BECKETT Burner, Furnace Manual L0805069
User Manual: BECKETT BECKETT Burner, Furnace Manual BECKETT Burner, Furnace Owner's Manual, BECKETT Burner, Furnace installation guides
Open the PDF directly: View PDF .
Page Count: 12
Download | |
Open PDF In Browser | View PDF |
iSys T" lVlodel7505 Advanced Burner Control Description / App|ications The Beckett GeniSys TM Advanced Burner Control isa 120 Vac primary safety control for residential and light commercial oil burners used in boiler, furnace, and water heater applications having firing rates less than 20 GPH. The GeniSys is used with a suitable cad cell flame sensor to control the oil burner motor, igniter, and optional solenoid valve. It has 24 Vac thermostat terminals (if applicable) compatible with both mechanical and many power stealing thermostats. It can provide interrupted or intermittent duty ignition, and it has a 30 second lockout time on recycle. Features o o o o Thermostat / Operating (if applicable) and Limit Control Compatible Welded Relay Protection Limited Recycle Limited Reset o 3 Status Lights o Valve-On Delay / Motor-Off Delay (Field programmable with Beckett add-on Display) o 15 Second Lockout Time o o o o Interrupted or Intermittent Duty Ignition Technician Pump Priming Mode Disable Function Cad Cell Resistance Indicator o Communication Ports (2) Specifications Electrical Ratings Inputs: o Voltage: 5Vdc+4% o Current: 25 mA maximum display current Environmental Ratings: o Storage Ambient Temperature: -22°F to +150°F (-35°C to +65°C) o Operating Ambient Temperature: -4°F to +150°F (-20°C to +65°C) o Moisture: 5 to 85% RH, non-condensing and non-crystalizing Table 1 =Models and Cross Reference Guide 7505A 0000 48245, 40200, 15 sec R7184A, R8184G 42230, 502001 7505B 1500 15 sec 15 sec R7184B 7505P 1515 15 sec 15 sec 15 sec R7184P, R7184U I 602001 7505P 1530 15 sec 15 sec 30 sec R7184P, R7184U I 602001 7505P 152M 15 sec 15 sec 2 min R7184P, R7184U I 602001 1 Beckett snap-on alarm module required for direct replacement of this control. 2 Valve-on delay and motor-off delay timings on all models are programmable with Beckett snapon programming display. Other factory set timings are available. Contact Beckett for alternate timings. Page 1 Figure 1 - Getting to know the control Reset Button with Red Light Green Light Communication Port 2 Communication Port 1 Terminals (if applicable) Wiring Connections Optional Snap-on Display Module: For programming and diagnostics Cad Cell Connections Optional Snap=on Alarm Module: For adding isolated tow voltage alarm contacts to the base control. See Alarm Module Instructions for specifications. Page 2 Do Not UseThis Control in an Application that is Not Within the Ratings Listedin This Section. ImproperControlOperationMay Result. Insta|llation/Operation/ ProfessionalService Required Incorrect installation or misuse of this control could result in severe Electrical Ratings inputs: + Voltage: 120 Vac nominal (102 to 132 Vac) + Current: 100 mA nominal (150 mA max at 132 Vac) + Frequency: 60 Hz Outputs: + Motor: 120Vac, 10full load amps (FLA),60 lockedrotor amps (LRA) *Note: Reduce motor FLA rating by igniter current + Igniter: 120 Vac, 3A@0.7 PF min + Solenoid Valve: 120 Vac, 1 A @ 0.7 PF min + Thermostat Anticipator Current: 0.1 A (if applicable) + Thermostat Voltage: 24 Vac (if applicable) Environmental Ratings: + Storage and Operating Ambient Temperature: -40°F to +150°F (-40°0 to +65°0) + Moisture: 5 to 95% RH, non-condensing and non-crystallizing Approvals: + Underwriters Laboratory Recognition per UL372 personal injury, death, or substantial property damage from heavy smoke, explosion or fire. Please read and understand the manual supplied with this control. This control must be installed, adjusted and put into operation only by a qualified individual or service agency that is: ', Licensed or certified to install and provide technical service to oil heating systems. ', Experienced with all applicable codes, standards and ordinances. + Responsible for the correct installation and commission of this equipment. ', Skilled in the adjustment of oil burners using combustion test instruments. The installation must strictly comply with all applicable codes, authorities having jurisdiction and the latest revision of the National Fire Protection Association Standard for the Installation of OilBurning Equipment, NFPA 31 (or CSA-B139 and CSA-B140 in Canada). Regulation by these authorities take precedence over the general instructions provided in this installation manual. and UL1998, and CSA C22.2 No. 199 Frozen Plumbingand Water DamageHazard Do Not Use This Control Above 19.9GPH Most codes and standards require additional safeguards and features for oil burner inputs above 19.9 gph. Consult the appliance manufacturer's instructions for control selection. Page 3 If the residence is unattended in severely cold weather, burner primary control safety lockout, heating system component failures, power outages or other electrical system failures could result in frozen plumbing and water damage in a matter of hours. For protection, take preventive actions such as having a security system installed that operates during power outages, senses low temperature and initiates an effective action. Consult with your heating contractor or a home security agency, Fireor Explosion Hazard Can cause severe property damage. " ', " injury, death, " Mounting: Mount the control on a 4" x 4" junction box on the burner, or inside the appliance cabinet. in replacement applications, mount the new control in the same location as the old or The control can malfunction if it gets wet, leading to accumulation of oil or explosive oil vapors. Never install where water can flood, drip or condense on the control. Never use a control that has been wet - replace it. control. In some replacement applications, it may be necessary to rotate the control on the 4" x 4" box for best fit. o Mounting orientation: any orientation is acceptable. " Wiring: Electrical Shock Hazard _ personal lectrical injury shockor death. can cause ', ', ,, " " " o Make connections to the control's terminals severe Disconnect ALL electrical power to the appliance/burner circuit before installing or servicing this control. Provide ground wiring to the appliance, burner and metal control mounting box. Perform all wiring in compliance with the National Electrical Code ANSl/NFPA 70 (Canada CSA C22.1). as shown in Figures 2 through 9. Refer to the label on the underside of the control for wiring details. Some Thermostats Are Polarity Sensitive. Reversed polarity could cause erratic cycling of the burner control. Explosion,Fire, Scald, and Burn Hazard " All heating appliances must have HIGH LIMIT protection to interrupt electrical power and shutdown the burner if ', operating or safety runaway condition. * o Makesureall appliancewiring complieswith all localcodesand ordinances. controls Connect the wire from the RHor R terminal on the thermostat to the TR terminal on the control (if applicable). Connect the wire from the W terminal on the thermostat to the TW terminal on the control (if applicable). fail and cause a Followthe appliance manufacturer's wiring diagrams and note all required safety controls. Typical safety controls include high temperature or pressure limits, low water cutoffs, pressure relief valves and blocked flue sensing switches. Verify all limit and safety controls are installed and functioning correctly, as specified by the manufacturer, applicable safety standards, codes and all authorities having jurisdiction. Ensure that the appliance is free of oil and oil Typical Boiler Wiring: Figure 2- 7505A (for replacement of R8184G) • Intermittent ignition, no valve-on delay, no motor-off delay LI BOILER CONTROL vapor before starting or resetting the burner. .. ,ooo,,oo, w,,,o,w,,, Result in Improper Control Operation ', " GeniSys wiring label colors may not match the wire colors of the burner or other manufacturers' controls. The GeniSys Control should be wired according to the appliance manufacturer's instructions. TR TW JUMPER TR TW Term!rials Located on opposite side of Contro] (If appl cable} Page4 Figure 3- 7505A(for replacement of R7184A) e Interruptedignition,no valve-onor motor-offdelay BOILER L2 Typical Furnace Wiring: CONTROL Figure 6- 7505A(for replacement of RSf84G) e Intermittentignition,no valve-onor motor-offdelays T IGNITER L2 _ SA ETYAND ERATING IGNITER JUMPER TW TR TW TR I nc_t_rl TR opposite side Contro] CAD CELL (if appl on opposite side Co_t_ol TW lelmmaEs Located on of _ TR TW JUMPER TR(_I applicable) cable) Figure 4 - 7505B (for replacement of R7184B) e Interrupted ignition, valve-on delay only (no motoroff delay) BO&ER of Located on opposite side of TR TW Terminals Control __ CONTROL Figure 7- 7505A(for replacement of R7184A) o Interruptedignition,no valve-onor motor-offdelay L2 LI_ @ L2 _ SA ETYAND RATING THERMOSTAT TR THERMOSTAT TW IGNITER JUMPER OIL TW _ TR CAD CELL TW Terminals Located on opposite side of Contro] _ (If app] -- cable) JUMPER _ TR TW TW Figure 5 - 7505P(for replacement of R7184P) = Interruptedignition,valve-onand motor-offdelays Located __BOILER on TR opposite TW ]el s_de minaEs of Control __ Figure 8 - 7505B (for replacement of R7184B) o Interrupted ignition, valve-on delay only (no motor-off delay) CONTROL @ THERMOSTAT TR TW JUMPER TR CAD CELL _ -- TW ]el mma_s Located on opposite s_de of Control (If applicable) NOTE: To disable motor-off delay on a 7505P control, jumperL1 and limittogetherand wire as shown in Fig.4. Page 5 TR TW lerm_rlals Located on opposite side of Contro_ Figure 9 - 7505P (for replacement of R7184P) • Interrupted ignition,valve-on and motor-off delays 5. End the call for heat. Verify that the burner turns off before leaving the installation site. " Check Safety Features o Safe Start Check 1. Place a jumper across the cad cell terminals. 2. Refer to the steps for "Starting the System" and have the system call for heat. 3. Burner must not start. Verify that the green light is on continuously and that the control remains in Standby mode. 4. End the call for heat and remove the cad cell jumper. TR TW JUMPER OlLV :@ TR TW Tem_inals Located on CAD CELL opposite side of Control Note: Motor-off delay on a 7505P will be disabled if the safety and operating limits as shown in Figures 5 and 9 interrupt power to the control terminal L1. Connect thermostat leads (if applicable) to the TR and TW terminals on the control or jumper the TR and TW terminals on the control as directed by the appliance wiring diagram. Note: If the thermostat short cycles or operates improperly, it may require an isolation relay for proper operation. The Beckett A/C Ready Kit (part no. 51950U) provides this function. Wiring instructions are included with the A/C Ready Kit. Startup 1. Refer to the steps for "Starting the System" and have the system call for heat. 2. After flame is established and the burner igniter turns off, close the hand valve in the oil supply line. 3. At flame loss, the control will enter Recycle mode. Verify that the green light is flashing. The control will remain in Recycle for 60 seconds. 4. After the 60 second recycle period, the control will try to restart the system. 5. After the 15 second lockout time, the control will lock out the burner and the reset button will flash. Verify that the burner motor and igniter are off and that the burner oil solenoid valve (if used) is not energized. / Checkout If the burner or control fails any of the following tests, recheck control wiring. If the burner or control still fails any tests, replace the control. • Starting the System 1. Open the shut-off valves in the supply line from the oil tank. 2. Close the disconnect switch to supply power to the burner. 3. Adjust the thermostat or boiler control to call for heat. • If the pump has not been primed, refer to "Priming the Pump" in the "Operation" section of this manual. 4. o Simulate Flame Failure and Ignition Failure Monitor burner operation to ensure that the burner ignites. Operation Fire Hazard Qualified Technician only. Reset and Service by Page 6 6. o Standby Open the hand valve in the oil line. 7. Click the reset button and verify that the red light in the reset button shuts off and that the burner lights. d / j-I @ f delay 8. End the call for heat. Before leaving the installation, verify that all thermostat and boiler/furnace control wiring is correct. Consult heating appliance manual for directions. " Sequence _.__ e Ignition I carryoverl _(_71oto r off 6= 1. Standby: The burner is idle, waiting for a call for heat. 2= Valve-On Delay: The igniter and motor are on while the control delays turning on the oil solenoid valve for the programmed time. 3= Trial For Ignition: The oil solenoid valve is energized. A flame should be established within the factory set trial for ignition time ("lockout time"). O _' - e a.The trial for ignition (lockout) time expired without flame being established. b.The cad cell detected flame at the end of the Valve On Delay state. Recycle: If the flame is lost while the burner is firing, the control shuts down the burner, enters a 60 second recycle delay, and repeats the ignition sequence. The control will continue to Recycle each time the flame is lost, until it reaches a pre-set time allotment. The control will then go into Hard Lockout instead d recycle. This feature prevents excessive accumulation of oil in the appliance firing chamber. 8= Motor-Off Delay: If applicable, the oil solenoid valve is turned off and the control delays turning the motor off for the set motor-off delay time before the control returns to standby. 9= Pump Prime: The igniter and motor are on with the oil solenoid valve energized for 4 minutes. During Pump Prime mode, the cad cell is disregarded, allowing the technician to prime the pump without having to jumper the cad cell. To reset the control from lockout click the button 1-second. NOTE: A recurrence of the above failure modes or a failed welded relay check could cause the control to enter a Hard Lockout state that must be reset only by a qualified service technician. " Reset Button Operation Table 2 explains what action the control wilt take when the reset button is pressed for different lengths of time during the various burner operating states. To reset from Hard Lockout, hold the reset button for 15 seconds until the yellow light turns on. Ignition Carryover: Once flame is established, the igniter remains on for 10 additional seconds to ensure flame stability. Run: The flame is sustained until the call for heat is satisfied. The burner is then sent to Motor-Off Delay, if applicable, or it is shut down and sent to Standby. 7= 4. Lockout: The control has shut down for one of the following safety reasons: Page 8 rialfor ignition _j prime e of Operation - Burner States 5= €-_- " Priming the Pump 1, Prepare the burner for priming by attaching a clear plastic hose over the bleed port fitting and fully opening the pump bleed port. Use a suitable container to collect purged oil. I • o Table Do not allow oil to spray into a hot combustion chamber while bleeding air from the pump. Install a gauge in the nozzle discharge port tubing or fully open the pump bleed valve to prevent oil spray from accumulating in the combustion chamber during the air bleed procedure. Ensure that all bubbles and froth are purged from the oil supply system before tightening the pump bleed valve. Ensure that the appliance is free of oil and oil vapor before starting or resetting the burner. 2 - Reset Button Initiate a call for heat. 2, Hot Gas Puff=Back and Heavy Smoke Hazard Failure to bleed the pump properly could result in unstable combustion, hot gas puff-back and heavy smoke. 3. After the burner starts, press and hold the reset button for 15 seconds until the yellow light turns on. This indicates that the button has been held long enough. 4. Release the reset button. The yellow light will turn off and the burner will start up again. 5. At burner start up, click the reset button while the igniter is still on. This will transition the control to a dedicated Pump Prime mode, during which the motor, igniter, and valve are powered for four minutes. The yellow light will be on. 6. Bleed the pump until all froth and bubbles are purged. If desired, terminate the call for heat or hold the reset button for at least one second to exit Pump Prime mode and return to Standby. Operation Pushing the reset button will: Button Click (press< t second) Lockout ResetfromSoftL0CK0Ut GotoPumuPrimesee Disablethe Burner: Priming the PumP"above/ Any time the burner is Valve-onDelay,Trial or Ignition,Ignition Carryover Yellowlight flashes _oindicatecaclcel resistance See "CadCe ResistanceIndicator"for table of resistancevalues Run Ogniteris shut off] Motor-OffDelay, Standby No action Pump Prime No action Table Button Hold (press> t second) 3 = Status running,press and hold the resetbutton to disable the burner The burnerwil remainoff as long as the buttonis nela Button Hold (press t5+ seconds) ResetfromRestricted (Hard)Lockout Enables Pump Priming: After the resetbutton has beenheld for 15seconds, the buttoncan thenbe clickedduringthe next ignitionsequenceto enter Pump Prime mode. ExitPump Prime modeand return to Standby Lights o: Light Color Red Restricted(Hard)Lockout SoftLockout Green FlameSensedduringnormaloperation (Couldbe straylight duringstandby) Recycle Yellow Controlis in PumpPrime modeor Resetbuttoncurrentlyheld for 15+ seconds. Cad Cell resistance. See "Cad Cell Resistance Indicator" on page 10 for a table of resistance values. Page 9 At the end of 4 minutes, the yellow light will turn off and the control will automatically return to standby mode. 7. If prime is not established during the four minute pump prime mode, return to step 5 to re-enter Pump Prime mode. Repeat steps 5 through 7 until the pump is fully primed and the oil is free of bubbles. 8. Terminate the call for heat, and the control will resume normal operation. 9. m Resetting From Restricted or Hard Lockout Fire & Smoke Hazard control from restricted lockout state, troubleshoot the heating Before starting or resetting the system for the root cause(s) of the lockout. Make necessary repairs or adjustment to ensure a safe start condition. Ensure that the appliance is free of oil and oil vapors before starting or resetting the burner. m Cad Cell Resistance indicator o During the burner Run state, click the reset button (less than 1 second) to check the cad cell resistance range. The yellow light will flash 1 to 4 times, depending on the amount of light detected by the cad cell. See chart below: Ye,ow Light Flame UeteCti0.Ra.ge Flashes 1 Normal (0 - 400 ohms) 2 Normal (400 - 800 ohms) 3 Normal (800 - 1600 ohms) 4 Limited (1600 ohms Lockout) If the control continues to lock out without a satisfied call for heat, or fails the motor relay check, the control enters Hard (restricted) Lockout in order to limit accumulation of unburned oil in the combustion chamber. o To reset, hold the button down for 15 seconds until the red light turns off and the yellow light turns on. o Always verify the control functions according to all specifications before leaving the installation site. o Replace the control if it does not operate as specified. " Disable Function o Any time the burner is running, press and hold the reset button to disable the burner. The burner will remain off as long as the button is held. Page 10 Maintenance Oil heating systems require annual service performed by a qualified, professional service agency. The 7505 primary control should be inspected during this service routine according to the following checklist: [] NOTE: The 7505 control has no serviceable internal parts. Do not attempt to remove cover. [] Inspect the exterior of the control. Replace the control if there is any sign of impact damage, water or corrosion. [] Use a muttimeter to test the line voltage at control L1 and L2. It should be 102 - 132 Vac. [] Inspect all external wiring for secure connections and verify insulation integrity. [] Verify the control lockout and operation sequence, (Reference Startup/Checkout section). [] Observe a full operating cycle to prove the sequence and timings are correct. [] Replace any control that does not meet listed specifications with an equivalent replacement unit. Page 11 Canada: U.S.A.: RO. Box 1289" Elyria, Ohio 44036 www.beckettcorp.com R.W. Beckett Canada, Ltd. • Unit #3,430 Laird Road. Guelph, Ontario N1G 3X7 Form No. 61649 IR08 Printed in USA4-08
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 12 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 4, 0, 0, 13 Create Date : Thu May 22 04:12:02 2008 Author : Title : Subject :EXIF Metadata provided by EXIF.tools