Requirements

Installation

2.5 UL Power-limited Wiring Requirements
Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet.
All power-limited circuit wiring must remain at least 0.25” (6.35 mm) away from any
nonpower-limited circuit wiring and nonpower-limited circuit wiring must enter and exit
the cabinet through different knockouts and/or conduits. A typical wiring diagram for the
Unimode 9600 is shown below.

Powe
r-l i m

ited C

ircuit

s
Nonp
ower
-li
Circu mited
its

Powe
r

-limi
ted C
ir

cuits

4XTMF

To E
IA
24 V -485 and
DC p
ow
route
d beh er
i
board nd

AC
Nonp Power
ower
-limi
ted

To B
at

Powe
rCircu limited
its

SLC-2

teries
Nonp
ower
-li
Circu mited
its

ms-9600wireroute.cdr

ADT-UDACT

Powe
rCircu limited
its

Figure 2.7 Typical UL Power-limited Wiring Requirements

Unimode 9600 PN 51336:C

11/06/01

29

Installation

Optional Modules and Devices

2.6 Optional Modules and Devices
WARNING! Disconnect all sources of power (AC and DC) before installing or removing
any modules or wiring.
Unimode 9600 Keypad/Display Removal
Removal of the keypad/display is normally not necessary. If, however, it becomes
necessary to replace the keypad/display, access the auxiliary trouble bus connectors at J16
and J17 or install future option modules, the Keypad/Display can be removed by inserting
a Phillips screwdriver into each of the three holes located in the flexible covering of the
Keypad/Display and loosening the three mounting screws. Note that it is not necessary to
disconnect the cables between the Keypad/Display and the main circuit board unless the
unit itself is being replaced. Carefully lift the Keypad/Display and rest the unit at the
bottom of the main circuit board.
Mounting Screw Access Hole

TB3

TB4

TB5

TB6

TB7

TB8

JP3
CUT TO
DISABLE
LOCAL
CHARGER

JP6

JP5

4XTM OPT BD

JP10

MAINTENANCE

AC POWER
FIRE ALARM

ALARM
SILENCED

SUPERVISORY

DISABLED

TROUBLE

BATTERY
GROUND

JP2

5

DEF

6

JP7

EVENT

9 JP6

J168
TUV

PRS

*

0

TB1
-/.

QZ

ALARM

SILENCE
OPT DACT

OPT SLC

ENTER
DRILL

ESC

J8

J6

WXY

LCD DISPLAY

#

J2

CLR

CUT TO

JKLMONITORMNO
4XTM

GHI

J17
7

ACK/STEP

3 JP8 1st
ABC

MODE

TB2

KEYPAD I/F

JP4

HOLD 2 SEC

1
2

RESET3

J3

RECALL

CB1

HOT NEUT EARTH

J7

+BATTERY-

Mounting Screw Access Holes

Figure 2.8 Keypad/Display Removal

30

Unimode 9600 PN 51336:C

96dact1.cdr

2

1
DISABLE
GND
FLT
4

11/06/01

2SWLRQDO0RGXOHVDQG'HYLFHV

,QVWDOODWLRQ

2.6.1 4XTMF Transmitter Module Installation
The 4XTMF provides a supervised output for a local energy municipal box transmitter in
addition to alarm and trouble reverse polarity. A jumper option allows the reverse polarity
circuit to open with a system trouble condition if no alarm condition exists. A disable
switch allows disabling of the transmitter output during testing to prevent accidental
calling of the monitoring service.
Local Energy Municipal Box Service (NFPA 72 Auxiliary Fire Alarm Systems):
Supervisory Current: 5.0 mA
Trip Current: 350 mA (subtracted from notification appliance power)
Coil Voltage: 3.65 VDC
Maximum Coil Resistance: 14.6 ohms
Maximum allowable wire resistance between panel and trip coil: 3 ohms
Municipal Box wiring can leave the building
Remote Station Service (NFPA 72 Remote Station Fire Alarm Systems) - Intended
for connection to a polarity reversal circuit or a Remote Station receiving unit having
compatible ratings:
Maximum load for each circuit: 10 mA
Reverse polarity output voltage: 24 VDC
Remote Alarm and Remote Trouble wiring can leave the building
Before installing the module, place the disconnect switch to the right (disconnect) position
to prevent accidental activation of the municipal box. Note that a Disconnect LED will
illuminate after the module is installed in the Unimode 9600. In addition, the System
Trouble LED will turn on to indicate the Disconnect condition.
Note: 4XTMF Module is not suitable for
transmitting reverse polarity supervisory signal.

}Remote Alarm (power-limited)*
}Remote Trouble (power-limited)*

* Wiring from these
terminals can exit the
protected premises.
Dummy load terminals
No connection
6 and 7 (4.7kΩ, ¼ watt
resistor) if Municipal
Municipal Box (nonpower-limited)*
Box is not connected.

}
+ - +
1 2 3

4

5

+ 6 7

Polarities are shown for module activation

4xtmfl.cdr

Disconnect LED

Disconnect Switch
shown in disconnect
position

TBL Jumper

Connect to FACP J10 & J11

Figure 2.9 4XTMF Transmitter Module

8QLPRGH31&



,QVWDOODWLRQ

2SWLRQDO0RGXOHVDQG'HYLFHV
The following steps must be followed when installing the 4XTMF module:
1. Remove all power (AC and DC) from the FACP before installing 4XTMF
2. Cut jumper JP6 on the main circuit board to allow the control panel to supervise the
4XTMF module
3. Carefully plug the connectors on the 4XTMF module into connectors J10 and J11
on the Unimode 9600 main circuit board, being careful not to bend any pins
4. Secure 4XTMF module to standoffs with supplied screws.
5. Reapply power to the FACP
6. For proper 4XTMF operation, the output relays must be programmed for the factory
default settings as shown on the PC board silkscreen: Alarm Relay, Trouble Relay
and Supervisory Relay
7. When the installation has been complete, enable the 4XTMF module by sliding the
disconnect switch to the left
8. Test system for proper operation
Standoff

Standoff

TB3

TB4

TB5

TB6

TB7

JP3
JP5

CUT TO
MONITOR 4XTM

Cut Jumper JP6

JP6

4XTM OPT BD

J10 & J11 Connectors

J11

J10

4XTMF

J2
OPT DACT

J16

TB1

Unimode 9600

CB1

J8

J6
LCD DISPLAY

HOT NEUT EARTH

TB2

SW1

KEYPAD I/F

+BATTERY-

J7

9604xtm1.cdr

J17

Figure 2.10 4XTMF Connectors to Unimode 9600 Connectors
NOTE: Jumper JP5 on the Unimode 9600 main circuit board can be used to configure the FACP
supervisory relay for operation with the 4XTMF module. The supervisory relay must be
programmed as shown on the main circuit board silkscreen (TB5, Terminals 4, 5 & 6).
Cutting JP5 will allow the 4XTMF to generate a trouble if the supervisory contact opens
Leaving JP5 in will prevent generation of a trouble if the supervisory contact opens

2.6.2 Auxiliary Trouble Input (J16 & J17)
Auxiliary Trouble Inputs 1 (J17) and 2 (J16), which are located on the Unimode 9600
main circuit board, can be used to monitor for trouble conditions on auxiliary equipment
such as power supplies. J16 and/or J17 can be connected to any open collector trouble
output on the auxiliary equipment. The Unimode 9600 control panel will indicate a
trouble condition if a trouble is sensed at the Auxiliary Trouble Inputs.
If the 4XTMF Module is installed and jumper JP6 on the Unimode 9600 has been cut to
supervise it, Auxiliary Trouble Input 1 (J17) will monitor the 4XTMF for trouble
conditions.



8QLPRGH31&

2SWLRQDO0RGXOHVDQG'HYLFHV

,QVWDOODWLRQ

2.6.3 SLC-2 Expander Module

Reference
Manual

The optional SLC-2 Expander Module provides a second SLC loop for the Unimode 9600
control panel. This allows connection of an additional 318 addressable devices, bringing
the total to 636 addressable devices which can be connected to the FACP. Refer to the
SLC Manual for information on connecting devices to the SLC.
The following steps must be followed when installing the SLC-2 Expander Module:
1. Remove all power (AC and DC) from the FACP before installing the SLC-2 module
2. Carefully plug connector J3 on the SLC-2 module into connector J3 on the
Unimode 9600 main circuit board, being careful not to bend any pins
3. Secure the SLC-2 Expander Module to the four standoffs on the FACP main circuit
board with the supplied screws
4. Connect the SLC wiring and devices to TB8 on the SLC Expander Module. Refer
to the SLC Manual for wiring information
5. Reapply power to the control panel

See Page

6. Program the addressable devices connected to the SLC-2 Expander Module as
detailed in "Master Programming Level" on page 42
7. Test the system for proper operation
SLC Loop 1
Shield B
Shield A
SLC ASLC BSLC A+
SLC B+

SLC Loop 2
Shield B
Shield A
SLC ASLC BSLC A+
SLC B+

TB8

TB8

OPT SLC

J3

J3

SLC-2 Expander Module

96optslc.cdr

TB7

Unimode 9600

Figure 2.11 SLC-2 Expander Module Installation

8QLPRGH31&



,QVWDOODWLRQ

2SWLRQDO0RGXOHVDQG'HYLFHV

2.6.4 Printer/PC
A serial printer or a PC (personal computer) may be connected to TB7 Terminals 1 - 4 on
the FACP. The printer can be used to provide a hard-copy printout of real-time events,
history file and walktest data. An IBM compatible PC can be connected to provide local
FACP programming capabilities using the PK-9600 programming utility. Installation of
either device requires panel programming to allow the FACP to communicate with the
device.

!

CAUTION! Do not connect a printer or PC to the Unimode 9600 FACP if a ground fault
exists on the control panel. Circuit damage may result. Remove all power (AC and DC)
before installing or removing any wiring.
Installation
Remote printers and PCs require separate primary power. Also required is the PRT/
PK-CABLE which is an interface cable prewired to a DB9F connector. Wire the PRT/PKCABLE to TB7 Terminals 1 - 4 as illustrated in the following figure. Connect the DB9F
connector to the printer or PC serial EIA-232 port. If a nine-pin serial connector is not
available on the printer or PC, use a DB25 adapter. Make certain that the DB25 adapter
does not swap the Transmit and Receive lines. Apply power to the FACP and printer or
PC. Note that a ground fault may occur on the FACP, dependent on the printer or PC
being used, due to this connection. For this reason, it is important that there be no
preexisting ground fault on the panel.
Note that the printer may or may not be supervised as determined by user programming.
Refer to "Printer/PC" on page 92.

Red
5 4 3 2 1

White

9 8 7 6

Green
Black

PRT/PK-CABLE
TX
RCV
DTR
GRND
T
B
6

SLC

RS-232 PC/PRINTER
XMT RCV DTR GRND

T
B
7

SLC

B+ A+ B- A-

SHIELD

B

A

T
B
8

Figure 2.12 Serial Printer and Computer Connections

9600tb7a.cdr

ACS
1 COMM 2

Printer Configuration
Refer to the documentation supplied with the printer for pertinent information about
printer setup. Set the printer’s options as listed in the following table:
COMMUNICATION SETUP
BUFFER:
DATA BITS:
PARITY:
STOP BIT:
BAUD RATE:
AUTOMATIC LINE FEED
AUTOMATIC CARRIAGE RETURN

LARGE
7
EVEN
1 STOP
2400/4800/9600
NO
NO

PC Configuration
The Windows-based PK-9600 Programming Utility Kit contains CD-ROM with on-line
help file.



8QLPRGH31&

2SWLRQDO0RGXOHVDQG'HYLFHV

,QVWDOODWLRQ

2.6.5 Digital Communicator and Annunciators
2.6.5.1 ADT-UDACT Digital Alarm Communicator/Transmitter

Reference
Manual

See Page

7KH$'78'$&7WUDQVPLWVV\VWHPVWDWXVWR8/OLVWHG&HQWUDO6WDWLRQUHFHLYHUVYLD
WKHSXEOLFVZLWFKHGWHOHSKRQHQHWZRUN,WLVFDSDEOHRIUHSRUWLQJXSWRVRIWZDUH
]RQHVRUXSWRDGGUHVVDEOHSRLQWV7KH$'78'$&7FDQEHPRXQWHGUHPRWHO\LQ
D8%6)RU$'7$%65)HQFORVXUHRULQWKHSDQHOFDELQHWXVLQJWKH31%5.7
8QLYHUVDO%UDFNHWUHIHUWR$'78'$&70DQXDO7KH8QLPRGHLV
FRPSDWLEOHZLWK$'78'$&7VRIWZDUH8'$&7DQGDERYH
3URJUDPPLQJ
7KH8QLPRGHPXVWEHSURJUDPPHGWRRSHUDWHZLWKWKH$'78'$&75HIHUWR
$QQXQFLDWRUV8'$&7RQSDJHIRUFRQWUROSDQHOSURJUDPPLQJLQIRUPDWLRQ

2.6.5.2 ADT-ACM-8R Relay Control Module

Reference
Manual

7KH$'7$&05PRGXOHSURYLGHVHLJKW)RUP&UHOD\VZLWKFRQWDFWVUDWHGIRU
DPSV:KHQLQVWDOOHGZLWKDQ8QLPRGH)$&3WKH$'7$&05PRGXOHV
SURYLGHUHOD\DFWLYDWLRQIRUHDFKRIWKHSRVVLEOH)$&3]RQHVSOXVVSHFLDOIXQFWLRQV
2SWLRQVH[LVWWRDOORZIRUDODUPRQO\RUDODUPDQGWURXEOHDFWLYDWLRQSHU]RQH2XWSXW
DFWLYDWLRQIRUJHQHUDODODUPJHQHUDOWURXEOHJHQHUDOVXSHUYLVRU\1$&IDXOW$&IDLO
ZDONWHVWVWDUWDQGEDWWHU\WURXEOHDUHDOVRDYDLODEOH7KH$'7$&05FDQEH
PRXQWHGUHPRWHO\LQDQ$'7$%65)DQQXQFLDWRUVXUIDFHPRXQWEDFNER[RULQWKH
SDQHOFDELQHWXVLQJWKH31%5.78QLYHUVDO%UDFNHW5HIHUWRWKH$'7$&0
5PDQXDOIRULQIRUPDWLRQRQVHWWLQJPRGXOHVZLWFKHVIRUDGGUHVVLQJDQGUHOD\
IXQFWLRQV

2.6.5.3 BRKT-9600 Universal Bracket Installation
7KHRSWLRQDO%5.78QLYHUVDO%UDFNHWFDQEHXVHGWRPRXQWVSHFLILFPRGXOHV
LQVLGHWKH8QLPRGHFDELQHW7KH%5.7PRXQWVWRWZRVWXGVORFDWHGLQWKH
ORZHUULJKWFRUQHURIWKHFRQWUROSDQHOFDELQHWDVLOOXVWUDWHGEHORZ,WLVVHFXUHGWRWKH
3(0VWXGVRQWKHEDFNZDOORIWKHFDELQHWZLWKWZRVXSSOLHGKH[QXWV
,03257$17:KHQWKH%5.7LVLQVWDOOHGWKH8QLPRGHFDELQHWFDQ
KROGDPD[LPXPRIWZR$PS+RXUEDWWHULHVZLWKWKHRULHQWDWLRQLOOXVWUDWHGEHORZ

TB3

TB5

TB4

TB6

TB7

TB8

JP3
CUT TO
DISABLE
LOCAL
CHARGER

JP5
4XTM OPT BD

JP11

JP10

AC POWER

MAINTENANCE

FIRE ALARM

ALARM
SILENCED

SUPERVISORY

DISABLED
BATTERY

TROUBLE

GROUND

JP2
DISABLE
GND
FLT
4

DEF

AB C

5

6

JP7

EVENT

9 JP6

J168
TUV

PRS

OPT SLC

DRILL

J8

J6

WXY

TB1

ALARM

SILENCE
OPT DACT
ENTER

ESC

LCD DISPLAY MO DE
#

0

*

J2

CLR

CUT TO
MNO
MONITOR 4XTM

JKL

GHI

J17
7

ACK/STEP

3 JP8 1st

TB2

KEYPAD I/F

JP4

HOLD 2 SEC

1
2

RESET3

-/.

QZ

J3

RECALL

CB1

HOT NEUT EARTH

+BATTERY-

J7

J12

Mount BRKT-9600 to PEM
studs on back of cabinet
using supplied hex nuts.

Unimode 9600 Cabinet

96brkmnt.cdr

2

1

Figure 2.13 BRKT-9600 Bracket Installation

8QLPRGH31&



,QVWDOODWLRQ

2SWLRQDO0RGXOHVDQG'HYLFHV
0RGXOH,QVWDOODWLRQRQ%5.7
7KHIROORZLQJPRGXOHVFDQEHLQVWDOOHGLQVLGHWKH8QLPRGHFDELQHWXVLQJWKH
%5.78QLYHUVDO%UDFNHW
✓ ADT-UDACT Digital Alarm Communicator/Transmitter - installs at standoff
location (A)
✓ ADT-ACM-8R Annunciator Control Module (Relay) - installs at standoff
location (A)
5HIHUWRWKHDSSURSULDWHPRGXOHPDQXDOIRUGHWDLOHGLQIRUPDWLRQRQPRGXOHRSHUDWLRQ
DQGZLULQJ
1. Install the two supplied standoffs in location (A) as indicated in Step 1 of the
following illustration
2. Position the module bottom in the slot located in the bottom of the BRKT-9600 as
indicated in Step 2 of the following illustration
3. Secure the module to the standoffs installed in the top of the BRKT-9600 with two
mounting screws as indicated in Step 3 of the following illustration
4. Refer to the appropriate module manual for detailed information on wiring the
module for power, communication, etc.
5. Install a maximum of two 12 Amp Hour batteries with the orientation illustrated in
Figure 2.13. Larger batteries require a separate UL listed battery box
1RWH'RQRWEULQJZLULQJRUFRQGXLWLQWRWKHERWWRPRIWKHFDELQHWIRUWKLV
DSSOLFDWLRQ

BRKT-9600

BRKT-9600
(A)

(A)

BRKT-9600
standoffs
mounting
screws

Step 1

module

96brcksd.cdr

9600brkt.cdr

module

Slot
Step 2

Step 3

Figure 2.14 BRKT-9600 Module Installation Steps



8QLPRGH31&

2SWLRQDO0RGXOHVDQG'HYLFHV

,QVWDOODWLRQ

2.6.5.4 ADT-ACS and ADT-AFM Series Annunciators
$'7$&6DQG$'7$)06HULHV$QQXQFLDWRUVSURYLGHYLVXDOLQGLFDWLRQVRI)$&3
VWDWXVLQUHPRWHORFDWLRQV5HIHUWRWKHDSSURSULDWHDQQXQFLDWRUPDQXDOIRU
LQIRUPDWLRQRQLQVWDOODWLRQZLULQJDQGRSHUDWLRQ
$'7$&6DQQXQFLDWRUDGGUHVVLQJLVVSHFLILFWRWKH8QLPRGHFRQWUROSDQHO7KH
IROORZLQJWDEOHGHVFULEHVWKH$'7$&6DQQXQFLDWRUDGGUHVVHVDQGWKHFRUUHVSRQGLQJ
DGGUHVVDEOHGHYLFHVWKDWZLOOEHDQQXQFLDWHGDWHDFKDQQXQFLDWRUDGGUHVV
ADT-ACS Annunciator Address
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32

Annunciator Displays the Following Points
8 General System Status Points & Zones 1 - 56
Zones 57 - 99 & 2 NACs
Loop 1, Module Addresses 1 - 64
Loop 2, Module Addresses 1 - 64
Loop 1, Module Addresses 65 - 128
Loop 2, Module Addresses 65 - 128
Loop 1, Module Addresses 129 - 159 & Loop 2 Module Addresses 129 - 159
Loop 1, Detector Addresses 1 - 64
Loop 2, Detector Addresses 1 - 64
Loop 1, Detector Addresses 65 - 128
Loop 2, Detector Addresses 65 - 128
Loop 1 Detector Addresses 129 - 159 & Loop 2 Detector Addresses 129 - 159
not used
not used
not used
not used
not used
not used
not used
8 General System Status Points & Zones 1 - 56
Zones 57 - 99 & 2 NACs
Loop 1, Module Addresses 1 - 64
Loop 2, Module Addresses 1 - 64
Loop 1, Module Addresses 65 - 128
Loop 2, Module Addresses 65 - 128
Loop 1, Module Addresses 129 - 159 & Loop 2 Module Addresses 129 - 159
Loop 1, Detector Addresses 1 - 64
Loop 2, Detector Addresses 1 - 64
Loop 1, Detector Addresses 65 - 128
Loop 2, Detector Addresses 65 - 128
Loop 1 Detector Addresses 129 - 159 & Loop 2 Detector Addresses 129 - 159
not used

,PSRUWDQW,ID$'78'$&7LVLQVWDOOHGLQWKH8QLPRGHDQGVHOHFWHGLQ
SURJUDPPLQJWKHFRQWUROSDQHOZLOODXWRPDWLFDOO\DVVLJQDQQXQFLDWRUDGGUHVVHV
WRWKH$'78'$&7DQGGLVDEOHWKHVHOHFWLRQRIWKHVHDGGUHVVHVLQSURJUDPPLQJIRU
$'7$&6DQQXQFLDWRUV'RQRWVHWDQ\$'7$&6DQQXQFLDWRUVWRWKHVHDGGUHVVHV
7KH8QLPRGHPXVWEHSURJUDPPHGIRUWKHDQQXQFLDWRUVLQVWDOOHGRQWKHV\VWHP
5HIHUWR$QQXQFLDWRUV8'$&7RQSDJHIRULQIRUPDWLRQRQ$'78'$&7DQG
DQQXQFLDWRUSURJUDPPLQJ0DNHFHUWDLQWRSURJUDPWKHDQQXQFLDWRUDGGUHVVHVWKDW
KDYHEHHQSK\VLFDOO\LQVWDOOHGRQWKHV\VWHP
1RWH7KH*HQHUDO6\VWHP6WDWXV3RLQWVLQFOXGHWKHIROORZLQJ
•
•
•
•
•
•
•
•

8QLPRGH31&

General Alarm
General Trouble
General Supervisory
Alarm Silenced
System Off Normal
AC Loss
Battery Fault
NAC Fault



3URJUDPPLQJ

SECTION 3

3URJUDPPLQJ'DWD(QWU\

Programming

3.1 Programming Data Entry
Programming can be accomplished using the Unimode 9600 keypad or by connecting an
optional standard computer keyboard. The keyboard can be connected to the PS-2
connector J7 on the control panel main circuit board.
The information presented in this section refers to programming the Unimode 9600 via the
onboard keypad. If an optional computer keyboard is connected to the Unimode 9600
main circuit board, the following table describes the keyboard keys which correspond to
the onboard keypad keys.
Keypad Keys

Computer Keyboard Keys

1st Event

Home

CLR

Delete

ESC

Esc

RECALL

Insert

*

*

#

#

A-Z

A-Z

0-9

0-9
(on QZ key)

Space bar

—

—

/

/

•

•

ENTER

Enter

Note: The main keypad function keys (ACK/STEP, ALARM SILENCE, DRILL and RESET)
are not available on the keyboard.



8QLPRGH31&

8VHU3URJUDPPLQJ

3URJUDPPLQJ

3.2 User Programming
!!

The Unimode 9600 is completely field programmable and requires no special software
skills. While programming the Unimode 9600, the fire protection capabilities of the
control panel are enabled.
Site-specific programming may be accomplished in three ways:
•

Autoprogramming Feature - This is a convenient method for quickly bringing the
FACP addressable SLC devices on-line without the necessity of programming each
device individually. Refer to "Autoprogram" on page 87 for a detailed description
of Autoprogramming

•

Manual programming or editing, using the FACP keypad or a PC keyboard

•

Off-line Programming and Editing Feature - allows creation and editing of sitespecific custom programs using a Windows-based computer. For programs
requiring a large amount of data entry, this method may be preferred. A PK-9600
programming kit can be ordered for this purpose

The System All Normal screen will be displayed in a programmed system with no active
alarms, troubles or supervisories, as illustrated below:

SYSTEM@ALL@NORMAL
10:00A@010801
Programming and Read Status mode can be entered while the panel is in any mode of
operation. If the panel is in alarm, the alarm condition must be acknowledged before
entering other modes. To access any of the programming or read status features, the Enter
or Mode key must be pressed, which will cause the LCD to display the following:

1=READ@STATUS
2=PROGRAMMING

See Page

Pressing 1, while this screen is being displayed, will cause the control panel to enter the
Read Status feature which allows the user to view the programmed features and status of
the control panel The Read Status feature is not password protected. Refer to "Read
Status" on page 117 for a detailed description of this feature.
Pressing 2 will select user Programming which may only be accomplished by an
authorized person. After pressing 2, a screen will prompt for a password. After entering
the correct password, the user may select from a list of programming options.
Exit Programming or Read Status
The programmer can exit Read Status or Programming mode by repeatedly pressing the
keypad ESC (Escape) key until the display reads System All Normal. Note that the data
which is entered during Programming mode is not saved until the programmer exits this
mode by repeatedly pressing the ‘ESC’ key. If the Reset key is pressed or power is lost
before exiting Programming mode, all data which was just entered will be lost.

8QLPRGH31&



3URJUDPPLQJ

,QLWLDO3RZHUXS
User Programming Levels
There are two user programming levels:
•

User Master Program Level 1 is used for programming panel specific data relating
to device types, zoning, messages, control panel functions, etc.

•

User Maintenance Program Level 2 is used by a qualified operator to access
features such as Disable/Enable, View and Clear History, Walktest and System
Time Change.

3.3 Initial Power-up
The following sections describe the initial programming procedures for a new system.
The same procedures are used to modify programming in an existing system.
After completing the wiring of addressable devices to the SLC, apply power to the control
panel. If the addressable devices have not yet been programmed into the FACP, their
LEDs will not flash and the following trouble message will be displayed.

TROUBL@IN@SYSTEM
NO@DEVICES@INSTALLED
09:03A@010801

3.4 Programming Screens Description

See Page

Two main options are available when the Enter key is pressed: Read Status and
Programming. Each option has multiple functions or features which may be chosen. To
view all of the choices, it is necessary that the programmer scroll through a number of
additional subscreens. These selections are displayed on multiple screens to make them
more readable for the programmer. Refer to "Master Programming Level" on page 42, for
additional information on the various screens.
The title of the main option screen will always be displayed at the top of the subscreens for
the programmer’s convenience. If additional subscreens exist, an Up or Down arrow will
be displayed in the upper right corner of the screen being viewed. The programmer can
then press the keypad Up or Down arrow key to view the new subscreen. To select one of
the choices in a screen, the programmer presses the keypad numerical key corresponding
to the desired choice.
Note that subscreens may also have multiple options which require viewing more than one
screen. The same process, as detailed in the previous paragraphs, is followed to view all
option choices.

3.5 Programming and Passwords

See Page



There are two factory set programming passwords which will access the Programming
screens as indicated in the following examples. From either of the screens, access to
specific system and device features or programming may be obtained. All user
programming entries are stored in nonvolatile memory. The factory set passwords can be
changed by the user as described in "Password Change" on page 93. If an invalid
password is entered, the blinking cursor will return to the first password character
position. To exit Programming or Read Status mode at any time, press the ESC (Escape)
key repeatedly. Note that Programming mode must be exited using the ESC key in order
to store the program data entered during this mode. If the Reset key is pressed or power is
lost before exiting Programming mode, the data just entered will not be saved.

8QLPRGH31&

3URJUDPPLQJDQG3DVVZRUGV

3URJUDPPLQJ

To access user Programming mode, press the Enter or Mode key. The LCD will display
the following:

1=READ@STATUS
2=PROGRAMMING

To enter the user Programming mode, press 2. The display will read as follows:

PROGRAMMING
ENTER@PASSWORD
*****

Entering the Master level password (default 00000) will cause the following screen to
appear:

@@@@PROGRAMMING
1=POINT@PROGRAM
2=ZONE@SETUP
3=LOOP@SETUP

If the Maintenance level password (default 11111) is entered, the following screen will
appear:

@@@@PROGRAMMING
1=POINT PROGRAM
2=HISTORY
3=PROGRAM CHECK

Note that in the two preceding screens, an arrow appears to inform the programmer that
additional options can be viewed by pressing the keypad down arrow key.

8QLPRGH31&



3URJUDPPLQJ

0DVWHU3URJUDPPLQJ/HYHO

3.6 Master Programming Level
When the Master Program Level password is entered, the control panel will enter user
Programming mode. In this mode, the piezo sounder remains off, the trouble relay is
activated and the system Trouble LED flashes until Programming mode is exited. The
following display will appear:

@@@@PROGRAMMING
1=POINT@PROGRAM
2=ZONE@SETUP
3=LOOP@SETUP
Programming Screen #1
The down arrow which appears in the display indicates that additional programming
choices can be viewed by pressing the down arrow key on the keypad. If a down and up
arrow appear in the display, pressing the ‘down’ arrow key will display the subsequent
Programming Screens as illustrated below while pressing the ‘up’ arrow key will display
the previous screen.

@@@@PROGRAMMING
1=SYSTEM@SETUP
2=AUTOPROGRAM
3=VERIFY@LOOPS
Programming Screen #2

@@@@PROGRAMMING
1=HISTORY
2=WALKTEST
3=OPTION@MODULES
Programming Screen #3

@@@@PROGRAMMING
1=PASSWORD@CHANGE
2=CLEAR@PROGRAM
3=PROGRAM@CHECK
Programming Screen #4



8QLPRGH31&

0DVWHU3URJUDPPLQJ/HYHO

3URJUDPPLQJ

3.6.1 Point Program
PROGRAMMING
1=POINT PROGRAM
2=ZONE SETUP
3=LOOP SETUP

Programming Screen #1

The Point Program option allows the programmer to add a new addressable device to an
SLC loop, delete an existing device from a loop or change the programming for an
existing device. Pressing 1, while viewing Programming Screen #1, will select the Point
Program option and display the following screen:

@@@POINT@PROGRAM
@@@@SELECT@LOOP
1=LOOP@1
2=LOOP@2
Point Program Screen #1
The programmer selects the desired SLC loop by pressing 1 or 2 in Point Program Screen
#1, which causes the panel to display the following screen:

@@@POINT@PROGRAM
@@@@SELECT@TYPE
1=DETECTOR
2=MODULE
Point Program Screen #2

3.6.1.1 Detector Programming
3UHVVLQJZKLOHYLHZLQJ3RLQW3URJUDP6FUHHQZLOODOORZWKHSURJUDPPHUWRDGG
GHOHWHRUFKDQJHWKHSURJUDPPLQJRIDQDGGUHVVDEOHGHWHFWRU7KHIROORZLQJVFUHHQ
ZLOOEHGLVSOD\HGE\WKHFRQWUROSDQHO

@@@@@@DETECTOR
1=ADD
2=DELETE
3=EDIT
Detector Screen
3.6.1.1.1 Add Detector
3UHVVLQJZKLOHYLHZLQJWKH'HWHFWRU6FUHHQZLOOGLVSOD\WKHIROORZLQJVFUHHQZKLFK
DOORZVWKHSURJUDPPHUWRDGGDQHZGHWHFWRUDGGUHVVWRSURJUDPPLQJ

@@@@ADD@DETECTOR
ENTER@DETECTOR#
***
Add Detector Screen
$IODVKLQJFXUVRUZLOODSSHDULQWKHSRVLWLRQRIWKHILUVWDVWHULVNWRWKHOHIW7KH
SURJUDPPHUNH\VLQWKHWKUHHGLJLWGHWHFWRUDGGUHVVVXFKDV

8QLPRGH31&



3URJUDPPLQJ

0DVWHU3URJUDPPLQJ/HYHO
:KHQWKHODVWGLJLWLVNH\HGLQWKHIROORZLQJVFUHHQZLOOEHGLVSOD\HG

@@@@ADD@DETECTOR
DETECTOR#@@@@@@@005
IS@ADDED

7KHSURJUDPPHUFDQFRQWLQXHDGGLQJGHWHFWRUVE\SUHVVLQJWKH(6&RUOHIWDUURZNH\
ZKLFKZLOOUHWXUQWKHGLVSOD\WRWKH$GG'HWHFWRU6FUHHQ
DETECTOR
1=ADD
2=DELETE
3=EDIT

Detector Screen

3.6.1.1.2 Delete Detector
3UHVVLQJLQWKH'HWHFWRU6FUHHQZLOOGLVSOD\WKH'HOHWH'HWHFWRU6FUHHQZKLFKDOORZV
WKHSURJUDPPHUWRGHOHWHDVSHFLILFGHWHFWRU

@@DELETE@DETECTOR
ENTER@DETECTOR#
***
Delete Detector Screen
$IODVKLQJFXUVRUZLOODSSHDULQWKHSRVLWLRQRIWKHILUVWDVWHULVNWRWKHOHIW7KH
SURJUDPPHUNH\VLQWKHWKUHHGLJLWGHWHFWRUDGGUHVVVXFKDV:KHQWKHODVWGLJLW
LVNH\HGLQWKHIROORZLQJVFUHHQZLOOEHGLVSOD\HG

@@DELETE@DETECTOR
DETECTOR#@@@@@@@005
IS@DELETED

7KHSURJUDPPHUFDQFRQWLQXHGHOHWLQJGHWHFWRUVE\SUHVVLQJWKH(6&RUOHIWDUURZNH\
ZKLFKZLOOUHWXUQWKHGLVSOD\WRWKH'HOHWH'HWHFWRU6FUHHQ
3.6.1.1.3 Edit Detector
TKHSURJUDPPHUFDQFKDQJHDGHWHFWRUVH[LVWLQJRUIDFWRU\GHIDXOWSURJUDPPLQJE\
SUHVVLQJLQWKH'HWHFWRU6FUHHQ7KHIROORZLQJVFUHHQZLOOEHGLVSOD\HG

@@EDIT@DETECTOR
ENTER@POINT@ADDRESS
***
Edit Detector Screen

$IODVKLQJFXUVRUZLOODSSHDULQWKHSRVLWLRQRIWKHILUVWDVWHULVNWRWKHOHIW7KH
SURJUDPPHUNH\VLQWKHWKUHHGLJLWGHWHFWRUDGGUHVVVXFKDV



8QLPRGH31&

0DVWHU3URJUDPPLQJ/HYHO

3URJUDPPLQJ
:KHQWKHODVWGLJLWLVNH\HGLQLIWKHVHOHFWHGDGGUHVVKDVQRWEHHQDGGHGWR
SURJUDPPLQJDVFUHHQVKRZLQJLQIRUPDWLRQDERXWDGHYLFHZLWKWKHKLJKHVWDGGUHVV
WKDWLVLQVWDOOHGZLOOEHGLVSOD\HG
,IQRGHWHFWRUVKDYHEHHQLQVWDOOHGRQWKHORRSWKHIROORZLQJZLOOEHGLVSOD\HG

@@@@NO@DETECTOR
@@@@@INSTALLED

Edit Detector Screen #1
,IWKHVHOHFWHGDGGUHVVKDVEHHQDGGHGWRSURJUDPPLQJGHYLFHVXPPDU\VFUHHQVZLOO
EHGLVSOD\HG7KHVHVFUHHQVDOORZWKHSURJUDPPHUWRYLHZDOOGHYLFHVHWWLQJVDWD
VLQJOHJODQFH3UHVVLQJWKHOHIWRUULJKWDUURZNH\VZLOODOORZWKHSURJUDPPHUWR
UDSLGO\YLHZWKHGHYLFHVDWWKHSUHYLRXVRUQH[WDGGUHVVLILQVWDOOHG
,IDGHWHFWRUVXFKDVDSKRWRHOHFWULFGHWHFWRUZLWKWKHVHOHFWHGDGGUHVVLVQRW
SK\VLFDOO\LQVWDOOHGRQWKH6/&RUKDVDFRPPXQLFDWLRQIDXOWEXWWKHDGGUHVVLV
SURJUDPPHGLQWKHV\VWHPWKHIROORZLQJVFUHHQZLOOEHGLVSOD\HG

@TROUBL@SMOKE(PHOTO)
@********************
@@@@@@@@@@@@@@@ZNNN
@@@@@@@@@@@*@@@@1D017
Edit Detector Screen #1
,IWKHVHOHFWHGDGGUHVVKDVEHHQDGGHGWRSURJUDPPLQJDQGDGHWHFWRUVXFKDVD
SKRWRHOHFWULFGHWHFWRUZLWKWKHVHOHFWHGDGGUHVVLVSK\VLFDOO\LQVWDOOHGRQWKH6/&DQG
LVFRPPXQLFDWLQJZLWKWKHFRQWUROSDQHOWKHIROORZLQJZLOOEHGLVSOD\HG

@NORMAL@SMOKE@(PHOTO)
@*********************
@@@@@@@@@@@@@@@@ZNNN
@@@@@@@@@@@@@V@@@1D017
Edit Detector Screen #1
7RFKDQJHWKHSURJUDPPLQJIRUWKHGLVSOD\HGGHWHFWRUSUHVVWKHNH\ERDUGµGRZQ¶
DUURZNH\WRYLHZWKH(GLW'HWHFWRUVFUHHQV
,QWKHSUHFHGLQJH[DPSOH
✓ Normal - indicates that the detector with the selected address is physically
installed on the SLC and communicating with the control panel (enabled)
✓  - represents the adjective and noun, which have been
programmed, describing the location of the displayed device
✓ ZNNN - represents the first of five possible software zones that the detector is
assigned to (NNN = the three digit zone number from 000 - 099)
✓ V or * - indicates whether or not alarm verification is enabled (V = alarm
verification enabled and * = alarm verification disabled)
✓ 1D017 - represents the Loop, Device type and Device address (1 = SLC Loop 1,
D=Detector and 017 = Detector Address 017)

8QLPRGH31&



3URJUDPPLQJ

0DVWHU3URJUDPPLQJ/HYHO
7KHIROORZLQJH[DPSOHVVKRZWKHHGLWLQJRIDSKRWRHOHFWULFsmoke detector with
address 017, located on the first SLC loop:

EDIT@DETECTOR@1D017
1=ENABLED@@@@@@@@YES
2=TYPE@@SMOKE(PHOTO)
3=VERIFICATION@@@OFF
Edit Detector Screen #2

EDIT@DETECTOR@1D017
1=WALKTEST@@@@@@@@NO
2=PAS@@@@@@@@@@@@@NO
3=PRE-SIGNAL@@@@@@NO
Edit Detector Screen #3

EDIT@DETECTOR@1D017
1=ZONE@ASSIGNMENT
@@@@00@**@**@**@**
Edit Detector Screen #4

EDIT@DETECTOR@1D017
1=NOUN/ADJECTIVE
2=DESCRIPTION
********************
Edit Detector Screen #5

(QDEOH'LVDEOH'HWHFWRU
EDIT DETECTOR
1=ENABLED
2=TYPE
3=VERIFICATION

Edit Detector Screen #2



7R(QDEOHRU'LVDEOHWKHGHWHFWRUSUHVVWKHNH\ZKLOHYLHZLQJWKH(GLW'HWHFWRU
6FUHHQ(DFKSUHVVRIWKHNH\ZLOOWRJJOHWKHVFUHHQEHWZHHQ(QDEOHG
@@@@@@@@@@@@@@@@ZNNN
@@@@@@@@@@@@@@@1M012
,IWKHVHOHFWHGDGGUHVVKDVEHHQDGGHGWRSURJUDPPLQJDQGDPRGXOHVXFKDVD
PRQLWRUPRGXOHZLWKWKHVHOHFWHGDGGUHVVLVSK\VLFDOO\LQVWDOOHGRQWKH6/&DQGLV
FRPPXQLFDWLQJZLWKWKHFRQWUROSDQHOWKHIROORZLQJVFUHHQZLOOEHGLVSOD\HG

@NORMAL@MONITOR
@@@@@@@
@@@@@@@@@@@@@@@@@ZNNN
@@@@@@@@@@@@@@@@1M012
7RFKDQJHWKHSURJUDPPLQJIRUWKHGLVSOD\HGPRGXOHSUHVVWKHNH\ERDUGGRZQDUURZ
NH\WRYLHZWKHIROORZLQJ(GLW0RQLWRUVFUHHQV,QWKHSUHFHGLQJH[DPSOH
✓ Normal - indicates that the module with the selected address is physically
installed on the SLC and communicating with the control panel (enabled)
✓  - represents the adjective and noun, which have been
programmed, describing the location of the displayed device
✓ ZNNN - represents the first of five possible software zones that the module is
assigned to (NNN = the two digit zone number from 000 - 099)
✓ 1M012 - represents the Loop, Device type and Device address (1 = SLC Loop 1,
M=Module and 012 = Module Address 012)

See Page

,IWKHVHOHFWHGDGGUHVVFRUUHVSRQGVWRDFRQWUROPRGXOHDVFUHHQGLVSOD\LQJ
LQIRUPDWLRQDERXWWKHFRQWUROPRGXOHZLWKWKHVHOHFWHGDGGUHVVZLOOEHGLVSOD\HGDV
VKRZQLQ(GLW0RGXOH6FUHHQIRU&RQWURO0RGXOHVRQSDJH

8QLPRGH31&



3URJUDPPLQJ

0DVWHU3URJUDPPLQJ/HYHO
,IWKHVHOHFWHGDGGUHVVFRUUHVSRQGVWRDPRQLWRUPRGXOHDVFUHHQGLVSOD\LQJ
LQIRUPDWLRQDERXWWKHPRGXOHZLWKWKHVHOHFWHGDGGUHVVZLOOEHGLVSOD\HGDVLOOXVWUDWHG
LQWKHIROORZLQJ

@NORMAL@MONITOR
@@@@@@
@@@@@@@@@@@@@@@@@ZNNN
@@@@@@@@@@@@@@@@1M012


EDIT@MONITOR@@1M012
1=ENABLED@@@@@@@@YES
2=TYPE@@MONITOR
Edit Monitor Screen #2

EDIT@MONITOR@@1M012
1=PRE-SIGNAL@@@@@@NO
2=PAS@@@@@@@@@@@@@NO
Edit Monitor Screen #3

EDIT@MONITOR@@1M012
1=WALKTEST@@@@@@@YES
2=ZONE@ASSIGNMENT
00@**@**@**@**
Edit Monitor Screen #4

EDIT@MONITOR@@1M012
1=ADJECTIVE/NOUN
2=DESCRIPTION
********************
Edit Monitor Screen #5



8QLPRGH31&

0DVWHU3URJUDPPLQJ/HYHO

3URJUDPPLQJ
(QDEOH'LVDEOH0RGXOH
7R(QDEOHRU'LVDEOHWKHPRQLWRUPRGXOHSUHVVWKHNH\ZKLOHYLHZLQJWKH(GLW
0RGXOH6FUHHQ(DFKSUHVVRIWKHNH\ZLOOWRJJOHWKHVFUHHQEHWZHHQ(QDEOHG
@@@@@@@@@@SW@@ZNNN
@@@@@@@@@@@@@@1M002
Edit Control Screen #1
,QWKHSUHFHGLQJH[DPSOH
✓ Normal - indicates that the module with the selected address is physically
installed on the SLC and communicating with the control panel (enabled)
✓  - represents the adjective and noun, which have been
programmed, describing the location of the displayed device
✓ Control - indicates that the selected module is a control module
✓ S or * - represents Silenceable (S) or Nonsilenceable (*)
✓ W or * - represents Waterflow Timer Delay (W = Waterflow Timer Delay
enabled, * = Waterflow Timer Delay disabled)
✓ ZNNN - represents the first of five possible software zones that the module is
assigned to (NNN = the three digit zone number from 000 - 099)
✓ 1M002 - represents the Loop, Device type and Device address (1 = SLC Loop 1,
M=Module and 002 = Module Address 02)

8QLPRGH31&



3URJUDPPLQJ

0DVWHU3URJUDPPLQJ/HYHO
7RFKDQJHWKHSURJUDPPLQJIRUWKHGLVSOD\HGPRGXOHSUHVVWKHNH\ERDUGGRZQDUURZ
NH\WRYLHZWKHIROORZLQJ(GLW&RQWUROVFUHHQV

EDIT@CONTROL
1=ENABLED@@@@@@@@YES
2=TYPE@@CONTROL
3=SILENCEABLE@@@@YES
Edit Control Screen #2

EDIT@CONTROL
1=WALKTEST@@@@@@@YES
2=ZONE@ASSIGNMENT
00@**@**@**@**
Edit Control Screen #3

EDIT@CONTROL
1=NOUN/ADJECTIVE
2=DESCRIPTION
********************
Edit Control Screen #4
EDIT CONTROL
1=ENABLED
2=TYPE
3=SILENCEABLE

Edit Control Screen #2



(QDEOH'LVDEOH0RGXOH
7R(QDEOHRU'LVDEOHWKHFRQWUROPRGXOHSUHVVWKHNH\ZKLOHYLHZLQJWKH(GLW
&RQWURO6FUHHQ(DFKSUHVVRIWKHNH\ZLOOWRJJOHWKHVFUHHQEHWZHHQ(QDEOHG@
@@@@@@@@@@@@@@@Z000
@10*00A@010801@1M001
After completion of the Walktest, press the Esc (Escape) key to exit Walktest Mode and
return to the Walktest Screen. The results of the Walktest can now be viewed by pressing
3 while viewing the Walktest Screen. The following screen will be displayed:

@@WALKTEST@RESULTS

View Result Screen
Use the up and down arrow keys to view all of the walktest results which will be displayed
as illustrated in the preceding screen. Note that the Walktest log is stored in RAM. If all
power (AC and DC) is removed from the FACP, the Walktest log information will be lost.
This information is also overwritten when subsequent walktests are performed.



8QLPRGH31&

0DVWHU3URJUDPPLQJ/HYHO

3URJUDPPLQJ

3.6.9 Option Modules
PROGRAMMING
1=HISTORY
2=WALKTEST
3=OPTION MODULES

Programming Screen #3

Options available for the Unimode 9600 include ADT-ACS Series, Graphic and LCD
annunciators, ADT-UDACT Digital Alarm Communicator/Transmitter (with software
#UDACT02.0 and above), printer connection for acquiring hardcopy printouts of panel
data and PC (Personal Computer) connection for uploading and downloading panel data.
Pressing 3 while viewing Programming Screen #3 will display the following screen:

@@@OPTION@MODULES
1=ANNUNCIATORS/UDACT
2=(NOT@USED)
3=PRINTER/PC@@PR4800
Options Screen
Note that PR4800 in the display indicates that a supervised printer, configured for 4800
baud, has been previously programmed into the system.

3.6.9.1 Annunciators/UDACT
3UHVVLQJZKLOHYLHZLQJWKH2SWLRQV6FUHHQZLOOFDXVHWKHFRQWUROSDQHOWRGLVSOD\WKH
IROORZLQJVFUHHQV

@@@@ANNUNCIATOR
1=TERM@ENABLED@@@YES
2=ACS@ENABLED@@@@YES
3=UDACT@@@@@@@@@@YES
Annunciator Screen #1

@@@@ANNUNCIATOR
1=ACS@INSTALLED

Annunciator Screen #2
$7HUPLQDO0RGHDQQXQFLDWRU
$&60RGHDQQXQFLDWRUDQGUHPRWH8'$&7FDQEH
LQVWDOOHGLQWKH8QLPRGHV\VWHP7RHQDEOHDQ\RIWKHVHGHYLFHVSUHVVWKH
QXPEHUFRUUHVSRQGLQJWRWKHVHOHFWHGGHYLFHVKRZQLQ$QQXQFLDWRU6FUHHQVRWKDW

SYSTEM ALL NORMAL
10:00A 010801

The Unimode 9600 performs the following functions at regular intervals while in Normal
mode:
✓ Monitors AC input voltage and battery voltage
✓ Monitors and reports status of SLC loop(s), option cards and control panel
✓ Polls all devices on the SLC loop(s) and flashes each device LED while checking
for valid replies, alarms, troubles, etc.
✓ Refreshes LCD display and updates time
✓ Scans control panel keypad for key presses
✓ Performs autotest for all SLC devices
✓ Tests memory
✓ Updates and reads all communications busses (EIA-485, EIA-232, etc.)

4.4 Trouble Operation
With no alarms in the system, the detection of a trouble will cause the following:
•

The piezo to pulse 1 second On and 1 second Off

•

The system Trouble LED to flash one second On and one second Off

•

The trouble relay to activate

•

TROUBL with device type, noun/adjective, address and trouble description will
appear on the LCD display

•

The same message, along with the time and date, is sent to the optional printer and
the history buffer.
Note that specific troubles will initiate additional actions; for example, loss of AC power
will turn off the AC Power LED, a ground fault will turn on the Ground LED, etc.

8QLPRGH31&



2SHUDWLQJ,QVWUXFWLRQV

7URXEOH2SHUDWLRQ
Addressable Smoke Detectors, Monitor Modules and Control Modules
For addressable devices connected to the SLC loop, the following is a typical message that
could appear on the LCD display for a device trouble:

TROUBL SMOKE (PHOTO)
 
INVREP
10:00A 010801 1D001
The information displayed in the above example provides the following information:
•

First line in display:
✓ The type of event; in this example TROUBL indicating a device trouble
✓ Device type identifier; in this example, SMOKE (PHOTO) indicates a
Photoelectric smoke detector. Other device type identifiers which can be
displayed include SMOKE (ION) for Ionization Detector, HEAT for Heat
Detector, CONTROL for Control Module and MONITOR for Monitor Module,
PULL STATION for a manual pull box, etc. Refer to "Edit Detector" on page 44,
"Edit Module Screen for Monitor Module" on page 54 and "Edit Module Screen
for Control Modules" on page 63 for information on additional device types.

•

Second line in display:
✓ ; refers to the user programmed adjective descriptor from library list
resident in the control panel or custom entry via PC.
✓ ; refers to the user programmed noun descriptor from library list
resident in the control panel or custom entry via PC.

•

Third line in display: INVREP indicates an invalid reply from the addressable
device. Other possible troubles include:
❒ SHORT - indicating a shorted circuit on an addressable device
❒ OPEN - indicating an open circuit on an addressable device
❒ DIRTY1 - maintenance alert indicating that a detector is near but below the
allowed alarm limit and is in need of maintenance before the performance is
compromised
❒ DIRTY2 - maintenance alert indicating that a detector needs immediate
maintenance since it has been within 80% of its alarm threshold for 24 hours
❒ INVREP - maintenance alert indicating a hardware problem in the detector
❒ TEST F - indicating a detector has failed the automatic test operation which
functionally checks its sensing chamber and electronics
❒ INV ID - indicating that an incorrect device code (Type ID) has been
programmed for an installed device (for example, Photo has been programmed
but an Ion detector has been installed)
❒ SW TBL - indicating a module has failed the testing of its Class A switching
relay

•

Fourth line in display:
✓ Time; the current time in this example is 10:00A which represents 10:00 AM
✓ Date; the current month, day and year in this example is 01 for January, 08 for the
8th day of the month and 01 for the year 2001
✓ Device Address; 1D001 in this example 1 represents SLC Loop1, D represents a
detector and 001 represents device address 001



8QLPRGH31&

$ODUP2SHUDWLRQ

2SHUDWLQJ,QVWUXFWLRQV
Pressing the Acknowledge/Step or Alarm Silence key will cause the pulsing piezo to
silence and the system Trouble LED to change from flashing to on steady. This block
acknowledgment occurs regardless of the number of troubles, alarms and supervisory
events active in the system. When the Acknowledge/Step key is pressed and at least one
new alarm or trouble exists in the system, the ‘acknowledge’ message is sent to the printer
and history file. If the trouble clears, either before or after the Acknowledge/Step key is
pressed, the ‘clear trouble’ message is sent to the printer and history file.
If all troubles clear and there are no supervisory or fire conditions active in the system, the
system returns to normal mode operation and the System All Normal message is shown on
the LCD display and sent to the history and printer files. The auto-restore feature will
restore cleared troubles even if the troubles were never acknowledged. Note that pressing
the Alarm Silence key when only troubles exist in the system will have the same effect as
pressing the Acknowledge/Step key except the Alarm Silenced LED will light.
If multiple trouble conditions exist in the system, they will be automatically scrolled on
the LCD display at a three second rate. If a combination of alarms, troubles and/or
supervisory conditions simultaneously occur in the system, only the alarms are scrolled on
the display.

4.5 Alarm Operation
Alarm operation is similar to trouble operation with the following differences:
•
•
•
•
•
•
•
•
•

The piezo sounder produces a steady output as opposed to a pulsed output
The Fire Alarm LED flashes 1 second On and 1 second Off
The LCD displays Alarm along with the device name, type, address, adjective/noun,
associated zones and time/date
Alarms latch and are not allowed to clear automatically
Alarms activate software zones if so programmed
Timers for Silence Inhibit, Autosilence and Trouble Reminder are started
Alarms activate the general alarm relay and general alarm zone Z00
The trouble relay is not activated
Store event in history buffer

A typical alarm display would be as illustrated below:

ALARM

PULL STATION
 
Z000
10:00A 010801 1M001

Note that the device type, which in this example is PULL STATION, can be any other
programmable alarm type.
The information displayed in the above example provides the following information:
•

First line in display:
✓ The type of event; in this example ALARM indicating an alarm condition
✓ Device type identifier; in this example, PULL STATION indicates a manual pull
box. Other device type identifiers which can be displayed include SMOKE (ION)
for Ionization Detector, HEAT for Heat Detector, CONTROL for Control Module
and MONITOR for Monitor Module, PULL STATION for a manual pull box, etc.
Refer to "Edit Detector" on page 44, "Edit Module Screen for Monitor Module"
on page 54 and "Edit Module Screen for Control Modules" on page 63 for
information on additional device types.

8QLPRGH31&



2SHUDWLQJ,QVWUXFWLRQV

6XSHUYLVRU\2SHUDWLRQ
•

Second line in display:
✓ ; refers to the user programmed adjective descriptor from library list
resident in the control panel or custom entry via PC.
✓ ; refers to the user programmed noun descriptor from library list
resident in the control panel or custom entry via PC.

•

Third line in display: Z000 indicates the zone programmed to this device which, in
this example, is general alarm Zone 000. Note that a single device can be
programmed to five different zones but only the first zone will be displayed.

•

Fourth line in display:
✓ Time; the current time in this example is 10:00A which represents 10:00 AM
✓ Date; the current month, day and year in this example is 01 for January, 08 for the
8th day of the month and 01 for the year 2001
✓ Device Address; 1M001 in this example 1 represents SLC Loop1, M represents a
module and 001 represents device address 001

4.6 Supervisory Operation
Supervisory operation is similar to alarm operation but with the following differences:
•

The piezo sounder pulses ½ second On and ½ second Off

•

The Supervisory LED flashes ½ second On and ½ second Off

•

The LCD displays the status label Active Supervisory along with the device name,
type, address, adjective/noun, associated zones and time/date

•

The supervisory relay is activated

•

The alarm relay is not activated

•

Silenced alarms are not resounded

•

Timers are not started

•

Store event in history buffer

A typical Supervisory event would be displayed as illustrated in the following:

ACTIVE
SUPERVISORY
 
Z000
10:00A 010801 1M001

Note that, like alarms, supervisory signals latch (except when programmed for
supervisory autoresettable) and can be assigned to software zones. Supervisory alarms do
not cause resound as do other alarm conditions. Open circuits in supervisory wiring are
processed by the control panel the same way as other trouble conditions. Refer to "Alarm
Operation" on page 109, for a description of the information displayed on the control
panel LCD.



8QLPRGH31&

3URFHVV0RQLWRU2SHUDWLRQ

2SHUDWLQJ,QVWUXFWLRQV

4.7 Process Monitor Operation
Process Monitor operation will initiate the following events:
•

The piezo sounder pulses ¼ second On and ¼ second Off

•

The LCD displays a process monitor message along with the device name, type,
address, adjective/noun, associated zones and time/date

•

Relays programmed for process monitoring will be activated

•

The alarm relay is not activated

•

Silenced alarms are not resounded

•

Timers are not started

•

Store event in history buffer

Note that, like supervisories, process monitor signals latch (except when programmed for
process monitor autoresettable) and can be assigned to software zones.

4.8 Hazard Condition Operation
Hazard Condition operation will initiate the following events:
•

The piezo sounder turns on steady

•

The LCD displays a hazard message along with the device name, type, address,
adjective/noun, associated zones and time/date

•

Relays programmed for process monitoring will be activated

•

The alarm relay is not activated

•

Silenced alarms are not resounded

•

Timers are not started

•

Store event in history buffer

Hazard conditions do not latch and will therefore clear when the hazard condition is
cleared. They can be assigned to software zones.

4.9 Medical Alert Condition Operation
Medical Alert Condition operation will initiate the following events:
•

The piezo sounder turns on steady

•

The LCD displays a medical alert message along with the device name, type,
address, adjective/noun, associated zones and time/date

•

Relays programmed for medical alert will be activated

•

The alarm relay is not activated

•

Silenced alarms are not resounded

•

Timers are not started

•

Store event in history buffer

Medical alert conditions do not latch and will therefore clear when the medical alert
condition is cleared. They can be assigned to software zones.

4.10 NAC Operation
There are two programmable NACs (Notification Appliance Circuits) resident on the
Unimode 9600 main circuit board. Both NACs may be programmed as silenceable or
nonsilenceable and may also be programmed for steady or coded operation. Coded
operation provides a choice between March Time, Temporal or California coding.

8QLPRGH31&



2SHUDWLQJ,QVWUXFWLRQV

3URJUDPPHG=RQH2SHUDWLRQ

4.11 Programmed Zone Operation
Each addressable detector and monitor module can be assigned to a maximum of five
software alarm zones. A general alarm zone Z00 may be listed for output (control) points,
but it is not necessary to list Z00 for input points, since this is the default zone for all alarm
input devices. Zone Z00 is not activated by supervisory points.
When an input device alarms and is not disabled, it activates all software zones assigned to
it. An output device that is not disabled is turned on when any of the software zones to
which it is programmed become active.

4.12 Disable/Enable Operation
Input points which are disabled do not cause an alarm or any zone activation. Disabled
output points are held in the off state. All disabled points are treated as if they were in
trouble, with the exception being the status label that will be displayed is DISABL.

4.13 Waterflow Circuits Operation
If an alarm exists from a monitor module point that has a waterflow type code and its
mapped NAC control module outputs are programmed for nonsilenceable operation, the
Alarm Silence key will not function.

4.14 Detector Functions
Maintenance Alert
Each addressable detector is monitored by the control panel for its maintenance status. If
a detector is near but below the allowed alarm limit, a ‘maintenance alert’ message will
automatically be displayed, signaling that the detector is in need of servicing.
Automatic Test Operation
An automatic test of an addressable detector is performed each minute, resulting in a
complete SLC loop test in approximately 2 hours and 40 minutes (if the loop has the
maximum number of devices installed). The detector’s sensing chamber and electronics
are functionally tested for normal, safe operation. A trouble message is displayed upon
failure of this test. A System Reset will clear this trouble.
Type Code Supervision
The control panel monitors addressable hardware device codes at slow intervals.
Mismatch of any type code, compared to the system program, will cause a device trouble.
System Alarm Verification
The control panel may be programmed to perform alarm verification to help eliminate the
nuisance of false alarms. Alarm verification applies to smoke detectors only.
Smoke Detector Data
Smoke detector data is monitored by the FACP, eliminating the need to test the sensitivity
of each detector at its location. A printout of each detector’s data can be retrieved from
the FACP using an optional printer. Detector sensing ability can decrease with age and
should be monitored as part of a system’s routine maintenance.

4.15 Time Functions: Real-Time Clock
The Unimode 9600 includes a crystal-based clock that provides time of day, date and day
of week. Time is displayed as 12 or 24 hour time with month/day/year and is stored in
RAM. Daylight savings time change-over is programmable and automatic. If both AC
and battery are lost, the time must be reset.



8QLPRGH31&

6\QFKURQL]HG1$&2SHUDWLRQ

2SHUDWLQJ,QVWUXFWLRQV

4.16 Synchronized NAC Operation
Synchronization is a panel feature that controls the activation of notification appliances in
such a way that all devices will turn on and off at exactly the same time. This is
particularly critical when activating strobes which must be synchronized to avoid random
activation and a potential hazard or confusion. The FACP can be programmed to operate
with a variety of manufacturer’s devices.
Important: When a Notification Appliance Circuit with a mix of audible and visual
devices is programmed for silenceable and the synchronization feature is selected, only
the audible devices will be turned off if the Silence key is pressed. The visual devices
(strobes, etc.) will continue to operate.

4.17 Coded Operation
The two NAC circuits resident on the control panel main circuit board can be programmed
for coded operation. The available pulse rates which can be programmed for coded
operation are as follows:
•
•
•

Continuous:
March Time:
Temporal Code:

•
•

California Code:
Two-Stage

Steady output with no pulsing
Pulses at 120 ppm (pulses per minute)
Pulses at ½ second On, ½ second Off, ½ second On, ½
second Off, ½ second On, 1½ second Off
10 seconds On, 5 seconds Off
Pulses at 20 ppm (pulses per minute) for 5 minutes and
then changes to on steady

4.18 Presignal
Presignal option programs an initiating device to delay the activation of NACs and/or
control modules while allowing visual verification by a person. Once a detector or
monitor module triggers an alarm, the onboard piezo sounds immediately, but the NACs
are not activated for a user programmed time duration of up to three minutes. Note that the
alarm relay and communicator will respond to the initial alarm immediately. In addition,
Zone 98 will activate. This zone can be programmed to a control module which may be
used to activate a sounder or indicator which the installer designates as a Presignal
indication. 'RQRWDVVLJQ=RQHWRD1RWLILFDWLRQ$SSOLDQFH&LUFXLWZKHQXVLQJWKLV
]RQHWRLQGLFDWHD3UHVLJQDOFRQGLWLRQ
After the programmed delay, the NACs will activate if the source of the alarm is not
cleared. Note that if a second alarm occurs during the programmed time delay, the alarm
will be processed immediately, causing activation of the appropriate output zones. The
events which occur upon Presignal activation are as follows:
✓
✓
✓
✓

onboard piezo sounds immediately
control panel LCD display will indicate a presignal event and the active point
control points programmed to Zone 98 will activate
annunciators (if enabled) will sound the local piezo, and pulse the alarm LED and
zone LED
✓ outputs (NACs and control modules) of associated zones will be inhibited from
activating for a user programmed time delay of up to three minutes
✓ second alarm occurring anytime during the time delay will cause immediate
activation of all associated outputs
Presignal does not affect monitor modules programmed as waterflow, supervisory, process
monitoring or remote switches. Presignal operation requires the approval of the local
Authority Having Jurisdiction.

8QLPRGH31&



2SHUDWLQJ,QVWUXFWLRQV

3RVLWLYH$ODUP6HTXHQFH

4.19 Positive Alarm Sequence
PAS (Positive Alarm Sequence) option will program an initiating device to delay panel
activation (including alarm relay and communicator) for a period of 15 seconds. Zone 97,
however, will activate immediately and may be used to connect a signaling device to
indicate PAS activation. 'RQRWDVVLJQ=RQHWRD1RWLILFDWLRQ$SSOLDQFH&LUFXLWZKHQ
XVLQJWKLV]RQHWRLQGLFDWHD3$6FRQGLWLRQ
When a detector or monitor module triggers an alarm, the onboard piezo sounds
immediately, but the NACs are prevented from activating for 15 seconds. This inhibit
time is factory set and cannot be changed. Pressing the Alarm Silence or Acknowledge/
Step key during the 15 second inhibit time will silence the piezo sounder and start a timer
which prevents activation of NACs for an additional time duration which can be user
programmed for up to three minutes. After the programmed delay, the NACs will activate
if the source of the alarm is not cleared. Note that if a second alarm occurs during either
time delay, the alarm will be processed immediately, causing activation of the appropriate
output zones. The events which occur upon PAS activation are as follows:
✓ onboard piezo sounds immediately
✓ control panel LCD display will indicate a presignal event and the active point
✓ control points programmed to Zone 97 will activate
✓ annunciators (if enabled) will sound the local piezo, and pulse the alarm LED and
zone LED
✓ outputs (NACs and control modules) of associated zones will be inhibited from
activating for a factory set duration of 15 seconds
✓ pressing the Alarm Silence or Acknowledge/Step key will start a timer which
inhibits output activation for additional time delay of up to three minutes which
is user programmable
✓ second alarm occurring anytime during either time delay will cause immediate
activation of all associated outputs
PAS does not affect monitor modules programmed as waterflow, supervisory, process
monitoring or remote switches. PAS operation requires the approval of the local Authority
Having Jurisdiction.
Note that the PAS BYPASS monitor type code, when activated, will inhibit the PAS
capability until the PAS BYPASS monitor is deactivated. While PAS is inhibited, signaling
devices will immediately place the control panel into alarm. This feature may be
employed by wiring a normally open device, such as a switch, to a monitor module which
has been programmed for PAS BYPASS.



8QLPRGH31&

6SHFLDO6\VWHP7LPHUV

2SHUDWLQJ,QVWUXFWLRQV

4.20 Special System Timers
4.20.1 Silence Inhibit Timer
This option, if selected, prevents the Alarm Silence key from functioning for 60 seconds
following an alarm. A new alarm during the initial 60 seconds will cause the timer to
restart with a new 60 seconds. Silence Inhibit operation requires the approval of the local
Authority Having Jurisdiction.

4.20.2 Autosilence Timer
If Autosilence is selected, the notification appliances, programmed as silenceable, will
automatically be silenced after a programmable duration of from 5 to 30 minutes.
Pressing the Drill key will restart the timer. Autosilence operation requires the approval
of the local Authority Having Jurisdiction.

4.20.3 Trouble Reminder
If selected, this feature causes a reminding ‘beep’ every 15 seconds during an alarm (after
the Alarm Silence key is pressed) and every two minutes during a trouble condition (after
the Acknowledge/Step or Alarm Silence key is pressed). The ‘beeps’ from the onboard
piezo sounder will occur until the alarm or fault is cleared.
Note that if the trouble is not cleared within 24 hours, the piezo will resound, indicating
that the trouble condition still exists.

4.20.4 Waterflow Retard Timer
If selected, this option will delay the activation of a waterflow type alarm for a
programmable time duration from 1 to 90 seconds. This delay is in addition to any time
delay inherent in the waterflow device. This feature requires the approval of the local
Authority Having Jurisdiction.

8QLPRGH31&



2SHUDWLQJ,QVWUXFWLRQV

:DONWHVW

4.20.5 Alarm Verification (None or Two Minutes)
If alarm verification is selected, an addressable smoke detector's alarm is ignored for a
retard time of 13 seconds and the detector's alarm condition is automatically reset. There
will be no alarm indication at the FACP during the Retard period. A confirmation period
of one minute and 47 seconds follows, during which a subsequent alarm from the same
detector will cause the panel to immediately activate the appropriate outputs and indicate
the alarm condition at the FACP. If a different detector alarms any time during the first
detector's verification period, the panel will immediately activate all appropriate outputs
and indicate the alarm condition at the FACP. If no additional detector alarms occur
within two minutes of the first alarm (13 second retard plus one minute and 47 second
confirmation), the timer resets and the panel is ready to verify any new detector alarms
which may occur.
0 sec.
Detector Alarm Verification
(Retard + Confirmation)

Detector Goes Into Alarm

13 sec.

120 sec.
CONFIRMATION

RETARD

Alarm Ignored

Control Panel Processes Alarm if Same Detector is Still in Alarm

Control Panel Immediately Processes Alarm

Different Detector Alarms
During First Detector's
Verification Period

Note: Alarm Verification is available only for addressable smoke detectors, not
conventional smoke detectors.

4.21 Walktest
Walktest is a feature which allows one person to test the fire alarm system. An audible
walktest will momentarily sound the Notification Appliance Circuits in the building and
store the walktest information in a file at the panel. A silent walktest will not sound the
NACs but will store the walktest information in a file which can be viewed at the panel.
Disabled NAC devices will not activate during walktest.
Alarm/Shorted Condition
When in audible Walktest, the panel responds to each new alarm and activates its
programmed control outputs for four seconds, if those outputs have been programmed for
silenceable activation. It also stores each alarm in the walktest history file which can be
sent to an optional printer. The stored display will be the same as if the device actually
activated except the colon (:) in the time stamp is replaced with an asterisk (*).
Open Condition
Addressable devices as well as both main circuit board NACs are monitored for fault
conditions during Walktest mode. When a new trouble condition occurs, the FACP will
activate all NACs and control modules programmed for Walktest, then shut them off after
eight seconds.
While in Walktest, the trouble relay is activated and the system Trouble LED flashes (as in
all of the Program and status change operations). The alarm relay is not activated.



8QLPRGH31&

5HDG6WDWXV

2SHUDWLQJ,QVWUXFWLRQV

4.22 Read Status
Read Status functions do not require a password. The control panel will continue to
provide fire protection while in Read Status mode. This mode can be entered while the
control panel is in alarm or trouble. If a new alarm or trouble occurs during these
functions, the Read Status is exited to prevent confusion.
Read Status Entry
When the operator presses the control panel Enter key, the LCD will display the
following:

1=READ STATUS
2=PROGRAMMING

Pressing 1, while this screen is being displayed, will cause the control panel to enter the
Read Status mode which allows the user to view and print the programmed features and
status of the control panel.
The following screens will be displayed:

READ STATUS
1=SYSTEM POINT
2=ZONES
3=POWER
Read Status Screen #1

READ STATUS
1=TROUBLE REMINDER
2=TIMERS
3=NAC
Read Status Screen #2

READ STATUS
1=ANNUNCIATORS
2=FUTURE USE
3=FUTURE USE
Read Status Screen #4

READ STATUS
1=FUTURE USE
2=PRINTER/PC
3=PRINT
Read Status Screen #5

READ STATUS
1=RELAYS
2=PROGRAM CHECK
3=HISTORY

READ STATUS
1=TIME-DATE

Read Status Screen #3

Read Status Screen #6

8QLPRGH31&



2SHUDWLQJ,QVWUXFWLRQV

5HDG6WDWXV

4.22.1 System Point
READ STATUS
1=SYSTEM POINT
2=ZONES
3=POWER

Pressing 1 while viewing Read Status Screen #1 will cause the following screen to be
displayed:

Read Status Screen #1

READ SYSTEM POINT
SELECT LOOP
1=LOOP 1
2=LOOP 2
The operator selects the loop containing the device to be read by pressing 1 for Loop 1 or
2 for Loop 2. The following screen will then be displayed:

READ SYSTEM POINT
SELECT TYPE
1=DETECTOR
2=MODULE

The operator now selects the type of device which is to be viewed by pressing 1 for
Detector or 2 for Module. If 1 is pressed, the display will change to the following screen:

READ SYSTEM POINT
ENTER DETECTOR#
***

Entering the three digit detector address will cause the control panel to display the current
status of the selected device. For example, if a detector with address 001 on loop 1 is
entered, a display similar to the following will appear:

NORMAL SMOKE(PHOTO)
NORTH CLASSROOM
Z005
1D001
The information in the preceding display includes:



•

NORMAL - the present status (could also be ALARM, TROUBL, DISABL, etc.)

•

SMOKE (PHOTO) - the device type which is a photoelectric smoke detector (could
also be ION for ionization smoke detector)

•

NORTH CLASSROOM - the Adjective/Noun label for this device

•

Z005 - the first of five possible assigned software zones

•

1D001 - 1 = Loop 1, D = Detector, 001 = Address 001

8QLPRGH31&

5HDG6WDWXV

2SHUDWLQJ,QVWUXFWLRQV
Pressing the down arrow key, while viewing the screen shown above, will allow the
operator to view additional programming information about the selected device, such as:
•

Enable/Disable Status

•

Device Type

•

Alarm Verification On/Off

•

Walktest Yes/No

•

PAS (Positive Alarm Sequence) Yes/No

•

Pre-Signal Yes/No

•

Zone Assignments (five maximum)

•

Adjective/Noun descriptor

4.22.2 Zones
READ STATUS
1=SYSTEM POINT
2=ZONES
3=POWER

Pressing 2 while viewing Read Status Screen #1 will cause the following screens to be
displayed:

Read Status Screen #1

ZONES
1=ZONES INSTALLED
2=ZONES ENABLED
3=ZONES DISABLED
Zones Screen #1

ZONES
1=SPECIAL PURPOSE
2=ZONE TYPE
Zones Screen #2
From the preceding screens, the control panel operator can view:
•

Zones Installed - all software zones programmed into the system (99 maximum)

•

Zones Enabled - all software zones that are enabled

•

Zones Disabled - all software zones that have been disabled

•

Special Purpose - on or off programming for Special Purpose Zones 97 reserved for
PAS, 98 reserved for Pre-signal and 99 reserved for future use

•

Zone Type - the Type assigned to each installed zone (default is Alarm)

8QLPRGH31&



2SHUDWLQJ,QVWUXFWLRQV

5HDG6WDWXV

4.22.3 Power
Pressing 3 while viewing Read Status Screen #1 will cause the following screens to be
displayed:

POWER
BATTERY
24 V RST
24 V NRST

27.21V
25.31
25.31

Zones Screen #1

CHARGER
NAC 1
NAC 2

POWER

28.36V
2.39V
2.39V

Zones Screen #2
A real-time display of the control panel voltages can be used to determine if a problem
exists in the system.
The following table lists the circuit being measured, possible conditions and their
respective voltage ranges:
Circuit

Condition

Voltage Range

Normal Battery (nominal)

27.05 - 28.15 VDC

Low Battery

20.0 - 20.8 VDC

No Battery

0 - 18.36 VDC

24V Resettable

Normal

21.25 - 27.50 VDC

24V Nonresettable

Normal

21.25 - 27.50 VDC

Charger

Normal

27.05 - 28.15 VDC

Normal

1.37 - 1.43 VDC

Open Circuit

2.30 - 2.40 VDC

Short Circuit

0 - 1.0 VDC

Battery

NAC 1 or NAC 2

4.22.4 Trouble Reminder
READ STATUS
1=TROUBLE REMINDER
2=TIMERS
3=NAC

Read Status Screen #2

Pressing 1 while viewing Read Status Screen #2 will display the following screen:

TROUBLE REMINDER
TROUBLE REM
ON

The screen indicates whether the Trouble Reminder feature is On or Off.



8QLPRGH31&

5HDG6WDWXV

2SHUDWLQJ,QVWUXFWLRQV

4.22.5 Timers
Pressing 2 while viewing Read Status Screen #2 will cause the following Timer screens to
be displayed:

TIMERS
PAS DELAY
PRE SIGNAL
WATERFLOW

TIMERS
AC LOSS DELAY

000
000
000

4

These screens will indicate the delay time, in seconds, for each of four possible delay
options.

4.22.6 NAC
Pressing 3 while viewing Read Status Screen #2 will display the following screen:

1=NAC 1
2=NAC 2

NAC

The operator can press 1 to view the programmed options for NAC 1 or 2 to view the
programmed options for NAC 2. The resulting screens will display the following
information:
•

Enable/Disable Status

•

Circuit Type (Bell, Strobe, etc.)

•

Silenceable/Nonsilenceable

•

Auto Silence Enable/Disable and time delay

•

Coding Selection (Temporal, Steady, etc.)

•

Zone Assignments

•

Silence Inhibit Enabled/Disabled

•

Synchronization Type (System Sensor, Wheelock or Gentex)

8QLPRGH31&



2SHUDWLQJ,QVWUXFWLRQV

5HDG6WDWXV

4.22.7 Relays
READ STATUS
1=RELAYS
2=PROGRAM CHECK
3=HISTORY

Pressing 1 while viewing Read Status Screen #3 will display the following screen:

RELAY
1=RELAY 1
2=RELAY 2
3=RELAY 3

Read Status Screen #3

The operator can view the programmed option for each relay by pressing the
corresponding number key.

4.22.8 Program Check
Pressing 2 while viewing Read Status Screen #3 will cause a screen similar to the
following to be displayed:

PROGRAM CHECK
1=NACS NO INPUT
2=ZONES NO INPUT
3=ZONES NO OUTPUT

Pressing 1 while viewing the Program Check screen will display a screen which will
indicate if any input zones have not been programmed to one of the Notification
Appliance Circuits. Use the up and down arrow keys to view both NACs.
Pressing 2 while viewing the Program Check screen will display a screen which will
indicate if any output zones have not been programmed to at least one input zone. Use the
up and down arrow keys to view all zones.
Pressing 3 while viewing the Program Check screen will display a screen which will
indicate if any input zones have not been programmed to at least one output zone. Use the
up and down arrow keys to view all zones.

4.22.9 History
Pressing 3 while viewing Read Status Screen #3 will display the following screen:

HISTORY
1=VIEW ALL
2=VIEW ALARMS
3=VIEW OTHER EVENTS

The operator can view all events which have been stored in the history file, only alarms or
other events, such as troubles or supervisories, by pressing the corresponding number key.



8QLPRGH31&

5HDG6WDWXV

2SHUDWLQJ,QVWUXFWLRQV

4.22.10 Annunciators
READ STATUS
1=ANNUNCIATORS
2=FUTURE USE
3=FUTURE USE

Pressing 1 while viewing Read Status Screen #4 will display the following screens:

ANNUNCIATORS
TERM ENABLED
YES
ACS ENABLED
YES
UDACT ENABLED
NO

Read Status Screen #4

Annunciator Screen #1

ANNUNCIATORS
1=ACS ADDRESS

Annunciator Screen #2
Annunciator Screen #1 indicates if Terminal Mode, ACS Mode and UDACT options are
enabled or disabled. Pressing ‘1’ while viewing Annunciator Screen #2 allows the
operator to view the ACS Mode Annunciator addresses which have been programmed into
the control panel.

4.22.11 Printer/PC
READ STATUS
1=FUTURE USE
2=PRINTER/PC
3=PRINT

Pressing 2 while viewing Read Status Screen #5 will display the following screens:

PRINTER PC
PRINTER PC
PR4800
START BIT
STOP BIT

Read Status Screen #5

PRINTER PC
DATA BITS
PARITY

The display will inform the operator as to whether the control panel is configured for a
printer or a PC. In the example above, PR4800 indicates that the panel is configured for a
printer with a baud rate of 4,800.

8QLPRGH31&



2SHUDWLQJ,QVWUXFWLRQV

5HDG6WDWXV

4.22.12 Print
To print program data or control panel status, press 3 while viewing Read Status Screen
#5. The following screens will be displayed:

PRINT
1=HISTORY
2=WALKTEST LOG
3=DETECTOR DATA
Print Screen #1

PRINT
1=EXIT PRINTING

Print Screen #2

Pressing 1 while viewing Print Screen #1 allows the user to print the History file which
will detail all of the system activities since the file was last cleared from memory.
Pressing 2 while viewing Print Screen #1 allows the user to print the Walktest log which
will detail all of the system activations during walktest since the log was last cleared.
Refer to "Walktest" on page 90 for additional information on the display.
Pressing 3 while viewing Print Screen #1 allows the user to print the data of each
addressable smoke detector connected to the system. A printout, similar to the following
example, will be generated if an optional printer is connected to the FACP.
DEVICE#

DEVICE TYPE

1D001
1D002
1D003
1D004
1D005
1D006
1D007
1D008
1D009

SMOKE (PHOTO)
SMOKE (PHOTO)
SMOKE (PHOTO)
SMOKE (PHOTO)
SMOKE (PHOTO)
SMOKE (PHOTO)
SMOKE (PHOTO)
SMOKE (PHOTO)
SMOKE (PHOTO)

%DRIFT COMP
20
20
21
20
21
20
20
20
20

CHAMBER
1281
1281
1259
1309
1281
1322
1280
1215
1310

TIME/DATE
12:01AM 01-08-2001
12:01AM 01-08-2001
12:01AM 01-08-2001
12:02AM 01-08-2001
12:02AM 01-08-2001
12:02AM 01-08-2001
12:02AM 01-08-2001
12:02AM 01-08-2001
12:02AM 01-08-2001

Chamber Value
The Chamber value should be within the indicated range for the following smoke
detectors:
•

SD350(T), D350P(R) and SD300(T) Addressable Photoelectric Smoke Detectors:
405 - 2100 (obscuration of 1.00%/ft. to 3.66%/ft.)

•

CP350 and CP300 Addressable Ionization Smoke Detectors: 750 - 2100
(obscuration of 0.50%/ft. to 1.44%/ft.)

If the addressable smoke detector’s Chamber reading is not within the acceptable range,
clean the detector and check the Chamber value again. If the reading is still not within the
acceptable range, immediately replace the detector.



8QLPRGH31&

5HDG6WDWXV

2SHUDWLQJ,QVWUXFWLRQV
Drift Compensation
Drift compensation uses software algorithms that identify and compensate for long-term
changes in the data readings from each addressable smoke detector. These long-term
changes in detector data readings are typically caused by dirt and dust accumulation inside
the smoke chamber. Drift compensation performs the following functions:
•

Allows a smoke detector to retain its original ability to detect actual smoke and
resist false alarms, even as dirt and dust accumulate

•

Reduces maintenance requirements by allowing the control panel to automatically
perform the periodic sensitivity measurements required by NFPA Standard 72

The FACP software also provides smoothing filters to remove transient noise signals,
usually caused by electrical interference.
Maintenance Alert
The software determines when the drift compensation for a detector reaches an
unacceptable level that can compromise detector performance. When a detector reaches
an unacceptable level, the control panel indicates a maintenance alert. Table 4.1
summarizes the three levels of maintenance alert:
Maintenance Level

FACP Status Display

Indicates

Low Chamber Value

INVREP

A hardware problem in the detector

Maintenance Alert

DIRTY1

Dust accumulation that is near but below the
allowed limit. DIRTY 1 indicates the need for
maintenance before the performance of the detector
is compromised

Maintenance Urgent

DIRTY2

Dust accumulation above the allowed limit.

Table 4.1 Maintenance Alert Levels
Figure 4.1 illustrates a graphic representation of the maintenance levels:

Maintenance
Urgent

DIRTY
Maintenance
Alert

Acceptable
Range
Low Chamber
Reading

LOW
VALUE

Figure 4.1 Diagram of Maintenance Levels

8QLPRGH31&



2SHUDWLQJ,QVWUXFWLRQV

5HDG6WDWXV

4.22.13 Time-Date
READ STATUS
1=TIME-DATE

The operator can view the daylight savings time and the month and week when daylight
savings time will begin and end. Pressing 1 while viewing Read Status Screen #6 will
display the following screens:

Read Status Screen #6

DAYLIGHT SAVINGS
ENABLED
YES
START MONTH
APR
START WEEK
WEEK-1

DAYLIGHT SAVINGS
END MONTH
OCT
END WEEK
LAST-W



8QLPRGH31&

Overview

Power Supply Calculations

Power Supply Calculations

SECTION 5
5.1 Overview

This section contains instructions and tables for calculating power supply currents in
alarm and standby conditions. This is a four-step process, consisting of the following:
1. Calculating the total amount of AC branch circuit current required to operate the
system
2. Calculating the power supply load current for non-fire and fire alarm conditions and
calculating the secondary (battery) load
3. Calculating the size of batteries required to support the system if an AC power loss
occurs
4. Selecting the proper batteries for your system

5.2 Calculating the AC Branch Circuit
The control panel requires connection to a separate, dedicated AC branch circuit, which
must be labeled FIRE ALARM. This branch circuit must connect to the line side of the
main power feed of the protected premises. No other non-fire alarm equipment may be
powered from the fire alarm branch circuit. The branch circuit wire must run
continuously, without any disconnect devices, from the power source to the control panel.
Overcurrent protection for this circuit must comply with Article 760 of the National
Electrical Codes as well as local codes. Use 14 AWG (2.00 mm2) wire with 600 volt
insulation for this branch circuit.
Use Table 5.1 , to determine the total amount of current, in AC amperes (A), that must be
supplied to the system.
Table 5.1 120 VAC Branch Circuit Requirements
Device Type

Number of
Devices

Unimode 9600
ADT-CHG-120

1

Current Draw
(AC amps)
X

3.2

=

[

]

X

2.0

=

[

]

X

[

]

Sum Column for AC Branch Current Required

Unimode 9600 PN 51336:C

11/06/01

Total Current
per Device
3.2

=
=

127

3RZHU6XSSO\&DOFXODWLRQV

&DOFXODWLQJWKH6\VWHP&XUUHQW'UDZ

5.3 Calculating the System Current Draw
5.3.1 Overview
7KHFRQWUROSDQHOPXVWEHDEOHWRSRZHUDOOLQWHUQDODQGH[WHUQDOGHYLFHVFRQWLQXRXVO\
GXULQJWKHQRQILUHDODUPFRQGLWLRQ7RFDOFXODWHWKHQRQILUHDODUPORDGRQWKHV\VWHP
SRZHUVXSSO\ZKHQSULPDU\SRZHULVDSSOLHGXVH&DOFXODWLRQ&ROXPQLQ7DEOHRQ
SDJH7KHFRQWUROSDQHOPXVWVXSSRUWDODUJHUORDGFXUUHQWGXULQJDILUHDODUPFRQGL
WLRQ7RFDOFXODWHWKHILUHDODUPORDGRQWKHSRZHUVXSSO\XVH&DOFXODWLRQ&ROXPQLQ
7DEOHRQSDJH7KHVHFRQGDU\SRZHUVRXUFHEDWWHULHVPXVWEHDEOHWRSRZHUWKH
V\VWHPGXULQJDSULPDU\SRZHUORVV7RFDOFXODWHWKHQRQILUHDODUPORDGRQWKHVHFRQGDU\
SRZHUVRXUFHXVH&DOFXODWLRQ&ROXPQLQ7DEOHRQSDJH
:KHQFDOFXODWLQJFXUUHQWGUDZDQGWKHEDWWHU\VL]HQRWHWKHIROORZLQJ
‡ µ3ULPDU\¶UHIHUVWRWKHPDLQSRZHUVRXUFHIRUWKHFRQWUROSDQHO
‡ µ6HFRQGDU\¶UHIHUVWRWKHFRQWUROSDQHO¶VEDFNXSEDWWHULHV
‡ $OOFXUUHQWVDUHJLYHQLQDPSHUHV$7DEOHVKRZVKRZWRFRQYHUWPLOOLDP
SHUHVDQGPLFURDPSHUHVWRIXOODPSHUHV
Table 5.2 Converting to Full Amperes
7RFRQYHUW

0XOWLSO\

0LOOLDPSHUHVP$WR
DPSHUHV$

P$[

0LFURDPSHUHV—$WR
DPSHUHV$

—$[

([DPSOH
P$[ $
—$[ $

5.3.2 How to Use Table 5.3 on page 129 to Calculate System
Current Draw
Use Table 5.3 on page 129 to calculate current draws as follows:
1. Enter the quantity of devices in all three columns
2. Enter the current draw where required. Refer to the ADT Device Compatibility
Document for compatible devices and their current draw
3. Calculate the current draws for each in all columns
4. Sum the total current for each column
5. Copy the totals from Column 2 and Column 3 to Table 5.4 on page 130
Following are the types of current that can be entered into Table 5.3 on page 129:
✓ Calculation Column 1 - The primary supply current load that the control panel
must support during a non-fire alarm condition, with AC power applied.
✓ Calculation Column 2 - The primary supply current load that the control panel
must support during a fire alarm condition, with AC power applied.
✓ Calculation Column 3 - The standby current drawn from the batteries in a nonfire alarm condition during a loss of AC power.



8QLPRGH31&

&DOFXODWLQJWKH6\VWHP&XUUHQW'UDZ

3RZHU6XSSO\&DOFXODWLRQV

Table 5.3 contains columns for calculating current draws. For each column, calculate the
current and enter the total (in amperes) in the bottom row. When finished, copy the totals
from Calculation Column 2 and Calculation Column 3 to Table 5.4 on page 130.
Table 5.3 System Current Draw Calculations
'HYLFH7\SH
0DLQ&LUFXLW%RDUG
6/&([SDQGHU0RGXOH
$'7$&05
$'7$&0$7
$'7$&0$
$(0$7
$(0$
$'7$)0$7
$'7$)0$
$'7$)0$
$'78'$&7
$'7/'0
$'7/'0(
$'7/&')
;70)
ZLUH'HWHFWRU+HDGV
3RZHU6XSHUYLVLRQ
5HOD\V
&3
6'
6'7
+
+5
'3
'53
%%+	%%+7
%5%5HOD\%DVH
%%,,VRODWRU%DVH
00)
0')
00)
00)
%*/;
&0)
&5)
,
1$&
1$&
&XUUHQW'UDZIURP7%
QRQDODUP
6XPHDFKFROXPQ
IRUWRWDOV

&DOFXODWLRQ&ROXPQ
3ULPDU\1RQ)LUH$ODUP&XUUHQW
DPSV

&DOFXODWLRQ&ROXPQ
3ULPDU\)LUH$ODUP&XUUHQW
DPSV

4W\

>@
>@

;>FXUUHQWGUDZ@
;>@
;>@
;>@

4W\

>@
>@

;>FXUUHQWGUDZ@
;>@
;>@
;>@

>@

;>@

>@

>@

;>@

>@
>@
>@
PD[
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@

;>@
;>@
;>@
;>@
;>@
;>@
;>@
;>@
;>@
;>@
;>@
;>@
;>@
;>@
;>@
;>@
;>@
;>@

4W\

>@
>@

;>FXUUHQWGUDZ@
;>@
;>@
;>@

;>@

>@

;>@

>@

;>@

>@

;>@

;>@

>@

;>@

>@

;>@

;>@

>@

;>@



>@

;>@

;>@

>@

;>@

>@

;>@

;>@
;>@
;>@
;>@
;>@

>@
>@
>@
>@
>@

;>@
;>@
;>@
;>@
;>@

>@
>@
>@
>@
>@

;>@
;>@
;>@
;>@
;>@

;>@

>@

;>@

>@

;>@

>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@

;>@
;>@
;>@
;>@
;>@
;>@
;>@
;>@
;>@
;>@
;>@
;>@
;>@
;>@
;>@
;>@
;>@
;>@

>@

>@

>@

3ULPDU\1RQ$ODUP

7RWDO


&DOFXODWLRQ&ROXPQ
6HFRQGDU\1RQ)LUH$ODUP&XUUHQW
DPSV

PD[LPXPDODUPGUDZ
IRUDOOGHYLFHV

>@
>@

;>@
;>@

>@

>@

3ULPDU\$ODUP

7RWDO




7RWDO


6HFRQGDU\$ODUP

Table Footnote

1. All eight ADT-ACM-8R relays activated on a single module.
2. All annunciator LEDs on
3. ADT-UDACT actively making phone call to central station. If the normally open contact is used, current
consumption increases to 100 mA.
4. ADT-LDM-32 with LEDs on
5. If using the Reverse Polarity Alarm output, add 0.005 amps; if using the Reverse Polarity Trouble output, add
another 0.005 amps.
6. Refer to the Device Compatibility Document for standby current.
7. Must use compatible listed Power Supervision Relay.
8. Maximum alarm current for each sounder base is 0.015 amps which must be supplied by aux. 24 VDC source.
9. Current limitation of Terminal TB4 circuits is 3.00 amps per NAC.
10.The total standby current must include both the resettable (TB3 Terminals 1 & 2) and nonresettable (TB3
Terminals 3 & 4, 5 & 6) power. Caution must be taken to ensure that current drawn from these outputs during
alarm does not exceed maximum ratings specified. Current limitations of TB3 circuits is 3.0 amps per output
11.Total current draw listed above cannot exceed 7.2 amps.

8QLPRGH31&



3RZHU6XSSO\&DOFXODWLRQV

&DOFXODWLQJWKH%DWWHU\6L]H

5.4 Calculating the Battery Size
Use Table 5.4 to calculate the total Standby and Alarm load in ampere hours (AH). This
total load determines the battery size (in AH), required to support the control panel under
the loss of AC power. Complete Table 5.4 as follows:
1. Enter the totals from Table 5.3 on page 129, Calculation Columns 2 and 3 where
shown
2. Enter the NFPA Standby and Alarm times (refer to ‘NFPA Requirements’ below)
3. Calculate the ampere hours for Standby and Alarm, then sum the Standby and
Alarm ampere hours
4. Multiply the sum by the derating factor of 1.2 to calculate the proper battery size (in
AH)
5. Write the ampere hour requirements on the Protected Premises label located inside
the cabinet door
Table 5.4 Total Secondary Power Requirements at 24 VDC
6HFRQGDU\6WDQGE\/RDG
WRWDOIURP7DEOH&DOFXODWLRQ
&ROXPQ
>@

5HTXLUHG6WDQGE\7LPH
RUKRXUV

3ULPDU\$ODUP/RDG
WRWDOIURP7DEOH&DOFXODWLRQ
&ROXPQ

5HTXLUHG$ODUP7LPH
IRUPLQHQWHU
IRUPLQHQWHU

>@

;>@

;>@

6XPRI6WDQGE\DQG$ODUP$PSHUH+RXUV
0XOWLSO\E\WKH'HUDWLQJ)DFWRU
%DWWHU\6L]H7RWDO$PSHUH+RXUV5HTXLUHG

$+

$+
$+
;
$+

5.4.1 NFPA Battery Requirements
•

NFPA 72 Local and Proprietary Fire Alarm Systems require 24 hours of standby
power followed by 5 minutes in alarm

•

NFPA 72 Central, Auxiliary and Remote Station Fire Alarm Systems require 60
hours of standby followed by 5 minutes in alarm. Batteries installed in a system
powered by a generator need to provide at least 4 hours of standby power

•

NFPA requires 24 hours of standby plus 15 minutes activation for audio systems.
The total ampere hours required cannot exceed 25 AH with an internal charger

5.4.2 Selecting and Locating Batteries
Select batteries that meet or exceed the total ampere hours calculated in Table 5.4 . The
control panel can charge batteries in the 7 AH to 25 AH range. The control panel cabinet
is capable of housing batteries up to 18 AH. Batteries larger than 18 AH require the BB55F or other UL listed external battery cabinet.



8QLPRGH31&

&RUUHODWLRQV

6RIWZDUH=RQHV

6RIWZDUH=RQHV

APPENDIX A
A.1 Correlations

Setup and configuration of an addressable system is different than a conventional system.
In a conventional system, assignment of input devices (smoke detectors, pull stations, heat
detectors, etc.) to zones is accomplished through wiring. The wiring is direct from clearly
marked panel terminals to any device assigned to a particular zone. Connection of output
devices (horns, bells, strobes, etc.) in a conventional system is accomplished by direct
wiring of the output devices to Notification Appliance Circuit terminals.
In an addressable system, a minimum of a single pair of wires (SLC communication loop)
is used to connect all addressable input and output devices. Communications between the
FACP (Fire Alarm Control Panel) and all addressable devices takes place over the wire
pair which originates from the FACP. Software programming is used to configure the
system as opposed to direct wiring. Zone assignments are created via software means,
hence the term software zones.
Setup of an Unimode 9600 software zone is accomplished by panel programming. Each
addressable device can be assigned to a maximum of five software zones. Each software
zone, however, may have from 1 to 99 addressable input devices assigned to it and from 1
to 99 addressable output devices assigned to it.
Monitor and control modules comprise one group of 99 addresses, with each module
having a unique address from 1 to 99. Detectors comprise a separate group of 99
addresses, each detector having a unique address from 1 to 99 in its group. Be careful not
to duplicate addresses within any one group (modules and detectors). Refer to the
following page for an example of zoning.
In the example on the following page:
•

Zone 01 has the following addressable devices assigned to it:
✓ SD350 smoke detectors with addresses 01 and 02
✓ MMF-300 monitor module with address 01
✓ MMF-302 monitor module with address 02 and 03
✓ CMF-300 control modules with addresses 05, 06, 07, 09 and 13

•

Zone 02 has the following addressable devices assigned to it:
✓ MMF-302 monitor module with addresses 02 and 03
✓ CP350 smoke detectors with addresses 03 and 04
✓ CMF-300 control modules with addresses 08, 09 and 10

•

Zone 03 has the following addressable devices assigned to it:
✓ SD350 smoke detectors with addresses 05, 06 and 07
✓ MMF-302 control module with address 04
✓ CMF-300 control modules with addresses 09, 11 and 12

The example points out some of the key assignment features of the Unimode 9600.
Addresses of detectors are not duplicated. Addresses of monitor and control modules are
not duplicated. The control module with address 09 is assigned to three software zones
(providing floor above and floor below). Be careful to properly plan the installation prior
to installing any devices.
CLIP

or Classic Loop Interface Protocol devices (modules and detectors) can only have
unique addresses of 1 to 99. Newer modules can have unique addresses of 1 to 159 which
means each zone can have up to 159 input and output devices assigned to it.

8QLPRGH31&



6RIWZDUH=RQHV

&RUUHODWLRQV
Correlation of Input and Output Zones

Input Devices

Zones

SD350
01

Output Devices
CMF-300
13

SD350
02

CMF-300
05
ZONE
01

MMF-300
01

CMF-300
06

MMF-302
02

CMF-300
07

CMF-300
09

MMF-302
03

CP350
03

ZONE
02

CMF-300
08

CMF-300
10

CP300
04

SD350
05
CMF-300
11

SD350
06

SD350
07

MMF-302
04

ZONE
03

CMF-300
12

The zone correlations which are shown graphically above are also presented in Table A.1
on page 133 and Table A.2 on page 134.



8QLPRGH31&

&RUUHODWLRQV

6RIWZDUH=RQHV

7DEOH$'HWHFWRU3URJUDPPLQJ6KHHW([DPSOH
Address
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50

Device
Type
SD350
SD350
CP350
CP350
SD350
SD350
SD350

8QLPRGH31&

Zone
Number
1
1
2
2
3
3
3

DETECTOR ZONE ASSIGNMENT
ADJ/NOUN
Address
Device
Type
FIRST HALL
51
ELEV. LOBBY
52
2ND FLOOR
53
ROOM 210
54
3RD FLOOR
55
MEZZANINE
56
MECH. ROOM
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100

Zone
Number

ADJ/NOUN



6RIWZDUH=RQHV

&RUUHODWLRQV

7DEOH$0RGXOH3URJUDPPLQJ6KHHW([DPSOH
Address
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50



Device
Type
MMF-300
MMF-302
MMF-302
MMF-302
CMF-300
CMF-300
CMF-300
CMF-300
CMF-300
CMF-300
CMF-300
CMF-300
CMF-300

MONITOR/CONTROL MODULE ZONE ASSIGNMENT
Zone
ADJ/
Address
Device
Zone
Number
NOUN
Type
Number
1
51
1, 2
52
1, 2
53
3
54
1
55
1
56
1
57
2
58
1, 2, 3
59
2
60
3
61
3
62
1
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100

ADJ/NOUN

8QLPRGH31&

&RUUHODWLRQV

6RIWZDUH=RQHV

7DEOH$%ODQN'HWHFWRU3URJUDPPLQJ6KHHWRI
Address

Device
Type

01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50

8QLPRGH31&

Zone
Number

DETECTOR ZONE ASSIGNMENT
ADJ/
Address
Device
NOUN
Type
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100

Zone
Number

ADJ/NOUN



6RIWZDUH=RQHV

&RUUHODWLRQV

7DEOH$%ODQN'HWHFWRU3URJUDPPLQJ6KHHWRI
Address
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150



Device
Type

Zone
Number

DETECTOR ZONE ASSIGNMENT
ADJ/
Address
Device
NOUN
Type
151
152
153
154
155
156
157
158
159

Zone
Number

ADJ/NOUN

8QLPRGH31&

&RUUHODWLRQV

6RIWZDUH=RQHV

7DEOH$%ODQN0RGXOH3URJUDPPLQJ6KHHWRI
Address

Device
Type

01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50

8QLPRGH31&

MONITOR/CONTROL MODULE ZONE ASSIGNMENT
Zone
ADJ/
Address
Device
Zone
Number
NOUN
Type
Number
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100

ADJ/NOUN



6RIWZDUH=RQHV

&RUUHODWLRQV

7DEOH$%ODQN0RGXOH3URJUDPPLQJ6KHHWRI
Address
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150



Device
Type

MONITOR/CONTROL MODULE ZONE ASSIGNMENT
Zone
ADJ/
Address
Device
Zone
Number
NOUN
Type
Number
151
152
153
154
155
156
157
158
159

ADJ/NOUN

8QLPRGH31&

&RUUHODWLRQV

'HIDXOW3URJUDPPLQJ

'HIDXOW3URJUDPPLQJ

APPENDIX B

The following table provides a list of the programming options and their factory default
settings.
Program Option

Factory Default

Program Option

Factory Default

Detector Programming

Not Installed

Daylight Savings

Yes

Detector Type

Smoke-Photo

Month Start Daylight Savings

April

Detector Verification

Off

Week Start Daylight Savings

1st Week

Detector Walktest

Yes

Month End Daylight Savings

October

Detector PAS

No

Week End Daylight

Last Week

Detector Presignal

No

Verification

No

Detector Zone Assign.

000 only

(future)

Detector Adj/Noun

none

PAS Timer

0

Module Programming

Not Installed

Presignal Timer

0

Module Type

Monitor

Waterflow Retard Timer

0

Module Walktest

Yes

NAC 1 & 2 Enable

Enabled

Module PAS

No

NAC 1 & 2 Silenceable

Yes

Module Presignal

No

NAC 1 & 2 Type

Bell

Module Zone Assign.

000 only

NAC 1 & 2 Sync Type

System Sensor

Module Adj/Noun

none

NAC 1 & 2 Autosilence

0

Zone 0 Enable

Enabled

NAC 1 & 2 Coding

Steady

Zone 1 Enable

Enabled

NAC 1 & 2 Zones

Zone 000 only

Zone 2 Enable

Enabled

NAC 1 & 2 Silence Inhibit

0

Zone 3 Enable

Enabled

Relay 1

Alarm

.........................through..........

.....................

Relay 2

Trouble

Zone 96 Enable

Enabled

Relay 3

Supervisory

Zones 97, 98 & 99

Enabled

(future)

No

Annunciator Terminal Mode

No

(future)
Loop 1 & 2 Style

Style 4

Annunciator ACS Mode

Loop 1 & 2 Protocol

CLIP

UDACT

No

Trouble Reminder

Off

ACS Installed

No

Banner

Fire•Lite

Printer-PC

No

Time Format

12 Hr

Printer Baud

9600

Hours Setting

12

Minutes Setting

00

Second Settings

00

AM-PM Setting

AM

Month Setting

01

Day Setting

01

Year Setting

00

8QLPRGH31&



:LUH5HTXLUHPHQWV

&RUUHODWLRQV

:LUH5HTXLUHPHQWV

APPENDIX C

T-tapping of the SLC loop wiring is allowed for 2-wire (Style 4) configurations. The total
resistance of any branch cannot exceed 40 ohms. The total wire length of all branches
cannot exceed 10,000 feet (3,000 m).
Connecting external system accessories to the Unimode 9600 main circuits must be
carefully considered to ensure proper operation. It is important to use the correct type of
wire, wire gauge and wire run length for each Unimode 9600 circuit. Reference the chart
below to specify wire requirements and limitations for each Unimode 9600 circuit.
Note: If the SLC loop is to be run in conduit with Notification Appliance Circuits, the risk
of encountering problems can be greatly reduced by exclusively employing electronic
sounders (such as MA/SS-24D) instead of more electronically noisy notification
appliances such as electromechanical bells or horns.
7DEOH&8QLPRGH:LUH6SHFLILFDWLRQV
CIRCUIT CONNECTIONS

WIRE REQUIREMENTS

Circuit Type

Circuit Function

Wire Type and Limitations

SLC loop
(power-limited)

Connects to
Addressable
Devices

Twisted, shielded pair, 40
ohms maximum per length
of Style 6 and 7 loops. 40
ohms per branch maximum
for Style 4 loops1

ACS/TERM
(EIA-485)
(power-limited)

Connects to
annunciator
modules and
ADT-UDACT
connects to
remote printer
and PC computer
Initiating Device
Circuit

EIA-232
(power-limited)
MMF-300 and
MMF-301
(power-limited)

Wire Gauge and Compatible Brands

Untwisted, unshielded pair
Twisted, shielded pair with a
characteristic impedance of
120 ohms

3,000 (900 m)
6,000 (1,800 m)

12 AWG (3.25 mm): Genesis 4410,
Signal 98230, Belden 9583, WPW999
14 AWG (2.00 mm):Genesis 4408 & 4608
Signal 98430, Belden 9581, WPW995
16 AWG (1.30 mm): Genesis 4406 & 4606
Signal 98630, Belden 9575, WPW991
Direct Burial Cable Isotec NP713110VNQ-S
18 AWG (0.75 mm): Genesis 4402 & 4602
Signal 98300, Belden 9574, WPW975
Direct Burial Cable Isotec NP714110VNQ-S
12-18 AWG (3.25 - 0.75 mm)
18 AWG (0.75 mm)

Twisted, shielded pair

50 (15 m)

18 AWG (0.75 mm) minimum

2,500 (760 m)

12-18 AWG (3.25 - 0.75 mm)

2,500 (760 m)

12-18 AWG (3.25 - 0.75 mm)

Distance limitation
set by 1.2 volt
maximum line
drop
Distance limitation
set by 1.2 volt
maximum line
drop
Distance limitation
set by 1.2 volt
maximum line
drop
20 (6 m)

12-18 AWG (3.25 - 0.75 mm)

MMF-302
(power-limited)

Initiating Device
Circuit

CMF-300
(power-limited)

Notification
Appliance
Circuit

Maximum loop wire
resistance is 40 ohms for the
MMF-300 and 20 ohms for
the MMF-301
No more than a 2.4 volt drop
allowed at end of circuit.
Maximum loop wire
resistance is 25 ohms
In alarm, no more than a 1.2
volt drop allowed at end of
circuit

24 VDC
filtered
resettable
(power-limited)
24 VDC
nonresettable
(power-limited)

Connects to
4-wire smoke
detectors

No more than 1.2 volt drop
allowed from supply source
to end of any branch

Connects to
control modules,
annunciators and
accessories
Remote
secondary power
source

No more than 1.2 volt drop
allowed from supply source
to end of any branch

CHG-120F

Recommended
Max. Distance
Feet (meters)
10,000 (3,000 m)
8,000 (2,400 m)
4,875 (1,450 m)
3,225 (980 m)

12 AWG (3.25 mm) in
conduit

12-18 AWG (3.25 - 0.75 mm)

12-18 AWG (3.25 - 0.75 mm)

12-18 AWG (3.25 - 0.75 mm)

Table Footnote

1. When using untwisted, unshielded wire, full conduit is recommended for optimum EMI/RFI protection.



8QLPRGH31&

Index
Numerics
300 Series addressable devices 20
4XTMF module
coil resistance 31
current 31
installation 31
installation steps 32
see also Transmitter Module
13, 20
voltage 31
A
AC Branch Circuit
calculations 127
AC Loss Delay 81
AC Power 27
current 14
current, maximum 27
voltage 14
wiring 14, 27
Acknowledge/Step 16, 105
ACM-8RF 13
contact rating 35
ACS LED annunciator 13
add Detector 43
add Module 53
address range 19
addressable 12
addressable detectors
see also detectors 13
Addressable Device Accessories 20
addressable modules 19
see also modules 13
addressing
annunciators 37
see also module or detector addressing 19
Adjective
control module 67
monitor module 60
multiple entries 52
Adjective list 50
ADT-ACM-16A Annunciator 22
ADT-ACM-32A Annunciator 22
ADT-ACM-8R 35
mounting to BRKT-9600 36
see also Relay Control Module
35
ADT-ACS LED annunciator 37
ADT-ACS Series
see also annunciator 22
ADT-AFM annunciator 37
ADT-AFM-16A Annunciator 22
ADT-AFM-16AT Annunciator 22
ADT-AFM-32A Annunciator 22
ADT-BG-10LX
see also manual pull station 20
ADT-BG-12LX
Unimode 9600 PN 51336:C

09/19/01

see also manual pull station 19
ADT-CHG-120
see also battery charger 22
see also remote battery charger
14
ADT-LCD-80F annunciator 13, 23
ADT-LDM Series annunciator 23
ADT-UDACT
mounting to BRKT-9600 36
programming 35
see also Digital Alarm Communicator/Transmitter 35
AEM-16AT Annunciator 22
AEM-32A Annunciator 22
Alarm 109
Alarm Silence 16, 105
alarm verification 12, 47, 112, 116
annunciator 22
ACS 13
ADT-ACM-8R 13
ADT-ACS 37
ADT-LCD-80F 13
LDM Graphic 13
annunciator addressing 37
annunciator, graphic
see also ADT- LDM Series 23
annunciator, remote
see also ADT- LCD-80F 23
annunciatorADTAFM 37
Auto Silence
NAC 84
Automatic Test Operation 112
Autoprogramming 13, 39, 87
Autosilence 13, 115
auxiliary DC power 27
Auxiliary Trouble Input 17, 32
B
backbox 18
see also cabinet 26
Banner 75
Banner setting 76
battery 18
cable connection 27
charger 17
charger capacity 14
Charging Circuit 14
see also secondary power 14,
27
battery box 21, 22
battery charger 22
disable 14
external 22
baud rate 92
BB-17F
see also battery box 21
BB-55F

see also battery box 18, 22
BRKT-9600
bracket installation 35, 36
see also Universal Bracket 35
C
C304 Control/Relay Module 20
cabinet 18
dimensions 25, 26
cabinet mounting 24
Calculate System Current Draw 128
Calculating the Battery Size 130
Class A 19, 28
Class B 19, 28
Classic Loop Interface Protocol 19
CLIP Mode
see also Classic Loop Interface
Protocol 19
Clock Format 78
CMF-300 control module 19
Coded Operation 113
Coding
NAC 84
Control Buttons 105
control module 19
description display 69
display 63
edit 63
enable/disable 64
noun 68
noun/adjective 66, 67
silenceable 65
type 65
type codes 65
Correlations 131
CP300 Ionization Detector 20
CP350 18
CRF-300 relay module 19
current
AC Power 27
availability 15
maximum 15
Current Draw Calculations 129
D
D350P 18
D350R 18
data
printout 124
see also smoke detector sensitivity 112
Data Entry
via computer keyboard 38
via keypad 38
Date setting 78
Daylight Savings Time 78
DC power
nonresettable 27
resettable 27
141

Index
see also auxiliary DC power 27
Default Programming 139
Delete Detector 44
Delete Module 54
Description
control module 69
detector label 52
monitor module 62
Detector 13
add 43
adding description 49
delete 44
edit 44
enable/disable 46
screen display 45
type 47
verification 47
Detector Annunciator 19
detector data 124, 125
acceptable range 124
Detector Programming 43
Digital Alarm Communicator/
Transmitter
see also ADT- UDACT 35
dimensions
cabinet 25
DIRTY1 125
DIRTY2 125
Disable 71
Disable Point
Maintenance Level 98
dress panel 18, 21
drift compensation 12
definition 125
Drill 16, 105
E
earth ground 27
edit
control module 63
detector 44
detector screens 45
module, monitor 54
EIA-232 34
for PC/Printer connection 15
see also Printer/PC interface 12
EIA-485
for ACS annunciators 15
for LCD-80F 15
Enable 70
Enable/Disable
control module 64
detector 46
module, monitor 57
End-of-Line Resistor Assembly 20
Enter key 41
Erase History 89
exiting
142

programming 39, 40
Read Status 39, 40
Expander Module 33
see also SLC-2 20
F
FACP
see also Fire Alarm Control
Panel 12
Features 12
Fire Alarm Control Panel
see also FACP 12
Form-C relay 17, 28, 35
G
general alarm zone 59
see also zone Z00 49
ground fault 34
H
H350 18
H350R 18
Hazard Condition 111
History 88
erase 89
Maintenance Level 99
view events 89
History file 12
I
I300
see also Isolator Module 19
Indicators 16
Installation 24
intelligent 12
Inventory 12
INVREP 125
Isolator Module 19
K
Key Panel 16
function keys 16
service/program keys 16
keyboard and keypad 38
Keypad/Display
removal and installation 30
L
lamp test 16
LCD display 12, 16
LDM-32 Graphic Annunciator 13
LED
AC Power 106
Alarm Silenced 106
Battery 106
Disabled 106
Fire Alarm 106
Ground 106
Maintenance 106
see also Indicators 16
Supervisory 106
Trouble 106
LED annunciator 22

Local Energy Municipal Box Service 31
Loop Setup 74
M
M300 Monitor Module 20
M301 Miniature Monitor Module
20
M302 2-wire Monitor Module 20
main circuit, mounting 24
Maintenance Alert 12, 112
maintenance alert 125
levels 125
Maintenance Program Level 2 40,
97
Manual programming 39
Manual Pull Station 19
Master Program Level 1 40, 42
MDF-300 monitor module 19
Medical Alert 111
MMF-300 monitor module 19
MMF-301 monitor module (miniature) 19
MMF-302 monitor module 19
Mode key 41
Module 13
add 53
addressing 19
delete 54
edit monitor 54
enable/disable 57
see also addressable modules
19
Module Programming 53
Monitor module
adjective 60
enable/disable 57
noun 61
noun/adjective 59
type 57
type action 58
Type list 57
type selection 58
monitor module 19
Mounting
cabinet 24
main circuit board 24
municipal box transmitter
see also 4XTMF module 31
N
NAC 14, 17, 81, 111
Auto Silence 84
coded 113
coding 84
current 14
End-of-Line Resistor 14
power 12
see also Notification Appliance
Unimode 9600 PN 51336:C

09/19/01

Index
Circuit 12, 28
silence inhibit 85
silenceable 83
synchronized 113
type codes 83
voltage drop 14
voltage, operating 14
wiring diagram 28
wiring Style 28
NAC enable/disable 82
NAC options 75
NAC type 83
N-ELR Mounting Plate 20
NFPA Battery Requirements 130
nonpower-limited
relay connections 28
Nonresettable Power 17, 27
current 14, 27
Normal 107
normal display 39
Notification Appliance Circuit 14,
81
see also NAC 12, 28
Noun
monitor module 61
multiple entries 52
Noun list 51
Noun/Adjective 49, 51
control module 66
monitor module 59
O
Off-line Programming 39
Operating Instructions 105
Operation
alarm 109
disable/enable 112
hazard condition 111
medical alert 111
NAC 111
normal 107
process monitor 111
programmed zone 112
supervisory 110
trouble 107
waterflow 112
Option Modules 20, 30, 91
annunciators/UDACT 91
Printer/PC 92
Options 12
Output Circuits 17
P
PAS 48, 71, 114
see also Positive Alarm Sequence 12, 47
selection 59
PAS BYPASS 114
PAS timer 79
Unimode 9600 PN 51336:C

09/19/01

Password 13, 40
change 93
Maintenance Level 2 41, 97
password
Master Level 1 41
PC (personal computer)
configuration 34
connection 34
ground fault 34
Piezo
see also sounder 16
PK-9600 Programming Utility 21
Point Program 43
Positive Alarm Sequence 47, 114
see also PAS 12
power
NAC 12
nonresettable 14
resettable smoke 14
system 12
power supply calculations 127
power-limited
relay connections 28
Power-up
first time 40
Pre-signal 12, 48, 71
function 113
selection 59
Pre-signal Delay timer 80
Pre-signal timer 79
primary power
see also AC Power 27
printer
baud rate 92
configuration 34
connection 34
ground fault 34
setup 34
Printer/PC interface 12
Process Monitor 111
Program
check 95
check correlations 95
clear 94
Program Check
Maintenance Level 100
program keys
see also Key Panel 16
Programming 38, 39
autoprogramming 39
exiting 39
factory default 139
Level 1 40
Level 2 40
manual 39
Master Level 1 42
modules 53

off-line computer 39
via computer keyboard 38
via panel keypad 38
Programming Levels 40
Programming Screens 40
Programming Sheet 133, 134, 135,
136, 138
Programming Utility
see also PK-9600 21
PRT/PK-CABLE
for PC/Printer connection 34
R
RA400Z
see also detector annunciator 19
Read Status 39, 117
annunciators 123
exiting 39
history 122
NAC 121
power 120
Print 124
printer/PC 123
program check 122
relay 122
system point 118
Time-Date 126
timers 121
trouble reminder 120
zones 119
Real-Time Clock 112
Recall/Increment Function 52, 62,
69
Relay 14, 17, 28, 86
connections 28
contact rating 14, 17, 28
fixed 28
Form-C 14, 86
programmable 12, 17, 28
programming 86
selections 86
trouble 12, 17, 28
Relay Control Module
see also ADT-ACM-8R 35
relay module 19
Relay options 75
Remote Station Service 31
remote switch functions 13
Reset 16, 105
Resettable Power 17, 27
current 27
see also Smoke Detector Power
14
S
SD300 Photoelectric Detector 20
SD300T Photoelectric Detector 20
SD350 18
SD350T 18
143

Index
Secondary Power Requirements 130
sensitivity 112
see also detector sensitivity 12
Signal rate 13
Signaling Line Circuit 14
Silence Inhibit 13, 85, 115
Silenceable
control module 65
NAC 83
SLC 13, 14, 17
current 14
reference manual 14
resistance 14
see also Signaling Line Circuit
12
Style 17
voltage 14
wiring length 14
SLC Loop Protocol 74
SLC loop selection 43
SLC Style 74
SLC-2 33
installation 33
wiring 33
SLC-2 Expander Module 20
smoke detector
chamber reading 124
data 124
sensitivity 112
Smoke Detector Power
current 14
smoke detector sensitivity 12
Software Zones 12, 131
sounder 16
Specifications 14
strobe synchronization 13
Style 12
Style B 19
Style D 19
Style Y 19, 28
Style Z 19, 28
subscreen 40
Supervisory 110
sync
programming 82
see also synchronization 85
synchronization 113, 121
by manufacturer 85
programming 85
see also strobe synchronization
13
Synchronized Signals 113
System
Maintenance Level 101
System Point 118
system power 12
System Setup 75
144

T
The 35
Time and Date
Maintenance Level 102
Time setting 77
Time-Date setting 75, 77
Timers 75
Transmitter Module 31
see also 4XTMF module 20
Trouble 107
trouble display 108
trouble relay 12
Trouble Reminder 75, 115, 120
trouble responses 108
Type
control module 65
detector 47
monitor module 57
NAC 83
type code
control module 65
supervision 112
type-code
verification 12
U
UL power-limited wiring requirements 29
see also power-limited and nonpower-limited 28
Universal Bracket
see also BRKT-9600 35
V
Verification
detector 47
Verify Loops 88
View Events 89
voltage
measurements 120
ranges 120
W
Walktest 12, 47, 66, 90
audible 90
Maintenance Level 101
operation 116
selection 59
silent 90
Waterflow Delay timer 79, 80
Waterflow Retard Timer 115
Wire Requirements 140
wiring
AC Power 27
earth ground 27
SLC-2 33
wiring control modules
see also Style Y or Style Z 19
wiring modules
see also Style B or Style D 19

wiring Style 12
Z
Z00 49, 59
Z97
PAS zone 48
Z98 48
Zone 97 71
Zone 98 71
Zone Assignment 49, 59
control module 66
Zone assignment 85
Zone Setup 70
Maintenance Level 103
zone type 73
list 73
Zone Z97 48
Zone Z98
pre-signal zone 48
Zones 119, 131
see also software zones 12
Zones Disabled 72
Zones Enabled 72
Zones Installed 72
zones per device 49

Unimode 9600 PN 51336:C

09/19/01

Notes

8QLPRGH31&



Notes



8QLPRGH31&

Notes

8QLPRGH31&





Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : Yes
Encryption                      : Standard V1.2 (40-bit)
User Access                     : Print, Copy, Fill forms, Extract, Assemble, Print high-res
Create Date                     : 2001:11:06 14:34:29Z
Modify Date                     : 2001:12:11 14:07:49-05:00
Page Count                      : 148
Creation Date                   : 2001:11:06 14:34:29Z
Mod Date                        : 2001:12:11 14:07:49-05:00
Producer                        : Acrobat Distiller 5.0 (Windows)
Author                          : PaulG
Metadata Date                   : 2001:12:11 14:07:49-05:00
Creator                         : PaulG
Title                           : adtuni9600_combenglC0.fm
EXIF Metadata provided by EXIF.tools

Navigation menu