Alarm Controls UT 1 Instructions Universal Timer Installation

User Manual: Alarm Controls UT-1 Universal Timer Installation Instructions Installation Instructions

Open the PDF directly: View PDF PDF.
Page Count: 2

DownloadAlarm Controls UT-1 Instructions Universal Timer Installation
Open PDF In BrowserView PDF
INSTALLATION INSTRUCTIONS
MODEL UT-1
UNIVERSAL TIMER
PROGRAMMABLE DIGITAL TIMER FOR ALL TIMING REQUIREMENTS
SIXTEEN ADJUSTABLE TIME RANGES
FOUR MODES OF OPERATION
RANGE FROM ONE SECOND TO ONE HOUR
TEMPERATURE RANGE -25C TO +70C
S.P.D.T. 12 AMP @ 28 VDC
NOISE IMMUNITY ON ALL INPUTS

TIME SELECTION TABLE
RANGE
NUMBER

TIME SELECTOR
SWITCHES
ON = I OFF = O

MINIDIP SWITCH SELECTS RANGE AND MODE
DELAY ON OPERATE
DELAY ON RELEASE
ONE SHOT MODE
PULSING MODE
EXTREME ACCURACY AND REPEATABILITY

SPECIFICATIONS

TIME
RANGE

1 2 3 4

VOLTAGE RANGE: 6 TO 18 VDC
CURRENT CONSUMPTION: 37 MA. MAXIMUM
TIME RANGE: 1 SECOND TO 1 HOUR
TEMPERATURE RANGE: -25C TO +70C
CONTACT RATING: 12 AMP. @ 28 VOLTS DC
MOUNTING: DOUBLE SIDED FOAM TAPE

1

O O O O

1S - 2M

2

I O O O

3M - 5M

3

O I O O

6M - 9M

4

I I O O

10M - 13M

5

O O I O

14M - 17M

6

I O I O

18M - 22M

7

O I

I O

23M - 26M

8

I I

I O

27M - 30M

9

O O O I

31M - 34M

10

I O O I

35M - 38M

11

O I O I

39M - 42M

12

I I O I

43M - 46M

13

O O I

I

47M - 50M

14

I O I

I

51M - 54M

15

O I

I

I

55M - 58M

16

I I

I

I

7. ADJUST THE TIME ADJUSTMENT POT TO THE DESIRED
TIME IF NECESSARY.

59M - 62M

8. REPEAT STEPS 5 AND 6.

MODE SELECTOR
SWITCHES
ON = I OFF = O

MODE

5

6

O

O

PULSING

I

O

DELAY ON OPERATE

O

I

DELAY ON RELEASE

I

I

ONE SHOT

PROCEDURE FOR SETTING DELAY TIME

1. CONVERT THE REQUIRED DELAY TIME TO MINUITES.
2. SELECT RANGE NUMBER IN WHICH DELAY TIME FALLS.
3. POSITION THE TIME SELECTOR SWITCHES TO THE
INDICATED REQUIRED SETTINGS ON THE CHART.
POSITION THE MODE SELECTOR SWITCHES TO THE I I
SETTING.
4. CONNECT THE PROPER INPUT VOLTAGE, 6 TO 18 VDC.
5. START THE TIMER BY APPLYING THE TRIGGER INPUT.
6. THE TIMING LED WILL LIGHT. LED WILL GO OFF WHEN
TIMING HAS BEEN COMPLETED.

9. WHEN THE CORRECT TIME HAS BEEN OBTAINED SET
THE MODE SELECTOR SWITCHES TO THE DESIRED
MODE.

Alarm Controls
ALARM CONTROLS
CORPORATION
19 Brandywine Drive
19 BRANDYWINE DRIVE, DEER PARK, NY 11729
Deer
Park, New York 11729
800 645-5538
(800) 645-5538
www.alarmcontrols.com

UT-1 UNIVERSAL TIMER
MODES OF OPERATION
DELAY ON OPERATE

THE DELAY TIME BEGINS WHEN THE TRIGGER VOLTAGE IS APPLIED. AT THE END OF THE DELAY TIME,
CONTACTS TRANSFER AND REMAIN IN THIS POSITION UNTIL TRIGGER VOLTAGE IS REMOVED.

DELAY ON RELEASE

THE CONTACTS TRANSFER IMMEDIATELY WHEN TRIGGER VOLTAGE IS APPLIED. THE DELAY BEGINS WITH
THE REMOVAL OF THE TRIGGER VOLTAGE. IF THE TRIGGER VOLTAGE IS NOT REMOVED, CONTACTS WILL
NOT TRANSFER.

ONE SHOT

A MOMENTARY OR SUSTAINED APPLICATION OF TRIGGER VOLTAGE WILL CAUSE THE CONTACTS TO
TRANSFER AND REMAIN UNTIL THE END OF THE DELAY PERIOD, AT WHITCH TIME CONTACTS WILL RETRANSFER.TRIGGER VOLTAGE DOES NOT HAVE TO BE REMOVED FOR THE CONTACTS TO RE-TRANSFER.

PULSING

CONTACTS WILL TRANSFER AND RE-TRANSFER WITH EQUAL OPERATE AND RELEASE TIME.

PULSING MODE

+

PWR

+

GND

N/C

ONE SHOT MODE N/O TRIGGER
PWR

VOLTAGE

-

LAMP
OR
SOUNDER

C

TRIG IN

+

+ PWR

N/O

VOLTAGE

-

DELAY ON OPERATE DOOR PROP ALARM

GND

N/O
SW.

N/O
C

TRIG IN

N/C

-

N
E
G

VOLTAGE

- N/C

GND

DOOR
CONTACT

N/O

1K
R
E
S

+

C
BUZZER

N/C

TRIG IN

ONE SHOT MODE N/C TRIGGER

+ PWR

VOLTAGE

-

GND
N/C
SW.

N/O

1K
R
E
S

TRIG IN

C
N/C

ALARM 19CONTROLS
CORPORATION
BRANDYWINE DRIVE, DEER PARK, NY 11729
800 645-5538
631 586-4220
EMAIL: INFO@ALARMCONTROLS.COM WWW.ALARMCONTROLS.COM

- NEG



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.6
Linearized                      : Yes
Author                          : HB
Create Date                     : 2015:08:11 13:29:37-07:00
Modify Date                     : 2015:08:11 13:29:57-07:00
XMP Toolkit                     : Adobe XMP Core 5.2-c001 63.139439, 2010/09/27-13:37:26
Metadata Date                   : 2015:08:11 13:29:57-07:00
Creator Tool                    : Adobe Illustrator CS6 (Windows)
Format                          : application/pdf
Title                           : UT-1 Instructions
Creator                         : HB
Document ID                     : uuid:b09c21c9-a28a-4afa-bea8-8a38a76b71da
Instance ID                     : uuid:c7bc6afe-b630-45c9-8fc2-570f51f9a132
Producer                        : Adobe PDF library 10.01
Page Count                      : 2
EXIF Metadata provided by EXIF.tools

Navigation menu