Aprilaire Humidifier 600M Users Manual 10008975A AA 600

600M to the manual 403ad891-df51-4e4b-b505-8771f9244667

2015-02-03

: Aprilaire Aprilaire-Humidifier-600M-Users-Manual-467254 aprilaire-humidifier-600m-users-manual-467254 aprilaire pdf

Open the PDF directly: View PDF PDF.
Page Count: 2

FURNACE
BLOWER MOTOR
MODEL 50
CURRENT SENSING RELAY
(IF REQUIRED)
24 VAC FURNACE ACCESSORY
TERMINALS OR TRANSFORMER
(10VA MINIMUM) SHUT-OFF
(SADDLE VALVE)
WATER SUPPLY
YELLOW 24V
SOLENOID
VALVE WIRES
IMPORTANT
USE 120 VAC POWER SOURCE OTHER THAN FURNACE MOTOR
CIRCUIT. HOWEVER, THE TRANSFORMER CAN BE POWERED
OFF THE HOT 120 VAC LINE BEFORE IT ENTERS THE FURNACE.
DO NOT WIRE TRANSFORMER INTO FURNACE BLOWER CIRCUIT.
IMPORTANT
WHEN MODEL 50 CURRENT
SENSING RELAY IS USED:
WIRE MODEL 50 CURRENT
SENSING RELAY INTO 24 VAC
HUMIDIFIER CONTROL
CIRCUIT ONLY! DO NOT
INSTALL IN TRANSFORMER
PRIMARY CIRCUIT.
CONNECT DRAIN LINE HERE
COMMON
HI
LO
YELLOW WIRES
G
Y
W
C
R
THERMOSTAT
110 VAC
R
C
W
Y
G
FURNACE
OUTDOOR TEMPERATURE
SENSOR FOR
AUTOMATIC MODE
NORTH, EAST
OR WEST SIDE
OF HOME
ABOVE EXPECTED
SNOW LINE
CONTINUOUSLY POWERED
24 VAC TRANSFORMER
PROVIDED WITH HUMIDIFIER
CONNECT TO
HOT WATER SUPPLY
CONNECT DRAIN
LINE HERE
OUTPUTSINPUTSPOWER
G
W
C
RHHODT GfA
ADHC TERMINAL STRIP
B
90-1510
90-1207
Model 600M
MANUAL CONTROL
Model 600
DIGITAL HUMIDIFIER CONTROL
READ COMPLETE SAFETY INSTRUCTIONS AND INSTALLATION TEMPLATE BEFORE STARTING INSTALLATION
This product must be installed by a qualified heating and air conditioning contractor. Failure to do so could result in serious injury from electrical shock.
This product must be installed in compliance with all local, state and federal codes.
Proper humidification and humidity control also requires that the home be constructed in accordance with local codes and good building practices.
ATTENTION INSTALLER:
MODEL 600 SERIES HUMIDIFIER
The Model 600 and 600M Aprilaire can be installed
on either the supply or return plenum of a forced
air handling system and is easily reversible for
installation with right hand or left hand bypass duct
connections. The humidifier dimensions and
serviceability must be considered when selecting
the best location for the humidifier. Here are
2 examples of many types of installations.
RESEARCH PRODUCTS CORPORATION • P.O. BOX 1467 • MADISON, WI 53701-1467 • CALL 800/334-6011 • FAX 608/257-4357
RETURN
SUPPLY
S
RETURN
R
SUPPLY
S
Horizontal
Upflow
90-1079
WARNING
1.ELECTRICAL SHOCK HAZARD.
Disconnect electrical power to the
furnace before starting installation.
Failure to do so could result in
serious injury from electrical shock.
2. SHARP EDGES HAZARD. Sharp
edges may cause serious injury from
cuts. Use care when making plenum
openings and handling ductwork.
3. RISK OF SCALDING. Water
temperature over 125°F can cause
severe burns and scald instantly.
Shut off the hot water supply before
disconnecting or tapping into any
hot water supply line.
SPECIFICATIONS
HUMIDIFIER DIMENSIONS
Width (including solenoid valve): 1538
Height (including drain spud): 15 34
Depth:1014
BYPASS DUCT OPENING
6” diameter
PLENUM OPENING
10”W x 1234”H
WATER FEED RATE
3 gph
ELECTRICAL DATA
24 VAC-60 Hz, 0.5 AMP
CAUTION
1. Do not install humidifier where freezing temperatures
could occur. The water line could freeze and crack
causing water damage to the home.
2. Do not install humidifier or bypass connection on the
furnace jacket.
3. Do not install humidifier or bypass connection on a
plenum face where the blanked off ends of the cooling
coil will restrict air movement through the humidifier.
4. Do not set humidity level above recommended or to
recommended level if condensation exists on inside
windows of any unheated space, as condensation
damage may result. Excess humidity can cause
moisture accumulation which can allow the possibility
for mold growth in the home.
5. Do not connect Model 600 or 600M transformer
to blower motor wiring. Premature component
failure may result.
6. When installing Humidifier Control on
downflow furnace, ensure blower continues to
run after a heat call is satisfied to eliminate
high temperatures from damaging the Control.
7. Do not install humidifier where water pressure
exceeds 125 psi, since damage to the
humidifier may result. Follow codes in effect
concerning pressure reduction.
8. Do not install humidifier on systems with
greater than 0.4 in. wg pressure differential
between supply and return plenums.
RISK OF PROPERTY AND EQUIPMENT DAMAGE.
INSTALLATION
OPTIONS
RECOMMENDED WIRING DIAGRAMS
(SEE STEP 7 ON BACK AND “HUMIDIFIER CONTROL SAFETY AND INSTALLATION INSTRUCTIONS” FOR DETAILED WIRING INSTRUCTIONS)
NOTE
When installing the Aprilaire humidifier with
the Aprilaire Digital Humidifier Control or on a
heat pump system, use hot water. The heated
water supplements the reduced supply air
temperature as added heat for evaporation.
READ COMPLETE SAFETY INSTRUCTIONS AND INSTALLATION TEMPLATE BEFORE STARTING INSTALLATION
TEMPLATE MUST BE LEVEL
– TOP –
READ REVERSE SIDE FIRST! READ REVERSE SIDE FIRST!
IMPORTANT! Be sure owner’s manual containing
instructions for operation and warranty information is given to
owner in order to avoid unnecessary calls. Warranty is void unless
humidifier is installed by qualified heating and air conditioning
contractor due to possible misapplication of product.
NOTE: BEFORE LEAVING THE
JOB SITE, MAKE SURE:
1. Saddle valve is fully open.
2. All plumbing connections are
watertight.
3. Humidifier functions properly.
4. Bypass damper is in proper
position.
Figure 1 Figure 2 Figure 3
10008975 B2205117A 4.10
90-1067 90-1068 90-1069
12
10
2
7
9
6
11
1
4
3
5
8
90-1250
FURNISHED ITEMS
ITEMS NOT FURNISHED
Built-in bypass damper
24 VAC Transformer
Digital Humidifier Control
(Model 600 only)
Manual Humidifier Control
(Model 600M only)
Humidifier Control Installation Instructions
Saddle valve
Humidifier Installation Template
Mounting screws (sheet metal screws)
Water supply line (14” copper)
Drain line (12” I.D. hose)
Low voltage wire
Bypass ductwork
Model 50 Current Sensing Relay (if required)
1. Front Cover
2. Base
3. Feed Tube
4. Water Distribution Tray
5. Water Panel Evaporator
6. Scale Control Insert
7. Integral Damper
8. Damper Handle
9. Drain Spud
10. Hole Plug
11. Nameplate
12. Solenoid Valve
PARTS LIST
1. Press top & bottom tabs
to remove cover (1).
Pull feed tube (3) out of
distribution tray (4). Remove
Water Panel®Evaporator
assembly. See Figure 1.
2. Humidifier is supplied
with bypass duct
connection on left. For right
side bypass, swap location
of drain spud (9) and cap
(10). Twist to remove spud
and cap.
3. Position template on
supply or return plenum.
Make sure template is level.
Allow clearance for drain
line and for servicing. Trace
template outline. Cut 10”
wide x 12-3/4” high opening.
Avoid injury from sharp
edges.
4. Place humidifier base (2) in
opening and secure with 6 screws
in openings provided.
5. Select location for 6” collar
on opposite plenum to minimize
length and number of elbows in
bypass duct. Install 6” bypass
duct components. Attach duct to
humidifier collar using 2 screws
in openings provided.
6. Insert Water Panel Evaporator
assembly into base. Make sure
bottom of scale control insert (6)
is in drain spud. Snap top of
evaporator assembly into base.
Insert feed tube into distribution
tray. See Figure 2. Rotate
nameplate (11) if necessary, so it
is right side up. Place point bypass
damper handle (8) to “WINTER”
(open) for heating season and
“SUMMER” for cooling season.
7. Control installation
and wiring. Disconnect
electrical power to furnace
before wiring control.
In order for humidifier to
operate, furnace must be
on and RH must be below
set-point of control.
Wiring diagrams illustrate
recommended method of
detecting furnace
operation.
MANUAL HUMIDIFIER
CONTROL, MODEL 600M:
Manual Control can be
mounted in return duct or
on wall in living space.
Knob and cover must be
removed to mount control.
See wiring diagram for 24V
control connections.
• For return duct mounting,
position template at least 6”
upstream of bypass duct
connection or humidifier.
Avoid injury from sharp
edges when cutting
opening. Make sure foam
gasket is in place and
secure control to duct using
2 screws in holes provided.
• For wall-mount, select
location that will not be
affected by drafts or heat
sources. Remove and
discard foam gasket and
secure control to wall over
wire access opening using
screws & anchors provided.
DIGITAL HUMIDIFIER
CONTROL, MODEL 600:
• Select location for control
on return duct at least 6”
upstream of bypass duct
connection or humidifier.
Drill 3/4” hole for sensor.
Knob and cover must be
removed to mount control.
Place control on duct with
RH sensor extending into
duct opening. Make sure
gasket is in place around
sensor cage. Secure control
to duct using 2 screws in
openings provided.
See wiring diagrams on
template and control
instructions for 24 V control
connections.
8. Humidifier will function with
cold, hot, softened or unsoftened
water. Hot water (140°F max) is
strongly recommended to provide
maximum evaporative capacity.
Saddle valve provided may be
used to tap into water supply.
See installation instructions on
saddle valve package. Saddle
valve is designed to be fully
opened or closed. Do not use
to regulate flow.
9. Run 1/4” copper tubing from
saddle valve to solenoid valve.
DOUBLE-WRENCH TO PREVENT
LEAKING. See Figure 3.
10. INSTALL DRAIN IN
ACCORDANCE WITH LOCAL
CODES. Run 1/2” I.D. hose
from drain spud to floor drain.
Make sure drain has constant
downward slope and is not
kinked. Do not over-tighten
hose clamp onto drain spud.
Do not use solvent adhesive
on drain spud.
11. Check humidifier
operation. Open saddle valve
and turn control to highest
setting. Turn on furnace. Allow
humidifier to run until water
flows from drain. Make sure
all electrical connections are
secure and all plumbing
connections are water-tight.
Set control to proper setting.

Navigation menu