Installation Guide Smart-UPS X
2000/2200/3000 XL Tower/Rack-Mount 4U
Important Safety Messages
Read the instructions carefully to become familiar with the equipment before trying to install, operate,
service or maintain it. The following special messages may appear throughout this manual or on the
equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a
procedure.
The addition of this symbol to a Caution product safety label indicates that a hazard exists that can result in
injury and product damage if the instructions are not followed.
The following safety messages may appear throughout this manual to warn of potential hazards.
Safety and General Information
Inspect the package contents upon receipt. Notify the carrier and dealer if there is any
damage.
Read the Safety Guide supplied with this unit before installing the UPS.
Adhere to all local and national electrical codes.
This UPS is intended for indoor use only.
Do not operate this UPS in direct sunlight, in contact with fluids, or where there is excessive dust or
humidity.
Be sure the air vents on the UPS are not blocked. Allow adequate space for proper ventilation.
The battery typically lasts for two to five years. Environmental factors impact battery life. Elevated
ambient temperatures, poor quality utility power, and frequent short duration discharges will shorten
battery life.
Connect the UPS power cable directly to a wall outlet. Do not use surge protectors or extension cords.
The batteries are heavy. Remove the batteries prior to installing the UPS in a rack.
Always install external battery packs (XLBPs) at the bottom of the rack. The UPS must be installed
above the XLBPs.
The UPS display interface will recognize as many as 10 external battery packs connected to the UPS.
However there is no limit to the number of XLBPs that can be used with the UPS.
Refer to Specifications in the Operation manual for UPS and battery weight.
CAUTION
CAUTION indicates a potentially hazardous situation which, if not avoided, can result in equipment damage and minor or
moderate injury.
CAUTION
CAUTION indicates a potentially hazardous situation which, if not avoided, can result in equipment damage.
Smart-UPS X 2000/2200/3000 VA XL Tower/Rack-Mount 4U2
Inventory
Inspect the contents upon receipt. Notify the carrier and dealer if the unit is damaged.
Included with all models
1 pair rail cleats
8 pan head screws 1 pair tower stabilizer brackets
Use 8 flat head screws to secure tower stabilizer brackets to the UPS
1 pair rack-mount brackets
Use 8 flat head screws to secure rack-mount brackets to the UPS
Use 4 ornamental screws to secure rack-mount brackets to the rails
Install a cage nut in the rack to secure the top hole of each rack-mount
bracket in a four post rack
(1) Documentation CD
(1) PowerChute software CD
Rack-mount support brackets and hardware Included with models that have factory installed
Network Management Cards
1 pair support
brackets
Two post racks
10 screws Four post racks
6 screws
6 washers
Included with High Voltage (HV) models
Smart-UPS X 2000/2200/3000 VA XL Tower/Rack-Mount 4U 3
Product Overview
Front panel features
Rear panel features
1Online LED
2Power ON/OFF button
3On Battery LED
4Site Wiring Fault LED
5Replace Battery LED
6LCD display screen
7UP/DOWN arrow keys
8ENTER key
9ESC key
1SmartSlot 7Controllable Outlet Group 3
2Chassis ground screw 8External battery pack connector
3UPS utility power input 9EPO connector
4Circuit Breaker reset :Serial port
5Controllable Outlet Group 1 ;USB port
6Controllable Outlet Group 2
2000 VA, 120 Vac Low Voltage 3000 VA, 120 Vac Low Voltage
su0343a
APC b
y
Schneider
Electric
su0756a
GROUP 1GROUP 2
GROUP 3
su0757a
Smart-UPS X 2000/2200/3000 VA XL Tower/Rack-Mount 4U4
Remove Battery
2200/3000 VA, 230 Vac High Voltage 3000 VA, 208 Vac High Voltage
CAUTION
DAMAGE TO EQUIPMENT OR PERSONNEL
The equipment is heavy. Always practice safe lifting techniques adequate for the weight of the equipment.
The UPS + the battery weighs 41 kg (90.4 lb).
The battery weighs 23.8 kg (52.4 lb). Remove the battery before installing the unit in a rack.
Use the battery handle to lift and slide the battery out of the UPS.
Failure to follow these instructions can result in equipment damage and minor or moderate injury
123
GROUP 2
GROUP 3
GROUP 1
su0755a
su0754a
GROUP 1 GROUP 3GROUP 2
su0758a
su0759a
Smart-UPS X 2000/2200/3000 VA XL Tower/Rack-Mount 4U 5
Tower Configuration
12
34
5
su0761a
su0763a
su0764a
su0774a
su0762a
Smart-UPS X 2000/2200/3000 VA XL Tower/Rack-Mount 4U6
Rack-Mount Configuration
Tower to rack-mount conversion
CAUTION
DAMAGE TO EQUIPMENT OR PERSONNEL
The equipment is heavy. Always practice safe lifting techniques adequate for the weight of the equipment.
The UPS + the battery weighs 41 kg (90.4 lb).
The battery weighs 23.8 kg (52.4 lb). Remove the battery before installing the unit in a rack.
Use the battery handle to lift and slide the battery out of the UPS.
Failure to follow these instructions can result in equipment damage and minor or moderate injury
12
34
56
su0764b
su0763b
su0583b
su0761b
su0766a
su0769a
Smart-UPS X 2000/2200/3000 VA XL Tower/Rack-Mount 4U 7
Two post rack installation
CAUTION
DAMAGE TO EQUIPMENT OR PERSONNEL
When installing equipment in a rack, always install external battery packs at the bottom of the rack.
The UPS should always be installed above the external battery packs in rack or stack configurations.
Failure to follow these instructions can result in equipment damage and minor or moderate injury
123
456
su0776a
su0768a
su0
770a
su0771a
su0773a
su0772a
Smart-UPS X 2000/2200/3000 VA XL Tower/Rack-Mount 4U8
Four post rack installation
Use an APC by Schneider Electric four post rail kit. To order the rail kit go to the APC by Schneider Electric
Web site apc.com.
UPS Configuration
Connect Emergency Power Off feature
For instructions on how to connect the Emergency Power Off (EPO) switch, refer to the Operation and
Maintenance manual on the Documentation CD (supplied).
Configure controllable outlet groups
The outlets on the UPS are configured into groups. To utilize the controlled outlet features, use the
Advanced menus on the display interface and navigate to: Main Menu > Control > Outlet1 Control.
123
45
67
su0777a
su0778a
su0779a
su0780a
su0781a
su0782a
Smart-UPS X 2000/2200/3000 VA XL Tower/Rack-Mount 4U 9
Electrical connections
CAUTION
RISK OF EQUIPMENT DAMAGE
Adhere to all local and national electrical codes.
Wiring should be performed by qualified electrician.
Always connect the UPS to a grounded outlet.
Failure to follow these instructions can result in equipment damage
Electronic Device
su0788a
UPS
Electronic Device
© 2013 APC by Schneider Electric. APC, the APC logo, Smart-UPS and PowerChute are owned by
Schneider Electric Industries S.A.S., or their affiliated companies. All other trademarks are property of
their respective owners. EN 990-4651A-002
03/2013
Select models are ENERGY STAR® qualified.
For more information go to www.apc.com/site/recycle/index.cfm/energy-efficiency/energy-star/

Navigation menu